Protection System
Protection System
Protection System
Prepared by
Er.R.KRISHNAN,B.E
Page 1 / 153
Contents :
1.
2.
15
3.
Overcurrent relays
37
4.
Differential relays
61
5.
69
6.
Distance relays
103
Motor protection
121
8.
Commissioning tests
129
Page 2 / 153
Refrences:
1.
2.
3.
4.
5.
6.
7.
8
9.
Page 3 / 153
or at a frequency of f cycles
4f webers/sec
giving an average induced voltage of
Vav = 4fN
where N is the number of turns
or in r.m.s value the knee point voltage is
V = 4.444fN
as Vrms = 1.11Vav
Also the flux = B A where B is the flux density in tesla, and A is
the core area in m2
So the Knee point voltage V = 4.444BAfN
Page 4 / 153
1
Page2 5 / 153
N1I1 = N2 ( I2 + Ie)
In practice Ie is small compared to I2 and is therefore ignored in
all CT calculations with exception of those concerned with ratio and
phase angle error.
fig 1.1
The magnetizing current depends on the voltage V2 which in
turn depends on the product of the secondary current and the impedance
of the burden plus CT secondary winding resistance.
V2 = I2 ( Rct + Rb + jX b )
Page 6 3/ 153
fig 1.2
The vector diagram of the CT is shown in the fig1.2. The
difference between the I1 and I2 is the ratio error and is the phase
angle error.
The magnetizing current Ie lags V2 by 90
. It can be seen that if the burden was wholly resistance then the ratio
error would be minimum. Whereas if the burden was wholly reactive
then the ratio error would be maximum and the phase angle error
minimum.
fig 1.3
The magnetizing characteristic of a CT is shown in fig1.3.
Since Ie small compared to the secondary current up to the knee-point of
the magnetizing characteristic, the ratio and phase angle error will be
small in this region. This means the primary / secondary current
relationship will be maintained in this region.
i.e. the product I2 ( Rct + Rb + jX b ) is Vk
e.g. R ct = 1, Rb + jX b = 7 + j0 , and Vk
= 150V
then linearity is repeated up to a secondary current of
V2
150
I2 = = = 18.75 A
( Rct + R b + jX b )
1+ 7
If linearity is to maintain up to 20 times CT rating the total impedance
should not exceed
150
Page4 7 / 153
( Rct + R b + jX b ) = = 7.5
20
Page 8 5/ 153
Page6 9 / 153
Assuming no saturation
Vk = 100 ( 2 + 0.32 ) = 232 volts
Vk = 4.44BAf N
232
B =
4.44120
10450
400
= 1.36 tesla
Bmax for cross is 1.48 tesla. So more suitable core material
without saturation is CROSS.
Illustration 2 :
A 100/5 bar primary CT supplies to a 3VA over current relay
set at 10% with a stalloy core. The maximum dimension of the CT
housing on the circuit breaker are 22 cm dia and 19cm deep. It is
required to cater for a current of 10 times the relay setting.
Find 1) Knee-point voltage
2)
Cross sectional area of the core
3)
CT dimension.
Secondary current to operate the relay = 0.5 A
VA
3
Volts to operate the relay = = = 6 volts.
Setting
0.5
Vk, the knee-point voltage = 106 = 60 volts
Vk = 4.44 BAfN
60
A = = 0.0135 m2
4.441.050
20
i.e. 0.0135104 = 135 cm2
So the core dimension may be 11.25cm 12cm.
Illustration 3 :
Three 100/5 bar primary CT with secondary resistance of
0.08 are connected to cater to three phase fault protection set to125%
Page811 / 153
and earth fault relays set to 40%. The relay burden at setting is 3VA for
phase fault relays and 2.4 VA for earth fault relays. What is the
maximum primary current to operate (POC) both phase and earth fault
relays?
3
3
O/C Relay impedance = = = 0.077
(51.25)2
6.252
2.4
2.4
E/F Relay impedance = = = 0.4
(50.4)2
22
Phase fault relay setting :
Total imped ance
= Rct + Rrelay
= 0.08 + 0.077 = 0.157
Volts from CT
= 0.157 6.25 = 0.98 volts.
Assuming the magnetizing current from the magnetizing characteristic
curve at 0.98 volts is 0.25Amps.
Primary current = N( Is + Imag)
= 20 ( 6.25 + 0.25) = 130 Amps.
Earth fault relays setting :
Voltage across the earth fault relay = 2 0.6 = 1.2 Volts
Assuming the magnetizing current from the magnetizing characteristic
curve at 1.28 volts is 0.3Amps.
Now the energized CT must supply exciting current to the other two
CTs.
Current through Rph relay +
exciting current to Yph & B ph = 2 + 0.3 + 0.3 = 2.6Amps.
Volts from CT
= 2.6 ( 0.077 + 0.08 ) + 1.2
= 1.608 volts
Assuming the magnetizing current from the magnetizing characteristic
curve at 1.608 volts is 0.41Amps.
Total secondary current = 0.41 + 2.6 = 3.01Amps.
100
Primary fault current
=
3.01 = 60.2 Amps.
5
fig 1.4
Illustration 4 :
An earthed 132 KV transformer is protected by REF protection
using four CTs and an earth fault relay with stabilizing resistor set at
40%. The system fault level is 3000MVA and loop lead impedance from
CT to relay is 2 ohms. The ratio of the CT is 500/1A and Rct is 0.7
ohms. Find the primary fault setting and the minimum stabilizing
resistor value. Assume relay burden at 1VA.
3500
= = 15.3KA
3 132
15300
CT sec. Current
= = 30.6A
500
Relay voltage setting = 30.6 (0.7 + 2) = 82.6 volts.
Assuming the magnetizing current from the magnetizing characteristic
curve at 82.6 volts is 0.0246Amps.
Primary fault setting
= 500{ (40.0246) + 0.4 }
= 250 Amps.
Stabilizing resister = ( Vk / Is ) - (VA / Is 2 )
82.6
1
=
0.4
0.42
= 250.25
E/F current
Page1013 / 153
Voltage transformers :
The voltage transformer for use with protection schemes has to
fulfill only one condition, which is the secondary output voltage of the
voltage transformer must be an accurate representation of the primary
voltage in both magnitude and phase angle. To meet this requirement
voltage transformers are designed to operate at very low flux densities.
Magnetizing current at low flux densities will be very low, and therefore
the ratio and phase angle errors are also will be small. To achieve this
the core area for a given output is larger than that of power transformer,
which increases the over all s ize of the voltage transformer. In addition a
five limbed construction is used instead of three one in power
transformers in order to reduce the magnetic interference between
phases. The condition of magnetic interference doesnt arise when three
single phase units are used as is common in EHV system, since each
phase unit will have a core with a closed magnetic circuit.
Accuracy :
Ratio error : The error in the secondary voltage due to incorrect ratio is
commonly known as the ratio error and is expressed as a percentage as
follows:
(Kn Vs Vp )
100%
Vp
where Kn is the nominal ratio (rated
primary/secondary
voltage
Vs is the actual secondary terminal voltage
Vp is the actual primary terminal voltage
A small turns compensation is usually be employed in V.T, so that the
error will be positive for low burden and negative for high burden.
Phase angle error : The phase angle error is the phase difference
between the reversed secondary and the primary voltage vector. It is
positive when the reverse secondary voltage leads the primary vector
and negative when it lags the primary vector.
Limits of error and phase difference for different classes of metering and
protective voltage transformers are given in table below:
Table 1
Accuracy
class
0.2
10
0.5
0.5
20
1.0
1.0
40
3.0
3.0
--Limits of error for measuring voltage transformer.
Table 2
Accuracy
class
3P
5P
Voltage factor :
the voltage factor Vf is the upper limit of operating voltage,
expressed in per unit of rated voltage. Earth faults cause a displacement
of system neutral, particularly in the case of unearthed or impedance
earthed systems, resulting rise in voltage on the unearthed phases. These
rise in voltage are important for correct relay operation and ability of the
voltage transformer withstanding under such condition.
Voltage factors with permissible duration for different type of
connection and system earthing are shown in the table below:
Table 3
Page1215 / 153
Voltage
factor Vf
1.2
Ratin
g
contin
uous
1.2
contin
uous
30s
contin
uous
1.5
1.2
fig 1.5
that phase, then the difference between the normal voltage and that
voltage is delivered to the relay.
Page1417 / 153
Page 19 / 153
Page 20 / 153
2
(KVbase)2
Z ba = ohm
2.1
MVAbase
The per-unit value of any impedance in a system is the ratio of the
actual impedance to base impedance. So,
Z ohm
Z p =
2.2
Z base
substituting eqn. 2.1 in eqn 2.2
MVA base
Z pu= Z ohm
2.3
(KVbase )2
Having chosen the base quantities of suitable magnitude, all
system impedance may be converted to the base quantities by the
equation given below:
New base MVA
Z pu( New baseMVA) = Z pu(Given base MVA)
2.4
Given base MVA
The fault MVA of the system is
Fault MVA
= 3 KV KA(f ault)
= 3 (KV/3) KA(f ault)
KV
KV
= 3
3
3 Z F.(ohm)
(KV) 2
=
2.5
Z F.(ohm)
Substituting the value of fault impedance in ohms in terms of base
quantities and per-unit values
(KV)2 MVAbase
Fault MVA =
Z F.pu (KV)2
MVA base
=
Z F.pu
The source impedance is merely a value which represents the
impedance between the system under consideration and the source. This
is determined from the fault level at the incoming bus bar.
MVAbase
The source impedance Zs =
2.6
MVAfault
Page 21 / 153
3
Page 22 / 153
4
fig 2.1
The impedance of any of these branches can be determined by
considering the short circuit impedance between pairs of windings with
the third winding open.
Thus
Zps = Zp + Zs
Zts = Zt + Zs
Page 23 / 153
5
Zpt = Zp + Zt
from which
Illustration 1:
Fig 2.2 shows a power system with all
components.
power system
Page 24 / 153
6
10
Z L 3-4 = 0.008
(3.3)2
= 0.00735 p.u
VR MVA base
Z pu =
IR (KVrated)2
43.7
10
=
= 0.05p.u
800 (3.3)2
The per-unit values to common base are shown in fig 2.3 below.
10
= 100MVA
0.1
10
Fault MVA for a fault at bus-2 =
= 96MVA
0.1+ 0.0042
10
Fault MVA for a fault at bus-3 =
= 42MVA
0.1 + 0.0042 + 0.1333
Fault MVA for a fault at bus-1 =
10
Fault MVA for a fault at bus-4 =
0.1+ 0.0042+ 0.1333+0.00735
= 40.84 MVA
10
Fault MVA for a fault at bus-5 =
0.1+ 0.0042+0.1333+0.00735+0.05
= 33.9MVA
Page 25 / 153
7
33.9
= 5.93 KA.
3 3.3
33.9
Fault current at 11KV interconnector = =1.78KA.
3 11
fig 2.4
Illustration 2:
fig 2.5
Page 26 / 153
8
10
0.032 = 0.002644p.u
112
6
10
XT = = 0.3p.u
10
2
The interconnecting cable to the 415volt bus is of six single core.
i.e. 2 1000mm2
Assume the reactance /phase of 415volt cable = 100/ m.
