Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Appendix E - Sizing of Water Piping System

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Color profile: Generic CMYK printer profile

Composite Default screen

APPENDIX E

SIZING OF WATER PIPING SYSTEM

E101.1 Scope.

E101.1.1 This appendix outlines two procedures for sizing


a water piping system (see Section E103.3). The design procedures are based on the minimum static pressure available
from the supply source, the head charges in the system
caused by friction and elevation, and the rates of flow necessary for operation of various fixtures.
SECTION PC E102
INFORMATION REQUIRED
E102.1 Preliminary. Obtain the necessary information
regarding the minimum daily static service pressure in the area
where the building is to be located. If the building supply is to
be metered, obtain information regarding friction loss relative
to the rate of flow for meters in the range of sizes likely to be
used. Friction loss data can be obtained from most manufacturers of water meters.
E102.2 Demand load.
E102.2.1 Estimate the supply demand of the building main
and the principal branches and risers of the system by totaling the corresponding demand from the applicable part of
Table E 103.3(3).
E102.2.2 Estimate continuous supply demands in gallons
per minute (L/m) for lawn sprinklers, air conditioners, etc.,
and add the sum to the total demand for fixtures. The result
is the estimated supply demand for the building supply.

SECTION PC E103
SELECTION OF PIPE SIZE
E103.1 General. Decide from Table 604.3 what is the desirable minimum residual pressure that should be maintained at
the highest fixture in the supply system. If the highest group of
fixtures contains flush valves, the pressure for the group should
not be less than 15 psi (103.4 kPa) flowing. For flush tank supplies, the available pressure should not be less than 8 psi (55.2
kPa) flowing, except blowout action fixtures must not be less
than 25 psi (172.4 kPa) flowing.
E103.2 Pipe sizing.
E103.2.1 Pipe sizes can be selected according to the following procedure or by other design methods conforming to
acceptable engineering practice and approved by the department. The sizes selected must not be less than the minimum
required by this code.
E103.2.2 Water pipe sizing procedures are based on a system of pressure requirements and losses, the sum of which

2008 NEW YORK CITY PLUMBING CODE

1
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:03 AM

must not exceed the minimum pressure available at the supply source. These pressures are as follows:
1. Pressure required at fixture to produce required flow.
See Section 604.3 and Section 604.5.
2. Static pressure loss or gain (due to head) is computed
at 0.433 psi per foot (9.8 kPa/m) of elevation change.
Example: Assume that the highest fixture supply
outlet is 20 feet (6096 mm) above or below the supply source. This produces a static pressure differential of 8.66 psi (59.8 kPa) loss.
3. Loss through water meter. The friction or pressure
loss can be obtained from meter manufacturers.
4. Loss through taps in water main. [See Table
E103.3.4(4)].
5. Losses through special devices such as filters, softeners, backflow prevention devices and pressure regulators. These values must be obtained from the
manufacturers.
6. Loss through valves and fittings. Losses for these
items are calculated by converting to equivalent
length of piping and adding to the total pipe length.
[See Tables E103.3(5) and E103.3(6)].
7. Loss due to pipe friction can be calculated when the
pipe size, the pipe length and the flow through the
pipe are known. With these three items, the friction
loss can be determined using Figures E103.3(2)
through E103.3(7). For piping flow charts not
included, use manufacturers tables and velocity recommendations.
Note: For the purposes of all examples, the following
metric conversions are applicable:
1 cubic foot per minute = 0.4719 L/s
1 square foot = 0.0929 m2
1 degree = 0.0175 rad
1 pound per square inch = 6.895 kPa
1 inch = 25.4 mm
1 foot = 304.8 mm
1 gallon per minute = 3.785 L/m
E103.3 Segmented loss method. The size of water service
mains, branch mains and risers by the segmented loss method,
must be determined according to water supply demand gpm
(L/m), available water pressure psi (kPa) and friction loss
caused by the water meter and developed length of pipe feet
(m), including equivalent length of fittings. This design procedure is based on the following parameters:
Calculate the friction loss through each length of the pipe.

