KTS Catalogue 2010/2011

Cable support systems

Welcome to Customer Service

Service telephone: +49 (0)2373 89-1500

Telefax for enquiries: +49 (0)2373 89-7777


Telefax for orders: +49 (0)2373 89-7755
E-mail: info@obo.de

Use the direct line to OBO Customer Service! On the Service Hotline +49 (0)2373 89-1500, we are
available every day from 7.30
a.m.to 5.00 p.m.for any questions
about the OBO product range for
electrical installations. The newly
structured OBO Customer Services can offer you the full works:

OBO

KTS

Competent contacts from your


region
All the information on the OBO
product range
Knowledgeable advice on special application topics

Quick, direct access to all the


technical data of the OBO products we also want to provide the best in customer relations!

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Internet: www.obo.de

Contents

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid

Mounting systems

139

Fastening systems

185

Cable tray systems

197

Cable tray systems, walk-on

234

Mesh cable tray systems

243

Cable ladder systems

261

Wide span systems

279

Vertical ladder systems

299

Luminaire support systems

317

Modular systems

325

Stainless steel systems V2A

333

Stainless steel systems V4A

379

Directories

397

KTS

OBO

OBO

KTS

Invitations to tender, product information and datasheets


We can make life easier for you,
with our comprehensive selection
of materials designed for practical
applications, which provide you
with effective support with the
planning and calculation of a project. These include:
Invitations to tender
Product information
Information sheets
Datasheets
These documents are continually
updated and can be downloaded
at no charge at any time from the
Internet download area at
www.obo.de.

Invitations to tender on the Internet at www.ausschreiben.de


More than 10,000 entries from the
KTS, BSS, TBS, LFS, EGS and
UFS ranges can be called up free
of charge. Regular updates and
extensions mean that you always
have a comprehensive overview of
the OBO products. All the current
file formats PDF, DOC, GAEB,
HTML, TEXT, XML, NORM are
available.
www.ausschreiben.de

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

OBO KTS seminars: First-hand


knowledge
With a comprehensive range of
training courses and seminars on
cable support systems, OBO is
able to provide users with firsthand support. Alongside the basic
theoretical principles, the programme also deals with practical
implementation in everyday applications. Special calculation and
application examples round off the
comprehensive programme of
knowledge transfer.

Contents of planning and mounting aids

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

General planning aid

Mounting systems

35

Fastening systems

57

RKSM cable tray systems

63

Walk-on cable tray system

79

Mesh cable tray systems

85

Cable ladder systems

97

Wide span systems

103

Vertical ladder systems

111

Luminaire support systems

117

Modular systems

123

Stainless steel systems

129

Additional information

132

KTS

OBO


With the AutoCAD-based OBO
Construct KTS software, OBO
can offer planners, installation
engineers and architects completely new options for the planning of cable support systems.

Besides the targeted assistance in


the selection of the optimal cable
support system, OBO Construct
KTS provides information for the
planning of cable route projects
using the integrated Route Editor,
and in the integration of function maintenance systems according to DIN 4102, Part 12.

A detailed parts list, created according to the user's specifications, provides a clear overview of
the material quantities required
and theirgross prices.
Software highlights:
Insertion of the cable routes
(individually or using the program)
Calculation of the usable
cross-section with the option of
specifying any number of cable assignmentsmanually
Automatic calculation of the
load of standard support structures
Menu-controlled KTS article selection integrated into the program

OBO

KTS

Generation of detailed parts


lists and transfer to a price enquiry in Microsoft Excel
Integrated functionmaintenance systems
Automatic labelling function
Simple insertion and editing of
fittings
Language variants: German,
English, French, Czech. This
selection is continually being
expanded.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

OBO Construct KTS: Project planning, drawing, generation

Planning aid, general


information
04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Besides the OBO Construct KTS


planning software, on the website,
you can download the useful, independent Cable Filling tool to enable you to select the optimum cable support system and also calculate the cable routing and the filling factor.

desk Incorporation, USA.

Technical note:
The OBO Construct KTS software
can either be ordered directly from
OBO or downloaded from the website at www.obo.de. Please note:
AutoCAD (version from 2006 to
2010) is required (full version or
LT version). The software can be
used in full for test purposes for a
period of 14 days. When the testing period has elapsed, the software is automatically deactivated.
You will need to register if you
wish to continue using the program. Registration costs 80 euros.
Microsoft Windows and Excel are
registered trademarks of the Microsoft Corporation, USA. AutoCAD
is a registered trademark of Auto-

KTS

OBO

Standardised work offers protection


OBO offers cable support systems made by professionals for
professionals: The technical properties are guaranteed by DIN EN
61537 (follow-up to DIN VDE
0639). It describes all the relevant
parameters from the area of application, through test conditions,
up to corrosion resistance and
temperature classification. As a
competent manufacturer of cable
support systems, OBO subjects itself to these requirements on a
daily basis. The tests described
below guarantee the use of systems which fulfil the requirements
of the systems.

Suitable protective clothing is required for safe handling during


transport and processing.

CE-conformant
All products in this catalogue are
CE-compliant in accordance with
the appropriate EC directives. This
also applies to standard parts
such as bolts, washers and nuts
that are components of various
product systems. The appropriate
EC declaration of conformity certifies agreement with the named directives or standards, but does

OBO

KTS

notguarantee properties. The safety instructions in the supplied product information and the general
safety regulations must be complied with during installation and
use.
Testing, equipotential bonding/protective conductor
Cable support systems must possess sufficient conductivity. Only
this can ensure that the equipotential bonding and the connection to
the earth potential is sufficient. A
reduction in conductivity is often
the result of contact resistances at
joints.
To keep these contact resistances
to a minimum on the OBO cable
support systems, during the development process we placed great
emphasis on a stable connection,
which is free of contact resistance.
Of course, the developed systems
were tested in the BET laboratory.
In this catalogue, the tested articles are marked with the
test marks shown below. You can
request the appropriate test reports at any time via our hotline.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Standards, regulations and tests

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Inclusion of the protective measures

Load tests for cable support systems


All the OBO articles and systems
are subjected to practical load testing. The basic principles for the
tests of OBO cable support systems are included in DIN EN
61537 and DIN VDE 0639. After
the load test, the maximum load
capacity can be determined for
each component, depending on
the support distances and specific
article parameters, such as component dimensions. This is all
shown in a chart, included with
each component.
You can find additional information
on the load tests for cable trays,
brackets and suspended supports
in this catalogue. The valuesgiven
do not take resistance against environmental forces such as snow,
wind and other outside influences
into account.

KTS

OBO

In recent years, the use of electronic circuits has increased continually. Whether in industrial
systems, medicine, households,
in telecommunications systems
or electrical building installations
everywhere, we see powerful
electric equipment and systems,
which switch ever greater currents, achieve greater radio ranges and transport ever more energy in smaller spaces.

However, the use of state-of-the-art


technology means that the complexity of applications also increases. The consequence of this is that
evermore opposing influences (electromagnetic interference) can
occur from system parts and cables, causing damage and economic losses.

unit to function satisfactorily in its


electromagnetic environment, without inappropriately influencing this
environment, to which other units
also belong (VDE 0870-1). In
terms of standardisation, electromagnetic compatibility is dealt with
by
the
EMC
directive
2004/108/EC. This means that
electrical resources emit electromagnetic interferences (emission),
which are picked up by other devices or units (immission) which act
as receivers (interference sink).
Thismeans that the function of an
interference sink can be severely
reduced, meaning, in the worst
case, total failure and economic
losses. The interferences can
spread along cables or in the form
of electromagnetic waves.

Here, we talk of electromagnetic


compatibility.
Electromagnetic
compatibility
(EMC) is the ability of an electrical

Path of faults
Fault source (transmitting emissions)

Coupling of interference variables


(spreading of interference)

Fault sink (receiving emissions)

For example
- Mobile telephones
- Switching components
- Ignition systems
- Frequency converters
- Lighting strike
- Welding devices

10

OBO

KTS

Galvanic
Inductive
Capacitive
Electromagnetic

Process computer
Radio receiver systems
Controllers
Converters
Measuring units

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Definition of electromagnetic compatibility (EMC)

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Guarantee of EMC

Guarantee of EMC
A systematic planning process is
necessary to guarantee EMC. The
interference sourcesmust be identified and quantified. The coupling
describes the spread of the interference from the interference
source up to the influenced device, the interference sink. The
task of EMC planning is to ensure
the compatibility at the source,
coupling path and sink using suitable measures. During their daily
work, planners and installation engineers are confronted with this
subject on an increasingly regular
basis. This means that EMC is a
basic factor to be taken into consideration during the planning of
installations and cabling systems.
Due to the high complexity of electromagnetic
compatibility,
the
problems of EMC must be analysed and solved using simplifying
hypotheses andmodels as well as
experiments andmeasurements.
Cable support systems and their
contribution to EMC
Cable support systems can make
an important contribution to the improvement of EMC. They are passive and can thus make a safe,
long-lasting contribution to EMC
through the fact that cables are
run within cable support systems
or are shielded by them. Routing
cables inside cable support systems greatly reduces the galvanic

decoupling and coupling due to


electrical and magnetic fields in
the cables. Thus cable support
systems can make a contribution
to the reduction of coupling from
the source to the sink. The shielding action of cable support systems can be quantified by the
coupling resistance and the shield
attenuation. Thisgives the planner
important engineering parameters
for cable support systems for the
EMC engineering.
Lightning discharge
From the analysis of the effectiveness of EMC in buildings (EN
62305-4), we know that lightning
discharge is one of the greatest
sources of interference to be expected. This causes a direct current feed into the entire equipotential bonding system in the building
and/or to magnetic decoupling of
interference currents in electrical
cables. With regard to these couplings, cable support systems can
offer an effective contribution to
the reduction of interference voltages.

