GRZ100D 6F2S0851 0.8r
GRZ100D 6F2S0851 0.8r
GRZ100D 6F2S0851 0.8r
INSTRUCTION MANUAL
DISTANCE RELAY
GRZ100 - D
TOSHIBA Corporation 2006
All Rights Reserved.
( Ver. 0.8 )
1
6 F 2 S 0 8 5 1
Safety Precautions
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GRZ100. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
Explanation of symbols used
Signal words such as DANGER, WARNING, and two kinds of CAUTION, will be followed by
important safety information that must be carefully reviewed.
Indicates an imminently hazardous situation which will result in death or
serious injury if you do not follow the instructions.
Indicates a potentially hazardous situation which could result in death or
serious injury if you do not follow the instructions.
CAUTION Indicates a potentially hazardous situation which if not avoided, may result in
minor injury or moderate injury.
CAUTION Indicates a potentially hazardous situation which if not avoided, may result in
property damage.
DANGER
WARNING
2
6 F 2 S 0 8 5 1
Current transformer circuit
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
Exposed terminals
Do not touch the terminals of this equipment while the power is on, as the high voltage generated
is dangerous.
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes about 30 seconds for the voltage to discharge.
Fiber optic
Do not view directly with optical instruments.
CAUTION
Earth
The earthing terminal of the equipment must be securely earthed.
CAUTION
Operating environment
The equipment must only be used within the range of ambient temperature, humidity and dust, etc.
detailed in the specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Printed circuit board
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Carefully handle the connection cable without applying excessive force.
Modification
Do not modify this equipment, as this may cause the equipment to malfunction.
DANGER
WARNING
3
6 F 2 S 0 8 5 1
Short-link
Do not remove a short-link which is mounted at the terminal block on the rear of the relay before
shipment, as this may cause the performance of this equipment such as withstand voltage, etc., to
reduce.
Disposal
This product does not contain expendable supplies nor parts that can be recycled. When disposing
of this product, do so in a safe manner according to local regulations.
This product contains a lithium-ion battery, which should be removed at the end-of-life of the
product. The battery must be recycled or disposed of in accordance with local regulations. The
battery can be removed by withdrawing the Signal Processing module (SPM) from the relay case,
and cutting the connecting leads and plastic strap which hold the battery.
Plastics material
This product contains the following plastics material.
- ABS, Polycarbonate, Acrylic resins
4
6 F 2 S 0 8 5 1
Contents
Safety Precautions 1
1. Introduction 8
2. Application Notes 11
2.1 Power System Protection - Basic Concepts 11
2.1.1 The Function of The Protection Relay 11
2.1.2 Protection Relay Requirements 11
2.1.3 Main Protection and Backup Protection 13
2.1.4 Distance Relay - General Performance 13
2.1.5 Power Swing and Out-of-Step 14
2.2 Principle of Distance Measurement 16
2.2.1 Phase Fault 16
2.2.2 Earth Fault 17
2.3 Multi-Terminal Line Protection 19
2.3.1 Increased Use of Multi-Terminal Lines 19
2.3.2 Protection Problems on Three-Terminal Application 19
2.3.3 Three-Terminal Line Protection 21
2.4 Protection Scheme 23
2.4.1 Time-Stepped Distance Protection 23
2.4.2 Zone 1 Extension Protection 49
2.4.3 Command Protection 52
2.4.4 Directional Earth Fault Protection 69
2.4.5 Overcurrent Backup Protection 75
2.4.6 Thermal Overload Protection 81
2.4.7 Switch-Onto-Fault Protection 84
2.4.8 Stub Protection 85
2.4.9 Overvoltage and Undervoltage Protection 86
2.4.10 Broken Conductor Protection 93
2.4.11 Breaker Failure Protection 96
2.4.12 Out-of-Step Protection 99
2.4.13 Voltage Transformer Failure Supervision 102
2.4.14 Power Swing Blocking 104
2.4.15 Tripping Output Signals 110
2.5 Autoreclose 112
2.5.1 Application 112
2.5.2 Scheme Logic 114
2.5.3 Setting 124
2.5.4 Autoreclose Output Signals 126
2.5.5 Voltage and Synchronism Check Elements OVL, UVL, OVB, UVB, and
SYN 127
2.6 Fault Locator 129
2.6.1 Application 129
5
6 F 2 S 0 8 5 1
2.6.2 Distance to Fault Calculation 129
2.6.3 Starting Calculation 130
2.6.4 Displaying Location 131
2.6.5 Setting 131
3. Technical Description 133
3.1 Hardware Description 133
3.1.1 Outline of Hardware Modules 133
3.1.2 Transformer Module 137
3.1.3 Signal Processing Module 138
3.1.4 Binary Input and Output Module 139
3.1.5 Human Machine Interface (HMI) Module 142
3.2 Input and Output Signals 144
3.2.1 Input Signals 144
3.2.2 Binary Output Signals 146
3.2.3 PLC (Programmable Logic Controller) Function 147
3.3 Automatic Supervision 148
3.3.1 Basic Concept of Supervision 148
3.3.2 Relay Monitoring and Testing 148
3.3.3 CT Circuit Current Monitoring 149
3.3.4 Signal Channel Monitoring and Testing 149
3.3.5 Disconnector Monitoring 150
3.3.6 PLC Data and IEC61850 Mapping Data Monitoring 150
3.3.7 IEC61850 Communication Monitoring 150
3.3.8 Failure Alarms 150
3.3.9 Trip Blocking 151
3.3.10 Setting 152
3.4 Recording Function 153
3.4.1 Fault Recording 153
3.4.2 Event Recording 154
3.4.3 Disturbance Recording 155
3.5 Metering Function 156
4. User Interface 157
4.1 Outline of User Interface 157
4.1.1 Front Panel 157
4.1.2 Communication Ports 159
4.2 Operation of the User Interface 161
4.2.1 LCD and LED Displays 161
4.2.2 Relay Menu 163
4.2.3 Displaying Records 166
4.2.4 Displaying Status Information 171
4.2.5 Viewing the Settings 175
4.2.6 Changing the Settings 176
4.2.7 Testing 200
4.3 Personal Computer Interface 206
6
6 F 2 S 0 8 5 1
4.4 Communication Interface 206
4.4.1 RSM (Relay Setting and Monitoring System) 206
4.4.2 IEC 60870-5-103 Interface 207
4.4.3 IEC 61850 Interface 208
4.5 Clock Function 208
5. Installation 209
5.1 Receipt of Relays 209
5.2 Relay Mounting 209
5.3 Electrostatic Discharge 209
5.4 Handling Precautions 209
5.5 External Connections 210
6. Commissioning and Maintenance 211
6.1 Outline of Commissioning Tests 211
6.2 Cautions 212
6.2.1 Safety Precautions 212
6.2.2 Cautions on Tests 212
6.3 Preparations 213
6.4 Hardware Tests 214
6.4.1 User Interfaces 214
6.4.2 Binary Input Circuit 215
6.4.3 Binary Output Circuit 216
6.4.4 AC Input Circuits 217
6.5 Function Test 218
6.5.1 Measuring Element 218
6.5.2 Timer Test 237
6.5.3 Protection Scheme 238
6.5.4 Metering and Recording 243
6.5.5 Fault Locator 243
6.6 Conjunctive Tests 244
6.6.1 On Load Test 244
6.6.2 Signaling Circuit Test 244
6.6.3 Tripping and Reclosing Circuit Test 246
6.7 Maintenance 248
6.7.1 Regular Testing 248
6.7.2 Failure Tracing and Repair 248
6.7.3 Replacing Failed Modules 250
6.7.4 Resumption of Service 252
6.7.5 Storage 252
7. Putting Relay into Service 253
7
6 F 2 S 0 8 5 1
Appendix A Block Diagrams 255
Appendix B Signal List 259
Appendix C Variable Timer List 301
Appendix D Binary Input/Output Default Setting List 303
Appendix E Details of Relay Menu and LED & Button Operation 307
Appendix F Case Outline 317
Appendix G External Connections 325
Appendix H Relay Setting Sheet 329
Appendix I Commissioning Test Sheet (sample) 353
Appendix J Return Repair Form 359
Appendix K Technical Data 365
Appendix L Symbols Used in Scheme Logic 377
Appendix M Example of Setting Calculation 381
Appendix N IEC60870-5-103: Interoperability and Troubleshooting 393
Appendix O Programmable Reset Characteristics and Implementation of Thermal
Model to IEC60255-8 405
Appendix P IEC61850: MICS & PICS 409
Appendix Q Inverse Time Characteristics 447
Appendix R Failed Module Tracing and Replacement 451
Appendix S Ordering 457
The data given in this manual are subject to change without notice. (Ver.0.8)
8
6 F 2 S 0 8 5 1
1. Introduction
GRZ100 is a fully numeric distance protection for application to transmission lines on solidly
earthed network.
The GRZ100 provides the following protection schemes.
- Time-stepped distance protection with four forward zones, three reverse zones, and one
non-directional zone
- Zone 1 extension protection
- Command protection (Distance protection using telecommunication)
- Overcurrent backup protection
- Thermal overload protection
- Switch-on-to-fault and stub protection
- Circuit breaker failure protection
- Broken conductor detection
- Out-of-step protection
- Overvoltage and undervoltage protection
For high-resistance earth faults, the GRZ100 provides the following directional earth fault
protections.
- Directional earth fault protection
- Directional earth fault protection utilizing telecommunications facilities
The GRZ100 actuates high-speed single-shot autoreclose or multi-shot autoreclose.
The GRZ100 provides the following metering and recording functions.
- Metering
- Fault record
- Event record
- Fault location
- Disturbance record
The GRZ100 provides the following menu-driven human interfaces for relay setting or viewing of
stored data.
- Relay front panel; LCD, LED display and operation keys
- Local PC
- Remote PC
Password protection is provided to change settings. Eight active setting groups are provided. This
allows the user to set one group for normal operating conditions while other groups may be set to
cover alternative operating conditions.
GRZ100 can provide the following serial interface ports:
9
6 F 2 S 0 8 5 1
- RS232C for a local PC and Relay Setting and Monitoring System (RSM100)
- RS485 for a remote PC, and Relay Setting and Monitoring System (RSM100) or Substation
control and Automation System (SAS) with IEC60870-5-103 protocol
- Fibre Optic (FO, option) for a remote PC, and Relay Setting and Monitoring System
(RSM100) or Substation control and Automation System (SAS) with IEC60870-5-103
protocol
- 100BASE-TX, or -FX (option) for Substation control and Automation System (SAS) with
IEC61850 protocol
Another interface IRIG-B port is provided for an external clock connection.
The RS232C port is located on the front panel of the relay. Other ports (RS485, FO,
100BASE-TX, 100BASE-FX and IRIG-B) are located on the rear of the relay.
Further, the GRZ100 provides the following functions.
- Configurable binary inputs and outputs
- Programmable logic for I/O configuration, alarms, indications, recording, etc.
- Automatic supervision
The GRZ100 has the following models:
Relay Type and Model
Relay Type:
- Type GRZ100; Numerical distance relay
Relay Model:
- Model 200 series: With autoreclose for single breaker scheme
Model 201D; 18 binary inputs, 23 binary outputs, 6 binary outputs for tripping
- Model 300 series: With autoreclose for one-and-a-half breaker scheme
Model 301D; 18 binary inputs, 23 binary outputs, 6 binary outputs for tripping
Model 303D; 24 binary inputs, 41 binary outputs, 6 binary outputs for tripping
10
6 F 2 S 0 8 5 1
Table 1.1.1 shows the measuring elements incorporated.
Table 1.1.1 Incorporated Measuring Elements
Model
Measuring elements
201 301, 303
Z1S, Z1SX, Z2S, Z3S,
ZFS, ZR1S, ZR2S, Z4S,
ZNDS
Distance element (phase fault)
Z1G, Z1GX, Z2G, Z3G,
ZFG, ZR1G, ZR2G,
Z4G, ZNDG
Distance element (earth fault)
UVC Phase selection element
DEFF, DEFR Directional earth fault element
OC, OCI Overcurrent element (phase fault)
EF, EFI Overcurrent element (earth fault)
SOTF (OCH) Switch-onto-fault protection
VTF (OVG, UVF, OCD) VT failure supervision
PSBS, PSBG Power swing blocking
OST Out-of-step tripping
BF Breaker failure protection
THM Thermal overload protection
OVS1, OVS2, OVG1,
OVG2, UVS1, UVS2,
UVG1, UVG2
Overvoltage & undervoltage
protection
BCD Broken conductor detection
FL Fault locator
ARC (SYN, UV, OV) Autoreclose function 1CB 2CB
Automatic monitoring AMF
Automatic testing
(Signal channel testing)
11
6 F 2 S 0 8 5 1
2. Application Notes
2.1 Power System Protection - Basic Concepts
2.1.1 The Function of The Protection Relay
The protection relay, which protects the power system from various faults, plays an extremely
important role in power system stability. Its main functions are as follows:
Prevention of power supply interruption:
Fault clearance and resumption of healthy power transmission as soon as
possible.
Prevention of damage to equipment:
Consecutive system faults will eventually lead to damage to primary
plant, for example destruction of insulators, rupture of lines, burning of
transformers, etc. The protection relay can help prevent such damage to
equipment.
Prevention of system instability:
is necessary to remove Power system faults at high speed by using
protection relays as the existence of a system fault for an extended period
of time may initiate a generator out-of-step condition.
2.1.2 Protection Relay Requirements
The protection relay, which plays the important role of protecting the power system from faults,
must meet several requirements. These requirements can be summarized as follows:
a) Selectivity: All faults that occur on the power system should be removed but at the same time
it must be ensured that only the minimum section of the power system must be
isolated in order to clear the fault. Figure 2.1.2.1 shows typical different
protection zones on the power system. In order to provide complete coverage by
the protection, the neighboring protection zones are set to overlap. Figure 2.1.2.2
shows the relationship between the circuit breaker and CT locations. In Figure
(a), the CTs are installed on both sides of the circuit breaker, one for line
protection and the other for busbar protection, enabling the protection coverage
to overlap. Figure (b) shows the case where the same CT is used for both the line
protection and busbar protection. In this case, the line protection would operate
for a fault which occurred midway between the CT and circuit breaker, but the
busbar protection would not operate, thus failing to remove the fault. It is
important to prevent blind spots in power system protection design.
b) High speed: In order to avoid damage to equipment or power system instability, it is
important to shorten the duration of faults by applying high-speed protection
relays. The GRZ100 has a minimum operating time of 18 ms. However, the
operating time of the circuit breaker and transmission delay in the case of carrier
protection, etc. must also be taken into consideration.
12
6 F 2 S 0 8 5 1
Figure 2.1.2.1 Protection Zones
(a) (b)
Figure 2.1.2.2 Protection Zone and CB, CT
c) Reliability: The protection relay is normally in a quiescent state and is available to respond to
faults that may occur on the power system in the protection zone.
In order that this may be achieved the availability of the protection relay is
checked even in its quiescent state.
A fundamental requirement to ensure that the reliability of the protection relay is
high is that its components must be extremely reliable. This can be achieved by
using high quality components and reducing the number of components. The
GRZ100 reduces the number of parts by using state-of-the-art highly integrated
semiconductor components.
To maintain high reliability, not only must the relay have a robust hardware
structure but it is also important to detect any fault immediately and not to leave
the relay in a faulted state for prolonged periods. Therefore, the GRZ100 is
equipped with an automatic supervision function. Whenever a hardware fault
occurs, an alarm is issued to inform the operator of the problem to permit
remedial action.
In order to dramatically improve the operating reliability of the relay in the event
of a system fault, there are two options: to use a protection relay with a
duplicated protection system or to provide an additional fault detection relay
within the relay with AND logic.
Line Line
Busbar Busbar
:Circuit Breaker
Busbar
Busbar Busbar
Line Line
13
6 F 2 S 0 8 5 1
2.1.3 Main Protection and Backup Protection
The power system protection system generally consists of a main protection and a backup
protection to reliably remove all faults. In principle, system faults must be removed in the shortest
possible time and cause the minimum outage. This important function is served by the main
protection. In distance protection, this function is served by the zone 1 element and command
protection, etc. However, the main protection may not always function perfectly. For example, the
main protection relay may not be able to function correctly due to a power supply failure, CVT
failure, data transmission device failure, circuit breaker failure or failure of the main protection
relay itself. In such cases, power system integrity depends on the backup protection.
The backup protection provides power system protection with a set time delay, its timer value is
set in a range that allows coordination with the main protection. To achieve time coordination with
the main protection, the time delay of the backup protection is determined with a margin in
consideration of the following factors:
Operating time of main protection relay
Operating time of circuit breaker
Reset time of backup protection relay
There are two types of backup protection: remote backup protection that provides backup from a
remote substation at a different location to the main protection, and local backup protection
installed in the same location as that of the main protection that provides backup from that
substation.
Each of these protections has the following features:
Remote backup protection: Possible causes for main protection failures include relay faults,
power supply faults, and various other factors. It is therefore
important to provide backup protection from a remote substation to
prevent the backup protection from failing due to the same causes as
the local main protection. The zone 2 and zone 3 elements of distance
relays, etc. provide as these remote backup protection functions.
Local backup protection: Provides backup protection at the same substation as that of the main
protection and often has the purpose of providing backup when the
circuit breaker fails to operate.
2.1.4 Distance Relay - General Performance
For distance relays, the reach of the zone 1 protection is usually set to approximately 80 to 90% of
the length of the transmission line. This is to ensure that overreach tripping does not occur for
external faults that occur beyond the busbar at the remote end. For internal faults that occur
beyond the reach of zone 1, time delayed tripping by the zone 2 element is applied. High-speed
tripping can be achieved by means of a "command protection system" that exchanges relay
operation information with the remote end.
There are various causes for measuring errors in a distance relay. In the case of a fault with
resistance, the reactance component seen by the relay at the power sending terminal is smaller than
the actual value and it tends to overreach. On the contrary, the reactance component seen by the
relay at the power receiving terminal is greater than the actual value and it tends to underreach.
The line impedance has different values in different phases. When its average value is used for the
relay setting, underreach will occur in a phase with a greater impedance than the average value. In
the case of fault resistance, its impedance is greater for earth faults where the fault is grounded via
a steel tower or tree rather than a phase fault consisting of arc resistance only. Therefore,
measuring errors in the earth fault relay are generally greater than those in the phase fault relay.
The fault arc is considered to be almost equivalent to pure resistance. But if the phase of a current
that flows into a fault point from the remote end is different from the phase of the local current, the
14
6 F 2 S 0 8 5 1
voltage at the fault will have a phase angle difference with respect to the local current, producing a
measuring error in the distance relay with the principle of measuring the reactance component.
The existence of a zero-sequence current on the protected line and adjacent line can also cause
errors in the earth fault relay. The zero-sequence current normally acts in the direction of relay
underreaching due to the effect of the induced voltage. The compensation method will be
described in detail in the next section. The earth fault relay contains more errors than the phase
fault relays even with these compensation methods. Therefore, the earth fault relays are usually set
with a greater margin than the phase fault relays.
Regarding protection relay measuring errors, it is also necessary to consider hardware errors in the
relay itself, errors introduced by coupling capacitor voltage transformers (CCVT), and transient
overreach errors caused by the DC component of the fault current. For GRZ100, the total of these
errors is specified to be less than 5%.
2.1.5 Power Swing and Out-of-Step
Power swings occur when the output voltages of generators at different points in the power system
slip relative to each other, as a result of system instabilities which may be caused by sudden
changes in load magnitude or direction, or by power system faults and their subsequent clearance.
During the course of such a power swing, the impedance seen by a distance relay may move
(relatively slowly) from the load area into the distance protection operating characteristic. In fact,
this phenomenon appears to the distance protection measuring elements like a three phase fault
condition and may result in tripping if no countermeasure is applied. Most power swings are
transient conditions from which the power system can recover after a short period of time, and
distance protection tripping is therefore highly undesirable in such cases. GRZ100 provides a
power swing blocking function (PSB) to prevent unwanted tripping during a power swing. Figure
2.1.5.1 illustrates the typical impedance locus as seen by a distance relay during a transient power
swing.
Figure 2 1.5.1 Impedance Locus during Transient Power Swing
A special case of the power swing condition occurs when the power system disturbance is so
severe that generators lose synchronism with each other and are said to be out-of-step. During an
out-of-step condition the phase angle between generators continues to increase and pass through
180, at which point a distance relay measures an impedance equal to that for a three phase fault at
the centre of the power system. The impedance locus typically describes an arc passing through
the electrical centre, as shown in Figure 2.1.5.2.
X
R
Load Area
Distance protection
characteristic (Mho)
Impedance locus during
transient power swing
15
6 F 2 S 0 8 5 1
Figure 2.1.5.2 Impedance Locus during Out-of-Step Condition
In the case of a full out-of-step condition (as opposed to a transient power swing) it is desirable to
separate the system in the vicinity of the centre of the out-of-step condition. GRZ100 provides an
out-of-step detection element (OST) which can provide tripping in these circumstances.
Although the power swing and out-of-step conditions are very closely related (in fact one is
simply the most severe form of the other), completely different actions are required from the
protection relay. The PSB function must ensure stability of the distance protection during transient
power system conditions, while the OST element initiates system separation by tripping in the
event that a severe power swing results in potentially irrecoverable loss of stability in the power
system. The PSB and OST elements are therefore completely separate functions within the
GRZ100 relay, with different characteristics, separate scheme logic and different settings.
X
R
Load Area
Distance protection
characteristic (Mho)
Impedance locus during
out-of-step condition
16
6 F 2 S 0 8 5 1
2.2 Principle of Distance Measurement
2.2.1 Phase Fault
The phase-fault distance relay measures the impedance from the relay to the fault point using a
delta voltage and current. The positive-sequence impedance is used as the line impedance. The
principle is described below.
Figure 2.2.1.1 shows the circuit in the event of a two-phase fault. Suppose that the impedance from
the relay to the fault is the same in both phase B and phase C, and that the self impedance is Z
s
and
the mutual impedance between phases is Z
m
. If the voltages and currents of phase B and phase C
are V
b
, V
c
, I
b
and I
c
and the fault point voltage is V
F
, then V
b
and V
c
are given by the following
equations.
V
b
= Z
s
I
b
+ Z
m
I
c
+ V
F
....................... (2-1)
V
c
= Z
s
I
c
+ Z
m
I
b
+ V
F
....................... (2-2)
From equations (2-1) and (2-2), the following equation is obtained.
V
b
V
c
= (Z
s
Z
m
) (I
b
I
c
) ......................... (2-3)
where,
Z
s
: Self impedance
Z
m
: Mutual impedance
Since the effect of the phase A current is small and is almost canceled when introducing equation
(2-3), it is omitted in equations (2-1) and (2-2).
When each phase of the line is symmetric to the other, the positive-sequence and zero-sequence
impedance Z
1
and Z
0
according to the method of symmetrical components are defined by the
following equations, using self impedance Z
s
and mutual impedance Z
m
:
Z1 = Zs Zm............................................... (2-4)
Z0 = Zs + 2Zm............................................. (2-5)
where,
Z
1
: Positive-sequence impedance
Z
0
: Zero-sequence impedance
Equation (2-3) can be rewritten as follows:
Z
1
= (V
b
V
c
)/(I
b
I
c
) .............................. (2-6)
As shown above, the positive-sequence impedance is used for the phase fault relay setting.
Figure 2.2.1.1 Two-Phase Fault
V
a
Z
s
V
F
V
F
V
b
i
b
V
c
i
c
Z
m
17
6 F 2 S 0 8 5 1
2.2.2 Earth Fault
Figure 2.2.2.1 shows the circuit in the event of a single-phase earth fault. It is not simple to exactly
measure the distance up to the fault point for a single-phase earth fault.
This is because the impedance of the zero-sequence circuit including the earth return is generally
different from the positive-sequence impedance. Therefore, the faulted phase voltage is not simply
proportional to the faulted phase current.
Figure 2.2.2.1 Single-Phase Earth Fault
It is necessary to analyze the impedance seen by the relay in the event of a single-phase earth fault
according to the method of symmetrical components. Figure 2.2.2.2 shows an equivalent circuit
for the single-phase earth fault based on the method of symmetrical components. Assuming the
positive-sequence, negative-sequence and zero-sequence voltages are V
1F
, V
2F
and V
0F
, the
voltage at the relay point of each symmetrical circuit is given by the following equation. However,
suppose that the positive-sequence impedance and negative-sequence impedance are the same and
influences of the fault resistance are ignored.
V
1
= Z
1
I
1
+ V
1F
..................................... (2-7)
V
2
= Z
1
I2
+ V
2F
..................................... (2-8)
V
0
= Z
0
I
0
+ Z
0m
I
0m
+ V
0F
............... (2-9)
where, V
1
: Relay point positive-sequence voltage
V
2
: Relay point negative-sequence voltage
V
0
: Relay point zero-sequence voltage
V
1F
: Fault point positive-sequence voltage
V
2F
: Fault point negative-sequence voltage
V
0F
: Fault point zero-sequence voltage
I
1
: Relay point positive-sequence current
I
2
: Relay point negative-sequence current
I
0
: Relay point zero-sequence current
I
0m
: Adjacent line zero-sequence current
Z
1
: Fault point - relay point positive-sequence impedance
Z
0
: Fault point - relay point zero-sequence impedance
Z
0m
: Adjacent line zero-sequence mutual impedance
Taking account of the fact that the faulted phase voltage V
aF
at the point of fault is,
V
aF
= V
1F
+ V
2F
+ V
0F
= 0......................................... (2-10)
phase A voltage V
a
at the relay is calculated from the following equation:
i
a
v
aF
v
a
v
b
v
c
18
6 F 2 S 0 8 5 1
V
a
= V
1
+ V
2
+ V
0
= Z
1
(I
a
+ (Z
0
Z
1
)/Z
1
I
0
+ Z
0m
/Z
1
I
0m
) ...... (2-11)
Where, I
a
is the current at phase "a" relay point and is defined in the following equation by the
symmetrical component of the current:
I
a
= I
1
+ I
2
+ I
0
.............................................................. (2-12)
Here, defining the current synthesized by the phase "a" relay as I
a'
, and
I
a'
= I
a
+ (Z
0
Z
1
)/Z
1
I
0
+ Z
0m
/Z
1
I
0m
................ (2-13)
then equation (2-11) can be rewritten as the following equation:
V
a
= Z
1
I
a'
................................................................... (2-14)
That is, positive-sequence impedance Z
1
up to the fault point can be obtained from the simple ratio
of phase "a" voltage V
a
to compensated current I
a'
according to equation (2-14).
Obtaining the compensated current according to equation (2-13) is called "zero-sequence
compensation." Note in this zero-sequence compensation, the compensation coefficient (Z
0
Z
1
)/Z
1
and Z
0m
/Z
1
are not real numbers, but complex numbers. The GRZ100 relay has a
configuration that allows this compensation coefficient to be set as a complex number and setting
the coefficient correctly makes it possible to measure exactly the distance up to the fault point.
In equations (2-7) to (2-9), the fault resistance was ignored. Since the measurement of the distance
up to the fault point based on equation (2-14) is carried out using the reactance component, in
principle there is no influence on the voltage component due to the fault resistance. However,
under real operating conditions, distance measurement errors are produced as a result of the fault
resistance combined with the power flow or the current flowing into the fault point from the point
opposite the relay location.
Figure 2.2.2.2 Equivalent Circuit of Single-Phase Earth Fault
V
1
V
1F
V
0F
V
2F
Z
1 I
1
V
2
I
2
V
0
I
0
Z
1
Z
0
Negative-sequence circuit
Zero-sequence circuit
Positive-sequence circuit
19
6 F 2 S 0 8 5 1
2.3 Multi-Terminal Line Protection
2.3.1 Increased Use of Multi-Terminal Lines
The number of multi-terminal transmission lines has increased in recent years, mainly for
economic reasons. For example, connecting three substations through three-terminal transmission
lines can reduce the construction cost considerably compared to connecting substations through
individual lines. On the other hand, from the standpoint of protection, multi-terminal lines cause
various difficulties. Taking an example of a three-terminal line, these problems are illustrated
below.
2.3.2 Protection Problems on Three-Terminal Application
2.3.2.1 Underreach in the Case of an Internal Fault Further than the Branch Point
In the three-terminal line shown in Figure 2.3.2.1, if a phase fault occurs near terminal C, the fault
current flows in from both terminal A and terminal B and the voltages at terminal A and terminal
B are influenced by the current from one another, have represented by the following equations:
V
A
= I
A
(Z
1
+ Z
3
) + I
B
Z
3
..................................... (2-15)
V
B
= I
B
(Z
2
+ Z
3
) + I
A
Z
3
..................................... (2-16)
where, V
A
: Voltage at terminal A
V
B
: Voltage at terminal B
I
A
: Current at terminal A
I
B
: Current at terminal B
Z
1
: Impedance from terminal A to branch point
Z
2
: Impedance from terminal B to branch point
Z
3
: Impedance from fault point to branch point
From equations (2-15) and (2-16), impedance Z
A
and impedance Z
B
seen from the relay at
terminal A and terminal B are given by the following equations:
Z
A
= V
A
/I
A
= (Z
1
+ Z
3
) + Z
3
I
B
/I
A
......................... (2-17)
Z
B
= V
B
/I
B
= (Z
2
+ Z
3
) + Z
3
I
A
/I
B
.......................... (2-18)
From equation (2-17), the impedance seen from the relay at terminal A is greater than the actual
impedance (Z
1
+ Z
3
) up to the fault point by (Z
3
I
B
/I
A
). That is, if the current infeed from local
terminal A is large its influence is small, but if the current infeed from local terminal B is large the
relay sees the fault point much further than the actual distance.
Z
3
Z
1
Terminal A
Terminal C
Terminal B
Z
2
Figure 2.3.2.1 Three-terminal line
20
6 F 2 S 0 8 5 1
2.3.2.2 Current Outfeed in the Event of an Internal Fault
In the event of an internal fault in a multi-terminal system, a fault current may flow out of a
specific terminal. An example is shown using a three-terminal system with two parallel lines
shown in Figure 2.3.2.2. The figure shows the case where only one circuit is used and another
circuit is open at terminal A. If a fault occurs at a close to terminal C, there is a route through which
the current flows from terminal B via the adjacent line into terminal C and part of the fault current
flows out of terminal B and flows into terminal C again. The magnitude of the outfeed current is a
maximum of approximately 1/2 of the infeed current from terminal A. If the fault point is
examined from terminal A, the impedance of the adjacent circuit between terminal B and terminal
C enters in parallel, and consequently the relay at terminal A sees it as smaller than the actual
impedance up to the fault point, which means this relay tends to overreach.
It is difficult to protect the system when a fault current flows out of one end. Since an ordinary
directional comparison method judges an external fault at one end and sends a block signal, it may
fail to remove the fault.
Figure 2.3.2.2 Current Outfeed in Event of Internal Fault
2.3.2.3 Diversion of Outfeed Current in the Event of an External Fault
If an external fault occurs at terminal C in the three-terminal system shown in Figure 2.3.2.3, the
fault current that flows into terminal A may not only flow out of terminal C but may also flow out
of terminal B and flow into the fault point. In this case, outfeed currents I
B
from terminal B and I
C
from terminal C become smaller than infeed current I
A
from terminal A. That is,
(Outfeed current) < (infeed current)............................... (2-19)
The directional comparison method sometimes cannot detect external faults under such
conditions, increasing the possibility of unwanted operation due to detection of an internal fault
from terminal A.
Terminal A Terminal C
Terminal B
I
B
I
C
I
A
Figure 2.3.2.3 Outfeed Current in Event of External Fault
Terminal A Terminal C
Terminal B
I
C
I
B
I
A
21
6 F 2 S 0 8 5 1
2.3.2.4 Possible Attenuation of Carrier Wave in Power Line Carrier
There are no particular problems related to power line carrier or multi-terminal lines. However,
when the distance of the line from a branch point is 1/4, 3/4, 5/4 and 7/4, etc. of the wavelength of
the carrier wave, the reflected wave from the branch line may cause considerable attenuation of the
carrier signal, and thus care is required in selecting the carrier frequency. Furthermore, when the
same carrier frequency is used for each terminal, the signal from each terminal may not be
received due to the beat phenomenon, and thus it is desirable to use the carrier wave for each
terminal with a different frequency in a multi-terminal system.
2.3.3 Three-Terminal Line Protection
2.3.3.1 Distance Relay Protection
The relay at terminal A in Figure 2.3.2.1 will underreach due to an infeed current from terminal B.
However, the zone 1 element of distance relay should not overreach for a fault on the busbar at the
remote end under any conditions. Therefore, the relay at terminal A is set so that it may operate
correctly for faults within the protected zone in the absence of a power source at terminal B. This
makes it unavoidable for the relay at terminal A to permit considerable underreach for an infeed
current from terminal B.
When there is a branch point on the line between terminal A and terminal B and it is connected
with terminal C via a short-distance line as shown in Figure 2.3.3.1, the setting range of the zone 1
element at terminal A and terminal B can only include part of the entire length of the line as shown
in the figure to avoid unwanted operations for external faults at terminal C. Therefore, for most of
the faults on this line, one end is delayed-tripped by the zone 2 element. To avoid such a problem
a directional comparison method or current differential method must be used.
Figure 2.3.3.1 Short-Distance Tapped Line (1)
2.3.3.2 Command Protection
Permissive Underreach Protection (PUP)
With the Permissive Underreach Protection (PUP) method, all the terminals are tripped via
transmission if zone 1 element operates at least at one terminal. In this system, a common power
line carrier is available.
In the system shown in Figure 2.3.3.2 where both terminal B and terminal C are near the branch
point and connected via a short-distance line, the distance relay at terminal B and terminal C must
unavoidably be set to an extremely short distance to prevent unwanted operations by busbar faults
at each other's end. In order for the relay at terminal A not to operate on a busbar fault at terminal
B or terminal C, it may not be able to set the branch point within the protection range, containing
a zone in which it is impossible to detect the fault as an internal fault. The fault in this zone is
removed by tripping of zone 2. When a current flows out of terminal B in the event of a fault inside
terminal C as shown in the example in Figure 2.3.2.2, the PUP system performs tripping of
terminal B sequentially following the tripping of terminal C.
Terminal B Terminal A
Terminal C
22
6 F 2 S 0 8 5 1
Figure 2.3.3.2 Short-Distance Tapped Line (2)
Permissive Overreach Protection (POP)
The Permissive Overreach Protection (POP) method carries out tripping on condition that zone 2
of each terminal (or zone 3 depending on the setting) has operated for an internal fault.
Accordingly it needs to use a different transmission channel when applied to three terminals.
Zone 2 in the POP method basically covers up to and including the busbar of all terminals at the
remote end of the protected zone. If the source behind each terminal is strong enough, in this
scheme all terminals will operate their distance relays for a fault in the protected zone. However, if
the impedance behind the power source changes, there is a tendency to underreach as a
consequence of the "branch effect." Therefore, it is necessary to check that the relay can operate
for faults in the protected zone even under the worst power source conditions.
Blocking Schemes
With the blocking scheme, a terminal sends a blocking signal to the other terminal for an external
fault and a common power line carrier channel can be used. It can also perform high-speed
tripping even if one end of the multi-terminal line is a non-power source and there is no fault
current infeed.
In the blocking scheme, it is necessary to pay attention to diversion of the outfeed current in the
event of an external fault. In the system shown in Figure 2.3.2.3, if a fault current flows out of
terminals B and C for an external fault, the outfeed currents of terminal B and terminal C are
smaller than the infeed current at terminal A due to the diversion. Therefore, it may be difficult to
operate the external detection relay of one terminal depending on the ratio of diversion.
Terminal B Terminal A
Terminal C
23
6 F 2 S 0 8 5 1
2.4 Protection Scheme
The GRZ100 series has the following protection schemes and is applied to transmission lines of
directly earthed networks. The function of high-speed detection and clearance of faults ensures
that the disturbance to the power system is kept to a minimum in combination with the built-in
autoreclose functions. Appendix A shows block diagrams of the GRZ100 series.
time-stepped distance protection
zone 1 extension protection
command protection (distance protection using telecommunication)
directional earth fault protection
overcurrent backup protection
thermal overload protection
SOTF and stub protection
overvoltage and undervoltage protection
broken conductor detection
circuit breaker failure protection
out-of-step protection
2.4.1 Time-Stepped Distance Protection
2.4.1.1 Application
Using reach and tripping time settings coordinated with adjacent lines, the GRZ100 provides up to
four steps of distance protection for forward faults and backup protection for reverse faults. These
are used as the main protection when telecommunications are not available, or as backup
protection for the protected line and adjacent lines.
The GRZ100 has maximum eight distance measuring zones for both phase and earth faults,
maximum four zones for forward faults and maximum three zones for reverse faults respectively.
There is also one non-directional zone. The zones can be defined with either mho-based
characteristic or quadrilateral characteristic. The characteristic is selected by setting the scheme
switch [ZS-C] for phase fault and [ZG-C] for earth fault to "Mho" or "Quad".
Figure 2.4.1.1 shows the mho-based characteristics. Zone 1 (Z1), Zone 1X (Z1X), Zone 2 (Z2),
additional forward Zone F (ZF) and reverse Zone R1 (ZR1) have a complex characteristic
combining the reactance element, mho element and blinder element, while Zone 3 (Z3), additional
reverse Zone R2 (ZR2) and Z4 elements have a complex characteristic combining the mho
element and blinder element. ZND elements have a complex characteristic combining the
impedance element and blinder element. Z3 is also used for detection of forward faults in
command protection. If Z3 is dedicated to command protection, ZF can be used for Zone 3 instead
of Z3 in time-stepped distance protection.
The blinder element (BFR) can be provided for each forward zone. The setting of blinder element
can be set independently or set common to forward zones by the scheme switch [BLZONE].
Figures 2.4.1.1 and 2.4.1.2 show the characteristics with an independent setting.
Since the Z4 is used for detection of reverse faults in command protection, the Z4 for phase faults
has an offset characteristic with an offset mho element which assures detection of close-up phase
faults. The operation of Z4 for phase faults in the event of internal faults is inhibited by the
operations of Z2, ZF and Z3.
24
6 F 2 S 0 8 5 1
Figure 2.4.1.2 shows the quadrilateral characteristics. These have a complex characteristic
combining the reactance element, directional element and blinder element.
The Z4 for phase faults has an offset characteristic with an offset directional element which
assures detection of close-up phase faults.
The operation is the same as the mho-based characteristics.
X
Z1XS
Z2S
Z4S
Z3S
Z1S
Z1S1
Z1S2
ZR1S
ZR2S
ZNDS
BFLS
BFRS
BRLS
BS: Blinder elements
BRRS
BNDS
R
75
ZFS
Z3S
Z4S
BNDS
X
Z1XG
Z2G
Z4G
Z3G
Z1G
Z1G1
Z1G2
ZR1G
ZR2G
BFLG
BFRG
BRLG
BRRG
BG: Blinder elements
ZNDG
BNDG
BNDG
R
75
ZFG
Z3G
Z4G
(a) Phase fault element (b) Earth fault element
Figure 2.4.1.1 Mho-based Characteristics
R
X
Z1XG
Z2G
Z4G
Z3G
Z1G
Z1G1
Z1G2
ZBG
ZFG
ZR2G
ZR1G
ZNDG
BFRG
BFLG
BRLG
BRRG
ZNDG
BNDG
BNDG
BG: Blinder elements
75
R
X
Z1XS
Z2S
Z4S
Z3S
Z1S
Z1S1
Z1S2
ZBS
ZFS
ZR2S
ZR1S
ZNDS
BFRS
BFLS
BNDS
BNDS
BRLS
BRRS
ZNDS
BS: Blinder elements
75
(a) Phase fault element (b) Earth fault element
Figure 2.4.1.2 Quadrilateral Characteristics
Figure 2.4.1.3 shows typical time-distance characteristics of the time-stepped distance protection
provided at terminal A.
25
6 F 2 S 0 8 5 1
Zone 1 is set to cover about 80% of the protected line. When GRZ100 is used as the main
protection, zone 1 generally provides instantaneous tripping but if used as a backup protection,
time delayed tripping can be provided. With the GRZ100, 5 types of zone 1 tripping modes can be
set using the trip mode setting switch.
Zone 2 is set to cover about 120% or more of the protected line, providing protection for the rest of
the protected line not covered by zone 1 and backup protection of the remote end busbar. In order
to coordinate the fault clearance time by the main protection, with the zone 1 protection of the
adjacent lines or by the remote end busbar protection, zone 2 carries out time delayed tripping.
Time
TR1
T3
T2
T1
C B A
Reverse Zone R1
Zone 2
Zone 1
Zone 3
Reverse Zone R2 TR2
TND
Zone ND Zone ND
(TF)
(Z3 or ZF)
Figure 2.4.1.3 Time/Distance Characteristics of Time-Stepped Distance Protection
Zone 3 is mainly provided for remote backup protection of adjacent lines. Its reach is set to at least
1.2 times the sum of the impedance of the protected line and the longest adjacent line. The zone 3
time delay is set so that it coordinates with the fault clearance time provided by zone 2 of adjacent
lines. (Z3 is applied to Zone 3. Z3 is also used for detection of forward faults in command
protection. If Z3 is dedicated to command protection, ZF can be used for Zone 3 instead of the Z3.)
The reverse looking zone R1 and R2 elements are used for time delayed local backup protection
for busbar faults and transformer faults. Furthermore, when applied to multi-terminal lines, it is
effective as the backup protection for adjacent lines behind the relaying point instead of the zone 3
protection at the remote terminal. This is because it is difficult for zone 3 at terminals A and C to
provide remote backup protection for the fault shown in Figure 2.4.1.4 due to fault infeed from the
other terminal, whereas reverse looking zone of terminal B is not affected by this.
Z4 element is used for reverse fault detection in command protection, but not for backup
protection.
The non-directional zone ND is used for time delayed backup protection including overall zones.
Zone 3
Zone R1
A
C
B
Figure 2.4.1.4 Reverse Zone Protection
26
6 F 2 S 0 8 5 1
To maintain stable operation for close-up three-phase faults which cause the voltages of all phases
to drop to 0 or close to 0, zone 1 for phase faults, once operated, changes its element to a reverse
offset element. This continues until the fault is cleared, and thus it is effective for time delayed
protection.
The reactance element characteristics of zone 1, zone 1 extension, zone 2, zone F and zone R1 are
parallel lines to the R axis and provide sufficient coverage for high-resistance faults. The reactance
element characteristics of zone 1 and zone 1 extension can be transformed to a broken line
depending on the load flow direction in order to avoid overreaching by the influence of load
current. The characteristic in the resistive direction is limited by the mho characteristic of zone 3.
The reactive reach setting is independent for each zone. It is also possible to have independent
settings for each individual phase fault and earth fault elements.
With a long-distance line or heavily loaded line, it is possible for the load impedance to encroach
on the operation zone of the mho element. Blinders are provided to limit the operation of the mho
element in the load impedance area.
Zero-sequence current compensation is applied to zone 1, zone 2 and reverse zone R1 for earth
fault protection. This compensates measuring errors caused by the earth return of zero-sequence
current. This allows the faulted phase reactance element to precisely measure the
positive-sequence impedance up to the fault point. Furthermore, in the case of double-circuit lines,
zero-sequence current from the parallel line is introduced to compensate for influences from
zero-sequence mutual coupling. (R1 is not provided with zero sequence mutual coupling
compensation for the parallel line.) Considering the case where the impedance angle of
positive-sequence impedance and zero-sequence impedance differ which is the most common in
cable circuits, GRZ100 carries out vectorial zero-sequence current compensation.
The autoreclose schemes are utilised with instantaneous zone 1 tripping. When single-phase
autoreclose or single- and three-phase autoreclose are selected, zone 1 executes single-phase
tripping for a single-phase earth fault. In order to achieve reliable fault phase selection even for
faults on heavily loaded long-distance lines or irrespective of variations in power source
conditions behind the relaying point, an undervoltage element with current compensation is used
as a phase selector. Other zones only execute three-phase tripping, and do not initiate autoreclose.
2.4.1.2 Scheme Logic
Figure 2.4.1.5 shows the scheme logic for the time-stepped distance protection. For zone 1
tripping, as described later, it is possible to select instantaneous tripping or time delayed tripping
using the scheme switch [Z1CNT] in the trip mode control logic. (Detail of the [Z1CNT] is
described after.) Zone 2, zone 3, zone F, zone R1, zone R2 and zone ND give time delayed
tripping. However, these zones can trip instantaneously by PLC signals Z_INST_TP. Timers
TZ2, TZ3, TZF, TZR1, TZR2 and TZND with time delayed tripping can be set for earth faults and
phase faults separately. Zone F, zone R1, zone R2 and zone ND backup tripping can be disabled
by the scheme switch [ZBT].
Note: For the symbols used in the scheme logic, see Appendix L.
27
6 F 2 S 0 8 5 1
S-TRIP
&
1
Trip
mode
control
logic
M-TRIP
TZ2
t 0
TZ3
t 0
TZF
t 0
&
&
&
Z1
Z2
Z3
ZF
" ON "
" ON "
" ON "
CRT USE
Phase
selection
logic Sigle-phase
tripping
command
0.00 - 10.00s
0.00 - 10.00s
0.00 - 10.00s
[PSB-Z3]
[PSB-Z2]
[PSB-Z1]
TZND
t 0
&
PSB
ZND
0.00 - 10.00s
+
[ZFBT]
" ON "
[PSB-ZF]
TZR1
t 0
&
ZR1
0.00 - 10.00s
+
[ZR1BT]
" ON "
[PSB-ZR1]
TZR2
t 0
&
ZR2
NON VTF
0.00 - 10.00s
+
[ZR2BT]
" ON "
[PSB-ZR2]
+
[ZNDBT]
" ON "
Three-phase
tripping
command
M-PROT_ON 1550
TZ1
t 0
0.00 - 10.00s
Figure 2.4.1.5 Scheme Logic of Time-stepped Distance Protection
Tripping by each zone can be blocked the binary input signal (PLC signal) Z_BLOCK. The
tripping can be also blocked in the event of a failure of the secondary circuit of the voltage
transformer or power swing. The former is detected by the VT failure detection function. The
signal VTF becomes 1 when a failure is detected. The latter is detected by the power swing
blocking function. The signal PSB becomes 1 when power swing is detected. The zone in which
tripping will be blocked during a power swing can be set using the selection switches [PSB-Z1] to
[PSB-ZR2]. For zone ND backup tripping, power swing blocking is inhibited. For the VTF and
PSB, see Section 2.4.12 and Section 2.4.13, respectively.
By using the trip mode control logic, Zone 1 can implement different trip modes. The trip modes
as shown in Table 2.4.1.1 can be selected according to the position of the scheme switch [Z1CNT]
and whether or not the command protection is in or out of service.
Note: When permissive underreach protection is applied as the command protection, instantaneous
tripping is required for zone 1 and autoreclose must be started. Therefore, position 1 or 4 must be
selected for [Z1CNT].
The service condition of the command protection is judged by the service condition of the
telecommunication and the main protection. The telecommunication in-service signal CRT_USE
28
6 F 2 S 0 8 5 1
is established when the binary input signal (PLC signal) CRT_BLOCK is "0" and the scheme
switch [CRSCM] is set to "ON" as shown in Figure 2.4.1.6.
CRT USE
+
"ON"
[CRSCM]
&
1
CRT_BLOCK 1601
9
Figure 2.4.1.6 Communication Service Logic
The service condition of the external main protection in duplicated scheme is input with the binary
input signal (PLC signal) M-PROT_ON. The command protection in Table 2.4.1.1 is out of
service when both main protections are out of service.
Table 2.4.1.1 Zone 1 Trip Mode Control
Z1CNT COMMAND PROTECTION
Position IN SERVICE OUT OF SERVICE
1 INST. TRIP & AUTO-REC INST. FINAL TRIP
2 DELAYED FINAL TRIP INST. FINAL TRIP
3 TRIP BLOCKED INST. FINAL TRIP
4 INST. TRIP & AUTO-REC
5 INST. FINAL TRIP
The zone 1 tripping mode at each position of the switch [Z1CNT] is as follows:
Position 1: When the command protection is in service, zone 1 executes instantaneous tripping
and starts autoreclose. Zone 1 performs single-phase tripping and reclosing or three-phase tripping
and reclosing depending on the reclose mode of the autoreclose function and the type of faults
(single-phase faults or multi-phase faults). If the autoreclose is out of service, zone 1 performs
instantaneous three-phase final tripping for all faults.
If the command protection is out of service, zone 1 performs instantaneous three-phase final
tripping.
Position 2: Zone 1 performs three-phase tripping with a time delay using timer TZ1 if the
command protection is in service, and it performs three-phase tripping instantaneously if the
command protection is out of service and does not start the autoreclose.
Position 3: Zone 1 tripping is blocked if the command protection is in service, and instantaneous
three-phase tripping is performed if it is out of service. Autoreclose is not started.
Position 4: Zone 1 executes instantaneous tripping irrespective of the command protection
conditions and initiates autoreclose. This instantaneous tripping becomes single-phase tripping or
three-phase tripping depending on the autoreclose mode and type of faults (single-phase faults or
multi-phase faults). If the autoreclose is out of service, zone 1 performs instantaneous three-phase
final tripping.
Position 5: Zone 1 performs instantaneous three-phase final tripping irrespective of the command
protection.
Zone 1 Trip Mode Control is performed using PLC function as shown in Figure 2.4.1.7. By
changing the PLC default setting, the Z1 trip can be controlled independently of the [Z1CNT]
setting.
29
6 F 2 S 0 8 5 1
Trip
Mode
Control
Logic
CRT USE
Z1CNT_INST
+
[Z1CNT]
Z1_INST_TP 1696
712
713
714
715
Zone 1
Z1CNT_3PTP
Z1CNT_ARCBLK
Z1CNT_TPBLK
Z1_3PTP 1712
Z1_ARC_BLOCK 1655
Z1G_BLOCK 1616
Z1S_BLOCK 1632
Z1 can trip instantaneously.
Z1 performs three-phase trip.
Z1 performs final tripping for all faults.
Z1G trip is blocked..
Z1S trip is blocked.
Defalt setting
Figure 2.4.1.7 Zone 1 Trip Mode Control Circuit
When zone 1 extension is used, normal zone 1 tripping is blocked. However, the blocking is
released by an autoreclose command that follows zone 1 extension tripping. Final tripping to the
reclose-on-to-permanent-fault is performed under the time-stepped distance protection including
zone 1.
Zone 1 tripping is provided with an additional phase selection element UVC and phase selection
logic to make sure the faulted phase is selected for the single-phase earth fault.
Figure 2.4.1.8 gives details of the phase selection logic in Figure 2.4.1.5. In case of single-phase
earth fault, the earth fault measuring zone 1 element Z1G with a certain phase and the phase
selection element UVC with the same phase operate together, and a single-phase tripping
command S-TRIP can be output to the phase.
&
UVC - C
UVC - B
UVC - A
Z1G - C
Z1G - B
Z1G - A
1
Z1S-BC
Z1S-AB
C
B
A
&
&
&
Z1S-CA
S-TRIP
M-TRIP
19
20
21
EFL
UVPWI-C
UVPWI-B
UVPWI-A
362
363
364
568
66
67
68
34
35
36
1
&
&
&
Z3G - C
Z3G - B
Z3G - A
28
29
30
1
&
&
&
Figure 2.4.1.8 Phase Selection Logic for Zone 1 Protection
30
6 F 2 S 0 8 5 1
Depending on the setting of the scheme switch [Z1CNT] or [ARC-M] which selects reclosing
mode, single-phase tripping may be converted to a three-phase tripping command. This is not
shown in the figure.
In case of multi-phase fault, the phase fault measuring zone 1 element Z1S and the two phases of
the UVC operate together, the Z1G trip is blocked and the three-phase tripping command M-TRIP
is always output. The condition for the UVC two-phase operation is to inhibit the Z1S from
overreaching in the event of a single-phase earth fault.
The UVC element is applied to the zone 1 distance elements.
EFL is an earth fault detection element, and UVPWI is a phase undervoltage relay to provide
countermeasures for overreaching of a leading-phase distance element at positive phase weak
infeed condition. These elements are applied to all earth fault distance elements. (Refer to
Appendix A.) The UVPWI can be disabled by the scheme switch [UVPWIEN].
2.4.1.3Setting
The following shows the necessary distance protection elements and their setting ranges.
Element Range Step Default Remarks
VT 1 - 20000 1 2000
CT 1 - 20000 1 400
Phase fault protection
ZS-C Mho - Quad Mho Characteristic selection
Z1S 0.01 - 50.00 0.01 1.60 Z1 reach
(0.10 - 250.00 0.01 8.00) (*1)
Z1S 1 0 - 45 1 0 Gradient of reactance element
Z1S 2 45 - 90 1 90
Z2S 0.01 - 50.00 0.01 3.00 Z2 reach
(0.10 - 250.00 0.01 15.00)
ZFS 0.01 - 50.00 0.01 4.00 ZF reach
(0.1 250.0 0.1 20.0)
Z3S 0.01 - 50.00 0.01 6.00 Z3 reach
(0.1 250.0 0.1 30.0)
Z3S (*2) 45 - 90 1 85 Characteristic angle of mho element
ZBS (*3) 0 - 45 1 5 Angle of directional element
BFR1S 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z1S
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
BFRXS 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z1XS
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
BFR2S 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z2S
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
BFRFS 0.10 - 20.00 0.01 5.10 Forward right blinder reach for ZFS
(0.5 - 100.0 0.1 25.5) Required If [BLZONE]=IND
BFRS 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z3S or Common
(0.5 - 100.0 0.1 25.5) setting of BLZONE
BFLS 90 - 135 1 120 Forward left blinder angle
ZR1S 0.01 - 50.00 0.01 2.00 ZR1 reach
(0.1 250.0 0.1 10.0)
ZR2S 0.01 - 50.00 0.01 4.00 ZR2 reach
(0.1 250.0 0.1 20.0)
Z4S 0.01 - 50.00 0.01 8.00 Z4 reach
31
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
(0.1 250.0 0.1 40.0)
BRRS 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
ZNDS 0.01 - 50.00 0.01 10.00 ZND reach
(0.1 250.0 0.1 50.0)
BNDS 0.10 - 20.00 0.01 12.00 ZNDS blinder reach
(0.5 - 100.0 0.1 60.0)
TZ1S 0.00 - 10.00 s 0.01 s 0.00 s Zone 1 timer
TZ2S 0.00 - 10.00 s 0.01 s 0.30 s Zone 2 timer
TZFS 0.00 - 10.00 s 0.01 s 0.35 s Zone F timer
TZ3S 0.00 - 10.00 s 0.01 s 0.40 s Zone 3 timer
TZR1S 0.00 - 10.00 s 0.01 s 0.50 s Zone R1 timer
TZR2S 0.00 - 10.00 s 0.01 s 0.60 s Zone R2 timer
TZNDS 0.00 - 10.00 s 0.01 s 0.70 s Zone ND timer
Earth fault protection
ZG-C Mho - Quad Mho Characteristic selection
Z1G 0.01 - 50.00 0.01 1.60 Z1 reach
(0.10 - 250.00 0.01 8.00)
Z1G 1 0 - 45 1 0 Gradient of reactance element
Z1G 2 45 - 90 1 90
Z2G 0.01 - 50.00 0.01 4.00 Z2 reach
(0.10 - 250.00 0.01 20.00)
ZFG 0.01 - 100.00 0.01 6.00 ZF reach
(0.1 500.0 0.1 30.0)
Z3G 0.01 - 100.00 0.01 8.00 Z3 reach
(0.1 500.0 0.1 40.0)
Z3G (*2) 45 - 90 1 85 Characteristic angle of mho element
ZBG(*3) 0 - 45 1 30 Angle of directional element
BFR1G 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z1G
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
BFRXG 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z1XG
(0.5 - 100.0 0.1 25.5) Required If [BLZONE]=IND
BFR2G 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z2G
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
BFRFG 0.10 - 20.00 0.01 5.10 Forward right blinder reach for ZFG
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
BFRG 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z3G or Common
(0.5 - 100.0 0.1 25.5) setting of BLZONE
BFLG 90 - 135 1 120 Forward left blinder angle
ZR1G 0.01 - 100.00 0.01 2.00 ZR1 reach
(0.1 500.0 0.1 10.0)
ZR2G 0.01 - 100.00 0.01 4.00 ZR2 reach
(0.1 500.0 0.1 20.0)
Z4G 0.01 - 100.00 0.01 8.00 Z4 reach
(0.1 500.0 0.1 40.0)
BRRG 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
ZNDG 0.01 - 100.00 0.01 10.00 ZND reach
32
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
(0.1 500.0 0.1 50.0)
BNDG 0.10 - 20.00 0.01 12.00 ZNDG blinder reach
(0.5 - 100.0 0.1 60.0)
Krs 0 - 1000 % 1% 340% Residual current compensation = R0/R1
Kxs 0 - 1000 % 1% 340% Residual current compensation = X0/X1
Krm 0 - 1000 % 1% 300% Mutual coupling compensation = ROM/R1
Kxm 0 - 1000 % 1% 300% Mutual coupling compensation = XOM/X1
KrsR 0 - 1000 % 1% 100% Residual current compensation for ZR = R0/R1
KxsR 0 - 1000 % 1% 100% Residual current compensation for ZR = X0/X1
TZ1G 0.00 - 10.00 s 0.01 s 0.00 s Zone 1 timer
TZ2G 0.00 - 10.00 s 0.01 s 0.30 s Zone 2 timer
TZFG 0.00 - 10.00 s 0.01 s 0.35 s Zone F timer
TZ3G 0.00 - 10.00 s 0.01 s 0.40 s Zone 3 timer
TZR1G 0.00 - 10.00 s 0.01 s 0.50 s Zone R1 timer
TZR2G 0.00 - 10.00 s 0.01 s 0.60 s Zone R2 timer
TZNDG 0.00 - 10.00 s 0.01 s 0.70 s Zone ND timer
UVC Phase selection element
UVCV 10 - 60 V 1 V 48 V Voltage setting
UVCZ 0.0 - 50.0 0.1 2.0 Reach setting
(0 - 250 1 10)
UVC 45 - 90 1 85 Characteristic angle
EFL 0.5 5.0 A 0.1 A 1.0 A Earth fault detection
(0.10 1.00 A 0.01 A 0.20 A)
UVPWI 30 V fixed UV for positive weak infeed
Scheme switch
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/
BOP/POP+DEF/UOP+DEF/
BOP+DEF/PUP+DEF
POP Scheme selection
CRSCM OFF/ON ON Telecommunication service
BLZONE COM/IND COM Common or independent setting for blinder
Z1CNT 1/2/3/4/5 1 Zone 1 trip mode selection
PSB - Z1 OFF/ON ON Z1 power swing blocking
PSB - Z2 OFF/ON ON Z2 power swing blocking
PSB - Z3 OFF/ON OFF Z3 power swing blocking
PSB - ZF OFF/ON OFF ZF power swing blocking
PSB - ZR1 OFF/ON OFF ZR1 power swing blocking
PSB - ZR2 OFF/ON OFF ZR2 power swing blocking
ZFBT OFF/ON OFF ZF backup tripping
ZR1BT OFF/ON OFF ZR1 backup tripping
ZR2BT OFF/ON OFF ZR2 backup tripping
ZNDBT OFF/ON OFF ND zone backup tripping
UVPWIEN OFF/ON OFF Countermeasures for overreaching of a
leading-phase distance element at positive phase
weak infeed condition
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the case
of 5 A rating.
(*2) Valid only when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid only when quadrilateral characteristic is selected by ZS-C and ZG-C.
The following elements have fixed setting values or their settings are interlinked with other
33
6 F 2 S 0 8 5 1
elements listed above. So no setting operation is required.
Element Setting Remarks
Z1BS Fixed to 1.5 Z1 reverse offset reach
(Fixed to 7.5)(*1)
BFRS Fixed to 75 Angle of forward right blinder BFRS
Z4BS Fixed to 1.5
(Fixed to 7.5)
Z4 offset reach. This is also the offset reach for Z1RS and Z2RS.
However, in these cases the offset reach is limited by the Z1S
setting when Z1RS and Z2RS are used for backup tripping.
Z4S (*2) Interlinked with Z3S Characteristic angle of zone 4 mho element
Z4BS (*3) Interlinked with ZBS Angle of Z4 offset directional element
BRRS Fixed to 75 Angle of reverse right blinder BRRS
BRLS Interlinked with BRRS Reverse left blinder
BRLS Interlinked with BFLS Angle of reverse left blinder BRLS
BFRG Fixed to 75 Angle of forward right blinder BFRG
BNDS Fixed to 75 Angle of BNDS blinder
Z4G (*2) Interlinked with Z3G Characteristic angle of Z4 mho element
Z4BG (*3) Interlinked with ZBG Angle of offset directional element
BRRG Fixed to 75 Angle of reverse right blinder BRRG
BRLG Interlinked with BRRG Reverse left blinder
BRLG Interlinked with BFLG Angle of reverse left blinder BRLG
BNDG Fixed to 75 Angle of BNDG blinder
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the
case of 5 A rating.
(*2) Valid when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid when quadrilateral characteristic is selected by ZS-C and ZG-C.
In order to coordinate with the distance protection provided for adjacent lines, care is required in
setting the reach and timer setting. Figure 2.4.1.9 shows an ideal zone and time coordination
between terminals.
Figure 2.4.1.9 Typical Zone/Time Coordination among A-D Terminals
Zone 1 setting
Since instantaneous tripping is allowed in zone 1, it is desirable to select a setting that will cover
Time
Zone 1 Zone 1
Zone 3 Zone 3
Zone 3 Zone 3
Zone 2 Zone 2
Zone 2 Zone 2 Zone 2
Zone 2
Zone 1 Zone 1 Zone 1
Zone 1
D C B A
T1
T2
T3
T1
T2
T3
34
6 F 2 S 0 8 5 1
the widest possible range of the protected line. Conversely, zone 1 elements must not respond to
faults further than the remote end. Therefore, the setting of the zone 1 reach is set to 80 to 90% of
the impedance of the protected line taking account of VT and CT errors and measurement error.
The reach is set on the X-axis.
In order to change the reactance element characteristic into a broken line, Z1S(G)1 and
Z1S(G)2 in Figure 2.4.1.1 or Figure 2.4.1.2 must be set.
Time delayed tripping of zone 1 is selected when instantaneous tripping by another main
protection is given priority. The time delay TZ1 is set to ensure that coordination is maintained
with fault clearance by the main protection. Suppose that the maximum operating time of the main
protection is Tp, the opening time of the circuit breaker is Tcb, the minimum operating time of
zone 1 element is T1 and the reset time of the zone 1 element is Tzone 1, then TZ1 must satisfy
the following condition:
TZ1 > Tp + Tcb + Tzone 1 T1
Zone 2 setting
Zone 2 is required to cover 10 to 20% of the remote end zone not covered by zone 1. To assure this
protection, it is set to 120% or greater of the protected line impedance. To maintain the selectivity
with zone 1 of the adjacent lines, the zone 2 reach should not exceed the zone 1 reach of the
shortest adjacent line. The reach is set on the X-axis.
Time delay TZ2 is set so that it may be coordinated with fault clearance afforded by the main
protection of the adjacent lines. If time delayed tripping is selected for zone 1 of the protected line,
coordination with the time delay should also be taken into account. Suppose that the main
protection operating time on the adjacent lines is Tp', the opening time of the circuit breaker is
Tcb', the minimum operating time of zone 2 element is T2 and the reset time of local terminal zone
2 element is Tzone 2, then TZ2 must satisfy the following two conditions:
TZ2 > Tp' + Tcb' + Tzone 2 T2
TZ2 > TZ1
If the adjacent lines are too short for zone 2 to coordinate with zone 1 of the adjacent lines in reach
setting, it is necessary to set a much greater time delay for zone 2 as shown in Figure 2.4.1.10.
Generally, in setting the zone 2, consideration should be given to ensure selectivity with even the
slowest timer of the following protections:
Remote end busbar protection
Remote end transformer protection
Line protection of adjacent lines
Remote end breaker failure protection
Figure 2.4.1.10 Zone 2 Setting (When one of the adjacent lines is very short)
Time
T2'
T2
Zone 3
Zone 2
Zone 2
Zone 1 Zone 1
C B A
35
6 F 2 S 0 8 5 1
Zone 3 setting
Zone 3, in cooperation with zone 2, affords backup protection for faults that have occurred on
adjacent lines. The reach should be set to exceed the remote end of the longest adjacent line
whenever possible. It is also necessary to take into account the effect of fault infeed at the remote
busbars. If an ideal reach setting as shown in Figure 2.4.1.9 is possible, the timer setting for zone 3
needs only to consider the coordination with the timer setting in zone 2 of the protected lines and
adjacent lines.
However, as shown in Figure 2.4.1.11, if there are short-distance adjacent lines and it is
impossible to establish coordination only by the reach setting, there may also be a case where the
time delay for zone 3 will need to be set greater than that of the adjacent lines.
The zone 3 reach is set on the characteristic angle when the mho characteristic is selected or set on
the X axis when the quadrilateral characteristic is selected.
Figure 2.4.1.11 Zone 3 Setting (When one of the adjacent lines is very short)
Zone F setting
When zone F is used for the zone 3 instead of Z3, above zone 3 setting is applied. If the zone F is
used separately from zone 3, the settings of zone F reach and time delay are set to be less than the
zone 3 settings.
Zone R1 setting
The setting of the zone R1 reach is set so as to exceed the end of the adjacent line behind the
relaying point. The reach is set on the X-axis. The time delay is set to be greater than that of the
zone 3 backup protection. The scheme switch [ZR1BT] is set to ON, and the scheme switch
[ZR2BT] must be set to ON and the zone R2 reach must be set greater than the zone R1 reach
even though the zone R2 is not used.
Zone R2 setting
The setting of the zone R2 reach is set so as to include the busbar of the adjacent terminal behind
the relaying point. The time delay is set to be greater than that of the zone R1.
The zone R2 reach is set on the characteristic angle when the mho characteristic is selected or set
on the X axis when the quadrilateral characteristic is selected. The scheme switch [ZR2BT] is set
to ON.
Zone ND setting
The setting of the zone ND reach is set so as to include all zone settings and the time delay is set
the greatest of all zones. The scheme switch [ZNDBT] is set to ON.
Zone 2
T3'
T3
Zone 2
Zone 1
Zone 1
C B A
D
Zone 3
Zone 3
36
6 F 2 S 0 8 5 1
Blinder setting
BFR and BRR reaches are set to the minimum load impedance with a margin. The minimum load
impedance is calculated using the minimum operating voltage and the maximum load current.
The blinder element (BFR) can be provided for each forward zone. The setting of blinder element
can be set independently or set common to forward zones by [BLZONE]=IND or
[BLZONE]=COM setting. In the [BLZONE]=IND setting, the forward zone blinder setting
should be set BFR1BFRXBFR2BFR. If BFRBFR1, for example, the reach of BFR1
is limited to the BFR setting reach as shown in Figure 2.4.1.12(b). The BFRF can be set larger
than the BFR. If the BFRF is larger than the maximum resistive reach of Z3, the area exceeding
the Z3 is invalid. The BFRF is limited to Z3 operating zone as shown in Figure 2.4.1.12(C).
X
R
BFR
Z3
Z2
BFR1
Z1
BFR2
X
R
BFR1
Z3
Z2
BFR
BFR2
Z1
X
R
BFR
BFRF
Z3
ZF
(a) (b) (c)
Figure 2.4.1.12 BFR Reach
The BFL angle can be set to 90 to 135 and is set to 120 as a default. The BRL angle is linked with
the BFL angle.
Figure 2.4.1.12 shows an example of the blinder setting when the minimum load impedance is
Z
Lmin
and Z
Lmin
under the load transmitting and receiving conditions.
BFR X
30
75
R
BFL
Load Area
Z
Lmin
75
Z
Lmin
BRL BRR
Figure 2.4.1.13 Blinder Setting
When Z4 is used for overreaching command protection ie. POP, UOP and BOP, it is necessary
when setting BRR to take account of the setting of the remote end BFR to ensure coordination.
That is, the BRR is set to a value greater than the set value of the remote end BFR (e.g., 120% of
BFR). This ensures that a reverse fault that causes remote end zone 2 or zone 3 to operate is
detected in local zone R1 or R2 and false tripping is blocked.
37
6 F 2 S 0 8 5 1
Setting of earth fault compensation factor (zero sequence compensation)
In order to correctly measure the positive-sequence impedance to the fault point, the current input
to the earth fault measuring elements is compensated by the residual current (3I
0
) of the protected
line in the case of a single circuit line and by residual current (3I
0
) of the protected line and
residual current (3I
0
) of the parallel line in the case of a double circuit line.
Generally, the following equation is used to compensate the zero-sequence voltage drop in the
case of phase a.
V
a
= (I
a
I
0
)Z
1
+ I
0
Z
0
+ I
om
Z
om
(1)
where,
V
a
: Phase a voltage
I
a
: Phase a current
I
0
: Zero-sequence current of the protected line
I
0m
: Zero-sequence current of the parallel line
Z
1
: Positive-sequence impedance (Z
1
= R
1
+ jX
1
)
Z
0
: Zero-sequence impedance (Z
0
= R
0
+ jX
0
)
Z
0m
: Zero-sequence mutual impedance (Z
om
= R
om
+ jX
om
)
Equation (1) can be written as follows:
V
a
= (R
1
+ jX
1
)I
a
+ {(R
0
R
1
) + j(X
0
X
1
)}I
0
+ (R
om
+ jX
om
)I
om
= R
1
(I
a
+
R
0
R
1
R
1
I
0
+
R
om
R
1
I
om
)
+ jX
1
(I
a
+
X
0
X
1
X
1
I
0
+
X
om
X
1
I
om
)
In the GRZ100, the voltage is compensated independently for resistance and reactance
components as shown in equation (2) in stead of general equation (1).
V
aR
+ jV
aX
= {R
1
( I
aR
+
K
rs
100
1
3
3I
0R
+
K
rm
100
3
3I
omR
)
X
1
( I
aX
+
K
xs
100
1
3
3I
0X
+
K
xm
100
3
3I
omX
)}
+ j{R
1
( I
aX
+
K
rs
100
1
3
3I
0X
+
K
rm
100
3
3I
omX
)
+ X
1
( I
aR
+
K
xs
100
1
3
3I
0R
+
K
xm
100
3
3I
omR
)} (2)
where,
K
xs
: compensation factor (K
xs
= X
0
/X
1
100)
K
rs
: compensation factor (K
rs
= R
0
/R
1
100)
K
xm
: compensation factor (K
xm
= X
om
/X
1
100)
K
rm
: compensation factor (K
rm
= R
om
/R
1
100)
X: imaginary part of the measured impedance
R: real part of the measured impedance
38
6 F 2 S 0 8 5 1
V
aX
: imaginary part of phase a voltage
V
aR
: real part of phase a voltage
I
aX
: imaginary part of phase a current
I
aR
: real part of phase a current
I
0X
: imaginary part of zero-sequence current of the protected line
I
0R
: real part of zero-sequence current of the protected line
I
omX
: imaginary part of zero-sequence current of the parallel line
I
omR
: real part of zero-sequence current of the parallel line
Figure 2.4.1.14 Earth Fault Compensation
The zero-sequence compensation factors are applied to the earth fault measuring elements as
shown in the table below
Element Protected line Parallel line
Z1G Krs, Kxs Krm, Kxm
Z1XG Krs, Kxs Krm, Kxm
Z2G Krs, Kxs Krm, Kxm
Z3G
ZFG
ZR1G KrsR, KxsR
ZR2G
Z4G
ZNDG
: Compensation is not provided.
Note: The operation of Z1 or Z2 element is limited within the Z3 operating zone if the reach of Z1 or
Z2 compensated with zero-sequence current exceeds the reach of Z3. The operation of ZR1G is
also limited within the reach of ZR2G.
The zero-sequence compensation of the parallel line is controlled by the ZPCC (Zero-sequence
Current Compensation) element.
When an earth fault occurs on the protected line, the ZPCC operates and parallel line
compensation is performed to prevent underreach caused by the mutual zero-sequence current of
the parallel line.
When an earth fault on the parallel line occurs, the ZPCC does not operate and the compensation
of parallel line is not performed to prevent overreach. The operating condition of the ZPCC is as
follows:
3I
0
/ 3I
om
0.8
I
0
I
1
, I
2
, I
o
Z
1
, Z
2
, Z
o
Z
om
P
F
V
a
39
6 F 2 S 0 8 5 1
Charging current compensation
When distance protection is applied to underground cables or long-distance overhead lines, the
effect of charging current cannot be ignored. It appears as a distance measurement error in the
fault.
To suppress the effect of the charging current and maintain the highly accurate distance
measurement capability, the GRZ100 has a charging current compensation function.
The compensation is recommended if the minimum fault current can be less than three times the
charging current.
The setting value of ZIC should be the charging current at the rated voltage Vn.
Element Range Step Default Remarks
ZIC 0.00 - 5.00 A 0.01 A 0.0 0 Charging current setting
( 0.00 - 1.00 A 0.01 A 0.00 A) (*)
Vn 100 - 120 1 V 110 V Rated line voltage
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
Setting of phase selection element
Phase selection is required only for faults on the protected line. Therefore, impedance reach
setting UVCZ is set to 120% of the positive-sequence impedance of the protected line. Impedance
angle setting UVC is set the same as the protected line angle.
Undervoltage setting UVCV is set higher than the estimated maximum fault voltage at the fault
point for a single-phase earth fault.
2.4.1.4 Characteristics of Measuring Elements
Distance Measuring Elements Z1, Z1X, Z2, ZF, Z3, Z4, ZR1, ZR2, ZND and PSB
The GRZ100 provides eight distance measuring zones with mho-based characteristics or
quadrilateral characteristics.
As shown in Figure 2.4.1.15, mho-based zone characteristics are composed of mho element, offset
mho element, impedance element, reactance element, and blinder element for phase fault
protection and earth fault protection.
Z1 (zone 1), Z1X (zone 1 extension), Z2 (zone 2), ZF (zone F) and ZR1 (reverse zone 1) are a
combination of the reactance element, mho element and blinder element.
Z3 (zone 3), ZR2 (reverse zone 2), and Z4 use the mho element and blinder element, but Z4 for
phase faults uses the offset mho element instead of mho element. This makes it possible to detect a
reverse close-up fault at high speed if Z4 for phase faults is used for the command protection.
ZND (non-directional zone) uses the impedance element and blinder element.
The blinder element is normally used to restrict the resistive reach of the mho or offset mho
element if their operating range encroaches upon the load impedance.
The blinder element (BFR) can be provided for each forward zone. The setting of blinder element
can be set independently or set common to forward zones by the scheme switch [BLZONE].
40
6 F 2 S 0 8 5 1
X
Z1XS
Z2S
Z4S
Z3S
Z1S
Z1S1
Z1S2
ZR1S
ZR2S
ZNDS
BFLS
BFRS
BRLS
BS: Blinder elements
BRRS
BNDS
R
75
ZFS
Z3S
Z4S
BNDS
X
Z1XG
Z2G
Z4G
Z3G
Z1G
Z1G1
Z1G2
ZR1G
ZR2G
BFLG
BFRG
BRLG
BRRG
BG: Blinder elements
ZNDG
BNDG
BNDG
R
75
ZFG
Z3G
Z4G
(a) Phase fault element (b) Earth fault element
Figure 2.4.1.15 Mho-based Characteristics
As shown in Figure 2.4.1.16, quadrilateral zone characteristics are composed of reactance
element, directional element and blinder element. Z4 for phase faults uses the offset directional
element to ensure a reverse close-up fault detection.
R
X
Z1XG
Z2G
Z4G
Z3G
Z1G
Z1G1
Z1G2
ZBG
ZFG
ZR2G
ZR1G
ZNDG
BFRG
BFLG
BRLG
BRRG
ZNDG
BNDG
BNDG
BG: Blinder elements
75
R
X
Z1XS
Z2S
Z4S
Z3S
Z1S
Z1S1
Z1S2
ZBS
ZFS
ZR2S
ZR1S
ZNDS
BFRS
BFLS
BNDS
BNDS
BRLS
BRRS
ZNDS
BS: Blinder elements
75
(a) Phase fault element (b) Earth fault element
Figure 2.4.1.16 Quadrilateral Four Zone Characteristics
The forward offset reach of reverse zones (ZR1, ZR2) for both mho-based and quadrilateral
characteristics is fixed as 7.5 ohms for 1A rating or 1.5 ohms for 5A rating. However, when they
are used for back-up tripping ([ZRBT]= "ON"), the forward offset reach is limited to the zone 1
reach setting, as shown in Figure 2.4.1.17. Z4, on the other hand, is normally used to provide
blocking in the command schemes, and its offset is not limited by the zone 1 reach setting. It is
41
6 F 2 S 0 8 5 1
fixed at 7.5 (or 1.5) in order to give reliable, fast blocking for a close-up reverse fault.
Zone 1, zone 1X, zone 2 and zone F can trip on condition that zone 3 has operated, in both
characteristics.
(a) Mho-based characteristic
R
X
ZR1S/ZR2S
Z1S
(b) Quadrilateral characteristic
R
X
Z1S
ZR1S/ZR2S
Figure 2.4.1.17 ZR1S and ZR2S Characteristic Offset Reach for Backup Tripping
The power swing blocking elements (PSBS and PSBG) are a combination of the reactance element
and blinder element as shown in Figure 2.4.1.18. The outer element PSBOUT encloses the inner
element PSBIN with a settable width of PSBZ.
PSBZ
PSBZ
PSBZ
0
PSBZ
PSBIN PSBOUT
R
X
Z3
Z4
ZR2
Figure 2.4.1.18 Power Swing Blocking Element
Mho element
The characteristic of the mho element is obtained by comparing the phases between signals S1 and
S2. If the angle between these signals is 90 or more, it means that the fault is within the mho
characteristic, and the mho element will operate.
S1 = V IZs
S2 = Vp
where,
V = fault voltage
42
6 F 2 S 0 8 5 1
I = fault current
Zs = zone reach setting
Vp = polarizing voltage
Figure 2.4.1.19 is a voltage diagram, which shows that the mho characteristic is obtained by the
phase comparison if V and Vp are in-phase.
The mho characteristic on the impedance plane is obtained by dividing the voltage in Figure
2.4.1.19 by current I.
Figure 2.4.1.19 Mho Element
Both the phase fault mho element and earth fault mho element of the GRZ100 employ a dual
polarization (self-polarization plus cross-polarization). Its polarizing voltage Vp is expressed by
the following equations.
For B-to-C-phase phase fault element
V
pbc
= 3 (V
a
V
0
) 90 + V
bc
For an A-phase earth fault element
V
pa
= 3 (V
a
V
0
) + V
bc
90
where,
V
a
= A-phase voltage
V
0
= zero-sequence voltage
V
bc
= B-to-C-phase voltage
The dual-polarization improves the directional security when applied to heavily loaded lines or
weak infeed terminals.
The polarizing voltage for the phase fault mho element has a memory action for the close-up
three-phase fault. V
a
and V
bc
mentioned above are the memorized pre-fault voltages. This
memory is retained for two cycles after a fault occurs. The polarizing voltage for the earth fault
mho element has no memory action.
R
V
IZs
S2 =Vp
S1 =V IZs
X
43
6 F 2 S 0 8 5 1
Figure 2.4.1.20 Offset of Z1 in Three-phase Fault
When a three-phase fault occurs within zone 1, the phase fault mho element for zone 1 is modified
to an offset mho characteristic as shown in Figure 2.4.1.20. This, together with voltage memory
action, enables zone 1 to perform tripping with a time delay as well as instantaneous tripping for
the close-up three-phase fault.
The Z1X, Z2, ZF and Z3 do not have the modifying function mentioned above.
Offset mho element
Three independent offset mho elements are used for Z1 for phase faults, reverse zone ZR2 and Z4
for phase faults.
The characteristics of each offset mho element are obtained by comparing the phases between
signals S1 and S2.
If the angle between these signals is 90 or more, the offset mho element operates.
S1 = V IZs
S2 = V + IZso
where,
V = fault voltage
I = fault current
Zs = zone reach setting
Zso = offset zone reach setting
Figure 2.4.1.21 is a voltage diagram showing the offset mho characteristics obtained by the phase
comparison between S1 and S2.
The offset mho characteristic on the impedance plane is obtained by dividing the voltage in Figure
2.4.1.21 by current I.
R
X
44
6 F 2 S 0 8 5 1
R
V
IZso
IZs
S2 =V + IZso
S1 =V IZs
X
Figure 2.4.1.21 Offset Mho Element
Reactance element
The reactance elements of Z1 and Z1X have a composite characteristic with the two straight lines,
one is parallel and the other is gradual descent toward the R-axis as shown in Figure 2.4.1.22.
The characteristic is defined by the reach setting Xs and the angle settings 1 and 2. This
composite characteristic is obtained only when the load current is transmitted from local to remote
terminal. When the load current flows from remote to local terminal or the load current does not
flow or 1 is set to 0, the reactance element characteristic is a horizontal line which is parallel to
the R-axis.
The characteristic is expressed by the following equations.
For horizontal characteristic
X Xs
For gradient characteristic
R Xs tan ( 90 2 ) + ( Xs X ) tan ( 90 1 )
where,
R = resistance component of measured impedance
X = reactance component of measured impedance
Xs = reach setting
The reactance element characteristic of Z2, ZF and ZR1 is given by a parallel line to the R axis.
R and X are calculated using an integration approximation algorithm. The reactance element
provides high measurement accuracy even in the presence of power system frequency fluctuations
and distorted transient waveforms containing low-frequency spectral components.
A decision to operate is made 6 times in each power frequency cycle using the above-mentioned
equation. The reactance element operates when two consecutive measurements are made if the
distance to a fault is within 90% of the reach setting. If the distance to a fault is more than 90%, the
reactance element operates when four consecutive measurements are made.
This decision method prevents transient overreaching occurring for faults close to the element
boundary.
45
6 F 2 S 0 8 5 1
Figure 2.4.1.22 Reactance Element
The setting of 1(Z11) and 2(Z12) are set to the following:
Z12 < tan
-1
( X / R
F
)
Where,
X = reactance component
R
F
= fault resistance
Z11 < tan
-1
{I
Lmax
/ (I
Lmax
+ I
Fmin
)}
I
Lmax
= maximum load current
I
Fmin
= minimum fault current
Blinder element
The blinder element is commonly applicable to Z1, Z1X, Z2, ZF, Z3, ZR1, ZR2 and Z4. As shown
in Figure 2.4.1.23, the blinder element provides the forward blinder and the reverse blinder. The
operating area of the forward blinder is the zone enclosed by the lines BFR and BFL, and that of
the reverse blinder is the zone enclosed by the lines BRR and BRL. The BFR has an angle of 75
to the R-axis and BFL 90 to 135. The angle of BRL is linked with that of BFL.
(a) Forward blinder
(b) Reverse blinder
BRL
R
X
-Rs
75
BRR
X
R
75
BFR BFL
R
Rs
X
Rs
Figure 2.4.1.23 Blinder element
The characteristic of the BFR is obtained by the following equation.
X (R Rs) tan 75
where,
R = resistance component of measured impedance
(b) Z2 and ZF
X
R
90
(a) Z1 and Z1X
2
R
1
X
46
6 F 2 S 0 8 5 1
X = reactance component of measured impedance
Rs = reach setting
The characteristic BFL is obtained by the following equation. Polarizing voltage employed is the
same as employed for mho element.
Vp I cos ( + 90 ) > 0
where,
Vp = polarizing voltage
I = fault current
= lagging angle of I to Vp
= angle setting
A blinder applicable to the offset mho element for the power swing blocking also has the same
characteristics as BFR.
The characteristics of BRR and BRL are expressed by the following equations.
For BRR
X (R + Rs) tan 75
For BRL
X (R Rs) tan (180 )
where,
R = resistance component of measured impedance
X = reactance component of measured impedance
Rs = reach setting
The reach settings of BFR and BRR are made on the R-axis. The BRL setting is interlinked with
the BRR setting.
If the minimum load impedance is known, then assuming a worst case load angle of 30 and a
margin of 80%, then the following equation can be used to calculate the blinder element resistive
settings:
R
set
< 0.8 Z
Lmin
(cos30
sin30
tan75
)
Directional element
The directional element is used for the quadrilateral four zone characteristics.
Vp
I
lag
Figure 2.4.1.24 Directional Element
The characteristic of the directional element is obtained by the following equation.
47
6 F 2 S 0 8 5 1
IVp cos ( ) 0
where,
I = fault current
Vp = polarizing voltage
= lagging angle of I to Vp
= directional angle setting
The polarizing voltage Vp is the same one as employed in the mho element.
For B-to-C-phase phase fault element
V
pbc
= 3 (V
a
V
0
) 90 + V
bc
For an A-phase earth fault element
V
pa
= 3 (V
a
V
0
) + V
bc
90
where,
V
a
= A-phase voltage
V
0
= zero-sequence voltage
V
bc
= B-to-C-phase voltage
The polarizing voltage for the phase fault element has a memory action for the close-up
three-phase fault. V
a
and V
bc
mentioned above are the memorized pre-fault voltages. This
memory is retained for two cycles after a fault occurs. The polarizing voltage for the earth fault
element has no memory action.
When a three-phase fault occurs within zone 1, the phase fault element for zone 1 is modified to an
offset characteristic as shown in Figure 2.4.1.25. This, together with voltage memory action,
enables zone 1 to perform tripping with a time delay as well as instantaneous tripping for the
close-up three-phase fault.
The Z1X, Z2, ZF and Z3 do not have the modifying function mentioned above.
X
R
Reactance
Blinder
Directional
Figure 2.4.1.25 Quadrilateral characteristic
48
6 F 2 S 0 8 5 1
Offset directional element
The offset directional element is used only in Z4 for phase faults in the quadrilateral four zone
characteristics.
Figure 2.4.1.26 Offset Directional Element
The characteristic of the offset directional element is obtained by the following equation.
X + R tan Z
B
where,
X = reactance component of measured impedance
R = resistance component of measured impedance
= directional angle setting (interlinked with directional element angle setting)
Z
B
= offset reach setting (fixed to 1.5 in 5A rating and 7.5 in 1A rating)
Phase Selection Element UVC
The phase selection element has the undervoltage characteristic shown in Figure 2.4.1.27 and is
used to select a faulty phase in case of a single-phase-to-earth fault.
I
V
Vs
IZs
Figure 2.4.1.27 Phase Selection Element
The characteristic is obtained by a combination of the equations below. If equation (1) or equation
(2), or both equations (3) and (4) are established, the UVC operates.
|V| Vs (1)
R
X
Z
B
49
6 F 2 S 0 8 5 1
|V IZs| Vs (2)
Vs V sin Vs (3)
0 V cos |IZs| (4)
where,
V = fault voltage
I = fault current
= angle difference between V and IZs
Zs = impedance setting
Vs = undervoltage setting
When the value and angle of Zs are set to those similar to the impedance of the protected line, the
phase selection element will detect all single-phase earth faults that have occurred on the protected
line even with a strong source and the voltage drop is small.
As a result of current compensation, the operating zone expands only in the direction leading the
current by the line impedance angle. Therefore, the effect of current compensation is very small
under load conditions where the current and voltage have almost the same phase angle.
2.4.2 Zone 1 Extension Protection
Application
The disadvantage of time-stepped distance protection is that faults near the remote end of the
protected line can only be cleared in zone 2 time, thus high speed protection cannot be performed
for all faults on the protected line. If telecommunication is available, this disadvantage can be
solved by command protection. If telecommunication is not available, zone 1 extension protection
using autoreclose will implement high speed protection at both terminals.
Zone 1 extension (zone 1X) has a complex characteristic combining the reactance element, mho
element and blinder element, and its characteristic is the same as zone 1.
Zone 1X for earth faults is provided with the same residual current compensation as zone 1 and
zone 2.
As shown in Figure 2.4.2.1, zone 1X is set to overreach the protected line and performs
instantaneous tripping. This tripping is followed by autoreclose. In the selected autoreclose mode,
one of three-phase tripping and autoreclose, single-phase tripping and autoreclose, or single- and
three-phase tripping and autoreclose is executed.
The zone 1 extension protection clears a fault on the protected line including an end zone fault at
high speed, displaying the performance equivalent to that of command protection.
On the other hand, unlike command protection, overreaching zone 1X also acts instantaneously
for a fault on adjacent lines and executes tripping. If the fault is a transient fault, power
transmission can be recovered by autoreclose with a transient loss of power supply.
High speed zone 1X tripping is not desirable following reclosure onto a permanent fault on an
adjacent line because more of the network is lost than necessary. Therefore, tripping by zone 1X is
blocked prior to the reclosing command to the circuit breaker. Whether or not the permanent fault
is on the protected line or on an adjacent line, tripping is performed under time-stepped distance
protection.
When autoreclose is out of service, the zone 1 extension protection is blocked.
50
6 F 2 S 0 8 5 1
C B
Zone 3
Zone 2
Zone 1
Zone 1X
T3
T2
T 1
A
T 4 Zone R
Time
Figure 2.4.2.1 Time/Distance Characteristics of Zone 1 Extension Protection
and Time-Stepped Distance Protection
Scheme Logic
The scheme logic of the zone 1 extension protection is shown in Figure 2.4.2.2. Zone 1X outputs
single-phase tripping signal S-TRIP or three-phase tripping signal M-TRIP through phase
selection logic on condition that the reclosing mode selection switch [ARC-M] of autoreclose be
set to "TPAR" or "SPAR & TPAR" and condition REC-READY1 = 1 be established. The phase
selection logic is the same as that for the zone 1 protection shown in Figure 2.4.1.7, except that
Z1XG and Z1XS are employed instead of Z1G and Z1S. When a power swing is detected (PSB =
1) and when a VT failure is detected (VTF = 1), tripping is blocked. Power swing blocking can be
disabled by the scheme switch [PSB-Z1X].
The zone 1 extension protection is disabled by the binary input signal (PLC signal)
Z1XG_BLOCK and Z1XS_BLOCK.
