Manual Piso Elevado
Manual Piso Elevado
Manual Piso Elevado
SustainAbility
to the Power of
Technical Resources:
Design & Resource Support
Tate offers a variety of avenues to access our unsurpassed
technical assistance and support from design through construction
completion. Draw upon our unmatched breadth of experience
using one or more of our valuable resources.
Dealer Network
Tates worldwide team of dealers will assist you with your
building needs. Find a dealer in your area by clicking on contacts
at www.tateinc.com.
Comprehensive Website
Find everything you need from detailed product information,
technical support documentation and specifications to industry links,
project case studies and more at www.tateinc.com.
Visit www.tateinc.com or call the Technical Services Team at 800.231.7788.
7
8
9
10
12
14
a point load of no less than (2) two times its design load rating
Safety Factor2 is the multiple of the design load to the ultimate load.
Design Features
Panel Construction
Flat steel top sheet welded 156 times to a waffle shape bottom sheet then filled internally with lightweight cement.
Recycled Content
Positive Engagement
Tates PosiLock pedestal head positions and retains panels in place without screws.
Combustibility*
Class A flame spread rating, and noncombustible compliant with ASTM E136-99.
Corner Screws
Screws do not extend below panel underneath. Screws are designed with retention feature.
Finish Options
Almost unlimited factory laminated finish options. PosiTile carpet & Integral Trim edge for HPL.
Performance
Walkability*
Safety Factor*
System provides a safety factor greater than two during static point load tests meeting all international standards.
Overload Protection
5 interchangeable panel strengths, meet all the requirements of a modern office building.
Cutout Strength*
System maintains design load and minimum safety factor strength when cut.
Air Leakage*
Straight, die cut panel edges yield low and predictable panel seam air leakage rates.
Plenum Divider
Attaches to pedestals maintaining underfloor access. Adjustable to meet any width requirement.
Painted steel panels with tight seams minimize dust and debris entering the air delivery plenum.
Industry Commitment
Tate is the oldest and largest manufacturer dedicated solely to the R&D and marketing of access flooring.
Easy to carry with one hand and can be removed with a suction cup lifter. Panels are 25% lighter than concrete panels.
Shock Resistance
Steel panels are free from unsightly cracks which improve life cycle and reuse.
Edge Design
Thin edge design eliminates adhesives from leaking between panels locking them place.
Ease of Cutting
Attaching Walls
Screws and shot-pin can be driven directly into the panel without sacrificing its integrity.
Key Features
Plenum
ConCore Panels
ConCore Access Floor panels are epoxy coated unitized
shells consisting of a flat steel top sheet welded to a formed
steel bottom sheet filled with a highly controlled mixture of
lightweight cement. Manufactured to exacting
tolerances, these non-combustible, rigid, solid
panels deliver the ultimate in strength, durability,
and acoustic performance.
Applications
With five standard load performance grades and an extensive
selection of understructure supports and floor finishes, it is
recommended that you visit our website: www.tateinc.com for
further information on product details, finish options, architectural
details, system specification, and selecting the proper panel to
meet the needs of your specific application.
Static Loads
Rolling Loads
Understructure
System
Weight
(lbs/ft2)
Design
Loads1
(lbs)
Safety
Factors2
(min 2.0)
10
Passes
(lbs)
10,000
Passes
(lbs)
Impact
Loads
(lbs)
ConCore 1000
PosiLock
8.0 (39kg/m2)
1000 (4.4kN)
PASS
800 (3.6kN)
600 (2.7kN)
150 (68kg)
ConCore 1250
PosiLock
8.5 (42kg/m2)
1250 (5.6kN)
PASS
1125 (5.0kN)
875 (3.9kN)
150 (68kg)
ConCore 1500
PosiLock
9.0 (44kg/m )
1500 (6.7kN)
PASS
1250 (5.6kN)
1000 (4.4kN)
150 (68kg)
ConCore 1000
Bolted Stringer
9.0 (44kg/m2)
1000 (4.4kN)
PASS
800 (3.6kN)
600 (2.7kN)
150 (68kg)
ConCore 1250
Bolted Stringer
10.0 (49kg/m2)
1250 (5.6kN)
PASS
1000 (4.4kN)
800 (3.6kN)
150 (68kg)
ConCore 1500
Bolted Stringer
10.5 (51kg/m2)
1500 (6.7kN)
PASS
1250 (5.6kN)
1000 (4.4kN)
150 (68kg)
ConCore 2000
Bolted Stringer
11.5 (56kg/m2)
2000 (8.9kN)
PASS
1500 (6.7kN)
1250 (5.6kN)
150 (68kg)
ConCore 2500
Bolted Stringer
12.0 (59kg/m )
2500 (11.1kN)
PASS
2000 (8.9kN)
2000 (8.9kN)
150 (68kg)
ConCore 3000
Bolted Stringer
13.0 (63kg/m2)
3000 (13.3kN)
PASS
200 (91kg)
Panel
*All tests are performed using CISCAs Recommended Test Procedures for Access Floors with the exception of Design Load
1. Design Load is tested using CISCAs Concentrated Load test method on actual understructure instead of steel blocks. Design Load is
determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur (yield point).
