Lighting REV 0

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 24

TITLE

PROJECT
CLIENT

Lighting and Small Power D

ISSUED FOR APPROVAL

No

Rev.

TABLE OF CONTENTS
1.0.0

CODES AND STANDARDS REFERENCES

2.0.0

GENERAL

2.1.0

Scope of Document

2.2.0

Average Illuminance Level (LUX)

2.3.0

Electrical Supply System

3.0.0

LIGHTING SYSTEM DESCRIPTION

3.1.0

Internal Lighting

4.0.0

CALCULATIONS OF ILLUMINANCE FOR INTERNAL LIGHTING

4.1.0

Calculation Of Number Of Fixtures For The building

4.1.1

Calculation Of Number Of Fixtures For The control room

4.1.2

1.0.0

CODES AND STANDARDS REFERENCES


Illuminating Engineering Society, IES
Code Of Practice For Emergency Lighting (BS-5266, Part 1: 1998)
National Electric Code (NEC-1999)
IEE Wiring Regulation 16th Edition (BS-7671: 1992)
Technical Specification, Volume. II, Section 3

2.0.0

GENERAL

2.1.0

Scope of Document

The purpose of this document is to present the lighting and small power design calculation f
outside the building and provides a safe, uniform and reliable system with required illuminan
phase and 380V, three phase sockets distributed in the various areas of the building.

2.2.0

Average Illuminance Level (LUX)


Refer to
LOCATIONS
Guard House
Store

;2.3.0

Electrical Supply System

Power Supply
Supply Voltage For Lighting
;3.0.0

LIGHTING SYSTEM DESCRIPTION

The light fixtures to be installed inside the building as well as the generator shed and the tran
The lighting fixtures for the building will be(

)W Fluorescent

The lighting fixtures for the Classes, Offices, Rooms, Store, Tool Room, Kitche

The internal lighting will be controlled by snap switch mounted on the wall of th

;4.0.0

CALCULATIONS OF ILLUMINANCE FOR INTERNAL LIGHTING

As per Chartered Institution Of Building Services, CIBS, code for interior lightings, the num

Where,
E = Average illuminance level (the values as given in electrical design criteria)
n = Number of lamps per fixture
= Lumen per lamp
MF= Maintenance Factor
U = Coefficient of Utilization Factor
Assumed Maintenance Factor (MF) for the calculation of required Lighting Fixture is 80 %

As per Chartered Institution Of Building Services, CIBS, code for interior lightings, the coef
ceiling, wall and floor. The Room Index (RI) is calculated from the following formula,

RI=
Where,
L and W are the length & width of the room respectively.
HA is the mounting height of Lighting fixture from working plane.
Mounting height of Lighting fixture from Working Plane, HA = HM - Hw
Where,
Hw= height of the working plane above the finish floor of the room
HM= mounting height of the lighting fixture from the finish floor of the room
For the calculation of the number of fixtures in the following sheets, it must be noted that
Room Area, A = LW

Assumed Reflectance of Ceiling, Wall, and Floor are 70%, 50% and, 20% respe
All dimensions are measured in meters unless otherwise specified
4.1.0

Calculation Of Number Of Fixtures For The building

Description
Room Length
Room Width
Room Height
Area
suspension height
Working Plane height
Mounting Height
Reflectance of Ceiling
Reflectance of Wall
Reflectance of Floor
Room Index
Coefficient Of Utilization
Maintenance Factor
Required Illumination
No Of ( 18 ) W Lamp Per Fitting
Given Lumen For One Lamp
Calculated Number Of (4*26) W, Fixture
Installed Number Of Fixtures W, 220V, 60 Hz, HPS

Lighting and Small Power Design Calculation

DOC. NO.

SEWAGE TREATMENT PLANT AT AQIQ CITY

DATE

MINISTRY OF WATER & ELECTRICITY

REV

and Small Power Design Calculation

Date

Prepared

Checked

L LIGHTING

small power design calculation for the building. The lighting design covers the requirements of all the areas in
ble system with required illuminance level based on suitable design procedures. The small power design covers
ous areas of the building.

ILLUMINANCE LEVEL (LUX)

380V, 3 Phase, 4wire, 60Hz


220V, 1 Phase, 60Hz

as the generator shed and the transformer area will be as follows,


)W Fluorescent

Rooms, Store, Tool Room, Kitchen, Office and Guard House will be surface mounted, fluorescent fixture with

p switch mounted on the wall of the room at suitable locations at a mounting height of 1200 mm from finished

L LIGHTING

ode for interior lightings, the number of lighting fixtures (N) are calculated from the following formula,

N=

NA
n U MF

ical design criteria)

equired Lighting Fixture is 80 %

ode for interior lightings, the coefficient of utilization factor can be calculated from the Room Index and the re
rom the following formula,

LW
H ( L W )

HA = HM - Hw

h floor of the room

ng sheets, it must be noted that

oor are 70%, 50% and, 20% respectively.

otherwise specified

Symbols

Values

L (m)

3.17

W (m)

7.11

H (m)

m2

22.5387

HS (m)

2.8

Hw (m)

0.75

HM (m)

2.05
70%
50%
20%

RI

1.0695027048

0.69

MF

0.8

E (LUX)

500

(lm)

1200

4.2532269022

220V, 60 Hz, HPS

16/02/2016
A

Checked

Approved

ments of all the areas inside as well as


ll power design covers the 220V, single

uorescent fixture with prismatic diffuser.

200 mm from finished floor.

owing formula,

Room Index and the reflectances of