Cable PLC Panel
Cable PLC Panel
CHAPTER
CHAPTER
CHAPTER
In This Chapter...
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
DirectLOGIC PLCs Password Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
PLC Communication Cables & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .65
PLC Communication Cables & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .66
AutomationDirect PLCs RS-232C Serial: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
AutomationDirect PLCs RS-422A/RS-485A: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .610
Direct LOGIC Universal Isolated Network Adapter, p/n FA-ISOCON: . . . . . . . . . . .616
Direct LOGIC Universal Converter, p/n F2-UNICON: . . . . . . . . . . . . . . . . . . . . . . .617
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples . . . . . . . . . . . . . . . . . . . .618
Allen-Bradley: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .622
GE: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .627
GE VersaMax Micro: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .627
Mitsubishi: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .627
Omron: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .629
Modicon ModBus RS-232: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .630
Modicon Micro Series: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .630
Modicon ModBus with RJ45: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .630
Siemens: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .631
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
62
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Introduction
The C-more family of touch panels is capable of communicating with a wide variety of
Programmable Logic Controllers. C-more is capable of communicating over RS232, RS422 and
RS485 serial networks as well as Ethernet networks. It communicates with all
AutomationDirect PLC's utilizing various protocols. C-more also communicates with other
brands of PLCs by their different protocols. The table on the next page lists all of the various
PLCs and protocols that can be configured. The page after the protocol table lists the various
serial communication cables that are available to purchase. The rest of this chapter is devoted to
show the pin to pin connections of all the available cables plus wiring diagrams that the user can
refer to in order to construct their own cables, along with wiring diagrams of cables that are not
available for purchase. To simplify RS422/RS485 wiring schemes, we have included wiring
diagrams showing connections for available terminal connectors such as our ZIPLink
Communication Adapter Module, p/n ZL-CMA15, used for example with our DL-06 and D2-
260 PLCs and C-more D-Sub 15-pin to Terminal Block Adapter p/n EA-COMCON-3.
If you have difficulty determining whether the particular PLC and/or protocol you are using
will work with the C-more series of touch panels, please contact our technical support group at
770-844-4200
DirectLOGIC PLCs Password Protection
NOTE: Many DirectLogic PLCs support multi-level password protection of the ladder program. This allows
password protection while not locking the communication port to an operator interface. The multilevel
password can be invoked by creating a password with an upper case "A" followed by seven numeric
characters (e.g. A1234567). Please refer to the specific PLC user manual for further details.
C-more to
Direct LOGIC
VGA 15-pin port
serial cable
p/n EA-2CBL-1
DL-06 PLC
C-more
Touch Panel
Port 2
PLC Protocol & Cables
PLC Compatibility Table continued on the next page.
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
63
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Compatibility Table
Model Protocols
AutomationDirect
Productivity3000
P3000 Serial
P3000 Ethernet
CLICK Modbus (CLICK)
DL05/DL06
all
K-Sequence
Direct NET
Modbus (Koyo addressing)
H0-ECOM/H0-ECOM100 Direct LOGIC Ethernet
DL105 all K-Sequence
DL205
D2-230 K-Sequence
D2-240
K-Sequence
Direct NET
D2-250/D2-250-1/D2-260
K-Sequence
Direct NET
Modbus (Koyo addressing)
D2-240/D2-250-1/D2-260
Using DCM
Direct NET
Modbus (Koyo addressing)
H2-ECOM/H2-ECOM100 Direct LOGIC Ethernet
DL305
D3-330/330P (Requires the use of a Data Communications Unit) Direct NET
D3-340 Direct NET
D3-350
K-Sequence
Direct NET
Modbus (Koyo addressing)
D3-350 DCM
Direct NET
Modbus (Koyo addressing)
DL405
D4-430
K-Sequence
Direct NET
D4-440
K-Sequence
Direct NET
D4-450
K-Sequence
Direct NET
Modbus (Koyo addressing)
All with DCM
Direct NET
Modbus (Koyo addressing)
H4-ECOM/H4-ECOM100 Direct LOGIC Ethernet
H2-WinPLC (Think & Do) Live V5.2 or later and Studio any version Think & Do Modbus RTU (serial port)
H2-WinPLC (Think & Do) Live V5.5.1 or later and Studio V7.2.1 or later Think & Do Modbus TCP/IP (Ethernet port)
GS Drives
GS Drives Serial
GS Drives TCP/IP (GS-EDRV)
SOLO Temperature Controllers SOLO Temperature Controller
PLC Protocol & Cables (contd)
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
64
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
RD
SD
shield
Wiring Diagram
SD +
RD +
GND
TERM
SIGNAL GND
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
TXD / RXD
EA-COMCON-3
Terminal Block Adapter
plugs into C-more 15-pin
PLC Serial Comm. Port
TXD / RXD +
Productivity3000 PAC RS485 Port to EA-COMCON-3 Terminal Block Adapter
Productivity3000
PS485 Port
* 120 resistor
*
NOTE: The RS-485 wiring diagrams shown above are not for multi-drop networks involving connecting more
than one PLC to a panel. Refer to the wiring diagram examples starting on page 6-18 if more than one PLC
will be connected to a panel.
