IEC 60127-1 - Definitions For Miniature Fuses and General Requirements For Miniature Fuse-Links
IEC 60127-1 - Definitions For Miniature Fuses and General Requirements For Miniature Fuse-Links
IEC 60127-1 - Definitions For Miniature Fuses and General Requirements For Miniature Fuse-Links
CONTENTS
FOREWORD ........................................................................................................................... 3
Bibliography .......................................................................................................................... 27
MINIATURE FUSES –
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60127-1 has been prepared by subcommittee 32C: Miniature
fuses, of IEC technical committee 32: Fuses.
This second edition cancels and replaces the first edition (1988), together with amendment 1
(1999) and amendment 2 (2002), and constitutes a technical revision.
The major technical changes with regard to the first edition concern subclause 9.2.3 where
the nature of the current source has been clarified; in addition, IEC 60038: I EC standard
voltages, has been added to the list of normative references.
–4– 60127-1 IEC:2006(E)
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This Part 1 of the IEC 60127 series covers definitions, general requirements and tests
applicable to all types of miniature fuses (e.g. cartridge fuse-links, sub-miniature fuse-links
and universal modular fuse-links). All subsequent parts of the complete series should be read
in conjunction with this Part 1.
IEC 60127 consists of the following parts, under the general heading Mi ni ature fuses:
Part 1: Definitions for miniature fuses and general requirements for miniature fuse-links
Part 2: Cartridge fuse-links
Part 3: Sub-miniature fuse-links
Part 4: Universal modular fuse-links (UMF) – Through-hole and surface mount types
Part 5: Guidelines for quality assessment of miniature fuse-links
Part 6: Fuse-holders for miniature fuse-links
Part 7: (Free for further documents)
Part 8: (Free for further documents)
Part 9: (Free for further documents)
Part 10: User guide for miniature fuses
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
MINIATURE FUSES –
This part of IEC 60127 covers the general requirements and tests applicable to all types of
miniature fuse-links (e.g. cartridge fuse-links, sub-miniature fuse-links and universal modular
fuse-links) for the protection of electric appliances, electronic equipment and component parts
thereof normally intended to be used indoors.
Specific details covering each major subdivision are given in subsequent parts.
This standard does not apply to fuses for appliances intended to be used under special
conditions, such as in a corrosive or explosive atmosphere.
2 Normative references
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
3.1
fuse
device that, by the fusing of one or more of its specially designed and proportioned
components, opens the circuit in which it is inserted by breaking the current when this
exceeds a given value for a sufficient time
NOTE The fuse comprises all the parts that form the complete device.
–6– 60127-1 IEC:2006(E)
3.2
miniature fuse
fuse in which the fuse-link is a miniature fuse-link
3.3
fuse-link
part of a fuse including the fuse-element(s) intended to be replaced after the fuse has
operated
3.4
enclosed fuse-link
fuse-link in which the fuse-element is totally enclosed, so that during operation within its
rating it cannot produce any harmful external effects, e.g. due to development of an arc, the
release of gas or the ejection of flame or metallic particles
3.5
miniature fuse-link
enclosed fuse-link of rated breaking capacity not exceeding 2 kA and which has at least one
of its principal dimensions not exceeding 10 mm
NOTE Principal dimensions are length, width, height and diameter.
3.6
sub-miniature fuse-link
miniature fuse-link of which the case (body) has no principal dimension exceeding 10 mm
NOTE Principal dimensions are length, width, height and diameter.