KTS

OBO

11

Themagnetic field (H) of strength 3 kA/m in a defined experimental setup: without cable support
system on the left, with cable support system on the right. 1 = Field H, 2 = V1 LzuPE

The magnetic shield insulation of


cable support systems is the ratio
in decibels (dB) of an induced voltage into an unprotected cable to
the induced voltage into the same
cable, when this is in a cable support system.
Experimental structure to determine the magnetic shield insulation of cable support systems:
An unshielded cable (NYM-J
5x6 mm) is subjected to an
8/20magnetic field with a strength
of 3 kA/m. Here, the induced voltage V1 is measured in the unshielded cable. The same cable is
then positioned in the centre of a
cable support system (once with a

cover, once without) and subjected


to the same magnetic field of 3
kA/m. Here, the induced voltage
V2 is measured in the unshielded
cable.
The magnetic shield insulation is
calculated from the measured values according to the formula:
S = 20 log (V1/V2) dB

was achieved with cable support


systems (cable trays) with covers.
Please refer to the information for
the individual products to find the
averagemeasured values.
Note:
The shield insulation against electrical fields is almost perfect, like a
Faraday cage.

Experiment result:
The magnetic shield effect S of a
cable support system could be
clearly proved by the experiments
and the simulation with an
FEMprogram.
The best result of around 50 dB

Magnetic shield insulation 8/20 dB


Type, cable tray/cable ladder

Without cover

With cover

RKSM 630 FS

20

50

MKS 630 FS

20

50

MKS 630 FT

20

50

MKSU 630 FS

20

50

MKSU 630 FT

20

50

MKSU 630 VA

20

50

GRM 55/300 FS

15

25

LG 630 NS FT

10

15

12

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Magnetic shield insulation of cable support systems

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Transfer impedance of cable support systems

Experimental structure for transfer impedance: 1 = Length l, 2 = U, 3 = I, 4 = Pulse source 8/20

VInterference: Interference voltagemeasured in cable


IInterference: Interference current, fed into the shied
from outside (KTS)
L : Length of the cable support system

Transfer impedance (coupling resistance) of cable support systems


The transfer impedance of a cable
support system is the ratio of
the measured voltage VInterfer,measured in the lengthwise dience
rection within the cable support
system, to the coupled current IIn.
terference
The transfer impedance is determined in the same way as with
the measurement of the electrical
conductivity properties in Chapter
11.1. (DIN EN 61537).
If there is a lightning strike in a
building, partial currents will flow
through the entire equipotential
bonding system.
Installed cables are best run within
a cable support system. Installed

Experiment result:
The effect of the cable support
against galvanic coupling was
clearly proved by the experiments!
The best result was achieved with
cable support systems (cable
trays) with covers. Please refer to
the information for the individual
products to find the averagemeasured values.

cable support systems are always


included in the equipotential bonding system. In so doing, the partial
current flows via the cable support
system. A very small component
can therefore still flow along the
cables laid within the cable support system. This component is
determined by the transfer impedance of the cable support system.
The following applies for the transfer impedance: ZT = VInterfer/(IInterference x L) [m/m]
ence
The values given are based
on measurements, in which a
pulse current of the wave shape
8/20 was passed through a defined length of a cable support
system.

Transfer impedance 8/20 mOhm/m


Type, cable tray/cable ladder

Without cover

With cover

MKS 630 FS

1.14

0.71

MKS 630 FT

1.14

0.71

MKSU 630 FS

0.44

0.09

MKSU 630 FT

0.44

0.09

GRM 55/300 FS

6.17

5.5

KTS

OBO

13

Surface testing/salt spray mist


test
All the system components must
show sufficient resistance against
corrosion in agreement with the
KTS standard, DIN EN 61537.
Theminimum zinc layer thicknesses
are
determined
through
ameasurement. Thegrouping into
the appropriate class is located at
the right of the table. The top of
the table shows the area of application and the zinc loss to be expected according to DIN EN ISO
12944.

14

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Surface testing and corrosion categories

Planning aid, general


information

Surface testing and corrosion categories

Corrosion categories to DIN EN ISO 12944


Corrosion
category

Typical environment, inside

Typical environment, outside

Corrosion
load

Average
zinc loss

C1

Heated buildings with neutral atmospheres,


e.g. offices, shops, schools, hotels

Insignificant

<0.1
m/a

C2

Unheated buildings in which condensation can


occur, e.g. warehouse, sports' halls

Atmosphere with low level of impurities


often rural areas

Low

0.1 to
0.7 m/a

C3

Production facilities with a high level of humidity and some air impurities, e.g. plants for food
production, laundries, breweries, dairies

City and industrial atmosphere, considerable impurities through sulphur dioxide, coastal areas with low salt load

Medium

0.7 to
2.1 m/a

C4

Chemical plants, swimming pools, boatsheds


over seawater

Industrial areas and coastal areas with


low salt load

Strong

2.1 to
4.2 m/a

C 5-I

Buildings or areas with almost constant condensation and with heavy impurities

Industrial areas with high levels of humidity and aggressive atmosphere

Very strong
(industry)

4.2 to
8.4 m/a

C 5-M

Buildings or areas with almost continuous condensation and with high levels of impurities

Coastal or offshore areas with salt


load

Very strong
(sea)

> 4.2 to
8.4 m/a

Classification of corrosion resistance (from the draft of DIN EN 61537)


Class

Reference material and surface treatment

0*

None

Electroplated to a minimum thickness of 5 m

Electroplated to a minimum thickness of 12 m

Pre-galvanised to 275 degrees according to EN 10327 and EN 10326

Pre-galvanised to 350 degrees according to EN 10327 and EN 10326

Galvanised to a zinc coating thickness of (minimum) 45 m according to ISO 1461

Galvanised to a zinc coating thickness of (minimum) 55 m according to ISO 1461

Galvanised to a zinc coating thickness of (minimum) 70 m according to ISO 1461

Galvanised to a zinc coating thickness of (minimum) 85 m according to ISO 1461 (usually high-alloy silicon steel)

9A

Rustproof steel, manufactured according to ASTM: A 240/A 240M 95 a designation S30403 or EN 10088 degree 14301 without finishing **

9B

Rustproof steel, manufactured according to ASTM: A 240/A 240M 95 a designation S31603 or EN 10088 degree 14301 without finishing

9C

Rustproof steel, manufactured according to ASTM: A 240/A 240M 95 a designation S30403 or EN 10088 degree 14301 with finishing **

9D

Rustproof steel, manufactured according to ASTM: A 240/A 240M 95 a designation S31603 or EN 10088 degree 14404 with finishing **

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

* For materials which do not have a declared corrosion resistance classification


** The end treatment process is used to improve the protection against crack corrosion and the contamination of other steels

KTS

OBO

15

Whether indoors or outdoors, in


aggressive atmospheres or under
special hygienic conditions: OBO
can offer the perfect surface
and materials for your cable support system, no matter what the
requirements may be. OBO cable
support systems are machined
from high-quality sheet steel or
steel wire and are available with
various surfaces. Different hardening and coating methods ensure tailor-made corrosion protection, specially tailored to the
appropriate application. In addition, OBO cable support systems
are available in stainless steel
and with coloured coatings.

Indoor use
For indoor areas, OBO can offer
cable support systems with galvanisation or strip galvanisation.
They are particularly suited to dry
atmospheres without any impact
from aggressive pollutants.

16

OBO

KTS

Electro-galvanisation
Electrolyticgalvanisation in accordance with DIN EN 12329
Average coating thickness approx. 2.510 m
According to RoHSguideline
Components: Mesh cable trays
and small parts such as bolts,
washers and nuts
Strip galvanisation
Hot-dipgalvanised according
to the strip-galvanisingmethod
in accordance with DIN EN
10327 (formerly DIN EN
10147 and DIN EN 10142)
Average coating thickness approx. 20 m
Joints in themetal are protected by cathodic corrosion protection up to a thickness of
2.0mm
Components: Metal products such
as cable trays, fittings and barrier
strips

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Surfaces for use in internal areas

Planning aid, general


information

Surfaces for use in external areas

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Outdoor use
OBO can offer versions with hot
dip galvanisation and doubledip galvanisation for outdoor and
wet room use.

Hot-dip galvanisation
Hotgalvanisation using the
dippingmethod according to
DIN EN ISO 1461
Coating thickness to DIN EN
ISO 1461 approx. 4060 m
Any interfaces added at a later
datemust also begalvanised
to protect against corrosion
Components: Sheet steel products
such as cable trays and welded
components such as supports and
brackets

Double-dip galvanisation
Hot dipping with zinc-aluminium coating in accordance with
DIN EN 10327
Average coating thickness approx. 23 m
Joints in themetal are protected by cathodic corrosion protection up to a thickness of
2.0mm
Components: Metal products such
as covers, barrier strips and
punched parts

KTS

OBO

17

Applications: Tunnel construction, food or chemical industries


There are also OBO stainless steel
systems for special hygiene and
quality requirements for special
visual criteria for open wiring.

18

OBO

KTS

SS304 stainless steel


OBO Code: V2A
Europeanmaterial number:
1.4301
Americanmaterial designation:
304
Welded components are additionally passivated
Unwelded components are
rinsed and degreased
Components: V2A selection programme with the title "V2A stainless steel systems"

V4A stainless steel


OBO Code: V4A
Europeanmaterial number:
1.4571
Americanmaterial designation:
316 / 316 T
Welded components are additionally passivated
Unwelded components are
rinsed and degreased
Components: V4A selection programme with the title "V4A stainless steel systems"

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Surfaces for use in tunnels, food or chemical industries

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Applications with specific optical


requirements or special environmental conditions
Colour-coated cable support systems are becoming ever more
popular. The coating may be required for optical reasons or for
reasons of corrosion protection:

Colour coatings for reasons of


corrosion protection
Cable support system in FT
(hot-dipgalvanised version)
All RAL colours available
Coating of the visible surfaces
and/or the complete system
Suitable for the colour of the
structure when routed openly
Separation of different voltages/functions (e.g. blue
230/400 V power supply; red
weak current such as telephone line and IT)

Colour-coated systems are not indicated specially in this catalogue.


You can obtain details for these
systems by contacting our telephone hotline on +49 (0)2373 891500.

KTS

OBO

19

Planning aid, general


information

Surfaces for special visual requirements or special environmental loads

Not all cables are the same. To


select the perfect cable support
system, you need to know which
type of cables are to be laid: Are
they sensitive data cables,
which must be laid at a certain
distance from each other on account of the necessary shielding? Or power cables, for which a
not inconsiderable heat buildup must be allowed for? For all
these applications OBO can offer
tailor-made system solutions.

20

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Which cabling method is used?

