Tyco Window Sprinkler

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Technical Services

800-381-9312
+1-401-781-8220
www.tyco-fire.com

Model WS Specific Application Window Sprinklers


Horizontal and Pendent Vertical Sidewall
5.6 K-Factor
General
Description
The TYCO 5.6 K-Factor Model WS
Specific Application Window Sprinklers
are fast response, glass bulb-type
spray sprinklers available in Horizontal
Sidewall and Pendent Vertical Sidewall
models.
These sprinklers are the first to be
specifically Listed to provide complete
wetting and coverage for heat strengthened or tempered glass windows using
closed sprinklers. As part of the testing,
the gas flow required to achieve the
time/temperature relationship specified
in ASTM E119 was established in a test
furnace without sprinkler protection. A
window assembly protected with the
TYCO Model WS Window Sprinklers
was then installed in the test furnace,
and the same gas flow conditions were
maintained for a two-hour test period.
No cracking or visible damage to the
window was permitted during the test
period, even when a hose stream was
directed at the window.
The success of the Model WS Window
Sprinkler is based on its fast response
thermal sensitivity and on its specially
designed deflector that ensures that the
spray pattern wets the entire surface of
the window.
Based on successful testing, the
Model WS Window Sprinkler can be
used as interior protection of windows
or glazing in a sprinklered building or
non-sprinklered building in accordance
with Section 104 of the IBC (Alternate
Materials, Design and Methods of
Construction and Eqiupment). Also,
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.

Page 1 of 8

the Model WS Window Sprinkler can be


used as an open sprinkler for Outside
Sprinkler Protection against Exposure
Fire, using the design requirements of
NFPA.
As with any specific application
sprinkler, the installation instructions
included in this data sheet must be
precisely followed. If there are additional local or jurisdictional installation standards/codes for window
sprinklers on glazed window systems,
this document does not relieve the
designer/installer from these requirements. Consult your local jurisdiction to
verify if or when these additional guidelines must be followed.
NOTICE
TYCO Model WS Specific Application
Window Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
recognized by the approval agency, in
addition to the standards of any authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.
Owners are responsible for maintaining their fire protection system and
devices in proper operating condition.
The installing contractor or manufacturer should be contacted with any
questions.

Model/Sprinkler
Identification
Number (SIN)
TY3388 - Horizontal Sidewall
TY3488 - Pendent Vertical Sidewall
TY3388 is a redesignation for C3388.
TY3488 is a redesignation for C3488.

DECEMBER 2011

TFP620

TFP620
Page 2 of 8

Technical
Data

Components:
1 - Frame
2 - Button
3 - Sealing
Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *

Approvals
UL, C-UL, and ULC Listed
NYC under MEA 289-04-E
Approvals only apply to the service
conditions indicated in the Design
Criteria section.

* Temperature
rating is
indicated on
Deflector.

6*

CROSS SECTION PLAN

Additional Recognition
Ontario Building Code

THREAD
RELIEF

Pipe Thread Connection


1/2 inch NPT
Discharge Coefficient
K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2)

SPRINKLER
FRAME ARMS

INDICATED TOP
OF SPRINKLER
DEFLECTOR

1/2"
NPT

Temperature Ratings
155F (68C)

13/16"
(20,6 mm)

CENTERLINE
OF SPRINKLER
WATERWAY

200F (93C)

1-5/8" DIA.
(41,3 mm)

Finish
Polyester Coated
Chrome Plated

7/16" (11,1 mm)


NOMINAL MAKE-IN

Natural Brass

2-1/8"
(54,0 mm)

Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . Brass
Button . . . . . . . . . . . . Bronze/Copper
Sealing Assembly . . . Beryllium Nickel
with TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . Glass
(3 mm dia.)
Compression Screw Brass
Deflector . . . . . . . . . . . . Brass/Bronze

Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.

