MSB Example
MSB Example
MSB Example
February 2015
Vacuum Breakers
7.0-1
Metal-Enclosed Switchgear
MEB & MSB Medium Voltage
Vacuum Breakers
Sheet 07 001
CA08104001E
Contents
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
MEB
MVS
MVS
Metal-Enclosed Switchgear
20
21
7.0-2
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
February 2015
7.1-1
Sheet 07 003
General Description
MEB Metal-Enclosed
Drawout Breaker
General Description
Eatons MEB (metal-enclosed breaker)
switchgear assembly consists of a
single-high drawout vacuum circuit
breaker (Type VCP-W) in a metalenclosed cabinet. This equipment has
been designed primarily where metalclad switchgear is not required and a
switch or switch and fuse combination
are not suitable. As primary protection
for single-ended substations, it can
eliminate the need for a secondary
main circuit breaker. It can also be
applied as the primary main device and
integrated with fused or unfused feeder
switches in an Eaton Type MVS load
interrupter switchgear assembly.
Two and three breaker automatic
transfer schemes are also available.
For drawout vacuum circuit breaker
metal-clad switchgear, Eaton Type
VacClad-W, see Tab 5.
For drawout vacuum circuit breaker
metal-enclosed front access only,
Type MEF switchgear, see Tab 6.
ii
Seismic Qualification
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
7.1-2
February 2015
Sheet 07 004
i
ii
1
2
3
Construction
Current and voltage transformers
associated with protection devices
such as the EDR-3000 or EDR-5000
electronic overcurrent relays are
applied using the same ratings as
drawout metal-clad switchgear.
Metering and protective relay devices
are mounted on the single front
hinged door. The front door may be
opened at any time to provide access
to low voltage components and to the
front of the circuit breaker without
being exposed to high voltage.
6
7
8
EDR-5000 Multifunction Protective Relay
10
11
Overcurrent Protection
Eatons MEB breaker can be furnished
with an Eaton Type EDR-3000 or
EDR-5000 relay to provide overcurrent
and fault protection. Optional zero
sequence 50/51G ground fault protection
is shown below. Refer to Tab 4 for
more details.
12
13
14
15
16
17
Relay Type
Protective Relay
IEEE Functions
Metering
EDR-3000
50/51; 50/51G
Amperes
and
ampere
demand
EDR-5000
Amps; volts;
pf, energy,
power; THD;
waveform
3-CTs
Vacuum
Breaker
52
EDR-3000 or
EDR-5000 1
50/51
50N/51N
18
1-Zero Sequence CT
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
February 2015
7.1-3
Sheet 07 005
Technical Data
Assembly Ratings
Rated
BIL kV
4.76
4.76
4.76
4.76
4.76
4.76
4.76
4.76
4.76
15
15
15
15
15
15
15
1
60
60
60
60
60
60
60
60
60
95
95
95
95
95
95
95
Rated Momentary
Current kA rms Asymmetrical
600
600
600
1200
1200
1200
1200
2000
2000
600
600
600
1200
1200
1200
1200
40
61
80
40
61
80
101
40
61
40
61
80
40
61
80
101
25
38
50
25
38
50
63
25
38
25
38
50
25
38
50
63
ii
1
2
3
4
The switchgear assembly is designed for use with Type VCP-W, VCP-WC and VCP-WG circuit breakers. However, please note that certain VCP-WC
circuit breakers may have higher capabilities than required by ANSI standards. In such cases, switchgear assembly ratings as given in this table
will apply.
