Control Panel UNF
Control Panel UNF
Rev. Rev. Issued: 98-03-12 Rota Document Format Langue Page No. of pages
Rev. Rev. Check 1: 98-03-16GM
ZAB A4 E 1 22
Rev. Rev. Check 2:
Dept. 1 Dept. 2 Der.from/Repla.: Released: 98-03-16 GM
IAR
Replaced by:
3BHS102402 E82
Excitation System
UNITROL
F Series
Functional Description
Control Panel UNS 0874
2
Functional Description Control Panel UNS 0874
3BHS102402 E82
Contents Page
1 SAFETY REGULATIONS ......................................................................................................................... 3
1.1 Use of the control panel ..................................................................................................................................... 3
1.2 Personnel categories ......................................................................................................................................... 3
2 DEVICE DESCRIPTION............................................................................................................................ 4
2.1 Introduction ....................................................................................................................................................... 4
2.2 Display formats.................................................................................................................................................. 5
2.3 Function keys .................................................................................................................................................... 7
2.4 Operating modes ............................................................................................................................................... 8
2.4.1 Actual Signal Display Mode......................................................................................................................... 8
2.4.2 Parameter Mode ......................................................................................................................................... 8
2.4.3 Function Mode ............................................................................................................................................ 9
2.4.4 Device Selection Mode................................................................................................................................ 9
2.4.5 Start Mode .................................................................................................................................................10
3 OPERATING MANUAL........................................................................................................................... 11
3.1 Normal operation..............................................................................................................................................11
3.1.1 To display signals ......................................................................................................................................11
3.1.2 To display the fault logger ..........................................................................................................................12
3.1.3 Fault resetting............................................................................................................................................13
3.1.4 Device Selection.........................................................................................................................................14
3.1.5 Adjusting the display contrast.....................................................................................................................14
3.2 Local control of the excitation system................................................................................................................15
3.2.1 Field breaker- and excitation control ...........................................................................................................15
3.2.2 Selecting the operating mode (AUTO-MANUAL etc.) ..................................................................................16
3.2.3 Setting reference values.............................................................................................................................17
3.3 Commissioning and servicing ...........................................................................................................................18
3.3.1 Altering parameters....................................................................................................................................18
3.3.1.1 Altering language of the control panel ........................................................................................................18
3.3.2 Uploading and downloading of parameters.................................................................................................19
3.3.3 Connecting function block inputs ................................................................................................................22
3
Functional Description Control Panel UNS 0874
3BHS102402 E82
1 Safety regulations
1.1 Use of the control panel
The control panel is a very versatile device which, in addition to featuring simple functions
for local operation, also provides all the means of intervening the excitation system which
are required in order to carry out complete commissioning. Serious intervening of the
operating behaviour of voltage regulators, limits, protection and control is possible.
All modifications to the system are carried out by means of so-called parameter settings
and are described in section 3.3.1 (p. 18). This work may only be carried out by
trained commissioning and service personnel. This does not apply to the alteration of
reference values in local operation (see section 3.2.3, p. 17). If the operating mode "Pa-
rameter-setting" is unintentionally activated through operating error, the following instruc-
tions are to be followed:
[. . . .]
As soon as a value in square brackets appears, the "Parame-
ter" mode is activated and the parameter value will be changed
each time the arrow keys are pressed.
Do not press the ENTER key after an operating error. This
saves any changes.
In order to cancel a change and quit the "Parameter" mode,
press the ACT key.
1.2 Personnel categories
This document explains the use of the control panel in connection with local control of the
excitation system, as well as servicing and commissioning. It is not an operating manual
for the excitation system, nor is it an instruction manual for servicing and commissioning.
Before carrying out any work on the excitation system, the corresponding manuals are to
be consulted; in particular, it is essential that the safety regulations in the operating man-
ual (for the excitation system) and in the instructions on servicing and fault-location are
complied with.
Operating personnel
The operating manual (section 3) is divided into two parts, a general section for the oper-
ating personnel and a special section for the service and commissioning personnel. The
first section contains all the functions required for local control of the excitation system
such as display of actual values, display of faults and fault resetting. It is essential that
the operating personnel familiarise themselves with the contents of this section.