S-TRIP
M-TRIP
Phase
Selection
"SPAR",
"SPAR +TPAR"
[ARC-M]
+
PSB
[PSB-Z1X]
"ON"
VTF
REC-READY1
Z1X
&
&
1
Z1X_INIT 1540
Z1XG_BLOCK
1617
Z1XS_BLOCK 1633
22:Z1XG-A 23:Z1XG-B 24:Z1XG-C
37:Z1XS-AB 38:Z1XS-BC 39:Z1XS-CA
1
&
1
"Z1-EXT"
Protection scheme
+
Z1X_F.ENABLE 1659
1
Figure 2.4.2.2 Zone 1 Extension Scheme Logic
REC-READY1 is a signal in the autoreclose function, and as shown in Figure 2.4.2.3,
REC-READY1 = 1 is established when the reclaim time has elapsed, that is, when autoreclose is
ready, and reset when a reclosing command is output.
Zone 1 extension can provide protection in the case of evolving faults provided that they occur
before the reclosing command is output. Otherwise, in the case of a permanent fault, it will not
respond to a reclose-on-to-fault.
51
6 F 2 S 0 8 5 1
Fault inception
Closed
Circuit
breaker
Open
Auto
- reclose
Trip
REC-
READY1
Reclaim time Reclaim time
Figure 2.4.2.3 Sequence Diagram of Zone 1 Extension
Zone 1 extension executes single-phase tripping and autoreclose for single-phase to earth faults
when the reclosing mode selection switch [ARC-M] is set to "SPAR & TPAR". A phase selection
element UVC and phase selection logic are used for reliable selection of the faulted phases. Phase
selection logic for zone 1X can be seen in Figure 2.4.1.7 by replacing zone 1 measuring elements
with zone 1X measuring elements.
Setting
The following table shows the setting elements necessary for zone 1 extension protection and their
setting ranges.
Element Range Step Default Remarks
Z1XS 0.01 50.00 0.01 2.40 Zone 1 extension reach
(0.10 250.00 0.01 12.00) (*)
Z1S 1 0 - 45 1 0 Gradient of reactance element
Z1S 2 45 - 90 1 90
BFRXS 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z1XS
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
Z1XG 0.01 50.00 0.01 2.40 Zone 1 extension reach
(0.10 250.00 0.01 12.00)
Z1G 1 0 - 45 1 0 Gradient of reactance element
Z1G 2 45 - 90 1 90
BFRXG 0.10 - 20.00 0.01 5.10 Forward right blinder reach for Z1XG
(0.5 - 100.0 0.1 25.5) Required if [BLZONE]=IND
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/BOP/PO
P+DEF/UOP+DEF/BOP+DEF/ PUP+DEF
POP Scheme selection
Autoreclose mode
(ARC M)
Disabled/SPAR/TPAR/
SPAR & TPAR/EXT1P/EXT3P
SPAR & TPAR Autoreclose mode selection
"SPAR" or "SPAR & TPAR" should be selected
BLZONE COM/IND COM Common or independent setting for blinder
PSB - Z1X OFF/ON ON Power swing blocking
(*) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the
case of 5 A rating.
The reach for zone 1 extension is set, for example, to 120% so as to completely cover the protected
line. It is not necessary to set the earth fault compensation factors because the same compensation
factors as those of zone 1 and zone 2 are used. The reach is set on the X-axis.
When the reactance element characteristic of zone 1 takes a broken line, that of zone 1 extension
follows it automatically.
When using zone 1 extension protection, either "SPAR & TPAR" or "TPAR" must be selected as
the reclosing mode of the autoreclose.
52
6 F 2 S 0 8 5 1
2.4.3 Command Protection
If operational information from the distance relays located at each end of the protected line is
exchanged by means of telecommunication, it is possible to accurately determine whether or not
the fault is internal or external to the protected line. Each terminal can provide high-speed
protection for any fault along the whole length of the protected line. The GRZ100 provides the
following command protection using the distance measuring elements.
Permissive underreach protection (PUP)
Permissive overreach protection (POP)
Unblocking overreach protection (UOP)
Blocking overreach protection (BOP)
Each command protection can initiate high-speed autoreclose. These protections perform
single-phase or three-phase tripping depending on the setting of the reclosing mode and the fault
type.
Each command protection includes the aforementioned time-stepped distance protection as
backup protection.
2.4.3.1 Permissive Underreach Protection
Application
In permissive underreach protection (PUP), the underreaching zone 1 protection operates and trips
the local circuit breakers and at the same time sends a trip permission signal to the remote terminal.
The terminal which receives this signal executes instantaneous tripping on condition that the local
overreaching element has operated. The overreaching element can be selected as either zone 2 or
zone 3.
Since the trip permission signal is sent only when it is sure that the fault exists in the operating
zone of zone 1, the PUP provides excellent security. On the other hand, the PUP does not provide
sufficient dependability for faults on lines that contain open terminals or weak infeed terminals for
which zone 1 cannot operate. Faults near open terminals or weak infeed terminals are removed by
delayed tripping of zone 2 elements at remote terminals.
Since only the operating signal of the underreaching element is transmitted, it is not necessary to
distinguish a transmit signal from a receive signal. That is, the telecommunication channel can be
shared by the terminals and a simplex channel can be used.
Scheme Logic
Figure 2.4.3.1 shows the scheme logic of the PUP. Once zone 1 starts to operate, it outputs a
single-phase tripping signal S-TRIP or three-phase tripping signal M-TRIP to the local terminal
instantaneously and at the same time sends a trip permission signal CS to the remote terminals.
When the trip permission signal R1-CR is received from the remote terminals, PUP executes
instantaneous tripping on condition that either zone 2 or zone 3 has operated. Whether or not zone
2 or zone 3 is used can be selected by the scheme switch [ZONESEL].
53
6 F 2 S 0 8 5 1
[ZONESEL]
NON_VTF
S-TRIP
&
&
1
M-TRIP
Phase
Selection
R1-CR
CS
Z1
Z3
Z2
PSB
" ON"
[PSB-CR]
"Z2"
"Z3"
R1-CR: Trip permission signal from the remote terminal.
Signal No. Signal name Description
1568: EXT_CAR.R1-1 Trip carrier signal from remote terminal
1569: EXT_CAR.R1-2 Guard/And carrier signal from remote terminal
TSBCT
0.00 1.00s
0 t
CS (Carrier send) signal
Signal No. Signal name
225: EXT_CAR-S
(PSBS_DET/PSBG_DET
from Figure 2.4.12.2.)
(from Figure 2.4.11.1.)
Figure 2.4.3.1 PUP Scheme Logic
To select the faulted phases reliably, phase selection is performed using the phase selection
element UVC. Phase selection logic in zone 1 tripping is shown in Figure 2.4.1.7 and its operation
is described in Section 2.4.1. Phase selection logic in command tripping is shown in Figure
2.4.3.9. Refer to Section 2.4.3.7.
Off-delay timer TSBCT is provided for the following purpose:
In many cases, most of the overreaching elements at both ends operate almost simultaneously.
However, there may be some cases where they cannot operate simultaneously due to unbalanced
distribution of fault currents. Non-operation of the overreaching elements can occur at a terminal
far from the fault, but they can operate if the other terminal trips. Transmission of the trip
permission signal continues for the setting time of TSBCT after reset of zone 1, and thus even the
terminal for which the overreaching element has delayed-picked up can also trip.
Setting
The following shows the setting elements necessary for the PUP and their setting ranges.
For the settings of Z1, Z2, Z3 and UVC, refer to Section 2.4.1.
Element Range Step Default Remarks
TSBCT 0.00 1.00s 0.01s 0.10s
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP
/BOP/POP+DEF/UOP+DEF/
BOP+DEF/PUP+DEF
POP Scheme selection
ZONESEL Z2/Z3 Z2 Overreaching element selection
PSB - CR OFF/ON ON Power swing blocking
2.4.3.2 Permissive Overreach Protection
Application
In permissive overreach protection (POP), the terminal on which the forward overreaching
element operates transmits a trip permission signal to the other terminal. The circuit breaker at the
local terminal is tripped on condition that the overreaching element of the local terminal has
operated and that a trip permission signal has been received from the remote terminal. That is, POP
54
6 F 2 S 0 8 5 1
determines that the fault exists inside the protected line based on the overlapping operation of the
forward overreaching elements at both terminals. It is possible to use zone 2 or zone 3, as the
forward overreaching element.
The POP is provided with an echo function and weak infeed trip function so that even when the
protection is applied to a line with open terminal or weak infeed terminal, it enables fast tripping of
both terminals for any fault along the whole length of the protected line. An undervoltage element
UVL is provided for weak infeed tripping. (See Section 2.4.3.5 for protection for weak infeed
terminal.)
When a sequential fault clearance occurs for a fault on a parallel line, the direction of the current
on the healthy line is reversed. The status of the forward overreaching element changes from an
operating to a reset state at the terminal where the current is reversed from an inward to an outward
direction, and from a non-operating status to operating status at the other terminal. In this process,
if the operating periods of the forward overreaching element of both terminals overlap, the healthy
line may be tripped erroneously. To prevent this, current reversal logic (CRL) is provided. (See
Section 2.4.3.6 for current reversal.)
Since the POP transmits a trip permission signal with the operation of the overreaching element, it
requires multiplex signaling channels or one channel for each direction. This ensures that the
transmitting terminal does not trip erroneously due to reception of its own transmit signal during
an external fault in the overreaching zone.
Scheme Logic
Figure 2.4.3.2 shows the scheme logic for the POP. The POP transmits a trip permission signal to
the other terminal for any of the following conditions.
The forward overreaching zone 2 or zone 3 selected by scheme switch [ZONESEL]
operates and the current reversal logic (CRL) has not picked up.
The circuit breaker is opened and a trip permission signal CR is received from the other
terminal.
The forward overreaching zone 2 or zone 3 and reverse looking Z4 have not operated
and a trip permission signal is received from the other terminal.
The last two are implemented when an echo function (ECH) is selected. (Refer to Section 2.4.3.5
for echo function.)
Transmission of the trip permission signal continues for the TSBCT setting even after the local
terminal is tripped by the delayed drop-off timer TSBCT. This is to ensure that command tripping
is executed at the remote terminal.
The POP outputs single-phase tripping signal S-TRIP or three-phase tripping signal M-TRIP to
the local terminal when the trip permission signal R1-CR is received from the remote terminal, the
current reversal logic (CRL) is not picked up and one of the following conditions is established.
The forward overreaching element operates.
The undervoltage element UVL (UVLS or UVLG) operates and the forward
overreaching and the reverse looking elements do not operate.
The latter is implemented when the weak infeed trip function is selected. (Refer to Section 2.4.3.5
for weak infeed trip function.)
To select the faulted phase reliably, phase selection is performed using the phase selection element
UVC. Phase selection logic is described in Section 2.4.3.7.
55
6 F 2 S 0 8 5 1
1
&
1
1
&
&
&
CB-OR
Z4
Z2
Z3
UVL
" ON "
NON VTF
PSB
ECH
WIT
0.01-10.00s
S-TRIP
M-TRIP
20ms
CS
Phase
Selection
t 0 0 t
&
CRL
[ZONESEL]
"Z3"
"Z2"
[PSB-CR]
1
R1-CR
TREBK
1
&
TECCB
0.00 - 200.00s
t 0
TSBCT
0.00 1.00s
0 t
() Note: Details of UVL
Signal No. Signal name Description
72: UVLS-AB A-B phase
73: UVLS-BC B-C phase
74: UVLS-CA C-A phase
78: UVLG-A A phase
79: UVLG-B B phase
80: UVLG-C C phase
()
&
Figure 2.4.3.2 POP Scheme Logic
Setting
The following shows the setting elements necessary for the POP and their setting ranges. For the
settings of Z2, Z3 and UVC, refer to Section 2.4.1.
Element Range Step Default Remarks
UVL Weak infeed trip element
UVLS 50 - 100 V 1V 77V Undervoltage detection (phase fault)
UVLG 10 - 60 V 1V 45V Undervoltage detection (earth fault)
Z4S 0.01 - 50.00 0.01 8.00 Z4 reach
(0.1 250.0 0.1 40.0) (*)
BRRS 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
Z4G 0.01 100.00 0.01 8.00 Z4 reach
(0.1 500.0 0.1 40.0)
BRRG 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
TREBK 0.00 - 10.00s 0.01s 0.10s Current reversal block time
TSBCT 0.00 1.00s 0.01s 0.10s
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/
BOP/POP+DEF/UOP+DEF/
BOP+DEF/PUP+DEF
POP Scheme selection
ZONESEL Z2/Z3 Z2 Overreaching element selection
PSB - CR OFF/ON ON Power swing blocking
56
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
ECHO OFF/ON ON Echo function
WKIT OFF/ON ON Weak infeed trip function
(*) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the
case of 5 A rating.
The following elements have fixed setting values or their settings are interlinked with other
elements listed above. So no setting operation is required.
Element Setting Remarks
Z4BS Fixed to 1.5 Z4 reverse offset reach
(Fixed to 7.5) (*1)
Z4S (*2) Interlinked with Z3S Characteristic angle of Z4 mho element
Z4BS (*3) Interlinked with ZBS Angle of Z4 directional element
BRRS Fixed to 75 Angle of reverse right blinder BRRS
BRLS Interlinked with BRRS Reverse left blinder
BRLS Interlinked with BFLS Angle of reverse left blinder BRLS
Z4G (*2) Interlinked with Z3G Characteristic angle of Z4 mho element
Z4BG (*3) Interlinked with ZBG Angle of Z4 directional element
BRRG Fixed to 75 Angle of reverse right blinder BRRG
BRLG Interlinked with BRRG Reverse left blinder
BRLG Interlinked with BFLG Angle of reverse left blinder BRLG
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in
the case of 5 A rating.
(*2) Valid only when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid only when quadrilateral characteristic is selected by ZS-C and ZG-C.
The reverse looking Z4 (G,S), BRR (G,S) and BRL (G,S) must always operate for reverse faults
for which the forward overreaching element of the remote end operates. The following setting
coordination is required.
When zone 2 is selected as the forward looking element:
Z4 setting = 1.2 (Zone 2 setting at remote end)
When zone 3 is selected:
Z4 setting = 1.2 (Zone 3 setting at remote end)
In both cases:
BRR setting = 1.2 (BFR setting at remote end)
2.4.3.3 Unblocking Overreach Protection
Application
If a power line carrier is used as the telecommunication media, there is a possibility that the
dependability of the PUP and POP could be reduced. This is because the trip permission signal
must be transmitted through the fault point and the attenuation of the signal may cause the PUP
and POP to fail to operate. To solve this problem, unblocking overreach protection (UOP) is
applied.
The signal transmitted under the UOP is a trip block signal and this is transmitted continuously
during non-fault conditions. When the forward overreaching element operates, transmission is
stopped. At the remote end, the non-receipt of a trip block signal is recognized as an actual trip
permission signal and tripping is executed on condition that the local forward overreaching
element operates.
57
6 F 2 S 0 8 5 1
In this system, the transmitted signal is a trip block signal, and transmission of that signal is
required only in the case of external faults. Therefore, even if power line carrier is used, a failure to
operate or false operation due to attenuation of the signal would not be experienced.
If the modulation method of the telecommunication circuits is a frequency shift method,
frequencies f1 and f2 are assigned to the trip block signal and trip permission signal, respectively.
The receive end recognizes signals CR1 and CR2 as corresponding to respective frequencies as
the actual trip permission signals when either one of the following conditions is established and
executes tripping on condition that the overreaching element should operate.
CR1 is lost and only CR2 is received.
Both CR1 and CR2 are lost.
The latter is also applicable if there is a telecommunication circuit failure in addition to attenuation
of the signal at the fault point. Therefore, when the latter condition continues for a certain period
or longer, the UOP is blocked and a telecommunication circuit failure alarm is output.
The UOP is provided with an echo function and weak infeed trip function and even when applied
to a line with open terminals or weak infeed terminals, it allows fast tripping of both terminals for
any fault along the whole length of the protected line. An undervoltage element UVL is provided
for weak infeed tripping. (See Section 2.4.3.5 for protection for weak infeed terminal.)
When a sequential fault clearance occurs for a fault on a parallel line, the direction of the current
on the healthy line is reversed. The status of the forward overreaching element changes from an
operating to a reset state at the terminal where the current is reversed from an inward to an outward
direction, and from a non-operating status to an operating status at the other terminal. In this
process, if the operating periods of the forward overreaching element of both terminals overlap,
the healthy line may be tripped erroneously. To prevent this, current reversal logic is provided.
(See Section 2.4.3.6 for current reversal.)
For the communication channel, a single channel shared by different terminals or multiplex
channels, one channel for each direction can be used.
Scheme Logic
Figure 2.4.3.3 shows the scheme logic of the UOP. The logic level of transmit signal CS and
receive signal R1-CR is "1" for a trip block signal and "0" for a trip permission signal.
The UOP changes its transmit signal CS from a trip block signal to trip permission signal under
one of the following conditions. The logic level of CS changes from 1 to 0.
The forward overreaching zone 2 or zone 3 selected by the scheme switch [ZONESEL]
operates and the current reversal logic (CRL) is not picked up.
The circuit breaker is open and the trip permission signal (R1-CR=0) is received from
the other terminal.
The forward overreaching zone 2 or zone 3 and reverse looking Z4 are not operating and
a trip permission signal is received from the other terminal.
The last two are implemented when an echo function (ECH) is selected. (Refer to Section 2.4.3.5
for echo function.)
Transmission of a trip permission signal continues for the TSBCT setting even after the local
terminal is tripped. This is to ensure that command tripping is executed at the remote terminal.
The UOP outputs single-phase tripping signal S-TRIP or three-phase tripping signal M-TRIP to
the local terminal when the trip permission signal (R1-CR=0) is received from the remote
terminal, the current reversal logic (CRL) is not picked up and one of the following conditions is
established.
58
6 F 2 S 0 8 5 1
The forward overreaching element operates.
The undervoltage element UVL (UVLS or UVLG) operates and the forward
overreaching and the reverse looking elements do not operate.
The latter is implemented when the weak infeed trip function is selected.
To select the faulted phase reliably, phase selection is performed using the phase selection element
UVC. Phase selection logic is described in Section 2.4.3.7.
1
&
&
CB-OR
Z4
Zone 2
Zone 3
UVL
" ON "
NON VTF
PSB
ECH
CRL
WIT
0.01-10.00s
S-TRIP
M-TRIP
20ms
CS
Phase
selection
t 0 0 t
&
&
1
1
1
&
1
&
[PSB-CR]
"Z3"
"Z2"
[ZONESEL]
1
R1-CR 1
TREBK
TECCB
0.00 - 200.00s
t 0
TSBCT
0.00 1.00s
0 t
&
Figure 2.4.3.3 UOP Scheme Logic
Setting
The following shows the setting elements necessary for the UOP and their setting ranges.
For the settings of Z2, Z3, and UVC, refer to Section 2.4.1.
Element Range Step Default Remarks
UVL Weak infeed trip element
UVLS 50 - 100 V 1V 77V Undervoltage detection (phase fault)
UVLG 10 - 60 V 1V 45V Undervoltage detection (earth fault)
Z4S 0.01 - 50.00 0.01 8.00 Z4 reach
(0.1 250.0 0.1 40.0) (*)
BRRS 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
Z4G 0.01 - 100.00 0.01 8.00 Z4 reach
(0.1 500.0 0.1 40.0)
BRRG 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
TREBK 0.00 - 10.00s 0.01s 0.10s Current reversal block time
59
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
TSBCT 0.00 1.00s 0.01s 0.10s
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/ BOP/
POP+DEF/UOP+DEF/BOP+DEF/PUP+DEF
POP Scheme selection
ZONESEL Z2/Z3 Z2 Overreaching element selection
PSB - CR OFF/ON ON Power swing blocking
ECHO OFF/ON ON Echo function
WKIT OFF/ON ON Weak infeed trip function
(*) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in
the case of 5 A rating.
The following elements have fixed setting values or their settings are interlinked with other
elements listed above. So no setting operation is required.
Element Setting Remarks
Z4BS Fixed to 1.5 Z4 reverse offset reach
(Fixed to 7.5) (*1)
Z4S (*2) Interlinked with Z3S Characteristic angle of Z4 mho element
Z4BS (*3) Interlinked with ZBS Angle of Z4 directional element
BRRS Fixed to 75 Angle of reverse right blinder BRRS
BRLS Interlinked with BRRS Reverse left blinder
BRLS Interlinked with BFLS Angle of reverse left blinder BRLS
Z4G (*2) Interlinked with Z3G Characteristic angle of Z4 mho element
Z4BG (*3) Interlinked with ZBG Angle of Z4 directional element
BRRG Fixed to 75 Angle of reverse right blinder BRRG
BRLG Interlinked with BRRG Reverse left blinder
BRLG Interlinked with BFLG Angle of reverse left blinder BRLG
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in
the case of 5 A rating.
(*2) Valid only when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid only when quadrilateral characteristic is selected by ZS-C and ZG-C.
The reverse looking elements Z4 (G,S), BRR (G,S) and BRL (G,S) must always operate for
reverse faults for which the forward overreaching element of the remote end operates. The
following setting coordination is required.
When zone 2 is selected as the forward-looking element,
Z4 setting = 1.2 (Zone 2 setting at remote end)
When zone 3 is selected,
Z4 setting = 1.2 (Zone 3 setting at remote end)
In both cases,
BRR setting = 1.2 (BFR setting at remote end)
2.4.3.4 Blocking Overreach Protection
Application
In blocking overreach protection (BOP), each terminal normally transmits a trip permission
signal, and transmits a trip block signal if the reverse looking Z4 operates and the forward
overreaching element does not operate. Tripping of the local circuit breaker is performed on
condition that the forward overreaching element has operated and a trip permission signal has
been received. As the forward overreaching element, it is possible to use zone 2 or zone 3.
If signal modulation is performed by an ON/OFF method, the signal is not normally transmitted
60
6 F 2 S 0 8 5 1
and a trip block signal is transmitted only when the reverse looking element operates. Tripping is
performed on condition that the forward overreaching element has operated and no signal has been
received. In this signaling system, the signal transmitted is a trip block signal and transmission of
this signal is only required in the event of an external fault. Therefore, even if power line carrier is
used, there will be no failure to operate or false operation due to attenuation of signals caused by
signal transmission through the fault.
The BOP receives a trip permission signal all the time. Therefore, when a forward external fault
occurs, the infeed terminal on which the forward overreaching element has operated attempts to
perform instantaneous tripping. At this time, at the remote outfeed terminal, the reverse looking
element operates and transmits a trip block signal. This signal is received at the infeed terminal
after a channel delay time. Therefore, a short delay is required for the tripping to check for the
reception of a trip block signal.
The BOP performs fast tripping for any fault along the whole length of the protected line even if an
open terminal exists. A strong infeed terminal operates for all internal faults even if a weak infeed
terminal exists. Therefore, no echo function is required. However, since no weak infeed logic is
applicable to the BOP, the weak infeed terminal cannot operate.
When a sequential fault clearance occurs for a fault on a parallel line, the direction of the current
on the healthy line is reversed. The status of the forward overreaching element changes from an
operating to a reset state at the terminal where the current is reversed from the inward direction to
outward direction, and from a non-operating status to an operating status at the other terminal. In
this process, if the operating periods of the forward overreaching element of both terminals
overlap, the healthy line may be tripped erroneously. To prevent this, current reversal logic is
provided. (See Section 2.4.3.6 for current reversal.)
Scheme Logic
Figure 2.4.3.4 shows the scheme logic of the BOP. The logic level of transmit signal CS and
receive signal R1-CR is "1" for a trip block signal and "0" for a trip permission signal.
The transmit signal is controlled in the BOP as follows:
In the normal state, the logic level of transmit signal CS is 0, and a trip permission signal is
transmitted. If the reverse looking Z4 operates and at the same time the forward overreaching
element zone 2 or zone 3 selected by the scheme switch [ZONESEL] does not operate, CS
becomes 1 and a trip block signal is transmitted. When this condition continues for 20 ms or more,
current reversal logic is picked up and a drop-off delay time of TREBK setting is given to reset the
transmission of the trip block signal.
Transmission of a trip permission signal continues for the TSBCT setting even after the local
terminal is tripped, assuring command tripping of the remote terminal.
The BOP outputs single-phase tripping signal S-TRIP or three-phase tripping signal M-TRIP to
the local terminal when zone 3 or zone 2 operates and at the same time the trip permission signal is
received (R1-CR=0). The delayed pick-up timer TCHD is provided to allow for the transmission
delay for receipt of the trip block signal from the remote terminal in the event of a forward external
fault.
To select the faulted phase reliably, phase selection is performed using the phase selection element
UVC. The phase selection logic is described in Section 2.4.3.7.
61
6 F 2 S 0 8 5 1
&
&
1
CS
Z4
20ms
t 0
0.01 10.00s
0 t
M-TRIP
S-TRIP Phase
Selection
& Z2
Z3
TCHD
0 - 50ms
t 0
"Z2"
"Z3"
[ZONESEL]
[PSB-CR]
" ON "
PSB
NON VTF
&
R1-CR 1
TREBK
TSBCT
0.00 1.00s
0 t
Figure 2.4.3.4 BOP Scheme Logic
Setting
The following shows the setting elements necessary for the BOP and their setting ranges.
For the settings of Z2, Z3 and UVC, refer to Section 2.4.1.
Element Range Step Default Remarks
Z4S 0.01 - 50.00 0.01 8.00 Z4 reach
(0.1 250.0 0.1 40.0) (*)
BRRS 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
Z4G 0.01 - 100.00 0.01 8.00 Z4 reach
(0.1 500.0 0.1 40.0)
BRRG 0.10 - 20.00 0.01 5.10 Reverse right blinder reach
(0.5 - 100.0 0.1 25.5)
TCHD 0 - 50 ms 1 ms 12 ms Channel delay time
TREBK 0.00 - 10.00s 0.01s 0.10s Current reversal block time
TSBCT 0.00 1.00s 0.01s 0.10s
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/
BOP /POP+DEF/UOP+DEF/
BOP+DEF/PUP+DEF
POP Scheme selection
ZONESEL Z2/Z3 Z2 Overreaching element selection
PSB - CR OFF/ON ON Power swing blocking
(*) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the
case of 5 A rating.
The following elements have fixed setting values or their settings are interlinked with other
elements listed above. So no setting operation is required.
Element Setting Remarks
Z4BS Fixed to 1.5 Z4 reverse offset reach
(Fixed to 7.5) (*1)
Z4S (*2) Interlinked with Z3S Characteristic angle of Z4 mho element
Z4BS (*3) Interlinked with ZBS Angle of Z4 directional element
BRRS Fixed to 75 Angle of reverse right blinder BRRS
BRLS Interlinked with BRRS Reverse left blinder
BRLS Interlinked with BFLS Angle of reverse left blinder BRLS
Z4G (*2) Interlinked with Z3G Characteristic angle of Z4 mho element
Z4BG (*3) Interlinked with ZBG Angle of Z4 directional element
BRRG Fixed to 75 Angle of reverse right blinder BRRG
62
6 F 2 S 0 8 5 1
Element Setting Remarks
BRLG Interlinked with BRRG Reverse left blinder
BRLG Interlinked with BFLG Angle of reverse left blinder BRLG
(*1) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the
case of 5 A rating.
(*2) Valid only when mho-based characteristic is selected by ZS-C and ZG-C.
(*3) Valid only when quadrilateral characteristic is selected by ZS-C and ZG-C.
The reverse looking elements Z4 (G,S), BRR (G,S) and BRL (G,S) must always operate for
reverse faults for which the forward overreaching element of the remote end operates. The
following setting coordination is required.
When zone 2 is selected as the forward-looking element,
Z4 setting = 1.2 (Zone 3 setting at remote end)
or
Z4 setting = (Zone 2 setting at remote end)
Note: should be determined in consideration of the extension of zone 2 by zero-sequence
compensation.
When zone 3 is selected,
Z4 setting = 1.2 (Zone 3 setting at remote end)
In both cases,
BRR setting = 1.2 (BFR setting at remote end)
The delayed pick-up timer TCHD is set as follows taking into account the transmission delay time
of the blocking signal and a safety margin of 5 ms.
TCHD setting = maximum signal transmission delay time(*) + 5ms
(*) includes delay time of binary output and binary input for the blocking signal.
2.4.3.5 Protection for Weak Infeed Terminal
The POP and UOP are provided with an echo function and weak infeed trip function. Both
functions are used for lines with weak infeed terminals.
Figure 2.4.3.5 shows the scheme logic for the echo function.
With the POP, when a trip permission signal is received (R1-CR=1) if neither forward
overreaching zone 2 or zone 3 nor reverse looking Z4 have operated, the echo function sends back
the received signal to the remote terminal. With the UOP, when reception of a blocking signal is
stopped (R1-CR=0) if neither forward overreaching zone 2 (or zone 3) nor reverse looking Z4
have operated, the echo function stops sending the blocking signal to the remote terminal. When
the circuit breaker is open (CB-OR = 0), too, the echo function sends back the trip permission
signal or stops sending the blocking signal. Timer TECCB is used to set the time from CB opened
to the echo logic enabled.
The terminal on which the forward overreaching element has operated can be tripped at high speed
by this echoed signal.
Once the forward overreaching element or reverse looking element have operated, transmission of
the echo signal is inhibited for 250 ms by delayed drop-off timer T1 even after they have reset.
In order to prevent any spurious echo signal from looping round between the terminals in a healthy
state, the echo signal is restricted to last for 200 ms by delayed pickup timer T2.
The echo function can be disabled by the scheme switch [ECHO].
63
6 F 2 S 0 8 5 1
The setting element necessary for the echo function and its setting range is as follows:
Element Range Step Default Remarks
TECCB 0.00 200.00 s 0.01 s 0.10 s Echo enable timer
ECHO OFF/ON ON Echo function
" ON "
&
&
&
1
200ms
50ms
(+)
t 0
Z3
Z2
Z4
T2
T1
250ms
0 t
0 t
ECH
[ZONESEL]
"Z3"
"Z2"
ECH
[ECHO]
1
CB-OR
1
R1-CR
1
&
TECCB
0.00 - 200.00s
t 0
619:C/R_DISECHO
Figure 2.4.3.5 Echo Logic
Figure 2.4.3.6 shows the scheme logic of the weak infeed trip function. Weak infeed tripping is
executed on condition that a trip permission signal has been received (R1-CR=1) for the POP, and
reception of a trip block signal has stopped (R1-CR=0) for the UOP, the undervoltage element
UVL (UVLS or UVLG) operates and neither forward overreaching zone 2 or zone 3 nor reverse
looking Z4 operates.
WIT &
WIT
[ZONESEL]
250ms
0 t
"Z3"
"Z2"
[WKIT]
"ON"
(+)
Z4
Z3
Z2
UVL
R1-CR
1
1
&
CB-OR
213:WI_TRIP
Figure 2.4.3.6 Weak Infeed Trip Logic
The undervoltage element responds to three phase-to-phase voltages and three phase-to-ground
voltages. The undervoltage element prevents false weak infeed tripping due to spurious operation
of the channel.
Single-phase tripping or three-phase tripping is also applicable to weak infeed tripping according
to the reclosing mode of the autoreclose function.
The weak infeed trip function can be disabled by the scheme switch [WKIT].
64
6 F 2 S 0 8 5 1
2.4.3.6 Measure for Current Reversal
In response to faults on parallel lines, sequential opening of the circuit breaker may cause a fault
current reversal on healthy lines. This phenomenon may cause false operation of the POP, UOP
and BOP schemes in the worst case. To prevent this, the POP, UOP and BOP are provided with
current reversal logic.
With the parallel line arrangement as shown in Figure 2.4.3.7 (a), suppose that a fault occurs at
time t1 at point F of line L1, A1 trips at time t2 first and then B1 trips at time t3. The direction of
the current that flows in healthy line L2 can be reversed at time t2. That is, the current flows from
terminal B to terminal A as indicated by a solid line in the period from time t1 to t2, and from
terminal A to terminal B as indicated by a broken line in the period from time t2 to t3. This current
reversal phenomenon may occur with the presence of an external looped circuit if not for parallel
lines.
Figure 2.4.3.7 (b) shows a sequence diagram of Z3 and Z4 and the current reversal logic CRL on
healthy line L2 before and after the occurrence of a current reversal. When the current is reversed,
Z3 operation and Z4 reset are seen at terminal A, while reset of Z3 and operation of Z4 are seen at
terminal B. If at this time, Z3 of A2 operates before Z3 of B2 is reset, this may cause false
operation of the POP, UOP and BOP on line L2.
Figure 2.4.3.7 Current Reversal Phenomenon
Figure 2.4.3.8 shows the current reversal logic. The current reversal logic is picked up on
condition that reverse looking Z4 has operated and forward overreaching zone 2 or zone 3 have
not operated, and the output CRL immediately controls the send signal to a trip block signal and at
the same time blocks local tripping. If the condition above continues longer than 20ms, the output
CRL will last for the TREBK setting even after the condition above ceases to exist.
A2
B2
B A
A1 B1
F L1
L2
(a) Direction of fault current
: Before A1 opened
: After A1 opened
t1
CRL
Z4
Z3
A2
(b) Sequence diagram
t2 t3
TREBK setting
TREBK setting
CRL
Z4
Z3
B2
65
6 F 2 S 0 8 5 1
1
TREBK
[ZONESEL]
CRL
Z2
Z3
Z4
&
0.01 10.00s
0 t
20ms
t 0
"Z3"
"Z2"
214:REV_BLK
Figure 2.4.3.8 Current Reversal Logic
The operation of the current reversal logic and its effect in the event of a fault shown in Figure
2.4.3.7 (a) are as follows. As shown in Figure 2.4.3.7 (b), the current reversal logic of terminal A2
operates (CRL = 1) immediately after the fault occurs. This operation lasts for TREBK setting
even after the current is reversed and Z3 operates, continuously blocking the local tripping and
transmitting a trip block signal to the terminal B2.
Even if overlap arises due to current reversal on the operation of Z3 at terminal A2 and terminal
B2, it will disappear while the current reversal logic is operating, thus avoiding false tripping of
the healthy line of parallel lines. When a current reversal occurs in the direction opposite to the
above, the current reversal logic at terminal B2 will respond similarly.
Current reversal logic is not picked up for internal faults, thus not obstructing high-speed
operation of any protection scheme.
2.4.3.7 Phase Selection Logic
Every command protection has phase selection logic for single-phase tripping. Figure 2.4.3.9
gives details of the phase selection logic displayed in blocks in Figures 2.4.3.1 to 2.4.3.4.
Tripping command signal TRIP of each command protection can be classified by the phase
selection logic as a single-phase tripping command or a three-phase tripping command. If the
distance measuring element for earth fault Z3G (or Z2G depending on the setting of the scheme
switch [ZONESEL]) is operating when a TRIP is input, a single-phase tripping command S-TRIP
is output to the phase in which the phase selection element UVC is operating. If the UVC is
operating with two or more phases, a three-phase tripping command M-TRIP is output.
The undervoltage detection element UVLS, not shown in Figure 2.4.3.9, is used for the phase
selection logic as phase fault detector. The UVLS is also used for fault location.
If the distance measuring element for phase fault Z3S (or Z2S) is operating when a TRIP is input,
a three-phase tripping command M-TRIP is output.
66
6 F 2 S 0 8 5 1
1
&
M - TRIP
1
Z3S - CA
Z3S - BC
Z3S - AB
1 &
S - TRIP
C
B
A
TRIP
1
Z3G - C
Z3G - B
Z3G - A
&
&
&
UVC - C
UVC - B
UVC - A
&
&
&
66
67
68
28
29
30
43
44
45
Figure 2.4.3.9 Phase Selection Logic for Command Protection
2.4.3.8 Interface with Signaling Equipment
GRZ100 interfaces with protection signaling equipment through binary input and output circuits
as shown in Figure 2.4.3.10.
Receiving command signals for remote terminal from the signaling equipment are input to
photo-coupler circuits BIn and BIm. A guard signal in frequency shift signaling or an alternative
trip signal is input to BIm. BIn and BIm output signals R1-CH1 and R1-CH2 through logic level
inversion (NOT logic) circuit by PLC function (refer to Section 3.2.3).
A sending command signal CS to the signaling equipment should be output to the auxiliary relay
BO13 through a logic level inversion circuit (Logic level inversion of CS can be performed by
BOSW switch or also by PLC function.). BO13 has one normally open contact.
In the BOP scheme, a signal channel automatic test function is available. Sending test signal SBT
can be assigned to any of the user configurable output relays BOn through a logic level inversion
circuit by PLC function. BOn has one normally close contact.
Note: In setting the signal SBT, the 0.2s delayed drop-off timer in the logic level inversion
circuit must be disabled by setting the scheme switch [BOTDn] to "OFF".
S-DEF2 or S-DEFBOP2 is a sending command signal used for DEF command protection and
assigned to any of the user configurable output relays BOn. (See Section 2.4.4.1.)
67
6 F 2 S 0 8 5 1
Logic Level
Inversion
Trip
Guard
or Trip
BIn
BIm
(+)
(-)
R1-CH1
Logic Level
Inversion
R1-CH2
Signal
Receiving
Signaling Equipment
Signal
Sending
BO13
Logic Level
Inversion (*)
CS Trip
BO9
Logic Level
Inversion (*)
SBT Test
BOn
Logic Level
Inversion (*)
S-DEF2
(or S-DEFBOP2)
Trip
(*): By PLC function.
Figure 2.4.3.10 Interface with Signaling Equipment
2.4.3.9 Signaling Channel
Table 2.4.3.1 shows the protection scheme and required signaling channel. "Simplex" here means
that a transmit signal is shared by all terminals. "Multiplex" means that a specific channel is used
for each terminal.
Table 2.4.3.1 Protection Scheme and Signaling Channel
Scheme
Simplex Multiplex
PUP
POP
UOP
BOP
Since the PUP transmits a trip permission signal through operation of the underreaching element,
it is not necessary to distinguish a transmit signal from a receive signal and a simplex channel
suffices. Of course, a multiplex channel can also be applied.
Since the POP transmits a trip permission signal through operation of the overreaching element, it
is necessary to distinguish a transmit signal from a receive signal to prevent false operation in case
of a fault in the overreaching zone. Therefore, a multiplex channel is necessary.
Since the UOP and BOP transmit a trip block signal, a simplex channel suffices. A multiplex
channel can also be applied.
The signal received from the protection signaling equipment is generally a single one, while with
frequency shift signaling, two signals, a trip signal and a guard signal, are received. The GRZ100
is equipped with signal receive logic shown in Figure 2.4.3.11 to respond to either case. In the case
of a single signal, a signal from the signaling equipment is input to R1-CH1 and the scheme switch
[CHSEL] is set to "Single". In the case of two signals, a trip signal is input to R1-CH1, a guard
signal or an alternative trip signal is input to R1-CH2 and the [CHSEL] is set to "Guard". Signal
R1-CR selected by this scheme switch is used as a receive signal in command protection.
When two signals are utilized, the signal receive logic outputs signal R1-CR only when receiving
a trip signal only or no trip signal nor guard signal is received for more than 20 ms. However, the
output by the latter lasts only for 100 ms. When the latter continues for more than 100 ms, a
telecommunication circuits failure alarm signal R1-CF is output.
68
6 F 2 S 0 8 5 1
1
&
&
R1-CH1
"Single"
"And"
R1-CR
[CHSEL]
"Guard"
R1-CH2
R1-CF
&
&
"CH1"
"CH2"
[CH-DEF]
"(PUP+DEF)"
-
1
R1-CR-DEF
[SCHEME]
+
-
+
"(POP+DEF)", "(UOP+DEF)", "(BOP+DEF)"
&
&
20ms 150ms
0 t
100ms
t 0
&
t 0
"Guard"
Figure 2.4.3.11 Signal Receive Logic
Selecting "And" for the scheme switch [CHSEL] in two signals reception will allow ANDing of
two signals to be set as signal R1-CR.
When directional earth fault command protection (see Section 2.4.4.1) is used with POP, UOP or
BOP scheme of distance protection and two channels are available, signal channel can be
separated from distance protection by setting the scheme switch [CHSEL] to "Single" and
[CH-DEF] to CH2. In this case, signals CH1 and CH2 are used for distance protection and
directional earth protection respectively. If the scheme switch [CH-DEF] is set to CH1, signal
CH1 is shared by the both protections.
When directional earth fault command protection is used with PUP scheme, signal channel is
separated irrespective of [CH-DEF] setting.
In three-terminal application, the signal receive logic for remote 2 is same as that of remote 1
shown in Figure 2.4.3.11.
Following table shows the scheme switch settings and usable signals:
Use of signal Scheme CHSEL setting CH-DEF setting
CH1 CH2
PUP+DEF Single CH1 PUP DEF
CH2 PUP DEF
POP+DEF Single CH1 POP and DEF (*) --
CH2 POP DEF
UOP+DEF Single CH1 UOP and DEF (*) --
CH2 UOP DEF
BOP+DEF Single CH1 BOP and DEF (*) --
CH2 BOP DEF
(*) CH1 is shared by the distance and directional earth fault command protections.
Setting
Element Range Step Default Remarks
CHSEL Single/Guard/And Single Signal receiving
CH-DEF CH1/CH2 CH1 Channel separation
69
6 F 2 S 0 8 5 1
2.4.4 Directional Earth Fault Protection
For a high-resistance earth fault for which the impedance measuring elements cannot operate, the
GRZ100 uses a directional earth fault element (DEF) to provide the following protections.
Directional earth fault command protection
Directional inverse or definite time earth fault protection
Figure 2.4.4.1 shows the scheme logic for the directional earth fault protection. The four kinds of
protection above can be enabled or disabled by the scheme switches [SCHEME], [CRSCM],
[DEFFEN] and [DEFREN]. The DEF and EF protections issue an alarm individually for the
backup trip for earth fault. The DEF protection can be blocked by the binary input signal (PLC
signal) DEF_BLOCK.
NON VTF
Command
Protection
&
CB-DISCR
&
M-TRIP
DEFR
DEFF
&
&
1
[DEFFEN]
TDEF
t 0
0.00 - 10.00s
"ON"
DEF_ALARM
[SCHEME]
S-TRIP
(from Figure 3.2.1.2.)
59
58
186
DEF_BLOCK 1629
1
[DEFREN]
TDER
t 0
0.00 - 10.00s
"ON"
[CRSCM]
"ON"
+
&
DEF_INST_TP 1705
&
DEFR_INST_TP 1707
[DEFBTAL]
"ON"
"
[DEFI]
NOD"
"R"
F"
EFI
&
61
EFI_BLOCK 1628
&
&
"
1
BU TRIP
(M-TRIP)
677
763 194
1
DEF_TRIP
DEFR_
TRIP
184
EFI_TRIP
DEFF_BLOCK 1849
DEFR_BLOCK 1851
&
&
Figure 2.4.4.1 Directional Earth Fault Protection
The directional earth fault command protection provides the POP, UOP and BOP schemes using
forward looking DEFF and reverse looking DEFR elements. All schemes execute three-phase
tripping and autoreclose.
The command protection is disabled during a single-phase autoreclosing period (CB-DISCR=1).
The directional earth fault protection as backup protection is described in Section 2.4.4.2.
The directional earth fault element DEF provides selective protection against a high-resistance
earth fault. The direction of earth fault is determined by the lagging angle () of the residual
current (3l
0
) with respect to the residual voltage (3V
0
). The residual voltage and residual current
are derived from the vector summation of the three-phase voltages and three-phase currents inside
the relay.
The phase angle in the event of an internal fault is equal to the angle of the zero-sequence
impedance of the system and in the directly-earthed system this value ranges approximately from
50 to 90. of the DEF can be set from 0 to 90. The minimum voltage necessary to maintain
directionality can be set from 1.7 to 21.0 V.
70
6 F 2 S 0 8 5 1
2.4.4.1 Directional Earth Fault Command Protection
High-speed directional earth fault command protection is provided using the forward looking
directional earth fault element DEFF and reverse looking directional earth fault element DEFR.
The signaling channel of DEF command protection can be shared with or separated from distance
protection by the scheme switch [CH-DEF].
The DEF command protections are applied in combination with the distance command protection
POP, UOP, BOP and PUP and enabled when the scheme switch [SCHEME] is set to "POP+DEF",
"UOP+DEF", "BOP+DEF" or "PUP+DEF". These protections are called as the DEF POP, DEF
UOP, DEF BOP and DEF PUP hereafter. The POP, UOP or BOP schemes can be selected as a
common scheme. However, in the DEF PUP, distance protection takes the PUP scheme but DEF
command protection takes the POP scheme and signaling channels of distance and DEF command
protections are always separated (CH1: distance, CH2: DEF, see Section 2.4.3.9.).
The DEF command protection can select fast tripping or delayed tripping by a timer setting.
Delayed tripping is used when it is desired to give priority to distance protection.
The DEF command protection is blocked during a single-phase autoreclose period by the distance
protection (CB-DISCR=1). The signal CB-DISCR is generated with the binary input signals (PLC
signals) of circuit breaker auxiliary contact (refer to Section 3.2.1).
"POP+DEF"
"UOP+DEF"
"BOP+DEF"
"PUP+DEF"
DEFFCR
DEFR
DEFF
NON VTF
&
CB-DISCR
TDEFF
t 0
[SCHEME]
&
TDEFR
t 0
0 300ms
DEFRCR
216
215
Figure 2.4.4.2 DEF Command Protection
DEF POP, DEF UOP and DEF PUP scheme logic
Figure 2.4.4.3 shows the scheme logic of the DEF POP and DEF UOP.
(UOP)
&
1 20ms
t 0
(UOP)
(POP)
TDEFR
0 - 300ms
S-TRIP
M-TRIP
&
1
1
t 0
t 0
R1-CR-DEF
R1-CR-DEF
CS
CS
DEFF
DEFR
1
TDEFF
(POP)
&
TREBK
0.01 10.00s
0 t
TSBCT
0.00 1.00s
0 t
R1-CR-DEF: Trip permission signal from the remote terminal.
Signal No. Signal name Description
1568: EXT_CAR.R1-1 Trip carrier signal from remote terminal
1569: EXT_CAR.R1-2 Guard/And carrier signal from remote terminal
CS (Carrier send) signal
Signal No. Signal name
225: EXT_CAR-S for Distance and DEF command protection (CH1)
338: EXT_DEFCAR-S for DEF command protection (CH2)
Figure 2.4.4.3 DEF POP and DEF UOP Scheme Logic
When the PUP+DEF scheme logic is selected, the DEF scheme logic is constructed same as the
71
6 F 2 S 0 8 5 1
DEF POP scheme logic in Figure 2.4.4.3.
The signal transmitted is a trip permission signal for the POP and a trip block signal for the UOP.
In the event of an internal fault, the POP transmits a signal, while the UOP stops transmission. In
Figure 2.4.4.3, a signal is transmitted when CS becomes 1, and when the signal is received
CR-DEF becomes 1.
When the DEFF operates, CS becomes 1 for the POP and a signal (that is, a trip permission signal)
is transmitted. For the UOP, CS becomes 0 and transmission of the signal (that is, a trip block
signal) is stopped.
When a signal is received in the POP, or no signal is received in the UOP, tripping is executed on
condition that the DEFF has operated. In order to assure tripping of the remote terminal,
transmission of a trip permission signal or stoppage of a trip block signal continues for the TSBCT
setting time even after the DEFF reset.
The DEFR is used for the current reversal logic in the same manner as reverse looking Z4 in the
distance protection (for the current reversal, refer to Section 2.4.3.6).
When operation of the DEFR and no-operation of the DEFF continue for 20 ms or more, even if
the DEFF operates or the DEFR is reset later, tripping of the local terminal or transmission of the
trip permission signal is blocked for the TREBK setting time.
The POP or UOP can be set for instantaneous operation or delayed operation by setting on-delay
timer TDEFF and TDEFR.
The DEF command protection is provided with an echo function and weak infeed trip function.
Both functions are used for lines with weak infeed terminals.
The echo function allows fast tripping of the terminal on which the DEFF has operated when
applied to a line with an open terminal or a weak infeed earth fault current terminal. The scheme
logic is shown in Figure 2.4.4.4.
With the POP, when a trip permission signal is received (R1-CR-DEF = 1) if neither the forward
looking DEFF nor the reverse looking DEFR operates, the echo function sends back the received
signal to the remote terminal. With the UOP, when reception of a blocking signal is stopped
(R1-CR-DEF = 0), if the DEFF and DEFR do not operate, the echo function stops transmission of
the blocking signal likewise. When the circuit breaker is open, the echo function also sends back
the trip permission signal or stops transmission of the blocking signal.
Once the DEFF or the DEFR operates, transmission of the echo signal is inhibited for 250 ms by
delayed drop-off timer T1 even after they are reset.
In order to prevent any spurious echo signal from looping round between terminals in a healthy
state, the echo signal is restricted to last 200 ms by delayed pick-up timer T2.
The echo function can be disabled by the scheme switch [ECHO].
When a signaling channel is shared by the distance protection and DEF protection, it is necessary
to unite the scheme logic of both echo functions so that the echo function may not be picked up in
the event of an external fault. The echo function at this time is blocked by Z2 (or Z3) and Z4
indicated by a dotted line in Figure 2.4.4.4.
72
6 F 2 S 0 8 5 1
"ON"
&
&
1
200ms
(+)
t 0
Z3
Z2
Z4
T2 T1
250ms
0 t
50ms
0 t
[ZONESEL]
"Z3"
"Z2"
[ECHO]
1
CB-OR
1
R1-CR-DEF(POP)
&
TECCB
0.00 - 200.00s
t 0
DEFFCR
DEFRY
1 R1-CR-DEF(UOP)
(UOP)
(POP)
CS
CS 1
R1-CR-DEF: Trip permission signal from the remote terminal.
Signal No. Signal name Description
1568: EXT_CAR.R1-1 Trip carrier signal from remote terminal
1569: EXT_CAR.R1-2 Guard/And carrier signal from remote terminal
CS (Carrier send) signal
Signal No. Signal name
225: EXT_CAR-S for Distance and DEF command protection (CH1)
338: EXT_DEFCARS for DEF command protection (CH2)
&
&
ECHO1_DEF-R1
Figure 2.4.4.4 Echo Function in DEF POP and DEF UOP Scheme Logic
Figure 2.4.4.5 shows the scheme logic of the weak infeed trip function. Weak infeed tripping is
executed on condition that a trip permission signal has been received (ECHO1_DEF-R1=1) for
the POP, the undervoltage element UVL (UVLS or UVLG) operates.
The undervoltage element responds to three phase-to-phase voltages and three phase-to-ground
voltages. The undervoltage element prevents false weak infeed tripping due to spurious operation
of the channel.
Single-phase tripping or three-phase tripping is also applicable to weak infeed tripping according
to the reclosing mode of the autoreclose function.
The weak infeed trip function can be disabled by the scheme switch [WKIT].
DEFWI_TRIP
&
[WKIT]
"ON"
(+)
UVL
ECHO1_DEF-R1
&
PUP
778, 779, 780
Figure 2.4.4.5 Weak Infeed Trip Logic
When the signaling channel of DEF POP or DEF UOP is separated from that of distance command
protection, the signal S-DEF2 is used for CS and assigned to a user configurable binary output
relay (see Section 3.2.2.).
DEF BOP scheme logic
Figure 2.4.4.6 shows the scheme logic of the DEF BOP.
&
&
1
0 - 50ms
TDEFR
TCHD
0 - 300ms
20ms
t 0
CS
DEFF
DEFR
t 0
t 0
M-TRIP
&
&
t 0
TDEFF
R1-CR-DEF
1
TSBCT
0.00 1.00s
0 t
0.01 10.00s
0 t
TREBK
Figure 2.4.4.6 DEF BOP Scheme Logic
73
6 F 2 S 0 8 5 1
With the BOP, the signal transmitted is a trip block signal. When the reverse looking DEFR
operates, the logic level of the transmit signal CS becomes 1 and a trip block signal is transmitted.
When the trip block signal is received, R1-CR-DEF becomes 1.
When the forward looking DEFF operates, it executes tripping on condition that no trip blocking
signal should be received.
The delayed pick-up timer TCHD is provided to allow for the transmission delay of the trip block
signal from the remote terminal. Therefore, the time is set depending on the channel delay time.
TCHD setting = maximum signal transmission delay time(*) + 5ms
(*) includes delay time of binary output and binary input for the blocking signal.
The DEFR is also used for the current reversal logic (for current reversal, see Section 2.4.3.6).
When operation of the DEFR and non-operation of the DEFF last for 20 ms or more, even if the
DEFF operates or the DEFR is reset later, tripping of the local terminal is blocked for the TREBK
setting time and transmission of the trip block signal continues for the TSBCT setting time.
When the signaling channel of DEF BOP is separated from that of distance command protection,
the signal S-DEFBOP2 is used for CS and assigned to a user configurable binary output relay (see
Section 3.2.2.).
Setting
The following setting is required for the DEF command protection:
Element Range Step Default Remarks
DEFF Forward looking DEF
DEFFI 0.5 - 5.0 A 0.1 A 1.0 A Residual current
(0.10 - 1.00 A 0.01 A 0.2 A) (*)
DEFFV 1.7 21.0 V 0.1 V 2.0 V Residual voltage
TDEFF 0.00 - 0.30 s 0.01 s 0.15 s Delayed tripping
DEFR Reverse looking DEF
DEFRI 0.5 - 5.0 A 0.1 A 1.0 A Residual current
(0.10 - 1.00 A 0.01 A 0.20 A)
DEFRV 1.7 21.0 V 0.1 V 2.0 V Residual voltage
TDEFR 0.00 - 0.30 s 0.01 s 0.15 s Delayed tripping
DEF 0 - 90 1 85 Characteristic angle
PROTECTION
SCHEME
3ZONE/Z1EXT/PUP/POP/UOP/ BOP/
POP+DEF/UOP+DEF/ BOP+DEF/PUP+DEF
POP Scheme selection
CHSEL Single/Guard/And Single
CH-DEF CH1/CH2 CH1
BODEFSW Active / Inactive Active BO for DEF: active or inactive
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
When the DEFF at the remote end operates, the local DEFR must always operate for reverse faults.
The setting levels of the residual current and residual voltage for the DEFR must be lower than that
for the DEFF.
The following setting elements are used in common with the BOP of distance protection or its
setting is interlinked with other elements listed above. So no setting operation is required here.
Element Range Step Default Remarks
TCHD 0-50 ms 1 ms 12 ms Used in common with BOP
TREBK 0.00 - 10.00s 0.01s 0.10s
TSBCT 0.00 - 1.00s 0.01s 0.10s
ECHO OFF/ON OFF Used in common with BOP
74
6 F 2 S 0 8 5 1
2.4.4.2 Directional Earth Fault Protection
The scheme logic is shown in Figure 2.4.4.1.
The directional inverse or definite time earth fault protection as backup protection executes
three-phase final tripping. The forward looking DEFF or reverse looking DEFR can be selected.
The directional inverse and definite time earth fault protections are available to trip
instantaneously by binary input DEF_INST-TRIP except for [DEFEN]= OFF setting.
In order to give priority to the distance protection, the directional earth fault protection enables
inverse time or definite time delayed tripping by the scheme switch [DEFEN].
Setting
The settings necessary for the directional earth fault protection are as follows:
Element Range Step Default Remarks
DEFF Forward looking DEF
DEFFI 0.5 - 5.0 A 0.1 A 1.0 A Residual current
(0.10 - 1.00 A 0.01 A 0.2 A) (*)
DEFFV 1.7 21.0 V 0.1 V 2.0 V Residual voltage
TDEF 0.00 - 0.30 s 0.01 s 2.0 s Definite time setting
DEFR Reverse looking DEF
DEFRI 0.5 - 5.0 A 0.1 A 1.0 A Residual current
(0.10 - 1.00 A 0.01 A 0.2 A) (*)
DEFRV 1.7 21.0 V 0.1 V 2.0 V Residual voltage
TDER 0.00 - 0.30 s 0.01 s 2.0 s Definite time setting
DEF 0 - 90 1 85 Characteristic angle
DEFFEN OFF/ON OFF Forward DEF backup trip enable
DEFREN OFF/ON OFF Reverse DEF backup trip enable
DEFI OFF/NOD/F/R OFF EFI directional control
DEFBTAL OFF/ON ON DEF backup trip alarm
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The DEF element is shared with the command protection.
2.4.4.3 Characteristics of Directional Earth Fault Elements DEFF and DEFR
There are two types of directional earth fault element, the forward looking element (DEFF) and
reverse looking element (DEFR). Their characteristics are shown in Figure 2.4.4.7.
Both the DEFF and DEFR use a residual voltage as their polarizing voltage and determine the fault
direction based on the phase relationship between the residual current and polarizing voltage.
75
6 F 2 S 0 8 5 1
3V
0
+180
DEFF
3I
0
I
sf
I
sr
DEFR
Figure 2.4.4.7 Directional Earth Fault Element
The operation decision is made using the following equation.
DEFF
3I
0
cos( ) I
sf
3V
0
V
sf
DEFR
3I
0
cos( 180) I
sr
3V
0
V
sr
where,
3I
0
= residual current
3V
0
= residual voltage
3V
0
= polarizing voltage
= lagging angle of (3I
0
) to (3V
0
)
= characteristic angle setting (lagging to polarizing voltage)
I
sf
, I
sr
= current setting
V
sf
, V
sr
= voltage setting
2.4.5 Overcurrent Backup Protection
Inverse time and definite time overcurrent protections are provided for phase faults and earth
faults respectively.
Scheme logic
The scheme logic of the overcurrent backup protection is shown in Figure 2.4.5.1. The phase
overcurrent protection issues single-phase tripping signals in the operation of OC and OCI, and
can issue a three-phase tripping signal BU-TRIP by PLC signals OC_3PTP and OCI_3PTP. The
default of the phase overcurrent backup protection is a three-phase tripping since both of the PLC
signals OC_3PTP and OCI_3PTP are assigned to 1(=logic level) (Signal No. =1). The earth
fault protection issues a three-phase tripping signal BU-TRIP in the operation of EF or EFI
element.
76
6 F 2 S 0 8 5 1
The overcurrent backup protection can provide a fail-safe function by assigning the PLC signals
OC-_FS and OCI-_FS to an output of relay element, etc. The PLC signals OC-_FS and
OCI-_FS are assigned to 1 (Signal No. =1) as default.
Tripping by each element can be disabled by the scheme switches [OCBT], [OCIBT], [EFBT] and
[EFIBT], and also can be disabled by the binary input signals (PLC signals) OC_BLOCK,
OCI_BLOCK, EF_BLOCK and EFIBLOCK. The EF element issues an alarm for the backup trip
for earth fault. The alarm can be disabled by the scheme switch [EFBTAL]. The OC and EF
protections can trip instantaneously by PLC signals OC_INST_TP and EF_INST_TP.
OC-A
1
&
0.00 10.00s
TOC
t 0
t 0
t 0
"ON"
[OCBT]
+
1 OC_BLOCK 1625
&
&
&
"ON"
[OCIBT]
+
1 OCI_BLOCK 1626
&
&
OC-B_FS 1609
94
95
96
97
98
99
OC_TRIP
326
OC_INST_TP 1703
OC-A_FS 1608
OC-A TP
OC-B TP
OC-C TP
1
1
1
OC_3PTP
1716
&
615
614
613
OC-A TRIP
OC-B TRIP
OC-C TRIP
1
OCI_TRIP
327
OCI-A TP
OCI-B TP
OCI-C TP
1
1
1
OCI_3PTP 1717
&
618
617
616
OCI-A TRIP
OCI-B TRIP
OCI-C TRIP
OC-B
OC-C
OCI-A
OCI-B
OCI-C
OC-C_FS 1610
&
&
&
1
1
1
OCI-B_FS 1613
OCI-A_FS 1612
OCI-C_FS 1614
(M-TRIP)
S-TRIP
S-TRIP
BU-TRIP
1
EF
TEF
t 0
0.00 10.00s
&
"ON"
[EFBT]
+
"ON"
[EFBTAL]
+
1 EF_BLOCK 1627
&
EFI
&
"NOD"
[DEFI]
+
1 EFI_BLOCK 1628
60
61
EF_BU-TRIP
EFI_TRIP
EF_ALARM
194
187
185
184
EF_INST_TP 1702
& 1 1
EF_TRIP
678
Figure 2.4.5.1 Overcurrent Backup Protection
2.4.5.1 Inverse Time Overcurrent Backup Protection
In a system in which the fault current is mostly determined by the fault location, without being
greatly affected by changes in the power source impedance, it is advantageous to use inverse
77
6 F 2 S 0 8 5 1
definite minimum time (IDMT) overcurrent protection. Reasonably fast tripping can be obtained
even at a terminal close to the power source by using inverse time characteristics. In the IDMT
overcurrent protection function, one of the following three IEC-standard-compliant inverse time
characteristics and one long time inverse characteristic is available.
standard inverse IEC 60255-3
very inverse IEC 60255-3
extremely inverse IEC 60255-3
The IDMT element has a reset feature with definite time reset.
If the reset time is set to instantaneous, then no intentional delay is added. As soon as the
energising current falls below the reset threshold, the element returns to its reset condition.
If the reset time is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising current exceeds the setting for a transient period without causing tripping,
then resetting is delayed for a user-definable period. When the energising current falls below the
reset threshold, the integral state (the point towards operation that it has travelled) of the timing
function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
Setting
The following table shows the setting elements necessary for the inverse time overcurrent backup
protection and their setting ranges.
Element Range Step Default Remarks
OCI 0.5 - 25.0 A 0.1 A 10.0 A
( 0.10 - 5.00 A 0.01 A 2.00 A) (*)
TOCI 0.05 - 1.00 0.01 0.50 OCI time setting
TOCIR 0.0 10.0 s 0.1 s 0.0 s OCI definite time reset delay
[MOCI] Long/Std/Very/Ext Std OCI inverse characteristic selection
[OCIBT] ON/OFF ON OCI backup protection
EFI 0.5 - 5.0 A 0.1 A 5.0 A Earth fault EFI setting
( 0.10 - 1.00 A 0.01 A 1.00 A) (*)
TEFI 0.05 - 1.00 0.01 0.50 EFI time setting
TEFIR 0.0 10.0 s 0.1 s 0.0 s EFI definite time reset delay
[MEFI] Long/Std/Very/Ext Std EFI inverse characteristic selection
[DEFI] OFF/NOD/F/R OFF EFI directional control
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The scheme switches [MOCI] and [MEFI] are used to select one of the four inverse time
characteristics. The DEFI is the scheme switch for directional control selection and if NOD is
selected, the inverse time overcurrent protection executes non-directional operation. If F or R is
selected, it executes forward operation or reverse operation in combination with the DEFF or
DEFR. If OFF is selected, the inverse time overcurrent protection is blocked.
Current setting
In Figure 2.4.5.2, the current setting at terminal A is set lower than the minimum fault current in
the event of a fault at remote end F1. Furthermore, when considering also backup protection of a
fault on an adjacent line, it is set lower than the minimum fault current in the event of a fault at
remote end F3. For grading of the current settings, the terminal furthest from the power source is
set to the lowest value and the terminals closer to the power source are set to a higher value.
The minimum setting is restricted so as not to operate on false zero-sequence currents caused by an
78
6 F 2 S 0 8 5 1
unbalance in the load current, errors in the current transformer circuits or zero-sequence mutual
coupling of parallel lines.
F3 F2 F1
C B A
Figure 2.4.5.2 Current Settings in Radial System
Time setting
Time setting is performed to provide selectivity in relation to the relays on adjacent lines. Consider
a minimum source impedance when the current flowing in the relay becomes a maximum. In
Figure 2.4.5.2, in the event of a fault at the near end, F2 of the adjacent line, the operating time is
set so that terminal A may operate by time grading Tc behind terminal B. The current flowing in
the relays may sometimes be greater when the remote end of the adjacent line is open. At this time,
time coordination must also be kept.
The reason why the operating time is set when the fault current reaches a maximum is that if time
coordination is obtained for a large fault current, then time coordination can also be obtained for
small fault current as long as relays with the same operating characteristic are used for each
terminal.
The grading margin Tc of terminal A and terminal B is given by the following expression for a
fault at point F2 in Figure 2.4.5.2.
Tc = T
1
+ T
2
+ T
m
where, T
1
: circuit breaker clearance time at B
T
2
: relay reset time at A
T
m
: time margin
When single-phase autoreclose is used, the minimum time of the earth fault overcurrent protection
must be set longer than the time from fault occurrence to reclosing of the circuit breaker. This is to
prevent three-phase final tripping from being executed by the overcurrent protection during a
single-phase autoreclose cycle.
2.4.5.2 Definite Time Overcurrent Backup Protection
In a system in which the fault current does not vary a great deal in relation to the position of the
fault, the advantages of the IDMT characteristics are not fully used. In this case, definite time
overcurrent protection is applied. The operating time can be set irrespective of the magnitude of
the fault current.
The definite time overcurrent protection consists of instantaneous overcurrent elements and
delayed pick-up timers started by them.
Identical current values can be set for terminals, but graded settings are better than identical
settings in order to provide a margin for current sensitivity. The farther from the power source the
terminal is located, the higher sensitivity (i.e. the lower setting) is required.
The operating time of the overcurrent element at each terminal is constant irrespective of the
magnitude of the fault current and selective protection is implemented by graded settings of the
delayed pick-up timer. As a result, the circuit breaker of the terminal most remote from the power
source is tripped in the shortest time.
When setting the delayed pick-up timers, time grading margin Tc is obtained in the same way as
explained in Section 2.4.5.1.
79
6 F 2 S 0 8 5 1
Setting
The setting elements necessary for the definite time overcurrent backup protection and their
setting ranges are shown below.
Element Range Step Default Remarks
OC 0.5 - 100.0 A 0.1 A 6.0 A Phase overcurrent
( 0.1 - 20.0 A 0.1 A 1.2 A) (*)
TOC 0.00 - 10.00 s 0.01 s 3.00 s OC delayed tripping
EF 0.5 - 5.0 A 0.1 A 1.0 A Residual overcurrent
( 0.10 - 1.00 A 0.01 A 0.20 A) (*)
TEF 0.00 - 10.00 s 0.01 s 3.00 s EF delayed tripping
[OCBT] OFF/ON ON OC backup protection
[EFBT] OFF/ON ON EF backup protection
[EFBTAL] OFF/ON ON EF backup trip alarm
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
2.4.5.3 Characteristics of Inverse Definite Minimum Time (IDMT) OC, EF, DEF Elements
As shown in Figure 2.4.5.3, the IDMT element has one long time inverse characteristic and three
inverse time characteristics in conformity with IEC 60255-3. One of these characteristics can be
selected.
These characteristics are expressed by the following equations.
Long Time Inverse
t = T
120
(I/Is)1
Standard Inverse
t = T
0.14
(I/Is)
0.02
1
Very Inverse
t = T
13.5
(I/Is) 1
Extremely Inverse
t = T
80
(I/Is)
2
1
where,
t = operating time
I = fault current
Is = current setting
T = time multiplier setting
80
6 F 2 S 0 8 5 1
1
0.1
0.5
1
5
10
50
100
Standard Inverse
Very Inverse
Extremely Inverse
5 10 20 30
200
0.2
2
20
Long-time
I
2
Current I (Multiple of setting)
(s)
Operating
time t
T =1.0
Figure 2.4.5.3 IDMT Characteristics
Definite time reset
The definite time resetting characteristic is provided.
If the delay period is set to instantaneous (TOCIR, TEFIR, TDEFR or TDERR=0.0s), then no
intentional delay is added. As soon as the energising current falls below the reset threshold, the
element returns to its reset condition.
If the delay period is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising current exceeds the setting for a transient period without causing tripping,
then resetting is delayed for a user-definable period. When the energising current falls below the
reset threshold, the integral state (the point towards operation that it has travelled) of the timing
function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
81
6 F 2 S 0 8 5 1
2.4.6 Thermal Overload Protection
The temperature of electrical plant rises according to an I
2
t function and the thermal overload
protection in GRZ100 provides a good protection against damage caused by sustained
overloading. The protection simulates the changing thermal state in the plant using a thermal
model.
The thermal state of the electrical system can be shown by equation (1).
=
I
I
e
AOL
t
2
2
1 100
% (1)
where:
= thermal state of the system as a percentage of allowable thermal capacity,
I = applied load current,
I
AOL
= allowable overload current of the system,
= thermal time constant of the system.
The thermal state 0% represents the cold state and 100% represents the thermal limit, which is the
point at which no further temperature rise can be safely tolerated and the system should be
disconnected. The thermal limit for any given system is fixed by the thermal setting I
AOL
. The relay
gives a trip output when = 100%.
The thermal overload protection measures the largest of the three phase currents and operates
according to the characteristics defined in IEC60255-8. (Refer to Appendix O for the
implementation of the thermal model for IEC60255-8.)
Time to trip depends not only on the level of overload, but also on the level of load current prior to
the overload - that is, on whether the overload was applied from cold or from hot.
Independent thresholds for trip and alarm are available.
The characteristic of the thermal overload element is defined by equation (2) and equation (3) for
cold and hot. The cold curve is a special case of the hot curve where prior load current Ip is
zero, catering to the situation where a cold system is switched on to an immediate overload.
t =Ln
I
I I
AOL
2
2 2
(2)
t =Ln
I I
I I
P
AOL
2 2
2 2
(3)
where:
t = time to trip for constant overload current I (seconds)
I = overload current (largest phase current) (amps)
I
AOL
= allowable overload current (amps)
I
P
= previous load current (amps)
= thermal time constant (seconds)
Ln = natural logarithm
Figure 2.4.6.1 illustrates the IEC60255-8 curves for a range of time constant settings. The
left-hand chart shows the cold condition where an overload has been switched onto a previously
un-loaded system. The right-hand chart shows the hot condition where an overload is switched
82
6 F 2 S 0 8 5 1
onto a system that has previously been loaded to 90% of its capacity.
Thermal Curves (Cold Curve - no
prior load)
0.01
0.1
1
10
100
1000
1 10
Over load Cur r ent (Mult iple of I
AOL
)
O
p
e
r
a
t
e
T
i
m
e
(
m
i
n
u
t
e
s
)
Thermal Curves (Hot Curve - 90%
prior load)
0.001
0.01
0.1
1
10
100
1000
1 10
Overload Current (Multiple of I
AOL
)
O
p
e
r
a
t
e
T
i
m
e
(
m
i
n
u
t
e
s
)
Figure 2.4.6.1 Thermal Curves
Scheme Logic
Figure 2.4.6.2 shows the scheme logic of the thermal overload protection.
The thermal overload element THM has independent thresholds for alarm and trip, and outputs
alarm signal THM_ALARM and trip signal THM_TRIP. The alarming threshold level is set as a
percentage of the tripping threshold.
The alarming and tripping can be disabled by the scheme switches [THMAL] and [THMT]
respectively or binary input signals THMA_BLOCK and THM_BLOCK.
& THM_ALARM
+
"ON"
[THMAL]
+
"ON"
[THMT]
THM_TRIP &
&
&
T
A
THM
1
THMA_BLOCK 1615
1
THM_BLOCK
1631
560
556
690
691
Figure 2.4.6.2 Thermal Overload Protection Scheme Logic
Setting
The table below shows the setting elements necessary for the thermal overload protection and their
setting ranges.
100
50
20
10
5
2
1
100
50
20
10
5
2
1
83
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
THM 2.0 10.0 A
(0.40 2.00 A)(*)
0.1 A
(0.01 A)
5.0 A
(1.00 A)
Thermal overload setting.
(THM = IAOL: allowable overload current)
THMIP 0.0 5.0 A
(0.00 1.00 A)(*)
0.1 A
(0.01 A)
0.0 A
(0.00 A)
Previous load current for testing
TTHM 0.5 - 300.0 min 0.1 min 10.0 min Thermal time constant
THMA 50 99 % 1 % 80 % Thermal alarm setting. (Percentage of THM setting.)
[THMT] Off / On Off Thermal OL enable
[THMAL] Off / On Off Thermal alarm enable
(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current
values are in the case of a 5 A rating.
Note: THMIP sets a minimum level of previous load current to be used by the thermal
element, and is only active when testing ([THMRST] = ON).
84
6 F 2 S 0 8 5 1
2.4.7 Switch-Onto-Fault Protection
In order to quickly remove a fault which may occur when a faulted line or busbar is energized, the
switch-onto-fault (SOTF) protection functions for a certain period after the circuit breaker is
closed.
The SOTF protection is performed by a non-directional overcurrent element and distance
measuring elements. The overcurrent protection is effective in detecting close-up three-phase
faults on the line in particular when the voltage transformer is installed on the line side. This is
because the voltage input to the distance measuring elements is absent continuously before and
after the fault, and thus it is difficult for the distance measuring elements to detect the fault.
The distance measuring elements can operate for faults other than close-up three-phase faults. One
of the zone 1 to zone ND elements can be used for the SOTF protection.
Scheme logic
The scheme logic for the SOTF protection is shown in Figure 2.4.7.1. The SOTF protection issues
a three-phase tripping signal M-TRIP for the operation of an overcurrent element OCH or distance
measuring elements Z1 to ZND for 500 ms after the circuit breaker is closed (CB-OR = 1) and/or
for 500ms after the undervoltage dead line detector resets. The method of controlling the SOTF
protection by CB closing and/or by undervoltage dead line detection is selected by scheme switch
[SOTF-DL]. Elements UVFS and UVLG provide undervoltage dead line detection.
Tripping by each element can be disabled by the scheme switches [SOTF-OC] to [SOTF-ZND].
When a VT failure is detected (NON VTF = 0), tripping by the distance measuring elements is
blocked.
1
&
& 1
1
0.5s
0 t
SOTF-TRIP
[SOTF-Z1]
[SOTF-OC]
NON VTF
CB-OR
OCH
Z1
"ON"
"ON"
Z2
"ON"
Z3
"ON"
0 - 300s
t 0
TSOTF
UVLS
1
0 - 300s
t 0
TSOTF
"UV",
"Both"
"CB",
"Both"
[SOTF-DL]
[SOTF-Z2]
[SOTF-Z3]
[SOTF-F]
ZF
"ON"
ZR1
"ON"
ZR2
"ON"
ZND
"ON"
[SOTF-R1]
[SOTF-R2]
[SOTF-ND]
&
55: OCH-A
56: OCH-B
57: OCH-C
UVLG
78:UVLG-A
79:UVLG-B
80:UVLG-C
72:UVLS-AB
73:UVLS-BC
74:UVLS-CA
&
SOTF_BLOCK 1623 1
183
Figure 2.4.7.1 SOTF Scheme Logic
Setting
The setting elements necessary for the SOTF protection and their setting ranges are as follows:
Element Range Step Default Remarks
OCH 2.0 - 15.0 A 0.1 A 6.0 A Overcurrent setting
( 0.4 - 3.0 A 0.1 A 1.2 A) (*)
TSOTF 0 300 s 1 s 5 s SOTF check timer
85
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
SOTF - OC OFF/ON ON Overcurrent tripping
SOTF - Z1 OFF/ON OFF Zone 1 tripping
SOTF - Z2 OFF/ON OFF Zone 2 tripping
SOTF - Z2 OFF/ON OFF Zone 3 tripping
SOTF - ZF OFF/ON OFF Zone F tripping
SOTF - ZR1 OFF/ON OFF Zone R1 tripping
SOTF - ZR2 OFF/ON OFF Zone R2 tripping
SOTF - ZND OFF/ON OFF Zone ND tripping
SOTF-DL CB/UV/BOTH CB SOTF control
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The OCH element and its setting are common with the stub protection.
2.4.8 Stub Protection
In the case of a busbar with a one-and-a-half breaker arrangement, the VT is generally installed on
the line side. If the line is separated from the busbar, the distance protection does not cover to the
"stub" area between the two CTs and line isolator. This is because the line VT cannot supply a
correct voltage for a fault in the "stub" area. For a fault in the stub area under such conditions, fast
overcurrent protection is applied.
Scheme logic
The scheme logic for the stub protection is shown in Figure 2.4.8.1. The stub protection performs
three-phase tripping on the condition that the line disconnector is open (DS_N/O_CONT = 0) and
the overcurrent element has operated (OCH = 1). CB condition (STUB_CB) can be added by
using programmable BI function (PLC function). Tripping can be disabled by the scheme switch
[STUB].
OCH
[STUB]
STUB_TRIP
(M-TRIP)
"ON"
&
1
1
182
DS_N/O_CONT 1542
STUB_CB 1649
STUB_BLOCK 1622
55: OCH-A
56: OCH-B
57: OCH-C
Figure 2.4.8.1 Stub Protection Scheme Logic
Setting
The setting elements necessary for the stub protection and their setting ranges are as follows:
Element Range Step Default Remarks
OCH 2.0 - 10.0 A 0.1 A 6.0 A Overcurrent setting
(0.4 - 2.0 A 0.1 A 1.2 A) (*)
STUB OFF/ON OFF Stub protection
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The OCH element and its setting are common with the SOTF protection.
86
6 F 2 S 0 8 5 1
2.4.9 Overvoltage and Undervoltage Protection
2.4.9.1 Overvoltage Protection
GRZ100 provides four independent overvoltage elements with programmable
dropoff/pickup(DO/PU) ratio for phase-to-phase voltage input and phase voltage input. OVS1 and
OVS2 are used for phase-to-phase voltage input, and OVG1 and OVG2 for phase voltage input.
OVS1 and OVG1 are programmable for inverse time (IDMT) or definite time (DT) operation.
OVS2 and OVG2 have definite time characteristic only.
The OVS1 and OVG1 overvoltage protection elements have an IDMT characteristic defined by
equation (1):
( )
=
1
1
Vs
V
TMS t
(1)
where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = overvoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.4.9.1.
The OVS2 and OVG2 elements are used for definite time overvoltage protection.
Definite time reset
The definite time resetting characteristic is applied to the OVS1 and OVG1 elements when the
inverse time delay is used.
If definite time resetting is selected, and the delay period is set to instantaneous, then no
intentional delay is added. As soon as the energising voltage falls below the reset threshold, the
element returns to its reset condition.
If the delay period is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising voltage exceeds the setting for a transient period without causing tripping,
then resetting is delayed for a user-definable period. When the energising voltage falls below the
reset threshold, the integral state (the point towards operation that it has travelled) of the timing
function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
Overvoltage elements OVS1, OVS2, OVG1 and OVG2 have a programmable dropoff/pickup
(DO/PU) ratio.
87
6 F 2 S 0 8 5 1
Overvol tage Inverse Ti me
Curves
0.100
1.000
10.000
100.000
1000.000
1 1.5 2 2.5 3
Applied Volt age (x Vs)
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
e
c
s
)
TMS =1
TMS =2
TMS =5
TMS =10
Figure 2.4.9.1 IDMT Characteristic
Scheme Logic
Figures 2.4.9.2 and 2.4.9.4 show the scheme logic of the OVS1 and OVG1 overvoltage protection
with selective definite time or inverse time characteristic. The definite time protection is selected
by setting [OV1EN] to DT, and trip signal OV1_TRIP is given through the delayed pick-up
timer TO1. The inverse time protection is selected by setting [OV1EN] to IDMT, and trip
signal OV1_TRIP is given.
The OVS1 and OVG1 protections can be disabled by the scheme switch [OV1EN] or the PLC
signal OV1_BLOCK.
These protections are available to trip instantaneously by the PLC signal OV1_INST_TP except
for [OV1EN]=OFF setting.
Figures 2.4.9.3 and 2.4.9.5 show the scheme logic of the OVS2 and OVG2 protection with definite
time characteristic. The OV2 gives the PLC signal OV2_ALARM through delayed pick-up
timer TO2.
The OV2_ALARM can be blocked by incorporated scheme switch [OV2EN] and the PLC
signal OV2_BLOCK.
These protections are also available to alarm instantaneously by the PLC signal OV2_INST_TP.
88
6 F 2 S 0 8 5 1
1
1
1
OVS1_TRIP
1
0.00 - 300.00s
TOS1
t 0
t 0
t 0
&
&
&
&
&
&
AB
OVS1
BC
CA
OVS1-CA_TRIP
OVS1-AB_TRIP
OVS1-BC_TRIP &
&
&
1
1
OVS1_BLOCK 1856
OVS1_INST_TP 1808
436
437
438
949
950
951
952
"DT"
"IDMT"
[OVS1EN]
+
1
Figure 2.4.9.2 OVS1 Overvoltage Protection
1
1
1
OVS2_ALARM 1
0.00 - 300.00s
TOS2
t 0
t 0
t 0
&
&
&
&
&
&
AB
OVS2
BC
CA
OVS2-CA_ALM
OVS2-AB_ALM
OVS2-BC_ALM
1 OVS2_BLOCK 1857
OVS2_INST_TP 1809
439
440
441
953
954
955
956
+
"On"
[OVS2EN]
Figure 2.4.9.3 OVS2 Overvoltage Protection
1
1
1
OVG1_TRIP 1
0.00 - 300.00s
TOG1
t 0
t 0
t 0
&
&
&
&
&
&
A
OVG1
B
C
OVG1-C_TRIP
OVG1-A_TRIP
OVG1-B_TRIP &
&
&
1
1
OVG1_BLOCK 1860
OVG1_INST_TP 1812
442
443
444
957
958
959
960
"DT"
"IDMT"
[OVG1EN]
+
1
Figure 2.4.9.4 OVG1 Overvoltage Protection
1
1
1
OVG2_ALARM 1
0.00 - 300.00s
TOG2
t 0
t 0
t 0
&
&
&
&
&
&
A
OVG2
B
C
OVG2-C_ALM
OVG2-A_ALM
OVG2-B_ALM
1 OVG2_BLOCK 1861
OVG2_INST_TP 1813
445
446
447
961
962
963
964
+
"On"
[OVG2EN]
Figure 2.4.9.5 OVG2 Overvoltage Protection
89
6 F 2 S 0 8 5 1
Setting
The table shows the setting elements necessary for the overvoltage protection and their setting
ranges.
Element Range Step Default Remarks
OVS1 5.0 150.0 V 0.1 V 120.0 V OVS1 threshold setting
TOS1I 0.05 100.00 0.01 10.00 OVS1 time multiplier setting. Required if [OVS1EN] = IDMT.
TOS1 0.00 300.00 s 0.01 s 0.10 s OVS1 definite time setting. Required if [OVS1EN] = DT.
TOS1R 0.0 300.0 s 0.1 s 0.0 s OVS1 definite time delayed reset.
OS1DP 10 98 % 1 % 95 % OVS1 DO/PU ratio setting.
OVS2 5.0 150.0 V 0.1 V 140.0 V OVS2 threshold setting.
TOS2 0.00 300.00 s 0.01 s 0.10 s OVS2 definite time setting.
OS2DP 10 - 98 % 1 % 95 % OVS2 DO/PU ratio setting.
OVG1 5.0 150.0 V 0.1V 70.0 V OVG1 threshold setting.
TOG1I 0.05 100.00 0.01 10.00 OVG1 time multiplier setting. Required if [OVG1EN]=IDMT.
TOG1 0.00 300.00 s 0.01 s 0.10 s OVG1 definite time setting. Required if [OVG1EN]=DT.
TOG1R 0.0 300.0 s 0.1 s 0.0 s OVG1 definite time delayed reset.
OG1DP 10 98 % 1 % 95 % OVG1 DO/PU ratio
OVG2 5.0 150.0 V 0.1V 80.0 V OVG2 threshold setting.
TOG2 0.00 300.00 s 0.01 s 0.10 s OVG2 definite time setting
OG2DP 10 98 % 1 % 95 % OVG2 DO/PU ratio
[OVS1EN] Off / DT / IDMT Off OVS1 Enable
[OVS2EN] Off / On Off OVS2 Enable
[OVG1EN] Off / DT / IDMT Off OVG1 Enable
[OVG2EN] Off / On Off OVG2 Enable
2.4.9.2 Undervoltage Protection
GRZ100 provides four independent undervoltage elements for phase and earth fault protection.
UVS1 and UVS2 are used for phase fault protection, and UVG1 and UVG2 for earth fault
protection. UVS1 and UVG1 are programmable for inverse time (IDMT) or definite time (DT)
operation. UVS2 and UVG2 have definite time characteristic only.
The UVS1 and UVG1 undervoltage protection elements have an IDMT characteristic defined by
equation (2):
( )
=
Vs
V
TMS t
1
1
(2)
where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = undervoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.4.9.6.
The UVS2 and UVG2 elements are used for definite time undervoltage protection.
90
6 F 2 S 0 8 5 1
Definite time reset
The definite time resetting characteristic is applied to the UVS1 and UVG1 elements when the
inverse time delay is used.
If definite time resetting is selected, and the delay period is set to instantaneous, then no
intentional delay is added. As soon as the energising voltage rises above the reset threshold, the
element returns to its reset condition.
If the delay period is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising voltage is below the undercurrent setting for a transient period without
causing tripping, then resetting is delayed for a user-definable period. When the energising
voltage rises above the reset threshold, the integral state (the point towards operation that it has
travelled) of the timing function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
Undervoltage Inverse Time
Curves
1.000
10.000
100.000
1000.000
0 0.2 0.4 0.6 0.8 1
Applied Voltage (x Vs)
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
e
c
s
)
TMS =10
TMS =5
TMS =2
TMS =1
Figure 2.4.9.6 IDMT Characteristic
Scheme Logic
Figures 2.4.9.7 and 2.4.9.9 show the scheme logic of the UVS1 and UVG1 undervoltage
protection with selective definite time or inverse time characteristic. The definite time protection
is selected by setting [UV1EN] to DT, and trip signal UV1 TRIP is given through the delayed
pick-up timer TU1. The inverse time protection is selected by setting [UV1EN] to IDMT, and
trip signal UV1_TRIP is given.
The UVS1 and UVG1 protections can be disabled by the scheme switch [UV1EN] or the PLC
signal UV1_BLOCK.
These protections are available to trip instantaneously by the PLC signal UV1_INST_TP except
for [UV1EN]=OFF setting.
Figures 2.4.9.8 and 2.4.9.10 show the scheme logic of the UVS2 and UVG2 protection with
definite time characteristic. The UV2 gives the PLC signal UV2_ALARM through delayed
91
6 F 2 S 0 8 5 1
pick-up timer TU2.
The UV2_ALARM can be blocked by incorporated scheme switch [UV2EN] and the PLC
signal UV2_BLOCK.
These protections are also available to alarm instantaneously by the PLC signal UV2_INST_TP.
In addition, there is user programmable voltage threshold UVSBLK and UVGBLK. If all three
phase voltages drop below this setting, then both UV1 and UV2 are prevented from operating.
This function can be blocked by the scheme switch [VBLKEN]. The [VBLKEN] should be set to
OFF (not used) when the UV elements are used as fault detectors, and set to ON (used) when
used for load shedding.
Note: The UVSBLK and UVGBLK must be set lower than any other UV setting values.
1
1
1
UVS1_TRIP 1
1
0.00 - 300.00s
TUS1
t 0
t 0
t 0
&
&
&
&
&
&
&
&
&
NON
UVSBLK
&
"ON"
[VBLKEN]
+
"OFF"
[UVTST]
+
UVSBLK
1
UVS1-CA_TRIP
UVS1-BC_TRIP
UVS1-AB_TRIP
AB
UVS1
BC
CA
UVS1_BLOCK 1864
UVS1_INST_TP 1816
454
455
456
965
966
967
968
"DT"
"IDMT"
[UVS1EN]
+
1
1
Figure 2.4.9.7 UVS1 Undervoltage Protection
+
"ON"
[UVS2EN]
0.00 - 300.00s
&
&
&
TUS2
t 0
t 0
t 0
AB
UVS2
BC
CA
UVS2_ALARM 1
UVS2-CA_ALM
UVS2-AB_ALM
UVS2-BC_ALM
&
&
&
NON UVSBLK
1
1
1
&
&
&
1 UVS2_BLOCK 1865
UVS2_INST_TP 1817
969
970
971
972
457
458
459
Figure 2.4.9.8 UVS2 Undervoltage Protection
Figure 2.4.9.9 UVG1 Undervoltage Protection
1
1
1
UVG1 TRI
1
1
0.00 - 300.00s
TUG1
t 0
t 0
t 0
&
&
&
&
&
&
&
&
&
NON
U GBL
&
"ON"
[VBLKEN]
+
"OFF"
[UVTST]
+
UVGBLK
1
UVG -CA TRI
UVG -BC TRI
UVG -AB TRI
A
UVG1
B
C
UVG1
_
BLOC
K
1868
UVG1_INST_TP 1820
460
461
462
973
974
975
976
"DT"
[IDMT]
[UVG1EN]
+
1
1
92
6 F 2 S 0 8 5 1
+
"ON"
[UVG2EN]
0.00 - 300.00s
&
&
&
TUG2
t 0
t 0
t 0
A
UVG2
B
C
UVG2_ALARM 1
UVG2-C_ALM
UVG2-A_ALM
UVG2-B_ALM
&
&
&
NON UVGBLK
1
1
1
&
&
&
1 UVG2_BLOCK 1869
UVG2_INST_TP 1821
977
978
979
980
463
464
465
Figure 2.4.9.10 UVG2 Undervoltage Protection
Setting
The table shows the setting elements necessary for the undervoltage protection and their setting
ranges.
Element Range Step Default Remarks
UVS1 5.0 150.0 V 0.1 V 60.0 V UVS1 threshold setting
TUS1I 0.05 100.00 0.01 10.00 UVS1 time multiplier setting. Required if [UVS1EN] = IDMT.
TUS1 0.00 300.00 s 0.01 s 0.10 s UVS1 definite time setting. Required if [UVS1EN] = DT.
TUS1R 0.0 300.0 s 0.1 s 0.0 s UVS1 definite time delayed reset.
UVS2 5.0 150.0 V 0.1 V 40.0 V UVS2 threshold setting.
TUS2 0.00 300.00 s 0.01 s 0.10 s UVS2 definite time setting.
VSBLK 5.0 20.0 V 0.1 V 10.0 V Undervoltage block threshold setting.
