DVC6200f Instruction Manual
DVC6200f Instruction Manual
DVC6200f Instruction Manual
D103412X012
www.Fisher.com
August 2012
The FIELDVUE DVC6200f Digital Valve Controller is a core component of the PlantWeb digital
plant architecture. The digital valve controller powers PlantWeb by capturing and delivering valve
diagnostic data. Coupled with ValveLink software, the DVC6200 provides users with an accurate
picture of valve performance, including actual stem position, instrument input signal, and
pneumatic pressure to the actuator. Using this information, the digital valve controller diagnoses
not only itself, but also the valve and actuator to which it is mounted.
Instruction Manual
D103412X012
August 2012
Contents
Section 1 Introduction and
Specifications . . . . . . . . . . . . . . . . . . . . . . 3
Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Instrument Description . . . . . . . . . . . . . . . . . . . . . . . . 3
Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Educational Services . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Section 2 Installation . . . . . . . . . . . . . . . . . 11
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DVC6200f Digital Valve Controller . . . . . . . . . . . . .
DVC6205f Base Unit . . . . . . . . . . . . . . . . . . . . . . . .
DVC6215 Feedback Unit . . . . . . . . . . . . . . . . . . . . .
SlidingStem Linear Actuators up to
210 mm (8.25 Inches) Travel . . . . . . . . . . .
Fisher Rotary Actuators and SlidingStem
Linear Actuators over 210 mm
(8.25 Inches) Travel . . . . . . . . . . . . . . . . . . .
GX Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . .
QuarterTurn Rotary Actuators . . . . . . . . . . . .
Fisher 67CFR Filter Regulator . . . . . . . . . . . . . . . . .
Pneumatic Connections . . . . . . . . . . . . . . . . . . . . . . .
Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Connection . . . . . . . . . . . . . . . . . . . . . .
Special Construction to Support
Solenoid Valve Testing . . . . . . . . . . . . . . . .
Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring and Electrical Connections . . . . . . . . . . . . . .
Connecting Fieldbus Wiring . . . . . . . . . . . . . . . . . .
TwistedShielded Pair . . . . . . . . . . . . . . . . . . . .
Quick Connect Cable Entry . . . . . . . . . . . . . . .
Remote Travel Sensor Connections . . . . . . . . . . . .
Communication Connections . . . . . . . . . . . . . . . . .
Simulate Enable Jumper . . . . . . . . . . . . . . . . . . . . . . .
Commissioning Tag . . . . . . . . . . . . . . . . . . . . . . . . . .
11
11
11
14
16
18
20
22
25
26
26
26
27
28
29
30
31
31
32
33
34
36
36
27
W9713_fieldbus
145
160
171
183
189
201
213
213
214
214
215
216
217
View Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . .
Device Variables . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . .
Device Variables . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Analog Output Function Block . . . . . . . . . . . . . . . . 113
Proportional/Integral/Derivative
Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Block Mode . . . . . . . . . . . . . . . . . . . . . .
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performance Tuner . . . . . . . . . . . . . . . . . . . . . . . . .
39
39
39
40
44
219
219
220
222
223
224
229
Instruction Manual
Component Replacement . . . . . . . . . . . . . . . . . . .
Removing the Module Base . . . . . . . . . . . . . . . . .
Replacing the Module Base . . . . . . . . . . . . . . . . . .
Submodule Maintenance . . . . . . . . . . . . . . . . . . . . .
I/P Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Printed Wiring Board (PWB) Assembly . . . . . . . . .
Pneumatic Relay . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gauges, Pipe Plugs or Tire Valves . . . . . . . . . . . . .
Terminal Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the Terminal Box . . . . . . . . . . . . . . . . .
Replacing the Terminal Box . . . . . . . . . . . . . . . . .
Stroking the Digital Valve Controller Output . . . . .
DVC6215 Feedback Unit . . . . . . . . . . . . . . . . . . . . .
Instrument Troubleshooting . . . . . . . . . . . . . . . . . .
D103412X012
235
235
236
237
237
239
240
241
241
241
242
242
242
243
249
249
250
250
250
250
251
251
251
252
252
275
275
275
277
277
277
277
288
288
288
289
290
291
291
291
292
292
293
293
293
294
294
295
296
296
297
298
298
300
301
303
304
309
310
310
310
312
312
315
315
315
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
Instruction Manual
D103412X012
August 2012
Note
All references to the DVC6200f digital valve controller include the DVC6205f base unit unless otherwise indicated.
This manual describes device setup using the 475 or 375 Field Communicator. For information on using Fisher
ValveLink software with the instrument, refer to the appropriate user guide or help.
Do not install, operate, or maintain a DVC6200f digital valve controller without being fully trained and qualified in
valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage,
it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions
and warnings. If you have any questions about these instructions, contact your Emerson Process Management sales
office before proceeding.
Instrument Description
DVC6200f digital valve controllers for FOUNDATION fieldbus are communicating, microprocessorbased instruments.
In addition to the traditional function of converting a digital signal to a pneumatic output pressure, the DVC6200f
digital valve controller, using FOUNDATION fieldbus communications protocol, gives easy access to information critical to
process operation as well as process control. This can be done using a DeltaV console, another FOUNDATION fieldbus
system console, or with ValveLink software version 10.2 or later.
Using a compatible fieldbus configuration device, you can obtain information about the health of the instrument, the
actuator, and the valve. You can also obtain asset information about the actuator or valve manufacturer, model, and
serial number. You can set input and output configuration parameters and calibrate the instrument.
Using the FOUNDATION fieldbus protocol, information from the instrument can be integrated into control systems.
DVC6200f digital valve controllers can be mounted on single or doubleacting slidingstem actuators, as shown in
figure 12, or on rotary actuators. It can also be integrally mounted to the Fisher GX control valve and actuator system,
as shown in figure 13. The DVC6200f mounts on most Fisher and other manufacturers' rotary and slidingstem
actuators.
Instruction Manual
D103412X012
W9616_fieldbus
W9643_fieldbus
DVC6200f digital valve controllers are available with several selections of control and diagnostic capability. Control
selections include:
Standard Control (SC) Digital valve controllers with Standard Control have the AO, PID, ISEL, OS, AI, MAI, DO, and
four DI function blocks in addition to the resource and transducer blocks.
Fieldbus Control (FC)Digital valve controllers with Fieldbus Control have the AO function block in addition to the
resource and transducer blocks.
Fieldbus Logic (FL)Digital valve controllers with Fieldbus Logic have the DO, and four DI function blocks, in
addition to the resource and transducer block.
The diagnostic capabilities include:
Performance Diagnostics (PD)
Advanced Diagnostics (AD)
Fieldbus Diagnostics (FD)
Performance and Advanced Diagnostics are available with ValveLink software. They provide visibility to instrument
alerts. Fieldbus Diagnostics can be viewed with any host system.
Instruction Manual
D103412X012
August 2012
Instrument Blocks
The digital valve controller is a blockbased device. For detailed information on the blocks within the digital valve
controller, see the Detailed Setup section of this manual.
The DVC6200f digital valve controller includes the resource and transducer block:
Resource BlockThe resource block contains the hardware specific characteristics associated with a device; it has
no input or output parameters. The resource block monitors and controls the general operation of other blocks
within the device. For example, when the mode of the resource block is Out of Service, it impacts all function
blocks.
Transducer BlockThe transducer block connects the analog output function block to the I/P converter, relay, and
travel sensor hardware within the digital valve controller.
Function Blocks
In addition to the resource and transducer block, the digital valve controller may contain the following function blocks.
For additional information on function blocks, refer to Appendix D, FOUNDATION fieldbus Communication.
Analog Output (AO) Function BlockThe analog output function block accepts the output from another function
block (such as a PID block) and transfers it as an actuator control signal to the transducer block. If the DO block is
selected, the AO block is not functional.
ProportionalIntegralDerivative (PID) Function BlockThe PID function block performs
proportionalplusintegralplusderivative control.
Input Selector (ISEL) Function BlockThe input selector function block selects from up to four inputs and may
provide the selected signal as input to the PID block. The input selection can be configured to select the first good
input signal; a maximum, minimum or average value; or a hot spare.
Output Splitter (OS) Function BlockThe output splitter function block accepts the output from another function
block (such as a PID block) and creates two outputs that are scaled or split, according to the user configuration. This
block is typically used for split ranging of two control valves.
Analog Input (AI) Function BlockThe analog input function block monitors the signal from a DVC6200f sensor or
internal measurement and provides it to another block.
Multiple Analog Input (MAI) Function BlockThe Multiple Analog Input (MAI) function block has the ability to
process up to eight DVC6200f measurements and make them available to other function blocks.
Discrete Output (DO) Function BlockThe discrete output function block processes a discrete set point and sends it
to a specified output channel, which can be transferred to the transducer block for actuator control. In the digital
valve controller, the discrete output block provides both normal open/closed control and the ability to position the
valve in 5% increments for course throttling applications. If the AO block is selected, the DO block is not functional.
Discrete Input (DI) Function BlockThe discrete input function block processes a single discrete input from a
DVC6200f and makes it available to other function blocks. In the digital valve controller, the discrete input function
block can provide limit switch functionality and valve position proximity detection.
Instruction Manual
D103412X012
An overview of the resource and transducer block menu structures are shown in Appendix B. Menu structures for the
function blocks are included with each function block section in Detailed Setup.
Throughout this document, parameters are typically referred to by their common name or label, followed by the
parameter name and index number; for example, Write Priority (WRITE_PRI [39]). However, not all interface systems
support the use of the parameter label and instead use only the Parameter Name, followed by the index number, when
referring to the block parameters.
Specifications
Specifications for the DVC6200f digital valve controller are shown in table 11.
Instruction Manual
D103412X012
August 2012
AI Block: 15 ms
MAI BLock: 35 ms
DO Block: 15 ms
DI Block: 15 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
Digital Communication Protocol
FOUNDATION fieldbus registered device
Physical Layer Type(s):
121Low-power signaling, buspowered,
Entity Model I.S.
511Low-power signaling, buspowered, FISCO I.S.
Instruction Manual
D103412X012
Electrical Housing
CSA Type 4X, IP66
FM NEMA 4X
ATEX IP66
IECEx IP66
The Gas Certified DVC6200f is CSA, FM, ATEX, and
IECEx approved for use with natural gas as the supply
medium
Independent Linearity(5)
Typical Value: 0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
ImmunityIndustrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 12 below.
EmissionsClass A
ISM equipment rating: Group 1, Class A
Lightning and Surge ProtectionThe degree of
immunity to lightning is specified as Surge immunity
in table 12. For additional surge protection
commercially available transient protection devices
can be used.
Vibration Testing Method
Tested per ANSI/ISA75.13.01 Section 5.3.5. A
resonant frequency search is performed on all three
axes. The instrument is subjected to the ISA specified
1/2 hour endurance test at each major resonance.
Other Classifications/Certifications
INMETRO Brazil
KGS Korea
NEPSI China
TIIS Japan
Contact your Emerson Process Management sales
office for classification/certification specific
information
Connections
Supply Pressure: 1/4 NPT internal and integral pad for
mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Tubing: 3/8inch recommended
Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal, M20 adapter optional
Actuator Compatibility
Instruction Manual
D103412X012
August 2012
Construction Materials
Housing, module base and terminal box: A03600 low
copper aluminum alloy (standard)
Stainless steel (optional)
Cover: Thermoplastic polyester
Elastomers: Nitrile (standard)
Fluorosilicone (extreme temperature)
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 / 23 /
EC. It was designed and manufactured in accordance
with Sound Engineering Practice (SEP) and cannot
bear the CE marking related to PED compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
Options
Supply and output pressure gauges or Tire
valves Integral mounted filter regulator
LowBleed Relay Extreme Temperature
Natural Gas Certified Remote Mount
Stainless Steel
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
2. Normal m3/hour - Normal cubic meters per hour at 0C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60F and 14.7 psia.
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Temperature limits vary based on hazardous area approval.
5. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long-stroke applications.
Enclosure
Basic Standard
IEC 6100042
4 kV contact
8 kV air
Radiated EM field
IEC 6100043
IEC 6100048
30 A/m at 50/60 Hz
Test Level
Performance
Criteria(1)
Phenomenon
A(2)
A(2)
IEC 6100044
1 kV
Surge
IEC 6100045
1 kV
Conducted RF
IEC 6100046
Instruction Manual
August 2012
D103412X012
Related Information
Fieldbus Installation and Wiring Guidelines
This manual describes how to connect the fieldbus to the digital valve controller. For a technical description, planning,
and installation information for a FOUNDATION fieldbus, refer to the FOUNDATION fieldbus Technical Overview available
from the Fieldbus Foundation and Fieldbus Installations in a DeltaV System available from your Emerson Process
Management sales office.
Related Documents
Other documents containing information related to the DVC6200f digital valve controller include:
Bulletin 62.1:DVC6200fFisher FIELDVUE DVC6200f Digital Valve Controller (D103399X012)
Bulletin 62.1:DVC6200f FDFisher FIELDVUE DVC6200f Digital Valve Controller (D103422X012)
Bulletin 62.1:DVC6200(S1)Fisher FIELDVUE DVC6200 Digital Valve Controller Dimensions (D103543X012)
Fisher FIELDVUE DVC6200 Series Quick Start Guide (D103556X012)
475 Field Communicator User's Manual
ValveLink Software Help or Documentation
All documents are available from your Emerson Process Management sales office. Also visit our website at
www.FIELDVUE.com.
Educational Services
For information on available courses for the DVC6200f digital valve controller, as well as a variety of other products,
contact:
Emerson Process Management
Educational Services, Registration
P.O. Box 190; 301 S. 1st Ave.
Marshalltown, IA 50158-2823
Phone: 800-338-8158 or
Phone: 641-754-3771
FAX: 641-754-3431
email: education@emerson.com
10
Instruction Manual
Installation
D103412X012
August 2012
Section 2 Installation2-2Installation
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before proceeding
with any Installation procedures:
Always wear protective clothing, gloves, and eyewear to prevent personal injury or property damage.
If installing into an existing application, also refer to the WARNINGS at the beginning of the Maintenance section of this
instruction manual.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.
Refer to the quick start guide that ships with the instrument (D103556X012) for Hazardous Area Approvals and Special
Instructions for Safe Use and Installations in Hazardous Locations.
Mounting
DVC6200f Digital Valve Controller
The DVC6200f housing is available in two different configurations, depending on the actuator mounting method.
Figure 21 shows the available configurations.
Figure 21. Housing Configurations
HOUSING FOR
LINEAR AND ROTARY ACTUATORS
HOUSING FOR
FISHER GX ACTUATORS
INTEGRAL OUTPUT
PRESSURE PORT
ROTARY NAMUR, M6
LINEAR, M8
W9703
W9704
SLOTS FOR
MOUNTING BOLTS
HOLE FOR
MOUNTING BOLT
11
Installation
Instruction Manual
August 2012
D103412X012
The feedback system for the DVC6200f digital valve controller utilizes a magnetic assembly for linkageless,
noncontacting position measurement. In order to prevent inadvertent stem movement while the instrument is in
operation, magnetic tools (such as a magnetictipped screwdriver) should not be used.
Note
The magnet assembly may be referred to as a magnetic array in user interface tools.
CAUTION
The magnet assembly material has been specifically chosen to provide a longterm stable magnetic field.
However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet
placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment
include, but are not limited to: transformers, DC motors, stacking magnet assemblies.
CAUTION
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless
of the positioner model, high power magnets can affect the positioners ability to control the valve. Technicians should
avoid the use of high power magnets in close proximity with any positioner.
Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6200f housing) has to remain within this range throughout the entire valve travel. See figure 22. The
linear magnet assemblies are symmetrical. Either end may be up.
12
Instruction Manual
Installation
D103412X012
August 2012
MAGNET ASSEMBLY
(ATTACHED TO VALVE STEM)
INDEX MARK
W9706
Note
Mounting the instrument vertically, with the vent at the bottom of the assembly, or horizontally, with the vent pointing down, is
recommended to allow drainage of moisture that may be introduced via the instrument air supply.
There are a variety of mounting brackets and kits that are used to mount the DVC6200f to different actuators.
Depending on the actuator, there will be differences in fasteners, brackets, and connecting linkages.
Each mounting kit will include one of the magnet assemblies illustrated in figure 23.
Figure 23. Magnet Assemblies
RSHAFT END
ASSEMBLY 90 DEG
AVAILABLE CONSTRUCTIONS:
SSTEM #7 ASSEMBLY (7 mm / 1/4 INCH)
SSTEM #19 ASSEMBLY (19 mm / 3/4 INCH)
SSTEM #25 ASSEMBLY (25 mm / 1 INCH)
AVAILABLE CONSTRUCTIONS:
SSTEM #38 ASSEMBLY (38 mm / 11/2 INCH)
SSTEM #50 ASSEMBLY (50 mm / 2 INCH)
SSTEM #100 ASSEMBLY (100 mm / 4 INCH)
SSTEM #210 ASSEMBLY (210 mm / 8-1/4 INCH)
AVAILABLE CONSTRUCTIONS:
SSTEM #1 ROLLER ASSEMBLY
RSHAFT #1 WINDOW ASSEMBLY
(FISHER 2052 SIZE 2 & 3, 1051/1052
SIZE 4070, 1061 SIZE 30100,
SLIDINGSTEM > 210 mm (8.25 INCHES)
RSHAFT #2 WINDOW ASSEMBLY
(2052 SIZE 1, 1051/1052 SIZE 20-33)
If ordered as part of a control valve assembly, the factory will mount the digital valve controller on the actuator and
calibrate the instrument. If purchased separately, you will need a mounting kit to mount the digital valve controller on
the actuator. Each mounting kit includes detailed information on mounting the digital valve controller to a specific
actuator. Refer to table 21 for the more common Fisher actuator mounting instructions, available at www.fisher.com
or your Emerson Process Management sales office.
13
Instruction Manual
Installation
August 2012
D103412X012
For general mounting guidelines, refer to the DVC6200 Series quick start guide (D103556X012), available at
www.fisher.com or your Emerson Process Management sales office.
Part Number
D103439X012
D103440X012
D103441X012
D103442X012
657 and 667 Size 70, 76, and 87 Actuators (up to 2 inch travel)
D103443X012
657 and 667 Size 70, 76, and 87 Actuators (4 inch travel)
D103444X012
D103445X012
D103446X012
D103447X012
D103448X012
D103449X012
D103450X012
D103451X012
D103453X012
D103452X012
D103454X012
D103455X012
D103456X012
D103457X012
D103458X012
D103459X012
Wall Mounting
Refer to figures 24 and 25. Drill two holes in the wall using the dimensions shown in figure 24. Attach the mounting
bracket to the base unit using four spacers and 25.4 mm (1inch) 1/420 hex head screws. Attach the base unit to the
wall using suitable screws or bolts.
Pipestand Mounting
Refer to figure 26. Position a standoff on the back of the base unit. Using two 101.6 mm (4inch) 1/420 hex head
screws loosely attach the base unit to the pipestand with the mounting bracket. Position the second standoff, then
using the remaining 101.6 mm (4inch) hex head screws, securely fasten the base unit to the pipe stand.
14
Instruction Manual
Installation
D103412X012
August 2012
Figure 24. FIELDVUE DVC6205f Base Unit with Mounting Bracket (Rear View)
10C1796A
4INCH 1/420
HEX HEAD SCREW
STANDOFF
MOUNTING BRACKET
X0437
15
Instruction Manual
Installation
August 2012
D103412X012
SPACER
1INCH 1/420
HEX HEAD
SCREW
MOUNTING BRACKET
X0428
HOUSING FOR
FISHER GX ACTUATORS
INTEGRAL OUTPUT
PRESSURE PORT
X0124
16
LINEAR, M8
ROTARY NAMUR, M6
X0125
HOLES FOR
MOUNTING BOLT
Instruction Manual
Installation
D103412X012
August 2012
CAUTION
The magnet assembly material has been specifically chosen to provide a longterm stable magnetic field.
However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet
placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment
include, but are not limited to: transformers, DC motors, stacking magnet assemblies.
CAUTION
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless
of the positioner model, high power magnets can affect the positioners ability to control the valve. Technicians should
avoid the use of high power magnets in close proximity with any positioner.
Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6215 housing) has to remain within this range throughout the entire valve travel. See figure 28. The linear
magnet assemblies are symmetrical. Either end may be up.
MAGNET ASSEMBLY
(ATTACHED TO VALVE STEM)
INDEX MARK
X0126
17
Installation
August 2012
Instruction Manual
D103412X012
There are a variety of mounting brackets and kits that are used to mount the DVC6215 to different actuators.
Note
The DVC6215 feedback unit uses the same mountings as the DVC6200f digital valve controller.
However, despite subtle differences in fasteners, brackets, and connecting linkages, the procedures for mounting can
be categorized as follows:
Slidingstem linear actuators
Fisher rotary actuators
GX actuator
Quarterturn actuators
See figure 23 for examples of the different travel feedback magnet assemblies.
X0127
18
Instruction Manual
Installation
D103412X012
August 2012
3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the DVC6215 housing.
4. Using the alignment template (supplied with the mounting kit), position the magnet assembly inside the retaining
slot.
5. Align the magnet assembly as follows:
For airtoopen actuators (e.g. Fisher 667) vertically align the magnet assembly so that the center line of the alignment
template is lined up as close as possible with the upper extreme of the valid travel range on the magnet assembly. The
magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within
the valid range on the magnet assembly throughout the range of travel. See figure 210.
For airtoclose actuators (e.g. Fisher 657) vertically align the magnet assembly so that the center line of the alignment
template is lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly. The
magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within
the valid range on the magnet assembly throughout the range of travel. See figure 211.
Figure 210. AirtoOpen Magnet Assembly
Alignment
ALIGNMENT
TEMPLATE
RETAINING
SLOT
INDEX
MARK
W9718
RETAINING
SLOT
ALIGNMENT
TEMPLATE
INDEX
MARK
W9719
19
Instruction Manual
Installation
August 2012
D103412X012
8. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
Note
Ensure that there is clearance between the magnet assembly and the DVC6215 housing slot throughout the full range of travel.
Fisher Rotary Actuators and SlidingStem Linear Actuators over 210 mm (8.25 Inches) Travel
The DVC6215 feedback unit uses a cam (designed for linear response) and roller as the feedback mechanism. See
figures 212 and 213.
Figure 212. Mounting on Rotary Actuators
MOUNTING
ADAPTOR
ROTARY MOUNTING
KIT (DVC6215 NOT
SHOWN)
LONG STROKE
MOUNTING
KIT (DVC6215
NOT SHOWN)
W9709
W9708
Note
All cams supplied with FIELDVUE mounting kits are characterized to provide a linear response.
There are three different mounting adaptions, based on the actuator design (see figure 214).
20
Instruction Manual
Installation
D103412X012
August 2012
2. Verify that the appropriate cam is installed on the actuator as described in the instructions included with the
mounting kit.
3. Mount the DVC6215 on the actuator as follows:
If required, a mounting adaptor is included in the mounting kit. Attach the adaptor to the feedback unit, then
attach the feedback unit assembly to the actuator. The roller on the feedback arm will contact the actuator cam
as it is being attached.
If no mounting adaptor is required, attach the feedback unit and mounting kit assembly to the actuator. The
roller on the feedback arm will contact the actuator cam as it is being attached.
Figure 214. Mounting Variations
ROLLER
ARM
VARIATION A
VARIATION
ROLLER
ARM
ROLLER
ARM
VARIATION B
VARIATION C
ACTUATOR
2052 Size 2 and 3
1051/1052 size 40-70
1061 Size 30-100
SlidingStem > 210 mm (8.25 inches)
B
C
2052 Size 1
1052 Size 20-33
1051 Size 33
NOTE THE DIFFERENCE IN THE SHAPE AND LENGTH OF THE ROLLER ARM
E1229
21
Installation
August 2012
Instruction Manual
D103412X012
GX Actuators
The DVC6215 feedback unit mounts directly on the GX actuator without the need for a mounting bracket.
Identify the yoke side to mount the DVC6215 feedback unit based on the actuator fail mode. Refer to the GX Control
Valve and Actuator System instruction manual (D103175X012).
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lockout procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.
CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the DVC6215 housing.
3. Using the alignment template (supplied with the mounting kit), position the feedback assembly inside the retaining
slot.
4. Align the magnet assembly as follows:
For airtoopen GX actuators vertically align the magnet assembly so that the center line of the alignment template is
lined up as close as possible with the upper extreme of the valid travel range on the magnet assembly. The magnet
assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within the valid
range on the magnet assembly throughout the range of travel. See figure 215.
For airtoclose GX actuators vertically align the magnet assembly so that the center line of the alignment template is
lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly. The magnet
assembly should be positioned so that the index mark on the pole pieces (back of the DVC6215 housing) is within the
valid range on the magnet assembly throughout the range of travel. See figure 216.
22
Instruction Manual
Installation
D103412X012
August 2012
ALIGNMENT TEMPLATE
ALIGNMENT TEMPLATE
RETAINING
SLOT
INDEX MARK
W9218
RETAINING
SLOT
INDEX MARK
W9219
5. Tighten the fasteners and remove the alignment template. Continue on with the appropriate step 6 below.
AirtoOpen GX Actuators
6. The pneumatic output port on the DVC6215 lines up with the integral GX actuator pneumatic port. See figure 217.
7. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad on the side that has the open
pneumatic port. Be sure to place the Oring between the feedback units pneumatic output and the actuator
mounting pad. Pneumatic tubing between the feedback unit and the actuator is not required because the air
passages are internal to the actuator.
8. Connect the pneumatic tubing from the DVC6205f to the feedback units pneumatic port provided on the front of
the DVC6215 as shown in figure 217.
9. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
10. If not already installed, install a vent in the port on the upper diaphragm casing's air supply connection on the
actuator yoke leg.
23
Instruction Manual
Installation
August 2012
D103412X012
PNEUMATIC
PORT
PNEUMATIC TUBING
FROM THE DVC6205f
INSTALL
ORING
X0128
AirtoClose GX Actuators
6. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad.
7. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
8. Install tubing between the actuator casing and the appropriate DVC6215 pneumatic output port.
9. If not already installed, install a vent in the port on the lower diaphragm casing.
Note
To convert to air-to-open, install an Oring between the feedback units pneumatic output and the actuator mounting pad.
Connect pneumatic tubing from the DVC6205f to the DVC6215. Refer to figure 217.
To convert to air-to-close, remove the Oring between the feedback units pneumatic output and the actuator mounting pad.
Disconnect the pneumatic tubing from the DVC6205f to the DVC6215. Install tubing between the pneumatic output connection
of the DVC6205f to the pneumatic port on top of the actuator casing.
24
Instruction Manual
Installation
D103412X012
August 2012
ORIENTATION
AT MIDTRAVEL
(FLATS PARALLEL
TO DVC6215
CHANNEL)
M6 MOUNTING
BOLTS (4)
X0129
ORIENTATION
AT THE OTHER
TRAVEL EXTREME
25
Instruction Manual
Installation
August 2012
D103412X012
IntegralMounted Regulator
Refer to figure 220. Lubricate an Oring and insert it in the recess around the SUPPLY connection on the digital valve
controller. Attach the 67CFR filter regulator to the side of the digital valve controller. Thread a 1/4inch sockethead
pipe plug into the unused outlet on the filter regulator. This is the standard method of mounting the filter regulator.
Figure 220. Mounting the Fisher 67CFR Regulator on a FIELDVUE DVC6200f Digital Valve Controller
67CFR
CAP SCREWS
ORING
NOTE:
1 APPLY LUBRICANT
SUPPLY CONNECTION
W9702-fieldbus
YokeMounted Regulator
Mount the filter regulator with two cap screws to the predrilled and tapped holes in the actuator yoke. Thread a
1/4inch sockethead pipe plug into the unused outlet on the filter regulator. No Oring is required.
CasingMounted Regulator
Use the separate 67CFR filter regulator casing mounting bracket provided with the filter regulator. Attach the
mounting bracket to the 67CFR and then attach this assembly to the actuator casing. Thread a 1/4inch sockethead
pipe plug into the unused outlet on the filter regulator. No Oring is required.
Pneumatic Connections
Pressure
Pressure connections are shown in figure 221. All pressure connections on the digital valve controller are 1/4 NPT
internal connections. Use at least10 mm (3/8inch) tubing for all pressure connections. If remote venting is required a
minimum of 12.7 mm (1/2inch) tubing should be used. Refer to the vent subsection for remote venting information.
26
Instruction Manual
Installation
D103412X012
August 2012
WIRING
TERMINAL BOX
OUTPUT A
CONNECTION
SUPPLY
CONNECTION
X0379-fieldbus
FEEDBACK CONNECTIONS
TERMINAL BOX
W9615-fieldbus
OUTPUT B
CONNECTION
Supply
The DVC6200f can be used with air as the supply medium. In addition, Gas Certified DVC6200f constructions can be
used with natural gas as the supply medium. If using natural gas as the pneumatic supply medium, natural gas will be
used in the pneumatic output connections of the DVC6200f to any connected equipment. In normal operation the
unit will vent the supply medium into the surrounding atmosphere unless it is remotely vented.
WARNING
Not all DVC6200f digital valve controllers are suitable for use with natural gas as the supply medium. If using natural gas as
the supply medium, the DVC6200f must be Gas Certified. Using natural gas as the supply medium in a noncertified
instrument can result in personal injury or property damage.
Gas Certified instruments can be identified by the natural gas approval label shown in figure 222. Contact your Emerson
Process Management sales office for information on obtaining a Gas Certified DVC6200f digital valve controller.
27
Installation
August 2012
Instruction Manual
D103412X012
WARNING
To avoid personal injury or property damage resulting from bursting or parts, do not exceed maximum supply pressure.
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and
appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of
the following: Remote venting of the unit, reevaluating the hazardous area classification, ensuring adequate ventilation,
and the removal of any ignition sources. For information on remote venting of this controller, refer to
page 30.
Severe personal injury or property damage may occur from an uncontrolled process if the instrument supply medium is not
clean, dry, oilfree, and noncorrosive. While use and regular maintenance of a filter that removes particles larger than 40
micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and
industry instrument air quality standards for use with corrosive air or if you are unsure about the amount of air filtration or
filter maintenance.
Supply pressure must be clean, dry air that meets the requirements of ISA Standard 7.0.01. A maximum 40
micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is
recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air
supply should be minimized.
Alternatively, natural gas may be used as the supply pressure medium in Gas Certified DVC6200f digital valve
controllers. Gas must be clean, dry, oilfree, and noncorrosive. H2S content should not exceed 20 ppm.
If you are using a 67CFR filter regulator with standard 5 micrometer filter, connect the supply line to the 1/4 NPT IN
connection and attach tubing from the output connection on the filter regulator to the SUPPLY connection on the
instrument. If you are using an integral mounted 67CFR filter regulator, connect the supply to the IN connection on
the regulator.
Output Connection
A factory mounted digital valve controller has its output piped to the supply connection on the actuator. If mounting
the digital valve controller in the field, connect the 1/4 NPT digital valve controller output connection to the
pneumatic actuator input connection.
SingleActing Actuators
When using a singleacting direct digital valve controller (relay A or C) on a singleacting actuator, connect OUTPUT A
to the actuator pneumatic input. When using a singleacting reverse digital valve controller (relay B) on a singleacting
actuator, connect OUTPUT B to the actuator diaphragm casing.
DoubleActing Actuators
DVC6200f digital valve controllers on doubleacting actuators always use relay A. With no instrument Fieldbus power
(Zero Power Condition) OUTPUT A is at 0 pressure and OUTPUT B is at full supply pressure when the relay is properly
adjusted. To have the actuator stem extend from the cylinder with increasing input signal, connect OUTPUT A to the
upper actuator cylinder connection. Connect OUTPUT B to the lower cylinder connection. To have the actuator stem
retract into the cylinder with increasing input signal, connect OUTPUT A to the lower actuator cylinder connection.
Connect OUTPUT B to the upper cylinder connection.
28
Instruction Manual
Installation
D103412X012
August 2012
In singleacting actuator applications with a solenoid valve installed, the DVC6200f can be configured to monitor the
health of the solenoid valve test, which is initiated by the Logic Solver. This is accomplished by connecting the unused
output port B from the DVC6200f to the pneumatic monitoring line between the solenoid valve and the actuator, as
shown in figure 223. When singleacting, direct relay C is installed, the unused output port is port B. When
singleacting, reverse relay B is used, the unused port is port A.
Figure 223. Pneumatic Hookup for Solenoid Testing (Instrument Level PD only)
24/48 VDC
110/220 VAC, etc.
FOUNDATION FIELDBUS
H1 SEGMENT
CONTROL LINE
Port A
Port B
SUPPLY PRESSURE
MONITORING LINE
NOTES:
Note
This application is called special application in the Setup Wizard relay selection.
This configuration is not possible with a doubleacting actuator or when using relay A in singleacting mode.
29
Installation
August 2012
Instruction Manual
D103412X012
Vent
WARNING
Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent
opening is open and free of debris to prevent pressure buildup under the cover.
WARNING
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a nonhazardous
(nonclassified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
reclassification.
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
reclassification.
Vent line piping should comply with local and regional codes, should be as short as possible with a minimum inside
diameter of 12.7 mm (1/2inch), and few bends to reduce case pressure buildup.
In addition to remote venting of the unit, ensure that all caps and covers are correctly installed. Failure to do so could result
in personal injury or property damage from fire or explosion, and area reclassification.
The relay constantly bleeds a small amount of supply medium into the area under the cover. The vent opening, located
below the wiring terminal box on the side of the housing, should be left open to prevent pressure buildup under the
cover. If a remote vent is required, the vent lines must be as short as possible with a minimum number of bends and
elbows.
To connect a remote vent, remove the plastic vent. The vent connection is 3/8 NPT. At a minimum, 12.7 mm
(1/2inch) tubing should be used when installing a remote vent to prevent excessive pressure from building up under
the cover.
30
Instruction Manual
D103412X012
Installation
August 2012
Note
As shipped from the factory, the DVC6200f digital valve controller will not move the valve when power is applied to the
instrument. To avoid the valve going to an unknown position when power is applied, the unit is shipped from the factory with the
transducer block mode Out of Service. See the Basic Setup section for information on setup and calibration and placing the
instrument in service.
WARNING
To avoid personal injury resulting from electrical shock, do not exceed the maximum input voltage specified in table 11 of
this quick start guide, or on the product nameplate. If the input voltage specified differs, do not exceed the lowest specified
maximum input voltage.
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and
temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially
explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere
conditions permit the safe removal of the terminal box cover before proceeding.
31
Instruction Manual
Installation
August 2012
D103412X012
TALK
TALK
EARTH
GROUND
LOOP
LOOP
GE41456-A
WARNING
Personal injury or property damage can result from the discharge of static electricity. Connect a 14 AWG (2.08 mm2)
ground strap between the digital valve controller and earth ground when flammable or hazardous gases are present. Refer
to national and local codes and standards for grounding requirements.
4. As shown in figure 224, two ground terminals are available for connecting a safety ground, earth ground, or drain
wire. The safety ground terminal is electrically identical to the earth ground. Make connections to these terminals
following national and local codes and plant standards.
WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.
32
Instruction Manual
Installation
D103412X012
August 2012
5. Replace and hand tighten the cover on the terminal box. To secure the terminal box cap engage the lock screw.
When the loop is ready for startup, apply power to the H1 card output.
2 (BROWN)
3 (NC)
4 (GREEN/YELLOW)
1/214 NPT
NOTES:
1.COLORS ARE WIRE COLORS.
2.NC=NO CONNECTION.
18B9424A
Note
The quick connect cable entry option is only available for intrinsically safe and nonincendive installations.
WARNING
Personal injury or property damage, caused by fire or explosion, can result from the discharge of static electricity. Connect
a 14 AWG (2.08 mm2) ground strap between the digital valve controller and earth ground when flammable or hazardous
gases are present. Refer to national and local codes and standards for grounding requirements.
To avoid static discharge from the plastic cover, do not rub or clean the cover with solvents. Clean with a mild detergent
and water only.
To avoid personal injury or property damage, do not use the Quick Connect option on instruments in explosionproof or
flameproof installations.
1. The quick connect cable entry should be installed on the digital valve controller at the factory. If it is, proceed to
step 3. If not continue with step 2.
2. To install the Quick Connect:
a. Remove the terminal box cap (key 4) from the terminal box (key 3).
b. Apply sealant to the threads of the quick connector.
c. Insert the wire pigtail into the desired conduit opening on the terminal box. Tighten the quick connector in the
conduit opening.
d. Cut and trim the wire ends.
33
Installation
August 2012
Instruction Manual
D103412X012
e. The instrument is not polarity sensitive. Refer to figure 224. Connect the blue wire to one of the LOOP terminals
in the terminal box. Connect the brown wire to the other LOOP terminal. Cut the green/yellow wire off inside of
the DVC6200f, and ensure that the shield is totally isolated at the instrument end.
Note
The green/yellow wire is cut off inside the DVC6200f to help prevent ground loop issues. The only wires that should be installed
and left on the connector are the two signal wires.
f. Replace the terminal box cap on the terminal box. To secure the terminal box cap engage the lock screw.
3. Connect the field wiring connector to the installed quick connector.
WARNING
Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit
with the remote feedback unit shares a conduit with any other power or signal wiring.
Do not place feedback wiring in the same conduit as other power or signal wiring.
Note
4conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection
between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator has been tested to 15
meters (50 feet) maximum without performance degradation.
34
Instruction Manual
Installation
D103412X012
August 2012
Figure 226. Terminal Details for Connecting the Base Unit and Feedback Unit for RemoteMounted Digital Valve
Controllers
FEEDBACK
CONNECTIONS
TERMINAL BOX
X0131-FF
FEEDBACK UNIT
GROUND
SCREW
BASE UNIT
TO FEEDBACK UNIT TERMINAL 1
TO FEEDBACK UNIT TERMINAL 2
TO FEEDBACK UNIT TERMINAL 3
TO FEEDBACK UNIT TERMINAL 4
FEEDBACK CONNECTIONS
TERMINAL BOX
TERMINAL 1
TERMINAL 2
TERMINAL S
TERMINAL 4
TERMINAL 3
FEEDBACK UNIT
WARNING
The cable shield is typically not insulated. It is required that you insulate the cable shield prior to installation.
When connecting the cable shield in step 8 ensure that the uninsulated shield wiring does not contact the DVC6215
housing. Failure to do so can result in ground loop issues.
8. Connect the cable shield between terminal S on the feedback unit and terminal S on the base unit.
CAUTION
Failure to secure the cable wires in the support clips in step 9 can cause wires to break in applications with high levels of
vibration.
9. Secure the cable wires, using the support clips in the DVC6215 feedback unit (as shown in figure 227), to help
prevent shifting and movement of the wires.
10. Replace and handtighten all covers.
35
Instruction Manual
Installation
August 2012
D103412X012
Communication Connections
WARNING
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially
explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere
conditions permit the safe removal of the terminal box cap before proceeding.
A FOUNDATION fieldbus communicating device, such as a Field Communicator or a personal computer running
ValveLink software, interfaces with the DVC6200f digital valve controller from any wiring termination point in the
segment. If you choose to connect the fieldbus communicating device directly to the instrument, attach the device to
the LOCAL connections inside the terminal box to provide local communications with the instrument.
Install a jumper across the SIMULATE ENABLE terminals to enable the instrument to accept a simulate command.
(These terminals are marked AUX on the terminal board, see figure 224). With the jumper in place and the simulate
parameter in the AO or DO block set to enabled, the transducer block ignores the output of the AO or DO block. The
simulate value and status become the readback value and status to the AO or DO block and the transducer block is
ignored. For more information on running simulations, see the Detailed Setup section of this manual, the FOUNDATION
fieldbus specifications, and the host documentation.
WARNING
Removing the jumper will disable the simulate, which may cause the valve to move. To avoid personal injury and property
damage caused by the release of pressure or process fluid, provide some temporary means of control for the process.
36
Instruction Manual
D103412X012
Installation
August 2012
Commissioning Tag
The DVC6200f digital valve controller is supplied with a removable paper commissioning tag, shown in figure 228.
This tag contains both the device ID and a space to record the device's tag number. The device ID is a unique code that
identifies a particular device in the absence of a device tag. The device tag is used as an operational identification for
the device and is usually defined by the piping and instrumentation diagram (P&ID).
Figure 228. Paper Commissioning Tag
18B9406G
When commissioning more than one device on a fieldbus segment, identifying which device is at a particular location
can be tedious without tags. The removable tag provided with the digital valve controller can be used to link the
device ID and the physical installation location. The installer should note the physical location in both places on the
removable commissioning tag and tear off the bottom portion. This should be done for each device on the segment.
The bottom portion of the tags can be used for commissioning the segment in the control system.
Prior to commissioning, the device ID is displayed by the host system if no device tag is configured in the digital valve
controller electronics. Typically the placeholder displays the device tag. The information on the paper tag enables the
engineer to match the device ID to the correct placeholder.
As an ordering option, the factory can enter a device tag into the digital valve controller electronics during the
manufacturing process. If this option is specified, the device tag is displayed at the host system prior to commissioning
rather than the device ID. This makes the job of commissioning the device easier.
37
Installation
August 2012
38
Instruction Manual
D103412X012
Instruction Manual
Basic Setup
D103412X012
August 2012
WARNING
Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application,
these changes may upset process control, which may result in personal injury or property damage.
When the DVC6200f digital valve controller is ordered as part of a control valve assembly, the factory mounts the
digital valve controller and sets up the instrument as specified on the order. When mounting to a valve in the field, the
instrument needs to be setup to match the instrument to the valve and actuator.
Before beginning basic setup, be sure the instrument is correctly mounted as described in the Installation section.
Basic Setup includes the following procedures:
Device Setup
Auto Travel Calibrate
Performance Tuner (Optional)
Note
The DVC6200f may keep the Transducer Block Mode OutofService if the instrument is not properly mounted.
To setup and calibrate the instrument, the Transducer Block Mode must be Manual, and the Protection must be None.
When using DD methods the method will request that you change the mode, but make changes in Protection automatically. If you
have a host system that overrides transducer block parameters ensure that the Protection setting is not left as None. Doing so will
result in transducer block parameters being overwritten.
To setup and calibrate the instrument, the transducer block mode must be in Manual. For more information about
transducer block mode, refer to page 62.
Protection
Field Communicator
To setup and calibrate the instrument, the protection must be set to None with the Field Communicator. For more
information about configuration protection refer to page 62.
39
Instruction Manual
Basic Setup
August 2012
D103412X012
Device Setup
Field Communicator
Follow the prompts on the Field Communicator display to automatically setup the instrument using specified actuator
information. Table 32 provides the actuator information required to setup and calibrate the instrument.
Note
If reverseacting relay B is used, you must manually set the Relay Type (BASIC_SETUP.RELAY_TYPE [42.5]) to B. This will not be set
during Device Setup.
1. Select whether Travel, Travel with Pressure fallback (auto recovery or manual recovery) or Pressure Control is
desired. Refer to page 66 for additional information.
2. Enter the pressure units:kPa, bar, psi, inHg, inH2O, or kg/cm2.
3. Enter the maximum instrument supply pressure and output pressure range (if required).
4. Enter the manufacturer of the actuator on which the instrument is mounted. If the actuator manufacturer is not
listed, select Other.
5. Enter the actuator model or type. If the actuator model is not listed, select Other.
6. Enter the actuator size.
7. Indicate whether a Volume Booster is being used.
8. Specify if factory defaults should be used for basic setup. If you select YES for factory default, the Field
Communicator sets the setup parameters to the values listed in table 31. If you select NO for the factory defaults,
the setup parameters listed in the table remain at their previous settings.
Table 31. Factory Default Settings
Setup Parameter
Default Setting
Travel Cutoff Hi
Travel Cutoff Lo
Travel Integral Gain
Travel Calibration Trigger
99.5%
0.5%
9.4 repeats/min
No
On
30%
-30%
0.25%
Pressure Cutoff Hi
Pressure Cutoff Lo
Pressure Integral Deadzone
Pressure Integral Hi Limit
Pressure Integral Lo Limit
99.5%
-0.5%
0.25%
50.0%
-50.0%
Input Characterization
Shutdown Trigger
Shutdown Recovery
Output Block Timeout
Linear
All Off
All Auto Recovery
600 sec
40
Instruction Manual
Basic Setup
D103412X012
August 2012
Actuator Model
657
667
1061
Fisher
Actuator Size
Actuator Style
25
50
60
68, 80
100, 130
30
34, 40
45, 50
46, 60, 70, 76, &
80100
30
34, 40
45, 50
46, 60, 70, 76, &
80100
20, 30
33
40
60, 70
30
40
60
68, 80, 100, 130
Starting
Tuning Set
E
I
J
L
M
User Specified
H
K
L
M
H
K
L
M
H
I
K
M
J
K
L
M
1066SR
20
27, 75
G
L
B
C
D
2052
1
2
3
3024
30, 30E
34, 34E, 40, 40E
45, 45E
H
K
M
E
H
K
X(1)
225
GX
Air to Extend
Air to Retract
Baumann
Rotary
750
1200
16
32
54
10
25
54
C
E
H
E
H
J
Air to Open
Towards the top
of the instrument
Air to Close
Away from the top of the
instrument
NOTE: Refer to figure 23 and table 410 for feedback connection (magnet assembly) information.
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Travel Sensor Motion in this instance refers to the motion of the magnet assembly.
3. Values shown are for Relay A and C. Reverse for Relay B.
41
Basic Setup
Instruction Manual
August 2012
D103412X012
Typically Device Setup determines the required setup information based upon the actuator manufacturer and model
specified. However, if you enter OTHER for the actuator manufacturer or the actuator model, then you will be
prompted for setup parameters such as:
Actuator StyleSelect spring & diaphragm, piston doubleacting without spring, piston singleacting with spring,
piston doubleacting with spring.
Valve StyleSelect the valve style, rotary or slidingstem.
Zero Power Conditionthis identifies whether the valve is fully open or fully closed when the input is 0%. If you are
unsure how to set this parameter, disconnect the instrument from the segment. (With doubleacting and
singleacting direct digital valve controllers, disconnecting the instrument from the segment is the same as setting
the output A pressure to zero. For singleacting reverse digital valve controllers, disconnecting the instrument from
the segment is the same as setting the output B pressure to supply.)
WARNING
If you answer YES to the prompt for permission to move the valve when setting the Travel Sensor Motion, the instrument
will move the valve through its full travel range. To avoid personal injury and property damage caused by the release of
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.
Travel Sensor MotionDevice Setup asks if it can move the valve to determine travel sensor motion. If you answer
Yes, the instrument will stroke the valve the full travel span to determine travel sensor motion. If you answer No,
then you must specify the direction of travel movement. For quarterturn actuators determine rotation by viewing
the rotation of the magnet assembly from the back of the instrument.
Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be
referred to as a magnetic array in user interface tools.
For instruments with relay A or C If increasing air pressure at output A causes the magnet assembly to move up, or
the actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet
assembly to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW. For
instruments with relay B.
For instruments with relay B If decreasing air pressure at output B causes the magnet assembly to move up, or the
actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet
assembly to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW.
Note
Relay A adjustment may be required before Device Setup can determine travel sensor motion. Follow the prompts on the Field
Communicator display if relay adjustment is necessary.
Table 32 lists the required Travel Sensor Motion selections for Fisher and Baumann actuators.
42
Instruction Manual
Basic Setup
D103412X012
August 2012
Tuning SetThere are twelve tuning sets to choose from. Each tuning set provides a preselected value for the digital
valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response. For
smaller actuators use tuning set C or D. For larger actuators using tuning set F or G. Table 33 lists the values for
preselected tuning sets.
Note
Tuning set B is only available in Pressure Control Mode.
Proportional Gain
4.4
4.8
5.5
6.2
7.2
8.4
9.7
11.3
13.1
15.5
18.0
User Adjusted
Pressure
Velocity Gain
Minor Loop
Feedback Gain
Proportional Gain
Integrator Gain
Minor Loop
Feedback Gain
3.0
3.0
3.0
3.1
3.6
4.2
4.8
5.6
6.0
6.0
6.0
User Adjusted
35
35
35
35
34
31
27
23
18
12
12
User Adjusted
0.5
2.2
2.4
2.8
3.1
3.6
4.2
4.8
5.6
6.6
7.8
9.0
User Adjusted
0.3
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
User Adjusted
35
35
35
35
35
34
31
27
23
18
12
12
User Adjusted
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury or property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
In addition, you can select Expert, which allows you to individually set the proportional gain, velocity gain, and minor
loop feedback gain for travel tuning and pressure proportional gain, pressure integrator gain, and pressure minor loop
feedback gain for pressure tuning. Refer to page 63 for additional information on travel tuning and page 65 for
pressure tuning.
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize or Performance Tuner may be used to achieve the desired results more rapidly than expert tuning.
Table 32 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are only
recommended starting points. After you finish setting up and calibrating the instrument, use Stabilize/Optimize to
adjust the tuning set to get the desired response.
43
Instruction Manual
Basic Setup
August 2012
D103412X012
When Device Setup is complete you are asked if you wish to run Auto Calibration now. Select yes to automatically
calibrate instrument travel at this time. Follow the prompts on the Field Communicator display. The calibration
procedure uses the valve and actuator stops as the 0% and 100% calibration points. For additional information, refer to
Auto Calibration in the Calibration section.
Note
Singleacting relay B and C are not useradjustable. However, it is recommended that you check the relay adjustment for
doubleacting relay A in new installations before proceeding with travel calibration.
Refer to page 215 for relay adjustment instructions.
If after completing setup and calibration the valve cycles or overshoots (unstable), or is unresponsive (sluggish), you
can improve operation by running Performance Tuner or Stabilize/Optimize.
Performance Tuner
Field Communicator
WARNING
During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.
The Performance Tuner is used to determine digital valve controller tuning. It will move the valve slightly and monitor
the effects of small tuning changes until an optimum control response is achieved. Because the Performance Tuner
can detect internal instabilities before they become apparent in the travel response, it can generally optimize tuning
more effectively than manual tuning. Typically, the Performance Tuner takes 3 to 5 minutes to tune an instrument,
although tuning instruments mounted on larger actuators may take longer.
44
Instruction Manual
D103412X012
Configure/Setup
Setup
Resource Block Mode
Field Communicator
Modes
The resource block can be in one of two modes (MODE_BLK [5]):
Automatic (Auto)This is the operational mode for this block. When the resource block is in the Auto mode, all
other function blocks are allowed to function normally.
Out of Service (OOS)Placing the resource block in Out of Service mode stops all function block execution, by
setting their modes to Out of Service as well. The actual mode of the function blocks is changed to Out of Service, but
the function block target modes are retained. Placing the resource block in the Out of Service mode does not affect
the mode of the transducer block.
Write Lock
Field Communicator
Write Lock
Write Lock (WRITE_LOCK [34]) determines if writes are permissible to other device parameters. The Firmware Write
Lock feature must be selected to be able to use Write Lock (see Features). When Write Lock is set to Locked, no writes
are permitted to any parameters within the device except to set Write Lock to Not Locked. When locked, the device
functions normally, updating inputs and outputs and executing algorithms. When Write Lock is set to Not Locked, the
Write Alarm (WRITE_ALM [40]) alert is active.
45
Instruction Manual
August 2012
D103412X012
Write Priority
Write Priority (WRITE_PRI [39]) sets the priority for Write Alarm. The lowest priority is 0. The highest is 15.
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your advanced control.
Default value for RCas Timeout is 20 seconds.
Shed Remote Cascade (SHED_RCAS [26]) determines how long function blocks in the DVC6200f should wait before
giving up on remote computer writes to RCas parameters. When the timeout is exceeded, the block sheds to the next
mode as defined by the block shed options. If Shed Remote Cascade is set to 0, the block will not shed from RCas.
Enter a positive value in the Shed Remote Cascade field. Time duration is in 1/32 milliseconds (640000 = 20 secs).
Shed Remote Out
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your advanced control.
Default value for Shed Remote Out is 20 seconds.
Shed Remote Out (SHED_ROUT [27]) determine how long function blocks in the DVC6200f should wait before giving
up on computer writes to ROut parameters. When the timeout is exceeded, the block sheds to the next mode as
defined by the block shed options. If Shed Remote Out is set to 0, the block will not shed from ROut. Enter a positive
value in the Shed Remote Out field. Time duration is in 1/32 milliseconds (640000 = 20 secs).
Options
Field Communicator
Diagnostic Options
Diagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the instrument.
Function Block Options
Function Block Options (FB_OPTIONS [44]) shows which function blocks are available in the instrument.
46
Instruction Manual
D103412X012
August 2012
Miscellaneous Options
Miscellaneous Options (MISC_OPTIONS [46]) indicates which miscellaneous licensing options are enabled.
Features Available
Features Available (FEATURES [17]) indicates which Resource Block Options features are available.
ReportsReports enables alert and event reporting. Reporting of specific alerts may be suppressed. See Alerts on
page 69.
Fault StateFault state enables the ability of the output block to react to various abnormal conditions by
shedding mode. See parameter descriptions for Set Fault State (SET_FSTATE [29]) and Clear Fault State
(CLR_FSTATE [30]) in table 43 and Action on Fault Detection.
Soft Write LockSoft Write lock permits using Write Lock (WRITE_LOCK [34]) to prevent any external change to
parameter values. Block connections and calculation results will proceed normally, but the configuration is locked.
Also see Write Lock, on page 45.
Multibit Alarm (BitAlarm) Support Multibit Alarm (BitAlarm) Support permits the instrument to treat each
PlantWeb alert separately when broadcast to the Host. Without MultiBit Alarm Support, an individual PlantWeb
alert must be acknowledged before another PlantWeb alert can be broadcast to the Host
Features Selected
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Fault State, Software Write Lock, and Output Readback are set by default.
Features Selected (FEATURE_SEL [18]) indicates which Resource Block Options features have been selected and is used
to select the desired features.
ReportsSelecting reports enables alert and event reporting. Reporting of specific alerts may be suppressed. See
Alerts on page 69.
Fault StateSelecting fault state enables the ability of the output block to react to various abnormal conditions by
shedding mode. See parameter descriptions for Set Fault State (SET_FSTATE [29]) and Clear Fault State
(CLR_FSTATE [30]) in table 43 and Action on Fault Detection.
Soft Write LockWhen selected, permits using Write Lock (WRITE_LOCK [34]) to prevent any external change to
parameter values. Block connections and calculation results will proceed normally, but the configuration is locked.
Also see Write Lock, on page 45.
Multibit Alarm (BitAlarm) Support When selected, the instrument will allow the instrument to treat each
PlantWeb alert separately when broadcast to the Host.
Alarm Handling
Field Communicator
Alert KeyAlert Key (ALERT_KEY [4]) is a number that permits grouping alerts. This number may be used to indicate
to the operator the source of the alert, such as the instrument, plant unit, etc. Enter a value between 1 and 255.
47
Instruction Manual
August 2012
D103412X012
Confirm TimeConfirm Time (CONFIRM_TIME [33]) determines the time, in 1/32 of a millisecond, the instrument
waits for confirmation of receipt of a report before trying again. If Confirm Time is 0, the instrument does not retry
to send the report. Enter 0 or a value between 320000 (10 secs) and 640000 (20 secs).
Limit NotifyLimit Notify (LIM_NOTIFY [32]) is the number of alert reports that the device can send without getting
a confirmation up to the maximum permitted in Maximum Notify (MAX_NOTIFY [31]). If Limit Notify is set to zero,
no alerts are reported. Enter a value between 0 and 3.
To have the instrument report alerts without having the host poll the alerts parameters, select the Reports feature
(see Feature Select).
Maximum NotifyMaximum Notify (MAX_NOTIFY [31]) indicates the maximum number of alert reports that the
device can send without getting a confirmation. This limit is determined by the amount of memory available for
alert messages. The number can be set lower, to control alert flooding, by adjusting Maximum Alerts Allowed
(LIM_NOTIFY [32]).
Block Alarm DisabledThe Block Alarm (BLOCK_ALM [36]) is used for all configuration, hardware, connection failure
or system problems in the block. Alarm Summary (ALARM_SUM [37]) determines if the Write Alarm (WRITE_ALM
[40]) and Block Alarm [BLOCK_ALM [36]) are disabled.
Block Alarm Auto AcknowledgeAcknowledge Option (ACK_OPTION [38]) determines if the block alarm will be
automatically acknowledged.