5
6
Table 7.1-3. Available Type VCP-W, VCP-WC and VCP-WG Vacuum Circuit Breakers Rated per ANSI Standards
Circuit
Breaker
Type 2345
Rated
Maximum
Voltage
Rated Voltage
Range Factor
kV rms
50 VCP-W 250
50 VCP-W 350
50 VCP-W 500
75 VCP-W 500
150 VCP-W 500
150 VCP-W 750
150 VCP-W 1000
150 VCP-W 1500
50 VCP-W 25
50 VCP-W 40
50 VCP-W 50
50 VCP-W 63
75 VCP-W 50
150 VCP-W 25
150 VCP-W 40
150 VCP-W 50
150 VCP-W 63
50 VCP-WG 50
50 VCP-WG 63
150 VCP-WG 50
150 VCP-WG 63
2
3
4
5
4.76
4.76
4.76
8.25
15
15
15
15
4.76
4.76
4.76
4.76
8.25
15
15
15
15
4.76
4.76
15
15
1.24
1.19
1.0
1.25
1.3
1.3
1.3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Rated
Continuous
Current
Rated Short-Circuit
Current at Rated
Maximum Voltage
K*I
7
8
2.6 * K * I
1.6 * K * I
Amperes
kA Crest
kA rms Asym
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
29
41
63
33
18
28
37
63
25
40
50
63
50
25
40
50
63
50
63
50
63
97
132
170
111
62
97
130
170
65
104
130
164
130
65
104
130
164
137
173
137
173
58
78
101
66
37
58
77
101
40
64
80
100.8
80
40
64
80
100.8
82
103
82
103
36
49
63
41
23
36
48
63
25
40
50
63
50
25
40
50
63
50
63
50
63
For detailed ratings of Type VCP-W circuit breakers, refer to Tab 5, Table 5.4-1A.
For detailed ratings of Type VCP-WC circuit breakers, refer to Tab 5, Table 5.4-2.
For detailed ratings of Type VCP-WG circuit breakers, refer to Tab 5, Table 5.4-3 and 5.4-4.
Please note certain Eaton breakers may have higher capabilities than required by ANSI standards. When these
breakers are applied in an MEB switchgear assembly, the assembly ratings as given in Table 7.1-2 will apply.
9
10
11
12
13
14
15
16
17
Table 7.1-4. VCP-W Breaker Stored Energy Mechanism Control Power Requirements
Rated Control
Voltage
Run Amperes
Time Seconds
Close or
Trip Amperes
Voltage Range
Inrush Amperes
Close
Trip
48 Vdc
125 Vdc
250 Vdc
120 Vac
240 Vac
36.0
16.0
9.2
16.0
9.2
9.0
4.0
2.0
4.0
2.0
6
6
6
6
6
16
7
4
6
3
3856
100140
200280
104127
208254
2856
70140
140180
104127
208254
18
19
20
21
CA08104001E
7.1-4
February 2015
Sheet 07 006
LayoutDimensions
i
ii
1
2
3
80.00
(2032.0)
4
5
Outdoor
95.50
(2425.7)
Indoor
90.38
(2295.6)
Outdoor
95.50
(2425.7)
PR
Indoor
90.38
(2295.6)
52
9
10
11
12
13
14
15
16
17
Outdoor
95.50
(2425.7)
PR
36.00
(914.4)
Arrangement 1
Single Unit, Cable In and Out
PR
Indoor
90.38
(2295.6)
52
Outdoor
41.00 (1041.4)
Indoor
36.00 (914.4)
Arrangement 2
Primary for Dry-Type Transformer
7
8
70.00
(1778.0)
70.00
(1778.0)
52
20.00
36.00
(508.0)
(914.4)
Arrangement 3
Primary for Liquid-Filled Transformer
70.00
(1778.0)
70.00
(1778.0)
Outdoor
95.50
(2425.7)
Outdoor
95.50
(2425.7)
PR
Indoor
90.38
(2295.6)
Indoor
90.38
(2295.6)
52
PR
PR
ATC
52
52
36.00
(914.4)
36.00
15.00
36.00
(914.4)
(381.0)
(914.4)
Arrangement 5
Two Breaker Auto TransferSingle Load
36.00
36.00
36.00
15.00
(914.4)
(914.4)
(914.4)
(381.0)
Arrangement 4
Main Device with Feeders; Metering Section (Optional)
36.00 48.00
(914.4 1219.2)
70.00
(1778.0)
Outdoor
95.50
(2425.7)
PR
PR
52
Indoor
90.38
(2295.6)
52
52
18
19
20
21
36.00
36.00
15.00
(914.4)
(381.0) (914.4)
Arrangement 6
Three Breaker Auto TransferMain-Tie-Main Feeders
36.00
(914.4)
36.00
(914.4)
36.00
(914.4)
Dimensions in inches (mm). Not to be used for construction purposes unless approved.