The reactance of 415volt cable
= 0.5 30 100 10-6
= 0.0015
10
Zl =
0.0015
= 0.0871p.u
(0.415)2
ZL =
fig 2.6
fig 2.7
Page 27 / 153
9
Illustration 3:
A 110KV sub-station A with a three phase fault level of 1158
MVA feeds radially to another 110KV sub-station B, 30KM away from
sub-station A. Two 110KV / 33KV, 10MVA transformers are connected
between 110KV and 33KV bus. Calculate the fault level at 33KV bus
and 110KV bus at sub-station B. The conductor used for 110KV
transmission line is panther conductor.
Page 28 / 153
10
fig 2.8
Assume base MVA = 100 MVA.
Base MVA
Source impedance of the grid SS Z s =
Fault MVA
100
=
= 0.018635p.u
1158
R&X values of panther conductor:
R = 0.1547/KM,
jX = 0.3975/KM
Ignore resistive value which will make little error in overall calculation.
X = 0.3975 30 = 11.925
MVAbase
Xp.u = Xohm
(KVbase)2
100
= 11.925
= 0.09855p.u
1102
Z%
MVAbase
Z Tp.u =
100
MVArating
10
100
= = 1p.u
100
10
Page 29 / 153
11
The impedance diagram is drawn as shown fig 2.9 and the simplif ied
diagram is shown in fig 2.10.
MVA base
Fault MVA at sub-station B 110KV bus =
Zf
100
= = 540MVA
0.8635 + 0.09855
Fault MVA at sub-station B 33Kvbus
100
=
0.8635 + 0.09855 + 0.5
= 146MVA
Illustration 4:
Page 30 / 153
12
fig 2.11
The part of a power system shown in fig 2.11 is a power station
with two incoming supplies and an inter bus-bar reactor which is
switched in when the generators are in operation to keep the fault level
to 260MVA which is the rupturing capacity of the switchgear.
Assume a common base of 10MVA.
24
10
Z G = = 0.32p.u
100
(6/0.8)
10.5
10
Z T = = 0.32p.u
100
15
MVAbase
10
Z S = = = 0.004p.u
MVAfault
2500
VR
MVA base
Z R =
IR
(KV)2
436
10
= = 0.045p.u
800
112
The impedance diagram with the per-unit impedance drawn to a
common base as shown in fig 2.12.
Page 31 / 153
13
fig 2.12
there is no simple series or parallel combination which can be
eliminated and so delta-star conversion must be made to 0.07, 0.07, and
0.045 impedances.
The equation for conversion is
Z 1Z 2
Z a =
Z1 + Z 2 + Z3
Z 2Z 3
Z b =
Z1 + Z 2 + Z3
Z 3Z 1
Z c =
Z1 + Z 2 + Z3
0.07 0.07
Z a =
= 0.0265
0.07 + 0.07 + 0.045
0.045 0.07
= 0.017
0.7 + 0.07 + 0.045
The modified imped ance diagram and the impedance diagrams for
different stages of reduction are shown in fig 2.13(a) to fig 2.13(f).
Zb = Zc
Page 32 / 153
14
fig 2.13
Page 33 / 153
15
10
The fault level for a for a fault at bus-3 is = = 253.47MVA
0.03945
The various stages of determining the current distribution are elaborated
in fig 2.14 (a) to fig 2.14(f) and fig 2.14(g) shows the fin al current
distribution for a fault in bus-3.
Page 34 / 153
16
fig 2.14
Illustration 5:
Application of bus impedance matrix in fault calculation.
Page 35 / 153
17
fig 2.15
1) Assume a common base of 200MVA.
2) Convert all the impedances to a common base.
18.2
200
Z G = = 0.164p.u
100
222
14
200
Z T1 = = 0.1333p.u
100
210
15
200
Z T2 =
100
120
200
Z L = 24.8
2752
= 0.25p.u
= 0.0656p.u
Page 36 / 153
18
fig 2.16
4) Draw the admittance diagram.
fig 2.17
Page 37 / 153
19
Page 38 / 153
20
fig 2.18
From the same short circuit matrix i.e. Z-bus, similar information can be
found for faults on any of the other buses.
Illustration 6:
The three phase rating of a three winding transformers are:
Primary
Y - connected 66KV, 30MVA
secondary Y - connected 13.2KV, 20MVA
Tertiary
- connected 2.3KV, 10MVA
Page 39 / 153
21
fig 2.19
Page 40 / 153
22
operating time
1
t = x K
0.339- 0.236/ I
0.14
t = x K
I0.02 - 1
13.5
t = x K
I-1
80
t = x K
2
I -1
120
t = x K
I-1
Logarithmic inverse
t = 5.8 - 1.35 log n (I / I n )
where t = relay operating time
K = scale constant or TMS according to curve
I = multiple of set current Is or PSM
Page 41 / 153
fig 3.1
Page 42 / 153
2
fig 3.2
Calculate the maximum and minimum load currents bus. Provide
current transformers of ratio as per system load requirements. Set the
relay with an equivalent primary current well above the maximum load
current. The relay setting must be well below the minimum fault current.
Complete the datas in a table as given below:
Table 3.1
loc
Total
ati
impedance
on
in ohms
Max
Min
A
B
C
D
0.81
1.41
2.36
4.56
1.62
2.22
3.17
5.37
Fault
current in
Amps
Max
Min
7840
4504
2694
1393
Total
load
current
3920
2860
2003
1183
500
350
175
75
CT.
Ratio
400/5
400/5
200/5
100/3
Relay
current
setting
per prima
cen
ry
t
curre
nt
150
600
125
500
100
200
100
100
Page 43 / 153
3
Page 44 / 153
4
Relay at D Fault at D
Relay at C Fault at D
Relay at C Fault at C
Relay at B Fault at C
Relay at B Fault at B
Relay at A Fault at B
Relay at A Fault at A
PSM
13.93
6.965
13.45
5.382
9
7.5
13.06
Tc
2.6
3.6
2.6
4.1
3.15
3.45
2.65
Relay setting
TMS
Ta
0.05
0.13
0.175
0.13 + 0.5 = 0.63
0.175
0.455
0.233
0.455 + 0.5 = 0.955
0.233
0.734
0.358
0.734 + 0.5 = 1.234
0.358
0.95
Tc :- Relay operating time from standard curve for the given PSM
Ta :- relay actual operating time
The grading of the remaining relays are proceeded in similar
way as illustrated above and tabulated.
Finally the discriminating curves of relay at substation A,B,C
and D are plotted on log-log sheet (fig). This can be done using a
template of relay operating characteristic at TMS of 1.0. From the plot it
can be seen that a grading margin of 0.5 sec has been achieved.
P rocedure for plotting discriminating curve :For this purpose it is necessary to prepare a transparent
template of the time current curve of the relay on a log - log paper
corresponding to TSM = 1. The template is so made that the origin of
the log - log paper corresponds to 1 - second of the curve along the Y axis and 100% plug setting for 1 - multiple P.S along the X - axis as in
fig 3.2(a).
Page 45 / 153
5
fig 3.2(a)
After having made the template the values of the current (in
amps) are plotted on a log -log paper along the X - axis and the time of
operating of the relay ( in seconds) along the Y - axis.
For plotting the characteristic of the relay - D in the above
illustration, the origin of the template is kept at 100 amps and 0.05 secs
and the curve of the template is transferred on the log - log paper.
Similarly for plotting the characteristic of the relay - C the orgin of the
template should be kept at 200 amps and 0.175 secs and the transfered to
the log - log paper. Repeat the procedure for B and A relays with the
origin of the of template kept at ( 500A, 0.233 s ) and ( 600A, 0.358 s )
respectively.
and current :Discrimination of over current relay
relays by both time
timeand
Relay co-ordination in the case of discrimination by time alone
has the disadvantage of, more severe faults are cleared in the longest
operating time. Discrimination by current can be applied only when
there is appreciable impedance between two circuit breakers. With the
use of inverse characteristic the time of operation is inversely
proportional to the fault current and the actual characteristic is a
function of time and current setting.
Illustration 2 :-
fig 3
It is necessary to convert all the system imped ance to a
common base.
Common base used
:10 MVA
Page 46 / 153
6
MVA base
=Z% x
MVArated
10
= 7 x = 17.5%
4
Percentage impedance of cable between
MVAbase
D &E to a common base of 10 MVA :
= Z ohm 100
( KV )2
10
= 0.04 x x 100 = 0.33%
112
Percentage impedance of cable between
10
C&D to a common base of 10 MVA : = 0.24 x x 100 =1.98%
112
percentage imped ance of 30 MVA
10
transformer :
= 22.5 x
=7.5%
30
10
Percentage impedance of 132KV line
= 6.2 x x100 = 0.36%
1322
Percentage impedance of 132KV source
Table 1
Page 47 / 153
7
Base MVA
= x 100
Fault MVA
10
= x 100
=0.29%
3500
R
el
ay
lo
ca
ti
on
D
C
B
A
Total impedance in
Z pu
Fault current in
Amps at 3.3KV base
Min
Max
Max
Min
0.1013
0.0815
0.0065
0.0029
0.2795
0.1013
0.0815
0.0065
17268
21466
269160
603292
6257
17268
21466
269160
Total
load
current
at
3.3KV
base
CT.
Ratio
CT. Ratio
to the
base of
33kv
Relay current
setting
perc
ent
700
1500
6000
20000
250/5
500/5
150/1
500/1
833/5
1666.6/5
6000/1
20000/1
100
100
100
100
Table 2
Relay at D Fault at D
Relay at C Fault at D
Relay at C Fault at C
Relay at B Fault at C
Relay at B fault at B
Relay at A Fault at B
Relay at A Fault at A
PSM
20.7
10.36
12.88
3.58
44.8
13.458
30.1
Tc
0.2
0.8
0.47
6
0.2
0.43
0.2
TMS
0.05
0.625
0.625
0.115
0.115
1
1
TC
0.1
0.1 + 0.4 = 0.5
0.29
0.29 + 0.4 = 0.69
0.023
0.023 + 0.4 =0.423
0.2
Page 48 / 153
8
primary
current
at 3.3kv
base
833
1666.6
6000
20000
4MVA
= 0.7KA
3 x3.3KV
CT ratio adopted
250/5A
corresponding CT ratio to the base of 3.3KV = 250 x (11/3.3) / 5
=833.3/5A
So a relay of 100% P.S (plug setting) corresponds to a current
of 833.3Amps(3.3KV base).
The calculations for the remaining relay locations are
proceeded in similar way as illustrated above and tabulated
Calculations were made for all the relay locations for the TMS
(time lever setting) in the same way as explained in the previous
example and tabulated in Table 2
Page 49 / 153
9
The discriminating curves were plotted for all the relays at sub
stations A, B, C, D &E on a log-log sheet (fig).
ILLUSTRAT ION 3
Coordination of over current relays for an industrial system :-
fig 3.4
The relays used for protection are :
i) for motor protection (relay G) a thermal relay with high set unit for
instantaneous over current element
ii) for transformer protection (relay H) over current relay with very
inverse characteristic and high over current element
iii) for feeder protection (relay J) a normal inverse characteristic
iv) for generator a voltage controlled normal inverse characteristic
with dual characteristic
For convenience a common voltage base of 6.6KV chosen and
scheme for relay co-ordination redrawn with this base.
Page 50 / 153
10
fig 3.5
Fuse characteristic :- The operating characteristic of the fuse should be
plotted on a log-log sheet with a suitable scale for maximum fault levels
on a common base voltage of 6.6KV.
Table 1
Operating current at
Operating Time
415V Base
6.6KV Base
795
50
40
955
60
13
1160
70
6
1270
80
3
1590
100
0.9
2700
170
0.1
Induction motor :Rating of the motor
Full load current
=100KW.