Planning aid, general


information

Mesh cable trays for the installation of light cables


Areas of application: IT cabling,
telephone cabling and control cables. Also suitable for use in false
ceilings and cavity floors.

Wide span cable trays and ladders for large support distances
Areas of application: For installations in which the support distances are more than three metres,
on account of the construction
conditions.

Modular system for special tasks


The product range that knows no
bounds. The range of individually
combinable products is particularly
suited to complex installation
tasks.

Cable ladders for power cables


with a large cross-section
Areas of application: Cables and
power conductors with large
cross-sections. These can be fastened to the rungs using clamp
clips. The high load capacity
and good ventilation ensure perfect cable laying.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Universal cable trays


Areas of application: From low
voltage cabling to power supply.

KTS

OBO

21

The usable cross-section of the cable simulates the cavity in real laying.

An important criterion for the selection of the correct cable support


system is the cable volume, for
which there must be sufficient
space in the cable tray. As the cables are never packed tightly together or are absolutely parallel, it
is not enough to base the volume
calculation solely on the cable diameter. A realistic calculation is
provided by the formula (2r). To
save you work, we have listed the
diameter and usable cross-section
of the most important cable types
below.
Important: These values are average values, which may vary
from manufacturer to manufacturer. Please refer to themanufacturer's specifications for the exact values.

22

OBO

KTS

Cable diameter (1) and space required (2)

Calculation with the formula (2r)


The diameter says little about the
actual space required by a cable.
Calculate: (2r). This value reflects
the realistic space requirements,
including the compartments.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

How can I work out the volume of cables?

Planning aid, general


information

How can I work out the volume of cables?

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Insulated power cables

Insulated power cables

Telecommunications cables

Type

Diameter
mm

Usable crosssection
cm

1x4

6.5

0.42

1 x 10

10.5

1.1

2 x 2 x 0.6

0.25

1x6

0.49

1 x 16

11.5

1.32

4 x 2 x 0.6

5.5

0.3

1 x 10

0.64

1 x 25

12.5

1.56

6 x 2 x 0.6

6.5

0.42

1 x 16

9.5

0.9

1 x 35

13.5

1.82

10 x 2 x 0.6

7.5

0.56

1 x 25

12.5

1.56

1 x 50

15.5

2.4

20 x 2 x 0.6

0.81

3 x 1.5

8.5

0.72

1 x 70

16.5

2.72

40 x 2 x 0.6

11

1.12

3 x 2.5

9.5

0.9

1 x 95

18.5

3.42

60 x 2 x 0.6

13

1.69

3x4

11

1.21

1 x 120

20.5

4.2

100 x 2 x 0.6

17

2.89

4 x 1.5

0.81

1 x 150

22.5

5.06

200 x 2 x 0.6

23

5.29

4 x 2.5

10.5

1.1

1 x 185

25

6.25

2 x 2 x 0.8

0.36

4x4

12.5

1.56

1 x 240

28

7.84

4 x 2 x 0.8

0.49

4x6

13.5

1.82

1 x 300

30

6 x 2 x 0.8

8.5

0.72

4 x 10

16.5

2.72

3 x 1.5

11.5

1.32

10 x 2 x 0.8

9.5

0.9

4 x 16

19

3.61

3 x 2.5

12.5

1.56

20 x 2 x 0.8

13

1.69

4 x 25

23.5

5.52

3 x 10

17.5

3.06

40 x 2 x 0.8

16.5

2.72

4 x 35

26

6.76

3 x 16

19.5

3.8

60 x 2 x 0.8

20

5 x 1.5

9.5

0.9

3 x 50

26

6.76

100 x 2 x 0.8

25.5

6.5

5 x 2.5

11

1.21

3 x 70

30

200 x 2 x 0.8

32

10.24

5x4

13.5

1.82

3 x 120

36

12.96

5x6

14.5

2.1

4 x 1.5

12.5

1.56

5 x 10

18

3.24

4 x 2.5

13.5

1.82

5 x 16

21.5

4.62

4x6

16.5

2.72

5 x 25

26

6.76

4 x 10

18.5

3.42

7 x 1.5

10.5

1.1

4 x 16

21.5

4.62

7 x 2.5

13

1.69

4 x 25

25.5

6.5

4 x 35

28

7.84

4 x 50

30

4 x 70

Type

Diameter
mm

Usable crosssection
cm

Type

Diameter
mm

Usable crosssection
cm

IT cables Type Cat...


Type

Diameter
mm

Usable crosssection
cm

Cat. 5

0.64

34

11.56

Cat. 6

0.64

4 x 95

39

15.21

4 x 120

42

17.64

4 x 150

47

22

4 x 185

52

27

4 x 240

58

33.6

5 x 1.5

13.5

1.82

5 x 2.5

14.5

2.1

5x6

18.5

3.42

5 x 10

20.5

4.2

5 x 16

22.5

5.06

5 x 25

27.5

7.56

5 x 35

34

11.56

5 x 50

40

16

Coax cable (Standard)


Type

Diameter
mm

Usable crosssection
cm

SAT/BK
cable

6.8

0.48

KTS

OBO

23

Cable height
The cable heightmay not exceed
the edge height of the cable tray.

Volume reserve
When selecting the system, a volume reserve of at least 30%
should be planned for possible later installations.

Branches
When dimensioning branches, the
bending radii of the cables must
be taken into account.

Separation of system levels


When selecting the volume, pay attention to the different conductors.
To separate different voltage levels, you must take the required
spacings into account.

Same usable cross-section, different requirements


The following table will help you to
choose a cable support system of
the right volume. It underlines the
interplay of tray or conductor
width, slant height and usable
cross-section. The difference when
laying the same volume of data
and power cables should be taken
into account: while it is possible to
select a narrow, high tray for data
cables, a wide, flat tray is necessary for power cables. When selecting the correct system, also observe with the current DIN/VDE
standards (0298 T1 to T4). They
provide information on the heating
of conductors, depending on the
amassment and the ambient temperature.

Examples
Flat, wide variant:
e.g. for power cables
Cable tray width: 300mm
Side rail height: 35mm
Usable cross-section: 103cm2
Narrow, high variant:
e.g. for data cables
Cable tray width: 100mm
Side height: 110mm
Usable cross-section: 108cm2

24

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

How can I find a system of the appropriate volume?

Planning aid, general


information

Reference laying types

Reference laying types


The specifications of DIN 298-4
with regard to themass and ventilation of cables should be taken into account during laying.

Reference laying type: E or F


Cable on perforated cable tray,
horizontal/vertical, e.g. type
RKS/MKS

Reference laying type: E, F or G


Cable or installation cable
onmesh cable trays, e.g. type
GR-Magic

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Reference laying type: C


Cable on unperforated cable tray,
e.g. type MKSU

KTS

OBO

25

100mm = 15kg/m.

200mm = 30kg/m

300mm = 45kg/m

400mm = 60kg/m

500mm = 75kg/m

600mm = 90kg/m

Of equal significance for the selection of the cable support systemmost suited to the application
is the load capacity of the system.
Thismust bematched with the expected cable weight (including the
reserve for later installation). There
are three variants for determining
the cable weight:

cable load, DIN VDE 0639 Part 1


(cable support systems) can offer
a formula.
In
the
example
calculation,
themaximum approved cable load
for a cable tray is worked out using the dimension 60 mm x
300 mm and a usable cross-section of 178cm.

only provide a rough overview.


They
are
average
values,
whichmay vary frommanufacturer
to manufacturer. Please refer to
the manufacturer's specifications
for the exact values.

Variant 1: Orientation to experience values


The average load capacity of a cable tray can be calculated roughly
using experience values. For a
system with a strut height of
60 mm, a value of 15 kg per
100 mm width is valid for
each metre of cable tray or cable
ladder. However, more accurate
than orientation to experience values is to calculate the cable load
using the formula from DIN VDE
0639 Part 1 (Variant 2) or
the manufacturer's specifications
(Variant 3).
The graphics show the load capacities, based on experience values, of cable trays with a rail
height of 60 mm, relative to cable
tray widths of 100 to 600mm.

Variant 3: Exact calculation according to manufacturer's specifications


Most cable manufacturers offer a
very accurate method of calculating cable weights, and appropriate
lists or tables can be obtained
from them. Important: The tables

Variant 2: Calculation formula according to VDE 0639 T1


To calculate amaximum approved

26

OBO

KTS

Cable load (F) =

1. Cable load (F) =

0.028 N
x usable-cross-section
m x mm

0.028 N
x 17,800mm = 500 N/m
m xmm

2. Conversion from Newtons (N) to kilogrammes (kg)


10 N ~ 1kg in our example, thismeans: 500 N/m = 50kg/m
3. Maximum occurring load = 50kg/m

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

How do I calculate the cable weight?

Planning aid, general


information

Actual cable weights of different cable types

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Insulated power cables


Type

Cable load
kg/m

1x4
1x6

Insulated power cables

Telecommunications cables

Type

Cable load
kg/m

Type

Cable load
kg/m

0.08

1 x 10

0.18

2 x 2 x 0.6

0.03

0.105

1 x 16

0.24

4 x 2 x 0.6

0.035

1 x 10

0.155

1 x 25

0.35

6 x 2 x 0.6

0.05

1 x 16

0.23

1 x 35

0.46

10 x 2 x 0.6

0.065

1 x 25

0.33

1 x 50

0.6

20 x 2 x 0.6

0.11

3 x 1.5

0.135

1 x 70

0.8

40 x 2 x 0.6

0.2

3 x 2.5

0.19

1 x 95

1.1

60 x 2 x 0.6

0.275

3x4

0.265

1 x 120

1.35

100 x 2 x 0.6

0.445

4 x 1.5

0.16

1 x 150

1.65

200 x 2 x 0.6

0.87

4 x 2.5

0.23

1 x 185

2 x 2 x 0.8

0.04

4x4

0.33

1 x 240

2.6

4 x 2 x 0.8

0.055

4x6

0.46

1 x 300

3.2

6 x 2 x 0.8

0.08

4 x 10

0.69

3 x 1.5

0.19

10 x 2 x 0.8

0.115

4 x 16

1.09

3 x 2.5

0.24

20 x 2 x 0.8

0.205

4 x 25

1.64

3 x 10

0.58

40 x 2 x 0.8

0.38

4 x 35

2.09

3 x 16

0.81

60 x 2 x 0.8

0.54

5 x 1.5

0.19

3 x 50

1.8

100 x 2 x 0.8

0.875

5 x 2.5

0.27

3 x 70

2.4

200 x 2 x 0.8

1.79

5x4

0.41

3 x 120

5x6

0.54

4 x 1.5

0.22

5 x 10

0.85

4 x 2.5

0.29

5 x 16

1.35

4x6

0.4

5 x 25

1.99

4 x 16

1.05

7 x 1.5

0.235

4 x 25

1.6

7 x 2.5

0.35

4 x 35

1.75

4 x 50

2.3

4 x 70

3.1

4 x 95

4.2

4 x 120

5.2

4 x 150

6.4

4 x 185

8.05

4 x 240

11

5 x 1.5

0.27

5 x 2.5

0.35

5x6

0.61

5 x 10

0.88

5 x 16

1.25

5 x 25

1.95

5 x 35

2.4

5 x 50

3.5

IT cables Type Cat...