101

SECTION PC E101
GENERAL

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

These types of fixtures must be assigned the gallon per minute (L/m) value.
3. Selection of pipe size. This water pipe sizing procedure
is based on a system of pressure requirements and losses,
the sum of which must not exceed the minimum pressure
available at the supply source. These pressures are as follows:

Because of the variable conditions encountered in hydraulic


design, it is impractical to specify definite and detailed rules for
sizing of the water piping system. Current sizing methods do
not address the differences in the probability of use and flow
characteristics of fixtures between types of occupancies. Creating an exact model of predicting the demand for a building is
impossible and final studies assessing the impact of water conservation on demand are not yet complete. The following steps
are necessary for the segmented loss method.
1. Preliminary. Obtain the necessary information regarding the minimum daily static service pressure in the area
where the building is to be located. If the building supply
is to be metered, obtain information regarding friction
loss relative to the rate of flow for meters in the range of
sizes to be used. Friction loss data can be obtained from
manufacturers of water meters. It is essential that enough
pressure be available to overcome all system losses
caused by friction and elevation so that plumbing fixtures operate properly. Section 604.6 requires the water
distribution system to be designed for the minimum pressure available taking into consideration pressure fluctuations. The lowest pressure must be selected to guarantee
a continuous, adequate supply of water. The lowest pressure in the public main usually occurs in the summer
because of lawn sprinkling and supplying water for
air-conditioning cooling towers. Future demands placed
on the public main as a result of large growth or expansion should also be considered. The available pressure
will decrease as additional loads are placed on the public
system.
2. Demand load. Estimate the supply demand of the building main and the principal branches and risers of the system by totaling the corresponding demand from the
applicable part of Table E103.3(3). When estimating
peak demand sizing methods typically use water supply
fixture units (see Table E103.3(2)). This numerical factor measures the load-producing effect of a single
plumbing fixture of a given kind. The use of such fixture
units can be applied to a single basic probability curve (or
table), found in the various sizing methods (Table
E103.3(3)). The fixture units are then converted into gallons per minute (L/m) flow rate for estimating demand.
2.1. Estimate continuous supply demand in gallons
per minute (L/m) for lawn sprinklers, air conditioners, etc., and add the sum to the total demand
for fixtures. The result is the estimated supply
demand for the building supply. Fixture units
cannot be applied to constant use fixtures such as
hose bibbs, lawn sprinklers and air conditioners.
102

2
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:04 AM

3.1. Pressure required at the fixture to produce


required flow. See Section 604.3 and Section
604.5.
3.2. Static pressure loss or gain (due to head) is computed at 0.433 psi per foot (9.8 kPa/m) of elevation change.
3.3. Loss through a water meter. The friction or pressure loss can be obtained from the manufacturer.
3.4. Loss through taps in water main (see Table
E103.3(4)).
3.5. Losses through special devices such as filters,
softeners, backflow prevention devices and pressure regulators. These values must be obtained
from the manufacturers.
3.6. Loss through valves and fittings. Losses for
these items are calculated by converting to equivalent length of piping and adding to the total pipe
length. [see Tables E103.3(5) and E103.3(6)].
3.7. Loss due to pipe friction can be calculated when
the pipe size, the pipe length and the flow through
the pipe are known. With these three items, the
friction loss can be determined using Figures
E103.3(2) through E103.3(7). When using
charts, use pipe inside diameters. For piping flow
charts not included, use manufacturers tables
and velocity recommendations. Before attempting to size any water supply system, it is necessary to gather preliminary information which
includes available pressure, piping material,
select design velocity, elevation differences and
developed length to most remote fixture. The
water supply system is divided into sections at
major changes in elevation or where branches
lead to fixture groups. The peak demand must be
determined in each part of the hot and cold water
supply system which includes the corresponding
water supply fixture unit and conversion to gallons per minute (L/m) flow rate to be expected
through each section. Sizing methods require the
determination of the most hydraulically
remote fixture to compute the pressure loss
caused by pipe and fittings. The hydraulically
remote fixture represents the most downstream
fixture along the circuit of piping requiring the
most available pressure to operate properly.
Consideration must be given to all pressure
demands and losses, such as friction caused by
pipe, fittings and equipment, elevation and the
residual pressure required by Table 604.3. The
two most common and frequent complaints
2008 NEW YORK CITY PLUMBING CODE

Based on a system of pressure losses, the sum of which


must not exceed the minimum pressure available at the
street main or other source of supply.
Pipe sizing shall be based on (1) estimated peak demand,
(2) total pressure losses caused by difference in elevation,
equipment, developed length and pressure required at most
remote fixture, (3) loss through taps in water main, (4)
losses through fittings, filters, backflow prevention devices, valves and pipe friction.