WRENCH
FLATS

ORIENT
DEFLECTOR
TOWARDS
WINDOW

SIDE ELEVATION

FIGURE 1
MODEL WS WINDOW SPRINKLER
HORIZONTAL SIDEWALL

Components:
1 - Frame
2 - Button
3 - Sealing
Assembly

4 - Bulb
5 - Compression
Screw
6 - Deflector *

* Temperature

rating is indicated
on Deflector.

1/2"
NPT

7/16" (11,1 mm)


NOMINAL MAKE-IN

1
WRENCH
FLATS

2
ORIENT
FLOW ARROW
(INDICATED ON
DEFLECTOR)
TOWARDS
WINDOW

3
4

SPRINKLER
FRAME
ARMS

2-1/8"
(54,0 mm)

5
CENTERLINE
OF SPRINKLER
WATERWAY

6*

5/8"
(15,9 mm)

TOP OF
SPRINKLER
DEFLECTOR

1-1/32"
(26,2 mm)
2-1/16"
(52,4 mm)

CROSS SECTION

TOWARDS WINDOW ELEVATION

FIGURE 2
MODEL WS WINDOW SPRINKLER
PENDENT VERTICAL SIDEWALL

TFP620
Page 3 of 8

Design Criteria
The TYCO Model WS Window
Sprinklers are UL and C-UL Listed and
NYC Approved (MEA 335-01-E) for
use as Specific Application Window
Sprinkler and as open sprinklers for
Outside use.
These sprinklers are also recognized by
Underwriters Laboratories of Canada
(ULC), and the Ontario Building Code
for use in the Province of Ontario,
Canada as providing a two-hour equivalency for a fire separation assembly
when installed in accordance with this
code.
Area of Use
When acceptable to the Authority
Having Jurisdiction and unless modified
by a local jurisdictional standard or
code mentioned previously, the TYCO
Model WS Window Sprinklers may be
used in either a sprinklered or unsprinklered building to protect non-operable
window openings that are part of a fire
separation provided:
in an interior fire separation, the
window sprinklers are installed on
both sides of the window in the fire
separation (Figure 3A-1),
in jurisdictions where exterior spatial
separation (that is, separation
from adjacent space) is defined as
protecting an adjacent building from
a fire in your building, window sprinklers are installed on the interior side
of the building (Figure 3A-2), or
in jurisdictions where exterior spatial
separation is defined as protecting
your building from a fire in an adjacent building (that is, exposure
protection), open window sprinklers
are installed on the exterior side of
the building (Figure 3A-3).

be connected by butt-joints using a


silicone sealant between the individual
panes or by Noncombustible Mullions
Refer to Figures 3B-1 and 3B-2.
Maximum Length of Window
Assembly
Unlimited
Maximum Height of Window
Assembly
13 (3,96 m)
Refer to Figures 3C and 3D.
Maximum Distance Between
Window Sprinklers
8 (2,44 m)
Refer to Figures 3B-1 and 3B-2.
Minimum Distance Between
Window Sprinklers
6 (1,83 m) unless separated by a baffle
or mullion of sufficient depth to act as
a baffle.
A mullion will act as a baffle, when
in the case of the Pendent Vertical
Sidewall, the mullion extends to the
back of the sprinkler deflector, and in
the case of the Horizontal Sidewall, the
mullion extends to the sprinkler wrench
flat.
Refer to Figures 3B-1 and 3B-2.
Minimum Distance from Standard
Sprinklers
6 (1,83 m) unless separated by a baffle
Sprinkler Location
Mullioned Glazing Assemblies:
Locate window sprinklers within each
mullioned glazing segment. Refer to
Figure 3B-1.
Butt-Jointed Glazing Assemblies:
Locate window sprinklers on
maximum 8 (2,44 m) centers. Refer
to Figure 3B-2.

Outside Exposure: Deluge

Maximum Distance from Vertical


Mullion
4 (1,22 m)
Refer to Figure 3B-1.

Glass Type
In all three cases cited below, each individual pane of the window assembly
must be at minimum 6 mm (1/4) thick.

Minimum Distance from Vertical


Mullions
4 (101,6 mm)
Refer to Figure 3B-1.