For more information, visit: www.eaton.com/consultants
CA08104001E
February 2015
7.1-5
Sheet 07 007
LayoutDimensions
16.00 (406.4)
8.00 (203.2)
95.46
(2424.7)
Outdoor
Height
10.00 (254.0)
10.00 (254.0)
Optional
Rear Door
1.50 (38.1)
Customer's Cable
Support (Locate at
Installation)
A&B
70.00
(1778.0)
CT
90.37
(2295.4)
Indoor
Height
2
3
VCPW
Roof Layout
Lug
36.00 (914.4)
Line or Bus
(Fixed)
16.00 (406.4)
10.00 (254.0)
10.00 (254.0)
Optional
Rear Door
VT
1.25 (31.8)
6.60 (167.6)
8.00 (203.2)
5
6
A&B
70.00
(1778.0)
70.00
(1778.0)
7
8
Figure 7.1-3. 5 and 15 kV MEB with Main Bus, Main Breaker and
Fixed Line or Bus VTs
1
ii
1.25 (31.8)
Floor Layout
Depth shown is based on the use of (2)-500 kcmil cables per phase.
For stand-alone cable in and cable out in the same section, minimum
80.00-inch (2032.0 mm) depth is required.
36.00 (914.4)
Note: Drawout VTs are not available in MEB switchgear. Use Type
VCP-W or MEF designs.
For cable in and cable out in same section, 80.00-inch (2032.0 mm)
depth is required.
9
10
5 or 15 kV Class
Indoor
Outdoor
11
MEB section
MVS section (non-fused)
Fuses (three) add
Transition section
1600 (726)
1500 (681)
200 (91)
300 (136)
1900 (863)
1800 (817)
200 (91)
12
13
14
15
16
17
18
19
20
21
CA08104001E
7.1-6
February 2015
Sheet 07 008
LayoutDimensions
a Locations for tie-down 0.65 (16.5 mm) diameter holes.
Four places. Customer provided bolts for anchoring
should be 0.5013 min. SAE Grade 5, (M12 x 1.75 min.
CL 10.9), and tightened to 75 ft-lbs (101.7 Nm).
i
ii
1
2
5.00
(127.0)
Typ.
1.25
(31.8)
2.95
(74.9)
3
6.00
(152.4)
Min.
4
3
6.00
(152.4)
Min.
1.25
(31.8)
4.25
(108.0)
4
18.00
(457.2)
Min.
FRONT DOOR
Optional
Rear Door
4.25
(108.0)
5
Min.