3.7
universal modular fuse-link
miniature fuse-link primarily adapted for direct electrical connection to printed circuit boards
or other conductive substrates, incorporating features designed to provide a degree of non-
interchangeability where necessary
3.8
fuse-link contact
conductive part of a fuse-link designed to engage with a fuse-base contact or with a fuse-
carrier contact
3.9
fuse-holder
combination of a fuse-base with its fuse-carrier
3.10
fuse-base
fuse-mount
fixed part of a fuse provided with contacts and terminals for connection to the system
3.11
fuse-base contact
fuse-mount contact
conductive part of a fuse-base, connected to a terminal designed to engage with a fuse-
carrier contact or with a fuse-link contact
3.12
fuse-carrier
movable part of a fuse designed to carry a fuse-link
60127-1 IEC:2006(E) –7–
3.13
fuse-carrier contact
conductive part of a fuse-carrier connected to a fuse-link contact and designed to engage with
a fuse-base contact
3.14
fuse-element
part of the fuse-link designed to melt when the fuse operates
3.15
homogeneous series (of fuse-links)
series of fuse-links, deviating from each other only in such characteristics that, for a given
test, the testing of one or a reduced number of particular fuse-links of the series may be taken
as representative of all the fuse-links of the series
NOTE Fuse-links are considered as forming a homogeneous series when the characteristics comply with the
following:
– the bodies have the same dimensions, material and method of manufacture;
– the caps or other end closures of the body have the same dimensions, materials and method of attachment and
sealing;
– the granular filler, if any, of the body is of the same material and completeness of filling. It should be of the
same size or any variation of the grain size with current rating should be monotonous;
– the fuse-elements are of the same material with the same principles of design and construction; any changes of
fuse-element dimensions with current rating should be monotonous;
– the rated voltage is the same;
– for low-breaking capacity fuse-links it is only necessary to test the highest rated breaking capacity in a
homogeneous series.
3.16
rating
general term employed to designate the characteristic values that together define the working
conditions upon which the tests are based and for which the fuse is designed
Examples of rated values usually stated for fuses:
− voltage (U N );
− current (I N );
− breaking capacity.
3.17
time/current characteristics (of a fuse-link)
a) For a.c.: curve giving, under stated conditions of operation, the value of time expressed as
virtual time as a function of the prospective symmetrical current, expressed as the r.m.s.
value
b) For d.c.: curve giving, under stated conditions of operation, the value of time expressed as
actual time as a function of the d.c. prospective current
NOTE Time/current characteristics usually stated for a fuse-link relate to the pre-arcing time and the operating
time.
3.18
conventional non-fusing current
value of current specified as that which the fuse-link is capable of carrying for a specified time
(conventional time) without melting
3.19
prospective current (of a circuit and with respect to a fuse)
current that would flow in a circuit, if a fuse situated therein were replaced by a link of
negligible impedance
–8– 60127-1 IEC:2006(E)
3.20
pre-arcing time (melting time)
interval of time between the beginning of a current large enough to cause a break in the fuse-
element and the instant when an arc is initiated
3.21
arcing time
interval of time between the instant of the initiation of the arc and the instant of final arc
extinction
3.22
operating time (total clearing time)
sum of the pre-arcing time and the arcing time
3.23
virtual time
value of I 2 t divided by the value of the square of the value of the prospective current
NOTE The values of the virtual times, usually stated for a fuse-link, are the values of the pre-arcing time and of
the operating time.
3.24
I 2 t (joule integral)
integral of the square of the current over a given time interval:
t
I²t = ∫i
2
dt
t =0
NOTE 1 The pre-arcing I 2 t is the I 2 t integral extended over the pre-arcing time of the fuse.
NOTE 2 The operating I 2 t is the I 2 t integral extended over the operating time of the fuse.
NOTE 3 The energy in joules released in 1 Ω of resistance in a circuit protected by a fuse is equal to the value of
the operating I 2 t expressed in A 2 s.
3.25
breaking capacity of a fuse-link
value (r.m.s. for a.c.) of prospective current that a fuse-link is capable of breaking at a stated
voltage under prescribed conditions of use and behaviour
3.26
recovery voltage
voltage which appears across the terminals of a fuse after breaking of the current
NOTE This voltage may be considered in two successive intervals of time, one during which a transient voltage
exists, followed by a second one during which the power frequency or the steady-state recovery voltage exists.