Discrete Alarm DisabledThe Write Alarm (WRITE_ALM [40]) is used to alert when parameters are writeable to the
device. Alarm Summary (ALARM_SUM [37]) determines if the Discrete Alarm is disabled.
Discrete Alarm Auto AcknowledgeAcknowledge Option (ACK_OPTION [38]) determines if the Write Alarm
associated with the block will be automatically acknowledged.
Identification
Field Communicator
48
Instruction Manual
D103412X012
August 2012
Diagnostic OptionsDiagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the
instrument.
Version
Field Communicator
Device RevisionThe Device Revision (DEV_REV [12]) is the manufacturer's revision number associated with the
resource, used by an interface device to locate the DD file for the resource.
Firmware RevisionFirmware Revision (FIRMWARE_REVISION [47]) identifies the revision of the firmware that is
currently in use.
Standby Firmware RevisionStandby Firmware Revision (STBY_FIRMWARE_REVISION [55]) identifies the revision of
the alternative firmware.
Hardware RevisionHardware Revision (HARDWARE_REV [48]) identifies the revision of the electronic hardware.
ITK VersionITK Version (ITK_VER [41]) identifies the major version of the Interoperability Tester used by the
Fieldbus Foundation in certifying the device as interoperable. This device revision meets the requirements of
version 5.
Block Errors
Table 41 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the
Resource block and are provided only for your reference.
Table 41. Resource Block BLOCK_ERR Conditions
Condition Number
Simulate Active Indicates that the simulation jumper is in place on the aux terminals. This is not an indication that the I/O
blocks are using simulation data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].
Device Needs Maintenance Soon Indicates a Maintenance or Advisory PlantWeb Alert condition is active.
10
Lost Static Data Indicates failure of the memory containing static parameters.
11
12
13
Device Needs Maintenance Now Indicates a Failed PlantWeb Alert condition is active.
14
Power Up Indicates the device has been powered up and the Resource Block is not running normally.
15
Out of Service (MSB) The resource block actual mode is Out of Service.
49
Instruction Manual
D103412X012
Parameter Name
Initial Value
Parameter Name
AO Block (continued)
Resource Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
MODE_BLK
TARGET
PERMITTED
NORMAL
Auto
Auto or Out of Service
Auto
14
18
20
GRANT_DENY
FEATURE_SEL
CYCLE_SEL
All bits: 0
Set by mfgr.
0:0
26
27
28
SHED_RCAS
SHED_ROUT
FAULT_STATE
640000
640000
1=Clear
32
33
34
37
LIM_NOTIFY
CONFIRM_TIME
WRITE_LOCK
ALARM_SUM
DISABLED
MAX_NOTIFY
640000
1=Unlocked
ACK_OPTION
WRITE_PRI
Disabled
0
38
39
All bits: 0
23
24
26
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT
8
9
11
12
0
spaces
0
0
Value
SHED_OPT
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
14
15
XD_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
IO_OPTS
STATUS_OPTS
17
CAS_IN
PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
100
0
%
2
13
14
OUT_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
CONTROL_OPTS
STATUS_OPTS
100
0
%
2
0: Bypass enable
All off
15
IN
10
11
18
19
20
21
22
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
SP_LO_LIM
CHANNEL
-Continued-
BAD:
NC:
const
0
0
Status
16
BAD:
NC:
const
0
+INF
+INF
100
0
1=analog valve input
0
spaces
0
0
NORMAL
SP
OUT
8
9
100
0
%
2
100
0
%
2
All off
All off
BAD:
NoComm:
NoVal:
const
0 Trk
All off
Out of Service
OOS+MAN+AUTO+CAS+
RCAS+ROUT
Auto
Dynamic
Dynamic
OOS+MAN+AUTO+CAS+RCAS
PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
0
0
Out of Service
Auto
Dynamic
Dynamic
FSTATE_TIME
FSTATE_VAL
RCAS_IN
Status
27
AO Block
1
2
3
4
17
18
19
20
21
22
23
24
25
26
27
Value
PV_FTIME
BYPASS
CAS_IN
Status
0
BAD:
NC:
const
0
+INF
+INF
100
Value
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
SP_LO_LIM
GAIN
RESET
BAL_TIME
RATE
BKCAL_IN
Status
0
1
+INF
0
0
BAD:
NC:
const
0
Value
-Continued-
50
Initial Value
Instruction Manual
D103412X012
August 2012
Parameter Name
Initial Value
Parameter Name
33
OUT_HI_LIM
OUT_LO_LIM
BKCAL_HYS
RCAS_IN
Status
100
0
0.5%
BAD:
NoCom:
NoVal:
const
0 Trk
Value
ROUT_IN
Status
BAD:
NoCom:
NoVal:
const
0 Trk
Value
34
37
38
39
40
SHED_OPT
TRK_SCALE
EU 100%
EU 0%
Engineering Units
Decimal places
TRK_IN_D
Status
BAD:
NC:
const
0
Value
TRK_VAL
Status
BAD:
NC:
const
0
Value
FF_VAL
Status
BAD:
NC:
const
0
Value
41
46
FF_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
FF_GAIN
ALARM_SUM
DISABLED
ACK_OPTION
47
48
49
50
51
ALARM_HYS
HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM
0.5%
0
+INF
0
+INF
52
53
54
55
LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM
0
-INF
0
-INF
56
57
58
59
DV_HI_PRI
DV_HI_LIM
DV_LO_PRI
DV_LO_LIM
0
+INF
0
-INF
42
45
100
0
%
2
0
0
Disabled
BIAS
SP_FTIME
MATHFORM
STRUCTURECONFIG
GAMMA
BETA
IDEABAND
0
0
0
ISEL Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
MODE_BLK
TARGET
PERMITTED
NORMAL
OUT
Out of Service
OOS+MAN+AUTO
Auto
0
100
0
%
2
Initial Value
7
8
10
11
12
OUT_RANGE
EU 100%
EU 0%
Engineering Units
Decimal Places
STATUS_OPTS
IN_1
Status
All off
BAD
NC
cons
0
Value
IN_2
Status
BAD
NC
cons
0
Value
13
14
IN_3
Status
BAD
NC
cons
0
Value
IN_4
Status
BAD
NC
cons
0
Value
15
16
100
0
%
2
DISABLE_1
Status
BAD
NC
cons
0
Value
DISABLE_2
Status
BAD
NC
cons
0
Value
-Continued-
-Continued-
51
Instruction Manual
D103412X012
Parameter Name
Initial Value
Parameter Name
18
DISABLE_3
Status
Value
DISABLE_4
Status
Value
19
20
22
SELECT_TYPE
MIN_GOOD
OP_SELECT
Status
25
26
28
Value
IN_6
Status
30
IN_7
Status
32
Value
IN_8
Status
35
36
37
DISABLE_5
Status
BAD
NC
cons
0
Value
DISABLE_6
Status
BAD
NC
cons
0
DISABLE_7
Status
Value
DISABLE_8
Status
AVG_USE
ALARM_SUM
DISABLED
ACK_OPTION
ALARM_HYS
HI_HI_PRI
All bits: 0
DI Block
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
OUT_D
XD_STATE
OUT_STATE
IO_OPTS
STATUS_OPTS
8
10
11
13
14
15
16
20
0
spaces
0
0
Out of Service
OOS+MAN+AUTO
Auto
0
0
All off
All off
21
22
23
CHANNEL
PV_FTIME
ALARM_SUM
DISABLED
ACK_OPTION
DISC_PRI
DISC_LIM
0
0
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT_1
OUT_2
OUT_1_RANGE
EU 100%
EU 0%
Engineering Units
Decimal Places
0
All off
0
0
OS Block
7
8
9
10
BAD
NC
cons
0
11
BAD
NC
cons
0
13
14
0
spaces
0
0
OUT_2_RANGE
EU 100%
EU 0%
Engineering Units
Decimal Places
STATUS_OPTS
CAS_IN
Status
100
0
%
2
100
0
%
2
BAD
NC
const
0
Value
0
0
0.5%
0
Out of Service
OOS+MAN+AUTO
AUTO+CAS
disabled
-Continued-
52
LO_LO_LIM
OUT_D
ALM_SEL
BAD
NC
cons
0
Value
33
34
44
49
50
BAD
NC
cons
0
Value
31
BAD
NC
cons
0
BAD
NC
cons
0
Value
29
0
0
0
0
0
0
BAD
NC
cons
0
Value
27
BAD
NC
cons
0
HI_HI_LIM
HI_PRI
HI_LIM
LO_PRI
LO_LIM
LO_LO_PRI
BAD
NC
constant
0
IN_5
Status
All off
0
Value
Initial Value
-Continued-
Instruction Manual
D103412X012
August 2012
Parameter Name
Initial Value
OS Block (continued)
19
BKCAL_1_IN
Status
Value
20
BKCAL_2_IN
Status
BAD
NC
const
0
0
21
Value
BAL_TIME
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
OUT
XD_SCALE
EU at 100%
EU 0%
Units Index
Decimal point
AI Block
8
10
11
13
14
15
16
17
18
22
0
spaces
0
0
Out of Service
OOS, MAN, AUTO
Auto
100
0
%
2
OUT_SCALE
EU 100%
EU 0%
Units Index
Decimal point
I/O OPTS
STATUS OPTS
CHANNEL
L_TYPE
100
0
Trk s/b%
2
disabled
disabled
0
0
0
0
23
24
LOW_CUT
PV_FTIME
ALARM_SUM
DISABLED
ACK_OPTION
ALARM_HYS
25
26
27
28
HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM
0
0
0
0
29
30
31
32
37
38
LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM
OUT_D
ALM_SEL
0
0
0
0
1
2
3
4
7
8
9
10
11
12
13
14
15
MODE_BLK
TARGET
PERMITTED
NORMAL
CHANNEL
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
1
2
3
4
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
unselected
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
0
spaces
0
0
Out of Service
OOS, MAN, AUTO
Auto
TB.FINAL_VALUE
TB.TRAVEL_TARGET
TB.FINAL_POSITION_VALUE
TB.TRAVEL
TB.SUPPLY_PRESS
TB.ACT_PRESS_A
TB.ACT_PRESS_B
TB.ACT_PRESS_DIFF
DO Block
0
spaces
0
0
8
9
NORMAL
SP_D
OUT_D
11
12
14
15
PV_STATE
XD_STATE
IO_OPTS
STATUS_OPTS
17
CAS_IN_D
Status
18
19
20
22
0
Disabled
0.5%
MAI Block
Initial Value
BAD
NC
const
0
Parameter Name
23
27
28
Value
CHANNEL
FSTATE_TIME
FSTATE_VAL_D
RCAS_IN_D
Status
Value
SHED_OPT
SP_RATE_UP
SP_RATE_DN
Out of Service
OOS+MAN+AUTO+CAS+
RCAS
AUTO+CAS
0
0
All off
All off
BAD
NC
const
0
22
0
0
BAD
NoComm
NoVal
const
0
All off
0
0
Transducer Block
1
2
3
4
5
87
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
PROTECTION
N/A
NULL
0
1
Out of Service
AUTO, MAN, OOS
Auto
None
-Continued-
53
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Initial
Value
Description
Static Revision
ST_REV
RO
NA
0 to 65535
Tag Description
TAG_DESC
RW
NA
7 bit ASCII
Spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET_MODE
5.1
RW
ALL
1 to 255
RW
ALL
3: Auto
7: OOS
3: Auto
N/A
ACTUAL_MODE
5.2
RO
NA
3: Auto
6: IMAN (only during
initialization
7: OOS
PERMITTED_MODE
5.3
RW
ALL
3: Auto
7: OOS
3: Auto
7: OOS
NORMAL_MODE
5.4
RW
ALL
3: Auto
3: Auto
N/A
0: Other
1: Block Configuration
Error
3:Simulate Active
6:Device needs
Maintenance Soon
9:Memory Failure
10:Lost Static Data
11:Lost NonVolatile
Memory
13:Device needs
Maintenance Now
14:Powerup
15:Outof
Service (MSB)
N/A
2:Initialization,
Actual mode=IMAN
4:Online, Actual
Mode=Auto
5:Standby, Actual
Mode=OOS
6:Failure, Actual
Mode=OOS
Block Error
BLOCK_ERR
Device State
RS_STATE
RO
RO
ALL
5: Standby
-Continued-
54
Dynamic
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
RO
N/A
Range
Initial
Value
Description
Spaces
Manufacturer Id
MANUFAC_ID
10
RO
N/A
0x5100
Device Type
DEV_TYPE
11
RO
N/A
4602
N/A
Varies with
release
Varies with
release
Device Revision
DEV_REV
12
DD Revision
DD_REV
13
Grant Deny
GRANT_DENY
14
RO
RO
N/A
GRANT
14.1
RW
ALL
DENY
14.2
RW
ALL
Hard Types
HARD_TYPES
Restart
RESTART
Features
FEATURES
15
16
17
RO
RW
RO
Valid Bits:
0: Program
1: Tune
2: Alarm
3: Local
N/A
0: Scalar Input
1: Scalar Output
2: Discrete Input
3: Discrete Output
ALL
1=Run
2=Restart resource
3=Restart with
defaults
4=Restart processor
ALL
1:Reports supported
2:Fault State
supported
3:Software Write
lock supported
10:Reannunciation
supported
All bits: 0
All bits: 0
0: 1
1: 1
2: 1
3: 1
1=Run
1: 1
2: 1
3: 1
10: 1
-Continued-
55
Instruction Manual
D103412X012
Features Selected
FEATURE_SEL
Cycle Type
CYCLE_TYPE
Cycle Selection
CYCLE_SEL
Memory Size
MEMORY_SIZE
Free Space
FREE_SPACE
Free Time
FREE_TIME
RCAS Timeout
SHED_RCAS
Index
Number
18
19
RO /
RW
RW
RO
20
21
22
23
24
25
26
Mode
Range
Initial
Value
ALL
1: Reports Supported
2: Fault State
supported
3: Software Write lock
supported
10:Reannunciation
supported
1:0
2:1
3:1
10:0
0: 1
0: 0
3200
45
576,000
640000
NA
ALL
RO
RO
RO
RO
RO
RW
NA
NA
NA
NA
NA
ALL
0: Scheduled
0: Scheduled
3200
45
Positive
0 to 100%
0 to 100%
Positive
-Continued-
56
Description
Instruction Manual
D103412X012
August 2012
ROUT Timeout
SHED_ROUT
Fault State
FAULT_STATE
Maximum Notify
MAX_NOTIFY
Index
Number
27
28
29
30
31
RO /
RW
RW
RO
RW
RW
RO
Mode
ALL
N/A
ALL
ALL
N/A
Range
Positive
1=Clear
2=Active
1=Off
2=Set
1=Off
2= Clear
32
RW
ALL
0 to MAX_NOTIFY
Confirm Time
CONFIRM_TIME
33
RW
ALL
> 0
Set by FCS
Initial
Value
Description
640000
1=Clear
1=Off
1=Off
MAX_NOTIFY
640000
-Continued-
57
Instruction Manual
D103412X012
Index
Number
Write Lock
WRITE_LOCK
34
Update Event
UPDATE_EVT
35
RO /
RW
Mode
Range
Description
Data Type: Unsigned8
If set to Locked, no writes from anywhere are
allowed except to clear WRITE_LOCK by entering
Unlocked. Block inputs will continue to be
updated if they are subscribers. The feature Soft
Write Lock must be selected to enable writing to
this parameter (see Device Features in this
section).
RW
ALL
0=Undefined
1=Unlocked
2=Locked
1=Unlocked
UNACKNOWLEDGED
35.1
RW
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
UPDATE_STATE
35.2
RO
NA
0=Undefined
1=Update reported
2=Update not
reported
0=Undefined
TIME_STAMP
35.3
RO
NA
STATIC_REVISION
35.4
RO
NA
RELATIVE_INDEX
35.5
RO
NA
RW
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=Undefined
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
36.1
36.2
RO
NA
TIME_STAMP
36.3
RO
NA
SUBCODE
36.4
RO
NA
VALUE
36.5
RO
NA
RO
NA
0: Discrete alarm
7: Block Alarm
All bits: 0
NA
0: Discrete alarm
7: Block Alarm
All bits: 0
All bits: 0
CURRENT
UNACKNOWLEDGED
36
ALARM_STATE
Alarm Summary
ALARM_SUM
37
37.1
37.2
RO
UNREPORTED
37.3
RO
NA
0: Discrete alarm
7: Block Alarm
DISABLED
37.4
RW
ALL
0: Discrete alarm
7: Block Alarm
All bits: 0
0: 0
7: 0
Acknowledge Option
ACK_OPTION
38
RW
ALL
0: Discrete Alarm
(Write Lock off)
7: Block Alarm
Write Priority
WRITE_PRI
39
RW
ALL
0 to 15
-Continued-
58
Initial
Value
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial
Value
40
40.1
RW
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=Undefined
ALARM_STATE
40.2
RO
NA
TIME_STAMP
40.3
RO
NA
SUBCODE
40.4
RO
NA
VALUE
40.5
RO
NA
ITK Version
ITK_VER
41
RO
N/A
42
RO
NA
43
Description
Data Type: DS72
This alarm is generated when Unlocked in the
WRITE_LOCK parameter is set. This alarm has a
priority of WRITE_PRI. For a WRITE_ALM to be
broadcast to the host the following conditions
must be met:
The feature Reports must be selected
Alert communication with the host must be
setup
In the ALARM_SUM parameter, the disable bit
for Write Alarm must be clear.
WRITE_PRI must be greater than 1.
Data Type: Unsigned16
Major version of ITK test this device has been
tested to. *Initial value depends on the revision
of the DVC6200f.
Extended Parameters
Diagnostic Options
DIAG_OPTIONS
44
45
Miscellaneous Options
MISC_OPTIONS
46
Firmware Revision
FIRMWARE_REVISION
47
0x5100
RO
Bits
0: AO
1: DO
2: AI
3: DI
4: PID
5: ISEL
6: OS
7: MAI
RO
NA
1=FD Fieldbus
Diagnostics
2=AD Advanced
Diagnostics
3=PD Performance
Diagnostics
RO
NA
0: Software Download
10: Travel Control
Capable
11: Pressure Control
Capable
12: Fallback Capable
All options
enabled
FD
0: 1
10: 1
11: 1
AD/PD
0: 1
10: 1
11: 1
12: 1
FIRMWARE_REV_MAJOR
47.1
RO
NA
0-255
FIRMWARE_REV_MINOR
47.2
RO
NA
0-255
FIRMWARE_REV_BUILD
47.3
RO
NA
0-255
IO_FIRMWARE_REV
47.4
RO
NA
0-255
DIAG_CAL_REV
47.5
RO
NA
0-255
FIRMWARE_REV_ALL
Hardware Revision
HARDWARE_REV
47.6
RO
NA
XX.XX.XX
48
RO
NA
Hardware revision
number
Factory Set
-Continued-
59
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
49
RO
NA
NA
Factory Set
50
RO
NA
NA
spaces
51
RW
NA
Any String
spaces
Detailed Status
DETAILED_STATUS
52
RO
NA
NA
53
RO
NA
NA
Device ID
DEVICE ID
54
RO
NA
NA
Device ID
STBY_FIRMWARE_REV
Initial
Value
55.1
RO
NA
0-255
STBY_FIRMWARE_REV_MINOR
55.2
RO
NA
0-255
STBY_FIRMWARE_REV_BUILD
55.3
RO
NA
0-255
STBY_IO_FIRMWARE_REV
55.4
RO
NA
0-255
STBY_DIAG_CAL_REV
55.5
RO
NA
0-255
FB_AVAILABLE
Description
Data Type: Visible String Electronics serial
number set by manufacturing.
55
STBY_FIRMWARE_REV_MAJOR
STBY_FIRMWARE_REV_ALL
60
Range
55.6
56
RO
RO
NA
XX.XX.XX
NA
Bits
0: AO
1: DO
2: AI
3: DI
4: PID
5: ISEL
6: OS
7: MAI
NA
All options
enabled
Instruction Manual
D103412X012
August 2012
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 44. Resource Block, View 1
Index Number
1
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
RS_STATE
25
FREE_TIME
28
FAULT_STATE
ALARM_SUM.CURRENT
37.2
ALARM_SUM.UNACKNOWLEDGED
37.3
ALARM_SUM.UNREPORTED
37.4
ALARM_SUM.DISABLED
Parameter
ST_REV
14.1
GRANT_DENY.GRANT
14.2
GRANT_DENY.DENY
18
FEATURE_SEL
20
CYCLE_SEL
23
NV_CYCLE_T
24
FREE_SPACE
26
SHED_RCAS
27
SHED_ROUT
32
LIM_NOTIFY
33
CONFIRM_TIME
34
WRITE_LOCK
Index Number
37.4
Parameter
ALARM_SUM.DISABLED
44
FB_OPTIONS
52
DETAILED_STATUS
53
TIME_SINCE_RESET
54
DEVICE_ID
37.1
Index Number
Index
Number
Parameter
ST_REV
STRATEGY
ALERT_KEY
10
MANUFAC_ID
11
DEV_TYPE
12
DEV_REV
13
DD_REV
15
HARD_TYPES
17
FEATURES
19
CYCLE_TYPE
21
MIN_CYCLE_T
22
MEMORY_SIZE
31
MAX_NOTIFY
38
ACK_OPTION
39
WRITE_PRI
41
ITK_VER
42
DISTRIBUTOR
43
DEV_STRING
45
DIAG_OPTIONS
46
MISC_OPTIONS
47.1
FIRMWARE_REVISION.FIRMWARE_REV_MAJOR
47.2
FIRMWARE_REVISION.FIRMWARE_REV_MINOR
47.3
FIRMWARE_REVISION.FIRMWARE_REV_BUILD
ST_REV
47.4
FIRMWARE_REVISION.IO_FIRMWARE_REV
5.1
MODE_BLK.TARGET_MODE
47.5
FIRMWARE_REVISION.DIAG_CAL_REV
5.2
MODE_BLK.ACTUAL_MODE
47.6
FIRMWARE_REVISION.FIRMWARE_REV_ALL
5.3
MODE_BLK.PERMITTED_MODE
48
HARDWARE_REV
5.4
MODE_BLK.NORMAL_MODE
49
ELECTRONICS_SN
BLOCK_ERR
50
FACTORY_SN
RS_STATE
51
FIELD_SN
25
FREE_TIME
55.1
STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_MAJOR
28
FAULT_STATE
55.2
STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_MINOR
37.1
ALARM_SUM.CURRENT
55.3
STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_BUILD
37.2
ALARM_SUM.UNACKNOWLEDGED
55.4
STBY_FIRMWARE_REV.STBY_IO_FIRMWARE_REV
37.3
ALARM_SUM.UNREPORTED
55.5
STBY_FIRMWARE_REV.STBY_DIAG_CAL_REV
55.6
STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_ALL
Parameter
-continued-
61
Instruction Manual
D103412X012
Transducer Block
Overview
The transducer block accepts a signal from an output block as a set point to position a valve using a pneumatic
actuator. Input to the transducer block is in percent. Closed is 0%, and open is 100%. The transducer block contains
setup and calibration information and can be tuned to closely match the actuator. Input characterization permits
modifying the overall characteristic of the instrumentactuatorvalve combination in order to modify the installed gain
characteristic of the loop. The transducer block can also be used to perform instrument and valve diagnostics and
trigger performance alerts.
The following procedures address only the key transducer block parameters; however, all transducer block parameters
are listed in table 414.
Detailed Setup
Note
To setup and calibrate the instrument, the transducer block Mode must be Manual and the Protection must be None.
Modes
The transducer block can be in one of three modes (MODE_BLK [5]):
Automatic (Auto) This is the normal mode for this block. When the transducer block is in the auto mode, it accepts
the output from the AO or DO block as a set point and outputs a drive signal to the I/P converter based upon this set
point.
Out of Service (OOS) Placing the transducer block in Out of Service mode changes the output to the zero power
(no I/P drive) condition.
Field Communicator
Manual (MAN) Placing the transducer block in Manual will hold the value at the current setpoint (FINAL_VALUE
[13]). The transducer block will not accept changes from the AO or DO blocks. This mode is required to change some
parameters and to run some diagnostics.
Protection
Field Communicator
To configure any parameters in the digital valve controller Write Lock (WRITE_LOCK [34]), in the resource block, must
be set to Unlocked (refer to page 45). In addition, protection is provided for various transducer block parameters, as
62
Instruction Manual
D103412X012
August 2012
indicated in the Protect Category column of table 414, to prevent inadvertently overwriting key data by the host
system or user.
All will protect all transducer block Parameters.
Setup and Calibration will protect only Setup and Calibration transducer block parameters.
Calibration will protect only Calibration transducer block parameters.
None will not protect any transducer block parameters.
Note
The Device Setup Auto Travel and Manual Travel methods automatically change transducer block protection for the user.
Response Control
Travel Tuning
Field Communicator
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury or property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
Travel Tuning SetThere are eleven Travel Tuning Sets (TVL_TUNING_SET [42.10]) to choose from. Each tuning set
provides a preselected value for the digital valve controller gain settings.
Tuning set C provides the slowest response and M provides the fastest response. Table 48 lists the proportional gain,
velocity gain and minor loop feedback gain values for preselected tuning sets.
In addition, you can specify Expert tuning and individually set the proportional gain, velocity gain, and minor loop
feedback gain. Individually setting or changing any tuning parameter or running the Performance Tuner or
Stabilize/Optimize will automatically change the tuning set to X (expert).
Table 48. Gain Values for Preselected Travel Tuning Sets
Tuning Set
C
D
E
F
G
3.0
3.0
3.0
3.1
3.6
35
35
35
35
34
H
I
J
K
L
M
X (Expert)
8.4
9.7
11.3
13.1
15.5
18.0
User Adjusted
4.2
4.8
5.6
6.0
6.0
6.0
User Adjusted
31
27
23
18
12
12
User Adjusted
Note
Use Expert tuning if standard tuning has not achieved the desired results.
63
Instruction Manual
D103412X012
Stabilize/Optimize may be used to achieve the desired results more rapidly than Expert tuning.
Table 32 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are
recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either
a higher or lower tuning set to get the desired response.
For an actuator not listed in table 32, you can estimate a starting tuning set by calculating the casing or cylinder
volume. Then, find an actuator in table 32 with the closest equivalent volume and use the tuning set suggested for
that actuator.
Travel Proportional GainTravel Proportional Gain (SERVO_GAIN [18]) is the proportional gain for the travel control
tuning set. Changing this parameter will also change the tuning set to Expert.
Travel Velocity GainTravel Velocity Gain (SERVO_RATE [20]) is the velocity gain for the travel control tuning set.
Changing this parameter will also change the tuning set to Expert.
Travel MLFB GainTravel MLFB Gain (TVL_MLFB_GAIN [44.5]) is the minor loop feedback gain for the travel control
tuning set. Changing this parameter will also change the tuning set to Expert.
Travel Integral EnableTravel Integral Enable (TVL_INTEG_ENABLE [44.1]) is used to enable the integral setting to
improve static performance by correcting for error that exists between the travel target and actual travel.
Travel Integral GainTravel Integral Gain (SERVO_RESET [19]) (also called reset) is the ratio of the change in output
to the change in input, based on the control action in which the output is proportional to the time integral of the
input.
Travel Integral Dead ZoneTravel Integral Dead Zone (TVL_INTEG_DEADZ [44.4]) is a window around the Primary
Setpoint in which the integral action is disabled. The dead band is configurable from 0 to 2%.
Travel Integral Limit HiTravel Integral Limit Hi (TVL_INTEG_LIM_HI [44.2]) provides an upper limit to the integrator
output. The high limit is configurable from 0 to 100% of the I/P drive signal.
Travel Integral Limit LoThe Travel Integral Limit Lo (TVL_INTEG_LIM_LO [44.3]) provides a lower limit to the
integrator output. The low limit is configurable from -100 to 0% of the I/P drive signal.
Performance Tuner
WARNING
During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.
Performance Tuner is used to determine digital valve controller tuning. It will move the valve slightly and monitor the
effects of small tuning changes until an optimum control response is achieved. Because the Performance Tuner can
detect internal instabilities before they become apparent in the travel response, it can generally optimize tuning more
effectively than manual tuning.
Stabilize/Optimize
WARNING
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.
64
Instruction Manual
D103412X012
If after completing initial setup and calibration the valve cycles or overshoots, or is sluggish, you can improve
operation by running Stabilize/Optimize.
Stabilize/Optimize is included with the device description (DD) firmware. Stabilize/Optimize is accessible from the
transducer block and permits changing the transducer block set point a small amount to see if the valve is unstable or
unresponsive. If valve response is unsatisfactory, the method permits adjusting the digital valve controller tuning to
improve response.
If the valve is unstable, select Decrease Response to stabilize valve operation. This selects the next lower tuning set
(e.g., F to E). If the valve response is sluggish, select Increase Response to make the valve more responsive. This selects
the next higher tuning set (e.g., F to G).
If after selecting Decrease Response or Increase Response the valve travel overshoot is excessive, Increase Damping or
Decrease Damping can be used to select a damping value not represented in a predefined tuning set. Select Decrease
Damping to select a damping value that allows more overshoot. Select Increase Damping to select a damping value that
will decrease the overshoot.
When valve operation is satisfactory, select Exit. Before exiting, you are asked if you want to return the transducer
block mode to Auto. Select Yes to change the transducer block mode to Auto. Select No to leave the transducer block
in its current mode.
Pressure Tuning
Field Communicator
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury or property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
65
Instruction Manual
D103412X012
0.3
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
User Adjusted
35
35
35
35
35
34
31
27
23
18
12
12
User Adjusted
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize may be used to achieve the desired results more rapidly than Expert tuning.
Pressure Proportional GainPressure Proportional Gain (PRESS_PROP_GAIN [47.3]) is the proportional gain for the
pressure control tuning set. Changing this parameter will also change the tuning set to Expert.
Pressure MLFB GainPressure MLFB Gain (PRESS_MLFB_GAIN [47.11]) is the minor loop feedback gain for the
pressure control tuning set. Changing this parameter will also change the tuning set to Expert.
Pressure Integral GainPressure Integral Gain (PRESS_INTEG_GAIN [47.4]) (also called reset) is the ratio of the
change in output to the change in input, based on the control action in which the output is proportional to the time
integral of the input. Changing this parameter will also change the tuning set to Expert.
Pressure Integral Dead ZonePressure Integral Dead Zone (PRESS_INTEG_DEADZ [47.6]) is a window around the
Primary Setpoint in which the integral action is disabled. The dead band is configurable from 0 to 2%.
Pressure Integral Limit HiPressure Integral Limit Hi (PRESS_INTEG_HI_LIM [47.7]) provides an upper limit to the
integrator output. The high limit is configurable from 0 to 100% of the I/P drive signal.
Pressure Integral Limit LoPressure Integral Limit Lo (PRESS_INTEG_LO_LIM [47.8]) provides a lower limit to the
integrator output. The low limit is configurable from -100 to 0% of the I/P drive signal.
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control
Travel/Pressure StateTravel/Pressure State (TVL_PRESS.STATE [41.2]) indicates if the instrument is being used for
travel control (position control) or as an I/P (pressure control)
Travel/Pressure Select
CAUTION
When using Pressure Fallback Manual Recovery or Pressure Fallback Auto Recovery, the valve travel has the potential of
moving rapidly causing potential process instability when returning to Travel Control.
66
Instruction Manual
D103412X012
August 2012
Note
Travel / Pressure Select must be set to Travel for double acting actuators.
Travel / Pressure Select (TVL_PRESS_SELECT [41.1]) determines if the instrument is setup for position or pressure
control. Select Travel, Pressure, Travel with Pressure Fallback/Auto recovery or Travel with Pressure Fallback/Manual
Recovery. If the travel sensor fails, and Travel with Pressure Fallback/Auto Recovery is selected, it will return to travel
control when the travel sensor starts working again. Travel with Pressure Fallback/Manual recovery will stay in pressure
control until Travel Pressure Select is changed to Travel or Travel with Pressure Fallback/Auto recovery. It is not
necessary to enable the Travel Sensor Alert for Pressure Fallback to occur.
Travel Deviation Pressure FallbackTravel Deviation Pressure Fallback occurs when the instrument detects that the
travel sensor is outside of its normal range of operation or that a gross deviation exists between set point and actual
travel. It switches to Pressure Control and no longer uses the travel sensor to position the valve.
Travel Cutoff HiTravel Cutoff Hi (FINAL_VALUE_CUTOFF_HI [15]) defines the high cutoff point for the travel in
percent (%) of precharacterized setpoint. Above this cutoff, the travel target is set to 123.0% of the ranged travel.
Travel Cutoff Hi is deactivated by setting it to 125.0%.
Travel Cutoff LoTravel Cutoff Lo (FINAL_VALUE_CUTOFF_LO [16]) defines the low cutoff point for the travel in
percent (%) of precharacterized setpoint. Below this cutoff, the travel target is set to -23%. A Travel Cutoff Lo of
0.5% is recommended to help ensure maximum shutoff seat loading. Travel Cutoff Lo is deactivated by setting it to
-25.0%
Pressure Cutoff OpenPressure Cutoff Open (PRESS_CUTOFF_HI [47.1]) defines the high cutoff point for the
pressure in percent (%) of precharacterized setpoint. Above this cutoff, the pressure target is set to 123.0%. A
Pressure Cutoff Open of 99.5% is recommended to ensure valve goes fully open. Pressure Cutoff Hi is deactivated by
setting it 125%.
Pressure Cutoff ClosedPressure Cutoff Closed (PRESS_CUTOFF_LO [47.2]) defines the low cutoff point for the
pressure in percent (%) of precharacterized setpoint. Below this cutoff, the pressure target is set to -23%. A Pressure
Cutoff Closed of 0.5% is recommended to help ensure maximum shutoff seat loading. Pressure Cutoff Closed is
deactivated by setting it to -25.0%
Pressure Range HiPressure Range Hi (PRESS_RANGE_HI [42.7]) is the high end of output pressure range. Enter the
pressure that corresponds with 100% valve travel when Zero Power Condition is closed, or 0% valve travel when
Zero Power Condition is open. This pressure must be greater than the Pressure Range Lo.
Pressure Range LoPressure Range Lo (PRESS_RANGE_LO [42.8]) is the low end of the output pressure range. Enter
the pressure that corresponds to 0% valve travel when Zero Power Condition is closed, or 100% valve travel when
Zero Power Condition is open. The pressure must be less than the Pressure Range Hi.
Input Characterization
Field Communicator
TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization
Input Characterization (INPUT_CHAR [50]) defines the relationship between the travel target and the setpoint
received from the output block. Travel target is the output from the characterization function.
67
Instruction Manual
D103412X012
Field Communicator
You can select from the three fixed input characteristics shown in figure 41 or you can select a custom characteristic.
Figure 41 shows the relationship between the travel target and travel set point for the fixed input characteristics.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel, for
a corresponding set point, in % of ranged set point. Set point values range from -25.0% to 125%. Before modification,
the custom characteristic is linear. You cannot modify the custom points if the Input Characterization (INPUT_CHAR
[50]) is set to custom.
Figure 41. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Power Condition = Closed)
125
100
100
Travel Target, %
Travel Target, %
125
-25
-25
-25
Set Point, %
100
125
-25
Set Point, %
Travel Target, %
100
-25
-25
A65351
68
100
Set Point, %
100
125
125
Instruction Manual
D103412X012
August 2012
Outblock Selection
Field Communicator
TB > Configure/Setup > Detailed Setup > Response Control > Outblock Selection
Outblock Selection (OUTBLOCK_SEL [96]) defines which output function block will control the setpoint of the valve.
The output block that is not selected will shed its mode to reflect that it does not have control of the valve.
Alerts
The DVC6200f provides two levels of alerts; Instrument alerts and PlantWeb alerts.
PlantWeb Alerts
Some instrument alert conditions can also be used to trigger PlantWeb alerts that will be reported in Failed,
Maintenance or Advisory categories, as configured by the user. PlantWeb alerts, when enabled, can participate in the
DeltaV alarm interface tools such as the alarm banner, alarm list and alarm summary.
When a PlantWeb alert occurs, the DVC6200f sends an event notification and waits a specified period of time for an
acknowledgment to be received. This occurs even if the condition that caused the alert no longer exists. If the
acknowledgment is not received within the prespecified timeout period, the event notification is retransmitted. This
reduces the possibility of alert messages getting lost.
PlantWeb alerts are modebased. Refer to table C1 for details.
Note
Additional details on setting up and using PlantWeb Alerts can be found in Appendix C of this manual.
Electronics Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts
Drive Current
Drive CurrentDrive Current (DRIVE_CURRENT [54]) displays the measured Drive Current actually flowing through
the I/P converter in percent of maximum drive.
Drive Current AlertThis alert is active when the difference between the expected Drive Current and the actual
Drive Current has exceeded the Drive Current Alert Time.
Drive Current Alert EnableWhen enabled Drive Current Alert Enable activates the Drive Current Alert.
Drive Current ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown for the Drive Current alert. When enabled, and the alert condition is present, the transducer Actual
69
Instruction Manual
August 2012
D103412X012
mode is placed Out of Service. The instrument will attempt to drive the valve to the Zero Power Condition and will
no longer execute transducer control function.
Drive Current Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when Drive Current Shutdown clears. If not enabled, the transducer block will remain Out of Service until
power is removed and restored or the user changes the transducer block target mode to Manual or Auto. In any
case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or until the
shutdown trigger is disabled.
Drive Current Alert PointThe Drive Current Alert Point (DRIVE_CURRENT_ALRT_PT [76.4]) is when the absolute
difference between the Drive Current and Drive Signal exceeds the set threshold for greater than the Drive Current
Alert Time.
Drive Current Alert TimeThe Drive Current Alert Time (DRIVE_CURRENT_TIME [76.5]) is the maximum time that
the Drive Current Alert Point can be exceeded before the Drive Current Alert is active.
Drive Signal
Drive SignalThe Drive Signal (DRIVE_SIGNAL [53]) displays the commanded Drive Signal being sent to the I/P
converter as a percentage of the maximum drive.
Drive Signal Alert
The Drive Signal Alert is active if one of the following conditions exist:
Where Zero Power Condition is defined as closed:
Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%
Where Zero Power Condition is defined as open:
Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%
Drive Signal Alert EnableWhen enabled Drive Signal Alert Enable activates the Drive Signal Alert.
Processor Impaired
Program Memory AlertThis alert is active if a pending Flash or NVM failure is present.
Program Memory Alert EnableWhen enabled Program Memory Alert Enable activates the Program Memory Alert.
Program Memory ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling
Self Test Shutdown. When enabled, and the Program Memory Alert is active, the transducer Actual mode is placed
out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
Program Memory Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Program Memory Shutdown clears. If not enabled, the transducer block will
70
Instruction Manual
D103412X012
August 2012
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
Static Memory AlertThis alert is active if a failure occurs in the FRAM memory where the static parameters are
stored.
Static Memory Alert EnableWhen enabled Static Memory Alert Enable activates the Static Memory Alert.
Static Memory ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the Static Memory Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
Static Memory Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Static Memory Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
Processor AlertThis alert is active if a failure occurs in the main processor.
Processor Alert EnableWhen enabled Processor Alert Enable activates the Processor Alert.
I/O Processor AlertThis alert is active if a failure occurs in the I/O processor.
I/O Processor ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the I/O Processor Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
I/O Processor Man RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or disabling
Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target mode when
the condition that caused I/O Processor Shutdown clears. If not enabled, the transducer block will remain Out of
Service until power is removed and restored or the user changes the transducer block target mode to Manual or
Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or
until the shutdown trigger is disabled.
Configuration Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts
71
Instruction Manual
August 2012
D103412X012
mode is placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no
longer execute transducer control function.
Output Block Timeout Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When enabled, the transducer block will return to Target mode
when the condition that caused Output Block Timeout Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
Output Block TimeoutThe Output Block Timeout (OUTPUT_BLK_TIMEOUT [76.3]) is the maximum time between
updates from the AO or DO block to the transducer block setpoint.
Blocks Set to Default
Blocks Set to Defaults AlertThis alert is active if the resource block has undergone Restart with Defaults. This will
stay active until the transducer block is changed from Out of Service.
Blocks Set to Defaults Alert EnableWhen enabled Blocks Set to Defaults Alert Enable activates the Blocks Set to
Default Alert.
Alert Key
The Alert Key (ALERT_KEY [4]) is the identification number of the plant unit. Devices in a loop or plant section can be
assigned with a common alert key to aid the operator in determining location of alerts.
Sensor Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts
Travel Sensor
Travel Sensor AlertThis alert is active if the Travel Sensor reading is outside the functional range, or the sensor
becomes disconnected.
Travel Sensor Alert EnableWhen enabled Travel Sensor Alert Enable activates the Travel Sensor Alert.
Travel Sensor ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the Travel Sensor alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
Travel Sensor Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When not enabled, the transducer block will return to Target
mode when Travel Sensor Shutdown clears. If enabled, the transducer block will remain Out of Service until power is
removed and restored or the user changes the transducer block target mode to Manual or Auto. In any case, the
target mode will remain Out of Service, if the condition that caused the shutdown remains or until the shutdown
trigger is disabled.
Pressure Sensors
Pressure A Sensor AlertThis alert is active if the Port A Pressure Sensor reading is outside the functional range.
Pressure A Sensor Alert EnableWhen enabled Pressure A Sensor Alert Enable activates the Pressure A Sensor Alert.
72
Instruction Manual
D103412X012
Pressure A Sensor ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling
Self Test Shutdown. When enabled, and the Port A Pressure Sensor Alert is active, the transducer Actual mode is
placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer
execute transducer control function.
Pressure A Sensor Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When not enabled, the transducer block will return to Target
mode when Pressure A Sensor Shutdown clears. If enabled, the transducer block will remain Out of Service until
power is removed and restored or the user changes the transducer block target mode to Manual or Auto. In any
case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or until the
shutdown trigger is disabled.
Pressure B Sensor AlertThis alert is active if the Port B Pressure Sensor reading is outside the functional range.
Pressure B Sensor Alert EnableWhen enabled Pressure B Sensor Alert Enable activates Pressure B Sensor Alert.
Supply Pressure Sensor AlertThis alert is active if the Supply Pressure Sensor reading is outside the functional
range.
Supply Pressure Sensor Alert EnableWhen enabled Supply Pressure Sensor Alert Enable activates the Supply
Pressure Sensor Alert.
Pressure Fallback
Pressure Fallback AlertThis alert is active if a travel sensor failure or a gross travel deviation has resulted in fallback
to pressure control.
Pressure Fallback Alert EnableWhen enabled Pressure Fallback Alert Enable activates the Pressure Fallback Alert.
Temperature Sensor
Temperature Sensor AlertThis alert is active if the Temperature Sensor reading is outside the functional range.
Temperature Sensor Alert EnableWhen enabled Temperature Sensor Alert Enable activates the Temperature
Sensor Alert.
Environment Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts
Supply Pressure
SupplySupply (SUPPLY_PRESSURE.VALUE [35.2]) displays the instrument supply pressure in kPa, bar, or psi.
Supply Pressure Hi AlertThis alert is active when the supply pressure exceeds the Supply Pressure Hi Alert Point.
Supply Pressure Hi Alert EnableWhen enabled Supply Pressure Hi Alert Enable activates Supply Pressure Hi Alert.
Supply Pressure Hi Alert PointThe Supply Pressure Hi Alert is active when supply pressure exceeds the Supply
Pressure Hi Alert Point (SUP_PRES_HI_ALRT_PT [76.8]).
Supply Pressure Lo AlertThis alert is active when the supply pressure is lower than the Supply Pressure Lo Alert
Point.
73
Instruction Manual
August 2012
D103412X012
Supply Pressure Lo Alert EnableWhen enabled Supply Pressure Lo Alert Enable activates Supply Pressure Lo Alert.
Supply Pressure Lo Alert PointSupply Pressure Lo Alert Point (SUP_PRES_LO_ALRT_PT [76.9]). When the supply
pressure falls below the supply pressure alert point, the supply pressure alert is active. To disable the supply
pressure alert, set Supply Pressure Alert Point to zero.
Temperature Limit
TemperatureDegrees Fahrenheit or Celsius. The temperature (TEMPERATURE [48]) is measured from a sensor
mounted on the digital valve controller's printed wiring board.
Temperature Hi AlertThis alert is active if the temperature is greater than the Temperature Hi Alert Point.
Temperature Hi Alert EnableWhen enabled Temperature Hi Alert Enable activates the Temperature Hi Alert.
Temperature Hi Alert PointThe Temperature Hi Alert is active when the instrument temperature exceeds the
Temperature Hi Alert Point (TEMP_HI_ALRT_PT [76.6]).
Temperature Lo AlertThis alert is active if the temperature is lower than the Temperature Lo Alert Point.
Temperature Lo Alert EnableWhen enabled Temperature Lo Alert Enable activates the Temperature Lo Alert.
Temperature Lo Alert PointThe Temperature Lo Alert is active when the instrument temperature is lower than the
Temperature Lo Alert Point (TEMP_LO_ALRT_PT [76.7]).
Travel Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts
Note
The alerts contained in this section are valid for both travel and pressure control.
Travel Target
Travel target is the output from the characterization function.
Travel
Travel (TRAVEL.VALUE [34.2]) displays the actual position of the valve in percent (%) of calibrated travel.
Travel Deviation
Travel DeviationTravel Deviation (TRAVEL_DEVIATION [52]) displays the absolute difference in percent between
Travel Target and Actual Travel.
Travel Deviation AlertThis alert is active if the Travel deviation exceeds the Travel Deviation Alert Point by more
than the Travel Deviation Time.
Travel Deviation Alert EnableWhen enabled Travel Deviation Alert Enable actives the Travel Deviation Alert.
74
Instruction Manual
D103412X012
August 2012
Travel Deviation Alert PointThe Travel Deviation Alert Point (TVL_DEV_ALRT_PT [77.1]) is the alert point for the
difference, expressed in percent (%), between the travel target and the actual travel. When the difference exceeds
the alert point for more than the Travel Deviation Time, the Travel Deviation Alert is set.
Travel Deviation TimeTravel Deviation Time (TVL_DEV_TIME [77.2]) is the time, in seconds, that the travel
deviation must exceed the Travel Deviation Alert Point before the alert is set.
Travel Deviation DeadbandTravel Deviation Deadband (TVL_DEV_DB [77.3]) is the travel in percent threshold (%)
of ranged travel required to clear a Travel Deviation alert, once it has been set. See figure 42.
Figure 42. Travel Hi Alert Deadband
ALERT IS SET
TRAVEL ALERT
HIGH POINT
TRAVEL ALERT
DEADBAND
ALERT IS CLEARED
A6532
Travel Limit
Travel Hi Hi AlertThis alert is active if the Travel exceeds the Travel Hi Hi Alert point.
Travel Hi Hi Alert EnableWhen enabled Travel Hi Hi Alert Enable activates the Travel Hi Hi Alert.
Travel Hi Hi Alert PointTravel Hi Hi Alert Point (TVL_HI_HI_ALRT_PT [77.18]) is the value of the travel, in percent
(%) of ranged travel, which, when exceeded, sets the Travel Alert Hi Hi alert.
Travel Hi Hi DeadbandTravel Hi Hi Deadband (TVL_HI_HI_DB [77.19]) is the travel, in percent (%) of ranged travel,
required to clear a Travel Hi Hi alert, once it has been set. See figure 42.
Travel Lo Lo AlertThis alert is active if the Travel is lower than the Travel Lo Lo Alert point.
Travel Lo Lo Alert EnableWhen enabled Travel Lo Lo Alert Enable activates the Travel Lo Lo Alert.
Travel Lo Lo Alert PointThe Travel Lo Lo alert is set when the value of the travel, in percent (%) of ranged travel,
goes below the Travel Lo Lo Alert Point (TVL_LO_LO_ALRT_PT [77.12]).
Travel Lo Lo DeadbandTravel Lo Lo Deadband (TVL_LO_LO_DB [77.13]) is the travel, in percent (%) of ranged
travel, required to clear a Travel Lo Lo alert once it has been set. See figure 43.
75
Instruction Manual
D103412X012
TRAVEL ALERT
DEADBAND
ALERT IS SET
TRAVEL ALERT
LO POINT
A65321
Travel Hi/Lo
Travel Hi AlertThis alert is active if the Travel exceeds the Travel Hi Alert point.
Travel Hi Alert EnableWhen enabled Travel Hi Alert Enable activates the Travel Hi Alert.
Travel Hi Alert PointTravel Hi Alert is set if the ranged travel rises above the Travel Hi Alert Point (TVL_HI_ALRT_PT
[77.16]). Once the alert is set, the ranged travel must fall below the alert high point set by the Travel Hi Deadband
before the alert is cleared. See figure 42.
Travel Hi DeadbandTravel Hi Deadband (TVL_HI_DB [77.17]) is the travel, in percent (%) of ranged travel, required
to clear a Travel Hi Alert, once it has been set. See figure 42.
Travel Lo AlertThis alert is active if the Travel is lower than the Travel Lo Alert point.
Travel Lo Alert EnableWhen enabled Travel Lo Alert Enable activates the Travel Lo alert.
Travel Lo Alert PointThe Travel Alert Lo alert is set when the value of the travel, in percent (%) of ranged travel,
goes below the Travel Lo Alert Point (TVL_LO_ALRT_PT [77.14]).
Travel Lo DeadbandTravel Lo Deadband (TVL_LO_DB [77.15]) is the travel, in percent (%) of ranged travel,
required to clear a travel lo alert, once it has been set. See figure 43.
Proximity Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts
Note
See page 203 for additional details on using Proximity detection.
Travel
Travel displays the actual position of the valve in percent (%) of calibrated travel.
76
Instruction Manual
D103412X012
August 2012
Travel Open
Travel Open AlertThis alert is active if the Travel is greater than the Travel Open Alert Point.
Travel Open Alert EnableWhen enabled Travel Open Alert Enable activates the Travel Open Alert.
Travel Open Alert PointTravel Open Alert Point (TVL_OPEN_ALRT_PT [77.8]) is the value of the travel in percent
(%) or ranged travel, which, when exceeded, sets the Travel Open Alert.
Travel Open DeadbandTravel Open Deadband (TVL_OPEN_DB [77.9]) is the travel in percent (%) of ranged travel
required to clear a Travel Open alert, once it has been set.
Travel Closed
This alert is active if the Travel is lower than the Travel Closed Alert Point.
Travel Closed AlertThis alert is active is the Travel goes below the Travel Closed Alert Point.
Travel Closed Alert EnableWhen enabled Travel Closed Alert Enable activates the Travel Closed Alert.
Travel Closed Alert PointThe Travel Closed Alert is set when the value of the travel, in percent (%) of ranged travel,
goes below the Travel Closed Alert Point (TVL_CLOSED_ALRT_PT [77.10]).
Travel Closed DeadbandTravel Closed Deadband (TVL_CLOSED_DB [77.11]) is the travel in percent (%) of ranged
travel required to clear a Travel Closed alert, once it has been set.
Proximity
Proximity Hi Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Hi Alert Point
and the Travel Hi Hi Deadband.
Proximity Hi Hi Alert EnableWhen enabled Proximity Hi Hi Alert Enable activates the Proximity Hi Hi Alert.
Proximity Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Alert Point and
the Travel Hi Deadband.
Proximity Hi Alert EnableWhen enabled Proximity Hi Alert Enable activates the Proximity Hi Alert.
Proximity Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Alert Point and
the Travel Lo Deadband.
Proximity Lo Alert EnableWhen enabled Proximity Lo Alert Enable activates the Proximity Lo Alert.
Proximity Lo Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Lo Alert Point
and the Travel Lo Lo Deadband.
Proximity Lo Lo Alert EnableWhen enabled Proximity Lo Lo Alert Enable activates the Proximity Lo Lo Alert.
77
Instruction Manual
D103412X012
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts
Cycle Counter
Cycle CounterThe Cycle Counter (CYCLE_COUNT [73]) records the number of times the travel changes direction.
The change in direction must occur after the deadband has been exceeded before it can be counted as a cycle. See
figure 44. You can reset the Cycle Counter by configuring it as zero.
Figure 44. Cycle Counter Deadband (set at 10%)
Deadband exceeded, and direction
changed, new Reference Point
established
Deadband Reference
Point
Deadband (+/- 5%)
Point at which
cycle is counted
A65331
Cycle Counter AlertThis alert is active if the Cycle Counter exceeds the Cycle Counter Alert Point. It is cleared after
you reset the Cycle Counter to a value less than the alert point.
Cycle Counter Alert EnableWhen enabled Cycle Counter Alert Enable activates checking of the difference between
the Cycle Counter and the Cycle Counter Alert point.
Cycle Counter Alert PointCycle Counter Alert Point (CYCLE_COUNT_ALRT_PT [77.6]) is the value of the Cycle
Counter, in cycles, which, when exceeded, sets the Cycle Counter Alert.
Cycle Counter DeadbandCycle Counter Deadband (CYCLE_COUNT_DB [77.7]) is the area around the travel
reference point, in percent (%) of ranged travel, that was established at the last increment of the Cycle Counter. This
area must be exceeded before a change in travel direction can be counted as a cycle. See figure 44.
Travel Accumulator
Travel AccumulatorTravel Accumulator (TRAVEL_ACCUM [72]) records the total change in travel, in percent (%) of
ranged travel, since the accumulator was last cleared. The value of the Travel Accumulator increments when the
magnitude of the change exceeds the Travel Accumulator Deadband. See figure 45. You can reset the Travel
Accumulator by configuring it to zero.
78
Instruction Manual
D103412X012
August 2012
Deadband Reference
Point
A6534
Travel Accumulator AlertThis alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point.
The Travel Accumulator Alert is set when the Travel Accumulator value exceeds the Travel Accumulator Alert Point.
It is cleared after you reset the Travel Accumulation to a value less than the alert point.
Travel Accumulator Alert EnableWhen enabled Travel Accumulator Alert Enable activates checking of the
difference between the Travel Accumulator value and the Travel Accumulator Alert Point.
Travel Accumulator Alert PointTravel Accumulator Alert Point (TVL_ACCUM_ALRT_PT [77.4]) is the value of the
Travel Accumulator, in percent (%) of ranged travel, which, when exceeded, sets the Travel Accumulator Alert.
Travel Accumulator DeadbandTravel Accumulator Deadband (TVL_ACCUM_DB [77.5]) is the area around the
travel reference point, in percent (%) of ranged travel, that was established at the last increment of the
accumulator. This area must be exceeded before a change in travel can be accumulated. See figure 45.
Performance Alerts
Field Communicator
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts
Note
Performance Alerts are only available with a PD tier instrument. Additionally, for the PD alerts to function properly:
The transducer block mode must not be out of service.
The travel/pressure control state must be in travel control mode, and
Bench Set Hi, Bench Set Lo, and Nominal Supply Pressure must be set in the Spec Sheets, then enable the Performance
Information instrument alert (PERF_ENABLE [75.7]).
PD Inside Status
PD Inside Status shows the status of Performance Diagnostics.
79
Instruction Manual
D103412X012
PD Run
PD Run enables or disables Performance Diagnostics in the instrument (PD Inside). Selecting PD Off disables PD Inside.
Selecting PD On enables PD Inside.
Performance Critical
Performance Critical AlertThis alert is active if the instrument is no longer able to control the valve or performance
has been dramatically reduced.
Performance Critical Alert EnableWhen enabled Performance Critical Alert Enable activates the Performance
Critical Alert.
Performance Reduced
Performance Reduced AlertThis alert is active if the instrument has detected a reduction in performance.
Performance Reduced Alert EnableWhen enabled Performance Reduced Alert Enable activates the Performance
Reduced Alert.
Performance Information
Performance Information AlertThis alert is active if the instrument has detected a condition that may pertain to
control performance.
Performance Information Alert EnableWhen enabled Performance Information Alert Enable activates the
Performance Information Alert.
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable
Failed EnableFailed Enable (FAILED_ENABLE [62]) enables or disables conditions that can cause a failed alert. A
failed alert indicates a failure within the device that will make the device or some part of the device nonoperational.
Table C2 lists the available PlantWeb alerts.
Maintenance EnableMaintenance Enable (MAINT_ENABLE [63]) enables or disables conditions that can cause a
maintenance alert. A maintenance alert indicates the device or some part of the device needs maintenance soon.
Table C2 lists the available PlantWeb alerts.
Advise EnableAdvise Enable (ADVISE_ENABLE [64]) enables or disables conditions that can cause an advisory alert.