AutomationDirect Productivity PAC
RS-485
Removable Connector
included with
Productivity3000 CPU
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
Use 120 ohm resistors as termination resistors (Term.)
3
5
TXD+ / RXD+
Ground
9
11
5
1
RD+
SD+
shield
8 10
12
RD
SD
Term.
13
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
15 = do not use
14 = do not use
13 = Termination
12 = SD (RS485)
11 = SD+ (RS485)
10 = RD (RS485)
9 = RD+ (RS485) 1
15
15-pin
D-sub
(male)
To C-more Touch
Panel Serial Port2
+
-
G
Term.
TXD- / RXD-
TXD+ / RXD+
TXD- / RXD-
Ground
AutomationDirect PLCs RS-422A/RS-485A (contd):
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
615
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
C
T
S
+
R
T
S
R
X
D
R
X
D
+
T
X
D
T
X
D
+
G
N
D
DirectLOGIC
DL205 PLC
DirectLOGIC
DL06 PLC
HD = High Density
10 9 6 13 11 14 12 15
15-pin
HD D-sub
(male) 8 = do not use
7 = Sig GND
6 = RXD
5 = do not use
4 = do not use
3 = do not use
2 = do not use
1 = do not use
15 = CTS
14 = CTS+
13 = RXD+
12 = RTS-
11 = RTS+
10 = TXD
9 = TXD+
1
6
15
7
R
T
S
+
C
T
S
C
T
S
+
R
T
S
R
X
D
R
X
D
+
T
X
D
T
X
D
+
G
N
D
10 9 6 13 11 14 12 15
TXD+
TXD
Signal GND Signal GND
Typical RS-422 Multi-Drop Wiring Diagram
Port 2
Shielded Cable
Shielded Cable
To DL06 PLC port 2
Port 2
To D2-250-1 PLC port 2
RXD
RXD+
TXD+
TXD
RXD
RXD+
*
* Termination resistors required at both ends of the
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms).
(Slave)
(Slave)
(example device communicating
across RS-422 connection)
(example RS-422 connection)
(example device communicating
across RS-422 connection)
(example RS-422 connection)
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
619
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
S
D
+
R
D
R
D
+
G
N
D
10 9 12 11 13 1
Typical RS-422 Multi-Drop Wiring Diagram (contd)
Signal GND
HD = High Density
15-pin
HD D-sub
(male) 8 = do not use
7 = Sig GND
6 = RXD
5 = do not use
4 = do not use
3 = do not use
2 = do not use
1 = do not use
15 = CTS
14 = CTS+
13 = RXD+
12 = RTS-
11 = RTS+
10 = TXD
9 = TXD+
1
6
15
Shielded Cable
Port 2
To C-more Touch Panel
TXD+
TXD
RXD
RXD+
Note: We recommend Belden 8103 shielded cable or equivalent.
7
R
T
S
+
C
T
S
C
T
S
+
R
T
S
R
X
D
R
X
D
+
T
X
D
T
X
D
+
G
N
D
10 9 6 13 11 14 12 15
Signal GND
To DL06 PLC port 2
TXD+
TXD
RXD
RXD+
(Master)
(Slave)
* Termination resistors required at both ends of the
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms). Jumper pin
13 to 9 on the C-more Touch Panel 15-pin connector
to place the 120 internal resistor into the network. If
the cable impedance is different, then use an external
resistor matched to the cable impedance.