=139 Amps at 415V base
ie
=8.75 Amps at 6.6KV base
Motor starting current ( 6 times full load current) =6 x 139 = 834 Amps
ie 52.48 Amps at 6.6KV base
Starting time
= 10 secs
The relay may be set for 100% setting corresponding to 9.43Amps at
6.6KV base ie. 13% overload.
The thermal characteristic of the relay is
Table 2
Page 51 / 153
11
multiples of current
1.25
1.5
2
3
4
5
6
operating
415v
base
187.5
225
300
450
600
750
900
current
6.6KV
base
11.79
14.15
18.85
28.3
37.5
47.2
56.6
operating time
Hot
Cold
1400
700
300
105
55
33
23
550
240
100
35
18
11
7.5
Page 52 / 153
12
Feeder protection:
Relay used
= normal inverse characteristic.
CT Ratio
= 200 / 5
The current setting on this relay should be based on the
maximum load of the 6.6 KV bus, plus a suitable margin for over load
on the transformer. Since no load values are specified the requirement
may assumed as 100%
Maximum fault for grading
= 1218amps
Relay PSM
= 1218 / 200 = 6.1
Relay operating time for6.1 times PS and 1.0 TMS is =3.8 secs
To grade relay J with relay H the operating time of relay H at
1218amps must be added to the fixed grading margin of 0.5sec.
ie 0.19 + 0.5 = 0.69sec.
So required TMS
=0.69 / 3.8 = 0.18
Plot the operating characteristic on the log-log sheet.
Generator :
Relay used . The relay used is with a duel characteristic
which changes its pick-up value to 40% of its nominal plug setting and
Page 53 / 153
13
= x 100 =33.33MVA
`
Xd
15
33.33
So the fault current
= = 2.916 KA
3 x 6.6
Relay PSM = 2916 / 200 = 14.57
Relay operating time for 14.57 times PS and 1.0 TMS is 2.5 secs.
Relay J operating time at 2916 Amps is 0.38 secs.
Grading margin 0.5 sec.
Hence operating time on fault curve should be
0.38
+ 0.5 = 0.88 secs
So TMS = 0.88 / 2.5 = 0.352
Plot the operating characteristic of the fault curve and over load
curve on the log-log sheet.
Page 54 / 153
14
fig 3.6
Instead of three separate CTs one open core CT (Core Balance
CT) can be used in networks three cable (Fig 3.7).
fig 3.7
In case of non-directional earth fault relays a capacitor across
the CBCT terminal will increase the sensitivity of the relay.( Fig 3.8)
The sensitivity of the relay can be increased by running the cable
several times through the CBCT. The sensitivity will increase twice for
two turns. (Fig3.9)
Page 55 / 153
15
fig 3.8
fig 3.9
fig 3.10
fig 3.11
Page 56 / 153
16
fig 3.12
Page 57 / 153
17
4.Differential relay
CT connection for differential relay:
The basic requirement of differential relay connection must satisfy the
follow ing conditions.
1) The relay must not operate for external faults.
2) The relay must operate for severe internal faults .
fig 4.1
Connect the CTs of star winding of power transformer in delta
and CTs of delta winding in star. Assume the ratio of power transformer
and CTs as 1:1, so that the current magnitude are equal. Once the proper
connections are arrived the actual ratio can be taken into account.
Assume arbitrarily the current flow in the transformer, but observe the
requirement imposed by the polarity marks that the current flows in
opposite directions in the winding on the same core. The completed
connections for the two winding transformer for differential relaying is
shown in fig 4.1
Page 58 / 153
4.DIFFERENTIAL RELAY
P hase and ratio com pensation of the biased differential protection for
power transformers using interposing current transformers :
In the case of power transformers there may be a phase rotation
between primary and secondary, e.g. group of connection yd5 or yd11,
which has to be compensated before the currents measured in primary
and secondary can be compared by differential relay. Should the ratios
of the current transformers primary and secondary not compared to rated
currents, the amplitude must also be compensated, so that difference
between them at the relay becomes zero under normal load conditions.
Finally the zero sequence component must be eliminated on winding
with grounded star-points.
Formerly, the compensation of group of connection and main
CT ratios was performed outside the differential relay by appropriate
connections of the main CT secondaries or of interposing CTs inserted
between the main CTs inserted between the main CTs and the
differential relay as shown in the fig 4.2
fig 4.2
The main CTs are Y-connected while three single phase inter
posing CTs are connected with the same vector group of connection as
the power transformer. Typical interposing CTs have several tapings for
adjusting their ratio KICT to the composite ratio of the power transformer
Page 59 / 153
2
4.DIFFERENTIAL RELAY
KT and the main CTs KS1 and KS2. The follow ing relationship for
determining the ratio of KICT is determined from fig 4.2
I2N / 3 . KS2
KICT =
I1N / KS1
KS1
=
3 .KT . KS2
where I1N and I2N are primary and secondary rated
current of the transformer.
Inter posing CTs are also used in the case Y-connected
primaries and secondaries. e.g. group of connection Yy0, to compensate
difference of ratio. Since the ICTs are also connected in Yy0 , the term
3 in the above equation is omitted while determining the ratio of KICT.
Phase and ratio compensation is essential in the case of three
winding transformer, because there is always a phase-shift between the
current of the three windings and the ratios of the three groups of main
CTs have to be adjusted to each other. The principle of compensation
for a Ydd three winding transformer with three groups of interposing
CTs ICT1 , ICT2 and ICT3 is shown in fig 4.3 in a simplif ied form.
fig4.3
The ratios of the interposing CTs in the three legs n can be determined
using the generally applicable formula
SN
1
Page 60 / 153
3
4.DIFFERENTIAL RELAY
KICT =
3. UN. KSN
m
where KSN = main CT ratios in legs n =1,2,3.
m = factordepending on ICT circuit
m = INP/3 incase of Y/
m = INP in case of Y/Y, INP being the main CT
nominal current i.e. the primary current of
ICT
Sn = rated transformer power.
Un = rated voltage of the respective winding.
Illustration 1
fig 4.4
Matching transformer required
=3.75 / 4.625
Assume the secondary turns of matching transformer as 25 turns.
The number of turns on the primary side T p = ( Is / Ip ) x T s
= ( 4.625 / 3.75 ) x25
= 30.83 31 turns.
Current imbalance due to the use of 31 turns limited to
30.83 - 31
Error =
x 100% = - 0.55%
30.683
Inter posing CT of ratio 4.625 / 5 could also have been used in
conjunction with the 200/5 CTs. In such case ICT used in conjunction
with the 1000/5 CT should be 3.75/5A.
In omitting to provide a second ICT the effective setting would
be increased by the ratio (5 /4.625) x 100% i.e. 108.1%.
Page 61 / 153
4
4.DIFFERENTIAL RELAY
Illustration 2
Three phase transformer , 30MVA , 11 / 66KV delta - star
fig 4.5
11KVWinding:
30x106
Normal current at 11KV = = 1574 .6 Amps
3 x 11 x 103
Bec ause the 11KV winding is Delta connected, the associated
current transformer will be star connected and under rated load
condition the current per pilot phase will be
Is = (1574.6 /1600) x 1A =0.984 Amps.
This current sufficiently close to relay rated current (1A).
6.6 KV winding :
30 x 106
Normal current at 6.6KV = = 262.43Amps.
3 x 6.6 x 103
To provide appropriate phase shif t correction the current
transformer associated with the star winding of the main transformer
Page 62 / 153
5
4.DIFFERENTIAL RELAY
Ip
0.875
Assume the secondary of the ICT uses 215 turns, then the primary turns
required is given by
Is / 3
0.984 x 215
T p = x T s = = 139.6 turns 140 turns
Ip
3 x 0.875
Illustration 3
Three winding transformer :
400MVA /100 MVA / 300 MVA, 500 / 13.45 / 138KV Star - Delta
fig 4.6
The current transformer ratios are chosen as a function of the winding
voltage and power rating of the particular winding with which they are
associated.
Page 63 / 153
6
4.DIFFERENTIAL RELAY
500KV winding :
Based on the 400MVA the rated current is given by
400 x 106
In = = 462Amps
3 x 500 x 103
Secondary current from 500 / 5A CT
Is = (462 / 500) x 5 = 4.62Amps.
The 500 / 5 A star connected CTs are associated with the 500KV star
winding, and thus the transition to delta connected secondary must be
made by means of an interposing CT.
Assuming the secondary of the ICT be 43 turns.
Is /3
5 x 43
Then primary turns T p = x Ts = = 26.86 or say 27 turns
Ip
3 x 4.62
138KV winding :
During external fault conditions the line CT out put current
must be related to the primary input MVA.
So based on 400MVA, the corresponding current
400 x 106
In = = 1674Amps.
3 x 138 x 103
secondary current of 138KV CT is
Is = (1674 /1200) x 5 = 6.975 Amps
The 1200 / 5A star connected CTs are associated with the
138KV star winding of the transformer. Hence necessary transition to
delta connection must be made by means of an ICT.
Assuming the secondary of the ICT be 43 turns,
Is /3
5 x 43
Then the primary turns T p = x Ts = = 17.79, say 18 turns
Ip
3 x6.975
13.45KV winding :
Based on 400MVA, the corresponding current
400 x 106
In = = 17170.2Amps.
3 x 13.45 x 103
Page 64 / 153
7
4.DIFFERENTIAL RELAY
Page 65 / 153
8
Page 66 / 153
Page 67 / 153
2
Page 68 / 153
3
3) The maximum loop lead burden between the relay and CTs
is used.
With one set of CTs saturated the maximum voltage developed
across the stabilizing resister and relay coil in series, is
If ( Rs + Rl ) / N volts
where If is the maximum fault current
Rs is the CT internal resistance
Rl is the maximum lead resistance
N is the CT ratio
For stability, the current through the relay coil at this voltage
must be insufficient to cause relay operation. A stabilizing resister is
chosen which will just allow setting current to flow through the coil.
Example 1 :Maximum voltage calculated by the above method.50 volts.
Setting on the relay ..0.1 Amps
Burden of the relay at the adopted setting .1 VA
Relay impedance at setting current = VA / Is2
= 1.0 / (0.1)2 = 100 ohm
Relay circuit impedance (Stabilizing resister and relay) = Vk/ Is
= 50 / 0.1 = 500 ohm
Therefore Stabilizing resister = ( Vk / Is ) - (VA / Is2 )
= 500 - 100 = 400 ohm.
Example 2 :Machine rating
247 MVA, 15.75 KV.
Sub transient reactance Xd `` = 21.4%
CT ratio 10000 / 5Amps, RCT = 1.5 ohm
1
1
Maximum sub transient through fault current = =
Xd``
0.214
= 4.67 pu
247
= 9.0 kA
3 x 15.75
= 4.67 x 9.06 = 42.3 kA
If
Page 69 / 153
4
Page 70 / 153
5
fig 5.1
Data required :
1) CT Ratio . 200 / 1 A
2) magnetizing characteristic of CT..Graph (fig), class X
3) CT secondary winding resistance .. 3 ohm
4) Lead resistance (loop) 3 ohm
5) Rating of transformer . 30
MVA
6) Ratio of transformer 132 / 11
kV
7) Required primary fault setting 25 %
8) power transformer impedance .. .. 9.5 %
9) Min CT knee point voltage .. 126 V
1
1
If = x 100
= x 100
= 10.5 %
% impedance
9.5%
Minimum knee point voltage Vk = 2 If ( R ct + R l )
= 2 x 10.5 x (3+3) = 126V
25
30 MVA
Required primary fault setting
= x = 33
Amp
100 3 x 132 kV
There fore secondary fault setting = 33 x ( 1/200 ) =0.165
Amp
Page 71 / 153
6
For actual setting all currents through shunt path must be subtracted.
