Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

DVC6200f Instruction Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 340

Instruction Manual

DVC6200f Digital Valve Controller

D103412X012

Fisherr FIELDVUE DVC6200f Digital Valve


Controller for FOUNDATION fieldbus

This manual applies to:


Device Type
4602
Device Revision
2
Hardware Revision 8
Firmware Revision 2.0
DD Revision
2 and 3
Instrument Level
FD, PD, AD

www.Fisher.com

August 2012

The FIELDVUE DVC6200f Digital Valve Controller is a core component of the PlantWeb digital
plant architecture. The digital valve controller powers PlantWeb by capturing and delivering valve
diagnostic data. Coupled with ValveLink software, the DVC6200 provides users with an accurate
picture of valve performance, including actual stem position, instrument input signal, and
pneumatic pressure to the actuator. Using this information, the digital valve controller diagnoses
not only itself, but also the valve and actuator to which it is mounted.

Instruction Manual

DVC6200f Digital Valve Controller

D103412X012

August 2012

Contents
Section 1 Introduction and
Specifications . . . . . . . . . . . . . . . . . . . . . . 3

Figure 11. FIELDVUE DVC6200f Digital Valve


Controller

Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Instrument Description . . . . . . . . . . . . . . . . . . . . . . . . 3
Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Related Information . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Educational Services . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Section 2 Installation . . . . . . . . . . . . . . . . . 11
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DVC6200f Digital Valve Controller . . . . . . . . . . . . .
DVC6205f Base Unit . . . . . . . . . . . . . . . . . . . . . . . .
DVC6215 Feedback Unit . . . . . . . . . . . . . . . . . . . . .
SlidingStem Linear Actuators up to
210 mm (8.25 Inches) Travel . . . . . . . . . . .
Fisher Rotary Actuators and SlidingStem
Linear Actuators over 210 mm
(8.25 Inches) Travel . . . . . . . . . . . . . . . . . . .
GX Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . .
QuarterTurn Rotary Actuators . . . . . . . . . . . .
Fisher 67CFR Filter Regulator . . . . . . . . . . . . . . . . .
Pneumatic Connections . . . . . . . . . . . . . . . . . . . . . . .
Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output Connection . . . . . . . . . . . . . . . . . . . . . .
Special Construction to Support
Solenoid Valve Testing . . . . . . . . . . . . . . . .
Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring and Electrical Connections . . . . . . . . . . . . . .
Connecting Fieldbus Wiring . . . . . . . . . . . . . . . . . .
TwistedShielded Pair . . . . . . . . . . . . . . . . . . . .
Quick Connect Cable Entry . . . . . . . . . . . . . . .
Remote Travel Sensor Connections . . . . . . . . . . . .
Communication Connections . . . . . . . . . . . . . . . . .
Simulate Enable Jumper . . . . . . . . . . . . . . . . . . . . . . .
Commissioning Tag . . . . . . . . . . . . . . . . . . . . . . . . . .

11
11
11
14
16
18
20
22
25
26
26
26
27
28
29
30
31
31
32
33
34
36
36
27

Section 3 Basic Setup . . . . . . . . . . . . . . . . . 39

W9713_fieldbus

Input Selector Function Block . . . . . . . . . . . . . . . . .


Output Splitter Function Block . . . . . . . . . . . . . . . .
Analog Input Function Block . . . . . . . . . . . . . . . . . .
Mulitple Analog Input Function Block . . . . . . . . . .
Discrete Output Function Block . . . . . . . . . . . . . . .
Discrete Input Function Block . . . . . . . . . . . . . . . . .

145
160
171
183
189
201

Section 5 Calibration . . . . . . . . . . . . . . . . 213


Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . .
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Auto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply Pressure Sensor . . . . . . . . . . . . . . . . . . . . .
Pressure A or B Sensor . . . . . . . . . . . . . . . . . . . . . .

213
213
214
214
215
216
217

Section 6 Viewing Device


Variables and Diagnostics . . . . . . . . . . 219

Section 4 Detailed Setup . . . . . . . . . . . . . . 45

View Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . .
Device Variables . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . .
Device Variables . . . . . . . . . . . . . . . . . . . . . . . . . . .

Resource Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Analog Output Function Block . . . . . . . . . . . . . . . . 113
Proportional/Integral/Derivative
Function Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126

Replacing the Magnetic Feedback Assembly . . . . . 234


Module Base Maintenance . . . . . . . . . . . . . . . . . . . . 234
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234

Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Block Mode . . . . . . . . . . . . . . . . . . . . . .
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Performance Tuner . . . . . . . . . . . . . . . . . . . . . . . . .

39
39
39
40
44

219
219
220
222
223
224
229

Section 7 Maintenance and


Troubleshooting . . . . . . . . . . . . . . . . . . 233

Instruction Manual

DVC6200f Digital Valve Controller


August 2012

Component Replacement . . . . . . . . . . . . . . . . . . .
Removing the Module Base . . . . . . . . . . . . . . . . .
Replacing the Module Base . . . . . . . . . . . . . . . . . .
Submodule Maintenance . . . . . . . . . . . . . . . . . . . . .
I/P Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Printed Wiring Board (PWB) Assembly . . . . . . . . .
Pneumatic Relay . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gauges, Pipe Plugs or Tire Valves . . . . . . . . . . . . .
Terminal Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the Terminal Box . . . . . . . . . . . . . . . . .
Replacing the Terminal Box . . . . . . . . . . . . . . . . .
Stroking the Digital Valve Controller Output . . . . .
DVC6215 Feedback Unit . . . . . . . . . . . . . . . . . . . . .
Instrument Troubleshooting . . . . . . . . . . . . . . . . . .

D103412X012

235
235
236
237
237
239
240
241
241
241
242
242
242
243

Section 8 Parts . . . . . . . . . . . . . . . . . . . . . 249


Parts Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/P Converter Assembly . . . . . . . . . . . . . . . . . . . . .
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PWB Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure Gauges, Pipe Plugs, or
Tire Valve Assemblies . . . . . . . . . . . . . . . . . . . .

249
249
250
250
250
250
251
251
251
252
252

Appendix A Principle of Operation . . . . . 259


Digital Valve Controller Operation . . . . . . . . . . . . . 259

Appendix B Field Communicator


Menu Tree . . . . . . . . . . . . . . . . . . . . . . . 261
Appendix C PlantWeb Alerts . . . . . . . . . . 275
Alert Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PlantWeb Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alert Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alert Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PlantWeb Alerts Set Block Status . . . . . . . . . . . . .
Setting PlantWeb Alerts . . . . . . . . . . . . . . . . . . . . . .
Using PlantWeb Alerts . . . . . . . . . . . . . . . . . . . . . . .

275
275
275
277
277
277
277

Appendix D FOUNDATION Fieldbus


Communication . . . . . . . . . . . . . . . . . . 287
Function Block Overview . . . . . . . . . . . . . . . . . . . . . 287
Function Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . 287

Instrument Specific Blocks . . . . . . . . . . . . . . . . . .


Resource Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Blocks . . . . . . . . . . . . . . . . . . . . . . . . .
Block Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explanation of Modes . . . . . . . . . . . . . . . . . . . . . .
Examples of Modes for Various
Operation Statuses . . . . . . . . . . . . . . . . . . . . . .
Device Descriptions . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Block Status and Limit Propagation . .
Status Propagation . . . . . . . . . . . . . . . . . . . . . . . .
Limit Propagation . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Communication . . . . . . . . . . . . . . . . . . . .
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . .
Link Active Scheduler . . . . . . . . . . . . . . . . . . . . . . .
Device Communications . . . . . . . . . . . . . . . . . . . .
Scheduled Transfers . . . . . . . . . . . . . . . . . . . .
Unscheduled Transfers . . . . . . . . . . . . . . . . . .
Function Block Scheduling . . . . . . . . . . . . . . . . . .
Network Management . . . . . . . . . . . . . . . . . . . . . . .

288
288
288
289
290
291
291
291
292
292
293
293
293
294
294
295
296
296

Appendix E Device Description


Installation . . . . . . . . . . . . . . . . . . . . . . 297
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Descriptions and Methods . . . . . . . . . . . . .
Installing DD on a DeltaV
ProfessionalPLUS Workstation . . . . . . . . . . . . . . . .
Installing DDs on Other Fieldbus Host Systems . . .
Displaying the Device Description Revision . . . . . .

297
298
298
300
301

Appendix F Operating with a


DeltaV System . . . . . . . . . . . . . . . . . . . 303
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transducer Block Parameter Configuration Index . . . . . . . . . . . . . . . . . . . . . . .
Resource Block Parameter - Configuration Index .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software Functionality/System Requirements . . .
Using AMS Device Manager . . . . . . . . . . . . . . . . . . .
Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing Parameters . . . . . . . . . . . . . . . . . . . . . . .
Bringing the Device OnLine . . . . . . . . . . . . . . . . . .
PlantWeb Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up PlantWeb Alerts . . . . . . . . . . . . . . . . . .

303
304
309
310
310
310
312
312
315
315
315

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325

Instruction Manual

Introduction and Specifications

D103412X012

August 2012

Section 1 Introduction and Specifications


Scope of Manual
This instruction manual is a supplement to the DVC6200 Series Quick Start Guide (D103556X012) that ships with
every instrument. This instruction manual includes product specifications, installation information, reference
materials, custom setup information, maintenance procedures, and replacement part details for the FIELDVUE
DVC6200f digital valve controller.

Note
All references to the DVC6200f digital valve controller include the DVC6205f base unit unless otherwise indicated.

This manual describes device setup using the 475 or 375 Field Communicator. For information on using Fisher
ValveLink software with the instrument, refer to the appropriate user guide or help.
Do not install, operate, or maintain a DVC6200f digital valve controller without being fully trained and qualified in
valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage,
it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions
and warnings. If you have any questions about these instructions, contact your Emerson Process Management sales
office before proceeding.

Instrument Description
DVC6200f digital valve controllers for FOUNDATION fieldbus are communicating, microprocessorbased instruments.
In addition to the traditional function of converting a digital signal to a pneumatic output pressure, the DVC6200f
digital valve controller, using FOUNDATION fieldbus communications protocol, gives easy access to information critical to
process operation as well as process control. This can be done using a DeltaV console, another FOUNDATION fieldbus
system console, or with ValveLink software version 10.2 or later.
Using a compatible fieldbus configuration device, you can obtain information about the health of the instrument, the
actuator, and the valve. You can also obtain asset information about the actuator or valve manufacturer, model, and
serial number. You can set input and output configuration parameters and calibrate the instrument.
Using the FOUNDATION fieldbus protocol, information from the instrument can be integrated into control systems.
DVC6200f digital valve controllers can be mounted on single or doubleacting slidingstem actuators, as shown in
figure 12, or on rotary actuators. It can also be integrally mounted to the Fisher GX control valve and actuator system,
as shown in figure 13. The DVC6200f mounts on most Fisher and other manufacturers' rotary and slidingstem
actuators.

Instruction Manual

Introduction and Specifications


August 2012

Figure 12 FIELDVUE DVC6200f Digital Valve


Controller Mounted on a Fisher SlidingStem Valve
Actuator

D103412X012

Figure 13. FIELDVUE DVC6200f Digital Valve


Controller Integrally Mounted to a Fisher GX Control
Valve and Actuator System

W9616_fieldbus
W9643_fieldbus

DVC6200f digital valve controllers are available with several selections of control and diagnostic capability. Control
selections include:
Standard Control (SC) Digital valve controllers with Standard Control have the AO, PID, ISEL, OS, AI, MAI, DO, and
four DI function blocks in addition to the resource and transducer blocks.
Fieldbus Control (FC)Digital valve controllers with Fieldbus Control have the AO function block in addition to the
resource and transducer blocks.
Fieldbus Logic (FL)Digital valve controllers with Fieldbus Logic have the DO, and four DI function blocks, in
addition to the resource and transducer block.
The diagnostic capabilities include:
Performance Diagnostics (PD)
Advanced Diagnostics (AD)
Fieldbus Diagnostics (FD)
Performance and Advanced Diagnostics are available with ValveLink software. They provide visibility to instrument
alerts. Fieldbus Diagnostics can be viewed with any host system.

Instruction Manual

Introduction and Specifications

D103412X012

August 2012

Instrument Blocks
The digital valve controller is a blockbased device. For detailed information on the blocks within the digital valve
controller, see the Detailed Setup section of this manual.
The DVC6200f digital valve controller includes the resource and transducer block:
Resource BlockThe resource block contains the hardware specific characteristics associated with a device; it has
no input or output parameters. The resource block monitors and controls the general operation of other blocks
within the device. For example, when the mode of the resource block is Out of Service, it impacts all function
blocks.
Transducer BlockThe transducer block connects the analog output function block to the I/P converter, relay, and
travel sensor hardware within the digital valve controller.

Function Blocks
In addition to the resource and transducer block, the digital valve controller may contain the following function blocks.
For additional information on function blocks, refer to Appendix D, FOUNDATION fieldbus Communication.
Analog Output (AO) Function BlockThe analog output function block accepts the output from another function
block (such as a PID block) and transfers it as an actuator control signal to the transducer block. If the DO block is
selected, the AO block is not functional.
ProportionalIntegralDerivative (PID) Function BlockThe PID function block performs
proportionalplusintegralplusderivative control.
Input Selector (ISEL) Function BlockThe input selector function block selects from up to four inputs and may
provide the selected signal as input to the PID block. The input selection can be configured to select the first good
input signal; a maximum, minimum or average value; or a hot spare.
Output Splitter (OS) Function BlockThe output splitter function block accepts the output from another function
block (such as a PID block) and creates two outputs that are scaled or split, according to the user configuration. This
block is typically used for split ranging of two control valves.
Analog Input (AI) Function BlockThe analog input function block monitors the signal from a DVC6200f sensor or
internal measurement and provides it to another block.
Multiple Analog Input (MAI) Function BlockThe Multiple Analog Input (MAI) function block has the ability to
process up to eight DVC6200f measurements and make them available to other function blocks.
Discrete Output (DO) Function BlockThe discrete output function block processes a discrete set point and sends it
to a specified output channel, which can be transferred to the transducer block for actuator control. In the digital
valve controller, the discrete output block provides both normal open/closed control and the ability to position the
valve in 5% increments for course throttling applications. If the AO block is selected, the DO block is not functional.
Discrete Input (DI) Function BlockThe discrete input function block processes a single discrete input from a
DVC6200f and makes it available to other function blocks. In the digital valve controller, the discrete input function
block can provide limit switch functionality and valve position proximity detection.

Introduction and Specifications


August 2012

Instruction Manual
D103412X012

Using This Manual


Navigation paths and fastkey sequences are included for procedures and parameters that can be accessed using the
Field Communicator.
For example, to access Resource Block Mode:
Field Communicator

RB > Configure/Setup > Setup > Resource Block Mode

An overview of the resource and transducer block menu structures are shown in Appendix B. Menu structures for the
function blocks are included with each function block section in Detailed Setup.
Throughout this document, parameters are typically referred to by their common name or label, followed by the
parameter name and index number; for example, Write Priority (WRITE_PRI [39]). However, not all interface systems
support the use of the parameter label and instead use only the Parameter Name, followed by the index number, when
referring to the block parameters.

Specifications
Specifications for the DVC6200f digital valve controller are shown in table 11.

Instruction Manual

Introduction and Specifications

D103412X012

August 2012

Table 11. Specifications


Available Mounting
DVC6200f digital valve controller and DVC6215
feedback unit:  Integral mounting to the Fisher GX
Control Valve and Actuator System  Integral
mounting to Fisher rotary actuators,  Slidingstem
linear applications  Quarterturn rotary applications
DVC6205f base unit for 2 inch pipestand or wall
mounting (for remote-mount)
The DVC6200f digital valve controller or DVC6215
feedback unit can also be mounted on other
actuators that comply with IEC 60534-6-1, IEC
60534-6-2, VDI/VDE 3845 and NAMUR mounting
standards.
Function Block Suites
 Standard Control (throttling control)
 Includes AO, PID, ISEL, OS, AI, MAI, DO,
 and four DI function block
 Fieldbus Control (throttling control)
 Contains the AO function block
 Fieldbus Logic [discrete (on/off) connectivity]
 Includes DO, and four DI function blocks
Block Execution Times
AO Block: 15 ms
PID Block: 20 ms
ISEL Block: 20 ms
OS Block: 20 ms

AI Block: 15 ms
MAI BLock: 35 ms
DO Block: 15 ms
DI Block: 15 ms

Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
Digital Communication Protocol
FOUNDATION fieldbus registered device
Physical Layer Type(s):
121Low-power signaling, buspowered,
Entity Model I.S.
511Low-power signaling, buspowered, FISCO I.S.

Fieldbus Device Capabilities


Backup Link Master capable
Supply Pressure(1)
Minimum Recommended: 0.3 bar (5 psig) higher
than maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Supply Medium
Air or natural gas
Air: Supply pressure must be clean, dry air that meets
the requirements of ISA Standard 7.0.01. A maximum
40 micrometer particle size in the air system is
acceptable. Further filtration down to 5 micrometer
particle size is recommended. Lubricant content is
not to exceed 1 ppm weight (w/w) or volume (v/v)
basis. Condensation in the air supply should be
minimized.
Natural Gas: Natural gas must be clean, dry, oilfree,
and noncorrosive. H2S content should not exceed 20
ppm.
Output Signal
Pneumatic signal, up to 95% of supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action:  Double,  Single Direct or  Reverse
Steady-State Air Consumption(2)(3)
Standard Relay: At 1.4 bar (20 psig) supply pressure:
Less than 0.38 normal m3/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than 1.3
normal m3/hr (49 scfh)
Low Bleed Relay: At 1.4 bar (20 psig) supply pressure:
Average value 0.056 normal m3/hr
(2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
0.184 normal m3/hr (6.9 scfh)
Maximum Output Capacity(2)(3)
At 1.4 bar (20 psig) supply pressure: 10.0 normal m3/hr
(375 scfh)
At 5.5 bar (80 psig) supply pressure: 29.5 normal m3/hr
(1100 scfh)
-continued-

Instruction Manual

Introduction and Specifications


August 2012

D103412X012

Table 11. Specifications (continued)


Operating Ambient Temperature Limits(1)(4)
-40 to 85C (-40 to 185F)
-52 to 85C (-62 to 185F) for instruments utilizing
the Extreme Temperature option (fluorosilicone
elastomers)
-52 to 125C (-62 to 257F) for remotemount
feedback unit

Electrical Housing
CSA Type 4X, IP66
FM NEMA 4X
ATEX IP66
IECEx IP66
The Gas Certified DVC6200f is CSA, FM, ATEX, and
IECEx approved for use with natural gas as the supply
medium

Independent Linearity(5)
Typical Value: 0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
ImmunityIndustrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 12 below.
EmissionsClass A
ISM equipment rating: Group 1, Class A
Lightning and Surge ProtectionThe degree of
immunity to lightning is specified as Surge immunity
in table 12. For additional surge protection
commercially available transient protection devices
can be used.
Vibration Testing Method
Tested per ANSI/ISA75.13.01 Section 5.3.5. A
resonant frequency search is performed on all three
axes. The instrument is subjected to the ISA specified
1/2 hour endurance test at each major resonance.

Other Classifications/Certifications
INMETRO Brazil
KGS Korea
NEPSI China
TIIS Japan
Contact your Emerson Process Management sales
office for classification/certification specific
information
Connections
Supply Pressure: 1/4 NPT internal and integral pad for
mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Tubing: 3/8inch recommended
Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal, M20 adapter optional
Actuator Compatibility

Humidity Testing Method


Tested per IEC 61514-2
Electrical Classification
Hazardous Area Approvals
CSA Intrinsically Safe and FISCO, Explosionproof,
Division 2, Dust Ignitionproof
FM Intrinsically Safe and FISCO, Explosionproof,
NonIncendive, Dust Ignitionproof
ATEXIntrinsically Safe, FISCO and Dust,
Flameproof and Dust, Type n and Dust
IECEx Intrinsically Safe and FISCO, Flameproof,
Type n

Stem Travel (SlidingStem Linear)


Minimum: 6.35 mm (0.25 inch)
Maximum: 606 mm (237/8 inches)
Shaft Rotation (QuarterTurn Rotary)
Minimum: 45
Maximum: 90
Weight
DVC6200f
Aluminum: 3.5 kg (7.7 lbs)
Stainless Steel: 8.6 kg (19 lbs)
DVC6205f: 4.1 kg (9 lbs)
DVC6215: 1.4 kg (3.1 lbs)
-continued-

Instruction Manual

Introduction and Specifications

D103412X012

August 2012

Table 11. Specifications (continued)


Contact your Emerson Process Management sales
office or go to www.FIELDVUE.com for additional
information.

Construction Materials
Housing, module base and terminal box: A03600 low
copper aluminum alloy (standard)
Stainless steel (optional)
Cover: Thermoplastic polyester
Elastomers: Nitrile (standard)
Fluorosilicone (extreme temperature)

Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 3 paragraph
3 of the Pressure Equipment Directive (PED) 97 / 23 /
EC. It was designed and manufactured in accordance
with Sound Engineering Practice (SEP) and cannot
bear the CE marking related to PED compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.

Options
 Supply and output pressure gauges or  Tire
valves  Integral mounted filter regulator
 LowBleed Relay  Extreme Temperature
 Natural Gas Certified  Remote Mount
 Stainless Steel

NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
2. Normal m3/hour - Normal cubic meters per hour at 0C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60F and 14.7 psia.
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Temperature limits vary based on hazardous area approval.
5. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long-stroke applications.

Table 12. EMC Summary ResultsImmunity


Port

Enclosure

Basic Standard

Electrostatic discharge (ESD)

IEC 6100042

4 kV contact
8 kV air

Radiated EM field

IEC 6100043

80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%


1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%

IEC 6100048

30 A/m at 50/60 Hz

Rated power frequency


magnetic field
Burst
I/O signal/control

Test Level

Performance
Criteria(1)

Phenomenon

A(2)

A(2)

IEC 6100044

1 kV

Surge

IEC 6100045

1 kV

Conducted RF

IEC 6100046

150 kHz to 80 MHz at 3 Vrms

Performance criteria: +/- 1% effect.


1. A = No degradation during testing. B = Temporary degradation during testing, but is selfrecovering.
2. Excluding Simulate function, which meets Performance Criteria B.

Introduction and Specifications

Instruction Manual

August 2012

D103412X012

Related Information
Fieldbus Installation and Wiring Guidelines
This manual describes how to connect the fieldbus to the digital valve controller. For a technical description, planning,
and installation information for a FOUNDATION fieldbus, refer to the FOUNDATION fieldbus Technical Overview available
from the Fieldbus Foundation and Fieldbus Installations in a DeltaV System available from your Emerson Process
Management sales office.

Related Documents
Other documents containing information related to the DVC6200f digital valve controller include:
Bulletin 62.1:DVC6200fFisher FIELDVUE DVC6200f Digital Valve Controller (D103399X012)
Bulletin 62.1:DVC6200f FDFisher FIELDVUE DVC6200f Digital Valve Controller (D103422X012)
Bulletin 62.1:DVC6200(S1)Fisher FIELDVUE DVC6200 Digital Valve Controller Dimensions (D103543X012)
Fisher FIELDVUE DVC6200 Series Quick Start Guide (D103556X012)
475 Field Communicator User's Manual
ValveLink Software Help or Documentation
All documents are available from your Emerson Process Management sales office. Also visit our website at
www.FIELDVUE.com.

Educational Services
For information on available courses for the DVC6200f digital valve controller, as well as a variety of other products,
contact:
Emerson Process Management
Educational Services, Registration
P.O. Box 190; 301 S. 1st Ave.
Marshalltown, IA 50158-2823
Phone: 800-338-8158 or
Phone: 641-754-3771
FAX: 641-754-3431
email: education@emerson.com

10

Instruction Manual

Installation

D103412X012

August 2012

Section 2 Installation2-2Installation
WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before proceeding
with any Installation procedures:
Always wear protective clothing, gloves, and eyewear to prevent personal injury or property damage.
If installing into an existing application, also refer to the WARNINGS at the beginning of the Maintenance section of this
instruction manual.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.

WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.

Refer to the quick start guide that ships with the instrument (D103556X012) for Hazardous Area Approvals and Special
Instructions for Safe Use and Installations in Hazardous Locations.

Mounting
DVC6200f Digital Valve Controller
The DVC6200f housing is available in two different configurations, depending on the actuator mounting method.
Figure 21 shows the available configurations.
Figure 21. Housing Configurations
HOUSING FOR
LINEAR AND ROTARY ACTUATORS

HOUSING FOR
FISHER GX ACTUATORS
INTEGRAL OUTPUT
PRESSURE PORT

ROTARY NAMUR, M6
LINEAR, M8
W9703

W9704

SLOTS FOR
MOUNTING BOLTS

HOLE FOR
MOUNTING BOLT

11

Installation

Instruction Manual

August 2012

D103412X012

The feedback system for the DVC6200f digital valve controller utilizes a magnetic assembly for linkageless,
noncontacting position measurement. In order to prevent inadvertent stem movement while the instrument is in
operation, magnetic tools (such as a magnetictipped screwdriver) should not be used.

Note
The magnet assembly may be referred to as a magnetic array in user interface tools.

CAUTION
The magnet assembly material has been specifically chosen to provide a longterm stable magnetic field.
However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet
placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment
include, but are not limited to: transformers, DC motors, stacking magnet assemblies.

CAUTION
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless
of the positioner model, high power magnets can affect the positioners ability to control the valve. Technicians should
avoid the use of high power magnets in close proximity with any positioner.

Use of Magnetic Tools with the DVC6200f


Magnetic Tip Screw Drivers Magnetic tip screw drivers can be used to work on the DVC6200f. However, they should
not be brought in close proximity to the magnet Assembly (located at the back of the instrument) during process
operations.
Calibrator Strap Magnets These are high power magnets used to hold 4-20 ma calibrators.
Normally, these calibrators would not be used while an instrument is controlling the process.
High power magnets should be kept at least 15 cm (6 inches) from the DVC6200f.

Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6200f housing) has to remain within this range throughout the entire valve travel. See figure 22. The
linear magnet assemblies are symmetrical. Either end may be up.

12

Instruction Manual

Installation

D103412X012

August 2012

Figure 22. Travel Range

VALID TRAVEL RANGE


50 mm (2 INCH) SHOWN

MAGNET ASSEMBLY
(ATTACHED TO VALVE STEM)
INDEX MARK

W9706

Note
Mounting the instrument vertically, with the vent at the bottom of the assembly, or horizontally, with the vent pointing down, is
recommended to allow drainage of moisture that may be introduced via the instrument air supply.

There are a variety of mounting brackets and kits that are used to mount the DVC6200f to different actuators.
Depending on the actuator, there will be differences in fasteners, brackets, and connecting linkages.
Each mounting kit will include one of the magnet assemblies illustrated in figure 23.
Figure 23. Magnet Assemblies

RSHAFT END
ASSEMBLY 90 DEG
AVAILABLE CONSTRUCTIONS:
SSTEM #7 ASSEMBLY (7 mm / 1/4 INCH)
SSTEM #19 ASSEMBLY (19 mm / 3/4 INCH)
SSTEM #25 ASSEMBLY (25 mm / 1 INCH)
AVAILABLE CONSTRUCTIONS:
SSTEM #38 ASSEMBLY (38 mm / 11/2 INCH)
SSTEM #50 ASSEMBLY (50 mm / 2 INCH)
SSTEM #100 ASSEMBLY (100 mm / 4 INCH)
SSTEM #210 ASSEMBLY (210 mm / 8-1/4 INCH)

AVAILABLE CONSTRUCTIONS:
SSTEM #1 ROLLER ASSEMBLY
RSHAFT #1 WINDOW ASSEMBLY
(FISHER 2052 SIZE 2 & 3, 1051/1052
SIZE 4070, 1061 SIZE 30100,
SLIDINGSTEM > 210 mm (8.25 INCHES)
RSHAFT #2 WINDOW ASSEMBLY
(2052 SIZE 1, 1051/1052 SIZE 20-33)

If ordered as part of a control valve assembly, the factory will mount the digital valve controller on the actuator and
calibrate the instrument. If purchased separately, you will need a mounting kit to mount the digital valve controller on
the actuator. Each mounting kit includes detailed information on mounting the digital valve controller to a specific
actuator. Refer to table 21 for the more common Fisher actuator mounting instructions, available at www.fisher.com
or your Emerson Process Management sales office.

13

Instruction Manual

Installation
August 2012

D103412X012

For general mounting guidelines, refer to the DVC6200 Series quick start guide (D103556X012), available at
www.fisher.com or your Emerson Process Management sales office.

Table 21. FIELDVUE DVC6200f Mounting Instructions


Instructions for Mounting:

Part Number

585C/585CR Size 25 Actuator with or without Handjack

D103439X012

585C/585CR Size 50 Actuator with or without Handjack

D103440X012

657 and 667 Size 30-60 Actuators

D103441X012

657 and 667 Size 34-60 Actuators with Handwheel

D103442X012

657 and 667 Size 70, 76, and 87 Actuators (up to 2 inch travel)

D103443X012

657 and 667 Size 70, 76, and 87 Actuators (4 inch travel)

D103444X012

657 and 667 Size 80 Actuators (up to 2 inch travel)

D103445X012

657 and 667 Size 80 Actuators (4 inch travel)

D103446X012

1051 Size 33 and 1052 Size 20 and 33 Actuators (Window Mount)

D103447X012

1051 and 1052 Size 33 Actuators (End Mount)

D103448X012

1051 and 1052 Size 40-70 Actuators (Window Mount)

D103449X012

1051 and 1052 Size 40-70 Actuators (End Mount)

D103450X012

1052 Size 20 Actuator (End Mount)

D103451X012

1061 Size 30-68 Actuator (Window Mount)

D103453X012

1061 Size 80-100 Actuator (Window Mount)

D103452X012

2052 Size 1, 2, 3 Actuator (End Mount)

D103454X012

2052 Size 1, 2, 3 Actuator with Spacer (Window Mount)

D103455X012

Baumann SlidingStem Actuators

D103456X012

GX Control Valve and Actuator System

D103457X012

IEC6053461 (NAMUR) Sliding-Stem Actuators

D103458X012

IEC6053462 (NAMUR) Rotary Actuators

D103459X012

DVC6205f Base Unit


For remotemounted digital valve controllers, the DVC6205f base unit ships separately from the control valve and
does not include tubing, fittings or wiring. See the instructions that come with the mounting kit for detailed
information on mounting the feedback unit to a specific actuator model.
Mount the DVC6205f base unit on a 50.8 mm (2 inch) pipestand or wall. The included bracket is used for either
mounting method.

Wall Mounting
Refer to figures 24 and 25. Drill two holes in the wall using the dimensions shown in figure 24. Attach the mounting
bracket to the base unit using four spacers and 25.4 mm (1inch) 1/420 hex head screws. Attach the base unit to the
wall using suitable screws or bolts.

Pipestand Mounting
Refer to figure 26. Position a standoff on the back of the base unit. Using two 101.6 mm (4inch) 1/420 hex head
screws loosely attach the base unit to the pipestand with the mounting bracket. Position the second standoff, then
using the remaining 101.6 mm (4inch) hex head screws, securely fasten the base unit to the pipe stand.

14

Instruction Manual

Installation

D103412X012

August 2012

Figure 24. FIELDVUE DVC6205f Base Unit with Mounting Bracket (Rear View)

10C1796A

Figure 25. FIELDVUE DVC6205f Base Unit Wall Mounting

4INCH 1/420
HEX HEAD SCREW

STANDOFF

MOUNTING BRACKET
X0437

15

Instruction Manual

Installation
August 2012

D103412X012

Figure 26. FIELDVUE DVC6205f Base Unit Pipestand Mounting

SPACER
1INCH 1/420
HEX HEAD
SCREW

MOUNTING BRACKET
X0428

DVC6215 Feedback Unit


If ordered as part of a control valve assembly, the factory mounts the feedback unit on the actuator, makes pneumatic
connections to the actuator, sets up, and calibrates the instrument. If you purchased the feedback unit separately, you
will need a mounting kit to mount the feedback unit on the actuator. See the instructions that come with the
mounting kit for detailed information on mounting the feedback unit to a specific actuator model.
The DVC6215 housing is available in two different configurations, depending on the actuator mounting method.
Figure 27 shows the available configurations. The feedback system for the DVC6215 feedback unit utilizes a magnetic
assembly for true linkageless, noncontacting position measurement. In order to prevent inadvertent stem
movement while the instrument is in operation, magnetic tools (such as a magnetictipped screwdriver) should not be
used.
Figure 27. Feedback Unit Housing Configurations
HOUSING FOR
LINEAR AND ROTARY ACTUATORS

HOUSING FOR
FISHER GX ACTUATORS
INTEGRAL OUTPUT
PRESSURE PORT

X0124

16

LINEAR, M8

ROTARY NAMUR, M6

X0125

HOLES FOR
MOUNTING BOLT

Instruction Manual

Installation

D103412X012

August 2012

CAUTION
The magnet assembly material has been specifically chosen to provide a longterm stable magnetic field.
However, as with any magnet, care must be taken when handling the magnet assembly. Another high powered magnet
placed in close proximity (less than 25 mm) can cause permanent damage. Potential sources of damaging equipment
include, but are not limited to: transformers, DC motors, stacking magnet assemblies.

CAUTION
General Guidelines for use of High Power Magnets with Positioners
Use of high power magnets in close proximity to any positioner which is operating a process should be avoided. Regardless
of the positioner model, high power magnets can affect the positioners ability to control the valve. Technicians should
avoid the use of high power magnets in close proximity with any positioner.

Use of Magnetic Tools with the DVC6215


Magnetic Tip Screw Drivers Magnetic tip screw drivers can be used to work on the DVC6215. However, they should
not be brought in close proximity to the magnet assembly (located at the back of the instrument) during process
operations.
Calibrator Strap Magnets These are high power magnets used to hold 4-20 ma calibrators.
Normally, these calibrators would not be used while an instrument is controlling the process.
High power magnets should be kept at least 15 cm (6 inches) from the DVC6215.

Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6215 housing) has to remain within this range throughout the entire valve travel. See figure 28. The linear
magnet assemblies are symmetrical. Either end may be up.

Figure 28. Travel Range


VALID TRAVEL RANGE
50 mm (2 INCH)
SHOWN

MAGNET ASSEMBLY
(ATTACHED TO VALVE STEM)
INDEX MARK
X0126

17

Installation
August 2012

Instruction Manual
D103412X012

There are a variety of mounting brackets and kits that are used to mount the DVC6215 to different actuators.

Note
The DVC6215 feedback unit uses the same mountings as the DVC6200f digital valve controller.

However, despite subtle differences in fasteners, brackets, and connecting linkages, the procedures for mounting can
be categorized as follows:
Slidingstem linear actuators
Fisher rotary actuators
GX actuator
Quarterturn actuators
See figure 23 for examples of the different travel feedback magnet assemblies.

SlidingStem Linear Actuators up to 210 mm (8.25 Inches) of Travel


The DVC6215 feedback unit has linkageless, noncontact feedback on slidingstem actuators with up to 210 mm
(8.25 inches) travel. Figure 29 shows a typical mounting on a sliding-stem actuator. For actuators with greater than
210 mm (8.25 inches) travel, see the guidelines on page 20.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lockout procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. Attach the mounting bracket to the actuator.
Figure 29. Mounting Parts for SlidingStem Actuator with up to 210 mm (8.25 inches) Travel

X0127

18

Instruction Manual

Installation

D103412X012

August 2012

3. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.

CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the DVC6215 housing.

4. Using the alignment template (supplied with the mounting kit), position the magnet assembly inside the retaining
slot.
5. Align the magnet assembly as follows:
For airtoopen actuators (e.g. Fisher 667) vertically align the magnet assembly so that the center line of the alignment
template is lined up as close as possible with the upper extreme of the valid travel range on the magnet assembly. The
magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within
the valid range on the magnet assembly throughout the range of travel. See figure 210.
For airtoclose actuators (e.g. Fisher 657) vertically align the magnet assembly so that the center line of the alignment
template is lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly. The
magnet assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within
the valid range on the magnet assembly throughout the range of travel. See figure 211.
Figure 210. AirtoOpen Magnet Assembly
Alignment

Figure 211. AirtoClose Magnet Assembly


Alignment

ALIGNMENT
TEMPLATE
RETAINING
SLOT

INDEX
MARK

W9718

RETAINING
SLOT

ALIGNMENT
TEMPLATE

INDEX
MARK

W9719

6. Tighten the fasteners and remove the alignment template.


7. Mount the feedback unit to the mounting bracket, using the mounting bolts.

19

Instruction Manual

Installation
August 2012

D103412X012

8. Check for clearance between the magnet assembly and the DVC6215 feedback slot.

Note
Ensure that there is clearance between the magnet assembly and the DVC6215 housing slot throughout the full range of travel.

Fisher Rotary Actuators and SlidingStem Linear Actuators over 210 mm (8.25 Inches) Travel
The DVC6215 feedback unit uses a cam (designed for linear response) and roller as the feedback mechanism. See
figures 212 and 213.
Figure 212. Mounting on Rotary Actuators

Figure 213. Mounting on SlidingStem (Linear)


Actuators over 210 mm (8.25 Inches) Travel

MOUNTING
ADAPTOR

ROTARY MOUNTING
KIT (DVC6215 NOT
SHOWN)

LONG STROKE
MOUNTING
KIT (DVC6215
NOT SHOWN)

W9709
W9708

Note
All cams supplied with FIELDVUE mounting kits are characterized to provide a linear response.

There are three different mounting adaptions, based on the actuator design (see figure 214).

Fisher Rotary Actuators


Refer to the following guidelines when mounting on rotary actuators.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lockout procedures to
be sure that the above measures stay in effect while working on the equipment.

20

Instruction Manual

Installation

D103412X012

August 2012

2. Verify that the appropriate cam is installed on the actuator as described in the instructions included with the
mounting kit.
3. Mount the DVC6215 on the actuator as follows:
If required, a mounting adaptor is included in the mounting kit. Attach the adaptor to the feedback unit, then
attach the feedback unit assembly to the actuator. The roller on the feedback arm will contact the actuator cam
as it is being attached.
If no mounting adaptor is required, attach the feedback unit and mounting kit assembly to the actuator. The
roller on the feedback arm will contact the actuator cam as it is being attached.
Figure 214. Mounting Variations

ROLLER
ARM

VARIATION A
VARIATION

ROLLER
ARM

ROLLER
ARM

VARIATION B

VARIATION C

ACTUATOR
2052 Size 2 and 3
1051/1052 size 40-70
1061 Size 30-100
SlidingStem > 210 mm (8.25 inches)

B
C

2052 Size 1
1052 Size 20-33
1051 Size 33

NOTE THE DIFFERENCE IN THE SHAPE AND LENGTH OF THE ROLLER ARM
E1229

21

Installation
August 2012

Instruction Manual
D103412X012

SlidingStem Linear Actuators over 210 mm (8.25 Inches) Travel


Refer to the following guidelines when mounting on slidingstem linear actuators over 210 mm (8.25 inches) travel
(see figure 213).
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the pneumatic actuator, releasing all pressure from the actuator. Use lockout procedures to
be sure that the above measures stay in effect while working on the equipment.
2. Install the cam to the valve stem connector as described in the instructions included with the mounting kit.
3. Install the mounting adaptor to the actuator.
4. Attach the feedback unit and mounting kit assembly to the mounting adaptor. The roller on the feedback arm will
contact the actuator cam as it is being attached.

GX Actuators
The DVC6215 feedback unit mounts directly on the GX actuator without the need for a mounting bracket.
Identify the yoke side to mount the DVC6215 feedback unit based on the actuator fail mode. Refer to the GX Control
Valve and Actuator System instruction manual (D103175X012).
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lockout procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. Loosely attach the feedback pieces and magnet assembly to the valve stem connector. Do not tighten the fasteners
because fine adjustment is required.

CAUTION
Do not install a magnet assembly that is shorter than the physical travel of the actuator. Loss of control will result from the
magnet assembly moving outside the range of the index mark in the feedback slot of the DVC6215 housing.

3. Using the alignment template (supplied with the mounting kit), position the feedback assembly inside the retaining
slot.
4. Align the magnet assembly as follows:
For airtoopen GX actuators vertically align the magnet assembly so that the center line of the alignment template is
lined up as close as possible with the upper extreme of the valid travel range on the magnet assembly. The magnet
assembly should be positioned so that the index mark in the feedback slot of the DVC6215 housing is within the valid
range on the magnet assembly throughout the range of travel. See figure 215.
For airtoclose GX actuators vertically align the magnet assembly so that the center line of the alignment template is
lined up as close as possible with the lower extreme of the valid travel range on the magnet assembly. The magnet
assembly should be positioned so that the index mark on the pole pieces (back of the DVC6215 housing) is within the
valid range on the magnet assembly throughout the range of travel. See figure 216.

22

Instruction Manual

Installation

D103412X012

August 2012

Figure 215. AirtoOpen Fisher GX Magnet Assembly


Alignment

Figure 216. AirtoClose Fisher GX Magnet Assembly


Alignment

ALIGNMENT TEMPLATE

ALIGNMENT TEMPLATE

RETAINING
SLOT

INDEX MARK

W9218

RETAINING
SLOT

INDEX MARK

W9219

5. Tighten the fasteners and remove the alignment template. Continue on with the appropriate step 6 below.

AirtoOpen GX Actuators
6. The pneumatic output port on the DVC6215 lines up with the integral GX actuator pneumatic port. See figure 217.
7. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad on the side that has the open
pneumatic port. Be sure to place the Oring between the feedback units pneumatic output and the actuator
mounting pad. Pneumatic tubing between the feedback unit and the actuator is not required because the air
passages are internal to the actuator.
8. Connect the pneumatic tubing from the DVC6205f to the feedback units pneumatic port provided on the front of
the DVC6215 as shown in figure 217.
9. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
10. If not already installed, install a vent in the port on the upper diaphragm casing's air supply connection on the
actuator yoke leg.

23

Instruction Manual

Installation
August 2012

D103412X012

Figure 217. Modifications for Fisher GX Actuator; AirtoOpen Construction Only

PNEUMATIC
PORT

PNEUMATIC TUBING
FROM THE DVC6205f

INSTALL
ORING

X0128

AirtoClose GX Actuators
6. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad.
7. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
8. Install tubing between the actuator casing and the appropriate DVC6215 pneumatic output port.
9. If not already installed, install a vent in the port on the lower diaphragm casing.

Note
To convert to air-to-open, install an Oring between the feedback units pneumatic output and the actuator mounting pad.
Connect pneumatic tubing from the DVC6205f to the DVC6215. Refer to figure 217.
To convert to air-to-close, remove the Oring between the feedback units pneumatic output and the actuator mounting pad.
Disconnect the pneumatic tubing from the DVC6205f to the DVC6215. Install tubing between the pneumatic output connection
of the DVC6205f to the pneumatic port on top of the actuator casing.

24

Instruction Manual

Installation

D103412X012

August 2012

QuarterTurn Rotary Actuators


The DVC6215 feedback unit can be mounted to any quarterturn rotary actuator, as well as those that comply with the
NAMUR guidelines. A mounting bracket and associated hardware are required. Refer to figure 218.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut
off all pressure lines to the actuator, releasing all pressure from the actuator. Use lockout procedures to be sure
that the above measures stay in effect while you work on the equipment.
2. Attach the magnet assembly to the actuator shaft. At midtravel, the flats on the magnet assembly must be parallel
to the channel on the back of the DVC6215 housing, as shown in figure 219.
3. Install the mounting bracket on the actuator.
4. Attach the feedback unit to the mounting bracket using the 4 mounting bolts, as shown in figure 218.
5. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
6. Install tubing between the actuator casing and the appropriate DVC6215 pneumatic output port.
Figure 218. Mounting on QuarterTurn Actuators

Figure 219. Magnet Assembly Orientation on


QuarterTurn Actuators
ORIENTATION
AT ONE TRAVEL
EXTREME

ORIENTATION
AT MIDTRAVEL
(FLATS PARALLEL
TO DVC6215
CHANNEL)

M6 MOUNTING
BOLTS (4)
X0129

ORIENTATION
AT THE OTHER
TRAVEL EXTREME

25

Instruction Manual

Installation
August 2012

D103412X012

Fisher 67CFR Filter Regulator


A 67CFR filter regulator, when used with a DVC6200f digital valve controller, can be mounted one of three ways.

IntegralMounted Regulator
Refer to figure 220. Lubricate an Oring and insert it in the recess around the SUPPLY connection on the digital valve
controller. Attach the 67CFR filter regulator to the side of the digital valve controller. Thread a 1/4inch sockethead
pipe plug into the unused outlet on the filter regulator. This is the standard method of mounting the filter regulator.
Figure 220. Mounting the Fisher 67CFR Regulator on a FIELDVUE DVC6200f Digital Valve Controller

67CFR

CAP SCREWS
ORING
NOTE:
1 APPLY LUBRICANT

SUPPLY CONNECTION

W9702-fieldbus

YokeMounted Regulator
Mount the filter regulator with two cap screws to the predrilled and tapped holes in the actuator yoke. Thread a
1/4inch sockethead pipe plug into the unused outlet on the filter regulator. No Oring is required.

CasingMounted Regulator
Use the separate 67CFR filter regulator casing mounting bracket provided with the filter regulator. Attach the
mounting bracket to the 67CFR and then attach this assembly to the actuator casing. Thread a 1/4inch sockethead
pipe plug into the unused outlet on the filter regulator. No Oring is required.

Pneumatic Connections
Pressure
Pressure connections are shown in figure 221. All pressure connections on the digital valve controller are 1/4 NPT
internal connections. Use at least10 mm (3/8inch) tubing for all pressure connections. If remote venting is required a
minimum of 12.7 mm (1/2inch) tubing should be used. Refer to the vent subsection for remote venting information.

26

Instruction Manual

Installation

D103412X012

August 2012

Figure 221. Pressure Connections


LOOP CONNECTIONS
TERMINAL BOX
1/2 NPT CONDUIT
CONNECTION

WIRING
TERMINAL BOX
OUTPUT A
CONNECTION

SUPPLY
CONNECTION

X0379-fieldbus

FEEDBACK CONNECTIONS
TERMINAL BOX

DVC6205f BASE UNIT

W9615-fieldbus

OUTPUT B
CONNECTION

VALVE MOUNTED UNIT

Supply
The DVC6200f can be used with air as the supply medium. In addition, Gas Certified DVC6200f constructions can be
used with natural gas as the supply medium. If using natural gas as the pneumatic supply medium, natural gas will be
used in the pneumatic output connections of the DVC6200f to any connected equipment. In normal operation the
unit will vent the supply medium into the surrounding atmosphere unless it is remotely vented.

WARNING
Not all DVC6200f digital valve controllers are suitable for use with natural gas as the supply medium. If using natural gas as
the supply medium, the DVC6200f must be Gas Certified. Using natural gas as the supply medium in a noncertified
instrument can result in personal injury or property damage.
Gas Certified instruments can be identified by the natural gas approval label shown in figure 222. Contact your Emerson
Process Management sales office for information on obtaining a Gas Certified DVC6200f digital valve controller.

Figure 222. Label for Natural Gas Certified Terminal Box

27

Installation
August 2012

Instruction Manual
D103412X012

WARNING
To avoid personal injury or property damage resulting from bursting or parts, do not exceed maximum supply pressure.
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and
appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of
the following: Remote venting of the unit, reevaluating the hazardous area classification, ensuring adequate ventilation,
and the removal of any ignition sources. For information on remote venting of this controller, refer to
page 30.
Severe personal injury or property damage may occur from an uncontrolled process if the instrument supply medium is not
clean, dry, oilfree, and noncorrosive. While use and regular maintenance of a filter that removes particles larger than 40
micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and
industry instrument air quality standards for use with corrosive air or if you are unsure about the amount of air filtration or
filter maintenance.

Supply pressure must be clean, dry air that meets the requirements of ISA Standard 7.0.01. A maximum 40
micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is
recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air
supply should be minimized.
Alternatively, natural gas may be used as the supply pressure medium in Gas Certified DVC6200f digital valve
controllers. Gas must be clean, dry, oilfree, and noncorrosive. H2S content should not exceed 20 ppm.
If you are using a 67CFR filter regulator with standard 5 micrometer filter, connect the supply line to the 1/4 NPT IN
connection and attach tubing from the output connection on the filter regulator to the SUPPLY connection on the
instrument. If you are using an integral mounted 67CFR filter regulator, connect the supply to the IN connection on
the regulator.

Output Connection
A factory mounted digital valve controller has its output piped to the supply connection on the actuator. If mounting
the digital valve controller in the field, connect the 1/4 NPT digital valve controller output connection to the
pneumatic actuator input connection.

SingleActing Actuators
When using a singleacting direct digital valve controller (relay A or C) on a singleacting actuator, connect OUTPUT A
to the actuator pneumatic input. When using a singleacting reverse digital valve controller (relay B) on a singleacting
actuator, connect OUTPUT B to the actuator diaphragm casing.

DoubleActing Actuators
DVC6200f digital valve controllers on doubleacting actuators always use relay A. With no instrument Fieldbus power
(Zero Power Condition) OUTPUT A is at 0 pressure and OUTPUT B is at full supply pressure when the relay is properly
adjusted. To have the actuator stem extend from the cylinder with increasing input signal, connect OUTPUT A to the
upper actuator cylinder connection. Connect OUTPUT B to the lower cylinder connection. To have the actuator stem
retract into the cylinder with increasing input signal, connect OUTPUT A to the lower actuator cylinder connection.
Connect OUTPUT B to the upper cylinder connection.

28

Instruction Manual

Installation

D103412X012

August 2012

Special Construction to Support Solenoid Valve Testing


Note
Solenoid valve testing is only available for instrument level PD.

In singleacting actuator applications with a solenoid valve installed, the DVC6200f can be configured to monitor the
health of the solenoid valve test, which is initiated by the Logic Solver. This is accomplished by connecting the unused
output port B from the DVC6200f to the pneumatic monitoring line between the solenoid valve and the actuator, as
shown in figure 223. When singleacting, direct relay C is installed, the unused output port is port B. When
singleacting, reverse relay B is used, the unused port is port A.
Figure 223. Pneumatic Hookup for Solenoid Testing (Instrument Level PD only)
24/48 VDC
110/220 VAC, etc.

FOUNDATION FIELDBUS
H1 SEGMENT

CONTROL LINE

Port A
Port B

DVC6200f DIGITAL VALVE


CONTROLLER WITH RELAY C

SUPPLY PRESSURE

MONITORING LINE

NOTES:

1/418 NPT X 3/8 OD TUBING


ELECTRICAL WIRING

SPRING RETURN ACTUATOR

Note
This application is called special application in the Setup Wizard relay selection.
This configuration is not possible with a doubleacting actuator or when using relay A in singleacting mode.

29

Installation
August 2012

Instruction Manual
D103412X012

Vent
WARNING
Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent
opening is open and free of debris to prevent pressure buildup under the cover.

WARNING
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a nonhazardous
(nonclassified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
reclassification.
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
reclassification.
Vent line piping should comply with local and regional codes, should be as short as possible with a minimum inside
diameter of 12.7 mm (1/2inch), and few bends to reduce case pressure buildup.
In addition to remote venting of the unit, ensure that all caps and covers are correctly installed. Failure to do so could result
in personal injury or property damage from fire or explosion, and area reclassification.

The relay constantly bleeds a small amount of supply medium into the area under the cover. The vent opening, located
below the wiring terminal box on the side of the housing, should be left open to prevent pressure buildup under the
cover. If a remote vent is required, the vent lines must be as short as possible with a minimum number of bends and
elbows.
To connect a remote vent, remove the plastic vent. The vent connection is 3/8 NPT. At a minimum, 12.7 mm
(1/2inch) tubing should be used when installing a remote vent to prevent excessive pressure from building up under
the cover.

30

Instruction Manual
D103412X012

Installation
August 2012

Wiring and Electrical Connections


Connecting Fieldbus Wiring
The digital valve controller is normally powered over the bus from a fieldbus power supply. Refer to the site planning
guide for proper wire types, termination, length, etc. for a fieldbus loop.

Note
As shipped from the factory, the DVC6200f digital valve controller will not move the valve when power is applied to the
instrument. To avoid the valve going to an unknown position when power is applied, the unit is shipped from the factory with the
transducer block mode Out of Service. See the Basic Setup section for information on setup and calibration and placing the
instrument in service.

WARNING
To avoid personal injury resulting from electrical shock, do not exceed the maximum input voltage specified in table 11 of
this quick start guide, or on the product nameplate. If the input voltage specified differs, do not exceed the lowest specified
maximum input voltage.

WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous area, ingress protection and
temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially
explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere
conditions permit the safe removal of the terminal box cover before proceeding.

31

Instruction Manual

Installation
August 2012

D103412X012

Twisted Shielded Pair


Refer to figure 82 for identification of parts.
Wire the digital valve controller as follows, refer to figure 224:
Figure 224. Loop Connections Terminal Box
SAFETY
GROUND

TALK
TALK

EARTH
GROUND
LOOP
LOOP
GE41456-A

1. Remove the wiring terminal box cap.


2. Bring the field wiring into the terminal box. When applicable, install conduit using local and national electrical codes
which apply to the application.
3. The instrument is not polarity sensitive. Connect one wire from the H1 card output to one of the LOOP screw
terminals on the pwb/terminal strip assembly in the terminal box shown in figure 224. Connect the other wire from
the H1 card output to the other LOOP screw terminal in the terminal box.

WARNING
Personal injury or property damage can result from the discharge of static electricity. Connect a 14 AWG (2.08 mm2)
ground strap between the digital valve controller and earth ground when flammable or hazardous gases are present. Refer
to national and local codes and standards for grounding requirements.

4. As shown in figure 224, two ground terminals are available for connecting a safety ground, earth ground, or drain
wire. The safety ground terminal is electrically identical to the earth ground. Make connections to these terminals
following national and local codes and plant standards.

WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.

32

Instruction Manual

Installation

D103412X012

August 2012

5. Replace and hand tighten the cover on the terminal box. To secure the terminal box cap engage the lock screw.
When the loop is ready for startup, apply power to the H1 card output.

Quick Connect Cable Entry


The DVC6200f is offered with a quick connect cable entry option, shown in figure 225, for the FOUNDATION fieldbus
signal. The quick connect cable entry provides an easier and more reliable interface to fieldbus devices and support
modules by providing a standard connection.
Figure 225. Quick Connect Connector
1 (BLUE)

2 (BROWN)

3 (NC)

4 (GREEN/YELLOW)

1/214 NPT
NOTES:
1.COLORS ARE WIRE COLORS.
2.NC=NO CONNECTION.
18B9424A

Note
The quick connect cable entry option is only available for intrinsically safe and nonincendive installations.

Refer to figure 82 for identification of parts.

WARNING
Personal injury or property damage, caused by fire or explosion, can result from the discharge of static electricity. Connect
a 14 AWG (2.08 mm2) ground strap between the digital valve controller and earth ground when flammable or hazardous
gases are present. Refer to national and local codes and standards for grounding requirements.
To avoid static discharge from the plastic cover, do not rub or clean the cover with solvents. Clean with a mild detergent
and water only.
To avoid personal injury or property damage, do not use the Quick Connect option on instruments in explosionproof or
flameproof installations.

1. The quick connect cable entry should be installed on the digital valve controller at the factory. If it is, proceed to
step 3. If not continue with step 2.
2. To install the Quick Connect:
a. Remove the terminal box cap (key 4) from the terminal box (key 3).
b. Apply sealant to the threads of the quick connector.
c. Insert the wire pigtail into the desired conduit opening on the terminal box. Tighten the quick connector in the
conduit opening.
d. Cut and trim the wire ends.

33

Installation
August 2012

Instruction Manual
D103412X012

e. The instrument is not polarity sensitive. Refer to figure 224. Connect the blue wire to one of the LOOP terminals
in the terminal box. Connect the brown wire to the other LOOP terminal. Cut the green/yellow wire off inside of
the DVC6200f, and ensure that the shield is totally isolated at the instrument end.

Note
The green/yellow wire is cut off inside the DVC6200f to help prevent ground loop issues. The only wires that should be installed
and left on the connector are the two signal wires.

f. Replace the terminal box cap on the terminal box. To secure the terminal box cap engage the lock screw.
3. Connect the field wiring connector to the installed quick connector.

Remote Travel Sensor Connections


The DVC6205f base unit is designed to receive travel information via the Emerson Process Management supplied
DVC6215 feedback unit.

WARNING
Personal injury or property damage, caused by wiring failure, can result if the feedback wiring connecting the base unit
with the remote feedback unit shares a conduit with any other power or signal wiring.
Do not place feedback wiring in the same conduit as other power or signal wiring.

Note
4conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection
between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator has been tested to 15
meters (50 feet) maximum without performance degradation.

1. On the feedback unit, remove the housing cap.


2. On the base unit, remove the feedback connections terminal box cap (see figure 221).
3. Install conduit between the feedback unit and the base unit following applicable local and national electrical codes.
Route the 4conductor shielded cable between the two units (refer to figure 226).
4. Connect one wire of the 4conductor shielded cable between terminal 1 on the feedback unit and terminal 1 on the
base unit.
5. Connect the second wire of the 4conductor shielded cable between terminal 2 on the feedback unit and terminal 2
on the base unit.
6. Connect the third wire of the 4conductor shielded cable between terminal 3 on the feedback unit and terminal 3
on the base unit.
7. Connect the fourth wire of the 4conductor shielded cable between terminal 4 on the feedback unit and terminal 4
on the base unit.

34

Instruction Manual

Installation

D103412X012

August 2012

Figure 226. Terminal Details for Connecting the Base Unit and Feedback Unit for RemoteMounted Digital Valve
Controllers

FEEDBACK
CONNECTIONS
TERMINAL BOX

X0131-FF

FEEDBACK UNIT
GROUND
SCREW

BASE UNIT
TO FEEDBACK UNIT TERMINAL 1
TO FEEDBACK UNIT TERMINAL 2
TO FEEDBACK UNIT TERMINAL 3
TO FEEDBACK UNIT TERMINAL 4

TO FEEDBACK UNIT TERMINAL S


USING CABLE SHIELD

FEEDBACK CONNECTIONS
TERMINAL BOX

TERMINAL 1
TERMINAL 2

TERMINAL S
TERMINAL 4
TERMINAL 3

FEEDBACK UNIT

WARNING
The cable shield is typically not insulated. It is required that you insulate the cable shield prior to installation.
When connecting the cable shield in step 8 ensure that the uninsulated shield wiring does not contact the DVC6215
housing. Failure to do so can result in ground loop issues.

8. Connect the cable shield between terminal S on the feedback unit and terminal S on the base unit.

CAUTION
Failure to secure the cable wires in the support clips in step 9 can cause wires to break in applications with high levels of
vibration.

9. Secure the cable wires, using the support clips in the DVC6215 feedback unit (as shown in figure 227), to help
prevent shifting and movement of the wires.
10. Replace and handtighten all covers.

35

Instruction Manual

Installation
August 2012

D103412X012

Figure 227. Secure Wires in Clips


CLIP TO SUPPORT THE WIRES OF
THE 4-CONDUCTOR SHIELDED CABLE
CLIP TO SUPPORT THE
INSULATED SHIELD WIRE

Communication Connections
WARNING
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially
explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere
conditions permit the safe removal of the terminal box cap before proceeding.

A FOUNDATION fieldbus communicating device, such as a Field Communicator or a personal computer running
ValveLink software, interfaces with the DVC6200f digital valve controller from any wiring termination point in the
segment. If you choose to connect the fieldbus communicating device directly to the instrument, attach the device to
the LOCAL connections inside the terminal box to provide local communications with the instrument.

Simulate Enable Jumper


WARNING
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially
explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere
conditions permit the safe removal of the terminal box cap before proceeding.

Install a jumper across the SIMULATE ENABLE terminals to enable the instrument to accept a simulate command.
(These terminals are marked AUX on the terminal board, see figure 224). With the jumper in place and the simulate
parameter in the AO or DO block set to enabled, the transducer block ignores the output of the AO or DO block. The
simulate value and status become the readback value and status to the AO or DO block and the transducer block is
ignored. For more information on running simulations, see the Detailed Setup section of this manual, the FOUNDATION
fieldbus specifications, and the host documentation.

WARNING
Removing the jumper will disable the simulate, which may cause the valve to move. To avoid personal injury and property
damage caused by the release of pressure or process fluid, provide some temporary means of control for the process.

36

Instruction Manual
D103412X012

Installation
August 2012

Commissioning Tag
The DVC6200f digital valve controller is supplied with a removable paper commissioning tag, shown in figure 228.
This tag contains both the device ID and a space to record the device's tag number. The device ID is a unique code that
identifies a particular device in the absence of a device tag. The device tag is used as an operational identification for
the device and is usually defined by the piping and instrumentation diagram (P&ID).
Figure 228. Paper Commissioning Tag

18B9406G

When commissioning more than one device on a fieldbus segment, identifying which device is at a particular location
can be tedious without tags. The removable tag provided with the digital valve controller can be used to link the
device ID and the physical installation location. The installer should note the physical location in both places on the
removable commissioning tag and tear off the bottom portion. This should be done for each device on the segment.
The bottom portion of the tags can be used for commissioning the segment in the control system.
Prior to commissioning, the device ID is displayed by the host system if no device tag is configured in the digital valve
controller electronics. Typically the placeholder displays the device tag. The information on the paper tag enables the
engineer to match the device ID to the correct placeholder.
As an ordering option, the factory can enter a device tag into the digital valve controller electronics during the
manufacturing process. If this option is specified, the device tag is displayed at the host system prior to commissioning
rather than the device ID. This makes the job of commissioning the device easier.

37

Installation
August 2012

38

Instruction Manual
D103412X012

Instruction Manual

Basic Setup

D103412X012

August 2012

Section 3 Basic Setup3-3Basic Setup


Field Communicator

TB > Configure/Setup > Basic Setup

WARNING
Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application,
these changes may upset process control, which may result in personal injury or property damage.

When the DVC6200f digital valve controller is ordered as part of a control valve assembly, the factory mounts the
digital valve controller and sets up the instrument as specified on the order. When mounting to a valve in the field, the
instrument needs to be setup to match the instrument to the valve and actuator.
Before beginning basic setup, be sure the instrument is correctly mounted as described in the Installation section.
Basic Setup includes the following procedures:
Device Setup
Auto Travel Calibrate
Performance Tuner (Optional)

Note
The DVC6200f may keep the Transducer Block Mode OutofService if the instrument is not properly mounted.
To setup and calibrate the instrument, the Transducer Block Mode must be Manual, and the Protection must be None.
When using DD methods the method will request that you change the mode, but make changes in Protection automatically. If you
have a host system that overrides transducer block parameters ensure that the Protection setting is not left as None. Doing so will
result in transducer block parameters being overwritten.

Transducer Block Mode


Field Communicator

TB > Configure/Setup > Detailed Setup > Transducer Block Mode

To setup and calibrate the instrument, the transducer block mode must be in Manual. For more information about
transducer block mode, refer to page 62.

Protection
Field Communicator

TB > Configure/Setup > Detailed Setup > Protection

To setup and calibrate the instrument, the protection must be set to None with the Field Communicator. For more
information about configuration protection refer to page 62.

39

Instruction Manual

Basic Setup
August 2012

D103412X012

Device Setup
Field Communicator

TB > Configure/Setup > Basic Setup > Device Setup

Follow the prompts on the Field Communicator display to automatically setup the instrument using specified actuator
information. Table 32 provides the actuator information required to setup and calibrate the instrument.

Note
If reverseacting relay B is used, you must manually set the Relay Type (BASIC_SETUP.RELAY_TYPE [42.5]) to B. This will not be set
during Device Setup.

1. Select whether Travel, Travel with Pressure fallback (auto recovery or manual recovery) or Pressure Control is
desired. Refer to page 66 for additional information.
2. Enter the pressure units:kPa, bar, psi, inHg, inH2O, or kg/cm2.
3. Enter the maximum instrument supply pressure and output pressure range (if required).
4. Enter the manufacturer of the actuator on which the instrument is mounted. If the actuator manufacturer is not
listed, select Other.
5. Enter the actuator model or type. If the actuator model is not listed, select Other.
6. Enter the actuator size.
7. Indicate whether a Volume Booster is being used.
8. Specify if factory defaults should be used for basic setup. If you select YES for factory default, the Field
Communicator sets the setup parameters to the values listed in table 31. If you select NO for the factory defaults,
the setup parameters listed in the table remain at their previous settings.
Table 31. Factory Default Settings
Setup Parameter

Default Setting

Travel Cutoff Hi
Travel Cutoff Lo
Travel Integral Gain
Travel Calibration Trigger

99.5%
0.5%
9.4 repeats/min
No

Travel Integral Enable


Travel Integral Limit Hi
Travel Integral Limit Lo
Travel Integral Deadzone

On
30%
-30%
0.25%

Pressure Cutoff Hi
Pressure Cutoff Lo
Pressure Integral Deadzone
Pressure Integral Hi Limit
Pressure Integral Lo Limit

99.5%
-0.5%
0.25%
50.0%
-50.0%

Input Characterization
Shutdown Trigger
Shutdown Recovery
Output Block Timeout

Linear
All Off
All Auto Recovery
600 sec

40

Instruction Manual

Basic Setup

D103412X012

August 2012

Table 32. Actuator Information for Initial Setup


Actuator
Manufacturer

Actuator Model

585C & 585CR

657

667

1051 & 1052

1061
Fisher

Actuator Size

Actuator Style

25
50
60
68, 80
100, 130
30
34, 40
45, 50
46, 60, 70, 76, &
80100
30
34, 40
45, 50
46, 60, 70, 76, &
80100
20, 30
33
40
60, 70

Piston Dbl w/ or w/o


Spring. See actuator
instruction manual and
nameplate.

30
40
60
68, 80, 100, 130

Starting
Tuning Set

Travel Sensor Motion(2)


Relay A or C(3)

E
I
J
L
M

User Specified

Spring & Diaphragm

H
K
L

Away from the top of the instrument

Spring & Diaphragm

M
H
K
L

Towards the top of the instrument

Spring & Diaphragm


(Window-mount)

Piston Dbl w/o Spring

M
H
I
K
M
J
K
L
M

Away from the top of the instrument

Depends upon pneumatic connections. See


description for Travel Sensor Motion
Mounting Style
A

1066SR

20
27, 75

Piston Sgl w/Spring

G
L

B
C
D

2052

1
2
3

3024

30, 30E
34, 34E, 40, 40E
45, 45E

Spring & Diaphragm


(Window-mount)

H
K
M

Away from the top of the instrument

Spring & Diaphragm

E
H
K

For Po operating mode (air opens):


Towards the top of the instrument
For Ps operating mode (air closes):
Away from the top of the instrument

X(1)

225
GX
Air to Extend
Air to Retract
Baumann
Rotary

750

Travel Sensor Motion


Away from the top of the
instrument
Towards the top of the
instrument
Towards the top of the
instrument
Away from the top of the
instrument

Spring & Diaphragm

1200

16
32
54
10
25
54

C
E
H
E
H
J

Spring & Diaphragm

Air to Open
Towards the top
of the instrument

Air to Close
Away from the top of the
instrument

Towards the top of the instrument


Away from the top of the instrument
Specify

NOTE: Refer to figure 23 and table 410 for feedback connection (magnet assembly) information.
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Travel Sensor Motion in this instance refers to the motion of the magnet assembly.
3. Values shown are for Relay A and C. Reverse for Relay B.

41

Basic Setup

Instruction Manual

August 2012

D103412X012

Typically Device Setup determines the required setup information based upon the actuator manufacturer and model
specified. However, if you enter OTHER for the actuator manufacturer or the actuator model, then you will be
prompted for setup parameters such as:
Actuator StyleSelect spring & diaphragm, piston doubleacting without spring, piston singleacting with spring,
piston doubleacting with spring.
Valve StyleSelect the valve style, rotary or slidingstem.
Zero Power Conditionthis identifies whether the valve is fully open or fully closed when the input is 0%. If you are
unsure how to set this parameter, disconnect the instrument from the segment. (With doubleacting and
singleacting direct digital valve controllers, disconnecting the instrument from the segment is the same as setting
the output A pressure to zero. For singleacting reverse digital valve controllers, disconnecting the instrument from
the segment is the same as setting the output B pressure to supply.)

WARNING
If you answer YES to the prompt for permission to move the valve when setting the Travel Sensor Motion, the instrument
will move the valve through its full travel range. To avoid personal injury and property damage caused by the release of
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.

Travel Sensor MotionDevice Setup asks if it can move the valve to determine travel sensor motion. If you answer
Yes, the instrument will stroke the valve the full travel span to determine travel sensor motion. If you answer No,
then you must specify the direction of travel movement. For quarterturn actuators determine rotation by viewing
the rotation of the magnet assembly from the back of the instrument.

Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be
referred to as a magnetic array in user interface tools.

For instruments with relay A or C If increasing air pressure at output A causes the magnet assembly to move up, or
the actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet
assembly to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW. For
instruments with relay B.
For instruments with relay B If decreasing air pressure at output B causes the magnet assembly to move up, or the
actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet
assembly to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW.

Note
Relay A adjustment may be required before Device Setup can determine travel sensor motion. Follow the prompts on the Field
Communicator display if relay adjustment is necessary.

Table 32 lists the required Travel Sensor Motion selections for Fisher and Baumann actuators.

42

Instruction Manual

Basic Setup

D103412X012

August 2012

Tuning SetThere are twelve tuning sets to choose from. Each tuning set provides a preselected value for the digital
valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response. For
smaller actuators use tuning set C or D. For larger actuators using tuning set F or G. Table 33 lists the values for
preselected tuning sets.

Note
Tuning set B is only available in Pressure Control Mode.

Table 33. Gain Values for Preselected Tuning Sets


Travel
Tuning Set
B
C
D
E
F
G
H
I
J
K
L
M
X (Expert)

Proportional Gain

4.4
4.8
5.5
6.2
7.2
8.4
9.7
11.3
13.1
15.5
18.0
User Adjusted

Pressure

Velocity Gain

Minor Loop
Feedback Gain

Proportional Gain

Integrator Gain

Minor Loop
Feedback Gain

3.0
3.0
3.0
3.1
3.6
4.2
4.8
5.6
6.0
6.0
6.0
User Adjusted

35
35
35
35
34
31
27
23
18
12
12
User Adjusted

0.5
2.2
2.4
2.8
3.1
3.6
4.2
4.8
5.6
6.6
7.8
9.0
User Adjusted

0.3
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
User Adjusted

35
35
35
35
35
34
31
27
23
18
12
12
User Adjusted

WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury or property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.

In addition, you can select Expert, which allows you to individually set the proportional gain, velocity gain, and minor
loop feedback gain for travel tuning and pressure proportional gain, pressure integrator gain, and pressure minor loop
feedback gain for pressure tuning. Refer to page 63 for additional information on travel tuning and page 65 for
pressure tuning.

Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize or Performance Tuner may be used to achieve the desired results more rapidly than expert tuning.

Table 32 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are only
recommended starting points. After you finish setting up and calibrating the instrument, use Stabilize/Optimize to
adjust the tuning set to get the desired response.

43

Instruction Manual

Basic Setup
August 2012

D103412X012

When Device Setup is complete you are asked if you wish to run Auto Calibration now. Select yes to automatically
calibrate instrument travel at this time. Follow the prompts on the Field Communicator display. The calibration
procedure uses the valve and actuator stops as the 0% and 100% calibration points. For additional information, refer to
Auto Calibration in the Calibration section.

Note
Singleacting relay B and C are not useradjustable. However, it is recommended that you check the relay adjustment for
doubleacting relay A in new installations before proceeding with travel calibration.
Refer to page 215 for relay adjustment instructions.

If after completing setup and calibration the valve cycles or overshoots (unstable), or is unresponsive (sluggish), you
can improve operation by running Performance Tuner or Stabilize/Optimize.

Performance Tuner
Field Communicator

TB > Configure/Setup > Basic Setup > Performance Tuner

WARNING
During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.

The Performance Tuner is used to determine digital valve controller tuning. It will move the valve slightly and monitor
the effects of small tuning changes until an optimum control response is achieved. Because the Performance Tuner
can detect internal instabilities before they become apparent in the travel response, it can generally optimize tuning
more effectively than manual tuning. Typically, the Performance Tuner takes 3 to 5 minutes to tune an instrument,
although tuning instruments mounted on larger actuators may take longer.

44

Instruction Manual
D103412X012

Detailed SetupResource Block


August 2012

Section 4 Detailed Setup 4-4Resource Block


Overview
The resource block contains the hardware specific characteristics associated with a device; it has no input or output
parameters. The resource block monitors and controls the general operation of other blocks within the device. Most of
the resource block parameters are operational parameters that provide information about the instrument such as
identification, hardware information, available options, etc. and are read only. Configuration of the resource block
involves selecting features from those that are available, setting the mode, setting write lock, and setting up alert
reporting details.
The following procedures address only the key resource block parameters; however, all resource block parameters are
listed in table 43.

Configure/Setup
Setup
Resource Block Mode
Field Communicator

RB > Configure/Setup > Setup > Resource Block Mode

Modes
The resource block can be in one of two modes (MODE_BLK [5]):

 Automatic (Auto)This is the operational mode for this block. When the resource block is in the Auto mode, all
other function blocks are allowed to function normally.
 Out of Service (OOS)Placing the resource block in Out of Service mode stops all function block execution, by
setting their modes to Out of Service as well. The actual mode of the function blocks is changed to Out of Service, but
the function block target modes are retained. Placing the resource block in the Out of Service mode does not affect
the mode of the transducer block.

Write Lock
Field Communicator

RB > Configure/Setup > Write Lock

Write Lock
Write Lock (WRITE_LOCK [34]) determines if writes are permissible to other device parameters. The Firmware Write
Lock feature must be selected to be able to use Write Lock (see Features). When Write Lock is set to Locked, no writes
are permitted to any parameters within the device except to set Write Lock to Not Locked. When locked, the device
functions normally, updating inputs and outputs and executing algorithms. When Write Lock is set to Not Locked, the
Write Alarm (WRITE_ALM [40]) alert is active.

45

Detailed SetupResource Block

Instruction Manual

August 2012

D103412X012

Write Priority
Write Priority (WRITE_PRI [39]) sets the priority for Write Alarm. The lowest priority is 0. The highest is 15.

Communication Time Out


Field Communicator

RB > Configure/Setup > Communication Time Out

Shed Remote Cascade

Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your advanced control.
Default value for RCas Timeout is 20 seconds.

Shed Remote Cascade (SHED_RCAS [26]) determines how long function blocks in the DVC6200f should wait before
giving up on remote computer writes to RCas parameters. When the timeout is exceeded, the block sheds to the next
mode as defined by the block shed options. If Shed Remote Cascade is set to 0, the block will not shed from RCas.
Enter a positive value in the Shed Remote Cascade field. Time duration is in 1/32 milliseconds (640000 = 20 secs).
Shed Remote Out

Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your advanced control.
Default value for Shed Remote Out is 20 seconds.

Shed Remote Out (SHED_ROUT [27]) determine how long function blocks in the DVC6200f should wait before giving
up on computer writes to ROut parameters. When the timeout is exceeded, the block sheds to the next mode as
defined by the block shed options. If Shed Remote Out is set to 0, the block will not shed from ROut. Enter a positive
value in the Shed Remote Out field. Time duration is in 1/32 milliseconds (640000 = 20 secs).

Options
Field Communicator

RB > Configure/Setup > Options

Diagnostic Options
Diagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the instrument.
Function Block Options
Function Block Options (FB_OPTIONS [44]) shows which function blocks are available in the instrument.

46

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Miscellaneous Options
Miscellaneous Options (MISC_OPTIONS [46]) indicates which miscellaneous licensing options are enabled.
Features Available
Features Available (FEATURES [17]) indicates which Resource Block Options features are available.
 ReportsReports enables alert and event reporting. Reporting of specific alerts may be suppressed. See Alerts on
page 69.
 Fault StateFault state enables the ability of the output block to react to various abnormal conditions by
shedding mode. See parameter descriptions for Set Fault State (SET_FSTATE [29]) and Clear Fault State
(CLR_FSTATE [30]) in table 43 and Action on Fault Detection.
 Soft Write LockSoft Write lock permits using Write Lock (WRITE_LOCK [34]) to prevent any external change to
parameter values. Block connections and calculation results will proceed normally, but the configuration is locked.
Also see Write Lock, on page 45.

 Multibit Alarm (BitAlarm) Support Multibit Alarm (BitAlarm) Support permits the instrument to treat each
PlantWeb alert separately when broadcast to the Host. Without MultiBit Alarm Support, an individual PlantWeb
alert must be acknowledged before another PlantWeb alert can be broadcast to the Host
Features Selected

Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Fault State, Software Write Lock, and Output Readback are set by default.

Features Selected (FEATURE_SEL [18]) indicates which Resource Block Options features have been selected and is used
to select the desired features.
 ReportsSelecting reports enables alert and event reporting. Reporting of specific alerts may be suppressed. See
Alerts on page 69.
 Fault StateSelecting fault state enables the ability of the output block to react to various abnormal conditions by
shedding mode. See parameter descriptions for Set Fault State (SET_FSTATE [29]) and Clear Fault State
(CLR_FSTATE [30]) in table 43 and Action on Fault Detection.
 Soft Write LockWhen selected, permits using Write Lock (WRITE_LOCK [34]) to prevent any external change to
parameter values. Block connections and calculation results will proceed normally, but the configuration is locked.
Also see Write Lock, on page 45.
 Multibit Alarm (BitAlarm) Support When selected, the instrument will allow the instrument to treat each
PlantWeb alert separately when broadcast to the Host.

Alarm Handling
Field Communicator

RB > Configure/Setup > Alarm Handling

Alert KeyAlert Key (ALERT_KEY [4]) is a number that permits grouping alerts. This number may be used to indicate
to the operator the source of the alert, such as the instrument, plant unit, etc. Enter a value between 1 and 255.

47

Detailed SetupResource Block

Instruction Manual

August 2012

D103412X012

Confirm TimeConfirm Time (CONFIRM_TIME [33]) determines the time, in 1/32 of a millisecond, the instrument
waits for confirmation of receipt of a report before trying again. If Confirm Time is 0, the instrument does not retry
to send the report. Enter 0 or a value between 320000 (10 secs) and 640000 (20 secs).
Limit NotifyLimit Notify (LIM_NOTIFY [32]) is the number of alert reports that the device can send without getting
a confirmation up to the maximum permitted in Maximum Notify (MAX_NOTIFY [31]). If Limit Notify is set to zero,
no alerts are reported. Enter a value between 0 and 3.
To have the instrument report alerts without having the host poll the alerts parameters, select the Reports feature
(see Feature Select).
Maximum NotifyMaximum Notify (MAX_NOTIFY [31]) indicates the maximum number of alert reports that the
device can send without getting a confirmation. This limit is determined by the amount of memory available for
alert messages. The number can be set lower, to control alert flooding, by adjusting Maximum Alerts Allowed
(LIM_NOTIFY [32]).
Block Alarm DisabledThe Block Alarm (BLOCK_ALM [36]) is used for all configuration, hardware, connection failure
or system problems in the block. Alarm Summary (ALARM_SUM [37]) determines if the Write Alarm (WRITE_ALM
[40]) and Block Alarm [BLOCK_ALM [36]) are disabled.
Block Alarm Auto AcknowledgeAcknowledge Option (ACK_OPTION [38]) determines if the block alarm will be
automatically acknowledged.
Discrete Alarm DisabledThe Write Alarm (WRITE_ALM [40]) is used to alert when parameters are writeable to the
device. Alarm Summary (ALARM_SUM [37]) determines if the Discrete Alarm is disabled.
Discrete Alarm Auto AcknowledgeAcknowledge Option (ACK_OPTION [38]) determines if the Write Alarm
associated with the block will be automatically acknowledged.

Identification
Field Communicator

RB > Configure/Setup > Identification

Device IDThe 32 character Device ID (DEVICE_ID [54]).


Electronics Serial NumberThe Electronics Serial Number (ELECTRONICS_SN [49]) set at the factory.
Factory Serial NumberThe Factory Serial Number (FACTORY_SN [50]) is the instrument serial number set at the
factory.
Field Serial NumberThe Field Serial Number (FIELD_SN [51]) is the serial number of instrument assigned in field.
Tag DescriptionThe Tag Description (TAG_DESC [2]) is used to assign a unique 32 character description to each
block within the digital valve controller to describe the intended application for the block.
StrategyStrategy (STRATEGY [3]) permits strategic grouping of blocks so the operator can identify where the
block is located. The blocks may be grouped by plant area, plant equipment, etc. Enter a value between 0 and
65535 in the Strategy field.
ManufacturerManufacturer Identification (MANUFAC_ID [10]) identifies the manufacturer of the instrument. It is
used by the host system to locate the DD file for the device. For Fisher the Manufacturer ID is 0x5100.
Device TypeDevice Type (DEV_TYPE [11]) identifies the type of device. It is used by the host system to locate the
DD file for the device. For a DVC6200f digital valve controller the device type is 0x4602.

48

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Diagnostic OptionsDiagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the
instrument.

Version
Field Communicator

RB > Configure/Setup > Version

Device RevisionThe Device Revision (DEV_REV [12]) is the manufacturer's revision number associated with the
resource, used by an interface device to locate the DD file for the resource.
Firmware RevisionFirmware Revision (FIRMWARE_REVISION [47]) identifies the revision of the firmware that is
currently in use.
Standby Firmware RevisionStandby Firmware Revision (STBY_FIRMWARE_REVISION [55]) identifies the revision of
the alternative firmware.
Hardware RevisionHardware Revision (HARDWARE_REV [48]) identifies the revision of the electronic hardware.
ITK VersionITK Version (ITK_VER [41]) identifies the major version of the Interoperability Tester used by the
Fieldbus Foundation in certifying the device as interoperable. This device revision meets the requirements of
version 5.

Block Errors
Table 41 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the
Resource block and are provided only for your reference.
Table 41. Resource Block BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other Set if a device initialization error occurred.

Block Configuration Error Set if FEATURE_SEL, CYCLE_SEL, or CYCLE_TYPE is set incorrectly.

Link Configuration Error N/A

Simulate Active Indicates that the simulation jumper is in place on the aux terminals. This is not an indication that the I/O
blocks are using simulation data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].

Local Override N/A

Device Fault State Indicates the device is in Fault State.

Device Needs Maintenance Soon Indicates a Maintenance or Advisory PlantWeb Alert condition is active.

Input failure/process variable had Bad status N/A

Output failure N/A

Memory failure Indicates a pending Flash or NVM failure.

10

Lost Static Data Indicates failure of the memory containing static parameters.

11

Lost NV Data Indicates failure of the memory containing nonvolatile parameters.

12

Readback Check Failed NA

13

Device Needs Maintenance Now Indicates a Failed PlantWeb Alert condition is active.

14

Power Up Indicates the device has been powered up and the Resource Block is not running normally.

15

Out of Service (MSB) The resource block actual mode is Out of Service.

