Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

150 Um011 - en P

Download as pdf or txt
Download as pdf or txt
You are on page 1of 306

User Manual

SMC-50 Solid-State Smart Motor Controller


Bulletin 150

Important User Information


Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Table of Contents
Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Chapter 1
Product Overview

Other Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9


Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
DeviceLogix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Chapter 2
Installation & Wiring

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Degree of Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Factor Correction Capacitors (PFCC) . . . . . . . . . . . . . . . . . . . . . .
Protective Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two-Speed Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Multi-Motor Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Winding Heater Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Terminal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Connected Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Delta Connected Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding Provision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Terminal Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock (RTC) Battery Replacement . . . . . . . . . . . . . . . . . . . . . .
Standard Controller Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

15
15
15
15
15
15
16
17
18
18
19
24
26
27
27
27
29
30
30
30
30
31
31
31
32
32
33
33
35
35
36
48
49
3

Table of Contents

Soft Stop, Pump Control, & Smart Motor Braking (SMB) . . . . . . . . . . . 66


Slow Speed with Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Preset Slow Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Chapter 3
Operating Modes

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Tuning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes of OperationStarting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Soft Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selectable Kickstart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current Limit Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Full Voltage Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Linear Acceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque Control Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Control Start & Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Start FeaturesFunctions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dual Ramp Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Timer (Start Delay) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Timed Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Backspin Timer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Winding Heater Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes of OperationStopping Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coast-to-Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Soft Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Linear Deceleration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smart Motor Braking (SMB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preset Slow Speed & Slow Speed with Braking. . . . . . . . . . . . . . . . . . .
Accu-Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Braking Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Running Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Solid-State (SCR) Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Bypass Control Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Energy Saver Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Emergency RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

73
73
73
74
74
75
76
77
78
79
80
81
81
83
83
83
83
84
84
85
85
86
87
89
90
91
91
91
93
94
94

Chapter 4
Protection & Diagnostic
Functions

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20-HIM-A6, 20-HIM-C6 & Configuration Software . . . . . . . . . .
Enabling Starter & Motor Faults & Alarms . . . . . . . . . . . . . . . . . . . .
Enabling Option Module Functional Faults & Alarm . . . . . . . . . . .
Protection & Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overload Fault & Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Underload Fault & Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

103
104
104
107
108
108
111

Table of Contents

Line Power Undervoltage Protection. . . . . . . . . . . . . . . . . . . . . . . . . .


Line Power Overvoltage Protection Fault & Alarm . . . . . . . . . .
Current Imbalance Protection Fault & Alarm. . . . . . . . . . . . . . .
Voltage Unbalance Protection Fault & Alarm . . . . . . . . . . . . . . .
Phase Reversal Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High & Low Line Power Frequency Protect. Fault & Alarm. .
Stall Protection Fault & Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Jam Detection Fault & Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Power Protection (MWatts). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reactive Power Protection (MVAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Over Power Reactive Positive Fault & Alarm . . . . . . . . .
Motor Under Power Reactive Positive Fault & Alarm . . . . . . .
Motor Over Power Reactive Negative Fault & Alarm . . . . . . . .
Motor Under Power Reactive Negative Fault & Alarm . . . . . .
Apparent Power Protection (MVA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Factor (PF) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Excessive Starts/Hour Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preventive Maintenance (PM) Protection . . . . . . . . . . . . . . . . . . . . . . . . .
Line Loss Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Silicon-Controlled Rectifier (SCR) Protection. . . . . . . . . . . . . . . . . . . . .
Shorted SCR Fault Phase A, B, or C . . . . . . . . . . . . . . . . . . . . . . . .
SCR Overtemperature Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Open SCR Gate Fault & Alarm Phase A, B, or C . . . . . . . . . . . .
Power Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Total Harmonic Distortion (THD) Fault & Alarm . . . . . . . . . . . .
Power Pole Overtemperature Fault. . . . . . . . . . . . . . . . . . . . . . . . .
Open Load Fault & Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current Transformers (CT) Loss Fault. . . . . . . . . . . . . . . . . . . . .
Locked Rotor Fault & Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expansion Module Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expansion Device Removed Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expansion Device Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expansion Module Incompatible Fault . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock (RTC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration Change Fault & Alarm. . . . . . . . . . . . . . . . . . . . . .
I/O Configuration Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Buffers & Storage Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Non-volatile Storage (NVS) Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Buffer & Fault Storage Parameters. . . . . . . . . . . . . . . . . . . . . . .
Alarm/Event Buffer & Alarm/Event Storage Parameters. . . . . . . .
Auto Restart from Fault Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

112
113
114
115
116
116
117
119
120
121
121
122
123
124
124
126
127
127
129
129
129
129
130
130
131
131
132
132
132
133
133
134
134
134
134
134
135
135
135
135
136
137

Chapter 5
Programming

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Table of Contents

Parameter Configuration Module (PCM) . . . . . . . . . . . . . . . . . . . . . . . . .


Human Interface Module (HIM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RAM (Random Access Memory). . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ROM (Read-only Memory) Set Defaults . . . . . . . . . . . . . . . . . . . .
EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the START UP Configuration Tool . . . . . . . . . . . . . . . . . . . .
Parameter Search & Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Search & Configuration by Parameter Number . . . . . .
Parameter Search & Configuration by FileGroup Structure . . .
Parameter Configuration - Using the Setup File Group . . . . . . . . . . . . .
Soft Start & Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current Limit Start with Simple Stop Mode . . . . . . . . . . . . . . . . . . .
Linear Acceleration (Speed Sense) Start with Stop . . . . . . . . . . . . . .
Torque Start with Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Full Voltage Start with Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dual Ramp Start with Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stop Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Slow Speed with Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accu-Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter File-Group Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SMC-50 Option Module Configuration . . . . . . . . . . . . . . . . . . . . . . . . . .

139
145
150
151
151
152
152
152
155
156
157
159
160
162
163
165
167
169
170
171
171
172
172
174
182

Chapter 6
Metering

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Viewing Metering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting Metering Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Metering Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Energy Savings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Elapsed Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Running Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actual Start Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Peak Start Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Total Starts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Total Harmonic Distortion (THD) . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

191
191
192
192
192
193
193
194
195
195
196
196
196
197
197
197
198
198

Table of Contents

Current Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198


Voltage Unbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199

Chapter 7
Optional HIM Operation

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HIM Control Buttons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HIM Control Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CopyCat Function of the 20-HIM-A6 . . . . . . . . . . . . . . . . . . . . . . . .

201
201
203
204

Chapter 8
Communications

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HIM Keypad & Displays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Loss of Communication with DPI Device . . . . . . . . . . . . . . . . . . . . . . . . .
Default Input/Output Communication Configuration . . . . . . . . . . . .
SMC-50 Bit Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameter Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scale Factors for PLC Communication . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Text Unit Equivalents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring DataLink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Updating Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

205
205
205
207
209
209
210
211
211
211
212
212
213

Chapter 9
Diagnostics

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protection Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Display (20-HIM-A6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault & Alarm Buffer - Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the Fault & Alarm Parameters . . . . . . . . . . . . . . . . . . . . . .
Accessing the Fault & Alarm Buffers . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Auxiliary Relay Output Fault or Alarm Indication . . . . . . . . . . . . . . . . .

215
215
215
218
218
219
219
221
222
228

Chapter 10
Troubleshooting

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Power Module Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239

Appendix A
Specifications

Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241


Electrical Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Table of Contents

SCPD Performance , Type 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246


Additional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249

Appendix B
Parameter Information

SMC-50 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
150-SM6 PCM Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
150-SM4 Digital I/O Module Information . . . . . . . . . . . . . . . . . . . . . . . .
150-SM2 Ground Fault Module Information . . . . . . . . . . . . . . . . . . . . . .
150-SM3 Analog I/O Module Information . . . . . . . . . . . . . . . . . . . . . . . .

253
276
277
281
282

Appendix C
Spare/Replacement Parts

SMC-50 Power Poles and Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


SMC-50 Control Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Option Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removable Terminal Blocks for Control Wiring . . . . . . . . . . . . . . . . . . .
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Covers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Renewal Part Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

287
287
288
288
288
288
289
289

Appendix D
Control Module/Power Pole
Assembly Replacement

Removal & Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291

Appendix E
Accessories

Catalog Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293

Appendix F
Using DeviceLogix

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function Block Elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bit and Analog I/O Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bit Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bit Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DeviceLogix scratchpad registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SMC-50 DeviceLogix Input Datalinks (P337P342) . . . . . . . . . . .
Program Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1: Selector Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . .
Example 2: Diverter Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 3: Wet Well Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

295
295
296
297
297
297
298
299
299
299
299
299
299
299
301
302

Chapter

Product Overview
Other Related Documents

Description

Quick Start Publication 150-QS003


Option Module Instructions:
Analog and Digital I/O Options: Publication 150-IN052
Parameter Configuration: Publication 150-IN053
PTC, Ground Fault, Current Feedback: Publication 150-IN051
Accessory Component Instructions:
Protection Modules: Publication 150-IN036
IEC Terminal Covers (Frame B): Publication 10000152881
External Bypass (Frames C and D): Publication 150-IN071
Selection GuidePublication 150-SG010
DeviceLogix User ManualPublication RA-UM003

Starting Modes/Features
The SMC-50 is a reduced voltage soft starter that utilizes a a state-of-the-art
microprocessor- based control module and solid-state (without an integral bypass
contactor) power structure. Using six back-to-back SCRs (two per phase), the
SMC-50 provides controlled acceleration, operation/run, and deceleration of
standard asynchronous induction motors.
The SMC-50 offers a full range of starting modes as standard:
Linear Speed Acceleration
Soft Start with selectable kickstart
Current Limit with selectable kickstart
Dual Ramp Start with selectable kickstart
Full Voltage Start
Preset Slow Speed from 1 to 15%, forward and reverse
Torque Control
Pump Control Pump Start with selectable Kickstart

Running Modes/Features
The SMC-50 offers three operational/run modes:
solid-state run mode

solid-state with energy external bypass run


saver run mode
mode (option)

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter 1

Product Overview

Stopping Modes/Features
The SMC-50 offers a full range of stopping modes as standard:
Linear Speed Deceleration
Coast
Soft Stop

Metering

Pump Control
Braking Control
Smart Motor Braking (SMB)
Slow Speed with Braking

The SMC-50 allows the user to monitor the following power parameters:
RMS current for each phase and average of all three phases
Line-to-line voltage for each phase and average of all three phases
Line-to-neutral voltage for each phase and average of all three phases
Line frequency
Voltage unbalance.
Current imbalance.
Torque
Real, reactive and apparent power for each phase
Real, reactive and apparent power maximum demand
Real, reactive and apparent energy
Power factor for each phase and total
Energy savings (when energy saving mode is selected)
Motor operation elapsed time total
Motor operation elapsed time since start command
Motor speed
Motor start time duration
Peak RMS motor starting current
Total motor starts since purchased from Rockwell Automation
Total Harmonic Distortion (THD) for voltage of each phase and the
average
THD for current of each phase and the average
During braking and slow speed, torque will be zero.
Estimated speed during starting and stopping when Linear Speed acceleration and deceleration is used. Displays
100 when the motor is at its full steady state (running) speed.
Data available for most recent five starts.

I/O

Inputs
The SMC-50 has two 24V DC inputs available as standard. The operation of
each input can be configured from a select group of functions by the user. See
Figure 1 for the location of the removable standard I/O terminal block.

10

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Product Overview

Chapter 1

The status of these two 24V DC inputs is available to networked devices using
any of the standard SMC-50 communication networks through the product logic
status word (Chapter 8, Communications).
NOTE:

Four additional 120...240V AC inputs can be added using a single Cat.


No. 150-SM4 Digital I/O Option Module. See Chapter 2, page 38.

The available configuration functions for each input are as follows:


Disable Input not activated
Start used in a 3-wire configuration
Coast used in a 3-wire configuration
Stop Option initiates a stop option stopping mode selected through the
Stop Mode, Parameter 65, used in a 3-wire configuration
Start/Coast 2-wire operation with Coast stopping method
Start/Stop Option 2-wire start/stop control with Stop Option stopping
mode
Slow Speed
Overload Select select between Motor Overload Class 1 and Motor
Overload Class 2
Fault active high fault input
Fault N.C. active low fault input
Clear Fault active high clears fault
Emergency Run active high disables all faults
Dual Ramp select between Starting Profile #1 and #2
Motor Winding Heater active high, enables heating feature when the
start command is present
The SMC-50 will generate an I/O configuration fault if:
1. any input is configured as a start or slow speed input and no input is
configured as a coast or stop, or
2. any input configuration is changed from a start input (Start, Start/Coast,
Start/Stop, or Slow Speed) to a non-start input, or
3. any input configuration is changed from a stop (Coast, Stop, Start/Coast,
Start/Stop) to a non-stop input.
In cases 2 and 3, the fault is generated when the parameter changes.
NOTE:

Two analog inputs (voltage or current) can be added using a single Cat.
No. 150-SM3 Analog I/O Option Module. See Chapter 2, page 39.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

11

Chapter 1

Product Overview

Outputs
The SMC-50 has two relay outputs provided as standard. These relay outputs can
be configured to follow a number of functions (see the relay output parameters
list below) and operate normally open (N.O.) or electrically held normally closed
(N.C.). In addition to the configured function, each relay can be individually
configured with an ON and OFF delay time.
See Figure 1 for the locations of the removable standard I/O terminal block.
Relay output parameters include:
Normal active when the start
command is initiated, inactive with
stop command
Up-to-Speed (UTS)
Fault
Alarm
External Bypass
NOTE:

External Brake
DeviceLogix
Aux Control
Network 1
Network 2
Network 3
Network 4

Three additional relay outputs can be added using a single 150-SM4 Digital
I/O Option Module. See page 38.
Two analog outputs (voltage or current) can be added using a single Cat. No.
150-SM3 Analog I/O Option Module. See page 39.

Communication

A Drives Programming Interface (DPI) communications port is provided as


standard (see Figure 1). This communications port enables the SMC-50 to
interface with other DPI communication devices (e.g., a 20-HIM-A6, a
1203-SSS, or a 1203-USB AnaCANda cable for PC interface software such as
DriveExplorer) and software that is PC based and network compatible (e.g.,
Connected Components Workbench).
Figure 1 - DPI Location & Standard Terminal Block

Top of SMC-50

DPI port 2

12

Standard I/O terminal block

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Product Overview

Chapter 1

The SMC-50 Controller supports DPI communication port numbers 1, 2, 3, and


4. Port 1 is assigned to support the optional slide-in front-mounted HIM (see
Figure 2). Port 2 is assigned to the DPI port located on the top of the control
module (see Figure 1). Communication port 4 is assigned to a 20-COMM-X
network module hardware expansion slot 9 (see Figure 2).
NOTE:

When the DPI splitter is placed into port 2, it is assigned communication port
numbers 2 and 3.

The front of the controller also contains a multi-color diagnostic STATUS LED
to provide simple operational and fault information. A PUSH TO RESET and
HOLD TO TEST push button provides the ability to reset a fault without
additional hardware. More detailed information about these tools can be found in
Chapter 10, Troubleshooting.
The SMC-50 has three hardware expansion ports (7, 8, and 9) which are used to
house optional expansion modules. These expansion modules provide additional
features/functions (e.g., I/O expansion, basic parameter configuration, ground
fault detection, etc.) to be added as necessary.
Figure 2 - SMC-50 - Front View
Slide-In Bezel for
Front-Mounted HIM
(DPI Port 1)
Status LED
Push to Reset
Hold to Test

DPI Port 4

Control Module
Expansion Ports
(7, 8, & 9)

Programming

ATTENTION: Two peripheral devices can be connected to the DPI port on


top of the SMC-50. The maximum output current through the DPI port is
280 mA.

The SMC-50 parameters can be programmed/configured using a Bulletin


20-HIM-A6 LCD configuration device, PC-based software (e.g.,
DriveExecutive or DriveExplorer), or a Cat. No. 150-SM6 Parameter
Configuration Module. Each configuration device must be ordered separately.
The SMC-50 does not include a configuration device.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

13

Chapter 1

Product Overview

The Cat. No. 150-SM2, -SM3, and -SM4 option modules can be
programmed/configured using a Cat. No. 20-HIM-A6 or -C6S LCD
configuration device or PC-based software.

DeviceLogix

14

DeviceLogix is an embedded component of SMC-50 Smart Motor Controllers.


It is used to control outputs and manage status information locally within the soft
starter. It can function stand-alone or complimentary to supervisory control. See
Appendix F, Using DeviceLogix for additional information and programming
examples.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Installation & Wiring

Overview

The SMC-50 Soft Starters can be used to start three-phase, line-type (up to
690V), or delta-type (up to 600V) motors. Line voltage and motor type are
automatically detected by the SMC-50 or can be configured by the user.

Degree of Protection

The line and load power terminals of the SMC-50 Soft Starters have an IP00
rating. Units rated 90180 A can have an IP2X rating with the addition of
optional 150-STCB terminal covers. Taking into account the ambient
conditions, the device must be installed in a suitable enclosure. Make sure that no
dust, liquids, or conductive parts can enter the soft starter. Soft starter operation
produces waste heat (i.e., heat loss). For details, see Table 1 in this chapter or
Appendix A, Specifications.

Receiving

It is the users responsibility to thoroughly inspect the equipment before


accepting the shipment from the freight company. Check the item(s) received
against the purchase order. If any items are damaged, it is the responsibility of the
user not to accept delivery until the freight agent has noted the damage on the
freight bill. Should any concealed damage be found during unpacking, it is again
the responsibility of the user to notify the freight agent. The shipping container
must be left intact and the freight agent should be requested to make a visual
inspection of the equipment.

Unpacking

Remove all packing material, wedges, or braces from within and around the
controller.

Inspecting

After unpacking, check the item(s) nameplate catalog number against the
purchase order.

Storing

The controller should remain in its shipping container prior to installation. If the
equipment is not to be used for a period of time, it must be stored according to
the following instructions in order to maintain warranty coverage:
Store in a clean, dry location.
Store within an ambient temperature range of 25 C to +75 C
(13 F to +167 F).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

15

Chapter 2

Installation & Wiring

Store within a relative humidity range of 0% to 95%, noncondensing.


Do not store equipment where it could be exposed to a corrosive
atmosphere.
Do not store equipment in a construction area.

General Precautions

In addition to the precautions listed throughout this manual, the following


statements, which are general to the system, must be read and understood.
ATTENTION: The controller contains ESD- (electrostatic discharge)
sensitive parts and assemblies. Static control precautions are required
when installing, testing, servicing, or repairing the assembly. Component
damage may result if ESD control procedures are not followed. If you are
not familiar with static control procedures, see applicable ESD protection
handbooks.
ATTENTION: An incorrectly applied or installed controller can damage
components or reduce product life. Wiring or application errors (e.g.
undersizing the motor, incorrect or inadequate AC supply, or excessive
ambient temperatures) may result in malfunction of the system.
ATTENTION: Only personnel familiar with the controller and associated
machinery should plan or implement the installation, start-up, and
subsequent maintenance of the system. Failure to do this may result in
personal injury and/or equipment damage.
ATTENTION: Hazardous voltages that can cause shock, burn, or death
are present on L1, L2, L3, T1, T2, and T3.
Power terminal covers can be installed on devices rated 90180 A to
prevent inadvertent contact with terminals. Disconnect the main power
before servicing the motor controller or associated wiring.

16

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Heat Dissipation

Chapter 2

The following table provides the maximum heat dissipation at the maximum
rated current for the controllers. For currents lower than the rated value, heat
dissipation will be reduced.
Table 1 - Control Power Requirements (Max. Control Circuit Consumption)
Description
Base Power Draw: Control
Module with Heat Sink Fan

Optional Power Adder (for


each option installed, add to
base power)

Control Voltage
100240V AC
24V DC
150 VA
75 W
150 VA
75 W
300 VA
300 W
10 VA
2W
30 VA
4W

Current Range [A]


90180
210320
361520
Human Interface Module (HIM)
150-SM2
150-SM3

30 VA
50 VA

150-SM4

4W
2W

150-SM6

5 VA

1W

20-COMM-X

25 VA

4W

Add to Base power using the formula below to obtain total power requirements.
Max. 1 of each option type per control module

Table 2 - Continuous Duty Power Structure Heat Dissipation at Rated Current


Description

Current Range [A]

Controller Rating [A]

90
110
140
180
210
260
320
361
420
520

Heat
Dissipation [W]
270
330
420
540
630
780
960
1083
1260
1560

Power Calculation
Max. total power
dissipation

Base Power

Options

Power Structure

Watts

Example: 361 A device with a 20-COMM-X module, HIM, and Cat. No.
150-SM4
Max. total power
dissipation

300
Base Power

(25 + 10 + 50)
Options

1083
Power Structure

Watts

Max. total power dissipation = 1468 Watts

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

17

Chapter 2

Installation & Wiring

Enclosures

The open-style design of the SMC-50 requires an enclosure with at least 150 mm
(6 in.) of clearance above and below the controller. The enclosure will allow air to
flow through the heat sink, keeping the surrounding air ambient temperature
within the required range of -20...40 C (-4104 F). See Table 3 for the
minimum enclosure size.
Table 3 - Minimum Enclosure Size (SMC-50 only)
Configuration
150-SB
150-SC
150-SD

IMPORTANT

Mounting

Line/Wye
Inside-the-Delta
All
All

Width
609.6 (24.0)
762.0 (30.0)
762.0 (30.0)
914.4 (36.0)

mm (in.)
Height
762.0 (30.0)
965.2 (38.0)
965.2 (38.0)
1295.4 (51.0)

Depth
304.8 (12.0)
355.6 (14.0)
355.6 (14.0)
355.6 (14.0)

The internal ambient temperature of the enclosure must be kept within


the range of -20...40 C (-4104 F).

All units are fan cooled. It is important to locate the controller in a position that
allows air to flow vertically through the power module.
IMPORTANT

The controller must be mounted in a vertical plane and have a minimum


of 6 in. (150 mm) free space above and below the controller. Side-to-side
spacing in not required. Horizontal mounting of the SMC-50 is not
allowed. Enclosure must be sized such that the enclosures internal
temperature remains within specified controller ratings.

When drilling or installing near the Soft Starter, make sure that adequate
measures are taken to protect the device from dust and debris, as illustrated
below.
Figure 3 - SMC-50 Mounting Protection

18

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Dimensions
NOTE:

Dimensions are in inches (millimeters). All dimensions are approximate


and are not intended for manufacturing purposes. Consult your local
Rockwell Automation sales office or Allen-Bradley distributor for complete
dimension drawings.

Cat. No. 150-SB Controllers


Figure 4 - Dimensions of Cat. No. 150-SB1SB4 Controller without Terminal
Covers
10.21
(259.2)
1.25
(31.8)

7.25
(184.2)

0.41 dia
(10.5)

See detail A

0.49
(12.5)
0.79
(20)

1.54
(39.1)

2.76
(70.0)

1.07
(27.1)
0.30
(7.5)

1.41
(35.8)
0.19
(4.8)

#8-32 UNC 2B

Detail A
6.25
(158.8)
13.95
(354.4)
13.39
(340.0)
14.63
(371.6)

15.62
(396.6)

2.51
(63.7)
6.69
(170.0)
7.65
(194.4)

2.51
(63.7)

Four Quantity
0.296
(7.51)

6.79
(172.5)

Note: When mounted in an enclosure, maintain a minimum of 6.0 inches (152.4


millimeters) clearance above or below the SMC-50. Side-to-side clearance is not
required.
Catalog Number Approximate Shipping Weight
150-SB1
150-SB2
150-SB3

15.7 kg
34.6 lb

150-SB4

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

19

Chapter 2

Installation & Wiring

Figure 5 - Dimension of Cat. No. 150-SB1SB4 Controller with Terminal Covers


6.98
(177.4)
7.62
(193.7)

3.86
(97.9)

20.13
(511.3)

1.40
(35.6)

9.22
(234.1)
9.93
(252.3)
10.19
(258.9)

1.54
(39.0)

Note: When mounted in an enclosure, maintain a minimum of 6.0 inches (152.4


millimeters) clearance above or below the SMC-50. Side-to-side clearance is not
required.
Catalog Number

Approximate Shipping Weight

150-SB1
150-SB2
150-SB3

15.92 kg
35.1 lb

150-SB4

20

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Cat. No. 150-SC Controllers


Figure 6 - Dimensions of Cat. No. 150-SC1SC3 Controller
10.75
(272.9)

9.84 (250)
7.17 (182.1)
0.67
(17)

9.11
(231.3)

2.47
(62.8)

3.92 (99.6)

2.00
(50.8)

See detail A
0.25
(6.4)

9.30
(236.2)

23.25
(590.6)

24.08
(611.6)

24.24
(615.7)

25.14
(638.5)

0.281 dia.

2.00
(50.8)
2.09
(53.1)

1.16
(29.5)

2.09
(53.1)

0.413 dia
(10.49) 2 holes

0.53
(13.5)

5.34 (135.6)

7.19
(182.6)

7.66 (194.6)

0.98
(25)

9.84 (250)
10.75
(273.1)

Detail A

Note: When mounted in an enclosure, maintain a minimum of 6.0 inches (152.4


millimeters) clearance above or below the SMC-50. Side-to-side clearance is not
required.
Catalog Number Approximate Shipping Weight
150-SC1
150-SC2

47.6 kg
105 lb

150-SC3

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

21

Chapter 2

Installation & Wiring

Figure 7 - Dimensions of Cat. No. 150-SC1SC3 Controller with Lugs, Bypass Kit,
and MOV options
6.08
(154.4)

0.35
(8.8)

3.08
(78.2)
1.44
(36.5)

1.02
(26)

0.53
(13.4)

23.25
(590.6)

26.17
(664.6)

1.70
(43.2)

26.84
(681.8)

27.23
(691.6)

2.14
(54.2)
1.44 (36.5)
8.23
(209.2)

3.15
(80)

Note: When mounted in an enclosure, maintain a minimum of 6.0 inches (152.4


millimeters) clearance above or below the SMC-50. Side-to-side clearance is not
required.
Catalog Number Approximate Shipping Weight
150-SC1
150-SC2

47.6 kg
105 lb

150-SC3

22

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Cat. No. 150-SD Controllers


Figure 8 - Dimensions of Cat. No. 150-SD1SD3 Controller
1.13 (28.7) dia.
lifting holes (4)

15.00 (381)
10.69
(271.5)

5.05
(128.3)

11.64 (295.8)
9.96 (253)
8.68 (220.5)

See detail A
0.39 (10) dia.
mounting holes (4)

2.04 (51.7)
0.25 (6.4)

1.31 (33.3)
3.00 (76.2)
1.53
(38.9)
0.69
(17.5)

9.21
(233.8)

2.13
(54)

Detail A

0.53 dia.
(13.5) 12 holes

26.43
(671.3)
25.25
(641.4)

25.88
(657.3)

3.156
3.156
(80.16)
(80.16)
7.844 (199.24)
10.908 (277.06)
15.00 (381)
17.38 (441.5)
18.00 (457.2)

27.25
(692.2)

0.400 dia.
8.63 (219.2)

Note: When mounted in an enclosure, maintain a minimum of 6.0 inches (152.4


millimeters) clearance above or below the SMC-50. Side-to-side clearance is not
required.

Catalog Number Approximate Shipping Weight


150-SD1
150-SD2

77.1 kg
170 lb

150-SD3

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

23

Chapter 2

Installation & Wiring

Figure 9 - Dimensions of Cat. No. 150-SD1SD3 Controller with Lugs, Bypass Kit,
and MOV options
8.68
(220.5)

1.54
(39.2)

0.33
(8.5)

3.49
(88.5)

25.25
(641.4)

28.58
(726)

29.79
(756.8)

2.41
(61.2)
1.82
(46.2)

1.44 (36.5)
10.08 (256)

Note: When mounted in an enclosure, maintain a minimum of 6.0 inches (152.4


millimeters) clearance above or below the SMC-50. Side-to-side clearance is not
required.
Catalog Number Approximate Shipping Weight
150-SD1
150-SD2

77.1 kg
170 lb

150-SD3

Power Factor
Correction Capacitors
(PFCC)

The SMC-50 controller can be installed on a system with PFCCs. The PFCCs
must be located on the line side of the controller. This must be done to prevent
damage to the silicon-controlled rectifiers (SCRs) in the controller power
section.
When discharged, a capacitor essentially has zero impedance. For switching,
sufficient impedance should be connected in series with the capacitor bank to
limit the inrush current. One method for limiting the surge current is to add
inductance in the capacitors conductors. This can be accomplished by creating
turns or coils in the power connections to the capacitors.

24

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

250V 150 mm (6 in.) diameter coil, 6 loops


480690V 150 mm (6 in.) diameter coil, 8 loops
Figure 10 and Figure 11 show a typical system wiring diagram using PFCCs.
DO NOT mount the coils directly on top of one another. Doing so will
cause a cancelling effect. To avoid parts acting as induction heaters, DO
mount the coils on insulated supports away from metal parts. If an
isolation contactor is used, DO place the capacitors in front of the
contactor. For further instructions, consult the PFC capacitor vendor.

IMPORTANT

Figure 10 - PFCC
L1/1

T1/2

L2/3

T2/4

L3/5

T3/6

3-Phase
M

Input Power

Branch
Protection

SMC-50
Controller

Power Factor
Correction Capacitors
1

Customer Supplied.

Figure 11 - PFC Capacitors & Contactor


L1/1

T1/2

L2/3

T2/4

L3/5

T3/6

3-Phase
Input Power
2

Branch
Protection

M
1

SMC-50
Controller

Power Factor
Correction Capacitors
1

Customer Supplied.
Energize for 1/2 of a second before starting command to SMC-50.
Open contactor after the stopping method is complete.
Alternate:
The alternate method can be accomplished with an Aux Output configured for UTS (up-to-speed).
Energize the contactor after motor is up to speed.
Open the contactor before initiating a stop.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

25

Chapter 2

Installation & Wiring

Protective Modules

A protective module (see Figure 12) containing MOVs (Metal Oxide Varistors)
should be installed to protect the SMC-50 power components from electrical
transients and/or electrical noise.
Protective modules can be installed on controllers rated from 200600V to
protect the power components from electrical transients. The protective modules
clip voltage transients generated on the lines to prevent such surges from
damaging the SCRs. The use of MOVs are highly recommended, as 480V and
600V MOVs offer maximum protection of 1400V and 1600V respectively.
NOTE:

Protective modules are not available for 690V applications.

Figure 12 - Protective Module

PR
OT
EC
TIV
EM
OD
ULE
MA

X. L

INE

IMPORTANT

M
VO ADE IN
LTA U
GE .S.A

Protective modules may be placed on the line, load, or both sides of the
SMC-50. However, protective modules must not be placed on the
load side of the SMC-50 when using inside-the-delta motor
connections or with pump, linear speed, or braking control.

There are two general situations that may occur which would indicate the need
for using the protective modules.
1. Transient Spikes Transient spikes will typically occur on the lines
feeding the SMC-50 or feeding the load from the SMC-50. Transient
spikes are created on the line when devices are attached with currentcarrying inductances that are open-circuited. The energy stored in the
magnetic field is released when the contacts open the circuit. Examples of
these are: lightly loaded motors, transformers, solenoids, full voltage
starters, and electromechanical brakes.

26

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

2. Fast-rising Wavefronts If the SMC-50 is installed on a system that has


fast-rising wavefronts present, although not necessarily high peak voltages,
protective modules may be needed. Additionally, if the SMC-50 is on the
same bus as other SCR devices (e.g. AC/DC drives, induction heating
equipment, or welding equipment), the firing of the SCRs in those devices
can cause noise.
ATTENTION: When installing or inspecting the protective module, make
sure that the controller has been disconnected from the power source.
The protective module should be inspected periodically for damage or
discoloration. Replace if necessary.

Motor Overload Protection

Thermal motor overload protection is provided as standard with the SMC-50. If


the overload trip class is less than the acceleration time of the motor, nuisance
tripping may occur.
ATTENTION: Overload protection should be properly coordinated with
the motor.

Two applications require special consideration: two-speed motors and


multi-motor protection.

Two-Speed Motors
The SMC-50 has overload protection available for single-speed motors. When
the SMC-50 is applied to a two-speed motor, the Overload function must be
disabled via Parameter #230Motor Fault En and separate overload relays must
be provided for each speed.

Multi-Motor Applications
The SMC-50 will operate with more than one motor connected to it. Motors
should be mechanically coupled. To size the controller, add the total nameplate
amperes of all of the connected loads. The stall and jam features should be turned
off. Separate overloads are still required to meet the National Electric Code
(NEC) requirements.
IMPORTANT

The SMC-50s built-in overload protection cannot be used in multi-motor


applications. Disable the SMC-50 Overload function using Parameter
#230Motor Fault En

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

27

Chapter 2

Installation & Wiring

Figure 13 - Multi-Motor Application


L1/1

T1/2

L2/3

T2/4

L3/5

T3/6

3-Phase

Motor
Number 1

Input Power

Branch 1
Protection

SMC-50
Controller

Overload Relay
(O.L.)

Motor
Number 2
1

O.L.

Customer supplied.

Disable the SMC-50 Overload function using Parameter #230Motor Fault En.

SMC-50 Controller as a Bypass to an AC Drive


By using the SMC-50 controller in a typical application, as shown in Figure 14, a
soft start characteristic can be provided in the event that an AC drive is
non-operational.
IMPORTANT

A controlled acceleration can be achieved with this scheme.

Figure 14 - Typical Application Diagram, Bypass Contactor for an AC Drive


AF

AF

3-Phase

O.L.

VFD

Input Power
VFD Branch
Protection

3
1

IC

L1/1

T1/2

L2/3

T2/4

L3/5

T3/6

SMC-50 4
Controller

IC

Mechanical interlock required.

Customer supplied.
Many variable speed drives (VFDs) are rated 150% full load amperes (FLA). Since the SMC-50 can be used for
600% FLA starting, separate branch circuit protection may be required.

Overload protection is included as a standard feature of the SMC-50.

28

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Motor Winding Heater


Capability

Chapter 2

SMC-50 Internal Motor Winding Heater Function


The SMC-50 motor winding heater function provides low levels of current to
each of the motor windings to preheat a cold motor before starting. To avoid
stressing a single motor winding, the SMC-50 cycles the current to the three
motor phases. This feature provides a programmable heating level, heating time,
and terminal block input.
The motor winding heater can be activated after a valid start command is
received. After a valid start, the activation of the heating function can be
performed by programming the Heating Time parameter to a non-zero value or
by configuring a terminal block input to "Motor Heater" and activating that input
prior to the start command. The heater function will continue for the specified
time or until the input is deactivated, at which time the motor will start.
The heater function will be disabled if the parameter Heater Level is set to zero or
the parameter Heater Time is set to zero and the input is inactive (or not
configured) at the time of the start command.

SMC-50 with an External Bulletin 1410 Motor Winding Heater


In addition to using the SMC-50 internal motor heater feature, an external
Bulletin 1410 motor winding heater can be used. A typical application diagram is
shown below in Figure 15.
Figure 15 - SMC-50 with an External Bulletin 1410 Motor Winding Heater
IC 1
L1/1

T1/2

L2/3

T2/4

L3/5

T3/6

O.L. 1

3-Phase
M 1

Input Power

SMC-50 Controller 2
HC 1

Bulletin 1410 Motor 1


Winding Heater

Customer supplied.
Overload protection is included as a standard feature of the SMC-50.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

29

Chapter 2

Installation & Wiring

Electromagnetic
Compatibility (EMC)

ATTENTION: This product has been designed for Class A equipment. Use
of the product in domestic environments may cause radio interference, in
which case the installer may need to employ additional mitigation
methods.

The following guidelines are provided for EMC installation compliance.

Enclosure
Install the product in a grounded metal enclosure.

Wiring
Wire in an industrial control application can be divided into three groups: power,
control, and signal. The following recommendations for physical separation
between these groups is provided to reduce the coupling effect:
Different wire groups should cross at 90 inside an enclosure.
Minimum spacing between different wire groups in the same tray should
be 16 cm (6 in.).
Wire runs outside of an enclosure should be run in conduit or have
shielding/armor with equivalent attenuation.
Different wire groups should be run in separate conduits.
Minimum spacing between conduits containing different wire groups
should be 8 cm (3 in.).
For additional guidelines, please see the installation instructions, Wiring
and Ground Guidelines, publication DRIVES-IN001*.

Additional Requirements
Wire earth ground to control terminal #3 control ground.
Use shielded wire for PTC and ground fault input.
Terminate shielded wires to the control module terminal #3 control
ground.
Ground fault CT must be inside or within 3 m (9.84 ft.) of metal
enclosure.
When an external HIM is used, a ferrite core must be placed around the
HIM cable. The recommended core is Fair-Rite Products, Corp. part
no. 0461164181 or equivalent.
For additional PTC, external CT, and ground fault requirements, see footnote
of Figure 28 on page 46.

30

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Wiring Terminal Locations

Chapter 2

The SMC-50 wiring terminal locations are shown in Figure 16. Incoming
three-phase power connections are made to terminals L1/1, L2/3, and L3/5.
Load connections to motors are made to T1/2, T2/4, and T3/6.
Figure 16 - Wiring Terminal Locations

L1/1

L2/3

L3/5

Incoming Three-Phase Power Connections


1

L1/1

L2/3

L3/5

T1/2

T2/4

T3/6

1
T1/2

T2/4

T3/6

Load Connections to Motors 2


See Table 4 for lug information.
Inside-the-delta connected motors require an additional delta distribution block. See Table 4.

For controllers rated 210520 A, a grounding nut (size 1/4-20) is provided for
grounding per applicable local codes.

Power Structure

The SMC-50 power structure is a solid-state SCR (silicon-controlled rectifier)


design capable of interfacing with 200480V AC or 200690V AC (690V line
and 600V inside-the-delta) motors. Released product will handle motor current
from 90520 A. The power structure incorporates true current-sensing and over
temperature protection. If the application requires, an external bypass contactor
may be utilized. See page 91.

Power Wiring
See the product nameplate or Table 4 for power lug termination information
including:
lug wire capacity
tightening torque requirement
lug kit

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

31

Chapter 2

Installation & Wiring

ATTENTION: Failure of solid-state power switching components can


cause overheating due to a single-phase condition in the motor. To prevent
injury or equipment damage, the following is recommended:
Use an isolation contactor or shunt trip type circuit breaker on the line side of
the SMC-50. This device should be capable of interrupting the motors lock
rotor current.
Wire the isolation contactors control relay to an auxiliary relay output
contact on the SMC-50. This will achieve coordinated operation with the
SMC-50. The auxiliary relay contact should be programmed for the normal
condition. See Chapter 5, Programming, for additional information.

Line Connected Motors


The SMC-50 can be connected to a line-controlled motor (see Figure 17). This
type of motor typically has three leads. The SMC-50 automatically detects the
motor wiring configuration during the tuning process. Since there is a small
amount of leakage current passing through a non-conducting SCR, it is
recommended that an Isolation Contactor (IC) be added to the circuit to provide
galvanic isolation of the motor and final electromechanical removal of power.
Figure 17 - SMC-50 Connected to a Line-Controlled Motor
2
IC 1

SMC-50

5/L3

2
6/T3

IC 1
3/L2

4/T2

1/L1

2/T1

M
3~

IC 1

Recommended.
See Table 4 for lug information.

Delta Connected Motors


The SMC-50 has the ability to run Wye-Delta motors in an inside-the-delta
configuration. These motors typically have 6 or 12 leads. The SMC-50
automatically detects the motor wiring configuration during the tuning process.
In a delta configuration, it is required that an isolation contactor (IC) be added
32

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

to the circuit to provide galvanic isolation of the motor and final


electromechanical removal of power.
Figure 18 - SMC-50 Connected to a Delta Connected Motor
Delta
Distribution Block 2
L3

L3

L2

L2

T4

L1

T6

L1
IC

SMC-50

L3/5

T3/6

L2/3

T2/4

L1/1

T1/2

T3

T6

T5

Motor

T2
T1

T5
T4

Required.
See Table 4 for lug and delta distribution block information.

Grounding Provision

Provision for connecting a field-installed grounding conductor is provided on


controllers rated 210520 A. The grounding location is identified by the green
grounding nut (size 1/4-20) near the controllers bottom mounting holes.

Power Lugs

Power lugs are required for devices rated 90520 A. These lugs are sold in kits.
Each kit contains three lugs. The number and type of lugs required is listed in
Table 4.
ATTENTION: Line and load terminal covers that can give units rated
90180 A deadfront protection (IP2X with 250-MCM cable) are
available. See Appendix E for the appropriate catalog numbers for
ordering.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

33

34
Lug-Bus

Line/Wye
23 Nm
(200 lbin.)

Inside-the-Delta
23 Nm
(200 lbin.)

23 Nm
(200 lbin.)

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Delta Distribution Block

SMC Lugs

Lug Kit No.

Wire Strip
Length [mm]

Conductor Range

42 Nm
(375 lbin.)

28 Nm
(250 lbin.)

Inside-the-Delta

625900

45
Marathon
Special Products
1352702

Marathon Special
Products
1353703
Allen-Bradley
1492-BG

45

54400 mm2
(1/0750 MCM)

54400 mm2
(1/0750 MCM)

Top Row = 23
Bottom Row = 48

45

16120 mm2
(#6250 MCM)

54400 mm
(1/0750 MCM)

35

35

Line
Load

25240 mm2
(#4500 MCM)

25240 mm
(#4500 MCM)

Load

Line

67.8 Nm
(600 lbin.)

31 Nm
(275 lbin.)

199-LG1

1825

42 Nm
(375 lbin.)

199-LG1

1825

Load

199-LF1

1820

67.8 Nm
(600 lbin.)

199-LF1

1820

67.8 Nm
(600 lbin.)

199-LF1

1820

42 Nm
(375 lbin.)

199-LF1

Lug Kit Cat. No.

Qty

42 Nm
(375 lbin.)

28 Nm
(250 lbin.)

Line/Wye

361520

Line

1820

Torque

31 Nm
(275 lbin.)

23 Nm
(200 lbin.)

Inside-the-Delta

363554

150-SD

16120 mm2
25240 mm2
16120 mm2 16120 mm2 16120 mm2
25240 mm2
(#6250 MCM) (#6250 MCM) (#6250 MCM) (#6250 MCM) (#4500 MCM) (#4500 MCM)

Line Side
Load Side

31 Nm
(275 lbin.)

31 Nm
(275 lbin.)

31 Nm
(275 lbin.)

Wire-Lug

Wire Strip
Length [mm]

Conductor Range

Max No. Lugs/Pole

Torque

Configuration

Line/Wye

90180

210320

150-SC

155311

150-SB

Rating [A]

Cat. No.

Chapter 2
Installation & Wiring

Table 4 - Power Wiring Information

Installation & Wiring

Control Power

Chapter 2

Control Power Ratings


The SMC-50 can accept control power input of 100240V AC (-15%+10%)
or 24V DC (-10%+10%). A minimum control power source is required. See
Table 5. This base control power requirement is for the control module with fan.
The control power requirement for the fan is supplied by the control module and
auto-configured. The control module and option module control power
requirements are shown in Table 5.
Table 5 - Control Power Requirements (Max. Control Circuit Consumption)
Description
Base Power Draw: Control
Module with Heat Sink Fan

Optional Power Adder (for


each option installed, add to
base power)

Current Range [A]


90180
210320
361520
Human Interface Module (HIM)
150-SM2
150-SM3

Control Voltage
100240V AC
24V DC
150 VA
75 W
150 VA
75 W
300 VA
300 W
10 VA
2W
30 VA
4W

150-SM4

30 VA
50 VA

4W
2W

150-SM6

5 VA

1W

20-COMM-X

25 VA

4W

Add to Base power to obtain total power requirements.


Max. 1 of each option type per control module

Each control terminal is removable and will accept a 14 AWG maximum and
24 AWG minimum wire size. The terminals are UL Recognized to accept a
maximum of two 16 AWG wires per terminal. See the product nameplate prior to
applying control power.
Table 6 provides the terminal wire capacity, the tightening torque requirements,
and the wire strip length for all SMC-50 control wiring and option module
wiring.
Table 6 - Control and Option Module Wiring Specifications
Wire Size

0.2...2.5 mm2 (#24...14 AWG)

Maximum Torque

0.8 Nm (7 lbin.)

Maximum Wire Strip Length 7 mm (0.27 in.)


Screw Type

Fan Power

M3 Slotted

The SCR heat sink fan of the SMC-50 is located at the bottom of the power
assembly. The fan is designed to cycle ON/OFF as necessary to cool the assembly
SCRs. The fan and fan cover are field replaceable. See Appendix C.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

35

Chapter 2

Installation & Wiring

Fan Terminations
The fan is self powered from the power applied to Control Terminals 1 and 2 on
the control module. Fan power is automatically configured based on control
power. No user connections or configuration is required.

Control Terminal
Designations

As shown in Figure 19, the SMC-50 contains 12 control terminals and is


equipped as standard with two digital 24V DC on/off inputs and two relay
outputs for auxiliary control function.

10

In1 DC

In2 DC

8
Intl DC Common

11

Enable I/O

12
Intl +24V DC

Figure 19 - Standard Digital I/O Wiring Terminal Block Identification

24V DC Inputs

7
Aux 2

-L2

+L1

Aux 1

Relay Outputs

Control
Power
& Ground

ATTENTION: IN1 DC (terminal 11) and IN2 DC (terminal 10) are 24V DC
inputs on controllers rated 120/240V AC AND 24V DC. Voltages exceeding
specified input range may cause damage to the controller.

Terminal Number Description


1

Control Power +L1

Control Power Common -L2

Ground To connect to the system/control ground point.

Auxiliary Relay Contact #1

Auxiliary Relay Contact #1

Auxiliary Relay Contact #2

Auxiliary Relay Contact #2

DC Internal I/O Power, DC Common

Enable I/O

10

Input #2 (24V DC) (range 1530V DC)

11

Input #1 (24V DC) (range 1530V DC)

12

+24V DC Internal I/O Power

Do not connect any additional loads to this terminal. Parasitic loads may cause problems with
operation.
When set to external bypass mode, the auxiliary contact is used to control a properly sized
external contactor and overload once the motor is at full speed.
RC snubbers are required when inductive loads are connected to terminal.

36

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

SMC-50 Option Modules

Chapter 2

The SMC-50 has three expansion ports to place optional modules (see Figure
20). These ports provide the capability to add control modules (e.g., additional
inputs and outputs (I/O), simple start/stop parameter configuration capability,
ground fault, etc.). Brief functional explanations are provided here with the
wiring termination identifications. See Chapter 5, Programming, for more
detailed functional and configuration information. See Figure 20 for compatible
port locations of the selected module.
ATTENTION: There is the potential to have voltage values above 220V
AC on the option modules. Before removing the control module cover to
access option modules, disconnect ALL power to the SMC-50 Controller.
Figure 20 - Port Number Identification
Expansion Port
for 20-HIM-A6 (DPI Port 1)

DPI Port 4

Control Module
Expansion Port 7

Control Module
Expansion
Port 9

Control Module
Expansion Port 8

Table 7 - Port Location for Compatible Option Modules


Compatible Control
Maximum Number of this
SMC-50 Control Module
Module Port
Type of Option Module
Compatible Option Modules Cat. Nos.
Port 7 Port 8 Port 9 per Control Module
150-SM2: Ground Fault/PTC/External CT

Yes

Yes

No

150-SM3: Analog I/O

Yes

Yes

Yes

150-SM4: Digital I/O

Yes

Yes

Yes

150-SM6: Parameter Configuration

Yes

Yes

Yes

20-COMM-X : Communications

No

No

Yes

See Chapter 8, Communications on page 205 for a list of compatible 20-COMM-X modules.
When installed in an SMC-50 controller, 20-COMM-X modules physically reside in the space assigned to Port 9,
but connects to DPI Port 4 with the ribbon cable that is supplied with the module.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

37

Chapter 2

Installation & Wiring

Optional Cat. No. 150-SM4 Digital I/O Module


A Cat. No. 150-SM4 Digital I/O Option Module provides four 120...240V AC
digital on/off inputs and three relay outputs to provide additional auxiliary
control or indications (e.g., up-to-speed (UTS), alarm, etc.) functions. The
150-SM4 module can be located in any of the three control module option ports
(See Figure 20). Up to three 150-SM4 modules can be used with a single control
module. The 150-SM4 module terminal block used to wire the I/O is removable.
1 When installed in Control Module Port 7, the orientation of the module
terminal block is rotated 180 along with its terminals.
NOTE:

2 The Cat. No. 150-SM4 Digital I/O Module can NOT be configured using a
150-SM6 PCM. This module can be configured using a 20-HIM-A6, network card,
or communications software (e.g., Connected Components Workbench).

A1

A2

A3

A4

A5

InA1

InA2

InA3

InA4

InCOM

Figure 21 - Optional Digital I/O Module Terminal Id

A6

A7

A8

A9 A10 A11 A12


NC

Aux A2

Aux A1

120V/240V AC Inputs

Aux A3

Relay Outputs

Terminal Number

Description

A1

Optional Input #1 (120/240V AC)

A2

Optional Input #2 (120/240V AC)

A3

Optional Input #3 (120/240V AC)

A4

Optional Input #4 (120/240V AC)

A5

Input Common

A6

Optional Auxiliary Relay Contact #1

A7

Optional Auxiliary Relay Contact #1

A8

Optional Auxiliary Relay Contact #2

A9

Optional Auxiliary Relay Contact #2

A10

Optional Auxiliary Relay Contact #3

A11

Optional Auxiliary Relay Contact #3

A12

NO CONNECT

Do not connect additional loads to this terminal. Parasitic loads may cause problems with
operation.
When set to external bypass mode, the auxiliary contact is used to control a properly sized
external contactor and overload once the motor is at full speed.
RC snubbers are required when inductive loads are connected to terminal.

38

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Optional Cat. No. 150-SM3 Analog I/O Module


An optional Cat. No. 150-SM3 Analog I/O Module provides two analog inputs
(voltage or current) and two analog outputs (voltage or current), seeTable 8 for
specifications.
The 150-SM3 module can be located in any of the three control module option
ports (See Figure 20). Up to three 150-SM3 modules can be used with a single
control module. The 150-SM3 module terminal block used to wire the I/O is
removable.
1 When installed in Control Module Port 7, the orientation of the module
terminal block is rotated 180 along with its terminals.
NOTE:

2 The Cat. No. 150-SM3 Analog I/O Module can NOT be configured using a
150-SM6 PCM. This module can be configured using a 20-HIM-A6, network card,
or communications software (e.g., Connected Components Workbench).

Figure 22 - Analog I/O Module Wiring Diagram


Voltage
or Current
Load

Voltage
or Current
Load

Voltage
Transmitter

or

Voltage
Transmitter

Current
Transmitter

or

Current
Transmitter

NC

B1

B2

B3

B4

B5

B6

B7

B8

B9

B10

B11

B12

V/I
OUT
1+

V/I
OUT
1-

V/I
OUT
2+

V/I
OUT
2-

V
IN
1+

I
IN
1+

V/I
IN
1-

V
IN
2+

I
IN
2+

V/I
IN
2-

NC

Control
Ground

Output #1

Output #2

Input #1

Input #2

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

39

Chapter 2

Installation & Wiring

Table 8 - Cat. No. 150-SM3 Input and Output Specifications


Control Circuit

150-SM3
Optional inputs:
Terminals B5B10

150-SM3
Optional outputs:
Terminals B1B4

40

Specification
Number of Inputs

2 differential inputs

Normal Operating Input Ranges

10V, 010V, 05V, 15V, 020 mA, 420 mA

Full Scale Operating Input Ranges

10.5V, 010.5V, -0.55.25V, 0.55.25V, 021 mA, 3.521 mA

Input Resolution

16 bit (sample rate = 60 Hz)/13 bit (sample rate = 250 Hz)

Data Refresh Rate:

Filter dependent: 100 ms (sample rate = 60Hz);24 ms (sample rate = 250Hz)

Rated Working Voltage

24V DC / 17V AC

Common Mode Voltage Range

10V DC / channel

Input Impedance

220 k: voltage mode


249 : current mode

Input Channel Diagnostics

Over and Under Range and Open Circuit

Open Circuit Detection Time

Positive Full Scale Reading: within 3 seconds (max)

Maximum Overload at Input Terminals

Voltage: 24V DC continuous at 0.1 mA


Current: 30 mA continuous at 7V DC

External Calibration

Not required: auto-calibration performed by the module if required to meet


specs.

Module Isolation to Control Board

Yes (1000V AC)

Removable Terminal Block

Yes (Cat. No.150-SM3RTB as a spare replacement part)

Cable Type

Belden 8760 (or equiv.) 0.750 mm2 (18 AWG twisted pair 100% shield with drain)

Number of Outputs

2 Single-ended

Normal Operating Ranges

10V, 010V, 05V, 020 mA, 420 mA

Full Scale Operating Ranges

10.5V, 010.5V, -0.55.25V, 021 mA, 3.521 mA

Output Resolution
10.5V, 0 10.5V, -0.55.25V,, 021
mA, 3.5 21 mA

16 bit (15 plus sign bipolar)

Resistive Load on Current Output

0750

Load Range on Voltage Output

1 k at 10V DC

Max. Inductive Load (Current Outputs)

15 mH

Max. Capacitive Load (Voltage Outputs)

100 F

Overall Accuracy

Voltage Terminal: 0.5% full scale at 25 C


Current Terminal: 0.35% full scale at 25 C

Accuracy Drift with Temperature

5 PPM / C

Output Impedance

15 (typical)

Open and Short-Circuit Protection

Yes

Maximum Short-Circuit Current

45 mA

Output Overvoltage Protection

Yes

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Optional Cat. No. 150-SM2 Positive Temperature Coefficient (PTC),


Ground-Fault, & External Current Transformer Option Module
An optional Cat. No. 150-SM2 module provides connectivity to external PTC
motor winding temperature sensors, ground-fault, and current transformer
sensors.
The 150-SM2 module can be located in control module Port 7 or 8. Only one
150-SM2 module is allowed to be used with the control module (See Figure 20).
All of the individual terminal blocks (TB2, TB3, and TB4) are removable. The
RG25U female connector provides a connection point for the male-to-male cable
provided with the 825-MCM current sensor/converter module.
1 When installed in Control Module Port 7, the orientation of the module
terminals is rotated 180 along with its terminals.
NOTE:

2 The Cat. No. 150-SM2 Option Module can NOT be configured using a
150-SM6 PCM. This module can be configured using a 20-HIM-A6, network
card, or communications software (e.g., Connected Components Workbench).

Figure 23 - Circuit Board

150-SM2 Module Circuit Board


RG25U
Female

TB4

Control Ground

PTC & GF
Shield Wire

TB4

825-MCM
Cable

Ground Fault

TB3

Ground Fault

TB2

PTC

TB3

PTC

TB2

Positive Temperature Coefficient (PTC) Sensor Motor Temperature


Sensing:
The optional 150-SM2 module provides the ability for the SMC-50 to interface
with motor PTC sensors. PTC thermistor sensors are commonly embedded in
motor stator windings by the motor manufacturer to provide temperature
monitoring of the motor windings. Since PTC thermistor sensors react to the
actual motor winding temperature, enhanced motor protection can be provided
to address such conditions as obstructed motor cooling and high ambient
temperature. The following table defines the required PTC thermistor input and
response ratings for operation with the 150-SM2.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

41

Chapter 2

Installation & Wiring

Table 9 - PTC Thermistor Input & Response Ratings


Thermistor Input

Response Ratings

Response Resistance:

3400 150

Reset Resistance:

1600 100

Short-circuit Trip Resistance:

25 10

Maximum Voltage at PTC Terminals: (RPTC = 4 K ohms):

< 7.5V

Maximum Voltage at PTC Terminals: (RPTC = open):

30V

Maximum Number of Sensors Connected in Series:

Maximum Cold Resistance of PTC Sensor Chain:

1500

Response Time:

800 ms

The following figure shows the required PTC sensor characteristics for operation
with the 150-SM2 Option Module, per IEC-34-11-2.
Figure 24 - PTC Sensor Characteristics per IEC-34-11-2
4000
1330
550
250
100

20
TNF -20K
TNF -5K
TNF +5K
TNF +20K

0 C

-20 C

10

TNF

For additional information concerning the configuration and diagnostic


information provided by the PTC part of the 150-SM2 Option Module, see
Chapter 5, Programming.

Ground Fault Sensing


In isolated or high impedance-grounded systems, core balanced current sensors
are typically used to detect low-level ground faults which could be due to motor
insulation breakdown or entry of foreign objects. Detection of ground faults can
be used to prevent further damage or alert personnel to perform maintenance.
The SMC-50 can provide ground fault indication when used with the 150-SM2
Option Module and the 825-CBCT External Ground Fault (Core Balance)
Current Sensor. The ground fault current sensor mounts separately from the

42

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

SMC-50 and must be placed within three meters of the SMC-50. A


customer-supplied cable for wiring the ground fault sensor to the 150-SM2
module must meet the requirements outlined in Table 10.
WARNING: The ground fault sensing feature of the SMC-50 is intended
for monitoring purposes only. It is not intended as a ground fault circuit
interrupter for personnel protection as defined in Article 100 of the
National Electric Code (NEC) and has not been evaluated to UL 1053.
Table 10 - Ground Fault Sensor Cable Requirements
Wire Type:

Shielded, twisted pair

Wire Size:

0.22.5 mm2 (#2414 AWG)


0.8 Nm (7.0 lbin.)

Terminal Torque:

See Figure 28 on page 46 for wiring details.


Figure 25 - 825-CBCT Dimensions
+

35
(1.38)

150
(5.91)

9.0
(0.35)

200
(7.87)
175
(0.69)

110
(4.33)

80
(3.15)
175
(6.90)

External Current Transformer Current Sensing in Bypass Mode


The 150-SM2 Option Module and an external current sensing device (e.g.,
825-MCM) can be used to provide current feedback to the SMC-50 when it is
used with an external bypass contactor. The external current feedback device
provides all current measurement and current protection functions while the
controller is in external bypass mode (running). A single 825-MCM Converter
provides external current feedback from all three motor phases. In all other
modes (e.g., starting, stopping, slow speed), the SMC-50s internal current
feedback signals are used.
NOTE:

External CTs can be used and enabled even without an external bypass.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

43

Chapter 2

Installation & Wiring

The following table provides the 825 converter to use based on the motor FLC
range.
Table 11 - 825 Converter Selection
Motor FLC Range

Catalog Number

30180 A

825-MCM180

181520 A

825-MCM20

User-supplied current transformers with 5 A secondary are required. See Figure 26.

Figure 26 - Current Transformer Connection to Converter Module


Current Transformer

L1

L2

L3

Converter Module

T1

T2

T3

Another current transformer connects L2 and T2, and another connects L3 and T3.
The converter module, Cat No. 825-MCM20, must be used in these applications.

To enable the 150-SM2 External CT function, the CT Enable parameter in the


150-SM2 must be set to "Enable" and the 825-MCM hardware must be correctly
configured. When the 150-SM2 External CT function is enabled, the external
CT is calibrated by the SMC-50 for scaling, phase shift, and inversion during the
SMC-50 tuning cycle. The tuning cycle will automatically occur before the first
start after the controller installation, after a "Load Default" parameter occurs, or
when the user forces tuning of the SMC-50 through the Force Tuning parameter
or the control modules Hold to Reset button. The scaling is displayed relative to
the units rating where 1.00 indicates that the external CTs and the internal CTs
are scaled the same.
Figure 27 shows the connection of the 825-MCM Converter to the SMC-50s
150-SM2 Option Module.

44

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 27 - Converter to Option Module Connection

825 Converter
Module

RG25U Male
Connection

150-SM2
Option Module

825-MCA Connection Cable 1


Provided as standard with the
825 Converter Module.

The cable length is fixed at 4 meters. Only the cable provided with the converter can be used. The use of any
other cable will result in incorrect data from the converter and incorrect controller operation.

The following table provides the terminal and wire specifications for the
150-SM2 (terminals TB2, TB3, and TB4).
Table 12 - Control and Option Module Wiring Specifications
Wire Size

0.2...2.5 mm2 (#24...14 AWG)

Maximum Torque

0.8 Nm (7 lbin.)

Maximum Wire Strip Length 7 mm (0.27 in.)


Screw Type

M3 Slotted

Figure 28 provides information for wiring all sensors to the 150-SM2 module.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

45

Chapter 2

Installation & Wiring

Figure 28 - Combined Wiring Diagram of all 150-SM2 Sensors

150-SM2 Module Circuit Board 5


TB2
TB2
2
1

RG25U
Female
RG25U
Male

TB3
TB3
1
2

TB4
TB4

Shield
Shield

Motor PTC
Sensor Cable

Bl

d
iel k
ac

Sh

825-MCM Cable 1 2

To Control
Module
Terminal #3
Ground

hit

1 2

M
(1)

825-MCM

T1/2

L1/1
Fast-Acting SCR 1
Fuses (optional)

SMC-50
T2/4

Circuit
Branch
Protection

L2/3

T3/6

L3/5
External Bypass 1 4

825-CBCT 1 3 6
Core Balance
Ground Fault
Sensor

Customer-supplied.
The 825-MCM can be used with or without an external bypass contactor. If an external bypass contactor is used then the 825-MCM must be installed in order to use
current-based motor protective features including the motor overload feature. Cable length is 4 meters. Only the cable provided with the 825-MCM is compatible with the
150-SM2. See Figure 29 for 825-MCM dimensions.
The 825-CBCT Core Balance Sensor mounts separately from the SMC-50 and must be placed within 3 meters of the SMC-50. When connecting the 825-CBCT ground-fault
sensor, the secondary of the CT must be shorted until connection to the 150-SM2 module is complete.
See Figure 44 on page 63 for additional bypass configurations (e.g., emergency run-off bypass) and application considerations.
To meet product susceptibility requirements, a single ferrite core must be placed around any or all sensor (e.g., PTC, ground fault, etc.) wires connected to the 150-SM2
Option Module. The recommended core is a Fair-Rite Products Corp Part Number 0431167281 or equivalent.
Ensure the 150-SM2 Turns Ratio, Parameter X.5, is configured to match the 825-CBCT Turns Ratio 100:1 (X.5=100).

46

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 29 - 825-MCM180 and -MCM20 Dimensions


5.3
(0.2)

5.3
(0.2)

55.0
(2.2) 118.0 (4.6)
or
85 (3.4)

38.5
(1.5)
100.0
(3.9)
120.0
(4.72)

72.0 (2.8)
or 66.0 (2.6)
102.0
(4.0)

Optional Cat. No. 150-SM6 Parameter Configuration Module


(PCM)
The Cat. No. 150-SM6 PCM provides simple and limited configuration of the
SMC-50. This PCM can be inserted into any control module option port (7, 8,
or 9).
This module contains five rotary dials and three banks of two-position,
eight-switch DIP switches.
Parameters that are configured by the PCM will appear as read-write parameters
to other configuration devices whose values represent the switch settings. The
parameter values set by the PCM are stored in the control module memory. If any
of these parameters are changed by an external device, the value will revert to the
PCM setting.
Parameters that are not defined and therefore are not configurable by the PCM
can be configured through other means (e.g., Human Interface Module (HIM),
DriveExplorer or DriveExecutive software), if necessary.
Only one (1) 150-SM6 Option Module can be installed in the control module.
Any of the three control module expansion ports can be used. A fault will be
generated if an attempt is made to install more than one 150-SM6 into the
control module.
A single PCM can be used to configure multiple SMC-50 controllers. After setup
of the initial SMC-50 is complete, remove all power and move the PCM to the
next SMC-50 that needs to be programmed. Upon powerup of the initial
SMC-50, the parameters set by the PCM are retained.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

47

Chapter 2

Installation & Wiring

Real Time Clock (RTC)


Battery Replacement

The SMC-50 Control Module comes standard with a RTC used to time and date
stamp Faults and Alarms. When the control power is not applied to the SMC-50,
the operation of the RTC is maintained by an off-the-shelf Lithium CR2032
coin cell battery. The battery must be replaced if the SMC-50s low battery alarm
is activated.
To replace the battery:
1. Perform the steps in Figure 97 on page 291 to remove the control module.
2. Locate the battery on the circuit board. Note the positive symbol is facing
upward.
Bottom Side of SMC-50
Remove and replace battery with postive (+)
symbol facing upward.

3. Remove the existing battery, disposing of it according to local


environmental codes.
4. With the positive symbol of the new battery facing upward, properly seat
the battery into place.
5. Perform the steps in Figure 98 on page 292 to replace the control module.
6. Reprogram/reset the clock.

