SCOPE
This specification covers requirements for 415V/240V Miniature and/or Residual
Current Circuit Breaker suitable for installation in a switchboard (LDB).
The Miniature-Residual Current circuit breaker shall comply with the latest
revision of IS : 8828 and the associated switch board shall conform to IS : 8623
with the relevant parts of standards mentioned in clause 2.0 except where
modified or extended by the provision of this specification.
Any material and component not specifically stated in this specification but
necessary for trouble free operation of the equipment and accessories specified
herein shall deemed to be included.
2.0
3.0
SERVICE CONDITIONS
Ambient temperature
Maximum 500C.
Altitude
Relative Humidity
Approximately 97 %.
Pollution degree
4.0
CONSTRUCTION
4.1
General
The miniature circuit breakers shall be suitable for mounting in 4 ways/8 ways/ 12
ways/16 ways distribution boards with IP-42 protection.
4.2
Enclosure
The enclosure shall be manufactured from at least 2 mm thick steel sheets in
aesthetically appealing powder coated finish. The boards are to confirm to the
requirement of IS : 8623 for factory built assemblies.
4.3
4.4
4.4.1 These breakers shall be current limiting devices with an inverse time delayed
thermal trip device and an undelayed magnetic trip device to take care of steady
overload and short circuit and earth leakage faults respectively. The breakers
shall be suitable for switching/control/protection/regulation of lighting, control and
motor circuits.
4.4.2 The circuit breakers should also be suitable for protection/control/switching of
three phase, 415 Volt motors upto 7.5 kW.
4.4.3 The technical data for Circuit breakers are given in Annexure-IA.
4.4.4 The technical data for Distribution Boards are given in Annexure-IB.
ANNEXURE IA
TECHNICAL SPECIFICATION FOR
MINIATURE /RESIDUAL CURRENT CIRCUIT BREAKERS
1
2
Applicable standard
Number of poles
: IS 8828
: 3 + N for incoming MCB and RCCB if
any.
3 + N/3/1 + N / 1 for outgoing for MCB.
Rated Current
: 0.5/1/5/10/16/25/32/40/63 A
Breaking capacity
: 9 kA
Rated voltage
Frequency
11 Terminals
: Snap fitting
: IEC - 68/2
: As mentioned in para 3.0
ANNEXURE - IB
TECHNICAL SPECIFICATION FOR
DISTRIBUTION BOARDS
Applicable Standard
: IS : 8623
: Suitable with TP + N.
Enclosure
No. of outgoings
No. of incoming
: 1 No.
Mounting
Cable entry
Protection
Finishing
10 Locking
11 Bus bar
12 Arrangement of breakers
: Vertical/Horizontal arrays.
SCOPE:
This coveres requirements for switch boards for tube light & fan circuits .
2.0 CODES:
The applicable codes are as under:
IS : 1293
IS : 3954
IS : 694
IS : 5133
IS : 9224
3.0 CONSTRUNCTION:
3.1 Switch Boards
i) The switch boards shall be made of 1.6 mm thick, MS sheet with 3 mm, thick
decorative, bakelite cover. The switch boards shall be hot dip galvanised and
provided with earthing terminal, mounting holes and screws, specified number of
conduit knock outs on both the sides etc. The switch boards shall be suitable for
surface mounting. The switchboards shall mount Piano Key switches and sockets .
ii)
The switches shall be Piano Key Type single pole, quick make quick break
suitable for operation on 230 V AC supply.
iii) The sockets shall be of 5 pin type 5/15 A, 230 V AC socket with 15 A switch.
iv) The switch boards shall be adequately sized to accommodate switches/fan
regulators/sockets. All switch boards mounted items shall be fully wired by 660 V
grade PVC insulated flexible Copper wire.
v) All in-coming and out-going wires shall be suitable for loop in loop out of 4 Sq. mm
stranded Aluminium wire and tap off of 1.5 Sq. MM copper wire.
ANNEXURE I
TECHNICAL INFORMATION
1.
Rated Voltage
230 V
2.
As required
3.
4.
As required
5.
As required
6.
Top cover
Decorative Backelite 3 mm
thick
7.
Switch board
8.
Internal wiring
9.
Mounting
Flush/projected
10. Earthing
As required
SCOPE
1.1
1.2
The fixtures shall comply with the latest revision of IS:1913, IS:3287, IS:4013,
IS:1777 & IS:10322 except where modified or extended by the provision of this
specification and with the relevant parts of standards mentioned in clause 2.0.
1.3
2.0
2.1
3.0
CONSTRUCTION
3.1
All lighting fixtures shall be complete with lamp holder, control gear, reflector and
cable gland. Power Factor of the fixtures shall be not less than 0.96. Suitable p.f.
correction capacitor shall be provided wherever required.
3.2
3.2.1 The single tube economy type fixtures of the batten type shall be made of M.S.
sheet finished in white stove enamel suitable for direct fixing to wall or ceiling.
The unit shall be complete with polyester filled choke, starter and lamp holders
with end covers.
3.2.2 The single/twin tube commercial type fixtures of the channel type shall be made
of cold rolled cold annealed (C.R.C.A.) M.S. sheets finished in white/grey stove
enamel suitable for direct fixing to wall or suspended from ceiling. The unit shall
be complete with polyester filled metal cased chokes, p.f. correction capacitor,
starter and rotor locking type lamp holders with end covers.
