TIP Catalogue 2011
TIP Catalogue 2011
TIP Catalogue 2011
Catalogue - 2011
Related Catalogues
3VL MCCB
Modular, Compact,
Communication-Capable
Underfloor Busbar
BT LV Portfolio
The Complete Portfolio for
Low-Voltage Power Distribution
Safe, cost-efficient and flexible
LX Busbar engineering
guide
LV72 2005
Small/medium Power
Busbars
LV70 2011
BT LV TIP Shortform Catalogue - 2011
ACB/MCCB
Automatic Transfer Control device
BT LV Portfolio
Busbar catalogues
Busbar Installation Instructions
Busbar Installation Videos
Energy Management
LV Circuit protection & Distribution boards
LV56
LV Switchgear
Power Management
Underfloor Busbar
TIP shortform catalogue 2011
Catalogue 2011/12
LX Busbar System
Underfloor Busbar
Power Management
devices/software
S4 Switchgear
10
11
1.1
1
1
Typical Specification
The following is intended as a guide to specifying CD-K Busbar Trunking:
All lighting busbar trunking shall be approved manufacture and comply
with degree of protection IP54 as defined in BSEN 60439. The current rating
shall be defined on the drawings and schedules but will be typically 25A,
32A & 40A, 4pole or 8pole.
The system shall be totally enclosed. The trunking shall be suitable for
use on a 400v 1, 2, 3, 4 phase (2, 3, 4 wire; PE = housing), 50/60 Hz
supply and for the installation to meet the requirements of the IEE Wiring
Regulations BS 7671 and BSEN 60439 parts 1 & 2. The enclosure shall be
manufactured from zinc coated sheet steel, finished in white (similar to
RAL 9002), rectangular in section with flanges to the manufacturers
standard suspension and luminaire support brackets. Phase and neutral
conductors shall be tinned copper, of equal cross section, fully insulated
and supported at both the tapping outlet positions and at each end of the
trunking.
The lighting Busbar trunking shall be manufactured in 2 or 3 metre lengths
each complete with a self-aligning electrical joint sleeve, interlocked to
prevent phase reversal.
Tapping outlet positions shall be provided at 0.5 or 1 metre interval each
complete with a non removable hinged cover complete with locking screw
to ensure IP54 rating and preventing accidental contact with the live
conductors.
All end feed units, end caps, joint sleeves and tap off units shall be
manufactured from non-hygroscopic, self-extinguishing halogen-free
insulating material and designed such that IP54 degree of protection is
maintained.
Tap-off Units
Tap-offs shall be rated at 10A or 16A, 3pole or 5pole as defined on the
drawings and schedules. They shall be plug-in and designed so as to
permit phase selection on site by inserting of prewired contact blocks
into the appropriate positions. Fused or unfused tap-off units shall be
provided as required.
The lighting trunking shall be Siemens CDK brand or equal and approved.
1.2
2000/3000
30
42
1
1000
NSV0_00218
500
500
500
NSV0_00203
NSV0_00202
Feeder Units
72
53
189
53
1.3
42
L1
L2
NSV0_00234
NSV0_00221
L3
59
48
40
Tap-off plugs
59
Degree of protection
30
30
30
2 x 25
40
40
40
2 x 40
1302
1303
1304
2254
1402
1403
1404
2404
-5C to +40C
IP54; IEC/EN 60529
Mounting
Conductors
Rated Operational Voltage Ue
V~
400
400
400
400
400
400
400
400
Frequency
Hz
5060
5060
5060
5060
5060
5060
5060
5060
Amps
30
30
30
2 x 25
40
40
40
2 x 40
Resistance R20
m/m
5.79
5.79
5.79
4.56
3.55
3.55
3.55
3.69
Reactance X20
m/m
0.26
0.26
0.26
0.15
0.40
0.40
0.40
0.13
Impedance Z720
m/m
5.80
5.80
5.80
4.56
3.57
3.57
3.57
3.69
AC Resistance RF
m/m
8.24
8.24
8.24
7.50
5.61
5.61
5.61
4.17
Reactance XF
m/m
0.44
0.44
0.44
0.32
0.80
0.80
0.80
0.40
Impedance ZF
m/m
8.25
8.25
8.25
7.51
5.67
5.67
5.67
4.18
14.33
Phase to N
m/m
24.24
24.24
24.24
18.59
14.85
14.85
14.85
Reactance X0
Phase to N
m/m
1.77
1.77
1.77
0.82
0.99
0.99
0.99
0.78
Impedance Z0
Phase to N
m/m
24.30
24.30
24.30
18.61
14.88
14.88
14.88
14.33
Resistance R0
Phase to PE
m/m
12
12
12
13.49
9.87
9.87
9.87
5.15
Reactance X0
Phase to PE
m/m
1.8
1.8
1.8
0.82
1.02
1.02
1.02
0.74
Impedance Z0
Phase to PE
m/m
12.13
12.13
12.13
13.52
9.92 9.
92
9.92
5.21
kg/m
0.75
0.78
0.81
1.06
0.78
0.83
0.88
1.22
Trunking Weight
Short Circuit Rating
Rated peak withstand Ipk
kA
2.4
2.4
2.4
3.6
3.6
3.6
3.6
kA
0.56
0.56
0.56
0.69
0.85
0.85
0.85
0.85
kA
1.6
1.6
1.6
2.4
2.4
2.4
2.4
2x4
2x4
mm2
3.2
3.2
3.2
mm2
3.2
3.2
3.2
PE (enclosure) Cu
mm2
Conductor Material
11
11
11
11
11
11
11
11
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Cu
Terminal Capacities
Designation
Type
CD-K--EA
N, L1, L2, L3
Min mm2
Max mm2
Min mm2
2.5
6 (f)
2.5
6 (f)
2.5
10 (st, so)
CD-K--EE
PE
Max mm2
Min mm2
2.5
6 (f)
10 (st, so)
10 (st, so)
2.5
6 (f)
10 (st, so)
Max mm2
6 (f)
10 (st, so)
2.5
6 (f)
10 (st, so)
Notes
so = solid, st = stranded, f = flexible with ferrule
Suspension Bracket
CD-BC
1.4
2
Flexible in every direction.
2.1
2
2
Typical Specification
The following is intended as a guide to specifying BD01 Busbar Trunking:
All busbar trunking shall be of approved manufacture and comply with
degree of protection IP54 (IP55 available with accessories) as defined in
BSEN 60439 when edgewise (tap off points at the side and bottom) and
IP50 when flat (tap off points on the top). The current rating shall be defined
on the drawings and schedules but will be typically 40A to 160A. The busbar
shall be designed and manufactured to comply with BSEN 60439 parts 1 &
2. For use on a 400v, 3phase 4wire (PE = Housing), 50/60Hz supply, and
capable of withstanding prospective fault levels as detailed on the drawing
schedules. The busbar trunking shall be manufactured in 2 or 3 metre
lengths. The enclosure shall be manufactured from pale grey (RAL 7035)
painted galvanised sheet steel and is the protective earth conductor. The
busbar trunking shall have solid conductors with silver-plated aluminium
and copper connection points at all tap off outlets and joint positions. Tap
off outlets shall be spaced at 0.5 and 1 metre distance and shall have
automatic opening and closing shutters. They will also ensure correct
polarity is maintained. The joint section shall provide electrical & mechanical
connection by four screws. The joint section shall absorb any differential
expansion between the trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar run,
manufacturers purpose made fittings such as junction units, feeder units,
end flanges and centre feeds shall be used. Where detailed on the drawings
and schedules interlocking coding sets shall be installed into the tap off
outlets and tap off units to provide non-interchange ability of tap off units to
non-designated tap off outlets.
Tap off units
Tap off units shall be plug-in type suitable to accept HRC fuses, MCBs, DIN
rail mounted devices and socket outlets as detailed on the drawings and
schedules. The enclosure shall be constructed from anodised aluminium
and/or insulation material, complying to the degree of protection IP54 (IP55
available with accessories), as defined in BSEN 60439. The earth connection
of the tap off unit shall provide the opening of the automatic shutter and
make before and break after the live connections are made. Where required
tap off units shall be extendible to allow additional components to be
installed onto the internal DIN rail. The busbar trunking system shall be
Siemens BD01, Barduct brand or equal and approved.