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

about the water supply system operation are lack


of adequate pressure and noise.
Problem: What size Type L copper water pipe, service and distribution will be required to serve a two-story factory building
having on each floor, back-to-back, two toilet rooms each
equipped with hot and cold water? The highest fixture is 21 feet
(6401 mm) above the street main, which is tapped with a 2-inch
(51 mm) corporation cock at which point the minimum pressure is 55 psi (379.2 kPa). In the building basement, a 2-inch
(51 mm) meter with a maximum pressure drop of 11 psi (75.8
kPa) and 3-inch (76 mm) reduced pressure principle backflow
preventer with a maximum pressure drop of 9 psi (621 kPa) are
to be installed. The system is shown by Figure E103.3(1). To be
determined are the pipe sizes for the service main and the cold
and hot water distribution pipes.
Solution: A tabular arrangement such as shown in Table
E103.3(1) should first be constructed. The steps to be followed
are indicated by the tabular arrangement itself as they are in
sequence, columns 1 through 10 and lines A through L.
Step 1 Columns 1 and 2: Divide the system into sections
breaking at major changes in elevation or where
branches lead to fixture groups. After point B (see
Figure E103.3(1)), separate consideration will be
given to the hot and cold water piping. Enter the
sections to be considered in the service and cold
water piping in Column 1 of the tabular arrangement. Column 1 of Table E103.3(1) provides a
line-by-line recommended tabular arrangement
for use in solving pipe sizing.
The objective in designing the water supply system is to ensure an adequate water supply and pressure to all fixtures and equipment. Column 2
provides the pounds per square inch (psi) to be
considered separately from the minimum pressure
available at the main. Losses to take into consideration are the following: the differences in elevations between the water supply source and the
highest water supply outlet, meter pressure losses,
the tap in main loss, special fixture devices such as
water softeners and prevention devices and the
pressure required at the most remote fixture outlet.
The difference in elevation can result in an
increase or decrease in available pressure at the
main. Where the water supply outlet is located
above the source, this results in a loss in the available pressure and is subtracted from the pressure at
the water source. Where the highest water supply
outlet is located below the water supply source,
there will be an increase in pressure that is added to
the available pressure of the water source.
Column 3: According to Table E103.3(3), determine the gpm (L/m) of flow to be expected in each
section of the system. These flows range from 28.6
to 108 gpm. Load values for fixtures must be determined as water supply fixture units and then converted to a gallon-per-minute (gpm) rating to
determine peak demand. When calculating peak
demands, the water supply fixture units are added
2008 NEW YORK CITY PLUMBING CODE

3
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:04 AM

and then converted to the gallon-per-minute rating. For continuous flow fixtures such as hose
bibbs and lawn sprinkler systems, add the gallon-per-minute demand to the intermittent demand
of fixtures. For example, a total of 120 water supply fixture units is converted to a demand of 48
gallons per minute. Two hose bibbs x 5 gpm
demand = 10 gpm. Total gpm rating = 48.0 gpm +
10 gpm = 58.0 gpm demand.
Step 2 Line A: Enter the minimum pressure available at
the main source of supply in Column 2. This is 55
psi (379.2 kPa). The local water authorities generally keep records of pressures at different times of
day and year. The available pressure can also be
checked from nearby buildings or from fire department hydrant checks.
Line B: Determine from Section 604.3 the highest
pressure required for the fixtures on the system,
which is 15 psi (103.4 kPa), to operate a
flushometer valve. The most remote fixture outlet
is necessary to compute the pressure loss caused
by pipe and fittings, and represents the most downstream fixture along the circuit of piping requiring
the available pressure to operate properly as indicated by Table 604.3.
Line C: Determine the pressure loss for the meter
size given or assumed. The total water flow from
the main through the service as determined in Step
1 will serve to aid in the meter selected. There are
three common types of water meters; the pressure
losses are determined by the American Water
Works Association Standards for displacement
type, compound type and turbine type. The maximum pressure loss of such devices takes into consideration the meter size, safe operating capacity
(gpm) and maximum rates for continuous operations (gpm). Typically, equipment imparts greater
pressure losses than piping.
Line D: Select from Table E103.3(4) and enter the
pressure loss for the tap size given or assumed. The
loss of pressure through taps and tees in pounds per
square inch (psi) are based on the total gallon-per-minute flow rate and size of the tap.
Line E: Determine the difference in elevation
between the main and source of supply and the
highest fixture on the system. Multiply this figure,
expressed in feet, by 0.43 psi (2.9 kPa). Enter the
resulting psi loss on Line E. The difference in elevation between the water supply source and the
highest water supply outlet has a significant
impact on the sizing of the water supply system.
The difference in elevation usually results in a loss
in the available pressure because the water supply
outlet is generally located above the water supply
source. The loss is caused by the pressure required
to lift the water to the outlet. The pressure loss is
subtracted from the pressure at the water source.
Where the highest water supply outlet is located
103

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

shower at the top most floors the developed length


would be from the water meter to the most remote
flush valve on the system. A rule of thumb is that
size will become progressively smaller as the system extends farther from the main source of supply. Trial pipe size may be arrived at by the
following formula:

below the water source, there will be an increase in


pressure which is added to the available pressure
of the water source.
Lines F, G and H: The pressure losses through filters, backflow prevention devices or other special
fixtures must be obtained from the manufacturer
or estimated and entered on these lines. Equipment
such as backflow prevention devices, check
valves, water softeners, instantaneous or tankless
water heaters, filters and strainers can impart a
much greater pressure loss than the piping. The
pressure losses can range from 8 psi to 30 psi.

