Power Distribution System
Power Distribution System
Power Distribution System
1.0-1
April 2016
Power Distribution
Systems
Sheet 01 001
Contents
Power Distribution Systems
System Design
Basic Principles. . . . . . . . . . . 1.1-1
Modern Electric Power
Technologies . . . . . . . . . . . 1.1-1
Goals of System Design . . . 1.1-2
Voltage Classifications; BILs
Basic Impulse Levels . . . . . 1.1-3
Three-Phase Transformer
Winding Connections . . . . 1.1-5
Types of SystemsRadial,
Loop, Selective, Two-Source,
Sparing Transformer, Spot
Network, Distribution . . . . 1.1-6
Health Care Facility
Design Considerations . . . 1.1-15
Generator Systems . . . . . . 1.1-18
Generator System Design
Types of Generators. . . . . . . 1.2-1
Generator Systems . . . . . . . 1.2-2
Generator Grounding. . . . . . 1.2-3
Generator Controls. . . . . . . . 1.2-4
Generator Short-Circuit
Characteristics . . . . . . . . . . 1.2-4
Generator Protection . . . . . . 1.2-5
System Analysis
Systems Analysis . . . . . . . . . 1.3-1
Short-Circuit Currents . . . . . 1.3-2
Fault Current Waveform
Relationships . . . . . . . . . . . 1.3-3
Fault Current Calculations
and Methods Index . . . . . . 1.3-4
Determine X and R from
Transformer Loss Data . . . 1.3-19
Voltage Drop
Considerations . . . . . . . . . . 1.3-20
System Application Considerations
Capacitors and
Power Factor . . . . . . . . . . . 1.4-1
Overcurrent Protection
and Coordination . . . . . . . . 1.4-3
Protection of Conductors. . . 1.4-5
Circuit Breaker Cable
Temperature Ratings . . . . . 1.4-5
Zone Selective Interlocking . 1.4-5
Ground Fault Protection . . . 1.4-6
i
Suggested Ground
Fault Settings. . . . . . . . . . . . . 1.4-6
Grounding/Ground Fault Protection
GroundingEquipment,
System, MV System,
LV System . . . . . . . . . . . . . . 1.4-9
Ground Fault Protection . . . . 1.4-11
Lightning and Surge
Protection . . . . . . . . . . . . . . 1.4-14
Grounding Electrodes . . . . . 1.4-14
MV Equipment Surge
Protection Considerations . 1.4-14
Surge Protection . . . . . . . . . . 1.4-14
Types of Surge
Protection Devices . . . . . . . 1.4-15
Power Quality
Terms, Technical Overview . . 1.4-18
SPD . . . . . . . . . . . . . . . . . . . . 1.4-19
Harmonics and
Nonlinear Loads . . . . . . . . . 1.4-21
UPS . . . . . . . . . . . . . . . . . . . . 1.4-25
Other Application Considerations
Secondary Voltage . . . . . . . . 1.4-31
Energy Conservation . . . . . . 1.4-32
Building Control Systems . . 1.4-33
Distributed Energy
Resources . . . . . . . . . . . . . . 1.4-33
Cogeneration . . . . . . . . . . . . 1.4-33
PV System Design
Considerations . . . . . . . . . . 1.4-34
Emergency Power. . . . . . . . . 1.4-35
Peak Shaving. . . . . . . . . . . . . 1.4-36
Sound Levels. . . . . . . . . . . . . 1.4-36
Reference Data
IEEE Protective Relay
Numbers . . . . . . . . . . . . . . . 1.5-1
Codes and Standards . . . . . . 1.5-6
Motor Protective
Device Data. . . . . . . . . . . . . 1.5-7
Chart of Short-Circuit
Currents for Transformers . . 1.5-9
Transformer Full Load
Amperes . . . . . . . . . . . . . . . 1.5-10
Impedances Data . . . . . . . . . 1.5-11
Transformer Losses . . . . . . . 1.5-12
Power Equipment Losses . . . 1.5-13
NEMA Enclosure Definitions. . 1.5-13
Cable R, X, Z Data . . . . . . . . . 1.5-15
Conductor Ampacities . . . . . 1.5-17
Conductor Temperature
Ratings . . . . . . . . . . . . . . . . 1.5-17
Formulas and Terms. . . . . . . 1.5-20
Seismic Requirements . . . . . 1.5-21
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
CA08104001E
21
1.0-2
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-1
Sheet 01 003
Basic Principles
The best distribution system is one
that will, cost-effectively and safely,
supply adequate electric service to
both present and future probable
loadsthis section is included to aid
in selecting, designing and installing
such a system.
