Cordex125 4k4W 5thed PDF
Cordex125 4k4W 5thed PDF
Cordex125 4k4W 5thed PDF
4kW
Modular Switched Mode Rectifier
010-589-B2
Visit www.argus.ca
Cordex 125-4.4kW
Modular Switched Mode Rectifier
010-589-B2
The following documents and drawings are included in this manual to provide the necessary information required for
installation, operation and fault diagnosis of the unit:
Specifications, Cordex 125-4.4kW:
010-589-B1 Rev A
Warranty Policy:
048-507-10
CSA/NRTL Equivalence:
048-554-10
010-589-C0 Rev A
030-769-06
030-769-08
010-589-G0
048-527-10
010-589-B2 Rev A WC
MANUAL ADDENDUM
Unit Description: Cordex 125-4.4kW Modular Switched Mode Rectifier
Manual P/N: 010-589-B2
Applies to Manual Revision: A
#
1
Date
07-11-20
Page#
7
of 010-589-C0
Line#
37
Correction to be implemented
Add text to Section 5.5:
WARNING
Use care when removing or replacing the covers for the AC input
connections. Never assume that an electrical connection or
conductor is not energized.
MANUAL ADDENDUM
Authorized by:
FORM 954-010-10
010589b2a1_addendum_coverplates.doc
Current:
Maximum Power:
4400W continuous/module
Better than 0.5% for any load change within rated limits
Better than 5% for 40% - 90 - 40% step load change at nominal output voltage
(output shall recover to static limits within 30ms)
Better than 0.1% for any change in input voltage within rated limits
Better than 1% for any change in input voltage within rated limits
(output shall recover to static limits within 10ms)
Hold-up Time:
>10ms
Time Stability:
Temperature Stability:
Heat Dissipation:
Electrical Noise:
Acoustic Noise:
EMI:
The unit meets requirements of EN55022 (see Standards for more EMC)
In accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines for
conformance to Part 15, Class A:
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
Any changes or modifications to this equipment not expressly described in this manual could void the FCC
compliance.
010-589-B1 Rev A WC
Page 1 of 4
Frequency:
Current:
20A @ 240Vac
23A @ 208Vac
26A @ 187Vac (maximum)
Protection:
Efficiency:
Inrush Current:
full load steady state current of the rectifier within rated limits
<5 seconds (excluding soft start) to complete inrush limit routine and ac
measurement (for OK signal)
Start-up Delay:
Soft Start:
User adjustable to at least 5 seconds (not including start-up delay time) and is
determined by output current limit ramp-up
T.H.D. (Current):
Environmental
Operating Temperature:
Storage Temperature:
-40 to +85C
(-40 to 185F)
Humidity:
0 to 95% non-condensing
Elevation:
Miscellaneous
MTBF:
010-589-B1 Rev A WC
Page 2 of 4
Mechanical
Module
Dimensions:
Weight:
19 Shelf (fits 5 modules)
Dimensions:
Weight:
Mounting:
Connections
Input:
Output:
Chassis Ground:
CAN Communication:
RJ-12 offset
Safety
EN
60950
UL
60950-1: 2002
CSA
CE
EN 60950, CB Scheme
Telcordia (Bellcore)
010-589-B1 Rev A WC
Page 3 of 4
EN 61000-3-2
EN 61000-3-3
EN 61000-4-2
ESD Immunity
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
IEC 60950
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
Specifications are subject to change without notice.
010-589-B1 Rev A WC
Page 4 of 4
Argus Technologies Ltd. warrants all equipment manufactured by it to be free from defects in parts
and labor, excluding third party OEM materials (example: air conditioners, batteries), for a period of
two years from the date of shipment from the factory. For third party products the OEMs warranty
shall apply. The liability of Argus applies solely to repairing, replacing or issuing credit (at Argus sole
discretion) for any equipment manufactured by it and returned by the customer during the warranty
period. The terms of the warranty are Ex Works (EXW) from Argus factory service location.
Argus reserves the right to void the warranty if:
(1) identification marks or serial numbers are removed or altered in any way,
(2) invoice is unpaid, or
(3) defect is the result of misuse, neglect, improper installation, environmental
conditions, non-authorized repair, alteration or accident.