System Protection Type


Interior: Wet Systems

Non-operable, heat-strengthened,
tempered, single-glazed (single pane)
Non-operable, heat-strengthened,
tempered, double-glazed (double
pane or insulated); or,
Non-operable, stronger glass window
assemblies.
Type of Window Frame/Mullion
Non-combustible Frame with a
standard EPDM rubber gasket seal
Vertical joints of glass panes must

Intermediate Horizontal Mullions


Intermediate Horizontal Mullions were
not tested with the Model WS Window
Sprinkler. Their use is outside the
scope of the Specific Application
Listing for the window sprinklers. Refer
to Figure 3B-3.
Deflector Location
Sprinkler Deflectors must be located as
described below in order to ensure that
the entire surface of the glass window

is covered. Sprinkler Deflectors are


positioned with respect to the window
frame, not the ceiling.
Horizontal Sidewall: Locate within the
outside edge of the window frame
from 1/2 to 4 (12,7 mm to 101,6
mm) away from the glass and 2
1 (50,8 mm 25,4 mm) down from
the top of the exposed glass. Refer
to Figure 3C.
Pendent Vertical Sidewall: Locate 4
to 12 (101,6 mm to 304,8 mm) from
the face of the glass and 3 1 (76,2
mm 25,4 mm) down from the top
of exposed glass. Refer to Figure 3D.
Minimum Clearance from Face of
Glass to Combustible Materials
All combustible materials shall be kept
2 (50,8 mm) from the front face of the
glass. This can be accomplished by
a minimum 36 (914,4 mm) pony wall
or other method acceptable to the
Authority Having Jurisdiction.
Escutcheon Assemblies
The Model WS Window Sprinklers
can be used with any metallic flush or
extended escutcheons, provided the
dimensions from the sprinkler deflector
to the window frame and glass surface
as specified in this data sheet are
maintained. These sprinklers are not
listed for recessed applications.
Recommended Hydraulic
Requirements
The Authority Having Jurisdiction
should be consulted to determine
the hydraulic requirements for each
installation.
Interior Protection Sprinklered
Building
Identify which compartmented area
has the most hydraulically demanding
window sprinklers. Calculate up to the
most demanding 46.5 linear feet of
Model WS Window Sprinklers on one
side of the glazing. The 46.5 linear feet
(14,2 linear meters) is based upon 1.2
x the square root of the system area
of operation, when the system area of
operation is 1500 sq.ft. in accordance
with NFPA 13 Light/Ordinary Hazard
density curves.
Where the area of Glazing is less than
14.2 linear meters, all window sprinklers
on one side shall be calculated.
If an area reduction for quick response
sprinklers is utilized, the linear length of
the calculated window sprinklers may
be reduced, but in no case shall be less
than 36 linear feet (1.2 x 900).

TFP620
Page 4 of 8

If a single fire can be expected to


operate Model WS Window Sprinklers
and sprinklers within the design area of
a hydraulically calculated system, the
water demand of the window sprinklers
shall be added to the water demand
of the hydraulic calculations and shall
be balanced to the calculated area
demand.
If the window sprinklers are located in
an area other than the hydraulic design
area, the demand of the window sprinklers is not required to be added to
the demand of the remote hydraulic
design area. However, it is necessary
to prove hydraulically the simultaneous
operation of the Model WS Window
Sprinklers and the ceiling sprinklers
adjacent to the window sprinklers.
Interior Protection Non-Sprinklered
Building
Calculate all sprinklers on the most
demanding side of the glazing
assembly within the enclosure.
Exterior Exposure Protection
Calculate all sprinklers controlled by the
deluge valve using the design requirements of NFPA.
Duration of Water Supply
Duration of water supply must comply
with requirements of NFPA. If window
sprinklers are used to provide the
equivalency of a fire rating, the water
supply must be capable of supplying
water for the required rating period.
Minimum Flow per Sprinkler
20 GPM (75,7 LPM) for sprinkler
spacing of 6 to 8 ft. (1,83 to 2,44 m)
or 15 GPM (56,8 LPM) for sprinkler
spacing less than 6 ft, (1,83 m).
Maximum Pressure per Sprinkler
Horizontal Sidewall: 70 psi (4,83 bar)*
* The 70 psi is only for cold solder
purposes. If there is a baffle or a
mullion of sufficient depth to act as a
baffle, separating the sprinklers, the
maximum pressure is 175 psi.

