J08423A-E-SP-15113,Section 8):
Cable Tray system is designed as per IEC 61537
Type of cable tray are Perforated, heavy duty, return flange type of cable
tray
Cable tray, ladders, tray covers, accessories shall be manufactured from
hot-dipped galvanized (ISO 1461) mild steel. Tray thick is to be 1.5 (or) 2
mm
Metal frame supports & accessories(Document No.J08423A-E-SP-
15113,Section 9):
Metal frame supports & accessories shall be designed as per ISO 1461
Channel combinations, cantilever arms & support brackets fabricated
min. thickness of 2.5 mm mild steel. Steel is hot-dipped galvanized(ISO
1461)
Fittings & accessories fabricated min. thick of 6 mm mild steel
Queries:
We need control & power cable schedule for cable tray sizing
We need firefighting pump pipe installation location drawing in
basement of buildings?
We dont have ISO 1461 std
We dont have IEC 61537 std
Lightning Protection(Document No.J08423A-E-SP-15114,Section 10):
Lightning Protection shall be designed as per IEC 62305
Air termination networks should consist of vertical or horizontal
conductors
Combination of both depending on the type of structure to be
protected. No part of the roof (where applicable) should be more than
5m from the nearest conductor
For flat roofs a surface air termination network mesh not exceeding a
20m x 10m grid shall be inserted
For structures classed as hazardous the mesh shall be reduced to a 10m
x 5m maximum grid
Where structures consist of portions of various heights and have more
than one roof air termination network the lower roof network should
not only be joined to its own down conductors, but also joined to the
down conductors of the taller portions of the structure
Queries:
Type of earthing conductor for panel & building earthing Drawing
autocad ?
Code of Practice for Earthing (Document No.J08423A-E-SP-15114,Section
6):
Earthing shall be designed as per BS 7430
The earthing network shall consist of a main grid of bare copper
conductors directly buried in the ground and connected to bored
earthing wells with surface link boxes to permit measurement of earth
resistance
The secondary connections are made with green / yellow insulated
copper flexible conductors of suitable cross-sectional area.
The earthing of the emergency generators star point for the low voltage
systems shall be carried out by connecting the star point to the earth
grid creating a TN-S earthing system as defined in IEC 60364.
Structural Bolts(Drawing No.J08423A-S-DW-18028,Section 3):
Cable tray supports 16 mm(min. with single heavy hexagon nut as per
ASTM A563M & single washer as per ASTM F436M.
ALRAR-INLET SEPERATION AND BOOSTING FACILITIES-ALGERIA
Queries:
Please clarify the incoming supply details for the LDB, PDB & ELDB.
Please give SLDs for main lighting distribution board, main power
distribution board & main power emergency lighting distribution board.
Clarify whether emergency lighting panel connected through DG.
For Lighting calculation we are using Dailux software. We need to know
the list of fitting vendors or default we shall take Philips fittings.
Clarify whether we want to do the Cable tray sizing only for LV lighting
cables & small power Cables. Are also to MV power & control cables.
Please mention any standard earthing material sizes for building
earthing & equipment earthing.
Kindly provide Autocad drawings for all buildings.
Kindly provide sample drawings for following.
Lighting
Earthing
Lightning
Cable tray
Kindly provide price schedule for this project.
Mention whether all drawings should be done in autocad or
microstation.