The function of the electric power
distribution system in a building or
an installation site is to receive power
at one or more supply points and
to deliver it to the individual lamps,
motors and all other electrically
operated devices. The importance
of the distribution system to the
function of a building makes it almost
imperative that the best system be
designed and installed.
In order to design the best distribution
system, the system design engineer
must have information concerning the
loads and a knowledge of the various
types of distribution systems that are
applicable. The various categories of
buildings have many specific design
challenges, but certain basic principles
are common to all. Such principles,
if followed, will provide a soundly
executed design.
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.1-2
April 2016
Sheet 01 004
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-3
Sheet 01 005
Summary
It is to be expected that the engineer
will never have complete load information available when the system is
designed. The engineer will have to
expand the information made available to him on the basis of experience
with similar problems. Of course, it
is desirable that the engineer has as
much definite information as possible
concerning the function, requirements,
and characteristics of the utilization
devices. The engineer should know
whether certain loads function
separately or together as a unit, the
magnitude of the demand of the loads
viewed separately and as units, the rated
voltage and frequency of the devices,
their physical location with respect
to each other and with respect to the
source and the probability and possibility of the relocation of load devices
and addition of loads in the future.
i
ii
1
2
3
4
5
6
7
Voltage Classifications
ANSI and IEEE standards define
various voltage classifications for
single-phase and three-phase systems.
The terminology used divides voltage
classes into:
Low voltage
Medium voltage
High voltage
Extra-high voltage
Ultra-high voltage
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.1-4
April 2016
Sheet 01 006
ii
Voltage
Class
Low
voltage
Medium
voltage
3
4
5
6
7
8
9
High
voltage
11
12
2400
4160
4800
6900
13,200
13,800
23,000
34,500
46,000
69,000
208Y/120
240/120
480Y/277
4160Y/2400
8320Y/4800
12000Y/6930
12470Y/7200
13200Y/7620
13800Y/7970
20780Y/12000
22860Y/13200
24940Y/14400
34500Y/19920
115,000
138,000
161,000
230,000
Extra-high
voltage
345,000
500,000
765,000
Ultra-high
voltage
1,100,000
15.5
27
38
15
15.5
27
95
110
125
38
38
150
170
1.2
2.5
5.0
8.7
15.0
25.0
34.5
2
Nominal
System
Voltage
(kV rms)
Distribution
1.2
2.5
5.0
30
45
60
8.7
15.0
25.0
75
95
150
34.5
46.0
69.0
200
250
350
1.2
2.5
5.0
45
60
75
30
45
60
8.7
15.0
25.0
95
110
150
75
95
34.5
46.0
69.0
200
250
350
200
250
95
125
150
10
240/120
240
480
600
Power
BIL
(kV Crest) 1
150 125
200
250
14
17
18
27.0
38.0
125
150
20
110
150
200
450
550
650
350
450
550
System
Voltage
460
2300
4000
up to 500
250 to 2000
250 to 3000
480
2400
4160
4600
13,200
250 to 3000
above 2000
4800
13,800
19
95
125
150
900
825 750 650
1175 1050
900
1675 1550 1425 1300
2050 1925 1800
16
60
110
125 3
230.0
345.0
500.0
765.0
60
95
95
30
45
60
95
125
4.76
8.25
15.0
20
30
45
60
550
650
750
95 3
10
20
30
45
115.0
138.0
161.0
15
Impulse
Withstand (kV)
Voltage Recommendations by
Motor Horsepower
13
Rated Maximum
Voltage (kV rms)
Nominal
System
Voltage
(kV rms)
Impulse
Withstand (kV)
4.76
8.25
15.0
60
95
95
27.0
38.0
125
150
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-5
Sheet 01 007
Notes
1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a three-wire service or a four-wire service with a mid-tap ground.