Commissioning and service personnel
The second part of the operating manual is intended as a reference work for this group of
persons. Individual settings can be carried out with reference to this manual. For more
complex work, including the commissioning of a system, we urgently recommend partici-
pation in a training course at our company or an intensive introduction by our commis-
sioning personnel when the system is commissioned for the first time.
4
Functional Description Control Panel UNS 0874
3BHS102402 E82
2 Device description
2.1 Introduction
This document describes the handling of the Control Panel UNS 0874 and its use in con-
nection with UNITROL
F devices for the local control of the excitation system and for
setting parameter values.
The panel has 16 membrane keys and an LCD display with 4 lines of 20 characters and
is approximately the size of a pocket calculator.
79.6
1
6
6
ENTER
ACT PAR FUNC
COM
SEL
REM
RESET REF LOC
0 I
UNITROL F
R
0 L 100.5 % II
MODE IND 1 AUTO
U MACH V 10500 V
I EXC A 16.5 A
Fig. 1 Control Panel UNS 0874
The control panel is linked with the UNITROL
F device.
These functions are called "upload" and "download".
Upload and download are used to copy a complete parameter set from one channel into
the second channel or into the UNITROL
F device, this value is limited to the set reference value range, e.g.
90 % to 110 % for the voltage regulator (AUTO).
18
Functional Description Control Panel UNS 0874
3BHS102402 E82
3.3 Commissioning and servicing
3.3.1 Altering parameters
Bedienungsschritt Taste resultierende Anzeige
1. To select parameter setting mode
PAR
1 L 0.0 % 00
3 CONTROL LOGIC
01 RELEASE FCB OFF
NO
2. To select the parameter group
oder
1 L 0.0 % 00
5 CONVERTER
01 U EXC V NOMINAL
350 V
3. To select the parameter
oder
1 L 0.0 % 00
5 CONVERTER
02 I EXC A NOMINAL
1000.0 A
4. To confirm the selection
The parameter value now appears
in square brackets
ENTER
1 L 0.0 % 00
5 CONVERTER
02 I EXC A NOMINAL
[1000.0 A]
5. To change the parameter value.
Use arrow keys for small changes.
Use double arrow keys for large
changes
1 L 0.0 % 00
5 CONVERTER
02 I EXC A NOMINAL
[1350.0 A]
6a.
6b.
Confirm new value
or
cancel the new setting by switch-
ing to a different display mode
ENTER
ACT PAR
FUNC
COM
SEL
1 L 0.0 % 00
5 CONVERTER
02 I EXC A NOMINAL
1350.0 A
1 L 0.0 % 00
5 CONVERTER
02 I EXC A NOMINAL
1000.0 A
It is essential to consult the Parameter and Signal List for the relevant software version in
order to determine the significance and consequences of parameter modifications. Per-
manent modifications are to be stored using the "Backstore mode" (see section 3.3.2, p.
21).
Some parameters are write-protected. If one attempts to al-
ter one of these values, this message appears on the dis-
play:
3.3.1.1 Altering language of the control panel
The language of the control panel can be alter with the parameter LANGUAGE (1215) in
the group MAINTENANCE. To alter parameter see the instruction before.
**WARNING**
WRITE ACCESS DENIED
PARAMETER SETTING
NOT POSSIBLE
19
Functional Description Control Panel UNS 0874
3BHS102402 E82
3.3.2 Uploading and downloading of parameters
UPLOAD
UNITROL F
1 L 104. 5 % I I
MODE I ND 1 A UTO
U MACH V 15000
I EX C A 147
Upload: All the parameters of the currently se-
lected device are copied into the control panel.
Uploading can be carried out while the machine is
running.
DOWNLOAD
UNITROL F
1 L 104. 5 % I I
MODE I ND 1 A UTO
U MACH V 15000
I EX C A 147
Download: Copies a complete parameter set
from the control panel into the currently selected
UNITROL