3.2.3 The twin tube decorative type fixtures with louvres of the hexagonal pattern shall
be supplied on a channel type fixture mentioned in para 3.2.2. The louvres
Vol-II / Sec.-IV.2 / Page - 149
3.3.1 The reflector shall be made of cast aluminium anodised and electrochemically
treated for brightness to give a concentrated light distribution.
3.3.2 The control gear shall comprise ballasts, p.f. correction capacitors, iguitor. The
control gear shall be housed adjacent to lamp holder housing. The lamp holder
housing shall have radial cooling fins for efficient heat dissipation.
3.3.3 Heat resistant gasket or suitable arrangement shall be provided between the
toughened glass and the reflector, between the lamp holder housing and the
reflector and between the top canopy and the control gear housing.
3.3.4 The reflector shall be attached to the lamp holder housing by slotted/ adjustable
strips for lowering/raising to carry out relamping.
3.3.5 A cable gland shall be provided on the side of the canopy.
3.3.6 The fixture shall be suspended by means of a suspension hook in the top of the
canopy. No chain suspension is acceptable.
3.3.7 The fixture shall be suitable for 1000 W HPMV lamp or 400 W HPSV lamp.
3.4
Industrial Weather proof bulk head fixtures for conveyor Gantry lighting
and other areas
3.5.1 The fixtures shall be a single piece aluminium body finished in stove enamel grey
outside and white inside
3.5.2 The unit shall be supplied with a frosted glass, synthetic rubber gasket and a
lamp holder for 70 Watt SV lamps.
3.6
3.6.1 The reflector shall be made of cast aluminium anodised and electrochemically
treated for birghtness and of parabolic shape to give a long beam throw.
3.6.2 A toughened front glass shall be sealed into the front of the fixture body with a
heat resistant
3.6.3 The fixture shall be suitable for 1000/400 Watt HPSV lamp or 1000 W halogen
lamp. The replacement of the lamp shall be done by opening a door/opening at
the back of the fixture body.
3.6.4 The cable entry gland shall be fitted to the lamp holder housing
3.6.5 A graduated disc shall be provided to enable adjustment in the spinning angle of
the fixture after mounting the fixture on a bracket.
3.6.6 The fixture shall be mounted on a bracket
3.7
3.7.1 The reflector shall be made of two cast aluminium anodised surfaces one on
either side.
3.7.2 A heat resistant prismatic bowl refractor shall be mounted on the reflector held
with a metal ring attached to the canopy by hinge and toggle catches.
3.7.3 The fixture incorporating reflector, control gear housing, lamp holder, terminal
block shall be made of one piece aluminium sheet deep drawn and finished silver
grey to resist corrossion.
3.7.4 The cable entry shall be from the side
3.7.5 A locking device shall be provided to prevent unauthorised opening of the fixture.
3.7.6 The fixture shall be suitable for mounting 70 Watt/80 Watt/125 Watt/250 Watt/
400 Watt lamps.
3.8
3.8.1 The canopy shall be fabricated from aluminium sheets finished in gray sloving
enamel.
3.8.2 The control gear shall comprise p.f. correction capacitor, polyester filled chokes
and starters
3.8.3 The control gear and the lamp holder shall be internally wired to a terminal block.
3.8.4 A transparent bowl moulded from acrylic sheet shall be filled rigidly against a
heat resistant rubber gasket fixed to the canopy by suitable means making the
fixture dust & water proof.
3.8.5 The fixture shall be suitable for mounting on cantilevers having outside diameter
50 mm.
3.8.6 The fixture shall be suitable for Single/Twin tubes
3.9
3.9.1 A cast aluminium spigot cap shall carry an opal acrylic bowl secured to it by
screws
3.9.2 This spigot cap shall also carry the lampholder and a bridge piece supported on
two pillars.
3.9.3 An aluminium canopy shall be fixed to the bridge piece by screw to make the
whole fixture totally enclosed.
3.9.4 For fixtures with mercury vapour lamps, the control gear comprising choke,
ignitor and p.f. correction capacitor shall be housed in aluminium canopy.
3.9.5 The fixture shall also be suitable for 1000 Watt tungsten GLS lamp & 80
Watt/125 Watt mercury vapour lamp.
3.10
3.10.1 The reflector shall comprise two electrochemically brightened and anodised
aluminium reflectors of curved sections
3.10.2 The reflector unit shall be housed inside cast aluminium canopy. The canopy
shall be curved to give full length support to the reflectors.
3.10.3 The reflector shall be totally enclosed by an acrylic bowl scaled on a heat
resistant rubber gasket.
3.10.4 All control gear components, i.e. ballast, p.f. correction capacitors and starters
shall be housed inside the canopy.
3.10.5 The canopy shall have a cable entry suitable for GI pipe with outside diameter 50
mm. The fixture shall be suitable for cantilever mounting on G.I. pipe.
3.10.6 The fixture shall be suitable for 135 Watt low pressure sodium vapour lamp
3.11
3.11.1 The reflector shall consist of an opal acrylic bowl secured to a cast aluminium
spigot on a aluminium frame-work. The reflector shall be enclosed by an
aluminium canopy.
3.11.2 The aluminium frame-work shall carry the lamp holders & control gear
components like ballasts and starters.
3.11.3 The p.f. correction capacitor & the HRC fuses shall be housed in a separate box
below the framework for easy replacement.
