Lighting REV 0
Lighting REV 0
Lighting REV 0
PROJECT
CLIENT
No
Rev.
TABLE OF CONTENTS
1.0.0
2.0.0
GENERAL
2.1.0
Scope of Document
2.2.0
2.3.0
3.0.0
3.1.0
Internal Lighting
4.0.0
4.1.0
4.1.1
4.1.2
1.0.0
2.0.0
GENERAL
2.1.0
Scope of Document
The purpose of this document is to present the lighting and small power design calculation f
outside the building and provides a safe, uniform and reliable system with required illuminan
phase and 380V, three phase sockets distributed in the various areas of the building.
2.2.0
;2.3.0
Power Supply
Supply Voltage For Lighting
;3.0.0
The light fixtures to be installed inside the building as well as the generator shed and the tran
The lighting fixtures for the building will be(
)W Fluorescent
The lighting fixtures for the Classes, Offices, Rooms, Store, Tool Room, Kitche
The internal lighting will be controlled by snap switch mounted on the wall of th
;4.0.0
As per Chartered Institution Of Building Services, CIBS, code for interior lightings, the num
Where,
E = Average illuminance level (the values as given in electrical design criteria)
n = Number of lamps per fixture
= Lumen per lamp
MF= Maintenance Factor
U = Coefficient of Utilization Factor
Assumed Maintenance Factor (MF) for the calculation of required Lighting Fixture is 80 %
As per Chartered Institution Of Building Services, CIBS, code for interior lightings, the coef
ceiling, wall and floor. The Room Index (RI) is calculated from the following formula,
RI=
Where,
L and W are the length & width of the room respectively.
HA is the mounting height of Lighting fixture from working plane.
Mounting height of Lighting fixture from Working Plane, HA = HM - Hw
Where,
Hw= height of the working plane above the finish floor of the room
HM= mounting height of the lighting fixture from the finish floor of the room
For the calculation of the number of fixtures in the following sheets, it must be noted that
Room Area, A = LW
Assumed Reflectance of Ceiling, Wall, and Floor are 70%, 50% and, 20% respe
All dimensions are measured in meters unless otherwise specified
4.1.0
Description
Room Length
Room Width
Room Height
Area
suspension height
Working Plane height
Mounting Height
Reflectance of Ceiling
Reflectance of Wall
Reflectance of Floor
Room Index
Coefficient Of Utilization
Maintenance Factor
Required Illumination
No Of ( 18 ) W Lamp Per Fitting
Given Lumen For One Lamp
Calculated Number Of (4*26) W, Fixture
Installed Number Of Fixtures W, 220V, 60 Hz, HPS
DOC. NO.
DATE
REV
Date
Prepared
Checked
L LIGHTING
small power design calculation for the building. The lighting design covers the requirements of all the areas in
ble system with required illuminance level based on suitable design procedures. The small power design covers
ous areas of the building.
Rooms, Store, Tool Room, Kitchen, Office and Guard House will be surface mounted, fluorescent fixture with
p switch mounted on the wall of the room at suitable locations at a mounting height of 1200 mm from finished
L LIGHTING
ode for interior lightings, the number of lighting fixtures (N) are calculated from the following formula,
N=
NA
n U MF
ode for interior lightings, the coefficient of utilization factor can be calculated from the Room Index and the re
rom the following formula,
LW
H ( L W )
HA = HM - Hw
otherwise specified
Symbols
Values
L (m)
3.17
W (m)
7.11
H (m)
m2
22.5387
HS (m)
2.8
Hw (m)
0.75
HM (m)
2.05
70%
50%
20%
RI
1.0695027048
0.69
MF
0.8
E (LUX)
500
(lm)
1200
4.2532269022
16/02/2016
A
Checked
Approved
owing formula,