2.2
BD01-40
BD01-63
BD01-100
BD01-125
BD01-160
Current paths
Rated Operational Voltage Ue
V~
400
400
400
400
400
Frequency
Hz
5060
5060
5060
5060
5060
A4
63
100
125
160
Resistance R20
m/m
3.960
1.936
0.938
0.910
0.578
Reactance X20
m/m
0.280
0.324
0.286
0.300
0.273
Impedance Z720
m/m
3.970
1.968
0.994
1.000
0.642
AC Resistance RF
m/m
5.991
4.128
2.841
2.420
2.189
Reactance XF
m/m
1.396
1.248
1.186
0.940
0.973
Impedance ZF
m/m
6.151
4.312
3.078
2.600
2.395
pf 0.7
2.57
1.37
0.75
0.74
0.52
mV/A/m
pf 0.8
2.89
1.51
0.80
0.79
0.54
mV/A/m
pf 0.9
3.19
1.63
0.84
0.82
0.55
mV/A/m
pf 1
3.43
1.68
0.81
0.79
0.50
Phase to N
m/m
15.904
7.911
4.115
3.810
3.167
Reactance X0
Phase to N
m/m
2.128
2.058
1.797
1.630
1.656
Impedance Z0
Phase to N
m/m
16.045
8.175
4.490
4.140
3.574
Resistance R0
Phase to PE
m/m
10.086
8.565
6.648
5.430
5.343
Reactance X0
Phase to PE
m/m
2.909
3.338
3.067
2.320
2.355
Impedance Z0
Phase to PE
m/m
10.498
9.183
7.322
5.910
5.839
kA
2.55
6.30
15.30
15.30
15.30
kA
0.58
1.15
2.50
2.50
2.50
kA
1.70
4.20
9.00
9.00
9.00
mm2
7.9
15.7
34.1
34.1
34.1
mm2
7.9
15.7
34.1
34.1
34.1
PE (enclosure) Cu
mm2
20.0
20.0
20.0
20.0
20.0
Al
Al
Al
Al
Cu
Conductor Material
Max. interval between trunking unit
edgewise
flat
1.5
1.5
1.5
1.5
1.5
Combustive Energy
kWh/m
0.76
0.76
0.76
0.76
0.76
Trunking Weight
kg/m
1.45
1.55
1.75
1.75
2.65
230 or 400
63
AC-20B
Terminal Capacities
Feeder units
Tap off units
L1, L2, L3
PE
Type
min mm2
max mm2
min mm2
max mm2
min mm2
max mm2
BD01-E
6 (e, m)
50 (m)
6 (e, m)
50 (m)
6 (e, m)
50 (m)
BD01-160-E
25 (m)
95 (m)
25 (m)
95 (m)
16 (m)
50 (m)
BD01-AK01X/ZS
BD01-AK02X/ZS3
BD01-AK02M0/A163
16 (so)
BD01-AK02M0/A323
16 (so)
BD01-AK1M1/A101
16 (so)
0.75 (so, f)
2.5 (so, f)
0.75 (so, f)
2.5 (so, f)
BD01-AK1M1/A161
17 (so)
0.75 (so, f)
2.5 (so, f)
0.75 (so, f)
2.5 (so, f)
BD01-AK1M1/A321
18 (so)
0.75 (so, f)
2.5 (so, f)
0.75 (so, f)
2.5 (so, f)
BD01-AK1M1/A...
16 (so)
16 (so)
BD01-AK1M1/A...N
16 (so)
16 (so)
16 (so)
BD01-AK1X/S14
4 (so)
16 (so)
Notes:
BD01-AK1X/S18
16 (so)
BD01-AK1X/GB...
16 (so)
16 (so)
so = solid
BD01-AK2X/F1451
16 (so)
16 (so)
st = stranded
BD01-AK2X/S27
16 (so)
BD01-AK2HX/S33
25 (f, st)
16 (so, st)
2.3
57,5
50
5,5
5,5
NSV0_00279
57
25
n 125
4,5
250
2000
500
1000
500
1000
4
2
6
3
3000
77
90
125
n a
316
NSV0_00281
L2
R
0
10
Type
L1
L2
BD01-...-R1
BD01-...-R2
500
1000
165
665
316
260
20
M63
130
150
NSV0_00283
104
1
2.4
3.1
Typical Specification
The following is intended as a guide to specifying BD2 Busbar Trunking:
All busbar trunking shall be of approved manufacture and the current
ratings detailed on the drawings and schedules typically from 160A to
1250A, and complying to degree of ingress protection IP52 defined in
BSEN 60439 and IP54 with accessories. The busbar shall be designed and
manufactured to comply with BSEN 60439 parts 1 & 2. For use on a 690v,
3phase 5wire (3L, N or half N, PE or half PE), 50/60Hz supply, and capable
of withstanding prospective fault levels as detailed on the drawing
schedules. The busbar trunking shall be manufactured in 1.25, 2.25 &
3.25 metre lengths or optional lengths from 0.5 up to 3.24 metres. The
enclosure shall be manufactured from pale grey (RAL 7035) painted
galvanised sheet steel. The busbar trunking shall have solid conductors
with nickel-plated and tinned aluminium or copper, with insulated tap off
outlets and busbar supports. Tap off outlets shall be spaced at 0.5 and 1
metre distance and shall have automatic opening and closing shutters.
They will also ensure correct polarity is maintained. The joint section
shall provide electrical and mechanical connection by four screws. The
joint section shall absorb any differential expansion between the
trunking and the conductors When a change in direction, rating or
termination occurs in a busbar run, manufacturers purpose-made
fittings such as L junction units, feeder units, end flanges and centre
feeds shall be used. When supplied as Rising Main busbar suitable fire
barriers must be fitted which meet the requirements of BSEN 60439 part
2 and of fire resistance Class S120.
Tap off units
Tap off units shall be plug-in type suitable to accept HRC and BS fuses,
MCBs, MCCBs, Switch Disconnectors, DIN rail mounted devices and
socket outlets as detailed on the drawings and schedules. The enclosure
shall be constructed from painted steel and/or insulation material,
complying to the degree of protection IP54, as defined in BSEN 60439.
The earth connection of the tap off unit shall provide the opening of the
automatic shutter and make before and break after the live connections
are made. Where required, tap off units shall be extendible to allow
additional components to be installed onto the internal DIN rail. The
busbar trunking system shall be Siemens BD2, Barduct brand or equal
and approved.
