C65 Ichp
C65 Ichp
C65 Ichp
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Capstone
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Telephone: (818) 734-5300 Facsimile: (818) 734-5320 Website: www.microturbine.com
Appl i c at i on Gui de -
Model C65 I nt egrat ed CHP (I CHP)
This document presents application information for the Capstone C65 MicroTurbine with the
Integrated CHP (ICHP) heat recovery module option.
Introduction
Capstone MicroTurbines are prime power generators, producing high quality, commercial-
grade electric power. The C65 ICHP System offers an energy dense, small footprint, with
clean exhaust and co-generation capabilities with complete control at the customers
fingertips. These characteristics allow for low installed cost, quick start-up and low
maintenance costs.
MicroTurbines can be used to produce power in parallel with a power grid (Grid Connect), to
work as a Stand Alone generator, or to provide Dual Mode functionality. Due to this
versatility, Capstones C65 ICHP Systems can be applied in a variety of applications, and
multiple units can be controlled as a MultiPac. They are currently used to provide continuous
power to hotels, grocery stores, oil-field processing equipment, schools and office buildings,
reliable off-grid power to data centers, telecom equipment and protected manufacturing
processes.
This document describes the application of MicroTurbines and external equipment in a
variety of power applications.
Table of Contents
Introduction.......................................................................................................... 1
Summary.............................................................................................................. 2
Modes of Operation.............................................................................................. 3
Heat Exchanger Water Connections.................................................................... 9
Water Specifications............................................................................................. 9
Thermal Performance Curves ............................................................................ 11
Water System Curves ........................................................................................ 16
Exhaust Ducting Requirements.......................................................................... 17
Application Examples......................................................................................... 19
Boiler Feedwater Preheat......................................................................................................19
Use of Intermediate Heat Exchanger....................................................................................20
Absorption Chiller...................................................................................................................21
Related Documentation...................................................................................... 22
Capstone Technical Information......................................................................... 22
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 2 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Summary
The C65 Integrated CHP System (C65 ICHP) is an integrated single package that includes a
high-pressure natural gas C65 MicroTurbine with a hot water heat exchanger mounted on the
top. The C65 ICHP system is available in Grid Connect or Dual Mode versions, and includes
an exhaust diverter and factory-installed modem.
The hot water thermal output depends on the position of the diverter (full heat recovery, full
bypass, or any intermediate position), the temperature and flow of the exhaust gas from the
MicroTurbine, and the inlet water temperature and water flow. The exhaust temperature and
flow of the MicroTurbine depend on the ambient temperature, elevation above sea level, and
electric power output. There is a minimum heat transfer to the hot water heat exchanger of
about 10,000 BTU/hr (3kWt), regardless of diverter position and electric power output. This is
due to a combination of conducted heat from the exhaust ducting and small amounts of
exhaust leakage into the heat exchanger core. This requires continuous water flow
whenever the microturbine is operating.
The nominal rated output at full heat recovery is 380,000 BTU/hr (112kWt) of hot water with
the MicroTurbine operating at full 65kW electrical power output under ISO conditions, inlet
water temperature of 140F (60C), and water flow of 40 gpm (2.5 l/s).
The following table provides general guidelines for how each of these variables impact the
hot water thermal output:
Table 1. Thermal Output Variables
Variable Change in
Variable
Change in Thermal Output
Engine Power Output Increase Increase
Ambient Temperature Increase Increase (assuming constant power)
Hot Water Inlet Temp Decrease Increase
Water Flow Rate Increase Increase
Elevation Increase No Change (assuming constant power)
Detailed performance data is provided in the Thermal Performance Curves section below.
The C65 ICHP System provides flexibility to operate in several thermal and electrical modes,
accepts analog and discrete control inputs, and provides discrete output signals. The
MicroTurbines integral microprocessor control system reads and displays inlet and outlet
water temperatures, and adjusts thermal or electrical output based on these measured
temperatures or external analog control signals. The user can set modes of operation and
read selected thermal information from the front panel or remotely using Capstone Remote
Monitoring (CRMS) Software.