49

Instruction Manual

Detailed SetupResource Block


August 2012

D103412X012

Table 42. Parameters Affected by Restart with


Defaults
Index
Number

Parameter Name

Initial Value

Table 42. Parameters Affected by Restart with


Defaults (Continued)
Index
Number

Parameter Name
AO Block (continued)

Resource Block
1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

0
spaces
0
0

MODE_BLK
TARGET
PERMITTED
NORMAL

Auto
Auto or Out of Service
Auto

14
18
20

GRANT_DENY
FEATURE_SEL
CYCLE_SEL

All bits: 0
Set by mfgr.
0:0

26
27
28

SHED_RCAS
SHED_ROUT
FAULT_STATE

640000
640000
1=Clear

32
33
34
37

LIM_NOTIFY
CONFIRM_TIME
WRITE_LOCK
ALARM_SUM
DISABLED

MAX_NOTIFY
640000
1=Unlocked

ACK_OPTION
WRITE_PRI

Disabled
0

38
39

All bits: 0

23
24
26

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT

8
9
11

12

0
spaces
0
0

Value
SHED_OPT

1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

MODE_BLK
TARGET
PERMITTED

14
15

XD_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
IO_OPTS
STATUS_OPTS

17

CAS_IN

PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places

100
0
%
2

13
14

OUT_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
CONTROL_OPTS
STATUS_OPTS

100
0
%
2
0: Bypass enable
All off

15

IN

10

11

18
19
20
21
22

SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
SP_LO_LIM
CHANNEL
-Continued-

BAD:
NC:
const
0
0

Status

16

BAD:
NC:
const
0
+INF
+INF
100
0
1=analog valve input

0
spaces
0
0

NORMAL
SP
OUT

8
9

100
0
%
2
100
0
%
2
All off
All off

BAD:
NoComm:
NoVal:
const
0 Trk
All off

Out of Service
OOS+MAN+AUTO+CAS+
RCAS+ROUT
Auto
Dynamic
Dynamic

OOS+MAN+AUTO+CAS+RCAS

PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places

0
0

PID Block Parameters

Out of Service
Auto
Dynamic
Dynamic

FSTATE_TIME
FSTATE_VAL
RCAS_IN
Status

27

AO Block
1
2
3
4

17
18

19
20
21
22
23
24
25
26
27

Value
PV_FTIME
BYPASS
CAS_IN
Status

0
BAD:
NC:
const
0
+INF
+INF
100

Value
SP_RATE_DN
SP_RATE_UP
SP_HI_LIM
SP_LO_LIM
GAIN
RESET
BAL_TIME
RATE
BKCAL_IN
Status

0
1
+INF
0
0
BAD:
NC:
const
0

Value
-Continued-

50

Initial Value

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Table 42. Parameters Affected by Restart with


Defaults (Continued)
Index
Number

Parameter Name

Initial Value

Table 42. Parameters Affected by Restart with


Defaults (Continued)
Index
Number

Parameter Name

PID Block (continued)


28
29
30
32

33

OUT_HI_LIM
OUT_LO_LIM
BKCAL_HYS
RCAS_IN
Status

100
0
0.5%
BAD:
NoCom:
NoVal:
const
0 Trk

Value
ROUT_IN
Status

BAD:
NoCom:
NoVal:
const
0 Trk

Value
34
37

38

39

40

SHED_OPT
TRK_SCALE
EU 100%
EU 0%
Engineering Units
Decimal places
TRK_IN_D
Status

BAD:
NC:
const
0

Value
TRK_VAL
Status

BAD:
NC:
const
0

Value
FF_VAL
Status

BAD:
NC:
const
0

Value
41

46

FF_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
FF_GAIN
ALARM_SUM
DISABLED
ACK_OPTION

47
48
49
50
51

ALARM_HYS
HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM

0.5%
0
+INF
0
+INF

52
53
54
55

LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM

0
-INF
0
-INF

56
57
58
59

DV_HI_PRI
DV_HI_LIM
DV_LO_PRI
DV_LO_LIM

0
+INF
0
-INF

42
45

PID Block (continued)


66
69
70
71
72
73
74

100
0
%
2
0
0
Disabled

BIAS
SP_FTIME
MATHFORM
STRUCTURECONFIG
GAMMA
BETA
IDEABAND

0
0
0

ISEL Block
1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

0
spaces
0
0

MODE_BLK
TARGET
PERMITTED
NORMAL
OUT

Out of Service
OOS+MAN+AUTO
Auto

0
100
0
%
2

Initial Value

7
8

10
11

12

OUT_RANGE
EU 100%
EU 0%
Engineering Units
Decimal Places
STATUS_OPTS
IN_1
Status

All off
BAD
NC
cons
0

Value
IN_2
Status

BAD
NC
cons
0

Value
13

14

IN_3
Status

BAD
NC
cons
0

Value
IN_4
Status

BAD
NC
cons
0

Value
15

16

100
0
%
2

DISABLE_1
Status

BAD
NC
cons
0

Value
DISABLE_2
Status

BAD
NC
cons
0

Value
-Continued-

-Continued-

51

Instruction Manual

Detailed SetupResource Block


August 2012

D103412X012

Table 42. Parameters Affected by Restart with


Defaults (Continued)
Index
Number

Parameter Name

Initial Value

Table 42. Parameters Affected by Restart with


Defaults (Continued)
Index
Number

Parameter Name

ISEL Block (continued)


17

18

DISABLE_3
Status

Value
DISABLE_4
Status

Value
19
20
22

SELECT_TYPE
MIN_GOOD
OP_SELECT
Status

25

26

28

Value
IN_6
Status

30

IN_7
Status

32

Value
IN_8
Status

35
36
37

DISABLE_5
Status

BAD
NC
cons
0

Value
DISABLE_6
Status

BAD
NC
cons
0

DISABLE_7
Status

Value
DISABLE_8
Status

AVG_USE
ALARM_SUM
DISABLED
ACK_OPTION
ALARM_HYS
HI_HI_PRI

All bits: 0
DI Block

1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

MODE_BLK
TARGET
PERMITTED
NORMAL
OUT_D
XD_STATE
OUT_STATE
IO_OPTS
STATUS_OPTS

8
10
11
13
14
15
16
20

0
spaces
0
0
Out of Service
OOS+MAN+AUTO
Auto
0
0
All off
All off

21
22
23

CHANNEL
PV_FTIME
ALARM_SUM
DISABLED
ACK_OPTION
DISC_PRI
DISC_LIM

0
0

1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

MODE_BLK
TARGET
PERMITTED
NORMAL
SP
OUT_1
OUT_2
OUT_1_RANGE
EU 100%
EU 0%
Engineering Units
Decimal Places

0
All off
0
0
OS Block

7
8
9
10

BAD
NC
cons
0

11

BAD
NC
cons
0

13
14

0
spaces
0
0

OUT_2_RANGE
EU 100%
EU 0%
Engineering Units
Decimal Places
STATUS_OPTS
CAS_IN
Status

100
0
%
2
100
0
%
2

BAD
NC
const
0

Value
0
0
0.5%
0

Out of Service
OOS+MAN+AUTO
AUTO+CAS

disabled

-Continued-

52

LO_LO_LIM
OUT_D
ALM_SEL

BAD
NC
cons
0

Value
33
34

44
49
50

BAD
NC
cons
0

Value
31

BAD
NC
cons
0

BAD
NC
cons
0

Value
29

0
0
0
0
0
0

BAD
NC
cons
0

Value
27

BAD
NC
cons
0

HI_HI_LIM
HI_PRI
HI_LIM
LO_PRI
LO_LIM
LO_LO_PRI

BAD
NC
constant
0

IN_5
Status

ISEL Block (continued)


38
39
40
41
42
43

All off
0

Value

Initial Value

-Continued-

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Table 42. Table Parameters Affected by Restart with


Defaults (Continued)
Index
Number

Parameter Name

Initial Value

Table 42. Parameters Affected by Restart with


Defaults (Continued)
Index
Number

OS Block (continued)
19

BKCAL_1_IN
Status

Value
20

BKCAL_2_IN
Status

BAD
NC
const
0
0

21

Value
BAL_TIME

1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

MODE_BLK
TARGET
PERMITTED
NORMAL
OUT
XD_SCALE
EU at 100%
EU 0%
Units Index
Decimal point

AI Block

8
10

11

13
14
15
16
17
18
22

0
spaces
0
0
Out of Service
OOS, MAN, AUTO
Auto

100
0
%
2

OUT_SCALE
EU 100%
EU 0%
Units Index
Decimal point
I/O OPTS
STATUS OPTS
CHANNEL
L_TYPE

100
0
Trk s/b%
2
disabled
disabled
0
0
0
0

23
24

LOW_CUT
PV_FTIME
ALARM_SUM
DISABLED
ACK_OPTION
ALARM_HYS

25
26
27
28

HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM

0
0
0
0

29
30
31
32
37
38

LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM
OUT_D
ALM_SEL

0
0
0
0

1
2
3
4

7
8
9
10
11
12
13
14
15

MODE_BLK
TARGET
PERMITTED
NORMAL
CHANNEL
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8

1
2
3
4

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

MODE_BLK
TARGET
PERMITTED

unselected

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY

0
spaces
0
0

Out of Service
OOS, MAN, AUTO
Auto
TB.FINAL_VALUE
TB.TRAVEL_TARGET
TB.FINAL_POSITION_VALUE
TB.TRAVEL
TB.SUPPLY_PRESS
TB.ACT_PRESS_A
TB.ACT_PRESS_B
TB.ACT_PRESS_DIFF
DO Block
0
spaces
0
0

8
9

NORMAL
SP_D
OUT_D

11
12
14
15

PV_STATE
XD_STATE
IO_OPTS
STATUS_OPTS

17

CAS_IN_D
Status

18
19
20
22

0
Disabled
0.5%

MAI Block

Initial Value

MAI Block (continued)


5

BAD
NC
const
0

Parameter Name

23
27
28

Value
CHANNEL
FSTATE_TIME
FSTATE_VAL_D
RCAS_IN_D
Status

Value
SHED_OPT
SP_RATE_UP
SP_RATE_DN

Out of Service
OOS+MAN+AUTO+CAS+
RCAS
AUTO+CAS

0
0
All off
All off
BAD
NC
const
0
22
0
0
BAD
NoComm
NoVal
const
0
All off
0
0

Transducer Block
1
2
3
4
5

87

ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
TARGET
PERMITTED
NORMAL
PROTECTION

N/A
NULL
0
1
Out of Service
AUTO, MAN, OOS
Auto
None

-Continued-

53

Instruction Manual

Detailed SetupResource Block


August 2012

D103412X012

Resource Block Parameter List


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter.
Table 43. Resource Block Parameter Definitions
Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Range

Initial
Value

Description

Static Revision
ST_REV

RO

NA

0 to 65535

Data Type: Unsigned16


The revision level of the static data. Increments
by one each time a static parameter changes.
The value is reset to 0 whenever a Restart with
Defaults is performed. See Restarting the
Instrument.

Tag Description
TAG_DESC

RW

NA

7 bit ASCII

Spaces

Data Type: Octet String


The user description of the intended application
of the block. Null characters are not allowed in
this data type.

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned16


Used to identify groupings of blocks. The data is
not checked or processed by the block.

Data Type: Unsigned8


The identification number of the plant unit.
Devices in a loop or plant section can be
assigned with a common alert key to aid the
operator in determining location of alerts.

Alert Key
ALERT_KEY

Block Mode
MODE_BLK

TARGET_MODE

5.1

RW

ALL

1 to 255

RW

ALL

3: Auto
7: OOS

3: Auto

N/A

ACTUAL_MODE

5.2

RO

NA

3: Auto
6: IMAN (only during
initialization
7: OOS

PERMITTED_MODE

5.3

RW

ALL

3: Auto
7: OOS

3: Auto
7: OOS

NORMAL_MODE

5.4

RW

ALL

3: Auto

3: Auto

N/A

0: Other
1: Block Configuration
Error
3:Simulate Active
6:Device needs
Maintenance Soon
9:Memory Failure
10:Lost Static Data
11:Lost NonVolatile
Memory
13:Device needs
Maintenance Now
14:Powerup
15:Outof
Service (MSB)

N/A

2:Initialization,
Actual mode=IMAN
4:Online, Actual
Mode=Auto
5:Standby, Actual
Mode=OOS
6:Failure, Actual
Mode=OOS

Block Error
BLOCK_ERR

Device State
RS_STATE

Test Read Write


TEST_RW

RO

RO

ALL

5: Standby

-Continued-

54

Dynamic

Data Type: DS69


The actual, target, permitted, and normal
modes.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

Data Type: Bit String


0 = Inactive
1 = Active
Error status associated with hardware or
software for the resource block. When an error is
shown it may be broadcast to the host through
BLOCK_ALM.

Data Type: Unsigned8


State of the function block application state
machine.

This parameter may be used in interoperability


testing to read and write all standard data types
supported by the Fieldbus Foundation.

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Table 43. Resource Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
DD Resource
DD_RESOURCE

Index
Number

RO /
RW

Mode

RO

N/A

Range

Initial
Value

Description

Spaces

Data Type: Visible String


String identifying the VFD tag of the resource
that contains the Device Description for this
resource.

Manufacturer Id
MANUFAC_ID

10

RO

N/A

0x5100

Data Type: Unsigned32


Manufacturer identification number, used by an
interface device or host to locate the DD file for
the resource. All manufacturer identification
numbers are maintained by the Fieldbus
Foundation. A host usually will have a base
directory for DD files. In this directory is a
subdirectory for each manufacturer id. In each
manufacturer id subdirectory is a directory for
each device type made by that manufacturer.
The device type directories contain files named
by combining the device revision for the
particular device type with the revision of the
device description. The manufacturer id for
Fisher is 0x005100.

Device Type
DEV_TYPE

11

RO

N/A

4602

Data Type: Unsigned16


Manufacturer's model number associated with
the resource, used by an interface device to
locate the DD file for the resource.

N/A

Varies with
release

Data Type: Unsigned8


Manufacturer's revision number associated with
the resource, used by an interface device to
locate the DD file for the resource.

Varies with
release

Data Type: Unsigned8


The minimum revision of the device description
(DD) than can be used with the device revision
of the instrument. Used by the interface device
to prevent the use of DDs that are incompatible
with the firmware in the instrument.

Device Revision
DEV_REV

12

DD Revision
DD_REV

13

Grant Deny
GRANT_DENY

14

RO

RO

N/A

GRANT

14.1

RW

ALL

DENY

14.2

RW

ALL

Hard Types
HARD_TYPES

Restart
RESTART

Features
FEATURES

15

16

17

RO

RW

RO

Valid Bits:
0: Program
1: Tune
2: Alarm
3: Local

N/A

0: Scalar Input
1: Scalar Output
2: Discrete Input
3: Discrete Output

ALL

1=Run
2=Restart resource
3=Restart with
defaults
4=Restart processor

ALL

1:Reports supported
2:Fault State
supported
3:Software Write
lock supported
10:Reannunciation
supported

All bits: 0

All bits: 0

Data Type: DS70


Options for controlling access of a host
computer and to block parameters. Parameter
contains two attributes Grant and Deny each
with program, tune, alarm and local
permissions. Clearing a grant permission sets
the corresponding deny permission, 0 = N/A, 1 =
granted.
Deny permissions may be cleared through the
Deny attribute but not set, 0 = N/A, 1 = denied.

0: 1
1: 1
2: 1
3: 1

Data Type: Bit String


0 = Inactive
1 = Active
The types of hardware available as channel
numbers in this resource.

1=Run

Data Type: Unsigned8


Allows a manual restart to be initiated. For
details see Restarting the Instrument in this
section.

1: 1
2: 1
3: 1
10: 1

Data Type: Bit String


0 = Inactive
1 = Active
Shows the supported resource block options.
Options are turned on and off via
FEATURE_SELECT.

-Continued-

55

Instruction Manual

Detailed SetupResource Block


August 2012

D103412X012

Table 43. Resource Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Features Selected
FEATURE_SEL

Cycle Type
CYCLE_TYPE

Cycle Selection
CYCLE_SEL

Minimum Cycle Time


MIN_CYCLE_T

Memory Size
MEMORY_SIZE

Nonvolatile Cycle Time


NV_CYCLE_T

Free Space
FREE_SPACE

Free Time
FREE_TIME

RCAS Timeout
SHED_RCAS

Index
Number

18

19

RO /
RW

RW

RO

20

21

22

23

24

25

26

Mode

Range

Initial
Value

ALL

1: Reports Supported
2: Fault State
supported
3: Software Write lock
supported
10:Reannunciation
supported

1:0
2:1
3:1
10:0

Data Type: Bit String


0 = Inactive
1 = Active
Shows the selected resource block options. For
details see Device Features in this section.

0: 1

Data Type: Bit String


0 = Inactive
1 = Active
Identifies the block execution methods available
for this resource, may be scheduled, completion
of block execution

0: 0

Data Type: Bit String


0 = Inactive
1 = Active
Identifies the block execution method selected
for this resource.

3200

Data Type: Unsigned32


Time duration of the shortest cycle interval (in
1/32 millisecond) of which the resource is
capable. In the digital valve controller this value
is fixed at 3200 (100 milliseconds).

45

Date Type: Unsigned16


Memory, in kilobytes, available for additional
function blocks. Because no additional function
blocks may be added to DVC6200f instruments,
this parameter value is fixed at 45.

576,000

Date Type: Unsigned32


This parameter identifies the minimum time
interval (in 1/32 milliseconds) between copies of
NV class data to NV memory. NV memory is
updated only if there has been a change in the
dynamic value. The last value saved in NV
memory will be available for the restart
procedure or a power cycle. A nonzero value
regulates the frequency of writes, thus
protecting the life span of the device. If the value
is zero, data will never be automatically copied.
Changes made by other than publishing to NV
parameters will be copied to nonvolatile
memory immediately. For DVC6200f
instruments, this parameter value is fixed at
576,000 (18 seconds).

Data Type: Float


Percent of memory available for additional
function blocks (see also MEMORY_SIZE).
Because no additional function blocks may be
added to DVC6200f instruments, this parameter
value is fixed at 0.

Data Type: Float


Percent of block processing time that is free to
process additional blocks. Because no additional
function blocks may be added to DVC6200f
instruments, this parameter value is fixed at 0.

640000

Date Type: Unsigned32


Time duration (in 1/32 millisecond) at which to
give up on computer writes to function block
RCAS parameters. If this time is exceeded then
the function block will change to a mode other
than RCAS based on the SHED_OPT parameter
setting. Shed from RCAS mode never happens
when SHED_RCAS is set to zero.

NA

ALL

RO

RO

RO

RO

RO

RW

NA

NA

NA

NA

NA

ALL

0: Scheduled

0: Scheduled

3200

45

Positive

0 to 100%

0 to 100%

Positive

-Continued-

56

Description

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Table 43. Resource Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

ROUT Timeout
SHED_ROUT

Fault State
FAULT_STATE

Set Fault State


SET_FSTATE

Clear Fault State


CLR_FSTATE

Maximum Notify
MAX_NOTIFY

Index
Number

27

28

29

30

31

RO /
RW

RW

RO

RW

RW

RO

Mode

ALL

N/A

ALL

ALL

N/A

Range

Positive

1=Clear
2=Active

1=Off
2=Set

1=Off
2= Clear

Maximum Alerts Allow


LIM_NOTIFY

32

RW

ALL

0 to MAX_NOTIFY

Confirm Time
CONFIRM_TIME

33

RW

ALL

> 0
Set by FCS

Initial
Value

Description

640000

Data Type: Unsigned32


Time duration (in 1/32 millisecond) at which to
give up on computer writes to function block
ROUT parameters. If this time is exceeded then
the function block will change to a mode other
than ROUT based on the SHED_OPT parameter
setting. Shed from ROUT mode never happens
when SHED_ROUT is set to zero.

1=Clear

Data Type: Unsigned8


Forces output function blocks that are not Out
of Service to the fault state condition. While this
parameter is active the output function blocks
will go to an actual mode of Local Override (LO)
and will perform their fault state actions (see
Action On Fault Detection for the output blocks
on pages 118 and 194 of this section). This
parameter is used to test the fault state behavior
that normally occurs when there is a
communication problem between devices. This
parameter is changed by the SET_FSTATE and
CLR_FSTATE parameters so long as the feature
Fault State is selected (see Feature Selection
[index number 18] in this table).

1=Off

Data Type: Unsigned8


Selecting Set changes the parameter
FAULT_STATE to Active. This is essentially a
write only parameter as it will always read OFF
because it is defined as momentary. Writing a
value of OFF has no affect. To use this parameter
the feature Fault State must be selected (see
Features Selected on page 47).

1=Off

Data Type: Unsigned8


Selecting Clear changes the parameter
FAULT_STATE to Clear and clears the output
function blocks of the FAULT_STATE if the field
condition, if any, has cleared. This is essentially a
write only parameter as it will always read OFF
because it is defined as momentary. Writing a
value of OFF has no affect. To use this parameter
the feature Fault State must be selected (see
Features Selected on page 47.

Data Type: Unsigned8


The maximum number of alert reports that this
device can send without getting a confirmation.
To control alert flooding, the number can be set
lower by adjusting the LIM_NOTIFY parameter
value. For DVC6200f instruments, this value is
fixed at 3.

MAX_NOTIFY

Data Type: Unsigned8


The number of alert reports that this device can
send without getting a confirmation up to the
maximum permitted in the parameter
MAX_NOTIFY. If set to zero, then no alerts are
reported.

640000

Data Type: Unsigned32


The time (in 1/32 millisecond) the device waits
for confirmation of receipt of an alert report
before trying again.

-Continued-

57

Instruction Manual

Detailed SetupResource Block


August 2012

D103412X012

Table 43. Resource Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

Write Lock
WRITE_LOCK

34

Update Event
UPDATE_EVT

35

RO /
RW

Mode

Range

Description
Data Type: Unsigned8
If set to Locked, no writes from anywhere are
allowed except to clear WRITE_LOCK by entering
Unlocked. Block inputs will continue to be
updated if they are subscribers. The feature Soft
Write Lock must be selected to enable writing to
this parameter (see Device Features in this
section).

RW

ALL

0=Undefined
1=Unlocked
2=Locked

1=Unlocked

UNACKNOWLEDGED

35.1

RW

ALL

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

UPDATE_STATE

35.2

RO

NA

0=Undefined
1=Update reported
2=Update not
reported

0=Undefined

TIME_STAMP

35.3

RO

NA

STATIC_REVISION

35.4

RO

NA

RELATIVE_INDEX

35.5

RO

NA

RW

ALL

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=Undefined

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

36.1

36.2

RO

NA

TIME_STAMP

36.3

RO

NA

SUBCODE

36.4

RO

NA

VALUE

36.5

RO

NA

RO

NA

0: Discrete alarm
7: Block Alarm

All bits: 0

NA

0: Discrete alarm
7: Block Alarm

All bits: 0
All bits: 0

CURRENT
UNACKNOWLEDGED

Data Type: DS73


This alert is generated by any change to the
static data. To support tracking changes in static
parameter values, the blocks static revision
parameter will be incremented each time a
static parameter value is changed. Also, the
blocks static revision parameter may be
incremented if a static parameter is written but
the value is not changed. If the Actual Mode is
not Out of Service and Reports is selected in the
Feature Select parameter, then this parameter
will be sent to the host system providing the
host has set up alert communications. Changes
to static data while the block is Out of Service
will be reported when the block transitions to
another mode.

36

ALARM_STATE

Alarm Summary
ALARM_SUM

Data Type: DS72


This alarm is generated by a nonzero value in the
Block Error. parameter. This alarm has a fixed
priority of 2. For a BLOCK_ALM to be broadcast
to the host the following conditions must be
met:
The feature Reports must be selected
Alert communication with the host must be
setup
In the ALARM_SUM parameter, the disable bit
for Block Alarm must be clear.

37
37.1
37.2

RO

UNREPORTED

37.3

RO

NA

0: Discrete alarm
7: Block Alarm

DISABLED

37.4

RW

ALL

0: Discrete alarm
7: Block Alarm

All bits: 0

0: 0
7: 0

Acknowledge Option
ACK_OPTION

38

RW

ALL

0: Discrete Alarm
(Write Lock off)
7: Block Alarm

Write Priority
WRITE_PRI

39

RW

ALL

0 to 15
-Continued-

58

Initial
Value

Data Type: DS74


0=clear, acknowledged, reported, enabled
Current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block. The
Resource block only has two alarms: Write Alarm
and Block Alarm.
Data Type: Bit String
0=Disable
1=Enable
Selection of whether alarms associated with the
block will be automatically acknowledged.
Data Type: Unsigned8
Priority of the alarm generated by setting
WRITE_LOCK to Unlocked.

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

Table 43. Resource Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Write Alarm
WRITE_ALM
UNACKNOWLEDGED

Index
Number

RO /
RW

Mode

Range

Initial
Value

40
40.1

RW

ALL

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=Undefined

ALARM_STATE

40.2

RO

NA

TIME_STAMP

40.3

RO

NA

SUBCODE

40.4

RO

NA

VALUE

40.5

RO

NA

ITK Version
ITK_VER

41

RO

N/A

Private Label Distributor


DISTRIBUTOR

42

RO

NA

Device String Array


DEV_STRING

43

Description
Data Type: DS72
This alarm is generated when Unlocked in the
WRITE_LOCK parameter is set. This alarm has a
priority of WRITE_PRI. For a WRITE_ALM to be
broadcast to the host the following conditions
must be met:
The feature Reports must be selected
Alert communication with the host must be
setup
In the ALARM_SUM parameter, the disable bit
for Write Alarm must be clear.
WRITE_PRI must be greater than 1.
Data Type: Unsigned16
Major version of ITK test this device has been
tested to. *Initial value depends on the revision
of the DVC6200f.

Extended Parameters

Function Block Options


FB_OPTIONS

Diagnostic Options
DIAG_OPTIONS

44

45

Miscellaneous Options
MISC_OPTIONS

46

Firmware Revision
FIRMWARE_REVISION

47

0x5100

Unused extended parameter.

RO

Bits
0: AO
1: DO
2: AI
3: DI
4: PID
5: ISEL
6: OS
7: MAI

RO

NA

1=FD Fieldbus
Diagnostics
2=AD Advanced
Diagnostics
3=PD Performance
Diagnostics

RO

NA

0: Software Download
10: Travel Control
Capable
11: Pressure Control
Capable
12: Fallback Capable

All options
enabled

Data Type: Bit String


0=disabled
1=enabled
Indicates which function block licensing options
are enabled. One bit for each block type that is
supported. Unlicensed blocks cannot be
scheduled and the Actual block mode will
remain OOS.

Data Type: Enum


Indicates which diagnostics licensing options are
enabled. *Initial value depends on the licensed
DVC6200f options.

FD
0: 1
10: 1
11: 1
AD/PD
0: 1
10: 1
11: 1
12: 1

FIRMWARE_REV_MAJOR

47.1

RO

NA

0-255

FIRMWARE_REV_MINOR

47.2

RO

NA

0-255

FIRMWARE_REV_BUILD

47.3

RO

NA

0-255

IO_FIRMWARE_REV

47.4

RO

NA

0-255

DIAG_CAL_REV

47.5

RO

NA

0-255

FIRMWARE_REV_ALL

Hardware Revision
HARDWARE_REV

Data Type: Unsigned32


Private label distributor

47.6

RO

NA

XX.XX.XX

48

RO

NA

Hardware revision
number

Factory Set

Data Type: Bit String


0=Disable
1=Enable
Indicates which miscellaneous licensing options
are enabled.

Data Type: Uint8


Describes software revision information. This is
the revision of the firmware that is currently in
use.
*Initial value depends on revision of DVC6200f.
Data Type: Visible String
Describes software revision information.
The range of this parameter consists of 47.1
through 47.5 values, converted to text, and
linked together.
*Initial value depends on revision of DVC6200f
Data Type: Uint8
Describe electronic hardware revision
information.

-Continued-

59

Instruction Manual

Detailed SetupResource Block


August 2012

D103412X012

Table 43. Resource Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Electronics Serial Number


ELECTRONICS_SN

49

RO

NA

NA

Factory Set

Factory Serial Number


FACTORY_SN

50

RO

NA

NA

spaces

Data Type: Visible String


Instrument serial number set by manufacturing.

Field Serial Number


FIELD_SN

51

RW

NA

Any String

spaces

Data Type: Visible String


Instrument serial number set in the field.

Detailed Status
DETAILED_STATUS

52

RO

NA

NA

Time Since Reset


TIME_SINCE_RESET

53

RO

NA

NA

Device ID
DEVICE ID

54

RO

NA

NA

Device ID

STBY_FIRMWARE_REV

Initial
Value

55.1

RO

NA

0-255

STBY_FIRMWARE_REV_MINOR

55.2

RO

NA

0-255

STBY_FIRMWARE_REV_BUILD

55.3

RO

NA

0-255

STBY_IO_FIRMWARE_REV

55.4

RO

NA

0-255

STBY_DIAG_CAL_REV

55.5

RO

NA

0-255

FB_AVAILABLE

Description
Data Type: Visible String Electronics serial
number set by manufacturing.

Data Type: Uint32


Not used
Number of seconds since the last time
DVC6200f was restarted. Restart due to power
up or restart command.
Data Type: Visible String
Unique 32 character ID used to identify the
device.

55

STBY_FIRMWARE_REV_MAJOR

STBY_FIRMWARE_REV_ALL

60

Range

55.6

56

RO

RO

NA

XX.XX.XX

NA

Bits
0: AO
1: DO
2: AI
3: DI
4: PID
5: ISEL
6: OS
7: MAI

NA

All options
enabled

Data Type: Uint8


Describes firmware revision information. This is
the revision of the alternative firmware.
*Initial value depends on revision of firmware in
standby.
Data Type: Visible String
Describes firmware revision information.
*Initial value depends on revision of firmware in
standby. The range of this parameter consists of
55.1 through 55.5 values, converted to text, and
linked together.

Data Type: Bit String


0=disabled
1=enabled
Indicates which function blocks are included in
the device.

Instruction Manual

Detailed SetupResource Block

D103412X012

August 2012

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 44. Resource Block, View 1
Index Number
1

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

RS_STATE

25

FREE_TIME

28

FAULT_STATE
ALARM_SUM.CURRENT

37.2

ALARM_SUM.UNACKNOWLEDGED

37.3

ALARM_SUM.UNREPORTED

37.4

ALARM_SUM.DISABLED

Table 45. Resource Block, View 2


1

Parameter
ST_REV

14.1

GRANT_DENY.GRANT

14.2

GRANT_DENY.DENY

18

FEATURE_SEL

20

CYCLE_SEL

23

NV_CYCLE_T

24

FREE_SPACE

26

SHED_RCAS

27

SHED_ROUT

32

LIM_NOTIFY

33

CONFIRM_TIME

34

WRITE_LOCK

Index Number
37.4

Parameter
ALARM_SUM.DISABLED

44

FB_OPTIONS

52

DETAILED_STATUS

53

TIME_SINCE_RESET

54

DEVICE_ID

Table 47. Resource Block, View 4

37.1

Index Number

Table 46. Resource Block, View 3 (continued)

Index
Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

10

MANUFAC_ID

11

DEV_TYPE

12

DEV_REV

13

DD_REV

15

HARD_TYPES

17

FEATURES

19

CYCLE_TYPE

21

MIN_CYCLE_T

22

MEMORY_SIZE

31

MAX_NOTIFY

38

ACK_OPTION

39

WRITE_PRI

41

ITK_VER

42

DISTRIBUTOR

43

DEV_STRING

45

DIAG_OPTIONS

46

MISC_OPTIONS

47.1

FIRMWARE_REVISION.FIRMWARE_REV_MAJOR

47.2

FIRMWARE_REVISION.FIRMWARE_REV_MINOR

47.3

FIRMWARE_REVISION.FIRMWARE_REV_BUILD

ST_REV

47.4

FIRMWARE_REVISION.IO_FIRMWARE_REV

5.1

MODE_BLK.TARGET_MODE

47.5

FIRMWARE_REVISION.DIAG_CAL_REV

5.2

MODE_BLK.ACTUAL_MODE

47.6

FIRMWARE_REVISION.FIRMWARE_REV_ALL

5.3

MODE_BLK.PERMITTED_MODE

48

HARDWARE_REV

5.4

MODE_BLK.NORMAL_MODE

49

ELECTRONICS_SN

BLOCK_ERR

50

FACTORY_SN

RS_STATE

51

FIELD_SN

25

FREE_TIME

55.1

STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_MAJOR

28

FAULT_STATE

55.2

STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_MINOR

37.1

ALARM_SUM.CURRENT

55.3

STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_BUILD

37.2

ALARM_SUM.UNACKNOWLEDGED

55.4

STBY_FIRMWARE_REV.STBY_IO_FIRMWARE_REV

37.3

ALARM_SUM.UNREPORTED

55.5

STBY_FIRMWARE_REV.STBY_DIAG_CAL_REV

55.6

STBY_FIRMWARE_REV.STBY_FIRMWARE_REV_ALL

Table 46. Resource Block, View 3


Index Number
1

Parameter

-continued-

61

Detailed SetupTransducer Block


August 2012

Instruction Manual
D103412X012

Transducer Block
Overview
The transducer block accepts a signal from an output block as a set point to position a valve using a pneumatic
actuator. Input to the transducer block is in percent. Closed is 0%, and open is 100%. The transducer block contains
setup and calibration information and can be tuned to closely match the actuator. Input characterization permits
modifying the overall characteristic of the instrumentactuatorvalve combination in order to modify the installed gain
characteristic of the loop. The transducer block can also be used to perform instrument and valve diagnostics and
trigger performance alerts.
The following procedures address only the key transducer block parameters; however, all transducer block parameters
are listed in table 414.

Detailed Setup
Note
To setup and calibrate the instrument, the transducer block Mode must be Manual and the Protection must be None.

Transducer Block Mode


Field Communicator

TB > Configure/Setup > Detailed Setup > Transducer Block Mode

Modes
The transducer block can be in one of three modes (MODE_BLK [5]):
 Automatic (Auto) This is the normal mode for this block. When the transducer block is in the auto mode, it accepts
the output from the AO or DO block as a set point and outputs a drive signal to the I/P converter based upon this set
point.
 Out of Service (OOS) Placing the transducer block in Out of Service mode changes the output to the zero power
(no I/P drive) condition.
Field Communicator

 Manual (MAN) Placing the transducer block in Manual will hold the value at the current setpoint (FINAL_VALUE
[13]). The transducer block will not accept changes from the AO or DO blocks. This mode is required to change some
parameters and to run some diagnostics.

Protection
Field Communicator

TB > Configure/Setup > Detailed Setup > Protection

To configure any parameters in the digital valve controller Write Lock (WRITE_LOCK [34]), in the resource block, must
be set to Unlocked (refer to page 45). In addition, protection is provided for various transducer block parameters, as

62

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

indicated in the Protect Category column of table 414, to prevent inadvertently overwriting key data by the host
system or user.
 All will protect all transducer block Parameters.
 Setup and Calibration will protect only Setup and Calibration transducer block parameters.
 Calibration will protect only Calibration transducer block parameters.
 None will not protect any transducer block parameters.

Note
The Device Setup Auto Travel and Manual Travel methods automatically change transducer block protection for the user.

See table 414 for individual parameter details.

Response Control
Travel Tuning
Field Communicator

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning

WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury or property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.

Travel Tuning SetThere are eleven Travel Tuning Sets (TVL_TUNING_SET [42.10]) to choose from. Each tuning set
provides a preselected value for the digital valve controller gain settings.
Tuning set C provides the slowest response and M provides the fastest response. Table 48 lists the proportional gain,
velocity gain and minor loop feedback gain values for preselected tuning sets.
In addition, you can specify Expert tuning and individually set the proportional gain, velocity gain, and minor loop
feedback gain. Individually setting or changing any tuning parameter or running the Performance Tuner or
Stabilize/Optimize will automatically change the tuning set to X (expert).
Table 48. Gain Values for Preselected Travel Tuning Sets
Tuning Set

Travel Velocity Gain

Travel Minor Loop Feedback Gain

C
D
E
F
G

Travel Proportional Gain


4.4
4.8
5.5
6.2
7.2

3.0
3.0
3.0
3.1
3.6

35
35
35
35
34

H
I
J
K
L
M
X (Expert)

8.4
9.7
11.3
13.1
15.5
18.0
User Adjusted

4.2
4.8
5.6
6.0
6.0
6.0
User Adjusted

31
27
23
18
12
12
User Adjusted

Note
Use Expert tuning if standard tuning has not achieved the desired results.

63

Detailed SetupTransducer Block


August 2012

Instruction Manual
D103412X012

Stabilize/Optimize may be used to achieve the desired results more rapidly than Expert tuning.

Table 32 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are
recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either
a higher or lower tuning set to get the desired response.
For an actuator not listed in table 32, you can estimate a starting tuning set by calculating the casing or cylinder
volume. Then, find an actuator in table 32 with the closest equivalent volume and use the tuning set suggested for
that actuator.
Travel Proportional GainTravel Proportional Gain (SERVO_GAIN [18]) is the proportional gain for the travel control
tuning set. Changing this parameter will also change the tuning set to Expert.
Travel Velocity GainTravel Velocity Gain (SERVO_RATE [20]) is the velocity gain for the travel control tuning set.
Changing this parameter will also change the tuning set to Expert.
Travel MLFB GainTravel MLFB Gain (TVL_MLFB_GAIN [44.5]) is the minor loop feedback gain for the travel control
tuning set. Changing this parameter will also change the tuning set to Expert.
Travel Integral EnableTravel Integral Enable (TVL_INTEG_ENABLE [44.1]) is used to enable the integral setting to
improve static performance by correcting for error that exists between the travel target and actual travel.
Travel Integral GainTravel Integral Gain (SERVO_RESET [19]) (also called reset) is the ratio of the change in output
to the change in input, based on the control action in which the output is proportional to the time integral of the
input.
Travel Integral Dead ZoneTravel Integral Dead Zone (TVL_INTEG_DEADZ [44.4]) is a window around the Primary
Setpoint in which the integral action is disabled. The dead band is configurable from 0 to 2%.
Travel Integral Limit HiTravel Integral Limit Hi (TVL_INTEG_LIM_HI [44.2]) provides an upper limit to the integrator
output. The high limit is configurable from 0 to 100% of the I/P drive signal.
Travel Integral Limit LoThe Travel Integral Limit Lo (TVL_INTEG_LIM_LO [44.3]) provides a lower limit to the
integrator output. The low limit is configurable from -100 to 0% of the I/P drive signal.
Performance Tuner

WARNING
During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.

Performance Tuner is used to determine digital valve controller tuning. It will move the valve slightly and monitor the
effects of small tuning changes until an optimum control response is achieved. Because the Performance Tuner can
detect internal instabilities before they become apparent in the travel response, it can generally optimize tuning more
effectively than manual tuning.
Stabilize/Optimize

WARNING
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury
and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize
pressure on both sides of the valve or bleed off the process fluid.

64

Instruction Manual
D103412X012

Detailed SetupTransducer Block


August 2012

If after completing initial setup and calibration the valve cycles or overshoots, or is sluggish, you can improve
operation by running Stabilize/Optimize.
Stabilize/Optimize is included with the device description (DD) firmware. Stabilize/Optimize is accessible from the
transducer block and permits changing the transducer block set point a small amount to see if the valve is unstable or
unresponsive. If valve response is unsatisfactory, the method permits adjusting the digital valve controller tuning to
improve response.
If the valve is unstable, select Decrease Response to stabilize valve operation. This selects the next lower tuning set
(e.g., F to E). If the valve response is sluggish, select Increase Response to make the valve more responsive. This selects
the next higher tuning set (e.g., F to G).
If after selecting Decrease Response or Increase Response the valve travel overshoot is excessive, Increase Damping or
Decrease Damping can be used to select a damping value not represented in a predefined tuning set. Select Decrease
Damping to select a damping value that allows more overshoot. Select Increase Damping to select a damping value that
will decrease the overshoot.
When valve operation is satisfactory, select Exit. Before exiting, you are asked if you want to return the transducer
block mode to Auto. Select Yes to change the transducer block mode to Auto. Select No to leave the transducer block
in its current mode.

Pressure Tuning
Field Communicator

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning

WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury or property damage
caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.

Pressure Tuning Set


There are twelve Pressure Tuning Sets (PRESS_TUNING_SET [42.11]) to choose from. Each tuning set provides a
preselected value for the digital valve controller gain settings.
Tuning set C provides the slowest response and M provides the fastest response. Tuning set B is appropriate for
controlling a pneumatic positioner. Table 49 lists the proportional gain, pressure integrator gain and minor loop
feedback gain values for preselected tuning sets.
In addition, you can specify Expert tuning and individually set the pressure proportional gain, pressure integrator gain,
and pressure minor loop feedback gain. Individually setting or changing any tuning parameter will automatically
change the tuning set to X (expert).

65

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 49. Gain Values for Preselected Pressure Tuning Sets


Tuning Set
B
C
D
E
F
G
H
I
J
K
L
M
X (Expert)

Pressure Proportional Gain


0.5
2.2
2.4
2.8
3.1
3.6
4.2
4.8
5.6
6.6
7.8
9.0
User Adjusted

Pressure Integrator Gain

Pressure Minor Loop Feedback Gain

0.3
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
User Adjusted

35
35
35
35
35
34
31
27
23
18
12
12
User Adjusted

Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize may be used to achieve the desired results more rapidly than Expert tuning.

Pressure Proportional GainPressure Proportional Gain (PRESS_PROP_GAIN [47.3]) is the proportional gain for the
pressure control tuning set. Changing this parameter will also change the tuning set to Expert.
Pressure MLFB GainPressure MLFB Gain (PRESS_MLFB_GAIN [47.11]) is the minor loop feedback gain for the
pressure control tuning set. Changing this parameter will also change the tuning set to Expert.
Pressure Integral GainPressure Integral Gain (PRESS_INTEG_GAIN [47.4]) (also called reset) is the ratio of the
change in output to the change in input, based on the control action in which the output is proportional to the time
integral of the input. Changing this parameter will also change the tuning set to Expert.
Pressure Integral Dead ZonePressure Integral Dead Zone (PRESS_INTEG_DEADZ [47.6]) is a window around the
Primary Setpoint in which the integral action is disabled. The dead band is configurable from 0 to 2%.
Pressure Integral Limit HiPressure Integral Limit Hi (PRESS_INTEG_HI_LIM [47.7]) provides an upper limit to the
integrator output. The high limit is configurable from 0 to 100% of the I/P drive signal.
Pressure Integral Limit LoPressure Integral Limit Lo (PRESS_INTEG_LO_LIM [47.8]) provides a lower limit to the
integrator output. The low limit is configurable from -100 to 0% of the I/P drive signal.

Travel Pressure Control


Field Communicator

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control

Travel/Pressure StateTravel/Pressure State (TVL_PRESS.STATE [41.2]) indicates if the instrument is being used for
travel control (position control) or as an I/P (pressure control)
Travel/Pressure Select

CAUTION
When using Pressure Fallback Manual Recovery or Pressure Fallback Auto Recovery, the valve travel has the potential of
moving rapidly causing potential process instability when returning to Travel Control.

66

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Note
Travel / Pressure Select must be set to Travel for double acting actuators.

Travel / Pressure Select (TVL_PRESS_SELECT [41.1]) determines if the instrument is setup for position or pressure
control. Select Travel, Pressure, Travel with Pressure Fallback/Auto recovery or Travel with Pressure Fallback/Manual
Recovery. If the travel sensor fails, and Travel with Pressure Fallback/Auto Recovery is selected, it will return to travel
control when the travel sensor starts working again. Travel with Pressure Fallback/Manual recovery will stay in pressure
control until Travel Pressure Select is changed to Travel or Travel with Pressure Fallback/Auto recovery. It is not
necessary to enable the Travel Sensor Alert for Pressure Fallback to occur.
Travel Deviation Pressure FallbackTravel Deviation Pressure Fallback occurs when the instrument detects that the
travel sensor is outside of its normal range of operation or that a gross deviation exists between set point and actual
travel. It switches to Pressure Control and no longer uses the travel sensor to position the valve.
Travel Cutoff HiTravel Cutoff Hi (FINAL_VALUE_CUTOFF_HI [15]) defines the high cutoff point for the travel in
percent (%) of precharacterized setpoint. Above this cutoff, the travel target is set to 123.0% of the ranged travel.
Travel Cutoff Hi is deactivated by setting it to 125.0%.
Travel Cutoff LoTravel Cutoff Lo (FINAL_VALUE_CUTOFF_LO [16]) defines the low cutoff point for the travel in
percent (%) of precharacterized setpoint. Below this cutoff, the travel target is set to -23%. A Travel Cutoff Lo of
0.5% is recommended to help ensure maximum shutoff seat loading. Travel Cutoff Lo is deactivated by setting it to
-25.0%
Pressure Cutoff OpenPressure Cutoff Open (PRESS_CUTOFF_HI [47.1]) defines the high cutoff point for the
pressure in percent (%) of precharacterized setpoint. Above this cutoff, the pressure target is set to 123.0%. A
Pressure Cutoff Open of 99.5% is recommended to ensure valve goes fully open. Pressure Cutoff Hi is deactivated by
setting it 125%.
Pressure Cutoff ClosedPressure Cutoff Closed (PRESS_CUTOFF_LO [47.2]) defines the low cutoff point for the
pressure in percent (%) of precharacterized setpoint. Below this cutoff, the pressure target is set to -23%. A Pressure
Cutoff Closed of 0.5% is recommended to help ensure maximum shutoff seat loading. Pressure Cutoff Closed is
deactivated by setting it to -25.0%
Pressure Range HiPressure Range Hi (PRESS_RANGE_HI [42.7]) is the high end of output pressure range. Enter the
pressure that corresponds with 100% valve travel when Zero Power Condition is closed, or 0% valve travel when
Zero Power Condition is open. This pressure must be greater than the Pressure Range Lo.
Pressure Range LoPressure Range Lo (PRESS_RANGE_LO [42.8]) is the low end of the output pressure range. Enter
the pressure that corresponds to 0% valve travel when Zero Power Condition is closed, or 100% valve travel when
Zero Power Condition is open. The pressure must be less than the Pressure Range Hi.

Input Characterization
Field Communicator

TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization

Input Characterization (INPUT_CHAR [50]) defines the relationship between the travel target and the setpoint
received from the output block. Travel target is the output from the characterization function.

67

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Custom Characterization Table


TB > Configure/Setup > Detailed Setup > Response Control > Custom Characterization Table

Field Communicator

You can select from the three fixed input characteristics shown in figure 41 or you can select a custom characteristic.
Figure 41 shows the relationship between the travel target and travel set point for the fixed input characteristics.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel, for
a corresponding set point, in % of ranged set point. Set point values range from -25.0% to 125%. Before modification,
the custom characteristic is linear. You cannot modify the custom points if the Input Characterization (INPUT_CHAR
[50]) is set to custom.
Figure 41. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Power Condition = Closed)
125

100

100

Travel Target, %

Travel Target, %

125

-25

-25
-25

Set Point, %

100

125

-25

Set Point, %

Input Characteristic Linear


125

Travel Target, %

100

-25
-25
A65351

68

100

Input Characteristic Equal Percentage

Set Point, %

100

Input Characteristic Quick Opening

125

125

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Outblock Selection
Field Communicator

TB > Configure/Setup > Detailed Setup > Response Control > Outblock Selection

Outblock Selection (OUTBLOCK_SEL [96]) defines which output function block will control the setpoint of the valve.
The output block that is not selected will shed its mode to reflect that it does not have control of the valve.

Alerts
The DVC6200f provides two levels of alerts; Instrument alerts and PlantWeb alerts.

Instrument Alert Conditions


Instrument Alert Conditions, when enabled, detect many operational and performance issues that may be of interest.
To view these alerts, the user must open the appropriate status screen on a host such as DeltaV, ValveLink software or
a Field Communicator.

PlantWeb Alerts
Some instrument alert conditions can also be used to trigger PlantWeb alerts that will be reported in Failed,
Maintenance or Advisory categories, as configured by the user. PlantWeb alerts, when enabled, can participate in the
DeltaV alarm interface tools such as the alarm banner, alarm list and alarm summary.
When a PlantWeb alert occurs, the DVC6200f sends an event notification and waits a specified period of time for an
acknowledgment to be received. This occurs even if the condition that caused the alert no longer exists. If the
acknowledgment is not received within the prespecified timeout period, the event notification is retransmitted. This
reduces the possibility of alert messages getting lost.
PlantWeb alerts are modebased. Refer to table C1 for details.

Note
Additional details on setting up and using PlantWeb Alerts can be found in Appendix C of this manual.

Electronics Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts

Drive Current
Drive CurrentDrive Current (DRIVE_CURRENT [54]) displays the measured Drive Current actually flowing through
the I/P converter in percent of maximum drive.
Drive Current AlertThis alert is active when the difference between the expected Drive Current and the actual
Drive Current has exceeded the Drive Current Alert Time.
Drive Current Alert EnableWhen enabled Drive Current Alert Enable activates the Drive Current Alert.
Drive Current ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown for the Drive Current alert. When enabled, and the alert condition is present, the transducer Actual

69

Detailed SetupTransducer Block

Instruction Manual

August 2012

D103412X012

mode is placed Out of Service. The instrument will attempt to drive the valve to the Zero Power Condition and will
no longer execute transducer control function.
Drive Current Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when Drive Current Shutdown clears. If not enabled, the transducer block will remain Out of Service until
power is removed and restored or the user changes the transducer block target mode to Manual or Auto. In any
case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or until the
shutdown trigger is disabled.
Drive Current Alert PointThe Drive Current Alert Point (DRIVE_CURRENT_ALRT_PT [76.4]) is when the absolute
difference between the Drive Current and Drive Signal exceeds the set threshold for greater than the Drive Current
Alert Time.
Drive Current Alert TimeThe Drive Current Alert Time (DRIVE_CURRENT_TIME [76.5]) is the maximum time that
the Drive Current Alert Point can be exceeded before the Drive Current Alert is active.
Drive Signal
Drive SignalThe Drive Signal (DRIVE_SIGNAL [53]) displays the commanded Drive Signal being sent to the I/P
converter as a percentage of the maximum drive.
Drive Signal Alert
The Drive Signal Alert is active if one of the following conditions exist:
Where Zero Power Condition is defined as closed:
Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%
Where Zero Power Condition is defined as open:
Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%
Drive Signal Alert EnableWhen enabled Drive Signal Alert Enable activates the Drive Signal Alert.
Processor Impaired
Program Memory AlertThis alert is active if a pending Flash or NVM failure is present.
Program Memory Alert EnableWhen enabled Program Memory Alert Enable activates the Program Memory Alert.
Program Memory ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling
Self Test Shutdown. When enabled, and the Program Memory Alert is active, the transducer Actual mode is placed
out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
Program Memory Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Program Memory Shutdown clears. If not enabled, the transducer block will

70

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
Static Memory AlertThis alert is active if a failure occurs in the FRAM memory where the static parameters are
stored.
Static Memory Alert EnableWhen enabled Static Memory Alert Enable activates the Static Memory Alert.
Static Memory ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the Static Memory Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
Static Memory Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Static Memory Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
Processor AlertThis alert is active if a failure occurs in the main processor.
Processor Alert EnableWhen enabled Processor Alert Enable activates the Processor Alert.
I/O Processor AlertThis alert is active if a failure occurs in the I/O processor.
I/O Processor ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the I/O Processor Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
I/O Processor Man RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or disabling
Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target mode when
the condition that caused I/O Processor Shutdown clears. If not enabled, the transducer block will remain Out of
Service until power is removed and restored or the user changes the transducer block target mode to Manual or
Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or
until the shutdown trigger is disabled.

Configuration Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts

Output Block Timeout


Output Block Timeout AlertThis alert is active if the analog or discrete output block has not executed for longer
than the configured timeout.
Output Block Timeout Alert EnableWhen enabled Output Block Timeout Alert Enable activates the Output Block
Timeout Alert.
Output Block Timeout ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or
disabling Self Test Shutdown. When enabled, and the Output Block Timeout Alert is active, the transducer Actual

71

Detailed SetupTransducer Block

Instruction Manual

August 2012

D103412X012

mode is placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no
longer execute transducer control function.
Output Block Timeout Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When enabled, the transducer block will return to Target mode
when the condition that caused Output Block Timeout Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
Output Block TimeoutThe Output Block Timeout (OUTPUT_BLK_TIMEOUT [76.3]) is the maximum time between
updates from the AO or DO block to the transducer block setpoint.
Blocks Set to Default
Blocks Set to Defaults AlertThis alert is active if the resource block has undergone Restart with Defaults. This will
stay active until the transducer block is changed from Out of Service.
Blocks Set to Defaults Alert EnableWhen enabled Blocks Set to Defaults Alert Enable activates the Blocks Set to
Default Alert.
Alert Key
The Alert Key (ALERT_KEY [4]) is the identification number of the plant unit. Devices in a loop or plant section can be
assigned with a common alert key to aid the operator in determining location of alerts.

Sensor Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts

Travel Sensor
Travel Sensor AlertThis alert is active if the Travel Sensor reading is outside the functional range, or the sensor
becomes disconnected.
Travel Sensor Alert EnableWhen enabled Travel Sensor Alert Enable activates the Travel Sensor Alert.
Travel Sensor ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the Travel Sensor alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
Travel Sensor Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When not enabled, the transducer block will return to Target
mode when Travel Sensor Shutdown clears. If enabled, the transducer block will remain Out of Service until power is
removed and restored or the user changes the transducer block target mode to Manual or Auto. In any case, the
target mode will remain Out of Service, if the condition that caused the shutdown remains or until the shutdown
trigger is disabled.
Pressure Sensors
Pressure A Sensor AlertThis alert is active if the Port A Pressure Sensor reading is outside the functional range.
Pressure A Sensor Alert EnableWhen enabled Pressure A Sensor Alert Enable activates the Pressure A Sensor Alert.

72

Instruction Manual
D103412X012

Detailed SetupTransducer Block


August 2012

Pressure A Sensor ShutdownThe Shutdown Trigger (SHUTDOWN_TRIGGER [76.1]) permits enabling or disabling
Self Test Shutdown. When enabled, and the Port A Pressure Sensor Alert is active, the transducer Actual mode is
placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer
execute transducer control function.
Pressure A Sensor Manual RecoveryShutdown Recovery (SHUTDOWN_RECOVERY [76.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When not enabled, the transducer block will return to Target
mode when Pressure A Sensor Shutdown clears. If enabled, the transducer block will remain Out of Service until
power is removed and restored or the user changes the transducer block target mode to Manual or Auto. In any
case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or until the
shutdown trigger is disabled.
Pressure B Sensor AlertThis alert is active if the Port B Pressure Sensor reading is outside the functional range.
Pressure B Sensor Alert EnableWhen enabled Pressure B Sensor Alert Enable activates Pressure B Sensor Alert.
Supply Pressure Sensor AlertThis alert is active if the Supply Pressure Sensor reading is outside the functional
range.
Supply Pressure Sensor Alert EnableWhen enabled Supply Pressure Sensor Alert Enable activates the Supply
Pressure Sensor Alert.
Pressure Fallback
Pressure Fallback AlertThis alert is active if a travel sensor failure or a gross travel deviation has resulted in fallback
to pressure control.
Pressure Fallback Alert EnableWhen enabled Pressure Fallback Alert Enable activates the Pressure Fallback Alert.
Temperature Sensor
Temperature Sensor AlertThis alert is active if the Temperature Sensor reading is outside the functional range.
Temperature Sensor Alert EnableWhen enabled Temperature Sensor Alert Enable activates the Temperature
Sensor Alert.

Environment Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts

Supply Pressure
SupplySupply (SUPPLY_PRESSURE.VALUE [35.2]) displays the instrument supply pressure in kPa, bar, or psi.
Supply Pressure Hi AlertThis alert is active when the supply pressure exceeds the Supply Pressure Hi Alert Point.
Supply Pressure Hi Alert EnableWhen enabled Supply Pressure Hi Alert Enable activates Supply Pressure Hi Alert.
Supply Pressure Hi Alert PointThe Supply Pressure Hi Alert is active when supply pressure exceeds the Supply
Pressure Hi Alert Point (SUP_PRES_HI_ALRT_PT [76.8]).
Supply Pressure Lo AlertThis alert is active when the supply pressure is lower than the Supply Pressure Lo Alert
Point.

73

Detailed SetupTransducer Block

Instruction Manual

August 2012

D103412X012

Supply Pressure Lo Alert EnableWhen enabled Supply Pressure Lo Alert Enable activates Supply Pressure Lo Alert.
Supply Pressure Lo Alert PointSupply Pressure Lo Alert Point (SUP_PRES_LO_ALRT_PT [76.9]). When the supply
pressure falls below the supply pressure alert point, the supply pressure alert is active. To disable the supply
pressure alert, set Supply Pressure Alert Point to zero.
Temperature Limit
TemperatureDegrees Fahrenheit or Celsius. The temperature (TEMPERATURE [48]) is measured from a sensor
mounted on the digital valve controller's printed wiring board.
Temperature Hi AlertThis alert is active if the temperature is greater than the Temperature Hi Alert Point.
Temperature Hi Alert EnableWhen enabled Temperature Hi Alert Enable activates the Temperature Hi Alert.
Temperature Hi Alert PointThe Temperature Hi Alert is active when the instrument temperature exceeds the
Temperature Hi Alert Point (TEMP_HI_ALRT_PT [76.6]).
Temperature Lo AlertThis alert is active if the temperature is lower than the Temperature Lo Alert Point.
Temperature Lo Alert EnableWhen enabled Temperature Lo Alert Enable activates the Temperature Lo Alert.
Temperature Lo Alert PointThe Temperature Lo Alert is active when the instrument temperature is lower than the
Temperature Lo Alert Point (TEMP_LO_ALRT_PT [76.7]).

Travel Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts

Note
The alerts contained in this section are valid for both travel and pressure control.

Travel Target
Travel target is the output from the characterization function.
Travel
Travel (TRAVEL.VALUE [34.2]) displays the actual position of the valve in percent (%) of calibrated travel.
Travel Deviation
Travel DeviationTravel Deviation (TRAVEL_DEVIATION [52]) displays the absolute difference in percent between
Travel Target and Actual Travel.
Travel Deviation AlertThis alert is active if the Travel deviation exceeds the Travel Deviation Alert Point by more
than the Travel Deviation Time.
Travel Deviation Alert EnableWhen enabled Travel Deviation Alert Enable actives the Travel Deviation Alert.

74

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Travel Deviation Alert PointThe Travel Deviation Alert Point (TVL_DEV_ALRT_PT [77.1]) is the alert point for the
difference, expressed in percent (%), between the travel target and the actual travel. When the difference exceeds
the alert point for more than the Travel Deviation Time, the Travel Deviation Alert is set.
Travel Deviation TimeTravel Deviation Time (TVL_DEV_TIME [77.2]) is the time, in seconds, that the travel
deviation must exceed the Travel Deviation Alert Point before the alert is set.
Travel Deviation DeadbandTravel Deviation Deadband (TVL_DEV_DB [77.3]) is the travel in percent threshold (%)
of ranged travel required to clear a Travel Deviation alert, once it has been set. See figure 42.
Figure 42. Travel Hi Alert Deadband
ALERT IS SET
TRAVEL ALERT
HIGH POINT
TRAVEL ALERT
DEADBAND

ALERT IS CLEARED
A6532

Travel Limit
Travel Hi Hi AlertThis alert is active if the Travel exceeds the Travel Hi Hi Alert point.
Travel Hi Hi Alert EnableWhen enabled Travel Hi Hi Alert Enable activates the Travel Hi Hi Alert.
Travel Hi Hi Alert PointTravel Hi Hi Alert Point (TVL_HI_HI_ALRT_PT [77.18]) is the value of the travel, in percent
(%) of ranged travel, which, when exceeded, sets the Travel Alert Hi Hi alert.
Travel Hi Hi DeadbandTravel Hi Hi Deadband (TVL_HI_HI_DB [77.19]) is the travel, in percent (%) of ranged travel,
required to clear a Travel Hi Hi alert, once it has been set. See figure 42.
Travel Lo Lo AlertThis alert is active if the Travel is lower than the Travel Lo Lo Alert point.
Travel Lo Lo Alert EnableWhen enabled Travel Lo Lo Alert Enable activates the Travel Lo Lo Alert.
Travel Lo Lo Alert PointThe Travel Lo Lo alert is set when the value of the travel, in percent (%) of ranged travel,
goes below the Travel Lo Lo Alert Point (TVL_LO_LO_ALRT_PT [77.12]).
Travel Lo Lo DeadbandTravel Lo Lo Deadband (TVL_LO_LO_DB [77.13]) is the travel, in percent (%) of ranged
travel, required to clear a Travel Lo Lo alert once it has been set. See figure 43.

75

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Figure 43. Travel Lo Alert Deadband


ALERT IS CLEARED

TRAVEL ALERT
DEADBAND

ALERT IS SET

TRAVEL ALERT
LO POINT

A65321

Travel Hi/Lo
Travel Hi AlertThis alert is active if the Travel exceeds the Travel Hi Alert point.
Travel Hi Alert EnableWhen enabled Travel Hi Alert Enable activates the Travel Hi Alert.
Travel Hi Alert PointTravel Hi Alert is set if the ranged travel rises above the Travel Hi Alert Point (TVL_HI_ALRT_PT
[77.16]). Once the alert is set, the ranged travel must fall below the alert high point set by the Travel Hi Deadband
before the alert is cleared. See figure 42.
Travel Hi DeadbandTravel Hi Deadband (TVL_HI_DB [77.17]) is the travel, in percent (%) of ranged travel, required
to clear a Travel Hi Alert, once it has been set. See figure 42.
Travel Lo AlertThis alert is active if the Travel is lower than the Travel Lo Alert point.
Travel Lo Alert EnableWhen enabled Travel Lo Alert Enable activates the Travel Lo alert.
Travel Lo Alert PointThe Travel Alert Lo alert is set when the value of the travel, in percent (%) of ranged travel,
goes below the Travel Lo Alert Point (TVL_LO_ALRT_PT [77.14]).
Travel Lo DeadbandTravel Lo Deadband (TVL_LO_DB [77.15]) is the travel, in percent (%) of ranged travel,
required to clear a travel lo alert, once it has been set. See figure 43.

Proximity Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts

Note
See page 203 for additional details on using Proximity detection.

Travel
Travel displays the actual position of the valve in percent (%) of calibrated travel.

76

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Travel Open
Travel Open AlertThis alert is active if the Travel is greater than the Travel Open Alert Point.
Travel Open Alert EnableWhen enabled Travel Open Alert Enable activates the Travel Open Alert.
Travel Open Alert PointTravel Open Alert Point (TVL_OPEN_ALRT_PT [77.8]) is the value of the travel in percent
(%) or ranged travel, which, when exceeded, sets the Travel Open Alert.
Travel Open DeadbandTravel Open Deadband (TVL_OPEN_DB [77.9]) is the travel in percent (%) of ranged travel
required to clear a Travel Open alert, once it has been set.
Travel Closed
This alert is active if the Travel is lower than the Travel Closed Alert Point.
Travel Closed AlertThis alert is active is the Travel goes below the Travel Closed Alert Point.
Travel Closed Alert EnableWhen enabled Travel Closed Alert Enable activates the Travel Closed Alert.
Travel Closed Alert PointThe Travel Closed Alert is set when the value of the travel, in percent (%) of ranged travel,
goes below the Travel Closed Alert Point (TVL_CLOSED_ALRT_PT [77.10]).
Travel Closed DeadbandTravel Closed Deadband (TVL_CLOSED_DB [77.11]) is the travel in percent (%) of ranged
travel required to clear a Travel Closed alert, once it has been set.
Proximity
Proximity Hi Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Hi Alert Point
and the Travel Hi Hi Deadband.
Proximity Hi Hi Alert EnableWhen enabled Proximity Hi Hi Alert Enable activates the Proximity Hi Hi Alert.
Proximity Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Alert Point and
the Travel Hi Deadband.
Proximity Hi Alert EnableWhen enabled Proximity Hi Alert Enable activates the Proximity Hi Alert.
Proximity Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Alert Point and
the Travel Lo Deadband.
Proximity Lo Alert EnableWhen enabled Proximity Lo Alert Enable activates the Proximity Lo Alert.
Proximity Lo Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Lo Alert Point
and the Travel Lo Lo Deadband.
Proximity Lo Lo Alert EnableWhen enabled Proximity Lo Lo Alert Enable activates the Proximity Lo Lo Alert.

77

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Travel History Alerts


Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts

Cycle Counter
Cycle CounterThe Cycle Counter (CYCLE_COUNT [73]) records the number of times the travel changes direction.
The change in direction must occur after the deadband has been exceeded before it can be counted as a cycle. See
figure 44. You can reset the Cycle Counter by configuring it as zero.
Figure 44. Cycle Counter Deadband (set at 10%)
Deadband exceeded, and direction
changed, new Reference Point
established

Deadband Reference
Point
Deadband (+/- 5%)

Point at which
cycle is counted

A65331

Cycle Counter AlertThis alert is active if the Cycle Counter exceeds the Cycle Counter Alert Point. It is cleared after
you reset the Cycle Counter to a value less than the alert point.
Cycle Counter Alert EnableWhen enabled Cycle Counter Alert Enable activates checking of the difference between
the Cycle Counter and the Cycle Counter Alert point.
Cycle Counter Alert PointCycle Counter Alert Point (CYCLE_COUNT_ALRT_PT [77.6]) is the value of the Cycle
Counter, in cycles, which, when exceeded, sets the Cycle Counter Alert.
Cycle Counter DeadbandCycle Counter Deadband (CYCLE_COUNT_DB [77.7]) is the area around the travel
reference point, in percent (%) of ranged travel, that was established at the last increment of the Cycle Counter. This
area must be exceeded before a change in travel direction can be counted as a cycle. See figure 44.
Travel Accumulator
Travel AccumulatorTravel Accumulator (TRAVEL_ACCUM [72]) records the total change in travel, in percent (%) of
ranged travel, since the accumulator was last cleared. The value of the Travel Accumulator increments when the
magnitude of the change exceeds the Travel Accumulator Deadband. See figure 45. You can reset the Travel
Accumulator by configuring it to zero.

78

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Figure 45. Travel Accumulator Deadband (set at 10%)


Deadband exceeded,
new Reference Point
established

This amount of change is


added to the Travel
Accumulator

Deadband Reference
Point
A6534

Deadband (+/- 5%)

Travel Accumulator AlertThis alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point.
The Travel Accumulator Alert is set when the Travel Accumulator value exceeds the Travel Accumulator Alert Point.
It is cleared after you reset the Travel Accumulation to a value less than the alert point.
Travel Accumulator Alert EnableWhen enabled Travel Accumulator Alert Enable activates checking of the
difference between the Travel Accumulator value and the Travel Accumulator Alert Point.
Travel Accumulator Alert PointTravel Accumulator Alert Point (TVL_ACCUM_ALRT_PT [77.4]) is the value of the
Travel Accumulator, in percent (%) of ranged travel, which, when exceeded, sets the Travel Accumulator Alert.
Travel Accumulator DeadbandTravel Accumulator Deadband (TVL_ACCUM_DB [77.5]) is the area around the
travel reference point, in percent (%) of ranged travel, that was established at the last increment of the
accumulator. This area must be exceeded before a change in travel can be accumulated. See figure 45.

Performance Alerts
Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts

Note
Performance Alerts are only available with a PD tier instrument. Additionally, for the PD alerts to function properly:
The transducer block mode must not be out of service.
The travel/pressure control state must be in travel control mode, and
Bench Set Hi, Bench Set Lo, and Nominal Supply Pressure must be set in the Spec Sheets, then enable the Performance
Information instrument alert (PERF_ENABLE [75.7]).

PD Inside Status
PD Inside Status shows the status of Performance Diagnostics.

79

Detailed SetupTransducer Block


August 2012

Instruction Manual
D103412X012

PD Run
PD Run enables or disables Performance Diagnostics in the instrument (PD Inside). Selecting PD Off disables PD Inside.
Selecting PD On enables PD Inside.
Performance Critical
Performance Critical AlertThis alert is active if the instrument is no longer able to control the valve or performance
has been dramatically reduced.
Performance Critical Alert EnableWhen enabled Performance Critical Alert Enable activates the Performance
Critical Alert.
Performance Reduced
Performance Reduced AlertThis alert is active if the instrument has detected a reduction in performance.
Performance Reduced Alert EnableWhen enabled Performance Reduced Alert Enable activates the Performance
Reduced Alert.
Performance Information
Performance Information AlertThis alert is active if the instrument has detected a condition that may pertain to
control performance.
Performance Information Alert EnableWhen enabled Performance Information Alert Enable activates the
Performance Information Alert.

PlantWeb Alert Enable


Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable

Failed EnableFailed Enable (FAILED_ENABLE [62]) enables or disables conditions that can cause a failed alert. A
failed alert indicates a failure within the device that will make the device or some part of the device nonoperational.
Table C2 lists the available PlantWeb alerts.
Maintenance EnableMaintenance Enable (MAINT_ENABLE [63]) enables or disables conditions that can cause a
maintenance alert. A maintenance alert indicates the device or some part of the device needs maintenance soon.
Table C2 lists the available PlantWeb alerts.
Advise EnableAdvise Enable (ADVISE_ENABLE [64]) enables or disables conditions that can cause an advisory alert.
An advisory alert indicates informative conditions that do not have a direct impact on the device's primary
functions. Table C2 lists the available PlantWeb alerts.

PlantWeb Alert Reporting


Field Communicator

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting

Failed SuppressFailed Suppress (FAILED_MASK [65]) determines which of the failed alert conditions are
suppressed so that they are not reported. Even if reporting is suppressed, the bit in Failed Active (FAILED_ACTIVE
[59]) is still set.
Maintenance SuppressMaintenance Suppress (MAINT_MASK [66]) determines which of the maintenance alert
conditions are suppressed so that they are not reported. Even if reporting is suppressed, the bit in Maintenance
Active (MAINT_ACTIVE [60]) is still set.

80

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Advise SuppressAdvise Suppress (ADVISE_MASK [67]) determines which of the advise alert conditions are
suppressed so that they are not reported. Even if reporting is suppressed, the bit in Advise Active (ADVISE_ACTIVE
[61]) is still set.

Instrument
Field Communicator

TB > Configure/Setup > Detailed Setup > Instrument

Tag DescriptionThe Tag Description (TAG_DESC [2]) is a 32 character description used to assign a unique
description to each block within the digital valve controller to describe the intended application for the block.
Pressure UnitsDefine the output and supply pressure units (PRESSURE_UNITS [90]) in either psi, bar, or kPa.
Temperature UnitsEnter the temperature units (TEMPERATURE_UNITS [89]) in degrees Fahrenheit or Celsius. The
temperature is measured from a sensor mounted on the digital valve controller's printed wiring board.
Travel UnitsDefine the units for valve travel (TVL_UNITS [91]) in inches, centimeters, millimeters or degrees.
Length UnitsDefine the units for valve dimensions (LENGTH_UNITS [92]) in inches, centimeters, or millimeters.
Area UnitsDefine the units for actuator area (AREA_UNITS [93]) in inches2, centimeter2 or millimeter2.
Spring Rate UnitsDefine the units for actuator spring rate (SPRING_RATE_UNITS [94]) in lbs/in2 or N/M.
Relay TypeEnter the Relay Type (RELAY_TYPE [42.5]).There are three categories of relays that result in
combinations from which to select.
Relay Type: The relay type is printed on the label affixed to the relay body:
A = doubleacting or single acting
B = singleacting, reverse
C= singleacting, direct
Special App: This is used in singleacting applications where the unused output port is configured to read the
pressure downstream of a solenoid valve. See page 29 for additional information.
Lo Bleed: The label affixed to the relay body indicates it is a low bleed version.
Zero Power ConditionZero Power Condition (ZERO_PWR_COND [42.2]) identifies whether the valve is open or
closed when instrument power is lost. If you are unsure how to set this parameter, disconnect the segment loop
power to the instrument. The resulting valve travel is the Zero Power Condition.
Maximum Supply PressureEnter the maximum supply pressure (MAX_SUPP_PRESS [42.6]) in psi, bar, or kPa,
depending on what was selected for pressure units.
Calibration PersonName of the person performing last calibration (XD_CAL_WHO [31]).
Calibration LocationIndicates the location of the last instrument calibration (XD_CAL_LOC [29]).
Calibration DateEnter a date with the format MM/DD/YY. Date is a userdefined variable that provides a place to
save the date of the last calibration (XD_CAL_DATE [30]).
Last Calibration TypeIndicates the type of the last calibration performed on the instrument. Possible values are:
Not Calibrated, Single Point Calibration, Auto Calibration, Manual Calibration.

81

Detailed SetupTransducer Block

Instruction Manual

August 2012

D103412X012

Valve and Actuator


Field Communicator

TB > Configure/Setup > Detailed Setup > Valve and Actuator

Valve
Valve ManufacturerEnter the identification number of the manufacturer of the valve (VALVE_MAN_ID [25]) on
which the instrument is mounted. Select from the dropdown list or enter the manufacturer's identification number
as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100.
Valve Model NumberEnter the valve model number (VALVE_MODEL_NUM [26]), (design letter or type number)
for the valve on which the instrument is mounted.
Valve Serial NumberEnter the serial number of the valve (VALVE_SN [27]) on which the instrument is mounted.
Valve StyleEnter the type of valve (VALVE_TYPE [28]), slidingstem or rotary, on which the instrument is mounted.
Valve SizeEnter the size of the valve (VALVE_SIZE [83.1]) on which the instrument is mounted.
Valve ClassEnter the valve pressure class rating (VALVE_CLASS [83.2]).
Rated TravelEnter the valve rated travel (RATEDTRAVEL [83.3]) in inches or mm for sliding-stem valves, or in
degrees of rotation for rotary valves.
Actual TravelEnter the actual travel (ACTUAL_TRAVEL [83.4]) in inches or mm for sliding-stem valves, or in degrees
of rotation for rotary valves.
Shaft Stem DiameterEnter the valve stem diameter (SHAFT_STEM_DIA [83.5]) in inches or millimeters.
Packing TypeEnter the valve packing construction (PACKING_TYPE [83.6]).
Inlet PressureEnter the valve inlet pressure (INLET_PRESSURE [83.7]).
Outlet PressureEnter the valve outlet pressure (OUTLET_PRESSURE [83.8]) in psig, kPa, Bar, inHg, inH2O, or kg/cm2.
Trim
Seat TypeEnter the valve seat type (SEAT_TYPE [84.1]).
Leak ClassEnter the valve leak class (LEAK_CLASS [84.2]).
Port DiameterEnter the valve port diameter (PORT_DIAMETER [84.3]) in inches or mm.
Port TypeEnter the valve port type (PORT_TYPE [84.4]).
Flow DirectionEnter the flow direction (FLOWDIRECTION [84.5]) through the valve.
Push Down ToEnter the effect on valve movement when the stem is moved down (PUSH_DOWN_TO [84.6]).
Flow Tends ToEnter the effect on valve travel with increasing flow (FLOW_TENDS_TO [84.7]).
Unbalanced AreaEnter the valve unbalanced area (UNBALANCED_AREA [84.8]) in in2 or mm2.

82

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Actuator
Actuator ManufacturerEnter the manufacturer's identification number (ACT_MAN_ID [22]) of the actuator on
which the instrument is mounted. Select from the dropdown list or enter the manufacturer's identification number
as defined by the Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100.
Actuator Model NumberEnter the type number for the actuator (ACT_MODEL_NUM [23]) on which the
instrument is mounted.
Actuator StyleSelect the Actuator Style (ACTUATOR_STYLE [42.1]), spring & diaphragm, piston doubleacting
without spring, piston singleacting with spring, or piston doubleacting with spring.
Actuator Serial NumberEnter the serial number (ACT_SN [24]) for the actuator on which the instrument is
mounted.
Actuator SizeEnter the size of the actuator (ACTUATOR_SIZE [85.1]) on which the instrument is mounted.
Actuator Fail ActionSets actuator action to be performed upon loss of actuator air pressure (ACT_FAIL_ACTION
[21]).
View / Edit Feedback ConnectionRefer to table 410 for Feedback Connection options. Choose the assembly that
matches the actuator travel range.

Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will
decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor
(on the back of the DVC6200f housing) has to remain within this range throughout the entire valve travel. See figure 22. The
linear magnet assemblies are symmetrical. Either end may be up.

Table 410. Feedback Connection Options


Magnet Assembly

Travel Range
mm

Inch

Degrees

SStem #7

4.2-7

0.17-0.28

SStem #19

8-19

0.32-0.75

SStem #25

20-25

0.76-1.00

SStem #38

26-38

1.01-1.50

SStem #50

39-50

1.51-2.00

SStem #100

51-100

2.01-4.00

SStem #210

101-210

4.01-8.25

SStem #1 Roller

60-90

RShaft Window #1

60-90

RShaft Window #2

60-90

RShaft End Mount

60-90

Travel Sensor Motion

WARNING
If you answer YES to the prompt for permission to move the valve when setting the Travel Sensor Motion, the instrument
will move the valve through its full travel range. To avoid personal injury and property damage caused by the release of

83

Detailed SetupTransducer Block

Instruction Manual

August 2012

D103412X012

pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.

Travel Sensor Motion (TRAVEL_SEN_MOTION [42.3]) establishes the proper valve travel sensor (feedback)
rotation/movement. For quarterturn actuators determine rotation by viewing the rotation of the magnet assembly
from the back of the instrument.

Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be
referred to as a magnetic array in user interface tools.

For instruments with relay A or C If increasing air pressure at output A causes the magnet assembly to move up, or the
actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet assembly
to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW. For instruments
with relay B.
For instruments with relay B If decreasing air pressure at output B causes the magnet assembly to move up, or the
actuator shaft to rotate counterclockwise, enter Towards Top of Instrument/CCW. If it causes the magnet assembly
to move down, or the actuator shaft to rotate clockwise, enter Away From Top of Instrument/CW.
Lever StyleEnter the lever style (LEVER_STYLE [85.10]) for rotary actuators as either Pivot Point or Rack and Pinion.
Lever Arm LengthDefines the lever arm length (MOMENT_ARM [85.11]) for rotary actuators.
Effective AreaEnter the actuator effective area (EFFECTIVE_AREA [85.2]) in in2, cm2, or mm2.
AirSelect Opens or Closes, indicating the effect of increasing air pressure (AIR [85.3]) on the valve travel.
Upper Bench SetEnter the upper actuator operating pressure (UPPER_BENCH_SET [85.5]).
Lower Bench SetEnter the lower actuator operating pressure (LOWER_BENCH SET [85.4]).
Nominal Supply PressureEnter the nominal instrument supply pressure (NOMINAL_SUPPLY PRESSURE [85.6]).
Spring RateEnter the actuator spring rate (SPRING_RATE [85.7]) in lbsin or Nm.
Reference
Trim Style 1Enter the valve trim style (TRIM_STYLE_1 [84.9]).
Trim Style 2Enter the valve trim style (TRIM_STYLE_2 [84.10]).
Stroking Time OpenEnter the time required to stroke the valve from closed to open (STROKING_TIME_OPEN
[85.8]).
Stroking Time CloseEnter the time required to stroke the valve from open to close (STROKING_TIME_CLOSE
[85.9]).

84

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 411. Output Block PV Status


FEATURE_SEL
PW Alarms Set PV Status

Enabled

Transducer Mode,
Actual

AO / DO
PV Status(2)

AO / DO
PV Substatus

AO/DO PV
Limit Substatus(1)

OOS

Bad

Device Failure

Constant

Man

Bad

Nonspecific

Constant

Auto

Fail

Uncertain

Subnormal

See table 412

Auto

Maintenance, no Fail

Uncertain

Nonspecific

See table 412

Good

Advisory

See table 412

Auto

Advisory, no Fail, no
Maintenance
None

Good

NonSpecific

See table 412

OOS

Bad

Device Failure

Constant

Man

Bad

NonSpecific

Constant

Auto

Fail

Good

NonSpecific

See table 412

Auto

Maintenance, no Fail

Good

NonSpecific

See table 412

Auto

Advisory, no Fail, no
Maintenance

Good

NonSpecific

See table 412

Auto

None

Good

NonSpecific

See table 412

Auto

Not Enabled

Active PlantWeb
Alarms

NOTES:
X = No Effect
1. PV limit substatus reflects only READBACK limit substatus. SP limit substatus reflects only out block rate limits.
2. Firmware Revision 1.1 and earlier will set AO/DO PV Status to Bad if Feedback Sensor has failed, i.e.; Travel Sensor Fail. However, if the Travel Sensor fails, and the instrument falls back to
pressure, PV Status will remain good.

MAI Channel Map


Field Communicator

TB > Configure/Setup > Detailed Setup > MAI Channel Map

Allows the user to specify which transducer block parameter is available through each of the MAI Block channels
(MAI_CHANNEL_1 through MAI_CHANNEL_8 [95.1 through 95.8]). Transducer block parameters available to each
channel:
11
12
13
14
15
16
17

=
=
=
=
=
=
=

18
19
10
11
12
13

FINAL_VALUE
TRAVEL_TARGET
FINAL_POSITION_VALUE
TRAVEL
SUPPLY_PRESS
ACT_PRESS_A
ACT_PRESS_B

=
=
=
=
=
=

ACT_PRESS_DIFF
DRIVE_SIGNAL
TRAVEL_DEVIATION
TEMPERATURE
CYCLE_COUNT
TRAVEL_ACCUM

Table 412. Limit Sub Status


Out Block

Transducer Mode

In Cutoff Region

Rate Limited

Limit SubStatus

AO, DO

OOS

Constant

AO, DO

MAN

Constant

AO

AUTO

High

High Limited

AO

AUTO

Low

Low Limited

AO

AUTO

High

High Limited

AO

AUTO

Low

Low Limited

AO

AUTO

None

None

Not Limited

DO

AUTO

High

High Limited

DO

AUTO

Low

Low Limited

DO

AUTO

None

Not Limited

NOTE: X = No Effect

85

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Alert Handling
Field Communicator

TB > Configure/Setup > Detailed Setup > Alert Handling

PlantWeb Alert Simulate


When enabled, PlantWeb Alert Simulate (PWA_SIMULATE [39]) allows the user to write to the following PlantWeb and
Instrument alert parameters; Failed Active, Maintenance Active, Advise Active, Environment Active, Travel Active,
Proximity Active, Travel History Active, Performance Active, PD Event Active, PD Detail 1 Active, PD Detail 2 Active, PD
Detail 3 Active, PD Detail 4 Active, PD Detail 5 Active, PD Detail 6 Active. This provides a way to simulate these alerts
for testing. In order to enable PWA Simulate, the Aux Terminal must be jumpered.
PlantWeb Alert Simulate is cleared on a power cycle. It can also be cleared manually, or by removing the Aux terminal
jumper.
Simulate Active Alerts
Failed ActivePermits simulating an active Failed alarm (FAILED_ACTIVE [59]).
Maintenance ActivePermits simulating an active Maintenance alarm (MAINT_ACTIVE [60]).
Advise ActivePermits simulating an active Advisory alarm (ADVISE_ACTIVE [61]).
PlantWeb Alert Handling
PlantWeb Alerts Set PV StatusWhen selected, PlantWeb alerts will set the PV status according to table 411.
Block Error ReportingWhen enabled, the AO or DO BLOCK_ERR [6] parameter will report PlantWeb Alerts. the
same as Block Error in the resource block.
Block Error bit 6 (Device Needs Maintenance Soon) will report any active PlantWeb Maintenance Alert.
Block Error bit 13 (Device Needs Maintenance Now) will report any active PlantWeb Failed Alert.

Block Errors
Table 413 lists conditions reported in the BLOCK_ERR [6] and XD_ERR [11] parameters. Conditions in italics are not
applicable for the transducer block and are provided only for your reference.
Table 413. Transducer Block BLOCK_ERR and XD_ERROR Conditions
Condition Number

86

Condition Name and Description

Other (N/A)

Block Configuration Error Indicates that one of the following parameters have been configured out of the proper range: 15,
16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.

Link Configuration Error (N/A)

Simulate Active Indicates that the simulation jumper is in place on the aux terminals. This is not an indication that the I/O
blocks are using simulation data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].

Local Override (N/A)

Device Fault State - (NA)

Maintenance Needed Soon (N/A)

Input failure/process variable has Bad status (N/A)

Output failure (N/A)

Memory failure (N/A)

10

Lost Static Data Indicates that manufacturing functional or thermal tests were incomplete

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now Indicates that manufacturing functional or thermal tests were incomplete

14

Power Up (N/A)

15

Out of Service Indicates Out of Service Mode.

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Transducer Block Parameter List


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Protection Category: Indicates whether or not the parameter is writable while the PROTECTION parameter
is set to a particular level.
-N/A indicates a readonly parameter that is never writable, regardless of the value of the PROTECTION parameter
-NONE indicates a readonly parameter that is always writable, regardless of the value of the PROTECTION parameter
-CAL indicates a parameter that is only writable while the value of the PROTECTION parameter is NONE.
-SETUP indicates a parameter that is only writable while the value of the PROTECTION parameter is NONE or CAL.
-ALL indicates a parameter that is writable while the value of the PROTECTION parameter is NONE, CAL, or SETUP & CAL.

 Double indentation and shaded Index Number indicates subparameter


Table 414. Transducer Block Parameter Definitions
Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Static Revision
ST_REV

RO

N/A

Tag Description
TAG_DESC

RW

ALL

Strategy
STRATEGY

RW

ALL

Alert Key
ALERT_KEY

Block Mode
MODE_BLK

RW

ALL

Range

0 to 65535

0 to 65535

1 to 255

Initial Value

Protect
Category

N/A

N/A

Data Type: Uint16


The revision level of the static data.
Increments by one each time a static
parameter is written. The value is
reset to 0 whenever a Restart with
Defaults is performed. See
Restarting the Instrument.

NULL

SETUP

Data Type: String


The description of the block.

SETUP

Data Type: Uint16


Used to help group blocks.

SETUP

Data Type: Uint8


The identification number of the
plant unit. Devices in a loop or plant
section can be assigned with a
common alert key to aid the
operator in determining location of
alerts.

TARGET

5.1

RW

ALL

7: OOS

NONE

ACTUAL

5.2

RO

N/A

N/A

N/A

3:AUTO
4:MANUAL
7: OOS

NONE

3:AUTO

NONE

N/A

N/A

PERMITTED

5.3

RW

ALL

NORMAL

5.4

RW

ALL

Block Error
BLOCK_ERR

RO

N/A

3:AUTO
4:MANUAL
7:OOS

3: Simulate Active
10: Static Memory Failed
(Functional or thermal
data missing)
13: Maintenance
Needed Now
(Functional or thermal
data missing)
15: OutofService

Description

Data Type: DS69


The actual, target, permitted, and
normal modes.
Target: The requested block mode
Actual: The current mode of
the block
Permitted: Allowed modes for
Target
Normal: Most common mode
for Target

Data Type: Bit String (2 byte)


Error status associated with
hardware or firmware for the
transducer block.

-Continued-

87

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Update Event
UPDATE_EVT

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

UNACKNOWLEDGED

7.1

RW

ALL

0=Undefined
1=Acknowledged
2=Unacknowledged

NONE

UPDATE_STATE

7.2

RO

N/A

0=Undefined
1=Updated reported
2=Update Not reported

N/A

TIME_STAMP

7.3

RO

N/A

N/A

STATIC_REVISION

7.4

RO

N/A

N/A

RELATIVE_INDEX

7.5

RO

N/A

N/A

RW

ALL

0=Undefined
1=Acknowledged
2=Unacknowledged

NONE

N/A

0=Undefined
1=Clear-reported
2=Clear-not reported
3=Active-reported
4=Active-not reported

N/A

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

ALARM_STATE

TIME_STAMP

Description

Data Type: DS73


Alert generated by change to static
data.

8
8.1

8.2

8.3

RO

RO

N/A

N/A

N/A

Data Type: DS72


Used to report the BLOCK_ERR
alarm to the host system

SUBCODE

8.4

RO

N/A

Subcode: Bit Number in


BLOCK_ERR

VALUE

8.5

RO

N/A

Value of parameter at
alarm time for a single
alarm, 0 for multiple
alarms

N/A

Transducer Directory
TRANSDUCER_DIRECTORY

RO

N/A

1,1

1,1

N/A

Data Type: Array [2] of Unit16


Not used

Transducer Type
TRANSDUCER_TYPE

10

RO

106

106

N/A

Data Type: Uint16


Identifies the type of the transducer.

Transducer Error
XD_ERROR or TDC_ERROR

11

RO

Valid Numbers:0 = No
Error

N/A

Data Type: Uint8


Error code for the transducer block.

Collection Directory
COLLECTION_DIRECTORY

12

RO

1,1,1,1,1

1,1,1,1,1

N/A

Data Type: Array [5] of Unit32


Not used


FINAL_VALUE

13

Setpoint Status
STATUS

13.1

RW

MAN
OOS

Setpoint
VALUE

13.2

RW

MAN
OOS

N/A

NONE

N/A

NONE

Setpoint Range
FINAL_VALUE_RANGE

-25 to 125

14

EU_100

14.1

RO

N/A

100

100

N/A

EU_0

14.2

RO

N/A

N/A

UNITS_INDEX

14.3

RO

N/A

PERCENT

1342

N/A

DECIMAL

14.4

RO

N/A

N/A

-Continued-

88

Data Type: DS65


In Travel Control: Setpoint for valve
travel in %, prior to characterization.
In Pressure Control: Setpoint for
implied valve travel as % or pressure
range, prior to characterization.
FINAL_VALUE is not updated unless
the AO block is selected in
FEATURE_SELECT. For example,
FINAL_VALUE still has last value
written by AO channel 1 when DO is
in control.
Data Type: DS68
High and Low range limit values,
engineering units code, and number
of digits to the right of the decimal
place to be used to display the Final
Value.

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Travel Cutoff Hi
FINAL_VALUE_CUTOFF_HI

Travel Cutoff Lo
FINAL_VALUE_CUTOFF_LO

FINAL_POSITION_VALUE

Index
Number

15

16

RO /
RW

RW

Mode

MAN
OOS

RW

MAN
OOS

Range

-25 to 125

-25 to 125

Initial Value

99.5

Protect
Category

SETUP

0.5

SETUP

N/A

N/A

17

Description
Data Type: Float
When the servo goes above this % of
span, the stem position goes to the
upper limit. Cutoffs are OFF when
Low is at -25% and high is at +125%.
Must be > low cutoff + .625%.
Data Type: Float
When the servo goes below this % of
span, the stem position goes to the
lower limit. Cutoffs are OFF when
Low is at -25% and high is at +125%.
Must be < hi cutoff - .625%.
Data Type: DS65
In Travel Control: Valve travel in %,
decharacterized to correlate with
Setpoint (FINAL_VALUE [13]).
In Pressure Control: Implied valve
travel as a % of pressure range,
decharacterized to correlate with
Setpoint (FINAL_VALUE [13]).
Controls AI channel 3.
Data Type: Float
Travel Control Only. Gain of servo.