48

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Standard Controller Wiring


Diagrams
T1/2

Figure 30 through Figure 42 show typical wiring diagrams for the SMC-50.
Figure 30 - For Standard 3-Wire Control DC Inputs, No DPI Control

L1/1

SMC-50
Soft Starter
M

T2/4

Fast-Acting SCR 1
Fuses (Optional)

Circuit
Protective
Device

L2/3

1 6

T3/6

Start

For 24V DC Controllers

24V DC
Power
Supply

10

In2 DC

Intl DC COM

11

Enable I/O

12

In1 DC

Intl +24V

3-Phase AC
Line Power

L3/5

120V/240V AC Control Transformer 2


or AC Power Supply

Stop

Chapter 2

6
Aux2

Control Module Standard I/O

-L2

+L1

Aux1
Control Mod
Power & Ground

Customer supplied.
See the controller nameplate to verify control power input ratings (100...240V AC or 24V DC).
Terminal 11 (In 1 DC) 24V DC input configured for START input using Parameter 56.
Terminal 10 (In 2 DC) 24V DC input configured for COAST, STOP option, etc. using Parameter 57.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is selected for COAST or STOP.
A customer supplied jumper is required to enable standard I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of off-stream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

49

Chapter 2

Installation & Wiring

Figure 31 - For 2-Wire Control with Stopping Capability DC Inputs, No DPI


Control

T1/2

L1/1
Circuit
Protective
Device

Fast-Acting 1
SCR Fuses (Optional)

M
1 5

T2/4

L2/3

T3/6

L3/5

Line Power

120V/240V AC Control Transformer 2


or AC Power Supply

For 24V DC Controllers

Start/Stop

3-Phase AC

24V DC
Power
Supply

4
2

12

11

10

In1 DC

In2 DC

Enable I/O

Intl DC COM

Intl +24V

Aux2

Control Module Standard I/O

-L2

+L1

Aux1
Control Mod
Power & Ground

Customer supplied.
See the controller nameplate to verify control power input ratings (100...240V AC or 24V DC).
Terminal 10 (In 2 DC) 24V DC N.O. input is configured for start/stop or start/coast using Parameter 57 (contact closed start initiated, contact open, stop initiated). When using
start/stop or start/coast, a N.O. input contact must be used.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is selected for COAST or STOP.
A customer-supplied jumper is required to enable controller standard I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
Configure In1 (Input 1 Parameter 56) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

50

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 32 - For 2-Wire Control with Stopping Capability AC Inputs, No DPI


Control

T1/2

L1/1

M
1

Circuit
Protective
Device

Fast-Acting 1
SCR Fuses (Optional)
T2/4

L2/3

3-Phase AC
Line Power

T3/6

L3/5

120V/240V AC Control Transformer 2


or AC Power Supply

1
1

Start/Stop

12

11

10

Intl +24V

In1 DC

In2 DC

Enable I/O

Intl DC COM

1 3

Aux2

A2

A3

A4

A5

InA1

InA2

InA3

InA4

InCOM

AC Inputs

A6

-L2

+L1

Aux1
Control Mod
Power & Ground

Control Module Standard I/O


A1

A7

AuxA1

A8

A9

AuxA2

A10

A11

A12
NC

AuxA3

Auxilliary Relay Outputs


150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify control power input ratings (100...240V AC).
Terminal A1 (InA1) 100...240V AC N.O. input is configured for start/stop or start/coast using Parameter 7-2 (control module port number 7) (contact closed, start initiated,
contact open, stop initiated). When using start/stop or start/coast, a N.O. input contact must be used.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is selected for COAST or STOP.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion slot option I/O module is located in on the control module.
However, the function associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

51

Chapter 2

Installation & Wiring

Figure 33 - For Dual Ramp Applications AC & DC Inputs

T1/2
L1/1
SMC-50
Fast-Acting SCR 1
Soft Starter Fuses (Optional)
T2/4
L2/3

M
1

T3/6

Circuit
Protective
Device
1

3-Phase AC
Line Power

L3/5
1

Ramp 1

Ramp 2

120V/240V AC Control Transformer


or AC Power Supply
1

Stop 1
Start

1
6

12

11

10

Intl +24V

In1 DC

In2 DC

Enable I/O

Intl DC COM

Aux2

Control Module Standard I/O

2
1
-L2 +L1

Aux1
Control Mod
Power & Ground
8

InCOM

InA4

99 99
A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12
NC
AuxA1 AuxA2 AuxA3
AC Inputs
Auxilliary Relay Outputs
150-SM4 Option I/O Module
InA3

InA1

A1

InA2

Customer supplied.
See the controller nameplate to verify control power input ratings (100...240V AC).
Terminal 11 (In 1 DC) 24V DC input configured for START input using Parameter 56.
Terminal 10 (In 2 DC) 24V DC input configured for COAST, STOP option, etc. using Parameter 57.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is selected for COAST or STOP.
Terminal A1 (INA1) 100...240V AC input is configured for Dual Ramp using Parameter 7-2 (control module port 7).
A customer supplied jumper is required to enable controller I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of off-stream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion slot option I/O module is located in on the control module.
However, the function associated with the terminal number remains the same.
Ensure that InA2, InA3, and InA4 are configured to "Disable" [Default].
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

52

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 34 - For Dual Ramp AC Inputs

T1/2
L1/1
SMC-50
Soft Starter
T2/4
L2/3

Circuit
Protective
Device

Fast-Acting 1
SCR Fuses (Optional)

1 6

T3/6

L3/5
2

Ramp 2
Stop

3-Phase AC
Line Power

120V/240V AC Control Transformer


or AC Power Supply

Ramp 1

Start
1 3
2

Enable I/O

Intl DC COM

11 10
In2 DC

12

In1 DC

Intl +24V

Aux2

Control Mod
Power & Ground

A6

InCOM

InA2

InA4

InA1

2
1
-L2 +L1

A7 A8 A9 A10 A11 A12


NC
AuxA3
AuxA1
AuxA2
Auxilliary Relay Outputs
AC Inputs
150-SM4 Option I/O Module
InA3

A2 A3 A4 A5

Aux1

Control Module Standard I/O


A1

Customer supplied.
See the controller nameplate to verify control power input ratings (100...240V AC).
Terminal A3 (InA3) 100...240V AC input configured for START input using Parameter 7-4 (control module port 7).
Terminal A2 (InA2) 100...240V AC input configured for COAST, STOP option, etc. using Parameter 7-3 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is selected for COAST or STOP.
Terminal A1 (InA1) 100...240V AC input is configured for Dual Ramp using Parameter 7-2 (control module port 7).
Due to current leakage through an SCR in the OFF state (controller stopped), some form of off-stream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion slot the option I/O module is located on the control in the control
module. However, the function associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

53

Chapter 2

Installation & Wiring

Figure 35 - For Start/Stop Control via HIM or Communications

T1/2

L1/1
Fast-Acting SCR 1
Fuses (optional)

SMC-50
Soft Starter
T2/4
L2/3

Circuit
Protective
Device

1 5

T3/6

3-Phase AC
Line Power

L3/5
2

120V/240V AC Control Transformer


or AC Power Supply

For 24V DC Controllers

24V DC
Power
Supply

10

Intl DC COM

11

Enable I/O

3
4

In2 DC

Intl +24V

12

3
4

In1 DC

+
2

-L2 +L1
Aux2

Control Module Standard I/O

Aux1
Control Mod
Power & Ground

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC or 24V DC).
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: If terminal 10 and 11 are required for a non Stop/Start function (e.g. slow speed), see Parameter 56 and Parameter 57 Communication Control word bits 0-5 for options.
For DPI operation, if the start/stop operation is done via communications (DPI port, 20-COMM module, or HIM) the appropriate bit (0...4) in the Logic Mask, Parameter 148,
must be set. See Chapter 8, Communications for additional details.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of off-stream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

54

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 36 - For Retrofit Applications AC Inputs, No DPI Control

M
1 5

L1/1
T1/2
SMC-50 Soft Fast-Acting SCR 1
Fuses (optional)
Starter
T2/4
L2/3

Circuit
Protective
Device

3-Phase AC

Line Power

M
T3/6

L3/5
Existing Motor
Starter 1 6

120/240V AC Control Transformer 2


or AC Power Supply

1
1

1 6

Stop

1 4

OL

Start

M 1

1
9

12

11

10

Intl +24V

In1 DC

In2 DC

Enable I/O

Int DC COM

Aux2

InA1

InA2

InCOM

InA4

A5 A6

InA3

A2 A3 A4

2
1
-L2 +L1

Aux1

Control Module Standard I/O


A1

A7 A8 A9

Control Mod
Power & Ground
A10 A11 A12
NC
AuxA3

AuxA1
AuxA2
AC Inputs
Auxilliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal A2 (InA2) 100...240V AC input configured for START input using Parameter 7-3 (control module port 7).
Terminal A1 (InA1) 100...240V AC input configured for Coast, Stop Option, etc, using Parameter 7-2 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. In this example, the Existing Motor Starter fulfills that requirement.
Due to existing motor starter overload protection, the overload protection should be disabled in the SMC-50 controller.
Set Aux 1 to NORMAL using Parameter 172. NORMAL = Aux 1 contact will close to energize the M coil with the START push button and will open to de-energize it when the
stop maneuver, initiated by the stop push button, is complete.
The order of the terminal numbers for the option I/O module cam be reversed depending on which expansion slot it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

55

Chapter 2

Installation & Wiring

Figure 37 - For Retrofit Applications DC Inputs, No DPI Control

M
1 6

L1/1
T1/2
SMC-50 Soft
Starter
T2/4
L2/3

Fast-Acting SCR 1
Fuses (optional)

Circuit
Protective
Device

M
T3/6

3-Phase AC
Line Power

L3/5
Existing Motor
Starter 1 7

120/240V AC Control Transformer


or AC Power Supply 2

1
1

Stop

Start

OL 1 7
4

M 1

1 3
5

12

11

10

Intl +24V

In1 DC

In2 DC

Enable I/O

Int DC COM

7
Aux2

2 1
-L2 +L1

Aux1

Control Module Standard I/O

Control Mod
Power & Ground

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal 11 (In1 DC) 24V DC input is configured for START input using Parameter 56.
Terminal 10 (In2 DC) 24V DC input configured for COAST, STOP OPTION, etc. using Parameter 57.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
A customer-supplied jumper is required to enable the controller I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. In this example, the existing Motor Starter fulfills that requirement.
Due to existing motor starter overload protection, the overload protection should be disabled in the SMC-50 controller.
Set Aux 1 to NORMAL using Parameter 172. NORMAL = Aux 1 contact will close to energize the M coil with the START push button and will open to de-energize it when the
stop maneuver, initiated by the stop push button, is complete.

56

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 38 - For Isolation Contactor Applications DC Inputs

M
1 6

T1/2
L1/1
SMC-50 Soft
Starter
T2/4
L2/3
T3/6

Circuit
Protective
Device

Fast-Acting SCR 1
Fuses (optional)

3-Phase AC
Line Power

L3/5
1

Isolation
Contactor
1

120/240V AC Control Transformer 2


or AC Power Supply

1
1

Stop 1 4
1

IC

Start 1
3
5

11

10

In2DC

Enable I/O

Intl DC COM

Intl +24V

12

In1DC

Aux2

Control Module Standard I/O

2
1
-L2 +L1

Aux1

Control Mod
Power & Ground

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal 11 (In1 DC) 24V DC input is configured for START input using Parameter 56.
Terminal 10 (In2 DC) 24V DC input configured for COAST, STOP OPTION, etc. using Parameter 57.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
A customer-supplied jumper is required to enable the controller I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation (e.g., the Isolation Contactor used in this diagram) is
recommended if maintenance is required on the motor.
Configure Aux 1 to NORMAL using Parameter 172. NORMAL = Aux 1 contact will close to energize the IC coil with the START push button and will open to de-energize it
when the stop maneuver, initiated by the stop push button, is complete.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor (as shown in this diagram) or shunt trip-type circuit breaker capable of interrupting the motors locked rotor
current on the line side of the SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to
NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

57

Chapter 2

Installation & Wiring

Figure 39 - For Isolation Contactor Applications AC Inputs

M
1 5

T1/2
L1/1
SMC-50 Soft
Starter
L2/3
T2/4
T3/6

Circuit
Protective
Device

Fast-Acting SCR 1
Fuses (optional)

L3/5
Isolation
Contactor

120/240V AC Control Transformer 2


or AC Power Supply

1
1

Stop

1 4

IC

12

11

10

In1DC

In2DC

Enable I/O

Intl DC COM

Start 1

Intl +24V

3-Phase AC
Line Power

7
Aux2

AC Inputs

A5

A6

2
-L2

1
+L1

Aux1
Control Module
Power & Ground

A7

A8

A9

A10

A11 A12
NC
AuxA2
AuxA3
AuxA1
Auxilliary Relay Outputs
150-SM4 Option I/O Module

InCOM

InA2

A4

InA4

InA1

A3

InA3

A2

Control Module Standard I/O


A1

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal A2 (InA2) 100...240V AC input is configured for START input using Parameter 7-3 (control module port 7).
Terminal A1 (InA1) 100...240V AC input configured for COAST, STOP OPTION, etc. using Parameter 7-2 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation (e.g., the isolation contactor used in this diagram) is
recommended if maintenance is required on the motor.
Configure Aux 1 to NORMAL using Parameter 172. NORMAL = Aux 1 contact will close to energize the IC coil with the START push button and will open to de-energize it
when the stop maneuver, initiated by the stop push button, is complete.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion slot it is located in on the control module. However, the function
associated with the terminal number remains the same.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor (as shown in this diagram) or shunt trip-type circuit breaker capable of interrupting the motors locked rotor
current on the line side of the SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to
NORMAL.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".

58

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 40 - For Shunt Trip Applications DC Inputs

T1/2

T3/6

Circuit
Protective
Device

Fast-Acting SCR 1
Fuses (optional)

SMC-50 Soft
Starter
T2/4
L2/3

M
1

L1/1

3-Phase AC
Line Power

L3/5
1

120/240V AC Control Transformer 2


or AC Power Supply
1
1

Stop 1 4
1

ST

Start 1
5
7

12

11

10

Intl +24V

In1DC

In2DC

Enable I/O

Intl DC COM

Aux2

Control Module Standard I/O

2
1
-L2 +L1

Aux1
Control Module
Power & Ground

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal 11 (In1 DC) 24V DC input is configured for START input using Parameter 56.
Terminal 10 (In2 DC) 24V DC input configured for COAST, STOP OPTION, etc. using Parameter 57.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
A customer-supplied jumper is required to enable the controller I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Application for details.
Configure Aux 1 to FAULT using Parameter 172. During a controller fault condition, the Aux 1 contact will close to energize the Shunt Trip (ST) coil.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

59

Chapter 2

Installation & Wiring

Figure 41 - For Shunt Trip Applications AC Inputs

T1/2 L1/1
SMC-50 Soft Fast-Acting SCR 1
Fuses (optional)
Starter
T2/4 L2/3

M
1 5

T3/6

Circuit
Protective
Device

3-Phase AC

Line Power

L3/5
1

120V/240V AC Control Transformer 2


or AC Power Supply
1
4

Stop 1
Start 1

ST

3
6

8
Intl DC COM

In1DC

Intl +24V

12 11 10

Enable I/O

In2DC

Aux2

InA1

InA2

InA4

InCOM

A4 A5

InA3

A2 A3

Aux1

Control Module Standard I/O


A1

2
1
-L2 +L1

Control Module
Power & Ground

A6 A7 A8 A9 A10 A11 A12


NC
AuxA3
AuxA1 AuxA2

Auxilliary Relay Outputs


AC Inputs
150-SM4 Option I/O Module
Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC or 24V DC).
Terminal A2 (InA2) 100...240V AC input is configured for START input using Parameter 7-3 (control module port 7).
Terminal A1 (InA1) 100...240V AC input configured for COAST, STOP OPTION, etc. using Parameter 7-2 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Application for details.
Configure Aux 1 to FAULT using Parameter 172. During a controlled fault condition the Aux 1 contact will close to energize the Shunt Trip (ST) coil.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion slot it is located in on the control module. However, the function
associated with the terminal number remains the same.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".

60

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 42 - For Single-Speed Reversing Applications DC Control

M
1 5

FWD

T1/2
L1/1
1
SMC-50 Soft Fast-Acting SCR
Fuses (optional)
Starter
T2/4
L2/3
T3/6

Circuit
Protective
Device

3-Phase AC

Line Power

L3/5
Reversing 1
Contactor
REV
1

120V/240V AC Control Transformer 2


or AC Power Supply

1
1

1
1

Rev

E-Stop

Fwd 1

F
4

12

11

10

In1DC

In2DC

Enable I/O

Intl DC COM

Intl +24V

OFF
F R

-L2 +L1
Aux2

Aux1

Control Module Standard I/O

Control Module
Power & Ground

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal 11 (In1 DC) 24V DC input is configured for START/COAST using Parameter 56.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
A customer-supplied jumper is required to enable the controller I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. In this example, the reversing contactor provides isolation.
Configure In2DC (Input 2 - Parameter 57) to "Disable".
NOTE: The SMC-50 minimum transition time for reversing is 0.5 s. The SMC-50 phase reversal must be disabled in reversing applications.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

61

Chapter 2

Installation & Wiring

Figure 43 - For Two-Speed Applications DC Control

H6
H
M
1 8

T1/2 L1/1
SMC-50 Soft Fast-Acting SCR 1
Fuses (optional)
Starter
T2/4 L2/3

L
7

T3/6

Circuit
Protective
Device

3-Phase AC

Line Power

L3/5

H
H
H
1

1 sec
5

HOL LOL
1

L1
H

1 sec

L1

Low High

H
H

12

11

10

In2DC

Enable I/O

Intl DC COM

In1DC

Intl +24V

Stop

Two-Speed
Motor Starter 1
5

120V/240V AC Control
Transformer or AC Power
Supply 2

6
Aux2

4
Aux1

Control Module Standard I/O

-L2

+L1

Control Module
Power & Ground

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal 11 (In1 DC) 24V DC input is configured for START/COAST using Parameter 56.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
A customer-supplied jumper is required to enable the controller I/O operation.
Customer-supplied timers with hard contact are required to accept DC power.
Two-speed consequent pole operations.
The SMC-50 overload must be disabled.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Application for details.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.
Configure In2DC (Input 2 - Parameter 57) to "Disable".

62

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 44 - For SMC Start, Run On Bypass DC Inputs

See External Bypass Control Mode on page 91 for additional configurations

825-MCM

T1/2 L1/1
SMC-50 Soft Fast-Acting SCR
Starter
Fuses (optional) 1
T2/4 L2/3

M
1 6

T3/6

3-Phase AC

Line Power

L3/5
1

Circuit
Protective
Device

120/240V AC Control Transformer


or AC Power Supply 2

Bypass Contactor (BC) 1 10


Stop

BC 10

Start 3
1

11

10

In2DC

Enable I/O

Intl DC COM

Intl +24V

12

In1DC

Aux2

Aux1

Control Module
Power & Ground

Control Module Standard I/O


150-SM2 Option Module
RG25U
TB2
TB3
TB4
Female
TB2
TB3
RG25U 7 TB4
Male

2
1
-L2 +L1

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal 11 (In1 DC) 24V DC input is configured for START input using Parameter 56.
Terminal 10 (In2 DC) 24V DC input configured for COAST, STOP OPTION, etc. using Parameter 57.
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
A customer-supplied jumper is required to enable the controller I/O operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications for details.
In Bypass Contactor RUN operation, the 825-MCM and the 150-SM2 provide current-based protective feedback features including overload. Only the cable provided with the
825-MCM converter can be used in this configuration. The maximum cable length is 4 m, thus the 825-MCM must be located within 4 m of the SMC-50.
The order of the terminal numbers for the 150-SM2 module can be reversed depending on which expansion slot it is located in the control module. However, the function
associated with the terminal number remains the same.
The Aux 1 relay output is configured for external bypass using Parameter 172.
In North America, size the bypass contactor per the motor Hp and FLA,. In IEC, size the bypass contactor per the motor AC-1 rating. The short-circuit rating of the bypass
contactor must be similar to the SMC-50.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

63

Chapter 2

Installation & Wiring

Figure 45 - Hand-OFF-Auto Control with Start/Stop Push Buttons AC Control

T1/2
L1/1
SMC-50 Soft Fast-Acting SCR 1
Starter
Fuses (optional)
T2/4 L2/3

M
1 4

T3/6

Circuit
Protective
3-Phase AC
Device
1
Line Power

L3/5
1

120V/240V AC Control Transformer


or AC Power Supply 2

Off 1
Stop Start 1
Hand Auto
C

1 Auto Device 1
6

12

11

10

Intl +24V

In1DC

In2DC

Enable I/O

Intl DC COM

C
6

Aux2

2
-L2

1
+L1

Aux1

Control Module Standard I/O

Control Module
Power & Ground

3
5

InCOM

InA4

InA3

InA2

InA1

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12


NC
AuxA3
AuxA1 AuxA2
AC Inputs
Auxilliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Terminal A1 (InA1) 100...240V AC input is configured for START/STOP or START/COAST using Parameter 7-2 (control module port 7, Start = Input High, Coast/Stop = Input
Low).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

64

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 46 - For Hand-OFF-Auto (DPI) with Start/Stop Push Buttons AC I/O

T1/2 L1/1
SMC-50 Soft
Starter
T2/4 L2/3

M
1 5

T3/6

3-Phase AC
Line Power

L3/5
1

Off 1
Hand
Auto

120/240V AC Control Transformer 2


or AC Power Supply

8
Stop

Circuit
Protective
Device

Fast-Acting SCR
Fuses (optional) 1

8
1

In2DC

In1DC

Intl +24V

12 11 10

8
Intl DC COM

Enable I/O

Start 1

Aux2

Aux1

Control Module Standard I/O


3

2 1
-L2 +L1

Control Module
Power & Ground

4
6

InCOM

InA4

InA3

InA2

InA1

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12


NC
AuxA3
AuxA1 AuxA2
AC Inputs
Auxilliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A2 (InA2) 100...240V AC input is configured for START input using Parameter 7-4 (control module port 7).
Option I/O Terminal A3 (InA3) 100...240V AC input configured for COAST, STOP OPTION, etc. using Parameter 7-3 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.
indicates that the switch is closed in this position.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

65

Chapter 2

Installation & Wiring

Soft Stop, Pump Control, &


Smart Motor Braking (SMB)

The following figure shows the typical wiring diagrams for the Soft Stop, Pump
Control, and SMB options.
Figure 47 - Soft Stop, Pump Stop, or Braking Control Option, AC Control

T1/2 L1/1
SMC-50 Soft
Starter
T2/4 L2/3

M
1 5

Fast-Acting SCR 1
Fuses (optional)

Circuit
Protective
Device

3-Phase AC

Line Power

T3/6 L3/5
1

Stop 1
1

Start 1

120V/240V AC Control Transformer 2


or AC Power Supply
1

Option Stop 1
12

11

10

Intl +24V

In1DC

In2DC

Enable I/O

Intl DC COM

Aux2

Control Module Standard I/O

Aux1

2 1
-L2 +L1

Control Module
Power & Ground

A4 A5 A6

AC Inputs

InCOM

A2 A3
InA3

A1

InA4

InA2

InA1

A7 A8 A9 A10 A11 A12


NC
AuxA3
AuxA2
AuxA1

Auxilliary Relay Outputs


150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A2 (InA2) 100...240V AC input is configured for START input using Parameter 7-3 (contact module port 7).
Option I/O Terminal A3 (InA3) 100...240V AC input configured for COAST using Parameter 7-4 (contact module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Option I/O module Terminal A1 (InA1) 120/240V AC input is configured for STOP OPTION using Parameter 7-2 (contact module port 7).
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the
function associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".

66

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Slow Speed with Braking

Figure 48 - For Isolation Contactor with STOP Option Applications, AC Inputs

T1/2 L1/1
SMC-50 Soft Fast-Acting SCR 1
Fuses (optional)
Starter
T2/4 L2/3

M
1 6

Circuit
Protective
Device
1

Isolation
Contactor
1 7

120V/240V AC Control Transformer


or AC Power Supply 2

Option Stop 1

Stop 1
1 IC

In1DC

In2DC

Aux2

2 1
-L2 +L1

Control Module
Power & Ground

A7

InCOM

InA4

InA3

A8 A9 A10 A11 A12


NC
AuxA3
AuxA1
AuxA2
AC Inputs
Auxiliary Relay Outputs
150-SM4 Option I/O Module

InA2

A4 A5 A6

Aux1

Control Module Standard I/O


3
4
5
A1 A2 A3

7
Intl DC COM

11

9
9
Enable I/O

12

9
10

Intl +24V

Start

InA1

3-Phase AC
Line Power

L3/5

T3/6

Chapter 2

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A3 (InA3) 100...240V AC input is configured for START input using Parameter 7-4 (control module port 7).
Option I/O Terminal A2 (InA2) 100...240V AC input configured for COAST using Parameter 7-3 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Option I/O module Terminal A1 (InA1) 100...240V AC input is configured for STOP OPTION using Parameter 7-2 (control module port 7).
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation (e.g., the one shown in this diagram) is
recommended if maintenance is required on the motor.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.
Configure Aux1 to NORMAL using Parameter 172. NORMAL = Aux1 contact will close to energize the IC coil with the START push button and open to de-energize when the
stop maneuver, initiated by the STOP push button, is complete.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

67

Chapter 2

Installation & Wiring

Figure 49 - For Isolation Contactor & Slow-Speed with Braking Application AC


Control

M
1 9

L1/1
T1/2
SMC-50 Soft Fast-Acting SCR 1
Starter
Fuses (optional)
T2/4
L2/3
T3/6

Circuit
Protective
Device
11

L3/5

Brake

Isolation 1
Contactor

Slow Speed
1
1

Stop
Start

3-Phase AC
Line Power

120/240V AC Control Transformer


or AC Power Supply

IC

1
2

Intl +24V
In1DC
In2DC
Enable I/O
Intl DC COM

12 11 10 9

7 6

Aux2

Aux1

2
1
-L2 +L1

Control Module Standard I/O


6

Control Module
Power & Ground

InCOM

InA4

InA3

InA1
InA2

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12


NC
AuxA1 AuxA2 AuxA3
AC Inputs
Auxiliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A4 (InA4) 100...240V AC input is configured for START input using Parameter 7-5 (control module port 7).
Option I/O Terminal A3 (InA3) 100...240V AC input configured for COAST, etc. using Parameter 7-4 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Option I/O module Terminal A1 (InA1) 100...240V AC input is configured for STOP OPTION using Parameter 7-2 (control module port 7). Set STOP MODE, Parameter 65, to
SMB.
Option I/O module Terminal A2 (InA2) 100...240V AC input is configured for SLOW SPEED using Parameter 7-3 (control module port 7).
Configure Aux1 to NORMAL using Parameter 172. NORMAL = Aux1 contact will close to energize the IC coil with the START push button and open to de-energize when the
stop maneuver, initiated by the STOP push button, is complete.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor (as shown in this diagram) or shunt trip-type circuit breaker capable of interrupting the motors locked rotor
current on the line side of the SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to
NORMAL.

68

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Preset Slow Speed


M
1 6

Chapter 2

Figure 50 - For Preset Slow Speed Control AC I/O

T1/2 L1/1
SMC-50 Soft
Starter
T2/4 L2/3

Fast-Acting SCR 1
Fuses (optional)

Circuit
Protective
Device

3-Phase AC

Line Power

T3/6 L3/5
120/240V AC Control Transformer 2
or AC Power Supply

Slow Speed

Stop 1
Start

1
8

In2DC
Enable I/O
Int DC Com

Intl +24V
In1DC

12 11 10 9

Aux2

Aux1

Control Module Standard I/O


5

2 1
-L2 +L1

Control
Module
Power &
Ground

InCOM

InA4

InA3

InA2

InA1

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12


NC
AuxA1 AuxA2 AuxA3
AC Inputs
Auxiliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A3 (InA3) 100...240V AC input is configured for START input using Parameter 7-4 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Option I/O Terminal A2 (InA2) 100...240V AC input configured for COAST, Stop Option, etc. using Parameter 7-3 (control module port 7).
Option I/O terminal A1 (InA1) 120/240V AC input configured for SLOW SPEED using Parameter 7-2 (control module port 7)
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

69

Chapter 2

Installation & Wiring

Figure 51 - For Preset Slow Speed Control for Hand-OFF-Auto (DPI) AC I/O

M
1 6

T1/2
L1/1
SMC-50 Soft Fast-Acting SCR 1
Starter
Fuses (optional)
T2/4
L2/3
T3/6

Circuit
Protective
Device
11

3-Phase AC
Line Power

L3/5

Hand Start
1

120/240V AC Control Transformer 2


or AC Power Supply

Off 1
Auto (DPI) Hand

Hand Stop

Slow Speed 1
1
8

Enable I/O

In2DC

Intl +24V
In1DC

12 11 10 9

8
Intl DC COM

Aux2

Aux1

Control Module Standard I/O


3

2 1
-L2 +L1

Control
Module
Power & Ground

4
7

InCOM

InA4

InA3

InA2

InA1

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12


NC
AuxA1 AuxA2 AuxA3
AC Inputs
Auxiliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A2 (InA2) 100...240V AC input is configured for START input using Parameter 7-3 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Option I/O Terminal A3 (InA3) 100...240V AC input configured for COAST, Stop Option, etc. using Parameter 7-4 (control module port 7).
Option I/O Terminal A1 (InA1) 120/240V input configured for SLOW SPEED using Parameter 7-2 (control module port 7).
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation os recommended if maintenance is required on the
motor. See the Isolation Contactor Application diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure both In1 (Input 1 Parameter 56) and In2 (Input 2 Parameter 57) to "Disable".
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

70

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Installation & Wiring

Chapter 2

Figure 52 - Accu-Stop AC I/O

M
1 6

T1/2
L1/1
SMC-50 Soft
Starter
L2/3
T2/4

Fast-Acting SCR 1
Fuses (optional)

Circuit
Protective
Device
11

L3/5

T3/6
8

Start

Stop 1

Line Power

120V/240V AC Control Transformer


or AC Power Supply 2

3-Phase AC

Slow Speed
1
9

Intl DC COM

Enable I/O

In2DC

Intl +24V

In1DC

12 11 10 9 8 7

6 5
Aux2

4 3
Aux1

Control Module Standard I/O


5

2 1
-L2 +L1

Control Module
Power & Ground

InCOM

InA4

InA3

InA2

InA1

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 7


NC
AuxA1 AuxA2 AuxA3
AC Inputs
Auxiliary Relay Outputs
150-SM4 Option I/O Module

Customer supplied.
See the controller nameplate to verify the control power input ratings (100...240V AC).
Option I/O Terminal A3 (InA3) 100...240V AC input configured for SLOW SPEED, Stop Option, etc. using Parameter 7-4 (control module port 7).
NOTE: The controller will generate an I/O configuration fault if any input is configured for START or SLOW speed and no input is configured for COAST or STOP.
Option I/O Terminal A2 (InA2) 100...240V AC input is configured for SART input using Parameter 7-3 (control module port 7).
Option I/O Terminal A1 (InA1) 120/240V Input configured for COAST using Parameter 7-2 (control module port 7).
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance is required on the
motor. See the Isolation Contactor Applications diagram for details.
The order of the terminal numbers for the option I/O module can be reversed depending on which expansion port it is located in on the control module. However, the function
associated with the terminal number remains the same.
Configure Stop Mode to SMB using Parameter 65; Braking Current using Parameter 69; Slow Speed using Parameter 72; and Slow Brake using Parameter 73 (Parameter 73
= 0 results in Coast).
Configure both In1(Input 1 - Parameter 56) and In2 (Input 2 - Parameter 57) to DISABLE.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching components allows
uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To prevent potential personal injury or
equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting the motors locked rotor current on the line side of the
SMC-50 is recommended. Operation of the isolation device should be coordinated using one of the SMC-50 Aux contacts configured to NORMAL.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

71

Chapter 2

Installation & Wiring

Notes:

72

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Operating Modes

Operation

The SMC-50 can operate standard squirrel-cage induction motors rated


30520 A or star-delta (wye-delta) type motors rated 52900 A operated
inside-the-delta.
IMPORTANT

Verify line and control as the voltage values on the product before
applying power.

Motor Configuration

Line-connected wye, line-connected delta, and inside-the-delta motor


configurations are possible with the SMC-50. The motor tuning feature of the
SMC-50 will automatically determine the motor connection. Motor tuning is
done automatically by the controller on initial motor start or forced to occur by
the user. The user can also enter the configuration of the Motor Connection,
Parameter 44, into the SMC-50. The Motor Line Voltage rating, Parameter 46,
must be entered into the controller by the user to enable the motor protection
features to function (default 480V).

Motor Tuning

The SMC-50 will perform the motor tuning process on the initial start sequence
of the motor. Motor tuning includes the identification of the motor parameters
and the detection of the motor connection type (Line or Delta). The SMC-50
uses the motor tuning data in its control algorithm.
During the tuning process the motor will not turn and will make some audible
noise including pulsing and buzzing. The time to complete the tuning process is
approximately 10 to 20 seconds but may vary based on the size and characteristics
of the individual motor being used. After successful completion of the tuning
process the motor will start based on the user programmed start profile. If the
tuning process is interrupted by the user giving a stop command or removing
power from the unit the tuning process will be repeated on the next start
command. Subsequent starts of the motor after a successful tuning will not
perform the tuning process.
After the initial successful tuning of the motor the process may be re-initiated by
the user via one of the following methods:
1. Change the status of Force Tuning, Parameter 194, to TRUE by using a
configuration tool (e.g., a HIM) with the motor stopped. During the next
start cycle, the tuning process will occur and Parameter 194 will change
back to FALSE. OR
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

73

Chapter 3

Operating Modes

2. Press the "HOLD TO TEST/PUSH TO RESET" push button, located


on the front of the controller, for ten seconds with the motor stopped.
During the next start cycle, the tuning process will occur. The controllers
status LED will flash amber indicating that Tuning will occur on the next
start cycle. OR
3. When the controller processes a "Load Factory Defaults" command via
Parameter Management, Parameter 229.
NOTE:

If a motor that is smaller or larger than normal is used for initial system
testing, a motor tuning cycle must be performed on the motor used in the
final installation.

The following table lists Parameter 194 Force Tuning along with the key motor
parameters checked by the SMC-50 controller during a motor tuning cycle.
Table 13 - Key Motor Parameters Checked During a Motor Tuning Cycle
Parameter Number Parameter Name Minimum/Maximum [Default] Access Units

Modes of Operation
Starting

194

Force Tuning

FALSE [TRUE]

R/W

195

Stator R

0.00-50.00

Ohms

196

Total R

0.00-50.00

Ohms

197

Coupling Factor

0.00-10.00

198

Inductance

0.00-1000.00

mH

45

Motor Connection

[Line] Delta

Overview
The SMC-50 starting mode is configured using Starting Mode, Parameter 49.
The available starting modes are: Soft Start [default], Current Limit, Torque
Ramp, Linear Speed, Pump Start, and Full Voltage.

Soft Start
This mode has the most general application. The motor is given an initial torque
setting using Parameter 51, which is user-adjustable from 090% of locked rotor
torque. From the initial torque level, the output voltage to the motor is linearly
increased during the acceleration ramp time. The acceleration ramp time is
adjustable from 01000 seconds using Parameter 50.
During soft start, a current limit override (50600% FLC) is also available to
limit current throughout the start cycle using Parameter 53. The controller has
Up-to-Speed (UTS) detection to determine when the motor is at full speed. If
the motor reaches UTS before the end of the ramp time, the SMC-50 applies full
voltage to the motor and the soft start is ended. The UTS level can be configured

74

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

in percent of the SMC-50s applied motor voltage using Parameter 186. The full
Soft Start parameter list can be found in Table 14.
NOTE:

If the controller is detecting UTS too soon, the UTS level should be increased.
This typically occurs in very high efficiency motors. If the controller is
detecting UTS too late or not at all, the UTS level should be lowered. This
typically occurs in very low efficiency motors. See Timed Start on page 83 for
additional details.

Figure 53 - Soft Start


Current Limit

Percent Voltage

100%

Initial
Torque

Ramp Time

Start

Run

Time in Seconds

Table 14 - Soft Start Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
49

Starting Mode

[Soft Start]

50

Ramp Time

0.0-1000.0 [10.0]

SEC

51

Initial Torque

0-90 [70]

%LRT

53

Cur Limit Level

50-600 [350]

%FLC

54

Kickstart Time

[0.0]-2.0

55

Kickstart Level

[0.0]-90

%LRT

182

Start Delay

[0.0]-30

SEC

186

UTS Level

0-100 [75]

78

Motor FLC

[1.0]-2200.0

Amps

R/W

SEC

Selectable Kickstart
This feature provides a torque (current) boost at startup to break away loads that
require a pulse of high torque to get started. The amount of torque pulse is
selectable from 090% of locked rotor torque using Kickstart Level, Parameter
55. The time duration for the selectable kickstart is user-adjustable from
0.02.0 seconds using Kickstart Time, Parameter 54.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

75

Chapter 3

Operating Modes

Kickstart is available in Soft Start, Current Limit, Pump, and Torque Control
starting modes.
Figure 54 provides a graphical representation of Kickstart. Table 15 provides the
Kickstart Mode Parameter List.
Figure 54 - Selectable Kickstart

Percent Voltage

100%

Kickstart
Level
Coast-to-Rest
Soft Stop

Kickstart
Time

Initial
Torque

Start

Run

Soft Stop

Time in Seconds

Table 15 - Kickstart Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
54

Kickstart Time

[0.0]-2.0

55

Kickstart Level

[0.0]-90

R/W

SEC
%LRT

Current Limit Start


This starting mode provides a true current limit start, and is used when it is
required to limit the maximum starting current to the load. This is accomplished
using Current Limit Level, Parameter 53, which is user-adjustable from
50600% of the motor full load current rating (FLC) and Ramp Time,
Parameter 50, which is user-adjustable from 0.01000.0 seconds. For current
limit, the Ramp Time is the time the controller will hold the current limit level
until switching to full voltage. If the controller senses that the motor has reached
the UTS condition during the current limit starting mode, the current limit ramp
will end. As with Soft Start, the UTS level can be modified to account for load or
motor characteristics. If Ramp Time has expired and UTS is not achieved, the
SMC-50 will hold the current limit until UTS is reached, a Motor Overload Trip,
or Starter Overtemp Fault occurs. Kickstart is also available with current limit.
Figure 55 provides a graphical depiction of a Current Limit Start. Table 16
provides a list of Current Limit Start parameters.

76

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Figure 55 - Current Limit Start

Percent Full Load Current

600%
Current Limit

50%

Start
Time in Seconds

Table 16 - Current Limit Start Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
50

Ramp Time

0.0-1000.0 [10.0]

SEC

53

Cur Limit Level

50-600 [350]

%FLC

54

Kickstart Time

[0.0]-2.0

SEC

55

Kickstart Level

[0.0]-90

182

Start Delay

[0.0]-30

SEC

186

UTS Level

0-100 [75]

78

Motor FLC

[1.0]-2200.0

Amps

R/W

%LRT

Full Voltage Start


This starting mode is used for applications requiring across-the-line starting. The
controller supplied voltage to the motor will reach full voltage within five AC
line cycles (0.08 s at 60 Hz and 0.1 s at 50 Hz). To enable Full Voltage Start, set
Parameter 49 to Full Voltage.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

77

Chapter 3

Operating Modes

Figure 56 - Full Voltage Start

Percent Voltage

100%

Time in Seconds

Linear Acceleration
The SMC-50 has the ability to start the motor following a timed linear ramp.
The Ramp Time, Parameter 50, is selectable from 0.01000.0 seconds and
determines the time the motor will ramp from a zero speed to full speed
condition. An Initial Torque, Parameter 51, value sets the starting torque
supplied to the motor from the controller. A current limit setting (50600%
selectable of motor FLC) is also available. If the controller reaches the current
limit setpoint, the acceleration ramp will stop. When the unit comes out of
current limit, the linear ramp will resume.
NOTE:

Kickstart is not available with this starting mode.

Figure 57 provides a graphical example of a linear acceleration and Table 17


provides a list of linear acceleration parameters.
Figure 57 - Linear Acceleration
Current Limit

Percent Speed

100%
Linear
Acceleration

Linear
Deceleration
Stop Time

Ramp Time

Start

78

Run
Time in Seconds

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Stop

Operating Modes

Chapter 3

Table 17 - Linear Acceleration Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
49

Starting Mode

Linear Speed

50

Ramp Time

0.0-1000.0 [10.0]

SEC

51

Initial Torque

0-90 [70]

%LRT
R/W

53

Cur Limit Level

50-600 [350]

%FLC

78

Motor FLC

[1.0]-2200.0

Amps

199

Speed PGain

0-10000 [1000]

Torque Control Start


This motor starting method provides a torque ramp from an initial starting
torque level to a maximum torque level over the start time. The torque levels are
entered in percent of rated motor torque. This requires that the Rated Torque
parameter be configured to the motors rated torque. The torque start operating
mode requires motor tuning to function properly. Tuning can be forced manually
or it will otherwise be performed automatically the first time the motor is started.
See Motor Tuning on page 73.
Figure 58 - Torque Start

Percent Rated Motor Torque

Current Limit
Maximum Motor Torque

100%
Torque
Ramp

Starting
Torque

Ramp Time

Stop Time

Start

Run

Stop

Time in Seconds

Table 18 provides a list of Torque Control Start parameters.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

79

Chapter 3

Operating Modes

Table 18 - Torque Start Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
49

Starting Mode

Torque Ramp

305

Starting Torque

0-300 [100]

52

Max Torque

0-300 [250]

50

Ramp Time

0.0-1000.0 [10.0]

SEC

47

Rated Torque

0-10000 [10]
R/W

Nm

48

Rated Speed

750, 900, 1500, [1800], 3600

RPM

53

Cur Limit Level

50-600 [350]

%FLC

54

Kickstart Time

[0.0]-2.0

SEC

55

Kickstart Level

[0.0]-90

%LRT

78

Motor FLC

[1.0]-2200.0

Amps

Pump Control Start & Stop


The pump control reduces surges (water hammer) during the starting and
stopping of a centrifugal pump by smoothly accelerating and decelerating the
motor. As such, starting and stopping parameters are typically configured
together. The microprocessor analyzes the motor variables and generates
commands that control the motor and reduce the possibility of surges occurring
in the system.
The starting time (Ramp Time, Parameter 50) is programmable from
0.01000.0 seconds and the stopping time (Stop Time, Parameter 66) is
programmable from 0999 seconds when the Pump Stop mode is selected from
Parameter 65.
Figure 59 - Pump Control

Motor Speed

100%

Pump Start
Ramp Time

80

Run
Time in Seconds

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Pump Stop
Stop Time

Operating Modes

Chapter 3

Table 19 - Pump Start Control Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
49

Starting Mode

Pump Start

50

Ramp Time

0.0-1000.0 [10.0]

SEC

51

Initial Torque

0-90 [70]

%LRT

67

Backspin Timer

[0]-999

54

Kickstart Time

[0.0]-2.0

SEC

55

Kickstart Level

[0.0]-90

%LRT

78

Motor FLC

[1.0]-2200.0

Amps

R/W

SEC

Table 20 - Pump Stop Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
65

Stop Mode

Pump Stop

66

Stop Time

[0.0]-999.0

68

Pump Pedestal

[0.0]-50.0

NOTE:

R/W

SEC
%

Pump Pedestal, Parameter 68, provides the ability to modify the internal pump
control algorithm for special application conditions.
For example, if overload trips persist during stopping, either reduce the Stop
Time, Parameter 66, or increase the Pump Pedestal in 5% increments. Try not
to exceed 40%

ATTENTION: Pump stopping is not intended to be used as an emergency


stop. See the applicable standard for emergency stop requirements.

ATTENTION: Pump stopping may cause motor heating depending on the


mechanical dynamics of the pumping system. Therefore, select the lowest
stopping time setting that will satisfactorily stop the pump.

Additional Start Features Dual Ramp Start


Functions

This feature is useful for applications that have varying loads (and therefore
varying starting feature requirements). Dual Ramp allows the user to select
between two separate start profiles with separately adjustable ramp times, initial
torque settings, etc. to best meet the application needs.
The second start profile is enabled by configuring one of the controller auxiliary
inputs to Dual Ramp and activating that input. When the Start command is then
activated, the second start profile will begin.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

81

Chapter 3

Operating Modes

Figure 60 - Dual Ramp Start


Current Limit 2
Current Limit 1

Percent Voltage

100%

Ramp #2

Initial
Torque #2
Ramp #1
Initial
Torque #1

Start #1
Start #2
Time in Seconds

Run #1
Run #2

Table 21 - Dual Ramp Start Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default]

82

Access Units

49

Starting Mode

Full Voltage, Current Limit, [Soft


Start], Linear Speed, Torque Ramp,
Pump Start

50

Ramp Time

0.0-1000.0 [10.0]

SEC

51

Initial Torque

0-90 [70]

%LRT

52

Max Torque

0-300 [250]

53

Cur Limit Level

50-600 [350]

%FLC

54

Kickstart Time

[0.0]-2.0

SEC

55

Kickstart Level

[0.0]-90

%LRT

305

Starting Torque

0-300 [100]

58

Starting Mode 2

Full Voltage, Current Limit, [Soft


Start], Linear Speed, Torque Ramp,
Pump Start

59

Ramp Time 2

0.0-1000.0 [10.0]

SEC

60

Initial Torque 2

0-90 [70]

%LRT

61

Max Torque 2

0-300 [250]

62

Cur Limit Level 2

50-600 [350]

%FLC

63

Kickstart Time 2

[0.0]-2.0

SEC

64

Kickstart Level 2

[0]-90

%LRT

306

Starting Torque 2

0-300 [100]

182

Start Delay

[0]-30

SEC

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

Operating Modes

Chapter 3

Start Timer (Start Delay)


This feature provides the ability to set a user-configurable start (030 s) delay
from the point when the start command is enabled until the start sequence
actually occurs. This feature applies to any start mode.

Timed Start
Timed Start, Parameter 183, forces the starting profile to complete the entire
user-configured ramp time before applying full voltage. In some starting modes
(e.g., soft start) and with certain loads (e.g., lightly loaded motor), an early UTS
condition can be generated placing the SMC-50 in full-voltage start, which
might cause excessive current. Setting Timed Start to "Enable" forces all starts to
complete the configured Ramp Time, Parameter 50.

Backspin Timer
A Backspin Timer, Parameter 67, is provided in order to avoid starting a motor
into a backspin condition, which may result in motor shaft damage. The
user-configured time begins to count down after a stop maneuver is complete. All
start inputs are ignored until the backspin timer has timed out.

Motor Winding Heater Function


The Motor Winding Heater function provides low levels of current to each of the
motor windings to preheat a cold motor before starting. To avoid thermally
stressing a single motor winding, the SMC-50 cycles the heating current to each
of the phases. This feature provides a programmable heating level, heating time,
and a control (terminal block) input which can be used to start the process.
NOTE:

Configuration of control module inputs is done via Input 1, Parameter 56, or


Input 2, Parameter 57. If a 150-SM4 Optional Digital I/O Module is configured,
its inputs can also be used for the motor winding heater function.

Table 22 - Motor Winding Heater Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
220

Heating Time

[0]-1000

221

Heating Level

[0]-100

R/W

SEC
%

The motor winding heater function can be activated after a valid start command
is received. After a valid start, the activation of the heating function can be
performed by:
programming the Heating Time, Parameter 220, to a non-zero value or
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

83

Chapter 3

Operating Modes

configuring an input to "Motor Heater" and activating that input prior to


the start command.
The heater function will continue for the specified time or until the input is
deactivated, at which time the motor will start. The heater function will be
disabled if the:
Heating Level, Parameter 221, is set to zero, or
Heating Time, Parameter 220, is set to zero, or
input is inactive (or not configured) at the time of the start command.

Modes of Operation
Stopping Modes

Overview
Stop Mode, Parameter 65, defines the type of stop maneuver performed by the
SMC-50 when a stop command is issued. The STOP command can be initiated
through any input , a network command, or the JOG key on the A6 HIM.
NOTE:

The STOP Key on a Cat. no. 20-HIM-A6 or 20-HIM-C6S device initiates a


Coast-to-Stop.

The available stopping modes are:


Coast-to-Stop
SMB Smart Motor Braking
Soft Stop
Pump Stop
Linear Speed Deceleration External Brake
To utilize terminal block inputs to initiate a Stop Mode, the respective input should be configured for Start/Stop
or Stop Option.

Coast-to-Stop
When Stop Mode, Parameter 65, is set to Coast-to-Stop and the STOP
command is initiated, the starter will not perform any other function and the
motor coasts to a stop. No other Stop parameters need to be configured if
Coast-to-Stop is enabled.
The Coast-to-Stop command overrides all other commands that could result in
motor operation. When this command is initiated, it is latched into the
controllers logic so that no other motor command can occur until it is cleared. It
will be cleared when all terminal block Start inputs are opened and any other Soft
Stop (Inhibits a Start) input is removed. Note that in a 2-wire control scheme,
this involves placing the Start/Stop input in the Stop position; in a 3-wire control
scheme, this involves opening the Start input.

84

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Table 23 - Stop Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default]

Access Units

65

R/W

Stop Mode

[Coast]

Soft Stop
The Soft Stop feature can be used in applications that require an extended stop
time. The voltage ramp down time is user-adjustable from 0999 seconds using
Stop Time, Parameter 66. The load will stop when the SMC-50 output voltage
drops to a point where the load torque is greater than the developed motor
torque.
ATTENTION: Soft Stop is not intended to be used as an emergency stop.
See the applicable standards for emergency stop requirements.

Figure 61 - Soft Stop

Percent Voltage

100%

Inital
Torque

Kickstart
Time

Coast-to-Rest
Soft Stop

Soft Start
Ramp Time

Start

Stop Time

Run
Time in Seconds

Soft Stop

Table 24 - Soft Stop Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
65

Stop Mode

Soft Stop

66

Stop Time

[0]-999

NOTE:

R/W

SECS

For additional details, see Figure 68 on page 95.

Linear Deceleration
When Stop Mode, Parameter 65, is configured for Linear Speed, the SMC-50
will stop the motor following a timed linear speed ramp configured in Stop Time,

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

85

Chapter 3

Operating Modes

Parameter 66. A current limit setting is also available to limit the current while
stopping. If the current limit level is reached, the motor will decelerate faster than
the defined ramp. If motor current falls below the current limit, the ramp is
resumed.
ATTENTION: Linear Stop is not intended to be used as an emergency
stop. See the applicable standards for emergency stop requirements.

Figure 62 - Linear Deceleration


Current Limit

Percent Speed

100%
Linear
Acceleration

Linear
Deceleration
Stop Time

Ramp Time

Start

Run
Time in Seconds

Stop

Table 25 - Linear Deceleration Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
65

Stop Mode

Linear Speed

R/W

66

Stop Time

[0.0]-999

SEC

53

Cur Limit Level

50-600 [350]

%FLC

For additional details, see Figure 68 on page 95.

Smart Motor Braking (SMB)


When Stop Mode, Parameter 65, is configured for SMB and the Stop Maneuver
is commanded, the SMC-50 will apply the configured braking current and brake
the motor to a stop. This function can be used in applications that require
reduced stopping times. The SMC-50 incorporates a microprocessor-based
system that applies braking current to the motor without any additional
equipment. This option offers a user-adjustable braking current setting from 0%

86

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

to 400% of the motors full load current rating using Braking Current, Parameter
69. Further, it provides automatic brake current shut-off at zero speed detection.
ATTENTION: Smart Motor Braking is not intended to be used as an
emergency stop. See applicable standards for emergency stop
requirements.
Figure 63 - SMB

Smart Motor
Braking

Motor Speed

100%

Coast-to-Rest
Automatic Zero
Speed Shut-Off
Stop
Time
Start

Brake

Run
Time in Seconds

Table 26 - SMB Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
65

Stop Mode

SMB

66

Stop Time

[0]-999

69

Braking Current

[0]-400

R/W

SECS
%FLC

Programming a Stop Time is not required when SMB is used. SMB automatically controls the duration
(Stop Time) of the braking current to the motor from the Running at Speed condition until a zero speed
condition (Zero Speed Braking Shut Off feature/function). Programming a Stop Time will override the
SMB Zero Speed Braking Shutoff feature/function. This could result in current being applied to a stopped
motor, which will cause the motor to overheat. See Figure 71 on page 98 and Chapter 5, Programming, for
additional details.

With Stop Time, Parameter 66, set to some time value other than zero, the user-selected "Braking
Current", Parameter 69, is applied for the user-configured "Stop Time" regardless of the motor speed (e.g.,
Automatic Zero Speed Detection disabled). This braking method can be used in applications where
detecting zero speed is ineffective or when braking the motor to a complete stop results in random
overload trips. Note that an ideal Stop Time setting can be accomplished by trial and error, but should
always allow for some coast time. Setting the Stop Time for too long of a time period can result in
braking current to be applied to a stopped motor and will likely result in overload trips.

Preset Slow Speed & Slow Speed with Braking


The Slow Speed Mode can be used in applications that require a jog for general
purpose positioning. Preset Slow Speed, Parameter 72, provides operation from
+1+15% forward or -1-15% reverse of the motor base speed.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

87

Chapter 3

Operating Modes

An SMC-50 control input must be configured for Slow Speed to initiate a slow
speed operation. A second input must be configured for Coast or Stop Option.
The Slow Speed operating mode requires motor tuning to function properly.
Tuning can be forced manually or it will otherwise be performed automatically
the first time the motor is started. See Motor Tuning on page 73.
To provide more precise stopping from a slow speed operation, braking from slow
speed can also be configured using Slow Brake Current, Parameter 73. The
maximum allowable brake current is 350% FLC. A value of 0 (default) applies no
braking and a motor coast-to-stop results and slow speed is terminated.
ATTENTION: Slow speed running is not intended for continuous
operation due to reduced motor cooling.

Figure 64 - Preset Slow Speed

Motor Speed

100%

Forward
15% - High
1% - Low

2 Brake
Start

Low

Run

1 Coast
Reverse
Time in Seconds

Table 27 - Preset Slow Speed & Slow Speed with Braking Parameter List
Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
72
73

Slow Speed
Slow Brake Cur

-15 to +15 [10]


[0]-350

Direction of the motor rotation is dependent on the sign () of Slow Speed %.


Brake if Slow Brake Cur Parameter >0 and <350; coast if 0.

88

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

%
R/W

%FLC

Operating Modes

Chapter 3

Accu-Stop
This function combines the benefits of the SMB and Preset Slow Speed features.
For general-purpose positioning, the Accu-Stop function provides a brake from
full speed to the preset slow speed setting, then a brake or coast-to-stop.
The Accu-Stop function is enabled whenever the Stop Mode, Parameter 65, is
configured for SMB and:
a control input is configured for Stop
a control input is configured for Start
a control input is configured for Slow Speed.
With the above SMC-50 control configuration and with the motor running,
enabling the Slow Speed input will initiate a SMB to the configured Slow Speed
percent value, Parameter 72. The SMC-50 will continue to run the motor in slow
speed until the Slow Speed input is disabled, At that point, the motor will either
Brake-to-Stop or Coast-to-Stop depending on the value of the Slow Brake Cur,
Parameter 73. If the value of Slow Brake Cur is zero (0), the motor will
Coast-to-Stop from Slow Speed. If the value of Slow Brake Cur is a value other
than zero, the SMC-50 will use braking to stop the motor using that value as a
percent of the Motor FLC. See Figure 65, Figure 72 and Table 28.
The Accu-Stop operating mode requires motor tuning to function properly.
Tuning can be forced manually or it will otherwise be performed automatically
the first time the motor is started. See Motor Tuning on page 73.
ATTENTION: Accu-Stop is not intended to be used as an Emergency
Stop. See applicable standards for emergency stop requirements.
Figure 65 - Accu-Stop

Motor Speed

100%

Braking
15%
15%
1%
Slow Speed
Braking

1%

Slow
Speed

Start

Run

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Slow Speed
Coast-toRest

Brake

89

Chapter 3

Operating Modes

Table 28 - Accu-Stop Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default]

Access Units

65

Stop Mode

SMB

66

Stop Time

[0]-999

69

Braking Current

[0]-400

72

Slow Speed

-15 to +15 [10]

73

Slow Brake Cur

[0]-350

%FLC

SECS
R/W

%FLC

Programming a Stop Time is not required when SMB is used. SMB automatically controls the duration (Stop
Time) of the braking current to the motor from the Running at Speed condition until a zero speed condition
(Zero Speed Braking Shut Off feature/function). Programming a Stop Time will override the SMB Zero
Speed Braking Shutoff feature/function. This could result in current being applied to a stopped motor,
which will cause the motor to overheat. See Figure 71 on page 98 and Chapter 5, Programming, for
additional details.

With Stop Time, Parameter 66, set to some time value other than zero, the user-selected "Braking Current",
Parameter 69, is applied for the user-configured "Stop Time" regardless of the motor speed (e.g.,
Automatic Zero Speed Detection disabled). This braking method can be used in applications where
detecting zero speed is ineffective or when braking the motor to a complete stop results in random
overload trips. Note that an ideal Stop Time setting can be accomplished by trial and error, but should
always allow for some coast time. Setting the Stop Time for too long of a time period can result in braking
current to be applied to a stopped motor and will likely result in overload trips.
The direction of motor rotation is determined by the sign (+ or -) of Slow Speed, Parameter 72.

With Slow Brake Cur, Parameter 73, set to 0 (default), the motor will coast-to-stop from Slow Speed. When
the value is between 1...350 braking current is applied from Slow Speed.

External Braking Control


The external braking control feature enables an external mechanical motor brake
to function in concert with the SMC-50 stop parameter. When the Stop Mode,
Parameter 65, is set to Ext Brake and the stop maneuver is commanded, the
starter will remove power to the motor and close any auxiliary output configured
for External Brake. The auxiliary output relay configured for External Brake
will remain active for the user-configured Stop Time, Parameter 66. Once the
Stop Time is complete, the unit will open the auxiliary output and switch to the
stopped state. While in the External Brake stopped mode, all relays and status
functions will operate as they would in any other mode.
The appropriate auxiliary relay must be configured for the Ext. Brake stopping function using the Aux X relay
configuration parameter (e.g., Aux 1:Parameter 172, Aux 2: Parameter 176, etc.).

Table 29 - External Braking Control Mode Parameter List


Parameter Number Parameter Name Minimum/Maximum [Default] Access Units

90

65

Stop Mode

Ext Brake

66

Stop Time

[0]-999

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

SECS

Operating Modes

Running Modes

Chapter 3

Solid-State (SCR) Control Mode


The unit will run at full voltage under SCR control mode when the unit is at full
speed and when no external bypass contactor is provided. All SMC-50 diagnostic
and power monitoring features are available in this running mode.

External Bypass Control Mode


An external bypass contactor may be configured to operate the motor while
running at full voltage and speed. The SMC-50 controls the external bypass
contactor by using one of the auxiliary relay outputs configured to Ext. Bypass
using that output's configuration parameter.

Devices rated 90180 A


In external bypass control mode on devices rated 90180 A, the controller's
integral current sensors are out of the control circuit. If all the current sensing
features (including motor overload) are desired while running in external bypass
control mode, then the optional PTC/Ground Fault/External Current
Transformer Expansion Module (150-SM2) and an 825-MCM180 current
sensor are required. See Figure 28 on page 46 and Figure 44 on page 63.

Devices rated 210520 A


In external bypass control mode on devices rated 210520 A, the controller's
integral current sensors remain in the control circuit by using Cat. No.
150-SCBK (devices rated 210320 A) or Cat. No. 150-SDBK (devices rated
361520 A) Bypass Kits. See Figure 66 on page 92. The optional PTC/Ground
Fault/External Current Transformer Expansion Module (150-SM2) and an
825-MCM20 with user supplied CTs with 5 A secondary can be used in place of
the bypass kits. See Figure 26 on page 44 and Figure 44 on page 63.
NOTE:

When using the Cat. No. 150-SCBK or 150-SDBK bypass kit, the controller
firmware must be FRN 3.001 or higher.

The Cat. No. 150-SM2 Expansion Module can only be inserted into control
module expansion port 7 or 8. In addition, only one 150-SM2 Expansion Module
can be used per control module. Once the 150-SM2 Expansion Module is
installed in the control module and power is applied, it must be configured using
the 20-HIM-A6, the 20-HIM-C6S, or PC software (e.g. DriveExplorer). For
additional configuration details refer to Chapter 2, Installation & Wiring, and
Chapter 5, Programming.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

91

Chapter 3

Operating Modes

Figure 66 - Wiring Diagram for Cat. No. 150-SC or Cat. No. 150-SD Devices
with Bypass Contactor and Bypass Bus Kit

M
1 3

T1/2 L1/1
SMC-50
T2/4 L2/3
T3/6

Circuit
Protective
Device

3-Phase AC

Line Power

L3/5

Bypass Contactor (BC) 1 4 5


Customer supplied.
SMC-50 Bypass bus kit Cat. No. 150-SCBK (Frame C; Cat. No. 150-SC) or 150-SDBK (Frame D; Cat. No. 150-SD).
NOTE: Controller FRN 3.001 or higher is required.

Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance
is required on the motor. See the Isolation Contactor Applications for details.

Bypass must be controlled by an auxiliary contact of the SMC-50 that is configured for external bypass.
In North America, size the bypass contactor per the motor Hp and FLA. In IEC applications, size the bypass contactor per the motor AC-1 rating.The
short-circuit rating of the bypass contactor must be similar to the SMC-50.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching
components allows uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To
prevent potential personal injury or equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting
the motors locked rotor current on the line side of the SMC-50 is recommended. Operation of the isolation device should be coordinated using one of
the SMC-50 auxiliary contacts configured to NORMAL.

External Overload (all devices)


The SMC-50 can also be used with an external overload in conjunction with the
external bypass. In this configuration the external bypass contactor must be fully
rated to the motor Hp/kW and FLA. See Figure 67 on page 93.

92

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Figure 67 - Wiring Diagram for all Cat. No. 150-S Devices with Bypass and
External Overload

M
1 2

Circuit
Protective
Device

T1/2 L1/1
SMC-50
T2/4 L2/3
T3/6

3-Phase AC
Line Power

L3/5

Bypass Contactor (BC) 1 3 4


Overload 1
Customer supplied.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if maintenance
is required on the motor. See the Isolation Contactor Applications for details.

Bypass must be controlled by an auxiliary contact of the SMC-50 that is configured for external bypass.
Bypass contactor must be fully rated to motor Hp/kW and FLA.
NOTE: In addition to a small amount of leakage current flowing through an SCR in the off-state, failure of one or more solid-state power switching
components allows uncontrolled current to flow to the winding(s) of the motor. This could potentially result in overheating or damage to the motor. To
prevent potential personal injury or equipment damage, the installation of an isolation contactor or shunt trip-type circuit breaker capable of interrupting
the motors locked rotor current on the line side of the SMC-50 is recommended. Operation of the isolation device should be coordinated using one of
the SMC-50 auxiliary contacts configured to NORMAL.

Energy Saver Mode


The energy saver function only applies during light motor load situations at
which time the SMC-50 reduces current to the motor and thereby saves energy.
When in energy saver operation, the Energy Savings status bit is set. In addition,
Energy Savings, Parameter 15, indicates the percentage energy savings.
Parameter 17 - [Power Factor] should be monitored and recorded when the
motor is running at no/light load and at full/heavy load. The power factor value
where the controller enters Energy Saver mode is determined by setting
Parameter 193 - [Energy Saver] to a value between the no/light load and
full/heavy load recorded values.
Table 30 - Energy Saver Mode Parameter List
Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
15

Energy Savings

0100

17

Power Factor

-1.001.00

193

Energy Saver

[0.00]-1.00

R/W

NOTE:

Set Parameter 193=0 to diable Energy Saver mode.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

93

Chapter 3

Operating Modes

Emergency RUN
With the SMC-50, a control terminal or network (via Comm Control Word)
input can be configured as the Emergency Run command input. When this input
is active all faults are disabled.
NOTE:

Sequence of Operation

The Emergency Run command input does not actually start the unit, but
causes the unit to run in the Emergency Run mode. The Emergency Run
command can be initiated at any time. This command is not latched allowing
the Emergency Run mode to be cancelled while the unit is still running.

Figure 68 through Figure 73 show the different operation sequences for the Soft
Stop, Preset Slow Speed, Pump Control, SMB Smart Motor Braking, Accu-Stop,
and Slow Speed with Braking options.
When control power is present but 3-phase line power is not applied, a valid
START command causes AUX contacts configured for "Normal" to close. While
waiting for 3-phase line power, the SMC-50 controller will indicate "Starting".
When 3-phase line power is applied, the start sequence will be initiated.
ATTENTION: The user is responsible for determining which stopping
mode is best suited to the application and will meet applicable standards
for operator safety on a particular machine.
ATTENTION: Stopping modes are NOT intended to be used as an
emergency stop. See applicable standards for emergency stop
requirements.
ATTENTION: The Energy Savings setting is motor and load dependent.
Setting this to high may cause the unit to enter energy savings to soon
and increase current.

94

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Figure 68 - Soft Stop

Motor Speed
100%
Coast-to-Rest
Soft Stop

Start

Soft Stop

Run

Time in Seconds
Push Buttons
Start

Closed
Open

Stop

Closed
Open

Soft Stop 1
(Stop Option)

Closed
Open

Auxillary Contacts

If Soft Stop is Selected

Normal
Closed
Open
Up-to-Speed

If Coast-to-Rest is Selected
Closed
Open

When the Stop Mode, Parameter 65, configured for Soft Stop and with the Input push button configured for the
Stop Option.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

95

Chapter 3

Operating Modes

Figure 69 - Preset Slow Speed

Motor Speed
100%
Coast-to-Rest
Soft Stop
1...15%

1 Coast
2 Brake
Slow Speed

Start

Push Buttons

Run

Soft Stop

Time in Seconds

Soft Stop 3
(Stop Option) Closed
Open
Start

Closed
Open

Stop
Closed
Open
Slow Speed

Coast

Closed
Open

Auxillary Contacts
Normal

If Soft Stop is selected


Closed
Open
If Coast-to-Rest is selected

Up-to-Speed
Closed
Open

Coast if Slow Brake Cur Parameter = 0.


Brake if Slow Brake Cur Parameter >0 and <350.
When the Stop Mode, Parameter 65, configured for Soft Stop and with the Input push button configured for the
Stop Option.

96

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Figure 70 - Pump Control

Motor Speed
100%

Coast-to-Rest

Pump Start

Run

Pump Stop

Time in Seconds
Push Buttons
Start
Closed
Open
Stop
Closed
Pump Stop 1
(Stop Option)

Open
Closed
Open

Auxillary Contacts
Normal

If the Pump Stop is Selected

Closed
Open

Up-to-Speed

If the Coast-to-Rest is Selected


Closed
Open

When Stop Mode, Parameter 65, is configured for Pump Stop and the Input push button is configured for Stop
Option.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

97

Chapter 3

Operating Modes

Figure 71 - Smart Motor Braking (SMB)

Motor Speed
100%

Smart Motor Braking


Coast-to-Rest

Automatic Zero
Speed Shut-Off
Start

Run

Brake

Time in Seconds
Push Buttons
Start
Closed
Open
Stop
Closed
Open
Smart Motor Braking
(Stop Option 1 ) Closed
Open

Auxillary Contacts
If Brake
Selected

Normal
Closed
Open
Up-to-Speed
Closed

If Coast-to-Rest
Selected

Open

When Stop Mode, Parameter 65, is configured for SMB and the Input push button is configured for Stop Option.

98

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Figure 72 - Accu-Stop
MOTOR SPEED
100%
Coast-to-Rest

Brake

Coast from
Slow Speed
Brake from
Slow Speed

Slow
Speed
Slow
Speed

Start

Run

Accu-Stop

Time in Seconds

STOP
Closed
Open
START
Closed
Open
SLOW SPEED
Closed
Open

NORMAL
Closed
Open
UTS

Closed

Coast Input
Open

Slow Brake
Current = 0 = Coast

Open

NOTE: Parameter Selections:


1. Parameter 65: Stop Mode = SMB
2. Parameter 69: Braking Current = User Defined Value
3. Parameter 72: Slow Speed = User Defined Value/Selection
4. Parameter 73: Slow Brake Cur = User Defined Value (0 selected enables Coast-to-Rest)

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

99

Chapter 3

Operating Modes

Figure 73 - Slow Speed with Braking

Motor Speed
100%
Coast-to-Stop

1 Coast
2 Brake
Slow Speed

Braking
Start

Run

Brake

Time in Seconds
Push Buttons

Start
Closed
Open
Stop
Closed
Open

Coast

Slow Speed
Closed
Open
SMB
(Stop Option 3 )
Closed
Open

Auxillary Contacts

Brake

Normal
Closed
Open
Up-to-Speed
If the Coast-to-Rest
is Selected

Closed
Open

Coast if Slow Brake Cur Parameter = 0.


Brake if Slow Brake Cur Parameter >0 and <350.
When the Stop Mode, Parameter 65, is configured for SMB and the Input push button is configured for Stop
Option.