The system is UL listed to 2200 and 1741, and meets IEEE 519. The heat recovery system
incorporates several safety features to prevent equipment damage, including an integral high
temperature switch to shut down the MicroTurbine if heat exchanger core temperatures
become too high, and a pressure relief valve to protect the core from excessive pressures. In
addition, the integral control system performs several self-checks during startup, and
monitors current draw from the diverter actuator to confirm proper operation.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 3 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Modes of Operation
There are three basic thermal operating (CHP) modes, as summarized in the table below:
Table 2. CHP Operating Modes
CHP
Mode G
r
i
d
C
o
n
n
e
c
t
S
t
a
n
d
A
l
o
n
e
Description
Thermal
Priority
X
The diverter is locked in the full heat recovery position. Electric power
is automatically adjusted to control thermal output using measured
water inlet, outlet or external temperature control signal. Temperature
setpoint and feedback are controlled by the Master. This mode cannot
be used in Stand Alone mode. If a Dual Mode unit has been set up to
operate in Thermal Priority mode, it will automatically switch to Electric
Priority mode when switched to Stand Alone operation, and switch
back to Thermal Priority in Grid Connect mode.
Electric
Priority
(with
Thermal
Tracking)
X X
In Grid Connect mode, electric power is controlled either as a fixed
setpoint or using one of several electric load following schemes. In
Stand Alone mode, the electric output is controlled by the connected
load. The diverter is automatically adjusted to try to maintain the
measured water inlet, outlet or external temperature control signal.
Maximum available heat recovery will depend on the electric output.
Thermal
Bypass X X
The diverter is locked in the full bypass position. A minimum amount
of heat will still be recovered, but will not depend strongly on the
electric power level. This is the default mode.
The most stable thermal tracking is achieved when the unit is grid connected and operating in
the Thermal Priority mode. This method also keeps thermal and electric outputs in
proportion, thereby preserving a high total system efficiency. This may be important if
specific overall system efficiencies must be maintained.
If electric output has higher value than thermal output, Electric Priority may be the best
operating mode. When the electric power output is fixed in Grid Connect operation, the
exhaust diverter will provide stable thermal tracking and will move to a stationary intermediate
position when thermal loads are constant.
When the MicroTurbine is set to electrically load follow in Grid Connect mode, or when
operating in Stand Alone mode, it may be forced to make constant electric power output
adjustments as loads change. This will result in the exhaust diverter constantly adjusting its
position to try to maintain the programmed thermal output. Therefore, when operating in
Electric Priority mode under these load changing conditions, thermal output control may not
be as stable as when set for a fixed electric output in Grid Connect mode. The system also
may not be able to provide the expected thermal output, since electric power will be
determined by load changes.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 4 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Another application consideration for operation in Stand Alone mode is the need for the water
flow to be maintained. This may require that a pump or other flow controls be powered by the
turbine output power.
Several C65 ICHP systems can be tied together using the Capstone MultiPac Cable Kits,
allowing information to be shared between systems. The CHP modes and electric MultiPac
operating modes are set independently, which provides application flexibility. However, not
all possible combinations can be used. When a system is set to operate in Thermal Priority
CHP Mode, it requires that the Master define the electrical output for the entire MultiPac
group. Therefore, the thermal requirement will be measured, and setpoint tracking done, only
by the Master. When MultiPac operation is enabled for a group that has been set to operate
in Thermal Priority CHP Mode, the Local C65 ICHP systems are automatically programmed
to reference the Masters temperature measurement and setpoint. If this is a Dual Mode unit,
the same Master temperature measurement and Master setpoint will be used in Stand Alone
mode. The table below summarizes how the systems are allowed to operate under different
MultiPac scenarios. First choose the desired CHP Mode for grid connect operation - the
corresponding CHP Mode for Stand Alone operation is then given in the table.
In the case that the MultiPac is disabled, it is still possible to read and set parameters for each
system in the group using CRMS software, provided they are communicating through the
MultiPac communications cable and the PC with CRMS software is connected to unit #1.
The two examples below illustrate different applications where the C65 ICHP Systems are
MultiPac-enabled with one Master and two Local units:
Example 1 presents an instance where two separate applications using the same MultiPac
output power require the same temperature setpoint but unique feedback sources.