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Tate recommend a minimum of 2.
Table
Header
Table
Table
Header
Header
Content
Content
Content
The safe working load or design load for the panels are
equal to the concentrated load
Applications
Completely non-combustible
Rolling Loads
Panel
Understructure
System
Weight
(lbs/ft2)
Design
Loads1
(lbs)
Safety
Factors2
(min 2.0)
10
Passes
(lbs)
10,000
Passes
(lbs)
Impact
Loads
(lbs)
Bolted Stringer
6.0 (29kg/m2)
1000 (4.4kN)
PASS
400 (1.8kN)
400 (1.8kN)
150 (68kg)
Bolted Stringer
7.0 (34kg/m2)
1250 (5.6kN)
PASS
500 (2.2kN)
500 (2.2kN)
150 (68kg)
Bolted Stringer
8.5 (42kg/m2)
1500 (6.7kN)
PASS
600 (2.7kN)
600 (2.7kN)
150 (68kg)
*All tests are performed using CISCAs Recommended Test Procedures for Access Floors with the exception of Design Load
1. Design Load is tested using CISCAs Concentrated Load test method on actual understructure instead of steel blocks. Design Load is
determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur (yield point).
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Tate recommend a minimum of 2.
Understructure Systems
for ConCore and All Steel Systems
PosiLock
Understructure Features
Self-capturing fastener remains within the panel - will not get lost.
Panel engagement
feature viewed from
underside
27/8" (7cm) finished floor height is ideal for renovation applications while
providing enough space under the floor to allow for easy cable
management.
Bolted Stringer
Understructure Features
Stringers provide lateral resistance to heavy rolling loads and seismic loading.
Seismic Pedestals
Understructure Features
Woodcore Panels
Woodcore panels consist of high density composite wood
core glued to and encased in hot dipped galvanized formed
steel sheets. These panels are ULC Listed for flame spread
and smoke development and provide excellent rigidity,
durability, and acoustic performance.
Panel Features
Internally grounded.
Applications
Woodcore panels are available with several understructure
Rolling Loads
Understructure
System
Weight
(lbs/ft2)
WC5000
CornerLock
6.9 (34kg/m2)
1000 (4.4kN)
PASS
1000 (4.4kN)
700 (3.1kN)
150 (68kg)
WC5000
Snap-Tite/Bolt-Tite
7.4 (36kg/m )
1000 (4.4kN)
PASS
1000 (4.4kN)
700 (3.1kN)
150 (68kg)
WC5000
7.6 (37kg/m2)
1250 (5.6kN)
PASS
1250 (5.6kN)
875 (3.9kN)
150 (68kg)
WC6000
8.3 (41kg/m )
1500 (6.7kN)
PASS
1500 (6.7kN)
1050 (4.7kN)
150 (68kg)
Panel
Design
Loads
(lbs)
Safety
Factors
(min 2.0)
10
Passes
(lbs)
10,000
Passes
(lbs)
Impact
Loads
(lbs)
*All tests are performed using CISCAs Recommended Test Procedures for Access Floors with the exception of Design Load
1. Design Load is tested using CISCAs Concentrated Load test method on actual understructure instead of steel blocks. Design Load is
determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur (yield point).
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Tate recommend a minimum of 2.
10
Understructure
Cornerlock
understructure system with the air
seal gasket mechanically
attached to the panel. Used
primarily for office environments
with modular carpet tile.