Type

Cable load
kg/m

Cat. 5

0.06

Cat.6

0.06

Coax cable (Standard)


Type

Cable load
kg/m

SAT/BK cable

0.06

KTS

OBO

27

Explanation of the pictograms: 1 = load in kN withoutman load, 2 = support width inm, 3 = strut bend inmm

Load tests for cable support systems


All the OBO articles and systems
are subjected to practical load testing. The basic principles for the
tests of OBO cable support systems are included in DIN EN
61537 and DIN VDE 0639. After
the load test, the maximum load
capacity can be determined for
each component, depending on
the support distances and specific
article parameters, such as component dimensions. This is shown
in a diagram, included with each
component.
You can find additional information
on the load tests for cable trays,
brackets and suspended supports
in this catalogue. The valuesgiven
do not take resistance against environmental forces such as snow,
wind and other outside influences
into account.

28

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Which trays and ladders can support which cable load?

Planning aid, general


information

Information 1: The testing process


The basic principles of the tests of
OBO cable support systems are
included in VDE 0639 Part 1 and
DIN EN 61537. The purpose of the
tests is to determine themaximum
load capacities for each component, depending on parameters
such as component width, support
spacing, etc. and to present this in
a diagram to be included with
each component. In our example,
we have selected the cable tray
MKS 60. The area highlighted in
blue schematises the experiment
setup with a variable support spacing (L) in the central area and a
factor of 0.8 x L at the front and
rear ends of the cable tray.

Information 2: Load curves for


selected cable tray or cable ladder widths
The load capacity of the cable
trays according to the support
width can be read off in the diagram using the load curves this
is an example for the cable tray
MKS 60/... for the tray widths 100
to 600 mm. A key factor for the
load capacity of the cable trays is,
beside the support spacing and
side height, thematerial thickness,
which varies according to type.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Load diagram, legend


1 = Load in kN/m without man
load
2 = Support width inm
3 = Strut bending inmm
4 = Schematic diagram of the
support widths for testingmethod
-- = Approved load for the different
tray widths depending on the
support spacing
-- = Rail bend according to the
support width

KTS

OBO

29

Information 3: Possible support


spacings
The theoretically possible spans
for the cable tray can be read off
on the axis at the foot of the table.
Using the load curves, it is easy to
read off to what extent the load capacity of the system falls as the
support spacing grows. On all
OBO cable support systems (with
the exception of the wide span
trays), we recommend not exceeding a support spacing of 1.5 m, if
possible.

Information 4: Ratio: load/span


Which load is possible at which
support spacing? With the diagram, you can find the appropriate
information at a glance. In our example (with the blue background)
a span of 2.25m on the MKS tray
produces amaximum load capacity of 0.75 kN for each runningmetre of cable tray. Please note that,
in this example, the volume of the
cable traymay exceed the permitted load. Therefore, if at possible,
do not exceed the support spacing
of 1.5 m, as recommended by
OBO.

Information 5: W = Strut sag


To what extent does the load on a
cable tray cause the strut to bend?
This information is supplied by the
blue curve (w) in millimetres (orientation values on the axis on the
right-hand side of the diagram).

The course of the blue curve clearly shows how quickly the cable
tray will sag as the support spacing increases. In our example, the
bend at a support spacing of
2.25 m is shown, here approximately 12mm.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Which trays and ladders can support which cable load?

30

OBO

KTS

Planning aid, general


information

Which bracket can support which cable load?

Load diagram, legend


1 = Bend inmm at the
bracket tip
2 = Load in kN/m
withoutman load
--= Load curves for the
various bracket lengths

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Key components of the OBO cable


support systems are the installation components, in particular the
brackets and suspended supports.
They connect the cable trays and
ladders to the wall and to the ceiling, and are thus an important
construction element of the overall
system. When calculating the load
capacity of a cable support system, the brackets and suspended
supports must not be forgotten.
The test diagram is also useful in
selecting the right products.

KTS

OBO

31

Information 1: Recommended maximum load of the brackets


The bracket is the part of the installation system upon which the
cable tray ormesh cable tray is located. It is either directly connected to the wall or is connected to
the
ceiling
using
supports.
The grey bar on the right edge of
the diagram provides information
on the maximum load capacity of
the bracket.

Information 4: Bending of the


bracket tip at maximum load
The bending factor of the bracket
at maximum load can also be
seen in the diagram. In our example (shown in orange), the bend
value for a 610 mm wide bracket
at amaximum load of approx. 3.0
kN is approximately 4.5 mm.
To minimise the bend, the centre
ofgravity of the cable load should
be as close as possible to the wall
or the support fastening.

32

OBO

KTS

Information 2: Load curves for all


bracket widths
The bending of the bracket is dependent on its width, which, in our
example, can range from 110mm
to 610 mm. The load curves are
assigned to the appropriate bracket type.

Information 3: Bending of the


bracket tip at a specific load
The load curve in the diagram provides information on the bending
of the boom tip at a specific load.
In our example (dotted orange
line), a 610mm wide bracket with
a load of 2 kN bends by approx.
3.1 mm. A basic rule of thumb is:
The shorter the bracket, the less
the bend will be.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, general


information

Which bracket can support which cable load?

Planning aid, general


information

Which support can support which cable load?

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Load diagram, legend


1 = Bend inmm at the
bracket tip
2 = Load in kN/m
withoutman load
--= Load curves for the
various bracket lengths

Information 1: Various support


lengths and bracket widths
The load capacity of a cable support system is not just dependent
on the width of a bracket, but also
on the length of a suspended support. The load curves in the diagram provide information on the
load capacity of a suspended support of length 600, 1,000, 1,500
or 2,000 mm, taking the bracket
width into account.

Information 2: Calculation of the


deflection for the example
The weight of the total suspended
support/bracket/cable tray system
causes an excursion of the suspended support from the vertical.
The excursion value can be read
off from the axis on the left edge
of the diagram. In our example
(blue background), a 1,500 mm
long suspended support, together
with a 400mm wide bracket and a
weight load of 4 kN at the end of
the support will produce an excursion of approximately 14mm.

Information 3: Calculation of the


excursion at maximum load for
the example
The excursion of the suspended
support at amaximum load can also be read off on the diagram. Our
blue example shows an excursion
of roughly 18mm at the end of the
support for a 1,500mm long suspended support, in combination
with a 400 mm wide bracket at
amaximum cable load of approximately 5 kN.

KTS

OBO

33

70

OBO

KTS

Contents

72

Mounting aid, cable tray systems MKS,SKS, DKS, IKS

KTS

OBO

71

Planning aid, cable tray systems

Mounting aid, cable tray system MKS, SKS

and materials ensure safe corrosion protection. Side heights of


35, 60, 85 and 110mm up to the
special cable tray systems DKS
and IKS with 30% perforations
and large entries and exits are
available.
When mounting fittings, always
plan additional supports.
Besides the various fittings, the
system also includes all types of

connectors and additional accessories such as barrier strips, joint


plates, mounting plates and covers.
You can find detailed mounting
examples and article descriptions
on the following pages. You can
find comprehensive information
on the use of function maintenance in our new BSS fire protection systems catalogue.
04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

The cable tray is suitable for universal cable routing. From low
voltage cabling to power supplies, from data cables to telecommunications networks. A full
product range with suitable system components can create perfect solutions to any task. Nomatter whether used in dry inner areas or in aggressive atmospheres:
Different
surface
versions

72

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Centre suspension application


Centre suspension of the cable tray systems
MKS, SKS, EKS, DKS and IKS with a central
suspension hanger, type MAH, and threaded
rod 2078/M10.

Ceiling mounting application


Ceiling mounting of a cable tray with support
and wall and support bracket.

Wall mounting application with bracket


Standard mounting of a cable tray on the wall
with wall and support brackets.

Screwless straight connector set, type RV


Illustration of the quick connector set RV.. contained in the scope of delivery, for strip galvanised cable trays (you can find information on
the connectors in the article description).

Installation of RV straight connector set


Simply clamp the two side sections of the connector set in the side rail.

Screwless straight connector set, type RV


Push the corresponding joint plate down until it
has locked in place.

Screwless straight connector set, type RV


Correctly used RV straight connector set.

Straight connection with joint cover


Cable tray with screwed straight connection
and joint plate, type SSLB. The joint plate can
also be mounted above the bar of the RV
straight connector set.

Horizontal angle connection of cable trays


Horizontal angle connection of cable trays for
brackets created during construction and cut
cable tray ends.

Vertical adjustable connection of cable trays


Vertical adjustable connection of cable tray for
construction-side height jumps of any angle.

Bend creation with corner connector


For 90 bends to be created at site, the corner
connector, type REV, can be used to increase
the internal radius.

KTS

OBO

73

Planning aid, cable tray systems

Mounting aid, cable tray system MKS, SKS

Direct connection with corner connectors


Corner connector, type REV, to increase the
angle when creating tees without fittings. Additional supports should be planned for the area
of the branches.

Branch with angle connectors


Installation of built T exit with angle connectors,
type WKV. Additional supports should be
planned for the area of the branches.

Installation of reducer / stop-end


The reducer / stop-end plate component is
used as closure and to reduce the width of cable trays.

Screwless barrier strip mounting


Screwless mounting of the barrier strip TSG ...
with clamping piece KS KR. The barrier strip
can be run over the joint without machining
and can be connected without bolts using the
TSGV barrier strip connector.