An advisory alert indicates informative conditions that do not have a direct impact on the device's primary
functions. Table C2 lists the available PlantWeb alerts.
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting
Failed SuppressFailed Suppress (FAILED_MASK [65]) determines which of the failed alert conditions are
suppressed so that they are not reported. Even if reporting is suppressed, the bit in Failed Active (FAILED_ACTIVE
[59]) is still set.
Maintenance SuppressMaintenance Suppress (MAINT_MASK [66]) determines which of the maintenance alert
conditions are suppressed so that they are not reported. Even if reporting is suppressed, the bit in Maintenance
Active (MAINT_ACTIVE [60]) is still set.
80
Instruction Manual
D103412X012
August 2012
Advise SuppressAdvise Suppress (ADVISE_MASK [67]) determines which of the advise alert conditions are
suppressed so that they are not reported. Even if reporting is suppressed, the bit in Advise Active (ADVISE_ACTIVE
[61]) is still set.
Instrument
Field Communicator
Tag DescriptionThe Tag Description (TAG_DESC [2]) is a 32 character description used to assign a unique
description to each block within the digital valve controller to describe the intended application for the block.
Pressure UnitsDefine the output and supply pressure units (PRESSURE_UNITS [90]) in either psi, bar, or kPa.
Temperature UnitsEnter the temperature units (TEMPERATURE_UNITS [89]) in degrees Fahrenheit or Celsius. The
temperature is measured from a sensor mounted on the digital valve controller's printed wiring board.
Travel UnitsDefine the units for valve travel (TVL_UNITS [91]) in inches, centimeters, millimeters or degrees.
Length UnitsDefine the units for valve dimensions (LENGTH_UNITS [92]) in inches, centimeters, or millimeters.
Area UnitsDefine the units for actuator area (AREA_UNITS [93]) in inches2, centimeter2 or millimeter2.
Spring Rate UnitsDefine the units for actuator spring rate (SPRING_RATE_UNITS [94]) in lbs/in2 or N/M.
Relay TypeEnter the Relay Type (RELAY_TYPE [42.5]).There are three categories of relays that result in
combinations from which to select.
Relay Type: The relay type is printed on the label affixed to the relay body:
A = doubleacting or single acting
B = singleacting, reverse
C= singleacting, direct
Special App: This is used in singleacting applications where the unused output port is configured to read the
pressure downstream of a solenoid valve. See page 29 for additional information.
Lo Bleed: The label affixed to the relay body indicates it is a low bleed version.
Zero Power ConditionZero Power Condition (ZERO_PWR_COND [42.2]) identifies whether the valve is open or
closed when instrument power is lost. If you are unsure how to set this parameter, disconnect the segment loop
power to the instrument. The resulting valve travel is the Zero Power Condition.
Maximum Supply PressureEnter the maximum supply pressure (MAX_SUPP_PRESS [42.6]) in psi, bar, or kPa,
depending on what was selected for pressure units.
Calibration PersonName of the person performing last calibration (XD_CAL_WHO [31]).
Calibration LocationIndicates the location of the last instrument calibration (XD_CAL_LOC [29]).
Calibration DateEnter a date with the format MM/DD/YY. Date is a userdefined variable that provides a place to
save the date of the last calibration (XD_CAL_DATE [30]).
Last Calibration TypeIndicates the type of the last calibration performed on the instrument. Possible values are:
Not Calibrated, Single Point Calibration, Auto Calibration, Manual Calibration.
81
Instruction Manual
August 2012
D103412X012
Valve
Valve ManufacturerEnter the identification number of the manufacturer of the valve (VALVE_MAN_ID [25]) on
which the instrument is mounted. Select from the dropdown list or enter the manufacturer's identification number
as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100.
Valve Model NumberEnter the valve model number (VALVE_MODEL_NUM [26]), (design letter or type number)
for the valve on which the instrument is mounted.
Valve Serial NumberEnter the serial number of the valve (VALVE_SN [27]) on which the instrument is mounted.
Valve StyleEnter the type of valve (VALVE_TYPE [28]), slidingstem or rotary, on which the instrument is mounted.
Valve SizeEnter the size of the valve (VALVE_SIZE [83.1]) on which the instrument is mounted.
Valve ClassEnter the valve pressure class rating (VALVE_CLASS [83.2]).
Rated TravelEnter the valve rated travel (RATEDTRAVEL [83.3]) in inches or mm for sliding-stem valves, or in
degrees of rotation for rotary valves.
Actual TravelEnter the actual travel (ACTUAL_TRAVEL [83.4]) in inches or mm for sliding-stem valves, or in degrees
of rotation for rotary valves.
Shaft Stem DiameterEnter the valve stem diameter (SHAFT_STEM_DIA [83.5]) in inches or millimeters.
Packing TypeEnter the valve packing construction (PACKING_TYPE [83.6]).
Inlet PressureEnter the valve inlet pressure (INLET_PRESSURE [83.7]).
Outlet PressureEnter the valve outlet pressure (OUTLET_PRESSURE [83.8]) in psig, kPa, Bar, inHg, inH2O, or kg/cm2.
Trim
Seat TypeEnter the valve seat type (SEAT_TYPE [84.1]).
Leak ClassEnter the valve leak class (LEAK_CLASS [84.2]).
Port DiameterEnter the valve port diameter (PORT_DIAMETER [84.3]) in inches or mm.
Port TypeEnter the valve port type (PORT_TYPE [84.4]).
Flow DirectionEnter the flow direction (FLOWDIRECTION [84.5]) through the valve.
Push Down ToEnter the effect on valve movement when the stem is moved down (PUSH_DOWN_TO [84.6]).
Flow Tends ToEnter the effect on valve travel with increasing flow (FLOW_TENDS_TO [84.7]).
Unbalanced AreaEnter the valve unbalanced area (UNBALANCED_AREA [84.8]) in in2 or mm2.
82
Instruction Manual
D103412X012
August 2012
Actuator
Actuator ManufacturerEnter the manufacturer's identification number (ACT_MAN_ID [22]) of the actuator on
which the instrument is mounted. Select from the dropdown list or enter the manufacturer's identification number
as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100.
Actuator Model NumberEnter the type number for the actuator (ACT_MODEL_NUM [23]) on which the
instrument is mounted.
Actuator StyleSelect the Actuator Style (ACTUATOR_STYLE [42.1]), spring & diaphragm, piston doubleacting
without spring, piston singleacting with spring, or piston doubleacting with spring.
Actuator Serial NumberEnter the serial number (ACT_SN [24]) for the actuator on which the instrument is
mounted.
Actuator SizeEnter the size of the actuator (ACTUATOR_SIZE [85.1]) on which the instrument is mounted.
Actuator Fail ActionSets actuator action to be performed upon loss of actuator air pressure (ACT_FAIL_ACTION
[21]).
View / Edit Feedback ConnectionRefer to table 410 for Feedback Connection options. Choose the assembly that
matches the actuator travel range.
Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6200f housing) has to remain within this range throughout the entire valve travel. See figure 22. The
linear magnet assemblies are symmetrical. Either end may be up.
Travel Range
mm
Inch
Degrees
SStem #7
4.2-7
0.17-0.28
SStem #19
8-19
0.32-0.75
SStem #25
20-25
0.76-1.00
SStem #38
26-38
1.01-1.50
SStem #50
39-50
1.51-2.00
SStem #100
51-100
2.01-4.00
SStem #210
101-210
4.01-8.25
SStem #1 Roller
60-90
RShaft Window #1
60-90
RShaft Window #2
60-90
60-90
WARNING
If you answer YES to the prompt for permission to move the valve when setting the Travel Sensor Motion, the instrument
will move the valve through its full travel range. To avoid personal injury and property damage caused by the release of
83
Instruction Manual
August 2012
D103412X012
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.
Travel Sensor Motion (TRAVEL_SEN_MOTION [42.3]) establishes the proper valve travel sensor (feedback)
rotation/movement. For quarterturn actuators determine rotation by viewing the rotation of the magnet assembly
from the back of the instrument.
Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be
referred to as a magnetic array in user interface tools.
For instruments with relay A or C If increasing air pressure at output A causes the magnet assembly to move up, or the
actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet assembly
to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW. For instruments
with relay B.
For instruments with relay B If decreasing air pressure at output B causes the magnet assembly to move up, or the
actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet assembly
to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW.
Lever StyleEnter the lever style (LEVER_STYLE [85.10]) for rotary actuators as either Pivot Point or Rack and Pinion.
Lever Arm LengthDefines the lever arm length (MOMENT_ARM [85.11]) for rotary actuators.
Effective AreaEnter the actuator effective area (EFFECTIVE_AREA [85.2]) in in2, cm2, or mm2.
AirSelect Opens or Closes, indicating the effect of increasing air pressure (AIR [85.3]) on the valve travel.
Upper Bench SetEnter the upper actuator operating pressure (UPPER_BENCH_SET [85.5]).
Lower Bench SetEnter the lower actuator operating pressure (LOWER_BENCH SET [85.4]).
Nominal Supply PressureEnter the nominal instrument supply pressure (NOMINAL_SUPPLY PRESSURE [85.6]).
Spring RateEnter the actuator spring rate (SPRING_RATE [85.7]) in lbsin or Nm.
Reference
Trim Style 1Enter the valve trim style (TRIM_STYLE_1 [84.9]).
Trim Style 2Enter the valve trim style (TRIM_STYLE_2 [84.10]).
Stroking Time OpenEnter the time required to stroke the valve from closed to open (STROKING_TIME_OPEN
[85.8]).
Stroking Time CloseEnter the time required to stroke the valve from open to close (STROKING_TIME_CLOSE
[85.9]).
84
Instruction Manual
D103412X012
August 2012
Enabled
Transducer Mode,
Actual
AO / DO
PV Status(2)
AO / DO
PV Substatus
AO/DO PV
Limit Substatus(1)
OOS
Bad
Device Failure
Constant
Man
Bad
Nonspecific
Constant
Auto
Fail
Uncertain
Subnormal
Auto
Maintenance, no Fail
Uncertain
Nonspecific
Good
Advisory
Auto
Advisory, no Fail, no
Maintenance
None
Good
NonSpecific
OOS
Bad
Device Failure
Constant
Man
Bad
NonSpecific
Constant
Auto
Fail
Good
NonSpecific
Auto
Maintenance, no Fail
Good
NonSpecific
Auto
Advisory, no Fail, no
Maintenance
Good
NonSpecific
Auto
None
Good
NonSpecific
Auto
Not Enabled
Active PlantWeb
Alarms
NOTES:
X = No Effect
1. PV limit substatus reflects only READBACK limit substatus. SP limit substatus reflects only out block rate limits.
2. Firmware Revision 1.1 and earlier will set AO/DO PV Status to Bad if Feedback Sensor has failed, i.e.; Travel Sensor Fail. However, if the Travel Sensor fails, and the instrument falls back to
pressure, PV Status will remain good.
Allows the user to specify which transducer block parameter is available through each of the MAI Block channels
(MAI_CHANNEL_1 through MAI_CHANNEL_8 [95.1 through 95.8]). Transducer block parameters available to each
channel:
11
12
13
14
15
16
17
=
=
=
=
=
=
=
18
19
10
11
12
13
FINAL_VALUE
TRAVEL_TARGET
FINAL_POSITION_VALUE
TRAVEL
SUPPLY_PRESS
ACT_PRESS_A
ACT_PRESS_B
=
=
=
=
=
=
ACT_PRESS_DIFF
DRIVE_SIGNAL
TRAVEL_DEVIATION
TEMPERATURE
CYCLE_COUNT
TRAVEL_ACCUM
Transducer Mode
In Cutoff Region
Rate Limited
Limit SubStatus
AO, DO
OOS
Constant
AO, DO
MAN
Constant
AO
AUTO
High
High Limited
AO
AUTO
Low
Low Limited
AO
AUTO
High
High Limited
AO
AUTO
Low
Low Limited
AO
AUTO
None
None
Not Limited
DO
AUTO
High
High Limited
DO
AUTO
Low
Low Limited
DO
AUTO
None
Not Limited
NOTE: X = No Effect
85
Instruction Manual
D103412X012
Alert Handling
Field Communicator
Block Errors
Table 413 lists conditions reported in the BLOCK_ERR [6] and XD_ERR [11] parameters. Conditions in italics are not
applicable for the transducer block and are provided only for your reference.
Table 413. Transducer Block BLOCK_ERR and XD_ERROR Conditions
Condition Number
86
Other (N/A)
Block Configuration Error Indicates that one of the following parameters have been configured out of the proper range: 15,
16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
Simulate Active Indicates that the simulation jumper is in place on the aux terminals. This is not an indication that the I/O
blocks are using simulation data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].
10
Lost Static Data Indicates that manufacturing functional or thermal tests were incomplete
11
12
13
Device Needs Maintenance Now Indicates that manufacturing functional or thermal tests were incomplete
14
Power Up (N/A)
15
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Static Revision
ST_REV
RO
N/A
Tag Description
TAG_DESC
RW
ALL
Strategy
STRATEGY
RW
ALL
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
RW
ALL
Range
0 to 65535
0 to 65535
1 to 255
Initial Value
Protect
Category
N/A
N/A
NULL
SETUP
SETUP
SETUP
TARGET
5.1
RW
ALL
7: OOS
NONE
ACTUAL
5.2
RO
N/A
N/A
N/A
3:AUTO
4:MANUAL
7: OOS
NONE
3:AUTO
NONE
N/A
N/A
PERMITTED
5.3
RW
ALL
NORMAL
5.4
RW
ALL
Block Error
BLOCK_ERR
RO
N/A
3:AUTO
4:MANUAL
7:OOS
3: Simulate Active
10: Static Memory Failed
(Functional or thermal
data missing)
13: Maintenance
Needed Now
(Functional or thermal
data missing)
15: OutofService
Description
-Continued-
87
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
UNACKNOWLEDGED
7.1
RW
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
NONE
UPDATE_STATE
7.2
RO
N/A
0=Undefined
1=Updated reported
2=Update Not reported
N/A
TIME_STAMP
7.3
RO
N/A
N/A
STATIC_REVISION
7.4
RO
N/A
N/A
RELATIVE_INDEX
7.5
RO
N/A
N/A
RW
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
NONE
N/A
0=Undefined
1=Clear-reported
2=Clear-not reported
3=Active-reported
4=Active-not reported
N/A
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
Description
8
8.1
8.2
8.3
RO
RO
N/A
N/A
N/A
SUBCODE
8.4
RO
N/A
VALUE
8.5
RO
N/A
Value of parameter at
alarm time for a single
alarm, 0 for multiple
alarms
N/A
Transducer Directory
TRANSDUCER_DIRECTORY
RO
N/A
1,1
1,1
N/A
Transducer Type
TRANSDUCER_TYPE
10
RO
106
106
N/A
Transducer Error
XD_ERROR or TDC_ERROR
11
RO
Valid Numbers:0 = No
Error
N/A
Collection Directory
COLLECTION_DIRECTORY
12
RO
1,1,1,1,1
1,1,1,1,1
N/A
FINAL_VALUE
13
Setpoint Status
STATUS
13.1
RW
MAN
OOS
Setpoint
VALUE
13.2
RW
MAN
OOS
N/A
NONE
N/A
NONE
Setpoint Range
FINAL_VALUE_RANGE
-25 to 125
14
EU_100
14.1
RO
N/A
100
100
N/A
EU_0
14.2
RO
N/A
N/A
UNITS_INDEX
14.3
RO
N/A
PERCENT
1342
N/A
DECIMAL
14.4
RO
N/A
N/A
-Continued-
88
Instruction Manual
D103412X012
August 2012
Travel Cutoff Hi
FINAL_VALUE_CUTOFF_HI
Travel Cutoff Lo
FINAL_VALUE_CUTOFF_LO
FINAL_POSITION_VALUE
Index
Number
15
16
RO /
RW
RW
Mode
MAN
OOS
RW
MAN
OOS
Range
-25 to 125
-25 to 125
Initial Value
99.5
Protect
Category
SETUP
0.5
SETUP
N/A
N/A
17
Description
Data Type: Float
When the servo goes above this % of
span, the stem position goes to the
upper limit. Cutoffs are OFF when
Low is at -25% and high is at +125%.
Must be > low cutoff + .625%.
Data Type: Float
When the servo goes below this % of
span, the stem position goes to the
lower limit. Cutoffs are OFF when
Low is at -25% and high is at +125%.
Must be < hi cutoff - .625%.
Data Type: DS65
In Travel Control: Valve travel in %,
decharacterized to correlate with
Setpoint (FINAL_VALUE [13]).
In Pressure Control: Implied valve
travel as a % of pressure range,
decharacterized to correlate with
Setpoint (FINAL_VALUE [13]).
Controls AI channel 3.
Data Type: Float
Travel Control Only. Gain of servo.
17.1
RO
N/A
Travel (Decharacterized)
VALUE
17.2
RO
N/A
-25 to 125%
18
RW
MAN
OOS
>=0
4.4
SETUP
19
RW
MAN
OOS
9.4
SETUP
20
RW
MAN
OOS
>=0
3.0
SETUP
21
RW
MAN
OOS
0=Uninitialized
1=SelfClosing
2=SelfOpening
1=
SelfClosing
SETUP
Actuator Manufacturer
ACT_MAN_ID
22
RW
ALL
0x5100
SETUP
23
RW
ALL
Null
SETUP
24
RW
ALL
Null
SETUP
Valve Manufacturer
VALVE_MAN_ID
25
RW
ALL
0x5100
SETUP
26
RW
ALL
Null
SETUP
27
RW
ALL
Null
SETUP
Valve Style
VALVE_TYPE
28
RW
ALL
1=sliding-stem
SETUP
Calibration Location
XD_CAL_LOC
29
RW
ALL
Null
CAL
Calibration Date
XD_CAL_DATE
30
RW
ALL
Uninitialized
CAL
Calibration Person
XD_CAL_WHO
31
RW
ALL
Null
CAL
1=sliding-stem
2=Rotary
N/A
-Continued-
89
Instruction Manual
D103412X012
SETPOINT_D
Index
Number
RO /
RW
Mode
32.1
RW
MAN
OOS
Setpoint(D)
VALUE
32.2
RW
MAN
OOS
33.1
RO
N/A
Travel (D)
VALUE
33.2
RO
N/A
NONE
0 = closed 1 = open
5,10,15.. = %
NONE
N/A
0 = closed 1 = open
5,10,15.. = %
N/A
34
Travel Status
STATUS
34.1
RO
N/A
N/A
Travel
VALUE
34.2
RO
N/A
N/A
SUPPLY_PRESSURE
35.1
RO
N/A
N/A
Supply Pressure
VALUE
35.2
RO
N/A
N/A
36
Pressure A Status
STATUS
36.1
RO
N/A
N/A
Pressure A
VALUE
36.2
RO
N/A
N/A
PRESSURE_B
Description
Data Type: DS_66
SETPOINT_D is not updated unless
the DO block is selected in
FEATURE_SEL.
STATUS indicates the validity of
value, set by the DO block
OUT.STATUS
VALUE is the discrete value of
setpoint. Only values of 0, 1, or
increments of 5 up to 95 are
allowed. Written by DO channel 22.
Data Type: DS_66
STATUS indicates the validity of
VALUE.
VALUE: 0=closed , 1=open
5,10,15.. = %. Controls DI Channel
23
Data Type: DS65
In Travel Control: Actual valve travel
in % of calibrated travel range.
In Pressure Control: Implied valve
travel in % of pressure range.
Controls AI channel 4.
35
PRESSURE_A
37
Pressure B Status
STATUS
37.1
RO
N/A
N/A
Pressure B
VALUE
37.2
RO
N/A
N/A
-Continued-
90
Protect
Category
33
Travel(D) Status
STATUS
TRAVEL
Initial Value
32
Setpoint(D) Status
STATUS
TRAVEL_D
Range
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
38
38.1
RO
N/A
N/A
Pressure Differential
VALUE
38.2
RO
N/A
N/A
PWA Simulate
PWA_SIMULATE
39
Grant Deny
GRANT_DENY
40
RO or
RW*
ALL
GRANT
40.1
RW
ALL
DENY
40.2
RW
ALL
1=Simulate Off
2=Simulate Enabled
0:Program
1:Tune
2:Alarm
3:Local
Description
Data Type: DS65
STATUS indicates the validity of
VALUE. VALUE is the difference
between PRESSURE_A and
PRESSURE_B, controls AI channel 8.
Data Type: Enum (Uint8)
When this is set to 2 all the alert
ACTIVE parameters can be written,
except for INST_ALERTS_ACTIVE.
SHUTDOWN_ALERT_ACTIVE. This
allows alerts to be simulated for
testing with hosts. NOTE: only
ACTIVE parameters are affected by
this. * PWA Simulate is RW only if a
jumper is installed across the Aux
Terminal. If no jumpered is installed
across the Aux Terminal, PWA
Simulate is RO.
1=Simulate Off
ALL
NONE
NONE
1=Travel
SETUP
N/A
41
Travel/Pressure Select
TVL_PRESS_SELECT
41.1
RW
ALL
1=Travel
2=Pressure
3=TVL/PRESS Auto Recv
4=TVL/PRESS Man Recv
Travel/Pressure State
TVL_PRESS_STATE
41.2
RO
N/A
1=Travel
2=Pressure
-Continued-
91
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Protect
Category
Description
42
Actuator Style
ACTUATOR_STYLE
42.1
RW
MAN
OOS
1=Spring &
Diaphragm
SETUP
42.2
RW
MAN
OOS
1=Valve Closed
2=Valve Open
1=Valve Closed
SETUP
42.3
RW
MAN
OOS
1=Counter Clockwise
2=Clockwise
1=Counter
Clockwise
SETUP
MAN
OOS
SETUP
SETUP
Feedback Connection
FEEDBACK_CONN
42.4
RW
Relay Type
RELAY_TYPE
42.5
RW
MAN
OOS
1=Relay A or CDouble or
Single Direct
2=Relay BSingle Reverse
5=Relay CSpecial App.
Single Direct
6=Relay BSpecial App.
Single Reverse
9=LoBleed Relay A or
=Relay A or
CDouble or Single
CDouble or
Direct
Single Direct
10=LoBleed Relay B
Single Reverse
13=LoBleed Relay
CSpecial App.Single
Direct
10=LoBleed Relay
BSpecial App.-Single
Reverse
42.6
RW
MAN
OOS
35 psig
SETUP
Pressure Range Hi
PRESS_RANGE_HI
42.7
RW
MAN
OOS
15.0 psig
SETUP
Pressure Range Lo
PRESS_RANGE_LO
42.8
RW
MAN
OOS
3.0 psig
SETUP
42.9
RW
MAN
OOS
SETUP
42.10
RW
MAN
OOS
1=B, 2= C, ...12=M
23=X
2=C
SETUP
42.11
RW
MAN
OOS
2=C
SETUP
-Continued-
92
Initial Value
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
43
Travel Count
TVL_COUNT
43.1
RO
N/A
Travel Hi Calibration
TVL_HI_CAL
43.2
RW
MAN
OOS
<TVL_FAC_HI
>TVL_LO_CAL
CAL
Travel Lo Calibration
TVL_LO_CAL
43.3
RW
MAN
OOS
>TVL_FAC_LO
<TVL_HI_CAL
CAL
Travel Crossover
TVL_CROSSOVER
43.4
RW
MAN
OOS
50%
CAL
Travel Fac Hi
TVL_FAC_HI
43.5
RO
N/A
Set by Factory
N/A
Travel Fac Lo
TVL_FAC_LO
43.6
RO
N/A
Set by Factory
N/A
Travel IP Bias
TVL_IP_BIAS
43.7
RW
MAN
OOS
0% - 100%
70%
CAL
43.8
RW
MAN
OOS
0 - 100%
50%
CAL
43.9
RW
MAN
OOS
0: Not Calibrated
1: Single Point Calibration
2: Auto Calibration CAL
2: Auto Calibration
3: Manual Calibration
TRAVEL_TUNE
44
44.1
RW
MAN
OOS
1=Off
2=On
2=On
SETUP
44.2
RW
MAN
OOS
0% - 100%
30%
SETUP
RW
MAN
OOS
-100% - 0%
-30%
SETUP
0% - 2%
0.25%
SETUP
>=0
35
SETUP
44.3
44.4
RW
MAN
OOS
44.5
RW
MAN
OOS
-Continued-
93
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Protect
Category
Description
45
45.1
RW
MAN
45.2
RO
N/A
45.3
Reserved
TVL_CAL_RESERVED
45.4
RO
N/A
1: Operating
2: Autocalibrate
3: Not Used by DVC6200f
4: Mark Full Open
5: Mark Full Closed
6: Manual Calibrate Final
7: Abort
8: Clear Cal Status
9: Manual Calibrate Init
10: Manual Calibrate
Restore
11: Reset Travel Sensor
Error
12: Reserved
1=Operating
13: Execute Performance
Tuner
14: Execute Performance
Tuner (Graphite Packing)
16: Execute Performance
Tuner (Booster)
17: Execute Performance
Tuner (Graphite Packing
and Booster)
19: Autocalibration, Set
Filter
20: Autocalibrate
Extended, Set Filter
0%
0: auto cal complete
1: calibration complete
2: auto cal in progress
3: manual cal in progress
3: Not Used by DVC6200f
5: upper position marked
6: lower position marked
7: calibration error
8: Performance Tuner
active
no bits set
9: Performance Tuner
Success
10: Performance Tuner
Error (No movement)
11: Performance Tuner
Error (Accessories
unstable)
12: Performance Tuner
Error (Other)
CAL
N/A
N/A
Reserved
-Continued-
94
Initial Value
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
46
46.1
RW
MAN
OOS
>0
CAL
46.2
RW
MAN
OOS
0 to 16383
CAL
Pressure A Scale
PRESS_A_SCALE
46.3
RW
MAN
OOS
>0
CAL
Pressure A Offset
PRESS_A_OFFSET
46.4
RW
MAN
OOS
0 to 16383
CAL
>0
CAL
CAL
Pressure B Scale
PRESS_B_SCALE
46.5
RW
MAN
OOS
Pressure B Offset
PRESS_B_OFFSET
46.6
RW
MAN
OOS
0 to 16383
Pressure IP Bias
PRESS_IP_BIAS
46.7
RW
MAN
OOS
0-100%
70%
CAL
46.8
RW
MAN
OOS
0-100%
50%
CAL
RW
MAN
OOS
-25 -125%,
> CUTOFF_LO
99.50%
SETUP
0.50%
SETUP
PRESS_TUNE
Pressure Cutoff Hi
PRESS_CUTOFF_HI
47
47.1
Pressure Cutoff Lo
PRESS_CUTOFF_LO
47.2
RW
MAN
OOS
47.3
RW
MAN
OOS
> = 0, < 32
2.2
SETUP
47.4
RW
MAN
OOS
> = 0, < 32
0.1
SETUP
47.5
RW
MAN
OOS
SETUP
47.6
RW
MAN
OOS
0.25%
SETUP
47.7
RW
MAN
OOS
20%
SETUP
47.8
RW
MAN
OOS
-20%
SETUP
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
47.9
RW
MAN
OOS
12%
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
47.10
RW
MAN
OOS
-12%
47.11
RW
MAN
OOS
35
SETUP
Temperature
TEMPERATURE
48
RO
N/A
N/A
N/A
Target Travel
TRAVEL_TARGET
49
RO
Status
STATUS
49.1
RO
MAN
OOS
N/A
Value
VALUE
49.2
RO
MAN
OOS
N/A
RW
MAN
OOS
Input Characterization
INPUT_CHAR
50
1=Linear
2=Equal %
3=Quick Opening
4=Reserved
5=Custom
1=Linear
SETUP
-Continued-
95
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Protect
Category
0 to 100%
N/A
N/A
0 to 100%
N/A
RO
N/A
0 to 100%
N/A
RO
N/A
-100% to 100%
N/A
RW
MAN
OOS
Travel Deviation
TRAVEL_DEVIATION
52
RO
N/A
Drive Signal
DRIVE_SIGNAL
53
RO
Drive Current
DRIVE_CURRENT
54
MLFB
MLFB
55
Failed Alarm
FAILED_ALM
56
Linear, Y=X
ALL
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
NONE
0=Undefined
1=Clear-reported
2=Clear-not reported
3=Active-reported
4=Active-not reported
0=Undefined
N/A
ALARM_STATE
56.2
RO
N/A
TIME_STAMP
56.3
RO
N/A
N/A
SUBCODE
56.4
RO
N/A
N/A
VALUE
56.5
RO
N/A
N/A
Maintenance Alarm
MAINT_ALM
57
UNACKNOWLEDGED
57.1
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
NONE
0=Undefined
1=Clear-reported
2=Clear-not reported
3=Active-reported
4=Active-not reported
0=Undefined
N/A
ALARM_STATE
57.2
RO
N/A
TIME_STAMP
57.3
RO
N/A
N/A
SUBCODE
57.4
RO
N/A
N/A
VALUE
57.5
RO
N/A
N/A
-Continued-
96
Description
SETUP
51
56.1
Initial Value
Custom Points
CUSTOM_POINTS
UNACKNOWLEDGED
Range
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
58
58.1
Description
Data Type: DS71
Used to report alerts to host system
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
NONE
0:Undefined
1:Clear-reported
2:Clear-not reported
3:Active-reported
4:Active-not reported
0=Undefined
N/A
ALARM_STATE
58.2
RO
N/A
TIME_STAMP
58.3
RO
N/A
N/A
SUBCODE
58.4
RO
N/A
N/A
VALUE
58.5
RO
N/A
N/A
N/A
0:Drive Current
1:Drive Signal
2:Processor Impaired
3:Output Block Timeout
4:Blocks Set to Defaults
5:Travel Sensor
6:Outlet Pressure Sensor
7:Supply Pressure
Sensor
8:Temperature Sensor
9:Supply Pressure
All bits: 0
10:Temperature Limit
11:Travel Deviation
12:Travel Limit
13:Travel Accumulator
14:Cycle Counter
15:Performance Critical
16:Performance
Reduced
17:Performance
Information
18: Shutdown Alert
N/A
N/A
0:Drive Current
1:Drive Signal
2:Processor Impaired
3:Output Block Timeout
4:Blocks Set to Defaults
5:Travel Sensor
6:Outlet Pressure Sensor
7:Supply Pressure
Sensor
8:Temperature Sensor
9:Supply Pressure
All bits: 0
10:Temperature Limit
11:Travel Deviation
12:Travel Limit
13:Travel Accumulator
14:Cycle Counter
15:Performance Critical
16:Performance
Reduced
17:Performance
Information
18: Shutdown Alert
N/A
Failed Active
FAILED_ACTIVE
Maintenance Active
MAINT_ACTIVE
59
60
RO(1)
RO(1)
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-
97
Instruction Manual
D103412X012
Advise Active
ADVISE_ACTIVE
Failed Enable
FAILED_ENABLE
Maintenance Enable
MAINT_ENABLE
Advise Enable
ADVISE_ENABLE
Failed Suppress
FAILED_MASK
Index
Number
61
62
63
64
65
RO /
RW
RO(1)
RW
RW
RW
RW
Mode
N/A
ALL
ALL
ALL
ALL
Range
0:Drive Current
1:Drive Signal
2:Processor Impaired
3:Output Block Timeout
4:Blocks Set to Defaults
5:Travel Sensor
6:Outlet Pressure Sensor
7:Supply Pressure
Sensor
8:Temperature Sensor
9:Supply Pressure
All bits: 0
10:Temperature Limit
11:Travel Deviation
12:Travel Limit
13:Travel Accumulator
14:Cycle Counter
15:Performance Critical
16:Performance
Reduced
17:Performance
Information
18: Shutdown Alert
Same as for
FAILED_ACTIVE above
Enabled Bits:
0: Drive Current
2: Processor
Impaired
4: Blocks Set to
Default
5: Travel Sensor
15: Performance
Critical
18: Shutdown
Alert
Same as for
MAINT_ACTIVE above
Enabled Bits:
1: Drive Signal
3: Output Block
Timeout
6: Outlet Pressure
Sensor
9: Supply Pressure
11: Travel
Deviation
13: Travel
Accumulator
14: Cycle Counter
16: Performance
Reduced
Same as for
ADVISE_ENABLE above
Enabled Bits:
8: Temperature
Sensor
9: Supply Pressure
Sensor
10: Temperature
Limit
12: Travel Limit
Same as for
FAILED_ACTIVE above
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-
98
Initial Value
All bits: 0
Protect
Category
Description
N/A
ALL
ALL
ALL
ALL
Instruction Manual
D103412X012
August 2012
Maintenance Suppress
MAINT_MASK
Index
Number
66
RO /
RW
RW
Mode
ALL
Range
Same as for
MAINT_ACTIVE above
Initial Value
All bits: 0
Protect
Category
Description
ALL
Advise Suppress
ADVISE_MASK
67
RW
ALL
Same as for
ADVISE_ENABLE above
All bits: 0
ALL
Failed Priority
FAILED_PRI
68
RW
ALL
0 to 15
SETUP
Maintenance Priority
MAINT_PRI
69
RW
ALL
0 to 15
SETUP
Advise Priority
ADVISE_PRI
70
RW
ALL
0 to 15
SETUP
Recommended Action
RECOMMENDED_ACTION
71
RO
N/A
0 to 65535
N/A
Travel Accumulator
TRAVEL_ACCUM
72
RW
ALL
Write:Anything
Read:Actual
CAL
ALL
Write:Anything
Read:Actual
CAL
Cycle Count
CYCLE_COUNT
73
RW
-Continued-
99
Instruction Manual
D103412X012
Electronics Active
ELECT_ACTIVE
Index
Number
RO /
RW
Mode
Range
Protect
Category
Description
74
74.1
RO(1)
ALL
0:Drive Current
1:Drive Signal
2:Memory Failure Pending
3:Static Memory
4:Processor
5:I/O Processor
6:Output Block Timeout
7:Block Set to Defaults
All bits: 0
N/A
N/A
N/A
Sensor Active
SENSOR_ACTIVE
74.2
RO(1)
ALL
0:Travel Sensor
1:Port A Pressure Sensor
2:Port B Pressure Sensor
3:Supply Pressure
All bits: 0
Sensor
4:Temperature Sensor
5: Pressure Fallback
Environment Active
ENVIRO_ACTIVE
74.3
RO(1)
ALL
ALL
0:Travel Deviation
1:Travel High High
2:Travel Low Low
3:Travel High
4:Travel Low
All bits: 0
N/A
All bits: 0
N/A
Travel Active
TRAVEL_ACTIVE
74.4
RO(1)
All bits: 0
Proximity Active
PROX_ACTIVE
74.5
RO(1)
N/A
0:Travel Open
1:Travel Closed
2:Proximity High High
3:Proximity High
4:Proximity Low
5:Proximity Low Low
74.6
RO(1)
ALL
0:Cycle Counter
1:Travel Accumulator
All bits: 0
N/A
Performance Active
PERF_ACTIVE
74.7
RO(1)
ALL
0:Performance Critical
1:Performance Reduced
2:Performance
Information
All bits: 0
N/A
ALL
N/A
PD Event Active
PD_EVENT_ACTIVE
74.8
RO(1)
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-
100
Initial Value
All bits: 0
Instruction Manual
D103412X012
August 2012
PD Detail 1 Active
PD_DETAIL1_ACTIVE
PD Detail 2 Active
PD_DETAIL2_ACTIVE
PD Detail 3 Active
PD_DETAIL3_ACTIVE
PD Detail 4 Active
PD_DETAIL4_ACTIVE
Index
Number
74.9
74.10
74.11
74.12
RO /
RW
RO(1)
RO(1)
RO(1)
RO(1)
Mode
ALL
Range
0:I/P Primary Plugged
1:I/P Nozzle Plugged
2:I/P Latched
3:Reserved
4:Relay Jammed
5:Relay Cross Misadj
6:Relay Bias Diaph Leak
7:Relay Port A Diaph
Leak
8:Relay Port B Diaph
Leak
9:Reserved
10:Valve Stuck Low or
Sensor Arm Damage
11:Valve Stuck High or
Sensor Arm Damage
12:Piston Ring Leak
13:Reserved
14:Low Supply Pressure
15:External Leak
16:SOV Trip
17:Air Line Blocked
18:Reserved
19:Reserved
20:Unknown
ALL
Reserved
ALL
ALL
Reserved
Initial Value
All bits:0
All bits: 0
All bits: 0
All bits: 0
Protect
Category
Description
N/A
N/A
N/A
N/A
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-
101
Instruction Manual
D103412X012
PD Detail 5 Active
PD_DETAIL5_ACTIVE
PD Detail 6 Active
PD_DETAIL6_ACTIVE
Shutdown Alerts
SHUTDOWN_ALERTS_ACTIVE
Index
Number
74.13
74.14
74.15
RO /
RW
RO(1)
RO(1)
RO
Mode
ALL
Range
0: Relay Disengaged
1: Insufficient Pressure
Differential
2: Travel Calibration Error
3: Reserved
4: High Supply Pressure*
5: Reserved
6: Near a Travel Cutoff Or
Stop
7:Reserved
8: Spec Sheet Fields
All bits: 0
Incomplete*
9: Sensor Failure*
10: Pressure Control
Active
11: Transducer Block
Mode OOS
12: Not Authorized for PD
13: PD Run Disabled*
14: Trigger Data
Available*
ALL
Reserved
N/A
0:Drive Current
1:Program Memory
2:Static Memory
3:Processor or I/O
Processor
All bits: 0
4:Travel Sensor
5:Port A Pressure Sensor
6: Output Block Timeout
7-31:(Reserved)
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-
102
Initial Value
All bits: 0
Protect
Category
N/A
Description
N/A
N/A
Instruction Manual
D103412X012
August 2012
Electronics Enable
ELECT_ENABLE
Sensor Enable
SENSOR_ENABLE
Environment Enable
ENVIRO_ENABLE
Travel Enable
TRAVEL_ENABLE
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
75
75.1
75.2
75.3
75.4
RW
RW
RW
RW
Enabled Bits:
0: Drive Current
1: Drive Signal
2: Program
Memory
3: Static Memory
4: Processor
5: I/O Processor
7: Block Set to
Default
ALL
0:Drive Current
1:Drive Signal
2:Program Memory
3:Static Memory
4:Processor
5:I/O Processor
6:Output Block Timeout
7:Blocks Set to Defaults
SETUP
ALL
Enabled Bits:
0:Travel Sensor
1:Port A Pressure
0:Travel Sensor
1:Port A Pressure Sensor Sensor
2:Port B Pressure Sensor 2:Port B Pressure
SETUP
Sensor
3:Supply Pressure
3:Supply Pressure
Sensor
Sensor
4:Temperature Sensor
4:Temperature
Sensor
ALL
Enabled Bits:
0:Supply Pressure
High
2:Temperature
SETUP
High
3:Temperature
Low
ALL
0:Travel Deviation
1:Travel High High
2:Travel Low Low
3:Travel High
4:Travel Low
Enabled Bits:
0:Travel
Deviation
SETUP
All bits: 0
SETUP
Proximity Enable
PROX_ENABLE
75.5
RW
ALL
0:Travel Open
1:Travel Closed
2:Proximity High High
3:Proximity High
4:Proximity Low
5:Proximity Low Low
75.6
RW
ALL
0:Cycle Counter
1:Travel Accumulator
All bits: 0
SETUP
ALL
0:Performance Critical
1:Performance Reduced
2:Performance
Information
Enabled Bits:
0:Performance
Critical
1:Performance
Reduced
SETUP
Performance Enable
PERF_ENABLE
75.7
RW
-Continued-
103
Instruction Manual
D103412X012
Shutdown Trigger
SHUTDOWN_TRIGGER
Index
Number
RO /
RW
Mode
Range
Protect
Category
Description
76
76.1
RW
ALL
0:Drive Current
1:Program Memory
2:Static Memory
3:Processor or I/O
Processor
All bits: 0
4:Travel Sensor
5:Port A Pressure Sensor
6: Output Block Timeout
7-31:(Reserved)
SETUP
SETUP
Shutdown Recovery
SHUTDOWN_RECOVERY
76.2
RW
ALL
0:(reserved)
1:Program Memory
2:Static Memory
3:Processor or I/O
Processor
All bits: 0
4:Travel Sensor
5:Port A Pressure Sensor
6: Output Block Timeout
7-31:(Reserved)
76.3
RW
ALL
600 sec
SETUP
76.4
RW
ALL
25%
SETUP
76.5
RW
ALL
5 sec
SETUP
76.6
RW
ALL
186 deg F
SETUP
76.7
RW
ALL
-63 deg F
SETUP
76.8
RW
ALL
145 psig
SETUP
76.9
RW
ALL
15 psig
SETUP
INST_ALERTS_CONFIG2
77
77.1
RW
ALL
5%
SETUP
77.2
RW
ALL
10 sec
SETUP
77.3
RW
ALL
2%
SETUP
77.4
RW
ALL
>=0
1,000,000
SETUP
77.5
RW
ALL
0 - 100%
1%
SETUP
77.6
RW
ALL
>=0
1,000,000
SETUP
77.7
RW
ALL
0 - 100%
1%
SETUP
-Continued-
104
Initial Value
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
77.8
RW
ALL
-25% to 125%
99.5%
SETUP
77.9
RW
ALL
1%
SETUP
77.10
RW
ALL
-25% to 125%
0.5%
SETUP
77.11
RW
ALL
1%
SETUP
77.12
RW
ALL
-25% to 125%
-25%
SETUP
Travel Lo Lo Deadband
TVL_LO_LO_DB
77.13
RW
ALL
5%
SETUP
77.14
RW
ALL
-25% to 125%
-25%
SETUP
Travel Lo Deadband
TVL_LO_DB
77.15
RW
ALL
5%
SETUP
77.16
RW
ALL
-25% to 125%
125%
SETUP
Travel Hi Deadband
TVL_HI_DB
77.17
RW
ALL
5%
SETUP
77.18
RW
ALL
-25% to 125%
125%
SETUP
Travel Hi Hi Deadband
TVL_HI_HI_DB
77.19
RW
ALL
5%
SETUP
-Continued-
105
Instruction Manual
D103412X012
Index
RO /
Number RW
78
RO
Mode
N/A
Range
Initial Value
Protect
Category
0:
All bits: 0
2: Integrator Limited Low
3: Integrator Limited
High
4: Travel Sensor Span
Error
5: MLFB Error
7: Travel Sensor High
Error
8: Travel Sensor Low Error
9: Pressure Sensor B
10: Pressure Sensor A
11: Supply Pressure
Sensor
13: IOP Failure
14: Drive Current
15: Simulate Jumper ON
Description
Health Index
HEALTH_INDEX
79
RO
N/A
Reserved A
RESERVED_A
80
RW
ALL
0 - 100
-Continued-
106
100
N/A
N/A
SETUP
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
81
RW
ALL
SETUP
82
RO
N/A
N/A
83
Valve Size
VALVE_SIZE
83.1
RW
ALL
NULL
ALL
Valve Class
VALVE_CLASS
83.2
RW
ALL
NULL
ALL
Rated Travel
RATEDTRAVEL
83.3
RW
ALL
0.00
ALL
Actual Travel
ACTUAL_TRAVEL
83.4
RW
ALL
0.00
ALL
83.5
RW
ALL
0.00
ALL
Packing Type
PACKING_TYPE
83.6
RW
ALL
NULL
ALL
Inlet Pressure
INLET_PRESSURE
83.7
RW
ALL
0.00
ALL
Outlet Pressure
OUTLET_PRESSURE
83.8
RW
ALL
0.00
ALL
RW
ALL
NULL
ALL
1= I
ALL
SPEC_SHEET_TRIM
Seat Type
SEAT_TYPE
84
84.1
Leak Class
LEAK_CLASS
84.2
RW
ALL
Port Diameter
PORT_DIAMETER
84.3
RW
ALL
0.00
ALL
ALL
1=balanced
2=unbalanced
ALL
RW
ALL
1=up
2=down
ALL
84.6
RW
ALL
1=open
2=close
ALL
Flow Tends To
FLOW_TENDS_TO
84.7
RW
ALL
1=open
2=close
ALL
Unbalanced Area
UNBALANCED_AREA
84.8
RW
ALL
0.00
ALL
Trim Style 1
TRIM_STYLE_1
84.9
RW
ALL
NULL
ALL
Trim Style 2
TRIM_STYLE_2
84.10
RW
ALL
NULL
ALL
Port Type
PORT_TYPE
84.4
RW
Flow Direction
FLOWDIRECTION
84.5
Push Down To
PUSH_DOWN_TO
-Continued-
107
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Protect
Category
Description
85
Actuator Size
ACTUATOR SIZE
85.1
RW
ALL
NULL
ALL
Effective Area
EFFECTIVE AREA
85.2
RW
ALL
0.00
ALL
Air
AIR
85.3
RW
ALL
ALL
85.4
RW
ALL
0.00
ALL
85.5
RW
ALL
0.00
ALL
85.6
RW
ALL
0.00
ALL
Spring Rate
SPRING_RATE
85.7
RW
ALL
0.00
ALL
85.8
RW
ALL
0.00
ALL
85.9
RW
ALL
0.00
ALL
Lever Style
LEVER_STYLE
85.10
RW
ALL
ALL
85.11
RW
ALL
0.00
ALL
DEVICE_RECORD
1=open
2=close
1=Pivot Point
2=Rack & Pinion
86
Temperature Maximum
TEMP_MAX
86.1
RO
N/A
-9999.99
N/A
86.2
RO
N/A
Zero time
N/A
Temperature Minimum
TEMP_MIN
86.3
RO
N/A
9999.99
N/A
86.4
RO
N/A
Zero time
N/A
86.5
RO
N/A
0.0
N/A
86.6
RO
N/A
Zero time
N/A
86.7
RO
N/A
9999.99
N/A
86.8
RO
N/A
Zero time
N/A
86.9
RW
N/A
SETUP
NONE
Protection
PROTECTION
87
RW
ALL
1=None
2=Calibration
3=Setup & Calibration
4=All
-Continued-
108
Initial Value
2=Calibration
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
88
PD Run
PD_COMMAND
88.1
RW
AUTO
MAN
1=PD On
2=PD Off
NONE
PD Status
PD_STATUS
88.2
RO
ALL
1=Not Running
2=Running
NONE
PD Configuration
PD_CONFIG
88.3
RW
ALL
NONE
PD Extra
PD_EXTRA
88.4
RW
ALL
NONE
Temperature Units
TEMPERATURE_UNITS
89
RW
ALL
C=1001
F=1002
SETUP
kPa
SETUP
1=PD On
Pressure Units
PRESSURE_UNITS
90
RW
ALL
kPa=1133
bar=1137
psig=1143
inHg=1155
inH2O=1146
Kg/cm2=1145
Travel Units
TVL_UNITS
91
RW
ALL
cm=1012
mm=1013
in=1019
deg=1005
mm
SETUP
Length Units
LENGTH_UNITS
92
RW
ALL
cm=1012
mm=1013
in=1019
mm
SETUP
Area Units
AREA_UNITS
93
RW
ALL
cm2=1025
mm2=1027
in2=1030
cm2
SETUP
94
RW
ALL
N/m=1165
lb/in=1596
N/m
SETUP
MAI_CHANNEL_MAP
95
MAI Channel 1
MAI_CHANNEL_1
95.1
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 2
MAI_CHANNEL_2
95.2
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 3
MAI_CHANNEL_3
95.3
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 4
MAI_CHANNEL_4
95.4
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 5
MAI_CHANNEL_5
95.5
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 6
MAI_CHANNEL_6
95.6
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 7
MAI_CHANNEL_7
95.7
RW
MAN,
OOS
1 through 13
SETUP
MAI Channel 8
MAI_CHANNEL_8
95.8
RW
MAN,
OOS
1 through 13
SETUP
RW
MAN,
OOS
1: AO Block
2: DO Block
96
97
RW
MAN,
OOS
1: No
2: Yes
1: AO Block
1: No
SETUP
SETUP
-Continued-
109
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Initial Value
Protect
Category
Description
Block Information
BLOCK_INFO
98
RO
Reserved B
RESERVED_B
99
RW
Travel Always
TRAVEL_ALWAYS
100
RO
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 415. Transducer Block, View 1
Index Number
1
Parameter
ST_REV
5.1
MODE_BLK.TARGET
10
5.2
MODE_BLK.ACTUAL
14.1
FINAL_VALUE_RANGE.EU_100
5.3
MODE_BLK.PERMITTED
14.2
FINAL_VALUE_RANGE.EU_0
5.4
MODE_BLK.NORMAL
14.3
FINAL_VALUE_RANGE.UNITS_INDEX
BLOCK_ERR
14.4
FINAL_VALUE_RANGE.DECIMAL
10
TRANSDUCER_TYPE
11
XD_ERROR
13.1
FINAL_VALUE.STATUS
13.2
FINAL_VALUE.VALUE
17.1
FINAL_POSITION_VALUE.STATUS
17.2
FINAL_POSITION_VALUE.VALUE
32.1
SETPOINT_D.STATUS
32.2
SETPOINT_D.VALUE
15
FINAL_VALUE_CUTOFF_HI
16
FINAL_VALUE_CUTOFF_LO
18
SERVO_GAIN
19
SERVO_RESET
20
SERVO_RATE
21
ACT_FAIL_ACTION
40.1
GRANT_DENY.GRANT
40.2
GRANT_DENY.DENY
50
110
Parameter
INPUT_CHAR
Instruction Manual
D103412X012
August 2012
Note
Because individual views are limited in size, View Lists 3 and 4 have multiple parts.
Parameter
ST_REV
Parameter
ST_REV
5.1
MODE_BLOCK.TARGET
74.1
INST_ALERTS_ACTIVE.ELECT_ACTIVE
5.2
MODE_BLOCK.ACTUAL
74.2
INST_ALERTS_ACTIVE.SENSOR_ACTIVE
5.3
MODE_BLOCK.PERMITTED
74.3
INST_ALERTS_ACTIVE.ENVIRO_ACTIVE
5.4
MODE_BLOCK.NORMAL
74.4
INST_ALERTS_ACTIVE.TRAVEL_ACTIVE
BLOCK_ERR
74.5
INST_ALERTS_ACTIVE.PROX_ACTIVE
10
TRANSDUCER_TYPE
74.6
INST_ALERTS_ACTIVE.TVL_HISTORY_ACTIVE
11
XD_ERROR
74.7
INST_ALERTS_ACTIVE.PERF_ACTIVE
13.1
FINAL_VALUE.STATUS
74.8
INST_ALERTS_ACTIVE.PD_EVENT_ACTIVE
13.2
FINAL_VALUE.VALUE
74.9
INST_ALERTS_ACTIVE.PD_DETAIL1_ACTIVE
17.1
FINAL_POSITION_VALUE.STATUS
74.10
INST_ALERTS_ACTIVE.PD_DETAIL2_ACTIVE
17.2
FINAL_POSITION_VALUE.VALUE
74.11
INST_ALERTS_ACTIVE.PD_DETAIL3_ACTIVE
32.1
SETPOINT_D.STATUS
74.12
INST_ALERTS_ACTIVE.PD_DETAIL4_ACTIVE
32.2
SETPOINT_D.VALUE
74.13
INST_ALERTS_ACTIVE.PD_DETAIL5_ACTIVE
35.1
SUPPLY_PRESSURE.STATUS
78
SELFTEST_STATUS
35.2
SUPPLY_PRESSURE.VALUE
79
HEALTH_INDEX
36.1
PRESSURE_A.STATUS
86.1
DEVICE_RECORD.TEMP_MAX
36.2
PRESSURE_A.VALUE
86.2
DEVICE_RECORD.TEMP_MAX_TIME
37.1
PRESSURE_B.STATUS
86.3
DEVICE_RECORD.TEMP_MIN
37.2
PRESSURE_B.VALUE
86.4
DEVICE_RECORD.TEMP_MIN_TIME
38.1
PRESSURE_DIFF.STATUS
86.5
DEVICE_RECORD.SUPP_PRESS_MAX
38.2
PRESSURE_DIFF.VALUE
86.6
DEVICE_RECORD.SUPP_PRESS_MAX_TIME
48
TEMPERATURE
86.7
DEVICE_RECORD.SUPP_PRESS_MIN
49
TRAVEL_TARGET
86.8
DEVICE_RECORD.SUPP_PRESS_MIN_TIME
52
TRAVEL_DEVIATION
53
DRIVE_SIGNAL
54
DRIVE_CURRENT
55
MLFB
Index Number
59
FAILED_ACTIVE
ST_REV
60
MAINT_ACTIVE
STRATEGY
61
ADVISE_ACTIVE
ALERT_KEY
71
RECOMMEND_ACTION
10
TRANSDUCER_TYPE
72
TRAVEL_ACCUM
22
ACT_MAN_ID
73
CYCLE_COUNT
23
ACT_MODEL_NUM
75.1
INST_ALERTS_ENABLE.ELECT_ENABLE
24
ACT_SN
75.2
INST_ALERTS_ENABLE.SENSOR_ENABLE
25
VALVE_MAN_ID
75.3
INST_ALERTS_ENABLE.ENVIRO_ENABLE
26
VALVE_MODEL_NUM
75.4
INST_ALERTS_ENABLE.TRAVEL_ENABLE
75.5
INST_ALERTS_ENABLE.PROX_ENABLE
75.6
INST_ALERTS_ENABLE.TVL_HISTORY_ENABLE
75.7
INST_ALERTS_ENABLE.PERF_ENABLE
Parameter
111
Instruction Manual
D103412X012
Index Number
Index Number
Parameter
ST_REV
67
ADVISE_MASK
27
VALVE_SN
68
FAILED_PRI
28
VALVE_TYPE
69
MAINT_PRI
29
XD_CAL_LOC
70
ADVISE_PRI
30
XD_CAL_DATE
31
XD_CAL_WHO
89
TEMPERATURE_UNITS
90
PRESSURE_UNITS
91
TVL_UNITS
92
LENGTH_UNITS
93
AREA_UNITS
94
SPRING_RATE_UNITS
Index Number
Parameter
ST_REV
39
PWA_SIMULATE
Index Number
1
41.1
TVL_PRESS_CONTROL.TVL_PRESS_SELECT
41.2
TVL_PRESS_CONTROL.TVL_PRESS_STATE
42.1
BASIC_SETUP.ACTUATOR_STYLE
42.2
BASIC_SETUP.ZERO_PWR_COND
42.3
BASIC_SETUP.TRAVEL_SEN_MOTION
42.4
BASIC_SETUP.FEEDBACK_CONN
42.5
BASIC_SETUP.RELAY_TYPE
42.6
BASIC_SETUP.MAX_SUPP_PRESS
42.7
BASIC_SETUP.PRESS_RANGE_HI
42.8
BASIC_SETUP.PRESS_RANGE_LO
Parameter
ST_REV
76.1
INST_ALERTS_CONFIG.SHUTDOWN_TRIGGER
76.2
INST_ALERTS_CONFIG.SHUTDOWN_RECOVERY
76.3
INST_ALERTS_CONFIG.OUTPUT_BLK_TIMEOUT
76.4
INST_ALERTS_CONFIG.DRIVE_CURRENT_ALRT_PT
76.5
INST_ALERTS_CONFIG.DRIVE_CURRENT_TIME
76.6
INST_ALERTS_CONFIG.TEMP_HI_ALRT_PT
76.7
INST_ALERTS_CONFIG.TEMP_LO_ALRT_PT
76.8
INST_ALERTS_CONFIG.SUP_PRES_HI_ALRT_PT
76.9
INST_ALERTS_CONFIG.SUP_PRES_LO_ALRT_PT
77.1
INST_ALERTS_CONFIG2.TVL_DEV_ALRT_PT
77.2
INST_ALERTS_CONFIG2.TVL_DEV_TIME
77.3
INST_ALERTS_CONFIG2.TVL_DEV_DB
77.4
INST_ALERTS_CONFIG2.TVL_ACCUM_ALRT_PT
77.5
INST_ALERTS_CONFIG2.TVL_ACCUM_DB
77.6
INST_ALERTS_CONFIG2.CYCLE_COUNT_ALRT_PT
77.7
INST_ALERTS_CONFIG2.CYCLE_COUNT_DB
77.8
INST_ALERTS_CONFIG2.TVL_OPEN_ALRT_PT
77.9
INST_ALERTS_CONFIG2.TVL_OPEN_DB
77.10
INST_ALERTS_CONFIG2.TVL_CLOSED_ALRT_PT
77.11
INST_ALERTS_CONFIG2.TVL_CLOSED_DB
77.12
INST_ALERTS_CONFIG2.TVL_LO_LO_ALRT_PT
77.13
INST_ALERTS_CONFIG2.TVL_LO_LO_DB
77.14
INST_ALERTS_CONFIG2.TVL_LO_ALRT_PT
77.15
INST_ALERTS_CONFIG2.TVL_LO_DB
77.16
INST_ALERTS_CONFIG2.TVL_HI_ALRT_PT
77.17
INST_ALERTS_CONFIG2.TVL_HI_DB
77.18
INST_ALERTS_CONFIG2.TVL_HI_HI_ALRT_PT
77.19
INST_ALERTS_CONFIG2.TVL_HI_HI_DB
42.9
BASIC_SETUP.TVL_CAL_TRIGGER
42.10
BASIC_SETUP.TVL_TUNING_SET
42.11
BASIC_SETUP.PRESS_TUNING_SET
44.1
TRAVEL_TUNE.TVL_INTEG_ENABLE
44.2
TRAVEL_TUNE.TVL_INTEG_LIM_HI
44.3
TRAVEL_TUNE.TVL_INTEG_LIM_LO
44.4
TRAVEL_TUNE.TVL_INTEG_DEADZ
44.5
TRAVEL_TUNE.TVL_MLFB_GAIN
47.1
PRESS_TUNE.PRESS_CUTOFF_HI
47.2
PRESS_TUNE.PRESS_CUTOFF_LO
47.3
PRESS_TUNE.PRESS_PROP_GAIN
47.4
PRESS_TUNE.PRESS_INTEG_GAIN
47.5
PRESS_TUNE.PRESS_RATE_GAIN
47.6
PRESS_TUNE.PRESS_INTEG_DEADZ
Index Number
47.7
PRESS_TUNE.PRESS_INTEG_HI_LIM
47.8
PRESS_TUNE.PRESS_INTEG_LO_LIM
95.1
MAI_CHANNEL_1
47.9
PRESS_TUNE.PRESS_INTEG_IC_HI
95.2
MAI_CHANNEL_2
47.10
PRESS_TUNE.PRESS_INTEG_IC_LO
95.3
MAI_CHANNEL_3
47.11
PRESS_TUNE.PRESS_MLFB_GAIN
95.4
MAI_CHANNEL_4
62
FAILED_ENABLE
95.5
MAI_CHANNEL_5
63
MAINT_ENABLE
95.6
MAI_CHANNEL_6
64
ADVISE_ENABLE
95.7
MAI_CHANNEL_7
65
FAILED_MASK
95.8
MAI_CHANNEL_8
66
MAINT_MASK
96
OUTBLOCK_SEL
97
PWA_SET_STATUS
-continued-
112
Parameter
82
UPGRADE_PROGRESS
87
PROTECTION
Parameter
ST_REV
Instruction Manual
D103412X012
August 2012
BKCALOUT
CAS IN
AO
OUT
READBACK
Note
The AO block actual mode will not move to Auto unless:
Resource Block actual mode is Auto, and
AO SHED_OPT [27] is set to a nonzero value.
Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain out of service and the block cannot be scheduled if the block has not
been licensed. Contact your Emerson Process Management sales office to upgrade product licensing.
Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain in IMAN and the block Readback status will be Bad - Not Connected if
the Output Block Selection is set incorrectly. From the transducer block method Outblock Selection, select the desired output
block, see page 69.
113
Instruction Manual
D103412X012
CASIN
SP
HI/LO
Limit
BKCALOUT
READBACK
PV
SPRATEDN
SPRATEUP
Convert
and Status
Calculation
SP
Rate
Limit
OUT
SPWRK
SPLOWLIM
SPHILIM
PVSCALE
IOOPTS
MODE
Shed
Mode
Access
Analog
Input
B2717
Position
Feedback
Access
Analog
Output
CHANNEL
Analog
Output
Modes
The Analog Output function block supports the following modes:
Manual (Man)You can manually set the output to the I/O channel through the OUT [9] attribute. This mode is used
primarily for maintenance, calibration and diagnostics.
Automatic (Auto)The block output (OUT [9]) reflects the target operating point specified by the setpoint (SP [8])
attribute. Typically the setpoint is set by the user.
Cascade (Cas)The SP [8] attribute is set by another function block through a connection to CAS_IN [17]. The SP [8]
value is used to set the OUT [9] attribute automatically. This is the most frequently used mode in the digital valve
controller.
Note
The transducer block must be in Auto for the mode to go to AUTO, CAS, MAN, or RCAS.
RemoteCascade (RCas)The SP [8] is set by a host computer by writing to the RCAS_IN [28] parameter. The SP [8]
value is used to set the OUT [9] attribute automatically.
114
Instruction Manual
D103412X012
August 2012
Out of Service (OOS)The block is not processed. The output channel is maintained at the last value and the status
of OUT [9] is set to Bad: Out of Service. The BLOCK_ERR [6] attribute shows Out of Service.
Initialization Manual (Iman)The path to the output hardware is broken and the AO block output will remain at the
last position. This means the transducer block mode is Out of Service or Manual or configured to respond to the DO
block.
Local Override (LO)The output of the block is not responding to inputs because the fault state action is active. OUT
[9] freezes or goes to value per IO_OPTS [14].
The target mode of the block may be restricted to one or more of the following modes: Man, Auto, Cas, RCas, or OOS.
Mode Handling
Shed OptionsRCAS Mode Only
Automatically changing through the permitted modes when starting from a remote mode, fall from (or shed) or climb
to a remote mode is determined by the parameter SHED_OPT [27]. A block climbs and sheds through the same path.
For example, if SHED_OPT [27] specifies that a block should shed to Auto, then, if the block target mode is set to RCas,
the block goes through Auto on the way to RCas.
When the block is in Cas mode and the CAS_IN [17] input goes bad, the block sheds mode to the next lower permitted
mode.
You can configure the shed option as follows:
Note
During Shed with Return Options, the actual mode is changed, while the target mode stays the same.
NormalOn failure of a remote cascade connection the block attempts to attain the highest permitted nonremote
mode until remote cascade is restored. Cas is the highest permitted nonremote mode and Auto is is the next
permitted nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the previous target mode before it was changed to RCAS or ROUT. On
failure of a remote cascade connection the block attempts to attain the retained target mode.
AutoOn failure of a remote cascade connection the block attempts to attain Auto, if permitted, until remote cascade
is restored.
ManOn failure of a remote cascade connection the block sheds to Man until a remote cascade connection is
restored.
115
Instruction Manual
August 2012
D103412X012
For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no
attempt to restore the connection following failure. The behavior on change to the remote cascade target mode is
identical to that for Shed With Return Options.
NormalOn failure of a remote cascade connection the block sets the target mode to the highest permitted
nonremote mode. Cas is the highest permitted nonremote mode and Auto is is the next highest permitted
nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the previous target mode before it was changed to RCAS or ROUT. On
failure of a remote cascade connection the block sets the target mode to the retained target mode.
AutoOn failure of a remote cascade connection, the block sets the target mode to Auto, if permitted.
ManOn failure of remote cascade connection, the block sets the target mode to Man, if permitted.
The user may configure SHED_OPT [27] so that it calls for a target mode that is not permitted. When doing this, the
mode logic uses the following rules as applied by the remote logic:
Shed logic never results in a nonpermitted target mode.
Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted.
Status Handling
Output or readback fault detection is reflected in the status of PV [7], OUT [9], and BKCAL_OUT [25]. A limited SP [8]
condition is reflected in the BKCAL_OUT [25] status. When simulation is enabled through the SIMULATE [10] attribute,
you can set the value and status for PV [7] and READBACK [16].
When the block is in Cas mode and the CAS_IN [17] input goes bad, the block sheds mode to the next permitted
mode.
Note
You must wire BKCAL_OUT [25] to BKCAL_IN [27] of the upstream block that provides CAS_IN [17]. Otherwise, the AO will not
initialize properly, and the setpoint at CAS_IN [17] will not be passed to OUT [9].
An analog readback value, such as valve position, is shown by the process value (PV [7]) attribute in engineering units.
To support testing, you can enable simulation, which allows you to manually set the channel feedback. There is no
alarm detection in the AO function block.
116
Instruction Manual
D103412X012
To select the manner of processing the SP and the channel output value configure the setpoint limiting options, the
tracking options, and the conversion and status calculations.
117
Instruction Manual
D103412X012
CAS_IN, 2
1 macrocycle
SPRATEDN
1 macrocycle
SPRATEUP
OUT
TRANSDUCER BLOCK
TRAVEL TARGET
SP
B27181
1 second
1 second
1 second
1 second
Time
I/O Options
The I/O options parameter (IO_OPTS [14]) allows you to select how the I/O signals are processed. You can set I/O
options in Out of Service mode only. The following I/O options are available in the AO block:
Use PV for BKCAL_OUTChanges the BKCAL_OUT [25] value to the PV [7] value. When the Use PV for BKCAL_OUT
option is not enabled (False), the BKCAL_OUT [25] value is the working setpoint value.
Target to Man if Fault State ActivatedSet the target mode to Man, thus losing the original target, if Fault State is
activated. This latches an output block into the manual mode.
118
Instruction Manual
D103412X012
August 2012
Use Fault State value on RestartUse the value of FSTATE_VAL [24] for SP [8] when power is restored or if the device is
restarted, otherwise use the last value saved in nonvolatile memory. This does not act like Fault State, it only uses the
value of FSTATE_VAL [24].
Fault State to ValueThe output action to take when a fault occurs (if not selected, use hold last value; if selected, use
FSTATE_VAL [24]).
Increase to CloseIf the Increase to Close bit is set the value to the transducer is inverted, e.g. 20% becomes 80%.
SP-PV Track in ManPermits the setpoint to track the process variable when the target mode of the block is MAN.
SP-PV Track in LO or IManPermits the setpoint to track the process variable when the actual mode of the block is LO
or IMan.
SP Track retained TargetPermits the setpoint to track the RCas or Cas parameter based on the retained target mode
when the actual mode of the block is LO or Man. When SPPV track options are enabled, the SP Track retained target
will have precedence in the selection of the value to track when the actual mode is Man and LO.
Simulation
When simulate is active, the transducer subparameters show the actual transducer block status and value as normally
passed back to the AO block. The Simulate subparameters are writable and replace actual transducer values.
Note
When simulate is active, the output block no longer writes values to the transducer block. If the Output Blk Timeout period is
exceeded, the transducer block may move the valve to the Zero Power Condition depending on the configuration of the Output
Block Timeout Alert.
Application Information
The configuration of an AO function block and its associated output channels depends on the specific application. A
typical configuration for the Analog Output involves the following attributes:
PV_SCALE
Set the range and engineering units to values that correspond to the operation range.
For the digital valve controller, PV_SCALE [11] is typically set between 0 and 100%.
BKCAL_OUT
If you are using the CAS_IN [17] connector wired from another block, wire the
BKCAL_OUT [25] attribute to the other block's BKCAL_IN [27] attribute.
IO_OPTS
SHED_OPT
Set the action to be taken when the set point or output are not updated in a remote
mode.
Block Errors
Table 424 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the AO
block and are provided only for your reference.
119
Instruction Manual
D103412X012
Other (N/A)
Simulate active Simulation is enabled and the block is using a simulated value in its execution.
Device Fault State Set AO block in fault state after FSTATE_TIME because of Bad status or IFS substatus on CAS_IN or
Resource block commanded fault state.
Device Needs Maintenance Soon Indicates a Maintenance PlantWeb Alert condition is active if Block Error Reporting is
enabled. See page 86.
10
11
12
13
Device Needs Maintenance Now Indicates Failed PlantWeb Alert condition is active if Block Error Reporting is enabled. See
page 86.
14
Power Up This condition exists after power up until actual mode is not Out of Service.
15
Index
Number
RO /
RW
Block
Mode
Range
Initial
Value
Description
Static Revision
ST_REV
RO
N/A
0 to 65535
Tag Description
TAG_DESC
RW
ALL
7 bit ASCII
Spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
RW
ALL
1 to 255
-Continued-
120
Instruction Manual
D103412X012
August 2012
ACTUAL
Index
Number
RO /
RW
Block
Mode
OOS
MAN
AUTO
AUTOCAS
AUTORCAS
OOS until
block is
configured,
then last valid
target
OOS+MAN+AUTO+
CAS+RCAS
5.1
RW
ALL
5.2
RO
ALL
OOS
OOS+MAN+A
UTO+
CAS+RCAS
5.3
RW
ALL
NORMAL
5.4
RW
ALL
Process Variable
PV
Initial
Value
Description
PERMITTED
Block Error
BLOCK_ERR
Range
RO
RO
AUTO
N/A
1: Block Configuration
Error
3: Simulate Active
4: Local Override
5: Device Fault State Set
8: Output Failure
14: Powerup
15: OutofService
N/A
Dynamic
Dynamic
Set Point
SP
OOS
MAN
AUTO
Dynamic
Output
OUT
MAN
OOS
Dynamic
Simulate
SIMULATE
10
SIMULATE_STATUS
10.1
RW
ALL
SIMULATE_VALUE
10.2
RW
ALL
TRANSDUCER_STATUS
10.3
RO
ALL
TRANSDUCER_VALUE
10.4
RO
ALL
ENABLE/DISABLE
Transducer Scale
XD_SCALE
10.5
11
12
RW
RW
RO
ALL
0: Not Initialized
1: Simulation Disable
2: Simulation Active
OOS
EU at 100%
EU at 0%
Units index
Decimal Point
100
0
%
2
OOS
EU at 100%
EU at 0%
Units index
Decimal Point
100 only
0 only
% only
2
1: Simulation
Disabled
-Continued-
121
Instruction Manual
D103412X012
Index
Number
RO /
RW
Block
Mode
13.1
RW
ALL
DENY
13.2
RW
ALL
Status Options
STATUS_OPTS
Initial
Value
13
GRANT
I/O Options
IO_OPTS
Range
14
OOS
15
OOS
0: Program
1: Tune
2: Alarm
3: Local
1: SP tracks PV in Man
3: SP tracks PV in LO or
Iman
4: SP Track retained
target in Man or LO
5: Increase to Close
6: Fault State to value
0=freeze
1=go to Fault State
value
7: Use Fault State
value on restart
8: Target to Man if
Fault State activated
9: Use PV for
BKCAL_OUT
0=SP
1=PV
4: Propagate Failure
Backward
All bits: 0
All bits: 0
Cascade Input
CAS_IN
16
17
RO
All bits: 0
All bits: 0
N/A
ALL
Status
Readback
READBACK
Description
Value
Dynamic
Status
BAD:
NC:
const
Value
18
ALL
Positive, 0 disables
rate limiting PV units
+INF
Setpoint Rate Up
SP_RATE_UP
19
ALL
Positive, 0 disables
rate limiting PV units
+INF
20
ALL
100
21
ALL
AO Channel
CHANNEL
22
OOS
1=Setpoint
23
ALL
Positive, seconds
-Continued-
122
1=Setpoint
Instruction Manual
D103412X012
August 2012
Index
Number
24
25
26
RO /
RW
Block
Mode
ALL
Range
PV Scale +/- 10%
Initial
Value
Description
Dynamic
Status Limits
RO
N/A
Value
Shed Options
SHED_OPT
27
28
Update Event
UPDATE_EVT
29
ALL
ALL
RO
N/A
Status
BAD: NoCom:
NoVal:
const
Value
0 Trk
Defined by FF spec
0=Invalid
1=Normal Shed,
Normal Return
2=Normal Shed, No
Return
3=Shed to Auto,
normal return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
Status
Value
Dynamic
UNACKNOWLEDGED
29.1
RW
N/A
0:Undefined
1:Acknowledged
2:Unacknowledged
0: Undefined
UPDATE_STATUS
29.2
RO
N/A
0:Undefined
1:Update reported
2:Update not reported
0: Undefined
TIME_STAMP
29.3
RO
N/A
STATIC_REVISION
29.4
RO
N/A
RELATIVE_INDEX
29.5
RO
N/A
RW
N/A
0:Undefined
1:Acknowledged
2:Unacknowledged
0:Undefined
1:Clear reported
2:Clear not reported
3:Active reported
4:Active not reported
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
30
30.1
0: Undefined
ALARM_STATE
30.2
RO
N/A
0: Undefined
TIME_STAMP
30.3
RO
N/A
SUBCODE
30.4
RO
N/A
VALUE
30.5
RO
N/A
0
-Continued-
123
Instruction Manual
D103412X012
Index
Number
RO /
RW
Block
Mode
Initial
Value
Range
Description
Extended Parameters
StdDev
STDDEV
31
RO
N/A
positive float
Dynamic
Cap StdDev
CAP_STDDEV
32
RO
N/A
positive float
Dynamic
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 426. AO Function Block, View 1
Index Number
1
Parameter
ST_REV
Index Number
1
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
BLOCK_ERR
PV
PV
SP
SP
OUT
OUT
16
READBACK
16
READBACK
17
CAS_IN
17
CAS_IN
25
BKCAL_OUT
26
RCAS_IN
28
RCAS_OUT
31
STDDEV
32
CAP_STDDEV
124
Parameter
ST_REV
11
PV_SCALE
12
XD_SCALE
13.1
GRANT_DENY.GRANT
13.2
GRANT_DENY.DENY
20
SP_HI_LIM
21
SP_LO_LIM
Parameter
ST_REV
STRATEGY
ALERT_KEY
14
IO_OPTS
15
STATUS_OPTS
18
SP_RATE_DN
19
SP_RATE_UP
22
CHANNEL
23
FSTATE_TIME
24
FSTATE_VAL
27
SHED_OPT
Instruction Manual
D103412X012
August 2012
Connectors
Back Calculation Output: Status
Back Calculation Output: Value
Cascade Input: Status
Cascade Input: Value
Output: Status
Output: Value
Online
Back Calculation Output: Status
Back Calculation Output: Value
Block Error
Cascade Input: Status
Cascade Input: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output: Status
Output: Value
Process Value: Status
Process Value: Value
Remote Cascade Input: Status
Remote Cascade Input: Value
Remote Cascade Output: Status
Remote Cascade Output: Value
Readback: Status
Readback: Value
Setpoint: Status
Setpoint: Value
Status
Block Error
Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
StdDev
Cap StdDev
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value: Status
Process Value: Value
Setpoint: Status
Setpoint: Value
Output: Status
Output: Value
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
Readback: Status
Readback: Value
Cascade Input: Status
Cascade Input: Value
Setpoint Rate Down
Setpoint Rate Up
Setpoint High Limit
Setpoint Low Limit
AO Channel
Fault State Time
Fault State Value
Back Calculation Output: Status
Back Calculation Output: Value
Remote Cascade Input: Status
Remote Cascade Input: Value
Shed Options
Remote Cascade Output: Status
Remote Cascade Output: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
StdDev
Cap StdDev
125
Instruction Manual
D103412X012
IN
CAS
IN
BKCALOUT
VAL
FF
TRK
TRK
IN
OUT
PID
IN
D
VAL
BKCAL_IN = THE ANALOG INPUT VALUE AND STATUS FROM ANOTHER BLOCK'S BKCAL
_OUT OUTPUT THAT IS USED FOR BACKWARD OUTPUT TRACKING FOR BUMPLESS
TRANSFER AND TO PASS LIMIT STATUS.
CAS_IN = THE REMOTE SETPOINT VALUE FROM ANOTHER FUNCTION BLOCK.
FF_VAL = THE FEEDFORWARD CONTROL INPUT VALUE AND STATUS.
IN = THE CONNECTION FOR THE PROCESS VARIABLEFROM ANOTHER FUNCTION BLOCK.
TRK_IN_D = INITIATES THE EXTERNAL TRACKING FUNCTION.
TRK_VAL = THE VALUE AFTER SCALING APPLIED TO OUT IN LOCAL OVERRIDE MODE.
BKCAL_OUT = THE VALUE AND STATUS REQUIRED BY THE BKCAL_IN INPUT OF ANOTHER
FUNCTION BLOCK TO PREVENT RESET WINDUP AND TO PROVIDE BUMPLESS TRANSFER
TO CLOSED LOOP CONTROL.
OUT = THE BLOCK OUTPUT AND STATUS.
B2720
The block supports two forms of the PID equation: Standard and Series. You can choose the appropriate equation
using the MATHFORM [70] parameter. The Standard ISA PID equation is the default selection.
ex
1 ) t s 1) 1 ) T
r
ex
t ds
)
t ds ) 1
1 ) t1s ) T t s t)s 1) 1 )F
d
where
GAIN:
r:
s:
laplace operator
d:
126
Instruction Manual
D103412X012
August 2012
F:
E:
To further customize the block for use in your application, you can configure filtering, feedforward inputs, tracking
inputs, setpoint and output limiting, PID equation structures, and block output action. Table 432 lists the PID block
parameters and their descriptions, units of measure, and index numbers, and figure 410 illustrates the internal
components of the PID function block.
FFGAIN
FFSCALE
Feedforward
Calculation
FFVAL
BKCALIN
MODE
TRKIND
BKCALOUT
RCASOUT
ROUTOUT
ROUTIN
RCASIN
Setpoint
Limiting
CASIN
Operator
Setpoint
IN
SPHILIM
SPLOLIM
SPRATEDN
SPRATEUP
Scaling
and
Filtering
PVSCALE
PVFILTER
TRKVAL
PID
Equation
GAIN
RATE
RESET
Alarm
Detection
Output
Limiting
OUT
OUTHILIM
OUTLOLIM
OUTSCALE
Operator
Output
HIHILIM
HILIM
DVHILIM
DVLOLIM
LOLIM
LOLOLIM
Convert
TRKSCALE
OUTSCALE
B2721
127
Instruction Manual
August 2012
D103412X012
Modes
The PID function block supports the following modes:
Manual (Man)The block output (OUT [9]) may be set manually.
Automatic (Auto)The SP [8] may be set manually and the block algorithm calculates OUT [9].
Cascade (Cas)The SP [8] is calculated in another block and is provided to the PID block through the CAS_IN [18]
connection.
RemoteCascade (RCas)The SP [8] is provided by a host computer that writes to the RCAS_IN [32] parameter.
RemoteOutput (ROut)The OUT [9] is provided by a host computer that writes to the ROUT_IN [33] parameter.
Local Override (LO)The track function is active. OUT [9] is set by TRK_VAL [39]. The BLOCK_ERR [6] parameter
shows Local override.
Initialization Manual (IMan)The output path is not complete (for example, the cascade-to-slave path might not be
open). In IMan mode, OUT [9] tracks BKCAL_IN [27].
Out of Service (OOS)The block is not processed. The OUT [9] status is set to Bad: Out of Service. The BLOCK_ERR
[6] parameter shows Out of service.
You can configure the Man, Auto, Cas, and OOS modes as permitted modes for operator entry.
Mode Handling
Shed OptionsRCAS Mode Only
Shed from or climb to a remote mode is determined by the parameter SHED_OPT [34]. A block climbs and sheds
through the same path. For example, if SHED_OPT [34] specifies that a block should shed to Auto, then, if the block
target mode is set to RCas, the block goes through Auto on the way to RCas. You can configure the shed option as
follows:
128
Instruction Manual
D103412X012
August 2012
Status Handling
If the input status on the PID block is Bad, the mode of the block reverts to Manual. In addition, you can select the
Target to Manual if Bad IN status option to direct the target mode to revert to manual. You can set the status option in
Manual or Out of Service mode only.
Auto
Man
CAS
SPHILIM
SPLOLIM
SPRATEUP
SPRATEDN
Setpoint
Limiting
Rate
Limiting
Auto
Man
CAS
B2722
In Automatic mode, the set point is entered manually by the operator, and the output is computed based on the set
point. In Auto mode, you can also adjust the set point limit and the set point rate of change using the SP_RATE_UP
[20] and SP_RATE_DN [19] parameters.
129
Instruction Manual
August 2012
D103412X012
In Manual mode the output is entered manually by the operator. In Remote Output mode, the output is entered by a
host computer.
Filtering
The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid
changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME [16] or SP_FTIME [69]
parameters. Set the filter time constant to zero to disable the filter feature.
Feedforward Calculation
The feedforward value (FF_VAL [40]) is scaled (FF_SCALE [41]) to a common range for compatibility with the output
scale (OUT_SCALE [11]). A gain value (FF_GAIN [42]) is applied to achieve the total feedforward contribution.
Output Tracking
Output tracking is enabled through the control options. You can set control options in Manual or Out of Service mode
only.
The Track Enable control option must be set to True for the track function to operate. When the Track in Manual
control option is set to True, the operator cannot override the tracking function in Manual mode. When Track in
Manual is False, the operator can override the tracking function when the block is in Manual mode. Activating the track
function causes the block's actual mode to revert to Local Override.
The TRK_VAL [38] parameter specifies the value to be converted and tracked into the output when the track function
is operating. The TRK_SCALE [37] parameter specifies the range of TRK_VAL [38].
When the TRK_IN_D [38] parameter is True and the Track Enable control option is True, the TRK_VAL [38] input is
converted to the appropriate value and output in units of OUT_SCALE [11].
130
Instruction Manual
D103412X012
August 2012
Act On IRIf this option is true, then when IR (Initialization Requested) is received on BKCAL_IN [27], the SP [8] will
be adjusted within setpoint limits to provide bumpless transfer when the cascade is closed. If the setpoint required
to provide bumpless transfer is outside the setpoint limits, then any difference added to provide bumpless transfer
will be removed in the BAL_TIME [25].
When one of these options is set, the SP[8] value is set to the PV [7] value while in the specified mode.
You can select the value that a master controller uses for tracking by configuring the Use PV for BKCAL_OUT control
option. The BKCAL_OUT [31] value tracks the PV value. BKCAL_IN [27] on a master controller connected to
BKCAL_OUT [31] on the PID block in an open cascade strategy forces its OUT [9] to match BKCAL_IN [27], thus
tracking the PV from the slave PID block into its cascade input connection (CAS_IN [18]). If the Use PV for BKCAL_OUT
option is not selected, the working set point (SP_WRK [68]) is used for BKCAL_OUT [31].
You can set control options in Manual or Out of Service mode only. When the mode is set to Auto, the SP [8] will
remain at the last value (it will no longer follow the PV [7].
Configure the STRUCTURECONFIG [71] parameter to select the PID equation structure. You can select one of the
following choices:
Proportional, integral, and derivative on error (PID)
Proportional and integral on error, derivative on PV (PI_D)
Integral on error, proportional and derivative on PV (I_PD)
Proportional on error, derivative on error (PD)
Integral on error, derivative on error (ID)
Integral on error, derivative on PV (I_D)
Two degrees of Freedom (2DOF)
Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block error for the PID
block are defined above.
131
Instruction Manual
D103412X012
Process alarm detection is based on the PV [7] value. You can configure the alarm limits of the following standard
alarms:
High (HI_LIM [51])
High high (HI_HI_LIM [49])
Low (LO_LIM [53])
Low low (LO_LO_LIM [55])
Additional process alarm detection is based on the difference between SP [8] and PV [7] values and can be configured
via the following parameters:
Deviation high (DV_HI_LIM [57])
Deviation low (DV_LO_LIM [59])
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent
of the PV span can be set using the ALARM_HYS [47] parameter. The priority of each alarm is set in the following
parameters:
HI_PRI [50]
HI_HI_PRI [48]
LO_PRI [52]
LO_LO_PRI [54]
DV_HI_PRI [56]
DV_LO_PRI [58]
Alarms are grouped into five levels of priority, as shown in table 430.
Table 430. PID Function Block Alarm Priorities
Priority Description(1)
Priority Number
0
An alarm condition with a priority of 1 can be recognized by the system. The device monitors the alarm but does not report it
until requested by the host system.
An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
diagnostics and system alerts).
3-7
8-15
1. The priority classes advise and critical have no relationship to Plant Web Alerts.
Application Information
The PID function block is a powerful, flexible control algorithm that is designed to work in a variety of control
strategies. The PID block is configured differently for different applications.
DeltaV Tune
DeltaV Tune quickly and automatically determines optimal tuning parameters for PID control loops. For more
information on DeltaV Tune, refer to DeltaV Books Online or DeltaV documentation.
Block Errors
Table 431 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the PID
block and are provided only for your reference.
132
Instruction Manual
D103412X012
August 2012
Other (N/A)
Input failure/process variable has Bad statusThe parameter linked to IN is indicating a Bad status.
10
11
12
13
14
Power UpSet if devices was powered up with this block in Out of Service (OOS) mode. Cleared on first change of mode to other
than OOS.
15
Index
Number
RO /
RW
Block
Mode
Range
Initial Value
Description
Static Revision
ST_REV
RO
N/A
0 to 65535
Tag Description
TAG_DESC
RW
ALL
7 bit ASCII
Spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
RW
ALL
TARGET
5.1
RW
ALL
ACTUAL
5.2
RO
ALL
PERMITTED
5.3
RW
ALL
NORMAL
5.4
RW
ALL
0 to 255
OOS until
block is
configured,
then last valid
target
OOS
OOS+MAN+AUTO+
CAS+RCAS+ROUT
OOS MAN,
AUTO CAS,
RCAS ROUT
AUTO
-Continued-
133
Instruction Manual
D103412X012
Index
Number
RO /
RW
Block
Mode
Range
Initial Value
Description
Dynamic
Dynamic
Dynamic
Status
OUT_SCALE +/- 10%
Dynamic
Defined Bits
Block Error
BLOCK_ERR
RO
N/A
Process Value
PV
RO
N/A
Setpoint
SP
OOS
MAN
AUTO
Output
OUT
MAN
OOS
10
Output Scale
OUT_SCALE
11
Grant Deny
GRANT_DENY
12
GRANT
DENY
Control Options
CONTROL_OPTS
Status Options
STATUS_OPTS
Input
IN
12.1
12.2
13
14
15
16
Value
OOS
EU at 100%
EU at 0%
Units index
Decimal Point
100
0
%
2
OOS
EU at 100%
EU at 0%t
Units index
Decimal Point
100
0
%
2
ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
OOS
0: Bypass Enable
1: SP tracks PV in MAN
2: SP tracks PV in ROUT
3: SP tracks PV in LO or MAN
4: SP tracks RCAS or CAS in
IMAN, LO, MAN or ROUT
5: Direct Acting
7: Track Enable
8: Track in Manual
9: Use PV for BKCAL_OUT
10: Act on IR
12: Restrict SP to limits in
Cas and RCas
13: No output limits in MAN
All bits: 0
OOS
All bits: 0
ALL
ALL
Status
BAD:
NC:
const
Value
Positive
-Continued-
134
DS65
The block output value and status.
Instruction Manual
D103412X012
August 2012
Cascade Input
CAS_IN
Index
Number
RO /
RW
Block
Mode
MAN
OOS
17
18
ALL
19
ALL
Range
Initial Value
1=Off
2=On
0=undefined
Status
BAD
NC:
const
Value
Positive
Description
Data Type: Enum
Used to override the calculation of the block.
When enabled, the SP is sent directly to the
output.
Data Type: DS65
The setpoint value from another block.
+ INF
Setpoint Rate UP
SP_RATE_UP
20
ALL
Positive
+ INF
21
ALL
100
22
ALL
PV Scale
+/- 10%, must be less than
SP_HI_LIM
Gain
GAIN
23
ALL
greater than 0
Reset
RESET
24
ALL
Positive
+ INF
Balance Time
BAL_TIME
25
ALL
Positive
Rate
RATE
26
ALL
Positive
Status
BAD:
NC:
const
Value
27
ALL
28
ALL
100
29
ALL
30
ALL
0 to 50%
31
32
RO
0.50%
N/A
ALL
Dynamic
BAD:
NoCom:
NoVal:
const
Status
Value
0 Trk
-Continued-
135
Instruction Manual
D103412X012
Shed Options
SHED_OPT
Tracking Scale
TRK_SCALE
Tracking Value
TRK_VAL
Index
Number
RO /
RW
33
ALL
34
35
36
37
38
39
40
Block
Mode
RO
Status
BAD:
NoCom:
NoVal:
const
Value
0 Trk
0=Invalid
1=Normal Shed, Normal
Return
2=Normal Shed, No Return
3=Shed to Auto, normal
return
4=Shed to Auto, no return.
Target mode changes to
Auto on detection of a shed
condition
5=Shed to Manual, normal
return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained target,
normal return
8=Shed to retained target,
no return. (Change target to
retained target)
Description
0=Invalid
Dynamic
N/A
Dynamic
MAN
OOS
100
0
%
2
N/A
ALL
ALL
ALL
BAD:
NC:
const
Status
Value
Status
BAD:
NC:
const
41
MAN
OOS
42
MAN
OOS
Value
Status
BAD:
NC:
const
Value
-Continued-
136
Initial Value
ALL
RO
Range
100
0
%
2
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Block
Mode
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Update reported
2=Update not reported
Range
Initial Value
43
43.1
UPDATE_STATE
43.2
RO
N/A
TIME_STAMP
43.3
RO
N/A
STATIC_REVISION
43.4
RO
N/A
RELATIVE_INDEX
43.5
RO
N/A
RW
N/A
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
44
44.1
44.2
RO
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clearreported
2=Clearnot reported
3=Active reported
4=Active not reported
TIME_STAMP
44.3
RO
N/A
SUBCODE
44.4
RO
N/A
VALUE
44.5
RO
N/A
Alarm Summary
ALARM_SUM
Description
45
CURRENT
45.1
RO
ALL
UNACKNOWLEDGED
45.2
RO
ALL
UNREPORTED
45.3
RO
ALL
DISABLED
45.4
RW
ALL
Acknowledge Option
ACK_OPTION
46
N/A
Alarm Hysteresis
ALARM_HYS
47
ALL
0 to 50%
48
ALL
0 to 15
49
ALL
PV_SCALE, or +INF
High Priority
HI_PRI
50
ALL
0 to 15
High Limit
HI_LIM
51
ALL
PV_SCALE, or +INF
Low Priority
LO_PRI
52
ALL
0 to 15
Low Limit
LO_LIM
53
ALL
PV_SCALE, or -INF
54
ALL
0 to 15
Dynamic
All bits: 0
0.50%
0
+INF
0
+INF
0
-INF
0
-Continued-
137
Instruction Manual
D103412X012
Index
Number
RO /
RW
Block
Mode
Range
Initial Value
55
ALL
PV_SCALE, or -INF
56
ALL
0 to 15
57
ALL
PV_SCALE, or +INF
58
ALL
0 to 15
59
ALL
60
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
UNACKNOWLEDGED
60.1
RW
0
+INF
0
-INF
ALARM_STATE
60.2
RO
N/A
TIME_STAMP
60.3
RO
N/A
SUBCODE
60.4
RO
N/A
VALUE
60.5
RO
N/A
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
High Alarm
HI_ALM
UNACKNOWLEDGED
61
61.1
61.2
RO
N/A
TIME_STAMP
61.3
RO
N/A
SUBCODE
61.4
RO
N/A
VALUE
61.5
RO
N/A
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
UNACKNOWLEDGED
ALARM_STATE
Low Alarm
LO_ALM
62
62.1
ALARM_STATE
62.2
RO
N/A
TIME_STAMP
62.3
RO
N/A
SUBCODE
62.4
RO
N/A
VALUE
62.5
RO
N/A
0
-Continued-
138
-INF
Description
Data Type: Float
The setting for the alarm limit used to detect the
LO LO alarm condition.
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Block
Mode
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
Range
Initial Value
63
63.1
ALARM_STATE
63.2
RO
N/A
TIME_STAMP
63.3
RO
N/A
SUBCODE
63.4
RO
N/A
VALUE
63.5
RO
N/A
64
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
UNACKNOWLEDGED
64.1
64.2
RO
N/A
TIME_STAMP
64.3
RO
N/A
SUBCODE
64.4
RO
N/A
VALUE
64.5
RO
N/A
65
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=undefined
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
0=undefined
65.1
ALARM_STATE
UNACKNOWLEDGED
Description
ALARM_STATE
65.2
RO
N/A
TIME_STAMP
65.3
RO
N/A
SUBCODE
65.4
RO
N/A
VALUE
65.5
RO
N/A
0
Extended Parameters
Bias
BIAS
66
Error
ERROR
67
RO
SP Work
SP_WRK
68
RO
N/A
Dynamic
N/A
Dynamic
ALL
SP FTime
SP_FTIME
69
ALL
Positive
Math Form
MATHFORM
70
OOS
0=Standard
1=Series
0=Standard
-Continued-
139
Instruction Manual
D103412X012
Structureconfig
STRUCTURECONFIG
UGamma
GAMMA (ugamma)
Index
Number
RO /
RW
71
72
Block
Mode
Range
Initial Value
OOS
0=PID terms
on error
1.0
1.0
OOS
> = 0, < = 1
Description
UBeta
BETA (ubeta)
73
OOS
> = 0, < = 1
IDeadBand
IDEADBAND
74
OOS
Positive
StdDev
STDDEV
75
RO
N/A
Dynamic
Cap StdDev
CAP_STDDEV
76
RO
N/A
Dynamic
T Request
T_REQUEST
77
RO
ALL
T State
T_STATE
78
RO
NONE
T Status
T_STATUS
79
RO
N/A
0=Request Tuning
1=Force Tuning
2=Reset Tuner
140
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Block
Mode
Range
Initial Value
Description
80
RO
N/A
0.0
T Ugain
T_UGAIN
81
RO
N/A
0.0
T Uperiod
T_UPERIOD
82
RO
N/A
0.0
T Psgain
T_PSGAIN
83
RO
N/A
0.0
T Ptimec
T_PTIMEC
84
RO
N/A
0.0
T Pdtime
T_PDTIME
85
RO
N/A
0.0
T Targetop
T_TARGETOP
86
ALL
T Hyster
T_HYSTER
87
ALL
> = 0.0
0.0
T Relayss
T_RELAYSS
88
ALL
> = 0.0
3.0
T Gain Magnifier
T_GAIN_MAGNIFIER
89
ALL
1.0
T Auto Extra DT
T_AUTO_EXTRA_DT
90
ALL
T Auto Hysteresis
T_AUTO_HYSTERESIS
91
ALL
T Aoperiods
T_AOPERIODS
92
N/A
RO
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 433. PID Function Block, View 1
Index Number
1
Parameter
Parameter
ST_REV
ST_REV
5.1
MODE_BLK.TARGET_MODE
10
PV_SCALE
5.2
MODE_BLK.ACTUAL_MODE
11
OUT_SCALE
5.3
MODE_BLK.PERMITTED_MODE
12.1
GRANT_DENY.GRANT
5.4
MODE_BLK.NORMAL_MODE
12.2
GRANT_DENY.DENY
BLOCK_ERR
17
BYPASS
PV
21
SP_HI_LIM
SP
22
SP_LO_LIM
OUT
28
OUT_HI_LIM
18
CAS_IN
29
OUT_LO_LIM
38
TRK_IN_D
39
TRK_VAL
45.1
ALARM_SUM.CURRENT
45.2
ALARM_SUM.UNACKNOWLEDGED
45.3
ALARM_SUM.UNREPORTED
45.4
ALARM_SUM.DISABLED
141
Instruction Manual
D103412X012
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
PV
SP
OUT
15
IN
18
CAS_IN
27
BKCAL_IN
31
BKCAL_OUT
32
RCAS_IN
33
ROUT_IN
35
RCAS_OUT
36
ROUT_OUT
38
TRK_IN_D
39
TRK_VAL
40
FF_VAL
45.1
ALARM_SUM.CURRENT
45.2
ALARM_SUM.UNACKNOWLEDGED
45.3
ALARM_SUM.UNREPORTED
45.4
ALARM_SUM.DISABLED
67
ERROR
68
SP_WORK
71
STRUCTURECONFIG
75
STDDEV
76
CAP_STDDEV
Parameter
ST_REV
STRATEGY
ALERT_KEY
13
CONTROL_OPTS
14
STATUS_OPTS
16
PV_FTIME
19
SP_RATE_DN
20
SP_RATE_UP
23
GAIN
24
RESET
25
BAL_TIME
26
RATE
30
BKCAL_HYS
34
SHED_OPT
37
TRK_SCALE
41
FF_SCALE
42
FF_GAIN
46
ACK_OPTION
47
ALARM_HYS
48
HI_HI_PRI
49
HI_HI_LIM
50
HI_PRI
51
HI_LIM
52
LO_PRI
53
LO_LIM
54
LO_LO_PRI
55
LO_LO_LIM
56
DV_HI_PRI
57
DV_HI_LIM
58
DV_LO_PRI
59
DV_LO_LIM
Note
Because individual views are limited in size, View List 4 has
two parts.
142
Parameter
ST_REV
66
BIAS
69
SP_FTIME
70
MATHFORM
71
STRUCTURECONFIG
72
GAMMA (ugamma)
73
BETA
74
IDEADBAND
Instruction Manual
D103412X012
August 2012
Advanced Config
Back Calculation Hysteresis
Feed Forward Gain
Feed Forward Scale: EU at 100%
Feed Forward Scale: EU at 0%
Feed Forward Scale: Units Index
Feed Forward Scale: Decimal
Shed Options
Setpoint Rate Down
Setpoint Rate Up
Static Revision
Status Options
Strategy
Tracking Scale: EU at 100%
Tracking Scale: EU at 0%
Tracking Scale: Units Index
Tracking Scale: Decimal
Tracking Value: Status
Tracking Value: Value
Connectors
Back Calculation Input: Status
Back Calculation Intput: Value
Back Calculation Output: Status
Back Calculation Output: Value
Cascade Input: Status
Cascade Input: Value
Feed Forward Value: Status
Feed Forward Value: Value
Input: Status
Input: Value
Output: Status
Ouput: Value
Tracking Input Discrete: Status
Tracking Input Descrete: Value
Tracking Value: Status
Tracking Value: Value
Online
Status
Block Error
143
Instruction Manual
D103412X012
All
144
Other
(continued)
Error
SP Work
SP FTime
mathform
structureconfig
Ugamma
UBeta
IDeadBand
StdDv
Cap StdDev
T Request
T State
T Status
T Ipgain
T Ugain
T Uperiod
T Psgain
T Ptimec
T Pdtime
T Targetop
T Hyster
T Relayss
T Gain Magnifier
T Auto Extra DT
T Auto Hysteresis
T Aoperiods
All (continued)
All (continued)
Cap StdDev
T Request
T State
T Status
T Ipgain
T Ugain
T Uperiod
T Psgain
T Ptimec
T Pdtime
T Targetop
T Hyster
T Relayss
T Gain Magnifier
T Auto Extra DT
T Auto Hysteresis
T Aoperiods
Instruction Manual
D103412X012
August 2012
OUT
IN (18)
DISABLE (18)
OUT_D
OP_SELECT
ISEL
SELECTED
SELECTED
OUT
OUT_D
FIELDBUS_56A
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
DISABLE_1
DISABLE_2
DISABLE_3
DISABLE_4
DISABLE_5
DISABLE_6
DISABLE_7
DISABLE_8
OP_SELECT
Modes
The ISEL function block supports three modes of operation as defined by the MODE_BLK [5] parameter:
Manual (Man)The block output (OUT [7]) may be entered manually.
Automatic (Auto)OUT [7] reflects the selected input value.
Out of Service (OOS)The block is not processed. The BLOCK_ERR [6] parameter shows Out of Service. In this
mode, you can make changes to all configurable parameters. The target mode of a block may be restricted to one
or more of the supported modes.
The Input Selector block Actual mode will be Out of Service if any of the following are true:
The Actual mode of the resource block is not Auto
The Input Selector block Target mode is Out of Service
145
Instruction Manual
D103412X012
The Input Selector block Target mode is Auto, OP_SELECT [22] is not being used, and SELECT_TYPE [19] is 0. In this
case, the BLOCK_ERR [6] parameter shows a Block Configuration Error.
The Input Selector block Actual mode will be Manual if all of the above is not true and the Target mode is Manual.
Figure 413. Input Selector Function Block Schematic
IN_1
IN_2
IN_3
AUTO
Selection
Algorithm
IN_4
OUT
MAN
DISABLE_1
SELECTED
DISABLE_2
DISABLE_4
OP_SELECT
SEL_TYPE
MIN_GOOD
fieldbusfbus_229a
DISABLE_3
SELECT_TYPE
NOTE: THIS FIGURE DOES NOT INCLUDE THE ADDITIONAL
4 INPUTS IN THE EXTENDED PARAMETERS.
Status Handling
Quality Use and Propagation
In Auto mode, OUT [7] reflects the value and status of the selected input based on the following criteria:
A bad or disabled input is never used by any of the selection algorithms
For a selection algorithm to use an input with status of Uncertain, the STATUS_OPTS [10] parameter must have
Use Uncertain as Good.
STATUS_OPTS [10] is applied before selection.
If the number of good inputs is less than MIN_GOOD [20], or if the number of inputs evaluated is 0, the status of
OUT [7] and SELECTED [21] will be Bad.
If an input is disabled or its status is Bad and is selected via OP_SELECT [22], then the status of OUT [7] and
SELECTED [21] will be Bad. If the quality of the input is Uncertain, and the selection for the STATUS_OPTS [10]
parameter is Use Uncertain as Good, then the status of OUT [7] and SELECTED [21] will be Uncertain. Otherwise
the status of OUT [7] and SELECTED [21] will be Good Noncascade.
146
Instruction Manual
D103412X012
August 2012
When the block is in the Manual mode the status and substatus of OUT [7] and SELECTED [21] will be as follows:
Substatus will be nonspecific and the limit will be constant.
Quality of OUT [7] and SELECTED [21] will be Uncertain if STATUS_OPTS [10] is Uncertain if in Manual mode.
Otherwise, the quality of OUT [7] and SELECTED [21] will be Good Noncascade.
Limit Propagation
Refer to figure 414. When SELECT_TYPE [19] is Average, Not Limited is propagated unless all inputs have the same
limit status. If ll inputs have the same limit status, the limit status of the inputs is propagated.
If SELECT_TYPE [19] is Middle and the number of inputs used by the algorithm is greater than one: Not Limited is
propagated unless all selected inputs have the same limit status, in which case the limit status of the inputs is
propagated.
If SELECT_TYPE [19] is Middle and a single input, or if Maximum or Minimum then: If the selected input is a constant
and Middle, Constant is propagated. Otherwise, if the selected input is a constant and Maximum or Minimum,
propagate low if Maximum, propagate high if Minimum. If the selected input is not a constant, propagate selected
input limit as is.
When SELECT_TYPE [19] is First Good or Hot Spare or if OP_SELECT [22] is nonzero, propagate selected input limit as
is.
Substatus Propagation
Refer to figure 415. For SELECT_TYPE [19] of Maximum, Minimum, First Good, Hot Spare, and Middle with only one
input, simply propagate substatus as is.
For SELECT_TYPE [19] of Maximum and Minimum with more than one input with the same value, propagate substatus
if all inputs are the same.
For SELECT_TYPE [19] of Average or Middle with more than one input, propagate NonSpecific.
If the status of OUT [7] is Bad, then the substatus will be as follows:
Out of Service if the Target mode is Out of Service.
Configuration Error with a BLOCK_ERR [6] of Configuration Error if the Actual mode is Out of Service.
Otherwise a substatus of NonSpecific.
147
Instruction Manual
D103412X012
Propagate
selected input
limit status
No
OP_SELECT
equal to zero?
Yes
SELECT_TYPE
Average?
Yes
Yes
No
No
Propagate
Not Limited
Yes
SELECT_TYPE
Middle?
More than 1
input?
Yes
No
No
Yes
Propagate that
limit status
No
Propagate
Not Limited
Input a
constant?
Yes
Propagate
Constant
No
SELECT_TYPE
Maximum?
Yes
Yes
Propagate
Low Limit
Yes
Propagate
High Limit
No
No
SELECT_TYPE
Minimum?
Input a
constant?
Yes
No
No
SELECT_TYPE
First Good or Hot
Spare?
Input a
constant?
Yes
Propagate
selected input
limit status
No
148
NOTES:
1
LIMIT
MANIPULATION FOR A CONSTANT INPUT FOR MAXIMUM AND MINIMUM IS BASED
UPON THE FOUNDATION FIELDBUS SPECIFICATION. THE REASONING IS BASED ON HIGH SELECT
PROVIDING A LOW LIMIT STATUS AND LOW SELECT PROVIDING A HIGH LIMIT STATUS.
Instruction Manual
D103412X012
August 2012
Yes
MODE_BLK
OOS?
Propagate Bad,
Out of Service
No
STATUS_OPTS Un
certain if Man
Mode?
Yes
MODE_BLK
MAN?
No
Yes
Propagate
Uncertain
No
Propagate Good
Noncascade
MODE_BLK must
be Auto
1
OP_SELECT
status?
Bad
Propagate Bad,
Nonspecific
Good
1
OP_SELECT
value >0?
Yes
Propagate Good
Noncascade
Bad
No
At least 1 good
input?
Good
Selected in
put status?
No
Propagate Bad,
Nonspecific
Yes
SELECT_TYPE
Middle or
Average?
Yes
One input?
Multiple
Inputs
No
SELECT_TYPE
Maximum or
Minimum?
Yes
Yes
One input?
Propagate
Nonspecific
Yes
Multiple
Inputs
No
Yes
Propagate input
substatus as is
Propagate input
substatus as is
No
Propagate
Nonspecific
No
Illegal Select Type
should never be reached
Yes
NOTES:
AN INPUT STATUS MAY BE BAD, GOOD, OR UNCERTAIN. IF BAD, THE INPUT IS NOT USED AND THE STATUS IS PROPAGATED
AS BAD WITH SUBSTATUS NONSPECIFIC. IF GOOD IT IS USED AND THE STATUS IS PROPAGATED AS GOOD
(NONCASCADE). IF UNCERTAIN, AND STATUS_OPTS IS USE UNCERTAIN AS GOOD THEN THE INPUT IS USED AND THE
STATUS IS PROPAGATED AS GOOD (NONCASCADE), OTHERWISE IT IS NOT USED AND THE STATUS IS PROPAGATED AS
BAD WITH SUBSTATUS NONSPECIFIC.
149
Instruction Manual
August 2012
D103412X012
STATUS_OPTS Supported
In the STATUS_OPTS [10] parameter, you can select from the following options to control the status handling:
Use Uncertain as Goodsets the OUT [7] status to Good when the selected input status is Uncertain.
Uncertain if in Manual mode: sets the OUT [7] status to Uncertain when the mode is Manual.
Note
The block mode must be Out of Service to set STATUS_OPTS [10].
Input Selection
The ISEL function block reads the values and statuses of as many as eight inputs (IN_1 [11], IN_2 [12], IN_3 [13], IN_4
[14], IN_5 [25], IN_6 [26], IN_7 [27], IN_8 [28]). To use any of the six selection algorithms to select the output,
OP_SELECT [22] must be 0. To specify which algorithm to use, configure the selector type parameter (SELECT_TYPE
[19]) as follows:
Maximumselects the input with the highest value from the inputs that are not bad and not disabled.
Minimumselects the input with the lowest value from the inputs that are not bad and not disabled.
Averagecalculates the average value of the inputs that are not bad and not disabled and provides it as the output.
For example, if the number used to average (AVG_USE [33]) is 4 and the number of connected inputs is 6, then the
highest and lowest values would be dropped prior to calculating the average. If AVG_USE [33] is 2 and the number
of connected inputs is 7, then the two highest and lowest values would be dropped prior to calculating the average
and the average would be based on the middle three inputs.
MiddleIf the number of good usable inputs is odd, then it selects the middle value. If the number of good usable
inputs is even, then it averages the middle two values and selects status as worst of two. If both inputs' limit status
are not the same then it sets limit status of Not Limited.
First Goodselects the first input that is not bad and not disabled, starting with IN_1 [11].
Hot Spareinitially uses the input selected as first good. If the selected input goes bad, the first good selection is
repeated. If the selected input remains good, it stays selected. If the originally selected input returns to good status
the selection does not change. Selection changes only if the currently selected input goes bad.
Disabling Inputs
Use the parameters DISABLE_1 [15], DISABLE_2 [16], DISABLE_3 [17], DISABLE_4 [18], DISABLE_5 [29], DISABLE_6
[30], DISABLE_7 [31] and DISABLE_8 [32] to disable the corresponding inputs. An input that is disabled will not be used
by any of the selection algorithms.
The status of the disable parameter must be Good, Good_Cascade, or Uncertain with a STATUS_OPTS [10] of
Use Uncertain as Good in order to be evaluated. If the status of the disable parameter is Bad, its last usable value is
maintained and acted upon. If the device restarts, losing the last usable value, the last usable value is set to disabled.
150
Instruction Manual
D103412X012
IN_1 through IN_8 and DISABLE_1 through DISABLE_8 are nonvolatile type parameters so if they are Linked they will
automatically have Bad status until connections are reestablished. If they are not Linked, they will be restored with the
previous value from NVM across device restarts.
Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block error for the PID
block are defined above.
Process alarm detection is based on OUT [7] value. You can configure the alarm limits of the following standard
alarms:
High (HI_LIM [40])
High high (HI_HI_LIM [38])
Low (LO_LIM [42])
Low low (LO_LO_LIM [44])
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent
of the PV span can be set using the ALARM_HYS [36] parameter. The priority of each alarm is set in the following
parameters:
HI_PRI [39]
HI_HI_PRI [37]
LO_PRI [41]
LO_LO_PRI [43]
ACK_OPTION [35] is used to set automatic acknowledgement of alarms.
ALARM_SUM [34] indicates the current alert status, unacknowledged states, and disabled states of the alarms
associated with the function block.
151
Instruction Manual
D103412X012
Alarms are grouped into five levels of priority, as shown in table 438.
Table 438. ISEL Function Block Alarm Priorities
Priority Description(1)
Priority Number
0
The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected.
An alarm condition with a priority of 1 can be recognized by the system. The device monitors the alarm but does not report it
until requested by the host system.
An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
diagnostics and system alerts).
3-7
8-15
1. The priority classes advise and critical have no relationship to Plant Web Alerts.
Block Errors
Table 439 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the
ISEL block and are provided only for your reference.
Table 439. BLOCK_ERR Conditions
Condition Number
Other (N/A)
Block Configuration Error If OP_SELECT is not being used, and SELECT_TYPE = 0. This implies OP_SELECT status is good and actual
mode is AUTO.
Input failure/process variable has Bad status Set if any IN or any DISABLE or OP_SELECT is bad and connected. This means that a
status of BAD NC would not cause an input failure but a status of BAD LUV or BAD no LUV would cause and input failure.
Output failure Set if OUT quality is bad and the Actual mode is not Out of Service.
10
11
12
13
14
Power Up Set if the Target mode is Out of Service when powered up until the mode is changed.