Travel Status (Decharacterized)


STATUS

17.1

RO

N/A

Travel (Decharacterized)
VALUE

17.2

RO

N/A

-25 to 125%

Travel Proportional Gain


SERVO_GAIN

18

RW

MAN
OOS

>=0

4.4

SETUP

Travel Integral Gain


SERVO_RESET

19

RW

MAN
OOS

> = 0 , = 0 causes wind


down

9.4

SETUP

Data Type: Float


Travel Control Only. If set to 0, will
cause integrator to wind down.

Travel Velocity Gain


SERVO_RATE

20

RW

MAN
OOS

>=0

3.0

SETUP

Data Type: Float


Travel Control Only. Rate of servo.

Actuator Fail Action


ACT_FAIL_ACTION

21

RW

MAN
OOS

0=Uninitialized
1=SelfClosing
2=SelfOpening

1=
SelfClosing

SETUP

Data Type: Enum (Uint8)


Action performed by actuator in the
event of air pressure.

Actuator Manufacturer
ACT_MAN_ID

22

RW

ALL

0x5100

SETUP

Data Type: Uint32


The actuator manufacturer
identification number.

Actuator Model Number


ACT_MODEL_NUM

23

RW

ALL

Null

SETUP

Data Type: Visible String


Model number of actuator.

Actuator Serial Number


ACT_SN

24

RW

ALL

Null

SETUP

Data Type: Visible String


Serial number of actuator.

Valve Manufacturer
VALVE_MAN_ID

25

RW

ALL

0x5100

SETUP

Data Type: Uint32


The valve manufacturer
identification number.

Valve Model Number


VALVE_MODEL_NUM

26

RW

ALL

Null

SETUP

Data Type: Visible String


The valve model number.

Valve Serial Number


VALVE_SN

27

RW

ALL

Null

SETUP

Data Type: Visible String


The valve serial number.

Valve Style
VALVE_TYPE

28

RW

ALL

1=sliding-stem

SETUP

Data Type: Enum (Uint8)


Selects Rotary or sliding-stem.

Calibration Location
XD_CAL_LOC

29

RW

ALL

Null

CAL

Data Type: Visible String


Where device was last calibrated.

Calibration Date
XD_CAL_DATE

30

RW

ALL

Uninitialized

CAL

Data Type: Date


Date of last calibration.

Calibration Person
XD_CAL_WHO

31

RW

ALL

Null

CAL

Data Type: Visible String


Name of person performing last
calibration.

1=sliding-stem
2=Rotary

N/A

-Continued-

89

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

SETPOINT_D

Index
Number

RO /
RW

Mode

32.1

RW

MAN
OOS

Setpoint(D)
VALUE

32.2

RW

MAN
OOS

33.1

RO

N/A

Travel (D)
VALUE

33.2

RO

N/A

NONE

0 = closed 1 = open
5,10,15.. = %

NONE

N/A
0 = closed 1 = open
5,10,15.. = %

N/A

34

Travel Status
STATUS

34.1

RO

N/A

N/A

Travel
VALUE

34.2

RO

N/A

N/A

SUPPLY_PRESSURE

35.1

RO

N/A

N/A

Supply Pressure
VALUE

35.2

RO

N/A

N/A

36

Pressure A Status
STATUS

36.1

RO

N/A

N/A

Pressure A
VALUE

36.2

RO

N/A

N/A

PRESSURE_B

Description
Data Type: DS_66
SETPOINT_D is not updated unless
the DO block is selected in
FEATURE_SEL.
STATUS indicates the validity of
value, set by the DO block
OUT.STATUS
VALUE is the discrete value of
setpoint. Only values of 0, 1, or
increments of 5 up to 95 are
allowed. Written by DO channel 22.
Data Type: DS_66
STATUS indicates the validity of
VALUE.
VALUE: 0=closed , 1=open
5,10,15.. = %. Controls DI Channel
23
Data Type: DS65
In Travel Control: Actual valve travel
in % of calibrated travel range.
In Pressure Control: Implied valve
travel in % of pressure range.
Controls AI channel 4.

35

Supply Pressure Status


STATUS

PRESSURE_A

37

Pressure B Status
STATUS

37.1

RO

N/A

N/A

Pressure B
VALUE

37.2

RO

N/A

N/A
-Continued-

90

Protect
Category

33

Travel(D) Status
STATUS

TRAVEL

Initial Value

32

Setpoint(D) Status
STATUS

TRAVEL_D

Range

Data Type: DS65


STATUS indicates the validity of
VALUE. VALUE is pressure of air
supply, controls AI channel 5.

Data Type: DS65


STATUS Indicates the validity of
VALUE.
Pressure of primary air output,
controls AI channel 6.
Data Type: DS65
STATUS indicates the validity of
VALUE. VALUE is the
Pressure on secondary output,
controls AI channel 7.

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
PRESSURE_DIFF

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

38

Pressure Differential Status


STATUS

38.1

RO

N/A

N/A

Pressure Differential
VALUE

38.2

RO

N/A

N/A

PWA Simulate
PWA_SIMULATE

39

Grant Deny
GRANT_DENY

40

RO or
RW*

ALL

GRANT

40.1

RW

ALL

DENY

40.2

RW

ALL

Travel Pressure Control


TVL_PRESS_CONTROL

1=Simulate Off
2=Simulate Enabled

0:Program
1:Tune
2:Alarm
3:Local

Description
Data Type: DS65
STATUS indicates the validity of
VALUE. VALUE is the difference
between PRESSURE_A and
PRESSURE_B, controls AI channel 8.
Data Type: Enum (Uint8)
When this is set to 2 all the alert
ACTIVE parameters can be written,
except for INST_ALERTS_ACTIVE.
SHUTDOWN_ALERT_ACTIVE. This
allows alerts to be simulated for
testing with hosts. NOTE: only
ACTIVE parameters are affected by
this. * PWA Simulate is RW only if a
jumper is installed across the Aux
Terminal. If no jumpered is installed
across the Aux Terminal, PWA
Simulate is RO.

1=Simulate Off

ALL

all bits cleared

NONE

all bits cleared

NONE

1=Travel

SETUP

Data Type: Enum (Uint8)


Selects whether travel sensor or port
A pressure is used for feedback.

N/A

Data Type: Enum (Uint8)


Indicates which sensor is used for
feedback

Data Type: DS50


Options for controlling access of
host computer and local control
panels to operating, tuning, and
alarm parameters of the block. Has
no effect on the DVC6200f.
GRANT: 0=N/A, 1= granted
DENY: 0=N/A, 1= denied

41

Travel/Pressure Select
TVL_PRESS_SELECT

41.1

RW

ALL

1=Travel
2=Pressure
3=TVL/PRESS Auto Recv
4=TVL/PRESS Man Recv

Travel/Pressure State
TVL_PRESS_STATE

41.2

RO

N/A

1=Travel
2=Pressure
-Continued-

91

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Basic Setup
BASIC_SETUP

Index
Number

RO /
RW

Mode

Range

Protect
Category

Description

42

Actuator Style
ACTUATOR_STYLE

42.1

RW

MAN
OOS

1=Spring & Diaphragm


2=PistonDbl w/o Spring
3=PistonDbl w/Spring
4=Piston Sgl w/Spring

1=Spring &
Diaphragm

SETUP

Data Type: Enum (Uint8)

Zero Power Condition


ZERO_PWR_COND

42.2

RW

MAN
OOS

1=Valve Closed
2=Valve Open

1=Valve Closed

SETUP

Data Type: (Uint8)


Enum Identifies whether the valve is
open or closed when instrument
power is lost.

Travel Sensor Motion


TRAVEL_SEN_MOTION

42.3

RW

MAN
OOS

1=Counter Clockwise
2=Clockwise

1=Counter
Clockwise

SETUP

Data Type: Enum (Uint8)

MAN
OOS

100: Default Array


64: SStem #19 Array
65: SStem #25 Array
66: SStem #38 Array
67: SStem #50 Array
70: SStem #100 Array
74: SStem #200 Array
85: SStem #1 Roller
Array
90: RShaft End Array
95: RShaft #1 Window
Array
97: RShaft #2 Window
Array

SETUP

Data Type: Enum (Uint8)

SETUP

Data Type: Enum (Uint8)

Feedback Connection
FEEDBACK_CONN

42.4

RW

Relay Type
RELAY_TYPE

42.5

RW

MAN
OOS

1=Relay A or CDouble or
Single Direct
2=Relay BSingle Reverse
5=Relay CSpecial App.
Single Direct
6=Relay BSpecial App.
Single Reverse
9=LoBleed Relay A or
=Relay A or
CDouble or Single
CDouble or
Direct
Single Direct
10=LoBleed Relay B
Single Reverse
13=LoBleed Relay
CSpecial App.Single
Direct
10=LoBleed Relay
BSpecial App.-Single
Reverse

Maximum Supply Pressure


MAX_SUPP_PRESS

42.6

RW

MAN
OOS

> 0, < = 150

35 psig

SETUP

Data Type: Float

Pressure Range Hi
PRESS_RANGE_HI

42.7

RW

MAN
OOS

> 0, < = 150

15.0 psig

SETUP

Data Type: Float


Defines pressure corresponding to
max pressure in pressure control
mode.

Pressure Range Lo
PRESS_RANGE_LO

42.8

RW

MAN
OOS

> = 0, < = 150

3.0 psig

SETUP

Data Type: Float


Defines pressure corresponding to
minimum pressure in pressure
control mode.

Travel Calibration Trigger


TVL_CAL_TRIGGER

42.9

RW

MAN
OOS

1 = Aux Term ignored

SETUP

Not available in the DVC6200f

Travel Tuning Set


TVL_TUNING_SET

42.10

RW

MAN
OOS

1=B, 2= C, ...12=M
23=X

2=C

SETUP

Data Type: Enum (Uint8)


Letter (B through M or X)

Pressure Tuning Set


PRESS_TUNING_SET

42.11

RW

MAN
OOS

1=B, 2=C, ...12= M


23=X

2=C

SETUP

Data Type: Enum (Uint8)


Letter (B through M or X)

-Continued-

92

Initial Value

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
TRAVEL_CAL

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Description

43

Travel Count
TVL_COUNT

43.1

RO

N/A

Travel Hi Calibration
TVL_HI_CAL

43.2

RW

MAN
OOS

<TVL_FAC_HI
>TVL_LO_CAL

CAL

Data Type: Uint16


Maximum drive calibration point

Travel Lo Calibration
TVL_LO_CAL

43.3

RW

MAN
OOS

>TVL_FAC_LO
<TVL_HI_CAL

CAL

Data Type: Uint16


Minimum drive calibration point

Travel Crossover
TVL_CROSSOVER

43.4

RW

MAN
OOS

>0% < = 100%

50%

CAL

Data Type: Float


Not used for the DVC6200f

Travel Fac Hi
TVL_FAC_HI

43.5

RO

N/A

Set by Factory

N/A

Data Type: Uint16


Maximum value of travel sensor
counts. Set at factory.

Travel Fac Lo
TVL_FAC_LO

43.6

RO

N/A

Set by Factory

N/A

Data Type: Uint16


Minimum value of travel sensor
counts. Set at factory.

Travel IP Bias
TVL_IP_BIAS

43.7

RW

MAN
OOS

0% - 100%

70%

CAL

Data Type: Float

Travel MLFB Bias


TVL_MLFB_BIAS

43.8

RW

MAN
OOS

0 - 100%

50%

CAL

Data Type: Float

Last Calibration Type


TVL_CAL_TYPE

43.9

RW

MAN
OOS

0: Not Calibrated
1: Single Point Calibration
2: Auto Calibration CAL
2: Auto Calibration
3: Manual Calibration

Data Type: Enum (Uint8)

TRAVEL_TUNE

Data Type: Uint16


Raw feedback from Travel Sensor

44

Travel Integral Enable


TVL_INTEG_ENABLE

44.1

RW

MAN
OOS

1=Off
2=On

2=On

SETUP

Data Type: Enum (Uint8)

Travel Integral Limit Hi


TVL_INTEG_LIM_HI

44.2

RW

MAN
OOS

0% - 100%

30%

SETUP

Data Type: Float

RW

MAN
OOS

-100% - 0%

-30%

SETUP

Data Type: Float

0% - 2%

0.25%

SETUP

Data Type: Float

>=0

35

SETUP

Data Type: Float

Travel Integral Limit Lo


TVL_INTEG_LIM_LO

44.3

Travel Integral Dead Zone


TVL_INTEG_DEADZ

44.4

RW

MAN
OOS

Travel MLFB Gain


TVL_MLFB_GAIN

44.5

RW

MAN
OOS

-Continued-

93

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
TRAVEL_CAL_RUN

Index
Number

RO /
RW

Mode

Range

Protect
Category

Description

45

Travel Calibration Command


TVL_CAL_CMD

45.1

RW

MAN

Travel Calibration Prog


TVL_CAL_PROG

45.2

RO

N/A

Travel Calibration Status


TVL_CAL_STATUS

45.3

Reserved
TVL_CAL_RESERVED

45.4

RO

N/A

1: Operating
2: Autocalibrate
3: Not Used by DVC6200f
4: Mark Full Open
5: Mark Full Closed
6: Manual Calibrate Final
7: Abort
8: Clear Cal Status
9: Manual Calibrate Init
10: Manual Calibrate
Restore
11: Reset Travel Sensor
Error
12: Reserved
1=Operating
13: Execute Performance
Tuner
14: Execute Performance
Tuner (Graphite Packing)
16: Execute Performance
Tuner (Booster)
17: Execute Performance
Tuner (Graphite Packing
and Booster)
19: Autocalibration, Set
Filter
20: Autocalibrate
Extended, Set Filter
0%
0: auto cal complete
1: calibration complete
2: auto cal in progress
3: manual cal in progress
3: Not Used by DVC6200f
5: upper position marked
6: lower position marked
7: calibration error
8: Performance Tuner
active
no bits set
9: Performance Tuner
Success
10: Performance Tuner
Error (No movement)
11: Performance Tuner
Error (Accessories
unstable)
12: Performance Tuner
Error (Other)

CAL

Data Type: Enum (Uint8)


Resets to 1 after a write

N/A

Data Type: Uint8

N/A

Data Type: Bit String (2 bytes)


All bits set to 0 when mode changes
from OOS. 0 = FALSE,
1 = TRUE

Reserved
-Continued-

94

Initial Value

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
PRESS_CAL

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Description

46

Supply Pressure Scale


SUPP_PRESS_SCALE

46.1

RW

MAN
OOS

>0

CAL

Data Type: Float

Supply Pressure Offset


SUPP_PRESS_OFFSET

46.2

RW

MAN
OOS

0 to 16383

CAL

Data Type: Uint16

Pressure A Scale
PRESS_A_SCALE

46.3

RW

MAN
OOS

>0

CAL

Data Type: Float

Pressure A Offset
PRESS_A_OFFSET

46.4

RW

MAN
OOS

0 to 16383

CAL

Data Type: Uint16

>0

CAL

Data Type: Float

CAL

Data Type: Uint16

Pressure B Scale
PRESS_B_SCALE

46.5

RW

MAN
OOS

Pressure B Offset
PRESS_B_OFFSET

46.6

RW

MAN
OOS

0 to 16383

Pressure IP Bias
PRESS_IP_BIAS

46.7

RW

MAN
OOS

0-100%

70%

CAL

Data Type: Float

Pressure MLFB Bias


PRESS_MLFB_BIAS

46.8

RW

MAN
OOS

0-100%

50%

CAL

Data Type: Float

RW

MAN
OOS

-25 -125%,
> CUTOFF_LO

99.50%

SETUP

Data Type: Float

-25 -125% < CUTOFF_HI

0.50%

SETUP

Data Type: Float


PRESS_TUNE
Pressure Cutoff Hi
PRESS_CUTOFF_HI

47
47.1

Pressure Cutoff Lo
PRESS_CUTOFF_LO

47.2

RW

MAN
OOS

Pressure Proportional Gain


PRESS_PROP_GAIN

47.3

RW

MAN
OOS

> = 0, < 32

2.2

SETUP

Data Type: Float


Proportional gain

Pressure Integral Gain


PRESS_INTEG_GAIN

47.4

RW

MAN
OOS

> = 0, < 32

0.1

SETUP

Data Type: Float


Integral resets per second

Pressure Rate Gain


PRESS_RATE_GAIN

47.5

RW

MAN
OOS

> = 0, < = 512

SETUP

Data Type: Float


Derivative gain

Pressure Integral Dead Zone


PRESS_INTEG_DEADZ

47.6

RW

MAN
OOS

= 0%, < = 2.0%

0.25%

SETUP

Data Type: Float


Integrator Deadzone, 1/2 width

Pressure Integral Limit Hi


PRESS_INTEG_HI_LIM

47.7

RW

MAN
OOS

> = 0%, < = 100%,


>INTEG_LO

20%

SETUP

Data Type: Float


Integrator limits

Pressure Integral Limit LO


PRESS_INTEG_LO_LIM

47.8

RW

MAN
OOS

< = 0%, > = -100%,


<INTEG_HI

-20%

SETUP

Data Type: Float


Integrator limits

Pressure Integral IC Hi
PRESS_INTEG_IC_HI

47.9

RW

MAN
OOS

>= -100%, < = 100%

12%

Not used by the DVC6200f

Pressure Integral IC Lo
PRESS_INTEG_IC_LO

47.10

RW

MAN
OOS

>= -100%, < = 100%

-12%

Not used by the DVC6200f

Pressure MLFB Gain


PRESS_MLFB_GAIN

47.11

RW

MAN
OOS

> 0, < = 100

35

SETUP

Data Type: Float

Temperature
TEMPERATURE

48

RO

N/A

N/A

N/A

Data Type: Float


Electronics temperature - Controls
AI channel 11

Target Travel
TRAVEL_TARGET

49

RO

Status
STATUS

49.1

RO

MAN
OOS

N/A

Value
VALUE

49.2

RO

MAN
OOS

N/A

RW

MAN
OOS

Input Characterization
INPUT_CHAR

50

1=Linear
2=Equal %
3=Quick Opening
4=Reserved
5=Custom

1=Linear

SETUP

Data Type: DS65


In Travel Control: Setpoint for valve
travel in %, post characterization.
In Pressure Control: Setpoint for
implied valve travel as a % or
pressure range, post
characterization.

Data Type: Enum (Uint8)

-Continued-

95

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Protect
Category

0 to 100%

N/A

Data Type: Float


Absolute value of (TRAVEL_TARGET
[49] - TRAVEL [34]), Controls AI
channel 10

N/A

0 to 100%

N/A

Data Type: Float


Controls AI channel 9

RO

N/A

0 to 100%

N/A

Data Type: Float

RO

N/A

-100% to 100%

N/A

Data Type: Float

RW

MAN
OOS

Travel Deviation
TRAVEL_DEVIATION

52

RO

N/A

Drive Signal
DRIVE_SIGNAL

53

RO

Drive Current
DRIVE_CURRENT

54

MLFB
MLFB

55

Failed Alarm
FAILED_ALM

56

Linear, Y=X

Data Type: DS71


Used to report alerts to host system.
RW

ALL

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

NONE

0=Undefined
1=Clear-reported
2=Clear-not reported
3=Active-reported
4=Active-not reported

0=Undefined

N/A

ALARM_STATE

56.2

RO

N/A

TIME_STAMP

56.3

RO

N/A

N/A

SUBCODE

56.4

RO

N/A

N/A

VALUE

56.5

RO

N/A

N/A

Maintenance Alarm
MAINT_ALM

57

UNACKNOWLEDGED

57.1

Data Type: Float


Value of parameter at alarm time for
single alarm, 0 for multiple alarms
Data Type: DS71
Used to report alerts to host system

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

NONE

0=Undefined
1=Clear-reported
2=Clear-not reported
3=Active-reported
4=Active-not reported

0=Undefined

N/A

ALARM_STATE

57.2

RO

N/A

TIME_STAMP

57.3

RO

N/A

N/A

SUBCODE

57.4

RO

N/A

N/A

VALUE

57.5

RO

N/A

N/A

-Continued-

96

Description

SETUP

51

56.1

Initial Value

Data Type: Unit16 Array[43]


Each item - 2500 to 12500
First integrator is number of valid
points. Followed by up to 21 X
values and then 21 Y values.
X values must be increasing.
Y values must be increasing or same.
A value of 2050 represent 20.50%
Custom Points can be written only if
Input Characterization
(INPUT_CHAR [50]) is not custom.

Custom Points
CUSTOM_POINTS

UNACKNOWLEDGED

Range

Data Type: Float


Value of parameter at alarm time for
single alarm, 0 for multiple alarms

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Advise Alarm
ADVISE_ALM
UNACKNOWLEDGED

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

58
58.1

Description
Data Type: DS71
Used to report alerts to host system

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

NONE

0:Undefined
1:Clear-reported
2:Clear-not reported
3:Active-reported
4:Active-not reported

0=Undefined

N/A

ALARM_STATE

58.2

RO

N/A

TIME_STAMP

58.3

RO

N/A

N/A

SUBCODE

58.4

RO

N/A

N/A

VALUE

58.5

RO

N/A

N/A

Data Type: Float


Value of parameter at alarm time for
single alarm, 0 for multiple alarms

N/A

0:Drive Current
1:Drive Signal
2:Processor Impaired
3:Output Block Timeout
4:Blocks Set to Defaults
5:Travel Sensor
6:Outlet Pressure Sensor
7:Supply Pressure
Sensor
8:Temperature Sensor
9:Supply Pressure
All bits: 0
10:Temperature Limit
11:Travel Deviation
12:Travel Limit
13:Travel Accumulator
14:Cycle Counter
15:Performance Critical
16:Performance
Reduced
17:Performance
Information
18: Shutdown Alert

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Failed Alert Status

N/A

0:Drive Current
1:Drive Signal
2:Processor Impaired
3:Output Block Timeout
4:Blocks Set to Defaults
5:Travel Sensor
6:Outlet Pressure Sensor
7:Supply Pressure
Sensor
8:Temperature Sensor
9:Supply Pressure
All bits: 0
10:Temperature Limit
11:Travel Deviation
12:Travel Limit
13:Travel Accumulator
14:Cycle Counter
15:Performance Critical
16:Performance
Reduced
17:Performance
Information
18: Shutdown Alert

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Maintenance Alert Status

Failed Active
FAILED_ACTIVE

Maintenance Active
MAINT_ACTIVE

59

60

RO(1)

RO(1)

1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-

97

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Advise Active
ADVISE_ACTIVE

Failed Enable
FAILED_ENABLE

Maintenance Enable
MAINT_ENABLE

Advise Enable
ADVISE_ENABLE

Failed Suppress
FAILED_MASK

Index
Number

61

62

63

64

65

RO /
RW

RO(1)

RW

RW

RW

RW

Mode

N/A

ALL

ALL

ALL

ALL

Range

0:Drive Current
1:Drive Signal
2:Processor Impaired
3:Output Block Timeout
4:Blocks Set to Defaults
5:Travel Sensor
6:Outlet Pressure Sensor
7:Supply Pressure
Sensor
8:Temperature Sensor
9:Supply Pressure
All bits: 0
10:Temperature Limit
11:Travel Deviation
12:Travel Limit
13:Travel Accumulator
14:Cycle Counter
15:Performance Critical
16:Performance
Reduced
17:Performance
Information
18: Shutdown Alert

Same as for
FAILED_ACTIVE above

Enabled Bits:
0: Drive Current
2: Processor
Impaired
4: Blocks Set to
Default
5: Travel Sensor
15: Performance
Critical
18: Shutdown
Alert

Same as for
MAINT_ACTIVE above

Enabled Bits:
1: Drive Signal
3: Output Block
Timeout
6: Outlet Pressure
Sensor
9: Supply Pressure
11: Travel
Deviation
13: Travel
Accumulator
14: Cycle Counter
16: Performance
Reduced

Same as for
ADVISE_ENABLE above

Enabled Bits:
8: Temperature
Sensor
9: Supply Pressure
Sensor
10: Temperature
Limit
12: Travel Limit

Same as for
FAILED_ACTIVE above

1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-

98

Initial Value

All bits: 0

Protect
Category

Description

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Advise Alert Status

ALL

Data Type: Bit String (4 byte)


0=disable
1=enable
Failed alert enable. Enable allows
detection of alert. All alerts can be
disabled.

ALL

Data Type: Bit String (4 byte)


0=disable
1=enable
Maintenance alert enable. Enable
allows detection of alert. All alerts
can be disabled.

ALL

Data Type: Bit String (4 byte)


0=disable
1=enable
Advise alert enable. Enable allows
detection of alert. All alerts can be
disabled.

ALL

Data Type: Bit String (4 byte)


0=disable
1=enable
Failed alert mask.
MASK controls whether an alert is
reported. If alert is enabled the alert
condition is evaluated and the
ACTIVE parameter is updated to
reflect if alert is active or not. If the
bit is set reporting is suppressed.
Default is all bits cleared.

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Maintenance Suppress
MAINT_MASK

Index
Number

66

RO /
RW

RW

Mode

ALL

Range

Same as for
MAINT_ACTIVE above

Initial Value

All bits: 0

Protect
Category

Description

ALL

Data Type: Bit String (4 byte)


0=disable
1=enable
Maintenance alert mask. MASK
controls whether an alert is
reported. If alert is enabled the alert
condition is evaluated and the
ACTIVE parameter is updated to
reflect if alert is active or not. If the
bit is set reporting is suppressed.
Default is all bits cleared.

Advise Suppress
ADVISE_MASK

67

RW

ALL

Same as for
ADVISE_ENABLE above

All bits: 0

ALL

Data Type: Bit String (4 byte)


0=disable
1=enable
Advise alert mask. MASK controls
whether an alert is reported. If alert
is enabled the alert condition is
evaluated and the ACTIVE
parameter is updated to reflect if
alert is active or not. If the bit is set
reporting is suppressed. Default is all
bits cleared.

Failed Priority
FAILED_PRI

68

RW

ALL

0 to 15

SETUP

Data Type: Uint8


Failed alert priority

Maintenance Priority
MAINT_PRI

69

RW

ALL

0 to 15

SETUP

Data Type: Uint8


Maintenance alert priority

Advise Priority
ADVISE_PRI

70

RW

ALL

0 to 15

SETUP

Data Type: Uint8


Advise alert priority

Recommended Action
RECOMMENDED_ACTION

71

RO

N/A

0 to 65535

N/A

Data Type: Uint16


Fix for most serious condition

Travel Accumulator
TRAVEL_ACCUM

72

RW

ALL

Write:Anything
Read:Actual

CAL

Data Type: Uint32


Total travel expressed in integer %
terms. Controls AI channel 13.

ALL

Write:Anything
Read:Actual

CAL

Data Type: Uint32


Number of cycle transitions above a
certain threshold of movement.
Controls AI channel 12.

Cycle Count
CYCLE_COUNT

73

RW

-Continued-

99

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

INST_ALERTS_ACTIVE

Electronics Active
ELECT_ACTIVE

Index
Number

RO /
RW

Mode

Range

Protect
Category

Description

74

74.1

RO(1)

ALL

0:Drive Current
1:Drive Signal
2:Memory Failure Pending
3:Static Memory
4:Processor
5:I/O Processor
6:Output Block Timeout
7:Block Set to Defaults

All bits: 0

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Electronics Alert status

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Sensor Alert status

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Environment Alert status

Sensor Active
SENSOR_ACTIVE

74.2

RO(1)

ALL

0:Travel Sensor
1:Port A Pressure Sensor
2:Port B Pressure Sensor
3:Supply Pressure
All bits: 0
Sensor
4:Temperature Sensor
5: Pressure Fallback

Environment Active
ENVIRO_ACTIVE

74.3

RO(1)

ALL

0:Supply Pressure High


1:Supply Pressure Low
2:Temperature High
3:Temperature Low

ALL

0:Travel Deviation
1:Travel High High
2:Travel Low Low
3:Travel High
4:Travel Low

All bits: 0

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Travel Alert status

All bits: 0

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Proximity Alert status.

Travel Active
TRAVEL_ACTIVE

74.4

RO(1)

All bits: 0

Proximity Active
PROX_ACTIVE

74.5

RO(1)

N/A

0:Travel Open
1:Travel Closed
2:Proximity High High
3:Proximity High
4:Proximity Low
5:Proximity Low Low

Travel History Active


TVL_HISTORY_ACTIVE

74.6

RO(1)

ALL

0:Cycle Counter
1:Travel Accumulator

All bits: 0

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Travel History Alert status

Performance Active
PERF_ACTIVE

74.7

RO(1)

ALL

0:Performance Critical
1:Performance Reduced
2:Performance
Information

All bits: 0

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Alert status

ALL

0:High I/P Drive Signal


1:Low I/P Drive Signal
2:High Air Mass Flow
3:Large Travel Deviation
4:Low Supply Pressure
5:High Supply Pressure
6:High Crossover
Pressure
7:Low Crossover
Pressure
8: No Air Mass Flow
Estimate

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic event
status.

PD Event Active
PD_EVENT_ACTIVE

74.8

RO(1)

1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-

100

Initial Value

All bits: 0

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

PD Detail 1 Active
PD_DETAIL1_ACTIVE

PD Detail 2 Active
PD_DETAIL2_ACTIVE

PD Detail 3 Active
PD_DETAIL3_ACTIVE

PD Detail 4 Active
PD_DETAIL4_ACTIVE

Index
Number

74.9

74.10

74.11

74.12

RO /
RW

RO(1)

RO(1)

RO(1)

RO(1)

Mode

ALL

Range
0:I/P Primary Plugged
1:I/P Nozzle Plugged
2:I/P Latched
3:Reserved
4:Relay Jammed
5:Relay Cross Misadj
6:Relay Bias Diaph Leak
7:Relay Port A Diaph
Leak
8:Relay Port B Diaph
Leak
9:Reserved
10:Valve Stuck Low or
Sensor Arm Damage
11:Valve Stuck High or
Sensor Arm Damage
12:Piston Ring Leak
13:Reserved
14:Low Supply Pressure
15:External Leak
16:SOV Trip
17:Air Line Blocked
18:Reserved
19:Reserved
20:Unknown

ALL

Reserved

ALL

0:I/P Primary Plugging


1:I/P Nozzle Plugging
2:I/P Calibration Shift
3:Reserved
4:Relay Cross Misadj
5:Relay Port A Diaph
Leak
6:Relay Port B Diaph
Leak
7:Reserved
8:Piston Ring Leak
9:Reserved
10:Reserved
11:Low Supply Pressure
12:Reserved
13:External Leak
14:Reserved
15:Travel Calibration
Shift
16:Unknown
17:Reserved
18:Reserved

ALL

Reserved

Initial Value

All bits:0

All bits: 0

All bits: 0

All bits: 0

Protect
Category

Description

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Critical
possible cause.

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Detail
status.

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Reduce
possible cause.

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Detail
status

1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-

101

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

PD Detail 5 Active
PD_DETAIL5_ACTIVE

PD Detail 6 Active
PD_DETAIL6_ACTIVE

Shutdown Alerts
SHUTDOWN_ALERTS_ACTIVE

Index
Number

74.13

74.14

74.15

RO /
RW

RO(1)

RO(1)

RO

Mode

ALL

Range

0: Relay Disengaged
1: Insufficient Pressure
Differential
2: Travel Calibration Error
3: Reserved
4: High Supply Pressure*
5: Reserved
6: Near a Travel Cutoff Or
Stop
7:Reserved
8: Spec Sheet Fields
All bits: 0
Incomplete*
9: Sensor Failure*
10: Pressure Control
Active
11: Transducer Block
Mode OOS
12: Not Authorized for PD
13: PD Run Disabled*
14: Trigger Data
Available*

ALL

Reserved

N/A

0:Drive Current
1:Program Memory
2:Static Memory
3:Processor or I/O
Processor
All bits: 0
4:Travel Sensor
5:Port A Pressure Sensor
6: Output Block Timeout
7-31:(Reserved)

1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
-Continued-

102

Initial Value

All bits: 0

Protect
Category

N/A

Description

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Detail
status
*Bits which, when set, will trigger
PERF_ACTIVE bit 2.

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Performance Diagnostic Detail
status

N/A

Data Type: Bit String (4 byte)


0=inactive
1=active
Indicates what caused an Instrument
Shutdown. Bit remains set even if
condition has passed if Shutdown
Recovery is Manual. All bits are
cleared when MODE_BLK.TARGET is
written. Always enabled whenever
the corresponding
SHUTDOWN_TRIGGER is enabled.

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
INST_ALERTS_ENABLE

Electronics Enable
ELECT_ENABLE

Sensor Enable
SENSOR_ENABLE

Environment Enable
ENVIRO_ENABLE

Travel Enable
TRAVEL_ENABLE

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Description

75

75.1

75.2

75.3

75.4

RW

RW

RW

RW

Enabled Bits:
0: Drive Current
1: Drive Signal
2: Program
Memory
3: Static Memory
4: Processor
5: I/O Processor
7: Block Set to
Default

ALL

0:Drive Current
1:Drive Signal
2:Program Memory
3:Static Memory
4:Processor
5:I/O Processor
6:Output Block Timeout
7:Blocks Set to Defaults

SETUP

Data Type: Bit String (4 byte)


0=disable
1=enable
Electronic Alerts Enable

ALL

Enabled Bits:
0:Travel Sensor
1:Port A Pressure
0:Travel Sensor
1:Port A Pressure Sensor Sensor
2:Port B Pressure Sensor 2:Port B Pressure
SETUP
Sensor
3:Supply Pressure
3:Supply Pressure
Sensor
Sensor
4:Temperature Sensor
4:Temperature
Sensor

Data Type: Bit String (4 byte)


0=disable
1=enable
Sensor Alerts Enable

ALL

0:Supply Pressure High


1:Supply Pressure Low
2:Temperature High
3:Temperature Low

Enabled Bits:
0:Supply Pressure
High
2:Temperature
SETUP
High
3:Temperature
Low

Data Type: Bit String (4 byte)


0=disable
1=enable
Environment Alerts Enable

ALL

0:Travel Deviation
1:Travel High High
2:Travel Low Low
3:Travel High
4:Travel Low

Enabled Bits:
0:Travel
Deviation

SETUP

Data Type: Bit String (4 byte)


0=disable
1=enable
Travel Alerts Enable

All bits: 0

SETUP

Data Type: Bit String (4 byte)


0=disable
1=enable
Proximity Alerts Enable

Proximity Enable
PROX_ENABLE

75.5

RW

ALL

0:Travel Open
1:Travel Closed
2:Proximity High High
3:Proximity High
4:Proximity Low
5:Proximity Low Low

Travel History Enable


TVL_HISTORY_ENABLE

75.6

RW

ALL

0:Cycle Counter
1:Travel Accumulator

All bits: 0

SETUP

Data Type: Bit String (4 byte)


0=disable
1=enable
Travel History Alerts Enable

ALL

0:Performance Critical
1:Performance Reduced
2:Performance
Information

Enabled Bits:
0:Performance
Critical
1:Performance
Reduced

SETUP

Data Type: Bit String (4 byte)


0=disable
1=enable
Performance Alerts Enable

Performance Enable
PERF_ENABLE

75.7

RW

-Continued-

103

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
INST_ALERTS_CONFIG

Shutdown Trigger
SHUTDOWN_TRIGGER

Index
Number

RO /
RW

Mode

Range

Protect
Category

Description

76

76.1

RW

ALL

0:Drive Current
1:Program Memory
2:Static Memory
3:Processor or I/O
Processor
All bits: 0
4:Travel Sensor
5:Port A Pressure Sensor
6: Output Block Timeout
7-31:(Reserved)

SETUP

Data Type: Bit String (4 byte)


0=Auto
1=Manual
Recovery action after a shutdown
trigger fail to zero drive above,

SETUP

Data Type: Bit String (4 byte)


0=attempt control,
1=fail to zero drive e.g. OOS mode
Action on specific instrument alerts:

Shutdown Recovery
SHUTDOWN_RECOVERY

76.2

RW

ALL

0:(reserved)
1:Program Memory
2:Static Memory
3:Processor or I/O
Processor
All bits: 0
4:Travel Sensor
5:Port A Pressure Sensor
6: Output Block Timeout
7-31:(Reserved)

Output Blk Timeout


OUTPUT_BLK_TIMEOUT

76.3

RW

ALL

Time > = 0, < = 800


seconds

600 sec

SETUP

Data Type: Float


The maximum time between
updates from the AO or DO block to
the transducer block setpoint.

Drive Current Alert Point


DRIVE_CURRENT_ALRT_PT

76.4

RW

ALL

> = 5, < = 100

25%

SETUP

Data Type: Float


(percent different) drive signal not
reaching I/P accurately.

Drive Current Alert Time


DRIVE_CURRENT_TIME

76.5

RW

ALL

= 0.25, < = 120 seconds

5 sec

SETUP

Data Type: Float


(percent different) drive signal not
reaching I/P accurately.

Temperature Hi Alert Point


TEMP_HI_ALRT_PT

76.6

RW

ALL

> -76 F, < 257 F

186 deg F

SETUP

Data Type: Float


Temperature HI Limits

Temperature Lo Alert Point


TEMP_LO_ALRT_PT

76.7

RW

ALL

> -76 F, < 257 F

-63 deg F

SETUP

Data Type: Float


Temperature LO Limits

Supply Pressure Hi Alert Point


SUP_PRES_HI_ALRT_PT

76.8

RW

ALL

> = 0, < = 150

145 psig

SETUP

Data Type: Float


Maximum supply pressure

Supply Pressure Lo Alert Point


SUP_PRES_LO_ALRT_PT

76.9

RW

ALL

> = 0, < = 150

15 psig

SETUP

Data Type: Float


Minimum supply pressure

INST_ALERTS_CONFIG2

77

Travel Deviation Alert Point


TVL_DEV_ALRT_PT

77.1

RW

ALL

> 0%, <= 125%

5%

SETUP

Data Type: Float


Alerts when difference between sp
and pv is too large for too long.

Travel Deviation Time


TVL_DEV_TIME

77.2

RW

ALL

> = 0, < = 120 seconds

10 sec

SETUP

Data Type: Float

Travel Deviation Deadband


TVL_DEV_DB

77.3

RW

ALL

> = 0%, < = 100%

2%

SETUP

Data Type: Float

Travel Accumulator Alert Point


TVL_ACCUM_ALRT_PT

77.4

RW

ALL

>=0

1,000,000

SETUP

Data Type: Uint32


Alerts when accumulated travel is
too much

Travel Accumulator Deadband


TVL_ACCUM_DB

77.5

RW

ALL

0 - 100%

1%

SETUP

Data Type: Float


Deadband

Cycle Count Alert Point


CYCLE_COUNT_ALRT_PT

77.6

RW

ALL

>=0

1,000,000

SETUP

Alerts when number of cycles is too


large.

Cycle Count Deadband


CYCLE_COUNT_DB

77.7

RW

ALL

0 - 100%

1%

SETUP

Data Type: Float


Deadband

-Continued-

104

Initial Value

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Description

Travel Open Alert Point


TVL_OPEN_ALRT_PT

77.8

RW

ALL

-25% to 125%

99.5%

SETUP

Data Type: Float


Alert when valve is open. Control DI
channel 24 regardless of alert enable
state.

Travel Open Deadband


TVL_OPEN_DB

77.9

RW

ALL

> = 0%, < =100%

1%

SETUP

Data Type: Float


Deadband

Travel Closed Alert Point


TVL_CLOSED_ALRT_PT

77.10

RW

ALL

-25% to 125%

0.5%

SETUP

Data Type: Float


Alerts when valve closed. Controls DI
channel 25 regardless of alert enable
state.

Travel Closed Deadband


TVL_CLOSED_DB

77.11

RW

ALL

> = 0%, < = 100%

1%

SETUP

Data Type: Float


Deadband

Travel Lo Lo Alert Point


TVL_LO_LO_ALRT_PT

77.12

RW

ALL

-25% to 125%

-25%

SETUP

Data Type: Float


Alert when valve position is less than
alert point. Controls DI channels 26
& 30 regardless of alert enable state.

Travel Lo Lo Deadband
TVL_LO_LO_DB

77.13

RW

ALL

> = 0%, < = 100%

5%

SETUP

Data Type: Float


Deadband

Travel Lo Alert Point


TVL_LO_ALRT_PT

77.14

RW

ALL

-25% to 125%

-25%

SETUP

Data Type: Float


Alert when valve position is less than
alert point. Controls DI channels 27
& 31 regardless of alert enable state.

Travel Lo Deadband
TVL_LO_DB

77.15

RW

ALL

> = 0%, < = 100%

5%

SETUP

Data Type: Float


Deadband

Travel Hi Alert Point


TVL_HI_ALRT_PT

77.16

RW

ALL

-25% to 125%

125%

SETUP

Data Type: Float


Alert when valve position is less than
alert point. Controls DI channels 28
& 32 regardless of alert enable state.

Travel Hi Deadband
TVL_HI_DB

77.17

RW

ALL

> = 0%, < = 100%

5%

SETUP

Data Type: Float


Deadband

Travel Hi Hi Alert Point


TVL_HI_HI_ALRT_PT

77.18

RW

ALL

-25% to 125%

125%

SETUP

Data Type: Float


Alert when valve position is less than
alert point. Controls DI channels 29
& 33 regardless of alert enable state.

Travel Hi Hi Deadband
TVL_HI_HI_DB

77.19

RW

ALL

> = 0%, < = 100%

5%

SETUP

Data Type: Float


Deadband

-Continued-

105

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
RO /
Number RW
78
RO

Mode
N/A

Range

Initial Value

Protect
Category

0:
All bits: 0
2: Integrator Limited Low
3: Integrator Limited
High
4: Travel Sensor Span
Error
5: MLFB Error
7: Travel Sensor High
Error
8: Travel Sensor Low Error
9: Pressure Sensor B
10: Pressure Sensor A
11: Supply Pressure
Sensor
13: IOP Failure
14: Drive Current
15: Simulate Jumper ON

Description

Self Test Status


SELFTEST_STATUS

Data Type: Bit String (2 byte)


0=inactive
1=active
Indicates the status of the
instrument self test.
Integrator Limited Low: Indicates
the integrator reached its limit and
cannot move the valve any further.
High valve friction may cause this
situation.
Integrator Limited High:
Indicates the integrator reached its
limit and cannot move the valve any
further. High valve friction may
cause this situation.
Travel Sensor Span Error:
Indicates that span between the
endpoints of travel are not far
enough apart. This error is reported
during automatic calibration.
MLFB Error: Indicates that the Minor
Loop Feedback sensor gave a
nonvalid value during automatic
calibration.
Travel Sensor High Error:
Indicates the travel sensor has
reported a travel position that is
significantly above the normal
operating range, and has failed.
Travel Sensor Low Error: Indicates
the travel sensor has reported a
travel position that is significantly
below the normal operating range,
and has failed.
Pressure B Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
Pressure A Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
Supply Sensor Failure:
Indicates the pressure sensor is
reporting a pressure that is
significantly outside of the normal
operating pressure, and has failed.
IOP Failure: Indicates the I/O
processor has failed.
Drive Current: Indicates that the
Drive Current has exceeded the
Drive Current Alert Point for more
than the Drive Current Alert Time.
Simulate Jumper ON: Indicates the
simulate jumper is connected to the
DVC6200f between the two AUX
terminals.

Health Index
HEALTH_INDEX

79

RO

N/A

Reserved A
RESERVED_A

80

RW

ALL

0 - 100

-Continued-

106

100

N/A

Data Type: Uint8


Represents overall health of device.
100 is perfect, 0 is completely bad.
Settings for DVC6200f will range
from 10 to 100.

N/A

SETUP

Data Type: Array, 118 x Unit8


Reserved

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Reserved AI
RESERVED_AI
Upgrade Progress
UPGRADE_PROGRESS
SPEC_SHEET_VALVE

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Description

81

RW

ALL

SETUP

Data Type: Uint16


Reserved

82

RO

N/A

N/A

Data Type: Enum (Uint8)


Not used by the DVC6200f

83

Valve Size
VALVE_SIZE

83.1

RW

ALL

NULL

ALL

Data Type: Visible String

Valve Class
VALVE_CLASS

83.2

RW

ALL

NULL

ALL

Data Type: Visible String

Rated Travel
RATEDTRAVEL

83.3

RW

ALL

0.00

ALL

Data Type: Float

Actual Travel
ACTUAL_TRAVEL

83.4

RW

ALL

0.00

ALL

Data Type: Float

Shaft Stem Diameter


SHAFT_STEM_DIA

83.5

RW

ALL

0.00

ALL

Data Type: Float

Packing Type
PACKING_TYPE

83.6

RW

ALL

NULL

ALL

Data Type: Visible String

Inlet Pressure
INLET_PRESSURE

83.7

RW

ALL

0.00

ALL

Data Type: Float

Outlet Pressure
OUTLET_PRESSURE

83.8

RW

ALL

0.00

ALL

Data Type: Float

RW

ALL

NULL

ALL

Data Type: Visible String

1= I

ALL

Data Type: Enum (Uint8)

SPEC_SHEET_TRIM
Seat Type
SEAT_TYPE

84
84.1

Leak Class
LEAK_CLASS

84.2

RW

ALL

Port Diameter
PORT_DIAMETER

84.3

RW

ALL

ANSI Seat Leakage


Classification
1: I
2: II
3: III
4: IV
5: V
6: VI
7: BFW
8: STD AIR
9: BFW II
10: BFW III
11: BFW IV
12: BFW V
13: BFW VI
14: 1/10th of IV
15: Bubble Tight

0.00

ALL

Data Type: Float

ALL

1=balanced
2=unbalanced

ALL

Data Type: Enum (Uint8)

RW

ALL

1=up
2=down

ALL

Data Type: Enum (Uint8)

84.6

RW

ALL

1=open
2=close

ALL

Data Type: Enum (Uint8)

Flow Tends To
FLOW_TENDS_TO

84.7

RW

ALL

1=open
2=close

ALL

Data Type: Enum (Uint8)

Unbalanced Area
UNBALANCED_AREA

84.8

RW

ALL

0.00

ALL

Data Type: Float

Trim Style 1
TRIM_STYLE_1

84.9

RW

ALL

NULL

ALL

Data Type: Visible String

Trim Style 2
TRIM_STYLE_2

84.10

RW

ALL

NULL

ALL

Data Type: Visible String

Port Type
PORT_TYPE

84.4

RW

Flow Direction
FLOWDIRECTION

84.5

Push Down To
PUSH_DOWN_TO

-Continued-

107

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
SPEC_SHEET_ACT

Index
Number

RO /
RW

Mode

Range

Protect
Category

Description

85

Actuator Size
ACTUATOR SIZE

85.1

RW

ALL

NULL

ALL

Data Type: Visible String

Effective Area
EFFECTIVE AREA

85.2

RW

ALL

0.00

ALL

Data Type: Float

Air
AIR

85.3

RW

ALL

ALL

Data Type: Enum (Uint8)

Lower Bench Set


LOWER_BENCH_SET

85.4

RW

ALL

0.00

ALL

Data Type: Float

Upper Bench Set


UPPER_BENCH_SET

85.5

RW

ALL

0.00

ALL

Data Type: Float

Nominal Supply Pressure


NOMINAL_SUPPLY_PRESSURE

85.6

RW

ALL

0.00

ALL

Data Type: Float

Spring Rate
SPRING_RATE

85.7

RW

ALL

0.00

ALL

Data Type: Float

Stroking Time Open


STROKING_TIME_OPEN

85.8

RW

ALL

0.00

ALL

Data Type: Float


Seconds

Stroking Time Close


STROKING_TIME_CLOSE

85.9

RW

ALL

0.00

ALL

Data Type: Float


Seconds

Lever Style
LEVER_STYLE

85.10

RW

ALL

ALL

Data Type: Enum (Uint8)

Lever Arm Length


MOMENT_ARM

85.11

RW

ALL

0.00

ALL

Data Type: Float

DEVICE_RECORD

1=open
2=close

1=Pivot Point
2=Rack & Pinion

These parameters can only reset


through VL/DD.

86

Temperature Maximum
TEMP_MAX

86.1

RO

N/A

-9999.99

N/A

Data Type: Float


Highest temperature recorded

Temperature Maximum Time


TEMP_MAX_TIME

86.2

RO

N/A

Zero time

N/A

Data Type: Time Value

Temperature Minimum
TEMP_MIN

86.3

RO

N/A

9999.99

N/A

Data Type: Float


Lowest temperature recorded

Temperature Minimum Time


TEMP_MIN_TIME

86.4

RO

N/A

Zero time

N/A

Data Type: Time Value

Supply Pressure Maximum


SUPP_PRESS_MAX

86.5

RO

N/A

0.0

N/A

Data Type: Float


Highest supply pressure recorded

Supply Pressure Maximum Time


SUPP_PRESS_MAX_TIME

86.6

RO

N/A

Zero time

N/A

Data Type: Time Value

Supply Pressure Minimum


SUPP_PRESS_MIN

86.7

RO

N/A

9999.99

N/A

Data Type: Float


Lowest supply pressure recorded

Supply Pressure Minimum Time


SUPP_PRESS_MIN_TIME

86.8

RO

N/A

Zero time

N/A

Data Type: Time Value

Comm Error Count


COMM_ERROR_COUNT

86.9

RW

N/A

SETUP

Not used by the DVC6200f

NONE

Data Type: Enum


Write lock enable/disable. If setting
is at or above a parameters
protection level then that parameter
is readonly.

Protection
PROTECTION

87

RW

ALL

1=None
2=Calibration
3=Setup & Calibration
4=All
-Continued-

108

Initial Value

2=Calibration

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
PERF_DIAG

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Description

88

PD Run
PD_COMMAND

88.1

RW

AUTO
MAN

1=PD On
2=PD Off

NONE

Data Type: Enum


Controls whether PD will run or not.

PD Status
PD_STATUS

88.2

RO

ALL

1=Not Running
2=Running

NONE

Data Type: Enum


Status of performance diagnostics.

PD Configuration
PD_CONFIG

88.3

RW

ALL

NONE

Data Type: Bit String


Bit string for configuring PD setup
and options.

PD Extra
PD_EXTRA

88.4

RW

ALL

NONE

Data Type: Uint32


Extra 32 bit integer for sending
values to PD.

Temperature Units
TEMPERATURE_UNITS

89

RW

ALL

C=1001
F=1002

SETUP

Data Type: Enum (Uint8)

kPa

SETUP

Data Type: Enum (Uint8)

1=PD On

Pressure Units
PRESSURE_UNITS

90

RW

ALL

kPa=1133
bar=1137
psig=1143
inHg=1155
inH2O=1146
Kg/cm2=1145

Travel Units
TVL_UNITS

91

RW

ALL

cm=1012
mm=1013
in=1019
deg=1005

mm

SETUP

Data Type: Enum (Uint8)


Travel units for spec sheet
ACTUAL_TRAVEL and RATEDTRAVEL
only.

Length Units
LENGTH_UNITS

92

RW

ALL

cm=1012
mm=1013
in=1019

mm

SETUP

Data Type: Enum (Uint8)


Not used for spec sheet
ACTUAL_TRAVEL OR RATEDTRAVEL

Area Units
AREA_UNITS

93

RW

ALL

cm2=1025
mm2=1027
in2=1030

cm2

SETUP

Data Type: Enum (Uint8)

Spring Rate Units


SPRING_RATE_UNITS

94

RW

ALL

N/m=1165
lb/in=1596

N/m

SETUP

Data Type: Enum (Uint8)

MAI_CHANNEL_MAP

95

MAI Channel 1
MAI_CHANNEL_1

95.1

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 2
MAI_CHANNEL_2

95.2

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 3
MAI_CHANNEL_3

95.3

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 4
MAI_CHANNEL_4

95.4

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 5
MAI_CHANNEL_5

95.5

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 6
MAI_CHANNEL_6

95.6

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 7
MAI_CHANNEL_7

95.7

RW

MAN,
OOS

1 through 13

SETUP

MAI Channel 8
MAI_CHANNEL_8

95.8

RW

MAN,
OOS

1 through 13

SETUP

RW

MAN,
OOS

1: AO Block
2: DO Block

Output Block Selection


OUTBLOCK_SEL

PlantWeb Alerts Set PV Status


PWA_SET_STATUS

96

97

RW

MAN,
OOS

1: No
2: Yes

1: AO Block

1: No

Data Type:Uint16 This defines


which transducer block channels will
be sent to each of the 8 MAI
channels. No scaling or other
conversion will be done. Values will
be sent in the currently defined
units. If set to 0, then no output to
MAI (status will be set to BAD).
1=FINAL_VALUE
2=TRAVEL_TARGET
3=FINAL_POSITION_VALUE
4=TRAVEL
5=SUPPLY_PRESS
6=ACT_PRESS_A
7=ACT_PRESS_B
8=ACT_PRESS_DIFF
9=DRIVE_SIGNAL
10=TRAVEL_DEVIATION
11=TEMPERATURE
12=CYCLE_COUNT
13=TRAVEL_ACCUM

SETUP

Data Type: Enum (Uint8)


Controls which output block (AO or
DO) the transducer block will
respond to.

SETUP

Data Type: Enum (Uint8)


Controls whether the status of the
PV fed back to the output block from
the transducer block will be affected
by an active PlantWeb alert.

-Continued-

109

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 414. Transducer Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Range

Initial Value

Protect
Category

Bit 0: Travel feedback


sensor detected
Bit 1: Output Block
Scheduled
Bit 2: Trigger Capturing
Bit 3: Output Block in
Normal Mode
Bit 4: Write Lock is on
Bit 5: Resource Block in
Auto Mode

Description

Block Information
BLOCK_INFO

98

RO

Reserved B
RESERVED_B

99

RW

Data Type: Bit String (4 bytes)

Travel Always
TRAVEL_ALWAYS

100

RO

Data Type: DS-65

Data Type: Bit String (2 bytes)

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 415. Transducer Block, View 1
Index Number
1

Parameter
ST_REV

Table 416. Transducer Block, View 2


Index Number
ST_REV
TRANSDUCER_TYPE

5.1

MODE_BLK.TARGET

10

5.2

MODE_BLK.ACTUAL

14.1

FINAL_VALUE_RANGE.EU_100

5.3

MODE_BLK.PERMITTED

14.2

FINAL_VALUE_RANGE.EU_0

5.4

MODE_BLK.NORMAL

14.3

FINAL_VALUE_RANGE.UNITS_INDEX

BLOCK_ERR

14.4

FINAL_VALUE_RANGE.DECIMAL

10

TRANSDUCER_TYPE

11

XD_ERROR

13.1

FINAL_VALUE.STATUS

13.2

FINAL_VALUE.VALUE

17.1

FINAL_POSITION_VALUE.STATUS

17.2

FINAL_POSITION_VALUE.VALUE

32.1

SETPOINT_D.STATUS

32.2

SETPOINT_D.VALUE

15

FINAL_VALUE_CUTOFF_HI

16

FINAL_VALUE_CUTOFF_LO

18

SERVO_GAIN

19

SERVO_RESET

20

SERVO_RATE

21

ACT_FAIL_ACTION

40.1

GRANT_DENY.GRANT

40.2

GRANT_DENY.DENY

50

110

Parameter

INPUT_CHAR

Instruction Manual

Detailed SetupTransducer Block

D103412X012

August 2012

Note
Because individual views are limited in size, View Lists 3 and 4 have multiple parts.

Table 417. Transducer Block, View 3.1


Index Number
1

Parameter
ST_REV

Table 418. Transducer Block, View 3.2


Index Number
1

Parameter
ST_REV

5.1

MODE_BLOCK.TARGET

74.1

INST_ALERTS_ACTIVE.ELECT_ACTIVE

5.2

MODE_BLOCK.ACTUAL

74.2

INST_ALERTS_ACTIVE.SENSOR_ACTIVE

5.3

MODE_BLOCK.PERMITTED

74.3

INST_ALERTS_ACTIVE.ENVIRO_ACTIVE

5.4

MODE_BLOCK.NORMAL

74.4

INST_ALERTS_ACTIVE.TRAVEL_ACTIVE

BLOCK_ERR

74.5

INST_ALERTS_ACTIVE.PROX_ACTIVE

10

TRANSDUCER_TYPE

74.6

INST_ALERTS_ACTIVE.TVL_HISTORY_ACTIVE

11

XD_ERROR

74.7

INST_ALERTS_ACTIVE.PERF_ACTIVE

13.1

FINAL_VALUE.STATUS

74.8

INST_ALERTS_ACTIVE.PD_EVENT_ACTIVE

13.2

FINAL_VALUE.VALUE

74.9

INST_ALERTS_ACTIVE.PD_DETAIL1_ACTIVE

17.1

FINAL_POSITION_VALUE.STATUS

74.10

INST_ALERTS_ACTIVE.PD_DETAIL2_ACTIVE

17.2

FINAL_POSITION_VALUE.VALUE

74.11

INST_ALERTS_ACTIVE.PD_DETAIL3_ACTIVE

32.1

SETPOINT_D.STATUS

74.12

INST_ALERTS_ACTIVE.PD_DETAIL4_ACTIVE

32.2

SETPOINT_D.VALUE

74.13

INST_ALERTS_ACTIVE.PD_DETAIL5_ACTIVE

35.1

SUPPLY_PRESSURE.STATUS

78

SELFTEST_STATUS

35.2

SUPPLY_PRESSURE.VALUE

79

HEALTH_INDEX

36.1

PRESSURE_A.STATUS

86.1

DEVICE_RECORD.TEMP_MAX

36.2

PRESSURE_A.VALUE

86.2

DEVICE_RECORD.TEMP_MAX_TIME

37.1

PRESSURE_B.STATUS

86.3

DEVICE_RECORD.TEMP_MIN

37.2

PRESSURE_B.VALUE

86.4

DEVICE_RECORD.TEMP_MIN_TIME

38.1

PRESSURE_DIFF.STATUS

86.5

DEVICE_RECORD.SUPP_PRESS_MAX

38.2

PRESSURE_DIFF.VALUE

86.6

DEVICE_RECORD.SUPP_PRESS_MAX_TIME

48

TEMPERATURE

86.7

DEVICE_RECORD.SUPP_PRESS_MIN

49

TRAVEL_TARGET

86.8

DEVICE_RECORD.SUPP_PRESS_MIN_TIME

52

TRAVEL_DEVIATION

53

DRIVE_SIGNAL

54

DRIVE_CURRENT

Table 419. Transducer Block, View 4.1

55

MLFB

Index Number

59

FAILED_ACTIVE

ST_REV

60

MAINT_ACTIVE

STRATEGY

61

ADVISE_ACTIVE

ALERT_KEY

71

RECOMMEND_ACTION

10

TRANSDUCER_TYPE

72

TRAVEL_ACCUM

22

ACT_MAN_ID

73

CYCLE_COUNT

23

ACT_MODEL_NUM

75.1

INST_ALERTS_ENABLE.ELECT_ENABLE

24

ACT_SN

75.2

INST_ALERTS_ENABLE.SENSOR_ENABLE

25

VALVE_MAN_ID

75.3

INST_ALERTS_ENABLE.ENVIRO_ENABLE

26

VALVE_MODEL_NUM

75.4

INST_ALERTS_ENABLE.TRAVEL_ENABLE

75.5

INST_ALERTS_ENABLE.PROX_ENABLE

75.6

INST_ALERTS_ENABLE.TVL_HISTORY_ENABLE

75.7

INST_ALERTS_ENABLE.PERF_ENABLE

Parameter

111

Instruction Manual

Detailed SetupTransducer Block


August 2012

D103412X012

Table 420. Transducer Block, View 4.2

Table 421. Transducer Block, View 4.3 (continued)

Index Number

Index Number

Parameter
ST_REV

67

ADVISE_MASK

27

VALVE_SN

68

FAILED_PRI

28

VALVE_TYPE

69

MAINT_PRI

29

XD_CAL_LOC

70

ADVISE_PRI

30

XD_CAL_DATE

31

XD_CAL_WHO

89

TEMPERATURE_UNITS

90

PRESSURE_UNITS

91

TVL_UNITS

92

LENGTH_UNITS

93

AREA_UNITS

94

SPRING_RATE_UNITS

Table 422. Transducer Block, View 4.4

Index Number

Parameter

ST_REV

39

PWA_SIMULATE

Index Number
1

Table 421. Transducer Block, View 4.3

41.1

TVL_PRESS_CONTROL.TVL_PRESS_SELECT

41.2

TVL_PRESS_CONTROL.TVL_PRESS_STATE

42.1

BASIC_SETUP.ACTUATOR_STYLE

42.2

BASIC_SETUP.ZERO_PWR_COND

42.3

BASIC_SETUP.TRAVEL_SEN_MOTION

42.4

BASIC_SETUP.FEEDBACK_CONN

42.5

BASIC_SETUP.RELAY_TYPE

42.6

BASIC_SETUP.MAX_SUPP_PRESS

42.7

BASIC_SETUP.PRESS_RANGE_HI

42.8

BASIC_SETUP.PRESS_RANGE_LO

Parameter
ST_REV

76.1

INST_ALERTS_CONFIG.SHUTDOWN_TRIGGER

76.2

INST_ALERTS_CONFIG.SHUTDOWN_RECOVERY

76.3

INST_ALERTS_CONFIG.OUTPUT_BLK_TIMEOUT

76.4

INST_ALERTS_CONFIG.DRIVE_CURRENT_ALRT_PT

76.5

INST_ALERTS_CONFIG.DRIVE_CURRENT_TIME

76.6

INST_ALERTS_CONFIG.TEMP_HI_ALRT_PT

76.7

INST_ALERTS_CONFIG.TEMP_LO_ALRT_PT

76.8

INST_ALERTS_CONFIG.SUP_PRES_HI_ALRT_PT

76.9

INST_ALERTS_CONFIG.SUP_PRES_LO_ALRT_PT

77.1

INST_ALERTS_CONFIG2.TVL_DEV_ALRT_PT

77.2

INST_ALERTS_CONFIG2.TVL_DEV_TIME

77.3

INST_ALERTS_CONFIG2.TVL_DEV_DB

77.4

INST_ALERTS_CONFIG2.TVL_ACCUM_ALRT_PT

77.5

INST_ALERTS_CONFIG2.TVL_ACCUM_DB

77.6

INST_ALERTS_CONFIG2.CYCLE_COUNT_ALRT_PT

77.7

INST_ALERTS_CONFIG2.CYCLE_COUNT_DB

77.8

INST_ALERTS_CONFIG2.TVL_OPEN_ALRT_PT

77.9

INST_ALERTS_CONFIG2.TVL_OPEN_DB

77.10

INST_ALERTS_CONFIG2.TVL_CLOSED_ALRT_PT

77.11

INST_ALERTS_CONFIG2.TVL_CLOSED_DB

77.12

INST_ALERTS_CONFIG2.TVL_LO_LO_ALRT_PT

77.13

INST_ALERTS_CONFIG2.TVL_LO_LO_DB

77.14

INST_ALERTS_CONFIG2.TVL_LO_ALRT_PT

77.15

INST_ALERTS_CONFIG2.TVL_LO_DB

77.16

INST_ALERTS_CONFIG2.TVL_HI_ALRT_PT

77.17

INST_ALERTS_CONFIG2.TVL_HI_DB

77.18

INST_ALERTS_CONFIG2.TVL_HI_HI_ALRT_PT

77.19

INST_ALERTS_CONFIG2.TVL_HI_HI_DB

42.9

BASIC_SETUP.TVL_CAL_TRIGGER

42.10

BASIC_SETUP.TVL_TUNING_SET

42.11

BASIC_SETUP.PRESS_TUNING_SET

44.1

TRAVEL_TUNE.TVL_INTEG_ENABLE

44.2

TRAVEL_TUNE.TVL_INTEG_LIM_HI

44.3

TRAVEL_TUNE.TVL_INTEG_LIM_LO

44.4

TRAVEL_TUNE.TVL_INTEG_DEADZ

44.5

TRAVEL_TUNE.TVL_MLFB_GAIN

47.1

PRESS_TUNE.PRESS_CUTOFF_HI

47.2

PRESS_TUNE.PRESS_CUTOFF_LO

47.3

PRESS_TUNE.PRESS_PROP_GAIN

47.4

PRESS_TUNE.PRESS_INTEG_GAIN

47.5

PRESS_TUNE.PRESS_RATE_GAIN

Table 423. Transducer Block View, 4.5

47.6

PRESS_TUNE.PRESS_INTEG_DEADZ

Index Number

47.7

PRESS_TUNE.PRESS_INTEG_HI_LIM

47.8

PRESS_TUNE.PRESS_INTEG_LO_LIM

95.1

MAI_CHANNEL_1

47.9

PRESS_TUNE.PRESS_INTEG_IC_HI

95.2

MAI_CHANNEL_2

47.10

PRESS_TUNE.PRESS_INTEG_IC_LO

95.3

MAI_CHANNEL_3

47.11

PRESS_TUNE.PRESS_MLFB_GAIN

95.4

MAI_CHANNEL_4

62

FAILED_ENABLE

95.5

MAI_CHANNEL_5

63

MAINT_ENABLE

95.6

MAI_CHANNEL_6

64

ADVISE_ENABLE

95.7

MAI_CHANNEL_7

65

FAILED_MASK

95.8

MAI_CHANNEL_8

66

MAINT_MASK

96

OUTBLOCK_SEL

97

PWA_SET_STATUS

-continued-

112

Parameter

82

UPGRADE_PROGRESS

87

PROTECTION

Parameter
ST_REV

Instruction Manual

Detailed SetupAO Function Block

D103412X012

August 2012

Analog Output Function Block


Overview
The Analog Output (AO) function block (figure 46) assigns an output value to a field device through a specified I/O
channel. The block supports mode control, signal status calculation, and simulation. Figure 47 illustrates the internal
components of the AO function block, and table 425 lists the definitions of the block parameters. The digital valve
controller measures and uses actual valve position for READBACK [16].
Figure 46. Analog Output (AO) Function Block

BKCALOUT
CAS IN

AO

OUT

READBACK

CASIN = The remote setpoint value from another


function block.
BKCALOUT = The value and status required by the
BKCALIN input of another block to prevent reset
windup and to provide bumpless transfer to closed
loop control.
OUT = The block output and status.
B27161

READBACK = Actual valve position.

Note
The AO block actual mode will not move to Auto unless:
Resource Block actual mode is Auto, and
AO SHED_OPT [27] is set to a nonzero value.

Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain out of service and the block cannot be scheduled if the block has not
been licensed. Contact your Emerson Process Management sales office to upgrade product licensing.

Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain in IMAN and the block Readback status will be Bad - Not Connected if
the Output Block Selection is set incorrectly. From the transducer block method Outblock Selection, select the desired output
block, see page 69.

113

Instruction Manual

Detailed SetupAO Function Block


August 2012

D103412X012

Figure 47. Analog Output Function Block Schematic


RCASOUT
RCASIN
Operator
Setpoint

CASIN

SP
HI/LO
Limit

BKCALOUT

READBACK
PV

SPRATEDN
SPRATEUP

Convert
and Status
Calculation

SP
Rate
Limit

OUT

SPWRK
SPLOWLIM
SPHILIM

PVSCALE
IOOPTS

MODE

Shed
Mode
Access
Analog
Input

B2717

Position
Feedback

Access
Analog
Output

CHANNEL

Analog
Output

Modes
The Analog Output function block supports the following modes:
Manual (Man)You can manually set the output to the I/O channel through the OUT [9] attribute. This mode is used
primarily for maintenance, calibration and diagnostics.
Automatic (Auto)The block output (OUT [9]) reflects the target operating point specified by the setpoint (SP [8])
attribute. Typically the setpoint is set by the user.
Cascade (Cas)The SP [8] attribute is set by another function block through a connection to CAS_IN [17]. The SP [8]
value is used to set the OUT [9] attribute automatically. This is the most frequently used mode in the digital valve
controller.

Note
The transducer block must be in Auto for the mode to go to AUTO, CAS, MAN, or RCAS.

RemoteCascade (RCas)The SP [8] is set by a host computer by writing to the RCAS_IN [28] parameter. The SP [8]
value is used to set the OUT [9] attribute automatically.

114

Instruction Manual

Detailed SetupAO Function Block

D103412X012

August 2012

Out of Service (OOS)The block is not processed. The output channel is maintained at the last value and the status
of OUT [9] is set to Bad: Out of Service. The BLOCK_ERR [6] attribute shows Out of Service.
Initialization Manual (Iman)The path to the output hardware is broken and the AO block output will remain at the
last position. This means the transducer block mode is Out of Service or Manual or configured to respond to the DO
block.
Local Override (LO)The output of the block is not responding to inputs because the fault state action is active. OUT
[9] freezes or goes to value per IO_OPTS [14].
The target mode of the block may be restricted to one or more of the following modes: Man, Auto, Cas, RCas, or OOS.

Mode Handling
Shed OptionsRCAS Mode Only
Automatically changing through the permitted modes when starting from a remote mode, fall from (or shed) or climb
to a remote mode is determined by the parameter SHED_OPT [27]. A block climbs and sheds through the same path.
For example, if SHED_OPT [27] specifies that a block should shed to Auto, then, if the block target mode is set to RCas,
the block goes through Auto on the way to RCas.
When the block is in Cas mode and the CAS_IN [17] input goes bad, the block sheds mode to the next lower permitted
mode.
You can configure the shed option as follows:

Shed With Return Options


Remote cascade connection failure shifts actual mode but keeps trying to restore remote cascade (in other words, the
remote cascade target mode stays in effect).

Note
During Shed with Return Options, the actual mode is changed, while the target mode stays the same.

NormalOn failure of a remote cascade connection the block attempts to attain the highest permitted nonremote
mode until remote cascade is restored. Cas is the highest permitted nonremote mode and Auto is is the next
permitted nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the previous target mode before it was changed to RCAS or ROUT. On
failure of a remote cascade connection the block attempts to attain the retained target mode.
AutoOn failure of a remote cascade connection the block attempts to attain Auto, if permitted, until remote cascade
is restored.
ManOn failure of a remote cascade connection the block sheds to Man until a remote cascade connection is
restored.

Shed With No Return Options


Note
During Shed with No Return Options, the target mode is changed, while the actual mode stays the same.

115

Detailed SetupAO Function Block

Instruction Manual

August 2012

D103412X012

For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no
attempt to restore the connection following failure. The behavior on change to the remote cascade target mode is
identical to that for Shed With Return Options.
NormalOn failure of a remote cascade connection the block sets the target mode to the highest permitted
nonremote mode. Cas is the highest permitted nonremote mode and Auto is is the next highest permitted
nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the previous target mode before it was changed to RCAS or ROUT. On
failure of a remote cascade connection the block sets the target mode to the retained target mode.
AutoOn failure of a remote cascade connection, the block sets the target mode to Auto, if permitted.
ManOn failure of remote cascade connection, the block sets the target mode to Man, if permitted.
The user may configure SHED_OPT [27] so that it calls for a target mode that is not permitted. When doing this, the
mode logic uses the following rules as applied by the remote logic:
Shed logic never results in a nonpermitted target mode.
Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted.

Status Handling
Output or readback fault detection is reflected in the status of PV [7], OUT [9], and BKCAL_OUT [25]. A limited SP [8]
condition is reflected in the BKCAL_OUT [25] status. When simulation is enabled through the SIMULATE [10] attribute,
you can set the value and status for PV [7] and READBACK [16].
When the block is in Cas mode and the CAS_IN [17] input goes bad, the block sheds mode to the next permitted
mode.

Setting the Output


To set the output for the AO block, you must first set the mode to define the manner in which the block determines its
setpoint. In Manual mode the value of the output attribute (OUT [9]) must be set manually by the user, and is
independent of the setpoint. In Automatic mode, OUT [9] is set automatically based on the value specified by the set
point (SP [8]) in engineering units and the I/O Options attribute. In addition, you can limit the SP [8] value and the rate
at which a change in the SP [8] is passed to OUT [9].
In Cascade mode, the cascade input connection (CAS_IN [17]) is used to update the SP [8]. The back calculation
output (BKCAL_OUT [25]) is wired to the back calculation input (BKCAL_IN [27]) of the upstream block that provides
CAS_IN [17]. This provides bumpless transfer on mode changes and windup protection in the upstream block.

Note
You must wire BKCAL_OUT [25] to BKCAL_IN [27] of the upstream block that provides CAS_IN [17]. Otherwise, the AO will not
initialize properly, and the setpoint at CAS_IN [17] will not be passed to OUT [9].

An analog readback value, such as valve position, is shown by the process value (PV [7]) attribute in engineering units.
To support testing, you can enable simulation, which allows you to manually set the channel feedback. There is no
alarm detection in the AO function block.

116

Instruction Manual
D103412X012

Detailed SetupAO Function Block


August 2012

To select the manner of processing the SP and the channel output value configure the setpoint limiting options, the
tracking options, and the conversion and status calculations.

Output Block PV Status


The Output Block PV Status is determined by the value of the PlantWeb Alerts Set PV Status parameter in the
transducer block (PWA_SET_STATUS [97]), the Transducer Block mode, and enabled Active PlantWeb alarms. Refer to
table 411.

Set Point Selection and Limiting


To select the source of the SP [8] value use the MODE [5] attribute. In Automatic (Auto) mode, the local,
manuallyentered SP [8] is used. In Cascade (Cas) mode, the SP [8] comes from another block through the CAS_IN [17]
input connector. In RemoteCascade (RCas) mode, the SP [8] comes from a host computer that writes to RCAS_IN [28].
The range and units of the SP [8] are defined by the PV_SCALE [11] attribute.
In Manual (Man) mode the SP [8] automatically tracks the PV [7] value when you select the SPPV Track in Man I/O
option in IO_OPTS [14]. This option can be used to minimize valve movement when the AO block is transitioned from
Manual mode to Auto. You can disable this option in OOS mode only.
The SP [8] value is limited to the range defined by the setpoint high limit attribute (SP_HI_LIM [20]) and the setpoint
low limit attribute (SP_LO_LIM [21]).
In Auto mode, the rate at which a change in the SP [8] is passed to OUT [9] is limited by the values of the setpoint
upward rate limit attribute (SP_RATE_UP [19]) and the setpoint downward rate limit attribute (SP_RATE_DN [18]). A
limit of zero disables rate limiting.
As shown in figure 48, the block executes a percentage of the set point change each macrocycle. For example, if the
set point rate is set at 10% per second and the macrocycle is 500 milliseconds (0.5 seconds or 50% of 1 second), then
during the first macrocycle the set point will change 5% (50% of the 10% per second rate). If the macrocycle is 750
milliseconds (0.75 seconds or 75% of 1 second), then during the first macrocycle the setpoint will change 7.5% (75% of
10).
When the transducer block receives the setpoint change from an AO block with rate limits, it will smoothly move the
valve to the requested setpoint at the rate limit configured in the AO block.
In Auto mode, the converted SP [8] value is stored in the OUT [9] attribute. In Man mode, the OUT [9] attribute is set
manually, and is used to set the analog output defined by the CHANNEL [22] parameter.
You can access the actuator position associated with the output channel through the READBACK [16] parameter (in
OUT units) and in the PV [7] attribute (in engineering units). The digital valve controller supports position feedback
and therefore provides the actual valve position in PV [7] and READBACK [16] directly.

117

Instruction Manual

Detailed SetupAO Function Block


August 2012

D103412X012

Figure 48. Analog Output Function Block Timing Diagram

CAS_IN, 2
1 macrocycle
SPRATEDN

1 macrocycle
SPRATEUP

OUT

TRANSDUCER BLOCK
TRAVEL TARGET

SP
B27181

1 second

1 second

1 second

1 second

Time

Action On Fault Detection


To define the action you wish the valve to take when the block is in CAS mode, and the CAS_IN [17] input detects a
communication failure, or is commanded to go to fault state by the upstream block or the resource block, configure
the following parameters:
IO_OPTS [14]: Determines the action OUT [9] will take upon a fault state. If the IO_OPTS [14] Fault State to Value is
not selected, then OUT [9] holds its last position when Fault State is set. If Fault State to Value is selected, OUT [9]
goes to the FSTATE_VAL [24] value when Fault State is set.
FSTATE_TIME [23]: The length of time, in seconds, that the AO block will wait to set Fault State. When Fault State is
set, the OUT [9] value goes to either the FSTATE_VAL [24] value or holds its last position, depending on I/O_OPTS [14].
When the block has a target mode of CAS, a fault condition will be detected if the CAS_IN [17] has a BAD status or an
Initiate Fault State substatus is received from the upstream block.
FSTATE_VAL [24]: Determines the OUT [9] value if IO_OPTS Fault State to Value is selected. The OUT [9] value
transitions to FSTATE_VAL [24] after FSTATE_TIME [23] elapses and the fault condition has not cleared.

I/O Options
The I/O options parameter (IO_OPTS [14]) allows you to select how the I/O signals are processed. You can set I/O
options in Out of Service mode only. The following I/O options are available in the AO block:
Use PV for BKCAL_OUTChanges the BKCAL_OUT [25] value to the PV [7] value. When the Use PV for BKCAL_OUT
option is not enabled (False), the BKCAL_OUT [25] value is the working setpoint value.
Target to Man if Fault State ActivatedSet the target mode to Man, thus losing the original target, if Fault State is
activated. This latches an output block into the manual mode.

118

Instruction Manual

Detailed SetupAO Function Block

D103412X012

August 2012

Use Fault State value on RestartUse the value of FSTATE_VAL [24] for SP [8] when power is restored or if the device is
restarted, otherwise use the last value saved in nonvolatile memory. This does not act like Fault State, it only uses the
value of FSTATE_VAL [24].
Fault State to ValueThe output action to take when a fault occurs (if not selected, use hold last value; if selected, use
FSTATE_VAL [24]).
Increase to CloseIf the Increase to Close bit is set the value to the transducer is inverted, e.g. 20% becomes 80%.
SP-PV Track in ManPermits the setpoint to track the process variable when the target mode of the block is MAN.
SP-PV Track in LO or IManPermits the setpoint to track the process variable when the actual mode of the block is LO
or IMan.
SP Track retained TargetPermits the setpoint to track the RCas or Cas parameter based on the retained target mode
when the actual mode of the block is LO or Man. When SPPV track options are enabled, the SP Track retained target
will have precedence in the selection of the value to track when the actual mode is Man and LO.

Simulation
When simulate is active, the transducer subparameters show the actual transducer block status and value as normally
passed back to the AO block. The Simulate subparameters are writable and replace actual transducer values.

Note
When simulate is active, the output block no longer writes values to the transducer block. If the Output Blk Timeout period is
exceeded, the transducer block may move the valve to the Zero Power Condition depending on the configuration of the Output
Block Timeout Alert.

Application Information
The configuration of an AO function block and its associated output channels depends on the specific application. A
typical configuration for the Analog Output involves the following attributes:
PV_SCALE

Set the range and engineering units to values that correspond to the operation range.
For the digital valve controller, PV_SCALE [11] is typically set between 0 and 100%.

BKCAL_OUT

If you are using the CAS_IN [17] connector wired from another block, wire the
BKCAL_OUT [25] attribute to the other block's BKCAL_IN [27] attribute.

IO_OPTS

Set the type of tracking and action upon fault state.

SHED_OPT

Set the action to be taken when the set point or output are not updated in a remote
mode.

Block Errors
Table 424 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the AO
block and are provided only for your reference.

119

Instruction Manual

Detailed SetupAO Function Block


August 2012

D103412X012

Table 424. BLOCK_ERR Conditions


Condition Number

Condition Name and Description

Other (N/A)

Block Configuration Error CHANNEL and SHED_OPT set to 0

Link Configuration Error (N/A)

Simulate active Simulation is enabled and the block is using a simulated value in its execution.

Local Override Device in fault state. Actual mode LO.

Device Fault State Set AO block in fault state after FSTATE_TIME because of Bad status or IFS substatus on CAS_IN or
Resource block commanded fault state.

Device Needs Maintenance Soon Indicates a Maintenance PlantWeb Alert condition is active if Block Error Reporting is
enabled. See page 86.

Input failure/process variable has Bad status (N/A)

Output failure PV has bad status.

Memory Failure (N/A)

10

Lost Static Data (N/A)

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now Indicates Failed PlantWeb Alert condition is active if Block Error Reporting is enabled. See
page 86.

14

Power Up This condition exists after power up until actual mode is not Out of Service.

15

Out of Service The block is in Out of Service (OOS) mode.

AO Function Block Parameter List (table 425)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter
Table 425. Analog Output Function Block Parameter Definitions
Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Range

Initial
Value

Description

Static Revision
ST_REV

RO

N/A

0 to 65535

Data Type: Unsigned16


The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.

Tag Description
TAG_DESC

RW

ALL

7 bit ASCII

Spaces

Data Type: Octet String


The user description of the intended application of
the block.

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.

Alert Key
ALERT_KEY

RW

ALL

1 to 255

Data Type: Unsigned8


The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.

-Continued-

120

Instruction Manual

Detailed SetupAO Function Block

D103412X012

August 2012

Table 425. Analog Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Block Mode
MODE_BLK
TARGET

ACTUAL


Index
Number

RO /
RW

Block
Mode

OOS
MAN
AUTO
AUTOCAS
AUTORCAS

OOS until
block is
configured,
then last valid
target

OOS+MAN+AUTO+
CAS+RCAS

5.1

RW

ALL

5.2

RO

ALL

OOS
OOS+MAN+A
UTO+
CAS+RCAS

5.3

RW

ALL

NORMAL


5.4

RW

ALL

Process Variable
PV

Initial
Value

Description

PERMITTED


Block Error
BLOCK_ERR

Range

RO

RO

Data Type: DS69


Valid Bits: 7: OOS, 6: IMAN, 5: LO, 4: MAN, 3: AUTO,
2: CAS, 1: RCAS
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
(Note: Bit 6 (IMAN) is valid for ACTUAL only)
Permitted: Allowed modes for Target
Normal: Most common mode for Target

AUTO

N/A

1: Block Configuration
Error
3: Simulate Active
4: Local Override
5: Device Fault State Set
8: Output Failure
14: Powerup
15: OutofService

N/A

PV Status set equal to


READBACK status

Dynamic

Data Type: Bit String (2 byte)


0=inactive
1=active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown. See table 424.

Dynamic

Data Type: DS65


The process variable used in block execution. This
value is converted from READBACK to show the
actuator position in the same units as the setpoint
value.

Set Point
SP

OOS
MAN
AUTO

PV_SCALE +/- 10%

Dynamic

Data Type: DS65


The SP of the analog block. Can be derived from
CAS_IN, RCAS_IN in normal modes, or can track PV
in MAN, IMan or LO modes. IO_OPTS is used to
determine value of SP in MAN, IMan or LO. If no
IO_OPTS for SP tracking are set, SP will freeze when
mode changes from CAS or RCAS.

Output
OUT

MAN
OOS

OUT_SCALE +/- 10%

Dynamic

Data Type: DS65


The primary value and status calculated by the
block in Auto mode. OUT may be set manually in
Man mode.

Simulate
SIMULATE

10

SIMULATE_STATUS

10.1

RW

ALL

SIMULATE_VALUE

10.2

RW

ALL

TRANSDUCER_STATUS

10.3

RO

ALL

TRANSDUCER_VALUE

10.4

RO

ALL

ENABLE/DISABLE

Process Value Scale


PV_SCALE

Transducer Scale
XD_SCALE

10.5

11

12

RW

RW

RO

Data Type: DS82


Allows the analog input to be manually supplied
when simulate is enabled. When simulation is
disabled, the simulate value and status track actual
value & status.

ALL

0: Not Initialized
1: Simulation Disable
2: Simulation Active

OOS

EU at 100%
EU at 0%
Units index
Decimal Point

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units
code, and number of decimal places to be used in
displaying the PV parameter and parameters which
have the same scaling as PV.

OOS

EU at 100%
EU at 0%
Units index
Decimal Point

100 only
0 only
% only
2

Data Type: DS68


The high and low scale values and engineering
units code are read only. This parameter
determines the number of digits to the right of the
decimal point used with the value obtained from
the transducer for a specified channel.

1: Simulation
Disabled

-Continued-

121

Instruction Manual

Detailed SetupAO Function Block


August 2012

D103412X012

Table 425. Analog Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Grant Deny
GRANT_DENY

Index
Number

RO /
RW

Block
Mode

13.1

RW

ALL

DENY

13.2

RW

ALL

Status Options
STATUS_OPTS

Initial
Value

13

GRANT

I/O Options
IO_OPTS

Range

14

OOS

15

OOS

0: Program
1: Tune
2: Alarm
3: Local
1: SP tracks PV in Man
3: SP tracks PV in LO or
Iman
4: SP Track retained
target in Man or LO
5: Increase to Close
6: Fault State to value
0=freeze
1=go to Fault State
value
7: Use Fault State
value on restart
8: Target to Man if
Fault State activated
9: Use PV for
BKCAL_OUT
0=SP
1=PV
4: Propagate Failure
Backward

All bits: 0
All bits: 0

Cascade Input
CAS_IN

16

17

RO

All bits: 0

All bits: 0

Data Type: Bit String


0=disable
1=enable
Options the user may select for the block
processing of status.

N/A

ALL

Data Type: DS70


Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block.
GRANT: 1 = granted, 0= N/A
DENY: 1 = denied, 0 = N/A

Data Type: Bit String (2 byte)


0=disable
1=enable
Allows you to select the type of tracking and the
output value when a fault condition occurs.

Status
Readback
READBACK

Description

Value

Dynamic

Status

BAD:
NC:
const

Value

Data Type: DS65


Readback is the decharacterized valve position as
reported by the transducer block parameter
FINAL_POSITION_VALUE [17]. This correlates with
the AO block parameter OUT [9], which is the
setpoint to the transducer. READBACK is the
simulated input if SIMULATE is enabled or the
transducer block feedback if SIMULATE is disabled.
Data Type: DS65
The setpoint value from another function block.

Setpoint Rate Down


SP_RATE_DN

18

ALL

Positive, 0 disables
rate limiting PV units

+INF

Data Type: Float


Ramp rate for downward set point changes. When
the ramp rate is set to zero, the set point is used
immediately.

Setpoint Rate Up
SP_RATE_UP

19

ALL

Positive, 0 disables
rate limiting PV units

+INF

Data Type: Float


Ramp rate for upward set point changes. When the
ramp rate is set to zero, the setpoint is used
immediately.

Setpoint High Limit


SP_HI_LIM

20

ALL

PV Scale +/- 10%

100

Data Type: Float


The highest set point value allowed. SP_HI_LIM
must be greater than SP_LO_LIM.

Setpoint Low Limit


SP_LO_LIM

21

ALL

PV Scale +/- 10%

Data Type: Float


The lowest set point value allowed. SP_LO_LIM
must be less than SP_HI_LIM.

AO Channel
CHANNEL

22

OOS

1=Setpoint

Fault State Time


FSTATE_TIME

23

ALL

Positive, seconds
-Continued-

122

1=Setpoint

Data Type: Unsigned16


Defines which transducer parameter receives the
AO output. Select Setpoint to control valve
position.
Data Type: Float
Time from failure detection to reaction if failure still
exists.

Instruction Manual

Detailed SetupAO Function Block

D103412X012

August 2012

Table 425. Analog Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

Fault State Value


FSTATE_VAL

24

Back Calculation Output


BKCAL_OUT

25

Remote Cascade Input


RCAS_IN

26

RO /
RW

Block
Mode
ALL

Range
PV Scale +/- 10%

Initial
Value

Description

Data Type: Float


Preset value to use if I/O_OPTS Fault State to Value
or Use Fault State Value on Restart is set.