Barrier strip mounting with screw connection


Screwed barrier strip fastening of the barrier
strip, TSG 60, with truss-head bolts M6x12. The
barrier strip can simply be run over the joint
and connected without bolts using the barrier
strip connector TSGV.

Installation of bend (width 100 300 mm)


The bend in widths 100 to 300 mm is pushed
into the rail on the one side and over the connector on the other. Additional supports should
be planned for the area of the fittings.

Installation of bend (width 400 600 mm)


The bend in widths 400 to 600 mm is connected to the cable tray using connectors and a
joint plate. Additional supports should be
planned for the area of the fittings.

Installation of add-on tee (width 100 300


mm)
To mount the add-on tee, separate the cable
tray rail and screw it tight. Additional supports
should be planned for the area of the fittings.

Installation of add-on tee (width 400 600


mm)
To mount the add-on tee, separate the cable
tray rail and screw it tight. Additional supports
should be planned for the area of the fittings.

74

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, cable tray systems

Mounting aid, cable tray system MKS, SKS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Installation of vertical add-on tee


Vertical mounting of the add-on tee as lengthwise funnel.

Installation of vertical add-on tee


Vertical mounting of the add-on tee as lengthwise funnel.

Installation of tee (width 100 300 mm)


The tee in widths 100 to 300 mm is pushed into the rail on the one side and over the connector on the other. Additional supports should
be planned for the area of the fittings.

Installation of tee (width 400 600 mm)


The tee in widths 400 to 600 mm is connected
to the cable tray using connectors and a joint
plate. Additional supports should be planned
for the area of the fittings.

Installation of cross-over (width 100 300


mm)
The cross-over in widths 100 to 300 mm is
pushed over connectors and screwed tight. Additional supports should be planned for the area of the fittings.

Installation of cross-over (width 400 600


mm)
The cross-over in widths 400 to 600 mm is
connected to the cable tray using connectors
and a joint plate. Additional supports should be
planned for the area of the fittings.

90 bend (rising/falling)
90 bend, rising or falling, for the creation of
simple vertical changes of direction.

Installation of adjustable vertical bend


element
Installation of the adjustable vertical bend element for the creation of adjustable bends. The
adjustable vertical bend element is connected
to the cable tray using adjustable connectors.

Installation of rising adjustable vertical bend


Adjustable vertical bend to bridge height offsets. The adjustable vertical bend is connected
with to the cable tray using the adjustable connectors.

KTS

OBO

75

Planning aid, cable tray systems

Mounting aid, cable tray system MKS, SKS

Screwless cover mounting


Screwless installation of the cover, type DRLU,
on a cable tray using the cover clamp, type
DKU. The cover clamp locks in the top hole of
the side rail.

Installation of bottom end plate


Fastening of the bottom end plate, type BEB, to
protect the cables.

Mounting plate with quick fastening


Fastening of the mounting plate, type MP, on
the cable tray. The mounting plate can be fastened to the rail with quick connectors, and
permanently fastened using truss-head bolts of
type FRS B.

Universal mounting plate


Fastening of the mounting plate, type MP uni,
on the cable tray.

Fastening on bracket
The cable tray is fastened to the bracket with
truss-head bolts FRS M6 x 12.

Cable tray mounting on steel girder


Cable tray mounting with chuck jaws of type
TKS-L-25 and U supports as cantilever beams
on steel girders. Use spacers, type DSK, for
safe functioning.

Complete mounting of a cable tray system


Illustration of a multi-layer cable tray system
mounted on the ceiling.

76

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, cable tray systems

Mounting aid, cable tray system MKS, SKS

96

OBO

KTS

Cable ladder systems

98

Mounting aid, cable ladder systems

KTS

OBO

97

Planning aid, cable ladder systems

Mounting aid, cable ladder system

98

OBO

KTS

factor guaranteeing easy mounting is the option of integrated fastening of cables using OBO U
clamps to the rungs, which are
available in various different versions. OBO cable ladder systems
are shipped folded up, thus saving space during transport and
storage. OBO cable ladder systems can be supplied in lengths

of 3 m and 6 m, in all standard


widths from 200 to 600 mm and
width rail heights of 45, 60 and
110mm. On the following pages,
you can select your preferred installation variant from the installation diagrams shown and then
combine the corresponding articles in the order section.
04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

The high load capacity and good


ventilation of the OBO cable ladder systems can offer tangible
benefits, in particular during the
installation of power cables. OBO
Bettermann's cable ladder systems can be used universally
and, due to the continuous rail
and rung perforation, can offer
countless installation benefits. A

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Mounting aid, cable ladder system

Jump application
Implementation of vertical jumps with adjustable connectors, e.g. for ceiling joists.

Threaded rod suspension application


Suspension of a cable ladder with threaded
rods and U supports as a cross-section.

Support suspension
Suspension of a cable ladder with supports
and support brackets.

Straight connection of cable ladders


Straight connection of cable ladder with
straight connector, type LVG.

Horizontal angle connection of cable ladders


Horizontal angle connection with straight and
angle connectors, type LWVG.

Vertical angle connection of cable ladders


Creation of a vertical angle connection using
adjustable connectors, type LGVG.

Installation of falling adjustable vertical bend


Adjustable vertical bend to bridge height offsets. The adjustable vertical bend is connected
to the cable ladder using the adjustable connectors.

Installation of a cable ladder bend


Connection of the cable ladder with the bend,
type LBI 90. Additional supports should be
planned for the area of the fittings.

Installation of a tee
Installation of a tee, type LT, to create a vertical
exit. Additional supports should be planned for
the area of the fittings.

Installation of an cross-over
Installation of an cross-over, type LK, for the
creation of two exits. Additional supports
should be planned for the area of the fittings.

Installation of tee
Creation of a horizontal tee exit of two cable
ladders at different heights. The support angle,
type LAW, is required to fix two cable ladders.

Planning aid, cable ladder systems

Support and threaded rod suspension


application
Example of installing cable ladders with supports of U profiles and threaded rod suspension.

KTS

OBO

99

Tee with corner plates


Creation of horizontal tees for cable ladders
running at the same height. To increase the cable supporting surface, use corner plates of
type LEB. Additional supports should be
planned for the area of the exits.

Tee with support plate


Creation of horizontal tees for cable ladders
running at the same height. To increase the cable supporting surface and to protect the cables, use support plates, type LALB. Additional
supports should be planned for the area of the
exits.

Vertical exit on support/bracket


Installation of a vertical exit in the area of the
support/bracket. Fasten the cable ladder using
the support, type LAL 70.

Vertical cable exit


The drop-out plate, type LAB, is used to increase the cable supporting surface for vertically exiting cables and as cable protection.

Screwless barrier strip fastening


Screwless fastening a barrier strip in cable ladders with clamping piece, type KS KL.

Screwed barrier strip fastening


Screwed mounting of the TSG barrier strip
through the perforated rung of the cable ladders.

Straight barrier strip connection


Screwless straight connection of barrier strips
in cable ladders using the barrier strip TSGV.

Cable ladder centre suspension with U profile


Installation of a cable ladder with central suspension hanger MAHU and a U support.

Cable ladder centre suspension with


threaded rod
Installation of a cable ladder with central suspension hanger MAHU and a threaded rod.

Installation of insert plate


Installation of insert plates, type ELB-L.

100

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Planning aid, cable ladder systems

Mounting aid, cable ladder system

Mounting aid, cable ladder system

Cable ladder as-delivered state


All cable ladders are supplied folded up.

Complete installation
Illustration of complete cable ladder mounting.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Cover mounting
Positioning and fastening of the cover on the
cable ladder using turn-buckle, type DRL.

KTS

OBO

101

Side height 110


Cable tray MKS
Type

Width
mm

MKS 110 FS
MKS 120 FS
MKS 130 FS
MKS 140 FS
MKS 150 FS
MKS 155 FS

Plate Length Useful Appr. load:


thickness
cross- 1.5 m 2.0 m
section
mm
mm
cm kN/m kN/m

100
200
300
400
500
550

ST Steel

1
1
1
1
1
1

3,000
3,000
3,000
3,000
3,000
3,000

108
218
328
438
548
603

1.85
1.85
1.85
1.85
1.85
1.85

1.3
1.3
1.3
1.3
1.3
1.3

2.5 m

3.0 m

kN/m

kN/m

0.75
0.75
0.75
0.75
0.75
0.75

Weight

Item No.

kg/100 m

0.6
0.6
0.6
0.6
0.6
0.6

243.100
308.500
373.900
438.700
503.700
536.700

6060 10 2
6060 19 6
6060 30 7
6060 40 4
6060 41 2
6060 52 8

/m

FS Strip-galvanised

Cable tray systems

MKS 110 =medium-duty cable tray system with a side height of 110mm.
Magnetic shield insulation without cover 20 dB, with cover 50 dB.
Including connector, type RLVL 110.
Load diagram, cable tray, type MKS 110

Approval cable tray/ladder


load in kN/m without man
load
Support width in m

Rail bend in mm at approved


kN/m
Load scheme during testing
Load curve with cable
tray/ladder width in mm
Strut bend curve according to
support width

Cable tray SKS


Type

Width

Plate
thickness

mm

mm

Length Useful Appr. load:


mm

cross- 1.5 m
section
cm kN/m

2.0 m

3.0 m

4.0 m

kN/m

kN/m

kN/m

Weight

Item No.

kg/100 m

SKS 110 FS
SKS 120 FS
SKS 130 FS
SKS 140 FS
SKS 150 FS
SKS 155 FS

100
200
300
400
500
550

1.5
1.5
1.5
1.5
1.5
1.5

3,000
3,000
3,000
3,000
3,000
3,000

108
218
328
438
548
603

3.0
3.0
3.0
3.0
3.0
3.0

2.4
2.4
2.4
2.4
2.4
2.4

1.2
1.2
1.2
1.2
1.2
1.2

0.8
0.8
0.8
0.8
0.8
0.8

243.000
308.200
373.300
438.700
503.700
804.700

6061 10 9
6061 20 6
6061 30 3
6061 40 0
6061 50 8
6061 55 9

SKS 110 FT
SKS 120 FT
SKS 130 FT
SKS 140 FT
SKS 150 FT
SKS 155 FT

100
200
300
400
500
550

1.5
1.5
1.5
1.5
1.5
1.5

3,000
3,000
3,000
3,000
3,000
3,000

108
218
328
438
548
603

3.0
3.0
3.0
3.0
3.0
3.0

2.4
2.4
2.4
2.4
2.4
2.4

1.2
1.2
1.2
1.2
1.2
1.2

0.8
0.8
0.8
0.8
0.8
0.8

383.200
490.000
570.000
697.400
725.100
852.900

6061 60 5
6061 62 1
6061 65 6
6061 67 2
6061 70 2
6061 72 9

ST Steel

FS Strip-galvanised FT Hot-dip galvanised

/m

SKS 110 = heavy-duty cable tray system with 110mm side height.
Magnetic shield insulation without cover 20 dB, with cover 50 dB.
04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

FS version includes connector, type RLVL 110.