UVG1 5.0 150.0 V 0.1 V 35.0 V UVG1 threshold setting
TUG1I 0.05 100.00 0.01 10.00 UVG1 time multiplier setting. Required if [UVG1EN] = IDMT.
TUG1 0.00 300.00 s 0.01 s 0.10 s UVG1 definite time setting. Required if [UVG1EN] = DT.
TUG1R 0.0 300.0 s 0.1 s 0.0 s UVG1 definite time delayed reset.
UVG2 5.0 150.0 V 0.1 V 25.0 V UVG2 threshold setting.
TUG2 0.00 300.00 s 0.01 s 0.10 s UVG2 definite time setting.
VGBLK 5.0 20.0 V 0.1 V 10.0 V Undervoltage block threshold setting.
[UVS1EN] Off / DT / IDMT Off UVS1 Enable
[UVG1EN] Off / DT / IDMT Off UVG1 Enable
[UVS2EN] Off / On Off UVS2 Enable
[UVG2EN] Off / On Off UVG2 Enable
[VBLKEN] Off / On Off UV block Enable
93
6 F 2 S 0 8 5 1
2.4.10 Broken Conductor Protection
Series faults or open circuit faults which do not accompany any earth faults or phase faults are
caused by broken conductors, breaker contact failure, operation of fuses, or false operation of
single-phase switchgear.
Figure 2.4.10.1 shows the sequence network connection diagram in the case of a single-phase
series fault assuming that the positive, negative and zero sequence impedance of the left and right
side system of the fault location is in the ratio of k
1
to (1 k
1
), k
2
to (1 k
2
) and k
0
to (1 k
0
).
Figure 2.4.10.1 Equivalent Circuit for a Single-phase Series Fault
Positive phase sequence
Single-phase series fault
Zero phase sequence
k
2
Z
2
(1-k
2
)Z
2
k
0
Z
0
(1-k
0
)Z
0
E
1A
E
1B
I
1F
I
1F
I
2F
I
2F
I
0F
I
0F
Negative phase sequence
(1-k
1
)Z
1
k
1
Z
1
E
1B
E
1A
k
1
1 k
1
E
1A
E
1B
I
1F
I
1F
(1-k
1
)Z
1
k
1
Z
1
k
2
Z
2
(1-k
2
)Z
2
K
0
Z
0
(1-k
0
)Z
0
E
1A
E
1B
I
1F
Z
1
Z
2
Z
0
94
6 F 2 S 0 8 5 1
Positive phase sequence current I
1F
, negative phase sequence current I
2F
and zero phase sequence
current I
0F
at fault location in a single-phase series fault are given by:
I
1F
+ I
2F
+ I
0F
=0 (1)
Z
2F
I
2F
Z
0F
I
0F
= 0 (2)
E
1A
E
1B
= Z
1F
I
1F
Z
2F
I
2F
(3)
where,
E
1A
, E
1B
: power source voltage
Z
1
: positive sequence impedance
Z
2
: negative sequence impedance
Z
0
: zero sequence impedance
From the equations (1), (2) and (3), the following equations are derived.
I
1F
=
Z
2
+ Z
0
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
(E
1A
E
1B
)
I
2F
=
Z
0
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
(E
1A
E
1B
)
I
0F
=
Z
2
Z
1
Z
2
+ Z
1
Z
0
+ Z
2
Z
0
(E
1A
E
1B
)
The magnitude of the fault current depends on the overall system impedance, difference in phase
angle and magnitude between the power source voltages behind both ends.
Broken conductor protection element BCD detects series faults by measuring the ratio of negative
to positive phase sequence currents (I
2F
/ I
1F
). This ratio is given with negative and zero sequence
impedance of the system:
I
2F
I
1F
=
|I
2F
|
|I
1F
|
=
Z
0
Z
2
+ Z
0
The ratio is higher than 0.5 in a system when the zero sequence impedance is larger than the
negative sequence impedance. It will approach 1.0 in a high-impedance earthed or a one-end
earthed system.
The characteristic of BCD element is shown in Figure 2.4.10.2 to obtain the stable operation.
I1
I2
0
0.01In
0.04In
|I2|/|I1| BCD
setting
|I1| 0.04In
& BCD
|I2| 0.01In
In: rated current
Figure 2.4.10.2 BCD Element Characteristic
95
6 F 2 S 0 8 5 1
Scheme Logic
Figure 2.4.10.3 shows the scheme logic of the broken conductor protection. BCD element outputs
trip signals BCD TRIP through a delayed pick-up timer TBCD.
The tripping can be disabled by the scheme switch [BCDEN] or the PLC signal BCD BLOCK.
BCD
BCD_TRIP
0.00 - 300.00s
&
TBCD
t 0
"ON"
[BCDEN]
+
1
BCD_BLOCK 1848
766
767
Figure 2.4.10.3 Broken Conductor Protection Scheme Logic
Settings
The table below shows the setting elements necessary for the broken conductor protection and
their setting ranges.
Element Range Step Default Remarks
BCD 0.10 1.00 0.01 0.20 I2 / I1
TBCD 0.00 300.00s 0.01s 1.00 s BCD definite time setting
[BCDEN] Off / On Off BCD Enable
Minimum setting of the BC threshold is restricted by the negative phase sequence current
normally present on the system. The ratio I
2
/ I
1
of the system is measured in the relay continuously
and displayed on the metering screen of the relay front panel, along with the maximum value of
the last 15 minutes I
21
max. It is recommended to check the display at the commissioning stage.
The BCD setting should be 130 to 150% of I
2
/ I
1
displayed.
Note: It must be noted that I
2
/ I
1
is displayed only when the positive phase sequence current
(or load current ) in the secondary circuit is larger than 2 % of the rated secondary circuit
current.
TBCD should be set to more than 1 cycle to prevent unwanted operation caused by a transient
operation such as CB closing.
96
6 F 2 S 0 8 5 1
2.4.11 Breaker Failure Protection
When fault clearance fails due to a breaker failure, the breaker failure protection (BFP) clears the
fault by backtripping adjacent circuit breakers.
If the current continues to flow even after a trip command is output, the BFP judges it as a breaker
failure. The existence of the current is detected by an overcurrent element provided for each phase.
For high-speed operation of the BFP, a high-speed reset overcurrent element is used.
In order to prevent the BFP from starting by accident during maintenance work and testing, and
thus tripping adjacent breakers, the BFP has the optional function of retripping the original
breaker. To make sure that the breaker has actually failed, a trip command is made to the original
breaker again before tripping the adjacent breakers to prevent unnecessary tripping of the adjacent
breakers following the erroneous start-up of the BFP. It is possible to choose not to use retripping
at all, or use retripping with trip command plus delayed pick-up timer, or retripping with trip
command plus overcurrent detection plus delayed pick-up timer.
Tripping by the BFP is three-phase final tripping and autoreclose is blocked.
An overcurrent element and delayed pick-up timer are provided for each phase which also operate
correctly during the breaker failure routine in the event of an evolving fault.
Scheme logic
The BFP is performed on an individual phase basis. Figure 2.4.11.1 shows the scheme logic for
one phase. The BFP is started by an initiation signal EXT_CBFIN from the external line
protection or an internal initiation signal CBF_INIT. The external initiation signals
EXT_CBFIN-A, -B, -C are assigned by binary input signals (PLC signals). Starting with an
external initiation signal can be disabled by the scheme switch [BFEXT]. These signals must
continuously exist as long as the fault is present.
&
& 1
50 - 500ms
t 0
TBF1
t 0
692:CBF_RETRIP
[BF1]
[BF1]
[BF2]
"ON"
"ON"
[BFEXT]
"T"
"TOC"
(Trip adjacent breakers)
(Trip original breaker)
CBF INIT-A, -B, -C
200:CBF_TRIP
OCBF
81:OCBF-A
82:OCBF-B
83:OCBF-C
EXT_CBFIN-A 1560
EXT_CBFIN-B 1561
EXT_CBFIN-C 1562
693:CBF_TRIP-A
694:CBF_TRIP-B
695:CBF_TRIP-C
196:CBF_RETRIP-A
197:CBF_RETRIP-B
198:CBF_RETRIP-C
50 - 500ms
TBF2
t 0
CBF_BLOCK 1640 1
&
Figure 2.4.11.1 BFP Scheme Logic
The backtripping signal to the adjacent breakers BF-TRIP is output if the overcurrent element
OCBF operates continuously for the setting time of the delayed pick-up timer TBF2 after
initiation. Tripping of adjacent breakers can be blocked with the scheme switch [BF2].
There are two kinds of modes of the retrip signal to the original breaker RETRIP, the mode in
which RETRIP is controlled by the overcurrent element OCBF, and the direct trip mode in which
RETRIP is not controlled. The retrip mode together with the trip block can be selected with the
scheme switch [BF1].
Figure 2.4.11.2 shows a sequence diagram for the BFP when a retrip and backup trip are used. If
the circuit breaker trips normally, the OCBF is reset before timer TBF1 or TBF2 is picked up and
the BFP is reset.
97
6 F 2 S 0 8 5 1
If the OCBF continues to operate, a retrip command is given to the original breaker after the
setting time of TBF1. Unless the breaker fails, the OCBF is reset by retrip. TBF2 does not time-out
and the BFP is reset. This sequence of events may happen if the BFP is initiated by mistake and
unnecessary tripping of the original breaker is unavoidable.
If the original breaker fails, retrip has no effect and the OCBF continues operating and the TBF2
finally picks up. A trip command BF-TRIP is given to the adjacent breakers and the BFP is
completed.
Figure 2.4.11.2 Sequence Diagram
Fault
CBF
TRIP
TBF2
RETRIP
TBF1
OCBF
Original
breakers
Adjacent
breakers
TRIP
Retrip
Toc Toc
Tcb T cb
TBF1
TBF2
Normal trip
Open Closed
Start BFP
Open Open Closed
Trip
98
6 F 2 S 0 8 5 1
Setting
The setting elements necessary for the breaker failure protection and their setting ranges are as
follows:
Element Range Step Default Remarks
OCBF 0.5 10.0 A 0.1 A 4.0 A Overcurrent setting
(0.1 - 2.0 A 0.1 A 0.8 A) (*)
TBF1 50 - 500 ms 1 ms 150 ms Retrip timer
TBF2 50 - 500 ms 1 ms 200 ms Related breaker trip timer
BFEXT OFF/ON OFF External start
BF1 OFF/T/TOC OFF Retrip mode
BF2 OFF/ON OFF Related breaker trip
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The overcurrent element OCBF checks that the circuit breaker has opened and that the current has
disappeared. Therefore, since it is allowed to respond to load current, it can be set to 10 to 200% of
the rated current.
The settings of TBF1 and TBF2 are determined by the opening time of the original circuit breaker
(Tcb in Figure 2.4.11.2) and the reset time of the overcurrent element (Toc in Figure 2.4.11.2).
The timer setting example when using retrip can be obtained as follows.
Setting of TBF1 = Breaker opening time + OCBF reset time + Margin
= 40ms + 10ms + 20ms
= 70ms
Setting of TBF2 = TBF1 + Output relay operating time + Breaker opening time +
OCBF reset time + Margin
= 70ms + 10ms + 40ms + 10ms + 10ms
= 140ms
If retrip is not used, the setting of the TBF2 can be the same as the setting of the TBF1.
Overcurrent detector OCBF
This detector measures A, B, and C phase currents and its sensitivity can be set. This detector is
used for breaker failure protection and resets when the current falls below 80% of the operating
value.
99
6 F 2 S 0 8 5 1
2.4.12 Out-of-Step Protection
Application
For an out-of-step condition on a power system, power system separation is executed in order to
recover power system stability or prevent the failure from extending to the entire system. Power
system separation by the distance protection with several operating zones is not desirable because
it is not always carried out at the optimal points. For optimal power system separation, the
GRZ100 has an out-of-step tripping (OST) function. The OST function uses independent
impedance measuring elements to discriminate against transient power swings and reliably detects
out-of-steps and operates only when the out-of-step locus crosses the protected line.
Scheme logic
The out-of-step element has three operating areas A, B and C by combining two impedance
measuring elements ZM and ZN as shown in Figure 2.4.12.1.
If an out-of-step occurs, the impedance viewed from the impedance measuring element moves
through the areas A, B and C in the sequence of A B C or C B A. The out-of-step
tripping logic shown in Figure 2.4.12.2 outputs a three-phase tripping command M-TRIP to the
circuit breaker when the impedance viewed from the impedance measuring element passes
through those areas in the sequence above and enters the third area and it stays in area A and area
C for the time set with the timers TOST1 and TOST2. The tripping command continues for 100
ms. The output signal is blocked when the scheme switch [OST] is set to "OFF" or binary signal
OST_BLOCK is input. The tripping signal of the out-of-step protection can be separated from
other protection tripping signals by the switch [OST]. In this case, the switch [OST] is set to "BO"
and the tripping signal OST-BO is assigned to a desired binary output number (for details, see
Section 4.2.6.9). When the tripping signal of the out-of-step protection is not separated from other
protection tripping signals, the switch [OST] is set to "TRIP".
The tripping logic does not operate for cases other than out-of-steps, for example, a power swing
in which the impedance moves from areas A B A or C B C or a system fault in which
the impedance passes through area A or C instantaneously.
Out-of-step tripping can be disabled with the scheme switch [OST].
R
75
X
ZN C B A ZM
OSTR1 OSTR2
OSTXB
OSTXF
Figure 2.4.12.1 Out-of-Step Element
100
6 F 2 S 0 8 5 1
[OST]
OST_TRIP
(M-TRIP)
"BO"
0.01 - 1.0s
+
TOST1
OST
OST-ZN
OST-ZM
1
1
&
100ms
t 0
0.01 - 1.0s
TOST2
1
1
&
0 t
&
&
&
&
t 0
&
1
84
85
&
"TRIP"
&
OST_BO
203
337
1 OST_BLOCK 1630
Figure 2.4.12.2 Out-of-Step Tripping Logic
Setting
The setting elements for the out-of-step protection and their setting ranges are as follows:
Element Range Step Default Remarks
OSTXF 1.0 - 50.0 0.1 6.0 Forward reactive reach
( 5 - 250 1 30) (*)
OSTXB O.2 - 10.0 0.1 1.0 Reverse offset reach
( 1 - 50 1 5)
OSTR1 3.0 - 30.0 0.1 5.1 Resistive reach (right)
( 15 - 150 1 25)
OSTR2 1.0 - 10.0 0.1 2.5 Resistive reach (left)
( 5 - 50 1 12)
TOST1 0.01 - 1.00 s 0.01 s 0.04 s Out - of - step timer
TOST2 0.01 - 1.00 s 0.01 s 0.04 s Out - of - step timer
OST OFF/TRIP/BO OFF Out - of - step protection
(*) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are in the
case of 5 A rating.
Characteristics of Out-of-Step Element OST
The out-of-step element used for out-of-step tripping contains two impedance measuring elements
with quadrilateral characteristics, ZM and ZN. Figure 2.4.12.3 shows their characteristics. The
quadrilateral characteristic of ZM is formed by the reactance lines parallel to the R-axis and the
ohm lines with a leading angle of 75 to the R-axis.
The characteristics of ZN can be obtained by shifting ZM in the R-axis direction by
(OSTR1-OSTR2).
101
6 F 2 S 0 8 5 1
R
75
X
ZN C B A ZM
OSTR1 OSTR2
OSTXB
OSTXF
Figure 2.4.12.3 Out-of-Step Element
Operation of the impedance measuring element Z1 is expressed by the following equations.
OSTXB X OSTXF
(R OSTR1)tan75 X (R OSTR2)tan75
where,
X = measured reactance
R = measured resistance
OSTXB, OSTXF = reactive reach setting
OSTR1, OSTR2 = resistive reach setting
102
6 F 2 S 0 8 5 1
2.4.13 Voltage Transformer Failure Supervision
When a fault occurs in the secondary circuit of the voltage transformer (VT), the voltage
dependent measuring elements may operate incorrectly. GRZ100 incorporates a VT failure
supervision function (VTFS) as a measure against such incorrect operation. When the VTFS
detects a VT failure, it blocks the following voltage dependent protections instantaneously. In 10
seconds, it displays the VT failure and outputs an alarm.
Zone 1-3, F, R1, R2 and ND distance protection
Zone 1 extension protection
Directional earth fault protection
Command protection
Resetting of the blocks above and resetting of the display and alarm are automatically performed
when it is confirmed that all three phases are healthy.
A binary input signal to indicate a miniature circuit breaker trip in the VT circuits is also available
for the VTFS.
Scheme logic
Figure 2.4.13.1 shows the scheme logic for the VTFS. VT failures are detected under any one of
the following conditions and then a trip block signal VTF is output.
VTF1: The phase-to-phase undervoltage element UVFS or phase-to-earth undervoltage
element UVFG operates (UVFS = 1 or UVFG =1) when the three phases of the circuit
breaker are closed (CB-AND = 1) and the phase current change detection element
OCD does not operate (OCD = 0).
VTF2: The residual overcurrent element EFL does not operate (EFL = 0), the residual
overvoltage element OVG operates (OVG = 1) and the phase current change detection
element OCD does not operate (OCD = 0).
In order to prevent detection of false VT failures due to unequal pole closing of the circuit breaker,
the VTFS is blocked for 200 ms after line energisation.
The trip block signal VTF is reset 100 milliseconds after the VT failure condition has reset. When
the VTF continues for 10s or more, an alarm signal VTF-ALM is output.
Further, the VT failure is detected when the binary input signal (PLC signal) EXT_VTF is
received.
This function can be enabled or disabled by the scheme switch [VTF1EN] or [VTF2EN] and has a
programmable reset characteristic. When set to ON, the latched operation for VTF1 is reset by
reset of UVFS/UVFG element, and that for VTF2 is reset by reset of OVG element. Set to
OPT-ON to reset the latched operation when OCD or EFL operates.
The VTFS can be disabled by the PLC signal VTF_BLOCK.
103
6 F 2 S 0 8 5 1
1
&
&
0.2s
VTF2_ALARM
VTF2
1
100ms
0 t
CB-AND
UVFS
UVFG
OCD
OVG
EFL
1
1
10s
t 0
1
[VTF1EN]
"ON", OPT-ON
+
[VTF2EN]
"ON", OPT-ON
+
1
VTF1_ALARM
VTF1
100ms
0 t
10s
t 0
62
568
142:UVFSOR
140:UVFGOR
63:OCD-A
64 OCD-B
65:OCD-C
VTF_BLOCK 1642 1
EXT_VTF 1541
1
VTF_ONLY_ALM
1643
1
& 1
175
173:VTF
NON VTF
VTF_ALARM
172
174
1
Figure 2.4.13.1 VTFS Logic
Setting
The setting elements necessary for the VTFS and their setting ranges are as follows:
Element Range Step Default Remarks
UVFS 50 - 100 V 1 V 88 V Phase - to - phase undervoltage
UVFG 10 - 60 V 1 V 51 V Phase - to - earth undervoltage
EFL 0.5 - 5.0 A 0.1 A 1.0 A Residual overcurrent
( 0.10 - 1.00 A 0.01 A 0.20 A) (*)
[VTF1EN] Off/On/OPT-On On VTF1 supervision
[VTF2EN] Off/On/OPT-On On VTF2 supervision
[VTF-Z4] Off / On On Z4 blocked by VTF
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The following elements have fixed setting values.
Element Setting Remarks
OCD Fixed to 0.5 A Current change detection
(Fixed to 0.1 A)
OVG Fixed to 20 V Residual overvoltage
(*) Current value shown in the parentheses is in the case of 1 A rating. Other current value is in the
case of 5 A rating.
When setting the UVFS, UVFG and EFL, the maximum detection sensitivity of each element
should be set with a margin of 15 to 20% taking account of variations in the system voltage, the
asymmetry of the primary system and CT and VT error.
104
6 F 2 S 0 8 5 1
2.4.14 Power Swing Blocking
When a power swing occurs on the power system, the impedance seen by the distance measuring
element moves away from the load impedance area into the operating zone of the distance
measuring element. The operation of the distance measuring element due to the power swing
occurs in many points of interconnected power systems. Therefore, tripping due to the operation
of the distance measuring element during a power swing is generally not allowed. The power
swing blocking function (PSB) of the GRZ100 detects the power swing and blocks tripping by the
distance measuring element. The GRZ100 provides PSBSZ and PSBGZ for phase fault measuring
elements and earth fault measuring elements. Their functions and characteristics are same.
Once the PSB is in operation, tripping of zone 1 to zone 3 of the time-stepped distance protection,
zone 1 extension protection, additional forward zone ZF, backup protection for reverse faults and
command protection using distance measuring elements can be blocked. These tripping blocks can
be disabled by setting the scheme switches.
Tripping of the non-directional zone ZND is not blocked. If a zero-phase current has been
detected, the PSB is inhibited. This allows tripping in the event of an earth fault during a power
swing or high resistance earth fault by which the resistance at the fault point changes gradually.
GRZ100 can provide a high-speed protection for one- and two-phase faults which occur during a
power swing by using negative sequence directional element and any of the command protection
PUP, POP, UOP and BOP.
Three-phase faults during a power swing are eliminated by distance and overcurrent backup
protection.
Scheme logic
A power swing is detected by using two PSB elements PSBIN and PSBOUT. They are composed
of blinder elements and reactance elements as shown in Figure 2.4.14.1. PSBOUT encloses
PSBIN with a settable width of PSBZ.
Figure 2.4.14.2 shows the power swing detection logic. During a power swing, the impedance
viewed from the PSB elements passes through the area between the PSBOUT and PSBIN in a
certain time. In the event of a system fault, the impedance passes through this area
instantaneously. Therefore, a power swing is detected in a time which commences on operation of
the PSBOUT until PSBIN starts to operate, if longer than the set value of delayed pick-up timer
TPSB. If the residual overcurrent element EFL operates, detection of the power swing is inhibited.
The trip block signal PSB generated as a result of the detection of a power swing is reset 500 ms
after the PSBOUT is reset by delayed timer T2.
PSBZ
PSBZ
PSBZ
0
PSBZ
PSBIN PSBOUT
R
X
Z3
Z4
ZR2
Figure 2.4.14.1 Power Swing Blocking Element
105
6 F 2 S 0 8 5 1
PSBSZ and PSBGZ have same functions and characteristics as shown in Figures 2.4.14.1 and
2.4.14.2, and block tripping of phase and earth fault elements respectively.
&
S Q
F/F
R
EFL
PSBSIN
PSBSOUT
PSBS_DET
TPSB
t 0
0.02 - 0.06s
&
T2
t 0
0.5s
323:PSBSIN-AB
324:PSBSIN-BC
325:PSBSIN-CA
49:PSBSOUT-AB
50:PSBSOUT-BC
51:PSNSOUT-CA
568
702
561:PSBGIN-A
562:PSBGIN-B
563:PSBGIN-C
565:PSBGOUT-A
566:PSBGOUT-B
567:PSNGOUT-C
&
S Q
F/F
R
PSBGIN
PSBGOUT
PSBG_DET
TPSB
t 0
0.02 - 0.06s
&
T2
t 0
0.5s
703
PSB_DET
176
PSB_BLOCK 1605
PSB_F.RESET 1651
1
1
1
1
Figure 2.4.14.2 Power Swing Detection Logic
One- and two-phase faults can be protected with the command protection even during a power
swing.
The PSB can be disabled or reset by the PLC signal PSB_BLOCK or PSB_F.RESET.
Figure 2.4.14.3 shows the scheme logic to control the sending signal of PUP, POP, UOP or BOP.
The scheme logic is valid when the scheme switch [PSB-TP] is set to "ON". CS1 is an original
sending signal for the distance and DEF command protection and CS2 is a controlled sending
signal. When a power swing is continuing (PSB_DET=1) and an internal fault is not detected
(PSB-CS=0), the sending signal of PUP or POP is forced to be 0 (that is, a trip permission signal
sending is blocked), and that of UOP or BOP is forced to be 1 (that is, a trip block signal is
continuously sent).
+
[PSB-TP]
"ON"
&
(POP) (PUP)
CS1
1
CS2
PSB_DET
&
&
(UOP) (BOP)
1
&
PSB-CS
225:EXT_CAR-S
Figure 2.4.14.3 Sending Signal Control
106
6 F 2 S 0 8 5 1
When an internal fault occurs during the power swing and all of the following conditions are
established, C/R SEND-PSB (PSB-CS) becomes 1 and the trip permission signal is sent for the
PUP or POP, and the trip block signal sending is stopped for the UOP or BOP as shown in Figure
2.4.14.4.
Power swing is continuing (PSB_DET=1).
Current change detection element operates (OCDP=1).
Reverse looking negative sequence directional element does not operate (DOCNR=0).
Forward looking negative sequence directional element operates (DOCNF=1).
Scheme switch PSB-TP is on.
Command protection is in service.
When a trip permission signal is received for the PUP or POP (CR=1), or no trip block signal is
received for the UOP or BOP (CR=0) as well as the conditions mentioned above are established
(PSB-CS=1), three-phase tripping signal is output (M-TRIP=1).
Reverse looking DOCNR is used for the current reversal logic (for current reversal logic, see
Section 2.4.3.6) in all the command protections.
(POP) (PUP)
1
CR-DEF
CR-DEF
M-TRIP
&
(UOP) (BOP)
DOCN-F
&
1 20ms 100ms
0 t 0 t
OCDP
PSB DET
+
[PSB-TP]
"ON"
DOCN-R
& PSB-CS
357:OCDP-A
358:OCDP-B
359:OCDP-C
361
360
Figure 2.4.14.4 Scheme Logic to Protect Faults during Power Swing
Setting
The setting elements necessary for the PSB and their setting ranges are as shown in the table
below.
Element Range Step Default Remarks
PSBSZ 0.50 - 15.00 0.01 2.00 PSBS detection zone
( 2.5 - 75.0 0.1 10.0) (*)
PSBGZ 0.50 - 15.00 0.01 2.00 PSBG detection zone
( 2.5 - 75.0 0.1 10.0) (*)
EFL 0.5 - 5.0 A 0.1 A 1.0 A Residual overcurrent
( 0.10 - 1.00 A 0.01 A 0.20 A)
TPSB 20 - 60 1 ms 40 ms Power swing timer
OCDP 0.5 10.0 A 0.1A 4.0 A Current change
( 0.1 2.0 A 0.1 A 0.8 A) detection element
DOCNF 4.0 A fixed Forward looking negative
107
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
( 0.8A fixed) sequence directional element
6 V fixed
DOCNR 4.0 A fixed Reverse looking negative
( 0.8A fixed) sequence directional element
6 V fixed
PSB-Z1 OFF/ON ON Z1 blocked under power swing
PSB-Z1X OFF/ON ON Z1X blocked under power swing
PSB-Z2 OFF/ON ON Z2 blocked under power swing
PSB-Z3 OFF/ON OFF Z3 blocked under power swing
PSB-CR OFF/ON ON Carrier trip blocked under power swing
PSB-ZF OFF/ON OFF ZF blocked under power swing
PSB-ZR1 OFF/ON OFF ZR1 blocked under power swing
PSB-ZR2 OFF/ON OFF ZR2 blocked under power swing
PSB-TP OFF/ON ON Command protection for faults under power swing
(*) Values shown in the parentheses are in the case of 1A rating. Other values are in the case of 5A
rating.
Residual overcurrent element EFL is used in common with the following functions.
VT failure detection
Earth fault distance protection
The PSBIN reach is set automatically to coordinate with the Z3 and Z4 settings.
Note: In the case of the quadrilateral characteristic, if the ZF and ZR2 reach is larger than the Z3 and
Z4 respectively, the PSBIN reach depends on the ZF and ZR2 reach. Therefore, the ZF and
ZR2 must be set less than the Z3 and Z4 respectively whether the ZF and ZR2 used or not.
The right side forward and reverse blinders for PSBIN are shared with the right side forward and
reverse blinders of the distance protection characteristic, BFRS/BFRG and BRRS/BRRG
respectively, ensuring that the PSB element coordinates properly with the protection, for both mho
and quadrilateral characteristics.
The positive reactive reach setting is fixed so that the setting makes the reactance element
tangential to the Z3 distance element when the Z3 is mho-based or takes the same value as the Z3
reactive reach setting when the Z3 is quadrilateral-based.
The negative resistive reach takes the same value as that of the positive reach. The negative
reactive reach setting is fixed so that the setting makes the reactance element tangential to the Z4
distance element when the Z4 is mho-based or takes the same value as the Z4 reactive reach setting
when the Z4 is quadrilateral-based.
PSBOUT encloses PSBIN and the margin between the two is determined by the user-settable
power swing detection zone width, PSBSZ and PSBGZ, for phase and earth fault characteristics
respectively.
Characteristics of Current Change Detection Elements OCD and OCDP
As shown in Figure 2.4.14.5, the current change detection element operates if the vectorial
difference between currents I
M
and I
N
observed one cycle apart is larger than the fixed setting.
Therefore, the operating sensitivity of this element is not affected by the quiescent load current
and can detect a fault current with high sensitivity.
The operation decision is made by the following equation.
|I
M
I
N
| > Is
where,
108
6 F 2 S 0 8 5 1
I
M
= present current
I
N
= current one cycle before
I
s
= fixed setting (10% of rated current)
Figure 2.4.14.5 Current Change Detection
Characteristic of Negative Sequence Directional Elements DOCNF and DOCNR
There are two types of negative sequence directional element, the forward looking element
(DOCNF) and reverse looking element (DOCNR). They are used to detect faults during a power
swing. Their characteristics are shown in Figure 2.4.14.6.
Both the DOCNF and DOCNR use negative sequence current and voltage and determine a fault
direction based on the phase relationship between the current and voltage.
The operation decision is made using the following equation.
DOCNF
Z
k
I
2
2
V
2
I
2
sin V
2k
|I
2
|
I
2
I
2k
DOCNR
Z
k
I
2
2
+ V
2
I
2
sin V
2k
|I
2
|
I
2
I
2k
where,
I
2
= negative sequence current
V
2
= negative sequence voltage
= lagging angle of I
2
to V
2
I
2k
= 0.267 rated current (fixed)
V
2k
= 6 V (fixed)
I
s
I
M
I
N
109
6 F 2 S 0 8 5 1
Z
k
= 2.5 ohm (1A rating, fixed) / 0.5 ohm (5A rating, fixed)
Figure 2.4.14. 6 Negative Sequence Directional Element
I
2
DOCN-F
0
DOCN-R
V
2k
Z
k
I
2
(V
2k
Z
k
I
2
)
110
6 F 2 S 0 8 5 1
2.4.15 Tripping Output Signals
The single-phase tripping signals drive the high-speed tripping output relays according to the
tripping logic in Figure 2.4.15.1.
Two sets of output relays are provided for each phase and each relay has one normally open
contact.
The tripping output relays reset 60ms(*) after the S-TRIP or M-TRIP signal disappears by clearing
the fault. The tripping circuit must be opened with a circuit breaker auxiliary contact prior to the
trip relay resetting in order to prevent the tripping relay from directly interrupting the circuit
breaker tripping coil current.
(*) Reset time is adjustable by PLC function. Default setting is 60ms.
In the following cases, per-phase-based tripping is converted to three-phase tripping.
When autoreclose is prohibited by a binary input signal (ARC_BLOCK = 1)
When the tripping mode selection switch [TPMODE] is set to "3PH".
When the autoreclose mode selection switch [ARC-M] is set to "EXT3P"
PLC command 3P_TRIP is established.
For the following trips, the logic level of M-TRIPA becomes 1, and single-phase tripping is then
forced to convert to three-phase tripping. For details of M-TRIPA, see Figure 2.5.2.1.
Tripping while reclaim is in progress.
Tripping when the reclose mode selection switch [ARC-M] is set to "Disabled" or "TPAR"
The signals TRIP-A, TRIP-B and TRIP-C are used to start the autoreclose.
The signal TRIP is used to initiate the breaker failure protection.
+
TRIP-A
TRIP-B
TRIP-C
1
1
1
M-TRIP
M-TRIPA
A-phase
trip
B-phase
trip
C-phase
trip
Tripping output
relay
TRIP
60ms
by PLC
0 t
S-TRIP
C
B
A
1
60ms
by PLC
0 t
60ms
by PLC
0 t
1
"EXT3P"
1
1
(See Figure 2.6.2.1)
3P_TRIP 1727
1
1
1
A-phase
trip
B-phase
trip
C-phase
trip
&
623
624
625
245
244
243
242
241
240
TP-A1
TP-B1
TP-C1
TP-A2
TP-B2
TP-C2
CBF_RETRIP-A
CBF_RETRIP-B
CBF_RETRIP-C
[AMC-M]
Figure 2.4.15.1 Tripping Logic
111
6 F 2 S 0 8 5 1
A tripping output relay is user configurable for the adjacent breakers tripping in the breaker failure
protection. For the default setting, see Appendix D.
If the signal No.1727 3P_TRIPassigned by PLC is activated, GRZ100 outputs a three-phase
tripping command without regard to faulted phase.
112
6 F 2 S 0 8 5 1
2.5 Autoreclose
2.5.1 Application
Most faults that occur on high voltage or extra-high voltage overhead lines are transient faults
caused by lightning. If a transient fault occurs, the circuit breaker is tripped to isolate the fault, and
then reclosed following a time delay to ensure that the gases caused by the fault arc have
de-ionized. This makes it possible to recover power transmission.
The time between clearing the fault and reclosing the circuit breaker, that is, the dead time, should
be made as short as possible to keep the power system stable. From the viewpoint of de-ionization
of the fault arc, the fault arc is de-ionized more thoroughly as the period of this dead time is
extended. The de-ionization commences when the circuit breakers for all terminals of the line are
tripped. Therefore, the dead time can be set at its minimum level if all terminals of the line are
tripped at the same time.
Autoreclose of the GRZ100 is started by any of the following protections that ensure high-speed
protection of all terminals.
command protection
zone 1 extension protection
specific zone 1 tripping
The GRZ100 provides two autoreclose systems, single-shot autoreclose and multi-shot
autoreclose.
Single-shot autoreclose
Three types of single-shot autoreclose modes are provided: single-phase autoreclose, three-phase
autoreclose, and single- and three-phase autoreclose. An optimal mode is selected form among
"Off (disable)" "SPAR", "TPAR", "SPAR&TPAR", "EXT1P" and "EXT3P" by the autoreclose
mode selection switch [ARC-M] or PLC signals (No.1683 1688). The PLC signals have priority
over the switch [ARC-M] setting. In any case, autoreclose is performed only once. If the fault state
still continues after reclosing, three-phases final tripping is activated.
Single-phase autoreclose:
In this mode, only the faulty phase is tripped, and then reclosed if a single-phase earth fault occurs.
In the case of a multi-phase fault, three phases are tripped, but reclosing is not made. Since power
can be transmitted through healthy phases even during dead time, this mode is convenient for
maintaining power system stablility. On the other hand, the capacitive coupling effect between the
healthy phase and faulty phase may cause a longer de-ionization time when compared to a
three-phase autoreclose. As a result, a longer dead time is required.
It is essential to correctly determine a faulty phase. The GRZ100 is equipped with an undervoltage
element with current compensation to correctly determine the faulty phase(s).
For single-phase autoreclose, each phase of the circuit breaker must be segregated.
This reclosing mode is simply expressed as "SPAR" in the following descriptions.
Three-phase autoreclose:
In this autoreclose mode, three phases are tripped, and then reclosed regardless of the fault mode,
whether single-phase fault or multi-phase fault. A shorter dead time can be set in this mode when
compared to the single-phase autoreclose. For the three-phase autoreclose, synchronism check and
voltage check between the busbar and the line are required.
This reclosing mode is simply expressed as "TPAR" in the following descriptions.
113
6 F 2 S 0 8 5 1
Single- and three-phase autoreclose:
In this autoreclose mode, single-phase tripping and reclosing are performed if a single-phase fault
occurs, while three-phase tripping and reclosing are performed if a multi-phase fault occurs.
This reclosing mode is simply expressed as "SPAR & TPAR" in the following descriptions.
Shingle-shot autoreclose can be applied to one-breaker reclosing and two-breaker reclosing in the
one-and-a-half breaker busbar system.
Multi-shot autoreclose
In the multi-shot autoreclose, any of two- to four-shot reclosing can be selected. In any case, the
first shot is selected from three types of autoreclose modes as described in the above single-shot
autoreclose. All successive shots (up to three times), which are applied if the first shot fails, are
three-phase tripping and reclosing.
Multi-shot autoreclose cannot be applied to two-breaker reclosing in the one-and-a-half breaker
busbar system..
The autoreclose can also be activated from an external line protection. At this time, all autoreclose
modes described above are effective.
If a fault occurs under the following conditions, three-phase final tripping is performed and
autoreclose is blocked.
Reclosing block signal is received from external unit locally or remotely.
Throughout the reclaim time
For evolving faults that occurred during the dead time between single-phase tripping and
reclosing, "SPAR & TPAR" functions as follows.
For evolving faults that occurred within the period of time set from the first fault, the reclosing
mode enters the three-phase autoreclose mode. At this time, the total dead time becomes the dead
time for three-phase autoreclose added to the dead time for single-phase autoreclose which has
been used until the evolving fault occurs.
For evolving faults occurred after the set time, three-phase final tripping is performed, and
reclosing is not performed.
If an evolving fault occurs when "SPAR" is selected, three-phase final tripping is performed, and
reclosing is not performed.
114
6 F 2 S 0 8 5 1
2.5.2 Scheme Logic
2.5.2.1 One-breaker Autoreclose
Figure 2.5.2.1 shows the simplified scheme logic for the single-shot autoreclose. Autoreclose for a
further fault incident is available when the circuit breaker is closed and ready for autoreclose (CB1
READY=1), the autoreclose mode by the switch [ARC-M] or the PLC is set to "SPAR", "TPAR"
or "SPAR & TPAR" and the on-delay timer TRDY1 is picked up. The TRDY1 is used to
determine the reclaim time.
"SPAR", "TPAR", "SPAR&TPAR"
&
+
[ARC-M]
5-300s
t 0
&
52A
52B
52C
CB1_READY 1545
TRIP-A
TRIP-B
TRIP-C
[ARC-EXT]
1
1
1
"ON"
"ON"
1
EXT_TRIP-A 1556
EXT_TRIP-B 1557
EXT_TRIP-C 1558
&
TP
F/F
Single-phase trip
+
[ARC-M]
"SPAR", "SPAR&TPAR"
&
&
0.01-10s
t 0
TRDY1 TSPR1
SPR.L-REQ 1824
"Default =CONSTANT 1"
&
Multi-phase trip
+
[ARC-M]
&
&
0.01-100s
t 0
TTPR1
TPR.L-REQ 1825
"Default =SYN-OP"
&
1
&
Single-phase trip
0.01-10s
t 0
TEVLV
Multi-phase trip
+
[ARC-M]
"TPAR", "SPAR&TPAR"
&
1
0.01-100s
t 0
TRR
1
0.1 - 10s
TW1
0.2s
ARC(*)
MSARC
(*)ARC
(For Leader CB)
(For Leader CB)
FT
1
ARC
(For Leader CB)
(For Leader CB)
(For Leader CB)
M-TRIPA
FT
1
0.1s
Trip when ARC1 READY not operated.
Multi phase trip in SPAR.
ARC1 READY
( ToFigure
2.10.2.8. )
CT-DG
&
"OFF"
+
[ARC-DEF]
BUP
ARC BLOCK 1544
"OFF"
[ARC-BU]
& "Disable"
+
[ARC-M]
ARC_BLOCK1 1564
1
ARC FAIL
(For Leader CB)
+
[ARC-SUC]
&
"ON"
Figure 2.5.2.1 Autoreclose Scheme Logic
If the autoreclose is ready, the internal tripping signal TRIP-A, B, C or external tripping signal
EXT_TRIP-A, B, C for each phase of the circuit breaker activates the autoreclose. These tripping
signals are output from the command protection, zone 1 extension protection, and specific zone 1
tripping. Whether or not the external trip signals are used to activate the reclosing is selected by
the scheme switch [ARC-EXT].
Once this autoreclose is activated, it is maintained by a flip-flop circuit until one reclosing cycle is
completed.
Autoreclose is not activated in the following conditions.
When the tripping is output by the directional earth fault command protection (CT-DG =1)
and the autoreclose selection switch [ARC-DEF] is set to "OFF".
When the tripping is performed by the out-of-step protection (OSTT =1), stub fault protection
(STUB=1), switch-onto-fault protection (SOTF =1) breaker failure protection (RETRIP=1) or
time-delayed backup protection (BUP =1).
115
6 F 2 S 0 8 5 1
When an autoreclose prohibiting binary input signal is applied (ARC_BLOCK =1)
If autoreclosing is not ready, a three-phase tripping command M-TRIP is output for all tripping
modes. At this time, autoreclose is not activated.
If all three phases of CB are closed, autoreclose is reset though it is initiated.
Autoreclose for single-phase fault
If the autoreclose mode is set to "SPAR" or "SPAR & TPAR", single-phase tripping is performed.
The dead time counter TSPR for single-phase reclosing is started by any of the tripping signals
TRIP-A to C. After the dead time has elapsed, reclosing command ARC is output.
If the autoreclose mode is set to "TPAR", three-phase tripping is performed and the dead time
counter TTPR1 for three-phase reclosing is started. After the dead time has elapsed, reclosing
command ARC is output based on the operating conditions of the voltage and synchronism check
elements output signal SYN-OP.
If the autoreclose mode is set to "Disable"("Off"), three-phase tripping is performed and
autoreclose is not started. Even though the autoreclose is started, the autoreclose is reset if all
phases of the CB are closing.
Autoreclose for multi-phase fault
Regardless of the autoreclose mode, three-phase tripping is performed and TRIP-A to C are
activated. If the autoreclose mode is set to "TPAR" or "SPAR & TPAR", the dead time counter
TTPR1 for three-phase reclosing is started. After the dead time has elapsed, reclosing command
ARC is output based on the operating conditions of the voltage and synchronism check elements
output signal SYN-OP. (The SYN-OP is assigned by the PLC as a default setting.)
If the autoreclose mode is set to "SPAR" or "Disable"("Off"), autoreclose is not activated.
If the operating conditions of the voltage and synchronism check elements are not satisfied during
three-phase reclosing, TRR is then picked up and reclosing is reset.
Autoreclose for evolving fault
Figure 2.5.2.2 shows the sequence diagram of autoreclose for an evolving fault. If single-phase
tripping is performed, the evolving fault detection timer TEVLV is started at the same time as the
TSPR is started. If no evolving faults occur, single-phase reclosing is performed when TSPR is
picked up.
Evolving fault First fault
Fault
Trip
3 reclosing 1 reclosing 1 trip 3 trip
TSPR
TEVLV
TSPR
TTPR1
TEVLV
TTPR1
Figure 2.5.2.2 Autoreclose for Evolving Fault
116
6 F 2 S 0 8 5 1
As shown in the figure, if an evolving fault occurs before TEVLV is picked up, three-phase
tripping is performed. If this occurs, TSPR and TEVLV are reset, and TTPR1 is now started.
After TTPR1 is picked up, three-phase reclosing is performed based on the status of the voltage
and synchronism check elements output signal SYN-OP. If an evolving fault occurs after the
TEVLV has picked up, autoreclose is reset and reclosing is not performed.
Voltage and synchronism check
There are four voltage modes as shown below when all three phases of the circuit breaker are
opened. The voltage and synchronism check is applicable to voltage modes 1 to 3 and controls the
energizing process of the lines and busbars in the three-phase autoreclose mode.
Voltage Mode 1 2 3 4
Busbar voltage (V
B
) live live dead dead
Line voltage (V
L
) live dead live dead
The synchronism check is performed for voltage mode 1 while the voltage check is performed for
voltage modes 2 and 3.
Figure 2.5.2.3 Energizing Control Scheme
Figure 2.5.2.3 shows the energizing control scheme. The voltage and synchronism check output
signal SYN-OP is generated when the following conditions have been established;
Synchronism check element SYN1 operates and on-delay timer TSYN1 is picked up.
Busbar overvoltage detector OVB and line undervoltage detector UVL1 operate, and on-delay
timer TLBD1 is picked up. (This detects live bus and dead line condition.)
Busbar undervoltage detector UVB and line overvoltage detector OVL1 operate, and on-delay
timer TDBL1 is picked up. (This detects dead bus and live line condition.)
Using the scheme switch [VCHK], the energizing direction can be selected.
&
SYN1
UVL1
OVL1
OVB
&
UVB
+
"OFF"
[VCHK]
"SY"
"DB"
"LB"
DBLL
LBDL
SYN-OP
TLBD1
0.01 10.00S
0.01 1.00S
TDBL1
0.01 1.00S
&
&
TSYN1
1
86
87
90
88
89
273
T3PLL
0.01 1.00S
397
3PLL
(Three phase live line)
117
6 F 2 S 0 8 5 1
Setting of [VCHK] Energizing control
LB Reclosed under "live bus and dead line" condition or with synchronism check
DB Reclosed under "dead bus and live line" condition or with synchronism check
SY Reclosed with synchronism check only.
OFF Reclosed without voltage and synchronism check.
When [VCHK] is set to "LB", the line is energized in the direction from the busbar to line under
the "live bus and dead line" condition. When [VCHK] is set to "DB", the lines are energized in the
direction from the line to busbar under the "dead bus and live line" condition.
When a synchronism check output exists, autoreclose is executed regardless of the position of the
scheme switch.
When [VCHK] is set to "SY", a three-phase autoreclose is performed with synchronism check
only.
When [VCHK] is set to "OFF", three-phase autoreclose is performed without voltage and
synchronism check.
The voltage and synchronism check require a single-phase voltage from the busbar or line as a
reference voltage. If the three-phase voltages that are used for the distance protection are supplied
from the line voltage transformer, the reference voltage has to be supplied from the busbar voltage
transformer. On the contrary, if the three-phase voltages that are used for the distance protection
are supplied from the busbar voltage transformer, the reference voltage has to be supplied from the
line voltage transformer.
Additionally, it is not necessary to fix the phase of the reference voltage.
The signal 3PLL shown in Figure 2.5.2.3 is output when all three phase voltages are live, and it is
available by the [3PH-VT] = LINE setting.
To match the busbar voltage and line voltage for the voltage and synchronism check option
mentioned above, the GRZ100 has the following three switches and VT ratio settings as shown in
Figure 2.5.2.4.
[VTPH-SEL]: This switch is used to match the voltage phases. If the A-phase voltage or
A-phase to B-phase voltage is used as a reference voltage, "A" is selected.
[VT-RATE]: This switch is used to match the magnitude and phase angle. "PH/G" is
selected when the reference voltage is a single-phase voltage while "PH/PH" is
selected when it is a phase-to-phase voltage.
[3PH-VT]: "Bus" is selected when the three-phase voltages are busbar voltages while
"Line" is selected when they are the line voltages.
VT: This setting is set to the VT ratio of busbar or line voltage for distance
protection
VTs1: This setting is set to the VT ratio of line or busbar reference voltage for voltage
check and synchronism check.
118
6 F 2 S 0 8 5 1
Distance
Measuring
Busbar or line
voltages
Line or busbar
reference voltage
[VTPH - SEL]
"C"
"B"
"A"
+
+
+
V
ref
V
c
V
b
V
a
[VT - RATE]
"PH/G"
[3PH - VT]
"Line"
"Bus"
"PH/PH"
+
+
+
+
Voltage check
&
Synchronism check
Figure 2.5.2.4 Matching of Busbar Voltage and Line Voltage
Autoreclosing requirement
Using PLC function, various reclose requirements can be designed. In Figure 2.5.2.1, a reclose
requirement for "SPAR", "TPAR" or "SPAR&TPAR" can be respectively assigned to the
following signals by PLC:
"SPAR": [SPR.L-REQ]
"TPAR": [TPR.L-REQ]
"SPAR&TPAR": [SPR.L-REQ], [TPR.L-REQ]
The default setting is as follows:
Reclose requirement Default setting Remarks
"SPAR" [SPR.L-REQ] = CONSTANT_1 No condition
"TPAR" [TPR.L-REQ] = SYP-ON Voltage and synchronism check
Permanent fault
When reclose-onto-a-fault is activated when a permanent fault exists, three-phase final tripping is
performed. However, this operation is performed only in the single-shot autoreclose mode. In the
multi-shot autoreclose mode, reclosing is retried as described below.
Multi-shot autoreclose
In multi-shot autoreclose, low-speed autoreclose is executed up to three times after high-speed
autoreclose fails. The first shot is high-speed autoreclose that functions in the same manner as
described for single-shot autoreclose. Figure 2.5.2.5 shows the simplified scheme logic for the
low-speed autoreclose of the second to fourth shot.
The multi-shot mode, two to four shots, is set with the scheme switch [ARC-SM].
119
6 F 2 S 0 8 5 1
F/F
F/F
F/F
F/F
&
1
SP2
SP1
FT
MSARC1
1
1
FT
MSARC2
SP1
F/F
FT
MSARC3
SP2
5 - 300s
FT
ARC
ARC
SYN-OP
"S2", "S3", "S4"
+
TP
ARC1
ARC1
t 0
STEP COUNTER
MULT.ARC
SP3
SP2
SP1
MSARC1
TS2R
TS2
5 - 300s
t 0
&
1
5 - 300s
t 0
5 - 300s
t 0
5 - 300s
t 0
5 - 300s
t 0
MSARC2
MSARC3
TS4R
MAR-FT
FT2
FT1
TS4
TS3R
TS3
&
SP2
SP1
&
SP3
FT3
&
1
&
1
1
&
&
&
CLR
CLOCK
1
0.1s
0 t
MSARC
1
FT
"S3"
"S4"
"S2"
[ARC-SM]
[ARC-SM]
0.5s
303
308
Figure 2.5.2.5 Scheme Logic for Multi-Shot Autoreclose
In low-speed autoreclose, the dead time counter TS2 for the second shot is activated if high-speed
autoreclose is performed (ARC = 1), but tripping occurs again (TP = 1). Second shot autoreclose is
performed only when the voltage and synchronism check element operates (SYN-OP = 1) after a
period of time set on TS2 has elapsed. At this time, outputs of the step counter are: SP1 = 1, SP2 =
0, and SP3 = 0.
Autoreclose is completed at this step if the two-shot mode is selected for the multi-shot mode.
Therefore, the tripping following the "reclose-onto-a-fault" becomes the final tripping (FT1 = 1).
If the voltage and synchronism check element does not operate within the period of time set on the
timer TS2R which is started at the same time as TS2 is started, the multi-shot autoreclose is
cancelled (MAR-FT = 1).
When the three shots mode is selected for the multi-shot mode, autoreclose is further retried after
the above tripping occurs. At this time, the TS3 and TS3R are started. The third shot autoreclose is
performed only when the voltage and synchronism check element operates after the period of time
set on the TS3 has elapsed. At this time, outputs of the step counter are: SP1 = 0, SP2 = 1, and SP3
= 0.
The three shot mode of autoreclose is then completed. Therefore, the tripping following the
"reclose-onto-a-fault" becomes the final tripping (FT2 = 1).
If the voltage and synchronism check element does not function within the period of time set on
the TS3R, multi-shot autoreclose is cancelled.
When four-shot autoreclose is selected, low-speed autoreclose is further retried once again for
tripping that occurs after the "reclose-onto-a-fault". This functions in the same manner as the
three-shot autoreclose.
120
6 F 2 S 0 8 5 1
Use of external automatic reclosing equipment
To use external automatic reclosing equipment instead of the built-in autoreclose function of the
GRZ100, the autoreclose mode is set to "EXT1P" or "EXT3P". When "EXT1P" is selected, the
GRZ100 performs single-phase tripping for a single-phase fault and three-phase tripping for a
multi-phase fault. When "EXT3P" is selected, three-phase tripping is performed for all faults. At
the same time, one binary signal for individual phase is output as an autoreclose start signal.
2.5.2.2 Two-breaker autoreclose
As shown in Figure 2.5.2.6, in the one-and-a-half breaker busbar arrangement, two circuit
breakers, the busbar breaker and the center breaker, must be reclosed. The GRZ100 series 300s is
provided with the two-breaker autoreclose scheme.
Multi-shot autoreclose is not applicable to two-breaker autoreclose; the scheme switch [ARC-SM]
is set to "OFF" for a default setting.
Autoreclose is not activated when an autoreclose prohibiting binary input signal is applied at the
local or remote terminal.
ARC_BLOCK signal common for leader and follower CB
ARC_BLOCK1 signal for leader CB
ARC_BLOCK2 signal for follower CB
The autoreclose scheme is different depending on the reclosing mode.
Center
breaker
Busbar
breaker
V
L2
V
L1
V
B
Protected line
Adjacent line
Figure 2.5.2.6 One-and-a-Half Breaker Busbar Arrangement
Single-phase autoreclose and single- and three-phase autoreclose
The breaker(s) to be reclosed and the reclosing order can be set by the scheme switch [ARC-CB]
as follows:
Setting of [ARC-CB] Autoreclose mode
ONE (Set when applied to a one-breaker system)
O1 Only the busbar breaker is reclosed and the center breaker is subjected to final tripping.
O2 Only the center breaker is reclosed and the busbar breaker is subjected to final tripping.
L1 Single-phase autoreclose: Both breakers are reclosed simultaneously.(*1)
Three-phase autoreclose: The busbar breaker is reclosed first. If successful, then the center
breaker is reclosed.
121
6 F 2 S 0 8 5 1
Setting of [ARC-CB] Autoreclose mode
L2 Single-phase autoreclose: Both breakers are reclosed simultaneously.(*1)
Three-phase autoreclose: The center breaker is reclosed first. If successful, then the busbar
breaker is reclosed.
Note : "ONE" is set only when the relay is applied to a one-breaker system. Trip and reclose commands
are output only for CB1(bus CB).
(1): Sequential autoreclose can be applied by changing of the dead timer setting or the PLC
setting.
The autoreclose scheme logic for the two circuit breakers are independent of each other and are
almost the same. The autoreclose scheme logic of the circuit breaker to be reclosed first (lead
breaker) is the same as that shown in Figure 2.5.2.1. The scheme logic of the circuit breaker to be
reclosed later (follower breaker) is different from that shown in Figure 2.5.2.7 in that the condition
that a reclosing command is output to the leader breaker is added to the start of the dead time
counter of the three-phase autoreclose.
"SPAR", "TPAR", "SPAR& TPAR"
&
+
[ARC-M]
5-300s
t 0
&
52A
52B
52C
CB2_READY 1546
&
TP
Single-phase trip
+
[ARC-M]
"SPAR", "SPAR& TPAR"
&
0.01-10s
t 0
TRDY2 TSPR2
SPR.F2-REQ 1833
"Default =CONSTANT 0"
&
Single-phase trip
0.01-10s
t 0
TEVLV
Multi-phase trip
+
[ARC-M]
"TPAR", "SPAR& TPAR"
&
1
0.01-100s
t 0
TRR
0.1 - 10s
TW2
0.1s
0.2s
1
ARC(*)
(*)ARC
(For Follower CB)
(For Follower CB)
FT
1
ARC
(For Follower CB)
(For Follower CB)
(For Follower CB)
FT
F/F
SPR.F-ST.REQ 1828
"Default =CONSTANT 1"
1 &
0.01-10s
t 0
TSPR1
&
&
1
Multi-phase trip
+
[ARC-M]
"TPAR"
&
0.01-10s
t 0
TTPR2
TPR.F-ST.REQ 1829
"Default ="ARC-SET"
&
0.01-100s
t 0
TTPR1
&
&
Trip when ARC2 READY not operated.
Multi phase trip in SPAR.
R.F-ST.REQ 1832
ARC2 READY
( FromFigure 2.6.2.1. )
1
&
CT-DG
&
"OFF"
+
[ARC-DEF]
BUP
ARC_BLOCK 1544
&
"OFF"
[ARC-BU]
&
"Disable"
+
[ARC-M]
SPR.F-REQ
"Default =CONSTANT 1"
&
1
TPR.F-REQ 1827
"Default =CONSTANT 0"
TPR.F2-REQ 1834
ARC FAIL
(For Follower CB)
+
[ARC-SUC]
&
"ON"
&
&
1826
Figure 2.5.2.7 Autoreclose Scheme for Follower Breaker
122
6 F 2 S 0 8 5 1
The start of the dead time counter can be configured by the PLC. In the default setting, the
single-phase autoreclose is started instantaneously after tripping, and the three-phase autoreclose
is started after the ARC-SET condition is satisfied.
The ARC-SET is a scheme signal whose logical level becomes 1 when a lead breakers
autoreclose command is output.
In default setting, therefore, the dead time of the follower breaker is as follows:
Three-phase autoreclose: equal to the sum of the dead time setting of the two breakers.
(TTPR1 + TTPR2)
Single-phase autoreclose: TSPR2
However, the dead time can be set that of the leader breaker by the PLC setting RF.ST-REQ.
The shortening of the dead time can be also applied when the leader breaker is final-tripped
because it is no ready.
Autoreclose start requirement
Using PLC function, various autoreclose start requirements can be designed. In Figure 2.5.2.7, a
reclose start requirement for "SPAR", "TPAR" or "SPAR&TPAR" can be respectively assigned to
the following signals by PLC:
"SPAR": [SPR.F-ST.REQ]
"TPAR": [TPR.F-ST.REQ]
"SPAR&TPAR": [SPR.F-ST.REQ], [TPR.F-ST.REQ]
The default setting for the follower CB autoreclose start requirement is as follows:
Reclose start
requirement
Default setting Remarks
"SPAR" [SPR.F-ST.REQ] = CONSTANT_1 No condition
"TPAR" [TPR.F-ST.REQ] = ARC-SET ARC-SET becomes 1 when the leader
CB is reclosed.
Autoreclose requirement
The autoreclose requirement can be designed by assigning a reclose requirement to the signals
[SPR.F-ST.REQ] and [TPR.F-ST.REQ] same as above.
The default setting for the follower CB autoreclose requirement is as follows:
Reclose requirement Default setting Remarks
"SPAR" [SPR.F-ST.REQ] = CONSTANT_1 No condition
"TPAR" [TPR.F-ST.REQ] = SYP-ON Voltage and synchronism check
Others
If the autoreclose start requirement is designed such as starting the follower CB in no-ready
condition of the leader CB, it is assigned to the signal [R.F-ST.REQ].
By assigning the autoreclose start requirement to the signal [R.F-ST.REQ], both the leader CB and
the follower CB are set the same dead time. The reclose requirement is assigned to the signals
[SPR.F2-ST.REQ] and [TPR.F2-ST.REQ].
The default setting for the follower CB is as follows:
123
6 F 2 S 0 8 5 1
Requirement Default setting
Reclose requirement [R.F-ST.REQ] = CONSTANT_0 (No used)
Reclose start requirement
"SPAR" [SPR.F2-REQ] = CONSTANT_0 (No used)
"TPAR" [TPR.F2-REQ] = CONSTANT_0 (No used)
Figure 2.5.2.8 shows the energizing control scheme of the two circuit breakers in the three-phase
autoreclose. OVB and UVB are the overvoltage and undervoltage detectors of busbar voltage V
B
in Figure 2.5.2.6. OVL1 and UVL1 are likewise the overvoltage and undervoltage detectors of line
voltage V
L1
.
OVL2 and UVL2 are likewise the overvoltage and undervoltage detectors of line voltage V
L2
.
V
L2
in the center breaker is equivalent to the busbar voltage V
B
in the busbar breaker.
SYN1 and SYN2 are the synchronism check elements to check synchronization between the two
sides of the busbar and center breakers, respectively.
TPARL-SET is a scheme signal whose logical level becomes 1 when a three-phase autoreclose
command is output to the lead breaker. SYN-OP is a voltage and synchronism check output.
&
SYN2
UVL2
OVL2
UVL1
OVL1
SYN1
UVB
OVB
TLBD1
0.01 1.00s
TDBL1
0.01 1.00s
0.01 10.00s
0.01 1.00s
0.01 1.00s
0.01 10.00s
1
1
&
&
&
&
&
&
&
1
&
&
TSYN1
1
1
"ONE"
"L1"
"L2"
"01"
"02"
[ARC-CB]
TPARL-SET
+
1
&
&
TLBD2
TDBL2
TSYN2
1
&
&
&
+
[VCHK]
"LB2"
"LB1"
"DB"
"SY"
"OFF"
SYN
-OP
86
87
89
90
88
273
91
92
93
T3PLL
0.01 1.00S
397
3PLL
(Three phase live line)
Note : [ARC-CB] is set to "ONE" only when the relay is applied to one-breaker system. Trip and reclose
commands are output only for CB1(bus CB).
Figure 2.5.2.8 Energizing Control Scheme for Two Circuit Breakers
124
6 F 2 S 0 8 5 1
The voltage and synchronism check is performed as shown below according to the [ARC-CB]
settings:
Setting of [ARC-CB] Voltage and synchronism check
ONE or O1 A voltage and synchronism check is performed using voltages V
B
and V
L1
.
O2 A voltage and synchronism check is performed using voltages V
L1
and V
L2
.
L1 Since the logical level of TPARL-SET is 0, a voltage and synchronism check is performed
for the busbar breaker using voltages V
B
and V
L1
. Then, the logical level of TPARL-SET
becomes 1 and a voltage and synchronism check is performed for the center breaker
using voltages V
L1
and V
L2
and a reclosing command is output to the center breaker.
L2 A voltage and synchronism check is performed for the center breaker using voltages V
L1
and V
L2
. Then, the logical level of TPARL-SET becomes 1 and a voltage and synchronism
check is performed for the busbar breaker using voltages V
B
and V
L1
.
Note : "ONE" is set only when the relay is applied to one-breaker system. Trip and reclose commands
are output only for CB1(bus CB).
The energizing control for the two circuit breakers can be set by the scheme switch [VCHK] as
follows:
Setting of [VCHK] Energizing control
LB1 The lead breaker is reclosed under the "live bus and dead line" condition or with
synchronism check, and the follower breaker is reclosed with synchronism check only.
LB2 The leader breaker is reclosed under the "live bus and dead line" condition or with
synchronism check, and the follower breaker is reclosed under the "dead bus and live line"
condition or with synchronism check.
DB Both breakers are reclosed under the "dead bus and live line" condition or with
synchronism check.
SYN Both breakers are reclosed with synchronism check only.
OFF Both breakers are reclosed without voltage and synchronism check.
The scheme switch [ARC-SUC] is used to check the autoreclose succeeds. If all three phase CB
contacts have been closed within TSUC time after ARC shot output, it is judged that the
autoreclose has succeeded (AS). If not, it is judged that the autoreclose has failed (AF), and
becomes the final tripping (FT).
The relay provides the user configurable switch [UARCSW] with three-positions (P1, P2, P3) to
be programmed by using PLC function. Any position can be selected. If this switch is not used for
the PLC setting, it is invalid.
2.5.3 Setting
The setting elements necessary for the autoreclose and their setting ranges are shown in the table
below.
Element Range Step Default Remarks
VT 1 - 20000 1 2000 VT ratio for distance protection
VTs1 1 - 20000 1 2000 VT ratio for voltage and synchronism check
TSPR1 0.01 - 10.00 s 0.01 s 0.80 s Dead time for single - phase autoreclose
TTPR1 0.01 - 100.00 s 0.01 s 0.60 s Dead time for three - phase autoreclose
TRR 0.01 - 100.00 s 0.01 s 2.00 s Autoreclose reset time
TEVLV 0.01 - 10.00 s 0.01 s 0.30 s Dead time reset for evolving fault
TRDY1 5 - 300 s 1 s 60 s Reclaim time
125
6 F 2 S 0 8 5 1
Element Range Step Default Remarks
SYN1 Synchronism check
SY1 5 - 75 1 30
SY1UV 10 - 150 V 1 V 83 V
SY1OV 10 - 150 V 1 V 51 V
OVB 10 - 150 V 1 V 51 V Live bus check
UVB 10 - 150 V 1 V 13 V Dead bus check
OVL1 10 - 150 V 1 V 51 V Live line check
UVL1 10 - 150 V 1 V 13 V Dead line check
TSYN1 0.01 - 10.00 s 0.01 s 1.00 s Synchronism check time
TLBD1 0.01 - 1.00 s 0.01 s 0.05 s Voltage check time
TDBL1 0.01 - 1.00 s 0.01 s 0.05 s Voltage check time
T3PLL 0.01 - 1.00 s 0.01 s 0.05 s Three phase live line check
TW1 0.1 - 10.0 s 0.1 s 0.2 s Reclosing signal output time
TS2 5.0 - 300.0 s 0.1 s 20.0 s Second shot dead time
TS3 5.0 - 300.0 s 0.1 s 20.0 s Third shot dead time
TS4 5.0 - 300.0 s 0.1 s 20.0 s Fourth shot dead time
TS2R 5.0 - 300.0 s 0.1 s 30.0 s Second shot reset time
TS3R 5.0 - 300.0 s 0.1 s 30.0 s Third shot reset time
TS4R 5.0 - 300.0 s 0.1 s 30.0 s Fourth shot reset time
ARC - M Disabled/SPAR/TPAR/
SPAR & TPAR/EXT1P/EXT3P
SPAR & TPAR Autoreclose mode
ARC - DEF OFF/ON OFF DEF autoreclose
ARC-BU OFF/ON OFF Backup trip autoreclose
ARC-EXT OFF/ON OFF External start
ARC - SM OFF/S2/S3/S4 OFF Multi - shot autoreclose mode
ARC-SUC OFF/ON OFF Autoreclose success checking
VCHK OFF/LB/DB/SY LB Energizing direction
VTPHSEL A/B/C A Phase of reference voltage
VT - RATE PH/G / PH/PH PH/G VT rating
3PH - VT BUS/LINE LINE Location of three - phase VTs
[UARCSW] P1/P2/P3 (P1)() User ARC switch for PLC
() If this switch is not used for PLC setting, it is invalid.
VT is VT ratio setting of distance protection, and VTs1 is VT ratio setting of a reference
voltage input for voltage and synchronism check element as shown in Figure 2.5.3.1.
In a voltage setting, set SY1UV, SY1OV, OVB, UVB, OVL1 and UVL1 based on
the VT rating for voltage and synchronism check. (When a voltage rating between line VT and
busbar VT is different as shown in Figure 2.5.3.1, the voltage input from VT is matched to the
rating of VTs1 using the setting of VT and VTs1.)
CB
Line VT
Busbar VT
VT setting
GRZ100
Busbar
Line
VL
X
VTs1 setting
VB
Reference voltage
for voltage and
synchronism check
For distance
protection
Figure 2.5.3.1 VT and VTs1 Ratio Setting for Busbar or Line Voltage
126
6 F 2 S 0 8 5 1
To determine the dead time, it is essential to find an optimal value while taking factors,
de-ionization time and power system stability, into consideration which normally contradict one
other.
Normally, a longer de-ionization time is required for a higher line voltage or larger fault current.
For three-phase autoreclose, the dead time is generally 15 to 30 cycles. In single-phase
autoreclose, the secondary arc current induced from the healthy phases may affect the
de-ionization time. Therefore, it is necessary to set a longer dead time for single-phase autoreclose
compared to that for three-phase autoreclose.
In three-phase autoreclose, if the voltage and synchronism check does not operate within the
period of time set on the delayed pick-up timer TRR which is started at the same time as the dead
time counter TTPR1 is started, reclosing is not performed and three-phase autoreclose is reset to
its initial state. Therefore, for example, TRR is set to the time setting of the TTPR1 plus 100 ms.
The TEVLV determines the possibility of three-phase reclosing for an evolving fault.
When the TEVLV is set to the same setting as the TSPR, three-phase reclosing is performed for all
evolving faults. As the setting for the TEVLV is made shorter, the possibility of three-phase
reclosing for an evolving fault becomes small and that of three-phase final tripping becomes large.
For the two-breaker autoreclose, the following additional settings are required.
Element Range Step Default Remarks
VTs2 1 - 20000 1 2000 VT ratio for voltage and synchronism check SYN2
TSPR2 0.1 10.0s 0.1s 0.1s Dead time for single-phase autoreclose of follower breaker
TTPR2 0.1 10.0s 0.1s 0.1s Dead time for three-phase autoreclose of follower breaker
TRDY2 5 300s 1s 60s Reclaim time of follower breaker
SYN2 Synchronism check
SY2
5 75 1 30
SY2UV 10 150V 1V 83V
SY2OV 10 150V 1V 51V
OVL2 10 150V 1V 51V Live line check
UVL2 10 150V 1V 13V Dead line check
TSYN2 0.01 10.00s 0.01s 1.00s Synchronism check time
TLBD2 0.01 1.00s 0.01s 0.05s Voltage check time
TDBL2 0.01 1.00s 0.01s 0.05s Voltage check time
TW2 0.1 10.0s 0.1s 0.2s Reclosing signal output time
[ARC-CB] ONE/O1/O2/L1/L2 L1 Two breaker autoreclose mode
[VCHK] OFF/LB1/LB2/DB/SYN LB1 Energizing direction
Note : [ARC-CB] is set to "ONE" only when the relay is applied to one-breaker system. Trip and reclose
commands are output only for CB1(bus CB).
2.5.4 Autoreclose Output Signals
The autoreclose scheme logic has two output reclosing signals: ARC1 and ARC2. ARC1 is a
reclosing signal for a single breaker autoreclose or a reclosing signal for the busbar breaker in a
two-breaker autoreclose scheme.
ARC2 is the reclosing signal for the center breaker of the two-breaker autoreclose scheme.
The assignment of these reclosing signals to the output relays can be configured, which is done
using the setting menu. For more information on this, see Section 3.2.2 and 4.2.6.9. For the default
setting, see Appendix D.
127
6 F 2 S 0 8 5 1
SY1UV
SY1OV
VB
VL
s
2.5.5 Voltage and Synchronism Check Elements OVL, UVL, OVB, UVB, and SYN
The voltage check and synchronism check elements are used for autoreclose.
The output of the voltage check element is used to check whether the line and busbar are dead or
live. The voltage check element has undervoltage detectors UVL and UVB, and overvoltage
detectors OVL and OVB for the line voltage and busbar voltage check. The under voltage detector
checks that the line or busbar is dead while the overvoltage detector checks that it is live. These
detectors function in the same manner as other level detectors described later.
Figure 2.5.5.1 shows the characteristics of the synchronism check element used for the autoreclose
if the line and busbar are live.
The synchronism check element operates if both the voltage difference and phase angle difference
are within their setting values.
Figure 2.5.5.1 Synchronism Check Element
For the element SYN1, the voltage difference is checked by the following equations.
SY1OV VB SY1UV
SY1OV VL SY1UV
where,
VB = busbar voltage
VL = line voltage
SY1OV = lower voltage setting
SY1UV = upper voltage setting
The phase difference is checked by the following equations.
VB VL cos 0
VB VL sin (SY1s) VB VL sin
where,
= phase difference between VB and VL
SY1s = phase difference setting
A detected slip cycle is determined by the following equation:
128
6 F 2 S 0 8 5 1
where,
f = slip cycle
TSYN = synchronism check timer setting
f =
180TSYN
s
129
6 F 2 S 0 8 5 1
2.6 Fault Locator
2.6.1 Application
The fault locator incorporated in the GRZ100 measures the distance to fault on the protected line
using local voltages and currents. The measurement result is expressed as a percentage (%) of the
line length and the distance (km) and is displayed on the LCD on the relay front panel. It is also
output to a local PC or RSM (relay setting and monitoring) system.
In fault location, the phase selection element UVC is used to detect a faulted phase.
To measure the distance to fault, the fault locator requires minimum 3 cycles as a fault duration
time.
In distance to fault calculations, the change in the current before and after the fault has occurred is
used as a reference current, alleviating influences of the load current and arc voltage. As a result,
the location error is a maximum of 2.5 km for faults at a distance of up to 100 km, and a
maximum of 2.5% for faults at a distance between 100 km and 250 km.
Note: If abnormal settings far from actual transmission line impedance, e.g. resistance value
so larger than reactance value, etc., are done, the location error will be larger.
The fault locator can display the fault point in all zones which is outside the protected line, if the
scheme switch [AZFLEN]="ON". In this case, the fault point is not always measured correctly.
The fault locator cannot correctly measure the distance to fault during a power swing.
Fault location is enabled or disabled by setting "Fault locator" to "ON" or "OFF" on the "Fault
record" screen in the "Record" sub-menu.
2.6.2 Distance to Fault Calculation
The distance to fault x
1
is calculated from equation (1) and (2) using the local voltage and current
of the fault phase and a current change before and after the fault occurrence. The current change
before and after the fault occurrence represented by I" and I" is used as the reference current.
The impedance imbalance compensation factor is used to maintain high measuring accuracy even
when the impedance of each phase has great variations.
Distance calculation for phase fault (in the case of BC-phase fault)
x
1
=
I
m
(V
bc
I") L
{I
m
(R
1
I
bc
I") + R
e
(X
1
I
bc
I")} K
bc
(1)
where,
V
bc
= fault voltage between faulted phases = V
b
V
c
I
bc
= fault current between faulted phases = I
b
I
c
I" = change of fault current before and after fault occurrence = (I
b
-I
c
) (I
Lb
-I
Lc
)
I
Lb
, I
Lc
= load current
R
1
= resistance component of line positive sequence impedance
X
1
= reactance component of line positive sequence impedance
K
bc
= impedance imbalance compensation factor
I
m
( ) = imaginary part in parentheses
R
e
( ) = real part in parentheses
L = line length (km)
130
6 F 2 S 0 8 5 1
Distance calculation for earth fault (in the case of A-phase earth fault)
x
1
=
I
m
(V
a
I
") L
{I
m
(R
1
I
I
" + R
0
I
0S
I
" + R
0m
I
0m
I
") + R
e
(X
1
I
I
" + X
0
I
0S
I
" + X
0m
I
0m
I
")} K
a
where,
V
a
= fault voltage
I
_
Set the cursor position in the bracket by selecting "" or "" and pressing the ENTER key.
Move the blinking cursor to a selecting character.
Press the ENTER key to enter the blinking character at the cursor position in the bracket on
the top line.
Press the END key to confirm the entry and return to the upper screen.
To correct the entered character, do either of the followings:
Discard the character by selecting "" and pressing the ENTER key, and enter the new
character.
Discard the whole entry by pressing the CANCEL key and restart the entry from the first.
To complete the setting
Even after making entries on each setting screen by pressing the ENTER key, the new settings
are not yet used for operation, though stored in the memory. To validate the new settings, take the
following steps.
Press the END key to return to the upper screen. Repeat this until the confirmation screen
shown below is displayed. The confirmation screen is displayed just before returning to the
"Setting (change)" sub-menu.
/ 2 * * * * * * * * * * * * *
?
*
C h a n g e s e t t i n g s
E n t e r = Y C a n c e l = N o
* * * *
e s
179
6 F 2 S 0 8 5 1
When the screen is displayed, press the ENTER key to start operation using the new settings,
or press the CANCEL key to correct or cancel the entries. In the latter case, the screen turns
back to the setting screen to enable reentries. Press the CANCEL key to cancel entries made
so far and to turn to the "Setting (change)" sub-menu.
4.2.6.2 Password
For the sake of security of changing the settings and testing the relay, password protection can be
set as follows;
Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
/ 1 S e t t i n g
1 = P a s s w o r d
( c h a n g ) e
2 = D e s c r i p t i o n 3 = C o m m
4 = R e c o r d
7 = B i n a r y i
5 = S t a t u s 6 = P r o t e c t i o n
n p u t 8 = B i n a y r t o u t p u 9 = L E D
.
Press 1 (= Password) to display the "Password" screen.
/ 2 P a s s w o r d
I n p u t n e w p a s s w o r d [ ]
R e t y p e n e w p a s s w o r d [ ]
Enter a 4-digit number within the brackets of "Input new password" and press the ENTER
key.
For confirmation, enter the same 4-digit number in the brackets of "Retype new password" and
press the ENTER key.
Press the END key to display the confirmation screen. If the retyped number is different
from that first entered, the following message is displayed on the bottom of the "Password"
screen before returning to the upper screen.
"Mismatch-password unchanged"
Reentry is then requested.
Press 2 (= Test) on the "Password" screen to set the password for the test.
/ 2 T e s t
I n p u t n e w p a s s w o r d [ ]
R e t y p e n e w p a s s w o r d [ ]
Set the password the same manner as that of the "Setting" above.
Password trap
After the password has been set, the password must be entered in order to enter the setting change
and the test screens.
If 4 (= Setting (change)) is entered on the top "MENU" screen, the password trap screen
"Password" is displayed. If the password is not entered correctly, it is not possible to move to the
"Setting (change)" sub-menu screens.
180
6 F 2 S 0 8 5 1
P a s s w o r d
I n p u t p a s s w o r d [
]
Canceling or changing the password
To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The
"Setting (change)" screen is then displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
If you forget the password
Press CANCEL and RESET keys together for one second on the top "MENU" screen. The
screen goes off, and the password protection of the GRZ100 is canceled. Set the password again.
4.2.6.3 Description
To enter the plant name and other data, do the following. These data are attached to records.
Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
Press 2 (= Description) to display the "Description" screen.
/ 2 D e s c r i p t i o n
1 = P l a n n a t e = D e i 2 s c r i t p m o n
To enter the plant name, select 1 (= Plant name) on the "Description" screen.
/ 3 P l a n t n a m e ] _ [
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ( ) [ ] @
a b c d e f g h i j k l m n o p q r s t u v w x y z { } * / + - < = >
0 1 2 3 4 5 6 7 8 9 ! # $ % & : ; , . ^ `
To enter special items, select 2 (= Description) on the "Description" screen.
/ 3 D e s c r p t i o ] _ [
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ( ) [ ] @
a b c d e f g h i j k l m n o p q r s t u v w x y z { } * / + - < = >
0 1 2 3 4 5 6 7 8 9 ! # $ % & ^ `
i n
Enter the text string.
The plant name and special items entered are viewed with the "Setting (view)" sub-menu and
attached to disturbance records when they are displayed on a local or a remote PC.
4.2.6.4 Communication
If the relay is linked with RSM (relay setting and monitoring system), IEC60870-5-103 or
Ethernet LAN, the relay address must be set. Do this as follows:
Press 4 (= Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
181
6 F 2 S 0 8 5 1
Press 3 (= Comm.) on the "Setting (change)" screen to display the "Communication" screen.
/ 2 c C o m m u n i n t a o i
c h 2 = S w i t
e s s 1 = A d d r t / P a r a m e r e
Press 1 (= Address/Parameter) to enter the relay address number.
For channel 1(port 1)
For SNTP server 1
For SNTP server 4
For channel 1(port 1)
Enter the address number on "HDLC" column for RSM and/or "IEC" column for
IEC60870-5-103 and the compensation value on "SYADJ" column for adjustment of time
synchronization of protocol used (: lags the time, +: leads the time).
Enter IP address for IP1-1 to IP1-4, Subnet mask for SM1-1 to SM1-4, Default gateway for
GW1-1 to GW1-4, and SNTP server address for SI1-1 to SI4-4. Four SNTP servers are
available.
Enter "0" or "1" on "SMODE" column to set the standard time synchronized mode for SNTP
server. Using low accuracy level of time server, synchronized compensation to maintain
synchronization accuracy may not be done automatically. Therefore enter "1", and
synchronized compensation is done forcibly. The default setting is "0".
Enter the time on "GOINT" to set the maximum GOOSE message publishing term if GOOSE
message receive checked.
Enter the time on "DEADT" to set the Keep Alive time.
Enter the IP address of the device for PG1-1 to PG1-4 if Ping response checked.
182
6 F 2 S 0 8 5 1
IP address: , , ,
IP1-1 IP1-2 IP1-3 IP1-4
SM1-1 to SM1-4, GW1-1 to GW1-4, SI1-1 to SI4-4, PG1-1 to PG1-4: same as above.
Enter the port switch time on "PSWTM" to judge the port is linked down. This setting is
available only when the switch "RLNSCH" is selected 1 (=HS1).
Press the ENTER key.
CAUTION: Do not overlap the number in a network.
Press 2 (=Switch) on the "Communication" screen to select the protocol, transmission speed
(baud rate) and test mode setting, etc., of the RSM or IEC60870-5-103 or IEC61850.
/ 3 S w i t c h 1 / *
2 3 2 C 1 = 9 . 6 2 = 1 9 . 2 = 3 3 8 . 4 4 = . 6 5 7 4
I E C B 1 = 9 . 6 2 = 1 9 . 2 R 2
I E C B K L 1 = N o r a l 2 = B c o k e d l m 1
1 C P R T C 1 = H D L 2 = I E C 3 0 2 L 1
8 5 0 B K L 1 = N o r a l 2 = B c o k e d l m 1
8 5 0 A T U 0 = O f f 1 = O n 1
T S T M D O 0 = O f f 1 = O n 0
G S E C K H 0 = O f f 1 = O n 0
P I N G H C 0 = O f f 1 = O n K 0
R L N S H C 0 = O f f 1 = H S 1 0
Select the number corresponding to the system and press the ENTER key.
<PRTCL1>
PRTCL1 is used to select the protocol for channel 1 (COM1 or OP1) of the serial communication
port RS485 or FO (fibre optic).
When the remote RSM system applied, select 1 (=HDLC). When the IEC60870-5-103
applied, select 2 (=IEC103).
<232C>
This line is to select the RS-232C baud rate when the RSM system applied.
Note: The default setting of the 232C is 9.6kbps. The 57.6kbps setting, if possible, is recommended to
serve user for comfortable operation. The setting of RSM100 is also set to the same baud rate.
<IECBR>
This line is to select the baud rate when the IEC60870-5-103 system applied.
<IECBLK>
Select 2 (=Blocked) to block the monitor direction in the IEC60870-5-103 communication. When
using the IEC60870-5-103 communication, select 1 (=Normal).
<850BLK>
Select 2 (=Blocked) to block the monitor direction in the IEC61850 communication. When using
the IEC61850 communication, select 1 (=Normal).
<850AUT>
In the IEC61850 communication, GRZ100 provides the access restriction which permits a client
183
6 F 2 S 0 8 5 1
to access only if an authentication parameter matches with a valid parameter (password).
Password is 4 digit number and shared with RSM100.
Select 1 (=On) to use the authentication function.
<TSTMOD>
Select 1 (=On) to set the test mode in the IEC61850 communication.
<GSECHK>
This function is to alarm if any one of GOOSE messages written in GOOSE subscribe file cannot
be received.
Select 1 (=On) to execute GOOSE receive check in the IEC61850 communication.
<PINGCHK>
This function is to check the health of network by regularly sending Ping to IP address which is set
on PG-.
Select 1 (=On) to execute Ping response check.
<RLNSCH>
This function is available only for two LAN port model. (Refer to Appendix S.)
Select 0 (=Off) to use the port 1 only.
Select 1 (=HS1) to use both LAN port 1 and LAN port 2 as a hot-standby communication system.
In this case, the communication port is automatically switched to another port if the one port
cannot be communicated caused by the link down over the PSWTM setting time or the device
failure.
CAUTION:
(1) In the communication using an optical port, the link-up/-down status is repeated if the port
connection is not perfectly such as an imperfect optical connector insertion, etc. Then, if the
link-down time is shorter than the PSWTM setting time, the link-down and link-up status will
continue. In this case, if the PSWTM is set to 0 ms, the link-down and link-up status will be
avoided.
(2) In the communication using an electrical LAN port, the auto-negotiation which sets
communication method/speed when linking up is executed. The link-down status continues
until the auto-negotiation completed even though the link-down is momentary. If the PSWTM
is set to a value more than the required time (about 1 to 2 s) for the auto-negotiation, the
automatically port switching by such a momentary link-down will be avoided.
4.2.6.5 Setting the Recording
To set the recording function as described in Section 4.2.3, do the following:
Press 4 (=Setting (change)) on the main "MENU" screen to display the "Setting (change)"
screen.
Press 4 (=Record) to display the "Record" screen.
R e c o
1 = r e c o r d
3 = D i s t u r b a n c e
/ 2 r
a u t F l 2 = E v e n t r e c o r d
r e c o r d
4 = A u t o m a t i c t e s t i n t e r v a l
d
184
6 F 2 S 0 8 5 1
Setting the fault recording
Press 1 (=Fault record) to display the "Fault record" screen.
r e c o r d
r 1 _
2 1 / / 3
0 = O f f
a u t F l
1 = O n l o c a t o a u t F l
N 0 0 = O f f 1 = O n Z F E A L
Enter 1 (=On) to record the fault location and all-zone fault location respectively.
Enter 0 (=Off) not to record the fault location and all-zone fault location respectively.
Press the ENTER key.
Setting the event recording
Press 2 (=Event record) to display the "Event record" screen.
E V 2 ( 0 - 3 0 7 1 ) : 1
E V 1 ( 0 - 3 0 7 1 ) : 0
/ 3 E v e n t r e c o r d 1 / 1 2 9
B I T R N ( 0 - 1 2 8 ) : 1 2 8 _
E V 3 ( 0 - 3 0 7 1 ) : 1
E V 4 ( 0 - 3 0 7 1 ) : 1
E V 5 ( 0 - 3 0 7 1 ) : 3 0 7 1
E V 6 ( 0 - 3 0 7 1 ) : 3 0 7 1
E V 7 ( 0 - 3 0 7 1 ) : 3 0 7 1
E V 8 ( 0 - 3 0 7 1 ) : 3 0 7 1
E V 9 ( 0 - 3 0 7 1 ) : 3 0 7 1
E V 1 0 ( 0 - 3 0 7 1 ) : 3 0 7 1
:
:
:
E V 1 2 8 ( 0 - 3 0 7 1 ) : 3 0 7 1
<BITRN>
Enter the number of event to record the status change both to "On" and "Off". If enter 20, both
status change is recorded for EV1 to EV20 events and only the status change to "On" is
recorded for EV21 to EV128 events.
<EV>
Enter the signal number to record as the event in Appendix B. It is recommended that this
setting can be performed by RSM100 because the signal name cannot be entered by LCD
screen. (Refer to Section 3.4.2.)
Setting the disturbance recording
Press 3 (=Disturbance record) to display the "Disturbance record" screen.
e 2 = S c h e m s w i t c h
/ 3 D i s t u r b a n c e r e c r o d
g i s n a y 3 = B i n r a l
1 = R e c o r m t i e t & s t a r e r d
Press 1 (=Record time & starter) to display the "Record time & starter" screen.
185
6 F 2 S 0 8 5 1
U V P - G ( 0 - 7 6 ) : 5 7 V
U V P - S ( 0 - 1 3 2 ) : 1 0 0 V
O C P - G ( 0 . 5 - 2 5 0 . 0 ) : 1 0 . 0 A
O C P - S ( 0 . 5 - 2 5 0 . 0 ) : 1 0 . 0 A
/ R e c o r d t i m e & s t a r t e r 1 / 5
T i m e ( 0 . 1 - 3 . 0 ) : 2 . 0 _ A
Enter the recording time and starter element settings.
To set each starter to use or not to use, do the following:
Press 2 (= Scheme switch) on the "Disturbance record" screen to display the "Scheme switch"
screen.
1 T R I P 0 = f O f 1 = O n
1 O C P - S 0 = O f f 1 = O n
1 / 5
/ 4 S c h e m e s w i t c h
1 O C P - G 0 = O f f 1 = O n
1 U V P - S 0 = O f f 1 = O n
1 U V P - G 0 = O f f 1 = O n
Enter 1 to use as a starter.
Press 3 (= Binary signal) on the "Disturbance record" screen to display the "Binary signal"
screen.
S I G 4 ( 0 - 3 0 7 1 ) : 4
S I G 3 ( 0 - 3 0 7 1 ) : 3
S I G 2 ( 0 - 3 0 7 1 ) : 2
/ B i n a r y s i g n a l 1 / 3 2
S I G 1 ( 0 - 3 0 7 1 ) : 1 _
S I G 3 2 ( 0 - 3 0 7 1 ) : 0
Enter the signal number to record binary signals in Appendix B. It is recommended that this
setting can be performed by RSM100 because the signal name cannot be entered by LCD screen.
(Refer to Section 3.4.3.)
Setting the automatic testing
Press 4 (= Automatic test interval) to display the "Automatic test interval" screen.
/ 3 A u t o m a t i c t e s t i n t e r v a l 1 / 1
C h a n n ( 1 - 2 4 ) : 1 2 _ h r s
Enter the test intervals of the signal channel.
4.2.6.6 Status
To set the status display described in Section 4.2.4, do the following.
Press 5 (= Status) on the "Setting (change)" sub-menu to display the "Status" screen.
186
6 F 2 S 0 8 5 1
3 = T i m e z o n e
2 = T i m e s y n c h r o n i z a t i o n
/ 2 S t a t u s
1 = M e t e r i n g
Setting the metering
Press 1 (= Metering) to display the "Metering" screen.
/ 3 M e t e r i n g 1 / 3
P o w e r ( P / Q ) 1 = S e n d 2 = R e c e i v e 1
C u r r e n t 1 = L a g 2 = L e a d 1
D i s p l a y v a l u e 1 = P r i m a r y 2 = S e c o n r y d a 1
Enter the selected number and press the ENTER key. Repeat this for all items.
Note: Power and Current setting
Active Power Display
Power setting=1(Send) Power setting=2(Receive)
V
I
V
I
Reactive Power Display
Current setting=1(Lag) Current setting=2(Lead)
V
I
V
I
Setting the time synchronization
The calendar clock can run locally or be synchronized with external IRIG-B time standard signal,
RSM clock, IEC60870-5-103(IEC) or SNTP. This is selected by setting as follows:
Press 2 (= Time synchronization) to display the "Time synchronization" screen.
Enter the selected number and press the ENTER key.
Note: When to select IRIG-B, RSM, IEC, or SNTP, check that they are active on the "Time
synchronization source" screen in "Status" sub-menu. If it is set to an inactive IRIG-B, RSM,
IEC, or SNTP, the calendar clock runs locally. RMT is available only for relay model with
integral digital communication and it is synchronised with the remote terminal relay.
Setting the time zone
When the calendar clock is synchronized with the IRIG-B time standard, it is possible to transform
GMT to the local time.
187
6 F 2 S 0 8 5 1
Press 3 (= Time zone) to display the "Time zone" screen.
