Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Hospital Product Application Guide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 49

Hospital

Product Application
Guide
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Hospital Power Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Radial Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Dual Source and Radial Secondary Generators . . . . . . . . . . . . . . . . . . . . . . . . .10
Secondary Selective Generators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Dual Source and Secondary Selective Generators . . . . . . . . . . . . . . . . . . . . . . .11
Selective Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Circuit breakers vs. fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Ground Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Typical Hospital Product One Line Diagram . . . . . . . . . . . . . . . . . . . . . . . . .16
Medium Voltage Product Offering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Metalclad

Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Arc Terminator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Metal Enclosed Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Medium Voltage Motor Control Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Medium Voltage Power Factor Correction Capacitors . . . . . . . . . . . . . . . . . . . . . .21
Medium Voltage Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Packaged Unit Substation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Power Monitoring and Network
Communications Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Protective Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Power Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Circuit Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Power Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
PowerLogic

Generator Testing Documentation . . . . . . . . . . . . . . . . . . . . . . . . . .26


Low Voltage Product Offering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Low Voltage Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Switchboards Rear Connected QED-6 with Masterpact

Circuit Breakers and PowerLogic Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28


Switchboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Panelboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Square D

Integrated Power and Control Solutions . . . . . . . . . . . . . . . . . . . . . . . .33


Lighting Control PowerLink

G3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Low Voltage Motor Control Centers (MCC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Harmonic Filtering and Power Factor Correction . . . . . . . . . . . . . . . . . . . . . . . . . .36
Low Voltage Energy Efficient Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
3
Medical Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Dual Output Voltage Isolation Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Duplex Hospital Isolation Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Medical Headwall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Medium and Low Voltage Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . .42
Masterpact

Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42


Medium Voltage Vacuum Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
PowerPact

H- and J- Frame Molded Case Circuit Breakers . . . . . . . . . . . . . . . . .44


Enclosed Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Other Power Distribution products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Square D Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Products and Engineering Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Engineering Studies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
New Installation Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Retrofill and Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Maintenance and Testing Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . .49
Workplace Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
4
Introduction
Schneider Electric offers a robust line-up of products and services that are ideally suited to the needs of the
healthcare industry. The electrical distribution and control equipment used in healthcare facilities must offer the
highest possible levels of reliability, safety and yet be flexible enough to cope with the rapidly changing needs
of a healthcare customer.
Providing innovative, cost effective solutions that reduce costs throughout the lifecycle of the facility is critical.
Through its close association with those involved in the specification, design, construction and operation of
buildings, Schneider Electric has developed and understanding of the key requirements of the healthcare
customer. Continuous development, carefully focused on satisfying customers requirements, means that today,
Schneider Electrics portfolio of products and services for the healthcare segment is more comprehensive
than ever before.
5
Glossary
Following is a list of terms and definitions that are used in hospitals. Many of the definitions are defined per
the NFPA99 and the National Electrical Code

(NEC

).
Alternate Power Source One or more generator sets, or battery systems where permitted, intended to provide
power during the interruption of the normal electrical services or the public utility electrical service intended to
provide power during interruption of service normally provided by the generating facilities on the premises.
The alternate source of power shall be one of the following:
Generator(s) driven by some form of prime mover(s) and located on the premises
Another generating unit(s) where the normal source consists of a generating unit(s) located on the premises
An external utility service when the normal source consists of a generating unit(s) located on the premises
Arc Flash According to NFPA70E, arc flash is a dangerous condition associated with the release of energy
caused by an electrical arc. It is measured in terms of arc flash incident energy (cal/cm
2
), which is used to
determine the level of personnel protection equipment (PPE), and in terms of an arc flash protection boundary.
An arc flash study is performed to determine the proper PPE equipment workers are required to wear and the flash
protection boundary when working on or around exposed energized parts.
Arc Resistance Switchgear Equipment designed to withstand the effects of an internal arcing fault with
the doors closed. Equipment is considered arc resistant by successfully meeting the test requirements of
ANSI C37.20.7.
ATS Sometimes has several definitions, automatic transfer switch, automatic transfer system or auto-throw-over
system between two paralleled sources.
Critical Branch Asubsystem of the emergency system consisting of feeders and branch circuits supplying
energy to task illumination, special power circuits, and selected receptacles serving areas and functions related to
patient care, and which are connected to alternate power sources by one or more transfer switches during
interruption of the normal power source. The critical branch of the emergency system shall supply power for task
illumination, fixed equipment, selected receptacles, and special power circuits serving the following areas and
functions related to patient care.
Critical care areas that utilize anesthetizing gases task illumination, selected receptacles and
fixed equipment
The isolated power systems in special environments
Patient care areas task illumination and selected receptacles in the following:
Infant nurseries
Medication preparation areas
Pharmacy dispensing areas
Selected acute nursing areas
Psychiatric bed areas (omit receptacles)
Ward treatment rooms
Nurses stations (unless adequately lighted by corridor luminaries)
Additional specialized patient care task illumination and receptacles, where needed
Nurse call systems
Blood, bone and tissue banks
Telephone equipment rooms and closets
Task illumination, selected receptacles and selected power circuits for the following:
General care beds (at least one duplex receptacle per patient bedroom)
Angiographic labs
Cardiac catheterization labs
Coronary care units
Hemodialysis rooms or areas
Selected emergency room treatment areas
6
Human physiology labs
Intensive care units
Postoperative recovery rooms
Critical Care Areas Critical care areas are those special care units, intensive care units, coronary care units,
angiography laboratories, cardiac catheterization laboratories, delivery rooms, operating rooms, and similar areas
in which patients are intended to be subjected to invasive procedures and connected to line-operated,
electromedical devices.
Electrical Life-Support Equipment Electrically powered equipment whose continuous operation is necessary
to maintain a patients life.
Equipment for Delayed Automatic Connection This equipment shall be arranged for delayed automatic
connection to alternate power source. This means an outage to this equipment can exceed 10 seconds.
Central suction systems serving medical and surgical functions, including controls. Such suction systems shall
be permitted on the critical branch
Sump pumps and other equipment required to operate for the safety of major apparatus, including associated
control systems and alarms
Compressed air systems serving medical and surgical functions, including controls. Such air systems shall be
permitted on the critical branch
Smoke control and stair pressurization systems, or both
Kitchen hood supply or exhaust systems, or both, if required to operate during a fire in or under the hood
Exception: Sequential delayed automatic connection to the alternate power source to prevent overloading the
generator shall be permitted where engineering studies indicate it is necessary
Equipment for Delayed Automatic or Manual Connection This equipment shall be arranged for either
delayed automatic or manual connection to alternate power source. As mentioned for delayed automatic
connection, an outage to this equipment can exceed 10 seconds.
Heating equipment to provide heating for operating, delivery, labor, recovery, intensive care, coronary care,
nurseries, infection/isolation rooms, emergency treatment spaces and general patient rooms
An elevator(s) selected to provide service to patient, surgical, obstetrical and ground floors during interruption
of normal power
Supply, return and exhaust ventilating systems for surgical and obstetrical delivery suites, intensive care,
coronary care, nurseries, infection/isolation rooms, emergency treatment spaces and exhaust fans for
laboratory fume hoods, nuclear medicine areas where radioactive material is used, ethylene oxide evacuation
and anesthesia evacuation
Hyperbaric facilities
Hypobaric facilities
Automatically operated doors
Minimal electrically heated autoclaving equipment shall be permitted to be arranged for either automatic or
manual connection to the alternate source
Selected controls
Emergency SystemAsystem of feeders and branch circuits meeting the requirements of the NEC and
intended to supply alternate power to a limited number of prescribed functions vital to the protection of life and
patient safety, with automatic restoration of electrical power within 10 seconds of power interruption.
Essential Electrical System (ESS) Asystem comprised of alternate sources of power and all connected
distribution systems and ancillary equipment, designed to ensure continuity of electrical power to designated
areas and functions of a health care facility during disruption of normal power sources and also designed to
minimize disruption within the internal wiring system.
Fault Hazard Current The hazard current of a given isolated system with all devices connected except
the line isolation monitor.
7
General Care Areas General care areas are patient bedrooms, examining rooms, treatment rooms, clinics and
similar areas in which it is intended that the patient shall come in contact with ordinary appliances such as a nurse
call system, electrical beds, examining lamps, telephone and entertainment devices. In such areas, it may also be
intended that patients be connected to electromedical devices (such as heating pads, electrocardiographs,
drainage pumps, monitors, otoscopes, ophthalmoscopes, intravenous lines, etc.).
Hazard Current For a given set of connections in an isolated power system, the total current that would flow
through a low impedance if it were connected between either isolated conductor and ground.
Health Care Facilities are defined by National Fire Protection Agency (NFPA), Buildings or portions of
buildings that contain, but are not limited to, occupancies such as hospitals; nursing homes; limited care;
supervisory care; clinics; medical and dental offices and ambulatory care, whether permanent or movable.
Hospital Abuilding or part thereof used for the medical, psychiatric, obstetrical, or surgical care, on a 24-hour
basis, of four or more inpatients. Hospital shall include general hospitals, mental hospitals, tuberculosis hospitals,
childrens hospitals and any such facilities providing inpatient care.
Isolated Power SystemAsystem comprising an isolating transformer or its equivalent, a line isolation monitor
and its ungrounded circuit conductors.
Isolation Transformer Atransformer of the multiple-winding type, with the primary and secondary windings
physically separated, which inductively couples its secondary winding to the grounded feeder systems that
energize its primary winding.
Life Safety Branch Systems Asubsystem of the emergency system consisting of feeders, branch circuits and
intended to provide adequate power needs to ensure safety to patients and personnel and which are automatically
connected to alternate power sources during interruption of the normal power source. No function other than those
listed in (a) through (f) shall be connected to the life safety branch. The life safety branch of the emergency system
shall supply power for the following lighting, receptacles and equipment.
Illumination of means of egress, such as lighting required for corridors, passageways, stairways and landings
at exit doors and all necessary ways of approach to exits. Switching arrangements to transfer patient corridor
lighting in hospitals from general illumination circuits to night illumination circuits shall be permitted provided
only one of two circuits can be selected and both circuits cannot be extinguished at the same time.
Exit signs and exit directional signs
Alarm and alerting systems. Alarm and alerting systems including the following:
Fire alarms
Alarms required for systems used for the piping of nonflammable medical gases
Hospital communications systems, where used for issuing instructions during emergency conditions
Generator set location; task illumination battery charger for emergency battery-powered lighting unit(s) and
selected receptacles at the generator set location
Elevator cab lighting and control
Line Isolation Monitor Atest instrument designed to continually check the balanced and unbalanced
impedance from each line of an isolated circuit to ground and equipped with a built-in test circuit to exercise the
alarm without adding to the leakage current hazard.
Monitor Hazard Current The hazard current of the line isolation monitor alone.
Paralleling Switchgear Two or more power sources are connected to a load in a parallel. Each source must
have equal voltage and frequency values, and must share in the load for both real power (kW) and reactive power
(kVAR). Operating one of more generators in parallel with the utility typically requires electrically operated circuit
breakers for the generators and utility services, fast update rate voltage and frequency transducers, PLCs,
and protective relays to manage the interconnection between local generators and the utility distribution grid.
Auto-throw-over scheme control backup generators and electrically operated breakers in switchgear (via PLC
control) during utility outages or testing.
8
Patient Equipment Grounding Point Ajack or terminal bus that serves as the collection point for redundant
grounding of electric appliances serving a patient vicinity or for grounding other items in order to eliminate
electromagnetic interference problems.
Reference Grounding Point The ground bus of the panelboard or isolated power system panel supplying
the patient care area.
Rotary UPS Arotary UPS system uses a motor-generator set, with its rotating inertia, to ride through brief
power interruptions. Power goes to critical loads by means of a generator driven by an AC or DC motor.
The motor-generator set will ride-thru power interruptions long enough to allow generators to backup essential
electrical systems.
Selective Coordination Localization of an overcurrent condition to restrict outages to the circuit or equipment
affected, accomplished by the choice of overcurrent protective devices and their ratings or settings. The following
National Electrical Code

(NEC

) sections address selective coordination:


