Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Steelwise PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3
At a glance
Powered by AI
The article discusses how floor diaphragms distribute lateral loads in buildings and the interaction between diaphragms and the lateral load resisting systems.

The floor diaphragm acts as a horizontal cantilever beam to collect and distribute lateral loads to vertical framing members like braced frames. Shear flows and chord forces are developed in the diaphragm.

Diaphragm forces result in axial loads and shears in supporting beams that must be considered in beam design. Beams collecting diaphragm forces act as beam-columns.

DECEMBER 2008 MODERN STEEL CONSTRUCTION

Under Foot
steelwise
Horizontal oor diaphragm load effects on
composite beam design.
ONE OF THE MOST NEGLECTED ELEMENTS in the design
of buildings is the horizontal foor diaphragm and its interaction
with the lateral load resisting systems. Most multi-story structures
depend on the foor slab and roof systems to act as horizontal dia-
phragms to collect and distribute the lateral loads to the vertical
framing members, which provide the overall structural stability.
In steel structures, foor diaphragms are most commonly con-
structed using composite steel deck with concrete fll, although
other systems, such as pre-cast planks, formed reinforced concrete,
or concrete on non-composite steel deck, may also be used. While
there are numerous references that discuss the design of the dia-
phragm itself, there is little guidance available on the transfer of
diaphragm forces into the lateral load resisting system. In addition,
the specifc issues related to beam design for members collecting
lateral loads in composite foor systems has gone largely undocu-
mented. The intent of this article is to help fll in the gaps on
these issues through a discussion of the effect of diaphragm forces
on the supporting steel beam behavior, as well as through practical
detailing guidelines.
General Diaphragm Behavior
Before delving into the specifc issues associated with the
transfer of diaphragm forces to the supporting framing, it is neces-
sary to understand general diaphragm behavior and how assump-
tions made affect the detailing required in establishing a robust
load path. Figure 1 depicts a foor plan for a typical steel building.
Braced frames are provided adjacent to stairwells near each end of
the building to resist the lateral loads, and the diaphragm strength
is assumed to be adequate to transfer the shear around the open-
ings. In a simple analysis, the foor diaphragm is idealized as a con-
tinuous cantilevered beam and the braced frames are treated as
beam supports. Due to the symmetry of this example and assum-
ing the braced frames have the same geometry and stiffness, the
diaphragm force at each braced frame will be equal to 50% of the
total applied lateral load.
Depending on the magnitude of lateral load to be transferred
to the braced frames, the designer can detail the force transfer to
occur uniformly along the entire frame line between grids A and
D on the grid lines where the braces occur, or they may elect to
concentrate the load transfer to a segment of this length, such as
the beam in the braced frame between grids B and C.
In the frst scenario, the load distribution is proportional to
the overall available transfer length, and beams A-B and C-D each
collect 35% of the total force while beam B-C collects 30% of
the total force. Beams A-B, B-C, and C-D are all crucial members
for getting load to the lateral load resisting system, and the con-
nections of these beams to the columns at grids B and C must
be designed for a horizontal force equal to the axial load being
transferred through the column joint to the braced frame plus
a vertical shear force resulting from the eccentricity of the dia-
phragm relative to the beam centerline. These member forces will
occur simultaneously with the vertical beam shear reactions due
to the gravity loads. Design and detailing of these joints for the
combined forces is often overlooked.
In the second scenario, beam B-C collects 100% of the force.
The distribution of axial, shear, and fexural member forces due
to the applied lateral load for this beam will depend on the spe-
cifc braced frame confguration. Once defned, these forces can
be transferred into the braces with standard braced frame con-
nections. Figure 2 illustrates the shear fow associated with this
scenario.
Tension and compression chord forces are developed at the
perimeter of the foor diaphragm due to the lateral loads. Typi-
cally, the foor slab concrete can resist the compression chord
forces. Tension chord forces can be resisted by the spandrel steel
beams, continuous steel closure plates, or by reinforcing steel
within the concrete slab. In order to use the spandrel steel beams
as the tension chord, the diaphragm chord forces must be trans-
ferred into the steel beams, and the steel beam connections at the
columns must have suffcient strength to transfer the beam forces
through the column joints. Again, this is a condition that often is
overlooked, where the beam connections must be designed for
the combined effects of vertical shear loads and horizontal axial
loads.
Once the basic distribution of horizontal forces is understood,
the effect of these forces on the design of the composite beams
can be examined.
BY SUSAN BURMEISTER, P.E., AND WILLIAM P. JACOBS, P.E.
Figure 1. Typical building floor plan Figure 2. Shear flow from lateral loads
MODERN STEEL CONSTRUCTION DECEMBER 2008
Additional Shear Connection?
The mechanical connection of the foor
system to the supporting steel beams in a com-
posite beam system is achieved using headed
steel studs or hot-rolled channel shear con-
nectors. Often, the beams are designed as com-
posite members for the gravity loads applied to
the foor system. Traditionally, if the beam also
serves as a collector element, additional shear
studs are added to account for transfer of the
superimposed horizontal load into the beam.
However, this practice is not always necessary
for two primary reasons.
First, the quantity of shear studs selected
for a composite beam is usually determined
based on a gravity load combination, such
as 1.2D+1.6L (LRFD) or 1.0D+1.0L (ASD).
When lateral loads are applied in conjunction
with the gravity loads, the load combinations
of ASCE 7 reduce the live load levels. Under
these reduced live loads, the shear studs pro-
vided to develop the composite action required
