DHC 100

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

PEAKTRONICS

DHC-100
Digital High-Resolution Controller

The Peaktronics DHC-100 is a high performance


digital positioner intended to control AC actuators, providing 450 points of resolution with quarter turn actuators
ranging from 2 sec to 120 sec and rated for 25% duty or
more. The DHC-100 has many automatic advanced features that will enhance any actuator while making it easy to
install and set up.
The simple three button control is used to configure
all parameters the unit needs for a wide variety of applications, and allows the open and closed positions to be easily
set for direct or reversing acting without any rewiring. The
unit can be configured for various command types (420mA, 1-5V, 0-5V, 0-10V, or a digital command) and its
default operation upon loss of command.
Various option modules are easily plugged into the
unit, providing other features such as a position feedback
signal (current or voltage), auxiliary switches, fault relay
contact, or digital communications. A wide range of data is
accessible through a digital communications module, providing additional control or information.
The unit is of single solid construction and is easily
mounted with two screws. The DHC-100 is interchangeable with the AMC and LRC standard size controllers, and
can be used to upgrade performance for those applications.

117VAC
234VAC
24VAC

DHC-100
DHC-100A
DHC-100B

DHC-100C (CE ready)


DHC-100D
DHC-100E (CE ready)

FEATURES

Positions to 0.1 with quarter-turn actuators ranging from 2 sec to 120 sec (with or
without a brake).

Adaptive Control feature continuously adjusts for load and actuator conditions and
eliminates calibration procedures and auto-cal operations.

Three button control provides easy setup and eliminates the need for instrumentation.

Polarity Detection feature allows direct or reverse acting operation without re-wiring.

Electronic Brake feature can eliminate need for a mechanical brake in many applications, and extends mechanical brake life when used.

Stall Detection feature protects actuator motor from a stall condition.

Automatic Duty Cycle Control feature prevents shutdown of a process due to a thermal overload of the actuator motor, and allows actuators rated for 25% duty or more to
be safely used.

Operating temperature range of 0 to 60C

U.S. Patent 7,466,100 applies to this product

DHC-100
OUTLINE
DHC-100
DHC-100A
DHC-100B

117VAC
234VAC
24VAC

DHC-100C
DHC-100D
DHC-100E

(CE ready)

ELECTRICAL
CONNECTIONS

PEAKTRONICS
Digital High Resolution
DIGITAL

(CE ready)

AUTO

4-20mA

MANUAL / FB POT CAL

1-5VDC

CLOSE

0-5VDC

OPEN

LAST
(BOTH OFF)
MODE

AUX CLOSE OUTPUT

0-10VDC

AUX OPEN OUTPUT


COMMAND TYPE
LOSS OF COMMAND
FAULT
(FLASHING)

J1

to Motor

AUX POSITION OUT


CAL (STEADY ON)

1
2
3
4
5
6

MOTOR 1 OUTPUT
NEUTRAL
MOTOR 2 OUTPUT
GND
WIPER
+2.5V
to Feedback Pot

J2

to AC Power
L2 NEUTRAL
L1 LINE
EARTH GND

FRONT PANEL

J7

1
2
3
4
5
6
7
8

SIGNAL GND ( )
4-20mA (+)
1-5V, 0-5V, 0-10V (+)
+5V OUT
+15V OUT
to Signal

*1.32"

* Add 0.04" when option module installed.

1.36"

J1

J2

J3

1 2 3 4 5 6

1 2 3 4 5 6 7 8

OPTION MODULE
CONNECTOR

FUSE
#6 clear hole
(2) places
GND
OVERRIDE INPUT

1.36"

0.25"

J7

to Auto/Manual Station

J3

3.50"

1
2

0.25"

U.S. Patent 7,466,100 applies to this product

PEAKTRONICS

DHC-100
BLOCK DIAGRAM
J1

MOTOR 1

NOTE: See input signal


configurations for more
information.