Line J (Pressure available to overcome pipe friction) x 100/equivalent length of run total developed length to most remote fixture x percentage
factor of 1.5 (note: a percentage factor is used only
as an estimate for friction losses imposed for fittings for initial trial pipe size) = psi (average pressure drops per 100 feet of pipe).
For trial pipe size see Figure E 103.3(3) (Type L
copper) based on 2.77 psi and a 108 gpm = 21/2
inches. To determine the equivalent length of run
to the most remote outlet, the developed length is
determined and added to the friction losses for fittings and valves. The developed lengths of the designated pipe sections are as follows:
AB
54 feet

Step 3 Line I: The sum of the pressure requirements and


losses that affect the overall system (Lines B
through H) is entered on this line. Summarizing
the steps, all of the system losses are subtracted
from the minimum water pressure. The remainder
is the pressure available for friction, defined as the
energy available to push the water through the
pipes to each fixture. This force can be used as an
average pressure loss, as long as the pressure available for friction is not exceeded. Saving a certain
amount for available water supply pressures as an
area incurs growth, or because of aging of the pipe
or equipment added to the system is recommended.
Step 4 Line J: Subtract Line I from Line A. This gives the
pressure that remains available from overcoming
friction losses in the system. This figure is a guide
to the pipe size that is chosen for each section,
incorporating the total friction losses to the most
remote outlet (measured length is called developed length).

Step 5 Column 4: Enter the length of each section from


the main to the most remote outlet (at Point E).
Divide the water supply system into sections
breaking at major changes in elevation or where
branches lead to fixture groups.
Step 6 Column 5: When selecting a trial pipe size, the
length from the water service or meter to the most
remote fixture outlet must be measured to determine the developed length. However, in systems
having a flush valve or temperature controlled

8 feet

CD

13 feet

DE

150 feet

Total developed length = 225 feet


The equivalent length of the friction loss in fittings and valves must be added to the developed
length (most remote outlet). Where the size of fittings and valves is not known, the added friction
loss should be approximated. A general rule that
has been used is to add 50 percent of the developed
length to allow for fittings and valves. For example, the equivalent length of run equals the developed length of run (225 ft x1.5 = 338 feet). The
total equivalent length of run for determining a
trial pipe size is 338 feet.

Exception: When the main is above the highest


fixture, the resulting psi must be considered a pressure gain (static head gain) and omitted from the
sums of Lines B through H and added to Line J.
The maximum friction head loss that can be tolerated in the system during peak demand is the difference between the static pressure at the highest
and most remote outlet at no-flow conditions and
the minimum flow pressure required at that outlet.
If the losses are within the required limits, then
every run of pipe will also be within the required
friction head loss. Static pressure loss is the most
remote outlet in feet x 0.433 = loss in psi caused by
elevation differences.

BC

Example: 9.36 (pressure available to overcome


pipe friction) x 100/ 338 (Equivalent length of
run = 225 x 1.5) = 2.77 psi (average pressure
drop per 100 feet of pipe).
Step 7 Column 6: Select from Table E103.3(6) the
equivalent lengths for the trial pipe size of fittings
and valves on each pipe section. Enter the sum for
each section in Column 6. (The number of fittings
to be used in this example must be an estimate.)
The equivalent length of piping is the developed
length plus the equivalent lengths of pipe corresponding to friction head losses for fittings and
valves. Where the size of fittings and valves is not
known, the added friction head losses must be
approximated. An estimate for this example is as
follows:
Step 8 Column 7: Add the figures from Column 4 and
Column 6, and enter in Column 7. Express the sum
in hundreds of feet.

104

4
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:04 AM

2008 NEW YORK CITY PLUMBING CODE

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

COLD WATER
PIPE SECTION

FITTINGS/VALVES

3-21/

A-B

B-C

Gate valves

PRESSURE LOSS
EXPRESSED AS
EQUIVALENT LENGTH
OF TUBE (FEET)

HOT WATER PIPE


SECTION

A-B

1-21/2 Side branch tee

12

1-21/2 Straight run tee

0.5

B-C

FITTINGS/VALVES

PRESSURE LOSS
EXPRESSED AS
EQUIVALENT OF TUBE
(FEET)

3-21/2 Gate valves

1-21/2 Side branch tee

12

1-2 Straight run tee

1-2 90-degree ell

C-F

1-21/

C-D
D-E

0.5

12

C-F

1-11/

1-21/2 90-degree ell

C-D

1-1/2 90-degree ell

1-21/2 Side branch tee

12

D-E

1-11/2 Side branch tee

Side branch tee

Side branch tee

Step 12 Line L: Subtract Line J from Line K and enter in


Column 10.