Shunt path current = number CT x their magnetizing current.
Thus actual setting = 0.165 - 3 x Imetrosil
In R.E.F application where through fault current is limited Imetrosil may
be ignored. Magnetizing current must be considered at relay setting Vs
which is now calculated.
From the magnetization curve in fig the knee point voltage
Vk
is 300 volts.
A stabilizing voltage within the range of Vk/2 to Vk /4 is
normal.
So Vs may be chosen as 150 volts.
The value of Imag at Vs = 150 is 0.015 Amps.
So setting in secondary amps = 0.15 - 3 x 0.015
= 0.12 Amps
The stabilizing resistance (series voltage dropping resistance)
for a stabilizing setting of 150V can be calculated as follows :
Vstability - Vrelay
Rs =
Is
Vs
Vr
Vs
Vr x Is
= - = -
Is
Is
Is
Is x Is
Vs
VA
= -
(where VA is relay burden)
Is
Is2
150
0.5
= -
0.12
(0.12)2
= 1250 - 34.7 = 1215 ohms
The nearest standard value of 1250 ohms may be used.
The 0.5 sec rating resistor R s =Is2 R (where Ir = Vf / R s )
Vf is the peak value developed across the resistor Rs under internal
condition.
Vf = 4(Vk3 x R s x Ifs) x 1.3
where Ifs = IRMS of secondary fault current
4
3
Vf = (300 x 1250 x 10.5) x 1.3
= 1003 volts
IR = 1003 / 1250 = 0.8 Amps for 0.5 sec.
Page 72 / 153
7
So ,
I2R s = (0.8)2 x 1250 = 800 Watts for 0.5 sec
continuos rating of the metrosil is given by
4 If
x x Vk
where N is CT ratio
N
4
2100
= x x 300 = 4010 jou les
200
which is well within the maximum rating of 3`` metrosil which is 43000
jou les.
Illustration 1:
voltage 11 kV, 3 phase, 50
Hz
output 30 MVA, 0.8 pf
machine transient reactance Xd` 19%
machine synchronous reactance . 200%
CT ratio 1500/5 A
VT ratio 11000/110 volts
Page 73 / 153
8
fig 5.2
Offset setting:
Machine transient reactance in secondary ohms = Xd% x (kV)2 x CTR
100
MVA PTR
= 19 x 112 x (1500/5)
100 30
(11000/110)
= 2.3 ohm
Required setting Xd `/2 = 2.3/2 =1.15 ohm.
Circle diameter setting:
Machine synchronous reactance in }
= Xs % x (kV)2 x CTR
secondary ohms }
100 MVA PTR
= 200 x 112 x (1500/5)
100 30
(11000/110)
= 24.2 ohm
Required circle diameter Xs
=
24.2 ohm
Illustration 2 :
Afield failure relay with K1 (setting for diameter of the
impedance circle) and K2 setting for offset of the impedance circle )
expressed as a percentage of nominal imped ance is used to protect as
alternator with the follow ing characteristics:
In = 2100 amps, Xs = 200%, Xd` = 30%
Nominal primary current of CT = 2500Amps
Find the pickup current at two levels of the characteristic with nominal
voltage and phase angle of +90 for a relay with Vn =110V and In = 5A
.
Page 74 / 153
9
fig 5.3
Relay nominal voltage
Vn = 110V
Relay nominal current
In = 5A
Relay nominal impedance Z n = Vn / (3In )
=110 / (3 x 5 ) = 12.7 ohms.
Under this condition with nominal test voltage 110volts the relay would
pickup at
IA = U x 100 = 110 x 100
= 48.1A
Zn
K2
12.7 x 18
IB = U x 100 = 110 x 100
= 3.38A
Zn
K2
12.7 x (238+18)
Page 75 / 153
10
Illustration 3 :
PGEN
= 200MW
UN.GEN = 15.85 kV
IN.GEN = 8625 Amps
Xd
= 1.9808pu
Xd`
= 0.2428pu
Xn
= 0.2pu
fig 5.4
In.Relay x IN.CT.Pri x UN.VT.Sec x UN.GEN
Xsec (pu) = Xpri (pu) x
IN.CT.Sec x IN.GEN x Un.Relay x UN.VT.Pri
CTR x UN.GEN x In. Relay
= Xpri (pu) x
PTR x IN.GEN x Un.Relay
UN.Relay
100
Z n.Relay =
=
= 11.55 ohm
3 x IN.Relay
3 x 5
CTR = 2000,
PTR =143.18
a) Setting impedance element for dynamic stability characteristic:
1 0.2428 x 2000 x 15750 x 5
Z 1A = Z 2A = x x 100%
2
143.18 x 8625 x 100
= - 15.48% 16%
2000 x 15750 x 5
Z 1B
= 1.9808 x x 100%
143.18x 8625 x 100
= - 252.6
253%
Z 2B = Z 2B / 2 = 253/2 126%
Page 76 / 153
11
fig 5.5
b) Setting impedance element for steady state and dynamic stability
characteristic:
Z 1A
Z 1B
fig 5.6
CTR x UN.GEN x In. Relay
= XN x
PTR x IN.GEN x Un.Relay
2000 x 15750 x 5
= 0.2 x x100%
143.15 x 8625 x 100
= + 25.5 26%
2000 x 15750 x 5
= 1.1 x 19808 x x100% + Z 1A
Page 77 / 153
12
Tripping time
tZ1
= 1.0s ( set between 0.5 to 3sec)
tZ1
= 0.25s ( set between 0.5 to 3sec)
Setting of under voltage element
The under voltage protection element is usually set to the
critical system voltage at which the generator loss of field jeopardizes
the system stability. The limit is normally 80% of the generator voltage.
UN.Gen
15750
U = 0.8 x = 0.8 x = 88%
PTR
143.18
Page 78 / 153
13
Page 79 / 153
14
Illustration 1:
Active power of the generator PGEN
Nominal current of the relay IN
Nominal voltage of the relay VN
CT ratio
PT ratio
Relay to be set 3% reverse power.
Reference power of the relay
PR =
3 x UN x IN x CTR x PTR
= 3 x 5 x 100 x 30 x 100
= 2598KW
If the relay should pick up at a reverse power of greater than 3%
(referred to the active power of the generator) the adjustment value on
the relay can be calculated as
PGEN
1500KW
Adjustment Value % = x %P = x 3% = 2%
PR
2598KW
Hence the relay should be set at 2%.
Illustration 2:
Active power of the generator PGEN = 210 MW
Nominal current of the relay IN
= 5A
Nominal voltage of the relay VN
= 100V
CT ratio
= 10000/5A
PT ratio
= 15.75KV/110V
Relay to be set 1% reverse power.
Reference power of the relay
PR = 3 x UN x IN x CTR x PTR
= 3 x 100 x 5 x 2000 x 143.18
= 248MW
PGEN
210MW
Adjustment Value % = x %P = x 1% = 0.846%
PR
248MW
Since the relay is fed from voltage transformers of 110V, the actual
setting for 1% reverse power is
U
x 0.846 = 0.93 1%
UN
Illustration 3:
Page 80 / 153
15
7.5%
1
10%
1.78
15%
4
20%
7.1
30%
16
I22 t = K1 x K3
K1 selectable between 1 to 10
Setting:
Select a plug board setting I2S equal to nearest below the
generator continuous negative phase sequence current withstand rating
i.e.
I2S = 10%
Choose appropriate value of K3 from the table of relay characteristic
Page 81 / 153
16
i.e.
K3 = 1.78
Choose the time multiplier setting K1 from the formula
I2 2t = K = K1 x K3
i.e.
K1 x K3 = 7.5
K1 = 7.5 / 1.8 = 4.21
Select the nearest lower tap value of K1 available
i.e.
K1 = 3.9
Comparison of relay operating time and generator withstand time at five
times relay setting current :
Generator withstand time tm = K / I22t = 7.5 / (5 0.1)2 = 30 sec
Relay operating time from graph of relay characteristic when K1is 1 and
at 5 setting current is 7sec
So relay operating time tr = K1 (operating when K1 = 1)
i.e.
tr = 3.9 7 = 27.3sec.
Illustration 2 :
Generator parameters
Nominal current
800A
CT Ratio
1000/5A
Continuously permissible unbalance current I2S
I 22t of generator
60s
Relay particulars
Nominal current In
5A
Setting range
I2t
0.02 to 0.5 In
I2w
0.02 to 0.5 In
Time selectable T (DEF)
1 to 200sec
T (INV)
300 to 3600sec
40%
( trip )
(warning )
Page 82 / 153
17
Illustration 3 :
Generator parameters
Nominal current
9060A
CT Ratio
10000/5A
Continuously permissible unbalance current I2S
5%
I 22t of generator
8s
Relay particulars
Nominal current In
5A (Type RARIB of ASEA)
In 2
operating characteristic t = K
I2
where K is I22t constant of generator.
Relay setting current I2s = 9060 (5/10000) = 4.53A
i.e.
(4.53/ 5) In
= 0.906 In
K = 8 on the relay.
Continuous negative sequence withstand characteristic of 5%
implies that maximum difference between the line current is
about 10%. So set the trip relay at 8% and alarm relay at 4%.
Page 83 / 153
18
Illustration 1 :
System details
Rating of generator
210MW/247MVA, 15.75KV.
Number of machine operating in parallel
2
Length of the longest line
185 KM
Line impedance /KM
0.335 ohm
Rating of transformer
250 MVA, Ratio 15.75/230 KV
% impedance
14 %
Taking under-reaching effect into consideration the impedance setting
required to cover the entire length is
Z T + NZ L
where Z T is the impedance of the transformer and Z L is the
impedance of the longest line both in primary ohms on HV basis. N is
the number of generator in parallel.
(KV)2
Z T = Z pu
MVA
14
2302
=
= 29.62 ohms
100
250
Z L = 185 0.335 = 61.98 ohms
Z T + Z L = 29.62 + 61.98 = 153.58 ohms
Impedance expresses at the
generator voltage level = Z ( VL / VH )2
= 153.58 (15.75 / 230 )2
= 0.72 ohm
CTR
Setting in secondary ohms
= Z
PTR
10000
110
= 0.72
5
15750
=10.057 ohms
The relays are supplied with delta voltages and delta currents
and connected for phase fault measurements. Therefore it will have a
setting of 1.15 times (derivation of which is given separately) actual
Page 84 / 153
19
setting i.e. If the actual setting is 3 to12 ohms the effective setting will
be 3.45 to13.2ohms.
So the setting required on the relay
= 10.057 / 1.15
= 8.745 ohms.
Alternate criteria for setting :
Criteria Set at 70% of the load imped ance.
KV2
2002
Z load = = = 1.004 /Ph
MVA
247
70
Primary setting = 1.004 = 0.703 / Ph
100
CTR
Secondary setting = Z
PTR
10000
110
= 0.703 = 9.82 / Ph
5
15750
Applying the effect of delta voltages and delta currents
9.82
Relay setting = = 8.539 8.5 /Ph
1.15
Illustration :
Page 85 / 153
20
fig 5.7
For this specific example a relay (Type RATUB of asea make)
is considered.