3.11.4 The aluminium frame-work shall be fixed to a G.I. pipe
3.11.5 The G.I. pipe shall be suitable for mounting on a mast 14 m/18 m long.
3.11.6 The fixture shall be suitable for 250 Watt HPSV/400 Watt HPMV lamps.
3.12
Chokes
Capacitors
SCOPE
1.1
1.2
The receptacles shall comply with the latest version of IS 8623 except where
modified or extended by this specification and with the relevant parts of
standards mentioned in clause 2.0.
1.3
2.0
2.1
2.2
3.0
SERVICE CONDITION
3.1
Maximum 50oC
b) Altitude
c)
3.2
Location
Operating Conditions
a) Nominal system voltage
415 V ( + 10%)
b) Supply frequency
50 Hz (-5% to +3%)
c) System earrthing
Effectively earthed
9 kA
4.0
DESIGN
4.1
Electrical
The receptacle shall be designed to ensure the following :
Mechanical
The receptacle shall be designed to ensure the following :
CONSTRUCTION
5.1
The recepctle shall comprise single front panel, metal enclosed, dust & vermin
proof, floor mounted and free standing type. The frame shall be fabricated from
suitable mild steel sheets of thickness not less han 2.0 mm. The frames shall be
covered by cold-rolled steel sheets of thickness not less than 1.6 mm. Doors and
covers shall also be of cold rolled sheets of thickness not less than 1.6 mm.
5.2
The panel edges and cover / door edges shall be reinforced against distortion by
rolling, bending or by the addition of welded reinforcement members.
5.3
The complete structure shall be rigid, self-supporting, free from flaws, twists and
bends. All cutouts shall be true in shape and devoid of sharp edges.
5.4
5.5
The panel shall be supplied with base frames made of mild steel section
alongwith all necessary mounting hardware required for welding down the base
frame to the foundation / steel insert plates. The base frame height shall be such
that floor finishing (50 mm thick) after erection of the board does not obstruct the
movement of doors, covers, withdrawable modules etc.
5.6
5.7
All components in a panel shall be neatly arranged and easily accessible for
operation and maintenance.
5.8
The ON/OFF switches in a receptacle shall be rotary type, heavy duty, double
break, AC 23 category, suitable for AC supply.
5.9
Plug and socket shall be of shrouded die cast Aluminium. Sockets shall be
provided with lid safety cover.
5.10
Robust mechanical inter-lock shall be provided such that the switch can be put
ON only when the plug is fully engaged. Plug can be withdrawn only when the
switch is in OFF position. Additional inter-lock should be provided such that
covers can be opened only when the switch is in off position.
5.11
Wiring inside the receptacles shall be carried out with 1100 V grade PVC
insulated 6 Sq. mm stranded Aluminium conductor.
5.12
Terminal block in the receptacles shall be of 1100 V grade, clip on stud type,
moulded in Melamine, suitable for terminating specified cable size. All the
terminals shall be shrouded.
5.13
All wiring shall be properly supported, neatly arranged, readily accessible and
securely connected to equipment terminals and terminal blocks.
5.14
All wiring terminations shall be made with solderless crimping type tinned copper
lugs which shall firmly grip the conductor or an equally secured method.
Insulating sleeves shall be provided over the exposed parts of lugs to the extent
possible.
5.15
5.16 Galvanised steel earth bus shall be provided at the bottom welded / bolted to the
bottom of a panel.
5.17 The earth bus shall have sufficient cross section to carry the short time fault
current to earth, without exceeding the allowable temperature rise.
5.18 Suitable arrangement shall be made at each end of the earth bus for bolting to
earthing conductors. The earth bus shall be projected out of the panel ends and
shall have predrilled holes for this connection. All joint splices to earth bus shall
be made through atleast two bolts and taps by proper lug and bolts connection.
5.19 All non-current carrying metal work in a panel shall be effectively bonded to the
earth bus.
5.20 Name plates and labels
a) The receptacle shall be provided with prominent, engraved identification plates.
b) The name plates shall be of non rusting metal with white non graved letterings on
black back grounds. Inscriptions shall be subject to purchaser's approval .
c) Caution plate with the inscription " WARNING LIVE TERMINALS" shall be
provided on the front face of a receptacle. .
5.21
Painting
The sheet steel work shall be pre treated in accordance with relevant code .
Degreasing shall be done by alkaline cleaning. Rust and scales shall be removed
by pickling with acid . After pickling phosphate coating of class C in accordance
with relevant code shall be provided. The phosphated surfaces shall be applied
with stove lead oxide primer coating followed by two coats of finishing synthetic
enamel paints. Electrostatic painting is also acceptable. Finishing paint on panels
shall be shade 692 (smoke grey) in accordance with relevant code . The inner
surface of the panels shall be glossy white. For electrostatic or powder painting
manufacturer's standard shade for inner surface of the panels shall also be
acceptable. Each coat of finishing paint shall be properly stoved. The finishing
paint thickness shall not be less than 50 microns. Finished surfaces shall be
coated by peelable compound by spraying method for protection against
scratches, grease, dirt & oil spots. All hardware shall be nickel chromium plated
or zinc passivated.
SCOPE :
This specification covers requirement for procuring, commissioning and
performance testing of lead acid battery for for control, indication, alarm and
protection circuit for each 6.6 kV switchboard located in Substation IV and VI.
Any material and component not specifically stated in this but necessary for
trouble free operation of the equipment and accessories specified herein shall
deemed to be included.