Dynamic

Data Type: DS65


The value and
status required by the BKCAL_IN input of another
block to prevent reset windup and to provide
bumpless transfer to closed loop control.

Status Limits
RO

N/A
Value

Shed Options
SHED_OPT

27

Remote Cascade Output


RCAS_OUT

28

Update Event
UPDATE_EVT

29

ALL

ALL

RO

N/A

Status

BAD: NoCom:
NoVal:
const

Value

0 Trk

Defined by FF spec
0=Invalid
1=Normal Shed,
Normal Return
2=Normal Shed, No
Return
3=Shed to Auto,
normal return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)
Status
Value

Dynamic

UNACKNOWLEDGED

29.1

RW

N/A

0:Undefined
1:Acknowledged
2:Unacknowledged

0: Undefined

UPDATE_STATUS

29.2

RO

N/A

0:Undefined
1:Update reported
2:Update not reported

0: Undefined

TIME_STAMP

29.3

RO

N/A

STATIC_REVISION

29.4

RO

N/A

RELATIVE_INDEX

29.5

RO

N/A

RW

N/A

0:Undefined
1:Acknowledged
2:Unacknowledged
0:Undefined
1:Clear reported
2:Clear not reported
3:Active reported
4:Active not reported

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

Data Type: DS65


Target SP and status by supervisory host

Data Type: Unsigned8


Defines the action to be taken when the set point is
not updated in a remote mode.

Data Type: DS65


Block set point and status after ramping

Data Type: DS73


This alert is generated by any changes to static data.

30
30.1

0: Undefined

ALARM_STATE

30.2

RO

N/A

0: Undefined

TIME_STAMP

30.3

RO

N/A

SUBCODE

30.4

RO

N/A

VALUE

30.5

RO

N/A

Data Type: DS72


The block alarm is used for all configuration,
hardware, connection failure, or system problems
in the block.

0
-Continued-

123

Instruction Manual

Detailed SetupAO Function Block


August 2012

D103412X012

Table 425. Analog Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Initial
Value

Range

Description

Extended Parameters
StdDev
STDDEV

31

RO

N/A

positive float

Dynamic

Data Type: Float


Standard Deviation. To support DeltaV Variability
measurement.

Cap StdDev
CAP_STDDEV

32

RO

N/A

positive float

Dynamic

Data Type: Float


Capability Standard Deviation. To support DeltaV
Variability measurement.

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 426. AO Function Block, View 1
Index Number
1

Parameter
ST_REV

Index Number
1

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

BLOCK_ERR

PV

PV

SP

SP

OUT

OUT

16

READBACK

16

READBACK

17

CAS_IN

17

CAS_IN

25

BKCAL_OUT

26

RCAS_IN

28

RCAS_OUT

31

STDDEV

32

CAP_STDDEV

Table 427. AO Function Block, View 2


Index Number

124

Table 428. AO Function Block, View 3

Parameter

ST_REV

11

PV_SCALE

12

XD_SCALE

13.1

GRANT_DENY.GRANT

13.2

GRANT_DENY.DENY

20

SP_HI_LIM

21

SP_LO_LIM

Table 429. AO Function Block, View 4


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

14

IO_OPTS

15

STATUS_OPTS

18

SP_RATE_DN

19

SP_RATE_UP

22

CHANNEL

23

FSTATE_TIME

24

FSTATE_VAL

27

SHED_OPT

Instruction Manual

Detailed SetupAO Function Block

D103412X012

August 2012

Field Communicator Menu Structure


ANALOG OUTPUT FUNCTION BLOCK
Quick Config
Alert Key
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Setpoint: Status
Setpoint: Value
Setpoint High Limit
Setpoint Low Limit
Common Config
Alert Key
I/O Options
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Setpoint: Status
Setpoint: Value
Setpoint High Limit
Setpoint Low Limit
Advanced Config
Fault State Time
Fault State Value
Shed Options
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Setpoint Rate Down
Setpoint Rate Up
Static Revision
Status Options
Strategy
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
I/O Reference
AO Channel

Connectors
Back Calculation Output: Status
Back Calculation Output: Value
Cascade Input: Status
Cascade Input: Value
Output: Status
Output: Value

Online
Back Calculation Output: Status
Back Calculation Output: Value
Block Error
Cascade Input: Status
Cascade Input: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output: Status
Output: Value
Process Value: Status
Process Value: Value
Remote Cascade Input: Status
Remote Cascade Input: Value
Remote Cascade Output: Status
Remote Cascade Output: Value
Readback: Status
Readback: Value
Setpoint: Status
Setpoint: Value

Status
Block Error

Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
StdDev
Cap StdDev

All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value: Status
Process Value: Value
Setpoint: Status
Setpoint: Value
Output: Status
Output: Value
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
Readback: Status
Readback: Value
Cascade Input: Status
Cascade Input: Value
Setpoint Rate Down
Setpoint Rate Up
Setpoint High Limit
Setpoint Low Limit
AO Channel
Fault State Time
Fault State Value
Back Calculation Output: Status
Back Calculation Output: Value
Remote Cascade Input: Status
Remote Cascade Input: Value
Shed Options
Remote Cascade Output: Status
Remote Cascade Output: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
StdDev
Cap StdDev

125

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

PID Function Block


Overview
The PID function block (figure 49) combines all of the necessary logic to perform proportional/integral/derivative
(PID) control. The block supports mode control, signal scaling and limiting, feedforward control, override tracking,
alarm limit detection, and signal status propagation.
Figure 49. Proportional+Integral+Derivative (PID) Function Block
BKCAL

IN

CAS

IN

BKCALOUT

VAL

FF

TRK
TRK

IN

OUT

PID

IN
D
VAL

BKCAL_IN = THE ANALOG INPUT VALUE AND STATUS FROM ANOTHER BLOCK'S BKCAL
_OUT OUTPUT THAT IS USED FOR BACKWARD OUTPUT TRACKING FOR BUMPLESS
TRANSFER AND TO PASS LIMIT STATUS.
CAS_IN = THE REMOTE SETPOINT VALUE FROM ANOTHER FUNCTION BLOCK.
FF_VAL = THE FEEDFORWARD CONTROL INPUT VALUE AND STATUS.
IN = THE CONNECTION FOR THE PROCESS VARIABLEFROM ANOTHER FUNCTION BLOCK.
TRK_IN_D = INITIATES THE EXTERNAL TRACKING FUNCTION.
TRK_VAL = THE VALUE AFTER SCALING APPLIED TO OUT IN LOCAL OVERRIDE MODE.
BKCAL_OUT = THE VALUE AND STATUS REQUIRED BY THE BKCAL_IN INPUT OF ANOTHER
FUNCTION BLOCK TO PREVENT RESET WINDUP AND TO PROVIDE BUMPLESS TRANSFER
TO CLOSED LOOP CONTROL.
OUT = THE BLOCK OUTPUT AND STATUS.
B2720

The block supports two forms of the PID equation: Standard and Series. You can choose the appropriate equation
using the MATHFORM [70] parameter. The Standard ISA PID equation is the default selection.

Standard Out + GAIN

Series Out + GAIN

ex

1 ) t s 1) 1 ) T
r

ex

t ds
)
t ds ) 1

1 ) t1s ) T t s t)s 1) 1 )F
d

where
GAIN:

proportional gain value

r:

integral action time constant (RESET parameter) in seconds

s:

laplace operator

d:

derivative action time constant (RATE parameter)

126

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

fixed smoothing factor of 0.1 applied to RATE

F:

feedforward control contribution from the feedforward input (FF_VAL)

E:

error between setpoint and process variable

To further customize the block for use in your application, you can configure filtering, feedforward inputs, tracking
inputs, setpoint and output limiting, PID equation structures, and block output action. Table 432 lists the PID block
parameters and their descriptions, units of measure, and index numbers, and figure 410 illustrates the internal
components of the PID function block.

Figure 410. PID Function Block Schematic

FFGAIN
FFSCALE

Feedforward
Calculation

FFVAL
BKCALIN

MODE

TRKIND

BKCALOUT
RCASOUT

ROUTOUT
ROUTIN

RCASIN
Setpoint
Limiting
CASIN
Operator
Setpoint

IN

SPHILIM
SPLOLIM
SPRATEDN
SPRATEUP
Scaling
and
Filtering

PVSCALE
PVFILTER
TRKVAL

PID
Equation

GAIN
RATE
RESET
Alarm
Detection

Output
Limiting

OUT

OUTHILIM
OUTLOLIM
OUTSCALE
Operator
Output

HIHILIM
HILIM
DVHILIM
DVLOLIM
LOLIM
LOLOLIM

Convert

TRKSCALE
OUTSCALE
B2721

127

Detailed SetupPID Function Block

Instruction Manual

August 2012

D103412X012

Modes
The PID function block supports the following modes:
Manual (Man)The block output (OUT [9]) may be set manually.
Automatic (Auto)The SP [8] may be set manually and the block algorithm calculates OUT [9].
Cascade (Cas)The SP [8] is calculated in another block and is provided to the PID block through the CAS_IN [18]
connection.
RemoteCascade (RCas)The SP [8] is provided by a host computer that writes to the RCAS_IN [32] parameter.
RemoteOutput (ROut)The OUT [9] is provided by a host computer that writes to the ROUT_IN [33] parameter.
Local Override (LO)The track function is active. OUT [9] is set by TRK_VAL [39]. The BLOCK_ERR [6] parameter
shows Local override.
Initialization Manual (IMan)The output path is not complete (for example, the cascade-to-slave path might not be
open). In IMan mode, OUT [9] tracks BKCAL_IN [27].
Out of Service (OOS)The block is not processed. The OUT [9] status is set to Bad: Out of Service. The BLOCK_ERR
[6] parameter shows Out of service.
You can configure the Man, Auto, Cas, and OOS modes as permitted modes for operator entry.

Mode Handling
Shed OptionsRCAS Mode Only
Shed from or climb to a remote mode is determined by the parameter SHED_OPT [34]. A block climbs and sheds
through the same path. For example, if SHED_OPT [34] specifies that a block should shed to Auto, then, if the block
target mode is set to RCas, the block goes through Auto on the way to RCas. You can configure the shed option as
follows:

Shed With Return Options


Remote cascade or remote output connection failure shifts actual mode but keeps trying to restore remote cascade or
remote output (in other words, the remote cascade or remote output target mode stays in effect).
NormalOn failure of a remote connection, the block attempts to attain the highest permitted nonremote mode
until the remote connection is restored. Cas is the highest permitted nonremote mode and Auto is is the next highest
permitted nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the mode the block was in before changing to one of the remote target
modes. On failure of a remote connection, the block attempts to attain the retained target mode.
AutoOn failure of a remote connection, the block attempts to attain Auto, if permitted, until the remote connection
is restored.
ManOn failure of a remote connection, the block sheds to Man until a remote connection is restored.

128

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Shed With No Return Options


For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no
attempt to restore the connection following failure. The behavior on change to a remote target mode is identical to
that for Shed With Return Options.
NormalOn failure of a remote connection, the block sets the target mode to the highest permitted nonremote
mode. Cas is the highest permitted nonremote mode and Auto is is the next permitted nonremote mode. If Cas or
Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the mode the block was in before changing to one of the remote target
modes. On failure of a remote connection, the block sets the target mode to the retained target mode.
AutoOn failure of a remote connection, the block sets the target mode to Auto, if permitted.
ManOn failure of a remote connection, the block sets the target mode to Man, if permitted.
The user may configure SHED_OPTS [34] so that it calls for a target mode that is not permitted. When doing this, the
mode logic uses the following rules as applied by the remote logic:
Shed logic never results in a nonpermitted target mode.
Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted.

Status Handling
If the input status on the PID block is Bad, the mode of the block reverts to Manual. In addition, you can select the
Target to Manual if Bad IN status option to direct the target mode to revert to manual. You can set the status option in
Manual or Out of Service mode only.

Set Point Selection and Limiting


The set point of the PID block is only valid when the block is in Auto, Cas, or RCas. Figure 411 illustrates the method
for set point selection. You can configure the SP_HI_LIM [21] and SP_LO_LIM [22] parameters to limit the set point. In
Cascade or Remote Cascade mode, the set point is adjusted by another function block or by a host computer, and the
output is computed based on the set point.
Figure 411. PID Function Block Set Point Selection
Operator
Set point

Auto
Man
CAS

SPHILIM
SPLOLIM

SPRATEUP
SPRATEDN

Setpoint
Limiting

Rate
Limiting

Auto
Man
CAS

B2722

In Automatic mode, the set point is entered manually by the operator, and the output is computed based on the set
point. In Auto mode, you can also adjust the set point limit and the set point rate of change using the SP_RATE_UP
[20] and SP_RATE_DN [19] parameters.

129

Detailed SetupPID Function Block

Instruction Manual

August 2012

D103412X012

In Manual mode the output is entered manually by the operator. In Remote Output mode, the output is entered by a
host computer.

Output Selection and Limiting


Output selection is determined by the mode and the set point. In Automatic, Cascade, or Remote Cascade mode, the
output is computed by the PID control equation. In Manual and Remote Output mode, the output may be entered
manually (see also Set Point Selection and Limiting). You can limit the output by configuring the OUT_HI_LIM [28] and
OUT_LO_LIM [29] parameters.

Filtering
The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid
changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME [16] or SP_FTIME [69]
parameters. Set the filter time constant to zero to disable the filter feature.

Feedforward Calculation
The feedforward value (FF_VAL [40]) is scaled (FF_SCALE [41]) to a common range for compatibility with the output
scale (OUT_SCALE [11]). A gain value (FF_GAIN [42]) is applied to achieve the total feedforward contribution.

Output Tracking
Output tracking is enabled through the control options. You can set control options in Manual or Out of Service mode
only.
The Track Enable control option must be set to True for the track function to operate. When the Track in Manual
control option is set to True, the operator cannot override the tracking function in Manual mode. When Track in
Manual is False, the operator can override the tracking function when the block is in Manual mode. Activating the track
function causes the block's actual mode to revert to Local Override.
The TRK_VAL [38] parameter specifies the value to be converted and tracked into the output when the track function
is operating. The TRK_SCALE [37] parameter specifies the range of TRK_VAL [38].
When the TRK_IN_D [38] parameter is True and the Track Enable control option is True, the TRK_VAL [38] input is
converted to the appropriate value and output in units of OUT_SCALE [11].

Set Point Tracking


You can configure the method for tracking the set point by configuring the following control options (CONTROL_OPTS
[12]):
SP-PV Track in ManPermits the SP [8] to track the PV [7] when the actual mode of the block is Man.
SP-PV Track in LO or IManPermits the SP [8] to track the PV [7] when the actual mode of the block is Local Override
(LO) or Initialization Manual (IMan).
SP-PV Track in ROUTPermits the SP [8] to track the PV [7] when the actual mode of the block is RemoteOut
(ROUT).
SP Track retained TargetCauses the set point to track the RCAS or CAS parameter based on the retained target
mode when the actual mode is MAN or LO.

130

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Act On IRIf this option is true, then when IR (Initialization Requested) is received on BKCAL_IN [27], the SP [8] will
be adjusted within setpoint limits to provide bumpless transfer when the cascade is closed. If the setpoint required
to provide bumpless transfer is outside the setpoint limits, then any difference added to provide bumpless transfer
will be removed in the BAL_TIME [25].
When one of these options is set, the SP[8] value is set to the PV [7] value while in the specified mode.
You can select the value that a master controller uses for tracking by configuring the Use PV for BKCAL_OUT control
option. The BKCAL_OUT [31] value tracks the PV value. BKCAL_IN [27] on a master controller connected to
BKCAL_OUT [31] on the PID block in an open cascade strategy forces its OUT [9] to match BKCAL_IN [27], thus
tracking the PV from the slave PID block into its cascade input connection (CAS_IN [18]). If the Use PV for BKCAL_OUT
option is not selected, the working set point (SP_WRK [68]) is used for BKCAL_OUT [31].
You can set control options in Manual or Out of Service mode only. When the mode is set to Auto, the SP [8] will
remain at the last value (it will no longer follow the PV [7].

PID Equation Structures for Enhanced PID Block


Note
Extended parameters are not available at this time for all host systems. Refer to your host system documentation, or contact your
Emerson Process Management sales office for additional information.

Configure the STRUCTURECONFIG [71] parameter to select the PID equation structure. You can select one of the
following choices:
Proportional, integral, and derivative on error (PID)
Proportional and integral on error, derivative on PV (PI_D)
Integral on error, proportional and derivative on PV (I_PD)
Proportional on error, derivative on error (PD)
Integral on error, derivative on error (ID)
Integral on error, derivative on PV (I_D)
Two degrees of Freedom (2DOF)

Reverse and Direct Action


To configure the block output action, set the Direct Acting control option. This option defines the relationship
between a change in PV [7] and the corresponding change in output. With Direct Acting enabled (True), an increase in
PV results in an increase in the output.
You can set control options in Manual or Out of Service mode only.

Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block error for the PID
block are defined above.

131

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

Process alarm detection is based on the PV [7] value. You can configure the alarm limits of the following standard
alarms:
High (HI_LIM [51])
High high (HI_HI_LIM [49])
Low (LO_LIM [53])
Low low (LO_LO_LIM [55])
Additional process alarm detection is based on the difference between SP [8] and PV [7] values and can be configured
via the following parameters:
Deviation high (DV_HI_LIM [57])
Deviation low (DV_LO_LIM [59])
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent
of the PV span can be set using the ALARM_HYS [47] parameter. The priority of each alarm is set in the following
parameters:
HI_PRI [50]
HI_HI_PRI [48]
LO_PRI [52]
LO_LO_PRI [54]
DV_HI_PRI [56]
DV_LO_PRI [58]
Alarms are grouped into five levels of priority, as shown in table 430.
Table 430. PID Function Block Alarm Priorities
Priority Description(1)

Priority Number
0

The alarm is disabled

An alarm condition with a priority of 1 can be recognized by the system. The device monitors the alarm but does not report it
until requested by the host system.

An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
diagnostics and system alerts).

3-7

Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.

8-15

Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.

1. The priority classes advise and critical have no relationship to Plant Web Alerts.

Application Information
The PID function block is a powerful, flexible control algorithm that is designed to work in a variety of control
strategies. The PID block is configured differently for different applications.

DeltaV Tune
DeltaV Tune quickly and automatically determines optimal tuning parameters for PID control loops. For more
information on DeltaV Tune, refer to DeltaV Books Online or DeltaV documentation.

Block Errors
Table 431 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the PID
block and are provided only for your reference.

132

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Table 431. BLOCK_ERR Conditions


Condition Number

Condition Name and Description

Other (N/A)

Block Configuration ErrorSHED_OPT or BYPASS set to 0

Link Configuration Error (N/A)

Simulate Active (N/A)

Local OverrideThe actual mode is LO and Track Enable is set.

Device Fault State Set (N/A)

Device Needs Maintenance Soon (N/A)

Input failure/process variable has Bad statusThe parameter linked to IN is indicating a Bad status.

Output Failure (N/A)

Memory Failure (N/A)

10

Lost Static Data (N/A)

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now (N/A)

14

Power UpSet if devices was powered up with this block in Out of Service (OOS) mode. Cleared on first change of mode to other
than OOS.

15

Out of ServiceThe actual mode is Out of Service (OOS).

PID Function Block Parameter List (table 432)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter
Table 432. PID Function Block System Parameters Definitions
Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Range

Initial Value

Description

Static Revision
ST_REV

RO

N/A

0 to 65535

Data Type: Unsigned16


The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static pa rameter value in
the block is changed.

Tag Description
TAG_DESC

RW

ALL

7 bit ASCII

Spaces

Data Type: Octet String


The user description of the intended application of
the block.

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.

Data Type: Unsigned8


The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.

Alert Key
ALERT_KEY

Block Mode
MODE_BLK

RW

ALL

TARGET

5.1

RW

ALL

ACTUAL

5.2

RO

ALL

PERMITTED

5.3

RW

ALL

NORMAL

5.4

RW

ALL

0 to 255

OOS, MAN, AUTO


CAS, RCAS, ROUT

OOS until
block is
configured,
then last valid
target
OOS

OOS+MAN+AUTO+
CAS+RCAS+ROUT

OOS MAN,
AUTO CAS,
RCAS ROUT

Data Type: DS69


Valid Bits: 7: OOS, 6: IMAN, 5: LO, 4: MAN, 3:
AUTO, 2: CAS, 1: RCAS, 0: ROUT
The actual, target, permitted, and normal modes
of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

AUTO
-Continued-

133

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Range

Initial Value

Description

Dynamic

Data Type: Bit String


0 = inactive
1 = active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string so that
multiple errors may be shown.

Dynamic

Data Type: DS65


The process variable used in block execution.

PV_SCALE +/- 10%

Dynamic

Data Type: DS65


The target block setpoint value. It is the result of
setpoint limiting and setpoint rate of change
limiting.

Status
OUT_SCALE +/- 10%

Dynamic

Defined Bits
Block Error
BLOCK_ERR

RO

N/A

Process Value
PV

RO

N/A

Setpoint
SP

OOS
MAN
AUTO

Output
OUT

MAN
OOS

Process Value Scale


PV_SCALE

10

Output Scale
OUT_SCALE

11

Grant Deny
GRANT_DENY

12

GRANT

DENY

Control Options
CONTROL_OPTS

Status Options
STATUS_OPTS

Input
IN

Process Value Filter Time


PV_FTIME

12.1

12.2

13

14

15

16

1: Block Configuration Error


4: Local Override
7: Input Failure/ Bad PV status
14: Powerup
15: OutofService

Value

OOS

EU at 100%
EU at 0%
Units index
Decimal Point

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with PV.

OOS

EU at 100%
EU at 0%t
Units index
Decimal Point

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with OUT.

ALL

0: Program
1: Tune
2: Alarm
3: Local

All bits: 0

ALL

0: Program
1: Tune
2: Alarm
3: Local

All bits: 0

OOS

0: Bypass Enable
1: SP tracks PV in MAN
2: SP tracks PV in ROUT
3: SP tracks PV in LO or MAN
4: SP tracks RCAS or CAS in
IMAN, LO, MAN or ROUT
5: Direct Acting
7: Track Enable
8: Track in Manual
9: Use PV for BKCAL_OUT
10: Act on IR
12: Restrict SP to limits in
Cas and RCas
13: No output limits in MAN

All bits: 0

Data Type: Bit String


0=disable
1=enable
Allows you to specify control strategy options.

OOS

0: IFS (Initiate Fault State)


if BAD IN
1: IFS if BAD CAS_IN
2: Use Uncertain as Good
5: Target to MAN if BAD IN

All bits: 0

Data Type: Bit String


0=disable
1=enable
Allows you to select options for status handling
and processing.

ALL

ALL

Status

BAD:
NC:
const

Value

Positive

-Continued-

134

DS65
The block output value and status.

Data Type: DS70


Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block. Not used by the
device.
GRANT: 0=N/A, 1=granted
DENY: 0 = N/A, 1= denied

Data Type: DS65


The primary input value of the block.
Data Type: Float
The time constant of the first-order PV filter. It is
the time, in seconds, required for a 63 percent
change in the IN value.

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME
Bypass
BYPASS

Cascade Input
CAS_IN

Setpoint Rate Down


SP_RATE_DN

Index
Number

RO /
RW

Block
Mode
MAN
OOS

17

18

ALL

19

ALL

Range

Initial Value

1=Off
2=On

0=undefined

Status

BAD
NC:
const

Value

Positive

Description
Data Type: Enum
Used to override the calculation of the block.
When enabled, the SP is sent directly to the
output.
Data Type: DS65
The setpoint value from another block.

+ INF

Data Type: Float


Ramp rate for downward SP changes. When the
ramp rate is set to zero, the SP is used
immediately. PV per second

Setpoint Rate UP
SP_RATE_UP

20

ALL

Positive

+ INF

Data Type: Float


Ramp rate for upward SP changes. When the ramp
rate is set to zero, the SP is used immediately. PV
per second

Setpoint High Limit


SP_HI_LIM

21

ALL

PV Scale +/- 10%, must be


greater than SP_LO_LIM

100

Data Type: Float


The highest SP value allowed.

Setpoint Low Limit


SP_LO_LIM

22

ALL

PV Scale
+/- 10%, must be less than
SP_HI_LIM

Data Type: Float


The lowest SP value allowed.

Gain
GAIN

23

ALL

greater than 0

Data Type: Float


The proportional gain value.

Reset
RESET

24

ALL

Positive

+ INF

Data Type: Float


The integral action time constant. Seconds per
repeat

Balance Time
BAL_TIME

25

ALL

Positive

Data Type: Float


The specified time, in seconds, for the internal
working value of bias to return to the operator set
bias. Also used to specify the time constant at
which the integral term will move to obtain
balance when the output is limited and the mode is
AUTO, CAS, or RCAS.

Rate
RATE

26

ALL

Positive

Data Type: Float


The derivative action time constant, in seconds.

Status

BAD:
NC:
const

Data Type: DS65


The analog input value and status from another
block's BKCAL_OUT output that is used for
backward output tracking for bumpless transfer
and to pass limit status.

Value

Back Calculation Input


BKCAL_IN

27

ALL

Output High Limit


OUT_HI_LIM

28

ALL

OUT_SCALE +/- 10%

100

Data Type: Float


Limits the maximum output value for modes other
than manual.

Output Low Limit


OUT_LO_LIM

29

ALL

OUT_SCALE +/- 10%

Data Type: Float


Limits the minimum output value for modes other
than manual.

Back Calculation Hysteresis


BKCAL_HYS

30

ALL

0 to 50%

Back Calculation Output


BKCAL_OUT

Remote Cascade Input


RCAS_IN

31

32

RO

0.50%

N/A

ALL

Dynamic

BAD:
NoCom:
NoVal:
const

Status
Value

Data Type: Float


The amount the output value must change away
from the its output limit before limit status is
turned off.
Data Type: DS65
The value and status required by the BKCAL_IN
input of another block to prevent reset windup and
to provide bumpless transfer of closed loop
control.
Data Type: DS65
Target setpoint and status that is provided by a
supervisory host. Used when mode is RCAS.

0 Trk
-Continued-

135

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME
Remote Out Input
ROUT_IN

Shed Options
SHED_OPT

Remote Cascade Output


RCAS_OUT

Remote Out Output


ROUT_OUT

Tracking Scale
TRK_SCALE

Tracking Input Discrete


TRK_IN_D

Tracking Value
TRK_VAL

Feed Forward Value


FF_VAL

Index
Number

RO /
RW

33

ALL

34

35

36

37

38

39

40

Block
Mode

RO

Status

BAD:
NoCom:
NoVal:
const

Value

0 Trk

0=Invalid
1=Normal Shed, Normal
Return
2=Normal Shed, No Return
3=Shed to Auto, normal
return
4=Shed to Auto, no return.
Target mode changes to
Auto on detection of a shed
condition
5=Shed to Manual, normal
return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained target,
normal return
8=Shed to retained target,
no return. (Change target to
retained target)

Description

Data Type: DS65


Target output and status that is provided by a
supervisory host. Used when mode is ROUT.

0=Invalid

Dynamic

Data Type: DS65


Block setpoint and status after ramping, filtering,
and limiting that is provided to a supervisory host
for back calculation to allow action to be taken
under limiting conditions or mode change. Used
when mode is RCAS.

N/A

Dynamic

Data Type: DS65


Block output that is provided to a supervisory host
for a back calculation to allow action to be taken
under limiting conditions or mode change. Used
when mode is RCAS.

MAN
OOS

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with the external tracking
value (TRK_VAL).

N/A

ALL

ALL

ALL

BAD:
NC:
const

Status
Value

Status

BAD:
NC:
const

Feed Forward Scale


FF_SCALE

41

MAN
OOS

Feed Forward Gain


FF_GAIN

42

MAN
OOS

Data Type: DS66


Discrete input that initiates external tracking of the
block output to the value specified by TRK_VAL.

Value

Data Type: DS65


The value (after scaling from TRK_SCALE to
OUT_SCALE) applied to OUT in LO mode when
external tracking is enabled by TRK_IN_D.

Status

BAD:
NC:
const

Data Type: DS65


The feedforward control input value and status.

Value

-Continued-

136

Initial Value

Data Type: Uint8


Defines action to be taken on remote control
device timeout.
Normal Return - actual mode changes to the next
lowest priority non-remote mode permitted but
returns to the target remote mode when the
remote computer completes the initialization
handshake.
No Return - Target mode changes to the next
lowest priority non-remote mode permitted. The
target remote mode is lost, so no return occurs.

ALL

RO

Range

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with the feedforward
value (FF_VAL).

Data Type: Float


The feedforward gain value. FF_VAL is multiplied
by FF_GAIN before it is added to the calculated
control output. A value of 0 disables feedforward.

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME
Update Event
UPDATE_EVT
UNACKNOWLEDGED

Index
Number

RO /
RW

Block
Mode

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined
1=Update reported
2=Update not reported

Range

Initial Value

43
43.1

UPDATE_STATE

43.2

RO

N/A

TIME_STAMP

43.3

RO

N/A

STATIC_REVISION

43.4

RO

N/A

RELATIVE_INDEX

43.5

RO

N/A

RW

N/A

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

ALARM_STATE

Data Type: DS73


This alert is generated by any changes to the static
data.

44
44.1

44.2

RO

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clearreported
2=Clearnot reported

3=Active reported
4=Active not reported

Data Type: DS72


The block alarm is used for all configuration,
hardware, connection failure, or system problems
in the block. The cause of the alarm will be set in
the subcode.
VALUE Data Type: Unsigned8

TIME_STAMP

44.3

RO

N/A

SUBCODE

44.4

RO

N/A

VALUE

44.5

RO

N/A

Alarm Summary
ALARM_SUM

Description

45

CURRENT

45.1

RO

ALL

UNACKNOWLEDGED

45.2

RO

ALL

UNREPORTED

45.3

RO

ALL

DISABLED

45.4

RW

ALL

1: High High Alarm


2: High Alarm
3: Low Low Alarm
4: Low Alarm
5: Deviation High Alarm
6: Deviation Low Alarm
7: Block Alarm
1: High High Alarm
2: High Alarm
3: Low Low Alarm
4: Low Alarm
5: Deviation High Alarm
6: Deviation Low Alarm
7: Block Alarm

Acknowledge Option
ACK_OPTION

46

N/A

Alarm Hysteresis
ALARM_HYS

47

ALL

0 to 50%

High High Priority


HI_HI_PRI

48

ALL

0 to 15

High High Limit


HI_HI_LIM

49

ALL

PV_SCALE, or +INF

High Priority
HI_PRI

50

ALL

0 to 15

High Limit
HI_LIM

51

ALL

PV_SCALE, or +INF

Low Priority
LO_PRI

52

ALL

0 to 15

Low Limit
LO_LIM

53

ALL

PV_SCALE, or -INF

Low Low Priority


LO_LO_PRI

54

ALL

0 to 15

Dynamic

All bits: 0

0.50%

0
+INF
0
+INF
0
-INF
0

Data Type: DS74


Current alert status, unacknowledged states,
unreported states, and disabled states of the
alarms associated with the function block.

Data Type: Bit String


0=Disable
1=Enable
Used to set auto acknowledgment of alarms.

Data Type: Float


The amount the alarm value must return to within
the alarm limit before the associated active alarm
condition clears.
Data Type: Unsigned8
The priority of the HI HI Alarm.
Data Type: Float
The setting for the alarm limit used to detect the
HI HI alarm condition.
Data Type: Unsigned8
The priority of the HI alarm.
Data Type: Float
The setting for the alarm limit used to detect the
HI alarm condition.
Data Type: Unsigned8
The priority of the LO alarm.
Data Type: Float
The setting for the alarm limit used to detect the
LO alarm condition.
Data Type: Unsigned8
The priority of the LO LO alarm.

-Continued-

137

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Range

Initial Value

Low Low Limit


LO_LO_LIM

55

ALL

PV_SCALE, or -INF

Deviation High Priority


DV_HI_PRI

56

ALL

0 to 15

Deviation High Limit


DV_HI_LIM

57

ALL

PV_SCALE, or +INF

Deviation Low Priority


DV_LO_PRI

58

ALL

0 to 15

Deviation Low Limit


DV_LO_LIM

59

ALL

-INF, or -PV span to 0

High High Alarm


HI_HI_ALM

60
N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=undefined

UNACKNOWLEDGED

60.1

RW

0
+INF
0
-INF

ALARM_STATE

60.2

RO

N/A

TIME_STAMP

60.3

RO

N/A

SUBCODE

60.4

RO

N/A

VALUE

60.5

RO

N/A

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=undefined

High Alarm
HI_ALM
UNACKNOWLEDGED

Data Type: Float


The setting for the alarm limit used to detect the
deviation high alarm condition.
Data Type: Unsigned8
The priority of the deviation low alarm.
Data Type: Float
The setting for the alarm limit use to detect the
deviation low alarm condition.

Data Type: DS71


The HI HI alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.

61
61.1

61.2

RO

N/A

TIME_STAMP

61.3

RO

N/A

SUBCODE

61.4

RO

N/A

VALUE

61.5

RO

N/A

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=undefined

UNACKNOWLEDGED

Data Type: Unsigned8


The priority of the deviation high alarm.

VALUE Data Type: Float

ALARM_STATE

Low Alarm
LO_ALM

Data Type: DS71


The HI alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
VALUE Data Type: Float

62
62.1

ALARM_STATE

62.2

RO

N/A

TIME_STAMP

62.3

RO

N/A

SUBCODE

62.4

RO

N/A

VALUE

62.5

RO

N/A

Data Type: DS71


The LO alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
VALUE Data Type: Float

0
-Continued-

138

-INF

Description
Data Type: Float
The setting for the alarm limit used to detect the
LO LO alarm condition.

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME
Low Low Alarm
LO_LO_ALM
UNACKNOWLEDGED

Index
Number

RO /
RW

Block
Mode

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=undefined

Range

Initial Value

63
63.1

ALARM_STATE

63.2

RO

N/A

TIME_STAMP

63.3

RO

N/A

SUBCODE

63.4

RO

N/A

VALUE

63.5

RO

N/A

Deviation High Alarm


DV_HI_ALM

64
RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=undefined

UNACKNOWLEDGED

64.1

64.2

RO

N/A

TIME_STAMP

64.3

RO

N/A

SUBCODE

64.4

RO

N/A

VALUE

64.5

RO

N/A

Deviation Low Alarm


DV_LO_ALM

65
RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=undefined

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

0=undefined

65.1

Data Type: DS71


The LO LO alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
VALUE Data Type: Float

ALARM_STATE

UNACKNOWLEDGED

Description

Data Type: DS71


The DV HI alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
VALUE Data Type: Float

ALARM_STATE

65.2

RO

N/A

TIME_STAMP

65.3

RO

N/A

SUBCODE

65.4

RO

N/A

VALUE

65.5

RO

N/A

Data Type: DS71


The DV LO alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
VALUE Data Type: Float

0
Extended Parameters

Bias
BIAS

66

Error
ERROR

67

RO

SP Work
SP_WRK

68

RO

Data Type: Float


The bias value used to calculate output for a PD
structure.

N/A

Dynamic

Data Type: Float


The error (SP-PV) used to determine the control
action.

N/A

Dynamic

Data Type: Float


The working set point of the block after limiting
and filtering is applied. EU of PV_SCALE

Data Type: Float


The time constant of the firstorder SP filter. It is
the time, in seconds, required for a 63 percent
change in the IN value. Applied after SP rate
limiting.

ALL

OUT_SCALE +/- 10%

SP FTime
SP_FTIME

69

ALL

Positive

Math Form
MATHFORM

70

OOS

0=Standard
1=Series

0=Standard

Data Type: Unsigned8


Selects equation form (series or standard)

-Continued-

139

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME

Structureconfig
STRUCTURECONFIG

UGamma
GAMMA (ugamma)

Index
Number

RO /
RW

71

72

Block
Mode

Range

Initial Value

OOS

0=PID terms on error


1=PI terms on error, D term
on PV
2=I terms on error, PD term
on PV
3=PD terms on error
4= P term on error, D term
on PV
5=ID terms on error
6=I term on error, D term on
PV
7=2 Deg. of Freedom PID

0=PID terms
on error

Data Type: Unsigned8


Defines PID equation structure to apply controller
action.

1.0

Data Type: Float


Fraction of derivative action taken on error versus
PV. For a value of 0.6, then 60% of the derivative
action will be based on error and 40% on PV. The
value of GAMMA may be changed over a range of
0-1 if STRUCTURE is set to Two Degrees of
Freedom Control. Otherwise, it is automatically set
to a value of 1 or 0 based on the Structure
selection.

1.0

Data Type: Float


Fraction of proportional action taken on error
versus PV. For a value of 0.6, then 60% of the
proportional action will be based on error and 40%
on PV. The value of BETA may be changed over a
range of 0-1 if STRUCTURE is set to Two Degrees of
Freedom Control. Otherwise, it is automatically set
to a value of 1 or 0 based on the Structure
selection.

OOS

> = 0, < = 1

Description

UBeta
BETA (ubeta)

73

OOS

> = 0, < = 1

IDeadBand
IDEADBAND

74

OOS

Positive

StdDev
STDDEV

75

RO

N/A

Dynamic

Data Type: Float


Standard deviation of PV.

Cap StdDev
CAP_STDDEV

76

RO

N/A

Dynamic

Data Type: Float


Standard deviation of PV changes.

T Request
T_REQUEST

77

RO

ALL

T State
T_STATE

78

RO

NONE

T Status
T_STATUS

79

RO

N/A

0=Request Tuning
1=Force Tuning
2=Reset Tuner

0=Scan Rate Too Low


Warning
1=Insufficient Process
Response (obsolete)
2=Scan Rate Too High
Warning
3=Inverse Direct Acting
Error
4=PV Deviation Too Large
5=Initial PV Deviation Too
Large
6=PV Limited or Constant
7=PV Bad
8=Invalid Mode for Tuning
9=BKCAL_IN Non Good or
Limited
10=Out Limited
11=Bypass Active
12=Mode Changed
13=Tracking Active
14=Disconnected
15=SP Changed
-Continued-

140

Data Type: Float


Integral action stops when ERROR is within
IDEADBAND, proportional and derivative action
continue. EU of PV_SCALE

Data Type: Bit String


Operator request to initiate/control autotuning.

Data Type: Unsigned8


Current autotuner state.

Data Type: Bit String


Autotuner status.

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Table 432. PID Function Block System Parameters Definitions (Continued)


Label
PARAMETER_NAME
T Ipgain
T_IPGAIN

Index
Number

RO /
RW

Block
Mode

Range

Initial Value

Description

80

RO

N/A

0.0

Data Type: Float


Integrated process gain.

T Ugain
T_UGAIN

81

RO

N/A

0.0

Data Type: Float


Ultimate gain.

T Uperiod
T_UPERIOD

82

RO

N/A

0.0

Data Type: Float


Ultimate period.

T Psgain
T_PSGAIN

83

RO

N/A

0.0

Data Type: Float


Process static gain.

T Ptimec
T_PTIMEC

84

RO

N/A

0.0

Data Type: Float


Process time constant.

T Pdtime
T_PDTIME

85

RO

N/A

0.0

Data Type: Float


Process dead time.

T Targetop
T_TARGETOP

86

ALL

T Hyster
T_HYSTER

87

ALL

> = 0.0

0.0

Data Type: Float


Hysteresis

T Relayss
T_RELAYSS

88

ALL

> = 0.0

3.0

Data Type: Float


Relay step size.

T Gain Magnifier
T_GAIN_MAGNIFIER

89

ALL

> 0.1, < 100

1.0

Data Type: Float


Scales amount of gain.

T Auto Extra DT
T_AUTO_EXTRA_DT

90

ALL

Data Type: Unsigned8


Allow additional cycle with extra deadtime.

T Auto Hysteresis
T_AUTO_HYSTERESIS

91

ALL

Data Type: Unsigned8


Allows calculation of hysteresis based on
CAP_STDDEV

T Aoperiods
T_AOPERIODS

92

N/A

Data Type: Unsigned8


Actual oscillation periods.

RO

Data Type: Unsigned8


Target oscillation periods.

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 433. PID Function Block, View 1
Index Number
1

Parameter

Table 434. PID Function Block, View 2


Index Number

Parameter

ST_REV

ST_REV

5.1

MODE_BLK.TARGET_MODE

10

PV_SCALE

5.2

MODE_BLK.ACTUAL_MODE

11

OUT_SCALE

5.3

MODE_BLK.PERMITTED_MODE

12.1

GRANT_DENY.GRANT

5.4

MODE_BLK.NORMAL_MODE

12.2

GRANT_DENY.DENY

BLOCK_ERR

17

BYPASS

PV

21

SP_HI_LIM

SP

22

SP_LO_LIM

OUT

28

OUT_HI_LIM

18

CAS_IN

29

OUT_LO_LIM

38

TRK_IN_D

39

TRK_VAL

45.1

ALARM_SUM.CURRENT

45.2

ALARM_SUM.UNACKNOWLEDGED

45.3

ALARM_SUM.UNREPORTED

45.4

ALARM_SUM.DISABLED

141

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012

Table 435. PID Function Block, View 3


Index Number
1

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

PV

SP

OUT

15

IN

18

CAS_IN

27

BKCAL_IN

31

BKCAL_OUT

32

RCAS_IN

33

ROUT_IN

35

RCAS_OUT

36

ROUT_OUT

38

TRK_IN_D

39

TRK_VAL

40

FF_VAL

45.1

ALARM_SUM.CURRENT

45.2

ALARM_SUM.UNACKNOWLEDGED

45.3

ALARM_SUM.UNREPORTED

45.4

ALARM_SUM.DISABLED

67

ERROR

68

SP_WORK

71

STRUCTURECONFIG

75

STDDEV

76

CAP_STDDEV

Table 436. PID Function Block, View 4.1


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

13

CONTROL_OPTS

14

STATUS_OPTS

16

PV_FTIME

19

SP_RATE_DN

20

SP_RATE_UP

23

GAIN

24

RESET

25

BAL_TIME

26

RATE

30

BKCAL_HYS

34

SHED_OPT

37

TRK_SCALE

41

FF_SCALE

42

FF_GAIN

46

ACK_OPTION

47

ALARM_HYS

48

HI_HI_PRI

49

HI_HI_LIM

50

HI_PRI

51

HI_LIM

52

LO_PRI

53

LO_LIM

54

LO_LO_PRI

55

LO_LO_LIM

56

DV_HI_PRI

57

DV_HI_LIM

58

DV_LO_PRI

59

DV_LO_LIM

Table 437. PID Function Block, View 4.2


Index Number

Note
Because individual views are limited in size, View List 4 has
two parts.

142

Parameter

ST_REV

66

BIAS

69

SP_FTIME

70

MATHFORM

71

STRUCTURECONFIG

72

GAMMA (ugamma)

73

BETA

74

IDEADBAND

Instruction Manual

Detailed SetupPID Function Block

D103412X012

August 2012

Field Communicator Menu Structure


PID FUNCTION BLOCK
Quick Config
Alert Key
Control Options
Deviation High Limit
Deviation Low Limit
Gain
High High Limit
High Limit
Low Limit
Low Low Limit
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Reset
Setpoint: Status
Setpoint: Value
Setpoint High Limit
Setpoint Low Limit
Common Config
Alarm Hysteresis
Alert Key
Control Options
Deviation High Limit
Deviation Low Limit
Gain
High High Limit
High Limit
Low Limit
Low Low Limit
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output High Limit
Output Low Limit
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Process Value Filter Time
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Rate
Reset
Setpoint: Status
Setpoint: Value
Setpoint High Limit
Setpoint Low Limit

Advanced Config
Back Calculation Hysteresis
Feed Forward Gain
Feed Forward Scale: EU at 100%
Feed Forward Scale: EU at 0%
Feed Forward Scale: Units Index
Feed Forward Scale: Decimal
Shed Options
Setpoint Rate Down
Setpoint Rate Up
Static Revision
Status Options
Strategy
Tracking Scale: EU at 100%
Tracking Scale: EU at 0%
Tracking Scale: Units Index
Tracking Scale: Decimal
Tracking Value: Status
Tracking Value: Value
Connectors
Back Calculation Input: Status
Back Calculation Intput: Value
Back Calculation Output: Status
Back Calculation Output: Value
Cascade Input: Status
Cascade Input: Value
Feed Forward Value: Status
Feed Forward Value: Value
Input: Status
Input: Value
Output: Status
Ouput: Value
Tracking Input Discrete: Status
Tracking Input Descrete: Value
Tracking Value: Status
Tracking Value: Value

Online

Back Calculation Input: Status


Back Calculation Intput: Value
Back Calculation Output: Status
Back Calculation Output: Value
Block Error
Bypass
Cascade Input: Status
Cascade Input: Value
Feed Forward Value: Status
Feed Forward Value: Value
Gain
Input: Status
Input: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output: Status
Output: Value
Process Value: Status
Process Value: Value
Remote Cascade Input: Status
Remote Cascade Input: Value
Remote Cascade Output: Status
Remote Cascade Output: Value
Remote Out Input: Status
Remote Out Input: Value
Remote Out Output: Status
Remote Out Output: Value
Setpoint: Status
Setpoint: Value
Tracking Input Discrete: Status
Tracking Input Descrete: Value
Tracking Value: Status
Tracking Value: Value

Status
Block Error

(menu continued on next page)

143

Instruction Manual

Detailed SetupPID Function Block


August 2012

D103412X012
All

PID FUNCTION BLOCK cont.


Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Balance Time
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
High Alarm: Unacknowledged
High Alarm: Alarm State
High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Deviation High Alarm: Unacknowledged
Deviation High Alarm: Alarm State
Deviation High Alarm: Time Stamp
Deviation High Alarm: Subcode
Deviation High Alarm: Float Value
Deviation Low Alarm: Unacknowledged
Deviation Low Alarm: Alarm State
Deviation Low Alarm: Time Stamp
Deviation Low Alarm: Subcode
Deviation Low Alarm: Float Value
Bias

144

Other
(continued)
Error
SP Work
SP FTime
mathform
structureconfig
Ugamma
UBeta
IDeadBand
StdDv
Cap StdDev
T Request
T State
T Status
T Ipgain
T Ugain
T Uperiod
T Psgain
T Ptimec
T Pdtime
T Targetop
T Hyster
T Relayss
T Gain Magnifier
T Auto Extra DT
T Auto Hysteresis
T Aoperiods

Characteristics: Block Tag


Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value: Status
Process Value: Value
Setpoint: Status
Setpoint: Value
Output: Status
Output: Value
Process Value Scale: EU at 100%
Process Value Scale: EU at 0%
Process Value Scale: Units Index
Process Value Scale: Decimal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Grant Deny: Grant
Grant Deny: Deny
Control Options
Status Options
Input: Status
Input: Value
Process Value Filter Time
Bypass
Cascade Input: Status
Cascade Input: Value
Setpoint Rate Down
Setpoint Rate Up
Setpoint High Limit
Setpoint Low Limit
Gain
Reset
Balance Time
Rate
Back Calculation Input: Status
Back Calculation Input: Value
Output High Limit
Output Low Limit
Back Calculation Hysteresis
Back Calculation Output: Status
Back Calculation Output: Value
Remote Cascade Input: Status
Remote Cascade Input: Value
Remote Out Input: Status
Remote Out Input: Value
Shed Options
Remote Cascade Output: Status
Remote Cascade Output: Value
Remote Out Output: Status
Remote Out Output: Value
Tracking Scale: EU at 100%
Tracking Scale EU at 0%
Tracking Scale: Units Index
Tracking Scale: Decimal
Tracking Input Discrete: Status
Tracking Input Descrete: Value
Tracking Value: Status
Tracking Value: Value
Feed Forward Value: Status
Feed Forward Value: Value
Feed Forward Scale: EU at 100%
Feed Forward Scale: EU at 0%
Feed Forward Scale: Units Index
Feed Forward Scale: Decimal
Feed Forward Gain

All (continued)

All (continued)

Updated Event: Unacknowledged


Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Alarm Hysteresis
High High Priority
High High Limit
High Priority
High Limit
Low Priority
Low Limit
Low Low Priority
Low Low Limit
Deviation High Priority
Deviation High Limit
Deviation Low Priority
Deviation Low Limit
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
High Alarm: Unacknowledged
High Alarm: Alarm State
High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Deviation High Alarm: Unacknowledged
Deviation High Alarm: Alarm State
Deviation High Alarm: Time Stamp
Deviation High Alarm: Subcode
Deviation High Alarm: Float Value
Deviation Low Alarm: Unacknowledged
Deviation Low Alarm: Alarm State
Deviation Low Alarm: Time Stamp
Deviation Low Alarm: Subcode
Deviation Low Alarm: Float Value
Bias
Error
SP Work
SP FTime
mathform
structureconfig
UGamma
UBeta
IDeadBand
StdDev

Cap StdDev
T Request
T State
T Status
T Ipgain
T Ugain
T Uperiod
T Psgain
T Ptimec
T Pdtime
T Targetop
T Hyster
T Relayss
T Gain Magnifier
T Auto Extra DT
T Auto Hysteresis
T Aoperiods

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

Input Selector Function Block


Overview
The Input Selector (ISEL) function block (figure 412) can be used to select the first good, maximum, minimum,
average, or hot backup from as many as eight input values and place it at the output. The block supports signal status
propagation. There is no process alarm detection in the Input Selector function block. Figure 413 illustrates the
internal components of the ISEL function block. Table 440 lists the ISEL block parameters, their index numbers, and
descriptions.
Figure 412. Input Selector Function Block

OUT

IN (18)
DISABLE (18)

OUT_D
OP_SELECT

ISEL
SELECTED

SELECTED
OUT
OUT_D

= Input used in the selection algorithm.


= Discrete input used to enable or disable
the associated input channel.
= Input used to override algorithm.
= The selected channel number.
.
= The block output and
status.
= Discrete output that signals
a selected alarm condition.

FIELDBUS_56A

IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
DISABLE_1
DISABLE_2
DISABLE_3
DISABLE_4
DISABLE_5
DISABLE_6
DISABLE_7
DISABLE_8
OP_SELECT

Modes
The ISEL function block supports three modes of operation as defined by the MODE_BLK [5] parameter:
Manual (Man)The block output (OUT [7]) may be entered manually.
Automatic (Auto)OUT [7] reflects the selected input value.
Out of Service (OOS)The block is not processed. The BLOCK_ERR [6] parameter shows Out of Service. In this
mode, you can make changes to all configurable parameters. The target mode of a block may be restricted to one
or more of the supported modes.
The Input Selector block Actual mode will be Out of Service if any of the following are true:
The Actual mode of the resource block is not Auto
The Input Selector block Target mode is Out of Service

145

Instruction Manual

Detailed SetupISEL Function Block


August 2012

D103412X012

The Input Selector block Target mode is Auto, OP_SELECT [22] is not being used, and SELECT_TYPE [19] is 0. In this
case, the BLOCK_ERR [6] parameter shows a Block Configuration Error.
The Input Selector block Actual mode will be Manual if all of the above is not true and the Target mode is Manual.
Figure 413. Input Selector Function Block Schematic
IN_1
IN_2
IN_3

AUTO

Selection
Algorithm

IN_4

OUT
MAN

DISABLE_1
SELECTED

DISABLE_2

DISABLE_4

OP_SELECT

SEL_TYPE

MIN_GOOD

fieldbusfbus_229a

DISABLE_3

SELECT_TYPE
NOTE: THIS FIGURE DOES NOT INCLUDE THE ADDITIONAL
4 INPUTS IN THE EXTENDED PARAMETERS.

Status Handling
Quality Use and Propagation
In Auto mode, OUT [7] reflects the value and status of the selected input based on the following criteria:
A bad or disabled input is never used by any of the selection algorithms
For a selection algorithm to use an input with status of Uncertain, the STATUS_OPTS [10] parameter must have
Use Uncertain as Good.
STATUS_OPTS [10] is applied before selection.
If the number of good inputs is less than MIN_GOOD [20], or if the number of inputs evaluated is 0, the status of
OUT [7] and SELECTED [21] will be Bad.
If an input is disabled or its status is Bad and is selected via OP_SELECT [22], then the status of OUT [7] and
SELECTED [21] will be Bad. If the quality of the input is Uncertain, and the selection for the STATUS_OPTS [10]
parameter is Use Uncertain as Good, then the status of OUT [7] and SELECTED [21] will be Uncertain. Otherwise
the status of OUT [7] and SELECTED [21] will be Good Noncascade.

146

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

When the block is in the Manual mode the status and substatus of OUT [7] and SELECTED [21] will be as follows:
Substatus will be nonspecific and the limit will be constant.
Quality of OUT [7] and SELECTED [21] will be Uncertain if STATUS_OPTS [10] is Uncertain if in Manual mode.
Otherwise, the quality of OUT [7] and SELECTED [21] will be Good Noncascade.

Limit Propagation
Refer to figure 414. When SELECT_TYPE [19] is Average, Not Limited is propagated unless all inputs have the same
limit status. If ll inputs have the same limit status, the limit status of the inputs is propagated.
If SELECT_TYPE [19] is Middle and the number of inputs used by the algorithm is greater than one: Not Limited is
propagated unless all selected inputs have the same limit status, in which case the limit status of the inputs is
propagated.
If SELECT_TYPE [19] is Middle and a single input, or if Maximum or Minimum then: If the selected input is a constant
and Middle, Constant is propagated. Otherwise, if the selected input is a constant and Maximum or Minimum,
propagate low if Maximum, propagate high if Minimum. If the selected input is not a constant, propagate selected
input limit as is.
When SELECT_TYPE [19] is First Good or Hot Spare or if OP_SELECT [22] is nonzero, propagate selected input limit as
is.

Substatus Propagation
Refer to figure 415. For SELECT_TYPE [19] of Maximum, Minimum, First Good, Hot Spare, and Middle with only one
input, simply propagate substatus as is.
For SELECT_TYPE [19] of Maximum and Minimum with more than one input with the same value, propagate substatus
if all inputs are the same.
For SELECT_TYPE [19] of Average or Middle with more than one input, propagate NonSpecific.
If the status of OUT [7] is Bad, then the substatus will be as follows:
Out of Service if the Target mode is Out of Service.
Configuration Error with a BLOCK_ERR [6] of Configuration Error if the Actual mode is Out of Service.
Otherwise a substatus of NonSpecific.

147

Instruction Manual

Detailed SetupISEL Function Block


August 2012

D103412X012

Figure 414. Input Selector Block Limit Propagation


START

Propagate
selected input
limit status

No

OP_SELECT
equal to zero?

Yes

SELECT_TYPE
Average?

Yes

All inputs with


same limit
status?

Yes

No

No

Propagate
Not Limited

Yes
SELECT_TYPE
Middle?

More than 1
input?

Yes

No

No

All inputs with


same limit
status?

Yes

Propagate that
limit status

No

Propagate
Not Limited

Input a
constant?

Yes

Propagate
Constant

No

SELECT_TYPE
Maximum?

Yes

Yes

Propagate
Low Limit

Yes

Propagate
High Limit

No

No

SELECT_TYPE
Minimum?

Input a
constant?

Yes

No

No

SELECT_TYPE
First Good or Hot
Spare?

Input a
constant?

Yes

Propagate
selected input
limit status

No

Illegal Select Type


should never be reached

148

NOTES:
1
LIMIT
MANIPULATION FOR A CONSTANT INPUT FOR MAXIMUM AND MINIMUM IS BASED
UPON THE FOUNDATION FIELDBUS SPECIFICATION. THE REASONING IS BASED ON HIGH SELECT
PROVIDING A LOW LIMIT STATUS AND LOW SELECT PROVIDING A HIGH LIMIT STATUS.

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

Figure 415. Input Selector Block Substatus Propagation


START

Yes

MODE_BLK
OOS?

Propagate Bad,
Out of Service

No

STATUS_OPTS Un
certain if Man
Mode?

Yes

MODE_BLK
MAN?

No

Yes

Propagate
Uncertain

No
Propagate Good
Noncascade

MODE_BLK must
be Auto

1
OP_SELECT
status?

Bad

Propagate Bad,
Nonspecific

Good

1
OP_SELECT
value >0?

Yes

Propagate Good
Noncascade

Bad

No

At least 1 good
input?

Good

Selected in
put status?

No

Propagate Bad,
Nonspecific

Yes

SELECT_TYPE
Middle or
Average?

Yes

One input?

Multiple
Inputs

No

SELECT_TYPE
Maximum or
Minimum?

Yes

Yes

One input?

Propagate
Nonspecific

Yes

Multiple
Inputs

No

All inputs with


same value?
SELECT_TYPE Must
be First Good or
Hot Spare?

Yes

Propagate input
substatus as is

Propagate input
substatus as is

No
Propagate
Nonspecific

No
Illegal Select Type
should never be reached

Yes

NOTES:
AN INPUT STATUS MAY BE BAD, GOOD, OR UNCERTAIN. IF BAD, THE INPUT IS NOT USED AND THE STATUS IS PROPAGATED
AS BAD WITH SUBSTATUS NONSPECIFIC. IF GOOD IT IS USED AND THE STATUS IS PROPAGATED AS GOOD
(NONCASCADE). IF UNCERTAIN, AND STATUS_OPTS IS USE UNCERTAIN AS GOOD THEN THE INPUT IS USED AND THE
STATUS IS PROPAGATED AS GOOD (NONCASCADE), OTHERWISE IT IS NOT USED AND THE STATUS IS PROPAGATED AS
BAD WITH SUBSTATUS NONSPECIFIC.

149

Detailed SetupISEL Function Block

Instruction Manual

August 2012

D103412X012

STATUS_OPTS Supported
In the STATUS_OPTS [10] parameter, you can select from the following options to control the status handling:
Use Uncertain as Goodsets the OUT [7] status to Good when the selected input status is Uncertain.
Uncertain if in Manual mode: sets the OUT [7] status to Uncertain when the mode is Manual.

Note
The block mode must be Out of Service to set STATUS_OPTS [10].

Input Selection
The ISEL function block reads the values and statuses of as many as eight inputs (IN_1 [11], IN_2 [12], IN_3 [13], IN_4
[14], IN_5 [25], IN_6 [26], IN_7 [27], IN_8 [28]). To use any of the six selection algorithms to select the output,
OP_SELECT [22] must be 0. To specify which algorithm to use, configure the selector type parameter (SELECT_TYPE
[19]) as follows:
Maximumselects the input with the highest value from the inputs that are not bad and not disabled.
Minimumselects the input with the lowest value from the inputs that are not bad and not disabled.
Averagecalculates the average value of the inputs that are not bad and not disabled and provides it as the output.
For example, if the number used to average (AVG_USE [33]) is 4 and the number of connected inputs is 6, then the
highest and lowest values would be dropped prior to calculating the average. If AVG_USE [33] is 2 and the number
of connected inputs is 7, then the two highest and lowest values would be dropped prior to calculating the average
and the average would be based on the middle three inputs.
MiddleIf the number of good usable inputs is odd, then it selects the middle value. If the number of good usable
inputs is even, then it averages the middle two values and selects status as worst of two. If both inputs' limit status
are not the same then it sets limit status of Not Limited.
First Goodselects the first input that is not bad and not disabled, starting with IN_1 [11].
Hot Spareinitially uses the input selected as first good. If the selected input goes bad, the first good selection is
repeated. If the selected input remains good, it stays selected. If the originally selected input returns to good status
the selection does not change. Selection changes only if the currently selected input goes bad.

Disabling Inputs
Use the parameters DISABLE_1 [15], DISABLE_2 [16], DISABLE_3 [17], DISABLE_4 [18], DISABLE_5 [29], DISABLE_6
[30], DISABLE_7 [31] and DISABLE_8 [32] to disable the corresponding inputs. An input that is disabled will not be used
by any of the selection algorithms.
The status of the disable parameter must be Good, Good_Cascade, or Uncertain with a STATUS_OPTS [10] of
Use Uncertain as Good in order to be evaluated. If the status of the disable parameter is Bad, its last usable value is
maintained and acted upon. If the device restarts, losing the last usable value, the last usable value is set to disabled.

150

Instruction Manual
D103412X012

Detailed SetupISEL Function Block


August 2012

IN_1 through IN_8 and DISABLE_1 through DISABLE_8 are nonvolatile type parameters so if they are Linked they will
automatically have Bad status until connections are reestablished. If they are not Linked, they will be restored with the
previous value from NVM across device restarts.

Direct Selection of Inputs


The parameter OP_SELECT [22] can be used to select a particular input. If OP_SELECT [22] is nonzero, the selection
algorithm is bypassed and the value of OP_SELECT [22] is interpreted as the input number to select. If the OP_SELECT
[22] value is greater than the number of inputs, then the highest input is selected. The status of OP_SELECT [22] must
be Good, Good_Cascade, or Uncertain with a STATUS_OPTS [10] of Use Uncertain as Good in order to be
evaluated. If the status of OP_SELECT [22] is Bad, then the OUT [7] status is Bad.

Identification of Selected Inputs


For a SELECT_TYPE [19] of Maximum, Minimum, Middle, First Good, and Hot Spare, SELECTED [21] indicates the
number of the selected input. When Middle is computed from more than one input, SELECTED [21] is set to 0.
For a SELECT_TYPE [19] of Average, SELECTED [21] indicates the number of inputs used in the average calculation.
When the block mode is Manual, SELECTED [21] is set to 0.

Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block error for the PID
block are defined above.
Process alarm detection is based on OUT [7] value. You can configure the alarm limits of the following standard
alarms:
High (HI_LIM [40])
High high (HI_HI_LIM [38])
Low (LO_LIM [42])
Low low (LO_LO_LIM [44])
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent
of the PV span can be set using the ALARM_HYS [36] parameter. The priority of each alarm is set in the following
parameters:
HI_PRI [39]
HI_HI_PRI [37]
LO_PRI [41]
LO_LO_PRI [43]
ACK_OPTION [35] is used to set automatic acknowledgement of alarms.
ALARM_SUM [34] indicates the current alert status, unacknowledged states, and disabled states of the alarms
associated with the function block.

151

Instruction Manual

Detailed SetupISEL Function Block


August 2012

D103412X012

Alarms are grouped into five levels of priority, as shown in table 438.
Table 438. ISEL Function Block Alarm Priorities
Priority Description(1)

Priority Number
0

The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected.

An alarm condition with a priority of 1 can be recognized by the system. The device monitors the alarm but does not report it
until requested by the host system.

An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
diagnostics and system alerts).

3-7

Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.

8-15

Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.

1. The priority classes advise and critical have no relationship to Plant Web Alerts.

Block Errors
Table 439 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the
ISEL block and are provided only for your reference.
Table 439. BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other (N/A)

Block Configuration Error If OP_SELECT is not being used, and SELECT_TYPE = 0. This implies OP_SELECT status is good and actual
mode is AUTO.

Link Configuration Error (N/A)

Simulate Active (N/A)

Local Override (N/A)

Device Fault State Set (N/A)

Device Needs Maintenance Soon (N/A)

Input failure/process variable has Bad status Set if any IN or any DISABLE or OP_SELECT is bad and connected. This means that a
status of BAD NC would not cause an input failure but a status of BAD LUV or BAD no LUV would cause and input failure.

Output failure Set if OUT quality is bad and the Actual mode is not Out of Service.

Memory Failure (N/A)

10

Lost Static Data (N/A)

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now (N/A)

14

Power Up Set if the Target mode is Out of Service when powered up until the mode is changed.

15

Out of Service The block is in Out of Service (OOS) mode

ISEL Function Block Parameter List (table 440)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentations and shaded Index Numbers indicate subparameters

152

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

Table 440. Input Selector Function Block Parameter Definitions


Label
PARAMETER_NAME

Index
Number

RO / RW

Block
Mode

Range

Initial
Value

Description

Static Revision
ST_REV

RO

N/A

0 to 65535

Data Type: Unsigned16


The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.

Tag Description
TAG_DESC

RW

ALL

7 bit ASCII

spaces

Data Type: Octet String


The user description of the intended application of the
block.

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.

Alert Key
ALERT_KEY

RW

ALL

1 to 255

Data Type: Unsigned8


The identification number of the plant unit. This
information may be used in the host for sorting alarms,
etc.

Block Mode
MODE_BLK

TARGET

5.1

RW

ALL

ACTUAL

5.2

RO

ALL

PERMITTED

5.3

RW

ALL

NORMAL

5.4

RW

ALL

Block Error
BLOCK_ERR

Output
OUT

Output Range
OUT_RANGE

Grant Deny
GRANT_DENY

RO

N/A

MAN
OOS

ALL

GRANT

9.1

ALL

DENY

9.2

ALL

Status Options
STATUS_OPTS

Input 1
IN_1

Input 2
IN_2

10

11

12

OOS

ALL

ALL

OOS, MAN, AUTO

OOS until
block is
configured,
then last
valid target

OOS+MAN+AUTO

OOS+MAN
+AUTO

Data Type: DS69


Valid Bits: 7: OOS, 4: MAN,
3: AUTO
The actual, target, permitted, and normal modes of the
block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

AUTO
1: Block
Configuration Error
7: Input Failure / Bad
PV status
8: Output Failure
14: Power Up
15: OutofService
Status
OUT_RANGE

Dynamic

Data Type: Bit String


0=Inactive
1=Active
This parameter reflects the error status associated with
the hardware or software components associated with
a block. It is a bit string, so that multiple errors may be
shown.

Dynamic

Data Type: DS65


The block output value and status.

Value
EU at 100%
EU at 0%
Units Index
Decimal Point

0: Program
1: Tune
2: Alarm
3: Local

100
0
%
2

All bits: 0
All bits:0

2: Use Uncertain as
GOOD
8: Uncertain if MAN

All bits: 0

Status

BAD
NC
constant

Value

Status

BAD
NC
constant

Value

Data Type: DS67


High and low scale values, engineering units code, and
number of digits to the right of the decimal point
associated with OUT.
Data Type: DS70
Options for controlling access of host computers and
local control panels to operating, tuning, and alarm
parameters of the block. Not used by device.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied
Data Type: Bit String
Allows you to select options for status handling and
processing. The supported status option for the input
selector block is: Use Uncertain as Good, Uncertain
if Man mode.
Data Type: DS65
The block input value and status.

Data Type: DS65


The block input value and status.

0
-Continued-

153

Instruction Manual

Detailed SetupISEL Function Block


August 2012

D103412X012

Table 440. Input Selector Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Input 3
IN_3

Input 4
IN_4

Disable Analog Input 1


DISABLE_1

Index
Number

RO / RW

13

Block
Mode
ALL

14

ALL

15

ALL

Range

BAD
NC
constant

Status
Value

Status

BAD
NC
constant

Value

Status

BAD
NC
constant

Value
0=Use
1=Disable

16

ALL

Value
0=Use
1=Disable

17

ALL

Value
0=Use
1=Disable

18

ALL

Data Type: DS66


Enable/Disable for Input_2, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

Data Type: DS66


Enable/Disable for Input_3, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

Data Type: DS66


Enable/Disable for Input_4, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

Data Type: Unsigned8


The minimum number of inputs which are good is
less than the value of MIN_GOOD then set the OUT
status to bad.

Min Good
MIN_GOOD

20

ALL

1-4
0 initial value only

Selected
SELECTED

21

Status
Value
0-8

Dynamic

Data Type: DS66


The integer indicating the selected input number.

Status

BAD
NC
constant

Data Type: DS66


An operator settable parameter to force a given input
to be used.

Value
0-8

ALL

-Continued-

154

Data Type: DS66


Enable/Disable for Input_1, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

Data Type: Unsigned8


Determines the selector action

ALL

22

Data Type: DS65


The block input value and status.

19

N/A

Data Type: DS65


The block input value and status.

Select Type
SELECT_TYPE

RO

Description

Value
0=Use
1=Disable
1=First Good
2=Minimum
3=Maximum
4=Middle
5=Average
6=Hot Spare

Operator Select
OP_SELECT

0
BAD
NC
constant

Status
Disable Analog Input 4
DISABLE_4

0
BAD
NC
constant

Status
Disable Analog Input 3
DISABLE_3

0
BAD
NC
constant

Status
Disable Analog Input 2
DISABLE_2

Initial
Value

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

Table 440. Input Selector Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Update Event
UPDATE_EVT
UNACKNOWLEDGED

Index
Number

RO / RW

Block
Mode

Range

Initial
Value

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined
1=Update Reported
2=Updated not
reported

23
23.1

RW

UPDATE_STATE

23.2

RO

N/A

TIME_STAMP

23.3

RO

N/A

STATIC_REVISION

23.4

RO

N/A

RELATIVE_INDEX

23.5

RO

N/A

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

Description

Data Type: DS73


This alert is generated by any change to the static data.

24
24.1

ALARM_STATE

24.2

RO

N/A

TIME_STAMP

24.3

RO

N/A

SUBCODE

24.4

RO

N/A

VALUE

24.5

RO

N/A

Data Type: DS72


The block alarm is used for all configuration, hardware,
connection failure, or system problems in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the active
status in BLOCK_ERR. As soon as the Unreported status
is cleared by the alert reporting task, another block
alert may be reported without clearing the Active
status, if the subcode has changed.

Extended Parameters
In 5
IN_5

In 6
IN_6

In 7
IN_7

25

26

27

ALL

ALL

ALL

BAD
NC
constant

Status
Value

Status

BAD
NC
constant

Data Type: DS65


Input value and status.

Data Type: DS65


Input value and status.

Value

Status

BAD
NC
constant

Data Type: DS65


Input value and status.

BAD
NC
constant

Data Type: DS65


Input value and status.

Value
In 8
IN_8

Disable Analog Input 5


DISABLE_5

28

29

ALL

ALL

Status
Value

Status

BAD
NC
constant

Value
0=Use
1=Disable

BAD
NC
constant
0

Status
Disable Analog Input 6
DISABLE_6

30

ALL
Value
0=Use
1=Disable

Data Type: DS66


Enable/Disable for Input_5, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

Data Type: DS66


Enable/Disable for Input_6, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

-Continued-

155

Instruction Manual

Detailed SetupISEL Function Block


August 2012

D103412X012

Table 440. Input Selector Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO / RW

Block
Mode

Range

BAD
NC
constant

Value
Disable Analog Input 7
DISABLE_7

31

ALL

Status
0=Use
1=Disable

Number used to average


AVG_USE
Alarm Summary
ALARM_SUM

32

ALL

33

0
BAD
NC
constant

Value
Disable Analog Input 8
DISABLE_8

Initial
Value

Status
0=Use
1=Disable
1 to 8

Description
Data Type: DS66
Enable/Disable for Input_7, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.

Data Type: DS66


Enable/Disable for Input_8, If parameter is TRUE then
input is disabled. If parameter status is BAD it is not
evaluated.
Data Type: Unsigned8
Number used to average the output. The number of
min and max dropped is the number of inputs minus
AVG_USE.

34

CURRENT

34.1

RO

NA

UNACKNOWLEDGED

34.2

RO

NA

UNREPORTED

34.3

RO

NA

DISABLED

34.4

RW

ALL

Data Type: DS74


Current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.

1: Hi Hi
2: Hi
3: Lo Lo
4: Lo

Data Type: Bit String


Selection of whether alarms associated with the block
will be automatically acknowledged.
0=Disable
1=Enable

ALL

1: Hi Hi
2: Hi
3: Lo Lo
4: Lo

36

ALL

0 to 50%

0.50%

High High Priority


HI_HI_PRI

37

ALL

0 TO 15

Data Type: Unsigned8


Priority of the alarm

High High Limit


HI_HI_LIM

38

ALL

Data Type: Float


Value of analog input which will generate an alarm

High Priority
HI_PRI

39

ALL

Data Type: Unsigned8


Priority of the alarm

High Limit
HI_LIM

40

ALL

Data Type: Float


Value of analog input which will generate an alarm

Low Priority
LO_PRI

41

ALL

Data Type: Unsigned8


Priority of the alarm

Low Limit
LO_LIM

42

ALL

Data Type: Float


Value of analog input which will generate an alarm

Low Low Priority


LO_LO_PRI

43

ALL

Data Type: Unsigned8


Priority of the alarm

Low Low Limit


LO_LO_LIM

44

ALL

Data Type: Float


Value of analog input which will generate an alarm

High High Alarm


HI_HI_ALM

45

Acknowledge Option
ACK_OPTION

35

Alarm Hysteresis
ALARM_HYS

UNACKNOWLEDGED

45.1

RW

0 TO 15

0 TO 15

0 TO 15

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported

156

ALARM_STATE

45.2

RO

N/A

TIME_STAMP

45.3

RO

N/A

SUBCODE

45.4

RO

N/A

VALUE

45.5

RO

N/A

0
-Continued-

Data Type: Float


Hysteresis on alarms

Data Type: DS71


The high high alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

Table 440. Input Selector Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
High Alarm
HI_ALM
UNACKNOWLEDGED

Index
Number

RO / RW

Block
Mode

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported

Range

Initial
Value

46
46.1

ALARM_STATE

46.2

RO

N/A

TIME_STAMP

46.3

RO

N/A

SUBCODE

46.4

RO

N/A

VALUE

46.5

RO

N/A

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported

Low Alarm
LO_ALM
UNACKNOWLEDGED

47.1

47.2

RO

N/A

TIME_STAMP

47.3

RO

N/A

SUBCODE

47.4

RO

N/A

VALUE

47.5

RO

N/A

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not
reported

UNACKNOWLEDGED

Data Type: DS71


The low alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.

48
48.1

ALARM_STATE

48.2

RO

N/A

TIME_STAMP

48.3

RO

N/A

SUBCODE

48.4

RO

N/A

VALUE

48.5

RO

N/A

Output Discrete
OUT_D

Data Type: DS71


The high alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.

47

ALARM_STATE

Low Low Alarm


LO_LO_ALM

Description

49

MAN
OOS

Data Type: DS71


The low low alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of the
alarm.

0
Status

Data Type: DS66


Discrete output to indicate a selected alarm value

Value
0, 1
Status

Alarm Select
ALM_SEL

50

ALL

1: Hi Hi
2: Hi
3: Lo Lo
4: Lo

All bits:0

Data Type: Bit String


Used to select the process alarm conditions that will
cause the OUT_D parameter to be set.

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.

157

Instruction Manual

Detailed SetupISEL Function Block


August 2012

D103412X012

Table 441. ISEL Function Block, View 1

Table 443. ISEL Function Block, View 3

Index Number

Index Number

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

BLOCK_ERR

OUT

OUT

11

IN_1

11

IN_1

12

IN_2

12

IN_2

13

IN_3

13

IN_3

14

IN_4

14

IN_4

15

DISABLE_1

15

DISABLE_1

16

DISABLE_2

16

DISABLE_2

17

DISABLE_3

17

DISABLE_3

18

DISABLE_4

18

DISABLE_4

21

SELECTED

21

SELECTED

22

OP_SELECT

22

OP_SELECT

25

IN_5

25

IN_5

26

IN_6

26

IN_6

27

IN_7

27

IN_7

28

IN_8

28

IN_8

29

DISABLE_5

29

DISABLE_5

30

DISABLE_6

30

DISABLE_6

31

DISABLE_7

31

DISABLE_7

32

DISABLE_8

32

DISABLE_8

34.1

ALARM_SUM.CURRENT

34.1

ALARM_SUM.CURRENT

34.2

ALARM_SUM.UNACKNOWLEDGED

34.2

ALARM_SUM.UNACKNOWLEDGED

34.3

ALARM_SUM.UNREPORTED

34.3

ALARM_SUM.UNREPORTED

34.4

ALARM_SUM.DISABLED

34.4

ALARM_SUM.DISABLED

49

Table 442. ISEL Function Block, View 2


Index Number

158

Parameter
ST_REV

Parameter

ST_REV

OUT_RANGE

9.1

GRANT_DENY.GRANT

9.2

GRANT_DENY.DENY

OUT_D

Table 444. ISEL Function Block, View 4


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

10

STATUS_OPTS

19

SELECT_TYPE

20

MIN_GOOD

33

AVG_USE

35

ACK_OPTION

36

ALARM_HYS

37

HI_HI_PRI

38

HI_HI_LIM

39

HI_PRI

40

HI_LIM

41

LO_PRI

42

LO_LIM

43

LO_LO_PRI

44

LO_LO_LIM

50

ALM_SEL

Instruction Manual

Detailed SetupISEL Function Block

D103412X012

August 2012

Field Communicator Menu Structure


INPUT SELECTOR FUNCTION BLOCK
Quick Config
Alert Key
Min Good
Output Range: EU at 100%
Output Range: EU at 0%
Output Range: Units Index
Output Range: Decimal
Select Type
Common Config
Min Good
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Range: EU at 100%
Output Range: EU at 0%
Output Range: Units Index
Output Range: Decimal
Select Type
Advanced Config
Alert Key
Static Revision
Status Options
Strategy

Online
Block Error
Disable Analog Input 1: Status
Disable Analog Input 1: Value
Disable Analog Input 2: Status
Disable Analog Input 2: Value
Disable Analog Input 3: Status
Disable Analog Input 3: Value
Disable Analog Input 4: Status
Disable Analog Input 4: Value
Input 1: Status
Input 1: Value
Input 2: Status
Input 2: Value
Input 3: Status
Input 3: Value
Input 4: Status
Input 4: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Operator Selected: Status
Operator Selected: Value
Output: Status
Output: Value
Selected: Status
Selected: Value
Status

Connectors
Block Error
Disable Analog Input 1: Status
Disable Analog Input 1: Value
Disable Analog Input 2: Status
Disable Analog Input 2: Value
Disable Analog Input 3: Status
Disable Analog Input 3: Value
Disable Analog Input 4: Status
Disable Analog Input 4 : Value
Input 1: Status
Input 1: Value
Input 2: Status
Input 2: Value
Input 3: Status
Input 3: Value
Input 4: Status
Input 4: Value
Operator Select: Status
Operator Select: Value
Output: Status
Output: Value
Selected: Status
Selected: Value

All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Output: Status
Output: Value
Output Range: EU at 100%
Output Range: EU at 0%
Output Range: Units Index
Output Range: Decimal
Grant Deny: Grant
Grant Deny: Deny
Status Options
Input 1: Status
Input 1: Value
Input 2: Status
Input 2: Value
Input 3: Status
Input 3: Value
Input 4: Status
Input 4: Value
Disable Analog Input 1: Status
Disable Analog Input 1: Value
Disable Analog Input 2: Status
Disable Analog Input 2: Value
Disable Analog Input 3: Status
Disable Analog Input 3: Value
Disable Analog Input 4: Status
Disable Analog Input 4: Value
Select Type
Min Good
Selected: Status
Selected: Value
Operator Select: Status
Operator Select: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Analog Input 5: Status
Analog Input 5: Value
Analog Input 6: Status
Analog Input 6: Value
Analog Input 7: Status
Analog Input 7: Value
Analog Input 8: Status
Analog Input 8: Value
Disable Analog Input 5: Status
Disable Analog Input 5: Value
Disable Analog Input 6: Status
Disable Analog Input 6: Value
Disable Analog Input 7: Status
Disable Analog Input 7: Value
Disable Analog Input 8: Status
Disable Analog Input 8: Value
Number Used to average

All continued
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Alarm Hysteresis
High High Priority
High High Limit
High Priority
High Limit
Low Priority
Low Limit
Low Low Priority
Low Low Limit
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
High Alarm: Unacknowledged
High Alarm: Alarm State
High High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Alarm Output: Status
Alarm Output: Value
Alarm Select

159

Instruction Manual

Detailed SetupOS Function Block


August 2012

D103412X012

Output Splitter Function Block


Overview
The Output Splitter (OS) block (figure 416) provides the capability to drive two control outputs from a single input.
Each output is a linear function of some portion of the input. Back calculation support is provided using the same linear
function in reverse. Cascade initialization is supported by a decision table for combinations of input and output
conditions.
Figure 416. Output Splitter (OS) Function Block

OS
RCAS IN
CAS IN

OUT 1

OUT 2

This block is normally used in split ranging or sequencing of multiple valve applications. A typical split range
application has both valves closed when the splitter input is 50%. One valve opens fully as the input drops to 0%. The
other valve opens as the input rises above 50%.
A typical sequencing application has both valves closed at 0% input. One valve fully opens as the input rises to 50% and
the other stays shut. The second valve opens as the input rises above 50%, and the first valve may remain open or shut
off quickly.
Because this block is in the control path, it is able to pass limit and cascade initialization information back to the
upstream block. Table 448 lists the OS block parameters and their descriptions, units of measure, and index numbers.
Figures 417 and 418 illustrate the internal components of the OS function block.

160

Instruction Manual

Detailed SetupOS Function Block

D103412X012

August 2012

Figure 417. Output Splitter Function Block Schematic

IN_ARRAY
OUT_ARRAY
LOCKVAL
RCAS_IN
OUT 1

SP

CAS_IN
Auto

OUT 2

BKCAL_IN_1

RCAS_OUT

BKCAL_IN_2

CAS_OUT

Figure 418. Output Splitter Function Block Schematic Diagram

CAS_IN

F

Setpoint
Limiting SP

"

Setpoint
Rate
Limiting

SP_WRK

"

SP_RATE_DN
SP_RATE_UP

IN_ARRAY
OUT_ARRAY
LOCKVAL

"

Calculate
Ouput

"

BKCAL_OUT

F
F
F

"
"

Balance
Ouput

BAL_TIME

"

BKCAL_IN_2

"

BKCAL_IN_1

"

Shed
Mode

"

"

MODE

"
F

"

Balance
Ouput

"

OUT 1

"

OUT 2

Modes
The Output Splitter function block supports the following actual modes:

161

Detailed SetupOS Function Block

Instruction Manual

August 2012

D103412X012

Out of Service (OOS)The block is not processed. FIELD_VAL and PV are not updated and the OUT status is set to
Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, you can make changes to all
configured parameters.
By using permitted mode the target mode of a block may be restricted to one or more of the following modes: Cas,
Auto or OOS.

Note
The output splitter function block must be in Auto for the mode to go to CAS.

Initialization Manual (IMan)The output path is not complete (for example, the cascade-to-slave path might not be
open). In IMan mode, OUT tracks BKCAL_IN, which allows for bumpless transfer of control.
Automatic (Auto)The block outputs (OUT_1 and OUT_2) reflect the target operating point specified by the
setpoint (SP) parameter.
Cascade (Cas)The SP parameter is set by another function block through a connection to CAS_IN. The SP value is
used to set the OUT parameters automatically. This is the most frequently used mode in this block.
The block's normal mode is Cascade (Cas). You can isolate the block for testing by using Automatic (Auto) mode and
adjusting the setpoint.
When a block attached to an output requests initialization, one of the following actions might occur:
When the other output is not in Cas mode, the block attached to the input is initialized.
When the other output is in Cas mode, this output returns to the value calculated from its slope in a specified time
period.

Status Handling
Substatus value received at CAS_IN [14] is passed to both outputs, except for those used in the cascade handshake.
An IFS goes to both outputs. The status option IFS if Bad CAS_IN is available.
If the Status Option to Propagate failure is set, the block propagates device failure only if both BKCAL_IN show failed
status. Otherwise the upstream cascade would be broken by a failure at either output.
The statuses of OUT_1 [8] and OUT_2 [9] are determined by the statuses of BKCAL_IN_1 and BKCAL_IN_2 and the
actual mode of the block.
When a BKCAL_IN input sees that its downstream block is not in Cas mode, the Splitter function block sets the
corresponding OUT value to the BKCAL_IN value. However, this may not be the same value that is calculated by the
splitter algorithm. When the mode of the downstream block is changed to Cas, the difference between the calculated
output and the backcalculation input is computed and the difference is added to the calculated output. Next, the
difference is reduced to zero over the time defined by the BAL_TIME parameter.
When both BKCAL_IN_1 and BKCAL_IN_2 indicate that the downstream blocks are not in Cas mode or have Bad status,
the first downstream block that goes to Cas mode causes the upstream block to initialize so that there is no difference
between the calculated output and the backcalculation input. This provides bumpless transfer for the first
downstream block.

162

Instruction Manual

Detailed SetupOS Function Block

D103412X012

August 2012

Limit Handling
The splitter function block is designed to combine the limit information from the two downstream blocks into limits
for the upstream block. The general principle is to allow the upstream block to continue control for as long as possible.
The upstream block is highlimited (BKCAL_OUT of the Splitter block has highlimited status) when:
Both downstream blocks are highlimited (both BKCAL_INS of the Splitter block have highlimited status)
or
One downstream block is highlimited, the associated output slope is positive, and the other block has Bad status or
is not in Cas mode
or
One downstream block is lowlimited, the associated output slope is negative, and the other block has Bad status or
is not in Cas mode
or
SP is greater than or equal to X22
The upstream block is lowlimited when:
Both downstream blocks are lowlimited
or
One downstream block is lowlimited, the associated output slope is positive, and the other block has Bad status or
is not in Cas mode
or
One downstream block is highlimited, the associated output slope is negative, and the other block has Bad status
or is not in Cas mode
or
SP is less than or equal to X11

Input to Output Mapping


The relationship of each output to the input may be defined by a line. Each line may be defined by its endpoints.
Examples of graphical representations of OUT_1 and OUT_2 vs. SP are shown in figure 419 for a split range and a
sequencing application.
The block has the same SP structure as the PID block, except that there is no limiting applied to the SP. The SP may be
used in Auto mode for testing. The operator would use the output of the PID to accomplish the same purpose. Each
downstream block can be taken out of cascade if it becomes necessary to gain control of them.
The examples shown in figure 419 do not show the full range of possibilities. The lines could overlap like an X, or both
start from the origin but have different slopes. The endpoints do not have to lie within 0-100%. Limits in the external

163

Instruction Manual

Detailed SetupOS Function Block


August 2012

D103412X012

blocks may effect the useful range of a line. Units of percent are used in the examples because the common
application of this block is to valves, but any units may be used to suit the application.
Figure 419. Split Range and Sequence Operation
Split Range
(X22 , Y22)

100%

Sequencing

(X12 , Y12)

100%

(X11 , Y11)

(X22 , Y22)

OUT_1
OUT_1
OUT_2

OUT_2

0%

(X21 , Y21)

(X12 , Y12)

0%

50%

100%

0%

(X21 , Y21)

(X11 , Y11)

0%

SP

50%

X
100%

SP

The following parameters as paired coordinates are used to specify the output splitter operation:
X11, Y11, X12, Y12
X21, Y21, X22, Y22
Where XnJ is the value of SP associated with OUT_n and Xn1 and Xn2 refer to the 1st and 2nd coordinates of the nth
curve respectively. YnJ is the value of OUT_n and Yn1 and Yn2 refer to the 1st and 2nd coordinates of the nth curve
respectively.
By specifying the coordinates as shown in tables 445 and 446, the endpoints of the lines are defined. The contents of
the respective X's are held in the IN_ARRAY parameter and the contents of the respective Y's are held in the
OUT_ARRAY parameter. If a set of points are specified such that a region of the input range is not specified, then the
corresponding OUT_n will be set to the closest endpoint of the input value, either high or low, when the specified
region is exceeded.
Table 445. IN_ARRAY Coordinates
Index

Coordinate

Table 446. OUT_ARRAY Coordinates


Index

Coordinate

X11 - Start value of SP for the OUT_1 line.


(X11 < X12)

Y11 - Value of OUT_1 at X11

X12 - End value of SP for the OUT_1 line.