Load diagram, cable tray, type SKS 110

Approval cable tray/ladder


load in kN/m without man
load
Support width in m

Rail bend in mm at approved


kN/m
Load scheme during testing
Load curve with cable
tray/ladder width in mm
Strut bend curve according to
support width

Always indicate the article number when ordering.

KTS

OBO

221

Side height 110


Straight and angle connector
Type

Side
height

Pack.

Weight

mm

pcs

kg/100 pcs.

Item No.

RLVL 110 FS 110

10

29.500 6067 13 1

RLVL 110 FT 110

10

29.500 6067 91 3

ST Steel

FS Strip-galvanised FT Hot-dip galvanised

/pc.

Straigt and angle connector for cable trays, fittings and barrier strips with a side height of
110mm.

Cable tray systems

Including appropriate fasteningmaterial.

Articulated connector
Type

Side
height

Pack.

Weight

mm

pcs

kg/100 pcs.

Item No.

RGV 110 FS 110

10

64.000 7082 03 7

RGV 110 FT 110

10

64.000 7082 43 6

ST Steel

FS Strip-galvanised FT Hot-dip galvanised

/pc.

Adjustable connector for cable trays and barrier strips with a side height of 110mm.

110

Including appropriate fasteningmaterial.

200

Corner connector
Type

130

100

7x30

Side
height

Pack.

Weight

mm

pcs

kg/100 pcs.

REV 110 FS 110

10

72.000 6067 99 9

REV 110 DD 110

10

72.000 6069 33 9

ST Steel

240

Item No.

FS Strip-galvanised DD Zinc-aluminium coated, double-dip

/pc.

Corner connector for cable trays with side height 110mm.


Fasteningmaterials should be ordered separately.

Reducer bracket and end closure

12.5

110

7 x 14

40

Type

7 x 32

Pack.

Weight

pcs

kg/100 pcs.

Item No.

mm

mm

RWEB 110 FS
RWEB 120 FS
RWEB 130 FS
RWEB 140 FS
RWEB 150 FS
RWEB 155 FS

110
110
110
110
110
110

100
200
300
400
500
550

1
1
1
1
1
1

16.400
29.000
41.000
52.900
64.800
70.700

7111 09 6
7111 20 7
7111 30 4
7111 42 8
7111 50 9
7111 54 1

RWEB 110 DD
RWEB 120 DD
RWEB 130 DD
RWEB 140 DD
RWEB 150 DD
RWEB 155 DD

110
110
110
110
110
110

100
200
300
400
500
550

1
1
1
1
1
1

16.300
29.100
41.000
52.800
64.700
70.700

7107 45 5
7107 47 1
7107 50 1
7107 53 6
7107 55 2
7107 56 0

B
B + 100

Side Width
height

ST Steel

/pc.

FS Strip-galvanised DD Zinc-aluminium coated, double-dip

Reducer / stop-end for cable trays with side height 110mm.


Including appropriate fasteningmaterial.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

45 bend
Type

Width

Pack.

Weight

mm

pcs

kg/100 pcs.

Item No.

RB 45 110 FS 100
RB 45 120 FS 200
RB 45 130 FS 300

1
1
1

70.000 7000 63 4
100.000 7000 65 0
135.000 7000 67 7

RB 45 110 FT 100
RB 45 120 FT 200
RB 45 130 FT 300

1
1
1

150.000 7068 11 5
110.000 7068 21 2
145.000 7068 32 8

ST Steel

FS Strip-galvanised FT Hot-dip galvanised

/pc.

45 bend, horizontal, for all cable tray types of 110mm side height.
The fitting is shipped in an unmounted state. The WKV 110 angle connector is designed for 90
bends and can be adjusted to 45 on site.
Including appropriate fasteningmaterial.

Always indicate the article number when ordering.

KTS

OBO

223

System accessories 35, 60, 85, 110


Joint plate
Width Quantity of
bolts
mm

pc.

Pack.

Weight

pcs

kg/100 pcs.

Item No.

SSLB 100 FS
SSLB 150 FS
SSLB 200 FS
SSLB 300 FS
SSLB 400 FS
SSLB 500 FS
SSLB 550 FS
SSLB 600 FS

85
135
185
285
385
485
535
585

2
2
2
3
4
5
5
6

20
20
20
20
20
20
20
20

7.700
12.200
16.700
25.700
34.700
43.700
48.200
52.700

7070 20 5
7070 20 9
7070 21 3
7070 21 7
7070 22 1
7070 22 5
7070 22 9
7070 23 3

SSLB 100 DD
SSLB 150 DD
SSLB 200 DD
SSLB 300 DD
SSLB 400 DD
SSLB 500 DD
SSLB 550 DD
SSLB 600 DD

85
135
185
285
385
485
535
585

2
2
2
3
4
5
5
6

20
20
20
20
20
20
20
20

7.700
12.200
16.700
25.700
34.700
43.700
48.200
52.700

7070 30 6
7070 31 0
7070 31 4
7070 31 8
7070 32 2
7070 32 6
7070 33 0
7070 33 4

ST Steel

Cable tray systems

Type

/pc.

FS Strip-galvanised DD Zinc-aluminium coated, double-dip

Wide joint plate for use in all cable trays and wide span cable trays.
Including appropriate fasteningmaterial.

Floor end plate


Type

Width

Pack.

Weight
kg/100 pcs.

Item No.

mm

pcs

BEB 050 FS
BEB 100 FS
BEB 150 FS
BEB 200 FS
BEB 300 FS
BEB 400 FS
BEB 500 FS
BEB 550 FS
BEB 600 FS

50
100
150
200
300
400
500
550
600

100
100
100
100
100
100
50
50
50

2.500
5.400
8.400
11.400
17.200
23.100
29.000
32.000
35.000

7083 04 1
7083 10 6
7083 15 7
7083 20 3
7083 30 0
7083 40 8
7083 50 5
7083 55 6
7083 60 2

BEB 050 DD
BEB 100 DD
BEB 150 DD
BEB 200 DD
BEB 300 DD
BEB 400 DD
BEB 500 DD
BEB 550 DD
BEB 600 DD

50
100
150
200
300
400
500
550
600

100
100
100
100
100
100
50
50
50

2.500
5.400
8.400
11.400
17.200
23.100
29.000
32.000
35.000

7083 61 6
7083 61 8
7083 62 2
7083 62 6
7083 63 0
7083 63 4
7083 63 8
7083 64 0
7083 64 2

ST Steel

/pc.

FS Strip-galvanised DD Zinc-aluminium coated, double-dip

Floor end plate for floor reinforcement at the ends of the cable tray and as cable protection.
For fastening, please order bolts, type FRSB M6 x 12, separately.

Mounting plate
Type

Height Width
mm

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

MP UNI FS

mm

Pack.

Weight

pcs

kg/100 pcs.

Item No.

115 170

40

13.300 7084 77 3

MP UNI DD 115 170

40

13.300 7085 11 4

ST Steel

/pc.

FS Strip-galvanised DD Zinc-aluminium coated, double-dip

Mounting plate, for fastening on the side rail of cable support systems.
Please order the truss-head bolt, type FRSB 6 x 12, separately.

Mounting plate
Type

Height Width
mm

mm

MP 225 UNI FS 115 225

ST Steel

Pack.

Weight

pcs

kg/100 pcs.

20

Item No.

20.000 7084 87 0

FS Strip-galvanised

/pc.

Mounting plate for universal use on side rails of cable trays andmesh cable trays.
Please order the truss-head bolt, type FRSB 6 x 12, separately.

Always indicate the article number when ordering.

KTS

OBO

227

Side rail height 110 mm


Cable ladder LG 110
Type

Width
mm

Length Useful Appr. load:


Rail
thickness
cross- 2.0 m 3.0 m
section
mm
mm
cm kN/m kN/m

4.0 m

5.0 m

kN/m

kN/m

Weight

Item No.

kg/100 m

LG 112 3000 FS
LG 113 3000 FS
LG 114 3000 FS
LG 115 3000 FS
LG 116 3000 FS

200
300
400
500
600

1.5
1.5
1.5
1.5
1.5

3,000
3,000
3,000
3,000
3,000

188
283
378
475
568

3.1
3.1
3.1
3.1
3.1

1.4
1.4
1.4
1.4
1.4

0.65
0.65
0.65
0.65
0.65

0.5
0.5
0.5
0.5
0.5

382.000
406.000
430.300
454.300
478.700

6216 40 4
6216 40 7
6216 41 0
6216 41 3
6216 41 6

LG 112 3000 FT
LG 113 3000 FT
LG 114 3000 FT
LG 115 3000 FT
LG 116 3000 FT

200
300
400
500
600

1.5
1.5
1.5
1.5
1.5

3,000
3,000
3,000
3,000
3,000

188
283
378
475
568

3.1
3.1
3.1
3.1
3.1

1.4
1.4
1.4
1.4
1.4

0.65
0.65
0.65
0.65
0.65

0.5
0.5
0.5
0.5
0.5

405.000
430.700
456.700
482.300
508.300

6216 42 3
6216 42 6
6216 42 9
6216 43 2
6216 43 5

LG 112 6000 FS
LG 113 6000 FS
LG 114 6000 FS
LG 115 6000 FS
LG 116 6000 FS

200
300
400
500
600

1.5
1.5
1.5
1.5
1.5

6,000
6,000
6,000
6,000
6,000

188
283
378
475
568

3.1
3.1
3.1
3.1
3.1

1.4
1.4
1.4
1.4
1.4

0.65
0.65
0.65
0.65
0.65

0.5
0.5
0.5
0.5
0.5

382.000
406.200
430.300
454.500
478.700

6216 44 2
6216 44 5
6216 44 8
6216 45 1
6216 45 4

LG 112 6000 FT
LG 113 6000 FT
LG 114 6000 FT
LG 115 6000 FT
LG 116 6000 FT

200
300
400
500
600

1.5
1.5
1.5
1.5
1.5

6,000
6,000
6,000
6,000
6,000

188
283
378
475
568

3.1
3.1
3.1
3.1
3.1

1.4
1.4
1.4
1.4
1.4

0.65
0.65
0.65
0.65
0.65

0.5
0.5
0.5
0.5
0.5

405.000
430.800
456.700
482.500
508.300

6216 46 5
6216 46 8
6216 47 1
6216 47 4
6216 47 7

ST Steel

/m

FS Strip-galvanised FT Hot-dip galvanised

Cable ladder systems

Cable ladder with perforated side rail of side height 110mm with riveted C profile rungs, open
in an upwards direction.