(+) 1-5, 0-5, 0-10 V INPUT


(+) 4-20mA INPUT
SIGNAL GND

EARTH GND
L1 LINE
L2 NEUTRAL

7
6
5
4

3
2

J2
ACTUATOR

+5V OUTPUT

THERMAL SWITCH

2 NEUTRAL

POWER / SIGNAL

+15V OUTPUT

MOTOR

LIMIT SWITCH

1 OUTPUT

MOTOR 2

LIMIT SWITCH

3 OUTPUT
optional
brake
coil

4 GND

5 WIPER

FEEDBACK
POT

6 +2.5V

OVERRIDE

J7

OVERRIDE
INPUT

AUTO/MANUAL
STATION
1 GND

DHC-100

See Special Applications

DESCRIPTION
The DHC-100 is rated for motors with up to 5A
running currents and comes in three versions to accommodate different voltage applications. The DHC-100 and
DHC-100C are rated for 117 VAC 10%; the DHC-100A
and DHC-100D are rated for 234 VAC 10%, and the
DHC-100B and DHC-100E are rated for 24 VAC 10%.
The unit is easily mounted with 2 screws and is equipped
with removable screw terminals that provide for easy field
wiring. The unit's size, mounting, and screw terminals are
compatible with the AMC-100, AMC-101 and LRC-101
series controllers - the DHC-100 can be used as a direct
replacement for those units in nearly any application.
The simple three button control (MODE, , and
) allows the user to perform a complete set-up from the
PEAKTRONICS

unit itself without the need for any instrumentation. The


adaptive control feature of the DHC-100 eliminates the
need for any calibration steps. In the simplest application,
only the closed and open positions need to be set and the
unit automatically and continuously sets all other parameters when placed in the AUTO mode.
CAUTION ! These units are intended to be
mounted in an appropriate enclosure to avoid electrical
shocks and exposure to electrostatic charges. High voltages are present on the outside of the unit when power is
applied. AC power should be disconnected and antistatic
measures should be taken prior to any wiring of these
units. A heater and thermostat should be used where condensation may occur.

U.S. Patent 7,466,100 applies to this product

DHC-100
tion of the DHC-100 and must be installed if the external
override functions are not used.

POWER / SIGNAL (J2)


Power is connected to pins 1, 2, and 3 as shown in
the block diagram. The fuse installed on the unit is rated
for maximum output current that can be safely delivered
by the AC outputs. Replacement fuses must not exceed
the maximum rating to prevent damage to the unit.
Smaller fuse sizes can be used with smaller motors - consult the actuator manufacturer for appropriate fuse size
and type.
An appropriate command signal, either 0-5V, 010V, 1-5V, or 4-20mA, should be connected to pin 5 or 6
(as shown in the Block Diagram) while using pin 4 as the
return signal ground. The DHC-100 must be configured
for the type of command signal that is to be used (see
COMMAND TYPE).
Pin 7 of J2 provides an auxiliary +5V output
which can be used to connect a command potentiometer.
By connecting one end of a potentiometer to pin 7, the
other end to pin 4, and the wiper to pin 6, a local control
knob can be implemented. Pin 8 provides an auxiliary
+15VDC output which can be used to power an input or
output 4-20mA transmitter.

ACTUATOR (J1)

The MODE button is used to select the desired


function of operation. When the MODE button is pressed,
the unit will switch to the next function and the appropriate LED indicator will turn on to let the user know which
function is selected. Except for the MANUAL/FB POT
CAL mode, the associated mode indicator will be steady
on; for some of the modes other indicators will flash to
indicate specific settings associated with the mode. Each
of the modes are described in more detail in the following
sections.
If a 0-5V or 0-10V command signal is used, the
LOSS OF COMMAND function cannot be used. The
MODE button will skip over the LOSS OF COMMAND
mode when the unit is configured for a 0-5V or 0-10V
command signal (see COMMAND TYPE). When the
OVERRIDE mode is enabled (see OVERRIDE MODE),
the MODE button is disabled and the Manual/Pot Cal indicator will turn on steady.

ADJUST UP () and ADJUST DOWN ()

The actuator motor and feedback potentiometer


are connected to J1 as shown in the Block Diagram. The
Motor Neutral wire must be connected to pin 2, while one
motor winding is connected to pin 1 and the other winding
to pin 3. The feedback potentiometer wiper must be connected to pin 5, while one end is connected to pin 4 and
the other end to pin 6. The Polarity Detection feature of
the DHC-100 automatically determines which motor
winding to control based on where the open and closed
positions are set; this feature also eliminates the need to
rewire the unit for direct or reverse acting applications.
When the and buttons are used to control
the actuator, the button will turn on the motor winding
connected to pin 1, while the button will turn on the
motor winding connected to pin 3. See MANUAL/FB
POT CAL for more details.