517.26 Application of other articles. The essential electrical system shall meet the requirements of Article 700,
except as amended by Article 517
700.27 Coordination. Emergency system(s) overcurrent devices shall be selectively coordinated with all supply
side overcurrent protective devices
701.18 Coordination. Legally required standby system(s) overcurrent devices shall be selectively coordinated
with all supply side overcurrent protective devices
Total Hazard Current The hazard current of a given isolated system with all devices, including the line isolation
monitor, connected.
UPS An uninterruptible power supply is a battery backup system that converts AC - DC (DC connected to
batteries) converts DC - AC and is continuously on-line. During a utility outage, the batteries will provide power to
critical loads for 10 to 45 minutes (depends on system design). During this time, the back up generators can start
and backup essential electrical systems.
Hospital Power Systems
There are several agencies and organizations that develop requirements for health care electrical distribution
system design. The following is a listing of some of the specific NFPAstandards that affect health care facility
design and implementation:
NFPA37 Standard for Stationary Combustion Engines and Gas Turbines
NFPA70 National Electrical Code
NFPA99 Health Care Facilities
NFPA101 Life Safety Code
NFPA110 Standard for Emergency and Standby Power Systems
NFPA111 Standard on Stored Electrical Energy Emergency and Standby Power Systems
These NFPAguidelines represent the most industry recognized standard requirements for health care electrical
design. However, the electrical design engineer should consult with the authorities having jurisdiction over the local
region for specific electrical distribution requirements.
All electrical power systems in health care facilities are very important, though some loads are not critical to the
safe operation of the facility. These non-essential or normal loads include things such as general lighting, general
lab equipment, non-critical service equipment, patient care areas, etc. These loads are not required to be backed
up with an alternate source of power. However, the electrical system requirements for the Essential Electrical
System (EES) do require an alternate source of power. According the 2005 NFPA99, Section 4.4, if electrical life
support or critical care areas are present then facility is classified as ESS Type 1. ESS Type 1 has the most
stringent requirements for providing continuity of electrical service.
9
NFPA99, Section 4.4 states that EES Type 1 power systems shall be designed with the following
important considerations:
Dual sources of normal power shall be considered but shall not constitute an alternate source of power
Distribution system arrangements shall be designed to minimize interruptions to the electrical systems due to
internal failures by the use of adequately rated equipment
The following factors shall be considered in the design of the distribution system:
Abnormal voltages such as single phasing of three-phase utilization equipment, switching and/or lightning
surges, voltage reductions, and so forth
Capability of achieving the fastest possible restoration of any given circuit(s) after clearing a fault
Effects of future changes, such as increased loading and/or supply capacity
Stability and power capability of the prime mover during and after abnormal conditions
Sequence reconnection of loads to avoid large current inrushes that trip overcurrent devices or overload
the generator(s)
Bypass arrangements to permit testing and maintenance of system components that could not otherwise
be maintained without disruption of important hospital functions
Effects of any harmonic currents on neutral conductors and equipment
Current-sensing devices, phase and ground, shall be selected to minimize the extent of interruption to the
electrical system due to abnormal current caused by overload and/or short circuits
Generator load-shed circuits designed for the purpose of load reduction or for load priority systems shall not
shed life safety branch loads, critical branch loads serving critical care areas, medical air compressors,
medical-surgical vacuum pumps, pressure maintenance (jockey) pump(s) for water-based fire protection
systems, generator fuel pumps or other generator accessories
Essential electrical systems shall have a minimum of two independent sources of power: a normal source
generally supplying the entire electrical system and one or more alternate sources for use when the normal
source is interrupted
Where the normal source consists of generating units on the premises, the alternate source shall be either
another generating set or an external utility service
ESS Type 1 systems are required to have a minimum of two independent sources of electrical power.
Anormal source that generally supplies the entire facility and one or more alternate sources that supply power
when the normal source is interrupted. The alternate source(s) must be an on-site generator driven by a prime
mover unless a generator(s) exists as the normal power source. In the case where a generator(s) is utilized as
the normal source, it is permissible for the alternate source to be a utility feed. Alternate source generators must be
classified as Type 10, Class X, Level 1 generator sets per NFPA110 2-2 capable of providing power to the load
in a maximum of 10 seconds.
Typically, the alternate sources of power are supplied to the loads through a series of automatic and/or manual
transfer switches. The transfer switches can be non-delayed automatic, delayed automatic or manual transfer
depending on the requirements of the specific branch of the EES that they are feeding. It is permissible to feed
multiple branches or systems of the EES from a single automatic transfer switch provided that the maximum
demand on the EES does not exceed 150 kVA. This configuration (Radial Generator, shown on the following
page) is typically seen in smaller health care facilities that must meet ESS Type 1 requirements.
Determining the power system configuration that will service your facility is most important. There are several
different power system configurations that can be found in healthcare facilities. They do not represent all power
system designs as they vary per engineering consultant, but are some of the most commonly seen in hospitals.
These designs generally meet the design requirements of ESS Type 1 in hospitals.
We have included advantages and disadvantages of these system types based on what is important over the life of
a power system in hospitals. Many large hospital complexes may have several incoming utility sources that are
connected to the following or a combination of these systems types from medium voltage (15 kV - 5 kV) down to
the 208 V level. Care should be taken when deciding on system design types and cost should not be the only
concern. Reliability, expandability, operation, and maintenance should be high on the priority list as indicated in
these system types and per NFPA99.
10
This is the simplest system to operate and has the lowest first cost. It is also very easy for maintenance people
to understand. System can have outages for faults and maintenance. If utility source Ais lost, the entire
system is lost for 10 seconds until generators can be brought on-line. This system is normally used on
smaller healthcare facilities.
Dual Source and Radial Secondary Generators
Radial Generator
System has the ability to switch between two utility sources via auto throw-over scheme. Electrically operated
medium voltage breakers are required for this transfer system. If both utility sources are lost, generators
back up essential electrical loads via transfer switches. System design is reliable and used for medium to
large size hospitals.
Advantages:
Low first cost
Simple operation and understanding
by personnel
Easily expanded
Radial ground fault
Disadvantages:
Low Reliability
Maintenance causes outages
Advantages:
Protection against loss of primary source
Possible paralleling of sources
Choice between Source Aor B
Reliable
Disadvantages:
Additional cost of equipment
11
The secondary selective system allows the transfer of load from one transformer to the other with the use of
electrically operated main and tie-breakers via auto throw-over scheme. This is important if one transformer fails or
needs maintenance. If both utility sources are lost, generators backup essential electrical loads via transfer
switches. Transformer sizing is critical if all secondary loads are to be serviced from one transformer. This is
usually accomplished by either loading the transformers to 50%, or by using the transformer forced air (fan) rating
with temperature controllers.
This system may require complex ground fault solution if both 480 Y/277 V transformers have separate grounds
or if 3 pole transfer switches are used for 4 wire loads. This causes circulating current on the neutral busses.
This system is common in large cities where the utility companies use transformers, located in vaults,
to service hospitals.
Dual Source and Secondary Selective Generators
Secondary Selective Generators
This system combines the advantages of both primary sources and secondary selective systems used with
backup generators. It not only provides the more reliable system, but also one of the most costly system.
Evaluation of the probability of total downtime costs will be necessary to justify the additional first cost. This system
may require complex ground fault solution if both 480 Y/277 V transformers have separate ground points or if
3 pole transfer switches are used for 4 wire loads. This causes circulating current on the neutral busses. This
power system is popular for large hospital complexes.
Advantages:
Normal operation as radial systemwith
stand-by generators
Isolation of cable or transformer for faults
or normal maintenance
Feed other side with use of transfer
scheme and electrically operated
breakers
Main and tie breakers can be
interchanged for maintenance to keep
outages to a minimum
Disadvantages:
Additional cost
Transformer load monitoring
May require complex ground fault system
if neutrals are tied together and sources
have multiple grounding points
Advantages:
High Reliability
Combined advantages of both sources
and generators
Disadvantages:
Higher initial cost
May require complex ground fault system
if neutrals are tied together and sources
have multiple grounding points
12
Selective Coordination
Selective coordination of overcurrent protective devices is very important in hospitals when patients lives are at
stake. Downstream overcurrent protection devices, closest to a fault, trip or clear is the focal point of this section.
The NFPA90, 2005 National Electrical Code

(NEC

) issue on selective coordination is addressed in sections


700.27 (Emergency Systems), 701.18 (legally required Standby Systems), 517.26 (Health Care Facilities) and
have made it mandatory that emergency power systems overcurrent protective devices are designed to selectively
coordinate. This increases the reliability of power systems for critical healthcare facilities.
The history behind selective coordination started with elevators in NEC section 620.62. The NEC states the
following Where more than one driving machine disconnecting means is supplied by a single feeder, the
overcurrent protective devices in each disconnecting means shall be selectively coordinated with any other supply
side overcurrent protective devices. This was a result of all elevators being fed from one feeder and not being
protected with individual branch overcurrent devices. Then when a fault occurred on one motor, the single feeder
overcurrent device feeding all the motors would interrupt and cause outages on the other elevators. This is
especially important because elevators are commonly used to carry firefighters and equipment closer to the fire
during fire-fighting operations. One selective solution was to feed each elevator motor with a separate overcurrent
device instead of one feeder for several motors. Installation cost for installing one feeder outweighed separate
feeds for this application and the NEC was forced to address selective coordination.
Selective coordination will be explained in the next two examples. The first example will address selective
coordination on any normal power system. Proper engineering, short circuit and coordination studies should be
performed on any electrical system to ensure that they are selective. Coordination curves for overcurrent
devices should be set to ensure systems are selective and the downstream overcurrent devices operate first
for all fault conditions.
For main bus Fault 1 in Figure 1a, the overcurrent device downstream in Panel 1, and closest to the fault, should
operate and isolate the rest of the system from the event. If the downstream device doesn't operate, and the
upstream overcurrent device FDR Atrips, then all the loads in Panel 1 are lost and unwanted outages occur.
The same for Fault 3, if the main breaker in Sub Atrips instead of the downstream FDR A, all the loads will be
lost in Sub A. This is the main emphasis for the 2005 NEC regulations for essential electrical systems in
Healthcare facilities.
For main bus Fault 2 in Figures 1a and 1b, the overcurrent device in Panel 3 has to coordinate with both the
Normal Source B and the emergency source. Regardless which source is operating, the system must have
selective coordination. If the upstream feeder or main in either Sub B or emergency switchgear trip before the
branch breaker in Panel 3, there will be a severe outage. Essential electrical systems will be lost and patients lives
in surgery, emergency rooms, coronary care, intensive care, etc. could be in danger.
The following time overcurrent coordination curves (shown in Figure 2) show proper selectivity per the NEC, using
circuit breakers in Sub B, Panel 3, and Panel 4 from Figure 1a. The 20 Abranch breaker curve shown in Figure 2 is
the last protective device in Panel 4 serving the critical load. It is also the first breaker to trip on downstream faults.
Circuit breakers vs. fuses
Both fuses and circuit breakers can be used on hospital power systems when considering selective coordination.
Choosing between using fuses or circuit breakers during the design of the hospital is usually the job of the
consulting engineer or engineering and maintenance supervisor. Their power system design must have selective
coordination when feeding essential electrical loads. Outages in hospitals are serious events and getting power
back on-line quickly and safely are the main concerns.
The following 2005 NFPA99, Section 4.4 distribution design factors should be considered when choosing fuses
over circuit breakers in hospital systems.
Abnormal voltages such as single phasing of three-phase utilization equipment. Fused switches typically do not
protect from single-phasing and this can cause damage to rotating equipment such as motors
Capability of achieving the fastest possible restoration of any given circuit(s) after clearing a fault. Power
cannot be restored unless spare fuses are available and the proper PPE equipment is worn. This can
cause extensive outages
13
Others benefits of using circuit breakers are:
Circuit breakers can be easily reset, thus reducing down time
Circuit breakers do not generally require maintenance personnel to suit up with Arc Flash Personal Protective
Equipment (PPE) when they are reset
Figure 1a: Shows selective coordination for essential electrical systems per 2005 NEC section 700.27.
The overcurrent protective device immediately above the fault should trip first. Breaker in Panel 1 shall trip for Fault 1
and FDR Ashall trip for Fault 3. This will provide a reliable electrical system and prevent unwanted power outages.
Figure 1b: Shows selective coordination for essential electrical systems per 2005 NEC section 700.27.
The overcurrent protective device immediately above the fault in Panel 3 shall trip first. This will provide a reliable
electrical system and prevent unwanted power outages to other life safety or critical loads.
14
Figure 2: These curves show selective coordination using circuit breakers from Square D