8
9
Figure 7.1-5. Typical Anchor Plan for MEB, Indoor or Outdoor
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
February 2015
7.2-1
Sheet 07 009
General Description
i
ii
1
2
3
4
5
6
7
ANSI/IEEE C37.20.3
ANSI/IEEE C37.20.4
ANSI C37.22
ANSI C37.57
ANSI C37.58
NEMA SG5
NEMA SG6
CSA 22.2 No. 31
EEMAC G8-3.3
CSA listable for Canada and
U.S. markets
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
7.2-2
February 2015
Sheet 07 010
General Description
Seismic Qualification
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
7.2-3
Sheet 07 011
Construction
Overcurrent Protection
ii
1
2
3
EDR-3000 Overcurrent Protective Relay
4
5
6
7
8
MSB with Control Switches,
Digitrip 3000 Overcurrent Relay
with Optional Metering Shown
9
10
11
12
13
14
Digitrip 520MCV
15
16
17
18
19
20
Digitrip 1150V
CA08104001E
21
7.2-4
February 2015
Sheet 07 012
Technical Data
i
ii
Overcurrent Protection
Relay Type
Protective Relay
IEEE Functions
Metering
DT 520MCV
Amperes
DT-1150V
MVS Load
Break
Switch
2
3
EDR-3000 or
EDR-5000 1
3-CTs
Vacuum
Breaker
50/51
50N/51N
Protective Relay
IEEE Functions
Metering
EDR-3000
50/51; 50/51G
Amperes and
ampere demand
EDR-5000
52
4
2
5
6
1-Zero Sequence CT
9
10
13
Rated
Rated Rated
Maximum BIL
Main Bus
Volts kV
kV
Current
Amperes
4.76
4.76
MVS
Switch
15
15
Phase Current
Sensors
VCP-TR or -TRL
Circuit Breaker
52
11
12
Assembly Ratings
Table 7.2-3. MSB Switchgear Assembly Ratings
Optional Ground
Current Sensor
TA
600, 1200
600, 1200
25
40
CTs
VYs
2 L-L or 3 L-G
Optional Ground
Current Sensor
R = Relay
DT-3010 or EDR-5000
TA
RP
EM
(if TRL
bkr)
Current
Sensors
TA = Trip Actuator
EM = Electromagnetic
Linear Actuator
RP = Rating Plug
ST = Shunt Trip Coil
Max Length = 50 Feet
18
Required if Using
EDR-5000
ST
MVS
Switch
VCP-TR or -TRL
Circuit Breaker 52
40
64
MVS
Switch
TA = Trip Actuator
EM = Electromagnetic
Linear Actuator
RP = Rating Plug
Substation
Transformer
17
20
95
95
Primary Source
Phase Current
Sensors
19
25
40
RP
EM
(if TRL
bkr)
Rated Short-TIme
(2 Seconds)
Current kA
Symmetrical
VCP-TR or -TRL
Circuit Breaker 52
16
Rated
Momentary
Current kA rms
Asymmetrical
60
60
14
15
RP
TA = Trip Actuator
EM = Electromagnetic
Linear Actuator
RP = Rating Plug
21
For more information, visit: www.eaton.com/consultants
CA08104001E
February 2015
7.2-5
Sheet 07 013
Technical Data
Table 7.2-4. Available Type VCP-TR and VCP-TRL Vacuum Circuit Breakers Rated per ANSI Standards
Circuit
Breaker
Type 12
Rated
Insulation Level
Rated
Maximum Power
Continuous
Impulse
Voltage
Frequency Withstand Current
Withstand Voltage
Voltage
(BIL)
60 Hz,
1.2 x 50
1 Minute microsec
Rated
ShortCircuit
Current
at Rated
Maximum
Voltage
Rated
Voltage
Range
Factor
kV rms
50VCP-TR25
50VCP-TRL25
50VCP-TR40
150VCP-TR25
150VCP-TRL25
150VCP-TR40
1
2
4.76
4.76
4.76
15
15
15
Maximum
Symmetrical
Interrupting
& 2-Second
Short-Time
Current
Carrying
Capability
Closing
and
Latching
Capability
(Momentary)
K*I
2.6 * K * I
kA rms sym
kA Crest
Amperes MVA
Vacuum
Interrupter
Mechanism
Cable
Charging
Breaking
Current
kV rms
kV Peak
Amperes
kA rms
sym
19
19
19
60
60
60
600, 1200
600, 1200
600, 1200
25
25
40
1
1
1
25
25
40
65
65
104
25
25
25
210
210
330
30,000
30,000
30,000
10,000
100,000
10,000
36
36
36
95
95
95
600, 1200
600, 1200
600, 1200
25
25
40
1
1
1
25
25
40
65
65
104
25
25
25
650
650
1040
30,000
30,000
30,000
10,000
100,000
10,000
Circuit
Breaker Type
Cable
Charging
VCP-TRC
25 A
(40 kA ratings)
Back-to-Back
ii
1
2
3
4
5
6
7
Rated interrupting time for all VCP-T circuit breakers is 3 cycle (50 ms).