3.2
Technical Data for BD2A 5 Bar, Aluminium Conductors Load Distribution Factor = 0.5
Rated Current
Rated Voltage
Voltage Drop, Balanced Load
Conductor Characteristics
R
X
Z
Protective Conductor
R0
X0
Weight
IP Rating
Dimensions
Short Time Rating
Prospective Short Circuit Rating
Number of Trunkings
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
160
690
0.440
0.470
0.500
0.490
250
690
0.330
0.360
0.380
0.380
400
690
0.210
0.210
0.210
0.190
630
690
0.130
0.130
0.140
0.130
800
690
0.090
0.100
0.100
0.080
1000
690
0.080
0.080
0.070
0.060
0.564
0.158
0.586
0.438
0.111
0.452
0.215
0.122
0.247
0.149
0.057
0.159
0.098
0.057
0.114
0.066
0.057
0.088
m/m
m/m
kg/M
Standard
Optional
mm
kA for 1 sec
kA
1.638
0.606
5.3
IP 52
IP 54
167x68
5.5
17
1
1.279
0.516
5.8
IP 52
IP 54
167x68
10
32
1
1.059
0.518
7.5
IP 52
IP 54
167x68
16
40
1
0.492
0.303
12.3
IP 52
IP 54
167x126
26
64
1
0.438
0.280
12.4
IP 52
IP 54
167x126
32
84
1
0.408
0.273
15.8
IP 52
IP 54
167x126
34
90
1
Technical Data for BD2C 5 Bar, Copper Conductors Load Distribution Factor = 0.5
Rated Current
Rated Voltage
Voltage Drop, Balanced Load
A
VAC
mV/A/m
Conductor Characteristics
R
X
Z
Protective Conductor
R0
X0
Weight
IP Rating
Dimensions
Short Time Rating
Prospective Short Circuit Rating
Number of Trunkings
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
160
690
0.300
0.310
0.320
0.290
250
690
0.330
0.350
0.360
0.330
400
690
0.220
0.230
0.230
0.210
630
690
0.120
0.130
0.140
0.130
800
690
0.070
0.070
0.070
0.060
1000
690
0.070
0.070
0.070
0.060
1250
690
0.060
0.060
0.050
0.040
0.333
0.157
0.368
0.383
0.158
0.414
0.239
0.115
0.266
0.151
0.053
0.160
0.065
0.053
0.084
0.068
0.053
0.086
0.041
0.054
0.068
m/m
m/m
kg/M
Standard
Optional
mm
kA for 1 sec
kA
1.027
0.641
7.3
IP 52
IP 54
167x68
5.5
17
1
1.139
0.529
7.5
IP 52
IP 54
167x68
10
32
1
0.956
0.507
9.5
IP 52
IP 54
167x68
16
40
1
0.470
0.277
15.6
IP 52
IP 54
167x126
26
64
1
0.258
0.265
18.9
IP 52
IP 54
167x126
32
84
1
0.270
0.249
25.1
IP 52
IP 54
167x126
34
90
1
0.174
0.265
37.6
IP 52
IP54
167x126
34
90
1
15
Fixing bracket
M32
314
M40 M32
34
169
199
M20
M25
205
7,2
100
320
3.3
11
7,2
c1
NSV0_00625a
33
77
50
50
101
354
NSV0_00658
20
A
VAC
mV/A/m
330
163
167
307
NSV0_00591a
220
n 500
Length
L-junction units
BD2.--LV(-G*), BD2.--LH(-G*)
G* = 85 175
NSV0_00593
x = 3601250
70
x = 3601250
NSV0_00592
70
G* = 85 175
y = 3601250
y = 3601250
c / mm
1 boxes
Cabling
100
BD2-400-EE
105
290
270
245
163
200
40 64
270
20
14 9
75
300
143,5
74
40 64
BD2-250-EE
423
100
250
563
NSV0_00607
85
219
395
420
440
478
163
200
200
605
687
387,5
14 9
NSV0_00608a
3.4
4.1
Typical Specification
The following is intended as a guide to specifying LX Busbar Trunking:
4.2
A
V~
mV/A/m
Conductor Characteristics
R
X
Z
Weight
IP Rating
Dimensions
Short Time Rating
(phase conductors only)
Prospective Short Circuit Rating
800
690
0.212
0.231
0.249
0.253
1000
690
0.167
0.179
0.189
0.184
1250
690
0.115
0.122
0.127
0.121
1600
690
0.073
0.077
0.080
0.074
2000
690
0.052
0.056
0.060
0.059
2500
690
0.048
0.050
0.052
0.048
3200
690
0.037
0.039
0.040
0.038
4000
690
0.027
0.029
0.030
0.029
4500
690
0.024
0.026
0.026
0.024
0.146
0.028
0.149
10.6
IP54
IP55
145x137
25
0.106
0.031
0.110
12.0
IP54
IP55
145x137
35
0.070
0.024
0.074
15.2
IP54
IP55
145x162
50
0.043
0.017
0.046
20.8
IP54
IP55
145x207
60
0.034
0.009
0.035
25.6
IP54
IP55
145x287
75
0.028
0.011
0.030
31.3
IP54
IP55
145x287
86
0.022
0.008
0.024
42.0
IP54
IP55
145x439
100
0.017
0.005
0.018
51.3
IP54
IP55
145x599
140
0.014
0.006
0.015
63.0
IP54
IP55
145x599
150
kA
53
70
110
132
158
194
220
255
255
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
Rated Current
Rated Voltage
Voltage Drop, Balanced Load
Conductor Characteristics
R
X
Z
Weight
IP Rating
Dimensions
Short Time Rating
(phase conductors only)
Prospective Short Circuit Rating
1000
690
0.134
0.143
0.150
0.144
1250
690
0.117
0.122
0.125
0.113
1400
690
0.091
0.097
0.101
0.095
1600
690
0.087
0.089
0.090
0.078
2000
690
0.059
0.062
0.064
0.061
2500
690
0.037
0.038
0.040
0.036
3200
690
0.033
0.034
0.033
0.028
4000
690
0.027
0.028
0.028
0.024
5000
690
0.020
0.020
0.021
0.019
6300
690
0.017
0.017
0.017
0.014
0.083
0.027
0.087
17.9
IP54
IP55
145x137
46
0.065
0.031
0.072
21.6
IP54
IP55
145x137
50
0.055
0.020
0.059
24.1
IP54
IP55
145x162
57
0.045
0.026
0.051
29.7
IP54
IP55
145x162
65
0.035
0.013
0.037
35.3
IP54
IP55
145x207
75
0.021
0.009
0.022
55.2
IP54
IP55
145x287
95
0.016
0.011
0.019
70.6
IP54
IP55
145x287
100
0.014
0.008
0.016
88.9
IP54
IP55
145x439
150
0.011
0.005
0.012
110.5
IP54
IP55
145x599
150
0.008
0.005
0.010
141.2
IP54
IP55
145x674
150
kA
96.6
110
125
143
165
209
220
255
255
255
A
V~
mV/A/m
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
A
V~
mV/A/m
Conductor Characteristics
R
X
Z
Weight
IP Rating
Dimensions
Short Time Rating
(phase conductors only)
Prospective Short Circuit Rating
800
690
0.211
0.231
0.248
0.252
1000
690
0.166
0.179
0.188
0.183
1250
690
0.114
0.121
0.127
0.121
1600
690
0.073
0.077
0.079
0.074
2000
690
0.052
0.056
0.059
0.058
2500
690
0.047
0.050
0.051
0.048
3200
690
0.036
0.038
0.040
0.038
4000
690
0.026
0.028
0.030
0.029
4500
690
0.024
0.025
0.026
0.024
0.146
0.028
0.149
11.6
IP54
IP55
145x137
25
0.106
0.031
0.110
13.3
IP54
IP55
145x137
35
0.070
0.024
0.074
17.0
IP54
IP55
145x162
50
0.043
0.017
0.046
23.8
IP54
IP55
145x207
60
0.034
0.009
0.029
29.3
IP54
IP55
145x287
75
0.028
0.011
0.025
36.3
IP54
IP55
145x287
86
0.022
0.008
0.024
48.5
IP54
IP55
145x439
100
0.017
0.005
0.018
59.2
IP54
IP55
145x599
140
0.014
0.006
0.015
73.2
IP54
IP55
145x599
150
kA
53
70
110
132
158
194
220
255
255
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
Conductor Characteristics
R
X
Z
Weight
IP Rating
Dimensions
Short Time Rating
(phase conductors only)
Prospective Short Circuit Rating
4.3
A
V~
mV/A/m
pf = 0.7
pf = 0.8
1000
690
0.134
0.143
1250
690
0.117
0.122
1400
690
0.091
0.096
1600
690
0.086
0.089
2000
690
0.058
0.062
2500
690
0.036
0.038
3200
690
0.033
0.033
4000
690
0.026
0.027
5000
690
0.019
0.020
6300
690
0.017
0.017
pf = 0.9
pf = 1.0
0.149
0.143
0.124
0.112
0.100
0.095
0.089
0.077
0.064
0.060
0.039
0.036
0.033
0.027
0.027
0.024
0.020
0.019
0.017
0.014
0.083
0.027
0.087
20.7
IP54
IP55
145x137
46
0.065
0.031
0.072
25.3
IP54
IP55
145x137
50
0.055
0.020
0.059
28.2
IP54
IP55
145x162
57
0.045
0.026
0.051
35.2
IP54
IP55
145x162
65
0.035
0.013
0.037
41.9
IP54
IP55
145x207
75
0.021
0.009
0.022
66.3
IP54
IP55
145x287
95
0.016
0.011
0.019
85.5
IP54
IP55
145x287
100
0.014
0.008
0.016
107.2
IP54
IP55
145x439
150
0.011
0.005
0.012
133.2
IP54
IP55
145x599
150
0.008
0.005
0.010
171.0
IP54
IP55
145x674
150
kA
96.6
110
125
143
165
209
220
255
255
255
350 x 350mm
1000-1600A
350 x 350mm
Standard 90 degree bends. Customised versions available on request to suit site measurements.