Argus shall not be liable to the customer or other parties for any loss of profits, loss of use, costs for
removal or installation of defective equipment, damages or consequential damages based upon
equipment failure during or after the warranty period. There shall be no other obligations either
expressed or implied. Argus will not honor warranties for batteries and other third party products
without prior written Argus authorization.
Freight Policy
Customer is responsible for all shipping and handling charges (COD and freight collect will not be
accepted without prior approval from Argus Technologies).
Payment terms are net 30 days subject to prior credit approval. All other orders require payment
before shipping.
Our RMA policy is designed to ensure prompt, efficient and high quality factory service. A Return
Material Authorization (RMA) number must be obtained before products can be accepted for
servicing by the Argus factory. For returns to an authorized service center (refer to Authorized
Service Centers for locations), please consult the individual service center for specific return policies
and instructions.
To obtain a RMA number for a factory return, customers must call the appropriate location with the
product serial and model number, as well as a brief description of the problem, shipment instructions
and billing details.
The original packing container should be used whenever possible. Both the shipping documents
and the outside of the box must have the RMA # clearly marked and the product shipped prepaid to
the Argus factory service center. Argus will endeavor to repair products within five working days of
receipt. Repairs to the returned product are warranted for a period of six months. A service charge
may be applied if no fault is found in the returned product. Argus will not accept products without an
RMA number.
Business Hours
Argus North American office hours are 7:30 am to 5:00 pm (Pacific Standard Time) Monday to Friday.
Canada and USA toll free 24 hour emergency technical support: +1 888 GO ARGUS (462 7487)
CSA (Canadian Standards Association also known as CSA International) was established in 1919 as
an independent testing laboratory in Canada. CSA received its recognition as an NRTL (Nationally
Recognized Testing Laboratory) in 1992 from OSHA (Occupational Safety and Health Administration) in
the United States of America (Docket No. NRTL-2-92). This was expanded and renewed in 1997, 1999,
and 2001. The specific notifications were posted on OSHAs official website as follows:
Federal Register #: 59:40602 - 40609 [08/09/1994]
Federal Register #: 64:60240 - 60241 [11/04/1999]
Federal Register #: 66:35271 - 35278 [07/03/2001]
When these marks appear with the indicator C and US or NRTL/C it means that the product is
certified for both the US and Canadian markets, to the applicable US and Canadian standards. (1)
Argus rectifier and power system products, bearing the aforementioned CSA marks, are
certified to CSA C22.2 No. 950 and UL 1950, or CSA/UL 60950.
As part of the reciprocal, US/Canada agreement regarding testing laboratories, the Standards Council
of Canada (Canadas national accreditation body) granted Underwriters Laboratories (UL) authority to
certify products for sale in Canada. (2)
Only Underwriters Laboratories may grant a licence for the use of this mark, which indicates compliance
with both Canadian and US requirements. (3)
NRTLs are third party organizations recognized by OSHA, US Department of Labor, under the NRTL
program.
The testing and certifications are based on product safety standards developed by US based standards
developing organizations and are often issued by the American National Standards Institute (ANSI). (4)
The NRTL determines that a product meets the requirements of an appropriate consensus-based
product safety standard either by successfully testing the product itself, or by verifying that a contract
laboratory has done so, and the NRTL certifies that the product meets the requirements of the product
safety standard. (4)
In 1983, in a suit brought on by an independent testing laboratory, OSHA was court ordered to remove
specific references to UL (Underwriters Laboratories) and FMRC (Factory Mutual Research Corporation)
from its regulations.
In 1988, OSHA revised its regulations to remove those references and the NRTL program was
established.
The NRTL Program is both national and international in scope with foreign labs permitted.
References:
Information in this document has been developed from the official websites of the respective
organizations.
(1) www.csa-international.org
(2) www.scc.ca
(3) www.ulc.ca
(4) www.osha.gov
argusdcpower.com
1. Please read this manual prior to use to become familiar with the products numerous features and operating
procedures. To obtain a maximum degree of safety, follow the sequences as outlined.
2. This manual provides warnings and special notes for the user:
a. Points that are vital to the proper operation of the product or the safety of the operator are
indicated by the heading: WARNING.
b. A notation that is in Bold or Italic typeface covers points that are important to the
performance or ease of use of the product.
3. Before using the product, read all instructions and cautionary markings on the product and any equipment
connected to the product.