(X11 < X12)

Y12 - Value of OUT_1 at X12

Y21 - Value of OUT_2 at X21

Y22 - Value of OUT_2 at X22

X21 - Start value of SP for the OUT_2 line.


(X21 < X22)

X22 - End value of SP for the OUT_2 line.


(X21 < X22)

A configuration error is set in BLOCK_ERR and the actual mode of the block goes to Out of Service if the X values have
any of the following conditions: X21 < X11, X12 < = X11, X22 < = X21.
Refer to figure 420 for an example of LOCKVAL = true, and figure 421 for an example of LOCKVAL = false. The
parameter LOCKVAL provides an option to specify whether OUT_1 remains at its ending level when control is switched

164

Instruction Manual

Detailed SetupOS Function Block

D103412X012

August 2012

to OUT_2, or goes to Y11. If LOCKVAL is true, OUT_1 remains at its ending value when X is greater than X12. If LOCKVAL
is false, then OUT_1 goes to Y11 when X is greater than X12 .
Figure 420. OUT with LOCKVAL True

OUT 2

OUT 1

Figure 421. OUT with LOCKVAL False

OUT 1 remains at
end point when
OUT_2 is nonzero

OUT 1

OUT 2
OUT_1 goes to zero
OUT_2 becomes

0%

50%
SP

0%

100%

50%
SP

100%

Some hysteresis in the switching point may be required because the output may change by a full stroke of the valve.
HYSTVAL [12] contains the amount of hysteresis. If X < = X12-HYSTVAL, OUT_1 may be determined by the calculated
y value. If X12-HYSTVAL < X < X12 and X has not reached X12 since it was less than X12-HYSTVAL, OUT_1 may be
determined by the calculated y value. If X12-HYSTVAL < X < X12 and X has reached X12 since it was less than
X12-HYSTVAL, OUT_1 may be determined by the LOCKVAL setting. If X12 < X, OUT_1 may be determined by the
LOCKVAL setting.

Initialization and Back Calculation Requirements


Refer to figure 422, Output Splitter Configuration, where:
PID1 = Upstream driving controller or function block.
Splitter = Split range function block being described.
AO = Receiver of OUT_1 for 0-50% range of SP
PID2 = Receiver of OUT_2 for 50-100% range of SP

Figure 422. Output Splitter Configuration

BK_CAL_IN
CASIN

PID1

OUT
CASIN

BK_CAL_IN2

Splitter
BK_CAL_IN1

PID2

BK_CAL_OUT

OUT2
BK_CAL_OUT
OUT1

CASIN

AO

BK_CAL_OUT

165

Instruction Manual

Detailed SetupOS Function Block


August 2012

D103412X012

CAS_IN of the Splitter receives the OUT of PID1. BKCAL_IN of PID1 receives BKCAL_OUT of the Splitter. CAS_IN of the
AO receives OUT_1 of the Splitter and PID2 receives OUT_2 of the Splitter. BKCAL_IN_1 of the Splitter receives
BKCAL_OUT of the AO and BKCAL_IN_2 of the Splitter receives BKCAL_OUT of PID2.
The discussion in this section defines the behavior which is used to handle the initial value calculation and status which
can in turn be sent to PID1. This behavior is defined in such a way that no bumps are generated by changing modes,
and that PID1 does not wind up.
The splitter utilizes special handling for cascade initialization because it has two independent outputs. When a
downstream block indicates to the splitter that it wants to initialize, by asserting IR (initialization request) on its
BKCAL_OUT, one of two things happens. Under some circumstances, it is possible to pass an initialization request from
a downstream block back up to the block upstream of the splitter, so that all three blocks balance for bumpless
transfer to cascade mode. Otherwise, the requested splitter output goes to the requested value by placing an internal
offset between that output and the output of the curve, and then ramping that offset to zero in BAL_TIME seconds
after the cascade is made up.
The splitter normally runs with both outputs connected to blocks in cascade mode. If one or both of the blocks is not in
cascade mode, special limiting action is taken. Specifically, if one block indicates that it is not in cascade by NI (not
invited) status on its BKCAL_OUT, then the BKCAL_OUT of the splitter asserts limits at the range extremes of the block
that is still in cascade mode. Even if the upstream controller does not want to operate in that range, there will be no
reset windup when it can move into the range. If both downstream blocks show NI, then the splitter can only wait until
one of them requests cascade initialization. BKCAL_OUT of the splitter can hold the upstream block at the value of the
SP. The actual mode is IMan.
When cascade initialization is requested, by IR substatus on a BKCAL_IN, it is first necessary to determine if the other
BKCAL_IN has NI substatus. If so, the value at the BKCAL_IN asserting IR is taken as the Y value for its curve, and the
resulting X value is sent on BKCAL_OUT to PID1. If the other substatus is OK, then the internal offset and BAL_TIME is
used. If both blocks have IR substatus, then one output is processed until its cascade is closed. The choice is based on
the presence of limit status in BKCAL_IN. If BKCAL_IN_1 is limited, then if BKCAL_IN_2 is not limited then OUT_2 is
processed first, else OUT_1 is processed first.
Cascade initialization is also required when the block transitions from Auto to Cas mode. This action is identical to that
described for the PID block.
The required actions are summarized in table 447.
Table 447. OUT_ARRAY Coordinates
BKCAL_IN_1

BKCAL_IN_2

BKCAL_OUT

Action

NI

NI

NI

Not Specified

NI

OK

OK

BKCAL_OUT limited to X21 low and X22 high

OK

NI

OK

BKCAL_OUT limited to X11 and X12 high

IR

NI

IR

Initialize cascade to value given by curve X1 vs Y1

IR

OK

OK

Initialize OUT_1 using internal offset from Y1

NI

IR

IR

Initialize cascade to value given by curve X2 vs Y2

OK

IR

OK

Initialize OUT_2 using internal offset from Y2

Note 1: OK means the cascade is closed.


Note 2: Recommend using the average of BKCAL_IN_1 and BKCAL_IN_2, or just SP.

The BKCAL_OUT status shows limited high if an increase in SP cannot be effectively passed on to either output because
the BKCAL_IN_n of both outputs indicates that a move in the needed direction is limited. Similarly, limited low is set if
a decrease in SP cannot be effectively passed on to either output. The slope of the limited line(s) affects the limit
direction. BKCAL_OUT also shows limit status at the X extremes X11 and X22.
Initialization is not automatic under all circumstance because some situations have conflicting needs. In general, when
a control region is in trouble, the upstream controller is limited so it will not drive further into that region. When you
want to move to the other active region, you can put the upstream controller into Man mode and move it, or you can

166

Instruction Manual

Detailed SetupOS Function Block

D103412X012

August 2012

drop the good downstream block out of Cas mode for one evaluation cycle and then restore Cas mode. This initializes
the upstream controller to the remaining good region of control.

OS Function Block Parameter List (table 448)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter

Table 448. Output Splitter Function Block Parameter Definitions


Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Initial
Value

Description

Static Revision
ST_REV

RO

N/A

0 to 65535

Data Type: Unsigned16


The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.

Tag Description
TAG_DESC

RW

ALL

7 bit ASCII

Spaces

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned 16:


The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the block.

Alert Key
ALERT_KEY

RW

ALL

1 to 255

Data Type: Unsigned8


The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.

Block Mode
MODE_BLK

5
7:OOS
3:AUTO
2:CAS

OOS until
block
configured,
then last
valid target

OOS+AUTO+CAS

Range

TARGET

5.1

RW

ACTUAL

5.2

RO

OOS
OOS AUTO
CAS

PERMITTED

5.3

RW

NORMAL

5.4

RW

Block Error
BLOCK_ERR

Setpoint
SP

Output 1
OUT_1

Output 2
OUT_2

Output 1 Range
OUT_1_RANGE

10

RO

RO

Data Type: Octet String


The user description of the intended application of the
block.

Data Type: DS69


The actual, target, permitted, and normal modes of the
block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

AUTO+CAS

N/A

1: Block
Configuration Error
7: Input Failure/Bad
PV Status
8: Output Failure
14: Powerup
15: OutofService

Dynamic

Data Type: Bit String


0=Inactive
1=Active
This parameter reflects the error status associated with the
hardware or software components associated with a block.
It is a bit string, so that multiple errors may be shown.

PV_SCALE +/- 10%

Data Type: DS65


Analog setpoint of the block

MAN
OOS

OUT_SCALE
+/- 10%

Data Type: DS65


The primary analog output value calculated as a result of
executing the function (the first output value and status).

MAN
OOS

OUT_SCALE
+/- 10%

Data Type: DS65


The primary analog output value calculated as a result of
executing the function (the second output value and
status).

EU at 100%
EU at 0 %
Unit Index
Decimal Point

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units code, and
number of decimal places to be used in displaying the OUT
value, this parameter has no effect on this block.

-Continued-

167

Instruction Manual

Detailed SetupOS Function Block


August 2012

D103412X012

Table 448. Output Splitter Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

RO /
RW

Output 2 Range
OUT_2_RANGE

11

RO

Grant Deny
GRANT_DENY

12

Block
Mode

EU at 100%
EU at 0 %
Unit Index
Decimal Point

GRANT

12.1

N/A

DENY

12.2

N/A

13

OOS

Status Options
STATUS_OPTS

Cascade Input
CAS_IN

Range

14

Initial
Value

Description

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units code, and
number of decimal places to be used in displaying the OUT
value, this parameter has not effect on this block.

0: Program
1: Tune
2: Alarm
3: Local

All bits: 0

Data Type: DS70


Options for controlling access of host computers and local
control panels to operating, tuning, and alarm parameters
of the block. GRANT:0=N/A, 1=granted
DENY: 0=N/A, 1= denied

1: IFS if BAD CAS_IN

All bits: 0

All bits: 0

Status

BAD:
NC:
const

Value

Data Type: Bit String


0=Disabled 1=Enabled
User option for status
Data Type: DS65
The remote setpoint from another block.
Data Type: DS65
Output value to another block for backwards output
tracking.

Back Calculation Output


BKCAL_OUT

15

Input Array
IN_ARRAY

16

All: 0

Data Type: Float


Used with OUT_ARRAY to map input to output. See Input to
Output Mapping, page 163.

Output Array
OUT_ARRAY

17

All: 0

Data Type: Float


Used with IN_ARRAY to map input to output. See Input to
Output Mapping, page 163.

Lockval
LOCKVAL

18

Back Calculation Input 1


BKCAL_1_IN

19

Back Calculation Input 2


BKCAL_2_IN

RO

Status Limits

0=Undfined
1=no lock
2=lock

BAD:
NC:
const

Status

20

0=
Undefined

Value

Status

BAD:
NC:
const

Value

Positive

Balance Time
BAL_TIME

21

Hystval
HYSTVAL

22

Update Event
UPDATE_EVT

23

RO

N/A

UNACKNOWLEDGED

23.1

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=
Undefined

UPDATE STATE

23.2

RO

N/A

0=Undefined
1=Update Reported
2=Updated not
reported

0=
Undefined

TIME_STAMP

23.3

RO

N/A

STATIC_REVISION

23.4

RO

N/A

RELATIVE_INDEX

23.5

RO

N/A

0
-Continued-

168

Data Type: Enum


Used with OUT_ARRAY to map input to output. See Input to
Output Mapping, page 163.
Data Type: DS65
The value and status reflecting the BKCAL_OUT of the lower
block associated with OUT_1. It is used for initialization and
to prevent windup in upstream blocks.
Data Type: DS65
The value and status reflecting the BKCAL_OUT of the lower
block associated with OUT_2. It is used for initialization and
to prevent windup in upstream blocks.
Data Type: Float
Specifies the time for the internal working value of bias or
ratio to return to the operator set bias or ratio, in seconds.

Data Type: DS73


This alert is generated by any change to the static data.

Instruction Manual

Detailed SetupOS Function Block

D103412X012

August 2012

Table 448. Output Splitter Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Index
Number

Block Alarm
BLOCK_ALM

RO /
RW

Block
Mode

RW

N/A

0: Undefined
1: Acknowledged
2: Unacknowledged
0: Undefined
1: Clear reported
2: Clear not reported
3: Active reported
4: Active not
reported

Range

Initial
Value

Description

24

UNACKNOWLEDGED

24.1

ALARM_STATE

24.2

RO

N/A

TIME_STAMP

24.3

RO

N/A

SUBCODE

24.4

RO

N/A

VALUE

24.5

RO

N/A

Data Type: DS72


The block alarm is used for all configuration, hardware,
connection failure, or system problems in the block. The
cause of the alert is entered in the subcode field.

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 449. OS Function Block, View 1

Table 451. OS Function Block, View 3

Index Number

Index Number

Parameter
ST_REV

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

BLOCK_ERR

SP

SP

OUT_1

OUT_1

OUT_2

OUT_2

14

CAS_IN

14

CAS_IN

15

BKCAL_OUT

19

BKCAL_1_IN

20

BKCAL_2_IN

Table 450. OS Function Block, View 2


Index Number

Parameter

ST_REV

10

OUT_1_RANGE

11

OUT_2_RANGE

12.1

GRANT_DENY.GRANT

12.2

GRANT_DENY.DENY

Table 452. OS Function Block, View 4


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

13

STATUS_OPTS

16

IN_ARRAY

17

OUT_ARRAY

18

LOCKVAL

21

BAL_TIME

169

Detailed SetupOS Function Block


August 2012

Field Communicator Menu Structure


OUTPUT SPLITTER FUNCTION BLOCK
All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Setpoint: Status
Setpoint: Value
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 1 Range: EU at 100%
Output 1 Range: EU at 0%
Output 1 Range: Units Index
Output 1 Range: Decimal
Output 2 Range: EU at 100%
Output 2 Range: EU at 0%
Output 2 Range: Units Index
Output 2 Range: Decimal
Grant Deny: Grant
Grant Deny: Deny
Status Options
Cascade Input: Status
Cascade Input: Value
Back Calculation Output: Status
Back Calculation Output: Value
Input Array[1]
Input Array[2]
Input Array[3]
Input Array[4]
Output Array[1]
Output Array[2]
Output Array[3]
Output Array[4]
Lockval
Back Calculation Input 1: Status
Back Calculation Input 1: Value
Back Calculation Input 2: Status
Back Calculation Input 2: Value
Balance Time
Hystval
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value

170

Instruction Manual
D103412X012

Instruction Manual

Detailed SetupAI Function Block

D103412X012

August 2012

Analog Input Function Block


Overview
The Analog Input (AI) function block (figure 423) processes field device measurements and makes them available to
other function blocks. The output value from the AI block is in engineering units and contains a status indicating the
quality of the measurement. The measuring device may have several measurements or derived values available in
different channels. Use the channel number to define the variable that the AI block processes.
Figure 423. Analog Input (AI) Function Block

OUT

OUT
OUT_D

FIELDBUSFBUS_31A

OUT_D

= THE BLOCK OUTPUT VALUE AND STATUS


= DISCRETE OUTPUT THAT SIGNALS A SELECTED
ALARM CONDITION

The AI block supports alarming, signal scaling, signal filtering, signal status calculation, mode control, and simulation.
In Automatic mode, the block's output parameter (OUT [8]) reflects the process variable (PV [7]) value and status. In
Manual mode, OUT [8] may be set manually. The Manual mode is reflected on the output status. A discrete output
(OUT_D [37]) is provided to indicate whether a selected alarm condition is active. Alarm detection is based on the OUT
[8] value and user specified alarm limits. Figure 424 illustrates the internal components of the AI function block, and
table 457 lists the AI block parameters and their units of measure, descriptions, and index numbers.

Modes
The AI function block supports three modes of operation as defined by the MODE_BLK [5] parameter:
Manual (Man) The block output (OUT [8]) may be set manually.
Automatic (Auto) OUT reflects the analog input measurement or the simulated value when simulation is enabled.
Out of Service (OOS) The block is not processed. FIELD_VAL [19] and PV [7] are not updated and the OUT [8] status
is set to Bad: Out of Service. The BLOCK_ERR [6] parameter shows Out of Service. In this mode, you can make
changes to all configured parameters. The target mode of a block may be restricted to one or more of the
supported modes.

Alarm Detection
A block alarm will be generated whenever the BLOCK_ERR [6] has an error bit set. The types of block errors for the AI
block are defined in table 455.

171

Instruction Manual

Detailed SetupAI Function Block


August 2012

D103412X012

Figure 424. Analog Input Function Block Schematic


ANALOG
MEASUREMENT
ALARM_TYPE

ACCESS
ANALOG
MEAS.

HI_HI_LIM
HI_LIM
LO_LO_LIM
LO_LIM

CHANNEL

ALARM
DETECTION

OUT_D

ALARM_HYS
LOW_CUT

SIMULATE

L_TYPE

FIELD_VAL

PV

FILTER

PV_FTIME
IO_OPTS

STATUS
CALC.

OUT

MODE

FIELDBUSFBUS_02A

CUTOFF

CONVERT

STATUS_OPTS

OUT_SCALE
XD_SCALE
NOTES:
OUT_D = BLOCK OUTPUT VALUE AND STATUS
OUT_D = DISCRETE OUTPUT THAT SIGNALS A SELECTED ALARM CONDITION.

Process Alarm detection is based on the OUT [8] value. You can configure the alarm limits of the following standard
alarms:
High (HI_LIM [28])
High high (HI_HI_LIM [26])
Low (LO_LIM [30])
Low low (LO_LO_LIM [32])
In order to avoid alarm chattering when the variable is oscillating around the alarm limit, an alarm hysteresis in percent
of the PV [7] span can be set using the ALARM_HYS [24] parameter. The priority of each alarm is set in the following
parameters:
HI_PRI [27]
HI_HI_PRI [25]
LO_PRI [29]
LO_LO_PRI [31]
Alarms are grouped into five levels of priority, as shown in table 453.
Table 453. AI Function Block Alarm Priorities
Priority Description(1)

Priority Number
0

The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected.

An alarm condition with a priority of 1 is recognized by the system, but is not reported to the operator.

An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
diagnostics and system alerts).

3-7

Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.

8-15

Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.

1. The priority classes advise and critical have no relationship to PlantWeb Alerts.

172

Instruction Manual

Detailed SetupAI Function Block

D103412X012

August 2012

Table 454. Channel Selections for the Analog Input Function Block
Parameter(1)

Channel

Block

Index Number

XD_SCALE Units

TRAVEL_TARGET

TB

49

% (1342)

FINAL_POSITION_VALUE

TB

17

% (1342)

TRAVEL

TB

34

% (1342)

SUPPLY_PRESS

TB

35

psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)

PRESSURE_A

TB

36

psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)

PRESSURE_B

TB

37

psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)

PRESSURE_DIFF

TB

38

psig (1143), bar (1137), kPa (1133), inHg (1155), inH20 (1146), kg/cm2 (1145)

DRIVE_SIGNAL

TB

53

% (1342)

10

TRAVEL_DEVIATION

TB

52

% (1342)

11

TEMPERATURE

TB

48

C (1001), F (1002)

12

CYCLE_COUNT

TB

73

no units (1588)

13

TRAVEL_ACCUMULATION

TB

72

% (1342)

1. Refer to table 414 for transducer block parameter descriptions and table 425 for AO parameter descriptions.

Status Handling
The AI block only gets Good NonSpecified Unlimited or Bad Device Failure for status from the transducer. This is
reflected in FIELD_VAL.STATUS [19.1]. PV.STATUS [7.1] is the same as FIELD_VAL.STATUS [19.1]. OUT.STATUS [8.1]
can also reflect Bad, Out of Service in addition to PV.STATUS [7.1] values.
In the STATUS_OPTS [14] parameter, you can select from the following options to control the status handling:
Propagate Fail ForwardIf the status from the sensor is Bad, Device failure or Bad, Sensor failure, propogate it to OUT
without generating an alarm. The use of these substatus in OUT is determined by this option. Through this option,
you may determine whether alarming (sending out an alert) will be done by the block or propagated downstream for
alarming.
Figure 425. Analog Input Function Block Timing Diagram

OUT (mode in man)


OUT (mode in auto)
PV

FIELD_VAL
TIME (seconds)
PV_FTIME

FIELDBUSFBUS_03A

63% of Change

Uncertain if in Manual modeThe status of the Output is set to Uncertain when the mode is set to Manual.

Note
1. The instrument must be in Out of Service mode to set the status option.
2. The AI block only supports the Uncertain if in Manual and Propagate failure. Unsupported options are not grayed out; they
appear on the screen in the same manner as supported options.

173

Instruction Manual

Detailed SetupAI Function Block


August 2012

D103412X012

Filtering
The filtering feature changes the response time of the device to smooth variations in output readings caused by rapid
changes in input. You can adjust the filter time constant (in seconds) using the PV_FTIME [18] parameter. Set the filter
time constant to zero to disable the filter feature.

Signal Conversion
You can set the signal conversion type with the Linearization Type (L_TYPE [16]) parameter. You can view the
converted signal (in percent of XD_SCALE [10]) through the FIELD_VAL [19] parameter.
FIELD_VAL =

100 X (Channel Value) - EU *@0%


(EU *@100% - EU *@0%)

*XD_SCALE values

You can choose from direct, indirect, or indirect square root signal conversion with the L_TYPE [16] parameter.

Direct
Direct signal conversion allows the signal to pass through the accessed channel input value (or the simulated value
when simulation is enabled).
PV = Channel Value

Indirect
Indirect signal conversion converts the signal linearly to the accessed channel input value (or the simulated value when
simulation is enabled) from its specified range (XD_SCALE [10]) to the range and units of the PV [7] and OUT [8]
parameters (OUT_SCALE [11]).

PV =

FIELD_VAL
100

X (EU **@100% - EU **@0%) + EU **@0%

**OUT_SCALE values

Indirect Square Root


Indirect Square Root signal conversion takes the square root of the value computed with the indirect signal conversion
and scales it to the range and units of the PV [7] and OUT [8] parameters.

PV =

FIELD_VAL
100

X (EU **@100% - EU **@0%) + EU **@0%

**OUT_SCALE values

174

Instruction Manual

Detailed SetupAI Function Block

D103412X012

August 2012

When the converted input value is below the limit specified by the LOW_CUT [17] parameter, a value of zero is used
for the converted value (PV [7]). This option is useful to eliminate false readings when the differential pressure
measurement is close to zero.

Note
Invert is the only I/O option supported by the AI block. You can set the I/O option in Out of Service mode only.

Advanced Features
The AI function block provided with the DVC6200f provides added capability through the addition of the following
parameters:
ALARM_SELAllows one or more of the process alarm conditions detected by the AI function block to be used in
setting its OUT_D [37] parameter.
OUT_DDiscrete output of the AI function block based on the detection of process alarm condition(s). This parameter
may be linked to other function blocks that require a discrete input based on the detected alarm condition.
STDDEV and CAP_STDDEV are diagnostic parameters that can be used to determine the variability of the process.

Simulation
To support testing, you can either change the mode of the block to manual and adjust the output value, or you can
enable simulation through the configuration tool and manually enter a value for the measurement value and its status.
To enable simulation, you must first install the Simulate Enable jumper across the instrument AUX terminals (see page
36). Next you must use the configuration tool to enable the parameter SIMULATE [9].
With simulation enabled, the actual measurement value has no impact on the OUT [8] value or the status.

Block Errors
Table 455 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are inactive for the AI block
and are given here only for your reference.
Table 455. BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other

Block Configuration Error the selected channel carries a measurement that is incompatible with the engineering units
selected in XD_SCALE, the L_TYPE parameter is not configured, or CHANNEL = zero.

Link Configuration Error

Simulate Active Simulation is enabled and the block is using a simulated value in its execution.

Local Override

Device Fault State

Device Needs Maintenance Soon

Input failure/process variable had Bad status The hardware is bad, or a bad status is being simulated

Output failure

Memory failure

10

Lost Static Data

11

Lost NV Data

12

Readback Check Failed

13

Device Needs Maintenance Now

14

Power Up - This condition exists until the AI function block executes for the first time.

15

Out of Service The actual mode is Out of Service.

175

Instruction Manual

Detailed SetupAI Function Block


August 2012

D103412X012

Troubleshooting
Refer to table 456 to troubleshoot any problem that you encounter.
Table 456. Troubleshooting
Symptom
Mode will not leave OOS

Possible Causes
Target mode is not set

Configuration error

Corrective Action
Set target mode to something other than OOS
BLOCK_ERR [6] will show the configuration error bit set. The
following are parameters that must be set before the block is
allowed out of OOS:
CHANNEL [15] must be set to a valid value and cannot be
left at initial value of 0.
XD_SCALE [10]. UNITS_INDEX must match the units in the
transducer block channel value.
L_TYPE [16] must be set to Direct, Indirect, or Indirect
Square Root and cannot be left at an initial value of 0.

Resource block
Schedule
Process and/or block alarms will not work

Features
Notification
Status Options

Value of output does not make sense

Linearization Type

Scaling

The actual mode of the Resource block is OOS. See Resource


Block Diagnostics for corrective action.
Block is not scheduled and therefore cannot execute to go to
Target Mode. Schedule the block to execute.
FEATURES_SEL [18] in the resource block does not have Alerts
enabled. Enable the Reports Supported bit.
LIM_NOTIFY [32] in the resource block is not high enough. Set
equal to MAX_NOTIFY [31], also in the resource block.
STATUS_OPTS [14] has Propagate Fault Forward bit set. This
should be cleared to cause an alarm to occur.
L_TYPE [16] must be set to Direct, Indirect, or Indirect Square
Root and cannot be left at an initial value of 0.
Scaling parameters are set incorrectly:
XD_SCALE.EU0 and EU100 should match that of the trans
ducer block channel value.
OUT_SCALE.EU0 and EU100 are not set properly.

Cannot set HI_LIMIT [28], HI_HI_LIMIT [26],


LO_LIMIT [30], or LO_LO_LIMIT [32] VALUES

Scaling

Limit values are outside the OUT_SCALE.EU0 and


OUT_SCALE.EU100 values. Change OUT_SCALE [11] or set
values within range.

AI Function Block Parameter List (table 457)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter

176

Instruction Manual

Detailed SetupAI Function Block

D103412X012

August 2012

Table 457. Analog Input Block Parameter Definitions


Label
PARAMETER_NAME

Index
Number

RO /
RW

Write Block
Mode

Range

Initial
Value

Description

N/A

0 to 65535

Data Type: Unsigned16


The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed

ALL

7 bit ASCII

spaces

Data Type: Octet String


The user description of the intended application of
the block.

ALL

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.

Data Type: Unsigned8


The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.

Static Revision
ST_REV

Tag Description
TAG_DESC
Strategy
STRATEGY

Alert Key
ALERT_KEY

Block Mode
MODE_BLK

RO

ALL

1 to 255

OOS
MAN
AUTO

OOS until block


is configured,
then last valid
target

TARGET

5.1

RW

ALL

ACTUAL

5.2

RO

ALL

OOS
OOS, MAN,
AUTO

PERMITTED

5.3

RW

ALL

NORMAL

5.4

RW

ALL

OOS+MAN+AUTO

Data Type: DS69


Valid Bits: 7: OOS, 4: MAN, 3: AUTO
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

AUTO

Block Error
BLOCK_ERR

RO

1: Block Configuration
Error
3: Simulate Active
7: Input Failure/ Bad PV
Status
14: Powerup
15: OutofService

Process Value
PV

RO

PV Status set equal to


FIELDV_VAL Status

Data Type: DS65


Reflects the scaled value from the configured
channel. Units set by OUT_SCALE and L_TYPE.

Primary Output
OUT

OUT_STATE

Data Type: DS68


The block output value and status.

Simulate
SIMULATE

OOS, MAN

SIMULATE_STATUS

9.1

ALL

SIMULATE_VALUE

9.2

ALL

 TRANSDUCER_STATUS

9.3

RO

TRANSDUCER_VALUE

9.4

RO

ENABLE/DISABLE

Transducer Scale
XD_SCALE

Output Scale
OUT_SCALE

9.5

10

11

0
0

Data Type: Bit String


0=Inactive
1=Active
Error status associated with the hardware or
software for the AI block.

Data Type: DS82


A group of data that contains the current transducer
value and status, the simulated transducer value
and status, and the enable/disable bit.

ALL

0=Not Initialized
1=Simulation Disabled
2=Simulation Active

OOS

EU at 100%
EU at 10%
Units Index
Decimal Point

100
0
%
2

Data Type: DS68


Transducer scaling (XD_SCALE) is applied to the
value from the channel to produce the FIELD_VAL in
percent. The XD_SCALE units code must match the
channel units code (if one exists), or the block will
remain in OOS mode after being configured.

OOS

EU at 100%
EU at 10%
Units Index
Decimal Point

100
0
%
2

Data Type: DS68


The high and low scale values, engineering units
code, and number of decimal places to be used in
displaying the OUT parameter and parameters
which have the same scaling as OUT.

1=simulate
disabled

-Continued-

177

Instruction Manual

Detailed SetupAI Function Block


August 2012

D103412X012

Table 457. Analog Input Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Grant Deny
GRANT_DENY

Index
Number

RO /
RW

Write Block
Mode

Range

Initial
Value

Description

All bits: 0

Data Type: DS70


Options for controlling access of host computer and
local control panels to operating, tuning, and alarm
parameters of the block.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied

12
Valid Bits
0: Program
1: Tune
2: Alarm
3: Local

GRANT

12.1

ALL

DENY

12.2

ALL

13

OOS

10: Low cutoff

All bits: 0

Data Type: Bit String


0=Disable
1=Enable
User options for Output Control.

All bits: 0

Data Type: Bit String


0=Disable
1=Enable
User options for Status

I/O Options
IO_OPTS

Status Options
STATUS_OPTS

14

OOS

3: Propagate Failure
forward
6: Uncertain if Limited
7: Bad if Limited
8: Uncertain in Man
Mode

AI Channel
CHANNEL

15

OOS

See table 454

0: Undefined
1: Direct
2: Indirect
3: Ind. Sqr. Root

All bits: 0

0: Undefined

Data Type: Unsigned16


Used to select the type of threshold that is used to
set the output.

0: Undefined

Data Type: Enum


Linearization type. Determines whether the field
value is used directly (Direct), is converted linearly
(Indirect), or is converted with the square root
(Indirect Square Root). The OUT_SCALE is normally
the same as the transducer, but if L_TYPE is set to
Indirect or Ind Sqr Root, OUT_SCALE determines the
conversion from FIELD_VAL to the output.

Linearization Type
L_TYPE

16

OOS, MAN

Low Cutoff
LOW_CUT

17

ALL

Positive

Data Type: Float


If calculated output is below this value the output is
0.

Process Value Filter Time


PV_FTIME

18

ALL

Positive

Data Type: Float


Time constant of first order filter on PV, in seconds.

Field Value
FIELD_VAL

19

Data Type: DS65


Value of the field device analog input, with a status
reflecting the Transducer condition.

Updated Event
UPDATE_EVT

20

RO

UNACKNOWLEDGED

20.1

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

UPDATE_STATE

20.2

RO

N/A

0=Undefined
1=Update reported
2=Update not reported

0=Undefined

TIME_STAMP

20.3

RO

N/A

STATIC_REVISION

20.4

RO

N/A

RELATIVE_INDEX

20.5

RO

N/A

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

21
21.1

RW

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clearreported
2=Clearnot reported
3=Activereported
4=Activenot reported

ALARM_STATE

21.2

RO

TIME_STAMP

21.3

RO

SUBCODE

21.4

RO

VALUE

21.5

RO
-Continued-

178

Data Type: DS73


This alarm is generated whenever a static parameter
is changed.

Data Type: DS72


The block alarm is used for all configuration,
hardware, connection failure or system problems in
the block. The cause of the alert is entered in the
subcode field.

Instruction Manual

Detailed SetupAI Function Block

D103412X012

August 2012

Table 457. Analog Input Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Alarm Summary
ALARM_SUM

Index
Number

RO /
RW

Write Block
Mode

Range

Initial
Value

22

CURRENT

22.1

RO

ALL

 UNACKNOWLEDGED

22.2

RO

ALL

UNREPORTED

22.3

RO

ALL

DISABLED

22.4

RW

ALL

0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm

All bits: 0

Description
Data Type: DS74 Current alert status,
unacknowledged states, unreported states, and
disabled states of the alarms associated with the
function block.
0=clear
0=acknowledged
0=reported
0=enabled

Acknowledge Option
ACK_OPTION

23

ALL

0: Discrete alarm
1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm
7: Block alarm

Alarm Hysteresis
ALARM_HYS

24

ALL

0 - 50%

0.50%

High High Priority


HI_HI_PRI

25

ALL

0 to 15

Data Type: Unsigned8


The priority of the hi hi alarm.

High High Limit


HI_HI_LIM

26

ALL

OUT_SCALE

Data Type: Float


Value of analog input which will generate an alarm.

High Priority
HI_PRI

27

ALL

0 to 15

Data Type: Unsigned8


The priority of the high alarm.

Hi Limit
HI_LIM

28

ALL

OUT_SCALE

Data Type: Float


Value of analog input which will generate an alarm.

Low Priority
LO_PRI

29

ALL

0 to 15

Data Type: Unsigned8


The priority of the low alarm.

Low Limit
LO_LIM

30

ALL

OUT_SCALE

Data Type: Float


Value of analog input which will generate an alarm.

Low Low Priority


LO_LO_PRI

31

ALL

0 to 15

Data Type: Unsigned8


The priority of the low low alarm.

Low Low Limit


LO_LO_LIM

32

ALL

OUT_SCALE

Data Type: Float


Value of analog input which will generate an alarm.

High High Alarm


HI_HI_ALM

33

All bits: 0

UNACKNOWLEDGED

33.1

RW

ALARM_STATE

33.2

RO

TIME_STAMP

33.3

RO

SUBCODE

33.4

RO

VALUE

33.5

RO

High Alarm
HI_ALM

N/A

Data Type: Float


Hysteresis on alarms.

Data Type: DS71


The status of the hi hi alarm and its associated time
stamp.

34

UNACKNOWLEDGED

34.1

RW

ALARM_STATE

34.2

RO

TIME_STAMP

34.3

RO

SUBCODE

34.4

RO

VALUE

34.5

RO

Low Alarm
LO_ALM

Data Type: Bit String


0=Disable
1=Enable
Selection of whether alarms associated with the
block will be automatically acknowledged.

N/A

Data Type: DS71


The status of the hi alarm and its associated time
stamp.

35

UNACKNOWLEDGED

35.1

RW

ALARM_STATE

35.2

RO

TIME_STAMP

35.3

RO

SUBCODE

35.4

RO

VALUE

35.5

RO

N/A

Data Type: DS71


The status of the lo alarm and its associated time
stamp.

0
0
-Continued-

179

Instruction Manual

Detailed SetupAI Function Block


August 2012

D103412X012

Table 457. Analog Input Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Low Low Alarm
LO_LO_ALM

Index
Number

RO /
RW

Write Block
Mode

Initial
Value

Range

Description

36

UNACKNOWLEDGED

36.1

RW

ALARM_STATE

36.2

RO

TIME_STAMP

36.3

RO

SUBCODE

36.4

RO

VALUE

36.5

RO

N/A

Data Type: DS71


The status of the lo lo alarm and its associated time
stamp.

0
0
Extended Parameter
Data Type: DS66
Discrete Output this is true (1) if any of the alarms
selected in ALM_SEL are active.

Output Discrete
OUT_D

37

OOS, MAN

Alarm Select
ALM_SEL

38

ALL

1: Hi Hi alarm
2: Hi Alarm
3: Lo Lo Alarm
4: Lo Alarm

StdDev
STDDEV

39

RO

N/A

Positive float

Data Type: Float


Standard deviation of the measurement.

Cap StdDev
CAP_STDDEV

40

RO

N/A

Positive float

Data Type: Float


Capability standard deviation, the best deviation
that can be achieved.

OUT_STATE

All bits: 0

Data Type: Bitstring


0=unselected
1=selected
Selected alarms that activate the alarm output.

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 458. AI Function Block, View 1

Table 459. AI Function Block, View 2

Index Number

Index Number

180

Parameter

Parameter

ST_REV

ST_REV

5.1

MODE_BLK.TARGET_MODE

10

XD_SCALE

5.2

MODE_BLK.ACTUAL_MODE

11

OUT_SCALE

5.3

MODE_BLK.PERMITTED_MODE

12.1

GRANT_DENY.GRANT

5.4

MODE_BLK.NORMAL_MODE

12.2

GRANT_DENY.DENY

BLOCK_ERR

PV

OUT

19

FIELD_VAL

22.1

ALARM_SUM.CURRENT

22.2

ALARM_SUM.UNACKNOWLEDGED

22.3

ALARM_SUM.UNREPORTED

22.4

ALARM_SUM.DISABLED

Instruction Manual

Detailed SetupAI Function Block

D103412X012

August 2012

Table 460. AI Function Block, View 3

Table 461. AI Function Block, View 4

Index Number

Index Number

Parameter

Parameter

ST_REV

ST_REV

5.1

MODE_BLK.TARGET_MODE

STRATEGY

5.2

MODE_BLK.ACTUAL_MODE

ALERT_KEY

5.3

MODE_BLK.PERMITTED_MODE

13

IO_OPTS

5.4

MODE_BLK.NORMAL_MODE

14

STATUS_OPTS

BLOCK_ERR

15

CHANNEL

PV

16

L_TYPE

OUT

17

LOW_CUT

19

FIELD_VAL

18

PV_FTIME

22.1

ALARM_SUM.CURRENT

23

ACK_OPTION

22.2

ALARM_SUM.UNACKNOWLEDGED

24

ALARM_HYS

22.3

ALARM_SUM.UNREPORTED

25

HI_HI_PRI

22.4

ALARM_SUM.DISABLED

26

HI_HI_LIM

37

OUT_D

27

HI_PRI

38

ALM_SEL

28

HI_LIM

39

STDDEV

29

LO_PRI

40

CAP_STDDEV

30

LO_LIM

31

LO_LO_PRI

32

LO_LO_LIM

181

Instruction Manual

Detailed SetupAI Function Block


August 2012

D103412X012

Field Communicator Menu Structure


ANALOG INPUT FUNCTION BLOCK

Quick Config
AI Channel
Linearization Type
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Common Config
Acknowledge Option
Alarm Hysteresis
Alert Key
High High Limit
High High Priority
High Limit
High Priority
I/O Options
Linearization Type
Low Low Limit
Low Low Priority
Low Limit
Low Priority
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Process Value Filter Time
Advanced Config
Low Cutoff
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Static Revision
Status Options
Strategy
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
I/O Reference
AI Channel
Connectors
Output: Status
Output: Value

182

Online
Block Error
Field Value: Status
Field Value: Value
Cascade Input: Status
Cascade Input: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output: Status
Output: Value
Process Value: Status
Process Value: Value
Status
Block Error
Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
High Alarm: Unacknowledged
High Alarm: Alarm State
High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Alarm output: Status
Alarm output: Value
Alarm Select
StdDev
Cap StdDev

All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value: Status
Process Value: Value
Output: Status
Output: Value
Simulate: Simulate Status
Simulate: Simulate Value
Simulate: Transducer Status
Simulate: Transducer Value
Simulate: Simulate En/Disable
Transducer Scale: EU at 100%
Transducer Scale: EU at 0%
Transducer Scale: Units Index
Transducer Scale: Decimal
Output Scale: EU at 100%
Output Scale: EU at 0%
Output Scale: Units Index
Output Scale: Decimal
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
AI Channel
Linearization Type
Low Cutoff
Process Value Filter TIme
Field Value: Status
Field Value: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option

All (continued)
Alarm Hysteresis
High High Priority
High High Limit
High Priority
High Limit
Low Priority
Low Limit
Low Low Priority
Low Low Limit
High High Alarm: Unacknowledged
High High Alarm: Alarm State
High High Alarm: Time Stamp
High High Alarm: Subcode
High High Alarm: Float Value
High Alarm: Unacknowledged
High Alarm: Alarm State
High Alarm: Time Stamp
High Alarm: Subcode
High Alarm: Float Value
Low Alarm: Unacknowledged
Low Alarm: Alarm State
Low Alarm: Time Stamp
Low Alarm: Subcode
Low Alarm: Float Value
Low Low Alarm: Unacknowledged
Low Low Alarm: Alarm State
Low Low Alarm: Time Stamp
Low Low Alarm: Subcode
Low Low Alarm: Float Value
Alarm output: Status
Alarm output: Value
Alarm select
StdDev
Cap StdDev

Instruction Manual

Detailed SetupMAI Function Block

D103412X012

August 2012

Multiple Analog Input Function Block


Overview
The Multiple Analog Input (MAI) function block (figure 426) has the ability to process up to eight field device
measurements and make them available to other function blocks. The output values from the MAI block are in
engineering units and contain a status indicating the quality of the measurement. The measuring device may have
several measurements or derived values available in different channels. Use the channel numbers to define the
variables that the MAI block processes.
Figure 426. Multiple Analog Input (MAI) Function Block

OUT_1

MAI

OUT_2
OUT_3

OUT_5
OUT_6
OUT_7

FIELDBUSFBUS_31A

OUT_4

OUT_8

Out1 = The block output value and


status for the first channel

The MAI block supports mode control. In Automatic mode, the block's output parameters (OUT_1 to OUT_8 [8
through 15]) reflects the process variable (PV) values and status. In Manual mode, OUT may be set manually. The
Manual mode is reflected in the output status. Table 464 lists the MAI block parameters, and their units of measure,
description and index numbers.

Modes
The MAI Function Block supports three modes of operation as defined by the MODE_BLK [5] parameter:
Manual (Man)The block output (OUT_1 to OUT_8 [8 through 15]) may be set manually.
Automatic (Auto)OUT_1 to OUT_8 [8 through 15] reflects the analog input measurement or the simulated value
when the simulation is enabled.
Out of Service (OOS)The block is not processed. PV is not updated and the OUT status is set to Bad: Out of Service.
The BLOCK_ERR [6] parameter shows Out of Service. In this mode, you can make changes to all configurable
parameters. The target mode of a block may be restricted to one or more of the supported modes.

Status Handling
In Man mode, the OUT status constant limit is set to indicate that the value is a constant and the OUT status is Good.

183

Instruction Manual

Detailed SetupMAI Function Block


August 2012

D103412X012

OUT_X status will be Bad if the transducer detects a problem with sensor associated with the channel.

Application Information
The intended use is for applications where it is necessary to convey DVC6200f measurements from a function.
The configuration of the MAI function block and its associated output channels depends on the specific application.
CHANNEL [7]: Channel must always be set to 21.
The output parameters (OUT_1 to OUT_8 [8 through 15]) are set through the transducer block Instrument menu.
Each output has a channel assigned to it in MAI Channel Map (TB.MAI_CHANNEL_MAP [95]) in the transducer block.
For additional information, refer to table 464.

Block Errors
Table 462 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are inactive for the MAI block
and are given here only for your reference.
Table 462. BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other

Block Configuration Error: the selected channel carries a measurement that is incompatible with the engineering units selected
in XD_SCALE, the L_TYPE parameter is not configured, or WRITE_CHECK = 0.

Link Configuration Error

Simulate Active

Local Override

Device Fault State

Device Needs Maintenance Soon

Input failure/process variable had Bad status The hardware is bad, or a bad status is being simulated

Output failure

Memory failure

10

Lost Static Data

11

Lost NV Data

12

Readback Check Failed

13

Device Needs Maintenance Now

14

Power Up - This condition exists after power up until the MAI function executes for the first time.

15

Out of Service The actual mode is Out of Service.

Troubleshooting
Refer to table 463 to troubleshoot any problem that you encounter.
Table 463. Troubleshooting
Symptom
Mode will not leave OOS

Possible Causes
Target mode is not set
Resource block

Schedule
Block alarms will not work

Features
Notification

184

Corrective Action
Set target mode to something other than OOS
The actual mode of the Resource block is OOS. See
Resource Block Diagnostics for corrective action.
Block is not scheduled and therefore cannot execute to go
to Target Mode. Typically, BLOCK_ERR [6] will show
PowerUp for all blocks that are not scheduled.
Schedule the block to execute.
FEATURES_SEL [18] in the resource block does not have
Alerts enabled. Enable the Alerts bit.
LIM_NOTIFY [32] in the resource block is not high
enough. Set equal to MAX_NOTIFY [31], also in the
resource block.

Instruction Manual

Detailed SetupMAI Function Block

D103412X012

August 2012

MAI Function Block Parameter List (table 464)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter
Table 464. MAI Function Block Parameter Definitions
 Label
Parameter Name

Index
Number

Static Revision
ST_REV

Tag Description
TAG_DESC

RO /
RW

RO

Mode

N/A

Range

Initial Value

Description
Data Type: Unsigned16
The revision level of the static data
associated with the input selector block.
The revision value will be incremented
each time a static parameter value in the
block is changed.

0 to 65535

7 bit ASCII

spaces

Strategy
STRATEGY

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify
grouping of blocks. This data is not
checked or processed by the block.

Alert Key
ALERT_KEY

1 to 255

Data Type: Unsigned8


The identification number of the plant
unit. This information may be used in the
host for sorting alarms, etc.

Block Mode
MODE_BLK

TARGET

5.1

RW

ALL

ACTUAL

5.2

RO

ALL

PERMITTED

5.3

RW

NORMAL

5.4

RW

Block Error
BLOCK_ERR

RO

OOS, MAN, AUTO

OOS

ALL

OOS+MAN+AUTO

OOS, MAN, AUTO

ALL

AUTO

OOS
AUTO

1: Block Configuration
Error
7: Input Failure/ Bad PV
Status
14: Powerup
15: OutofService

Data Type: Octet String


The user description of the intended
application of the block.

Data Type: DS69


The actual, target, permitted, and normal
modes of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: Bit String
0 = Inactive
1 = Active
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is a
bit string, so that multiple errors may be
shown.
This variable must be set to 21. Channel
assignments to the 8 outputs is done
through MAI_CHANNEL_MAP parameter
in transducer block.

MAI Channel
CHANNEL

21 only

0 = undefined

1=FINAL_VALUE
2=TRAVEL_TARGET
3=FINAL_POSITION_VALUE
4=TRAVEL
5=SUPPLY_PRESS
6=ACT_PRESS_A
7=ACT_PRESS_B
8=ACT_PRESS_DIFF
9=DRIVE_SIGNAL
10=TRAVEL_DEVIATION
11=TEMPERATURE
12=CYCLE_COUNT
13=TRAVEL_ACCUM

-Continued-

185

Instruction Manual

Detailed SetupMAI Function Block


August 2012

D103412X012

Table 464. MAI Function Block Parameter Definitions (Continued)


 Label
Parameter Name

Index
Number

RO /
RW

Mode

Range

Initial Value

Description

Output 1
OUT_1

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.FINAL_VALUE

Data Type: DS65


The block output value and status.

Output 2
OUT_2

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.TRAVEL_TARGET

Data Type: DS65


The block output value and status.

Output 3
OUT_3

10

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.FINAL_POSITION_VA
LUE

Data Type: DS65


The block output value and status.

Output 4
OUT_4

11

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.TRAVEL

Data Type: DS65


The block output value and status.

Output 5
OUT_5

12

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.SUPPLY_PRESS

Data Type: DS65


The block output value and status.

Output 6
OUT_6

13

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.ACT_PRESS_A

Data Type: DS65


The block output value and status.

Output 7
OUT_7

14

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.ACT_PRESS_B

Data Type: DS65


The block output value and status.

Output 8
OUT_8

15

OOS
MAN

Channel assigned by
TB.MAI_CHANNEL_MAP

TB.ACT_PRESS_DIFF

Data Type: DS65


The block output value and status.

Update Event
UPDATE_EVT

16
N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

0=Undefined
1=Update reported
2=Updated not reported

0=Undefined

UNACKNOWLEDGED

RW

UPDATE_STATE

16.2

RO

N/A

TIME_STAMP

16.3

RO

N/A

STATIC_REVISION

16.4

RO

N/A

RELATIVE_INDEX

16.5

RO

N/A

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

186

16.1

Data Type: DS73


This alarm is generated whenever a static
parameter is changed.

17
17.1

RW

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

ALARM_STATE

17.2

RO

TIME_STAMP

17.3

RO

SUBCODE

17.4

RO

VALUE

17.5

RO

Data Type: DS72


The block alarm is used for all
configuration , hardware, connection
failure or system problems in the block.
The cause of the alert is entered in the
subcode field.

Instruction Manual

Detailed SetupMAI Function Block

D103412X012

August 2012

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 465. MAI Function Block, View 1

Table 467. MAI Function Block, View 3

Index Number

Index Number

Parameter
ST_REV

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

BLOCK_ERR

OUT_1

OUT_1

OUT_2

OUT_2

10

OUT_3

10

OUT_3

11

OUT_4

11

OUT_4

12

OUT_5

12

OUT_5

13

OUT_6

13

OUT_6

14

OUT_7

14

OUT_7

15

OUT_8

15

OUT_8

Table 466. MAI Function Block, View 2


Index Number
1

Parameter
ST_REV

Table 468. MAI Function Block, View 4


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

CHANNEL

187

Instruction Manual

Detailed SetupMAI Function Block


August 2012

D103412X012

Field Communicator Menu Structure


MULTIPLE ANALOG INPUT FUNCTION BLOCK

Quick Config
MAI Channel
Common Config
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Advanced Config
Static Revision
Strategy
I/O Reference
MAI Channel
Connectors
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 3: Status
Output 3: Value
Output 4: Status
Output 4: Value
Output 5: Status
Output 5: Value
Output 6: Status
Output 6: Value
Output 7: Status
Output 7: Value
Output 8: Status
Output 8: Value

188

Online
Block Error
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 3: Status
Output 3: Value
Output 4: Status
Output 4: Value
Output 5: Status
Output 5: Value
Output 6: Status
Output 6: Value
Output 7: Status
Output 7: Value
Output 8: Status
Output 8: Value
Status
Block Error
Other
Tag Description
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value

All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
MAI Channel
Output 1: Status
Output 1: Value
Output 2: Status
Output 2: Value
Output 3: Status
Output 3: Value
Output 4: Status
Output 4: Value
Output 5: Status
Output 5: Value
Output 6: Status
Output 6: Value
Output 7: Status
Output 7: Value
Output 8: Status
Output 8: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value

Instruction Manual

Detailed SetupDO Function Block

D103412X012

August 2012

Discrete Output Function Block


Overview
The Discrete Output (DO) function block (figure 427) processes a discrete set point and outputs it to the specified I/O
channel to produce an output signal. The DVC6200f digital valve controller discrete output block provides both
normal open/closed control and the ability to position the valve in 5% increments for coarse throttling applications.
The digital valve controller measures and uses actual valve position for READBACK_D [16].
Figure 427. Discrete Output (DO) Function Block

BKCAL_OUT_D
CAS_IN_D

DO

OUT_D
READBACK_D

CASIND= The remote set point value from another function block.
BKCALOUTD = The value and status required by the
BKCALIND input of another block for output tracking.
OUT_D = The block output and status.
READBACK_D = Actual valve position

The DO block supports mode control and simulation. In operation, the DO function block determines its set point and
sets the output. The transducer block provides a readback signal of actual position from the instrument. Figure 427
illustrates the primary inputs and outputs of the DO function block, figure 428 illustrates the internal components of
the DO function block. Table 472 lists definitions for the function block parameters.

189

Instruction Manual

Detailed SetupDO Function Block


August 2012

D103412X012

Figure 428. Discrete Output Function Block Schematic

RCAS_OUT_D
RCAS_IN_D

BKCAL_OUT_D
PV_D

SP_D
CONVERT AND
STATUS
CALCULATION

CAS_IN_D

IO_OPTS

OUT_D

READBACK_D

MODE

SIMULATE_D

SHED MODE
CHANNEL

TRANSDUCER
BLOCK FEEDBACK

TRANSDUCER
BLOCK

When setting up the DO block, CHANNEL [18] must be set to 22, and SHED_OPT [23] must be nonzero.

Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain out of service and the block cannot be scheduled if the block has not
been licensed. Contact your Emerson Process Management sales office to upgrade product licensing.

Note
Actual Block Mode (MODE_BLK.ACTUAL [5.2]) will remain in IMAN and the block Readback status will be Bad - Not Connected if
the Output Block Selection is set incorrectly. From the transducer block method Outblock Selection, select the desired output
block, see page 69.

Modes
The DO block supports the following modes:
Manual (Man)The block output OUT_D [9] value may be entered manually.
Automatic (Auto)The block algorithm uses the local set point SP_D [8]value to determine OUT_D [9].

190

Instruction Manual

Detailed SetupDO Function Block

D103412X012

August 2012

Cascade (Cas)The block uses a set point supplied by another function block.

Note
The transducer block must be in Auto for the mode to go to AUTO, CAS or MAN.

RemoteCascade (RCas)The block uses a set point supplied by a host computer.


Out of Service (OOS)The block is not processed and the output is not transferred to I/O. The BLOCK_ERR [6]
attribute shows Out of service.

Mode Handling
Shed Options RCAS Mode Only
Shed from or climb to a remote mode is determined by the parameter SHED_OPT [23]. A block climbs and sheds
through the same path. For example, if SHED_OPT [23] specifies that a block should shed to Auto, then, if the block
target mode is set to RCas, the block goes through Auto on the way to RCas. You can configure the shed option as
follows:

Shed With Return Options


Remote cascade connection failure shifts actual mode but keeps trying to restore remote cascade (in other words, the
remote cascade target mode stays in effect).
NormalOn failure of a remote cascade connection, the block attempts to attain the highest permitted nonremote
mode until remote cascade is restored. Cas is the highest permitted nonremote mode and Auto is is the next
permitted nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the target mode for the block before changing the target mode to a
remote mode. On failure of a remote cascade connection, the block attempts to attain the retained target mode.
AutoOn failure of a remote cascade connection, the block attempts to attain Auto, if permitted, until remote
cascade is restored.
ManOn failure of a remote cascade connection, the block sheds to Man until a remote cascade connection is
restored.

Shed With No Return Options


For any shed with no return option, the target mode changes as determined by the option. Therefore, there is no
attempt to restore the connection following failure. The behavior on change to the remote cascade target mode is
identical to that for Shed With Return Options.
NormalOn failure of a remote cascade connection, the block sets the target mode to the highest permitted
nonremote mode. Cas is the highest permitted nonremote mode and Auto is is the next highest permitted
nonremote mode. If Cas or Auto are not available, the block will shed by default to Man.
Retained TargetThe retained target mode is the target mode for the block before changing the target mode to a
remote mode. On failure of a remote cascade connection, the block sets the target mode to the retained target mode.

191

Instruction Manual

Detailed SetupDO Function Block


August 2012

D103412X012

AutoOn failure of a remote cascade connection, the block sets the target mode to Auto, if permitted.
ManOn failure of remote cascade connection, the block sets the target mode to Man, if permitted.
The user may configure SHED_OPT [23] so that it calls for a target mode that is not permitted. When doing this, the
mode logic uses the following rules as applied by the remote logic:
Shed logic never results in a nonpermitted target mode.
Shed logic never attempts to attain an actual mode of Auto or Cas if that mode is not permitted.

Block Initialization
The Fieldbus Foundation specification requires that certain parameters have initial values of uninitialized in function
blocks. In addition to setting the Resource block mode to AUTO, the control system or the user must change those
parameters from their uninitialized value to a valid value in order for the function block to move from the Out of
Service mode. For the DO function block, the parameters that must be initialized are:
SHED_OPT [23] (see page 191 for valid values)
CHANNEL [18]

Status Handling
Under normal operating conditions, the status of OUT_D [9] is Good NonCascade, and the status of BKCAL_OUT_D
[21] is Good:Cascade. If the output hardware fails, the status of BKCAL_OUT_D [21] is set to Bad:Device Fail, and the
BLOCK_ERR [6] shows Output Failure. If the hardware used for output feedback fails, the status of READBACK_D [16]
and PV_D [7] is set to Bad:DeviceFail, and the BLOCK_ERR [6] shows Process Variable has Bad Status. If the transducer
block mode is Out of Service, the status of READBACK_D [16] and PV_D [7] is set to Bad:Out of Service.

I/O Selection
To select the I/O associated with the discrete output, configure the value of the CHANNEL [18] parameter. Table 469
lists the valid Channel selections for the DO block.
Table 469. Channel Selections for the Discrete Output Function Block
Selection

Transducer Block Parameter

Transducer block Index

Description

22

SETPOINT_D

32

Discrete Valve Control

Uninitialized

Setting the Output


To set the output for the DO block, you must first set the mode to define the manner in which the block determines its
set point and output. In Cascade mode, the set point equals the input value at the CAS_IN_D [17] parameter. In
Automatic or Manual mode, the set point must be entered manually by the user. For Automatic, the value must be
written to the SP_D [8] parameter and for Manual, the value must be written to OUT_D [9]. In Remote Cascade mode,
the set point is determined by a host computer that is writing to the RCAS_IN_D [22] parameter. Table 470 lists
discrete states used by the digital valve controller for the set point.

192

Instruction Manual

Detailed SetupDO Function Block

D103412X012

August 2012

Table 470. Valve Set Point for Discrete State


Discrete State

Valve Set Point with IO_OPTS Invert = 0

Closed

Valve Set Point with IO_OPTS Invert = 1


Open

Open

Closed

5%

Closed

10

10%

Closed

15

15%

Closed

20

20%

Closed

25

25%

Closed

30

30%

Closed

35

35%

Closed

40

40%

Closed

45

45%

Closed

50

50%

Closed

55

55%

Closed

60

60%

Closed

65

65%

Closed

70

70%

Closed

75

75%

Closed

80

80%

Closed

85

85%

Closed

90

90%

Closed

95

95%

Closed

100

Open

Closed

To further customize the output, configure the following supported I/O options: SP tracks PV in Man,
SP tracks PV in LO, SP Track retained target in Man or LO, Fault State to Value, Use Fault State value on restart, Target
to Man if Fault State activated, and US PV for BKCAL_OUT.

Note
You can configure the supported I/O options in Out of Service mode only.

The SP_PV Track in Man option permits the set point to track the process variable when the block is in Manual mode.
With this option enabled, the set point (SP_D [8]) becomes a copy of the process variable
(PV_D [7]), and a manuallyentered SP_D [8] value is overwritten on the block's next execution cycle. This option can
prevent a state change when transitioning from Manual to Automatic mode. You can disable this option in Manual or
Out of Service mode only.
The Invert option inverts the set point at SP_D [8] before it is stored in OUT_D [9]. With this option enabled, OUT_D
[9] becomes an inverted copy of SP_D [8] where nonzero values of SP_D [8] are considered a logic 1. With this option
disabled, OUT_D [9] is a direct copy of SP_D [8]. The readback value is processed through the Invert option to become
PV_D [7]. The Use PV for BKCAL_OUT option specifies that BKCAL _OUT equal the value of the process variable (PV_D
[7]) instead of the set point (SP_D [8]). If you do not enable this option, BKCAL_OUT will equal SP_D [8].

Output Block PV Status


The Output Block PV Status is determined by the value of the PlantWeb Alerts Set PV Status parameter in the
transducer block (PWA_SET_STATUS [97]), the Transducer Block mode, and enabled Active PlantWeb alarms. Refer to
table 411.

193

Instruction Manual

Detailed SetupDO Function Block


August 2012

D103412X012

Block Errors
Table 471 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the DO
block and are provided only for your reference.
Table 471. BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other (N/A)

Block Configuration Error SHED_OPT or CHANNEL set to 0 (uninitialized)

Link Configuration Error (N/A)

Simulate active Simulation is enabled and the block is using a simulated value in its execution.

Local Override Device in fault state. Actual mode LO.

Device Fault State Set DO block in fault state after FSTATE_TIME because of Bad status or IFS substatus on CAS_IN_D or Resource
block commanded fault state.

Device Needs Maintenance Soon Indicates a Maintenance PlantWeb Alert condition is active if Block Error Reporting is enabled. See
page 86.

Input failure/process variable has Bad status PV has bad status and Feature Select in the Resource block has the Out Readback bit set
or the transducer block mode is Out of Service.

Output failure PV has bad status or the transducer block mode is Out of Service.

Memory Failure (N/A)

10

Lost Static Data (N/A)

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now Indicates Failed PlantWeb Alert condition is active if Block Error Reporting is enabled. See page 86.

14

Power Up This condition exists after power up until actual mode is not Out of Service.

15

Out of Service The block is in Out of Service (OOS) mode.

Action on Fault Detection


Fault State is caused by one of three sources: A status pertaining to CAS, A status pertaining to RCAS, or SET_FSTATE
[29] in the resource block. To implement Fault State, configure the following parameters:
IO_OPTS [14]: Determines the action OUT_D [9] will take upon a fault state. If the IO_OPTS [14] Fault State to Value
is not selected, then OUT_D [9] holds its last position when Fault State is set. If Fault State to Value is selected,
OUT_D [9] goes to the FSTATE_VAL_D [20] value when Fault State is set.
FSTATE_TIME [19]: The length of time, in seconds, that the DO block will wait to set Fault State. When
Fault State is set, the OUT_D [9] value goes to either the FSTATE_VAL_D [20] value or holds its last position, depending
on I/O_OPTS [14]. When the block has a target mode of CAS, a fault condition will be detected if the CAS_IN_D [17]
has a BAD status or an Initiate Fault State substatus is received from the upstream block.
FSTATE_VAL_D [20]: Determines the OUT_D [9] value if IO_OPTS [14] Fault State to Value is selected. The OUT_D
[9] value transitions to FSTATE_VAL_D [20] after FSTATE_TIME [19] elapses and the fault condition has not cleared.

Simulation
To support testing of the control strategy, you can enable the SIMULATE_D [17] parameter. Normally, the valve
position value and status used for READBACK_D [16] in the DO block reflect actual process values to the nearest 5%, as
provided by the transducer block. When the SIMULATE_D [17] parameter is enabled, value and status used for
READBACK_D [16] is supplied by the user manually. To enable simulation in the DO function block, the simulate
jumper must be installed. Refer to page 36 of the Installation section for information on the installation of this jumper.

194

Instruction Manual

Detailed SetupDO Function Block

D103412X012

August 2012

Note
When simulate is active, the output block no longer writes values to the transducer block. If the Output Blk Timeout period is
exceeded, the transducer block may move the valve to the Zero Power Condition depending on the configuration of the Output
Block Timeout Alert.

The SIMULATE_D [10] parameter has three components:


Simulate Enable_Disable determines whether the function block will use the actual valve position value and status,
or Simulate Value and Simulate Status.
Transducer Value and Status reflect the process values provided by the transducer block.
Simulate Value and Status may be entered by the user when Simulate Enable_Disable is set to Enabled.
To use simulate, first install the simulate jumper in the terminal box, then set Simulate Enable_Disable to Enabled,
then enter the desired values for Simulate Value and Status.
When SIMULATE_D [10] is Enabled, the Simulate Active bit of the BLOCK_ERR [6] parameter is set (refer to the Block
Errors description). When the simulate jumper is installed, the Simulate Jumper bit of the transducer block parameter
SELFTEST_STATUS [78] is set.

DO Function Block Parameter List (table 472)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter
Table 472. Discrete Output Function Block Parameter Definitions
Label
PARAMETER_NAME

Index
Number

RO /
RW

Mode

Range

Initial Value

Description

Static Revision
ST_REV

RO

N/A

0 to 65535

Data Type: Unsigned16


The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.

Tag Description
TAG_DESC

RW

ALL

7 bit ASCII

Spaces

Data Type: Octet String


The user description of the intended application of
the block.

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.

Alert Key
ALERT_KEY

RW

ALL

1 to 255

Data Type: Unsigned8


The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.

-Continued-

195

Instruction Manual

Detailed SetupDO Function Block


August 2012

D103412X012

Table 472. Discrete Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Block Mode
MODE_BLK

Index
Number

RO /
RW

Mode

Range

Initial Value

Description

OOS
MAN
AUTO
AUTOCAS, AUTORCAS

OOS until
block is
configured,
then last valid
target

OOS+MAN+AUTO+
CAS+RCAS

Data Type: DS69


Valid Bits: 7: OOS, 5: LO, 4: MAN, 3: AUTO
2: CAS, 1: RCAS
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

TARGET

5.1

RW

ALL

ACTUAL

5.2

RO

ALL

OOS
OOS+MAN+A
UTO+CAS
+RCAS

PERMITTED

5.3

RW

ALL

NORMAL

5.4

RW

ALL

AUTO+CAS

Block Error
BLOCK_ERR

RO

N/A

1: Block Configuration
Error
3: Simulate Active
4: Local Override
5: Device Fault State Set
7: Input Failure / Bad PV
Status
8: Output Failure
14: Powerup
15: OutofService

Process Value Discrete


PV_D

RO

N/A

PV_D Status set equal


to Readback_D Status

Setpoint Discrete
SP_D

OOS
MAN
AUTO

PV_STATE

Data Type: DS66


The discrete target block output value (set point).

Output Discrete
OUT_D

MAN

OUT_STATE

Data Type: DS66


Position target of valve. 0=closed, 1=open, 2-100
position the value in 5% steps.

Simulate Discrete
SIMULATE_D

10

Dynamic

Data Type: Bit String


0=Inactive
1=Active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown.

Dynamic

Data Type: DS66


The discrete process variable calculated from
READBACK_D.

SIMULATE_STATUS

10.1

ALL

SIMULATE_VALUE

10.2

ALL

TRANSDUCER_STATUS

10.3

RO

TRANSDUCER_VALUE

10.4

RO

ENABLE/DISABLE

0
0
0=Not initialized
1=Simulation Disabled
2=Simulation Active

Data Type: DS83


Allows the transducer discrete input or output to
the block to be manually supplied when simulate is
enabled. When simulation is disabled, the simulate
value and status track the actual value and status.

10.5

ALL

Process Value State


PV_STATE

11

ALL

Data Type: Uint16


Index to the text describing the states of a discrete
output.

Transducer State
XD_STATE

12

ALL

Data Type: Uint16


Index to the text describing the states of a discrete
for the value obtained from the transducer.

Grant Deny
GRANT_DENY

13
All bits: 0

Data Type: DS70


Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block.
GRANT:0=N/A, 1=granted
DENY: 0=N/A, 1=denied

GRANT

13.1

N/A

DENY

13.2

N/A

0: Program
1: Tune
2: Alarm
3: Local
-Continued-

196

All bits: 0

Instruction Manual

Detailed SetupDO Function Block

D103412X012

August 2012

Table 472. Discrete Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

I/O Options
IO_OPTS

Index
Number

RO /
RW

14

Status Options
STATUS_OPTS

15

Readback Discrete
READBACK_D

16

Cascade Input Discrete


CAS_IN_D

17

Mode

Range

OOS

Valid Bits
0: Invert
1: SP tracks PV in Man
3: SP tracks PV in LO
4: SP Track retained
target in Man or LO
6: Fault State to value
0: freeze
1: go to Fault State
value
7: Use Fault State value
on restart
8: Target to Man if Fault
State activated
9: Use PV for
BKCAL_OUT
0: SP
1: PV

OOS

RO

4: Propagate Failure
Backward

N/A

ALL

All bits: 0

Data Type: Bit String


0=Disable
1=Enable
Options the user may select for the block processing
of status.

Dynamic

Data Type: DS66


0=closed, 1=open, 5, 10, 15, 30...etc. are position in
5% increments.

Value

OOS

0=undefined
22=Setpoint (D)

Fault State Time


FSTATE_TIME

19

ALL

Positive

Fault State Value Discrete


FSTATE_VAL_D

20

Back Calculation Output Discrete


BKCAL_OUT_D

21

22

All bits: 0

Data Type: Bit String


0=Disable
1=Enable
Allows you to select the type of tracking and the
output value when a fault condition occurs.
Supported I/O options for the DO function block are
SP Tracks PV in Man, SP Tracks PV in LO, SP Tracks
Retained Target in Man or LO, Fault State to Value,
Use Fault state on Restart, Target to Man if Fault
State Activated, and Use PV for BKCAL_OUT.

BAD:
NC:
const

18

Remote Cascade Input Discrete


RCAS_IN_D

Description

Status

DO Channel
CHANNEL

RO

Initial Value

22=
Setpoint (D)

Data Type: DS66


The remote set point value from another block.
Data Type: Unsigned16
Defines which transducer parameter receives the
DO output. Select Setpoint (D) to control valve
position.

Data Type: Float


Time from detection of a fault in the remote set
point to the Fault State output action.

ALL

Date Type: Unsigned8


Preset discrete SP_D value to use if I/O_OPTS Fault
State to Value is set.

N/A

Dynamic

Data Type: DS66


The value and status required by the BKCAL_IN_D
input of another block for output tracking

ALL

BAD:
NoCom:
NoVal:
const

Status
Value

Date Type: DS66


Target set point and status provided by a
supervisory host to a discrete control or output
block.

-Continued-

197

Instruction Manual

Detailed SetupDO Function Block


August 2012

D103412X012

Table 472. Discrete Output Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME

Shed Options
SHED_OPT

Index
Number

RO /
RW

23

Remote Cascade Output Discrete


RCAS_OUT_D

24

Update Event
UPDATE_EVT

25

Mode

Range

ALL

0=Uninitialized
1=Normal Shed, Normal
Return
2=Normal Shed, No
Return
3=Shed to Auto, normal
return
4=Shed to Auto, no
return. Target mode
changes to Auto on
detection of a shed
condition
5=Shed to Manual,
normal return
6=Shed to Manual, No
return. Target mode
changes to MAN on
detection of a shed
condition.
7=Shed to retained
target, normal return
8=Shed to retained
target, no return.
(Change target to
retained target)

RO

N/A

Initial Value

Description

Data Type: Unsigned8


Defines action to be taken on remote control device
timeout.
Normal Return - actual mode changes to the next
lowest priority nonremote mode permitted but
returns to the target remote mode when the
remote computer completes the initialization
handshake.
No Return - Target mode changes to the next lowest
priority nonremote mode permitted. The target
remote mode is lost, so no return occurs.

Dynamic

Data Type: DS66


Block set point and status after ramping, provided
to a supervisory host for back calculation and to
allow action to be taken under limiting conditions or
mode change.

UNACKNOWLEDGED

25.1

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

UPDATE_STATE

25.2

RO

N/A

0=Undefined
1=Update reported
2=Update not reported

0=Undefined

TIME_STAMP

25.3

RO

N/A

STATIC_REVISION

25.4

RO

N/A

RELATIVE_INDEX

25.5

RO

N/A

RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

Data Type: DS73


This alert is generated by any change to the static
data.

26
26.1

ALARM_STATE

26.2

RO

N/A

TIME_STAMP

26.3

RO

N/A

SUBCODE

26.4

RO

N/A

VALUE

26.5

RO

N/A

Data Type: DS72


The block alarm is used for all configuration,
hardware, connection failure, or system problems in
the block. The cause of the alert is entered in the
subcode field. The first alert to become active will
set the active status in the status parameter. As
soon as the Unreported status is cleared by the alert
reporting procedure, and other block alert may be
reported without clearing the Active status, if the
subcode has changed.

Extended Blocks
Setpoint Rate Up
SP_RATE_UP

27

>= 0

Data Type: Float


The ramp rate for SP up in AUTO, CAS, and RCAS
modes. Measured in PV units/sec.

Setpoint Rate Down


SP_RATE_DN

28

> = 0

Data Type: Float


The ramp rate for SP down in AUTO, CAS, and RCAS
modes. Measured in PV units/sec.

198

Instruction Manual

Detailed SetupDO Function Block

D103412X012

August 2012

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 473. DO Function Block, View 1

Table 475. DO Function Block, View 3

Index Number

Index Number

Parameter
ST_REV

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

BLOCK_ERR

PV_D

PV_D

SP_D

SP_D

OUT_D

OUT_D

16

READBACK_D

16

READBACK_D

17

CAS_IN_D

17

CAS_IN

21

BKCAL_OUT_D

22

RCAS_IN_D

24

RCAS_OUT_D

Table 474. DO Function Block, View 2


Index Number

Parameter

ST_REV

11

PV_STATE

12

XD_STATE

13.1

GRANT_DENY.GRANT

13.2

GRANT_DENY.DENY

Table 476. DO Function Block, View 4


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

14

IO_OPTS

15

STATUS_OPTS

18

CHANNEL

19

FSTATE_TIME

20

FSTATE_VAL_D

24

SHED_OPT

27

SP_RATE_UP

28

SP_RATE_DN

199

Instruction Manual

Detailed SetupDO Function Block


August 2012

D103412X012

Field Communicator Menu Structure


DISCRETE OUTPUT FUNCTION BLOCK
Quick Config
Alert Key
Process Value Discrete: Status
Process Value Discrete: Value
Setpoint Discrete: Status
Setpoint Discrete: Value
Common Config
Alert Key
I/O Options
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Setpoint Discrete: Status
Setpoint Discrete: Value
Advanced Config
Fault State Time
Fault State Value Discrete
Process Value State
Shed Options
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Static Revision
Status Options
Strategy
Transducer State
I/O Reference
DO Channel
Connectors
Back Calculation Output Discrete: Status
Back Calculation Output Discrete: Value
Cascade Input Discrete: Status
Cascade Input Discrete: Value
Output Discrete: Status
Output Discrete: Value

200

Online
Back Calculation Output Discrete: Status
Back Calculation Output Discrete: Value
Block Error
Cascade Input Discrete: Status
Cascade Input Discrete: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Discrete: Status
Output Discrete: Value
Process Value Discrete: Status
Process Value Discrete: Value
Remote Cascade Input Discrete: Status
Remote Cascade Input Discrete: Value
Remote Cascade Output Discrete: Status
Remote Cascade Output Discrete: Value
Readback Discrete: Status
Readback Discrete: Value
Setpoint Discrete: Status
Setpoint Discrete: Value
Status
Block Error
Other
Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Setpoint Rate Up
Setpoint Rate Down

All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value Discrete: Status
Process Value Discrete: Value
Setpoint Discrete: Status
Setpoint Discrete: Value
Output Discrete: Status
Output Discrete: Value
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Process Value State
Transducer State
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
Readback Discrete: Status
Readback Discrete: Value
Cascade Input Discrete: Status
Cascade Input Discrete: Value
DO Channel
Fault State Time
Fault State Value
Back Calculation Output Discrete: Status
Back Calculation Output Discrete: Value
Remote Cascade Input Discrete: Status
Remote Cascade Input Discrete: Value
Shed Options
Remote Cascade Output Discrete: Status
Remote Cascade Output Discrete: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Setpoint Rate Up
Setpoint Rate Down

Instruction Manual

Detailed SetupDI Function Block

D103412X012

August 2012

Discrete Input Function Block


Overview
The Discrete Input (DI) function block (figure 429) processes a single discrete input from a field device and makes it
available to other function blocks. You can configure inversion and alarm detection on the input value. In the
DVC6200f digital valve controller, the discrete input function block can provide limit switch functionality and valve
position proximity detection. The DI function block supports mode control, signal status propagation, and simulation.
Figure 429. Discrete Input (DI) Function Block

DI

TRANSDUCER
BLOCK

OUT_D

OUT_D = The block output and status

Normally, the block is used in Automatic mode so that the process variable (PV_D [7]) is copied to the output (OUT_D
[8]). You can change the mode to Manual to disconnect the field signal and substitute a manuallyentered value for
the output. In this case, PV_D [7] continues to show the value that will become the OUT_D [8] when the mode is
changed to Automatic.
To support testing, you can enable simulation, which allows the measurement value to be supplied manually through
the SIMULATE_D [9] parameter. Figure 430 illustrates the internal components of the DI function block, and table
481 lists the definitions of the block parameters.
Figure 430. Discrete Input Function Block Schematic
Discrete Signal

FIELD_VAL_D

Alarm Detection

OUT_D
Invert Option

SIMULATE

PV_D

MODE

201

Detailed SetupDI Function Block

Instruction Manual

August 2012

D103412X012

Modes
The Discrete Input function block supports the following modes:
Manual (Man)The block output (OUT_D [8]) is disconnected from the field and set manually.
Automatic (Auto)The block algorithm determines output.
Out of Service (OOS)The block is not processed. The OUT_D [8] status is set to Bad: Out of Service. The
BLOCK_ERR [6] parameter shows Out of Service.

Block Initialization
The Fieldbus Foundation specification requires that certain parameters in the function blocks have initial values of
uninitialized. In addition to setting the Resource block mode to AUTO, the control system or the user must change
those parameters from their uninitialized value to a valid value in order for the function block to move from the Out of
Service mode. For the DI function block, the CHANNEL [15] parameter must be initialized.

Status Handling
Under normal conditions, a Good: NonCascade status is passed through to OUT_D [8]. The block also supports the
Status Action On Failure and BLOCK_ERR [6] indications.
When SIMULATE_D [9] is enabled, FIELD_VAL_D [7], PV_D [7], and OUT_D [8] change to the simulated status. When
the block is set to Manual mode, OUT_D [7] is set to Good: Non-cascade, Constant status.

I/O Selection
To select the I/O associated with the discrete measurement, configure the value of the CHANNEL [15] parameter.
In the digital valve controller, the four classes of channels are
Valve travel
Open/Closed limit switch
Variable limit switch based on transducer block travel alarm settings.
Proximity position detection based on transducer block travel alarm settings.
The CHANNEL [15] parameter for each of the four DI blocks available in the digital valve controller may be set
independently to achieve the desired position detection. The DI block CHANNEL [15] definitions are listed in table
477. Refer to the following descriptions for details of the operation of these channels.

Valve Travel
Channel 23 provides valve travel.
0 = Closed, 1 = 100% open, 5 = 5% open, 10 = 10% open, 15 = 15% open, etc.

202

Instruction Manual

Detailed SetupDI Function Block

D103412X012

August 2012

Table 477. Channel Selection for the Discrete Input Function Block
Transducer Block Parameter(1)

Selection

Bit Number(2)

Transducer Block Index Number

23

TRAVEL_D

24

INST_ALERTS_ACTIVE:PROX_ACTIVE

74.5

33
0: Travel Open

N/A

25

INST_ALERTS_ACTIVE:PROX_ACTIVE

74.5

1: Travel Closed

26

INST_ALERTS_ACTIVE:TRAVEL_ACTIVE

74.4

2: Travel Limit Lo Lo

27

INST_ALERTS_ACTIVE:TRAVEL_ACTIVE

74.4

4: Travel Limit Lo

28

INST_ALERTS_ACTIVE:TRAVEL_ACTIVE

74.4

3: Travel Limit Hi

29

INST_ALERTS_ACTIVE:TRAVEL_ACTIVE

74.4

1: Travel Limit Hi Hi

30

INST_ALERTS_ACTIVE:PROX_ACTIVE

74.5

5: Proximity Lo Lo

31

INST_ALERTS_ACTIVE:PROX_ACTIVE

74.5

4: Proximity Lo

32

INST_ALERTS_ACTIVE:PROX_ACTIVE

74.5

3: Proximity Hi

33

INST_ALERTS_ACTIVE:PROX_ACTIVE

74.5

2: Proximity Hi Hi

1. Refer to table 414 for parameter descriptions.


2. See pages 74 and 76, Travel ALerts and Prox Alerts, for information on accessing these alerts. Refer to Appendix F for information on accessing these alerts through DeltaV.

Open/Closed Limit Switch


Channels 24 and 25 provide valve open and closed limit switch functionality for the DI block. These channels will
detect if the valve position is more than the Travel Open Alert Point for open detection or less than the Travel Closed
Alert Point for closed detection. These channels provide an adjustable deadband to clear the detected position.
0= Not Active, 1= Active

Variable Limit Switch


Channels 26 through 29 provide variable limit switch functionality for the DI block. Trip points for this limit switch
functionality are based on the Travel Alert settings in the transducer Block. The DI function block provides the same
type of position detection as the travel alerts in the transducer block. Table 478 lists the transducer block parameters
used with DI block channels 26 through 29. Refer to Travel and Prox, on page 74 for more information on the
transducer block travel alerts.
0= Not Active, 1= Active
Table 478. Transducer Block Parameters Used with Discrete Input Function Block Channels 26 through 29
(Variable Limit Switch)
Transducer Block Parameter

Parameter Function

Travel Lo Lo Alert Point

Lo Lo Limit Switch Trip Point

Travel Lo Lo Alert Deadband

Lo Lo Limit Switch Deadband

Travel Lo Alert Point

Lo Limit Switch Trip Point

Travel Lo Alert Deadband

Lo Limit Switch Deadband

Travel Hi Alert Point

Hi Limit Switch Trip Point

Travel Hi Alert Deadband

Hi Limit Switch Deadband

Travel Hi Hi Alert Point

Hi Hi Limit Switch Trip Point

Travel Hi Hi Alert Deadband

Hi Hi Limit Switch Deadband

Valve Position Proximity Detection


Channels 30 through 33 provide valve position proximity detection for the DI block. The transducer block Travel Alert
Point and Travel Alert Deadband parameters are also used with the valve position proximity, but they provide a
different function. The Travel Alert Point for the selected channel determines the center point for the position to be
detected. The Travel Alert Deadband for the selected channel sets the upper and lower trigger points, or the width of
the proximity detection band. A 1% deadzone exists above and below this band that the travel must exceed to clear

203

Instruction Manual

Detailed SetupDI Function Block


August 2012

D103412X012

the detected position. Figure 431 illustrates the operation of the proximity detection function. Travel Alert Point
refers to Travel Lo Alert Point, Travel Hi Alert Point, Travel Lo Lo Alert Point, and Travel Hi Hi Alert Point in table 479.
Travel Alert Deadband refers to Travel Lo Alert Deadband, Travel Hi Alert Deadband, Travel Lo Lo Alert Deadband, and
Travel Hi Hi Alert Deadband in table 479.
Figure 431. Discrete Input Proximity Detection Function
DISCRETE INPUT
CLEARED
DEADZONE, 1% OF TRAVEL

Valve Position

TRIGGER POINT FOR DOWNWARD VALVE


TRAVEL DETERMINED BY TRAVEL ALERT
DEADBAND

CENTER POINT OF PROXIMITY DETECTION


DETERMINED BY TRAVEL ALERT POINT

DISCRETE INPUT SET

TRIGGER POINT FOR UPWARD VALVE TRAVEL


DETERMINED BY TRAVEL ALERT DEADBAND

0= Not Active, 1= Active


Table 479 lists the transducer block parameters used for proximity detection with DI block channels 30 through 33.
Table 479. Transducer Block Parameters Used with Discrete Input Function Block Channels 30 through 33
Transducer Block Parameter

Parameter Function

Travel Lo Lo Alert Point

Lo Lo Proximity Detection Center Point

Travel Lo Lo Alert Deadband

Lo Lo Proximity Detection Width

Travel Lo Alert Point

Lo Proximity Detection Center Point

Travel Lo Alert Deadband

Lo Proximity Detection Width

Travel Hi Alert Point

Hi Proximity Detection Center Point

Travel Hi Alert Deadband

Hi Proximity Detection Width

Travel Hi Hi Alert Point

Hi Hi Proximity Detection Center Point

Travel Hi Hi Alert Deadband

Hi Hi Proximity Detection Width

Field Value Processing


The Invert bit of the IO_OPTS [13] parameter may be used to logically invert the value of FIELD_VAL_D [17] before it is
stored as PV_D [7]. PV_FTIME [16] may
be used to set the length of time that FIELD_VAL_D [17] must be in a new state before that new state is reflected in
PV_D. The PV_D [7] value goes to the mode switch where it becomes OUT_D [8] when the actual mode is AUTO.
OUT_D [8] is also tested for an alarm state.

Note
Invert is the only I/O option that the DI block supports. You can set the I/O option only when the block mode is Out of Service.

204

Instruction Manual

Detailed SetupDI Function Block

D103412X012

August 2012

Alarm Detection
To select the state that initiates an input alarm, and to set discrete alarm substatus in the output, configure the
DISC_LIM [23] parameter. You can enter any value between 0 and 255. A value of 255 disables the alarm. When
OUT_D [8] matches the DISC_LIM [23] state, the discrete value of an alarm is set.

Block Errors
Table 480 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the DI
block and are provided only for your reference.
Table 480. BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other (N/A)

Block Configuration ErrorCHANNEL set to 0 through 10 (uninitialized)

Link Configuration Error (N/A)

Simulate ActiveSimulate is enabled. Output does not reflect process conditions

Local Override (N/A)

Device Fault State Set (N/A)

Device Needs Maintenance Soon (N/A)

Input failure/process variable has Bad statusThe hardware is bad or the transducer block mode is Out of Service

Output Failure (N/A)

Memory Failure (N/A)

10

Lost Static Data (N/A)

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now (N/A)

14

Power UpSet after powerup until actual mode is not Out of Service

15

Out of ServiceThe actual mode is Out of Service (OOS). The block is not being processed.

Action on Failure
In case of hardware failure, FIELD_VAL_D [17], PV_D [7], and OUT_D [8] change to a Bad status and the BLOCK_ ERR
[6] parameter shows Process Variable has Bad Status. If the transducer block mode is Out of Service, the status of
FIELD_VAL_D [17], PV_D [7], and OUT_D [8] is set to Bad:Out of Service.

Simulation
To support testing of the control strategy, you can enable the SIMULATE_D [9] parameter. Normally the measurement
value and status used for FIELD_VAL_D [17] in the DI block reflect actual process values as provided by the transducer
block. When the SIMULATE_D [9] parameter is enabled, value and status used for FIELD_VAL_D [17] is supplied by the
user manually. To enable simulation in the DI function block, the simulate jumper must be installed. For information
on the installation of this jumper, see the Installation section.
The SIMULATE_D [9] parameter has three components:
Simulate_D enable/disable determines whether the function block will use the actual process value and status, or
Simulate Value and Simulate Status.
Transducer Value and Status reflect the process values provided by the transducer block.
Simulate Value and Status may be entered by the user when enable/disable is set to enabled.

205

Instruction Manual

Detailed SetupDI Function Block


August 2012

D103412X012

To use simulate, first install the simulate jumper in the terminal box, then set Simulate_D enable/disable to enabled,
then enter the desired values for Simulate Value and Status.
When SIMULATE_D [9] is enabled, the Simulate Active bit of the BLOCK_ERR [6] parameter is set (refer to the Block
Errors description). When the simulate jumper is installed, the Simulate Jumper bit of the transducer block parameter
SELFTEST_STATUS [78] is set.

Application Information
Figure 432 compares the operation of a standard discrete input to a proximity discrete input. With the standard
discrete input, the discrete input changes state when the valve position passes a configurable trip point. This can be
used to indicate if the valve position is above or below the trip point.
Figure 432. Proximity Discrete Input Compared to a Standard Discrete Input
STANDARD DISCRETE INPUT

DISCRETE
INPUT VALUE

PROXIMITY DISCRETE INPUT

Configurable
Band

DISCRETE
INPUT VALUE

1
0

With the proximity discrete input a configurable band can be established about a central point. Whenever the valve
position enters this configurable band, the discrete input changes state. A proximity discrete input is useful for
applications which require knowing the location of the valve when the valve is not near 0% or 100%.

DI Function Block Parameter List (table 481)


 Read/Write Capability: RO - Read Only, RW - Read Write
 Mode: The block mode(s) required to write to the parameter
 Double indentation and shaded Index Number indicates subparameter

206

Instruction Manual

Detailed SetupDI Function Block

D103412X012

August 2012

Table 481. Discrete Input Function Block Parameter Definitions


Label
PARAMETER_NAME

Index
Number

RO /
RW

Block
Mode

Range

Initial Value

Description
Data Type: Unsigned16
The revision level of the static data associated
with the function block. The revision value will
be incremented each time a static parameter
value in the block is changed.