3.27
maximum sustained dissipation
power dissipation of a fuse-link measured under prescribed conditions of measurement at the
maximum current level that can be sustained for a minimum of 1 h
NOTE 1 The figure for maximum sustained dissipation is used in connection with the maximum power acceptance
of fuse-holders for miniature fuse-links in accordance with IEC 60127-6.
NOTE 2 These values are often exceeded for short periods of time immediately before the fuse-element melts.
Values as high as twice the maximum sustained dissipation have been recorded.
60127-1 IEC:2006(E) –9–
4 General requirements
Fuse-links shall be so constructed that they are reliable and safe in operation and consistent
in performance at any current up to and including the breaking capacity rating and at any
voltage up to the rated voltage, when used within the limits of this standard.
During normal use of the fuse-link and within the conditions given in this standard, no
permanent arc, no external arcing, nor any flame that can endanger the surroundings, shall
be produced. During the test for establishing the maximum sustained dissipation and after
operation, the fuse-link shall not have suffered damage hindering its replacement and the
marking shall still be legible.
5 Standard ratings
– rated voltage,
– rated current,
– rated breaking capacity.
6 Marking
Unless otherwise stated in subsequent parts, the requirements for marking are as follows:
a) Rated current in milliamperes for rated currents below 1 A, and in amperes for rated
currents of 1 A or more. The marking of the rated current shall precede and be adjacent to
the marking of the rated voltage.
To accommodate existing practice in some countries, for the time being, the current may
also be indicated in fractions of ampere.
b) Rated voltage in volts (V).
c) Maker's name or trade mark.
d) A symbol denoting the relative pre-arcing time/current characteristic as given in the
relevant standard sheet. This symbol shall be placed before and adjacent to the rated
current.
These symbols read as follows:
FF: denoting very quick acting
F: denoting quick acting
M: denoting medium time-lag
T: denoting time-lag
TT: denoting long time-lag.
– 10 – 60127-1 IEC:2006(E)
Compliance is checked by inspection and by rubbing the marking by hand for 15 s with a
piece of cloth soaked in water and again for 15 s with a piece of cloth soaked in petroleum
spirit.
NOTE 1 For petroleum spirit the use of an aliphatic solvent hexane, with an aromatics content of maximum 0,1 %
volume, a kauri-butanol value of 29, initial boiling point approximately 65 °C, dry-point approximately 69 °C and
specific gravity of approximately 0,68 is recommended.
NOTE 2 In the case of colour coding, the test for indelibility need not be applied.
6.3 The marking according to 6.1 shall be printed on the packing together with a reference to
this standard and an indication of the appropriate standard sheet. The marking on the packing
shall include the abbreviation A and mA.
6.4 Further identification of the current rating and the time/current characteristics by means
of colour bands may be used.
It is recommended that where acceptance tests are required, they are chosen from the type
tests in this standard.
7.1.1 Unless otherwise specified in subsequent parts, all tests shall be carried out under the
following atmospheric conditions:
Where the above-mentioned conditions have a significant influence, they shall be kept
substantially constant during the tests.
Fuse-links shall be tested in the specified bases in free air, and be protected from draughts
and direct heat radiation. The position of the fuse-holder shall be horizontal.
If temperature has a marked effect on the results of the tests, these shall be performed at a
temperature of 23 °C ± 1 °C.
7.1.2 In every test report, the ambient temperature shall be stated. If the standard conditions
for relative humidity or pressure are not fulfilled during tests, a note to this effect shall be
added to the report.
Where tests are required at elevated temperatures, these tests shall be carried out at an
ambient temperature of 70 °C ± 2 °C, unless otherwise specified.
60127-1 IEC:2006(E) – 11 –
7.2.2 Based on the results of the test in item d) above, the fuse-links shall be sorted in
descending order of voltage drop, and numbered consecutively, lower numbers being
allocated to the fuse-links having the highest voltage drop. Tests from these fuse-links shall
then be made in accordance with the relevant testing schedule.