A
V~
mV/A/m
Conductor Characteristics
R
X
Z
Weight
IP Rating
Dimensions
Short Time Rating
(phase conductors only)
Prospective Short Circuit Rating
800
690
0.211
0.231
0.248
0.252
1000
690
0.166
0.179
0.188
0.183
1250
690
0.114
0.121
0.127
0.121
1600
690
0.073
0.077
0.079
0.074
2000
690
0.052
0.056
0.059
0.058
2500
690
0.047
0.050
0.051
0.048
3200
690
0.036
0.038
0.040
0.038
4000
690
0.026
0.028
0.030
0.029
4500
690
0.024
0.025
0.026
0.024
0.146
0.028
0.149
12.6
IP54
IP55
145x137
25
0.106
0.031
0.110
14.7
IP54
IP55
145x137
35
0.070
0.024
0.074
18.9
IP54
IP55
145x162
50
0.043
0.017
0.046
26.8
IP54
IP55
145x207
60
0.034
0.009
0.029
33.1
IP54
IP55
145x287
75
0.028
0.011
0.025
41.3
IP54
IP55
145x287
86
0.022
0.008
0.024
55.0
IP54
IP55
145x439
100
0.017
0.005
0.018
67.2
IP54
IP55
145x599
140
0.014
0.006
0.015
83.7
IP54
IP55
145x599
150
kA
53
70
110
132
158
194
220
255
255
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
Conductor Characteristics
R
X
Z
Weight
IP Rating
Dimensions
Short Time Rating
(phase conductors only)
Prospective Short Circuit Rating
A
V~
mV/A/m
1000
690
0.134
0.143
0.149
0.143
1250
690
0.117
0.122
0.124
0.112
1400
690
0.091
0.096
0.100
0.095
1600
690
0.086
0.089
0.089
0.077
2000
690
0.058
0.062
0.064
0.060
2500
690
0.036
0.038
0.039
0.036
3200
690
0.033
0.033
0.033
0.027
4000
690
0.026
0.027
0.027
0.024
5000
690
0.019
0.020
0.020
0.019
6300
690
0.017
0.017
0.017
0.014
0.083
0.027
0.087
23.5
IP54
IP55
145x137
46
0.065
0.031
0.072
29.0
IP54
IP55
145x137
50
0.055
0.020
0.059
32.4
IP54
IP55
145x162
57
0.045
0.026
0.051
40.8
IP54
IP55
145x162
65
0.035
0.013
0.037
48.6
IP54
IP55
145x207
75
0.021
0.009
0.022
77.5
IP54
IP55
145x287
95
0.016
0.011
0.019
100.4
IP54
IP55
145x287
100
0.014
0.008
0.016
125.4
IP54
IP55
145x439
150
0.011
0.005
0.012
155.9
IP54
IP55
145x599
150
0.008
0.005
0.010
200.8
IP54
IP55
145x674
150
kA
96.6
110
125
143
165
209
220
255
255
255
pf = 0.7
pf = 0.8
pf = 0.9
pf = 1.0
4.4
Compact size, high IP rating busbar can carry large current ratings
through the most difficult environments.
4 Bar
5 Bar
5.1
5
Typical Specification
The following is intended as a guide to specifying LR Cast Resin
Busbar Trunking:
All busbar systems shall be of approved manufacture and comply with
degree of protection IP68, as defined in IEC60529. The current ratings
shall be as defined on technical data sheets, drawings and schedules.
The trunking shall be suitable for use up to 1000V 50Hz supply, and
available in 4 and 5 bar versions, and meet the requirements of the IEE
wiring regulations (BS7671) and IEC60439-1 and IEC60439-2. The
enclosure shall be manufactured from an agglomerate of quartz and
epoxy. Phase and Neutral conductors (as well as the internal PE
conductor where required) shall be HDHC copper, of equal cross section.
The busbar must maintain its rated current when mounted in any
installation position (flat, edge or vertical). The single body system shall
cover up to 3150A in a single-conductor single-body construction, and
up to 6150A in a double-conductor single-body construction.
Various junction units shall be supplied as standard, including elbows,
knees, tees and flanged switchboard connections.
The Cast Resin Busbar trunking shall be Siemens LRC range or equal
and approved.
5.2
A
VAC
Standard
mm
Sq mm
kA for 1 sec
kA
400
1000
IP68
90x90
176
12
24
SB
630
1000
IP68
90x90
236
12
24
SB
800
1000
1200
1400
1600
2000
2500
3200
4000
4600
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
90x90 100x110 100x130 100x150 100x190 100x230 100x270 100x380 100x460 100x540
354
472
592
712
944
1184
1424
1889
2368
2849
26.5
26.6
53
53
65
65
65
100
100
100
55.7
55.8
117
117
143
143
143
220
220
220
SB
SB
SB
SB
SB
SB
SB
SB
SB
SB
400
1000
IP68
90x90
176
12
24
SB
630
1000
IP68
90x90
236
12
24
SB
800
1000
1200
1400
1600
2000
2500
3200
4000
4600
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
90x90 120x110 120x130 120x150 120x190 120x230 120x270 120x380 120x460 120x540
354
472
592
712
944
1184
1424
1889
2368
2849
26.5
26.6
53
53
65
65
65
100
100
100
55.7
55.8
117
117
143
143
143
220
220
220
SB
SB
SB
SB
SB
SB
SB
SB
SB
SB
630
1000
IP68
90x90
176
23
48
SB
800
1000
IP68
90x90
236
23
48
SB
1000
1350
1600
1700
2000
2500
3200
4000
5000
6150
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
90x90 100x110 100x130 100x150 100x190 100x230 100x270 100x380 100x460 100x540
354
472
592
712
944
1184
1424
1889
2368
2849
38
65
65
65
65
80
80
100
100
100
80
140
140
140
140
176
176
220
220
220
SB
SB
SB
SB
SB
SB
SB
SB
SB
SB
630
1000
IP68
90x90
176
23
48
SB
800
1000
IP68
90x90
236
23
48
SB
1000
1350
1600
1700
2000
2500
3200
4000
5000
6150
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
IP68
90x90 120x110 120x130 120x150 120x190 120x230 120x270 120x380 120x460 120x540
354
472
592
712
944
1184
1424
1889
2368
2849
38
65
65
65
65
80
80
100
100
100
80
140
140
140
140
176
176
220
220
220
SB
SB
SB
SB
SB
SB
SB
SB
SB
SB
A
VAC
Standard
mm
Sq mm
kA for 1 sec
kA
Rated Current
Rated Voltage
IP Rating
Dimensions
Conductor Cross-sectional Area
Short Time Rating
Prospective Short Circuit Rating
Form-Single/Double
A
VAC
Standard
mm
Sq mm
kA for 1 sec
kA
5.3
A
VAC
Standard
mm
Sq mm
kA for 1 sec
kA
TRACK
Short circuit protection provided by
fuselinks BS-88 and BS 1361 100 amp
maximum.
Prospective current 16.5kA
Mechanical withstand 10kA peak
Thermal withstand 1200A for 0.1 seconds
TAP-OFF UNITS
Mechanical withstand 10kA peak
Thermal withstand 1200A for 0.1 seconds
Earth Fault Loop Impedance (measured
at 1.0A)
The IEE Wiring Regulations require
accurate determination of the total earth
loop impedance, which must be low
enough to ensure that the protective
device will operate within the specified
time, which for circuits incorporating
socket outlets is 0.4 seconds. The values
for the Britmac System for calculating the
earth fault loop impedance are as follows:
Phase busbar 1.97mV/m
Earth busbar to housing 1.38mV/m
Construction
TRACK
Body extrusion Galvanised Steel
Track base Galvanised steel
Busbar High conductivity copper
Degree of protection Track IP4X; In-feed
housing IP3X C
TAP-OFF UNITS
Standard, Clean Earth and Dual Track
tap-offs are non- interchangeable. All types
available in fused and unfused versions.
STANDARDS
BSEN 60439: Part 1 & Part 2.
The track system enables compliance with
the latest IEE Wiring Regulations,
BS 7671:2008.
TRACK CURRENT RATING
63 amps, 240V ac; 50Hz single phase
ambient temperature 25C.