DELTA-DELTA Connection
Phasor
Diagram:
i
ii
X2
H2
H1
H3
X1
X3
H2
X2
X0
X1
H1
H3
X3
WYE-DELTA Connection
Phasor
Diagram:
H2
X2
X1
H1
H3
X3
WYE-WYE Connection
Phasor
Diagram:
X2
H2
X0
H1
H3
X1
X3
X2
H2
X0
H0
H1
H3
X1
X3
X2
H2
4
5
6
7
8
9
10
11
12
13
X4
14
15
16
17
18
19
20
H1
H3
X1
X3
21
CA08104001E
1.1-6
April 2016
Sheet 01 008
i
ii
1
2
3
4
5
6
7
8
Types of Systems
In many cases, power is supplied by
the utility to a building at the utilization
voltage. In these cases, the distribution
of power within the building is achieved
through the use of a simple radial
distribution system.
In cases where the utility service voltage
is at some voltage higher than the
utilization voltage within the building,
the system design engineer has a choice
of a number of types of systems that
may be used. This discussion covers
several major types of distribution
systems and practical modifications
of them.
1. Simple radial
2. Loop-primary system
radial secondary system
3. Primary selective system
secondary radial system
4. Two-source primary
secondary selective system
9
10
11
12
13
14
15
16
17
18
19
20
21
600V Class
Switchboard
Distribution
Dry-Type
Transformer
Distribution
Panel
MCC
Distribution
Panel
Lighting
Panelboard
Primary
Cables
Secondary Unit
Substation
CA08104001E
April 2016
1.1-7
Sheet 01 009
CA08104001E
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
52
52
52
Tie
Breaker
52
52
13
Loop A
Loop B
NC
NO
NC
14
NC
Fault Sensors
15
16
NC
NC
NO
NC
NC
NC
17
18
19
20
21
1.1-8
April 2016
Sheet 01 010
Loop
Feeder
Loop
Feeder
Load Break
Loop Switches
ii
1
Fused
Disconnect
Switch
2
3
4
5
6
Alternate Source
3-Position
Selector Switch
Vacuum Fault
Interrupter (VFI)
8
9
10
11
12
13
15
Primary Metal-Clad
Switchgear Lineup
52
Bus A
Loop Feeder
Loop Feeder
Partial Range
Current-Limiting Fuse
Bay-O-Net
Expulsion Fuse
4-Position
T-Blade
Sectionalizing
Load-Break
Switch
52
Bus B
52
52
52
Feeder A1
14
cable has been faulted, the loop sectionalizing switches on each side of the
faulted conductor can be opened, the
loop sectionalizing switch that had
been previously left open then closed
and service restored to all secondary
unit substations while the faulted
conductor is replaced. If the fault
should occur in a conductor directly
on the load side of one of the loop
feeder breakers, the loop feeder
breaker is kept open after tripping and
the next load side loop sectionalizing
switch manually opened so that the
faulted conductor can be sectionalized
and replaced.
52
52
Feeder B1
Feeder B2
Feeder A2
To Other
Substations
NO
NC
16
NO
17
18
NC
NO
NC
19
Figure 1.1-7. Basic Primary SelectiveRadial Secondary System
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-9
Sheet 01 011
Primary
Feeders
52
Loop A
Load Break
Switches
Loop A
Fuses
Primary
Feeders
Non-Load Break
Selector Switches
Interlock
Load Break
Disconnect
Fuses
This means limited cable space especially if double lugs are furnished for
each line as shown in Figure 1.1-7 and
should a faulted primary conductor
have to be changed, both lines would
have to be de-energized for safe
changing of the faulted conductors.
A second alternative is utilizing a
three-position selector switch internal
to the transformer, allowing only one
primary feeder to be connected to
the transformer at a time without the
need for any interlocking. The selector
switch is rated for load-breaking.
If overcurrent protection is also
required, a vacuum fault interrupter
(VFI), also internal to the transformer,
may be utilized, reducing floor space.