Masterpact

NW 2000 A
main and 1600 Afeeder breakers downstream to 400 AType Pbreaker in Panel 3 and to branch 20 AFAmolded
case circuit breaker in Panel 4 feeding a critical load 50' away. These curves ensure that any fault on emergency
system will be cleared by upstream device per NEC 700.27.
Ground Fault Protection
Ground fault protection is required on any feeder or service disconnect 1000 Aor larger on systems with line to
ground voltages of 150 volts or greater and phase-to-phase voltages of 600 volts or less, per NEC articles 230.95
and 517.17. In healthcare facilities, an additional step of ground fault protection shall be provided in the next level
of feeder disconnecting means downstream toward the load per NEC 517.17 (refer to Figure 3). Such protection
shall consist of overcurrent devices and current transformers or other equivalent protective equipment that shall
cause the feeder disconnecting means to open.
Wherever ground fault protection (GFP) of equipment is applied to the service providing power to a health care
facility, whether by design or by reason of the requirements of NEC, an additional level of ground fault protection
is required downstream. Under this rule, ground fault protection is required to be applied to every feeder, and
additional ground fault protective devices may be applied farther downstream at the option of the governing body of
the health care facility. With proper coordination, this additional ground fault protection is intended to limit
a ground fault to a single feeder and thereby prevent a total outage of the entire health care system. Coordination
includes consideration of the trip setting, the time setting, and the time required for operation (opening time) of
each level of the ground fault protection system.
15
It is not intended that ground fault protection be installed between the on-site generators and the transfer
switch(es) or on the load side of the essential electrical system transfer switch(es). The NEC article 517.17
prohibits the use of additional levels of ground fault protection on the following systems. This is to ensure that the
essential electrical system and generators do not trip off-line due to a ground fault condition.
1. On the load side of an essential electrical system transfer switch, or
2. Between the on-site generating unit(s) and the essential electrical system transfer switch(es), or
3. On electrical systems that are not solidly grounded wye systems with greater than 150 volts to ground but not
exceeding 600 volts phase-to-phase.
Ground fault protection for operation of the service and feeder disconnecting means shall be fully selective such
that the feeder device and not the service device shall open on ground faults on the load side of the feeder device.
Asix-cycle (.1 sec) minimum separation between the service and feeder ground fault tripping bands shall be
provided. Operating time of the disconnecting devices shall be considered in selecting the time spread between
these two bands to achieve 100 percent selectivity.
For ground fault protection of equipment, the alternate source for emergency systems (generators, etc.) shall not
be required to have ground fault protection with automatic disconnecting means. Ground fault indication of the
emergency source shall be provided per NEC section 700.7 (see Figure 3). The sensor for the ground fault signal
devices shall be located at, or ahead of, the main system disconnecting means for the emergency source, and
the maximum setting of the signal devices shall be for a ground fault current of 1200 A. Therefore, for the above
NEC reason, health care power systems provide ground fault indication (alarm) on stand-by generators. This
alarm is usually tied to a power monitoring or building management system to alert personnel when a ground fault
does exist.
Figure 3: An additional step of ground fault protection is required in healthcare facilities for normal loads. This is to
ensure that the downstream feeder breakers trip before the main breaker. Asix-cycle (.1 sec) minimum separation
between the service (main) and feeder ground fault tripping bands shall be provided. Ground fault is not allowed
between generators and transfer switches or on the load side of transfer switches. This is to ensure that the
essential electrical system and generators do not trip off-line due to a ground fault condition.
16
Typical Product One Line Diagram
17
18
Medium Voltage Product Offering
Metalclad

Switchgear
Masterclad

medium voltage switchgear is used in a wide variety of switching, control and protective applications
for hospital. In large systems, its mainly used for the main incoming service equipment and the generator
paralleling gear. Auto transfer schemes allow Metalclad breakers to seamlessly switch between utility sources
and paralleling gear during scheduled or uncontrolled power outages.
Metalclad switchgear is also used for the primary disconnect on the 12.47 kV to 480 V and 208 V transformers.
This allows users to electrically transfer between two sources without the use of generators. This is also important
for isolating cable faults that may occur while in operation.
Significantly, most of the Masterclad switchgear specified for these applications is relied upon to provide the critical
main service entrance protection and controls.
This class of switchgear protects transformers, generators and feeder circuits.
Benefits
Long life and minimum maintenance Vacuum interrupter design is capable of 20 to 100 full fault operations
(varies by ratings), Total fault clearing time is 3 cycles. This is the fastest in the industry and reduces voltage
sags on the system.
Safety barriers and interlocks Full compartmentalization is supplied with primary functions separated by
grounded metal barriers. All bussing is insulated and live parts are not exposed. Safety interlocks work with the
breaker racking system. These protective features provide safety for operating personnel.
Breakers can withstand various levels of commissioning which involves many switching operations.
Hospital Applications
Main service switchgear
Paralleling switchgear
Ratings
4.76 kV 15 kV (to 13.8 kV nominal)
1200 A 3000 A
250 MVA 1000 MVAinterrupting capacity
60 kV and 95 kV BIL
Indoor and outdoor enclosures
Standard Features (as defined by ANSI C37.20.2)
Removable (drawout) circuit breaker
Fully compartmented construction
Grounded metal barriers enclose all live parts
Automatic shutters
Insulated bus
Mechanical interlocks
Disconnect type voltage transformers CPTand VTs
Grounded breaker truck in and between test/disconnected and connected positions
Low voltage instrument/control compartment isolated from primary voltage areas
19
Arc Terminator
Medium voltage switchgear can have an additional degree of protection from damaging open arcing faults with
the Arc terminator arc extinguishing system. This system detects and controls the effects of arcing faults.
It extinguishes arcs rapidly, significantly minimizing equipment damage and reducing equipment downtime.
Benefits
Confines the effects of the arc to the point of initiation
Enhances protection by detecting and commuting arc fault current
Extinguishes high magnitude arc currents within less than
1
/
4
of a cycle and prevents the buildup of
high internal pressures
Features
Uses sensors to detect arcs in medium voltage switchgear
Initiates the closing of a high-speed vacuum switch if an arc is detected via the electronic control unit
Uses two sensing inputs:
Optical sensors detect arcing faults
Current transformers are used to detect any change in current (both input events must occur together
to operate the high-speed switch)
The Arc Terminator system can be shipped with any new switchgear lineup
Easy to install and operate: no settings or other calculations required during switchgear installation
Switchgear protective relaying functions are coordinated to provide maximum protection with the addition of
the Arc Terminator system
How it works
The Arc Terminator system confines the effects of an arcing fault to the point of initiation. When an arc is detected,
a high speed vacuum switch closes, effectively crow-baring the short circuit. This action creates a solid conducting
path for the current parallel with the arc. The open burning arc is extinguished, preventing the buildup of damaging
pressures. The energy released by the arcing fault is significantly reduced. The electronic control requires two
sensing inputs: (1) optical sensors to detect arcing faults and (2) current sensors to detect changes in the current
waveform.
An indicator on the junction box (which serves as a collector for the optical inputs), points to the compartment
where the arcing fault occurred, making it easy to pinpoint the location of a fault and repair the problem quickly.
Once the cause of the fault has been fixed, the system is ready to be reset and returned to normal operation. For
critical applications such as large hospitals and healthcare complexes this means less downtime.
Metal Enclosed Switchgear
Metal enclosed interrupter switches are most often used in hospitals for protecting medium voltage transformers
that service low voltage (480 V and 208 V) switchgear. The load interrupter switches are also useful for isolating
cables between Metalclad

breakers and transformers when maintenance is required. This equipment is ideal for
applications where high duty cycle operation (switching) is not required and equipment cost is a concern.
Hospital Application
Primary protection (fusible) and isolation (non-fused) for medium voltage transformers
HVL/cc

switchgear features 2.4 kV to 38 kV switching, control, and overload protection are ideal for hospital
applications. Improving reliability and performance are the primary goals of switchgear in any switching, control or
protective application.
20
Medium Voltage Motor Control Centers
Motorpact medium voltage motor control centers are normally used to supply and protect large chiller motors
200 HPand above in hospitals. Feeding large motors with lower voltages becomes cost prohibitived because
equipment sizes get very large, limited, or unavailable and multiple sets of conduit and cable are needed.
Our Motorpact is designed and manufactured to meet your power and chiller control challenges. Our motor
controllers feature industry-first innovations that provide unmatched performance, high reliability, low maintenance
and exclusive technologies. Our different motor controllers available are listed below.
Full Voltage Controller
This controller is used for full-voltage starting and stopping of AC motor applications at 2300 V and above and
provides the following.
Motor overload and short circuit protection in one package
Incoming line connection
Control power transformer (115 volt secondary)
Magnetic three-pole vacuum contactor (mechanically latched types are also available)
Run-test circuit
Reduced Voltage Auto-transformer Controller
This type of controller is typically used to start very large motors that may cause a voltage drop on the rest of the
power system. It also helps with reducing the size of medium voltage transformers needed for these applications.
Available from 2300 V to 7200 V with ranges of horsepower up to 5000 HP
Provides the highest torque per ampere of line current
Features an inherently closed transition type, to full voltage running
Features voltage taps, which permit the adjustment of starting voltage, allowing the customer to adjust the
starting voltage to suit the system capabilities and limit voltage sags on the power system
Offers acceleration times up to 30 seconds for medium duty, making it suitable for a long starting period
Weve taken these goals further with HVL/cc medium voltage metal enclosed switchgear. Its exclusive operational
features offer a higher level of system protection, yet it also incorporates innovative design features that reduce
the risk of costly maintenance problems. The major differentiating features of HVL/cc switchgear include:
Smallest footprint in the industry (approximately one-quarter size of traditional medium voltage metal enclosed
switchgear) makes it ideal for retrofit applications requiring increased load or duplex switches. Compact
footprint fits easily through standard doorways
Compartmentalized construction the fuse/cable compartment is isolated from the main bus, while the main
switch contacts are housed in a sealed interrupter
Low maintenance Sealed for life interruption saves time and expense with maintenance-free main contacts
and ground switch contacts. Prevents switch contamination especially in harsh environments
Fault-making grounding switch (optional) prevents access to hot fuse/cable compartment with
mechanical interlock
Front access eliminates need for service space behind switchgear
FuseLogic system provides single-phase protection and blown fuse indication. This protects downstream
motors from overheating due to negative sequence currents
No other medium voltage metal enclosed switchgear on the market offers these advantages. When you make the
comparison based on installation simplicity, performance, and total cost of ownership, HVL/cc switchgear becomes
the clear choice for system protection and reliability.
21
Medium Voltage Reduced Voltage Soft Start Controller
This type of controller is typically used to start large motors that have special load conditions applications.
Motorpact reduced voltage soft start (RVSS) motor control units provide:
Pre-engineered, integrated motor control package for reduced voltage starting and soft stopping
Allows customer to fine-tune the starting parameters to meet a wide variety of unique load conditions and to
prevent voltage sags on the power system
Offers a better alternative to traditional reactor or auto-transformer type reduced voltage starters
Reduces voltage drop on the system while starting
Allows the use of smaller medium voltage transformers for this application
Transparent Ready

Motorpact

motor controllers allow users to view meter readings in real-time, without having to
walk the entire facility. Plus, users can access a running minimum/maximum history, which can help users spot
abnormal conditions.
Medium Voltage Power Factor Correction Capacitors
Reactivar

metal enclosed medium voltage capacitor systems provide power factor correction, harmonic filtering
and voltage regulation. Depending on the specific application issues and level of harmonic content in the network.
Fixed, standard (MV5000), anti-resonant (MV6000) and filtered (MV7000) capacitor systems are available up to
20 MVAR, at 15 kV. Large hospital power users (over 5 MW) can benefit from centralized medium voltage
compensation of power factor and harmonics. Medium voltage solutions usually require lower initial capital
expenditures ($/kVAR) than low voltage solutions while addressing most common power quality problems.
Power factor correction capacitors also provide the following benefits.
Economical advantages when monetary incentives such as power factor penalty are enforced
Added caps to a power system causes the voltage to rise, this provides voltage support when starting
large motors
Released capacity (kVA) on transformers. When capacitors deliver reactive power the current on the power
system is reduced allowing additional loads to be added to distribution equipment and transformers
Reduced current reduces I2R losses on power system equipment and cables, allowing them to operate more
efficient and cost effective
Medium Voltage Transformers
Consultants specify many different types of medium voltage transformers when designing hospitals: Liquid filled,
cast primary cast secondary, cast primary sealed epoxy secondary and VPI (dry-type) on primary and secondary.
The main objective of what is specified depends on the installation location (indoor or outdoor) of the transformers,
the emergency loading it may be subjected to (fan packages), and the life the hospital engineering manager
expects from the transformer. Depending on the transformer design and its loading or uses, the expected life could
be up to 40 years.
Schneider Electric offers a full range of medium voltage transformer products. All transformers are manufactured in
ISO certified facilities that ensure the highest quality products are provided, built and tested to applicable
ANSI/IEEE, CSAand NEMAstandards. Our products are available with ULListing. We offer high efficient standard
designs including optional low loss TP1 designs.
Transformers are designed, manufactured and tested to Square D

specifications ensuring the highest


quality in the industry
Available ULListing
Liquid-filled transformers available with FM label
All products meet or exceed applicable ANSI/IEEE standards
Square D brand transformers are manufactured in ISO9001 certified facilities (the most comprehensive
standard in the internationally recognized ISO9000 series)
22
Liquid-Filled Padmount
45 kVAto 20,000 kVA
Primary voltages 2.4 kVAto 46 kV, 250 kV BILmaximum
Secondary voltages to 25 kV
Mineral oil, less flammable hydrocarbon fluid, silicone and less flammable seed-oil based fluid
Liquid-Filled Substations
112.5 kVAto 20,000 kVA
Primary voltages 2.4 kVAto 69 kV, 350 kV BILmaximum
Secondary voltage to 34.5 kV, 200 kV BILmaximum
Mineral oil, less flammable hydrocarbon fluid, silicone and less flammable seed-oil based fluid
Power-Cast