100

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Operating Modes

Chapter 3

Figure 74 - External Braking


Motor Speed

100%
Coast
External
Brake

Start
Closed

Open

Stop
Closed

Open
Ext. Brake
(Stop Option 1 )

Closed

Open
External
Brake

Aux Normal
Closed

Open

Coast

Aux External
Brake
Closed
User-Defined
Time

Open

When the Stop Mode, Parameter 65, is configured for Ext. Brake, (Eternal Brake) and the input push button is
configured for STOP option.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

101

Chapter 3

102

Operating Modes

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Protection & Diagnostic Functions

Overview

The SMC-50 provides both diagnostic and protection functions. These


functions are in the form of user-configured parameters which provide motor and
starter Alarms and Faults. Each configurable Alarm and Fault can be individually
enabled or disabled. In addition, many Alarms and Faults have a user defined time
delay available to help limit nuisance tripping. A Fault condition results in a
controller shutdown. An alarm can be used to alert an operator to a pending fault.
Motor and starter faults can be individually configured for automatic
reset/restart after configuring the number of restart attempts and restart time
delay. Restart attempts and restart delay are universal to all faults. See the Auto
Restart from Fault section in this chapter for additional details.
A multi-colored (red, green, amber) STATUS LED is located on the front of the
SMC-50 directly below the bezel/pocket for the 20-HIM-A6.
Figure 75 - Controller Status LED

L1/1

L2/3

STATUS

L3/5

PUSH
TO
RESET

HOLD
TO
TEST

STATUS
Controller
Status LED

T1/2

T2/4

T3/6

LED Display

Fault Condition

Solid RED

NON-resettable fault has occurred

Flashing RED

Resettable fault has occured

Additional diagnostic LEDs are located on the optional Bulletin 150-SM6


Parameter Configuration Module (PCM). This module provides simple and
limited parameter configurations. For additional diagnostic LED information,
see Chapter 9, Diagnostics.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

103

Chapter 4

Protection & Diagnostic Functions

20-HIM-A6, 20-HIM-C6 & Configuration Software


(e.g., DriveExplorer)
The 20-HIM-A6, 20-HIM-C6, and PC configuration/monitoring software
(e.g., DriveExplorer) provide detailed Fault and Alarm information. When an
SMC-50 Fault occurs, the HIM display indicates FAULTED along with the
Fault Code, a simple fault description, and the elapsed time since the fault
occurred. Other HIM screens provide more detailed data along with the ability
to reset the Fault/Alarm from the keypad. For more details regarding the
diagnostic use of these tools, see Chapter 9, Diagnostics.
To simplify identifying the source of a DPI port related Fault or Alarm, the
SMC-50 displays the DPI port number when posting the Fault or Alarm number.
EXAMPLE

If a 150-SM4 Digital I/O Option Module is located in the SMC-50 DPI Port
7 and is the source of a Fault, port number 7 will be displayed with the
Fault Code (e.g.,Port 7, Fault 26 is displayed as 7026).

Table 31 - SMC-50 DPI-Assigned Port Numbers & Source


DPI Port Number Source

DPI Port Number Source

SMC-50 Controller

Reserved

Front-Mounted HIM

Control Module Port 7

Remote DPI (top of SMC-50)

Control Module Port 8

Remote DPI

Control Module Port 9

20-COMM-X Module

10-15

Reserved

Reserved

When using a 20-COMM-X network communication module, it must physically be located in Control
Module Port 9. However, its DPI Port Number assignment is 4 because of the cable connection to the DPI
Port 4 located below the front-mounted HIM.

To access Port 3, the use of a 1203-S03 splitter inserted into Port 2 is required.

Enabling Starter & Motor Faults & Alarms


Motor and starter Faults and Alarms can be individually configured, enabled, and
disabled by the user. The parameters Motor Fault En, Starter Fault En, Motor
Alarm En, and Starter Alarm En are numbered bit fields for configuration to
enable (bit=1) or disable (bit =0) specific motor and/or starter Faults and
Alarms. This can be done by configuration tools (e.g., HIM or PC software) or
network communications.
Due to the number of Faults and Alarms being greater than 32, the configuration
bits are located in the lower and upper 16-bit fields (numbered 0-31) of the
associated SMC-50 parameters. The bits are broken up into the starter Faults and
motor Faults.

104

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

These parameters do not enable or disable Faults that may be generated by


expansion modules (e.g., 150-SM2, -SM4, etc.). When an expansion module is
plugged into a control module port (7, 8, or 9), a set of configuration parameters
appear to enable configuration of that specific module.
The following tables provide an overview of the motor and starter Fault and
Alarm Enable parameters. All bits are read (R) and write (W) enabled.
Table 32 - Enable/Disable Starter Fault/Alarm Matrix
Parameter
Number

Function/
Description

Fault/Alarm
Name

Bit
Bit
Units
Assignment Access [Default]

Starter Fault En

Volt Unbal
Overvoltage
Undervoltage
Phase Rev
[Line Loss]
[Open Gate]
Config Change
Freq
THD V

0
1
2
3
4
5
6
7
8

R/W

Bit = 0 Disabled
Bit = 1 Enabled
[Enabled]

Starter Alarm En Volt Unbal


Overvoltage
Undervoltage
Phase Rev
Line Loss
Open Gate
Config Change
Freq
THD V

0
1
2
3
4
5
6
7
8

R/W

Bit = 0 Disabled
Bit = 1 Enabled
[All Disabled as
Default]

Starter Fault
136

Starter Alarm
137

As displayed on the HIM or DriveExplorer configuration tools.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

105

Chapter 4

Protection & Diagnostic Functions

Table 33 - Enable/Disable Motor Fault/Alarm Matrix


Parameter
Number

Function/
Description

Fault/Alarm
Name

Bit
Bit
Units
Assignment Access [Default]

Motor Fault En

[Overload]
Underload
MWatts Over
MWatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Under
MVA Over
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
[Power Qual]
[Open Load]
THD1
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
27
18
19
20
21
22
23

R/W

Bit = 0 Disabled
Bit = 1 Enabled
[Enabled]

Motor Alarm En

Overload
Underload
MWatts Over
MWatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Under
MVA Over
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
Power Qual
Open Load
THD1
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
27
18
19
20
21
22
23

R/W

Bit = 0 Disabled
Bit = 1 Enabled
[All Disabled as
Default]

Motor Fault
230

Motor Alarm
231

As displayed on the HIM or DriveExplorer configuration tools.

106

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Enabling Option Module Functional Faults & Alarm


Not all option modules have faults and alarms associated with their specific
function(s). For example, the 150-SM4 Option I/O and 150-SM6 Parameter
Configuration Modules do not have functional faults or alarms. However, when
an option module has functional faults and alarms, it also has the ability to
individually configure, enable, and disable them like faults and alarms for the
controller and motor.

150-SM2 Option Module


The 150-SM2 Option Module has individually enabled faults and alarms
associated with the Ground Fault and Motor PTC functions. The following table
provides an overview.
Table 34 - 150-SM2 Faults & Alarms
Parameter
Number

Function/
Description

Fault/Alarm
Name

Bit
Bit
Units
Assignment Access [Default]

X02

Fault En

PTC
Gnd Flt

0
1

R/W

X03

Alarm En

PTC
Gnd Flt

0
1

R/W

NOTE:
Bit=0 Disabled
Bit=1 Enabled
[All Disabled]

As displayed on the HIM or DriveExplorer configuration tools.


X = the control module port number (7 or 8) in which the 150-SM2 resides.

150-SM3 Option Module


The 150-SM3 Option Module has individually enabled faults and alarms
associated with the analog inputs and outputs. The following table provides an
overview.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

107

Chapter 4

Protection & Diagnostic Functions

Table 35 - 150-SM3 Faults & Alarms


Parameter
Number

Function/
Description

Fault/Alarm
Name

Bit
Bit
Units
Assignment Access [Default]

X37

Fault En

IN1 Over
IN1 Under
IN2 Over
IN2 Under
OUT1 Shorted
OUT1 Open
OUT2 Shorted
OUT2 Open

0
1
2
3
4
5
6
7

R/W

X38

Alarm En

IN1 Over
IN1 Under
IN2 Over
IN2 Under
OUT1 Shorted
OUT1 Open
OUT2 Shorted
OUT2 Open

0
1
2
3
4
5
6
7

R/W

NOTE:
Bit=0 Disabled
Bit=1 Enabled
[All Disabled]

As displayed on the HIM or DriveExplorer configuration tools.


X = the control module port number (7 or 8) in which the 150-SM2 resides.

Protection & Diagnostics

The following describes the SMC-50 protection and diagnostic functions.

Overload Fault & Alarm


Overload Fault (Code 21)
The SMC-50 meets applicable requirements as a motor overload protective
device. Thermal memory provides added protection and maintains motor
thermal data when control power is removed.
The SMC-50 provides overload protection through true RMS current
measurement of the individual phase currents of the connected motor. A thermal
model that simulates the actual heating of the motor is calculated based on the
following:
measured maximum motor current value,
Motor FLC Setting, Parameter 78,
Overload (Trip) Class Setting, Parameter 75, and
Motor Service Factor, Parameter 77, (obtained from the motor nameplate)
Trip Class is defined as the maximum time in seconds for an overload trip to occur when the motors operating
current is six times its rated current. The SMC-50 overload function offers an adjustable Trip Class range of 5...30,
which can be programmed in increments of one via Overload Class, Parameter 75, and Overload Class 2, Parameter
76 (configuration for a second OL Class).

108

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

The Motor Thermal Usage (MTU), Parameter 18, displays the percentage of the
motor overload currently utilized. The SMC-50 overload fault will trip the motor
when (1) the motor overload fault is enabled and (2) the MTU reaches 100%.
The overload function calculates and provides motor overload data through:
MTU, Parameter 18,
Time to OL Trip, Parameter 19, and
Time to OL Reset, Parameter 20.
NOTE:

Trip rating is 118% of the programmed motor FLC.

The SMC-50 continues to calculate the reduction in MTU (decay rate) when the
motor is powered down (cooling). This is enabled using the SMC-50s real time
clock (RTC) function. When control power is lost, the SMC-50 saves the power
down thermal level and time. Then, when power is reapplied, the SMC-50 reads
the current time, power down time, and power down thermal level. From this
data, the SMC-50 calculates the new thermal information for the overload.

Overload Alarm
In addition to the Overload Fault, an Overload Alarm is also available. The
desired value or level of the alarm is set up with Overload Alarm Level, (Overload
A Lvl), Parameter 83, which can be set from 0% to 100%. When the MTU value
reaches the set percentage of the thermal trip level, then the alarm becomes active.
When the MTU value falls below the set percentage of the thermal trip level, the
alarm becomes inactive.
Motor Thermal Usage (Mtr Therm Usage), Parameter 18, provides the current
motor thermal usage value. This parameter reads from 0% to 200%, where 100%
corresponds to a fault condition.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

109

Chapter 4

Protection & Diagnostic Functions

Figure 76 - Overload Trip Curves


Class 10

100

10

0.1
1

3 4 5

100

10

0.1
1

10

Multiples of FLC

100

10

1
1

10

10000

Approximate Trip Time (in seconds)

Approximate Trip Time (in seconds)

100

1000

100

10

1
1

10

Multiples of FLC

10

Class 30

Class 25

1000

2 3 4 5

Multiples of FLC

10000

2 3 45

1000

2 3 4 5 10

Class 20

10000

Multiples of FLC

10000

Approximate Trip Time (in seconds)

Class 15

10000

Approximate Trip Time (in seconds)

Approximate Trip Time (in seconds)

Approximate Trip Time (in seconds)

Class 5
10000

3 4 5

10

1000

100

10

2 3 45

10

Multiples of FLC

Multiples of FLC

Approximate Trip Time for


3-Phase Balanced Condition from:
Cold Start
Hot Start

Figure 77 - Restart Trip Curves after Auto Reset


100000

Time in Seconds

1000

100

10

Class
10
15
20
30

100

Auto Reset Time


in Seconds
90
135
180
270

1000

% Full Load Current Setting

Overload Shunt Time, Parameter 81, allows disabling (shunt) the overload at the
beginning of the start cycle. The length of time that the overload is disabled
(shunted) is defined by this parameter. The motor overload is not accumulating
data (MTU) during this period.
110

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

The SMC-50 can be configured to automatically reset the overload fault when it
has cooled to the set Overload Reset Level, Parameter 80. The Motor Restart
Enabled (Motor Restart En), Parameter 264, must be enabled (Overload = Set)
to allow the Overload Reset Level parameter to function.
The Time to Overload Trip (Time to OL Trip), Parameter 19, provides
indication of how much time is left before an overload trip will occur given the
current operating conditions. If the overload fault is disabled, this parameter will
read its maximum value.
The Time to OL Reset, Parameter 20, provides indication of how much time is
left before an overload fault will clear based on the cooling (decay) algorithm. If
the overload parameter is disabled or has not tripped, then this parameter will be
zero.
Table 36 - Overload Parameter List
Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
75

Overload Class

5-30 [10]

76

Overload Class 2

5-30 [10]

77

Service Factor

0.01-1.99 [1.15]

78

Motor FLC

[1.0]-2200.0

Amps

80

OL Reset Level

1-99 [75]

%MTU

18

Motor Therm Usage

0-200

81

OL Shunt Time

[0]-999

82

OL Inhibit Time

[0]-999

83

Overload A Lvl

[0]-100

19

Time to OL Trip

0-10000

20

Time to OL Reset

0-10000

84

Locked Rtr Level

400-1000 [600]

R/W

%FLC

85

Locked Rtr Time

[1]-1000

R/W

SECS

R/W

%MTU
SECS

R/W

SECS
%MTU

SECS
SECS

As displayed on the HIM or DriveExplorer configuration tools. Configuration for a second OL Class.

Underload Fault & Alarm


The SMC-50 provides the ability to trip on underload when the motor current
falls below a user-defined level for a user-defined time.

Underload Fault (Code 22)


Motor current less than a specific level may indicate a mechanical malfunction in
the installation (e.g., a torn conveyor belt, damaged fan blade, broken shaft, or
worn tool). Such conditions may not harm the motor, but can lead to loss of

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

111

Chapter 4

Protection & Diagnostic Functions

production. Rapid Underload Fault detection helps to minimize damage and loss
of production.
Underload Fault current protection, Fault Code 22, is enabled or disabled via the
motor Underload Enable/Disable bit in the Motor Fault Enable, Parameter 230.
The value or level of the Fault current is configured using Underload Fault Level
(Underload F Lvl), Parameter 86. A configurable Fault Delay Time using
Underload Fault Delay (Underload F Dly), Parameter 87, is also available to help
eliminate nuisance faults.

Underload Alarm
A motor Underload Alarm is also available. This is configured exactly as the
Underload Fault using Underload Alarm Level (Underload A Lvl), Parameter 88,
and Underload Alarm Delay (Underload A Dly), Parameter 89. The Alarm can
be enabled or disabled using the Underload bit in the Motor Alarm Enabled,
Parameter 231.
The SMC-50 checks for a motor Underload condition approximately every
0.025 seconds.
NOTE:

Underload protection is active when the motor is at speed.

Table 37 - Underload Parameter List


Parameter Number Parameter Name

Minimum/Maximum [Default] Access Units

86

Underload F Lvl

[0]-99

87

Underload F Dly

[0.1]-99.0

88

Underload A Lvl

[0]-99

89

Underload A Dly

[0.1]-99.0

%FLC
R/W

SECS
%FLC
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Line Power Undervoltage Protection


Undervoltage Fault (Code 20)
The SMC-50 has the ability to protect against low line power voltage. The
Undervoltage Fault, Code 20, provides protection from a line power
undervoltage condition. An undervoltage fault condition exists if the average of
the three-phase Line Voltage (Line Voltage), Parameter 46, falls below the
user-defined voltage level (Undervolt F Lvl), Parameter 98, for a user-defined
time Undervolt Fault Delay. See Table 38
Undervoltage Fault protection is enabled or disabled via the Undervoltage
Enable/Disable bit in the Starter Fault Enable, Parameter 136.

112

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Undervoltage Alarm
In addition to the Fault, an Undervoltage Alarm is also available. This is set up
exactly like the Fault using the "Undervolt A Lvl", Parameter 100, and the
"Undervolt A Dly", Parameter 101. The Undervoltage Alarm is enabled or
disabled via the Undervoltage Enable/Disable bit in the Starter Alarm Enable,
Parameter 137.
Table 38 - Undervoltage Protection Parameter List
Parameter Number Parameter Name

Minimum/Maximum [Default] Access Units

46

Line Voltage

0-700 [400]

Volts

98

Undervolt F Lvl

0-100 [90]

%V

99

Undervolt F Dly

0.1-99.0 [3.0]

100

Undervolt A Lvl

0-100 [90]

%V

101

Undervolt A Dly

0.1-99.0 [3.0]

SECS

R/W

SECS

As displayed on the HIM or DriveExplorer configuration tools.

Line Power Overvoltage Protection Fault & Alarm


Overvoltage Fault (Code 19)
The SMC-50 has the ability to protect against high line power voltage. The
Overvoltage Fault, Code 19, provides protection from a line power Overvoltage
condition. An overvoltage condition exists if the average of the three-phase line
voltage exceeds a user-defined percent above that level (Overvolt F Lvl) for a
user-defined time, "Overvolt F Dly". See Table 39 on page 114.
Overvoltage protection is enabled or disabled via the Overvoltage
Enable/Disable bit in the Starter Fault Enable, Parameter 136.

Overvoltage Alarm
In addition to the Fault, an Overvoltage Alarm is also available. This is set up
exactly as like the Overvoltage Fault using the Overvoltage Alarm Level and
Overvoltage Alarm Delay parameters.
The Overvoltage Alarm is enabled or disabled via the Overvoltage
Enable/Disable bit in the Starer Alarm Enable, Parameter 137.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

113

Chapter 4

Protection & Diagnostic Functions

Table 39 - Overvoltage Protection Parameter List


Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

46

Line Voltage

0-700 [400]

Volts

102

Overvolt F Lvl

100-199 [110]

103

Overvolt F Dly

0.1-.99.0 [3.0]

104

Overvolt A Lvl

100-199 [110]

105

Overvolt A Dly

0.1-.99.0 [3.0]

SECS

R/W

SECS

As displayed on the HIM or DriveExplorer configuration tools.

Current Imbalance Protection Fault & Alarm


A current imbalance condition can be caused by an unbalance in the voltage
supply, unequal motor winding impedance, or long and varying wire lengths.
When a current imbalance condition exists, the motor can experience an
additional temperature rise, resulting in degradation of the motor insulation and
reduction in life expectancy. Rapid current imbalance fault detection helps
extend the motors life expectancy and minimize potential damage and loss of
production.
The current imbalance calculation is equal to the largest deviation of the three
current signals (RMS phase current) from the average phase current, divided by
the average phase current. Note that the power pole current is used for the current
imbalance calculation.

Current Imbalance Fault (Code 42)


A Current Imbalance Fault condition, Fault Code 42, occurs when the calculated
imbalance level rises above a user-defined level, Current Imbalance Fault Level,
for a user-defined time, Current Imbalance Fault Delay. See Table 40 on
page 115.
Current imbalance protection is enabled or disabled using the Current Imbalance
bit in the Motor Fault Enable, Parameter 230.

Current Imbalance Alarm


In addition to the Current Imbalance Fault, a Current Imbalance Alarm is also
available. This is set up exactly like the Current Imbalance Fault using the
Current Imbalance Alarm Level and Current Imbalance Alarm Delay parameters.
The Current Imbalance Alarm can be enabled or disabled using the Current
Imbalance bit in the Motor Alarm Enable, Parameter 231.

114

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Table 40 - Current Imbalance Parameter List


Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

110

Cur Imbal F Lvl

1-25 [15]

111

Cur Imbal F Dly

0.1-.99.0 [3.0]

112

Cur Imbal A Lvl

1-25 [10]

113

Cur Imbal A Dly

0.1-.99.0 [3.0]

%
R/W

SECS
%
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Voltage Unbalance Protection Fault & Alarm


An unbalance in the voltage supply results in a current imbalance. This causes the
motor to experience an additional temperature rise, resulting in degradation of
the motor insulation and reducing its life expectancy. Voltage unbalance
detection helps extend the motor life expectancy and minimize potential damage
and loss of production.
The voltage unbalance (Vu) calculation is equal to the largest deviation (Vd) of
the three-phase voltage signals (RMS phase voltage) from the average of the RMS
phase voltage (Vave), divided by the average voltage. In other words:
Vu% = 100

( VV )
d
ave

Note that the phase-to-phase voltage is used in the calculation for voltage
unbalance.

Voltage Unbalance Fault (Code 18)


A Voltage Unbalance Fault condition, Fault Code 18, occurs when the calculated
unbalance level rises above a user-defined level, Voltage Unbalance Fault Level,
for a user-defined time, Voltage Unbalance Fault Delay. See Table 41 on
page 116.
Voltage unbalance protection is enabled or disabled using the Voltage Unbalance
bit in the Starter Fault Enable, Parameter 136.

Voltage Unbalance Alarm


In addition to the Voltage Unbalance Fault, a Voltage Unbalance Alarm is also
available. This is set up exactly like that of the Voltage Unbalance Fault using the
Voltage Unbalance Alarm Level and Voltage Unbalance Alarm Delay parameters.
This Voltage Unbalance Alarm is enabled or disabled using the Voltage
Unbalance bit in the Starter Alarm Enable, Parameter 137.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

115

Chapter 4

Protection & Diagnostic Functions

Table 41 - Voltage Unbalance Protection Parameter List


Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

106

Volt Unbal F Lvl

1-25 [15]

107

Volt Unbal F Dly

0.1-.99.0 [3.0]

108

Volt Unbal A Lvl

1-25 [10]

109

Volt Unbal A Dly

0.1-.99.0 [3.0]

%
R/W

SECS
%
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Phase Reversal Protection


Phase Reversal Fault (Code 25)
The SMC-50 provides Fault Protection, Fault Code 25, against reverse
connection (CBA) of line power phases.
Phase Reversal protection is enabled or disabled via the "Phase Rev" bit in the
Starter Fault Enable, Parameter 136. There are no phase reversal fault parameters
to configure.
A phase reversal Alarm is also available and enabled via the "Phase Rev" bit in the
Starter Alarm Enable, Parameter 137. There are no Alarm parameters to
configure.

High & Low Line Power Frequency Protection Fault & Alarm
The SMC-50 has the ability to protect against poor line power quality by
offering programmable frequency-based protection. The user can fault the starter
if the line power frequency is either too high or too low.
High and low frequency limits for both Faults and Alarms are configured
through the parameters listed in Table 42. Note that each also has a
programmable delay to limit nuisance trips.

Frequency Fault (Code 49)


The high/low Frequency Fault, Code 49, is enabled or disabled using the
Frequency bit "Freq" in the Starter Fault Enable, Parameter 136.

116

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Frequency Alarm
In addition to the Fault, a Frequency Alarm is also available. The Frequency
Alarm is enabled or disabled using the Frequency bit in the Starter Alarm Enable,
Parameter 137.
NOTE:

Regardless of the user-defined high or low frequency Fault or Alarm levels, if


the line power frequency falls below 45 Hz or above 66 Hz, the SMC-50 will
enter a wait state (stop and will not start, or will not start if already stopped)
until the frequency returns within the 45 Hz to 66 Hz range.

Table 42 - High & Low Line Power Frequency Parameter List


Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

129

Freq High F Lvl

45-66 [63]

Hz

225

Freq High F Dly

[0.1]-.99.0

SECS

130

Freq Low F Lvl

45-66 [47]

Hz

227

Freq Low F Dly

[0.1]-.99.0

131

Freq High A Lvl

45-66 [63]

226

Freq High A Dly

[0.1]-.99.0

SECS

132

Freq Low A Lvl

45-66 [47]

Hz

228

Freq Low A Dly

[0.1]-.99.0

SECS

R/W

SECS
Hz

As displayed on the HIM or DriveExplorer configuration tools.

Stall Protection Fault & Alarm


When a motor stalls (stops) during its starting sequence, the motor heats up very
rapidly; after some permissible stall time, the motor reaches the temperature limit
of its insulation. Rapid stall detection during the starting sequence can extend the
motors life as well as minimize the potential damage and loss of production.

Stall Fault (Code 24)


When the SMC-50 is instructed to start a motor and the programmed start
Ramp Time has completed before the motor is Up-to-Speed (UTS), the start
sequence will continue until one of the following occurs:
motor reaches full speed,
Stall Fault, Code 24, occurs,
indefinitely if the stall fault is disabled, or
until a motor overload or SCR overtemperature condition
When the stall feature is enabled, the SMC-50 will start an internal timer when
the programmed Ramp Time expires. When this timer reaches the time value
programmed in the Stall Delay, Parameter 188, a Stall Fault is generated. If the
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

117

Chapter 4

Protection & Diagnostic Functions

Stall Delay parameter is set to zero, then the Fault will occur immediately if the
motor is not UTS at the completion of the programmed Ramp Time. If the
SMC-50 detects that the motor is UTS before the Stall Delay, it will consider the
start sequence complete, switch to full voltage, and not generate a Stall
Fault/Alarm.
NOTE:

Due to the beginning of the Linear Speed Starting mode being an open loop
voltage control, the actual starting time may vary depending on the motor
load. For this reason (and to avoid nuisance faults), the SMC-50 automatically
adds a time to the configured starting ramp time before the stall timer begins
to count. The time factor is 50% of the configured start ramp time.

Stall Fault protection is enabled or disabled via the "Stall" bit in the Motor Fault
Enable, Parameter 230.

Stall Alarm
In addition to the Stall Fault, a Stall Alarm can also be enabled, which will
activate under the same condition as the Stall Fault. In this case, the Alarm will be
cleared once the motor leaves the starting state (e.g., is UTS, is stopped, faulted,
etc.).
The Stall Alarm is enabled or disabled via the "Stall" bit in the Motor Alarm
Enable, Parameter 231.
Table 43 - Stall Protection Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

188

0.0-30.0 [10.0]

Stall Delay

R/W

As displayed on the HIM or DriveExplorer configuration tools.


Figure 78 - Stall Protection

% FLC

600%

Programmed Start Time


Time in Seconds

118

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Stall

SECS

Protection & Diagnostic Functions

Chapter 4

Jam Detection Fault & Alarm


Motor operational (run) current greater than the motor nameplate rating may
indicate a jam condition due to a conveyor jam or jammed drive gear. These
conditions can result in overheating of the motor and equipment damage. Rapid
Jam detection helps to minimize damage and loss of production.
NOTE:

The SMC-50 starter SCR Overtemperature Fault (see SCR Overtemperature)


may occur before the jam trip in the case of high current situations.

Jam Fault (Code 23)


The SMC-50 Jam Fault, Fault Code 23, provides detection of a motor jam. A jam
condition exists if the motor current rises above a user-defined level for a
user-defined time while in the run mode.
NOTE:

This fault is not active during starting or stopping.

The Jam Level, Parameter 114, is a percentage of the motors Full Load Current
Parameter 78. If the actual motor current rises above the Jam Fault Level ( Jam F
Lvl) for a time equal to the Jam Fault Delay ( Jam F Dly) then a Fault will be
generated. See Table 44 and Figure 79. Jam protection is enabled or disabled
using the Jam bit in the Motor Fault Enable, Parameter 230.

Jam Alarm
In addition to the Fault, a Jam Alarm is also available. This is set up exactly like
the Fault Jam, using Jam Alarm Level and Jam Alarm Delay. This Alarm is
enabled or disabled using the Jam bit in the Motor Alarm Enable, Parameter 231.
Table 44 - Jam Detection Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

78

Motor FLC

[1.0]-2200.0

Amps

114

Jam F Lvl

0-[1000]

%FLC

115

Jam F Dly

[0.1]-99.0

116

Jam A Lvl

0-[1000]

%FLC

117

Jam A Dly

[0.1]-99.0

SECS

R/W

SECS

As displayed on the HIM or DriveExplorer configuration tools.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

119

Chapter 4

Protection & Diagnostic Functions

Figure 79 - Jam Detection

% FLC

User-Defined Trip Level

100%

Jam

Running
Time in Seconds

Real Power Protection


(MWatts)

Motor Over Power Real Fault & Alarm


Motor Over Power Real Fault (Code 44)
A Motor Over Power Real Fault, Code 44, condition occurs when the real power
being consumed by the motor has risen above a user-defined level MWatts Ov F
Lvl, Parameter 90, for the user-defined time MWatts Ov F Dly, Parameter 91.
This over power real Fault is enabled or disabled using the MWatts Over bit in
the Motor Fault Enable, Parameter 230.

Motor Over Power Real Alarm


A motor overpower real Alarm is also available. This is set up exactly like the
motor Fault using Parameter MWatts Ov A Lvl and MWatts Ov A Dly. This
alarm is enabled or disabled using the MWatts Over bit in the Motor Alarm
Enable, Parameter 231.
Table 45 - Motor Overpower Real Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

90

MWatts Ov F Lvl

[0.000]-1000.00

91

MWatts Ov F Dly

[0.1]-99.0

92

MWatts Ov A Lvl

[0.000]-1000.00

93

MWatts Ov A Dly

[0.1]-99.0

As displayed on the HIM or DriveExplorer configuration tools.

120

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

MW
R/W

SECS
MW
SECS

Protection & Diagnostic Functions

Chapter 4

Motor Under Power Real Fault & Alarm


Motor Under Power Real Fault (Code 43)
A Motor Under Power Real Fault, Fault Code 43, condition occurs when the real
power being consumed by the motor falls below a user-defined level MWatts Un
F Lvl, Parameter 94, for the user-defined time MWatts Un F Dly, Parameter 95.
This Fault is enabled or disabled using the MWatts Under bit in the Motor Fault
En, Parameter 230.

Motor Under Power Real Alarm


In addition to the Fault, an Alarm is also available. This is set up exactly like the
motor Fault using Parameter MWatts Un A Lvl and MWatts Un A Dly. This
alarm is enabled or disabled using the MWatts Under bit in the Motor Alarm En,
Parameter 231.
Table 46 - Motor Over Power Real Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

94

MWatts Un F Lvl

[0.000]-1000.000

95

MWatts Un F Dly

[0.1]-99.0

96

MWatts Un A Lvl

[0.000]-1000.000

97

MWatts Un A Dly

[0.1]-99.0

MW
R/W

SECS
MW
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Reactive Power Protection


(MVAR)

The SMC-50 has the ability to protect against excessive reactive power (MVAR).
The user can protect (Fault) or issue a warning (Alarm) in the event that the
motor reactive power (MVAR) consumption (+) or generation (-) is too high.
This protection can be used with synchronous motors or motors that have active
Power Factor correction capacitors.

Motor Over Power Reactive Positive (Motor Consumed) Fault


& Alarm
Motor Over Power Reactive Positive Fault (Code 46)
A Motor Over Power Reactive Positive Fault condition, Fault Code 46, occurs
when the reactive power being consumed by the motor rises above a user-defined
level +MVAR Ov F Lvl, Parameter 232, for the user-defined delay time +MVAR
Ov F Dly, Parameter 233.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

121

Chapter 4

Protection & Diagnostic Functions

This Fault is enabled or disabled using the +MVAR Over bit in the Motor Fault
Enable, Parameter 230.

Motor Over Power Reactive Positive Alarm


In addition to the Fault, a Motor Over Power Reactive Alarm is also available.
This is set up exactly like the Fault using parameters +MVAR Ov A Lvl and
+MVAR Ov A Dly, as shown in Table 47. The Alarm is enabled or disabled using
the +MVAR Over bit in the Motor Alarm Enable, Parameter 231.
Table 47 - Motor Over Power Reactive Positive Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

232

+MVAR Ov F Lvl

[0.000]-1000.000

233

+MVAR Ov F Dly

[0.1]-99.0

234

+MVAR Ov A Lvl

[0.000]-1000.000

235

+MVAR Ov A Dly

[0.1]-99.0

MVAR
R/W

SECS
MVAR
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Motor Under Power Reactive Positive (Motor Consumed) Fault


& Alarm
Motor Under Power Reactive Positive Fault (Code 45)
A Motor Under Power Reactive Positive Fault condition, Fault Code 45, occurs
when the reactive power being consumed by the motor falls below the
user-defined level +MVAR Un F Lvl, Parameter 236, for the user-defined delay
time +MVAR Un F Dly, Parameter 237.
This Fault is enabled or disabled using the +MVAR Under bit in the Motor Fault
Enable, Parameter 230.

Motor Under Power Reactive Positive Alarm


In addition to the Fault, an Under Power Reactive Alarm is also available. This is
set up exactly like the Fault using parameters +MVAR Un A Lvl and +MVAR Un
A Dly, as shown in Table 48. The Alarm is enabled or disabled using the +MVAR
Under bit in the Motor Alarm Enable, Parameter 231.

122

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Table 48 - Motor Underpower Reactive Positive Parameter List


Parameter Number Parameter Name

Minimum/Maximum [Default] Access Units

236

+MVAR Un F Lvl

[0.000]-1000.000

237

+MVAR Un F Dly

[0.1]-99.0

238

+MVAR Un A Lvl

[0.000]-1000.000

239

+MVAR Un A Dly

[0.1]-99.0

MVAR
R/W

SECS
MVAR
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Motor Over Power Reactive Negative (Motor Generated) Fault


& Alarm
Motor Over Power Reactive Negative Fault (Code 67)
A Motor Over Power Reactive Negative Fault, Fault Code 67, condition occurs
when the Reactive Power being generated by the motor rises above a user-defined
level -MVAR Ov F Lvl, Parameter 297, for a user-defined time -MVAR Ov F Dly,
Parameter 298. This only occurs when the Reactive Power is negative.
The Over Power Reactive Negative Fault is enabled or disabled using the -MVAR
Over bit in the Motor Fault Enable, Parameter 230.

Motor Over Power Reactive Negative Alarm


In addition to the Over Power Reactive Negative Fault, an Over Power Reactive
Negative Alarm is also available. This is set up exactly like the Fault, using -MVAR
Ov A Lvl, Parameter 299, and -MVAR Ov A Dly, Parameter 300. This Alarm is
enabled or disabled using the -MVAR Over bit in the Motor Alarm Enable,
Parameter 231.
Table 49 - Motor Over Power Reactive Negative Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

297

-MVAR Ov F Lvl

-1000.000-[0.000]

298

-MVAR Ov F Dly

[0.1]-99.0

299

-MVAR Ov A Lvl

-1000.000-[0.000]

300

-MVAR Ov A Dly

[0.1]-99.0

MVAR
R/W

SECS
MVAR
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

123

Chapter 4

Protection & Diagnostic Functions

Motor Under Power Reactive Negative (Motor Generated)


Fault & Alarm
Motor Under Power Reactive Negative Fault (Code 68)
A Motor Under Power Reactive Negative Fault, Fault Code 68, condition occurs
when the Reactive Power being generated by the motor falls below a user-defined
level -MVAR Un F Lvl, Parameter 301, for the user-defined time -MVAR Un F
Dly, Parameter 302. This only occurs when the Reactive Power is negative.
The Motor Under Power Reactive Negative Fault is enabled or disabled using the
-MVAR Under bit in the Motor Fault Enable, Parameter 230.

Motor Under Power Reactive Negative Alarm


In addition to the Motor Under Power Reactive Negative Fault, a Motor
Underpower Reactive Negative Alarm is also available. This is set up exactly like
the Fault, using -MVAR Un A Lvl, Parameter 303, and -MVAR Un A Dly,
Parameter 304. This Alarm is enabled or disabled using the -MVAR Under bit in
the Motor Alarm Enable, Parameter 231.
Table 50 - Motor Underpower Reactive Negative Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

301

-MVAR Un F Lvl

-1000.000- [0.000]

302

-MVAR Un F Dly

[0.1]-99.0

303

-MVAR Un ALvl

-1000.000- [0.000]

304

-MVAR Un A Dly

[0.1]-99.0

MVAR
R/W

SECS
MVAR
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Apparent Power Protection


(MVA)

The SMC-50 has the ability to protect against excessive apparent power. The
user can protect (Fault) or issue a warning (Alarm) in the event that the apparent
power (MVA) consumption of the motor being controlled is too high or too low.

Motor Over Power Apparent Fault & Alarm


Motor Over Power Apparent Fault (Code 48)
A Motor Over Power Apparent Fault, Fault Code 48, condition occurs when the
Apparent Power being consumed by the motor rises above a user-defined level
(MVA Ov F Lvl), Parameter 240, for a user-defined time, MVA Ov F Dly,
Parameter 241. This Fault is enabled or disabled using the MVA Over Power bit
in the Motor Fault Enable, Parameter 230.

124

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Motor Over Power Apparent Alarm


In addition to the Motor Over Power Apparent Fault, a Motor Over Power
Apparent Alarm is also available. This is set up exactly like the Fault using MVA
Over Alarm Level, Parameter 242, and MVA Over Alarm Delay, Parameter 243.
This Alarm is enabled or disabled using the MVA Over Power bit in the Motor
Alarm Enable, Parameter 231.
Table 51 - Motor Over Power Apparent Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

240

MVA Ov F Lvl

[0.000] - 1000.000

241

MVA Ov F Dly

[0.1]-99.0

242

MVA Ov A Lvl

[0.000] - 1000.000

243

MVA Ov A Dly

[0.1]-99.0

MVA
R/W

SECS
MVA
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Motor Under Power Apparent Fault & Alarm


Motor Under Power Apparent Fault (Code 47)
A Motor Under Power Apparent Fault, Fault Code 47, condition occurs when
the Apparent Power being consumed by the motor falls below a user-defined
time, MVA Un F Lvl, Parameter 244, for a user-defined time, MVA Un F Dly,
Parameter 245. This Fault is enabled or disabled using the MVA Under Power bit
in the Motor Fault Enable, Parameter 230.

Motor Under Power Apparent Alarm


In addition to the Motor Under Power Apparent Fault, a Motor Under Power
Apparent Alarm is also available. This is set up exactly like the Fault using MVA
Under Alarm Level, Parameter 246, and MVA Over Alarm Delay, Parameter 242.
This Alarm is enabled or disabled using the MVA Under Power bit in the Motor
Alarm Enable, Parameter 231.
Table 52 - Motor Under Power Apparent Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

244

MVA Un F Lvl

[0.000] - 1000.000

245

MVA Un F Dly

[0.1]-99.0

246

MVA Un A Lvl

[0.000] - 1000.000

247

MVA Un A Dly

[0.1]-99.0

MVA
R/W

SECS
MVA
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

125

Chapter 4

Protection & Diagnostic Functions

Power Factor (PF)


Protection

Motor Power Factor (PF) Fault & Alarm


Lagging Power Factor Under Fault (Code 63)
Leading Power Factor Under Fault (Code 64)
Lagging Power Factor Over Fault (Code 65)
Leading Power Factor Over Fault (Code 66)
Lagging Power Factor Under Alarm
Leading Power Factor Under Alarm
Lagging Power Factor Over Alarm
Leading Power Factor Over Alarm
The SMC-50 has the ability to protect against an excessive PF for specific
applications that require monitoring the phase angle difference between voltage
and current. The user can protect the motor by using the Fault function or issue a
warning using the Alarm function in the event that the PF for an electric motor is
either too high or too low for both Leading, Fault Code 64 and 66, and Lagging,
Fault Code 63 and 65, conditions.
In addition to the configurable Fault and Alarm levels, both Motor Leading and
Motor Lagging Fault and Alarm functions provide a configurable delay time to
limit nuisance trips. PF Faults and PF Alarms are individually enabled and
disabled through the Motor Fault Enable, Parameter 230, and Motor Alarm
Enable, Parameter 231.
Table 53 - PF Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

248

Lead PF Ov F Lvl

[0] -1.00

249

Lead PF Ov F Dly

[0.1]-99.0

SECS

250

Lead PF Ov A Lvl

[0] -1.00

251

Lead PF Ov A Dly

[0.1]-99.0

SECS

252

Lead PF Un F Lvl

[0] -1.00

253

Lead PF Un F Dly

[0.1]-99.0

SECS

254

Lead PF Un A Lvl

[0] -1.00

255

Lead PF Un A Dly

[0.1]-99.0

256

Lag PF Ov F Lvl

[0] -1.00

257

Lag PF Ov F Dly

[0.1]-99.0

SECS

258

Lag PF Ov A Lvl

[0] -1.00

259

Lag PF Ov A Dly

[0.1]-99.0

SECS

260

Lag PF Un F Lvl

[0] -1.00

261

Lag PF Un F Dly

[0.1]-99.0

SECS

262

Lag PF Un A Lvl

[0] -1.00

263

Lag PF Un A Dly

[0.1]-99.0

SECS

As displayed on the HIM or DriveExplorer configuration tools.


126

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

SECS

Protection & Diagnostic Functions

Excessive Starts/Hour
Protection

Chapter 4

Motor Starts/Hour Fault & Alarm


Starts per Hour Fault (Code 29)
The SMC-50 can be programmed to limit the maximum number of
starter/motor starts within a sliding one-hour time window. Once the number of
starts per hour is reached as configured by the user in Starts Per Hour, Parameter
128, any additional starts will cause an Excessive Starts Fault, Fault Code 29. This
fault is enabled or disabled using the Starts/Hr bit in the Motor Fault Enable,
Parameter 230.

Starts per Hour Alarm


A Starts Per Hour Alarm is also available. This Alarm is enabled or disabled using
the Starts/Hr bit in the Motor Alarm Enable, Parameter 231. The Starts per
Hour Faults and Alarm is activated when the starts within the last hour exceed
the value configured in Starts Per Hour, Parameter 128. The starts count value is
cleared when the starts in the previous hour are less than or equal to the Starts Per
Hour parameter.
Table 54 - Starts per Hour Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

128

1-[99]

Starts Per Hour

R/W

As displayed on the HIM or DriveExplorer configuration tools.

Preventive Maintenance
(PM) Protection

PM Hours Protection Fault & Alarm


PM Hours Fault (Code 50) and Alarm
The SMC-50 can be configured to provide a Fault and/or Alarm to indicate that
PM should be performed after a programmed number of hours have elapsed,
Fault Code 50. This is done by setting a value in the Time to PM, Parameter 21,
to indicate the amount of running time before PM needs to be done.
The programmed Time to PM value counts down while the motor is starting,
stopping, operating in slow speed, and running. When the Time to PM
parameter value reaches zero, the configured Fault and/or Alarm condition is
activated and the parameter counter stops decrementing.
After the preventative maintenance is complete, the user can reset the Fault
and/or Alarm. The user must reload the Time to PM to the value configured and
stored in the PM Hours, Parameter 126, through the Meter Reset, Parameter 16,
via the HIM or network connection.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

127

Chapter 4

Protection & Diagnostic Functions

The PM Hours Fault is enabled using the PM Hours bit in the Motor Fault
Enable, Parameter 230. The PM Hours Alarm is enabled using the PM Hours bit
in the Motor Alarm Enable, Parameter 231.
Table 55 - PM Hours Protection Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

126

PM Hours

1-[10000]

R/W

HRS

21

Time to PM

[0.0-10000.00

HRS

16

Meter Reset

[Ready], Elapsed Time, Energy,


Time to PM, Starts to PM

R/W

As displayed on the HIM or DriveExplorer configuration tools.

PM Starts Protection Fault & Alarm


PM Starts Fault (Code 51) & Alarm
The SMC-50 can be configured to provide a Fault and/or Alarm to indicate that
PM should be performed after a pre-defined number of starts have occurred,
Fault Code 51. This is done by using the PM Starts, Parameter 127, Starts to PM,
Parameter 22, and Meter Reset, Parameter 16.
The Starts to PM parameter indicates the number of starts before preventative
maintenance needs to be performed. This value counts down by one for each
start initiated, even if the start is not completed. When the Starts to PM value
reaches zero, the configured Fault and/or Alarm condition is activated and the
counter stops counting.
After the preventative maintenance is complete, the user can reset the Fault
and/or Alarm. The user must reload the Starts to PM to the value configured and
stored in the PM Starts parameter through the Meter Reset, Parameter 16 via a
HIM or network communications.
The PM Starts Alarm function is enabled using the PM Starts bit in the Motor
Fault Enable, Parameter 230. The Alarm is enabled using the PM Starts bit in the
Motor Alarm Enable, Parameter 231.
Table 56 - Starts Protection Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

127

PM Starts

1-50000 [100]

R/W

22

Starts to PM

[0]-50000

16

Meter Reset

[Ready], Elapsed Time, Energy,


Time to PM, Starts to PM

R/W

As displayed on the HIM or DriveExplorer configuration tools.

128

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Line Loss Protection

Chapter 4

Line Loss Fault Phase A (Code1)


Line Loss Fault Phase B (Code 2)
Line Loss Fault Phase C (Code 3)
The SMC-50 is able to individually identify and provide a Fault and or Alarm if a
power line loss occurs on any phase.
NOTE:

Phase A, B, or C loss = Fault Code 1, 2, or 3 respectively. There are no line loss


Fault Parameters to configure.

The Line Loss Fault is enabled or disabled using the Line Loss bit in the Starter
Fault Enable, Parameter 136. In addition, a Line Loss Alarm can be enabled or
disabled using the Line Loss bit in the Starter Alarm Enable, Parameter 137.
NOTE:

If Line Loss is disabled, consider enabling the Undervoltage Fault to limit


potential motor damage caused by phase loss.

Silicon-Controlled Rectifier Shorted SCR Fault Phase A, B, or C


(SCR) Protection
Shorted SCR Fault Phase A (Code 4)
Shorted SCR Fault Phase B (Code 5)
Shorted SCR Fault Phase C (Code 6)

The SMC-50 is able to detect if any one of its SCRs are shorted in any phase. The
shorted SCR Fault is always enabled (user cannot disable). No user intervention
or parameter configuration is required and no shorted SCR Alarm exists.
NOTE:

Shorted SCR detection is performed as part of a prestart check.

SCR Overtemperature Fault


SCR Overtemperature Fault (Code 10)
The SMC-50 is able to detect if any one of its SCRs has reached an over
temperature condition, which could indicate excessive current draw or excessive
number of starts. This function is accomplished using an I2t calculation. There
are no SCR overtemperature parameters for the user to configure. The SCR
Overtemperature Fault is always enabled. There is no SCR Overtemperature
Alarm.
The SCR temperature calculation/algorithm also controls the cyclic operation of
the SMC-50s fan(s) in the power section. The SMC-50 internal fan is turned on
whenever the motor it is controlling is running or the estimated SCR

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

129

Chapter 4

Protection & Diagnostic Functions

temperature is above 50 C. The fan is turned off when the motor is not
energized and the estimated SCR temperature is below 49 C.

Open SCR Gate Fault & Alarm Phase A, B, or C


Open SCR Phase A (Code 7)
Open SCR Phase B (Code 8)
Open SCR Phase C (Code 8)
The SMC-50 is able to detect if an SCR control gate in any power phase has
malfunctioned and initiate a Fault or Alarm. There are no user-configurable
Open Gate parameters.
The Open SCR Gate Fault is enabled and disabled using the Open Gate bit in
the Starter Fault Enable, Parameter 136. The Open SCR Gate Alarm is enabled
and disabled in the Starter Alarm Enable, Parameter 137.

Power Quality

Power Quality Fault & Alarm Phase A, B, or C


Power Quality Phase A (Code 52)
Power Quality Phase B (Code 53)
Power Quality Phase C (Code 54)
A power quality Fault or Alarm will occur when the starter is not properly firing
its phase A, B, or C SCRs. This condition is generally attributed to power line
problems that are not detected by other line monitoring functions. There are no
user-configurable Power Quality Fault or Alarm parameters to configure.
Phase A, B, and C Power Quality equates to Fault Code 52, 53, or 54 respectively.
This can be enabled or disabled using the Power Quality bit in the Motor Fault
Enable, Parameter 230.
In addition, a Power Quality Alarm can be enabled or disabled using the Power
Quality bit in the Motor Alarm Enable, Parameter 231.

130

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Total Harmonic Distortion (THD) Fault & Alarm


Power Quality THDV (Fault Code 55) & Power Quality THDI (Fault Code 56)
Fault & Alarm
The SMC-50 provides the ability to read power line THD which is the average of
32 line frequency harmonics. The calculation for THDI and THDV (THDx) is:
THDx =

...+THD )
(THD + THD
THD
2
2

2
3

2
31

Excessive THD indicates a problem in the power source and/or the application.
This can have an adverse effect on the performance of the overall system. THD
Fault and Alarm parameters are available for both voltage THDV and current
THD I. A Fault and Alarm delay time and a level are also available to configure
each of these parameters.
Table 57 - THD Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

118

THD V F Lvl

0.0-[1000.0]

119

THD V F Dly

[0.1]-99.0

SECS

120

THD V A Lvl

0.0-[1000.0]

121

THD V A Dly

[0.1]-99.0

122

THD I F Lvl

0.0-[1000.0]

123

THD I F Dly

[0.1]-99.0

SECS

124

THD I A Lvl

0.0-[1000.0]

125

THD I A Dly

[0.1]-99.0

SECS

R/W

SECS
%

As displayed on the HIM or DriveExplorer configuration tools.

Power Pole Overtemperature Fault


PTC Power Pole Overtemperature Fault (Code 60)
A built-in PTC is used to measure the SMC-50s power pole temperature. The
SMC-50 will generate a Power Pole PTC Fault, Fault Code 60, when the
temperature in the power pole rises above the PTC trip temperature.
NOTE:

There are no user-configurable Power Pole Overtemperature Fault parameter


and it cannot be disabled. The Fault cannot be reset until the unit cools.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

131

Chapter 4

Protection & Diagnostic Functions

Open Load Fault & Alarm


No Load Motor Fault (Code 14)
Open Motor Phase A Loss Fault (Code 15)
Open Motor Phase B Loss Fault (Code 16)
Open Motor Phase C Loss Fault (Code 17)
The SMC-50 can detect and report a No Load Motor Fault (no motor detected),
Fault Code 14, condition and Open Motor Phase Loss Fault condition for each
individual motor phase A, B, or C, Fault Code 15, 16, & 17. A check for No
Load and Open Motor Phase is done as an SMC-50 pre-start activity and is
checked immediately after the motor start command and before the first SCR
gating pulse. There are no user configurable parameters associated with this Fault.
The No Load and Open Motor Phase Loss Fault can be enabled or disabled using
the Open Load bit in the Motor Fault Enable, Parameter 230.
In addition to the Open Load Fault, an Open Load Alarm can be enabled or
disabled using the Open Load bit in the Motor Alarm Enable, Parameter 231.

Current Transformers (CT) Loss Fault


CT Loss Phase A Fault (Code 30)
CT Loss Phase B Fault (Code 31)
CT Loss Phase C Fault (Code 32)
The CT Loss Fault is provided on a per phase basis (phase A, B, & C; Fault Code
30, 31, & 32) and occurs when the current feedback signal from one of the
SMC-50s internal CTs is invalid. Indication of an invalid CT feedback signal is
when the SMC-50 remains at the minimum negative current or maximum
positive current for its current range. This Fault cannot be disabled and no
parameters need to be configured.

Locked Rotor Fault & Alarm


Locked Rotor Fault (Code 70)
The Locked Rotor Fault, Fault Code 70, provides indication that the rotor of the
motor under SMC-50 control and operating in any running mode (e.g., Slow
Speed) has become frozen or locked.
NOTE:

132

The Locked Rotor Fault is similar to the Jam Fault except it is active during
all running modes, not just at full speed.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

The value or level of the Locked Rotor Fault is configured as a percentage of the
motor FLC using Locked Rotor F Lvl, Parameter 84. A configurable delay time
using Locked Rtr F Dly, Parameter 85, is also available to help eliminate nuisance
Faults.
Locked Rotor protection is enabled or disabled via the Locked Rotor bit in the
Motor Fault Enable, Parameter 230.
In addition to the Locked Rotor Fault, a Locked Rotor Alarm can also be
enabled, which will activate under the same condition as the Locked Rotor Fault.
The Locked Rotor Alarm is enabled or disabled via the Locked Rotor bit in the
Motor Alarm Enable, Parameter 231,
Table 58 - Locked Rotor Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

84

Locked Rtr F Lvl

400-1000 [600]

85

Locked Rtr F Dly

[0.1]-100.0

310

Locked Rtr A Lvl

400-1000 [600]

311

Locked Rtr A Dly

[0.1]-100.0

% FLC
R/W

SECS
% FLC
SECS

As displayed on the HIM or DriveExplorer configuration tools.

Expansion Module
Functions

Expansion Device Removed Fault


Expansion Module Removed Fault (Code x026)
When an expansion module (e.g., 150-SM) is removed from a powered down
control module and power is reapplied, Expansion Removed, Fault Code 26, is
generated. For SMC-50 expansion modules, the Fault code includes the control
module port number (7, 8, or 9) to distinguish which expansion module caused
the Fault (e.g., an expansion module located in port 8 would display the Fault
Code 8026).
For physical DPI devices that support this function, the Fault will be generated
only when the associated bit is set in the Logic Mask Act, Parameter 149.
IMPORTANT

Ensure all line and control power is removed from the SMC-50 before
removing or installing any expansion or communication module.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

133

Chapter 4

Protection & Diagnostic Functions

Expansion Device Fault


Expansion Module Fault (Code x028)
This fault code is generated directly by any option module or DPI device and is
separate from the Expansion Device Removed fault (control module generated).
This fault is always enabled (user cannot disable) in the control module.
Individual option modules or DPI devices may enable or disable these faults as
needed.
NOTE:

Not all devices use this fault.

Expansion Module Incompatible Fault


Incompatible Expansion Module Fault (Code x027)
If an expansion module (e.g., 150-SM) is plugged into an incompatible
expansion port or the expansion module is not supported by the control module
firmware revision (FRN), an Expansion Incompatible, Fault Code 27, will be
generated. The SMC-50 port number (7, 8, or 9) of the expansion module
generating the Fault is also displayed (e.g., an expansion module located in port 7
would display the Fault Code 7027). This fault cannot be disabled.

Real Time Clock (RTC)

Battery Low
RTC Battery Low Fault (Code 69)
An RTC Battery Low, Fault Code 69, provides indication of a control module
battery low condition. This condition is checked upon power up of the control
module. The battery maintains the operation of the control modules RTC when
the control power is removed. Once the Alarm is posted, the battery should be
replaced as soon as possible. This alarm cannot be disabled.
To clear this alarm, the battery must be replaced and the time/date set with a
HIM or applicable PC software (e.g., DriveExplorer).

Configuration Functions

Configuration Change Fault & Alarm


Configuration Change Fault (Code 57)
By setting the Configuration Change bit in the Starter Fault Enable, Parameter
136, any change to the controller configuration will result in a Configuration
Change Fault, Fault Code 57. An Alarm can also be initiated by setting the

134

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

"Config Change" bit in the Starter Alarm Enable, Parameter 137. The Fault can
be cleared immediately and the Alarm will clear upon the next motor start
command.

I/O Configuration Fault


I/O Configuration Fault (Code 61)
The SMC-50 will generate an I/O Configuration Fault, Fault Code 61, if any
control input is programmed as a Start or Slow Speed command and no input is
configured for Coast or Stop. The Fault occurs when the Start or operational
maneuver is attempted (the motor will not start). This Fault is also generated
when an input configuration changes from:
1. one that cannot start the motor to one that can start the motor OR
2. an input that can stop the motor to one that cannot.
This Fault is always enabled; no parameter adjustments are required and no alarm
is available.

Buffers & Storage


Functions

Non-volatile Storage (NVS) Fault


NVS Fault (Code 34)
The NVS Error Fault, Fault Code 34, is posted if a read/write checksum error
occurs within the user data portion of the SMC-50s non-volatile memory. This
Fault can only be cleared by the user modifying/storing a parameter value
(requires changing any parameter). It is recommended that the user perform a
Load Defaults command to make sure that all controller parameters are within
range. This error cannot be cleared by cycling the SMC-50 controller power.

Fault Buffer & Fault Storage Parameters


The Fault Buffer is used to store the last five system Faults. The Fault Buffer is
accessed via the Diagnostic screen of a 20-HIM-A6, 20-HIM-C6S, or from the
Device Properties screen, which is accessed using the DriveExplorers
Explore>Device Properties pull-down menu. The most recent Fault is located at
the top of the buffer (number 1 for the HIM or number 1.1 for the software
configuration tool. The Fault Buffer also stores the date and time that the Fault
occurred.
NOTE:

The date and time information is obtained from the SMC-50s RTC. Ensure the
RTC is set correctly.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

135

Chapter 4

Protection & Diagnostic Functions

The five most recent Faults are stored in Parameter 138 through Parameter 142.
This stored Fault history in the parameter list can be accessed by any networked
device. The Fault date and time are not available from the parameters list.
Table 59 - Fault Buffer & Fault Storage Parameter List
Parameter Number Parameter Name
138

Fault 1

139

Fault 2

140

Fault 3

141

Fault 4

142

Fault 5

Fault Code

Access Units

0-10000

As displayed on the HIM or DriveExplorer configuration tools.

Alarm/Event Buffer & Alarm/Event Storage Parameters


In addition to storing (buffering) Alarm Data, the Alarm Buffer is used to store
several key controller events. The type of events stored includes:
Event

Alarm Code

Start

71

Slow Speed

72

Stop Option

73

Coast

74

Clear Fault

75 a Fault has been cleared

Fault

76

Parameter Change 77 change to any Parameter occurred

The Alarm Buffer can be accessed via the Diagnostic screen of a 20-HIM-A6,
20-HIM-C6S, or from the Device Fault/Alarm button of Connected
Components Workbench. The last 100 events are stored in the Alarm Buffer
with the most recent event numbered as 1 (HIM) or 1.1 (software) in the list.
Along with the Alarm Code, the date and time that the event occurred is also
listed.
NOTE:

The date and time information is obtained from the SMC-50s RTC. Ensure the
RTC is set correctly.

In addition to the Alarm Buffer, the last five Alarm Events are available via
Parameter 143 through Parameter 147. Storing this Alarm history in the
parameter list provides access by any networked device. The Alarm/Event date
and time are not available from the parameter list.

136

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Protection & Diagnostic Functions

Chapter 4

Table 60 - Alarm/Event Parameter List


Parameter Number Parameter Name
143

Alarm 1

144

Alarm 2

145

Alarm 3

146

Alarm 4

147

Alarm 5

Alarm Code Access Units

0-10000

As displayed on the HIM or DriveExplorer configuration tools.

Auto Restart from Fault


Function

This function allows the SMC-50 to automatically restart from various Starter or
Motor Fault conditions. Auto Restart from Fault is individually bit enabled or
disabled using Starter Restart Enable, Parameter 135, or Motor Restart Enable,
Parameter 264. See Table 61 on page 138.
Parameter 133, Restart Attempts, allows the user to define the allowable number
of restart attempts from the fault before ending the retry process. The Retry
Counter is cleared whenever the controller receives a valid Stop command.
In addition, Restart Delay Time, Parameter 134, allows the user to define a time
delay from when the Fault event occurred until a Restart Attempt can be
effective.
NOTE:

This delay is not used with an Overload Fault. Instead, the restart attempt will
occur when the Mtr Therm Usage, Parameter 18, falls below the OL Reset
Level, Parameter 80.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

137

Chapter 4

Protection & Diagnostic Functions

Table 61 - Auto Restart from Fault Parameter List


Parameter
Number

Parameter
Name

135

Strtr Restart En

264

Fault Name

Bit
Bit
Assignment Access Units

Volt Umbal
Overvoltage
Undervoltage
Phase Rev
Line Loss
Open Gate
Config Change
Freq
THD V

0
1
2
3
7
5
6
7
8

Motor Restart En Overload


Underload
MWatts Over
MWatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Under
MVA Over
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
Power Qual
Open Load
THD I
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor

0
1
2
3
7
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22.
23

Bit = 0, Disabled
Bit = 1, Enabled

R/W

[All Disabled as
Default]

Bit = 0, Disabled
Bit = 1, Enabled
[All Disabled as
Default]

R/W

As displayed on the HIM or DriveExplorer configuration tools.


Table 62 - Auto Restart Parameter List
Parameter Number Parameter
Name

Minimum/Maximum [Default] Access Units

133

Restart Attempts

[0] -5

134

Restart Dly

[0]-60

As displayed on the HIM or DriveExplorer configuration tools.

138

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

SECS

Chapter

Programming

Overview

This chapter provides a basic understanding of the programming/configuration


tools available to modify the SMC-50s parameters. Unlike previous SMC
products (e.g., SMC-3 and SMC Flex), the SMC -50 comes without a built-in
programming tool. This allows the user to select from several programming tools
to best suit their application.

Parameter Configuration
Module (PCM)

Using the PCM (150-SM6)


The Cat. No. 150-SM6 PCM provides simple and limited configuration of the
SMC-50. This PCM can be inserted into any control module option port (7, 8,
or 9). Only one PCM is allowed per control module.
Parameters that are configured by the PCM will appear as read-write parameters
to other configuration devices and whose values represent the switch settings.
The parameter values set by the PCM are stored in the control module memory.
Therefore, using the appropriate removal procedure (remove all power to
Control Module and Power Module), the PCM can be removed from the control
module with its parameter settings retained.
Parameters that are not defined and therefore are not configurable by the Cat.
No. 150-SM6 PCM can be configured through other means (e.g., Human
Interface Module (HIM), Connected Components Workbench, or
DriveExecutive software), if necessary.
Application considerations for the 150-SM6 PCM are listed below.
If another configuration tool attempts to configure a parameter setup by
an installed 150-SM6, that parameter will revert back to the 150-SM6
configuration. The PCM overrides other configuration tools.
The 150-SM6 can only configure the onboard control I/O of the Control
Module. If additional I/O are added by using a 150-SM4 Digital I/O
Option Module, those I/O must be configured by another programming
tool.
When using a Cat. No. 150-SM6 PCM to configure the SMC-50, it should be
noted that the following features, functions, and modes are not configurable:
Full voltage start
Torque ramp start
External brake stop

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

139

Chapter 5

Programming

Option card I/O configuration (Cat. No. 150-SM option modules)


External bypass
Specialized output relay configuration (e.g., network control,
DeviceLogix, auxiliary control)
Specialized operation modes/features
Dual ramp, motor winding heater, emergency run
Overload select (Class)
Adjustment of slow speed set point
If the PCM is removed, another configuration tool (e.g., a HIM) can change a parameter
that was previously altered by an installed PCM.

NOTE:

Figure 80 - DIP Switch & Rotary Switch Locations


S1

45
23

89
67 A

I/O

45
23

5
6

DEVICE

DEVICE

89
67 A

F01

2
7
8

45
23

F01

89
67 A

OPEN

OPEN

S4

BCDE

89
67 A

PROTECTION

F01

MFG DATE
yy/mm/dd

PROTECTION

S3

BCDE

S5

BCDE

45
23

BCDE
F01

S1 Initial Torque
S2 Current Limit
S3 Ramp Time
S4 Stop Time
S5 Motor FLC

MFC LOC
FACxx

I/O

S2

OPEN

SER.

CAT.

150-SM6

SMC-50 PARAMETER CONFIGURATION

Diagnostic
LEDs

F01

89
67 A

BCDE

45
23

DIP Switch

Rotary Switch

The 150-SM6 PCM contains five rotary switches, S1 through S5, each with
designations 0-F and three banks of ON/OFF 8-switch DIP switches.
The following tables show the resulting values of the position setting functions
for each of the five rotary switches and the associated controller parameter
numbers. For details on the functions of these parameters, see Chapter 3, 4, 6,
and Appendix B.
Table 63 - S1 = Initial Torque Configuration Controller Parameter 51

140

Resulting Initial Torque


Position Setting Value (% motor torque)

Resulting Initial Torque


Position Setting Value (% motor torque)

10

58

16

64

22

70 (default)

28

76

34

82

40

88

46

94

52

100

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Table 64 - S2 = Current Limit Level Configuration Controller Parameter 53


Resulting Current Limit
Position Setting Value (% (FLC)

Resulting Current Limit


Position Setting Value (% FLC)

200

360 (default)

220

380

240

400

260

420

280

440

300

460

320

480

340

500

Table 65 - S3 = Ramp Time Configuration Starting Controller Parameter 50


Starting Ramp Time
Position Setting (seconds)

Starting Ramp Time


Position Setting (seconds)

0.1

16

18

20

22

24

10 (default)

26

12

28

14

30

Table 66 - S4 = Stop Time Configuration Controller Parameter 66


Position Setting Stop Time (seconds)

Position Setting Stop Time (seconds)

Coast -to-Stop (default)

16

18

20

22

24

10

26

12

28

14

30

When the braking STOP MODE is selected (device configuration bank switch #3 and #4), the controller
multiplies the selected stop time by ten.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

141

Chapter 5

Programming

Table 67 - S5 = Motor FLC Configuration Controller Parameter 78


FLC
Position Setting (% of controllers max)

FLC
Position Setting (% of controllers max)

40 (default))

72

44

76

48

80

52

84

56

88

60

92

64

96

68

100

Since a set of switches do not provide the resolution to enter all possible FLC combinations like a keypad,
switch S5 allows you to configure the motors FLC in the SMC-50 by using a percent (%) of the controllers rated
FLC (e.g., 90 A, 110 A, 180 A, etc.).
EXAMPLE
For a 60 A motor and a 90 A controller:
% of controllers max FLC for a 60 A motor = 64% of 90 A (57.6 A), or Switch Position 6

To determine the S5 switch setting for an inside-the-delta motor configuration, use the following equations:
Step 2

Step 1

X
x 100 = S5 Switch Setting
SMC-50 Controller Rating

Motor Nameplate FLC


=X
1.73
EXAMPLE
Step 1

Step 2
100 A
1.73

= 57.8 A

57.8 A
90 A

x 100 = 64%

Result From the result of 64%, the S5 switch setting is position 6.

1 If the calculated value does not match a switch position, use the previous
(lower percent) switch setting.

NOTE:

2 The inside-the-delta motor configuration can be selected using Motor


Connection, Parameter 44, or automatically during a controller tuning process.
The tuning process is done during the initial system start after changing any of
the tuning parameters and initializing a start or by pressing and holding the
SMC-50 reset push button for at least 10 seconds with the motor stopped and
then initializing a start. If another configuration device is available (e.g., a
20-HIM-A6 or PC software such as DriveExplorer), changing Force Tuning,
Parameter 194, to TRUE or resetting the controller to "Default" will also result in
tuning to occur.

The following tables define the functions for the three banks of ON/OFF
8-switch DIP switches. Each of the three banks is defined by a high level,
functional name with each switch having a unique function.

142

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Table 68 - ON/OFF 8-Switch DIP Switch Definitions Device


DEVICE Configuration Bank
(O = Switch OPEN)
Starting Mode
Controller
Parameter 49

Stop Mode
Controller
Parameter 65

Switch Number
#1 #2 #3 #4 #5 #6 #7 #8

Linear Speed Acceleration (default) 0

Current Limit

Soft Start

Pump Start

Linear Speed Deceleration (default)

Soft Stop

Braking

Pump Stop

Energy Saver
Controller
Parameter 193

Enable

Disable (default)

Braking Current
Controller
Parameter 69

50%

100%

150%

200% (default)

250%

300%

350%

400%

When the "Stop Mode" is configured as (a) "Linear Speed Decel", (b) " Soft Stop", (c) "Pump Stop", and the

"Stop Time" (rotary switch S4) is set to zero, a "Coast" stop will result. A non-zero "Stop Time" value for the three
previously listed "Stop Modes" defines the time to stop period which is based on that specific configuration.
If the "Stop Mode" is configured as "Braking", then the "Stop Time" setting (Rotary Switch S4) is used to select
either the "Automatic Zero Speed Detection" method ("Stop Time" is set to zero) or the "Timed Brake" method
("Stop Time" is not set to zero).
With the Energy Saver switch (#5) set to Enable, the Energy Saver Level, Parameter 193, is automatically
configured by the PCM to 0.25.

NOTE: 1 With the "Automatic Zero Speed Detection" method, the controller applies the

user-selected "Braking Current" defined by the Device Configuration Switch Bank. Switch #6,
#7, and #8 senses a motor "Zero Speed" condition and automatically stops the braking
process (brake current OFF).