4. Do not expose the product to rain or snow; install only in a clean, dry environment.
5. CAUTION Unless otherwise noted, use of an attachment not recommended or sold by the product
manufacturer may result in a risk of fire, electric shock, or injury to persons.
6. CAUTION Do not operate the product if it has received a sharp blow, it has been dropped, or otherwise
damaged in any way return it to a qualified service center for repair.
7. CAUTION Do not disassemble the product call our qualified service centers for servicing. Incorrect
reassembling may result in a risk of electrical shock or fire.
8. WARNING The output voltages of the product are hazardous. Extreme caution should be maintained when
servicing or touching conductive components connected to the products output.
TABLE OF CONTENTS
1
INTRODUCTION ............................................................................................................................................................. 1
1.1
1.2
1.3
OPERATION ................................................................................................................................................................ 10
6.1
6.2
6.3
6.4
Packing Materials.......................................................................................................................................... 5
Check for Damage ........................................................................................................................................ 5
INSTALLATION .............................................................................................................................................................. 6
4.1
4.2
4.3
Front Panel.................................................................................................................................................... 2
Rear Panel .................................................................................................................................................... 3
True Module Fail Alarm................................................................................................................................. 3
Heat Dissipation ............................................................................................................................................ 3
Over Temperature Protection ....................................................................................................................... 3
Wide AC Range ............................................................................................................................................ 4
AC Inrush/Transient Suppression ................................................................................................................. 4
Soft Start ....................................................................................................................................................... 4
Start Delay .................................................................................................................................................... 4
Current Limit/Short Circuit Protection ........................................................................................................... 4
Power Limiting............................................................................................................................................... 4
High Voltage Shutdown (HVSD) ................................................................................................................... 4
Battery Eliminator Operation......................................................................................................................... 4
INSPECTION.................................................................................................................................................................. 5
3.1
3.2
MAINTENANCE ........................................................................................................................................................... 14
8.1
8.2
Fan Replacement........................................................................................................................................ 14
MOV Replacement...................................................................................................................................... 15
Numbering System...................................................................................................................................... 16
Acronyms and Definitions ........................................................................................................................... 16
FIGURES
Figure 1Cordex 125-4.4kW rectifier front panel ............................................................................................................. 2
Figure 2CAN serial ports and termination selection ....................................................................................................... 9
Figure 3Fan replacement ............................................................................................................................................. 14
Figure 4MOV replacement ........................................................................................................................................... 15
ii
Introduction
1.1
NOTE: To aid the user with installation, frequent reference is made to drawings located at the rear of the manual.
1.2
Product Overview
A complete Cordex rectifier system consists of one or more power modules in a common shelf enclosure. The
shelf has connections for AC inputs, DC output, and system communications.
Cordex rectifier modules use a high frequency, switched mode conversion technique to provide a fully regulated
and isolated DC output from the AC mains. The rectifier input is wide range to allow use on 208/220/240Vac
50/60Hz electrical service.
Rectifier power modules are hot swappable meaning they can be inserted or removed from the shelf without
cutting power to or from the system or the load.
Additional power modules can be included with the system at the time of ordering or added after the shelf has
been installed.
The shelf rectifier system is designed to operate with the Argus Cordex System Controller (CXC).
The CXC allows the user to configure, monitor and control the entire DC power system from its touch screen
display similar to that used in a Personal Digital Assistant (PDA). Other features of the unit include temperature
compensation, auto equalization, remote access, dial out on alarm, battery diagnostics, as well as Web server
and Simple Network Management Protocol (SNMP) support for configuration and monitoring.
Details of controller operation are provided in the current version software manual.
There are two external CXC models of the system controller that communicate with the shelf via offset RJ-12
shelf connectors. The CXCR is mounted in a rack and the CXCP is (factory) mounted in a panel.
See manual #018-570-B2.
1.3
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
010-589-C0 Rev A WC
Page 1 of 16
Rectifier Features
2.1
Front Panel
LEDs
Thumbscrew
LEDs
The front panel LEDs provide:
Rectifier status summary will show the rectifier alarm status, communication fail status and rectifier on/off status.
2.1.1.1
AC ON
The top LED (green) is on when AC is within valid range. The LED will flash (~2Hz) when AC is
outside the nominal range AC voltage is invalid if the AC Mains Low or AC Mains High
alarm is active. The LED turns off when AC has failed.