G M T m ( - 5 9 - + 5 9 ) : + 0 m i n
/ 3 T i m e z o n e 1 / 2
G M T ( - 1 2 - + 1 2 ) : + 9 _ h r s
Enter the difference between GMT and local time. Enter a numerical value to GMT (hrs) and
GMTm (min), and press the ENTER key.
4.2.6.7 Protection
The GRZ100 can have 8 setting groups for protection in order to accommodate changes in the
operation of the power system. One setting group is assigned active. To set the protection, proceed
as follows:
Press 6 (= Protection) on the "Setting (change)" screen to display the "Protection" screen.
/ 2 P r o t e c t i o n
1 = C h a n g e a c t i v e g r o u p
2 = C h a n g e s e t t i n g
3 = C o p y g r o u p
Changing the active group
Press 1 (= Change active group) to display the "Change active group" screen.
/ 3 C h a n g e a c t i v e g r o u p ( A c t i v e g r o u p = * )
1 = G r o u p 1 2 = G r o u p 2 3 = G r o u p 3 4 = G r o u p 4
5 = G r o u p 5 6 = G r o u p 6 7 = G r o u p 7 8 = G r o u p 8
C u r r e n t N o . = * S e l e c t N o . =
Enter the selected number and press the ENTER key.
Changing the settings
Almost all the setting items have default values that are set when the product was shipped. For the
default values, see Appendix D and H.
To change the settings, do the following:
Press 2 (= Change setting) to display the "Change setting" screen.
/ 3 C h a n g e s e t t i n g ( A c t i v e g r o u p = * )
1 = G r o u p 1 2 = G r o u p 2 3 = G r o u p 3 4 = G r o u p 4
5 = G r o u p 5 6 = G r o u p 6 7 = G r o u p 7 8 = G r o u p 8
Press the group number to change the settings and display the "Protection" screen.
/ 4
L i n e p a r a m e t e r
( G r o u p * )
1 =
2 = T r p i
3 = A u t o r c l o s e e
P r o t e c t i o n
Setting the line parameters
Enter the line name, VT&CT ratio and settings for the fault locator as follows:
188
6 F 2 S 0 8 5 1
Press 1 (= Line parameter) on the "Protection" screen to display the "Line parameter" screen.
/ 5 L i n e p a r a m e t e r ( G r o u p * )
1 = L i n e n a m e
2 = V T & C T r a t i o
3 = F a u l t l o c a t o r
Press 1 (= Line name) to display the "Line name" screen.
Enter the line name as a text string.
Press the END key to return the display to the "Line parameter" screen.
Press 2 (= VT&CT ratio) to display the "VT&CT ratio" screen.
Enter the VT ratio for protection function and press the ENTER key.
Enter the VTs1 ratio and/or VTs2 ratio for autoreclose function and press the
ENTER
key.
VTs1 is used for the VT ratio setting for voltage and synchronism check of autoreclose
function. VTs2 is used for the VT ratio setting for the other voltage and synchronism check at
the time of two-breaker autoreclose.
Enter the CT ratio for protection function and press the ENTER key.
Press the END key to return the display to the "Line parameter" screen.
Press 3 (= Fault locator) to display the "Fault locator" screen.
/ 6 F a u l a l c o 1 / 5 1 t t o r
R 1 ( 0 . 9 9 . ) 9 9 0 0 0 0 - 1 : . 2
R 0 0 ( 0 . 0 0 9 9 . ) 9 9 0 - 1 : . 2
K b a ( 1 ) 0 2 8 0 0 - : 1 % 0
( L i n e 0 . 0 3 9 9 ) 9 . 0 - 8 : . m k 0
X 1 ( 0 . 9 9 . ) 9 9 1 0 0 0 - 1 : . 0 0
X 0 ( 0 . 0 0 9 9 . ) 9 9 4 - 1 : . 0 3 0
1 X 0 ( 0 m . 0 9 9 . ) 9 9 2 - 0 : . 0 0
L ( Z O B - 0 . 0 9 9 . ) 9 9 0 - 1 : . 0 0 1 0
B Z 0 ( 0 . 0 0 0 - : . 0 9 9 . ) 9 9 1 - R 1 0
K c b ( 1 ) 0 2 8 0 0 - : 1 % 0
K a c ( 1 ) 0 2 8 0 0 - : 1 % 0
K a ( 1 ) 0 2 8 0 0 - : 1 % 0
K b ( 1 ) 0 2 8 0 0 - : 1 % 0
K c ( 1 ) 0 2 8 0 0 - : 1 % 0
( T N F L . 0 0 0 0 . ) 0 0 . - 2 : 0 s
B 0 2 3
Enter the setting and press the ENTER key for each item.
Press the END key after completing the settings to return the display to the "Line
parameters" screen.
Setting the protection function
To set the protection schemes, scheme switches and protection elements, do the following.
Protection elements are the measuring elements and timers.
189
6 F 2 S 0 8 5 1
Note: Depending on the selected protection scheme and scheme switch setting, some of the scheme
switches and protection elements are not used and so need not be set. The protection function
setting menu of the GRZ100 does not display unnecessary setting items. Therefore, start by
setting the protection scheme, then set the scheme switch, then the protection elements.
As a result of the above, note that some of the setting items described below may not appear in
the actual setting.
Press 2 (= Trip) on the "Protection" screen to display the "Trip" screen.
/ 5 T r i p ( G r o u p * )
1 = P r o t e c t i o n s c h e m e
2 = S c h e m e s w i t c h
3 = P r o t e c t i o n e l e m e n t
Protection scheme setting
Press 1 (= Protection scheme) on the "Trip" screen to display the "Protection scheme" screen.
/ 6 P r o t e c t i o n s c h e m e
1 = 3 Z O N E 2 = Z 1 - E X T 3 = P U P 4 = P O P 5 = U O P 6 = B O P
7 = P O P + D E F 8 = U O P + D E F 9 = B O P + D E F
C u r r e n t N o . = 2 S e l e c t N o . =
0 = P U P + D E F 1
Select the protection scheme to be used by entering the number corresponding to the
protection scheme and press the ENTER key.
Press the END key to return to the "Trip" screen.
Setting the scheme switches
Press 2 (= Scheme switch) on the "Trip" screen to display the "Scheme switch" screen.
190
6 F 2 S 0 8 5 1
Enter the number corresponding to the switch status to be set and press the ENTER key for
each switch.
191
6 F 2 S 0 8 5 1
After setting all switches, press the END key to return to the "Trip" screen.
Setting the protection elements
Press 3 (= Protection element) to display the "Protection element" screen.
/ 6 P r o t e c t i o n e l e m e n t ( G r o u p * )
1 = D i s t a n c e 2 = P S B & O S T 3 = O C , D E F & U V
4 = C o m m a n d t r i p
<Distance>
Press 1 (= Distance) to display the "Distance" screen. The measuring elements and timers used
in the distance protection are set using this screen.
192
6 F 2 S 0 8 5 1
193
6 F 2 S 0 8 5 1
Enter the numerical value and press the ENTER key for each element.
After setting all elements, press the END key to return to the "Protection element" menu.
<PSB&OST>
Press 2 (= PSB&OST) to display the "PSB & OST" screen. The measuring elements and
timers used in the power swing blocking and out-of-step tripping are set using this screen.
Enter the numerical value and press the ENTER key for each element.
After setting all elements, press the END key to return to the "Protection element" menu.
<OC, DEF&UV>
Press 3 (= OC, DEF&UV) to display the "OC, DEF&UV" screen. The overcurrent,
undervoltage and directional earth fault elements and timers are set using this screen.
194
6 F 2 S 0 8 5 1
Enter the numerical value and press the ENTER key for each element.
After setting all elements, press the END key to return to the "Protection element" menu.
<Command trip>
Press 4 (= Command trip) to display the "Command trip" screen. The timers used in the
command protection are set using this screen(*).
195
6 F 2 S 0 8 5 1
T C H D ( 0 - 5 0 ) : 1 2 m s
T D E F R ( 0 . 0 0 - 0 . 3 0 ) : 0 . 0 0 s
/ 7 C o m m a n d t r i p 1 / 7
T D E F F ( 0 . 0 0 - 0 . 3 0 ) : 0 . 0 0 _ s
T S B C T ( 0 . 0 0 - 1 . 0 0 ) : 0 . 1 0 s
T R E B K ( 0 . 0 0 - 1 0 . 0 0 ) : 0 . 1 0 s
T E C C B ( 0 . 0 0 - 2 0 0 . 0 0 ) : 0 . 1 0 s
T C H D E ( 0 - 5 0 ) : 2 0 m s
Enter the numerical value and press the ENTER key for each timer.
After setting all timers, press the END key to return to the "Protection element setting"
menu.
(*) As described in the "Notes on setting", if the protection scheme is set to 3ZONE, Z1-EXT, PUP,
POP or UOP, no setting items are displayed in the "Command trip" screen. Press the END key
to return to the upper screen.
Setting the autoreclose function
To set the autoreclose mode, scheme switches and autoreclose elements, do the following:
Note: Depending on the autoreclose mode and scheme switch setting, some of the scheme switches
and autoreclose elements are not used and so do not need to be set. The autoreclose function
setting menu of the GRZ100 does not display unnecessary setting items. Therefore, start by
setting the autoreclose mode, and proceed to set the scheme switch, then the autoreclose
elements.
As a result of the above, note that some of the setting items described below may not appear in
the actual setting.
Press 3 (= Autoreclose) on the "Protection" screen to display the "Autoreclose" screen.
/ 5 A u t o r e c l o s e ( G r o u p * )
1 = A u t o r e c l o s e m o d e
2 = S c h e m e s w i t c h
3 = A u t o r e c l o s e e l e m e n t
Setting the Autoreclose mode
Press 1 (= Autoreclose mode) to display the "Autoreclose mode" screen.
/ 6 A u t o r e c l o s e m o d e
1 = D i s a e l b 2 = S P A R 3 = T P R A 4 =
5 = E X T 1 P
C u r r e n t N o . = 4 S e l e c t N o . =
S P A & R T P R A
3 = E X T 3 P
Select the autoreclose mode to be used by entering the number corresponding to the
autoreclose mode and press the ENTER key.
Press the END key to return to the "Autoreclose" screen.
Setting the scheme switches
Press 2 (= Scheme switch) to display the "Scheme switch" screen.
196
6 F 2 S 0 8 5 1
/ 6 S c h e m e s w i t c h 1 / 0
A R C - E X T 0 = O f f 1 = O n 0
A R C - D E F 0 = O f f 1 = O n 0
V C H K 0 = O f f 1 = L B 2 = D B 3 = S Y 1
A R C - S M 0 = O f f 1 = S 2 2 = S 3 3 = S 4 0
V T P H S E L 1 = A 2 = B 3 = C 1
V T - R A T E 1 = P H / G 2 = P H / P H 1
3 P H - V T 1 = B u s 2 = L i n e 1
A R C - B U 0 = O f f 1 = O n 0
A R C - S U C 0 = O f f 1 = O n 0
U A R C S W P 1 = P 1 3 2 = P 2 1 3 =
1
Enter the number corresponding to the switch status to be set and press the ENTER key for
each switch.
After setting all switches, press the END key to return to the "Autoreclose" screen.
Setting the autoreclose elements
Press 3 (= Autoreclose element) to display the "Autoreclose element" screen.
/ 6 A u t o r e c o s e e l e m e n t ( G r o u p * )
1 = A u t o r e c l o s e t i m e r
2 = S y n c h r o c h e c k
l
<Autoreclose timer>
Press 1 (= Autoreclose timer) to display the "Autoreclose timer" screen.
T S P R 1 ( 0 . 0 1 - 1 0 . 0 ) : 0 . 8 0 s
T R D Y 1 ( 5 - 3 0 0 ) : 6 0 s
/ 7 A u t o r e c l o s e t i m e r 1 / 1 3
T E V L V ( 0 . 0 1 - 1 0 . 0 ) : 1 . 0 0 _ s
T R R ( 0 . 0 1 - 1 0 0 . 0 0 ) : 2 . 0 0 s
T T P R 1 ( 0 . 0 1 - 1 0 0 . 0 0 ) : 0 . 6 0 s
T S 2 ( 5 . 0 - 3 0 0 . 0 ) : 2 0 . 0 s
T S 2 R ( 5 . 0 - 3 0 0 . 0 ) : 3 0 . 0 s
T S 3 ( 5 . 0 - 3 0 0 . 0 ) : 2 0 . 0 s
T S 4 ( 5 . 0 - 3 0 0 . 0 ) : 2 0 . 0 s
T S 4 R ( 5 . 0 - 3 0 0 . 0 ) : 3 0 . 0 s
T W 1 ( 0 . 1 - 1 0 . 0 ) : 0 . 3 s
T S 3 R ( 5 . 0 - 3 0 0 . 0 ) : 3 0 . 0 s
T S U C ( 0 . 1 - 1 0 . 0 ) : 3 . 0 s
Enter the numerical value and press the ENTER key for each timer.
After setting all timers, press the END key to return to the "Autoreclose element" menu.
<Synchrocheck>
Press 2 (= Synchrocheck) to display the "Synchrocheck" screen for voltage check and
synchronism check elements.
197
6 F 2 S 0 8 5 1
O V L 1 ( 1 0 - 1 5 0 ) : 5 1 V
U V B ( 1 0 - 1 5 0 ) : 1 3 V
/ 7 S y n c h r o c h e c k 1 / 1 1
O V B ( 1 0 - 1 5 0 ) : 5 1 _ V
S Y 1 U V ( 1 0 - 1 5 0 ) : 8 3 V
U V L 1 ( 1 0 - 1 5 0 ) : 1 3 V
S Y 1 ( 5 - 7 5 ) : 3 0 d e g
T S Y N 1 ( 0 . 0 1 - 1 0 . 0 0 ) : 0 . 0 1 s
T D B L 1 ( 0 . 0 1 - 1 . 0 0 ) : 0 . 0 1 s
T L B D 1 ( 0 . 0 1 - 1 . 0 0 ) : 0 . 0 1 s
S Y 1 O V ( 1 0 - 1 5 0 ) : 5 1 V
T 3 P L L ( 0 . 0 1 - 1 . 0 0 ) : 0 . 0 5 s
Enter the numerical value and press the ENTER key for each element.
After setting all elements, press the END key to return to the "Autoreclose element" menu.
Setting group copy
To copy the settings of one group and overwrite them to another group, do the following:
Press 3 (= Copy group) on the "Protection" screen to display the "Copy group A to B" screen.
/ 3 C o p y g r o u p A t o B ( A c t i v e g r o u p = * )
A ( 1 - 8 )
B ( 1 - 8 )
Enter the group number to be copied in line A and press the ENTER key.
Enter the group number to be overwritten by the copy in line B and press the ENTER key.
4.2.6.8 Binary Input
The logic level of binary input signals can be inverted by setting before entering the scheme logic.
Inversion is used when the input contact cannot meet the requisite described in the Table 3.2.2.
Press 7 (= Binary input) on the "Setting (change)" sub-menu to display the "Binary input"
screen.
B I S W 4 1
B I S W 5 1
B I S W 1 6 1
B I S W 1 7 1
B I S W 1 8 1
B I S W 2 6 1
B I S W 2 7 1
B I S W 2 8 1
/ 2 B i n a r y i n p u t
1 = N o r m 2 = I n v
1 /
B I S W 1 1
B I S W 2 1
B I S W 3 1
B I S W 3 4 1
B I S W 3 5 1
B I S W 3 6 1
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
1 = N o r m 2 = I n v
198
6 F 2 S 0 8 5 1
Enter 1 (= Normal) or 2 (= Inverted) and press the ENTER key for each binary input.
4.2.6.9 Binary Output
All the binary outputs of the GRZ100 except the tripping command, signal for command
protection and relay failure signal are user-configurable. It is possible to assign one signal or up to
6 ANDing or ORing signals to one output relay. Available signals are listed in Appendix B.
It is also possible to attach a delayed drop-off delay time of 0.2 seconds to these signals. The delay
drop-off time is disabled by the scheme switch [BOTD].
Appendix D shows the factory default settings.
To configure the binary output signals, do the following:
Selection of output module
Press 8 (= Binary output) on the "Setting (change)" screen to display the "Binary output"
screen. The available output module(s) will be shown. (The screen differs depending on the
relay model.)
/ 2 B i n a r y o u t p u t
1 = I O # 2 = I O # 2 3
Press the number corresponding to the selected output module to display the "Binary output"
screen.
/ 3 B i n a r y o u t p u t ( * * * * * )
S e l e c t B O ( 1 - * * )
S e l e c t N o . =
Note: This setting is required for all of the binary outputs. If any of the binary output is not used, enter
0 to the logic gates #1-#6 in assigning signals.
Selecting the output relay
Enter the output relay number and press the ENTER key to display the "Setting" screen.
/ 4 S e t t i n g ( B O 1 o f I O # 2
1 = L o g i c g a t e t y p e & d e l a y t i m e r
2 = I n p u t t o l o g i c g a t e
)
Setting the logic gate type and timer
Press 1 to display the "Logic gate type and delay timer" screen.
/ 5 L o g i c g a t e t y p e & d e l a y t i m e r 1 / 2
L o g i c 1 = O R 2 = A N D 1
B O T D 0 = O f f 1 = O n 1
Enter 1 or 2 to use an OR gate or AND gate and press the ENTER key.
Enter 0 or 1 to add 0.2s delayed drop-off time to the output relay if required and press the
ENTER key.
199
6 F 2 S 0 8 5 1
Press the END key to return to the "Setting" screen.
Assigning signals
Press 2 on the "Setting" screen to display the "Input to logic gate" screen.
/ 5 I n p u t t o l o g i c g a t e 1 / 6
I n # 1 ( 0 - 0 7 1 ) 2 1
I n # 2 ( 0 - 0 7 1 ) 4
I n # 3 ( 0 - 0 7 1 ) 6 7
I n # 4 ( 0 - 0 7 1 ) 0
I n # 5 ( 0 - 0 7 1 ) 0
I n # 6 ( 0 - 0 7 1 ) 0
3
3
3
3
3
3
Assign signals to gates (In #1- #6) by entering the number corresponding to each signal
referring to Appendix B.
Note: If signals are not assigned to all the gates #1-#6, enter 0 to the unassigned gate(s).
Repeat this process for the outputs to be configured.
4.2.6.10 LED
Four LEDs of the GRZ100 are user-configurable. Each is driven via a logic gate which can be
programmed for OR gate or AND gate operation. Further, each LED has a programmable reset
characteristic, settable for instantaneous drop-off, or for latching operation. The signals listed in
Appendix B can be assigned to each LED as follows.
Selection of LED
Press 9 (= LED) on the "Setting (change)" screen to display the "LED" screen.
/ 2 L E D
S e l e c t L E ( 1 - D 4 )
S e l e c t N o . =
Enter the LED number and press the ENTER key to display the "Setting" screen.
/ 3 S e t t i n g ( L E D 1 )
1 = L o g i c g a t e t y p e & r e s e t
2 = I n p u t t o l o g i c g a t e
Setting the logic gate type and reset
Press 1 to display the "Logic gate type and reset" screen.
/ 4 L o g i c g a t e t y p e & r e s e t 1 / 2
L o g i c 1 = O R 2 = A N D 1
R e s e 0 = I n s t t 1 = L a 1 t c h
Enter 1 or 2 to use an OR gate or AND gate and press the ENTER key.
Enter 0 or 1 to select Instantaneous reset or Latch reset and press the ENTER key.
Press the END key to return to the "Setting" screen.
200
6 F 2 S 0 8 5 1
Note: To release the latch state, refer to Section 4.2.1.
Assigning signals
Press 2 on the "Setting" screen to display the "Input to logic gate" screen.
/ 4 I n p u t t o l o g i c g a t e 1 / 4
I n # 1 ( 0 - 0 7 1 ) 2 1
I n # 2 ( 0 - 0 7 1 ) 4
I n # 3 ( 0 - 0 7 1 ) 6 7
I n # 4 ( 0 - 0 7 1 ) 0
3
3
3
3
Assign signals to gates (In #1- #4) by entering the number corresponding to each signal
referring to Appendix B.
Note: If signals are not assigned to all the gates #1-#4, enter 0 to the unassigned gate(s).
Repeat this process for other LEDs to be configured.
4.2.7 Testing
The sub-menu "Test" provides such functions as setting of test switches, manual starting of
automatic tests, forced operation of binary outputs, time measurement of the variable setting timer
and logic signal observation. The password must be entered in order to enter the test screens
because the "Test" menu has password security protection. (See the section 4.2.6.2.)
4.2.7.1 Setting the Switches
The automatic monitor function (A.M.F.) can be disabled by setting the switch [A.M.F] to "Off."
Disabling the A.M.F. inhibits trip blocking even in the event of a failure in the items being
monitored by this function. It also prevents failures from being displayed on the "ALARM" LED
and LCD described in Section 4.2.1. No events related to the A.M.F. are recorded, either.
Disabling A.M.F. is useful for blocking the output of unnecessary alarms during testing.
Note: Set the switch [A.M.F] to "Off" before applying the test inputs, when the A.M.F is disabled.
When a three-phase voltage source is not available, the distance measuring element operation can
be tested using a single-phase voltage source by setting the switch [Z1S-1PH] to "On". This is not
fit for the high-accuracy test, though.
The switch [ZB-CTRL] is used to test the Z1 characteristic with offset or not. When the switch
[ZB-CTRL] is set to "1", the Z1 is an offset characteristic. When the switch [ZB-CTRL] is set to
"2", the Z1 is a characteristic without offset.
Offset
characteristic
(setting "1")
X
R
X
(b) Quadrilateral (a) Mho
Figure 4.2.7.1 Z1 Characteristics by [ZB-CTRL] Setting
The gradient characteristic of Zone 1 and Zone 1X reactance elements is obtained only when the
201
6 F 2 S 0 8 5 1
load current is transmitted from local to remote terminal. So, the switch [XANGLE] is used to fix
the gradient characteristic for testing. When testing, the switch [XANGLE] is set to "1".
R
Z1S1 or Z1G1
X
Figure 4.2.7.2 Gradient Characteristic of Zone 1 and Zone 1X
DOCN element can operate during a power swing condition. So, to test the DOCN characteristic,
the switch [DOCN-C] is used. When testing, the switch [DOCN-C] is set to "1".
The switches [Z1S-1PH], [ZB-CTRL], [XANGLE] and [DOCN-C] are implemented only for the
function test.
While the switch [A.M.F] is set to "0", [Z1S-1PH] is set to "1", [ZB-CTRL] is set to "1" or "2",
[XANGLE] is set to "1", [DOCN-C] is set to "1", the red "TESTING" LED is lit for alarming.
Caution: Be sure to restore these switches after the tests are completed.
Disabling automatic monitoring
Press 5 (= Test) on the top "MENU" screen to display the "Test" screen.
/ 1 T e s t
1 = S w i t c h 2 = M a n u a l t e s t
3 = B i n a r y o u t p u t 4 = T i m e r
5 = L o g i c c i r c u i t
Press 1 (= Switch) to display the Switch screen.
Enter 0 for A.M.F to disable the automatic monitoring function and enter 1 for Z1S-1PH to
enable the test to use a single-phase voltage source.
/ 2 S w i t c h 1 / 8
A . M . F 1
Z 1 S - 1 H
D O C N - C 0 O f f
T H M R S T 0
U V T E S T 0
I E C T S T 0
Z B - C T L 0
=
X A N G L
.
P
R
E
0 = O f f
0 = O f f
0 = O f f
0 = O f f
0 = O f f
0 = O f f
0 = N o r m 1 = O F S T
1 = O n
1 = O n
1 = O n
1 = O n
1 = O n
1 = O n
1 = O n
2 = N o n - O F S T
0
0
0
Testing the offset characteristic of Z1
Enter 0 for A.M.F to disable the automatic monitoring function and enter 1 for ZB-CTRL to
modify the offset characteristic forcibly.
Press the END key to return to the "Test" screen.
Testing the gradient characteristic of Zone 1 and Zone 1X
Enter 0 for A.M.F to disable the automatic monitoring function and enter 1 for XANGLE to
modify the gradient characteristic forcibly.
202
6 F 2 S 0 8 5 1
Press the END key to return to the "Test" screen.
Testing the characteristic of DOCN
Enter 0 for A.M.F to disable the automatic monitoring function and enter 1 for DOCN-C to
enable the DOCN element to operate.
Press the END key to return to the "Test" screen.
IECTST
Enter 1(=On) for IECTST to transmit test mode to the control system by IEC60870-5-103
communication when testing the local relay, and press the
ENTER
key.
Press the END key to return to the "Test" screen.
THMRST
The switch [THMRST] is used to set the reset delay time to instantaneous reset or not and to test
the hot curve characteristic of THM. The function is active when the [THMRST] is ON.
Enter 1(=On) for testing the thermal overload element, and press the
ENTER
key.
Press the END key to return to the "Test" screen.
UVTEST
Enter 0(=Off) or 1(=On) to set disable/enable the UV blocking (UVBLK) and press the
ENTER key.
Press the END key to return to the "Test" screen.
4.2.7.2 Manual Testing
The automatic test of the telecommunication circuit can be performed manually by key operations.
The manual test performed here is also counted as the count displayed in Section 4.2.3.4.
Press 2 (= Manual test) on the "Test" screen to display the "Manual test" screen.
/ 2 M a n u a l t e s t
1 = T e l e c o m m c h a n n e l t e s t
P r e s s n u m b e r t o s t a r t t e s t .
Performing the signal channel test
Press 1 on the "Manual test" screen to start the test. The display shown below appears.
/ 2 M a n u a l t e s t
T e l e c o m m c h a n n e l t e s t i n g . . .
If the test is completed normally, the display shown below appears on the LCD for 5 seconds and
then changes to the "Manual test" screen.
203
6 F 2 S 0 8 5 1
/ 2 M a n u a l t e s t
C o m p l e t e d .
T e l e c o m m c h a n n e l t e s t i n g . . .
If an abnormality is found during testing, the LCD displays the following indication for 5 seconds
and returns to the "Manual test" screen. The "ALARM" LED remains lit.
/ 2 M a n u a l t e s t
R e m o t e 1 f
T e l e c o m m c h a n n e l t e s t i n g . . .
a i l e d .
Note: Under any of the following conditions, the test will not start. Neither "Completed" nor the
"Failed" screen is displayed.
- BOP is not selected as the protection scheme.
- Telecommunication equipment is out of service.
- Scheme switch [CHMON] is set to "OFF."
- Circuit breaker is open.
4.2.7.3 Binary Output Relay
It is possible to forcibly operate all binary output relays for checking connections with the external
devices. Forced operation can be performed on one or more binary outputs at a time for each
module.
Press 2 (= Binary output) on the "Test" screen to display the "Binary output" screen.
/ 2 B i n a r y o u t p u t
1 = I O # 2 = I O # 3 = I O # 1 2 3
The LCD displays the output modules installed depending on the model.
Enter the selected number corresponding to each module to be operated. Then the LCD
displays the name of the module, the name of the output relay, the name of the terminal block
and the terminal number to which the relay contact is connected.
/ 3 B O ( 0 = D i s a b l e 1 = E n a b l e ) 1 / 1 4
I O # B O 1 1
I O # B O 2 1
I O # B O 3 1
I O # B O 4 0
I O # B O 5 0
I O # B O 6 0
I O # B O 7 0
I O # B O 8 0
I O # B O 9 0
I O # B O 1 0 0
I O # B O 1 1 0
I O # B O 1 2 0
I O # F A I L 0
I O # 0 B O 1 3
2
2
2
2
2
2
2
2
2
2
2
2
2
2
204
6 F 2 S 0 8 5 1
Enter 1 and press the ENTER key to operate the output relays forcibly.
After completing the entries, press the END key. Then the LCD displays the screen shown
below.
/ 3 B O
K e e p p r e s s i n o t 1 g o p e r a t e .
P r e s s C A N C E L t o c a n c e l .
Keep pressing the 1 key to operate the assigned output relays.
Release pressing the 1 key to reset the operation.
Press the CANCEL key to return to the upper screen.
4.2.7.4 Timer
The pick-up or drop-off delay time of the variable timer used in the scheme logic can be measured
with monitoring jacks A and B. Monitoring jacks A and B are used to observe the input signal and
output signal to the timer respectively.
Press 4 (= Timer) on the "Test" screen to display the "Timer" screen.
/ 2 T i m e r 1 / 1
T i m e r ( 1 - 6 0 ) 1
Enter the number corresponding to the timer to be observed and press the ENTER key. The
timers and related numbers are listed in Appendix C.
Press the END key to display the following screen.
/ 2 T i m e r
P r e s s E N T E R t o o p e r a t e .
P r e s s C A N C E L t o c a n c e l .
Press the ENTER key to operate the timer. The "TESTING" LED turns on, and the timer is
initiated and the following display appears. The input and output signals of the timer can be
observed at monitoring jacks A and B respectively. The LEDs above monitoring jacks A or B
are also lit if the input or output signal exists.
/ 2 T i m e r
O p e r a t i n g . . .
P r e s s E N D t o r e s e t .
P r e s s C A N C E L t o c a n c e l .
Press the CANCEL key to test other timers.
Press the END key to reset the input signal to the timer. The "TESTING" LED turns off.
To measure the drop-off delayed time, press the END key after the LED above jack B lights.
4.2.7.5 Logic Circuit
It is possible to observe the binary signal level on the signals listed in Appendix B with monitoring
205
6 F 2 S 0 8 5 1
jacks A and B.
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
/ 2 L o g i c c i r c u i t 1 / 2
T e r m A ( 0 - 0 7 1 ) 1
T e r m B ( 0 - 0 7 1 ) 4 8
3
3
Enter a signal number to be observed at monitoring jack A and press the ENTER key.
Enter the other signal number to be observed at monitoring jack B and press the ENTER key.
After completing the setting, the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
On screens other than the above screen, observation with the monitoring jacks is disabled.
206
6 F 2 S 0 8 5 1
4.3 Personal Computer Interface
The relay can be operated from a personal computer using an RS232C port on the front panel. On
the personal computer, the following analysis and display of the fault voltage and current are
available in addition to the items available on the LCD screen.
Display of voltage and current waveform: Oscillograph, vector display
Symmetrical component analysis: On arbitrary time span
Harmonic analysis: On arbitrary time span
Frequency analysis: On arbitrary time span
4.4 Communication Interface
The relay can be provided with the following communication interfaces:
- RSM100 (Relay Setting and Monitoring)
- IEC 60870-5-103
- IEC 61850
4.4.1 RSM (Relay Setting and Monitoring System)
The Relay Setting and Monitoring (RSM) system is a system that retrieves and analyses the data
on power system quantities, fault and event records and views or changes settings in individual
relays via a telecommunication network using a remote PC.
For the details, see the separate instruction manual "PC INTERFACE RSM100".
Figure 4.4.1.1 shows the typical configuration of the RSM system via a protocol converter
G1PR2. The relays are connected through twisted pair cables, and the maximum 256 relays can be
connected since the G1PR2 can provide up to 8 ports. The total length of twisted pair wires should
not exceed 1200 m. Relays are mutually connected using an RS485 port on the relay rear panel and
connected to a PC RS232C port via G1PR2. Terminal resistor (150 ohms) is connected the last
relay. The transmission rate used is 64 kbits/s.
Figure 4.4.1.2 shows the configuration of the RSM system with Ethernet LAN (option). The relays
are connected to HUB through UTP cable using RJ-45 connector at the rear of the relay. The relay
recognizes the transmission speed automatically.
In case of the optional fiber optic interface (option), the relays are connected through graded-index
multi-mode 50/125m or 62.5/125m type optical fiber using ST connector at the rear of the
relay.
207
6 F 2 S 0 8 5 1
G1PR2
Twisted paired
cable
Figure 4.4.1.1 Relay Setting and Monitoring System (1)
PC
HUB.
UTP cable
(10Base-T or
100Base TX)
100/110/115/120V
214B-13- 10
Other
relays
Relay
Figure 4.4.1.2 Relay Setting and Monitoring System (2)
4.4.2 IEC 60870-5-103 Interface
The relay can support the IEC60870-5-103 communication protocol. This protocol is mainly used
when the relay communicates with substation automation system and is used to transfer the
following measurand, status data and general command from the relay to the control system.
Measurand data: current, voltage, active power, reactive power, frequency
Status data: events, fault indications, etc.
The IEC60870-5-103 function in the relay can be customized with the original software IEC103
configurator. It runs on a personal computer (PC) connected to the relay, and can help setting of
Time-tagged messages, General command, Metering, etc. For details of the setting method, refer
to IEC103 configurator manual. For the default setting of IEC60870-5-103, see Appendix N.
The protocol can be used through the RS485 port on the relay rear panel and can be also used
through the optional fibre optical interface.
The relay supports two baud-rates 9.6kbps and 19.2kbps.
The data transfer from the relay can be blocked by the setting.
For the settings, see the Section 4.2.6.4.
208
6 F 2 S 0 8 5 1
4.4.3 IEC 61850 Interface
The relay can also communicate with substation automation system via Ethernet communication
networks using IEC 61850 protocols.
Figure 4.4.3.1 Substation Automation System using Ethernet-based IEC 61850 protocol
4.5 Clock Function
The clock function (Calendar clock) is used for time-tagging for the following purposes:
Event records
Disturbance records
Fault records
Metering
Automatic supervision
Display of the system quantities on the digest screen
Display of the fault records on the digest screen
Display of the automatic monitoring results on the digest screen
The calendar clock can run locally or be synchronised with the external IRIG-B time standard
signal, RSM or IEC clock, etc. This can be selected by setting.
If it is necessary to synchronise with the IRIG-B time standard signal, it is possible to transform
GMT to the local time by setting.
When using time synchronisation via Ethernet according to SNTP server, the maximum four
SNTP servers can be connected. If More than one SNTP is set, priority to servers is decided in
ascending order of synchronised stratum value (in order of higher-accuracy) and the server of
smallest value is selected.
When the relays are connected to the RSM system as shown in Figure 4.4.1.1, the calendar clock
of each relay is synchronised with the RSM clock. If the RSM clock is synchronised with the
external time standard (GPS clock etc.), then all the relay clocks are synchronised with the
external time standard.
209
6 F 2 S 0 8 5 1
5. Installation
5.1 Receipt of Relays
When relays are received, carry out the acceptance inspection immediately. In particular, check
for damage during transportation, and if any is found, contact the vendor.
Check that the following accessories are attached.
3 pins for the monitoring jack, packed in a plastic bag.
An attachment kit required in rack-mounting, if ordered. (See Appendix F.)
1 large bracket with 5 round head screws, spring washers and washers (M410)
1 small bracket with 3 countersunk head screws (M46)
2 bars with 4 countersunk head screws (M38)
Always store the relays in a clean, dry environment.
5.2 Relay Mounting
Either a rack or flush mounting relay is delivered as designated by the customer. The GRZ100
models are classified into two types by their case size, type A and type B. Appendix F shows the
case outlines.
If the customer requires a rack-mounting relay, support metal fittings necessary to mount it in the
19-inch rack are also supplied with the relay.
When to mount the relay in the rack, detach the original brackets fixed on both sides of the relay
and seals on the top and bottom of the relay. Attach the larger bracket and smaller bracket on the
left and right side of the relay respectively and the two bars on the top and bottom of the relay.
How to mount the attachment kit, see Appendix F.
Dimensions of the attachment kits EP-101 and EP-102 is also shown in Appendix F.
5.3 Electrostatic Discharge
CAUTION
Do not take out any modules outside the relay case since electronic components on the modules
are very sensitive to electrostatic discharge. If it is absolutely essential to take the modules out of
the case, do not touch the electronic components and terminals with your bare hands.
Additionally, always put the module in a conductive anti-static bag when storing it.
5.4 Handling Precautions
A person's normal movements can easily generate electrostatic potential of several thousand volts.
Discharge of these voltages into semiconductor devices when handling electronic circuits can
cause serious damage, which often may not be immediately apparent but the reliability of the
circuit will have been reduced.
The electronic circuits are completely safe from electrostatic discharge when housed in the case.
Do not expose them to risk of damage by withdrawing modules unnecessarily.
Each module incorporates the highest practicable protection for its semiconductor devices.
However, if it becomes necessary to withdraw a module, precautions should be taken to preserve
210
6 F 2 S 0 8 5 1
the high reliability and long life for which the equipment has been designed and manufactured.
CAUTION
Before removing a module, ensure that you are at the same electrostatic potential as the
equipment by touching the case.
Handle the module by its front plate, frame or edges of the printed circuit board. Avoid
touching the electronic components, printed circuit board or connectors.
Do not pass the module to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
Place the module on an anti-static surface, or on a conducting surface which is at the same
potential as yourself.
Do not place modules in polystyrene trays.
It is strongly recommended that detailed investigations on electronic circuitry should be carried
out in a Special Handling Area such as described in the IEC 60747.
5.5 External Connections
External connections are shown in Appendix G.
Note: In wire connections of terminal block for type A case, the following connections are
recommended because a communication port is located between terminal blocks.
Communication port
(LAN port)
Wire
Relay
Top View
Wire
Terminal
block
Figure 5.5.1 Example of Wire Connection
211
6 F 2 S 0 8 5 1
6. Commissioning and Maintenance
6.1 Outline of Commissioning Tests
The GRZ100 is fully numerical and the hardware is continuously monitored.
Commissioning tests can be kept to a minimum and need only include hardware tests and
conjunctive tests. The function tests are at the users discretion.
In these tests, user interfaces on the front panel of the relay or local PC can be fully applied.
Test personnel must be familiar with general relay testing practices and safety precautions to avoid
personal injuries or equipment damage.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by monitoring which circuits
functions when the DC power is supplied.
User interfaces
Binary input circuits and output circuits
AC input circuits
Function tests
These tests are performed for the following functions that are fully software-based. Tests of the
protection schemes and fault locator require a dynamic test set.
Measuring elements
Timers
Protection schemes
Autoreclose
Metering and recording
Fault locator
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment,
telecommunication equipment and other external equipment.
The following tests are included in these tests:
On load test: phase sequence check and polarity check
Signaling circuit test
Tripping and reclosing circuit test
212
6 F 2 S 0 8 5 1
6.2 Cautions
6.2.1 Safety Precautions
CAUTION
The relay rack is provided with a grounding terminal.
Before starting the work, always make sure the relay rack is grounded.
When connecting the cable to the back of the relay, firmly fix it to the terminal block and
attach the cover provided on top of it.
Before checking the interior of the relay, be sure to turn off the power.
Failure to observe any of the precautions above may cause electric shock or malfunction.
6.2.2 Cautions on Tests
CAUTION
While the power is on, do not connect/disconnect the flat cable on the front of the printed
circuit board (PCB).
While the power is on, do not mount/dismount the PCB.
Before turning on the power, check the following:
- Make sure the polarity and voltage of the power supply are correct.
- Make sure the CT circuit is not open.
- Make sure the VT circuit is not short-circuited.
Be careful that the transformer module is not damaged due to an overcurrent or overvoltage.
If settings are changed for testing, remember to reset them to the original settings.
Failure to observe any of the precautions above may cause damage or malfunction of the relay.
Before mounting/dismounting the PCB, take antistatic measures such as wearing an earthed
wristband.
213
6 F 2 S 0 8 5 1
6.3 Preparations
Test equipment
The following test equipment is required for the commissioning tests.
1 Three-phase voltage source
1 Single-phase current source
1 Dynamic three-phase test set (for protection scheme test)
1 DC power supply
3 AC voltmeters
3 Phase angle meter
1 AC ammeter
1 DC voltmeter
1 Time counter, precision timer
1 PC (not essential)
Relay settings
Before starting the tests, it must be specified whether the tests will use the users settings or the
default settings.
For the default settings, see the following appendixes:
Appendix D Binary Output Default Setting List
Appendix H Relay Setting Sheet
Visual inspection
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected. Contact the vendor.
Relay ratings
Check that the items described on the nameplate on the front of the relay conform to the users
specification. The items are: relay type and model, AC voltage, current and frequency ratings, and
auxiliary DC supply voltage rating.
Local PC
When using a local PC, connect it with the relay via the RS232C port on the front of the relay.
RSM100 software is required to run the PC.
For the details, see the separate volume "PC INTERFACE RSM100".
214
6 F 2 S 0 8 5 1
6.4 Hardware Tests
The tests can be performed without external wiring, but a DC power supply and an AC voltage and
current source are required.
6.4.1 User Interfaces
This test ensures that the LCD, LEDs and keys function correctly.
LCD display
Apply the rated DC voltage and check that the LCD is off.
Note: If there is a failure, the LCD displays the "Auto-supervision" screen when the DC voltage is
applied.
Press the RESET key for 1 second when the LCD is off, and check that black dots appear on
the whole screen.
LED display
Apply the rated DC voltage and check that the "IN SERVICE" LED is lit in green.
Press the RESET key for 1 second when the LCD is off, and check that seven LEDs under
the "IN SERVICE" LED and two LEDs for monitoring jacks A and B are lit in red.
VIEW and RESET keys
Press the VIEW key when the LCD is off and check that the "Metering" screen is displayed
on the LCD.
Press the RESET key and check that the LCD turns off.
Keypad
Press any key on the keypad when the LCD is off and check that the LCD displays the
"MENU" screen. Press the END key to turn off the LCD.
Repeat this for all keys.
215
6 F 2 S 0 8 5 1
6.4.2 Binary Input Circuit
The testing circuit is shown in Figure 6.4.2.1.
TB
BI2
BI1
-A16
-A17
E
TB4
GRZ100
DC
power
supply
+
BI15
:
TB
BI17
BI16
BI18
:
TB
BI20
BI19
BI28
:
:
Terminal block (TB) and Terminal numbers are
depending on the relay model. Refer to Appendix G.
TB
BI35
BI34
BI36
(+)
()
Figure 6.4.2.1 Testing Binary Input Circuit
Display the "Binary input & output status" screen from the "Status" sub-menu.
/ 2 B i n a r y i n p u t & o u t p u t 3 / 8
I n p u t ( I O# 1 [ 0 0 0 0 0 0 0 0 0 0 0 0 ]
I n p u t ( I O# 2 [ 0 0 0 ]
O u t p u t ( I O 1 - t r i p ) [ 0 0 0 0 0 0 ]
O u t p u t ( I O# 3 [ 0 0 0 0 0 0 0 0 0 0 ]
O u t p u t ( I O# 4 [ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ]
)
)
O u t p u t ( I O# 2 [ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ]
I n p u t ( I O# 3 [ 0 0 0 0 0 0 0 0 0 0 ] )
)
)
)
#
I n p u t ( I O# 4 [ 0 0 0 ] )
Apply rated DC voltage to terminals of each binary input circuit.
Note: Terminal number depends on the relay model. So see Appendix G for details.
Check that the status display corresponding to the input signal changes from 0 to 1. (For the
binary input status display, see Section 4.2.4.2.)
The user will be able to perform this test for one terminal to another or for all terminals at once.
216
6 F 2 S 0 8 5 1
6.4.3 Binary Output Circuit
This test can be performed by using the "Test" sub-menu and forcibly operating the relay drivers
and output relays. Operation of the output contacts is monitored at the output terminal. The output
contact and corresponding terminal number are shown in Appendix G.
Press 3 (= Binary output) on the "Test" screen to display the "Binary output" screen. The LCD
displays the output modules installed depending on the model.
Enter the selected number corresponding to each module to be operated. The LCD will display
the name of the module, the name of the output relay, the name of the terminal block and the
terminal number to which the relay contact is connected.
Enter 1 and press the ENTER key.
After completing the entries, press the END key. The LCD will display the screen shown
below. If 1 is entered for all of the output relays, the following forcible operation can be
performed collectively.
/ 3 B O
K e e p p r e s s n i g 1 t o o p e r
C A N C E t o c a n c e l . L P r e s s
a t e .
Keep pressing the 1 key to operate the output relays forcibly.
Check that the output contacts operate at the terminal.
Release the 1 key to reset the operation.
217
6 F 2 S 0 8 5 1
6.4.4 AC Input Circuits
This test can be performed by applying known values of voltage and current to the AC input
circuits and verifying that the values applied coincide with the values displayed on the LCD
screen.
The testing circuit is shown in Figure 6.4.4.1. A three-phase voltage source and a single-phase
current source are required.
Three-phase
voltage
source
A
V
TB1
-12
-11
V V
Single-phase
current
source
DC
power
supply
+
-13
-14
TB1
-2
-1
-3
-4
-6
-5
-7
-8
-10
-9
-A16
-A17
E
TB4
I
a
I
b
I
c
GRZ100
Figure 6.4.4.1 Testing AC Input Circuit
Check that the metering data is set to be expressed as secondary values (Display value = 2) on
the "Metering" screen.
"Setting (view)" sub-menu "Status" screen "Metering" screen
If the setting is Primary (Display value = 1), change the setting in the "Setting (change)"
sub-menu. Remember to reset it to the initial setting after the test is finished.
Open the "Metering" screen in the "Status" sub-menu.
"Status" sub-menu "Metering" screen
Apply AC rated voltages and currents and check that the displayed values are within 5% of the
input values.
3I
o
3I
om
Vc
Vb
Va
218
6 F 2 S 0 8 5 1
6.5 Function Test
CAUTION
The function test may cause the output relays to operate including the tripping output relays.
Therefore, the test must be performed with tripping circuits disconnected.
6.5.1 Measuring Element
Measuring element characteristics are realized by software, so it is possible to verify the overall
characteristics by checking representative points.
Operation of the element under test is observed by the binary output signal at monitoring jacks A
or B or by the LED indications above the jacks. In any case, the signal number corresponding to
each element output must be set on the "Logic circuit" screen of the "Test" sub-menu.
/ 2 L o g 1 / 2
T e r m ( 0 - 0 7 1 ) 0
T e r m ( 0 - 0 7 1 ) 0
i c c i r c u i t
A
B
3
3
When a signal number is entered for the TermA line, the signal is observed at monitoring jack A
and when entered for the TermB line, observed at monitoring jack B.
Note: The voltage level at the monitoring jacks is +15V 3V for logic level "1" when measured by
an instrument with 10k input impedance, and less than 0.1V for logic level "0".
CAUTION
Use test equipment with more than 1 k of internal impedance when observing the
output signal at the monitoring jacks.
Do not apply an external voltage to the monitoring jacks.
In case of a three-phase element, it is enough to test a representative phase. A-phase and AB-phase
elements are selected for the earth fault element and phase fault element respectively hereafter.
219
6 F 2 S 0 8 5 1
6.5.1.1 Distance Measuring Element Z1, Z1X, Z2, Z3, Z4, ZF, ZR1, ZR2 and PSBS
Phase fault element reach test
The test voltage and current input test circuit is shown in Figure 6.5.1.1.
Three-phase
voltage
source
A
V
TB1
-12
-11
V
a
V V
Single-phase
current
source
DC
voltmeter
-13
-14
TB1
-2
-1
-3
-4
-A16
-A17
E
TB4
V
c
V
b
I
a
I
b
GRZ100
DC
power
supply
+
Monitoring
jack
A
0V
Figure 6.5.1.1 Testing Phase-Fault Element
Phase fault elements and their output signal numbers are listed below.
Measuring element Signal number
Z1S-AB 34
Z1XS-AB 37
Z2S-AB 40
Z3S-AB 43
Z4S-AB 46
ZFS-AB 577
ZR1S-AB 553
ZR2S-AB 557
ZNDS-AB 581
PSBSIN-AB 323
PSBSOUT-AB 49
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter a signal number to be observed at monitoring jack A and press the ENTER key.
220
6 F 2 S 0 8 5 1
Apply three-phase rated voltage.
Choose a test current IT by referring to the table below, the table shows the relationship
between the reach setting, test current and measuring error.
Reach setting IT Error
0.01 - 0.05
(0.1 - 0.2
25A
5A)(*)
10%
0.06 - 0.09
(0.3 - 0.4
20A
4A)
7%
0.10 - 1.00
(0.5 - 5.0
10A
2A)
5%
1.01 - 10.00
(5.1 - 50.0
5A
1A)
5%
10.01 - 20.00
(50.1 100.0
2.5A
0.5A)
5%
20.01 - 50.00
(100.1 250.0
1A
0.2A)
7%
(*) Values shown in parentheses are in the case of 1A rating.
Other values are in the case of 5A rating.
Set the voltage and current phase relationship as shown below. That is, V
a
lags Vc by 90, Vb
= - V
a
and IT lags V
a
by or + 180. is 90 when testing.
IT
90
V
b
V
c
V
a
Z1S, Z1XS, Z2S, ZFS, ZNDS, Z3S and PSB
+180
IT
V
b
V
a
V
c
ZR1S,ZR2S and Z4S
Adjust the magnitude of V
a
and V
b
while retaining the conditions above and measure the
voltage V
a
at which the element operates.
The theoretical operating voltage is obtained by 2IT ZS when the setting reach is ZS. Check
that the measured voltage is within the above-mentioned error of the theoretical voltage value
when it is expressed with 2V
a
(= V
a
V
b
).
Element reach setting (ZS) IT 2IT ZS Measured voltage (2V
a
)
Z1S
Z1XS
Z2S
Z3S
Z4S
221
6 F 2 S 0 8 5 1
ZFS
ZR1S
ZR2S
ZNDS
PSBSIN
PSBSOUT
[Testing of Zone 1 bending characteristic]
The test circuit and test method is same as above.
The operating voltage of Zone 1 bending characteristic can be calculated as follows:
X
R
(X1, R1)
1
2
0
1: Z1S1 setting angle
2: Z1S2 setting angle
sin
1
tan
tan
1
tan
tan
1
sin
1
1
2
1
1
+
= = I
X
I X V
p
where,
X
1
is the Z1S setting reach.
is the angle difference between voltage and current.
Note: Toshiba recommend that a minimum of three values for be tested to check that the
correct relay settings have been applied.
Care must be taken in choosing values of to ensure that the testing points come within
the operating boundary defined by the Z1S 2 setting and either the load blinder or mho
settings, as appropriate
222
6 F 2 S 0 8 5 1
Earth fault element reach test
The test circuit is shown in Figure 6.5.1.2.
Three-phase
voltage
source
A
V
TB1
-12
-11
V
a
Single-phase
current
source
DC
voltmeter
-13
-14
TB1
-2
-1
-7
-8
-A16
-A17
E
TB4
V
c
V
b
I
a
3I
o
GRZ100
DC
power
supply
+
Monitoring
jack
A
0V
-9
-10
3I
om
(for Zero-sequence
current of own line)
(for Zero-sequence
current of parallel line)
IT
Figure 6.5.1.2 Testing Earth-Fault Element
Earth fault elements and their output signal number are listed below.
Measuring element Signal number
Z1G-A 19
Z1XG-A 22
Z2G-A 25
Z3G-A 28
Z4G-A 31
ZFG-A 593
ZR1G-A 569
ZR2G-A 573
ZNDG-A 597
PSBGIN-A 561
PSBGOUT-A 565
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
Enter a signal number to be observed at monitoring jack A and press the ENTER key.
Apply three-phase rated voltage.
Choose a test current IT by referring to the table below, the table shows the relationship
between the reach setting, test current and measuring error.
223
6 F 2 S 0 8 5 1
Reach setting IT Error
0.01 - 0.05
(0.1 - 0.2
25A
5A)(*)
10%
0.06 - 0.09
(0.3 - 0.4
20A
4A)
7%
0.1 - 1.0
(0.5 - 5.0
10A
2A)
5%
1.01 - 10.0
(5.1 - 50.0
5A
1A)
5%
10.01 - 20.0
(50.1 - 100
2.5A
0.5A)
5%
20.01 - 50.0
(100.1 - 250
1A
0.2A)
7%
50.01 - 100
(250.1 - 500
0.6A
0.12A)
10%
(*) Values shown in parentheses are in the case of 1A rating. Other values are in the case of 5A rating.
Set the test voltage and test current phase relation as shown below. That is, V
a
, V
b
, and V
c
are
balanced, and IT lags V
a
by or + 180. is 90 when testing.
+180
ZR1G, ZR2G andZ4G
IT
V
b
V
c
V
a
Z1G, Z1XG, ZFG, ZNDG, Z2G, and Z3G
IT
V
b
V
c
V
a
Adjust the magnitude of Va while retaining the conditions above and measure the voltage at
which the element operates.
The theoretical operating voltage Vop is obtained by the following equations when the setting
reach is ZG. Check that the measured voltage is within the above-mentioned error of the
theoretical voltage.
Z1G, Z1XG, Z2G: Vop = ZG ( IT
+
K
xs
100
1
3
IT +
K
xm
100
3
IT)
ZR1G: Vop = ZG ( IT
+
K
xs
100
1
3
IT)
ZFG, Z3G, ZR2G, Z4G: Vop = IT ZG
Element ZG IT Vop Measured voltage
Z1G
Z1XG
Z2G
Z3G
Z4G
224
6 F 2 S 0 8 5 1
ZFG
ZR1G
ZR2G
ZNDG
PSBGIN
PSBGOU
T
[Testing of Zone 1 bending characteristic]
The test circuit and test method is same as above.
The operating voltage of Zone 1 bending characteristic can be calculated as follows:
X
R
(X1, R1)
1
2
0
1: Z1G1 setting angle
2: Z1G2 setting angle
sin
1
'
'
'
tan
tan
1
tan
tan
1
sin
1
'
1
2
1
1
+
= =
x
r
x
x p
I
I
I
X
I X V
where,
m
xm xs
x
I
k
I
k
I I
0 0
100 100
100
' +
+ = ,
m
rm rs
r
I
k
I
k
I I
0 0
100 100
100
' +
+ =
X
1
is the Z1G setting reach.
is the angle difference between voltage and current.
Note: Toshiba recommend that a minimum of three values for be tested to check that the
correct relay settings have been applied.
Care must be taken in choosing values of to ensure that the testing points come within
the operating boundary defined by the Z1G 2 setting and either the load blinder or mho
settings, as appropriate
6.5.1.2 Out-of-step Element OST
The testing circuit is shown in Figure 6.5.1.1.
The output signal numbers of the OST-ZM and OST-ZN elements are as follows:
Measuring element Signal number
OST-ZM 84
OST-ZN 85
The followings are the cases for OST-ZM. (The test procedure for OSTR1 and OSTR2 must be
changed in case of OST-ZN.)
225
6 F 2 S 0 8 5 1
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter 84 as a signal number to be observed at monitoring jack A and press the ENTER key.
Apply a three-phase rated voltage.
Choose a test current IT by referring to the table below, which shows the relation of setting
reach and test current.
Reach setting IT
0.2 3.0
(1 - 15
10A
2.0A)(*)
3.1 10.0
(16 - 50
5A
1.0A)
10.1 20.0
(51 - 100
2.5A
0.5A)
20.1 30.0
(101 - 150
1.5A
0.3A)
30.1 50.0
(151 - 250
1A
0.2A)
(*) Values shown in parentheses are in the case of 1A rating.
Other values are in the case of 5A rating.
OSTXF
Set the voltage and current phase relation as shown below. That is, V
a
lags V
c
by 90, V
b
=
V
a
and IT lags V
a
by 90.
90
90
V
b
V
a
V
c
IT
Adjust the magnitude of V
a
and V
b
while retaining the conditions above and measure the
voltage V
a
at which the element operates.
The theoretical operating voltage is obtained by 2IT Z
OST
when the setting reach is Z
OST
.
Check that the measured voltage is within 5% of the theoretical voltage value when it is
expressed with 2V
a
(= V
a
V
b
).
Element Z
OST
IT 2IT Z
OST
Measured voltage (2V
a
)
OSTXF
OSTXB
Set the voltage and current phase relation as shown below. That is, V
a
lags V
c
by 90, V
b
=
V
a
and IT leads V
a
by 90.
226
6 F 2 S 0 8 5 1
90
IT
V
b
V
a
V
c
Adjust the magnitude of V
a
and V
b
while retaining the conditions above and measure the
voltage V
a
at which the element operates.
The theoretical operating voltage is obtained by 2IT Z
OST
when the setting reach is Z
OST
.
Check that the measured voltage is within 5% of the theoretical voltage value when it is
expressed with 2V
a
(= V
a
V
b
).
Element Z
OST
IT 2IT Z
OST
Measured voltage (2V
a
)
OSTXB
OSTR1
Set the voltage and current phase relation as shown below. That is, Va lags Vc by 90, Vb =
Va and IT is in phase with Va.
90
IT
V
b
V
a
V
c
Adjust the magnitude of V
a
and V
b
while retaining the conditions above and measure the
voltage V
a
at which the element operates.
The theoretical operating voltage is obtained by 2IT Z
OST
when the setting reach is Z
OST
.
Check that the measured voltage is within 5% of the theoretical voltage value when it is
expressed with 2V
a
(= V
a
V
b
).
Element Z
OST
IT 2ITZ
OST
Measured voltage (2V
a
)
OSTR1
OSTR2
Set the voltage and current phase relation as shown below. That is, V
a
lags V
c
by 90, V
b
=
V
a
and IT is in counter-phase with V
b
.
90
IT
V
b
V
a
V
c
227
6 F 2 S 0 8 5 1
Adjust the magnitude of V
a
and V
b
while retaining the conditions above and measure the
voltage V
a
at which the element operates.
The theoretical operating voltage is obtained by 2IT Z
OST
when the setting reach is Z
OST
.
Check that the measured voltage is within 5% of the theoretical voltage value when it is
expressed with 2V
a
(= V
a
V
b
).
Element Z
OST
IT 2ITZ
OST
Measured voltage (2V
a
)
OSTR2
6.5.1.3 Phase Selection Element UVC
The testing circuit is shown in Figure 6.5.1.2.
UVC elements and their output signal numbers are listed below.
Measuring element Signal number
UVC-A 66
UVC-B 67
UVC-C 68
The following shows the case when testing UVC-A.
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
Enter 66 as a signal number to be observed at monitoring jack A and press the ENTER key.
Apply a three-phase rated voltage.
Set the test current IT to zero ampere and adjust the voltage. Measure the voltage at which the
element operates. Check that the voltage is within 5% of the setting UVCV. (The default
setting of the UVCV is 48 V.)
Choose a test current IT by referring to the table below, which shows the relation of setting
reach UVCZ, test current IT and measuring error.
UVCZ IT Error
0.0- 2.0
(0 - 10
10A
5A) (*)
5%
2.1 10.0
(11 - 50
5A
1A)
5%
10.1 20.0
(51 - 100
2.5A
0.5A)
5%
20.1 50.0
(101 - 250
1A
0.2A)
7%
(*) Values shown in parentheses are in the case of 1A rating. Other values are in the case of 5A
rating.
Set the test voltage and test current phase relation as shown below. That is, V
a
, V
b
, and V
c
are
balanced, and IT lags V
a
by UVC characteristic angle UVC .
(The default setting of UVC is 85.)
228
6 F 2 S 0 8 5 1
IT
V
b
V
c
V
a
Adjust the magnitude of V
a
while retaining the conditions above and measure the voltage V
a
at which the element operates.
The theoretical operating voltage is obtained by (IT UVCZ + UVCV) when the setting reach
is UVCZ. Check that the measured voltage is within the above-mentioned error of the
theoretical voltage value. (The default setting of the UVCZ is 2.0 ohm for 5A rating and 10
ohm for 1A rating.)
Element UVCV UVCZ IT ITUVCZ + UVCV Measured voltage
UVCZ
6.5.1.4 Directional Earth Fault Element DEF
The testing circuit is shown in Figure 6.5.1.2.
DEF elements and their output signal number are listed below.
Measuring element Signal number
DEFF 59
DEFR 58
The following shows the case when testing DEFF.
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
Enter 59 as a signal number to be observed at monitoring jack A and press the ENTER key.
Residual current level detection is verified as follows:
Apply three-phase rated voltage and single-phase test current IT (= 3
Io
).
Set IT to lag V
a
by DEFF characteristic angle DEF . (The default setting of DEF is 85.)
Lower V
a
to 10 V to generate a residual voltage. Changing the magnitude of IT while retaining
the phase angle with the voltages, and measure the current at which the element operates.
Check that the measured current magnitude is within 5% of the current setting.
IT
3V
o
V
b
V
c
V
a
V
a
229
6 F 2 S 0 8 5 1
Residual voltage level detection is verified as follows:
Set IT to rated current and the three-phase voltage to rated voltage. Lower the magnitude of V
a
while retaining the phase angle with the current and measure the voltage V
a
at which the
element operates. Operating residual voltage is expressed by (VR-V
a
), where VR is the rated
voltage. Check that the (VR-V
a
) is within 5% of the residual voltage setting.
6.5.1.5 Negative Sequence Directional Element DOCN
The testing circuit is shown in Figure 6.5.1.3.
DOCN elements and their output signal number are listed below.
Measuring element Signal number
DOCNF 360
DOCNR 361
The following shows the case when testing DOCNF.
Press 1 (= Switch) on the Test screen to display the switch screen and enter 1 for DOCN-C to
test the DOCN elements.
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
Enter 360 as a signal number to be observed at monitoring jack A and press the ENTER key.
Apply single-phase rated current I
a
and single-phase test voltage V.
Set V to lag I
a
by 90.
Changing the magnitude of test voltage while retaining the phase angle with the current, and
measure the voltage at which the element operates. Check that the measured voltage
magnitude is within 5% of 15.5V.
The test of the DOCNR is same as that of DOCNF except for the voltage leading the current I
a
by
90.
Single-phase
voltage
source
A
V
TB1
-11
V
a
Single-phase
current
source
-14
TB1
-2
-1
I
a
GRZ100
Monitoring
jack
A
0V
DC
voltmeter
-A16
-A17
E
TB4
DC
power
supply
+
Figure 6.5.1.3 Testing DOCN Element
230
6 F 2 S 0 8 5 1
6.5.1.6 Inverse Definite Minimum Time Overcurrent Element (IDMT) OCI, EFI
The testing circuit is shown in Figure 6.5.1.4.
Single-phase
current
source
A
TB1
-2
-1
-7
-8
I
a
3I
o
GRZ100
Monitoring
jack
A
0V
Time
counter
TB4
-A16
-A17
E
DC
power
supply
+
Start
Stop
OV
Figure 6.5.1.4 Testing IDMT
One of the four inverse time characteristics can be set, and the output signal numbers of the IDMT
are as follows:
Element Signal number
OCI-A 97
OCI-B 98
OCI-C 99
EFI 61
Fix the time characteristic to test by setting the scheme switch MEFI or MOCI on the "Scheme
switche" screen.
"Setting (change)" sub-menu "Protection" screen "Trip" screen "Scheme switch" screen
The test procedure is as follows:
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter a signal number to observe the OCI or EFI output at monitoring jack A and press the
ENTER key.
Apply a test current and measure the operating time. The magnitude of the test current should
be between 1.2 I
s
to 20 I
s
, where I
s
is the current setting.
Calculate the theoretical operating time using the characteristic equations shown in Section
2.4.5.3. Check that the measured operating time is within IEC 60255-3 class 5 for standard,
very and long-time inverse or IEC 60255-3 class 7.5 for extremely inverse.
231
6 F 2 S 0 8 5 1
6.5.1.7 Thermal overload element THM-A and THM-T
The testing circuit is same as the circuit shown in Figure 6.5.1.4.
The output signal of testing element is assigned to the monitoring jack A.
The output signal numbers of the elements are as follows:
Element Signal No.
THM-A 560
THM-T
556
To test easily the thermal overload element, the scheme switch [THMRST] in the "Switch" screen
on the "Test" menu is used.
Set the scheme switch [THMRST] to "ON".
Enter the signal number to observe the operation at the monitoring jack A as shown in Section
6.5.1.
Apply a test current and measure the operating time. The magnitude of the test current should
be between 1.2 I
s
to 10 I
s
, where I
s
is the current setting.
CAUTION
After the setting of a test current, apply the test current after checking that the THM% has
become 0 on the "Metering" screen.
Calculate the theoretical operating time using the characteristic equations shown in Section
2.4.6. Check that the measured operating time is within 5%.
6.5.1.8Broken conductor detection element BCD
The testing circuit is shown in Figure 6.5.1.5.
Three-phase
Current
source
TB1
-2
-1
-3
-4
-6
-5
I
a
I
b
GRZ100
-A16
-A17
E
TB4
DC
power
supply
+
A
I
c
A
A
DC
voltmeter
+
0V
Monitoring
jack
A
0V
Figure 6.5.1.5 Testing BCD element
The output signal of testing element is assigned to the monitoring jack A.
The output signal numbers of the elements are as follows:
232
6 F 2 S 0 8 5 1
Element Signal No.
BCD 766
Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Apply the three-phase balance current at 10% of the rated current and interrupt a phase
current.
Then, check the BCD element operates.
6.5.1.9 Overvoltage / undervoltage elements OVS1, OVS2, OVG1, OVG2, UVS1, UVS2, UVG1, UVG2
The testing circuit is shown in Figure 6.5.1.6.
TB4
-A16
-A17
E
GRZ100
DC
power
supply
+
V
TB1
+
Variable-
Voltage source
-11
-12 or
-14(*)
DC
voltmeter
+
0V
Monitoring
jack
A
0V
() TB1-12 for OVS1, OVS2, UVS1 and UVS2, TB1-14 for OVG1, OVG2, UVG1 and UVG2.
Figure 6.5.1.6 Operating Value Test Circuit
The output signal of testing element is assigned to the monitoring jack A.
Overvoltage and undervoltage elements and their output signal number are listed below.
Element Signal No.
OVS1-AB
OVS2-AB
OVG1-A
OVG2-A
UVS1-AB
UVS2-AB
UVG1-A
UVG2-A
436
439
442
445
454
457
460
463
Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Operating value test of OVS1, OVS2, OVG1, OVG2
Apply a rated voltage as shown in Figure 6.5.1.6.
Increase the voltage and measure the value at which the element operates. Check that the
measured value is within 5% of the setting.
233
6 F 2 S 0 8 5 1
Operating value test of UVS1, UVS2, UVG1, UVG2
Apply a rated voltage and frequency as shown Figure 6.5.1.6.
Decrease the voltage and measure the value at which the element operates. Check that the
measured value is within 5% of the setting.
Operating time check of OVS1, OVG1, UVS1, UVG1 IDMT curves
Apply a rated voltage at the IDMT time multiplier setting 10.0 of the relay.
Change the voltage from the rated voltage to the test voltage quickly and measure the
operating time. Test voltage: 1.5 (setting voltage) or 0.5 (setting voltage)
Calculate the theoretical operating time using the characteristic equations shown in Section
2.4.9.1 and 2.4.9.2. Check the measured operating time within 5%.
6.5.1.10 Voltage and Synchronism Check Elements
The testing circuit is shown in Figure 6.5.1.7. If scheme switch [3PH-VT] is set to "Bus", the
three-phase voltage simulates the busbar voltage, and the single-phase voltage simulates the line
voltage. If the switch is set to "Line", the opposite is true.
Three-phase
voltage
source
V
TB1
-12
-11
Single-phase
voltage
source
DC
voltmeter
-13
-14
-15
-18
-16
-17
-A16
-A17
E
TB4
V
s1
V
s2
GRZ100
DC
power
supply
+
Monitoring
jack A
A
0V
V
V
a
V
b
V
c
(*) In case of testing OVL2, UVL2, and SYN2.
(**) In case when [VT-RATE] is set to "PH/PH".
(*)
(**)
Figure 6.5.1.7 Testing Synchronism Check Elements
When testing OVL2, UVL2 and SYN2, the single-phase voltage must be applied to terminal 17
and 18, instead of 15 and 16 and 3PH-VT is set to "Line".
Voltage and synchronism check elements and their output signal number are listed below. OVL2,
UVL2 and SYN2 are used for two-breaker autoreclose and provided in Model 300 series.
Measuring element Signal number
OVB 86
UVB 87
OVL1 89
234
6 F 2 S 0 8 5 1
UVL1 90
OVL2 91
UVL2 92
SYN1 88
SYN2 93
Connect a phase angle meter to the three-phase voltages taking the scheme switch [VT-RATE]
and [VTPHSEL] setting into consideration. The phase angle meter connection shown in Figure
6.5.1.7 is the case for the default settings, that is, [VT-RATE] and [VTPHSEL] are set to "PH/G"
and "A" respectively.
[VT-RATE] setting [VTPH-SEL] setting Meter connection phase
PH/G A A-N
B B-N
C C-N
PH/PH A A-B
B B-C
C C-A
Voltage check element OVB, UVB, OVL1, UVL1, OVL2, and UVL2
Press 5 (= Logic circuit) on the "Test" screen to display the Logic circuit screen.
Enter a signal number for TermA line to observe at monitoring jack A and press the ENTER
key.
Apply three-phase rated voltage and single-phase rated voltage as shown in Figure 6.5.1.7.
OVB and UVB :
Change the magnitude of the three-phase voltage if the scheme switch [3PH-VT] is set to
"Bus" or adjust the magnitude of the single-phase voltage if it is set to "Line". Measure the
value at which the element operates and check that it is within 5% of the setting.
OVL1 and UVL1 :
Adjust the magnitude of the single-phase voltage if the scheme switch [3PH-VT] is set to
"Bus"; adjust the magnitude of the three-phase voltage if the scheme switch [3PH-VT] is set to
"Line". Measure the value at which the element operates and check that it is within 5% of the
setting.
OVL2 and UVL2 :
Adjust the magnitude of voltage applied to terminal 17 and 18 and measure the value at which
the element operates. Check that the measured value is within 5% of the setting.
Synchronism check element SYN1
Press 5 (= Logic circuit) on the Test screen to display the Logic circuit screen.
Enter a signal number for TermA line to observe at monitoring jack A and press the ENTER
key.
Apply a three-phase rated voltage and a single-phase rated voltage as shown Figure 6.5.1.7.
Voltage check:
Set the three-phase voltage to any value over the SY1OV setting. (The default setting of
235
6 F 2 S 0 8 5 1
SY1OV is 51 V.)
Whilst keeping V
s1
in-phase with V
a
, increase the single-phase voltage V
s1
from zero volt.
Measure the voltage at which the element operates. Check that the measured voltage is within
5% of the SY1UV setting.
Further increase V
s1
and measure the voltage at that the element resets. Check that the
measured voltage is within 5% of the SY1OV setting.
Phase angle check:
Set V
a
and V
s1
to any value between the SY1OV and SY1UV settings keeping V
a
in-phase
with V
s1
. Then the SYN1 element operates.
Shift the angle of V
s1
from that of V
a
, and measure the angle at which the element resets.
Check that the measured angle is within 5 of the SY1 setting. (The default setting of SY1
is 30.)
Change V
a
and V
s1
, and repeat the above.
Synchronism check element SYN2
Apply a single-phase rated voltage to terminal 17 and 18 as shown with broken lines in Figure
6.5.1.7 and set the scheme switch [3PH-VT] to "Line". The test can be performed taking the
same step as testing SYN1.
6.5.1.11 Current Change Detection Elements OCD and OCDP
The test circuit is shown in Figure 6.5.1.8.
Single-phase
current
source
A
TB1
DC
voltmeter
TB4
-1
-2
-A16
-A17
E
GRZ100
DC
power
supply
+
Monitoring
jack
A
0V
Figure 6.5.1.8 Testing Current Change Detection Element
The output signal number of the OCD and OCDP is as follows:
Measuring element Signal number
OCD-A 63
OCD-B 64
OCD-C 65
OCDP-A 357
OCDP-B 358
236
6 F 2 S 0 8 5 1
Measuring element Signal number
OCDP-C 359
Operation must be verified by abruptly changing the test current from 0 A to 1.2 Setting value or
vice versa.
OCD has a fixed setting of 0.5 A and 0.1 A for 5 A rating and 1 A rating respectively.
6.5.1.12 Level Detectors OCH, OC, EF, EFL, OVG, UVLS and UVLG, UVFS and UVFG, OCBF
Voltage or current level detectors are tested by applying voltage or current individually. A
single-phase test source is adequate for these tests.
Change the magnitude of the voltage or current applied and measure the value at which the
element operates. Check that the measured value is within 5% of the setting.
Level detectors and their output signal numbers are listed below.
Measuring element Signal number Remarks
OCH-A 55 A-phase current
OC-A 94 A-phase current
EF 60 Residual current
EFL 568 Residual current
OVG 62 Residual voltage
UVFS-AB 69 A-to-B-phase voltage
UVFG-A 75 A-phase voltage
UVLS-AB 72 A-to-B-phase voltage
UVLG-A 78 A-phase voltage
OCBF-A 81 A-phase current
237
6 F 2 S 0 8 5 1
6.5.2 Timer Test
The delayed pick-up time of the variable timer can be measured by connecting the monitoring
jacks A and B to a time counter as shown in Figure 6.5.2.1. Jacks A and B are used to observe the
input signal and output signal of the timer respectively.
Time
counter
TB4
-A16
-A17
E
GRZ100
DC
power
supply
+
Monitoring
jack
A
0V
Start
Stop
0V
B
Figure 6.5.2.1 Testing Variable Timer
Press 4 (= Timer) on the "Test" screen to display the "Timer" screen.
Enter the number corresponding to the timer to be observed. The timers and assigned numbers
are listed in Appendix C.
Enter the number corresponding to the timer output signal. The timer output signal numbers
are listed in Appendix B.
After completing both settings, press the END key to display the following screen.
/ 2
P r e s s E N T E R t o o p e r a t e .
C A N C E t o c a n c e l . L P r e s s
T i m e r
Press the
ENTER
key to operate the timer. The "TESTING" LED turns on, and the timer is
initiated and the following display appears. The input and output signals of the timer can be
observed at monitoring jacks A and B respectively. The LEDs above monitoring jacks A or B
are also lit if the input or output signal exists.
Check that the measured time is within 10 ms of the setting time.
/ 2
P r e s s E N D t o r e s e t .
C A N C E t o c a n c e l . L P r e s s
T i m e r
O p e r a t i n g . . . . . .
Press the END key to reset the input signal to the timer. The "TESTING" LED turns off.
Press CANCEL key to test other timers. Repeat the above testing.
To measure the drop-off delay time, press the END key after the LED above jack B lights. The
off-delay time is the time from a signal at the monitoring jack A resets till a signal at the
monitoring jack B resets.
238
6 F 2 S 0 8 5 1
6.5.3 Protection Scheme
In the following protection scheme tests, a dynamic test set with a three-phase voltage source and
current source is required to simulate power system pre-fault, fault and post-fault conditions.
In the following command tripping test, the remote end is not simulated and the receiving signal is
simulated by energizing a binary input circuit locally. If an end-to-end synchronized test is
possible, then it should be conducted.
The autoreclose function can be tested together with these tests. A permanent fault should be
applied to test a reclose-onto-fault.
Zone 1 tripping
This performs instantaneous or time-delayed, and single-phase or three-phase tripping depending
on the fault types, setting of trip mode control switch [Z1CNT] and autoreclose mode switch
[ARC-M].
Zone 1 tripping should be checked for the fault at 50% of the zone 1 reach setting.
Operating time is measured on operation of the trip output relay. It will typically be 1 cycle in case
of instantaneous tripping.
Check that the indications and recordings are correct.
Zone 2 tripping
Check that three-phase time-delayed final tripping is performed for all kinds of faults. Faults
should be set midway between zone 1 and zone 2.
Check that the operating time is 1-1.5 cycle plus zone 2 timer setting.
Check that the indications and recordings are correct.
Zone F tripping
Check that three-phase time-delayed final tripping is performed for all kinds of faults. Faults
should be set midway between zone 2 and zone F.
Check that the operating time is 1-1.5 cycle plus zone F timer setting.
Check that the indications and recordings are correct.
Zone 3 tripping
Check that three-phase time-delayed final tripping is performed for all kinds of faults. Faults
should be set midway between zone 2 and zone 3.
Check that the operating time is 1-1.5 cycle plus zone 3 timer setting.
Check that the indications and recordings are correct.
Zone R1 tripping
Set the scheme switches [ZR1BT] and [ZR2BT] to "On". (The [ZR1BT] and [ZR2BT] default
setting is "Off".)
Check that three-phase time-delayed final tripping is performed for all kinds of faults. Faults
should be set in the center of zone R1.
Check that the operating time is 1-1.5 cycle plus zone R1 timer setting.
Check that the indications and recordings are correct.
239
6 F 2 S 0 8 5 1
Zone R2 tripping
Set the scheme switch [ZR2BT] to "On". (The [ZR2BT] default setting is "Off".)
Check that three-phase time-delayed final tripping is performed for all kinds of faults. Faults
should be set midway zone R1 and zone R2.
Check that the operating time is 1-1.5 cycle plus zone R2 timer setting.
Check that the indications and recordings are correct.
Zone ND tripping
Set the scheme switch [ZNDBT] to "On". (The [ZNDBT] default setting is "Off".)
Check that three-phase time-delayed final tripping is performed for all kinds of faults. Faults
should be set midway zone 3 and zone ND.
Check that the operating time is 1-1.5 cycle plus zone ND timer setting.
Check that the indications and recordings are correct.
Zone 1X tripping
Set the scheme switch [SCHEME] to "Z1EXT", and [ARC-M] to "TPAR" or "SPAR&TPAR" or
"SPAR". CB ready condition (binary input signal BI10) and 52A, 52B and 52C must be
established.
Faults should be set midway between zone 1 and zone 1X.
Check that it performs instantaneous single-phase or three-phase tripping depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Check that the operating time is 1-1.5 cycle or less.
Check that the indications and recordings are correct.
Command Protection
The followings are described as default setting for binary inputs and binary outputs.
PUP tripping
Set the scheme switch [SCHEME] to "PUP".
Energize the binary input BI4 ("Trip signal") to simulate a trip permission signal reception and
apply a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
De-energize the binary input BI4 and apply a zone 2 fault. Check that PUP tripping does not occur.
Apply a zone 1 fault, and check that binary output relay BO13 ("Send signal") operates.
Check that the indications and recordings are correct.
POP tripping
Set the scheme switch [SCHEME] to "POP", [WKIT] and [ECHO] to "off".
Energize the binary input BI4 to simulate a trip permission signal reception and apply a zone 2
fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
240
6 F 2 S 0 8 5 1
Set [WKIT] and [ECHO] to "On" and apply a weak-infeed fault. Check that instantaneous tripping
is performed.
De-energize the binary input BI4 and apply a zone 2 fault. Check that POP tripping does not occur.
Apply a zone 2 fault, and check that binary output relay BO13 operates.
Set the scheme switch [ECHO] to "On".
De-energize the binary inputs BI1, BI2 and BI3 to simulate the breaker being open.
Check that binary output relay BO13 operates when the binary input BI4 is energized.
Apply a zone 4 fault (reverse fault) while the binary inputs BI1, BI2 and BI3 are energized, and
check that the binary output relay BO13 does not operate when the binary input BI4 is energized.
Check that the indications and recordings are correct.
UOP tripping
Set the scheme switch [SCHEME] to "UOP", [WKIT] and [ECHO] to "Off".
De-energize the binary input BI4 to simulate interruption of a trip block signal reception and apply
a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Set [WKIT] and [ECHO] to "On" and apply a weak-infeed fault. Check that instantaneous tripping
is performed.
Energize the binary input BI14 to simulate trip block signal reception and apply a zone 2 fault.
Check that UOP tripping does not occur.
Check that binary output relay BO13 operates in the normal condition.
Apply a zone 2 fault, and check that the BO13 resets.
Set the scheme switch [ECHO] to "On".
De-energize the binary inputs BI1, BI2 and BI3 to simulate the breaker being open.
Check that binary output relay BO13 resets when the binary input BI4 is de-energized.
Apply a zone 4 fault (reverse fault) while the binary inputs BI1, BI2 and BI3 are energized, and
check that the binary output relay BO13 remains operated when the binary input BI4 is
de-energized.
Check that the indications and recordings are correct.
BOP tripping
Set the scheme switch [SCHEME] to "BOP".
Check that the binary input BI4 is de-energized and apply a zone 2 fault.
Check that instantaneous single-phase or three-phase tripping is performed depending on the fault
types and setting of autoreclose mode selection switch [ARC-M].
Energize the binary input BI4 to simulate trip block signal reception and apply a zone 2 fault.
Check that BOP tripping does not occur.
Apply a zone 2 fault, and check that binary output relay BO13 does not operate. Apply a zone 4
fault (reverse fault), and check that BO13 operates.
Check that the indications and recordings are correct.
SOTF tripping
SOTF tripping is carried out by distance measuring element Z1 to Z4 operation or overcurrent
241
6 F 2 S 0 8 5 1
element OCH operation. Z1 to Z4 can perform the SOTF tripping by setting.
The SOTF function is activated when the breaker has been open for timer TSOTF (0 300s)
setting and active for an additional 500ms after the breaker is closed.
The SOTF function is checked as follows:
Set the scheme switch [SOTF-OC] to "On" and [SOTF-Z] to "Off".
De-energize the binary input signals BI1 to BI3 (terminal number A4, B4 and A5 of terminal block
TB4) for more than TSOTF (0 300s) setting.
Energize the binary input signals and apply a zone 1 fault at the same time.
Check that the operating time is within 1-1.5 cycle.
Set the scheme switch [SOTF-OC] to "Off" and [SOTF-Z] to "On" and repeat the above.
Breaker failure tripping
Set the scheme switch [BF1] to "T" or "TOC" and BF2 to "On".
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter a signal number 199 for the TermA line to observe the retrip signal at monitoring jack A
and 200 for the TermB line to observe the adjacent circuit breaker trip signal at monitoring
jack B and press the ENTER key.
Apply a zone 1 fault and maintain it. Check that the retrip signal is generated after the time
setting of TBF1 and the adjacent circuit breaker trip signal is generated after the time setting of
the TBF2.
Out-of-step tripping
Set the scheme switch [OST] to "On".
To simulate out-of-step, the impedance seen by the OST element must be moved slowly from the
first quadrant to the second quadrant or vice versa.
The following shows the case of the former.
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter signal number 203 for the TermA line to observe the out-of-step tripping signal at
monitoring jack A and press the ENTER key.
Apply a three-phase rated voltage and current.
Gradually lower the voltage to zero, keeping the voltage and current sources in-phase. Then
gradually raise the voltage from zero to the rated value, while keeping the phase angle of
voltage and current in anti-phase.
During this process, keep the current at the rated value.
Check that out-of-step tripping takes places at monitoring jack A.
Check that out-of-step tripping does not take place if the voltage was lowered or raised steeply
or was gradually raised while retaining the phase angle of voltage and current in-phase, not
anti-phase.
Voltage transformer failure supervision
A voltage transformer (VT) failure is detected when an undervoltage element or residual
overvoltage element operates but a current change detection element or residual overcurrent
element does not operate accordingly.
242
6 F 2 S 0 8 5 1
VT failure detection is checked as follows:
Set the circuit breaker closed condition by applying a "1" signal to binary inputs BI1, BI2 and
BI3.
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter signal number 172 for the TermA line to observe the VT failure alarm signal, and 173
for the TermB line to observe the VT failure detection signal at monitoring jack A and B. Press
the ENTER key.
Apply a three-phase rated voltage. Then, remove single-, two- or three-phase voltage. Check
that the signals are instantly observed at jack B and observed at jack A after a 10s delay.
Blocking of the voltage-dependent protection is checked as follows:
Apply a three-phase rated voltage. Then, remove single-, two- or three-phase voltage and at
the same time apply a zone 1 fault. During this process, do not change the current.
Check that neither zone 1 tripping nor command tripping takes place.
In the similar manner, apply a zone 1 extension, zone 2 or zone 3 fault and check that tripping
does not take place.
Check that VT failure is recorded on the event record.
Power swing blocking
A power swing is detected when the condition that the PSBSOUT element operates and PSBSIN
element and residual overcurrent element EFL do not operate, for a period of TPSB setting or
more.
Power swing detection is checked as follows:
Press 5 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
Enter signal number 176 for the TermA line to observe the power swing blocking signal at
monitoring jack A and press the ENTER key.
Apply a phase fault which is set to midway between PSBSIN and PSBSOUT. Check that the
signal is generated with a delay of TPSB setting after the PSBSOUT operates. The PSBSOUT
operating time will be 1-2 cycles.
Reset the fault and check that the monitoring signal resets with a 500ms delay after PSBSOUT
resets.
Apply an earth fault which is set to midway between PSBSIN and PSBSOUT. Check that the
signal is not generated.
Power swing blocking is checked as follows:
Apply a zone 1 phase fault after generating the power swing blocking signal. The blocking
signal is generated in the way as mentioned above. Check that zone 1 tripping takes place if
scheme switch [PSB-Z1] is set to "Off" and does not take place if set to "On".
In the similar manner, apply zone 1x, zone 2, zone 3, zone F, zone R1 and zone R2 faults, and
check that tripping takes place or does not take place depending on the "On" or "Off" setting of
scheme switch [PSB-Z1X], [-Z2], [-Z3], [-ZF], [-ZR1] and [-ZR2].
Check that power swing blocking is recorded on the event record.
243
6 F 2 S 0 8 5 1
6.5.4 Metering and Recording
The metering function can be checked while testing the AC input circuit. See Section 6.4.4.
Fault recording can be checked while testing the protection schemes. Open the "Fault records"
screen and check that the descriptions are correct for the applied fault.
The default setting of events is shown in Appendix H. Event recording on the external events such
as CB1 ready, Ind.reset, etc., can be checked by changing the status of binary input signals.
Change the status in the same way as the binary input circuit test (see Section 6.4.2) and check that
the description displayed on the "Event Records" screen is correct.
Note: The choice of whether to record or not can be set for each event. Change the status of the binary
input signal after confirming that the related event is set to record. (The default setting enables
all the events to be recorded.)
Some of the internal events such as Trip, VTF, etc., can be checked in the protection scheme tests.
Disturbance recording can be checked while testing the protection schemes. The LCD display
only shows the date and time when a disturbance is recorded. Open the "Disturbance records"
screen and check that the descriptions are correct.
Details can be displayed on the PC. Check that the descriptions on the PC are correct. For details
on how to obtain disturbance records on the PC, see the RSM100 Manual.
6.5.5 Fault Locator
In the fault locator tests, a dynamic test set with a three-phase voltage source and current source is
required to simulate power system pre-fault, fault and post-fault conditions.
The fault locator starts measurement with one of the following tripping signals: command trip, Z1,
Z2, ZF, Z3 and Z1X trip, external main protection trip and PLC signal. If the [AZFLEN] setting is
"On", the fault locator also starts measurement with one of the following trip signals: ZR1 and
ZR2 trip, or forward Z3 and reverse ZR2 reset when no trip occurs. Therefore, it is preferable to
test it while testing the protection schemes by applying a fault.
The line parameter settings must be changed to meet those of the test set.
The measurement result is expressed as a percentage of the line length and the distance and
displayed on the "Fault Record" screen of the LCD. It is not displayed if the fault point is over
100% of the protected line and the [AZFLEN] setting is "Off". If the [AZFLEN] setting is "On",
the fault point displayed but it is not always measured correctly.
Note: If abnormal settings far from actual transmission line impedance, e.g. resistance value
so larger than reactance value, etc., are done, the location error will be larger.
244
6 F 2 S 0 8 5 1
6.6 Conjunctive Tests
6.6.1 On Load Test
With the relay connected to the line which is carrying a load current, it is possible to check the
polarity of the voltage transformer and current transformer and the phase rotation with the
metering displays on the LCD screen.
Open the following "Metering" screen from the "Status" sub-menu.
/ 2 M e t e r i n g
V a 6 3 . 5 V 0
V b 6 3 . 4 V - 1 2 0 A
V c 6 3 . 5 V 1 2 0
2 . 1 0 l
. 0
- 1 1 5 . 0
. 0
. 1
b
l a
l c
A 2 . 1 0
A 2 . 1 5
4 . 9
1 2 5 . 1
. . .
A c t i v e p o w e r + 3 1 8 . 5 0 M
R e a c t i e 2 9 . 0 0 M
. . .
W
v p o w e r - r a v
F r e q u e c n y 6 0 . 0 H z
3 3 / 1
+ +
+
+
Note: The magnitude of voltage, current and power can be set in values on the primary side or on the
secondary side by the setting. (The default setting is the primary side.)
Phase angles are expressed taking that of positive sequence voltage as the reference angle.
The sign of the phase angle can be set positive for either lagging phase or leading phase. (In the
default setting, it is set positive when the phase is leading to the reference angle.)
The sign of the power flow direction can be set positive for either power sending or power
receiving. (The default setting is power sending.)
Check that the phase rotation is correct.
Verify the phase relationship between the voltage and current with the known load current
direction.
6.6.2 Signaling Circuit Test
This test is performed when a command protection using a signaling channel is applied. The test is
carried out after the signal receive and send contacts are connected to the telecommunication
circuit.
The signal send circuit from the relay to the telecommunication equipment is checked by forcibly
operating the signal send relay and monitoring the signal at the telecommunication equipment.
Signal sending is performed on the LCD using the "Test" sub-menu as follows.
Press 3 (= Binary output) on the "Test" screen to display the "Binary output" screen. The LCD
displays the output modules installed depending on the model.
Enter 2 to select the IO#2 module, the LCD will display the screen shown below, indicating
the name of the module, the name of the output relay, the name of the terminal block and the
terminal number to which the relay contact is connected.
245
6 F 2 S 0 8 5 1
/ 3 B O ( 0 = D i s a b l e 1 = E n a b l e ) 1 / 1 4
I O # B O 1 0
I O # B O 2 0
I O # B O 3 0
.
.
O B O 1 I # 1
2
2
2
2
3
Move the cursor to the bottom line to select the BO13 output relay by pressing the key,
then enter 1 and press the ENTER key.
After completing the entries, press the END key. The LCD will display the screen shown
below.
/ 3 B O
K e e p i n g 1 t o o p e r a t e .
C A N C E t o c a n c e l . L P r e s s
p r e s s
Keep pressing the 1 key to operate the BO13 output relay forcibly. Then the BO13 output
contact will close. Monitor this at the telecommunication equipment.
The signal receive circuit from the telecommunication equipment to the relay is checked with the
"Binary input & output" screen on the LCD as follows:
Note: The receive signal is assigned to any of the binary inputs by the user setting. The following
description is the case of BI4 and BI5 assigned.