Operating duty for all VCP-T circuit breakers is O-0.3sec-CO-3min-CO.
Time
Seconds
48 Vdc
125 Vdc
250 Vdc
4.0
3.0
2.0
5
5
5
120 Vac
240 Vac
3.0
2.0
5
5
Close or Trip
Amperes
Voltage Range
Close
Trip
10
5.2
3.6
1.8
3856
100140
200280
2856
70140
140180
11
3.6
1.8
104127
208254
104127
208254
12
13
14
15
16
17
18
19
20
21
CA08104001E
7.2-6
February 2015
Sheet 07 014
LayoutDimensions
i
ii
1
2
3
70.00
(1778.0)
Outdoor
95.50
(2425.7)
Indoor
90.38
(2295.7)
6
7
62.00
(1574.8)
62.00
(1574.8)
Outdoor
95.50
(2425.7)
Outdoor
95.50
(2425.7)
PR
Indoor
90.38
(2295.7)
52
52
8
9
Indoor
36.00
(914.4)
20.00
(508.0)
Arrangement 3
Primary for Liquid Filled
Transformer
62.00
(1574.8)
Outdoor
95.50
(2425.7)
Outdoor
95.50
(2425.7)
11
36.00
(914.4)
Arrangement 2
Primary for Dry-Type
Transformer
62.00
(1574.8)
10
52
Outdoor
41.00
(1041.4)
36.00
(914.4)
Arrangement 1
Single Unit,
Cable In and Out
PR
Indoor
90.38
(2295.7)
PR
Indoor
90.38
(2295.7)
PR
Indoor
90.38
(2295.7)
PR
52
52
PR
PR
PR
52
52
52
36.00
(914.4)
36.00
(914.4)
36.00
(914.4)
12
36.00 - 48.00
(914.4 - 1219.2)
13
36.00
(914.4)
15.00
(381.0)
36.00
(914.4)
36.00 - 48.00
(914.4 - 1219.2)
36.00
(914.4)
Arrangement 6
Main Lugs with Feeders; Metering Section (Optional) 1
Arrangement 5
Main Device with Feeders; Metering Section (Optional) 1
14
62.00
(1574.8)
62.00
(1574.8)
15
Outdoor
95.50
(2425.7)
Outdoor
95.50
(2425.7)
16
Indoor
ATC
90.38
(2295.7)
17
PR
52
PR
Indoor
90.38
(2295.7)
PR
52
PR
52
52
52
36.00
(914.4)
36.00
(914.4)
ATC
18
36.00
(914.4)
19
20
21
36.00
(914.4)
15.00
(381.0)
36.00
(914.4)
36.00
(914.4)
Arrangement 7
Two Breaker Auto TransferSingle Load
15.00
(381.0)
36.00
(914.4)
15.00
(381.0)
15.00
(381.0)
36.00
(914.4)
Arrangement 8
Three Breaker Auto TransferMain-Tie-Main with Feeders
Note: PROvercurrent protective relay, typical functions50/51, 50/51N or 50/51G. Eatons EDR-3000 or EDR-5000.
Dimensions in inches (mm). Not to be used for construction purposes unless approved.
For more information, visit: www.eaton.com/consultants
CA08104001E
February 2015
7.2-7
Sheet 07 015
LayoutDimensions
10.00 (254.0)
10.00 (254.0)
Optional
Rear Door
1.50 (38.1)
8.00 (203.2)
1.25 (31.8)
ii
1
A&B
Roof Layout
95.46
(2424.7)
Outdoor
Height
16.00 (406.4)
VT
Switch
CT
36.00 (914.4)
90.37
(2295.3)
Indoor
Height
4
10.00 (254.0)
Optional
Rear Door
6.60 (167.6)
8.00 (203.2)
Vacuum
Breaker
16.00 (406.4)
10.00 (254.0)
1.25 (31.8)
A&B
Floor Layout
5
6
7
62.00
(1574.8)
36.00 (914.4)
Minimum depth 70.00 inches (1778.0 mm) if two sets of CTs are required.