2.0
STANDARDS TO BE FOLLOWED :
2.1
The Battery shall be designed to comply with all applicable provision of current
Indian standards.
Where Indian Standards are not available, International Standards which ensure
performance equivalent or superior to Indian Standards shall be followed.
Nothing in this specification shall be construed as to relieve the supplier of the
responsibility for correctness of the design and construction of the equipment.
All the standards being followed shall be listed out in the tender. Where any
foreign standard is being followed, the copy of the same shall be provided with
the tender.
Wherever service conditions and requirements laid down in this specification
differ from applicable standards, the conditions specified herein shall prevail.
2.2
The battery shall comply with all the latest applicable statutory rules, regulations,
acts and safety codes which may be in force during the period of execution and
which are related with design, construction and operation of equipment in the
locality where the equipment is to be installed.
The application acts and statutory regulations are as under :
a) Fire Insurance Regulation
b) Tariff Advisory committee Regulations
c) The Indian Electricity Act.
d) Indian Electricity rules
e) National Fire Code
f) DGMS Regulations
3.0
BATTERY
3.1
Three banks of 220 volts battery unit, one each for Substation IV, V and VI have
been envisaged. One bank of 220 V Battery unit along with associated charging
unit comprising of transformer, rectifier etc. shall be provided for control,
indication, alarm and protection circuit for each 6.6 kV switchboard located in
Substation IV and VI.
Vol-II / Sec.-IV.2 / Page - 158
3.2
The D.C. voltage shall be obtained from 415V, three phase, 4 wire, 50 Hz, AC
supply after necessary rectification by the battery charger.
3.3
3.4
The battery shall be floating on the DC bus during the normal operation. The
battery shall supply the DC power during emergency operation i.e. during failure
of AC input power to the battery charger for atleast one hour. The battery shall be
of suitable rating to meet the requirement. The scope of design, supply and
installation also includes a suitable DC Distribution Board along with necessary
wiring, metering and protection arrangements.
3.5
Capacity
1 Lot
1 set
3.6
The battery shall be maintenance free and complete with all accessories like
hydrometer, cell testing voltmeter, thermometer (glass type) with gravity
correction chart, spanner, glass funnel, Rubber siphon, Rubber Apron and gloves
etc.
3.7
TESTS :
The tenderer must ensure that the test mentioned in relevant BIS or Electricity
Rules have been performed.
ANNEXURE I
TECHNICAL PARAMETERS
a) Service
Indoor
b) No. required
c) Number of phases
Three phase
d) Frequency
50 Hz
e) Input supply
415V
+ 10%
g) Frequency variation
+ 3%
220V
+2%
+ 4% RMS
a discharged battery
8/10 Hours
l) Ambient temperature
500C
m)Relative humidity
100%
n) Cooling
Natural
1.1
SCOPE
1.1.1 This specification covers requirements for 6.6 kV grade XLPE insulated
Aluminium conductor HT cables.
1.1.2 The cable shall comply with the latest version of IS:7098 except where modified
or extended by this specification and with the relevant parts of standards
mentioned in clause 2.0.
1.1.3 Any material, component or accessory not specifically stated in this specification
but necessary for trouble free operation shall bne deemed to be included.
1.2
CODES
The other relevant standards applicable are as under :
S : 10418
Specification of drums for electric cables
IS : 8130
Conductors for insulated electric cables and flexible cords
IS : 3975
Specification for mild steel wires, strips and tapes
IS : 10462
Fictitious calculation method for determination of dimensions of
protective covering of cables. Part I elastometric and thermoplastic
insulated cables
IS : 2
Rules for rounding off values
IS : 10810
Method of test for cables (Part 0 to Part 63)
IS : 1885
Electrotechnical vacabulary part 32, cables, conductors and
accessories
IS : 4905
Methods for random sampling.
1.3
CONSTRUCTION
1.3.1 Material
(a)
(b)
The fillers and inner sheath shall be either of the following types :
Unvulcanized rubber
Thermoplastic material
Proofed tapes ( for inner sheath only)
The outer sheath shall be of Poly Vinyl Chloride (PVC) compound conforming to
the requirements of Type ST 1 compound .
Unvulcanized rubber or thermoplastic material used for filler and inner sheath
shall not be harder than PVC used for outer sheath. The material shall be chosen
to be compatible with the temperature rating of the cable (900 C) and shall have
no deleterious effect on any other component of the cable.
(c)
ii)
iii)
Galvanised steel wires/ ropes shall comply with the requirements of relevant
Code. A binder tape on the armour shall be provided.
300 mm from the nearest joint in any other wire or strip in the complete cable.
The outer sheath shall be applied by extrusion over the armouring.
The colour of the outer sheath shall be black. The thickness of outer sheath shall
be not less than 3 mm.
2.0
2.1
SCOPE
2.1.1 This specification covers requirements for 660 V/1.1 kV grade PVC insulated
(Heavy duty)Armoured Aluminium conductor electric cables.
2.1.2 The cable shall comply with the latest version of IS:1554 (Part 1) except where
modified or extended by this specification and with the relevant parts of
standards mentioned in clause 2.0.
2.1.3 Any material, component or accessory not specifically stated in this specification
but necessary for trouble free operation shall bne deemed to be included.