2.1.1.2
DC ON
The middle LED (green) is on when the rectifier is delivering power to the load. The LED will
flash when communication is lost. The LED turns off when the rectifier is off; e.g., when
commanded via the CXC.
2.1.1.3
ALARM
The bottom LED (red) is on continuously in the event of an active Module Fail alarm; if the
module is unable to source power as a result of any of the following conditions:
Output fuse blown
High voltage (OVP) shutdown
UPF fail
The LED will flash (~2Hz) when a minor alarm is detected; if the modules output capability has
been reduced or a minor component failure is detected during the following conditions:
VAC meter fail
Fan (1 or 2) fail
Current limit (programmable option)
Temperature sense fail
AC foldback
Low output voltage
Power limit (programmable option)
Soft start operation
Remote equalize
High output voltage
High temperature foldback
Communications lost.
The LED remains off in the absence of an alarm. If the unit output is not connected to a battery
or parallel rectifier, the LED will extinguish if no AC power is present.
Argus Technologies Ltd.
Printed in Canada. 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
010-589-C0 Rev A WC
Page 2 of 16
2.1.1.4
2.1.1.5
2.1.2
Mechanical
A thumbscrew is provided to secure the rectifier into the shelf. During normal operation the rectifier shall be
locked into position. A handle (or grip) is incorporated into the front panel to facilitate the removal of the rectifier
from the shelf. No special tools are required.
2.2
Rear Panel
Located on the rear panel of the rectifier is a single connector for shelf power and communications.
2.3
NOTE: For Cordex rectifier systems without batteries (or with a very light load; below 2.5% of rated output) it is
recommended that the ramp test be disabled to avoid nuisance alarms. The Ramp Test feature is
enabled/disabled via the CXC menu item: Rectifiers, Configure Settings.
2.4
Heat Dissipation
Each rectifier module is equipped with at least one front-mounted fan. The fan operates at temperatures above
0C (32F). Cooling of the module is front-to-rear with the exhaust air exiting at the back. The fan is variable
speed; which is determined by heatsink temperature and load.
2.5
Under normal conditions, a battery connected to the output of the rectifier will draw current when the voltage ramp occurs. Therefore the rectifier fail
alarm will not be generated with a battery connected.
Argus Technologies Ltd.
Printed in Canada. 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
010-589-C0 Rev A WC
Page 3 of 16
2.6
Wide AC Range
A minor alarm is generated when the AC input voltage drops below specification. Rectifier output power is
reduced linearly between 187Vac and 90Vac to 40% of the rated output power (the unit will deliver derated output
power down to 80Vac).
At 80Vac, the module will shut down and will not restart until the AC is greater than or equal to 90Vac; however,
the restart voltage depends on the load current. At reduced load current the unit may restart with the input voltage
as low as 100Vac.
For voltages above 265Vac, power factor and total harmonic distortion may be derated. Up to 312Vac, the
rectifier will be operational and shall not suffer any damage.
2.7
AC Inrush/Transient Suppression
The inrush current of the rectifier module is limited to the full load steady state line current to prevent surge on the
AC line. Modules are also protected from input lightning and transient surges in accordance with IEEE/ANSI
C62.41 Category B3.
2.8
Soft Start
To eliminate an instantaneous demand on the AC source, a soft start feature is employed. Soft Start, sometimes
referred to as current walk-in, works by gradually (up to five seconds) ramping the current limit up from zero to
the actual or defined customer setting. The rectifier output voltage is ramped up from the minimum voltage to the
float voltage.
2.9
Start Delay
The rectifier modules are equipped with a delay timer in order to stagger start a series of modules to prevent
excessive loading of generators upon start up. The built-in timer delays the turn on of the module depending on
the value selected (up to 120 seconds) via the CXC. A minimum one-second delay is preset to allow charging of
the input capacitors.
2.10
2.11
Power Limiting
Each rectifier module is designed to limit power output to the module specification. This enables more current to
be supplied at lower output voltages, and allows matching of output to the demand of constant power loads,
normally seen with telecom equipment.
This feature may also be used for a faster recharge of flooded batteries paralleled with the load.
