Characteristics
RM17TE00
Range of product
Zelio Control
Product or component
type
Relay type
Product specific
application
Relay name
RM17TE
Relay monitored
parameters
Asymmetry
Phase failure detection
Phase sequence
Undervoltage and overvoltage in window mode
Time delay
Adjustable 0.1...10 s, 10 %
Switching capacity in
VA
1250 VA
Measurement range
183...528 V AC
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Complementary
Reset time
250 V AC
250 V DC
10 mA at 5 V DC
5 A AC
5 A DC
208...480 V AC 3 phases
183...528 V AC
- 12 %, + 10 % Un
Power consumption
<= 1.8 VA AC
50...60 Hz +/- 10 %
Output contacts
1 C/O
5A
Hysteresis
2%
Measuring cycle
Voltage range
5...15 % of Un selected
Measurement accuracy
Repeat accuracy
Measurement error
0.7 Un
Response time
7/9/2011
Marking
CE : 73/23/EEC
CE : EMC 89/336/EEC
Overvoltage category
Insulation resistance
Supply frequency
50/60 Hz +/- 10 %
Operating position
Electrical connection
Tightening torque
Housing material
Self-extinguishing plastic
Status LED
Mounting support
Electrical durability
100000 cycles
Mechanical durability
30000000 cycles
Operating rate
Utilisation category
Width
17.5 mm
Product weight
0.13 kg
Environment
Immunity to microbreaks
10 ms
Electromagnetic compatibility
Standards
EN/IEC 60255-6
Product certifications
CSA
C-Tick
GL
GOST
UL
-40...70 C
-20...50 C
Relative humidity
Vibration resistance
Shock resistance
IP degree of protection
Pollution degree
Compliant
0701
RM17TE00
RM17TE00
RM17TE00
Function Diagrams
Phase Sequence Control, Phase Failure Detection (U measured < 0.7 x nominal supply voltage) and Asymmetry
Detection
Tt
Time delay after crossing of threshold (adjustable on front panel)
L1, Phases of the supply voltage monitored
L2,
L3
A
Asymmetry threshold (adjustable from 5...15% of the nominal supply voltage)
H
Hysteresis
11-12,Output relay connections (refer to Connections and Schema)
11-14
Relay status: black color = energized.
Tt
Time delay after crossing of threshold (adjustable on front panel)
H
Hysteresis
U> Overvoltage threshold
U< Undervoltage threshold
L1, Phases of the supply voltage monitored
L2,
L3
11-12,Output relay connections (refer to Connections and Schema)
11-14
Relay status: black color = energized.
The overvoltage and undervoltage threshold in window mode is adjustable from 220% of Un:
Un
208V
220V
480V
<
- 12- 2
- 17- 2
- 20- 2
>
+ 2+
20
+ 2+ 20
+ 2+ 20
+ 2+ 10
- 20- 2