In Figure 1.1-7 when a primary feeder
fault occurs, the associated feeder
breaker opens and the transformers
normally supplied from the faulted
feeder are out of service. Then manually, each primary switch connected to
the faulted line must be opened and
then the alternate line primary switch
can be closed connecting the transformer to the live feeder, thus restoring
service to all loads. Note that each of the
primary circuit conductors for Feeder
A1 and B1 must be sized to handle the
sum of the loads normally connected
to both A1 and B1. Similar sizing of
Feeders A2 and B2, etc., is required.
If a fault occurs in one transformer,
the associated primary fuses blow
and interrupt the service to just
the load served by that transformer.
Service cannot be restored to the loads
normally served by the faulted
transformer until the transformer
is repaired or replaced.
Cost of the primary selective
secondary radial system is greater
than that of the simple primary radial
system of Figure 1.1-1 because of the
additional primary main breakers, tie
breaker, two-sources, increased number
of feeder breakers, the use of primaryduplex or selector switches, and the
greater amount of primary feeder
cable required. The benefits from the
reduction in the amount of load lost
when a primary feeder is faulted, plus
the quick restoration of service to all
or most of the loads, may more than
offset the greater cost. Having two
sources allows for either manual or
automatic transfer of the two primary
main breakers and tie breaker should
one of the sources become unavailable.
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
April 2016
Sheet 01 012
i
ii
1
2
3
4
5
6
7
8
9
4. Two-Source Primary
Secondary Selective System
This system uses the same principle
of duplicate sources from the power
supply point using two primary main
breakers and a primary tie breaker.
The two primary main breakers and
primary tie breaker being either
manually or electrically interlocked
to prevent closing all three at the same
time and paralleling the sources. Upon
loss of voltage on one source, a manual
or automatic transfer to the alternate
source line may be used to restore
power to all primary loads.
.
10
52
52
11
52
52
12
52
52
52
To Other Substations
13
14
To Other Substations
Typical
Double-Ended
Unit
Substation
15
16
17
18
Transformer
Tie Breaker
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-11
Sheet 01 013
Sparing Transformer
K
Typical Single-Ended Substation
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 014
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
The network relay is usually a solidstate microprocessor-based component integrated into the protector
enclosure that functions to automatically close the protector only when the
voltage conditions are such that its
associated transformer will supply
power to the secondary network loads,
and to automatically open the protector when power flows from the secondary to the network transformer.
The purpose of the network protector
is to protect the integrity of the network bus voltage and the loads served
from it against transformer and primary feeder faults by quickly disconnecting the defective feedertransformer pair from the
network when backfeed occurs.
Typical Feeder
Primary Circuit
To Other
Networks
Network Transformer
Network Protector
Fuses
Optional Main, 50/51
Relaying and/or
Network Disconnect
Tie
Tie
NC
LV Feeder
Customer
Loads
Drawout
Low Voltage
Switchgear
NC
Customer
Loads
Customer
Loads
CA08104001E
April 2016
1.1-13
Sheet 01 015
i
Utility #2
Utility #1
Standby
Normal
ii
1
Utility
2
G
52 NO
52 NC
3
Loads
52
52
Main Bus
52
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 016
i
ii
1
2
3
Utility #2
4
5
6
52 NC
52 NC
NO
7
8
Bus #1
52
Bus #2
52
52
Load
Load
9
Figure 1.1-16. Two-Source Utility with
Tie Breaker
11
If looped or primary selective distribution system for the loads is used, the
buses can be extended without a shutdown by closing the tie breaker and
transferring the loads to the other bus.
13
14
15
Summary
The medium voltage system configurations shown are based on using metalclad drawout switchgear. The service
continuity required from electrical
systems makes the use of single-source
systems impractical.
52 NC
Bus #1
Utility #2
Utility #1
10
12
Utility #3
52 NC
52 NC
NO
52
52 NO 52 Typical Feeder
Bus #2
52
NO
Bus #3
52
52
52 NO
Tie Busway
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-15
Sheet 01 017
ii
Description
Ambulatory
surgical
facilities
Other health
care facilities
1. Non-essential or normal
electrical system.
2. Essential electrical system.
All electrical power in a health care
facility is important, though some
loads are not critical to the safe operation of the facility. These non-essential
or normal loads include things such
as general lighting, general lab equipment, non-critical service equipment,
patient care areas, etc. These loads are
not required to be fed from an alternate
source of power.