Step 9 Column 8: Select from Figure E103.3(3) the friction loss per 100 feet (30 480 mm) of pipe for the
gallon-per-minute flow in a section (Column 3)
and trial pipe size (Column 5). Maximum friction
head loss per 100 feet is determined on the basis of
total pressure available for friction head loss and
the longest equivalent length of run. The selection
is based on the gallon-per-minute demand, the uniform friction head loss, and the maximum design
velocity. Where the size indicated by hydraulic
table indicates a velocity in excess of the selected
velocity, a size must be selected which produces
the required velocity.

The result should always be a positive or plus


figure. If it is not, repeat the operation using Columns 5, 6, 8 and 9 until a balance or near balance is
obtained. If the difference between Lines J and K is
a high positive number, it is an indication that the
pipe sizes are too large and should be reduced, thus
saving materials. In such a case, the operations
using Columns 5, 6, 8 and 9 should again be
repeated.
The total friction losses are determined and subtracted from the pressure available to overcome
pipe friction for trial pipe size. This number is critical as it provides a guide to whether the pipe size
selected is too large and the process should be
repeated to obtain an economically designed system.

Step 10 Column 9: Multiply the figures in Columns 7 and


8 for each section and enter in Column 9.
Total friction loss is determined by multiplying
the friction loss per 100 feet (30 480 mm) for each
pipe section in the total developed length by the
pressure loss in fittings expressed as equivalent
length in feet. Note: section C-F should be considered in the total pipe friction losses only if greater
loss occurs in section C-F than in pipe section D-E.
section C-F is not considered in the total developed
length. Total friction loss in equivalent length is
determined as follows:

Answer: The final figures entered in Column 5


become the design pipe size for the respective sections. Repeating this operation a second time using
the same sketch but considering the demand for
hot water, it is possible to size the hot water distribution piping. This has been worked up as a part of
the overall problem in the tabular arrangement
used for sizing the service and water distribution
piping. Note that consideration must be given to
the pressure losses from the street main to the
water heater (section A-B) in determining the hot
water pipe sizes.

Step 11 Line K: Enter the sum of the values in Column 9.


The value is the total friction loss in equivalent
length for each designated pipe section.

FRICTION LOSS EQUIVALENT LENGTH (feet)


PIPE SECTIONS

Cold Water

Hot Water

A-B

0.69 x 3.2 = 2.21

0.69 x 3.2 = 2.21

B-C

0.085 x 3.1 = 0.26

0.16 x 1.4 = 0.22

C-D

0.20 x 1.9 = 0.38

0.17 x 3.2 = 0.54

D-E

1.62 x 1.9 = 3.08

1.57 x 3.2 = 5.02

Total pipe friction losses


(Line K)

5.93

7.99

2008 NEW YORK CITY PLUMBING CODE

5
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:05 AM

105

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

For SI: 1 foot = 304.8 mm, 1 gpm = 3.785 L/m.


FIGURE E103.3(1)
EXAMPLE-SIZING

106

6
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:08 AM

2008 NEW YORK CITY PLUMBING CODE

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

FIGURE E103.3(2)
FRICTION LOSS IN SMOOTH PIPEa (TYPE K, ASTM B 88 COPPER TUBING)

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa,
1 foot per second = 0.305 m/s.
a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram.

2008 NEW YORK CITY PLUMBING CODE

7
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:13 AM

107

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

FIGURE E103.3(3)
FRICTION LOSS IN SMOOTH PIPEa (TYPE L, ASTM B 88 COPPER TUBING)

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa,
1 foot per second = 0.305 m/s.
a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram.

108

8
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:17 AM

2008 NEW YORK CITY PLUMBING CODE

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

FIGURE E103.3(4)
FRICTION LOSS IN SMOOTH PIPEa (TYPE M, ASTM B 88 COPPER TUBING)

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa,
1 foot per second = 0.305 m/s.
a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram.

2008 NEW YORK CITY PLUMBING CODE

9
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:21 AM

109

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

FIGURE E103.3(5)
FRICTION LOSS IN FAIRLY SMOOTH PIPEa

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa,
1 foot per second = 0.305 m/s.
a. This chart applies to smooth new steel (fairly smooth) pipe and to actual diameters of standard-weight pipe.

110

10
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:26 AM

2008 NEW YORK CITY PLUMBING CODE

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

FIGURE E103.3(6)
FRICTION LOSS IN FAIRLY ROUGH PIPEa

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa,
1 foot per second = 0.305 m/s.
a. This chart applies to fairly rough pipe and to actual diameters which in general will be less than the actual diameters of the new pipe of the same kind.