15
152
Instruction Manual
D103412X012
August 2012
Index
Number
RO / RW
Block
Mode
Range
Initial
Value
Description
Static Revision
ST_REV
RO
N/A
0 to 65535
Tag Description
TAG_DESC
RW
ALL
7 bit ASCII
spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
RW
ALL
1 to 255
Block Mode
MODE_BLK
TARGET
5.1
RW
ALL
ACTUAL
5.2
RO
ALL
PERMITTED
5.3
RW
ALL
NORMAL
5.4
RW
ALL
Block Error
BLOCK_ERR
Output
OUT
Output Range
OUT_RANGE
Grant Deny
GRANT_DENY
RO
N/A
MAN
OOS
ALL
GRANT
9.1
ALL
DENY
9.2
ALL
Status Options
STATUS_OPTS
Input 1
IN_1
Input 2
IN_2
10
11
12
OOS
ALL
ALL
OOS until
block is
configured,
then last
valid target
OOS+MAN+AUTO
OOS+MAN
+AUTO
AUTO
1: Block
Configuration Error
7: Input Failure / Bad
PV status
8: Output Failure
14: Power Up
15: OutofService
Status
OUT_RANGE
Dynamic
Dynamic
Value
EU at 100%
EU at 0%
Units Index
Decimal Point
0: Program
1: Tune
2: Alarm
3: Local
100
0
%
2
All bits: 0
All bits:0
2: Use Uncertain as
GOOD
8: Uncertain if MAN
All bits: 0
Status
BAD
NC
constant
Value
Status
BAD
NC
constant
Value
0
-Continued-
153
Instruction Manual
D103412X012
Input 4
IN_4
Index
Number
RO / RW
13
Block
Mode
ALL
14
ALL
15
ALL
Range
BAD
NC
constant
Status
Value
Status
BAD
NC
constant
Value
Status
BAD
NC
constant
Value
0=Use
1=Disable
16
ALL
Value
0=Use
1=Disable
17
ALL
Value
0=Use
1=Disable
18
ALL
Min Good
MIN_GOOD
20
ALL
1-4
0 initial value only
Selected
SELECTED
21
Status
Value
0-8
Dynamic
Status
BAD
NC
constant
Value
0-8
ALL
-Continued-
154
ALL
22
19
N/A
Select Type
SELECT_TYPE
RO
Description
Value
0=Use
1=Disable
1=First Good
2=Minimum
3=Maximum
4=Middle
5=Average
6=Hot Spare
Operator Select
OP_SELECT
0
BAD
NC
constant
Status
Disable Analog Input 4
DISABLE_4
0
BAD
NC
constant
Status
Disable Analog Input 3
DISABLE_3
0
BAD
NC
constant
Status
Disable Analog Input 2
DISABLE_2
Initial
Value
Instruction Manual
D103412X012
August 2012
Index
Number
RO / RW
Block
Mode
Range
Initial
Value
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Update Reported
2=Updated not
reported
23
23.1
RW
UPDATE_STATE
23.2
RO
N/A
TIME_STAMP
23.3
RO
N/A
STATIC_REVISION
23.4
RO
N/A
RELATIVE_INDEX
23.5
RO
N/A
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
Description
24
24.1
ALARM_STATE
24.2
RO
N/A
TIME_STAMP
24.3
RO
N/A
SUBCODE
24.4
RO
N/A
VALUE
24.5
RO
N/A
Extended Parameters
In 5
IN_5
In 6
IN_6
In 7
IN_7
25
26
27
ALL
ALL
ALL
BAD
NC
constant
Status
Value
Status
BAD
NC
constant
Value
Status
BAD
NC
constant
BAD
NC
constant
Value
In 8
IN_8
28
29
ALL
ALL
Status
Value
Status
BAD
NC
constant
Value
0=Use
1=Disable
BAD
NC
constant
0
Status
Disable Analog Input 6
DISABLE_6
30
ALL
Value
0=Use
1=Disable
-Continued-
155
Instruction Manual
D103412X012
Index
Number
RO / RW
Block
Mode
Range
BAD
NC
constant
Value
Disable Analog Input 7
DISABLE_7
31
ALL
Status
0=Use
1=Disable
32
ALL
33
0
BAD
NC
constant
Value
Disable Analog Input 8
DISABLE_8
Initial
Value
Status
0=Use
1=Disable
1 to 8
Description
Data Type: DS66
Enable/Disable for Input_7, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
34
CURRENT
34.1
RO
NA
UNACKNOWLEDGED
34.2
RO
NA
UNREPORTED
34.3
RO
NA
DISABLED
34.4
RW
ALL
1: Hi Hi
2: Hi
3: Lo Lo
4: Lo
ALL
1: Hi Hi
2: Hi
3: Lo Lo
4: Lo
36
ALL
0 to 50%
0.50%
37
ALL
0 TO 15
38
ALL
High Priority
HI_PRI
39
ALL
High Limit
HI_LIM
40
ALL
Low Priority
LO_PRI
41
ALL
Low Limit
LO_LIM
42
ALL
43
ALL
44
ALL
45
Acknowledge Option
ACK_OPTION
35
Alarm Hysteresis
ALARM_HYS
UNACKNOWLEDGED
45.1
RW
0 TO 15
0 TO 15
0 TO 15
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported
156
ALARM_STATE
45.2
RO
N/A
TIME_STAMP
45.3
RO
N/A
SUBCODE
45.4
RO
N/A
VALUE
45.5
RO
N/A
0
-Continued-
Instruction Manual
D103412X012
August 2012
Index
Number
RO / RW
Block
Mode
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported
Range
Initial
Value
46
46.1
ALARM_STATE
46.2
RO
N/A
TIME_STAMP
46.3
RO
N/A
SUBCODE
46.4
RO
N/A
VALUE
46.5
RO
N/A
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported
Low Alarm
LO_ALM
UNACKNOWLEDGED
47.1
47.2
RO
N/A
TIME_STAMP
47.3
RO
N/A
SUBCODE
47.4
RO
N/A
VALUE
47.5
RO
N/A
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported
UNACKNOWLEDGED
48
48.1
ALARM_STATE
48.2
RO
N/A
TIME_STAMP
48.3
RO
N/A
SUBCODE
48.4
RO
N/A
VALUE
48.5
RO
N/A
Output Discrete
OUT_D
47
ALARM_STATE
Description
49
MAN
OOS
0
Status
Value
0, 1
Status
Alarm Select
ALM_SEL
50
ALL
1: Hi Hi
2: Hi
3: Lo Lo
4: Lo
All bits:0
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
157
Instruction Manual
D103412X012
Index Number
Index Number
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
BLOCK_ERR
OUT
OUT
11
IN_1
11
IN_1
12
IN_2
12
IN_2
13
IN_3
13
IN_3
14
IN_4
14
IN_4
15
DISABLE_1
15
DISABLE_1
16
DISABLE_2
16
DISABLE_2
17
DISABLE_3
17
DISABLE_3
18
DISABLE_4
18
DISABLE_4
21
SELECTED
21
SELECTED
22
OP_SELECT
22
OP_SELECT
25
IN_5
25
IN_5
26
IN_6
26
IN_6
27
IN_7
27
IN_7
28
IN_8
28
IN_8
29
DISABLE_5
29
DISABLE_5
30
DISABLE_6
30
DISABLE_6
31
DISABLE_7
31
DISABLE_7
32
DISABLE_8
32
DISABLE_8
34.1
ALARM_SUM.CURRENT
34.1
ALARM_SUM.CURRENT
34.2
ALARM_SUM.UNACKNOWLEDGED
34.2
ALARM_SUM.UNACKNOWLEDGED
34.3
ALARM_SUM.UNREPORTED
34.3
ALARM_SUM.UNREPORTED
34.4
ALARM_SUM.DISABLED
34.4
ALARM_SUM.DISABLED
49
158
Parameter
ST_REV
Parameter
ST_REV
OUT_RANGE
9.1
GRANT_DENY.GRANT
9.2
GRANT_DENY.DENY
OUT_D
Parameter
ST_REV
STRATEGY
ALERT_KEY
10
STATUS_OPTS
19
SELECT_TYPE
20
MIN_GOOD
33
AVG_USE
35
ACK_OPTION
36
ALARM_HYS
37
HI_HI_PRI
38
HI_HI_LIM
39
HI_PRI
40
HI_LIM
41
LO_PRI
42
LO_LIM
43
LO_LO_PRI
44
LO_LO_LIM
50
ALM_SEL
Instruction Manual
D103412X012
August 2012
Online
Block Error
Disable Analog Input 1: Status
Disable Analog Input 1: Value
Disable Analog Input 2: Status
Disable Analog Input 2: Value
Disable Analog Input 3: Status
Disable Analog Input 3: Value
Disable Analog Input 4: Status
Disable Analog Input 4: Value
Input 1: Status
Input 1: Value
Input 2: Status
Input 2: Value
Input 3: Status
Input 3: Value
Input 4: Status
Input 4: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Operator Selected: Status
Operator Selected: Value
Output: Status
Output: Value
Selected: Status
Selected: Value
Status
Connectors
Block Error
Disable Analog Input 1: Status
Disable Analog Input 1: Value
Disable Analog Input 2: Status
Disable Analog Input 2: Value
Disable Analog Input 3: Status
Disable Analog Input 3: Value
Disable Analog Input 4: Status
Disable Analog Input 4 : Value
Input 1: Status
Input 1: Value
Input 2: Status
Input 2: Value
Input 3: Status
Input 3: Value
Input 4: Status
Input 4: Value
Operator Select: Status
Operator Select: Value
Output: Status
Output: Value
Selected: Status
Selected: Value
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Output: Status
Output: Value
Output Range: EU at 100%
Output Range: EU at 0%
Output Range: Units Index
Output Range: Decimal
Grant Deny: Grant
Grant Deny: Deny
Status Options
Input 1: Status
Input 1: Value
Input 2: Status
Input 2: Value
Input 3: Status
Input 3: Value
Input 4: Status
Input 4: Value
Disable Analog Input 1: Status
Disable Analog Input 1: Value
Disable Analog Input 2: Status
Disable Analog Input 2: Value
Disable Analog Input 3: Status
Disable Analog Input 3: Value
Disable Analog Input 4: Status
Disable Analog Input 4: Value
Select Type
Min Good
Selected: Status
Selected: Value
Operator Select: Status
Operator Select: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Analog Input 5: Status
Analog Input 5: Value
Analog Input 6: Status
Analog Input 6: Value
Analog Input 7: Status
Analog Input 7: Value
Analog Input 8: Status
Analog Input 8: Value
Disable Analog Input 5: Status
Disable Analog Input 5: Value
Disable Analog Input 6: Status
Disable Analog Input 6: Value
Disable Analog Input 7: Status
Disable Analog Input 7: Value
Disable Analog Input 8: Status
Disable Analog Input 8: Value
Number Used to average
All continued
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Alarm Hysteresis
High High Priority
High High Limit
High Priority
High Limit
Low Priority
Low Limit
Low Low Priority
Low Low Limit
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
High Alarm: Unacknowledged
High Alarm: Alarm State
High High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Alarm Output: Status
Alarm Output: Value
Alarm Select
159
Instruction Manual
D103412X012
OS
RCAS IN
CAS IN
OUT 1
OUT 2
This block is normally used in split ranging or sequencing of multiple valve applications. A typical split range
application has both valves closed when the splitter input is 50%. One valve opens fully as the input drops to 0%. The
other valve opens as the input rises above 50%.
A typical sequencing application has both valves closed at 0% input. One valve fully opens as the input rises to 50% and
the other stays shut. The second valve opens as the input rises above 50%, and the first valve may remain open or shut
off quickly.
Because this block is in the control path, it is able to pass limit and cascade initialization information back to the
upstream block. Table 448 lists the OS block parameters and their descriptions, units of measure, and index numbers.
Figures 417 and 418 illustrate the internal components of the OS function block.
160
Instruction Manual
D103412X012
August 2012
IN_ARRAY
OUT_ARRAY
LOCKVAL
RCAS_IN
OUT 1
SP
CAS_IN
Auto
OUT 2
BKCAL_IN_1
RCAS_OUT
BKCAL_IN_2
CAS_OUT
CAS_IN
F
Setpoint
Limiting SP
"
Setpoint
Rate
Limiting
SP_WRK
"
SP_RATE_DN
SP_RATE_UP
IN_ARRAY
OUT_ARRAY
LOCKVAL
"
Calculate
Ouput
"
BKCAL_OUT
F
F
F
"
"
Balance
Ouput
BAL_TIME
"
BKCAL_IN_2
"
BKCAL_IN_1
"
Shed
Mode
"
"
MODE
"
F
"
Balance
Ouput
"
OUT 1
"
OUT 2
Modes
The Output Splitter function block supports the following actual modes:
161
Instruction Manual
August 2012
D103412X012
Out of Service (OOS)The block is not processed. FIELD_VAL and PV are not updated and the OUT status is set to
Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, you can make changes to all
configured parameters.
By using permitted mode the target mode of a block may be restricted to one or more of the following modes: Cas,
Auto or OOS.
Note
The output splitter function block must be in Auto for the mode to go to CAS.
Initialization Manual (IMan)The output path is not complete (for example, the cascade-to-slave path might not be
open). In IMan mode, OUT tracks BKCAL_IN, which allows for bumpless transfer of control.
Automatic (Auto)The block outputs (OUT_1 and OUT_2) reflect the target operating point specified by the
setpoint (SP) parameter.
Cascade (Cas)The SP parameter is set by another function block through a connection to CAS_IN. The SP value is
used to set the OUT parameters automatically. This is the most frequently used mode in this block.
The block's normal mode is Cascade (Cas). You can isolate the block for testing by using Automatic (Auto) mode and
adjusting the setpoint.
When a block attached to an output requests initialization, one of the following actions might occur:
When the other output is not in Cas mode, the block attached to the input is initialized.
When the other output is in Cas mode, this output returns to the value calculated from its slope in a specified time
period.
Status Handling
Substatus value received at CAS_IN [14] is passed to both outputs, except for those used in the cascade handshake.
An IFS goes to both outputs. The status option IFS if Bad CAS_IN is available.
If the Status Option to Propagate failure is set, the block propagates device failure only if both BKCAL_IN show failed
status. Otherwise the upstream cascade would be broken by a failure at either output.
The statuses of OUT_1 [8] and OUT_2 [9] are determined by the statuses of BKCAL_IN_1 and BKCAL_IN_2 and the
actual mode of the block.
When a BKCAL_IN input sees that its downstream block is not in Cas mode, the Splitter function block sets the
corresponding OUT value to the BKCAL_IN value. However, this may not be the same value that is calculated by the
splitter algorithm. When the mode of the downstream block is changed to Cas, the difference between the calculated
output and the backcalculation input is computed and the difference is added to the calculated output. Next, the
difference is reduced to zero over the time defined by the BAL_TIME parameter.
When both BKCAL_IN_1 and BKCAL_IN_2 indicate that the downstream blocks are not in Cas mode or have Bad status,
the first downstream block that goes to Cas mode causes the upstream block to initialize so that there is no difference
between the calculated output and the backcalculation input. This provides bumpless transfer for the first
downstream block.
162
Instruction Manual
D103412X012
August 2012
Limit Handling
The splitter function block is designed to combine the limit information from the two downstream blocks into limits
for the upstream block. The general principle is to allow the upstream block to continue control for as long as possible.
The upstream block is highlimited (BKCAL_OUT of the Splitter block has highlimited status) when:
Both downstream blocks are highlimited (both BKCAL_INS of the Splitter block have highlimited status)
or
One downstream block is highlimited, the associated output slope is positive, and the other block has Bad status or
is not in Cas mode
or
One downstream block is lowlimited, the associated output slope is negative, and the other block has Bad status or
is not in Cas mode
or
SP is greater than or equal to X22
The upstream block is lowlimited when:
Both downstream blocks are lowlimited
or
One downstream block is lowlimited, the associated output slope is positive, and the other block has Bad status or
is not in Cas mode
or
One downstream block is highlimited, the associated output slope is negative, and the other block has Bad status
or is not in Cas mode
or
SP is less than or equal to X11
163
Instruction Manual
D103412X012
blocks may effect the useful range of a line. Units of percent are used in the examples because the common
application of this block is to valves, but any units may be used to suit the application.
Figure 419. Split Range and Sequence Operation
Split Range
(X22 , Y22)
100%
Sequencing
(X12 , Y12)
100%
(X11 , Y11)
(X22 , Y22)
OUT_1
OUT_1
OUT_2
OUT_2
0%
(X21 , Y21)
(X12 , Y12)
0%
50%
100%
0%
(X21 , Y21)
(X11 , Y11)
0%
SP
50%
X
100%
SP
The following parameters as paired coordinates are used to specify the output splitter operation:
X11, Y11, X12, Y12
X21, Y21, X22, Y22
Where XnJ is the value of SP associated with OUT_n and Xn1 and Xn2 refer to the 1st and 2nd coordinates of the nth
curve respectively. YnJ is the value of OUT_n and Yn1 and Yn2 refer to the 1st and 2nd coordinates of the nth curve
respectively.
By specifying the coordinates as shown in tables 445 and 446, the endpoints of the lines are defined. The contents of
the respective X's are held in the IN_ARRAY parameter and the contents of the respective Y's are held in the
OUT_ARRAY parameter. If a set of points are specified such that a region of the input range is not specified, then the
corresponding OUT_n will be set to the closest endpoint of the input value, either high or low, when the specified
region is exceeded.
Table 445. IN_ARRAY Coordinates
Index
Coordinate
Coordinate
A configuration error is set in BLOCK_ERR and the actual mode of the block goes to Out of Service if the X values have
any of the following conditions: X21 < X11, X12 < = X11, X22 < = X21.
Refer to figure 420 for an example of LOCKVAL = true, and figure 421 for an example of LOCKVAL = false. The
parameter LOCKVAL provides an option to specify whether OUT_1 remains at its ending level when control is switched
164
Instruction Manual
D103412X012
August 2012
to OUT_2, or goes to Y11. If LOCKVAL is true, OUT_1 remains at its ending value when X is greater than X12. If LOCKVAL
is false, then OUT_1 goes to Y11 when X is greater than X12 .
Figure 420. OUT with LOCKVAL True
OUT 2
OUT 1
OUT 1 remains at
end point when
OUT_2 is nonzero
OUT 1
OUT 2
OUT_1 goes to zero
OUT_2 becomes
0%
50%
SP
0%
100%
50%
SP
100%
Some hysteresis in the switching point may be required because the output may change by a full stroke of the valve.
HYSTVAL [12] contains the amount of hysteresis. If X < = X12-HYSTVAL, OUT_1 may be determined by the calculated
y value. If X12-HYSTVAL < X < X12 and X has not reached X12 since it was less than X12-HYSTVAL, OUT_1 may be
determined by the calculated y value. If X12-HYSTVAL < X < X12 and X has reached X12 since it was less than
X12-HYSTVAL, OUT_1 may be determined by the LOCKVAL setting. If X12 < X, OUT_1 may be determined by the
LOCKVAL setting.
BK_CAL_IN
CASIN
PID1
OUT
CASIN
BK_CAL_IN2
Splitter
BK_CAL_IN1
PID2
BK_CAL_OUT
OUT2
BK_CAL_OUT
OUT1
CASIN
AO
BK_CAL_OUT
165
Instruction Manual
D103412X012
CAS_IN of the Splitter receives the OUT of PID1. BKCAL_IN of PID1 receives BKCAL_OUT of the Splitter. CAS_IN of the
AO receives OUT_1 of the Splitter and PID2 receives OUT_2 of the Splitter. BKCAL_IN_1 of the Splitter receives
BKCAL_OUT of the AO and BKCAL_IN_2 of the Splitter receives BKCAL_OUT of PID2.
The discussion in this section defines the behavior which is used to handle the initial value calculation and status which
can in turn be sent to PID1. This behavior is defined in such a way that no bumps are generated by changing modes,
and that PID1 does not wind up.
The splitter utilizes special handling for cascade initialization because it has two independent outputs. When a
downstream block indicates to the splitter that it wants to initialize, by asserting IR (initialization request) on its
BKCAL_OUT, one of two things happens. Under some circumstances, it is possible to pass an initialization request from
a downstream block back up to the block upstream of the splitter, so that all three blocks balance for bumpless
transfer to cascade mode. Otherwise, the requested splitter output goes to the requested value by placing an internal
offset between that output and the output of the curve, and then ramping that offset to zero in BAL_TIME seconds
after the cascade is made up.
The splitter normally runs with both outputs connected to blocks in cascade mode. If one or both of the blocks is not in
cascade mode, special limiting action is taken. Specifically, if one block indicates that it is not in cascade by NI (not
invited) status on its BKCAL_OUT, then the BKCAL_OUT of the splitter asserts limits at the range extremes of the block
that is still in cascade mode. Even if the upstream controller does not want to operate in that range, there will be no
reset windup when it can move into the range. If both downstream blocks show NI, then the splitter can only wait until
one of them requests cascade initialization. BKCAL_OUT of the splitter can hold the upstream block at the value of the
SP. The actual mode is IMan.
When cascade initialization is requested, by IR substatus on a BKCAL_IN, it is first necessary to determine if the other
BKCAL_IN has NI substatus. If so, the value at the BKCAL_IN asserting IR is taken as the Y value for its curve, and the
resulting X value is sent on BKCAL_OUT to PID1. If the other substatus is OK, then the internal offset and BAL_TIME is
used. If both blocks have IR substatus, then one output is processed until its cascade is closed. The choice is based on
the presence of limit status in BKCAL_IN. If BKCAL_IN_1 is limited, then if BKCAL_IN_2 is not limited then OUT_2 is
processed first, else OUT_1 is processed first.
Cascade initialization is also required when the block transitions from Auto to Cas mode. This action is identical to that
described for the PID block.
The required actions are summarized in table 447.
Table 447. OUT_ARRAY Coordinates
BKCAL_IN_1
BKCAL_IN_2
BKCAL_OUT
Action
NI
NI
NI
Not Specified
NI
OK
OK
OK
NI
OK
IR
NI
IR
IR
OK
OK
NI
IR
IR
OK
IR
OK
The BKCAL_OUT status shows limited high if an increase in SP cannot be effectively passed on to either output because
the BKCAL_IN_n of both outputs indicates that a move in the needed direction is limited. Similarly, limited low is set if
a decrease in SP cannot be effectively passed on to either output. The slope of the limited line(s) affects the limit
direction. BKCAL_OUT also shows limit status at the X extremes X11 and X22.
Initialization is not automatic under all circumstance because some situations have conflicting needs. In general, when
a control region is in trouble, the upstream controller is limited so it will not drive further into that region. When you
want to move to the other active region, you can put the upstream controller into Man mode and move it, or you can
166
Instruction Manual
D103412X012
August 2012
drop the good downstream block out of Cas mode for one evaluation cycle and then restore Cas mode. This initializes
the upstream controller to the remaining good region of control.
Index
Number
RO /
RW
Block
Mode
Initial
Value
Description
Static Revision
ST_REV
RO
N/A
0 to 65535
Tag Description
TAG_DESC
RW
ALL
7 bit ASCII
Spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
RW
ALL
1 to 255
Block Mode
MODE_BLK
5
7:OOS
3:AUTO
2:CAS
OOS until
block
configured,
then last
valid target
OOS+AUTO+CAS
Range
TARGET
5.1
RW
ACTUAL
5.2
RO
OOS
OOS AUTO
CAS
PERMITTED
5.3
RW
NORMAL
5.4
RW
Block Error
BLOCK_ERR
Setpoint
SP
Output 1
OUT_1
Output 2
OUT_2
Output 1 Range
OUT_1_RANGE
10
RO
RO
AUTO+CAS
N/A
1: Block
Configuration Error
7: Input Failure/Bad
PV Status
8: Output Failure
14: Powerup
15: OutofService
Dynamic
MAN
OOS
OUT_SCALE
+/- 10%
MAN
OOS
OUT_SCALE
+/- 10%
EU at 100%
EU at 0 %
Unit Index
Decimal Point
100
0
%
2
-Continued-
167
Instruction Manual
D103412X012
Index
Number
RO /
RW
Output 2 Range
OUT_2_RANGE
11
RO
Grant Deny
GRANT_DENY
12
Block
Mode
EU at 100%
EU at 0 %
Unit Index
Decimal Point
GRANT
12.1
N/A
DENY
12.2
N/A
13
OOS
Status Options
STATUS_OPTS
Cascade Input
CAS_IN
Range
14
Initial
Value
Description
100
0
%
2
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
All bits: 0
All bits: 0
Status
BAD:
NC:
const
Value
15
Input Array
IN_ARRAY
16
All: 0
Output Array
OUT_ARRAY
17
All: 0
Lockval
LOCKVAL
18
19
RO
Status Limits
0=Undfined
1=no lock
2=lock
BAD:
NC:
const
Status
20
0=
Undefined
Value
Status
BAD:
NC:
const
Value
Positive
Balance Time
BAL_TIME
21
Hystval
HYSTVAL
22
Update Event
UPDATE_EVT
23
RO
N/A
UNACKNOWLEDGED
23.1
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=
Undefined
UPDATE STATE
23.2
RO
N/A
0=Undefined
1=Update Reported
2=Updated not
reported
0=
Undefined
TIME_STAMP
23.3
RO
N/A
STATIC_REVISION
23.4
RO
N/A
RELATIVE_INDEX
23.5
RO
N/A
0
-Continued-
168
Instruction Manual
D103412X012
August 2012
Index
Number
Block Alarm
BLOCK_ALM
RO /
RW
Block
Mode
RW
N/A
0: Undefined
1: Acknowledged
2: Unacknowledged
0: Undefined
1: Clear reported
2: Clear not reported
3: Active reported
4: Active not
reported
Range
Initial
Value
Description
24
UNACKNOWLEDGED
24.1
ALARM_STATE
24.2
RO
N/A
TIME_STAMP
24.3
RO
N/A
SUBCODE
24.4
RO
N/A
VALUE
24.5
RO
N/A
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 449. OS Function Block, View 1
Index Number
Index Number
Parameter
ST_REV
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
BLOCK_ERR
SP
SP
OUT_1
OUT_1
OUT_2
OUT_2
14
CAS_IN
14
CAS_IN
15
BKCAL_OUT
19
BKCAL_1_IN
20
BKCAL_2_IN
Parameter
ST_REV
10
OUT_1_RANGE
11
OUT_2_RANGE
12.1
GRANT_DENY.GRANT
12.2
GRANT_DENY.DENY
Parameter
ST_REV
STRATEGY
ALERT_KEY
13
STATUS_OPTS
16
IN_ARRAY
17
OUT_ARRAY
18
LOCKVAL
21
BAL_TIME
169
170
Instruction Manual
D103412X012
Instruction Manual
D103412X012
August 2012
OUT
OUT
OUT_D
FIELDBUSFBUS_31A
OUT_D
The AI block supports alarming, signal scaling, signal filtering, signal status calculation, mode control, and simulation.
In Automatic mode, the block's output parameter (OUT [8]) reflects the process variable (PV [7]) value and status. In
Manual mode, OUT [8] may be set manually. The Manual mode is reflected on the output status. A discrete output
(OUT_D [37]) is provided to indicate whether a selected alarm condition is active. Alarm detection is based on the OUT
[8] value and user specified alarm limits. Figure 424 illustrates the internal components of the AI function block, and
table 457 lists the AI block parameters and their units of measure, descriptions, and index numbers.
Modes
The AI function block supports three modes of operation as defined by the MODE_BLK [5] parameter:
Manual (Man) The block output (OUT [8]) may be set manually.
Automatic (Auto) OUT reflects the analog input measurement or the simulated value when simulation is enabled.
Out of Service (OOS) The block is not processed. FIELD_VAL [19] and PV [7] are not updated and the OUT [8] status
is set to Bad: Out of Service. The BLOCK_ERR [6] parameter shows Out of Service. In this mode, you can make
changes to all configured parameters. The target mode of a block may be restricted to one or more of the
supported modes.
Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block errors for the AI
block are defined in table 455.
171
Instruction Manual
D103412X012
ACCESS
ANALOG
MEAS.
HI_HI_LIM
HI_LIM
LO_LO_LIM
LO_LIM
CHANNEL
ALARM
DETECTION
OUT_D
ALARM_HYS
LOW_CUT
SIMULATE
L_TYPE
FIELD_VAL
PV
FILTER
PV_FTIME
IO_OPTS
STATUS
CALC.
OUT
MODE
FIELDBUSFBUS_02A
CUTOFF
CONVERT
STATUS_OPTS
OUT_SCALE
XD_SCALE
NOTES:
OUT_D = BLOCK OUTPUT VALUE AND STATUS
OUT_D = DISCRETE OUTPUT THAT SIGNALS A SELECTED ALARM CONDITION.
Process Alarm detection is based on the OUT [8] value. You can configure the alarm limits of the following standard
alarms:
High (HI_LIM [28])
High high (HI_HI_LIM [26])
Low (LO_LIM [30])
Low low (LO_LO_LIM [32])
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent
of the PV [7] span can be set using the ALARM_HYS [24] parameter. The priority of each alarm is set in the following
parameters:
HI_PRI [27]
HI_HI_PRI [25]
LO_PRI [29]
LO_LO_PRI [31]
Alarms are grouped into five levels of priority, as shown in table 453.
Table 453. AI Function Block Alarm Priorities
Priority Description(1)
Priority Number
0
The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected.
An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.
An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
diagnostics and system alerts).
3-7
8-15
1. The priority classes advise and critical have no relationship to PlantWeb Alerts.
172
Instruction Manual
D103412X012
August 2012
Table 454. Channel Selections for the Analog Input Function Block
Parameter(1)
Channel
Block
Index Number
XD_SCALE Units
TRAVEL_TARGET
TB
49
% (1342)
FINAL_POSITION_VALUE
TB
17
% (1342)
TRAVEL
TB
34
% (1342)
SUPPLY_PRESS
TB
35
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
PRESSURE_A
TB
36
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
PRESSURE_B
TB
37
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
PRESSURE_DIFF
TB
38
psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)
DRIVE_SIGNAL
TB
53
% (1342)
10
TRAVEL_DEVIATION
TB
52
% (1342)
11
TEMPERATURE
TB
48
C (1001), F (1002)
12
CYCLE_COUNT
TB
73
no units (1588)
13
TRAVEL_ACCUMULATION
TB
72
% (1342)
1. Refer to table 414 for transducer block parameter descriptions and table 425 for AO parameter descriptions.
Status Handling
The AI block only gets Good NonSpecified Unlimited or Bad Device Failure for status from the transducer. This is
reflected in FIELD_VAL.STATUS [19.1]. PV.STATUS [7.1] is the same as FIELD_VAL.STATUS [19.1]. OUT.STATUS [8.1]
can also reflect Bad, Out of Service in addition to PV.STATUS [7.1] values.
In the STATUS_OPTS [14] parameter, you can select from the following options to control the status handling:
Propagate Fail ForwardIf the status from the sensor is Bad, Device failure or Bad, Sensor failure, propogate it to OUT
without generating an alarm. The use of these substatus in OUT is determined by this option. Through this option,
you may determine whether alarming (sending out an alert) will be done by the block or propagated downstream for
alarming.
Figure 425. Analog Input Function Block Timing Diagram
FIELD_VAL
TIME (seconds)
PV_FTIME
FIELDBUSFBUS_03A
63% of Change
Uncertain if in Manual modeThe status of the Output is set to Uncertain when the mode is set to Manual.
Note
1. The instrument must be in Out of Service mode to set the status option.
2. The AI block only supports the Uncertain if in Manual and Propagate failure. Unsupported options are not grayed out; they
appear on the screen in the same manner as supported options.
173
Instruction Manual
D103412X012
Filtering
The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid
changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME [18] parameter. Set the filter
time constant to zero to disable the filter feature.
Signal Conversion
You can set the signal conversion type with the Linearization Type (L_TYPE [16]) parameter. You can view the
converted signal (in percent of XD_SCALE [10]) through the FIELD_VAL [19] parameter.
FIELD_VAL =
*XD_SCALE values
You can choose from direct, indirect, or indirect square root signal conversion with the L_TYPE [16] parameter.
Direct
Direct signal conversion allows the signal to pass through the accessed channel input value (or the simulated value
when simulation is enabled).
PV = Channel Value
Indirect
Indirect signal conversion converts the signal linearly to the accessed channel input value (or the simulated value when
simulation is enabled) from its specified range (XD_SCALE [10]) to the range and units of the PV [7] and OUT [8]
parameters (OUT_SCALE [11]).
PV =
FIELD_VAL
100
**OUT_SCALE values
PV =
FIELD_VAL
100
**OUT_SCALE values
174
Instruction Manual
D103412X012
August 2012
When the converted input value is below the limit specified by the LOW_CUT [17] parameter, a value of zero is used
for the converted value (PV [7]). This option is useful to eliminate false readings when the differential pressure
measurement is close to zero.
Note
Invert is the only I/O option supported by the AI block. You can set the I/O option in Out of Service mode only.
Advanced Features
The AI function block provided with the DVC6200f provides added capability through the addition of the following
parameters:
ALARM_SELAllows one or more of the process alarm conditions detected by the AI function block to be used in
setting its OUT_D [37] parameter.
OUT_DDiscrete output of the AI function block based on the detection of process alarm condition(s). This parameter
may be linked to other function blocks that require a discrete input based on the detected alarm condition.
STDDEV and CAP_STDDEV are diagnostic parameters that can be used to determine the variability of the process.
Simulation
To support testing, you can either change the mode of the block to manual and adjust the output value, or you can
enable simulation through the configuration tool and manually enter a value for the measurement value and its status.
To enable simulation, you must first install the Simulate Enable jumper across the instrument AUX terminals (see page
36). Next you must use the configuration tool to enable the parameter SIMULATE [9].
With simulation enabled, the actual measurement value has no impact on the OUT [8] value or the status.
Block Errors
Table 455 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are inactive for the AI block
and are given here only for your reference.
Table 455. BLOCK_ERR Conditions
Condition Number
Other
Block Configuration Error the selected channel carries a measurement that is incompatible with the engineering units
selected in XD_SCALE, the L_TYPE parameter is not configured, or CHANNEL = zero.
Simulate Active Simulation is enabled and the block is using a simulated value in its execution.
Local Override
Input failure/process variable had Bad status The hardware is bad, or a bad status is being simulated
Output failure
Memory failure
10
11
Lost NV Data
12
13
14
Power Up - This condition exists until the AI function block executes for the first time.
15
175
Instruction Manual
D103412X012
Troubleshooting
Refer to table 456 to troubleshoot any problem that you encounter.
Table 456. Troubleshooting
Symptom
Mode will not leave OOS
Possible Causes
Target mode is not set
Configuration error
Corrective Action
Set target mode to something other than OOS
BLOCK_ERR [6] will show the configuration error bit set. The
following are parameters that must be set before the block is
allowed out of OOS:
CHANNEL [15] must be set to a valid value and cannot be
left at initial value of 0.
XD_SCALE [10]. UNITS_INDEX must match the units in the
transducer block channel value.
L_TYPE [16] must be set to Direct, Indirect, or Indirect
Square Root and cannot be left at an initial value of 0.
Resource block
Schedule
Process and/or block alarms will not work
Features
Notification
Status Options
Linearization Type
Scaling
Scaling
176
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Write Block
Mode
Range
Initial
Value
Description
N/A
0 to 65535
ALL
7 bit ASCII
spaces
ALL
0 to 65535
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
RO
ALL
1 to 255
OOS
MAN
AUTO
TARGET
5.1
RW
ALL
ACTUAL
5.2
RO
ALL
OOS
OOS, MAN,
AUTO
PERMITTED
5.3
RW
ALL
NORMAL
5.4
RW
ALL
OOS+MAN+AUTO
AUTO
Block Error
BLOCK_ERR
RO
1: Block Configuration
Error
3: Simulate Active
7: Input Failure/ Bad PV
Status
14: Powerup
15: OutofService
Process Value
PV
RO
Primary Output
OUT
OUT_STATE
Simulate
SIMULATE
OOS, MAN
SIMULATE_STATUS
9.1
ALL
SIMULATE_VALUE
9.2
ALL
TRANSDUCER_STATUS
9.3
RO
TRANSDUCER_VALUE
9.4
RO
ENABLE/DISABLE
Transducer Scale
XD_SCALE
Output Scale
OUT_SCALE
9.5
10
11
0
0
ALL
0=Not Initialized
1=Simulation Disabled
2=Simulation Active
OOS
EU at 100%
EU at 10%
Units Index
Decimal Point
100
0
%
2
OOS
EU at 100%
EU at 10%
Units Index
Decimal Point
100
0
%
2
1=simulate
disabled
-Continued-
177
Instruction Manual
D103412X012
Index
Number
RO /
RW
Write Block
Mode
Range
Initial
Value
Description
All bits: 0
12
Valid Bits
0: Program
1: Tune
2: Alarm
3: Local
GRANT
12.1
ALL
DENY
12.2
ALL
13
OOS
All bits: 0
All bits: 0
I/O Options
IO_OPTS
Status Options
STATUS_OPTS
14
OOS
3: Propagate Failure
forward
6: Uncertain if Limited
7: Bad if Limited
8: Uncertain in Man
Mode
AI Channel
CHANNEL
15
OOS
0: Undefined
1: Direct
2: Indirect
3: Ind. Sqr. Root
All bits: 0
0: Undefined
0: Undefined
Linearization Type
L_TYPE
16
OOS, MAN
Low Cutoff
LOW_CUT
17
ALL
Positive
18
ALL
Positive
Field Value
FIELD_VAL
19
Updated Event
UPDATE_EVT
20
RO
UNACKNOWLEDGED
20.1
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
UPDATE_STATE
20.2
RO
N/A
0=Undefined
1=Update reported
2=Update not reported
0=Undefined
TIME_STAMP
20.3
RO
N/A
STATIC_REVISION
20.4
RO
N/A
RELATIVE_INDEX
20.5
RO
N/A
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
21
21.1
RW
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clearreported
2=Clearnot reported
3=Activereported
4=Activenot reported
ALARM_STATE
21.2
RO
TIME_STAMP
21.3
RO
SUBCODE
21.4
RO
VALUE
21.5
RO
-Continued-
178
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Write Block
Mode
Range
Initial
Value
22
CURRENT
22.1
RO
ALL
UNACKNOWLEDGED
22.2
RO
ALL
UNREPORTED
22.3
RO
ALL
DISABLED
22.4
RW
ALL
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm
All bits: 0
Description
Data Type: DS74 Current alert status,
unacknowledged states, unreported states, and
disabled states of the alarms associated with the
function block.
0=clear
0=acknowledged
0=reported
0=enabled
Acknowledge Option
ACK_OPTION
23
ALL
0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm
Alarm Hysteresis
ALARM_HYS
24
ALL
0 - 50%
0.50%
25
ALL
0 to 15
26
ALL
OUT_SCALE
High Priority
HI_PRI
27
ALL
0 to 15
Hi Limit
HI_LIM
28
ALL
OUT_SCALE
Low Priority
LO_PRI
29
ALL
0 to 15
Low Limit
LO_LIM
30
ALL
OUT_SCALE
31
ALL
0 to 15
32
ALL
OUT_SCALE
33
All bits: 0
UNACKNOWLEDGED
33.1
RW
ALARM_STATE
33.2
RO
TIME_STAMP
33.3
RO
SUBCODE
33.4
RO
VALUE
33.5
RO
High Alarm
HI_ALM
N/A
34
UNACKNOWLEDGED
34.1
RW
ALARM_STATE
34.2
RO
TIME_STAMP
34.3
RO
SUBCODE
34.4
RO
VALUE
34.5
RO
Low Alarm
LO_ALM
N/A
35
UNACKNOWLEDGED
35.1
RW
ALARM_STATE
35.2
RO
TIME_STAMP
35.3
RO
SUBCODE
35.4
RO
VALUE
35.5
RO
N/A
0
0
-Continued-
179
Instruction Manual
D103412X012
Index
Number
RO /
RW
Write Block
Mode
Initial
Value
Range
Description
36
UNACKNOWLEDGED
36.1
RW
ALARM_STATE
36.2
RO
TIME_STAMP
36.3
RO
SUBCODE
36.4
RO
VALUE
36.5
RO
N/A
0
0
Extended Parameter
Data Type: DS66
Discrete Output this is true (1) if any of the alarms
selected in ALM_SEL are active.
Output Discrete
OUT_D
37
OOS, MAN
Alarm Select
ALM_SEL
38
ALL
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
StdDev
STDDEV
39
RO
N/A
Positive float
Cap StdDev
CAP_STDDEV
40
RO
N/A
Positive float
OUT_STATE
All bits: 0
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 458. AI Function Block, View 1
Index Number
Index Number
180
Parameter
Parameter
ST_REV
ST_REV
5.1
MODE_BLK.TARGET_MODE
10
XD_SCALE
5.2
MODE_BLK.ACTUAL_MODE
11
OUT_SCALE
5.3
MODE_BLK.PERMITTED_MODE
12.1
GRANT_DENY.GRANT
5.4
MODE_BLK.NORMAL_MODE
12.2
GRANT_DENY.DENY
BLOCK_ERR
PV
OUT
19
FIELD_VAL
22.1
ALARM_SUM.CURRENT
22.2
ALARM_SUM.UNACKNOWLEDGED
22.3
ALARM_SUM.UNREPORTED
22.4
ALARM_SUM.DISABLED
Instruction Manual
D103412X012
August 2012
Index Number
Index Number
Parameter
Parameter
ST_REV
ST_REV
5.1
MODE_BLK.TARGET_MODE
STRATEGY
5.2
MODE_BLK.ACTUAL_MODE
ALERT_KEY
5.3
MODE_BLK.PERMITTED_MODE
13
IO_OPTS
5.4
MODE_BLK.NORMAL_MODE
14
STATUS_OPTS
BLOCK_ERR
15
CHANNEL
PV
16
L_TYPE
OUT
17
LOW_CUT
19
FIELD_VAL
18
PV_FTIME
22.1
ALARM_SUM.CURRENT
23
ACK_OPTION
22.2
ALARM_SUM.UNACKNOWLEDGED
24
ALARM_HYS
22.3
ALARM_SUM.UNREPORTED
25
HI_HI_PRI
22.4
ALARM_SUM.DISABLED
26
HI_HI_LIM
37
OUT_D
27
HI_PRI
38
ALM_SEL
28
HI_LIM
39
STDDEV
29
LO_PRI
40
CAP_STDDEV
30
LO_LIM
31
LO_LO_PRI
32
LO_LO_LIM
181
Instruction Manual
D103412X012
Quick Config
AI Channel
Linearization Type
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Common Config
Acknowledge Option
Alarm Hysteresis
Alert Key
High High Limit
High High Priority
High Limit
High Priority
I/O Options
Linearization Type
Low Low Limit
Low Low Priority
Low Limit
Low Priority
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Process Value Filter Time
Advanced Config
Low Cutoff
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Static Revision
Status Options
Strategy
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
I/O Reference
AI Channel
Connectors
Output: Status
Output: Value
182
Online
Block Error
Field Value: Status
Field Value: Value
Cascade Input: Status
Cascade Input: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output: Status
Output: Value
Process Value: Status
Process Value: Value
Status
Block Error
Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
High Alarm: Unacknowledged
High Alarm: Alarm State
High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Alarm output: Status
Alarm output: Value
Alarm Select
StdDev
Cap StdDev
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value: Status
Process Value: Value
Output: Status
Output: Value
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
AI Channel
Linearization Type
Low Cutoff
Process Value Filter TIme
Field Value: Status
Field Value: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
All (continued)
Alarm Hysteresis
High High Priority
High High Limit
High Priority
High Limit
Low Priority
Low Limit
Low Low Priority
Low Low Limit
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
High Alarm: Unacknowledged
High Alarm: Alarm State
High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Alarm output: Status
Alarm output: Value
Alarm select
StdDev
Cap StdDev
Instruction Manual
D103412X012
August 2012
OUT_1
MAI
OUT_2
OUT_3
OUT_5
OUT_6
OUT_7
FIELDBUSFBUS_31A
OUT_4
OUT_8
The MAI block supports mode control. In Automatic mode, the block's output parameters (OUT_1 to OUT_8 [8
through 15]) reflects the process variable (PV) values and status. In Manual mode, OUT may be set manually. The
Manual mode is reflected in the output status. Table 464 lists the MAI block parameters, and their units of measure,
description and index numbers.
Modes
The MAI Function Block supports three modes of operation as defined by the MODE_BLK [5] parameter:
Manual (Man)The block output (OUT_1 to OUT_8 [8 through 15]) may be set manually.
Automatic (Auto)OUT_1 to OUT_8 [8 through 15] reflects the analog input measurement or the simulated value
when the simulation is enabled.
Out of Service (OOS)The block is not processed. PV is not updated and the OUT status is set to Bad: Out of Service.
The BLOCK_ERR [6] parameter shows Out of Service. In this mode, you can make changes to all configurable
parameters. The target mode of a block may be restricted to one or more of the supported modes.
Status Handling
In Man mode, the OUT status constant limit is set to indicate that the value is a constant and the OUT status is Good.
183
Instruction Manual
D103412X012
OUT_X status will be Bad if the transducer detects a problem with sensor associated with the channel.
Application Information
The intended use is for applications where it is necessary to convey DVC6200f measurements from a function.
The configuration of the MAI function block and its associated output channels depends on the specific application.
CHANNEL [7]: Channel must always be set to 21.
The output parameters (OUT_1 to OUT_8 [8 through 15]) are set through the transducer block Instrument menu.
Each output has a channel assigned to it in MAI Channel Map (TB.MAI_CHANNEL_MAP [95]) in the transducer block.
For additional information, refer to table 464.
Block Errors
Table 462 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are inactive for the MAI block
and are given here only for your reference.
Table 462. BLOCK_ERR Conditions
Condition Number
Other
Block Configuration Error: the selected channel carries a measurement that is incompatible with the engineering units selected
in XD_SCALE, the L_TYPE parameter is not configured, or WRITE_CHECK = 0.
Simulate Active
Local Override
Input failure/process variable had Bad status The hardware is bad, or a bad status is being simulated
Output failure
Memory failure
10
11
Lost NV Data
12
13
14
Power Up - This condition exists after power up until the MAI function executes for the first time.
15
Troubleshooting
Refer to table 463 to troubleshoot any problem that you encounter.
Table 463. Troubleshooting
Symptom
Mode will not leave OOS
Possible Causes
Target mode is not set
Resource block
Schedule
Block alarms will not work
Features
Notification
184
Corrective Action
Set target mode to something other than OOS
The actual mode of the Resource block is OOS. See
Resource Block Diagnostics for corrective action.
Block is not scheduled and therefore cannot execute to go
to Target Mode. Typically, BLOCK_ERR [6] will show
PowerUp for all blocks that are not scheduled.
Schedule the block to execute.
FEATURES_SEL [18] in the resource block does not have
Alerts enabled. Enable the Alerts bit.
LIM_NOTIFY [32] in the resource block is not high
enough. Set equal to MAX_NOTIFY [31], also in the
resource block.
Instruction Manual
D103412X012
August 2012
Index
Number
Static Revision
ST_REV
Tag Description
TAG_DESC
RO /
RW
RO
Mode
N/A
Range
Initial Value
Description
Data Type: Unsigned16
The revision level of the static data
associated with the input selector block.
The revision value will be incremented
each time a static parameter value in the
block is changed.
0 to 65535
7 bit ASCII
spaces
Strategy
STRATEGY
0 to 65535
Alert Key
ALERT_KEY
1 to 255
Block Mode
MODE_BLK
TARGET
5.1
RW
ALL
ACTUAL
5.2
RO
ALL
PERMITTED
5.3
RW
NORMAL
5.4
RW
Block Error
BLOCK_ERR
RO
OOS
ALL
OOS+MAN+AUTO
ALL
AUTO
OOS
AUTO
1: Block Configuration
Error
7: Input Failure/ Bad PV
Status
14: Powerup
15: OutofService
MAI Channel
CHANNEL
21 only
0 = undefined
1=FINAL_VALUE
2=TRAVEL_TARGET
3=FINAL_POSITION_VALUE
4=TRAVEL
5=SUPPLY_PRESS
6=ACT_PRESS_A
7=ACT_PRESS_B
8=ACT_PRESS_DIFF
9=DRIVE_SIGNAL
10=TRAVEL_DEVIATION
11=TEMPERATURE
12=CYCLE_COUNT
13=TRAVEL_ACCUM
-Continued-
185
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Initial Value
Description
Output 1
OUT_1
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.FINAL_VALUE
Output 2
OUT_2
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.TRAVEL_TARGET
Output 3
OUT_3
10
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.FINAL_POSITION_VA
LUE
Output 4
OUT_4
11
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.TRAVEL
Output 5
OUT_5
12
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.SUPPLY_PRESS
Output 6
OUT_6
13
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.ACT_PRESS_A
Output 7
OUT_7
14
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.ACT_PRESS_B
Output 8
OUT_8
15
OOS
MAN
Channel assigned by
TB.MAI_CHANNEL_MAP
TB.ACT_PRESS_DIFF
Update Event
UPDATE_EVT
16
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
0=Undefined
1=Update reported
2=Updated not reported
0=Undefined
UNACKNOWLEDGED
RW
UPDATE_STATE
16.2
RO
N/A
TIME_STAMP
16.3
RO
N/A
STATIC_REVISION
16.4
RO
N/A
RELATIVE_INDEX
16.5
RO
N/A
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
186
16.1
17
17.1
RW
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
ALARM_STATE
17.2
RO
TIME_STAMP
17.3
RO
SUBCODE
17.4
RO
VALUE
17.5
RO
Instruction Manual
D103412X012
August 2012
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 465. MAI Function Block, View 1
Index Number
Index Number
Parameter
ST_REV
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
BLOCK_ERR
OUT_1
OUT_1
OUT_2
OUT_2
10
OUT_3
10
OUT_3
11
OUT_4
11
OUT_4
12
OUT_5
12
OUT_5
13
OUT_6
13
OUT_6
14
OUT_7
14
OUT_7
15
OUT_8
15
OUT_8
Parameter
ST_REV
Parameter
ST_REV
STRATEGY
ALERT_KEY
CHANNEL
187
Instruction Manual
D103412X012
Quick Config
MAI Channel
Common Config
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Advanced Config
Static Revision
Strategy
I/O Reference
MAI Channel
Connectors
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 3: Status
Output 3: Value
Output 4: Status
Output 4: Value
Output 5: Status
Output 5: Value
Output 6: Status
Output 6: Value
Output 7: Status
Output 7: Value
Output 8: Status
Output 8: Value
188
Online
Block Error
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 3: Status
Output 3: Value
Output 4: Status
Output 4: Value
Output 5: Status
Output 5: Value
Output 6: Status
Output 6: Value
Output 7: Status
Output 7: Value
Output 8: Status
Output 8: Value
Status
Block Error
Other
Tag Description
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
MAI Channel
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 3: Status
Output 3: Value
Output 4: Status
Output 4: Value
Output 5: Status
Output 5: Value
Output 6: Status
Output 6: Value
Output 7: Status
Output 7: Value
Output 8: Status
Output 8: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Instruction Manual
D103412X012
August 2012
BKCAL_OUT_D
CAS_IN_D
DO
OUT_D
READBACK_D
CASIND= The remote set point value from another function block.
BKCALOUTD = The value and status required by the
BKCALIND input of another block for output tracking.
OUT_D = The block output and status.
READBACK_D = Actual valve position
The DO block supports mode control and simulation. In operation, the DO function block determines its set point and
sets the output. The transducer block provides a readback signal of actual position from the instrument. Figure 427
illustrates the primary inputs and outputs of the DO function block, figure 428 illustrates the internal components of
the DO function block. Table 472 lists definitions for the function block parameters.
189
Instruction Manual
D103412X012
RCAS_OUT_D
RCAS_IN_D
BKCAL_OUT_D
PV_D
SP_D
CONVERT AND
STATUS
CALCULATION
CAS_IN_D
IO_OPTS
OUT_D
READBACK_D
MODE
SIMULATE_D
SHED MODE
CHANNEL
TRANSDUCER
BLOCK FEEDBACK
TRANSDUCER
BLOCK
When setting up the DO block, CHANNEL [18] must be set to 22, and SHED_OPT [23] must be nonzero.
Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain out of service and the block cannot be scheduled if the block has not
been licensed. Contact your Emerson Process Management sales office to upgrade product licensing.
Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain in IMAN and the block Readback status will be Bad - Not Connected if
the Output Block Selection is set incorrectly. From the transducer block method Outblock Selection, select the desired output
block, see page 69.
Modes
The DO block supports the following modes:
Manual (Man)The block output OUT_D [9] value may be entered manually.
Automatic (Auto)The block algorithm uses the local set point SP_D [8]value to determine OUT_D [9].
190
Instruction Manual
D103412X012
August 2012
Cascade (Cas)The block uses a set point supplied by another function block.
Note
The transducer block must be in Auto for the mode to go to AUTO, CAS or MAN.
Mode Handling
Shed Options RCAS Mode Only
Shed from or climb to a remote mode is determined by the parameter SHED_OPT [23]. A block climbs and sheds
through the same path. For example, if SHED_OPT [23] specifies that a block should shed to Auto, then, if the block
target mode is set to RCas, the block goes through Auto on the way to RCas. You can configure the shed option as
follows:
191
Instruction Manual
D103412X012
AutoOn failure of a remote cascade connection, the block sets the target mode to Auto, if permitted.
ManOn failure of remote cascade connection, the block sets the target mode to Man, if permitted.
The user may configure SHED_OPT [23] so that it calls for a target mode that is not permitted. When doing this, the
mode logic uses the following rules as applied by the remote logic:
Shed logic never results in a nonpermitted target mode.
Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted.
Block Initialization
The Fieldbus Foundation specification requires that certain parameters have initial values of uninitialized in function
blocks. In addition to setting the Resource block mode to AUTO, the control system or the user must change those
parameters from their uninitialized value to a valid value in order for the function block to move from the Out of
Service mode. For the DO function block, the parameters that must be initialized are:
SHED_OPT [23] (see page 191 for valid values)
CHANNEL [18]
Status Handling
Under normal operating conditions, the status of OUT_D [9] is Good NonCascade, and the status of BKCAL_OUT_D
[21] is Good:Cascade. If the output hardware fails, the status of BKCAL_OUT_D [21] is set to Bad:Device Fail, and the
BLOCK_ERR [6] shows Output Failure. If the hardware used for output feedback fails, the status of READBACK_D [16]
and PV_D [7] is set to Bad:DeviceFail, and the BLOCK_ERR [6] shows Process Variable has Bad Status. If the transducer
block mode is Out of Service, the status of READBACK_D [16] and PV_D [7] is set to Bad:Out of Service.
I/O Selection
To select the I/O associated with the discrete output, configure the value of the CHANNEL [18] parameter. Table 469
lists the valid Channel selections for the DO block.
Table 469. Channel Selections for the Discrete Output Function Block
Selection
Description
22
SETPOINT_D
32
Uninitialized
192
Instruction Manual
D103412X012
August 2012
Closed
Open
Closed
5%
Closed
10
10%
Closed
15
15%
Closed
20
20%
Closed
25
25%
Closed
30
30%
Closed
35
35%
Closed
40
40%
Closed
45
45%
Closed
50
50%
Closed
55
55%
Closed
60
60%
Closed
65
65%
Closed
70
70%
Closed
75
75%
Closed
80
80%
Closed
85
85%
Closed
90
90%
Closed
95
95%
Closed
100
Open
Closed
To further customize the output, configure the following supported I/O options: SP tracks PV in Man,
SP tracks PV in LO, SP Track retained target in Man or LO, Fault State to Value, Use Fault State value on restart, Target
to Man if Fault State activated, and US PV for BKCAL_OUT.
Note
You can configure the supported I/O options in Out of Service mode only.
The SP_PV Track in Man option permits the set point to track the process variable when the block is in Manual mode.
With this option enabled, the set point (SP_D [8]) becomes a copy of the process variable
(PV_D [7]), and a manuallyentered SP_D [8] value is overwritten on the block's next execution cycle. This option can
prevent a state change when transitioning from Manual to Automatic mode. You can disable this option in Manual or
Out of Service mode only.
The Invert option inverts the set point at SP_D [8] before it is stored in OUT_D [9]. With this option enabled, OUT_D
[9] becomes an inverted copy of SP_D [8] where nonzero values of SP_D [8] are considered a logic 1. With this option
disabled, OUT_D [9] is a direct copy of SP_D [8]. The readback value is processed through the Invert option to become
PV_D [7]. The Use PV for BKCAL_OUT option specifies that BKCAL _OUT equal the value of the process variable (PV_D
[7]) instead of the set point (SP_D [8]). If you do not enable this option, BKCAL_OUT will equal SP_D [8].
193
Instruction Manual
D103412X012
Block Errors
Table 471 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the DO
block and are provided only for your reference.
Table 471. BLOCK_ERR Conditions
Condition Number
Other (N/A)
Simulate active Simulation is enabled and the block is using a simulated value in its execution.
Device Fault State Set DO block in fault state after FSTATE_TIME because of Bad status or IFS substatus on CAS_IN_D or Resource
block commanded fault state.
Device Needs Maintenance Soon Indicates a Maintenance PlantWeb Alert condition is active if Block Error Reporting is enabled. See
page 86.
Input failure/process variable has Bad status PV has bad status and Feature Select in the Resource block has the Out Readback bit set
or the transducer block mode is Out of Service.
Output failure PV has bad status or the transducer block mode is Out of Service.
10
11
12
13
Device Needs Maintenance Now Indicates Failed PlantWeb Alert condition is active if Block Error Reporting is enabled. See page 86.
14
Power Up This condition exists after power up until actual mode is not Out of Service.
15
Simulation
To support testing of the control strategy, you can enable the SIMULATE_D [17] parameter. Normally, the valve
position value and status used for READBACK_D [16] in the DO block reflect actual process values to the nearest 5%, as
provided by the transducer block. When the SIMULATE_D [17] parameter is enabled, value and status used for
READBACK_D [16] is supplied by the user manually. To enable simulation in the DO function block, the simulate
jumper must be installed. Refer to page 36 of the Installation section for information on the installation of this jumper.