VT cannot be located
here when using
40 kA breaker
Roof for
Outdoor Unit
8
9
10
11
VT
12
13
95.46
(2424.7)
Outdoor
Height
90.37
(2295.3)
Indoor
Height
Switch
14
CT
15
Vacuum
Breaker
16
17
18
19
Minimum depth 80.00 inches (2032.0 mm) if two sets of CTs are required.
20
Dimensions in inches (mm).
Not to be used for construction purposes unless approved.
CA08104001E
21
7.2-8
February 2015
Sheet 07 016
LayoutDimensions
a Locations for tie-down 0.65 inches
(16.5 mm) diameter holes for
four places. Customer provided
bolts for anchoring should be
0.5013 min. (M12 x 1.75 min.
CL 10.9) and tightened to 75 ft-lbs
(101.7 Nm).
i
ii
5
1
2
5.00
(127.0)
Typ.
Optional
Rear Door
4.25
(108.0)
1.25
(31.8)
2.95
(74.9)
3
4
6.00
(152.4)
Min.
6.00
(152.4)
Min.
5
1.25
(31.8)
4.25
(108.0)
FRONT DOOR
4
Min.
8
9
10
11
12
Indoor
Outdoor
MSB section
MVS section (non-fused)
Fuses (three) add
Transition section
1700 (773)
1500 (681)
200 (91)
300 (136)
2000 (909)
1800 (817)
200 (91)
13
14
15
16
17
18
19
20
21
CA08104001E
Vacuum Breakers
February 2015
7.3-1
Sheet 07 017
Application Examples
Application Examples
ii
52-1
1
2
Unprotected
Zone for
Ground
Fault
Protection
R
251G
251G 151G
5
Complete Secondary Ground
Fault Protection Using WVB
for Primary Device
Figure 7.3-1. Low Resistance Ground Scheme (Phase and Primary Ground Fault Protection not Shown)
50/51
50N/51N
DT 520MCV
DT 1150V
EDR-3000
or EDR-5000 1
6
7
8
9
10
52
11
52-2
52-2
EDR-3000
or EDR-5000 1
50/51
50N/51N
12
Figure 7.3-2. Single-Ended Unit Substations Using Primary Breaker Protection (MEB)
1
13
14
15
16
17
50/51
50N/51N
EDR-3000
or EDR-5000 1
52
50/51
50N/51N
DT-520MCV
or DT-1150V
18
19
20
Figure 7.3-3. Single-Ended Unit Substations Using Primary Breaker Protection (MSB)
1
CA08104001E
21
7.3-2
Vacuum Breakers
February 2015
Sheet 07 018
i
ii
1
2
3
4
5
6
7
8
9
10
Surge Arresters
IEEE Standard C62.11 for metal-oxide
surge arresters lists the maximum
rated ambient temperature as 40 C.