II
112.5 kVAto 13,000 kVA
Primary voltages 2.4 kV to 46 kV, 200 kV BILmaximum
Secondary voltage to 15 kV
Aluminum windings available
Forced air provides 50% overload for 1000 kVAthrough 5000 kVA, 33% overload on all other kVAratings
No pre-drying before energizing
UniCast II

112.5 kVAto 3,000 kVA


600 V secondary
Copper windings available
Forced air provides 33% overload
Power Dry II

112.5 kVAto 13,000 kVA


Primary voltage 2.4 kV to 35 kV150 kV BIL
Secondary voltage up to 15.0 kV
Forced air provides 33% overload
Packaged Unit Substation
Combining a primary switch, dry-type transformer and I-Line

distribution section into a single unit, the Model III


package unit substation is the smallest footprint in the industry. The compact size of this product makes it ideal for
servicing outpatient, boiler or maintenance buildings in hospital complexes where real estate is a premium. In
addition, top fed units are only 37.5'' deep and 90'' high, allowing the entire substation to pass through standard
size single doorways and narrow hallways.
The Model III package unit substation can be used in retrofit applications requiring increased electrical demand,
as well as new construction requiring multiple zones. Substations are available in sizes 75 kVAthrough 1000 kVA
with three phase primary voltages of 2400 V though 13800 V.
23
Power Monitoring and Network
Communications Products
Atypical modern hospital utilizes networks for patient accounts, building management, power management and
lighting control systems, while operating an interoffice or corporate Ethernet information network. Many times,
these networks employ different communication protocols as well as different physical wiring and interface
equipment. Each of these systems provides critical information for efficient facility operation, but blocks
interoperability of the separate systems. Managing separate networks for each facility system requires resources,
experience, extensive support and continuous training. These activities increase operating costs and decrease
facility efficiency and reliability.
Schneider Electrics policy for networks is based on open standards in order to ensure open connectivity for our
customers. The Transparent Ready

family of products emphasizes Ethernet and web technologies (TCP/IP, HTTP,


XML, etc.). Modbus

, a defacto protocol standard in many markets, continues to play a central role in our network
policy as the main messaging protocol, whether its at the Ethernet level over TCP/IP(Modbus TCP) or over RS-
485 multi-point communications (Modbus RTU or Modbus serial).
Implementing web-based technologies on Ethernet provides an extremely flexible communications infrastructure.
Utilizing common technologies and infrastructure allows shorter design cycles, lower implementation costs, and
lower maintenance costs, and provides for continuous process improvement. Utilizing the power of web
technologies like TCP/IPprovides an open path to information and control systems on a facilitys existing Ethernet
network. This approach provides all the benefits of a secure and deterministic architecture without locking into
proprietary networks and protocols. Combining those benefits provides unmatched real-time control and open
access to critical systems information without the restrictions of proprietary environments or the threat of
implementing a field bus that may not exist in a few years. Hospital engineering and maintainence managers can
fully integrate data from many systems within their facilities and be able to better manage their efficiencies.
Transparent Ready

Equipment
Schneider Electric is the first manufacturer in the world to provide Ethernet connectivity across our comprehensive
portfolio of power distribution equipment. We call this innovative technology platform Transparent Ready
Equipment. Its simply the easiest and most open solution for accessing information about your hospital
electrical systems.
All Transparent Ready Equipment products feature an Ethernet connection and embedded web server, designed to
organize valuable information for easy access from any computer on your network using any standard web
browser. By making it simple to connect your power equipment, we help you get the actionable information you
need to reduce costs, and increase productivity.
Transparent Ready Equipment is web-enabled via PowerLogic

technology.
Intelligent devices are connected to the LAN via a PowerLogic Ethernet Server:
CM3000/4000 with ECC Ethernet card
EGX Ethernet Gateway
Power server (with optional local display)
Obtain data from any of these devices:
Masterpact

or Powerpact

breakers with Micrologic

trip units
Sepam protective relays
Circuit monitors CM4000 and CM3000
Power meters, enercept or energy meters
Model 98 transformer temperature controllers
Variable speed drive
PLC-based auto transfer schemes
Power Monitoring
Many hospital engineering and maintenance managers have reached the same conclusion about their
electrical power systems. By employing sophisticated power monitoring equipment to analyze historical and
real-time data, they can reduce the cost of electricity and improve its quality and reliability and enhance their
troubleshooting abilities.
Intelligent analysis of power data prevents electrical system problems and saves money. Below are some of these
benefits from a power monitoring system.
Better understanding of electrical system loading and demand. This helps cut capital cost from over designing
when expansions or modifications are needed
Easy to compare electric bills (kWHs) with utility company statements
Catch voltage sags and disturbances that may be causing critical equipment to trip off-line such
as UPSs or variable speed drives
Easier to troubleshoot system problems such as faults or harmonics
Helps provide a better understanding of entire electrical system
24
Protective Relays
From a simple protection relay or a multifunctional, communicating protection unit for remote network management
and operation, the PowerLogic

Sepam protection device is the right solution. Sepam Series 20, 40 and 80 are
ideally suited to the most commonly encountered applications in hospital facilities. This devices is ideal for retrofit
or installation into medium voltage equipment (including Metalclad

switchgear, metal enclosed switchgear and


motor control center).
Complete line of protective relays Feeder, motor, generator, transformer and bus protection, all in a
common relay family
Preventative maintenance alerts Self-diagnostics for protection assurance, and external diagnostics for
breaker, CT/VTand trip coils
Customizable protective settings Adaptive logic editor utilizes Boolean logic, allowing users to adapt standard
control functions to suit varying needs of a power system
Intuitive, graphic display Graphic LCD display features a back light with auto contrast adjustment, and allows
user access to operational and diagnostic information, power measurements and alarms, as well as
password-protected setup
Zone selective interlocking Accelerated coordination between protection devices to minimize
equipment damage
Power monitoring functionality Relays include power monitoring functionality to assist in managing
the electrical system
Modbus

communications
Hospital Application
Metalclad switchgear
Medium voltage paralleling switchgear
25
Power Meters
Power meters are typically used on feeder breakers for medium voltage switchgear and low voltage switchgear or
switchboards. They are also used downstream on low voltage motor control centers and power distribution
switchboards and panelboards. These devices have become very powerful and provide more monitoring
capabilities than circuit monitors manufactured in the late 90s. Below are some of the features of power meters.
Basic metering functions, allowing metering of current, volts, power, energy and demand readings
Power quality readings include total harmonic distortion for current and voltage readings
Min/max values
Alarm/relay functions
Event and data logging on pre-configured values
Ethernet communications available via Transparent Ready

Hospital Application
Motor control centers
Distribution switchboards
Panelboards
Circuit Monitors
Circuit monitors are typically used to monitor power system parameters on medium voltage switchgear, 480 V
substations, motor control centers and switchboards. Locating them on this equipment enhances your ability to
completely understand and troubleshoot your power system when needed. Below are some of the features of
the circuit monitors.
Basic and advanced metering functions, along with a 0.04 percent typical accuracy rate
14 data logs and up to 32 MB of memory available
Waveform capture to 255th harmonic
Three types of waveform capture steady state, disturbance and adaptive
Sag/swell detection to less than 1/2 cycle
Trending and forecasting functions
Optional web-enabled access directly to meter
15 MHz sampling rate that allows detection of transients lasting only one microsecond (available
with CM4000T)
GPS time synchronization option
Sequence event time stamping option
Hospital Application
Main service switchgear
Paralleling switchgear
26
PowerLogic

Generator Testing Documentation


Improper routine testing is one of the leading causes of generator non-performance. Exercising a generator below
recommended loading can actually reduce its reliability and result in unburned fuel and/or carbon build up in the
exhaust system. This condition is known as wet stacking. Its presence is readily indicated by black smoke during
engine-run operation. Left undetected, it could make an emergency power system useless.
Many facilities are opting for PowerLogic monitoring systems with automatic emergency power supply system
reporting and relying on it as an indispensable tool to:
Pass indication gives confidence that the emergency power supply system generator and ATS tests have been
performed correctly
Automatic collection reduces documentation time
Expedites performance verification
Eliminates inaccurate manual readings of loading levels
Continuous monitoring and alarming for entire power system
Square D

power management provides comprehensive service necessary to automate the emergency power
supply system testing documentation. For hospitals, testing documentation meets EC.2.10.4.1 for acute care
facilities, ambulatory surgical centers and long term care facilities, required by the Joint Commission of HealthCare
Organizations (JCAHO) and the centers for Medicare and Medicaid Services (CMS).
Comprehensive monitoring of utility mains, feeders, generators, compressors and virtually any Modbus

communicating device
Troubleshooting aids such as diagram depicting the status of power sources, breaker position, temperatures,
tank levels, pressures, run/stop, metering parameters, etc.
Early detection and alarm notification to pager, email and graphical interface so you can head off
problems quickly
Automatic data collection and web reporting with emailing and network sharing capabilities for instant access
to emergency power supply system test results, cost allocation, energy consumption reports, power quality
analysis and trending of any monitored point
Customization services are available for interface design, control schemes, sequence of events recording
and many other retrofit solutions
For more information on automating testing and documentation for exercising Emergency Power Supply Systems (EPSS) refer
to document 3000HO0403/R505 or visit www.powerlogic.com.
27
Low Voltage Product Offering
Schneider Electric offers a wide variety of low voltage power distribution products, from our QED-2 Powerstyle

switchboards using group-mounted I-Line

construction to our QED-6 compartmentalized switchboards. Schneider


Electric provides a complete ULoffering. Power-Zone

4 switchgear is built to strict ANSI standards and features


the industry preferred Masterpact

NW and NTcircuit breakers.