EES Type
Hospitals
NFPA 99 Chap. 13 Type 1
Nursing homes NFPA 99 Chap. 17 Type 2
Limited care
facilities
NFPA 99 Chap. 18 Type 2
Definition
3
4
5
6
7
8
9
10
11
Normal Source
Normal Source
Normal Source
12
13
14
15
16
Non-Essential Loads
Non-Essential Loads
17
18
Equipment
System
Automatic (Non-Delaying)
Transfer Switch
CA08104001E
19
20
21
April 2016
Sheet 01 018
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Non-Essential
Loads
Entire Essential
Electric System
(150 kVA or Less)
Standard
Section
Design
Sources
NFPA 99
NFPA 99
Uses
Emergency
Power Supply
Classification
NFPA 99
4.4.1.1.1
4.4.1.1.4 thru
4.4.4.1.1.7.2
4.4.1.1.8 (1-3)
NFPA 110
Distribution
NFPA 99
NEC
4.4.2
517.30
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-17
Sheet 01 019
Standard
Section
General
NFPA 99
NEC
4.4.2.2.2
517.31
Life safety
branch
NFPA 99
NEC
4.4.2.2.2.2
517.32
Critical branch
NFPA 99
NEC
4.4.2.2.2.3
517.33
Wiring
NFPA 99
NEC
4.4.2.2.4
517.30(C)
2. Equipment systemconsists of
major electrical equipment necessary
for patient care and Type 1 operation.
The equipment system is a subsystem
of the EES that consists of large electrical
equipment loads needed for patient
care and basic hospital operation.
Loads on the equipment system that
are essential to generator operation are
required to be fed by a non-delayed
automatic transfer switch.
The following equipment must be
arranged for delayed automatic transfer
to the emergency power supply:
1. Central suction systems for medical
and surgical functions.
2. Sump pumps and other equipment
required for the safe operation of
a major apparatus.
3. Compressed air systems for
medical and surgical functions.
4. Smoke control and stair
pressurization systems.
5. Kitchen hood supply and exhaust
systems, if required to operate
during a fire.
Standard
Section
General
NFPA 99
NEC
4.4.2.2.3
517.34
Equipment
NFPA 99
NEC
4.4.2.2.3 (3-5)
517.34(A)-(B)
Normal Source
Normal Source(s)
480/277V 1
1000 A
Service
GF
or Larger
Entrance
GF GF GF GF GF
480/277 V 1
1000 A
Service
GF
or Larger
Entrance
1000 A
Service
GF
or Larger
Entrance
Additional Level
of Ground Fault
Protection
Non-Essential Loads
GF GF GF
GF GF GF
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
G
480/277V
15
16
17
18
Non-Essential Loads
19
GF = Ground Fault Protection Required
Essential Electrical System
Ground fault protection is required for service disconnects 1000 A and larger or systems with less than 600 V phase-to-phase and greater than 150 V to
ground per NEC 230.95.
CA08104001E
20
21
April 2016
Sheet 01 020
ii
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Description
Standard
Section
Services
Feeders
NEC
NEC
230.95
215.10
Additional level
NEC
NFPA 99
517.17
4.3.2.5
Alternate source
NEC
NEC
700.26
701.26
Standard
Section
General
NFPA 99
NEC
4.3.2.2.9
517.20
Isolated power
systems
NFPA 99
NEC
4.3.2.6
517.160
Standard
Section
Grounding
NFPA 99
4.3.3.1
Emergency power
system
NFPA 99
JCAHO
4.4.4.1.1
EC.2.14(d)
Generator
NFPA 110
8.4
Transfer switches
NFPA 110
8.3.5, 8.4.6
Breakers
NFPA 99
NFPA 110
4.4.4.1.2
8.4.7
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.1-19
Sheet 01 021
ii
3
4
5
6
Utility
Transformer
Utility
Metering
G2
Gx
Typical
Generator
Breaker
10
Service Main
Emergency Bus
Normal Bus
Optional
Electrically
Operated
Stored
Energy
Breakers
Optional Electrically
Operated Stored
Energy Breakers
F1
F2
EF1
Fx
EF2
11
12
EFx
13
14
Equipment
ATS # 1
Non-Essential
Loads
EP1
Life Safety
ATS # 2
EP2
Typical
Panelboards
Critical
ATS # X
EPX
Load Shed/Load
Add ATS Units
Optional Closed
Transition
Paralleling of
Generators and
Utility
15
16
17
Figure 1.1-21. Typical One-Line for a Paralleling Switchgear Lineup Feeding the Essential Electrical System (EES)
18
19
20
21
CA08104001E
April 2016
Sheet 01 022
i
ii
Transformer
1
2
Fire-Rated Wall
or Separation Barrier
Utility
G1
Utility
Protective
Relay
Closed
Transition
Paralleling of
Generators and
Utility, Plus
Soft Loading/
Unloading
Service Main
G2
Gx
Typical
Generator
Breaker
Normal Bus
Emergency Bus
4
5
6
TIE
Optional
Electrically
Operated
Stored
Energy
Breakers
F1
7
8
9
10
F2
Fx
Optional TIE
Field Installed
Cable or Busway