194
Instruction Manual
D103412X012
August 2012
Note
When simulate is active, the output block no longer writes values to the transducer block. If the Output Blk Timeout period is
exceeded, the transducer block may move the valve to the Zero Power Condition depending on the configuration of the Output
Block Timeout Alert.
Index
Number
RO /
RW
Mode
Range
Initial Value
Description
Static Revision
ST_REV
RO
N/A
0 to 65535
Tag Description
TAG_DESC
RW
ALL
7 bit ASCII
Spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
RW
ALL
1 to 255
-Continued-
195
Instruction Manual
D103412X012
Index
Number
RO /
RW
Mode
Range
Initial Value
Description
OOS
MAN
AUTO
AUTOCAS, AUTORCAS
OOS until
block is
configured,
then last valid
target
OOS+MAN+AUTO+
CAS+RCAS
TARGET
5.1
RW
ALL
ACTUAL
5.2
RO
ALL
OOS
OOS+MAN+A
UTO+CAS
+RCAS
PERMITTED
5.3
RW
ALL
NORMAL
5.4
RW
ALL
AUTO+CAS
Block Error
BLOCK_ERR
RO
N/A
1: Block Configuration
Error
3: Simulate Active
4: Local Override
5: Device Fault State Set
7: Input Failure / Bad PV
Status
8: Output Failure
14: Powerup
15: OutofService
RO
N/A
Setpoint Discrete
SP_D
OOS
MAN
AUTO
PV_STATE
Output Discrete
OUT_D
MAN
OUT_STATE
Simulate Discrete
SIMULATE_D
10
Dynamic
Dynamic
SIMULATE_STATUS
10.1
ALL
SIMULATE_VALUE
10.2
ALL
TRANSDUCER_STATUS
10.3
RO
TRANSDUCER_VALUE
10.4
RO
ENABLE/DISABLE
0
0
0=Not initialized
1=Simulation Disabled
2=Simulation Active
10.5
ALL
11
ALL
Transducer State
XD_STATE
12
ALL
Grant Deny
GRANT_DENY
13
All bits: 0
GRANT
13.1
N/A
DENY
13.2
N/A
0: Program
1: Tune
2: Alarm
3: Local
-Continued-
196
All bits: 0
Instruction Manual
D103412X012
August 2012
I/O Options
IO_OPTS
Index
Number
RO /
RW
14
Status Options
STATUS_OPTS
15
Readback Discrete
READBACK_D
16
17
Mode
Range
OOS
Valid Bits
0: Invert
1: SP tracks PV in Man
3: SP tracks PV in LO
4: SP Track retained
target in Man or LO
6: Fault State to value
0: freeze
1: go to Fault State
value
7: Use Fault State value
on restart
8: Target to Man if Fault
State activated
9: Use PV for
BKCAL_OUT
0: SP
1: PV
OOS
RO
4: Propagate Failure
Backward
N/A
ALL
All bits: 0
Dynamic
Value
OOS
0=undefined
22=Setpoint (D)
19
ALL
Positive
20
21
22
All bits: 0
BAD:
NC:
const
18
Description
Status
DO Channel
CHANNEL
RO
Initial Value
22=
Setpoint (D)
ALL
N/A
Dynamic
ALL
BAD:
NoCom:
NoVal:
const
Status
Value
-Continued-
197
Instruction Manual
D103412X012
Shed Options
SHED_OPT
Index
Number
RO /
RW
23
24
Update Event
UPDATE_EVT
25
Mode
Range
ALL
0=Uninitialized
1=Normal Shed, Normal
Return
2=Normal Shed, No
Return
3=Shed to Auto, normal
return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
RO
N/A
Initial Value
Description
Dynamic
UNACKNOWLEDGED
25.1
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
UPDATE_STATE
25.2
RO
N/A
0=Undefined
1=Update reported
2=Update not reported
0=Undefined
TIME_STAMP
25.3
RO
N/A
STATIC_REVISION
25.4
RO
N/A
RELATIVE_INDEX
25.5
RO
N/A
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
26
26.1
ALARM_STATE
26.2
RO
N/A
TIME_STAMP
26.3
RO
N/A
SUBCODE
26.4
RO
N/A
VALUE
26.5
RO
N/A
Extended Blocks
Setpoint Rate Up
SP_RATE_UP
27
>= 0
28
> = 0
198
Instruction Manual
D103412X012
August 2012
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 473. DO Function Block, View 1
Index Number
Index Number
Parameter
ST_REV
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
BLOCK_ERR
PV_D
PV_D
SP_D
SP_D
OUT_D
OUT_D
16
READBACK_D
16
READBACK_D
17
CAS_IN_D
17
CAS_IN
21
BKCAL_OUT_D
22
RCAS_IN_D
24
RCAS_OUT_D
Parameter
ST_REV
11
PV_STATE
12
XD_STATE
13.1
GRANT_DENY.GRANT
13.2
GRANT_DENY.DENY
Parameter
ST_REV
STRATEGY
ALERT_KEY
14
IO_OPTS
15
STATUS_OPTS
18
CHANNEL
19
FSTATE_TIME
20
FSTATE_VAL_D
24
SHED_OPT
27
SP_RATE_UP
28
SP_RATE_DN
199
Instruction Manual
D103412X012
200
Online
Back Calculation Output Discrete: Status
Back Calculation Output Discrete: Value
Block Error
Cascade Input Discrete: Status
Cascade Input Discrete: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Discrete: Status
Output Discrete: Value
Process Value Discrete: Status
Process Value Discrete: Value
Remote Cascade Input Discrete: Status
Remote Cascade Input Discrete: Value
Remote Cascade Output Discrete: Status
Remote Cascade Output Discrete: Value
Readback Discrete: Status
Readback Discrete: Value
Setpoint Discrete: Status
Setpoint Discrete: Value
Status
Block Error
Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Setpoint Rate Up
Setpoint Rate Down
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value Discrete: Status
Process Value Discrete: Value
Setpoint Discrete: Status
Setpoint Discrete: Value
Output Discrete: Status
Output Discrete: Value
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Process Value State
Transducer State
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
Readback Discrete: Status
Readback Discrete: Value
Cascade Input Discrete: Status
Cascade Input Discrete: Value
DO Channel
Fault State Time
Fault State Value
Back Calculation Output Discrete: Status
Back Calculation Output Discrete: Value
Remote Cascade Input Discrete: Status
Remote Cascade Input Discrete: Value
Shed Options
Remote Cascade Output Discrete: Status
Remote Cascade Output Discrete: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Setpoint Rate Up
Setpoint Rate Down
Instruction Manual
D103412X012
August 2012
DI
TRANSDUCER
BLOCK
OUT_D
Normally, the block is used in Automatic mode so that the process variable (PV_D [7]) is copied to the output (OUT_D
[8]). You can change the mode to Manual to disconnect the field signal and substitute a manuallyentered value for
the output. In this case, PV_D [7] continues to show the value that will become the OUT_D [8] when the mode is
changed to Automatic.
To support testing, you can enable simulation, which allows the measurement value to be supplied manually through
the SIMULATE_D [9] parameter. Figure 430 illustrates the internal components of the DI function block, and table
481 lists the definitions of the block parameters.
Figure 430. Discrete Input Function Block Schematic
Discrete Signal
FIELD_VAL_D
Alarm Detection
OUT_D
Invert Option
SIMULATE
PV_D
MODE
201
Instruction Manual
August 2012
D103412X012
Modes
The Discrete Input function block supports the following modes:
Manual (Man)The block output (OUT_D [8]) is disconnected from the field and set manually.
Automatic (Auto)The block algorithm determines output.
Out of Service (OOS)The block is not processed. The OUT_D [8] status is set to Bad: Out of Service. The
BLOCK_ERR [6] parameter shows Out of Service.
Block Initialization
The Fieldbus Foundation specification requires that certain parameters in the function blocks have initial values of
uninitialized. In addition to setting the Resource block mode to AUTO, the control system or the user must change
those parameters from their uninitialized value to a valid value in order for the function block to move from the Out of
Service mode. For the DI function block, the CHANNEL [15] parameter must be initialized.
Status Handling
Under normal conditions, a Good: NonCascade status is passed through to OUT_D [8]. The block also supports the
Status Action On Failure and BLOCK_ERR [6] indications.
When SIMULATE_D [9] is enabled, FIELD_VAL_D [7], PV_D [7], and OUT_D [8] change to the simulated status. When
the block is set to Manual mode, OUT_D [7] is set to Good: Non-cascade, Constant status.
I/O Selection
To select the I/O associated with the discrete measurement, configure the value of the CHANNEL [15] parameter.
In the digital valve controller, the four classes of channels are
Valve travel
Open/Closed limit switch
Variable limit switch based on transducer block travel alarm settings.
Proximity position detection based on transducer block travel alarm settings.
The CHANNEL [15] parameter for each of the four DI blocks available in the digital valve controller may be set
independently to achieve the desired position detection. The DI block CHANNEL [15] definitions are listed in table
477. Refer to the following descriptions for details of the operation of these channels.
Valve Travel
Channel 23 provides valve travel.
0 = Closed, 1 = 100% open, 5 = 5% open, 10 = 10% open, 15 = 15% open, etc.
202
Instruction Manual
D103412X012
August 2012
Table 477. Channel Selection for the Discrete Input Function Block
Transducer Block Parameter(1)
Selection
Bit Number(2)
23
TRAVEL_D
24
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
33
0: Travel Open
N/A
25
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
1: Travel Closed
26
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
2: Travel Limit Lo Lo
27
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
4: Travel Limit Lo
28
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
3: Travel Limit Hi
29
INST_ALERTS_ACTIVE:TRAVEL_ACTIVE
74.4
1: Travel Limit Hi Hi
30
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
5: Proximity Lo Lo
31
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
4: Proximity Lo
32
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
3: Proximity Hi
33
INST_ALERTS_ACTIVE:PROX_ACTIVE
74.5
2: Proximity Hi Hi
Parameter Function
203
Instruction Manual
D103412X012
the detected position. Figure 431 illustrates the operation of the proximity detection function. Travel Alert Point
refers to Travel Lo Alert Point, Travel Hi Alert Point, Travel Lo Lo Alert Point, and Travel Hi Hi Alert Point in table 479.
Travel Alert Deadband refers to Travel Lo Alert Deadband, Travel Hi Alert Deadband, Travel Lo Lo Alert Deadband, and
Travel Hi Hi Alert Deadband in table 479.
Figure 431. Discrete Input Proximity Detection Function
DISCRETE INPUT
CLEARED
DEADZONE, 1% OF TRAVEL
Valve Position
Parameter Function
Note
Invert is the only I/O option that the DI block supports. You can set the I/O option only when the block mode is Out of Service.
204
Instruction Manual
D103412X012
August 2012
Alarm Detection
To select the state that initiates an input alarm, and to set discrete alarm substatus in the output, configure the
DISC_LIM [23] parameter. You can enter any value between 0 and 255. A value of 255 disables the alarm. When
OUT_D [8] matches the DISC_LIM [23] state, the discrete value of an alarm is set.
Block Errors
Table 480 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the DI
block and are provided only for your reference.
Table 480. BLOCK_ERR Conditions
Condition Number
Other (N/A)
Input failure/process variable has Bad statusThe hardware is bad or the transducer block mode is Out of Service
10
11
12
13
14
Power UpSet after powerup until actual mode is not Out of Service
15
Out of ServiceThe actual mode is Out of Service (OOS). The block is not being processed.
Action on Failure
In case of hardware failure, FIELD_VAL_D [17], PV_D [7], and OUT_D [8] change to a Bad status and the BLOCK_ ERR
[6] parameter shows Process Variable has Bad Status. If the transducer block mode is Out of Service, the status of
FIELD_VAL_D [17], PV_D [7], and OUT_D [8] is set to Bad:Out of Service.
Simulation
To support testing of the control strategy, you can enable the SIMULATE_D [9] parameter. Normally the measurement
value and status used for FIELD_VAL_D [17] in the DI block reflect actual process values as provided by the transducer
block. When the SIMULATE_D [9] parameter is enabled, value and status used for FIELD_VAL_D [17] is supplied by the
user manually. To enable simulation in the DI function block, the simulate jumper must be installed. For information
on the installation of this jumper, see the Installation section.
The SIMULATE_D [9] parameter has three components:
Simulate_D enable/disable determines whether the function block will use the actual process value and status, or
Simulate Value and Simulate Status.
Transducer Value and Status reflect the process values provided by the transducer block.
Simulate Value and Status may be entered by the user when enable/disable is set to enabled.
205
Instruction Manual
D103412X012
To use simulate, first install the simulate jumper in the terminal box, then set Simulate_D enable/disable to enabled,
then enter the desired values for Simulate Value and Status.
When SIMULATE_D [9] is enabled, the Simulate Active bit of the BLOCK_ERR [6] parameter is set (refer to the Block
Errors description). When the simulate jumper is installed, the Simulate Jumper bit of the transducer block parameter
SELFTEST_STATUS [78] is set.
Application Information
Figure 432 compares the operation of a standard discrete input to a proximity discrete input. With the standard
discrete input, the discrete input changes state when the valve position passes a configurable trip point. This can be
used to indicate if the valve position is above or below the trip point.
Figure 432. Proximity Discrete Input Compared to a Standard Discrete Input
STANDARD DISCRETE INPUT
DISCRETE
INPUT VALUE
Configurable
Band
DISCRETE
INPUT VALUE
1
0
With the proximity discrete input a configurable band can be established about a central point. Whenever the valve
position enters this configurable band, the discrete input changes state. A proximity discrete input is useful for
applications which require knowing the location of the valve when the valve is not near 0% or 100%.
206
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Block
Mode
Range
Initial Value
Description
Data Type: Unsigned16
The revision level of the static data associated
with the function block. The revision value will
be incremented each time a static parameter
value in the block is changed.
Static Revision
ST_REV
RO
N/A
0 to 65535
Tag Description
TAG_DESC
RW
ALL
7 bit ASCII
Spaces
Strategy
STRATEGY
RW
ALL
0 to 65535
Alert Key
ALERT_KEY
RW
ALL
1 to 255
Block Mode
MODE_BLK
5
OOS
MAN
AUTO
OOS until
block is
configured,
then last valid
target
OOS+MAN+AUTO
TARGET
5.1
RW
ALL
ACTUAL
5.2
RO
ALL
OOS
OOS+MAN+A
UTO
PERMITTED
5.3
RW
ALL
NORMAL
5.4
RO
ALL
Block Error
BLOCK_ERR
Output Discrete
OUT_D
Simulate Discrete
SIMULATE_D
RO
RO
AUTO
N/A
Defined Bits
1: Block Configuration
Error
3: Simulate Active
7: Input Failure / Bad PV
Status
14: Powerup
15: OutofService
N/A
OOS
MAN
OUT_STATE
Dynamic
Dynamic
SIMULATE_STATUS
9.1
ALL
SIMULATE_VALUE
9.2
ALL
TRANSDUCER_STATUS
9.3
RO
ALL
TRANSDUCER_VALUE
9.4
RO
ALL
ENABLE/DISABLE
0
0=Not initialized
1=Simulation Disabled
2=Simulation Active
9.5
1=Simulation
Disabled
Transducer State
XD_STATE
10
ALL
Output State
OUT_STATE
11
ALL
-Continued-
207
Instruction Manual
D103412X012
Index
Number
RO /
RW
Block
Mode
12.1
ALL
DENY
12.2
ALL
Status Options
STATUS_OPTS
DI Channel
CHANNEL
13
14
15
16
17
Update Event
UPDATE_EVT
18
UNACKNOWLEDGED
18.1
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
All bits:0
OOS
3=Propagate Failure
Forward
8=Uncertain in MAN mode
All bits:0
OOS
0=undefined
23=Valve Position or
Pressure (Discrete)
24= PV > 97%
25= PV < 3%
26=PV Below LO LO limit
27=PV Below LO limit
28=PV Above HI limit
29=PV Above HI HI limit
30=PV Within Proximity of
LO LO
31=PV Within Proximity of
LO
32=PV within Proximity of
HI
33=PV within Proximity of
HI HI
0=Undefined
OOS
0: Invert
ALL
Positive
RO
RW
All bits:0
Description
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
0=Undefined
1=Update Reported
2=Updated not reported
0=Undefined
UPDATE_STATE
18.2
RO
N/A
TIME_STAMP
18.3
RO
N/A
STATIC_REVISION
18.4
RO
N/A
RELATIVE_INDEX
18.5
RO
N/A
0
-Continued-
208
Initial Value
12
GRANT
I/O Options
IO_OPTS
Range
Instruction Manual
D103412X012
August 2012
Index
Number
RO /
RW
Block
Mode
19
19.1
Initial Value
Description
Dynamic
RW
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
ALARM_STATE
19.2
RO
N/A
TIME_STAMP
19.3
RO
N/A
SUBCODE
19.4
RO
N/A
VALUE
19.5
RO
Alarm Summary
ALARM_SUM
Range
0: Discrete alarm
7: Block Alarm
20
CURRENT
20.1
RO
All bits: 0
UNACKNOWLEDGED
20.2
RO
All bits: 0
UNREPORTED
20.3
RO
All bits: 0
DISABLED
20.4
RW
All bits: 0
Acknowledge Option
ACK_OPTION
21
ALL
0: Discrete
1: Block Alarm
Discrete Priority
DISC_PRI
22
ALL
0 to 15
Discrete Limit
DISC_LIM
23
ALL
PV_STATE
Discrete Alarm
DISC_ALM
24
N/A
0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported
UNACKNOWLEDGED
24.1
RW
ALARM_STATE
24.2
RO
N/A
TIME_STAMP
24.3
RO
N/A
SUBCODE
24.4
RO
N/A
VALUE
24.5
RO
N/A
All bits: 0
209
Instruction Manual
D103412X012
View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 482. DI Function Block, View 1
Index Number
Index Number
Parameter
ST_REV
5.1
MODE_BLK.TARGET_MODE
5.1
MODE_BLK.TARGET_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.2
MODE_BLK.ACTUAL_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.3
MODE_BLK.PERMITTED_MODE
5.4
MODE_BLK.NORMAL_MODE
5.4
MODE_BLK.NORMAL_MODE
BLOCK_ERR
BLOCK_ERR
PV_D
PV_D
OUT_D
OUT_D
17
FIELD_VAL_D
17
FIELD_VAL_D
20.1
ALARM_SUM.CURRENT
20.1
ALARM_SUM.CURRENT
20.2
ALARM_SUM.UNACKNOWLEDGED
20.2
ALARM_SUM.UNACKNOWLEDGED
20.3
ALARM_SUM.UNREPORTED
20.3
ALARM_SUM.UNREPORTED
20.4
ALARM_SUM.DISABLED
20.4
ALARM_SUM.DISABLED
210
Parameter
ST_REV
Parameter
ST_REV
10
XD_STATE
11
OUT_STATE
12.1
GRANT_DENY.GRANT
12.2
GRANT_DENY.DENY
Parameter
ST_REV
STRATEGY
ALERT_KEY
13
IO_OPTS
14
STATUS_OPTS
15
CHANNEL
16
PV_FTIME
21
ACK_OPTION
22
DISC_PRI
23
DISC_LIM
Instruction Manual
D103412X012
August 2012
Common Config
Alert Key
Discrete Limit
I/O Options
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Process Value Filter Time
Online
Block Error
Field Value Discrete: Status
Field Value Discrete: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Discrete: Status
Output Discrete: Value
Process Value Discrete: Status
Process Value Discrete: Value
Status
Block Error
Advanced Config
Other
DI Channel
Output State
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Static Revision
Status Options
Transducer State
Connectors
Output Discrete: Status
Output Discrete: Value
Strategy
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Discrete Alarm: Unacknowledged
Discrete Alarm: Alarm State
Discrete Alarm: Time Stamp
Discrete Alarm: Subcode
Discrete Alarm: Discrete Value
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value Discrete: Status
Process Value Discrete: Value
Output Discrete: Status
Output Discrete: Value
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Transducer State
Output State
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
DI Channel
Process Value Filter Time
Field Value Discrete: Status
Field Value Discrete: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Discrete Priority
Discrete Limit
Discrete Alarm: Unacknowledged
Discrete Alarm: Alarm State
Discrete Alarm: Time Stamp
Discrete Alarm: Subcode
Discrete Alarm: Discrete Value
211
212
Instruction Manual
D103412X012
Instruction Manual
Calibration
D103412X012
August 2012
Calibration
Field Communicator
Auto Calibration This procedure automatically calibrates the travel. The calibration procedure uses the valve and
actuator stops as the 0% and 100% calibration points. See page 214.
Manual Calibration This procedure permits manual calibration of the travel. This calibration procedure allows you
to determine the 0% and 100% calibration points. See page 214.
Relay This procedure permits adjustment of the pneumatic relay. See page 215.
Supply Pressure This procedure permits calibrating the supply pressure sensor. Normally the sensor is calibrated at
the factory and should not need calibration. See page 216.
Pressure A This procedure permits calibrating the pressure A sensor. Normally the sensor is calibrated at the
factory and should not need calibration. See page 217.
Pressure B This procedure permits calibrating the pressure B sensor. Normally the sensor is calibrated at the
factory and should not need calibration. See page 217.
Note
The Instrument Mode must be Out Of Service and the Protection set to None before the instrument can be calibrated.
If you are operating in burst mode, we recommend that you disable burst before continuing with calibration. Once calibration is
complete, burst mode may then be turned back on.
WARNING
During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.
213
Instruction Manual
Calibration
August 2012
D103412X012
If a doubleacting relay is used, you will be prompted to run the relay adjustment when auto or manual calibration is
selected. Select Yes to adjust the relay, select No to proceed with calibration. For additional information, refer to Relay
Adjustment in this section.
Note
Relay Adjustment is only available for the doubleacting relay (Relay A).
Auto Calibration
Field Communicator
Follow the prompts on the Field Communicator display to automatically calibrate travel.
1. The auto calibration procedure is automatic. It is completed when the Calibration menu appears.
During calibration, the instrument seeks the high and low end points and the minor loop feedback (MLFB) and output
bias. By searching for the end points, the instrument establishes the limits of physical travel, i.e. the actual travel 0 and
100% positions. This also determines how far the relay beam swings to calibrate the sensitivity of the MLFB sensor.
2. Place the instrument In Service and verify that the travel properly tracks the current source.
Manual Calibration
Field Communicator
Note
0% Travel = Valve Closed ; 100% Travel = Valve Open
1. From the adjustment menu, select the direction and size of change required to set the travel at 0% (move the valve
to close). Selecting large, medium, and small adjustments causes changes of approximately 10.0%, 1.0%, and 0.1%,
respectively, to the travel feedback movement. Selecting Next will implement the adjustment.
If another adjustment is required, repeat step 1. Otherwise, select Done and go to step 2.
2. From the adjustment menu, select the direction and size of change required to set the travel to 100% (move the
valve to open).
If another adjustment is required, repeat step 2. Otherwise, select Done and go to step 3.
3. Enter the name of the person performing the calibration procedure.
4. Enter the location of the calibration procedure.
5. Enter the date of the calibration procedure.
6. Place the Transducer Block Mode in Manual and verify that the travel properly tracks the setpoint changes.
214
Instruction Manual
Calibration
D103412X012
August 2012
Relay
Field Communicator
Follow the prompts on the Field Communicator display to check relay adjustment. Replace the digital valve controller
cover when finished.
Note
Relay B and C are not useradjustable.
DoubleActing Relay
The doubleacting relay is designated by Relay A on a label affixed to the relay itself. For doubleacting actuators, the
valve must be near midtravel to properly adjust the relay. The Field Communicator will automatically position the
valve when Relay is selected.
CAUTION
Care should be taken during relay adjustment as the adjustment disc may disengage if rotated too far.
Rotate the adjustment disc, shown in figure 51, until the output pressure displayed on the Field Communicator is
between 50 and 70% of supply pressure. This adjustment is very sensitive. Be sure to allow the pressure reading to
stabilize before making another adjustment (stabilization may take up to 30 seconds or more for large actuators).
Figure 51. Relay A Adjustment (Shroud Removed for Clarity)
ADJUSTMENT DISC
215
Instruction Manual
Calibration
August 2012
D103412X012
If the low bleed relay option has been ordered stabilization may take approximately two minutes longer than the
standard relay.
Relay A may also be adjusted for use in singleacting direct applications. Rotate the adjustment disc as shown in figure
51 for singleacting direct operation.
SingleActing Relays
WARNING
For instrument level PD only:
If the unused port is monitoring pressure, ensure that the pressure source conforms to ISA Standard 7.0.01 and does not
exceed the pressure supplied to the instrument.
Failure to do so could result in personal injury or property damage caused by loss of process control.
Note
The pressure sensor is calibrated at the factory and should not require calibration.
To calibrate the supply pressure sensor, connect an external reference gauge to the output side of the supply
regulator. The gauge should be capable of measuring maximum instrument supply pressure. Select Follow the
prompts on the Field Communicator display to calibrate the instrument's supply pressure sensor.
1. Select a) Zero Only, or b) Zero and Span (gauge required).
a. If Zero Only calibration is selected, adjust the supply pressure regulator to remove supply pressure from the
instrument. Press OK. Once calibration is complete, go to step 5.
b. If Zero and Span calibration is selected, adjust the supply pressure regulator to remove supply pressure from the
instrument. Press OK. Adjust the supply regulator to the maximum instrument supply pressure. Press OK.
Proceed with step 2.
216
Instruction Manual
D103412X012
Calibration
August 2012
Pressure A or B Sensor
Field Communicator
Field Communicator
To calibrate the output pressure sensor, connect an external reference gauge to the output being calibrated. The
gauge should be capable of measuring maximum instrument supply pressure. Select . Follow the prompts on the Field
Communicator display to calibrate the instrument's output pressure sensor.
1. Adjust the supply pressure regulator to the maximum instrument supply pressure. Press OK.
2. The instrument reduces the output pressure to 0. The following message appears.
Use the Increase and
Decrease selections
until the displayed
pressure matches the
output x pressure.
Press OK when you have read the message.
3. The value of the output pressure appears on the display. Press OK to display the adjustment menu.
4. From the adjustment menu, select the direction and size of adjustment to the displayed value. Selecting large,
medium, and small adjustments causes changes of approximately 3.0 psi/0.207 bar/20.7 kPa, 0.30 psi/0.0207
bar/2.07 kPa, and 0.03 psi/0.00207 bar/0.207 kPa, respectively. If the displayed value does not match the output
pressure, press OK, then repeat this step (step 4) to further adjust the displayed value. When the displayed value
matches the output pressure, select Done and go to step 5.
217
Instruction Manual
Calibration
August 2012
D103412X012
5. The instrument sets the output pressure to full supply. The following message appears.
Use the Increase and
Decrease selections
until the displayed
pressure matches the
output x pressure.
Press OK when you have read the message.
6. The value of the output pressure appears on the display. Press OK to display the adjustment menu.
7. From the adjustment menu, select the direction and size of adjustment to the displayed value. If the displayed value
does not match the output pressure, press OK, then repeat this step (step 7) to further adjust the displayed value.
When the displayed value matches the output pressure, select Done and go to step 8.
8. Place the instrument In Service and verify that the displayed pressure matches the measured output pressure.
218
Instruction Manual
D103412X012
August 2012
Note
Views Lists are used by hosts for efficient monitoring of multiple parameters. Normally you will not be aware of view list usage, as
they are hidden by the host software.
Resource Block
This section contains information on the DVC6200f digital valve controller resource block. The resource block defines
the physical resources of the device. The resource block also handles functionality that is common across multiple
blocks. The block has no linkable inputs or outputs.
Table 61. Resource Block BLOCK_ERR Conditions
Condition Number
Simulate Active Indicates that the simulation jumper is in place on the aux terminals. This is not an indication that the I/O
blocks are using simulation data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].
Device Needs Maintenance Soon Indicates a Maintenance PlantWeb Alert condition is active.
10
Lost Static Data Indicates failure of the memory containing static parameters
11
12
13
Device Needs Maintenance Now Indicates a Failed PlantWeb Alert condition is active.
14
Power Up Indicates the device has been powered up and the Resource Block is not running normally.
15
Out of Service (MSB) The resource block actual mode is Out of Service.
219
Instruction Manual
August 2012
D103412X012
Device Diagnostics
Resource Block Error
(RB > Device Diagnostics > Resource Block Error)
Field Communicator
Block Error (BLOCK_ERR [6]) indicates an error status associated with hardware or software for the resource block.
Table 61 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the
resource block and are provided only for your reference.
Device State
Field Communicator
Device State (RS_STATE [7]) indicates the state of the function blocks. Four states are possible:
InitializationThe instrument enters this state upon restart or failure. The function blocks are in the IMan mode.
During the initialization state, all unreported function block alarms are automatically confirmed and acknowledged.
Once the instrument is considered operational, block execution is scheduled and the instrument state moves to
Online.
OnlineThe instrument will be in this state if it is operational. The function blocks are initially in the Auto mode, but
can be changed to a higher level mode.
StandbyThe instrument enters this state if the resource block mode is Out of Service (OOS). In this state all
function block modes are forced to Out of Service. The transducer block mode is not affected. When the resource
block mode is changed to Auto, the instrument state moves to Online.
Failure The instrument moves to this state whenever a hardware or memory failure is detected which would
prevent reliable operation. All function blocks and the transducer block modes are Out of Service.
Write Lock
Field Communicator
220
Instruction Manual
D103412X012
August 2012
Block Alarm
Field Communicator
The Block Alarm (BLOCK_ALM [36]) is used for all configuration, hardware, connection failure or system problems in
the block.
Block Alarm: Alarm State
Block Alarm: Alarm State (BLOCK_ALM. ALARM_STATE [36.2]) indicates the state of the Block Alarm. Five states are
possible:
Undefined
Clear reported
Clear not reported
Active reported
Active not reported
Maintenance
Field Communicator
Restart Actions
WARNING
Restarting the instrument may cause loss of process control. To avoid personal injury and property damage caused by the
release of pressure of process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or
bleed off the process fluid.
You can restart the instrument to reset parameters, links, etc. within the instrument. However, due to the effect that a
restart can have on the instrument, and therefore the control loop, restarting the instrument should be used
cautiously and only as a last measure. The following procedure describes how to use Restart Options to restart the
instrument with a Field Communicator. You can also restart the instrument using ValveLink software or from a host
system using the Restart method included with the device description (DD) software.
You can restart the instrument any time it is connected to an active segment.
Field Communicator
1. Restart informs you about what can happen when an instrument restart is performed. Select Yes to continue, or No
to abort without restarting.
2. Select the desired restart action or select EXIT to exit Restart. Select Help (not the Help button) to get information
on restart actions.
221
Instruction Manual
August 2012
D103412X012
There are two different restarts: Restart Processor, and Restart with Defaults:
When selecting either of these options, Restart informs you of the consequences of this action and asks if you want to
continue. Select Yes to perform the restart action, select No to select another action or exit. Restart informs you when
the restart is completed. You must acknowledge the message to continue.
Restart ProcessorPerforming a Restart Processor has the same effect as removing power from the instrument and
reapplying power. Configuration and calibration do not change.
Restart with DefaultsPerforming a Restart with Defaults should be done with care. This restart resets most of the
static and nonvolatile parameters for all of the blocks in the instrument to their initial value, as listed in table 42. After
a Restart with Defaults, you should place the instrument in service (the transducer block mode to auto) and run Device
Setup and download the instrument configuration from the control system to properly setup the instrument. You also
may need to reestablish communication links and trends.
Fault StateFault State (FAULT_STATE [28]), when active, indicates that the resource block is currently forcing the
output block to perform its FSTATE action. Selecting Fault State enables the ability to manually set and clear the
fault state.
Set Fault StateSelecting Set Fault State (SET_FSTATE [29]) changes the Fault State (FAULT_STATE [28]) to Active.
Setting Set FState (SET_FSTATE [29]) to SET manually places the instrument in the fault state.
Clear Fault StateSetting Clear FState (CLR_FSTATE [30]) to CLEAR clears the device fault state, if no faults are
currently active. You can test the actions the output blocks will perform by manually setting fault state active.
Device Variables
Instrument
Field Communicator
The following parameters are contained in the the Instrument menu of the resource block.
Identification
Device IDThe 32 character Device ID (DEVICE_ID [54]).
Electronics Serial NumberThe Electronics Serial Number (ELECTRONICS_SN [49]) set at the factory.
Factory Serial NumberThe Factory Serial Number (FACTORY_SN [50]) is the instrument serial number set at the
factory.
Field Serial NumberThe Field Serial Number (FIELD_SN [51]) is the serial number of the valve and actuator on
which the instrument is mounted.
Tag DescriptionThe Tag Description (TAG_DESC [2]) is unique description of each block within the digital valve
controller, used to describe the intended application for the block. Follow the prompts on the Field Communicator
to enter an up to 32 character description for the block in the Tag Description field. (This parameter is read/write.)
StrategyStrategy (STRATEGY [3]) permits strategic grouping of blocks so the operator can identify where the
block is located. The blocks may be grouped by plant area, plant equipment, etc. Enter a value between 0 and
65535 in the Strategy field.
222
Instruction Manual
D103412X012
August 2012
Version
Device RevisionDevice Revision (DEV_REV [12]) identifies the device revision number. It is used by the host system
to locate the DD file for the device.
Firmware RevisionFirmware Revision (FIRMWARE_REV_ALL [47.6]) shows all device firmware revisions currently in
operation.
Standby Firmware RevisionStandby Firmware Revision (STBY_FIRMWARE_REV_ALL [55.6]) shows all device
firmware revisions currently in standby.
Hardware RevisionHardware Revision(HARDWARE_REV[48]) identifies the electronic hardware revision.
ITK VersionITK Version (ITK_VER [41]) identifies the major version of the Interoperability Tester used by the
Fieldbus Foundation in certifying the device as interoperable. This device revision meets the requirements of
version 5.
Options
Field Communicator
The following parameters are contained in the the Options menu of the resource block.
Diagnostic OptionsDiagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the
instrument.
Function Block OptionsFunction Block Options (FB_OPTIONS [44]) shows which function blocks are licenced and
enabled in the instrument.
Miscellaneous OptionsMiscellaneous Options (MISC_OPTIONS [46]) indicates which miscellaneous licensing
options are enabled.
Features AvailableFeatures (FEATURES [17]) shows the supported resource block options.
DD Information
Field Communicator
Transducer Block
This section contains information on the DVC6200f digital valve controller transducer block. Descriptions of all
transducer block parameters are included. The transducer block decouples function blocks from the local output
functions required to command output hardware. The transducer block typically contains setup and calibration
information.
223
Instruction Manual
D103412X012
Device Diagnostics
Active PlantWeb Alerts
Field Communicator
Alert Conditions
Field Communicator
Instrument Alert Conditions, when enabled, detect many operational and performance issues that may be of interest.
The alert conditions for each group of alerts are listed below. If there are no alerts active for a particular group the
group will not be displayed on the Field Communicator.
Electronicsif an electronics alert is active it will appear under ELECT ALERTS
Drive Current
Drive Current AlertThis alert is active when the difference between the expected Drive Current and the actual Drive
Current has exceeded the Drive Current Alert Time.
Drive Signal
Drive Signal AlertThe Drive Signal Alert is active if one of the following conditions exist:
Where Zero Power Condition is defined as closed:
Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%
Where Zero Power Condition is defined as open:
Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%
Processor Impaired
Program Memory AlertThis alert is active if a pending flash or NVM failure is present.
Static Memory AlertThis alert is active when there is a failure of the FRAM memory where static parameters are
stored.
Processor AlertThis alert is active when there is a failure of the main processor.
I/O Processor AlertThis alert is active when there is a failure of the I/O processor.
ConfigurationIf a configuration alert is active it will appear under CONFIG ALERTS
Output Block Timeout
Output Block Timeout AlertThis alert is active if the output block has not executed for a period of time longer than
the configured timeout.
224
Instruction Manual
D103412X012
August 2012
225
Instruction Manual
August 2012
D103412X012
Travel Closed
Travel Closed AlertThis alert is active if the travel is greater than the travel closed alert point.
Proximity
Proximity Hi Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Hi Alert Point
and the Travel Hi Hi Deadband.
Proximity Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Alert Point and the
Travel Hi Deadband.
Proximity Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Alert Point and the
Travel Lo Deadband.
Proximity Lo Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Lo Alert Point
and the Travel Lo Lo Deadband.
Travel HistoryIf a travel history alert is active it will appear under TVL HIST ALERTS
Cycle Counter
Cycle Counter AlertThis alert is active if the Cycle Counter exceeds the Cycle Count Alert Point.
Travel Accumulator
Travel Accumulator AlertThis alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point.
Performanceif a performance alert is active it will appear under PERF ALERTS
Performance Critical
Performance Critical AlertThis alert is active if the instrument is no longer able to control the valve or performance
has been dramatically reduced.
Performance Reduced AlertThis alert is active if the instrument has detected a reduction in performance.
Performance Information AlertThis alert is active if the instrument has detected a condition that may pertain to
control performance.
Status
Field Communicator
226
Instruction Manual
D103412X012
August 2012
Travel Sensor Span ErrorIndicates that span between the endpoints of travel are not far enough apart. This error is
reported during automatic calibration.
MLFB ErrorIndicates that the Minor Loop Feedback sensor gave a nonvalid value during automatic calibration.
Travel Sensor Hi ErrorIndicates the travel sensor has reported a travel position that is significantly above the normal
operating range, and has failed.
Travel Sensor Lo ErrorIndicates the travel sensor has reported a travel position that is significantly below the normal
operating range, and has failed.
Pressure B Sensor FailureIndicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
Pressure A Sensor FailureIndicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
Supply Sensor FailureIndicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
IOP FailureIndicates the I/O processor has failed.
Drive Current AlertIndicates that the Drive Current has exceeded the Drive Current Alert Point for more than the Drive
Current Alert Time.
Simulate Jumper ONIndicates the simulate jumper is connected to the DVC6200f between the two AUX terminals.
Block Error
Table 62 lists conditions reported in the BLOCK_ERR [6] and XD_ERROR [11] parameters. Conditions in italics are not
applicable for the transducer block and are provided only for your reference.
Table 62. Transducer Block BLOCK_ERR and XD_ERROR Conditions
Condition Number
Other (N/A)
Block Configuration Error Indicates that one of the following parameters have been configured out of the proper range: 15,
16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
Simulate Active Indicates that alerts are being simulated. This is not an indication that the I/O blocks are using simulation
data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].
10
Lost Static Data Indicates that manufacturing functional or thermal tests were incomplete
11
12
13
Device Needs Maintenance Now Indicates that manufacturing functional or thermal tests were incomplete
14
Power Up (N/A)
15
227
Instruction Manual
August 2012
D103412X012
Device Record
Field Communicator
The following parameters are contained in the Device Record menu of the transducer block.
Maximum Recorded TemperatureMaximum Recorded Temperature (TEMP_MAX [86.1]) shows the maximum
temperature the instrument has experienced since installation.
Maximum Recorded Temperature TimeMaximum Recorded Temperature Time (TEMP_MAX_TIME [86.2]) shows
the date and time when the Temperature Maximum occurred.
Minimum Recorded TemperatureMinimum Recorded Temperature (TEMP_MIN [86.3]) shows the minimum
temperature the instrument has experienced since installation.
Minimum Recorded Temperature TimeMinimum Recorded Temperature Time (TEMP_MIN_TIME [86.4]) shows
the date and time when the Temperature Minimum occurred.
Maximum Recorded Supply PressureMaximum Recorded Supply Pressure (SUPPLY_PRESS_MAX [86.5]) shows the
maximum supply pressure the instrument has experienced since installation.
Maximum Recorded Supply Pressure TimeMaximum Recorded Supply Pressure Time (SUPP_PRESS_MAX_TIME
[86.6]) shows the date and time when the Supply Pressure Maximum occurred.
Minimum Recorded Supply PressureMinimum Recorded Supply Pressure (SUPP_PRESS_MIN [86.7]) shows the
minimum supply pressure the instrument has experienced since installation.
Minimum Recorded Supply Pressure TimeMinimum Recorded Supply Pressure Time (SUPP_PRESS_MIN_TIME
[86.8]) shows the date and time when the Supply Pressure Minimum occurred.
Stroke Valve is used to confirm proper valve operation. Follow the prompts on the Field Communicator display to
select from the following: Done, Ramp Open, Ramp Closed, Ramp to Target, Step to Target, and Stop.
DoneSelect this if you are done. All ramping is stopped when DONE is selected.
Ramp Openramps the travel toward open at the rate of 1.0% per second of the ranged travel.
Ramp Closedramps the travel toward closed at the rate of 1.0% per second of the ranged travel.
Ramp to Targetramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.
Step to Targetsteps the travel to the specified target.
Stopstops the command.
228
Instruction Manual
D103412X012
August 2012
Trend
Field Communicator
Trend chart of Setpoint (FINAL_VALUE.VALUE [13.2]), Travel (TRAVEL.VALUE [34.2]), and Pressure A
(PRESSURE_A.VALUE [36.2]).
Device Variables
Field Communicator
Note
Block Mode:Actual drops the AUTO bit for the cascade targets. For example, target mode might have Cas and Auto set, but actual
mode will only have Cas set.
229
Instruction Manual
August 2012
D103412X012
AO Control - PreCharacterization
Setpoint
Setpoint (FINAL_VALUE.VALUE [13.2]) shows the value of the setpoint in % (percent) of ranged travel or pressure.
Setpoint is used for both travel and pressure control. This parameter will be written directly if the transducer block is in
MAN mode, or will be written automatically by the AO block if the transducer block is in AUTO mode.
Setpoint Status
Shows the Foundation Fieldbus status of Setpoint Value (FINAL_VALUE.STATUS [13.2]); Good, Uncertain, or Bad.
Travel (DeChar)
Travel (FINAL_POSITION_VALUE.VALUE [17.2]) shows the value of the travel in % (percent) of ranged travel. Travel
always represents how far the valve is open.
AO ControlPost Characterization
Travel Target
Travel target is the output from the characterization function.
Travel
Travel (TRAVEL.VALUE [34.2]) displays the actual position of the valve in percent (%) of calibrated travel.
Travel Status
Shows the Foundation Fieldbus status of Travel Value (TRAVEL.STATUS [34.1]); Good, Uncertain, or Bad.
DO Control
Setpoint(D)
Discrete Setpoint (SETPOINT_D.VALUE [32.2]) shows the value of the setpoint in discrete values.
0 = closed, 1 = open, 5, 10, 15... = setpoint in 5% units. This parameter will be written directly if the transducer block is
in MAN mode, or will be written automatically by the DO block if the transducer block is in AUTO mode.
Travel(D)
Travel (TRAVEL_D.VALUE [33.2]) shows the value of the setpoint in discrete values.
0 = closed, 1 = open, 5, 10, 15... = setpoint in 5% units.
Input Characterization
Input Characterization (INPUT_CHAR [50]) defines the relationship between the setpoint specified by the output
function block and the desired valve position.
230
Instruction Manual
D103412X012
August 2012
Travel/Pressure State
Travel/Pressure State (TVL_PRESS.STATE [41.2]) indicates if the instrument is being used for travel control (position
control) or as an I/P (pressure control).
PD Inside Status
PD Inside Status shows the status of Performance Diagnostics.
Protection
Indicates the status of Protection.
Drive Signal
Drive Signal (DRIVE_SIGNAL [53]) indicates the drive signal, as a percentage of the maximum drive available, going to
the I/P converter from the printed wiring board. In most applications, the drive signal ranges between 50% and 75% of
the maximum drive signal.
Temperature
Temperature (TEMPERATURE [48]) displays the internal temperature of the instrument in either degrees Fahrenheit or
Celsius.
Cycle Counter
Cycle Counter (CYCLE_COUNT [73]) records the number of times the travel changes direction. The change in direction
must occur after the deadband has been exceeded before it can be counted as a cycle.
Travel Accumulator
Travel Accumulator (TRAVEL_ACCUM [72]) indicates the total change in travel, in percent of ranged travel. The
accumulator only increments when travel exceeds the deadband. Then the greatest amount of change in one
direction from the original reference point (after the deadband has been exceeded) will be added to the Travel
Accumulator.
Travel Count
Travel Count (TVL_COUNT [43.1]) is the Travel Sensor readback displayed in A/D counts.
231
Instruction Manual
D103412X012
Pressures
Supply
Supply (SUPPLY_PRESSURE_VALUE [35.2]) shows the value of the supply pressure in psi, bar, kPa, inHg, inH2O, or
kg/cm2.
Pressure A
Pressure A (PRESSURE_A.VALUE [36.2]) shows the value of Output Pressure A in psi, bar, kPa, inHg, inH2O, or kg/cm2.
Pressure B
Pressure B (PRESSURE_B.VALUE [37.2]) shows the value of Output Pressure B in psi, bar, kPa, inHg, inH2O, or kg/cm2.
A Minus B
A Minus B (PRESSURE_DIFF.VALUE [38.2]) shows the value of the output pressure differential in psi, bar, kPa, inHg,
inH2O, or kg/cm2.
232
Instruction Manual
D103412X012
August 2012
Section 7 Maintenance and Troubleshooting7-7The DVC6200f digital valve controller enclosure is rated Type 4X and IP66, therefore periodic cleaning of internal
components is not required. If the DVC6200f is installed in an area where the exterior surfaces tend to get heavily
coated or layered with industrial or atmospheric contaminants, however, it is recommended that the vent (key 52) be
periodically inspected to ensure it is fully open. If the vent appears to be clogged, it can be removed, cleaned and
replaced. Lightly brush the exterior of the vent to remove contaminants and run a mild water/detergent solution
through the vent to ensure it is fully open. Allow the vent to dry before reinstalling.
WARNING
Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent
opening is open and free of debris to prevent pressure buildup under the cover.
WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing
any maintenance procedures on the DVC6200f digital valve controller:
Always wear protective clothing, gloves, and eyewear.
Do not remove the actuator from the valve while the valve is still pressurized.
Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
from both sides of the valve.
Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression.
Use lockout procedures to be sure that the above measures stay in effect while you work on the equipment.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
WARNING
When using natural gas as the supply medium, or for explosion proof applications, the following warnings also apply:
Remove electrical power before removing the housing cap. Personal injury or property damage from fire or explosion
may result if power is not disconnected before removing the cap.
Remove electrical power before disconnecting any of the pneumatic connections.
When disconnecting any of the pneumatic connections or any pressure retaining part, natural gas will seep from the
unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may result
233
Instruction Manual
D103412X012
from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken.
Preventive measures may include, but are not limited to, one or more of the following: ensuring adequate ventilation
and the removal of any ignition sources.
Ensure that the cover is correctly installed before putting this unit back into service. Failure to do so could result in
personal injury or property damage from fire or explosion.
CAUTION
When replacing components, use only components specified by the factory. Always use proper component replacement
techniques, as presented in this manual. Improper techniques or component selection may invalidate the approvals and
the product specifications, as indicated in table 11, and may also impair operations and the intended function of the
device.
Because of the diagnostic capability of the DVC6200f, predictive maintenance is available through the use of ValveLink
software. Using the digital valve controller, valve and instrument maintenance can be enhanced, thus avoiding
unnecessary maintenance. For information on using ValveLink software, refer to the ValveLink software online help.
Tools Required
Table 71 lists the tools required for maintaining the DVC6200f digital valve controller.
Table 71. Tools Required
Tool
Phillips Screwdriver
Hex key
Hex key
Hex key
Hex key
234
Size
5 mm
1.5 mm
2.5 mm
6 mm
Component
Relay, printed wiring board assembly, and cover screws
Terminal box screw
Terminal box cover screw
I/P converter screws
Module base screws
Instruction Manual
D103412X012
Component Replacement
When replacing any of the components of the DVC6200f, the maintenance should be performed in an instrument
shop whenever possible. Make sure that the electrical wiring and pneumatic tubing is disconnected prior to
disassembling the instrument.
WARNING
To avoid personal injury or equipment damage from bursting of parts, turn off the supply pressure to the digital valve
controller and bleed off any excess supply pressure before attempting to remove the module base assembly from the
housing.
1. Unscrew the four captive screws in the cover (key 43) and remove the cover from the module base (key 2).
2. Using a 6 mm hex socket wrench, loosen the threesocket head screws (key 38). These screws are captive in the
module base by retaining rings (key 154).
Note
The module base is linked to the housing by two cable assemblies. Disconnect these cable assemblies after you pull the module
base out of the housing.
CAUTION
To avoid affecting performance of the instrument, take care not to damage the module base seal or guide surface. Do not
bump or damage the bare connector pins on the PWB assembly. Damaging either the module base or guide surface may
result in material damage, which could compromise the instruments ability to maintain a pressure seal.
3. Pull the module base straight out of the housing (key 1). Once clear of the housing, swing the module base to the
side of the housing to gain access to the cable assemblies.
4. The digital valve controller has two cable assemblies, shown in figure 71, which connect the module base, via the
printed wiring board assembly, to the travel sensor and the terminal box. Disconnect these cable assemblies from
the printed wiring board assembly on the back of the module base.
235
Instruction Manual
D103412X012
HOUSING
CABLE
TO TERMINAL BOX
W99241
TERMINAL BOX
CONNECTOR
GE39341
Note
To avoid affecting performance of the instrument, inspect the guide surface on the module and the corresponding seating area in
the housing before installing the module base assembly. These surfaces must be free of dust, dirt, scratches, and contamination.
Ensure the module base seal is in good condition. Do not reuse a damaged or worn seal.
236
Instruction Manual
D103412X012
August 2012
1. Ensure the module base seal (key 237) is properly installed in the housing (key 1). Ensure the Oring (key 12) is in
place on the module base assembly.
2. Connect the terminal box connector to the PWB assembly (key 50). Orientation of the connector is required.
3. Connect the travel sensor connector to the PWB assembly (key 50). Orientation of the connector is required.
4. Insert the module base (key 2) into the housing (key 1).
5. Install three socket head screws (key 38) in the module base into the housing. If not already installed, press three
retaining rings (key 154) into the module base. Evenly tighten the screws in a crisscross pattern to a final torque of
16 Nm (138 lbfin).
CAUTION
Personal injury, property damage, or disruption of process control can result if the cable assemblies/wiring are damaged
when attaching the cover to the module base assembly
Ensure that the cable assemblies/wiring are positioned in the cavity of the module base so they do not get compressed or
damaged when attaching the cover to the module base assembly in step 6.
Submodule Maintenance
The digital valve controller's module base contains the following submodules: I/P converter, PWB assembly, and
pneumatic relay. If problems occur, these submodules may be removed from the module base and replaced with new
submodules. After replacing a submodule, the module base may be put back into service.
CAUTION
Exercise care when performing maintenance on the module base. Reinstall the cover to protect the I/P converter and
gauges when servicing other submodules.
In order to maintain accuracy specifications, do not strike or drop the I/P converter during submodule maintenance.
I/P Converter
Refer to figure 82 or 84 for key number locations. The I/P converter (key 41) is located on the front of the module
base.
Note
After I/P converter submodule replacement, calibrate the digital valve controller to maintain accuracy specifications.
237
Instruction Manual
D103412X012
1. Remove the I/P converter (key 41) and shroud (key 169) as described in the Removing the I/P Converter procedure.
2. Remove the screen (key 231) from the supply port.
3. Install a new screen in the supply port as shown in figure 73.
4. Inspect the Oring (key 39) in the I/P output port. if necessary, replace it.
5. Reinstall the I/P converter (key 41) and shroud (key 169) as described in the Replacing the I/P Converter procedure.
Figure 73. I/P Filter Location
W8072
238
Instruction Manual
D103412X012
August 2012
I/P CONVERTER
(KEY 41)
W9328
SHROUD
(KEY 169)
SOCKETHEAD
SCREWS (4)
(KEY 23)
BOOTS
(KEY 210)
3. Install the I/P converter (key 41) straight into the module base (key 2), taking care that the two electrical leads feed
into the guides in the module base. These guides route the leads to the printed wiring board assembly submodule.
4. Install the shroud (key 169) over the I/P converter (key 41).
5. Install the four sockethead screws (key 23) and evenly tighten them in a crisscross pattern to a final torque of 1.6
Nm (14 lbfin).
6. After replacing the I/P converter, calibrate travel or perform touchup calibration to maintain accuracy
specifications.
Note
The DVC6200f PWB assembly must be firmware revision 2.0 or later.
Note
If the PWB assembly submodule is replaced, calibrate and configure the digital valve controller to maintain accuracy specifications.
Separate the module base from the housing by performing the Removing the Module Base procedure.
Remove three screws (key 33).
Lift the PWB assembly (key 50) straight out of the module base (key 2).
Ensure that the Orings (key 40) remain in the pressure sensor bosses on the module base assembly (key 2) after the
PWB assembly (key 50) has been removed.
239
Instruction Manual
August 2012
D103412X012
2. Properly orient the PWB assembly (key 50) as you install it into the module base. The two electrical leads from the
I/P converter (key 41) must guide into their receptacles in the PWB assembly and the pressure sensor bosses on the
module base must fit into their receptacles in the PWB assembly.
3. Push the PWB assembly (key 50) into its cavity in the module base.
4. Install and tighten three screws (key 33) to a torque of 1 Nm (10.1 lbfin).
5. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
6. Setup and calibrate the digital valve controller.
Note
Calibration is required for either Travel or Pressure Control after PWB Assembly replacement.
Note that only one calibration is needed, depending on control selection.
Pneumatic Relay
Refer to figure 82 or 84 for key number locations. The pneumatic relay (key 24) is located on the front of the module
base.
Note
After relay submodule replacement, calibrate the digital valve controller to maintain accuracy specifications.
RELAY SEAL
W8074
240
Instruction Manual
D103412X012
August 2012
3. Position the relay (with shroud) on the module base. Tighten the four screws, in a crisscross pattern, to a final
torque of 2 Nm (20.7 lbfin).
4. Using the Field Communicator, verify that the value for Relay Type parameter matches the relay type installed.
5. After replacing the relay and verifying the relay type, calibrate travel or perform touchup calibration to maintain
accuracy specifications
Terminal Box
WARNING
Refer to the Maintenance WARNING at the beginning of this section.
1. Loosen the set screw (key 58) in the cap (key 4) so that the cap can be unscrewed from the terminal box.
2. After removing the cap (key 4), note the location of field wiring connections and disconnect the field wiring from
the terminal box.
3. Separate the module base from the housing by performing the Removing the Module Base procedure.
241
Instruction Manual
August 2012
D103412X012
4. Disconnect the terminal box wiring connector from the PWB assembly (key 50).
5. Remove the screw (key 72). Pull the terminal box assembly straight out of the housing.
1. Apply lubricant, silicone sealant to the Oring (key 34) and install the Oring over the stem of the terminal box.
2. Insert the terminal box assembly stem into the housing until it bottoms out. Position the terminal box assembly so
that the hole for the screw (key 72) in the terminal box aligns with the threaded hole in the housing. Install the
screw (key 72).
3. Connect the terminal box wiring connector to the PWB assembly (key 50).
4. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
5. Reconnect the field wiring as noted in step 2 in the Removing the Terminal Box procedure.
6. Apply lubricant, silicone sealant to the Oring (key 36) and install the Oring over the 25/8 inch threads of the
terminal box. Use of a tool is recommended to prevent cutting the Oring while installing it over the threads.
7. Apply lithium grease (key 63) to the 25/8 inch threads on the terminal box to prevent seizing or galling when the
cap is installed.
8. Screw the cap (key 4) onto the terminal box.
9. Install a set screw (key 58) into the cap (key 4). Loosen the cap (not more than 1 turn) to align the set screw over
one of the recesses in the terminal box. Tighten the set screw (key 58).
242
Instruction Manual
D103412X012
August 2012
Instrument Troubleshooting
What to Do First
When a problem occurs, check the following first:
Mounting
Is the feedback linkage connected correctly? See the beginning of this section.
Utility Connections
Are pneumatic connections correct? Are there any air leaks? See the Installation section.
Is the air supply pressure sufficient to drive the valve?
Is the digital valve controller correctly connected to the fieldbus? See the Installation section.
Is there power to the device? Is the terminal voltage between 9 and 32 volts? See the Installation section.
Is the segment terminated correctly? See host system documentation.
Is the host system connected to the segment? See host system documentation.
If communication or output difficulties are experienced with the instrument, refer to the troubleshooting information
provided in table 72.
Also see the Technical Support Checklist found on page 248.
243
Instruction Manual
D103412X012
Possible Cause
1a No power to device
Action
1a1 Ensure device is connected to the segment (see
host system documentation).