Display the "Binary I/O" screen from the "Status" sub-menu. Position BI4 indicates a receive
signal status. Position BI5 indicates the status of the guard signal in case of frequency shift
signaling.
/ 2 B i n a r y i n p u t & o u t p u t 3 / 8
I n p u t ( I O# 1 [ 0 0 0 0 0 0 0 0 0 0 0 0 ]
I n p u t ( I O# 2 [ 0 0 0 ]
O u t p u t ( I O 1 - t r i p ) [ 0 0 0 ]
O u t p u t ( I O# 3 [ 0 0 0 0 0 0 0 0 0 0 ]
O u t p u t ( I O# 4 [ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ]
)
)
O u t p u t ( I O# 2 [ 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ]
I n p u t ( I O# 3 [ 0 0 0 0 0 0 0 0 0 0 ] )
)
)
)
#
I n p u t ( I O# 4 [ 0 0 0 ] )
Send a signal or interrupt sending a signal at the telecommunication equipment and monitor on
the screen that the status of BI4 or BI5 changes accordingly.
If the signaling circuit connection is completed from the local relay to the remote relay, the test
above can be extended to an end-to-end test.
Send the signal by operating the BO13 output relay at one end with the "Test" sub-menu as
described above and monitor the signal reception at the other end on the "Binary input &
output" screen.
In the BOP scheme, the end-to-end test can be carried out more simply on the "Manual test" screen
of the "Test" sub-menu. For the details, see Section 4.2.7.2.
Note: In these tests it is recommended to block the tripping circuit to prevent false tripping.
246
6 F 2 S 0 8 5 1
6.6.3 Tripping and Reclosing Circuit Test
The tripping and reclosing circuit including the circuit breaker is checked by forcibly operating
the output relay and monitoring the circuit breaker to confirm that it is tripped or reclosed.
Forcible operation of the output relay is performed on the "Binary output" screen of the "Test"
sub-menu as described in Section 6.4.3.
Tripping circuit
Set the breaker to be closed.
Press 3 (= Binary output) on the "Test" sub-menu screen to display the "Binary output" screen.
The LCD displays the output modules mounted.
Enter 1 to select the IO#1 module, then the LCD displays the screen shown below.
/ 3 B O ( 0 = D i s a b l e 1 = E n a b l e ) 1 / 3
I O #
T P -
0
I O # 0
I O # 0
B 1
T P - A 1
T P - C 1
1
1
1
TP-A1, B1 and C1 are output relays with one normally open contact, and trip the A-phase,
B-phase and C-phase circuit breakers.
Enter 1 for TP-A1 and press the ENTER key.
Press the END key. Then the LCD displays the screen shown below.
/ 3 B O
K e e p p r e s s 1 o o p e r a t e .
C A N C E t o c a n c e l . L P r e s s
n i g t
Keep pressing the 1 key to operate the output relay TP-A1 and check that the A-phase
breaker is tripped.
Release the 1 key to reset the operation.
Repeat the above for all the phases.
Reclosing circuit
The test is applied to the autoreclose function if used.
Ensure that the circuit breaker is open.
Press 3 (= Binary output) on the "Test" sub-menu screen to display the "Binary output" screen.
The LCD displays the output modules mounted.
Enter the selected number corresponding to each module to be operated. The LCD will display
the name of the module, the name of the output relay, the name of the terminal block and the
terminal number to which the relay contact is connected.
Note: The autoreclose command is assigned to any of the output relays by the user setting. The
following description is the case for the default setting of model 201.
In the default setting, the autoreclose command is set to BO10 of the IO#2 module.
Enter 2 to select the IO#2 module, then the LCD displays the screen shown below.
247
6 F 2 S 0 8 5 1
/ 3 B O ( 0 = D i s a b l e 1 = E n a b l e ) 1 / 1 4
I O #
B O 2
0
I O # 0
I O # 0
B O 1
B O 3
B O 1 I O # 1
I O # 0
0
B O 1 1
. . .
I O # 0 B O 1 2
I O # 0 F A I L
I O # 0 S B X
2
2
2
2
2
2
2
2
Note: Terminal block number depends on the relay model. So see Appendix G for details.
Move the cursor by pressing the key and select BO10. BO10 is an autoreclose command output
relay with one normally open contact.
Enter 1 and press the ENTER key.
Press the END key. Then the LCD displays the screen shown below.
/ 3 B O
p r e s s K e e p t o o p e r a t e .
C A N C E t
1
o c a n c e l . L P r e s s
i n g
Keep pressing the 1 key to forcibly operate the output relay BO10 and check that the circuit
breaker is closed.
Release the 1 key to reset the operation.
In case of two-breaker autoreclose, repeat the forcible operation for BO11.
248
6 F 2 S 0 8 5 1
6.7 Maintenance
6.7.1 Regular Testing
The relay is almost completely self-supervised. The circuits which can not be supervised are
binary input and output circuits and human interfaces.
Therefore regular testing can be minimized to checking the unsupervised circuits. The test
procedures are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3.
6.7.2 Failure Tracing and Repair
Failures will be detected by automatic supervision or regular testing.
When a failure is detected by supervision, a remote alarm is issued with the binary output signal of
FAIL (*) and the failure is indicated on the front panel with LED indicators or LCD display. It is
also recorded in the event record.
(*) Failure signals on the external circuits, that is signaling channel, VT circuit and isolator circuit,
can be allotted to any of the binary output relays by the user. Failure signals of the signaling
channel and VT circuit are set to BO12 of the IO module as the default setting.
Failures detected by supervision are traced by checking the "Auto-supervision" screen on the
LCD.
If any messages are shown on the LCD, the failed module or failed external circuits can be located
by referring to the Table 6.7.2.1.
This table shows the relationship between message displayed on the LCD and estimated failure
location. The location marked with (1) has a higher probability than the location marked with (2).
As shown in the table, some of the messages cannot identify the fault location definitely but
suggest plural possible failure locations. In these cases, the failure location is identified by
replacing the suggested failed modules with spare modules one by one or investigating and
restoring the monitored external circuits (that is signaling channel, VT circuit and isolator circuit)
until the "Alarm" LED is turned off.
The replacement or investigation should be performed first for the module or circuit with higher
probability in the table.
If there is a failure and the LCD is not working such as a screen is frozen or not displayed, the
failure location is any one of SPM and HMI module.
249
6 F 2 S 0 8 5 1
Table 6.7.2.1 LCD Message and Failure Location
Message Failure location
VCT SPM IO1 IO2 IO3 IO4 HMI Channel Discon-
nector
AC
cable
VT LAN
cable/
network
PLC,
IEC61850
data
Checksum err
ROM data err
ROM-RAM err
SRAM err
CPU err
Invalid err
NMI err
BU-RAM err
EEPROM err
A/D err
Sampling err
V0 err (2) (1) (2)
V2 err (2) (1) (2)
I0 err (2) (1) (2)
CT err (2) (2) (1)
DIO err (2) (1) (1) (1) (1)
RSM err (1) (2)
LCD err
Trip output err
DS fail (2) (2) (1)
Ch. fail (2) (2) (2) (1)
VT fail (2) (1)
DC supply off
RTC err
PCI err
LAN err
GOOSE stop (2) (1)
Ping err (2) (1)
PLC stop
MAP stop
No-working of
LCD
(2) (1)
The location marked with (1) has a higher probability than the location marked with (2).
250
6 F 2 S 0 8 5 1
If no message is shown on the LCD, this means that the failure location is either in the DC power
supply circuit or in the microprocessors mounted on the SPM module. Then check the "ALARM"
LED. If it is off, the failure is in the DC power supply circuit. If it is lit, open the relay front panel
and check the LEDs mounted on the SPM module. If the LED is off, the failure is in the DC power
supply circuit. If the LED is lit, the failure is in the microprocessors.
In the former case, check if the correct DC voltage is applied to the relay.
If so, replace the IO1 module mounting the DC/DC converter and confirm that the "Alarm" LED is
turned off.
In the latter case, replace the SPM module mounting the processors and confirm that the "Alarm"
LED is turned off.
When a failure is detected during regular testing, it will not be difficult to identify the failed
module to be replaced.
Note: When a failure or an abnormality is detected during the regular test, confirm the following
first:
- Test circuit connections are correct.
- Modules are securely inserted in position.
- Correct DC power voltage is applied.
- Correct AC inputs are applied.
- Test procedures comply with those stated in the manual.
6.7.3 Replacing Failed Modules
If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (VCT, SPM, IO2, etc.) and
hardware type-form as the removed module. Furthermore, the SPM module should have the same
software name.
The module name is indicated on the bottom front of the relay case. The hardware type-form is
indicated on the module in the following format:
Module name Hardware type-form
VCT G1PC1-
SPM G1SP -
IO1 G1IO1-
IO2 G1IO2-
IO3 G1IO3-
IO4#1 G1IO2-
IO4#2 G1IO2-
HMI ---------
251
6 F 2 S 0 8 5 1
The software name is indicated on the memory device on the module with letters such as
GSPZM1-, etc.
CAUTION When handling a module, take anti-static measures such as wearing an earthed
wrist band and placing modules on an earthed conductive mat. Otherwise, many
of the electronic components could suffer damage.
CAUTION After replacing the SPM module, check all of the settings including the data
related the PLC, IEC103 and IEC61850, etc. are restored the original settings.
The initial replacement procedure is as follows:
Switch off the DC power supply.
Disconnect the trip outputs.
Short circuit all AC current inputs and disconnect all AC voltage inputs.
Hazardous voltage can be present in the DC circuit just after switching off the
DC power supply. It takes approximately 30 seconds for the voltage to
discharge.
Unscrew the relay front cover.
Replacing the Human Machine Interface Module (front panel)
Open the front panel of the relay by unscrewing the binding screw located on the left side of
the front panel.
Unplug the ribbon cable on the front panel by pushing the catch outside.
Remove the two retaining screws and one earthing screw on the relay case side, then detach
the front panel from the relay case.
Attach the replacement module in the reverse procedure.
Replacing the Transformer Module
Open the right-side front panel (HMI module) by unscrewing the two binding screws located
on the left side of the panel.
Open the left-side front panel (blind panel) (*) by unscrewing the two binding screws located
on the right side of the panel.
(*) This blind panel is attached only to models assembled in the type B case.
Detach the module holding bar by unscrewing the binding screw located on the left side of the
bar.
Unplug the ribbon cable on the SPM by nipping the catch.
Remove the metal cover by unscrewing the binding screw located at the top and bottom of the
cover.
Pull out the module by grasping the handles.
Insert the replacement module in the reverse procedure.
Replacing other modules
Open the right-side front panel (HMI module) by unscrewing the two binding screws
located on the left side of the panel.
Open the left-side front panel (blind panel) (*) by unscrewing the two binding screws located
on the right side of the panel.
WARNING
252
6 F 2 S 0 8 5 1
(*) This panel is attached only to models assembled in the type B case.
Detach the module holding bar by unscrewing the binding screw located on the left side of the
bar.
Unplug the ribbon cable running among the modules by nipping the catch (in case of black
connector) and by pushing the catch outside (in case of gray connector) on the connector.
Pull out the module by pulling up or down at the top and bottom levers.
Insert the replacement module in the reverse procedure.
After replacing the SPM module, input the user setting values again.
6.7.4 Resumption of Service
After replacing the failed module or repairing failed external circuits, take the following
procedures to restore the relay to service.
Switch on the DC power supply and confirm that the "IN SERVICE" green LED is lit and the
"ALARM" red LED is not lit.
Note: Supply DC power after checking that all the modules are in their original positions and the
ribbon cables are plugged in.
If the telecommunication circuit was repaired, perform a "Manual test" and check that the
circuit is normal. For the "Manual test", refer to Section 4.2.7.2.
Supply the AC inputs and reconnect the trip outputs.
6.7.5 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC Standard
60255-6 the storage temperature should be 25C to +70C, but the temperature of 0C to +40C
is recommended for long-term storage.
253
6 F 2 S 0 8 5 1
7. Putting Relay into Service
The following procedure must be adhered to when putting the relay into service after finishing
commissioning or maintenance tests.
Check that all external connections are correct.
Check the setting of all measuring elements, timers, scheme switches, recordings and clock are
correct.
In particular, when settings are changed temporarily for testing, be sure to restore them.
Clear any unnecessary records on faults, events and disturbances which are recorded during
the tests.
Reset the counter figures of automatic test and autoreclose, if necessary. For resetting the
count, see Section 4.2.3.4 and 4.2.3.5.
Press the VIEW key and check that no failure message is displayed on the
"Auto-supervision" screen.
Check that the green "IN SERVICE" LED is lit and no other LEDs are lit on the front panel.
254
6 F 2 S 0 8 5 1
255
6 F 2 S 0 8 5 1
Appendix A
Block Diagram
256
6 F 2 S 0 8 5 1
Model 201
TZ1G
TZ2G
TZFG
TZ3G
Zone 1 Trip
Zone Back-up Trip
1
&
&
&
Phase
Selection
1
1 &
&
1
1
t 0 t 0
t 0 t 0
t 0 t 0
t 0 t 0
Z1G
Z1XG
Z2G
Z3G
ZFG
UVC
TZ1S
TZ2S
Zone 1 Extension
Trip
TZFS
TZ3S
1
Z1-EXT
Zone 1 extension
scheme logic
t 0 t 0
t 0 t 0
t 0 t 0
t 0 t 0
&
Z1S
Z1XS
Z2S
Z3S
ZFS
Command protection scheme logic
- PUP/PUP+DEF
- POP/POP+DEF
- UOP/UOP+DEF
- BOP/BOP+DEF
Command protection Trip
SOTF Trip
Stub Trip
CBF Re-trip
CBF Related CB trip
Out of step trip
: Measuring element
: Binary input/output
TBF1
TBF2
CB
Z1,Z2,Z3, ZF,
ZR1, ZR2 or ZND
CB
STUB scheme
logic
Isolator
Trip
MCB trip
of VT
Phase
Selection
SOTF scheme
logic
&
PSB scheme
logic
VTF scheme
logic
&
Related CB Trip Command
Signal Send
t 0 t 0
t 0 t 0
1 1
OST scheme
logic
OCH
OCBF
OVG
UVF
OCD
PSB
OST
UVL
EF
Back-up Trip
OC Back-up
Trip
TDEF t 0
TEF t 0
1
Signal receive
1
t 0 t 0
t 0 t 0
DEFF
DEFR
EF
OCI
EFI
TOC t 0 t 0
OC
1
&
&
0
ZR1G
t TZR1G
&
0
ZR2G
t TZR2G
&
0
ZNDG
t TZNDG
TZR1S t 0 t 0
ZR1S
TZR2S t 0 t 0
ZR2S
TZNDS t 0 t 0
ZNDS
Z4G
Z4S
THM
THM Trip
EFL
UVPWI
&
&
1
TDER t 0 t 0 t 0
1
DEF
Back-up Trip
TBCD t 0 t 0 t 0 BCD
TOS1
t 0 t 0
OVS1
TOS2 t 0 t 0 t 0
OVS2
TOG1
t 0 t 0
OVG1
TUS1
t 0 t 0
UVS1
TUG1
t 0 t 0
UVG1
TOG2 t 0 t 0 t 0
OVG2
TUS2 t 0 t 0 t 0
UVS2
TUG2 t 0 t 0 t 0
UVG2
1
BCD Trip
OV & UV Trip
OV Alarm
UV Alarm
CB Reclose Command
Autoreclose scheme logic
- SPAR
- TPAR
(with synchronism check)
- SPAR+TPAR
- Multi-shot Autoreclose (4shots)
SYN
UV
OV
Directional
control
CB Trip Command
257
6 F 2 S 0 8 5 1
Model 301, 303
TZ1G
TZ2G
TZFG
TZ3G
Zone 1 Trip
Zone Back-up Trip
1
&
&
&
Phase
Selection
1
1 &
&
1
1
t 0 t 0
t 0 t 0
t 0 t 0
t 0 t 0
Z1G
Z1XG
Z2G
Z3G
ZFG
UVC
TZ1S
TZ2S
Zone 1 Extension
Trip
TZFS
TZ3S
1
Z1-EXT
Zone 1 extension
scheme logic
t 0 t 0
t 0 t 0
t 0 t 0
t 0 t 0
&
Z1S
Z1XS
Z2S
Z3S
ZFS
Command protection scheme logic
- PUP/PUP+DEF
- POP/POP+DEF
- UOP/UOP+DEF
- BOP/BOP+DEF
Command protection Trip
SOTF Trip
Stub Trip
CBF Re-trip
CBF Related CB trip
Out of step trip
: Measuring element
: Binary input/output
TBF1
TBF2
CB
Z1,Z2,Z3, ZF,
ZR1, ZR2 or ZND
CB
STUB scheme
logic
Isolator
Trip
MCB trip
of VT
Phase
Selection
SOTF scheme
logic
&
PSB scheme
logic
VTF scheme
logic
&
Related CB Trip Command
Signal Send
t 0 t 0
t 0 t 0
1 1
OST scheme
logic
OCH
OCBF
OVG
UVF
OCD
PSB
OST
UVL
EF
Back-up Trip
OC Back-up
Trip
TDEF t 0
TEF t 0
1
Signal receive
1
t 0 t 0
t 0 t 0
DEFF
DEFR
EF
OCI
EFI
TOC t 0 t 0
OC
1
&
&
0
ZR1G
t TZR1G
&
0
ZR2G
t TZR2G
&
0
ZNDG
t TZNDG
TZR1S t 0 t 0
ZR1S
TZR2S t 0 t 0
ZR2S
TZNDS t 0 t 0
ZNDS
Z4G
Z4S
THM
THM Trip
EFL
UVPWI
&
&
1
TDER t 0 t 0 t 0
1
DEF
Back-up Trip
TBCD t 0 t 0 t 0 BCD
TOS1
t 0 t 0
OVS1
TOS2 t 0 t 0 t 0
OVS2
TOG1
t 0 t 0
OVG1
TUS1
t 0 t 0
UVS1
TUG1
t 0 t 0
UVG1
TOG2 t 0 t 0 t 0
OVG2
TUS2 t 0 t 0 t 0
UVS2
TUG2 t 0 t 0 t 0
UVG2
1
BCD Trip
OV & UV Trip
OV Alarm
UV Alarm
Center CB Reclose Command
Autoreclose scheme logic
- SPAR
- TPAR
(with synchronism check)
- SPAR+TPAR
- Multi-shot Autoreclose (4shots)
SYN
UV
OV
Directional
control
Bus CB Trip Command
Center CB Trip Command
Bus CB Reclose Command
258
6 F 2 S 0 8 5 1
259
6 F 2 S 0 8 5 1
Appendix B
Signal List
260
6 F 2 S 0 8 5 1
Signal List
Signal list
0 CONSTANT 0 constant 0
1 CONSTANT 1 constant 1
2
3
4
5
6
7
8
9 CRT USE CARRIER IN SERVICE
10
11
12
13
14
15
16
17
18
19 Z1G-A EARTH FAULT RELAY Z1G
20 Z1G-B ditto
21 Z1G-C ditto
22 Z1XG-A EARTH FAULT RELAY Z1XG
23 Z1XG-B ditto
24 Z1XG-C ditto
25 Z2G-A EARTH FAULT RELAY Z2G
26 Z2G-B ditto
27 Z2G-C ditto
28 Z3G-A EARTH FAULT RELAY Z3G
29 Z3G-B ditto
30 Z3G-C ditto
31 Z4G-A EARTH FAULT RELAY Z4G
32 Z4G-B ditto
33 Z4G-C ditto
34 Z1S-AB PHASE FAULT RELAY Z1S
35 Z1S-BC ditto
36 Z1S-CA ditto
37 Z1XS-AB PHASE FAULT RELAY Z1XS
38 Z1XS-BC ditto
39 Z1XS-CA ditto
40 Z2S-AB PHASE FAULT RELAY Z2S
41 Z2S-BC ditto
42 Z2S-CA ditto
43 Z3S-AB PHASE FAULT RELAY Z3S
44 Z3S-BC ditto
45 Z3S-CA ditto
46 Z4S-AB PHASE FAULT RELAY Z4S
47 Z4S-BC ditto
48 Z4S-CA ditto
49 PSBSOUT-AB POWER SWING BLOCK for ZS OUTER ELEMENT
50 PSBSOUT-BC ditto
51 PSBSOUT-CA ditto
52 OCCR-A OC RELAY FOR LINE VT
53 OCCR-B ditto
54 OCCR-C ditto
55 OCH-A HIGH SET OC RELAY
56 OCH-B ditto
57 OCH-C ditto
58 DEFR DIRECT. EF RLY (EXTERNAL)
59 DEFF DIRECT. EF RLY (INTERNAL)
60 EF EARTH FAULT RELAY
61 EFI EARTH FAULT IDMT RELAY
62 OVG EARTH OV RELAY
63 OCD-A CURRENT CHANGE DETEC. RELAY
64 OCD-B ditto
65 OCD-C ditto
66 UVC-A UV RELAY (PHASE SELECTOR)
67 UVC-B ditto
68 UVC-C ditto
69 UVFS-AB UV RELAY (High set)
70 UVFS-BC ditto
Contents No. Signal Name
261
6 F 2 S 0 8 5 1
Signal list
71 UVFS-CA ditto
72 UVLS-AB UV RELAY (Low set)
73 UVLS-BC ditto
74 UVLS-CA ditto
75 UVFG-A UV RELAY (High set)
76 UVFG-B ditto
77 UVFG-C ditto
78 UVLG-A UV RELAY (Low set)
79 UVLG-B ditto
80 UVLG-C ditto
81 OCBF-A OC RELAY FOR CBF DETECTION
82 OCBF-B ditto
83 OCBF-C ditto
84 OST-ZM OST-ZM
85 OST-ZN OST-ZN
86 OVB OVB
87 UVB UVB
88 SYN1 SYN1
89 OVL1 OVL1
90 UVL1 UVL1
91 OVL2 OVL2
92 UVL2 UVL2
93 SYN2 SYN2
94 OC-A OC-A
95 OC-B OC-B
96 OC-C OC-C
97 OCI-A OCI-A
98 OCI-B OCI-B
99 OCI-C OCI-C
100 CHECKING CHECKING
101 CB-AND CB CONTACT (3PHASE AND)
102 CB-OR CB CONTACT (3PHASE OR)
103 Z1G-AX Z1G-AX
104 Z1G-BX Z1G-BX
105 Z1G-CX Z1G-CX
106 Z1XG-AX Z1XG-AX
107 Z1XG-BX Z1XG-BX
108 Z1XG-CX Z1XG-CX
109 Z2G-AX Z2G-AX
110 Z2G-BX Z2G-BX
111 Z2G-CX Z2G-CX
112 Z3G-AX Z3G-AX
113 Z3G-BX Z3G-BX
114 Z3G-CX Z3G-CX
115 Z4G-AX Z4G-AX
116 Z4G-BX Z4G-BX
117 Z4G-CX Z4G-CX
118 Z1S-ABX Z1S-ABX
119 Z1S-BCX Z1S-BCX
120 Z1S-CAX Z1S-CAX
121 Z1XS-ABX Z1XS-ABX
122 Z1XS-BCX Z1XS-BCX
123 Z1XS-CAX Z1XS-CAX
124 Z2S-ABX Z2S-ABX
125 Z2S-BCX Z2S-BCX
126 Z2S-CAX Z2S-CAX
127 Z3S-ABX Z3S-ABX
128 Z3S-BCX Z3S-BCX
129 Z3S-CAX Z3S-CAX
130 Z4S-ABX Z4S-ABX
131 Z4S-BCX Z4S-BCX
132 Z4S-CAX Z4S-CAX
133 PSBSOUT-ABX PSBSOUT-ABX
134 PSBSOUT-BCX PSBSOUT-BCX
135 PSBSOUT-CAX PSBSOUT-CAX
136 OCCROR OCCROR
137 OCHOR OCHOR
138 OCDOR OCDOR
139 UVCOR UVCOR
140 UVFSOR UVFSOR
Contents No. Signal Name
262
6 F 2 S 0 8 5 1
Signal list
141 UVLSOR UVLSOR
142 UVFGOR UVFGOR
143 UVLGOR UVLGOR
144 2PH 2PH
145 TZ1GA TZ1GA
146 TZ1GB TZ1GB
147 TZ1GC TZ1GC
148 Z1G TRIP Z1G TRIP
149 Z1G-A TRIP Z1G TRIP A ph.
150 Z1G-B TRIP Z1G TRIP B ph.
151 Z1G-C TRIP Z1G TRIP C ph.
152
153 Z2G TRIP Z2G TRIP
154 Z2GOR Z2G RELAY OR LOGIC
155
156 Z3G TRIP Z3G TRIP
157 Z3GOR Z3G RELAY OR LOGIC
158 Z1PTT ZONE1 RELAY O/P FOR PTTSCHEME
159 TZ1S Z1S TRIP TIMER
160 Z1S TRIP Z1S TRIP
161
162 Z2S TRIP Z2S TRIP
163 Z2SOR Z2S RELAY OR LOGIC
164
165 Z3S_TRIP Z3S TRIP
166 Z3SOR Z3S RELAY OR LOGIC
167 Z1XG_TRIP Z1XG TRIP
168 Z1X-A TRIP Z1XG TRIP A ph.
169 Z1X-B TRIP Z1XG TRIP B ph.
170 Z1X-C TRIP Z1XG TRIP C ph.
171 Z1XS TRIP Z1XS TRIP
172 VTF ALARM VTF ALARM
173 VTF VTF BLOCK SIGNAL
174 VTF1 ALARM 3PH VTF DETECT.
175 VTF2 ALARM 1 OR 2PH VTF DETECT
176 PSB DET PSB DETECTION
177 PSB-Z1 PSB FOR ZONE1 RELAY
178 PSB-Z1X PSB FOR ZONE1X RELAY
179 PSB-Z2 PSB FOR ZONE2 RELAY
180 PSB-Z3 PSB FOR ZONE3 RELAY
181 PSB-CR PSB FOR CARRIER TRIP
182 STUB TRIP STUB TRIP
183 SOTF TRIP SOTF TRIP
184 EFI TRIP EF IDMT TRIP
185 EF ALARM EF BACK-UP TRIP ALARM
186 DEF ALARM DEF BACK-UP TRIP ALARM
187 EF BU-TRIP EF or DEF BACK-UP TRIP
188 TZ4S Z4S BACK-UP TRIP TIMER
189 ZR1S TRIP ZR1S TRIP
190 ZR1SOR ZR1S RELAY OR LOGIC
191 TZ4G Z4G BACK-UP TRIP TIMER
192 ZR1G TRIP ZR1G BACK-UP TRIP
193 ZR1GOR ZR1G RELAY OR LOGIC
194 BU TRIP BACK-UP TRIP
195 BURECLK BU RECLOSE BLOCK
196 CBF RETRIP-A RE-TRIP A ph. FOR CBF
197 CBF RETRIP-B RE-TRIP B ph. FOR CBF
198 CBF RETRIP-C RE-TRIP C ph. FOR CBF
199 CBF DET CBF DETECTION
200 CBF TRIP RELATED CB TRIP FOR CBF
201 TOST1 OS DETECTION TIMER 1
202 TOST2 OS DETECTION TIMER 2
203 OST TRIP OS TRIP
204 EXT CAR-R1 CARRIER RECEIVE FROM REMOTE TERM.1
205 C/R PUP CARRIER SEND FOR PUTT
206 CRG-PUP PUTT LOCAL TRIP
207 CRS-PUP ditto
208 ZGCX CARRIER CONTROL RELAY(Z2G/Z3G)
209 ZSCX CARRIER CONTROL RELAY(Z2S/Z3S)
210 C/R POUP CARRIER SEND FOR POTT/UNBLK
Contents No. Signal Name
263
6 F 2 S 0 8 5 1
Signal list
211 CRG-POP/UOP POTT/UNBLK LOCAL TRIP
212 CRS-POP/UOP ditto
213 WI TRIP WEAK INFEED TRIP
214 REV BLK CARRIER SEND FOR BLOCK
215 DEFFCR DEF CARRIER TRIP DELAY TIMER
216 DEFRCR CARR. COORDINATION DEFR TIMER
217 C/R DEF DEF CARR. SEND (PUTT,POTT,UNBLK)
218 DEFCAR TRIP DEF CARR. TRIP (ditto)
219 C/R DEFBOP DEF CARR. SEND (BLK)
220 DEFBOP TRIP DEF CARR. TRIP (BLK)
221 C/R BOP CARRIER SEND FOR BLOCKING
222 CRG-BOP BLOCKING LOCAL TRIP
223 CRS-BOP ditto
224 LK-BOP CARRIER SEND FOR BLOCKING
225 EXT CAR-S EXTERNAL CARRIER SEND COMMAND
226 CAR-G TRIP CARRIER TRIP(G)
227 CAR-S TRIP CARRIER TRIP(S)
228 CAR-A TRIP DISTANCE or DEF CARRIER TRIP (A ph.)
229 CAR-B TRIP DISTANCE or DEF CARRIER TRIP (B ph.)
230 CAR-C TRIP DISTANCE or DEF CARRIER TRIP (C ph.)
231 CAR TRIP DISTANCE or DEF CARRIER TRIP
232 DEFCR TRIP DEF CARRIER TRIP
233 WICAR TRIP WEAK CARRIER TRIP
234 TPMD3PH TRIP MODE 3ph.
235 TRIP-A TRIP A ph.
236 TRIP-B TRIP B ph.
237 TRIP-C TRIP C ph.
238 TRIP-OR TRIP O/P OR
239 TRIP TRIP SINGLE SHOT
240 TRIP-A1 TRIP O/P FOR BUS CB
241 TRIP-B1 ditto
242 TRIP-C1 ditto
243 TRIP-A2 TRIP O/P FOR CENTER CB
244 TRIP-B2 ditto
245 TRIP-C2 ditto
246 FDX1 FD OUTPUT 1 (OPTION)
247 FDX2 FD OUTPUT 2 (OPTION)
248 M-OR MAIN TRIP OR
249 M-AND MAIN TRIP AND
250 FD FD TRIP OR
251 FD-AND FD TRIP AND
252 SBT CARRIER SEND FOR TEST/MONITOR
253 CHF CARRIER CHANNEL FAILURE
254 RLYFAIL RELAY FAILURE
255 RLY O/P BLK RELAY OUTPUT BLOCK
256 SV-LOCK SV BLOCK
257 LSSV LS FAILURE
258 TEVLV EVOLVING FAULT WAITING TIMER
259 TSPR1 LEAD SPAR DEAD LINE TIMER
260 TTPR1 LEAD TPAR DEAD LINE TIMER
261 TRR1 LEAD RESET TIMER
262 TPARL-SET LEAD TPAR O/P CONFIRMED
263 TSPR2 FLW SPAR DEAD LINE TIMER
264 TTPR2 FLW TPAR TIMING
265 TRR2 FLW RESET TIMER
266 TPAR.F FLW TPAR O/P CONFIRMED
267 LB.DL-1 LEAD LIVE BUS & DEAD LINE
268 DB.LL-1 LEAD DEAD BUS & LIVE LINE
269 LB.LL.SYN-1 LEAD LIVE BUS & LIVE LINE +SYN.
270 LB.DL-2 FLW LIVE BUS & DEAD LINE
271 DB.LL-2 FLW DEAD BUS & LIVE LINE
272 LB.LL.SYN-2 FLW LIVE BUS & LIVE LINE SYN.
273 SYN-OP SYN. CONDITION FOR TPAR
274 SYN-SEL SYN. ELEMENT SELECT SIGNAL
275 TDBL1 VOLTAGE CHECK TIMER
276 TLBD1 ditto
277 TSYN1 LEAD SYN CHECK TIMER
278 TDBL2 VOLTAGE CHECK TIMER
279 TLBD2 ditto
280 TSYN2 FLW SYN CHECK TIMER
Contents No. Signal Name
264
6 F 2 S 0 8 5 1
Signal list
281 REC.READY1 LEAD REC. READY SIGNAL
282 REC.READY2 FLW REC. READY SIGNAL
283 BRIDGE1 LEAD BRIDGE CONDITION
284 BRIDGE2 FLW BRIDGE CONDITION
285 IN-PROG1 LEAD REC. IN PROGRESS
286 IN-PROG2 FLW REC. IN PROGRESS
287 SPAR1 LEAD SPAR O/P
288 SPAR2 FLW SPAR O/P
289 TPAR1 LEAD TPAR O/P
290 TPAR2 FLW TPAR O/P
291 ARC1 REC OUTPUT FOR BUS CB
292 ARC2 REC OUTPUT FOR CENTER CB
293 94TT1 LEAD REMAINING PHASE TRIP
294 94TT2 FLW REMAINING PHASE TRIP
295 FT1 LEAD FINAL TRIP SIGNAL
296 FT2 FLW FINAL TRIP SIGNAL
297 TS2 MULTI.SHOT-2 DEAD TIMER
298 TS3 MULTI.SHOT-3 DEAD TIMER
299 TS4 MULTI.SHOT-4 DEAD TIMER
300 TS2R MULTI.SHOT-2 RESET TIMER
301 TS3R MULTI.SHOT-3 RESET TIMER
302 TS4R MULTI.SHOT-4 RESET TIMER
303 MULTI.ARC MULTI. SHOT REC. OUTPUT
304 MAR-OK0 1 SHOT REC. SUCCESS
305 MAR-OK1 2 SHOT REC. SUCCESS
306 MAR-OK2 3 SHOT REC. SUCCESS
307 MAR-OK3 4 SHOT REC. SUCCESS
308 MAR-FT MULTI. REC. FINAL TRIP
309 TRIP-H TRIP SIGNAL HOLD
310 SBT-INV CARRIER SEND FOR TEST/MONITOR
311 BFS-AB BLINDER FOR ZS (FORWARD)
312 BFS-BC ditto
313 BFS-CA ditto
314 BRS-AB BLINDER FOR ZS (REVERSE)
315 BRS-BC ditto
316 BRS-CA ditto
317 BFG-A BLINDER FOR ZG (FORWARD)
318 BFG-B ditto
319 BFG-C ditto
320 BRG-A BLINDER FOR ZG (REVERSE)
321 BRG-B ditto
322 BRG-C ditto
323 PSBSIN-AB POWER SWING BLOCK FOR ZS INNER ELEMENT
324 PSBSIN-BC ditto
325 PSBSIN-CA ditto
326 OC TRIP OC BACK-UP TRIP
327 OCI TRIP IDMT OC BACK-UP TRIP
328 OC BU-TRIP OC or OCI BACK-UP TRIP
329 TSPR3 FLW DEAD LINE TIMER
330 TTPR3 FLW DEAD LINE TIMER
331 Z1GTORT Z1G TRIP
332 Z1STT Z1S TRIP
333
334
335
336
337 OST BO OST BINARY OUTPUT
338 EXT DEFCAR-S EXTERNAL DEF CARRIER SEND COMMAND
339 S-DEFBOP2 DEF CARRIER SEND2(BLOCKING)
340
341 Z1+Z1X+CRT MAIN TRIP
342 Z1 TRIP ZONE1 TRIP
343 Z1X TRIP ZONE1 EXTENTION TRIP
344 Z2 TRIP ZONE2 TRIP
345 Z3 TRIP ZONE3 TRIP
346 ZR1 TRIP ZONE-R1 TRIP
347 Z2+Z3+ZR1 ZONE2-R1 TRIP
348 Z3+ZR1 ZONE3 AND ZONE-R1 TRIP
349 EF/DEF ALARM EF/DEF/EFI ALARM
350 SOTF+STUB SOTF/STUB TRIP
Contents No. Signal Name
265
6 F 2 S 0 8 5 1
Signal list
351 PUP TRIP PUP TRIP
352 PSBSIN-ABX PSBSIN-ABX
353 PSBSIN-BCX PSBSIN-BCX
354 PSBSIN-CAX PSBSIN-CAX
355 TP-2PH Multi phase trip signal
356 TP-MPH Multi phase trip signal
357 OCDP-A CURRENT CHANGE DET. DURING PS
358 OCDP-B ditto
359 OCDP-C ditto
360 DOCN-F NEGATIVE DIR.RELAY (FORWARD)
361 DOCN-R NEGATIVE DIR.RELAY (REVERSE)
362 UVPWI-A UV RELAY
363 UVPWI-B UV RELAY
364 UVPWI-C UV RELAY
365 TP-1PH Single phase trip
366
367
368 ARC COM.ON Autorecloser active (for IEC103)
369 TELE.COM.ON Teleprotection active (for IEC103)
370 PROT.COM.ON Protection active (for IEC103)
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393 OVL-ABC OVL element output (for 3phase line voltage)