Mode: Electrical Priority (Grid Connect or Stand Alone operation)
Settings: CHP Setpoint source Master
CHP Feedback source Local
Scenario: Master controls water temperature setpoint for the entire MultiPac, but
each C65 ICHP uses its own temperature feedback source. Note that each C65
ICHP System can be set to use its own inlet RTD, outlet RTD, or an external
temperature sensor for its temperature feedback source.
Grid Connect Operation Stand Alone Operation Unit Type
CHP Mode
Temperature
Measurements
and Setpoints
CHP Mode
Temperature
Measurements
and Setpoints
Thermal Priority Master Only
Grid Connect
65C-HG4-XXXX
Electric Priority with
Thermal Tracking
Master or Local
Thermal Priority Master Only
Electric Priority with
Thermal Tracking
Master Only
Dual Mode
65C-HD4-XXXX
Electric Priority with
Thermal Tracking
Master or Local
Electric Priority with
Thermal Tracking
Master or Local
MultiPac Operating Modes (MultiPac Enabled)
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 5 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Example 2 presents an instance where three separate applications using the same MultiPac
output power require unique temperature setpoints and temperature feedback sources.
Mode: Electrical Priority (Grid Connect or Stand Alone operation)
Settings: CHP Setpoint source Local
CHP Feedback source Local
Scenario: Each C65 ICHP System uses its own temperature feedback source and
temperature setpoint to control the output water temperature. Note that each C65
ICHP System can be set to use its own inlet RTD, outlet RTD, or an external
temperature sensor for its temperature feedback source.
MultiPac
Electrical Load
Connection
80 F
70 F
95 F
#1 #2
#3
Thermal
Appl. 1
Thermal
Appl. 2
Thermal
Appl. 3
The C60/C65 Integrated CHP System Technical Reference (410043) provides additional
details on how to set up the C65 ICHP Systems to enable each of these MultiPac modes.
Three
C65 ICHP Systems
in MultiPac
Three
C65 ICHP Systems
in MultiPac
MultiPac
Electrical Load
Connection
75 F 75 F 75 F
#1 #2 #3
Thermal
Application 1
Thermal
Application 2
Local Temperature
Feedback
Sources
Setpoint for
Systems #2 & 3
Controlled by #1
Local Temperature
Feedback
Sources
Setpoints
Controlled by Each
System
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 6 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
WARNING
Excessive water temperatures may result in personal injury and/or equipment
damage. Follow good engineering practice in the design and installation of
any hot water circuit, and consider the unique operating characteristics of the
Capstone C65 Integrated CHP System as noted below.
The C65 ICHP System is designed to protect itself from excessive temperatures and
pressures. However, it is the responsibility of the person(s) designing and installing the
system to assure that resulting temperatures and pressures do not cause a safety hazard or
damage other equipment. Several points should always be considered:
1. As a general precaution, the Over Temperature limits for each C65 ICHP System should
be set to cause shutdown of the system when outlet water temperatures go above the
safety and/or equipment damage levels for the specific application. Refer to the
C60/C65 ICHP System Technical Reference (410043) for setting these Over
Temperature limits.
2. Temperatures should be monitored at points in the water circuit where excessive
temperature may cause a safety hazard or damage equipment. Consideration should
be given to automatically adjust power output, or even shut down the associated C65
ICHP Systems, if safe operating limits are exceeded.
3. For any MultiPac application where the Master is providing the temperature feedback
signal, care should be taken to assure that this temperature signal is proper for the hot
water output of all other C65 ICHP systems that are MultiPac-enabled under all possible
operating scenarios. For example, if the water circuit for one of the Local C65 ICHP
Systems is different than the water circuit for the Master, temperature feedback signals
from the Master could result in continued heat addition from the Local C65 ICHP System
that could result in safety and/or equipment damage issues. For water circuits that have
taken this into account during normal intended operation, the potential for a water circuit
to be inadvertently put into an unsafe condition must be considered (such as from valve
and/or water pump failure or manual adjustment of valves or pumps).