C-more
Touch Panel
(example device communicating
across RS-422 connection)
(example RS-422 connection)
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
620
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
C
T
S
+
R
T
S
R
X
D
+
T
X
D
+
R
X
D
T
X
D
G
N
D
HD = High Density
6 10 13 9 11 14 12 15
15-pin
HD D-sub
(male) 8 = do not use
7 = Sig GND
6 = RXD
5 = do not use
4 = do not use
3 = do not use
2 = do not use
1 = do not use
15 = CTS
14 = CTS+
13 = RXD+
12 = RTS-
11 = RTS+
10 = TXD
9 = TXD+
1
6
15
7
R
T
S
+
C
T
S
C
T
S
+
R
T
S
R
X
D
+
T
X
D
+
R
X
D
T
X
D
G
N
D
6 10 13 9 11 14 12 15
Typical RS-485 Multi-Drop Wiring Diagram
To DL06 PLC port 2 To D2-250-1 PLC port 2
*
* Termination resistors required at both ends of
the network to match the impedance of the cable
(between 100 and 500 ohms).
TXD+ / RXD+
TXD / RXD
Signal GND
TXD+ / RXD+
TXD / RXD
Signal GND
DirectLOGIC
DL06 PLC
(example device communicating
across RS-485 connection)
(example RS-485 connection)
(example device communicating
across RS-485 connection)
(example RS-485 connection)
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
621
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
C
T
S
+
R
T
S
R
X
D
+
T
X
D
+
R
X
D
T
X
D
G
N
D
6 10 13 9 11 14 12 15
shield
TXD+ / RXD+
TXD / RXD
Signal GND
5
*
T
e
r
m
.
S
H
D
R
D
+
S
D
+
R
D
S
D
G
N
D
10 12 9 11 13 1
Typical RS-485 Multi-Drop Wiring Diagram (contd)
HD = High Density
15-pin
HD D-sub
(male) 8 = do not use
7 = Sig GND
6 = RXD
5 = do not use
4 = do not use
3 = do not use
2 = do not use
1 = do not use
15 = CTS
14 = CTS+
13 = RXD+
12 = RTS-
11 = RTS+
10 = TXD
9 = TXD+
1
6
15
To DL06 PLC port 2
TXD+ / RXD+
TXD / RXD
Signal GND
DirectLOGIC
DL06 PLC
(example device communicating
across RS-485 connection)
(example RS-485 connection)
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
622
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Allen-Bradley:
Allen-Bradley MicroLogix 1000/1100/1200/1400/1500
RS-232C (p/n EA-MLOGIX-CBL)
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To AB MicroLogix RS-232
communication channel
To C-more Touch
Panel PLC Port
7
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
1 = do not use
2 = Sig GND
3 = do not use
4 = RXD
5 = do not use
6 = do not use
7 = TXD
8 = do not use
15-pin
D-sub
(male)
4
2
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
0.35
DIA.
Mini Din
8-pin Male
0
.
2
9
0
1 2
3 4 5
6 7 8
Nonstandard
keying
Allen-Bradley SLC 5-03/04/05, ControlLogix, CompactLogix,
FlexLogix, MicroLogix, DF1, RS-232C (p/n EA-SLC-232-CBL)
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To PLC
9-Pin Port
To C-more Touch
Panel PLC Port
3
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
2
5
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
9-pin
D-sub
(female)
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
1
9
1 = do not use
2 = RXD
3 = TXD
4 = do not use
5 = Signal GND
6 = do not use
7 = do not use
8 = do not use
9 = do not use
Allen-Bradley PLC5 DF1
RS-232C (p/n EA-PLC5-232-CBL)
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To PLC
25-Pin Port
To C-more Touch
Panel PLC Port
2
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
3
7
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
25-pin
D-sub
(male)
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
1
25
25 = do not use
24 = do not use
23 = do not use
22 = do not use
21 = do not use
20 = do not use
19 = do not use
18 = do not use
17 = do not use
16 = do not use
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
8 = do not use
7 = Signal GND
6 = do not use
5 = do not use
4 = do not use
3 = RXD
2 = TXD
1 = do not use
EA-MLOGIX-CBL
EA-SLC-232-CBL
EA-PLC5-232-CBL
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
623
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Allen-Bradley (contd):
Allen-Bradley SLC500, 5/01, /02, /03 DH-485
Point-to-Point
RS-485A (p/n EA-DH485-CBL)
8 = do not use
7 = do not use
6 = LE
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
To AB SLC500
DH-485 Port
To C-more Touch
Panel PLC Port
1
15 = do not use
14 = do not use
13 = Termination
12 = SD (RS485)
11 = SD+ (RS485)
10 = RD (RS485)
9 = RD+ (RS485)
1
15
1 = TXD/RXD+
2 = TXD/RXD
3 = do not use
4 = Signal GND
5 = LE
6 = do not use
7 = Signal GND
8 = do not use
15-pin
D-sub
(male)
2
7
TXD/RXD+
TXD/RXD
GND
9
10
5
1
RD+
RD
shield
RJ45 8-pin
Phone Plug
(8P8C)
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
4
GND
11
12
13
SD+
SD
Term.