2.2
CODES
The other relevant standards applicable are as under :
IS : 10418 : Specification of drums for electric cables
IS : 8130
: Conductors for insulated electric cables and flexible cords
IS : 3975
: Specification for mild steel wires, strips and tapes
IS : 5831
: PVC insulation for armouring cables and sheath of electric cables
IS : 10462 : Fictitious calculation method for determination of dimensions of
protective covering of cables. Part I elastometric and thermoplastic
insulated cables
IS : 2
: Rules for rounding off values
IS : 10810 : Method of test for cables (Part 0 to Part 63)
IS : 1885
: Electrotechnical vacabulary part 32, cables, conductors and
accessories
IS : 4905
: Methods for random sampling.
2.3
CONSTRUCTION
2.3.1 Material
(a)
(b)
The fillers and inner sheath shall be either of the following types :
Unvulcanized rubber or
Thermoplastic material
Proofed tapes ( for inner sheath only)
Vol-II / Sec.-IV.2 / Page - 163
The outer sheath shall be of Poly Vinyl Chloride (PVC) compound conforming to
the requirements of Type ST 1 compound conforming to relevant codes.
Unvulcanized rubber or thermoplastic material used for filler and inner sheath
shall not be harder than PVC used for insulation and for outer sheath. The
material shall be chosen to be compatible with the temperature rating of the
cable (700 C) and shall have no deleterious effect on any other component of the
cable.
(c)
The outer most layer of the cores shall be laid together with a suitable right hand
lay and successive layers shall be laid with opposite lay. Where necessary, the
interstices shall be filled with non-hygroscopic material.
The laid up cores shall be provided with inner sheath applied either by extrusion
or by wrapping.
It shall be ensured that the shape is as circular as possible
Inner sheath shall be so applied that it fits closely on the laid up cores and it shall
be possible to remove it while terminating a cable without damaging the
insulation.
The values of thickness of inner sheath shall not be less than 0.4 mm to 0.7 mm
depending the nominal area of the conductor.
3.1
SCOPE
3.1.1 This specification covers requirements for 660 V/1.1 kV grade PVC insulated
unarmoured Aluminium conductor electric cables for power supply to light & fan
circuits.
3.1.2 The cable shall comply with the latest version of IS:694 except where modified or
extended by this specification and with the relevant parts of standards mentioned
in clause 2.0.
3.1.3 Any material, component or accessory not specifically stated in this specification
but necessary for trouble free operation shall bne deemed to be included.
3.2
CODE
The other relevant standards applicable are as under :
IS : 3961
Recommended current ratings for PVC insulated cables
IS : 5831
PVC insulation and sheath of electric cables
IS : 8130
Conductors for insulated electric cables and flexible cables
IS : 10810 Methods of tests for cables
3.3
CONSTRUCTION
3.3.1 Material
(a)
(b)
The fillers and inner sheath shall be either of the following types :
vulcanized rubber
Unvulcanized rubber
Thermoplastic material
The filler material shall be suitable for continuous operation without exceeding
700 C & compatible with other components of the cable. Unvulcanized rubber or
thermoplastic material used for filler shall not be harder than PVC used for
insulation and sheath .
3.3.2 Conductor
(a) The construction of the conductors shall be for fixed wiring. Conductors shall be
circular .
(b) The construction of the conductors shall be stranded only .
(c) The conductor shall be provided with PVC insulation applied by extrusion. The
insulation shall be so applied that it fits closely on the conductor and it shall be
possible to remove it without damage to the conductor. The thickness of the
insulation shall be between 0.7 to 1 mm .
(d) The cores shall be identified by different colouring of PVC insulation, such as
Red & Black .
(e) The cables shall have two cores laid side by side in the same plane with a
suitable right hand lay.
(f) The sheath shall be applied by extrusion. It shall be applied over the laid up
cores fitting closely. It shall be possible to remove the sheath without damage to
the sheath. The colour of the sheath shall be Black. The thickness of the sheath
shall be between 0.9 to 1.4 mm .
4.0
4.1
SCOPE
4.1.1 This specification covers requirements for 660 V/1.1 kV grade PVC insulated
Armoured copper conductor control cables.
4.1.2 The cable shall comply with the latest version of IS:1554 (Part 1) except where
modified or extended by this specification and with the relevant parts of
standards mentioned in clause 2.0.
4.1.3 Any material, component or accessory not specifically stated in this specification
but necessary for trouble free operation shall bne deemed to be included.
4.2
CODES
The other relevant standards applicable are as under :
IS : 10418 : Specification of drums for electric cables
IS : 8130
IS : 3975
IS : 5831
IS : 10462
IS : 2
IS : 10810
IS : 1885
IS : 4905
4.3
CONSTRUCTION
4.3.1
Material
(a)
(b)
The fillers and inner sheath shall be either of the following types :
Unvulcanized rubber or
Thermoplastic material
Proofed tapes ( for inner sheath only)
The outer sheath shall be of Poly Vinyl Chloride (PVC) compound conforming to
the requirements of Type ST 1 compound conforming to relevant codes.
Unvulcanized rubber or thermoplastic material used for filler and inner sheath
shall not be harder than PVC used for insulation and for outer sheath. The
material shall be chosen to be compatible with the temperature rating of the
cable (700 C) and shall have no deleterious effect on any other component of the
cable.
(c)
The conductor with protective barrier shall be provided with PVC insulation
applied by extrusion.
The average thickness of insulation shall not be less than 0.8 mm to 0.9 mm
depending upon the nominal area of the conductor. The tolerance of thickness of
insulation shall be such that the smallest of measured values of thickness of
insulation shall not fall below 0.18 mm to 0.19 mm respectively.