6.1
6
Minimum floor void 50mm
Minimum floor
void 73mm
6.2
Consumer Units
ALPHA BS I All Insulated & Metalclad Surface Mounting
Features:
Distribution Boards
ALPHA BS II Type B Surface Mounting
Features:
Design
External Dimensions
H x W x D (mm)
Order No
Design
All insulated
Main Switch All Insulated Consumer Units with 100A Incomer
5 way
8 way
11 way
14 way
19 way
230
230
230
230
230
190
243
294
344
439
120
120
120
120
120
8GB1 335-1DA
8GB1 335-2DA
8GB1 335-3DA
8GB1 335-4DA
8GB1 335-5DA
230
230
230
294
344
439
120
120
120
8GB1 335-6DA
8GB1 335-7DA
8GB1 335-8DA
210
210
210
210
210
188
242
292
343
439
122
122
122
122
122
8GB3 335-1DA
8GB3 335-2DA
8GB3 335-3DA
8GB3 335-4DA
8GB3 335-5DA
210
210
210
292
343
439
490
570
650
815
895
975
1140
430
430
430
430
430
430
430
Order No
155
155
155
155
155
155
155
8GP1 204-2DA54
8GP1 206-2DA54
8GP1 208-2DA54
8GP1 212-2DA54
8GP1 216-2DA54
8GP1 220-2DA54
8GP1 224-2DA54
155
155
155
155
155
8GP1 104-2DA50
8GP1 108-2DA50
8GP1 112-2DA50
8GP1 116-2DA50
8GP1 120-2DA50
5TE1 201-0DA
5TE1 301-0DA
5TE1 401-0DA
5TE1 202-0DA
5TE1 302-0DA
5TE1 402-0DA
5SM3 345-0
5SM3 645-0
8GP1 854-0DA10
8GP1 856-0DA10
8GP1 855-0DA10
4 way
8 way
12 way
16 way
20 way
650
815
975
1140
1140
430
430
430
430
430
Metal Clad
Main Switch Metalclad Consumer Units with 100A Incomer
5 way
8 way
11 way
14 way
19 way
External Dimensions
H x W x D (mm)
User defined Split Load All Insulated Consumer Unit with 100A
Main Switch incomer and 80A 30mA rccb
9 way
12 way
17 way*
4 way
6 way
8 way
12 way
16 way
20 way
24 way
8GB3 335-6DA
8GB3 335-7DA
8GB3 335-8DA
Conversion/Connection Kits
125A TP to SP Conversion Kit
4P rccb Connection Kit
8GP1 853-0DA20
8GP1 886-0DA10
8GP1 994-0DA10
8GP1 937-2DA50
8GP1 981-2DA10
*** For use with 125A 16, 20 & 24 way TP&N Distribution Boards only
7.1
Distribution Boards
UK produced flexible format with/without metering
Consumer units / Distribution boards / Panel boards'
Technical Data
Distribution Boards
ALPHA BS II Type B Surface Mounting
Features:
Designed to BS EN 60439-3
125A rated Current
Rated Voltage 230/400V 50/60Hz
Modular Construction
1mm Sheet Steel Enclosure
Design
External Dimensions
H x W x D (mm)
Order No
Design
External Dimensions
H x W x D (mm)
Order No
8GP1 921-2DA80
8GP1 991-2DA80
8GP1 990-2DA10
8GP1 991-2DA10
650
815
815
895
975
1085
1190
430
430
430
430
430
430
430
155
155
155
155
155
155
155
8GP1 204-4DA54
8GP1 206-4DA54
8GP1 208-4DA54
8GP1 212-4DA54
8GP1 216-4DA54
8GP1 220-4DA54
8GP1 224-4DA54
8GP1 643-4DA40
8GP1 617-0DA41
8GP1 643-4DA50
8GP1 618-0DA51
8GP1 867-0DA10
Dims:
420
430
8GP1 992-2DA10
8GP1 993-2DA10
** For use with 200A 16, 20 & 24 way TP&N Distribution Boards only
8GP1 901-0DA10
8GP1 902-0DA10
8GP1 903-0DA10
8GP1 904-0DA10
8GP1 905-0DA10
Dims:
245
430
155
8GP1 995-0DA13
8GP1 995-0DA14
8GP1 910-0DA10
8GP1 990-4DA10
8GP1 991-4DA10
7.2
8GP1 937-4DA50
8GP1 981-4DA10
155
735
430
8GP1 992-4DA10
8GP1 993-4DA10
155
Distribution Boards
UK produced flexible format with/without metering
Technical Data
Features:
Features:
Standards: EN 60898
Rated Voltage: 230/400V AC
Degree of Protection: IP20
Solid/stranded conductor csa:
<25mm
70mm device
mounting depth
Rating
In
A
5SY6, 6kA
Characteristic B
Order No.
5SY6, 6kA
5SY6, 6kA
Characteristic C Characteristic D
Order No.
Order No.
1 pole
6
10
16
20
25
32
40
50
63
5SY6 106-6
5SY6 110-6
5SY6 116-6
5SY6 120-6
5SY6 125-6
5SY6 132-6
5SY6 140-6
5SY6 150-6
5SY6 163-6
5SY6 106-7
5SY6 110-7
5SY6 116-7
5SY6 120-7
5SY6 125-7
5SY6 132-7
5SY6 140-7
5SY6 150-7
5SY6 163-7
5SY6 106-8
5SY6 110-8
5SY6 116-8
5SY6 120-8
5SY6 125-8
5SY6 132-8
5SY6 140-8
5SY6 150-8
5SY6 163-8
3 pole
6
10
16
20
25
32
40
50
63
5SY6 306-6
5SY6 310-6
5SY6 316-6
5SY6 320-6
5SY6 325-6
5SY6 332-6
5SY6 340-6
5SY6 350-6
5SY6 363-6
5SY6 306-7
5SY6 310-7
5SY6 316-7
5SY6 320-7
5SY6 325-7
5SY6 332-7
5SY6 340-7
5SY6 350-7
5SY6 363-7
5SY6 306-8
5SY6 310-8
5SY6 316-8
5SY6 320-8
5SY6 325-8
5SY6 332-8
5SY6 340-8
5SY6 350-8
5SY6 363-8
Standards: EN 60898
Rated Voltage: 230/400V AC
Degree of Protection: IP20
Solid/stranded conductor csa:
<25mm
70mm device
mounting depth
Rating
In
A
5SY4, 10kA
Characteristic B
Order No.
5SY4, 10kA
5SY4, 10kA
Characteristic C Characteristic D
Order No.
Order No.
1 pole
6
10
16
20
25
32
40
50
63
80
5SY4 106-6
5SY4 110-6
5SY4 116-6
5SY4 120-6
5SY4 125-6
5SY4 132-6
5SY4 140-6
5SY4 150-6
5SY4 163-6
5SY4 180-6*
5SY4 106-7
5SY4 110-7
5SY4 116-7
5SY4 120-7
5SY4 125-7
5SY4 132-7
5SY4 140-7
5SY4 150-7
5SY4 163-7
5SY4 180-7*
5SY4 106-8
5SY4 110-8
5SY4 116-8
5SY4 120-8
5SY4 125-8
5SY4 132-8
5SY4 140-8
5SY4 150-8
5SY4 163-8
-
5SY4 306-6
5SY4 310-6
5SY4 316-6
5SY4 320-6
5SY4 325-6
5SY4 332-6
5SY4 340-6
5SY4 350-6
5SY4 363-6
5SY4 380-6**
5SY4 306-7
5SY4 310-7
5SY4 316-7
5SY4 320-7
5SY4 325-7
5SY4 332-7
5SY4 340-7
5SY4 350-7
5SY4 363-7
5SY4 380-7**
5SY4 306-8
5SY4 310-8
5SY4 316-8
5SY4 320-8
5SY4 325-8
5SY4 332-8
5SY4 340-8
5SY4 350-8
5SY4 363-8
-
7.3
Distribution Boards
UK produced flexible format with/without metering
Distribution components
Technical Data
Features:
Features:
Standards: EN 60898
Rated Voltage: 230/400V AC
Degree of Protection: IP20
Solid/stranded conductor csa:
<25mm
Rating
In
A
5SY7, 15kA
Characteristic B
Order No.
5SY7, 15kA
5SY7, 15kA
Characteristic C Characteristic D
Order No.
Order No.