The characteristic of the relay is
K
t = 0.8 + 0.18
( m 1)2
( V/f )
where m = and
(V/f)set
K = the adjustable time constant.
Transformer working flux density
= 1.6 Tesla (assumed )
Transformer saturation flux density = 1.9 Tesla (assumed )
Flux ratio = 1.9 /1.6 = 1.185 1.1 (say).
The maximum permitted excitation corresponds to
110
1.1 = 2.42 V/Hz on the relay side
50
So V/f start level setting =2.4 V/Hz.
Calculate appropriate K factor for 150% excitation.
( V/f )
1.5
150% excitation corresponds to
= = 1.3636
(V/f)set
1.1
fig 5.8
From the excitation characteristic of step up transformer (see graph)
time for 150% excitation is 5.5secs.
t 0.8 V/f
2
K = 1
0.18 V/fset
Page 86 / 153
21
5.5 0.8
( 1.3636 1 )2 3.4
0.18
Choose K = 3 and check the operating time for different points on the
excitation curve of the transformer and plot it on the same sheet.
0.18 3
t = 0.8 +
V/f
2
1
V/fset
Page 87 / 153
22
Page 88 / 153
23
Illustration :
Generator rating 247MVA, 15.75KV
Sub transient reactance Xd`` = 21.4%
Generator transformer rating 250MVA, (240/3) /15.75 KV
Percentage impedance 14%
Fault level of the 240 KV bus 5000 MVA.
fig 5.9
KV2
Generator sub transient reactance in ohms = Xd``pu
MVA
21.4
15.752
=
100
247
Page 89 / 153
24
XG
XT
Source impedance
=
=
=
=
0.2149
0.9 X
0.9 0.2149
01934
KV2
= Xpu
MVA
14
15.752
=
100
250
= 0.1389
Fault MVA
=
KV2
5000
=
15.752
= 0.0496
fig 5.10
From the graph off -set
= 0.185
CTR
Off - set in secondary ohms = Primary ohm
PTR
Time setting
10000
110
= 0.185
5
15750
= 2.584
1
=
Rate of slip
So
t
Page 90 / 153
25
270 182
=
=
=
=
=
1600
55 m . sec
115% of FLC
4.525 0.115
5.2 amps
fig5.11
KV2
15.752
Load impedance = = = 1.004
MVA
247
Assume minimum load resistance R L.M IN = 85%
Z A = XT + XN
= 0.1389 + 0.0496 = 0.1885
Z B = Xd`
= 0.2149
Z C = 0.9 XT
= 0.9 0.1389 = 0.125
Page 91 / 153
26
10000
110
= 0.1885
5
15750
= 0.1885 13.968 = 2.63
ZB
= 0. 2149 13.968 = 3
ZC
= 0.125 13.968 = 1.746
RL.M IN
*
= 180 2 tan 1 1.54
ZA +ZB
0.85 1.004
= 180 2 tan -1 1.54
0.1885 + 2149
= 180 2 tan-1(3.258) = 34
( If is less than 90 set at 90)
setting available is 90 to 150
So set at = 90
Set = 85 ( 5 higher than system angle )
operation time of the relay 50 ms (fixed )
Page 92 / 153
27
Page 93 / 153
28
6.Distance relays
General P rinciple :
Distance protection monitors the imped ance of the protected
unit as seen from the relay location. The impedance is high when there
is no fault on the protected unit and low when there is a fault. Distance
protection is used as a primarily protection for transmission lines, and
as a backup protection for large generators, power transformer and autotransformer.
The important advantage of distance protection in comparison
with graded over current protection is its extremely fast operation for
faults in the first zone of protection, which is usually between 80 to 90%
of the protected line. Thus faults close to the source can be tripped just
quickly as faults at the end of the line. From fig 6.1 it can also be seen
that each of the distance relays RZ 1 to RZ3 has several impedance zones
fig 6.1
with different operating times. The second and higher zones provide
back-up protection for other section of line, should either their
protection or circuit breaker fails to clear the fault. This means that
assuming a fault on L 2( fault location F2) distance relay RZ 1 would trip
circuit breaker-1 after the time t1II should the relay RZ2 fail to clear the
fault in its first time step (operating time t2I ). A fault at F3 (last 10 to
15% of the line) on the other hand would be detected by distance relay
Page 94 / 153
6.Distance relays
RZ 2 in its second Zone and tripped after the time t2II. Should this not
take place, RZ 1 would trip circuit breaker-1 until the time t3III has
expired, because the fault lies in its third impedance zone.
It follows from this explanation that discrimination is
achieved in the case of distance protection by giving tripping priority to
the relay which measures the lowest impedance, i.e. the shortest distance
to the fault. It was also explained, that the first zone cannot be set to
cover the full length of the line. In order to ensure proper discrimination
under all conditions it has to be set short and as a result fau8lts in the
last 10 to 15% are detected in the second Zone. This margin has to be
observed, because if the first zone were to be set to 100% of the line,
faults at the beginning of the next section of the line might be detected
by mistake due to inaccuracies of the distance measurement and line
impedance data. This apparent disadvantage is overcome by installing a
communication channel between the relay at two end of the line or, if
auto-reclosure is used, by an appropriate auto-reclosure log ic.
Measuring principle:
A simplif ied illustration of the principle of distance
measurement is given in fig 6.2 a & 6.2 b.
It assumes that only the positive-sequence component of the
line impedance is
measured and the
zone of
protection
corresponds to
Page 95 / 153
2
6.Distance relays
Protected circuit
fig 6.2 a
UL = IF.Z LAF
IF`.Z M
UL` = UL / KNU
Measuring
Impedance characteristic
UM =
principle
fig 6.2 b
the first zone of any of the relays e.g. RZ1, as shown in the fig 6.1. This
means that all faults occurring between station-A and zone limit G are in
Page 96 / 153
3
6.Distance relays
the operating area of the distance relay characteristic, and fault outside
this area are not detected in the first zone. It is the relays job to decide
whether the fault impedance lies within or outside the characteristic.
One possibility of doing this is to compare the absolute values of two
variables, one which is the voltage drop UL across the impedance of the
fault loop Z LAF and the other is the voltage drop UM across what is
referred to as the replica impedance Z M connected to the secondary of
the CT. The reflected impedance of the replica on the primary side of
the current transformer corresponds to the line impedance Z 1I i.e. the
impedance of the first zone. The two variables at the input of the
amplitude comparator M are thus given by the relationship
UL
IK . Z LAF
UL`
=
1
KNU
KNU
IK . Z M
UM
=
IK` . Z M
=
2
KNI
where IK
IK`
primary fault
current IK
=
i.e. IK`
IK / KNI
KNI
KNU
Z LAF
= nominal CT ratio
= nominal V.T ratio
= impedance of the line loop
between
section
and
fault location F
ZM
= replica impedance, in this
case Z M = Z 1I
As mentioned above , the absolute values of the voltages UL`
and UM are compared and therefore for a limit of the first zone (G in
fig6.2b)
| UL` |
=
| UM |
3
Page 97 / 153
4
6.Distance relays
This means that the signals applied to the amplitude comparator M are
balanced and the condition for tripping is not fulfilled. If both sides of
equation 1 and 2 are divided by IK and IK` equation 3 becomes
Z L ` = Z M = Z 1I
The graphical representation of the characteristic in the R/X plane is a
circle with its center at the origin of the system coordinates ( fig 6.2b).
This is also the location of the beginning of the protected line. Since the
ratio between X and R of the line is known, the impedance of the line
between A and B can be represented by the impedance vector Z AB if a
corresponding scalar value is assumed. The operating area of the
protection lies inside the circular characteristic and the restrained area
outside. Thus tripping condition is expressed by the follow ing inequality.
|Z M|
>
|Z L`|
4
which in terms of voltage means |UL| < |UM| and is the case assumed
in fig 6.2b. The fault location F lies in the first zone and therefore |Z LAF |
is less than Z LAG = Z M. Since the same fault current flows through both
impedances, the voltage |UL `| is also less than UM and protection trips.
For faults beyond the limit of the first zone, |Z L`| > |Z M| and therefore
also |UL`| > |UM| and the protection restrains.
The consideration up to the present were concerned with the
application of distance protection to radial lines. If fault energy can be
supplied from both ends, distance relays have to be installed at both
terminal stations as shown in fig 6.3.
Assuming that the relay should only trip for faults in the
forward direction, the two relays must have operating characteristic
which are capable of making a clear directional decision. A
protection
Page 98 / 153
5
6.Distance relays
fig 6.3
with an impedance characteristic according to fig 6.2b cannot fulfill this
requirement, because the impedance vector seen by the relays RZ I and
RZ 2 for the fault locations F1 and F3 are also in the operating area. For
respective relays, these faults are in the third quadrant of the R/X plane
as shown for RZ 1 in fig c. to prevent a distance relay from operating for
faults in the reverse direction, its characteristics in the R/X plane must
not encroach on the third quadrant. The desired mode of operation is
Page 99 / 153
6
6.Distance relays
Setting recommendation :
Positive sequence impedance:The line impedance converted to the secondary side of the
instrument transformer with the follow ing formula
CT Ratio
Z sec
= Z pri
PT Ratio
CT pri
VT sec
=
Z pri
CT sec
VT sec
Due to errors in relays, current transformers, voltage
transformers and inaccuracies inline data an under reaching zone 1
reach is normally set at 80% of the calculated line impedance. For the
same reason an over reaching zone 2 reach is set to cover the protected
line plus 50% of the adjacent shortest line or 120% of the protected line
whichever is greater. The zone 2 setting should never exceed 80% of the
impedance corresponding to the protected line plus the first zone reach
of the shortest adjacent line and the impedance corresponding to the
protected line plus the impedance of the maximum number of
transformers in parallel on the bus at the remote end of thee protected
line. The zone 3 reach is set to cover 120% of the protected line plus the
6.Distance relays
longest adjacent line. It should at least two times the zone 1 setting. The
zone 3reverse function can also be used for backup protection of the bus
bars behind the relay and is typically at 25% of zone 1 setting.
Zero sequence compensation :The measuring loop at single phase to ground faults consists of
two impedances, the positive sequence impedance the positive sequence
impedance Z 1 and the zero sequence Z 0 . To measure the impedance upto
fault point correctly, a compensation factor known as zero sequence
compensation or residual compensation must be applied.
Z0 Z 1
This compensation is calculated as
Kn
3Z1
Fault resistance:The single phase to ground fault is of great importance in
distance protection as normally more than 70% of the faults on
transmission line are single phase to ground. The fault resistant
composed of two components, the arc resistance and the tower footing
resistance. The arc resistance as per Warington formula is
28707 l
Rarc =
I1.4
where I =
the actual fault current
l =length of the arc in meters.
l is approximately 2 -3 times the arc foot spacing. The tower
footing resistance must be calculated or measured for the specific cases
as the variation of this parameter is very large.
Distance relay cannot be used to detect very high resistive
ground faults as the reach is limited by the load impedance and load
transfer.
Margin between resistive reach and load impedance in the ase of
quadrilateral characteristic :the maximum permissible resistive reach for any zone should
be checked to ensure that sufficient setting margin between the relay
boundary and minimum load impedance. The minimum load impedance
is calculated as
(KV)2
Z load =
= ohm/phase.
6.Distance relays
MVA
Since the safety margin is required to avoid load encroachment
under three phase fault conditions and to avoid healthy phase relay
operation under combined three phase load and ground faults, both the
phase to phase and phase to ground characteristic should be considered.