Transparent Ready

communications technology with PowerLogic

components is offered throughout the full range


of low voltage distribution equipment. All Transparent Ready products feature an Ethernet connection and
embedded web server, designed to organize valuable information for easy access from any computer on your
network using any standard web browser. By making it simple to connect your power and control equipment, we
help you get the actionable information you need to reduce costs, and increase productivity.
These products and components are the preferred choice for many end users, consultants and contractors. They
are used by many of the leading specialty OEMs sub-systems such as paralleling switchgear and UPS equipment.
Low Voltage Switchgear
Power-Zone 4 with Masterpact Circuit Breakers and PowerLogic Monitoring
One of the major benefits for using ANSI-rated switchgear is the structure and breakers have defined short time
withstand ratings (short circuit current withstand for 30 cycles). When properly adjusted, this allows main and
feeder breakers to coordinate with downstream protective devices to ensure the device closest to the fault clears
first. This is very important when trying to selectively coordinate with downstream feeder breakers or other devices
downstream. In addition to short time withstand ratings, other benefits such as 100% rated breakers (from 800 Ato
5000 Aframes), drawout construction, and maintainability for extended life make Power-Zone 4 switchgear the
primary choice in hospitals.
Hospital Application
Main service switchgear
Paralleling switchgear
Major new design and operational features have also been built into the Power-Zone 4 switchgear structures, for
longer life and increased reliability. Below is a list of product features.
Smallest footprint in the industry
Masterpact circuit breakers have higher short time ratings and interrupting ratings than competitive products
and met ANSI specified number of operations with no maintenance required
Electrically operated breakers are listed to UL1066, and the structure is listed to UL1558
200 kASCCR without fuses
Increased wire bending space
Available up to 5000 Abus rating
Micrologic

trip units with power monitoring, control and communications


28
Optional PLC based auto transfer schemes
Optional Transparent Ready

communications utilizing PowerLogic

technology
Optional Surgelogic

TVSS
Differential ground fault option for 4W systems with multiple sources
Arc flash application options
Arc flash limiting feeder breakers up to 2000 Areduce arc incident energy on downstream equipment such as
MCCs and PDPs
Thru-the-door breaker operation allows unit to be operated/racked while door is closed; this reduces NFPA
70E PPE category by one level
Rear-hinged doors allow easy access to cables; this reduces NFPA70E 2004 PPE category by one level
Benefits of using Power-Zone

4 in hospital applications:
Drawout construction is required for quick circuit breaker change-out
Transfer system requirements call for circuit breakers to close within five-cycles and stored energy circuit
breakers are required for reliability
Front access to control wires is desired for ease of installation, maintenance and upgrade
Circuit breaker compartmentalization is required for system integrity
Segregation of circuit breaker compartments, from bus and cable compartments, is required
for equipment
Isolation breakers without fuses are required for high short circuit current ratings up to 200 kAIR
Switchboards Rear Connected QED-6 with Masterpact

Circuit Breakers
and PowerLogic

Monitoring
Rear connected switchboards offer many of the same benefits of ANSI rated switchgear listed above. Short times
withstand ratings on the breakers, and structures as well as high short circuit interrupting ratings. Lower equipment
cost, drawout breakers (breaker frame sizes to 250 Ato 5000 A) and maintainability for extended life are reasons
this product is used in these facilities.
Hospital Application
Main service switchgear
Paralleling switchgear
QED-6 switchboard structures offer many of the same benefits as Power-Zone 4 switchgear. Some of these
features differences are listed below.
Masterpact and PowerPact

circuit breakers have higher short time ratings and interrupting ratings than
competitive products
Up to eight Masterpact NTcircuit breakers can be mounted in a single 30''-wide section
PowerPact circuit breakers 250 Aand 600 Aframe for smaller loads
Electrically operated breakers UL489 rated and structure UL891 listed
150 kASCCR without fuses @480 V (200 kAIR @240 V)
29
Switchboards
QED-2 switchboards are used in almost every level of the hospital electrical system. Oftentimes, on smaller
hospital systems, QED-2 switchboards make up the majority of the equipment installed. They are used for service
entrance, supplying power to HVAC and building equipment, and to primary of 480 V transformers that supply
208/120 V power distribution units. We also supply custom solutions for paralleling equipment when using 4-pole
breakers on high resistance grounded systems. The QED-2 switchboards along with 4-pole breakers provide
maintenance isolation for generators.
QED-2 switchboards are available with single or multiple mains and distribution sections. Individually mounted
mains use PowerPact

P- and R-frame electronic or Micrologic

molded case circuit breakers through 2,500 A,


Masterpact

NW two-step stored energy electronic trip circuit breakers, for fixed or drawout applications
through 5,000 A.
QED-2 distribution sections include I-Line

circuit breakers. With I-Line plug-on circuit breaker construction, the line
end of the circuit breaker plugs directly onto the I-Line panel bus assembly. This design allows you to quickly install
and wire circuit breakers from the front of the switchboard. In addition, I-Line circuit breakers are keyed to mounting
slots in the support pan for automatic alignment and faster installation. I-Line switchboard sections are available in
single- or double-row construction.
If you require higher feeder ampacities, QED-2 switchboards are available with individually mounted branch
devices up to 4,000 A. They include both thermal-magnetic and electronic trip molded case circuit breakers.
For equipment ground fault protection you can use electronic trip. With QED-2 switchboards, you can also specify
options such as automatic throw-over systems.
Hospital Application
Service entrance switchboard
Paralleling switchboards
Building and HVAC distribution switchboards
Features
Front accessible load connections
Front and rear alignment standard
Switchboard fed by cable, busway, transformer, QED switchboard or other
Switchboard ratings through 5000 A, 200 kA; higher amperages available
Thermal-magnetic, electronic, Micrologic or stored energy fix-mounted and Masterpact NW drawout mounted
circuit breaker mains and feeders
Main devices in six sub-division or single main configurations
Main and branch devices in single section configuration
Main lugs in separate section in line-up or behind devices
Group-mounted mains and branches
Thermal-magnetic and electronic circuit breakers with standard, high, extra-high or current limiting capability
Exclusive Micrologic

trip circuit breakers, 80% or 100% rated.


Zone selective interlocking on Micrologic circuit breakers, group-mounted 100 A/250 Athermal-magnetic circuit
breakers with add-on ground fault.
PowerLogic

system customer metering from ammeter, voltmeter, wattmeter to waveform capture, data
logging, alarm/relay functions, disturbance monitoring and programmable logic, including custom
communications capability and inter-wiring
30
Custom engineering including main-tie-mains, multiple sets of through bus, reduced height and
engineered houses
4-pole breakers are optional
Transfer switches are optional
Automatic throw-over systems are optional
Panelboards
Engineering and maintenance managers, engineering consultants and contractors prefer Square D

I-Line

NF and
NQOD panelboards for use in hospital applications because these products are widely recognized as the industry
leaders in reliability and versatility.
600 V Panelboards I-Line

Hospital Applications
Paralleling panelboards
Cafeteria equipment
Building and HVAC distribution panels
Main Breaker Panelboards
Accept a maximum 1200 A, thermal magnetic 80% or 100% rated electronic main and branch breakers
Available factory-assembled or merchandised
Factory-assembled main circuit breaker interiors are available bottom-feed or top-feed
Available with a short circuit current rating (SCCR) up to 200 kAmaximum (100 kA@600 VAC) when supplied
by an I-Limiter

circuit breaker
Available with a silver-plated or tin-plated copper bus or tin-plated aluminum bus
Solid neutral is mounted in the main compartment with the main circuit breaker
Main Lugs Only Panelboards
Available with main lug only interiors rated up to 1200 A
Accept a maximum 1200 A, thermal magnetic 80% or 100% rated electronic branch breakers
Available factory-assembled or merchandised
Available with a short circuit current rating (SCCR) up to 200 kAmaximum (100 kA@600 VAC) when supplied
by an I-Limiter circuit breaker
Available with a silver-plated or tin-plated copper bus or tin-plated aluminum bus
Solid neutral is mounted in the main compartment with the main lugs
Hinged cover, isolated main lugs compartment
Main lug interiors are available as top-feed or bottom-feed
I-Line Plug-on Unit with Surgelogic

TVSS
Plug-on design requires less cable and conduit than end gutter-mounted TVSS unit, saving labor time and
material costs
Bus-connected design enhances performance
Integrated TVSS and circuit breaker disconnect feature compact design, requiring only 13.50" (343 mm) of
branch mounting space
SCCR up to 200 kArating (100 kA@600 VAC) meets a wide variety of customer applications
31
I-Line

Circuit Breakers
I-Line panelboards are designed to accept the following circuit breakers: FY, FA, FH, FC, FJ, FK, FI, HD, HG,
HJ, HL, QB, QD, QG, QJ, QO, KA, KH, KC, KI, JD, JG, JJ, JL, LA, LH, LC, LI, LE, LX, LXI, MG, MJ, PG, PJ,
PL, RG, RJ and RL
480/277 V Panelboards NF
Square D

NF panelboards are typically used for supplying power to HVAC, 277 V lighting, and to supply 480 V
transformers for 208/120 V panels.
Ratings main lugs 125 Ato 800 A, main circuit breaker 125 Ato 600 A
Branch circuit breakers (bolt-on), 1-pole, 15 Ato 70 A; 2-pole, 15 Ato 125 A; 3-pole, 15 Ato 125 A
Main Lugs Interiors
Top or bottom feed
65 kAIR maximum branch circuit breakers at 480 Y/277 VAC
Series rated to 200 kAIR maximum when supplied by remote I-Limiter

circuit breaker
Factory-installed main lugs on all interiors
125 A- 400 Amain lug interiors are convertible to main circuit breaker by adding a main circuit breaker adapter
kit and main circuit breaker
Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard). Tin-plated copper bus is
available as an option; 600 Aand 800 Aare only available with copper
Branch connector fingers are tin-plated copper; silver-plated branch connector fingers are optional
Optional TVSS available
Main Circuit Breaker Interiors
Top or bottom feed
65 kAIR maximum branch circuit breakers at 480 Y/277 VAC
200 kAIR with I-Limiter main circuit breaker
Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard)
Tin-plated copper bus is available as an option; 600 Aonly available with copper
Branch connector fingers are tin-plated copper; silver-plated branch connector fingers are optional
125 Amain circuit breaker interiors contain factory-installed back-fed EDB, EGB or EJB main circuit breakers
Optional TVSS available
250 Amain breaker interiors use the standard main lug interior and the appropriate HG, HJ, HL, JD, JG, JJ, JL
or KI breaker
400 Amain breaker interiors use the standard main lug interior and the appropriate LAor LH breaker
600 Amain breaker interiors use the standard main lug interior and the appropriate LC or LI breaker
32
208/120 V Panelboards NQOD
In addition to supplying office and patient lighting, Square D

NQOD panelboards are ideally suited for use


in office receptacles, dietary, X-Ray, data processing and cafeteria equipment and personal computers in
hospitals. They are the preferred brand to install by contractors and are designed to meet both single and
three-phase applications.
Main Lugs Interiors
Will accept plug-on or bolt-on branch circuit breakers
Top or bottom feed
65 kAIR maximum branch circuit breakers (fully rated)
200 kAIR maximum when supplied by remote I-Limiter

circuit breaker (series rated)


Field-installable sub-feed lug kits for 100 Ato 225 Ainteriors
Factory installed main lugs on all interiors
225 Ato 400 Amain lug interiors are convertible to main circuit breaker by adding a main circuit breaker and
adapter kit
Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard). Tin-plated copper bus is
available as an option. Branch connector fingers are all tin-plated copper; silver-plated branch connector
fingers are optional
200% neutral bus optional
TVSS optional
Main Circuit Breaker Interiors
Will accept plug-on or bolt-on branch circuit breakers
Top or bottom feed
65 kAIR maximum branch circuit breakers (fully rated)
200 kAIR maximum when supplied by I-Limiter circuit breaker (series rated)
Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard). Tin-plated copper bus is
available as an option. Branch connector fingers are all tin-plated copper; silver-plated branch connector
fingers are optional
200% neutral bus optional
TVSS optional
100 Amain circuit breaker interiors include a factory-installed back-fed QOB main circuit breaker
225 Amain circuit breaker interiors use:
Standard main lug interiors
Main circuit breaker adapter kit
Appropriate QBL, QDL, QGL, QJL, JDL, JGL, JJL, JLLor KILcircuit breaker
250 Amain circuit breaker interiors are factory assembled only
400 Amain circuit breaker interiors use:
Standard main lug interior
Main circuit breaker adapter kit
Appropriate LALor LHLcircuit breaker
Square D

Integrated Power and Control Solutions


Square D integrated power and control solutions (IPaCS) offers a family of products that combine electrical
distribution equipment, building controls and automation into a single factory-assembled and pre-wired enclosure,
based upon specific requirements. These solutions work great for those crowded electrical closets on patient floors
where equipment can be integrated in one enclosure that will save installation time and valuable floor space.
For over 30 years, we have been providing integrated equipment solutions to eliminate the headaches and hassles
of getting your electrical system up and running. An integrated equipment solutions maximizes floor space because
the components are assembled in a single line-up. This modular approach also means less conduit, connectors
and feeder cables, dramatically reducing onsite installation time and material costs.
And because our integrated electrical solutions are shipped as one complete system, there are fewer pieces to
receive and install at the job site. In addition, all pre-engineered circuits comply with national codes and standards,
and the complete system is factory tested prior to shipment. Compare this to a traditional, stick-built electrical room
(below) where panelboards, transformers, lighting controls and building management systems are individually
ordered, received, installed and tested, usually from multiple manufacturers.
Why choose Square D IPaCS?
Space savings integrated electrical solutions decrease the overall size requirement of an electrical room,
freeing floor space for future expansion or other needs
Labor savings reduces onsite material handling and installation labor
Cycle time reduction pre-assembled construction shortens lead times and reduces total installation time
Design flexibility distribution equipment is configured from a broad product offering to provide customer-
specific solutions
Design consistency integrated electrical solutions are ideal for multi-site locations such as large hospitals and
campus-style medical facilities
Single point of responsibility because we integrate the electrical distribution equipment, controls and
automation, there is one point of responsibility that ensures your integrated system arrives on time and
working properly
33
Integrated Power Center (IPC)
The innovative integrated power center allows for greater design complexity and is custom-designed to your
specifications. Shipped to site fully assembled, completely pre-tested, ULlisted and ready to install. The IPC is also
2000 IBC seismically qualified. Allows for integration of a variety of controls, including:
Electrical distribution equipment
HVAC controls
Lighting controls
Power quality/power conditioning
Surge suppression
Building automation
Before After
34
Modular Panel System (MPS)
The pre-engineered modular panel system is tailored to your specifications, and may include panels, transformers
and lighting control. The MPS is also 2000 IBC seismically qualified.
Special interiors available, such as Powerlink

G3 lighting control systems


Options include power and control cable wiring, contactors, terminal blocks, TVSS and equipment space
Integrated Power Center 2 (IPC2
TM
)
The IPC2 is a switchboard based platform design that bundles panelboards, individually mounted
circuit breakers, lighting control, third party controls and transformers into a factory assembled and
prewired integrated solution. These switchboards are UL listed, seismically qualified and compatible
with Square D

integrated panelboard centers, modular panelboard systems and QED switchboards.