1 pole
6
10
16
20
25
32
40
50
63
5SY7 106-6
5SY7 110-6
5SY7 116-6
5SY7 120-6
5SY7 125-6
5SY7 132-6
5SY7 140-6
5SY7 150-6
5SY7 163-6
5SY7 106-7
5SY7 110-7
5SY7 116-7
5SY7 120-7
5SY7 125-7
5SY7 132-7
5SY7 140-7
5SY7 150-7
5SY7 163-7
5SY7 106-8
5SY7 110-8
5SY7 116-8
5SY7 120-8
5SY7 125-8
5SY7 132-8
5SY7 140-8
5SY7 150-8
5SY7 163-8
3 pole
6
10
16
20
25
32
40
50
63
5SY7 306-6
5SY7 310-6
5SY7 316-6
5SY7 320-6
5SY7 325-6
5SY7 332-6
5SY7 340-6
5SY7 350-6
5SY7 363-6
5SY7 306-7
5SY7 310-7
5SY7 316-7
5SY7 320-7
5SY7 325-7
5SY7 332-7
5SY7 340-7
5SY7 350-7
5SY7 363-7
5SY7 306-8
5SY7 310-8
5SY7 316-8
5SY7 320-8
5SY7 325-8
5SY7 332-8
5SY7 340-8
5SY7 350-8
5SY7 363-8
Standards: EN 60947-2
Rated Voltage: 230/400V AC
Degree of Protection: IP20
Solid/stranded conductor csa:
<25mm
Rating
In
A
5SY8, 25kA
Characteristic B
Order No.
5SY8, 25kA
5SY8, 25kA
Characteristic C Characteristic D
Order No.
Order No.
1 pole
6
10
16
20
25
32
40
50
63
5SY8 106-7
5SY8 110-7
5SY8 116-7
5SY8 120-7
5SY8 125-7
5SY8 132-7
5SY8 140-7
5SY8 150-7
5SY8 163-7
5SY8 106-8
5SY8 110-8
5SY8 116-8
5SY8 120-8
5SY8 125-8
5SY8 132-8
5SY8 140-8
5SY8 150-8
5SY8 163-8
3 pole
6
10
16
20
25
32
40
50
63
5SY8 306-7
5SY8 310-7
5SY8 316-7
5SY8 320-7
5SY8 325-7
5SY8 332-7
5SY8 340-7
5SY8 350-7
5SY8 363-7
5SY8 306-8
5SY8 310-8
5SY8 316-8
5SY8 320-8
5SY8 325-8
5SY8 332-8
5SY8 340-8
5SY8 350-8
5SY8 363-8
8GP1 960-0DA10
8GP1 961-0DA10
8GP1 975-0DA10
8GP1 970-0DA11
8GP1 971-1DA11
8GP1 972-0DA12
8GP1 973-0DA15
8GP1 974-0DA10
7.4
8GP1 962-0DA10
8GP1 920-0DA41
8GP1 920-0DA42
8GP1 920-0DA43
8GP1 920-0DA44
8GP1 920-0DA45
8GP1 920-0DA46
8GP1 920-0DA47
8GP1 976-0DA16
8GP1 930-0DA47
8GP1 931-0DA47
8GP1 932-0DA47
8GP1 933-0DA47
8GP1 934-0DA47
8GP1 935-0DA47
Distribution Boards
UK produced flexible format with/without metering
Technical Data
Features:
Rating
In
A
Characteristic B
Order No.
Rating
In
A
Characteristic C
Order No.
5SU9 106-1KK10
5SU9 106-1KK16
5SU9 106-1KK20
5SU9 106-1KK32
5SU9 106-1KK40
5SU9 106-1KK45
Characteristic B
Order No.
Characteristic C
Order No.
5SU9 104-1KK10
5SU9 104-1KK16
5SU9 104-1KK20
5SU9 104-1KK25
5SU9 104-1KK32
5SU9 104-1KK40
5SU9 104-1KK45
5SU9 306-0KK10
5SU9 306-0KK16
5SU9 306-0KK20
5SU9 306-0KK25
5SU9 306-0KK32
5SU9 306-0KK40
-
5SU9 306-1KK06
5SU9 306-1KK10
5SU9 306-1KK16
5SU9 306-1KK20
5SU9 306-1KK25
5SU9 306-1KK32
5SU9 306-1KK40
5SU9 306-1KK45
5SU9 406-0KK10
5SU9 406-0KK16
5SU9 406-0KK20
5SU9 406-0KK25
5SU9 406-0KK32
5SU9 406-0KK40
5SU9 406-1KK06
5SU9 406-1KK10
5SU9 406-1KK16
5SU9 406-1KK20
5SU9 406-1KK25
5SU9 406-1KK32
5SU9 406-1KK40
5SU9 304-0KK10
5SU9 304-0KK16
5SU9 304-0KK20
5SU9 304-0KK25
5SU9 304-0KK32
5SU9 304-0KK40
-
5SU9 304-1KK06
5SU9 304-1KK10
5SU9 304-1KK16
5SU9 304-1KK20
5SU9 304-1KK25
5SU9 304-1KK32
5SU9 304-1KK40
5SU9 304-1KK45
5SU9 404-0KK10
5SU9 404-0KK16
5SU9 404-0KK20
5SU9 404-0KK25
5SU9 404-0KK32
5SU9 404-0KK40
5SU9 404-1KK06
5SU9 404-1KK10
5SU9 404-1KK16
5SU9 404-1KK20
5SU9 404-1KK25
5SU9 404-1KK32
5SU9 404-1KK40
5SU9 604-1KK06
5SU9 604-1KK10
5SU9 604-1KK16
5SU9 604-1KK20
5SU9 604-1KK25
5SU9 604-1KK32
5SU9 604-1KK40
7.5
Overview
The Sentron family of circuit breakers is built
on a modular design principle encompassing
ratings from 16-6300A and breaking
capacities from 50-150kA. Designed with
flexibility in mind the Sentron family
applications can include incoming and
8.1
Size I
Size II
Size III
3WL11
I
N
Not available
3-pole, 4-pole
up to 1000
30/25/20
(with 300/600/1000 V DC)
3WL12
II
N
3WL13
III
H
kA 55
kA 55
kA 121
66
66
145
66
66
145
80
80
176
100
100
220
kA 42
kA 42
kA 88
50
50
105
50
50
105
75
75
165
kA 55
kA 42
66
50
66
55
80
66
C
3-pole
C
4-pole
100
100
220
150
150
330
130
130
286
85
85
187
85
85
187
150
150
330
130
130
286
100
80
100
100
100
100
100
100
ETU15B
ETU25B
ETU27B
ETU45B
ETU76B
Optional
8.2
8.3
Type
Rated current In
with 50 C ambient temperature1)
Rated operational voltage Ue
50/60 Hz AC
Overcurrent releases
Thermal-magnetic
Electronic ETU LCD
Replaceable
PROFIBUS module COM10
Switching capacity Icu/Ics
effective value, in acc. with IEC 60947-2
Standard switching capacity N3)
with 415 V AC
High switching capacity H2)
with 415 V AC
with 690 V AC
Very high switching capacity L2)
with 415 V AC
with 690 V AC
VL160X/3VL1
16 to 160
VL160/3VL2
26 to 160
VL250/3
80 to 250
690
690
690
690
690
690
690
kA 55/55
55/55
55/55
55/55
kA 70/70
kA 12/63)
70/70
12/6
70/70
12/6
70/70
15/8
kA
kA
100/75
12/6
100/75
12/6
100/75
15/8
VL3 VL400
125 to 400
VL630/3VL5
252 to 630
VL800/3VL6
320 to 800
VL1250/3VL7
400 to 1250
VL1600/3VL8
640 to 1600
16 to 100
690
690
690
690
690
690
690
690
p to 415
kA 45/45
50/50
50/25
50/
25 18/9
kA 70/70
kA 30/15
70/70
30/15
70/35
30/15
70/35
30/15
kA 100/75
kA 20/10
100/75
20/10
100/50
35/17
100/50
35/17
8.4
7HFKQLFDOVSHFLILFDWLRQV
&KDUDFWHULVWLF' , Q $
W >V@
162B
6ZLWFK'LVFRQQHFWRUV
6WDQGDUGV
(1
,(&
(1,(&
(1,(&
(1,(&
5DWHGRSHUDWLRQDOFXUUHQW , H
$
,X
5DWHGRSHUDWLRQDOYROWDJH 8H
5DWHGIUHTXHQF\ I Q
5DWHGLPSXOVHZLWKVWDQGYROWDJH