4. For any MultiPac application where the Master is providing either the temperature
feedback signal or the temperature setpoint for the entire MultiPac, the consequences of
failure of the Master must be considered. The Capstone MultiPac logic is set up to
control operation of the Local C65 ICHP units. Note that in Electric Priority mode, the
Local C65 ICHP units will continue to provide hot water output at the last setpoint issued
from the Master, which may provide more hot water than required. Means to avoid this
situation must be included in the total system control scheme, such as by interlocking
the Master with the Local units to cause them to shut down in the case of a failure of the
Master.
The following table describes the impact on Local MultiPac-enabled units if the MultiPac
Master fails:
CHP Mode GC SA Impact on Local MultiPac-enabled Units if Master Fails
Thermal Priority X Local units will shut down
Electric Priority X X
Local units will continue operating at the last commanded
setpoint
Thermal Bypass X X Local units will continue operating
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 7 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Major System Components
Figure 1 shows the major elements in the C65 ICHP system heat recovery module. The
MicroTurbine components provide the same functionality and control as the standard
Capstone C65 high pressure natural gas system. The CHP system adds the following major
elements:
1. Gas to Water Heat Exchanger An efficient heat exchanger core is provided to extract
energy from the MicroTurbine exhaust. It uses counter flow of exhaust and water to
provide the maximum heat transfer. Standard construction is copper tubes with copper
fins on the exhaust gas side. An all stainless steel construction is available as an option.
2. Exhaust Gas Diverter An exhaust gas diverter plate controls the amount of waste
exhaust heat that passes through the heat exchanger. In the bypass position, nearly all
of the MicroTurbines exhaust is directed straight out, avoiding contact with the heat
exchanger. Only a small amount (approximately 10,000 BTU/hr, or 3kWt) of the
MicroTurbines waste heat is transmitted into the water in the heat exchanger through
conduction in the heat exchanger assembly and convection due to small amounts of
exhaust leakage past the diverter. When moved to the full heat recovery position, the
diverter forces most of the MicroTurbine exhaust through the heat exchanger. The
diverter is also able to operate at intermediate positions, allowing part of the exhaust to
flow across the heat exchanger. The diverter is driven by a linear actuator, which is
controlled by the internal system logic and can modulate to provide Thermal Tracking
independently of electric power output.
3. Linear Actuator The linear actuator controls the diverter position, and receives its input
command from the CHP Control Board. The actuator is rated for the high temperatures it
may encounter near the heat exchanger and exhaust ducting.
4. CHP Control Board Most of the CHP system inputs and outputs are monitored and
controlled with the CHP control board assembly. This control board is an intelligent I/O
module able to convert analog signals to digital values and communicate them to the
MicroTurbines main CPU using the Capstone internal RS 485 communications bus. It is
also a power supply for the linear actuator, providing the current to drive the diverter
between bypass and recovery positions.
5. Water Temperature Sensors Resistive thermal device (RTD) sensors are mounted to
the water inlet and outlet connections of the heat exchanger, and are read by the CHP
Control Board. These measured water temperatures can also be read from the C65
MicroTurbine display.
6. Flow Switch A water flow switch is provided on the heat exchanger outlet to confirm
proper system operation. Its contact output is wired into the CHP Control Board. The
flow switch will close its contacts to indicate water flow above about 1.3 l/s (20 gpm). If
no flow is detected (flow switch contact open), the CHP Control Board will signal a fault
condition, and the C65 MicroTurbine will shut down to prevent or limit over temperature
damage to the heat exchanger core.
7. Safety Relief Valve A pressure relief valve set for 125 psi is installed at the water outlet
to prevent damage to the heat exchanger core due to unexpected high pressure.
WARNING
Excessive water temperatures may result in personal injury and/or equipment
damage. Pipe the relief valve outlet to a suitable location.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 8 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
8. Thermostat The system may also include a thermally activated switch to indicate over
temperature of the heat exchanger core. If the temperature limit is reached, the switch
contact will open, causing the CHP Control Board to signal a fault condition and shut
down the MicroTurbine.