Lighting Control PowerLink

G3
PowerLink G3 lighting control systems provide an immediate return on your energy savings investment by
automatically switching lights off during unoccupied periods. Corridor lighting, parking garages, physical therapy,
training centers, cafeteria, dietary, central supply, outpatient surgery or even surgery lighting can be automated
when they are not occupied for more than two shifts. This means big savings and a quick payback.
Compared with other energy savings technologies, a PowerLink G3 lighting control system can provide both
a lower initial capital outlay and greater energy savings.
Reduce energy costs save up to 15% on your electric bill by controlling when and where energy is
being used
See rapid return on investment typically less than two years.
Improve productivity save energy without sacrifice to occupant comfort
Receive email or pager notification be notified via email or by pager when a particular circuit or lighting area
does not operate as planned
Low Voltage Motor Control Centers (MCC)
Model 6 Motor Control Centers
The Model 6 Motor Control Center (MCC) provides the best method for grouping electrical motor control,
automation, and power distribution into a compact and economical package. The Model 6 MCC is a modular
system of dead front, free standing structure housing not only electro-mechanical motor starters, but also
adjustable frequency drives, reduced voltage solid-state motor controllers, power monitoring units, and advanced
system communications. The pre-engineered and coordinated component selection helps assure the power and
control integrity of critical infrastructure.
Model 6 Motor Control Centers are used in many applications within the medical facility to supply power to cooling
towers, chilled water supplies, boilers, compressed air and vacuum pumps, air handling units, and more. The motor
control center may also be integrated into the building automation system.
Space saving design structure dimensions 20 in. wide by 90 in. high by 15 or 20 in. deep. Acommon bus bar
for distributing power to control units, and a network of wire trough and conductor entrance areas for
accommodating incoming and outgoing load and control wires are all included
Robust structure design rigid free-standing enclosures can be seismically certified, with an importance factor
of 1.5, to meet the latest building code for most of the United States
ULlisted certified by Underwriters Laboratories to meet or exceed ULStandards for Safety for Motor Control
Centers, UL845
35
Top mounted main horizontal bus and industry exclusive two-piece sliding non-conductive horizontal bus
barrier allows enhanced main bus access without the need to remove any panel, resulting in lower
installation and maintenance cost
Captive, four-bolt, horizontal slice bars reduces installation and maintenance time with self-contained
hardware allowing front access single tool joining of bus sections
Full depth vertical wireway features largest vertical wireway in the industry, allowing segregation of power,
control, or communications cables
Vertical ground bus sections are provided with a vertical ground bus which mates with ground stabs on each
plug-in unit to create a positive ground connection
Intelligent Motor Control Centers (iMCC)
The integration of automation and intelligence into components has driven a revolution in motor protection, data
acquisition, and distributed control. The Model 6 intelligent motor control centers takes full advantage of these
capabilities using our Transparent Ready

architecture. This patented technology allows instant access to system


information, configuration, and diagnostics without special software via common web browsers.
Features
Immediate access to alarms and diagnostic information identifies potential problems for maintenance staff,
before they become more serious, and facilitates locating problems when they do occur
Factory installation, testing and verification of I/O points simplifies the integration of automation and reduces
field-commissioning time
Embedded Transparent Ready Ethernet web servers provides web-based access to motor control center
devices without special software via common web browsers
Integral network communications reduces installation cost, typically an integrated network in the
motor control center will reduce the comparable installed cost by 20%
Integrated communication cable eliminates the control wire bundle. Mechanically protected and including
micro-style connectors enhance network reliability in harsh industrial applications
36
Harmonic Filtering and Power Factor Correction
Power electronic loads such as drives, have become increasingly abundant in hospitals due to their many benefits.
But they have one major drawback: they produce harmonics. Harmonics may disrupt other loads, increase
operating costs and lower the reliability of the electrical network.
In addition, applying power factor correction is complicated by the presence of harmonics in a network. Symptoms
of problematic harmonic levels include overheating of motors, drives and cables, thermal tripping of protective
devices; and logic faults of digital devices; all of which can result in downtime. The life span of many devices may
be reduced by overheating. Furthermore, by reducing harmonic levels, the need to oversize transformers and
cables to account for harmonic heating effects is lessened. Schneider Electric offers many types of harmonic
filtering and power factor correction solutions to address these common problems.
AccuSine

PCS
AccuSine PCS is commonly identified as an active harmonic filter. It is much more. Square D

AccuSine PCS
dynamically corrects power quality by providing:
Active harmonic filtration
Resonance prevention
Power factor correction
Dynamic VAR compensation
AccuSine PCS can be universally applied for all types of harmonic generating loads, even on the same supply bus.
It can be applied on sources rated 208 V to 480 V, 50 Hz or 60 Hz. Additionally, the performance is the same
regardless of the source characteristics. Whether the source is utility, generator, UPS or multiple sources,
AccuSine operates the same and is selected according to the loads. No electrical simulations are needed.
AccuSine PCS is offered in standard NEMA1 enclosure or in the Model 6 MCC. Other enclosure types are
available upon request. AccuSine is also designed to meet the most stringent level of IEEE 519-1992 Table 10.3 at
the PCC with a utility, at an internal bus or at an individual nonlinear load.
Reactivar

Power Factor Correction Capacitors and Passive Harmonic Filter Systems


When the total content of nonlinear loads is less than 15% of all loads, fixed or stepped power factor capacitors
can be used for displacement power factor correction. Products such as the AV4000 and AV5000 series are
excellent choices.
When the total content of nonlinear loads is less than 50% of all loads, fixed or stepped detuned power factor
systems, AV6000/AT6000, or fixed or stepped fifth harmonic tuned filters, AV7000/AT7000, are good product
choices. In all cases, be sure to perform simulations to ensure that capacitor resonance does not occur. When the
nonlinear load content exceeds 50% of the total loads, AccuSine PCS is typically the best solution.
Fixed Capacitors
Fixed capacitors are offered but not recommended in the presence of AC and DC drives. Capacitors are a low
impedance path for harmonic currents given off by drives and other harmonic generating loads. These harmonic
currents absorbed by the capacitors will cause it to fail prematurely. Also, be careful when using fixed capacitors in
motor control centers with motors. If the capacitor is not sized properly with the motor, switching can cause
transient over voltages that can damage the windings.
37
Low Voltage Energy Efficient Transformers
These highly efficient transformers are designed to meet anticipated Department of Energy guidelines set
forth in the 1992 Energy Act, H.R. 776, which requires lower energy consumption levels, including electrical.
Schneider Electric and the National Electrical Manufacturers Association (NEMA) have been proactive in
developing an Energy Efficient Standard (TP1-1996) designed to provide lower energy consumption levels.
Minimum efficiencies have been established for each size of transformer, and extensive design, testing and
manufacturing time has been spent to ensure each transformer meets or exceeds these efficiencies. These units
are the same physical size as their standard counterpart, but offer greater energy savings. Atypical model will see
a payback in three years at $.065 per kWH.
Surveys show that typical loading of low voltage dry type transformers on a 24-hour average basis is only 35%
of full load rating.
At such loading levels, purchase of standard, low temperature rise designs with the intent of saving energy can
actually result in a loss penalty. In contrast, users of energy efficient transformers often see a payback in three
to five years.
Medical Products
Operating Room Panels (OR)
This unit is the isolation panel most often used to supply 120 V service to the receptacles in an operating room.
However, its use is not restricted to that application; it can also be used in critical care areas.
This panel incorporates:
The isolation transformer which is standard low-leakage, electrostatically shielded, 220 C insulation system
80 C temperature rise maximum, 30 dB sound level isolating transformer
Aprimary circuit breaker
Eight secondary 2-pole circuit breakers
Square D

ISO-GARD

Line Isolation Monitor (LIM)


Isolated power panels are non-ventilated and have a #304 stainless steel trim with a brushed finish. Under
continuous full load and normal hospital ambient conditions, the front trim panels total temperature will be no
greater than 50 C. Square D Isolated Power Panels are ULlisted under Section 1047 Isolated Power
Systems Equipment.
Intensive Care/Coronary Care Panels (ICU/CCU)
The ICU/CCU panel incorporates the same components and features as the operating room panels, but have the
added feature of power receptacles and approved grounding jacks which connect to a ground bus for attaching
fixed equipment and building structural grounds. The power receptacles are hospital only locking type
receptacles, duplex or single receptacles. Although the panel is designed to serve the needs of a coronary care
or intensive care bed, it has been widely applied to provide power within special procedure rooms, cardiovascular
laboratories, and general operating rooms.
Controlled Power Panel
The Square D controlled power panel is designed to provide economical electric service for portable X-ray
and laser outlets. The panel can serve eight locations within the hospital. Interlocking circuitry allows a
predetermined number of circuits to be used at any given time. Consequently, the LIM monitors only the wiring
and its inherent leakage to those circuits. Remote indicator alarm stations must be located at the receptacle
location. Control options include contactors, mechanical interlocking devices and PLC controllers. Where only one
or two X-ray receptacles are required, the interlocking system or PLC may not be necessary. Contact Schneider
Electric for additional information.
The PLC controlled power panel is the more popular panel since it allows control of the isolated power within the
room at the receptacle module.
38
Remote Alarm Indicator
The RA1 remote alarm indicator from Square D

medical products is designed to fit virtually anywhere


a single-gang wiring device can be mounted. Its low-profile design offers all the features required by NFPA-99,
plus a meter scale and a Push to Test function for periodic testing. Its visual and audible indicators emulate those
of the Iso-Gard

Series D (IGD) line isolation monitor (LIM). The RA1 is not designed for use with any
Square D brand remote alarm Indicator that incorporates an analog meter.
Dual Output Voltage Isolation Panels
The dual output voltage isolation panel is a single, ungrounded hospital isolation panel that can supply
two different output voltages simultaneously. Similar to a standard distribution panel or load center, it can
supply both 120 V and 208 V or 120 V and 240 V of ungrounded, isolated, single-phase power using only
one isolation transformer.
Other hospital isolation panels can supply only one output voltage. Typically, the 208 V or 240 V circuits of the dual
output voltage panel supply power to operating room equipment such as mobile X-ray machines or surgical lasers.
Simultaneously, the panels 120 V circuits can supply power to convenience receptacles, surgical lights, X-ray film
illuminators, sterilizers, and other 120 V appliances commonly found in operating rooms. This panel is ideally
suited as a power supply to power/ground modules and X-ray indicator/receptacle modules.
The dual output voltage panel is factory equipped with eight 20 A, 2-pole branch circuit breakers for the 120 V
applications and is field expandable up to 16 circuits. The 208 V and 240 V application has one main breaker fed
from a transformer rated at 15 kVAonly and two branch breakers (20 A, 2-pole through 60 A, 2-pole). The panel is
sized according to the 120 V kVArequirements and coordinating the 208 V and 240 V requirements. The panel is
designed to supply ungrounded power to only one operating room. Use of the panel to supply power to more than
one room may conflict with National Fire Protection Association (NFPA).
The transformers overall power rating in the dual output voltage isolation panel is the sum of the two secondary
windings. The 208 V and 240 V secondary winding is always rated at 60 A, while the 120 V secondary winding
can be rated at 5.0, 7.5, or 10.0 kVA. All applications include a primary main circuit breaker as well as secondary
main circuit breakers for both windings (208 V and 240 V, and 120 V). The 208 V and 240 V secondary main circuit
breaker is always rated at 60 A, while the 120 V secondary is rated to comply with the size rating of the 120 V
secondary winding.
Features
Low leakage, copper-wound, dual output voltage isolation transformer with electrostatic shield
manufactured by Schneider Electric
One 120 V load center with eight factory-installed 20 A, 2-pole branch circuit breakers, field expandable
to 16 circuits
One 208 V and 240 V load center with space for two 10 A, 2-pole through 60 A, 2-pole field-installed
branch circuit breakers
NEMAType 1 enclosure with Type 304 stainless steel trim
Two ISO-GARD

microprocessor controlled line isolation monitors (LIMs)