Core identification shall be made by colour scheme of PVC insulation by
adopting the following :
2 Core
Red, Black
3 Core
4 Core
5 Core
The outer most layer of the cores shall be laid together with a suitable right hand
lay and successive layers shall be laid with opposite lay. Where necessary, the
interstices shall be filled with non-hygroscopic material.
The laid up cores shall be provided with inner sheath applied either by extrusion
or by wrapping.
It shall be ensured that the shape is as circular as possible
Inner sheath shall be so applied that it fits closely on the laid up cores and it shall
be possible to remove it while terminating a cable without damaging the
insulation.
The values of thickness of inner sheath shall not be less than 0.3 mm.
Armouring shall be provided over the inner sheath.
The armour wires/strips shall be applied as closely as practicable.
The direction of lay of the armour shall be left hand.
A binder tape may be provided on the armour. The armour of the cables shall
consists of either galvanized round steel wires or galvanized steel strips.
The nominal thickness of steel strips shall be between 0.8 mm to 1.4 mm and the
nominal diameter of round armour wire shall be between 1.4 mm to 4 mm.
The joints in armour wires or strips shall be made by brazing or welding and any
surface irregularities shall be removed. A joint in any wire/strip shall be at least
300 mm from the nearest joint in any other wire or strip in the complete cable.
The outer sheath shall be applied by extrusion over the armouring. The colour of
the outer sheath shall be black. The minimum thickness of outer sheath shall be
1.24 mm.
5.0
6.0
SPECIAL CABLES
Special cables shall be provided including but not limited to the following:
a) Temperature detectors from HT motors to the selector switches,
b) Level indicators from coal bunker level, Silo level
c) Temperature detectors to associated electronic enclosure, etc.
These cables shall be heavy duty fire retarding self extinguishing, colour
coded, shielded, armoured copper conductor 650/1100 volts grade coaxial
screwed compensating mineral insulated etc.
7.0
PERFORMANCE
The cables shall carry the rated current for the type of installation and ambient
temperature in accordance with the relevant Code. The cable shall also be able
to withstand the fault level in accordance with the relevant Code.
8.0
9.0
ANNEXURE I
TECHNICAL INFORMATION FOR XLPE INSULATED HT CABLES
Applicable Code
- IS 7098
Cable Code
- A2XFY/2XFY
Voltage Grade
-6.6 KV
Conductor Size
- As required
No. of Cores
- Three
TECHNICAL INFORMATION FOR 660/1100 V GRADE PVC ARMOURED
CABLE
Applicable Code
IS 1554 (Part-1)
Cable Code
AYFY
Voltage Grade
660/1100 V
Conductor Size
As required
No. of Cores
3/3.5/4
TECHNICAL INFORMATION 660 /1100 V GRADE UNARMOURED CABLE
Applicable Code
- IS 694
Cable Code
- AYY
Voltage Grade
- 660/1100 V
Conductor Size
- As required
No. of Cores
- Two/Three/Four
TECHNICAL INFORMATION FOR 660/1100 V GRADE CONTROL CABLE
Applicable Code
IS 1554 (Part-1)
Cable Code
YWY/YFY
Voltage Grade
660/1100 V
Conductor Size
1.5/2.5 mm2
No. of Cores
As required
SCOPE
1.1
This covers requirements for accessories of cabling work like cable trays, cable
ladders, PVC & Steel conduits and fittings, support systems.
1.2
1.3
2.0
CODE
The applicable codes are as under :
IS 732
Code of practice for electrical wiring
IS 513
Cold rolled low carbon steel and strips .
IS 1079
Hot rolled carbon steel and strips .
IS 9537
Conduits for electrical installation
IS 2667
Fittings for rigid steel conduits for electrical wiring .
IS 8309
Compression type tubular terminal ends for Aluminium
conductors of insulated cables .
IS 2629
Recommended practice for hot dip galvanizing .
IS 2633
Methods for testing uniformity of coating of Zinc coated articles .
IS 1367
Technical supply conditions for threaded steel fasteners .
IS 1663
Method for tensile testing of steel sheet & strip of thickness
0.5 mm to 3 mm .
3.0
CONSTRUCTION
3.1
i)
In RCC trenches, the cable trays shall be of cantilever construnction, with one or
multi tiers complete with matching fittings (like elbows, bends, reducers, tees,
crosses, etc.), accessories (like side coupler plates etc.) and hardware (like bolts,
nuts, springs, washers, etc.) as may be required. In vertical sections the trays
shall be of ladder construnction with one or multi tiers complete with matching
fittings (like elbows, bends, reducers, tees, crosses etc.), accessories (like side
coupler plates etc.) and hardware (like bolts, nuts, springs, washers, etc.) as may
be required.
ii)
Cable trays, fittings and accessories shall be fabricated out of rolled Mild Steel
sheets free from flaws such as laminations, rolling marks, pitting etc. conforming
to relevant codes. Minimum thickness of Mild Steel sheets used for fabrication of
cable trays and fittings shall be 2mm. The thickness of side coupler plates shall
be minimum 3 mm. These shall be hot dip galvanized.
iii)
Cable trays in the RCC trenches shall be of standard width 250 mm and of
standard lengths 2.5 metre. Cable ladders shall be of widths varying between
150 to 250 mm and of standard lengths 2.5 metre.
iv)
Each size and type of cable tray / ladder of 2.5 metre length and 250 mm width
simply supported at the ends and uniformly loaded @ 76 kg. per metre shall not
have deflection at the mid span exceeding 7 mm.