2 With the "Timed Brake" method, the user-selected "Braking Current" is applied for the
user-configured "Stop Time" regardless of the motor speed (e.g., "Automatic Zero Speed
Detection" disabled). The "Timed Brake" method can be used in applications where detecting
zero speed is ineffective or when braking the motor to a complete stop results in random
overload trips. With this method, braking is applied for a fixed time equal to the "Stop Time"
setting (Rotary Switch S4) and multiplied by ten. An ideal "Stop Time" setting can be
accomplished by trial and error, but should always allow for some coast time. Setting the
"Stop Time" for too long of a time period can result in braking current to be applied to a
stopped motor and will likely result in overload trips.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

143

Chapter 5

Programming

Table 69 - ON/OFF 8-Switch DIP Switch Definitions Protection


Switch Number

PROTECTION Configuration Bank


(O = Switch OPEN)
Preset Protection Level
Parameter

#1 #2 #3 #4 #5 #6 #7 #8
Enabled (default)

Disabled

Stall Fault Parameter 230 Enabled (default)


Disable
Phase Reversal Fault Enable
Parameter 136
Disable (default)
OL Restart Parameter 264 Enable
Disable (default)
OL Enable Parameter 230 Enabled (default)
Disable
OL Class Parameter 75 10 (default)

1
0
1
0
1
0
1
0
0

15

20

30

The Preset Production Level DIP switch allows the following Faults to be enabled (1) or disabled (0) as a

group.
Current Imbalance Fault Parameter Number: 110 [default value: 15)
Voltage Unbalance Fault Parameter Number: 106 [default value: 15]
Line Loss Fault Parameter Number: NA [default value: no value required - see Chapter 4, Line Loss
Protection on page 129]
Open Gate Fault Parameter Number: NA [default value: no value required - see Chapter 4, Open SCR Gate
Fault & Alarm Phase A, B, or C on page 130]
No/Open Load Fault Parameter Number: NA [default value: no value required - see Chapter 4, Open Load
Fault & Alarm on page 132]

The PCM configuration setting for each of these Faults follows the currently entered/loaded
parameter value for each Fault. This will typically be the default setting unless a 20-HIM-A6 or other
configuration tool (e.g., PC software or network device) is used to change a parameter setting. The
switch setting also overrides the Motor Fault Enable, Parameter 230, and Starter Fault Enable,
Parameter 136, function to enable or disable these Faults.
Note that with the Preset Protection Level switch set to Disable, all Starter and Motor Faults are
disabled (as defaults except the Power Quality Fault).

144

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Table 70 - ON/OFF 8-Switch DIP Switch Definitions Configuration


Switch Number

I/O Configuration Bank


(O = Switch OPEN)

#1 #2 #3 #4 #5 #6 #7 #8

Aux #1 Configuration Normal (default)


Parameter 172
Up-to-Speed (UTS)

Fault

Alarm

Aux #2 Configuration Normal


Parameter 176
UTS [default]

Fault

Alarm

Input #1 Parameter 56 Start/Coast (default)


Start/Stop Option

0
1

Input #2 Parameter 57 Stop Option (default)

Clear Fault

Slow Speed

Fault

The I/O Configuration ability of the 150-SM6 is limited to the Control Modules standard I/O.

Human Interface Module


(HIM) (Cat. No. 20-HIM-A6
or 20-HIM-C6S)

The 20-HIM-A6 provides the ability to:


configure/monitor all controller parameters,
configure/monitor all option modules (e.g., 150-SM4, digital I/O,
150-SM6 PCM, etc.), and
use the SMC-50s general startup configuration wizard.
NOTE: The 20-HIM-A3 cannot configure the option modules or use the general startup configuration
wizard. Therefore, the 20-HIM-A3 is not recommended for use with the SMC-50 and is not
mentioned in this document.

The 20-HIM-A6 is typically inserted into the HIM bezel port located on the
upper right of the control module. Inserting the HIM into the bezel provides
operation in a NEMA Type 1 environment. The 20-HIM-C6S, a remote
(door-mount) version of the 20-HIM-A6, provides operation in a NEMA 4X/12
environment and includes a 1202-C30 interface cable to the SMC-50 DPI Port 2
on the top of the controller. For additional information on mounting the
20-HIM-A6 or the 20-HIM-C6S, see the HIM User Manual, publication
20HIM-UM001.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

145

Chapter 5

Programming

Figure 81 - HIM Mounting Locations


SMC-50 Front View
HIM Bezel Port

SMC-50 Top View

DPI Port 2
(Port 2 & 3 with Splitter)

The following information describes some of the basic screens and keypad
functions of the 20-HIM-A6 or 20-HIM-C6S. Additional details concerning all
HIM functions can be found in the User Manual, publication 20HIM-UM001.

146

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

HIM Single-Function Keys


The four single-function keys only perform their dedicated functions no matter
which screen or data entry mode is being used.
Table 71 - HIM Single-Function Keys

Start

Folders

Controls

Stop

Key

Function

Start

Starts the controller if the SMC-50 Logic Mask is enabled for the port the HIM is
connected to.

Folders

Accesses folders for parameters, diagnostics, memory functions, preferences, and


other tests.

Controls

Accesses jog, direction, auto/manual, and other control functions.

Stop

Stops the SMC-50 or clears a fault. The Stop key is always active.

If the device (port) is enabled and removed under power or an expansion device is removed, a fault is
generated. The bit location (e.g., 0, 1, 2, etc.) corresponds to the DPI port numbers.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

147

Chapter 5

Programming

HIM Soft Keys


Up to five dynamic soft keys can be shown at the bottom of the HIM screen.
Based on the specific screen or the data entry mode being used, a soft key name
and its function may change. When a soft key is active, its presentation function
and corresponding soft key label are shown at the bottom of the HIM screen.
Table 72 - HIM Soft Key Functions
Soft Key

Description

Multi-Function Blue

Scrolls through menus and


screens as directed by each
arrow
Performs corresponding
functions displayed in the data
area

Enters their respective numeric


values

8
7

Function

Numeric Keys Grey


3

1
2
0

5/Enter

Enters the numeric value, 5


Displays the next level of a
selected menu item
Enters new values
Performs intended actions

Password Modification Using the HIM


The SMC-50 provides password protection by numeric code (0 to 65,535) to
prevent unwanted modification of parameters. Data and parameter values can be
viewed/monitored without entering the password, but modification requires
password entry.
The password can be modified from the PROPERTIES folder screen of the
20-HIM-A6 or 20-HIM-C6S, as shown in Figure 82 on page 149.

148

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Figure 82 - PROPERTIES Folder Screen


Allen-Bradley
AUTO
F

Stopped
0 Amps

PROPERTIES
PROPERTIES
00

ESC

NOTE:

Change Password
Select Language
Set Proc Display
Set Date and Time

If the default password (0=default) is modified, ensure the modified password is


written down in a secure place. There is no way to reset the password if it is forgotten.
For additional information on password modification, see the 20-HIM-A6 User Manual,
publication 20HIM-UM001.

To modify the default password, perform the following steps using the
20-HIM-A6 or 20-HIM-C6S:
1. From the initial power-up screen, press the FOLDERS single function key.
2. Use the forward or back arrow key until the PROPERTIES folder screen is
displayed, as shown in Figure 82.
3. Select the CHANGE PASSWORD option, then press the Enter (#5) key.
4. Enter a numeric password, then press the Enter (#5) key. This will load the
password into the SMC-50s memory.

Parameter Access Level Modification Using the HIM


The SMC-50 provides three different parameter access levels: Monitor, Basic,
and Advanced. These access levels provide the ability to limit user access and/or
speed viewing or changing of certain parameters.

NOTE:

The access level is not maintained if power to the controller is cycled.


The default access level is Basic.
The advanced level provides access to all parameters.
Individual parameter access levels are shown in Figure 87 through
Figure 91 beginning on page 174 and is also contained in the Parameter
Linear List, Table 73 through Table 77 beginning on page 177.

To view/modify the current access level, perform the following steps using the
20-HIM-A6:
1. From the initial power-up screen, press the FOLDERS single function key.
2. Use the forward or back arrow key until the DEV PARAM folder screen is
displayed.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

149

Chapter 5

Programming

3. Select the PARAM ACCESS LEVEL option, then press the Enter (#5)
key. The Dev Parameter screen appears.

Allen-Bradley
AUTO
F

Stopped
0 Amps

DEV PARAM
00

ESC

Linear List
File-Group
Changed Parameters
Param Access Level

4. Use the up or down arrow to scroll up or down to until the desired access
level is reached, then press Enter (#5) to view that access level.

Parameter Management

Before you begin programming, it is important to understand how the memory is


structured within the SMC-50 and used on power-up and during normal
operation.
Figure 83 - Memory Block Diagram

SMC-50 Memory

150

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

RAM (Random Access Memory)


RAM is the work area of the controller after it is powered up. The SMC-50 uses
an Auto Store feature when programming parameters. When parameters are
modified in the program mode, the new values are stored immediately in RAM
and then in EEPROM (Electrically Erasable Programmable Read-Only Memory), once
the enter key has been pressed. If control power is lost prior to the enter key being
pressed, these values will be lost. When the device first powers up, the values from
the EEPROM area of memory are copied into RAM.

ROM (Read-only Memory) Set Defaults


Allen-Bradley
AUTO
F

Stopped
0 Amps

MEMORY
00

HIM CopyCat
Set Defaults

ESC

The SMC-50 comes with factory default parameter values. These settings are
stored in non-volatile ROM and are displayed the first time you enter the
Program mode via the Linear List or File-Group mode using the HIM. To restore
factory parameter defaults:
1. Navigate to the Memory folders screen with Port <00> displayed.
NOTE:

Option modules can also be restored to defaults using this method. Ensure its
respective port number is displayed.

2. Select/highlight the Set Defaults line, then press ENTER (#5). The
following text will be displayed: WARNING: Sets all Parameters to
factory defaults. Continue?
3. Press the ENTER soft key to change defaults or the ESC soft key to return
to the previous screen.
NOTE:

Factory defaults can also be restored using the Parameter Management, Parameter
229, available in the Utility File-Group (see Figure 91 on page 176).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

151

Chapter 5

Programming

EEPROM
The SMC-50 provides a non-volatile area for storing user-modified parameter
values in the EEPROM.

Parameter Configuration

Using the START UP Configuration Tool (20-HIM-A6 or


20-HIM-C6S)
The general START UP configuration tool provides the ability to rapidly
configure an SMC-50. Enabled by the SMC-50 and the 20-HIM-A6 or
20-HIM-C6S, a series of questions required to configure starting (e.g., Soft,
Linear, Pump, etc.) and stopping (e.g., Coast, Pump, etc.) modes are displayed on
the HIM via this tool.
Not all parameters are configured with this tool. Non-configured START-UP
parameters can be configured using the parameter number or File Group
search method. See the Basic Configuration using the HIM on page 182.

Accessing the General START UP Tool


1. Select the FOLDERS single-function key located on the lower left portion
of the keypad.
2. Use the left or right arrow key until the START UP folders screen is
displayed.
Allen-Bradley
AUTO
F

Stopped
0 Amps

START UP
Begin Start Up

00

ESC

3. Press the ENTER (#5) key to begin the configuration process. The HIM
will display "Run General Start-up?".

152

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

4. Press the Yes soft key to begin the process or Abort soft key to return to the
START UP folders screen.
Allen-Bradley
SMC-50
Run General Start-Up?

Abort

Yes

The HIM will display a series of questions pertaining to the Motor, Start,
and Stop processes.
Depending on the answers to the Start and Stop processes, some screens may not be
displayed.
EXAMPLE
If: Soft Start, Linear Speed, or Pump Start is selected:
Then: Starting Torque, Max Torque, Rated Torque, and Rated Speed will not be
displayed.
Reason: These parameters are specific to the Torque Start parameter group.
See Figure 84 on page 155 which shows the flow of the General Start-up, and the
parameters used with the Starting and Stopping modes.

NOTE:

Entering Data into General Startup


1. Display the parameter.
If the HIM provides the allowable range (e.g., 1.0 << 2200.0) at the
bottom of the screen, enter the data value. If an up or down arrow soft key
is displayed, use the soft key to display the desired selection.
If this screen appears, enter the data value.

If this screen appears, use the or soft


keys to display the desired selection.

Allen-Bradley

Allen-Bradley

SMC-50
General Start-Up
Edit Ramp Time

SMC-50
General Start-Up
Edit Stop Mode

Soft Stop 1

Secs

0<<5

0.0 < < 1000.0

ESC

Enter

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

ESC

Enter

153

Chapter 5

Programming

2. Enter the desired value, then press the ENTER soft key.
TIP

If an incorrect value was entered: Press the ESC soft key to return to the
previous screen, then enter the desired value. Use the left arrow soft key to
delete a single digit at a time from the data field to enter the correct digit. If
a group of selections is displayed, the left arrow soft key moves to the
lowest numbered selection.

Once all parameters are entered, the START-UP folders screen will appear.

Review/Modify Parameter Data


1. Display the START UP folder screen.
2. Press the ENTER (#5) key.
3. Select the "Yes" soft key when "Run General Start-Up?" is displayed.
4. Individually review each parameter (required), pressing the ENTER soft
key to move onto the next parameter. If necessary, press the ESC soft key
to review the previous parameter.
NOTE:

154

To modify parameter data, use the procedure outlined in Entering Data into General
Startup above.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Figure 84 - Flow Chart General Start-Up Parameters


Line Voltage

Starting Mode

No

Input 1 OR Input 2
Motor Heater
Yes

Current Limit

Soft Start

Linear Speed

Torque

Pump

Ramp Time

Ramp Time

Ramp Time

Ramp Time

Ramp Time

Heating Time

Cur. Limit
Level

Cur. Limit
Level

Cur. Limit
Level

Cur. Limit
Level

Initial Torque

Heating Level

Initial Torque

Initial Torque

Full Voltage

Starting Torque
No

Input 1 OR Input 2
Dual Ramp
Max. Torque

Yes

Rated Torque

Starting
Mode 2
(repeat of
Starting Mode
selections)

Rated Speed

Stop Mode

Soft Stop
Stop Time

Linear Speed
Stop Time

Pump Stop
Stop Time

Aux 1 Config

Ext Brake

SMB

Stop Time

Braking
Current

Coast

Aux 2 Config

Done

Motor FLC
Overload Class
Input 1
Input 2

No

Input 1 OR Input 2
Slow Speed
Yes
Slow Speed

No

Input 1 OR Input 2
OL Select
Yes
OL Class 2

Parameter Search & Configuration


The 20-HIM-A6 or 20-HIM-C6S can access all of the SMC-50 parameters. It
provides two basic ways to search for and modify a specific parameter or group of
parameters by: (1) parameter number or (2) File-Group. The following example
explains how to search by parameter number using the 20-HIM-A6.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

155

Chapter 5

Programming

Parameter Search & Configuration by Parameter Number


To perform a parameter number search and modification, perform the following
steps.
EXAMPLE

Parameter Search & Configuration by Parameter Number

1. Ensure the initial SMC-50 Power Up screen appears on the HIM as shown
below.
Allen-Bradley
AUTO
F

Stopped
0 Amps

SMC-50
Standard
00 Rev 1. 001 Ser. A

ESC

REF

PAR#

TEXT

2. Using the PAR# soft key, type the desired parameter number to display,
press the ENTER soft key, then press the EDIT soft key. The following
screen appears.
Allen-Bradley
AUTO

Stopped
0 Amps

SMC-50
PROPERTIES
Jump to Param #

00

ESC

NOTE:

1
ENTER

To access the next/previous PAR# from the one currently displayed, use the UP/DOWN
arrow soft keys to display the desired parameter for modification.

3. Press ENTER to load the changed value into memory.


NOTE:

For a complete SMC-50 linear list, see Table 73 through Table 77 beginning on
page 177.

For additional details on these procedures, see the 20-HIM-A6 or 20-HIM-C6S


User Manual, publication 20HIM-UM001.

156

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Parameter Search & Configuration by FileGroup Structure


Parameter Structure
The parameters of the SMC-50 are structured into five parameter File-Groups:
1. Monitoring
2. Setup
3. Motor Protection
4. Communications
5. Utility
The parameters associated with each of these five File Groups are shown in
Figure 87 through Figure 91 beginning on page 174 of this chapter.

Parameter Search & Configuration by File-Group (SMC-50 Category Search)


EXAMPLE

1. From the HIM Power-Up screen, press the FOLDERS single-function key.
2. Press the LEFT or RIGHT arrow key until the screen displays DEV
PARAM. Ensure Port 00 SMC-50 is selected from the PORTS screen.

Allen-Bradley
Stopped
0 Amps

AUTO
F

DEV PARAM
00

ESC

Linear List
File-Group
Changed Parameters
Param Access Level

3. Using the DOWN arrow key, scroll to the File-Group selection, then press
ENTER (#5 keypad). The screen will display Port 00 Param File-Group at
the top of the screen.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

157

Chapter 5

Programming

4. Using the DOWN arrow key, scroll to the Set Up selection, then press
ENTER. The screen will display the Set Up categories (e.g., Basic,
Starting, etc.).
Allen-Bradley
Stopped
0 Amps

Port 00
FILE
FILE
FILE
FILE
FILE

AUTO
F

Param File-Group

MonitoringPROPERTIES
Set Up
Motor Protection
Communications
Utility

ESC

5. With Basic highlighted, press ENTER (number 5 on the keypad).


6. Scroll to the desired parameter (e.g., Line Voltage) to modify it, then press
ENTER (number 5 on the keypad).
7. With the parameter displayed, press the EDIT soft key.
8. Enter the desired value, then press the ENTER soft key to save the value.
9. Press the ESC key to return to the Basic category.
10. To modify another parameter in the Basic category, follow step 5 though 7
above. To back out to a higher level category, press the BACK arrow key.
NOTE:

158

Using the DEV PARAM folder screen and the File-Group selection, SMC-50 parameters
can be selected and configured by functional category. See the SMC-50 Category/File
Structure parameters, Figure 87 through Figure 91 beginning on page 174.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Parameter Configuration - Overview


Using the Setup File Group

The following figure shows the parameter sets available within the Basic Setup
group.
Figure 85 - Setup File Group

Setup
Starting (BA)
Starting Mode
Ramp Time
Cur Limit Level
Initial Torque
Starting Torque
Max Torque
Kickstart Time
Kickstart Level
Heating Time
Heating Level
Start Delay

Basic (BA)
Motor Config
Line Voltage
Starting Mode
Ramp Time
Initial Torque
Max Torque
Cur Limit Level
Stop Mode
Stop Time
Input 1
Input 2
Aux1 Config
Aux2 Config
Overload Class
Service Factor
Motor FLC
Starting Torque
Max. Torque
Rated Torque
Rated Speed

NOTE:

Stopping (BA)
Stop Mode
Stop Time
Braking Current
Backspin Timer
Slow Speed
Slow Speed (BA)
Slow Brake Cur (BA)
SS Ref Gain (A)
SS Trans Gain (A)
Dual Ramp (BA)
Starting Mode 2
Ramp Time 2
Cur Limit Level 2
Initial Torque 2
Starting Torque 2
Max Torque 2
Kickstart Time 2
Kickstart Level 2

Advanced
Pump Pedestal (A)
Load Type (A)
High Eff Brake (A)
UTS Level (A)
Stall Position (A)
Stall Level (A)
V Shut Off Level (A)
I Shut Off Level (A)
Notch Maximum (A)
Timed Start (A)
Bypass Delay (A)
Energy Saver (BA)
Demand Period (BA)
Num of Periods (BA)

I/O (BA)
Input 1
Input 2
Aux 1 Config
Aux 1 Invert
Aux 1 On Delay
Aux 1 Off Delay
Aux 2 Config
Aux 2 Invert
Aux 2 Invert
Aux 2 On Delay
Aux 2 Off Delay
Aux Control

Advanced Tuning
Force Tuning (A)
Starter R (MBA)
Total R (MBA)
Coupling Factor (MBA)
Inductance (MBA)
Speed PGain (A)
Transient Gain (A)
Transient Zero (A)
Transient Mag (A)
Ping Degree (A)
Pings (A)
Phase Shift 0% (A)
Phase Shift 10% (A)
Phase Shift 20% (A)
Phase Shift 30% (A)
Phase Shift 40% (A)
Phase Shift 50% (A)
Phase Shift 60% (A)
Phase Shift 70% (A)
Phase Shift 80% (A)
Phase Shift 90% (A)
Phase Shift 100% (A)

For a complete parameter set listing within each parameter File Group, see
Figure 87 through Figure 91 beginning on page 174.

The Basic parameter set in the Setup group is limited, yet powerful. It allows for
quick system startup with minimal adjustments and provides quick access to
parameters required for standard motor connection and overload protection. If
advanced controller features (e.g., Dual Ramp, Braking, etc.) will be used,
however, the parameter set associated with those features must also be utilized.
The Setup group will be used throughout this section as a baseline for system
configuration.
IMPORTANT

Parameter values that are modified while the motor is operating are not
valid until the next time the operation for that parameter occurs.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

The following figure shows the initial FILE Setup screens using the HIM.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

159

Chapter 5

Programming

Figure 86 - Initial FILE Setup Screens


Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00
FILE
FILE
FILE
FILE
FILE

Param File-Group

Monitoring
PROPERTIES
Set Up
Motor Protection
Communications
Utility

ESC

Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00
FILE

Param File-Group
Set Up

GROUP
Motor Config
Line Voltage
Starting Mode

ESC

PROPERTIES

Basic

ENTER

Soft Start & Stop


To program a Soft Start with simple Stop Mode operation, the following
parameters are provided for user adjustment. The Basic parameter set can be
accessed with the HIM from the Port <00> DEV PARAM folder under the
File-Group, File: Setup, Group: Basic Selection sequence.
Parameter

Motor Configuration Setting for the motor configuration Line Connected Wye or
Inside-the-Delta.
NOTE: In the AUTO Detect [default] selection, the controller will automatically
check the motor configuration.
Line Voltage Select the value of line voltage being used in the system. The correct
line voltage value must be entered for the voltage protection functions to work
properly.
Starting Mode This mode must be programmed for Soft Start.
Ramp Time Programs the time period that the SMC-50 will ramp the output
voltage up to full voltage and to full speed form the Initial Torque level.
Initial Torque The initial reduced output voltage (torque) level for the voltage
ramp to the motor is established and adjusted with this parameter the torque
level at which the ramp begins.
Current Limit Level Limits the current supplied to the motor throughout the Soft
Start cycle.
NOTE: Enter a value so as to limit the current but not so low as to inhibit the start
cycle.
Stop Mode Programs the desired Stop Mode.
NOTE: The mode of stopping does not need to match the starting mode (e.g., a Soft
Start can have a stop mode programmed for [Coast], Linear Stop, or SMB there
is no Current Limit Stop or Torque Stop mode).

160

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Option [default]

Line, Delta,
[Auto Detect]

0700V [480V]
Soft Start
01000 [10] seconds
090% [70%] LRT

50...600% [350%] FLC


[Coast], Soft Stop,
Linear Speed, Pump
Stop, SMB ,
Ext Brake

Programming

Parameter

Chapter 5

Option [default]

Stop Time Programs the amount of time desired to ramp from full to zero voltage for
Soft, Linear, and Pump Stop mode. The actual ramp stop time will depend on the
stopping mode selected and load inertia.
Input 1 Programs the desired operation of the Control Module to a change in status
of Input #1 wired to control terminal #11 (24V DC). [Default: Start/Coast]
Input 2 Programs the desired operation of the Control Module to a change in status
of Input #2 wired to control terminal #10 (24V DC). [Default: Disable]
Aux 1 Config Programs the control function of the Auxiliary Output Contact #1,
wired across control terminal #4 and #5.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Aux 2 Config Programs the control function of the Auxiliary Output Contact #2,
wired across control terminal #6 and #7.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Overload Class Required for motor protection. Allows the user to select the
time-to-trip for the built-in Motor Overload. This selection is based on the type of
motor being used and the application it is being applied to.
Service Factor Required for motor protection. This value is taken directly from the
nameplate and used by the controller to determine the ultimate Overload Trip
Current.
Motor FLC Required for motor protection. This programmed value is taken directly
from the motor nameplate.
Starting Torque NOT used for a Soft Start.
Max Torque NOT used for a Soft Start.
Rated Torque NOT used for a Soft Start.
Rated Speed NOT used for a Soft Start.

[0]999 seconds
Disable, Start, Coast,
Stop Option, Start/
Coast, Start/Stop,
Slow Speed, Dual
Ramp, OL Select,
Fault, Fault NC, Clear
Fault, Emerg Run,
Motor Heater
[Normal], UTS, Fault,
Alarm, Ext Bypass, Ext
Brake,
Aux Control ,
Network 1, Network
2, Network 3,
Network 4.
530 [10]

0.01...1.99 [1.15]
1.0...2200.0 [1.0]
Amps
0...300% [100%] RMT
0...300% [250%] RMT
0...10000 [10] Nm
750, 900, 1500,
[1800], 3500, 3600
RPM

Kickstart is available when using Soft Start. A Kickstart Level and Time must be configured if this mode is used. Access these

parameters via the Starting Setup Group. The Starting Setup Group can be accessed with the HIM from the Port <00> DEV PARAM
folder under the File-Group, File: Setup, Group: Starting selection sequence (see Figure 85 on page 159). Setting either parameter to
zero disables Kickstart.
A Start Delay Time can also be programmed to delay starting for a period of time after the initiation of the START command. The Start

Delay parameter can be accessed from the Group Starting selection as noted in above.
In addition to Stop Mode for SMB, a Braking Current value must be configured from the Group Stopping selection (see Figure 85 on
page 159).

To use Ext. Braking, one of the Auxiliary Outputs must be programmed to Ext Brake. When programmed for Ext Brake, the function of

this Auxiliary is to energize the external brake device to stop the motor. The relay stays ON from the beginning of the STOP command
until the STOP time parameter has timed out.
Any auxiliary output configured for Aux Control using the AuxX Config parameter will be under control of its associated bit from the Aux
Control, Parameter 180. See Parameter 180 information for bit assignments.

NOTE: This function enables forcing an output, ON or OFF.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

161

Chapter 5

Programming

Current Limit Start with Simple Stop Mode


To program a Current Limit Start with simple Stop Mode operation, the
following parameters are provided for user adjustment. The basic parameter set
can be accessed with the HIM (see Figure 88 on page 175).
Parameter

Motor Config Setting for the motor configuration Line Connected Wye or
Inside-the-Delta.
NOTE: In the AUTO Detect [default] selection, the controller will automatically
check the motor configuration.
Line Voltage Select the value of line voltage being used in the system. The correct
line voltage value must be entered for the voltage protection functions to work
properly.
Starting Mode This mode must be programmed for Current Limit.
Ramp Time Programs the time period that the SMC-50 will HOLD the fixed
reduced voltage/current before switching to full voltage.
Initial Torque NOT used for a Current Limit Start.
Current Limit Level Limits the current supplied to the motor throughout the Start
cycle.
NOTE: Enter a value so as to limit the current but not so low as to inhibit the start
cycle.
Stop Mode Programs the desired Stop Mode.
NOTE: The mode of stopping does not need to match the starting mode (e.g., a Soft
Start can have a stop mode programmed for [Coast], Linear Stop, or SMB there
is no Current Limit Stop or Torque Stop mode).
Stop Time Programs the amount of time desired to ramp from full to zero voltage for
Soft, Linear, and Pump Stop mode. The actual ramp stop time will depend on the
stopping mode selected and load inertia.
Input 1 Programs the desired operation of the Control Module to a change in status
of Input #1 wired to control terminal #11 (24V DC). [Default: Start/Coast]

Input 2 Programs the desired operation of the Control Module to a change in status
of Input #2 wired to control terminal #10 (24V DC). [Default: Disable]

Aux 1 Config Programs the control function of the Auxiliary Output Contact #1,
wired across control terminal #4 and #5.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Aux 2 Config Programs the control function of the Auxiliary Output Contact #2,
wired across control terminal #6 and #7.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Overload Class
Required for motor protection. Allows the user to select the time-to-trip for the
built-in Motor Overload. This selection is based on the type of motor being used
and the application it is being applied to.
Service Factor Required for motor protection. This programmed value is taken
directly from the nameplate and used by the controller to determine the ultimate
Overload Trip Current.
Motor FLC Required for motor protection. This programmed value is taken directly
from the motor nameplate.
Starting Torque NOT used for a Current Limit Start.
Max Torque NOT used for a Current Limit Start.

162

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Option [default]

Line, Delta,
[Auto Detect]

0700V [480V]
Current Limit
01000 [10] seconds
090% [70%] LRT
50...600% [350%] FLC
[Coast], Soft Stop,
Linear Speed, Pump
Stop, SMB , Ext
Brake
[0]999 seconds
Disable, Start, Coast,
Stop Option,
Start/Coast,
Start/Stop, Slow
Speed,
Dual Ramp, OL Select,
Fault, Fault NC, Clear
Fault, Emerg Run,
Motor Heater
[Normal], UTS, Fault,
Alarm, Ext Bypass, Ext
Brake, Aux Control ,
Network 1, Network 2,
Network 3, Network 4.

5-30 [10]

0.01...1.99 [1.15]
1.0...2200.0 [1.0] Amps
0...300% [100%] RMT
0...300% [250%] RMT

Programming

Chapter 5

Parameter

Option [default]

Rated Torque NOT used for a Current Limit Start.

0...10000 [10] Nm
750, 900, 1500, [1800],
3500, 3600 rpm

Rated Speed NOT used for a Current Limit Start.

Kickstart is available when using Current Limit Start. A Kickstart Level and Time must be configured if this mode is used. Access these

parameters via the Starting Setup Group. The Starting Setup Group can be accessed with the HIM from the Port <00> DEV PARAM
folder under the File-Group, File: Setup, Group: Starting selection sequence (see Figure 85 on page 159). Setting either parameter to
zero disables Kickstart.
A Start Delay Time can also be programmed to delay starting for a period of time after the initiation of the START command. The Start

Delay parameter can be accessed from the Group Starting selection as noted in above.
In addition to Stop Mode for SMB, a Braking Current value must be configured from the Group Stopping selection (see Figure 85 on
page 159).

To use Ext. Braking, one of the Auxiliary Outputs must be programmed to Ext Brake. When programmed for Ext Brake, the function of this

Auxiliary is to energize the external brake device to stop the motor. The relay stays ON from the beginning of the STOP command until
the STOP time parameter has timed out.
Any auxiliary output configured for Aux Control using the AuxX Config parameter will be under control of its associated bit from the Aux
Control, Parameter 180. See Parameter 180 information for bit assignments.
NOTE: This function enables forcing an output, ON or OFF.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

Linear Acceleration (Speed Sense) Start with Stop


To use the Basic Setup Group to program a Linear Acceleration Start and Simple
Stop Mode operation, the following parameters are provided for user adjustment.
The Basic parameter set can be accessed with the HIM (see Figure 88).
Parameter

Motor Config Setting for the motor configuration Line Connected Wye or
Inside-the-Delta.
NOTE: In the AUTO Detect [default] selection, the controller will automatically
check the motor configuration.
Line Voltage Select the value of line voltage being used in the system. The correct
line voltage value must be entered for the voltage protection functions to work
properly.
Starting Mode This mode must be programmed for Linear Speed.
Ramp Time Programs the time period that the SMC-50 will ramp the output
voltage up to full voltage and to full speed from Stop. With the Linear Speed
Starting mode, the time to ramp to full speed will closed to this value depending on
load characteristics.
Initial Torque The initial reduced output (torque) level for the voltage ramp to the
motor is established and adjusted to this parameter. Torque level at which the ramp
begins.
Current Limit Level Limits the current supplied to the motor throughout the Linear
Start and Stop cycle.
NOTE: Enter a value so as to limit the current but not so low as to inhibit the start
cycle.

Option [default]

Line, Delta,
[Auto Detect]

0700V [480V]
Linear Speed
01000 [10] seconds

090% [70%] LRT

50...600% [350%] FLC

Stop Mode Programs the desired Stop Mode.


NOTE: The mode of stopping does not need to match the starting mode (e.g., a Soft
Start can have a stop mode programmed for [Coast], Linear Stop, or SMB there
is no Current Limit Stop or Torque Stop mode).

[Coast], Soft Stop,


Linear Speed,
Pump Stop, SMB ,
Ext Brake

Stop Time Programs the amount of time desired to ramp from full to zero voltage for
Soft, Linear, and Pump Stop mode. The actual ramp stop time will depend on the
stopping mode selected and load inertia.

[0]999 seconds

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

163

Chapter 5

Programming

Parameter

Option [default]

Input 1 Programs the desired operation of the Control Module to a change in status
of Input #1 wired to control terminal #11 (24V DC). [Default: Start/Coast]

Disable, Start, Coast,


Stop Option,
Start/Coast,
Start/Stop, Slow
Speed,
Dual Ramp, OL Select,
Fault, Fault NC, Clear
Fault, Emerg Run,
Motor Heater

Input 2 Programs the desired operation of the Control Module to a change in status
of Input #2 wired to control terminal #10 (24V DC). [Default: Disable]

Aux 1 Config Programs the control function of the Auxiliary Output Contact #1,
wired across control terminal #4 and #5.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Aux 2 Config Programs the control function of the Auxiliary Output Contact #2,
wired across control terminal #6 and #7.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Overload Class Required for motor protection. Allows the user to select the
time-to-trip for the built-in Motor Overload. This selection is based on the type of
motor being used and the application it is being applied to.
Service Factor Required for motor protection. This programmed value is taken
directly from the nameplate and used by the controller to determine the ultimate
Overload Trip Current.
Motor FLC Required for motor protection. This programmed value is taken directly
from the motor nameplate.
Starting Torque NOT used for a Linear Speed Start.
Max Torque NOT used for a Linear Speed Start.
Rated Torque NOT used for a Linear Speed Start.
Rated Speed NOT used for a Linear Speed Start.

[Normal], UTS, Fault,


Alarm, Ext Bypass,
Ext Brake,
Aux Control ,
Network 1, Network 2,
Network 3, Network 4
5-30 [10]

0.01...1.99 [1.15]
1.0...2200.0 [1.0] Amps
0...300% [100] RMT
0...300% [250] RMT
0...10000 [10] Nm
750, 900, 1500, [1800],
3500, 3600 RPM

For best results with Linear Acceleration, Motor Tuning Cycle should be performed. The SMC-50 will do this automatically the first time
the motor is run. The user can also force this manually by setting the Force Tuning parameter to true (=1), which is accessed from the
File Setup, Group Adv. Tuning or by pressing and holding the SMC-50s Reset button for 10 seconds with the motor stopped.
A Start Delay Time can also be programmed to delay starting for a period of time after the initiation of the START command. The Start
Delay parameter can be accessed from the Group Starting selection (see Figure 85 on page 159).
In addition to Stop Mode for SMB, a Braking Current value must be configured from the Group Stopping selection (see Figure 85 on
page 159).
To use Ext. Braking, one of the Auxiliary Outputs must be programmed to Ext Brake. When programmed for Ext Brake, the function of this
Auxiliary is to energize the external brake device to stop the motor. The relay stays ON from the beginning of the STOP command until
the STOP time parameter has timed out.
Any auxiliary output configured for Aux Control using the AuxX Config parameter will be under control of its associated bit from the Aux
Control, Parameter 180. See Parameter 180 information for bit assignments.
NOTE: This function enables forcing an output, ON or OFF.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

164

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Torque Start with Stop


To program a Torque Start with simple Stop operation, the following parameters
are provided for user adjustment. The Basic parameter set can be accessed with
the HIM (see Figure 88 on page 175).
Parameter

Motor Config Setting for the motor configuration Line Connected Wye or
Inside-the-Delta.
NOTE: In the AUTO Detect [default] selection, the controller will automatically
check the motor configuration.
Line Voltage Select the value of line voltage being used in the system. The correct
line voltage value must be entered for the voltage protection functions to work
properly.
Starting Mode This mode must be programmed for Torque Ramp.
Ramp Time Programs the time period that the SMC-50 will ramp the output
voltage from the Starting Torque Value to the Programmed Max Torque Value.
Initial Torque NOT used for a Torque Ramp Start.
Current Limit Level Limits the current supplied to the motor throughout the Torque
Ramp Start cycle.
NOTE: Enter a value so as to limit the current but not so low as to inhibit the start
cycle.
Stop Mode Programs the desired Stop Mode.
NOTE: The mode of stopping does not need to match the starting mode (e.g., a Soft
Start can have a stop mode programmed for [Coast], Linear Stop, or SMB there
is no Current Limit Stop or Torque Stop mode).
Stop Time Programs the amount of time desired to ramp from full to zero voltage for
Soft, Linear, and Pump Stop mode. The actual ramp stop time will depend on the
stopping mode selected and load inertia.
Input 1 Programs the desired operation of the Control Module to a change in status
of Input #1 wired to control terminal #11 (24V DC). [Default: Start/Coast]
Input 2 Programs the desired operation of the Control Module to a change in status
of Input #2 wired to control terminal #10 (24V DC). [Default: Disable]
Aux 1 Config Programs the control function of the Auxiliary Output Contact #1,
wired across control terminal #4 and #5.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Aux 2 Config Programs the control function of the Auxiliary Output Contact #2,
wired across control terminal #6 and #7.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are provided in the
File: Setup, Group: I/O selection sequence. See Figure 85 on page 159.
Overload Class Required for motor protection. Allows the user to select the
time-to-trip for the built-in Motor Overload. This selection is based on the type of
motor being used and the application it is being applied to.
Service Factor Required for motor protection. This programmed value is taken
directly from the nameplate and used by the controller to determine the ultimate
Overload Trip Current.
Motor FLC Required for motor protection. This programmed value is taken directly
from the motor nameplate.
Starting Torque Programmed initial or starting point for a Torque Ramp Start.
Max Torque Programmed end point for a Torque Ramp Start.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Option [default]

Line, Delta,
[Auto Detect]

0700V [480V]
Torque Ramp
01000 [10] seconds
090% [70%] LRT
50...600% [350%] FLC
[Coast], Soft Stop,
Linear Speed,
Pump Stop, SMB ,
Ext Brake
0999 seconds
Disable, Start, Coast,
Stop Option, Start/Coast,
Start/Stop, Slow Speed,
Dual Ramp, OL Select,
Fault, Fault NC, Clear
Fault, Emerg Run, Motor
Heater
[Normal], UTS, Fault,
Alarm, Ext Bypass,
Ext Brake, Aux Control
,
Network 1, Network 2,
Network 3, Network 4

5-30 [10]

0.01...1.99 [1.15]
1...2200 [1.0] Amps
0...300% [100] RMT
0...300% [250] RMT

165

Chapter 5

Programming

Parameter

Option [default]

Rated Torque The actual rated torque of the motor being used in a Torque Ramp
Start.

0...10000 [10] Nm

Rated Speed The actual rated speed of the motor used in the Torque Ramp Start.

750, 900, 1500, [1800],


3500, 3600 RPM

Torque Ramp Starting requires that a Motor Tuning Cycle be performed. The SMC-50 will do this automatically the first time the motor is

run. The user can also force this manually by setting the Force Tuning, Parameter 194, to TRUE (=1), which is accessed from the File Setup,
Group Adv. Tuning or by pressing and holding the SMC-50s Reset button for 10 seconds with the motor stopped.
A Start Delay Time can also be programmed to delay starting for a period of time after the initiation of the START command. The Start
Delay parameter can be accessed from the Group Starting selection (see Figure 85 on page 159).
Kickstart is available when using Torque Start. A Kickstart Level and Time must be configured if this mode is used. Access these
parameters via the Starting Setup Group. The Starting Setup Group can be accessed with the HIM from the Port <00> DEV PARAM folder
under the File-Group, File: Setup, Group: Starting selection sequence (see Figure 85 on page 159). Setting either parameter to zero disables
Kickstart.
In addition to Stop Mode for SMB, a Braking Current value must be configured from the Group Stopping selection (see Figure 85 on
page 159).
To use Ext. Braking, one of the Auxiliary Outputs must be programmed to Ext Brake. When programmed for Ext Brake, the function of this
Auxiliary is to energize the external brake device to stop the motor. The relay stays ON from the beginning of the STOP command until the
STOP time parameter has timed out.
Any auxiliary output configured for Aux Control using the AuxX Config parameter will be under control of its associated bit from the Aux
Control, Parameter 180. See Parameter 180 information for bit assignments.
NOTE: This function enables forcing an output, ON or OFF.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

Pump Start with Stop


To program a Pump Start with simple Stop operation, the following parameters
are provided for user adjustment. The Basic Setup parameter set can be accessed
with the HIM (see Figure 88 on page 175).
Parameter

Motor Config Setting for the motor configuration Line Connected Wye or
Inside-the-Delta.
NOTE: In the AUTO Detect [default] selection, the controller will
automatically check the motor configuration.
Line Voltage Select the value of line voltage being used in the system.
The correct line voltage value must be entered for the voltage protection
functions to work properly.
Starting Mode This mode must be programmed for Pump Start.
Ramp Time Programs the time period that the SMC-50 will ramp the
output voltage to full voltage and motor speed from the programmed Initial
Torque value.
Initial Torque The initial reduced output voltage (torque) level for the
voltage ramp to the motor is established and adjusted with this parameter.
The torque level at which the ramp begins.
Current Limit Level Limits the current supplied to the motor throughout the
Torque Ramp Start cycle.
NOTE: Enter a value so as to limit the current but not so low as to inhibit
the start cycle.

166

Option [default]

Line, Delta,
[Auto Detect]

0700V [480V]
Pump Start
01000 [10] seconds

090% [70%] LRT

50...600% [350%] FLC

Stop Mode Programs the desired Stop Mode.


NOTE: The mode of stopping does not need to match the starting mode
(e.g., a Soft Start can have a stop mode programmed for [Coast], Linear
Stop, or SMB there is no Current Limit Stop or Torque Stop mode).

[Coast], Soft Stop,


Linear Speed,
Pump Stop, SMB ,
Ext Brake

Stop Time Programs the amount of time desired to ramp from full to zero
voltage for Soft, Linear, and Pump Stop mode. The actual ramp stop time
will depend on the stopping mode selected and load inertia.

[0]999 seconds

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Parameter

Option [default]

Input 1 Programs the desired operation of the Control Module to a change


in status of Input #1 wired to control terminal #11 (24V DC). [Default:
Start/Coast]

Disable, Start, Coast,


Stop Option,
Start/Coast,
Start/Stop, Slow
Speed,
Dual Ramp, OL Select,
Fault, Fault NC, Clear
Fault, Emerg Run,
Motor Heater

Input 2 Programs the desired operation of the Control Module to a change


in status of Input #2 wired to control terminal #10 (24V DC). [Default:
Disable]
Aux 1 Config Programs the control function of the Auxiliary Output Contact
#1, wired across control terminal #4 and #5.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are
provided in the File: Setup, Group: I/O selection sequence. See Figure 85 on
page 159.
Aux 2 Config Programs the control function of the Auxiliary Output Contact
#2, wired across control terminal #6 and #7.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are
provided in the File: Setup, Group: I/O selection sequence. See Figure 85 on
page 159.
Overload Class Required for motor protection. Allows the user to select the
time-to-trip for the built-in Motor Overload. This selection is based on the
type of motor being used and the application it is being applied to.
Service Factor Required for motor protection. This programmed value is
taken directly from the nameplate and used by the controller to determine
the ultimate Overload Trip Current.
Motor FLC
Required for motor protection. This programmed value is taken directly
from the motor nameplate.
Starting Torque NOT used for Pump Start.
Max Torque NOT used for Pump Start.
Rated Torque NOT used for Pump Start.
Rated Speed NOT used for Pump Start.

[Normal], UTS, Fault,


Alarm, Ext Bypass,
Ext Brake,
Aux Control ,
Network 1, Network 2
Network 3, Network 4

5-30 [10]

0.01...1.99 [1.15]

[1]...2200 Amps
0...300% [100%] RMT
0...300% [250%] RMT
0...10000 [10] Nm
750, 900, 1500, [1800],
3500, 3600 RPM

For best results with a Pump Start, it is recommended that the tuning cycle be run. The SMC-50 will automatically perform the

tuning cycle the first time the motor is run. The user can also force this manually by setting the Force Tuning parameter to
TRUE (=1), which is accessed from the File Setup, Group Adv. Tuning or by pressing and holding the SMC-50s Reset button for
10 seconds with the motor stopped.
A Start Delay Time can also be programmed to delay starting for a period of time after the initiation of the START command.
The Start Delay parameter can be accessed from the Group Starting selection (see Figure 85 on page 159).
In addition to Stop Mode for SMB, a Braking Current value must be configured from the Group Stopping selection (see
Figure 85 on page 159).
To use Ext. Braking, one of the Auxiliary Outputs must be programmed to Ext Brake. When programmed for Ext Brake, the
function of this Auxiliary is to energize the external brake device to stop the motor. The relay stays ON from the beginning of
the STOP command until the STOP time parameter has timed out.
Any auxiliary output configured for Aux Control using the AuxX Config parameter will be under control of its associated bit
from the Aux Control, Parameter 180. See Parameter 180 information for bit assignments.
NOTE: This function enables forcing an output, ON or OFF.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

Full Voltage Start with Stop


The SMC-50 may be programmed to provide a full voltage start (output voltage
to the motor reaches full voltage within five line power cycles).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

167

Chapter 5

Programming

To provide a Full Voltage Start to the motor, the only start parameter that
requires adjustment is the Starting Mode. The Basic parameter set should be used
to program Full Voltage Start to ensure configuration of other motor
configuration and basic protection parameters. To use the Basic parameter set to
program a Full Voltage Start and Simple or Stop Mode operation, the following
parameters are provided for user adjustment. The Basic Setup parameter set can
be accessed with the HIM (see Figure 88 on page 175).
Parameter

Motor Config Setting for the motor configuration Line Connected Wye or
Inside-the-Delta.
NOTE: In the AUTO Detect [default] selection, the controller will
automatically check the motor configuration.
Line Voltage Select the value of line voltage being used in the system.
The correct line voltage value must be entered for the voltage protection
functions to work properly.
Starting Mode This mode must be programmed for Full Voltage Start.
Ramp Time NOT used for Full Voltage Start.
Initial Torque NOT used for Full Voltage Start.
Current Limit Level NOT used for Full Voltage Start.
Stop Mode Programs the desired Stop Mode.
NOTE: The mode of stopping does not need to match the starting mode
(e.g., a Soft Start can have a stop mode programmed for [Coast], Linear
Stop, or SMB there is no Current Limit Stop or Torque Stop mode).
Stop Time Programs the amount of time desired to ramp from full to zero
voltage for Soft, Linear, and Pump Stop mode. The actual ramp stop time
will depend on the stopping mode selected and load inertia.
Input 1 Programs the desired operation of the Control Module to a change
in status of Input #1 wired to control terminal #11 (24V DC). [Default:
Start/Coast]
Input 2 Programs the desired operation of the Control Module to a change
in status of Input #2 wired to control terminal #10 (24V DC). [Default:
Disable]
Aux 1 Config Programs the control function of the Auxiliary Output Contact
#1, wired across control terminal #4 and #5.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are
provided in the File: Setup, Group: I/O selection sequence. See Figure 85 on
page 159.
Aux 2 Config Programs the control function of the Auxiliary Output Contact
#2, wired across control terminal #6 and #7.
NOTE: Relay Operational Options (e.g., ON and OFF delay, etc.) are
provided in the File: Setup, Group: I/O selection sequence. See Figure 85 on
page 159.
Overload Class Required for motor protection. Allows the user to select the
time-to-trip for the built-in Motor Overload. This selection is based on the
type of motor being used and the application it is being applied to.
Service Factor Required for motor protection. This programmed value is
taken directly from the nameplate and used by the controller to determine
the ultimate Overload Trip Current.
Motor FLC Required for motor protection. This programmed value is taken
directly from the motor nameplate.
Starting Torque NOT used for Full Voltage Start.
Max Torque NOT used for Full Voltage Start.

168

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Option [default]

Line, Delta,
[Auto Detect]

0700V [480V]
Full Voltage
01000 [10] seconds
090% [70%] LRT
50...600% [350%] FLC
[Coast], Soft Stop,
Linear Speed,
Pump Stop, SMB ,
Ext Brake
[0]999 seconds
Disable, Start, Coast,
Stop Option,
Start/Coast,
Start/Stop, Slow
Speed,
Dual Ramp, OL Select,
Fault, Fault NC,
Clear Fault, Emerg
Run, Motor Heater
[Normal], UTS, Fault,
Alarm, Ext Bypass,
Ext Brake,
Aux Control ,
Network 1, Network 2,
Network 3, Network 4

5-30 [10]

0.01...1.99 [1.15]
[1]...2200 Amps
0...300% [100%] RMT
0...300% [250%] RMT

Programming

Chapter 5

Parameter

Option [default]

Rated Torque NOT used for Full Voltage Start.

0...10000 [10] Nm
750, 900, 1500, [1800],
3500, 3600 RPM

Rated Speed NOT used for Full Voltage Start.

A Start Delay Time can also be programmed to delay starting for a period of time after the initiation of the START command.
The Start Delay parameter can be accessed from the Group Starting selection.

In addition to Stop Mode for SMB, a Braking Current value must be configured from the Group Stopping selection (see
Figure 85 on page 159).

To use Ext. Braking, one of the Auxiliary Outputs must be programmed to Ext Brake. When programmed for Ext Brake, the

function of this Auxiliary is to energize the external brake device to stop the motor. The relay stays ON from the beginning of
the STOP command until the STOP time parameter has timed out.
Any auxiliary output configured for Aux Control using the AuxX Config parameter will be under control of its associated bit
from the Aux Control, Parameter 180. See Parameter 180 information for bit assignments.
NOTE: This function enables forcing an output, ON or OFF.

ATTENTION: For Overload Protection, it is critical that the data be


entered into the SMC-50 as it appears on the motor nameplate.

Dual Ramp Start with Stop


The SMC-50 provides the ability to select between two start profiles. Start
Profile 1 can be configured using the Basic parameter set as explained in the
previous sections. The Basic Setup parameter set can be accessed with the HIM
(see Figure 88 on page 175).

NOTE:

The Stop mode selected in the Basic parameter set will apply to both start profiles.
The Basic parameter set provides the method to select between the operation of Start
Profile 1 and Start Profile 2 by configuration of Input 1 or Input 2 to the Dual Ramp. If
the input configured for Dual Ramp is open (low), Start Profile 1 is selected. If the input
is closed (high), Profile 2 is selected.

Setup of Start Profile 2 is accomplished using the Dual Ramp parameter set. Dual
Ramp can be accessed with the HIM from the <Port 00> DEV PARAM folder
(see Setup on page 175). The following parameters are provided for user Dual
Ramp adjustment.
Parameter

Starting Mode 2 Select the desired starting mode for Profile 2 (Soft
Start, Full Voltage, Linear Speed, Torque Start, Current Limit, Pump
Start).
Ramp Time 2 Programs the Profile 2 time period that the SMC-50 will
ramp the output voltage to full voltage and motor speed from the
programmed Initial Torque value.
Current Limit Level 2 The Profile 2 setting limits the current supplied in
the motor throughout the Soft Start, Linear Speed, or Torque Ramp cycle.
NOTE: Enter a value so as to limit current but not so low as to inhibit the
start cycle.
Initial Torque 2 The initial reduced output voltage (torque) level for the
Profile 2 Voltage Ramp to the motor is established and adjusted with
this parameter. The torque level at which the ramp begins for Profile 2.
NOTE: Not used for Torque Ramp.
Starting Torque 2 For a Torque Ramp Start, the programmed initial or
start torque point for Profile 2. This parameter is not used for other
starting modes.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Option [default]

Soft Start, Linear, etc.

01000 [10] seconds

50...600% [350%] FLC

0...90% [70%]

0...300% [100%] RMT

169

Chapter 5

Programming

Parameter

Max Torque 2 For Start Profile 2, the programmed torque end point for a
Torque Ramp start. This parameter is not used for other starting modes.
Kickstart Time 2 For Start Profile 2, if required, a boost of current (torque)
is provided to motor for this programmed time period. NOTE: Available
for Soft Start, Current Limit, and Torque Start modes. Set to zero to
disable Kickstart.
Kickstart Level 2 For Start Profile 2, if required, this parameter
programs the amount of current (torque) applied to the motor during
Kickstart time.
NOTE: Available for Soft Start, Current Limit, and Torque Start modes.
Set to zero to disable Kickstart.

Option [default]

0...300% [250%] RMT

[0]...2 seconds

750, 900, 1500, [1800],


3500, 3600 RPM

Torque Ramp and Linear Speed Starting modes require that a Motor Tuning Cycle be performed. The SMC-50 will

automatically perform the tuning cycle the first time the motor is run. The user can also force this manually by setting the
Force Tuning, Parameter 194, to TRUE (=1), which is accessed from the File Setup, Group Adv. Tuning or by pressing and
holding the SMC-50 Reset button for 10 seconds with the motor stopped.
A Start Delay Time can also be programmed and will apply to both Start Profile 1 and Start Profile 2. The Start Delay
parameter can be accessed from the Group Starting selection (see Figure 85 on page 159).

Start Options
Motor Winding Heater Function
The motor winding heater can be activated after a valid Start command is
received. After a valid Start command is received, the activation of the heating
function can be performed by either programming the Heating Time parameter
to a non-zero value or by configuring a terminal block input to Motor Heater and
activating that input prior to the Start command. The Motor Winding Heater
function will continue for the specified time or until the Motor Heater Input is
deactivated, at which time the motor will start based on the prior Start command
signal. The Motor Winding Heater function will be disabled if the Heater Level
parameter is set to zero, the Heater Time is set to zero, or the Input is inactive (or
not configured) at the time of the Start command.
To program the Motor Winding Heater function, use the File Setup, Group Basic
parameter list to configure the motor and the majority of the Start/Stop
functions. See any of the previous programming sections for details based on the
selected Start mode. The two key parameters (Heating Time and Heating Level),
however, are in the File Setup Group Starting parameter list. See Figure 88 on
page 175 for a basic understanding of accessing the Starting group. See the table
below for details concerning the Heating Time and Heating Level parameters.
Parameter

Option [default]

Heating Time The amount of time the Motor Winding Heater function will
remain engaged after receiving a valid Start command.
Heating Level The percent Heating Level is sequentially applied to each
winding.

[0]...1000 seconds

[0]...100%

If the Terminal Block Input, configured to Motor Heater, is used to initiate the Motor Winding Heater function, Heating Time
can be zero (0), The heater function will be active after the terminal input is active and a start command.

170

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Stop Options
SMB Smart Motor Breaking
To use the SMB function, the Stopping file group parameter set must be selected
from FILE Setup group using the HIM (see Figure 88 on page 175).
Parameter

Stop Mode Allows selection of the desired Stop mode. The mode must be
programmed for SMB.
Stop Time NOT used for SMB. SMB automatically controls the duration (stop
time) of the braking current to the motor from the "running at speed" condition
until a zero speed condition is reached (zero speed braking shutoff
feature/function).
Braking Current The amount of braking current to be applied to the motor.
Backspin Timer The amount of time which much expire before another Start
cycle can occur. The timer begins after the Stop maneuver is completed. All
Start commands are ignored until the timer has expired. If the Start command is
momentary and ends before the timer has expired, the motor will not start. This
is used to prevent starting a motor that is still cycling.

Option [default]

SMB

[0]...999 seconds
[0]...400% FLC

[0]...999 seconds

Programming a non-zero value for Stop Time will override the SMB zero-speed detection feature/function and use the exact
time programmed for Stop Time to apply the programmed Braking Current to the motor. Doing this is useful in applications
where detecting zero-speed is difficult (e.g., a specific motor type or when the purpose is to reduce the number of overload
trips associated with driving the motor to a complete stop). Setting the Stop Time to a specific value will turn off braking
current at a set time and each time a stopping maneuver is performed. To achieve an ideal Stop Time setting, use trial and
error and always allow for some small coast time.
NOTE: Setting the Stop Time to a longer duration will cause braking current to be applied to a stopped motor and likely result
in overload trips.

Slow Speed with Braking


The SMC-50 Slow Speed feature provides a slow speed jog capability for general
purpose positioning which is typically used for system setup. Slow Speed can
drive the motor within a range of 1 to 15% of normal speed in the forward or
reverse direction without a reversing contactor. Braking from Slow Speed is also
provided.
To use the Slow Speed with Braking feature, use the HIM. Navigate from the Port
00 DEV PARAM folder: File-Group, File: Setup, Group: Slow Speed. See
Figure 88 on page 175 for detailed information.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

171

Chapter 5

Programming

Parameter

Option [default]

Slow Speed Allow selection of the best Slow Speed value for the application.
NOTE: The plus (+) or minus (-) sign determines the motor direction.
Slow Brake Current The desired brake current to be applied from the
programmed Slow Speed.
NOTE: A value of zero results in Coast-to-Stop.
Slow Speed Reference Gain Provides the ability to adjust the flux reference while
the motor is running.
Slow Speed Transient Gain Provides the ability to adjust the control reference
when transitioning between slow speed and any starting mode.

-15...+15 [+10]
[0]...350% FLC
0.1...2.00 [1.00]
0.1...2.0 [1.00]

Accu-Stop
This function combines the benefits of SMB and Preset Slow Speed features. For
general purpose positioning, the Accu-Stop function provides a brake from full
speed to the preset slow speed setting, then a brake from Slow Speed or a
Coast-to-Stop.
The Accu-Stop function is enabled whenever a control input is configured for
Stop and another control input is configured for Slow Speed; the Stop Mode is
configured for SMB and Slow Speed is configured. When the Slow Speed Input
is enabled in this configuration, a SMB-to-Slow Speed occurs and Slow Speed
continues until the Slow Speed Input is enabled.
To program Accu-Stop with the HIM, Setup Group Slow Speed and Setup
Group Stopping must be used. See the two previous programming sections, SMB
Smart Motor Breaking and Slow Speed with Braking.

Motor Protection

The Motor Protection Group (see Figure 89 on page 175) is used to program
motor and starter protection functions. The Motor Protection Group is accessed
from the HIM using the Port 00 DEV PARAM folder under the File-Group,
File: Motor Protection selection sequence. By using this file group, the SMC-50
provides the ability to individually enable, disable, or restart the motor and
starter Faults and Alarms. Each of the 21 different Motor/Starter Protection
Setup groups (e.g., Overload, Underload, Jam, Stall, Voltage Unbal, etc.) has at
least one selection for Fault Enable, Alarm Enable, and Restart Enable. For bit
assignment definitions for the related Faults and Alarms, see Table 32 and
Table 33 on page 105 in Chapter 4.
IMPORTANT

The majority of parameters have a Fault and an Alarm setting.

To modify any Fault or Alarm bit for enable/disable functionality, perform the
following steps.

172

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

1. From the Motor Protection Group, select the desired group.


Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00

Param File-Group

Motor Protection
PROPERTIES
Overload
Underload
Undervoltage
Overvoltage

FILE
GROUP
GROUP
GROUP
GROUP

ESC

2. Press ENTER (number 5 from keypad) to display the associated bit


parameters.
Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00
FILE
GROUP
Motor
Motor
Motor

Param File-Group

Motor Protection
PROPERTIES
Overload
Fault En
Alarm En
Restart En

ESC

ENTER

3. Select the desired 16 bit field, then press EDIT.


Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00

Dev Param

230

PROPERTIES
Motor Fault Enable
0000 0000 0000 0000
Bit

01 - Underload

ESC

NOTE:

UPPER

PAR #

EDIT

The UPPER and LOWER soft key allows for switching between the upper (16 to 31)
and lower (0 to 16) bits.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

173

Chapter 5

Programming

4. Use the right or left arrow to move the cursor to the desired bit. The bit
function is displayed at the bottom of the screen.
5. Enter a 1 to enable or 0 to disable, then press ENTER to load the change
into the controller.
Allen-Bradley
AUTO
F

Stopped
0 Amps

Port
Host Param
Edit07 Motor
Fault En 2
PROPERTIES

xxxx
Bit

16

ESC

xxxx 0000
- Power

0000

Qual

ENTER

For details concerning mot or and controller (Fault and Alarm) protection
parameters, see Chapter 4, Protection & Diagnostic Functions.

Parameter File-Group
Structure

The five parameter File-Groups are structured as shown below. The access levels
for each parameter are abbreviated as follows:
M Monitoring,
B Basic,
A Advanced, and
MBA Monitoring, Basic, and Advanced.
Figure 87 - Monitoring

Monitoring
Metering Basic (MBA)
Volts P-P Ave
Volts P-N Ave
Current Average
Torque
Motor Speed
Power Factor
Real Power
Reactive Power
Apparent Power
Real Energy
Reactive Energy +
Reactive Energy Apparent Energy
Meter Reset
Metering Volts (MBA)
Volts P-P Ave
Volts Phase A-B
Volts Phase B-C
Volts Phase C-A
Volts P-N Ave
Volts Phase A-N
Volts Phase B-N
Volts Phase C-N
Volts Unbal

174

Metering Current (MBA) Metering Power (MBA)


Real Power
Current Ave
Real Power A
Current Phase A
Real Power B
Current Phase B
Real Power C
Current Phase C
Real Demand
Current Imbal
Max Real Demand
Reactive Power
Reactive Power A
Reactive Power B
Reactive Power C
Reactive Demand
Max Reactive Demand
Apparent Power
Apparent Power A
Apparent Power B
Apparent Power C
Apparent Demand
Max Apparent Demand
Power Factor
Power Factor A
Power Factor B
Power Factor C

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Start Stats (MBA)


Start Time 1
Start Time 2
Start Time 3
Start Time 4
Start Time 5
Peak Current 1
Peak Current 2
Peak Current 3
Peak Current 4
Peak Current 5
Monitoring (MBA)
Elapsed Time
Elapsed Time 2
Running Time
Energy Savings
Motor Therm Usage
Time to OL Trip
Time to OL Reset
Time to PM
Starts to PM
Total Starts
Product Status

Power Quality (MBA)


THD Va
THD Vb
THD Vc
THD Vave
THD Ia
THD Ib
THD Ic
THD Iave

Programming

Chapter 5

Figure 88 - Setup

Setup
Basic (BA)
Motor Config
Line Voltage
Starting Mode
Ramp Time
Initial Torque
Max Torque
Cur Limit Level
Stop Mode
Stop Time
Input 1
Input 2
Aux1 Config
Aux2 Config
Overload Class
Service Factor
Motor FLC
Starting Torque
Max. Torque
Rated Torque
Rated Speed

Starting (BA)
Starting Mode
Ramp Time
Cur Limit Level
Initial Torque
Starting Torque
Max Torque
Kickstart Time
Kickstart Level
Heating Time
Heating Level
Start Delay

Stopping (BA)
Stop Mode
Stop Time
Braking Current
Backspin Timer
Slow Speed
Slow Speed (BA)
Slow Brake Cur (BA)
SS Ref Gain (A)
SS Trans Gain (A)
Dual Ramp (BA)
Starting Mode 2
Ramp Time 2
Cur Limit Level 2
Initial Torque 2
Starting Torque 2
Max Torque 2
Kickstart Time 2
Kickstart Level 2

Advanced
Pump Pedestal (A)
Load Type (A)
High Eff Brake (A)
UTS Level (A)
Stall Position (A)
Stall Level (A)
V Shut Off Level (A)
I Shut Off Level (A)
Notch Maximum (A)
Timed Start (A)
Bypass Delay (A)
Energy Saver (BA)
Demand Period (BA)
Num of Periods (BA)

I/O (BA)
Input 1
Input 2
Aux 1 Config
Aux 1 Invert
Aux 1 On Delay
Aux 1 Off Delay
Aux 2 Config
Aux 2 Invert
Aux 2 Invert
Aux 2 On Delay
Aux 2 Off Delay
Aux Control

Advanced Tuning
Force Tuning (A)
Starter R (MBA)
Total R (MBA)
Coupling Factor (MBA)
Inductance (MBA)
Speed PGain (A)
Transient Gain (A)
Transient Zero (A)
Transient Mag (A)
Ping Degree (A)
Pings (A)
Phase Shift 0% (A)
Phase Shift 10% (A)
Phase Shift 20% (A)
Phase Shift 30% (A)
Phase Shift 40% (A)
Phase Shift 50% (A)
Phase Shift 60% (A)
Phase Shift 70% (A)
Phase Shift 80% (A)
Phase Shift 90% (A)
Phase Shift 100% (A)

Figure 89 - Motor Protection

Motor Protection
Overload (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Overload Class
Overload Class 2
Service Factor
Motor FLC
OL Reset Level
OL Shunt Time
OL Inhibit Time
Overload A Lvel
Underload (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Underload F Level
Underload F Delay
Underload A Level
Underload A Delay

Jam (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Jam F Level
Jam F Delay
Jam A Level
Jam A Delay
Stall (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Stall Delay

Real Power (BA)


Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Mwatts Ov F Level
Mwatts OV F Delay
Mwatts Ov A Level
Undervoltage (BA)
Mwatts OV A Delay
Starter Fault Enable
Mwatts Un F Level
Starter Alarm Enable Mwatts Un F Delay
Starter Restart Enable Mwatts Un A Level
Undervolt F Level
Mwatts Un A Delay
Undervolt F Delay
Undervolt A Level
Reactive+ Power (BA)
Undervolt A Delay
Motor Fault Enable
Motor Alarm Enable
Overvoltage (BA)
Motor Restart Enable
+MVAR Ov F Level
Starter Fault Enable
Starter Alarm Enable +MVAR OV F Delay
Starter Restart Enable +MVAR Ov A Level
+MVAR OV A Delay
Overvolt F Level
+MVAR Un F Level
Overvolt F Delay
+MVAR Un F Delay
Overvolt A Level
+MVAR Un A Level
Overvolt A Delay
+MVAR Un A Delay

Apparent Power (BA)


Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
MVA Ov F Level
MVA OV F Delay
MVA Ov A Level
MVA OV A Delay
MVA Un F Level
MVA Un F Delay
MVA Un A Level
MVA Un A Delay
Leading PF (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Lead PF Level
Lead PF F Delay
Lead PF A Level
Lead PF A Delay
Lead PF F Level
Lead PF F Delay
Lead PF A Level
Lead PF A Delay
Lagging PF (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Lag PF F Level
Lag PF F Delay
Lag PF A Level
Lag PF A Delay
Lag PF F Level
Lag PF F Delay
Lag PF A Level
Lag PF A Delay

Current Imbal (BA)


Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Current Imbal F Level
Current Imbal F Delay
Current Imbal A Level
Current Imbal A Delay
Voltage THD (BA)
Starter Fault Enable
Starter Alarm Enable
Starter Restart Enable
THD V F Level
THD V F Delay
THD V A Level
THD V A Delay
Current THD (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
THD I F Level
THD I F Delay
THD I A Level
THD I A Delay
Line Frequency (BA)
Starter Fault Enable
Starter Alarm Enable
Starter Restart Enable
Frequency High F Level
Frequency High F Delay
Frequency High A Level
Frequency High A Delay
Frequency Low F Level
Frequency Low F Delay
Frequency Low A Level
Frequency Low A Delay

Maintenance
Motor Fault Enable (BA)
Motor Alarm Enable (BA)
Motor Restart Enable (BA)
PM Hours (BA)
PM Starts (BA)
Time to PM (MBA)
Starts to PM (MBA)
Starts per Hour (BA)
History (MBA)
Fault 1
Fault 2
Fault 3
Fault 4
Fault 5
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Restart (BA)
Motor Restart Enable
Starter Restart Enable
Restart Attempts
Restart Delay
Locked Rotor (BA)
Motor Fault Enable
Motor Alarm Enable
Motor Restart Enable
Locked Rotor F Level
Locked Rotor F Delay
Locked Rotor A Level
Locked Rotor A Delay

Voltage Unbal (BA)


Starter Fault Enable
Reactive- Power (BA) Starter Alarm Enable
Starter Restart Enable
Motor Fault Enable
Voltage Unbal F Level
Motor Alarm Enable
Voltage Unbal F Delay
Motor Restart Enable Voltage Unbal A Level
-MVAR Ov F Level
Voltage Unbal A Delay
-MVAR OV F Delay
-MVAR Ov A Level
-MVAR OV A Delay
-MVAR Un F Level
-MVAR Un F Delay
-MVAR Un A Level
-MVAR Un A Delay

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

175

Chapter 5

Programming

Figure 90 - Communications

Communications
Communcation Masks (BA)
Logic Mask
Logic Mask Act
Write Mask Cfg
Write Mask Act
Port Mask Act

Data Links (BA)


Data In A1
Data In A2
Data In B1
Data In B2
Data In C1
Data In C2
Data In D1
Data In D2
Data Out A1
Data Out A2
Data Out B1
Data Out B2
Data Out C1
Data Out C2
Data Out D1
Data Out D2

Figure 91 - Utility

Utility
Motor Data
Preferences
Motor Connection (MBA)
Language (BA)
Line Voltage (BA)
Fan Configuration (BA)
Motor FLC (BA)
Motor Configuration (BA)
Parameter Management (A) Rated Torque (BA)
Rated Speed (BA)
User CT Ratio (A)
Factory CT Ratio (A)
Voltage Ratio (A)
Parameter Management (A)

Expansion (MBA)
Expansion A Configuration
Expansion B Configuration
Expansion C Configuration

DeviceLogix parameters are Parameters 335346, located in the parameter


linear list. See Appendix F for additional information and programming
examples.