11
Solid Panel
Understructure
System
Weight
(lbs/ft2)
Design
Loads*
(lbs)
Safety
Factors*
(min 2.0)
All
6.50 (32kg/m2)
1250 (5.6kN)
Pass
150 (68kg)
All
6.50 (32kg/m2)
1250 (5.6kN)
Pass
100 (45kg)
FF1250 Grates
All
7.25 (35kg/m )
1250 (5.6kN)
Pass
150 (68kg)
All
Pass
200 (91kg)
All
7.40 (36kg/m2)
Pass
100 (45kg)
Panel
2000 (8.9kN)
10
Passes
(lbs)
10,000
Passes
(lbs)
*All tests are performed using CISCAs Recommended Test Procedures for Access Floors with the exception of Design Load
1. Design Load is tested using CISCAs Concentrated Load test method on actual understructure instead of steel blocks. Design Load is
determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur (yield point).
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Tate recommend a minimum of 2.
Understructure
FF3000 Panel
Stringerless System
FF1250 Panel
Interchangeable Panels
12
Impact
Loads
(lbs)
13
14
Made with PVC Edge for consistent seams that look more like
tradition grout lines.
PosiTile Carpet
PosiTile System Features
Tate Hardwood
Engineered Hardwood System Features
15
Cork
Wood Laminate
Engineered Hardwood
Porcelain
Rubber
Luxury Vinyl
Terrazzo
Carpet Tile
Linoleum
Finishes Online
There are many different materials, vendors and application methods
used to apply finishes on or over access flooring. Tate has
comprised an online resource of tested and approved finishes for
access floor applications. On the website you will find vendor contact
information, application renderings, and product photos to help you
select a finish for your facility.
To access the finishes section of our website please visit
www.tateinc.com/products/finishes.aspx. If you are interested in
using a material or vendor that does not appear on the list or would
like a printed finished brochure please contact the Tate Hotline at
877-999-8283 or e-mail tateinfo@tateinc.com
16
18
19
20
21
22
24
26
27
17
NEW!
Directional Perf Panel
(with 25% open area)
DirectAire Panel
(with 68% open area)
DirectAire Panels
Like the DirectAire panels the Directional Perf angles the airflow
bypass air and achieve a 93% Total Air Capture (TAC) rate. This
means 93% of the air delivered through the panel is entering the
nearly twice the airflow through the panel is entering the face of
Panel Features
Design
Loads1
(lbs)
Rolling Loads
Safety
Factors2
(min 2.0)
10
Passes
(lbs)
10,000
Passes
(lbs)
Impact
Loads
(lbs)
Total
Air
Capture
Panel
Understructure
DirectAire & X2
Bolted Stringer
2000 (8.9kN)
2000 (8.9kN)
200 (91kg)
93%
DPerf 800
Bolted Stringer
9.5 (46kg/m2)
800 (3.6kN)
150 (68kg)
93%
DPerf 1000
Bolted Stringer
10.0 (49kg/m )
1000 (4.4kN)
150 (68kg)
93%
DPerf 1250
Bolted Stringer
10.5 (51kg/m2)
1250 (5.6kN)
150 (68kg)
93%
*All tests are performed using CISCAs Recommended Test Procedures for Access Floors with the exception of Design Load
1. Design Load is tested using CISCAs Concentrated Load test method on actual understructure instead of steel blocks. Design Load is
determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur.
2. Safety factor is the factor of Design load that can be divided into the Ultimate Load. International standards recommend a minimum of 2.
18
GrateAire Panel
(with 56% open area)
Perforated Panel
(with 25% open area)
GrateAire Panels
Perforated Panels
Panel Features
Panel Features
Rolling Loads
Panel
Understructure
System
Weight
(lbs/ft2)
GrateAire
Bolted Stringer
8.0 (39kg/m2)
1000 (4.4kN)
1000 (4.4kN)
800 (3.6kN)
100 (45kg)
50%
Perf 800
Bolted Stringer
9.5 (46kg/m )
800 (3.6kN)
150 (68kg)
50%
Perf 1000
Bolted Stringer
10.0 (49kg/m2)
1000 (4.4kN)
150 (68kg)
50%
Perf 1250
Bolted Stringer
10.5 (51kg/m )
1250 (5.6kN)
150 (68kg)
50%
Design
Loads1
(lbs)
Safety
Factors2
(min 2.0)
10
Passes
(lbs)
10,000
Passes
(lbs)
Impact
Loads
(lbs)
Total
Air
Capture
*All tests are performed using CISCAs Recommended Test Procedures for Access Floors with the exception of Design Load
1. Design Load is tested using CISCAs Concentrated Load test method on actual understructure instead of steel blocks. Design Load is determined by
taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur.
2. Safety factor is the factor of Design load that can be divided into the Ultimate Load. International standards recommend a minimum of 2.