If a test is to be repeated, spare fuse-links having approximately the same voltage drop as the
original fuse-links shall be used for the repeat test.
7.2.3
a) No failure is allowed in any of the tests covered by Clauses 6 and 8, nor those described
in 9.1, 9.2.2 and 9.7 and such additional clauses and subclauses as shall be specified in
subsequent parts.
b) If in the tests covered by 9.2.1 and 9.3, two failures occur at any one current, the fuse-
links are deemed not to comply with this standard. If, however, one failure occurs, the test
shall be repeated on twice the number of fuse-links, at the same current and a second
failure shall be a cause for rejection.
If two failures occur, but not both in the same test, the fuse-link shall be deemed to comply
provided that there are no further failures in repeat tests with twice the number of fuse-
links.
If more than two failures occur, the fuse-link shall be deemed not to comply with this
standard.
c) In each of the tests according to 9.4, 9.5 and 9.6, one failure is allowed. If two or more
fuse-links fail in any one test, the fuse-links are deemed not to comply with this standard,
unless otherwise specified in subsequent parts.
For tests that require a fuse-base for mounting the fuse-links, a base according to the
requirements specified in subsequent parts shall be used.
The nature of the supply for the electrical tests is specified in the relevant clauses or in the
relevant standard sheets in subsequent parts.
For a.c., the test voltage is of substantially sinewave form with a frequency between 45 Hz
and 62 Hz.
– 12 – 60127-1 IEC:2006(E)
8.1 Dimensions
The dimensions of the fuse-links shall comply with the relevant standard sheet, given in
subsequent parts.
8.2 Construction
The fuse-element shall be completely enclosed. Further details of the construction are given,
as appropriate, in subsequent parts.
8.3 Terminations
Nickel or silver plating is deemed to be adequate protection for brass end caps.
Tests for firm attachment are given, where appropriate, in subsequent parts.
Appropriate tests for alignment or position of pins, etc., as applicable, are given in subsequent
parts.
Externally visible soldered joints (e.g., on end caps) shall not melt during normal use and
operation.
Compliance is checked by inspection of the soldered joints after the tests described in 9.2.1,
9.2.2, 9.4, 9.5 and 9.6.
9 Electrical requirements
The voltage drop across the fuse-links at their rated current shall not exceed the maximum
values given on the relevant standard sheet.
Individual values shall not deviate from the mean value determined for the model under test
during type tests by more than 15 %.
NOTE 1 Attention is drawn to the fact that the second paragraph is based on the assumption that the fuse-links,
which are submitted to a type test, belong to the same manufacturing batch. Where samples are drawn at random,
the condition for the permitted deviation from the mean value need not be fulfilled. If, due to the Peltier effect,
different voltage drops are measured when the current through the fuse-link is reversed, the highest value shall be
taken.
Compliance is checked by measuring the voltage drop when the fuse-link has carried its rated
current for a time sufficient to reach temperature stability.
Direct current shall be used for this test; equipment shall be used which does not influence
the result of the test significantly.
60127-1 IEC:2006(E) – 13 –
Temperature stability is considered to be reached when the voltage drop changes by less
than 2 % of the previously observed value per minute. During this test, the current through the
fuse-link shall not deviate by more than ±1 % from the rated current and the accuracy of the
voltage drop measurement shall be within a tolerance of ±1 %.
NOTE 2 Problems can arise when fuse-links are used at voltages considerably lower than their rated voltage,
mainly for low ratings. Due to the increase of the voltage drop when the element of a fuse-link approaches its
melting point, care should be taken to ensure that there is sufficient circuit voltage available to cause the fuse-link
to interrupt the current when an electrical fault occurs. Furthermore, fuse-links of the same type and rating may,
due to difference in design or element material, have different voltage drops and may therefore not be
interchangeable in practice when used in applications with low circuit voltages, especially in combination with fuse-
links of lower rated currents.
The time/current characteristic shall be within the limits specified in the relevant standard
sheets.
Compliance is checked by measuring the pre-arcing time under the atmospheric conditions
mentioned in 7.1.