5DWHGLQVXODWLRQYROWDJH 8L
8LPS
PD[$&
+]
N9
8WLOL]DWLRQFDWHJRU\
VHOHFWLYLW\$&9
VZLWFKLQJPRGH
, Q $
5DWHGVKRUWWLPHZLWKVWDQGFXUUHQW
5DWHGXOWLPDWHVKRUWFLUFXLWEUHDNLQJ
FDSDFLW\UPVYDOXH , FX 8H
3VT1
, FZ W
2IIWLPHDW , FX
97(($$
&LUFXLW%UHDNHUV
1XPEHURISROHV
5DWHGFXUUHQW , Q
5DWHGXQLQWHUUXSWHGFXUUHQW
2UGHU1R
6ZLWFKGLVFRQQHFWRUV
PV
5DWHGVHUYLFHVKRUWFLUFXLWEUHDNLQJ
FDSDFLW\UPVYDOXH , FV 8H
[, Q
5DWHGVKRUWFLUFXLWPDNLQJFDSDFLW\
SHDNYDOXH , FP 8H
/RVVHVSHUSROHDW , Q $
PD[$&
PD[$&
$
$& $
$& $
$& $
$
$& $
$& $
'& $
$& $
N$V
N$V
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$'& 9
PD[ PV
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$'& 9
PD[ PV
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
VHHWDEOHSDJH
0HFKDQLFDOHQGXUDQFH
F\FOHV
F\FOHV
2SHUDWLQJIRUFH
F\FOHV
KU
)URQWVLGHGHYLFHSURWHFWLRQ
,3
7HUPLQDOSURWHFWLRQ
,3
DYDLODEOH
XQDYDLODEOH
LQSUHSDUDWLRQ
8.5
&LUFXLW%UHDNHUV
$SSURYDOPDUNV
6SHFLILFDWLRQV
:KHQUHYHUVLQJWKHFLUFXLWEUHDNHUFRQQHFWLRQSRZHUVXSSO\FRQQHFWHGWR
WHUPLQDOV1RXWSXWWRWHUPLQDOV1, FX GRHVQRWFKDQJH
5DQJHVRIUDWHGFXUUHQWVYDU\DFFRUGLQJWRFKDUDFWHULVWLFVVHHSDJH
3HUPLVVLEOHORDGRI1SROHLV
PLQ
,U
162B
[
PD[
,U
,L
5DWHGFXUUHQW, Q
5DWHGXQLQWHUUXSWHGFXUUHQW , X
5DWHGRSHUDWLRQDOFXUUHQW , H
5DWHGRSHUDWLRQDOYROWDJH 8H
$&PD[
$& PD[
'& PD[
5DWHGIUHTXHQF\ IQ
+]
N9
5DWHGLQVXODWLRQYROWDJH8L
$
$&%
'& 9
6HULHV8H
[
[
[
[
,L
5DWHGVKRUWFLUFXLWPDNLQJFDSDFLW\SHDNYDOXH , FP 8H
2IIWLPHDW, FX
, Q $
[
[
[
[
97+
N$
N$
N$
N$
N$
N$
N$
N$
N$
N$
N$
N$
N$
F \F OHV
F \F OHV
F \F OHV
KU
2S HUDWLQJ IRUF H
[
[
[
[
,L
Ir
6SHFLILFDWLRQV
NSO0_00357
max.
Ir
Ii
0.02
0.02
0.01
0.1
(1,(&
(1,(&
$
5DWHGXQLQWHUUXSWHGFXUUHQW , X
5DWHGRSHUDWLRQDOFXUUHQW , H
5DWHGRSHUDWLRQDOYROWDJH 8H
$&PD[
$& PD[
'& PD[
5DWHGIUHTXHQF\ IQ
+]
N9
5DWHGLQVXODWLRQYROWDJH8L
5DWHGFXUUHQW, Q
In = 250 A
In = 400 A
4x
12.5x
4x
12.5x
4x
12.5x
4x
12.5x
Ii
4x
4x
12.5x
Ii
I r = 575 A.630 A ~ I i = 7 kA
10
50
20
xI n
$&%
'&%
N$PVN$PVN$ V
97+
N$
N$
N$
N$
N$
N$
N$
N$
5DWHGVKRUWFLUFXLWEUHDNLQJ
FDSDFLW\UPVYDOXH , FV 8H
N$
N$
N$
N$
N$
2IIWLPHDW,FX
PV
F \F OHV
F\FOHV
F \F OHV
KU
2S HUDWLQJ IRUF H
/RVVHVSHUSROHDW , Q $
12.5x
$& 9 , FZ W
971
5DWHGVKRUWFLUFXLWPDNLQJFDSDFLW\
SHDNYDOXH, FP 8H
Ii
In = 630 A
0.5
5DWHGXOWLPDWHVKRUWFLUFXLWEUHDNLQJ
FDSDFLW\UPVYDOXH , FX
6HULHV8H
0.2
N$$& 9
N$$&9
6WDQGDUGV
5DWHGVKRUWWLPHZLWKVWDQGFXUUHQW 8H
0.01
0.1
0.05
$& 9
6ZLWFKGLVFRQQHFWRUV
VHOHFWLYLW\$& 9
VZLWFKLQJPRGH $& 9
'& 9
0.02
0.01
0.1
0.05
N$
8WLOL]DWLRQFDWHJRU\
In = 250 A
In = 400 A
In = 630 A
1
0.5
0.2
0.1
0.05
97$$$$
97$$$$
&LUFXLWEUHDNHUV
5DWHGLPSXOVHZLWKVWDQGYROWDJH 8LPS
20
$& 9
$& 9
$& 9
$& 9
7\SH
1XPEHURISROHV
100
50
N$
N$
N$
N$
$SSURYDOPDUNV
200
10
5
,3
7HFKQLFDOVSHFLILFDWLRQV
,3
$& 9
$& 9
$& 9
$& 9
[, Q
10000
5000
t [s]
2000
1000
500
)URQWVLGHGHYLFHSURWHFWLRQ
7HUPLQDOSURWHFWLRQ
8H
, Q $
N$ V
971
PV
/RVVHVSHUSROHDW , Q $
,L
'&%
N$V
5DWHGXOWLPDWHVKRUWFLUFXLWEUHDNLQJFDSDFLW\UPVYDOXH , FX
, Q $
$& 9, FZ W
$& 9
5DWHGVKRUWWLPHZLWKVWDQGFXUUHQW 8H
(1,(&
8WLOL]DWLRQFDWHJRU\VZLWFKLQJPRGH
, Q $
, Q $
, Q $
6ZLWFKGLVFRQQHFWRUV
(1,(&
&LUFXLWEUHDNHUV
6WDQGDUGV
5DWHGLPSXOVHZLWKVWDQGYROWDJH 8LPS
6SHFLILFDWLRQV
1XPEHURISROHV
7HFKQLFDOVSHFLILFDWLRQV
$SSURYDOPDUNV
3VT5
3VT4
3VT3
3VT2
$& 9
$& 9
$& 9
$& 9
N$
N$
N$
N$
$& 9
$& 9
$& 9
$& 9
N$
$& 9
N$$& 9
N$$& 9
)URQWVLGHGHYLFHSURWHFWLRQ
,3
7HUPLQDOSURWHFWLRQ
,3
DYDLODEOH
XQDYDLODEOH
LQSUHSDUDWLRQ
N$ V
8H
,QFDVHFLUFLXWEUHDNHUFRQQHFWLRQLVUHYHUVHGLQSXWWHUPLQDOV
RXWSXWWHUPLQDOV, FX GRHVQRWFKDQJH
8.6
7ULSSLQJFKDUDFWHULVWLFV
PLQ
,U
6SHFLILFDWLRQV
PD[
,U
6WDQGDUGV
1XPEHURISROHV
, Q
,Q
,,Q
Q
,,Q
Q
,,Q
Q
$
$
$
$
$
$
$
$
, L>N$@
, Q $
5DWHGRSHUDWLRQDOYROWDJH 8H
$&PD[
$& PD[
'& PD[
5DWHGIUHTXHQF\ IQ
+]
N9
5DWHGLQVXODWLRQYROWDJH8L
$&%
'&%
N$V
N$V
5DWHGXOWLPDWHVKRUWFLUFXLWEUHDNLQJ
FDSDFLW\UPVYDOXH , FX 8H
$& N$9
$& N$9
$& N$9
$& N$9
2IIWLPHDW, FX
PV
$& N$9
$& N$9
$& N$9
$& N$9
N$$& 9
N$$& 9
N$'& 9
'& 9
, L>N$@
, Q $
, L>N$@
, Q $
PLQ
/RVVHVSHUSROHDW , Q $
F \F OHV
F \F OHV
F \F OHV
KU
2S HUDWLQJ IRUF H
)URQWVLGHGHYLFHSURWHFWLRQ
,3
7HUPLQDOSURWHFWLRQ
,3
DYDLODEOH
XQDYDLODEOH
$%
$& 9
5DWHGVKRUWFLUFXLWPDNLQJFDSDFLW\
SHDNYDOXH, FP 8H
7HFKQLFDOVSHFLILFDWLRQV
162B
6SHFLILFDWLRQV
PD[
,U
97FLUFXLWEUHDNHUV
6ZLWFKGLVFRQQHFWRUV
(1,(&
(1,(&
7\SH
,L
6WDQGDUGV
$SSURYDOPDUNV
1XPEHURISROHV
, Q
,Q
,Q
, Q
, Q
,Q
, Q
,Q
$
$
$
$
$
$
$
$
5DWHGFXUUHQW, Q
5DWHGRSHUDWLRQDOFXUUHQW, H
$&PD[
$& PD[
'& PD[
5DWHGIUHTXHQF\ IQ
+]
N9
5DWHGLQVXODWLRQYROWDJH8L
5DWHGQRUPDOFXUUHQW, X
5DWHGRSHUDWLRQDOYROWDJH 8H
5DWHGLPSXOVHZLWKVWDQGYROWDJH 8LPS
, Q $
, Q $
$%
8WLOL]DWLRQFDWHJRU\VZLWFKLQJPRGH
$& 9
'& 9
$&%
'&%
$& 9, FZ W
PV
2IIWLPHDW, FX
/RVVHVSHUSROHDW , Q $
0HFKDQLFDOHQGXUDQFH
, L>N$@
, Q $
5DWHGVKRUWFLUFXLWPDNLQJFDSDFLW\
SHDNYDOXH, FP 8H
, L>N$@
, Q $
, L>N$@
N$ V
5DWHGXOWLPDWHVKRUWFLUFXLWEUHDNLQJFDSDFLW\
UPVYDOXH , FX
, L>N$@
[, Q
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
N$$& 9
F\FOHV
6ZLWFKLQJIUHTXHQF\
F\FOHV
KU
2SHUDWLQJIRUFH
)URQWVLGHGHYLFHSURWHFWLRQ
,3
7HUPLQDOSURWHFWLRQ
,3
DYDLODEOH
XQDYDLODEOH
LQSUHSDUDWLRQ
5DWHGVKRUWWLPHZLWKVWDQGFXUUHQW8H