2.12
2.13
010-589-C0 Rev A WC
Page 4 of 16
Inspection
3.1
Packing Materials
All Argus products are shipped in rugged, double walled boxes and suspended via solid inserts to minimize shock
that may occur during transportation. Packaging assemblies and methods are tested to International Safe Transit
Association standards.
Products are also packaged with Cortex. This plastic wrap contains a corrosive-inhibitor that protects the product
from corrosion for up to two years.
3.1.1
NOTE: Argus Technologies is not responsible for damage caused by the improper packaging of returned products.
3.2
Verify that you have all the necessary parts per your order for proper assembly.
010-589-C0 Rev A WC
Page 5 of 16
Installation
This chapter is provided for qualified personnel to install the product, which shall be mounted in a clean and dry
environment.
NOTE: To aid the user with installation, frequent reference is made to drawings located at the rear of the manual.
4.1
Safety Precautions
WARNING
Hazardous voltages are present at the input of power systems. The DC output from the rectifiers
is classified as hazardous voltage and has a high short circuit current capacity that may cause
severe burns and electrical arcing.
Before working with any live battery or power system/distribution center, the following precautions should be
followed:
4.2
Shelf Preparation/Mounting
The 19 shelf has been designed for flush mounting in a standard 19 relay rack. Universal mounting brackets
allow for mid-mounting in a 19 or 23 rack. The configuration depends on the options chosen. See drawing 030769-06.
NOTE: The shelf shall be mounted in a clean and dry environment. Allow at least 1.75 of free space in front of the unit
for unrestricted cooling airflow.
Mounting brackets accommodate either 1 or 1-3/4 rack spacing. The shelf should be mounted to the rack using
at least two #12 24 x 1/2 screws in each bracket. Philips-type screws and screwdriver should be used to
eliminate the possibility of slippage and scratching of the units exterior. Washers (such as internal tooth) or
special screws that are designed to cut through the painted surface should be used to ensure a good chassis
ground.
4.3
NOTE: It is recommended that the first module be inserted into the front leftmost position using the side of the shelf as a
guide. Subsequent modules may be inserted using the previous module as a guide.
Tighten the screw on the bottom of the faceplate to secure the module to the shelf.
NOTE: Do not force a module into position if it does not seat properly. All modules are keyed to ensure that the correct
module (voltage/polarity) type is used.
To remove a module, loosen the screw on the bottom of the faceplate. Grasp handle and pull out, sliding the
module away from the rear connector and out of the shelf.
010-589-C0 Rev A WC
Page 6 of 16
5.1
Safety Precautions
WARNING
Hazardous AC voltages may be present. Ensure power at the AC service panel is off before
attempting work on the AC connections. Use a voltmeter to verify the absence of voltage. Clearly
mark the correct polarity of the battery leads before commencing work on DC connections.
Refer to the previous (Installation) chapter for additional safety precautions.
5.2
Tools Required
Various tools are essential for product installation. Use this list as a guide:
5.3
5.4
AC Feeder Protection/Sizing
To maximize system reliability, each power module should be fed from a dedicated protection feeder breaker
located at the AC distribution panel. The feeder breaker can also act as the disconnect device for the connected
module. Refer to the specifications at the front of this manual for Argus recommendations.
5.5
AC Input Connections
CAUTION: AC input wires should be routed in flexible or rigid conduit as far away as possible
from the DC power wires to minimize EMI disturbances.
Ensure all modules are removed from the shelf.
The wireway is designed for two customer-supplied 1 conduit fittings for AC supply located one on each side of
the shelf.
Remove the metal covers (2 places) from the rear of the shelf to expose the AC input terminal blocks, L1 and L2
for each rectifier. Each terminal pair relates to an individual power module as marked.
Attach the conduit retainers to the wireway hole(s) and route the AC cables through.
Secure the wires to the AC input and chassis ground terminals as required.
Tighten the cable connector to the AC cable (conduit similar).
Replace rear cover(s) once all connections have been completed.
010-589-C0 Rev A WC
Page 7 of 16
5.6
5.7
DC Output Connections
WARNING
Leave cables or bus bars disconnected at battery and verify output polarity using a voltmeter.
Make battery connections only after all other wiring is completed.
DC output wire shall be UL approved XHHW or RHH/RHW (for Canadian users, RW90 Type). Control and sense
wires shall be UL approved Style 1015 (for Canadian users, TEW type).