The current through the fuse-link shall be adjusted to within ±1 % of the required value.
The current stability during the test shall be maintained within ±1 % of the adjusted value. The
voltage of the source shall not exceed the rated voltage of the fuse-link under test.
The accuracy of the measurement of time shall be within a tolerance of ±5 % for times of less
than 10 s and ±2 % for times of 10 s or more.
In the case of very short pre-arcing times at high levels of the current where constant current
no longer can be maintained, the I 2 t value should be measured and the virtual time be
calculated.
When specified on the standard sheet, fuse-links shall also be tested for 1 h at an ambient
temperature and with the multiple of the rated current as specified on the relevant standard
sheet.
The current stability during the test shall be maintained within ±2,5 % of the adjusted value.
The fuse-link shall not operate.
The output voltage of the current source shall be sufficient to limit the variation of current
during the pre-arcing time. Additionally, the output voltage shall not exceed a value declared
by the manufacturer and chosen from the list of d.c. voltages in Table 6 of IEC 60038.
The time constant of the circuit shall not exceed 3 % of the pre-arcing time.
Where there is a possible influence of the Peltier effect, care should be taken to reverse the
direction of the current passing through the fuse-link for each successive sample.
NOTE 3 Where the influence of the Peltier effect is essentially due to the construction, the time/current
characteristic should be tested with twice the number of fuse-links at 2,0 I N or 2,1 I N . The additional samples may
be taken from the spare fuse-links.
– 14 – 60127-1 IEC:2006(E)
Attention is drawn to the fact that, for certain types of fuse-links, the time/current
characteristic with a.c. can be significantly different from the characteristic determined with
d.c. and particularly with currents just exceeding the conventional non-fusing current.
Furthermore, it should be noted that due to the small thermal inertia of the fuse-elements for
low currents, the characteristic of the fuse-links may change considerably at very low
frequencies.
If the time/current characteristics with the current as independent variable are plotted, it is
preferred that they are presented with logarithmic scales on both co-ordinate axes. The basis
of the logarithmic scales shall be in the ratio 2:1 with the longer dimension on the abscissa.
If the multiple of the rated current is used as the independent variable, the ratio shall be 3:1.
NOTE Examples of such formats are given in Annex B.
Fuse-links shall operate satisfactorily without endangering the surroundings when breaking
prospective currents between the conventional non-fusing current and rated breaking capacity
in accordance with the relevant standard sheets in subsequent parts.
The recovery voltage shall be between 1,02 and 1,05 1 times the rated voltage of the fuse-
links and shall be maintained for 30 s after the fuse has operated.
For the breaking capacity test, the current shall be adjusted by changing the series
resistance.
The impedance of the a.c. source shall be less than 10 % of the adjusted value of the total
impedance of the applicable circuit.
NOTE 1 The breaking capacity may be lower with d.c. than with a.c. It is influenced by the circuit inductance and,
with a.c., additionally by the instant of closing the circuit.
NOTE 2 The d.c. value, if required by the purchaser or user, should be specified by the manufacturer.
More details of appropriate tests for the breaking capacity of each type of miniature fuse may
be found in the subsequent parts.
———————
1 This tolerance may be exceeded with the manufacturer’s consent.
60127-1 IEC:2006(E) – 15 –
In each of the tests, the fuse-link shall operate satisfactorily without any of the following
phenomena:
– permanent arcing;
– ignition;
– bursting of the fuse-link.
Additional criteria for satisfactory performance of individual types of miniature fuse-links are
given, where appropriate, in subsequent parts.
NOTE Changes in colour are not considered as a failure.
After the breaking capacity test, the insulation resistance between the fuse-link terminations
shall be measured with a d.c. voltage equal to twice the rated voltage of the fuse-link, but not
less than 250 V. The resistance shall be not less than 0,1 MΩ.
Fuse-links having the largest rated current shall be tested completely according to the
relevant testing schedule for the maximum ampere rating of a homogeneous series given in
the subsequent parts.
