ACW Booster Pump Calculation
ACW Booster Pump Calculation
ACW Booster Pump Calculation
Date:
PROJECT:
PPD BY :
SL NO DESCRIPTION
1>
DOC NO:
CKD BY:
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
VELOCITY
Equivalent
Length
(mtrs)
Discharge
(m3/hr)
m/sec
feet/ sec
560
2.046
6.711
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
PUMP Discharge(A-B)
PIPE
0.3111
1.020
BF VALVE
0.3111
1.020
560
2.046
6.711
0.455
0.097
CHECK VALVE
0.3111
1.020
560
2.046
6.711
1.3
0.277
90 degree bends
0.3111
1.020
560
2.046
6.711
0.39
0.333
0.3111
1.020
560
2.046
6.711
0.78
0.166
Expander 250x300
0.3111
1.020
560
2.046
6.711
0.0588
0.013
SUB TOTAL
0.139
0.139
0.886
GRAND TOTAL
2>
SECTION B-G'
PIPE
20
0.4412
1.447
1120
2.035
6.674
0.4412
1.447
1120
2.035
6.674
0.4412
1.447
1120
2.035
Expander 250x300
0.4412
1.447
1120
2.035
20
1.026
0.263
0.24
0.203
6.674
0.24
0.051
6.674
0.0588
0.012
SUB TOTAL
0.263
0.266
GRAND TOTAL
2>
SECTION G'-1
PIPE
60
0.3111
1.020
90 degree bends
0.3111
1.020
60
430
1.571
5.153
430
1.571
5.153
SUB TOTAL
0.528
0.733
0.39
0.733
0.294
GRAND TOTAL
1.028
2.000
3>
0.294
SECTION G-H
PIPE
0.3906
1.281
1025
2.376
7.793
BF VALVE
0.3906
1.281
1025
2.376
7.793
0.3906
1.281
1025
2.376
REDUCER (450x400)
0.4412
1.447
1025
1.862
241454199.xls.ms_office
0.101
0.325
0.093
7.793
0.78
0.224
6.108
0.0138
0.002
SL NO DESCRIPTION
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
Equivalent
Length
(mtrs)
VELOCITY
Discharge
(m3/hr)
m/sec
feet/ sec
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
SUB TOTAL
GRAND TOTAL
241454199.xls.ms_office
0.101
0.320
0.421
SL NO DESCRIPTION
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
Equivalent
Length
(mtrs)
VELOCITY
Discharge
(m3/hr)
m/sec
feet/ sec
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
4>
30.000
5>
6.000
6>
SECTION I-J
PIPE
0.3906
1.281
1025
2.376
7.793
BF VALVE
0.3906
1.281
1025
2.376
7.793
0.325
0.093
0.3906
1.281
1025
2.376
7.793
0.26
0.075
Expander(400x450)
0.4412
1.447
1025
1.862
6.108
0.0138
0.002
SUB TOTAL
0.101
0.101
0.171
GRAND TOTAL
7>
0.271
SECTION 1-K
PIPE
25
0.1035
0.339
90 degree bends
0.1035
45 degree bends
0.1035
25
40
1.320
4.331
0.339
40
1.320
4.331
0.339
40
1.320
4.331
0.1035
0.339
40
1.320
4.331
0.34
0.030
0.1035
0.339
40
1.320
4.331
0.34
0.060
SUB TOTAL
0.798
0.51
0.000
0.798
0.317
GRAND TOTAL
8>
0.227
1.116
SECTION K-L
PIPE
0.0670
0.220
90 degree bends
0.0670
GATE Valve
0.0670
EXPANDER (65X100)
REDUCER (100X65)
20
1.576
5.168
0.220
20
1.576
5.168
0.54
0.137
0.220
20
1.576
5.168
0.144
0.018
0.1035
0.339
20
0.660
2.166
0.913
0.020
0.1035
0.339
20
0.660
2.166
0.913
0.020
SUB TOTAL
GRAND TOTAL
241454199.xls.ms_office
0.514
0.514
0.195
0.710
SL NO DESCRIPTION
9>
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
Equivalent
Length
(mtrs)
VELOCITY
Discharge
(m3/hr)
m/sec
feet/ sec
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
30.000
10>
11>
SECTION M-N
15.000
PIPE
0.0670
0.220
20
1.576
5.168
90 degree bends
0.0670
0.220
20
1.576
5.168
0.54
0.137
GATE Valve
0.0670
0.220
20
1.576
5.168
0.144
0.018
EXPANDER (65X100)
0.1035
0.339
20
0.660
2.166
0.913
0.020
REDUCER (100X65)
0.1035
0.339
20
0.660
2.166
0.913
0.020
SUB TOTAL
0.514
0.514
0.195
GRAND TOTAL
0.710
2.000
12>
SECTION N-J
PIPE
70
0.1035
0.339
40
1.320
4.331
90 degree bends
0.1035
0.339
70
40
1.320
4.331