5.7.1
Cable
Terminate cable leads with appropriate crimp lugs for 3/8 holes on 1 centers.
Secure the positive and negative to the shelf output post of the correct polarity; i.e., +Vcable to +Vpost. Ensure
the washers are on the bolts in the same order in which they were shipped from the factory. Tighten the bolts as
per Customer Connections drawing at the rear of this manual.
5.7.2
Bus Bar
Bus bar adapters may be factory-installed, for the option selected, to easily accommodate direct connections to
customers vertical bus bars.
Secure the positive and negative to the shelf output post of the correct polarity; i.e., +Vcable to +Vpost. Ensure
the washers are on the bolts in the same order in which they were shipped from the factory. Tighten the bolts as
per Customer Connections drawing at the rear of this manual.
010-589-C0 Rev A WC
Page 8 of 16
5.8
5.8.1
CAN Termination
A jumper (or switch depending on your configuration) allows setting of the CAN OUT to be open (to the next shelf
in the system) or terminated. Termination must be enabled in final shelf on the CAN bus only. Access termination
selection (inside the shelf) by removing the leftmost rectifier #1 (MDL 1).
010-589-C0 Rev A WC
Page 9 of 16
Operation
6.1
Off,
Start delay,
Soft start,
Normal operation,
Turning off.
Each state is characterized as being distinct and necessary for the operation of the rectifier. These states are
briefly described below.
6.1.1
Off State
The rectifier will be in the Off state immediately after power is applied to the rectifier or after a rectifier shutdown.
The shutdown source may be remote or local shutdown, AC shutdown, OVP or thermal shutdown.
When the rectifier is in this state the DC-DC converter is turned off and the CXC will be monitoring its inputs for
the proper conditions to begin the start up sequence.
When the conditions have been met for the rectifier to start up, it will transition to the Start Delay state.
6.1.2
NOTE: Soft start, or current walk-in, gradually increases the voltage and current output of the rectifier upon startup. This
is done to reduce the instantaneous load on the AC source.
6.1.3
6.1.4
6.1.5
010-589-C0 Rev A WC
Page 10 of 16
6.2
6.2.1
Active when
Float
Equalize
Battery Test
Safe
Manual Test
Output voltage can be manually adjusted outside of the standard adjustment ranges.
Active when
Output current and power limit have been reduced due to high temperature of the
heatsink or internal ambient temperature sensor.
AC foldback mode
Output current and power limit have been reduced due to low AC input voltage. Note:
this will reduce the risk of tripping an AC breaker due to increased AC current draw as
the AC voltage decreases.
Output current limit has been reduced due to a short circuit at the output.
6.3
010-589-C0 Rev A WC
Page 11 of 16
6.4
Setting
Default
90 160V
130.5V
90 160V
132.9V
90 160V
106.3V
OVP
137.8V
9 100%
100%
0 100%
100%
0 250s
1s
0 600s
0s
90 160V
106.3V
90 160V
134.1V
EQ Timeout
1 2399h
30h
BT Timeout
1 250h
8h
Softstart Ramp-rate
Normal/Fast
Normal
CL/PL Alarm
Enable/Disable
Enable
Remote Shutdown
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
010-589-C0 Rev A WC
Page 12 of 16
System Startup
After completing the shelf wiring and installation, perform the following startup and test procedure to ensure
proper operation:
7.1
7.2
7.3
7.4
Ensure AC is off, battery is disconnected, and all power modules are removed from the shelf.
Triple check the polarity of all connections.
Verify correct battery polarity using a voltmeter (ensuring no cells or batteries are reversed).
Connect battery as required to the output of the system or turn on battery breaker.
Install remaining power modules.
In the adjustments menu of the CXC, set Float and Equalize voltage to the levels specified by the battery
manufacturer.
Using the CXC, test functionality of various module alarms and controls. In addition, perform a load test with
the system using a resistive load box as needed.
CXC Reset
The reset button located on the front panel of the optional CXC is for restarting the microprocessor. When
pressed momentarily, the unit beeps twice then resets. The front-panel LEDs will illuminate temporarily, but will
extinguish after the system has finished its 15-second self-test.
010-589-C0 Rev A WC
Page 13 of 16
Maintenance
Although very little maintenance is required with Argus systems, routine checks and adjustments are
recommended to ensure optimum system performance. Qualified service personnel should do repairs.