Fuse-links having the smallest rated current shall be tested according to the relevant testing
schedule for the minimum ampere rating of a homogeneous series given in the subsequent
parts.
Direct current shall be used for this test, unless otherwise specified in subsequent parts.
a) A current specified in the relevant standard sheet is passed through the fuse-link for a
period of 1 h. The current is then switched off for a period of 15 min. This cycle is
repeated 100 times.
The current stability during the test shall be maintained within ±1 % of the adjusted value.
The test should be run continuously, but where unavoidable, a single interruption is
permitted.
b) A current specified in the relevant standard sheets is then passed through the fuse-link for
1 h. At the end of this test the voltage drop across the fuse-link is measured and used for
the calculation of the maximum sustained power dissipation, where this is specified in
subsequent parts.
c) Finally, the voltage drop across the fuse-link is measured again according to 9.1. The
voltage drop across the fuse-link after the test shall not have increased by more than 10 %
of the value measured before the test.
d) After the test, the marking shall still be legible and soldered joints on end caps, for
example, shall not show any appreciable deterioration.
The values calculated from the measurement taken in accordance with 9.4 b) shall be within
the limits specified in the relevant standard sheet.
Where pulse tests are required in subsequent parts, they shall be performed as follows:
a) A current pulse specified in the relevant standard sheet is passed through the fuse-link
1 000 times at the repetition rate specified in the relevant standard sheet. The fuse-link is
then allowed to cool for at least 1 h at room temperature.
b) A current equal to the value specified in the relevant standard sheet is then passed
through the fuse-link for the time recommended on the relevant standard sheet.
c) Finally, the voltage drop across the fuse-link after the test is measured again according
to 9.1.
The voltage drop across the fuse-link after the test shall not have increased by more than
10 % of the value measured before the test.
d) After the test, the marking shall still be legible and soldered joints on end caps, for
example, shall not show any appreciable deterioration.
Where temperature tests are required in subsequent parts, they shall be performed as
follows:
The temperature rise, as measured at any location on the fuse-link enclosure or fuse-link
terminations, shall not exceed 135 K when the fuse-link is tested as follows:
NOTE 1 Due to the difficulty of specifying the location of the hottest point, it should be determined during the
initial 15 min.
NOTE 2 A thermocouple or other measuring methods that do not appreciably affect the temperature shall be used
to measure the temperature rise.
The test base for mounting and connection of the fuse-link shall be in accordance with 7.3.
60127-1 IEC:2006(E) – 17 –
Annex A
(informative)
Where colour bands are used for additional identification of the current rating and the
time/current characteristics, the following system shall be applied:
a) The miniature fuse-links specified in the relevant standard sheets are provided with four
colour bands, the first three identifying the rated current expressed in milliamperes and
the last, broader, colour band identifying the time/current characteristics.
b) The colour bands shall extend over at least half the circumference of the fuse body and
shall be evenly spaced and clearly separated as indicated in Figure A.1.
NOTE 1 In the case of transparent miniature fuse-links, the spacings still allow for the visibility of the fuse-
element.
c) The IEC standards with regard to colour coding practices, i.e. IEC 60062 and IEC 60425,
shall be used as far as applicable.
e) In addition to the requirements given in 6.3, it is recommended to print the relevant colour
coding of the contents on the packing also.
d d
d
s 2s
s s
IEC 1064/06
Annex B
(informative)
1 000
100
10
Current A
1
0, 1
0, 01
10 000
1 000
100
10
0,1
0,01
0,001
100 000
10 000
1 000
100
10
Time s
0,1
0,01
0,001
1 10 100
× IN IEC 1066/06
Annex C
(informative)
This annex contains instructions for audit testing and surveillance of fuse-links. The tests and
inspections described in this annex are optional. However, if they are carried out, it is
essential that the requirements for audit testing and surveillance are met.