5
LE *
6
LE *
* Note: The LE signal is wired in the cable
as shown, but not required for
point-to-point communications.
DH-485
Peripheral
CPU
J1
Power
Allen-Bradley
SLC 500 Modular
PLC Controller
DH-485 Link
(See manufacturers litature for details.)
AB 1747-AIC
DH485 Link Coupler
AB 1747-C11 A
Cable
J2
DH-485
Peripheral
CPU
J1
Power
J2
C-more
Touch Panel
C-more
Touch Panel
Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network
using the AB DH485 Link Coupler, p/n 1747-AIC. Select the Allen-Bradly DH485/AIC SLC500 MircroLogix driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
C-more
EA-DH485-CBL
Cable
C-more
EA-DH485-CBL
Cable
Allen-Bradley SLC500, 5/01, /02, /03 DH-485/AIC to Multiple C-more Touch Panels
RS-485A (using C-more cable p/n EA-DH485-CBL)
AB 1747-AIC
DH485 Link Coupler
Channel 1 must be
set to DH485.
EA-DH485-CBL
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
624
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Allen-Bradley (contd):
Allen-Bradley
SLC 5/03 Modular
PLC Controller
DH-485 Link
(See manufacturers litature for details.)
AB 1761-NET-AIC
AIC + Advanced
Interface Converter
AB 1747-CP3
RS-232 Cable
C-more
Touch Panel
C-more
Touch Panel
Note: The above diagram shows connecting multiple C-more touch panels to an Allen-Bradley DH485/AIC network using the
AB AIC+ Advanced Interface Converter, p/n 1761-NET-AIC. Select the Allen-Bradly DH485/AIC SLC500 MircroLogix driver
in the C-more Programming Software when starting the project. Also, set the AB channel configuration for DH485.
C-more
EA-MLOGIX-CBL
Cable
C-more
EA-SLC-232-CBL
Cable
Allen-Bradley SLC500 5/03 DH-485/AIC to Multiple C-more Touch Panels
(using C-more cables p/n EA-MLOGIX-CBL, EA-SLC-232-CBL)
AB 1761-NET-AIC
AIC + Advanced
Interface Converter
Channel 0 must be
set to DH485.
To additional
C-more
Touch Panel
C-more
EA-MLOGIX-CBL
Cable
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
625
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Allen-Bradley (contd):
Allen-Bradley
SLC 5/03 Modular
PLC Controller
C-more
Touch Panel
Multiple Allen-Bradley PLCs connected to multiple C-more Touch Panels
(using AB Ethernet Network Interface p/n 761-NET-ENI with EtherNet/IP protocol)
AB 1761-NET-ENI
ETHERNET
FAULT
RS232
TX/RX
PWR
CABLE
EXTERNAL
IP
Ethernet
Hub or Switch
10/100 Base-T
AB mini DIN to mini DIN
cable p/n 1761-CBL-AM00
Allen-Bradley
MicroLogix 1000
PLC Controller
Allen-Bradley
MicroLogix 1500
PLC Controller
AB 1761-NET-ENI
AB 1761-NET-ENI
C-more
Touch Panel
ETHERNET
FAULT
RS232
TX/RX
PWR
CABLE
EXTERNAL
IP
ETHERNET
FAULT
RS232
TX/RX
PWR
CABLE
EXTERNAL
IP
Ethernet/IP
Network
AB mini DIN to D-shell
cable p/n 1761-CBL-AP00
Allen-Bradley (contd):
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
626
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
GE:
GE VersaMax Micro:
Mitsubishi:
GE 90/30 and 90/70 15-pin D-sub port,
RS-422A (p/n EA-90-30-CBL)
To PLC
15-Pin Port
To C-more Touch
Panel PLC Port
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
13
12
7
SD(B)
SD(A)
GND
9
10
5
1
RD+
RD
shield
RD(B)
RD(A)
11
10
11
12
SD+
SD
Term.