394 OVL-A OVL-A element output (for 3phase line voltage)
395 OVL-B OVL-B element output (for 3phase line voltage)
396 OVL-C OVL-C element output (for 3phase line voltage)
397 3PLL Three phase live line element output
398
399
400
401 OCMF-L1 MULTI-STEP OC RELAY LEVEL 1
402 OCMF-L2 ditto LEVEL 2
403 OCMF-L3 ditto LEVEL 3
404 OCMF-L4 ditto LEVEL 4
405 OCMF-L5 ditto LEVEL 5
406 OCMF-L6 ditto LEVEL 6
407 OCMF-L7 ditto LEVEL 7
408 OCMF ditto OR LOGIC
409 OCDF-A CURRENT CHANGE DETECTION RELAY
410 OCDF-B ditto
411 OCDF-C ditto
412
413
414
415
416 EFF EARTH FAULT DETECTION RELAY
417 UVSF-AB UV RELAY
418 UVSF-BC ditto
419 UVSF-CA ditto
420
Contents No. Signal Name
266
6 F 2 S 0 8 5 1
Signal list
421 UVGF-A ditto
422 UVGF-B ditto
423 UVGF-C ditto
424
425 UVDF-A VOLTAGE CHANGE DETECTION RELAY
426 UVDF-B ditto
427 UVDF-C ditto
428
429
430
431 52AND1 CB1 contact AND logic
432 52AND2 CB2 contact AND logic
433 LB Selected live bus mode
434 DB Selected dead bus mode
435 SYN Selected Synchronism check mode
436 OVS1-AB OVS1-AB relay element output
437 OVS1-BC OVS1-BC relay element output
438 OVS1-CA OVS1-CA relay element output
439 OVS2-AB OVS2-AB relay element output
440 OVS2-BC OVS2-BC relay element output
441 OVS2-CA OVS2-CA relay element output
442 OVG1-A OVG1-A relay element output
443 OVG1-B OVG1-B relay element output
444 OVG1-C OVG1-C relay element output
445 OVG2-A OVG2-A relay element output
446 OVG2-B OVG2-B relay element output
447 OVG2-C OVG2-C relay element output
448 OVS1-AB INST OVS1-AB relay element start
449 OVS1-BC INST OVS1-BC relay element start
450 OVS1-CA INST OVS1-CA relay element start
451 OVG1-A INST OVG1-A relay element start
452 OVG1-B INST OVG1-B relay element start
453 OVG1-C INST OVG1-C relay element start
454 UVS1-AB UVS1-AB relay element output
455 UVS1-BC UVS1-BC relay element output
456 UVS1-CA UVS1-CA relay element output
457 UVS2-AB UVS2-AB relay element output
458 UVS2-BC UVS2-BC relay element output
459 UVS2-CA UVS2-CA relay element output
460 UVG1-A UVG1-A relay element output
461 UVG1-B UVG1-B relay element output
462 UVG1-C UVG1-C relay element output
463 UVG2-A UVG2-A relay element output
464 UVG2-B UVG2-B relay element output
465 UVG2-C UVG2-C relay element output
466 UVS1-AB INST UVS1-AB relay element start
467 UVS1-BC INST UVS1-BC relay element start
468 UVS1-CA INST UVS1-CA relay element start
469 UVG1-A INST UVG1-A relay element start
470 UVG1-B INST UVG1-B relay element start
471 UVG1-C INST UVG1-C relay element start
472 UVSBLK-AB UVS BLK-AB relay element output
473 UVSBLK-BC UVS BLK-BC relay element output
474 UVSBLK-CA UVS BLK-CA relay element output
475 UVGBLK-A UVG BLK-A relay element output
476 UVGBLK-B UVG BLK-B relay element output
477 UVGBLK-C UVG BLK-C relay element output
478
479
480 ARCMD OFF Autoreclosing mode (Disable)
481 ARCMD SPAR ditto (SPAR)
482 ARCMD TPAR ditto (MPAR)
483 ARCMD S&T ditto (SPAR & TPAR)
484 ARCMD EXT1P ditto (EXT1P)
485 ARCMD EXT3P ditto (EXT3P)
486 ARC-SET output set signal in leader CB autoreclose
487 CB UNDRY.L ST Starting signal for final trip with CB unready
488 TSUC1 ARC.L success reset signal
489 TSUC2 ARC.F success reset signal
490 ARC SUCCESS1 Leader CB autoreclose success signal
Contents No. Signal Name
267
6 F 2 S 0 8 5 1
Signal list
491 ARC SUCCESS2 Follower CB autoreclose success signal
492 ARC FAIL1 Leader CB autoreclose fail signal
493 ARC FAIL2 Follower CB autoreclose fail signal
494
495
496
497
498
499
500
501 UARCSW P1 User ARC switch Position1
502 UARCSW P2 User ARC switch Position2
503 UARCSW P3 User ARC switch Position3
504
505
506
507
508
509
510
511
512
513 BI1 COMMAND Binary input signal BI1
514 BI2 COMMAND Binary input signal BI2
515 BI3_COMMAND Binary input signal BI3
516 BI4_COMMAND Binary input signal BI4
517 BI5_COMMAND Binary input signal BI5
518 BI6 COMMAND Binary input signal BI6
519 BI7 COMMAND Binary input signal BI7
520 BI8 COMMAND Binary input signal BI8
521 BI9 COMMAND Binary input signal BI9
522 BI10 COMMAND Binary input signal BI10
523 BI11 COMMAND Binary input signal BI11
524 BI12 COMMAND Binary input signal BI12
525 BI13 COMMAND Binary input signal BI13
526 BI14 COMMAND Binary input signal BI14
527 BI15 COMMAND Binary input signal BI15
528 BI16 COMMAND Binary input signal BI16
529 BI17 COMMAND Binary input signal BI17
530 BI18 COMMAND Binary input signal BI18
531 BI19 COMMAND Binary input signal BI19
532 BI20 COMMAND Binary input signal BI20
533 BI21 COMMAND Binary input signal BI21
534 BI22 COMMAND Binary input signal BI22
535 BI23 COMMAND Binary input signal BI23
536 BI24 COMMAND Binary input signal BI24
537 BI25 COMMAND Binary input signal BI25
538 BI26 COMMAND Binary input signal BI26
539 BI27 COMMAND Binary input signal BI27
540 BI28 COMMAND Binary input signal BI28
541 BI34 COMMAND Binary input signal BI34
542 BI35 COMMAND Binary input signal BI35
543 BI36 COMMAND Binary input signal BI36
544
545
546
547
548
549
550
551
552
553 ZR1S-AB PHASE FAULT RELAY ZR1S
554 ZR1S-BC ditto
555 ZR1S-CA ditto
556 THM-T Thermal trip relay
557 ZR2S-AB PHASE FAULT RELAY ZR2S
558 ZR2S-BC ditto
559 ZR2S-CA ditto
560 THM-A Thermal alarm relay
Contents No. Signal Name
268
6 F 2 S 0 8 5 1
Signal list
561 PSBGIN-A POWER SWING BLOCK FOR ZG INNER ELEMENT
562 PSBGIN-B ditto
563 PSBGIN-C ditto
564
565 PSBGOUT-A POWER SWING BLOCK for ZG OUTER ELEMENT
566 PSBGOUT-B ditto
567 PSBGOUT-C ditto
568 EFL EARTH FAULT RELAY
569 ZR1G-A EARTH FAULT RELAY ZR1G
570 ZR1G-B ditto
571 ZR1G-C ditto
572
573 ZR2G-A EARTH FAULT RELAY ZR2G
574 ZR2G-B ditto
575 ZR2G-C ditto
576
577 ZFS-AB PHASE FAULT RELAY ZFS
578 ZFS-BC ditto
579 ZFS-CA ditto
580
581 ZNDS-AB PHASE FAULT RELAY ZNDS
582 ZNDS-BC ditto
583 ZNDS-CA ditto
584
585
586
587
588
589
590
591
592
593 ZFG-A EARTH FAULT RELAY ZFG
594 ZFG-B ditto
595 ZFG-C ditto
596
597 ZNDG-A EARTH FAULT RELAY ZNDG
598 ZNDG-B ditto
599 ZNDG-C ditto
600
601
602
603
604
605
606
607
608
609 ZR1S-ABX ZR1S-ABX
610 ZR1S-BCX ZR1S-BCX
611 ZR1S-CAX ZR1S-CAX
612 EXT CAR-R2 CARRIER RECEIVE FROM REMOTE TERM.2
613 OC TRIP-A OC trip signal (A-Phase)
614 OC TRIP-B OC trip signal (B-Phase)
615 OC TRIP-C OC trip signal (C-Phase)
616 OCI TRIP-A OCI trip signal (A-Phase)
617 OCI TRIP-B OCI trip signal (B-Phase)
618 OCI TRIP-C OCI trip signal (C-Phase)
619 C/R DISECHO Distance carrier echo signal
620 C/R DEFECHO DEF carrier echo signal
621 CHF-SV R1 CARRIER CHANNEL FAILURE (Remote terminal-1)
622 CHF-SV R2 CARRIER CHANNEL FAILURE (Remote terminal-2)
623 TP-A Trip A-phase command without off-delay timer
624 TP-B Trip B-phase command without off-delay timer
625 TP-C Trip C-phase command without off-delay timer
626 ZFG-AX ZFG-AX
627 ZFG-BX ZFG-BX
628 ZFG-CX ZFG-CX
629 ZR1G-AX ZR1G-AX
630 ZR1G-BX ZR1G-BX
Contents No. Signal Name
269
6 F 2 S 0 8 5 1
Signal list
631 ZR1G-CX ZR1G-CX
632 ZR2G-AX ZR2G-AX
633 ZR2G-BX ZR2G-BX
634 ZR2G-CX ZR2G-CX
635 ZFS-ABX ZFS-ABX
636 ZFS-BCX ZFS-BCX
637 ZFS-CAX ZFS-CAX
638 ZR2S-ABX ZR2S-ABX
639 ZR2S-BCX ZR2S-BCX
640 ZR2S-CAX ZR2S-CAX
641 Z2G-A TRIP Z2G TRIP A ph.
642 Z2G-B TRIP Z2G TRIP B ph.
643 Z2G-C TRIP Z2G TRIP C ph.
644 Z3G-A TRIP Z3G TRIP A ph.
645 Z3G-B TRIP Z3G TRIP B ph.
646 Z3G-C TRIP Z3G TRIP C ph.
647 ZFG TRIP ZFG TRIP
648 ZFG-A TRIP ZFG TRIP A ph.
649 ZFG-B TRIP ZFG TRIP B ph.
650 ZFG-C TRIP ZFG TRIP C ph.
651 ZFS TRIP ZFS TRIP
652 ZR1G-A TRIP ZR1G TRIP A ph.
653 ZR1G-B TRIP ZR1G TRIP B ph.
654 ZR1G-C TRIP ZR1G TRIP C ph.
655 ZR2G TRIP ZR2G TRIP
656 ZR2G-A TRIP ZR2G TRIP A ph.
657 ZR2G-B TRIP ZR2G TRIP B ph.
658 ZR2G-C TRIP ZR2G TRIP C ph.
659 ZR2S TRIP ZR2S TRIP
660 Z1GOR Z1G RELAY OR LOGIC
661 Z1SOR Z1S RELAY OR LOGIC
662 ZFGOR ZFG RELAY OR LOGIC
663 ZFSOR ZFS RELAY OR LOGIC
664 ZR2GOR ZR2G RELAY OR LOGIC
665 ZR2SOR ZR2S RELAY OR LOGIC
666 ZNDG-AX ZNDG-AX
667 ZNDG-BX ZNDG-BX
668 ZNDG-CX ZNDG-CX
669 ZNDS-ABX ZNDS-ABX
670 ZNDS-BCX ZNDS-BCX
671 ZNDS-CAX ZNDS-CAX
672 ZNDG TRIP ZNDG TRIP
673 ZNDG-A TRIP ZNDG TRIP A ph.
674 ZNDG-B TRIP ZNDG TRIP B ph.
675 ZNDG-C TRIP ZNDG TRIP C ph.
676 ZNDS TRIP ZNDS TRIP
677 DEF TRIP DEF BACK-UP TRIP
678 EF TRIP EF BACK-UP TRIP
679 STUB-A TRIP Stub TRIP A ph.
680 STUB-B TRIP Stub TRIP B ph.
681 STUB-C TRIP Stub TRIP C ph.
682 SOTF-A TRIP SOTF-OCH TRIP A ph.
683 SOTF-B TRIP SOTF-OCH TRIP B ph.
684 SOTF-C TRIP SOTF-OCH TRIP C ph.
685 SOTF-Z TRIP SOTF-Zistance TRIP
686 OCH TRIP OCH TRIP
687 OCH-A TRIP OCH TRIP A ph.
688 OCH-B TRIP OCH TRIP B ph.
689 OCH-C TRIP OCH TRIP C ph.
690 THM ALARM THERMAL ALARM
691 THM TRIP THERMAL TRIP
692 CBF RETRIP RE-TRIP FOR CBF
693 CBF TRIP-A RELATED CB TRIP A ph. FOR CBF
694 CBF TRIP-B RELATED CB TRIP B ph. FOR CBF
695 CBF TRIP-C RELATED CB TRIP C ph. FOR CBF
696 PSBGOUT-AX PSBGOUT-AX
697 PSBGOUT-BX PSBGOUT-BX
698 PSBGOUT-CX PSBGOUT-CX
699 PSBGIN-AX PSBGIN-AX
700 PSBGIN-BX PSBGIN-BX
Contents No. Signal Name
270
6 F 2 S 0 8 5 1
Signal list
701 PSBGIN-CX PSBGIN-CX
702 PSBS DET PSB for ZS DETECTION
703 PSBG DET PSB for ZG DETECTION
704 ZF TRIP ZONE-F TRIP
705 ZR2 TRIP ZONE-R2 TRIP
706 ZND TRIP ZONE-ND TRIP
707 SHOT NUM1 Trip/Auto-Reclosing shot number1 condition
708 SHOT NUM2 Trip/Auto-Reclosing shot number2 condition
709 SHOT NUM3 Trip/Auto-Reclosing shot number3 condition
710 SHOT NUM4 Trip/Auto-Reclosing shot number4 condition
711 SHOT NUM5 Trip/Auto-Reclosing shot number5 condition
712 Z1CNT INST Z1 CONTROL COMMAND (Instantly trip)
713 Z1CNT 3PTP Z1 CONTROL COMMAND (3-phase trip)
714 Z1CNT ARCBLK Z1 CONTROL COMMAND (Autoreclosing block)
715 Z1CNT TPBLK Z1 CONTROL COMMAND (Trip block)
716 ZNDGOR ZNDG RELAY OR LOGIC
717 ZNDSOR ZNDS RELAY OR LOGIC
718
719
720 ZGC-AX CARRIER CONTROL RELAY(Z2G/Z3G-A ph.)
721 ZGC-BX CARRIER CONTROL RELAY(Z2G/Z3G-B ph.)
722 ZGC-CX CARRIER CONTROL RELAY(Z2G/Z3G-C ph.)
723 C/R PUP-A CARRIER SEND FOR PUTT (ZG-A ph.)
724 C/R PUP-B CARRIER SEND FOR PUTT (ZG-B ph.)
725 C/R_PUP-C CARRIER SEND FOR PUTT (ZG-C ph.)
726 C/R_PUP-S CARRIER SEND FOR PUTT (ZS)
727 PUP_TRIP-A PUTT LOCAL TRIP (A ph.)
728 PUP TRIP-B PUTT LOCAL TRIP (B ph.)
729 PUP TRIP-C PUTT LOCAL TRIP (C ph.)
730 C/R POUP-A CARRIER SEND FOR POTT/UNBLOCK (ZG-A ph.)
731 C/R POUP-B CARRIER SEND FOR POTT/UNBLOCK (ZG-B ph.)
732 C/R POUP-C CARRIER SEND FOR POTT/UNBLOCK (ZG-C ph.)
733 C/R POUP-S CARRIER SEND FOR POTT/UNBLOCK (ZS)
734 POUP TRIP-A POTT/UNBLOCK LOCAL TRIP (A ph.)
735 POUP TRIP-B POTT/UNBLOCK LOCAL TRIP (B ph.)
736 POUP TRIP-C POTT/UNBLOCK LOCAL TRIP (C ph.)
737 REV BLK-A CARRIER SEND FOR BLOCK (ZG-A ph.)
738 REV BLK-B CARRIER SEND FOR BLOCK (ZG-B ph.)
739 REV BLK-C CARRIER SEND FOR BLOCK (ZG-C ph.)
740 REV BLK-S CARRIER SEND FOR BLOCK (ZS)
741 C/R BOP-A CARRIER SEND FOR BLOCKING (ZG-A ph.)
742 C/R BOP-B CARRIER SEND FOR BLOCKING (ZG-B ph.)
743 C/R BOP-C CARRIER SEND FOR BLOCKING (ZG-C ph.)
744 C/R BOP-S CARRIER SEND FOR BLOCKING (ZS)
745 BOP TRIP-A BLOCKING LOCAL TRIP (A ph.)
746 BOP TRIP-B BLOCKING LOCAL TRIP (B ph.)
747 BOP TRIP-C BLOCKING LOCAL TRIP (C ph.)
748 C/R DEF-A DEF CARRIER SEND (PUTT,POTT,UNBLOCK) (A ph.)
749 C/R DEF-B DEF CARRIER SEND (PUTT,POTT,UNBLOCK) (B ph.)
750 C/R DEF-C DEF CARRIER SEND (PUTT,POTT,UNBLOCK) (C ph.)
751 DEFCR TRIP-A DEF CARRIER LOCAL TRIP (PUTT,POTT,UNBLOCK) (A ph.)
752 DEFCR TRIP-B DEF CARRIER LOCAL TRIP (PUTT,POTT,UNBLOCK) (B ph.)
753 DEFCR TRIP-C DEF CARRIER LOCAL TRIP (PUTT,POTT,UNBLOCK) (C ph.)
754 C/R DEFBOP-A DEF CARRIER SEND (BLOCKING) (A ph.)
755 C/R DEFBOP-B DEF CARRIER SEND (BLOCKING) (B ph.)
756 C/R DEFBOP-C DEF CARRIER SEND (BLOCKING) (C ph.)
757 DEFBOP TRIP-A DEF CARRIER LOCAL TRIP (BLOCKING) (A ph.)
758 DEFBOP TRIP-B DEF CARRIER LOCAL TRIP (BLOCKING) (B ph.)
759 DEFBOP TRIP-C DEF CARRIER LOCAL TRIP (BLOCKING) (C ph.)
760 POUP TRIP POUP TRIP
761 BOP TRIP BOP TRIP
762 REV BLK-DEF DEF CARRIER SEND FOR BLOCK
763 DEFR TRIP DEFR BACK-UP TRIP
764 UVSBLK UVS BLOCK
765 UVGBLK UVG BLOCK
766 BCD BCD relay element output
767 BCD TRIP BCD TRIP
768 C/R DISECHO-A CARRIER SEND FOR ECHO (ZG-A ph.)
769 C/R DISECHO-B CARRIER SEND FOR ECHO (ZG-B ph.)
770 C/R DISECHO-C CARRIER SEND FOR ECHO (ZG-C ph.)
Contents No. Signal Name
271
6 F 2 S 0 8 5 1
Signal list
771 C/R DISECHO-S CARRIER SEND FOR ECHO (ZS)
772 C/R DEFECHO-A DEF CARRIER SEND FOR ECHO (A ph.)
773 C/R DEFECHO-B DEF CARRIER SEND FOR ECHO (B ph.)
774 C/R DEFECHO-C DEF CARRIER SEND FOR ECHO (C ph.)
775 WI TRIP-A WEEK INFEED LOCAL TRIP (A ph.)
776 WI TRIP-B WEEK INFEED LOCAL TRIP (B ph.)
777 WI TRIP-C WEEK INFEED LOCAL TRIP (C ph.)
778 DEFWI TRIP-A DEF CARRIER WEEK INFEED LOCAL TRIP (A ph.)
779 DEFWI TRIP-B DEF CARRIER WEEK INFEED LOCAL TRIP (B ph.)
780 DEFWI TRIP-C DEF CARRIER WEEK INFEED LOCAL TRIP (C ph.)
781
782
783
784 DISCR TRIP DISTANCE CARRIER TRIP
785 DISCR-A TRIP DISTANCE CARRIER TRIP (A ph.)
786 DISCR-B TRIP DISTANCE CARRIER TRIP (B ph.)
787 DISCR-C TRIP DISTANCE CARRIER TRIP (C ph.)
788 DEFCR-A TRIP DEF CARRIER TRIP (A ph.)
789 DEFCR-B TRIP DEF CARRIER TRIP (B ph.)
790 DEFCR-C TRIP DEF CARRIER TRIP (C ph.)
791 PSBTP TRIP PSBTP CARRIER TRIP
792 PSBTP-A TRIP PSBTP CARRIER TRIP (A ph.)
793 PSBTP-B TRIP PSBTP CARRIER TRIP (B ph.)
794 PSBTP-C TRIP PSBTP CARRIER TRIP (C ph.)
795
796
797
798
799
800 C/R SEND-A DISTANCE CARRIER SEND COMMAND (ZG-A ph.)
801 C/R SEND-B DISTANCE CARRIER SEND COMMAND (ZG-B ph.)
802 C/R SEND-C DISTANCE CARRIER SEND COMMAND (ZG-C ph.)
803 C/R SEND-S DISTANCE CARRIER SEND COMMAND (ZS)
804 C/R SEND-DEFA DEF CARRIER SEND COMMAND (A ph.)
805 C/R SEND-DEFB DEF CARRIER SEND COMMAND (B ph.)
806 C/R SEND-DEFC DEF CARRIER SEND COMMAND (C ph.)
807
808
809
810
811
812 C/R SEND-PSBA PSBTP CARRIER SEND COMMAND (A ph.)
813 C/R SEND-PSBB PSBTP CARRIER SEND COMMAND (B ph.)
814 C/R SEND-PSBC PSBTP CARRIER SEND COMMAND (C ph.)
815 C/R SEND-PSB PSBTP CARRIER SEND COMMAND
816 CAR-R-R1 Distance carrier OR signal from remote term-1
817 DEFCAR-R-R1 DEF carrier OR signal from remote term-1
818 PSBCAR-R-R1 PSB carrier OR signal from remote term-1
819
820 CAR-R-R2 Distance carrier OR signal from remote term-2
821 DEFCAR-R-R2 DEF carrier OR signal from remote term-2
822 PSBCAR-R-R2 PSB carrier OR signal from remote term-2
823
824
825
826
827
828
829
830
831
832 TR1 TRIP TRANSFER TRIP-1
833 TR1-A TRIP TRANSFER TRIP-1 (A ph.)
834 TR1-B TRIP TRANSFER TRIP-1 (B ph.)
835 TR1-C TRIP TRANSFER TRIP-1 (C ph.)
836 INTER TRIP1 INTER TRIP-1
837 INTER TRIP1-A INTER TRIP-1 (A ph.)
838 INTER TRIP1-B INTER TRIP-1 (B ph.)
839 INTER TRIP1-C INTER TRIP-1 (C ph.)
840 TR2 TRIP TRANSFER TRIP-2
Contents No. Signal Name
272
6 F 2 S 0 8 5 1
Signal list
841 TR2-A TRIP TRANSFER TRIP-2 (A ph.)
842 TR2-B TRIP TRANSFER TRIP-2 (B ph.)
843 TR2-C TRIP TRANSFER TRIP-2 (C ph.)
844 INTER TRIP2 INTER TRIP-2
845 INTER TRIP2-A INTER TRIP-2 (A ph.)
846 INTER TRIP2-B INTER TRIP-2 (B ph.)
847 INTER TRIP2-C INTER TRIP-2 (C ph.)
848 LOCAL TEST LOCAL TESTING SW ON
849 ARCMD ALARM PLC Autoreclosing mode discrepancy alarm
850
851 NTP FL TRG FL calculation trigger by no tripping
852
853
854
855
856
857
858
859
860 Z4G-X-OR Z4G-X (3PHASE OR)
861 Z4SCX Z4S-X (3PHASE OR)
862 OC OP-OR OC OP (3PHASE OR)
863 CBF-OR CBF (3PHASE OR)
864 OVS1 OP-OR OVS1 OP (3PHASE OR)
865 OVS2_OP-OR OVS2 OP (3PHASE OR)
866 OVG1_OP-OR OVG1 OP (3PHASE OR)
867 OVG2_OP-OR OVG2 OP (3PHASE OR)
868 UVS1 OP-OR UVS1 OP (3PHASE OR)
869 UVS2 OP-OR UVS2 OP (3PHASE OR)
870 UVG1 OP-OR UVG1 OP (3PHASE OR)
871 UVG2 OP-OR UVG2 OP (3PHASE OR)
872 WI TRIP-OR WI TRIP (3PHASE OR)
873 DEFWI TRIP-OR DEFWI TRIP (3PHASE OR)
874
875
876
877
878
879
880 SEVERE CF Severe CF detection
881 SEVERE CF-L Severe CF detection at local terminal
882 DATA.CH1-DIS CH1 receiving data disable
883 DATA.CH2-DIS CH2 receiving data disable
884 BUCAR MODE Back up carrier mode condition
885
886
887
888 MASTER Being set to master terminal
889 SLAVE Being set to slave terminal
890 CH1.DATA USE CH1 comm.data using
891 CH2.DATA USE CH2 comm.data using
892
893
894
895
896 REM1 READY Remote term.1 ready condition
897 CF1 Remote term.1 comm.fail
898 SPF1 Remote term.1 SP.sync.fail
899
900 COMM1 FAIL Remote term.1 Comm.fail alarm (902+903+906+907)
901 READY1 Remote term.1 Ready alarm
902 UNREADY1 Remote term.1 Un-Ready alarm
903 CFSV1 Remote term.1 Comm.fail alarm
904 SPSV1 Remote term.1 SP.sync.fail alarm
905 TX LEVEL1 Remote term.1 Transmission signal level drop alarm
906 RX LEVEL1 Remote term.1 Receiving signal level drop alarm
907 CLK1 Remote term.1 Clock signal interruption alarm
908 CFSV1-L Remote term.1 Receiving Comm.fail alarm
909 CFSV1-R Remote term.1 Sending Comm.fail alarm
910
Contents No. Signal Name
273
6 F 2 S 0 8 5 1
Signal list
911
912 REM2_READY Remote term.2 ready condition
913 CF2 Remote term.2 comm.fail
914 SPF2 Remote term.2 SP.sync.fail
915
916 COMM2_FAIL Remote term.2 Comm.fail alarm (918+919+922+923)
917 READY2 Remote term.2 Ready alarm
918 UNREADY2 Remote term.2 Un-Ready alarm
919 CFSV2 Remote term.2 Comm.fail alarm
920 SPSV2 Remote term.2 SP.sync.fail alarm
921 TX_LEVEL2 Remote term.2 Transmission signal level drop alarm
922 RX_LEVEL2 Remote term.2 Receiving signal level drop alarm
923 CLK2 Remote term.2 Clock signal interruption alarm
924 CFSV2-L Remote term.2 Receiving Comm.fail alarm
925 CFSV2-R Remote term.2 Sending Comm.fail alarm
926
927
928 CH1_CF Ch1 comm.fail (for Severe-CF detection)
929 CH1_CAN.CODE Ch1 cancel-code receiving (for Severe-CF detection)
930 CH1_CF-R1 Remote term 1 Ch1 comm.fail (for Severe-CF detection)
931 CH1_CAN-R1 Remote term 1 Ch1 cancel-code (for Severe-CF detection)
932
933 PORT1_FAIL LAN-Port1 fail condition
934 PORT2_FAIL LAN-Port2 fail condition
935 PORT1_ACT LAN-Port1 active
936 PORT2_ACT LAN-Port2 active
937 PORT1_INACT LAN-Port1 inactive
938 PORT2_INACT LAN-Port2 inactive
939 PORT1_LN_DOWN LAN-Port1 link down
940 PORT2_LN_DOWN LAN-Port2 link down
941
942
943
944 CH2_CF Ch2 comm.fail (for Severe-CF detection)
945 CH2_CAN.CODE Ch2 cancel-code receiving (for Severe-CF detection)
946 CH2_CF-R1 Remote term 1 Ch2 comm.fail (for Severe-CF detection)
947 CH2_CAN-R1 Remote term 1 Ch2 cancel-code (for Severe-CF detection)
948
949 OVS1_TRIP OVS1 TRIP
950 OVS1-AB_TRIP OVS1-AB TRIP
951 OVS1-BC_TRIP OVS1-BC TRIP
952 OVS1-CA_TRIP OVS1-CA TRIP
953 OVS2_ALARM OVS2 ALARM
954 OVS2-AB_ALM OVS2-AB ALARM
955 OVS2-BC_ALM OVS2-BC ALARM
956 OVS2-CA_ALM OVS2-CA ALARM
957 OVG1_TRIP OVG1 TRIP
958 OVG1-A_TRIP OVG1-AB TRIP
959 OVG1-B_TRIP OVG1-BC TRIP
960 OVG1-C_TRIP OVG1-CA TRIP
961 OVG2_ALARM OVG2 ALARM
962 OVG2-A_ALM OVG2-AB ALARM
963 OVG2-B_ALM OVS2-BC ALARM
964 OVG2-C_ALM OVG2-CA ALARM
965 UVS1_TRIP UVS1 TRIP
966 UVS1-AB_TRIP UVS1-AB TRIP
967 UVS1-BC_TRIP UVS1-BC TRIP
968 UVS1-CA_TRIP UVS1-CA TRIP
969 UVS2_ALARM UVS2 ALARM
970 UVS2-AB_ALM UVS2-AB ALARM
971 UVS2-BC_ALM UVS2-BC ALARM
972 UVS2-CA_ALM UVS2-CA ALARM
973 UVG1_TRIP UVG1 TRIP
974 UVG1-A_TRIP UVG1-AB TRIP
975 UVG1-B_TRIP UVG1-BC TRIP
976 UVG1-C_TRIP UVS1-CA TRIP
977 UVG2_ALARM UVG2 ALARM
978 UVG2-A_ALM UVG2-AB ALARM
979 UVG2-B_ALM UVG2-BC ALARM
980 UVG2-C_ALM UVG2-CA ALARM
Contents No. Signal Name
274
6 F 2 S 0 8 5 1
Signal list
981 OVS1-AB_RST OVS1-AB relay element delayed reset
982 OVS1-BC_RST OVS1-BC relay element delayed reset
983 OVS1-CA_RST OVS1-CA relay element delayed reset
984 OVG1-A_RST OVG1-A relay element delayed reset
985 OVG1-B_RST OVG1-B relay element delayed reset
986 OVG1-C_RST OVG1-C relay element delayed reset
987 UVS1-AB_RST UVS1-AB relay element delayed reset
988 UVS1-BC_RST UVS1-BC relay element delayed reset
989 UVS1-CA_RST UVS1-CA relay element delayed reset
990 UVG1-A_RST UVG1-A relay element delayed reset
991 UVG1-B_RST UVG1-B relay element delayed reset
992 UVG1-C_RST UVG1-C relay element delayed reset
993 OV/UV_TRIP OV/UV trip
994
995
996
997
998
999
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
1013
1014
1015
1016
1017
1018
1019
1020
1021
1022
1023
1024
1025
1026
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
1038
1039
1040 FAULT_PHA_A fault_phase_A
1041 FAULT_PHA_B fault_phase_B
1042 FAULT_PHA_C fault_phase_C
1043 FAULT_PHA_N fault_phase_N
1044 FL_ERR fault location start up error
1045 FL_OB_FWD fault location out of bounds(forward)
1046 FL_OB_BACK fault location out of bounds(backward)
1047 FL_NC fault location not converged
1048 FL_COMPLETED fault location completed
1049 FL_OJ fault location over junction
1050 FL_Z One-terminal fault location(TERM=3TERM)
Contents No. Signal Name
275
6 F 2 S 0 8 5 1
Signal list
1051
1052
1053
1054
1055
1056
1057
1058
1059
1060
1061
1062
1063
1064
1065
1066
1067
1068
1069
1070
1071
1072
1073
1074
1075
1076
1077
1078
1079
1080
1081
1082
1083
1084
1085
1086
1087
1088 COM1-R1 Comm. data receive signal from remote term-1
1089 COM2-R1 ditto
1090 COM3-R1 ditto
1091 COM4-R1 ditto
1092 COM5-R1 ditto
1093 COM6-R1 ditto
1094 COM7-R1 ditto
1095 COM8-R1 ditto
1096 COM9-R1 ditto
1097 COM10-R1 ditto
1098 COM11-R1 ditto
1099 COM12-R1 ditto
1100 COM13-R1 ditto
1101 COM14-R1 ditto
1102
1103
1104 COM1-R1_UF Comm. data receive signal from remote term-1 (unfiltered)
1105 COM2-R1_UF ditto
1106 COM3-R1_UF ditto
1107 COM4-R1_UF ditto
1108 COM5-R1_UF ditto
1109 COM6-R1_UF ditto
1110 COM7-R1_UF ditto
1111 COM8-R1_UF ditto
1112 COM9-R1_UF ditto
1113 COM10-R1_UF ditto
1114 COM11-R1_UF ditto
1115 COM12-R1_UF ditto
1116 COM13-R1_UF ditto
1117 COM14-R1_UF ditto
1118
1119
1120 SUB_COM1-R1 Sub comm. data receive signal from term-1
Contents No. Signal Name
276
6 F 2 S 0 8 5 1
Signal list
1121 SUB_COM2-R1 ditto
1122 SUB_COM3-R1 ditto
1123 SUB_COM4-R1 ditto
1124 BUCAR-R1 Back up carrier mode in remote term-1 data
1125
1126
1127
1128
1129
1130
1131
1132
1133
1134
1135
1136 COM1-R2 Comm. data receive signal from remote term-2
1137 COM2-R2 ditto
1138 COM3-R2 ditto
1139 COM4-R2 ditto
1140 COM5-R2 ditto
1141 COM6-R2 ditto
1142 COM7-R2 ditto
1143 COM8-R2 ditto
1144 COM9-R2 ditto
1145 COM10-R2 ditto
1146 COM11-R2 ditto
1147 COM12-R2 ditto
1148 COM13-R2 ditto
1149 COM14-R2 ditto
1150
1151
1152 COM1-R2_UF Comm. data receive signal from remote term-2 (unfiltered)
1153 COM2-R2_UF ditto
1154 COM3-R2_UF ditto
1155 COM4-R2_UF ditto
1156 COM5-R2_UF ditto
1157 COM6-R2_UF ditto
1158 COM7-R2_UF ditto
1159 COM8-R2_UF ditto
1160 COM9-R2_UF ditto
1161 COM10-R2_UF ditto
1162 COM11-R2_UF ditto
1163 COM12-R2_UF ditto
1164 COM13-R2_UF ditto
1165 COM14-R2_UF ditto
1166
1167
1168 SUB_COM1-R2 Sub comm. data receive signal from term-2
1169 SUB_COM2-R2 ditto
1170 SUB_COM3-R2 ditto
1171 SUB_COM4-R2 ditto
1172 BUCAR-R2 Back up carrier mode in remote term-2 data
1173
1174
1175
1176
1177
1178
1179
1180
1181
1182
1183
1184
1185
1186
1187
1188
1189
1190
Contents No. Signal Name
277
6 F 2 S 0 8 5 1
Signal list
1191
1192
1193
1194
1195
1196
1197
1198
1199
1200
1201
1202
1203
1204
1205
1206
1207
1208
1209
1210
1211
1212
1213
1214
1215
1216
1217
1218
1219
1220
1221
1222
1223
1224
1225
1226
1227
1228
1229
1230
1231
1232
1233
1234
1235
1236
1237
1238
1239
1240
1241 IEC_MDBLK monitor direction blocked
1242 IEC_TESTMODE IEC61870-5-103 testmode
1243 GROUP1_ACTIVE group1 active
1244 GROUP2_ACTIVE group2 active
1245 GROUP3_ACTIVE group3 active
1246 GROUP4_ACTIVE group4 active
1247 GROUP5_ACTIVE group5 active
1248 GROUP6_ACTIVE group6 active
1249 GROUP7_ACTIVE group7 active
1250 GROUP8_ACTIVE group8 active
1251 RLY_FAIL RELAY FAILURE
1252 RLY_OP_BLK RELAY OUTPUT BLOCK
1253 AMF_OFF SV BLOCK
1254
1255
1256
1257
1258 RELAY_FAIL-A
1259
1260
Contents No. Signal Name
278
6 F 2 S 0 8 5 1
Signal list
1261 TRIP-H Trip signal hold
1262 CT ERR UF CT error(unfiltered)
1263 I0 ERR UF I0 error(unfiltered)
1264 V0 ERR UF V0 error(unfiltered)
1265 V2 ERR UF V2 error(unfiltered)
1266 CT ERR CT error
1267 I0 ERR I0 error
1268 V0 ERR V0 error
1269 V2 ERR V2 error
1270
1271
1272
1273
1274
1275
1276 50/60Hz Frequency pulse signal
1277
1278
1279 GEN PICKUP General start/pick-up
1280 GEN TRIP General trip
1281
1282
1283
1284 BI1 COM UF Binary input signal BI1 (unfiltered)
1285 BI2 COM UF Binary input signal BI2 (unfiltered)
1286 BI3 COM UF Binary input signal BI3 (unfiltered)
1287 BI4 COM UF Binary input signal BI4 (unfiltered)
1288 BI5 COM UF Binary input signal BI5 (unfiltered)
1289 BI6 COM UF Binary input signal BI6 (unfiltered)
1290 BI7 COM UF Binary input signal BI7 (unfiltered)
1291 BI8 COM UF Binary input signal BI8 (unfiltered)
1292 BI9 COM UF Binary input signal BI9 (unfiltered)
1293 BI10 COM UF Binary input signal BI10 (unfiltered)
1294 BI11 COM UF Binary input signal BI11 (unfiltered)
1295 BI12 COM UF Binary input signal BI12 (unfiltered)
1296 BI13 COM UF Binary input signal BI13 (unfiltered)
1297 BI14 COM UF Binary input signal BI14 (unfiltered)
1298 BI15 COM UF Binary input signal BI15 (unfiltered)
1299 BI16 COM UF Binary input signal BI16 (unfiltered)
1300 BI17 COM UF Binary input signal BI17 (unfiltered)
1301 BI18 COM UF Binary input signal BI18 (unfiltered)
1302 BI19 COM UF Binary input signal BI19 (unfiltered)
1303 BI20 COM UF Binary input signal BI20 (unfiltered)
1304 BI21 COM UF Binary input signal BI21 (unfiltered)
1305 BI22 COM UF Binary input signal BI22 (unfiltered)
1306 BI23 COM UF Binary input signal BI23 (unfiltered)
1307 BI24 COM UF Binary input signal BI24 (unfiltered)
1308 BI25 COM UF Binary input signal BI25 (unfiltered)
1309 BI26 COM UF Binary input signal BI26 (unfiltered)
1310 BI27 COM UF Binary input signal BI27 (unfiltered)
1311 BI28 COM UF Binary input signal BI28 (unfiltered)
1312 BI34 COM UF Binary input signal BI34 (unfiltered)
1313 BI35 COM UF Binary input signal BI35 (unfiltered)
1314 BI36 COM UF Binary input signal BI36 (unfiltered)
1315
1316
1317
1318
1319
1320
1321
1322
1323
1324
1325
1326
1327
1328 GOOSE IN Q1 Goose Input Quality #1
1329 GOOSE IN Q2 Goose Input Quality #2
1330 GOOSE IN Q3 Goose Input Quality #3
Contents No. Signal Name
279
6 F 2 S 0 8 5 1
Signal list
1331 GOOSE IN Q4 Goose Input Quality #4
1332 GOOSE IN Q5 Goose Input Quality #5
1333 GOOSE IN Q6 Goose Input Quality #6
1334 GOOSE IN Q7 Goose Input Quality #7
1335 GOOSE IN Q8 Goose Input Quality #8
1336 GOOSE IN Q9 Goose Input Quality #9
1337 GOOSE IN Q10 Goose Input Quality #10
1338 GOOSE IN Q11 Goose Input Quality #11
1339 GOOSE IN Q12 Goose Input Quality #12
1340 GOOSE IN Q13 Goose Input Quality #13
1341 GOOSE IN Q14 Goose Input Quality #14
1342 GOOSE IN Q15 Goose Input Quality #15
1343 GOOSE IN Q16 Goose Input Quality #16
1344 GOOSE IN Q17 Goose Input Quality #17
1345 GOOSE IN Q18 Goose Input Quality #18
1346 GOOSE IN Q19 Goose Input Quality #19
1347 GOOSE IN Q20 Goose Input Quality #20
1348 GOOSE IN Q21 Goose Input Quality #21
1349 GOOSE IN Q22 Goose Input Quality #22
1350 GOOSE IN Q23 Goose Input Quality #23
1351 GOOSE IN Q24 Goose Input Quality #24
1352 GOOSE IN Q25 Goose Input Quality #25
1353 GOOSE IN Q26 Goose Input Quality #26
1354 GOOSE IN Q27 Goose Input Quality #27
1355 GOOSE IN Q28 Goose Input Quality #28
1356 GOOSE IN Q29 Goose Input Quality #29
1357 GOOSE IN Q30 Goose Input Quality #30
1358 GOOSE IN Q31 Goose Input Quality #31
1359 GOOSE IN Q32 Goose Input Quality #32
1360 GOOSE IN 1 Goose Input #1
1361 GOOSE IN 2 Goose Input #2
1362 GOOSE IN 3 Goose Input #3
1363 GOOSE IN 4 Goose Input #4
1364 GOOSE IN 5 Goose Input #5
1365 GOOSE IN 6 Goose Input #6
1366 GOOSE IN 7 Goose Input #7
1367 GOOSE IN 8 Goose Input #8
1368 GOOSE IN 9 Goose Input #9
1369 GOOSE IN 10 Goose Input #10
1370 GOOSE IN 11 Goose Input #11
1371 GOOSE IN 12 Goose Input #12
1372 GOOSE IN 13 Goose Input #13
1373 GOOSE IN 14 Goose Input #14
1374 GOOSE IN 15 Goose Input #15
1375 GOOSE IN 16 Goose Input #16
1376 GOOSE IN 17 Goose Input #17
1377 GOOSE IN 18 Goose Input #18
1378 GOOSE IN 19 Goose Input #19
1379 GOOSE IN 20 Goose Input #20
1380 GOOSE IN 21 Goose Input #21
1381 GOOSE IN 22 Goose Input #22
1382 GOOSE IN 23 Goose Input #23
1383 GOOSE IN 24 Goose Input #24
1384 GOOSE IN 25 Goose Input #25
1385 GOOSE IN 26 Goose Input #26
1386 GOOSE IN 27 Goose Input #27
1387 GOOSE IN 28 Goose Input #28
1388 GOOSE IN 29 Goose Input #29
1389 GOOSE IN 30 Goose Input #30
1390 GOOSE IN 31 Goose Input #31
1391 GOOSE IN 32 Goose Input #32
1392
1393
1394
1395
1396
1397
1398
1399
1400
Contents No. Signal Name
280
6 F 2 S 0 8 5 1
Signal list
1401 LOCAL OP ACT local operation active
1402 REMOTE OP ACT remote operation active
1403 NORM LED ON IN-SERVICE LED ON
1404 ALM LED ON ALARM LED ON
1405 TRIP LED ON TRIP LED ON
1406 TEST LED ON TEST LED ON
1407
1408 PRG LED RESET Latched progammable LED RESET
1409 LED RESET TRIP LED RESET
1410
1411 ARC COM ON IEC103 communication command
1412 TELE COM ON IEC103 communication command
1413 PROT COM ON IEC103 communication command
1414 PRG LED1 ON PROGRAMMABLE LED1 ON
1415 PRG LED2 ON PROGRAMMABLE LED2 ON
1416 PRG LED3 ON PROGRAMMABLE LED3 ON
1417 PRG LED4 ON PROGRAMMABLE LED4 ON
1418
1419
1420
1421
1422
1423
1424
1425
1426
1427
1428
1429
1430
1431
1432
1433
1434 F.Record DONE fault location completed
1435 F.Record CLR Fault record clear
1436 E.Record CLR Event record clear
1437 D.Record CLR Disturbance record clear
1438 Data Lost Data clear by BU-RAM memory monitoring error
1439
1440
1441
1442
1443
1444
1445 PLC data CHG PLC data change
1446 IEC103 data CHG IEC-103 data change
1447 IEC850 data CHG IEC-850 data change
1448 Sys.set change System setting change
1449 Rly.set change Relay setting change
1450 Grp.set change Group setting change
1451
1452
1453
1454
1455
1456 KEY-VIEW VIEW key status (1:pressed)
1457 KEY-RESET RESET key status (2:pressed)
1458 KEY-ENTER ENTER key status (3:pressed)
1459 KEY-END END key status (4:pressed)
1460 KEY-CANCEL CANCEL key status (5:pressed)
1461
1462
1463 TRIP chk fail Trip check fail
1464 TRIP out err Trip out error
1465 DC supply err DC supply error
1466 RTC err RTC stopped
1467 PCI err PCI bus error
1468 GOOSE stop GOOSE stopped
1469 Ping err Ping no anwer
1470 PLC err PLC stopeed
Contents No. Signal Name
281
6 F 2 S 0 8 5 1
Signal list
1471 61850 err 61850 stopped
1472 SUM err Program ROM checksum error
1473 ROM RAM err Rom - Ram mismatch error
1474 SRAM err SRAM memory monitoring error
1475 BU-RAM err BU-RAM memory monitoring error
1476
1477 EEPROM err EEPROM memory monitoring error
1478
1479 A/D err A/D accuracy checking error
1480 CPU err Program error
1481 Invalid Invalid error
1482 NMI NMI
1483 Sampling err Sampling error
1484 DIO err DIO card connection error
1485 LAN err LAN error
1486 LCD err LCD panel connection error
1487 ROM data err Data ROM checksum error
1488 COM int err GCOM interrupt error
1489 COM DPRAMerr1 DP-RAM memory monitoring error
1490 COM stopped GCOM stopped.
1491 COM SUM err GCOM sum error.
1492 COM ROM RAM err
1493 COM SRAM err
1494 COM DPRAMerr2
1495 COM_A/D_err
1496 COM_IRQ_err
1497 Sync1_fail
1498 Sync2 fail
1499 Com1 fail
1500 Com2 fail
1501 Com1 fail-R
1502 Com2 fail-R
1503 CLK1 fail
1504 CLK2 fail
1505 Term1 rdy off
1506 Term2 rdy off
1507 TX level1 err Tx signal power level out of range error(Ch1)
1508 TX level2 err Tx signal power level out of range error(Ch2)
1509 RX level1 err Rx signal power level out of range error(Ch1)
1510 RX level2 err Rx signal power level out of range error(Ch2)
1511 Td1 over Time difference is out of range(Ch1)
1512 Td2 over Time difference is out of range(Ch2)
1513 RYID1 err
1514 RYID2 err
1515
1516
1517
1518
1519
1520
1521
1522
1523
1524
1525
1526
1527
1528
1529
1530
1531
1532
1533
1534
1535 (reserved)
Contents No. Signal Name
282
6 F 2 S 0 8 5 1
Signal list
1536 CB1 CONT-A CB1 contact (A-phase)
1537 CB1 CONT-B (B-phase)
1538 CB1 CONT-C (C-phase)
1539
1540 Z1X INIT Z1X protection initiation command
1541 EXT VTF External VTF command
1542 DS N/O CONT DS N/O contact
1543 DS N/C CONT DS N/C contact
1544 ARC BLOCK Autoreclosing block command
1545 CB1 READY Autoreclisng ready command of bus CB
1546 CB2 READY Autoreclisng ready command of center CB
1547 ARC RESET Autoreclosing out of service command
1548 IND.RESET Indication reset command
1549 M-PROT TRIP Duplicated Main protection trip command
1550 M-PROT ON Duplicated Main protection in service command
1551
1552 CB2 CONT-A CB2 contact (A-phase)
1553 CB2 CONT-B (B-phase)
1554 CB2 CONT-C (C-phase)
1555
1556 EXT TRIP-A External trip comand (A-Phase)
1557 EXT TRIP-B (B-phase)
1558 EXT TRIP-C (C-phase)
1559
1560 EXT CBFIN-A External CBF initiation command (A-Phase)
1561 EXT CBFIN-B (B-Phase)
1562 EXT CBFIN-C (C-Phase)
1563
1564 ARC BLOCK1 Autoreclosing block command
1565 ARC BLOCK2 Autoreclosing block command
1566
1567
1568 EXT CAR.R1-1 Trip carrier from remote terminal-1
1569 EXT CAR.R1-2 Guard/And carrier from remote terminal-1
1570 OPEN TERM-R1 Remote terminal-1 out of service command
1571 SEVERE CF-R1 Severe CF information command from remote terminal-1
1572
1573
1574
1575
1576
1577
1578
1579
1580
1581
1582
1583
1584 EXT CAR.R2-1 Trip carrier from remote terminal-2
1585 EXT CAR.R2-2 Guard/And carrier from remote terminal-1
1586 OPEN TERM-R2 Remote terminal-2 out of service command
1587 SEVERE CF-R2 Severe CF information command from remote terminal-2
1588
1589
1590
1591
1592
1593
1594
1595
1596
1597
1598
1599
1600 PROT BLOCK Protection block command
Contents No. Signal Name
283
6 F 2 S 0 8 5 1
Signal list
1601 CRT BLOCK Carrier trip block command
1602 DISCRT BLOCK Carrier protection out of service command
1603 DEFCRT BLOCK DEF carrier trip block command
1604 PSBTP BLOCK PSBTP block command
1605 PSB BLOCK PSB detection block command
1606
1607
1608 OC-A FS Fail safe command for OC-A trip
1609 OC-B FS Fail safe command for OC-B trip
1610 OC-C FS Fail safe command for OC-C trip
1611
1612 OCI-A FS Fail safe command for OCI-A trip
1613 OCI-B FS Fail safe command for OCI-B trip
1614 OCI-C FS Fail safe command for OCI-C trip
1615 THMA BLOCK Thermal alarm block command
1616 Z1G BLOCK Z1G trip block command
1617 Z1XG BLOCK Z1XG trip block command
1618 Z2G BLOCK Z2G trip block command
1619 Z3G BLOCK Z3G trip block command
1620 ZR1G BLOCK ZR1G trip block command
1621 ZFG BLOCK ZFG trip block command
1622 STUB BLOCK Stub trip block command
1623 SOTF BLOCK SOTF trip block command
1624 OCH BLOCK OCH trip block command
1625 OC BLOCK OC trip block command
1626 OCI BLOCK OCI trip block command
1627 EF BLOCK EF trip block command
1628 EFI BLOCK EFI trip block command
1629 DEF BLOCK DEF trip block command
1630 OST BLOCK OST trip block command
1631 THM BLOCK Thermal trip block command
1632 Z1S BLOCK Z1S trip block command
1633 Z1XS BLOCK Z1XS trip block command
1634 Z2S BLOCK Z2S trip block command
1635 Z3S BLOCK Z3S trip block command
1636 ZR1S BLOCK ZR1S trip block command
1637 ZFS BLOCK ZFS trip block command
1638 ZR2G BLOCK ZR2G trip block command
1639 ZR2S BLOCK ZR2S trip block command
1640 CBF BLOCK CBF trip block command
1641 EXTTP BLOCK External trip block command
1642 VTF BLOCK VTF monitoering block command
1643 VTF ONLY ALM VTF only alarm command
1644 TR1 BLOCK Transfer trip 1 block command
1645 TR2 BLOCK Transfer trip 2 block command
1646 ZNDG BLOCK ZNDG trip block command
1647 ZNDS BLOCK ZNDS trip block command
1648 Z1S G-BLK Z1S block by multi-phase ground fault command
1649 STUB CB CB close command for stub protection
1650 OCHTP ON OCH trip pemmisive command
1651 PSB.F RESET PSB forcibly reset command
1652 DEF PHSEL-A Fault phase selection command for DEF
1653 DEF PHSEL-B ditto
1654 DEF PHSEL-C ditto
1655 Z1 ARC BLOCK Auto reclosing block command by Zone1 trip
1656 Z2G-A FS Z2G-A fail-safe command
1657 Z2G-B FS Z2G-B fail-safe command
1658 Z2G-C FS Z2G-C fail-safe command
1659 Z1X F.ENABLE Z1X forcibly enable command
1660
1661 EXT FLST TP External FL caluculation start command (by trip)
1662 EXT FLDS External FL data saving command
1663 EXT FLST NTP External FL caluculation start command (no trip)
1664 ZFG-A BLOCK ZFG-A block command
1665 ZFG-B BLOCK ZFG-B block command
1666 ZFG-C BLOCK ZFG-C block command
1667
1668 ZNDG-A COM ZNDG-A operating command
1669 ZNDG-B COM ZNDG-B operating command
1670 ZNDG-C COM ZNDG-C operating command
Contents No. Signal Name
284
6 F 2 S 0 8 5 1
Signal list
1671 ZNDS COM ZNDS operating command
1672 Z2G-A BLOCK Z2G-A block command
1673 Z2G-B BLOCK Z2G-B block command
1674 Z2G-C BLOCK Z2G-C block command
1675
1676
1677
1678
1679
1680 TP-A DELAY Trip command off-delay timer setting
1681 TP-B DELAY Trip command off-delay timer setting
1682 TP-C DELAY Trip command off-delay timer setting
1683 ARC OFF Autoreclosing mode changing command
1684 ARC SPAR ditto
1685 ARC TPAR ditto
1686 ARC S&T ditto
1687 ARC EXT1P ditto
1688 ARC EXT3P ditto
1689
1690
1691
1692
1693
1694
1695
1696 Z1_INST_TP Z1 instantly trip command
1697
1698 Z2 INST TP Z2 instantly trip command
1699 Z3 INST TP Z3 instantly trip command
1700 ZR1 INST TP ZR1 instantly trip command
1701 ZF INST TP ZF instantly trip command
1702 EF INST TP EF instantly trip command
1703 OC INST TP OC instantly trip command
1704
1705 DEF INST TP DEF instantly trip command
1706
1707 DEFR INST TP DEF instantly trip command
1708 ZR2 INST TP ZR2 instantly trip command
1709 ZND INST TP ZND instantly trip command
1710
1711
1712 Z1 3PTP Z1 3-phase trip command
1713 Z1X 3PTP Z1X 3-phase trip command
1714 Z2 3PTP Z2 3-phase trip command
1715
1716 OC 3PTP OC 3-phase trip command
1717 OCI 3PTP OCI 3-phase trip command
1718
1719
1720 CAR 3PTP Distance CAR 3-phase trip command
1721 DEFCAR 3PTP DEF.CAR 3-phase trip command
1722 PSBTP 3PTP PSBTP 3-phase trip command
1723
1724 TR1 3PTP Transfer trip 1 3-phase trip command
1725 TR2 3PTP Transfer trip 2 3-phase trip command
1726
1727 3P TRIP 3-Phase trip command
1728 CAR-A-R1 Distance carrier command from remote term-1
1729 CAR-B-R1 ditto
1730 CAR-C-R1 ditto
1731 CAR-S-R1 ditto
1732 DEFCAR-A-R1 DEF carrier command from remote term-1
1733 DEFCAR-B-R1 ditto
1734 DEFCAR-C-R1 ditto
1735
1736
1737
1738
1739
1740 PSBCAR-A-R1 PSBTP carrier command from remote term-1
Contents No. Signal Name
285
6 F 2 S 0 8 5 1
Signal list
1741 PSBCAR-B-R1 ditto
1742 PSBCAR-C-R1 ditto
1743
1744 TR1-A-R1 Transfer trip-1 command from remote term-1
1745 TR1-B-R1 ditto
1746 TR1-C-R1 ditto
1747
1748 TR2-A-R1 Transfer trip-2 command from remote term-1
1749 TR2-B-R1 ditto
1750 TR2-C-R1 ditto
1751
1752
1753
1754
1755
1756
1757
1758
1759
1760 CAR-A-R2 Distance carrier command from remote term-2
1761 CAR-B-R2 ditto
1762 CAR-C-R2 ditto
1763 CAR-S-R2 ditto
1764 DEFCAR-A-R2 DEF carrier command from remote term-2
1765 DEFCAR-B-R2 ditto
1766 DEFCAR-C-R2 ditto
1767
1768
1769
1770
1771
1772 PSBCAR-A-R2 PSBTP carrier command from remote term-2
1773 PSBCAR-B-R2 ditto
1774 PSBCAR-C-R2 ditto
1775
1776 TR1-A-R2 Transfer trip-1 command from remote term-2
1777 TR1-B-R2 ditto
1778 TR1-C-R2 ditto
1779
1780 TR2-A-R2 Transfer trip-2 command from remote term-2
1781 TR2-B-R2 ditto
1782 TR2-C-R2 ditto
1783
1784
1785
1786
1787
1788
1789
1790
1791
1792 IO#1-TP-A1 Binary output signal of TP-A1
1793 IO#1-TP-B1 TP-B1
1794 IO#1-TP-C1 TP-C1
1795 IO#1-TP-A2 Binary output signal of TP-A2
1796 IO#1-TP-B2 TP-B2
1797 IO#1-TP-C2 TP-C2
1798
1799
1800
1801
1802
1803
1804
1805
1806
1807
1808 OVS1_INST_TP OVS1 instantly trip command
1809 OVS2_INST_TP OVS2 instantly trip command
1810
Contents No. Signal Name
286
6 F 2 S 0 8 5 1
Signal list
1811
1812 OVG1 INST TP OVG1 instantly trip command
1813 OVG2 INST TP OVG2 instantly trip command
1814
1815
1816 UVS1 INST TP UVS1 instantly trip command
1817 UVS2 INST TP UVS2 instantly trip command
1818
1819
1820 UVG1 INST TP UVG1 instantly trip command
1821 UVG2 INST TP UVG2 instantly trip command
1822
1823
1824 SPR.L-REQ Leader SPAR requirement
1825 TPR.L-REQ Leader TPAR requirement
1826 SPR.F-REQ Follower SPAR requirement
1827 TPR.F-REQ Follower TPAR requirement
1828 SPR.F-ST.REQ Follower SPAR starting requirement
1829 TPR.F-ST.REQ Follower TPAR starting requirement
1830
1831
1832 R.F-ST.REQ Follower AR starting requirement
1833 SPR.F2-REQ Follower SPAR requirement
1834 TPR.F2-REQ Follower TPAR requirement
1835
1836
1837
1838 ARC.L TERM Leader terminal of Autoreclosing
1839 ARC.F TERM Follower terminal of Autoreclosing
1840
1841
1842
1843
1844
1845
1846
1847
1848 BCD BLOCK BCD trip block command
1849 DEFF BLOCK DEFF trip block command
1850
1851 DEFR BLOCK DEFR trip block command
1852
1853
1854
1855
1856 OVS1 BLOCK OVS1 trip block command
1857 OVS2 BLOCK OVS2 trip block command
1858
1859
1860 OVG1 BLOCK OVG1 trip block command
1861 OVG2 BLOCK OVG2 trip block command
1862
1863
1864 UVS1 BLOCK UVS1 trip block command
1865 UVS2 BLOCK UVS2 trip block command
1866
1867
1868 UVG1 BLOCK UVG1 trip block command
1869 UVG2 BLOCK UVG2 trip block command
1870
1871
1872
1873
1874
1875
1876
1877
:
:
2040
Contents No. Signal Name
287
6 F 2 S 0 8 5 1
Signal list
2041
2042
2043
2044
2045
2046
2047
2048 COM1-S Communication on/off data send command
2049 COM2-S ditto
2050 COM3-S ditto
2051 COM4-S ditto
2052 COM5-S ditto
2053 COM6-S ditto
2054 COM7-S ditto
2055 COM8-S ditto
2056 COM9-S ditto
2057 COM10-S ditto
2058 COM11-S ditto
2059 COM12-S ditto
2060 COM13-S ditto
2061 COM14-S ditto
2062
2063
2064 SUB COM1-S Sub communication on/off data send command
2065 SUB COM2-S ditto
2066 SUB COM3-S ditto
2067 SUB COM4-S ditto
2068
2069
2070
2071
2072
2073
2074
2075
2076
2077
2078
2079
2080 CHG PORT2 LAN-Port change command (from port1 to port2)
2081 CHG PORT1 LAN-Port change command (from port2 to port1)
2082
2083
2084
2085
2086
2087
2088
2089
2090
2091
2092
2093
2094
2095
2096
2097
2098
2099
2100
2101
2102
2103
2104
2105
2106
2107
:
:
2580
Contents No. Signal Name
288
6 F 2 S 0 8 5 1
Signal list
2581
2582
2583
2584
2585
2586
2587
2588
2589
2590
2591
2592
2593
2594
2595
2596
2597
2598
2599
2600
2601
2602
2603
2604
2605
2606
2607
2608
2609
2610 ALARM_LED_SET Alarm LED set
2611
2612
2613
2614
2615
2616
2617
2618
2619
2620
2621
2622
2623
2624 F.RECORD1 Fault record stored command 1
2625 F.RECORD2 Fault record stored command 2
2626 F.RECORD3 Fault record stored command 3
2627 F.RECORD4 Fault record stored command 4
2628
2629
2630
2631
2632 D.RECORD1 Disturbance record stored command 1
2633 D.RECORD2 Disturbance record stored command 2
2634 D.RECORD3 Disturbance record stored command 3
2635 D.RECORD4 Disturbance record stored command 4
2636
2637
2638
2639
2640 SET.GROUP1 Active setting group changed commamd (Change to group1)
2641 SET.GROUP2 2
2642 SET.GROUP3 3
2643 SET.GROUP4 4
2644 SET.GROUP5 5
2645 SET.GROUP6 6
2646 SET.GROUP7 7
2647 SET.GROUP8 8
2648
2649
2650
Contents No. Signal Name
289
6 F 2 S 0 8 5 1
Signal list
2651
2652
2653
2654
2655
2656 CON_TPMD1 User configrable trip mode in fault record
2657 CON_TPMD2 ditto
2658 CON_TPMD3 ditto
2659 CON_TPMD4 ditto
2660 CON_TPMD5 ditto
2661 CON_TPMD6 ditto
2662 CON_TPMD7 ditto
2663 CON_TPMD8 ditto
2664
2665
2666
2667
2668
2669
2670
2671
2672
2673
2674
2675
2676
2677
2678
2679
2680
2681
2682
2683
2684 ARC_COM_RECV Auto-recloser inactivate command received
2685 TELE_COM_RECV Teleprotection inactivate command received
2686 PROT_COM_RECV protection inactivate command received
2687
2688 TPLED_RST_RCV TRIP LED RESET command received
2689
2690
2691
2692
2693
2694
2695
2696
2697
2698
2699
2700
2701
2702
2703
2704
2705
2706
2707
2708
2709
2710
2711
2712
2713
2714
2715
2716
2717
:
:
2790
Contents No. Signal Name
290
6 F 2 S 0 8 5 1
Signal list
2791
2792
2793
2794
2795
2796
2797
2798
2799
2800
2801
2802
2803
2804
2805
2806
2807
2808
2809
2810
2811
2812
2813
2814
2815
2816 TEMP001
2817 TEMP002
2818 TEMP003
2819 TEMP004
2820 TEMP005
2821 TEMP006
2822 TEMP007
2823 TEMP008
2824 TEMP009
2825 TEMP010
2826 TEMP011
2827 TEMP012
2828 TEMP013
2829 TEMP014
2830 TEMP015
2831 TEMP016
2832 TEMP017
2833 TEMP018
2834 TEMP019
2835 TEMP020
2836 TEMP021
2837 TEMP022
2838 TEMP023
2839 TEMP024
2840 TEMP025
2841 TEMP026
2842 TEMP027
2843 TEMP028
2844 TEMP029
2845 TEMP030
2846 TEMP031
2847 TEMP032
2848 TEMP033
2849 TEMP034
2850 TEMP035
2851 TEMP036
2852 TEMP037
2853 TEMP038
2854 TEMP039
2855 TEMP040
2856 TEMP041
2857 TEMP042
2858 TEMP043
2859 TEMP044
2860 TEMP045
Contents No. Signal Name
291
6 F 2 S 0 8 5 1
Signal list
2861 TEMP046
2862 TEMP047
2863 TEMP048
2864 TEMP049
2865 TEMP050
2866 TEMP051
2867 TEMP052
2868 TEMP053
2869 TEMP054
2870 TEMP055
2871 TEMP056
2872 TEMP057
2873 TEMP058
2874 TEMP059
2875 TEMP060
2876 TEMP061
2877 TEMP062
2878 TEMP063
2879 TEMP064
2880 TEMP065
2881 TEMP066
2882 TEMP067
2883 TEMP068
2884 TEMP069
2885 TEMP070
2886 TEMP071
2887 TEMP072
2888 TEMP073
2889 TEMP074
2890 TEMP075
2891 TEMP076
2892 TEMP077
2893 TEMP078
2894 TEMP079
2895 TEMP080
2896 TEMP081
2897 TEMP082
2898 TEMP083
2899 TEMP084
2900 TEMP085
2901 TEMP086
2902 TEMP087
2903 TEMP088
2904 TEMP089
2905 TEMP090
2906 TEMP091
2907 TEMP092
2908 TEMP093
2909 TEMP094
2910 TEMP095
2911 TEMP096
2912 TEMP097
2913 TEMP098
2914 TEMP099
2915 TEMP100
2916 TEMP101
2917 TEMP102
2918 TEMP103
2919 TEMP104
2920 TEMP105
2921 TEMP106
2922 TEMP107
2923 TEMP108
2924 TEMP109
2925 TEMP110
2926 TEMP111
2927 TEMP112
2928 TEMP113
2929 TEMP114
2930 TEMP115
Contents No. Signal Name
292
6 F 2 S 0 8 5 1
Signal list
2931 TEMP116
2932 TEMP117
2933 TEMP118
2934 TEMP119
2935 TEMP120
2936 TEMP121
2937 TEMP122
2938 TEMP123
2939 TEMP124
2940 TEMP125
2941 TEMP126
2942 TEMP127
2943 TEMP128
2944 TEMP129
2945 TEMP130
2946 TEMP131
2947 TEMP132
2948 TEMP133
2949 TEMP134
2950 TEMP135
2951 TEMP136
2952 TEMP137
2953 TEMP138
2954 TEMP139
2955 TEMP140
2956 TEMP141
2957 TEMP142
2958 TEMP143
2959 TEMP144
2960 TEMP145
2961 TEMP146
2962 TEMP147
2963 TEMP148
2964 TEMP149
2965 TEMP150
2966 TEMP151
2967 TEMP152
2968 TEMP153
2969 TEMP154
2970 TEMP155
2971 TEMP156
2972 TEMP157
2973 TEMP158
2974 TEMP159
2975 TEMP160
2976 TEMP161
2977 TEMP162
2978 TEMP163
2979 TEMP164
2980 TEMP165
2981 TEMP166
2982 TEMP167
2983 TEMP168
2984 TEMP169
2985 TEMP170
2986 TEMP171
2987 TEMP172
2988 TEMP173
2989 TEMP174
2990 TEMP175
2991 TEMP176
2992 TEMP177
2993 TEMP178
2994 TEMP179
2995 TEMP180
2996 TEMP181
2997 TEMP182
2998 TEMP183
2999 TEMP184
3000 TEMP185
Contents No. Signal Name
293
6 F 2 S 0 8 5 1
Signal list
3001 TEMP186
3002 TEMP187
3003 TEMP188
3004 TEMP189
3005 TEMP190
3006 TEMP191
3007 TEMP192
3008 TEMP193
3009 TEMP194
3010 TEMP195
3011 TEMP196
3012 TEMP197
3013 TEMP198
3014 TEMP199
3015 TEMP200
3016 TEMP201
3017 TEMP202
3018 TEMP203
3019 TEMP204
3020 TEMP205
3021 TEMP206
3022 TEMP207
3023 TEMP208
3024 TEMP209
3025 TEMP210
3026 TEMP211
3027 TEMP212
3028 TEMP213
3029 TEMP214
3030 TEMP215
3031 TEMP216
3032 TEMP217
3033 TEMP218
3034 TEMP219
3035 TEMP220
3036 TEMP221
3037 TEMP222
3038 TEMP223
3039 TEMP224
3040 TEMP225
3041 TEMP226
3042 TEMP227
3043 TEMP228
3044 TEMP229
3045 TEMP230
3046 TEMP231
3047 TEMP232
3048 TEMP233
3049 TEMP234
3050 TEMP235
3051 TEMP236
3052 TEMP237
3053 TEMP238
3054 TEMP239
3055 TEMP240
3056 TEMP241
3057 TEMP242
3058 TEMP243
3059 TEMP244
3060 TEMP245
3061 TEMP246
3062 TEMP247
3063 TEMP248
3064 TEMP249
3065 TEMP250
3066 TEMP251
3067 TEMP252
3068 TEMP253
3069 TEMP254
3070 TEMP255
3071 TEMP256
Contents No. Signal Name
294
6 F 2 S 0 8 5 1
For IEC61850
Measure Table
NO SIGNAL NAME CONTENTS
0 Va_mag Va magnitude
1 Vb_mag Vb magnitude
2 Vc_mag Vc magnitude
3 Va_ang Va angle
4 Vb_ang Vb angle
5 Vc_ang Vc angle
6 Ia_mag Ia magnitude
7 Ib_mag Ib magnitude
8 Ic_mag Ic magnitude
9 Ia_ang Ia angle
10 Ib_ang Ib angle
11 Ic_ang Ic angle
12 Vab_mag Vab magnitude
13 Vbc_mag Vbc magnitude
14 Vca_mag Vca magnitude
15 Vab_ang Vab angle
16 Vbc_ang Vbc angle
17 Vca_ang Vca angle
18 Iab_mag Iab magnitude
19 Ibc_mag Ibc magnitude
20 Ica_mag Ica magnitude
21 Iab_ang Iab angle
22 Ibc_ang Ibc angle
23 Ica_ang Ica angle
24 V1_mag V1 magnitude
25 V2_mag V2 magnitude
26 V0_mag V0 magnitude
27 V1_ang V1 angle
28 V2_ang V2 angle
29 V0_ang V0 angle
30 I1_mag I1 magnitude
31 I2_mag I2 magnitude
32 I0_mag I0 magnitude
33 I1_ang I1 angle
34 I2_ang I2 angle
35 I0_ang I0 angle
36 P Active Power
37 Q Reactive Power
38 Freq Frequency
39 FLT_DIS_KM FLT_DIS_KM
40 FLT_Z FLT_Z
295
6 F 2 S 0 8 5 1
Setting Table
NO SIGNAL NAME CONTENTS
0 GROUP_NO number of groups
1 ACT_GROUP active group number
2 EDIT_GROUP edit group number
3 CHG_GROUP change active group
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
NO SIGNAL NAME CONTENTS
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80 BFR1S BFR1S
81 BFRXS BFRXS
82 BFR2S BFR2S
83 BFRFS BFRFS
84 BFR1G BFR1G
85 BFRXG BFRXG
86 BFR2G BFR2G
87 BFRFG BFRFG
88
89
90 1A2_5A1 1A:2 5A:1
91 1A1_5A2 1A:1 5A:2
92 1A1_5A0 1A:1 5A:0
93 1A0_5A1 1A:0 5A:1
94
95
96
97
98
99
100 Sof tType Sof tware type
101 MappingName Mapping inf o
102 Vendor vendor name
103
104
105
106
107
108
109
110 Const0 Always 0
111 Const1 Always 1
112 Const2 Always 2
113 Const3 Always 3
114
115
116
117
118
119
296
6 F 2 S 0 8 5 1
Status Table
NO SIGNAL NAME CONTENTS
0 GOOSE_V_001 GOOSE_Value_001
1 GOOSE_V_002 GOOSE_Value_002
2 GOOSE_V_003 GOOSE_Value_003
3 GOOSE_V_004 GOOSE_Value_004
4 GOOSE_V_005 GOOSE_Value_005
5 GOOSE_V_006 GOOSE_Value_006
6 GOOSE_V_007 GOOSE_Value_007
7 GOOSE_V_008 GOOSE_Value_008
8 GOOSE_V_009 GOOSE_Value_009
9 GOOSE_V_010 GOOSE_Value_010
10 GOOSE_V_011 GOOSE_Value_011
11 GOOSE_V_012 GOOSE_Value_012
12 GOOSE_V_013 GOOSE_Value_013
13 GOOSE_V_014 GOOSE_Value_014
14 GOOSE_V_015 GOOSE_Value_015
15 GOOSE_V_016 GOOSE_Value_016
16 GOOSE_V_017 GOOSE_Value_017
17 GOOSE_V_018 GOOSE_Value_018
18 GOOSE_V_019 GOOSE_Value_019
19 GOOSE_V_020 GOOSE_Value_020
20 GOOSE_V_021 GOOSE_Value_021
21 GOOSE_V_022 GOOSE_Value_022
22 GOOSE_V_023 GOOSE_Value_023
23 GOOSE_V_024 GOOSE_Value_024
24 GOOSE_V_025 GOOSE_Value_025
25 GOOSE_V_026 GOOSE_Value_026
26 GOOSE_V_027 GOOSE_Value_027
27 GOOSE_V_028 GOOSE_Value_028
28 GOOSE_V_029 GOOSE_Value_029
29 GOOSE_V_030 GOOSE_Value_030
30 GOOSE_V_031 GOOSE_Value_031
31 GOOSE_V_032 GOOSE_Value_032
32 GOOSE_V_033 GOOSE_Value_033
33 GOOSE_V_034 GOOSE_Value_034
34 GOOSE_V_035 GOOSE_Value_035
35 GOOSE_V_036 GOOSE_Value_036
36 GOOSE_V_037 GOOSE_Value_037
37 GOOSE_V_038 GOOSE_Value_038
38 GOOSE_V_039 GOOSE_Value_039
39 GOOSE_V_040 GOOSE_Value_040
40 GOOSE_V_041 GOOSE_Value_041
41 GOOSE_V_042 GOOSE_Value_042
42 GOOSE_V_043 GOOSE_Value_043
43 GOOSE_V_044 GOOSE_Value_044
44 GOOSE_V_045 GOOSE_Value_045
45 GOOSE_V_046 GOOSE_Value_046
46 GOOSE_V_047 GOOSE_Value_047
47 GOOSE_V_048 GOOSE_Value_048
48 GOOSE_V_049 GOOSE_Value_049
49 GOOSE_V_050 GOOSE_Value_050
50 GOOSE_V_051 GOOSE_Value_051
51 GOOSE_V_052 GOOSE_Value_052
52 GOOSE_V_053 GOOSE_Value_053
53 GOOSE_V_054 GOOSE_Value_054
54 GOOSE_V_055 GOOSE_Value_055
55 GOOSE_V_056 GOOSE_Value_056
56 GOOSE_V_057 GOOSE_Value_057
57 GOOSE_V_058 GOOSE_Value_058
58 GOOSE_V_059 GOOSE_Value_059
59 GOOSE_V_060 GOOSE_Value_060
60 GOOSE_V_061 GOOSE_Value_061
61 GOOSE_V_062 GOOSE_Value_062
62 GOOSE_V_063 GOOSE_Value_063
63 GOOSE_V_064 GOOSE_Value_064
64 GOOSE_V_065 GOOSE_Value_065
65 GOOSE_V_066 GOOSE_Value_066
66 GOOSE_V_067 GOOSE_Value_067
67 GOOSE_V_068 GOOSE_Value_068
68 GOOSE_V_069 GOOSE_Value_069
69 GOOSE_V_070 GOOSE_Value_070
70 GOOSE_V_071 GOOSE_Value_071
NO SIGNAL NAME CONTENTS
71 GOOSE_V_072 GOOSE_Value_072
72 GOOSE_V_073 GOOSE_Value_073
73 GOOSE_V_074 GOOSE_Value_074
74 GOOSE_V_075 GOOSE_Value_075
75 GOOSE_V_076 GOOSE_Value_076
76 GOOSE_V_077 GOOSE_Value_077
77 GOOSE_V_078 GOOSE_Value_078
78 GOOSE_V_079 GOOSE_Value_079
79 GOOSE_V_080 GOOSE_Value_080
80 GOOSE_V_081 GOOSE_Value_081
81 GOOSE_V_082 GOOSE_Value_082
82 GOOSE_V_083 GOOSE_Value_083
83 GOOSE_V_084 GOOSE_Value_084
84 GOOSE_V_085 GOOSE_Value_085
85 GOOSE_V_086 GOOSE_Value_086
86 GOOSE_V_087 GOOSE_Value_087
87 GOOSE_V_088 GOOSE_Value_088
88 GOOSE_V_089 GOOSE_Value_089
89 GOOSE_V_090 GOOSE_Value_090
90 GOOSE_V_091 GOOSE_Value_091
91 GOOSE_V_092 GOOSE_Value_092
92 GOOSE_V_093 GOOSE_Value_093
93 GOOSE_V_094 GOOSE_Value_094
94 GOOSE_V_095 GOOSE_Value_095
95 GOOSE_V_096 GOOSE_Value_096
96 GOOSE_V_097 GOOSE_Value_097
97 GOOSE_V_098 GOOSE_Value_098
98 GOOSE_V_099 GOOSE_Value_099
99 GOOSE_V_100 GOOSE_Value_100
100 GOOSE_V_101 GOOSE_Value_101
101 GOOSE_V_102 GOOSE_Value_102
102 GOOSE_V_103 GOOSE_Value_103
103 GOOSE_V_104 GOOSE_Value_104
104 GOOSE_V_105 GOOSE_Value_105
105 GOOSE_V_106 GOOSE_Value_106
106 GOOSE_V_107 GOOSE_Value_107
107 GOOSE_V_108 GOOSE_Value_108
108 GOOSE_V_109 GOOSE_Value_109
109 GOOSE_V_110 GOOSE_Value_110
110 GOOSE_V_111 GOOSE_Value_111
111 GOOSE_V_112 GOOSE_Value_112
112 GOOSE_V_113 GOOSE_Value_113
113 GOOSE_V_114 GOOSE_Value_114
114 GOOSE_V_115 GOOSE_Value_115
115 GOOSE_V_116 GOOSE_Value_116
116 GOOSE_V_117 GOOSE_Value_117
117 GOOSE_V_118 GOOSE_Value_118
118 GOOSE_V_119 GOOSE_Value_119
119 GOOSE_V_120 GOOSE_Value_120
120 GOOSE_V_121 GOOSE_Value_121
121 GOOSE_V_122 GOOSE_Value_122
122 GOOSE_V_123 GOOSE_Value_123
123 GOOSE_V_124 GOOSE_Value_124
124 GOOSE_V_125 GOOSE_Value_125
125 GOOSE_V_126 GOOSE_Value_126
126 GOOSE_V_127 GOOSE_Value_127
127 GOOSE_V_128 GOOSE_Value_128
128 XCBR_POS0 XCBR_POS0
129 XCBR_POS1 XCBR_POS1
130 XCBR_POS2 XCBR_POS2
131 XCBR_POS3 XCBR_POS3
132 XCBR_POS4 XCBR_POS4
133 XCBR_POS5 XCBR_POS5
134
135 LEDRST_EXEC LEDRST_EXEC
136 RREC1 RREC1
137 RREC2 RREC2
138 FLT_LOOP_ST flt loop value
139 XCBR_OPCNT0 XCBR_OPCNT0
140 XCBR_OPCNT1 XCBR_OPCNT1
297
6 F 2 S 0 8 5 1
NO SIGNAL NAME CONTENTS
141 XCBR_OPCNT2 XCBR_OPCNT2
142 XCBR_OPCNT3 XCBR_OPCNT3
143 XCBR_OPCNT4 XCBR_OPCNT4
144 XCBR_OPCNT5 XCBR_OPCNT5
145 RPSB1 RPSB1
146 RPSB2 RPSB2
147
148
149
150 HEALTH HEALTH
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200 MOD_001 IEC-MODE_001
201 MOD_002 IEC-MODE_002
202 MOD_003 IEC-MODE_003
203 MOD_004 IEC-MODE_004
204 MOD_005 IEC-MODE_005
205 MOD_006 IEC-MODE_006
206 MOD_007 IEC-MODE_007
207 MOD_008 IEC-MODE_008
208 MOD_009 IEC-MODE_009
209 MOD_010 IEC-MODE_010
210 MOD_011 IEC-MODE_011
NO SIGNAL NAME CONTENTS
211 MOD_012 IEC-MODE_012
212 MOD_013 IEC-MODE_013
213 MOD_014 IEC-MODE_014
214 MOD_015 IEC-MODE_015
215 MOD_016 IEC-MODE_016
216 MOD_017 IEC-MODE_017
217 MOD_018 IEC-MODE_018
218 MOD_019 IEC-MODE_019
219 MOD_020 IEC-MODE_020
220 MOD_021 IEC-MODE_021
221 MOD_022 IEC-MODE_022
222 MOD_023 IEC-MODE_023
223 MOD_024 IEC-MODE_024
224 MOD_025 IEC-MODE_025
225 MOD_026 IEC-MODE_026
226 MOD_027 IEC-MODE_027
227 MOD_028 IEC-MODE_028
228 MOD_029 IEC-MODE_029
229 MOD_030 IEC-MODE_030
230 MOD_031 IEC-MODE_031
231 MOD_032 IEC-MODE_032
232 MOD_033 IEC-MODE_033
233 MOD_034 IEC-MODE_034
234 MOD_035 IEC-MODE_035
235 MOD_036 IEC-MODE_036
236 MOD_037 IEC-MODE_037
237 MOD_038 IEC-MODE_038
238 MOD_039 IEC-MODE_039
239 MOD_040 IEC-MODE_040
240 MOD_041 IEC-MODE_041
241 MOD_042 IEC-MODE_042
242 MOD_043 IEC-MODE_043
243 MOD_044 IEC-MODE_044
244 MOD_045 IEC-MODE_045
245 MOD_046 IEC-MODE_046
246 MOD_047 IEC-MODE_047
247 MOD_048 IEC-MODE_048
248 MOD_049 IEC-MODE_049
249 MOD_050 IEC-MODE_050
250 MOD_051 IEC-MODE_051
251 MOD_052 IEC-MODE_052
252 MOD_053 IEC-MODE_053
253 MOD_054 IEC-MODE_054
254 MOD_055 IEC-MODE_055
255 MOD_056 IEC-MODE_056
256 MOD_057 IEC-MODE_057
257 MOD_058 IEC-MODE_058
258 MOD_059 IEC-MODE_059
259 MOD_060 IEC-MODE_060
260 MOD_061 IEC-MODE_061
261 MOD_062 IEC-MODE_062
262 MOD_063 IEC-MODE_063
263 MOD_064 IEC-MODE_064
264 MOD_065 IEC-MODE_065
265 MOD_066 IEC-MODE_066
266 MOD_067 IEC-MODE_067
267 MOD_068 IEC-MODE_068
268 MOD_069 IEC-MODE_069
269 MOD_070 IEC-MODE_070
270 MOD_071 IEC-MODE_071
271 MOD_072 IEC-MODE_072
272 MOD_073 IEC-MODE_073
273 MOD_074 IEC-MODE_074
274 MOD_075 IEC-MODE_075
275 MOD_076 IEC-MODE_076
276 MOD_077 IEC-MODE_077
277 MOD_078 IEC-MODE_078
278 MOD_079 IEC-MODE_079
279 MOD_080 IEC-MODE_080
280 MOD_081 IEC-MODE_081
298
6 F 2 S 0 8 5 1
NO SIGNAL NAME CONTENTS
280 MOD_081 IEC-MODE_081
281 MOD_082 IEC-MODE_082
282 MOD_083 IEC-MODE_083
283 MOD_084 IEC-MODE_084
284 MOD_085 IEC-MODE_085
285 MOD_086 IEC-MODE_086
286 MOD_087 IEC-MODE_087
287 MOD_088 IEC-MODE_088
288 MOD_089 IEC-MODE_089
289 MOD_090 IEC-MODE_090
290 MOD_091 IEC-MODE_091
291 MOD_092 IEC-MODE_092
292 MOD_093 IEC-MODE_093
293 MOD_094 IEC-MODE_094
294 MOD_095 IEC-MODE_095
295 MOD_096 IEC-MODE_096
296 MOD_097 IEC-MODE_097
297 MOD_098 IEC-MODE_098
298 MOD_099 IEC-MODE_099
299 MOD_100 IEC-MODE_100
300 BEH_001 IEC-Behavier_001
301 BEH_002 IEC-Behavier_002
302 BEH_003 IEC-Behavier_003
303 BEH_004 IEC-Behavier_004
304 BEH_005 IEC-Behavier_005
305 BEH_006 IEC-Behavier_006
306 BEH_007 IEC-Behavier_007
307 BEH_008 IEC-Behavier_008
308 BEH_009 IEC-Behavier_009
309 BEH_010 IEC-Behavier_010
310 BEH_011 IEC-Behavier_011
311 BEH_012 IEC-Behavier_012
312 BEH_013 IEC-Behavier_013
313 BEH_014 IEC-Behavier_014
314 BEH_015 IEC-Behavier_015
315 BEH_016 IEC-Behavier_016
316 BEH_017 IEC-Behavier_017
317 BEH_018 IEC-Behavier_018
318 BEH_019 IEC-Behavier_019
319 BEH_020 IEC-Behavier_020
320 BEH_021 IEC-Behavier_021
321 BEH_022 IEC-Behavier_022
322 BEH_023 IEC-Behavier_023
323 BEH_024 IEC-Behavier_024
324 BEH_025 IEC-Behavier_025
325 BEH_026 IEC-Behavier_026
326 BEH_027 IEC-Behavier_027
327 BEH_028 IEC-Behavier_028
328 BEH_029 IEC-Behavier_029
329 BEH_030 IEC-Behavier_030
330 BEH_031 IEC-Behavier_031
331 BEH_032 IEC-Behavier_032
332 BEH_033 IEC-Behavier_033
333 BEH_034 IEC-Behavier_034
334 BEH_035 IEC-Behavier_035
335 BEH_036 IEC-Behavier_036
336 BEH_037 IEC-Behavier_037
337 BEH_038 IEC-Behavier_038
338 BEH_039 IEC-Behavier_039
339 BEH_040 IEC-Behavier_040
340 BEH_041 IEC-Behavier_041
341 BEH_042 IEC-Behavier_042
342 BEH_043 IEC-Behavier_043
343 BEH_044 IEC-Behavier_044
344 BEH_045 IEC-Behavier_045
345 BEH_046 IEC-Behavier_046
346 BEH_047 IEC-Behavier_047
347 BEH_048 IEC-Behavier_048
348 BEH_049 IEC-Behavier_049
349 BEH_050 IEC-Behavier_050
350 BEH_051 IEC-Behavier_051
NO SIGNAL NAME CONTENTS
351 BEH_052 IEC-Behavier_052
352 BEH_053 IEC-Behavier_053
353 BEH_054 IEC-Behavier_054
354 BEH_055 IEC-Behavier_055
355 BEH_056 IEC-Behavier_056
356 BEH_057 IEC-Behavier_057
357 BEH_058 IEC-Behavier_058
358 BEH_059 IEC-Behavier_059
359 BEH_060 IEC-Behavier_060
360 BEH_061 IEC-Behavier_061
361 BEH_062 IEC-Behavier_062
362 BEH_063 IEC-Behavier_063
363 BEH_064 IEC-Behavier_064
364 BEH_065 IEC-Behavier_065
365 BEH_066 IEC-Behavier_066
366 BEH_067 IEC-Behavier_067
367 BEH_068 IEC-Behavier_068
368 BEH_069 IEC-Behavier_069
369 BEH_070 IEC-Behavier_070
370 BEH_071 IEC-Behavier_071
371 BEH_072 IEC-Behavier_072
372 BEH_073 IEC-Behavier_073
373 BEH_074 IEC-Behavier_074
374 BEH_075 IEC-Behavier_075
375 BEH_076 IEC-Behavier_076
376 BEH_077 IEC-Behavier_077
377 BEH_078 IEC-Behavier_078
378 BEH_079 IEC-Behavier_079
379 BEH_080 IEC-Behavier_080
380 BEH_081 IEC-Behavier_081
381 BEH_082 IEC-Behavier_082
382 BEH_083 IEC-Behavier_083
383 BEH_084 IEC-Behavier_084
384 BEH_085 IEC-Behavier_085
385 BEH_086 IEC-Behavier_086
386 BEH_087 IEC-Behavier_087
387 BEH_088 IEC-Behavier_088
388 BEH_089 IEC-Behavier_089
389 BEH_090 IEC-Behavier_090
390 BEH_091 IEC-Behavier_091
391 BEH_092 IEC-Behavier_092
392 BEH_093 IEC-Behavier_093
393 BEH_094 IEC-Behavier_094
394 BEH_095 IEC-Behavier_095
395 BEH_096 IEC-Behavier_096
396 BEH_097 IEC-Behavier_097
397 BEH_098 IEC-Behavier_098
398 BEH_099 IEC-Behavier_099
399 BEH_100 IEC-Behavier_100
400 Const0 Const0
401 Const1 Const1
402 Const2 Const2
403 Const3 Const3
404 Const4 Const4
405 Const5 Const5
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
299
6 F 2 S 0 8 5 1
NO SIGNAL NAME CONTENTS
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
NO SIGNAL NAME CONTENTS
491
492
493
494
495
496
497
498
499
300
6 F 2 S 0 8 5 1
Control Table
NO SIGNAL NAME CONTENTS
0 LEDRST_SIG LED Reset
1 LEDRST_ORCAT Control - LED Reset Originator category
2 LEDRST_ORID Control - LED Reset Originator category
3 LEDRST_ORCAT_ST Status - LED Rst Originator category
4 LEDRST_ORID_ST Status - LED Rst Originator category
301
6 F 2 S 0 8 5 1
Appendix C
Variable Timer List
302
6 F 2 S 0 8 5 1
Variable Timer List
Timer Timer No. Contents Timer Timer No. Contents
TZ1GA
TZ1GB
TZ1GC
TZ2G
TZ3G
TZ1S
TZ2S
TZ3S
TEF
TDEF
TZR1S
TZR1G
TBF1A
TBF1B
TBF1C
TBF2A
TBF2B
TBF2C
TOST1
TOST2
TDEFF
TDEFR
TCHD
TEVLV
TRDY1
TSPR1
TTPR1
TRR1
TW1
TRDY2
TSPR2
TTPR2
TRR2
TW2
TSYN1
TSYN2
TDBL1
TDBL2
TLBD1
TLBD2
TS2
TS3
TS4
TS2R
TS3R
TS4R
TOC
TPSB
TSOTF
TZFG
TZFS
TZR2G
TZR2S
TZNDG
TZNDS
TREBK
TECCB
TSBCT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Z1G TRIP TIMER
ditto
ditto
Z2G TRIP TIMER
Z3G TRIP TIMER
Z1S TRIP TIMER
Z2S TRIP TIMER
Z3S TRIP TIMER
EF BACK-UP TRIP TIMER
DEFF BACK-UP TRIP TIMER
ZR1S BACK-UP TRIP TIMER
ZR1G BACK-UP TRIP TIMER
CBF DETECTION TIMER 1
ditto
ditto
CBF DETECTION TIMER 2
ditto
ditto
OUT-OF-STEP DET. TIMER
ditto
DEF CARRIER TRIP DELAY TIMER
CARR.COORDINATION DEFR TIMER
CARRIER COORDINATION TIMER
EVOLVING FAULT WAITING TIMER
RECLAIM TIMER
SPAR DEAD LINE TIMER
TPAR DEAD LINE TIMER
RESET TIMER
RECLOSING O/P FOR BUS CB
FLW RECLAIM TIMER
FLW SPAR DEAD LINE TIMER
FLW TPAR DEAD LINE TIMER
FLW RESET TIMER
RECLOSING O/P FOR CENTER CB
LEAD SYN CHECK TIMER
FLW SYN CHECK TIMER
VOLTAGE CHECK TIMER
ditto
ditto
ditto
MULTI. SHOT DEAD TIMER
ditto
ditto
MULTI. SHOT RESET TIMER
ditto
ditto
OC BACK-UP TRIP TIMER
PSB DETECTION TIMER
SOTF CHECK TIMER
ZFG TRIP TIMER
ZFS TRIP TIMER
ZR2G BACK-UP TRIP TIMER
ZR2S BACK-UP TRIP TIMER
ZNDG BACK-UP TRIP TIMER
ZNDS BACK-UP TRIP TIMER
CURRENT REVERSAL BLOCKING TIME
ECHO ENABLE TIME FROM CB OPENED
SBCNT TIME
T3PLL
TDER
TOS1
TOS2
TOG1
TOG2
TUS1
TUS2
TUG1
TUG2
TBCD
61
62
63
64
65
66
67
68
69
70
71
THREE PHASE LIVE LINE TIMER
DEFR BACK-UP TRIP TIMER
OVS1 BACK-UP TRIP TIMER
OVS2 BACK-UP TRIP TIMER
OVG1 BACK-UP TRIP TIMER
OVG2 BACK-UP TRIP TIMER
UVS1 BACK-UP TRIP TIMER
UVS2 BACK-UP TRIP TIMER
UVG1 BACK-UP TRIP TIMER
UVG2 BACK-UP TRIP TIMER
BCD TRIP TIMER
303
6 F 2 S 0 8 5 1
Appendix D
Binary Input/Output Default Setting
List
304
6 F 2 S 0 8 5 1
Binary Input Default Setting List
Model
1CB-ARC,NO-FD 2CB-ARC,NO-FD
201 301 303
BI1 CB1-A
BI2 CB1-B
BI3 CB1-C
BI4 Signal Receive(CH1)
BI5 Signal Receive(CH2) or Z1X init
BI6 EXT VTF
BI7 DS-N/O
BI8 DS-N/C
BI9 Carrier block
BI10 CB1 ready
BI11 (SPARE) CB2 ready
BI12 REC BLOCK
BI13 IND.RESET
BI14 M-prot Trip
BI15 M-prot On
BI16 EXT trip-A
BI17 EXT trip-B
BI18 EXT trip-C
BI19 -- --
BI20 -- --
BI21 -- --
BI22 --
BI23 --
BI24 --
BI25 --
BI26 --
BI27 --
BI28 --
BI34 -- -- (SPARE)
BI35 -- -- (SPARE)
BI36 -- -- (SPARE)
No.
305
6 F 2 S 0 8 5 1
Binary Output Default Setting List (1)
Relay Model Module BO No. Terminal No. Signal Name Contents Setting
Name
Signal No.
LOGIC
(OR:1, AND:2)
TIMER
(OFF:0, ON:1)
GRZ100
-201
IO#2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
TB3:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A13-B13
TRIP-A1
TRIP-B1
TRIP-C1
CAR/Z1G/Z1S_
TRIP
Z2G/Z3G/ZR1G/
Z2S/Z3S/ZR1S_
TRIP
EF_BU-TRIP
SOTF/STUB_TRIP
BURECLK
CBF_TRIP
ARC1
VTF_ALARM,CHF
CBF_DET
EXT_CAR-S
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Distance or DEF carrier/Z1G/
Z1S trip
Z2G/Z3G/ZR1G Back-up/
Z2S/Z3S/ZR1S trip
EF or DEF Back-up trip
SOTF/Stub trip
BU reclose block
Related CB trip for CBF
Rec output for bus CB
VTF alarm, Carrier channel
failure
CBF Detection
External carrier send
command
240
241
242
231,148,160
153,156,192,162,165
189
187
183,182
195
200
291
172,253
199
225
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
0
(FAIL) A12-B12 RELAY FAILURE -- -- -- --
IO#3
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
TB2:
A1-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-OR
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P or
240
241
242
240
241
242
240
241
242
238
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
IO#2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
TB3:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A13-B13
TRIP-A1,2
TRIP-B1,2
TRIP-C1,2
CAR/Z1G/Z1S_
TRIP
Z2G/Z3G/ZR1G/
Z2S/Z3S/ZR1S_
TRIP
EF_BU-TRIP
SOTF/STUB_TRIP
BURECLK
CBF_TRIP
ARC1
ARC2
VTF_ALARM,CHF
EXT_CAR-S
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Distance or DEF carrier/Z1G/
Z1S trip
Z2G/Z3G/ZR1G Back-up/
Z2S/Z3S/ZR1S trip
EF or DEF back-up trip
SOTF/Stub trip
BU reclose block
Related CB trip for CBF
Rec output for bus CB
Rec output for center CB
VTF alarm, Carrier channel
failure
External carrier send
command
240,243
241,244
242,245
231,148,160
153,156,192,162,165
,189
187
183,182
195
200
291
292
172,253
225
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
1
0
(FAIL) A12-B12 RELAY FAILURE -- -- -- --
GRZ100
-301
IO#3
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
TB2:
A1-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
TRIP-A1,2
TRIP-B1,2
TRIP-C1,2
TRIP-A1,2
TRIP-B1,2
TRIP-C1,2
TRIP-A1,2
TRIP-B1,2
TRIP-C1,2
TRIP-OR
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P or
240,243
241,244
242,245
240,243
241,244
242,245
240,243
241,244
242,245
238
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
306
6 F 2 S 0 8 5 1
Binary Output Default Setting List (2)
Relay Model Module BO No. Terminal No. Signal Name Contents Setting
Name
Signal No.
LOGIC
(OR:1, AND:2)
TIMER
(OFF:0, ON:1)
IO#2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
TB2:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A13-B13
TRIP-A1,2
TRIP-B1,2
TRIP-C1,2
CAR/Z1G/Z1S_
TRIP
Z2G/Z3G/ZR1G/
Z2S/Z3S/ZR1S_
TRIP
EF_BU-TRIP
SOTF/STUB_TRIP
BURECLK
CBF_TRIP
ARC1
ARC2
VTF_ALARM,CHF
EXT_CAR-S
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Trip O/P for bus/center CB
Distance or DEF carrier/Z1G/
Z1S trip
Z2G/Z3G/ZR1G Back-up/
Z2S/Z3S/ZR1S trip
EF or DEF back-up trip
SOTF/Stub trip
BU reclose block
Related CB trip for CBF
Rec output for bus CB
Rec output for center CB
VTF alarm, Carrier channel
failure
External carrier send
command
240,243
241,244
242,245
231,148,160
153,156,192,162,165
189
187
183,182
195
200
291
292
172,253
225
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
1
0
(FAIL) A12-B12 RELAY FAILURE -- -- -- --
IO#3
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
TB5:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A12-B12
A13-B13
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A1
TRIP-B1
TRIP-C1
TRIP-A2
TRIP-B2
TRIP-C2
TRIP-A2
TRIP-B2
TRIP-C2
TRIP-OR
TRIP-OR
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for bus CB
Trip O/P for center CB
Trip O/P for center CB
Trip O/P for center CB
Trip O/P for center CB
Trip O/P for center CB
Trip O/P for center CB
Trip O/P or
Trip O/P or
240
241
242
240
241
242
243
244
245
243
244
245
238
238
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
GRZ100
-303
IO#4
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
TB3:
A2-A1
A2-B1
A2-B2
A3-B3
A4-B4
A5-B5
A6-B6
A7-B7
A8-B8
A9-B9
A10-B10
A11-B11
A12-B12
A13-B13
Z1G_TRIP
Z2G_TRIP
Z3G_TRIP
Z1S_TRIP
Z2S_TRIP
Z3S_TRIP
STUB_TRIP
SOTF_TRIP
EF_BU-TRIP
ZR1G_TRIP
ZR1S_TRIP
CBF_DET
DEFCR/WICAR_
TRIP
ARC1/2
Z1G trip
Z2G trip
Z3G trip
Z1S trip
Z2S trip
Z3S trip
Stub trip
SOTF trip
EF or DEF back-up trip
ZR1G back-up trip
ZR1S trip
CBF Detection
DEF/WEAK carrier trip
Rec output for bus/center CB
148
153
156
160
162
165
182
183
187
192
189
199
232,233
291,292
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
307
6 F 2 S 0 8 5 1
Appendix E
Details of Relay Menu
308
6 F 2 S 0 8 5 1
MENU
1=Recor d 2=St at us
3=Set t i ng( vi ew) 4=Set t i ng( change)
5=Test
/ 1 Record
1=Faul t record 2=Event record
3=Di st urbance record 4=Aut omat i c t est
5=Aut orecl ose count
/ 2 Faul t record
1=Di spl ay 2=Cl ear
/ 3 Faul t record 2/ 8
#1 16/ Oct / 1998 23: 18: 03. 913
#2 12/ Feb/ 1998 03: 51: 37. 622
#3 30/ J an/ 1997 15: 06: 11. 835
/ 2 Faul t record
Cl ear al l f aul t records ?
ENTER=Yes CANCEL=No
/ 4 Faul t record #2 3/ 33
16/ Oct / 1998 23: 18: 03. 913
Phase BC Tri p ABC/ ABC
Z1, CRT
/ 2 Aut omat i c t est
1=Tel ecommchannel t est
/ 2 Event record
Cl ear al l event records ?
ENTER=Yes CANCEL=No
/ 2 Di st urbance record
Cl ear al l di st urbance records ?
ENTER=Yes CANCEL=No
/ 3 Tel ecommchannel t est
1=Di spl ay count & i nt erval
2=Reset count
/ 2 Event record
1=Di spl ay 2=Cl ear
/ 3 Event record 2/ 48
16/ Oct / 1998 23: 18: 04. 294 Tri p Of f
16/ Oct / 1998 23: 18: 03. 913 Tri p On
12/ Feb/ 1998 03: 51: 37. 622 Rl y. set change
/ 2 Di st urbance record
1=Di spl ay 2=Cl ear
/ 3 Di st urbance record 1/ 11
#1 16/ Oct / 1998 23: 18: 03. 913
#2 12/ Feb/ 1998 03: 51: 37. 622
#3 30/ J an/ 1997 15: 06: 11. 835
/ 4 Tel ecommchannel t est
Test count : 11
Test i nt erval : 12 hours
/ 3 Tel ecommchannel t est
Reset count ?
ENTER=Yes CANCEL=No
/ 2 Aut orecl ose count
1=Di spl ay 2=Reset
/ 3 Aut orecl ose count
SPAR TPAR
CB1 [ 46] [ 46]
/ 3 Reset aut orecl ose count
1=CB1
/ 3 Reset aut orecl ose count
Reset count ?
ENTER=Yes CANCEL=No
a- 1
309
6 F 2 S 0 8 5 1
/ 2 Descri pt i on 2/ 2
Pl ant name: ********************
Descri pt i on: ********************
/ 1 St at us
1=Met eri ng 2=Bi nary I / O
3=Rel ay el ement 4=Ti me sync source
5=Cl ock adj ust ment 6=Di rect i on
/ 2 Met eri ng 12/ Feb/ 1998 22: 56 3/ 15
Va ***. *kV ***. * I a **. **kA ***. *
Vb ***. *kV ***. * I b **. **kA ***. *
Vc ***. *kV ***. * I c **. **kA ***. *
/ 2 12/ Feb/ 1998 22: 56: 19 [ l ocal ] 1/ 5
Mi nut e ( 0 - 59) : 56 _
Hour ( 0 - 23) : 22
Day ( 1 - 31) : 12
/ 2 Rel ay versi on 3/ 5
Rel ay t ype : ********************
Seri al No. : ********************
Mai n sof t ware: ********************
/ 2 Bi nary i nput & out put 3/ 8
I nput ( I O#1) [ 000 000 000 000 ]
I nput ( I O#2) [ 000 ]
I nput ( I O#3) [ 000 000 000 0 ]
/ 2 Rel ay el ement 3/ 12
ZG [ 000 000 000 000 000]
ZG2 [ 000 000 000 000 ]
ZS [ 000 000 000 000 000]
/ 2 Ti me synchroni zat i on source
*I RI G: Act i ve
RSM: I nact i ve
I EC: I nact i ve
/ 2 Communi cat i on
1=Address/ Paramet er
2=Swi t ch
/ 3 Faul t record 1/ 2
Faul t l ocat or 0=Of f 1=On 1
AZFLEN 0=Of f 1=On 0
/ 3 Event record
1=Si gnal no.
2=Event name
/ 1 Set t i ng( vi ew)
1=Versi on 2=Descri pt i on 3=Comm.
4=Record 5=St at us 6=Prot ect i on
7=Bi nary i nput 8=Bi nary out put 9=LED
/ 2 Record
1=Faul t record 2=Event record
3=Di st urbance record
4=Aut omat i c t est i nt erval
/ 3 Di st urbance record
1=Record t i me & st art er
2=Scheme swi t ch
3=Bi nary si gnal 4=Si gnal name
/ 4 Record t i me & st art er 2/ 3
Ti me ( 3. 0 s ) OCP- S ( 50. 0 A )
OCP- G ( 50. 0 A ) UVP- S ( 0 V )
UVP- G ( 0 V )
/ 4 Scheme swi t h 1/ 5
TRI P 0=Of f 1=On 1
OCP- S 0=Of f 1=On 1
OCP- G 0=Of f 1=On 1
/ 3 Aut omat i c t est i nt erval 1/ 1
Chann( 6 hrs)
/ 2 St at us
1=Met eri ng
2=Ti me Synchroni zat i on
3=Ti me zone
/ 3 Ti me synchroni zat i on
0=Of f 1=I RI G 2=RSM3=I EC
Current No. =2
/ 3 Ti me zone 1/ 1
GMT ( +9 hrs )
/ 3 Met eri ng 3/ 3
Di spl ay val ue 1=Pri mary 2=Secondary 1
Power ( P/ Q) 1=Send 2=Recei ve 1
Current 1=Lag 2=Lead 1
a- 1
a- 2 a- 1
/ 4 Bi nary si gnal 3/ 16
SI G1 ( 128 ) SI G2 ( 3071 )
SI G3 ( 0 ) SI G4 ( 1 )
SI G5 ( 1 ) SI G6 ( 2 )
/ 3 Address/ Paamet er 1/ 2
HDLC ( 1 )
I EC ( 1 ) SYADJ ( 0 ms )
/ 3 Swi t ch 3/ 4
PRTCLl 1=HDLC 2=I EC103 1
232C 1=9. 6 2=19. 2 3=38. 4 4=57. 6 4
I ECBR 1=9. 6 2=19. 2 2
/ 2 Di rect i on
Phase A: Forward
Phase B: Reverse
Phase C: _______
/ 4 Si gnal no. 3/ 65
BI TRN ( 128 ) EV1 ( 3071 )
EV2 ( 0 ) EV3 ( 1 )
EV4 ( 1 ) EV5 ( 2 )
/ 4 Event name 3/ 128
Event name1 [ Event record name 1 ]
Event name2 [ ]
Event name3 [ ]
/ 4 Si gnal name 3/ 32
Si gnal name1 [ Si gnal name 1 ]
Si gnal name2 [ ]
Si gnal name3 [ ]
310
6 F 2 S 0 8 5 1
a- 1 a- 2
/ 4 Li ne paramet er ( Group 1)
1=Li ne name
2=VT & CT rat i o
3=Faul t l ocat or
/ 4 Tri p ( Group 1)
1=Prot ect i on scheme
2=Scheme swi t ch
3=Prot ect i on el ement
/ 5 Faul t l ocat or 3/ 7
X1 ( 32. 60 ) X0 ( 2. 90 )
X0m ( 14. 00 ) R1 ( 60. 00 )
R0 ( 5. 00 ) R0m( 10. 00 )
/ 5 Pr ot ect i on scheme
1=3ZONE 2=Z1- EXT 3=PUP 4=POP 5=UOP 6=BOP
7=POP+DEF 8=UOP+DEF 9=BOP+DEF 10=PUP+DEF
Cur r ent No. =7
/ 2 Prot ect i on ( Act i ve group=*)
1=Group1 2=Group2 3=Group3 4=Group4
5=Group5 6=Group6 7=Group7 8=Group8
/ 5 Li ne name 1/ 1
Li ne name ********************
/ 3 Prot ect i on ( Group 1)
1=Li ne paramet er
2=Tri p
3=Aut orecl ose
/ 5 VT & CT rat i o 2/ 2
VT ( 2000 ) VTs1 ( 2000 )
VTs1 ( 2000 ) CT ( 200 )
/ 5 Scheme swi t ch 3/
Z1CNT 1=1 2=2 3=3 4=4 5=5 1
TPMODE 1=3PH 2=1PH
PSB- Z1 0=Of f 2=On
/ 5 Prot ect i on el ement ( Group 1)
1=Di st ance 2=PSB&OST 3=OC, DEF&UV
4=Command t ri p
/ 6 OC, DEF&UV 3/ 14
OCH ( 2. 0 A ) TPSB ( 40 ms )
OCBF ( 0. 5 A ) TBF1 ( 50 ms )
TBF2 ( 50 ms ) DEFFI ( 0. 5 A)
/ 6 Di st ance 3/
Z1S ( 0. 01 ) Z1S1 ( 0 deg )
Z1S2 ( 90 deg ) Z1XS ( 0. 01 )
Z2S ( 0. 01 ) Z3S ( 1. 0 )
/ 6 PSB&OST 3/ 4
PSBSZ ( 0. 50 ) PSBGZ ( 0. 50 )
TPSB ( 40 ms ) OSTR1 ( 1. 0 )
OSTR2 ( 1. 0 ) OSTXF ( 0. 2 )
/ 4 Aut orecl ose ( Group 1)
1=Aut orecl ose mode
2=Scheme swi t ch
3=Aut orecl ose el ement
/ 5 Scheme swi t ch 3/ 8
ARC- CB 1=ONE 2=01 3=03 4=L1 5=L2 1
ARC- EXT 0=Of f 1=On 0
ARC- DEF 0=Of f 1=On 1
/ 5 Aut orecl ose el ement ( Group 1)
1=Aut orecl ose t i mer
2=Synchrocheck
/ 6 Aut orecl ose t i mer 3/ 8
TEVLV( 0. 30 s ) TRDY1( 60 s )
TSPR ( 0. 80 s ) TTPR1( 0. 60 s )
TRR ( 2. 00 s ) TW1 ( 0. 3 s )
/ 6 Synchrocheck 3/ 9
OVB ( 51 V ) UVB ( 13 V )
OVL1 ( 51 V ) UVL1 ( 13 V )
SY1UV( 83 V ) SY1OV( 51 V )
/ 6 Command t ri p 1/ 2
TDEF ( 0. 00 s ) TDEFR ( 0. 00 s )
TCHD ( 12 ms )
/ 5 Aut orecl ose mode
1=Di sabl e 2=SPAR 3=TPAR 4=SPAR&TPAR
5=EXT1P 6=EXT3P
Current No. =4
/ 3 Prot ect i on ( Group 8)
1=Li ne paramet er
2=Tri p
3=Aut orecl ose rel ay
/ 3 Prot ect i on ( Group 2)
1=Li ne paramet er
2=Tri p
3=Aut orecl ose rel ay
a- 1 a- 2
311
6 F 2 S 0 8 5 1
a- 1 a- 2
/ 2 Password
I nput newpassword [ _ ]
Ret ype newpassword [ ]
/ 2 Descri pt i on
1=Pl ant name 2=Descri pt i on
/ 3 Faul t record 1/ 2
Faul t l ocat or 0=Of f 1=On 1 _
AZFLEN 0=Of f 1=On 0
/ 3 Event record 1/ 129
BI TRN ( 0- 128) : 128 _
EV1 ( 0- 3071) : 0
EV2 ( 0- 3071) : 1
/ 1 Set t i ng( change)
1=Password 2=Descri pt i on 3=Comm.
4=Record 5=St at us 6=Prot ect i on
7=Bi nary i nput 8=Bi nary out put 9=LED
/ 2 Record
1=Faul t record 2=Event record
3=Di st urbance record
4=Aut omat i c t est i nt erval
/ 3 Di st urbance record
1=Record t i me & st art er
2=Scheme swi t ch
3=Bi nary si gnal
/ 4 Record t i me & st art er 1/ 5
Ti me ( 0. 1- 3. 0) : 2. 0 _ s
OCP- S ( 0. 5- 250. 0) : 10. 0 A
OCP- G ( 0. 5- 250. 0) : 10. 0 A
/ 4 Scheme swi t ch 1/ 5
TRI P 0=Of f 1=On 1 _
OCP- S 0=Of f 1=On
OCP- G 0=Of f 1=On
/ 3 Aut omat i c t est i nt erval 1/ 1
Chann( 1- 24) : 12 _ hrs
a- 1
/ 2 Bi nary out put
1=I O#2 2=I O#3 3=I O#4
/ 2 Bi nary i nput 3/ 18
BI SW1 1=Norm =I nv 1
BI SW2 1=Norm =I nv 1
BI SW3 1=Norm =I nv 1
/ 3 Bi nary out put ( I O#2) 3/ 12
BO1 ( 1, 2, 3, 4, 5, 6) AND, D
BO2 ( 1, 2, 3, 4, 5, 6) OR,
BO3 ( 1, 2, 3, 4, 5, 6) OR, D
/ 2 LED 2/ 4
LED1 ( 1, 309, 0, 0) AND, I
LED2 ( 0, 0, 0, 0) OR, I
LED3 ( 15, 16, 17, 0) OR, L
/ 3 Bi nary out put ( I O#4) 3/ 12
BO1 ( 1, 2, 3, 4, 5, 6) AND, D
BO2 ( 1, 2, 3, 4, 5, 6) OR,
BO3 ( 1, 2, 3, 4, 5, 6) OR, D
: Confirmation trap
: Password trap
Password
I nput password [ _ ]
/ 2 *************
Change set t i ngs?
ENTER=Yes CANCEL=No
/ 3 Pl ant name [ _ ]
ABCDEFGHI J KLMNOPQRSTUVWXYZ( ) [ ] @_
abcdef ghi j kl mnopqrst uvwxyz{}*/ +- <=>
0123456789!#$%& : ; , . ^
/ 3 Descri pt i on [ _ ]
ABCDEFGHI J KLMNOPQRSTUVWXYZ( ) [ ] @_
abcdef ghi j kl mnopqrst uvwxyz{}*/ +- <=>
0123456789!#$%& : ; , . ^
a- 3
/ 4 Bi nary si gnal 3/ 32
SI G1 ( 0 - 3071) : 1
SI G2 ( 0 - 3071) : 1
SI G3 ( 0 - 3071) : 1 _
/ 2 Communi cat i on
1=Address/ Paramet er
2=Swi t ch
/ 3 Address/ Paramet er 1/ 3
HDLC ( 1- 32) : 1 _
I EC ( 2- 254) : 2
SYADJ ( - 9999 - 9999) : 0 ms
/ 3 Swi t ch 1/ 4
Prot ocol 1=HDLC 2=I EC103 1 _
232C 1=9. 6 2=19. 2 3=38. 4 4=57. 6 4
I ECBR 1=9. 6 2=19. 2 2
312
6 F 2 S 0 8 5 1
/ 5 Li ne paramet er ( Group 1)
1=Li ne name
2=VT & CT rat i o
3=Faul t l ocat or
/ 5 Tri p ( Group 1)
1=Prot ect i on scheme
2=Scheme swi t ch
3=Prot ect i on el ement
/ 6 Faul t l ocat or 1/ 13
X1 ( 0. 00 - 199. 99) : 32. 60 _
X0 ( 0. 00 - 199. 99) : 2. 90
X0m ( 0. 00 - 199. 99) : 0. 10
/ 6 Protecti on scheme
1=3ZONE 2=Z1- EXT 3=PUP 4=POP 5=UOP 6=BOP
7=POP+DEF 8=UOP+DEF 9=BOP+DEF 10=PUP+DEF
Current No. =7 Sel ect No. =_
/ 2 Prot ect i on
1=Change act i ve group
2=Change set t i ng
3=Copy group
/ 6 Li ne name [ _ ]
ABCDEFGHI J KLMNOPQRSTUVWXYZ( ) [ ] @_
abcdef ghi j kl mnopqrst uvwxyz{}*/ +- <=>
0123456789!#$%& : ; , . ^
/ 4 Prot ect i on ( Group 1)
1=Li ne paramet er
2=Tri p
3=Aut orecl ose
/ 6 VT & CT rat i o 1/ 3
VT ( 1- 20000) : 2200 _
VTs1 ( 1- 20000) : 2200
CT ( 1- 20000) : 400
/ 6 Scheme swi t ch 1/
ZS- C 1=Mho 2=Quad 1 _
ZG- C 1=Mho 2=Quad 1
BLZONE 1=COM 2=I ND 1
/ 6 Prot ect i on el ement ( Group 1)
1=Di st ance 2=PSB&OST 3=OC, DEF&UV
4=Command t ri p
/ 7 OC, DEF&UV 1/ 21
OCH ( 2. 0 - 10. 0) : 2. 0 _ A
TSOTF( 0 300) : 5 s
OCBF ( 0. 5 - 10. 0) : 0. 5 A
/ 7 Di st ance 1/
Z1S ( 0. 01 - 50. 00) : 0. 01 _
Z1XS ( 0. 01 - 50. 00) : 0. 01
Z1S1( 0 - 45) : 0 deg
/ 7 PSB&OST 1/ 9
PSBSZ ( 0. 50 - 15. 00) : 0. 50 _
PSBGZ ( 0. 50 - 15. 00) : 0. 50
TPSB ( 20 - 60) : 40 ms
/ 7 Command t ri p 1/ 7
TDEFF ( 0. 00- 0. 30) : 0. 00 _ s
TDEFR ( 0. 00- 0. 30) : 0. 00 s
TCHD ( 0- 50) : 12 ms
/ 2 St at us
1=Met eri ng
2=Ti me Synchroni zat i on
3=Ti me zone
/ 3 Ti me synchroni zat i on
0=Of f 1=I RI G 2=RSM3=I EC
Current No/ =0 Sel ect No. =_
/ 3 Ti me zone 1/ 1
GMT ( - 12 - +12) : +9 _ hrs
/ 3 Met eri ng 1/ 3
Di spl ay val ue 1=Pri mary 2=Secondary 1_
Power ( P/ Q) 1=Send 2=Recei ve 1
Current 1=Lag 2=Lead 1
/ 3Change act i ve group( Act i ve group=*)
1=Group1 2=Group2 3=Group3 4=Group4
5=Group5 6=Group6 7=Group7 8=Group8
Current No. =* Sel ect No. =_
/ 3 Change set t i ng ( Act i ve group=*)
1=Group1 2=Group2 3=Group3 4=Group4
5=Group5 6=Group6 7=Group7 8=Group8
a- 1 a- 3
a- 1 a- 3 a- 4 a- 5 a- 6 a- 1
313
6 F 2 S 0 8 5 1
/ 7 Aut orecl ose t i mer 1/ 12
TEVLV ( 0. 01- 10. 00) : 0. 30 _ s
TRDY1 ( 5- 300) : 60 s
TSPR ( 0. 01- 10. 00) : 0. 80 s
/ 7 Synchrocheck 1/ 18
OVB ( 10 - 150) : 51 _ V
UVB ( 10 - 150) : 13 V
OVL1 ( 10 - 150) : 51 V
a- 1 a- 3 a- 4 a- 5 a- 6
/ 3 Bi nary out put ( I O#2 )
Sel ect BO ( 1- 12)
Sel ect No. =_
/ 2 Bi nary i nput 1/ 18
BI SW1 1=Norm 2=I nv 1 _
BI SW2 1=Norm 2=I nv 1
BI SW3 1=Norm 2=I nv 1
/ 5 Logi c gat e t ype & del ay t i mer 1/ 2
Logi c 1=OR 2=AND 1 _
BOTD 0=Of f 1=On 1
/ 5 I nput t o l ogi c gat e 3/ 6
I n #1 ( 0 - 3071) : 21
I n #2 ( 0 - 3071) : 67
I n #3 ( 0 - 3071) : 12 _
/ 5 Aut orecl ose ( Group 1)
1=Aut orecl ose mode
2=Scheme swi t ch
3=Aut orecl ose el ement
/ 6 Scheme swi t ch 1/ 8
ARC- EXT 0=Of f 1=On 0 _
ARC- DEF 0=Of f 1=On 0
ARC- BU 0=Of f 1=On 0
/ 6 Aut orecl ose el ement ( Group 1)
1=Aut orecl ose t i mer
2=Synchrocheck
/ 6 Aut orecl ose mode
1=Di sabl e 2=SPAR 3=TPAR 4=SPAR&TPAR
5=EXT1P 6=EXT3P
Current No. =4 Sel ect No. =_
/ 3 Copy groupA t o B ( Act i ve group=1)
A ( 1- 8) : _
B ( 1- 8) :
/ 4 Prot ect i on ( Group 8)
1=Li ne paramet ers
2=Tri p
3=Aut orecl ose
/ 4 Prot ect i on ( Group 2)
1=Li ne paramet er
2=Tri p
3=Aut orecl ose
/ 2 Bi nary out put
1=I O#2 2=I O#3 3=I O#4
/ 4 Set t i ng ( BO 1 of I O#2 )
1=Logi c gat e t ype & del ay t i mer
2=I nput t o l ogi c gat e
/ 4 Set t i ng ( BO 12 of I O#2 )
1=Logi c gat e t ype & del ay t i mer
2=I nput t o l ogi c gat e
/ 4 Bi nary out put ( I O#4 )
Sel ect BO ( 1- 8)
Sel ect No. =_
a- 1
/ 2 LED
Sel ect LED ( 1 - 4)
Sel ect No. =_
/ 4 Logi c gat e t ype & del ay t i mer 1/ 2
Logi c 1=OR 2=AND 1 _
Reset 0=I nst 1=Lat ch 1
/ 4 I nput t o l ogi c gat e 1/ 4
I n #1 ( 0 - 3071) : 274 _
I n #2 ( 0 - 3071) : 289
I n #3 ( 0 - 3071) : 295
/ 3 Set t i ng ( LED1)
1=Logi c gat e t ype & reset
2=I nput t o l ogi c gat e
/ 3 Set t i ng ( LED4)
1=Logi c gat e t ype & reset
2=I nput t o l ogi c gat e
314
6 F 2 S 0 8 5 1
a-1
/ 1 Test
1=Swi t ch 2=Manual t est
3=Bi nary out put 4=Ti mer
5=Logi c ci rcui t
/ 2 Swi t ch 1/ 5
A. M. F. 0=Of f 1=On 1 _
Z1S- 1PH 0=Of f 1=On 0
ZB- CTRL 0=Norm1=OFST 2=Non- OFST 0
/ 2 Ti mer 1/ 1
Ti mer( 1 - 60) : 8 _
/ 2 Manual t est
1=Tel ecommchannel t est
Press number t o st art t est .
/ 2 Manual t est
Tel ecomchannel t est i ng . . .
/ 2 Bi nary out put
1=I O#1 2=I O#2 3=I O#3 4=I O#4
/ 2 Manual t est
Tel ecomchannel t est i ng . . .
Compl et ed.
/ 3 BO ( 0=Di sabl e 1=Enabl e) 1/ 3
I O#1 TP- A1 1 _
I O#1 TP- B1 1
I O#1 TP- C1 1
/ 3 BO
Press ENTER t o operat e.
Press CANCEL t o cancel .
/ 3 BO
Operat i ng . . .
Press END t o reset .
Press CANCEL t o cancel .
/ 2 Ti mer 1/ 1
Press ENTER t o operat e.
Press CANCEL t o cancel .
/ 2 Ti mer 1/ 1
Operat i ng . . .
Press END t o reset .
Press CANCEL t o cancel .
/ 2 Logi c ci rcui t 1/ 2
TermA( 0 - 3071) : 12 _
TermB( 0 - 3071) : 48
/ 3 BO ( 0=Di sabl e 1=Enabl e) 1/ 14
I O#4 BO1 1 _
I O#4 BO2 1
I O#4 BO3 1
315
6 F 2 S 0 8 5 1
LCD AND BUTTON OPERATION INSTRUCTION
NORMAL
(DISPLAY OFF)
VIEW
METERING 1
( DISPLAY ON )
VIEW RESET
LATEST FAULT *
( DISPLAY ON )
VIEW
AUTO SUPERVISON *
( DISPLAY ON )
RESET
VIEW RESET
TRIP OUTPUT
ISSUED !
TRIP
( LED ON )
MANUAL
MODE
AUTO-
MODE 1
RELAY
FAILED !
ALARM
( LED ON )
AUTO-
MODE 2
PRESS ANY
BUTTON
EXCEPT FOR
"VIEW" AND
"RESET"
MENU
( DISPLAY ON )
1=RECORD
1=FAULT RECORD
2=EVENT RECORD
4=AUTOMATIC TEST
2=STATUS
1=METERING
2=BINARY INPUT&OUPUT
3=RELAY ELELMENT
4=TIME SYNC SOURCE
5=CLOCK ADJUSTMENT
3=SETTING
(VIEW)
1=RELAY VERSION
2=DESCRIPTION
3=COMMUNICATION
4=RECORD
5=STATUS
6=PROTECTION
7=BINARY INPUT
8=BINARY OUTPUT
9=LED
5=TEST
1=SWITCH
3=BINARY OUTPUT
4=TIMER
5=LOGIC CIRCUIT
1. PRESS ARROW KEY TO MOVE TO EACH DISPLAYED
ITEMS
2. PRESS "END" KEY TO BACK TO PREVIOUS SCREEN
*. "LATEST FAULT" AND "AUTO
SUPERVISION" SCREEN IS
DISPLAYED ONLY IF DATA
IS STORED
4=SETTING
(CHANGE)
6=DIRECTION
2=MANUAL TEST
3=DISTURBANCE RECORD
5=AUTORECLOSE COUNT
Same as SETTING (VIEW) menu
316
6 F 2 S 0 8 5 1
317
6 F 2 S 0 8 5 1
Appendix F
Case Outline
Case Type-A: Flush Mount Type
Case Type-B: Flush Mount Type
Case Type-A, B: Rack Mount Type
318
6 F 2 S 0 8 5 1
Front View Side view
Rear view Panel cut-out
TB1
1 2
19 20
TB3/TB4 TB2
A1 B1
A1 B1
A10 B10
A18 B18
TB2-TB4:
M3.5 Ring
terminal
TB1:
M3.5 Ring
terminal
34.75
190.5 260
6.2
235.4
223
4-5.5
220
216
E
CN1
TB1
TB2
TB4 TB3
266
254
276.2 2
65
28
Case Type-A: Flush Mount Type for Model 201, 301
319
6 F 2 S 0 8 5 1
Front View Side view
Rear view Panel cut-out
TB2-TB5:
M3.5 Ring
terminal
TB1:
M3.5 Ring
terminal
TB1
1 2
19 20
TB2 - TB5
A1 B1
A18 B18
E
CN1
TB5 TB4 TB3 TB2
TB1
326
330
34.75
190.5 260
6.2
345.4
333
4-5.5
65
266
364 276.2
2
28
Case Type-B: Flush Mount Type for Model 303
320
6 F 2 S 0 8 5 1
Top View
2
6
5
.
9
3
7
.
7
100/110/115/120V
Front View
Rack Mount Type: Case Type-A for Model 201, 301
3
1
2
Attachment kit
(large bracket)
Attachment kit
(small bracket)
Attachment kit
(top bar)
4 HOLES - 6.8x10.3
465.1
483.0
321
6 F 2 S 0 8 5 1
Top View
Front View
Rack Mount: Case Type-B for Model 303
3
1
2
Attachment kit
(large bracket)
Attachment kit
(small bracket)
Attachment kit
(top bar)
2
6
5
.
9
3
7
.
7
483.0
4 HOLES - 6.8x10.3
465.1
322
6 F 2 S 0 8 5 1
Dimensions of Attachment Kit EP-101
1
3
6
2
6
5
.
9
247.8
(a) Large Bracket
2
6
5
.
9
19.4
18.8
(b) Small Bracket
216
1
8
(c) Bar for Top and Bottom of Relay
Parts
(a) 1 Large bracket, 5 Round head screws with spring washers and washers (M4x10)
(b) 1 Small bracket, 3 Countersunk head screws (M4x6)
(c) 2 Bars, 4 Countersunk head screws (M3x8)
323
6 F 2 S 0 8 5 1
(a) Large Bracket (b) Small Bracket
(c) Bar for Top and Bottom of Relay
Parts
(a) 1 Large bracket, 5 Round head screws with spring washers and washers (M4x10)
(b) 1 Small bracket, 3 Countersunk head screws (M4x6)
(c) 2 Bars, 4 Countersunk head screws (M3x8)
Dimensions of Attachment Kit EP-102
1
3
2
2
6
5
.
9
137.8
2
6
5
.
9
19.4
18.8
326
1
8
324
6 F 2 S 0 8 5 1
How to Mount Attachment Kit for Rack-Mounting
Caution: Be careful that the relay modules or terminal blocks, etc., are not damage while mounting.
Tighten screws to the specified torque according to the size of screw.
Step 1.
GPS ALARM
SYNC. ALARM
MODE 2A
CF
Step 2.
Step 3
Step 4
Remove case cover.
Remove the left and right brackets by
unscrewing the three screws respectively,
then remove two screws on left side of the
relay.
And then, remove four seals on the top
and bottom of the relay.
Right bracket
Left bracket
Top bar
Bottom bar
Mount the small bracket by screwing three
countersunk head screws(M4x6) and apply
adhesives to the screws to prevent them
from loosening.
Mount the large bracket by five round head
screws(M4x10) with washer and spring
washer.
And then, mount the top and bottom bars by
two countersunk head screws(M3x8)
respectively.
Small bracket
Large bracket
Completed.
Seal
Seal
Screw
325
6 F 2 S 0 8 5 1
Appendix G
External Connections
326
6 F 2 S 0 8 5 1
BUS
TB1 -1
4
3
2
7
6
5
9
8
10
12
11
13
15
14
16
BUS VT
CT
CB
VT
BUS VT
Io from
adjacent Line CT
A2
B2
A3
A4
B3
B4
A5
A6
B5
B6
A7
A8
B7
B8
A9
B9
TB2- A1
B1
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
IO#3
A10
B10
BO10
B9
(-)
(+)
(-)
BI1
BI10
B4
A5
B5
A6
B6
A7
B7
A8
B8
A9
TB4 -A4
BI11
BI2
BI8
BI12
BI9
BI5
BI6
BI7
BI3
BI4
A10
BI13
B10
BI14
A11
BI15
TB3 -A14
B11
BI16
B14
BI17
B15
A15
BI18
A3
B3
A4
A5
B4
B5
A6
A7
B6
B7
A8
A9
B8
B9
A10
A11
B11
B10
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
TB3- A2
A1
B1
B2
A12
B12
RELAY FAILURE
B13
TB3-A13
SIGNAL SEND
(HIGH SPEED RELAY)
BO13
FAIL
DD FAIL.
TB4-A16
(-)
(+)
+5Vdc
0V
B18
A18
E
B17
B16
A17
DC
SUPPLY
CASE EARTH
DC-DC
RELAY FAIL.
1
B15
A15
TRIP-B
TRIP-A
TRIP-C
BUS CB
(+)
TRIP-B
TRIP-A
TRIP-C
B14
A12
A13
B13
TP-A1
TP-B1
TP-C1
(+)
TB4- A3
A1
B3
A2
B2
TP-A2
TP-B2
TP-C2
TB4- A14
IRIG-B
19 20
B18 A18
TB3 TB4
TB1
1
B1 A1
TB2
IO#3
IO#1
Terminal Block Arrangement (Rear vi ew)
VCT
IO#2
B10
A18
A1
B18
B1
1 2
CN1
(IRIG-B)
E
20
CASE EARTH
CN1
RS485 I/F
COM-B
COM-A
TB3-A18
B18
A17
B17
A16
B16
COM-0V
(1)
(1)These connections are connected
by short-bars before shipment.
IO#1
IO#2
Programmable BI
Ethernet LAN I/F x1 or x2
(100Base-TX:RJ45 connector)
T(T1,T2):
option
Opt. interface for IEC103
(ST connector)
Ethernet LAN I/F
(100Base-FX:SC connector)
OP1
F(F1,F2):
option
(1)
Model 201
IO module
IO#1 IO1
IO#2 IO2
IO#3 IO3
327
6 F 2 S 0 8 5 1
A2
B2
A3
A4
B3
B4
A5
A6
B5
B6
A7
A8
B7
B8
A9
B9
TB2-A1
B1
IO#3
A10
B10
A3
B3
A4
A5
B4
B5
A6
A7
B6
B7
A8
A9
B8
B9
A10
A11
B11
B10
TB3- A2
A1
B1
B2
B9
(-)
(-)
B5
A6
B6
A7
B7
A8
B8
A9
A10
B10
A11
TB3 -A14
B11
B14
B15
A15
BUS
BUS
TB1 -1
4
3
2
7
6
5
9
8
10
12
11
13
15
14
16
BUS VT
CT
CT
CB
CB
VT
BUS VT
Io from
adjacent Line CT
17
18
ADJACENT LINE VT
CB
B4
A5
TB4-A4
(+)
A12
B12
COM-B
COM-A
RS485 I/F
RELAY FAILURE
B13
TB3-A13
SIGNAL SEND
(HIGH SPEED RELAY)
BO13
FAIL
TB3-A18
B18
A17
B17
A16
B16
DD FAIL.
TB4 -A16
(-)
(+)
+5Vdc
0V
B18
A18
E
B17
B16
A17
DC
SUPPLY
CASE EARTH
DC-DC
RELAY FAIL.
1
B15
A15
TRIP-B
TRIP-A
TRIP-C
BUS CB
CENTER CB
(+)
TRIP-B
TRIP-A
TRIP-C
B14
A12
A13
B13
TP-A1
TP-B1
TP-C1
(+)
TB4- A3
A1
B3
A2
B2
TP-A2
TP-B2
TP-C2
TB4-A14
IRIG-B
BI1
BI10
BI11
BI2
BI8
BI12
BI9
BI5
BI6
BI7
BI3
BI4
BI13
BI14
BI15
BI16
BI17
BI18
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO1
BO2
BO3
20
CN1
COM-0V
B
A18
A
1
TB3 TB4
TB1
1
A1 B1
TB2
A
1
IO#3
IO#1
Terminal Block Arrangement (Rear Vi ew)
IO#2
A18
A1
B18
B10
B1
1 2
19 20
CN1
(IRIG-B)
E
B18
(1)
(1)These connections are connected
by short-bars before shipment.
IO#1
IO#2
Programmable BI
Ethernet LAN I/F x1 or x2
(100Base-TX:RJ45 connector)
T(T1,T2):
option
Opt. interface for IEC103
(ST connector)
Ethernet LAN I/F x1 or x2
(100Base-FX:SC connector)
OP
F(F1,F2):
option
CASE EARTH
(1)
IO module
IO#1 IO1
IO#2 IO2
IO#3 IO3
Model 301
328
6 F 2 S 0 8 5 1
CN1
IRIG-B
(1)These connections are
connected by short-bars before
hi
IO#1
TB1
TB2 TB4 TB5
VCT
IO#2 IO#3
Terminal Bl ock Arr angement (Rear view)
A18
A1
B18
B1
1 2
19 20
CN1
(IRIG-B)
E
IO#4
TB3
B9
(-)
(-)
B5
A6
B6
A7
B7
A8
B8
A9
A10
B10
A11
TB2 -A14
B11
B14
B15
A15
BUS
BUS
TB1 -1
4
3
2
7
6
5
9
8
10
12
11
13
15
14
16
BUS VT
CT
CT
CB
CB
VT
BUS VT
Io from
adjacent Line CT
17
18
ADJACENT LINE VT
CB
B4
A5
TB4- A4
(+)
A12
B12
RELAY FAILURE
B13
TB2-A13
SIGNAL SEND
(HIGH SPEED RELAY)
BO13
FAIL
COM-B
COM-A
COM-0V
RS485 I/F
TB2-A18
B18
A17
B17
A16
B16
TRIP-B
TRIP-A
TRIP-C
BUS CB
CENTER CB TRIP-B
TRIP-A
TRIP-C
B14
A12
A13
B13
TP-A1
TP-B1
TP-C1
TB4-A3
A1
B3
A2
B2
TP-A2
TP-B2
TP-C2
TB4-A14
BI35
BI36
BI34
BI1
BI10
BI11
BI2
BI8
BI12
BI9
BI5
BI6
BI7
BI3
BI4
BI13
BI14
BI15
BI16
BI17
BI18
BO1
BO2
BO3
TB3- B15
TB3- A15
TB3- A14
TB3- B14
20
(-)
A3
B3
A4
A5
B4
B5
A6
A7
B6
B7
A8
A9
B8
B9
A10
A11
B11
B10
TB2- A2
A1
B1
B2
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
A3
B3
A4
A5
B4
B5
A6
A7
B6
B7
A8
A9
B8
B9
A11
B11
A12
A13
B12
B13
IO#3
TB5- A2
A1
B1
B2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
IO#1
IO#2
IO#4
A3
B3
A4
A5
B4
B5
A6
A7
B6
B7
A8
A9
B8
B9
A11
B11
A12
A13
B12
B13
IO#4
TB3- A2
A1
B1
B2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
Programmable BI
(-)
TB5 -A14
B14
B15
A15
BI19
BI20
BI21
IO#3
Ethernet LAN I/F x1 or x2
(100Base-TX:RJ45 connector)
T(T1,T2):
option
Opt. interface for IEC103
(ST connector)
Ethernet LAN I/F x1 or x2
(100Base-FX:SC connector)
OP
F(F1,F2):
option
DD FAIL.
TB4 -A16
+5Vdc
0V
B18
A18
E
B17
B16
A17
DC
SUPPLY
CASE EARTH
DC-DC
RELAY FAIL.
1
B15
A15
(1)
(1)
Model 303
IO module
IO#1 IO1
IO#2 IO2
IO#3 IO4#1
IO#4 IO4#2
329
6 F 2 S 0 8 5 1
Appendix H
Relay Setting Sheet
Relay Identification
Transmission line parameters
Distance scheme
Autoreclose scheme
Contacts setting
Relay and Protection Scheme Setting Sheets
PLC default setting
330
6 F 2 S 0 8 5 1
Relay Setting Sheets
1. Relay Identification Date:
Relay type Serial Number
Frequency CT rating
VT rating dc supply voltage
Password
Active setting group
2. Transmission line parameters
Line type Line length
Line impedance Z1 =
Z0 = Z0 (mutual) =
Zm =
VT ratio CT ratio
Tripping mode 1 + 3 phase/3 phase
3. Distance scheme
Basic (3zone)
Zone 1 extension
PUP
POP
UOP
BOP
POP + DEF
UOP + DEF
BOP + DEF
PUP + DEF
4. Autoreclose scheme
Not used
SPAR
SPAR + TPAR
TPAR
EX1P (external autoreclose SPAR + TPAR scheme)
EX3P (external autoreclose TPAR scheme)
1CB or 2CB reclosing
Multi-shot autoreclose
1 shot, 2 shots, 3 shots or 4 shots
331
6 F 2 S 0 8 5 1
5. Contacts setting
(1) IO#2 BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
(2) IO#3 BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
(3) IO#4 BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
BO11
BO12
BO13
BO14
(Memo: For relay elements and scheme logic settings, the setting list as shown on the next page is made.)