5DWHGRSHUDWLRQDOFXUUHQW , H
, L>N$@
, Q $
5DWHGQRUPDOFXUUHQW, X
5DWHGVKRUWFLUFXLWVHUYLFHEUHDNLQJ
FDSDFLW\UPVYDOXH , FV 8H
W >V@
(1,(&
7ULSSLQJFKDUDFWHULVWLFV
(1,(&
5DWHGFXUUHQW, Q
5DWHGLPSXOVHZLWKVWDQGYROWDJH 8LPS
[, Q
6ZLWFKGLVFRQQHFWRUV
$SSURYDOPDUNV
97FLUFXLWEUHDNHUV
7\SH
,L
,QFDVHWKHFLUFLXWEUHDNHUFRQQHFWLRQLVUHYHUVHGLQSXWWHUPLQDOV
RXWSXWWHUPLQDOV, FX GRHVQRWFKDQJH
Anschlussklemmen
Accessories:
Auxiliary switch
Shunt trip units
Motor operators
mechanical Interlocks
Undervoltage trip
Locking mechanisms
Insulation barriers
Connection covers
mounting adaptors
... and more.
Leistungsschalter
10
11
8
12
13
14
NSO0_00258a
W >V@
7HFKQLFDOVSHFLILFDWLRQV
162B
Drehantriebe
15
17
18
19
20
16
23
22
8.7
21
1 Leistungsschalter 3VT
2 Rundleiteranschlussklemme
3 Frontseitiger Anschluss
24
10
11
12
27
26
25
Unterspannungsauslser
Adapter fr 35 mm DIN Schiene
Verriegelung Kipphebel
19
20
21
PAC3100
Power measurement
System integration and communication
PAC3200
> 30
e.g. voltage, current, power, energy values,
frequency, power factor (min./max. values)
e.g. THD, unbalance for current and voltage
e.g. phase angle,
phase displacement angle,
harmonics in voltage and current
Power meters (input and output)
Load profile record with time stamp
Ethernet
RS485 (Modbus RTU) integrated
PROFIBUS DP (V1)
S0 interface
integrated
optional
PAC4200
> 50
integrated
optional
optional
DI/DO usable as S0 interface
> 200
optional
Direct connection
up to 80 A
up to 80 A
up to 80 A
up to 80 A
up to 80 A
Transformer connection
...15 A
Calibrated version
SO interface
IR interface (for the connection of communication modules)
Sentron Powermanager is a PC based software platform, which addresses all of the prerequisites detailed above. Not only does it provide a clear window in to the energy
flow, identifying areas for saving in accordance to the latest standards for Energy Management EN16001, it does this in an intuitive, extremely user friendly manner.
9.1
9.2
Benefits
Transparency of power flows
Exact knowledge of the consumption profile
Increase of energy efficiency
Optimization of power supply contracts
Compliance with contractual terms
Assignment of power costs to cost centers
Optimization of plant maintenance
Identification of critical system conditions
In the SENTRON product family the user will find
not only a power management software in the
form of SENTRON powermanager but also the
matching hardware in the form of SENTRON PAC
power monitoring devices and SENTRON
3WL/3VL circuit breakers for realizing a complete
power management system. The components are
optimally coordinated with each other, e.g. special
drivers for the SENTRON devices are integrated in
the SENTRON powermanager software so that on
the one hand the power data acquisition can take
place without any great configuration effort and
on the other hand the most important measured
values or states are indicated by predefined
displays.
This reduces the engineering expenditures for
the customer and gives the user the assurance
of knowing that the device functions are
optimally supported in the software.
System configuration
Integration of measuring instruments by means
of predefined device templates for the SENTRON
PAC family and the SENTRON 3WL/3VL circuit
breakers
Easy integration of existing modbus-capable
detecting devices
Communication through Standard Ethernet
Integration of devices with RS485 interface
(Modbus RTU) through Modbus gateway, e.g.
the SENTRON PAC4200 can be used as gateway
System requirements
Processor: Intel Pentium IV 2.8 GHz (or better)
RAM: At least 2 GB
Hard disk: At least 1 GB free
Graphics: VGA with at least 1280 x 1024 pixels and 16-bit color
intensity
Supported operating systems
Windows Vista: Business, Ultimate; SP1
Windows XP: XP with SP2/SP3
Windows 2003: Server 2003 Server (32-bit)
Windows 2008: Server 2008 Server (32-bit)
9.3
10
10.1
10
Construction:
The Sivacon S4 energy distribution concept consists of full galvanised chromed sheet steelframes, of sturdy self standing design , flush
or wall mounted.
Sivacon S4 low-voltage power distribution are constructed in accordance to a modular design system by means of flexible assembly
kits, and can be combined to meet a wide range of power distribution needs
10
10.2
Measured Variable
Nominal system voltage Un
Voltage unbalance
Phase loss
Phase sequence
Frequency
11
11.1
Basic setting
100 . 690V
Left, Right
50 / 60 Hz
80% 100%
101% 120%
Delay time
0.1 900s
0.1 900s
0.1 900s
0.1 30s
0.1 900s
0.1 900s
Can be deactivated
11
Mechanical protection
Second digit
Mechanical protection
No protection
No protection
n/a
n/a
n/a
n/a
n/a
n/a
Agreement between
manufacturer and user. Must be
more stringent than IP67
Contact Information
Please read and recycle
Siemens
I BT LV
Sharston Road
Wythenshawe
Manchester M22 4RA
Tel: +44 (0) 161 998 5454
Fax: +44 (0) 8456 053114
www.industry.siemens.co.uk/buildingtechnologies/uk
44
Rd&M 201791 07.11