Factory-installed primary and secondary main circuit breakers
Factory-installed, copper reference ground bar
Optional Acessories
Panel mounted indicator alarms for the panels line isolation monitors
Alarms are commonly used when the panel is mounted within the operating room
Panel mounted receptacles. Up to six hospital grade, 120 V, convenience receptacles and up to two 208 V and
240 V receptacles can be mounted on the face of the panel
Panel mounted 30 A, green ground jacks for grounding of non-electrical equipment
39
Advantages of dual output voltage isolation panel:
Lower labor costs-installation is simpler when one panel can be substituted for two separate panels
Lower material cost-one panel rather than two separate panels reduces material costs
Duplex Hospital Isolation Panel
The Duplex hospital isolation panel is a single enclosure containing two complete 120 V secondary hospital
isolation systems. Adivider in the unit's backbox separates the systems from top to bottom and front to back.
Each system has its own set of equipment:
Primary circuit breaker
Isolation transformer
Reference ground bus bar
ISO-GARD

line isolation monitor


Load center
The compact Duplex design minimizes the width of the panel, which uses less horizontal wall space than two
conventional isolation panels mounted side by side. This slim design is of particular benefit when the isolation
panel is mounted in an operating room where wall space is limited. The unit is available in 5, 7 or 10 kVAratings
and includes a stainless steel cover. Because the panels provide power to life support equipment, a lockable door
is included on all units. The door covers the branch circuit breakers and line isolation monitors to help restrict
unauthorized access. The unit is totally enclosed and non-ventilated to help keep out dust, dirt, recirculating air and
cleaning solutions. An optional surface mount back-box is available for remodeling applications. The entire panel
assembly is listed under ULStandard 1047, Hospital Isolated Power Systems. Duplex hospital isolation panels are
ideally suited for large operating rooms where more than 14 circuits are required. The branch circuits can be
divided between the two systems to keep branch circuit leakage current from exceeding the limits set by National
Fire Protection Association (NFPA) 99 Standard for Health Care Facilities.
For isolation systems with a 120 V secondary, the hazard current limit is 600 microamperes for the fixed wiring on
the secondary of the isolation transformer. The limit is usually reached when 12 to 14 branch circuits are
connected. The Duplex hospital isolation panel accommodates 16 branch circuit breakers for each of its two
systems. The Duplex hospital isolation panel can also be used to satisfy requirements of the NFPA70, The
National Electrical Code

(NEC

) Article 517.19(a), Critical Care Areas. The panel can be applied to both critical
system and normal system power. One half of the panel can be used to supply critical system power, while the
other half supplies normal system power.
Features
Two complete isolated power systems in one enclosure
Available in either 5, 7 or 10 kVAratings
Each system is capable of accepting up to 16 branch circuit breakers
Each panel includes two ISO-GARD

Series D microprocessor-controlled line isolation monitors


Stainless steel trim with lockable door to restrict unauthorized access to circuit breakers and line
isolation monitors
ISO-GARD Line Isolation Monitor (LIM)
The ISO-GARD line isolation monitor is a distinct fifth-generation line isolation monitor. It uses microprocessor
technology that improves the performance, versatility, and reliability of this unit over any previous line isolation
monitors. This monitor is included as a standard component of all Square D

hospital isolation panels. The


ISO-GARD line isolation monitor can also be purchased separately and installed as a replacement for any
outdated line isolation monitor.
40
Medical Headwalls
Square D

medical headwalls help to provide services in patient care areas from a simple patient console to a
complex neonatal unit. Built to specific architectural designs and conforming to the requirements of NFPA, the
Square D medical headwalls are designed to fit into any patient care area where services such as vacuum, and
gases are required.
Axiom Patient Care Headwall
The Axiom patient care headwall is manufactured in a variety of configurations and sizes to meet the needs of
various areas of the hospital.
Features
Standard vertical equipment tracks are part of each headwall
Large selection of track accessories
Flexible headwall designs easily accept customer options
Durable, low-maintenance construction
Accept all brands of medical gas outlets or nurse call systems
Options
Nurse call
Medical gas outlets
Equipotential grounding system
Storage cabinets
Bed bumpers
Monitor support
Isolated power
Emergency electrical receptacles
Normal electrical receptacles
Slimline Surface Mounted Patient Headwall
The Slimline surface mounted patient headwall (bedhead unit) is designed to accommodate lighting, electrical
receptacles, medical gas outlets, nurse call and telephone in a convenient package. The enclosure is constructed
of extruded, heat-treated, anodized aluminum alloy sections to provide a modular, surface-mounted wall unit.
Integral horizontal raceways are included for normal power, emergency power, communications, and medical gas
pipes. The fascia can be removed for access to individual components mounted within and is available in a wide
choice of colors. Each unit is pre-wired and pre-piped for easy field connections. Plus, a wide choice of
components can be pre-installed, including medical gas outlets, electrical receptacles, switches, and
communications (nurse call, telephone, monitoring, etc.) Abuilt-in fluorescent light is available. The indirect (up)
and the reading (down) lights are available in single or dual lamps and use T-5 color corrected lamps with
electronic ballasts (lamps are included). The Slimline is ULlisted and CSArecognized. The headwall can be
manufactured in accordance to NFPA, HTM2022 or DIN standards.
Mirage

Patient Care System


The Mirage patient care systemprovides all the advantages of modular headwalls while maintaining a warm,
comfortable appearance. In addition, like Axiom

headwalls, the Mirage can be custom tailored to the needs of


each room and hospital.
Features
Heavy duty high pressure plastic laminate or real wood surfaces available in a wide range of colors and
wood grains
Special pocket doors conceal services when not in use, yet are out of the way when services are needed
Secondary equipment such as flowmeters, regulators, or Sphygmomanometer remains in place when the
doors are closed
41
The Wedge

Patient Service Column


Two fully functional headwalls in a single, freestanding unit provide flexible patient care with minimum floor space
requirements. Conceived with flexible patient access and staff productivity in mind, the Wedge patient service
columns comes complete with vertical equipment mounting rails on three sides, allowing hospital personnel to
position ventilators, pumps, IVs, and baskets exactly where needed for each patient.
Beds can be placed at whatever angle allows maximum access to the patient and best use of equipment.
Two beds can be parked at the column for recovery and pre-op applications.The unique angles of the Wedge allow
optimum access to one or two patients while using minimal floor space.
In addition, the Wedge patient services column requires only single-point connections for medical gas and
electrical services. Shipped completely pre-wired and pre-piped, the Wedge patient service columns is quickly
installed and ready for use.
Features
Patented Unimount

and Eclipse

equipment rails for pumps, IVs, and baskets


Communications wiring can be pre-installed
Dual headwall design allows two patient service
Unique angled design allows medical personnel to position the bed for access to whichever side of the
patient is necessary
Available in over 570 colors and textures to complement any dcor
Single-point connections for medical gas and electrical connections make installation simple
Manufactured to fit a hospitals specific needs
Genesis

Neonatal Patient Care Systems


Genesis neonatal patient care systems are custom manufactured to the exact requirements of the hospital.
Sample units are shown in the photographs below. We can design units to meet your specific needs, and can
manufacture to the requirements of NFPA, HTM2022, or DIN requirements. All NFPAunits are listed by
Underwriters Laboratories. All units are pre-piped and pre-wired for easy installation.
Aurora

Overbed Light Fixture


The Aurora overbed light fixture is a high-quality patient room light that provides three-way lighting with
convenience and elegance. It is designed for both acute care and general patient rooms. The Aurora light provides
examination lighting by rotating the upper portion of the fixture over to aim all four lamps on the patient. Lights in
patient rooms can sometimes be damaged or even torn off the wall by IV holders, traction bars, or other equipment
attached to a rising bed. To prevent damage to the light, the bed is plugged into a receptacle that is powered via a
microswitch in the light. If pressure is exerted under the light, the switch opens, the receptacle is de-energized, and
the bed motor is stopped. The Aurora contains four fluorescent, rapid-start lamps with separate circuits for the
down light and the up light. The fixture can be for either 3 or 4 ft. (914 or 1219 mm) lamps. Plus, night-lights are
available for either left or right hand, and are mounted within the fixture.
The Aurora fixture is designed specifically for hospital use. Smooth, flush fitting surfaces reduce housekeeping
chores. This sturdy unit has engineered resin end caps. Quality aluminum extrusions form the body and mounting
plate. Upper and lower lenses are impact resistant, non-yellowing virgin acrylic plastic.
Features
Designed specifically for hospital use
Smooth, flush fitting surfaces reduce housekeeping chores
Sturdy design has engineered resin end caps
Features quality aluminum extrusions form the body and mounting plates
Upper and lower lenses are impact resistant, non-yellowing virgin ac
42
Medium and Low Voltage Circuit Breakers
Many circuit breakers that we manufacture are not only used in our medium and low voltage switchgear,
switchboards and panelboards. We sell many breakers to OEM customers because we offer many solutions for
their needs such as the highest short circuit ratings, most reliable breakers manufactured with the least amount of
maintenance and highest switching operations. Our circuit breakers are used by OEMs who assemble or
manufacture the following equipment:
Medium and low voltage paralleling switchgear
Medium and Low voltage generator main breakers
Masterpact

Circuit Breakers
Most OEMs in the health care market have either used or are aware of our Masterpact circuit breakers. These
breakers are the workhorses of the industry that are used in the most critical equipment such as generators,
paralleling switchgear, switchgear and switchboards. They are very attractive because of their low maintenance
requirements, their wide range of short circuit protection, and electrically operated accessories.
Hospital Application
Main service low voltage switchgear Power-Zone

4, QED-6 and QED-2


Low voltage paralleling switchgear Power-Zone 4, QED-6 and QED-2
Low voltage load bank switchgear Power-Zone 4, QED-6 and QED-2
Generator main output breakers
NW ANSI
Complete product offering through 200 kAIR without fuses
800 Ato 5000 Aframes available
Rated for all AC voltage systems through 635 V
ANSI short-time withstand ratings up to 100 kA
Four racking positions connected, test, disconnected, removed with status indicator on cradle
Simple, visual contact wear indicators
Meets ANSI standard C37.13 and UL1066
Full complement of field-installable devices
Selection of four interchangeable Micrologic

trip units with PowerLogic

power metering, communications and


monitoring capabilities available in advanced trip units
Most common relay functions as defined by ANSI C37.2 and C37.90 integrated into circuit breaker
Electrically operated optional
4-pole breakers available
Mechanical and electrical operations test w/o maintenance
800 Ato 1600 Aframe 12,500 mechanical operations with 2800 electrical
ANSI value is 1750 (9700 total)
2000 Ato 3200 Aframe 10,000 mechanical operations with 1000 electrical
ANSI value is 250 (1100 total)
4000 Ato 5000 Aframe 5,000 mechanical operations with 1000 electrical
ANSI value is 250 (1100 total)
Arc flash limiting breakers available
43
NW UL489
NW UL489 circuit breaker has most of the same features as listed for the Masterpact

NW. The differences are


listed below.
Rated for all AC voltage systems through 600 V
Available for mounting in fixed or drawout configurations
Available in constructions that meet ANSI C37.13 and UL1066 standards
NT ANSI
The Masterpact NTANSI