C.2 Overview
This annex describes the obligations of the fuse-link manufacturers and the National
Certification Body (NCB) for audit testing and surveillance of fuse-link production.
It covers the preparation of the Conformity Assessment Report and the audit testing and
surveillance considered to be the minimum requirements of the NCB. Such inspections, tests
and measures are implemented by the NCB as an audit of the means that the manufacturer
exercises to determine the conformance of products with the requirements of the appropriate
parts of IEC 60127.
C.3.1
applicant
party who requests the conformity assessment, and controls the manufacturing of the product
C.3.2
conformity assessment
any activity concerned with determining directly or indirectly that relevant requirements are
fulfilled
C.3.3
significant sample
sample taken to be representative of a homogeneous series of fuse-links
C.3.4
Conformity Assessment Report
a document containing product and factory conformity assessment information issued by
Body A to the applicant
The part of the Conformity Assessment Report regarding product description shall identify
only those details of components and dimensions that have a major impact on the
– 22 – 60127-1 IEC:2006(E)
performance of the fuse-link. The following are examples of the type of details that may be
used to prepare the descriptive part of the Conformity Assessment Report:
a) fuse-element: material, thickness, and diagram of overall shape for every ampere rating;
b) time-delay section: defines general terms such as spring-loaded, solder slug, etc.; gives
details on fusing alloy material, dimensions and any other major components;
c) body: material and minimum wall thickness;
d) filler: generic description of filler material; grain size if applicable;
e) contacts: material and plating, method of securement, and key dimensions not covered
by overall dimension requirements;
f) miscellaneous: description of other components which have a major impact on the fuse-
link design and performance.
IEC 1067/06
Cylindrical fuse-links 20 mm long by 5 mm in diameter containing a wire element helically wound on a ceramic
core. The wire element is soldered to the contacts at each end of the fuse-link.
i. Contacts: cylindrical end caps of plated or unplated copper alloy with a minimum wall thickness of
0,25 mm.
ii. Core: ceramic.
iii. Fuse-element: wire helically wound on a supporting core.
Ampere rating: 6,3 A
Wire diameter: 0,40 mm
Basic material: copper alloy
Plating material tin
iv. Filler: quartz sand; grain size 100 µm to 300 µm.
v. Tube: glass with a minimum wall thickness of 0,50 mm.
vi. Miscellaneous items: none.
When the reduced sampling plan is used, the Conformity Assessment Report shall identify the
significant samples that are necessary for testing, chosen on the basis of their representation
of a homogeneous series. If a certain fuse-link rating requires no testing or only a partial test
programme due to similarities with another fuse-link which is already scheduled for tests, this
shall be noted.
60127-1 IEC:2006(E) – 23 –
The requirements of IEC 60127-1 and the relevant subsequent parts shall be applied for the
audit testing and surveillance, except where information in the Conformity Assessment Report
specifically overrides these requirements. Specific references are noted in Tables C.1 and
C.2.
Four programme options are available to verify the ability of the applicant to supply fuse-links
that continue to meet the requirements of the relevant part of IEC 60127. The applicant shall
choose one of these options. The programmes are not intended for combined use, though
different programmes may be chosen for different fuse-link series.
Option 1: a complete test programme according to the relevant part of IEC 60127 shall be
performed on every ampere rating of each fuse-link series. The complete programme shall
be repeated at 10 year intervals according to C.6.1 below.
Option 2: a complete test programme according to the relevant part of IEC 60127 shall be
per-formed on every ampere rating of each fuse-link series. The complete programme shall be
repeated at 10 years intervals, and the applicant's quality control system shall be utilized
according to C.6.2 below.
Option 3: a test programme which uses the homogeneous series (significant sample)
approach shall be performed according to C.6.3 below.
Option 4: a test programme which uses the homogeneous series (significant sample)
approach and the applicant’s quality control system shall be performed according to C.6.4
below.
A complete test programme according to the relevant part of IEC 60127 shall be performed on
every ampere rating of each fuse-link series. The complete programme shall be repeated at
10 year intervals. These audit tests may be witness testing, re-testing, TMP or SMT.