19
Slide Damper
Tate's slide damper is used to manually control airflow under
a GrateAire or Perforated panel. The slide damper is
mechanically attached to the panel to provide airflow control.
Key Performance Characteristics
Easily adjustable from above without panel removal
Mechanically attached to panel for easy underfloor access
20
Zero maintenance
21
PowerAire
PowerAire Quad
Equipped with a variable speed fan drive the fan can be throttled
Zero maintenance
Zero maintenance
22
CFM (L/s) (kW/Rack) CFM (L/s) (kW/Rack) CFM (L/s) (kW/Rack) CFM (L/s) (kW/Rack) CFM (L/s) (kW/Rack)
DirectAire
w/o Damper
1151 (543)
8.5
1626 (767)
12.0
2007 (947)
14.8
2318 (1093)
17.1
2594 (1224)
19.1
w/ OBD
986 (465)
7.3
1427 (673)
10.5
1789 (844)
13.2
2056 (970)
15.2
2331 (1100)
17.2
w/ SmartAire
938 (443)
6.9
1310 (618)
9.7
1666 (786)
12.3
1912 (902)
14.1
2134 (1007)
15.8
w/ PowerAire
2717 (1282)
20.1
2780 (1312)
20.5
2877 (1358)
21.2
2974 (1404)
22.0
3014 (1422)
22.2
w/ PA Quad
2012 (950)
14.9
2061 (973)
15.2
2111 (996)
15.6
2158 (1018)
15.9
2199 (1038)
16.2
w/o Damper
357 (168)
2.6
496 (234)
3.7
602 (284)
4.4
689 (325)
5.1
765 (361)
5.6
w/ Slide damper
260 (123)
1.9
367 (173)
2.7
447 (211)
3.3
515 (243)
3.8
574 (271)
4.2
w/o Damper
916 (432)
3.6
1320 (623)
5.2
1608 (759)
6.4
1860 (878)
7.4
2096 (989)
8.3
w/ OBD
907 (428)
3.6
1313 (620)
5.2
1587 (749)
6.3
1841 (869)
7.3
2062 (973)
8.2
w/ Slide damper
504 (238)
2.0
712 (336)
2.8
876 (413)
3.5
1008 (476)
4.0
1128 (532)
4.5
w/o Damper
332 (152)
1.3
476 (224)
1.9
584 (275)
2.3
666 (314)
2.6
746 (352)
3.0
w/ Slide damper
237 (112)
0.9
328 (155)
1.3
402 (190)
1.6
461 (218)
1.8
515 (243)
2.0
Directional Perf
GrateAire
Standard Perf
*Cooling capacity per rack are calculated based on the following formula (CFM x TAC) / 126 (CFM needed to cool 1kW @ 25T)
23
Aisle Containment
Cold Aisle Containment
partitions around the top of the racks since the hot air will need
used when solid ceiling tiles are in place over the aisle.
ContainAire Partitions
The ContainAire Vertical Partition System combines costeffectiveness and ease of installation to create the finest ceiling
mounted partition system for both hot and cold aisle containment.
Tate formulated special ceiling attachments with a 360 degree swivel
so as to easily attach to ceiling grid in any direction and at any point
along the track.
High-grade aluminum tracks are connected with splicers and then
hung with UL and FM rated fire suppression links designed so that
curtains fall away during a fire, allowing sprinklers full operation range.
Features
Unlimited lengths
24
easy to install ceiling mounted solution for sealing the aisles of the
hot and cold air stream segregated while also allowing for easy
Each door kit includes all of the components and fasteners required
other objects.
to assemble and install the door. The door can be installed without
The ContainAire Strip Door kit includes all of the components and
having to hang it onto the aisle end racks. Instead the door sits on
the floor with two small attachments to the top of the racks.
Features
cement, etc.).
Features
25
KoldLok
Tate offers the full range of surface mount and flush mount
KoldLok grommets in addition to the co-branded Tate KOLDLOK
air sealing grommet. Tate KOLDLOK is a 8.75x11 (22.2cm x
27.9cm) injection molded ABS plastic grommet designed to
mount in a raised floor panel. Supplied with an optional rigid lid
capable of supporting up to 250lbs (113kg) this grommet is
HotLok
HotLok products consisting of blanking panels and rack mounted
grommets reduce high intake air temperatures by preventing hot
exhaust air from circulating to the front of the IT cabinets. This
improves IT equipment reliability and supports cooling infrastructure
optimization.