When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are in an interior fire separation, the window sprinklers
are installed on both sides of the window in the fire separation.

INSIDE

INSIDE

FIGURE 3A-1 - INTERIOR FIRE SEPARATION


When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a fire separation provided in jurisdictions
where exterior spatial separation is defined as protecting an adjacent building from a fire in
your building, window sprinklers are installed on the interior side of the glass.

OUTSIDE

INSIDE
EXPOSURE
SIDE

FIGURE 3A-2 -- EXTERIOR FIRE SEPARATION - SPRINKLERS INSIDE


When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a fire separation provided in jurisdictions
where exterior spatial separation is defined as protecting your building from a fire in an
adjacent building, open window sprinklers are installed on the exterior side of the glass.

INSIDE

Vertical Sidewall: 175 psi (12,07 bar)


OUTSIDE
EXPOSURE
SIDE

FIGURE 3A-3 - EXTERIOR FIRE SEPARATION - SPRINKLERS OUTSIDE

FIGURE 3A (A-1 TO A-3)


TYPICAL NON-OPERABLE WINDOW OPENINGS

TFP620
Page 5 of 8

HORIZONTAL
OR VERTICAL
MODEL WS
SPRINKLER

6'-0" (1,83 m)
MINIMUM *

8'-0" (2,44 m)
MAXIMUM

* Minimum distance between


Window Sprinklers is 6'-0"
(1,83 m) unless separated
by a baffle or mullion of
sufficient depth to act as a
baffle.

4'-0" (1,22 m) MAXIMUM


0'-4" (101,6 mm) MINIMUM

MULLION

FIGURE 3B-1 - MULTIPLE WINDOWS SEPARATED BY MULLIONS

HORIZONTAL
OR VERTICAL
MODEL WS
SPRINKLER

6'-0" (1,83 m)
MINIMUM
Window Sprinklers are NOT
required to be located with
respect to horizontal or
vertical butt joints.

8'-0" (2,44 m)
MAXIMUM
MULLION

BUTT JOINT

4'-0" (1,22 m) MAXIMUM


0'-4" (101,6 mm) MINIMUM

FIGURE 3B-2 - MULTIPLE WINDOWS SEPARATED BY BUTT JOINTS

HORIZONTAL OR
VERTICAL MODEL
WS SPRINKLER

Window Sprinklers are NOT


listed to protect windows
when intermediate horizontal
mullions are present.

MULLION

INTERMEDIATE
MULLION

FIGURE 3B-3 - WINDOWS WITH HORIZONTAL MULLIONS

FIGURE 3B (B-1 TO B-3)


WINDOW MULLIONS AND BUTT JOINTS

TFP620
Page 6 of 8

3. With pipe-thread sealant applied to


the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.

"TOP"
INDICATED
ON SPRINKLER
DEFLECTOR

BUILDING
STRUCTURE
NO MAXIMUM
DISTANCE

WINDOW
FRAME
2" (50,8 mm)
1" (25,4 mm)

NO
MAXIMUM
HEIGHT

1/2" (12,7 mm)


TO 4" (101,6 mm)

13'-0"
(3,96 m)
MAXIMUM
EXPOSED
GLAZING
HEIGHT

NONOPERABLE
GLASS WINDOW
INSTALLATION NOTE:
SPRINKLER SHALL
BE ORIENTED WITH
FRAME ARMS ALIGNED
VERTICALLY AND MARKED
SIDE OF DEFLECTOR
FACING AND PARALLEL
TO GLAZING

ALL COMBUSTIBLE
MATERIALS SHALL BE
KEPT 2" (50,8 mm) MINIMUM
FROM SPRINKLERED FACE
OF GLAZING. THIS MAY BE
DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
"PONY WALL", OR BY
ANY OTHER METHOD
ACCEPTABLE TO THE
AUTHORITY HAVING
JURISDICTION.
MODEL WS SPRINKLER
SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY.