176

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Table 73 - SMC-50 Parameter Linear List Parameter 1-67


Number

Name

1 (M, B, A)

Voltage

2 (M, B, A)
3 (M, B, A)

VoltsPhase

4 (M, B, A)

Number

Name

P-P Ave 35 (M, B, A)

Va

A-B

36 (M, B, A)

Vb

B-C

37 (M, B, A)

Vc

C-A

38 (M, B, A)
THD

5 (M, B, A)

7 (M, B, A)

39 (M, B, A)

Ia

40 (M, B, A)

Ib

41 (M, B, A)

Ic

42 (M, B, A)

Iave

Current Average

6 (M, B, A)
Current Phase

8 (M, B, A)
9 (M, B, A)

Torque

43 (M, B, A)

Product Status

10 (M, B, A)

Real Power

44 (B, A)

Motor Config

11 (M, B, A)

Real Energy

45 (M, B, A)

Motor Connection

12 (M, B, A)

Elapsed Time

46 (B, A)

Line Voltage

13 (M, B, A)

Elapsed Time 2

47 (B, A)

14 (M, B, A)

Running Time

48 (B, A)

15 (M, B, A)

Energy Savings

49 (B, A)

Starting Mode

16 (M, B, A)

Meter Reset

50 (B, A)

Ramp Time

17 (M, B, A)

Power Factor

51 (B, A)

Initial Torque

18 (M, B, A)

Motor Therm Usage

52 (B, A)

Maximum Torque

Trip

53 (B, A)

Current Limit Level

Reset

54 (B, A)

19 (M, B, A)
20 (M, B, A)

Time to OL

Vave

21 (M, B, A)

Time to PM

55 (B, A)

22 (M, B, A)

Starts to PM

56 (B, A)

23 (M, B, A)

Total Starts

57 (B, A)

Rated

Kickstart

Input

Torque
Speed

Time
Level
1
2

24 (M, B, A)

58 (B, A)

Starting Mode 2

25 (M, B, A)

59 (B, A)

Ramp Time 2

60 (B, A)

Initial Torque 2

27 (M, B, A)

61 (B, A)

Maximum Torque 2

28 (M, B, A)

62 (B, A)

Current Limit Level 2

29 (M, B, A)

63 (B, A)

30 (M, B, A)

64 (B, A)

65 (B, A)

32 (M, B, A)

66 (B, A)

33 (M, B, A)

67 (B, A)

26 (M, B, A)

31 (M, B, A)

34 (M, B, A)

Start Time

Peak Current

Motor Speed

Kickstart

Stop

Time 2
Level 2
Mode
Time

Backspin Timer

M, B, A = Access Level; see Parameter Access Level using


the HIM.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

177

Chapter 5

Programming

Table 74 - SMC-50 Parameter Linear List Parameter 68-135


Number

Name

Number

68 (A)

Pump Pedestal

102 (B, A)

69 (B, A)

Braking Current

103 (B, A)

70 (B, A)

Load Type

104 (B, A)

71 (B, A)

High Eff Brake

105 (B, A)

A Dly

72 (B, A)

Slow Speed

106 (B, A)

F Lvl

73 (B, A)

Slow Brake Current

107 (B, A)

74 ()

Reserved

108 (B, A)

75 (B, A)

Overload Class

109 (B, A)

A Dly

76 (B, A)

Overload Class 2

110 (B, A)

F Lvl

77 (B, A)

Service Factor

111 (B, A)

78 (B, A)

Motor FLC

112 (B, A)

79 (B, A)

Motor FLC 2

113 (B, A)

A Dly

80 (B, A)

OL Reset Level

114 (B, A)

F Lvl

81 (B, A)

OL Shunt Time

115 (B, A)

82 (B, A)

OL Inhibit Time

116 (B, A)

83 (B, A)

Overload A Lvl

117 (B, A)

A Dly

F Lvl

118 (B, A)

F Lvl

F Dly

119 (B, A)

F Lvl

120 (B, A)

F Dly

121 (B, A)

A Dly

A Lvl

122 (B, A)

F Lvl

89 (B, A)

A Dly

123 (B, A)

90 (B, A)

F Lvl

124 (B, A)

F Dly

125 (B, A)

A Lvl

126 (B, A)

PM Hours

93 (B, A)

A Dly

127 (B, A)

PM Starts

94 (B, A)

F Lvl

128 (B, A)

Starts Per Hour

F Dly

129 (B, A)

Frequency High F Lvl

A Lvl

130 (B, A)

Frequency Low F Lvl

97 (B, A)

A Dly

131 (B, A)

Frequency High A Lvl

98 (B, A)

F Lvl

132 (B, A)

Frequency Low A Lvl

F Dly

133 (B, A)

Restart Attempts

A Lvl

134 (B, A)

Restart Delay

A Dly

135 (B, A)

Starter Restart Enable

84 (B, A)
85 (B, A)

Locked Rotor

86 (B, A)
87 (B, A)
88 (B, A)

91 (B, A)
92 (B, A)

95 (B, A)
96 (B, A)

99 (B, A)
100 (B, A)
101 (B, A)

Underload

MWatts Ov

MWatts Un

Undervolt

M, B, A = Access Level; see Parameter Access Level using the HIM.

178

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Name
F Lvl
Overvolt

Volt Unbal

Cur Imbal

Jam

THD V

THD I

F Dly
A Lvl

F Dly
A Lvl

F Dly
A Lvl

F Dly
A Lvl

F Dly
A Lvl

F Dly
A Lvl
A Dly

Programming

Chapter 5

Table 75 - SMC-50 Parameter Linear List Parameter 136 - 205


Number

Name

Number

Name

136 (B, A)

Starter Fault Enable

171 (A)

Factory CT Ratio

137 (B, A)

Starter Alarm Enable

172 (B, A)

138 (M, B, A)

173 (B, A)

139 (M, B, A)

174 (B, A)

140 (M, B, A) Fault

175 (B, A)

Off Delay

141 (M, B, A)

176 (B, A)

Config

142 (M, B, A)

177 (B, A)

143 (M, B, A)

178 (B, A)

144 (M, B, A)

179 (B, A)

145 (M, B, A) Alarm

180 (B, A)

Aux Control

146 (M, B, A)

181 (B, A)

Language

147 (M, B, A)

182 (B, A)

Start Delay

Config
Aux 1

Aux 2

Logic Mask

183 (A)

Timed Start

149 (B, A)

Logic Mask Act

184 (A)

V Shut Off Level

150 (B, A)

Write Mask Cfg

185 (A)

I Shut Off Level

151 (B, A)

Write Mask Act

186 (A)

UTS Level

152 (B, A)

Port Mask Act

187 (A)
A1 188 (B, A)

154 (B, A)

A2 189 (A)

155 (B, A)

B1 190 (A)

Notch Maximum

B2 191 (A)

Notch Position

C1 192 (A)

Bypass Delay

158 (B, A)

C2 193 (B, A)

Energy Saver

159 (B, A)

D1 194 (A)

Force Tuning

160 (B, A)

D2 195 (M, B, A)

Stator R

161 (B, A)

A1 196 (M, B, A)

Total R

162 (B, A)

A2 197 (M, B, A)

Coupling Factor

163 (B, A)

B1 198 (M, B, A)

Inductance

B2 199 (A)

Speed PGain

157 (B, A)

164 (B, A)
165 (B, A)

Data Out

Stall

C2 201 (A)

167 (B, A)

D1 202 (A)

168 (B, A)

D2 203 (A)

On Delay

Delay
Position

C1 200 (A)

166 (B, A)

Invert

Level

153 (B, A)

Data In

On Delay

Off Delay

148 (B, A)

156 (B, A)

Invert

Gain
Transient

Zero
Mag

Ping Degree

169 (A)

Voltage Ratio

204 (A)

Pings

170 (A)

User CT Ratio

205 (A)

Phase Shift 0

M, B, A = Access Level; see Parameter Access Level using the HIM.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

179

Chapter 5

Programming

Table 76 - SMC-50 Parameter Linear List Parameter 206 - 277


Number

Number

Name

Name

206 (A)

10

242 (B, A)

Ov A Lvl

207 (A)

20

243 (B, A)

Ov A Dly

30

244 (B, A)

209 (A)

40

245 (B, A)

210 (A)

50

246 (B, A)

Un A Lvl

211 (A)

60

247 (B, A)

Un A Dly

212 (A)

70

248 (B, A)

Ov F Lvl

80

249 (B, A)

Ov F Dly

214 (A)

90

250 (B, A)

Ov A Lvl

215 (A)

100

251 (B, A)

208 (A)

213 (A)

Phase Shift

Phase Shift

MVA

Lead PF

Un F Lvl
Un F Dly

Ov A Dly

216 (M, B, A)

Board Temp

252 (B, A)

217 (B, A)

Exp 7 Config

253 (B, A)

Un F Dly

218 (B, A)

Exp 8 Config

254 (B, A)

Un A Lvl

219 (B, A)

Exp 9 Config

255 (B, A)

Un A Dly

Time

256 (B, A)

Ov F Lvl

Level

257 (B, A)

Ov F Dly

Config

258 (B, A)

Ov A Lvl

220 (B, A)
221 (B, A)
222 (B, A)
223 (M, B, A)
224 (M, B, A)
225 (B, A)
226 (B, A)
227 (B, A)
228 (B, A)
229 (A)
230 (B, A)

Heating

Fan

Connection 259 (B, A)

Line Frequency
Freq High

Freq Low

260 (B, A)

Lag PF

Un F Lvl

Ov A Dly
Un F Lvl

F Dly

261 (B, A)

Un F Dly

A Dly

262 (B, A)

Un A Lvl

F Dly

263 (B, A)

Un A Dly

A Dly

264 (B, A)

Motor Restart En

265 (M, B, A)

Voltage

Parameter Management

P-N Ave

Fault En

266 (M, B, A)

Alarm En

267 (M, B, A)

232 (B, A)

Ov F Lvl

268 (M, B, A)

C-N

233 (B, A)

Ov F Dly

269 (M, B, A)

234 (B, A)

Ov A Lvl

270 (M, B, A)

Ov A Dly

271 (M, B, A)

236 (B, A)

Un F Lvl

272 (M, B, A)

Real Demand

237 (B, A)

Un F Dly

273 (M, B, A)

Max Real Demand

238 (B, A)

Un A Lvl

274 (M, B, A)

239 (B, A)

Un A Dly

275 (M, B, A)

Ov F Lvl

276 (M, B, A)

Ov F Dly

277 (M, B, A)

231 (B, A)

235 (B, A)

240 (B, A)
241 (B, A)

Motor

+MVAR

MVA

A-N
Volts Phase

Real Power

B-N

B
C

A
Reactive Power

B
C

Reactive Power

M, B, A = Access Level; see Parameter Access Level using the HIM. The "+" for MVAR indicates power consumed.

180

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Table 77 - SMC-50 Parameter Linear List Parameter 278 - 333


Number
278 (M, B, A)
Reactive Energy
279 (M, B, A)
280 (B, A)

Number

Name

307 (A)

SS Ref Gain

308 (A)

SS Trans Gain

Name

Reactive Energy

309 (M, B, A) Input Status

281 (M, B, A) Reactive Demand

310 (B, A)

282 (M, B, A) Max Reactive Demand

311 (B, A)

283 (M, B, A)

284 (M, B, A) Apparent Power

285 (M, B, A)

Locked Rotor

312 (A)

Product Command

313 (B, A)

Rebalance Level

A Lvl
A Dly

286 (M, B, A) Apparent Power

314 (M, B, A)

287 (M, B, A) Apparent Energy

315 (M, B, A) Peak Voltage

288 (M, B, A) Apparent Demand

316 (M, B, A)

289 (M, B, A)

Max Apparent Demand

317 (M, B, A)

290 (B, A)

Demand Period

318 (M, B, A) Peak Current

291 (B, A)

Number of Periods

319 (M, B, A)

292 (M, B, A)

320 (M, B, A)

Phase A-B Voltage

293 (M, B, A) Power Factor

321 (M, B, A)

Phase B-C Voltage

294 (M, B, A)

322 (M, B, A)

Phase C-A Voltage

295 (M, B, A) Current Imbal

323 (M, B, A)

Phase A Current

296 (M, B, A) Voltage Unbal

324 (M, B, A)

Phase B Current
Phase C Current

297 (B, A)

Ov F Lvl

325 (M, B, A)

298 (B, A)

Ov F Dly

326 (M, B, A)

299 (B, A)

Ov A Lvl

327 (M, B, A)

Ov A Dly

328 (M, B, A)

Motor Speed

Un F Lvl

329 (M, B, A)

THD Voltage Average

302 (B, A)

Un F Dly

330 (M, B, A)

THD Current Average

303 (B, A)

Un A Lvl

331 (M, B, A)

Product Status

304 (B, A)

Un A Dly

332 (M, B, A)

Board Temp
Line Frequency

300 (B, A)
301 (B, A)

-MVAR

Snap Shot

305 (B, A)

Starting Torque

333 (M, B, A)

306 (B, A)

Starting Torque 2

334 (M, B, A) Restart Auto

307 (A)

SS Ref Gain

Power Factor
Motor Thermal Usage

M, B, A = Access Level; see Parameter Access Level using the HIM. The "-" for MVAR indicates power generated.
C=Consumed. P=Produced

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

181

Chapter 5

Programming

Table 78 - SMC-50 Parameter Linear List Parameter 334 - 346


Number

Name

335 (M, B, A)

DLX Input 1

336 (M, B, A)

DLX Input 2

337 (M, B, A)

DLX DL Input 1

338(M, B, A)

DLX DL Input 2

339 (M, B, A)

DLX DL Input 3

340 (M, B, A)
341 (M, B, A)

DeviceLogix

DLX DL Input 4
DLX DL Input 5

342 (M, B, A)

DLX DL Input 6

343 (M, B, A)

DLX Output 1

344 (M, B, A)

DLX Output 2

345 (M, B, A)

DLX Command

346 (M, B, A)

DLX Status

M, B, A = Access Level; see Parameter Access Level using the HIM.

SMC-50 Option Module


Configuration

Basic Configuration using the HIM


When an SMC-50 Option Module is plugged into one of the three available
ports (07, 08, or 09), the option module may require parameter configuration.
The option module parameters are resident in the option module through one of
the controller ports (07, 08, or 09) and are not included in the SMC-50
Controller (Port <00>) parameter list.
Perform the following steps to access the option module parameters using the
HIM.
NOTE:

Before proceeding with these steps: Take note of the SMC-50 port number (07,
08, or 09) that the option module is connected to.

1. Press the FOLDERS single function key.

182

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

2. Use the forward or back arrow until the PORTS folder screen is displayed.

Allen-Bradley
Stopped
0 Amps

AUTO
F

PORTS
09

ESC

00
02
03
09

SMC-50
20-HIM-x6
1203-USB
SMC-50 Option

3. Use the up or down arrow until the noted port number of the option
module is displayed. The HIM will display the HOST PARM file screen
and indicate the option module port controller number below the AB
logo.
Ensure the correct port
number is displayed
before modifying the
option module parameter.

Allen-Bradley
Stopped
0 Amps

AUTO
F

HOST PARAM

09

Linear List
File-Group
Changed Parameters

ESC

4. Ensure the correct port number is displayed, then configure the parameters
using either the Linear List or File-Group selection.

NOTE:

Parameters can be restored to factory defaults using its respective Parameter


Management parameter or the Set Defaults function from the HIMs memory screen.
Ensure the correct port number of the device to be restored is displayed before
restoring.

For additional information using the FOLDERS function of the HIM, see the
20-HIM-A6 User Manual, publication 20HIM-UM001.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

183

Chapter 5

Programming

150-SM4 Digital I/O Option Module


In addition to the SMC-50 two on-board 24V DC input and two auxiliary relay
outputs, the 150-SM4 Digital I/O Option Module has four 120...240V AC
inputs and three auxiliary relay outputs. These inputs and outputs can be used for
control functions.

Configure 120...240V AC Inputs


NOTE:

Before proceeding with the following steps, perform the steps 1 through 4 in Basic
Configuration using the HIM on page 182.

1. From the File-Group screen, press ENTER (number 5 on the keypad).


The four inputs are displayed.
Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 09
FILE
GROUP
Input1
Input2
Input3

ESC

Param File-Group

Inputs
Inputs

PROPERTIES

ENTER

2. Use the up or down arrow to select the input, then press ENTER (number
5 on the keypad). The display will show the current setting of the input.
3. Press the EDIT soft key to change the selected input function.
4. Use the up or down arrow to select the desired function (e.g., Start, Stop,
Coast, Slow Speed, etc.), then press the ENTER soft key to load the
selection. If necessary, use the back arrow to return to the previous
selection.
NOTE:

For a complete list of 150-SM4 parameters, see the Digital I/O Option Module
Parameter List on page 186.

For additional information using the FILE GROUP function of the HIM, see
the 20-HIM-A6 User Manual, publication 20HIM-UM001.

184

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

Configure Auxiliary Relay Outputs


NOTE:

Before proceeding with the following steps, perform the steps 1 through 4 in Basic
Configuration using the HIM on page 182.

1. Use the up or down arrow to select the one of the Aux Outputs, then press
ENTER (number 5 on the keypad).
Allen-Bradley
AUTO

Stopped
0 Amps

Port 09
FILE
GROUP
GROUP
GROUP

Param File-Group

Outputs
Aux 1
Aux 2
Aux 3

PROPERTIES

ESC

2. Select one of the four configuration options (Aux X Config, Aux X Invert,
Aux X On Delay, or Aux X Off Delay), then press ENTER (keypad or soft
key).
3. Modify the auxiliary relay output as desired. If necessary, use the back
arrow to return to the previous selection.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

185

Chapter 5

Programming

Digital I/O Option Module Parameter List


The allowable selections for the 150-SM4 are listed below.
Parameter
Number

Name

Min/Max
[default]
Bit 0 = Module
Ready/Disabled
Bit 1 = Input 1
Status
Bit 2 = Input 2
Status
Bit 3 = Input 3
Status
[Disable]
Start
Coast
Stop Option
Start/Coast
Start/Stop
Slow Speed

Bit 4 = Input 4
Status
Bit 5 = Aux 1 Status
R
Bit 6 = Aux 2 Status
Bit 7 = Aux 3 Status

X.1

Module
Status

X.2
X.3
X.4

Input 1
Input 2
Input 3

X.5

Input 4

X.6

Aux 1 Config

X.7
X.8
X.9

Aux 1 Invert
Aux 1 On Delay
Aux 1 Off Delay

X.10

Aux 2 Config

X.11
X.12
X.13

Aux 2 Invert
Aux 2 On Delay
Aux 2 Off Delay

X.14

Aux 3 Config

X.15
X.16
X.17

Aux 3 Invert
Aux 3 On Delay
Aux 3 Off Delay
Parameter
[Ready] Factory Default
Mgmt

X.18

Access

Dual Ramp
OL Select
Fault
Fault NC
Clear Fault
Emerg Run
Motor Heater
DeviceLogix
[Normal]
UTS (Up-to-Speed) Aux Control
Fault
Network 1
Alarm
Network 2
Ext Bypass
Network 3
Ext Brake
Network 4
[Disable] Enable
[0.0]-10.0
[0.0]-10.0
DeviceLogix
[Normal]
UTS (Up-to-Speed) Aux Control
Fault
Network 1
Alarm
Network 2
Ext Bypass
Network 3
Ext Brake
Network 4
[Disable] Enable
[0.0]-10.0
[0.0]-10.0
DeviceLogix
[Normal]
UTS (Up-to-Speed) Aux Control
Fault
Network 1
Alarm
Network 2
Ext Bypass
Network 3
Ext Brake
Network 4
[Disable]
Enable
[0.0]-10.0
[0.0]-10.0

Units

0 = Disabled
OFF
1 = Enabled
ON

R/W

NA

R/W

NA

R/W
R/W
R/W

seconds
seconds

R/W

NA

R/W
R/W
R/W

NA
seconds
seconds

R/W

NA

R/W
R/W
R/W

NA
seconds
seconds

R/W

NA

"X" indicates the port number (07, 08, or 09) the 150-SM4 is connected to the SMC-50. This port

number is displayed on the HIM screen below the AB brand logo.


An auxiliary output configured for Aux Control using the AuxX Config parameter will be under
control of its associated bit form the AuxControl, Parameter 180. See 150-SM6 PCM Information on
page 276 in Appendix B for bit assignments. This function enables forcing an output, ON or OFF.

186

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

150-SM6 Parameter Configuration Option Module


The 150-SM6 Parameter Configuration Option Module is used to configure a
select group of parameters. The option module itself requires no user
configuration. The option module status and switch positions that configure its
select parameters can be read using the HIM or PC software.
NOTE:

Only one 150-SM6 is allowed per SMC-50.

To read the 150-SM6 switch positions, follow the steps in Basic Configuration
using the HIM on page 182. When Linear List is selected, use the up or down
arrow to view the module switch positions.
Allen-Bradley
AUTO

Stopped
0 Amps

Port 08

Host Param

Rotary SwitchPROPERTIES
1
ESC

PAR #

The following table provides the parameter detail of the 150-SM6.


Parameter
Number

Name

Min./Max.
[Default]

X.1

Module Status

Ready

X.2

Rotary Switch 1 (Initial Torque)

X.3

Rotary Switch 2 (Current Limit)

X.4

Rotary Switch 3 (Ramp Time)

X.5

Rotary Switch 4 (Stop Time)

X.6

Rotary Switch 5 (Motor FLC)


Device Config
Protect Config
I/O Config

X.7
X.8
X.9

Access Units
1=Ready
R
0=Disabled

0.0...15.0

0...1.5=0...F

0.0...255.0

R/W

Bit Numbered

"X" indicates the SMC-50s port number (07, 08, or 09) that the 150-SM6 is connected to. This
port number is displayed on the HIM screen below the AB brand logo.
For 150-SM6: Rotary Switch 1 = S1, Rotary Switch 2 = S2, etc. Rotary switch positions equal 1 to
F. As displayed on the HIM, A=10, B=11, C=12, etc.
Bit 0 and 1 values represent the ON/OFF switch positions within the associated switch bank (e.g.,
Device Config) where 0=OFF and 1=ON.
NOTE: Switch #1=Bit 0, Switch #2=Bit 1, etc. as displayed on the HIM.

For switch setting details, see Table 63 through Table 67 beginning on page 140.
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

187

Chapter 5

Programming

150-SM2 PTC, Ground Fault, & External Current Transformer


Module
The 150-SM2 Option Module provides simultaneous interface capability to
three different types of external sensing devices which can be used by the
SMC-50 for certain application conditions. When installing the 150-SM2 into
the SMC-50, the following installation requirements must be followed:
Only one 150-SM2 can be installed in one SMC-50.
The 150-SM2 must reside in port 7 or 8 only. DO NOT use port 9 with
the 150-SM2.
When the external CT function is enabled through the 150-SM2 CT
Enable Bit, the external CT is calibrated by the SMC-50 for scaling, phase
shift, and inversion. The calibration cycle will automatically occur:
before the first START occurs after the 150-SM2 installation and when
the CT Enable, Parameter X.12, = Enable,
after a Load Defaults occurs, and
when the user forces tuning of the SMC-50 through the Force Tuning,
Parameter 194, or the HOLD TO TEST button on the SMC-50 is
held for > 10 seconds when stopped.
To configure the 150-SM2, follow the steps in Basic Configuration using the
HIM on page 182 then proceed with the steps below.
Allen-Bradley
Stopped
0 Amps

Port 07

FILE

AUTO

Param File-Group

Linear List
PROPERTIES

GROUP L i n e a r L i s t
Module Status
Fault Enable
Alarm Enable

ESC

ENTER

1. Using the File-Group selection, press ENTER (number 5 on the keypad)


until the Group Linear List is displayed.
2. Use the up or down arrow to scroll to the desired parameter, then press
ENTER.
If the parameter is bit configured (e.g., Fault Enable):
a. Use the left or right arrow to move to the bit location that needs to be
modified. The bit function is displayed at the bottom of the screen.
b. Press EDIT to move to the edit screen.

188

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Programming

Chapter 5

c. Change the bit assignment, then press EDIT.


If the parameter is not bit configured (e.g., Turns Ratio):
a. Press the EDIT.
b. Change the value within the displayed limits, then press ENTER to
load the parameter contents into memory.
Allen-Bradley
AUTO

Stopped
0 Amps

Port 07

Host Param

Fault Enable PROPERTIES

xxxx xxxx xxxx xx00


Bit

01

Ground Fault

ESC

PAR #

EDIT

The following table provides the parameter detail of the 150-SM2.


Parameter
Number

Name

X.1

Module Status

X.2
X.3
X.4
X.5

Fault Enable
Alarm Enable
Restart Enable
Turns Ratio

X.6

Ground Fault Level


Ground Fault Delay
Ground Fault A Level
Ground Fault A Delay

X.7
X.8
X.9
X.10
X.11
X.12
X.13
X.14
X.15

Min/Max
[default]
Bit 0 = Module Ready
Bit 1 = PTC
Bit 2 = CT Loss

Access Units
R

Bit = 0 Disable
Bit = 1 Enable

Bit 0 = PTC
Bit 1 = Ground Fault

R/W

Bit = 0 Disable
Bit = 1 Enable

100-2000 [1000]

R/W

NA

0.005.00 [2.5]
0.1250.0 [0.5]
0.005.00 [2.5]
0.1250.0 [0.5]
Ground Fault Inh Time 0.0250.0 [10.0]
Ground Current
[0.00]5.00
CT Enable
[Disable] Enable
CT Scaling A
CT Scaling B
0.105.00 [1.00]
CT Scaling C

R/W
R/W
R/W
R/W
R/W
R
R/W

Amps
Seconds
Amps
Seconds
Seconds
Amps
NA

NA

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

189

Chapter 5

Programming

Parameter
Number
X.16
X.17
X.18
X.19

Name
Phase Shift A
Phase Shift B
Phase Shift C
Parameter Mgmt

Min/Max
[default]

Access Units

-12.5012.50 [0.00]

[Ready] Factory Default R/W

Degree
NA

"X" indicates the port number (07, 08, or 09) the 150-SM4 is connected to the SMC-50. This
port number is displayed on the HIM screen below the AB brand logo.
The sensing range of the module.
Inhibit Time provides the ability to inhibit (disable) ground fault protection for the time
selected during starting.
Configure Turns Ratio to the value of the Ground Fault sensor CT Turns Ratio (e.g.,
825-CBCT=100:1 Set X.5 to 100.

190

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Metering

Overview

While the SMC-50 operates a motor, it is also monitoring several different


parameters to provide a full-function metering package.

Viewing Metering Data

To access the metering information using the 20-HIM-A6, follow the procedure
below using the keypad.
1. From the SMC-50 standard power-up screen, select FOLDERS.
2. Use the right or left arrow until the Port 00 DEV PARAM screen is
displayed.
NOTE: Ensure the Advanced Access Level is selected, located at the bottom of the
DEV PARAM screen. For additional configuration details, see Parameter
Access Level Modification Using the HIM on page 149 in Chapter 5.

3. From the Port 00 DEV PARAM screen, select File-Group, then press the
ENTER key (number 5 on the keypad). The Port 00 Param File-Group
screen will appear.
4. Use the up or down Arrow key to select File Monitoring. The Port 00
Param File-Group File Monitoring screen will appear with seven GROUP
metering selections (Metering Basics, Metering Volts, Metering Current,
Metering Power, Start Stats. Monitoring, Power Quality).
Allen-Bradley
Stopped
0 Amps

Port 00
FILE
FILE
FILE
FILE
FILE

Allen-Bradley
AUTO
F

Param File-Group

MonitoringPROPERTIES
Set Up
Motor Protection
Communications
Utility

ESC

AUTO
F

Stopped
0 Amps

Port 00
FILE
GROUP
GROUP
GROUP
GROUP

Param File-Group

MonitoringPROPERTIES
Metering Power
Start Stats
Monitoring
Power Quality

ESC

5. Use the up or down arrow key to select the desired GROUP, then press the
ENTER key (number 5 on the keypad).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

191

Chapter 6

Metering

6. Select the desired parameter from the previous group selected, then press
the ENTER key to monitor the metering parameter.
NOTE: With the exception of the Meter Reset, Parameter 16, the metering
parameters contained in the Monitoring File-Group are Read (R) only. See
Metering on page 10 in Chapter 1 and Metering Parameters on page 192 in
this chapter for a detailed list of metering parameters.

Resetting Metering Parameters


Meter Reset, Parameter 16, is used to clear (reset to 0) the contents of metering
parameters Elapsed Time, Energy, Time to PM (Preventative Maintenance), and
Starts to PM. To clear the contents of any one of these parameters, configure
Meter Reset to the specific parameter you wish to clear.
EXAMPLE

To clear (reset to 0) the Elapsed Time, configure Meter Reset to Elapsed


Time. The controller will then clear the Elapsed Time and the value of
Meter Reset will return to Ready 0.

To access Meter Reset using the 20-HIM-A6, perform steps 1 through 4, Viewing
Metering Data, beginning on page 191.
1. From Step 4, select the Metering Basic Group, then press ENTER
(number 5 on the keypad).
2. Use the down arrow on the keypad to select/highlight Meter Reset.
3. With Meter Reset highlighted, press the ENTER key (number 5 on the
keypad) or the ENTER soft key.
4. Press the EDIT soft key.
5. Use the up or down arrow to select the desired parameter (Elapsed Time,
Energy, Time to PM, or Starts to PM) to be reset, then press the soft
ENTER soft key. The selected parameter will be reset to zero with the
exception of the Starts to PM.
NOTE:

Metering Parameters

When the ENTER key is pressed and Starts to PM is selected, its contents will
be set to the value contained in PM Starts, Parameter 127.

Current
The SMC-50 calculates true RMS current based on Current Transformer (CT)
feedback for all three phases. In addition, an average value of the three phase
currents is calculated. During Braking and Slow Speed operation, the calculated
current is estimated based on time and current settings.
The accuracy of the current calculation is +/-5% of the true RMS current.

192

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Metering

Chapter 6

Table 79 - Metering Parameters Associated with Current


Parameter Number
5
6
7
8

Name/Description Min/Max [Default] Access Units


Current Average
Current Phase A
[0]...15,000
R
Amps
Current Phase B
Current Phase C

Voltage
Line-to-Line and Line-to-Neutral RMS voltage is calculated for all three phases
with the average of the three voltages also provided. The data is provided
whenever 3-phase power is applied.
The accuracy of the voltage calculations will be +/-2% of the true RMS voltage.
Table 80 - Metering Parameters Associated with Voltage
Parameter Number
1
2
3
4
265
266
267
268

Name/Description Min/Max [Default] Access Units


Voltage P-P Average
Volts Phase A-B
[0]...700
R
Volts
Volts Phase B-C
Volts Phase C-A
Voltage P-N Average
Volts Phase A-N
[0]....450
R
Volts
Volts Phase B-N
Volts Phase C-N

Torque
The SMC-50 calculates true electromechanical torque based on the existing
motor voltage and current feedback data.
NOTE:

1 During Braking and Slow Speed operations, Torque will read 0.


2 In order for the Torque parameter to display correctly, the motor value for
Rated Torque, Parameter 47, and Rated Speed, Parameter 48, must be
correctly configured.

The accuracy of the torque calculations is +/-10% of the true electromechanical


torque.
Table 81 - Metering Parameters Associated with Torque
Parameter Number Name/Description Min/Max [Default] Access Units
9
Torque
-50...300 [0]
R
%

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

193

Chapter 6

Metering

Power
Real, Reactive, and Apparent power calculations (along with demand and
maximum demand) are made on each line power phase along with a total for all
three phases.
The Energy parameters can be cleared using the Meter Reset parameter. See
Resetting Metering Parameters on page 192 for further details.
NOTE:

For Reactive Energy, Parameter 278 and 279, the system will keep a:
positive energy, which only integrates power when it is positive,
negative energy, which only integrates power when it is negative, and
net energy, which always integrates.

The demand numbers are calculated as follows:


Energy is calculated over a period of time defined by "Demand Period",
Parameter 290.
The previous "n" period values are averaged and the result is written to the
Demand, Parameter 272, 281 and 288, which is used in calculating the
Max Demand values. This averaging uses a rolling window algorithm
where the previous "n" periods are averaged.
Table 82 - Metering Parameters Associated with Power
Parameter Number
269
270
271
10
11
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289

194

Name/Description
Real Power A
Real Power B
Real Power C
Real Power
Real Energy
Real Demand
Max Real Demand
Reactive Power A
Reactive Power B
Reactive Power C
Reactive Power
Reactive Energy C
Reactive Energy P
Reactive Energy
Reactive Demand
Max. Reactive Dmd
Apparent Power A
Apparent Power B
Apparent Power C
Apparent Power
Apparent Energy
Apparent Demand
Max. Apparent Demand

Min/Max [Default]

Access Units

+/- 1000.000 [0.000]

MW

+/- 1000.000 [0.000]

MWH

+/- 1000.000 [0.000]

MW

+/- 1000.000 [0.000]

MVAR

1000.000 [0.000]

MVRH

+/- 1000.000 [0.000]

MVRH

+/- 1000.000 [0.000]

MVAR

MVA
+/- 1000.000 [0.000]

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R
MVAH
MVA
MVA

Metering

Parameter Number Name/Description


290
Demand Period
291
Number of Periods

Min/Max [Default]
[1]...255
[1]...15

Chapter 6

Access Units
R/W
min
R/W

M = Mega

Power Factor
Power Factor is calculated for each phase along with a total power factor value.
The power factor calculation does not apply during Slow Speed and Braking
operations.
Table 83 - Metering Parameters Associated with Power Factor
Parameter Number
292
293
294
17

Name/Description Min/Max [Default] Access Units


Power Factor A
Power Factor B
-1.00...1.00 [0.00]
R
NA
Power Factor C
Power Factor

Energy Savings
The energy saver function only applies during light motor load situations at
which time the SMC-50 reduces current to the motor and thereby saves energy.
When in energy saver operation, the Energy Savings status bit is set. In addition,
Energy Savings, Parameter 15, indicates the percentage energy savings.
Parameter 17 - [Power Factor] should be monitored and recorded when the
motor is running at no/light load and at full/heavy load. The power factor value
where the controller enters Energy Saver mode is determined by setting
Parameter 193 - [Energy Saver] to a value between the no/light load and
full/heavy load recorded values.
Table 84 - Energy Saver Mode Parameter List
Parameter Number Parameter Name Minimum/Maximum [Default] Access Units
15

Energy Savings

0100

17

Power Factor

-1.001.00

193

Energy Saver

[0.00]-1.00

R/W

NOTE:

Set Parameter 193 = 0 to disable Energy Saver mode.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

195

Chapter 6

Metering

Elapsed Time
The SMC-50 keeps a log of the total accumulated hours the controlled motor has
been running via the Elapsed Time metering parameter. The Elapsed Time meter
value is updated every 10 minutes and stored at power down (accurate to 1/6 of
an hour). The Elapsed Time meter accumulates to 50,000 hours of operation and
can be reset to zero via the Meter Reset parameter (see Resetting Metering
Parameters on page 192).
Elapsed Time 2 is similar to Elapsed Time. Elapsed Time 2 differs in that it
cannot be reset by the user and will count up to 50,000 hours and then hold that
value (it will not roll over).
Table 85 - Metering Parameters Associated with Elapsed Time
Parameter Number Name/Description Min/Max [Default] Access Units
12
Elapsed Time
R/W
[0.0]...50000.0
Hours
13
Elapsed Time 2
R

Running Time
The Running Time meter parameter logs the amount of time the motor has been
operating. The timer resets to zero and begins counting as each start command is
received.
NOTE:

When the SMC-50 is stopped, the parameter displays the length of time the
motor was previously operating.

Table 86 - Metering Parameters Associated with Running Time


Parameter Number Name/Description Min/Max [Default] Access Units
14
Running Time
[0.0]...5000.0
R
Hours

Motor Speed
The Motor Speed meter parameter is only valid when using the Linear Speed
Starting or Linear Speed Stopping modes. It provides the estimated motor speed
during either the starting or stopping maneuver. When the SMC-50 is not in
these modes, the Motor Speed meter parameter reads zero except when the unit is
at speed. In this case, the parameter displays 100%.
Table 87 - Metering Parameters Associated with Motor Speed
Parameter Number Name/Description Min/Max [Default] Access Units
34
Motor Speed
[0]...100
R
%

196

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Metering

Chapter 6

Actual Start Time


The SMC-50 logs the start time of the last five motor starts and stores that
information in Parameters 24 through 28. The start time data is stored in a
first-in, first-out method so the record of the last five starts is always maintained.
Table 88 - Metering Parameters Associated with Actual Start Time
Parameter Number
24
25
26
27
28

Name/Description Min/Max [Default] Access Units


Start Time 1
Start Time 2
Start Time 3
[0]...1000
R
Seconds
Start Time 4
Start Time 5

Peak Start Current


The SMC-50 logs the peak average RMS current during each start and stores that
information in Parameters 29 through 33. The Peak Start Current data is stored
in a first-in, first-out method so the record of the last five starts is always
maintained.
Table 89 - Metering Parameters Associated with Peak Start Current
Parameter Number
29
30
31
32
33

Name/Description Min/Max [Default] Access Units


Peak Current 1
Peak Current 2
Peak Current 3
[0]...15,000
R
Amps
Peak Current 4
Peak Current 5

Total Starts
The SMC-50 maintains a Total Start counter which is incremented each time the
controller is started. As shipped, the counter value is zero. It cannot be reset by
the user.
NOTE:

The Total Starts counter is not incremented if the controller faults on a


pre-start fault. It is incremented once SCR gating begins.

Table 90 - Metering Parameters Associated with Total Starts


Parameter Number Name/Description Min/Max [Default] Access Units
23
Total Starts
[0]...30,000
R
NA

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

197

Chapter 6

Metering

Total Harmonic Distortion (THD)


The SMC-50 provides the IEEE calculated THD value for the three Line
Voltages (Line-to-Neutral) and the three Motor Phase Currents (current through
SMC-50 Power Pole ). In addition, the average THD is calculated for both
Line Voltage and Phase Current.
The controller algorithm uses a round-robin approach to gather the six signals by
sampling one signal and then calculating the THD value for that signal. In other
words, each power cycle current and voltage THD are calculated for a phase, then
for the next phase and so on.
NOTE:

When the motor is not running, the Current-Based THD values will read 0.

When in external bypass running mode/configuration, an external CT (825-MCM)


and a 150-SM2 Option Module can be used to read current-based (THD Ix) values.

Table 91 - Metering Parameters Associated with THD


Parameter Number Name/Description Min/Max [Default] Access Units
THD Va
35
36

THD Vb

37

THD Vc

38

THD V ave

39

THD Ia

40

THD Ib

41

THD Ic

42

THD I ave

[0.0]...1000.0

[0.0]...1000.0

Line Frequency
The SMC-50 measures and displays the system 3-phase AC Line Frequency.
Upon power up, the Line Frequency parameter displays zero until a valid AC
Line Frequency is measured. When three-phase power is removed from the
SMC-50, the parameter maintains the value of the previous frequency reading.
Table 92 - Metering Parameters Associated with Line Frequency
Parameter Number Name/Description Min/Max [Default] Access Units
224
Line Frequency
[0]...100
R
Hz

Current Imbalance
The SMC-50 provides a calculated Current Imbalance value. The Current
Imbalance calculation is equal to the largest deviation of the three RMS phase
198

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Metering

Chapter 6

current signals from the average RMS phase current, divided by the average. Note
that the SMC-50 Power Pole Current is used for the Current Imbalance
calculation.
Table 93 - Metering Parameters Associated with Current Imbalance
Parameter Number Name/Description Min/Max [Default] Access Units
295
Current Imbalance
[0]...100
R
%

Voltage Unbalance
The SMC-50 provides a calculated Voltage Unbalance value. The Voltage
Unbalance calculation is equal to the largest deviation of the three RMS phase
voltage signals from the average RMS phase voltage divided by the average. Note
that the phase-to-neutral voltage is used in the calculation for voltage unbalance.
Table 94 - Metering Parameters Associated with Voltage Unbalance
Parameter Number Name/Description Min/Max [Default] Access Units
296
Voltage Unbalance
[0]...100
R
%

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

199

Chapter 6

200

Metering

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Optional HIM Operation

Overview

The SMC-50 offers a variety of unique control options that provide enhanced
motor starting and stopping capabilities.

HIM Control Buttons

The control buttons available with the Bulletin 20-HIM-A6 LCD modules are
compatible with the SMC-50s control options. The following table details the
functionality of each control button with regards to each option.
IMPORTANT

The logic mask port must be enabled prior to initiating control commands
except for Stop, which will always initiate a Coast-to-Stop to the
SMC-50. See Chapter 8, Control Enable on page 207 for instructions.
The control terminals must be wired according to Figure 35 on page 54 or
Figure 46 on page 65 in Chapter 2, Installation & Wiring.

Figure 92 - 20-HIM-A6 Control Button Functionality


Option
Standard

Action

Operation When Pressed


The green start button will commence motor acceleration
to full speed.

Soft Stop
Current Limit
Full Voltage
Linear Speed

The red stop button will provide a coast stop, and/or


reset a fault.
This button will bring up the Control Screen to enable the
stop option maneuver. See the HIM Control Screen
section on page 203.
The green start button, when pressed, will commence
motor acceleration to full speed.

Preset Slow Speed

The red stop button, when pressed, will provide a coast


stop and/or reset a fault.
This button will display the Control screen.
* Slow Speed cannot be operated via the HIM.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

201

Chapter 7

Optional HIM Operation

Option
Pump Control

Action

Operation When Pressed


The green start button will commence motor
acceleration to full speed.
The red stop button will provide a coast stop, and/or
reset a fault.

Pump Control

Displays the Control Screen with the Jog button. The


jog button will initiate a pump stop maneuver.
Braking Control
The green start button will commence motor
acceleration to full speed.
Smart Motor Braking

The red stop button will provide a coast stop, and/or


reset a fault.
Displays the Control Screen with the Jog button. The
jog button will initiate a brake stop.
The green start button will commence motor
acceleration to full speed.
The red stop button will provide a coast stop, and/or
reset a fault.

Accu-Stop

Displays the Control Screen with the Jog button. The


jog button will initiate braking to slow speed operation.
The controller will maintain slow speed operation as
long as the jog button is pressed.
The green start button will commence motor
acceleration to full speed.
Slow Speed with
Braking

The red stop button will provide a coast stop, and/or


reset a fault.
Displays the Control Screen with the Jog button. The
jog button will initiate a brake stop from slow speed.
* Slow Speed cannot be operated via the HIM.

Accu-Stop is not included as a parameter/function as the SMC-Flex was. However, Accu-Stop is accomplished with the
Stop option and the Slow Speed with Braking.

NOTE:

For additional details on using the 20-HIM-A6, see the 20-HIM-A6 User
Manual, publication 20HIM-UM001.
ATTENTION: The Bulletin 20-HIM-A6 LCD modules stop push button is
not intended to be used as an emergency stop. See applicable standards
for emergency stop requirements.

202

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Optional HIM Operation

Chapter 7

HIM Control Screen


The HIM Control Screen is typically used to directly control a drive. Press the
(controls) key to display the Control Screen.
IMPORTANT

To navigate from the Control Screen to another HIM menu screen, the
ESC soft key must be pressed. This deactivates the Control Screen and
displays the previous screen.

Figure 93 - HIM Control Screen


Control Screen Navigation
Number Keys

Control Screens Key Function

Allen-Bradley

7
AUTO
F

Stopped
0 Amps
REMOVE
HIM
REF FBK

ESC

REV
JOG

REF

REF

FWD

MANUAL
PROPERTIES
EDIT
REF

6
3

HELP

NOTE: The Control Screens Key Function


map coorespond with the Control Screen
Navigation/Number keys on the HIM.

Table 95 - Control Screen Soft Key Functionality


Label
ESC

Name
Escape

Function
Reverts back to the previous screen.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

203

Chapter 7

Optional HIM Operation

Table 96 - Control Screen Navigation/Number Keys


Label

Name

Function

JOG

Stop Option for SMC-50

REF

82

NA

HELP

Displays Rockwell Automation Drives Technical Support direct phone


number, website address, and email address.

REV

EDIT REF

NA

NA

FWD 

NA

REMOVE HIM

Allows HIM removal without causing a fault if the HIM is not the last
controlling device. The REMOVE HIM label is not available when the HIM
has a manual control of the host SMC-50. In this case, a fault will occur if
the HIM is removed.

REF

88

NA

MANUAL

NA

Technical Support is not applicable to the SMC-50. Technical Support for the SMC-50 may be reached at:
440-646-5800 (option 2 and option 4) or raictechsupport@ra.rockwell.com.

CopyCat Function of the 20-HIM-A6


The SMC-50 supports the CopyCat function of the 20-HIM-A6. For details on
using the CopyCat function, see the 20-HIM-A6 User Manual,
20HIM-UM001_EN-P.

204

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Communications

Overview

The SMC-50 provides advanced communications capabilities that allow it to be


started and stopped from multiple sources as well as provide diagnostic
information through the use of communication interfaces. The SMC-50 uses
DPI as an internal method of communication bus, therefore all standard DPI
communication interfaces used by other devices (e.g., PowerFlex Drives) can be
used in the SMC-50. ScanPort devices are not supported by the SMC-50.
Standard DPI communications cards are available for various protocols including
DeviceNet, ControlNet, ModBus, and Profibus DP. Other modules may be
available in the future. For specific programming examples, configuration, or
programming information, see the user manual for the communication module
being used. A list of available modules is shown below.
Table 97 - Communication Card Selection by Protocol Type
Protocol Type
DeviceNet
ControlNet
Profibus
RS-485
InterBus
EtherNet/IP
Dual Port EtherNet/IP
RS485 HVAC
ControlNet (Fiber)
CANopen

Cat. No.
20-COMM-D
20-COMM-C
20-COMM-P
20-COMM-S
20-COMM-I
20-COMM-E
20-COMM-ER
20-COMM-H
20-COMM-Q
20-COMM-K

User Manual
20COMM-UM002
20COMM-UM003
20COMM-UM006
20COMM-UM005
20COMM-UM007
20COMM-UM010
20COMM-UM015
20COMM-UM009
20COMM-UM003
20COMM-UM012

Communication Ports

The SMC-50 supports four DPI ports for communication. Port 1 is for the front
mounted (bezel) Human Interface Module (HIM). Ports 2 and 3 are supported
through the serial connection on the top of the device and are typically used to
interface with a door mounted HIM or a PC. Port 2 is the default connection
with port 3 available by installing a splitter on port 2. DPI Port 4 is supported by
connecting one of the communication cards listed above in Table 97 to the
internal DPI communication card connection (SMC-50 hardware controller
port 9).

HIM Keypad & Displays

The SMC-50 can be programmed with the optional Bulletin 20-HIM-A6 LCD
display. Parameters are organized in a multi-level menu structure and divided into
programming groups.
Rockwell Automation Publication 150-UM011C-EN-P - March 2014

205

Chapter 8

Communications

Connecting the HIM to the Controller


Figure 94 shows how to connect a HIM and DPI device to the SMC-50.
Table 98 on page 206 provides a description of each port.
TIP The SMC-50 only supports the use of DPI communication modules and DPI
20-HIM-A6 Modules.

See the control wiring diagram that enables start-stop control from a HIM.
Figure 94 - SMC-50 with a HIM
SMC-50 Front View
HIM Bezel Port

SMC-50 Top View

DPI Port 2
(Port 2 & 3 with Splitter)

Table 98 - Description of Ports


DPI Port Number Source
1

Front-Mounted HIM (HIM Bezel)

Remote DPI (top of SMC-50)

Remote DPI (top of SMC-50 with splitter)

20-COMM-x Module

When using a 20-COMM-x network communication module, it must physically be located in control module
hardware port 9. However, its DPI Port Number assignment is 4. The cable connection for the DPI Port 4 is
located below the HIM bezel (see Figure 94).

206

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Communications

Control Enable

Chapter 8

Logic Mask, Parameter 148, allows the user to configure whether a


communication device (HIM or network connection) can perform motor
control commands such as starting. Each communication port (1 through 4) can
be enabled (bit= 1) or disabled (bit = 0) as required. When a given device is
enabled through the logic mask that device is allowed to execute control
commands. In addition, disconnecting any device with the logic mask enabled
will result in an Exp Removed (X026) communication fault. A device that is
disabled through the logic mask can be disconnected without causing a fault.
When a given device is disabled through the logic mask that device cannot execute control commands, but can
still be used for configuration and monitoring. X = DPI port number of the device causing the Fault.

If a 20-HIM-A6 is enabled for control via the Logic Mask, it can still be removed using the HIM control screen.
See Chapter 7, Optional HIM Operation.

IMPORTANT

Stop commands override all start commands and can be initiated from
the hardwired inputs or any DPI port regardless of the logic mask.

Logic Mask Enable/Disable using a HIM


To enable motor control using a connected HIM, follow the procedure below
with the connected HIMs programming keys.
The Bulletin 20-HIM-A6 provides start and stop control of the SMC-50.
However, the Logic Mask factory default settings disable control commands
other than Stop through the controllers DPI ports 1, 2, 3, or 4.
To enable motor control from either of the four ports using a connected
20-HIM-A6, the following steps must be performed from the SMC-50 standard
power-up screen.
1. Press the
key. Use the right or left arrow key on the keypad to
display the <00> DEV PARAM folder screen.
2. Select/highlight the File-Group.
3. Press the
appear.

(enter) key. The Port 00 Param File-Group screen will

NOTE: Ensure the Advanced Access Level is selected, located at the bottom of the
DEV PARAM screen. For additional configuration details, see Parameter
Access Level Modification Using the HIM on page 149 in Chapter 5.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

207

Chapter 8

Communications

4. Press the
to select FILE Communications, then press
GROUP Comm Masks and Data Links screen will appear.

. The

Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00

Allen-Bradley

Param File-Group

MonitoringPROPERTIES
Set Up
Motor Protection
Communications
Utility

FILE
FILE
FILE
FILE
FILE

AUTO
F

Stopped
0 Amps

Port 00
FILE

ESC

GROUP
GROUP

Param File-Group

Communications
PROPERTIES
Comm Masks
Data Links

ESC

5. With Comm Mask selected/highlighted, press the 5 key. The


GROUP Comm Masks screen will appear with the associated Logic Mask
Action selected.
6. Select/highlight Logic Mask, then press the
Mask screen with bit field will appear.

key. The Edit Logic

Allen-Bradley
AUTO
F

Stopped
0 Amps

Edit

Logic

Mask

PROPERTIES
x000 0000 0000 0000

Bit

ESC

02
ENTER

7. Press the EDIT key to modify the settings, then use the left or right arrow
to select the desired bit, 1 through 4, then press the

key.

To enable motor control, press 1 or press 0 to disable motor


control from the selected DPI port, then press EDIT.

208

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Communications

Chapter 8

Table 99 - Logic Mask & Logic Mask Active Parameter Specifications


Parameter
Number Name
148
Logic Mask

Bit Number
0 - NA
1
Logic Mask Act 2
3
4
5 - 15 NA

149

IMPORTANT

DPI Assignment Access Units [default]


Port 0 - NA
R/W
Bit = 0 [disabled]
Port 1
Bit = 1 enabled
Port 2
R
Bit = 0 [disabled]
Port 3
Bit = 1 enabled
Port 4
[Follows Logic Mask]
Port 5 - 15 NA

The Logic Mask must be set to 0 or the "REMOVE HIM" key is

depressed via the HIM controller screen (see Chapter 7) prior to


disconnecting the HIM from the SMC-50 controller. If not, the unit will
fault on a Exp. Removed.
The Logic Mask Active, Parameter 149, is a read-only parameter that
shows the logic mask actually in use at any given time. It typically
follows the Logic Mask, Parameter 148, except in some application
environments where network communication is in use.

Loss of Communication
with DPI Device

An "Exp. Removed" fault indicates a device was improperly removed. There is a


Fault code determined by port number.
DPI provides a separate Exp. fault for each port. This fault can be generated
directly by the peripheral and is separate from the Exp. Removed fault (device
specific).

Default Input/Output
Communication
Configuration

The default configuration for I/O communication is 4 bytes in and 4 bytes out
(TX = 4 bytes, RX = 4 bytes). The total size may very when used with a
communication card. The default configuration is arranged according to the
following table.
Table 100 - Default Configuration
Word Produced Data (Status)

Consumed Data (Control)

Logic Status

Logic Command

Feedback

Reference

The feedback word is always Ave Current.


The reference word is not used with the SMC-50, however the space must be reserved.
Variable Input/Output Configuration

TIP The total data size produced or consumed may vary, depending on the
communication card being used. For more information, see the User Manual of
the specific communication card being used with the SMC-50.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

209

Chapter 8

Communications

The SMC-50 supports 32-bit Data Links. Therefore, the device can be
configured to return additional information. The I/O message size depends on
how many DataLinks are enabled. The following table summarizes the I/O data
sizes.
Table 101 - I/O Data Sizes
DataLinks

Rx
Size

Tx
Size

Logic Status/Command Reference/FeedBack


(16-bit)
(16-bit)

12

12

20

20

28

28

36

36

A B C D

To configure DataLinks, see Configuring DataLink on page 212.

SMC-50 Bit
Identification

Product Functional (Logic) Status, Parameter 43, is used to provide SMC-50


functional (logic) status to communication devices. The following table details
Parameter 43, which is a read-only parameter.
Table 102 - Logic Status
Bit
Number Status/Function

210

Enabled/Ready

Running

2
3

Phasing
Phasing Active

Starting (Accel)

Stopping (Decel)

Alarm

Fault

At Speed

Start/Isolation

10
11
12-13
14
15

Bypass
Ready
Reserved
Input #1
Input #2

Description
1
Control Power Applied
Power applied to motor
(gating SCRs or bypass closed)
ABC phasing
Three-phase is valid
Performing a start maneuver
(slow speed not included)
Performing a stop maneuver
(coast to stop not included)
Alarm present
Fault condition exists and has
not been cleared
Full voltage applied
(bypass or full SCR conduction)
Start/Isolation contactor
enabled
Bypass contactor enabled
Ready to Run
Always 0
Control Module Input #1 Status
Control Module Input #2 Status

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

0
Control Power NOT applied
Power NOT applied to motor
CBA phasing
No valid three-phase detected
Not performing a start maneuver
Not performing a stop maneuver
No alarm present
No fault condition
No full voltage applied
Start/Isolation contactor disabled
Bypass contactor disabled
Control Inhibit Active (do not run)

Communications

Chapter 8

Table 103 - Logic Command Word (Control)


Bit
Number Control
0
1
2
3
4
5
6
7-10

Stop
Start
Jog
Clear Fault
Slow Speed
Emergency Run
Motor Winding Heater
Reserved

11

Aux Enable

12

Network #1

13

Network #2

14

Network #3

15

Network #4

Description
1

Coast/Inhibit
No action
Start
No action
Stop/Maneuver
No action
Clear fault
No action
Run at slow speed
No action
Enable emergency run mode
Disable emergency run mode
Enable motor winding heater
Disable motor winding heater
These bits must always be set to 0
Ignore the Network #1 - #4
Use the Network #1 - #4 bits
bits
Closes any output configured
Opens any output configured
for Network #1
for Network #1
Closes any output configured
Opens any output configured
for Network #2
for Network #2
Closes any output configured
Opens any output configured
for Network #3
for Network #3
Closes any output configured
Opens any output configured
for Network #4
for Network #4

Reference/Feedback

The SMC-50 does not offer the analog Reference feature. The analog Feedback
feature is supported and will provide Current Average, Parameter 5, automatically
as the feedback word.

Parameter Information

A complete listing of the SMC-50 parameters is located in Appendix B.

Scale Factors for PLC


Communication

The parameter values stored and produced by the SMC-50 through


communication are unscaled numbers. When reading or writing values from a
PLC image table, it is important to apply the proper scaling factor, which is based
on the number of decimal places.

Read Example
Power Factor, Parameter 17 The stored value is 85. Since this value has two
decimal places, the value should be divided by 100. The correctly read value is
0.85.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

211

Chapter 8

Communications

Write Example
Motor FLC, Parameter 78 The example value, which is to be written to the
SMC-50, is 75 A. Since this value has one decimal place, the value should be
multiplied by 10. The correctly written value is 750.

Display Text Unit


Equivalents

Some parameters have text descriptions when viewed from a HIM or through a
communication software program such as RSNetworx. When receiving or
sending information from a PLC each text description has a numerical
equivalent. The table below shows an example of Meter Reset, Parameter 16, and
the appropriate relationship between the text descriptor and the equivalent value.
This relationship is identical for other similar parameters located in Appendix B.
EXAMPLE

Configuring DataLink

Text Descriptor
Ready
Elapsed Time
Energy
Time to PM
Starts to PM

Numerical Equivalent
0
1
2
3
4

DataLink is supported in the SMC-50. DataLink is a mechanism used by most


drives to transfer data to and from the controller without using an explicit
message. The SMC-50 supports a 32-bit DataLink, therefore the device can be
configured to return up to eight additional pieces of information without the
need for an explicit message.

Criteria for Using DataLink


Each set of DataLink parameters in an SMC-50 can be used by only one
adapter. If more than one adapter is connected, multiple adapters must not
try to use the same DataLink.
Parameter settings (contents) in the SMC-50 determine the data passed
through the DataLink mechanism.
When DataLink is used to change a value in the SMC-50, the value is not
written to the Non-Volatile Storage (NVS). However, if the SMC-50 is
powered down, the current value is written to NVS.
To configure DataLink, Parameters 153168 of the SMC-50 must be used. See
Table 104 below for a detailed listing of these parameters. For additional
information regarding DataLink, see the communication interfaces user manual.

212

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Communications

Chapter 8

Table 104 - Parameter 153 - 168 DataLinks Detail


Parameter Number
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168

Description

Data In

Data Out

A1
A2
B1
B2
C1
C2
D1
D2
A1
A2
B1
B2
C1
C2
D1
D2

Min/Max [Default]

[0]-Max Parameter Number

Access Units

R/W

The data transferred via the DataLink function is the setting (content(s)) of the parameter number as entered by
the user here.

Updating Firmware

The latest version of firmware and instructions for the SMC-50 can be obtained
from www.ab.com.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

213

Chapter 8

214

Communications

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

Diagnostics

Overview

This chapter describes the fault diagnostics of the SMC-50. Further, this section
describes the conditions that cause various faults to occur.

Protection Programming

Many of the protective features available with the SMC-50 can be enabled and
adjusted through the programming parameters provided. For further details on
programming, see Motor Protection on page 172 in Chapter 5, Programming.

Diagnostic LEDs

The SMC-50 multi-color Diagnostic LED Status Indicator and HOLD TO


TEST, PUSH TO RESET button are located below the HIM bezel port. The
Status LED indicates the status and fault conditions of the SMC-50.
Table 105 - Corresponding LED Color and Fault Conditions
Status LED
Color

Device
Mode

SMC Status

Green

Running

Running without an alarm

Green/Amber

Running

Running with an alarm

Green Flashing

Ready

Ready (no inhibit and no fault) without an alarm

Amber/Flashing Ready

Ready (no inhibit and no fault) with tuning enabled on the next start

Amber

Ready

Ready with alarm (no tuning enabled)

Red/Amber

Inhibit

Inhibited; cannot start due to a Stop command

Red

Faulted

A non-resettable fault has occurred

Red/Flashing

Faulted

A resettable fault has occurred

Red/Green

Download

Firmware is being downloaded

The HOLD TO TEST, PUSH TO RESET button provides the ability to reset
an alarm/fault, test for a fault condition, and initiate the tuning mode.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

215

Chapter 9

Diagnostics

Table 106 - Function Initiation of the HOLD TO TEST, PUSH TO RESET Button
Function

Time Required to Press Button

Fault Reset

Momentary (less than 2 seconds)

Test Fault

Greater than 3 seconds, but less than 10 seconds

Initiate Tuning Mode

Greater than 10 seconds

The motor must be stopped.

Using the Controller Status LED & Parameter Configuration Module


(150-SM6) LEDs
When a 150-SM6 is installed in one of the three control module ports (7, 8, or 9)
of the SMC-50, additional LED diagnostic information is provided beyond that
of the Status LED.
The 150-SM6 has four diagnostic/status LEDs to display an LED code for each
fault/alarm. When the SMC-50s Status LED indicates the control module has
faulted, the 150-SM6 displays a specific fault code. If the unit is not faulted but in
an alarm condition, the 150-SM6 displays the alarm code. If the unit is neither
faulted or in an alarm condition, all 150-SM6 LEDs will not be illuminated.
The 150-SM6 > (<) LED indicates whether the fault/alarm is a SMC-50 device
fault/alarm or a motor fault/alarm. The on/off status of the other three LEDs
indicate the actual fault/alarm codes.
Depending on which SMC-50 port the 150-SM6 is installed into, the position of
the LEDs (e.g., >, III, II, and I versus I, II, III, and <) change. The table below
displays the LED order when the 150-SM6 is installed in port 7. When the
150-SM6 is installed in port 8 or 9, the order is reversed, but the LED diagnostic
code is the same.
Table 107 - LED Order When 150-SM6 is Installed in Port 7 of the SMC-50
LED On/Off State
LED Error Code

>

III

II

Off Off Off

Off Off On

Off On Off

3
4

Red = SMC
Off On On
Yellow = Motor
Off = No Fault or Alarm On Off Off

On Off On

On On Off

On On On

The displayed LED error code is either a fault or an alarm code depending on the
cause. For example, if the LED code is 1, Line Loss A is either a fault or an alarm.

216

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Diagnostics

Chapter 9

If a more detailed display of the error code source is desired, a human interface
module (HIM) or configuration software is recommended.
The following table provides a list of faults with LED fault/alarm codes for the
150-SM6 Parameter Configuration Module.
Table 108 - LED Error Code with Respective Fault/Alarm Source
LED
Error Code

Fault/Alarm
Source

Referenced HIM/
Configuration
Software Code

LED
Error Code

Fault/Alarm
Source

Referenced HIM/
Configuration
Software Code

HAL ID

33

Red = SMC

Line Loss

NVS Error

34

V24 Recovery

35

V24 Loss

36

V Control Loss

37

1
Shorted
SCR

Open Gate

RTC Battery Low

69

System Faults

100-199

SCR Overtemp

10

Pwr Pole PTC

60

30

31

32

Terminal
Block
Input

38

39

40

41

Test Fault

62
A

11

12

13

CT Loss
7

Open Bypass

Yellow = Motor
No Load

14

Overload

21

15

Stall

24

16

Phase Reversal

25

17
7
18

Current
Imbalance

42

Volt Imbalance

2
Open Load

The Fault/Alarm code, available from a HIM or configuration software, provides more detailed information concerning the
source of the fault/alarm. Fault and Alarm codes for the same event (e.g., Line Loss) are the same.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

217

Chapter 9

Diagnostics

Fault Display (20-HIM-A6)

When the SMC-50 is used with a 20-HIM-A6, the HIM displays the fault
information.
Figure 95 - Fault Display
Allen-Bradley
Faulted
0 Amps

AUTO

F A U L T E D
PROPERTIES
9026

Fault Code
Exp Removed
Elapsed Time

ESC

IMPORTANT

0 : 00 : 16

CLR

Resetting a fault will not correct the cause of the fault condition.
Corrective action must be taken before resetting the fault.
The fault display will remain active as long as control power is applied. If
control power is cycled, the fault will be cleared, the controller will
re-initialize, and the display will show a status of Stopped unless the
Fault condition still exists.
You can press Esc to get to another programming/diagnostic list, but the
SMC-50 will still be in a faulted state.

Clear Fault

A fault can be cleared using any of the following methods:


Program the SMC-50 to automatically clear a fault using Restart Enable,
Parameter 135 or 264.
Press the SMC-50 HOLD TO TEST, PUSH TO RESET button.
Connect a N.O. push button to Option Input #1 (terminal 11) or # 2
(terminal 10). Option Input #1 or #2 must be programmed for Clear Fault
using Parameter 56 or 57.
NOTE: This can also be done with an Input from a 150-SM4 Option I/O Module.

Cycle the control power to the SMC-50.


IMPORTANT

218

An overload fault cannot be reset until the value of the Motor Thermal
Usage, Parameter 18, is below the value programmed in OL Reset,
Parameter 80. See Enabling Option Module Functional Faults & Alarm on
page 107 for further details.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Diagnostics

Fault & Alarm Buffer Parameter List

Chapter 9

The SMC-50 stores the five most recent Fault and Alarm codes (Fault Parameter
List 138 to 142, Alarm Parameter List 143 to 147) in parameter memory from
newest to oldest.

Accessing the Fault & Alarm Parameters


Using the 20-HIM-A6, the fault and alarm parameter lists can be displayed in the
Motor Protection File Group or Linear List parameter number search (Fault
Parameter List 138 to 142, Alarm Parameter List 143 to 147). To use the
File-Group method, perform the following steps:
1. From the SMC-50 standard power up screen, press the Folders keypad key
at the lower left of the display.
NOTE: Ensure the Advanced access level (located at the bottom of the <00> DEV
PARAM screen) is selected before pressing ENTER. See Program Access
Level Configuration in Chapter 5 for additional details.