1a2 Measure the terminal voltage. Terminal voltage
should be between 9 and 32 VDC.
1a3 Check to be sure device is drawing current. There
should be approximately 19 mA.
1b1 Verify connectors are plugged into the printed
wiring board correctly (see Printed Wiring Board
Assembly on page 239).
1b2 Check continuity of cable between terminal box
and printed wiring board. If necessary, replace the
terminal box assembly (see Replacing the Terminal Box
on page 242).
1b3 Check for damaged printed wiring board lands and
terminals. If necessary, replace the terminal box
assembly (see Replacing the Terminal Box on page
242).
2c Electronics failing.
244
Instruction Manual
D103412X012
August 2012
Possible Cause
4a Resource block actual mode is Out of Service.
Action
4a Change Resource block target mode to Auto (see
page 45, Resource Block Mode, or host system
documentation).
4b Change transducer block target mode to Auto (see
page 62, Transducer Block Mode or host system
documentation).
4c Set the schedules using host system or
configuration tool. All function blocks must be in a
schedule that is downloaded to the device.
4d Look for configuration error bit in BLOCK_ERR. By
default, all enumerature type parameters are initialized
to 0 (undefined). They must be configured before the
block can be put into service.
5a Change Resource block target mode to Auto (see
page 45, Resource Block Mode, or host system
documentation).
5b Change transducer block target mode to Auto (see
page 62, Transducer Block Mode or host system
documentation).
5c A bad status is passed to the block's READBACK or
FIELD_VAL parameter. See transducer section of
Detailed Setup for repair information.
5d Use Outblock Selection to select the desired output
block. The deselected block will have a bad status for
READBACK. This will keep it in IMAN mode when target
is other than OOS.
5e The Actual Block Mode (MODE_BLK.ACTUAL [5.2])
will remain out of service and the block cannot be
scheduled if the block has not bee licensed. Contact
your Emerson Process Management sales office to
upgrade product licensing.
5f Set the schedules using host system or configuration
tool. All function blocks must be in a schedule that is
downloaded to the device.
5g Look for configuration error bit in BLOCK_ERR. By
default, all enumerature type parameters are initialized
to 0 (undefined). They must be configured before the
block can be put into service.
-Continued-
245
Instruction Manual
D103412X012
Possible Cause
Action
-Continued-
246
Instruction Manual
D103412X012
August 2012
Possible Cause
14f Oring(s) between I/P converter ass'y missing or hard 14f Replace Oring(s) (refer to the I/P Converter section
and flattened losing seal.
on page 237).
14g I/P converter ass'y damaged/corroded/clogged.
14g Check for bent flapper, open coil (continuity),
contamination, staining, or dirty air supply. Coil
resistance should be between 1680 1860 ohms.
Replace I/P ass'y if damaged, corroded, clogged, or
open coil (see Replacing the I/P Converter on page 238).
14h I/P converter ass'y out of spec.
14h I/P converter ass'y nozzle may have been adjusted.
Verify drive signal (55 to 80% for doubleacting; 60 to
85% for singleacting) with the valve off the stops.
Replace I/P converter ass'y if drive signal is continuously
high or low (see Replacing the I/P Converter on page
238).
14i Defective module base seal.
14i Check module base seal for condition and position.
If necessary, replace seal. Refer to Module Base
Maintenance on page 234.
14j Defective relay.
14j Depress relay beam at adjustment location in
shroud, look for increase in output pressure. Remove
relay, inspect relay seal. Replace relay seal or relay if I/P
converter ass'y good and air passages not blocked
(refer to Replacing the Pneumatic Relay on page 240).
Check relay adjustment (refer to page 215).
14k Defective 67CFR regulator, supply pressure gauge
14k Replace 67CFR regulator.
jumps around.
15a Configuration errors.
15a Verify configuration.
15b Magnet assembly is not correctly installed.
Action
247
Instruction Manual
D103412X012
Target Modes:
Permitted Modes:
Pressure A _________
Pressure B _________
Travel _________%
Pressure B _________
12. What is the safe position of the valve? Fail Closed ____ Fail Open ____
Interface and Diagnostic Tools
13. What interface and diagnostic tools are available?___________________________________
14. Provide any available supporting documentation, such as Status Monitor, Detailed Setup, any alert readings.
Mounting
Reference
1. Actuator application: sliding-stem? _________ Rotary? _________
2. Which digital valve controller do you have? DVC6200f _________ DVC6205f/DVC6215 _________
3. What Make, Brand, Style, Size, etc. actuator is the DVC6200f mounted on? _________________________
Operational
4. What is the full travel of the valve?__________________________________
5. What is the Mounting Kit part number? ______________________________
Other
6. If mounting kits are made by LBP/Customer, please provide pictures of installation.
248
Instruction Manual
Parts
D103412X012
August 2012
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Process Management should
not, under any circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson Process
Management may void your warranty, might adversely affect the performance of the instrument, and could cause personal
injury and property damage.
Parts Kits
Kit
Description
1*
Part Number
Description
6*
7*
19B5402X012
19B5402X022
2*
3*
4*
Kit
14B5072X182
Aluminum
Housing A (used for GX actuator)
Standard (nitrile elastomers)
Extreme Temperature option
(fluorosilicone elastomers)
Housing B (used for all actuators except GX)
Standard (nitrile elastomers)
Extreme Temperature option
(fluorosilicone elastomers)
5*
I/P Converter Kit
Standard
GE44077X012
GE44081X012
GE44078X012
Stainless Steel
Housing B (used for all actuators except GX)
Standard (nitrile elastomers)
Extreme Temperature option
(fluorosilicone elastomers)
GE44082X012
GE44080X012
38B6041X152
38B6041X132
8*
Part Number
GE48798X032
GE48798X042
GE48798X072
GE48798X082
GE48798X092
GE48798X102
GE29183X012
249
Instruction Manual
Parts
August 2012
Kit
9*
Description
Part Number
10*
D103412X012
GE46670X012
GE40178X012
GE09169X022
GE09169X032
GE09169X072
GE09169X012
GE09169X082
GE09169X042
GE09169X092
GE09170X012
GE09169X102
GE09169X062
GE09169X132
Common Parts
(see figure 82, 83, and 84)
DVC6200f and DVC6205f
16*
29
33
38
43*
48
49
61
63
64
65
154
236
237
Note
Part numbers are shown for recommended spares only. For part
numbers not shown, contact your Emerson Process Management sales
office.
Parts with footnote numbers are available in parts kits; see footnote
information at the bottom of the page.
Description
Description
248
249
250
267
271
287
288
GE43790X012
GE09169X112
Parts List
Key
Key
Part Number
Oring(1) (3 req'd)
Warning label, for use only with LCIE hazardous area
classifications
Mach Screw, pan hd, SST(2) (3 req'd)
Cap Screw, hex socket, SST(2)(6) (3 req'd)
Cover Assembly (includes cover screws)
Standard
38B9580X022
Extreme temperature option
(fluorosilicone elastomers)
38B9580X032
Nameplate
Screw, self tapping (2 req'd)(6)
Pipe Plug, hex socket(6)
Housing A with relay C (2 req'd ) (used for GX actuator)
Housing A with relay B (1 req'd) (used for GX actuator)
Housing B with relay B and C (1 req'd)
(used for all actuators except GX)
Not required for relay A
Lithium grease (not furnished with the instrument)
Zinc based antiseize compound (not furnished with the
instrument)
Lubricant, silicone sealant (not furnished with the instrument)
Retaining Ring(2) (3 req'd)
Screen (required for relay B and C only)(7)
Module Base Seal(1)
Module Base
(see figure 82 and 84)
DVC6200f and DVC6205f
2
11
12
19
61
243
Module Base(6)
Drive Screw(6) (2 req'd)
Oring(1)
Label, Shield Assembly(6)
Pipe Plug, hex socket(6) (3 req'd)
Slotted Pin (flame arrestor)(6) (3 req'd)
250
Housing(7)
Drive Screw (2 req'd) (DVC6205f only)
Shield (DVC6205f only)
Vent, plastic(2)
Mounting Bracket (DVC6205f only)
*Recommended spare
1. Available in the Elastomer Spare Parts Kit
2. Available in the Small Hardware Spare Parts Kit
6. Available in the Spare Module Base Assembly Kit
7. Available in the Spare Housing Assembly Kit
Instruction Manual
Parts
D103412X012
Key
Description
August 2012
Part Number
GASBLOCKING
PRESSFIT ADAPTOR
Key
W99231
38B5786X182
38B5786X172
38B5786X132
38B5786X052
38B5786X092
38B5786X202
38B5786X192
38B5786X152
38B5786X072
38B5786X112
Description
Part Number
264
*Recommended spare
1. Available in the Elastomer Spare Parts Kit
2. Available in the Small Hardware Spare Parts Kit
3. Available in the Seal Screen Kit
4. Available in the Terminal Box Kit
5. Available in the I/P Converter Kit
8. Available in the Spare Shroud Kit
251
Instruction Manual
Parts
August 2012
Key
Description
PWB Assembly
(see figure 82 and 84)
DVC6200f and DVC6205f
D103412X012
Key
Description
Part Number
Note
Contact your Emerson Process Management sales office for PWB
Assembly FS numbers.
50*
252
PWB Assembly
Standard Control
Fieldbus Diagnostics
Advanced Diagnostics
Performance DIagnostic
Fieldbus Control
Fieldbus Diagnostics
Advanced Diagnostics
Performance Diagnostics
Fieldbus Logic
Fieldbus Diagnostics
Advanced Diagnostics
Performance Diagnostics
47*
66
67
Instruction Manual
Parts
D103412X012
August 2012
DOUBLEACTING
DIRECTACTING
REVERSEACTING
253
Instruction Manual
Parts
August 2012
D103412X012
Figure 82. FIELDVUE DVC6200f Digital Valve Controller Housing Assembly (continued)
SECTION C-C
SCALE 2 : 1
SECTION A-A
SECTION E-E
SCALE 2 : 1
SECTION F-F
SCALE 2 : 1
GE40185 sheet 2 of 3
DOUBLEACTING
DIRECTACTING
254
REVERSEACTING
Instruction Manual
Parts
D103412X012
August 2012
SECTION B-B
SECTION A-A
SECTION H-H
255
Instruction Manual
Parts
August 2012
D103412X012
SECTION C-C
SCALE 2 : 1
SECTION E-E
SCALE 2 : 1
DOUBLEACTING
DOUBLEACTING SHOWN
DIRECTACTING
256
REVERSEACTING
Instruction Manual
Parts
D103412X012
August 2012
WALL MOUNTING
PIPE MOUNTING
257
Instruction Manual
Parts
August 2012
D103412X012
SECTION A-A
PARTS NOT SHOWN: 158
APPLY LUBRICANT, SEALANT, OR THREAD LOCK
GE46670-B
HOUSING A
(USED FOR GX ACTUATOR)
SECTION A-A
HOUSING B
(USED FOR ALL ACTUATORS EXCEPT GX)
258
Instruction Manual
Principle of Operation
D103412X012
August 2012
932 VOLT
FIELDBUS
PRINTED
WIRING BOARD
DRIVE
SIGNAL
AUXILIARY
TERMINALS
OUTPUT A
I/P
CONVERTER
TERMINAL BOX
PNEUMATIC
RELAY
SUPPLY
PRESSURE
OUTPUT B
VALVE AND
ACTUATOR
VENT
E1376
The DVC6200f digital valve controller is a buspowered instrument that provides a control valve position in response
to a digital setpoint from the control room. The following describes a direct acting DVC6200f digital valve controller
mounted on a sliding-stem piston actuator, where the valve is closed with zero power to the instrument.
The setpoint is routed into the terminal box through a single pair of wires and then to the printed wiring board
assembly submodule where it is read by the microprocessor, processed by a digital algorithm, and converted into an
analog I/P drive signal.
259
Instruction Manual
Principle of Operation
August 2012
D103412X012
As the setpoint increases, the drive signal to the I/P converter increases, increasing the I/P output pressure. The I/P
output pressure is routed to the pneumatic relay submodule. The relay is also connected to supply pressure and
amplifies the small pneumatic signal from the I/P converter. The relay accepts the amplified pneumatic signal and
provides two output pressures. With relay A, an increasing setpoint will produce increasing pressure at output A and
decreasing pressure at output B. With relay B an increasing setpoint will produce decreasing pressure at output B
(output A is not available). With relay C an increasing setpoint will produce an increasing pressure on output A (output
B is not available). The output A pressure is used for doubleacting and singleacting direct applications. The output B
pressure is used for doubleacting and singleacting reverse applications.
Figure A2. FIELDVUE DVC6200f Digital Valve Controller Assembly
HOUSING
PNEUMATIC
RELAY
GAUGES
COVER
TERMINAL BOX
WITH COVER
PRINTED WIRING
BOARD ASSEMBLY
I/P CONVERTER
W99251
As shown in figure A1, the increased output A pressure causes the actuator stem to move upward. The stem position
is sensed by the travel sensor. The stem continues to move upward until the correct stem position is attained. At this
point the printed wiring board assembly stabilizes the I/P drive signal. This prevents any further increase in the
pneumatic signal from the I/P converter.
As the digital setpoint decreases, the drive signal to the I/P converter submodule decreases, decreasing the I/P output
pressure. The pneumatic relay decreases the output A pressure and increases the output B pressure. The stem moves
downward until the correct position is attained. At this point the printed wiring board assembly stabilizes the I/P drive
signal. This prevents any decrease in the pneumatic signal from the I/P converter.
260
Instruction Manual
D103412X012
August 2012
261
Instruction Manual
D103412X012
Menu Structure
A Minus B
Actual Travel
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Actual Travel
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Fail Action
Actuator Manufacturer
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Manufacturer
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Model Number
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Serial Number
Actuator Size
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Size
Actuator Style
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Style
Advise Active
TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Advise Active
Advise Enable
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Advise Enable
Advise Suppress
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Advise Suppress
Air
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Air
Alert Conditions
Alert Key
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Alert Key
Area Units
TB > Configure/Setup > Detailed Setup > Instrument > Area Units
TB > Device Diagnostics > Status > Block Error > Block Configuration Error
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Blocks Set to Defaults > Block Set to Defaults Alert
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Blocks Set to Defaults > Block Set to Defaults Alert Enable
Calibration Date
TB > Configure/Setup > Detailed Setup > Instrument > Calibration Date
Calibration Location
TB > Configure/Setup > Detailed Setup > Instrument > Calibration Location
Calibration Person
TB > Configure/Setup > Detailed Setup > Instrument > Calibration Person
TB > Configure/Setup > Detailed Setup > Response Control > Custom Characterization Table
Cycle Counter
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter
TB > Device Variables > Cycle Counter
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Deadband
TB > Device Diagnostics > Status > Block Error > Device Needs Maintenance Now
Drive Current
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current
TB > Device Diagnostics > Status > Self Test Status > Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Time
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Shutdown
Drive Signal
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal
TB > Device Variables > Drive Signal
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal Alert Enable
Effective Area
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Effective Area
Failed Active
TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Failed Active
Failed Enable
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Failed Enable
Failed Suppress
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Failed Suppress
Feedback Connection
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Feedback Connection
Flow Direction
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Direction
Flow Tends To
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Tends To
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Man Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Shutdown
Inlet Pressure
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Inlet Pressure
Continued
262
Instruction Manual
D103412X012
August 2012
Menu Structure
TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization
TB > Device Variables > Input Characterization
Integrator Limited Hi
TB > Device Diagnostics > Status > Self Test Status > Integrator Limited Hi
Integrator Limited Lo
TB > Device Diagnostics > Status > Self Test Status > Integrator Limited Lo
Integrator Suspended
TB > Device Diagnostics > Status > Self Test Status > Integrator Suspended
IOP Failure
TB > Device Diagnostics > Status > Self Test Status > IOP Failure
TB > Configure/Setup > Detailed Setup > Instrument > Last Calibration Type
Leak Class
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Leak Class
Length Units
TB > Configure/Setup > Detailed Setup > Instrument > Length Units
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Arm Length
Lever Style
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Style
TB > Device Diagnostics > Status > Block Error > Lost Static Data
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lower Bench Set
MAI Channel 1
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 1
MAI Channel 2
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 2
MAI Channel 3
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 3
MAI Channel 4
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 4
MAI Channel 5
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 5
MAI Channel 6
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 6
MAI Channel 7
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 7
MAI Channel 8
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 8
Maint Active
TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Maint Active
Maintenance Enable
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Maintenance Enable
Maintenance Suppress
TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Maintenance Suppress
TB > Device Diagnostics > Device Record > Maximum Recorded Supply Pressure
TB > Device Diagnostics > Device Record > Maximum Recorded Supply Pressure Time
Maximum Recorded
Temperature
TB > Device Diagnostics > Device Record > Maximum Recorded Temperature
Maximum Recorded
Temperature Time
TB > Device Diagnostics > Device Record > Maximum Recorded Temperature Time
TB > Configure/Setup > Detailed Setup > Instrument > Maximum Supply Pressure
TB > Device Diagnostics > Device Record > Minimum Recorded Supply Pressure
TB > Device Diagnostics > Device Record > Minimum Recorded Supply Pressure Time
Minimum Recorded
Temperature
TB > Device Diagnostics > Device Record > Minimum Recorded Temperature
Minimum Recorded
Temperature Time
TB > Device Diagnostics > Device Record > Minimum Recorded Temperature Time
MLFB Error
TB > Device Diagnostics > Status > Self Test Status > MLFB Error
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Nominal Supply Pressure
Out of Service
TB > Device Diagnostics > Status > Block Error > Out of Service
Outlet Pressure
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Outlet Pressure
Outblock Selection
TB > Configure/Setup > Detailed Setup > Response Control > Outblock Selection
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Alert
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Manual
Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Shutdown
Packing Type
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Packing Type
PD Inside Status
PD Run
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > PD Run
Continued
263
Instruction Manual
D103412X012
Menu Structure
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Critical Alert
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Critical Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Information Alert
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Information Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Reduced Alert
TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Reduced Alert Enable
Performance Tuner
TB > Configure/Setup > Detailed Setup > Alert Handling > PlantWeb Alert Simulate
Port Diameter
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Diameter
Port Type
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Type
Pressure A
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Alert Enable
TB > Device Diagnostics > Status > Self Test Status > Pressure A Sensor Error
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Shutdown
Pressure B
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure B Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure B Sensor Alert Enable
TB > Device Diagnostics > Status > Self Test Status > Pressure B Sensor Error
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Cutoff Closed
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Cutoff Open
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Fallback > Pressure Fallback Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Fallback > Pressure Fallback Alert Enable
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Dead Zone
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Gain
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Limit Hi
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Limit Lo
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure MLFB Gain
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Proportional Gain
Pressure Range Hi
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Range Hi
Pressure Range Lo
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Range Lo
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Tuning Set
Pressure Units
TB > Configure/Setup > Detailed Setup > Instrument > Pressure Units
Processor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Processor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Processor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Shutdown
Protection
Proximity Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Alert Enable
Proximity Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Hi Alert Enable
Proximity Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Alert Enable
Proximity Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Lo Alert Enable
Push Down To
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Push Down To
Continued
264
Instruction Manual
D103412X012
August 2012
Menu Structure
Rated Travel
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Rated Travel
Relay Type
TB > Configure/Setup > Detailed Setup > Instrument > Relay Type
Seat Type
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Seat Type
Setpoint
Setpoint Status
Setpoint(D)
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Shaft Stem Diameter
Simulate Active
TB > Device Diagnostics > Status > Block Error > Simulate Active
Simulate Jumper ON
TB > Device Diagnostics > Status > Self Test Status > Simulate Jumper ON
Spring Rate
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Spring Rate
TB > Configure/Setup > Detailed Setup > Instrument > Spring Rate Units
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Shutdown
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Close
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Open
Supply
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply
TB > Device Variables > Pressures > Supply
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Supply Pressure Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Supply Pressure Sensor Alert Enable
TB > Device Diagnostics > Status > Self Test Status > Supply Sensor Failure
Tag Description
TB > Configure/Setup > Detailed Setup > Instrument > Tag Description
Temperature
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature
Temperature Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert Point
Temperature Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Temperature Sensor > Temperature Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Temperature Sensors > Temperature Sensor Alert Enable
Temperature Units
TB > Configure/Setup > Detailed Setup > Instrument > Temperature Units
Travel
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel
Travel (DeChar)
Travel Accumulator
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator
TB > Device Variables > Travel Accumulator
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Deadband
Travel Count
Travel Cutoff Hi
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Cutoff Hi
Continued
265
Instruction Manual
D103412X012
Menu Structure
Travel Cutoff Lo
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Cutoff Lo
Travel Deviation
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Deadband
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Deviation Pressure Fallback
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Time
Travel Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert Point
Travel Hi Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Deadband
Travel Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert Point
Travel Hi Hi Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Deadband
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Dead Zone
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Enable
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Gain
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Limit Hi
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Limit Lo
Travel Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert Point
Travel Lo Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Deadband
Travel Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert Point
Travel Lo Lo Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Deadband
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel MLFB Gain
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Deadband
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Proportional Gain
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Alert Enable
TB > Device Diagnostics > Status > Self Test Status > Travel Sensor Hi Error
TB > Device Diagnostics > Status > Self Test Status > Travel Sensor Lo Error
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Manual Recovery
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Travel Sensor Motion
TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Shutdown
TB > Device Diagnostics > Status > Self Test Status > Travel Sensor Span Error
Travel Status
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Tuning Set
Travel Units
TB > Configure/Setup > Detailed Setup > Instrument > Travel Units
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Velocity Gain
Travel(D)
Travel/Pressure Select
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel/Pressure Select
Travel/Pressure State
TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel/Pressure State
TB > Device Variables > Travel/Pressure State
Trend
Trim Style 1
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 1
Continued
266
Instruction Manual
D103412X012
August 2012
Menu Structure
Trim Style 2
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 2
Unbalanced Area
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Unbalanced Area
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Upper Bench Set
Valve Class
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Class
Valve Manufacturer
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Manufacturer
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Model Number
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Serial Number
Valve Size
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Size
Valve Style
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Style
TB > Configure/Setup > Detailed Setup > Instrument > Zero Power Condition
TRANSDUCER BLOCK
BASIC SETUP
Top Level
Configure/Setup
Device Diagnostics
Device Variables
Configure/Setup
Basic Setup
Detailed Setup
Calibration
Basic Setup
Device Setup
Performance Tuner
267
Instruction Manual
D103412X012
Travel Tuning
TRANSDUCER BLOCK
DETAILED SETUP
Response Control
Travel Tuning
Pressure Tuning
Travel Press Control
Input Characterization
Custom Characterization Table
Outblock Selection
Top Level
Configure/Setup
Device Diagnostics
Device Variables
Configure/Setup
Basic Setup
Detailed Setup
Calibration
Detailed Setup
Transducer Block Mode
Protection
Response Control
Alerts
Instrument
Valve and Actuator
MAI Channel Map
Alert Handling
Alert Handling
PlantWeb Alert Simulate
Simulate Active Alerts
PlantWeb Alert Handling
:MAI Channel 1
:MAI Channel 2
:MAI Channel 3
:MAI Channel 4
:MAI Channel 5
:MAI Channel 6
:MAI Channel 7
:MAI Channel 8
:Travel/Pressure State
:Travel/Pressure Select
Travel Deviation Pressure Fallback
Travel Cutoff Hi
Travel Cutoff Lo
:Pressure Cutoff Open
:Pressure Cutoff Closed
:Pressure Range Hi
:Pressure Range Lo
Tag Description
Pressure Units
Temperature Units
Travel Units
Length Units
Area Units
Spring Rate Units
:Relay Type
:Zero Power Condition
:Maximum Supply Pressure
Calibration Person
Calibration Location
Calibration Date
:Last Calibration Type
Failed Active
Maint Active
Advise Active
Valve
Trim
Actuator
Reference
Reference
268
:Trim Style 1
:Trim Style 2
:Stroke Time Open
:Stroke Time Close
Pressure Tuning
Actuator
Actuator Manufacturer
Actuator Model Number
:Actuator Style
Actuator Serial Number
:Actuator Size
Actuator Fail Action
:Feedback Connection
:Travel Sensor Motion
:Lever Style
:Lever Arm Length
:Effective Area
:Air
:Upper Bench Set
:Lower Bench Set
:Nominal Supply Pressure
:Spring Rate
Elect Alerts
Configuration Alerts
Sensor Alerts
Environment Alerts
Travel Alerts
Prox Alerts
Travel History Alerts
Performance Alerts
PlantWeb Alert Enable
PlantWeb Alert Reporting
Valve
Valve Manufacturer
Valve Model Number
Valve Serial Number
Valve Style
:Valve Size
:Valve Class
:Rated Travel
:Actual Travel
:Shaft Stem Diameter
:Packing Type
:Inlet Pressure
:Outlet Pressure
Trim
:Seat Type
:Leak Class
:Port Diameter
:Port Type
:Flow Direction
:Push Down To
:Flow Tends To
:Unbalanced Area
Instruction Manual
D103412X012
August 2012
Drive Current
TRANSDUCER BLOCK
DETAILED SETUP > ALERTS
(continued on next page)
Drive Current
:Drive Current Alert
:Drive Current Alert Enable
:Drive Current Shutdown
:Drive Current Manual Recovery
:Drive Current Alert Point
:Drive Current Alert Time
Elect Alerts
Drive Current
Drive Signal
Processor Impaired
Alerts
Elect Alerts
Configuration Alerts
Sensor Alerts
Environment Alerts
Travel Alerts
Prox Alerts
Travel History Alerts
Performance Alerts
PlantWeb Alert Enable
PlantWeb Alert Reporting
Configuration Alerts
Output Block Timeout
Blocks Set to Default
Alert Key
Drive Signal
Processor Impaired
:Program Memory Alert
:Program Memory Alert Enable
:Program Memory Shutdown
:Program Memory Manual Recovery
:Static Memory Alert
:Static Memory Alert Enable
:Static Memory Shutdown
:Static Memory Manual Recovery
:Processor Alert
:Processor Alert Enable
:I/O Processor Alert
:I/O Processor Alert Enable
:I/O Processor Shutdown
:I/O Processor Man Recovery
Drive Signal
:Drive Signal Alert
:Drive Signal Alert Enable
Sensor Alerts
Travel Sensor
Pressure Sensors
Pressure Fallback
Temperature Sensor
Travel Sensor
Pressure Fallback
:Pressure Fallback Alert
:Pressure Fallback Alert Enable
Temperature Sensor
:Temperature Sensor Alert
:Temperature Sensor Alert Enable
Environment Alerts
Supply Pressure
Temperature Limit
Temperature Limit
Temperature
:Temperature Hi Alert
:Temperature Hi Alert Enable
Temperature Hi Alert Point
:Temperature Lo Alert
:Temperature Lo Alert Enable
:Temperature Lo Alert Point
Supply Pressure
:Supply
:Supply Pressure Hi Alert
:Supply Pressure Hi Alert Enable
Supply Pressure Hi Alert Point
:Supply Pressure Lo Alert
:Supply Pressure Lo Alert Enable
:Supply Pressure Lo Alert Point
269
Instruction Manual
D103412X012
TRANSDUCER BLOCK
DETAILED SETUP > ALERTS
Alerts
Travel Open
Elect Alerts
Configuration Alerts
Sensor Alerts
Environment Alerts
Travel Alerts
Prox Alerts
Travel History Alerts
Performance Alerts
PlantWeb Alert Enable
PlantWeb Alert Reporting
Travel Alerts
Travel Deviation
:Travel Target
:Travel
Travel Deviation
Travel Limit
Travel Hi/Lo
Travel Deviation
:Travel Deviation Alert
:Travel Deviation Alert Enable
:Travel Deviation Alert Point
:Travel Deviation Time
:Travel Deviation Deadband
Travel Limit
:Travel Hi Hi Alert
:Travel Hi Hi Alert Enable
:Travel Hi Hi Alert Point
:Travel Hi Hi Deadband
:Travel Lo Lo Alert
:Travel Lo Lo Alert Enable
:Travel Lo Lo Alert Point
:Travel Lo Lo Deadband
Prox Alerts
:Travel
Travel Open
Travel Closed
Proximity
Travel Hi/Lo
:Travel Hi Alert
:Travel Hi Alert Enable
:Travel Hi Alert Point
:Travel Hi Deadband
:Travel Lo Alert
:Travel Lo Alert Enable
:Travel Lo Alert Point
:Travel Lo Deadband
Proximity
:Proximity Hi Hi Alert
:Proximity Hi Hi Alert Enable
:Proximity Hi Alert
:Proximity Hi Alert Enable
:Proximity Lo Alert
:Proximity Lo Alert Enable
:Proximity Lo Lo Alert
:Proximity Lo Lo Alert Enable
Travel Closed
:Travel Closed Alert
:Travel Closed Alert Enable
:Travel Closed Alert Point
:Travel Closed Deadband
Failed Enable
Maintenance Enable
Advise Enable
Travel History Alerts
Cycle Counter
Travel Accumulator
Performance Alerts
:PD Inside Status
:PD Run
Performance Critical
Performance Reduced
Performance Information
Cycle Counter
:Cycle Counter Alert
:Cycle Counter Alert Enable
:Cycle Counter Alert Point
:Cycle Counter Deadband
Travel Accumulator
Travel Accumulator
:Travel Accumulator Alert
:Travel Accumulator Alert Enable
:Travel Accumulator Alert Point
:Travel Accumulator Deadband
Performance Information
Performance Information Alert
Performance Information Alert Enable
270
Cycle Counter
Performance Reduced
Performance Critical
Instruction Manual
D103412X012
August 2012
TRANSDUCER BLOCK
CALIBRATION
Top Level
Configure/Setup
Device Diagnostics
Device Variables
Configure/Setup
Basic Setup
Detailed Setup
Calibration
Calibration
Auto Calibration
Manual Calibration
Relay
Supply Pressure
Pressure A
Pressure B
TRANSDUCER BLOCK
DEVICE DIAGNOSTICS
Status
Top Level
Configure/Setup
Device Diagnostics
Device Variables
Device Diagnostics
Active PlantWeb Alerts
Alert Conditions
Status
Device Record
Stroke Valve
Trend
Block Error
Block Configuration Error
Simulate Active
Lost Static Data
Device Needs Maintenance Now
Out of Service
Device Record
:Maximum Recorded Temperature
:Maximum Recorded Temperature Time
:Minimum Recorded Temperature
:Minimum Recorded Temperature Time
:Maximum Recorded Supply Pressure
:Maximum Recorded Supply Pressure Time
:Minimum Recorded Supply Pressure
:Minimum Recorded Supply Pressure Time
TRANSDUCER BLOCK
DEVICE VARIABLES
AO Control - PreChar
Top Level
Device Variables
Configure/Setup
Device Diagnostics
Device Variables
:Setpoint
:Setpoint Status
:Travel (DeChar)
AO Control - PostChar
:Travel Target
:Travel
:Travel Status
DO Control
:Setpoint(D)
:Travel(D)
Pressures
:Supply
:Pressure A
:Pressure B
:A Minus B
271
Instruction Manual
D103412X012
Menu Structure
Alert Key
RB > Configure/Setup > Alarm Handling > Block Alarm Automatically Acknowledge
Confirm Time
DD Information
Device ID
RB > Configure/Setup > Identification > Device ID or RB > Device Variables > Instrument > Identification > Device ID
Device Revision
RB > Configure/Setup > Version > Device Revision or RB > Device Variables > Instrument > Version > Device Revision
Device State
Device Type
RB > Configure/Setup > Identification > Device Type or RB > Device Variables > Instrument > Identification > Device Type
Diagnostics Options
RB > Configure/Setup > Alarm Handling > Discrete Alarm Automatically Acknowledge
RB > Configure/Setup > Identification > Elect S/N or RB > Device Variables > Instrument > Identification > Electronics Serial Number
RB > Configure/Setup > Identification > Factory S/N or RB > Device Variables > Instrument > Identification > Factory Serial Number
Fault State
Features Available
RB > Configure/Setup > Options > Features Available or RB > Device Variables > Options > Features Available
Features Selected
RB > Configure/Setup > Identification > Field S/N or RB > Device Variables > Instrument > Identification > Field Serial Number
Firmware Revision
RB > Configure/Setup > Version > Firmware Revision or RB > Device Variables > Instrument > Version > Firmware Revision
RB > Configure/Setup > Options > Function Block Options or RB > Device Variables > Options > Function Block Options
Hardware Revision
RB > Configure/Setup > Version > Hardware Revision or RB > Device Variables > Instrument > Version > Hardware Revision
ITK Version
RB > Configure/Setup > Version > ITK Version or RB > Device Variables > Instrument > Version > ITK Version
Limit Notify
Manufacturer
RB > Configure/Setup > Identification > Manufacturer or RB > Device Variables > Instrument > Identification > Manufacturer
Maximum Notify
Miscellaneous Options
RB > Configure/Setup > Options >Miscellaneous Options or RB > Device Variables > Options >Miscellaneous Options
RB > Configure/Setup > Communication Time Out > Shed Remote Cascade
RB > Configure/Setup > Communication Time Out > Shed Remote Out
RB > Configure/Setup > Version > Standby Software Revision or RB > Device Variables > Instrument > Version > Standby Software
Revision
Strategy
RB > Configure/Setup > Identification > Strategy or RB > Device Variables > Instrument > Identification > Strategy
Tag Description
RB > Configure/Setup > Identification > Tag Description or RB > Device Variables > Instrument > Identification > Tag Description
RB > Device Diagnostics > Write Lock > Write Alarm: Alarm State
Write Lock
RB > Configure/Setup > Write Lock > Write Lock or RB > Device Diagnostics > Write Lock > Write Lock
Write Priority
272
Instruction Manual
D103412X012
August 2012
Write Lock
Write Priority
Configure/Setup
Device Diagnostics
Device Variables
Options
Device Revision
Firmware Revision
Standby Firmware Revision
Hardware Rev
ITK Version
Identification
Device ID
Electronics Serial Number
Factory Serial Number
Field Serial Number
Tag Description
Strategy
Manufacturer
Device Type
Diagnostics Options
Features Available
Alert Key
Confirm Time
Limit Notify
Maximum Notify
Block Alm Disabled
Block Alarm Auto Acknowledge
Disc Alm Disabled
Discrete Alarm Auto Acknowledge
Reports
Fault State
Soft W Lock
Multibit Alarm (BitAlarm) Support
Maintenance
Restart Actions
Fault State
Set Fault State
Clear Fault State
RESOURCE BLOCK
DEVICE VARIABLES
Top Level
Instrument
Configure/Setup
Device Diagnostics
Device Variables
Device Variables
Instrument
Options
DD Information
Options
Diagnostics Options
Function Block Options
Miscellaneous Options
Features Available
Features Selected
Reports
Fault State
Soft W Lock
Multibit Alarm (BitAlarm) Support
Resource Block Error
Configure/Setup
Device Diagnostics
Device Variables
Firmware Download
Travel Control Capable
Pressure Control Capable
Pressure Fallback Capable
Alarm Handling
Device Diagnostics
Top Level
Miscellaneous Options
Diagnostics Options
Function Block Options
Miscellaneous Options
Features Available
Features Selected
Version
RESOURCE BLOCK
DEVICE DIAGNOSTICS
AO
DO
AI
DI
PID
IS
OS
MAI
Comm Timeout
Configure/Setup
Top Level
Function
Block Options
Write Lock
RESOURCE BLOCK
CONFIGURE/SETUP
Identification
Version
Function
Block Options
AO
DO
AI
DI
PID
IS
OS
MAI
Features Available
Miscellaneous Options
Reports
Fault State
Soft W Lock
Multibit Alarm (BitAlarm) Support
Firmware Download
Travel Control Capable
Pressure Control Capable
Pressure Fallback Capable
Other
Block Configuration Error
Simulate Active
Device Needs Maintenance Soon
Memory Failure
Lost Static Data
Lost NV Data
Device Needs Maintenance Now
Power Up
Out of Service
Write Lock
Write Alarm Alarm State
Write Lock
Block Alarm
Block Alarm Alarm State
Block Alarm Unacknowledged
Identification
Device ID
Electronics Serial Number
Factory Serial Number
Field Serial Number
Tag Description
Strategy
Manufacturer
Device Type
Version
Device Revision
Firmware Revision
Standby Firmware Revision
Hardware Rev
ITK Version
273
274
Instruction Manual
D103412X012
Instruction Manual
D103412X012
PlantWeb Alerts
August 2012
PlantWeb Alerts
Some instrument alert conditions can also be used to trigger PlantWeb alerts that will be reported in Failed,
Maintenance or Advisory categories, as configured by the user. PlantWeb alerts, when enabled, can participate in the
DeltaV alarm interface tools such as the alarm banner, alarm list and alarm summary. For specific information on
setting up PlantWeb Alerts in a DeltaV system, refer to the PlantWeb Alerts section in Appendix F.
When a PlantWeb alert occurs, the DVC6200f sends an event notification and waits a specified period of time for an
acknowledgment to be received. This occurs even if the condition that caused the alert no longer exists. If the
acknowledgment is not received within the prespecified timeout period, the event notification is retransmitted. This
reduces the possibility of alert messages getting lost.
Alert Handling
Alert handling is diagrammed in figure C1. There are two ways of seeing PlantWeb alerts. One way is to see if the
instrument alert condition causing a PlantWeb alert is detected. The second is to view alerts reported to the system
operator console. For a PlantWeb alert to be active, it has to pass four tests. The first is to check if the Instrument alert
condition is enabled. If a condition is not enabled, the instrument does not check for the alert condition.
Second, the condition that will cause an alert must exist. For example, the current travel is above the Travel Limit Hi
Alert Point.
Third, the corresponding PlantWeb alert must be enabled in one or more of the three categories: Failed, Maintenance
or Advise.
Fourth, the transducer block mode must be correct. See table C1.
Note
Additional details on setting up and using Instrument Alerts can be found on page 69 of this manual.
275
Instruction Manual
PlantWeb Alerts
August 2012
D103412X012
START
"
ALERT
CONDITION
ENABLED?
Enable Instrument
Alert Condition in
the Transducer
Block
Yes
"
LIMITS EXCEEDED TO
CAUSE ALERT?
No
Enable PlantWeb
Alert in the
Transducer Block
Yes INSTRUMENT
" ALERT
CONDITION
ACTIVE
Yes
"
Yes
"
PLANTWEB
ALERT
ENABLED?
No
No
Yes
PLANTWEB
" ALERT ACTIVE
No
NO ACTIVE
PLANTWEB ALERT
1
TRANSDUCER
BLOCK MODE
AUTO
B
NO ACTIVE INSTRUMENT
ALERT CONDITION
No
REPORT
ALERTS?
Yes
B
No
Select Reports
Supported from
FEATURE_SEL in the
Resource Block
PRIORITY
>1?
B Yes
B
Instrument Alert
Conditions active,
but not reported
NOTE:
1
CERTAIN
PLANTWEB ALERTS ARE MODEBASED.
SEE TABLE C1 FOR DETAILS.
276
PlantWeb Alert
Drive Current
AUTO
Drive Signal
AUTO
Processor Impaired
Any Mode
Any Mode
Any Mode
Travel Sensor
AUTO
Any Mode
Any Mode
Temperature Sensor
Any Mode
Supply Pressure
AUTO
Temperature Limit
AUTO
Travel Deviation
AUTO
Travel Limit
AUTO
Cycle Counter
AUTO
Travel Accumulator
AUTO
Performance Critical
AUTO
Performance Reduced
AUTO
Performance Information
AUTO
Pressure Fallback
AUTO
Yes
SUPPRESS
REPORTINGAL
ERT
CONDITION?
B No
PLANTWEB
ALERTS
REPORTED
Suppress Alert
Condition Reporting
with Alarm Suppress
Parameters in
Transducer Block
Instruction Manual
D103412X012
PlantWeb Alerts
August 2012
Alert Reporting
For PlantWeb alerts to be reported to the operator console, they must pass four tests:
Alerts must be active
Reports must be selected in Feature Select
Alert priority must be greater than 1
Reporting must not be suppressed for those conditions that caused active alerts.
Features Selected in the Resource block determines if reporting by the instrument is supported. Refer to page 47 for
additional information on Features Selected.
Failed Priority (FAILED_PRI [68]), Maintenance Priority (MAINT_PRI [69]), and Advise Priority (ADVISE_PRI [70])
determine the PlantWeb alert priorities. Although 16 priorities are available only three are actually meaningful for
PlantWeb alerts. If the priority is 0, no reporting occurs. If the priority is 1, reporting is simulated within the
instrument, but the alert is not actually reported over the bus. The alert condition is reported for priorities 2 through
15, with the higher priorities taking precedence over the lower priorities.
Failed Suppress (FAILED_MASK [65]), Maintenance Suppress (MAINT_MASK [66]), and Advise Suppress (ADVISE_MASK
[67]) determine which of the alert conditions are suppressed so that they are not reported.
277
Instruction Manual
PlantWeb Alerts
August 2012
D103412X012
Alert Condition
(Default)
Drive Current
(Enabled)
Related Parameters
(Default)
Drive Signal
(Electronics)
(Maintenance)
Drive Signal
(Enabled)
Processor Impaired
(Electronics)
(Maintenance)
Program Memory
(Enabled)
Static Memory
(Enabled)
Processor
(Enabled)
I/O Processor
(Enabled)
Output Block
Timeout
(Disabled)
None
Shutdown Alert
(Configuration)
(Maintenance)
N/A
None
-Continued-
278
Instruction Manual
PlantWeb Alerts
D103412X012
August 2012
Alert Condition
(Default)
Related Parameters
(Default)
Travel Sensor
(Sensors)
(Failed)
Travel Sensor
(Enabled)
Port A Pressure
Sensor (Enabled)
Port B Pressure
Sensor (Enabled)
None
None
Temperature Sensor
(Sensors)
(Advisory)
Temperature Sensor
(Enabled)
None
Pressure Fallback
(Enabled)
None
Supply Pressure
(Environment)
(Maintenance)
Supply Press Low
(Enabled)
-Continued-
279
Instruction Manual
PlantWeb Alerts
August 2012
D103412X012
Alert Condition
(Default)
Related Parameters
(Default)
Temperature High
(Enabled)
Temperature Limit
(Environment)
(Advisory)
Temperature Low
(Enabled)
Travel Deviation
(Travel)
(Maintenance)
Travel Limit
(Travel)
(Advisory)
N/A
(Travel)
(N/A)
N/A
(Proximity)
(N/A)
Travel Deviation
(Enabled)
Travel Limit Hi Hi
(Disabled)
Travel Limit Lo Lo
(Disabled)
Travel Limit Hi
(Disabled)
Travel Limit Lo
(Disabled)
Travel Open
(Disabled)
Travel Closed
(Disabled)
Proximity Hi Hi
(Disabled)
Proximity Hi
(Disabled)
Proximity Lo
(Disabled)
Proximity Lo Lo
(Disabled)
Cycle Counter
(Travel History)
(Maintenance)
Cycle Counter
(Disabled)
280
Instruction Manual
PlantWeb Alerts
D103412X012
August 2012
Alert Condition
(Default)
Related Parameters
(Default)
Travel Accumulator
(Travel History)
(Maintenance)
Travel Accumulator
(Disabled)
Performance Critical
(Performance)
(Failed)
Performance Critical
(Enabled)
None
Performance Reduced
(Performance)
(Maintenance)
Performance
Reduced
(Enabled)
None
Performance Information
(Performance)
(Advisory)
Performance
Information
(Enabled)
Performance Information
based on continuous PD tests
internal to the instrument.
None
Alert Condition
(Default)
Effect on Valve/Instrument
Recommended
Action
Help
Drive Current
(Electronics)
(Failed)
Drive Current
(Enabled)
Drive Signal
(Electronics)
(Maintenance)
Drive Signal
(Enabled)
Check instrument
pneumatics
281
Instruction Manual
PlantWeb Alerts
August 2012
D103412X012
Alert Condition
(Default)
Effect on Valve/Instrument
Recommended
Action
Program Memory
(Enabled)
Replace PWB
assembly
Static Memory
(Enabled)
Processor
(Enabled)
I/O Processor
(Enabled)
Output Block
Timeout
(Disabled)
Check Output
Block
Help
1) Download the
control schedule from
the host configuration
device.
2) Make sure the Time
Out Alert Point is
greater than the block
execution schedule.
This alert should only
be utilized in very
critical loops where
execution time is
critical.
Blocks Set to Default
(Configuration)
(Failed)
Blocks Set to
Default
(Enabled)
Download device
configuration
Shutdown Alert
(Configuration)
(Failed)
N/A
-Continued-
282
Same as the
configured Self
Test Shutdown.
Instruction Manual
PlantWeb Alerts
D103412X012
August 2012
Alert Condition
(Default)
Travel Sensor
(Enabled)
Effect on Valve/Instrument
Recommended
Action
Check mounting
and linkage
Help
Travel feedback value is
outside expected
limits. If this problem
occurs during
instrument setup, the
most likely cause is
faulty mounting or
improper adjustment
of the travel sensor. If
this problem occurs
during normal
operation, the most
likely cause is a failure
of the travel sensor.
To correct,
1) Insure proper
mounting and linkage
adjustment.
2) Inspect and test
travel sensor
3) Toggle the
transducer target
mode.
If the problem persists,
replace the printed
wiring board (PWB)
assembly.
Port A Pressure
Sensor (Enabled)
Port B Pressure
Sensor (Enabled)
Supply Press Sensor
(Sensors)
(Advisory)
Supply Press
Sensor (Enabled)
Confirm proper
air supply
Confirm proper
air supply
Temperature Sensor
(Sensors)
(Advisory)
Temperature
Sensor (Enabled)
Replace PWB
assembly.
The temperature
sensor onboard the
device has failed or the
unit has been exposed
to an temperature
extreme beyond the
recommended limits.
-Continued-
283
Instruction Manual
PlantWeb Alerts
August 2012
D103412X012
Alert Condition
(Default)
Effect on Valve/Instrument
Recommended
Action
Help
Pressure Fallback
(Sensors)
(Maintenance)
Pressure Fallback
(Enabled)
Check instrument
feedback linkage
and travel sensor.
Supply Pressure
(Environment)
(Maintenance)
Confirm proper
air supply.
Temperature High
(Enabled)
Temperature Low
(Enabled)
Temperature Limit
(Environment)
(Advisory)
-Continued-
284
The instrument
temperature has
exceeded the user
configured high
temperature limit.
Operation of the
instrument above the
rated temperature may
degrade instrument
components. This may
affect instrument
performance and/or
reduce the life of the
instrument.
The instrument
temperature has
dropped below the user
configured low
temperature limit.
Operation of the
instrument below the
rated temperature may
degrade instrument
components. This may
affect instrument
performance and/or
reduce the life of the
instrument.
Instruction Manual
PlantWeb Alerts
D103412X012
August 2012
Alert Condition
(Default)
Travel Deviation
(Enabled)
Effect on Valve/Instrument
Recommended
Action
Check valve
friction, supply
air, instrument
tuning
Help
The valve travel is not
following setpoint.
Check operation of the
valve and instrument.
Possible items include;
sticking valve, low
supply pressure,
broken feedback
linkage, instrument
pneumatic
components, actuator,
instrument tubing,
poor instrument
tuning, etc.
Test the control valve
assembly for proper
operation. ValveLink
software diagnostics
can be used for this
purpose.
Travel Limit
(Travel)
(Advisory)
Travel Limit Hi Hi
(Disabled)
None
Check process
loop
Travel Limit Lo Lo
(Disabled)
None
Check process
loop
N/A
(Travel)
(N/A)
Travel Limit Hi
(Disabled)
None
Check process
loop
Travel Limit Lo
(Disabled)
None
Check process
loop
Travel Open
(Disabled)
None
Check process
loop
Travel Closed
(Disabled)
None
Check process
loop
Proximity Hi Hi
(Disabled)
None
Check process
loop
N/A
(Proximity)
(N/A)
Proximity Hi
(Disabled)
None
Proximity Lo
(Disabled)
None
Proximity Lo Lo
(Disabled)
None
Cycle Counter
(Travel History)
(Maintenance)
Cycle Counter
(Disabled)
None
Perform periodic
maintenance
Travel Accumulator
(Travel History)
(Maintenance)
Travel
Accumulator
(Disabled)
None
Perform periodic
maintenance
-Continued-
285
Instruction Manual
PlantWeb Alerts
August 2012
D103412X012
Alert Condition
(Default)
Effect on Valve/Instrument
Recommended
Action
Help
Performance Critical
(Performance)
(Failed)
Performance
Critical
(Enabled)
Onboard diagnostics
have detected a critical
performance issue that
may result in loss of
control or severe
reduction in control
performance. Check or
replace the component
indicated in the
possible cause detail.
Performance Reduced
(Performance)
(Maintenance
Performance
Reduced (Enabled)
Onboard diagnostics
have detected a
performance issue that
has reduced control
performance. Check or
replace the component
indicated in the
possible cause detail.
Performance Information
(Performance)
(Advisory)
Performance
Information
(Enabled)
Performance Information
based on continuous PD tests
internal to the instrument.
No action
required.
Onboard diagnostics
have detected an
abnormal performance
condition. No
immediate action
required.
Enabled
Not Enabled
Transducer Mode,
Actual
Active PlantWeb
Alarms
AO / DO
PV Status
AO / DO PV
Substatus
OOS
Bad
Device Failure
Constant
Man
Bad
Nonspecific
Constant
Auto
Fail
Uncertain
Subnormal
See table C5
Auto
Maint, no Fail
Uncertain
Nonspecific
See table C5
Auto
Good
Advisory
See table C5
Auto
None
Good
NonSpecific
See table C5
OOS
Bad
Device Failure
Constant
Man
Bad
NonSpecific
Constant
Auto
Fail
Good
NonSpecific
See table C5
Auto
Maint, no Fail
Good
NonSpecific
See table C5
Auto
Good
NonSpecific
See table C5
Auto
None
Good
NonSpecific
See table C5
NOTES:
X = No Effect
1. PV limit substatus reflects only READBACK limit substatus. SP limit substatus reflects only out block rate limits.
Transducer Mode
In Cutoff Region
Rate Limited
Limit SubStatus
AO, DO
OOS
Constant
AO, DO
MAN
Constant
AO
AUTO
High
High Limited
AO
AUTO
Low
Low Limited
AO
AUTO
High
High Limited
AO
AUTO
Low
Low Limited
AO
AUTO
None
None
Not Limited
DO
AUTO
High
High Limited
DO
AUTO
Low
Low Limited
DO
AUTO
None
Not Limited
NOTE: X = No Effect
286
Instruction Manual
D103412X012
August 2012
Function Blocks
Function blocks within the fieldbus device perform the various functions required for process control. Because each
system is different, the mix and configuration of functions are different. Therefore, the Fieldbus Foundation has
designed a range of function blocks, each addressing a different need: Analog Input Block (AI), Multiple Analog Input
(MAI), Discrete Input Block (DI), Manual Loader Block (ML), Bias/Gain Station Block (BG), Control Selector Block (CS), P,
PD Controller Block (PD), PID, PI, I Controller Block (PID), Ratio Station Block (RA), Analog Output Block (AO) and
Discrete Output Block (DO).
Function blocks perform process control functions, such as analog input (AI) and analog output (AO) functions as well
as proportionalintegralderivative (PID) functions. The standard function blocks provide a common structure for
defining function block inputs, outputs, control parameters, events, alarms, and modes, and combining them into a
process that can be implemented within a single device or over the fieldbus network. This simplifies the identification
of characteristics that are common to function blocks.
The Fieldbus Foundation has established the function blocks by defining a set of parameters used in all function blocks
called universal parameters. The Fieldbus Foundation has also defined a standard set of function block classes, such as
input, output, control, and calculation blocks. Each of these classes have a set of parameters established for it.
Additionally, they have published definitions for transducer blocks commonly used with standard function blocks.
Examples include temperature, pressure, level, and flow transducer blocks.
Fieldbus Foundation specifications and definitions allow vendors to add their own, extended parameters, as well as
their own algorithms. This approach permits extending function block definitions as new requirements are discovered
and as technology advances.
Each block has a tag name. Service personnel need only know the tag name of the block to access or change the
appropriate block parameters.
Input events may affect the operation of the algorithm. An execution control function regulates the receipt of input
events and the generation of output events during execution of the algorithm. Upon completion of the algorithm, the
data internal to the block is saved for use in the next execution, and the output data is snapped, releasing it for use by
other function blocks.
Once the inputs are snapped, the algorithm operates on them, generating outputs as it progresses. Algorithm
executions are controlled through the setting of internal parameters. Internal parameters do not appear as normal
input and output parameters. However, they may be accessed and modified remotely, as specified by the function
block.
287
Instruction Manual
D103412X012
Figure D1 illustrates the internal structure of a function block. When execution begins, input parameter values from
other blocks are snappedin by the block. The input snap process ensures that these values do not change during the
block execution. New values received for these parameters do not affect the snapped values and will not be used by
the function block during the current execution.
Function blocks are also capable of performing shortterm data collection and storage for reviewing their behavior.
InstrumentSpecific Blocks
In addition to function blocks, fieldbus devices contain two other block types to support the function blocks. These are
the resource block and the transducer block. The resource block contains the hardware specific characteristics
associated with a device. Transducer blocks couple the function blocks to local input/output functions.
Figure D1. Function Block Internal Structure
Input Parameter
Linkages
Input
Events
Execution Control
Input
Snap
Processing
Algorithm
status
Output
Events
Output
Snap
Output
Parameter
Linkages
status
B2711
Resource Blocks
The resource block contains hardware specific characteristics associated with the device; it has no input or output
parameters. The algorithm within a resource block monitors and controls the general operation of the physical device
hardware. The execution of this algorithm is dependent on the characteristics of the physical device, as defined by the
manufacturer. As a result of this activity, the algorithm may cause the generation of events. There is only one resource
block defined for a device. For example, placing the resource block in Out of Service mode stops all function block
execution, by setting their modes to Out of Service as well. The actual mode of the function blocks is changed to Out
of Service, but the function block target modes will not change. Placing the resource block in the Out of Service mode
does not affect the mode of the transducer block.
Transducer Blocks
Transducer blocks connect function blocks to local input/output functions. They read sensor hardware and write to
effector (actuator) hardware. This permits the transducer block to execute as frequently as necessary to obtain good
data from sensors and ensure proper writes to the actuator without burdening the function blocks that use the data.
The transducer block also isolates the function block from the specific characteristics of the physical I/O.
288
Instruction Manual
D103412X012
August 2012
Block Modes
All blocks have modes. The mode determines the source of the set point, the destination of the output, how the block
executes, and the relationship between setpoint and output. The block mode is determined by the Block Mode
parameter. It is a structured parameter composed of the attributes actual, target, permitted, and normal. The
following defines each of the attributes.
Target modeThe Target mode is the mode requested by the user or host system. Only one mode is allowed to be
set and it must be a permitted mode as defined by the permitted attribute of the mode parameter.
Actual modeThis is the current mode of the block. The actual mode may differ from the target mode due to
operating conditions of the block.
Permitted modeThe permitted mode defines the modes allowed for the block. This is set by the user or host
system but is restricted by the instrument to modes supported by the instrument for the particular block. Any
change request to the Target or Normal attribute is checked against the permitted attribute to ensure the
requested mode is permitted.
When setting the Permitted mode, there is no check against any of the other attributes (Normal or Target modes).
Therefore, the normal or target mode attributes may have a value that is not permitted because the permitted
attribute was modified after the Normal or Target mode was set. This will have no effect on the instrument until the
user attempts to modify the Target or Normal mode. At this time these attributes are tested against the Permitted
modes, thus the user cannot change the Normal or Target modes to what was formerly permitted.
Normal modeThe normal mode is the mode the block should be in during normal operating conditions. The
normal mode is set by the user or host system and can only be set to a permitted mode (see permitted mode). The
user or host system can compare the actual mode to the normal mode and, based on the results, determine if the
block is operating normally.
Table D1 lists the modes supported by each block contained in the digital valve controller.
Table D1. DVC6200f Block Modes
Block
Resource
Transducer
AO
PID
ISEL
OS
AI
MAI
DO
DI
Changing the block mode requires accessing the Block Mode parameter. For information on using the host system to
change the block mode via this parameter, see the appropriate host documentation.
289
Instruction Manual
D103412X012
Note
A downstream block changing to Out of Service impacts the mode of the upstream block. Refer to the block hierarchy in
figure D2.