-Certified/UL1066 Listed power circuit breaker meets or exceeds all ANSI and
UL489 design and testing standards. It also meets ANSI high level endurance testing without maintenance.
Plus, state-of-the-art, thermoset composite resin construction provides higher electrical ratings than traditional
circuit breakers all in a lighter, easier-to-install package. The Masterpact NTANSI-Certified/UL1066 Listed power
circuit breaker provides unsurpassed performance in the smallest package available on the market today.
70% smaller than standard sized 800 Ato 3200 AMasterpact NW
Meets ANSI C37.13 and UL1066. Also available in constructions that meet IEC 60947-2 and UL489
Complete product offering through 42 kAIR at 508 V
Rated for all AC voltage systems through 508 V
800 Aframe size available
ANSI short-time withstand ratings up to 42 kA
Small size allows for higher density in switchgear. Can install up to eight 800 Abreakers in one 30-inch section
of Power-Zone

4 Switchgear
Four racking positions (connected, test, disconnected and removed) with status indicator on cradle
Selection of four interchangeable Micrologic

trip units with PowerLogic

power metering, communications


and monitoring capabilities available in advanced trip units
Most common relay functions, as defined by ANSI C37.2 and C37.90, integrated into the trip unit system
Trip units, sensor plugs and most accessories are field-installable without circuit breaker adjustment
Electrically operated optional
Mechanical and electrical operations test w/o maintenance
800 A 12,500 mechanical operations with 2800 electrical ANSI value is 1750 (9700 total)
NT UL 489
NTUL489 breaker has most of the same features as listed for the Masterpact NT. The differences are listed below.
Complete product offering through 100 kAIR at 480 VAC
800 Ato 1200 Aframes available
Rated for AC voltage systems through 600 V
Short-time withstand ratings up to 35 kAand interrupting ratings up to 100 kAat 480 V
Small size allows for higher density in switchboards. Can install up to eight 1200 Abreakers in one 30'' section
of QED-6 switchboard
Masterpact Onboard Intelligence
For smarter breakers, a range of Micrologic

trip units is available. These units provide advanced functionality,


such as a communications interface, and power metering and monitoring capabilities, which allow for integration
and coordination of your electrical system. With the appropriate Micrologic trip unit, you can communicate with
breakers, gather power information, monitor events and remotely control breakers based on predetermined
conditions, leading to substantial savings in electrical system operating costs.
44
Medium Voltage Vacuum Circuit Breakers
Amodel of reliability with simplicity, the VR circuit breaker with the Type RI advanced design motor-charge stored
energy mechanism is virtually maintenance free. With an operating life exceeding the ANSI test requirements, the
RI mechanism with synchronizing crossbar is electrically and mechanically trip-free. An integral handle
(non-removable) is provided for manual charging and slow closing during testing.
The VR vacuum circuit breakers are designed for long life. The interrupters copper chromium contacts,
hermetically sealed for life in a vacuum, are protected from external atmospheric influences. Dust, moisture,
and all other possible contaminants are sealed out. This state-of-the-art vacuum interrupter design is capable
of 20 to 100 full fault interruptions (varies by rating).
The high dielectric strength of the vacuum environment allows a very short clearing time during fault interruption
to limit the energy dissipated into the arc. Total fault clearing time is less than three cycles and contact travel is
only 3/8 to 1/2 inch, depending on the ratings of the circuit breaker. The short stroke produces less mechanical
shock to the operating mechanism.
Ratings: 4.76 kV-15 kV (to 13.8 kV nominal)
1200 A, 2000 Aand 3000 A
250, 350, 500, 750 and 1000 MVAinterrupting capacity
Hospital Application
Medium voltage paralleling switchgear
Metalclad

switchgear
PowerPact

H- and J- Frame Molded Case Circuit Breakers


Designed to address the unique demands of generator manufacturers, PowerPact H- and J-Frame molded case
circuit breakers give you the right combination of features and performance to satisfy your circuit breaker
requirements. PowerPact circuit breakers deliver unmatched design flexibility across the entire range of 15 Ato
250 Aframe sizes offering the benefits of a flexible, modular circuit breaker that OEM manufacturers demand.
Design standardization enables OEM manufacturers to improve their productivity so when specifications change,
their design can remain the same.
Hospital Application
QED-6 switchboards
QED-2 switchboards
Panelboards
Generator output breaker
Feature
H-Frame 150 Aavailable in both standard and 100% ratings with standard amperage ratings from
15 Ato 150 A. Interrupting ratings (AIR) include D-18 kA, G-35 kA, J-65 kAand L-100 kAat 480 V
J-Frame 250 Aavailable in both standard and 100% ratings with standard amperage ratings from
150 Ato 250 A. Interrupting ratings (AIR) include D-18 kA, G-35 kA, J-65 kA, and L-100 kAat 480 V
Field-installable accessories are common for H- J- and D- Frame circuit breakers to make stocking
and installation easy
Unique snap-in terminals make converting bus bar and lug configurations simple and easy
Field-installable trip units lower inventory costs and reduce stocking space by configuring products
at point of use
Allows design standardization for 15 Ato 250 Aapplications with common mounting holes, handle locations,
and trim dimensions for both H- and J-Frame circuit breakers
Many configuration options provide application flexibility, with I-Line

, plug-in, drawout, rear connected


Motor operators, rotary handles and cable operators provide options for integrating into a variety of
applications
Certified to global standards, including UL, IEC, CSAand NOM
45
Enclosed Drives
Enclosed Drives
The Class 8839 Enclosed 58M family of AC Drives incorporates the Altivar

58 TRX platform to provide a robust


adjustable speed drive solution for a variety of applications. It combines rugged enclosure construction with a white
interior for the improved visibility commonly preferred by industrial users and specifiers.
The Class 8839 Enclosed 58M product is designed for maximum flexibility, tailored to your specifications.
Schneider Electric offers a wide array of pre-engineered, engineered and customizable specifier options that
include control operators, circuit breaker disconnects, fully rated isolation and bypass contactors, line reactors,
motor protection filters, door-mounted keypad display, PowerLogic

monitoring, communications, and expanded


construction features. The Class 8839 Enclosed 58M is offered in a parallel Class 8898 MCC design. Additionally,
a wide array of harmonic mitigation options such as 18-Pulse converter configurations and harmonic injection are
also available.
The drives are UL508C Listed and CSACertified to 65 kAor 100 kAshort circuit current rating depending upon the
horsepower rating selected.
Product Range
1 to 500 HP, 460 V models
1 to 50 HP, 208/230 V models
Type 1, Type 1 Aand Type 12 enclosures
The Econo-flex

family of enclosed AC drives provides an efficient and economical adjustable speed solution for
HVAC and pump applications. It combines the sturdy construction of a fully enclosed cabinet with a hinged door
and rotary through-the-door disconnect.
The Econo-flex family also offers the most optimized and efficient Type 3R outdoor rated enclosure design in the
marketplace. This gives the user the ability to free up space in congested mechanical rooms and saves cost in
wiring and installation expenses.
Options available for applications include industrial control operators, fully rated isolation and bypass contactors,
circuit breaker disconnect, line reactors and door-mounted keypad provide unparalleled value. UL508C and cUL
Listed. The following communications options are also available: Lonworks

, Modbus

and Metasys

N2.
Key Application
Pumps
Fans
Product Range
1 HPto 100 HP, 460 V models
1 HPto 50 HP, 208/230 V models
Type 1, Type 12 K and Type 3R
Type 1 and 12 K rated -10 to 40 C for indoor installations
Type 3R rated -10 to 50 C for outdoor installations
46
Other Power Distribution Products
Schneider Electric can meet a full range of power distribution needs, with circuit breakers and power breakers;
transient voltage surge suppression (TVSS), feeder and plug-in busway, control and emergency backup
transformers; NEMA-style contactors and starters; safety switches; equipment lockout; and remote racking
systems for maximum operator safety.
47
Square D

Services
Products and Engineering Services
Square D Services offers one source of service expertise on all major brands of electrical equipment.
Our solutions are designed to enhance performance, improve reliability and extend equipment life.
Power System Assessment
Evaluates the condition of the electrical system
Improves system reliability and availability
Enhances electrical safety
Provides essential documentation of system configuration, condition and maintenance
Ensures proper operation of new or modified loads
Prioritizes system improvements
Engineering Studies
Power Quality Studies
Analyze power system disturbances and interruptions that decrease productivity and reliability
Reduce cost effect of poor power quality
Troubleshooting power system problems caused from utility voltage sags, lightning or from medium voltage
capacitors switching
Harmonic Studies
Identify excessive harmonic distortion and loading
Properly size capacitors in the presence of harmonic generating loads
Evaluate and identify harmonic mitigating saving opportunities
Solve problem due to voltage notching cause by SCR firing in DC drives
Optimize existing electrical distribution system and ensure proper operation of sensitive equipment
IEEE 519 compliance
Short Circuit, Coordination and Arc Flash Analysis
Identifies overdutied equipment due to high fault currents caused by system design additions or utility
network changes
Prevents nuisance tripping of protective devices and ensures coordination with downstream devices
Checks that feeder and branch conductors are adequately protected
Generates updated AutoCAD one line diagram model of facility
Addresses ground fault coordination and grounding concerns
Identifies NEC code violations
Determines proper Personal Protective Equipment (PPE) for workers who work on energized parts per NFPA
70E or IEEE 1584
Provides arc flash tables to determine required labels for equipment
Determines arc flash boundaries for non-qualified personnel
Additional Studies available
Power factor correction
Transient motor starting
Load flow using portable metering or simulated with software
48
New Installation Services
Start-up and Commissioning
Inspection and testing of Square D

equipment prior to energization to verify equipment


Is free of damage during shipment and installation
Has been properly installed
Performs to the system design specifications
Meets optimum performance standards
Performed by factory-trained technicians, knowledgeable of our latest product innovations
Verification of proper installation through mechanical and electrical testing and inspection prior to equipment
energization
As-installed documentation to establish a baseline for future reference and trending
Training
Offered for all Square D products
Designed around customers equipment
Offered on-site and typically includes classroom and hands-on training
Customer value
Square D product knowledge
Factory-trained technicians
Customer focused
Retrofill and Upgrade
Direct Replacement Circuit Breakers
Extends the life of existing switchgear at a fraction of the cost and installation time of new equipment
Install a new circuit breaker element and carriage assembly into an existing line-up with little-to-no
modifications to the switchgear
The new circuit breaker interfaces with the existing structure and maintains safety interlocks inherent in
the original design
Designs available for most major manufacturers switchgear
Upgrades line-up to current technology with minimal downtime
Available for low- and medium-voltage equipment using Masterpact

and Magnum

circuit breakers
MV and LV Retrofill Solutions
Install a new circuit breaker and cradle into an existing switchgear cubicle, which has been adapted to accept
the new equipment
Includes new cubicle racking mechanism, primary and secondary disconnects
Designs available for most major manufacturers switchgear
Cost-effective way to upgrade switchgear to current technology
Available for low- and medium-voltage equipment


2
0
0
5

S
c
h
n
e
i
d
e
r

E
l
e
c
t
r
i
c






A
l
l

R
i
g
h
t
s

R
e
s
e
r
v
e
d



t
k
11-05 Order Number 4800SM0501
Schneider Electric - North American Operating Division
1415 S. Roselle Road
Palatine, IL 60067
Tel: 847-397-2600
Fax: 847-925-7500
C
5
Reconditioned Program
The C
5
Reconditioned program for low voltage and medium voltage power circuit breakers ensures each breaker is
Checked, Cleaned, Corrected, Calibrated and Certified through the following steps:
Complete disassembly and inspection of the circuit breaker at the component level
Clean and repaint/replate key components; replace old hardware
Identify damaged or defective components for replacement (additional charge to replace)
Relubricate moving parts and operating mechanisms
Calibrate to manufacturers specification when the circuit breaker is reassembled
Maintenance and Testing Preventive Maintenance
Periodic inspection and maintenance to help extend equipment life and ensure operating efficiency
Comprehensive mechanical and electrical testing to ensure proper functional operation, including:
Cable testing
Relay and metering calibration
Infrared testing
Also available:
Custom service agreements
Facility-wide outage management
Services also available for non-Square D

equipment
Workplace Safety
NFPA70E Training Workshop
8-hour course taught by certified instructors
Designed to provide participants with a basic understanding of safe workplace practices
NFPA70E Part 2 (Arc Flash) standards are reviewed and explained
Includes an overview of proper distribution equipment maintenance
Emergency Services and Disaster Recovery
Problem analysis
Project management
Single point of contact
1-888-SQUARED
24-Hour access to Schneider Electric
Manufacturing plants

You might also like