2008 NEW YORK CITY PLUMBING CODE

11
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:30 AM

111

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

FIGURE E103.3(7)
FRICTION LOSS IN FAIRLY ROUGH PIPEa

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa,
1 foot per second = 0.305 m/s.
a. This chart applies to very rough pipe and existing pipe and to their actual diameters.

112

12
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:34 AM

2008 NEW YORK CITY PLUMBING CODE

2008 NEW YORK CITY PLUMBING CODE

13
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:35 AM

288
264
132
132
132

BC. . . . . . . . . . . . . . . . . . . . . 24

A B. . . . . . . . . . . . . . . . . . . 288

AB. . . . . . . . . . . . . . . . . . . . .
BC. . . . . . . . . . . . . . . . . . . . .
CD. . . . . . . . . . . . . . . . . . . . .
b
CF . . . . . . . . . . . . . . . . . . . .
b
DE . . . . . . . . . . . . . . . . . . . .

FU

Total pipe friction losses (hot)


Difference (line) minus Line K

DEb. . . . . . . . . . . . . . . . . . . . 12

Pipe section (from diagram) Diagram hot water


CD. . . . . . . . . . . . . . . . . . . . . 12
distribution piping
CF b. . . . . . . . . . . . . . . . . . . . 12

Total pipe friction losses (cold)


Difference (Line J minus Line K)

DESIGNATION
Pipe section (from diagram) Cold water
distribution piping

108.0
38.0
28.6
28.6
28.6

108.0
104.5
77.0
77.0
77.0

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 gpm = 3.785 L/m.
a. To be considered as pressure gain for fixtures below main (to consider separately, omit from I and add to J).
b. To consider separately, in K use C-F only if greater loss than above.

K
L

K
L

54
8
13
150
150

54
8
13
150
150

21/2
2
11/2
11/2
11/2

21/2
21/2
21/2
21/2
21/2

12.00
7.5
4.0
7.00
7.00

15.00
0.5
7.00
12.00
12.00

0.69
0.16
0.17
1.57
1.57

0.69
0.85
0.20
1.62
1.62

3.3
1.4
3.2
3.2
3.2

3.2
3.1
1.9
1.9
1.9

Total
Friction
Equivalent
length of
equivalent
loss per
Lb per
Gal. per min Length of Trial pipe fittings and length col. 100 feet of
4 and col. 6 trial size
square inch
through
section
size
valves
(psi)
section
(feet)
(inches)
(feet)
(100 feet)
pipe (psi)

Service and cold Minimum pressure available at main. . . . . . . . . . . . . . . . 55.00


water distribution Highest pressure required at a fixture (Section 604.3). . 15.00
pipinga
Meter loss 2 meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.00
Tap in main loss 2 tap (Table E103A). . . . . . . . . . . . . . . 1.61
Static head loss 21 x 43 psi. . . . . . . . . . . . . . . . . . . . . . . . 9.03
Special fixture loss backflow preventer. . . . . . . . . . . . . . . 9.00
Special fixture lossFilter. . . . . . . . . . . . . . . . . . . . . . . . 0.00
Special fixture lossOther. . . . . . . . . . . . . . . . . . . . . . . . 0.00
Total overall losses and requirements
(Sum of Lines B through H). . . . . . . . . . . . . . . . . . . . 45.64
Pressure available to overcome pipe friction
(Line A minus Lines B to H). . . . . . . . . . . . . . . . . . . . . 9.36

Description

Line

A
B
C
D
E
F
G
H

COLUMN

TABLE E103.3(1)
RECOMMENDED TABULAR ARRANGEMENT FOR USE IN SOLVING PIPE SIZING PROBLEMS

7.99

2.21
0.22
0.54
5.02
5.02

5.93

2.21
0.26
0.38
3.08
3.08

Friction loss
in equivalent
length col. 8
x col. 7 (psi)

1.37

3.43

Excess
pressure over
friction losses
(psi)

10

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

113

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

TABLE E103.3(2)
LOAD VALUES ASSIGNED TO FIXTURESa
LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu)
FIXTURE

TYPE OF SUPPLY
CONTROL

OCCUPANCY

Cold

Hot

Total

Bathroom group

Private

Flush tank

2.7

1.5

3.6

Bathroom group

Private

Flush valve

6.0

3.0

8.0

Bathtub

Private

Faucet

1.0

1.0

1.4

Bathtub

Public

Faucet

3.0

3.0

4.0

Bidet

Private

Faucet

1.5

1.5

2.0

Combination fixture

Private

Faucet

2.25

2.25

3.0

Dishwashing machine

Private

Automatic

1.4

1.4

Drinking fountain

Offices, etc.