OVERRIDE (J7)
J7 provides a simple 2-wire connection that can
override the DHC-100 to perform a variety of external
control functions. Using an appropriate interface module,
commonly used auto/manual station switches are easily
implemented with low voltage/low current switches. See
Special Applications for more details. The factory installed jumper between pins 1 and 2 enables normal opera4

MODE

The adjust up () and adjust down () buttons


are used to adjust the setting of any given function. When
a function is selected by the MODE button, the adjust buttons will affect that function only. Note, that the AUTO
mode does not have any adjustable settings, and therefore,
the adjust up () and adjust down () buttons have no
effect. Also, the adjust buttons are disabled in the
OVERRIDE mode.

OVERRIDE MODE
The OVERRIDE mode is not selected by the
MODE button and can be enabled at anytime by connecting a resistance greater than 250 ohms to the Override Input (J7 pin 1 and pin 2). While the OVERRIDE mode is
enabled, the MODE button and adjust buttons are disabled, and the Manual/Pot Cal indicator will turn on
steady to indicate that the unit is being controlled by the
Override Input. Shorting J7 pin 1 to pin 2 returns the unit
to normal operation and the previously selected mode.
Note that earlier models may not have connector J7, and
therefore do not have the OVERRIDE mode feature.
Controlling the DHC-100 from the Override Input
is accomplished by connecting a specific resistance to select a specific operation. The table below defines the op-

U.S. Patent 7,466,100 applies to this product

PEAKTRONICS

DHC-100
erations and their associated resistance. See Special Applications for details on using the Override Input for an
Auto/Manual Station.
RESISTANCE

> 4.3K ohms


3.3K ohms
2K ohms
1.2K ohms
510 ohms

5%
5%
5%
5%

OPERATION

OFF
LATCH
OPEN
CLOSE
STOP

The OPEN function will operate the motor in the


open direction as set by the OPEN mode, while the
CLOSE function operates the motor in the closed direction
as set by the CLOSE mode. The LATCH function will
maintain the previously selected function; this allows
momentary switches to be used for the OPEN and CLOSE
functions. The OFF and STOP functions turn the motor
off, which also unlatches the OPEN or CLOSE functions.
Note that the OPEN and CLOSE functions may
work in reverse until the open and closed positions are set
by the OPEN and CLOSE modes. The DHC-100 will automatically turn the motor off when the open or closed
positions are reached. However, if a feedback fault occurs
(see FAULT INDICATOR), the motor will be turned on
for a period of 15 minutes in the selected direction. For
this reason, limit switches should be used when using the
OVERRIDE mode, and should be set to a position acceptable for the application. The 15 minute period can also be
terminated using the OFF or STOP function.
The motor is also automatically turned off if the
DHC-100 detects a stall (see STALL DETECTION). An
OPEN or CLOSE operation can be attempted again after
switching to the OFF, LATCH, or STOP functions first.

AUTO
The AUTO function is the normal mode of operation for the DHC-100; all the other functions are used to
set up the unit. While in AUTO, the unit can be controlled
by various external signals, some of which can be selected
by the COMMAND INPUT function. When the unit is
not in the AUTO mode, all external controls described
below will be disabled.
Once the open and closed positions have been set,
the AUTO mode will control the position of the actuator
according to the command input signal. For an input signal of 0V (for 0-5V or 0-10V input), 1V (for 1-5V input),
4.0 mA (for 4-20mA input), or 0% (for a digital input), the
DHC-100 will position the actuator to the closed position
as set by the user. Conversely, an input of 10V, 5V,
20mA, or 100% will position the actuator to the defined
open position.
PEAKTRONICS

When the DHC-100 is configured to use a 0-5V,


0-10V, 1-5V, or 4-20mA command, the command signal
should be connected to the appropriate pin on J2 - note
that the unused input pin must be left unconnected. When
the DHC-100 is configured for a Digital command type,
an appropriate communications option module must be
installed. A communications module may be installed
when using one of the analog command types and can be
used to override the analog command. The AUTO indicator will flash whenever the unit is being controlled by the
communications module.