Equipment
ATS # 1
Non-Essential
Loads
EP1
Electrically Operated
Stored Energy
Breakers
EF1
EF2
EFx
Life Safety
ATS # 2
EP2
Critical
ATS # X
EPX
Load Shed/
Load Add
ATS Units
Typical
Panelboards
Figure 1.1-22. Typical One-Line Health Care Facility with Complete Generator Backup and Utility Interconnect
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.2-1
Sheet 01 023
Generators and
Generator Systems
Introduction
The selection and application
of generators into the electrical
distribution system will depend on
the particular application. There are
many factors to consider, including
code requirements, environmental
constraints, fuel sources, control
complexity, utility requirements and
load requirements. The health care
requirements for legally required
emergency standby generation
systems are described starting on
Page 1.1-15. Systems described in
this section are applicable to health
care requirements, as well as other
facilities that may require a high
degree of reliability. The electrical
supply for data centers, financial
institutions, telecommunications,
government and public utilities
also require high reliability. Threats
of disaster or terror attacks have
prompted many facilities to require
complete self-sufficiency for
continuous operation.
Types of Engines
Many generator sets are relatively
small in size, typically ranging from
several kilowatts to several megawatts.
These units are often required to come
online and operate quickly. They need
to have the capacity to run for an
extended period of time. The internal
combustion engine is an excellent
choice as the prime mover for the
majority of these applications. Turbines
may also be used. Diesel-fueled
engines are the most common, but
other fuels used include natural gas,
digester gas, landfill gas, propane,
biodiesel, crude oil, steam and others.
Some campuses and industrial
facilities use and produce steam
for heating and other processes.
These facilities may find it economically
feasible to produce electricity as a
byproduct of the steam production.
These installations would typically
be classified as a cogeneration facility
producing a fairly constant power
output and operating in parallel with
the electric utility system.
Types of Generators
Generators can be either synchronous
or asynchronous. Asynchronous
generators are also referred to as
induction generators. The construction
is essentially the same as an induction
motor. It has a squirrel-cage rotor and
wound stator. An induction generator
is a motor driven above its designed
synchronous speed thus generating
power. It will operate as a motor if it
is running below synchronous speed.
The induction generator does not have
an exciter and must operate in parallel
with the utility or another source. The
induction generator requires VARs from
an external source for it to generate
power. The induction generator
operates at a slip frequency so its
output frequency is automatically
locked in with the utility's frequency.
An induction generator is a popular
choice for use when designing
cogeneration systems, where it will
operate in parallel with the utility.
This type of generator offers certain
advantages over a synchronous
generator. For example, voltage and
frequency are controlled by the utility;
thus voltage and frequency regulators
are not required. In addition, the
generator construction offers high
reliability and little maintenance.
Also, a minimum of protective relays
and controls are required. Its major
disadvantages are that it requires
VARs from the system and it normally
cannot operate as a standby/
emergency generator.
Synchronous generators, however,
are the most common. Their output is
determined by their field and governor
controls. Varying the current in the
DC field windings controls the voltage
output. The frequency is controlled
by the speed of rotation. The torque
applied to the generator shaft by
the driving engine controls the power
output. In this manner, the synchronous generator offers precise control
over the power it can generate. In
cogeneration applications, it can be
used to improve the power factor of
the system.