The following table lists a few maintenance procedures for this system. These procedures should be performed at
least once a year.
WARNING: HIGH VOLTAGE AND SHOCK HAZARD.
Use extreme care when working inside the shelf while the system is energized.
Do not make contact with live components or parts.
Circuit cards, including RAM chips, can be damaged by static electricity. Always wear a grounded
wrist strap when handling or installing circuit cards.
Procedure
Clean ventilation openings
Inspect all system connections (re-torque as necessary)
Verify alarm/control settings
Verify alarm relay operation
Date Completed
8.1
Fan Replacement
010-589-C0 Rev A WC
Page 14 of 16
1.
2.
3.
4.
5.
6.
7.
8.
8.2
Shut off the unit and unscrew the front fastener that secures the power module to the shelf.
Slide the module 10 cm (4) out of the shelf and wait two minutes for module capacitors to discharge.
Remove the four screws (two each side) that secure the front panel to the module chassis.
Slide the front panel out.
Disconnect the fan power lead wires (one set per fan) and front panel ribbon cable from the module.
Remove the screws that secure the fans to the front panel.
Note the direction of airflow and remove the fans from the front panel.
Install the replacement fans following the preceding steps in reverse order.
MOV Replacement
010-589-C0 Rev A WC
Page 15 of 16
Argus Conventions
9.1
Numbering System
Argus Technologies uses an eight-digit drawing number system, which is broken into three blocks. The first three
digits describe the category of the product; e.g., rectifier or fuse panel. The next three digits indicate the sequence
in which the product number was allocated in a particular category. The last two digits indicate the type of
drawing, for example:
-06
-08
-20
Outline Drawing
Customer Connections
Main Assembly
Argus uses an eight-digit part numbering system for all components and sub assemblies. Each part is covered by
its own unique number. Due to the quantity, categories will not be listed within this manual.
9.2
Alternating current
American National Standards Institute
American Wire Gauge
British thermal unit
Controller area network
Canadian Electrical Code
Canadian Standards Association
Cordex series; e.g., CXC for Cordex System Controller
Direct current
Dynamic Host Configuration Protocol
Electronic Industries Alliance
Electromagnetic compatibility
Electromagnetic interference
Electromagnetic Compatibility and Radio Spectrum Matters
Electrostatic Discharge
Federal Communications Commission (for the USA)
High voltage shutdown
International Electrotechnical Commission
Institute of Electrical and Electronics Engineers
Internet Protocol
Light emitting diode
Low voltage disconnect
Metal oxide varistor
Mean time between failures
Normally closed
National Electrical Code (for the USA)
Normally open
Occupational Safety & Health Administration
Over voltage protection
Random access memory
Rack unit (1.75)
Transmission Control Protocol / Internet Protocol
Total harmonic distortion
Underwriters Laboratories
010-589-C0 Rev A WC
Page 16 of 16
REVISIONS
DESCRIPTION
REV BY
DATE
APPD
S.D.W.
5.92 150.3
5.42 137.6
7.42 188.4
6.92 175.7
10.36 263.1
9.86 250.4
11.86 301.2
11.36 288.5
16.10 408.9
15.28 388.2
17.40 441.9
17.40 441.9
LTR
6.97
6.55
6.05
5.05
177.0
166.4
153.7
128.3
REAR VIEW
REAR COVER AND MODULES ARE HIDDEN
(LIST 82 OUTPUT BARS)
0
0.93 23.6
TOP VIEW
REAR COVER IS HIDDEN
(LIST 82 OUTPUT BARS)
17.17 436.0
LIST 90
MODULE BLANK
010-589-20
4.4kW CORDEX MODULE
FRONT VIEW
DESIGN
WH/EOF
MATERIAL
EOF/J.U.
2006/05
G.S.
2006/05
APPROVED
G.S.
2006/05
FINISH
1mm
0.5mm
0.25mm
SCALE
TOLERANCES
X.X
0.04"
X.XX
0.02"
X.XXX 0.01"
2006/05
DRAWN
CHECKED
[X]
[X.X]
[X.XX]
N.T.S.