MANUAL/FB POT CAL


The MANUAL/FB POT CAL function allows
manual operation of the actuator by using the adjust buttons ( and ) without affecting any other settings within the DHC-100. When the button is pressed, the motor winding connected to J1-1 is turned on while the
button turns on the J1-3 winding. Whether the actuator
moves toward the open or closed position depends on
which motor winding is connected to J1-1 and J1-3.
The POT CAL feature provides an indication of
the feedback potentiometer's setting. When the MANUAL/POT CAL function is selected, the Manual/Pot Cal
indicator will turn on - it may flash or be on steady, depending on the actuator position. The indicator will be on
steady whenever the DHC-100 detects that the feedback
potentiometer is at midrange of its rotation. As the actuator moves, causing the feedback potentiometer to move
away from midrange, the indicator will begin to flash, and
the indicator will flash at a decreasingly slower rate as the
actuator moves further away from midrange.
By using the adjust buttons to position the actuator to midstroke (half way point between the desired open
and closed positions), the feedback potentiometer can then
be adjusted until a steady light occurs. This insures that
the feedback potentiometer has maximum range to reach
the open and closed positions.

CLOSE
The CLOSE function is used to set the desired
closed position; however, prior to doing this, the feedback
potentiometer should be checked for optimum position
(see MANUAL/POT CAL), and the limit switches should
be set outside of the operating range (see STALL DETECTION FEATURE). In the CLOSE function, the adjust buttons are used to set the actuator to any desired position, and upon pressing the MODE button (to select the
next function, OPEN), the DHC-100 will retain the setting
as the defined closed position.

U.S. Patent 7,466,100 applies to this product

DHC-100
Upon selecting the CLOSE function, the DHC100 will begin moving the actuator to the previously set
closed position; it is not necessary to make an adjustment
if the unit has been previously set to the desired position.
A command signal input of 0V, 1V, 4mA, or 0% automatically corresponds to the defined closed position.

OPEN
The OPEN function works the same way as the
CLOSE function with the exception that the adjust buttons
are used to set the desired open position. As with the
CLOSE function, upon selecting the OPEN function, the
actuator will move to the previously set open position.
Once the desired position is set, the DHC-100 will automatically correspond a command signal input of 10V, 5V,
20mA, or 100% to the open position.

COMMAND TYPE
The COMMAND TYPE function is used to configure the command signal input for either 4-20mA, 1-5V,
0-5V, 0-10V, or digital so as to match the type of command signal being used. Upon selecting the COMMAND
TYPE function, the Command Input indicator will turn on
steady, while the indicator for the selected type will flash.
Use the adjust buttons ( or ) to select the desired input
type. The selection will be saved when the MODE button
is pressed, which will also advance the unit to the LOSS
OF COMMAND function.

LOSS OF COMMAND

AUX CLOSE OUTPUT


The AUX CLOSE OUTPUT function is used to
set an optional output setting that is associated with the
closed position - an appropriate relay option module is
required to use this output. The adjust buttons are used to
set the actuator to a desired position. Whenever the actuator position falls between the defined closed position and
the Aux Close position, the Aux Close Output indicator
will flash. Additionally, the DHC-100 will turn on a relay
output on the optional relay module - the output can be
used to drive an alarm or merely act as an auxiliary limit
switch.
Upon selecting the AUX CLOSE OUTPUT function, the DHC-100 will begin moving the actuator to the
previously set position. It is not necessary to make an adjustment if the unit has been previously set to the desired
position.

AUX OPEN OUTPUT


The AUX OPEN OUTPUT function is used to set
an optional output setting that is associated with the open
position - an appropriate relay option module is required
to use this output. The adjust buttons are used to set the
actuator to a desired position. Whenever the actuator position falls between the defined open position and the Aux
Open position, the Aux Open Output indicator will flash.
Additionally, the DHC-100 will turn on a relay output on
the optional relay module - the output can be used to drive
an alarm or merely act as an auxiliary limit switch.
Upon selecting the AUX OPEN OUTPUT function, the DHC-100 will begin moving the actuator to the
6

previously set position. It is not necessary to make an adjustment if the unit has been previously set to the desired
position.