4. Wrench-tighten the sprinkler using


only the W-Type 20 (End A) Sprinkler
Wrench (Figure 4). Appy the W-Type
20 (End A) Sprinkler Wrench to the
Sprinkler Wrench flats only.

Care and
Maintenance
The TYCO Model WS Window
Sprinklers must be maintained and
serviced in accordance with the
following instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Exercise care to avoid damage to
sprinklers before, during, and after
installation. Never paint, plate, coat,
or otherwise alter automatic sprinklers
after they leave the factory.
Replace sprinklers that:
were modified or over-heated.
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
are leaking or exhibiting visible signs
of corrosion.

FIGURE 3C
MODEL WS HORIZONTAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION

Installation
The TYCO Model WS Window
Sprinklers must be installed in accordance with the following instructions.
NOTICE
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
Obtain a leak-tight 1/2 inch NPT
sprinkler joint by applying a minimumto-maximum torque of 7 to 14 ft.lbs.
(9,5 to 19,0 Nm). Higher levels of torque

may distort the sprinkler inlet with


consequent leakage or impairment of
the sprinkler.
1. Install the pendent vertical sidewall sprinkler only in the pendent
position with the center-line of
the sprinkler parallel to the glass
surface. Orient the sprinkler so that
the direction of flow indicated on
the sprinkler deflector is facing the
window.
2. Install the horizontal sidewall sprinkler only in the horizontal position
with the center-line of the sprinkler
perpendicular to the glass surface.
Orient the sprinkler so that the word
Top indicated on the sprinkler
deflector is facing the top of window
frame.

were exposed to corrosive products


of combustion but have not operated,
if you cannot easily remove combustion by-products with a cloth.
have a cracked Bulb or have lost
liquid from the Bulb. Refer to the
Installation section in this data sheet.
Responsibility lies with the owner for
the inspection, testing, and maintenance of their fire protection system
and devices in compliance with this
document, as well as with the applicable standards recognized by the
Approval agency (for example, NFPA
25), in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems are recommended to be inspected, tested, and
maintained by a qualified Inspection
Service in accordance with local
requirements and/or national codes.

TFP620
Page 7 of 8

CENTERLINE
OF SPRINKLER
WATERWAY

BUILDING
STRUCTURE
NO MAXIMUM
DISTANCE

FLOW DIRECTION
INDICATED ON
SPRINKLER
DEFLECTOR
NO
MAXIMUM
HEIGHT

4" (101,6 mm)


TO 12" (304,8 mm)

13'-0"
(3,96 m)
MAXIMUM
EXPOSED
GLAZING
HEIGHT

NONOPERABLE
GLASS WINDOW
INSTALLATION NOTE:
SPRINKLER SHALL
BE ORIENTED WITH
FRAME ARMS ALIGNED
PARALLEL TO GLAZING
AND DEFLECTOR FLOW
ARROW POINTED
TOWARD GLAZING

WINDOW
FRAME
3" (76,2 mm)
1" (25,4 mm)
ALL COMBUSTIBLE
MATERIALS SHALL BE
KEPT 2" (50,8 mm) MINIMUM
FROM SPRINKLERED FACE
OF GLAZING. THIS MAY BE
DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
"PONY WALL", OR BY
ANY OTHER METHOD
ACCEPTABLE TO THE
AUTHORITY HAVING
JURISDICTION.
MODEL WS SPRINKLER
SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY.