2. From the <00> DEV PARAM folder screen select File-Group, then press
ENTER (number 5 from the keypad). The Port 00 Param File Group
screen will appear.
3. Use the down arrow key to select (highlight) FILE Motor Protection, then
press ENTER (number 5 from the keypad).
Allen-Bradley
Stopped
0 Amps

Port 00
FILE
FILE
FILE
FILE
FILE

AUTO
F

Param File-Group

Motor Protection
PROPERTIES
Set Up
Motor Protection
Communications
Utility

ESC

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

219

Chapter 9

Diagnostics

4. Use the down arrow key to select GROUP History, then press ENTER
(number from the keypad).
Allen-Bradley
AUTO
F

Stopped
0 Amps

Port 00
FILE
GROUP
GROUP
GROUP
GROUP

Param File-Group

Motor Protection
PROPERTIES
Maintenance
History
Restart
Locked Rotor

ESC

5. Use the arrow keys on the keypad to navigate to the Fault or Alarm number
to review, then press ENTER (number 5 from the keypad).
Allen-Bradley
Stopped
0 Amps

Port 00

AUTO
F

Param File-Group

FILE
Motor Protection
PROPERTIES
GROUP History
Fault 4
Fault 5
Alarm 1

ESC

ENTER
Allen-Bradley
AUTO

Stopped
0 Amps

Port 00

Fault 1

Dev Param

138

PROPERTIES
61

ESC

PAR #

NOTE: In the example above, Fault 61 is displayed. For Fault/Alarm code data, see
Table 110 on page 224.

220

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Diagnostics

Chapter 9

Accessing the Fault & Alarm Buffers


In addition to the SMC-50 storing the most recent Alarm and Fault codes as
parameters, the date and time the Fault or Alarm occurred is stored in the Fault
Buffer (last five faults) and Alarm Buffer (last 100 alarms). To access Fault buffers
and Alarm Buffers using the 20-HIM-A6, the Diagnostic folder must be accessed.
To do so, perform the following steps.
1. From the SMC-50 standard power up screen, press the Folders key at the
lower left of the display.
2. Using the right or left arrow key, display the DIAGNOSTIC folder.
3. Using the up or down arrow key, select either Faults or Alarms, then press
ENTER. In this example, Faults will be used.
Allen-Bradley
AUTO
F

Stopped
0 Amps

DIAGNOSTIC
PROPERTIES
Faults
Alarms
Reset Device
Device Version

00

ESC

The HIM will display the five most recent Fault codes if Faults was
selected. The HIM will display the 100 most recent Alarm codes with an
abbreviated description if Alarm codes were selected. The most recent
code will be listed as 01 with the second most recent code as 02, and so on.
Allen-Bradley
AUTO
F

Stopped
0 Amps

Port
01
02
03
04

ESC

00
Faults
PROPERTIES
61 IO Config
7028 Exp
9026 Exp Removed
0 None

TOP

END

CLR

ENTER

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

221

Chapter 9

Diagnostics

4. Select the Fault or Alarm in question, then press ENTER. The date and
time that the Fault or Alarm occurred will be displayed.
Allen-Bradley
Stopped
0 Amps

AUTO
F

Port
Fault0001
Time StampFaults
PROPERTIES
01 61 IO Config
02 7028 Exp
11 : 43 19
032011/05/25
9026 Exp Removed
04
0 None

ESC

NOTE: The Fault/Alarm buffers are available using DriveExplorer via the Explore and
Device properties drop-down menu. Ensure 0-SMC-50 is selected from the list
of Devices.

Fault Codes
The following table provides a complete cross-reference of the available fault
codes and corresponding fault descriptions.

222

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Diagnostics

Chapter 9

34

M
M
M
M
M
M
M
M
M
M
M
M
M
M
D
M
M
D
D

X
X

X
X
X
X
X
X
X
X
X

X
X

X
X

Test Fault

62

Und PF Lag
Und PF Lead
Ovr PF Lag
Ovr PF Lead
MVAR Over
MVAR Under
RTC Battery Low
Locked Rotor

63
64
65
66
67
68
69
70
71

M
M
M
M
M
M
D
M

X
X
X
X
X
X
X

D Slow Speed

72

Host

43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61

Category

Exp 7, 8, 9

NVS Error

Fault/Alarm Name
Under Power Real
Over Power Real
Un Power Reac +
Ov Power Reac +
Und Power App
Ov Power App
Frequency
PM Hours
PM Starts
A
Power Quality
B
C
Power Quality THD V
Power Quality THD I
Config Change
Ground Fault
Motor PTC
Power Pole PTC
I/O Config

DPI/HIM/COMM

X
X
X

Host

Exp 7, 8, 9

1 D X

1 D X

2 D X

3 D X
2 M X

2 M X

3 M X
M X
M X
4 M X
M X
M X
5 M X
6 M X
D X
D
D X
M X

4 D X

5 D X

Category

DPI/HIM/COMM

1
2
3
4
5
6
7
8
9
10
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

LED Code

LED Code

A
Line Loss
B
C
A
Shorted SCR B
C
A
Open Gate
B
C
SCR Overtemp
No Load
A
Open Load
B
C
Voltage Unbal
Overvoltage
Undervoltage
Overload
Underload
Jam
Stall
Phase Reversal
Exp Removed
Exp Incompat
Expansion
Excess Starts
A
CT Loss
B
C
HAL ID

Code

Fault/Alarm
Name

Code

Table 109 - Fault/Alarm Code Cross-Reference

Start

V24 Recovery

35

Stop Option

73

V24 Loss

36

Coast

74

37

Clear Fault

75

X Fault

76

VControl Loss
1
TB Input

Current Imbal

38

39

3
4

40
41
42

X X Param Change
77
X Reserved
78-99
X
System Faults
100-199 5 D X
7 M X
6

For Category, M= Motor; D=Device TB = Terminal Block Input Codes 71...77 are Event codes.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

223

Chapter 9

Diagnostics

The following table provides an overview of the Fault and Alarm codes with
Time Delay and Restart options plus a basic description of what causes each Fault
or Alarm to occur.
NOTE:

Most Faults and Alarms are individually bit enabled and disabled (F/A Bit
Enab) and can have a user configurable delay time to help avoid nuisance
trips (Time Delay Aval). In addition, many have the ability to automatically
restart once the condition is cleared (Restart En). See Chapter 4 for additional
information on Faults and Alarms.

Shorted
SCR

1
2
3
4
5

Description
F/A= Fault & Alarm, A= Alarm, F= Fault

F/A Loss of line power for Phase A, B, or C

A
B
C

7
8
9

SCR
Overtemp

10

No Load

14

15
16
17

Open
Gate

Open
Load

224

A
B
C
A
B

Restart Enable

Line Loss

F/A Bit Enable

Fault/Alarm
Code Name

Time Delay Avail.

F/A Code

Table 110 - Linear Listing Fault & Alarm Code Overview

A
B
C

Voltage
Unbalance

18

Overvoltage

19

Undervoltage

20

Overload

21

Underload

22

A During prestart
checks (motor
stopped not running),
NA the SMC-50 monitors
for current flow in
each individual
phase.
Y

NOTE: In Wye configurations,


a single Phase A, B, or C
shorted SCR will not be
detected until the unit is
started. This fault is always
enabled.

F/A Indicates that an abnormal condition that causes


faulty firing (e.g., open SCR Gate) has been sensed
during the starting sequence.

F The SMC-50 protects the SCRs from damage caused


NA by overtemperature operation using an internally
configured I2T. NOTE: This fault is always enabled.
F/A The SMC-50 can determine if a load connection
Y exists (total load lost or all load leads lost) and a No
Load Fault and/or Alarm can be indicated.
F/A An Open Load A Fault/Alarm indicates that the
Y F/A An Open Load B Phase X load lead connection
F/A An Open Load C is OFF/Open.
F/A Indicates that when the calculated unbalance
level is greater than the user-defined Fault and/or
Y
Alarm level. See Chapter 4 for calculated value
details.
F/A Indicates that if the average line voltage is greater
Y
than the user-defined Fault and/or Alarm level.
F/A Indicates that if the average line voltage is less
Y
than the user-defined Fault and/or Alarm level.
F/A Enabled in the Motor Protection Group by
Y
programming the: Overload Class, Overload Reset,
Motor FLC, and Service Factor.
F/A Motor operation will halt (Fault only) if the value
Y
of the motors average RMS current is less than the
user-defined value.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Fault/Alarm
Code Name

F/A Code

Time Delay Avail.

F/A Bit Enable

Restart Enable

Diagnostics

Jam

23

Stall

24

Phase Reversal

25

Exp Removed

26

NA

Exp Incompat

27

NA

Expansion

28

NA

Starts per Hour

29

NA

CT Loss

30

31

32

HAL ID

33

NA

NVS Error

34

NA

Future Use

35

V24 Loss

36

NA

Chapter 9

Description
F/A= Fault & Alarm, A= Alarm, F= Fault
F/A Indicates that the motor current increases above
the user-defined Fault and or Alarm level while the
motor is running at speed. This F/A condition is not
active during starting or stopping.
F/A Condition exists and a Fault/Alarm is generated if
the SMC-50 senses that the motor is NOT
Up-to-Speed (UTS) at the end of the programmed
starting ramp time plus the time programmed in the
Stall Delay time.
F/A Fault/Alarm is indicated when the incoming power
to the SMC-50 is in any sequence other than ABC.
F Removing an expansion module (device) (e.g., a
150-SM4) from a SMC-50 will result in a x026 fault,
where "x" is the SMC-50 port number (7, 8, or 9) the
expansion module was installed. DPI devices (e.g.,
20-HIM-A6 or 20-COMM-X) will only generate this
fault if its associated bit in Logix Mask parameter is
set.
NOTE: If an expansion module (device) (e.g., a
150-SM4 is removed from a SMC-50), the message
"Device Conflicts Port xy Not Found" will be displayed
on the HIM or PC software) when power returns.
F Inserting an expansion module or DPI device into an
incompatible controller port number or inserting an
expansion module into a controller with incompatible
version of firmware will result in this Fault. The port
number of the offending device is included as the first
digit of this Fault code.
F General Fault that can be generated by an expansion
or peripheral device. The port number of the offending
device is included as the first digit of this Fault code.
F/A Starts per Hour is the maximum number of starts
(user configured) within a sliding one hour window.
Once the number of starts per hour is reached, any
additional starts will cause a Fault/Alarm Code 29.
F CT Loss A
(Phase A)
fault will occur when current
F CT Loss B
feedback is invalid. This Fault
(Phase B)
is always enabled.
F CT Loss B
(Phase B)
F HAL ID Fault is generated if the controller
determines that an incorrect (incompatible) power pole
is installed. This Fault is always enabled.
F Indicates an error in the SMC-50s nonvolatile
memory storage. Clearing the Fault requires a change
to the parameter or loading defaults (preferred). It is
not cleared by cycling power. This Fault is always
enabled.
Future use.
F Indicates that the voltage level of the SMC-50s
internal 24V DC supply which provides power to the
controller logic and on-board 24V DC I/O has fallen
outside of the allowable range. This Fault is always
enabled.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

225

Fault/Alarm
Code Name

Time Delay Avail.

F/A Bit Enable

Restart Enable

Diagnostics

F/A Code

Chapter 9

VControl Loss

37

F Indicates that the control voltage level of the user


control voltage has fallen outside the
NA applied
allowable upper or lower limit. This Fault is always
enabled.

38
39
40
41

F Occurs when the Control Input is configured to


NA generate a Fault and the input condition (N.O. or N.C.)
is satisfied.

Current Imbal

42

Under Power Real

43

Over Power Real

44

Un Power Reac +

45

Ov Power Reac +

46

Under Power App

47

Over Power App

48

Frequency

49

PM Hours

50

PM Starts

51

52
53
54

55

F/A Indicates a high, voltage based total harmonic


distortion level.

56

F/A Indicates a high, current based total harmonic


distortion level.

Config Change

57

Ground Fault

58

Motor PTC

59

F/A Indicates any change to the SMC-50 parameter


configuration.
F/A Indicates the value of Ground Fault Current goes
above the user-defined fault/alarm level.
NOTE: A 150-SM2 Ground Fault PTC Feedback
Module and 825-CBCT Core Balanced Ground Fault
Sensor are required to configure this Fault/Alarm.
F/A Indicates the embedded motor PTC sensing device
is tripped/closed due to a motor overtemperature
condition. NOTE: A 150-SM2 Ground Fault PTC
Feedback Module is required to configure this
Fault/Alarm.

TB Input

Power Quality
Power Quality
THD V
Power Quality
THD I

226

1
2
3
4

A
B
C

Description
F/A= Fault & Alarm, A= Alarm, F= Fault

F/A Exists when the calculated imbalance level is


equal to or greater than the user-defined Fault/Alarm
level. See Chapter 4 for calculated value details.
falls below the user-defined
F/A Occurs when the fault/alarm level.
Real Power:
rises above the user-defined
fault/alarm level.
falls below the user-defined
F/A Occurs when the fault/alarm level.
Reactive Power +:
rises above the user-defined
fault/alarm level.
falls below the user-defined
F/A Occurs when the fault/alarm level.
Apparent Power+:
rises above the user-defined
fault/alarm level.
F/A Occurs if the line frequency goes above or below
the user-defined frequency high or frequency low
Fault/Alarm level.
F/A User-defined value which sets the number of
elapsed hours (actual operating hours of the motor)
before a fault/alarm is signaled indicating that
preventative maintenance should be performed.
F/A User-defined value which sets the number of
starts before a fault/alarm is signaled indicating that
preventative maintenance should be performed.
F/A Fault condition
A Phase SCR.
which indicates that B Phase SCR.
the starter is not
C Phase SCR.
properly firing its:

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

F/A Bit Enable

Power Pole PTC

60

I/O Config

61

Test Fault

62

Under PF Lag

63

Under PF Lead

64

Over PF Lag

65

Over PF Lead

66

-MVAR Over

67

-MVAR Under

68

RTC Battery Low

69

Locked Rotor

70

Start
Slow Speed
Stop Option
Coast
Clear Fault
Fault

71
72
73
74
75
76

NA
NA
NA
NA
NA
NA

NA
NA
NA
NA
NA
NA

Parm Change

77

NA NA

F Built-in Power Pole PTC Temperature Sensor is used


measure power pole temperature. A fault will occur
NA to
when the temperature rises above a predetermined
level. This fault is always enabled.
F Occurs when any input is programmed as a start or
slow speed and no input is configured as a coast or
stop. The fault will occur when the start or maneuver
is attempted (the motor will not start). This fault is
NA also generated when the input configuration changes
from one that cannot start the motor to one that can. It
will also be generated when a parameter is changed
from an input that can stop the motor to one that
cannot. This fault is always enabled.
F Occurs when the Push-to-Test, Hold-to-Reset push
NA button on the SMC-50 is pushed for 3 seconds but <
10 seconds.
F/A Occurs when the lagging Power Factor goes below
Y
the user-defined fault/alarm level.
F/A Occurs when the leading Power Factor goes below
Y
the user-defined fault/alarm level.
F/A Occurs when the lagging Power Factor goes above
Y
the user-defined fault/alarm level.
F/A Occurs when the leading Power Factor goes above
Y
the user-defined fault/alarm level.
F/A Occurs when the magnitude of the Reactive Power
Y
rises above the user-defined level.
F/A Occurs when the magnitude of the Reactive Power
Y
falls below the user-defined level.
A Occurs when the SMC-50 battery that maintains the
NA value of the Real Time Clock (RTC) is low and needs to
be replaced immediately. Alarm is always enabled.
F/A Occurs when the motor current increases above
the user-defined fault/alarm level while the motor is in
Y
any running mode. This F/A condition is not active
during starting or stopping.
NA
Start Event tracking.
NA
Slow Speed Event tracking.
NA
Stop Option Event tracking.
This is an Event Code
NA and is stored in the
Coast Event tracking.
NA Alarm Buffer for:
Clear Fault Event tracking.
NA
Fault Event tracking.
Parameter Change Event
NA
tracking.

Reserved

7899

System Faults

100N
199

A general Fault/Alarm typically associated with the


NA SMC-50 hardware (e.g., system Watchdog Time
failure).

Restart Enable

Fault/Alarm
Code Name

Time Delay Avail.

Chapter 9

F/A Code

Diagnostics

Description
F/A= Fault & Alarm, A= Alarm, F= Fault

Future Use.

Overload is inherently a time-based fault.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

227

Chapter 9

Diagnostics

Auxiliary Relay Output


Fault or Alarm Indication

228

Auxiliary Relay Output contacts can be programmed for Fault or Alarm, N.O. or
N.C. indication. In addition, an ON or OFF Delay Time can also be configured.
Basic parameter setup (without N.C. or timed functions) can be found in the
Setup / I/O Parameter Group. Alternatively, full configuration is available from
the Setup / I/O Parameter Group.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Chapter

10

Troubleshooting

Introduction

For safety of maintenance personnel as well as others who might be exposed to


electrical hazards associated with maintenance activities, follow the local safety
related work practices (e.g., NFPA 70E, Part II in the United States).
Maintenance personnel must be trained in the safety practices, procedures, and
requirements that pertain to their respective job assignments.
SHOCK HAZARD: Hazardous voltage is present in the motor circuit even
when the SMC-50 is off. To avoid shock hazard, disconnect main power
before working on the controller, motor, and control devices (e.g.,
Start-Stop push buttons). Procedures that require parts of the equipment
to be energized during troubleshooting, testing, etc., must be performed
by properly qualified personnel using appropriate local safety work
practices and precautionary measures.
ATTENTION: Disconnect the controller from the motor before measuring
insulation resistance (IR) of the motor windings. Voltages used for
insulation resistance testing can cause SCR failure. Do not make any
measurements on the controller with an IR tester (megger).

The following flowchart is provided to aid in quick troubleshooting.


NOTE:

The time it takes for the motor to come up to speed may be more or less than
the time programmed. This depends upon the motor and load characteristics.

NOTE:

Depending upon the application, the braking options (SMB Smart Motor
Braking and Slow Speed) may cause some vibration or noise during the
stopping cycle. To minimize vibration or noise, lower the braking current
adjustment. If this is a concern in your application, please consult the factory
before implementing the braking options.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

229

Chapter 10

Troubleshooting

Figure 96 - Troubleshooting Flowchart


YES

Fault Displayed?

NO

Define nature
of
trouble.

Motor will not start.


There is no output
voltage to the motor.

See Table 111

See Table 112

Motor rotates but


does not accelerate
to full speed.

See Table 113

Motor stops
while running.

See Table 114

Miscellaneous
situations.

See Table 115

Table 111 - Fault Display Explanation


Display

Fault Code

Fault Enabled

Possible Causes

Possible Solutions

Line Loss
(with phase indication)

1, 2, 3

Prestart &
Running

Shorted SCR
(with phase Indication)

4, 5, 6

In All Modes

Open Gate
(with phase indication)

SCR Overtemp or
PTC Power Pole

No Load or Open Load


(with Phase Indication)

Voltage Unbalance or
Current Imbalance

230

7, 8, 9

In All Modes

14,
15,
16,
17

Prestart Only

Running

Check for line and load loose connections.


Check for open line (e.g., blown fuse).
Check for open line lead(s).
Verify power quality.
Disable this fault/alarm feature.

Shorted power module.

Check for shorted SCR, perform a resistance check


(see Power Module Check section), or replace
power module if necessary.

Open gate circuitry


Loose gate lead

Perform a resistance check (see Power Module


Check section), replace power module if necessary.
Remove control module from the power section and
check gate lead connections (TB5, TB6, and TB 7)
are firmly seated to the control module.
Disable this fault/alarm feature.

Check for proper controller ventilation.


Check application-appropriate duty cycle.
Wait for controller to cool or provide external
cooling if ambient temperature is high.
Check for fan operation. Replace fan, if necessary.
Replace power module or control module as
needed.

Start or Stop

10 or 60

18 or 42

High impedance line connection


Missing supply phase
Motor not connected properly
Incoming 3-phase voltage instability

Controller ventilation blocked


Controller duty cycle exceeded
Fan failure
Ambient temperature limit exceeded
Failed thermistor

Loss of load side power wiring with


phase indication (15=A, 17=C)
Start command cycled unexpectedly
with motor rotating

Check all load side power connections.


Check motor windings (megger).

Power line unbalance is greater than


the programmed value
The delay time programmed is too
short for the application

Check the power system and correct if necessary or


change the programmed value.
Extend the delay time to match the application
requirements.
Disable this fault/alarm feature.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Troubleshooting

Chapter 10

Table 111 - Fault Display Explanation


Display

Overvoltage

Undervoltage

Overload

Fault Code

19

20

21

Fault Enabled

Possible Causes

Possible Solutions

Running

Power line grid voltage is greater


than the programmed value
Abnormal voltage regulation
The parameter settings &/or delay
time programmed are not suited for
the application

Check the power system and correct if necessary.


NOTE: If the power source is a backup generator,
check the stability of the generator voltage
regulator. Replace if necessary.
Modify the parameter &/or extend the delay time to
match the application requirements.
Disable this fault/alarm feature.

Power line grid voltage is less than


the programmed value
Abnormal voltage regulation
The parameter settings & or delay
time programmed are not suited for
the application

Check the power system and correct if necessary.


NOTE: If the power source is a backup generator,
check the stability of the generator voltage
regulator. Replace if necessary.
Modify the parameter &/or extend the delay time to
match the application requirements.
Disable this fault/alarm feature.

Motor overloaded
Overload parameters are not
matched to the motor

Check motor overload condition.


Check programmed values for overload class and
motor FLC; verify current draw of the motor.
Disable this fault/alarm feature.

Running

Running

Underload

22

Running

Broken motor shaft, belt, grating,


etc.
Pump cavitation
Programmed setting incorrect for
application

Check machine drive components and loading.


Check pump system.
Repair or replace motor.
Check programmed settings.
Disable this fault/alarm feature.

Jam

23

Running

Motor current has exceeded the


user programmed jam level for the
programmed time

Correct source of jam or excessive loading.


Check programmed time value.
Disable this fault/alarm feature.
Check pump system, machine drive components,
and loading; repair or replace motor, if necessary.
Check programmed settings.
Disable this fault/alarm feature.

Stall

24

Running

The motor did not reach full speed


by the end of the programmed ramp
time
Incorrect programmed setting

Phase Reversal

25

Prestart Only

The controller is not detecting


incoming supply voltage in the
expected ABC sequence

Check power wiring and correct, if necessary.


Disable this fault/alarm feature.

Exp Removed

x026

In All Modes

Expansion module is loose or


removed
Expansion module is defective

Reseat or replace the expansion module connector


to the control module and tighten module screws.
Replace defective module.

In All Modes

Expansion module is inserted into an


incompatible control module port
number
Controller firmware is not
compatible with the expansion
module
Expansion module is defective

Insert the expansion module into a compatible


control module port.
Update the control module firmware
Replace defective module.

Expansion module is loose or


removed
Expansion module is defective
Expansion module is inserted into an
incompatible control module port
number
Controller firmware is not
compatible with the expansion
module

Reseat and/or replace loose/removed module and


tighten module screws.
Replace defective expansion module.
Update control module firmware.

The number of starts within the last


hour has exceeded the programmed
value
Programmed setting is incorrect for
the application

Wait for the hour to expire, then restart the motor.


Reduce the actual number of starts per hour or
increase the programmed start time (if allowed by
the application) and controller thermal limits.
Turn off this fault/alarm feature.

Exp Incompat

Expansion

Starts per Hour

x027

x028

29

In All Modes

Starting

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

231

Chapter 10

Troubleshooting

Table 111 - Fault Display Explanation


Display

Fault Code

Fault Enabled

Possible Causes

Possible Solutions
Remove the control module from the power section;
verify connectors TB2 (A), TB3 (B), and TB4 (C) are
firmly seated to the control module.
Replace the control module and/or the power
section.
Inspect the CT sensor cables for loose connections;
check CTs for damage; repair/replace CTs if
necessary; replace 150-SM2 option module if
necessary.

CT Loss
A, B, or C

30,
31, or
32

In All Modes

Loose CT cable connection between


the power section and the control
module
Phase A (F30), B (F31), or C (F32)
current transformer feedback circuit
has failed
Option Module 150-SM2 with
external CT operation (Fault Code
7030, 8030)

Hall ID

33

In All Modes

Loose cables between the controller


and power section.
Incompatible power section
installed with the controller

Remove the control module from the power section;


verify connectors TB2 (A), TB3 (B), and TB4 (C) are
firmly seated to the control module.
Check the power section and replace, if necessary.
Modify a parameter or load parameter defaults
(preferred) and reload the customer-specific
parameters.
Check the option module sensor cables.
Replace the option module.

NVS Error

34

In All Modes

Controller memory corrupted


Option module error (Fault Code
7034, 8034, or 9034)

Future Use

35

NA

NA

NA

Loose connection at Control


Terminals 1 (+L1) and 2 (-L2)
Excessive load on internal 24V
supply
Low line voltage condition

Check the control power and verify it is within the


specification; check the line connections and
grounding to the SMC-50 control terminals.
Replace the control module.

Loose connection at Control


Terminals 1 (+L1) and 2 (-L2)
Low line voltage condition

Check the control power and verify it is within the


specification; check the connections and grounding
to the SMC-50 control terminals.
Replace the control module.
Clear the fault condition.
Rewire and/or reconfigure the input.

In All Modes

The condition to generate the TB


Input fault is satisfied
Terminal wiring configuration or
fault N.O./N.C. configuration of
input is incorrect

Running

Power line unbalance is greater than


the programmed value
The delay time programmed is too
short for the application

Check the power system and correct if necessary or


change the programmed value.
Extend the delay time to match the application
requirements.
Disable this fault/alarm feature.

Running

Abnormally reduced real (MW)


power draw by the motor possibly
due to broken mechanical
connection (belt, gears, etc.)
between motor and load
Pump cavitation
Programmed setting is incorrect for
the application

Repair/replace the condition causing the reduced


real power load.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

Abnormally high real (KW) power


draw by the motor
Programmed setting is incorrect for
the application

Repair/replace the condition causing the high KW


power draw.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

Abnormally reduced reactive


(+MVAR) power produced by the
motor
Programmed setting is incorrect for
the application

Repair/replace the condition causing the reduced


+MVAR power draw.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

V24 Loss

36

In All Modes

V Control Loss

37

In All Modes

TB Input
1, 2, 3 & 4

38,
39,
40, &
41

Voltage Unbalance or
Current Imbalance

Und Pwr Real

Ovr Pwr Real

Un Pwr Reac+

232

42 or 18

43

44

45

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Troubleshooting

Chapter 10

Table 111 - Fault Display Explanation


Display

Ov Pwr Reac+

Und Pwr App

Ovr Pwr App

Frequency

Fault Code

46

47

48

49

Fault Enabled

Possible Causes

Possible Solutions

Abnormally high reactive (+MVAR)


power produced by the motor
Programmed settings are incorrect
for the application

Repair/replace the condition causing the high


+MVAR power draw.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

Abnormally reduced apparent (MVA)


power draw by the motor
Programmed settings are incorrect
for the application

Repair/replace the condition causing the reduced


+MVA power draw.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

Abnormally high apparent (MVA)


power draw by the motor
Programmed settings are incorrect
for the application

Repair/replace the condition causing the high


+MVA power draw.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Speed control regulation system of


the generator prime mover (e.g.,
diesel engine) is unable to adjust to
current load conditions or is
defective
Abnormal power grid connections;
power generation source is
operating outside its normal
frequency limits or range

Reduce the generator load, increase generator


output, replace the speed control system, or
generator.

Running

Running

NOTE: For a diesel generator system, Rockwell


Automation recommends it be oversized by a
factor of three for Soft Start applications.
Contact the power company for additional
information.
Modify the programmed fault/alarm parameters to
better suit the application.

PM Hours

50

In All Modes

The number of hours programmed in


the PM Hours Parameter has been
reached

Perform required maintenance and reset the PM


Hours parameter.
Disable this fault/alarm feature.

PM Starts

51

Pre-Start

The number of Starts programmed in


the PM Start Parameter has been
reached

Perform required maintenance and reset the PM


Hours parameter.
Disable this fault/alarm feature.

Power Quality
A, B, or C

52,
53, or
54

Start or Stop

Incoming 3-phase voltage instability


or distortion
High impedance line or load
connection

Check supply voltage for capability to start/stop the


motor; check for loose connections on the line side
or motor side of the power wires.
Verify and correct the input power quality issue
Disable this fault/alarm feature.

Running

The current mix of loads on the


power line contributing to the THD V
has exceeded the programmed THD
V level &/or time

Check the mix of loads (what was added, what was


changed); modify the load mix if necessary.
Change the programmed THD V level &/or delay
time.
Disable this fault/alarm feature.

The current mix of loads on the


power line contributing to the THD I
has exceeded the programmed THD
I level &/or time

Check the mix of loads (what was added, what was


changed); modify the load mix if necessary.
Change the programmed THD I level &/or delay
time.
Disable this fault/alarm feature.

A controller parameter has been


modified

Disable this fault/alarm feature.

The ground fault current level has


exceeded the programmed value
The delay time is too short for the
application

Check the power system and motor; correct if


necessary.
Check the programmed ground fault levels to match
application requirements; modify if necessary.
Extend the delay time to match the application
requirements.
Disable this fault/alarm feature.

Power Quality
THD V

55

Power Quality
THD I

56

Running

Config Change

57

In All Modes

Ground Fault

X058

Running

NOTE: An optional 150-SM2


Ground Fault PTC Module is
required for this fault.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

233

Chapter 10

Troubleshooting

Table 111 - Fault Display Explanation


Display

Motor PTC

Fault Code

X059

Fault Enabled

In All Modes

SCR Overtemp or
PTC Power Pole

60 or 10

In All Modes

I/O Config

61

Pre-Start

Test Fault

Und PF Lag

Und PF Lead

Ovr PF Lag

Ovr PF Lead

-MVAR Over

-MVAR Under

234

62

63

64

65

66

67

68

Possible Causes

Possible Solutions

Motor ventilation is blocked.


Motor duty cycle is exceeded
PTC open or shorted

Check for proper ventilation.


Check application duty cycle.
Wait for motor to cool or provide external cooling,
then check resistance of PTC.
Disable this fault/alarm feature.

NOTE: An optional 150-SM2


Ground Fault PTC Module is
required for this fault.

Controller ventilation blocked


Controller duty cycle exceeded
Fan failure
Ambient temperature limit exceeded
Failed thermistor

Check for proper controller ventilation.


Check application-appropriate duty cycle.
Wait for controller to cool or provide external
cooling if ambient temperature is high.
Check for fan operation. Replace fan, if necessary.
Replace power module or control module as
needed.

The configuration of the control I/O


does not meet the system rules as
defined in Chapter 4, Configuration
Functions on page 134

Modify the control I/O configuration to meet the


established rules.

The SMC-50s Push to Reset/Hold to


Test push button was pressed for
more than three seconds, but less
than ten
The SMC-50s Push to Reset/Hold to
Test push button is stuck or
damaged

To reset the Test fault, press the Push to Reset/Hold


to Test push button for less than two seconds.

In All Modes

A lagging PF is abnormally under the


typical value; less inductance or
more capacitance has been
introduced to the power line
A programmed setting or time value
is incorrect for the application

Determine the cause of the reduced Lagging PF.


Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

A leading PF is abnormally under the


typical value; less inductance or
more capacitance has been
introduced to the power line
A programmed setting or time value
is incorrect for the application

Determine the cause of the reduced Leading PF


Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

A lagging PF is abnormally over the


typical value; more inductance or
less capacitance has been
introduced to the power line
A programmed setting or time value
is incorrect for the application

Determine the cause of the Over PF Lagging


Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Running

A leading PF is abnormally under the


typical value; less inductance or
more capacitance has been
introduced to the power line
A programmed setting or time value
is incorrect for the application

Determine the cause of the Over PF Leading.


Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Abnormally high reactive (-MVAR)


power consumed by the motor
Programmed settings are incorrect
for the application

Repair/replace the condition causing the high


-MVAR.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

Abnormally reduced reactive


(-MVAR) power consumed by the
motor
Programmed settings are incorrect
for the application

Repair/replace the condition causing the reduced


-MVAR.
Modify the programmed fault/alarm parameters to
better suit the application.
Disable the fault/alarm feature.

In All Modes

Running

Running

NOTE: Only use the Push to Reset push button


when absolutely necessary.
Attempt to dislodge the push button or replace the
control module if necessary.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Troubleshooting

Chapter 10

Table 111 - Fault Display Explanation


Display

Fault Code

Fault Enabled

Possible Causes

Possible Solutions

69

Pre-Start

Battery reading is below the


acceptable level to potentially
maintain the real time clock and
calendar

Replace battery (CR2032) as soon as possible.

RTC Battery Low

Motor has stalled; rotor is not


turning

Check motor and load for binding or jammed


conditions
Parameters are not adequately configured for the
application. Review and adjust.
Disable the fault/alarm feature.

Locked Rotor

70

In All Modes

Start

71

Starting

A start event (command) has


occurred. This is not a fault.

NA

Slow Speed

72

Slow Speed

A slow speed event (command) has


occurred. This is not a fault.

NA

Stop Option

73

Stop Option

A stop option event (command) has


occurred. This is not a fault.

NA

Coast

74

Coast

A coast-to-stop event (command)


has occurred. This is not a fault.

NA

75

Faulted

A clear fault event (command) has


occurred. This does not generate a
fault.

NA

Clear Fault

Fault

76

Faulted

A fault event (command) has


occurred. This is not a fault.

NA

77

Stopped

A change to one of the controller


parameters has occurred. This is not
a fault.

NA

Param Change
Reserved

78-99

NA

NA

NA

There is an issue with the control


module wiring
The control module is defective

Review the control module wiring. Ensure the


ground terminal is secure and connected to the
systems earth ground. Ensure an RC
snubber/suppressor is connected to all inductive
loads in the control circuit. See input wiring.
Replace the control module.

System Faults

100-199

In All Modes

"X" indicates a port number in which the expansion module resides in the SMC-50.
The Real, Reactive, and Apparent Power faults/alarms are best suited to provide indication of an abnormal running operation of the motor or system which
another parameter (e.g., Underload, Overload, Jam, Stall, etc.) does not provide. To understand what is an abnormal running operation, a "normal" or "typical"
value, usually established during system startup, needs to be determined by the user.
If controller based motor overload is disabled, external motor overload protection should be used.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

235

Chapter 10

Troubleshooting

Table 112 - Motor Will Not Start No Output Voltage to the Motor
Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 111 addressing fault


conditions

HIM display is blank

Check control wiring and correct


if necessary
Check HIM connection
Cycle control power
Replace HIM only
Replace control module only

Stopped
0.0 Amps

Pilot devices
SMC Enable input is open at
terminal 9
Configured or wired input
terminals are not wired
correctly
Start-Stop control has not
been enabled for the human
interface module
Control voltage
Failed control module

Check wiring; follow the


instructions on page 209 to
enable control capability.
Check control voltage
Replace control module

Starting

One or more power phases are


missing
Isolation contactor (if used) is
not picking up

Check power system


Check that the SMC-50 Aux.
relay output controlling the
Isolation Contactor is configured
to "Normal".
Check the Isolation Contactor for
proper operation

Failed HIM
Control voltage is absent
Failed control module
HIM connection is loose

Table 113 - Motor Rotates but Does Not Accelerate to Full Speed

236

Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See Table 111 addressing fault


conditions

Starting

Mechanical problems
Inadequate Current Limit
setting
Failed control module

Check for binding or external loading


and correct
Check motor
Adjust the Current Limit Level to a
higher setting
Replace control module

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Troubleshooting

Chapter 10

Table 114 - Motor Stops While Running


Display

Possible Cause

Possible Solutions

Fault displayed

See fault description

See addressing fault conditions

HIM display is blank

Replace HIM
Check control wiring and correct
if necessary
Replace control module
Check HIM connection

Stopped
0.0 Amps

Pilot devices

Failed HIM
Control voltage is absent
Failed control module
HIM connection is loose

Failed control module


Starting

One or more power phases are


missing
Failed control module

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Check control wiring and correct


if necessary
Replace control module
Check power system
Replace control module

237

Chapter 10

Troubleshooting

Table 115 - Miscellaneous Situations


Situation

Possible Cause

Possible Solutions

Motor current and


voltage fluctuates

Motor
Erratic Load

Verify type of motor as a standard squirrel


cage induction motor
Check load conditions

Erratic operation

Loose connections

Shut off all power to controller and check


for loose connections

Accelerates too fast

Starting time
Initial torque
Current limit setting
Kickstart

Increase starting time


Lower initial torque setting
Decrease current limit setting
Lower kickstart time or turn off

Accelerates too
slow

Starting time
Initial torque
Current limit setting
Kickstart

Decrease starting time


Increase initial torque setting
Increase current limit setting
Increase kickstart time or turn off

Fan does not


operate

Control wiring
Failed fan(s)

Check control wiring and correct if necessary


Replace fan module

Motor stops too


quickly with Soft
Stop option

Time setting

Verify the programmed stopping time and


correct if necessary

Motor stops too


slowly with Soft
Stop option

Stopping time setting


Misapplication

Verify the programmed stopping time and


correct if necessary
The Soft Stop option is intended to extend
the stopping time for loads that stop
suddenly when power is removed from the
motor.

Fluid surges with


pumps still occur
with the Soft Stop
option

Misapplication

Soft Stop ramps voltage down over a set


period of time. In the case of pumps, the
voltage may drop too rapidly to prevent
surges. A closed loop system such as Pump
Control would be more appropriately suited.

Motor overheats

Duty cycle

Preset Slow Speed and SMB options:


Extended operation at slow speeds reduces
motor cooling efficiency. Consult motor
manufacturer for motor limitations.
Smart Motor Braking option: Check duty
cycle. Consult motor manufacturer for motor
limitations.

Motor short circuit

Winding fault

Identify fault and correct.


Check for shorted SCR; replace if necessary.
Ensure power terminals are secure.

Fan operation is controlled by the SMC-50 Control Module. The fan may not run in low ambient temperature conditions. See
Chapter 2, Fan Power on page 35 for additional details.

238

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Troubleshooting

Power Module Check

Chapter 10

If a power module needs to be checked, use the applicable procedure that follows.
ATTENTION: To avoid shock hazard, disconnect main power before
working on the controller, motor, or control devices such as Start/Stop
push buttons.

ATTENTION: Make sure that wires are properly marked and


programmed parameter values are recorded.

Shorted SCR Test


1. Using an ohm meter, measure the resistance between the line and load
terminals of each phase on the controller. (L1-T1, L2-T2, & L3-T3)
The resistance should be greater than 5,000 ohms. Replace the power assembly if
this reading is not reached. See Appendix C for the list of Spare/Replacement
SMC-50 parts.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

239

Chapter 10

Troubleshooting

Notes:

240

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Appendix

Specifications

Standard Features

Table 116 - Functional Design Specifications


Standard Features
Power Wiring
Installation
Control Wiring
Keypad
Configuration/
Setup

Software
Parameter Configuration
Option Module

Communications
Basic Starting & Stopping Modes
Pump Control

Start & Stop


SMB Smart Motor Braking

Braking
Control

Accu-Stop
Slow Speed with Braking
External Braking

Protection & Diagnostics

Metering Indication

LED Status Indication by Multi-Color


(standard)
Auxiliary Contacts (two standard)

Description
standard squirrel-cage induction motor or Wye-Delta, six-lead motor
two- and three- wire control for a wide variety of applications
Cat. No. 20-HIM-A6 full numeric keypad with LCD display
Cat. No. 20-HIM-C6S remote panel mount full numeric keypad with LCD
display
parameter values are downloaded to the SMC-50 with the Connected
Components Workbench and DriveTools programming software
Cat. No. 150-SM6 provides limited configuration by DIP and rotary switches
four DPI ports for local serial communications, network communication is
supported by optional 20-COMM-X modules
modes include: Soft Start, Current Limit Start, Dual Ramp, Full Voltage, Linear
Speed Acceleration (start), Linear Speed Deceleration (stop), Torque Start,
Preset Slow Speed, and Soft Stop
helps reduce fluid surges in centrifugal pumping systems during the starting
and stopping period
provides motor braking without additional equipment for applications that
require the motor to stop quickly
provides controlled position stopping; during stopping, brake torque is applied
to the motor until the motor reaches the preset slow speed and holds the
motor at this speed until a stop command is given - braking torque is then
applied until the motor reaches zero speed - braking current is programmable
used on applications that require slow speed in the forward or reverse
position for positioning or alignment and requires braking control to stop.
activates an external braking device by using an auxiliary relay output
displays: Power Loss, Line Fault, Voltage Unbalance, Excessive Starts/Hour,
Phase Reversal, Undervoltage, Overvoltage, Controller Temperature, Stall,
Jam, Open Gate, Overload, Underload, and Communication Fault
provides: Phase Current, Current Average, Phase-to-Phase Voltage, Voltage
P-P Average, Phase-to-Neutral Voltage, Calculated Torque, Real Phase Power,
Real Power, Real Energy, Real Demand, Max Real Demand, Reactive Power,
Reactive Energy + & -, Reactive Energy, Reactive Demand, Max Reactive
Demand, Apparent Power, Apparent Energy, Apparent Demand, Number of
Periods, Power Factor, Energy Savings, Elapsed Time 1 & 2, Running Time,
Motor Speed, Start Time 1-5, Peak Current 1-5, Total Starts, THD V, THD I, THD
V Average, THD I Average, Line Frequency, Current Imbalance, and Voltage
Unbalance
displays status, fault, and alarm codes: Running - with alarm, Running - no
alarm, Ready - with alarm, Ready - no alarm, Ready - tuning enabled on next
start, and Firmware Download Active - with alarm
two fully programmable contacts as: normal, UTS, fault, alarm, external brake,
auxiliary control, network, or external bypass

The configuration option must be ordered separately from the controller, which does not include a setup tool.
Accu-Stop is accomplished using the SMB Mode and Slow Speed with Braking.
Diagnostic indication depends on the type of configuration tool used, The standard LED status indication displays: Inhibit (stop

enabled), Fault (non-resettable), Fault (resettable). For full local access, a HIM or PC software is required. Remote full access to data
can also be obtained using a 20-COMM-XX communication module.
Metering Indication depends on the type of configuration tool being used. Metering Indication requires the use of a HIM or PC
software configuration tool for full local access. Full access to data can also be obtained via network using a 20-COMM-XX
communication module.
Not intended to be used as an emergency stop. See applicable standards for emergency stop requirements.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

241

Appendix A

Specifications

Electrical Ratings

Table 117 - Power Circuit & Utilization Category Ratings


Type
# of Controlled Poles
Rated Operation Voltage
Rated Isolation Voltage
Rated Impulse Voltage
Dielectric Withstand
Repetitive Peak Inverse
Voltage Rating
Operating Frequency
Normal Duty
Heavy Duty
Protection Against
Electrical Shock

Device
Rating
3
480V
690V
480V
690V
480V
690V
480V
690V
480V
690V
All

90...520 A

UL/CSA/NEMA
Power Circuit

200...480V AC (-15%, +10%)


200...600V AC (-15%, +10%)
N/A

IEC

200...415V (-15%, +10%)


200...690V /Y (-15%, +10%)
500V
690V

N/A

6000V

2200V AC

2500V

1400V
1800V
47...63 Hz
Utilization Category
MG1

90...520 A
N/A
90...180 A

1400V
1800V
47...63 Hz
AC-53a: 3.5-10:99-2
AC-53a: 3.5-30:99-1
IP00
(IP20 - Control Terminals only)
IP2X
(with 150-STCB Terminal Cover)

480V
RC Snubber Network
690V
480...600V
Metal Oxide Varistors: 220 Joules
Transient Protection
690V
None
Control Power Specifications
Rated Operation Voltage
100...240V AC (-15...+10%) or 24V DC (-10...+10%)
240V
Rated Insulation Voltage
NA
3000V
Rated Impulse Voltage
NA
1500V
Dielectric Withstand
1500V AC
Operating Frequency
47...63 Hz
Control Power Ride Through
22 mS
Max Output of 24V DC Internal Supply
300mA
(Terminals 8 & 12)
Control Module Battery Type
CR 2032
DV/DT Protection

242

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Specifications

Appendix A

Table 118 - Control Module Standard Input/Output Ratings


Type

UL/CSA/NEMA
IEC
Control Module Standard Control Inputs: Terminals 10 & 11

Normal Operating Voltage

24V DC

Operating Voltage Range

15...30V DC

On-State
Off State

Current Minimum

2.8 mA

Voltage Minimum

10V DC

Current Maximum

3 mA

Voltage Maximum

10.9V DC

Inrush Current Maximum

7 mA

Input Delay Time

On-to-Off: 30 mS; Off-to-On: 20 mS

Reverse Polarity Protection

Yes

Rated Insulation Voltage

NA

60V

Rated Impulse Voltage

NA

500V

500V AC

1000V AC

Dielectric Withstand

Control Module Standard Outputs: Terminals 4/5 and 6/7


Type of Control Circuit

Electromagnetic Relay

Number of Contacts per Relay

Type of Contacts

Programmable N.O./N.C.

Type of Current

AC

Rated Operational Current

3 A @ 120V AC, 1.5 A @ 240V AC

Conventional Thermal Current Ith


AC/DC

5A

Make/Brake VA

3600/360

Utilization Category

B300/AC-15
0.024 mA @ 24V

Off-State Leakage Current

0.12 mA @ 120V
0.24 mA @240V

Electrically held closed

Table 119 - Control I/O Wiring Terminals


Terminal Style

M3 Screw Clamp

Terminal Wire Size

Terminal Type

Removable

Wire Strip Length

0.2...2.5 mm2 (24...14 AWG)


7.0 mm (0.27 in.)

Screw Terminal Torque

0.8 Nm (7.0 lbin)

Maximum Torque

0.8 Nm (7.0 lbin)

Applies to Control Module Standard I/O and 150-SM Expansion Module Terminals (150-SM2, 150-SM3, 150-SM4 Terminals).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

243

Appendix A

Specifications

Table 120 - Cat. No. 150-SM4 Optional Digital Control Input/Output Ratings
Type

UL/CSA/NEMA

IEC

150-SM4 Optional Digital Control Inputs: Terminals A1 & A2


Normal Operating Voltage

100...240V AC

Operating Voltage Range

85V...264V AC @ 47 Hz63 Hz

On-State
Off State

Current Minimum

9.7 mA @ 47 Hz; 9.7 mA @ 62.4 Hz

Voltage Minimum

74.5 V AC @ 47 Hz; 55.9 V AC @ 62.4 Hz

Current Maximum

9.0 mA @ 47 Hz; 9.3 mA @ 62.4 Hz

Voltage Maximum

68.8 V AC @ 47 Hz; 53.6 V AC @ 62.4 Hz

Inrush Current Maximum

3.64 A

Input Delay Time

On-to-Off: 30 mS; Off-to-On: 25 mS

Rated Insulation Voltage

NA

240V

Rated Impulse Voltage

NA

3000V

1600V AC

2000V

Dielectric Withstand

150-SM4 Optional Digital Control Inputs: Terminals A3 & A4


Normal Operating Voltage

100...240V AC

Operating Voltage Range

85V...264V AC @ 47...63 Hz

On-State
Off State

Current Minimum

5.1 mA @ 47 Hz; 5.0 mA @ 62.4 Hz

Voltage Minimum

74.5 V AC @ 47 Hz; 55.8 V AC @ 62.4 Hz

Current Maximum

4.7 mA @ 47 Hz; 4.8 mA @ 62.4 Hz

Voltage Maximum

68.6 V AC@ 47 Hz; 53.5 V AC @ 62.4 Hz

Inrush Current Maximum

3.64 A

Input Delay Time

On-to-Off: 30 mS; Off-to-On: 25 mS

Rated Insulation Voltage

NA

240V

Rated Impulse Voltage

NA

3000V

1600V AC

2000V

Dielectric Withstand

150-SM4 Optional Digital Outputs: Terminals A6/A7, A8/A9, A10/A11


Type of Control Circuit

Electromagnetic Relay

Number of Contacts per Relay

Type of Contacts

Programmable N.O./N.C.

Type of Current

AC

Rated Operational Current

3 A @ 120V AC, 1.5 A @ 240V AC

Conventional Thermal Current Ith


AC/DC

5A

Make/Brake VA

3600/360

Utilization Category

B300/AC-15
0.024 mA @ 24V

Off-State Leakage Current

0.12 mA @ 120V
0.24 mA @240V

Meets IEC Type 2 Specifications for Inputs per EN 60947-1 for 240V AC only.
Electrically held closed.

244

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Specifications

Appendix A

Table 121 - Cat. No. 150-SM3 Optional Analog Control Input/Output Ratings
Cat. No. 150-SM3 Optional Analog Control Inputs: Terminals B5B10
Number of Inputs

2 differential inputs

Normal Operating Input Ranges


Full Scale Operating Input Ranges
Input Resolution

10V, 010V, 05V, 15V, 020 mA, 420 mA


10.5V, 010.5V, -0.55.25V, 0.55.25V, 021 mA, 3.521 mA
16 bit (sample rate = 60 Hz)/13 bit (sample rate = 250 Hz)
Filter dependent: 100 ms (sample rate = 60Hz);24 ms
(sample rate = 250 Hz)

Data Refresh Rate


Rated Working Voltage

24V DC / 17V AC

Common Mode Voltage Range

10V DC / channel
220 k: voltage mode

Input Impedance

249 : current mode

Input Channel Diagnostics


Open Circuit Detection Time
Maximum Overload at Input Terminals
External Calibration

Over and Under Range and Open Circuit


Positive Full Scale Reading: within 3 seconds (max)
Voltage: 24V DC continuous at 0.1 mA
Current: 30 mA continuous at 7V DC
Not required: auto-calibration performed by the module if required to
meet specs.

Module Isolation to Control Board


Removable Terminal Block

Yes (1000V AC)


Yes (Cat. No.150-SM3RTB as a spare replacement part)
Belden 8760 (or equiv.) 0.750 mm2 (18 AWG twisted pair 100% shield
with drain)

Cable Type

Cat. No. 150-SM3 Optional Analog Control Outputs: Terminals B1B4


Number of Outputs
Normal Operating Ranges
Full Scale Operating Ranges
Output Resolution
10.5V, 0 10.5V, -0.55.25V,
021 mA, 3.5 21 mA

2 Single-ended
10V, 010V, 05V, 020 mA, 420 mA
10.5V, 010.5V, -0.55.25V, 021 mA, 3.521 mA
16 bit (15 plus sign bipolar)

0750

Resistive Load on Current Output


Load Range on Voltage Output

1 k at 10V DC

Max. Inductive Load (Current Outputs)

15 mH

Max. Capacitive Load (Voltage Outputs)

100 F

Overall Accuracy

Voltage Terminal: 0.5% full scale at 25 C


Current Terminal: 0.35% full scale at 25 C

Accuracy Drift with Temperature

5 PPM / C

Output Impedance

15 (typical)

Open and Short-Circuit Protection

Yes

Maximum Short-Circuit Current

45 mA

Output Overvoltage Protection

Yes

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

245

Appendix A

Specifications

SCPD Performance , Type 1


Table 122 - SCCR List Standard Capacity Fault
SCPD Performance
Motor Connection Type Catalog
Number

Type 1
Current
Non-Time Delay Fuse
Rating [A]
Max.
Amps
Standard
Typical
Available
Fault (kA)

Line

Inside Delta

10

Time Delay Fuse

Max.

150-SB1N*

90

250

350

150-SB2N*

110

300

400

150-SB3N*

140

400

150-SB4N*

180

150-SC1N*

210

150-SC2N*

260

Max.
Amps
Standard
Typical
Available
Fault (kA)
10

500
500

18

600

18

700
800

Inverse Time (Thermal Magnetic)


Circuit Breaker
Max.

150

200

175

225

Max.
Amps
Standard
Typical
Available
Fault (kA)
10

Max.

225

350

250

300

225

300

350

400

300

400

450

500

350

450

450

500

500

700

600

800

18

500

600

600

700

150-SC3N*

320

150-SD1N*

361

150-SD2N*

420

1200

700

800

1000

1200

150-SD3N*

520

1200

800

1000

1200

1200

150-SB1N*

155

250

300

350

450

150-SB2N*

190

500

300

400

450

500

150-SB3N*

242

700

400

500

600

700

150-SB4N*

311

800

500

600

700

800

150-SC1N*

363

600

800

800

1000

150-SC2N*

450

1200

700

1000

1000

1200

150-SC3N*

554

1600

800

1200

1200

1600

150-SD1N*

625

1000

1200

1200

1600

150-SD2N*

727

2000

1200

1600

1600

2000

150-SD3N*

900

2500

1200

2000

2000

2500

30 / 18

18

30

42

1000

450

1000

1600

30 / 18

18

30

42

30 / 18

18

30

42

800

800

800

1000

Consult local codes for proper sizing of short-circuit protection.


Basic Requirements for Type 1 Coordination: Under the short-circuit condition, the starter shall cause no danger to persons or to the installation. The starter may not be
suitable for further service without repair or replacement of parts. For further details, see UL 508/CSA C22.2 No. 14 and EN 60947-4-2.
Non-time Delay Fuses: Class K5 up to 600 A, Class L above 600 A.
Time Delay Fuses: Devices rated 90180 A (155 311 A): Class RK5. Devices rated 210520 A (363900 A): Class RK5 or Class J up to 600 A, Class L above 600 A
UL/CSA (Type 1) & EN 60947-4-2 (Type 1) for Line-Connected Motors: Suitable for use on a circuit capable of delivering not more than the listed
maximum RMS symmetrical amperes (UL: 600V maximum, IEC: 690V maximum).
UL/CSA applications = 30kA, 600V maximum. IEC applications = 18kA, 690V maximum
UL/CSA (Type 1) & EN 60947-4-2 (Type 1) for Inside-the-Delta Connected Motors: Suitable for use on a circuit capable of delivering not more than the listed
maximum RMS symmetrical amperes (UL: 600V maximum, IEC: 600V maximum)

246

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Specifications

Appendix A

Table 123 - SCCR List High Capacity Fault


SCPD Performance
Motor
Connection
Type

Line

Inside Delta

Catalog
Number

Type 1 Coordination

Current
Rating [A]

Class J or Class L Fuse


Max. High
Capacity
Available
Fault
(600V)
[kA]
100

Inverse Time (Thermal Magnetic) Circuit Breaker

Amps

480V, 65kA Maximum

Typical

Max.

140U
Frame

Max.
Amps

Catalog
Number

Rating Plug

150-SB1N*

90

150

200

350

140U-M6D3-D35

N/A

150-SB2N*

110

175

225

300

140U-M6D3-D30

N/A

150-SB3N*

140

225

300

400

140U-M6D3-D40

N/A

150-SB4N*

180

300

400

400

140U-M6D3-D40

N/A

150-SC1N*

210

350

450

600

140U-M6D3-D60

N/A

150-SC2N*

260

450

500

700

140U-M6D3-D70

N/A

800

140U-M6D3-D80

N/A

1000

140U-N6L3-E12

140U-NRP3-E10

150-SC3N*

320

500

700

150-SD1N*

361

601

800

150-SD2N*

420

700

800

1200

140U-N6L3-E12

140U-NRP3-E12

150-SD3N*

520

800

1000

1200

140U-N6L3-E12

140U-NRP3-E12

150-SB1N*

155

250

300

450

140U-M6D3-D45

N/A

150-SB2N*

190

300

400

500

140U-M6D3-D50

N/A

150-SB3N*

242

400

500

700

140U-M6D3-D70

N/A

150-SB4N*

311

500

600

700

140U-M6D3-D70

N/A

150-SC1N*

363

601

800

1000

140U-N6L3-E12

140U-NRP3-E10

150-SC2N*

450

700

1000

1200

140U-N6L3-E12

140U-NRP3-E12

150-SC3N*

554

800

1200

1200

140U-N6L3-E12

140U-NRP3-E12

150-SD1N*

625

1000

1200

1600

140U-R6L3-E20

140U-R20RP3-E16

150-SD2N*

727

1200

1600

2000

140U-R6L3-E20

140U-R20RP3-E20

150-SD3N*

900

1200

2000

2000

140U-R6L3-E20

140U-R20RP3-E20

65

Consult local codes for proper sizing of short-circuit protection


Basic Requirements for Type 1 Coordination: Under the short-circuit condition, the starter shall cause no danger to persons or to the installation.
The starter may not be suitable for further service without repair or replacement of parts. For further details, refer to UL 508/CSA C22.2 No. 14 and EN
60947-4-2
High Capacity fault ratings when used with time delay Class J or time delay Class L fuse
Circuit breaker must be of the designated 140U Frame
Other circuit breakers pending

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

247

Appendix A

Specifications

Table 124 - Semiconductor Fusing and Type 2 Coordination Ratings


Semiconductor (SCR) Fusing
Catalog
Number

Current Rating

North America

Type 2 Coordination Per EN 60947-4-2

Line

Inside
Delta

I2t
Reference
(103 A2s)

150-SB1N*

90

155

92

150-SB2N*

110

190

95

A70QS175

6,9URD30*0200

150-SB3N*

140

242

100

A70QS200

6,9URD30*0250

150-SB4N*

180

311

106

A70QS250

6,9URD31*0315

150-SC1N*

210

363

200

A70QS350

6,9URD30*0315

150-SC2N*

260

450

238

A70QS400

6,9URD31*0400

150-SC3N*

320

554

320

A70QS450

6,9URD31*0450

150-SD1N*

361

625

1000

A70QS500

6,9URD31*0500

150-SD2N*

420

727

1100

A70QS600

6,9URD31*0630

150-SD3N*

520

900

1200

A70QS700

6,9URD31*0700

Max.
Available
Fault (480V)
[kA]

Fuse Part
Number

Max. Available Fault (500V)


[kA]

Fuse Part Number

65

A70QS150

65

6,9URD30*0200

Consult local codes for proper sizing of short-circuit protection


Calculated only, NOT tested.
Fuse size based on a start profile of 350% of the controller maximum current rating for 10 seconds. Contact Technical Support at
raictechsupport@ra.rockwell.com or 440-646-5800 for applications with a longer start time or higher starting current.
Basic Requirements for Type 2 Coordination: Per EN 60947-4-2 under short-circuit conditions, the device shall cause no danger to persons or
installation and shall be suitable for further use.
For Line Connected Motors, connect fuses to the SMC-50 in line with three-phase power terminals L1, L2, and L3
For Delta Connected Motors, connect fuses to the SMC-50 inside the delta after terminals L1-T6, L2-T4, and L3-T5.
Ferraz Shawmut - Mersen part number

248

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Specifications

Appendix A

Additional Specifications
Table 125 - Control Power Requirements (Max. Control Circuit Consumption)
Description
Base Power Draw: Control
Module with Heat Sink Fan

Option Power Adder

Control Voltage

Current Range [A]

100240V AC

24V DC

90180

150 VA

75 W

210320

150 VA

75 W

361520

300 VA

300 W

Human Interface Module (HIM)

10 VA

2W

150-SM2

30 VA

4W

150-SM3

30 VA

4W

150-SM4

50 VA

2W

150-SM6

5 VA

1W

20-COMM-X

25 VA

4W

Heatsink fans are powered from the same source as the control module. The 100240V AC fans can be either 110/120V AC
or 220/240V AC (auto-configured).

Add to Base power using the formula below to obtain total power requirements.
Max. 1 of each option type per control module

Table 126 - Continuous Duty Power Structure Heat Dissipation at Rated Current
Description

Heat Dissipation
[W]

Current Range [A]

Controller Rating [A]

90

270

110

330

140

420

180

540

210

630

260

780

320

960

361

1083

420

1260

520

1560

Power Calculation
Max. total power
dissipation

Base Power

Options

Power Structure

Watts

Example: 361 A device with a 20-COMM-X module, HIM, and Cat. No.
150-SM4
Max. total power
dissipation

300
Base Power

(25 + 10 + 50)
Options

1083
Power Structure

Watts

Max. total power dissipation = 1468 Watts

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

249

Appendix A

Specifications

Table 127 - Additional Electrical Ratings


PTC Input Ratings (150-SM2 Required)
Response Resistance

3400 150

Reset Resistance

1600 100

Short-Circuit Trip Resistance

25 10

Max. Voltage at PTC Terminals (RPTC = 4 k)

< 7.5V

Max. Voltage at PTC Terminals (RPTC = open)

30V

Max. Number of Sensors (wired in series)

Max. Cold Resistance of PTC Sensor Chain

1500

Response TIme

800 mS

Table 128 - Environmental and Mechanical Specifications


Environmental
Operating Ambient Temperature Range
(surrounding air ambient)

-20...+40 C (-4...+104 F) (no derating) For operation at 40 C...65


C (104...149 F); see Thermal Wizard.

Storage & Transportation Temperature Range

-25...+75 C (-13...+167 F)

Altitude

2000 m (6560 ft.) without derating For operation at 2000...7000 m


(6560...22965 ft.), see Thermal Wizard.

Humidity

5...95% (non-condensing)

Pollution Degree

Mounting Position

Vertical

Atmospheric Protection

ANSI/ISA - 71.04-2013; Class G3 Environment


Mechanical

Operational

Resistance
to Vibration

Non-Operational

Resistance
to Shock

Non-Operational

Operational

Construction

90...520 A
90...520 A

15 G
30 G

Power Poles

Heatsink Hockey Puck Thyristor Modular Design

Control Modules

Thermoset & Thermoplastic moldings

Metal Parts
Power Terminal Lugs
Terminals

plated brass, copper, or steel


90...180 A

one 10.5 mm (0.41 in.) hole per power pole

210320 A

two 10.5 mm (0.41 in.) holes per power pole

361520 A

two 13.5 mm (0.53 in.) holes per power pole

M3 screw clamp

clamping yoking connection

Power Terminal Markings


Control Terminals

250

1.0 G Peak, 0.15 mm (0.006 in.) displacement


2.5 G Peak, 0.38 mm (0.015 in.) displacement

NEMA, CENELEC EN50 012

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Specifications

Appendix A

Table 129 - Other Specifications


Other EN/IEC
EMC Emission
Levels

Conducted Radio Frequency Emissions


Radiated Emissions
Electrostatic Discharge

EMC Immunity Radio Frequency Electromagnetic Field


Levels
Fast Transient

Class A (per EN 60947-4-2)


8 kV air discharge
per EN 60947-4-2

Surge Transient
Overload Characteristics

Current Range

Line

Delta

90

30...90

52...155

110

37...110

65...180

140

47...140

82...242

180

60...180

104...311

210

70210

122363

260

87260

151450

320

107320

186554

361

120361

210625

420

140420

243727

520

174520

302900
2t algorithm

Overload Type
Trip Classes

electronic using an I
5 to 30

Trip Current Rating

118% of motor FLC

Number of Poles

Certifications

CE marked for low voltage directive 73/23/EEC, 93, 68, EEC UL


Listed (File No. E96956)

Open-Type Controllers

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

251

Appendix A

252

Specifications

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Appendix

Parameter Information

SMC-50 Information
Number

Name

1
2
3

Units

Table 130 - Parameter 118


Min./Max.
[Default]

Enum Text

A-B
Volt
B-C

0/700
[0]

NA

Displays the Phase A to Phase B voltage applied to the SMC at the


supply terminals.
Displays the Phase B to Phase C voltage applied to the SMC at the
supply terminals.

C-A

Displays the Phase C to Phase A voltage applied to the SMC at the


supply terminals.

Ave

Displays the average of the three phase currents flowing through the
SMC Power section to the load.

6
7

Current
Phase

Read/Write
Access

Displays the calculated average voltage of the applied three phase to


phase line voltages being measured by the SMC-50.

PP Ave
Volts
Phase

Description

A
Amps
B

0/15000
[0]

NA

Displays the Current flowing through the Phase A power pole of the
SMC Power section to the load.
Displays the Current flowing through the Phase B power pole of the
SMC Power section to the load.

Displays the Current flowing through the Phase C power pole of the
SMC Power section to the load.

Torque

-5.0/30.0
[0.0]

NA

Displays the true electromechanical torque calculated based on current


and voltage feedback. In order for this reading to display correctly the
value for Rated Torque parameter must be set.

10

Real Power

MW

-1000.000/1000.00
[0.000]

NA

Displays the total Real Power.

11

Real Energy

MWH

-1000.000/1000.00
[0.000]

NA

Displays the Real Energy, where Real Energy equal to Real Power X
Time. This parameter is updated every 1/10 of an hour (6 minutes).

12

Elapsed Time

Hours

0.0/50000.0
[0.0]

NA

Displays the elapsed motor running time since the last reset of the
Elapsed timer by the user.

13

Elapsed Time 2

Hours

0.0/50000.0
[0.0]

NA

Displays the elapsed motor running time since the control module was
manufactured.

14

Running Time

Hours

0.0/50000.0
[0.0]

NA

Displays the time the motor has been running since the last start
command. This value will go to zero when a motor is restarted after a
stop command or fault.

15

Energy Savings

0/100
[0]

NA

Displays the energy saving when the energy saving mode is enabled.

Provides the user the ability to reset various timers and counters by
selecting the appropriate reset option.

Ready

Ready state of parameter, waiting for selection.

16

Meter Reset

0/4
[0]

Elapsed Timer

Zero the elapsed timer.

Time to PM

Resets the Time to PM timer to the value set in parameter PM Hours


(126).

Starts to PM

Reset the Starts to PM counter to the value set in parameter PM Starts


(127).

R/W

17

Power Factor

-1.00/1.00
[0.00]

NA

Displays the Cosine of the phase angle between the voltage and
current. A positive values is leading and negative value is lagging.

18

Motor Therm
Usage

%MT
U

0/200
[0]

NA

Displays the thermal capacity utilized in the motor overload algorithm. A


value of 100% will result in a motor overload fault. This value can go
over 100% depending on the rate at which the motor is heating before
an overload trip.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

253

Appendix B

Parameter Information

Table 131 - Parameter 1942

Number

Name

Units

19

Time to OL Trip

Secs

20

Time to OL
Reset

21

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

0/1000
[0]

NA

Displays the estimated time before an overload trip will occur if the present
operating conditions persist. If operating below ultimate trip current the value will
display the max value.

Secs

0/1000
[0]

NA

Displays the estimated time until the motor overload fault can be reset. The MTU
reset level is set by the OL reset parameter (80).

Time to PM

Hrs

0/1000
[0]

NA

Displays the estimated time to a preventive maintenance event if enabled. The


scheduled time for a PM event is set by the user via the PM Hours parameter
(126).This value can be reset by the user after an event via the meter reset parameter
(16).

22

Starts to PM

0/50000
[0]

NA

Displays the estimated number of starts to a PM event if enabled. The scheduled


number of starts for a PM event is set by the user via the PM Starts parameter
(127).This value can be reset by the user after an event via the meter reset parameter
(16).

23

Total Starts

0/30000
[0]

NA

Displays the total number of SMC starts. The SMC keeps a Start Counter which will
be incremented each time the SMC is started. This parameter cannot be reset by the
customer and leaves the factory with a value of 0.

24

25

26

Start Time

Displays the measured start time of the previous start.


Displays the measured start time of the 2nd previous start.
Secs

0/1000
[0]

NA

Displays the measured start time of the 3rd previous start.