The load impedance is a function of minimum operation
voltage and maximum load current under emergency conditions.
Umin
Z load.min =
= ohm /phase
3 Imax
To avoid load encroachment the resistive reach should be set
less than 80% of the minimum load imped ance.
Power swing blocking :power swings are variations in power flow which occur when
the voltage of generator at different points of the power system slip
relative to each other to cater for changes of load magnitude and
direction or as a result of fault and their subsequent clearance.
fig 6.4
The results of a power swing may cause the impedance
presented to the distance relay to move away from the normal load area
and into the relay characteristic. In the case transient power swing it is
important that the distance relay should not trip and should allow the
power system to return to a stable condition. For this reason an optional
power swing blocking relay is provided in distance protection schemes.
Since the power swing is a balanced three phase condition a single phase
6.Distance relays
Illustration 1 :
fig 6.5
Length
of
the
180KM
Length of the adjacent shortest line
length of the adjacent longest line
Positive
sequence
0.0264 + j0.3289
ohm/KM
protected
line
220KM
380KM
impedance
6.Distance relays
i.e.
0.3385.42
ohm/KM
Zero
sequence
0.08887 + j1.1094 ohm/KM
impedance
i.e.
1.11385.42
Line
85.42
Relay
75
CT
1000 /1 A
PT
400,000/110V
ohm/KM
angle
angle
ratio
ratio
CTR
1000
110
Transformation ratio
= 0.275
PTR
1
400,000
Primary impedance of the
protected line
= 0.33
180
= 59.4 ohm
Secondary impedance of the
protected line
Impedance Transformation ratio
=
59.4 0.275
relay
Cos(L R )
16.335
Pri.
= 16.335ohm
16.61ohm
Cos(85.42 75 )
Primary impedance of the
Pri.Imp
angle
6.Distance relays
20.299 ohm
0.33
220
72.6 0.275
19.965
relay angle
Cos(85.42 75)
Primary impedance of the
adjacent longest line
= 0.33 380
= 125.4 ohm
Secondary impedance of the
adjacent longest line
= 125.4 0.275
= 34.485 ohm
Sec. Impedance along the
34.485
relay angle
=
= 35.063 ohm
Cos(85.42 75)
Zone 1 reach
of the protected line
= 0.8 16.61
Zone 2 reach
protected line
80%
13.287 ohm
=
120% of the
or
protected
line + 50%of the adjacent
shortest
line whichever is greater
16.61 or
1.2
19.932
or 26.7998 ohm
Zone 2 reach adopted
Zone 3 forward reach
longest
=
=
26.7998 ohm
120% of (protected line +
6.Distance relays
adjacent line)
=
1.2
( 16.61 + 35.0632 )
=
ohm
Zone 3 reverse reach
0.25 13.287
=3.3217 ohm
Starter setting
setting
i.e. Forward reach
62
125%of Zone 3
( 0.25 Z 3F ) + Z 3F
=
( 0.25 62 ) + 62
=
Reverse reach
77.5 ohm
=
(0.25 62 ) + 3.3217
= 18.82 ohm
Power swing blocking relay setting =
i.e. Forward reach
Z 3F
=
( 0.5 62 ) + 62
Reverse reach
( 0.25 Z 3F ) + Z 3R
=
93 ohm
=
( 0.5 Z 3F ) +
Z 3R
=
(0.5 62 ) + 3.3217 = 34.32 ohm
Z0 Z 1
Neutral compensation
100
3ZI
1.113 0.33
=
100
3 0.33
Time setting :
=79.09 %
Zone 2 time
= 0.4 sec
6.Distance relays
Zone 3 time
= 0.
8sec
Illustration 2 :
(reactance relay)
fig 6.6
Length
of
the
70KM
Length of the adjacent shortest line
length of the adjacent longest line
Positive sequence impedance
+ j0.4
ohm/KM
Zero
sequence
0.04 + j1.0 ohm/KM
Line
angle
67.3
Relay
75 (power swing
protected
line
30KM
55KM
0.016
impedance
1 (0.4/0.16)
tan
angle
blocking relay )
CT
300 /1 A
PT
110,000/110V
ratio
ratio
CTR
300
110
Transformation ratio
= 0.3
1
PTR
110,000
6.Distance relays
= (0.16 + j0.4) 70
Pri. Impedance
= 11.2 + j28
ohm 0.3 = 3.36 + j8.4 ohm
Primary impedance of the
adjacent shortest line
= (0.16 + j0.4) 30 =
4.8 + j12 ohm
Secondary impedance of the
adjacent shortest line
= (4.8 + j12) 0.3
=
1.44 + j3.6 ohm
Primary impedance of the
adjacent longest line
= (0.16 + j0.4) 55
= 8.8 + j22 ohm
Secondary impedance of the
adjacent longest line
=
(8.8 + j22) 0.3
=
2.64 + j6.6 ohm
Zone 1 reach (reactance only)
= 80% of the protected line
=
0.8 8.4
= 6.72 ohm
Zone 2 reach (reactance only)
= 120% of the protected line
or
protected line + 50%of the adjacent
shortest
line whichever is greater
=
1.2 8.4 or
10.08
or 10.2 ohm
Zone 2 reach adopted
Zone 3 forward reach
line + longest
10.2 ohm
= 120% of (protected
6.Distance relays
adjacent line)
=
1.2 ( 8.4 + 6.6 )
=
18 ohm
Zone 3 reverse reach
= No reverse reach setting in
reactance relays
Mho starting unit :
Zone 3 reach in reactance = 18 ohm
Line angle
= 67.3
18
Zone 3 reach in impedance
ohm
19.51
7.285
sin67.3
6.72
Zone 3 reach in impedance
ohm
sin67.3
Starter setting (impedance)
setting
i.e. Forward reach
=
=
125%of Zone 3
( 0.25 Z 3F ) + Z 3F
=
( 0.25 Z 3F ) + 0.25
=
6.Distance relays
Reverse reach
( 0.5 Z 3F ) + Z 3R
=
3XI
1
0.4
100
50%
3 0.4
Illustration 3 :
fig 6.7
the
Length
of
135KM
Length of the adjacent shortest line
length of the adjacent longest line
Positive sequence impedance
j0.4125
ohm/KM
Zero
sequence
0.263 + j1.51 ohm/KM
protected
line
16KM
140KM
0.08 +
impedance
6.Distance relays
Line
angle
79
Max.load
250MVA
CT
800 /1 A
PT
230,000/110V
1
(0.4125/0.08)
tan
transfer
ratio
ratio
CTR
800
110
Transformation ratio
= 0.3826
PTR
1
230,000
Primary impedance of the
protected line
= (0.08 +
j0.4125) 135
=10.8 + j55.68 ohm
Secondary impedance of the
protected line
Pri. Impedance
Transformation ratio
= 10.8 + j55.68 0.3826
= 4.13 + j21.3 ohm
Primary impedance of the
adjacent shortest line
(0.08 + j0.4125) 16
=
0.08 + j0.4125)
=
6.Distance relays
(11.2 + j57.75)
=
=18.1 ohm
or
10001.4
0.8 21.3
17.04 ohm
or
protected line + 50%of the adjacent
shortest
line whichever is greater
=
21.3 or
1.2
25.56
or 22.5625 ohm
Zone 2 reach adopted
Zone 3 forward reach
+ longest
= 25.56 ohm
= 120% of (protected line
adjacent line)
=
1.2 ( 21.3 + 22.09 )
6.Distance relays
=
43.39 ohm
Maximum transformer at station B is
200MVA
Per unit impedance Z pu
=
0.14pu
(average)
MVA
200
Fault MVA
= =
= 1428MVA
Z pu
0.14
(KV)2
2302
Fault impedance =
= = 37.07 ohm
MVA(fault)
1428
The over reach of 4.26 ohm (i.e. 25.56 21.3) of zone 2 at
station A is much smaller than the above impedance. Hence the setting
chosen for zone 2 is O.K.
( KV)2
2302
Z load
=
=
= 211.6 ohm
MVA(load)
250
X0 X1
Zero sequence compensation factor =
3X1
1.51 0.4125
=
=0.886
3 0.4125
Resistive reach
Rfn
=
20 ohm/loop for ground fault
Rf
=
3 ohm/phase for phase to phase fault
Rfn
= 20 0.3826 =
7.652 ohm (secondary )
Rf
=
3 0.3826 = 1.148 ohm (secondary)
Maximum setting of resistive reach is
Z load (MIN)
Rmax < 0.8
1.2
<
80.96
0.8 = 54 ohm
1.2
Required setting
6.Distance relays
Rset
X
KN
Rf +
RNset
X
for ph-ph faults
tan R
Rf +
tan N
where
and
= tan 1(X/R)
= tan 1(0.4125/0.08)
X0
1.51 0.4125
0.263 Zone 1
N
80.53
= tan
R0
0.08
17.04
Rset
1.148 +
17.04
0.886 17.04
RNset
tan 79
tan 80.53
2.52
=
Zone 2
13.48ohm
7.652
25.56
6.116ohm
Rset
79
X1
= tan
R1
= 4.46 ohm
tan
79
7.652
1.148
3.312
tan 79
25.56
0.886 25.56
tan 79
RNset
7.652
tan 80.53
= 16.4 ohm
6.Distance relays
Zone 3
Rset
9.582 ohm
43.39
1.148 +
tan 79
43.39
0.88643.39
tan 79
RNset
7.652
tan 80.53
=
22.5
ohm
As the required reach 22.5 ohm is much less than the minimum
load impedance, there is no risk for load encroachment.
7.Motor Protection
protection relays :
Setting of motor
motorprotection
Illustration :
Motor rating
Voltage
Full load current
CT ratio
Starting time
Starting current
Stalling current
locked rotor withstand time
1700KW
6.6 KV
148.7 Amps
200/1 Amps
7 sec
6 FLC
6 FLC
Hot
10sec
Cold 19sec
Thermal characteristic
rated current
Hot time
Cold time
1.4
400
390
2
200
170
3
90
70
4
48
31
6
19
10
Thermal setting :
CT sec
CT pri
1
= 148.7
= 0.7435 or say 0.76
400
Thermal curve selection ( ) :
The characteristic of modern thermal relays an exponential
characteristic up to two times Ieq (equivalent thermal current ) and an
adiabatic characteristic beyond two times Ieq.
The operating time of relay below 2Ieq is given by
Ieq 2 K3 (IL)2
t = log e
Ieq 2 (K Is )2
where is the heating time constant
IL equivalent pre fault load current
Is thermal current setting of the relay
K 1.03 (minimum operating current )
K3 constant used to provide different
Is = FLC
7.Motor protection
hot/cold ratio
Ieq equivalent current of over load defined by
the equation Ieq = (I12 K2 I22 )
During cold start pre fault load current IL = 0
Ieq 2
t = log e
Ieq 2 (K Is )2
dividing the equation by Is2
( Ieq / Is ) 2
t = log e
(Ieq / Is)2 K2
Ieq.th 2
t = log e
(1)
Ieq.th 2 K2
where Ieq.th = Ieq / Is which is the equivalent load
current expressed in terms thermal setting Is.
So
Ieq FLC CTsec
Ieq.th =
Is CTpri
The operating time of the relay above 2 Ieq is given by
K2
t =
Ieq 2
K2
t =
(2)
Ieq.th 2
Using the equation (1) and (2) calculate at three different points, say
1.4, 3, and 6 (locked rotor current )of the cold withstand characteristic of
the motor.