9. Optional Shutoff Valve and Pressure Sensor (External) The CHP Control Board will
accept a digital input from a pressure switch, and provide a 0.5A, 24Vdc output signal to
control a shutoff valve. The terminals on the CHP Control Board have a jumper installed
at the factory. Opening this jumper connection will cause a fault condition and shut down
the MicroTurbine. To use the external pressure switch input, the jumper must be
removed and pressure switch wired as a normally closed contact.
10. UCB Analog Inputs (not shown) Terminal J 14 in the UCB provides for analog control
and measurement inputs. Three 0 to 5Vdc (4 to 20mA) inputs are provided. These can
be defined during commissioning to represent electric power output control, external
water temperature measurement (for thermal control), and water flow measurement.
11. UCB Control Output (not shown) One of the six UCB digital output relay contacts can
be used as control output for turning a water pump on and off. The 5Vdc output becomes
active at lightoff (exhaust gas detected), and inactive at shutdown (no exhaust gas
detected). This output will become inactive immediately in case of an E-stop command to
the system.
12. Heat Recovery Unit Drain (not shown) A drain connection is provided to allow excess
moisture from condensation during start/stop sequences or small water leaks in the heat
exchanger core or associated connections. The drain is capable of water flow rates of
0.13 l/s (2 gpm), and should be piped to a suitable building drain location.
NOTE: Refer to C60/C65 Integrated CHP System Technical Reference (410043) for details.
Figure 1 - Heat Recovery Module
Water Supply Inlet
Exhaust
out
Water Inlet Temp (RTD)
C
o
n
t
r
o
l
B
o
a
r
d
Intra Harness
(inside microturbine)
Linear Actuator (with
integral limit switches)
Thermostat
(overtemp =open)
Flow Switch
(no flow =open)
Heat exchanger
Exhaust
In
Water outlet Temp (RTD)
Water Supply Outlet
Optional Shutoff and
Pressure Sensor for
Potable Water
Diverter
Bypass
Control
Pressure Switch
(low pressure =open)
.5A
24Vdc
Safety Relief Valve
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 9 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Heat Exchanger Water Connections
In general, connections should be made to the C65 Integrated CHP System according to
sound engineering practice and local building codes for hot water heaters. Galvanic isolation
is suggested to prevent premature erosion of the heat exchanger and associated connections
whenever any metals other than copper are part of the total water circuit (note that the heat
exchanger is not warranted against such electro-chemical attack). Typically, shutoff valves
would be added at the inlet and outlet to the heat recovery unit to facilitate maintenance. The
C65 ICHP system includes a safety relief valve that must be connected to a suitable water
drain. There is also a water drain for collecting condensation or water leaks from the heat
exchanger core. This drain should also be plumbed to a suitable building drain. Refer to the
Model C60/C65 Integrated CHP System Technical Reference (410043) for more details on
these thermal connections.
Water Specifications
The Capstone heat recovery module has been designed for operation with water and
water/glycol mix. Figure 2 shows the allowable water flow rates versus outlet water
temperature, and Table 3 provides water quality requirements for reliable system operation.
A water/glycol mix is also acceptable up to 50 percent glycol. It is strongly recommended that
no other fluids or water flow rates be used directly in the heat recovery module, as corrosion
or erosion may result which are not covered by Capstones standard warranty. A suitable
intermediate heat exchanger should be used to isolate the Capstone heat recovery module
from chlorinated swimming pool water, salt water, or any other fluid not meeting the
specification in Table 3.
Figure 2. Heat Recovery Module Water Flow Requirements
10
20
30
40
50
60
70
60 80 100 120 140 160 180 200 220
Outlet Water Temperature [F]
W
a
t
e
r
F
l
o
w
[
g
p
m
]
Allowable Water Flow Range
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Application Guide: Model C65 Integrated CHP
480014 Rev A (February 2006) Page 10 of 22
Capstone reserves the right to change or modify without notice, the design, the equipment ratings, and/or the contents of this
document without incurring any obligation either with respect to equipment previously sold or in the process of construction.
When using water/glycol mixtures, the application must consider the lower heat transfer and
higher pumping losses for the chosen fluid mix.
Keep in mind the ambient temperatures for each application. For water, the minimum
ambient temperature should not go below 1.7
C (35