for the gravity loads will be under-used and
thus have additional capacity available for the
transfer of the diaphragm forces.
Second, the interaction of the shear fow
from the different loading conditions is addi-
tive for some studs but opposite for others. The
distribution of horizontal shear from beam
fexure is assumed to fow in two directions
from the point of maximum moment to the
point of zero moment. For a typical simple-
span composite beam with uniform gravity
loads, this shear fow is as indicated in Figure 3.
While the beam shear is greatest at the ends
of the beams, it is common practice to assume
that the shear studs will deform and redistrib-
ute the shear uniformly to all studs.
Conversely, lateral loads induce shear in
only one direction. When these beams are used
to collect the diaphragm forces, the shears due
to the lateral loads are superimposed on the
horizontal shears due to the gravity loads, as
indicated in Figure 4. On one side of the beam,
the lateral loads increase the horizontal shears
over the gravity-induced values, while on the
other side of the beam, the lateral loads oppose
the gravity-induced horizontal shears.
Assuming the shear studs have suffcient
ductility to distribute the horizontal shears
evenly along the beam, a composite beam can
transfer a horizontal shear due to lateral loads
between the foor diaphragm and steel beam
that is equal to the summation of the strengths
of all the shear studs on the beam regardless
of demand on the shear studs from the gravity
loads.
Non-Composite Composite Beams
Designers encounter many conditions
where steel beams are designed as non-com-
posite members under gravity loads. Shear
studs placed on these beams for transfer of lat-
eral forces still will be subjected to horizontal
shears due to fexure from gravity loads. This
is unavoidable. Therefore, in order to ensure
the anchors are not overloaded under the grav-
ity loads, it is recommended that all beams
that transfer diaphragm forces to the lateral
load resisting systems have enough anchors
to achieve a minimum 25% partial compos-
ite action. When less anchors than this are
provided, large deformations of the studs may
occur under the gravity load case, inhibiting
the ability of the beam to function as intended
under lateral loading.
To Phi or not to Phi?
The nominal strength of the individual
shear studs, Q
n
, can be determined from the
equations in the AISC Specifcation. The cur-
rent shear connector strength equations
generally are used as nominal strength equa-
tions in composite beam design where the
anchors are part of a composite system; the
and come in later in the calculation of the
beam fexural strength. However, when the
shear stud strength is checked as a connection
between the diaphragm and beam, a resistance
(or safety) factor should be applied to the shear
stud nominal strength. Based on preliminary
results of ongoing research at the University
of Illinois at Urbana-Champaign, = 0.65
(LRFD) or = 2.30 (ASD) are recommended.
These values are in line with similar recom-
mendations by PCI and ACI.
Secondary Shears and Moments
Once the designer deals with the transfer
of force from the foor diaphragm into the
supporting steel beam, the effect of the dia-
phragm forces on the design of the beam and
its connections to the remainder of the lateral
load resisting system must be considered. Of
particular concern is the effect of the vertical
offset (eccentricity) between the plane of the
diaphragm and the centerline of the support-
ing beam as indicated in Figure 5. Intuitively,
one would anticipate additional moments
imposed on the beam as a result of the eccen-
tricity. However, this is not the case.
As an example, consider a simple-span
beam with uniform horizontal shears from the
lateral loads and resulting reactions as shown in
Figure 5. For this scenario, assume the member
is connected to the lateral load resisting system
at the left end of the beam only.
The free body diagram in Figure 6 shows
the internal member forces that result from
this applied uniform load. The axial load in
the beam will increase linearly toward the end
of the beam designed to transfer the collected
force to the lateral load resisting system, but
the internal moment due to this applied lat-
eral load, even considering the d/2 eccentricity,
will be zero. The member should be designed
as a beam-column, considering the combined
effects of the axial forces due to the lateral loads
and the fexural forces due only to the gravity
loads. The shear is a constant value and must
be considered in the connection design at both
ends of the member.
Force Interaction
The rigorous design of composite beams for combined axial force and
fexure is complex. As a reasonable simplifcation for design purposes, it
is acceptable to use the non-composite axial strength and the composite
fexural strength in combination using the interaction equations in the
AISC Specifcation, Chapter H. Note that for compressive loading, this
type of composite beam-column is generally considered unbraced for
buckling between braced points about the major axis, and fully braced by
the composite diaphragm for buckling about the minor axis.
As with all structural systems, there is an element of engineering
judgment involved in the proper design and detailing of horizontal dia-
phragms and composite beam interaction. Careful consideration should
be made to provide a continuous load path. The designer must account
for the required axial forces and shears to be transferred at the end con-
nections of all beams. Though there are many aspects to consider for
the design of composite beams subject to horizontal diaphragm forces
as reviewed in this article, their implementation is straightforward, thus
allowing the composite beams to be used as an economical and effcient
component of the lateral force resisting system.
Susan Burmeister is an associate with Cagley and Associates, Inc., Rockville, Md.,
and William P. Jacobs is a design engineer with SDL Structural Engineers,
Atlanta.
Beam Lateral loads increase net
shear in steel anchors
within this zone
Lateral loads decrease
net shear in steel anchors
within this zone
Shear ow from gravity loads
Shear ow from lateral loads
(Fig. 3)
(Fig. 4)
(Fig. 5)
(Fig. 6)
Fig. 3. Shear flow due to gravity loads only
Fig. 4. Shear flow due to gravity and lateral loads in combination
Fig. 5. Analytical model of simple span beam
Fig. 6. Free body diagram of beam segment

You might also like