Ieq.th at 1.4 times Ieq is given by
1.4 148.7 1
Ieq.th = = 1.37
0.76 200
tc
1.4 =
Ieq.th 2
log e
Ieq.th 2 K2
7.Motor protection
400
1.372
log e
1.37 2 1.032
= 479.78 sec or say 7.996 minutes
Ieq.th at 3 times Ieq is given by
3 148.7 1
Ieq.th = = 2.935
0.76 200
tc Ieq. th2
3 =
K2
90 2.9352
3 =
=730.7 sec
1.032
or say 12.18 minutes.
Ieq.th at 6 times Ieq is given by
6 148.7 1
Ieq.th = = 5.87
0.76 200
tc Ieq. th2
6 =
K2
19 5.872
6 =
= 617 sec
1.032
or say 10.28 minutes.
The selected for the motor should be lower than all the above three
values. Since 1.4 is only 7.996 select a of 7. So the relay operating
time at 1.4 times Ieq and a of 7 is given by
1.372
7 60 log e
= 350 sec
1.37 2 1.032
The value of selected should be such that the gap between the
motor withstand time and relay operating time at any multiple of the
setting current is greater than 15%of the motor withstand time or 4 sec
whichever is greater.
1.4 =
7.Motor protection
motor
relay operating
gap
withstand time
time
7
1.4
1.37
400
350
50
Since the gap between motor withstand time and relay
operating time doesnt meet the above requirement when is 7, the
value of should be selected to the next lower value.
i.e. a of 6
Hot/Cold ratio selection :
The value of hot/cold ratio should be such that the relay hot
characteristic comes below the motor hot characteristic and the gap
between the hot withstand time and relay hot operating time at any
multiple of the setting current is greater than 15% of the motor
withstand time or 4 sec whichever is greater.
Select a hot /cold ratio if 0.67. The relay hot /cold operating
time, motor hot /cold operating time etc. at various multiples of Ieq.th
are shown below in the table. If the above criteria is not met choose a
different hot/cold ratio.
Sl.No
Multiples of Is
Motor withstand
Relay operating
setting
time
time
Ieq
Ieq.th
cold
hot
cold
hot
1
1.4
1.37
400
390
300.14 201.09
2
2.0
1.96
200
170
116.83
78.27
3
2.03
1.98
198
168
96.84
64.88
4
3
2.93
90
70
44.34
29.7
5
4
3.913
48
31
24.44
16.71
6
6
3.87
19
10
11.08
7.43
Ieq
Ieq.th
7.Motor protection
7.Motor protection
c) for high inertia motors like ID fan motors etc. time should
be 25% of starting time.
For the given motor time setting = starting time + 2 sec
i.e. tstl = 7 + 2 = 9sec
This is more than hot stall withstand time. So adopt a setting of
7 sec only.
For slip ring motors
current setting
starting current
CTsec
Istl = 1.25
thermal setting
CTpri
time setting
tstl = 0.5 hot stall withstand time.
Prolonged start protection :
current setting
starting current at 80% voltage
CTsec
Ist = 0.8
thermal setting
CTpri
If the starting current at reduced voltage is not available from
the manufacturer, assume
starting current at 80% voltage = 0.8 starting current at 100% voltage
So
0.8 starting current CTsec
Ist = 0.8
thermal setting
CTpri
0.8 6 148.7 1
Ist = 0.8
0.76
200
= 3.76 Amps
For slip ring motors
full load current CTsec
Ist = 1.2
thermal setting
CTpri
Time setting
set at 1.2 starting time
or
max. starting time + 5sec whichever is greater.
For the given motor set at tst = 7 + 5 =12 sec.
7.Motor protection
7.Motor protection
8.Commissioning Tests
CT polarity tests:
In many protection schemes the relative polarity of CT is more
important and therefore the correct polarity must be ensured before they
are connected. The normal current flow convention of CT is when the
primary flows from P1 toP2, the secondary current flows from S1to S2
in the external circuit as shown in the fig 8.1
fig
8.1
fig 8.2
A simple way to check the polarity is flick test which uses a
battery, center zero ammeter, and a push button connected as shown in
the fig8.2. When the push button is pressed the ammeter makes a
positive flick and a negative flick when the push button is released, if
the assumed polarity is correct.
CT ratio check :
The polarity and ratio check can be carried out by the primary
inject ion tests described below:
The circuit for the test is shown in the fig 8.3. A short
circuit is placed across the phases on one side of the CTs and single
phase inject ion is carried out on the other side. One ammeter A2 is
provided in the phase side of the CT circuit and another ammeter A3 is
provided in the residual circuit of the CT. current is injected through the
primary conductor and measured on test set ammeter A1. The secondary
8.Commissioning
Tests
fig 8.3
The ammeter A3 in the residual circuit will read few milliamps if the CT
polarity is correct. The reading A3 twice that of A2 shows wrong
polarity. Single phase inject ion should be carried out for each pair of
phases.
If an earth fault relay with low setting is provided in the
residual circuit its operating should be temporarily short circuited during
the test to avoid overheating.
P olarity
check using series injection :
olaritycheck
The test circuit is as shown in the fig8.4 & 8.5 below.
Inject current approximate to rated current. The ammeter A3
will read three times A2 if the polarity is correct. If the reading of
ammeter A3 is equal to A2,the relative polarity of one of the CT is
wrong.
8.Commissioning
Tests
CT magnetizing curve:
8.Commissioning
Tests
F ig 8.6
The voltmeter is connected in such away that the ammeter
doesnt read the voltmeter current. It will be useful to find roughly the
voltage at which saturation starts by increasing the voltage until there is
a large increase in current for a small change in voltage. From this it can
be decided at what values to take readings to give sufficient point to plot
the curve. Initially take readings in large steps (say 20 or 30 volts) and
smaller steps (say 10 or 5 volts) when saturation starts. Tabulate and
plot the readings.
Voltage
current in mA
0
0
20
1
40
16
60
23
80
31
90
37
100
46
110
65
120
105
For 100vols
Ie =
For (110 +10 ) % i.e.
65 mA
110 volts
100 =
Ie =
65 46
41%
46
105 mA
105 65
8.Commissioning
Tests
i.e. increase
100 =
61%
65
fig 8.7
8.Commissioning
Tests
fig 8.8
The over current relays can be checked using an over current
test set. Alternatively a test setup as shown in the fig 8.8 may be used.
While checking over current relays care should be taken to avoid
excessive currents flowing through the coil for a long time to avoid
excessive heating.
Instantaneous over current relays are checked for minimum
current required for operation (pick-up) of the relay and maximum
8.Commissioning
Tests
current at which the relay resets (drop-off) for each current setting of the
relay.
Definite time over current relays are first checked for pick-up
and drop-off as detailed above with timer setting at zero. Then the time
delay should be checked at 1.3 times (approx.) the current setting.
For inverse time over current relays the follow ing checks
should be performed.
1) Check that starting current ( i.e. the current at which the disc just
begins to move but does not completes its travel to close the
contact.) is within specified limits.
2) Check that the closing current ( i.e. the minimum current at which
at which the disc completes its travel to close its contact) is
within its limits.
3) Check the operating time of the relay at 2,5,10 times the current
setting (plug setting ). These times should be within the tolerance
limits. (For electronic and numerical relays the checking of
starting and closing current does not arise.
Differential relays :
The sensitivity of the differential relay can be checked using a
over current test set as described below:
fig 8.9
fig 8.10
While checking unbiased differential relay the current setting
should be checked by slowly raising the current until the relay pickup.
8.Commissioning
Tests
This should be checked for all the setting and finally for the required
setting.
The biased differential relay can be checked with the over
current test set by inject ing current simultaneously to the operating coil
and the bias coil as shown in fig8.10 above, at different points of the
bias characteristic by adjusting the rheostats R1 and R 2. Record the
operating currents for different values of bias current. The ratio of the
operating current A1 to the through current A2 is approximate to the
value of the bias slope of the relay.
The relative value of the resistor R 2 and R 1 should roughly the
same as the ratio of the bias slope of the relay.
e.g. for bias slope of 30%, R2 /R1 = 0.3
To determine the position of the characteristic inject a current
of I2 Amps through R2 and adjust R1 until the relay operates.
Let the operating current be I1
I2 + ( I1 + I2 )
I1
Then the average bias
IB =
= I2 +
2
2
I1
Then the bias slope of the relay is
IB
Repeat the test for other values of currents to plot the curve.
8.Commissioning
Tests
fig 8.11
The current setting of the negative phase sequence relay is
usually expressed in terms of negative phase sequence currents. The
relay can be checked with over current test set. If the relay is provided
with an external filter current inject ion should be made before the filter.
The relay can be checked for phase to earth fault or phase to
earth fault simulation. If the relay is checked for phase to earth fault
simulation 1/3rd of the injected current is negative sequence current. If
the relay is checked for phase to phase fault simulation 1/3 times of the
injected current is negative sequence current.
For phase to earth fault simulation of a relay rated for 1amps
and I2s setting of 10%
10
I2s
= 1 = 0.1Amps
100
In order to obtain 0.1Amps negative phase sequence current a
test current of 3 0.1 Amps should be injected into each phase in turn.
Test current = 0.1 3 2 = 0.6 Amps.
The factor 2 is for two times the set current and the
factor 3 is for phase
to neutral simulation.
For phase to phase fault simulation of a relay rated for 5amps
and I2s setting of 7.5%
8.Commissioning
Tests
7.5
5 = 0.375Amps
100
In order to obtain 0.375Amps negative phase sequence current,
a test current of 3 0.375 Amps should be injected into each pair of
phase in turn.
Test current = 0.375 3 4 = 2.6 Amps.
The factor 4 is for four times the set current and the
factor 3 is for phase to phase
simulation.
I2s
Directional relays :
8.Commissioning
Tests
fig 8.12
The directional characteristic and maximum torque angle of
many relays can be checked with a phase shif ting transformer as shown
in the fig8.12. The phase shif ting transformer permits the phase angle of
the relay voltage to be varied with respect to the relay current. Adjust
the current flowing through the relay current coil to correspond to rated
current and the applied voltage to the voltage coil corresponds to the
rated voltage. Rotate the phase shif ter till the phase angle meter reads
zero degree (unity PF). Check the relay is in operated position. If not
reverse the voltage or current connection and check the operation of the
relay at UPF. Rotate the phase shif ter in the clockwise direction until the
relay contact opens and then rotate back in the anti clockwise direction
and note the phase angle meter reading 1,when the relay contact just
close. Continue to rotate in the anti clockwise direction till the relay
contact open again, then rotate backwards in clockwise direction and
note the phase angle meter reading 2, when the contact just close. The
maximum torque angle line of the relay is given by the bisector of 1
2 and the angle between this line and the zero degree line (UPF)gives
the maximum torque angle of the relay which should be within 4 of
the declared maximum torque angle (MTA).