FIGURE 3D
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION

Limited
Warranty
Products manufactured by Tyco
Fire Protection Products (TFPP) are
warranted solely to the original Buyer
for ten (10) years against defects
in material and workmanship when
paid for and properly installed and
maintained under normal use and
service. This warranty will expire
ten (10) years from date of shipment
by TFPP. No warranty is given for
products or components manufactured by companies not affiliated by
ownership with TFPP or for products
and components which have been
subject to misuse, improper installation, corrosion, or which have not
been installed, maintained, modified
or repaired in accordance with applicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFPP to be defective shall be either
repaired or replaced, at TFPPs sole
option. TFPP neither assumes, nor
authorizes any person to assume for
it, any other obligation in connection
with the sale of products or parts of
products. TFPP shall not be responsible for sprinkler system design errors
or inaccurate or incomplete information supplied by Buyer or Buyers
representatives.
In no event shall TFPP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential
damages, including but not limited to
labor charges, regardless of whether
TFPP was informed about the possibility of such damages, and in no event
shall TFPPs liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of
merchantability and fitness for a particular purpose.
This limited warranty sets forth the
exclusive remedy for claims based
on failure of or defect in products,
materials or components, whether the
claim is made in contract, tort, strict
liability or any other legal theory.
This warranty will apply to the full
extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.

TFP620
Page 8 of 8

Ordering
Procedure
RECESSED
CEILING
SPACE

BUILDING
STRUCTURE

Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N). Refer to the Price List for a
complete listing of P/Ns.
Model WS HSW Window Sprinkler
with NPT Thread Connections
Specify Model WS Specific Application
Window Sprinkler TY3388, Horizontal
Sidewall, with (temperature rating),
(finish), and P/N (below).

WINDOW
FRAME

TYPICAL
WINDOW
COVERING

INSTALLATION NOTE:
VERTICAL AND
HORIZONTAL MODEL
WS SPRINKLERS
MAY BE INSTALLED
INTO RECESSED
CEILING SPACES.
BLINDS, CURTAINS
OR OTHER WINDOW
COVERINGS SHALL
NOT BE LOCATED
BETWEEN SPRINKLER
AND GLAZING.

ALL COMBUSTIBLE
MATERIALS SHALL BE
KEPT 2" (50,8 mm) MINIMUM
FROM SPRINKLERED FACE
OF GLAZING. THIS MAY BE
DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
"PONY WALL", OR BY
ANY OTHER METHOD
ACCEPTABLE TO THE
AUTHORITY HAVING
JURISDICTION.

NONOPERABLE
GLASS WINDOW

MODEL WS SPRINKLER
SHOWN ON ONE SIDE OF
GLAZING FOR CLARITY.

155F (68C)
Natural Brass P/N 50-305-1-155
155F (68C)
Chrome Plated P/N 50-305-9-155
155F (68C)
White Coated P/N 50-305-4-155
200F (93C)
Natural Brass P/N 50-305-1-200
200F (93C)
Chrome Plated P/N 50-305-9-200
200F (93C)
White Coated. . . . . . . . . . . . . . P/N 50-305-4-200

* Eastern Hemisphere sales only.

Model WS Pendent Vertical Sidewall


Window Sprinkler with NPT Thread
Connections
Specify Model WS Specific Application
Window Sprinkler TY3488, Pendent
Vertical Sidewall, with (temperature
rating), (finish), and P/N (below).
155F (68C)
Natural Brass P/N 50-304-1-155
155F (68C)
Chrome Plated P/N 50-304-9-155
155F (68C)
White Coated P/N 50-304-4-155
200F (93C)
Natural Brass P/N 50-304-1-200

FIGURE 3E
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
RECESSED CEILING TYPICAL INSTALLATION

200F (93C)
Chrome Plated P/N 50-304-9-200
200F (93C)
White Coated. . . . . . . . . . . . . . P/N 50-304-4-200

* Eastern Hemisphere sales only.

Sprinkler Wrench
Specify W-Type 20 Sprinkler Wrench,
P/N 56-000-1-106.
WRENCH RECESS
(USE END "A" FOR
MODEL WS)

FIGURE 4
W-TYPE 20 SPRINKLER
WRENCH

Copyright 2002-2011 Tyco Fire Protection Products. All rights reserved.