Edwards Signaling 302-EPM-194 Data Sheet
Edwards Signaling 302-EPM-194 Data Sheet
Edwards Signaling 302-EPM-194 Data Sheet
Rate Compensation
Heat Detectors
Box mount
Surface Mount
302 Series
MEA
Overview
Application
Series 302 heat detectors are designed for use in normal environments as well as environments where the detectors are subject to
weather, moisture (internal condensation), and explosive atmospheres. They are normally-open devices designed to close an
electrical circuit upon activation. All models feature rate compensation and are available with either 135 F (57.2 C) or 194 F (90
C) ratings. They are self restoring, hermetically sealed, shock and
corrosion resistant, and are tamperproof.
Standard Features
Sensors Rated
Temperature
Minimum Ambient
Air Temperature
Maximum Ceiling
Temperature
135 F (57.2 C)
194 F (90 C)
-40 F (-40 C)
-40 F (-40 C)
100 F (38 C)
150 F (66 C)
The sensor's aluminum tube acts as a heat collector when sources of heat radiate directly on the tube. Install these sensors out of
direct sunlight and away from radiating heat sources including the
direct flow from heaters and heat ducts.
Page 1 of 4
S85001-0589
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Typical Wiring
Rate Compensation
302 Series sensors feature rate compensation, which improves
performance by offsetting thermal lag, an inherent property of
conventional fixed temperature heat sensors.
A slow rate of temperature rise allows the heat to penetrate the
inner expansion struts. The tubular shell and the struts expand
slowly until the total device has been heated to its rated temperature level of 135 F (57.2 C) or 194 F (90 C). At this point, the
silver contact points close and an alarm is initiated.
When subjected to a rapid rate temperature rise, there is not as
much time for heat to penetrate the inner strut. However, the rapid
lengthening of the shell allows the struts to come together at a
lower level.
Black
To control
panel or
next device
End of
Line
Resistor
White
Electrical Rating
Voltage
6-125 VAC
6-25 VDC
125 VDC
Current
5 amps
1 amp
0.5 amp
Maintenance
302 Series heat sensors are low maintenance. Sensors automatically restore when temperatures drop below their rated temperatures. The accumulation of dust and dirt does not normally affect
the sensors operation.
Testing
Testing for operation is simple and can be done before or after the
sensor has been installed. Heat the sensor with a hair dryer (do
not use any device with an open flame to test sensors). The sensor should operate shortly after the hot air is applied.
Setting screw
Devcon hermetic seal
Refer to NFPA 72, National Fire Alarm Code and/or the local
authority having jurisdiction to determine testing frequency, record
keeping, and other testing considerations.
Detector Spacing
Model
UL- Vertical Spacing
(all models)
UL- Horizontal Spacing
(all models)
FM - Horizontal
or vertical spacing.*
302
50' x 50'
(15.2 x 15.2 m)
40' x 40'
(12.2 x 12.2 m)
30' x 30'
(9.1 x 9.1m)
302-AW
50' x 50'
(15.2 x 15.2 m)
40' x 40'
(12.2 x 12.2 m)
30' x 30'
(9.1 x 9.1m)
302-ET
50' x 50'
(15.2 x 15.2 m)
40' x 40'
(12.2 x 12.2 m)
30' x 30'
(9.1 x 9.1m)
302-EPM
40' x 40'
(12.2 x 12.2 m)
30' x 30'
(9.1 x 9.1m)
Not Listed
Spacing is based on smooth ceilings that are up to 10' (3 m) high. Refer to NFPA 72 for ceilings that are not considered smooth or are higher than 10' (3
m).
* EPM models are not FM approved.
Dimensions
Model
Tube Length
Tube Diameter
NPT Thread
Hex Base
Page 2 of 4
ET
3" (76.2 mm)
0.5" (12.7 mm)
0.5" (12.7 mm)
1" (25.4 mm) plastic
EMP
3" (76.2 mm)
0.5" (12.7 mm)
0.5" (12.7 mm)
1.25" (31.75 mm)
brass
WARNING Use For Property Protection Only: Heat detectors do not protect life against fire
and smoke. In most fires, hazardous levels of smoke, heat and toxic gases can build up before a
heat sensor would initiate an alarm. Independent studies indicate that heat sensors should only
be used when property protection alone is involved. In cases where life safety is a factor, the use
of smoke detectors is recommended.
Under no circumstances should heat detectors be relied upon as the sole measure to ensure fire
safety. However, if they are spaced in accordance with the specifications found under Application,
these sensors can contribute, within an overall fire safety program, to reducing the risk of avoidable property losses.
When used with automatic fire suppression systems such as pre-action and deluge sprinkler
systems, carbon dioxide systems, halon systems, and dry chemical systems, at least two sensors should be used to initiate the alarm. This is commonly referred to as cross-zoning or priority
matrix zoning and is necessary to eliminate premature discharge of the system. Refer to NFPA 72
for more information.
S85001-0589
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Ordering Information
Interior applications
302-135
302-194
Ship Wt.
302-AW-194
Ship Wt.
Hermetically sealed for moisture proof
or dust proof installations. Requires no
special back box when the all-weather
leads are properly spliced to THW
or equivalent type wire and splices are
moisture proof. For indoor or outdoor
use.
302-ET-194
Ship Wt.
Hermetically sealed for moisture proof
or dust proof installations. Requires no
special back box. Has plastic hexagonal
grip bushing with " conduit threads
for attachment to threaded hub cover,
or any outlet box. For indoor or outdoor
use when watertight seal is required,
use weatherproof box.
302-EPM194
Decorative white plastic adaptor plate for mounting 302 and 302-AW to any 3" outlet box
or 4" octagon outlet box.
Page 3 of 4
Ship Wt.
3 " Weatherproof, round backbox and cover (" thread hubs back, four sides and cover)
JALX11
Ship Wt.
Outlet body
STONCO27
Ship Wt.
Adapter plate
AP-P
Ship Wt.
Explosion proof outlet body with cover (" thread hubs back, four sides and cover) - Killark
S85001-0589
D ATA S H E E T
Not to be used for installation purposes. Issue 2
Contact us...
Phone: 1-800-336-4206
Web: www.edwardssignaling.com
Edwards Signaling is
an EDWARDS brand.
3 Farm Glen Boulevard
Farmington, CT 06032
In Canada, contact Chubb Edwards...
Email: inquiries@chubbedwards.com
Web: www.chubbedwards.com
2013 UTC Fire & Security Americas
Corporation, Inc. All rights reserved.
Specifications subject to change
without notice. Edwards is part of UTC
Climate, Controls & Security, a unit of
United Technologies Corporation.
S85001-0589
D ATA S H E E T
Not to be used for installation purposes. Issue 2