The ambient temperature inside an
MEB and MSB switchgear vertical
section may exceed this temperature,
especially in outdoor applications
Table 7.3-1. Suggested Minimum Ratings (kV) for Metal-Oxide Surge Arresters Located in Metal-Enclosed Switchgear
Service
Voltage
Line-to-Line
kV
Low Resistance
Grounded System
High Resistance or
Solidly
Ungrounded System Grounded System
Nominal
Nominal
Arrester Ratings kV
Nominal
MCOV
Low Resistance
Grounded System
High Resistance or
Ungrounded System
Nominal
Nominal
Arrester Ratings kV
MCOV
MCOV
Nominal
MCOV
MCOV
MCOV
2.30
2.40
3.30
3
3
3
2.55
2.55
2.55
3
3
3
2.55
2.55
2.55
3
6
6
2.55
5.10
5.10
3
3
3
2.55
2.55
2.55
3
3
3
2.55
2.55
2.55
3
6
6
2.55
5.10
5.10
4.00
4.16
4.76
3
6
6
2.55
5.10
5.10
6
6
6
5.10
5.10
5.10
6
6
9
5.10
5.10
7.65
3
6
6
2.55
5.10
5.10
6
6
6
5.10
5.10
5.10
6
6
9
5.10
5.10
7.65
4.80
6.60
6.90
6
6
6
5.10
5.10
5.10
6
6
6
5.10
5.10
5.10
9
9
9
7.65
7.65
7.65
6
6
6
5.10
5.10
5.10
6
6
9
5.10
5.10
7.65
9
9
9
7.65
7.65
7.65
7.20
8.32
8.40
6
9
9
5.10
7.65
7.65
6
9
9
5.10
7.65
7.65
10
12
12
8.40
10.20
10.20
6
9
9
5.10
7.65
7.65
9
9
9
7.65
7.65
7.65
10
12
12
8.40
10.20
10.20
11.00
11.50
12.00
9
9
10
7.65
7.65
8.40
9
10
10
7.65
8.40
8.40
15
18
18
12.70
15.30
15.30
9
9
10
7.65
7.65
8.40
10
12
12
8.40
10.20
10.20
15
18
18
12.70
15.30
15.30
12.47
13.20
13.80
10
12
12
8.40
10.20
10.20
12
12
12
10.20
10.20
10.20
18
18
18
15.30
15.30
15.30
10
12
12
8.40
10.20
10.20
12
12
15
10.20
10.20
12.70
18
18
18
15.30
15.30
15.30
14.40
12
10.20
12
10.20
21
17.00
12
10.20
15
12.70
21
17.00
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
Vacuum Breakers
February 2015
7.3-3
Sheet 07 019
ATC Controller
Eatons ATC-900 controller is equipped
to display history information either
via the front panel or over the
PowerNet power monitoring system.
ATC-900 controller stores 320 time
stamped events. Oscillographic data
for last 10 events can be downloaded
via USB port or displayed in the
controllers display window. Controller allows communications via RS-232
or Modbus through RS-458 port,
Ethernet or via USB interface.
ATC Controller
Standard Features
Typical Three-Breaker
(Two Mains and Normally Open Tie)
Automatic Transfer Control
The automatic transfer switchgear
assembly includes two main breakers
and one tie breaker, and an integrated
automatic transfer control system
containing sensing devices, low
voltage logic control and auxiliary
equipment. The transfer control
system monitors both sources for
correct voltages. An automatic-manual
transfer selector switch is provided
for selection of manual or automatic
operating mode. In manual mode,
all three breakers can be manually
operated. Interlocking is provided in
manual mode of operation to prevent
closing all three breakers at the same
time. In the automatic mode, the basic
sequence of operation based upon two
normally energized sources is carried
out as follows. Normal operation is
with the main breakers closed and the
tie breaker open. Upon detection of
an undervoltage(s) to the line side
of a main breaker, and after a fieldadjustable time delay, that main
breaker opens and after an additional
field-adjustable time delay, the tie
breaker closes to restore power to the
affected portion of the facility. Upon
restoration of voltage to the line side
of the main breaker, and after a fieldadjustable time delay, the tie breaker
opens and after a field-adjustable time
delay, the opened main breaker closes.
Interlocking is provided to prevent
closing all three breakers simultaneously in manual mode.
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Optional Features
17
18
19
20
21
CA08104001E
7.3-4
Vacuum Breakers
February 2015
Sheet 07 020
i
ii
Partial Discharge
Sensing and Monitoring
for Switchgear
1
2
3
4
Coupling Capacitor
Type PD Sensor
RFCT Sensor
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
InsulGard Relay
(PD Monitoring)
Temp Sensor
Humidity Sensor
Input
Terminal
Block
InsulGard
Relay
120 Vac
Auxiliary
Power
Optional
Modem
Output
Alarm
Status
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
Vacuum Breakers
7.3-5
Sheet 07 021
i
ii
1
2
3
4
5
6
7
8
9
10
Note: Use one set of epoxy bottles with ground stress shield on bus
side (either in the top or bottom compartment) at every two vertical
sections. Use standard bottles at all other locations.
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
7.3-6
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E