3/

0.25

0.25

Kitchen sink

Private

Faucet

1.0

1.0

1.4

Kitchen sink

Hotel, restaurant

Faucet

3.0

3.0

4.0

Laundry trays (1 to 3)

Private

Faucet

1.0

1.0

1.4

Lavatory

Private

Faucet

0.5

0.5

0.7

Lavatory

Public

Faucet

1.5

1.5

2.0

Service sink

Offices, etc.

Faucet

2.25

2.25

3.0

Shower head

Public

Mixing valve

3.0

3.0

4.0

Shower head

Private

Mixing valve

1.0

1.0

1.4

Urinal

Public

1 flush valve

10.0

10.0

Urinal

Public

3/

5.0

5.0

Urinal

Public

Flush tank

3.0

3.0

Washing machine (8 lb)

Private

Automatic

1.0

1.0

1.4

Washing machine (8 lb)

Public

Automatic

2.25

2.25

3.0

Washing machine (15 lb) Public

Automatic

3.0

3.0

4.0

Water closet

Private

Flush valve

6.0

6.0

Water closet

Private

Flush tank

2.2

2.2

Water closet

Public

Flush valve

10.0

10.0

Water closet

Public

Flush tank

5.0

5.0

Water closet

Public or private

Flushometer tank

2.0

2.0

valve

flush valve

For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg.


a. For fixtures not listed , loads should be assumed by comparing the fixture to one listed using water in similar quantities and at similar rates. The assigned loads for
fixtures with both hot and cold water supplies are given for separate hot and cold water loads and for total load. The separate hot and cold water loads being
three-fourths of the total load for the fixture in each case.

114

14
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:36 AM

2008 NEW YORK CITY PLUMBING CODE

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

TABLE E103.3(3)
TABLE FOR ESTIMATING DEMAND
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH VALVES

SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS


Load

Demand

Load

(Water supply fixture units)

(Gallons per minute)

(Cubic feet per minute) (Water supply fixture units)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
25
30
35
40
45
50
60
70
80
90
100
120
140
160
180
200
225
250

3.0
5.0
6.5
8.0
9.4
10.7
11.8
12.8
13.7
14.6
15.4
16.0
16.5
17.0
17.5
18.0
18.4
18.8
19.2
19.6
21.5
23.3
24.9
26.3
27.7
29.1
32.0
35.0
38.0
41.0
43.5
48.0
52.5
57.0
61.0
65.0
70.0
75.0

0.04104
0.0684
0.86892
1.06944
1.256592
1.430376
1.577424
1.711104
1.831416
1.951728
2.058672
2.13888
2.20572
2.27256
2.3394
2.90624
2.459712
2.513184
2.566656
2.620128
2.87412
3.114744
3.328632
3.515784
3.702936
3.890088
4.27776
4.6788
5.07984
5.48088
5.81508
6.41664
7.0182
7.61976
8.15448
8.6892
9.3576
10.026

275

80.0

300
400
500
750

Demand
(Gallons per minute)

(Cubic feet per minute)

5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
25
30
35
40
45
50
60
70
80
90
100
120
140
160
180
200
225
250

15.0
17.4
19.8
22.2
24.6
27.0
27.8
28.6
29.4
30.2
31.0
31.8
32.6
33.4
34.2
35.0
38.0
42.0
44.0
46.0
48.0
50.0
54.0
58.0
61.2
64.3
67.5
73.0
77.0
81.0
85.5
90.0
95.5
101.0

2.0052
2.326032
2.646364
2.967696
3.288528
3.60936
3.716304
3.823248
3.930192
4.037136
4.14408
4.241024
4.357968
4.464912
4.571856
4.6788
5.07984
5.61356
5.88192
6.14928
6.41664
6.684
7.21872
7.75344
8.181216
8.595624
9.0234
9.75864
10.29336
10.82808
11.42964
12.0312
12.76644
13.50168

10.6944

275

104.5

13.96956

85.0

11.3628

300

108.0

14.43744

105.0

14.0364

400

127.0

16.97736

124.0

16.57632

500

143.0

19.11624

170.0

22.7256

750

177.0

23.66136

1,000

208.0

27.80544

1,000

208.0

27.80544

1,250

239.0

31.94952

1,250

239.0

31.94952

1,500

269.0

35.95992

1,500

269.0

35.95992

1,750

297.0

39.70296

1,750

297.0

39.70296

2,000

325.0

43.446

2,000

325.0

43.446

2,500

380.0

50.7984

2,500

380.0

50.7984

3,000

433.0

57.88344

3,000

433.0

57.88344

4,000

535.0

70.182

4,000

525.0

70.182

5,000

593.0

79.27224

5,000

593.0

79.27224

(continued)
2008 NEW YORK CITY PLUMBING CODE

15
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:36 AM

115

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

TABLE E103.3(4)
LOSS OF PRESSURE THROUGH TAPS AND TEES IN POUNDS PER SQUARE INCH (psi)
SIZE OF TAP OR TEE (inches)
GALLONS PER MINUTE