27

28

Displays the measured start time of the 5th previous start.

29

Displays the measured peak current of the previous start.

30
31

Peak
Current

32

33

34

Motor Speed

Displays the measured start time of the 4th previous start.

2
3

Amps

0/150000
[0]

Displays the measured peak current of the 2nd previous start.


NA

Displays the measured peak current of the 3rd previous start.

Displays the measured peak current of the 4th previous start.


Displays the measured peak current of the 5th previous start.
%

0/100
[0]

NA

Displays the estimated motor speed during starting and stopping. This parameter is
only valid when using the linear speed starting or linear speed stopping modes.

35

THD Va

Measures the THD of the applied Phase A line voltage.

36

THD Vb

Measures the THD of the applied Phase B line voltage.

37

THD Vc

38

THD Vave

39

THD Ia

40

THD Ib

41

THD Ic

42

THD Iave

0/1000.0
[0]

NA

Measures the THD of the applied Phase C line voltage.

Displays the calculated average of the three voltage THD measurements.


Measures the THD of the applied Phase A current.
%

0/1000.0
[0]

NA

Measures the THD of the applied Phase B current.


Measures the THD of the applied Phase C current.
Displays the calculated average of the three current THD measurements.

THD = A Power Quality measurement that provides the ability to measure total harmonic distortion levels.

254

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 132 - Parameter 4351

Number

43

Name

Product Status

Units

Min./Max.
[Default]

0/65535
[0]

Enum Text

Description

The product Logic Status is made available to all DPI devices and is
also available as a bit enumerated parameter "Product Status". The
bits in this parameter correspond with the bits in the Product Logic
Status defined for DPI.

bit 0 = Enabled/Ready

1 Ready
0 Not Ready

bit 1 = Running

1 Power Applied to Motor (Gating SCRs or Bypass closed)


0 Power NOT Applied to Motor

bit 2 = Phasing

1 ABC Phasing
0 CBA Phasing

bit 3 = Phasing Active

1 3-phase is valid
0 No valid 3-phase detected

bit 4 = Starting (Accel)

1 Performing a Start Maneuver (slow speed not included)


0 Not Performing a Start Maneuver

bit 5 = Stopping (Decel)

1 Performing a Stop Maneuver (coast to stop not included)


0 Not Performing a Stop Maneuver

bit 6 = Alarm

1 Alarm Present
0 No Alarm Present

bit 7 = Fault

1 Fault Condition Exists and hasnt been cleared


0 No Fault Condition

bit 8 = At Speed

1 Full Voltage Applied (Bypass or full SCR conduction)


0 Not Full Voltage Applied

bit 9 = Start/Isolate

1 Start/Isolate Contactor Enabled


0 Start/Isolate Contactor Disabled

bit 10 = Bypass

1 Bypass Contactor Enabled


0 Bypass Contactor Disabled

bit 11 = Ready

1 indicates that the SMC is ready to accept a Start command. The


device is not faulted or in the process of stopping, starting or jogging.

Read/Write
Access

bit 12 - 13 = Reserved

Always 0.

bit 14 = Input #1

Control Module Input #1 Status. 1 = Input Closed.

bit 15 = Input #2

Control Module Input #2 Status. 1 = Input Closed.


Provides the user the ability to select the type of motor connection the
SMC is being applied to, 'Line' or 'Delta'. It can also be set to 'Auto
Config' and the SMC will determine the motor connection.

R/W

44

Motor Config

0/2
[2]

Line
Delta
[Auto]

45

Motor Connection

0/1
[0]

[Line]
Delta

Displays the type of motor connection the SMC is configured to


operate with.

46

Line Voltage

Volt

0/700
[480]

NA

The Line voltage applied to the SMC L1, L2, L3 terminals.

R/W

47

Rated Torque

Nm

0/10000
[10]

NA

Enables the user the ability to enter the rated torque of the motor as
read from the motor specifications (typically nameplate). This is
required for proper torque mode starts and stops.

R/W

48

Rated Speed

RPM

0/5
[3]

750, 900, 1500, [1800],


3500, 3600

49

Starting Mode

0/5
[2]

50

Ramp Time

Sec

0.0/1000.0
[10.0]

51

Initial Torque

%LRT

0/90
[70]

Enables the user the ability to enter the rated motor speed as read
from the motor specifications (typically nameplate). This is required
for proper torque mode starts and stops.
Used to program the SMC controller for the type of starting mode that
best fits the application.

Full Voltage

Apply full voltage to the motor at start.

Current Limit

Apply limited current for a programmed period of time.

[Soft Start]

Slowly increase current to load over a programmed period of time.

Linear Speed

Increase current to cause a linear acceleration of the motor.

Torque Ramp

Slowly increase torque generated by motor over fixed period of time.

R/W

R/W

Pump Start

Special starting algorithm for pump applications.

NA

Enables the user the ability to configure the time period during which
the controller will ramp the output voltage.

R/W

NA

The initial reduced voltage output level for the voltage ramp is
established and adjusted with this parameter.

R/W

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

255

Appendix B

Parameter Information

Table 133 - Parameter 5257

Number

Name

Units

52

Max. Torque

53

Cur Limit Level

54
55

Min./Max.
[Default]

Description

0/300
[250]

NA

Gives the user ability to configure the maximum torque limit of a torque ramp during
a torque start operation.

R/W

%FLC

50/600
[350]

NA

The current limit level that is applied for the ramp time selected.

R/W

Kickstart Time

SEC

0.0/2.0
[0.0]

NA

A boost of current is applied to the motor for this programmed time.

R/W

Kickstart Level

%LRT

0/90
[0]

NA

Gives the user the ability to adjust the amount of current boost applied to the motor
during the kickstart period.

R/W

Allows the user to select the operation of Terminal 11, Input 1 on the control module.

Disable

Disable the input - ignores any assertion to Input 1, Terminal 11.

Start

Initiates a start as set up by the start parameters at Input 1, Terminal 11 (High).

Coast

Initiates a coast stop.- no current to motor at Input 1, Terminal 11 (Low).

Stop Option

Initiates a stop maneuver as set up by the stopping parameters at Input 1 (Low).

[Start/Coast]
Start/Stop
56

Input 1

0/13
[4]

Slow Speed

0/13
[0]

0- Initiates a stop maneuver as set up by stopping parameters


1- Initiates a start as set up by the start parameters

Runs motor in slow speed mode as set up by slow speed parameters (High).

if Input 1 =

0 - Use Motor Overload Class 1


1 - Use Motor Overload Class 2

Fault

A fault condition forced if Input 1= 1.

Fault NC

A fault condition forced if Input 1 = 0.

Clear Fault

Clear a fault from input 1 Terminal 11 (High).

Emerg Run

Allow motor to run in emergency run mode if asserted from Input 1, Terminal 11 does not start motor (High).

Motor Heater

Run motor heating algorithm if asserted from Input 1, Terminal 11 (High).

Allows the user to select the operation of Terminal 10, Option Input 2, on the control
module.

[Disable]

Disable the input - ignores any assertion to Input 2 Terminal 10.

Start

Initiate a start as set up by the start parameters at Input 2 Terminal 10 (High).

Coast

Initiates a coast stop.- no current to motor at Input 2 Terminal 10 (Low).

Stop Option

Initiates a stop maneuver as set up by the stopping parameters at Input 2 (Low).

Slow Speed

If Input 2=

0 - Stops motor
1- Initiate a start as set up by the start parameters

If Input 2 =

0- Initiate a stop maneuver as set up by stopping parameters


1- Initiate a start as set up by the start parameters

Runs motor in slow speed mode as set up by slow speed parameters (High).
If Input 2=

0 - Use Starting Mode 1


1 - Use Starting Mode 2

OL Select

If Input 2 =

0 - User Motor Overload Class 1


1 - Use Motor Overload Class 2

Fault

A fault condition is forced if Input 2= 1.

Dual Ramp

256

if Input 1 =

OL Select

Start/Stop

0 - Stops motor
1- Initiates a start as set up by the start parameters

0 - Use starting mode 1


1 - Use starting mode 2

Start/Coast

Input 2

if Input 1 =

if Input 1 =

Dual Ramp

57

Read/Write
Access

Enum Text

Fault NC

A fault condition is forced if Input 2 = 0.

Clear Fault

Clear a fault from Input 2 (High).

Emerg Run

Allow motor to run in emergency run mode if asserted on Input 2 - does not start
motor (High).

Motor Heater

Run motor heating algorithm if asserted at Input 2 (High).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

R/W

Parameter Information

Appendix B

Table 134 - Parameter 5871

Number

58

Name

Starting Mode 2

Units

Min./Max.
[Default]

0/5 [2]

Enum Text

Description

Allows the user to program an alternate starting mode for the SMC-50 that suits
the application.

Full Voltage

Apply full voltage to the motor at start.

Current Limit

Apply limited current for a programmed period of time.

[Soft Start]

Slowly increase current to load over a programmed period of time.

Linear Speed

Increase current to cause a linear acceleration of the motor.

Torque Ramp

Slowly increase torque generated by the motor over a fixed period of time.

Read/Write
Access

R/W

Pump Start

Special starting algorithm for pump applications.

NA

Allows the user to set an alternate time period during which the controller will
ramp the output voltage.

R/W

59

Ramp Time 2

Sec

0.0/1000.0
[10.0]

60

Initial Torque 2

%LRT

0/90
[70]

NA

Allows the user to set an alternate initial reduced voltage output level for the
voltage ramp.

R/W

61

Max. Torque 2

0/300
[250]

NA

Allows the user to set a alternate maximum torque limit of a torque ramp during a
torque start operation.

R/W

62

Cur Limit Level 2

%FLC

50/600
[350]

NA

Allows the user to set an alternate current limit level that is applied for the ramp
time selected.

R/W

63

Kickstart Time 2

Sec

0/2
[0]

NA

Allows the user to set an alternate boost current to be applied to the motor for the
programmed time.

R/W

64

Kickstart Level 2

%LRT

0/90
[0]

NA

Allows the user to set an alternate adjustment of the amount of current applied to
the motor during the kickstart period.

R/W

Allows the user to program the SMC-50 for the type of stopping that best suits the
application.

[Coast]

Coast-to-Rest

Soft Stop

Slowly reduces current by reducing voltage applied to the motor over a


programmed period of time.

Linear Speed

Stops the motor following a linear speed ramp over a programmed period of time.

Pump Stop

Slowly reduces current by reducing voltage applied to the motor using the pump
stop algorithm over a programmed period of time.

SMB

Brakes the motor to a stop using an SCR firing pattern to create current flow to
brake the motor per the configuration of the braking parameters.

External
Brake

Closes an external contactor to apply braking current to the motor.

65

Stop Mode

0/5
[0]

R/W

66

Stop Time

Sec

0/999
[0]

NA

Sets the time period which the controller will ramp the voltage during a stopping
maneuver.

R/W

67

Backspin Timer

Sec

0/999
[0]

NA

Avoids starting into a backspin condition. The timer begins counting after a stop is
completed (coast, stop maneuver, fault etc). All start inputs will be ignored until
the backspin timer has timed out.

R/W

68

Pump Pedestal

0/50
[0]

NA

Provides the ability to adjust the pump algorithm slightly for different applications.
Typically, this is used to shorten the ramp time before the SMC-50 starts to get
aggressive in its pump stopping maneuver.

R/W

69

Braking Current

%FLC

0/400
[0]

NA

Provides the ability to program the intensity of the braking current applied to the
motor.

R/W

Identifies the load type to enable appropriate braking algorithms.


70

71

Load Type

High Eff Brake

0/3
[0]

0/99
[0]

Standard

High Inertia

High Friction

Ramp 89

Special braking mode that reduces braking torques.

NA

Adds additional time to a braking sequence after the SMC-50 detects a zero speed
condition that indicates the end of the braking sequence. Can adjust if additional
time is needed to stop the load.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

R/W

257

Appendix B

Parameter Information

Table 135 - Parameter 7294

Enum Text

Description

Read/Write
Access

-15/15
[10]

NA

Allows the user to program the slow speed that best suits the application.

R/W

%FLC

0/350
[0]

NA

Provides braking from slow speed. If set to 0, no braking will be provided. Any
other setting will result in motor braking when the slow speed operation is
terminated.

R/W

Overload Class

5/30
[10]

NA

Sets the desired trip class of internal solid state overload. Overload fault and
alarms are enabled and disabled in the Starter Fault En and Starter Alarm
parameters.

R/W

76

Overload Class 2

5/30
[10]

NA

Allows user to set the internal solid state overload to an alternate trip class. This
Trip Class is used when an input (configured as overload select) is asserted.

R/W

77

Service Factor

0.01/1.990
[1.15]

NA

Parameter to enter the value of the motor's service factor from the nameplate.

R/W

78

Motor FLC

Amps

1.0/2200.0
[1.0]

NA

Parameter to enter the Full Load Current (FLC) value from the motor's nameplate.

R/W

79

Motor FLC 2

Amps

1.02200.0
[1.0]

N/A

Second motor FLC setting to be used when Overload #2 is selected using the
"Overload 2" input.

R/W

80

OL Reset Level

%MTU

1/99
[75]

NA

When the level of Motor Thermal Usage (MTU) drops below this limit after an OL
fault, an overload reset can occur. If restart is enabled, the motor overload will
automatically reset when the MTU drops below this level

R/W

81

OL Shunt Time

Secs

0/999
[0]

NA

Disables the overload from incrementing MTU for the selected time period after
a start or stop command is initiated.

R/W

82

OL Inhibit Time

Secs

0/999
[0]

NA

Disables the overload from tripping during slow speed and stopping maneuvers.
The MTU. Therm Usage continues to increment during these maneuvers.

R/W

83

Overload A Level

%MTU

0/100
[90]

NA

The MTU level that will set off an alarm when exceeded. The Overload bit the
Motor Alarm En parameter must be set to signal an alarm.

R/W

84

Locked Rtr F Lvl

%FLC

400/1000
[600]

NA

The peak phase current to the load that, if exceeded for the time period defined
in Locked Rtr Delay, will signal a fault. The Locked Rotor bit in the Motor Fault En
parameter must be set to signal a fault.

R/W

85

Locked Rtr F Dly

Secs

0.1/100.0
[0.1]

NA

The time period that the peak phase current exceeds the Locked Rtr F Level to
signal a fault. The Locked Rotor bit in the Motor Fault En parameter must be set
to signal a fault.

R/W

86

Underload F Lvl

%FLC

0/99
[0]

NA

If phase current drops below this level for the period of time set in Underload F
Dly parameter, an Underload Fault will be signaled. The Underload bit in the
Motor Fault En parameter must be set to signal a fault.

R/W

87

Underload F Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the phase current must be below the level set in the
Underload F Level parameter before a underload fault is signaled. The Underload
bit in the Motor Fault En parameter must be set to signal a fault.

R/W

88

Underload A Lvl

%FLC

0/99
[0]

NA

If phase current drops below this level for the period of time set in Underload A
Dly parameter, an Underload Alarm will be signaled. The Underload bit in the
Motor Alarm En parameter must be set to signal a alarm.

R/W

89

Underload A Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the phase current must be below the level set in the
Underload A Level parameter before an Underload Alarm is signaled. The
Underload bit in the Motor Alarm En parameter must be set to signal a alarm.

R/W

90

MWatts Ov F Lvl

MW

0.000/1000.00
[0.000]

NA

If the Real Power exceeds this level for the time period set in MWatts Ov F Dly
parameter, an MWatts Ov fault will be signaled. The MWatts Ov bit in the Motor
Fault En parameter must be set to signal a fault.

R/W

91

MWatts Ov F Dly

Secs

0.1/99.0
[0.1]

NA

The time period that Real Power must exceed MWatts Ov F Lvl to signal a fault.
The MWatts Ov bit in the Motor Fault En parameter must be set to signal fault.

R/W

92

MWatts Ov A Lvl

MW

0.000/1000.00
[0.000]

NA

If the Real Power exceeds this level for the time period set in MWatts Ov A Dly
parameter, a MWatts Ov Alarm will be signaled. The MWatts Ov bit in the Motor
Alarm En parameter must be set to signal an alarm.

R/W

93

MWatts Ov A Dly

Secs

0.1/99.0
[0.1]

NA

The time period that Real Power must exceed MWatts Ov A Lvl to signal an
alarm. The MWatts Ov bit in the Motor alarm En parameter must be set to signal
an alarm.

R/W

94

MWatts Un F Lvl

MW

0.000/1000.00
[0.000]

NA

If the Real Power drops below this level for the time period set in MWatts Un F
Dly parameter, an MWatts Un Fault will be signalled. The MWatts Un bit in the
Motor Fault En parameter must be set to signal a fault.

R/W

Number

Name

Units

72

Slow Speed

73

Slow Brake Cur

75

258

Min./Max.
[Default]

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 136 - Parameter 95113

Number

Name

Units

95

MWatts Un F Dly

Secs

96

MWatts Un A Lvl

97

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

0.1/99.0
[0.1]

NA

The time period that Real Power must drop below MWatts Un F Lvl to signal a
fault. The MWatts Un bit in the Motor Fault En parameter must be set to signal a
fault.

R/W

MW

0.000/1000.00
[0.000]

NA

If the Real Power drops below this level for the time period set in MWatts Un A
Dly parameter, an MWatts Un Alarm will be signaled. The MWatts Un bit in the
Motor Alarm En parameter must be set to signal an alarm.

R/W

MWatts Un A Dly

Secs

0.1/99.0
[0.1]

NA

The time period that Real Power must drop below MWatts Un A Level to signal
an alarm. The MWatts Un bit in the Motor Alarm En parameter must be set to
signal an alarm.

R/W

98

Undervolt F Lvl

%V

0/100
[90]

NA

If the average three phase line voltage drops below this level for the time period
set in the Undervolt F Dly parameter, an Undervolt fault will be signaled. The
Undervolt bit in the Starter Fault En parameter must be set to signal a fault.

R/W

99

Undervolt F Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the average three phase voltage must remain below
Undervolt F Level to signal a fault. The Undervolt bit in the Starter Fault En
parameter must be set to signal a fault.

R/W

100

Undervolt A Lvl

%V

0/100
[90]

NA

If the average three phase line voltage drops below this level for the time period
set in the Undervolt A Dly parameter, an Undervolt Alarm will be signaled. The
Undervolt bit in the Starter Alarm En parameter must be set to signal an Alarm.

R/W

101

Undervolt A Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the average three phase voltage must remain below
Undervolt A Lvl to signal an Alarm. The Undervolt bit in the Starter Alarm
parameter must be set to signal an Alarm.

R/W

102

Overvolt F Lvl

%V

100/199
[110]

NA

If the average three phase line voltage exceed this level for the time period set in
the Overvolt F Dly parameter, an Overvolt fault will be signaled. The Overvolt bit
in the Starter Fault En parameter must be set to signal a fault.

R/W

103

Overvolt F Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the average three phase voltage must exceed the Overvolt F
Level to signal a fault. The Overvolt bit in the Starter Fault En parameter must be
set to signal a fault.

R/W

104

Overvolt A Lvl

%V

100/199
[110]

NA

If the average three phase line voltage exceed this level for the time period set in
the Overvolt A Dly parameter, an Overvolt alarm will be signaled. The Overvolt bit
in the Starter Alarm parameter must be set to signal an alarm.

R/W

105

Overvolt A Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the average three phase voltage must exceed the Overvolt A
Level to signal an alarm The Overvolt bit in the Starter alarm En parameter must
be set to signal a alarm.

R/W

106

Volt Unbal F Lvl

1/25
[15]

NA

If the line-to-line voltage imbalance condition exceeds the Volt Unbal F Lvl for the
period set in Volt Unbal F Dly, a fault will be signalled. The Volt Unbal bit must be
set in the Starter Fault En parameter to signal a fault. See manual for details on
imbalance calculations.

R/W

107

Volt Unbal F Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the voltage imbalance exceeds the Volt Unbal F Lvl to signal
a fault. The Volt Unbal bit in the Starter Fault En parameter must be set to signal
a fault.

R/W

108

Volt Unbal A Lvl

1/25
[15]

NA

If the line-to-line voltage imbalance condition exceeds the Volt Unbal A Lvl for
the time period set in Volt Unbal A Dly, an alarm will be signalled. The Volt Unbal
bit must be set in the Starter Alarm parameter to signal a alarm. See manual for
details on imbalance calculations.

R/W

109

Volt Unbal A Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the voltage imbalance exceeds the Volt Unbal A Level to
signal a alarm. The Volt Unbal bit in the Starter Alarm parameter must be set to
signal a alarm.

R/W

110

Cur Imbal F Lvl

1/25
[15]

NA

If the line-to-line current imbalance condition exceeds the Cur Imbal F Lvl for the
time period set in Cur Imbal F Dly, a fault will be signalled. The Cur Imbal bit must
be set in the Motor Fault En parameter to signal a fault.

R/W

111

Cur Imbal F Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the current imbalance exceeds the Cur Imbal F Lvl to signal a
fault. The Cur Imbal bit in the Motor Fault En parameter must be set to signal a
fault.

R/W

112

Cur Imbal A Lvl

1/25
[15]

NA

If the line-to-line current imbalance condition exceeds the Cur Imbal A Lvl for the
time period set in Cur Imbal A Dly, an alarm will be signalled. The Cur Imbal bit
must be set in the Motor Alarm En parameter to signal a Alarm.

R/W

113

Cur Imbal A Dly

Secs

0.1/99.0
[3.0]

NA

The time period that the current imbalance exceeds the Cur Imbal A Lvl to signal
an alarm. The Cur Imbal bit in the Motor Alarm En parameter must be set to
signal an alarm.

R/W

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

259

Appendix B

Parameter Information

Table 137 - Parameter 114134

Number

Name

Units

114

Jam F Lvl

%FLC

115

Jam F Dly

116

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

0/1000
[1000]

NA

If the peak phase current exceeds the Jam F Lvl for the time period set in Jam F
Dly, a fault will be signaled. The Jam bit must be set in the Motor Fault En
parameter to signal a fault.

R/W

Secs

0.1/99.0
[0.1]

NA

The time period that the peak phase current exceeds the Jam F Lvl to signal a
fault. The Jam bit in the Motor fault En parameter must be set to signal a fault.

R/W

Jam A Lvl

%FLC

0/1000
[1000]

NA

If the peak phase current exceeds the Jam A Lvl for the time period set in Jam A
Dly, an alarm will be signaled. The Jam bit must be set in the Motor Alarm En
parameter to signal a alarm.

R/W

117

Jam A Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the peak phase current exceeds the Jam A level to signal an
alarm. The Jam bit in the Motor Alarm En parameter must be set to signal a
alarm.

R/W

118

THD V F Lvl

0/1000
[1000]

NA

If the average total harmonic distortion (THD) on the line voltage exceeds the
THD V F Lvl for the time period set in THD V F Dly, a fault will be signaled. The
THD V bit must be set in the Starter Fault En parameter to signal a fault.

R/W

119

THD V F Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the average THD on the line voltage exceeds the THD V F Lvl
to signal a fault. The THD V bit in the Starter Fault En parameter must be set to
signal a fault.

R/W

120

THD V A Lvl

0/1000
[1000]

NA

If the average THD on the line voltage exceeds the THD V A Lvl for the time
period set in THD V Dly, an alarm will be signaled. The THD V bit must be set in
the Starter Alarm parameter to signal a alarm.

R/W

121

THD V A Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the average THD on the line voltage exceeds the THD V A
Lvl to signal a alarm. The THD V bit in the Starter Alarm parameter must be set to
signal an alarm.

R/W

122

THD I F Lvl

0/1000
[1000]

NA

If the average THD on the phase current exceeds the THD I F Lvl for the period set
in THD I F Dly, a fault will be signalled. The THD I bit must be set in the Motor
Fault En parameter to signal a fault.

R/W

123

THD I F Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the average THD on the phase current exceeds the THD I F
Lvl to signal a fault. The THD I bit in the Motor Fault En parameter must be set to
signal a fault.

R/W

124

THD I A Lvl

0/1000
[1000]

NA

If the average THD on the phase current exceeds the THD I A Lvl for the time
period set in THD I A Dly, an alarm will be signaled. The THD I bit must be set in
the Motor Alarm En parameter to signal an alarm.

R/W

125

THD I A Dly

Secs

0.1/99.0
[0.1]

NA

The time period that the average THD on the phase current exceeds the THD I A
Lvl to signal an alarm. The THD I bit in the Motor Alarm En parameter must be set
to signal an alarm.

R/W

126

PM Hours

Hrs

1/100 [1000]

NA

This is a counter the user can set to generate an alarm or fault to signal a need
for preventive maintenance. The Hours to PM parameter is initialized to this
value and counts down when the motor is running.

R/W

127

PM Starts

1/50000 [100]

NA

This is a counter the user can set to generate an alarm or fault to signal a need
for preventive maintenance. The Starts to PM parameter is initialized to this
value and counts down each time the motor is started.

R/W

128

Starts per Hour

1/99 [99]

NA

The user can program the maximum number of starts within a sliding one-hour
window. Once the number of starts per hour is reached any additional starts will
cause a fault.

R/W

129

Freq High F Lvl

Hz

45/66 [63]

NA

The highest line voltage frequency that can be applied to the SMC-50 before
causing a Freq High F Lvl fault. The Freq High bit in the Starter Fault En parameter
must be set to signal a fault.

R/W

130

Freq Low F Lvl

Hz

45/66 [47]

NA

The lowest line voltage frequency that can be applied to the SMC-50 before
causing a Freq Low F Lvl fault.The Freq Low bit in the Starter Fault En parameter
must be set to signal a fault.

R/W

131

Freq High A Lvl

Hz

45/66 [63]

NA

The highest line voltage frequency that can be applied to the SMC-50 before
causing a Freq High F Lvl alarm. The Freq High bit in the Starter Alarm parameter
must be set to signal an alarm.

R/W

132

Freq Low A Lvl

Hz

45/66 [47]

NA

The lowest line voltage frequency that can be applied to the SMC-50 before
causing a Freq Low F Lvl alarm. The Freq Low bit in the Starter Alarm parameter
must be set to signal an alarm.

R/W

133

Restart Attempts

0/5 [0]

NA

Allows the user to enable the SMC-50 to auto-restart for up-to five attempts
after a thyristor has failed to fire and results in an open gate fault trip.

R/W

134

Restart Dly

Secs

0/60 [0]

NA

Provides a delay time prior to the SMC-50s attempt to restart the motor after a
fault.

R/W

260

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 138 - Parameter 135148

Number

Name

Units

Min./Max.
[Default]

Enum Text

Description

Read/Write
Access

Volt Unbal
Overvoltage
Undervoltage
Phase Rev
135

Strtr Restart En

Line Loss
Open Gate
Config Change

Allows the user to select which type of fault that the SMC-50 can try to restart
from once the restart delay period has expired. To enable a restart from a fault,
the function must be selected (1).
Restart Attempts, Parameter 133, and Restart Delay, Parameter 134, must be
configured.

R/W

Allows the user to enable faults associated with the control module. The bit for a
fault must be set (1) for the fault to be asserted.

R/W

Allows the user to enable alarms associated with the control module. The bit for
an alarm must be set (1) for the alarm to be asserted.

R/W

Freq
THD V
Future

136

Starter Fault En

Future

Volt Unbal

Overvoltage

Undervoltage

Phase Rev

[1]

Line Loss

[1]

Open Gate

Config Change

Freq

THD V
Volt Unbal
Overvoltage
Undervoltage
Phase Rev

137

Starter Alarm En

Line Loss
Open Gate
Config Change
Freq
THD V

138

139

140

Fault

141

First entry in the fault buffer and is the most recent fault to have occurred.
Second entry in the fault buffer.

0/1000
[0]

NA

Third entry in the fault buffer.

142

Fifth entry in the fault buffer. The oldest fault displayed in the fault buffer.

143

First entry in the alarm buffer and is the most recent alarm to have occurred.

144

Second entry in the alarm buffer.

145

146

Alarm

147

148

0/1000
[0]

Third entry in the alarm buffer.


NA

Fourth entry in the alarm buffer.

R/W

Fifth entry in the alarm buffer. There can be up to 100 events stored in the alarm
buffer. To see the whole buffer, go the diagnostics tab on the HIM or
DriveExplorer.

Logic Mask

R/W

Fourth entry in the fault buffer.

0/65535 [0]

NA

The bits in this parameter allow the user to enable (bit=1) or disable (bit=0) which
DPI ports the SMC-50 will accept Start and Maneuver commands from. Coast
Stop commands are always accepted from any port.
bit 1 = port 1 (On board HIM) [Default=0]
bit 2 = port 2(DPI port on control module) [Default=0]
bit 3 = port 3(DPI port on control module with splitter) [Default=0]
bit 4 = port 4(Internal Comm module) [Default=0]
bit 5-13 = unused
bit 14 = port 14 [DeviceLogix engine]
bit 15 = unused

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

261

Appendix B

Parameter Information

Table 139 - Parameter 149171

Number

149

150

151

152

Name

Units

Logic Mask Act

Write Mask Cfg

Write Mask Act

Port Mask Act

Min./Max.
[Default]

0/65535
[0]

0/65535
[7FFF]

0/65535
[0]

0/65535
[0]

Read/Write
Access

Enum Text

Description

NA

Displays which DPI port the SMC-50 will accept a start command from. It may be
different from the Logic Mask set by the local user if someone changes it over the
network.
bit 1 = port 1 (on board HIM)
bit 2 = port 2 (DPI port on control module)
bit 3 = port 3 (DPI port on control module with splitter)
bit 4 = port 4 (Internal Comm module)
bit 5-15 = reserved

NA

This bits in this parameter allow the user to enable (bit=1) or disable (Bit=0) which
DPI ports the SMC-50 will accept write commands from. Only selected ports can
modify parameters.
bit 1 = port 1 (on board HIM) [Default=1]
bit 2 = port 2 (DPI port on control module) [Default=1]
bit 3 = port 3 (DPI port on control module with splitter) [Default=1]
bit 4 = port 4 (Internal Comm module) [Default=1]
bit 5-15 = reserved [Default=0]

R/W

NA

Displays which DPI ports the SMC will accept write commands from that can
change parameters. It may be different from the Write Mask Cfg parameter setup
by the local user if someone changes it over the network.
bit 1 = port 1 (on board HIM)
bit 2 = port 2 (DPI port on control module)
bit 3 = port 3 (DPI port on control module with splitter)
bit 4 = port 4 (Internal Comm module)
bit 5-15 = reserved

NA

Displays which DPI ports are active on the control module and will accept
operational commands from.
bit 1 = port 1 (on board HIM)
bit 2 = port 2 (DPI port on control module)
bit 3 = port 3 (DPI port on control module with splitter)
bit 4 = port 4 (Internal Comm module)
bit 5-15 = reserved

153

A1

A1

154

A2

A2

155

B1

156

B2

157

Data In

C1

B1

0/159999
[0]

NA

This is the channel

B2
C1

158

C2

C2

159

D1

D1

160

D2

D2

161

A1

A1

162

A2

A2

163

B1

164

B2

165

Data Out

C1

B1

0/159999
[0]

NA

This is the channel

B2
C1

166

C2

C2

167

D1

D1

168

D2

In Datalink index, holding the parameter number of the


parameter that will be written to during Datalink
communications. A value of 0 indicates that it is
disabled.

R/W

Out Datalink index, holding the parameter number of


the parameter that will be read from during Datalink
communications. A value of 0 indicates that it is
disabled.

R/W

D2

169

Voltage Ratio

1/32767
[3079]

170

User CT Ratio

10/500
[100]

NA

Allows the user to achieve proper current ratio for FLC ratings when using external
CTs. This is a MV specific parameter and has no function at 690 volts and below.

R/W

171

Factory CT Ratio

1/15000
[50]

NA

Set at the factory to achieve proper current ratio for FLC ratings when using
external CTs. This is a MV specific parameter and has no function at 690 volts and
below.

R/W

262

NA

Allow OEMs to fine-tune their voltage dividers.This is a Medium Voltage specific


parameter and has no function at 690 volts and below.

R/W

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 140 - Parameter 172177

Number

172

173

Name

Aux1 Config

Aux 1 Invert

Units

Min./Max.
[Default]

0/11
[0]

[Normal]

Aux 1 closes when start command asserted and opens when motor stops [Default].

UTS (Up-To
-Speed)

Aux 1 closes when motor reaches up to speed and opens when motor is not at speed.

Fault

Aux1 closes when the SMC-50 enters a fault state and opens when the fault is cleared.

Alarm

Aux1 closes when the SMC-50 detects an alarm condition and opens when alarm is
cleared.

Ext Bypass

Aux1 closes when the SMC-50 enters the external bypass mode and opens when it
leaves that mode.

Ext Brake

Aux1 closes when Ext Braking command is active and opens when it is not active.

DeviceLogix

Aux1 is controlled by DeviceLogix program

Aux Control

When an auxiliary is configured for Aux Control, a bit within the parameter Aux Control
controls the state of that auxiliary.

Network 1

With an auxiliary configured as Network 1, it is controlled over the Local Area Network
(LAN) as Relay 1.

Network 2

With an auxiliary configured as Network 2 it is controlled over the LAN as Relay 2.

Network 3

With an auxiliary configured as Network 3 it is controlled over the LAN as Relay 3.

Network 4

With an auxiliary configured as Network 4 it is controlled over the LAN as Relay 4.

Enables the user to invert the logic of the Aux 1 output. When disabled, it is a normally
open relay output contact when de-energized. By enabling the invert function, the relay
contact becomes a normally closed contact when de-energized.

Disable

Aux 1 relay output not inverted [Default] (N.O.).

R/W

Aux 1 relay output inverted (N.C.) .

NA

A time delay in activating the Aux1 relay contact can be programmed.

R/W

NA

A time delay in de-activating the Aux1 relay contact can be programmed.

R/W

Allows the user to configure the functionality of the Aux1 relay output on the control
module based on the following selections.

[Normal]

Aux 2 closes when start command asserted and opens when motor stops [Default].

UTS

Aux 2 closes when motor reaches up to speed and opens when motor is not at speed.

Fault

Aux2 closes when the SMC-50 enters a fault state and opens when the fault is cleared.

Alarm

Aux2 closes when the SMC-50 detects an alarm condition and opens when alarm is
cleared.

Ext Bypass

Aux2 closes when the SMC-50 enters the external bypass mode and opens when it
leaves that mode.

Ext Brake

Aux2 closes when Ext Braking command is active and opens when it is not active.

Secs

175

Aux1 Off Delay

Secs

0.0/10.0
[0.0]

Aux 2 Invert

Allows the user to configure the functionality of the Aux1 relay output on the control
module based on the following selections.

Enable
Aux1 On Delay

177

Read/Write
Access

174

Aux2 Config

Description

0/1
[0]

0.0/10.0
[0.0]

176

Enum Text

0/11
[0]

0/1
[0]

DeviceLogix

Aux2 is controlled by DeviceLogix program

Aux Control

When an auxiliary is configured for Aux Control, a bit within the parameter Aux Control
controls the state of that auxiliary.

Network 1

With an auxiliary configured as Network 1, it is controlled over the Local Area Network
(LAN) as Relay 1.

Network 2

With an auxiliary configured as Network 2 it is controlled over the LAN as Relay 2.

Network 3

With an auxiliary configured as Network 3 it is controlled over the LAN as Relay 3.

Network 4

With an auxiliary configured as Network 4 it is controlled over the LAN as Relay 4.

Enables the user to invert the logic of the Aux2 output. When disabled, it is a normally
open relay output contact when de-energized. By enabling the invert function, the relay
contact becomes a normally closed contact when de-energized.

Disable

Aux2 relay output not inverted [Default] (N.O.).

Enable

Aux2 relay output inverted (N.C.) .

R/W

R/W

R/W

N.C. is electrically held.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

263

Appendix B

Parameter Information

Table 141 - Parameter 178185

Number

Name

Units

178

Aux2 On Delay

Secs

179

Aux2 Off Delay

Secs

180

Aux Control

Min./Max.
[Default]

Enum Text

Description

Read/Write
Access

0.0/10.0
[0.0]

NA

A time delay in activating the Aux2 relay contact can be programmed.

R/W

0.0/10.0
[0.0]

NA

A time delay in de-activating the Aux2 relay contact can be programmed.

R/W

When an Auxiliary Relay output is configured for "Aux Control" a bit within this
parameter will control the state of the auxiliary.

Aux 1

Bit 0 - Control Module Aux Relay 1

Aux 2

Bit 1 - Control Module Aux Relay 2

Aux 7-1

Bit 2 - Expansion Port 7 Aux Relay 1

Aux 7-2

Bit 3- Expansion Port 7 Aux Relay 2

Aux 7-3

Bit 4- Expansion Port 7 Aux Relay 3

[0]

Aux 7-4

Bit 5- Expansion Port 7 Aux Relay 4

Aux 8-1

Bit 6 - Expansion Port 8 Aux Relay 1

Aux 8-2

Bit 7- Expansion Port 8 Aux Relay 2

Aux 8-3

Bit 8- Expansion Port 8 Aux Relay 3

Aux 8-4

Bit 9- Expansion Port 8 Aux Relay 4

Aux 9-1

Bit 10 - Expansion Port 9 Aux Relay 1

Aux 9-2

Bit 11 - Expansion Port 9 Aux Relay 2

Aux 9-3

Bit 12 - Expansion Port 9 Aux Relay 3

Aux 9-4

R/W

Bit 13 - Expansion Port 9 Aux Relay 4


Bit 14 - Reserved
Bit 15 - Reserved

[English]
French
Spanish
181

Language

Provides the ability to configure the language that is displayed for any interface device.
The selected language will be the same for all devices connected to the SMC-50.

R/W

NA

The time between asserting a start command with valid 3-phase applied and the
SMC-50 starting the motor can be delayed by setting the "Start Delay". If a stop is
asserted during the delay period, the start is cancelled.

R/W

This parameter is used to force the starting profile to complete its entire time ramp
period. This ability can help to avoid conditions where an up-to-speed is sensed before
the motor is actually up to speed.

Disable

Complete starting mode when up-to-speed detected.

Enable

Complete starting mode when ramp time expires.

NA

Provides the ability to manually adjust the threshold for the controllers voltage (notch)
shutoff detection level. Since this parameter has the potential to modify the SCR
operational control scheme, it is important that any change made be in small (several
percent) increments. Do NOT disable (0) this parameter and Parameter 185 (I Shutoff
Level) at the same time or SCR firing (motor control) instability can occur. Contact RA
Technical Support for assistance. When running high-efficiency motors with Energy
Saver, this value may need to be adjusted downward.

R/W

NA

Provides the ability to adjust the level at which the SMC-50 expects to see current or the
level of current which the SMC-50 determines the SCR has turned off. A common reason
for increasing this value would be to compensate for the inability of the control to sense
a voltage notch due to significant LINE voltage noise or LINE distortion. Since this
parameter has the potential to modify the SCR operational control scheme, it is
important that any change made be in small (several percent) increments.Do NOT
disable (0) this parameter and Parameter 184 (V Shutoff Level) at the same time or SCR
firing (motor control) instability can occur. Contact Rockwell Automation Technical
Support for assistance.

R/W

Italian

[0]

German
Portuguese
Mandrin
182

183

184

185

264

Start Delay

Timed Start

V Shutoff Level

I Shutoff Level

Secs

0/30 [0]

0/1 [0]

0/100 [25]

0/37 [0]

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

Parameter Information

Appendix B

Table 142 - Parameter 186204

Number

Name

Units

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

R/W

186

UTS Level

0/100
[75]

NA

The SMC-50 has the ability to determine if the motor is up-to-speed (UTS). If the
SMC-50 encounters a problem detecting motor UTS, this parameter can be modified
by the user to compensate. If the SMC-50 is detecting the UTS condition to soon (e.g.,
abrupt speed change), this number should be increased (this typically occurs on high
efficiency motors). If the SMC-50 is detecting the UTS condition to late or not at all
(display does not indicate At Speed), this number should be lowered. Contact RA
Technical Support for assistance.

187

Stall Level

0/100
[75]

NA

Allows the user to set the motor winding voltage level (as a percentage of line
voltage) at which the SMC-50 will consider the motor stalled.

R/W

188

Stall Delay

Secs

0.0/30.0
[10.0]

NA

Allows the user to configure the time period after the start maneuver start time that
the motor has to reach UTS, or else a stall fault will occur.

R/W

189

Stall Position

0/100
[75]

NA

Allows the user to set the change in the notch position at which the SMC-50 will
consider the motor stalled.

R/W

190

Notch
Maximum
(Pump Control)

50.0/70.0
[60.0]

NA

Allows the user to change the maximum notch value during pump stop. This
parameter is not typically modified and it is recommended that RA Technical Support
be contacted for assistance before attempting to do so.

R/W

191

Notch Position

40.0/100.0
[87.5]

NA

Enables the user to make a manual adjustment to an internal value used for notch
control gain, which impacts the SMC-50 starting control algorithm. This parameter is
not typically modified and it is recommended that RA Technical Support be contacted
for assistance before attempting to do so.

R/W

192

Bypass Delay

Secs

1/15
[1]

NA

For possible future use with internal bypass contactor operation: Not applicable for
use with an external bypass contactor system. Allows a time delay upon closing an
internal bypass.

R/W

0.00/1.00
[0.00]

Allows the user to enable the controllers energy saving control scheme, which opens
the "notch" (reduces power applied) to lightly loaded motors thereby reducing the
motor terminal voltage and winding losses. This value should be set between the
no/light load value and the full/heavy load value of Parameter 17. Set Parameter
193=0 to disable Energy Saver mode.

R/W

Enables the controller's tuning algorithms to analyze the load and supply and adjust
parameters for easy set up and optimum performance.

FALSE

Do not run tuning algorithm (was already run or disabled by user).

193

194

Energy Saver

Forced Tuning

R/W

0/1 [1]

TRUE

Run tuning algorithm at next start command [Default].

NA

Enables the user to read/view the motor stator resistance value that was measured
during the tuning process.

195

Stator R

Ohms

0.00/50.00
[0.00]

196

Total R

Ohms

0.00/50.00
[0.00]

NA

Enables the user to read/view the motor total load resistance that was measured
during the tuning process.

197

Coupling Factor

0.00/10.00
[0.00]

NA

This is a coefficient inserted by the controller during the tuning process and viewable
by the user.

198

Inductance

mH

0.00/1000.00
[0.00]

NA

Enables the user to read/view the motor inductance that was measured during the
tuning process.

199

Speed PGain

1/10000
[1000]

200

Transient Mag

0.00/2.00
[0.90]

NA

Provides the ability to adjust the gain factor used in speed measurement algorithms.
These parameters are not typically modified and it is recommended that RA Technical
Support be contacted for assistance before attempting to do so.

R/W

201

Transient Zero

0.00/10.00
[5.00]

202

Transient Gain

0.00/4.00
[1.00]

203

Ping Degree

0.0/180.0
[50.0]

NA

204

Pings

0/20
[2]

NA

Timing parameter used in speed measurement algorithms. These parameters are not
typically modified and it is recommended that RA Technical Support be contacted for
assistance before attempting to do so.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W
R/W

265

Appendix B

Parameter Information

Table 143 - Parameter 205226

Number

Name

Units

205

206

10

207

20

208

30

209

40

210

Phase Shift

50

211

60

212

70

213

80

214

90

215
216

217

218

Min./Max.
[Default]

Enum Text

Description

Read/Write
Access

-360/360
[0]

NA

Timing parameters used in speed measurement algorithms. These


parameters are not typically modified and it is recommended that RA
Technical Support be contacted for assistance before attempting to do so.

R/W

-25/100 [20]

NA

Displays the internal temperature of the SMC control module.

0/5
[0]

None
Input/Output
Analog I/O
(future)
GndF/PTC/CT
DIP Switch
Seq Start
(future)

Displays the type of expansion board plugged into Expansion Port 7.

0/5
[0]

None
Input/Output
Analog I/O
(future)
GndF/PTC/CT
DIP Switch
Seq Start
(future)

Displays the type of expansion board plugged into Expansion Port 8.

0/5
[0]

None
Input/Output
Analog I/O
(future)
GndF/PTC/CT
DIP Switch
Seq Start
(future)

Displays the type of expansion board plugged into Expansion Port 9.

100
Board Temp

Exp 7 Config

Exp 8 Config

219

Exp 9 Config

220

Heating Time

Secs

0/1000
[0]

NA

Provides the ability to configure the time period the motor winding heating
algorithm is active after asserting the motor heating command.

R/W

221

Heating Level

0/100
[0]

NA

Provides the ability to configure the amount of current applied during the
motor winding heating process.

R/W

222

Fan Config

0/2
[0]

120V
240V
[Auto Detect]

Allows the user to configure the voltage applied to the internal SMC-50
cooling fans. If configured for Auto Detect [Default], the SMC-50 will use the
control voltage applied to the SMC-50 as the level and configure the fans to
work at that level.

R/W

223

Fan Connection

0/1
[0]

[120V]
240V

Displays the voltage configuration of the fans. If Auto Detect was selected in
the Fan Config parameter, this will display the result of the Auto Detect
process.

224

Line Frequency

Hz

0/100 [0]

NA

Displays the line frequency of the three phase voltage applied to the SMC-50
at terminals L1, L2, and L3.

225

Freq High F Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to configure the time period that the supplied line voltage
frequency must exceed Freq High F Lvl parameter value before causing a Freq
High fault. The Freq High bit must be set in the Starter Fault En parameter for
the fault to activate.

226

Freq High A Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to configure the time period that the supplied line voltage
frequency must exceed Freq High A Lvl parameter value before causing a
Freq High alarm. The Freq High bit must be set in the Starter Alarm parameter
for the fault to activate.

266

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 144 - Parameter 227230

Number

Name

Units

227

Freq Low F Dly

Secs

228

Freq Low A Dly

Secs

229

230

Parameter Mgmt

Motor Fault En

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

0.1/99.0
[0.1]

NA

Allows the user to configure the time period that the supplied line voltage
frequency must drop below Freq Low F Lvl parameter value before causing a
Freq Low fault. The Freq Low bit must be set in the Starter Fault En parameter
for the fault to activate.

0.1/99.0
[0.1]

NA

Allows the user to configure the time period that the supplied line voltage
frequency must drop below Freq Low A Lvl parameter value before causing a
Freq Low alarm. The Freq Low bit must be set in the Starter Alarm parameter
for the fault to activate.

Allows the user to force all the Control Module parameters to default values.
This has no impact on any option module(s) installed. Each Option module
has its own associated Parameter Mgmt parameter

[Ready]

Waiting for command to set factory defaults

Factory
Default

Command for SMC to set all Control Module Writable Parameters to factory
default values. This command does not impact Option Module parameters.

0/1 [0]

1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
0
0
0

[Overload]
Underload
MWatts Over
MWatts
Under
+MVAR Over
+MVAR
Under
-MVAR Over
-MVAR
Under
MVA Under
MVA Over
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
[Power Qual]
[Open Load]
THD I
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor

R/W

Allows the user to enable Motor related faults that can be detected by the
SMC-50.
0 = Fault Disabled
1 = Fault Enabled
[Default]

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

267

Appendix B

Parameter Information

Table 145 - Parameter 231240

Number

Name

Units

231

Motor Alarm En

232

+MVAR Ov F Lvl

Min./Max.
[Default]

Enum Text

Description

Read/Write
Access

Allows the user to enable Motor related alarms that can be detected by the
SMC-50.
0 = Fault Disabled
1 = Fault Enabled
[All Disabled as Default]

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Overload
Underload
MWatts Over
MWatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Under
MVA Over
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
Power Qual
Open Load
THD I
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor

MVAR

0.000/1000.000
[0.000]

NA

Allows the user to enter a value for the Consumed Reactive Power Over Fault
Level (+MVAR Ov F Lvl). If the current actual +MVAR value is greater than the
+MVAR OV F Lvl for a time period greater than that defined by +MVAR Ov F
Dly, a +MVAR Ov Fault will be signaled.

R/W

NA

Allows the user to enter a time value for the +MVAR Over Fault delay. If the
current actual value of Consumed Reactive Power (+MVAR) is greater than
the +MVAR OV F Lvl for a time period greater than that defined by +MVAR Ov
F Dly, a +MVAR Ov Fault will be signaled.

R/W

NA

Allows the user to enter a value for the Consumed Reactive Power Over
Alarm Level (+MVAR OV A Lvl). If the current actual +MVAR value is greater
than the +MVAR OV A Lvl for a time period greater than that defined by
+MVAR Ov A Dly, a +MVAR Ov Alarm will be signaled.

R/W

R/W

R/W

233

+MVAR Ov F Dly

Secs

0.1/99.0
[0.1]

234

+MVAR Ov A Lvl

MVAR

0.000/1000.000
[0.000]

NA

Allows the user to enter a time value for the +MVAR Over Alarm Delay
(+MVAR Ov A Dly). If the current actual value of Consumed Reactive Power
(+MVAR) is greater than the +MVAR Ov A Level for a time period greater than
that defined by +MVAR Ov A Dly, a +MVAR Ov Alarm will be signaled.

NA

Allows the user to enter a value for the Consumed Reactive Power Under
Fault Level (+MVAR Un F Lvl). If the current actual +MVAR value is less than
the +MVAR Un F Level for a time period greater than that defined by +MVAR
Un F Dly, a +MVAR Un Fault will be signaled.

R/W

NA

Allows the user to enter a time value for the +MVAR Under Fault delay. If the
Consumed Reactive Power (+MVAR) is less than the +MVAR Un F Level for a
time period greater than that defined by +MVAR Un F Dly, a +MVAR Un Fault
will be signaled.

R/W

NA

Allows the user to enter a value for the Consumed Reactive Power Under
Alarm Level (+MVAR Un A Lvl). If the current actual value of Consumed
Reactive Power (+MVAR) is less than the +MVAR Un A Level for a time period
greater than that defined by +MVAR Un A Dly a +MVAR Un Alarm will be
signaled.

R/W

R/W

R/W

235

+MVAR Ov A Dly

Secs

0.1/99.0
[0.1]

236

+MVAR Un F Lvl

MVAR

0.000/1000.000
[0.000]

Secs

0.1/99.0
[0.1]

MVAR

0.000/1000.000
[0.000]

NA

Allows the user to enter a time value for the +MVAR Under Alarm Delay
(+MVAR Un A Dly). If the current actual value of Consumed Reactive Power
(+MVAR) is less than the +MVAR Un A Level for a time period greater than
that defined by +MVAR Un A Dly, a +MVAR Un Alarm will be signaled.

NA

Allows the user to enter a value for the MVA Over Fault Level (MVA Ov F Lvl).
If the current actual value of Apparent Power (MVA) is greater than the MVA
Ov F Lvl for a time period greater than that defined by MVA Ov F Dly, a MVA
Ov Fault will be signaled.

237

238

+MVAR Un F Dly

+MVAR Un A Lvl

239

+MVAR Un A Dly

Secs

0.1/99.0
[0.1]

240

MVA Ov F Lvl

MVA

0.000/1000.000
[0.000]

To implement an Alarm or Fault, the appropriate bit in the Motor Fault En, Parameter 230, or Motor Alarm En, Parameter 231, must also be set.
268

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 146 - Parameter 241253

Number

Name

Units

241

MVA Ov F Dly

Secs

242

MVA Ov A Lvl

243

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Apparent Power Over Fault Delay
(MVA Ov F Dly). If the current actual value of Apparent Power (MVA) is greater
than the MVA Ov F Lvl for a time period greater than that defined by MVA Ov
F Dly, a MVA Ov Fault will be signaled.

R/W

MVA

0.000/1000.000
[0.000]

NA

Allows the user to enter a value for the MVA Over Alarm Level (MVA Ov A
Lvl). If the current actual value of the Apparent Power (MVA) is greater than
the MVA Ov A Lvl for a time period greater than that defined by MVA Ov A
Dly, a MVA Ov Alarm will be signaled.

R/W

MVA Ov A Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Apparent Power Over Alarm
Delay (MVA Ov A Dly). If the current actual value of the Apparent Power
(MVA) is greater than the MVA Ov A Lvl for a time period greater than that
defined by MVA Ov A Dly, a MVA Ov Alarm will be signaled.

R/W

244

MVA Un F Lvl

MVA

0.000/1000.000
[0.000]

NA

Allows the user to enter a value for the MVA Under Fault Level (MVA Un F
Lvl). If the current actual value of the Apparent Power (MVA) is less than the
MVA Un F Lvl for a time period greater than that defined by MVA Un F Dly, a
MVA Un Fault will be signaled.

R/W

245

MVA Un F Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Apparent Power Under Fault
Delay (MVA Un F Dly). If the current actual value of the Apparent Power (MVA)
is less than the MVA Un F Lvl for a time period greater than that defined by
MVA Un F Dly, a MVA Un Fault will be signaled.

R/W

246

MVA Un A Lvl

MVA

0.000/1000.000
[0.000]

NA

Allows the user to enter a value for the MVA Under Alarm Level (MVA Un A
Lvl). If the current actual value of the Apparent Power (MVA) is less than the
MVA Un A Lvl for a time period greater than that defined by MVA Un A Dly, a
MVA Un Alarm will be signaled.

R/W

247

MVA Un A Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Apparent Power Under Alarm
Delay (MVA Un A Dly). If the current actual value of the Apparent Power
(MVA) is less than the MVA Un A Lvl for a time period greater than that
defined by MVA Un A Dly, a MVA Un Alarm will be signaled.

R/W

248

Lead PF Ov F Lvl

0.00/1.00
[0.00]

NA

Allows the user to enter a value for the Leading Power Factor Over Fault Level
(Lead PF Ov F Lvl). If the current actual Power Factor value is leading more
than the Lead PF Ov F Lvl for a time period greater than that defined by Lead
PF Ov F Dly, a Lead PD Ov Fault will be signaled.

R/W

249

Lead PF Ov F Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Leading Power Factor Over Fault
Delay (Lead PF Ov F Dly). If the current actual Power Factor value is leading
more than the Lead PF Ov F Lvl for a period greater than that defined by Lead
PF Ov F Dly, a Lead PD Ov fault will be signaled.

R/W

250

Lead PF Ov A Lvl

0.00/1.00
[0.00]

NA

Allows the user to enter a value for the Leading Power Factor Over Alarm
Level (Lead PF Ov A Lvl). If the current actual Power Factor value is leading
more than the Lead PF Ov A Lvl for a period greater than that defined by Lead
PF Ov A Dly, a Lead PD Ov alarm will be signaled.

R/W

251

Lead PF Ov A Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Leading Power Factor Over Alarm
Delay (Lead PF Ov A Dly). If the current actual Power Factor value is leading
more than the Lead PF Ov A Lvl for a period greater than that defined by Lead
PF Ov A Dly, a Lead PD Ov alarm will be signaled.

R/W

252

Lead PF Un F Lvl

0.00/1.00
[0.00]

NA

Allows the user to enter a value for the Leading Power Factor Under Fault
Level (Lead PF Un F Lvl). If the current actual Power Factor value is leading
less than the Lead PF Un A Lvl for a time period greater than that defined by
Lead PF Un A Dly, a Lead PD Un Fault will be signaled.

R/W

253

Lead PF Un F Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Leading Power Factor Under
Fault Delay (Lead PF Un F Dly). If the current actual Power Factor value is
leading less than the Lead PF Un A Lvl for a time period greater than that
defined by Lead PF Un A Dly, a Lead PD Un Fault will be signaled.

R/W

To implement an Alarm or Fault, the appropriate bit in the Motor Fault En, Parameter 230, or Motor Alarm En, Parameter 231, must also be set.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

269

Appendix B

Parameter Information

Table 147 - Parameter 254263

Number

Name

Units

254

Lead PF Un A Lvl

255

Lead PF Un A Dly

256

Min./Max.
[Default]

Read/Write
Access

Enum Text

Description

0.00/1.00
[0.00]

NA

Allows the user to enter a value for the Leading Power Factor Under Alarm
Level (Lead PF Un A Lvl). If the current actual Power Factor value is leading
less than the Lead PF Un A Lvl for a time period greater than that defined by
Lead PF Un A Dly, a Lead PD Un Alarm will be signaled.

R/W

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Leading Power Factor Under
Alarm Delay (Lead PF Un A Dly). If the current actual Power Factor value is
leading less than the Lead PF Un A Lvl for a time period greater than that
defined by Lead PF Un A Dly, a Lead PD Un Alarm will be signaled.

R/W

Lag PF Ov F Lvl

-1.00/0.00
[0.00]

NA

Allows the user to enter a value for the Lagging Power Factor Over Fault
Level (Lag PF Ov F Lvl). If the current actual Power Factor value lags more
than the Lag PF Ov F Lvl for a time period greater than that defined by Lag PF
Ov F Dly, a Lag PF Ov Fault will be signaled.

R/W

257

Lag PF Ov F Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Lagging Power Factor Over
Fault Delay (Lag PF Ov F Dly). If the current actual Power Factor value lags
more than the Lag PF Ov F Lvl for a time period greater than that defined by
Lag PF Ov F Dly, a Lag PF Ov Fault will be signaled.

R/W

258

Lag PF Ov A Lvl

-1.00/0.00
[0.00]

NA

Allows the user to enter a value for the Lagging Power Factor Over Alarm
Level (Lag PF Ov A Lvl). If the current actual Power Factor value lags more
than the Lag PF Ov A Lvl for a time period greater than that defined by Lag
PF Ov A Dly, a Lag PF Ov Alarm will be signaled.

R/W

259

Lag PF Ov A Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Lagging Power Factor Over
Alarm Delay (Lag PF Ov A Dly). If the current actual Power Factor value lags
more than the Lag PF Ov A Lvl for a time period greater than that defined by
Lag PF Ov A Dly, a Lag PF Ov Alarm will be signaled.

R/W

260

Lag PF Un F Lvl

-1.00/0.00
[0.00]

NA

Allows the user to enter a value for the Lagging Power Factor Under Fault
Level (Lag PF Un F Lvl). If the current actual Power Factor value lags less
than the Lag PF Un F Lvl for a time period greater than that defined by Lag PF
Un F Dly, a Lag PF Un Fault will be signaled.

R/W

261

Lag PF Un F Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Lagging Power Factor Under
Fault Delay (Lag PF Un F Dly). If the current actual Power Factor value lags
less than the Lag PF Un F Lvl for a time period greater than that defined by
Lag PF Un F Dly, a Lag PF Un Fault will be signaled.

R/W

262

Lag PF Un A Lvl

-1.00/0.00
[0.00]

NA

Allows the user to enter a value for the Lagging Power Factor Under Alarm
Level (Lag PF Un A Lvl). If the current actual Power Factor value lags less
than the Lag PF Un A Lvl for a time period greater than that defined by Lag
PF Un A Dly, a Lag PF Un Alarm will be signaled.

R/W

263

Lag PF Un A Dly

Secs

0.1/99.0
[0.1]

NA

Allows the user to enter a time value for the Lagging Power Factor Under
Alarm Delay (Lag PF Un A Dly). If the current actual Power Factor value lags
less than the Lag PF Un A Lvl for a period greater than that defined by Lag PF
Un A Dly, a Lag PF Un alarm will be signalled.

R/W

To implement an Alarm or Fault, the appropriate bit in the Motor Fault En, Parameter 230, or Motor Alarm En, Parameter 231, must also be set.

270

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 148 - Parameter 264281

Number

Name

Units

264

Motor Restart En

Min./Max.
[Default]

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Enum Text

Overload
Underload
MWatts Over
MWatts Under
+MVAR Over
+MVAR Under
-MVAR Over
-MVAR Under
MVA Over
MVA Under
Curr Imbal
Jam
Stall
Starts/Hr
PM Hours
PM Starts
Power Qual
Open Load
THD I
Lead PF Un
Lead PF Ov
Lag PF Un
Lag PF Ov
Locked Rotor

Description
Enables the user to adjust the Motor Restart Enable conditions. Setting
(=1) a bit causes the motor to attempt a restart after the selected event
is detected. A limit to the number of starts attempted before a fault is
signalled can be set in the Restart Attempts parameter.
0 = Do not attempt a restart after fault is cleared
1 = Attempt a restart after this fault is cleared
NOTE: Restart attempts, Parameter 133, and Restart Delay, Parameter
134, must also be configured.

Read/Write
Access
R/W

[All Disabled as Default]

265

Voltage Pn Ave

Displays the average of the sum of the three phase voltages to neutral.

266

Voltage Phase A-N

Displays Phase A (L1) to neutral voltage.

267

Voltage Phase B-N

268

Voltage Phase C-N

Displays Phase C (L3) to neutral voltage.

269

Real Power A

Displays the Real Power of the Phase A branch which is equal to Phase
A Voltage x Phase A Current x PF.

270

Real Power B

271

Real Power C

272

Real Demand

MW

-1000.000/1000.000
[0.000]

NA

Displays Real Energy (MWH) averaged over a period of time defined by


Demand Period.

273

Max. Real Demand

MW

-1000.000/1000.000
[0.000]

NA

Displays the Maximum energy demand recorded since the last energy
meter reset.

274

Reactive Power A
MVAR

-1000.000/1000.000
[0.000]

275

Reactive Power B

276

Reactive Power C

277

Reactive Power

278

Reactive Energy C

279

Reactive Energy P

280

Reactive Energy

281

Reactive Demand

Volts

MW

0/450 [0]

-1000.000/1000.000
[0.000]

NA

NA

Displays Phase B (L2) to neutral voltage.

Displays the Real Power of the Phase B branch which is equal to Phase
B Voltage x Phase B Current x PF.

Displays the real power of the Phase C branch which is equal to Phase C
Voltage x Phase C Current x PF.

Displays the reactive power of the Phase A branch.


NA

Displays the reactive power of the Phase B branch.

Displays the reactive power of the Phase C branch.


MVAR

-1000.000/1000.000
[0.000]

MVRH

-1000.000/1000.000
[0.000]

NA

-1000.000/1000.000
[0.000]

NA

NA

Displays the total reactive power.

Displays the reactive energy being consumed by the load.

MVAR

Displays the reactive energy being produced by the load.

Displays the total reactive energy which is equal to Reactive Power X


time.
Displays the Reactive Energy consumed or generated by the system over
the Demand Time Period.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

271

Appendix B

Parameter Information

Table 149 - Parameter 282302


Min./Max.
[Default]

Number

Name

Units

282

Max. Reactive Dmd

MVAR

-1000.000/1000.000
[0.000]

283

Apparent Power A
MVA

-1000.000/1000.000
[0.000]

Enum Text

Description

NA

Displays the maximum reactive energy demand recorded since the energy
meters were reset

Read/Write
Access
R

Displays the Apparent Power (VA) measured in the phase A branch.

284

Apparent Power B

285

Apparent Power C

NA

Displays the VA measured in the phase B branch.

286

Apparent Power

MVA

-1000.000/1000.000
[0.000]

NA

Displays the total apparent power consumed (-) or produced (+) by the
load.

287

Apparent Energy

MVAH

-1000.000/1000.000
[0.000]

NA

Displays the Apparent Energy which is equal to Apparent Power x Time.

288

Apparent Demand

MVA

-1000.000/1000.000
[0.000]

NA

Displays the total amount of Apparent Energy which is equal to MVAH x


demand period produced or consumed by the load.

289

Max. Apparent Dmd

MVA

-1000.000/1000.000
[0.000]

NA

Displays the maximum apparent demand recorded since energy meters


were reset.

290

Demand Period

Mins

1/255 [1]

NA

Enables the user to enter the time period that energy samples are taken
to calculate demand.

R/W

291

Num of Periods

1/15 [1]

NA

Enables the user to enter the number of periods that energy


measurements are taken in calculating demand.

R/W

292

Power Factor A

-1.00/1.00
[0.00]

Displays the VA measured in the phase C branch.

Displays the power factor in the Phase A branch of the load circuit.

293

Power Factor B

NA

Displays the power factor in the Phase B branch of the load circuit.

294

Power Factor C

295

Current Imbal

0/100 [0.00]

NA

Displays the percent current imbalance measured in the load circuit (max
deviation of current from the average of three currents / average current
of three currents).

296

Voltage Imbal

0/100 [0.00]

NA

Displays the percent voltage imbalance measured in the load circuit (max
deviation of voltage from the average of three voltages / average current
of three voltages).

297

-MVAR Ov F Lvl

MVAR

-1000.000/0.000
[0.000]

NA

Enables the user to enter a value for the Generated Reactive Power Over
Fault Level (-MVAR Ov F Lvl). If the current actual value for Generated
Reactive Power is more than the -MVAR Ov F Lvl for a period greater than
that defined by -MVAR Ov F Dly, a -MVAR Ov fault will be signaled.

R/W

NA

Enables the user to enter a time value for the Generated Reactive Power
Over Fault Delay (-MVAR Ov F Dly). If the current actual value for the
Generated Reactive Power is more than the -MVAR Ov F Lvl for a time
period greater than that defined by -MVAR Ov F Dly, a -MVAR Ov fault
will be signaled.

R/W

NA

Enables the user to enter a value for the Generated Reactive Power Over
Alarm Level (-MVAR Ov A Lvl). If the current actual value for Generated
Reactive Power is more than the -MVAR Ov A Lvl for a period greater than
that defined by -MVAR Ov A Dly, a -MVAR Ov Alarm will be signaled.

R/W

R/W

Displays the power factor in the Phase C branch of the load circuit.

298

-MVAR Ov F Dly

Secs

0.1/99.0
[0.1]

299

-MVAR Ov A Lvl

MVAR

-1000.000/0.000
[0.000]

NA

Enables the user to enter a time value for the Generated Reactive Power
Over Alarm Delay (-MVAR Ov A Dly). If the current actual value for the
Generated Reactive Power is more than the -MVAR Ov A Lvl for a period
greater than that defined by -MVAR Ov A Dly, a -MVAR Ov alarm will be
signaled.

NA

Enables the user to enter a value for the Generated Reactive Power Under
Fault Level (-MVAR Un F Lvl). If the current actual value for Generated
Reactive Power is less than the -MVAR Un F Lvl for a period greater than
that defined by -MVAR Un F Dly, a -MVAR Un Fault will be signaled.

R/W

NA

Enables the user to enter a time value for the Generated Reactive Power
Under Fault Delay (-MVAR Un F Dly). If the current actual value for
Generated Reactive Power is less than the -MVAR Un F Lvl for a period
greater than that defined by -MVAR Un F Dly, a -MVAR Un Fault will be
signaled.

R/W

300

-MVAR Ov A Dly

Secs

0.1/99.0
[0.1]

301

-MVAR Un F Lvl

MVAR

-1000.000/0.000
[0.000]

Secs

0.1/99.0
[0.1]

302

-MVAR Un F Dly

To implement an Alarm or Fault, the appropriate bit in the Motor Fault En, Parameter 230, or Motor Alarm En, Parameter 231, must also be set.

272

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

Appendix B

Table 150 - Parameter 303311

Number

303

Name

-MVAR Un A Lvl

304

-MVAR Un A Dly

305

Starting Torque

306

Starting Torque 2

307

SS Ref Gain

Units

Min./Max.
[Default]

MVAR

-1000.000/0.000
[0.000]

Description

NA

Enables the user to enter a value for the Generated Reactive Power
Under Alarm Level (-MVAR Un A Lvl). If the current actual value for
Generated Reactive Power is less than the -MVAR Un A Lvl for a period
greater than that defined by -MVAR Un A Dly, a MVAR Un Alarm will be
signaled.

