Plating
All bus bars are electroplated with tin.
This unique tin plating provides excellent
conductivity and resists outside
elements from attaching to the bars.
Optional silver plating is also available.
Insulation
Sentron Busway is insulated with an
Epoxy Powder Coating system designed
by Siemens Engineers, Epoxy System
Engineers and Epoxy Powder
Specialists, specifically for Siemens
Busway products.
The Siemens exclusive Electrostatic
Spray insulation process produces
uniform application of Epoxy powder
over the entire conductor bar. This is
further enhanced by the inline filter
process and magnetic separator that
helps to eliminate contaminants
common to fluidized bed systems. The
electrostatic application also provides a
better coating consistency than that of
the older fluidized bed process. The
combination of electrostatic spray and
lower oven temperatures produces a
consistent coverage with fewer
impurities and pinholes in the insulation.
The lower oven temperatures reduce the
risk of bar annealing, which affects the
overall quality of the system.
Sentron Busway insulation is Class B,
130C Rated. Every bus bar and
completed assembly is dielectricly
tested to ensure the insulation is free
of defects.
14-21
BUSWAY
SYSTEMS
Housing
Sentron Busway incorporates an all
aluminum housing. This lightweight
totally enclosed, non-ventilated housing
resists rust and other elements,
distributes heat away from the
conductors, and provides an excellent
ground path. The totally enclosed design
also eliminates the need for derating of
the system regardless of installation
orientation. The housing is covered with
an electrostatically applied light gray
ANSI 61 polyester urethane powder
paint that is scratch resistant and has a
1,000-hour salt spray resistance rating.
Conductors
Sentron Busway conductors have a
compact construction and can be
configured as 3-phase 3-wire, 3-phase
4-wire or 3-phase 4-wire with 200%
neutral. The conductors may be ordered
in copper (98% conductivity), 1000A/in2
M-Rated Copper, Aluminum (58%
conductivity) and 750A/in2 L-Rated
Aluminum. The optional 200% neutral
helps to handle harmonic conditions that
may exist. This system is especially
useful with discharge lighting
(fluorescent) and computer installations.
This will help to minimize overheating
and prolong the life cycle of your power
distribution equipment.
Ground
Sentron Busway offers ground options
to meet your specifications: standard
integral aluminum housing ground and
optional internal grounding bars. An
optional isolated ground is also available
which is especially useful in applications
where a clean ground is needed.
14
Overview
Busway Systems
BUSWAY
SYSTEMS
14
Overview
Plug-in Opening
Sentron Busway offer plug-in style
busway which feature plug-in openings
rated for finger safety to IP2X in
accordance with IEC 529 and BS EN
60439-1, -2 and BS EN 60529.
Each plug-in opening has a reversible
hinged dead front designed to protect
the contact surfaces from dirt, dust or
moisture. Gasketing is used where
applications require a splash proof
(IP55) rating.
IP Ratings
Sentron Busway is available in a variety
of IP ratings. Use the chart below to
determine the IP rating that best fits
your application needs.
Testing
Each piece of Sentron Busway is factory
tested before shipping. Tests performed
include dielectric tests, which are used
to insure integrity of insulation. In
addition, Sentron Busway is tested in
accordance with both UL and IEC
standards. All Sentron Busway is
manufactured and inspected in an ISO
9001:2000 registered facility.
Standards
All Sentron Busway products meet the
following standards:
UL 857
NEMA BU1
CSA C22.2
IEC 439-1(1993), IEC 439-2 (1993),
IEC 529 (1989)
BS EN 60529
BS EN 60439-1, 60439-2
UL 1479
DIN 4102 Parts 9&12
BS 6387 Parts 11.1 and 11.2
Labor Savings
Using Sentron Busway instead of cable
and conduit can create savings of up to
20 - 30% on total installed costs. Sentron
busway is lightweight, compact and
takes half the time to install as cable and
conduit. Siemens Sentron Busway Cable/Conduit Conversion Software
Program will show you side by side
comparisons of busway vs. cable/conduit.
These comparisons include material
costs, labor costs, bill of materials, and
technical information between busway
and cable/conduit. Contact your local
Siemens sales office to find out more
information, or visit our web site at
www.sea.siemens.com.
Joint Assembly
Description
Feeder
Plug-In
IP 2X
Plug-In outlet protects against access to live parts by .472 in. (12 mm) test probe, even with cover
opened. Finger Safe
IP 40
Enclosure protects against entry of .039 in. (1.0 mm) test probe. Indoor (Typical UL Designation)
IP 55
Enclosure protects against entry of dust and water jets. Splash Proof
IP 66
Enclosure is dust tight and protects against powerful water jets. Outdoor (International Only)
NEMA 3R
Enclosure protects against rain, sleet and damage from ice formation. Outdoor - NAFTA