3.2
3.3
i)
i)
Cabling Accessories:
a) Cable Glands :
Cable glands shall be single compression type suitable for the voltage grade of
cables and as per relevant codes. The glands shall be of robust construction
capable of clamping cable and cable armour (for armoured cables) firmly without
injury to insulation. The glands shall be heavy duty brass, machine finished and
nickel chrome plated of minimum 10 micron thickness. All washers and
hardware shall be made of brass with nickel chrome plating. Rubber
components shall be of neoprene and of tested quality.
b) Cable Lugs :
Cable lugs shall be tinned copper solder or crimping type suitable for the voltage
grade of cables suitable for Aluminium conductor cables and copper conductor
control cables.
c) Galvanising
Galvanising of steel components and accessories shall conform to relevant
codes. The galvanising shall be uniform, clean, smooth, continuous and free
from acid spots. Should the galvanizing of the samples be found defective, the
entire batch of steel shall have to be re-galvanised at contractor's cost after
pickling.
. The amount of zinc deposit over threaded portion of bolts, nuts, screws and
washers shall be as per relevant codes. The removal of extra zinc on threaded
portion of components shall be carefully done to ensure that the threads have
the required zinc coating on them.
d) Painting
Cable supports and cable trays mounting structures and all other non
galvanized parts shall be brushed before giving one coat of red lead primer, one
coat of oil primer followed by two finishing coats of Aluminium paint.
SCOPE
1.1
This specification covers requirements for swagged type steel tubular poles for
outdoor lighting.
1.2
The poles shall comply with the requirements of IS : 2713 except where modified
or extended by this specification and with the relevant part or standards
mentioned in clause 2.0.
1.3
2.0
3.0
CONSTRUCTION
3.1
3.2
The thickness of the steel sheets shall conform to the relevant standards.
3.3
The section shall be hard dip galvanised in accordance with the relevant
standards.
3.4
The section shall be applied with 2 coats of primer and one coat of final paint in
accordance with the relevant standards.
3.5
In case of swan neck pole, top section shall be curved in accordance with the
drawing enclosed. The lamp fixture shall freely fit in with the coupler. For other
type of poles, the lamp fixture mounted on a bracket clamped on the pole at a
height of not less than 7 m from the road surface and projecting at least 1.3 m
into the road from the centre of the pole.
3.6
The lower most section shall be provided with a base plate having holes for firm
fixation in the foundation. The height of the pole shall be 9 m.
The bidder/supplier shall submit the dimensioned drawings for different sections
for approval by Purchaser before fabrication.
SCOPE
This specification covers requirements for high masts for outdoor lighting with
street light/flood light fixtures.
2.0
CONSTRUCTION
The mast shall comprise the following components :
2.1
The mast shall comprise sections of over 6 metre length. Each section shall be
made of steel complying with I.S. 226 of appropriate grade, polygonal section,
telescopic jointed and fillet welded with the exception of site joints. The welding
shall be in accordance with B.S. 5135. Each section shall include one telescopic
and welded joint which provides diaphragm stiffness to maintain the structural
strength during delivery and in service. The whole mast shall be continuously
tapered. A door shall be provided at the base of the mast to permit clear access
to winch assembly and power supply sockets. The door shall be weather
resistant with a heavy duty lock. The base flange of welded construction shall
provide full strength to the mast assembly. The mast shall be delivered to site in
sections and joined with sleeve joints. No welded or bolted joints shall be
allowed.
2.2
The foundation shall be provided by anchor plates with high tensile bolts.
2.3
The entire mast section shall be hot dip galvanised in accordance with I.S. 2629.
Each section shall be given two coats of primer and one coat of final paint in
accordance with shade 631 of I.S. 5.
2.4
For installation and maintenance of the top luminaire assembly a winch shall be
provided at the base of the mast. The winch shall be completely self sustaining
without the need for brakes, springs, or clutches which require adjustment. The
winch shall have one or more drums corresponding to number of steel ropes
required for suspension of the top luminaire assembly. The drums shall be
suitably grooved ensuring tidy rope lay and smooth return of the rope for each
lay. At least 4 turns of rope shall remain on a drum when the top luminaire
assembly is fully lowered.
The winch shall be manually operable and also by power tools incorporating two
speed reversible 240 volt single phase 50 Hz AC/DC universal motor coupled by
a gear assembly of adequate ratio. The driving spindle shall be positively locked
when not in use by a suitable automatic means. The winch shall be self
lubricated by an oil bath. The capacity, the operating speed and the
Separate pulleys shall be mounted on a chassis integral with a sleeve which slips
over the top of the mast axially and in azimuth. The pulleys made of noncorrodible material and run on self lubricating bearings with stainless steel
spindles shall take on steel wire ropes and electric cables on suitable grooves.
Suitable guides and stops shall be provided for the steel wire ropes for correct
guiding of the luminaire assembly. The pulley assembly along with chassis shall
be hot dip galvanised in accordance with relevant code aforesaid. The assembly
shall be supplied in a weatherproof enclosure.
2.6
2.7
Stainless steel stud of diameter not less than 12 mm shall be attached to the
mast structure at a convenient point within the base compartment to provide a
earthing point.