Static Revision
ST_REV

RO

N/A

0 to 65535

Tag Description
TAG_DESC

RW

ALL

7 bit ASCII

Spaces

Data Type: Octet String


The user description of the intended
application of the block.

Strategy
STRATEGY

RW

ALL

0 to 65535

Data Type: Unsigned16


The strategy field can be used to identify
grouping of blocks. This data is not checked or
processed by the block.

Alert Key
ALERT_KEY

RW

ALL

1 to 255

Data Type: Unsigned8


The identification number of the plant unit.
This information may be used in the host for
sorting alarms, etc.

Block Mode
MODE_BLK

5
OOS
MAN
AUTO

OOS until
block is
configured,
then last valid
target

OOS+MAN+AUTO

TARGET

5.1

RW

ALL

ACTUAL

5.2

RO

ALL

OOS
OOS+MAN+A
UTO

PERMITTED

5.3

RW

ALL

NORMAL

5.4

RO

ALL

Block Error
BLOCK_ERR

Process Value Discrete


PV_D

Output Discrete
OUT_D

Simulate Discrete
SIMULATE_D

RO

RO

AUTO

N/A

Defined Bits
1: Block Configuration
Error
3: Simulate Active
7: Input Failure / Bad PV
Status
14: Powerup
15: OutofService

N/A

PV_D Status set equal to


Field_Val_D Status

OOS
MAN

OUT_STATE

Dynamic

Data Type: Bit String


0=Inactive
1=Active
This parameter reflects the error status
associated with the hardware or software
components associated with a block. Multiple
errors may be shown, see table 480.

Dynamic

Data Type: DS66


The process variable used in block execution.
Value is converted from Readback to show the
actuator position in the same units as the set
point value.
Data Type: DS66
The primary discrete value calculated as a
result of executing the function.

SIMULATE_STATUS

9.1

ALL

SIMULATE_VALUE

9.2

ALL

TRANSDUCER_STATUS

9.3

RO

ALL

TRANSDUCER_VALUE

9.4

RO

ALL

ENABLE/DISABLE

0
0=Not initialized
1=Simulation Disabled
2=Simulation Active

9.5

Data Type: DS69


Valid Bits: 7:OOS, 4:MAN, 3:AUTO
The actual, target, permitted, and normal
modes of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target

1=Simulation
Disabled

Data Type: DS83


Allows the transducer discrete input or output
to the block to be manually supplied when
simulate is enabled. When simulation is
disabled, the simulate value and status track
the actual value and status.

Transducer State
XD_STATE

10

ALL

Data Type: Uint16


Index to the text describing the states of a
discrete for the value obtained from the
transducer.

Output State
OUT_STATE

11

ALL

Data Type: Unsigned16


Index to the text describing the states of a
discrete output.

-Continued-

207

Instruction Manual

Detailed SetupDI Function Block


August 2012

D103412X012

Table 481. Discrete Input Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Grant Deny
GRANT_DENY

Index
Number

RO /
RW

Block
Mode

12.1

ALL

DENY

12.2

ALL

Status Options
STATUS_OPTS

DI Channel
CHANNEL

13

14

15

Process Value Filter Time


PV_FTIME

16

Field Value Discrete


FIELD_VAL_D

17

Update Event
UPDATE_EVT

18

UNACKNOWLEDGED

18.1

0: Program
1: Tune
2: Alarm
3: Local

All bits: 0

Data Type: DS70


Options for controlling access of host
computers and local control panels to
operating, tuning, and alarm parameters of
the block.
GRANT: 0=NA, 1=granted
DENY: 0=NA, 1=denied

All bits:0

OOS

3=Propagate Failure
Forward
8=Uncertain in MAN mode

All bits:0

Data Type: Bit String


0=Disable
1=Enable
Options the user may select for the block
processing of status.

OOS

0=undefined
23=Valve Position or
Pressure (Discrete)
24= PV > 97%
25= PV < 3%
26=PV Below LO LO limit
27=PV Below LO limit
28=PV Above HI limit
29=PV Above HI HI limit
30=PV Within Proximity of
LO LO
31=PV Within Proximity of
LO
32=PV within Proximity of
HI
33=PV within Proximity of
HI HI

0=Undefined

Data Type: Unsigned16


Defines the functionality of the discrete input.
See I/O Selection for details. Refer to table
477.

Data Type: Float


Time that FIELD_VAL_D must be in a new
state, before the change is reflected to PV_D
and OUT_D.

Data Type: DS66


Raw value of the field device discrete input,
with a status reflecting the transducer
condition.

OOS

0: Invert

ALL

Positive

RO

RW

All bits:0

Description

Data Type: Bit String


0=Disable
1=Enable
Allows you to select how the I/O signals are
processed.

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged

0=Undefined

0=Undefined
1=Update Reported
2=Updated not reported

0=Undefined

UPDATE_STATE

18.2

RO

N/A

TIME_STAMP

18.3

RO

N/A

STATIC_REVISION

18.4

RO

N/A

RELATIVE_INDEX

18.5

RO

N/A

0
-Continued-

208

Initial Value

12

GRANT

I/O Options
IO_OPTS

Range

Data Type: DS73


This alert is generated by any change to the
static data.

Instruction Manual

Detailed SetupDI Function Block

D103412X012

August 2012

Table 481. Discrete Input Function Block Parameter Definitions (Continued)


Label
PARAMETER_NAME
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED

Index
Number

RO /
RW

Block
Mode

19
19.1

Initial Value

Description

Dynamic
RW

N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

ALARM_STATE

19.2

RO

N/A

TIME_STAMP

19.3

RO

N/A

SUBCODE

19.4

RO

N/A

VALUE

19.5

RO

Alarm Summary
ALARM_SUM

Range

Data Type: DS72


The block alarm is used for all configuration,
hardware, connection failure, or system
problems in the block. The cause of the alert is
entered in the subcode field. The first alert to
become active will set the active status in the
status parameter. As soon as the unreported
status is cleared by the alert reporting
procedure, and other block alert may be
reported without clearing the active status, if
the subcode has changed.

0: Discrete alarm
7: Block Alarm

20

CURRENT

20.1

RO

All bits: 0

UNACKNOWLEDGED

20.2

RO

All bits: 0

UNREPORTED

20.3

RO

All bits: 0

DISABLED

20.4

RW

All bits: 0

Data Type: DS74


The current alert status, unacknowledged
states, unreported states, and disabled states
of the alarms associated with the function
block.
0=clear reported
0=acknowledged
0=reported
0=enabled
Data Type: Bit String
0=Disable
1=Enable
Used to set auto acknowledgement of alarms

Acknowledge Option
ACK_OPTION

21

ALL

0: Discrete
1: Block Alarm

Discrete Priority
DISC_PRI

22

ALL

0 to 15

Data Type: Unsigned8


Priority of the discrete alarm.

Discrete Limit
DISC_LIM

23

ALL

PV_STATE

Data Type: Unsigned8


State of discrete input which will generate an
alarm.

Discrete Alarm
DISC_ALM

24
N/A

0=Undefined
1=Acknowledged
2=Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
3=Active reported
4=Active not reported

UNACKNOWLEDGED

24.1

RW

ALARM_STATE

24.2

RO

N/A

TIME_STAMP

24.3

RO

N/A

SUBCODE

24.4

RO

N/A

VALUE

24.5

RO

N/A

All bits: 0

Data Type: DS72


The discrete alarm is used for indication of a
state change in selected discrete channel.

209

Instruction Manual

Detailed SetupDI Function Block


August 2012

D103412X012

View Lists
View lists allow the values of a set of parameters to be accessed at the same time. Views 1 and 2 contain operating
parameters and are defined by the Fieldbus Foundation. View 3 contains dynamic parameters and View 4 contains
static parameters with configuration and maintenance information. Views 3 and 4 are defined by the manufacturer.
Table 482. DI Function Block, View 1

Table 484. DI Function Block, View 3

Index Number

Index Number

Parameter
ST_REV

5.1

MODE_BLK.TARGET_MODE

5.1

MODE_BLK.TARGET_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.2

MODE_BLK.ACTUAL_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.3

MODE_BLK.PERMITTED_MODE

5.4

MODE_BLK.NORMAL_MODE

5.4

MODE_BLK.NORMAL_MODE

BLOCK_ERR

BLOCK_ERR

PV_D

PV_D

OUT_D

OUT_D

17

FIELD_VAL_D

17

FIELD_VAL_D

20.1

ALARM_SUM.CURRENT

20.1

ALARM_SUM.CURRENT

20.2

ALARM_SUM.UNACKNOWLEDGED

20.2

ALARM_SUM.UNACKNOWLEDGED

20.3

ALARM_SUM.UNREPORTED

20.3

ALARM_SUM.UNREPORTED

20.4

ALARM_SUM.DISABLED

20.4

ALARM_SUM.DISABLED

Table 483. DI Function Block, View 2


Index Number

210

Parameter
ST_REV

Parameter

ST_REV

10

XD_STATE

11

OUT_STATE

12.1

GRANT_DENY.GRANT

12.2

GRANT_DENY.DENY

Table 485. DI Function Block, View 4


Index Number

Parameter

ST_REV

STRATEGY

ALERT_KEY

13

IO_OPTS

14

STATUS_OPTS

15

CHANNEL

16

PV_FTIME

21

ACK_OPTION

22

DISC_PRI

23

DISC_LIM

Instruction Manual

Detailed SetupDI Function Block

D103412X012

August 2012

Field Communicator Menu Structure


DISCRETE INPUT FUNCTION BLOCK
Quick Config
Alert Key
Process Value Discrete: Status
Process Value Discrete: Value

Common Config
Alert Key
Discrete Limit
I/O Options
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Process Value Filter Time

Online
Block Error
Field Value Discrete: Status
Field Value Discrete: Value
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Output Discrete: Status
Output Discrete: Value
Process Value Discrete: Status
Process Value Discrete: Value
Status
Block Error

Advanced Config
Other
DI Channel
Output State
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Static Revision
Status Options
Transducer State

Connectors
Output Discrete: Status
Output Discrete: Value
Strategy

Tag Description
Grant Deny: Grant
Grant Deny: Deny
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Discrete Alarm: Unacknowledged
Discrete Alarm: Alarm State
Discrete Alarm: Time Stamp
Discrete Alarm: Subcode
Discrete Alarm: Discrete Value

All
Characteristics
Static Revision
Tag Description
Strategy
Alert Key
Block Mode: Target
Block Mode: Actual
Block Mode: Permitted
Block Mode: Normal
Block Error
Process Value Discrete: Status
Process Value Discrete: Value
Output Discrete: Status
Output Discrete: Value
Simulate Discrete: Simulate Status
Simulate Discrete: Simulate Value
Simulate Discrete: Transducer Status
Simulate Discrete: Transducer Value
Simulate Discrete: Simulate En/Disable
Transducer State
Output State
Grant Deny: Grant
Grant Deny: Deny
I/O Options
Status Options
DI Channel
Process Value Filter Time
Field Value Discrete: Status
Field Value Discrete: Value
Update Event: Unacknowledged
Update Event: Update State
Update Event: Time Stamp
Update Event: Static Rev
Update Event: Relative Index
Block Alarm: Unacknowledged
Block Alarm: Alarm State
Block Alarm: Time Stamp
Block Alarm: Subcode
Block Alarm: Value
Alarm Summary: Current
Alarm Summary: Unacknowledged
Alarm Summary: Unreported
Alarm Summary: Disabled
Acknowledge Option
Discrete Priority
Discrete Limit
Discrete Alarm: Unacknowledged
Discrete Alarm: Alarm State
Discrete Alarm: Time Stamp
Discrete Alarm: Subcode
Discrete Alarm: Discrete Value

211

Detailed SetupDI Function Block


August 2012

212

Instruction Manual
D103412X012

Instruction Manual

Calibration

D103412X012

August 2012

Section 5 Calibration 5-5Calibration Overview


When a DVC6200f digital valve controller is ordered as part of a control valve assembly, the factory mounts the digital
valve controller on the actuator and connects the necessary tubing, then sets up and calibrates the controller.
For digital valve controllers that are ordered separately, recalibration of the pressure sensors generally is unnecessary.
However, after mounting on an actuator, perform the initial setup then calibrate travel by selecting Configure / Setup >
Calibration > Auto Calibration. For more detailed calibration information, refer to the following calibration procedures.

Calibration
Field Communicator

TB > Configure/Setup > Calibration

Auto Calibration This procedure automatically calibrates the travel. The calibration procedure uses the valve and
actuator stops as the 0% and 100% calibration points. See page 214.
Manual Calibration This procedure permits manual calibration of the travel. This calibration procedure allows you
to determine the 0% and 100% calibration points. See page 214.
Relay This procedure permits adjustment of the pneumatic relay. See page 215.
Supply Pressure This procedure permits calibrating the supply pressure sensor. Normally the sensor is calibrated at
the factory and should not need calibration. See page 216.
Pressure A This procedure permits calibrating the pressure A sensor. Normally the sensor is calibrated at the
factory and should not need calibration. See page 217.
Pressure B This procedure permits calibrating the pressure B sensor. Normally the sensor is calibrated at the
factory and should not need calibration. See page 217.

Note
The Instrument Mode must be Out Of Service and the Protection set to None before the instrument can be calibrated.
If you are operating in burst mode, we recommend that you disable burst before continuing with calibration. Once calibration is
complete, burst mode may then be turned back on.

WARNING
During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release of
pressure or process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the
process fluid.

213

Instruction Manual

Calibration
August 2012

D103412X012

If a doubleacting relay is used, you will be prompted to run the relay adjustment when auto or manual calibration is
selected. Select Yes to adjust the relay, select No to proceed with calibration. For additional information, refer to Relay
Adjustment in this section.

Note
Relay Adjustment is only available for the doubleacting relay (Relay A).

Auto Calibration
Field Communicator

TB > Configure/Setup > Calibration > Auto Calibration

Follow the prompts on the Field Communicator display to automatically calibrate travel.
1. The auto calibration procedure is automatic. It is completed when the Calibration menu appears.
During calibration, the instrument seeks the high and low end points and the minor loop feedback (MLFB) and output
bias. By searching for the end points, the instrument establishes the limits of physical travel, i.e. the actual travel 0 and
100% positions. This also determines how far the relay beam swings to calibrate the sensitivity of the MLFB sensor.
2. Place the instrument In Service and verify that the travel properly tracks the current source.

Manual Calibration
Field Communicator

TB > Configure/Setup > Calibration > Manual Calibration

Note
0% Travel = Valve Closed ; 100% Travel = Valve Open

1. From the adjustment menu, select the direction and size of change required to set the travel at 0% (move the valve
to close). Selecting large, medium, and small adjustments causes changes of approximately 10.0%, 1.0%, and 0.1%,
respectively, to the travel feedback movement. Selecting Next will implement the adjustment.
If another adjustment is required, repeat step 1. Otherwise, select Done and go to step 2.
2. From the adjustment menu, select the direction and size of change required to set the travel to 100% (move the
valve to open).
If another adjustment is required, repeat step 2. Otherwise, select Done and go to step 3.
3. Enter the name of the person performing the calibration procedure.
4. Enter the location of the calibration procedure.
5. Enter the date of the calibration procedure.
6. Place the Transducer Block Mode in Manual and verify that the travel properly tracks the setpoint changes.

214

Instruction Manual

Calibration

D103412X012

August 2012

Relay
Field Communicator

TB > Configure/Setup > Calibration > Relay

Follow the prompts on the Field Communicator display to check relay adjustment. Replace the digital valve controller
cover when finished.

Note
Relay B and C are not useradjustable.

DoubleActing Relay
The doubleacting relay is designated by Relay A on a label affixed to the relay itself. For doubleacting actuators, the
valve must be near midtravel to properly adjust the relay. The Field Communicator will automatically position the
valve when Relay is selected.

CAUTION
Care should be taken during relay adjustment as the adjustment disc may disengage if rotated too far.

Rotate the adjustment disc, shown in figure 51, until the output pressure displayed on the Field Communicator is
between 50 and 70% of supply pressure. This adjustment is very sensitive. Be sure to allow the pressure reading to
stabilize before making another adjustment (stabilization may take up to 30 seconds or more for large actuators).
Figure 51. Relay A Adjustment (Shroud Removed for Clarity)

FOR SINGLEACTING DIRECT


RELAYS: ROTATE ADJUSTMENT
DISC IN THIS DIRECTION UNTIL IT
CONTACTS THE BEAM
FOR DOUBLEACTING RELAYS:
ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO DECREASE
OUTPUT PRESSURE

ADJUSTMENT DISC

FOR DOUBLEACTING RELAYS:


ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO INCREASE
OUTPUT PRESSURE
W9034

215

Instruction Manual

Calibration
August 2012

D103412X012

If the low bleed relay option has been ordered stabilization may take approximately two minutes longer than the
standard relay.
Relay A may also be adjusted for use in singleacting direct applications. Rotate the adjustment disc as shown in figure
51 for singleacting direct operation.

SingleActing Relays
WARNING
For instrument level PD only:
If the unused port is monitoring pressure, ensure that the pressure source conforms to ISA Standard 7.0.01 and does not
exceed the pressure supplied to the instrument.
Failure to do so could result in personal injury or property damage caused by loss of process control.

SingleActing Direct Relay


The singleacting direct relay is designated by Relay C on a label affixed to the relay itself. Relay C requires no
adjustment.
SingleActing Reverse Relay
The singleacting reverse relay is designated by Relay B on a label affixed to the relay itself. Relay B is calibrated at the
factory and requires no further adjustment.

Supply Pressure Sensor


Field Communicator

TB > Configure/Setup > Calibration > Supply Pressure

Note
The pressure sensor is calibrated at the factory and should not require calibration.

To calibrate the supply pressure sensor, connect an external reference gauge to the output side of the supply
regulator. The gauge should be capable of measuring maximum instrument supply pressure. Select Follow the
prompts on the Field Communicator display to calibrate the instrument's supply pressure sensor.
1. Select a) Zero Only, or b) Zero and Span (gauge required).
a. If Zero Only calibration is selected, adjust the supply pressure regulator to remove supply pressure from the
instrument. Press OK. Once calibration is complete, go to step 5.
b. If Zero and Span calibration is selected, adjust the supply pressure regulator to remove supply pressure from the
instrument. Press OK. Adjust the supply regulator to the maximum instrument supply pressure. Press OK.
Proceed with step 2.

216

Instruction Manual
D103412X012

Calibration
August 2012

2. The following message appears:


Use the Increase and
Decrease selections until
the displayed pressure
matches the instrument
supply pressure.
Press OK when you have read this message.
3. The value of the pressure appears on the display.
4. From the adjustment menu, select the direction and size of adjustment to the displayed value. Selecting large,
medium, and small adjustments causes changes of approximately 3.0 psi/0.207 bar/20.7 kPa, 0.30 psi/0.0207
bar/2.07 kPa, and 0.03 psi/0.00207 bar/0.207 kPa, respectively. Adjust the displayed value until it matches the
supply pressure, select Done and go to step 5.
5. Place the instrument In Service and verify that the displayed pressure matches the measured supply pressure.

Pressure A or B Sensor
Field Communicator

TB > Configure/Setup > Calibration > Pressure A

Field Communicator

TB > Configure/Setup > Calibration > Pressure B

To calibrate the output pressure sensor, connect an external reference gauge to the output being calibrated. The
gauge should be capable of measuring maximum instrument supply pressure. Select . Follow the prompts on the Field
Communicator display to calibrate the instrument's output pressure sensor.
1. Adjust the supply pressure regulator to the maximum instrument supply pressure. Press OK.
2. The instrument reduces the output pressure to 0. The following message appears.
Use the Increase and
Decrease selections
until the displayed
pressure matches the
output x pressure.
Press OK when you have read the message.
3. The value of the output pressure appears on the display. Press OK to display the adjustment menu.
4. From the adjustment menu, select the direction and size of adjustment to the displayed value. Selecting large,
medium, and small adjustments causes changes of approximately 3.0 psi/0.207 bar/20.7 kPa, 0.30 psi/0.0207
bar/2.07 kPa, and 0.03 psi/0.00207 bar/0.207 kPa, respectively. If the displayed value does not match the output
pressure, press OK, then repeat this step (step 4) to further adjust the displayed value. When the displayed value
matches the output pressure, select Done and go to step 5.

217

Instruction Manual

Calibration
August 2012

D103412X012

5. The instrument sets the output pressure to full supply. The following message appears.
Use the Increase and
Decrease selections
until the displayed
pressure matches the
output x pressure.
Press OK when you have read the message.
6. The value of the output pressure appears on the display. Press OK to display the adjustment menu.
7. From the adjustment menu, select the direction and size of adjustment to the displayed value. If the displayed value
does not match the output pressure, press OK, then repeat this step (step 7) to further adjust the displayed value.
When the displayed value matches the output pressure, select Done and go to step 8.
8. Place the instrument In Service and verify that the displayed pressure matches the measured output pressure.

218

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

Section 6 Viewing Device Variables and Diagnostics6-6View Lists


View Lists allow the values of a set of parameters to be accessed at the same time. View lists are available for the
resource and transducer blocks, and the function blocks.
Resource Blocktables 44 through 47

OS Function Blocktables 449 through 452

Transducer Blocktables 415 through 423

AI Function Blocktables 458 through 461

AO Function Blocktables 426 through 429

MAI Function Blocktables 465 through 468

PID Function Blocktables 433 through 437

DO Function Blocktables 473 through 476

IS Function Blocktables 441 through 444

DI Function Blocktables 482 through 485

Note
Views Lists are used by hosts for efficient monitoring of multiple parameters. Normally you will not be aware of view list usage, as
they are hidden by the host software.

Resource Block
This section contains information on the DVC6200f digital valve controller resource block. The resource block defines
the physical resources of the device. The resource block also handles functionality that is common across multiple
blocks. The block has no linkable inputs or outputs.
Table 61. Resource Block BLOCK_ERR Conditions
Condition Number

Condition Name and Description

Other Set if a device initialization error occurred.

Block Configuration Error Set if FEATURE_SEL, CYCLE_SEL, or CYCLE_TYPE is set incorrectly.

Link Configuration Error N/A

Simulate Active Indicates that the simulation jumper is in place on the aux terminals. This is not an indication that the I/O
blocks are using simulation data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].

Local Override N/A

Device Fault State N/A

Device Needs Maintenance Soon Indicates a Maintenance PlantWeb Alert condition is active.

Input failure/process variable had Bad status N/A

Output failure N/A

Memory failure Indicates a pending Flash or NVM failure.

10

Lost Static Data Indicates failure of the memory containing static parameters

11

Lost NV Data Indicates failure of the memory containing nonvolatile parameters.

12

Readback Check Failed NA

13

Device Needs Maintenance Now Indicates a Failed PlantWeb Alert condition is active.

14

Power Up Indicates the device has been powered up and the Resource Block is not running normally.

15

Out of Service (MSB) The resource block actual mode is Out of Service.

219

Viewing Device Variables and Diagnostics

Instruction Manual

August 2012

D103412X012

Device Diagnostics
Resource Block Error
(RB > Device Diagnostics > Resource Block Error)
Field Communicator

RB > Device Diagnostics > Resource Block Error

Block Error (BLOCK_ERR [6]) indicates an error status associated with hardware or software for the resource block.
Table 61 lists conditions reported in the BLOCK_ERR [6] parameter. Conditions in italics are not applicable for the
resource block and are provided only for your reference.

Device State
Field Communicator

RB > Device Diagnostics > Device State

Device State (RS_STATE [7]) indicates the state of the function blocks. Four states are possible:

 InitializationThe instrument enters this state upon restart or failure. The function blocks are in the IMan mode.

During the initialization state, all unreported function block alarms are automatically confirmed and acknowledged.
Once the instrument is considered operational, block execution is scheduled and the instrument state moves to
Online.

 OnlineThe instrument will be in this state if it is operational. The function blocks are initially in the Auto mode, but
can be changed to a higher level mode.

 StandbyThe instrument enters this state if the resource block mode is Out of Service (OOS). In this state all

function block modes are forced to Out of Service. The transducer block mode is not affected. When the resource
block mode is changed to Auto, the instrument state moves to Online.

 Failure The instrument moves to this state whenever a hardware or memory failure is detected which would
prevent reliable operation. All function blocks and the transducer block modes are Out of Service.

Write Lock
Field Communicator

RB > Device Diagnostics > Write Lock

Write Alarm: Alarm State


Write Lock
Write Lock (WRITE_LOCK [34]) determines if writes are permissible to other device parameters. The Soft Write Lock
feature must be selected to be able to use Write Lock (see Selecting Features). When Write Lock is set to Locked, no
writes are permitted to any parameters within the device except to set Write Lock to Not Locked. When locked, the
block functions normally, updating inputs and outputs and executing algorithms. When Write Lock is set to Not
Locked, the Write Alarm alert is active.

220

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

Block Alarm
Field Communicator

RB > Device Diagnostics > Block Alarm

The Block Alarm (BLOCK_ALM [36]) is used for all configuration, hardware, connection failure or system problems in
the block.
Block Alarm: Alarm State
Block Alarm: Alarm State (BLOCK_ALM. ALARM_STATE [36.2]) indicates the state of the Block Alarm. Five states are
possible:






Undefined
Clear reported
Clear not reported
Active reported
Active not reported

Block Alarm: Unacknowledged


Block Alarm: Unacknowledged (BLOCK_ALARM. UNACKNOWLEDGED [36.1])
1 = Undefined
2 = Acknowledged
3 = Unacknowledged

Maintenance
Field Communicator

RB > Device Diagnostics > Maintenance

Restart Actions

WARNING
Restarting the instrument may cause loss of process control. To avoid personal injury and property damage caused by the
release of pressure of process fluid, isolate the valve from the process and equalize pressure on both sides of the valve or
bleed off the process fluid.

You can restart the instrument to reset parameters, links, etc. within the instrument. However, due to the effect that a
restart can have on the instrument, and therefore the control loop, restarting the instrument should be used
cautiously and only as a last measure. The following procedure describes how to use Restart Options to restart the
instrument with a Field Communicator. You can also restart the instrument using ValveLink software or from a host
system using the Restart method included with the device description (DD) software.
You can restart the instrument any time it is connected to an active segment.
Field Communicator

RB > Device Diagnostics > Maintenance > Restart Actions

1. Restart informs you about what can happen when an instrument restart is performed. Select Yes to continue, or No
to abort without restarting.
2. Select the desired restart action or select EXIT to exit Restart. Select Help (not the Help button) to get information
on restart actions.

221

Viewing Device Variables and Diagnostics

Instruction Manual

August 2012

D103412X012

There are two different restarts: Restart Processor, and Restart with Defaults:
When selecting either of these options, Restart informs you of the consequences of this action and asks if you want to
continue. Select Yes to perform the restart action, select No to select another action or exit. Restart informs you when
the restart is completed. You must acknowledge the message to continue.
Restart ProcessorPerforming a Restart Processor has the same effect as removing power from the instrument and
reapplying power. Configuration and calibration do not change.
Restart with DefaultsPerforming a Restart with Defaults should be done with care. This restart resets most of the
static and nonvolatile parameters for all of the blocks in the instrument to their initial value, as listed in table 42. After
a Restart with Defaults, you should place the instrument in service (the transducer block mode to auto) and run Device
Setup and download the instrument configuration from the control system to properly setup the instrument. You also
may need to reestablish communication links and trends.
Fault StateFault State (FAULT_STATE [28]), when active, indicates that the resource block is currently forcing the
output block to perform its FSTATE action. Selecting Fault State enables the ability to manually set and clear the
fault state.
Set Fault StateSelecting Set Fault State (SET_FSTATE [29]) changes the Fault State (FAULT_STATE [28]) to Active.
Setting Set FState (SET_FSTATE [29]) to SET manually places the instrument in the fault state.
Clear Fault StateSetting Clear FState (CLR_FSTATE [30]) to CLEAR clears the device fault state, if no faults are
currently active. You can test the actions the output blocks will perform by manually setting fault state active.

Device Variables
Instrument
Field Communicator

RB > Device Variables > Instrument

The following parameters are contained in the the Instrument menu of the resource block.

Identification
Device IDThe 32 character Device ID (DEVICE_ID [54]).
Electronics Serial NumberThe Electronics Serial Number (ELECTRONICS_SN [49]) set at the factory.
Factory Serial NumberThe Factory Serial Number (FACTORY_SN [50]) is the instrument serial number set at the
factory.
Field Serial NumberThe Field Serial Number (FIELD_SN [51]) is the serial number of the valve and actuator on
which the instrument is mounted.
Tag DescriptionThe Tag Description (TAG_DESC [2]) is unique description of each block within the digital valve
controller, used to describe the intended application for the block. Follow the prompts on the Field Communicator
to enter an up to 32 character description for the block in the Tag Description field. (This parameter is read/write.)
StrategyStrategy (STRATEGY [3]) permits strategic grouping of blocks so the operator can identify where the
block is located. The blocks may be grouped by plant area, plant equipment, etc. Enter a value between 0 and
65535 in the Strategy field.

222

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

ManufacturerManufacturer Identification (MANUFAC_ID [10]) identifies the manufacturer of the instrument. It is


used by the host system to locate the DD file for the device. For Fisher the Manufacturer ID is 0x5100.
Device TypeDevice Type (DEV_TYPE [11]) identifies the type of device. It is used by the host system to locate the
DD file for the device. For a DVC6200f digital valve controller with Standard Control the device type is 0x4602.

Version
Device RevisionDevice Revision (DEV_REV [12]) identifies the device revision number. It is used by the host system
to locate the DD file for the device.
Firmware RevisionFirmware Revision (FIRMWARE_REV_ALL [47.6]) shows all device firmware revisions currently in
operation.
Standby Firmware RevisionStandby Firmware Revision (STBY_FIRMWARE_REV_ALL [55.6]) shows all device
firmware revisions currently in standby.
Hardware RevisionHardware Revision(HARDWARE_REV[48]) identifies the electronic hardware revision.
ITK VersionITK Version (ITK_VER [41]) identifies the major version of the Interoperability Tester used by the
Fieldbus Foundation in certifying the device as interoperable. This device revision meets the requirements of
version 5.

Options
Field Communicator

RB > Device Variables > Options

The following parameters are contained in the the Options menu of the resource block.
Diagnostic OptionsDiagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the
instrument.
Function Block OptionsFunction Block Options (FB_OPTIONS [44]) shows which function blocks are licenced and
enabled in the instrument.
Miscellaneous OptionsMiscellaneous Options (MISC_OPTIONS [46]) indicates which miscellaneous licensing
options are enabled.
Features AvailableFeatures (FEATURES [17]) shows the supported resource block options.

DD Information
Field Communicator

RB > Device Variables > DD Information

DD Information contains information about the Device Description (DD).

Transducer Block
This section contains information on the DVC6200f digital valve controller transducer block. Descriptions of all
transducer block parameters are included. The transducer block decouples function blocks from the local output
functions required to command output hardware. The transducer block typically contains setup and calibration
information.

223

Viewing Device Variables and Diagnostics


August 2012

Instruction Manual
D103412X012

Device Diagnostics
Active PlantWeb Alerts
Field Communicator

TB > Device Diagnostic > Active PlantWeb Alerts

To view the active PlantWeb alerts select Active PlantWeb Alerts.

Alert Conditions
Field Communicator

TB > Device Diagnostic > Active Conditions

Instrument Alert Conditions, when enabled, detect many operational and performance issues that may be of interest.
The alert conditions for each group of alerts are listed below. If there are no alerts active for a particular group the
group will not be displayed on the Field Communicator.
Electronicsif an electronics alert is active it will appear under ELECT ALERTS
Drive Current
Drive Current AlertThis alert is active when the difference between the expected Drive Current and the actual Drive
Current has exceeded the Drive Current Alert Time.
Drive Signal
Drive Signal AlertThe Drive Signal Alert is active if one of the following conditions exist:
Where Zero Power Condition is defined as closed:
Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%
Where Zero Power Condition is defined as open:
Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%
Processor Impaired
Program Memory AlertThis alert is active if a pending flash or NVM failure is present.
Static Memory AlertThis alert is active when there is a failure of the FRAM memory where static parameters are
stored.
Processor AlertThis alert is active when there is a failure of the main processor.
I/O Processor AlertThis alert is active when there is a failure of the I/O processor.
ConfigurationIf a configuration alert is active it will appear under CONFIG ALERTS
Output Block Timeout
Output Block Timeout AlertThis alert is active if the output block has not executed for a period of time longer than
the configured timeout.

224

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

Blocks Set to Default


Blocks Set to Default AlertThis alert is active if the resource block has undergone Restart with Defaults. This will stay
active until the transducer block is changed from Out of Service.
SensorIf a configuration alert is active it will appear under SENSOR ALERTS
Travel Sensor
Travel SensorThis alert is active if the Travel Sensor reading is outside the functional range, or the sensor becomes
disconnected.
Pressure Sensors
Pressure A Sensor AlertThis alert is active if the Port A Pressure Sensor reading is outside the functional range.
Pressure B Sensor AlertThis alert is active if the Port B Pressure Sensor reading is outside the functional range.
Supply Pressure Sensor AlertThis alert is active if the Pressure Sensor reading is outside the functional range.
Pressure Fallback
Pressure Fallback AlertThis alert is active if a travel sensor failure or a gross travel deviation has resulted in fallback to
pressure control.
Temperature Sensor
Temperature Sensor AlertThis alert is active if the temperature sensor reading is outside the functional range of the
sensor.
EnvironmentIf an environment alert is active it will appear under ENVIRO ALERTS
Supply Pressure
Supply Pressure Hi AlertThis alert is active if the supply pressure exceeds the Supply Pressure Hi Alert.
Supply Pressure Lo AlertThis alert is active if the supply pressure exceeds the Supply Pressure Lo Alert.
Temperature Limit
Temperature Hi AlertThis alert is active if the temperature is greater than the Temperature Hi Alert Point.
Temperature Lo AlertThis alert is active if the temperature is greater than the Temperature Lo Alert Point.
TravelIf a travel alert is active it will appear under TRAVEL ALERTS
Travel Deviation
Travel Deviation AlertThis alert is active if the Travel deviation exceeds the Travel Deviation Alert Point by more than
the Travel Deviation Time.
Travel Limit
Travel Limit Hi Hi AlertThis alert is active if Travel exceeds the Travel Limit Hi Hi Alert point.
Travel Limit Lo Lo AlertThis alert is active if Travel is lower than the Travel Limit Lo Lo Alert point.
Travel Hi/Lo
Travel Limit Hi AlertThis alert is active if Travel exceeds the Travel Limit Hi Alert point.
Travel Limit Lo AlertThis alert is active if Travel is lower than the Travel Limit Lo Alert point.
ProximityIf a proximity alert is active it will appear under PROX ALERTS
Travel Open
Travel Open AlertThis alert is active if the travel is greater than the travel open alert point.

225

Viewing Device Variables and Diagnostics

Instruction Manual

August 2012

D103412X012

Travel Closed
Travel Closed AlertThis alert is active if the travel is greater than the travel closed alert point.
Proximity
Proximity Hi Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Hi Alert Point
and the Travel Hi Hi Deadband.
Proximity Hi AlertThis alert is active if the Travel is within the detection band set by the Travel Hi Alert Point and the
Travel Hi Deadband.
Proximity Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Alert Point and the
Travel Lo Deadband.
Proximity Lo Lo AlertThis alert is active if the Travel is within the detection band set by the Travel Lo Lo Alert Point
and the Travel Lo Lo Deadband.
Travel HistoryIf a travel history alert is active it will appear under TVL HIST ALERTS
Cycle Counter
Cycle Counter AlertThis alert is active if the Cycle Counter exceeds the Cycle Count Alert Point.
Travel Accumulator
Travel Accumulator AlertThis alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point.
Performanceif a performance alert is active it will appear under PERF ALERTS
Performance Critical
Performance Critical AlertThis alert is active if the instrument is no longer able to control the valve or performance
has been dramatically reduced.
Performance Reduced AlertThis alert is active if the instrument has detected a reduction in performance.
Performance Information AlertThis alert is active if the instrument has detected a condition that may pertain to
control performance.

Status
Field Communicator

TB > Device Diagnostic > Status

Self Test Status


Integrator SuspendedThe integrator function is temporarily suspended. The integrator is suspended if any of the
following conditions are met:
The setpoint and actual travel are greater than 98% or less than 2%.
The set point is in cutoff
The Transducer block is Out of Service (OOS)
Integrator Limited LoIndicates the integrator reached its limit and cannot move the valve any further. High valve
friction may cause this situation.
Integrator Limited HiIndicates the integrator reached its limit and cannot move the valve any further. High valve
friction may cause this situation.

226

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

Travel Sensor Span ErrorIndicates that span between the endpoints of travel are not far enough apart. This error is
reported during automatic calibration.
MLFB ErrorIndicates that the Minor Loop Feedback sensor gave a nonvalid value during automatic calibration.
Travel Sensor Hi ErrorIndicates the travel sensor has reported a travel position that is significantly above the normal
operating range, and has failed.
Travel Sensor Lo ErrorIndicates the travel sensor has reported a travel position that is significantly below the normal
operating range, and has failed.
Pressure B Sensor FailureIndicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
Pressure A Sensor FailureIndicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
Supply Sensor FailureIndicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
IOP FailureIndicates the I/O processor has failed.
Drive Current AlertIndicates that the Drive Current has exceeded the Drive Current Alert Point for more than the Drive
Current Alert Time.
Simulate Jumper ONIndicates the simulate jumper is connected to the DVC6200f between the two AUX terminals.

Block Error
Table 62 lists conditions reported in the BLOCK_ERR [6] and XD_ERROR [11] parameters. Conditions in italics are not
applicable for the transducer block and are provided only for your reference.
Table 62. Transducer Block BLOCK_ERR and XD_ERROR Conditions
Condition Number

Condition Name and Description

Other (N/A)

Block Configuration Error Indicates that one of the following parameters have been configured out of the proper range: 15,
16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.

Link Configuration Error (N/A)

Simulate Active Indicates that alerts are being simulated. This is not an indication that the I/O blocks are using simulation
data. See AO block parameter SIMULATE [10] and DO block parameter SIMULATE_D [10].

Local Override (N/A)

Device Fault State - (NA)

Maintenance Needed Soon (N/A)

Input failure/process variable has Bad status (N/A)

Output failure (N/A)

Memory failure (N/A)

10

Lost Static Data Indicates that manufacturing functional or thermal tests were incomplete

11

Lost NV Data (N/A)

12

Readback Check Failed (N/A)

13

Device Needs Maintenance Now Indicates that manufacturing functional or thermal tests were incomplete

14

Power Up (N/A)

15

Out of Service Indicates Out of Service Mode.

227

Viewing Device Variables and Diagnostics

Instruction Manual

August 2012

D103412X012

Device Record
Field Communicator

TB > Device Diagnostic > Device Record

The following parameters are contained in the Device Record menu of the transducer block.
Maximum Recorded TemperatureMaximum Recorded Temperature (TEMP_MAX [86.1]) shows the maximum
temperature the instrument has experienced since installation.
Maximum Recorded Temperature TimeMaximum Recorded Temperature Time (TEMP_MAX_TIME [86.2]) shows
the date and time when the Temperature Maximum occurred.
Minimum Recorded TemperatureMinimum Recorded Temperature (TEMP_MIN [86.3]) shows the minimum
temperature the instrument has experienced since installation.
Minimum Recorded Temperature TimeMinimum Recorded Temperature Time (TEMP_MIN_TIME [86.4]) shows
the date and time when the Temperature Minimum occurred.
Maximum Recorded Supply PressureMaximum Recorded Supply Pressure (SUPPLY_PRESS_MAX [86.5]) shows the
maximum supply pressure the instrument has experienced since installation.
Maximum Recorded Supply Pressure TimeMaximum Recorded Supply Pressure Time (SUPP_PRESS_MAX_TIME
[86.6]) shows the date and time when the Supply Pressure Maximum occurred.
Minimum Recorded Supply PressureMinimum Recorded Supply Pressure (SUPP_PRESS_MIN [86.7]) shows the
minimum supply pressure the instrument has experienced since installation.
Minimum Recorded Supply Pressure TimeMinimum Recorded Supply Pressure Time (SUPP_PRESS_MIN_TIME
[86.8]) shows the date and time when the Supply Pressure Minimum occurred.

Stroking the Digital Valve Controller Output


Field Communicator

TB > Device Diagnostic > Stroke Valve

Stroke Valve is used to confirm proper valve operation. Follow the prompts on the Field Communicator display to
select from the following: Done, Ramp Open, Ramp Closed, Ramp to Target, Step to Target, and Stop.
DoneSelect this if you are done. All ramping is stopped when DONE is selected.
Ramp Openramps the travel toward open at the rate of 1.0% per second of the ranged travel.
Ramp Closedramps the travel toward closed at the rate of 1.0% per second of the ranged travel.
Ramp to Targetramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.
Step to Targetsteps the travel to the specified target.
Stopstops the command.

228

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

Trend
Field Communicator

TB > Device Diagnostic > Trend

Trend chart of Setpoint (FINAL_VALUE.VALUE [13.2]), Travel (TRAVEL.VALUE [34.2]), and Pressure A
(PRESSURE_A.VALUE [36.2]).

Device Variables
Field Communicator

TB > Device Variables

All Block Modes


Block Mode: Target
The Target (TARGET [5.1]) mode is the mode requested by the user or host system. Generally, only one mode is
allowed to be set, and it must be a permitted mode as defined by the permitted attribute of the mode parameter.
Additionally, all cascade targets (Cas, Rcas) must have AUTO set.
Block Mode: Actual
This is the current mode of the block. The actual (ACTUAL [5.2]) mode may differ from the target mode due to
operating conditions of the block.

Note
Block Mode:Actual drops the AUTO bit for the cascade targets. For example, target mode might have Cas and Auto set, but actual
mode will only have Cas set.

Block Mode: Permitted


The permitted (PERMITTED [5.3]) mode defines the modes allowed for the block. This is set by the user or host system
but is restricted by the instrument to modes supported by the instrument for the particular block. Any change request
to the Target or Normal attribute is checked against the permitted attribute to ensure the requested mode is
permitted. When setting the Permitted mode, there is no check against any of the other attributes (Normal or Target
modes). Therefore, the normal or target mode attributes may have a value that is not permitted because the
permitted attribute was modified after the Normal or Target mode was set. This will have no effect on the instrument
until the user attempts to modify the Target or Normal mode. At this time these attributes are tested against the
Permitted modes, thus the user cannot change the Normal or Target modes to what was formerly permitted.
Block Mode: Normal
The normal (NORMAL [5.4]) mode is the mode the block should be in during normal operating conditions. The normal
mode is set by the user or host system and can only be set to a permitted mode (see permitted mode). The user or
host system can compare the actual mode to the normal mode and, based on the results, determine if the block is
operating normally.

229

Viewing Device Variables and Diagnostics

Instruction Manual

August 2012

D103412X012

AO Control - PreCharacterization
Setpoint
Setpoint (FINAL_VALUE.VALUE [13.2]) shows the value of the setpoint in % (percent) of ranged travel or pressure.
Setpoint is used for both travel and pressure control. This parameter will be written directly if the transducer block is in
MAN mode, or will be written automatically by the AO block if the transducer block is in AUTO mode.
Setpoint Status
Shows the Foundation Fieldbus status of Setpoint Value (FINAL_VALUE.STATUS [13.2]); Good, Uncertain, or Bad.
Travel (DeChar)
Travel (FINAL_POSITION_VALUE.VALUE [17.2]) shows the value of the travel in % (percent) of ranged travel. Travel
always represents how far the valve is open.

AO ControlPost Characterization
Travel Target
Travel target is the output from the characterization function.
Travel
Travel (TRAVEL.VALUE [34.2]) displays the actual position of the valve in percent (%) of calibrated travel.
Travel Status
Shows the Foundation Fieldbus status of Travel Value (TRAVEL.STATUS [34.1]); Good, Uncertain, or Bad.

DO Control
Setpoint(D)
Discrete Setpoint (SETPOINT_D.VALUE [32.2]) shows the value of the setpoint in discrete values.
0 = closed, 1 = open, 5, 10, 15... = setpoint in 5% units. This parameter will be written directly if the transducer block is
in MAN mode, or will be written automatically by the DO block if the transducer block is in AUTO mode.
Travel(D)
Travel (TRAVEL_D.VALUE [33.2]) shows the value of the setpoint in discrete values.
0 = closed, 1 = open, 5, 10, 15... = setpoint in 5% units.

Input Characterization
Input Characterization (INPUT_CHAR [50]) defines the relationship between the setpoint specified by the output
function block and the desired valve position.

230

Instruction Manual

Viewing Device Variables and Diagnostics

D103412X012

August 2012

Travel/Pressure State
Travel/Pressure State (TVL_PRESS.STATE [41.2]) indicates if the instrument is being used for travel control (position
control) or as an I/P (pressure control).

PD Inside Status
PD Inside Status shows the status of Performance Diagnostics.

Protection
Indicates the status of Protection.

Drive Signal
Drive Signal (DRIVE_SIGNAL [53]) indicates the drive signal, as a percentage of the maximum drive available, going to
the I/P converter from the printed wiring board. In most applications, the drive signal ranges between 50% and 75% of
the maximum drive signal.

Temperature
Temperature (TEMPERATURE [48]) displays the internal temperature of the instrument in either degrees Fahrenheit or
Celsius.

Cycle Counter
Cycle Counter (CYCLE_COUNT [73]) records the number of times the travel changes direction. The change in direction
must occur after the deadband has been exceeded before it can be counted as a cycle.

Travel Accumulator
Travel Accumulator (TRAVEL_ACCUM [72]) indicates the total change in travel, in percent of ranged travel. The
accumulator only increments when travel exceeds the deadband. Then the greatest amount of change in one
direction from the original reference point (after the deadband has been exceeded) will be added to the Travel
Accumulator.

Travel Count
Travel Count (TVL_COUNT [43.1]) is the Travel Sensor readback displayed in A/D counts.

231

Viewing Device Variables and Diagnostics


August 2012

Instruction Manual
D103412X012

Pressures
Supply
Supply (SUPPLY_PRESSURE_VALUE [35.2]) shows the value of the supply pressure in psi, bar, kPa, inHg, inH2O, or
kg/cm2.
Pressure A
Pressure A (PRESSURE_A.VALUE [36.2]) shows the value of Output Pressure A in psi, bar, kPa, inHg, inH2O, or kg/cm2.
Pressure B
Pressure B (PRESSURE_B.VALUE [37.2]) shows the value of Output Pressure B in psi, bar, kPa, inHg, inH2O, or kg/cm2.
A Minus B
A Minus B (PRESSURE_DIFF.VALUE [38.2]) shows the value of the output pressure differential in psi, bar, kPa, inHg,
inH2O, or kg/cm2.

232

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

Section 7 Maintenance and Troubleshooting7-7The DVC6200f digital valve controller enclosure is rated Type 4X and IP66, therefore periodic cleaning of internal
components is not required. If the DVC6200f is installed in an area where the exterior surfaces tend to get heavily
coated or layered with industrial or atmospheric contaminants, however, it is recommended that the vent (key 52) be
periodically inspected to ensure it is fully open. If the vent appears to be clogged, it can be removed, cleaned and
replaced. Lightly brush the exterior of the vent to remove contaminants and run a mild water/detergent solution
through the vent to ensure it is fully open. Allow the vent to dry before reinstalling.

WARNING
Personal injury or property damage can occur from cover failure due to overpressure. Ensure that the housing vent
opening is open and free of debris to prevent pressure buildup under the cover.

WARNING
To avoid static discharge from the plastic cover when flammable gases or dust are present, do not rub or clean the cover
with solvents. To do so could result in a spark that may cause the flammable gases or dust to explode, resulting in personal
injury or property damage. Clean with a mild detergent and water only.

WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing
any maintenance procedures on the DVC6200f digital valve controller:
Always wear protective clothing, gloves, and eyewear.
Do not remove the actuator from the valve while the valve is still pressurized.
Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
from both sides of the valve.
Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression.
Use lockout procedures to be sure that the above measures stay in effect while you work on the equipment.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.

WARNING
When using natural gas as the supply medium, or for explosion proof applications, the following warnings also apply:
Remove electrical power before removing the housing cap. Personal injury or property damage from fire or explosion
may result if power is not disconnected before removing the cap.
Remove electrical power before disconnecting any of the pneumatic connections.
When disconnecting any of the pneumatic connections or any pressure retaining part, natural gas will seep from the
unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may result

233

Instruction Manual

Maintenance and Troubleshooting


August 2012

D103412X012

from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken.
Preventive measures may include, but are not limited to, one or more of the following: ensuring adequate ventilation
and the removal of any ignition sources.
Ensure that the cover is correctly installed before putting this unit back into service. Failure to do so could result in
personal injury or property damage from fire or explosion.

CAUTION
When replacing components, use only components specified by the factory. Always use proper component replacement
techniques, as presented in this manual. Improper techniques or component selection may invalidate the approvals and
the product specifications, as indicated in table 11, and may also impair operations and the intended function of the
device.

Because of the diagnostic capability of the DVC6200f, predictive maintenance is available through the use of ValveLink
software. Using the digital valve controller, valve and instrument maintenance can be enhanced, thus avoiding
unnecessary maintenance. For information on using ValveLink software, refer to the ValveLink software online help.

Replacing the Magnetic Feedback Assembly


To remove the magnet assembly from the actuator stem, perform the following basic steps.
1. Make sure that the valve is isolated from the process.
2. Remove the instrument terminal box cover.
3. Disconnect the field wiring from the terminal board.
4. Shut off the instrument air supply.
5. Disconnect the pneumatic tubing and remove the DVC6200f or the DVC6215 from the actuator.
6. Remove the screws holding the magnet assembly to the connector arm.
When replacing the instrument, be sure to follow the mounting guidelines in the Installation section. Setup and
calibrate the instrument prior to returning to service.

Module Base Maintenance


The digital valve controller contains a module base consisting of the I/P converter, printed wiring board assembly, and
pneumatic relay. The module base may be easily replaced in the field without disconnecting field wiring or tubing.

Tools Required
Table 71 lists the tools required for maintaining the DVC6200f digital valve controller.
Table 71. Tools Required
Tool
Phillips Screwdriver
Hex key
Hex key
Hex key
Hex key

234

Size
5 mm
1.5 mm
2.5 mm
6 mm

Component
Relay, printed wiring board assembly, and cover screws
Terminal box screw
Terminal box cover screw
I/P converter screws
Module base screws

Instruction Manual
D103412X012

Maintenance and Troubleshooting


August 2012

Component Replacement
When replacing any of the components of the DVC6200f, the maintenance should be performed in an instrument
shop whenever possible. Make sure that the electrical wiring and pneumatic tubing is disconnected prior to
disassembling the instrument.

Removing the Module Base


Refer to figure 82 or 84 for key number locations.

WARNING
To avoid personal injury or equipment damage from bursting of parts, turn off the supply pressure to the digital valve
controller and bleed off any excess supply pressure before attempting to remove the module base assembly from the
housing.

1. Unscrew the four captive screws in the cover (key 43) and remove the cover from the module base (key 2).
2. Using a 6 mm hex socket wrench, loosen the threesocket head screws (key 38). These screws are captive in the
module base by retaining rings (key 154).

Note
The module base is linked to the housing by two cable assemblies. Disconnect these cable assemblies after you pull the module
base out of the housing.

CAUTION
To avoid affecting performance of the instrument, take care not to damage the module base seal or guide surface. Do not
bump or damage the bare connector pins on the PWB assembly. Damaging either the module base or guide surface may
result in material damage, which could compromise the instruments ability to maintain a pressure seal.

3. Pull the module base straight out of the housing (key 1). Once clear of the housing, swing the module base to the
side of the housing to gain access to the cable assemblies.
4. The digital valve controller has two cable assemblies, shown in figure 71, which connect the module base, via the
printed wiring board assembly, to the travel sensor and the terminal box. Disconnect these cable assemblies from
the printed wiring board assembly on the back of the module base.

235

Instruction Manual

Maintenance and Troubleshooting


August 2012

D103412X012

Figure 71. Printed Wiring Board Cable Connections


TERMINAL
BOX

MODULE BASE ASSEMBLY


PRINTED WIRING
BOARD
ASSEMBLY

HOUSING

CABLE
TO TERMINAL BOX

W99241

CABLE TO TRAVEL SENSOR

Replacing the Module Base


Refer to figure 82 or 84 for key number locations. Refer to figure 72 for a view of the back of the PWB assembly
submodule.
Figure 72. Back View of PWB Assembly SubModule

TERMINAL BOX
CONNECTOR
GE39341

PINS REMOVED FOR


CONNECTOR KEYING

TRAVEL SENSOR CONNECTOR

Note
To avoid affecting performance of the instrument, inspect the guide surface on the module and the corresponding seating area in
the housing before installing the module base assembly. These surfaces must be free of dust, dirt, scratches, and contamination.
Ensure the module base seal is in good condition. Do not reuse a damaged or worn seal.

236

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

1. Ensure the module base seal (key 237) is properly installed in the housing (key 1). Ensure the Oring (key 12) is in
place on the module base assembly.
2. Connect the terminal box connector to the PWB assembly (key 50). Orientation of the connector is required.
3. Connect the travel sensor connector to the PWB assembly (key 50). Orientation of the connector is required.
4. Insert the module base (key 2) into the housing (key 1).
5. Install three socket head screws (key 38) in the module base into the housing. If not already installed, press three
retaining rings (key 154) into the module base. Evenly tighten the screws in a crisscross pattern to a final torque of
16 Nm (138 lbfin).

CAUTION
Personal injury, property damage, or disruption of process control can result if the cable assemblies/wiring are damaged
when attaching the cover to the module base assembly
Ensure that the cable assemblies/wiring are positioned in the cavity of the module base so they do not get compressed or
damaged when attaching the cover to the module base assembly in step 6.

6. Attach the cover (key 43) to the module base assembly.

Submodule Maintenance
The digital valve controller's module base contains the following submodules: I/P converter, PWB assembly, and
pneumatic relay. If problems occur, these submodules may be removed from the module base and replaced with new
submodules. After replacing a submodule, the module base may be put back into service.

CAUTION
Exercise care when performing maintenance on the module base. Reinstall the cover to protect the I/P converter and
gauges when servicing other submodules.
In order to maintain accuracy specifications, do not strike or drop the I/P converter during submodule maintenance.

I/P Converter
Refer to figure 82 or 84 for key number locations. The I/P converter (key 41) is located on the front of the module
base.

Note
After I/P converter submodule replacement, calibrate the digital valve controller to maintain accuracy specifications.

Replacing the I/P Filter


A screen in the supply port beneath the I/P converter serves as a secondary filter for the supply medium. To replace this
filter, perform the following procedure:

237

Instruction Manual

Maintenance and Troubleshooting


August 2012

D103412X012

1. Remove the I/P converter (key 41) and shroud (key 169) as described in the Removing the I/P Converter procedure.
2. Remove the screen (key 231) from the supply port.
3. Install a new screen in the supply port as shown in figure 73.
4. Inspect the Oring (key 39) in the I/P output port. if necessary, replace it.
5. Reinstall the I/P converter (key 41) and shroud (key 169) as described in the Replacing the I/P Converter procedure.
Figure 73. I/P Filter Location

ORING LOCATED IN I/P


CONVERTER OUTPUT PORT

SCREEN (FILTER) LOCATED IN I/P


CONVERTER SUPPLY PORT

W8072

Removing the I/P Converter


1. Remove the front cover (key 43), if not already removed.
2. Refer to figure 74. Using a 2.5 mm hex socket wrench, remove the four sockethead screws (key 23) that attach the
shroud (key 169) and I/P converter (key 41) to the module base (key 2).
3. Remove the shroud (key 169); then pull the I/P converter (key 41) straight out of the module base (key 2). Be
careful not to damage the two electrical leads that come out of the base of the I/P converter.
4. Ensure that the Oring (key 39) and screen (key 231) stay in the module base and do not come out with the I/P
converter (key 41).

Replacing the I/P Converter


1. Refer to figure 73. Inspect the condition of the Oring (key 39) and screen (key 231) in the module base (key 2).
Replace them, if necessary. Apply silicone lubricant to the Orings.
2. Ensure the two boots (key 210) shown in figure 74 are properly installed on the electrical leads.

238

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

Figure 74. I/P Converter

I/P CONVERTER
(KEY 41)

W9328

SHROUD
(KEY 169)

SOCKETHEAD
SCREWS (4)
(KEY 23)

BOOTS
(KEY 210)

3. Install the I/P converter (key 41) straight into the module base (key 2), taking care that the two electrical leads feed
into the guides in the module base. These guides route the leads to the printed wiring board assembly submodule.
4. Install the shroud (key 169) over the I/P converter (key 41).
5. Install the four sockethead screws (key 23) and evenly tighten them in a crisscross pattern to a final torque of 1.6
Nm (14 lbfin).
6. After replacing the I/P converter, calibrate travel or perform touchup calibration to maintain accuracy
specifications.

Printed Wiring Board (PWB) Assembly


Refer to figure 82 or 84 for key number locations. The PWB assembly (key 50) is located on the back of the module
base assembly (key 2).

Note
The DVC6200f PWB assembly must be firmware revision 2.0 or later.

Note
If the PWB assembly submodule is replaced, calibrate and configure the digital valve controller to maintain accuracy specifications.

Removing the Printed Wiring Board Assembly


1.
2.
3.
4.

Separate the module base from the housing by performing the Removing the Module Base procedure.
Remove three screws (key 33).
Lift the PWB assembly (key 50) straight out of the module base (key 2).
Ensure that the Orings (key 40) remain in the pressure sensor bosses on the module base assembly (key 2) after the
PWB assembly (key 50) has been removed.

Replacing the Printed Wiring Board Assembly


1. Apply silicone lubricant to the pressure sensor Orings (key 40) and install them on the pressure sensor bosses in the
module base assembly.

239

Maintenance and Troubleshooting

Instruction Manual

August 2012

D103412X012

2. Properly orient the PWB assembly (key 50) as you install it into the module base. The two electrical leads from the
I/P converter (key 41) must guide into their receptacles in the PWB assembly and the pressure sensor bosses on the
module base must fit into their receptacles in the PWB assembly.
3. Push the PWB assembly (key 50) into its cavity in the module base.
4. Install and tighten three screws (key 33) to a torque of 1 Nm (10.1 lbfin).
5. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
6. Setup and calibrate the digital valve controller.

Note
Calibration is required for either Travel or Pressure Control after PWB Assembly replacement.
Note that only one calibration is needed, depending on control selection.

Pneumatic Relay
Refer to figure 82 or 84 for key number locations. The pneumatic relay (key 24) is located on the front of the module
base.

Note
After relay submodule replacement, calibrate the digital valve controller to maintain accuracy specifications.

Removing the Pneumatic Relay


1. Loosen the four screws that attach the relay (key 24) to the module base. These screws are captive in the relay.
2. Remove the relay.

Replacing the Pneumatic Relay


1. Visually inspect the holes in the module base to ensure they are clean and free of obstructions. If cleaning is
necessary, do not enlarge the holes.
2. Apply silicone lubricant to the relay seal and position it in the grooves on the bottom of the relay as shown in
figure 75. Press small seal retaining tabs into retaining slots to hold relay seal in place.
Figure 75. Pneumatic Relay Assembly

RELAY SEAL
W8074

240

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

3. Position the relay (with shroud) on the module base. Tighten the four screws, in a crisscross pattern, to a final
torque of 2 Nm (20.7 lbfin).
4. Using the Field Communicator, verify that the value for Relay Type parameter matches the relay type installed.
5. After replacing the relay and verifying the relay type, calibrate travel or perform touchup calibration to maintain
accuracy specifications

Gauges, Pipe Plugs, or Tire Valves


Depending on the options ordered, the DVC6200f will be equipped with either gauges (key 47), pipe plugs (key 66), or
tire valves (key 67). Singleacting direct instruments will also have a screen (key 236, figure 83). These are located on
the top of the module base next to the relay.
Perform the following procedure to replace the gauges, tire valves, or pipe plugs. Refer to figure 82and 83 for key
number locations.
1. Remove the front cover (key 43).
2. Remove the gauge, pipe plug, or tire valve as follows:
For gauges (key 47), the flats are on the gauge case. Use a wrench on the flats of the gauge to remove the gauge from
the module base. For doubleacting instruments, to remove the supply gauge remove one of the output gauges.
For pipe plugs (key 66) and tire valves (key 67), use a wrench to remove these from the module base.
3. Apply zinc based anti-seize sealant (key 64) to the threads of the replacement gauges, pipe plugs, or tire valves.
4. Using a wrench, screw the gauges, pipe plugs, or tire valves into the module base.

Terminal Box
WARNING
Refer to the Maintenance WARNING at the beginning of this section.

Refer to figure 82 or 84 for key number locations.


The terminal box is located on the housing and contains the terminal strip assembly for field wiring connections.

Removing the Terminal Box


WARNING
To avoid personal injury or property damage caused by fire or explosion, remove power to the instrument before removing
the terminal box cover in an area which contains a potentially explosive atmosphere or has been classified as hazardous.

1. Loosen the set screw (key 58) in the cap (key 4) so that the cap can be unscrewed from the terminal box.
2. After removing the cap (key 4), note the location of field wiring connections and disconnect the field wiring from
the terminal box.
3. Separate the module base from the housing by performing the Removing the Module Base procedure.

241

Maintenance and Troubleshooting

Instruction Manual

August 2012

D103412X012

4. Disconnect the terminal box wiring connector from the PWB assembly (key 50).
5. Remove the screw (key 72). Pull the terminal box assembly straight out of the housing.

Replacing the Terminal Box


Note
Inspect all Orings for wear and replace as necessary.

1. Apply lubricant, silicone sealant to the Oring (key 34) and install the Oring over the stem of the terminal box.
2. Insert the terminal box assembly stem into the housing until it bottoms out. Position the terminal box assembly so
that the hole for the screw (key 72) in the terminal box aligns with the threaded hole in the housing. Install the
screw (key 72).
3. Connect the terminal box wiring connector to the PWB assembly (key 50).
4. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
5. Reconnect the field wiring as noted in step 2 in the Removing the Terminal Box procedure.
6. Apply lubricant, silicone sealant to the Oring (key 36) and install the Oring over the 25/8 inch threads of the
terminal box. Use of a tool is recommended to prevent cutting the Oring while installing it over the threads.
7. Apply lithium grease (key 63) to the 25/8 inch threads on the terminal box to prevent seizing or galling when the
cap is installed.
8. Screw the cap (key 4) onto the terminal box.
9. Install a set screw (key 58) into the cap (key 4). Loosen the cap (not more than 1 turn) to align the set screw over
one of the recesses in the terminal box. Tighten the set screw (key 58).

Stroking the Digital Valve Controller Output


After completing maintenance procedures, confirm proper valve operation by stroking the digital valve controller
output. Refer to page 228.

DVC6215 Feedback Unit


There are no replaceable parts on the DVC6215 feedback unit. Contact your Emerson Process Managment if a
replacement DVC6215 feedback unit is needed.

242

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

Instrument Troubleshooting
What to Do First
When a problem occurs, check the following first:

Mounting
Is the feedback linkage connected correctly? See the beginning of this section.

Utility Connections
Are pneumatic connections correct? Are there any air leaks? See the Installation section.
Is the air supply pressure sufficient to drive the valve?
Is the digital valve controller correctly connected to the fieldbus? See the Installation section.
Is there power to the device? Is the terminal voltage between 9 and 32 volts? See the Installation section.
Is the segment terminated correctly? See host system documentation.
Is the host system connected to the segment? See host system documentation.
If communication or output difficulties are experienced with the instrument, refer to the troubleshooting information
provided in table 72.
Also see the Technical Support Checklist found on page 248.

243

Instruction Manual

Maintenance and Troubleshooting


August 2012

D103412X012

Table 72. Instrument Troubleshooting


Symptom
1 Instrument will not communicate.

Possible Cause
1a No power to device

1b Internal device wiring problems.

Action
1a1 Ensure device is connected to the segment (see
host system documentation).
1a2 Measure the terminal voltage. Terminal voltage
should be between 9 and 32 VDC.
1a3 Check to be sure device is drawing current. There
should be approximately 19 mA.
1b1 Verify connectors are plugged into the printed
wiring board correctly (see Printed Wiring Board
Assembly on page 239).
1b2 Check continuity of cable between terminal box
and printed wiring board. If necessary, replace the
terminal box assembly (see Replacing the Terminal Box
on page 242).
1b3 Check for damaged printed wiring board lands and
terminals. If necessary, replace the terminal box
assembly (see Replacing the Terminal Box on page
242).

1c Incompatible network settings


1d Defective printed wiring board (PWB) assembly.
1e Defective terminal box.

2 Device does not stay on segment.

3 A value cannot be written to a


parameter.

1f Defective Field Communicator or ValveLink


modem cable.
1g Fieldbus card defective or not compatible with PC.
2a Incorrect signal level.

1f If necessary, repair or replace cable.

2b Excess noise on segment.

2b1 Check integrity of wiring connections. Make sure


cable shield is grounded only at the control system.
2b2 Check for corrosion or moisture on terminals in
terminal box (refer to page 242 for terminal box
information).
2b3 Check for bad power supply.

2c Electronics failing.

2c. Replace printed wiring board assembly (see


Replacing the PWB Assembly on page 239).
3a Change Write Lock to Not Locked (refer to page 45).

3a Resource block parameter Write Lock may be set to


Locked.
3b If a transducer block parameter, the mode may be
incorrect or the parameter may be protected.

3c You have attempted to write a value that is outside


the valid range.
3.d Function block or in/out block mode may be
incorrect.
-Continued-

244

1c Change host parameters. Refer to host


documentation for procedure.
1dReplace printed wiring board (see Replacing the
PWB Assembly on page 239.
1e Check continuity from each screw terminal to the
corresponding PWB connector pin. If necessary, replace
the terminal box assembly (see Replacing the Terminal
Box on page 242).

1g Replace Fieldbus card.


2a1 Check that segment is properly terminated (see
host system documentation).
2a2 Wrong cable type or segment length too long. See
Site Planning Guide.
2a3 Bad power supply or conditioner.

3b1 Check table 414. If necessary change the


transducer block target mode to Manual.
3b2 Check table 414. If necessary change data
protection.
3c Check the range values listed for the parameter
(refer to the parameter tables in Section 4).
3.d. Confirm that block is in correct mode for writing to
any given parameter.

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

Table 72. Instrument Troubleshooting (Continued)


Symptom
4 Function block actual mode does not
change with target mode.

Possible Cause
4a Resource block actual mode is Out of Service.

4b Transducer block actual mode is not Auto.

4c Schedules that define when function blocks execute


are not set correctly.
4d Configuration error

5 Input or Output Block does not go to


mode target

5a Resource block actual mode is Out of Service

5b Transducer block actual mode is not Auto.

5c Transducer has detected a hardware failure.

5d Wrong output block is active.

5e Output block is not licensed.

5f Schedules that define when function blocks execute


are not set correctly.
5g Configuration error.

Action
4a Change Resource block target mode to Auto (see
page 45, Resource Block Mode, or host system
documentation).
4b Change transducer block target mode to Auto (see
page 62, Transducer Block Mode or host system
documentation).
4c Set the schedules using host system or
configuration tool. All function blocks must be in a
schedule that is downloaded to the device.
4d Look for configuration error bit in BLOCK_ERR. By
default, all enumerature type parameters are initialized
to 0 (undefined). They must be configured before the
block can be put into service.
5a Change Resource block target mode to Auto (see
page 45, Resource Block Mode, or host system
documentation).
5b Change transducer block target mode to Auto (see
page 62, Transducer Block Mode or host system
documentation).
5c A bad status is passed to the block's READBACK or
FIELD_VAL parameter. See transducer section of
Detailed Setup for repair information.
5d Use Outblock Selection to select the desired output
block. The deselected block will have a bad status for
READBACK. This will keep it in IMAN mode when target
is other than OOS.
5e The Actual Block Mode (MODE_BLK.ACTUAL [5.2])
will remain out of service and the block cannot be
scheduled if the block has not bee licensed. Contact
your Emerson Process Management sales office to
upgrade product licensing.
5f Set the schedules using host system or configuration
tool. All function blocks must be in a schedule that is
downloaded to the device.
5g Look for configuration error bit in BLOCK_ERR. By
default, all enumerature type parameters are initialized
to 0 (undefined). They must be configured before the
block can be put into service.

6 Block dynamic parameters do not


update

6a Block actual mode is Out of Service

6a Change the block target mode to an operational


mode (see Appendix D, FOUNDATION fieldbus
Communication and host system documentation).

7 Transducer block Setpoint


(FINAL_VALUE [13]) is not being
automatically updated from the AO
block.

7a Transducer block mode in not Auto.

7a Change transducer block mode to Auto.

7b AO block is not active.

7b Change Outblock Selection to AO Control.

8 Transducer block setpoint


Setpoint(D) (SETPOINT_D [32]) is not
being automatically updated from the
DO block.

8a Transducer block mode is not Auto.

8a Change transducer block mode to Auto.

8b DO block is not active.

8.b Change Outblock Selection to DO Control.

9 Valve does not move when the set


point is changed

9a A function block actual mode is Out of Service or


Transducer Block Actual mode is Out of Service or
Manual.

9a1 Change the target mode to an operational mode


(see Appendix D, FOUNDATION fieldbus Communication
and host system documentation).
9a2 Verify that the correct block (AO or DO) is
configured in Feature Select in the resource block. Only
the selected out block is able to set the transducer
setpoint and move the valve.

9b Pneumatic connections are incorrect or supply


pressure is incorrect

9b Check pneumatic connections and supply pressure.


Be sure supply pressure regulator is set correctly (see
Pneumatic Connections on page 26).

-Continued-

245

Instruction Manual

Maintenance and Troubleshooting


August 2012

D103412X012

Table 72. Instrument Troubleshooting (Continued)


Symptom

Possible Cause

Action

9c Instrument is in fault state.

10 Valve does not stroke from 0 to


100% with set point change

11 Deviation between set point and


actual valve position remains.

12 The valve cycles, does not stay on


set point.

13 Valve responds too slowly.

9c Set Clear FState to Clear (Refer to Fault State on


page 47 of the Detailed Setup / Blocks Section, or host
system documentation).
9d The valve has failed.
9d Apply a pneumatic pressure to the valve actuator
and check valve action.
9e The I/P converter or relay has failed.
9e Replace the I/P converter or relay (see Replacing the
I/P Converter on page 238).
10a Insufficient supply pressure or leak in pneumatic
10a Check supply pressure and supply pressure
connections.
regulator setting. Check for leaks around pneumatic
connections.
10b Setpoint may be limited.
10b Check the AO Block values of SP_HI_LIMIT and
SP_LO_LIMIT (see page 122 or host system
documentation).
11aDigital valve controller output is in cutoff.
11a Check values for Travel Cutoff High and Travel
Cutoff Low (see page 67 or host system
documentation).
11b Digital valve controller is not calibrated correctly
11b Perform Auto or Manual Travel Calibration (Travel
Calibration on page 214.)
11c Incorrect turning. Tuning that is too conservative will 11c Perform Stabilizing/Optimize Valve Response
result in excess error.
procedure toadjust tuning and stabilize/optimize
valve response (see Stabilize/Optimize on page 64).
12a Large amount of packing friction.
12a1 Perform Stabilizing/Optimize Valve Response
procedure toadjust tuning and stabilize/optimize
valve response (see Stabilize/Optimize on page 64).
12a2 Use a larger size actuator.
13a Insufficient instrument gain.

13b I/P converter input filter clogged or air blockage in


I/P ass'y nozzle block.

13 Valve responds too slowly.

13c Oring(s) between I/P converter missing or hard and


flattened losing seal.
13d I/P ass'y out of spec.

13e Defective gasket.

13f Defective relay.

13f Remove relay, inspect for missing Belleville washer,


missing valve spring, missing valve plug. Inspect lip
under top Oring for breakage due to relay removal.
Inspect Orings and replace if hard or damaged.
Replace parts or relay if I/P ass'y good and air passages
not blocked (see Replacing the Pneumatic Relay on
page 240).

13g If responds slowly only upon air demand, there may


be a restriction in the air line, the supply run may be
excessively long, or the supply regulator may be
defective or capacity not large enough.

13g1 Check supply line to ensure it is not clogged or


damaged. Replace if necessary.
13g2 If supply run is excessively long, a volume tank
may need to be installed on the the supply side of the
pressure regulator
13g3 Replace supply regulator

-Continued-

246

13a Perform Stabilize/Optimize Valve Response


procedure toadjust tuning and stabilize valve
response (see Stabilize/Optimize on page 64).
13b1 Replace I/P converter filter (see Replacing the I/P
Filter on page 237).
13b2 Replace I/P converter (see Replacing the I/P
Converter on page 238).
13c Replace Oring(s) (refer to the I/P Converter section
on page 237).
13d I/P ass'y nozzle may have been adjusted.
Verify drive signal (55% to 80%) (refer to Elect and
Config on page 69 or host system documentation).
Replace I/P ass'y if drive signal is continuously high or
low (see Replacing the I/P Converter on page 238).
13e Check gasket for closed holes, excessive
deformation due to overtightening or oozing. If
necessary, replace gasket (see the beginning of this
section).

Instruction Manual

Maintenance and Troubleshooting

D103412X012

August 2012

Table 72. Instrument Troubleshooting (Continued)


Symptom
14 Instrument will not calibrate, has
sluggish performance or oscillates.

15 Instrument will not calibrate.

Possible Cause

14a Replace the housing (key 1)

14b Travel feedback is out of accepted range

14c Cables not plugged into PWB correctly.

14b Check the mounting. Ensure the correcting


mounting kit has been selected and the magnetic array
is properly installed.
14c Inspect connections and correct.

14d Configuration errors.

14d Verify configuration. Use Device Setup on page 40.

14e Restricted pneumatic passages in I/P converter

14e Check screen in I/P converter supply port of the


module base. Replace if necessary. If passages in I/P
converter restricted, replace I/P converter (see
Replacing the I/P Converter on page 238).

14f Oring(s) between I/P converter ass'y missing or hard 14f Replace Oring(s) (refer to the I/P Converter section
and flattened losing seal.
on page 237).
14g I/P converter ass'y damaged/corroded/clogged.
14g Check for bent flapper, open coil (continuity),
contamination, staining, or dirty air supply. Coil
resistance should be between 1680 1860 ohms.
Replace I/P ass'y if damaged, corroded, clogged, or
open coil (see Replacing the I/P Converter on page 238).
14h I/P converter ass'y out of spec.
14h I/P converter ass'y nozzle may have been adjusted.
Verify drive signal (55 to 80% for doubleacting; 60 to
85% for singleacting) with the valve off the stops.
Replace I/P converter ass'y if drive signal is continuously
high or low (see Replacing the I/P Converter on page
238).
14i Defective module base seal.
14i Check module base seal for condition and position.
If necessary, replace seal. Refer to Module Base
Maintenance on page 234.
14j Defective relay.
14j Depress relay beam at adjustment location in
shroud, look for increase in output pressure. Remove
relay, inspect relay seal. Replace relay seal or relay if I/P
converter ass'y good and air passages not blocked
(refer to Replacing the Pneumatic Relay on page 240).
Check relay adjustment (refer to page 215).
14k Defective 67CFR regulator, supply pressure gauge
14k Replace 67CFR regulator.
jumps around.
15a Configuration errors.
15a Verify configuration.
15b Magnet assembly is not correctly installed.

15c Cables not plugged into PWB correctly.


16 ValveLink diagnostic tests provide
erroneous results.

Action

14a Travel sensor failed.

16b Pressure sensor Oring(s) missing.

16a Replace PWB (see Replacing the PWB Assembly on


page 239).
16b Replace Oring(s).

17 Cannot perform advanced


diagnostics.

17a Instrument does not have proper tiering.

17a Upgrade tiering.

18 A PlantWeb alert is active, but not


reported (broadcast) automatically.

18a PlantWeb alerts in firmware 1.5 and higher are


modebased. Transducer block mode may be in MAN or
OOS.
19a Battery pack not charged.

18a Check transducer block mode. Change to AUTO if


appropriate.

19 Field Communicator does not turn


on.

16a Defective pressure sensor(s).

15b Check the mounting. Ensure the correcting


mounting kit has been selected and the magnetic array
is properly installed.
15c Inspect connections and correct.

19a Charge battery pack.


Note: Battery pack can be charged while attached to the
Field communicator or separately. The Field
Communicator is fully operable while the battery pack is
charging. Do not attempt to charge the battery pack in
a hazardous area.

247

Instruction Manual

Maintenance and Troubleshooting


August 2012

D103412X012

Technical Support Checklist


Have the following information available prior to contacting your Emerson Process Management sales office for
support.
Reference
1. Instrument serial number as read from nameplate _________________________________________
2. What is the firmware version of the DVC6200f? _________________
3. What is the hardware version of the DVC6200f? ________________
4. What is the Diagnostic Tier of the DVC6200f? FD___ AD___ PD___
5. What is the Control Tier of the DVC6200f? SC___ FL___ FC___
6. What is the address of the DVC6200f? ________________________
Mode and Status
7. What are the DVC6200f Block Modes?
Actual Modes:

Resource Block _____ Transducer Block_____ Analog Output Block _____

Target Modes:

Resource Block _____ Transducer Block_____ Analog Output Block _____

Permitted Modes:

Resource Block _____ Transducer Block_____ Analog Output Block _____

8. What is the status of the individual function blocks?


Operational
9. Does the digital valve controller respond to the control signal? Yes _________ No _________
If No, describe
10. Is it on Travel or Pressure control?
11. What are the following parameter readings?
Setpoint _________

Drive Signal _________%

Supply Pressure _________

Pressure A _________

Pressure B _________

Travel Target _________%

Travel _________%

Pressure B _________

12. What is the safe position of the valve? Fail Closed ____ Fail Open ____
Interface and Diagnostic Tools
13. What interface and diagnostic tools are available?___________________________________
14. Provide any available supporting documentation, such as Status Monitor, Detailed Setup, any alert readings.

Mounting
Reference
1. Actuator application: sliding-stem? _________ Rotary? _________
2. Which digital valve controller do you have? DVC6200f _________ DVC6205f/DVC6215 _________
3. What Make, Brand, Style, Size, etc. actuator is the DVC6200f mounted on? _________________________
Operational
4. What is the full travel of the valve?__________________________________
5. What is the Mounting Kit part number? ______________________________
Other
6. If mounting kits are made by LBP/Customer, please provide pictures of installation.

248

Instruction Manual

Parts

D103412X012

August 2012

Section 8 Parts8-8Parts Ordering


Whenever corresponding with your Emerson Process Management sales office about this equipment, always mention
the controller serial number. When ordering replacement parts, refer to the 11character part number of each
required part as found in the following parts list. Part numbers are shown for kits and recommended spares only. For
part numbers not shown, contact your Emerson Process Management sales office.

WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Process Management should
not, under any circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson Process
Management may void your warranty, might adversely affect the performance of the instrument, and could cause personal
injury and property damage.

Parts Kits
Kit

Description

1*

Elastomer Spare Parts Kit (kit contains parts to


service one digital valve controller)
Standard
Extreme Temperature option
(fluorosilicone elastomers)

Part Number

Description

6*

Spare Module Base Assembly Kit


[kit contains module base (key 2); drive screws, qty. 2,
(key 11); shield/label (key 19); hex socket cap screw, qty. 3,
(key 38); self tapping screw, qty. 2 (key 49); pipe plug, qty. 3
(key 61); retaining ring, qty. 3 (key 154); screen (key 236);
and flame arrestors, qty. 3 (key 243)]
Aluminum
GE18654X012
Stainless Steel
GE18654X022

7*

Spare Housing Assembly Kit,


[kit contains housing (key 1); vent assembly (key 52);
seal (only included in Housing A kits) (key 288);
seal (key 237); Oring (key 34); Oring (only used
with integrally mounted regulator) (key 5)]

19B5402X012
19B5402X022

2*

Small Hardware Spare Parts Kit (kit contains parts


to service one digital valve controller)
19B5403X012

3*

Seal Screen Kit


[kit contains 25 seal screens (key 231)
and 25 Orings (key 39)]
Standard and Extreme Temperature option
(fluorosilicone elastomers)

4*

Kit

14B5072X182

Aluminum
Housing A (used for GX actuator)
Standard (nitrile elastomers)
Extreme Temperature option
(fluorosilicone elastomers)
Housing B (used for all actuators except GX)
Standard (nitrile elastomers)
Extreme Temperature option
(fluorosilicone elastomers)

Terminal Box Kit


Aluminum
Standard
Standard, Natural Gas approved
Extreme Temperature option
(fluorosilicone elastomers)
Extreme Temperature option
(fluorosilicone elastomers)
Natural Gas Approved

Stainless Steel, fluorosilicone elastomers

5*
I/P Converter Kit
Standard

For Extreme Temperature option


(fluorosilicone elastomers)

*Recommended spare parts

GE44077X012
GE44081X012
GE44078X012

Stainless Steel
Housing B (used for all actuators except GX)
Standard (nitrile elastomers)
Extreme Temperature option
(fluorosilicone elastomers)

GE44082X012
GE44080X012

38B6041X152
38B6041X132


8*

Spare I/P Shroud Kit


[kit contains shroud (key 169) and
hex socket cap screw, qty. 4 (key 23)]

Part Number

GE48798X032
GE48798X042
GE48798X072
GE48798X082

GE48798X092
GE48798X102

GE29183X012

249

Instruction Manual

Parts
August 2012

Kit
9*

Description

Part Number

Remote Mount Feedback Unit Kit (see figure 85)


[remote housing assembly (key25); hex socket set
screw (key 58); 1/2 NPT pipe plug (key 62); wire retainer, qty 2
(key 131); terminal cover (key 255); o-ring (key 256); gasket
(Housing A only, used for GX actuator) (key 287); seal
(Housing A only, used for GX actuator) (key 288)
Housing A (used for GX actuator)
Housing B (used for all actuators except GX)

10*

D103412X012

GE46670X012
GE40178X012

Feedback Array Kit


[kit contains feedback array and machine screws, qty. 2 and
washers, qty. 2; 210 mm (8-1/4 inch) kit also contains insert]
7 mm (1/4-inch)
Aluminum
19 mm (3/4-inch)
Aluminum
Stainless steel
25 mm (1-inch)
Aluminum
Stainless steel
38 mm (1-1/2 inch)
Aluminum
Stainless steel
50 mm (2-inch)
Aluminum
Stainless steel
100 mm (4-inch)
Aluminum
Stainless steel
210 mm (8-1/4 inch)
Aluminum
Stainless steel

GE09169X022
GE09169X032
GE09169X072
GE09169X012
GE09169X082
GE09169X042
GE09169X092
GE09170X012
GE09169X102

GE09169X062
GE09169X132

Screw, hex head (4 reqd) (DVC6205f only)


Screw, hex head (4 reqd) (DVC6205f only)
Spacer (4 reqd) (DVC6205f only)
Standoff (2 reqd) (DVC6205f only)
Screen(7)
Gasket, Housing A only (used for GX actuator) (DVC6200f only)
Seal, Housing A only (used for GX actuator) (DVC6200f only)

Common Parts
(see figure 82, 83, and 84)
DVC6200f and DVC6205f
16*
29
33
38
43*

48
49
61

63
64
65
154
236
237

Note
Part numbers are shown for recommended spares only. For part
numbers not shown, contact your Emerson Process Management sales
office.
Parts with footnote numbers are available in parts kits; see footnote
information at the bottom of the page.

Description

Description

248
249
250
267
271
287
288

GE43790X012
GE09169X112

Parts List

Key

Key

Part Number

Housing (see figure 82 and 84)

Oring(1) (3 req'd)
Warning label, for use only with LCIE hazardous area
classifications
Mach Screw, pan hd, SST(2) (3 req'd)
Cap Screw, hex socket, SST(2)(6) (3 req'd)
Cover Assembly (includes cover screws)
Standard
38B9580X022
Extreme temperature option
(fluorosilicone elastomers)
38B9580X032
Nameplate
Screw, self tapping (2 req'd)(6)
Pipe Plug, hex socket(6)
Housing A with relay C (2 req'd ) (used for GX actuator)
Housing A with relay B (1 req'd) (used for GX actuator)
Housing B with relay B and C (1 req'd)
(used for all actuators except GX)
Not required for relay A
Lithium grease (not furnished with the instrument)
Zinc based antiseize compound (not furnished with the
instrument)
Lubricant, silicone sealant (not furnished with the instrument)
Retaining Ring(2) (3 req'd)
Screen (required for relay B and C only)(7)
Module Base Seal(1)

Module Base
(see figure 82 and 84)
DVC6200f and DVC6205f
2
11
12
19
61
243

Module Base(6)
Drive Screw(6) (2 req'd)
Oring(1)
Label, Shield Assembly(6)
Pipe Plug, hex socket(6) (3 req'd)
Slotted Pin (flame arrestor)(6) (3 req'd)

DVC6200f and DVC6205f


1
11
20
52
74

250

Housing(7)
Drive Screw (2 req'd) (DVC6205f only)
Shield (DVC6205f only)
Vent, plastic(2)
Mounting Bracket (DVC6205f only)

*Recommended spare
1. Available in the Elastomer Spare Parts Kit
2. Available in the Small Hardware Spare Parts Kit
6. Available in the Spare Module Base Assembly Kit
7. Available in the Spare Housing Assembly Kit

Instruction Manual

Parts

D103412X012

Key

Description

August 2012

Part Number

Figure 81. Terminal Box of Natural Gas Certified


FIELDVUE DVC6200f Digital Valve Controller
WIRING CONNECTOR

I/P Converter Assembly


(see figure 82 and 84)

GASBLOCKING
PRESSFIT ADAPTOR

DVC6200f and DVC6205f


23
39*
41
169
210*
231*

Cap Screw, hex socket, SST(2)(8) (4 req'd)


Oring(1)(3)(5)
I/P Converter(5)
Shroud(5)(8) (not shown, see figure 74)
Boot, nitrile(1)(5) (2 req'd) (see figure 74)
Seal Screen(1)(3)(5)

Relay (see figure 82 and 84)


DVC6200f and DVC6205f

Key

24* Relay Assembly, (includes shroud, relay seal, mounting screws)


Standard (nitrile elastomers)
Standard Bleed
Housing A (used for GX actuator)
Single/acting direct (relay C)
Singleacting reverse (relay B)
Housing B (used for all actuators except GX)
Singleacting direct (relay C)
Doubleacting (relay A)
Singleacting reverse (relay B)
Low Bleed
Housing A (used for GX actuator)
Singleacting direct (relay C)
Singleacting reverse (relay B)
Housing B (used for all actuators except G)
Singleacting direct (relay C)
Doubleacting (relay A)
Singleacting reverse (relay B)

W99231

38B5786X182
38B5786X172
38B5786X132
38B5786X052
38B5786X092

38B5786X202
38B5786X192
38B5786X152
38B5786X072
38B5786X112

Extreme Temperature option (fluorosilicone elastomers)


Standard Bleed
Singleacting direct (relay C)
38B5786X142
Doubleacting (relay A)
38B5786X032
Singleacting reverse (relay B)
38B5786X102
Low Bleed
Singleacting direct (relay C)
38B5786X162
Doubleacting (relay A)
38B5786X082
Singleacting reverse (relay B)
38B5786X122

Description

Part Number

Loop Connections Terminal Box


(see figure 82 and 84)
DVC6200f and DVC6205f
4
34*
36*
58
72
164

Terminal Box Cap


Oring(1)(4)
Oring(1)(4)
Set Screw, hex socket, SST(2)
Cap Screw, hex socket, SST(2)
Terminal Box Assembly

Feedback Connections Terminal


Box (see figure 84)
DVC6205f
4
34*
36*
58
62
64
262
263*

264

Terminal Box Cap


Oring(1)(4)
Oring(1)(4)
Set Screw, hex socket, SST(2)
Pipe Plug, hex hd, SST
Antiseize compound (not furnished with the instrument)
Adapter
O-ring
Standard
1F463606992
Extreme temperature option, (fluorosilicone)
1F4636X0092
Terminal Box Assembly, remote

*Recommended spare
1. Available in the Elastomer Spare Parts Kit
2. Available in the Small Hardware Spare Parts Kit
3. Available in the Seal Screen Kit
4. Available in the Terminal Box Kit
5. Available in the I/P Converter Kit
8. Available in the Spare Shroud Kit

251

Instruction Manual

Parts
August 2012

Key

Description

PWB Assembly
(see figure 82 and 84)
DVC6200f and DVC6205f

D103412X012

Key

Description

Part Number

Pressure Gauges, Pipe Plugs, or


Tire Valve Assemblies
(see figure 83)
DVC6200f and DVC6205f

Note
Contact your Emerson Process Management sales office for PWB
Assembly FS numbers.