13
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
15 = do not use
14 = do not use
13 = Termination
12 = SD (RS422)
11 = SD+ (RS422)
10 = RD (RS422)
9 = RD+ (RS422) 1
15
15-pin
D-sub
(male)
8
15
5
8 = CTS(B)
7 = Logic GND
6 = do not use
5 = +5V
4 = do not use
3 = do not use
2 = do not use
1 = do not use
15 = CTS(A)
14 = do not use
13 = SD(B)
12 = SD(A)
11 = RD(B)
10 = RD(A)
9 = do not use
1
15
15-pin
D-sub
(male)
CTS(B)
CTS(A)
+5V
Mitsubishi FX Series 25-pin D-sub port,
RS-422A (p/n EA-MITSU-CBL)
To PLC
25-Pin Port
To C-more Touch
Panel PLC Port
25-pin
D-sub
(male)
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
1
25
25 = do not use
24 = do not use
23 = do not use
22 = do not use
21 = do not use
20 = do not use
19 = do not use
18 = do not use
17 = do not use
16 = SD (RS422)
15 = RD (RS422)
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
8 = do not use
7 = Signal GND
6 = do not use
5 = do not use
4 = Signal GND
3 = SD+ (RS422)
2 = RD+ (RS422)
1 = do not use
3
16
7
SD+
SD
GND
9
10
5
1
RD+
RD
shield
RD+
RD
2
15
11
12
SD+
SD
Term.
13
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
15 = do not use
14 = do not use
13 = Termination
12 = SD (RS422)
11 = SD+ (RS422)
10 = RD (RS422)
9 = RD+ (RS422) 1
15
15-pin
D-sub
(male)
4
GND
EA-90-30-CBL
EA-MITSU-CBL
GE VersaMax Micro Port 1
RS-232C
8 = do not use
7 = do not use
6 = donot use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To PLC
RJ45 Port 1
To C-more Touch
Panel PLC Port
4
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
3
8
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
1 = RTS
2 = CTS
3 = RXD
4 = TXD
5 = DCD
6 = DTR
7 = +5V
8 = GND
RJ45 8-pin
Phone Plug
(8P8C)
User Constructed
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
628
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Mitsubishi(contd):
Mitsubishi FX Series 8-pin MINI-DIN,
RS-422A (p/n EA-MITSU-CBL-1)
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
To PLC
8-Pin Port
To C-more Touch
Panel PLC Port
7
15 = do not use
14 = do not use
13 = Termination
12 = SD (RS422)
11 = SD+ (RS422)
10 = RD (RS422)
9 = RD+ (RS422)
1
15
1 = RD (RS-422)
2 = RD+ (RS-422)
3 = Sig GND
4 = SD (RS-422)
5 = do not use
6 = do not use
7 = SD+ (RS-422)
8 = do not use
15-pin
D-sub
(male)
4
3
SD+
SD
GND
9
10
5
1
RD+
RD
shield
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend Belden 8103 shielded cable or equivalent.
Mini Din
8-pin Male
1 2
3 4 5
6 7 8
RD+
RD
2
1
11
12
SD+
SD
Term.