0.51
0.272
45 degree bends
0.1035
0.339
40
1.320
4.331
0.272
0.048
0.1035
0.339
40
1.320
4.331
0.34
0.030
0.1035
0.339
40
1.320
4.331
0.34
0.060
SUB TOTAL
2.236
2.236
0.411
GRAND TOTAL
13>
2.647
SECTION J-O
PIPE
32
0.4412
1.447
1025
1.862
6.108
0.4412
1.447
32
1025
1.862
6.108
0.72
0.127
90 degree bends
0.4412
1.447
1025
1.862
6.108
0.36
0.064
SUB TOTAL
GRAND TOTAL
241454199.xls.ms_office
0.356
0.356
0.191
0.547
SL NO DESCRIPTION
14>
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
VELOCITY
Equivalent
Length
(mtrs)
Discharge
(m3/hr)
m/sec
feet/ sec
16
1025
1.862
6.108
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
SECTION B-C
PIPE
16
0.4412
1.447
0.4412
1.447
1025
1.862
6.108
0.24
0.042
0.4412
1.447
1025
1.862
6.108
0.24
0.170
SUB TOTAL
0.178
0.178
0.212
GRAND TOTAL
15>
0.390
SECTION C-D
PIPE
0.1575
0.517
95
1.354
4.442
BF VALVE
0.1575
0.517
95
1.354
4.442
0.675
0.063
0.1575
0.517
95
1.354
4.442
0.45
0.084
REDUCER 150X100
0.1575
0.517
95
1.354
4.442
0.86
0.080
SUB TOTAL
0.144
0.144
0.228
GRAND TOTAL
16>
17>
SECTION E-F
0.371
7.000
PIPE
0.1575
0.517
95
1.354
4.442
BF VALVE
0.1575
0.517
95
1.354
4.442
0.123
0.675
0.063
0.1575
0.517
95
1.354
4.442
0.45
0.042
0.1575
0.517
95
1.354
4.442
0.9
0.084
EXPANDER (100x150)
0.1575
0.517
95
1.354
0.86
0.080
4.442
SUB TOTAL
0.123
0.270
GRAND TOTAL
18>
0.393
SECTION F-O
PIPE
32
0.4412
1.447
1120
2.035
6.674
0.4412
1.447
32
1120
2.035
6.674
0.24
0.051
0.4412
1.447
1120
2.035
6.674
0.24
0.051
90 degree bends
0.4412
1.447
1120
2.035
6.674
0.36
0.076
SUB TOTAL
GRAND TOTAL
241454199.xls.ms_office
0.420
0.420
0.177
0.597
SL NO DESCRIPTION
19>
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
VELOCITY
Equivalent
Length
(mtrs)
Discharge
(m3/hr)
m/sec
feet/ sec
45
1120
1.63621
5.367
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
PIPE
45
0.492
1.614
0.492
1.614
1120
1.63621
5.367
0.24
0.033
0.492
1.614
1120
1.63621
5.367
0.24
0.033
0.492
1.614
1120
1.63621
5.367
0.24
0.033
0.492
1.614
1120
1.63621
5.367
0.72
0.098
0.492
1.614
1120
1.63621
5.367
0.36
0.295
SUB TOTAL
0.348
0.348
0.491
GRAND TOTAL
20>
0.839
PUMP Suction
PIPE
0.3906
1.281
BF VALVE
0.3906
0.3906
REDUCER (400x250)
0.3906
560
1.298
4.257
1.281
560
1.298
4.257
0.325
0.028
1.281
560
1.298
4.257
0.39
0.067
1.281
560
1.298
4.257
0.795
0.068
SUB TOTAL
0.033
0.033
GRAND TOTAL
21>
0.196
1.500
241454199.xls.ms_office
0.163
SL NO DESCRIPTION
QUANTITY
(Mtrs. /
Nos.)
DIAMETER
(mtrs)
(feet)
Equivalent
Length
(mtrs)
VELOCITY
Discharge
(m3/hr)
m/sec
feet/ sec
'K' VALUE
FOR
HEAD LOSS
Hf =
FITTINGS
(mtrs.)
KV2/2g(mwc)
(for one
fitting)
ROUTE1:AB+BC+CD+DE+EF+FO
13.194
ROUTE2: AB+BG+GH+HI+IJ+JO
6.212
ROUTE3:AB+BG+GK+KL+LM+MN+NJ+JO
10.272
1. THOUGH THE MAXIMUM PRESSURE DROP IS ALONG ROUTE-1, THE TERMINAL PRESSURE REQUIRED AT THE INLET OF THE AIR COMPRESSOR IS 30 MWC
2. THE TERMINAL PRESSURE AT THE INLET OF THE AIR COMPRESSOR IS 30 MWC
3. THE PRESSURE AVAILABLE FROM THE CW PUMPS IS 15 MWC
4. PRESSURE DROP UPTO THE AIR COMPRESSOR TERMINAL POINT IS = AB+BG+GK+KL= (.839+.516+2.921+.710)1.1=5.4846
5. ACTUAL PRESSURE REQUIRED AT THE AIR COMPRESSOR TERMINAL POINT IS 30+5.4846+2=37.48
6. HENCE THE ACW PUMP HEAD=ACTUAL PRESS REQUIRED AT AIR COMPRESSOR TERMINAL-PRESSURE AVAILABLE AT SUCTION=37.48-15=25 MWC
ACW PUMP HEAD SELECTED :
THE REQUIRED PUMP HEAD = 25 MWC