Magnetic shield insulation without cover 10 dB, with cover 15 dB.


The cable ladder is shipped folded up.
You can find the appropriate U clamp of type 2056 in the vertical ladder systems chapter.
Load diagram, cable ladder, type LG 110 VS

Approval cable tray/ladder


load in kN/m without man
load
Support width in m

Rail bend in mm at approved


kN/m
Load scheme during testing
Load curve with cable
tray/ladder width in mm
Strut bend curve according to
support width

Protective cap
Type

Colour

Pack.

Weight

pair

kg/100 pairs

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

SKH 110 OR Pastel orange

20

Item No.

1.400 6222 55 3

/pair

PE Polyethylene
Protective cap to cover cable ladder ends of side height 110mm.

Straight connector
Type

Side
height

Pack.

Weight

mm

pcs

kg/100 pcs.

Item No.

LVG 110 FS 110

20

41.600 6216 54 5

LVG 110 FT 110

20

44.900 6216 54 8

ST Steel

FS Strip-galvanised FT Hot-dip galvanised

/pc.

Straight connector as external connector to connect cable ladders and fittings with a side height
of 110mm and continuous rail perforation.

The bolt fastening ensures the continuity of the equipotential bonding.

Always indicate the article number when ordering.

KTS

OBO

271

Side rail height 110 mm


Angle connector
Type

LWVG 110 FS

Side
height

Pack.

Weight

mm

pcs

kg/100 pcs.

Item No.

110

20

48.800 6216 58 7

LWVG 110 VA4301 110

20

48.800 6216 59 0

ST Steel

V2A Stainless steel, 1.4301

/pc.

FS Strip-galvanised Bright

Angle connector as external connector to join cable ladders and fittings with a side height of
110mm and continuous rail perforation.

The bolt fastening ensures the continuity of the equipotential bonding.

Articulated connector
Type

Side
height

Pack.

Weight

mm

pcs

kg/100 pcs.

Item No.

LGVG 110 FS 110

10

61.000 6216 65 0

LGVG 110 FT 110

10

65.000 6216 65 3

ST Steel

/pc.

FS Strip-galvanised FT Hot-dip galvanised

Adjustable connector as external connector to join cable ladders and fittings with a side height
of 110mm and continuous rail perforation. Angle can be adjusted vertically.

The bolt fastening ensures the continuity of the equipotential bonding.

Connection piece
Weight

pcs

kg/100 pcs.

Item No.

LAS 110 FS

10

20.000 6221 41 6

LAS 110 FT

10

20.000 6221 42 4

ST Steel

/pc.

FS Strip-galvanised FT Hot-dip galvanised

115.3

Pack.

37

50

Cable ladder systems

Type

52

Connector for creation of branches at the same height at a later date.


To increase the cable supporting surface, use a conjunction of corner plates of type LEB.

Barrier strip
Type

Dimen- Dimension H sion L


mm

mm

Pack.

Weight

kg/100 m

Item No.

TSG 85 FS

85 3,000

45

0.000 6062 11 4

TSG 85 DD

85 3,000

45

0.000 6062 33 1

ST Steel

/m

FS Strip-galvanised DD Zinc-aluminium coated, double-dip

Barrier strip for separation of cables of different voltages or functions.

Barrier strip connector


Type

TSGV VA4310

Pack.

Weight

pcs

kg/100 pcs.

10

Item No.

1.000 6067 97 0

/pc.

V2A Stainless steel, 1.4310

Barrier strip connector for screwless connection of the TSG barrier strip in all side heights.

Type

KS KL VA4310

Pack.

Weight

pcs

kg/100 pcs.

30

V2A Stainless steel, 1.4310

Item No.

0.512 6062 28 4

/100 pc.

Clamping piece for screwless fastening of barrier strips in cable ladders.

272

OBO

KTS

Always indicate the article number when ordering.

04_KTS_Katalog_2010_Neuer_Stand / en / 17/03/2010 (LLExport_00942)

Clamping piece for barrier strip fastening

450

OBO

KTS

04_KTS_Katalog_2010_Neuer_Stand / en / 15/03/2010 (LLExport_00942)

Terms and conditions of sale and delivery of the companies OBO BETTERMANN GmbH & Co. KG and OBO BETTERMANN Projekt und
Systemtechnik GmbH,
and OBO Befestigungselemente GmbH, Menden
1.
All our supplies and services shall be governed exclusively by the following terms and conditions, including
our additional terms and conditions for cable tray business transactions. Any terms and conditions of business and
purchasing of the customer shall be valid only if we have acknowledged them in writing. Our quotations are without
engagement; they are mere invitations to submit contract offers. Any and all transactions and agreements, including those entered into by our employees and agents shall only be binding upon our written confirmation or invoicing. The foregoing provision shall also apply to any modifications of the agreed formal requirements.
2.
The documents and data pertaining to the quotation, such as illustrations, brochures, drawings, dimensions,
loading capacity values and weight details are approximate only, unless they are expressly stipulated to be binding.
Samples are non-binding samples for inspection. Any purchase according to sample will be subject to customary
deviations and deviations resulting from normal production processes. The properties of the sample shall be no
guaranteed quality of the purchase object unless expressly stated otherwise in the confirmation of order. Samples
must be returned to us at the latest within four weeks in perfect condition. If they are not returned within this period
in proper condition, we shall be entitled to charge the purchase price for the sample in accordance with our current
price list. All information on our products, in particular the illustrations, drawings, weight, dimension and performance data included in our quotations and printed matter shall be regarded as approximate average values and
shall not represent any quality guarantee.
With regard to products made according to customer drawings, samples and other instructions of the customer, we
will not provide any warranty nor assume any liability for the due and proper functioning of the product or for any
other defects if and to the extent they are based upon the customer's specifications. The customer shall indemnify
us from any third party claims, including claims for product liability as may be asserted against us for damages resulting from the products unless we have caused such damages by intent or gross negligence. The customer shall
warrant that the manufacture and supply of products made in accordance with his instructions will not infringe any
proprietary rights of third parties. Should any proprietary rights be asserted against us, we shall be entitled, without
any legal review of the third party claims, to withdraw from the contract after hearing the customer, unless the third
party withdraws the claims asserted against us under its proprietary rights within eight days by written declaration.
The customer shall compensate us for any damage sustained as a result of the assertion of proprietary rights. In
case of withdrawal, the work we have carried out so far shall be remunerated. Further rights under the statutory
provisions shall not be affected thereby.
Any moulds, tools and design data produced by us for the execution of the order shall be our exclusive property.
Unless expressly agreed otherwise, the customer shall not have any claims thereto, even if he has contributed to
the costs of producing any such moulds, tools and design data.
3.
The packing, shipping route and means of transportation shall be left to our discretion in the absence of any
other agreements. They shall be charged at their cost price. We will take back undamaged cases, when being returned carriage paid, at 2/3 of the amount invoiced. The one-way or pool pallets used for transport shall be either
exchanged upon taking delivery or returned. The smallest packing units stocked and listed may not be broken up
for rationalisation reasons. In case of orders for different quantities, the nearest packing unit will be supplied.
We reserve the right to deviate from the agreed delivery quantity, in particular in the case of custom-made products, to a customary extent or in conformity with national or international standards. In case of a demand for adhering to a precise quantity, an express reference is necessary and subject to confirmation.
Master and call orders shall oblige the customer to accept the total quantity on which the master/call order is based. Where no particular call orders are specified in the contract, the total quantity of the master call order must be
called within twelve months. If the customer fails to adhere to call deadlines, we shall be entitled to deliver and
charge the total quantity in full after four weeks from written notice with reference to the consequences of any failure to call. Our rights arising from any default of the customer shall not be affected thereby.
4.
Unless otherwise agreed, our prices are quoted ex works and do not include packing and insurance. The
value added tax at the rate applicable on the date of dispatch will be added to our prices. The purchaser shall ensure the correctness of his VAT identification number, which he must notify to us immediately without being asked.
He shall undertake to inform both us and the competent domestic tax authority without delay of any change in his
name, address and VAT identification number.
Delivery shall be franco domicile within Germany, i.e. carriage and packing prepaid, if the net order value is in excess of 1,200. For small orders below 100 (net excluding value added tax), we shall invoice a lower quantity
surcharge of 10 (net) per order. Upon transfer of our supplies and services to a carrier or forwarding agent, at the
latest upon their leaving our warehouse or supply plant, the risk shall pass to the recipient, even in case of deliveries free place of destination.
5.
Delivery periods and delivery deadlines shall be approximate only unless we have expressly stated in writing
that they are binding. Delivery periods shall commence upon receipt of our confirmation of order, but not before
clarification of all execution details, ex place of delivery. The customer shall only be entitled to withdraw from the
contract after having granted a reasonable extension of time. We reserve the right to make partial deliveries.
Claims for damages and reimbursement of expenses - for any reason whatsoever - shall be subject to the provisions set out in article 10.
In the event of any circumstances that are beyond our control within the scope of normal operating risks and obstruct or make impracticable any delivery, we shall be entitled to suspend delivery by the duration of such
obstruction plus a reasonable start-up period or to withdraw from the contract for the part not yet fulfilled. The purchaser can demand a statement from us as to whether we wish to deliver within a reasonable period or withdraw. If
we fail to make such a statement, the purchaser may withdraw. Our notice to the purchaser shall be deemed to be
sufficient evidence that we have been prevented from delivering.
Delivery time is extended in case of such events as labour disputes, strikes and lockouts, orders from the authorities, difficulties with the procurement of materials, spoiled work or post-processing, shutdowns and staff
shortage as well as shortage of means of transport, and general occurrence of unforeseen events beyond our
scope of influence, by the length of duration of these events.
6.
Payments shall be made upon receipt of invoice less a 3% cash discount for payment within 10 days or net
after 30 days from date of invoice. Erection work and all paid labour work must be paid within 10 days without deduction of any cash discount. In case of non-cash payments, the date of the credit note will be deemed to be the
date of receipt of payment. Payments received shall always be credited first against costs, then against interest
and then against the earliest liability. Cheques and bills of exchange shall only be accepted as means of payment.
Any payment by bill of exchange shall be subject to a prior separate and written agreement, whereby all bill costs
shall be borne by the customer and no discount can be granted. The customer shall have no right to refuse performance and no right of retention - for any legal reason whatsoever - unless we have acknowledged his claim beforehand in writing or his claim has the force of law.
The customer shall only be entitled to set off claims which have the force of law, are undisputed or acknowledged
by us in writing.
7.
We shall retain title to the goods supplied by us until all our claims arising from our business transactions
with the customer have been satisfied - current account clause - and all bills of exchange or cheques submitted for
payment by the customer have been honoured.
Any treatment or processing of goods subject to our retention of title (reserved goods) shall be carried out for us as
the manufacturer in accordance with 950 BGB (German Civil Code) without any obligation on our part. If our reserved goods are to be regarded as the main item or the main item is owned by the customer, full title to the new
item shall pass to us when it is created. In other cases, we shall acquire a co-ownership interest in the new item in
the proportion of the sales value of our reserved goods to the other goods used for the new item at the time of
processing, intermingling, joining or mixing. The customer shall take custody of our ownership or co-ownership interest free of charge; it shall be treated as reserved goods.
Before transfer of title, our goods shall be neither pledged nor assigned as collateral without our prior consent. In
addition, any third party rights or pledges shall be notified to us immediately and we shall be given all details and
provided all documents necessary for intervention; otherwise the customer must bear our loss. In the latter case,
our total claims against the customer shall also be immediately payable.
The customer shall be entitled to sell or to use our reserved goods in the ordinary course of business subject to the
condition that the relevant claims are transferred in accordance with article 8 below. This right shall lapse upon the
customer's failure to promptly meet his payment obligations towards us or in the event of any cheque or bill protests or his suspension of payments. In such cases, we shall be entitled to take back the goods provisionally at the