332
6 F 2 S 0 8 5 1
6. Default setting
Relay and protection scheme setting sheet
Default Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
A 1 21000 Active group 1 - 8 Active setting group 1
2 5000 Line name Specified by user Line name no-name
3 6000 VT 1 -20000 VT ratio 2000
4 6002 VTs1 1 -20000 VT ratio 2000
5 6003 VTs2 1 -20000 VT ratio -- 2000
6 6001 CT 1 -20000 CT ratio 400
7 4000 X1 0.00 - 199.99 0.0 - 999.9 Fault location 2.00 / 10.0
8 4001 X0 0.00 - 199.99 0.0 - 999.9 ditto 6.80 / 34.0
9 4002 X0m 0.00 - 199.99 0.0 - 999.9 ditto 2.00 / 10.0
10 4003 R1 0.00 - 199.99 0.0 - 999.9 ditto 0.20 / 1.0
11 4004 R0 0.00 - 199.99 0.0 - 999.9 ditto 0.70 / 3.5
12 4005 R0m 0.00 - 199.99 0.0 - 999.9 ditto 0.20 / 1.0
13 4014 Z0B-L 0.00 - 199.99 0.0 - 999.9 ditto 2.00 / 10.0
14 4015 Z0B-R 0.00 - 199.99 0.0 - 999.9 ditto 2.00 / 10.0
15 4006 Kab 80 - 120 % ditto 100
16 4007 Kbc 80 - 120 % ditto 100
17 4008 Kca 80 - 120 % ditto 100
18 4009 Ka 80 - 120 % ditto 100
19 4010 Kb 80 - 120 % ditto 100
20 4011 Kc 80 - 120 % ditto 100
21 4012 Line 0.0 - 399.9 km ditto 50.0
22 4022 TNFLB 2.00 - 300.00 s Timer of No-trip-FL trigger blocking 2.00
23 1060 Protection scheme
3ZONE - Z1-EXT - PUP -
POP - UOP - BOP -
POP+DEF - UOP+DEF -
BOP+DEF - PUP+DEF
Protection scheme selection POP
24 1103 ZS-C Mho - Quad ZS relay characteristic Mho
25 1104 ZG-C Mho - Quad ZG relay characteristic Mho
26 1173 BLZONE COM - IND Blinder setting mode COM
27 1010 Z1CNT 1 - 2 - 3 - 4 - 5 Z1 trip mode 1
28 1000 PSB-Z1 Off - On PSB for Z1 element On
29 1001 PSB-Z1X Off - On PSB for Z1X element On
30 1002 PSB-Z2 Off - On PSB for Z2 element On
31 1003 PSB-Z3 Off - On PSB for Z3 element Off
32 1004 PSB-CR Off - On PSB for carrier trip On
33 1130 PSB-ZF Off - On PSB for ZF element Off
34 1131 PSB-ZR1 Off - On PSB for ZR1 element Off
35 1132 PSB-ZR2 Off - On PSB for ZR2 element Off
36 1005 PSB-TP Off - On Trip for under PSB On
37 1134 UVPWIEN Off - On Countermeasure for lead phase overreaching Off
38 1020 STUB Off - On Stub protection Off
39 1108 SOTF-DL CB - UV - Both SOTF condition judged CB
40 1021 SOTF-OC Off - On SOTF OC trip On
41 1136 SOTF-Z1 Off - On SOTF Zone1 trip Off
42 1137 SOTF-Z2 Off - On SOTF Zone2 trip Off
43 1138 SOTF-Z3 Off - On SOTF Zone3 trip Off
44 1140 SOTF-F Off - On SOTF Zone-F trip Off
45 1141 SOTF-R1 Off - On SOTF Zone-R1 trip Off
46 1142 SOTF-R2 Off - On SOTF Zone-R2 trip Off
47 1143 SOTF-ND Off - On SOTF Zone-ND trip Off
48 1144 ZFBT Off - On ZF element back-up trip Off
49 1034 ZR1BT Off - On ZR1 element back-up trip Off
50 1145 ZR2BT Off - On ZR2 element back-up trip Off
51 1146 ZNDBT Off - On Non-directional zone back-up trip Off
52 1036 OCBT Off - On OC back-up trip On
53 1037 OCIBT Off - On OCI back-up trip On
54 1093 MOCI Long - Std - Very - Ext OCI back-up trip Std
55 1030 EFBT Off - On EF back-up trip On
56 1031 EFBTAL Off - On EF back-up trip alarm On
57 1179 DEF DEFFEN Off - On Forward DEF back-up trip enable On
58 1181 BU-trip DEFREN Off - On Reverse DEF back-up trip enable On
59 1033 DEFBTAL Off - On DEF back-up trip alarm On
60 1092 DEFI Off - NOD - F - R DEF back-up trip Off
61 1091 MEFI Long - Std - Very - Ext EFI back-up trip Std
62 1183 OVS OVS1EN Off - DT - IDMT OVS1 enable Off
63 1184 OVS2EN Off - On OVS2 enable Off
64 1185 OVG OVG1EN Off - DT - IDMT OVG1 enable Off
65 1186 OVG2EN Off - On OVG2 enable Off
66 1187 UVS UVS1EN Off - DT - IDMT UVS1 enable Off
67 1188 UVS2EN Off - On UVS2 enable Off
68 1189 UVG UVG1EN Off - DT - IDMT UVG1 enable Off
69 1190 UVG2EN Off - On UVG2 enable Off
70 1191 UVS/UVG VBLKEN Off - On UV block enable Off
Units Contents
T
Name
Range
333
6 F 2 S 0 8 5 1
Relay and protection scheme setting sheet
Default Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
A 1 21000 Active group 1 8 Active setting group 1
71 1192 BCDEN Off - On Broken conductor enable Off
72 1061 CRSCM Off - On Carrier out of service On
73 1062 CHSEL Single - Guard - And Carr.Channel configuration Single
74 1063 BOSW Normal - Inverse Carrier sending signal Normal
75 1064 ZONESEL Z2 - Z3 Carrier control element Z2
76 1066 ECHO Off - On ECHO carrier send On
77 1067 WKIT Off - On Weak carrier trip(Echo) On
78 1085 CH-DEF CH1 - CH2 DEF carrier channel setting CH1
79 1086 BODEFSW Active - Inactive Binary switch for DEF carr. Active
80 1040 BF1 Off - T - TOC CBF re-trip Off
81 1041 BF2 Off - On CBF related trip Off
82 1042 BFEXT Off - On CBF initiation by ext. trip Off
83 1050 OST Off - Trip - BO Out of step trip Off
84 1152 THMT Off - On Thermal trip enable Off
85 1153 THMAL Off - On Thermal alarm enable Off
86 1149 VTF1EN Off - On - OPT-On VTF1 enable On
87 1150 VTF2EN Off - On - OPT-On VTF2 enable On
88 1151 VTF-Z4 Off - On Z4-car blocked by VTF On
89 1100 CHMON Off - On Carrier monitoring/testing On
90 1101 LSSV Off - On LS monitoring Off
91 1102 SVCNT ALM&BLK - ALM Supervision control ALM&BLK
92 1158 CTSV Off - ALM&BLK - ALM CT supervision control Off
93 1109 FL-Z0B Off - On Fault locator Off
94 1163 AOLED Off - On ALARM LED lighting control at alarm On
95 3000 ZS Z1S 0.01 - 50.00 0.10 - 250.00 Z1S reactance 1.60 / 8.00
96 3001 Z1BS 1.5 (fixed) 7.5 (fixed) Z1S mho offset (back) --
97 Z1S-Uvm V Minimum voltage phase detector --
98 3002 Z1XS 0.01 - 50.00 0.10 - 250.00 Z1XS reactance 2.40 / 12.00
99 3088 Z1S1 0 - 45 deg Z1S angle with reference to an X-axis 0
100 3089 Z1S2 45 - 90 deg Angle for Z1S hooked point with reference to an R-axis 90
101 3161 BFR1S 0.10 - 20.00 0.5 - 100.0 Blinder for Z1S forward ( R) 5.10 / 25.5
102 3148 BFRXS 0.10 - 20.00 0.5 - 100.0 Blinder for Z1XS forward ( R) 5.10 / 25.5
103 3003 Z2S 0.01 - 50.00 0.10 - 250.00 Z2S reactance 3.00 / 15.00
104 3162 BFR2S 0.10 - 20.00 0.5 - 100.0 Blinder for Z2S forward ( R) 5.10 / 25.5
105 3128 ZFS 0.01 - 50.00 0.1 - 250.0 ZFS reactance 4.00 / 20.0
106 3169 BFRFS 0.10 - 20.00 0.5 - 100.0 Blinder for ZFS forward ( R) 5.10 / 25.5
107 3004 Z3S 0.01 - 50.00 0.1 - 250.0 Z3S mho 6.00 / 30.0
108 3005 Z3S 45 - 90 deg Line angle for Z3S(Mho) element 85
109 3114 ZBS 0 - 45 deg Angle of direction(Quad) element 5
110 3006 BFRS 0.10 - 20.00 0.5 - 100.0 Blinder for ZS forward ( R) 5.10 / 25.5
111 3007 BFRS 75 (fixed) deg Angle of BFRS --
112 BFLS 0 (fixed) Blinder for ZS reverse (-R) --
113 3009 BFLS 90 - 135 deg Angle of BFLS 120
114 3130 ZR1S 0.01 - 50.00 0.1 - 250.0 ZR1S reactance 2.00 / 10.0
115 3131 ZR2S 0.01 - 50.00 0.1 - 250.0 ZR2S reactance 4.00 / 20.0
116 3010 Z4S 0.01 - 50.00 0.1 - 250.0 Z4S mho 8.00 / 40.0
117 3011 Z4BS 1.5 (fixed) 7.5 (fixed) Z4S offset-mho (back) --
118 Z4S 45 - 90 deg Line angle for Z4S(Mho) element -- (Linked with Z3S)
119 Z4BS 0 - 45 deg Angle of Z4S(Quad) offset -- (Linked with ZBS)
120 3013 BRRS 0.10 - 20.00 0.5 - 100.0 Blinder for ZS reverse (-R) 5.10 / 25.5
121 3014 BRRS 75 (fixed) deg Angle of BRRS --
122 BRLS 0.10 - 20.00
0.5 - 100.0
Blinder for ZS reverse (-R) -- (Linked with BRRS)
123 3016 BRLS 90 - 135 deg Angle of BRLS -- (Linked with BFLS)
124 3138 ZNDS 0.01 - 50.00
0.1 - 250.0
ZNDS 10.00 / 50.0
125 3139 BNDS 0.10 - 20.00
0.5 - 100.0
Blinder for ZNDS 12.00 / 60.0
126 12000 TZ1S 0.00 - 10.00 s Z1S time-delay trip 0.00
127 12001 TZ2S 0.00 - 10.00 s Z2S back-up trip timer 0.30
128 12071 TZFS 0.00 - 10.00 s ZFS back-up trip timer 0.35
129 12002 TZ3S 0.00 - 10.00 s Z3S back-up trip timer 0.40
130 12003 TZR1S 0.00 - 10.00 s ZR1S back-up trip timer 0.50
131 12072 TZR2S 0.00 - 10.00 s ZR2S back-up trip timer 0.60
132 12073 TZNDS 0.00 - 10.00 s Non-directional zone trip timer 0.70
133 3021 ZG Z1G 0.01 - 50.00 0.10 - 250.00 Z1G reactance 1.60 / 8.00
134 3022 Z1XG 0.01 - 50.00 0.10 - 250.00 Z1XG reactance 2.40 / 12.00
135 3094 Z1G1 0 - 45 deg Z1G angle with reference to an X-axis 0
136 3095 Z1G2 45 - 90 deg Angle for Z1G hooked point with reference to an R-axis 90
137 3164 BFR1G 0.10 - 20.00 0.5 - 100.0 Blinder for Z1G forward ( R) 5.10 / 25.5
138 3150 BFRXG 0.10 - 20.00 0.5 - 100.0 Blinder for Z1XG forward ( R) 5.10 / 25.5
139 3023 Z2G 0.01 - 50.00 0.10 - 250.00 Z2G reactance 4.00 / 20.00
140 3165 BFR2G 0.10 - 20.00 0.5 - 100.0 Blinder for Z2G forward ( R) 5.10 / 25.5
141 3129 ZFG 0.01 - 100.00 0.1 - 500.0 ZFG reactance 6.00 / 30.0
142 3191 BFRFG 0.10 - 20.00 0.5 - 100.0 Blinder for ZFG forward ( R) 5.10 / 25.5
143 3024 Z3G 0.01 - 100.00 0.1 - 500.0 Z3G mho 8.00 / 40.0
144 3025 Z3G 45 - 90 deg Line angle for Z3S(Mho) element 85
145 3115 ZBG 0 - 45 deg Angle of direction(Quad) element 30
5.5 (fixed)
Units Contents
T
Name
Range
334
6 F 2 S 0 8 5 1
Relay and protection scheme setting sheet
Default Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
146 3026 BFRG 0.10 - 20.00 0.5 - 100.0 Blinder for ZG forward ( R) 5.10 / 25.5
147 3027 BFRG 75 (fixed) deg Angle of BFRG --
148 BFLG 0 (fixed) Blinder for ZG forward (-R) --
149 3029 BFLG 90 - 135 deg Angle of BFLG 120
150 3132 ZR1G 0.01 - 50.00 0.1 - 250.0 ZR1G reactance 2.00 / 10.0
151 3133 ZR2G 0.01 - 100.00 0.1 - 500.0 ZR2G reactance 4.00 / 20.0
152 3030 Z4G 0.01 - 100.00 0.1 - 500.0 Z4G mho 8.00 / 40.0
153 Z4G 45 - 90 deg Line angle for Z4G(Mho) element -- (Linked with Z3G)
154 Z4BG 0 - 45 deg Angle of Z4G(Quad) offset -- (Linked with ZBG)
155 3032 BRRG 0.10 - 20.00 0.5 - 100.0 Blinder for ZG reverse (-R) 5.10 / 25.5
156 3033 BRRG 75 (fixed) deg Angle of BRRG --
157 BRLG 0.10 - 20.00 0.5 - 100.0 Blinder for ZG reverse ( R) -- (Linked with BRRG)
158 BRLG 90 - 135 deg Angle of BRLG -- (Linked with BFLG)
159 3036 Krs 0 - 1000 % Zero phase current factor: Self line "R0/R1" 340
160 3037 Kxs 0 - 1000 % Zero phase current factor: Self line "X0/X1" 340
161 3038 Krm 0 - 1000 % Zero phase current factor: Adjacent line "Rom/R1" 300
162 3039 Kxm 0 - 1000 % Zero phase current factor: Adjacent line "Xom/X1" 300
163 3134 KrsR 0 - 1000 % Zero phase current factor for ZR element: Self line 100
164 3135 KxsR 0 - 1000 % Zero phase current factor for Zr element: Self line "X0/X1" 100
165 3140 ZNDG 0.01 - 100.00 0.1 - 500.0 ZNDG 10.00 / 50.0
166 3141 BNDG 0.10 - 20.00 0.5 - 100.0 Blinder for ZNDG 12.00 / 60.0
167 12004 TZ1G 0.00 - 10.00 s Z1G time-delay trip 0.00
168 12005 TZ2G 0.00 - 10.00 s Z2G back-up trip timer 0.30
169 12074 TZFG 0.00 - 10.00 s ZFG back-up trip timer 0.35
170 12006 TZ3G 0.00 - 10.00 s Z3G back-up trip timer 0.40
171 12007 TZR1G 0.00 - 10.00 s ZR1G back-up trip timer 0.50
172 12075 TZR2G 0.00 - 10.00 s ZR2G back-up trip timer 0.60
173 12076 TZNDG 0.00 - 10.00 s Non-directional zone trip timer 0.70
174 3090 ZIC 0.00 - 5.00 0.00 - 1.00 A Charging current compensation 0.00
175 3047 Vn 100 - 120 V Rated voltage 110
176 3044 ZPCC ZPCC 0.8 (Sensitivity ratio) Zero phase current --
177 OCG 0.2 (fixed) 0.04 (fixed) A compensation controller --
178 3046 PSB PSBSZ 0.50 - 15.00 2.5 - 75.0 Power swing block for Ph-Ph 2.00 / 10.0
179 3136 PSBGZ 0.50 - 15.00 2.5 - 75.0 Power swing block for Ph-G 2.00 / 10.0
180 PSBR 75 (fixed) deg ditto --
181 PSBL 105 (fixed) deg ditto --
182 12015 TPSB 20 - 60 ms PS detection timer 40
183 3050 OST OSTR1 3.0 - 30.0 15 - 150 Out of step relay 5.1 / 25
184 3051 OSTR2 1.0 - 10.0 5 - 50 ditto 2.5 / 12
185 3052 OSTXF 1.0 - 50.0 5 - 250 ditto 6.0 / 30
186 3053 OSTXB 0.2 - 10.0 1 - 50 ditto 1.0 / 5
187 12010 TOST1 0.01 - 1.00 s ditto 0.04
188 12011 TOST2 0.01 - 1.00 s ditto 0.04
189 3056 OCH 2.0 - 15.0 0.4 - 3.0 A Overcurrent element 6.0 / 1.2
190 12027 TSOTF s CB open detect timer for SOTF 5
191 3058 CBF OCBF 0.5 - 10.0 0.1 - 2.0 A Overcurrent element 4.0 / 0.8
192 12020 TBF1 50 - 500 ms CBF timer for re-trip 150
193 12021 TBF2 50 - 500 ms CBF timer for related trip 200
194 OCD 0.5 (fixed) 0.1 (fixed) A Curr. change detector --
195 3057 OCCR 0.4 (fixed) 0.08 (fixed) A OC element --
196 3062 DEF DEFFI 0.5 - 5.0 0.10 - 1.00 A Directional earth fault element 1.0 / 0.20
197 3063 DEFFV 1.7 - 21.0 V ditto 2.0
198 3066 DEFRI 0.5 - 5.0 0.10 - 1.00 A ditto 1.0 / 0.20
199 3067 DEFRV 1.7 - 21.0 V ditto 2.0
200 3064 DEF 0 - 90 deg ditto 85
201 12086 DEF TDEF 0.00 - 10.00 s Forward definite timer 3.00
202 12087 BU-trip TDER 0.00 - 10.00 s Reverse definite timer 3.00
203 3060 OC OC 0.5 - 100.0 0.1 - 20.0 A OC element 6.0 / 1.2
204 12024 TOC 0.00 - 10.00 s ditto 3.00
205 3073 OCI OCI 0.5 - 25.0 0.10 - 5.00 A IDMT OC element 1.0 / 0.20
206 3074 TOCI 0.05 - 1.00 ditto 0.50
207 3142 TOCIR 0.0 - 10.0 s OC definite time reset delay 0.0
208 3069 EF EF 0.5 - 5.0 0.10 - 1.00 A Earth fault OC element 1.0 / 0.20
209 12023 TEF 0.00 - 10.00 s ditto 3.00
210 3071 EFI EFI 0.5 - 5.0 0.10 - 1.00 A IDMT earth fault OC element 1.0 / 0.20
211 3072 TEFI 0.05 - 1.00 ditto 0.50
212 3143 TEFIR 0.0 - 10.0 s EF definite time reset delay 0.0
213 3137 EFL 0.5 - 5.0 0.10 - 1.00 A EF element for ZG fail safe 1.0 / 0.20
214 3075 UVC UVCV 10 - 60 V Undervoltage element with current compensation 48
215 3076 UVCZ 0.0 - 50.0 0.0 - 250.0 ditto 2.0 / 10.0
216 3079 UVC 45 - 90 deg ditto 85
217 UVCKrs 0 - 1000 % ditto -- (Linked with Krs of ZG)
218 UVCKxs 0 - 1000 % ditto -- (Linked with Kxs of ZG)
219 OVG 20 (fixed) V OV element --
0 - 300
Units Contents
T
Name
Range
335
6 F 2 S 0 8 5 1
Relay and protection scheme setting sheet
Default Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
220 3081 UVFS 50 - 100 V UV ph-ph element 88
221 3082 UVLS 50 - 100 V UV ph-ph element "L" level 77
222 3083 UVFG 10 - 60 V UV ph-g element 51
223 3084 UVLG 10 - 60 V UV ph-g element "L" level 45
224 UVPWI 30 (fixed) V UV for positive weak infeed --
225 3065 OCDP 0.5 - 10.0 0.1 - 2.0 A Curr. change detector for fault under PSB 4.0 / 0.8
226 3170 OVS OVS1 5.0 - 150.0 V OVS1 element 120.0
227 3171 TOS1I 0.05 - 100.00 OVS1 IDMT timer 10.00
228 12093 TOS1 0.00 - 300.00 s OVS1 definite timer 0.10
229 3157 TOS1R 0.0 - 300.0 s OVS1 definite time reset delay 0.0
230 3172 OS1DP 10 - 98 % OVS1 DO/PU ratio 95
231 3173 OVS2 5.0 - 150.0 V OVS2 element 140.0
232 12094 TOS2 0.00 - 300.00 s OVS2 definite timer 0.10
233 3174 OS2DP 10 - 98 % OVS2 DO/PU ratio 95
234 3175 OVG OVG1 5.0 - 150.0 V OVG1 element 70.0
235 3176 TOG1I 0.05 - 100.00 OVG1 IDMT timer 10.00
236 12095 TOG1 0.00 - 300.00 s OVG1 definite timer 0.10
237 3158 TOG1R 0.0 - 300.0 s OVG1 definite time reset delay 0.0
238 3177 OG1DP 10 - 98 % OVG1 DO/PU ratio 95
239 3178 OVG2 5.0 - 150.0 V OVG2 element 80.0
240 12096 TOG2 0.00 - 300.00 s OVG2 definite timer 0.10
241 3179 OG2DP 10 - 98 % OVG2 DO/PU ratio 95
242 3180 UVS UVS1 5.0 - 150.0 V UVS1 element 60.0
243 3181 TUS1I 0.05 - 100.00 UVS1 IDMT timer 10.00
244 12097 TUS1 0.00 - 300.00 s UVS1 definite timer 0.10
245 3159 TUS1R 0.0 - 300.0 s UVS1 definite time reset delay 0.0
246 3182 UVS2 5.0 - 150.0 V UVS2 element 40.0
247 12098 TUS2 0.00 - 300.00 s UVS2 definite timer 0.10
248 3183 VSBLK 5.0 - 20.0 V UVS blocking threshold 10.0
249 3184 UVG UVG1 5.0 - 150.0 V UVG1 element 35.0
250 3185 TUG1I 0.05 - 100.00 UVG1 IDMT timer 10.00
251 12099 TUG1 0.00 - 300.00 s UVG1 definite timer 0.10
252 3160 TUG1R 0.0 - 300.0 s UVG1 definite time reset delay 0.0
253 3186 UVG2 5.0 - 150.0 V UVG2 element 25.0
254 12100 TUG2 0.00 - 300.00 s UVG2 definite timer 0.10
255 3187 VGBLK 5.0 - 20.0 V UVG blocking threshold 10.0
256 3188 BCD BCD 0.10 - 1.00 Broken conductor threshold 0.20
257 12101 TBCD 0.00 - 300.00 s BCD definite timer 1.00
258 3144 Thermal THM 2.0 - 10.0 0.40 - 2.00 A Thermal overload setting 5.0 / 1.00
259 3145 THMIP 0.0 - 5.0 0.00 - 1.00 A Prior load setting 0.0 / 0.00
260 3146 TTHM 0.5 - 300.0 min Thermal Time Constant 10.0
261 3147 THMA 50 - 99 % Thermal alarm setting 80
262 12040 TDEFF 0.00 - 0.30 s DEF carrier trip delay timer 0.15
263 12041 TDEFR 0.00 - 0.30 s ditto 0.15
264 12042 TCHD 0 - 50 ms Coordination timer 12
265 12078 TREBK 0.00 - 10.00 s Current reverse blocking time 0.10
266 12079 TECCB 0.00 - 200.00 s Echo enable timer from CB opened 0.10
267 12080 TSBCT 0.00 - 1.00 s SBCNT timer 0.10
268 1070 Autoreclose mode
(Off) - Disable - SPAR -
TPAR - SPAR&TPAR -
EXT1P - EXT3P
Autoreclosing mode SPAR&TPAR
269 1072 ARC-CB ONE - O1 - 02 - L1 - L2 ARC mode for 1.5CB system -- L1
270 1075 ARC-EXT Off - On ARC initiated by ext. trip Off
271 1074 ARC-DEF Off - On ARC by DG carr. trip Off
272 1082 ARC-BU Off - On ARC by back-up trip Off
Off - LB - DB - SY TPAR condition (1CB) LB --
Off - LB1 - LB2 - DB - SY TPAR condition (2CB) -- LB1
274 1071 ARC-SM Off - S2 - S3 - S4 Multi. shot ARC mode Off
275 1162 ARC-SUC Off - On ARC success reset Off
276 1078 VTPHSEL A - B - C VT phase selection A
277 1079 VT-RATE PH/G - PH/PH VT rating PH/G
278 1080 3PH-VT Bus - Line 3ph. VT location Line
279 1164 UARCSW P1 - P2 - P3 User ARC switch P1
280 12050 TEVLV 0.01 - 10.00 s Dead timer reset timing 0.30
281 12054 TRDY1 5 - 300 s Reclaim timer 60
282 12051 TSPR1 0.01 - 10.00 s SPAR dead line timer 0.80
283 12052 TTPR1 0.01 - 100.00 s TPAR dead line timer 0.60
284 12056 TRR 0.01 - 100.00 s ARC reset timer 2.00
285 12057 TW1 0.1 - 10.0 s ARC output pulse timer 0.2
286 12055 TRDY2 5 - 300 s Reclaim timer -- 60
287 12081 TSPR2 0.01 - 10.00 s SPAR dead line timer -- 0.80
288 12053 TTPR2 0.1 - 10.0 s ARC timing for follower CB -- 0.1
289 12058 TW2 0.1 - 10.0 s ARC reset timer -- 0.2
290 12059 TS2 5.0 - 300.0 s Multi. shot dead timer 20.0
291 12062 TS2R 5.0 - 300.0 s Multi. shot reset timer 30.0
VCHK
Units Contents
T
Name
Range
273 1073
VCHK
336
6 F 2 S 0 8 5 1
Relay and protection scheme setting sheet
Default Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
292 12060 TS3 5.0 - 300.0 s Multi. shot dead timer 20.0
293 12063 TS3R 5.0 - 300.0 s Multi. shot reset timer 30.0
294 12061 TS4 5.0 - 300.0 s Multi. shot dead timer 20.0
295 12064 TS4R 5.0 - 300.0 s Multi. shot reset timer 30.0
296 12084 TSUC 0.1 - 10.0 s ARC success reset timer 3.0
297 3097 OVB 10 - 150 V OV element 51
298 3098 UVB 10 - 150 V UV element 13
299 3099 OVL1 10 - 150 V OV element 51
300 3100 UVL1 10 - 150 V UV element 13
301 3085 SYN1 SY1UV 10 - 150 V Synchro. check (UV) 83
302 3086 SY1OV 10 - 150 V Synchro. check (OV) 51
303 3087 SY1 5 - 75 deg Synchro. check (ph. diff.) 30
304 12030 TSYN1 0.01 - 10.00 s Synchronism check timer 1.00
305 12031 TDBL1 0.01 - 1.00 s Voltage check timer 0.05
306 12032 TLBD1 0.01 - 1.00 s Voltage check timer 0.05
307 12085 T3PLL 0.01 - 1.00 s three phase live line check timer 0.05
308 3101 OVL2 10 - 150 V OV element -- 51
309 3102 UVL2 10 - 150 V UV element -- 13
310 3091 SYN2 SY2UV 10 - 150 V Synchro. check (UV) -- 83
311 3092 SY2OV 10 - 150 V Synchro. check (OV) -- 51
312 3093 SY2 5 - 75 deg Synchro. check (ph. diff.) -- 30
313 12033 TSYN2 0.01 - 10.00 s Synchronism check timer -- 1.00
314 12034 TDBL2 0.01 - 1.00 s Voltage check timer -- 0.05
315 12035 TLBD2 0.01 - 1.00 s Voltage check timer -- 0.05
316 22000 BISW 1 Norm - Inv Binary input Norm
317 22001 BISW 2 Norm - Inv ditto Norm
318 22002 BISW 3 Norm - Inv ditto Norm
319 22003 BISW 4 Norm - Inv ditto Norm
320 22004 BISW 5 Norm - Inv ditto Norm
321 22005 BISW 6 Norm - Inv ditto Norm
322 22006 BISW 7 Norm - Inv ditto Norm
323 22007 BISW 8 Norm - Inv ditto Norm
324 22008 BISW 9 Norm - Inv ditto Norm
325 22009 BISW 10 Norm - Inv ditto Norm
326 22010 BISW 11 Norm - Inv ditto Norm
327 22011 BISW 12 Norm - Inv ditto Norm
328 22012 BISW 13 Norm - Inv ditto Norm
329 22013 BISW 14 Norm - Inv ditto Norm
330 22014 BISW 15 Norm - Inv ditto Norm
331 22015 BISW 16 Norm - Inv ditto Norm
332 22016 BISW 17 Norm - Inv ditto Norm
333 22017 BISW 18 Norm - Inv ditto Norm
334 22018 BISW 19 Norm - Inv ditto --
335 22019 BISW 20 Norm - Inv ditto --
336 22020 BISW 21 Norm - Inv ditto --
337 22033 BISW 34 Norm - Inv ditto -- Norm
338 22034 BISW 35 Norm - Inv ditto -- Norm
339 22035 BISW 36 Norm - Inv ditto -- Norm
340 23032 LED1 Logic OR - AND ConfigurableLEDs OR
341 23033 Reset Inst - Latch Inst
342 23000 In #1 0 - 3071 0
343 23004 In #2 0 - 3071 0
344 23008 In #3 0 - 3071 0
345 23012 In #4 0 - 3071 0
346 23034 LED2 Logic OR - AND ConfigurableLEDs OR
347 23035 Reset Inst - Latch Inst
348 23001 In #1 0 - 3071 0
349 23005 In #2 0 - 3071 0
350 23006 In #3 0 - 3071 0
351 23007 In #4 0 - 3071 0
352 23036 LED3 Logic OR - AND ConfigurableLEDs OR
353 23037 Reset Inst - Latch Inst
354 23002 In #1 0 - 3071 0
355 23009 In #2 0 - 3071 0
356 23010 In #3 0 - 3071 0
357 23011 In #4 0 - 3071 0
358 23038 LED4 Logic OR - AND ConfigurableLEDs OR
359 23039 Reset Inst - Latch Inst
360 23003 In #1 0 - 3071 0
361 23013 In #2 0 - 3071 0
362 23014 In #3 0 - 3071 0
363 23015 In #4 0 - 3071 0
364 17000 Plant name Specified by user Plant name no-name
365 17001 Description ditto Memorandum for user no-data
Units Contents
T
Name
Range
337
6 F 2 S 0 8 5 1
Relay and protection scheme setting sheet
Def ault Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
366 19000 HDLC 1 - 32
IP Address 192
370 19097 IP1-2 0-254
IP Address 168
371 19098 IP1-3 0-254
IP Address 19
372 19099 IP1-4 0-254
IP Address 172
373 19100 SM1-1 0-255
Subnet Mask 0
377 19104 GW1-1 0-254
Gateway Address 19
380 19107 GW1-4 0-254
Gateway Address 1
381 19084 IP2-1 0-254
IP Address 192
382 19085 IP2-2 0-254
IP Address 168
383 19086 IP2-3 0-254
IP Address 19
384 19087 IP2-4 0-254
IP Address 173
385 19088 SM2-1 0-255
Subnet Mask 0
389 19092 GW2-1 0-254
Gateway Address 19
392 19095 GW2-4 0-254
Gateway Address 1
393 19108 SI1-1 0-254
IEC61850 Authorize Of f
427 19038 TSTMOD Of f - On
Ping check Of f
430 19125 RLNSCH Of f - HS1
Disturbance trigger On
440 18050 OCP-S Of f - On
ditto On
441 18051 OCP-G Of f - On
ditto On
442 18052 UVP-S Of f - On
ditto On
443 18053 UVP-G Of f - On
ditto On
Units Contents Name
Range
338
6 F 2 S 0 8 5 1
Relay and protection scheme setting sheet
Def ault Setting of Relay Series
(5A rating / 1A rating) User
1CB-ARC 2CB-ARC Setting
5A rating 1A rating 201 301 303
R
444 18038 Chann 1 - 24 hrs
Carrier testing timer
(Automatic test interval)
8
445 20000 Display value Primary - Secondary
Metering Primary
446 20001 Power (P/Q) Send - Receive
Metering Send
447 20002 Current Lag - Lead
Metering Lead
448 20008 Time sync Off - IRIG- RSM - IEC - RMT - SNTP
Time Of f
449 20009 GMT -12 - +12 hrs Time 0
450 20010 GMTm -59 - 59 min Time 0
Units Contents Name
Range
339
6 F 2 S 0 8 5 1
Event record default setting
Default setting
Sig. NO. Signal name type
1 EV1 0 - 3071 Event record signal 1536 CB1 A On/Off
2 EV2 0 - 3071 ditto 1537 CB1 B On/Off
3 EV3 0 - 3071 ditto 1538 CB1 C On/Off
4 EV4 0 - 3071 ditto 1552 CB2 A On/Off
5 EV5 0 - 3071 ditto 1553 CB2 B On/Off
6 EV6 0 - 3071 ditto 1554 CB2 C On/Off
7 EV7 0 - 3071 ditto 1542 DS On/Off
8 EV8 0 - 3071 ditto 9 COM.block On/Off
9 EV9 0 - 3071 ditto 1545 CB1 ready On/Off
10 EV10 0 - 3071 ditto 1546 CB2 ready On/Off
11 EV11 0 - 3071 ditto 1547 ARC block On/Off
12 EV12 0 - 3071 ditto 1548 Ind.reset On/Off
13 EV13 0 - 3071 ditto 1549 Ext.M.trip On/Off
14 EV14 0 - 3071 ditto 1550 Ext.M.prot. On/Off
15 EV15 0 - 3071 ditto 1556 Ext.trip A On/Off
16 EV16 0 - 3071 ditto 1557 Ext.trip B On/Off
17 EV17 0 - 3071 ditto 1558 Ext.trip C On/Off
18 EV18 0 - 3071 ditto 238 Trip On/Off
19 EV19 0 - 3071 ditto 291 CB1 ARC On/Off
20 EV20 0 - 3071 ditto 292 CB2 ARC On/Off
21 EV21 0 - 3071 ditto 172 VTF On/Off
22 EV22 0 - 3071 ditto 176 PSB On/Off
23 EV23 0 - 3071 ditto 253 Ch.fail On/Off
24 EV24 0 - 3071 ditto 254 Relay fail On/Off
25 EV25 0 - 3071 ditto 1268 V0 err On/Off
26 EV26 0 - 3071 ditto 1269 V2 err On/Off
27 EV27 0 - 3071 ditto 1267 I0 err On/Off
28 EV28 0 - 3071 ditto 257 DS fail On/Off
29 EV29 0 - 3071 ditto 490 AS1 On/Off
30 EV30 0 - 3071 ditto 491 AS2 On/Off
31 EV31 0 - 3071 ditto 492 AF1 On/Off
32 EV32 0 - 3071 ditto 493 AF2 On/Off
33 EV33 0 - 3071 ditto 0 On/Off
34 EV34 0 - 3071 ditto 0 On/Off
35 EV35 0 - 3071 ditto 0 On/Off
36 EV36 0 - 3071 ditto 0 On/Off
37 EV37 0 - 3071 ditto 0 On/Off
38 EV38 0 - 3071 ditto 0 On/Off
39 EV39 0 - 3071 ditto 0 On/Off
40 EV40 0 - 3071 ditto 0 On/Off
41 EV41 0 - 3071 ditto 0 On/Off
42 EV42 0 - 3071 ditto 0 On/Off
43 EV43 0 - 3071 ditto 0 On/Off
44 EV44 0 - 3071 ditto 0 On/Off
45 EV45 0 - 3071 ditto 0 On/Off
46 EV46 0 - 3071 ditto 0 On/Off
47 EV47 0 - 3071 ditto 0 On/Off
48 EV48 0 - 3071 ditto 0 On/Off
49 EV49 0 - 3071 ditto 1258 Relay fail-A On/Off
50 EV50 0 - 3071 ditto 1438 Data lost On/Off
51 EV51 0 - 3071 ditto 1266 CT err On/Off
52 EV52 0 - 3071 ditto 0 On/Off
53 EV53 0 - 3071 ditto 0 On/Off
54 EV54 0 - 3071 ditto 0 On/Off
55 EV55 0 - 3071 ditto 0 On/Off
56 EV56 0 - 3071 ditto 0 On/Off
57 EV57 0 - 3071 ditto 0 On/Off
58 EV58 0 - 3071 ditto 0 On/Off
59 EV59 0 - 3071 ditto 0 On/Off
60 EV60 0 - 3071 ditto 0 On/Off
61 EV61 0 - 3071 ditto 0 On/Off
62 EV62 0 - 3071 ditto 0 On/Off
63 EV63 0 - 3071 ditto 0 On/Off
64 EV64 0 - 3071 ditto 0 On/Off
All models Unit Contents No. Name Range
340
6 F 2 S 0 8 5 1
Event record default setting
Default setting
Sig. NO. Signal name type
65 EV65 0 - 3071 ditto 0 On/Off
66 EV66 0 - 3071 ditto 0 On/Off
67 EV67 0 - 3071 ditto 0 On/Off
68 EV68 0 - 3071 ditto 0 On/Off
69 EV69 0 - 3071 ditto 0 On/Off
70 EV70 0 - 3071 ditto 0 On/Off
71 EV71 0 - 3071 ditto 0 On/Off
72 EV72 0 - 3071 ditto 0 On/Off
73 EV73 0 - 3071 ditto 0 On/Off
74 EV74 0 - 3071 ditto 0 On/Off
75 EV75 0 - 3071 ditto 0 On/Off
76 EV76 0 - 3071 ditto 0 On/Off
77 EV77 0 - 3071 ditto 0 On/Off
78 EV78 0 - 3071 ditto 0 On/Off
79 EV79 0 - 3071 ditto 0 On/Off
80 EV80 0 - 3071 ditto 0 On/Off
81 EV81 0 - 3071 ditto 0 On/Off
82 EV82 0 - 3071 ditto 0 On/Off
83 EV83 0 - 3071 ditto 0 On/Off
84 EV84 0 - 3071 ditto 0 On/Off
85 EV85 0 - 3071 ditto 0 On/Off
86 EV86 0 - 3071 ditto 0 On/Off
87 EV87 0 - 3071 ditto 0 On/Off
88 EV88 0 - 3071 ditto 0 On/Off
89 EV89 0 - 3071 ditto 0 On/Off
90 EV90 0 - 3071 ditto 0 On/Off
91 EV91 0 - 3071 ditto 0 On/Off
92 EV92 0 - 3071 ditto 0 On/Off
93 EV93 0 - 3071 ditto 0 On/Off
94 EV94 0 - 3071 ditto 0 On/Off
95 EV95 0 - 3071 ditto 0 On/Off
96 EV96 0 - 3071 ditto 0 On/Off
97 EV97 0 - 3071 ditto 0 On/Off
98 EV98 0 - 3071 ditto 0 On/Off
99 EV99 0 - 3071 ditto 0 On/Off
100 EV100 0 - 3071 ditto 0 On/Off
101 EV101 0 - 3071 ditto 1243 SET.GROUP1 On
102 EV102 0 - 3071 ditto 1244 SET.GROUP2 On
103 EV103 0 - 3071 ditto 1245 SET.GROUP3 On
104 EV104 0 - 3071 ditto 1246 SET.GROUP4 On
105 EV105 0 - 3071 ditto 1247 SET.GROUP5 On
106 EV106 0 - 3071 ditto 1248 SET.GROUP6 On
107 EV107 0 - 3071 ditto 1249 SET.GROUP7 On
108 EV108 0 - 3071 ditto 1250 SET.GROUP8 On
109 EV109 0 - 3071 ditto 1448 Sys. Set change On
110 EV110 0 - 3071 ditto 1449 Rly. Set change On
111 EV111 0 - 3071 ditto 1450 Grp. Set change On
112 EV112 0 - 3071 ditto 0 On
113 EV113 0 - 3071 ditto 0 On
114 EV114 0 - 3071 ditto 0 On
115 EV115 0 - 3071 ditto 0 On
116 EV116 0 - 3071 ditto 0 On
117 EV117 0 - 3071 ditto 0 On
118 EV118 0 - 3071 ditto 0 On
119 EV119 0 - 3071 ditto 1445 PLC data CHG On
120 EV120 0 - 3071 ditto 0 On
121 EV121 0 - 3071 ditto 1409 LED RST On
122 EV122 0 - 3071 ditto 1435 F.record_CLR On
123 EV123 0 - 3071 ditto 0 On
124 EV124 0 - 3071 ditto 1436 E.record_CLR On
125 EV125 0 - 3071 ditto 1437 D.record_CLR On
126 EV126 0 - 3071 ditto 851 NTP_FL_TRG On
127 EV127 0 - 3071 ditto 0 On
128 EV128 0 - 3071 ditto 0 On
All models Unit Contents No. Name Range
341
6 F 2 S 0 8 5 1
Disturbance record default setting
Default setting Model
Signal No. Signal name 201 301, 303
1 SIG1 0 - 3071 disturbance record triger 235 TRIP-A
2 SIG2 0 - 3071 ditto 236 TRIP-B
3 SIG3 0 - 3071 ditto 237 TRIP-C
4 SIG4 0 - 3071 ditto 291 ARC1
5 SIG5 0 - 3071 ditto 292 ARC2 --
6 SIG6 0 - 3071 ditto 194 BU_TRIP
7 SIG7 0 - 3071 ditto 231 CAR_TRIP
8 SIG8 0 - 3071 ditto 342 Z1_TRIP
9 SIG9 0 - 3071 ditto 343 Z1X_TRIP
10 SIG10 0 - 3071 ditto 347 Z2+Z3+ZR1
11 SIG11 0 - 3071 ditto 349 EF/DEF_ALARM
12 SIG12 0 - 3071 ditto 328 OC_BU-TRIP
13 SIG13 0 - 3071 ditto 350 SOTF+STUB
14 SIG14 0 - 3071 ditto 176 PSB_DET
15 SIG15 0 - 3071 ditto 203 OST_TRIP
16 SIG16 0 - 3071 ditto 225 EXT_CAR-S
17 SIG17 0 - 3071 ditto 204 EXT_CAR-R1
18 SIG18 0 - 3071 ditto 1540 Z1X_INIT
19 SIG19 0 - 3071 ditto 1536 CB1_CONT-A
20 SIG20 0 - 3071 ditto 1537 CB1_CONT-B
21 SIG21 0 - 3071 ditto 1538 CB1_CONT-C
22 SIG22 0 - 3071 ditto 1542 DS_N/O_CONT
23 SIG23 0 - 3071 ditto 1545 CB1_READY
24 SIG24 0 - 3071 ditto 1546 CB2_READY --
25 SIG25 0 - 3071 ditto 1552 CB2_CONT-A --
26 SIG26 0 - 3071 ditto 1553 CB2_CONT-B --
27 SIG27 0 - 3071 ditto 1554 CB2_CONT-C --
28 SIG28 0 - 3071 ditto 0 NA
29 SIG29 0 - 3071 ditto 0 NA
30 SIG30 0 - 3071 ditto 0 NA
31 SIG31 0 - 3071 ditto 0 NA
32 SIG32 0 - 3071 ditto 0 NA
Unit Contents No. Name Range
342
6 F 2 S 0 8 5 1
PLC default setting
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
1604 PSBTP_BLOCK
1605
1606
1607
1608 OC-A_FS X 0 [1]CONSTANT_1 X
1609 OC-B_FS X 0 [1]CONSTANT_1 X
1610 OC-C_FS X 0 [1]CONSTANT_1 X
1611
1612 OCI-A_FS X 1 [1]CONSTANT_1 X
1613 OCI-B_FS X 1 [1]CONSTANT_1 X
1614 OCI-C_FS X 1 [1]CONSTANT_1 X
1615 THMA_BLOCK
1616 Z1G_BLOCK X 0 [715]Z1CNT_TPBLK X
1617 Z1XG_BLOCK
1618 Z2G_BLOCK
1619 Z3G_BLOCK
1620 ZR1G_BLOCK
1621 ZFG_BLOCK
1622 STUB_BLOCK X -- X
1623 SOTF_BLOCK X -- X
1624 OCH_TRIP
1625 OC_BLOCK X -- X
1626 OCI_BLOCK X -- X
1627 EF_BLOCK
1628 EFI_BLOCK X -- X
1629 DEF_BLOCK X -- X
1630 OST_BLOCK
1631 THM_BLOCK
1632 Z1S_BLOCK X 0 [715]Z1CNT_TPBLK X
1633 Z1XS_BLOCK
1634 Z2S_BLOCK
1635 Z3S_BLOCK
1636 ZR1S_BLOCK
1637 ZFS_BLOCK
1638 ZR2G_BLOCK
1639 ZR2S_BLOCK
1640 CBF_BLOCK
1641 EXTTP_BLOCK X -- X
1642 VTF_BLOCK
1643 VTF_ALARM
1644 TR1_BLOCK
1645 TR2_BLOCK
1646 ZNDG_BLOCK
1647 ZNDS_BLOCK
1648 Z1S_G-BLK
1649 STUB_CB X 1 [1]CONSTANT_1 X
1650 OCHTP_ON X
[708]SHOT_NUM2 + [709]SHOT_NUM3 + [710]SHOT_NUM4 +
[711]SHOT_NUM5
X
1651 PSB.F_RESET
1652 DEF_PHSEL-A
1653 DEF_PHSEL-B
1654 DEF_PHSEL-C
1655 Z1_ARC_BLOCK X 0 [714]Z1CNT_ARCBLK X
1656 Z2G-A_FS X 1 [1]CONSTANT_1 X
1657 Z2G-B_FS X 1 [1]CONSTANT_1 X
1658 Z2G-C_FS X 1 [1]CONSTANT_1 X
1659 Z1X_F.ENABLE
1660
1661
1662
1663
1664 ZFG-A_BLOCK X [29]Z3G-B X
1665 ZFG-B_BLOCK X [30]Z3G-C X
1666 ZFG-C_BLOCK X [28]Z3G-A X
1667
1668 ZNDG-A_COM X [666]ZNDG-AX X
1669 ZNDG-B_COM X [667]ZNDG-BX X
1670 ZNDG-C_COM X [668]ZNDG-CX X
1671 ZNDS_COM X [669]ZNDS-ABX + [670]ZNDS-BCX + [671]ZNDS-CAX X
None Signal Turn On
Delay
One
Shot
Time Value
Back
Up
Release
Signal
30 90 User
Off
Delay
Norm
343
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
1672 Z2G-A_BLOCK X [29]Z3G-B X
1673 Z2G-B_BLOCK X [30]Z3G-C X
1674 Z2G-C_BLOCK X [28]Z3G-A X
1675
1676
1677
1678
1679
1680 TP-A_DELAY X [623]TP-A X 60 ms
1681 TP-B_DELAY X [624]TP-B X 60 ms
1682 TP-C_DELAY X [625]TP-C X 60 ms
1683 ARC_DISABLE
1684 ARC_SPAR
1685 ARC_TPAR
1686 ARC_S&T
1687 ARC_EXT1P
1688 ARC_EXT3P
1689
1690
1691
1692
1693
1694
1695
1696 Z1_INST_TP X 0 [712]Z1CNT_INST X
1697
1698 Z2_INST_TP
1699 Z3_INST_TP
1700 ZR1_INST_TP
1701 ZF_INST_TP
1702 EF_INST_TP
1703 OC_INST_TP
1704
1705 DEF_INST_TP
1706
1707
1708 ZR2_INST_TP
1709 ZND_INST_TP
1710
1711
1712 Z1_3PTP X 0 [713]Z1CNT_3PTP X
1713 Z1X_3PTP
1714 Z2_3PTP X 2 [1]CONSTANT_1 X
1715
1716 DEFCAR_3PTP X 2 [1]CONSTANT_1 X
1717 PSBTP_3PTP X 2 [1]CONSTANT_1 X
1718
1719
1720 CAR_3PTP
1721 DEFCAR_3PTP X 2 [1]CONSTANT_1 X
1722 PSBTP_3PTP X 2 [1]CONSTANT_1 X
1723
1724 TR1_3PTP
1725 TR2_3PTP
1726
1727 3P_TRIP
1728 CAR-A-R1 X [1088]COM1-R1 X
1729 CAR-B-R1 X [1089]COM2-R1 X
1730 CAR-C-R1 X [1090]COM3-R1 X
1731 CAR-S-R1 X [1091]COM4-R1 X
1732 DEFCAR-A-R1 X [1092]COM5-R1 X
1733 DEFCAR-B-R1 X [1093]COM6-R1 X
1734 DEFCAR-C-R1 X [1094]COM7-R1 X
1735
1736
1737
1738
1739
90 User
Off
Delay
Norm
None Signal Turn On
Delay
One
Shot
Time Value
Back
Up
Release
Signal
30
344
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
1740 PSBCAR-A-R1 X [1095]COM8-R1 X
1741 PSBCAR-B-R1 X [1095]COM8-R1 X
1742 PSBCAR-C-R1 X [1095]COM8-R1 X
1743
1744 TR1-A-R1 X [1096]COM9-R1 X
1745 TR1-B-R1 X [1096]COM9-R1 X
1746 TR1-C-R1 X [1096]COM9-R1 X
1747
1748 TR2-A-R1 X -- X
1749 TR2-B-R1 X -- X
1750 TR2-C-R1 X -- X
1751
1752
1753
1754
1755
1756
1757
1758
1759
1760 CAR-A-R2 X [1136]COM1-R2 X
1761 CAR-B-R2 X [1137]COM2-R2 X
1762 CAR-C-R2 X [1138]COM3-R2 X
1763 CAR-S-R2 X [1139]COM4-R2 X
1764 DEFCAR-A-R2 X [1140]COM5-R2 X
1765 DEFCAR-B-R2 X [1141]COM6-R2 X
1766 DEFCAR-C-R2 X [1142]COM7-R2 X
1767
1768
1769
1770
1771
1772 PSBCAR-A-R2 X [1143]COM8-R2 X
1773 PSBCAR-B-R2 X [1143]COM8-R2 X
1774 PSBCAR-C-R2 X [1143]COM8-R2 X
1775
1776 TR1-A-R2 X [1144]COM9-R2 X
1777 TR1-B-R2 X [1144]COM9-R2 X
1778 TR1-C-R2 X [1144]COM9-R2 X
1779
1780 TR2-A-R2 X -- X
1781 TR2-B-R2 X -- X
1782 TR2-C-R2 X -- X
1783
1784
1785
1786
1787
1788
1789
1790
1791
1792 IO#1-TP-A1 X [240]TRIP-A1 X
1793 IO#1-TP-B1 X [241]TRIP-B1 X
1794 IO#1-TP-C1 X [242]TRIP-C1 X
1795 IO#1-TP-A2 X [243]TRIP-A2 X
1796 IO#1-TP-B2 X [244]TRIP-B2 X
1797 IO#1-TP-C2 X [245]TRIP-C2 X
1798
1799
1800
1801
1802
1803
1804
1805
1806
1807
90 User
Off
Delay
Norm
None Signal Turn On
Delay
One
Shot
Time Value
Back
Up
Release
Signal
30
345
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
1808 OVS1_INST_TP
1809 OVS2_INST_TP
1810
1811
1812 OVG1_INST_TP
1813 OVG2_INST_TP
1814
1815
1816 UVS1_INST_TP
1817 UVS2_INST_TP
1818
1819
1820 UVG1_INST_TP
1821 UVG2_INST_TP
1822
1823
1824 SPR.L-REQ
1825 TPR.L-REQ
1826 SPR.F-REQ
1827 TPR.F-REQ
1828 SPR.F-ST.REQ
1829 TPR.F-ST.REQ
1830
1831
1832 R.F-ST.REQ
1833 SPR.F2-REQ
1834 TPR.F2-REQ
1835
1836
1837
1838 ARC.L_TERM
1839 ARC.F_TERM
1840
1841
1842
1843
1844
1845
1846
1847
1848 BCD_BLOCK
1849 DEFF_BLOCK
1850
1851 DEFR_BLOCK
1852
1853
1854
1855
1856 OVS1_BLOCK
1857 OVS2_BLOCK
1858
1859
1860 OVG1_BLOCK
1861 OVG2_BLOCK
1862
1863
1864 UVS1_BLOCK
1865 UVS2_BLOCK
1866
1867
1868 UVG1_BLOCK
1869 UVG2_BLOCK
1870
1871
1872
:
:
2010
None Signal Turn On
Delay
One
Shot
Time Value
Back
Up
Release
Signal
30 90 User
Off
Delay
Norm
346
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035
2036
2037
2038
2039
2040
2041
2042
2043
2044
2045
2046
2047
2048 COM1-S X [800]C/R_SEND-A X
2049 COM2-S X [801]C/R_SEND-B X
2050 COM3-S X [802]C/R_SEND-C X
2051 COM4-S X [803]C/R_SEND-S X
2052 COM5-S X [804]C/R_SEND-DEFA X
2053 COM6-S X [805]C/R_SEND-DEFB X
2054 COM7-S X [806]C/R_SEND-DEFC X
2055 COM8-S X [815]C/R_SEND-PSB X
2056 COM9-S X [516]BI4_COMMAND X
2057 COM10-S X -- X
2058 COM11-S
2059 COM12-S
2060 COM13-S
2061 COM14-S
2062
2063
2064 SUB_COM1-S
2065 SUB_COM2-S
2066 SUB_COM3-S X [848]LOCAL_TEST X
2067 SUB_COM4-S X [881]SEVERE_CF-L X
2068
2069
2070
2071
2072
2073
2074
2075
:
:
2600
90 User
Off
Delay
Norm
None Signal Turn On
Delay
One
Shot
Time Value
Back
Up
Release
Signal
30
347
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
2601
2602
2603
2604
2605
2606
2607
2608
2609
2610 ALARM_LED_SET X [909]CFSV1-R + [925]CFSV2-R X
2611
2612
2613
2614
2615
2616
2617
2618
2619
2620
2621
2622
2623
2624 F.RECORD1
2625 F.RECORD2
2626 F.RECORD3
2627 F.RECORD4
2628
2629
2630
2631
2632 D.RECORD1
2633 D.RECORD2
2634 D.RECORD3
2635 D.RECORD4
2636
2637
2638
2639
2640 SET.GROUP1
2641 SET.GROUP2
2642 SET.GROUP3
2643 SET.GROUP4
2644 SET.GROUP5
2645 SET.GROUP6
2646 SET.GROUP7
2647 SET.GROUP8
2648
2649
2650
2651
2652
2653
2654
2655
2656 CON_TPMD1
2657 CON_TPMD2
2658 CON_TPMD3
2659 CON_TPMD4
2660 CON_TPMD5
2661 CON_TPMD6
2662 CON_TPMD7
2663 CON_TPMD8
2664
2665
:
:
2815
None Signal Turn
30 90 User Norm
One
Shot
Time Value
Back
Up
Release
Signal
Off
Delay
On
Delay
348
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
2816 TEMP001 X -- X
2817 TEMP002 X -- X
2818 TEMP003 X -- X
2819 TEMP004
2820 TEMP005
2821 TEMP006
2822 TEMP007
2823 TEMP008
2824 TEMP009
2825 TEMP010
2826 TEMP011
2827 TEMP012
2828 TEMP013
2829 TEMP014
2830 TEMP015
2831 TEMP016
2832 TEMP017
2833 TEMP018
2834 TEMP019
2835 TEMP020
2836 TEMP021
2837 TEMP022
2838 TEMP023
2839 TEMP024
2840 TEMP025
2841 TEMP026
2842 TEMP027
2843 TEMP028
2844 TEMP029
2845 TEMP030
2846 TEMP031
2847 TEMP032
2848 TEMP033
2849 TEMP034
2850 TEMP035
2851 TEMP036
2852 TEMP037
2853 TEMP038
2854 TEMP039
2855 TEMP040
2856 TEMP041
2857 TEMP042
2858 TEMP043
2859 TEMP044
2860 TEMP045
2861 TEMP046
2862 TEMP047
2863 TEMP048
2864 TEMP049
2865 TEMP050
2866 TEMP051
2867 TEMP052
2868 TEMP053
2869 TEMP054
2870 TEMP055
2871 TEMP056
2872 TEMP057
2873 TEMP058
2874 TEMP059
2875 TEMP060
2876 TEMP061
2877 TEMP062
2878 TEMP063
2879 TEMP064
2880 TEMP065
2881 TEMP066
2882 TEMP067
2883 TEMP068
Back
Up
Release
Signal
Off
Delay
On
Delay
None Signal Turn
30 90 User Norm
One
Shot
Time Value
349
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
2884 TEMP069
2885 TEMP070
2886 TEMP071
2887 TEMP072
2888 TEMP073
2889 TEMP074
2890 TEMP075
2891 TEMP076
2892 TEMP077
2893 TEMP078
2894 TEMP079
2895 TEMP080
2896 TEMP081
2897 TEMP082
2898 TEMP083
2899 TEMP084
2900 TEMP085
2901 TEMP086
2902 TEMP087
2903 TEMP088
2904 TEMP089
2905 TEMP090
2906 TEMP091
2907 TEMP092
2908 TEMP093
2909 TEMP094
2910 TEMP095
2911 TEMP096
2912 TEMP097
2913 TEMP098
2914 TEMP099
2915 TEMP100
2916 TEMP101
2917 TEMP102
2918 TEMP103
2919 TEMP104
2920 TEMP105
2921 TEMP106
2922 TEMP107
2923 TEMP108
2924 TEMP109
2925 TEMP110
2926 TEMP111
2927 TEMP112
2928 TEMP113
2929 TEMP114
2930 TEMP115
2931 TEMP116
2932 TEMP117
2933 TEMP118
2934 TEMP119
2935 TEMP120
2936 TEMP121
2937 TEMP122
2938 TEMP123
2939 TEMP124
2940 TEMP125
2941 TEMP126
2942 TEMP127
2943 TEMP128
2944 TEMP129
2945 TEMP130
2946 TEMP131
2947 TEMP132
2948 TEMP133
2949 TEMP134
2950 TEMP135
2951 TEMP136
Back
Up
Release
Signal
Off
Delay
On
Delay
None Signal Turn
30 90 User Norm
One
Shot
Time Value
350
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
2952 TEMP137
2953 TEMP138
2954 TEMP139
2955 TEMP140
2956 TEMP141
2957 TEMP142
2958 TEMP143
2959 TEMP144
2960 TEMP145
2961 TEMP146
2962 TEMP147
2963 TEMP148
2964 TEMP149
2965 TEMP150
2966 TEMP151
2967 TEMP152
2968 TEMP153
2969 TEMP154
2970 TEMP155
2971 TEMP156
2972 TEMP157
2973 TEMP158
2974 TEMP159
2975 TEMP160
2976 TEMP161
2977 TEMP162
2978 TEMP163
2979 TEMP164
2980 TEMP165
2981 TEMP166
2982 TEMP167
2983 TEMP168
2984 TEMP169
2985 TEMP170
2986 TEMP171
2987 TEMP172
2988 TEMP173
2989 TEMP174
2990 TEMP175
2991 TEMP176
2992 TEMP177
2993 TEMP178
2994 TEMP179
2995 TEMP180
2996 TEMP181
2997 TEMP182
2998 TEMP183
2999 TEMP184
3000 TEMP185
3001 TEMP186
3002 TEMP187
3003 TEMP188
3004 TEMP189
3005 TEMP190
3006 TEMP191
3007 TEMP192
3008 TEMP193
3009 TEMP194
3010 TEMP195
3011 TEMP196
3012 TEMP197
3013 TEMP198
3014 TEMP199
3015 TEMP200
3016 TEMP201
3017 TEMP202
3018 TEMP203
3019 TEMP204
Back
Up
Release
Signal
Off
Delay
On
Delay
None Signal Turn
30 90 User Norm
One
Shot
Time Value
351
6 F 2 S 0 8 5 1
PLC default setting
Output Timing Logic expression Delay Time / Flip Flop
Cycle Relay model Flip Flop Timer
201, 301, 303
Filename: GRZ100-
3020 TEMP205
3021 TEMP206
3022 TEMP207
3023 TEMP208
3024 TEMP209
3025 TEMP210
3026 TEMP211
3027 TEMP212
3028 TEMP213
3029 TEMP214
3030 TEMP215
3031 TEMP216
3032 TEMP217
3033 TEMP218
3034 TEMP219
3035 TEMP220
3036 TEMP221
3037 TEMP222
3038 TEMP223
3039 TEMP224
3040 TEMP225
3041 TEMP226
3042 TEMP227
3043 TEMP228
3044 TEMP229
3045 TEMP230
3046 TEMP231
3047 TEMP232
3048 TEMP233
3049 TEMP234
3050 TEMP235
3051 TEMP236
3052 TEMP237
3053 TEMP238
3054 TEMP239
3055 TEMP240
3056 TEMP241
3057 TEMP242
3058 TEMP243
3059 TEMP244
3060 TEMP245
3061 TEMP246
3062 TEMP247
3063 TEMP248
3064 TEMP249
3065 TEMP250
3066 TEMP251
3067 TEMP252
3068 TEMP253
3069 TEMP254
3070 TEMP255
3071 TEMP256
Back
Up
Release
Signal
Off
Delay
On
Delay
None Signal Turn
30 90 User Norm
One
Shot
Time Value
352
6 F 2 S 0 8 5 1
353
6 F 2 S 0 8 5 1
Appendix I
Commissioning Test Sheet (sample)
1. Relay identification
2. Preliminary check
3. Hardware check
3.1 User interface check
3.2 Binary input/Binary output circuit check
3.3 AC input circuit check
4. Function test
4.1 Phase fault element ZS test
4.2 Earth fault element ZG test
4.3 Out-of-step element OST test
4.4 Phase selection element UVC test
4.5 Directional earth fault element DEF test
4.6 Negative sequence directional element DOCN test
4.7 Inverse definite minimum time overcurrent element
(IDMT) EFI and OCI test
4.8 Voltage and synchronism check elements test
4.9 Thermal overload element
4.10 Current change detection element
4.11 Level detectors test
4.12 BCD element check
4.13 Overvoltage and undervoltage elements test
5. Protection scheme test
6. Metering and recording check
7. Conjunctive test
354
6 F 2 S 0 8 5 1
1. Relay identification
Type Serial number
Model System frequency
Station Date
Circuit Engineer
Protection scheme Witness
Active settings group number
2. Preliminary check
Ratings
CT shorting contacts
DC power supply
Power up
Wiring
Relay inoperative
alarm contact
Calendar and clock
3. Hardware check
3.1 User interface check
3.2 Binary input/Binary output circuit check
Binary input circuit
Binary output circuit
3.3 AC input circuit
355
6 F 2 S 0 8 5 1
4. Function test
4.1 Phase fault element ZS test
Element Reach setting (ZS) IT 2IT ZS Measured voltage (2V
a
)
Z1S
Z1XS
Z2S
Z3S
ZFS
Z4S
ZR1S
ZR2S
ZNDS
PSBIN
PSBOUT
4.2 Earth fault element ZG test
Element Reach setting (ZG) IT 2IT ZG Measured voltage (2V
a
)
Z1G
Z1XG
Z2G
Z3G
ZFG
Z4G
ZR1G
ZR2G
ZNDG
PSBIN
PSBOUT
4.3 Out-of-step element OST test
Element Reach setting (Z
OST
) IT 2IT Z
OST
Measured voltage (2V
a
)
OSTXF
OSTXB
OSTR1
OSTR2
4.4 Phase selection element UVC test
Element Reach setting (UVCZ) IT IT UVCZ + UVCV Measured voltage
UVC 0 0
356
6 F 2 S 0 8 5 1
4.5 Directional earth fault element DEF test
(1)
Element Current setting Measured current
DEFF
DEFR
(2)
Element Voltage setting Measured voltage
DEFF
DEFR
4.6 Negative sequence directional element DOCN test
Element Test current Measured voltage
DOCNF I
N
DOCNR I
N
4.7 Inverse definite minimum time overcurrent element (IDMT) EFI and OCI test
Element Test current Measured operating time
EFI 1.2 I
s
20 I
s
OCI 1.2 I
s
20 I
s
4.8 Voltage and synchronism check elements test
(1) Voltage check element
Element Setting Measured voltage
OVB
UVB
OVL1
UVL1
OVL2
UVL2
(2) Synchronism check element
Voltage check
Element Setting Measured voltage
SYN1 (SY1UV)
SYN1 (SY1OV)
SYN2 (SY2UV)
SYN2 (SY2OV)
357
6 F 2 S 0 8 5 1
Phase angle check
Element Setting Measured angle
SYN1 (SY1)
SYN2 (SY2)
4.9 Thermal overload element test
Element Test current Measured operating time
THM-A 1.2 I
s
THM-T 10 I
s
4.10 Current change detection element
Element Test current Result
OCD 1.2 Fixed setting
OCDP 1.2 Setting value
4.11 Level detectors test
Element Setting Measured value
OCH
EF
EFL
OC
OVG
UVLS
UVLG
UVFS
UVFG
OCBF
4.12 BCD element check
4.13 Overvoltage and undervoltage elements test
(1) Operating value test
Element Voltage
setting
Measured
voltage
Element Voltage
setting
Measured
voltage
OVS1 OVG1
OVS2 OVG2
UVS1 UVG1
UVS2 UVG2
358
6 F 2 S 0 8 5 1
(2) Operating time test (IDMT)
Element Voltage setting Multiplier setting Changed voltage Measured time
OVS1 10.0 1.5 Voltage setting
OVG1 10.0 1.5 Voltage setting
UVS1 10.0 0.5 Voltage setting
UVG1 10.0 0.5 Voltage setting
5. Protection scheme test
Scheme Results
6. Metering and recording check
7. Conjunctive test
Scheme Results
On load check
Signaling circuit
Tripping circuit
Reclosing circuit
359
6 F 2 S 0 8 5 1
Appendix J
Return Repair Form
360
6 F 2 S 0 8 5 1
RETURN / REPAIR FORM
Please complete this form up and return it to TOSHIBA CORPORATION with the GRZ100 to be
repaired.
TOSHIBA CORPORATION Fuchu Complex
1, Toshiba-cho, Fuchu-shi, Tokyo, Japan
For: Power Systems Protection & Control Department
Quality Assurance Section
Type: GRZ100 Model:
(Example: Type: GRZ100 Model: 201D-30-A0 )
Product No.:
Serial No. :
Date:
1. Why the relay is being returned ?
mal-operation
does not operate
increased error
investigation
others
2. Fault records, event records or disturbance records stored in the relay and relay settings are very
helpful information to investigate the incident.
Please inform us of this information in respect to in the incident on a Floppy Disk, or by
completing the Fault Record sheet and Relay Setting sheet attached.
361
6 F 2 S 0 8 5 1
Fault Record
Date/Month/Year Time / / / : : .
(Example: 04/ Nov./ 1997 15:09:58.442)
Faulty phase:
Fault Locator : km ( %)
Prefault values (CT ratio: kA/: A, VT ratio: kV/: V)
V
a
: kV or V I
a
: kA or A
V
b
: kV or V I
b
: kA or A
V
c
: kV or V I
c
: kA or A
V
ab
: kV or V I
ab
: kA or A
V
bc
: kV or V I
bc
: kA or A
V
ca
: kV or V I
ca
: kA or A
V
1
: kV or V I
1
: kA or A
V
2
: kV or V I
2
: kA or A
V
0
: kV or V I
0
: kA or A
I
0a
: kA or A
Fault values
V
a
: kV or V I
a
: kA or A
V
b
: kV or V I
b
: kA or A
V
c
: kV or V I
c
: kA or A
V
ab
: kV or V I
ab
: kA or A
V
bc
: kV or V I
bc
: kA or A
V
ca
: kV or V I
ca
: kA or A
V
1
: kV or V I
1
: kA or A
V
2
: kV or V I
2
: kA or A
V
0
: kV or V I
0
: kA or A
I
0a
: kA or A
R
a
: X
a
:
R
b
: X
b
:
R
c
: X
c
:
R
ab
: X
ab
:
R
bc
: X
bc
:
R
ca
: X
ca
:
362
6 F 2 S 0 8 5 1
3. What was the message on the LCD display at the time of the incident.
4. Please write the detail of the incident.
5. Date of the incident occurred.
Day/ Month/ Year: / / /
(Example: 10/ July/ 1998)
6. Please write any comments on the GRZ100, including the document.
363
6 F 2 S 0 8 5 1
Customer
Name:
Company Name:
Address:
Telephone No.:
Facsimile No.:
Signature:
364
6 F 2 S 0 8 5 1
365
6 F 2 S 0 8 5 1
Appendix K
Technical Data
366
6 F 2 S 0 8 5 1
Ratings
AC current I
n
: 1A or 5A
AC voltage V
n
: 100V, 110V, 115V, 120V
Frequency: 50Hz or 60Hz
DC power supply: 110Vdc/125Vdc (Operative range: 88 - 150Vdc)
220Vdc/250Vdc (Operative range: 176 - 300Vdc)
48Vdc/54Vdc/60Vdc (Operative range: 38.4 to 72Vdc)
24Vdc/30Vdc (Operative range: 19.2 to 36Vdc)
AC ripple on DC supply IEC60255-11 maximum 12%
DC supply interruption IEC60255-11
Permissive duration of DC supply voltage
interruption to maintain normal operation:
Restart time:
less than 50ms at 110V
less than 10s
Binary input circuit DC voltage 110Vdc/125Vdc
220Vdc/250Vdc
48Vdc/54Vdc/60Vdc
24Vdc/30Vdc
Overload Ratings
AC current input
AC voltage input
4 times rated continuous
100 times rated for 1s
2 times rated continuous
2.5 times rated for 1s
Burden
AC current input 0.2VA per phase (at rated 5A)
0.4 VA at zero-sequence circuit (at rated 5A)
0.1VA per phase (at rated 1A)
0.3 VA at zero-sequence circuit (at rated 1A)
AC voltage input 0.1VA (at rated voltage)
DC power supply: less than15W (quiescent)
less than 25W (operation)
Binary input circuit: 0.5W/input at 110Vdc
CT Ratio Setting
CT ratio 1 to 20000 in 1 steps
Full Scale of Current for Measurement
Current 65 times rated current
Phase Fault Distance Measuring Element
Z1S, Z2S and Z1XS
Z1S 1
Z1S 2
ZFS, ZR1S and ZR2S
Z3S and Z4S
Characteristic angle
Z1S, ZR1S, ZR2S and Z4S offset
ZNDS
Blinder (BFR1S, BFR2S, BFRS, BRRS, BNDS)
BRLS: Linked with BRRS
Characteristic angle (BFR1S, BFR2S, BFRS, BRRS,
BNDS)
Characteristic angle (BFLS)
0.10 to 250.00 in 0.01 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0 to 45 in 1 steps
45 to 90 in 1 steps
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
45 to 90 in 1 steps
7.5 fixed (1A relay)
1.5 fixed (5A relay)
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0.5 to 100.0 in 0.1 steps (1A relay)
0.10 to 20.00 in 0.01 steps (5A relay)
75 fixed
90 to 135
367
6 F 2 S 0 8 5 1
Earth Fault Distance Measuring Element
Z1G, Z2G and Z1XG
Z1G 1
Z1G 2
ZR1G
ZFG, Z3G, ZR2G and Z4G
Characteristic angle
ZNDG
Blinder (BFR1G, BFR2G, BFRG, BRRG, BNDG)
BRLG: Linked with BRRG
Characteristic angle (BFR1G, BFR2G, BFRG, BRRG,
BNDG)
Characteristic angle (BFLG)
0.10 to 250.00 in 0.01 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0 to 45 in 1 steps
45 to 90 in 1 steps
0.1 to 250.0 in 0.1 steps (1A relay)
0.01 to 50.00 in 0.01 steps (5A relay)
0.1 to 500.0 in 0.1 steps (1A relay)
0.01 to 100.00 in 0.01 steps (5A relay)
45 to 90 in 1 steps
0.1 to 500.0 in 0.1 steps (1A relay)
0.01 to 100.00 in 0.01 steps (5A relay)
0.5 to 100.0 in 0.1 steps (1A relay)
0.10 to 20.00 in 0.01 steps (5A relay)
75 fixed
90 to 135
Time Setting for Zone Protection
Time setting of Z1S, Z2S, Z3S, ZFS, ZR1S, ZR2S, ZNDS,
Z1G, Z2G, Z3G, ZFG, ZR1G, ZR2G, ZNDG
0.00 to 10.00s in 0.01s steps
Command Protection
Coordination time for BOP scheme 0 to 50ms in 1ms steps
Operating and Resetting Time of Distance Measuring Element
Typical operating time
Operating time curve (SIR curve)
Resetting time
20ms
Refer to Figure K-1.
less than 30ms (for tripping output)
less than 40ms (for signal output)
Accuracy of Distance Measuring Element
Static accuracy
Static angle accuracy
Transient overreach
5% under SIR < 30, 10% under 30 < SIR < 50
5
+5%
Minimum Operating Current
Current
0.08A (1A relay)
0.4A (1A relay)
Residual Current Compensation
Residual current compensation for reactance element of
Z1G, Z1XG, Z2G, ZR1G
Earth return compensation
Mutual coupling compensation (ZR1G excluded)
Adjustable as follows:
0 to 1000% in 1% steps
0 to 1000% in 1% steps
Phase Selection Element
Undervoltage
Impedance
Characteristic angle
Residual current compensation
10 to 60V in 1V steps
0.0 to 250.0 in 1 steps (1A relay)
0.0 to 50.0 in 1 steps (5A relay)
45 to 90 in 1 steps
Automatically set according to residual current
compensation setting of reactance element
Switch-on-to-fault and Stub protection
Overcurrent 0.4 to 3.0A in 0.1A steps (1A relay)
2.0 to 15.0A in 0.1A steps (5A relay)
368
6 F 2 S 0 8 5 1
Broken Conductor Detection
Broken conductor threshold (I
2
/I
1
):
DTL delay:
OFF, 0.10 to 1.00 in 0.01 steps
0.00 to 300.00s in 0.01s steps
Voltage Transformer Failure Supervision
Undervoltage element (phase-to-phase)
Undervoltage element (phase-to-earth)
Current change detection element
Residual voltage element
Residual current element
50 to 100V in 1V steps
10 to 60V in 1V steps
0.1A fixed (1A relay)
0.5A fixed (5A relay)
20V fixed
Common use with earth fault detection element
Power Swing Blocking
Detection zone (PSBZS, PSBZG)
Current change detection element
Detection time
Resetting time
2.5 to 75.0 in 0.1 steps (1A relay)
0.50 to 15.00 in 0.01 steps (5A relay)
0.1 to 2.0A in 0.1A steps (1A relay)
0.5 to 10.0A in 0.1A steps (5A relay)
30 to 60ms in 1ms steps
500ms fixed
Out-of-step Protection
Resistive reach (OSTR1)
Resistive reach (OSTR2)
Resistive reach (OSTXF)
Resistive reach (OSTXF)
Detection time (TOST)
15 to 150 in 1 steps (1A relay)
3.0 to 30.0 in 0.1 steps (5A relay)
5 to 50 in 1 steps (1A relay)
1.0 to 10.0 in 0.1 steps (5A relay)
5 to 250 in 1 steps (1A relay)
1.0 to 50.0 in 0.1 steps (5A relay)
1 to 50 in 1 steps (1A relay)
0.2 to 10.0 in 0.1 steps (5A relay)
0.01 to 1.00s in 0.01s steps
Breaker Failure (BF) Protection
Overcurrent element
BF timer for retry-trip of failed breaker
BF timer for related breaker trip
Operating time of overcurrent element
Resetting time of overcurrent element
0.1 to 2.0A in 0.1A steps (1A relay)
0.5 to 10.0A in 0.1A steps (5A relay)
50 to 500ms in 1ms steps
50 to 500ms in 1ms steps
less than 20ms at 50Hz or less than 17ms at 60Hz
less than 15ms at 50Hz or less than 13ms at 60Hz
Inverse Time Overcurrent Protection
Overcurrent
Time multiplier
Characteristic
Accuracy of inverse time characteristics
Reset definite time
0.10 to 5.00A in 0.01A steps (1A relay)
0.5 to 25.0A in 0.1A steps (5A relay)
0.05 to 1.00 in 0.01 steps
Refer to Figure 8.
Standard, Very and Long-time: IEC60255-3 class 5
Extremely inverse: IEC60255-3 class 7.5
0.0 to 10.0s in 0.1s steps
Definite Time Overcurrent Protection
Overcurrent
Time for delayed trip
Operating time of overcurrent element
Accuracy of pick-up value
0.1 to 20.0A in 0.1A steps (1A relay)
0.5 to 100.0A in 0.1A steps (5A relay)
0.00 to 10.00s in 0.01s steps
less than 20ms
5%
369
6 F 2 S 0 8 5 1
Directional Earth Fault Protection
Characteristic angle
Polarising voltage (3V0)
Zero-sequence current (3I0)
Definite time delay for backup trip
Accuracy of pick-up value
0 to 90 in 1 steps (3I0 lags for 3V0)
1.7 to 21.0V in 0.1V steps
0.10 to 1.00A in 0.01A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
0.00 to 10.00s in 0.01s steps
5%
Directional Earth Fault Command Protection
Time for delayed trip
Coordination time
0.00 to 0.30s in 0.01s steps
0 to 50ms in 1ms steps
Inverse Time Earth Fault Protection (*)
Earth fault
Time multiplier
Characteristic
Accuracy of inverse time characteristics
Reset definite time
(*) Directional control is available.
0.10 to 1.00A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
0.05 to 1.00 in 0.01 steps
Refer to Figure 8.
Standard, Very and Long-time: IEC60255-3 class 5
Extremely inverse: IEC60255-3 class 7.5
0.0 to 10.0s in 0.1s steps
Definite Time Earth Fault Protection
Earth fault
Time for delayed trip
Accuracy of pick-up value
0.10 to 1.00A in 0.01A steps (1A relay)
0.5 to 5.0A in 0.1A steps (5A relay)
0.00 to 10.00s in 0.01s steps
5%
Weak Infeed and Echo Protection
Phase-to-phase undervoltage element
Phase-to-earth undervoltage element
50 to 100V in 1V steps
10 to 60V in 1V steps
Thermal overload Protection
Thermal setting (THM = k.I
FLC
)
Time constant ()
Thermal alarm
Pre-load current setting
OFF, 0.40 2.00A in 0.01A steps (1A rating)
OFF, 2.0 10.0A in 0.1A steps (5A rating)
0.5 300.0mins in 0.1min steps
OFF, 50% to 99% in 1% steps
0.00 1.00A in 0.01A steps (1A rating)
0.0 5.0A in 0.1A steps (5A rating)
Overvoltage Protection
1
st
, 2
nd
Overvoltage thresholds:
Delay type:
IDMTL Time Multiplier Setting TMS:
DTL delay:
DO/PU ratio
Reset Delay (1
st
threshold only):
OFF, 5.0 150.0V in 0.1V steps (for both
phase-to-phase and phase-to-neutral voltage)
DTL, IDMTL(1
st
threshold only)
0.05 100.00 in 0.01 steps
0.00 300.00s in 0.01s steps
10 98% in 1% steps
0.0 300.0s in 0.1s steps
Undervoltage Protection
1
st
, 2
nd
Undervoltage thresholds:
Delay type:
IDMTL Time Multiplier Setting TMS:
DTL delay:
DO/PU ratio
Reset Delay (1
st
threshold only):
OFF, 5.0 150.0V in 0.1V steps (for both
phase-to-phase and phase-to-neutral voltage)
DTL, IDMTL(1
st
threshold only)
0.05 100.00 in 0.01 steps
0.00 300.00s in 0.01s steps
10 98% in 1% steps
0.0 300.0s in 0.1s steps
370
6 F 2 S 0 8 5 1
Autoreclose Function
Number of shots
Timer settings
Dead time for single-phase autoreclose
Dead time for three-phase autoreclose
Multi-shot dead line time
Multi-shot reset time
Reclaim time
Pulse width of reclosing signal output
Autoreclose reset time
Reset time for developing fault
One-and-a-half breaker scheme
Follower breaker autoreclose delay time
Voltage and synchronism check element
Synchronism check angle
UV element
OV element
Busbar or line dead check
Busbar or line live check
Synchronism check time
Voltage check time
Operating time of synchronism check element
Operating time of UV and OV elements
1 to 4 shots
0.01 to 10.00s in 0.01s steps
0.01 to 100.00s in 0.01s steps
5.0 to 300.0s in 0.1s steps
5.0 to 300.0s in 0.1s steps
5 to 300s in 1s steps
0.1 to 10.0s in 0.1s steps
0.01 to 100.00s in 0.01s steps
0.01 to 10.00s in 0.01s steps
0.1 to 10.0s in 0.1s steps
5 to 75 in 1 steps
10 to 150V in 1V steps
10 to 150V in 1V steps
10 to 150V in 1V steps
10 to 150V in 1V steps
0.01 to 10.00s in 0.01s steps
0.01 to 1.00s in 0.01s steps
less than 50ms
less than 40ms
Fault Locator
Line reactance and resistance setting
Line length
Correction factor of impedance between lines
Correction factor of impedance between in each phase
Accuracy
Minimum measuring cycles
0.0 to 999.9 in 0.1 steps (1A relay)
0.00 to 199.99 in 0.01 steps (5A relay)
0.0 to 399.9km in 0.1km steps
80 to 120% in 1% steps
80 to 120% in 1% steps
2.5km (up to 100km)
2.5% (up to 399.9km)
2.5 cycles
Disturbance Record Initiation
Overcurrent element
Undervoltage element
Pre-fault time
Post-fault time
0.1 to 50.0A in 0.1A steps (1A relay)
0.5 to 250.0A in 0.1A steps (5A relay)
0 to 132V in 1V steps (for phase fault)
0 to 76V in 1V steps (for earth fault)
0.3s fixed
0.1 to 3.0s in 0.1s steps
371
6 F 2 S 0 8 5 1
Communication Port
Front communication port (local PC)
Connection
Cable type
Cable length
Connector
Point to point
Multi-core (straight)
15m (max.)
RS232C 9-pin D-subminiature connector female
Rear communication port (remote PC)
RS485 I/F:
Transmission data rate for RSM system
Connection
Connector
Cable and length
Isolation
64kbps
Multidrop mode (max. 32 relays)
Screw terminals
Twisted pair cable, max. 1200m
2kVac for 1min.
Fibre optic I/F:
ST connector, graded-index multi-mode 50/125m or
62.5/125m type optical fibres
Ethernet LAN I/F: 100BASE-TX: RJ-45 connector
100BASE-FX: SC connector
IRIG-B Port
IRIG Time Code
Input impedance
Input voltage range
Connector type
Cable type
IRIG-B122
4k-ohm
4Vp-p to 10Vp-p
BNC connector
50 ohm coaxial cable
Binary Inputs
Operating voltage Typical 74Vdc(min.70Vdc) for 110V/125Vdc rating
Typical 138Vdc(min.125Vdc) for 220V/250Vdc rating
Contact Ratings
Trip contacts
Make and carry
Break
Auxiliary contacts
Make and carry
Break
Durability
Make and carry
Break
5A continuously,
30A, 290Vdc for 0.5s (L/R=10ms)
0.15A, 290Vdc (L/R=40ms)
4A continuously,
10A, 220Vdc for 0.5s (L/R 5ms)
0.1A, 220Vdc (L/R=40ms)
10,000 operations minimum
100,000 operations minimum
Mechanical design
Weight
Case colour
Installation
10kg (Type-A), 13kg (Type-B)
10YR8/1
Flush mounting or rack mounting
372
6 F 2 S 0 8 5 1
Note: In the case of a 60Hz relay the operate time is reduced by approximately 15% to 20%.
Figure K-1
a) Minimum operating time (50Hz) b) Maximum operating time (50Hz)
Phase to phase fault
a) Minimum operating time (50Hz) b) Maximum operating time (50Hz)
Phase to earth fault
373
6 F 2 S 0 8 5 1
CT Requirement
The requirement for minimum CT knee-point voltage for GRZ100 is assessed for the following
three cases separately:
a) Stability for faults beyond the zone 1 reach point:
V
k
> k
1
I
f_z1_max
(R
ct
+ R
2
)
b) Stability for close-up reverse faults:
V
k
> k
2
I
f_rev_max
(R
ct
+ R
2
)
c) Dependability of tripping for close-up forward faults:
V
k
> k
3
I
f_max
(R
ct
+ R
2
)
where,
V
k
: Knee point voltage.
I
f_z1_max
: Maximum fault current at the zone 1 reach point.
I
f_rev_max
: Maximum close-up reverse fault current.
I
f_max
: Maximum close-up forward fault current.
R
ct
: Resistance of CT.
R
2
: Burden including connecting leads.
k
1
, k
2
, k
3
: Transient dimensioning factor
(All values refer to the CT secondary side)
The minimum requirement for V
k
is determined for each of the three cases and the highest of the
three results is used to dimension the CT. k
1
, k
2
and k
3
are chosen depending on the primary
system time constant as follows:
Transient dimensioning factor, k
a) Stability for faults
beyond the zone 1
reach point (I
f_z1_max
)
b) Stability for
close-up reverse
faults (I
f_rev_max
)
c) Dependability of
tripping for close-up
forward faults (I
f_max
)
Primary system
time constant,
Td (ms)
k
1
k
2
k
3
< 35 6 2 2
< 50 7 3 2
< 75 8 6 2
< 100 8 6 2
< 150 8 6 2
Notes:
1. Knee-point voltage, V
k
, is defined according to IEC 60044-1 as the minimum sinusoidal
e.m.f. (r.m.s.) at rated power frequency when applied to the secondary terminals of the
transformer, all other terminals being open circuited, which when increased by 10%, causes
the r.m.s. exciting current to increase by no more than 50%.
2. In cases where CTs are specified as P-class protective current transformers according to IEC
60044-1 (e.g. 5P10, 5P20 etc.), the knee point voltage can be approximated as follows:
V
k
0.8 n I
n
(R
ct
+ R
VA
)
where,
374
6 F 2 S 0 8 5 1
V
k
: Knee point voltage.
I
n
: Rated secondary current.
R
ct
: Resistance of CT.
R
VA
: Rated burden.
n: Accuracy limiting factor of CT (e.g. 20 for 5P20)
(All values refer to the CT secondary side)
3. Remanent flux has not been considered. In cases where a high level of remanent flux may be
experienced, it may be necessary to include an additional margin when dimensioning the CT.
4. The data provided is valid for 50Hz and 60Hz power systems.
375
6 F 2 S 0 8 5 1
ENVIRONMENTAL PERFORMANCE CLAIMS
Test Standards Details
Atmospheric Environment
Temperature IEC60068-2-1/2 Operating range: -10C to +55C.
Storage / Transit: -25C to +70C.
Humidity IEC60068-2-78 56 days at 40C and 93% relative humidity.
Enclosure Protection IEC60529 IP51 (Rear: IP20)
Mechanical Environment
Vibration IEC60255-21-1 Response - Class 1
Endurance - Class 1
Shock and Bump IEC60255-21-2 Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC60255-21-3 Class 1
Electrical Environment
Dielectric Withstand IEC60255-5 2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
High Voltage Impulse IEC60255-5 Three positive and three negative impulses of 5kV(peak),
1.2/50s, 0.5J between all terminals and between all terminals
and earth.
Electromagnetic Environment
High Frequency Disturbance
/ Damped Oscillatory Wave
IEC60255-22-1 Class 3,
IEC61000-4-12 / EN61000-4-12
1MHz 2.5kV applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
Electrostatic Discharge IEC60255-22-2 Class 3,
IEC61000-4-2 / EN61000-4-2
6kV contact discharge, 8kV air discharge.
Radiated RF Electromagnetic
Disturbance
IEC60255-22-3 Class 3,
IEC61000-4-3 / EN61000-4-3
Field strength 10V/m for frequency sweeps of 80MHz to 1GHz
and 1.7GHz to 2.2GHz. Additional spot tests at 80, 160, 450,
900 and 1890MHz.
Fast Transient Disturbance IEC60255-22-4, IEC61000-4-4 /
EN61000-4-4
4kV, 2.5kHz, 5/50ns applied to all inputs.
Surge Immunity IEC60255-22-5,
IEC61000-4-5 / EN61000-4-5
1.2/50s surge in common/differential modes:
HV ports: 2kV/1kV (peak)
PSU and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted RF
Electromagnetic Disturbance
IEC60255-22-6 Class 3,
IEC61000-4-6 / EN61000-4-6
10Vrms applied over frequency range 150kHz to 100MHz.
Additional spot tests at 27 and 68MHz.
Power Frequency
Disturbance
IEC60255-22-7, IEC61000-4-16 /
EN61000-4-16
300V 50Hz for 10s applied to ports in common mode.
150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Conducted and Radiated
Emissions
IEC60255-25,
EN55022 Class A,
IEC61000-6-4 / EN61000-6-4
Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 30m):
30 to 230MHz: <30dB
230 to 1000MHz: <37dB
89/336/EEC Compliance with the European Commission Electromagnetic
Compatibility Directive is demonstrated according to EN
61000-6-2 and EN 61000-6-4.
73/23/EEC Compliance with the European Commission Low Voltage
Directive is demonstrated according to EN 50178 and EN
60255-5.
376
6 F 2 S 0 8 5 1
377
6 F 2 S 0 8 5 1
Appendix L
Symbols Used in Scheme Logic
378
6 F 2 S 0 8 5 1
Symbols used in the scheme logic and their meanings are as follows:
Signal names
Marked with : Measuring element output signal
Marked with : Signal number
Marked with : Signal number and name of binary input by PLC function
Signal No. Signal name
Marked with [ ] : Scheme switch
Marked with " " : Scheme switch position
Unmarked : Internal scheme logic signal
AND gates
A B C Output
1 1 1 1
Other cases 0
A B C Output
1 1 0 1
Other cases 0
A B C Output
1 0 0 1
Other cases 0
OR gates
A B C Output
0 0 0 0
Other cases 1
A B C Output
0 0 1 0
Other cases 1
A B C Output
0 1 1 0
Other cases 1
A
Output
B &
C
A
Output
B 1
C
A
Output
B &
C
A
Output
B
C
A
Output
B 1
C
A
Output
B 1
C
&
379
6 F 2 S 0 8 5 1
Signal inversion
A Output
0 1
1 0
Timer
Delaye pick-up timer with fixed setting
XXX: Set time
Delayed drop-off timer with fixed setting
XXX: Set time
Delaye pick-up timer with variable setting
XXX - YYY: Setting range
Delayed drop-off timer with variable setting
XXX - YYY: Setting range
One-shot timer
XXX - YYY: Setting range
Flip-flop
S R Output
0 0 No change
1 0 1
0 1 0
1 1 0
Scheme switch
A Switch Output
1 ON 1
Other cases 0
Switch Output
ON 1
OFF 0
0
t
XXX
t
0
XXX
0
t
XXX - YYY
XXX - YYY
t
0
Output
Output
ON
ON
+
A
S
Output F/F
R
Output
A 1
XXX - YYY
A Output
A
Output
380
6 F 2 S 0 8 5 1
381
6 F 2 S 0 8 5 1
Appendix M
Example of Setting Calculation
382
6 F 2 S 0 8 5 1
1. Power System Data
[Example system]
Line impedance of A s/s - Bs/s
- Positive sequence impedance: 0.0197 + j0.2747 (ohms/km)
- Zero sequence impedance: 0.4970 + j1.4387 (ohms/km)
- Mutual impedance: 0.0212 + j0.3729 (ohms/km)
Back impedance
- A s/s: 0.94 (%pu) at 100MVA base
- B s/s: 0.94 (%pu) at 100MVA base
Normal load current: 594.7A
Minimum fault current: 2.05kA
2. Relay Setting
- Relay application:
Relay type: GRZ100-201D
Protection scheme: BOP (Blocking overreach protection), 3 zone time-stepped distance
protection
Autoreclose mode: 1 + 3
3. Setting Calculation
3.1 Normal load current
To calculate load current, back impedance is converted from a percent unit value to an
impedance value.
Base impedance Zbase = (Vbase)
2
/VAbase
= (150kV/ 3 )
2
/100MVA
= 75 ohms
CT: 600/5A
VT: 150kV/ 3 : 110V/ 3
Line length: 16.8km
B s/s A s/s
CT: 600/5A
VT: 150kV/ 3 : 110V/ 3
383
6 F 2 S 0 8 5 1
Therefore, load current I
L
is:
I
L
= (Source voltage)/(A s/s back impedance + Line impedance + B s/s impedance)
= (150kV/ 3 )/(0.94 75 + 16.8 (0.0197
2
+ 0.2747
2
) + 0.94 75)
= 594.7A
3.2 Minimum fault current
The minimum fault current I
fmin
on a protected transmission line is the current of the phase to
earth fault on the nearest remote terminal.
To calculate I
fmin
, zero sequence earth fault current (I
o
), positive sequence earth fault current
(I
1
) and negative earth fault current (I
2
) are calculated as follows:
I
0
= I
1
= I
2
= (Source voltage)/{(Back impedance of A s/s)
+ (Transmission line zero sequence impedance)
+ (Transmission line positive sequence impedance) 2*}
= (150kV/ 3 )/{(0.94 75) + 16.8 (0.4970
2
+ 1.4387
2
)
+ 2 16.8 (0.0197
2
+ 0.2747
2
) }
= 822.28A
So,
I
fmin
= I
0
+ I
1
+ I
2
= 3 822.28 = 2.47kA
*Note: Assuming that positive sequence impedance = negative sequence impedance.