50*

252

PWB Assembly
Standard Control
Fieldbus Diagnostics
Advanced Diagnostics
Performance DIagnostic
Fieldbus Control
Fieldbus Diagnostics
Advanced Diagnostics
Performance Diagnostics
Fieldbus Logic
Fieldbus Diagnostics
Advanced Diagnostics
Performance Diagnostics

47*

Pressure Gauge, nickelplated brass case, brass connection


Doubleacting (3 req'd); Singleacting (2 req'd)
PSI/MPA Gauge Scale
To 60 PSI, 0.4 MPa
18B7713X042
To 160 PSI, 1.1 MPa
18B7713X022
PSI/bar Gauge Scale
To 60 PSI, 4 bar
18B7713X032
To 160 PSI, 11 bar
18B7713X012
PSI/KG/CM2 Gauge Scale
To 60 PSI, 4 KG/CM2
18B7713X072
To 160 PSI, 11 KG/CM2
18B7713X082

66

Pipe Plug, hex hd


For doubleacting and singleacting direct w/gauges
(none req'd)
For singleacting reverse w/gauges (1 req'd)
For all units w/o gauges (3 req'd)
Tire Valve, used with Tire Valve Option only
Doubleacting (3 req'd); Singleacting (2 req'd)

67

*Recommended spare parts

Instruction Manual

Parts

D103412X012

August 2012

Figure 82. FIELDVUE DVC6200f Digital Valve Controller


Housing Assembly

HOUSING ABACK VIEW


(USED FOR GX ACTUATOR)

DOUBLEACTING

DIRECTACTING

HOUSING BBACK VIEW


(USED FOR ALL
ACTUATORS EXCEPT GX)

REVERSEACTING

APPLY LUBRICANT, SEALANT, OR THREAD LOCK


APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED
GE40185 sheet 1 of 3

253

Instruction Manual

Parts
August 2012

D103412X012

Figure 82. FIELDVUE DVC6200f Digital Valve Controller Housing Assembly (continued)

SECTION C-C
SCALE 2 : 1

SECTION A-A

SECTION E-E
SCALE 2 : 1

APPLY LUBRICANT, SEALANT, OR THREAD LOCK


APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED

SECTION F-F
SCALE 2 : 1

GE40185 sheet 2 of 3

Figure 83. Gauge Configuration

DOUBLEACTING

DIRECTACTING

FOR PIPE PLUG OPTION REPLACE 47 WITH 66


FOR TIRE VALVE OPTION REPLACE 47 WITH 67
APPLY LUBRICANT, SEALANT, OR THREAD LOCK
APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED
GE40185 sheet 3 of 3

254

REVERSEACTING

Instruction Manual

Parts

D103412X012

August 2012

Figure 84. FIELDVUE DVC6205f Base Unit Housing Assembly

SECTION B-B

SECTION A-A

APPLY LUBRICANT, SEALANT, OR THREAD LOCK

SECTION H-H

APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED


GE40181

255

Instruction Manual

Parts
August 2012

D103412X012

Figure 84. FIELDVUE DVC6205f Base Unit Housing Assembly (continued)

SECTION C-C
SCALE 2 : 1

SECTION E-E
SCALE 2 : 1

DOUBLEACTING

DOUBLEACTING SHOWN

DIRECTACTING

APPLY LUBRICANT, SEALANT, OR THREAD LOCK


APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED
GE40181

256

REVERSEACTING

Instruction Manual

Parts

D103412X012

August 2012

Figure 84. FIELDVUE DVC6205f Base Unit Housing Assembly (continued)

WALL MOUNTING

PIPE MOUNTING

APPLY LUBRICANT, SEALANT, OR THREAD LOCK


APPLY LUBRICANT ON ALL O-RINGS UNLESS OTHERWISE SPECIFIED
GE40181

257

Instruction Manual

Parts
August 2012

D103412X012

Figure 85. FIELDVUE DVC6215 Remote Feedback Assembly

SECTION A-A
PARTS NOT SHOWN: 158
APPLY LUBRICANT, SEALANT, OR THREAD LOCK
GE46670-B

HOUSING A
(USED FOR GX ACTUATOR)

SECTION A-A

PARTS NOT SHOWN: 158


APPLY LUBRICANT, SEALANT, OR THREAD LOCK
GE40178-B

HOUSING B
(USED FOR ALL ACTUATORS EXCEPT GX)

258

Instruction Manual

Principle of Operation

D103412X012

August 2012

Appendix A Principle of OperationAA


Digital Valve Controller Operation
The DVC6200f digital valve controller has a single module base that may be easily replaced in the field without
disconnecting field wiring or tubing. The master module contains the following submodules: currenttopneumatic
(I/P) converter, printed wiring board assembly, and pneumatic relay. The relay position is detected by sensing the
magnet on the relay beam via a detector on the printed wiring board. This sensor is used for the minor loop feedback
(MLFB) reading. The master module can be rebuilt by replacing the submodules. See figures A1 and A2.
Figure A1. FIELDVUE DVC6200f Digital Valve Controller Block Diagram
DIGITAL
SETPOINT

932 VOLT
FIELDBUS

VALVE TRAVEL FEEDBACK

PRINTED
WIRING BOARD
DRIVE
SIGNAL

AUXILIARY
TERMINALS

OUTPUT A
I/P
CONVERTER
TERMINAL BOX

PNEUMATIC
RELAY

SUPPLY
PRESSURE
OUTPUT B

VALVE AND
ACTUATOR

VENT
E1376

The DVC6200f digital valve controller is a buspowered instrument that provides a control valve position in response
to a digital setpoint from the control room. The following describes a direct acting DVC6200f digital valve controller
mounted on a sliding-stem piston actuator, where the valve is closed with zero power to the instrument.
The setpoint is routed into the terminal box through a single pair of wires and then to the printed wiring board
assembly submodule where it is read by the microprocessor, processed by a digital algorithm, and converted into an
analog I/P drive signal.

259

Instruction Manual

Principle of Operation
August 2012

D103412X012

As the setpoint increases, the drive signal to the I/P converter increases, increasing the I/P output pressure. The I/P
output pressure is routed to the pneumatic relay submodule. The relay is also connected to supply pressure and
amplifies the small pneumatic signal from the I/P converter. The relay accepts the amplified pneumatic signal and
provides two output pressures. With relay A, an increasing setpoint will produce increasing pressure at output A and
decreasing pressure at output B. With relay B an increasing setpoint will produce decreasing pressure at output B
(output A is not available). With relay C an increasing setpoint will produce an increasing pressure on output A (output
B is not available). The output A pressure is used for doubleacting and singleacting direct applications. The output B
pressure is used for doubleacting and singleacting reverse applications.
Figure A2. FIELDVUE DVC6200f Digital Valve Controller Assembly
HOUSING

PNEUMATIC
RELAY

GAUGES

COVER

TERMINAL BOX
WITH COVER
PRINTED WIRING
BOARD ASSEMBLY

MODULE BASE ASSEMBLY

I/P CONVERTER

W99251

As shown in figure A1, the increased output A pressure causes the actuator stem to move upward. The stem position
is sensed by the travel sensor. The stem continues to move upward until the correct stem position is attained. At this
point the printed wiring board assembly stabilizes the I/P drive signal. This prevents any further increase in the
pneumatic signal from the I/P converter.
As the digital setpoint decreases, the drive signal to the I/P converter submodule decreases, decreasing the I/P output
pressure. The pneumatic relay decreases the output A pressure and increases the output B pressure. The stem moves
downward until the correct position is attained. At this point the printed wiring board assembly stabilizes the I/P drive
signal. This prevents any decrease in the pneumatic signal from the I/P converter.

260

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

Appendix B Field Communicator Menu StructureBB


This section contains the Field Communicator menu trees for the transducer block and the resource block. It also
contains Fast Key Sequence tables with coordinates to help locate the function/variable on the appropriate menu tree.

261

Instruction Manual

Field Communicator Menu Structure


August 2012

D103412X012

Transducer Block (TB) Menu Structure


Parameter Label

Menu Structure

A Minus B

TB > Device Variables > Pressures > A Minus B

Actual Travel

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Actual Travel

Actuator Fail Action

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Fail Action

Actuator Manufacturer

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Manufacturer

Actuator Model Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Model Number

Actuator Serial Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Serial Number

Actuator Size

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Size

Actuator Style

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Style

Advise Active

TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Advise Active

Advise Enable

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Advise Enable

Advise Suppress

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Advise Suppress

Air

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Air

Alert Conditions

TB > Device Diagnostics > Alert Conditions

Alert Key

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Alert Key

Area Units

TB > Configure/Setup > Detailed Setup > Instrument > Area Units

Block Configuration Error

TB > Device Diagnostics > Status > Block Error > Block Configuration Error

Blocks Set to Defaults Alert

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Blocks Set to Defaults > Block Set to Defaults Alert

Blocks Set to Defaults Alert


Enable

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Blocks Set to Defaults > Block Set to Defaults Alert Enable

Calibration Date

TB > Configure/Setup > Detailed Setup > Instrument > Calibration Date

Calibration Location

TB > Configure/Setup > Detailed Setup > Instrument > Calibration Location

Calibration Person

TB > Configure/Setup > Detailed Setup > Instrument > Calibration Person

Custom Characterization Table

TB > Configure/Setup > Detailed Setup > Response Control > Custom Characterization Table

Cycle Counter

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter
TB > Device Variables > Cycle Counter

Cycle Counter Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert

Cycle Counter Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert Enable

Cycle Counter Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Alert Point

Cycle Counter Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Cycle Counter > Cycle Counter Deadband

Device Needs Maintenance Now

TB > Device Diagnostics > Status > Block Error > Device Needs Maintenance Now

Drive Current

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current

Drive Current Alert

TB > Device Diagnostics > Status > Self Test Status > Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert

Drive Current Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Enable

Drive Current Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Point

Drive Current Alert Time

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Alert Time

Drive Current Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Manual Recovery

Drive Current Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Current > Drive Current Shutdown

Drive Signal

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal
TB > Device Variables > Drive Signal

Drive Signal Alert

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal Alert

Drive Signal Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Drive Signal > Drive Signal Alert Enable

Effective Area

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Effective Area

Failed Active

TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Failed Active

Failed Enable

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Failed Enable

Failed Suppress

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Failed Suppress

Feedback Connection

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Feedback Connection

Flow Direction

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Direction

Flow Tends To

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Tends To

I/O Processor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Alert

I/O Processor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Alert Enable

I/O Processor Man Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Man Recovery

I/O Processor Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > I/O Processor Shutdown

Inlet Pressure

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Inlet Pressure
Continued

262

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

Transducer Block (TB) Menu Structure (Continued)


Parameter Label
Input Characterization

Menu Structure
TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization
TB > Device Variables > Input Characterization

Integrator Limited Hi

TB > Device Diagnostics > Status > Self Test Status > Integrator Limited Hi

Integrator Limited Lo

TB > Device Diagnostics > Status > Self Test Status > Integrator Limited Lo

Integrator Suspended

TB > Device Diagnostics > Status > Self Test Status > Integrator Suspended

IOP Failure

TB > Device Diagnostics > Status > Self Test Status > IOP Failure

Last Calibration Type

TB > Configure/Setup > Detailed Setup > Instrument > Last Calibration Type

Leak Class

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Leak Class

Length Units

TB > Configure/Setup > Detailed Setup > Instrument > Length Units

Lever Arm Length

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Arm Length

Lever Style

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Style

Lost Static Data

TB > Device Diagnostics > Status > Block Error > Lost Static Data

Lower Bench Set

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lower Bench Set

MAI Channel 1

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 1

MAI Channel 2

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 2

MAI Channel 3

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 3

MAI Channel 4

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 4

MAI Channel 5

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 5

MAI Channel 6

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 6

MAI Channel 7

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 7

MAI Channel 8

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 8

Maint Active

TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate Active Alerts > Maint Active

Maintenance Enable

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Enable > Maintenance Enable

Maintenance Suppress

TB > Configure/Setup > Detailed Setup > Alerts > PlantWeb Alert Reporting > Maintenance Suppress

Maximum Recorded Supply


Pressure

TB > Device Diagnostics > Device Record > Maximum Recorded Supply Pressure

Maximum Recorded Supply


Pressure Time

TB > Device Diagnostics > Device Record > Maximum Recorded Supply Pressure Time

Maximum Recorded
Temperature

TB > Device Diagnostics > Device Record > Maximum Recorded Temperature

Maximum Recorded
Temperature Time

TB > Device Diagnostics > Device Record > Maximum Recorded Temperature Time

Maximum Supply Pressure

TB > Configure/Setup > Detailed Setup > Instrument > Maximum Supply Pressure

Minimum Recorded Supply


Pressure

TB > Device Diagnostics > Device Record > Minimum Recorded Supply Pressure

Minimum Recorded Supply


Pressure Time

TB > Device Diagnostics > Device Record > Minimum Recorded Supply Pressure Time

Minimum Recorded
Temperature

TB > Device Diagnostics > Device Record > Minimum Recorded Temperature

Minimum Recorded
Temperature Time

TB > Device Diagnostics > Device Record > Minimum Recorded Temperature Time

MLFB Error

TB > Device Diagnostics > Status > Self Test Status > MLFB Error

Nominal Supply Pressure

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Nominal Supply Pressure

Out of Service

TB > Device Diagnostics > Status > Block Error > Out of Service

Outlet Pressure

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Outlet Pressure

Outblock Selection

TB > Configure/Setup > Detailed Setup > Response Control > Outblock Selection

Output Block Timeout

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout

Output Block Timeout Alert

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Alert

Output Block Timeout Alert


Enable

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Alert Enable

Output Block Timeout Manual


Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Manual
Recovery

Output Block Timeout Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Configuration Alerts > Output Block Timeout > Output Block Timeout Shutdown

Packing Type

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Packing Type

PD Inside Status

TB > Configure/Setup > Device Variables > PD Inside Status

PD Run

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > PD Run
Continued

263

Instruction Manual

Field Communicator Menu Structure


August 2012

D103412X012

Transducer Block (TB) Menu Structure (Continued)


Parameter Label

Menu Structure

Performance Critical Alert

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Critical Alert

Performance Critical Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Performance Critical Alert Enable

Performance Information Alert

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Information Alert

Performance Information Alert


Enable

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Information Alert Enable

Performance Reduced Alert

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Reduced Alert

Performance Reduced Alert


Enable

TB > Configure/Setup > Detailed Setup > Alerts > Performance Alerts > Peformance Reduced Alert Enable

Performance Tuner

TB > Configure/Setup > Basic Setup > Performance Tuner


TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Performance Tuner

PlantWeb Alert Simulate

TB > Configure/Setup > Detailed Setup > Alert Handling > PlantWeb Alert Simulate

Port Diameter

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Diameter

Port Type

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Type

Pressure A

TB > Device Variables > Pressures > Pressure A

Pressure A Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Alert

Pressure A Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Alert Enable

Pressure A Sensor Failure

TB > Device Diagnostics > Status > Self Test Status > Pressure A Sensor Error

Pressure A Sensor Manual


Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Manual Recovery

Pressure A Sensor Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure A Sensor Shutdown

Pressure B

TB > Device Variables > Pressures > Pressure B

Pressure B Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure B Sensor Alert

Pressure B Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Pressure B Sensor Alert Enable

Pressure B Sensor Failure

TB > Device Diagnostics > Status > Self Test Status > Pressure B Sensor Error

Pressure Cutoff Closed

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Cutoff Closed

Pressure Cutoff Open

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Cutoff Open

Pressure Fallback Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Fallback > Pressure Fallback Alert

Pressure Fallback Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Fallback > Pressure Fallback Alert Enable

Pressure Integral Dead Zone

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Dead Zone

Pressure Integral Gain

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Gain

Pressure Integral Limit Hi

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Limit Hi

Pressure Integral Limit Lo

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Integral Limit Lo

Pressure MLFB Gain

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure MLFB Gain

Pressure Proportional Gain

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Proportional Gain

Pressure Range Hi

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Range Hi

Pressure Range Lo

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Pressure Range Lo

Pressure Tuning Set

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning > Pressure Tuning Set

Pressure Units

TB > Configure/Setup > Detailed Setup > Instrument > Pressure Units

Processor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Processor Alert

Processor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Processor Alert Enable

Program Memory Alert

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Alert

Program Memory Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Alert Enable

Program Memory Manual


Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Manual Recovery

Program Memory Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Program Memory Shutdown

Protection

TB > Device Variables > Protection

Proximity Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Alert

Proximity Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Alert Enable

Proximity Hi Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Hi Alert

Proximity Hi Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Hi Hi Alert Enable

Proximity Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Alert

Proximity Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Alert Enable

Proximity Lo Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Lo Alert

Proximity Lo Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Proximity > Proximity Lo Lo Alert Enable

Push Down To

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Push Down To
Continued

264

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

Transducer Block (TB) Menu Structure (Continued)


Parameter Label

Menu Structure

Rated Travel

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Rated Travel

Relay Type

TB > Configure/Setup > Detailed Setup > Instrument > Relay Type

Seat Type

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Seat Type

Setpoint

TB > Device Variables > AO ControlPreChar > Setpoint

Setpoint Status

TB > Device Variables > AO ControlPreChar > Setpoint Status

Setpoint(D)

TB > Device Variables > DO Control > Setpoint(D)

Shaft Stem Diameter

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Shaft Stem Diameter

Simulate Active

TB > Device Diagnostics > Status > Block Error > Simulate Active

Simulate Jumper ON

TB > Device Diagnostics > Status > Self Test Status > Simulate Jumper ON

Spring Rate

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Spring Rate

Spring Rate Units

TB > Configure/Setup > Detailed Setup > Instrument > Spring Rate Units

Static Memory Alert

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Alert

Static Memory Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Alert Enable

Static Memory Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Manual Recovery

Static Memory Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Elect Alerts > Processor Impaired > Static Memory Shutdown

Stroke Time Close

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Close

Stroke Time Open

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Open

Supply

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply
TB > Device Variables > Pressures > Supply

Supply Pressure Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert

Supply Pressure Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert Enable

Supply Pressure Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Hi Alert Point

Supply Pressure Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert

Supply Pressure Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert Enable

Supply Pressure Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Supply Pressure > Supply Pressure Lo Alert Point

Supply Pressure Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Supply Pressure Sensor Alert

Supply Pressure Sensor Alert


Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Pressure Sensors > Supply Pressure Sensor Alert Enable

Supply Sensor Failure

TB > Device Diagnostics > Status > Self Test Status > Supply Sensor Failure

Tag Description

TB > Configure/Setup > Detailed Setup > Instrument > Tag Description

Temperature

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature

Temperature Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert

Temperature Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert Enable

Temperature Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Hi Alert Point

Temperature Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert

Temperature Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert Enable

Temperature Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment Alerts > Temperature Limit > Temperature Lo Alert Point

Temperature Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Temperature Sensor > Temperature Sensor Alert

Temperature Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Temperature Sensors > Temperature Sensor Alert Enable

Temperature Units

TB > Configure/Setup > Detailed Setup > Instrument > Temperature Units

Travel

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel

Travel (DeChar)

TB > Device Variables > AO ControlPreChar > Travel(DeChar)

Travel Accumulator

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator
TB > Device Variables > Travel Accumulator

Travel Accumulator Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert

Travel Accumulator Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert Enable

Travel Accumulator Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Alert Point

Travel Accumulator Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel History Alerts > Travel Accumulator > Travel Accumulator Deadband

Travel Closed Alert

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert

Travel Closed Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert Enable

Travel Closed Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Alert Point

Travel Closed Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Closed > Travel Closed Deadband

Travel Count

TB > Device Variables > Travel Count

Travel Cutoff Hi

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Cutoff Hi
Continued

265

Instruction Manual

Field Communicator Menu Structure


August 2012

D103412X012

Transducer Block (TB) Menu Structure (Continued)


Parameter Label

Menu Structure

Travel Cutoff Lo

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Cutoff Lo

Travel Deviation

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation

Travel Deviation Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert

Travel Deviation Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert Enable

Travel Deviation Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Alert Point

Travel Deviation Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Deadband

Travel Deviation Pressure


Fallback

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel Deviation Pressure Fallback

Travel Deviation Time

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Deviation > Travel Deviation Time

Travel Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert

Travel Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert Enable

Travel Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Alert Point

Travel Hi Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Hi Deadband

Travel Hi Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert

Travel Hi Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert Enable

Travel Hi Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Alert Point

Travel Hi Hi Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Hi Hi Deadband

Travel Integral Dead Zone

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Dead Zone

Travel Integral Enable

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Enable

Travel Integral Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Gain

Travel Integral Limit Hi

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Limit Hi

Travel Integral Limit Lo

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Integral Limit Lo

Travel Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert

Travel Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert Enable

Travel Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Alert Point

Travel Lo Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Hi/Lo > Travel Lo Deadband

Travel Lo Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert

Travel Lo Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert Enable

Travel Lo Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Alert Point

Travel Lo Lo Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel Alerts > Travel Limit > Travel Lo Lo Deadband

Travel MLFB Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel MLFB Gain

Travel Open Alert

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert

Travel Open Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert Enable

Travel Open Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Alert Point

Travel Open Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Prox Alerts > Travel Open > Travel Open Deadband

Travel Proportional Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Proportional Gain

Travel Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Alert

Travel Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Alert Enable

Travel Sensor Hi Error

TB > Device Diagnostics > Status > Self Test Status > Travel Sensor Hi Error

Travel Sensor Lo Error

TB > Device Diagnostics > Status > Self Test Status > Travel Sensor Lo Error

Travel Sensor Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Manual Recovery

Travel Sensor Motion

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Travel Sensor Motion

Travel Sensor Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Sensor Alerts > Travel Sensor > Travel Sensor Shutdown

Travel Sensor Span Error

TB > Device Diagnostics > Status > Self Test Status > Travel Sensor Span Error

Travel Status

TB > Device Variables > AO ControlPostChar > Travel Status

Travel Tuning Set

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Tuning Set

Travel Units

TB > Configure/Setup > Detailed Setup > Instrument > Travel Units

Travel Velocity Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning > Travel Velocity Gain

Travel(D)

TB > Device Variables > DO Control > Travel(D)

Travel/Pressure Select

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel/Pressure Select

Travel/Pressure State

TB > Configure/Setup > Detailed Setup > Response Control > Travel Pressure Control > Travel/Pressure State
TB > Device Variables > Travel/Pressure State

Trend

TB > Device Diagnostics > Trend

Trim Style 1

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 1
Continued

266

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

Transducer Block (TB) Menu Structure (Continued)


Parameter Label

Menu Structure

Trim Style 2

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 2

Unbalanced Area

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Unbalanced Area

Upper Bench Set

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Upper Bench Set

Valve Class

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Class

Valve Manufacturer

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Manufacturer

Valve Model Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Model Number

Valve Serial Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Serial Number

Valve Size

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Size

Valve Style

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Style

Zero Power Condition

TB > Configure/Setup > Detailed Setup > Instrument > Zero Power Condition

TRANSDUCER BLOCK
BASIC SETUP

Top Level
Configure/Setup
Device Diagnostics
Device Variables

Configure/Setup
Basic Setup
Detailed Setup
Calibration

Basic Setup
Device Setup
Performance Tuner

267

Instruction Manual

Field Communicator Menu Structure


August 2012

D103412X012
Travel Tuning

TRANSDUCER BLOCK
DETAILED SETUP

:Travel Tuning Set


Travel Proportional Gain
Travel Velocity Gain
:Travel MLFB Gain
:Travel Integral Enable
:Travel Integral Gain
:Travel Integral Dead Zone
:Travel Integral Limit Hi
:Travel Integral Limit Lo
Performance Tuner
Stabilize / Optimize

Response Control
Travel Tuning
Pressure Tuning
Travel Press Control
Input Characterization
Custom Characterization Table
Outblock Selection

Top Level
Configure/Setup
Device Diagnostics
Device Variables

Travel Press Control

Configure/Setup
Basic Setup
Detailed Setup
Calibration

Detailed Setup
Transducer Block Mode
Protection
Response Control
Alerts
Instrument
Valve and Actuator
MAI Channel Map
Alert Handling

MAI Channel Map

Alert Handling
PlantWeb Alert Simulate
Simulate Active Alerts
PlantWeb Alert Handling

:MAI Channel 1
:MAI Channel 2
:MAI Channel 3
:MAI Channel 4
:MAI Channel 5
:MAI Channel 6
:MAI Channel 7
:MAI Channel 8

:Travel/Pressure State
:Travel/Pressure Select
Travel Deviation Pressure Fallback
Travel Cutoff Hi
Travel Cutoff Lo
:Pressure Cutoff Open
:Pressure Cutoff Closed
:Pressure Range Hi
:Pressure Range Lo

Tag Description
Pressure Units
Temperature Units
Travel Units
Length Units
Area Units
Spring Rate Units
:Relay Type
:Zero Power Condition
:Maximum Supply Pressure
Calibration Person
Calibration Location
Calibration Date
:Last Calibration Type

Simulate Active Alarms

Valve and Actuator

PlantWeb Alerts Set PV Status


Block Error Reporting

Failed Active
Maint Active
Advise Active

Valve
Trim
Actuator
Reference

Reference

268

:Pressure Tuning Set


:Pressure Proportional Gain
:Pressure MLFB Gain
:Pressure Integral Gain
:Pressure Integral Dead Zone
:Pressure Integral Limit Hi
:Pressure Integral Limit Lo

Alerts (See facing page)


Instrument

PlantWeb Alert Handling

:Trim Style 1
:Trim Style 2
:Stroke Time Open
:Stroke Time Close

Pressure Tuning

Actuator
Actuator Manufacturer
Actuator Model Number
:Actuator Style
Actuator Serial Number
:Actuator Size
Actuator Fail Action
:Feedback Connection
:Travel Sensor Motion
:Lever Style
:Lever Arm Length
:Effective Area
:Air
:Upper Bench Set
:Lower Bench Set
:Nominal Supply Pressure
:Spring Rate

Elect Alerts
Configuration Alerts
Sensor Alerts
Environment Alerts
Travel Alerts
Prox Alerts
Travel History Alerts
Performance Alerts
PlantWeb Alert Enable
PlantWeb Alert Reporting

Valve
Valve Manufacturer
Valve Model Number
Valve Serial Number
Valve Style
:Valve Size
:Valve Class
:Rated Travel
:Actual Travel
:Shaft Stem Diameter
:Packing Type
:Inlet Pressure
:Outlet Pressure
Trim
:Seat Type
:Leak Class
:Port Diameter
:Port Type
:Flow Direction
:Push Down To
:Flow Tends To
:Unbalanced Area

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

Drive Current

TRANSDUCER BLOCK
DETAILED SETUP > ALERTS
(continued on next page)

Drive Current
:Drive Current Alert
:Drive Current Alert Enable
:Drive Current Shutdown
:Drive Current Manual Recovery
:Drive Current Alert Point
:Drive Current Alert Time

Elect Alerts
Drive Current
Drive Signal
Processor Impaired

Alerts
Elect Alerts
Configuration Alerts
Sensor Alerts
Environment Alerts
Travel Alerts
Prox Alerts
Travel History Alerts
Performance Alerts
PlantWeb Alert Enable
PlantWeb Alert Reporting

Configuration Alerts
Output Block Timeout
Blocks Set to Default
Alert Key

Drive Signal
Processor Impaired
:Program Memory Alert
:Program Memory Alert Enable
:Program Memory Shutdown
:Program Memory Manual Recovery
:Static Memory Alert
:Static Memory Alert Enable
:Static Memory Shutdown
:Static Memory Manual Recovery
:Processor Alert
:Processor Alert Enable
:I/O Processor Alert
:I/O Processor Alert Enable
:I/O Processor Shutdown
:I/O Processor Man Recovery

Drive Signal
:Drive Signal Alert
:Drive Signal Alert Enable

Output Block Timeout


Blocks Set to Default
:Blocks Set to Defaults Alert
:Blocks Set to Defaults Alert Enable

:Output Block Timeout Alert


:Output Block Timeout Alert Enable
:Output Block Timeout Shutdown
:Output Block Timeout Manual Recovery
:Output Block Timeout

Sensor Alerts
Travel Sensor
Pressure Sensors
Pressure Fallback
Temperature Sensor

Travel Sensor

Pressure Fallback
:Pressure Fallback Alert
:Pressure Fallback Alert Enable
Temperature Sensor
:Temperature Sensor Alert
:Temperature Sensor Alert Enable

Environment Alerts
Supply Pressure
Temperature Limit
Temperature Limit
Temperature
:Temperature Hi Alert
:Temperature Hi Alert Enable
Temperature Hi Alert Point
:Temperature Lo Alert
:Temperature Lo Alert Enable
:Temperature Lo Alert Point

Supply Pressure

:Travel Sensor Alert


:Travel Sensor Alert Enable
:Travel Sensor Shutdown
:Travel Sensor Manual Recovery
Pressure Sensors
:Pressure A Sensor Alert
:Pressure A Sensor Alert Enable
:Pressure A Sensor Shutdown
:Pressure A Sensor Manual Recovery
:Pressure B Sensor Alert
:Pressure B Sensor Alert Enable
:Supply Pressure Sensor Alert
:Supply Pressure Sensor Alert Enable

:Supply
:Supply Pressure Hi Alert
:Supply Pressure Hi Alert Enable
Supply Pressure Hi Alert Point
:Supply Pressure Lo Alert
:Supply Pressure Lo Alert Enable
:Supply Pressure Lo Alert Point

269

Instruction Manual

Field Communicator Menu Structure


August 2012

D103412X012

TRANSDUCER BLOCK
DETAILED SETUP > ALERTS

Alerts

Travel Open

Elect Alerts
Configuration Alerts
Sensor Alerts
Environment Alerts
Travel Alerts
Prox Alerts
Travel History Alerts
Performance Alerts
PlantWeb Alert Enable
PlantWeb Alert Reporting

Travel Open Alert


Travel Open Alert Enable
:Travel Open Alert Point
:Travel Open Deadband

Travel Alerts

Travel Deviation

:Travel Target
:Travel
Travel Deviation
Travel Limit
Travel Hi/Lo

Travel Deviation
:Travel Deviation Alert
:Travel Deviation Alert Enable
:Travel Deviation Alert Point
:Travel Deviation Time
:Travel Deviation Deadband
Travel Limit
:Travel Hi Hi Alert
:Travel Hi Hi Alert Enable
:Travel Hi Hi Alert Point
:Travel Hi Hi Deadband
:Travel Lo Lo Alert
:Travel Lo Lo Alert Enable
:Travel Lo Lo Alert Point
:Travel Lo Lo Deadband

Prox Alerts
:Travel
Travel Open
Travel Closed
Proximity

Travel Hi/Lo
:Travel Hi Alert
:Travel Hi Alert Enable
:Travel Hi Alert Point
:Travel Hi Deadband
:Travel Lo Alert
:Travel Lo Alert Enable
:Travel Lo Alert Point
:Travel Lo Deadband

Proximity
:Proximity Hi Hi Alert
:Proximity Hi Hi Alert Enable
:Proximity Hi Alert
:Proximity Hi Alert Enable
:Proximity Lo Alert
:Proximity Lo Alert Enable
:Proximity Lo Lo Alert
:Proximity Lo Lo Alert Enable

PlantWeb Alert Reporting


Failed Suppress
Maintenance Suppress
Advise Suppress
PlantWeb Alert Enable

Travel Closed
:Travel Closed Alert
:Travel Closed Alert Enable
:Travel Closed Alert Point
:Travel Closed Deadband

Failed Enable
Maintenance Enable
Advise Enable
Travel History Alerts
Cycle Counter
Travel Accumulator
Performance Alerts
:PD Inside Status
:PD Run
Performance Critical
Performance Reduced
Performance Information

Cycle Counter
:Cycle Counter Alert
:Cycle Counter Alert Enable
:Cycle Counter Alert Point
:Cycle Counter Deadband
Travel Accumulator
Travel Accumulator
:Travel Accumulator Alert
:Travel Accumulator Alert Enable
:Travel Accumulator Alert Point
:Travel Accumulator Deadband

Performance Information
Performance Information Alert
Performance Information Alert Enable

270

Cycle Counter

Performance Reduced

Performance Critical

Performance Reduced Alert


Performance Reduced Alert Enable

Performance Critical Alert


Performance Critical Alert Enable

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

TRANSDUCER BLOCK
CALIBRATION
Top Level
Configure/Setup
Device Diagnostics
Device Variables

Configure/Setup
Basic Setup
Detailed Setup
Calibration

Calibration
Auto Calibration
Manual Calibration
Relay
Supply Pressure
Pressure A
Pressure B

TRANSDUCER BLOCK
DEVICE DIAGNOSTICS
Status

Top Level
Configure/Setup
Device Diagnostics
Device Variables

Self Test Status


Block Error

Device Diagnostics
Active PlantWeb Alerts
Alert Conditions
Status
Device Record
Stroke Valve
Trend

Block Error
Block Configuration Error
Simulate Active
Lost Static Data
Device Needs Maintenance Now
Out of Service
Device Record
:Maximum Recorded Temperature
:Maximum Recorded Temperature Time
:Minimum Recorded Temperature
:Minimum Recorded Temperature Time
:Maximum Recorded Supply Pressure
:Maximum Recorded Supply Pressure Time
:Minimum Recorded Supply Pressure
:Minimum Recorded Supply Pressure Time

TRANSDUCER BLOCK
DEVICE VARIABLES

Self Test Status


Integrator Suspended
Integrator Limited Lo
Integrator Limited Hi
Travel Sensor Span Error
MLFB Error
Travel Sensor Hi Error
Travel Sensor Lo Error
Pressure B Sensor Failure
Pressure A Sensor Failure
Supply Sensor Failure
IOP Failure
Drive Current Alert
Simulate Jumper ON

AO Control - PreChar

Top Level

Device Variables

Configure/Setup
Device Diagnostics
Device Variables

All Block Modes


AO Control - PreChar
AO Control - PostChar
DO Control
Input Characterization
:Travel/Pressure State
:PD Inside Status
Protection
Drive Signal
Temperature
Cycle Counter
Travel Accumulator
:Travel Count
Pressures

:Setpoint
:Setpoint Status
:Travel (DeChar)
AO Control - PostChar
:Travel Target
:Travel
:Travel Status
DO Control
:Setpoint(D)
:Travel(D)
Pressures
:Supply
:Pressure A
:Pressure B
:A Minus B

271

Instruction Manual

Field Communicator Menu Structure


August 2012

D103412X012

Resource Block (RB) Menu Structure


Parameter Label

Menu Structure

Alert Key

RB > Configure/Setup > Alarm Handling > Alert Key

Block Alarm: Alarm State

RB > Device Diagnostics > Block Alarm > Alarm State

Block Alarm: Unacknowledged

RB > Device Diagnostics > Block Alarm > Unacknowledge

Block Alarm Disabled

RB > Configure/Setup > Alarm Handling > Block Alarm Disabled

Block Alarm Automatically


Acknowledge

RB > Configure/Setup > Alarm Handling > Block Alarm Automatically Acknowledge

Confirm Time

RB > Configure/Setup > Alarm Handling > Confirm Time

DD Information

RB > Device Variables > DD information

Device ID

RB > Configure/Setup > Identification > Device ID or RB > Device Variables > Instrument > Identification > Device ID

Device Revision

RB > Configure/Setup > Version > Device Revision or RB > Device Variables > Instrument > Version > Device Revision

Device State

RB > Display > Resource Status > Device State


RB > Device Diagnostics > Device State

Device Type

RB > Configure/Setup > Identification > Device Type or RB > Device Variables > Instrument > Identification > Device Type

Diagnostics Options

RB > Configure/Setup > Options > Diagnostics Options

Discrete Alarm Disabled

RB > Configure/Setup > Alarm Handling > Discrete Alarm Disabled

Discrete Alarm Automatically


Acknowledge

RB > Configure/Setup > Alarm Handling > Discrete Alarm Automatically Acknowledge

Electronics Serial Number

RB > Configure/Setup > Identification > Elect S/N or RB > Device Variables > Instrument > Identification > Electronics Serial Number

Factory Serial Number

RB > Configure/Setup > Identification > Factory S/N or RB > Device Variables > Instrument > Identification > Factory Serial Number

Fault State

RB > Device Diagnostics > Maintenance > Fault State

Features Available

RB > Configure/Setup > Options > Features Available or RB > Device Variables > Options > Features Available

Features Selected

RB > Configure/Setup >Options > Features Selected

Field Serial Number

RB > Configure/Setup > Identification > Field S/N or RB > Device Variables > Instrument > Identification > Field Serial Number

Firmware Revision

RB > Configure/Setup > Version > Firmware Revision or RB > Device Variables > Instrument > Version > Firmware Revision

Function Block Options

RB > Configure/Setup > Options > Function Block Options or RB > Device Variables > Options > Function Block Options

Hardware Revision

RB > Configure/Setup > Version > Hardware Revision or RB > Device Variables > Instrument > Version > Hardware Revision

ITK Version

RB > Configure/Setup > Version > ITK Version or RB > Device Variables > Instrument > Version > ITK Version

Limit Notify

RB > Configure/Setup > Alarm Handling > Limit Notify

Manufacturer

RB > Configure/Setup > Identification > Manufacturer or RB > Device Variables > Instrument > Identification > Manufacturer

Maximum Notify

RB > Configure/Setup > Alarm Handling > Maximum Notify

Miscellaneous Options

RB > Configure/Setup > Options >Miscellaneous Options or RB > Device Variables > Options >Miscellaneous Options

Resource Block Error

RB > Device Diagnostics > Resource Block Error

Shed Remote Cascade

RB > Configure/Setup > Communication Time Out > Shed Remote Cascade

Shed Remote Out

RB > Configure/Setup > Communication Time Out > Shed Remote Out

Standby Firmware Revision

RB > Configure/Setup > Version > Standby Software Revision or RB > Device Variables > Instrument > Version > Standby Software
Revision

Strategy

RB > Configure/Setup > Identification > Strategy or RB > Device Variables > Instrument > Identification > Strategy

Tag Description

RB > Configure/Setup > Identification > Tag Description or RB > Device Variables > Instrument > Identification > Tag Description

Write Alarm: Alarm State

RB > Device Diagnostics > Write Lock > Write Alarm: Alarm State

Write Lock

RB > Configure/Setup > Write Lock > Write Lock or RB > Device Diagnostics > Write Lock > Write Lock

Write Priority

RB > Configure/Setup > Write Lock > Write Priority

272

Instruction Manual

Field Communicator Menu Structure

D103412X012

August 2012

Write Lock
Write Priority

Configure/Setup
Device Diagnostics
Device Variables

Shed Remote Cascade


Shed Remote Out

Resource Block Mode


Write Lock
Comm Timeout
Options
Alarm Handling
Identification
Version

Options

Device Revision
Firmware Revision
Standby Firmware Revision
Hardware Rev
ITK Version
Identification
Device ID
Electronics Serial Number
Factory Serial Number
Field Serial Number
Tag Description
Strategy
Manufacturer
Device Type
Diagnostics Options

Features Available

Alert Key
Confirm Time
Limit Notify
Maximum Notify
Block Alm Disabled
Block Alarm Auto Acknowledge
Disc Alm Disabled
Discrete Alarm Auto Acknowledge

Reports
Fault State
Soft W Lock
Multibit Alarm (BitAlarm) Support

Maintenance
Restart Actions
Fault State
Set Fault State
Clear Fault State

RESOURCE BLOCK
DEVICE VARIABLES
Top Level

Instrument

Configure/Setup
Device Diagnostics
Device Variables

Device Variables
Instrument
Options
DD Information
Options
Diagnostics Options
Function Block Options
Miscellaneous Options
Features Available

Features Selected
Reports
Fault State
Soft W Lock
Multibit Alarm (BitAlarm) Support
Resource Block Error

Resource Block Error


Device State
Write Lock
Block Alarm
Maintenance

Configure/Setup
Device Diagnostics
Device Variables

Firmware Download
Travel Control Capable
Pressure Control Capable
Pressure Fallback Capable

Alarm Handling

Device Diagnostics

Top Level

Miscellaneous Options

Diagnostics Options
Function Block Options
Miscellaneous Options
Features Available
Features Selected

Version

RESOURCE BLOCK
DEVICE DIAGNOSTICS

AO
DO
AI
DI
PID
IS
OS
MAI

Comm Timeout

Configure/Setup

Top Level

Function
Block Options

Write Lock

RESOURCE BLOCK
CONFIGURE/SETUP

Identification
Version
Function
Block Options
AO
DO
AI
DI
PID
IS
OS
MAI

Features Available

Miscellaneous Options

Reports
Fault State
Soft W Lock
Multibit Alarm (BitAlarm) Support

Firmware Download
Travel Control Capable
Pressure Control Capable
Pressure Fallback Capable

Other
Block Configuration Error
Simulate Active
Device Needs Maintenance Soon
Memory Failure
Lost Static Data
Lost NV Data
Device Needs Maintenance Now
Power Up
Out of Service
Write Lock
Write Alarm Alarm State
Write Lock
Block Alarm
Block Alarm Alarm State
Block Alarm Unacknowledged
Identification
Device ID
Electronics Serial Number
Factory Serial Number
Field Serial Number
Tag Description
Strategy
Manufacturer
Device Type
Version
Device Revision
Firmware Revision
Standby Firmware Revision
Hardware Rev
ITK Version

273

Field Communicator Menu Structure


August 2012

274

Instruction Manual
D103412X012

Instruction Manual
D103412X012

PlantWeb Alerts
August 2012

Appendix C PlantWeb AlertsCC


Instrument Alert Conditions
Instrument Alert Conditions, when enabled, detect many operational and performance issues that may be of interest.
To view these alerts, the user must open the appropriate status screen on a host such as a DeltaV system, ValveLink
software or a Field Communicator.

PlantWeb Alerts
Some instrument alert conditions can also be used to trigger PlantWeb alerts that will be reported in Failed,
Maintenance or Advisory categories, as configured by the user. PlantWeb alerts, when enabled, can participate in the
DeltaV alarm interface tools such as the alarm banner, alarm list and alarm summary. For specific information on
setting up PlantWeb Alerts in a DeltaV system, refer to the PlantWeb Alerts section in Appendix F.
When a PlantWeb alert occurs, the DVC6200f sends an event notification and waits a specified period of time for an
acknowledgment to be received. This occurs even if the condition that caused the alert no longer exists. If the
acknowledgment is not received within the prespecified timeout period, the event notification is retransmitted. This
reduces the possibility of alert messages getting lost.

ModeBased PlantWeb Alerts


Some PlantWeb alerts are not active unless the transducer block (actual) mode is Auto.
1. Alerts which can be triggered by the activities of the service technician are reported only when the transducer block
mode is AUTO.
2. Alerts which are unrelated to service technician activities are reported in all transducer block modes.
Exceptions are as follows:
Alerts can be simulated regardless of transducer block mode but must be enabled to be reported.
When a shutdown condition exists (either currently active or latched on through the shutdown recovery parameter)
in the transducer block, alerts are reported even though the mode of the transducer block is OOS.
Refer to table C1 for reporting of PlantWeb Alerts.

Alert Handling
Alert handling is diagrammed in figure C1. There are two ways of seeing PlantWeb alerts. One way is to see if the
instrument alert condition causing a PlantWeb alert is detected. The second is to view alerts reported to the system
operator console. For a PlantWeb alert to be active, it has to pass four tests. The first is to check if the Instrument alert
condition is enabled. If a condition is not enabled, the instrument does not check for the alert condition.
Second, the condition that will cause an alert must exist. For example, the current travel is above the Travel Limit Hi
Alert Point.
Third, the corresponding PlantWeb alert must be enabled in one or more of the three categories: Failed, Maintenance
or Advise.
Fourth, the transducer block mode must be correct. See table C1.

Note
Additional details on setting up and using Instrument Alerts can be found on page 69 of this manual.

275

Instruction Manual

PlantWeb Alerts
August 2012

D103412X012

Figure C1. Alert Handling


Set Alert Points
and Deadband in
the Transducer
Block

START

"

ALERT
CONDITION
ENABLED?

Enable Instrument
Alert Condition in
the Transducer
Block

Yes
"

LIMITS EXCEEDED TO
CAUSE ALERT?

No

Enable PlantWeb
Alert in the
Transducer Block

Yes INSTRUMENT
" ALERT
CONDITION
ACTIVE

Yes
"

Use Resource and Transducer


Block Parameters to Configure

Yes
"

PLANTWEB
ALERT
ENABLED?

No

No

Yes
PLANTWEB
" ALERT ACTIVE

No

NO ACTIVE
PLANTWEB ALERT

1
TRANSDUCER
BLOCK MODE
AUTO

B
NO ACTIVE INSTRUMENT
ALERT CONDITION

No

REPORT
ALERTS?

Yes

B
No

Select Reports
Supported from
FEATURE_SEL in the
Resource Block

PRIORITY
>1?

Set Priority with


PlantWeb Alarm
Priority parameters in
Transducer Block using
DeltaV

B Yes
B
Instrument Alert
Conditions active,
but not reported

NOTE:
1
CERTAIN
PLANTWEB ALERTS ARE MODEBASED.
SEE TABLE C1 FOR DETAILS.

Table C1. PlantWeb Alerts Reporting Requirements

276

PlantWeb Alert

Transducer Block Mode (Actual)

Drive Current

AUTO

Drive Signal

AUTO

Processor Impaired

Any Mode

Output Block Timeout

Any Mode

Block Set to Defaults

Any Mode

Travel Sensor

AUTO

Output Pressure Sensor

Any Mode

Supply Pressure Sensor

Any Mode

Temperature Sensor

Any Mode

Supply Pressure

AUTO

Temperature Limit

AUTO

Travel Deviation

AUTO

Travel Limit

AUTO

Cycle Counter

AUTO

Travel Accumulator

AUTO

Performance Critical

AUTO

Performance Reduced

AUTO

Performance Information

AUTO

Pressure Fallback

AUTO

Yes

SUPPRESS
REPORTINGAL
ERT
CONDITION?

B No
PLANTWEB
ALERTS
REPORTED

Suppress Alert
Condition Reporting
with Alarm Suppress
Parameters in
Transducer Block

Instruction Manual
D103412X012

PlantWeb Alerts
August 2012

Alert Reporting
For PlantWeb alerts to be reported to the operator console, they must pass four tests:
 Alerts must be active
 Reports must be selected in Feature Select
 Alert priority must be greater than 1
 Reporting must not be suppressed for those conditions that caused active alerts.
Features Selected in the Resource block determines if reporting by the instrument is supported. Refer to page 47 for
additional information on Features Selected.
Failed Priority (FAILED_PRI [68]), Maintenance Priority (MAINT_PRI [69]), and Advise Priority (ADVISE_PRI [70])
determine the PlantWeb alert priorities. Although 16 priorities are available only three are actually meaningful for
PlantWeb alerts. If the priority is 0, no reporting occurs. If the priority is 1, reporting is simulated within the
instrument, but the alert is not actually reported over the bus. The alert condition is reported for priorities 2 through
15, with the higher priorities taking precedence over the lower priorities.
Failed Suppress (FAILED_MASK [65]), Maintenance Suppress (MAINT_MASK [66]), and Advise Suppress (ADVISE_MASK
[67]) determine which of the alert conditions are suppressed so that they are not reported.

PlantWeb Alerts Set Block Status


If a PlantWeb Alert is active, the AO or DO Block Readback parameter status may change. This behavior is controlled
with the PlantWeb Alerts Set PV Status (PWA_SET_STATUS [97]) parameter in the transducer block

Setting PlantWeb Alerts


Refer to table C2 for information on setting PlantWeb alerts. When selected, PlantWeb alarms will set the PV status
according to table C4.

Using PlantWeb Alerts


Refer to table C3 for information on using PlantWeb alerts.

277

Instruction Manual

PlantWeb Alerts
August 2012

D103412X012

Table C2. Setting PlantWeb Alerts


PlantWeb Alert
(Group)
(Default Alert Category)
Drive Current
(Electronics)
(Failed)

Alert Condition
(Default)

Drive Current
(Enabled)

What the Alert is Detecting

Related Parameters
(Default)

The difference between the


expected Drive Current and the
actual Drive Current has
exceeded the Drive Current
Alert Time.

Self Test Shutdown (No)


Shutdown Recovery (Auto)
Alert Point (50%)
Alert Time (5 sec)

Guidelines for Setting

Use default settings

If one of the following


conditions exist:

Drive Signal
(Electronics)
(Maintenance)

Drive Signal
(Enabled)

Where Zero Power Condition is


defined as closed:
Drive Signal < 10% and
Calibrated Travel > 3%
Drive Signal > 90% and
Calibrated Travel < 97%

Use default setting

Where Zero Power Condition is


defined as open:
Drive Signal < 10% and
Calibrated Travel < 97%
Drive Signal > 90% and
Calibrated Travel > 3%

Processor Impaired
(Electronics)
(Maintenance)

Output Block Timeout


(Configuration)
(Maintenance)

Program Memory
(Enabled)

A pending Flash or NVM failure


is present.

Self Test Shutdown (No)


Shutdown Recovery (Auto)

Use default settings

Static Memory
(Enabled)

A failure of the FRAM memory


where static parameters are
stored.

Self Test Shutdown (No)


Shutdown Recovery (Auto)

Use default settings

Processor
(Enabled)

A failure of the main Processor.

Self Test Shutdown (No)


Shutdown Recovery (Auto)

Use default settings

I/O Processor
(Enabled)

A failure of the I/O Processor.

Self Test Shutdown (No)


Shutdown Recovery (Auto)

Use default settings

Output Block
Timeout
(Disabled)

If the analog or discrete output


block has not executed for
longer than the configured
timeout.

Timeout Alert Point (600 s)


Self Test Shutdown (No)
Shutdown Recovery (Auto)

Enable this alert for loops where the


execution is critical. If the AO or DO block
is not scheduled, or scheduled incorrectly,
it will trigger an alert after the Timeout
Alert Point has been exceeded. Set the
Timeout Alert Point to a value between
a. 30 seconds and
b. the maximum time before a user
should be notified. The minimum number
depends on the time it takes for a host to
download a configuration to the device.
Shutdown can be enabled if it is desired to
move the valve to the Zero Power
Condition at the same time that the alert
is generated.

Blocks Set to Default


(Configuration)
(Maintenance)

Blocks Set to Default


(Enabled)

If the resource block has


undergone Restart with
Defaults

None

Use default settings

Shutdown Alert
(Configuration)
(Maintenance)

N/A

A user configured Self Test


Shutdown condition has taken
the instrument to OOS.

None

Use default settings

-Continued-

278

Instruction Manual

PlantWeb Alerts

D103412X012

August 2012

Table C2. Setting PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category)

Alert Condition
(Default)

What the Alert is Detecting

Related Parameters
(Default)

Guidelines for Setting


Double Acting Actuators Enable the
alert and configure it to report in the
Failed Alert Category. Self Test Shutdown
is generally not enabled.

Travel Sensor
(Sensors)
(Failed)

Travel Sensor
(Enabled)

The travel feedback is within


acceptable limits.

Self Test Shutdown (No)


Shutdown Recovery (Auto)

Single Acting Actuators


If Travel / Pressure Control is configured
as Travel with Pressure Fallback: enable
the alert and configure it to report in the
Maintenance Alert Category. Do not
enable Self Test Shutdown.
IIf Travel / Pressure Control is configured
as Travel: Enable the alert and configure it
to report in the Failed Alert Category. Self
Test Shutdown is generally not enabled.

Output Press Sensor


(Sensors)
(Maintenance)

Port A Pressure
Sensor (Enabled)

The pressure sensor reading is


outside the functional range of
the sensor.

Port B Pressure
Sensor (Enabled)

Self Test Shutdown (No)


Shutdown Recovery (Auto)

If Travel / Pressure Control is configured


as Pressure: enable the alert and
configure it to report in the Failed Alert
Category. Enable the Self Test Shutdown.
For all other Travel / Pressure Control
selections, enable the alert to report in
the Maintenance Alert Category and do
not enable the Self Test Shutdown.

None

Use default settings

Supply Press Sensor


(Sensors)
(Advisory)

Supply Press Sensor


(Enabled)

The pressure sensor reading is


outside the functional range of
the sensor.

None

Use default settings

Temperature Sensor
(Sensors)
(Advisory)

Temperature Sensor
(Enabled)

The temperature sensor


reading is outside the
functional range of the sensor.

None

Use default settings

Pressure Fallback (Sensors)


(Maintenance)

Pressure Fallback
(Enabled)

A travel sensor failure or large


travel deviation has resulted in
fallback to pressure control.

None

Use default settings

Alert Point (145 psig)

Enable the alert in the Maintenance Alert


Category. Set the Alert Point to which
ever is lower of
a. the maximum instrument pressure of
145 psig or
b. the maximum actuator casing
pressure.

Alert Point (19 psig)

Enable the alert in the Maintenance Alert


Category.
Double Acting Actuators Set the Alert
Point above the minimum required for
valve shutoff and no greater than
1 psig below the supply regulator setting
Single Acting Actuators Set the Alert
Point above the minimum required for
valve shutoff and no greater than
1 psig below the supply regulator setting.
This is generally about 3 psig above the
actuator upper bench set (stroking)
pressure.

Supply Press High


(Enabled)

The supply pressure has


exceeded the Supply Pressure
Hi Alert Point.

Supply Pressure
(Environment)
(Maintenance)
Supply Press Low
(Enabled)

The supply pressure is lower


than the Supply Pressure Lo
Alert Point.

-Continued-

279

Instruction Manual

PlantWeb Alerts
August 2012

D103412X012

Table C2. Setting PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category)

Alert Condition
(Default)

What the Alert is Detecting

Related Parameters
(Default)

Guidelines for Setting


Use default settings

Temperature High
(Enabled)

Temperature Limit
(Environment)
(Advisory)
Temperature Low
(Enabled)

The temperature is greater


than the Temperature Hi Alert
Point.

The temperature is lower than


the Temperature Lo Alert
Point.

Alert Point ( 186F)

Alert Point ( -63F)

Other alert points may be chosen to


indicate changes in the instrument
environment.
Enable the alert in the Maintenance Alert
Category. Set the Alert Point at -40F if
the instrument uses Nitrile elastomers
and -63F if it uses Fluorosilicone
elastomers.
Other alert points may be chosen to
indicate changes in the instrument
environment.
Enable the alert in the Maintenance Alert
Category. Use the default settings with
valves that are 4 inch and smaller with
PTFE packing systems.

Travel Deviation
(Travel)
(Maintenance)

Travel Limit
(Travel)
(Advisory)

N/A
(Travel)
(N/A)

N/A
(Proximity)
(N/A)

Travel Deviation
(Enabled)

Alert Point (5%)


Alert Time (10 sec)
Deadband (2%)

Travel Limit Hi Hi
(Disabled)

The Travel has exceeded the


Travel Limit Hi Hi Alert Point

Alert Point (125%)


Deadband (5%)

Enable this alert for critical loops, where it


is important to alert an operator if the
valve is approaching the wide open
position. A typical setting might be 95%.

Travel Limit Lo Lo
(Disabled)

The Travel is lower than the


Travel Limit Lo Lo Alert Point.

Alert Point (-25%)


Deadband (5%)

Enable this alert for critical loops, where it


is important to alert an operator if the
valve is approaching the closed position.
A typical setting might be 5%.

Travel Limit Hi
(Disabled)

The Travel has exceeded the


Travel Limit Hi Alert Point.

Alert Point (125%)


Deadband (5%)

Use the Alert Points and Deadband to


configure the Proximity Alerts below.

Travel Limit Lo
(Disabled)

The Travel is lower than the


Travel Limit Lo Alert Point.

Alert Point (-25%)


Deadband (5%)

Use the Alert Points and Deadband to


configure the Proximity Alerts below.

Travel Open
(Disabled)

The Travel is greater than the


Open Alert Point

Alert Point (99.5%)


Deadband (5%)

Enable and set to report Travel with DI


Block

Travel Closed
(Disabled)

The Travel is greater than the


Closed Alert Point

Alert Point (0.5%)


Deadband (5%)

Enable and set to report Travel with DI


Block

Alert Point (125%)


Deadband (5%)

Enable and set to report Travel with DI


Block

Alert Point (125%)


Deadband (5%)

Enable and set to report Travel with DI


Block

Alert Point (-25%)


Deadband (5%)

Enable and set to report Travel with DI


Block

Alert Point (-25%)


Deadband (5%)

Enable and set to report Travel with DI


Block

Alert Point (1,000,000)


Deadband (1%)

Bellows Seal Bonnets enable the alert in


the Maintenance Alert Category. Use the
bellows manufacturer's cycle life data to
set cycle limits.

Proximity Hi Hi
(Disabled)
Proximity Hi
(Disabled)
Proximity Lo
(Disabled)

The Travel is within the


configured band of the
configured center point.

Proximity Lo Lo
(Disabled)
Cycle Counter
(Travel History)
(Maintenance)

Cycle Counter
(Disabled)

The number of travel reversals


has exceeded the configured
limit.
-Continued-

280

With other valves, the user can refine the


settings with ValveLink software Dynamic
Error Band and Step Response Tests. Set
the related parameters as follows:
Tvl Dev Alert Pointset equal times 2 the
Maximum Dynamic Error, minimum 3%
Tvl Dev DBset equal to the Dynamic
Error Band, minimum 2%
Tvl Dev Timeset equal to the T98 time
for a Step Test from 0 to 100% Travel,
minimum 10 seconds.

The Travel Deviation has


exceeded the Travel Deviation
Alert Point by more than the
Travel Deviation Time.

Instruction Manual

PlantWeb Alerts

D103412X012

August 2012

Table C2. Setting PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category)

Alert Condition
(Default)

Related Parameters
(Default)

What the Alert is Detecting

Guidelines for Setting

Travel Accumulator
(Travel History)
(Maintenance)

Travel Accumulator
(Disabled)

The accumulated travel has


exceeded the configured limit.

Alert Point (1,000,000)


Deadband (1%)

Packing Bonnets enable the alert in the


Maintenance Alert Category. When
packing leaks are discovered, set the
Travel Accumulator alert to 90% of the
current Travel Accumulator Value,
triggering an alert prior to anticipated
leak.

Performance Critical
(Performance)
(Failed)

Performance Critical
(Enabled)

Critical performance issues


based on continuous PD tests
internal to the instrument.

None

Use default setting

Performance Reduced
(Performance)
(Maintenance)

Performance
Reduced
(Enabled)

Reduced performance issues


based on continuous PD tests
internal to the instrument.

None

Use default setting

Performance Information
(Performance)
(Advisory)

Performance
Information
(Enabled)

Performance Information
based on continuous PD tests
internal to the instrument.

None

Use default setting

Table C3. Using PlantWeb Alerts


PlantWeb Alert
(Group)
(Default Alert Category

Alert Condition
(Default)

What the Alert is Detecting

Effect on Valve/Instrument

Recommended
Action

Help

Drive Current
(Electronics)
(Failed)

Drive Current
(Enabled)

The difference between the


expected Drive Current and the
actual Drive Current has
exceeded the Drive Current
Alert Time.

If configured for Self Test


Shutdown, then the transducer
Actual mode is placed Out of
Service until the problem is
fixed. Out of Service results in
the instrument output
pressure(s) and actuator
position being at the Zero
Power Condition.

Check I/P module

The instrument has


detected that the
difference between the
expected Drive Current
and the actual Drive
Current is greater than
the configured limit
1) Replace the I/P
module
2) Calibrate the device.
If the problem persists,
replace the printed
wiring board (PWB)
assembly.

Drive Signal
(Electronics)
(Maintenance)

Drive Signal
(Enabled)

If one of the following


conditions exist:

None - Indicates reduced


performance.

Check instrument
pneumatics

The instrument I/P


drive signal necessary
to generate the
pressure output from
the instrument is not
within the expected
range. Potential causes
include I/P filter
plugged, instrument
pneumatic relay failure,
low supply pressure, air
leaks, or valve sticking.
Test the control valve
assembly for proper
operation. ValveLink
diagnostics can be used
for this purpose.

Where Zero Power Condition is


defined as closed:
Drive Signal < 10% and
Calibrated Travel > 3%
Drive Signal > 90% and
Calibrated Travel < 97%
Where Zero Power Condition is
defined as open:
Drive Signal < 10% and
Calibrated Travel < 97%
Drive Signal > 90% and
Calibrated Travel > 3%
-Continued-

281

Instruction Manual

PlantWeb Alerts
August 2012

D103412X012

Table C3. Using PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category
Processor Impaired
(Electronics)
(Maintenance)

Output Block Timeout


(Configuration)
(Maintenance

Alert Condition
(Default)

What the Alert is Detecting

Effect on Valve/Instrument

Recommended
Action

Program Memory
(Enabled)

A pending Flash or NVM failure


is present.

Replace PWB
assembly

Static Memory
(Enabled)

A failure of the FRAM memory


where static parameters are
stored.

An error has been


detected in the printed
wiring board (PWB)
assembly. Replace the
PWB assembly.

Processor
(Enabled)

A failure of the main Processor.

I/O Processor
(Enabled)

A failure of the I/O Processor.

If configured for Self Test


Shutdown, then the transducer
Actual mode is placed Out of
Service until the problem is
fixed. Out of Service results in
the instrument output
pressure(s) and actuator
position being at the Zero
Power Condition.

Output Block
Timeout
(Disabled)

If the AO or DO block has not


executed for longer than the
configured timeout, this alert is
detected.

If configured for Self Test


Shutdown, then the transducer
Actual mode is placed Out of
Service until the problem is
fixed. Out of Service results in
the instrument output
pressure(s) and actuator
position being at the Zero
Power Condition.

Check Output
Block

The function block


providing the setpoint
for the valve position
(AO or DO function
block) has not executed
within the user
configured time limit. If
configured for Self Test
Shutdown, the
transducer Actual
mode is set to Out of
Service.

Help

1) Download the
control schedule from
the host configuration
device.
2) Make sure the Time
Out Alert Point is
greater than the block
execution schedule.
This alert should only
be utilized in very
critical loops where
execution time is
critical.
Blocks Set to Default
(Configuration)
(Failed)

Blocks Set to
Default
(Enabled)

If the resource block has


undergone Restart with
Defaults.

The transducer Actual mode


is placed Out of Service when
the defaults are applied. Out of
service results in the actuator
being at the Zero Power
Condition.

Download device
configuration

When restoring power


to the device, the
configuration
parameters could not
be recalled from
nonvolatile memory.
When the instrument
detects this condition,
the transducer Actual
mode is set to Out of
Service.
To correct this
situation, download the
configuration to the
device and set the
Target Mode of the
Resource block.

Shutdown Alert
(Configuration)
(Failed)

N/A

A user configured Self Test


Shutdown condition has taken
the instrument to OOS.

None - Indicates why the


instrument remains OOS.

-Continued-

282

Same as the
configured Self
Test Shutdown.

The instrument Actual


mode remains OOS due
to a configured Self
Test Shutdown, where
Manual Recovery was
specified, even though
the condition may have
cleared. Check
Recommended Action
for the indicated
condition.

Instruction Manual

PlantWeb Alerts

D103412X012

August 2012

Table C3. Using PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category
Travel Sensor
(Sensors)
(Failed)

Alert Condition
(Default)
Travel Sensor
(Enabled)

What the Alert is Detecting

Effect on Valve/Instrument

The travel feedback is within


acceptable limits.

If configured for Self Test


Shutdown, then the transducer
Actual mode is placed Out of
Service until the problem is
fixed. Out of service results in
the actuator being at the Zero
Power Condition.

Recommended
Action
Check mounting
and linkage

Help
Travel feedback value is
outside expected
limits. If this problem
occurs during
instrument setup, the
most likely cause is
faulty mounting or
improper adjustment
of the travel sensor. If
this problem occurs
during normal
operation, the most
likely cause is a failure
of the travel sensor.
To correct,
1) Insure proper
mounting and linkage
adjustment.
2) Inspect and test
travel sensor
3) Toggle the
transducer target
mode.
If the problem persists,
replace the printed
wiring board (PWB)
assembly.

Output Press Sensor


(Sensors)
(Maintenance)

Port A Pressure
Sensor (Enabled)

The pressure sensor reading is


outside the functional range of
the sensor.

Port B Pressure
Sensor (Enabled)
Supply Press Sensor
(Sensors)
(Advisory)

Supply Press
Sensor (Enabled)

If configured for Self Test


Shutdown, then the transducer
Actual mode is placed Out of
Service until the problem is
fixed. Out of service results in
the actuator being at the No
Power condition.

Confirm proper
air supply

If it is verified that the


air supply is ok, replace
the printed wiring
board (PWB) assembly.

None - Indicates a possible


hardware problem that would
degrade diagnostic capability.
The pressure sensor reading is
outside the functional range of
the sensor.

None - Indicates a possible


hardware problem that would
degrade diagnostic capability.

The pressure sensor


onboard the device
has failed. This may be
due to excessive supply
pressure or
contaminated air.

Confirm proper
air supply

The pressure sensor


onboard the device
has failed. This may be
due to excessive supply
pressure or
contaminated air.
If it is verified that the
air supply is ok, replace
the printed wiring
board (PWB) assembly.

Temperature Sensor
(Sensors)
(Advisory)

Temperature
Sensor (Enabled)

The temperature sensor


reading is outside the
functional range of the sensor.

None - Indicates a possible


hardware problem that would
degrade instrument calibration
and diagnostic capability.

Replace PWB
assembly.

The temperature
sensor onboard the
device has failed or the
unit has been exposed
to an temperature
extreme beyond the
recommended limits.

-Continued-

283

Instruction Manual

PlantWeb Alerts
August 2012

D103412X012

Table C3. Using PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category

Alert Condition
(Default)

What the Alert is Detecting

Effect on Valve/Instrument

Recommended
Action

Help

Pressure Fallback
(Sensors)
(Maintenance)

Pressure Fallback
(Enabled)

A travel sensor failure or large


travel deviation has resulted in
fallback to pressure control.

None - Indicates a reduced


performance condition.

Check instrument
feedback linkage
and travel sensor.

The instrument has


detected that the travel
sensor is outside its
normal range of
operation or that a
gross deviation exists
between set point and
actual travel. It has
switched to Pressure
Control and is no
longer using the travel
sensor to position the
valve.

Supply Pressure
(Environment)
(Maintenance)

Supply Press High


(Enabled)

The supply pressure has


exceeded the Supply Pressure
Hi Alert Point.

None - Indicates a condition


that could cause damage to
the instrument or actuator.

Confirm proper
air supply.

The Supply Pressure


sensor onboard has
detected an abnormally
high supply pressure.
Verify the proper
supply pressure and
that the alert is
properly set.

Supply Press Low


(Enabled)

The supply pressure is lower


than the Supply Pressure Lo
Alert Point.

None - Indicates a condition


that could reduce performance
or prevent the valve from
shutting tightly.

Temperature High
(Enabled)

The temperature is greater


than the Temperature Hi Alert
Point.

None - Indicates a condition


that could shorten service life
or lead to reduced
performance.

Temperature Low
(Enabled)

The temperature is lower than


the Temperature Lo Alert
Point.

Temperature Limit
(Environment)
(Advisory)

-Continued-

284

The Supply Pressure


sensor onboard has
detected an abnormally
low supply pressure.
Verify the proper
supply pressure and
that the alert is
properly set.
Check instrument
environment.

The instrument
temperature has
exceeded the user
configured high
temperature limit.
Operation of the
instrument above the
rated temperature may
degrade instrument
components. This may
affect instrument
performance and/or
reduce the life of the
instrument.
The instrument
temperature has
dropped below the user
configured low
temperature limit.
Operation of the
instrument below the
rated temperature may
degrade instrument
components. This may
affect instrument
performance and/or
reduce the life of the
instrument.

Instruction Manual

PlantWeb Alerts

D103412X012

August 2012

Table C3. Using PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category
Travel Deviation
(Travel)
(Maintenance)

Alert Condition
(Default)
Travel Deviation
(Enabled)

What the Alert is Detecting

Effect on Valve/Instrument

The Travel Deviation has


exceeded the Travel Deviation
Alert Point by more than the
Travel Deviation Time.

None - Indicates a reduced


performance condition.

Recommended
Action
Check valve
friction, supply
air, instrument
tuning

Help
The valve travel is not
following setpoint.
Check operation of the
valve and instrument.
Possible items include;
sticking valve, low
supply pressure,
broken feedback
linkage, instrument
pneumatic
components, actuator,
instrument tubing,
poor instrument
tuning, etc.
Test the control valve
assembly for proper
operation. ValveLink
software diagnostics
can be used for this
purpose.

Travel Limit
(Travel)
(Advisory)

Travel Limit Hi Hi
(Disabled)

The Travel has exceeded the


Travel Limit Hi Hi Alert Point.

None

Check process
loop

Travel Limit Lo Lo
(Disabled)

The Travel is lower than the


Travel Limit Lo Lo Alert Point.

None

Check process
loop

N/A
(Travel)
(N/A)

Travel Limit Hi
(Disabled)

The Travel has exceeded the


Travel Limit Hi Alert Point.

None

Check process
loop

The actual valve


position has exceeded
the configurable travel
limit (in %).

Travel Limit Lo
(Disabled)

The Travel is lower than the


Travel Limit Lo Alert Point.

None

Check process
loop

The actual valve


position has exceeded
the configurable travel
limit (in %).

Travel Open
(Disabled)

The Travel is greater than the


Open Alert Point

None

Check process
loop

The actual valve


position is near the full
open position.

Travel Closed
(Disabled)

The Travel is greater than the


Closed Alert Point

None

Check process
loop

The actual valve


position is near the full
closed position.

Proximity Hi Hi
(Disabled)

The Travel is within the


configured band of the
configured center point.

None

Check process
loop

The actual valve


position is near the
configured center
point.

N/A
(Proximity)
(N/A)

Proximity Hi
(Disabled)

None

Proximity Lo
(Disabled)

None

Proximity Lo Lo
(Disabled)

None

The actual valve


position has exceeded
the configurable travel
limit (in %).

Cycle Counter
(Travel History)
(Maintenance)

Cycle Counter
(Disabled)

The number of travel reversals


has exceeded the configured
limit.

None

Perform periodic
maintenance

The cycle count limit


has been exceeded.
Perform periodic
maintenance. Check
packing, linkages,
diaphragms, seals, etc.

Travel Accumulator
(Travel History)
(Maintenance)

Travel
Accumulator
(Disabled)

The accumulated travel has


exceeded the configured limit.

None

Perform periodic
maintenance

The travel accumulator


limit has been
exceeded. Perform
periodic maintenance.
Check packing,
linkages, diaphragms,
seals, etc.

-Continued-

285

Instruction Manual

PlantWeb Alerts
August 2012

D103412X012

Table C3. Using PlantWeb Alerts (Continued)


PlantWeb Alert
(Group)
(Default Alert Category

Alert Condition
(Default)

What the Alert is Detecting

Effect on Valve/Instrument

Recommended
Action

Help

Performance Critical
(Performance)
(Failed)

Performance
Critical
(Enabled)

Critical performance issues


based on continuous PD tests
internal to the instrument.

None - Indicates control has


been lost or severely reduced.

Check I/P, Relay,


Valve, Actuator
or Ext. Tubing as
indicated.

Onboard diagnostics
have detected a critical
performance issue that
may result in loss of
control or severe
reduction in control
performance. Check or
replace the component
indicated in the
possible cause detail.

Performance Reduced
(Performance)
(Maintenance

Performance
Reduced (Enabled)

Reduced performance issues


based on continuous PD tests
internal to the instrument.

None - Indicates reduced


performance.

Check I/P, Relay,


Valve, Actuator
or Ext. Tubing as
indicated.

Onboard diagnostics
have detected a
performance issue that
has reduced control
performance. Check or
replace the component
indicated in the
possible cause detail.

Performance Information
(Performance)
(Advisory)

Performance
Information
(Enabled)

Performance Information
based on continuous PD tests
internal to the instrument.

None - Indicates information


that may pertain to control
performance.

No action
required.

Onboard diagnostics
have detected an
abnormal performance
condition. No
immediate action
required.

Table C4. Output Block PV Status


FEATURE_SEL
PW Alarms Set PV Status

Enabled

Not Enabled

Transducer Mode,
Actual

Active PlantWeb
Alarms

AO / DO
PV Status

AO / DO PV
Substatus

AO/DO PV Limit Substatus(1)

OOS

Bad

Device Failure

Constant

Man

Bad

Nonspecific

Constant

Auto

Fail

Uncertain

Subnormal

See table C5

Auto

Maint, no Fail

Uncertain

Nonspecific

See table C5

Auto

Advisory, no Fail, no Maint

Good

Advisory

See table C5

Auto

None

Good

NonSpecific

See table C5

OOS

Bad

Device Failure

Constant

Man

Bad

NonSpecific

Constant

Auto

Fail

Good

NonSpecific

See table C5

Auto

Maint, no Fail

Good

NonSpecific

See table C5

Auto

Advisory, no Fail, no Maint

Good

NonSpecific

See table C5

Auto

None

Good

NonSpecific

See table C5

NOTES:
X = No Effect
1. PV limit substatus reflects only READBACK limit substatus. SP limit substatus reflects only out block rate limits.

Table C5. Limit Sub Status


Out Block

Transducer Mode

In Cutoff Region

Rate Limited

Limit SubStatus

AO, DO

OOS

Constant

AO, DO

MAN

Constant

AO

AUTO

High

High Limited

AO

AUTO

Low

Low Limited

AO

AUTO

High

High Limited

AO

AUTO

Low

Low Limited

AO

AUTO

None

None

Not Limited

DO

AUTO

High

High Limited

DO

AUTO

Low

Low Limited

DO

AUTO

None

Not Limited

NOTE: X = No Effect

286

Instruction Manual

FOUNDATION fieldbus Communication

D103412X012

August 2012

Appendix D FOUNDATION fieldbus Communication9DD


DVC6200f digital valve controllers use the FOUNDATION fieldbus to communicate with other fieldbus instruments and
the control system. Fieldbus is an all digital, serial, twoway communication system which interconnects field
equipment such as transmitters, digital valve controllers, and process controllers. Fieldbus is a localarea network
(LAN) for instruments used in both process and manufacturing automation with builtin capability to distribute the
control application across the network.

Function Block Overview


A fieldbus system is a distributed system composed of field devices and control and monitoring equipment integrated
into the physical environment of a plant or factory. Fieldbus devices work together to provide I/O and control for
automated processes and operations. The Fieldbus Foundation provides a framework for describing these systems as a
collection of physical devices interconnected by a fieldbus network. One of the ways that the physical devices are used
is to perform their portion of the total system operation by implementing one or more function blocks.

Function Blocks
Function blocks within the fieldbus device perform the various functions required for process control. Because each
system is different, the mix and configuration of functions are different. Therefore, the Fieldbus Foundation has
designed a range of function blocks, each addressing a different need: Analog Input Block (AI), Multiple Analog Input
(MAI), Discrete Input Block (DI), Manual Loader Block (ML), Bias/Gain Station Block (BG), Control Selector Block (CS), P,
PD Controller Block (PD), PID, PI, I Controller Block (PID), Ratio Station Block (RA), Analog Output Block (AO) and
Discrete Output Block (DO).
Function blocks perform process control functions, such as analog input (AI) and analog output (AO) functions as well
as proportionalintegralderivative (PID) functions. The standard function blocks provide a common structure for
defining function block inputs, outputs, control parameters, events, alarms, and modes, and combining them into a
process that can be implemented within a single device or over the fieldbus network. This simplifies the identification
of characteristics that are common to function blocks.
The Fieldbus Foundation has established the function blocks by defining a set of parameters used in all function blocks
called universal parameters. The Fieldbus Foundation has also defined a standard set of function block classes, such as
input, output, control, and calculation blocks. Each of these classes have a set of parameters established for it.
Additionally, they have published definitions for transducer blocks commonly used with standard function blocks.
Examples include temperature, pressure, level, and flow transducer blocks.
Fieldbus Foundation specifications and definitions allow vendors to add their own, extended parameters, as well as
their own algorithms. This approach permits extending function block definitions as new requirements are discovered
and as technology advances.
Each block has a tag name. Service personnel need only know the tag name of the block to access or change the
appropriate block parameters.
Input events may affect the operation of the algorithm. An execution control function regulates the receipt of input
events and the generation of output events during execution of the algorithm. Upon completion of the algorithm, the
data internal to the block is saved for use in the next execution, and the output data is snapped, releasing it for use by
other function blocks.
Once the inputs are snapped, the algorithm operates on them, generating outputs as it progresses. Algorithm
executions are controlled through the setting of internal parameters. Internal parameters do not appear as normal
input and output parameters. However, they may be accessed and modified remotely, as specified by the function
block.

287

Instruction Manual

FOUNDATION fieldbus Communication


August 2012

D103412X012

Figure D1 illustrates the internal structure of a function block. When execution begins, input parameter values from
other blocks are snappedin by the block. The input snap process ensures that these values do not change during the
block execution. New values received for these parameters do not affect the snapped values and will not be used by
the function block during the current execution.
Function blocks are also capable of performing shortterm data collection and storage for reviewing their behavior.

InstrumentSpecific Blocks
In addition to function blocks, fieldbus devices contain two other block types to support the function blocks. These are
the resource block and the transducer block. The resource block contains the hardware specific characteristics
associated with a device. Transducer blocks couple the function blocks to local input/output functions.
Figure D1. Function Block Internal Structure

Input Parameter
Linkages

Input
Events

Execution Control

Input
Snap

Processing
Algorithm

status

Output
Events

Output
Snap

Output
Parameter
Linkages

status

B2711

Resource Blocks
The resource block contains hardware specific characteristics associated with the device; it has no input or output
parameters. The algorithm within a resource block monitors and controls the general operation of the physical device
hardware. The execution of this algorithm is dependent on the characteristics of the physical device, as defined by the
manufacturer. As a result of this activity, the algorithm may cause the generation of events. There is only one resource
block defined for a device. For example, placing the resource block in Out of Service mode stops all function block
execution, by setting their modes to Out of Service as well. The actual mode of the function blocks is changed to Out
of Service, but the function block target modes will not change. Placing the resource block in the Out of Service mode
does not affect the mode of the transducer block.

Transducer Blocks
Transducer blocks connect function blocks to local input/output functions. They read sensor hardware and write to
effector (actuator) hardware. This permits the transducer block to execute as frequently as necessary to obtain good
data from sensors and ensure proper writes to the actuator without burdening the function blocks that use the data.
The transducer block also isolates the function block from the specific characteristics of the physical I/O.

288

Instruction Manual

FOUNDATION fieldbus Communication

D103412X012

August 2012

Block Modes
All blocks have modes. The mode determines the source of the set point, the destination of the output, how the block
executes, and the relationship between setpoint and output. The block mode is determined by the Block Mode
parameter. It is a structured parameter composed of the attributes actual, target, permitted, and normal. The
following defines each of the attributes.
Target modeThe Target mode is the mode requested by the user or host system. Only one mode is allowed to be
set and it must be a permitted mode as defined by the permitted attribute of the mode parameter.
Actual modeThis is the current mode of the block. The actual mode may differ from the target mode due to
operating conditions of the block.
Permitted modeThe permitted mode defines the modes allowed for the block. This is set by the user or host
system but is restricted by the instrument to modes supported by the instrument for the particular block. Any
change request to the Target or Normal attribute is checked against the permitted attribute to ensure the
requested mode is permitted.
When setting the Permitted mode, there is no check against any of the other attributes (Normal or Target modes).
Therefore, the normal or target mode attributes may have a value that is not permitted because the permitted
attribute was modified after the Normal or Target mode was set. This will have no effect on the instrument until the
user attempts to modify the Target or Normal mode. At this time these attributes are tested against the Permitted
modes, thus the user cannot change the Normal or Target modes to what was formerly permitted.
Normal modeThe normal mode is the mode the block should be in during normal operating conditions. The
normal mode is set by the user or host system and can only be set to a permitted mode (see permitted mode). The
user or host system can compare the actual mode to the normal mode and, based on the results, determine if the
block is operating normally.
Table D1 lists the modes supported by each block contained in the digital valve controller.
Table D1. DVC6200f Block Modes
Block
Resource
Transducer

Supported Mode Values


Auto and OOS
Auto, Manual, and OOS

AO

RCas, Cas, Auto, Man, LO(1), IMan(1), and OOS

PID

ROut, RCas, Cas, Auto, Man, LO(1), IMan(1), and OOS

ISEL

Auto, Man and OOS

OS

IMan(1), Auto, Cas and OOS

AI

Man, Auto, and OOS

MAI

Man, Auto, and OOS

DO

RCas, Cas, Auto, Man, LO(1), IMan(1), and OOS

DI

Auto, Man, and OOS

1.This mode cannot be specified as a target mode.

Changing the block mode requires accessing the Block Mode parameter. For information on using the host system to
change the block mode via this parameter, see the appropriate host documentation.

289

Instruction Manual

FOUNDATION fieldbus Communication


August 2012

D103412X012

Note
A downstream block changing to Out of Service impacts the mode of the upstream block. Refer to the block hierarchy in
figure D2.

Figure D2. Digital Valve Controller Block Hierarchy Example

RESOURCE BLOCK

PID BLOCK

ANALOG OUTPUT
(AO) BLOCK

TRANSDUCER
BLOCK

NOTES:
1.CHANGING THE RESOURCE BLOCK TO OUT OF SERVICE CHANGES ALL FUNCTION BLOCKS
TO OUT OF SERVICE, BUT DOES NOT AFFECT THE TRANSDUCER BLOCK.
2.CHANGING A DOWNSTREAM BLOCK TO OUT OF SERVICE AFFECTS THE UP STREAM BLOCK.
FOR EXAMPLE: WHEN THE TRANSDUCER BLOCK IS OUT OF SERVICE, THE AO BLOCK MODE
WILL CHANGE TO IMAN (INITIALIZE MANUAL).

Note
There is no mode associated with the FOUNDATION fieldbus Loop. Mode is dependent on the blocks within the Loop.

Explanation of Modes
Out of Service (OOS)The functions performed by the block are not executed. If the block has any outputs, these
typically do not update and the status of any values passed to downstream blocks will be BAD. To make changes to
some of the parameters in a block requires that the block be Out of Service.
Initialization Manual (IMan)Only the AO, DO, OS and PID blocks support this mode. When one of these blocks
detects a loss of a correct path to the downstream block (such as when the downstream block is in the OOS, Man, or
LO mode), it enters the IMan mode. For example, when the transducer block enters the OOS mode, the AO block
enters the IMan mode.
Local Override (LO)Only the AO, DO, and PID blocks support this mode. If the PID block enters the LO mode, the
block output follows the tracking value (TRK_VAL), if external tracking is enabled by TRK_IN_D. In the AO and DO
block, the block enters LO mode when the block detects that fault state is active. In this case, the output is determined
by the selection for I/O_OPTS.
Manual (Man)If the data status of a function block's input is bad or its target mode is Man, the block enters the
manual mode. In this mode, the function block does not update its OUT value. If the target is Man, the user may write
a desired value to the output.
Automatic (Auto)The block performs the specified calculations based on the local set point and outputs the result,
independently without interfacing with another block. The user can write to the set point of a block in this mode. Any
block outputs continue to update.
Cascade (Cas)The block performs the specified calculations based on the set point from another block via the
cascade input parameter and outputs the result. Any block outputs continue to update.

290

Instruction Manual

FOUNDATION fieldbus Communication

D103412X012

August 2012

Remote Output (ROut)The block outputs are set to the value of the remote output parameter that is written by a
host computer or others. To prevent a sudden change in output, the block's calculations are initialized when a change
in mode occurs.
Remote Cascade (RCas)The block performs the specified calculations based on a set point from a host computer or
others via the remote cascade input and outputs the result. If the block has any outputs, these continue to update.

Examples of Modes for Various Operational Statuses


Table D2 shows examples of block mode combinations in a digital valve controller (however it does not show all
combinations). When a block changes mode or the data status signal changes for some reason, the other blocks
connected to that block identify the change by detecting the change in status of an input signal, and change their
modes too. For example, when the data status of BKCAL_IN in a PID block changes to bad, the PID block automatically
changes its mode to Iman to initialize the control of its downstream block.
Table D2. Examples of Block Mode Combinations and Operational statuses for an Instrument with Standard Control
Operational Status

Blocks
TB(1)

PID

AO

Initial Setup and calibration

---

OOS

OOS

Modification of some transducer block parameters

---

IMan

Manual

Constant valve position control


PID Singleloop control
PID Cascadeloop control

---

Auto

Auto

Auto

Cas

Auto

Primary PID, Auto


Secondary PID, Cas

Cas

Auto

1.TB=Transducer Block

The respective modes to which each block should enter upon occurrence of a communication error and at a restart,
and the handling of signals in each mode may be defined in the block's option parameters such as IO_OPTS and
STATUS_OPTS. For details, see the detailed descriptions of each function block.

Device Descriptions
Device Descriptions are specified definitions that are associated with blocks. Device descriptions provide for the
definition and description of blocks and their parameters.
Device descriptions may also include a set of processing routines called Methods. Methods provide a procedure for
accessing and manipulating a series of parameters within a device, such as for setup and calibration. Methods are used
for a variety of functions including automatic calibration, setting protection and setting up the instrument. These
Methods are a predetermined sequence of steps for information required to setup, calibrate, and perform other
functions on the instrument.

Transducer Block Status and Limit Propagation


Every FOUNDATION fieldbus parameter has a value and a status. The status attribute is divided into three components:
Quality, Quality substatus, and a Limit. The Quality can be Good (Cascade), Good (NonCascade), Uncertain, and Bad.
Each quality can have a substatus as shown in table D3. Each status attribute also has four possible limit states: Not
limited, Low limited, High limited, and Constant. Refer to the Fieldbus Foundation specifications for a more detailed
description. The following describes how the transducer block passes status information to the AO block. For
information on status handling by the function blocks within the digital valve controller, refer to the Detailed Setup
section.