R/W

Secs

0.1/99.0
[0.1]

NA

Enables the user to enter a time value for the Generated Reactive
Power Under Alarm Delay (-MVAR Un A Dly). If the current actual value
for Generated Reactive Power is less than the -MVAR Un A Lvl for a
period greater than that defined by -MVAR Un A Dly, a -MVAR Un Alarm
will be signaled.

R/W

0/300
[100]

NA

308

Read/Write
Access

Enum Text

0.10/2.00
[1.00]

NA

SS Trans Gain

Enables the user to enter Starting Torque value required for a torque
start operation.
Enables the user to enter an alternate Starting Torque required for a
torque start operation.
Enables the user to enter Slow Speed Reference Gain value (SS Ref
Gain) used to adjust slow speed operation. This parameter is rarely
adjusted. Contact RA Technical Support for further information.
Enables the user to enter Slow Speed Transfer Gain value (SS Trans
Gain) used to adjust slow speed operation. This parameter is rarely
adjusted. Contact RA Technical Support for further information.

R/W

R/W

Displays the status of all the digital inputs for the SMC-50.
Input 1

309

Input Status

0/65535
[0]

Bit 0 - Displays status of Control Module Input #1.

Input 2

Bit 1 - Displays status of Control Module Input #2.

Input 7-1

Bit 2 - Displays status of Control Module Port 7, 150-SM4 Option


Module Input #1.

Input 7-2

Bit 3 - Displays status of Control Module Port 7, 150-SM4 Option


Module Input #2.

Input 7-3

Bit 4- Displays status of Control Module Port 7, 150-SM4 Option


Module Input #3.

Input 7-4

Bit 5- Displays status of Control Module Port 7, 150-SM4 Option


Module Input #4.

Input 8-1

Bit 6 - Displays status of Control Module Port 8, 150-SM4 Option


Module Input #1.

Input 8-2

Bit 7- Displays status of Control Module Port 8, 150-SM4 Option


Module Input #2.

Input 8-3

Bit 8- Displays status of Control Module Port 8, 150-SM4 Option


Module Input #3.

Input 8-4

Bit 9- Displays status of Control Module Port 8, 150-SM4 Option


Module Input #4.

Input 9-1

Bit 10 - Displays status of Control Module Port 9, 150-SM4 Option


Module Input #1.

Input 9-2

Bit 11 - Displays status of Control Module Port 9, 150-SM4 Option


Module Input #2.

Input 9-3

Bit 12 - Displays status of Control Module Port 9, 150-SM4 Option


Module Input #3.

Input 9-4

Bit 13 - Displays status of Control Module Port 9, 150-SM4 Option


Module Input #4.

Bit 14 & 15 - Reserved.

310

Locked Rotor A Lvl

%FLC

400/1000
[600]

311

Locked Rotor A Dly

Secs

0.1/100.0
[0.1]

NA

Enables the user to enter a value for the Locked Rotor Alarm Level
(Locked Rtr A Lvl). The locked rotor value represents the motor peak
phase current to the load that if exceeded for the period defined in
Locked Rtr A Delay will signal a fault. The Locked Rotor bit in the Motor
Alarm En parameter must be set to signal a alarm.

R/W

NA

The time period that the peak phase current exceeds the Locked Rtr F
Level to signal a fault. The Locked Rotor bit in the Motor Fault En
parameter must be set to enable a fault.

R/W

To implement an Alarm or Fault, the appropriate bit in the Motor Fault En, Parameter 230, or Motor Alarm En, Parameter 231, must also be set.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

273

Appendix B

Parameter Information

Table 151 - Parameters 312325

Number

Name

Units

312

Product
Command

Min./Max.
[Default]

Enum Text

0/65535
[0]

Description

Read/Write
Access

Displays an image of the DPI product command required for DPI communications.

Stop

1 Coast / Inhibit
0 No Action

Start

1 Start
0 No Action

Jog

1 Stop Maneuver / Inhibit


0 No Action

Clear Fault

1 Clear Faults
0 No Action

Slow Speed

1 Run at Slow Speed


0 No Action

Emer Run

1 Enable Emergency Run Mode


0 Disable Emergency Run Mode

Motor Heater

1 Enable Motor Winding Heater


0 Disable Motor Winding Heater

Reserved

Reserved

Reserved

Reserved

Aux Enable

1 Use the Network #1 - #4 bits


0 Ignore the Network #1 - #4 bits

Network_1

1 Closes any Output Configured for Network 1


0 Opens any Output Configured for Network 1

Network_2

1 Closes any Output Configured for Network 2


0 Opens any Output Configured for Network 2

Network_3

1 Closes any Output Configured for Network 3


0 Opens any Output Configured for Network 3

Network_4

1 Closes any Output Configured for Network 4


0 Opens any Output Configured for Network 4

313

Rebalance
Level

0/100 [0]

NA

The percentage of motor current imbalance above which the SMC-50 will rebalance the
motor current

R/W

314

Va Peak

Volt

0/15000 [0]

NA

The peak value of the Phase A line to neutral voltage during the motor start, run, and
stop cycle. The value resets to 0 when the motor starts.

315

Vb Peak

Volt

0/15000 [0]

NA

The peak value of the Phase B line to neutral voltage during the motor start, run, and
stop cycle.The value resets to 0 when the motor starts.

316

Vc Peak

Volt

0/15000 [0]

NA

The peak value of the Phase C line to neutral voltage during the motor start, run, and
stop cycle. The value resets to 0 when the motor starts.

317

Ia Peak

Amps

0/15000 [0]

NA

The peak value of the Phase A current during the motor start, run, and stop cycle. The
value resets to 0 when the motor starts.

318

Ib Peak

Amps

0/15000 [0]

NA

The peak value of the Phase B current during the motor start, run, and stop cycle. The
value resets to 0 when the motor starts.

319

Ic Peak

Amps

0/15000 [0]

NA

The peak value of the Phase C current during the motor start, run, and stop cycle. The
value resets to 0 when the motor starts.

320

SSVolts
Phas A-B

Volt

0/700 [0]

NA

Snapshot of the Phase A-B voltage when a fault occurs. The value is overwritten if a
subsequent fault occurs

321

SSVolts
Phas B-C

Volt

0/700 [0]

NA

Snapshot of the Phase B-C voltage when a fault occurs. The value is overwritten if a
subsequent fault occurs.

322

SSVolts
Phas C-A

Volt

0/700 [0]

NA

323

SSCurrent
Phas A

Amps

0/15000 [0]

NA

324

SSCurrent
Phas B

Amps

0/15000 [0]

NA

Snapshot of the Phase B current when a fault occurs. The value is overwritten if a
subsequent fault occurs.

325

SSCurrent
Phas C

Amps

0/15000 [0]

NA

Snapshot of the Phase C current when a fault occurs. The value is overwritten if a
subsequent fault occurs.

274

Snapshot of the Phase C-A voltage when a fault occurs. The value is overwritten if a
subsequent fault occurs.
Snapshot of the Phase A current when a fault occurs. The value is overwritten if a
subsequent fault occurs.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R
R

Parameter Information

Appendix B

Table 152 - Parameter 326333

Number

Name

Units

Min./Max.
[Default]

Enum
Text

326

SSPower
Factor

-1.00/1.00 [0]

NA

Snapshot of the Motor Power Factor when a fault occurs. The value is overwritten if
a subsequent fault occurs.

327

SSMtr Thrm
Usage

%MTU

0/200 [0]

NA

Snapshot of the Motor Thermal Usage when a fault occurs. The value is overwritten
if a subsequent fault occurs.

328

SSMotor
Speed

0/100 [0]

NA

Snapshot of the Motor Speed when a fault occurs. The value is overwritten if a
subsequent fault occurs.

329

SSTHD Vave

0.0/1000.0 [0]

NA

Snapshot of the average voltage Total Harmonic Distortion (THD) when a fault
occurs. The value is overwritten if a subsequent fault occurs,

330

SSTHD Iave

0.0/1000.0 [0]

NA

Snapshot of the average current Total Harmonic Distortion (THD) when a fault
occurs. The value is overwritten if a subsequent fault occurs.

Snapshot of the product status when a fault occurs. The value is overwritten if a
subsequent fault occurs.

bit 0 =
Enabled/
Ready

331

SSProduct
Status

0/65535 [0]

Description

1 Ready
0 Not Ready

bit 1 =
Running

1 Power Applied to Motor (Gating SCRs or Bypass closed)

bit 2 =
Phasing

1 ABC Phasing

bit 3 =
Phasing
Active

1 3-phase is valid

bit 4 =
Starting
(Accel)

1 Performing a Start Maneuver (slow speed not included)

bit 5 =
Stopping
(Decel)

1 Performing a Stop Maneuver (coast to stop not included)

bit 6 =
Alarm

1 Alarm Present

bit 7 =
Fault

Read/Write
Access

0 Power NOT Applied to Motor

0 CBA Phasing

0 No valid 3-phase detected

0 Not Performing a Start Maneuver

0 Not Performing a Stop Maneuver

0 No Alarm Present
1 Fault Condition Exists and hasnt been cleared
0 No Fault Condition

bit 8 = At
Speed

1 Full Voltage Applied (Bypass or full SCR conduction)

bit 9 =
Start/Isol
ate

1 Start/Isolate Contactor Enabled

bit 10 =
Bypass

1 Bypass Contactor Enabled

bit 11 =
Ready

1 indicates that the SMC is ready to accept a Start command. The device is not
faulted or in the process of stopping, starting or jogging.

bit 12 13 =
Reserved

Always 0

bit 14 =
Input #1

Control Module Input #1 Status. 1 = Input Closed

bit 15 =
Input #2

Control Module Input #2 Status. 1 = Input Closed

0 Not Full Voltage Applied

0 Start/Isolate Contactor Disabled

0 Bypass Contactor Disabled

332

SSBoard
Temp

degC

-25/100 [20]

NA

Snapshot of the internal temperature of the SMC control module when a fault
occurs. The value is overwritten if a subsequent fault occurs

333

SSLine
Frequency

HZ

0/100 [0]

NA

Snapshot of the line frequency of the three phase voltage when a fault occurs. The
value is overwritten if a subsequent fault occurs

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

275

Appendix B

Parameter Information

Table 153 - Parameter 334346

Number

Name

Units

Min./Max.
[Default]

334

Restart Auto

335

DLX Input 1

336

Read/Write
Access

Enum Text

Description

[all disabled]

Volt Unbal
Overvoltage
Undervoltage
Line Loss

Modifies the Auto Restarting of the selected faults so that the restart is
attempted when the fault condition is removed rather than after a fixed time
delay.

R/W

-2147483648
2147483647 [0]

NA

General purpose parameter used as an input to the DeviceLogix Engine.

R/W

DLX Input 2

-2147483648
2147483647 [0]

NA

General purpose parameter used as an input to the DeviceLogix Engine.

R/W

337

DLX DL Input 1

0 / 159999 [1]

NA

General purpose datalink used to select another parameter within the


SMC-50 as an input to the DeviceLogix Engine.

R/W

338

DLX DL Input 2

0 / 159999 [1]

NA

General purpose datalink used to select another parameter within the


SMC-50 as an input to the DeviceLogix Engine.

R/W

339

DLX DL Input 3

0 / 159999 [1]

NA

General purpose datalink used to select another parameter within the


SMC-50 as an input to the DeviceLogix Engine.

R/W

340

DLX DL Input 4

0 / 159999 [1]

NA

General purpose datalink used to select another parameter within the


SMC-50 as an input to the DeviceLogix Engine.

R/W

341

DLX DL Input 5

0 / 159999 [1]

NA

General purpose datalink used to select another parameter within the


SMC-50 as an input to the DeviceLogix Engine.

R/W

342

DLX DL Input 6

0 / 159999 [1]

NA

General purpose datalink used to select another parameter within the


SMC-50 as an input to the DeviceLogix Engine.

R/W

343

DLX Output 1

-2147483648
2147483647 [0]

NA

General purpose parameter that can be written by the DeviceLogix engine


and monitored from a HIM or network device.

344

DLX Output 2

-2147483648
2147483647 [0]

NA

General purpose parameter that can be written by the DeviceLogix engine


and monitored from a HIM or network device.

345

DLX Command

Ready
Enable
Disable

Allows the user to enable or disable the DeviceLogix engine. Once the
"Enable" or "Disable" command has been executed the parameter will
automatically revert back to "Ready".

R/W

346

DLX Status

Enable
Disable

Indicates the current state of the DeviceLogix engine.

150-SM6 PCM Information

Table 154 - Parameter X.1X.9

Number Name

Min./Max.
Units Enum
Text
[Default]

Description

Read/Write
Access

X.1

Module Status

0/1 [1]

NA

Displays information about the operational status of the 150-SMB Parameter


Configuration Option I/O Module.

X.2

Rotary Switch 1

0/15 [0]

NA

X.3

Rotary Switch 2

0/15 [0]

NA

NA

Displays the numeric position of Rotary Switch 2 = Current Limit.

X.4

Rotary Switch 3

0/15 [0]

NA

NA

Displays the numeric position of Rotary Switch 3 = Ramp Time.

X.5

Rotary Switch 4

0/15 [0]

NA

NA

Displays the numeric position of Rotary Switch 4 = Stop Time.

X.6

Rotary Switch 5

0/15 [0]

NA

NA

Displays the numeric position of Rotary Switch 5 = Motor FLC.

R
R

Ready

Bit 0 - Ready; Bit Set = 1 indicates the module is ready for operation.

NA

Displays the numeric position of Rotary Switch 1 = Initial Torque

X.7

Device Config

0/255 [0]

NA

NA

Displays the Device Config DIP switch bit status


(1=Sw ON & 2=Sw OFF).

X.8

Protect Config

0/255 [0]

NA

NA

Displays the Protect Config DIP switch bit status


(1=Sw ON & 2=Sw OFF).

X.9

IO Config

0/255 [0]

NA

NA

Displays the IO Config DIP switch bit status (1=Sw ON & 2=Sw OFF).

X indicates the Control Module port number in which the 150-SM6 Option Module is installed. Allowable ports = 7, 8, or 9.

276

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Parameter Information

150-SM4 Digital I/O Module


Information
Number Name

X.1

X.2

Module Status

Input 1

Table 155 - Parameter X.1X.18

Min./Max.
Units Enum Text
[Default]

0/256
[0]

0/13
[0]

NA

NA

Appendix B

Description

Displays information about the operational status of the 150-SM4 Digital


I/O Option Module.

Ready

Bit 0 = Ready;
Bit Set = indicates the module is ready for operation.

Input 1

Bit 1 = Input 1;
Bit Set (1) indicates the input is ON.

Input 2

Bit 2 = Input 2;
Bit Set (1) indicates the input is ON.

Input 3

Bit 3 = Input 3;
Bit Set (1) indicates the input is ON.

Input 4

Bit 4 = Input 4;
Bit Set (1) indicates the input is ON.

Aux 1

Bit 5 = Aux 1; Bit Set (1) indicates the auxiliary relay output is ON.

Aux 2

Bit 6 = Aux 2; Bit Set (1) indicates the auxiliary relay output is ON.

Aux 3

Bit 7 = Aux 3; Bit Set (1) indicates the auxiliary relay output is ON.

Bit 8-15 Spare

Bit 8-15 Spare

Allows the user to select the operation of Input Terminal A1, Option Input 1
on the 150-SM4 Digital I/O Option Module.

[Disable]

Disable the input; ignores any assertion to Input A1Terminal (High).

Start

Initiate a start as set up by the start parameters at Input Terminal A1.

Coast

Initiates a coast stop; no current to motor at Input Terminal A1 (Low).

Stop Option

Initiates a stop maneuver as set up by the stopping parameters at Input


Terminal A1 (Low).

Start/Coast

If Input Terminal A1 = 0 stops motor, 1 initiates a start as set up by the start


parameters.

Start/Stop

If Input Terminal A1 = 0 initiates a stop maneuver as set up by stopping


parameters, 1 initiates a start as set up b the start parameters.

Slow Speed

Runs motor in slow speed mode as set up by slow speed parameters (High).

Dual Ramp

If Input Terminal A1 = 0, use starting mode 1;


1, use starting mode 2.

OL Select

If Input Terminal A1 = 0, use Motor Overload Class 1;


1, use Motor Overload Class 2.

Fault

A fault condition is forced if Input Terminal A1 = 1.

Fault NC

A fault condition is forced if Input Terminal A1 = 0.

Clear Fault

Clear a fault from Input Terminal A1 (High).

Emerg Run

Allows motor to run in emergency run mode if asserted from Input Terminal
A1; does not start motor (High).

Motor Heater

Runs motor heating algorithm if asserted at Input Terminal A1 (High).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Read/Write
Access

R/W

277

Appendix B

Parameter Information

Number Name

X.3

X.4

278

Input 2

Input 3

Min./Max.
Units Enum Text
[Default]

0/13
[0]

0/13
[0]

NA

NA

Description

Allows the user to select the operation of Input Terminal A2, Option Input 2
on the 150-SM4 Digital I/O Option Module.

[Disable]

Disable the input; ignores any assertion to Input A2 Terminal.

Start

Initiate a start as set up by the start parameters at Input Terminal A2 (High).

Coast

Initiates a coast stop; no current to motor at Input Terminal A2 (Low).

Stop Option

Initiates a stop maneuver as set up by the stopping parameters at Input


Terminal A2 (High).

Start/Coast

If Input Terminal A2 = 0 stops motor, 1 initiates a start as set up by the start


parameters.

Start/Stop

If Input Terminal A2 = 0 initiates a stop maneuver as set up by stopping


parameters, 1 initiates a start as set up b the start parameters.

Slow Speed

Runs motor in slow speed mode as set up by slow speed parameters (High).

Dual Ramp

If Input Terminal A2 = 0, use starting mode 1;


1, use starting mode 2.

OL Select

If Input Terminal A2 = 0, use Motor Overload Class 1;


1, use Motor Overload Class 2.

Fault

A fault condition is forced if Input Terminal A2 = 1.

Fault NC

A fault condition is forced if Input Terminal A2 = 0.

Clear Fault

Clear a fault from Input Terminal A2 (High).

Emerg Run

Allows motor to run in emergency run mode if asserted from Input Terminal
A2; does not start motor (High).

Motor Heater

Runs motor heating algorithm if asserted at Input Terminal A2 (High).

Allows the user to select the operation of Input Terminal A3, Option Input 3
on the 150-SM4 Digital I/O Option Module.

[Disable]

Disable the input; ignores any assertion to Input A3 Terminal.

Start

Initiate a start as set up by the start parameters at Input Terminal A3 (High).

Coast

Initiates a coast stop; no current to motor at Input Terminal A3 (Low).

Stop Option

Initiates a stop maneuver as set up by the stopping parameters at Input


Terminal A3 (Low).

Start/Coast

If Input Terminal A3 = 0 stops motor, 1 initiates a start as set up by the start


parameters.

Start/Stop

If Input Terminal A3 = 0 initiates a stop maneuver as set up by stopping


parameters, 1 initiates a start as set up b the start parameters.

Slow Speed

Runs motor in slow speed mode as set up by slow speed parameters (High).

Dual Ramp

If Input Terminal A3 = 0, use starting mode 1;


1, use starting mode 2.

OL Select

If Input Terminal A3 = 0, use Motor Overload Class 1;


1, use Motor Overload Class 2.

Fault

A fault condition is forced if Input Terminal A3 = 1.

Fault NC

A fault condition is forced if Input Terminal A3 = 0.

Clear Fault

Clear a fault from Input Terminal A3 (High).

Emerg Run

Allows motor to run in emergency run mode if asserted from Input Terminal
A3; does not start motor (High).

Motor Heater

Runs motor heating algorithm if asserted at Input Terminal A3 (High).

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Read/Write
Access

R/W

R/W

Parameter Information

Number Name

Min./Max.
Units Enum Text
[Default]

X.5

X.6

X.7

Input 4

Aux1 Config

Aux1 Invert

0/13
[0]

0/11
[0]

0/1
[0]

X.8

Aux1 On Delay

0.0/10.0
[0.0]

X.9

Aux1 Off Delay

0.0/10.0
[0.0]

NA

NA

Description

Read/Write
Access

Allows the user to select the operation of Input Terminal A4, Option Input 4
on the 150-SM4 Digital I/O Option Module.

[Disable]

Disable the input; ignores any assertion to Input A4 Terminal.

Start

Initiate a start as set up by the start parameters at Input Terminal A4 (High).

Coast

Initiates a coast stop; no current to motor at Input Terminal A4 (Low).

Stop Option

Initiates a stop maneuver as set up by the stopping parameters at Input


Terminal A4.

Start/Coast

If Input Terminal A4 = 0 stops motor, 1 initiates a start as set up by the start


parameters.

Start/Stop

If Input Terminal A4 = 0 initiates a stop maneuver as set up by stopping


parameters, 1 initiates a start as set up b the start parameters.

Slow Speed

Runs motor in slow speed mode as set up by slow speed parameters (High).

Dual Ramp

If Input Terminal A4 = 0, use starting mode 1;


1, use starting mode 2.

OL Select

If Input Terminal A4 = 0, use Motor Overload Class 1;


1, use Motor Overload Class 2.

Fault

A fault condition is forced if Input Terminal A4 = 1.

Fault NC

A fault condition is forced if Input Terminal A4 = 0.

Clear Fault

Clear a fault from Input Terminal A4 (High).

Emerg Run

Allows motor to run in emergency run mode if asserted from Input Terminal
A4; does not start motor (High).

Motor Heater

Runs motor heating algorithm if asserted at Input Terminal A4 (Low).

Allows the user to configure the functionality of the Aux1 Relay Output on
the 150-SM4 Digital I/O Option Module.

[Normal]

Aux1 closes when start asserted, opens when motor stops.

Up-to-Speed

Aux1 closes when motor reaches up-to-speed and opens when the motor is
not at speed.

Fault

Aux1 closes when the SMC-50 enters a fault state and opens when the fault
is cleared.

Alarm

Aux1 closes when the SMC-50 detects an alarm condition and opens when
the alarm is cleared.

Ext Bypass

Aux1 closes when the SMC-50 enters the external bypass mode and opens
when it leaves that mode (SCR Control).

Ext Brake

Aux1 closes when the external braking command is active and opens when
it is not active.

Device Logix

Aux1 is controlled by the Device Logix program.

Aux Control

When an auxiliary output is configured for Aux Control, a bit within the
parameter Aux Control will control the state of the auxiliary.

Network 1

With an auxiliary configured as Network 1, it is controlled over the LAN as


Relay 1.

Network 2

With an auxiliary configured as Network 2, it is controlled over the LAN as


Relay 2.

Network 3

With an auxiliary configured as Network 3, it is controlled over the LAN as


Relay 3.

Network 4

With an auxiliary configured as Network 4, it is controlled over the LAN as


Relay 4.

Enables the user to invert the logic of the Aux1 output. When disabled, it is
a normally open relay output contact when de-energized. By enabling the
invert function, the relay contact becomes a normally closed contact when
de-energized.

[Disable]

Aux1 Relay Output is not inverted (N.O.).

NA

Appendix B

R/W

R/W

R/W

Enable

Aux1 Relay Output is inverted (N.C.) .

sec

NA

A user-selected time delay in activating the Aux1 Relay Contact can be


programmed.

R/W

sec

NA

A user-selected time delay in de-activating the Aux1 Relay Contact can be


programmed.

R/W

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

279

Appendix B

Parameter Information

Number Name

X.10

X.11

Aux2 Config

Aux2 Invert

Min./Max.
Units Enum Text
[Default]

0/11
[0]

0/1
[0]

NA

Description

Allows the user to configure the functionality of the Aux2 Relay Output on
the 150-SM4 Digital I/O Option Module.

[Normal]

Aux2 closes when start asserted, opens when motor stops.

Up-to-Speed

Aux2 closes when motor reaches up-to-speed and opens when the motor is
not at speed.

Fault

Aux2 closes when the SMC-50 enters a fault state and opens when the fault
is cleared.

Alarm

Aux2 closes when the SMC-50 detects an alarm condition and opens when
the alarm is cleared.

Ext Bypass

Aux2 closes when the SMC-50 enters the external bypass mode and opens
when it leaves that mode (SCR Control).

Ext Brake

Aux2 closes when the external braking command is active and opens when
it is not active.

Device Logix

Aux2 is controlled by the Device Logix program

Aux Control

When an auxiliary output is configured for Aux Control, a bit within the
parameter Aux Control will control the state of the auxiliary.

Network 1

With an auxiliary configured as Network 1, it is controlled over the LAN as


Relay 1.

Network 2

With an auxiliary configured as Network 2, it is controlled over the LAN as


Relay 2.

Network 3

With an auxiliary configured as Network 3, it is controlled over the LAN as


Relay 3.

Network 4

With an auxiliary configured as Network 4, it is controlled over the LAN as


Relay 4.

Enables the user to invert the logic of the Aux2 output. When disabled, it is
a normally open relay output contact when de-energized. By enabling the
invert function, the relay contact becomes a normally closed contact when
de-energized.

[Disable]

Aux2 Relay Output is not inverted (N.O.).

Enable

Aux2 Relay Output is inverted (N.C.) .

NA

Read/Write
Access

R/W

R/W

X.12

Aux2 On Delay

0.0/10.0
[0.0]

sec

NA

A user-selected time delay in activating the Aux2 Relay Contact can be


programmed.

R/W

X.13

Aux2 Off Delay

0.0/10.0
[0.0]

sec

NA

A user-selected time delay in de-activating the Aux2 Relay Contact can be


programmed.

R/W

Allows the user to configure the functionality of the Aux3 Relay Output on
the 150-SM4 Digital I/O Option Module.

[Normal]

Aux3 closes when start asserted, opens when motor stops.

Up-to-Speed

Aux3 closes when motor reaches Up-to-Speed and opens when the motor is
not at speed.

Fault

Aux3 closes when the SMC-50 enters a fault state and opens when the fault
is cleared.

Alarm

Aux3 closes when the SMC-50 detects an alarm condition and opens when
the alarm is cleared.

Ext Bypass

Aux3 closes when the SMC-50 enters the external bypass mode and opens
when it leaves that mode (SCR Control).

Ext Brake

Aux3 closes when the external braking command is active and opens when
it is not active.

Device Logix

Aux3 is controlled by the Device Logix program

Aux Control

When an auxiliary output is configured for Aux Control, a bit within the
parameter Aux Control will control the state of the auxiliary.

Network 1

With an auxiliary configured as Network 1, it is controlled over the LAN as


Relay 1.

Network 2

With an auxiliary configured as Network 2, it is controlled over the LAN as


Relay 2.

Network 3

With an auxiliary configured as Network 3, it is controlled over the LAN as


Relay 3.

Network 4

With an auxiliary configured as Network 4, it is controlled over the LAN as


Relay 4.

X.14

280

Aux3 Config

0/11
[0]

NA

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

Parameter Information

Number Name

X.15

Aux3 Invert

Min./Max.
Units Enum Text
[Default]

0/1
[0]

Description

Enables the user to invert the logic of the Aux3 output. When disabled, it is
a normally open relay output contact when de-energized. By enabling the
invert function, the relay contact becomes a normally closed contact when
de-energized.

[Disable]

Aux3 Relay Output is not inverted (N.O.).

Enable

Aux3 Relay Output is inverted (N.C.) .

NA

Appendix B

Read/Write
Access

R/W

X.16

Aux3 On Delay

0.0/10.0
[0.0]

sec

NA

A user-selected time delay in activating the Aux3 Relay Contact can be


programmed.

R/W

X.17

Aux3 Off Delay

0.0/10.0
[0.0]

sec

NA

A user-selected time delay in de-activating the Aux3 Relay Contact can be


programmed.

R/W

0/1
[0]

Allows the user to set all 150-SM4 Digital I/O Option Module parameters to
default values.

X.18

Parameter
Management

[Ready]

Waiting for command to set defaults.

Factory Default

Set all writable parameters to factory default values.

NA

R/W

X indicates the Control Module port number in which the 150-SM4 Option Module is installed. Allowable ports = 7, 8, or 9.
N.C. is electrically held closed.

150-SM2 Ground Fault


Module Information

Table 156 - Parameter X.1X.19

Number Name

Min./Max.
Units Enum Text
[Default]

Description

X.1

0/7
[7]

Displays information about the operational status of the 150-SM2 PTC,


Ground Fault, and External Current Transformer (CT) Option Module.

Ready

Bit 0 = Ready; Bit Set =1 indicates the module is ready for operation.

PTC

Bit 1 = PTC; 1 = PTC Indicating Fault 0; = No fault

CT Loss

Bit 2 = CT Loss; 1 = CT disconnected; 0 = CT Connected

Module Status

NA

Read/Write
Access

X.2

Fault Enable

0/3
[0]

NA

PTC

0 = PTC Fault Disabled; 1 = PTC Fault Enabled

Ground Fault

0 = Ground Fault Disabled; 1 = Ground Fault Enabled

R/W

x.3

Alarm Enable

0/3
[0]

NA

PTC

0 = PTC Alarm Disabled; 1 = PTC Alarm Enabled

Ground Fault

0 = Ground Fault Alarm Disabled; 1 = Ground Fault Alarm Enabled

R/W

X.4

Restart Enable

0/3
[0]

NA

PTC

0 = does not restart after PTC Fault is cleared; 1 = restart after PTC Fault is
cleared

Ground Fault

0 = does not restart after the Ground Fault is cleared; 1 = restart after the
Ground Fault is cleared

R/W

X.5

Turns Ratio

100/2000
[1000]

:1

NA

Enables user to configure the turns ratio for the CT being used.

R/W

X.6

Gnd Flt Level

0.00/5.00
[2.50]

Amps

NA

Enables the user to configure the level (value) of ground current that
determines a ground fault condition.

R/W

X.7

Gnd Flt Delay

0.1/250.0
[0.5]

Secs

NA

Sets the time limit that the ground fault level must be exceeded before
signalling a fault.

R/W

X.8

Gnd Flt A Level

0.00/5.00
[2.50]

Amps

NA

Sets the level of ground current that determines a ground fault alarm
condition.

R/W

X.9

Gnd Flt A Delay

0.1/250.0
[0.5]

Secs

NA

Sets the time limit that the ground fault level must be exceeded before
signalling an alarm.

R/W

X.10

Gnd Flt Inh Time

0.0/250.0
[10.0]

Secs

NA

User configurable time delay to inhibit ground fault after a start.

R/W

X.11

Ground Current

0.00/5.00
[0.00]

Amps

NA

Measured ground current.

R/W

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

281

Appendix B

Parameter Information

Number Name

Min./Max.
Units Enum Text
[Default]

Description

Read/Write
Access

X.12

0/1
[0]

Disable

Disables the CT function.

R/W

Enable

Enables the CT function.

CT Enable

X.13

CT Scaling A

X.14

CT Scaling B

X.15

CT Scaling C

X.16

Phase Shift A

X.17

Phase Shift B

X.18

Phase Shift C

X.19

Parameter Mgmt

NA

0.00/5.00
[0.01]

NA

NA

Displayed result of the SMC-50 tuning feature determination of the scaling


between external CT and the internal current measuring circuitry.

-12.5/12.5
[0.00]

Deg

NA

Displayed result of the SMC-50 tuning feature determination of the phase


shift between external CT and the internal current measuring circuitry.

0/1
[0]

NA

Ready

Waiting for command to set defaults.

R/W

Factory Default

Set all writable parameters to factory default values.

X indicates the Control Module port number in which the 150-SM2 PTC, Ground Fault, and External CT Option Module is installed. Allowable ports = 7 or 8.

150-SM3 Analog I/O


Module Information
Number Name

X.1

Module Status

Table 157 - Parameter X.1X.56

Min./Max.
[Default]

Units Enum Text

0/4096 [0]

NA

Description

Displays information about the operational status of the 150-SM3


Analog I/O Option Module

Ready

Bit 0 = Ready
Bit Set = indicates the module is ready for operation

In1 Over Flt

Bit 1 = Input 1 Over Fault


Bit Set = Input 1 Overrange fault

In1 Over Alm

Bit 2 = Input 1 Over Alarm


Bit Set = Input 1 Overrange alarm

In1 Undr Flt

Bit 3 = Input 1 Under Fault


Bit Set = Input 1 Underrange fault

In1 Undr Alm

Bit 4 = Input 1 Under Alarm


Bit Set = Input 1 Underrange Alarm

In2 Over Flt

Bit 5 = Input 2 Over Fault


Bit Set = Input 2 Overrange fault

In2 Over Alm

Bit 6 = Input 2 Over Alarm


Bit Set = Input 2 Overrange alarm

In2 Undr Flt

Bit 7 = Input 2 Under Fault


Bit Set = Input 2 Underrange fault

In2 Undr Alm

Bit 8 = Input 2 Under Alarm


Bit Set = Input 2 Underrange Alarm

Out 1 Shorted

Bit 9 = Output 1 Shorted


Bit Set = indicates Output 1 is shorted

Out 1 Open

Bit 10 = Output 1 Open


Bit Set = indicates Output 1 is an open circuit

Out 2 Shorted

Bit 11 = Output 2 Shorted


Bit Set = indicates Output 2 is shorted

Out 2 Open

Bit 12 = Output 2 Open


Bit Set = indicates Output 2 is an open circuit

Bits 13-15

Reserved

60 Hz

Selects a 60 Hz filter on Input 1 and Input 2

250 Hz

Selects a 250 Hz filter on Input 1 and Input 2

Read/Write
Access

X.2

Sample Rate

0/1[0]

NA

X.3

Input 1 Scaled

-3000.0/ 3000.0
[0.0]

NA

NA

Input 1 scaled to user units

X.4

Input 1 Analog

-21.000/ 21.000
[0.000]

V or
mA

NA

Input 1 in electrical units (volts or milliamps)

282

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

Parameter Information

Appendix B

Number Name

Min./Max.
[Default]

Units Enum Text

Description

Read/Write
Access

X.5

Input 1 Percent

-105.00/105.00
[0.00]

NA

Input 1 as a percentage of configured range

X.6

Input 1 Raw

-32768/32768 [0]

NA

X.7

Input 1 Range

0/5 [1]

NA

NA
NA

Input 1 unscaled

+/- 10V

Input 1 set to voltage mode with range of -10V to +10V

10V

Input 1 set to voltage mode with range of 0V to 10V

5V

Input 1 set to voltage mode with range of 0V to 5V

1-5V

Input 1 set to voltage mode with range of 1V to 5V

0-20mA

Input 1 set to current mode with range of 0mA to 20mA

4-20mA

Input 1 set to current mode with range of 4mA to 20mA

R/W

X.8

Input 1 Offset

-10000/10000 [0]

NA

NA

Offset value of Input 1 subtracted from the Input 1 Raw value (positive
offset lowers the resulting value)

R/W

X.9

Input 1 Data Hi

-3000.0/3000.0
[1000.0]

NA

NA

User defined maximum value of Input 1 custom value range

R/W

X.10

Input 1 Data Lo

-3000.0/3000.0
[0.0]

NA

NA

User defined minimum value of Input 1 custom value range

R/W

X.11

Input 1 High

-21.000/21.000
[10.000]

V or
mA

NA

Correlates Input 1 Data Hi to the Input 1 Raw value

R/W

X.12

Input 1 Low

-21.000/21.000
[0.000]

V or
mA

NA

Correlates Input 1 Data Low to the Input 1 Raw value

R/W

X.13

Input 2 Scaled

-3000.0/3000.0
[0.0]

NA

NA

Input 2 scaled to user units

X.14

Input 2 Analog

-21.000/21.000
[0.000]

V or
mA

NA

Input 2 in electrical units (volts or milliamps)

X.15

Input 2 Percent

-105.00/105.00
[0.00]

NA

NA

Input 2 as a percentage of configured range

X.16

Input 2 Raw

-32768/32768 [0]

NA

X.17

Input 2 Range

0/5 [1]

NA

NA

Input 2 unscaled

+/- 10V

Input 2 set to voltage mode with range of -10V to +10V

10V

Input 2 set to voltage mode with range of 0V to 10V

5V

Input 2 set to voltage mode with range of 0V to 5V

1-5V

Input 2 set to voltage mode with range of 1V to 5V

0-20mA

Input 2 set to current mode with range of 0mA to 20mA

4-20mA

Input 2 set to current mode with range of 4mA to 20mA

R/W

X.18

Input 2 Offset

-10000/10000 [0]

NA

NA

Offset value of Input 2 subtracted from the Input 2 Raw value. (positive
offset lowers the resulting value)

R/W

X.19

Input 2 Data Hi

-3000.0/3000.0
[1000.0]

NA

NA

User defined maximum value of Input 2 custom value range

R/W

X.20

Input 2 Data Lo

-3000.0/3000.0
[0.0]

NA

NA

User defined minimum value of Input 2 custom value range

R/W

X.21

Input 2 High

-21.000/21.000
[10.000]

V or
mA

NA

Correlates Input 2 Data Hi to the Input 2 Raw value

R/W

X.22

Input 2 Low

-21.000/21.000
[0.000]

V or
mA

NA

Correlates Input 2 Data Low to the Input 2 Raw value

R/W

+/- 10V

Output 1 set to voltage mode with range of -10V to +10V

10V

Output 1 set to voltage mode with range of 0V to 10V

X.23

X.24

Output 1 Range

0/4 [1]

NA

5V

Output 1 set to voltage mode with range of 0V to 5V

0-20mA

Output 1 set to current mode with range of 0mA to 20mA

4-20mA

Output 1 set to current mode with range of 4mA to 20mA

R/W

Output 1 Select

0/15999 [1]

NA

NA

X.25

Output 1 High

-20.000/20.000
[10.000]

V or
mA

Selects the parameter used to drive Output 1

R/W

NA

Output level when the selected parameter (Output 1 Select) reaches


"Output 1 Data Hi"

R/W

X.26

Output 1 Low

X.27

Output 1 Data Hi

-20.000/20.000
[0.000]
-300000000/30000
0000 [480]

V or
mA
V or
mA

Output level when the selected parameter (Output 1 Select) reaches


"Output 1 Data Lo"
Level of the selected parameter (Output 1 Select) corresponding to an
output of "Output 1 High"

R/W

X.28

Output 1 Data Lo

-300000000/30000
0000 [0]

V or
mA

NA

Level of the selected parameter (Output 1 Select) corresponding to an


output of "Output 1 High"

R/W

X.29

Output1
Setpoint

0/65535 [0]

NA

NA

Raw value sent to Output 1 when "Output 1 Select" is set to "Disabled"

R/W

NA
NA

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

283

Appendix B

Parameter Information

Number Name

Min./Max.
[Default]

Units Enum Text


+/- 10V

X.30

X.31

Output 2 Range

0/4 [1]

NA

Output 2 Select

0/15999 [1]

NA

X.32

Output 2 High

-20.000/20.000
[10.000]

X.33

Output 2 Low

X.34

Description

Read/Write
Access

Output 2 set to voltage mode with range of -10V to +10V

10V

Output 2 set to voltage mode with range of 0V to 10V

5V

Output 2 set to voltage mode with range of 0V to 5V

0-20mA

Output 2 set to current mode with range of 0mA to 20mA

4-20mA

Output 2 set to current mode with range of 4mA to 20mA

R/W

NA

Selects the parameter used to drive Output 2

R/W

V or
mA

NA

Output level when the selected parameter (Output 2 Select) reaches


"Output 2 Data Hi"

R/W

-20.000/20.000
[0.000]

V or
mA

NA

Output level when the selected parameter (Output 2 Select) reaches


"Output 2 Data Lo"

R/W

Output 2 Data Hi

-300000000/
300000000 [480]

V or
mA

NA

Level of the selected parameter (Output 2 Select) corresponding to an


output of "Output 2 High"

R/W

X.35

Output 2 Data Lo

-300000000/
300000000 [0]

V or
mA

NA

Level of the selected parameter (Output 2 Select) corresponding to an


output of "Output 2 High"

R/W

X.36

Output2
Setpoint

0/65535 [0]

NA

NA

Raw value sent to Output 2 when "Output 2 Select" is set to "Disabled"

R/W

Allows the user to enable the Input/Output faults


0 = Fault Disabled
1 = Fault Enabled

R/W

Allows the user to enable the Input/Output alarms


0 = Alarm Disabled
1 = Alarm Enabled

R/W

0 = Do not attempt a restart after fault is cleared


1 = Attempt a restart after fault is cleared
Note: Restart Attempts, Parameter 133 and Restart Delay, Parameter
134 must also be configured

R/W

In1 Over
In1 Under
In2 Over
X.37

Fault Enable

0/255 [0]

NA

In2 Under
Out1 Shorted
Out1 Open
Out2 Shorted
Out2 Open
In1 Over
In1 Under
In2 Over

X.38

Alarm Enable

0/255 [0]

NA

In2 Under
Out1 Shorted
Out1 Open
Out2 Shorted
Out2 Open
In1 Over
In1 Under
In2 Over

X.39

Restart Enable

0/255 [0]

NA

In2 Under
Out1 Shorted
Out1 Open
Out2 Shorted
Out2 Open

X.40

In1 Over F Lvl

-3000.0/3000.0
[1050.0]

NA

NA

If Input 1 exceeds this level for the time period set in the In1 Over F Dly
parameter, an In1 Over fault will be signaled. The In1 Over bit must be
set in the Fault Enable Parameter

R/W

X.41

In1 Over F Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 1 must exceed the In1 Over F Lvl to signal a
fault. The In1 Over bit must be set in the Fault Enable Parameter

R/W

X.42

In1 Over A Lvl

-3000.0/3000.0
[1000.0]

NA

NA

If Input 1 exceeds this level for the time period set in the In1 Over A Dly
parameter, an In1 Over alarm will be signaled. The In1 Over bit must be
set in the Alarm Enable Parameter

R/W

X.43

In1 Over A Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 1 must exceed the In1 Over F Lvl to signal a
fault. The In1 Over bit must be set in the Fault Enable Parameter.

R/W

X.44

In1 Under F Lvl

-3000.0/3000.0
[-50.0]

NA

NA

X.45

In1 Under F Dly

0.1/99.0 [3.0]

sec

NA

284

If Input 1 remains below this level for the time period set in the In1
Under F Dly parameter, an In1 Under fault will be signaled. The In1
Under bit must be set in the Fault Enable Parameter
The time period that Input 1 must remain below the In1 Under F Lvl to
signal a fault. The In1 Under bit must be set in the Fault Enable
Parameter

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

R/W

R/W

Parameter Information

Appendix B

Number Name

Min./Max.
[Default]

Units Enum Text

Description

Read/Write
Access

X.46

In1 Under A Lvl

-3000.0/3000.0
[0.0]

NA

NA

If Input 1 remains below this level for the time period set in the In1
Under A Dly parameter, an In1 Under alarm will be signaled. The In1
Under bit must be set in the Alarm Enable Parameter

R/W

X.47

In1 Under A Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 1 must remain below the In1 Under F Lvl to
signal a fault. The In1 Under bit must be set in the Fault Enable
Parameter.

R/W

X.48

In2 Over F Lvl

-3000.0/3000.0
[1050.0]

NA

NA

If Input 2 exceeds this level for the time period set in the In2 Over F Dly
parameter, an In2 Over fault will be signaled. The In2 Over bit must be
set in the Fault Enable Parameter

R/W

X.49

In2 Over F Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 2 must exceed the In2 Over F Lvl to signal a
fault. The In2 Over bit must be set in the Fault Enable Parameter

R/W

X.50

In2 Over A Lvl

-3000.0/3000.0
[1000.0]

NA

NA

If Input 2 exceeds this level for the time period set in the In2 Over A Dly
parameter, an In2 Over alarm will be signaled. The In2 Over bit must be
set in the Alarm Enable Parameter

R/W

X.51

In2 Over A Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 2 must exceed the In2 Over F Lvl to signal a
fault. The In2 Over bit must be set in the Fault Enable Parameter

R/W

X.52

In2 Under F Lvl

-3000.0/3000.0
[-50.0]

NA

NA

If Input 2 remains below this level for the time period set in the In2
Under F Dly parameter, an In2 Under fault will be signaled. The In2
Under bit must be set in the Fault Enable Parameter

R/W

X.53

In2 Under F Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 2 must remain below the In2 Under F Lvl to
signal a fault. The In2 Under bit must be set in the Fault Enable
Parameter

R/W

X.54

In2 Under A Lvl

-3000.0/3000.0
[0.0]

NA

NA

If Input 2 remains below this level for the time period set in the In2
Under A Dly parameter, an In2 Under alarm will be signaled. The In2
Under bit must be set in the Alarm Enable Parameter

R/W

X.55

In2 Under A Dly

0.1/99.0 [3.0]

sec

NA

The time period that Input 2 must remain below the In2 Under F Lvl to
signal a fault. The In2 Under bit must be set in the Fault Enable
Parameter

R/W

X.56

Parameter Mgmt

0/1 [0]

NA

Ready

Waiting for command to set defaults

Set Defaults

Set all writable parameters to factory default values

R/W

X indicates the Control module Port number in which the Cat. No. 150-SM3 Analog I/O option module is installed. Allowable ports = 7, 8, or 9.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

285

Appendix B

286

Parameter Information

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Appendix

Spare/Replacement Parts

SMC-50 Power Poles and


Assemblies

Table 158 - Power Poles and Assemblies Cat. Nos.

Description

Frame B Power Structure Assembly


(Contains all three power poles in a
single package and includes the
pole-to-control module transition
cover and cooling fan.)

Frame C Power Pole


(Contains one power pole SCR
and heatsink assembly and cable.)

Frame D Power Pole


(Contains one power pole SCR
and heatsink assembly and cable.)

SMC-50 Control Modules

Rating
90 A, 200480V AC line
110 A, 200480V AC line
140 A, 200480V AC line
180 A, 200480V AC line
90 A, 200690V AC line
110 A, 200690V AC line
140 A, 200690V AC line
180 A, 200690V AC line
210 A, 200480V AC line
260 A, 200480V AC line
320 A, 200480V AC line
210 A, 200690V AC line
260 A, 200690V AC line
320 A, 200690V AC line
361 A, 200480V AC line
420 A, 200480V AC line
520 A, 200480V AC line
361 A, 200690V AC line
420 A, 200690V AC line
520 A, 200690V AC line

Cat. No.

Cat. No.

150-SPPB1B
150-SPPB1BR
150-SPPB2B
150-SPPB2BR
150-SPPB3B
150-SPPB3BR
150-SPPB4B
150-SPPB4BR
150-SPPB1U
150-SPPB1UR
150-SPPB2U
150-SPPB2UR
150-SPPB3U
150-SPPB3UR
150-SPPB4U
150-SPPB4UR
150-SPPC1B
150-SPPC2B
150-SPPC3B
150-SPPC1U
150-SPPC2U
150-SPPC3U
150-SPPD1B
150-SPPD2B
150-SPPD3B
150-SPPD1U
150-SPPD2U
150-SPPD3U

Table 159 - SMC-50 Replacement Control Module Cat. Nos.


Description

Cat. No.

Replacement Control Module 100...240V AC Control Power (Two 24V DC


Inputs, Two Relay Outputs)
Replacement Control Module 24V DC Control Power (Two 24V DC Inputs, Two
Relay Outputs)

150-SCMD
150-SCMR

Control module includes cover.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

287

Appendix C

Spare/Replacement Parts

Option Modules

Table 160 - Option Module Cat. Nos.


Description

Rating

Cat. No.

PTC, Ground Fault, & Current Feedback

Two analog inputs (voltage or


current) and two analog outputs
(voltage or current)
Four inputs (120/240V AC)
3 relay outputs
DIP & Rotary Switch Configuration

150-SM2
150-SM3

Analog I/O Module


Digital I/O Module
Parameter Configuration Module

Removable Terminal
Blocks for Control Wiring

Where
Used

Control Module Control I/O replacement removable terminal block


PTC Module replacement removable terminal block (set of 3)
Analog I/O Option replacement removable terminal block
Digital I/O Option replacement removable terminal block

Covers

Control
Module
150-SM2
150-SM3
150-SM4

Cat. No.
150-SCMRTB
150-SM2RTB
150-SM3RTB
150-SM4RTB

Table 162 - Replacement Fan Cat. Nos.


Description

Rating

Replacement Fan for Cat. No. 150-SB


Controller

90180 A

Replacement Fan for Cat. No. 150-SC


Controller

210320 A

Replacement Fan for Cat. No.


150-SD Controller

361520 A

Control Power

Cat. No.

100240V AC
24V DC
100240V AC
24V DC
100240V AC

150-SF1
150-SF1R
150-SF2D

24V DC

150-SF3R

150-SF2R
150-SF3D

Table 163 - Replacement Cover Cat. Nos.


Description
Replacement Fan Cover for Cat. No. 150-SB Controller
Replacement Fan Cover for Cat. No. 150-SC Controller
Replacement Fan Cover for Cat. No. 150-SD Controller
Replacement Control Module Front Cover
Replacement Controller Cover
Replacement Controller Cover

288

150-SM6

Table 161 - Replacement Terminal Block(s) Cat. Nos.

Description

Fan

150-SM4

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Rating

Cat. No.

90180 A
210320 A
361520 A
90520 A
210320 A
361520 A

150-SBFC
150-SCFC
150-SDFC
150-SCMRC
150-SCRC
150-SDRC

Spare/Replacement Parts

Battery

Appendix C

Table 164 - Replacement Battery for RTC


Description
Manganese Dioxide Lithium Coin Cell
Battery

Rating

Cat. No.

Normal Capacity: 220 m A h


Nominal Voltage: 3V

Not a RA Listed
Cat. No.

Commercially available as CR2032.

Renewal Part Instructions:

Fan: Publication 150-IN054


Fan Cover: Publication 150-IN057
Control Module Cover: Publication 10000152882
I/O Module RTB: Publication 150-IN058
PTC Option Module RTB: Publication 10000152885
Control Module RTB: Publication 10000152887
Power Section, Frame B: Publication 10000152876
Power Pole, Frame C: Publication 150-IN069
Power Pole, Frame D: Publication 150-IN070
Control Module, Frame B: Publication 10000152876
Control Module, Frames C and D: Publication 150-IN067
Shroud, Frames C and D: Publication 150-IN068

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

289

Appendix C

290

Spare/Replacement Parts

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Appendix

Control Module/Power Pole Assembly


Replacement

SHOCK HAZARD: To prevent electrical shock, disconnect the control


module and power pole assembly from all power sources before
installing or servicing. Install in a suitable enclosure. Keep free from
contaminants.

Removal & Replacement

Figure 97 - Control Module Removal

Step 1
1
x4

210520 A Devices

90180 A Devices

Step 2
P6
TB3

TB4

TB2

TB7
TB6

TB5

90520 A Devices

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

291

Appendix D

Control Module/Power Pole Assembly Replacement

Figure 98 - Control Module Replacement


Step 1

90520 A Devices
P6
TB2 TB3 TB4

P6

TB4

TB3
TB2

TB5

TB6

TB7

TB7
TB6
TB5

Step 2
90180 A Devices

210520 A Devices

x4

0.7 Nm
(6 lb-in)

Click

292

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Appendix

Accessories

Catalog Numbers

Table 165 - Accessories Cat. Nos.

Description

Cat. No.
Option Modules

PTC, Ground Fault, & Current Feedback

150-SM2

Analog I/O

150-SM3

Digital I/O

150-SM4
150-SM6

Parameter Configuration Module


Converter Modules
30180 A Three-Phase Current Monitoring

825-MCM180

181520 A Three-Phase Current Monitoring

825-MCM20
825-CBCT

90520 A Core Balance Ground Fault Sensor


Protective Modules
90520 A, 480V AC

150-F84L
150-F86L

90520 A, 600V AC
Terminal Lugs
90320 A

199-LF1

361520 A

199-LG1

155311 A Inside-the-Delta Connection Distribution Block

1492-BG

363554 A Inside-the-Delta Connection Distribution Block

Marathon Special Products


1353703

625900 A Inside-the-Delta Connection Distribution Block

Marathon Special Products


1352702

90180 A Bypass Connection

1494R-N14

210320 A Bypass Kits

150-SCBK

361520 A Bypass Kits

150-SDBK
IEC Terminal Covers

90180 A Line or Load Terminal Cover

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

150-STCB

293

Appendix E

Accessories

HIM
SMC-50 Bezel Mount or Hand-Held

20-HIM-A6

Door-Mounted (includes cable) NEMA Type 4X/1A

20-HIM-C6S

Remote Mount Bezel

20-HIM-B1

Extension Cables

0.3 m (0.98 ft)

1202-H03

1.0 m (3.28 ft)

1202-H10

3.0 m (9.8 ft)

1202-H30

9.0 m (29.5 ft)

1202-H90
1203-S03

Splitter Cable
Communication Modules
DeviceNet

20-COMM-D

ControlNet

20-COMM-C

Profibus

20-COMM-P

RS 485 DF1

20-COMM-S

InterBus

20-COMM-I

Modbus/TCP

20-COMM-M

EtherNet

20-COMM-E

Dual-Port EtherNet

20-COMM-ER

RS 485 HVAC

20-COMM-H

ControlNet (Fiber)

20-COMM-Q

Programming Software for


Windows 7/2000/XP/Vista

PC Interface

DriveExecutive

9303-4DTE01ENE

DriveTools SP

9303-4DTS01ENE

Connected Components Workbench

download from
www.rockwellautomation.com

AnaCANda RS232 to DPI Serial

1203-SSS

AnaCANda USB to DPI

1203-USB

USB

Used with a Cat. No. 150-SM2 to provide current feedback to the SMC-50 when in external bypass configuration.
Requires user-supplied current transformers with 5 A secondary.
Requires Cat. No. 199-LF1 lugs.
Requires Cat. No. 199-LG1 lugs.
For remote mounting details, see the HIM User Manual, 20HIM-UM001.
The hand-held HIM requires a Cat. No. 20-HIM-H10 cable
Includes a Cat. No. 1202-C30 cable that is 3.0 m (9.8 ft) in length.
Includes DriveExecutive and DriveObserver.
Includes Cat. No. 1203-SFC and 1202-C10 cables.
Includes Cat. No. 20-HIM-H10 and 22-HIM-H10 cables.

294

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Appendix

Using DeviceLogix

Introduction

DeviceLogix (DLX) is a standard feature in the SMC-50 (firmware 4.002 and


higher). DeviceLogix can be used to control and monitor the SMC-50.
DeviceLogix programming for the SMC-50 is accomplished through a
DeviceLogix Editor component (
icon), available in Connected Components
Workbench version 6 and later. Other DeviceLogix Editors, such as RSNetWorx for
DeviceNet, cannot be used.
Table 166 - Basic features:
SMC-50 4.002 and later
DeviceLogix Library
Maximum number of function blocks
Program update time per number of blocks used

Version 5
32
20 ms (fixed): 110 blocks
30 ms (fixed): 1121 blocks
40 ms (fixed): 2232 blocks

The SMC-50 DeviceLogix implementation provides basic logic capability for


applications. A 2040 ms scan time is provided depending on program size.
DeviceLogix can be used in both networked and stand- alone environments.
DeviceLogix continues execution independent of the SMC-50s state (starting,
running, fault, etc.)
There is no data retention in DeviceLogix during a power cycle. Timer and counter
accumulators, calculation results, latched bits, etc. will be cleared.
Controlling the SMC-50 operating modes (starting, stopping, slow speed etc.)
through DeviceLogix requires that bit #14 of the Logic Mask (parameter #148)
be set.

Parameters

See Parameter 334346 on page 276 for DeviceLogix parameter descriptions.

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

295

Appendix F

Using DeviceLogix

Function Block Elements

The following function block elements are available:


Bit and Analog I/O
Process
Select/Limit
Timer/Counter
Compare
Compute/Math
Move/Logical
Macro Block
Bit and Analog I/O do not count against the Function Block total. All other elements count, with each instance

counting as one Function Block.

The DeviceLogix Editor provides a graphical interface for configuring Function


Blocks to provide local control within the drive. DeviceLogix Editor navigation
and programming basics are not covered in this manual. Refer to the DeviceLogix
User Manual, publication RA-UM003A for additional information. It can be
found on the RA Literature Library web site at:
http://www.rockwellautomation.com/literature.

Macro Blocks
Up to five Macro Blocks can be created by the user and each can be used five
times. The selections will be empty until a Macro Block gets created. The icon
text associated with each Macro Block is also created by the user.

296

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Using DeviceLogix

Appendix F

Bit and Analog I/O Points


The DeviceLogix controller in Port 14 uses (32) bit inputs, (18) bit outputs, (24)
analog inputs, and (2) analog outputs.

Bit Inputs
Available bit inputs to the DeviceLogix program include:
Bit Inputs

(17) Hardware Boolean Inputs

Name

Description

Input 1, Input 2

State of the 2 inputs on the control module.

P7 Ready, P8 Ready, P9
Ready

Status indicating that the expansion card installed into


the corresponding expansion port is functioning and
Ready

PX input 1 PX input 4

Status of the Boolean inputs from the expansion cards


See the Expansion Card Mapping table below

Running
Phase Rotation
Phase Detection
Starting
Stopping
Alarm
Fault
At Speed
Start
Bypass
Ready

These Boolean inputs correspond to the statuses listed


in Table 102 - Logic Status on page 210

Network Bit 1
Network Bit 2
Network Bit 3
Network Bit 4

These Boolean inputs correspond to the statuses listed


in Table 103 - Logic Command Word (Control) on
page 211

(15) Network Boolean Inputs

The function of the expansion port inputs depends on the card installed in the
given port. The following table shows how the bit inputs are mapped for each
card type:
Bit Input

Digital I/O
(150-SM4)

Analog I/O
(150-SM3)

PTC / Grd Fault


(150-SM2)

Parameter Config
(150-SM6)
None (always 0)

PX Input 1

Input #1

DAC #1 Open Status

PTC Status

PX Input 2

Input #2

DAC #1 Shorted Status

CT Loss Status

None (always 0)

PX Input 3

Input #3

DAC #2 Open Status

None (always 0)

None (always 0)

PX Input 4

Input #4

DAC #1 Shorted Status

None (always 0)

None (always 0)

Bit Outputs
Bit Outputs are used to connect to real-world output devices (pilot lights, relays,
etc.) that are wired to an Auxiliary Relay in the SMC-50. Available bit outputs
from the DeviceLogix program include:

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

297

Appendix F

Using DeviceLogix

Bit Outputs
(11) Hardware Boolean Outputs

Name

Description

Aux 1, Aux2

Auxiliary Relays available on the control board.

PX Aux1 PX Aux3

Auxiliary Relays #1 - #3 available on the Digital I/O


(150-SM4) Expansion Card

Coast
Start
Stop
CLR Fault
Slow Speed
Emergency Run
Motor Heater

These outputs can be used to control the SMC-50 in the


same way a PLC can control the SMC-50. See Table 103 Logic Command Word (Control) on page 211 for a
definition of these control bits.

(7) Network Boolean Outputs

The Auxiliary Relays must be programmed to Device Logix to allow the DeviceLogix program to control each
specific relay. For example, if you want to control Aux 1 on the control module you must configure Aux1
Config (parameter #172) to Device Logix. Similarly, to control Aux 1 in a Digital I/O (150-SM4) expansion
card you must configure Aux 1 Config (parameter #6 in the expansion card) to Device Logix.

Analog Inputs
Available analog inputs to the DeviceLogix program are all 32-bit integers and
include the following data points:
Analog Inputs

(22) Network Analog


Inputs

Name

Description

Volt PP Ave

Average Phase to Phase Voltage (Param #1 - Volts)

I Ave

Average Current (Param #5 Amps)

Torque

Average Torque (Param #9 - %)

Real Power

Total Real Power (Param #10 Kwatts)

Power Factor

Average Power Factor (Param #17 in hundredths)

Volt PN Ave

Average Phase to Neutral Voltage (Param #265 Volts)

Reactive Power

Total Reactive Power (Param #277 Kwatts)

Apparent Power

Total Apparent Power (Param #286 Kwatts)

DLX In 1, DLX In 2

DLX General Purpose Input parameters (Param #335, #336)

DLX DL1 DLX DL6 DLX Datalink Input Parameters (Param #337-342)
PX In 1 PX In 2

Analog inputs from the expansion cards See the Expansion


Card Mapping table below

The function of the expansion port inputs depends on the card installed in the
given port. The following table shows how the analog inputs are mapped for each
card type:

298

Bit Input

Digital I/O
(150-SM4)

Analog I/O
(150-SM3)

PTC / Grd Fault


(150-SM2)

Parameter Config
(150-SM6)

PX In 1
PX In 2

None (always 0)

Analog In #1 (Param X.6)

Ground Current (Param #11)

None (always 0)

None (always 0)

Analog In #2 (Param X.16)

None (always 0)

None (always 0)

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Using DeviceLogix

Appendix F

Analog Outputs
Available analog outputs from the DeviceLogix program are all 32-bit integers
and include the following data points:
Analog Outputs

Name

Description

(2) Network Analog Outputs A Out 1 A Out 2

Tips

General Purpose Output parameters (Param #343, #344)

Data types
The SMC-50 DeviceLogix implementation supports 32-bit integers only.

DeviceLogix scratchpad registers


The SMC-50 provides 2 input (parameter #335, #336) and 2 output (parameter
#343, #344) scratchpad registers. The input parameters can be written by any
configuration or network device and used as an input to DeviceLogix. The
output parameters can be written by DeviceLogix and displayed on configuration
devices or read using network devices.

SMC-50 DeviceLogix Input Datalinks (P337P342)


The SMC-50 provides parameters directly to DeviceLogix as analog inputs.
Additional parameters from the host and expansion cards can be made available
through the DeviceLogix Datalink inputs. The value of the parameter linked to
by the datalink will be made available to DeviceLogix. For example, configuring a
datalink to Mtr Therm Usage (parameter #18) would make the motor thermal
usage value available to DeviceLogix.

Program Examples

Example 1: Selector Switch Operation


This example demonstrates how a selector switch could be used to select 1 or 4
parameters to write to one of the scratchpad output parameters.
The truth table below represents the inputs and outputs for a 4 position selector
switch.
Inputs

Outputs

Input 1

Input 2

Output Selection

Volt PP Ave

Volt Phase A-B

Volt Phase B-C

Volt Phase C-A

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Selector Switch Output

299

Appendix F

Using DeviceLogix

Parameter Configuration
Since the individual phase voltage parameters are not directly available in
DeviceLogix (only the average voltage Volt PP Ave is) we will use three of the
DeviceLogix Datalink parameters to make those values available to DeviceLogix
as follows:
Parameter No.
337

Parameter

Value

Description

DLX DL Input 1

Port 0: Volts Phase A-B

Value for Selection 01

338

DLX DL Input 2

Port 0: Volts Phase B-C

Value for selection 10

339

DLX DL Input 3

Port 0: Volts Phase C-A

Value for selection 11

Figure 99 - Function Block Programming

300

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Using DeviceLogix

Appendix F

Example 2: Diverter Operation


This example demonstrates basic control logic to operate a diverter in a conveyor
system using a in Digital I/O (150-SM4) option module card installed in Port #8.
The diverter directs parts from an upstream conveyor to one of two downstream
conveyors. The parameter DLX Input 1 (parameter # 335) defines the total
number of boxes diverted to conveyer A (when the diverter control signal is
off ). The parameter DLX Input 2 (parameter # 336) defines the total number
of boxes diverted to conveyer B (when the diverter control signal is on).
Sensor

Diverter

Upstream Conveyor
Downstream Conveyor

The application consists of the following discrete I/O:


Type

Name

Description

Inputs

Part Present Sensor

Identifies that a part is present Connected to Input #1 on an Digital


I/O (150-SM4) card installed in Port #8

Outputs

Diverter Actuator

Controls the diverter actuator to direct the flow of parts Connected


to Aux #1 on an Digital I/O (150-SM4) card installed in Port #8

Example logic requirements:


When Part Present Sensor transitions to ON increment the parts counter
If parts counter is greater than or equal to DLX Input 1 then set the
diverter actuator
When the counter reaches DLX Input 1 + DLX Input 2 reset the
counter.

Parameter Configuration
The following parameters are configured for this example:
Port Parameter No.

Parameter

Value

Description

335

DLX Input 1

Send 5 boxes down conveyer A

336

DLX Input 2

8.6
Port #8
Parameter #6

Aux 1 Config

Send 5 boxes down conveyer B


Device Logix

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Auxiliary #1 is used to control the Diverter. In


order for Device Logix to control the Auxiliary it
must be configured to Device Logix.

301

Appendix F

Using DeviceLogix

Figure 100 - Function Block Programming

Example 3: Wet Well Operation


This example demonstrates how basic control logic can be used for motor
control. It is assumed that a Digital I/O (150-SM4) option module is installed in
Port #8.
Figure 101 - Wet Well

Inflow
Critical High Level Sensor
High Level Sensor

Low Level Sensor

Outflow

302

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Using DeviceLogix

Appendix F

The application consists of the following discrete I/O:


Type

Inputs

Location of I/O

Name

Description

Port #8 Input #2

Critical High Level


sensor

Indicates a critically high level. It is normally a backup to


the High Level sensor and is also used to detect if the
High Level sensor is faulty.

Port #8 Input #3

High Level sensor

Indicates the well is at a high level and it is time to start


pumping using the SMC-50.

Port #8 Input #4

Low Level sensor

When OFF, it is used to indicate that the well is empty


(as long as the High and Critical High Level sensors are
also OFF). The SMC-50 stops operating (end of pumping
cycle).

Port #8 Aux #1

Sensor Failure pilot


light

Indicates that there is a problem with either the High


Level or Low Level sensors

Outputs Port #8 Aux #2


No External Wiring

Start

Critical Level Pilot light Indicates that the Critical Level Sensor is active.
Start signal to the SMC-50.

No External Wiring

Stop

Stop signal to the SMC-50.

Example logic requirements:


Start the motor when the High Level Sensor is ON.
Stop the motor when all the level sensors are OFF.
Annunciate a Sensor Fault condition and Stop the SMC-50 when any of
these conditions exist:
The Low Level sensor is OFF when either the High Level or Critical
High Level sensors are ON
The High Level sensor is OFF when the Critical High Level sensor is
ON
Activate the Critical High Level Pilot when the Critical High Level sensor
is active.
Reset alarms / faults with a Reset push button input

Parameter Configuration
The following parameters are configured for this example.
Port Parameter No. Parameter

Value

Description

0.148.14
Host Parameter #148 Logic Mask
Bit #14

Set bit #14

Allow DeviceLogix to control the motor.

8.6
Port #8
Parameter #6

Aux 1 Config

Device Logix

Auxiliary #1 is used to control the Sensor


Failure pilot light. In order for DeviceLogix to
control the Auxiliary it must be configured to
Device Logix.

8.10
Port #8
Parameter #10

Aux 2 Config

Device Logix

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Auxiliary #2 is used to control the Critical


Level pilot light. In order for DeviceLogix to
control the Auxiliary it must be configured to
Device Logix.

303

Appendix F

Using DeviceLogix

Figure 102 - Function Block Programming

304

Rockwell Automation Publication 150-UM011C-EN-P - March 2014

Rockwell Automation Support


Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to
software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software
updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.

Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada

1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local


Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Automation maintains current product environmental information on its website at


http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Rockwell Automation Publication 150-UM011C-EN-P - March 2014


Supersedes Publication 150-UM011B-EN-P January 2013

Copyright 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like