B s/s
Line length: 16.8km
A s/s
M Earth fault
GRZ100
384
6 F 2 S 0 8 5 1
3.3 Scheme setting
Element Contents Setting
SCHEME Protection scheme selection BOP
ZS-C Mho or Quadrilateral characteristic Mho or Quad (Note *1)
ZG-C Mho or Quadrilateral characteristic Mho or Quad (Note *1)
CRSCM Carrier out of service ON
CHSEL Carrier channel configuration SINGLE
BOSW Carrier sending signal A
ZONESEL Carrier control element Z2
ECHO ECHO carrier send ON
WKIT Weak carrier trip ON
CH-DEF DEF carrier channel --
PSB-Z1 PSB for Z1 elements ON
PSB-Z1X PSB for Z1X elements ON
PSB-Z2 PSB for Z2 elements ON
PSB-Z3 PSB for Z3 elements ON
PSB-CR PSB for carrier trip ON
PSB-ZF PSB for ZF elements OFF
PSB-ZR1 PSB for ZR1 elements OFF
PSB-ZR2 PSB for ZR2 elements OFF
PSB-TP Trip under PSB ON
BLZONE Blinder setting mode COM
Z1CNT Z1 trip mode 1
TPMODE Trip mode --
STUB STUB protection OFF
SOTF-OC SOTF OC trip ON
SOTF-Z1 SOTF Z1 trip OFF
SOTF-Z2 SOTF Z2 trip OFF
SOTF-Z3 SOTF Z3 trip OFF
SOTF-F SOTF ZF trip OFF
SOTF-R1 SOTF ZR1 trip OFF
SOTF-R2 SOTF ZR2 trip OFF
SOTF-ND SOTF ZND trip OFF
ZFBT ZF element back-up trip OFF
ZR1BT ZR1 element back-up trip OFF
ZR2BT ZR2 element back-up trip OFF
ZNDBT ZND element back-up trip OFF
OCBT OC back-up trip OFF
OCIBT OCI back-up trip OFF
EFBT EF back-up trip ON
EFBTAL EF back-up trip alarm ON
DEFFEN DEF back-up trip ON
DEFBTAL DEF back-up trip alarm ON
BF1 CBF re-trip OFF
BF2 CBF related trip OFF
BFEXT CBF initiation by ext. trip OFF
385
6 F 2 S 0 8 5 1
OST Out of step trip OFF
THMT Thermal trip OFF
THMAL Thermal alarm OFF
Autoreclose mode Autoreclosing mode SPAR&TPAR
ARC-SM Multi. Shot ARC mode OFF
ARC-CB ARC mode for 1.5CB system --
ARC-DEF REC. by DG carr. trip OFF
ARC-BU ARC initiated by back-up trip OFF
ARC-EXT ARC initiated by ext. trip OFF
VCHK TPAR condition LB
VTPHSEL VT phase selection A
VT-RATE VT rating PH/G
3PH-VT 3ph. VT location BUS
3.4 Impedance setting
Element Standard setting (Recommended) Setting
Z1S 80% of protected line reactance 80%
Z1XS 120% or more of protected line reactance 130%
Z2S 120% or more of protected line reactance 130%
Z3S 100% of protected line impedance plus 150%
of next line section
300%
Z3S Line angle setting (Note *1)
Z4S 120% of Z3S 120% of Z3S setting
Z1G 75% - 80% of protected line reactance 75%
Z1XG 120% or more of protected line reactance 130%
Z2G 120% or more of protected line reactance 130%
Z3G 400% - 600% of protected line impedance 500%
Z3G Line angle setting (Note *1)
Z4G 120% of Z3G 120% of Z3G setting
PSBSZ 2 ohms (5A rating) 2 ohms
PSBGZ 2 ohms (5A rating) 2 ohms
Step 1
Calculate the setting impedance from the given recommended reach point table.
Step 2
Multiply the actual impedance by the factor k to calculate the relay impedance:
Relay impedance = k Actual impedance
Factor k is calculated as follows:
K = (CT ratio)/(VT ratio) = (600/5A)/((150kV/ 3 )/(110V)/ 3 )) = 0.088
Note *1: Z3S and Z3G line angle settings are applicable if [ZS-C] and [ZG-C] are set to
Mho.
Line angle = tan
-1
(0.2747/0.0197) = 85.9
386
6 F 2 S 0 8 5 1
The line angle setting is set to 85. Alternatively set to a smaller angle (e.g. 80) in consideration
of higher levels of fault resistance.
<Z1S, Z1XS, Z2S, Z3S, Z4S, Z1G, Z1XG, Z2G element>
Z1S, Z1XS, Z2S, Z3S, Z4S, Z1G, Z1XG, Z2G element settings are calculated as shown in the
following table.
<Z3G, Z4G element>
Zero sequence current compensation is not applied to Z3 or Z4. Z3G and Z4G settings should be
larger than the calculated values because of the underreaching effect without zero sequence
current compensation.
a. Setting condition of Z3G element:
The Z3G element must operate on all faults for which the Z2G element operates.
(lower setting limit: Z3G > Z2G)
The Z3G element must not operate on load current. (upper setting limit), so:
X3G setting = [Zline 130%](Z2G setting) 2.6(operating margin for no zero phase
sequence current compensation) 1.5(operating margin)
= 500% of Zline
b. Setting condition of Z4G element
The operation zone of the Z4G element includes the operating zone of the Z3G element
remote terminal relay.
Element Actual impedance
(ohms)
k factor Relay impedance
(ohms)
Z1S 3.692 0.32
Z1XS 5.999 0.53
Z2S 5.999 0.53
Z3S 13.84 1.22
Z4S 16.61 1.46
Z1G 3.461 0.088 0.30
Z1XG 5.999 0.53
Z2G 5.999 0.53
Z3G 23.07 2.03
Z4G 27.68 2.44
PSBSZ ----- 2.00
PSBGZ ----- 2.00
3.5 Blinder setting
Zero sequence compensation is not applied to the blinder elements.
Recommended setting: 5.00 ohms
These elements should not operate under maximum load current:
387
6 F 2 S 0 8 5 1
Rset < load impedance/margin
< V rating/(2.5 times of I rating)
= (110V/ 3 )/(2.5 5A)
= 5.08
Element Setting
BLZONE COM
BFRS 5.00
BFLS 120
BRRS 5.00
BRLS Linked with BFRS
BFRG 5.00
BFLG 120
BRRG 5.00
BRLG Linked with BRRG
3.6 Zero sequence compensation
In the GRZ100, vector type zero sequence compensation is applied to Zone 1 and Zone 2, and
the compensation factor is given in the resistive and reactive components independently.
Step 1
Calculate the positive, zero sequence impedance and mutual impedance:
Z
1
= [R
1
: 0.0197] + j[X
1
: 0.2747] (ohms)
Z
0
= [R
0
: 0.497] + j[X
0
: 1.4287] (ohms)
Z
m
= [R
m
: 0.0212] + j[X
m
: 0.3729] (ohms)
Step 2
Calculate the zero and mutual sequence compensation factor setting according to the following
equations:
K
RS
= R
0
/R
1
100 = 0.497/0.0197 = 2523*
K
XS
= X
0
/X
1
100 = 1.4387/0.2747 = 524
K
Rm
= R
m
/R
1
100 = 0.0212/0.0197 = 108
K
Xm
= X
m
/X
1
100 = 0.3729/0.2747 = 136
*Note: If the calculated value exceeds 1000, then a setting of 1000 should be applied, this being
considered to be the maximum practical value.
Element Setting
K
RS
1000
K
XS
524
K
Rm
108
388
6 F 2 S 0 8 5 1
K
Xm
136
3.7 Current setting
a. Definite time earth fault protection (EF)
The EF element may be used either to provide back-up earth fault protection or,
alternatively, open circuit protection. For example, to detect open faults of the CT circuit,
the operating value of the detector should be lower than the normal load current on the line:
EF (normal load current/CT ratio) 0.5
= (594.7 5/600) 0.5
= 2.48A
Element Setting (A)
EF 2.4
b. Directional earth fault element (DEF)
The DEF element should not be operated by the unbalance current or voltage present in
normal conditions. It is recommended to set the current and voltage after measuring the
actual unbalance residual current and voltage on the site.
DEFFI, DEFRI > Max. zero sequence current (3I
o
) in normal conditions
DEFFV, DEFRV > Max. zero sequence voltage (3V
o
) in normal conditions
Element Setting
DEFFI 2.5 (A)
DEFRI 2.5 (A)
DEFFV 21.0 (V)
DEFRV 21.0 (V)
DEFF 85
DEFR 85
c. IDMT overcurrent element (EFI)
The EFI element should not be operated by the unbalance current present under normal
conditions. It is recommended to set the current after measuring the actual unbalance
residual current for the protected line.
EFI > Max. zero sequence current (3I
o
) in normal condition
Element Setting
EFI 2.5 (A)
TEFI 0.5
MEFI S
DEFI F
d. Switch-on-to-fault/stub protection (OCH)
The setting of the OCH element should be lower than the minimum fault current (I
fmin
) at
the busbar:
OCH < (I
fmin
/CT ratio) 0.5
389
6 F 2 S 0 8 5 1
= {(0.8(margin) 2.47kA)/(600/5)} 0.5
= 8.23A
Element Setting
OCH 8.2 (A)
e. Breaker failure protection (BF)
The setting of the BF element should be lower than the minimum fault current:
OCBF < (I
fmin
/CT ratio) 0.5
= {(0.5 2.47kA)/(600/5)} 0.5
= 5.14A
Setting of TBF1 = Breaker opening time + OCBF reset time + Margin
= 40ms + 10ms + 20ms
= 70ms
Setting of TBF2 = TBF1 + Output relay operating time + Breaker opening time +
OCBF reset time + Margin
= 70ms + 10ms + 40ms + 10ms + 10ms
= 140ms
Element Setting
OCBF 5.1 (A)
TBF1 70ms
TBF2 140ms
3.8 Undervoltage element
a. Undervoltage element with current compensation (Phase selector)
(1) Undervoltage element (UVCV)
The UVCV element should be set not to work with the current of the power system.
UVCV < rated voltage 0.7
= 63.5V 0.7
= 44.5
(2) Reach setting (UVCZ)
The UVCZ element is set to the line impedance value:
UVCZ = 16.8 (0.0197
2
+ 0.2747
2
) 0.088
= 0.41 ohms
Element Setting
UVCV 45V
UVCZ 0.41
UVC 85
390
6 F 2 S 0 8 5 1
b. VT failure supervision
The undervoltage element for VT failure supervision (UVFS, UVFG) is set to about 50% of
the rated voltage.
Element Setting
UVFS 52V
UVFG 30V
c. Weak infeed tripping function
The undervoltage element for weak infeed tripping (UVLS, UVLG) is set to 70% of the
rated voltage.
Element Setting
UVLS 77V
UVLG 45V
3.9 Time setting
a. Time delay setting for zone distance protection
b. Coordination time setting for protection signaling channel
This time setting is required only for the Blocking scheme. The time should be set larger
than the time delay of protection signaling equipment (PSE) including propagation time of
PLC (Power Line Carrier) or other communication link. The time setting should include an
operation margin of 5ms.
Time setting = Time delay of PSE + Margin
= 12ms + 5ms
= 17ms
c. Time setting of earth fault element EF (TEF)
This time setting is for time delay of the EF element. If it is set to 3s, the trip/alarm contact
will close 3s after detecting an unbalance current (residual current) such as a CT open
circuit fault. In addition to CT open circuit faults, this element can detect a broken
conductor condition.
d. Time setting of directional earth fault relay (TDEF)
Set the time delay for the directional earth fault element for back-up.
Element Setting (s)
TZ1S 0.00
TZ2S 0.30
TZ3S 0.40
TZ1G 0.00
TZ2G 0.30
TZ3G 0.40
TCHD 0.017
TEF 3.00
TDEF 3.00
391
6 F 2 S 0 8 5 1
3.10 Autoreclose setting
a. Dead timer reset timing
b. Dead line timer
The SPAR and TPAR timer are provided to present the deionized time of the line. The
SPAR element is initiated simultaneously by the reclose initiation for single-pole
autoreclose dead time. TPAR is for three-pole autoreclose dead time.
c. Reclaim timer
The reclosing command signal is blocked during adjusted time set by reclaim timer, after
the breaker is closed manually or automatically.
d. ARC reset timer
This time element starts to run upon reclosing initiation.
e. ARC output pulse timer
The duration of the reclosing pulse depends on the operation time of the breaker. The
required pulse time is set by this time element.
Element Setting (s)
TEVLV 0.30
TSPR 0.80
TTPR 0.60
TRDY 60
TRR 2.00
TW 0.2
3.11 Synchronism check element
The synchronism check element setting is as follows.
Element Setting
SY1UV 83V
SY10V 51V
SY1 30deg.
TSYN1 1.00s
TDBL1 0.05s
TLBD1 0.05s
OVB 51V
UVB 13V
OVL1 51V
UVL1 13V
392
6 F 2 S 0 8 5 1
393
6 F 2 S 0 8 5 1
Appendix N
IEC60870-5-103: Interoperability
394
6 F 2 S 0 8 5 1
IEC60870-5-103 Configurator
IEC103 configurator software is included in a same CD as RSM100, and can be installed easily
as follows:
Installation of IEC103 Configurator
Insert the CD-ROM (RSM100) into a CDROM drive to install this software on a PC.
Double click the Setup.exe of the folder \IEC103Conf under the root directory, and
operate it according to the message.
When installation has been completed, the IEC103 Configurator will be registered in the start
menu.
Starting IEC103 Configurator
Click [Start][Programs][IEC103 Configurator][IECConf] to the IEC103 Configurator
software.
Note: The instruction manual of IEC103 Configurator can be viewed by clicking
[Help][Manual] on IEC103 Configurator.
IEC60870-5-103: Interoperability
1. Physical Layer
1.1 Electrical interface: EIA RS-485
Number of loads, 32 for one protection equipment
1.2 Optical interface
Glass fibre (option)
ST type connector (option)
1.3 Transmission speed
User setting: 9600 or 19200 bit/s
2. Application Layer
COMMON ADDRESS of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
3. List of Information
The following items can be customized with the original software tool IEC103 configurator.
(For details, refer to IEC103 configurator manual No.6F2S0839.)
- Items for Time-tagged message: Type ID(1/2), INF, FUN, Transmission
condition(Signal number), COT
- Items for Time-tagged measurands: INF, FUN, Transmission condition(Signal
number), COT, Type of measurand quantities
- Items for General command: INF, FUN, Control condition(Signal number)
- Items for Measurands: Type ID(3/9), INF, FUN, Number of measurand, Type of
395
6 F 2 S 0 8 5 1
measurand quantities
- Common setting
Transmission cycle of Measurand frame
FUN of System function
Test mode, etc.
CAUTION: To be effective the setting data written via the RS232C, turn off the DC supply
of the relay and turn on again.
3. 1 IEC60870-5-103 Interface
3.1.1 Spontaneous events
The events created by the relay will be sent using Function type (FUN) / Information numbers
(INF) to the IEC60870-5-103 master station.
3.1.2 General interrogation
The GI request can be used to read the status of the relay, the Function types and Information
numbers that will be returned during the GI cycle are shown in the table below.
For details, refer to the standard IEC60870-5-103 section 7.4.3.
3.1.3 Cyclic measurements
The relay will produce measured values using Type ID=3 or 9 on a cyclical basis, this can be
read from the relay using a Class 2 poll. The rate at which the relay produces new measured
values can be customized.
3.1.4 Commands
The supported commands can be customized. The relay will respond to non-supported
commands with a cause of transmission (COT) of negative acknowledgement of a command.
For details, refer to the standard IEC60870-5-103 section 7.4.4.
3.1.5 Test mode
In test mode, both spontaneous messages and polled measured values, intended for processing
in the control system, are designated by means of the CAUSE OF TRANSMISSION test
mode. This means that CAUSE OF TRANSMISSION = 7 test mode is used for messages
normally transmitted with COT=1 (spontaneous) or COT=2 (cyclic).
For details, refer to the standard IEC60870-5-103 section 7.4.5.
3.1.6 Blocking of monitor direction
If the blocking of the monitor direction is activated in the protection equipment, all indications
and measurands are no longer transmitted.
For details, refer to the standard IEC60870-5-103 section 7.4.6.
3.2 List of Information
The followings are the default settings.
396
6 F 2 S 0 8 5 1
List of Information
IEC103 Configurator Default setting
INF Description Contents GI Type COT FUN DPI
ID Signal No. OFF ON
Standard Information numbers in monitor direction
System Function
0 End of General Interrogation Transmission completion of GI items. -- 8 10 255 -- -- --
0 Time Synchronization Time Synchronization ACK. -- 6 8 255 -- -- --
2 Reset FCB Reset FCB(toggle bit) ACK -- 5 3 128 -- -- --
3 Reset CU Reset CU ACK -- 5 4 128 -- -- --
4 Start/Restart Relay start/restart -- 5 5 128 -- -- --
5 Power On Relay power on. Not supported -- -- --
Status Indications
16 Auto-recloser active
If it is possible to use auto-recloser, this item is set
active, if impossible, inactive.
GI 1 1, 9, 11, 12 128 1411 1 2
17 Teleprotection active
If protection using telecommunication is available, this
item is set to active. If not, set to inactive.
GI 1 1, 9, 12 128 1412 1 2
18 Protection active
If the protection is available, this item is set to active. If
not, set to inactive.
GI 1 1, 9, 12 128 1413 1 2
19 LED reset Reset of latched LEDs -- 1 1, 11, 12 128 1409 -- 2
20 Monitor direction blocked
Block the 103 transmission from a relay to control
system. IECBLK: "Blocked" settimg.
GI 1 9, 11 128 1241 1 2
21 Test mode
Transmission of testmode situation from a relay to
control system. IECTST "ON" setting.
GI 1 9, 11 128 1242 1 2
22 Local parameter Setting
When a setting change has done at the local, the
event is sent to control system.
Not supported
23 Characteristic1 Setting group 1 active GI 1 1, 9, 11, 12 128 1243 1 2
24 Characteristic2 Setting group 2 active GI 1 1, 9, 11, 12 128 1244 1 2
25 Characteristic3 Setting group 3 active GI 1 1, 9, 11, 12 128 1245 1 2
26 Characteristic4 Setting group 4 active GI 1 1, 9, 11, 12 128 1246 1 2
27 Auxiliary input1 Binary input 1 No set
28 Auxiliary input2 Binary input 2 No set
29 Auxiliary input3 Binary input 3 No set
30 Auxiliary input4 Binary input 4 No set
Supervision Indications
32 Measurand supervision I Zero sequence current supervision GI 1 1, 9 128 1267 1 2
33 Measurand supervision V Zero sequence voltage supervision GI 1 1, 9 128 1268 1 2
35 Phase sequence supervision Negative sequence voltage supevision GI 1 1, 9 128 1269 1 2
36 Trip circuit supervision Output circuit supervision Not supported
37 I>>backup operation Not supported
38 VT fuse failure VT failure GI 1 1, 9 128 172 1 2
39 Teleprotection disturbed CF(Communication system Fail) supervision GI 1 1, 9 128 253 1 2
46 Group warning Only alarming GI 1 1, 9 128 1258 1 2
47 Group alarm Trip blocking and alarming GI 1 1, 9 128 1252 1 2
Earth Fault Indications
48 Earth Fault L1 A phase earth f ault No set
49 Earth Fault L2 B phase earth f ault No set
50 Earth Fault L3 C phase earth f ault No set
51 Earth Fault Fwd Earth fault forward Not supported
52 Earth Fault Rev Earth fault reverse Not supported
397
6 F 2 S 0 8 5 1
IEC103 Configurator Default setting
INF Description Contents GI Type COT FUN DPI
ID Signal NO. OFF ON
Fault Indications
64 Start/pick-up L1 A phase, A-B phase or C-A phase element pick-up No set
65 Start/pick-up L2 B phase, A-B phase or B-C phase element pick-up No set
66 Start/pick-up L3 C phase, B-C phase or C-A phase element pick-up No set
67 Start/pick-up N Earth fault element pick-up No set
68 General trip Any trip -- 2 1 128 1280 -- 2
69 Trip L1 A phase, A-B phase or C-A phase trip No set
70 Trip L2 B phase, A-B phase or B-C phase trip No set
71 Trip L3 C phase, B-C phase or C-A phase trip No set
72 Trip I>>(back-up) Back up trip -- 2 1 128 194 -- 2
73 Fault location X In ohms Fault location -- 4 1 128 1048 -- --
74 Fault forward/line Forward fault Not supported
75 Fault reverse/Busbar Reverse fault Not supported
76
Teleprotection Signal
transmitted
Carrier signal sending Not supported
77 Teleprotection Signal received Carrier signal receiving Not supported
78 Zone1 Zone 1 trip -- 2 1 128 342 -- 2
79 Zone2 Zone 2 trip -- 2 1 128 344 -- 2
80 Zone3 Zone 3 trip -- 2 1 128 345 -- 2
81 Zone4 Zone 4 trip No set
82 Zone5 Zone 5 trip No set
83 Zone6 Zone 6 trip No set
84 General Start/Pick-up Any elements pick-up No set
85 Breaker Failure CBF trip or CBF retrip -- 2 1 128 199 -- 2
86 Trip measuring system L1 Not supported
87 Trip measuring system L2 Not supported
88 Trip measuring system L3 Not supported
89 Trip measuring system E Not supported
90 Trip I> Inverse time OC trip -- 2 1 128 327 -- 2
91 Trip I>> Definite time OC trip -- 2 1 128 326 -- 2
92 Trip IN> Inverse time earth fault OC trip -- 2 1 128 184 -- 2
93 Trip IN>> Definite time earth fault OC trip -- 2 1 128 678 -- 2
Autoreclose indications
128 CB 'ON' by Autoreclose CB close command output -- 1 1 128 291 -- 2
129
CB 'ON' by long-time
Autoreclose
Not supported
130 Autoreclose Blocked Autoreclose block GI 1 1, 9 128 1544 1 2
Details of Fault location settings in IEC103 configurator
INF Tbl Offset Data type Coeff
73 5 26 short 0.1
398
6 F 2 S 0 8 5 1
IEC103 configurator Default setting
INF Description Contents
GI
Type
ID
COT FUN Max. No.
Measurands
144 Measurand I <meaurand I> No 0
145 Measurand I,V <meaurand I> No 0
146 Measurand I,V,P,Q <meaurand I> No 0
147 Measurand IN,VEN <meaurand I> No 0
148
Measurand IL1,2,3, VL1,2,3,
P,Q,f
Ia, Ib, Ic, Va, Vb, Vc, P, Q, f measurand
<meaurand II>
-- 9 2, 7 128 9
Generic Function
240 Read Headings Not supported
241
Read attributes of all entries
of a group
Not supported
243 Read directory of entry Not supported
244 Real attribute of entry Not supported
245 End of GGI Not supported
249 Write entry with confirm Not supported
250 Write entry with execute Not supported
251 Write entry aborted Not supported
Details of MEA settings in IEC103 configurator
INF MEA Tbl Offset Data type Limit Coeff
Lower Upper
148 Ia 1 36 short 0 4096 3.41333
Ib 1 40 short 0 4096 3.41333
Ic 1 44 short 0 4096 3.41333
Va 1 0 short 0 4096 0.26877
Vb 1 4 short 0 4096 0.26877
Vc 1 8 short 0 4096 0.26877
P 2 8 long -4096 4096 0.00071661
Q 2 12 long -4096 4096 0.00071661
f 2 16 short 0 4096 0.34133
399
6 F 2 S 0 8 5 1
IEC103 Configurator Default setting
Control
direction
Type
ID
COT FUN
Selection of standard information numbers in control direction
System functions
0
Initiation of general
interrogation
-- 7 9 255
0 Time synchronization -- 6 8 255
General commands
16 Auto-recloser on/off ON/OFF 20 20 128
17 Teleprotection on/off ON/OFF 20 20 128
18 Protection on/off (*1) ON/OFF 20 20 128
19 LED reset Reset indication of latched LEDs. ON 20 20 128
23 Activate characteristic 1 Setting Group 1 ON 20 20 128
24 Activate characteristic 2 Setting Group 2 ON 20 20 128
25 Activate characteristic 3 Setting Group 3 ON 20 20 128
26 Activate characteristic 4 Setting Group 4 ON 20 20 128
Generic functions
240
Read headings of all defined
groups
Not supported
241
Read values or attributes of all
entries of one group
Not supported
243
Read directory of a single
entry
Not supported
244
Read values or attributes of a
single entry
Not supported
245
General Interrogation of
generic data
Not supported
248 Write entry Not supported
249 Write entry with confirmation Not supported
250 Write entry with execution Not supported
INF Description Contents
(1) Note: While the relay receives the "Protection off" command, "IN SERVICE LED" is off.
Details of Command settings in IEC103 configurator
INF DCO
Sig off Sig on Rev Valid time
16 2684 2684 0
17 2685 2685 0
18 2686 2686 0
19 0 2688 200
23 0 2640 1000
24 0 2641 1000
25 0 2642 1000
26 0 2643 1000
: signal reverse
400
6 F 2 S 0 8 5 1
Description Contents GRZ100 supported Comment
Basic application functions
Test mode Yes
Blocking of monitor direction Yes
Disturbance data No
Generic services No
Private data Yes
Miscellaneous
Measurand
Max. MVAL = rated
value times
Current L1 Ia Configurable
Current L2 Ib Configurable
Current L3 Ic Configurable
Voltage L1-E Va Configurable
Voltage L2-E Vb Configurable
Voltage L3-E Vc Configurable
Active power P P Configurable
Reactive power Q Q Configurable
Frequency f f Configurable
Voltage L1 - L2 Vab Configurable
Details of Common settings in IEC103 configurator
- Setting files remark: GRZ100_1.00
- Remote operation valid time [ms]: 4000
- Local operation valid time [ms]: 4000
- Measurand period [s]: 2
- Function type of System functions: 128
- Signal No. of Test mode: 1242
- Signal No. for Real time and Fault number: 1279
401
6 F 2 S 0 8 5 1
[Legend]
GI: General Interrogation (refer to IEC60870-5-103 section 7.4.3)
Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.1)
1 : time-tagged message
2 : time-tagged message with relative time
3 : measurands I
4 : time-tagged measurands with relative time
5 : identification
6 : time synchronization
8 : general interrogation termination
9 : measurands II
10: generic data
11: generic identification
20: general command
23: list of recorded disturbances
26: ready for transmission for disturbance data
27: ready for transmission of a channel
28: ready for transmission of tags
29: transmission of tags
30: transmission of disturbance values
31: end of transmission
COT: Cause of Transmission (refer to IEC60870-5-103 section 7.2.3)
1: spontaneous
2: cyclic
3: reset frame count bit (FCB)
4: reset communication unit (CU)
5: start / restart
6: power on
7: test mode
8: time synchronization
9: general interrogation
10: termination of general interrogation
11: local operation
12: remote operation
20: positive acknowledgement of command
21: negative acknowledgement of command
31: transmission of disturbance data
40: positive acknowledgement of generic write command
41: negative acknowledgement of generic write command
42: valid data response to generic read command
43: invalid data response to generic read command
44: generic write confirmation
FUN: Function type (refer to IEC60870-5-103 section 7.2.5.1)
DPI: Double-point Information (refer to IEC60870-5-103 section 7.2.6.5)
DCO: Double Command (refer to IEC60870-5-103 section 7.2.6.4)
402
6 F 2 S 0 8 5 1
IEC103 setting data is recommended to be saved as follows:
(1) Naming for IEC103setting data
The file extension of IEC103 setting data is .csv. The version name is recommended to be
provided with a revision number in order to be changed in future as follows:
First draft: _01.csv
Second draft: _02.csv
Third draft: _03.csv
Revision number
The name is recommended to be able to discriminate the relay type such as GRZ100 or
GRL100, etc. The setting files remark field of IEC103 is able to enter up to 12 one-byte characters.
It is utilized for control of IEC103 setting data.
(2) Saving theIEC103 setting data
The IEC103 setting data is recommended to be saved in external media such as FD (floppy disk) or
CD-R, not to remain in the folder.
403
6 F 2 S 0 8 5 1
Troubleshooting
No. Phenomena Supposed causes Check / Confirmation
Object Procedure
Address setting is incorrect. BCU
RY
Match address setting between BCU and relay.
Avoid duplication of address with other relay.
Transmission baud rate setting is
incorrect.
BCU
RY
Match transmission baud rate setting between
BCU and relay.
Start bit, stop bit and parity settings of
data that BCU transmits to relay is
incorrect.
BCU Go over the following settings by BCU. Relay
setting is fixed as following settings.
- Start bit: 1bit
- Stop bit: 1bit
- Parity setting: even
RS485 or optical cable interconnection
is incorrect.
Cable - Check the connection port.(CH1/CH2)
- Check the interconnection of RS485 A/B/COM
- Check the send and received interconnection of
optical cable.
The setting of converter is incorrect.
(RS485/optic conversion is executed
with the transmission channel, etc.)
Converter In the event of using G1IF2, change the DIPSW
setting in reference to INSTRUCTION MANUAL
(6F2S0794).
The relationship between logical 0/1 of
the signal and Sig.on/off is incorrect. (In
the event of using optical cable)
BCU Check the following;
Logical0 : Sig.on
Logical1:Sig.off
Terminal resistor is not offered.
(Especially when RS485 cable is long.)
cable Impose terminal resistor (150[ohms]) to both ends
of RS 485 cable.
Relay cannot receive the requirement
frame from BCU.
(The timing coordination of sending and
receiving switch control is irregular in
half-duplex communication.)
BCU Check to secure the margin more than 15ms
between receiving the reply frame from the relay
and transmitting the next requirement frame on
BCU.
1 Communication
trouble (IEC103
communication is
not available.)
The requirement frame from BCU and
the reply frame from relay contend.
(The sending and receiving timing
coordination is irregular in half-duplex
communication.)
BCU Check to set the time-out of reply frame from the
relay.
Time-out setting: more than 100ms (acceptable
value of response time 50ms plus
margin)
404
6 F 2 S 0 8 5 1
The relevant event sending condition is
not valid.
RY Change the event sending condition (signal
number) of IEC103 configurator if there is a setting
error. When the setting is correct, check the signal
condition by programmable LED, etc.
The relevant event Information Number
(INF) and/or Function Type (FUN) may
be different between the relay and SAS.
RY
SAS
Match the relevant event Information Number
(INF) or Function Type (FUN) between the relay
and SAS.
The relay is not initialised after writing
IEC103 configurator setting.
RY Check the sum value of IEC103 setting data from
the LCD screen. When differing from the sum
value on IEC103 configurator, initialise the relay.
2 HMI does not
display IEC103
event on the SAS
side.
It changes to the block mode. RY Change the IECBR settling to Normal.
BCU does not transmit the frame of time
synchronisation.
BCU Transmit the frame of time synchronisation. 3 Time can be
synchronised with
IEC103
communication.
The settling of time synchronisation
source is set to other than IEC.
RY Change the settling of time synchronisation
source to IEC.
(Note) BCU: Bay control unit, RY: Relay
405
6 F 2 S 0 8 5 1
Appendix O
Programmable Reset Characteristics
and Implementation of Thermal
Model to IEC60255-8
406
6 F 2 S 0 8 5 1
Programmable Reset Characteristics
The overcurrent stages for phase and earth faults, OC1 and EF1, each have a programmable reset
feature. Resetting may be instantaneous or definite time delayed.
Instantaneous resetting is normally applied in multi-shot auto-reclosing schemes, to ensure correct
grading between relays at various points in the scheme.
The definite time delayed reset characteristic may be used to provide faster clearance of intermittent
(pecking or flashing) fault conditions. An example of where such phenomena may be experienced is
in plastic insulated cables, where the fault energy melts the cable insulation and temporarily
extinguishes the fault, after which the insulation again breaks down and the process repeats.
An inverse time overcurrent protection with instantaneous resetting cannot detect this condition until
the fault becomes permanent, thereby allowing a succession of such breakdowns to occur, with
associated damage to plant and danger to personnel. If a definite time reset delay of, for example, 60
seconds is applied, on the other hand, the inverse time element does not reset immediately after each
successive fault occurrence. Instead, with each new fault inception, it continues to integrate from the
point reached during the previous breakdown, and therefore operates before the condition becomes
permanent. Figure O-1 illustrates this theory.
Figure O-1
TRIP LEVEL
TRIP LEVEL
Inverse Time Relay
with Instantaneous
Reset
Intermittent
Fault Condition
Inverse Time Relay
with Definite Time
Reset
Delayed Reset
407
6 F 2 S 0 8 5 1
Implementation of Thermal Model to IEC60255-8
Heating by overload current and cooling by dissipation of an electrical system follow exponential time
constants. The thermal characteristics of the electrical system can be shown by equation (1).
=
I
I
e
AOL
t
2
2
1 100
% (1)
where:
= thermal state of the system as a percentage of allowable thermal capacity,
I = applied load current,
I
AOL
= allowable overload current of the system,
= thermal time constant of the system.
The thermal stateis expressed as a percentage of the thermal capacity of the protected system, where
0% represents the cold state and 100% represents the thermal limit, that is the point at which no further
temperature rise can be safely tolerated and the system should be disconnected. The thermal limit for
any given electrical plant is fixed by the thermal setting I
AOL
. The relay gives a trip output when =
100%.
If current I is applied to a cold system, then will rise exponentially from 0% to (I
2
/I
AOL
2
100%), with time
constant , as in Figure O-2. If = 100%, then the allowable thermal capacity of the system has been reached.
Figure O-2
A thermal overload protection relay can be designed to model this function, giving tripping times
according to the IEC60255-8 Hot and Cold curves.
t =Ln
I
I I
AOL
2
2 2
t
AOL
e
I
I
% 100 2
2
AOL
I
I
408
6 F 2 S 0 8 5 1
I
P
= prior load current.
In fact, the cold curve is simply a special case of the hot curve where prior load current I
P
= 0, catering
for the situation where a cold system is switched on to an immediate overload.
Figure O-3 shows a typical thermal profile for a system which initially carries normal load current, and
is then subjected to an overload condition until a trip results, before finally cooling to ambient
temperature.
(%)
t (s)
100%
Normal Load
Current Condition
Cooling Curve
Overload Current
Condition
Trip at 100%
Figure O-3
409
6 F 2 S 0 8 5 1
Appendix P
IEC61850: MICS & PICS
410
6 F 2 S 0 8 5 1
MICS: IEC61850 Model Implementation Conformance Statement
The GRZ100 relay supports IEC 61850 logical nodes and common data classes as indicated in the
following tables.
Logical nodes in IEC 61850-7-4
Logical Nodes GRZ100
L: System Logical Nodes
LPHD Yes
Common Logical Node Yes
LLN0 Yes
P: Logical Nodes for Protection functions
PDIF ---
PDIR ---
PDIS Yes
PDOP ---
PDUP ---
PFRC ---
PHAR ---
PHIZ ---
PIOC ---
PMRI ---
PMSS ---
POPE ---
PPAM ---
PSCH Yes
PSDE ---
PTEF ---
PTOC Yes
PTOF ---
PTOV Yes
PTRC Yes
PTTR Yes
PTUC ---
PTUV Yes
PUPF ---
PTUF ---
PVOC ---
PVPH ---
PZSU ---
R: Logical Nodes for protection related functions
RDRE ---
RADR ---
RBDR ---
RDRS ---
RBRF Yes
RDIR ---
RFLO Yes
RPSB Yes
RREC Yes
RSYN Yes
C: Logical Nodes for Control
CALH ---
CCGR ---
CILO ---
CPOW ---
CSWI ---
G: Logical Nodes for Generic references
GAPC ---
GGIO Yes
Nodes GRZ100
GGIO_GOOSE Yes
GSAL ---
I: Logical Nodes for Interfacing and archiving
IARC ---
IHMI ---
ITCI ---
ITMI ---
A: Logical Nodes for Automatic control
ANCR ---
ARCO ---
ATCC ---
AVCO ---
M: Logical Nodes for Metering and measurement
MDIF ---
MHAI ---
MHAN ---
MMTR ---
MMXN ---
MMXU Yes
MSQI Yes
MSTA ---
S: Logical Nodes for Sensors and monitoring
SARC ---
SIMG ---
SIML ---
SPDC ---
X: Logical Nodes for Switchgear
XCBR Yes
XSWI ---
T: Logical Nodes for Instrument transformers
TCTR ---
TVTR ---
Y: Logical Nodes for Power transformers
YEFN ---
YLTC ---
YPSH ---
YPTR ---
Z: Logical Nodes for Further power system equipment
ZAXN ---
ZBAT ---
ZCAB ---
ZCAP ---
ZCON ---
ZGEN ---
ZGIL ---
ZLIN ---
ZMOT ---
ZREA ---
ZRRC ---
ZSAR ---
ZTCF ---
ZTCR ---
411
6 F 2 S 0 8 5 1
Common data classes in IEC61850-7-3
Common data classes GRZ100
Status information
SPS Yes
DPS ---
INS Yes
ACT Yes
ACD Yes
SEC ---
BCR ---
Measured information
MV Yes
CMV Yes
SAV ---
WYE Yes
DEL Yes
SEQ Yes
HMV ---
HWYE ---
HDEL ---
Controllable status information
SPC ---
DPC Yes
INC Yes
BSC ---
ISC ---
Controllable analogue information
APC ---
Status settings
SPG Yes
ING Yes
Analogue settings
ASG Yes
CURVE Yes
Description information
DPL Yes
LPL Yes
CSD ---
412
6 F 2 S 0 8 5 1
LPHD class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
PhyName DPL Physical device name plate M Y
PhyHealth INS Physical device health M Y
OutOv SPS Output communications buffer overflow O N
Proxy SPS Indicates if this LN is a proxy M Y
InOv SPS Input communications buffer overflow O N
NumPwrUp INS Number of Power ups O N
WrmStr INS Number of Warm Starts O N
WacTrg INS Number of watchdog device resets detected O N
PwrUp SPS Power Up detected O N
PwrDn SPS Power Down detected O N
PwrSupAlm SPS External power supply alarm O N
RsStat SPC Reset device statistics T O N
Common Logical Node class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Mandatory Logical Node Information (Shall be inherited by ALL LN but LPHD)
Mod INC Mode M Y
Beh INS Behaviour M Y
Health INS Health M Y
NamPlt LPL Name plate M Y
Optional Logical Node Information
Loc SPS Local operation O N
EEHealth INS External equipment health O N
EEName DPL External equipment name plate O N
OpCntRs INC Operation counter resetable O N
OpCnt INS Operation counter O N
OpTmh INS Operation time O N
Data Sets (see IEC 61850-7-2)
Inherited and pecialized from Logical Node class (see IEC 61850-7-2)
Control Blocks (see IEC 61850-7-2)
Inherited and pecialized from Logical Node class (see IEC 61850-7-2)
Services (see IEC 61850-7-2)
Inherited and pecialized from Logical Node class (see IEC 61850-7-2)
413
6 F 2 S 0 8 5 1
LLNO class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Loc SPS Local operation for complete logical device O Y
OpTmh INS Operation time O N
Controls
Diag SPC Run Diagnostics O Y
LEDRs SPC LED reset T O Y
PDIS class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
Settings
PoRch ASG Polar Reach is the diameter of the Mho diagram O Y
PhStr ASG Phase Start Value O Y
GndStr ASG Ground Start Value O Y
DirMod ING Directional Mode O Y
PctRch ASG Percent Reach O N
Ofs ASG Offset O Y
PctOfs ASG Percent Offset O N
RisLod ASG Resistive reach for load area O N
AngLod ASG Angle for load area O N
TmDlMod SPG Operate Time Delay Mode O N
OpDlTmms ING Operate Time Delay O Y
PhDlMod SPG Operate Time Delay Multiphase Mode O N
PhDlTmms ING Operate Time Delay for Multiphase Faults O N
GndDlMod SPG Operate Time Delay for Single Phase Ground Mode O N
GndDlTmms ING Operate Time Delay for single phase ground faults O N
X1 ASG Positive sequence line (reach) reactance O Y
LinAng ASG Line Angle O Y
RisGndRch ASG Resistive Ground Reach O Y
RisPhRch ASG Resistive Phase Reach O Y
K0Fact ASG Residual Compensation Factor K0 O N
K0FactAng ASG Residual Compensation Factor Angle O N
RsDlTmms ING Reset Time Delay O N
414
6 F 2 S 0 8 5 1
PSCH class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
ProTx SPS Teleprotection signal transmitted T M Y
ProRx SPS Teleprotection signal received T M Y
Str ACD Start M Y
Op ACT Operate T M Y
CarRx ACT Carrier received after unblock logic O N
LosOfGrd SPS Loss of guard O N
Echo ACT Echo signal from weak end infeed function O Y
WeiOp ACT Operate signal from weak end infeed function O Y
RvABlk ACT Block signal from current reversal function O Y
GrdRx SPS Guard Received O N
Settings
SchTyp ING Scheme Type O N
OpDlTmms ING Operate Delay Time O N
CrdTmms ING Co-ordination timer for blocking scheme O Y
DurTmms ING Minimum duration of carrier send signal O N
UnBlkMod ING Unblock function mode for scheme type O N
SecTmms ING Pickup security timer on loss of carrier guard signal O N
WeiMod ING Mode of weak end infeed function O N
WeiTmms ING Co-ordination time for weak end infeed function O N
PPVVal ASG Voltage level for weak end infeed function phase-phase O N
PhGndVal ASG Voltage level for weak end infeed function phase-ground O N
RvAMod ING Mode of current reversal function O N
RvATmms ING Pickup time for current reversal logic O N
RvRsTmms ING Delay time for reset of current reversal output O Y
415
6 F 2 S 0 8 5 1
PTOC class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
TmASt CSD Active curve characteristic O N
Settings
TmACrv CURVE Operating Curve Type O Y
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
TypRsCrv ING Type of Reset Curve O N
RsDlTmms ING Reset Delay Time O N
DirMod ING Directional Mode O N
PTOV class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T O Y
TmVSt CSD Active curve characteristic O N
Settings
TmVCrv CURVE Operating Curve Type O Y
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N
416
6 F 2 S 0 8 5 1
PTRC class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Tr ACT Trip C Y
Op ACT Operate (combination of subscribed Op from protection functions) C N
Str ACD Sum of all starts of all connected Logical Nodes O N
Settings
TrMod ING Trip Mode O N
TrPlsTmms ING Trip Pulse Time O N
Condition C: At least one of the two status information (Tr, Op) shall be used.
PTTR class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Measured Values
Amp MV Current for thermal load model O N
Tmp MV Temperature for thermal load O N
TmpRl MV Relation between temperature and max. temperature O N
LodRsvAlm MV Load reserve to alarm O N
LodRsvTr MV Load reserve to trip O N
AgeRat MV Ageing rate O N
Status Information
Str ACD Start O Y
Op ACT Operate T M Y
AlmThm ACT Thermal Alarm O Y
TmTmpSt CSD Active curve characteristic O N
TmASt CSD Active curve characteristic O N
Settings
TmTmpCrv CURVE Characteristic Curve for temperature measurement O N
TmACrv CURVE Characteristic Curve for current measurement /Thermal model O N
TmpMax ASG Maximum allowed temperature O N
StrVal ASG Start Value O Y
OpDlTmms ING Operate Delay Time O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
RsDlTmms ING Reset Delay Time O N
ConsTms ING Time constant of the thermal model O N
AlmVal ASG Alarm Value O N
417
6 F 2 S 0 8 5 1
PTUV class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start M Y
Op ACT Operate T M Y
TmVSt CSD Active curve characteristic O N
Settings
TmVCrv CURVE Operating Curve Type O N
StrVal ASG Start Value O Y
TmMult ASG Time Dial Multiplier O N
MinOpTmms ING Minimum Operate Time O N
MaxOpTmms ING Maximum Operate Time O N
OpDlTmms ING Operate Delay Time O Y
RsDlTmms ING Reset Delay Time O N
RBRF class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start, timer running O Y
OpEx ACT Breaker failure trip (external trip) T C N
OpIn ACT Operate, retrip (internal trip) T C Y
Settings
FailMod ING Breaker Failure Detection Mode (current, breaker status, both, other) O Y
FailTmms ING Breaker Failure Time Delay for bus bar trip O Y
SPTrTmms ING Single Pole Retrip Time Delay O N
TPTrTmms ING Three Pole Retrip Time Delay O N
DetValA ASG Current Detector Value O Y
ReTrMod ING Retrip Mode O N
Condition C: At least one of either data shall be used depending on the applied tripping schema.
418
6 F 2 S 0 8 5 1
RFLO class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class
M
OpCntRs INC Resetable operation counter O N
Measured values
FDOhm MV Fault Distance in M Y
FDkm MV Fault Distance in km M Y
Status Information
FltLoop INS Fault Loop O Y
Settings
LinLenKm ASG Line length in km O Y
R1 ASG Positive-sequence line resistance O Y
X1 ASG Positive-sequence line reactance O Y
R0 ASG Zero-sequence line resistance O Y
X0 ASG Zero-sequence line reactance O Y
Z1Mod ASG Positive-sequence line impedance value O N
Z1Ang ASG Positive-sequence line impedance angle O N
Z0Mod ASG Zero-sequence line impedance value O N
Z0Ang ASG Zero-sequence line impedance angle O N
Rm0 ASG Mutual resistance O Y
Xm0 ASG Mutual reactance O Y
Zm0Mod ASG Mutual impedance value O N
Zm0Ang ASG Mutual impedance angle O N
RPSB class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Status Information
Str ACD Start (Power Swing Detected) C1 (*1)
Op ACT Operate (Out of step Tripping) T C2 Y
BlkZn SPS Blocking of correlated PDIS zone C1 (*1)
Settings
ZeroEna SPG Zero Enable O N
NgEna SPG Negative Sequence Current Supervision Enabled O N
MaxEna SPG Max Current Supervision Enabled O N
SwgVal ASG Power Swing Delta O (*1)
SwgRis ASG Power Swing Delta R O (*2)
SwgReact ASG Power Swing Delta X O (*2)
SwgTmms ING Power Swing Time O (*1)
UnBlkTmms ING Unblocking Time O N
MaxNumSlp ING Maximum number of pole slips until tripping (Op, Out of step tripping) O N
EvTmms ING Evaluation time (time window, Out of step tripping) O N
Condition C1: Mandatory if RPSB is used for Power swing blocking
Condition C2: Mandatory if RPSB is used for Out of step tripping
(*1): RPSB_0=Y, RPSB_1=N
(*2): RPSB_0=N, RPSB_1=Y
419
6 F 2 S 0 8 5 1
RREC class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
OpCntRs INC Resetable operation counter O N
Controls
BlkRec INC Block Reclose O N
ChkRec SPC Check Reclosing O N
Auto SPC Automatic Operation (external switch status) O N
Status Information
Op ACT Operate (used here to provide close to XCBR) T M Y
AutoRecSt INS Auto Reclosing Status M Y
Settings
Rec1Tmms ING First Reclose Time O N
Rec2Tmms ING Second Reclose Time O N
Rec3Tmms ING Third Reclose Time O N
PlsTmms ING Close Pulse Time O Y
RclTmms ING Reclaim Time O Y
RSYN class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Controls
RHz SPC Raise Frequency O N
LHz SPC Lower Frequency O N
RV SPC Raise Voltage O N
LV SPC Lower Voltage O N
Status Information
Rel SPS Release M Y
VInd SPS Voltage Difference Indicator O N
AngInd SPS Angle Difference Indicator O N
HzInd SPS Frequency Difference Indicator O N
SynPrg SPS Synchronising in progress O N
Measured values
DifVClc MV Calculated Difference in Voltage O N
DifHzClc MV Calculated Difference in Frequency O N
DifAngClc MV Calculated Difference of Phase Angle O N
Settings
DifV ASG Difference Voltage O N
DifHz ASG Difference Frequency O N
DifAng ASG Difference Phase Angle O Y
LivDeaMod ING Live Dead Mode O N
DeaLinVal ASG Dead Line Value O N
LivLinVal ASG Live Line Value O N
DeaBusVal ASG Dead Bus Value O N
LivBusVal ASG Live Bus Value O N
PlsTmms ING Close Pulse Time O N
BkrTmms ING Closing time of breaker O N
420
6 F 2 S 0 8 5 1
GGIO class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind1 SPS General indication (binary input) O Y
Ind2 SPS General indication (binary input) O Y
Ind3 SPS General indication (binary input) O Y
Ind4 SPS General indication (binary input) O Y
Ind5 SPS General indication (binary input) O Y
Ind6 SPS General indication (binary input) O Y
Ind7 SPS General indication (binary input) O Y
Ind8 SPS General indication (binary input) O Y
Ind9 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
:
:
:
Ind64 SPS General indication (binary input) O Y
421
6 F 2 S 0 8 5 1
GGIO_GOOSE class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Loc SPS Local operation O N
OpCntRs INC Resetable operation counter O N
Measured values
AnIn MV Analogue input O N
Controls
SPCSO SPC Single point controllable status output O N
DPCSO DPC Double point controllable status output O N
ISCSO INC Integer status controllable status output O N
Status Information
IntIn INS Integer status input O N
Alm SPS General single alarm O N
Ind1 SPS General indication (binary input) O Y
Ind2 SPS General indication (binary input) O Y
Ind3 SPS General indication (binary input) O Y
Ind4 SPS General indication (binary input) O Y
Ind5 SPS General indication (binary input) O Y
Ind6 SPS General indication (binary input) O Y
Ind7 SPS General indication (binary input) O Y
Ind8 SPS General indication (binary input) O Y
Ind9 SPS General indication (binary input) O Y
Ind10 SPS General indication (binary input) O Y
Ind11 SPS General indication (binary input) O Y
Ind12 SPS General indication (binary input) O Y
Ind13 SPS General indication (binary input) O Y
Ind14 SPS General indication (binary input) O Y
Ind15 SPS General indication (binary input) O Y
Ind16 SPS General indication (binary input) O Y
MMXU class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
Measured values
TotW MV Total Active Power (Total P) O N
TotVAr MV Total Reactive Power (Total Q) O N
TotVA MV Total Apparent Power (Total S) O N
TotPF MV Average Power factor (Total PF) O N
Hz MV Frequency O Y
PPV DEL Phase to phase voltages (VL1VL2, ) O Y
PhV WYE Phase to ground voltages (VL1ER, ) O Y
A WYE Phase currents (IL1, IL2, IL3) O Y
W WYE Phase active power (P) O N
VAr WYE Phase reactive power (Q) O N
VA WYE Phase apparent power (S) O N
PF WYE Phase power factor O N
Z WYE Phase Impedance O N
422
6 F 2 S 0 8 5 1
MSQI class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
EEHealth INS External equipment health (external sensor) O N
EEName DPL External equipment name plate O N
Measured values
SeqA SEQ Positive, Negative and Zero Sequence Current C Y
SeqV SEQ Positive, Negative and Zero Sequence Voltage C Y
DQ0Seq SEQ DQ0 Sequence O N
ImbA WYE Imbalance current O N
ImbNgA MV Imbalance negative sequence current O N
ImbNgV MV Imbalance negative sequence voltage O N
ImbPPV DEL Imbalance phase-phase voltage O N
ImbV WYE Imbalance voltage O N
ImbZroA MV Imbalance zero sequence current O N
ImbZroV MV Imbalance zero sequence voltage O N
MaxImbA MV Maximum imbalance current O N
MaxImbPPV MV Maximum imbalance phase-phase voltage O N
MaxImbV MV Maximum imbalance voltage O N
Condition C: At least one of either data shall be used.
XCBR class
Attribute Name Attr. Type Explanation T M/O GRZ100
LNName Shall be inherited from Logical-Node Class (see IEC 61850-7-2)
Data
Common Logical Node Information
LN shall inherit all Mandatory Data from Common Logical Node Class M
Loc SPS Local operation (local means without substation automation
communication, hardwired direct control)
M Y
EEHealth INS External equipment health O N
EEName DPL External equipment name plate O N
OpCnt INS Operation counter M Y
Controls
Pos DPC Switch position M Y
BlkOpn SPC Block opening M Y
BlkCls SPC Block closing M Y
ChaMotEna SPC Charger motor enabled O N
Metered Values
SumSwARs BCR Sum of Switched Amperes, resetable O N
Status Information
CBOpCap INS Circuit breaker operating capability M Y
POWCap INS Point On Wave switching capability O N
MaxOpCap INS Circuit breaker operating capability when fully charged O N
423
6 F 2 S 0 8 5 1
SPS class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal BOOLEAN ST dchg TRUE | FALSE M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV TRUE | FALSE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
INS class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
stVal INT32 ST dchg M Y(*3)
q Quality ST qchg M Y
t TimeStamp ST M Y
Substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
(*3): ENUM type is also used.
424
6 F 2 S 0 8 5 1
ACT class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
phsA BOOLEAN ST dchg O Y
phsB BOOLEAN ST dchg O Y
phsC BOOLEAN ST dchg O Y
neut BOOLEAN ST dchg O N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
operTm TimeStamp CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
ACD class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
status
general BOOLEAN ST dchg M Y
dirGeneral ENUMERATED ST dchg unknown | forward | backward |
both
M Y
phsA BOOLEAN ST dchg GC_2 (1) Y
dirPhsA ENUMERATED ST dchg unknown | forward | backward GC_2 (1) Y
phsB BOOLEAN ST dchg GC_2 (2) Y
dirPhsB ENUMERATED ST dchg unknown | forward | backward GC_2 (2) Y
phsC BOOLEAN ST dchg GC_2 (3) Y
dirPhsC ENUMERATED ST dchg unknown | forward | backward GC_2 (3) Y
neut BOOLEAN ST dchg GC_2 (4) N
dirNeut ENUMERATED ST dchg unknown | forward | backward GC_2 (4) N
q Quality ST qchg M Y
t TimeStamp ST M Y
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 13
425
6 F 2 S 0 8 5 1
MV class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
measured values
instMag AnalogueValue MX O N
mag AnalogueValue MX dchg M Y
range ENUMERATED MX dchg normal | high | low | high-high | low-low
|
O N
q Quality MX qchg M Y
t TimeStamp MX M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal AnalogueValue SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
units Unit CF see Annex A O Y
db INT32U CF 0 100 000 O N
zeroDb INT32U CF 0 100 000 O N
sVC ScaledValueConfig CF AC_SCAV N
rangeC RangeConfig CF GC_CON N
smpRate INT32U CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
426
6 F 2 S 0 8 5 1
CMV class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
measured values
instCVal Vector MX O N
cVal Vector MX dchg M Y
range ENUMERATED MX dchg normal | high | low | high-high | low-low
|
O N
q Quality MX qchg M Y
t TimeStamp MX M Y
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal Vector SV PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
units Unit CF see Annex A O Y
db INT32U CF 0 100 000 O N
zeroDb INT32U CF 0 100 000 O N
rangeC RangeConfig CF GC_CON N
magSVC ScaledValueConfig CF AC_SCAV N
angSVC ScaledValueConfig CF AC_SCAV N
angRef ENUMERATED CF V | A | other O N
smpRate INT32U CF O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
427
6 F 2 S 0 8 5 1
WYE class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsA CMV GC_1 Y
phsB CMV GC_1 Y
phsC CMV GC_1 Y
neut CMV GC_1 N
net CMV GC_1 N
res CMV GC_1 N
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | Vab | Vbc
| Vca | Vother | Aother
O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
Delta class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
phsAB CMV GC_1 Y
phsBC CMV GC_1 Y
phsCA CMV GC_1 Y
DataAttribute
configuration, description and extension
angRef ENUMERATED CF Va | Vb | Vc | Aa | Ab | Ac | Vab | Vbc
| Vca | Vother | Aother
O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
428
6 F 2 S 0 8 5 1
SEQ class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
Data
c1 CMV M Y
c2 CMV M Y
c3 CMV M Y
DataAttribute
measured attributes
seqT ENUMERATED MX pos-neg-zero | dir-quad-zero M Y
configuration, description and extension
phsRef ENUMERATED CF A | B | C | O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 21
429
6 F 2 S 0 8 5 1
SPC class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O Y
ctlNum INT8U_RO CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M Y
Cancel Cancel CO AC_CO_SBO_N_M
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
N
stVal BOOLEAN ST dchg FALSE | TRUE AC_ST Y
q Quality ST qchg AC_ST Y
t TimeStamp ST AC_ST Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal BOOLEAN SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31
430
6 F 2 S 0 8 5 1
DPC class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal BOOLEAN CO off (FALSE) | on (TRUE) AC_CO_M N
operTm TimeStamp CO AC_CO_O N
origin Originator_RO CO, ST AC_CO_O N
ctlNum INT8U_RO CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M N
Cancel Cancel CO AC_CO_SBO_N_M
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
N
stVal CODED_ENUM ST dchg intermediate-state | off | on | bad-state M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal CODED_ENUM SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
pulseConfig PulseConfig CF AC_CO_O N
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31
431
6 F 2 S 0 8 5 1
INC class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
control and status
ctlVal INT32 CO AC_CO_M Y(*4)
operTm TimeStamp CO AC_CO_O N
origin Originator CO, ST AC_CO_O N
ctlNum INT8U CO, ST 0..255 AC_CO_O N
SBO VISIBLE STRING65 CO AC_CO_SBO_N_M N
SBOw SBOW CO AC_CO_SBOW_E_M N
Oper Oper CO AC_CO _M N
Cancel Cancel CO AC_CO_SBO_N_M
and
AC_CO_SBOW_E_M
and
AC_CO_TA_E_M
N
stVal INT32 ST dchg M Y
q Quality ST qchg M Y
t TimeStamp ST M Y
stSeld BOOLEAN ST dchg AC_CO_O N
substitution
subEna BOOLEAN SV PICS_SUBST N
subVal INT32 SV FALSE | TRUE PICS_SUBST N
subQ Quality SV PICS_SUBST N
subID VISIBLE STRING64 SV PICS_SUBST N
configuration, description and extension
CtlModel CtlModels CF M Y
sboTimeout INT32U CF AC_CO_O N
sboClass SboClasses CF AC_CO_O N
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 (maxVal minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 31
(*4): ENUM type is used.
432
6 F 2 S 0 8 5 1
ING class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setVal INT32 SP AC_NSG_M Y(*3)
setVal INT32 SG, SE AC_SG_M N
configuration, description and extension
minVal INT32 CF O N
maxVal INT32 CF O N
stepSize INT32U CF 1 (maxVal minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 39
(*3): ENUM type is also used.
ASG class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setMag AnalogueValue SP AC_NSG_M Y
setMag AnalogueValue SG, SE AC_SG_M N
configuration, description and extension
units Unit CF see Annex A O Y
sVC ScaledValueConfig CF AC_SCAV Y
minVal AnalogueValue CF O N
maxVal AnalogueValue CF O N
stepSize AnalogueValue CF 1 (maxVal minVal) O N
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 42
433
6 F 2 S 0 8 5 1
CURVE class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
setting
setCharact ENUMERATED SP AC_NSG_M Y
setParA FLOAT32 SP AC_NSG_O N
setParB FLOAT32 SP AC_NSG_O N
setParC FLOAT32 SP AC_NSG_O N
setParD FLOAT32 SP AC_NSG_O N
setParE FLOAT32 SP AC_NSG_O N
setParF FLOAT32 SP AC_NSG_O N
setCharact ENUMERATED SG, SE AC_SG_M N
setParA FLOAT32 SG, SE AC_SG_O N
setParB FLOAT32 SG, SE AC_SG_O N
setParC FLOAT32 SG, SE AC_SG_O N
setParD FLOAT32 SG, SE AC_SG_O N
setParE FLOAT32 SG, SE AC_SG_O N
setParF FLOAT32 SG, SE AC_SG_O N
configuration, description and extension
d VISIBLE STRING255 DC Text O N
dU UNICODE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 42
434
6 F 2 S 0 8 5 1
DPL class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
hwRev VISIBLE STRING255 DC O N
swRev VISIBLE STRING255 DC O Y
serNum VISIBLE STRING255 DC O N
model VISIBLE STRING255 DC O Y
location VISIBLE STRING255 DC O N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45
LPL class
Attribute
Name
Attribute Type FC TrgOp Value/Value Range M/O/C GRZ100
DataName Inherited from Data Class (see IEC 61850-7-2)
DataAttribute
configuration, description and extension
vendor VISIBLE STRING255 DC M Y
swRev VISIBLE STRING255 DC M Y
d VISIBLE STRING255 DC M Y
dU UNICODE STRING255 DC O N
configRev VISIBLE STRING255 DC AC_LN0_M Y
ldNs VISIBLE STRING255 EX shall be included in LLN0 only;
for example "IEC 61850-7-4:2003"
AC_LN0_EX N
lnNs VISIBLE STRING255 EX AC_DLD_M N
cdcNs VISIBLE STRING255 EX AC_DLNDA_M N
cdcName VISIBLE STRING255 EX AC_DLNDA_M N
dataNs VISIBLE STRING255 EX AC_DLN_M N
Services
As defined in Table 45
435
6 F 2 S 0 8 5 1
PICS: IEC61850 ASCI Conformance Statement
Client/
subscriber
Server/
publisher
GRZ10
0
Remarks
Client-server roles
B11 Server side (of TWO-PARTY-
APPLICATION-ASSOCIATION)
- c1 Y
B12 Client side of (TWO-PARTY-
APPLICATION-ASSOCIATION)
c1 - -
SCSMs supported
B21 SCSM: IEC61850-8-1 used Y
B22 SCSM: IEC61850-9-1 used N
B23 SCSM: IEC61850-9-2 used N
B24 SCSM: other -
Generic substation event model (GSE)
B31 Publisher side - O Y
B32 Subscriber side O - Y
Transmission of sampled value model (SVC)
B41 Publisher side - O N
B42 Subscriber side O - N
If Server side (B11) supported
M1 Logical device c2 c2 Y
M2 Logical node c3 c3 Y
M3 Data c4 c4 Y
M4 Data set c5 c5 Y
M5 Substitution O O N
M6 Setting group control O O Y
Reporting
M7 Buffered report control O O Y
M7-1 sequence-number Y
M7-2 report-time-stamp Y
M7-3 reason-for-inclusion Y
M7-4 data-set-name Y
M7-5 data-reference Y
M7-6 buffer-overflow Y
M7-7 entryID Y
M7-8 BufTm Y
M7-9 IntgPd Y
M7-10 GI Y
Unbuffered report control O O Y
M8-1 sequence-number Y
M8-2 report-time-stamp Y
M8-3 reason-for-inclusion Y
M8-4 data-set-name Y
M8-5 data-reference Y
M8-6 BufTm Y
M8-7 IntgPd Y
M8-8 GI Y
Logging O O N
M9 Log control O O N
M9-1 IntgPd N
M10 Log O O N
M11 Control M M Y
If GSE (B31/B32) is supported
GOOSE O O Y
M12-1 entryID
M12-2 DataRefInc
436
6 F 2 S 0 8 5 1
M13 GSSE O O N
If SVC (B41/B42) is supported
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File Transfer O O Y
Server
S1 ServerDirectory M Y
Application association
S2 Associate M M Y
S3 Abort M M Y
S4 Release M M Y
Logical device
S5 LogicalDeviceDirectory M M Y
Logical node
S6 LogicalNodeDirectory M M Y
S7 GetAllDataValues O M Y
Data
S8 GetDataValues M M Y
S9 SetDataValues O O N
S10 GetDataDirectory O M Y
S11 GetDataDefinition O M Y
Data set
S12 GetDataSetValues O M Y
S13 SetDataSetValues O O N
S14 CreateDataSet O O N
S15 DeleteDataSet O O N
S16 GetDataSetDirectory O O Y
Substitution
S17 SetDataValues M M N
Setting group control
S18 SelectActiveSG O O Y
S19 SelectEditSG O O N
S20 SetSGValues O O N
S21 ConfirmEditSGValues O O N
S22 GetSGValues O O N
S23 GetSGCBValues O O Y
Reporting
Buffered report control block (BRCB)
S24 Report c6 c6 Y
S24-1 data-change (dchg) Y
S24-2 quality-change (qchg) Y
S24-3 data-update (dupd) N
S25 GetBRCBValues c6 c6 Y
S26 SetBRCBValues c6 c6 Y
Unbuffered report control block (BRCB)
S27 Report c6 c6 Y
S27-1 data-change (dchg) Y
S27-2 quality-change (qchg) Y
S27-3 data-update (dupd) N
S28 GetURCBValues c6 c6 Y
S29 SetURCBValues c6 c6 Y
Logging
Log control block
S30 GetLCBValues M M N
S31 SetLCBValues O M N
Log
437
6 F 2 S 0 8 5 1
S32 QueryLogByTime c7 M N
S33 QueryLogAfter c7 M N
S34 GetLogStatusValues M M N
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
S35 SendGOOSEMessage c8 c8 Y
S36 GetGoReference O c9 N
S37 GetGOOSEElementNumber O c9 N
S38 GetGoCBValues O O Y
S39 SetGoCBValues O O Y
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage c8 c8 N
S41 GetGsReference O c9 N
S42 GetGSSEElementNumber O c9 N
S43 GetGsCBValues O O N
S44 SetGsCBValues O O N
Transmission of sampled value model (SVC)
Multicast SVC
S45 SendMSVMessage c10 c10 N
S46 GetMSVCBValues O O N
S47 SetMSVCBValues O O N
Unicast SVC
S48 SendUSVMessage c10 c10 N
S49 GetUSVCBValues O O N
S50 SetUSVCBValues O O N
Control
S51 Select M O N
S52 SelectWithValue M O N
S53 Cancel O O N
S54 Operate M M Y
S55 CommandTermination M O Y
S56 TimeActivatedOperate O O N
File Transfer
S57 GetFile O M Y
S58 SetFile O O N
S59 DeleteFile O O N
S60 GetFileAttributeValues O O Y
Time
T1 Time resolution of internal clock 1ms
T2 Time accuracy of internal clock 1ms T1
T3 Supported TimeStamp resolution 1ms
M Mandatory
O Optional
c1 shall be M if support for LOGICAL-DEVICE model has been declared.
c2 shall be M if support for LOGICAL-NODE model has been declared.
c3 shall be M if support for DATA model has been declared.
c4 shall be M if support for DATA-SET, Substitution, Report, Log Control, or Time model has been declared.
c5 shall be M if support for Report, GSE, or SV models has been declared.
c6 shall declare support for at least one (BRCB or URCB)
c7 shall declare support for at least one (QueryLogByTime or QueryLogAfter).
c8 shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage)
c9 shall declare support if TWO-PARTY association is available.
c10 shall declare support for at least one (SendMSVMessage or SendUSVMessage).
438
6 F 2 S 0 8 5 1
PICS for A-Profile support
Client Server A-Profile
shortcut
Profile Description
F/S F/S
GRZ100 Remarks
A1 Client/server A-Profile c1 c1 Y
A2 GOOSE/GSE
management A-Profile
c2 c2 Y
A3 GSSE A-Profile c3 c3 N
A4 TimeSync A-Profile c4 c4 Y
c1 Shall be m if support for any service specified in Table 2 are declared within the ACSI basic conformance statement.
c2 Shall be m if support for any service specified in Table 6 are declared within the ACSI basic conformance statement.
c3 Shall be m if support for any service specified in Table 9 are declared within the ACSI basic conformance statement.
c4 Support for at least one other A-Profile shall be declared (e.g. in A1-A3) in order to claim conformance to IEC 61850-8-1.
PICS for T-Profile support
Client Server A-Profile
shortcut
Profile Description
F/S F/S
GRZ100 Remarks
T1 TCP/IP T-Profile c1 c1 Y
T2 OSI T-Profile c2 c2 N
T3 GOOSE/GSE T-Profile c3 c3 Y
T4 GSSE T-Profile c4 c4 N
T5 TimeSync T-Profile o o Y
c1 Shall be m if support for A1 is declared. Otherwise, shall be 'i'.
c2 Shall be o if support for A1 is declared. Otherwise, shall be 'i'.
c3 Shall be m if support for A2 is declared. Otherwise, shall be 'i.
c4 Shall be m if support for A3 is declared. Otherwise, shall be 'i.
439
6 F 2 S 0 8 5 1
MMS InitiateRequest general parameters
Client-CR Server-CR
InitiateRequest
Base F/S Value/range Base F/S Value/range
GRZ100
InitiateRequest
localDetailCalling m m m m Y
proposedMaxServOutstandingCalling m m 1 or greater m m 1 or greater Y
proposedMaxServOustandingCalled m m 1 or greater m m 1 or greater Y
initRequestDetail m m m m Y
InitiateRequestDetail
proposedVersionNumber m m shall be 2.1 m m shall be 2.1 Y
proposedParameterCBB m m m m Y
servicesSupportedCalling m m m m Y
additionalSupportedCalling c1 x c1 x N
additionalCbbSupportedCalling c1 x c1 x N
privilegeClassIdentityCalling c1 x c1 x N
c1 Conditional upon Parameter CBB CSPI
MMS InitiateResponse general parameters
Client-CR Server-CR
InitiateRequest
Base F/S Value/range Base F/S Value/range
GRZ100
InitiateResponse
localDetailCalled m m m m Y
negotiatedMaxServOutstandingCalling m m 1 or greater m m 1 or greater Y
negotiatedMaxServOustandingCalled m m 1 or greater m m 1 or greater Y
initResponseDetail m m m m Y
InitiateResponseDetail
negotiatedVersionNumber m m shall be 2.1 m m shall be 2.1 Y
negotiatedParameterCBB m m m m Y
servicesSupportedCalled m m m m Y
additionalSupportedCalled c1 x c1 x N
additionalCbbSupportedCalled c1 x c1 x N
privilegeClassIdentityCalled c1 x c1 x N
c1 Conditional upon Parameter CBB CSPI
440
6 F 2 S 0 8 5 1
MMS service supported conformance table
Client-CR Server-CR
MMS service supported CBB
Base F/S Value/range Base F/S Value/range
GRZ100
status o o o m Y
getNameList o o o c1 Y
identify o o m m Y
rename o o o o N
read o o o c2 Y
write o o o c3 Y
getVariableAccessAttributes o o o c4 Y
defineNamedVariable o o o o N
defineScatteredAccess o i o i N
getScatteredAccessAttributes o i o i N
deleteVariableAccess o o o o N
defineNamedVariableList o o o o N
getNamedVariableListAttributes o o o c5 Y
deleteNamedVariableList o o o c6 N
defineNamedType o i o i N
getNamedTypeAttributes o i o i N
deleteNamedType o i o i N
input o i o i N
output o i o i N
takeControl o i o i N
relinquishControl o i o i N
defineSemaphore o i o i N
deleteSemaphore o i o i N
reportPoolSemaphoreStatus o i o i N
reportSemaphoreStatus o i o i N
initiateDownloadSequence o i o i N
downloadSegment o i o i N
terminateDownloadSequence o i o i N
initiateUploadSequence o i o i N
uploadSegment o i o i N
terminateUploadSequence o i o i N
requestDomainDownload o i o i N
requestDomainUpload o i o i N
loadDomainContent o i o i N
storeDomainContent o i o i N
deleteDomain o i o i N
getDomainAttributes o o o c14 Y
createProgramInvocation o i o i N
441
6 F 2 S 0 8 5 1
Client-CR Server-CR
MMS service supported CBB
Base F/S Value/range Base F/S Value/range
GRZ100
deleteProgramInvocation o i o i N
start o i o i N
stop o i o i N
resume o i o i N
reset o i o i N
kill o i o i N
getProgramInvocationAttributes o i o i N
obtainFile o c9 o c9 N
defineEventCondition o i o i N
deleteEventCondition o i o i N
getEventConditionAttributes o i o i N
reportEventConditionStatus o i o i N
alterEventConditionMonitoring o i o i N
triggerEvent o i o i N
defineEventAction o i o i N
deleteEventAction o i o i N
alterEventEnrollment o i o i N
reportEventEnrollmentStatus o i o i N
getEventEnrollmentAttributes o i o i N
acknowledgeEventNotification o i o i N
getAlarmSummary o i o i N
getAlarmEnrollmentSummary o i o i N
readJournal o c13 o c13 N
writeJournal o o o o N
initializeJournal o o o c12 N
reportJournalStatus o i o i N
createJournal o i o i N
deleteJournal o i o i N
fileOpen o c8 o c8 Y
fileRead o c8 o c8 Y
fileClose o c8 o c8 Y
fileRename o i o i N
fileDelete o c9 o c9 N
fileDirectory o c11 o c11 Y
unsolicitedStatus o i o i N
informationReport o c7 o c7 Y
eventNotification o i o i N
attachToEventCondition o i o i N
attachToSemaphore o i o i N
conclude m m m m N
cancel o o o m N
getDataExchangeAttributes o c10 o c10 N
exchangeData o c10 o c10 N
442
6 F 2 S 0 8 5 1
Client-CR Server-CR
MMS service supported CBB
Base F/S Value/range Base F/S Value/range
GRZ100
defineAccessControlList o c10 o c10 N
getAccessControlListAttributes o c10 o c10 N
reportAccessControlledObjects o c10 o c10 N
deleteAccessControlList o c10 o c10 N
alterAccessControl o c10 o c10 N
reconfigureProgramInvocation o c10 o c10 N
c1 Shall be m if logical device or logical node model support is declared in ACSI basic conformance statement.
c2 Shall be m if logical node model support is declared in ACSI basic conformance statement or if support for the MMS
write service is declared.
c3 Shall be m if ACSI support for SetDataValues service is declared or implied.
c4 Shall be m if logical node model support is declared in ACSI basic conformance statement.
c5 Shall be m if data set support is declared in the ACSI basic conformance statement.
c6 Shall be m if support for defineNamedVariableList is declared.
c7 Shall be 'm' if support for ACSI Report or ACSI command termination is declared.
c8 Shall be 'm' if support for ACSI GetFile is declared.
c9 Shall be 'm' if support for ACSI SetFile is declared.
c10 Shall not be present since MMS minor version is declared to be 1.
c11 Shall be 'm' if support for ACSI GetFileAttributeValues is declared.
c12 Shall be 'm' if support for the ACSI log model is declared.
c13 Shall be 'm' if support for the ACSI QueryLogByTime or QueryLogAfter is declared.
c14 Shall be 'm' if support for the ACSI logical device model is declared.
MMS Parameter CBB
Client-CR Server-CR
MMS parameter CBB
Base F/S Value/range Base F/S Value/range
GRZ10
0
STR1 o o o c1 Y
STR2 o o o o N
NEST 1 1 or greater 1 c2 Y(10)
VNAM o o o c1 Y
VADR o o o o N
VALT o o o c1 Y
bit x x x x N
TPY o o o o N
VLIS o c1 o c3 Y
bit x x x x N
bit x x x x N
CEI o i o i N
ACO o c4 o c4 N
SEM o c4 o c4 N
CSR o c4 o c4 N
CSNC o c4 o c4 N
CSPLC o c4 o c4 N
CSPI o c4 o c4 N
c1 Shall be m if ACSI logical node model support declared.
c2 Shall be five(5) or greater if ACSI logical node model support is declared.
c3 Shall be m if ACSI data set, reporting, GOOSE, or logging model support is declared.
c4 Shall not be present. Receiving implementations shall assume not supported.
443
6 F 2 S 0 8 5 1
GetNameList conformance statement
Client-CR Server-CR
GetNameList
Base F/S Value/range Base F/S Value/range
GRZ100
Request
ObjectClass m m m m Y
ObjectScope m m m m Y
DomainName o o m m Y
ContinueAfter o m m m Y
Response+
List Of Identifier m m m m Y
MoreFollows m m m m Y
Response-
Error Type m m m m Y
NOTE Object class vmd' (formerly VMDSpecific in MMS V1.0) shall not appear. If a request contains this ObjectClass,
an MMS Reject shall be issued.
AlternateAccessSelection conformance statement
Not applicable.
VariableAccessSpecification conformance statement
Client-CR Server-CR
VariableAccessSpecification
Base F/S Value/range Base F/S Value/range
GRZ100
listOfVariable o o o c1 Y
variableSpecification o o o c1 Y
alternateAccess o o o c1 Y
variableListName o o o c2 Y
c1 Shall be m if ACSI support for Logical Node Model is declared.
c2 Shall be m if ACSI support for ACSI DataSets, reporting, or logging is declared.
VariableSpecification conformance statement
Client-CR Server-CR
VariableSpecification
Base F/S Value/range Base F/S Value/range
GRZ100
name o o o m Y
address o o o i N
variableDescription o o o i N
scatteredAccessDescription o x o x N
invalidated o x o x N
444
6 F 2 S 0 8 5 1
Read conformance statement
Client-CR Server-CR
Read
Base F/S Value/range Base F/S Value/range
GRZ100
Request
specificationWithResult o o o m Y
variableAccessSpecification m m m m Y
Response
variableAccessSpecification o o o m Y
listOfAccessResult m m m m Y
Write conformance statement
Client-CR Server-CR
Write
Base F/S Value/range Base F/S Value/range
GRZ100
Request
variableAccessSpecification m m m m Y
listOfData m m m m Y
Response
failure m m m m Y
success m m m m Y
InformationReport conformance statement
Client-CR Server-CR
InformationReport
Base F/S Value/range Base F/S Value/range
GRZ100
Request
variableAccessSpecification m m m m Y
listOfAccessResult m m m m Y
GetVariableAccessAttributes conformance statement
Client-CR Server-CR GRZ100 GetVariableAccessAttribute
s Base F/S Value/range Base F/S Value/range
Request
name o o m m Y
address o o m x N
Response
mmsDeletable m m m m Y
address o x o x N
typeSpecification m m m m Y
DefineNamedVariableList conformance statement
Not applicable.
445
6 F 2 S 0 8 5 1
GetNamedVariableListAttributes conformance statement
Client-CR Server-CR
GetNamedVariableListAttributes
Base F/S Value/range Base F/S Value/range
GRZ100
Request
ObjectName m m m m Y
Response
mmsDeletable m m m m Y
listOfVariable m m m m Y
variableSpecification m m m m Y
alternateAccess o m o i N
DeleteNamedVariableList conformance statement
Not applicable.
ReadJournal conformance statement
Not applicable.
JournalEntry conformance statement
Not applicable.
InitializeJournal conformance statement
Not applicable.
FileDirectory conformance statement
Client-CR Server-CR
FileDirectory
Base F/S Value/range Base F/S Value/range
GRZ100
Request
filespecification o o m m Y
continueAfter o o m m Y
Response+
listOfDirectoryEntry m m m m Y
MoreFollows m m m m Y
FileOpen conformance statement
Client-CR Server-CR
FileOpen
Base F/S Value/range Base F/S Value/range
GRZ100
Request
filename m m m m Y
initialPosition o o m m Y
Response+
frsmID m m m m Y
fileAttributes m m m m Y
446
6 F 2 S 0 8 5 1
FileRead conformance statement
Client-CR Server-CR
FileRead
Base F/S Value/range Base F/S Value/range
GRZ100
Request
frsmID m m m m Y
Response+
fileData m m m m Y
MoreFollows m m m m Y
FileClose conformance statement
Client-CR Server-CR
FileClose
Base F/S Value/range Base F/S Value/range
GRZ100
Request
frsmID m m m m Y
Response+ m m m m Y
GOOSE conformance statement
Subscriber Publisher Value/comment GRZ100
GOOSE Services c1 c1 Y
SendGOOSEMessage m m Y
GetGoReference o c3 N
GetGOOSEElementNumber o c4 N
GetGoCBValues o o Y
SetGoCBValues o o Y
GSENotSupported c2 c5 N
GOOSE Control Block (GoCB) o o Y
c1 Shall be m if support is declared within ACSI basic conformance statement.
c2 Shall be m if ACSI basic conformance support for either GetGoReference or GetGOOSEElementNumber is declared.
c3 Shall be m if support for ACSI basic conformance of GetGoReference is declared.
c4 Shall be m if support for ACSI basic conformance of GetGOOSEElementNumber.
c5 Shall be m if no support for ACSI basic conformance of GetGOOSEElementNumber is declared.
GSSE conformance statement
Not applicable.
447
6 F 2 S 0 8 5 1
Appendix Q
Inverse Time Characteristics
448
6 F 2 S 0 8 5 1
IEC/UK Inverse Curves (NI)
(Time Multiplier TMS = 0.1 - 1.5)
0.1
1
10
100
1 10 100
Current (Multiple of Setting)
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
)
1.
0.5
0.1
0.2
1.5
TMS
IEC/UK Inverse Curves (VI)
(Time Multiplier TMS = 0.1 - 1.5)
0.01
0.1
1
10
100
1 10 100
Current (Multiple of Setting)
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
)
1.0
0.5
0.2
0.1
1.5
TMS
Normal Inverse Very Inverse
449
6 F 2 S 0 8 5 1
IEC/UK Inverse Curves (EI)
(Time Multiplier TMS = 0.1 - 1.5)
0.01
0.1
1
10
100
1000
1 10 100
Current (Multiple of Setting)
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
)
1.0
0.5
0.2
0.1
1.5
TMS
UK Inverse Curves (LTI)
(Time Multiplier TMS = 0.1 - 1.5)
0.1
1
10
100
1000
1 10 100
Current (Multiple of Setting)
O
p
e
r
a
t
i
n
g
T
i
m
e
(
s
)
1.0
0.2
0.5
0.1
1.5
TMS
Extremely Inverse Long Time Inverse
450
6 F 2 S 0 8 5 1
451
6 F 2 S 0 8 5 1
Appendix R
Failed Module Tracing and Replacement
452
6 F 2 S 0 8 5 1
1. Failed module tracing and its replacement
If the ALARM LED is ON, the following procedure is recommended. If not repaired, contact
the vendor.
ALARM LED ON?
Any LCD messages?
Locate the failed module.
Module replacement
If both IN SERVICE LED and ALARM LED are
OFF, check the followings.
Check: Is DC supply voltage available with the correct
polarity and of adequate magnitude, and
connected to the correct terminals?
No
No failure
Locate the failed module referring to Table R-1.
Caution: Check that the replacement module has an
identical module name (VCT, SPM, IO1,
IO2, etc.) and hardware type-form as the
failed module. Furthermore, the SPM
module must have the same software
name and version. Refer to Section
4.2.5.1.
Countermeasure
As shown in the table, some of the messages cannot
identify the fault location definitely but suggest plural
possible failure locations. In these cases, the failure
location is identified by replacing the suggested
failed modules with spare modules one by one until
the "ALARM" LED is turned off.
DC supply OFF
DC supply ON
ALARM LED OFF?
No
Contact the vendor.
End
No
Not displayed
Press [VIEW] key
Contact the vendor.
Not displayed
Press [VIEW] key
Yes
Yes
Procedure
453
6 F 2 S 0 8 5 1
Table R-1 LCD Message and Failure Location
Message Failure location
VCT SPM IO1 IO2 IO3 IO4 HMI Channel Discon-
nector
AC
cable
VT LAN
cable/
network
PLC,
IEC61850
data
Checksum err
ROM data err
ROM-RAM err
SRAM err
CPU err
Invalid err
NMI err
BU-RAM err
EEPROM err
A/D err
Sampling err
V0 err (2) (1) (2)
V2 err (2) (1) (2)
I0 err (2) (1) (2)
CT err (2) (2) (1)
DIO err (2) (1) (1) (1) (1)
RSM err (1) (2)
LCD err
Trip output err
DS fail (2) (2) (1)
Ch. fail (2) (2) (2) (1)
VT fail (2) (1)
DC supply off
RTC err
PCI err
LAN err
GOOSE stop (2) (1)
Ping err (2) (1)
PLC stop
MAP stop
No-working of
LCD
(2) (1)
The location marked with (1) has a higher probability than the location marked with (2).
454
6 F 2 S 0 8 5 1
2. Methods of Replacing the Modules
CAUTION When handling a module, take anti-static measures such as wearing an
earthed wrist band and placing modules on an earthed conductive mat.
Otherwise, many of the electronic components could suffer damage.
CAUTION After replacing the SPM module, check all of the settings including the data
related the PLC, IEC103 and IEC61850, etc. are restored the original settings.
The initial replacement procedure is as follows:
1). Switch off the DC power supply.
Hazardous voltage may remain in the DC circuit just after switching off the
DC power supply. It takes about 30 seconds for the voltage to discharge.
2). Remove the front panel cover.
3). Open the front panel.
Open the front panel of the relay by unscrewing the binding screw located on the left side of
the front panel.
Case size : 1/2inchs
4). Detach the holding bar.
Detach the module holding bar by unscrewing the binding screw located on the left side of
the bar.
WARNING
455
6 F 2 S 0 8 5 1
5). Unplug the cables.
Unplug the ribbon cable running among the modules by nipping the catch (in case of black
connector) and by pushing the catch outside (in case of gray connector) on the connector.
6). Pull out the module.
Pull out the failure module by pulling up or down the top and bottom levers (white).
7). Insert the replacement module.
Insert the replacement module into the same slots where marked up.
.
8). Do the No.5 to No.1 steps in reverse order.
CAUTION Supply DC power after checking that all the modules are in their original
positions and the ribbon cables are plugged in. If the ribbon cables are not
plugged in enough (especially the gray connectors), the module could suffer
damage.
Gray connector
Black connector
SPM module
Details of the gray connector on modules (top side)
Not enough
Enough
456
6 F 2 S 0 8 5 1
9). Lamp Test
RESET key is pushed 1 second or more by LCD display off.
It checks that all LCDs and LEDs light on.
10). Check the automatic supervision functions.
LCD not display Auto-supervision screens in turn, and Event Records
Checking the IN SERVICE LED light on and ALARM LED light off.
457
6 F 2 S 0 8 5 1
Appendix S
Ordering
458
6 F 2 S 0 8 5 1
Distance Protection Relay
Relay Type:
Distance protection relay GRZ100
Relay Model:
-Model200: With autoreclose for single breaker scheme
18 BIs, 23 BOs, 6 trip BOs
201
-Model300: With autoreclose for one and a half breaker scheme
18 BIs, 23 BOs, 6 trip BOs
24 BIs, 41 BOs, 6 trip BOs
301
303
Ratings:
1A, 50Hz, 110V/125V
1A, 60Hz, 110V/125V
5A, 50Hz, 110V/125V
5A, 60Hz, 110V/125V
1A, 50Hz, 220V/250V
1A, 60Hz, 220V/250V
5A, 50Hz, 220V/250V
5A, 60Hz, 220V/250V
1A, 50Hz, 48V/54V/60Vdc
1A, 60Hz, 48V/54V/60Vdc
5A, 50Hz, 48V/54V/60Vdc
5A, 60Hz, 48V/54V/60Vdc
1A, 50Hz, 24V/30Vdc
1A, 60Hz, 24V/30Vdc
5A, 50Hz, 24V/30Vdc
5A, 60Hz, 24V/30Vdc
1
2
3
4
5
6
7
8
A
B
C
D
E
F
G
H
Integral communication interface:
None (external comm. only) 0
Communications:
RS485 + 100BASE-TX (RJ-45 connector)
RS485 + 100BASE-FX (SC connector)
Fibre optic (ST connector) + 100BASE-FX (SC connector)
Dual 100BASE-FX (SC connector) :LAN port x 2
A
B
E
G
Miscellaneous:
None 0
LED label:
Standard
Option: User configurable LED label
None
J
GRZ100 D 0
459
6 F 2 S 0 8 5 1
Version-up Records
Version
No.
Date Revised Section Contents
0.0 Oct. 17, 2006 -- First issue
0.1 Nov. 14, 2006 3.3.6, 3.3.7
3.3.8
3.3.10
3.4.3
4.2.6.4
6.7.2
Appendices
Added Sections 3.3.6 and 3.3.7.
Modified Table 3.3.8.1.
Modified the setting range table.
Modified Table 3.4.3.1.
Modified the description and the LCD sample screen.
Modified Table 6.7.2.1.
Modified Appendix P.
0.2 Mar. 2, 2007 2.4.1.3
3.2.1
3.4.1, 3.4.3
4.2.4.4, 4.2.6.4
4.4.1, 4.5
6.5.1.1
6.7.2
Appendices
Modified the description of Blinder setting and Figures 2.4.1.12 and 2.4.1.13.
Modified Table 3.2.1.2.
Modified the description.
Modified the description.
Modified the description.
Modified the description.
Modified Table 6.7.2.1.
Modified Appendix B, C, E, K, M, N and P.
0.3 Mar.23, 2007 2.4.1.3
2.7.1, 2.7.3, 2.7.4
2.7.5
3.4.1
4.2.3.1, 4.2.6.5,
4.2.6.7
5.5
6.7.2
Appendices
Modified the description of Blinder setting and Figures 2.4.1.12.
Modified the description.
Modified the setting range table.
Modified the description.
Modified the description and the LCD sample screen.
Modified the description and added Figure 5.5.1.
Modified Table 6.7.2.1.
Modified Appendix E H, and added Appendix P.
0.4 Sep. 11, 2007 2.4.10
2.4.14
2.5.1
3.1.4.1
6.7.3
Appendices
Added Figure 2.4.10.2.
Modified Figure 2.4.14.1.
Modified the description of Reactance element.
Modified the description.
Modified the description of CAUTION.
Added Appendix Q. (Old QR, RS)
Modified Appendix G, K, M, N and R.
0.5 May 30, 2008 2.4.6
2.7.1, 6.5.5
4.2.7.1
6.5.1.1
Appendices
Modified the description of Setting.
Added Note.
Modified the description of THMRST.
Modified the description and Figure 6.5.1.2.
Modified Appendix B, H and K.
0.6 Jul. 31, 2009 Precautions
2.4, 2.5
2.4.1.3
2.4.3.9
2.4.4
2.4.5
2.4.7
2.4.9.2
2.4.11
2.4.13
4.2.2,4.2.6.2,4.2.7
4.2.6.4
Appendices
Modified the description of Disposal.
Delete Section 2.5 and insert the characteristics of measuring elements to
Section 2.4.
Modified the description(add Note) and Figure 2.4.1.12
Modified Figure 2.4.3.11.
Modified Figure 2.4.4.1
Modified Figure 2.4.5.1.
Modified Figure 2.4.7.1.
Modified Figure 2.4.9.9.
Modified Figure 2.4.11.1.
Modified Figure 2.4.13.1.
Modified the description. (Added the explanation of password for test screen.)
Modified the description. (Add DEADT.)
Modified Appendix B, D, E, H, K and S.
460
6 F 2 S 0 8 5 1
Version
No.
Date Revised Section Contents
0.7 Dec. 17, 2009 Precautions
2.4.3.2
2.4.3.3
2.4.3.5
Modified the description of Disposal.
Modified Figure 2.4.3.2.
Modified Figure 2.4.3.3
Modified the description.(Change CB-OR=1 to CB-OR=0)
0.8 Oct. 15, 2010 3.1.1
3.1.3
4.2.1
4.2.6.4
Appendices
Modified Figures 3.1.1.3 and 3.1.1.4.
Modified Figure 3.1.3.1.
Added Displays in communication port status.
Added items PSWTM and RLNSCH.
Modified Appendix B, G, H, K, P and S.