Configuring Fisher DVC SMART Positioners For Optimum Diagnostics
Configuring Fisher DVC SMART Positioners For Optimum Diagnostics
Configuring Fisher DVC SMART Positioners For Optimum Diagnostics
Hart Protocol
Key Features
Increased availability
Increased uptime
Decreased unscheduled outages for control valve problems
Faster problem identification and resolution
Increased maintenance effectiveness
Lower maintenance costs by pinpointing problems and eliminating
unnecessary expenditures on parts, labor, or downtime
Increased plant safety.
DVC2000 Series
Linkage-Less Feedback Sliding Stem
Linear stem movement
No linkages
No contacting parts
Magnetic
Array
On Valve
Stem
Hall Effect
Sensor
in DVC
Capabilities
High Vibration
Inaccessible Valves
Minor Loop
Feedback
Drive Signal
Output A
Gauge
I/P Converter
Air Supply
Pneumatic
Relay
Gauge
Output B
I/P Output
Pressure
Gauge
End Build
Quick Tutorial
Valve Signature Basics
Configuration
Calibration
Alerts (travel deviation, travel hi/low, supply pressure, internal device failures,
cycle count, etc) Alerts
Valve Diagnostics (Signature, Step Response, Drive Signal, Dynamic Error Band)
Suite of On-line/In-Service Tests with real-time trending of critical variables to
help pin-point problems
PD Diagnostics
On-Line (In Service) Pre-configured tests
PD One Button
On-Line In-Service
24/7 access
Non-Intrusive
Easy
Problem Description
Possible Cause
Recommended Action
Quick ly I ndicates
issue and severity
PD Diagnostics
On-Line (In Service) Friction Test
Friction/Dead Band Test
Stem deformation
Rotary plug wear
Packing issue
Trim damage
Calculates average
PD Diagnostics
Triggered Profile & Profiler
Triggered Profile
Profiler
Online Architecture
AMS Device Manager with companion software AMS ValveLink Snap-ON
connected to a HART network using Multiplexers or pass-through
technology in the DCS.
Talking to all devices and monitoring alerts in real-time and scheduling PD
diagnostics
Diagnostic Planning
Configuring the Smart Positioner
The following items needed to be accounted for, to get the
most out of an Online system:
Setting up the alerts (Travel Deviation Alert, Drive Signal Alert and Supply
Pressure Alert) these alerts are NOT configured by the factory (all Tiers)
Setting up the Alert Record (data buffer in the device) so that events can
be captured 24/7 (all Tiers)
Setting up the specification sheet in the device so that Advanced
Diagnostics can performed and analyzed properly (AD or PD Tier &
ValveLink Snap-ON)
Schedule PD One Button Sweeps which are predetermined Inline Service
tests to verify the condition of valve and positioner (PD Tier & ValveLink
Snap-ON)
Schedule PD Friction Test (PD Tier & ValveLink Snap-ON)
Setting up Triggered Profile to capture 4 HART variables based on travel
deviation (PD Tier & ValveLink Snap-ON)
Diagnostic Planning
Other Considerations
Other things to consider that are important:
Also, the assets need to be configured in Alert Monitor in AMS
Device Manager and it will be based on criticality ranking as
well
Work practices need to change to incorporate an Online AMS
Device Manager package and hopefully trips to the field are
minimized
During outages, valves should be scanned (Valve Signature) by
ValveLink Snap-ON and this should minimize the numbers of
valves for overhaul KEY POINT, BASELINE DATA SHOULD BE
COLLECTED SO THAT VARIATIONS ARE NOTICED!
Fieldvue Diagnostics
Typical Alerts
Valve Alerts
Travel Deviation
Travel Hi
Travel Lo
Travel Hi Hi
Travel Lo Lo
Travel Accumulator
Drive Signal
Supply Pressure
Cycle Count
ESD Valve Stuck
ESD Pressure Deviation
Ref. Voltage Failure
Pressure Sensor Fail
NVM Fail
Drive Current Fail
Temp Sensor Fail
Travel Sensor Fail
Auto Tvl Cal Failed
Power Starvation Alert
Calibration in Progress
Alert Record Not Empty
Alert Record Full
Variable Out of Range
Diagnostic in Progress
No Free Time
Integrator Saturated Low
Internal Sensor Out of Limits
Flash Integrity Error
Integrator Saturated High
Configuration Changed
Aux Input
Analog Input Saturated
Travel Deviation
Drive Signal
Supply P ressure
Fieldvue Diagnostics
Diagnostics Methodology
Performance Diagnostics
(on-line)
(graphs, interpretation)
Total Scan
Step Response
Stroke Valve
Analyzed Data
In Service Diagnostics
Device Status
PD One Button
PD Traces
Quick ly I ndicates
issue and severity