13
EA-MITSU-CBL-1
Mitsubishi Q02 / Q02H / Q06H / Q12H / Q25H Serial Driver
and QnA Serial Driver with Direct Connection to
the Serial Port on Q00 and Q01 CPUs
RS-232C
8 = do not use
7 = do not use
6 = donot use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
2
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
1
3
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
To C-more Touch
Panel PLC Port
To PLC
6-Pin Port
1 = RXD (232C)
2 = TXD (232C)
3 = Logic GND
4 = do not use
5 = do not use
6 = do not use
Mini Din
6-pin Male
1 2
3 4
5 6
User Constructed
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To PLC
9-Pin Port
1
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
4
5
TXD
RXD
GND
3
RXD
TXD
shield
9-pin
D-sub
(female)
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
1
9
1 = CD
2 = RXD
3 = TXD
4 = DTR
5 = Signal GND
6 = DSR
7 = RS
8 = CS
9 = do not use
To C-more Touch
Panel PLC Port
Mitsubishi Q / QnA Serial PLC
QJ71C24N
RS-232C
7
2
1
3
2
6
5
8
CD
DTR
CS
DSR
RS
User Constructed
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
629
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Omron:
Omron FINS (CQM1, CPM1, CPM2, C200, CJ1 & CS1)
RS-232C
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To PLC
9-Pin Port
To C-more Touch
Panel PLC Port
2
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
3
9
TXD
RXD
SG
3
2
5
1
RXD
TXD
shield
9-pin
D-sub
(male)
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
1
9
1 = do not use
2 = TXD
3 = RXD
4 = RTS
5 = CTS
6 = do not use
7 = do not use
8 = do not use
9 = Signal GND
RTS
CTS
4
5
Omron Host Link CQM1 using CQM1-CIF02 Peripheral Port Connecting Cable
RS-232C
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To Peripheral
Port Cable
To C-more Touch
Panel PLC Port
3
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
2
5
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
9-pin
D-sub
(male)
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend using 22 AWG shielded cable.
1
9
1 = do not use
2 = RXD
3 = TXD
4 = do not use
5 = Signal GND
6 = do not use
7 = do not use
8 = do not use
9 = do not use
Omron Host Link (C200 Adapter, C500),
RS-232C (p/n EA-OMRON-CBL)
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = RXD (232C)
2 = TXD (232C)
1 = Frame GND
To PLC
25-Pin Port
To C-more Touch
Panel PLC Port
2
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
1
15
15-pin
D-sub
(male)
3
7
TXD
RXD
GND
3
2
5
1
RXD
TXD
shield
25-pin
D-sub
(male)
Wiring Diagram
Note: Use the above wiring diagram if you need to make your own cable. We recommend using 22 AWG shielded cable.
4
RTS
5
CTS
1
25
25 = do not use
24 = do not use
23 = do not use
22 = do not use
21 = do not use
20 = do not use
19 = do not use
18 = do not use
17 = do not use
16 = do not use
15 = do not use
14 = do not use
13 = do not use
12 = do not use
11 = do not use
10 = do not use
9 = do not use
8 = do not use
7 = Signal GND
6 = do not use
5 = CTS
4 = RTS
3 = RXD
2 = TXD
1 = do not use
User Constructed
User Constructed
EA-OMRON-CBL
EA-USER-M Hardware User Manual, 2nd Ed. Rev. F, 05/11
630
Chapter 6: PLC Communications
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Siemens:
Siemens S7-200 CPU Port 0 or 1
RS-485A
To PLC
9-Pin Port
To C-more Touch
Panel PLC Port
Wiring Diagram
Note: Use the above wiring diagram to make your own cable. We recommend Belden 9842 shielded cable or equivalent.
3
5
RS-485
Signal B
Logic
Common
9
11
5
1
RD+
SD+
shield
RS-485
Signal A
8 10
12
RD
SD
Term.
13
8 = do not use
7 = do not use
6 = do not use
5 = Logic GND
4 = do not use
3 = do not use
2 = do not use
1 = Frame GND
15 = do not use
14 = do not use
13 = Termination
12 = SD (RS485)
11 = SD+ (RS485)
10 = RD (RS485)
9 = RD+ (RS485) 1
15
15-pin
D-sub
(male)
9-pin
D-sub
(male)
1
9
1 = Logic Com
2 = Logic Com
3 = RS485 Sig B
4 = do not use
5 = Logic Com
6 = +5 VDC
7 = +24 VDC
8 = RS485 Sig A
9 = do not use
User Constructed