When using 1-5V, 4-20mA, or a Digital input type


for the command signal, the DHC-100 will detect when
the command signal is lost or out of range. A loss of command condition is detected whenever the input is disconnected, the input becomes less than 0.75V or 3mA, or the
input becomes greater than 5.25V or 21mA. If the DHC100 detects a loss of the command signal, the Fault indicator will flash and the actuator will be moved to one of
three preset positions: the open position, the closed position, or the position last attained prior to losing the command signal. The LOSS OF COMMAND function is used
to set the desired default position.
When the LOSS OF COMMAND function is selected, the adjust buttons are used to set the default position. The DHC-100 indicates the selected default setting
by flashing the Open function indicator for the open default position, or it will flash the Close function indicator
for the closed default position. When neither indicator is
on, then the "last position" default is selected.
When a 0-5V or 0-10V command signal is used, a
loss of command signal cannot be detected. Therefore, if
the unit is configured for a 0-5V or 0-10V command signal (see COMMAND INPUT), the MODE button will not
select the LOSS OF COMMAND function.

AUX POSITION OUT CAL


Note that the AUX POSITION OUT CAL indicator also serves as a Fault indicator. When the indicator is
on steady, the AUX POSITION OUT CAL function is
selected. When the indicator flashes, a Fault condition has
been detected (see FAULT INDICATOR for details). The

U.S. Patent 7,466,100 applies to this product

PEAKTRONICS

DHC-100
AUX POSITION OUT CAL function is used to calibrate
an optional feedback transmitter output. An appropriate
transmitter option module is required to use this feature.
When the AUX POSITION OUT CAL function is
first selected (by pressing the MODE button while in the
LOSS OF COMMAND function), the CLOSE indicator
will flash, and the voltage or current associated with the
closed position will appear at the option module output. If
desired, the output can be adjusted (using the adjust buttons) to any value from 0 to 10V (for a voltage output) or
0 to 20mA (for a current output). The new setting is then
associated with the closed position.
Pressing the MODE button again will leave the
unit in the AUX POSITION OUT CAL function except
that the OPEN indicator will flash, and the output voltage
or current associated with the open position will appear at
the option module output. Like the closed setting, the
output can be adjusted to any voltage (from 0 to 10V) or
current (from 0 to 20mA), and the new setting is then associated with the open position.

output only, and the fault is cleared when the DHC-100


detects a motion greater than 1.5 in either direction. The
fault can be cleared if 1) the command signal commands a
Motor 2 operation, 2) manual operation with the adjust
buttons results in a motion greater than 1.5, or 3) a mechanical manual override forces the 1.5 motion, provided
the mechanical motion is monitored by the feedback pot.
MOTOR 2 STALL - A fault is detected when no actuator
motion is detected while the Motor 2 output is turned on.
The fault can be cleared in the same manner as a Motor 1
Stall (see above).
DOUBLE STALL - If the DHC-100 detects no actuator
motion in either direction, both motor outputs will be disabled. The command signal cannot clear this condition;
only manual operation or a mechanical override can clear
the fault. Alternatively, the DHC-100 can be powered off
and then on to temporarily clear the fault; however, this
practice should be avoided without permanently correcting
the cause of such a fault.

FAULT INDICATOR
The DHC-100 detects various fault conditions that
prohibit the unit from controlling the actuator. When any
of these conditions are detected, the Fault indicator will
flash, and the motor outputs are turned off until all fault
conditions have been corrected. If an appropriate relay
option module is installed, the Fault relay output on the
option module will also turn off. A communications option module can read the specific condition(s) causing the
fault. Note that a fault condition DOES NOT disable the
motor outputs when manually controlling the actuator
with the the adjust buttons; while useful for troubleshooting, care should be excercised when operating the motor
under a fault condition. The OVERRIDE mode can also
operate the motor when a fault condition exists - see
OVERRIDE MODE for details. The various fault conditions are described below:
LOSS OF COMMAND - If the command signal is disconnected or out of range, the fault indicator will remain
on until the signal is reconnected or back in range.
FEEDBACK POT FAULT - A fault condition is detected
whenever the feedback signal is out of range (that is, less
than 5% of the potentiometer value or more than 95% of
the potentiometer value), or when any of the potentiometer connections are broken. Normal operation resumes
when the potentiometer is reconnected or back in range.
MOTOR 1 STALL - A fault condition is detected when no
actuator motion is detected while the Motor 1 output is
turned on. The fault condition will disable the Motor 1
PEAKTRONICS