291

Instruction Manual

FOUNDATION fieldbus Communication


August 2012

D103412X012

Table D3. Status Attribute Quality and Substatus Components


Quality

Substatus

Good (NC)

Nonspecific

Good (NC)

Active Block Alarm

Good (NC)

Active Advisory Alarm

Good (NC)

Active Critical Alarm

Good (NC)

Unack Block Alarm

Good (NC)

Unack Advisory Alarm

Good (NC)

Unack Critical Alarm

Uncertain

Nonspecific

Uncertain

Last Usable Value

Uncertain

Substitute/Manual Entry

Uncertain

Initial Value

Uncertain

Sensor Conversion not Accurate

Uncertain

Engineering Unit Range Violation

Uncertain

Subnormal

Good (C)

Nonspecific

Good (C)

Initialization Acknowledge

Good (C)

Initialization Request

Good (C)

Not Invited

Good (C)

Not Selected

Good (C)

Local Override

Good (C)

Fault State Active

Good (C)

Initiate Fault State

Bad

Nonspecific

Bad

Configuration Error

Bad

Not Connected

Bad

Device Failure

Bad

Sensor Failure

Bad

No Comm, with LUV

Bad

No Comm, no LUV

Bad
(NC)=(Noncascade)

Out of Service
(C)= (Cascade)

Status Propagation
The transducer block accepts the output from the AO block or DO block if the output parameter status is Good
(Noncascade) or Good (Cascade). When the AO or DO block is Out of Service the output parameter status is Bad. In
this case, the transducer block holds the last value.
If the transducer block actual mode is Out of Service, the AO block READBACK parameter status is Bad-Out of Service.
This could be caused by a Failed Alert. If a Failed Alert is active, the block error parameter (parameter name
BLOCK_ERR) for the Resource block will indicate Device Needs Maintenance Now. For more information on the
Resource and Transducer block error indications, refer to the Viewing Device Information section of this manual.
If the transducer block is functioning correctly the AO block READBACK parameter status is Good
(Noncascade)-Nonspecific. If a Maintenance or Advisory alert is active the substatus will reflect a Unacknowledged or
Active advisory alert. When a Maintenance or Advisory alert is active, the block error for the resource block indicates
Device Needs Maintenance Soon.

Limit Propagation
The following describes limit propagation:

292

Instruction Manual

FOUNDATION fieldbus Communication

D103412X012

August 2012

AO Block
If the valve position is below the low cutoff value, the AO block READBACK status limit is LOW_LIMITED.
If the valve position is above the high cutoff value, the AO block READBACK status limit is HIGH_LIMITED.
If the transducer block actual mode is Auto and the above conditions are not true, the AO block READBACK status
limit is NOT_LIMITED.
If the transducer block actual mode is Out of Service, the AO block READBACK status limit is CONSTANT.
DO Block
If the transducer block actual mode is Auto, the DO block READBACK_D status is NOT_LIMITED.
If the transducer block actual mode is Out of Service, the DO block READBACK_D status is CONSTANT.
The control strategy should be configured to monitor the Analog Output block status and take action where
appropriate when the status is no longer Good.

Network Communication
Figure D3 illustrates a simple fieldbus network consisting of a single segment.
Figure D3. Simple SingleLink Fieldbus Network

LAS

Fieldbus Segment

LINK MASTER

BASIC DEVICES
LAS = Link Active Scheduler
B27121

Device Addressing
Fieldbus uses addresses between 0 and 255. Addresses 0 through 15 are typically reserved for group addressing and
for use by the data link layer. If there are two or more devices with the same address, the first device to start will use its
programmed address. Each of the other devices will be given one of four temporary addresses between 248 and 251. If
a temporary address is not available, the device will be unavailable until a temporary address becomes available.
Commission devices use addresses 20-35, and standby devices use addresses 232247.

Link Active Scheduler (LAS)


There is only one active Link Active Scheduler (LAS) for the entire fieldbus control system. The digital valve controller
includes an LAS. The Link Active Scheduler operates as the bus arbiter for the link, and

293

FOUNDATION fieldbus Communication

Instruction Manual

August 2012

D103412X012

recognizes and adds new devices to the link.


removes nonresponsive devices from the link.
distributes Data Link (DL) and Link Scheduling (LS) time on the link. Data Link Time is a networkwide
time periodically distributed by the LAS to synchronize all device clocks on the bus. Link Scheduling time is a
linkspecific time represented as an offset from Data Link Time. It is used to indicate when the LAS on each link begins
and repeats its schedule. It is used by system management to synchronize function block execution with the data
transfers scheduled by the LAS.
polls devices for process loop data at scheduled transmission times.
distributes a prioritydriven token to devices between scheduled transmissions.
The DVC6200f can be designated to act as the backup Link Active Scheduler (LAS) in the event that the LAS is
disconnected from the segment. As the backup LAS, the DVC6200f will take over the management of
communications until the host is restored. The host system may provide a configuration tool specifically designed to
designate a particular device as a backup LAS. Otherwise, this can be configured manually as follows:
1. Access the Management Information Base (MIB) for the DVC6200f.
2. To activate the LAS capability, write 0x02 to the BOOT_OPERAT_FUNCTIONAL_CLASS object (Index 605). To
deactivate, write 0x01.
Restart the processor.
Only one device can communicate at a time. Permission to communicate on the bus is controlled by a centralized
token passed between devices by the LAS. Only the device with the token can communicate. The LAS maintains a list
of all devices are a member of the bus. This list is called the Live List.
Two types of tokens are used by the LAS. A timecritical token, compel data (CD), is sent by the LAS according to a
schedule. A nontime critical token, pass token (PT), is sent by the LAS to each device in numerical order according to
address.

Device Communication
Scheduled Transfers
Information is transferred between devices over the fieldbus using three different types of communication:
Publisher/Subscriber: This type of communication is used to transfer critical process loop data, such as the process
variable. The data producers (publishers) post the data in a buffer that is transmitted to the subscriber (S), when the
publisher is issued the Compel Data (CD) message from the LAS. The buffer contains only one copy of the data. New
data completely overwrites previous data. Updates to published data are transferred simultaneously to all
subscribers in a single broadcast. Transfers of this type are scheduled on a precisely periodic basis.
Figure D4 diagrams the method of scheduled data transfer. Scheduled data transfers are typically used for the regular
cyclic transfer of process loop data between devices on the fieldbus. Scheduled transfers use publisher/subscriber type
of reporting for data transfer. The Link Active Scheduler maintains a list of transmit times for all publishers in all devices
that need to be cyclically transmitted. When it is time for a device to publish data, the LAS issues a Compel Data (CD)
message to the device. Upon receipt of the CD, the device broadcasts or publishes the data to all devices on the
fieldbus. Any device that is configured to receive the data is called a subscriber.

294

Instruction Manual

FOUNDATION fieldbus Communication

D103412X012

August 2012

Figure D4. Scheduled Data Transfer


Host System
LAS

Schedule
X
Y
Z

DT(A )

CD (X, A)

LAS=Link Active Scheduler


P=Publisher
S=Subscriber
CD=Compel Data
DT=Data Transfer Packet

Device X

Device Y

Device Z

B27131

Unscheduled Transfers
Figure D5 diagrams an unscheduled transfer. Unscheduled transfers are used for things like userinitiated changes,
including set point changes, mode changes, tuning changes, and upload/download. Unscheduled transfers use either
report distribution or client/server type of reporting for transferring data.
Figure D5. Unscheduled Data Transfer
Host System
LAS
PT (Z)
Schedule
X
Y
Z

LAS=Link Active Scheduler


P=Publisher
S=Subscriber
PT=Pass Token
M=Message

Device X

M
S

Device Y

Device Z

B27141

All of the devices on the fieldbus are given a chance to send unscheduled messages between transmissions of
scheduled data. The LAS grants permission to a device to use the fieldbus by issuing a pass token (PT) message to the
device. When the device receives the PT, it is allowed to send messages until it has finished or until the maximum
token hold time has expired, whichever is the shorter time. The message may be sent to a single destination or to
multiple destinations.

295

Instruction Manual

FOUNDATION fieldbus Communication


August 2012

D103412X012

Report Distribution: This type of communication is used to broadcast and multicast event and trend reports.
Client/Server: This type of communication is used for request/ response exchanges between pairs of devices, such
as a set point change. Like Report Distribution reporting, the transfers are queued, unscheduled, and prioritized.
Queued means the messages are sent and received in the order submitted for transmission, according to their
priority, without overwriting previous messages.

Function Block Scheduling


Figure D6 shows an example of a link schedule. A single iteration of the linkwide schedule is called the macrocycle.
When the system is configured and the function blocks are linked, a master linkwide schedule is created for the LAS.
Each device maintains its portion of the linkwide schedule, known as the Function Block Schedule. The Function Block
Schedule indicates when the function blocks for the device are to be executed. The scheduled execution time for each
function block is represented as an offset from the beginning of the macrocycle start time.
Figure D6. Example Link Schedule Showing Scheduled and Unscheduled Communication
Start of Next Macrocycle
Macrocycle Start Time
Offset from macrocycle
start time = 0 for AI Execution
Device 1

Sequence Repeats

AI

AI
Offset from macrocycle
start time = 20 for AI
Communication

Scheduled
Communication

Unscheduled
Communication
Offset from macrocycle
start time = 30 for AI
Execution

Device 2

PID

AO

PID

AO

Offset from macrocycle


start time = 50 for AO
Communication

B27151

20

40

60

80

100

120

20

40

60

80

100

120

Macrocycle

To support synchronization of schedules, periodically Link Scheduling (LS) time is distributed. The beginning of the
macrocycle represents a common starting time for all Function Block schedules on a link and for the LAS linkwide
schedule. This permits function block executions and their corresponding data transfers to be synchronized in time.

Network Management
Information for setting up network communications, including Virtual Communication Relationships (VCRs), host
timer recommendations, and other network parameters, can be found in the capabilities file (.cff) available from the
website www.FIELDVUE.com or from the Fieldbus Foundation website.

296

Instruction Manual

Device Description Installation

D103412X012

August 2012

Appendix E Device Description Installation10EE


Overview
Several support files are required for the DVC6200f digital valve controller. They are:
Device Description (DD) filesThese files define the data interface to the digital valve controller (file extensions
.sym and .ffo).
Capabilities FileThese files allow a host to configure the control system offline (e.g., without having a device
physically attached to the host) (file extension .cff).
DeltaV Registry FileThis file is used by DeltaV to define the device interface (file extension .reg)
DeltaV fhx FileThis file is used by DeltaV to define the device and the data interface to the device (file extension
.fhx).
DeltaV Windows Resource FileThese files define the user interface for the device for DeltaV and include the
definitions for the transducer block interface and the resource block interface (file extension .dll).
The directory structure defined by the Fieldbus Foundation for device descriptions is as follows:
....\xxxxxx\yyyy\rrddcc.eee
where:
....\

is the path to the DD structure as implemented by the host system. This is typically defined as the base path
to the DD since access to the specific device DD is predefined from the base folder. For a DeltaV system, the
DDs are included with the support files and are located in a folder named amsdevices. For other hosts, the
Fieldbus Foundation defines a folder named release that is included with the CDROM, however, you do not
need to retain this folder name.

xxxxxx is the 6digit hexadecimal equivalent of the manufacturer's identification number as defined by the Fieldbus
Foundation. Fisher Controls' ID number is 5100 (or in the folder format 005100). This number is also stored in
the instrument Resource Block in the parameter Mfg ID (parameter name MANUFAC_ID).
yyyy

is the 4digit hexadecimal equivalent of the device type, as defined by the manufacturer. For example, the
device type for the DVC6200f digital valve controller is 4602. This number is stored in the instrument
Resource Block in the parameter Device Type (parameter name DEV_TYPE).

rr

is the 2digit hexadecimal equivalent of the device revision, as defined by the manufacturer. It is stored in the
instrument Resource Block in the parameter Device Revision (parameter name DEV_REV).

dd

is the 2digit hexadecimal equivalent of the device description (DD) revision that applies to the device, as
defined by the manufacturer. The host will always use the latest version of the DD that it finds for a particular
device revision. When part of the name of a capabilities file, this value is always the same as the value of the
DD_REV parameter stored in the Resource Block of the instrument. The value of the DD_REV parameter
represents the earliest version of the DD that is compatible with the device revision of the instrument.

cc

is a 2digit hexadecimal equivalent for the capabilities files (.cff) revision, as defined by the manufacturer. The
latest revision of the capabilities files, for a particular device revision, is the file with the largest value for this
number.

eee

is the file extension. At this time, five extensions exist for files, they are:
.symThis extension denotes a device description (DD) symbol file as defined by the Fieldbus
Foundation.

297

Device Description Installation

Instruction Manual

August 2012

D103412X012

.ffoThis extension denotes a complete, tokenized, device description for the instrument as defined by
the Fieldbus Foundation.
.cffThis extension denotes a capabilities file for the instrument as defined by the FOUNDATION Fieldbus
Common File Format specification.
.fhxThis extension denotes a DeltaV device definition file.
.dllThis extension denotes a windows resource file used by DeltaV.
.regThis extension denotes a DeltaV registry file.
.almThis extension denotes a DeltaV alarm file (DeltaV version 6 only).

Device Description and Methods


FOUNDATION fieldbus technology uses Device Descriptions (DD) and function blocks to achieve interoperability
between instruments and control systems or hosts from various manufacturers. The DD provides information to
describe the data interface to the device.
The following table describes the compatibility between the DVC6200f firmware revisions and DD revisions.
Device Description Compatibility
Firmware Revision
2.0

DD Compatibility
2 and 3

For fieldbus devices, in addition to providing parameter definitions and other information required by the control
system to communicate with the fieldbus device, the DD may also include methods. Methods can be used for a variety
of functions including automatic calibration, setting protection, setting up the instrument, etc. These methods are a
predetermined sequence of steps for information required to setup, calibrate, and perform other functions on the
instrument. How the method prompts the user, and how messages appear is determined by the host system. For
information on using methods on the host system see the appropriate host system documentation.
Table E1 contains the methods available in the DVC6200f, the block it is found in, and the page number where it is
described.

Installing DD on a DeltaV ProfessionalPLUS Workstation


The following is general information that may apply when installing the DD on a DeltaV system during the Add Device
Definition procedure. This procedure is accessed from the DeltaV/Library, as shown in figure E1. For complete
information, refer to the DeltaV documentation.
Figure E1. Add Device Definition

298

Instruction Manual

Device Description Installation

D103412X012

August 2012

Note
Before beginning the Add Device Definition procedure, it is recommended that the Add Device Utility be installed on DeltaV. This
may help prevent installation errors from occurring.

Table E1. Methods


Method

Block

Description Location

Auto Calibration

Transducer

page 214

Block Error Reporting

Transducer

page 86

Transducer

page 62

Resource

page 45

Display DD Version

Resource

page 301

Instrument Alerts

Transducer

page 69

Manual Travel Calibration

Transducer

page 214

Output A Sensor Calibration

Transducer

page 217

Output B Sensor Calibration

Transducer

page 217

PlantWeb Alerts

Transducer

page 69

Relay Adjust

Transducer

page 215

Reset Options

Resource

page 221

Device Setup

Transducer

page 40

Stabilize/Optimize

Transducer

page 64

Stroke Valve

Transducer

page 228

Supply Sensor Calibration

Transducer

page 216

Define Custom Characteristic

Transducer

page 68

Travel Deviation Fallback

Transducer

page 67

Outblock Selection

Transducer

page 69

PlantWeb Alerts Set PV Status

Transducer

page 86

Performance Tuner

Transducer

page 44, 64

Block Mode

Note
Be sure to select the correct DD for the DeltaV revision being used. The resource files are different for each revision of DeltaV.

Device descriptions furnished by Fisher contain only those files applicable to Fisher. All the files are located in the
manufacturer ID Folder (005100 for xxxxxx in directory structure above). A readme file is included at the top level.
Read this file for any additional information regarding DD installation.
Device descriptions furnished by the Fieldbus Foundation (on CDROM or diskette) contain the files for each
registered manufacturer and their associated device(s). It is placed on the media starting with the release folder,
which then contains a folder (xxxxxx) for each manufacturer as defined above. For Fisher this folder is 005100. A
readme file may be included at the top level. Read this file for any additional information regarding the DD.
For the DVC6200fThe device type parameter for this unit is 4602. This device includes the AO, PID, ISEL, OS, AI,
MAI, DO and DI function blocks. From DeltaV Explorer, select the amsdevices\005100\4602 folder (refer to
figure E2).

299

Device Description Installation


August 2012

Instruction Manual
D103412X012

Figure E2. amsdevices folder

The most recent device description for Fisher devices can be downloaded from the internet at www.FIELDVUE.com.
If you are downloading from the internet, the file on the website will be compressed (zipped) and must be
decompressed (unzipped) before proceeding. Refer to the website download and installation procedures for setting
up the DD on your system. Note the folder where the decompressed files are placed. This information will be
required later in the installation procedure.

Note
Record any warning/error messages from the message window in DeltaV Explorer so that it can be communicated to the DeltaV
Technical Support Group.

Installing DDs on Other Fieldbus Host Systems


The following is a generic procedure for installing the device descriptions on a host system. Refer to your host system
documentation for specific information. In general the following may apply:
Device descriptions furnished by Fisher contain only those files applicable to Fisher. All the files are located in the
manufacturer ID Folder (005100 for xxxxxx in directory structure above). A readme file is included at the top level.
Read this file for any additional information regarding DD installation.
Device descriptions furnished by the Fieldbus Foundation (on CDROM or diskette) contain the files for each
registered manufacturer and their associated device(s). It is placed on the media starting with the release folder,
which then contains a folder (xxxxxx) for each manufacturer as defined above. For Fisher this folder is 005100. A
readme file may be included at the top level. Read this file for any additional information regarding the DD.
For the DVC6200f Digital Valve ControllerThe device type parameter for this unit is 4602. This device includes the
AO, PID, ISEL, OS, AI, MAI, DO and DI function blocks. From Windows Explorer, select the release\005100\4602
folder.
The most recent device description for Fisher devices can be downloaded from the internet at www.fisher.com. If
you are downloading from the internet, the file on the website will be compressed (zipped) and must be
decompressed (unzipped) before proceeding. Refer to the website download and installation procedures for setting

300

Instruction Manual

Device Description Installation

D103412X012

August 2012

up the DD on your system. Note the folder where the decompressed files are placed. This information will be
required later in the installation procedure.

Note
This procedure will install the necessary Device Description files (*.ffo and *.sym), and Capabilities file (*.cff) for the device.

1. Locate or create the folder on the host system to contain all the DD and capabilities files.
If you are creating a folder, you can name this new folder whatever you would like and it can have any path you define.
For this installation procedure, this folder will be referred to as the base folder.
2. On the CDROM or in the website download files, locate the folder with the new support files. This folder is called
\RELEASE.
3. Open this folder and select the folder named 005100.
4. Copy the 005100 folder (and all its subfolders) from the CDROM or website download location to the base folder.
If this is an update (the folders already exist), the system informs you that the folders already exist and asks if they
should be replaced. Answer Yes or OK so the folders are properly updated.
5. The new support files are now installed. You may have to restart applications and drivers in order for the new files to
become active.
DD installation is complete. Consult the system documentation for commissioning new devices or updating existing
devices.

Displaying the Device Description Version


You can use the DD In Use method to display version information for the device descriptions installed on the system.
The DD in Use method is included with the device description (DD) software. For information on using methods, see
the host system documentation.
DD in Use displays the version number displayed in the format: device type.device revision.DD revision. The Min
Compatible DD revision displayed is the latest device description revision that is compatible with the displayed device
revision.
This method is available via the resource block.

301

Device Description Installation


August 2012

302

Instruction Manual
D103412X012

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Appendix F Operating with a DeltaV SystemFF


Process Systems DeltaV System
Getting Started with DeltaV Host Systems

Appropriate Device Descriptions (DDs) installed. See the Device Description Compatibility table on
page 298. For DD installation information see Appendix E.

Digital valve controller correctly mounted on actuator. For mounting information see the
Installation section of this manual and the instructions included with the mounting kit.

Utilities connected. For information on making pneumatic and electrical connections, see the
Installation section of this manual. For information on applying power to the segment, see DeltaV
books online.

Instrument in standby. For information on placing the instrument in standby, see DeltaV books
online.

Perform the initial setup. See the Basic Setup section of this manual. If the valve is shipped from the
factory mounted on an actuator, perform basic setup only to verify setup is correct and valve
operation is satisfactory.

Device Commissioned. For information on commissioning a device, see DeltaV books online.

Additional configuration required, such as setting alarms, cutoffs, and other resource block and
transducer block parameters. See the Detailed Setup section of this manual.

Control strategy defined. For information on defining a control strategy, see DeltaV books online.

Associate I/O with device. See DeltaV books online.


Download device. See DeltaV books online.

303

Instruction Manual

Operating with a DeltaV System


August 2012

D103412X012

Table F1. Transducer Block (TB) Parameters - Configuration Index


Parameter Label

Path to Parameter

Actual Travel

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Actual Travel

Actuator Fail Action

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Fail Action

Actuator Manufacturer ID

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Manufacturer ID

Actuator Model Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Model Number

Actuator Serial Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Serial Number

Actuator Size

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Size

Actuator Style

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Actuator Style

Air

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Air

Alert Conditions

TB > Device Diagnostics > Alert Conditions

Alert Key

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Alert Key

Area Units

TB > Configure/Setup > Detailed Setup > Instrument > Units: Area Units

Block Configuration Error

TB > Device Diagnostics > Status > Transducer Block Error: Block Configuration Error

Blocks Set to Default Alert

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Blocks Set to Default: Block Set to Default Alert

Blocks Set to Default Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Blocks Set to Default: Block Set to Default Alert Enable

Calibration Date

TB > Configure/Setup > Detailed Setup > Instrument > Calibration: Calibration Date

Calibration Location

TB > Configure/Setup > Detailed Setup > Instrument > Calibration: Calibration Location

Calibration Person

TB > Configure/Setup > Detailed Setup > Instrument > Calibration: Calibration Person

Cycle Count

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter:Cycle Count
TB > Device Variables > Overview > Cycle Count

Cycle Count Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter: Cycle Count Alert

Cycle Count Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter: Cycle Count Alert Enable

Cycle Count Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter Cycle Count Alert Point

Cycle Count Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Cycle Counter: Cycle Count Deadband

Device Needs Maintenance Now

TB > Device Diagnostics > Status > Transducer Block Error: Device Needs Maintenance Now

Drive Current

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current

Drive Current Alert

TB > Device Diagnostics > Status > Self Test Status: Drive Current Alert
TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert

Drive Current Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert Enable

Drive Current Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert Point

Drive Current Alert Time

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Alert Time

Drive Current Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Manual Recovery

Drive Current Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Current: Drive Current Shutdown

Drive Signal

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Signal: Drive Signal
TB > Device Variables > Overview > Drive Signal

Drive Signal Alert

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Signal: Drive Signal Alert

Drive Signal Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Drive Signal: Drive Signal Alert Enable

Effective Area

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Effective Area

Feedback Connection

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Feedback Connection

Flow Direction

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Direction

Flow Tends To

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Flow Tends To

I/O Processor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Alert

I/O Processor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Alert Enable

I/O Processor Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Man Recovery

I/O Processor Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: I/O Processor Shutdown

Inlet Pressure

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Inlet Pressure

Input Characterization

TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization > Input Characterization
TB > Device Variables > Overview > Input Characterization

Integrator Limited Hi

TB > Device Diagnostics > Status > Self Test Status: Integrator Limited Hi

Integrator Limited Lo

TB > Device Diagnostics > Status > Self Test Status: Integrator Limited Lo

Integrator Suspended

TB > Device Diagnostics > Status > Self Test Status: Integrator Suspended

IOP Failure

TB > Device Diagnostics > Status > Self Test Status: IOP Failure

Last Valid Point

TB > Configure/Setup > Detailed Setup > Response Control > Input Characterization > Last Valid Point

Leak Class

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Leak Class

Length Units

TB > Configure/Setup > Detailed Setup > Instrument > Units: Length Units
-Continued-

304

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Table F1. Transducer Block (TB) Parameters - Configuration Index (Continued)


Parameter Label
Lever Style

Path to Parameter
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lever Style

Lost Static Data

TB > Device Diagnostics > Status > Transducer Block Error: Lost Static Data

Lower Bench Set

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Lower Bench Set

MAI Channel 1

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 1

MAI Channel 2

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 2

MAI Channel 3

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 3

MAI Channel 4

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 4

MAI Channel 5

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 5

MAI Channel 6

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 6

MAI Channel 7

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 7

MAI Channel 8

TB > Configure/Setup > Detailed Setup > MAI Channel Map > MAI Channel 8

Maximum Supp Pressure

TB > Configure/Setup > Detailed Setup > Instrument > Application: Max Supp Pressure

MLFB Error

TB > Device Diagnostics > Status > Self Test Status: MLFB Error

Moment Arm Length

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Moment Arm

Nominal Supply Pressure

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Nominal Supply Pressure

Out of Service

TB > Device Diagnostics > Status > Transducer Block Error: Out of Service

Outlet Pressure

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Outlet Pressure

Output Block Timeout

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Blk Timeout

Output Block Timeout Alert

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Alert

Output Block Timeout Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Alert Enable

Output Block Timeout Manual


Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Manual Recovery

Output Block Timeout Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Configuration > Output Block Timeout: Output Block Timeout Shutdown

Packing Type

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Packing Type

PD Inside Status

TB > Configure/Setup > Detailed Setup > Alerts > Performance > PD Inside Status

PD Inside Status

TB > Device Variables > Overview > PD Inside Status

PD Run

TB > Configure/Setup > Detailed Setup > Alerts > Performance > PD Run

Performance Critical Alert

TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Critical: Performance Critical Alert

Performance Critical Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Critical: Performance Critical Alert Enable

Performance Information Alert

TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Information: Performance Information Alert

Performance Information Alert


Enable

TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Information: Performance Information Alert Enable

Performance Reduced Alert

TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Reduced: Performance Reduced Alert

Performance Reduced Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Performance > Performance Reduced: Performance Reduced Alert Enable

Performance Tuner(1)

TB > Configure/Setup > Basic Setup > Performance Tuner

Port Diameter

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Diameter

Port Type

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Port Type

Pressure A Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Alert

Pressure A Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Alert Enable

Pressure A Sensor Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Manual Recovery

Pressure A Sensor Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure A Sensor Shutdown

Pressure B Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure B Sensor Alert

Pressure B Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Pressure B Sensor Alert Enable

Pressure Cutoff Close

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Cutoff Close

Pressure Cutoff Open

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Cutoff Open

Pressure Integral Deadzone

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Deadzone

Pressure Integral Gain

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Gain

Pressure Integral Limit Hi

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Limit Hi

Pressure Integral Limit Lo

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Integral Limit Lo

Pressure MLFB Gain

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure MLFB Gain

Pressure Proportional Gain

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Prop Gain

Pressure Range Hi

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Range Hi

Pressure Range Lo

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Pressure Control: Pressure Range Lo

Pressure Tuning Set

TB > Configure/Setup > Detailed Setup > Response Control > Pressure Tuning: Pressure Tuning Set
-Continued-

305

Instruction Manual

Operating with a DeltaV System


August 2012

D103412X012

Table F1. Transducer Block (TB) Parameters - Configuration Index (Continued)


Parameter Label
Pressure A

Path to Parameter
TB > Device Variables > Overview > Pressures: Pressure A

Pressure A Sensor Failure

TB > Device Diagnostics > Status > Self Test Status: Pressure A Sensor Failure

Pressure B

TB > Device Variables > Overview > Pressures: Pressure B

Pressure B Sensor Failure

TB > Device Diagnostics > Status > Self Test Status: Pressure B Sensor Failure

Pressure Differential

TB > Device Variables > Overview > Pressures: Pressure Diff

Pressure Fallback Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Fallback: Pressure Fallback Alert

Pressure Fallback Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Fallback: Pressure Fallback Alert Enable

Pressure Units

TB > Configure/Setup > Detailed Setup > Instrument > Units: Pressure Units

Processor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Processor Alert

Processor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Processor Alert Enable

Program Memory Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Alert Enable

Program Memory Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Manual Recovery

Program Memory Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Shutdown

Program Memory Alert

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Program Memory Alert

Protection

TB > Device Variables > Overview > Protection

Proximity Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Alert

Proximity Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Alert Enable

Proximity Hi Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Hi Alert

Proximity Hi Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Hi Hi Alert Enable

Proximity Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Alert

Proximity Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Alert Enable

Proximity Lo Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Lo Alert

Proximity Lo Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Proximity: Proximity Lo Lo Alert Enable

Push Down To

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Push Down To

Simulate PlantWeb Alerts

TB > Configure/Setup > Detailed Setup > Alert Handling > Simulate PlantWeb Alerts

Rated Travel

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Rated Travel

Relay Type

TB > Configure/Setup > Detailed Setup > Instrument > Application: Relay Type

Seat Type

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Seat Type

Setpoint

TB > Device Variables > Overview > AO ControlPreCharacterization: Setpoint

Setpoint Status

TB > Device Variables > Overview > AO ControlPreCharacterization: Setpoint Status

Setpoint(D)

TB > Device Variables > Overview > DO Control: Setpoint(D)

Shaft Stem Diameter

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Shaft Stem Dia

Simulate Active

TB > Device Diagnostics > Status > Transducer Block Error: Simulate Active

Simulate Jumper ON

TB > Device Diagnostics > Status > Self Test Status: Simulate Jumper ON

Spring Rate

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Spring Rate

Spring Rate Units

TB > Configure/Setup > Detailed Setup > Instrument > Units: Spring Rate Units

Static Memory Alert

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Alert

Static Memory Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Alert Enable

Static Memory Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Manual Recovery

Static Memory Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Electronic > Processor Impaired: Static Memory Shutdown

Stroke Time Close

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Close

Stroke Time Open

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Stroke Time Open

Supply Pressure Maximum

TB > Device Diagnostics > Device Record > Supp Pressure Max

Supply Pressure Maximum Time

TB > Device Diagnostics > Device Record > Supp Pressure Maximum Time

Supp Pressure Minimum

TB > Device Diagnostics > Device Record > Supp Pressure Minimum

Supp Pressure Minimum Time

TB > Device Diagnostics > Device Record > Supp Pressure Minimum Time

Supply Pressure

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure

Supply Pressure

TB > Device Variables > Overview > Pressures: Supply Pressure

Supply Pressure Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Hi Alert

Supply Pressure Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Pressure Hi Alert Enable

Supply Pressure Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Hi Alert Point

Supply Pressure Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Lo Alert

Supply Pressure Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Lo Alert Enable

Supply Pressure Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Supply Pressure: Supply Pressure Lo Alert Point
-Continued-

306

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Table F1. Transducer Block (TB) Parameters - Configuration Index (Continued)


Parameter Label
Supply Pressure Sensor Alert

Path to Parameter
TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Supply Pressure Sensor Alert

Supply Pressure Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Pressure Sensors: Supply Pressure Sensor Alert Enable

Supply Sensor Failure

TB > Device Diagnostics > Status > Self Test Status: Supply Sensor Failure

Tag Description

TB > Configure/Setup > Detailed Setup > Instrument > Tag Description

Temperature Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Hi Alert Point

Temperature Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert Point

Temperature Maximum

TB > Device Diagnostics > Device Record > Temperature Maximum

Temperature Maximum Time

TB > Device Diagnostics > Device Record > Temperature Maximum Time

Temperature Minimum

TB > Device Diagnostics > Device Record > Temperature Minimum

Temperature Minimum Time

TB > Device Diagnostics > Device Record > Temperature Minimum Time

Temperature

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature
TB > Device Variables > Overview > Temperature

Temperature Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Hi Alert

Temperature Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Hi Alert Enable

Temperature Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert

Temperature Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert Enable

Temperature Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Environment > Temperature Limit: Temperature Lo Alert Point

Temperature Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Temperature Sensor: Temperature Sensor Alert

Temperature Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Temperature Sensor: Temperature Sensor Alert Enable

Temperature Units

TB > Configure/Setup > Detailed Setup > Instrument > Units: Temperature Units
TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel

Travel

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel
TB > Device Variables > Overview > AO Control PostCharacterization: Travel

Travel(D)

TB > Device Variables > Overview > DO Control: Travel(D)

Travel(DeChar)

TB > Device Variables > Overview > AO Control PreCharacterization: Travel(DeChar)

Travel Status

TB > Device Variables > Overview > AO Control PostCharacterization: Travel Status

Trend

TB > Device Diagnostics > Trend

Trim Style 1

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 1

Trim Style 2

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Reference > Trim Style 2

Travel Accumulator

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator
TB > Device Variables > Overview > Travel Accumulator

Travel Accumulator Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Alert

Travel Accumulator Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Alert Enable

Travel Accumulator Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Alert Point

Travel Accumulator Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel History > Travel Accumulator: Travel Accumulator Deadband

Travel Closed Alert

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Alert

Travel Closed Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Alert Enable

Travel Closed Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Alert Point

Travel Closed Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Closed: Travel Closed Deadband

Travel Count

TB > Device Variables > Overview > Travel Count

Travel Cutoff Hi

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel Control: Travel Cutoff Hi

Travel Cutoff Lo

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel Control: Travel Cutoff Lo

Travel Deviation Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Deviation: Travel Deviation Alert Point

Travel Deviation Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel: Travel Deviation Deadband

Travel Deviation Time

TB > Configure/Setup > Detailed Setup > Alerts > Travel: Travel Deviation Time

Travel Deviation Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Deviation: Travel Deviation Alert

Travel Deviation Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Deviation: Travel Deviation Alert Enable

Travel Integral Deadzone

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Deadzone

Travel Integral Enable

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Enable

Travel Integral Limit Hi

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Limit Hi

Travel Integral Limit Lo

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Limit Lo

Travel Integral Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Integral Gain

Travel Limit Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Hi Alert

Travel Limit Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Hi Alert Enable
-Continued-

307

Operating with a DeltaV System

Instruction Manual

August 2012

D103412X012

Table F1. Transducer Block (TB) Parameters - Configuration Index (Continued)


Parameter Label
Travel Hi Alert Point

Path to Parameter
TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Hi Alert Point

Travel Hi Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Hi Deadband

Travel Limit Hi Hi Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Hi Hi Alert

Travel Limit Hi Hi Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Hi Hi Alert Enable

Travel Limit Hi Hi Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Hi Hi Alert Point

Travel Limit Hi Hi Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Hi Hi Deadband

Travel Limit Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Lo Alert

Travel Limit Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Limit Lo Alert Enable

Travel Limit Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Lo Alert Point

Travel Limit Lo Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit Hi/Lo: Travel Lo Deadband

Travel Limit Lo Lo Alert

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Lo Lo Alert

Travel Limit Lo Lo Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Limit Lo Lo Alert Enable

Travel Limit Lo Lo Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Lo Lo Alert Point

Travel Limit Lo Lo Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Limit: Travel Lo Lo Deadband

Travel MLFB Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel MLFB Gain

Travel Open Alert

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Alert

Travel Open Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Alert Enable

Travel Open Alert Point

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Alert Point

Travel Open Deadband

TB > Configure/Setup > Detailed Setup > Alerts > Proximity > Travel Open: Travel Open Deadband

Travel Proportional Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Proportional Gain

Travel Sensor Motion

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Travel Sensor Motion

Travel Sensor Alert

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Alert

Travel Sensor Alert Enable

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Alert Enable

Travel Sensor Hi Error

TB > Device Diagnostics > Status > Self Test Status: Travel Sensor Hi Error

Travel Sensor Lo Error

TB > Device Diagnostics > Status > Self Test Status: Travel Sensor Lo Error

Travel Sensor Manual Recovery

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Manual Recovery

Travel Sensor Shutdown

TB > Configure/Setup > Detailed Setup > Alerts > Sensor > Travel Sensor: Travel Sensor Shutdown

Travel Sensor Span Error

TB > Device Diagnostics > Status > Self Test Status: Travel Sensor Span Error

Travel Target

TB > Configure/Setup > Detailed Setup > Alerts > Travel > Travel Target

Travel Target

TB > Device Variables > Overview > AO Control PostCharacterization: Travel Target

Travel Tuning Set

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Tuning Set

Travel Units

TB > Configure/Setup > Detailed Setup > Instrument > Units > Travel Units

Travel Velocity Gain

TB > Configure/Setup > Detailed Setup > Response Control > Travel Tuning: Travel Velocity Gain

Travel/Pressure Select

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel/Pressure Select

Travel/Pressure State

TB > Configure/Setup > Detailed Setup > Response Control > Travel / Pressure Control > Travel/Pressure State
TB > Device Variables > Overview > Travel/Pressure State

Unbalanced Area

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Trim > Unbalanced Area

Upper Bench Set

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Actuator > Upper Bench Set

Valve Class

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Class

Valve Manufacturer ID

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Manufacturer ID

Valve Model Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Model Number

Valve Serial Number

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Serial Number

Valve Size
Zero Power Condition

308

TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Size
TB > Configure/Setup > Detailed Setup > Valve and Actuator > Valve > Valve Style
TB > Configure/Setup > Detailed Setup > Instrument > Application: Zero Power Condition

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Table F2. Resource Block (RB) Parameters - Configuration Index


Parameter Name

Path to Parameter

Alert Key

RB > Configure/Setup > Setup > Alarm Handling > Alert Key

Block Alarm: Alarm State

RB > Device Diagnostics > Status > Block Alarm: Alarm State

Block Alarm Disabled

RB > Configure/Setup > Setup > Alarm Handling > Block Alarm: Block Alarm Disabled

Block Alarm Auto Acknowledge

RB > Configure/Setup > Setup > Alarm Handling > Block Alarm: Block Alarm Auto Acknowledge

Discrete Alarm Auto Acknowledge

RB > Configure/Setup > Setup > Alarm Handling > Write Alarm: Discrete Alarm Auto Acknowledge

Confirm Time

RB > Configure/Setup > Setup > Alarm Handling > All Alarms: Confirm Time

Device ID
Device Revision
Device State
Device Type
DD Revision
Diagnostic Options
Electronics S/N
Factory S/N
Fault State
Function Block Options
Features Available

RB > Configure/Setup > Setup > Identification > Identification: Device ID


RB > Device Variables > Instrument > Identification: Device ID
RB > Configure/Setup > Setup > Version > Version Information: Device Revision
RB > Device Variables > Instrument > Version Information: Device Revision
RB > Device Diagnostics > Status > Device State
RB > Configure/Setup > Setup > Identification > Identification: Device Type
RB > Device Variables > Identification: Device Type
RB > Configure/Setup > Setup > Version > Version Information: DD Revision
RB > Device Variables > Identification: DD Revision
RB > Configure/Setup > Setup > Options > Diagnostic Options
RB > Device Variables > Options > Diagnostics Options
RB > Configure/Setup > Setup > Identification > Identification:Electronics S/N
RB > Device Variables > Identification: Electronics S/N
RB > Configure/Setup > Setup > Identification > Identification:Factory S/N
RB > Device Variables > Identification: Factory S/N
RB > Device Diagnostics > Status > Fault State
RB > Configure/Setup > Setup > Options > Function Block Options
RB > Device Variables > Options > Function Block Options
RB > Configure/Setup > Setup > Options > Features Available
RB > Device Variables > Options > Features Available

Features Selected

RB > Configure/Setup > Setup > Options > Features Selected

Field S/N

RB > Configure/Setup > Setup > Identification > Identification: Field S/N

Field S/N

RB > Device Variables > Identification: Field S/N

Hardware Revision

RB > Configure/Setup > Setup > Version > Version Information: Hardware Revision

ITK Version

RB > Configure/Setup > Setup > Version > Version Information: ITK Version

Manufacturer

RB > Configure/Setup > Setup > Identification > Identification: Manufacturer

Manufacturer

RB > Device Variables > Identification: Manufacturer

Maximum Alerts Allow

RB > Configure/Setup > Setup > Alarm Handling > All Alarms: Maximum Alerts Allow

Maximum Alert Possible

RB > Configure/Setup > Setup > Alarm Handling > All Alarms: Maximum Alerts Possible

Miscellaneous Options

RB > Configure/Setup > Setup > Options > Miscellaneous Options


RB > Device Variables > Options > Miscellaneous Options

Resource Block Error

RB > Device Diagnostics > Status > Resource Block Error

RCas Timeout

RB > Configure/Setup > Setup > Comm Timeout > RCas Timeout

ROut Timeout

RB > Configure/Setup > Setup > Comm Timeout > ROut Timeout

Firmware Revision

RB > Configure/Setup > Setup > Version > Version Information: Firmware Revision

Status

RB > Device Diagnostics > Status

Standby Firmware Revision

RB > Configure/Setup > Setup > Version > Version Information: Standby Firmware Revision

Strategy
Tag Description

RB > Configure/Setup > Setup > Identification > Identification: Strategy


RB > Device Variables > Identification: Strategy
RB > Configure/Setup > Setup > Identification > Identification: Tag Description
RB > Device Variables > Identification: Tag Description

Write Alarm: Alarm State

RB > Device Diagnostics > Status > Write Alarm: Alarm State

Write Alarm Disabled

RB > Configure/Setup > Setup > Alarm Handling > Write Alarm: Write Alarm Disabled

Write Lock
Write Priority

RB > Configure/Setup > Setup > Write Lock > Write Lock
RB > Device Diagnostics > Status > Write Lock
RB > Configure/Setup > Setup > Write Lock > Write Priority

309

Operating with a DeltaV System


August 2012

Instruction Manual
D103412X012

Introduction
Note
This appendix does not necessarily provide the latest information on the DeltaV system. For the latest information on using the
DeltaV system, refer to the online help or documentation supplied with the system.

This appendix provides specific instructions for performing basic setup operations on the DeltaV host system. It is not
a comprehensive resource, rather a starting point. For more information, refer to the following sources:
Section 3: Basic Setup and Tuning for detailed information regarding initial setup, and stabilizing and optimizing valve
response.
Section 4: Detailed Setup for detailed information on configuring all of the blocks in the instrument, and an overview
of the function blocks.
Section 5: Calibration for complete calibration information.
Appendix A: Principle of Operation for information on how digital valve controller operation.
Appendix D: FOUNDATION fieldbus Communication for an overview of function block and block modes, as well as
additional information pertaining to fieldbus communication.
Appendix E: DD Installation for information on installing the device description (DD) software on your host system.
DeltaV OnLine Help or Documentation for complete and current information about navigating in the DeltaV system.

Software Functionality/System Requirements


DVC6200f digital valve controllers are designed to permit remote setup, calibration, and testing using Process
Systems DeltaV system as the host system.
To use the methods, accessed as described in this appendix, requires that the device description (DD) for the
DVC6200f digital valve controller be installed on the host system. For information on installing the device description,
refer to DD Installation (Appendix E) and the host system documentation.

Using AMS Device Manager


Refer to figures F1 and F2 to access the digital valve controller using AMS Suite: Intelligent Device Manager.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the the digital valve controller icon in the All Containers pane (the left panel) and rightclick once on the
digital valve controller icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.

310

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Figure F1. Navigating to AMS Device Manager

DIGITAL VALVE
CONTROLLER ICON
AND NAME

OPEN WITH AMS


DEVICE MANAGER

Figure F2. Accessing the Digital Valve Controller Through AMS Device Manager

LEFTCLICK TO
ACCESS THE DELTAV
NETWORK

DIGITAL VALVE
CONTROLLER
ICON AND
NAME

311

Operating with a DeltaV System


August 2012

Instruction Manual
D103412X012

Methods
Transducer Block
The following methods are accessed via the transducer block: Device Setup, Auto Travel Calibration, Manual Travel
Calibration, Supply Sensor Calibration, Output A Sensor Calibration, Output B Sensor Calibration, Travel Sensor Adjust,
Stroke Valve, Performance Tuner, Stabilize/Optimize, and Relay Adjust.
Refer to figures F1, F2, and F3 and the following steps to access these methods.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the the digital valve controller icon in the All Containers pane (the left panel) and rightclick once on the
digital valve controller icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Methods in the Actions menu, as shown in figure F3 and rightclick once.
6. Select the desired method from the the Actions menu and leftclick to start the method.

Resource Block
The Restart Options method and the DD Information method are available via the resource block. Refer to figure F3
and the following steps to access these methods.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the digital valve controller icon in the All Containers pane (the left panel) and rightclick once on the digital
valve controller icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Methods in the Actions menu, as shown in figure F3 and rightclick once.
6. Select the desired method from the the Actions menu and leftclick to start the method.

Accessing Parameters
Transducer Block
For detailed information on the parameters that are changed via the transducer block, refer to the Detailed Setup
section of this manual. Refer to figures F2, F3, and F4 for information on accessing transducer block parameters.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the digital valve controller icon in the All Containers pane and rightclick once on the digital valve controller
icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Configure/Setup in the Actions menu (see figure F3) and leftclick to access Configuration and Setup
parameters.
6. Leftclick on Digital Valve Controller (TRANSDUCER) to access the transducer block parameters. Refer to table F1
for the transducer block configuration menu.

312

Instruction Manual

Operating with a DeltaV System

D103412X012

Figure F3. Actions Menu

August 2012

ACTIONS

CONFIGURE/SETUP

RESOURCE BLOCK
METHODS

TRANSDUCER
BLOCK METHODS

Note
To access diagnostic parameters leftclick on Device Diagnostics, and then on Digital Valve Controller (TRANSDUCER). See
figure F4.
To access device variables leftclick on Device Variables, and then on Digital Valve Controller (TRANSDUCER). See figure F4.

313

Operating with a DeltaV System

Instruction Manual

August 2012

D103412X012

Figure F4. Accessing Configure/Setup, Device Diagnostics, and Device Variables

DIGITAL VALVE
CONTROLLER
(TRANSDUCER)

RESOURCE
(RESOURCE)

DEVICE
DIAGNOSTICS

DEVICE
VARIABLES

Resource Block
For detailed information on the parameters that are changed via the resource block, refer to the Detailed Setup
section of this manual. Refer to figures F2, F3, and F4 for information on accessing resource block parameters.
1. Start DeltaV Explorer by selecting DeltaV Explorer from the Start menu.
2. Locate the digital valve controller icon in the All Containers pane and rightclick once on the block icon or name.
3. Locate Open with AMS Device Manager in the context menu and leftclick to bring up the Device Connection View.
4. Navigate to the digital valve controller icon or name as shown in figure F2 and leftclick.
5. Locate Configure/Setup in the Actions menu (see figure F3) and leftclick to access Configuration and Setup
parameters.
6. Leftclick on Resource (RESOURCE) to access the resource block parameters. Refer to table F2 for the resource
block configuration menu.

Note
To access diagnostic parameters leftclick on Device Diagnostics, and then on Resource (RESOURCE). See figure F4.
To access device variables leftclick on Device Variables, and then on Resource (RESOURCE). See figure F4.

314

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Bringing the Device OnLine


To completely configure the digital valve controller for use in a fieldbus loop, the following conditions must be met.
Refer to DeltaV OnLineHelp or documentation for detailed information on accomplishing these steps.
1. A place holder must be created - a place holder is an electronic representation of the digital valve controller that
exists in the DeltaV database with no associated physical device.
2. Device must be commissioned - Commissioning the device involves downloading applicable parameters from the
device place holder to the physical device.
3. Any additional configuration that is required, such as setting alarms, cutoffs, and other resource block and
transducer block parameters. See the Detailed Setup section of this manual.
4. Define the control strategy
5. Associate I/O to the digital valve controller.
6. The device is now ready to be downloaded.

PlantWeb Alerts
Fieldbus devices detect and report their device alarms to a DeltaV system (or other host system). This includes
detecting whether an alert condition is active, reporting the alarm to DeltaV and later clearing the alarm when the
condition is no longer active. Whether a particular alert condition can be suppressed, disabled or configured offline
are all determined by the device.
For Fieldbus, the DeltaV system is responsible for knowing which devices have alarms, ensuring that alarms are
properly represented (such as after controller switchovers) and reporting to operators, Event Chronicle, AMS, OPC
Alarms and Events server, etc. So the only alarms DeltaV shows for a Fieldbus device are those the device has defined
as alarms and has reported to DeltaV.
All device alarms are configured and processed in the DeltaV system identically to process alarms. This means that
how the alarms are communicated within the system, what workstations are notified, alarm annunciation, graphical
representations, event recording, acknowledgement, etc. are identical for process and device alarms. This ensures
that device alarms and process alarms are available to all users and applications in a consistent fashion.

Setting up PlantWeb Alerts


This section walks you through the steps and considerations to implement PlantWeb alerts.

DeltaV Hardware and Software Requirements


The first step to implement PlantWeb alerts is to have the correct hardware and software:
DeltaV v6.3 or later
DeltaV Operate
MD Controllers
Fieldbus devices - While device alerts are supported on all fieldbus devices, devices that offer PlantWeb alerts
provide significantly more useful information.
Series 2 H1 cards

315

Operating with a DeltaV System


August 2012

Instruction Manual
D103412X012

Initial Device Setup


When new FF devices are commissioned on the DeltaV system, device alarms are automatically enabled and default
priorities are assigned to the alarms. Select properties on the device, then the Alarms and Displays tab, as shown in
figure F5 to view whether device alarms are enabled on a particular device.
Figure F5. Alarms & Display Tab

The Enable Device Alarms configuration option modifies the device configuration. Thus changing this setting requires
a download to the device. Devices that are migrated from older DeltaV systems will have their device alarms disabled.

Note
1. Use the default setting of device alarms enabled. If the user does not want notification of device alarms, this can be configured
on each individual alarm. Later on, you can modify the alarm configurations without downloading the device. Disabling device
alarms disables all of the alarms, including the device communication failure alarm.
2. Use the same control display for the device as for the control module.
3. If you suspect a rogue device is generating extra H1 bus traffic from device alarms, disabling device alarms stops the device from
sending the alarms.
4. If the Alarms and Displays tab is not shown, then you either do not have an MD controller or the device is on a Series 1 H1 card.

316

Instruction Manual

Operating with a DeltaV System

D103412X012

August 2012

Area Assignment
Controllers use this area assignment to report node status (e.g. not communicating). Devices and control modules use
this area assignment to determine where to send their alarms.
Area A is the default area assignment for all controllers and workstations (see figures F6 and F7). Also, by default Area
A is assigned to all workstations Alarms and Events subsystem. This means that all controller status problems are sent
to all workstations by default.
Figure F6. Controller Properties

Figure F7. Device Properties

The controller is assigned to Area A. A device that is NOT yet


associated with a control module will default to the same area
as the controller.

A fieldbus device will change its area association once the device is configured to a control module. In addition, the
device is assigned to the same place in the logical hierarchy as this control module. So if the control module is under a
unit, the device is also considered under this same unit.
The device is automatically associated with the same area as the control module that uses the lowest index number
function block in the device. This block is usually the primary input or output function block of the device. This ensures
that wherever the control module is reporting information, all device information that may also be relevant is also
reported.

Note
1. For devices with multiple inputs or outputs (such as the 848), you need to decide which area is best for device alarm reporting
and be sure to assign the correct control module to the lowest index number function block. If there is no module assigned to this
function block, then the device will always be assigned to the same area as the controller.
2. With controller area default of AREA A, and the default of AREA A being assigned to all workstations, you need to evaluate the
alarm settings when commissioning a new fieldbus device with device alarms enabled. If the device detects a FAILED or COM FAIL
alarm prior to being assigned to a control module, this device alarm will be reported and annunciated to all workstations. This is

317

Operating with a DeltaV System


August 2012

Instruction Manual
D103412X012

because all workstations have Area A assigned. Consider lowering the priority of these alarms to ADVISORY until the end of the
commissioning process.

Reporting Alarms and Events to a Workstation


Device alarm and event reporting is no different than control module reporting. Alarm and event reporting to
workstations is determined by assigning areas to workstations. The workstation area assignment is all you need to do
to ensure that you have all of the information (device and process) for that area.
This is important so that ALL of the information about an area -- both the process and device information -- is available
at any workstation that is responsible for that area. That way the Event Chronicle has a complete record for that area,
and any user can drill into a graphic or tag and access all of the information.
This DOES NOT determine WHO views the device alarms. Who views the alarms is determined by filtering at each
workstation.
Now that all of the device (and process) information is assigned to a workstation, the next step is to decide what
priority of device and process alarms cause alarm annunciation to the users on that workstation.

Setting up WHO Sees Device Alarms


The priority of the alarms, and the settings at that workstation determine what alarms are annunciated on a particular
workstation. Annunciated means sound the horn and shown in the alarm banner, Alarm List display, etc.
There are two different approaches that can be used to adjust the device alarm filtering for a particular workstation:
Adjust the default DeltaV Operate alarm settings in the UserRef/UserSettings file
Adjust the individual device alarm priorities
By default, DeltaV Operator Stations have all process alarms are annunciated, and show up on the Alarm Banner, Alarm
List, graphical displays, etc. on all operator workstations. Also by default, the device alarms with priority settings below
WARNING (8) are NOT annunciated or shown in the alarm banner. The low priority device alarms can be shown in
graphics and on summaries defined to not be limited by the alarm settings.
The DeltaV Maintenance Station uses the same DeltaV Operate alarm setting for device alarm annunciation. This
license only shows device alarms on Maintenance Station graphics. NO process alarms are shown in the alarm banner
or ANY alarm summary.
Thus, device alarms and process alarms can be either combined and/or separated for specific user installations, based on
their operating philosophy.

Setting DeltaV Operate Device Alarm Annunciation Defaults


DeltaV Operate has default settings in the UserRef.grf file for what priority of device alarms will annunciate and show
in the alarm banner. The default DeltaV Operate alarm settings annunciate device alarms that are of the priority
WARNING (8) or higher. Device alarms below this priority will not sound the horn or show up in the alarm banner.
Operator Station displays can be configured to show any alarms reporting to that workstation. Along with typical
display configuration, alarm summaries can be configured to display alarms that match the alarm banner settings, or
user specified ranges. The standard AlarmSum display is configured to show all alarms reporting to that workstation
(see figure F8).

318

Instruction Manual
D103412X012

Operating with a DeltaV System


August 2012

Figure F8. DeltaV Alarm Summary Configuration

Each display alarm summary can be configured to


match the alarm banner or be uniquely defined.

Note
If you think you should be seeing a device alarm in the alarm banner and it is not there, verify that the device is shown on the
AlarmSum display. This display shows ALL of the alarms reporting to that workstation, regardless of the device alarm annunciation
settings. If the device is not shown in this display, then it is not reporting to this workstation (or the logged on user does not have
responsibility for that area).

The default for device alarm annunciation (sounds the horn and shown in the alarm banner) can be modified for all
operator/maintenance stations. Or unique settings can be defined for specific workstations. Use the workstation name
to adjust settings for specific workstations in UserSettings.grf.
For example, if an installation has a Maintenance Station named 'MAINT', then the UserRef.grf (then renamed to
UserSettings.grf) would contain alarm settings for the MAINT workstation as appropriate for maintenance (e.g. all
device alarms in the alarm banner).

Note
To easily find the device alarm configuration in UserRef or UserSettings, open the display in the Standard directory, right click and
select EDIT SCRIPT, then select Edit, Find and type in DEVICE. This will take you to the location in the file with the device alarm
settings.

319

Operating with a DeltaV System

Instruction Manual

August 2012

D103412X012

Deciding Device Alarm Priorities


Each device alarm, just like every process alarm, has a priority assigned to it. When a device is created, the device
alarms are assigned default alarm priorities as shown in figure F9.
Figure F9. Default PlantWeb Alert Priorities

The priority of a device alarm defines whether the


alarm is annunciated on a particular workstation, in
addition to the color of the alarm and the horn sound.

The DeltaV workstation default is to annunciate device alarms above the ADVISORY (7) priority.
Therefore, by default both the FAILED and COMM PlantWeb alerts annunciate to the operator.
The priority of each alarm needs to be considered. The priority of a device alarm is determined by how important that
device problem is and the consequences to the process.
The priority is not based solely on the type of device. This means that while some DVC6200f's may be critical to
operation, other DVC6200f's may not. In this example, the DVC6200f's would have different default alarm priorities.

Note
1. If your installation has the Fieldbus devices, but is not ready to use PlantWeb alerts, then you can disable the individual alarms at
the device - or through the System Alarm Management application. Later on, individual alarms can be enabled without having to
download the device.
2. When you first begin to use device alarms, be sure that your alarm priority settings for the workstations or the individual device
alarm priorities are such that they don't cause undue operator burden. This could mean only having a few device alarms set at
WARNING or above, or changing the DeltaV Operate default such that only CRITICAL device alarms (or even perhaps NO device
alarms annunciate to the operator).
3. DO NOT enable ALL of the PlantWeb alerts in a device. Only enable the alerts that are needed.

320

Instruction Manual

Glossary

D103412X012

August 2012

Glossary
Algorithm
A set of logical steps to solve a problem or
accomplish a task. A computer program contains
one or more algorithms.

Deadband
Region around a reference point that must be
exceeded before a new event occurs.

Deviation
Alphanumeric
Consisting of letters and numbers.

ANSI (acronym)
The acronym ANSI stands for the American
National Standards Institute

ANSI Class
Valve pressure/temperature rating.

Bench Set
Pressure, supplied to an actuator, required to
drive the actuator through rated valve travel.
Expressed in pounds per square inch.

Byte
A unit of binary digits (bits). A byte consists of
eight bits.

Configuration
Stored instructions and operating parameters for
a FIELDVUE Instrument.

Control Loop
An arrangement of physical and electronic
components for process control. The electronic
components of the loop continuously measure
one or more aspects of the process, then alter
those aspects as necessary to achieve a desired
process condition. A simple control loop
measures only one variable. More sophisticated
control loops measure many variables and
maintain specified relationships among those
variables.

Controller

Usually, the difference between set point and


process variable. More generally, any departure
from a desired or expected value or pattern.

Device ID
Unique identifier embedded in the instrument at
the factory.

Drive Signal
The signal to the I/P converter from the printed
wiring board. It is the percentage of the total
microprocessor effort needed to drive the valve
fully open. In most applications, drive signal
ranges from 55% to 75%.

Feedback Arm
The mechanical connection between the valve
stem linkage and the FIELDVUE Instrument travel
sensor.

Feedback Signal
Indicates to the instrument the actual position of
the valve. The travel sensor provides the feedback
signal to the instrument printed wiring board
assembly. A mechanical linkage connects the
travel sensor to the valve stem or shaft.

Firmware
The combination of a hardware device and
computer instructions and data that reside as
readonly software on that device.

Note
1. This term (firmware) is sometimes used to refer only to
the hardware device or only to the computer instructions or
data, but these meanings are deprecated.
2. The confusion surrounding this term has led some to
suggest that it be avoided altogether. The term is included
here because of its use in older documentation and culture.

A device that operates automatically to regulate a


controlled variable.

321

Instruction Manual

Glossary
August 2012

Gain
The ratio of output change to input change.

D103412X012

Pressure Sensor
A FIELDVUE instrument internal device that
senses the output pressure from the pneumatic
relay.

Hardware Revision
Revision number of the Fisher instrument
hardware. The physical components of the
instrument are defined as the hardware.

Instrument Level
Determines the functions available for the
instrument.

Random Access Memory (RAM)


A type of semiconductor memory that is normally
used by the microprocessor during normal
operation that permits rapid retrieval and storage
of programs and data. See also Read Only
Memory (ROM) and NonVolatile Memory (NVM).

Rate
Leak Class
Defines the allowable leakage by a valve when it is
closed. Leak class numbers are listed in two
standards: ANSI/FCI 702 and IEC 5344.

Linearity, dynamic
Linearity (independent) is the maximum
deviation from a straight line best fit to the
opening and closing curves and a line
representing the average value of those curves.

Memory
A type of semiconductor used for storing
programs or data. FIELDVUE instruments use
three types of memory: Random Access Memory
(RAM), Read Only Memory (ROM), and
NonVolatile Memory (NVM).

NonVolatile Memory (NVM)


A type of semiconductor memory that retains its
contents even though power is disconnected.
NVM contents can be changed during
configuration unlike ROM which can be changed
only at time of instrument manufacture. NVM
stores configuration restart data.

Amount of change in output proportional to the


rate of change in input.

ReadOnly Memory (ROM)


A memory in which information is stored at the
time of instrument manufacture. You can
examine but not change ROM contents.

Seat Load
Force exerted on the valve seat, typically
expressed in pounds force per lineal inch of port
circumference. Seat load is determined by shutoff
requirements.

Software
Computer programs, procedures, and possibly
associated documentation and data pertaining to
the operation of a computer system.

Temperature Sensor
A device within the FIELDVUE instrument that
measures the instrument's internal temperature.

Travel
Movement of the valve stem or shaft which
changes the amount the valve is open or closed.

Octet
See byte

Parallel
Simultaneous: said of data transmission on two or
more channels at the same time.

322

Travel Sensor
A device within the FIELDVUE instrument that
senses valve stem or shaft movement. The travel
sensor in the DVC6200f is the Hall Effect sensor
that measures the position of the magnet
assembly.

Instruction Manual

Glossary

D103412X012

Travel Sensor Motion


Increasing or decreasing air pressure causes the
magnet assembly to move up or down or the
rotary shaft to turn clockwise or
counterclockwise. Device Setup asks if it can
move the valve to determine travel.

Tuning
The adjustment of control terms or parameter
values to produce a desired control effect.

Tuning Set
Preset values that identify gain and rate settings
for a FIELDVUE instrument. The tuning set and
supply pressure together determine an
instrument's response to input signal changes.

August 2012

Watch Dog Timer


A timer that the microprocessor must pulse
periodically. If the microprocessor is unable to
pulse the timer, the instrument shuts down.

Zero Power Condition


The position of the valve (open or closed) when
the electrical segment power to the instrument is
removed. Zero Power Condition (ZPC) is
determined by relay and actuator action where:
for Relay A and C, Port A will be at atmosphere
pressure, and if doubleacting, Port B will be at
supply pressure. For Relay B, Port B will be at
supply pressure.

323

Glossary
August 2012

324

Instruction Manual
D103412X012

Instruction Manual

Index

D103412X012

Index
A
Acknowledge Option, Resource Block, 48
Act On IR, 131
Action on Failure, DI Function Block, 205
Action on Fault Detection
AO Function Block, 118
DO Function Block, 194
Active PlantWeb Alerts, 224
Actuator
Fail Action, 83
Manufacturer, 83
Model Number, 83
Serial Number, 83
Size, 83
Style, 83
Device Setup, 42
Actuator Compatibility, 8
Actuator Information, for initial setup, 41
Advanced Diagnostics (AD), 4
Air, 84
as supply medium, 7, 27
Alarm Detection
AI Function Block, 171
DI Function Block, 205
ISEL Function Block, 151
PID Function Block, 131
Alarm Handling, 47
Alarm Priorities
ISEL Function Block, 152
PID Function Block, 132
Alert Conditions, 224
Instrument, 69

August 2012

Alerts
Configuration, 71
Electronics, 69
Environment, 73
Instrument, 69
Performance, 79
PlantWeb, 69
Proximity, 76
Sensor, 72
Travel, 74
AMS Device Manager, using, 310
Analog Input (AI) Function Block, 5, 171
Advanced Features, 175
Alarm Detection, 171
Block Errors, 175
Field Communicator Menu Structure, 182
Filtering, 174
Modes, 171
parameters, 176
Signal Conversion, 174
Simulation, 175
Status Handling, 173
Troubleshooting, 176
View Lists, 180
Analog Output (AO) Function Block, 5, 113
Action on Fault Detection, 118
Application Information, 119
Block Errors, 119
Field Communicator Menu Structure, 125
I/O Options, 118
Mode Handling, 115
parameters, 120
Set Point Selection and Limiting, 117
Setting the Output, 116
Simulation, 119
Status Handling, 116
View Lists, 124
ANSI/ISA75.13.01 Section 5.3.5, Vibration Testing
Method, 8
AO Control - PreCharacterization, Device Variables,
230
AO ControlPost Characterization, Device Variables,
230

Alert Handling, 86
PlantWeb Alert Handling, 86
PlantWeb Alert Simulate, 86
PlantWeb Alerts, 275
Simulate Active Alerts, 86

Application Information
AO Function Block, 119
DI Function Block, 206
MAI Function Block, 184
PID Function Block, 132

Alert Key, 72

Area Units, 81

Alert Reporting, PlantWeb Alerts, 277

ATEX, 8

325

Instruction Manual

Index
August 2012

Auto Calibration, 214

D103412X012

Supply Pressure Sensor, 216


Calibration Date, 81

B
Backup Link Master, 7
Basic Setup, 39
Bench Set
Lower, 84
Upper, 84
Block Alarm, Resource Block, 221
Block Alarm Auto Acknowledge, Resource Block, 48
Block Alarm Disabled, Resource Block, 48
Block Error
Resource Block, 220
Transducer Block, 227
Block Error Reporting, 86
Block Errors, 86
AI Function Block, 175
AO Function Block, 119
DI Function Block, 205
DO Function Block, 194
ISEL Function Block, 152
MAI Function Block, 184
PID Function Block, 132
Resource Block, 49
Block Execution Times, 7
Block Initialization
DI Function Block, 202
DO Function Block, 192

Calibration Location, 81
Calibration Person, 81
Certification
INMETRO, Brazil, 8
KGS, Korea, 8
NEPSI, China, 8
TIIS, Japan, 8
Clear Fault State, Resource Block, 222
Commissioning Tag, 37
Communication Connections, 36
Communication Time Out, 46
Shed Remote Cascade, 46
Shed Remote Out, 46
Configuration Alerts, 71, 224
Alert Key, 72
Blocks Set to Default, 72, 225
Output Block Timeout, 71, 224
Configure/Setup, 45
Confirm Time, 48
Connections
Communications, 36
Pneumatic, 26
Pressure, 26
Supply, 27
Specifications, 8
Vent, 30
Wiring and Electrical, 31
Fieldbus, 31

Block Modes, 289


All, Device Variables, 229
DVC6200f, 289

Construction Materials, 9

Blocks
Function, 5
Resource Block, 5
Transducer Block, 5

CSA, 8

Blocks Set to Default, Alerts, 72

C
Calibration, 213
Auto, 214
Manual, 214
Pressure A or B Sensor, 217
Relay, 215

326

control options, PID Function Block, 130


Control selections, 4
Custom Characterization, 68
Cycle Counter
Alerts, 78
Device Variables, 231

D
DD Information, 223
Declaration of SEP, 9
DeltaV ProfessionalPLUS Workstation, Installing DD
on, 298

Instruction Manual

Index

D103412X012

DeltaV System
operating with, 303
Software Functionality/System Requirements, 310
DeltaV Tune, for PID control loops, 132
Detailed Setup, 62
Device Addressing, 293
Device Communication, 294
Scheduled Transfers, 294
Unscheduled Transfers, 295
Device Description, Overview, 297
Device Description Version, displaying, 301
Device Descriptions, 291
Installing on a DeltaV ProfessionalPLUS Workstation,
298
Installing on Other Fieldbus Host Systems, 300
Device Diagnostics
Resource Block, 220
Transducer Block, 224
Device ID, 37, 48, 222
Device Revision, 49, 223
Device Setup, 40
Device State, Resource Block, 220
Device Type, 48, 223
Device Variables
Resource Block, 222
Transducer Block, 229
diagnostic capabilities, 4
Diagnostic Options, 46, 49, 223

August 2012

Modes, 202
parameters, 206
Simulation, 205
Status Handling, 202
View Lists, 210
Discrete Output (DO) Function Block, 5, 189
Action on Fault Detection, 194
Block Errors, 194
Block Initialization, 192
I/O Selection, 192
Mode Handling, 191
Modes, 190
Output Block PV Status, 193
parameters, 195
Setting the Output, 192
Shed Options RCAS Mode Only, 191
Simulation, 194
Status Handling, 192
View Lists, 199
DO Control, Device Variables, 230
DoubleActing Relay, calibration, 215
Drive Current, Alerts, 69
Drive Signal
Alerts, 70
Device Variables, 231
DVC6205 base unit, 14

E
Educational Services, 10
Effective Area, 84

Direct Action, PID Function Block, 131

Electrical Classification
Electrical Housing, 8
Hazardous Area Approvals, 8

Direct Selection of Inputs, ISEL Function Block, 151

Electrical Housing, 8

Direct signal conversion, AI Function Block, 174

Electromagnetic Compatibility, Specification, 8

Disabling Inputs, ISEL Function Block, 150

Electronics Alerts, 69, 224


Drive Current, 69, 224
Drive Signal, 70, 224
Processor Impaired, 70, 224

Digital Communication Protocol, 7

Discrete Alarm Auto Acknowledge, 48


Discrete Alarm Disabled, 48
Discrete Input (DI) Function Block, 5, 201
Action on Failure, 205
Alarm Detection, 205
Application Information, 206
Block Errors, 205
Block Initialization, 202
Field Value Processing, 204
I/O Selection, 202

Electronics Serial Number, 48, 222


EMC Summary ResultsImmunity, 9
EN 61326-1 (First Edition), 8
Enable Jumper, Simulate, 36
Environment Alerts, 73, 225
Supply Pressure, 73, 225
Temperature Limit, 74, 225

327

Instruction Manual

Index
August 2012

Expert tuning, 43
Pressure, 66
Travel, 63

F
Factory Serial Number, 48, 222

D103412X012

Function Blocks, 5
Analog Input (AI), 5, 171
Analog Output (AO), 5, 113
Discrete Input (DI), 201
Discrete Output (DO), 5, 189
Input Selector (ISEL), 5
Multiple Analog Input (MAI), 5, 183
Output Splitter (OS), 5, 160
Proportional-Integral-Derivative (PID), 5, 126

Fail Action, Actuator, 83


Fault State, Resource Block, 222
Features Available, 47
Features Selected, 47
Feedback Connection Options, 83

G
Gain Values, preselected tuning sets, 43
Gas Certified, DVC6200f, 8, 27
Gauges, Pipe Plugs, or Tire Valves, maintenance, 241

Feedforward Calculation, PID Function Block, 130


Field Communicator Menu Structure
AI Function Block, 182
AO Function Block, 125
DO Function Block, 200
ISEL Function Block, 159
MAI Function Block, 188
OS Function Block, 170

H
Hardware Revision, 49, 223

Field Serial Number, 48, 222

Hazardous Area Approvals, 8


ATEX, 8
CSA, 8
FM, 8
IECEx, 8

Field Value Processing, DI Function Block, 204

Humidity Testing, Method, 8

Fieldbus Connections, 31
Quick Connect Cable Entry, 33
Twisted Shielded Pair, 32

Fieldbus Control (FC), 4

I/O Options, AO Function Block, 118

Fieldbus Diagnostics (FD), 4

I/O Selection
DI Function Block, 202
DO Function Block, 192

Fieldbus Installation and Wiring Guidelines, 10


Fieldbus Logic (FL), 4
Fieldbus Wiring, connecting, 31
Filtering
AI Function Block, 174
PID Function Block, 130

I/P Converter
maintenance, 237
removing, 238
replacing, 238
I/P Filter, replacing, 237

Firmware Revision, 49, 223

Identification of Selected Inputs, ISEL Function Block,


151

Flow Direction, 82

IEC 61514-2, humidity testing method, 8

FM, 8

IECEx, 8

Function Block
Input Selector (ISEL), 145
Overview, 287

Independent Linearity, Specification, 8

Function Block Options, 46, 223


Function Block Scheduling, 296

328

Indirect signal conversion, AI Function Block, 174


Indirect Square Root, AI Function Block, 174
Initialization and Back Calculation Requirements, OS
Function Block, 165

Instruction Manual

Index

D103412X012

August 2012

INMETRO, Brazil, Certification, 8

Link Active Scheduler (LAS), 293

Input Characterization, 67
Device Variables, 230

linkageless, noncontacting position measurement,


12

Input Selection, ISEL Function Block, 150

Lower Bench Set, 84

Input Selector (ISEL) Function Block, 5, 145


Alarm Detection, 151
Alarm Priorities, 152
Block Errors, 152
Field Communicator Menu Structure, 159
Input Selection, 150
Direct Selection of Inputs, 151
Disabling Inputs, 150
Identification of Selected Inputs, 151
Modes, 145
parameters, 152
Status Handling, 146
Limit Propagation, 147
Quality Use and Propagation, 146
STATUS_OPTS Supported, 150
Substatus Propagation, 147
View Lists, 157
Input to Output Mapping, OS Function Block, 163
Installation, 11
Instrument Alert, Conditions, 275
Instrument Alert Conditions, 69, 224
ITK Version, 49, 223

K
KGS, Korea, Certification, 8

M
magnet assemblies, 13
linear, 12
magnet assembly
material, 12
travel range, 12
Magnetic Feedback Assembly, replacing, 234
Magnetic Tools, use of, 12, 17
Magnets, high power, 12, 17
MAI Channel Map, 85
MAI Function Block, parameters, 185
Maintenance
Gauges, Pipe Plugs, or Tire Valves, 241
I/P Converter, 237
Module Base, 234, 235
Pneumatic Relay, 240
PWB Assembly, 239
Resource Block, 221
Terminal Box, 241
Tools Required, 234
Fieldbus Connections with Twisted Shielded Pair, 32
Manual Calibration, 214
Manufacturer Identification, 48, 223
Maximum Notify, 48

L
Last Calibration Type, 81
Leak Class, 82
Length Units, 81
Lever Arm Length, 84
Lever Style, 84
Lightning and Surge Protection, 8
Limit Handling, OS Function Block, 163
Limit Notify, 48
Limit Propagation
ISEL Function Block, 147
Transducer Block, 292

Maximum Output Capacity, Specification, 7


Maximum Recorded Supply Pressure, 228
Maximum Recorded Supply Pressure Time, 228
Maximum Recorded Temperature, 228
Maximum Recorded Temperature Time, 228
Maximum Supply Pressure, 81
Methods, 298
Minimum Recorded Supply Pressure, 228
Minimum Recorded Supply Pressure Time, 228
Minimum Recorded Temperature, 228
Minimum Recorded Temperature Time, 228
Miscellaneous Options, 47, 223

329

Instruction Manual

Index
August 2012

Mode Handling
AO Function Block, 115
DO Function Block, 191
PID Function Block, 128
Modes
AI Function Block, 171
AO Function Block, 114
Blocks, 289
DI Function Block, 202
DO Function Block, 190
Explanation of, 290
ISEL Function Block, 145
MAI Function Block, 183
OS Function Block, 161
PID Function Block, 128
Resource Block, 45
Transducer Block, 62
Module Base
removing, 235
replacing, 236

D103412X012

O
Open/Closed Limit Switch, Channel 24 and 25, DI
Function Block, 203
Options, 9
Resource Block
Diagnostic, 46
Features Available, 47
Features Selected, 47
Function Block, 46
Miscellaneous, 47
Outblock Selection, 69
Output Block PV Status, 85
AO Function Block, 117
DO Function Block, 193
Output Block Timeout, Alerts, 71
Output Connection, 28
Output Selection and Limiting, PID Function Block, 130
Output Signal, Specifications, 7

Mounting
67CFR, 26
DVC6200f, 11
DVC6205 base unit
Pipestand, 14
Wall, 14
DVC6215 feedback unit, 16
Troubleshooting, 243

Output Splitter (OS) Function Block, 5, 160


Field Communicator Menu Structure, 170
Initialization and Back Calculation Requirements,
165
Modes, 161
parameters, 167
Status Handling, 162
View Lists, 169

mounting brackets, for DVC6200f, 13

Output Tracking, PID Function Block, 130

mounting instructions, 13, 14


mounting kits, DVC6200f, 13
Multiple Analog Input (MAI) Function Block, 5, 183
Application Information, 184
Field Communicator Menu Structure, 188
Modes, 183
Status Handling, 183
View Lists, 187

P
Parameters
AI Function Block, 176
AO Function Block, 120
DI Function Block, 206
DO Function Block, 195
ISEL Function Block, 152
MAI Function Block, 185
OS Function Block, 167
PID Function Block, 133
Resource Block, 54
Transducer Block, 87

natural gas, as supply medium, 7, 8, 27, 233

Parts Kits, 249

NEPSI, China, Certification, 8

Parts List, 250

Network Communication, 293

Parts Ordering, 249

Network Management, 296


Nominal Supply Pressure, 84

330

PD Inside Status
Alert, 79
Device Variables, 231

Instruction Manual

Index

D103412X012

PD Run, Alert, 80
Performance Alerts, 79, 226
PD Inside Status, 79
PD Run, 80
Performance Critical, 80, 226
Performance Information, 80
Performance Reduced, 80
Performance Critical, Alerts, 80

August 2012

Performance, 79
Proximity, 76
Sensor, 72
Set Block Status, 277
Setting, 277
Travel, 74
Travel History, 78
Using, 277, 281
PlantWeb Alerts Set PV Status, 86

Performance Diagnostics (PD), 4

Pneumatic Connections, 26

Performance Information, Alerts, 80

Pneumatic Relay
removing, 240
replacing, 240

Performance Reduced, Alerts, 80


Performance Tuner, 43, 44, 64
PID Equation Structures for Enhanced PID Block, 131
PID Function Block, 126
Alarm Detection, 131
Alarm Priorities, 132
Application Information, 132
Block Errors, 132
Feedforward Calculation, 130
Filtering, 130
Mode Handling, 128
Modes, 128
Output Selection and Limiting, 130
Output Tracking, 130
parameters, 133
Reverse and Direct Action, 131
Set Point Tracking, 130
Status Handling, 129
PlantWeb Alert Enable, 80
Advise Enable, 80
Failed Enable, 80
Maintenance Enable, 80
PlantWeb Alert Handling, Alert Handling, 86
PlantWeb Alert Reporting, 80
Advise Suppress, 81
Failed Suppress, 80
Maintenance Suppress, 80

Port Diameter, 82
Port Type, 82
Pressure, Connections, 26
Pressure A or B Sensor, calibration, 217
Pressure Cutoff Closed, 67
Pressure Cutoff Open, 67
Pressure Fallback, Alerts, 73
Pressure Fallback Auto Recovery, 66
Pressure Fallback Manual Recovery, 66
Pressure Integral Dead Zone, 66
Pressure Integral Gain, 66
Pressure Integral Limit Hi, 66
Pressure Integral Limit Lo, 66
Pressure MLFB Gain, 66
Pressure Proportional Gain, 66
Pressure Range Hi, 67
Pressure Range Lo, 67
Pressure Sensors, Alerts, 72
Pressure Tuning, 65
Pressure Tuning Set, 65

PlantWeb Alert Simulate, Alert Handling, 86

Pressure Tuning Sets, Gain Values, 66

PlantWeb Alerts, 69
Alert Handling, 275
Alert Reporting, 277
Conditions, 275
Configuration, 71
Electronics, 69
Environment, 73
in a DeltaV System, 315
Mode-Based, 275

Pressure Units, 81
Pressures, 232
Principle of Operation, Block Diagram, 259
Printed Wiring Board (PWB) Assembly
removing, 239
replacing, 239
Processor Impaired, Alerts, 70

331

Instruction Manual

Index
August 2012

ProportionalIntegralDerivative (PID) Function Block,


5
Protection, 39, 62
Device Variables, 231
Proximity, Alerts, 77
Proximity Alerts, 76, 225
Proximity, 77, 226
Travel, 76
Travel Closed, 77, 226
Travel Open, 77, 225
Push Down To, 82

D103412X012

Set Fault State, 222


Strategy, 222
Tag Description, 222
View Lists, 61
Device Diagnostics, 220
Write Lock, 220
Resource Block (RB)
Menu Structure, 272
Menu Tree, 273
Resource Block Error, 220
Resource Block Mode, 45
Response Control, 63

Restart Actions, Resource Block, 221

Quality Use and Propagation, ISEL Function Block, 146

Restart Processor, Resource Block, 222

Quick Connect Cable Entry, 33

Restart with Defaults


parameters affected by, 50
Resource Block, 222

R
Regulator (67CFR), 26
Casing-Mounted, 26
Integral-Mounted, 26
Yoke-Mounted, 26
Related Documents, 10
Relay, calibration, 215
Relay A, 215
Relay B, 40, 215, 216
Relay C, 215, 216
Relay Type, 81
Remote Travel Sensor Connections, 34
remote vent, 30
Resource Block, 288
Block Alarm, 221
Block Errors, 49
Clear Fault State, 222
Device State, 220
Device Variables, 222
Options
Diagnostic, 223
Features Available, 223
Function Block, 223
Miscellaneous, 223
Overview, 45
parameters, 54
Restart Actions, 221

332

Reverse Action, PID Function Block, 131

S
Scheduled Transfers, Device Communication, 294
Seat Type, 82
Self Test Status, 226
Sensor Alerts, 72, 225
Pressure Fallback, 73, 225
Pressure Sensors, 72, 225
Temperature Sensor, 225
Travel Sensor, 225
Travel Sensor Alert, 72
Serial Number
Actuator, 83
Electronics, 48, 222
Factory, 48, 222
Field, 48, 222
Valve, 82
Set Block Status, PlantWeb Alerts, 277
Set Fault State, Resource Block, 222
Set Point Selection and Limiting, AO Function Block,
117
Set Point Tracking, PID Function Block, 130

Instruction Manual

Index

D103412X012

August 2012

Setting the Output


AO Function Block, 116
DO Function Block, 192
Output Block PV Status, AO Function Block, 117

Steady-State Air Consumption, Specifications, 7

Shed Options RCAS Mode Only, DO Function Block,


191

Stroking Time Close, 84

Shed OptionsRCAS Mode Only


AO Function Block, 115
PID Function Block, 128

Substatus Propagation, ISEL Function Block, 147

Signal Conversion, AI Function Block, 174


Simulate Active Alerts, Alert Handling, 86
SIMULATE ENABLE terminals, 36
Simulation
AI Function Block, 175
AO Function Block, 119
DI Function Block, 205
DO Function Block, 194
SingleActing Relays, calibration, 216
Solenoid Valve Testing, Special Construction to
Support Testing, 29
SP Track retained Target, 130
SP-PV Track in LO or IMan, 130
SP-PV Track in Man, 130
SP-PV Track in ROUT, 130
Special Instructions for Safe Use and Installations in
Hazardous Locations, 11

Strategy, Resource Block, 48, 222


Stroking the Digital Valve Controller Output, 242
Stroking Time Open, 84
Supply, Connections, 27
Output, 28
Supply Pressure
Alerts, 73
Maximum, 81
Maximum Recorded, 228
Minimum Recorded, 228
Specifications, 7
Supply Pressure Sensor, calibration, 216

T
Tag Description
Resource Block, 48, 222
Transducer Block, 81
Temperature
Device Variables, 231
Maximum Recorded, 228
Minimum Recorded, 228
Temperature Limit, Alerts, 74

Specifications, DVC6200f, 7

Temperature Limits, Operating Ambient, 8

Spring Rate, 84

Temperature Units, 81

Spring Rate Units, 81


Stabilize/Optimize, 43, 64

Terminal Box
removing, 241
replacing, 242

Standard Control (SC), 4

TIIS, Japan, Certification, 8

Standby Firmware Revision, 49, 223

Transducer Block, 288


Block Error, 227
Device Diagnostics, 224
Device Variables, 229
parameters, 87
Status and Limit Propagation, 291
View Lists, 110

static discharge, avoiding, 233


Status Handling
AI Function Block, 173
AO Function Block, 116
DI Function Block, 202
DO Function Block, 192
ISEL Function Block, 146
MAI Function Block, 183
OS Function Block, 162
PID Function Block, 129

Transducer Block (TB)


Menu Structure, 262
Menu Tree, 267, 268, 269, 270, 271
Transducer Block Mode, 39, 62

Status Propagation, Transducer Block, 292

Transducer Block Overview, 62

STATUS_OPTS Supported, ISEL Function Block, 150

Travel, Alert, 74, 76

333

Instruction Manual

Index
August 2012

D103412X012

Travel Accumulator
Alerts, 78
Device Variables, 231

Travel/Pressure State, 66
Device Variables, 231

Travel Alerts, 74, 225


Travel, 74
Travel Deviation, 74, 225
Travel Hi/Lo, 76, 225
Travel Limit, 75, 225
Travel Target, 74

Trim Style 1, 84

Travel Closed, Alerts, 77


Travel Count, Device Variables, 231
Travel Cutoff Hi, 67
Travel Cutoff Lo, 67
Travel Deviation, Alerts, 74
Travel Deviation Pressure Fallback, 67
Travel Hi/Lo, Alerts, 76
Travel History, Alerts, 78
Travel History Alerts, 78, 226
Cycle Counter, 78, 226
Travel Accumulator, 78, 226
Travel Integral Dead Zone, 64
Travel Integral Enable, 64
Travel Integral Gain, 64
Travel Integral Limit Hi, 64
Travel Integral Limit Lo, 64

Trend, 229
Trim Style 2, 84
Troubleshooting
AI Function Block, 176
DVC6200f, 243
MAI Function Block, 184
mounting, 243
utility connections, 243
Tuning
Pressure, 65
Travel, 63
Tuning Set
Device Setup, 43
Pressure, 65
Travel, 63
Tuning Set B, 43
Tuning Sets, Gain Values, 43

U
Unbalanced Area, 82
Unscheduled Transfers, Device Communication, 295
Upper Bench Set, 84
Utility Connections, Troubleshooting, 243

Travel Limit, Alerts, 75


Travel MLFB Gain, 64
Travel Open, Alerts, 77
Travel Pressure Control, 66
Travel Proportional Gain, 64
Travel Sensor, Alerts, 72
Travel Sensor Motion, 83, 84
Device Setup, 42
Travel Target, Alert, 74
Travel Tuning, 63
Travel Tuning Set, 63
Travel Tuning Sets, Gain Values, 63
Travel Units, 81

V
Valve
Actual Travel, 82
Class, 82
Inlet Pressure, 82
Manufacturer, 82
Model Number, 82
Outlet Pressure, 82
Packing Type, 82
Serial Number, 82
Shaft Stem Diameter, 82
Size, 82
Style, 82
Device Setup, 42

Travel Velocity Gain, 64

Valve Position Proximity Detection, Channels 30-33, DI


Function Block, 203

Travel/Pressure Select, 66

Valve Travel, Channel 23, DI Function Block, 202

334

Instruction Manual

Index

D103412X012

Variable Limit Switch, Channels 26-29, DI Function


Block, 203
Vent, 30
Vibration Testing, Method, 8

August 2012

W
Weight
DVC6200f, 8
DVC6205f, 8
DVC6215, 8

View / Edit Feedback Connection, 83

Wiring and Electrical Connections, 31

View Lists, 219


AI Function Block, 180
Analog Output (AO) Function Block, 124
DI Function Block, 210
DO Function Block, 199
ISEL Function Block, 157
MAI Function Block, 187
OS Function Block, 169
PID Function Block, 141
Resource Block, 61
Transducer Block, 110

Write Alarm, 48
Write Lock, 45
Resource Block, 220
Write Lock, 45
Write Priority, 46

Z
Zero Power Condition, 81
Device Setup, 42

335

Index
August 2012

336

Instruction Manual
D103412X012

N97

Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, ValveLink, PlantWeb, DeltaV, and Baumann are marks owned by one of the companies in the Emerson Process Management business unit
of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.
FOUNDATION fieldbus is a mark owned by the Fieldbus Foundation. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore

www.Fisher.com
2010, 2012 Fisher Controls International LLC. All rights reserved.

You might also like