RESOURCE BLOCK
PID BLOCK
ANALOG OUTPUT
(AO) BLOCK
TRANSDUCER
BLOCK
NOTES:
1.CHANGING THE RESOURCE BLOCK TO OUT OF SERVICE CHANGES ALL FUNCTION BLOCKS
TO OUT OF SERVICE, BUT DOES NOT AFFECT THE TRANSDUCER BLOCK.
2.CHANGING A DOWNSTREAM BLOCK TO OUT OF SERVICE AFFECTS THE UP STREAM BLOCK.
FOR EXAMPLE: WHEN THE TRANSDUCER BLOCK IS OUT OF SERVICE, THE AO BLOCK MODE
WILL CHANGE TO IMAN (INITIALIZE MANUAL).
Note
There is no mode associated with the FOUNDATION fieldbus Loop. Mode is dependent on the blocks within the Loop.
Explanation of Modes
Out of Service (OOS)The functions performed by the block are not executed. If the block has any outputs, these
typically do not update and the status of any values passed to downstream blocks will be BAD. To make changes to
some of the parameters in a block requires that the block be Out of Service.
Initialization Manual (IMan)Only the AO, DO, OS and PID blocks support this mode. When one of these blocks
detects a loss of a correct path to the downstream block (such as when the downstream block is in the OOS, Man, or
LO mode), it enters the IMan mode. For example, when the transducer block enters the OOS mode, the AO block
enters the IMan mode.
Local Override (LO)Only the AO, DO, and PID blocks support this mode. If the PID block enters the LO mode, the
block output follows the tracking value (TRK_VAL), if external tracking is enabled by TRK_IN_D. In the AO and DO
block, the block enters LO mode when the block detects that fault state is active. In this case, the output is determined
by the selection for I/O_OPTS.
Manual (Man)If the data status of a function block's input is bad or its target mode is Man, the block enters the
manual mode. In this mode, the function block does not update its OUT value. If the target is Man, the user may write
a desired value to the output.
Automatic (Auto)The block performs the specified calculations based on the local set point and outputs the result,
independently without interfacing with another block. The user can write to the set point of a block in this mode. Any
block outputs continue to update.
Cascade (Cas)The block performs the specified calculations based on the set point from another block via the
cascade input parameter and outputs the result. Any block outputs continue to update.
290
Instruction Manual
D103412X012
August 2012
Remote Output (ROut)The block outputs are set to the value of the remote output parameter that is written by a
host computer or others. To prevent a sudden change in output, the block's calculations are initialized when a change
in mode occurs.
Remote Cascade (RCas)The block performs the specified calculations based on a set point from a host computer or
others via the remote cascade input and outputs the result. If the block has any outputs, these continue to update.
Blocks
TB(1)
PID
AO
---
OOS
OOS
---
IMan
Manual
---
Auto
Auto
Auto
Cas
Auto
Cas
Auto
1.TB=Transducer Block
The respective modes to which each block should enter upon occurrence of a communication error and at a restart,
and the handling of signals in each mode may be defined in the block's option parameters such as IO_OPTS and
STATUS_OPTS. For details, see the detailed descriptions of each function block.
Device Descriptions
Device Descriptions are specified definitions that are associated with blocks. Device descriptions provide for the
definition and description of blocks and their parameters.
Device descriptions may also include a set of processing routines called Methods. Methods provide a procedure for
accessing and manipulating a series of parameters within a device, such as for setup and calibration. Methods are used
for a variety of functions including automatic calibration, setting protection and setting up the instrument. These
Methods are a predetermined sequence of steps for information required to setup, calibrate, and perform other
functions on the instrument.
291
Instruction Manual
D103412X012
Substatus
Good (NC)
Nonspecific
Good (NC)
Good (NC)
Good (NC)
Good (NC)
Good (NC)
Good (NC)
Uncertain
Nonspecific
Uncertain
Uncertain
Substitute/Manual Entry
Uncertain
Initial Value
Uncertain
Uncertain
Uncertain
Subnormal
Good (C)
Nonspecific
Good (C)
Initialization Acknowledge
Good (C)
Initialization Request
Good (C)
Not Invited
Good (C)
Not Selected
Good (C)
Local Override
Good (C)
Good (C)
Bad
Nonspecific
Bad
Configuration Error
Bad
Not Connected
Bad
Device Failure
Bad
Sensor Failure
Bad
Bad
No Comm, no LUV
Bad
(NC)=(Noncascade)
Out of Service
(C)= (Cascade)
Status Propagation
The transducer block accepts the output from the AO block or DO block if the output parameter status is Good
(Noncascade) or Good (Cascade). When the AO or DO block is Out of Service the output parameter status is Bad. In
this case, the transducer block holds the last value.
If the transducer block actual mode is Out of Service, the AO block READBACK parameter status is Bad-Out of Service.
This could be caused by a Failed Alert. If a Failed Alert is active, the block error parameter (parameter name
BLOCK_ERR) for the Resource block will indicate Device Needs Maintenance Now. For more information on the
Resource and Transducer block error indications, refer to the Viewing Device Information section of this manual.
If the transducer block is functioning correctly the AO block READBACK parameter status is Good
(Noncascade)-Nonspecific. If a Maintenance or Advisory alert is active the substatus will reflect a Unacknowledged or
Active advisory alert. When a Maintenance or Advisory alert is active, the block error for the resource block indicates
Device Needs Maintenance Soon.
Limit Propagation
The following describes limit propagation:
292
Instruction Manual
D103412X012
August 2012
AO Block
If the valve position is below the low cutoff value, the AO block READBACK status limit is LOW_LIMITED.
If the valve position is above the high cutoff value, the AO block READBACK status limit is HIGH_LIMITED.
If the transducer block actual mode is Auto and the above conditions are not true, the AO block READBACK status
limit is NOT_LIMITED.
If the transducer block actual mode is Out of Service, the AO block READBACK status limit is CONSTANT.
DO Block
If the transducer block actual mode is Auto, the DO block READBACK_D status is NOT_LIMITED.
If the transducer block actual mode is Out of Service, the DO block READBACK_D status is CONSTANT.
The control strategy should be configured to monitor the Analog Output block status and take action where
appropriate when the status is no longer Good.
Network Communication
Figure D3 illustrates a simple fieldbus network consisting of a single segment.
Figure D3. Simple SingleLink Fieldbus Network
LAS
Fieldbus Segment
LINK MASTER
BASIC DEVICES
LAS = Link Active Scheduler
B27121
Device Addressing
Fieldbus uses addresses between 0 and 255. Addresses 0 through 15 are typically reserved for group addressing and
for use by the data link layer. If there are two or more devices with the same address, the first device to start will use its
programmed address. Each of the other devices will be given one of four temporary addresses between 248 and 251. If
a temporary address is not available, the device will be unavailable until a temporary address becomes available.
Commission devices use addresses 20-35, and standby devices use addresses 232247.
293
Instruction Manual
August 2012
D103412X012
Device Communication
Scheduled Transfers
Information is transferred between devices over the fieldbus using three different types of communication:
Publisher/Subscriber: This type of communication is used to transfer critical process loop data, such as the process
variable. The data producers (publishers) post the data in a buffer that is transmitted to the subscriber (S), when the
publisher is issued the Compel Data (CD) message from the LAS. The buffer contains only one copy of the data. New
data completely overwrites previous data. Updates to published data are transferred simultaneously to all
subscribers in a single broadcast. Transfers of this type are scheduled on a precisely periodic basis.
Figure D4 diagrams the method of scheduled data transfer. Scheduled data transfers are typically used for the regular
cyclic transfer of process loop data between devices on the fieldbus. Scheduled transfers use publisher/subscriber type
of reporting for data transfer. The Link Active Scheduler maintains a list of transmit times for all publishers in all devices
that need to be cyclically transmitted. When it is time for a device to publish data, the LAS issues a Compel Data (CD)
message to the device. Upon receipt of the CD, the device broadcasts or publishes the data to all devices on the
fieldbus. Any device that is configured to receive the data is called a subscriber.
294
Instruction Manual
D103412X012
August 2012
Schedule
X
Y
Z
DT(A )
CD (X, A)
Device X
Device Y
Device Z
B27131
Unscheduled Transfers
Figure D5 diagrams an unscheduled transfer. Unscheduled transfers are used for things like userinitiated changes,
including set point changes, mode changes, tuning changes, and upload/download. Unscheduled transfers use either
report distribution or client/server type of reporting for transferring data.
Figure D5. Unscheduled Data Transfer
Host System
LAS
PT (Z)
Schedule
X
Y
Z
Device X
M
S
Device Y
Device Z
B27141
All of the devices on the fieldbus are given a chance to send unscheduled messages between transmissions of
scheduled data. The LAS grants permission to a device to use the fieldbus by issuing a pass token (PT) message to the
device. When the device receives the PT, it is allowed to send messages until it has finished or until the maximum
token hold time has expired, whichever is the shorter time. The message may be sent to a single destination or to
multiple destinations.
295
Instruction Manual
D103412X012
Report Distribution: This type of communication is used to broadcast and multicast event and trend reports.
Client/Server: This type of communication is used for request/ response exchanges between pairs of devices, such
as a set point change. Like Report Distribution reporting, the transfers are queued, unscheduled, and prioritized.
Queued means the messages are sent and received in the order submitted for transmission, according to their
priority, without overwriting previous messages.
Sequence Repeats
AI
AI
Offset from macrocycle
start time = 20 for AI
Communication
Scheduled
Communication
Unscheduled
Communication
Offset from macrocycle
start time = 30 for AI
Execution
Device 2
PID
AO
PID
AO
B27151
20
40
60
80
100
120
20
40
60
80
100
120
Macrocycle
To support synchronization of schedules, periodically Link Scheduling (LS) time is distributed. The beginning of the
macrocycle represents a common starting time for all Function Block schedules on a link and for the LAS linkwide
schedule. This permits function block executions and their corresponding data transfers to be synchronized in time.
Network Management
Information for setting up network communications, including Virtual Communication Relationships (VCRs), host
timer recommendations, and other network parameters, can be found in the capabilities file (.cff) available from the
website www.FIELDVUE.com or from the Fieldbus Foundation website.
296
Instruction Manual
D103412X012
August 2012
is the path to the DD structure as implemented by the host system. This is typically defined as the base path
to the DD since access to the specific device DD is predefined from the base folder. For a DeltaV system, the
DDs are included with the support files and are located in a folder named amsdevices. For other hosts, the
Fieldbus Foundation defines a folder named release that is included with the CDROM, however, you do not
need to retain this folder name.
xxxxxx is the 6digit hexadecimal equivalent of the manufacturer's identification number as defined by the Fieldbus
Foundation. Fisher Controls' ID number is 5100 (or in the folder format 005100). This number is also stored in
the instrument Resource Block in the parameter Mfg ID (parameter name MANUFAC_ID).
yyyy
is the 4digit hexadecimal equivalent of the device type, as defined by the manufacturer. For example, the
device type for the DVC6200f digital valve controller is 4602. This number is stored in the instrument
Resource Block in the parameter Device Type (parameter name DEV_TYPE).
rr
is the 2digit hexadecimal equivalent of the device revision, as defined by the manufacturer. It is stored in the
instrument Resource Block in the parameter Device Revision (parameter name DEV_REV).
dd
is the 2digit hexadecimal equivalent of the device description (DD) revision that applies to the device, as
defined by the manufacturer. The host will always use the latest version of the DD that it finds for a particular
device revision. When part of the name of a capabilities file, this value is always the same as the value of the
DD_REV parameter stored in the Resource Block of the instrument. The value of the DD_REV parameter
represents the earliest version of the DD that is compatible with the device revision of the instrument.
cc
is a 2digit hexadecimal equivalent for the capabilities files (.cff) revision, as defined by the manufacturer. The
latest revision of the capabilities files, for a particular device revision, is the file with the largest value for this
number.
eee
is the file extension. At this time, five extensions exist for files, they are:
.symThis extension denotes a device description (DD) symbol file as defined by the Fieldbus
Foundation.
297
Instruction Manual
August 2012
D103412X012
.ffoThis extension denotes a complete, tokenized, device description for the instrument as defined by
the Fieldbus Foundation.
.cffThis extension denotes a capabilities file for the instrument as defined by the FOUNDATION Fieldbus
Common File Format specification.
.fhxThis extension denotes a DeltaV device definition file.
.dllThis extension denotes a windows resource file used by DeltaV.
.regThis extension denotes a DeltaV registry file.
.almThis extension denotes a DeltaV alarm file (DeltaV version 6 only).
DD Compatibility
2 and 3
For fieldbus devices, in addition to providing parameter definitions and other information required by the control
system to communicate with the fieldbus device, the DD may also include methods. Methods can be used for a variety
of functions including automatic calibration, setting protection, setting up the instrument, etc. These methods are a
predetermined sequence of steps for information required to setup, calibrate, and perform other functions on the
instrument. How the method prompts the user, and how messages appear is determined by the host system. For
information on using methods on the host system see the appropriate host system documentation.
Table E1 contains the methods available in the DVC6200f, the block it is found in, and the page number where it is
described.
298
Instruction Manual
D103412X012
August 2012
Note
Before beginning the Add Device Definition procedure, it is recommended that the Add Device Utility be installed on DeltaV. This
may help prevent installation errors from occurring.
Block
Description Location
Auto Calibration
Transducer
page 214
Transducer
page 86
Transducer
page 62
Resource
page 45
Display DD Version
Resource
page 301
Instrument Alerts
Transducer
page 69
Transducer
page 214
Transducer
page 217
Transducer
page 217
PlantWeb Alerts
Transducer
page 69
Relay Adjust
Transducer
page 215
Reset Options
Resource
page 221
Device Setup
Transducer
page 40
Stabilize/Optimize
Transducer
page 64
Stroke Valve
Transducer
page 228
Transducer
page 216
Transducer
page 68
Transducer
page 67
Outblock Selection
Transducer
page 69
Transducer
page 86
Performance Tuner
Transducer
page 44, 64
Block Mode
Note
Be sure to select the correct DD for the DeltaV revision being used. The resource files are different for each revision of DeltaV.
Device descriptions furnished by Fisher contain only those files applicable to Fisher. All the files are located in the
manufacturer ID Folder (005100 for xxxxxx in directory structure above). A readme file is included at the top level.
Read this file for any additional information regarding DD installation.
Device descriptions furnished by the Fieldbus Foundation (on CDROM or diskette) contain the files for each
registered manufacturer and their associated device(s). It is placed on the media starting with the release folder,
which then contains a folder (xxxxxx) for each manufacturer as defined above. For Fisher this folder is 005100. A
readme file may be included at the top level. Read this file for any additional information regarding the DD.
For the DVC6200fThe device type parameter for this unit is 4602. This device includes the AO, PID, ISEL, OS, AI,
MAI, DO and DI function blocks. From DeltaV Explorer, select the amsdevices\005100\4602 folder (refer to
figure E2).
299
Instruction Manual
D103412X012
The most recent device description for Fisher devices can be downloaded from the internet at www.FIELDVUE.com.
If you are downloading from the internet, the file on the website will be compressed (zipped) and must be
decompressed (unzipped) before proceeding. Refer to the website download and installation procedures for setting
up the DD on your system. Note the folder where the decompressed files are placed. This information will be
required later in the installation procedure.
Note
Record any warning/error messages from the message window in DeltaV Explorer so that it can be communicated to the DeltaV
Technical Support Group.
300
Instruction Manual
D103412X012
August 2012
up the DD on your system. Note the folder where the decompressed files are placed. This information will be
required later in the installation procedure.
Note
This procedure will install the necessary Device Description files (*.ffo and *.sym), and Capabilities file (*.cff) for the device.
1. Locate or create the folder on the host system to contain all the DD and capabilities files.
If you are creating a folder, you can name this new folder whatever you would like and it can have any path you define.
For this installation procedure, this folder will be referred to as the base folder.
2. On the CDROM or in the website download files, locate the folder with the new support files. This folder is called
\RELEASE.
3. Open this folder and select the folder named 005100.
4. Copy the 005100 folder (and all its subfolders) from the CDROM or website download location to the base folder.
If this is an update (the folders already exist), the system informs you that the folders already exist and asks if they
should be replaced. Answer Yes or OK so the folders are properly updated.
5. The new support files are now installed. You may have to restart applications and drivers in order for the new files to
become active.
DD installation is complete. Consult the system documentation for commissioning new devices or updating existing
devices.
301
302
Instruction Manual
D103412X012
Instruction Manual
D103412X012
August 2012
Appropriate Device Descriptions (DDs) installed. See the Device Description Compatibility table on
page 298. For DD installation information see Appendix E.
Digital valve controller correctly mounted on actuator. For mounting information see the
Installation section of this manual and the instructions included with the mounting kit.
Utilities connected. For information on making pneumatic and electrical connections, see the
Installation section of this manual. For information on applying power to the segment, see DeltaV
books online.
Instrument in standby. For information on placing the instrument in standby, see DeltaV books
online.
Perform the initial setup. See the Basic Setup section of this manual. If the valve is shipped from the
factory mounted on an actuator, perform basic setup only to verify setup is correct and valve
operation is satisfactory.
Device Commissioned. For information on commissioning a device, see DeltaV books online.
Additional configuration required, such as setting alarms, cutoffs, and other resource block and
transducer block parameters. See the Detailed Setup section of this manual.
Control strategy defined. For information on defining a control strategy, see DeltaV books online.
303
Instruction Manual
D103412X012
Path to Parameter
Actual Travel
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Actual Travel
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Fail Action
Actuator Manufacturer ID
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Manufacturer ID
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Model Number
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Serial Number
Actuator Size
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Size
Actuator Style
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Style
Air
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Air
Alert Conditions
Alert Key
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Alert Key
Area Units
TB > Configure/Setup > Detailed Setup > Instrument > Units: Area Units
TB > Device Diagnostics > Status > Transducer Block Error: Block Configuration Error
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Blocks Set to Default: Block Set to Default Alert
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Blocks Set to Default: Block Set to Default Alert Enable
Calibration Date
TB > Configure/Setup > Detailed Setup > Instrument > Calibration: Calibration Date
Calibration Location
TB > Configure/Setup > Detailed Setup > Instrument > Calibration: Calibration Location
Calibration Person
TB > Configure/Setup > Detailed Setup > Instrument > Calibration: Calibration Person
Cycle Count
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter:Cycle Count
TB > Device Variables > Overview > Cycle Count
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter: Cycle Count Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter: Cycle Count Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter Cycle Count Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter: Cycle Count Deadband
TB > Device Diagnostics > Status > Transducer Block Error: Device Needs Maintenance Now
Drive Current
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current
TB > Device Diagnostics > Status > Self Test Status: Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert Time
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Shutdown
Drive Signal
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Signal: Drive Signal
TB > Device Variables > Overview > Drive Signal
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Signal: Drive Signal Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Signal: Drive Signal Alert Enable
Effective Area
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Effective Area
Feedback Connection
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Feedback Connection
Flow Direction
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Direction
Flow Tends To
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Tends To
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Man Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Shutdown
Inlet Pressure
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Inlet Pressure
Input Characterization
TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization > Input Characterization
TB > Device Variables > Overview > Input Characterization
Integrator Limited Hi
TB > Device Diagnostics > Status > Self Test Status: Integrator Limited Hi
Integrator Limited Lo
TB > Device Diagnostics > Status > Self Test Status: Integrator Limited Lo
Integrator Suspended
TB > Device Diagnostics > Status > Self Test Status: Integrator Suspended
IOP Failure
TB > Device Diagnostics > Status > Self Test Status: IOP Failure
TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization > Last Valid Point
Leak Class
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Leak Class
Length Units
TB > Configure/Setup > Detailed Setup > Instrument > Units: Length Units
-Continued-
304
Instruction Manual
D103412X012
August 2012
Path to Parameter
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Style
TB > Device Diagnostics > Status > Transducer Block Error: Lost Static Data
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lower Bench Set
MAI Channel 1
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 1
MAI Channel 2
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 2
MAI Channel 3
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 3
MAI Channel 4
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 4
MAI Channel 5
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 5
MAI Channel 6
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 6
MAI Channel 7
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 7
MAI Channel 8
TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 8
TB > Configure/Setup > Detailed Setup > Instrument > Application: Max Supp Pressure
MLFB Error
TB > Device Diagnostics > Status > Self Test Status: MLFB Error
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Moment Arm
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Nominal Supply Pressure
Out of Service
TB > Device Diagnostics > Status > Transducer Block Error: Out of Service
Outlet Pressure
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Outlet Pressure
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Blk Timeout
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Alert
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Shutdown
Packing Type
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Packing Type
PD Inside Status
TB > Configure/Setup > Detailed Setup > Alerts > Performance > PD Inside Status
PD Inside Status
PD Run
TB > Configure/Setup > Detailed Setup > Alerts > Performance > PD Run
TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Critical: Performance Critical Alert
TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Critical: Performance Critical Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Information: Performance Information Alert
TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Information: Performance Information Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Reduced: Performance Reduced Alert
TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Reduced: Performance Reduced Alert Enable
Performance Tuner(1)
Port Diameter
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Diameter
Port Type
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Type
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Shutdown
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure B Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure B Sensor Alert Enable
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Cutoff Close
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Cutoff Open
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Deadzone
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Gain
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Limit Hi
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Limit Lo
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure MLFB Gain
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Prop Gain
Pressure Range Hi
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Range Hi
Pressure Range Lo
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Range Lo
TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Tuning Set
-Continued-
305
Instruction Manual
D103412X012
Path to Parameter
TB > Device Variables > Overview > Pressures: Pressure A
TB > Device Diagnostics > Status > Self Test Status: Pressure A Sensor Failure
Pressure B
TB > Device Diagnostics > Status > Self Test Status: Pressure B Sensor Failure
Pressure Differential
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Fallback: Pressure Fallback Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Fallback: Pressure Fallback Alert Enable
Pressure Units
TB > Configure/Setup > Detailed Setup > Instrument > Units: Pressure Units
Processor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Processor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Processor Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Shutdown
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Alert
Protection
Proximity Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Alert Enable
Proximity Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Hi Alert Enable
Proximity Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Alert Enable
Proximity Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Lo Alert Enable
Push Down To
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Push Down To
TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate PlantWeb Alerts
Rated Travel
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Rated Travel
Relay Type
TB > Configure/Setup > Detailed Setup > Instrument > Application: Relay Type
Seat Type
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Seat Type
Setpoint
Setpoint Status
Setpoint(D)
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Shaft Stem Dia
Simulate Active
TB > Device Diagnostics > Status > Transducer Block Error: Simulate Active
Simulate Jumper ON
TB > Device Diagnostics > Status > Self Test Status: Simulate Jumper ON
Spring Rate
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Spring Rate
TB > Configure/Setup > Detailed Setup > Instrument > Units: Spring Rate Units
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Shutdown
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Close
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Open
TB > Device Diagnostics > Device Record > Supp Pressure Max
TB > Device Diagnostics > Device Record > Supp Pressure Maximum Time
TB > Device Diagnostics > Device Record > Supp Pressure Minimum
TB > Device Diagnostics > Device Record > Supp Pressure Minimum Time
Supply Pressure
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure
Supply Pressure
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Pressure Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Hi Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Lo Alert Point
-Continued-
306
Instruction Manual
D103412X012
August 2012
Path to Parameter
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Supply Pressure Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Supply Pressure Sensor Alert Enable
TB > Device Diagnostics > Status > Self Test Status: Supply Sensor Failure
Tag Description
TB > Configure/Setup > Detailed Setup > Instrument > Tag Description
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Hi Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert Point
Temperature Maximum
TB > Device Diagnostics > Device Record > Temperature Maximum Time
Temperature Minimum
TB > Device Diagnostics > Device Record > Temperature Minimum Time
Temperature
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature
TB > Device Variables > Overview > Temperature
Temperature Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Hi Alert Enable
Temperature Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Temperature Sensor: Temperature Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Temperature Sensor: Temperature Sensor Alert Enable
Temperature Units
TB > Configure/Setup > Detailed Setup > Instrument > Units: Temperature Units
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel
Travel
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel
TB > Device Variables > Overview > AO Control PostCharacterization: Travel
Travel(D)
Travel(DeChar)
Travel Status
TB > Device Variables > Overview > AO Control PostCharacterization: Travel Status
Trend
Trim Style 1
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 1
Trim Style 2
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 2
Travel Accumulator
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator
TB > Device Variables > Overview > Travel Accumulator
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Deadband
Travel Count
Travel Cutoff Hi
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel Control: Travel Cutoff Hi
Travel Cutoff Lo
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel Control: Travel Cutoff Lo
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Deviation: Travel Deviation Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel: Travel Deviation Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel: Travel Deviation Time
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Deviation: Travel Deviation Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Deviation: Travel Deviation Alert Enable
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Deadzone
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Enable
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Limit Hi
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Limit Lo
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Gain
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Hi Alert Enable
-Continued-
307
Instruction Manual
August 2012
D103412X012
Path to Parameter
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Hi Alert Point
Travel Hi Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Hi Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Hi Hi Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Hi Hi Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Hi Hi Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Hi Hi Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Lo Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Lo Deadband
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Lo Lo Alert
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Lo Lo Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Lo Lo Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Lo Lo Deadband
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel MLFB Gain
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Alert
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Alert Enable
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Alert Point
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Deadband
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Proportional Gain
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Travel Sensor Motion
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Alert
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Alert Enable
TB > Device Diagnostics > Status > Self Test Status: Travel Sensor Hi Error
TB > Device Diagnostics > Status > Self Test Status: Travel Sensor Lo Error
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Manual Recovery
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Shutdown
TB > Device Diagnostics > Status > Self Test Status: Travel Sensor Span Error
Travel Target
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Target
Travel Target
TB > Device Variables > Overview > AO Control PostCharacterization: Travel Target
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Tuning Set
Travel Units
TB > Configure/Setup > Detailed Setup > Instrument > Units > Travel Units
TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Velocity Gain
Travel/Pressure Select
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel/Pressure Select
Travel/Pressure State
TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel/Pressure State
TB > Device Variables > Overview > Travel/Pressure State
Unbalanced Area
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Unbalanced Area
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Upper Bench Set
Valve Class
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Class
Valve Manufacturer ID
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Manufacturer ID
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Model Number
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Serial Number
Valve Size
Zero Power Condition
308
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Size
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Style
TB > Configure/Setup > Detailed Setup > Instrument > Application: Zero Power Condition
Instruction Manual
D103412X012
August 2012
Path to Parameter
Alert Key
RB > Configure/Setup > Setup > Alarm Handling > Alert Key
RB > Device Diagnostics > Status > Block Alarm: Alarm State
RB > Configure/Setup > Setup > Alarm Handling > Block Alarm: Block Alarm Disabled
RB > Configure/Setup > Setup > Alarm Handling > Block Alarm: Block Alarm Auto Acknowledge
RB > Configure/Setup > Setup > Alarm Handling > Write Alarm: Discrete Alarm Auto Acknowledge
Confirm Time
RB > Configure/Setup > Setup > Alarm Handling > All Alarms: Confirm Time
Device ID
Device Revision
Device State
Device Type
DD Revision
Diagnostic Options
Electronics S/N
Factory S/N
Fault State
Function Block Options
Features Available
Features Selected
Field S/N
RB > Configure/Setup > Setup > Identification > Identification: Field S/N
Field S/N
Hardware Revision
RB > Configure/Setup > Setup > Version > Version Information: Hardware Revision
ITK Version
RB > Configure/Setup > Setup > Version > Version Information: ITK Version
Manufacturer
Manufacturer
RB > Configure/Setup > Setup > Alarm Handling > All Alarms: Maximum Alerts Allow
RB > Configure/Setup > Setup > Alarm Handling > All Alarms: Maximum Alerts Possible
Miscellaneous Options
RCas Timeout
RB > Configure/Setup > Setup > Comm Timeout > RCas Timeout
ROut Timeout
RB > Configure/Setup > Setup > Comm Timeout > ROut Timeout
Firmware Revision
RB > Configure/Setup > Setup > Version > Version Information: Firmware Revision
Status
RB > Configure/Setup > Setup > Version > Version Information: Standby Firmware Revision
Strategy
Tag Description
RB > Device Diagnostics > Status > Write Alarm: Alarm State
RB > Configure/Setup > Setup > Alarm Handling > Write Alarm: Write Alarm Disabled
Write Lock
Write Priority
RB > Configure/Setup > Setup > Write Lock > Write Lock
RB > Device Diagnostics > Status > Write Lock
RB > Configure/Setup > Setup > Write Lock > Write Priority
309
Instruction Manual
D103412X012
Introduction
Note
This appendix does not necessarily provide the latest information on the DeltaV system. For the latest information on using the
DeltaV system, refer to the online help or documentation supplied with the system.
This appendix provides specific instructions for performing basic setup operations on the DeltaV host system. It is not
a comprehensive resource, rather a starting point. For more information, refer to the following sources:
Section 3: Basic Setup and Tuning for detailed information regarding initial setup, and stabilizing and optimizing valve
response.
Section 4: Detailed Setup for detailed information on configuring all of the blocks in the instrument, and an overview
of the function blocks.
Section 5: Calibration for complete calibration information.
Appendix A: Principle of Operation for information on how digital valve controller operation.
Appendix D: FOUNDATION fieldbus Communication for an overview of function block and block modes, as well as
additional information pertaining to fieldbus communication.
Appendix E: DD Installation for information on installing the device description (DD) software on your host system.
DeltaV OnLine Help or Documentation for complete and current information about navigating in the DeltaV system.
310
Instruction Manual
D103412X012
August 2012
DIGITAL VALVE
CONTROLLER ICON
AND NAME
Figure F2. Accessing the Digital Valve Controller Through AMS Device Manager
LEFTCLICK TO
ACCESS THE DELTAV
NETWORK
DIGITAL VALVE
CONTROLLER
ICON AND
NAME
311
Instruction Manual
D103412X012
Methods
Transducer Block
The following methods are accessed via the transducer block: Device Setup, Auto Travel Calibration, Manual Travel
Calibration, Supply Sensor Calibration, Output A Sensor Calibration, Output B Sensor Calibration, Travel Sensor Adjust,
Stroke Valve, Performance Tuner, Stabilize/Optimize, and Relay Adjust.
Refer to figures F1, F2, and F3 and the following steps to access these methods.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the the digital valve controller icon in the All Containers pane (the left panel) and rightclick once on the
digital valve controller icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Methods in the Actions menu, as shown in figure F3 and rightclick once.
6. Select the desired method from the the Actions menu and leftclick to start the method.
Resource Block
The Restart Options method and the DD Information method are available via the resource block. Refer to figure F3
and the following steps to access these methods.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the digital valve controller icon in the All Containers pane (the left panel) and rightclick once on the digital
valve controller icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Methods in the Actions menu, as shown in figure F3 and rightclick once.
6. Select the desired method from the the Actions menu and leftclick to start the method.
Accessing Parameters
Transducer Block
For detailed information on the parameters that are changed via the transducer block, refer to the Detailed Setup
section of this manual. Refer to figures F2, F3, and F4 for information on accessing transducer block parameters.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the digital valve controller icon in the All Containers pane and rightclick once on the digital valve controller
icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Configure/Setup in the Actions menu (see figure F3) and leftclick to access Configuration and Setup
parameters.
6. Leftclick on Digital Valve Controller (TRANSDUCER) to access the transducer block parameters. Refer to table F1
for the transducer block configuration menu.
312
Instruction Manual
D103412X012
August 2012
ACTIONS
CONFIGURE/SETUP
RESOURCE BLOCK
METHODS
TRANSDUCER
BLOCK METHODS
Note
To access diagnostic parameters leftclick on Device Diagnostics, and then on Digital Valve Controller (TRANSDUCER). See
figure F4.
To access device variables leftclick on Device Variables, and then on Digital Valve Controller (TRANSDUCER). See figure F4.
313
Instruction Manual
August 2012
D103412X012
DIGITAL VALVE
CONTROLLER
(TRANSDUCER)
RESOURCE
(RESOURCE)
DEVICE
DIAGNOSTICS
DEVICE
VARIABLES
Resource Block
For detailed information on the parameters that are changed via the resource block, refer to the Detailed Setup
section of this manual. Refer to figures F2, F3, and F4 for information on accessing resource block parameters.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the digital valve controller icon in the All Containers pane and rightclick once on the block icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Configure/Setup in the Actions menu (see figure F3) and leftclick to access Configuration and Setup
parameters.
6. Leftclick on Resource (RESOURCE) to access the resource block parameters. Refer to table F2 for the resource
block configuration menu.
Note
To access diagnostic parameters leftclick on Device Diagnostics, and then on Resource (RESOURCE). See figure F4.
To access device variables leftclick on Device Variables, and then on Resource (RESOURCE). See figure F4.
314
Instruction Manual
D103412X012
August 2012
PlantWeb Alerts
Fieldbus devices detect and report their device alarms to a DeltaV system (or other host system). This includes
detecting whether an alert condition is active, reporting the alarm to DeltaV and later clearing the alarm when the
condition is no longer active. Whether a particular alert condition can be suppressed, disabled or configured offline
are all determined by the device.
For Fieldbus, the DeltaV system is responsible for knowing which devices have alarms, ensuring that alarms are
properly represented (such as after controller switchovers) and reporting to operators, Event Chronicle, AMS, OPC
Alarms and Events server, etc. So the only alarms DeltaV shows for a Fieldbus device are those the device has defined
as alarms and has reported to DeltaV.
All device alarms are configured and processed in the DeltaV system identically to process alarms. This means that
how the alarms are communicated within the system, what workstations are notified, alarm annunciation, graphical
representations, event recording, acknowledgement, etc. are identical for process and device alarms. This ensures
that device alarms and process alarms are available to all users and applications in a consistent fashion.
315
Instruction Manual
D103412X012
The Enable Device Alarms configuration option modifies the device configuration. Thus changing this setting requires
a download to the device. Devices that are migrated from older DeltaV systems will have their device alarms disabled.
Note
1. Use the default setting of device alarms enabled. If the user does not want notification of device alarms, this can be configured
on each individual alarm. Later on, you can modify the alarm configurations without downloading the device. Disabling device
alarms disables all of the alarms, including the device communication failure alarm.
2. Use the same control display for the device as for the control module.
3. If you suspect a rogue device is generating extra H1 bus traffic from device alarms, disabling device alarms stops the device from
sending the alarms.
4. If the Alarms and Displays tab is not shown, then you either do not have an MD controller or the device is on a Series 1 H1 card.
316
Instruction Manual
D103412X012
August 2012
Area Assignment
Controllers use this area assignment to report node status (e.g. not communicating). Devices and control modules use
this area assignment to determine where to send their alarms.
Area A is the default area assignment for all controllers and workstations (see figures F6 and F7). Also, by default Area
A is assigned to all workstations Alarms and Events subsystem. This means that all controller status problems are sent
to all workstations by default.
Figure F6. Controller Properties
A fieldbus device will change its area association once the device is configured to a control module. In addition, the
device is assigned to the same place in the logical hierarchy as this control module. So if the control module is under a
unit, the device is also considered under this same unit.
The device is automatically associated with the same area as the control module that uses the lowest index number
function block in the device. This block is usually the primary input or output function block of the device. This ensures
that wherever the control module is reporting information, all device information that may also be relevant is also
reported.
Note
1. For devices with multiple inputs or outputs (such as the 848), you need to decide which area is best for device alarm reporting
and be sure to assign the correct control module to the lowest index number function block. If there is no module assigned to this
function block, then the device will always be assigned to the same area as the controller.
2. With controller area default of AREA A, and the default of AREA A being assigned to all workstations, you need to evaluate the
alarm settings when commissioning a new fieldbus device with device alarms enabled. If the device detects a FAILED or COM FAIL
alarm prior to being assigned to a control module, this device alarm will be reported and annunciated to all workstations. This is
317
Instruction Manual
D103412X012
because all workstations have Area A assigned. Consider lowering the priority of these alarms to ADVISORY until the end of the
commissioning process.
318
Instruction Manual
D103412X012
Note
If you think you should be seeing a device alarm in the alarm banner and it is not there, verify that the device is shown on the
AlarmSum display. This display shows ALL of the alarms reporting to that workstation, regardless of the device alarm annunciation
settings. If the device is not shown in this display, then it is not reporting to this workstation (or the logged on user does not have
responsibility for that area).
The default for device alarm annunciation (sounds the horn and shown in the alarm banner) can be modified for all
operator/maintenance stations. Or unique settings can be defined for specific workstations. Use the workstation name
to adjust settings for specific workstations in UserSettings.grf.
For example, if an installation has a Maintenance Station named 'MAINT', then the UserRef.grf (then renamed to
UserSettings.grf) would contain alarm settings for the MAINT workstation as appropriate for maintenance (e.g. all
device alarms in the alarm banner).
Note
To easily find the device alarm configuration in UserRef or UserSettings, open the display in the Standard directory, right click and
select EDIT SCRIPT, then select Edit, Find and type in DEVICE. This will take you to the location in the file with the device alarm
settings.
319
Instruction Manual
August 2012
D103412X012
The DeltaV workstation default is to annunciate device alarms above the ADVISORY (7) priority.
Therefore, by default both the FAILED and COMM PlantWeb alerts annunciate to the operator.
The priority of each alarm needs to be considered. The priority of a device alarm is determined by how important that
device problem is and the consequences to the process.
The priority is not based solely on the type of device. This means that while some DVC6200f's may be critical to
operation, other DVC6200f's may not. In this example, the DVC6200f's would have different default alarm priorities.
Note
1. If your installation has the Fieldbus devices, but is not ready to use PlantWeb alerts, then you can disable the individual alarms at
the device - or through the System Alarm Management application. Later on, individual alarms can be enabled without having to
download the device.
2. When you first begin to use device alarms, be sure that your alarm priority settings for the workstations or the individual device
alarm priorities are such that they don't cause undue operator burden. This could mean only having a few device alarms set at
WARNING or above, or changing the DeltaV Operate default such that only CRITICAL device alarms (or even perhaps NO device
alarms annunciate to the operator).
3. DO NOT enable ALL of the PlantWeb alerts in a device. Only enable the alerts that are needed.
320
Instruction Manual
Glossary
D103412X012
August 2012
Glossary
Algorithm
A set of logical steps to solve a problem or
accomplish a task. A computer program contains
one or more algorithms.
Deadband
Region around a reference point that must be
exceeded before a new event occurs.
Deviation
Alphanumeric
Consisting of letters and numbers.
ANSI (acronym)
The acronym ANSI stands for the American
National Standards Institute
ANSI Class
Valve pressure/temperature rating.
Bench Set
Pressure, supplied to an actuator, required to
drive the actuator through rated valve travel.
Expressed in pounds per square inch.
Byte
A unit of binary digits (bits). A byte consists of
eight bits.
Configuration
Stored instructions and operating parameters for
a FIELDVUE Instrument.
Control Loop
An arrangement of physical and electronic
components for process control. The electronic
components of the loop continuously measure
one or more aspects of the process, then alter
those aspects as necessary to achieve a desired
process condition. A simple control loop
measures only one variable. More sophisticated
control loops measure many variables and
maintain specified relationships among those
variables.
Controller
Device ID
Unique identifier embedded in the instrument at
the factory.
Drive Signal
The signal to the I/P converter from the printed
wiring board. It is the percentage of the total
microprocessor effort needed to drive the valve
fully open. In most applications, drive signal
ranges from 55% to 75%.
Feedback Arm
The mechanical connection between the valve
stem linkage and the FIELDVUE Instrument travel
sensor.
Feedback Signal
Indicates to the instrument the actual position of
the valve. The travel sensor provides the feedback
signal to the instrument printed wiring board
assembly. A mechanical linkage connects the
travel sensor to the valve stem or shaft.
Firmware
The combination of a hardware device and
computer instructions and data that reside as
readonly software on that device.
Note
1. This term (firmware) is sometimes used to refer only to
the hardware device or only to the computer instructions or
data, but these meanings are deprecated.
2. The confusion surrounding this term has led some to
suggest that it be avoided altogether. The term is included
here because of its use in older documentation and culture.
321
Instruction Manual
Glossary
August 2012
Gain
The ratio of output change to input change.
D103412X012
Pressure Sensor
A FIELDVUE instrument internal device that
senses the output pressure from the pneumatic
relay.
Hardware Revision
Revision number of the Fisher instrument
hardware. The physical components of the
instrument are defined as the hardware.
Instrument Level
Determines the functions available for the
instrument.
Rate
Leak Class
Defines the allowable leakage by a valve when it is
closed. Leak class numbers are listed in two
standards: ANSI/FCI 702 and IEC 5344.
Linearity, dynamic
Linearity (independent) is the maximum
deviation from a straight line best fit to the
opening and closing curves and a line
representing the average value of those curves.
Memory
A type of semiconductor used for storing
programs or data. FIELDVUE instruments use
three types of memory: Random Access Memory
(RAM), Read Only Memory (ROM), and
NonVolatile Memory (NVM).
Seat Load
Force exerted on the valve seat, typically
expressed in pounds force per lineal inch of port
circumference. Seat load is determined by shutoff
requirements.
Software
Computer programs, procedures, and possibly
associated documentation and data pertaining to
the operation of a computer system.
Temperature Sensor
A device within the FIELDVUE instrument that
measures the instrument's internal temperature.
Travel
Movement of the valve stem or shaft which
changes the amount the valve is open or closed.
Octet
See byte
Parallel
Simultaneous: said of data transmission on two or
more channels at the same time.
322
Travel Sensor
A device within the FIELDVUE instrument that
senses valve stem or shaft movement. The travel
sensor in the DVC6200f is the Hall Effect sensor
that measures the position of the magnet
assembly.
Instruction Manual
Glossary
D103412X012
Tuning
The adjustment of control terms or parameter
values to produce a desired control effect.
Tuning Set
Preset values that identify gain and rate settings
for a FIELDVUE instrument. The tuning set and
supply pressure together determine an
instrument's response to input signal changes.
August 2012
323
Glossary
August 2012
324
Instruction Manual
D103412X012
Instruction Manual
Index
D103412X012
Index
A
Acknowledge Option, Resource Block, 48
Act On IR, 131
Action on Failure, DI Function Block, 205
Action on Fault Detection
AO Function Block, 118
DO Function Block, 194
Active PlantWeb Alerts, 224
Actuator
Fail Action, 83
Manufacturer, 83
Model Number, 83
Serial Number, 83
Size, 83
Style, 83
Device Setup, 42
Actuator Compatibility, 8
Actuator Information, for initial setup, 41
Advanced Diagnostics (AD), 4
Air, 84
as supply medium, 7, 27
Alarm Detection
AI Function Block, 171
DI Function Block, 205
ISEL Function Block, 151
PID Function Block, 131
Alarm Handling, 47
Alarm Priorities
ISEL Function Block, 152
PID Function Block, 132
Alert Conditions, 224
Instrument, 69
August 2012
Alerts
Configuration, 71
Electronics, 69
Environment, 73
Instrument, 69
Performance, 79
PlantWeb, 69
Proximity, 76
Sensor, 72
Travel, 74
AMS Device Manager, using, 310
Analog Input (AI) Function Block, 5, 171
Advanced Features, 175
Alarm Detection, 171
Block Errors, 175
Field Communicator Menu Structure, 182
Filtering, 174
Modes, 171
parameters, 176
Signal Conversion, 174
Simulation, 175
Status Handling, 173
Troubleshooting, 176
View Lists, 180
Analog Output (AO) Function Block, 5, 113
Action on Fault Detection, 118
Application Information, 119
Block Errors, 119
Field Communicator Menu Structure, 125
I/O Options, 118
Mode Handling, 115
parameters, 120
Set Point Selection and Limiting, 117
Setting the Output, 116
Simulation, 119
Status Handling, 116
View Lists, 124
ANSI/ISA75.13.01 Section 5.3.5, Vibration Testing
Method, 8
AO Control - PreCharacterization, Device Variables,
230
AO ControlPost Characterization, Device Variables,
230
Alert Handling, 86
PlantWeb Alert Handling, 86
PlantWeb Alert Simulate, 86
PlantWeb Alerts, 275
Simulate Active Alerts, 86
Application Information
AO Function Block, 119
DI Function Block, 206
MAI Function Block, 184
PID Function Block, 132
Alert Key, 72
Area Units, 81
ATEX, 8
325
Instruction Manual
Index
August 2012
D103412X012
B
Backup Link Master, 7
Basic Setup, 39
Bench Set
Lower, 84
Upper, 84
Block Alarm, Resource Block, 221
Block Alarm Auto Acknowledge, Resource Block, 48
Block Alarm Disabled, Resource Block, 48
Block Error
Resource Block, 220
Transducer Block, 227
Block Error Reporting, 86
Block Errors, 86
AI Function Block, 175
AO Function Block, 119
DI Function Block, 205
DO Function Block, 194
ISEL Function Block, 152
MAI Function Block, 184
PID Function Block, 132
Resource Block, 49
Block Execution Times, 7
Block Initialization
DI Function Block, 202
DO Function Block, 192
Calibration Location, 81
Calibration Person, 81
Certification
INMETRO, Brazil, 8
KGS, Korea, 8
NEPSI, China, 8
TIIS, Japan, 8
Clear Fault State, Resource Block, 222
Commissioning Tag, 37
Communication Connections, 36
Communication Time Out, 46
Shed Remote Cascade, 46
Shed Remote Out, 46
Configuration Alerts, 71, 224
Alert Key, 72
Blocks Set to Default, 72, 225
Output Block Timeout, 71, 224
Configure/Setup, 45
Confirm Time, 48
Connections
Communications, 36
Pneumatic, 26
Pressure, 26
Supply, 27
Specifications, 8
Vent, 30
Wiring and Electrical, 31
Fieldbus, 31
Construction Materials, 9
Blocks
Function, 5
Resource Block, 5
Transducer Block, 5
CSA, 8
C
Calibration, 213
Auto, 214
Manual, 214
Pressure A or B Sensor, 217
Relay, 215
326
D
DD Information, 223
Declaration of SEP, 9
DeltaV ProfessionalPLUS Workstation, Installing DD
on, 298
Instruction Manual
Index
D103412X012
DeltaV System
operating with, 303
Software Functionality/System Requirements, 310
DeltaV Tune, for PID control loops, 132
Detailed Setup, 62
Device Addressing, 293
Device Communication, 294
Scheduled Transfers, 294
Unscheduled Transfers, 295
Device Description, Overview, 297
Device Description Version, displaying, 301
Device Descriptions, 291
Installing on a DeltaV ProfessionalPLUS Workstation,
298
Installing on Other Fieldbus Host Systems, 300
Device Diagnostics
Resource Block, 220
Transducer Block, 224
Device ID, 37, 48, 222
Device Revision, 49, 223
Device Setup, 40
Device State, Resource Block, 220
Device Type, 48, 223
Device Variables
Resource Block, 222
Transducer Block, 229
diagnostic capabilities, 4
Diagnostic Options, 46, 49, 223
August 2012
Modes, 202
parameters, 206
Simulation, 205
Status Handling, 202
View Lists, 210
Discrete Output (DO) Function Block, 5, 189
Action on Fault Detection, 194
Block Errors, 194
Block Initialization, 192
I/O Selection, 192
Mode Handling, 191
Modes, 190
Output Block PV Status, 193
parameters, 195
Setting the Output, 192
Shed Options RCAS Mode Only, 191
Simulation, 194
Status Handling, 192
View Lists, 199
DO Control, Device Variables, 230
DoubleActing Relay, calibration, 215
Drive Current, Alerts, 69
Drive Signal
Alerts, 70
Device Variables, 231
DVC6205 base unit, 14
E
Educational Services, 10
Effective Area, 84
Electrical Classification
Electrical Housing, 8
Hazardous Area Approvals, 8
Electrical Housing, 8
327
Instruction Manual
Index
August 2012
Expert tuning, 43
Pressure, 66
Travel, 63
F
Factory Serial Number, 48, 222
D103412X012
Function Blocks, 5
Analog Input (AI), 5, 171
Analog Output (AO), 5, 113
Discrete Input (DI), 201
Discrete Output (DO), 5, 189
Input Selector (ISEL), 5
Multiple Analog Input (MAI), 5, 183
Output Splitter (OS), 5, 160
Proportional-Integral-Derivative (PID), 5, 126
G
Gain Values, preselected tuning sets, 43
Gas Certified, DVC6200f, 8, 27
Gauges, Pipe Plugs, or Tire Valves, maintenance, 241
H
Hardware Revision, 49, 223
Fieldbus Connections, 31
Quick Connect Cable Entry, 33
Twisted Shielded Pair, 32
I/O Selection
DI Function Block, 202
DO Function Block, 192
I/P Converter
maintenance, 237
removing, 238
replacing, 238
I/P Filter, replacing, 237
Flow Direction, 82
FM, 8
IECEx, 8
Function Block
Input Selector (ISEL), 145
Overview, 287
328
Instruction Manual
Index
D103412X012
August 2012
Input Characterization, 67
Device Variables, 230
K
KGS, Korea, Certification, 8
M
magnet assemblies, 13
linear, 12
magnet assembly
material, 12
travel range, 12
Magnetic Feedback Assembly, replacing, 234
Magnetic Tools, use of, 12, 17
Magnets, high power, 12, 17
MAI Channel Map, 85
MAI Function Block, parameters, 185
Maintenance
Gauges, Pipe Plugs, or Tire Valves, 241
I/P Converter, 237
Module Base, 234, 235
Pneumatic Relay, 240
PWB Assembly, 239
Resource Block, 221
Terminal Box, 241
Tools Required, 234
Fieldbus Connections with Twisted Shielded Pair, 32
Manual Calibration, 214
Manufacturer Identification, 48, 223
Maximum Notify, 48
L
Last Calibration Type, 81
Leak Class, 82
Length Units, 81
Lever Arm Length, 84
Lever Style, 84
Lightning and Surge Protection, 8
Limit Handling, OS Function Block, 163
Limit Notify, 48
Limit Propagation
ISEL Function Block, 147
Transducer Block, 292
329
Instruction Manual
Index
August 2012
Mode Handling
AO Function Block, 115
DO Function Block, 191
PID Function Block, 128
Modes
AI Function Block, 171
AO Function Block, 114
Blocks, 289
DI Function Block, 202
DO Function Block, 190
Explanation of, 290
ISEL Function Block, 145
MAI Function Block, 183
OS Function Block, 161
PID Function Block, 128
Resource Block, 45
Transducer Block, 62
Module Base
removing, 235
replacing, 236
D103412X012
O
Open/Closed Limit Switch, Channel 24 and 25, DI
Function Block, 203
Options, 9
Resource Block
Diagnostic, 46
Features Available, 47
Features Selected, 47
Function Block, 46
Miscellaneous, 47
Outblock Selection, 69
Output Block PV Status, 85
AO Function Block, 117
DO Function Block, 193
Output Block Timeout, Alerts, 71
Output Connection, 28
Output Selection and Limiting, PID Function Block, 130
Output Signal, Specifications, 7
Mounting
67CFR, 26
DVC6200f, 11
DVC6205 base unit
Pipestand, 14
Wall, 14
DVC6215 feedback unit, 16
Troubleshooting, 243
P
Parameters
AI Function Block, 176
AO Function Block, 120
DI Function Block, 206
DO Function Block, 195
ISEL Function Block, 152
MAI Function Block, 185
OS Function Block, 167
PID Function Block, 133
Resource Block, 54
Transducer Block, 87
330
PD Inside Status
Alert, 79
Device Variables, 231
Instruction Manual
Index
D103412X012
PD Run, Alert, 80
Performance Alerts, 79, 226
PD Inside Status, 79
PD Run, 80
Performance Critical, 80, 226
Performance Information, 80
Performance Reduced, 80
Performance Critical, Alerts, 80
August 2012
Performance, 79
Proximity, 76
Sensor, 72
Set Block Status, 277
Setting, 277
Travel, 74
Travel History, 78
Using, 277, 281
PlantWeb Alerts Set PV Status, 86
Pneumatic Connections, 26
Pneumatic Relay
removing, 240
replacing, 240
Port Diameter, 82
Port Type, 82
Pressure, Connections, 26
Pressure A or B Sensor, calibration, 217
Pressure Cutoff Closed, 67
Pressure Cutoff Open, 67
Pressure Fallback, Alerts, 73
Pressure Fallback Auto Recovery, 66
Pressure Fallback Manual Recovery, 66
Pressure Integral Dead Zone, 66
Pressure Integral Gain, 66
Pressure Integral Limit Hi, 66
Pressure Integral Limit Lo, 66
Pressure MLFB Gain, 66
Pressure Proportional Gain, 66
Pressure Range Hi, 67
Pressure Range Lo, 67
Pressure Sensors, Alerts, 72
Pressure Tuning, 65
Pressure Tuning Set, 65
PlantWeb Alerts, 69
Alert Handling, 275
Alert Reporting, 277
Conditions, 275
Configuration, 71
Electronics, 69
Environment, 73
in a DeltaV System, 315
Mode-Based, 275
Pressure Units, 81
Pressures, 232
Principle of Operation, Block Diagram, 259
Printed Wiring Board (PWB) Assembly
removing, 239
replacing, 239
Processor Impaired, Alerts, 70
331
Instruction Manual
Index
August 2012
D103412X012
R
Regulator (67CFR), 26
Casing-Mounted, 26
Integral-Mounted, 26
Yoke-Mounted, 26
Related Documents, 10
Relay, calibration, 215
Relay A, 215
Relay B, 40, 215, 216
Relay C, 215, 216
Relay Type, 81
Remote Travel Sensor Connections, 34
remote vent, 30
Resource Block, 288
Block Alarm, 221
Block Errors, 49
Clear Fault State, 222
Device State, 220
Device Variables, 222
Options
Diagnostic, 223
Features Available, 223
Function Block, 223
Miscellaneous, 223
Overview, 45
parameters, 54
Restart Actions, 221
332
S
Scheduled Transfers, Device Communication, 294
Seat Type, 82
Self Test Status, 226
Sensor Alerts, 72, 225
Pressure Fallback, 73, 225
Pressure Sensors, 72, 225
Temperature Sensor, 225
Travel Sensor, 225
Travel Sensor Alert, 72
Serial Number
Actuator, 83
Electronics, 48, 222
Factory, 48, 222
Field, 48, 222
Valve, 82
Set Block Status, PlantWeb Alerts, 277
Set Fault State, Resource Block, 222
Set Point Selection and Limiting, AO Function Block,
117
Set Point Tracking, PID Function Block, 130
Instruction Manual
Index
D103412X012
August 2012
T
Tag Description
Resource Block, 48, 222
Transducer Block, 81
Temperature
Device Variables, 231
Maximum Recorded, 228
Minimum Recorded, 228
Temperature Limit, Alerts, 74
Specifications, DVC6200f, 7
Spring Rate, 84
Temperature Units, 81
Terminal Box
removing, 241
replacing, 242
333
Instruction Manual
Index
August 2012
D103412X012
Travel Accumulator
Alerts, 78
Device Variables, 231
Travel/Pressure State, 66
Device Variables, 231
Trim Style 1, 84
Trend, 229
Trim Style 2, 84
Troubleshooting
AI Function Block, 176
DVC6200f, 243
MAI Function Block, 184
mounting, 243
utility connections, 243
Tuning
Pressure, 65
Travel, 63
Tuning Set
Device Setup, 43
Pressure, 65
Travel, 63
Tuning Set B, 43
Tuning Sets, Gain Values, 43
U
Unbalanced Area, 82
Unscheduled Transfers, Device Communication, 295
Upper Bench Set, 84
Utility Connections, Troubleshooting, 243
V
Valve
Actual Travel, 82
Class, 82
Inlet Pressure, 82
Manufacturer, 82
Model Number, 82
Outlet Pressure, 82
Packing Type, 82
Serial Number, 82
Shaft Stem Diameter, 82
Size, 82
Style, 82
Device Setup, 42
Travel/Pressure Select, 66
334
Instruction Manual
Index
D103412X012
August 2012
W
Weight
DVC6200f, 8
DVC6205f, 8
DVC6215, 8
Write Alarm, 48
Write Lock, 45
Resource Block, 220
Write Lock, 45
Write Priority, 46
Z
Zero Power Condition, 81
Device Setup, 42
335
Index
August 2012
336
Instruction Manual
D103412X012
N97
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, ValveLink, PlantWeb, DeltaV, and Baumann are marks owned by one of the companies in the Emerson Process Management business unit
of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.
FOUNDATION fieldbus is a mark owned by the Fieldbus Foundation. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
2010, 2012 Fisher Controls International LLC. All rights reserved.