STALL DETECTION FEATURE


The Stall Detection feature of the DHC-100 (see
FAULT INDICATOR) essentially performs a similar
function as commonly used torque switches; however, the
differences should be considered before eliminating the
torque switches. The DHC-100 feature does not measure
torque, but rather motion; if the load is sensitive to excessive torque, the torque switches may be desirable. Since
common torque switches are mechanical devices, they can
provide a fail safe feature in the event of electrical failures
(such as shorted wires or damage to the DHC-100).
The Stall Detection feature is useful for detecting
when any of the motor wires become disconnected. However, limit switches employed in actuators essentially disconnect one of the motor windings. The DHC-100 will
detect this as a motor stall. To avoid this condition, the
limit switches must be set outside of the operating range
set by the CLOSE and OPEN functions.

ELECTRONIC BRAKE FEATURE


The Electronic Brake feature of the DHC-100
provides highly reliable and accurate braking of the motor,
and it is a key element in achieving high resolution. A
mechanical brake can still be implemented without interfering with the DHC-100 operation. Mechanical brakes
can be useful for providing a holding brake in the event
power to the actuator is lost.

U.S. Patent 7,466,100 applies to this product

DHC-100
Since the Electronic Brake feature provides the
primary braking of the motor, the life of a mechanical
brake is dramatically extended. Additonally, the Adaptive Control feature of the DHC-100 automatically compensates for changes in a mechanical brake's performance
due to temperature or age.
Note that the actuator's limit switches should be
set outside of the operating range set by the CLOSE and
OPEN functions. The Electronic Brake feature degrades
in performance if a limit switch is engaged. Limit switches exhibit wide variations, and the DHC-100 can position
the actuator more precisely at closed and open than the
limit switches. A limit switch serves better as a fail safe
device to protect against electrical failures in the actuator.

DUTY CYCLE CONTROL FEATURE


The Duty Cycle Control feature of the DHC-100
allows actuators rated at 25% duty or more to be safely
used in automated valve applications. The DHC-100 ac-

curately monitors the relative heating of the motor and


automatically duty cycles the unit at a safe level when a
process becomes unstable, or if a control loop is not properly set. While the thermal switch in the motor protects
the motor from overheating, thermal switches can shutdown the actuator for ten minutes or more. Further, typical thermal switches do not activate until temperatures
inside the actuator become too high for other components
in the actuator.
The Duty Cycle Control feature allows continuous operation of the motor until it detects an excess heat
build up in the motor (usually well below the limit of the
thermal switch). At that time, duty cycle operation is automatically enabled and continues until the motor cools
enough to resume continuous operation. The duty cycle
period is approximately 2 seconds with an on time that
automatically varies depending on the heating of the motor. While this operation slows down the actuator's operation, it does not impact the resolution performance of the
DHC-100, and it prevents disruption of a process due to a
thermal switch shutdown.

OPTION MODULES
Various option modules can be plugged into the
DHC-100 option module connector, J3. Option modules
provide additional features such as position feedback signals, auxiliary switch outputs, or digital communications.
Plug option module into J3,
lock module in front panel
slots, and retighten front
panel screws.

Contact the factory for the latest available modules. Refer


to the diagram below for instructions on installing an option module.

Loosen front panel screws and lift front panel up to


allow option module to plug in underneath.

Option
Module

J3

DHC Series
Installing an Option Module

U.S. Patent 7,466,100 applies to this product

PEAKTRONICS

DHC-100
SPECIFICATIONS
POWER REQUIREMENTS
DHC-100, DHC-100C: 117VAC 10%, 50/60 Hz
DHC-100A, DHC-100D: 234VAC 10%, 50/60 Hz
DHC-100B, DHC-100E: 24VAC 10%, 50/60 Hz
12 VA typical (not including output load)
Fuse Type: 6.3A TR5 Time Delay (replaceable)

COMMAND SIGNAL INPUT


Input Impedance
20K ohms (1-5 VDC, 0-5 VDC, 0-10 VDC Input)
251 ohms 1% (4-20 mA Input)
Loss of Command threshold
< 0.75V or > 5.5V (1-5 VDC input)
< 3mA or > 22mA (4-20mA input)

FEEDBACK SIGNAL INPUT


Input Voltage: 0 to 2.5 VDC
External Feedback Potentiometer: 1K ohm

POWER SUPPLY OUTPUTS


+15V OUT (J2-8): 125mA maximum (not including option module)
+5V OUT (J2-7): 5mA maximum
NOTE: Do not connect these outputs to other power supplies.