2.8
The luminaire assembly shall consist of radial steel conduits for cables supplying
power to fixtures. The assembly shall have fixing arms and plates for mounting
junction boxes.Junction boxes in two separable halves shall provid supply of
power to different fixtures. The assembly shall be provided with buffer
arrangements to prevent damage to the mast finish.
2.9
Multicore flexible power cables shall be terminated on metal cased plug and
sockets in the base compartment of the mast. At the mast head cables shall be
connected to the weather proof junction box aforesaid with nylon glands.
2.10
Extension leads of multicore cables shall be provided with plug and socket to
enable the fixtures to be tested when in the lower most position using base
compartment socket supply.
ANNEXURE -I
TECHNICAL INFORMATION
1
Height of mast
: 14 M/18M/25M/30M
: 100mm/100mm/150mm/150 mm
Number of sections
: 2/2/3/3
Luminaire assembly
This shall comprise :
a) High mast street light fixtures with aluminium body, integral control
gear, lamp holder and variable optic reflector. The fixture shall be of
IP 54 construction and suitable for mounting 400 watt HPSV lamp.
b) Flood light fixture with aluminium body, integral control gear, lamp
holder and cradle with fixture adjuster. The unit shall be of IP 54
construction and suitable for mounting 400 watt HPSV and 1000 watt
Tungsten Halogen lamps.
b)
c)
d)
e)
Inverter emergency lights shall be provided in all sub-stations and silo loading
complex.
f)
2.0
Conveyor Accessories
2.1
2.2
2.3
switches shall also serve as belt sequence switches for the preceeding conveyor.
These switches shall have 1 NO & 1 NC change over contact. Zero speed
switches shall be provided at the tail and/or preferably on drive end of each
conveyor to keep the operational speed within a set limit. It shall have cast/metal
clad dust and weather proof enclosure.
3.0
4.0
4.1
Metal enclosed non-segregated phase bus duct assemblies shall be supplied for
incoming connection from the transformers to MCCs.
The enclosure shall be made of aluminium alloy. The section of the bus duct shall
be rectangular. The design of the bus duct enclosure shall be of sturdy
construction such that it will withstand the internal or external forces resulting from
the various operating conditions. The enclosure sheet thickness shall not be less
than 3 mm.
The entire duct shall be designed for dust, vermin and weatherproof construction.
A suitable aluminium sheet hood shall be provided to cover all outdoor bus duct
enclosure joints to facilitate additional protection against rainwater ingress. Bus
duct enclosure in the indoor portion shall have a degree of protection not less than
IP-52 and that in the outdoor portion shall have a protection not less than IP-55
accordance with IS 2147.
The inside of the bus enclosure shall be treated with black paint to enable efficient
heat dissipation. The matt paint used shall be suitable for temperature experienced
during continuous loading of the bus conductor.
Flexible expansion joints for the enclosure shall be provided wherever deemed
necessary by the Bidder. Necessary bonding shall be provided at the expansion
points if made of insulating material.
Enclosures shall be provided with flanged ends with drilling dimensions to suit the
flanges at the switchgear and transformer terminals. The flanges shall be provided
with gaskets, nuts, bolts, etc. Details of the flanges provided on
transformer/switchgear ends shall be properly co-ordinated with bus duct
Contractor.
Busbar
The material of the conductor shall be aluminium. The busbars shall be rated in
accordance with the service conditions and the rated continuous and short time
current ratings as specified.
Busbars shall be adequately supported on insulator to withstand dynamic stresses
due to short circuit current specified, without permanent deformation. Successful
bidder shall furnish calculations establishing adequacy of busbar for specified
current rating during detailed design.
All busbar joints and bus tap joints shall be either silver faced or thoroughly
cleaned at the joints, and a suitable no oxide contact grease applied before making
a joint. Plain and spring washers shall be provided to ensure good contacts at the
joints and lamps.
Flexible connections for terminations at transformer bushing and switchgear shall
also be included in the bidders scope of supply.
Expansion joints made of aluminium strips shall be provided, wherever felt
necessary by the bidder, to take care of expansion and contraction of the busbars
under normal operating conditions.
All the joints shall be tested for temperature rise to establish the adequacy of
design. The maximum temperature rise at the joints when carrying rated current
shall not exceed 55oC with silver plated joints and 40oC with all other type of joints,
over an outside ambient 50oC.
The busbar clamps at insulators shall be designed to withstand the forces due to
momentary circuit current the busbars during expansion and contraction. The
material of the clamps shall be aluminium alloy. Suitable aluminium spacers shall
be provided, wherever necessary.
All bolts, nuts and lock washers used in the bus assembly shall be of high tensile
steel, plated for corrosion resistance. Spring washers/Belleville washers shall be
used.
: IS : 933
: IS : 934
: IS : 933
The equipment shall be portable, wall mounted with refilling and recharging facility
from time to time.
6.0 MISCELLANEOUS:
6.1 Painting :
All electrical equipment should be painted with air drying synthetic enamel paint in
accordance with respective manufacturer's standard practice.
6.2 Standards :
The electrical equipment included in this tender shall comply with relevant IS
specifications and IS code of practice. In the absence of IS, BS any other standard
of repute shall be followed.
6.3 Tests:
The offer shall include all test certificates as required by ISS and Indian Electricity
Rules.
6.4 Tools & Tackles:
Tenderers shall quote separate price for standard tools and tackles required for
maintenance of the electrical equipment. This shall also include the necessary
measuring instruments, rubber mats & gloves etc.
Vol-II / Sec.-IV.2 / Page - 181