C.6.1.2 Surveillance
Routine inspection shall take place no less than once per year. The inspection shall review
each product for consistency with the product description in the Conformity Assessment
Report.
The NCB is required to assess the manufacturer’s quality system. In addition, the
manufacturer’s quality system shall be reviewed to ensure that it includes the surveillance
detailed below.
A complete test programme according to the relevant part of IEC 60127 shall be performed on
every ampere rating of each fuse-link series. The complete programme shall be repeated at
10 year intervals. These audit tests may be witness testing, re-testing, TMP, or SMT.
C.6.2.4 Surveillance
Routine inspection shall take place no less than once every two years. The inspection shall
review each product for conformance with the product description in the Conformity
Assessment Report. The inspection shall also comprise routine assessment of the operation
of the quality plan and the quality system.
The applicant shall record all routine tests required by the applicant’s quality system and
make these records available for verification and review on the NCB’s request.
The NCB shall inspect the results of all routine tests required by the applicant's quality system
every two years.
A test programme utilizing the homogeneous series (significant sample) approach shall be
performed.
A test programme according to the homogeneous series concepts of IEC 60127 shall be
performed on significant samples in accordance with the schedule shown in Table C.1. These
audit tests may be witness testing, re-testing, TMP, or SMT.
60127-1 IEC:2006(E) – 25 –
A Tested annually.
s Spare fuse-links, only used if non-conforming results are obtained.
C.6.3.2 Surveillance
Routine inspections shall take place no less than once per year. The inspection shall review
each significant sample for conformance with the product description in the Conformity
Assessment Report.
A test programme which uses the homogeneous series (significant sample) approach and the
applicant’s quality control system shall be performed.
The NCB is required to assess the manufacturer’s quality system. In addition, the
manufacturer’s quality system shall be reviewed to ensure that it includes the surveillance and
audit testing detailed below.
A test programme shall be performed in accordance with the schedule shown in Table C.2.
These audit tests may be witness testing, re-testing, TMP, or SMT.
– 26 – 60127-1 IEC:2006(E)
C.6.4.4 Surveillance
Routine inspections shall take place no less than once every two years. The inspection shall
review each significant sample. The inspection shall also comprise routine assessment of the
operation of the quality plan and the quality system.
The applicant shall record all routine tests required by the applicant’s quality system and
make these records available for verification and review on the NCB’s request.
The NCB shall inspect the routine test results every two years.
If more than one sample has non-conforming results during the audit testing, the fuse-link and
all represented fuse-links shall be rejected.
If a single non-conforming result is obtained for a particular test during the audit testing, a
second set of samples from the same lot shall be selected and subjected to the same test.
The second set shall have the same number of samples as the first set. If any non-conforming
results are obtained on the second set, the fuse-link and all represented fuse-links shall be
rejected.
If any non-conforming results are obtained during the surveillance, the NCB shall consult with
the manufacturer and applicant to determine whether the non-conformance is significant, and
whether corrections need to be made, or type testing performed.
60127-1 IEC:2006(E) – 27 –
Bibliography
IEC 60062:2004, Marki ng codes for resi stors and capaci tors
IEC 60425:1973, Gui de for the choi ce of colours to be used for the marki ng of capaci tors and
resi stors
IECEE 03:2005, Rules of Procedure of the Scheme of the I ECEE for Mutual Recogni ti on of
Conformi ty Assessment Certi fi cates accordi ng to Standards for Electri cal and Electroni c
Equi pment and Components (CBFCS)
_________
– 28 – 60127-1 IEC:2006(E)
FOREWORD
This amendment has been prepared by subcommittee 32C: Miniature fuses, of IEC technical
committee 32: Fuses.
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this publication will remain unchanged until
the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
___________
The voltage drop shall not have increased by more than 10 % of the value measured before
the test and shall not exceed the maximum value specified in the relevant standard sheet.
___________