AC MOTOR OUTPUTS
Off-state Leakage Current: <15mA
Maximum Load Current @ 60C: 5A

ENVIRONMENTAL
Operating Temperature Range: 0 C to 60 C
Storage Temperature Range: -40 C to 85 C
Relative Humidity Range: 0 to 90 % (noncondensing)

CE CERTIFICATION (DHC-100D only)


EN55011, Class A RF Emission
EN61000-4-2 Electrostatic Discharge (ESD)
EN61000-4-3 Radiated RF Immunity (10V/m)*
EN61000-4-4 Electrical Fast Transient (EFT)
EN61000-4-5 Surge Pulse (Class 3 with less than 10m cable)
EN61000-4-6 Conducted RF Immunity (3V)
EN61000-4-11 Brown Out / Black Out
Peaktronics reference document: 1001-6A
* The unit exhibits a particular sensitivity at 137MHz. Installations suspected of having a strong exposure near the specified limit in the range of 132Mhz to 142Mhz can increase immunity by installing a clamp-on ferrite (250 ohms or more at 100MHz) around the I/O cable(s). A Steward 28A20290A2 ferrite or equivalent is recommended.

PEAKTRONICS

U.S. Patent 7,466,100 applies to this product

DHC-100
WIRING DIAGRAMS
Input Signal Configurations

J2-6
1-5V, 0-5V, 0-10V

DHC-100

1-5V
0-5V
or
0-10V
DAC

DHC-100

J2-5
4-20mA
4-20mA
J2-4
SIGNAL GND

J2-4
SIGNAL GND

Sourcing
or
Sinking
output

4-20mA Input using a self powered transmitter

1-5/0-5/0-10V Input using digital-to-analog card

MLT-100A
(includes dial and knob)

XMA-104A

XMA-108

J2-8
+15V
OUT

J2-8
+15V OUT

CW
4-20mA WHT
Transmitter
Command
Pot

OPEN
4-20mA
Transmitter

DHC-100

DHC-100
135 ohm
Slide
Wire

J2-5
4-20mA

J2-5
4-20mA

135 ohm Slide Wire


using the 4-20mA Input Signal

10

RED

BLK

Remote Command Pot


using the 4-20mA Input Signal

U.S. Patent 7,466,100 applies to this product

PEAKTRONICS

DHC-100
WIRING DIAGRAMS
Special Applications

DHC-100
J3

OTR-100
OTX-100
(Option Module)

Voltage Feedback Monitor

7 Voltage Output
6 mA Output
mA Feedback Monitor

5 GND
4 AUX Close Output
3 AUX Open Output
2 Fault Output

OTR-100 only

1 Common

NOTE: The Fault Output contact will


open when power is lost or when a
fault condition exists.

Connecting a position feedback transmitter

Mechanical
Manual Override
Switch
J7-2

Manual
Override
Normal
Operation

DHC
Series
J7-1

Connecting a mechanical manual override switch

PEAKTRONICS

U.S. Patent 7,466,100 applies to this product

11

DHC-100
WIRING DIAGRAMS
Special Applications (continued)

DHC
Series

MECHANICAL
MANUAL OVERRIDE
SWITCH
(optional)

USING
MOMENTARY
SWITCHES

AMM-100
1

STOP
(optional)

J7-1

DHC
Series

MECHANICAL
MANUAL OVERRIDE
SWITCH
(optional)

OPEN

OFF (optional)
MANUAL

CLOSE

STOP
(optional)

AUTO

J7-2

AMM-100
1

J7-1

USING
TOGGLE
SWITCHES

OFF
AUTO

J7-2

Connect for latching function.


Note, one STOP switch will
be required.

CLOSE

OPEN

OFF (optional)
MANUAL

Connecting an auto/manual station

www.peaktronics.com
PEAKTRONICS, Inc. 1363 Anderson

Clawson, MI 48017

Phone (248) 542-5640

FAX (248) 542-5643

800-128H