8.Commissioning
Tests
fig 8.13
Distance relays:
Distance relay s are required to measure impedance accurately
over a wide range of current and voltages. The impedance measurement
of these relays can be checked using a phase shif ting transformer
explained earlier for checking directional relays. These equipment
measures the impedance at static conditions i.e. the current increased
slowly or the voltage is decreased slowly until the relay operates. While
testing high speed distance relays, it is important to apply simulated
fault conditions suddenly, because during the fault condition the relay
voltage falls suddenly from nominal voltage to fault voltage and the
current from the load value to fault value accompanied by changes in
phase angles. So in order to check the distance relays under dynamic
condition most of the manufacturers of relay have developed dynamic
test set. The basic principle of operation of the dynamic test set is as
detailed below:
8.Commissioning
Tests
fig 8.14
Normal working voltage is applied to the relay through a
voltage auto transformer. When the fault contactor is closed the fault
current If is applied to the relay. At the same instant the voltage applied
to the relay collapses to the fault voltage VL. The magnitude of the fault
voltage VL depends on the ratio of the source impedance to line
impedance (Zs / Z L). The voltage auto transformer has 10%and 1%
tapings to allow the line impedance Z L to be matched to the relay ohmic
setting. By varying the source impedance Z S the relay ohmic setting can
be checked over a wide range of voltage and current magnitudes.
Usually the distance relay ohmic setting is checked at actual
line angle. For this a choke and resistance with tapping of the line
impedance Z L are provided. Angles other than line impedance angles
may be chosen for checking the characteristic of mho or reactance relays .
The points usually checked on the mho and reactance relay
characteristic are shown in fig 8.15.
8.Commissioning
Tests
fig 8.15
P rimary injection tests :
Over current and earth fault relays :
The sensitivity of the over current relays can be checked by
phase to phase inject ion. Phase to phase inject ion is explained earlier in
CT ratio and polarity checks. For checking earth fault relays single
phase inject ion should be used as shown in fig8.16.
8.Commissioning
Tests
Directional relays :
The directional feature of the directional over current, earth
fault, distance and other wattmetric relays can be checked by the use of
load current.
The phase fault directional over current relays can be checked
by use of load current when the load current is appreciable and the
direction is in no doubt. The relay contact should close in the operating
direction and open in the reverse direction. The direction of the current
to the relay can be reversed by cross connecting the voltage or current
leads to the relay through the test plug as shown in fig 8.17.
fig 8.17
Earth fault over current relays are usually fed from broken delta
voltage of the three phase voltage transformer and residual current of the
main current transformers. Under normal condition the relay is not
energized, so it is necessary to simulate the earth fault condition. With
one phase of the voltage transformer disconnected and short circuited
while the current transformers of the other two phases disconnected
and short circuited as shown in fig8.18, simulates a condition of earth
fault on the phase from which voltage is disconnected. The relay should
operate when the load current flows in the operating direction.
8.Commissioning
Tests
fig 8.18
Mho relays can be made to operate with load current flowing in
the operating direction by removing the restraint voltage from the relay.
In most modern distance relays a convenient switch link or plug is
provided o the relay to facilitate this test. The removal of the restraint
voltage from the mho relay changes the mho circle characteristic into a
plain directional characteristic with the same characteristic angle as
shown in the fig8.19.
fig 8.19
With lagg ing current flowing in the operating direction the relay will
operate a soon as the restraint voltage is removed. The relay should be
8.Commissioning
Tests
then checked for non operation for load flow in the opposite direction.
This can be done by inserting a test plug with crossover connection of
the current transformer leads as shown in the fig 8.20 to reverse the
current flow to the relay.
fig 8.20
differential protection :
Generator
Generatordifferential
The sensitivity of this type of differential scheme can be
checked by primary inject ion test as shown in the fig 8.21.
8.Commissioning
Tests
fig 8.21
Primary current is passed through one of the main CT and
slowly raised until the relay operates. This gives the true operating
current necessary in the primary to cause operation, that includes the
magnetizing current of the CT shunting the relay. the voltage across
the relay coil and stabilizing resistance should also be measured at the
time of operation of the relay to check the voltage developed by the
main CT that causes the relay operation. The sensitivity check should be
carried out by inject ing through the CT primary of each phases in turn to
check all units of the relay.
Another method of checking the sensitivity is by use of
machine itself to supply the primary current by carefully controlling the
machine excitation from a low value to the required primary current. For
this the main circuit breaker is left open and a three phase short circuit is
provided in the generator link cubicle to simulate an internal fault as
shown in fig 8.22.
8.Commissioning
Tests
fig 8.22
The machine is then run up to full speed and the excitation is raised
slowly until the three elements of the relay operates. The suitability of
this type of checking depends on the type of excitation and degree of
control available.
The stability of the generator differential protection can be
checked by providing a short circuit at the bus side of the generator
circuit breaker as shown in fig8.23.
8.Commissioning
Tests
fig 8.23
The circuit breaker should be closed and excitation of the machine
raised until full load current is circulated in the primary circuit. The
operating coil of the relay should be short circuited and an ammeter of
twice the rated current of the CT should be used initially until the
correct polarity of the CT is confirmed. Wrongly connected or open
circuited CT will produce higher spill current reading in the ammeter. If
the ammeter reads very little current when circulating full load in the
primary circuit, the ammeter may replaced with a higher sensitive meter
to measure the spill current which will in the order of milli-amperes.
The stability of motor and generator protection can be checked
by primary injection as detailed below :
fig 8.23(a)
Current injected through R & y phases as shown in fig 8.23(a)
keeping the R & Y windings short circuited. While primary current is
flowing, the relay should maintain stability and the reading of the
ammeters should read few milli-amps only. Wrongly connected or
open circuited CT will produce higher spill currents. It is advisable to
short circuit the relay coils and stabilizing resistors throughout the test.
Repeat the test for Y & B and B & R phases to confirm the stability in
all the phases.
8.Commissioning
Tests
T rans
former biased differential protection :
ransformer
The sensitivity of the relay can be checked with a single phase
primary injection test set as described for generator differential
protection. The test can also be carried out by inject ing current through
one CT to simulate earth fault or two CTs to simulate phase fault as
shown in fig 8.24 & 8.25.
fig 8.24
8.Commissioning
Tests
8.Commissioning
Tests
fig 8.26
If there is no machine available to circulate full load current
through the transformer, connect the transformer to the local bus bars
that have voltage rating of approximately 5% to 12% of one of the
winding. The transformer short circuit impedance must be known in
order to calculate the bus-bar voltage required to circulate full load
current. If both the above possibility is not available of protection can be
checked when the transformer is first put in load.
When the load current flowing through the transformer winding
the protective relay should remain stable and the spill current in the
operating coil of the relay should be very small, provided the CT ratios
associated with each winding of the transformer are chosen correctly
and the transformer tap changer is at the nominal tap. Measure the spill
current through the relay during the load test with the tap changer at its
maximum and minimum tap. This spill current expressed as a
percentage of load current indicates the minimum amount of bias of
the relay required to maintain stability for through faults. If the relay
operates on load with the bias set correctly, the circuit diagram should
be checked for correct CT connection according to the vector group of
the transformer being protected. The possible errors in diagram or actual
wiring and the respective spill current are tabulated below.
8.Commissioning
Tests
POSSIBL E ERRORS
1
2
3
4
5
R
2I
3I
I
Y
2I
3I
3I
I
B
2I
3I
3I
I
2I
PILOT
CURRENT
S
R Y B
I
I
I
I
I
I
I
I
I
I
I
I
I
OPERATING
CURRENTS
Sensitivity check
fig 8.27
8.Commissioning
Tests
Stability check
fig 8.28
While carrying out this test measure the voltage developed across the
relay coil and stabilizing resistance so as to check the voltage by the
main CT to relay operation.
The stability of the REF protection can be checked by inject ing
current through the neutral CT and each phase CT in turn as shown in
fig8.28. If the protection is combined with differential protection the
connection to the differential relay should be short circuited. While
primary current is flowing the relay should maintain stability and the
reading in ammeter connected in series with the relay coil should be few
milliamperes only. It is advisable to short circuit the relay coil and the
stabilizing through the test.
8.Commissioning
Tests
fig 8.29
NPS relays are usually calibrated in NPS currents only. To check the
relay for phase to phase fault simulation, inject 3 times the setting
current
i.e. 1/3 times the injected current is the negative phase
sequence current.
To test the relay at four times the set current for a NPS setting
of 7.5% and a CT ratio of 1000/5A with phase to phase fault
simulation, inject a primary current of
7.5
1000 3 4
i.e. 520 Amps.
100
For phase to earth fault simulation the same test current should be
7.5
1000 3 4
i.e. 900 Amps.
100
The relay should also be checked for load test when it is first put on
service. When the load is balanced and phase sequence of the current
supplied to the relay is correct, the relay should not operate. To confirm
the relay for operation on NPS current, two of the main CT inputs to the
relay should be transposed. This can be done by either using a test plug
inserted into the relay or by reconnecting the leads too the terminals of
the relay. in this case all the phase current entering the relay is NPS
current and the relay will operate if the current is above the set current.
8.Commissioning
Tests
Bus-bar protection :
In bus-bar protection scheme all the current transformers are
connected to form a circulating current scheme. So the ratios of al the
CTs should be same and connected with correct polarity. The polarity
and ratio of the bus-bar protection scheme can be checked by choosing
one CT circuit as reference after checking its ratio and polarity and use
it to check the remaining CT circuits.
To check the polarity and ratio of the reference CT provide a
short in the bus-bars as shown in fig 8.30.
fig 8.30
Inject current through R and Y phase of the bus-bars. The ratio
of the ammeter reading A1 to that of A2 should approximate to the ratio
marked on the CT name plate. The ammeter A3 connected in the neutral
test link will read a few milliampere if the CT polarity is correct.
Reading A3 twice that of A2 shows wrong polarity. Repeat the test with
current inject ion in Y and B phases bus-bars. During the test the
operating coil of the relay and stabilizing resistance should be short
circuited to avoid overheating as they are not continuously rated. A
convenient way to do this is by manually operating the supervision
relay which in turn short circuit the bus- wires. If the scheme of
8.Commissioning
Tests
duplicate bus bar type in the CTs are switched between the main and
reserve bus wires by isolator auxiliary switches, then it is advisable to
carryout the test with bus bar isolators in both the position in order to
check the wiring.
After checking the ratio and polarity of the reference CTs, the
other CTs can be checked against the reference CT. This is carried out
by providing a temporary short circuit on the test circuit and inject ing a
primary current in R & Y phases of the reference circuit as shown in the
fig 8.31
fig 8.31
The ammeter A2 provide the ratio check and A3 check the polarity as
explained earlier. Repeat the test with current inject ion in Y & B phases.
If the scheme is a duplicate bus bar type the test should be carried out
with the bus bar isolators in both the positions to check the wiring.
The sensitivity of the bus bar protection relay can be checked
by passing single phase primary current through one CT only as shown
in fig 8.32 and measuring the current necessary to cause operation of the
8.Commissioning
Tests
fig8.32
circulating current relay with maximum number of CTs in id le shunt.
If the scheme provided with an overall check feature, the sensitivity of
this can be checked in the same manner and at the same time. The
sensitivity check should be carried out for each discriminating zone. A
voltmeter should be connected across the relay coil and stabilizing
resistor in order to check the correctness of value of stabilizing resistor.
Table 1
Relay location
D
C
B
A
Total impedance
in Z pu
Min
Max
Max
Min
0.1013
0.0815
0.0065
0.0029
0.2795
0.1013
0.0815
0.0065
17268
21466
269160
603292
6257
17268
21466
269160
Total load
current at
3.3KV
base
CT.
Ratio
CT. Ratio
to the
base of
33kv
percent
700
1500
6000
20000
250/5
500/5
150/1
500/1
833/5
1666.6/5
6000/1
20000/1
100
100
100
100
primary
current at
3.3kv base
833
1666.6
6000
20000