TITLE
ISSUE
DATE
B D2
030-769-06
REV
17.08 433.9
5.03 127.7
5.03 127.7
LIST 90
MODULE BLANK
010-589-20
4.4kW CORDEX MODULE
6.97 177.0
6.97 177.0
6.74 171.1
5.49 139.3
5.49 139.3
3.74 94.9
3.24 82.2
1.49 37.7
0.65 16.6
0
1.49 37.7
0.24 6.0
0
17.40 441.9
17.40 441.9
18.31 465.1
22.31 566.7
19.0 483
23.06 585.7
19.4 493
SCALE
N.T.S.
TITLE
ISSUE
DATE
SIZE TYPE DWG NO.
B D2
SHEET
OF
030-769-06
REV
REVISIONS
LTR
B
REV BY
DESCRIPTION
ADDED MOUNTING BRACKETS
DATE
APPD
S.D.W.
CAN
UNTERMINATED
CAN
TERMINATED
REMOVE COVERS
AC WIREWAY
BLANK PLATE
J8
J7
REAR VIEWS
AC WIREWAY (2 PLACES)
1.3 [34] HOLE FOR
CUSTOMER SUPPLIED
1" CONDUIT FITTING
SEE AC INPUT
DETAILS
PROTECTIVE EARTH
TERMINAL
2 PLACES
AC INPUT DETAILS
SINGLE PHASE INPUTS, 208V - 277VAC
L1
L2
L1
L2
GND
CAN H
NOT CONNECTED
CAN L
NOT CONNECTED
NOT CONNECTED
GND
CAN H
NOT CONNECTED
CAN L
NOT CONNECTED
NOT CONNECTED
L1
L2
L1
L2
L1
L2
MATERIAL
DESIGN
WH
2006/05
DRAWN
J.U.
2006/05
G.S.
2006/05
FINISH
1mm
0.5mm
0.25mm
SCALE
CHECKED
APPROVED
TOLERANCES
X.X
0.04"
X.XX
0.02"
X.XXX 0.01"
[X]
[X.X]
[X.XX]
N.T.S.
TITLE
CUSTOMER CONNECTION
19" SHELF, 4.4kW CORDEX
c 2006 ARGUS TECHNOLOGIES
O
ISSUE
DATE
SIZE TYPE DWG NO.
B D2
SHEET
OF
030-769-08
REV
POSITIVE (+)
OUTPUT TERMINAL
DC WIRING
(CUSTOMER SUPPLIED)
SCALE
N.T.S.
TITLE
CUSTOMER CONNECTION
19" SHELF, 4.4kW CORDEX
ISSUE
DATE
SIZE TYPE DWG NO.
B D2
SHEET
OF
030-769-08
REV
ARGUS TECHNOLOGIES
SPARE PARTS LIST
POWER MODULE, CORDEX 125-4.4KW
DRAWING #010-589-G0
Type WD
APPROVED: ______________
ISSUED: ______________
ITEM QTY
PART NO.
REV
DESCRIPTION
CIRCUIT DESIGNATION
OR REMARKS
List 0; ON SITE:
1
747-212-20
List 0
Assy,Fan,Cordex 24-3.1kW
Fn100,101
707-374-20
List 0
(A8)
Technical support staff are available for answering general questions related to installation, operation
and maintenance of Argus products. In Canada and the USA, call Argus toll free 7:30 am to 5:00 pm
Pacific Standard Time at:
+1-888 GO ARGUS
(+1-888-462-7487)
Training
Argus offers various levels of product and technical training. These workshops provide a mix of
theory and hands on application for qualified customers. Please consult your sales representative for
course schedules, locations and costs, or visit our website at www.argusdcpower.com.
All service, beyond initial adjustments, should be carried out by qualified factory service personnel.
For these procedures, please contact Argus Technologies at the locations listed to the right.
Product Returns
Before returning any product for service, please obtain a Return Material Authorization (RMA) number
from an Argus factory service representative. The representative will require the model and serial
number, as well as a brief description of the problem prior to issuing the RMA number. All material
must be pre-authorized before being returned.
See document 048-507-10 Warranty and Repair Information for more details.
Units must be suitably packed in the original shipping container (or equivalent) prior to re-shipping.
The box should be completely enclosed and constructed of wood or double-wall, corrugated
cardboard. At least 3 of foam or shock absorbing packing material must surround the unit.
Canada and USA toll free 24 hour emergency technical support: +1 888 GO ARGUS (462 7487)