/8

/4

11/4

11/2

10

1.35

0.64

0.18

0.08

20

5.38

2.54

0.77

0.31

0.14

30

12.10

5.72

1.62

0.69

0.33

0.10

40

10.20

3.07

1.23

0.58

0.18

50

15.90

4.49

1.92

0.91

0.28

60

6.46

2.76

1.31

0.40

70

8.79

3.76

1.78

0.55

0.10

80

11.50

4.90

2.32

0.72

0.13

90

14.50

6.21

2.94

0.91

0.16

100

17.94

7.67

3.63

1.12

0.21

120

25.80

11.00

5.23

1.61

0.30

140

35.20

15.00

7.12

2.20

0.41

150

17.20

8.16

2.52

0.47

160

19.60

9.30

2.92

0.54

180

24.80

11.80

3.62

0.68

200

30.70

14.50

4.48

0.84

225

38.80

18.40

5.60

1.06

250

47.90

22.70

7.00

1.31

275

27.40

7.70

1.59

300

32.60

10.10

1.88

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kpa, 1 gallon per minute = 3.785 L/m.
TABLE E103.3(5)
ALLOWANCE IN EQUIVALENT LENGTHS OF PIPE FOR FRICTION LOSS IN VALVES AND THREADED FITTINGS (feet)
PIPE SIZE (inches)
1

/4

11/4

11/2

21/2

45-degree elbow

1.2

1.5

1.8

2.4

3.0

4.0

5.0

6.0

90-degree elbow

2.0

2.5

3.0

4.0

5.0

7.0

8.0

10.0

Tee, run

0.6

0.8

0.9

1.2

1.5

2.0

2.5

3.0

Tee, branch

3.0

4.0

5.0

6.0

7.0

10.0

12.0

15.0

Gate valve

0.4

0.5

0.6

0.8

1.0

1.3

1.6

2.0

Balancing valve

0.8

1.1

1.5

1.9

2.2

3.0

3.7

4.5

Plug-type cock

0.8

1.1

1.5

1.9

2.2

3.0

3.7

4.5

Check valve, swing

5.6

8.4

11.2

14.0

16.8

22.4

28.0

33.6

Globe valve

15.0

20.0

25.0

35.0

45.0

55.0

65.0

80.0

Angle valve

8.0

12.0

15.0

18.0

22.0

28.0

34.0

40.0

FITTING OR VALVE

/2

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
116

16
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:36 AM

2008 NEW YORK CITY PLUMBING CODE

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

TABLE E103.3(6)
PRESSURE LOSS IN FITTINGS AND VALVES EXPRESSED AS EQUIVALENT LENGTH OF TUBEa (feet)
FITTINGS

VALVES

NOMINAL OR
STANDARD SIZE
(inches)

90 Degree

45 Degree

Side Branch

Straight Run

Coupling

Ball

Gate

Butterfly

Check

3/

0.5

1.5

1.5

1/

0.5

5/

1.5

0.5

2.5

3/

0.5

2.5

4.5

0.5

4.5

Standard EII

90-Degree Tee

11/

5.5

0.5

0.5

0.5

5.5

11/

1.5

0.5

0.5

0.5

6.5

5.5

0.5

0.5

0.5

0.5

7.5

2.5

12

0.5

0.5

10

11.5

3.5

15

1.5

15.5

14.5

3.5

14

12.5

12.5

21

16

18.5

16

27

1.5

1.5

11.5

23.5

19

34

3.5

13.5

26.5

29

11

50

12.5

39

2
21/

3
31/

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.01745 rad.
a. Allowances are for streamlined soldered fittings and recessed threaded fittings. For threaded fittings, double the allowances shown in the table. The equivalent
lengths presented above are based on a C factor of 150 in the Hazen-Williams friction loss formula. The lengths shown are rounded to the nearest half-foot.

2008 NEW YORK CITY PLUMBING CODE

17
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:36 AM

117

Color profile: Generic CMYK printer profile


Composite Default screen

APPENDIX E

SECTION PC E201
SELECTION OF PIPE SIZE
RESERVED

118

18
18_appE_NYC_2008_IPC.prn
M:\data\CODES\STATE CODES\New York City\2008\Plumbing\Final VP\18_appE_NYC_2008_IPC.vp6
Monday, June 02, 2008 10:14:37 AM

2008 NEW YORK CITY PLUMBING CODE

You might also like