AisleLok
AisleLok products such as under rack panels and expandable air
26
CRAC Hood
Rack Shield
The CRAC Hood extension is a ceiling return duct that connects the
top of the CRAC unit directly to a ceiling return plenum greatly
increasing cooling capacity and efficiency by capturing hot exhaust
air and channeling it directly into the CRAC unit. The CRAC Hood
will eliminate hot and cold air mixture helping to maintain the proper
Delta T. It will also balance the thermal load by drawing air from one
common source.
The Tate CRAC Hood is a recommended extension for both cold
CRAC Hood
(shown with access door)
28
30
31
32
33
34
Telecom
Rack
Power
Breaker
Panel
Zone
Distribution
Box
Home Run
Cable
Power
Distribution
Box
Power
Extender
Cable
Thermostat
Power
Extender
Cable
PCM
(24 volt)
PVD
Servicenter
Data
Voice
30
In-floor Active
Chilled Beams
Advantages of UFAD
direction control.
Increased daylighting
option through reduction
in large ceiling void
6"
No mixing of indoor
air pollutants
12"
31
12'6"
9'0"
2-Pipe
4-Pipe
Heating
Cooling
{
{
200
400
600
800
1000
1200
1400
1600
Capacity (BTU/hr/LF)
32
1800
2000
2200
2400
EcoCore
Phase Change Technology for Energy Efficiency
EcoCore access floor panels are steel welded shells filled with an
unique mixture of structural cement and PCM that allows the
panel to absorb thermal energy while maintaining the high level of
integrity and quality expected from Tates raised access floors.
This is possible due to utilizing a patent pending method of
mixing microscopic spheres of encapsulated PCM into the
cement. The spheres maintain their size, shape and integrity
throughout phase transitions. This allows the panels to
seamlessly integrate into a raised floor installation providing a low
impact thermal mass to absorb energy during the day that would
otherwise affect both the energy efficiency and comfort level of
the office. The stored energy is then released again overnight as
the temperature drops below the 75 F melting point.
PCM lasts the life of the building (over 100,000 changes)
Benefits of Phase Change in a Raised Floor
Tates raised floor panels provide a safe solution for applying
phase change material in a building. By embedding the material
in cement and then fully encapsulating it in a steel welded shell,
the material is protected from the external environment
2:00PM
8:00PM
33
2:00AM
Casino AirConnect
Creating A Healthy Gaming Environment
Tates AirConnect provides significant advantages in maintaining
air quality, flexibility and the aesthetic integrity of a Casinos
gaming environment. AirConnect uses a variable-air-volume
damper or flexible duct to tap into the pressurized plenum of an
underfloor air distribution system. The air is then delivered at or
near the floor through diffusers mounted in slot bases and other
structures built on top of the raised floor. AirConnect offers the
same flexibility and improved indoor air quality of a typical floor
mounted diffuser only the diffusers can be concealed out of sight
for a more appealing aesthetic.
Features
Easily mounts under any slot base cabinet or pit boss stand.
Can be used with any air diffuser provide by a third party
vendor or custom fabricated by the slot base manufacturer
for a seamless integrated look.
All components are quick connect for easy installation and
removal during casino layout configuration changes.
34
35
Corporate Headquarters:
7510 Montevideo Road, Jessup, MD 20794
Tate Hotline: 1-800-231-7788
Tel: 410-799-4200 Fax: 410-799-4207
Production Facilities:
7510 Montevideo Road, Jessup, MD 20794
52 Springvale Road, Red Lion, PA 17356
Canadian Office & Production Facilities:
880 Equestrian Court, Oakville, ON L6L 6L7 Canada
Tate Hotline: 1-800-231-7788
Tel: 905+847-0138 Fax: 905+847-0141
tateinc.com
kingspan.com
International Sales & Support Office:
169 Jalan Jurong Kechil
#7-011, Sherwood
Singapore 598669
Tel: 65-6468-1332 Fax: 65-6468-6681
tateglobal.com
A member of
0DUNVPXVWEH
DWOHDVWWDOO
DVVKRZQKHUH
;;
FDUERQ
RIIVHW
Tate, ConCore, PosiLock, PosiTile, PVD Servicenter, Floating Floors, Integral Trim, GrateAire, DirectAire, SmartAire, PowerAire and SustainAbility are registered trademarks of
;;
Tate Access Floors, Inc. ContainAire is a trademark of Tate Access Floors, Inc. 2001 Tate Access Floors, Inc. Revised 2013
FDUERQ
RIIVHW
306RU&0<.