customer's expense and to sell them at our duly exercised discretion after a corresponding reminder has been sent
to the customer. We will then pass the due amount to the customer's credit.
8.
If our goods are sold before payment of our claim, the customer shall be obliged to retain our title against his
purchaser until the goods have been paid for in full by the purchaser. The claim arising against the purchaser from
such resale as well as any other ancillary rights or security interests of the customer resulting from the sale and
any claims for compensation in case of damage to or destruction of our reserved property, including the relevant
insurance sum shall hereby be assigned to us. We hereby accept this assignment. Where our co-ownership interest is sold, the relevant claims shall be assigned in the amount corresponding to the value of our interest.
The customer shall, at our request, inform us of his purchasers, notify them of the assignment made and provide
us with any and all documents required to assert our rights.
As long as the customer meets his contractual obligations without delay, he shall be authorised to collect the
claims assigned. He shall keep the amounts collected on our behalf separately and remit them to us immediately
as soon and as far as our claims become due. The authorisation shall lapse in case of any cheque or bill protest of
the customer or his definite suspension of payments. The customer shall bear the costs incurred for any action
taken against third parties and shall advance them upon request.
If the security provided to us by the retention of title and the anticipatory assignment should exceed the claims to
be secured by more than 20%, we shall, at the customer's request, release paid supplies of our choice. Upon payment of all our claims by the customer, assigned claims shall pass to the customer.
9.
Any complaints for obvious defects regarding the quantity or quality of our supplies and services that are
identifiable upon careful inspection shall without delay, but at the latest within the period of limitation of eight days
from arrival of the goods at the address of the customer or the person appointed by him, be notified in writing to us,
not to our representatives. Slight deviations in dimensions and designs within the scope of defined technical tolerances shall not give rise to any right of complaint. Any rejected goods may only be returned to us with our prior
written authorisation.
In case of justified complaints within the prescribed period, we shall, at our option, take remedial action by way of
subsequent performance, by rectifying the defect, supplying non-defective goods or providing a credit note for the
lower value calculated.
We shall be entitled to refuse subsequent performance in accordance with the statutory provisions. If we refuse
subsequent performance, if any subsequent performance remains unsuccessful or if the customer cannot be reasonably expected to accept any subsequent performance, the latter shall be entitled to withdraw from the contract
in compliance with the provisions of the following sentences. The customer shall only be entitled to withdraw from
the contract - where a withdrawal is not excluded by law - upon the unsuccessful expiry of a reasonable period for
subsequent performance set by him, unless this period was not required under the statutory provisions ( 281
para. 2, 323 para. 2, 440, 441 para. 1 BGB (German Civil Code)).
In case of his withdrawal, the customer shall be liable for any deterioration, destruction or loss of use resulting from
any negligence or intent on his part. Any claims for damages or reimbursement of expenses of the customer shall
be subject to the provisions set out in article 10.
In the case of any fraudulent concealment of a defect or in the case of any provision of a quality guarantee for the
goods sold at the time of the passing of risk within the meaning of 444 BGB (German Civil Code) (seller's
declaration that the object sold has a specific property at the time of the passing of risk and that the seller, regardless of any fault on his part, intends to be answerable for any and all consequences resulting from its
absence), the customer's rights shall be exclusively governed by the statutory provisions.
We shall - in addition to the statutory grounds for refusal - also be entitled to refuse subsequent performance if and
as long as the customer fails to send us, at our request, the rejected goods or a sample thereof; the customer shall
have no right of withdrawal for any such refusal. We may further refuse any subsequent performance if the goods
concerned have been altered or modified without our consent unless the customer can prove that the defect was
not caused by such alteration or modification.
The limitation period for any claims arising from defects shall be one year; in the case of goods which have been
used in accordance with their intended purpose for a building and have caused its defectiveness, the limitation period shall be two years. The provisions of 478, 479 BGB (German Civil Code) on recourse in the chain of suppliers shall not be affected thereby.
10. In the case of a pre-contractual, contractual or non-contractual breach of duty, including unsatisfactory delivery, tortious conduct and producer's liability, we shall only be liable for compensatory damages and reimbursement
of expenses - subject to further contractual or statutory liability requirements - in the case of intent, gross negligence or slightly negligent breach of a material contractual duty (contractual duty the infringement of which jeopardises the fulfilment of the object of the contract). However - except in the case of intent - our liability shall be limited to the typical contractual damage that was foreseeable at the time the contract was entered into.
The purchaser shall not be permitted to make a claim for expenses incurred in vain.
Except for any breach of material duties, our liability for slight negligence shall be excluded, but in any case be limited to the amount of the purchase price.
Any claim asserted by the customer or a third party for payment of a contractual penalty shall be excluded.
With regard to damages caused by delay, we shall only be liable for slight negligence up to the amount of 5% of
the purchase price agreed with us.
The exclusions and limitations of liability set forth above shall not apply in the event that a guarantee is given with
respect to the quality of the object sold within the meaning of 444 BGB (German Civil Code) if a defect is fraudulently concealed or in the event of injury to life, physical injury or injury to health, or strict liability under the German
Product Liability Act.
Any and all claims for damages against us, for any legal reason whatsoever, shall become statute-barred at the latest after one year from delivery of the goods to the customer, in the case of tortious liability from the time of knowledge, or grossly negligent ignorance, of the circumstances giving rise to the claim and the person liable to pay
damages. This provision shall not apply in the case of liability for intent and in the event that a guarantee is
given for the quality of the object sold, in the case of fraudulent concealment of a defect or in the event of injury to
life, physical injury or injury to health, or strict liability under the German Product Liability Act. Any shorter limitation
periods shall take precedence.
11. We shall be entitled to process and store any customer data obtained with regard to or in connection with
the business relationship in accordance with the German Federal Data Protection Act, irrespective of whether
suchdata is provided by the purchaser himself or by any third parties.
12. Place of performance for delivery and payment is Menden/Sauerland. The court of competent jurisdiction for
any and all disputes, including disputes with regard to bills of exchange and cheques, is the Local Court (Amtsgericht) of Menden or, at our option, the District Court (Landgericht) of Arnsberg, irrespective of the value of the object
in dispute. We shall, however, also be entitled to take legal proceedings against the customer at the place of his
registered office.
German law shall be exclusively applicable. The application of international purchase laws is hereby excluded.
Should, for any reason whatsoever, individual provisions of our terms and conditions of sale and delivery be invalid, the validity and binding nature of the other provisions shall not be affected thereby. The customer agrees,
that the invalid provision shall be replaced by a valid provision that comes as close as possible to the economic
meaning of the invalid provision.
13. The prices of products made of brass and copper are subject to certain fluctuations that are based on the
relevant DEL listings. The prices of our brass articles are based on a DEL listing of 150 for Ms 58, those of our
copper products on a DEL value for electrolyte copper of 200.
In case of any increase or reduction in these prices by more than 15, a five per cent surcharge or deduction shall
be made for each 15 points. The calculation of any such surcharges or deductions shall be based on the DEL listing of the date of our receipt of the order.
Valid from August 2004

With the QR Code you have direct access to our products on the Internet.

You can find further information on the QR Code at


www.obo-bettermann.com.

OBO Bettermann GmbH & Co. KG


P.O. Box 1120
58694 Menden, Germany

Customer Service Germany


Tel. +49 (0)2373 891 500
Fax +49 (0)2373 897 777
E-mail: info@obo.de

www.obo-bettermann.com

OBO BETTERMANN Order no. 9158031 01/2010 EN

QR-Code

You might also like