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.2-2
April 2016
Sheet 01 024
Generator Systems
ii
1
2
3
4
5
6
7
8
Utility
G1
10
11
ATS
12
13
14
Load
G2
Switchgear
ATS-1
ATS-2
Load 1
Load 2
G2
Switchgear
Load 1
Load 2
Load 3
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.2-3
Sheet 01 025
Generator Fundamentals
A generator consists of two primary
components, a prime mover and an
alternator. The prime mover is the
energy source used to turn the rotor
of the alternator. It is typically a
diesel combustion engine for most
emergency or standby systems.
In cogeneration applications, the
prime mover may come from a steam
driven turbine or other source. On
diesel units, a governor and voltage
regulator are used to control the speed
and power output.
The alternator is typically a synchronous machine driven by the prime
mover. A voltage regulator controls its
voltage output by adjusting the field.
The output of a single generator or
multiple paralleled generator sets is
controlled by these two inputs. The
alternator is designed to operate at a
specified speed for the required output
frequency, typically 60 or 50 Hz. The
voltage regulator and engine governor
along with other systems define the
generators response to dynamic
load changes and motor starting
characteristics.
Generators are rated in power and
voltage output. Most generators are
designed to operate at a 0.8 power
factor. For example, a 2000 kW
generator at 277/480 V would have a
kVA rating of 2500 kVA (2000 kW/
08 pf) and a continuous
current rating
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
HRG
51G
Gen
86
Phase
Relays
R
R LRG
59G
14
87GN
15
16
17
18
19
20
21
CA08104001E
1.2-4
April 2016
Sheet 01 026
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
Generator Controls
The engine generator set has controls
to maintain the output frequency
(speed) and voltage. These controls
consist of a governor and voltage
regulator. As loads change on the
system, the frequency and voltage
will change. The speed control will
then adjust the governor to correct
for the load (kW) change. The
voltage regulator will change the
field current to adjust the voltage
to the desired voltage value. These
are the basic controls found on all
synchronous generators.
Multiple generator systems require
more sophisticated controls. Generators
are paralleled in a multi-generator
system and they must share the load.
These systems often have a load shed
scheme, which adds to the complexity.
Multiple generator schemes need a
master controller to prevent units from
being connected out-of-phase. The
sequence of operation is to send a
start signal to all generators simultaneously. The first unit up to frequency
and voltage will be permitted to close
its respective breaker and energize the
paralleling bus. Breakers for the other
generators are held open, not permitted to close, until certain conditions
are met. Once the paralleling bus is
energized, the remaining generators
must be synchronized to it before
the generators can be paralleled.
Synchronization compares the voltage
phasors angle and magnitude. Both
generators must be operating at the
same frequency and phase-matched
within typically 5 to 10 degrees with
each other. The voltage magnitude
typically must be within 20 to 24%.
Generator Short-Circuit
Characteristics
If a short circuit is applied directly to
the output terminals of a synchronous
generator, it will produce an extremely
high current initially, gradually decaying
to a steady-state value. This change
is represented by a varying reactive
impedance. Three specific reactances
are used for short-circuit fault currents.
They are:
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.2-5
Sheet 01 027
Generator Protection
Generator protection will vary and
depend on the size of the generator,
type of system and importance of the
generator. Generator sizes are defined
as: small1000 kVA maximum up
to 600 V (500 kVA maximum when
above 600 V); medium over 1000 kVA
to 12,500 kVA maximum regardless
of voltage; largefrom 12,500
50,000 kVA. The simplest is a single
generator system used to feed emergency and/or standby loads. In this
case, the generator is the only source
available when it is operating and
it must keep operating until the
normal source returns.
Figure 1.2-5 Part (A) shows minimum
recommended protection for a single
generator used as an emergency or
standby system. Phase and ground
time overcurrent protection (Device
51 and 51G) will provide protection for
external faults. For medium voltage
generators, a voltage controlled time
overcurrent relay (Device 51V) is
recommended for the phase protection as it can be set more sensitive
than standard overcurrent relays and
is less likely to false operate on normal
overloads. This scheme may not
provide adequate protection for
internal generator faults when no
other power source exists. Local
generator controllers may offer
additional protection for voltage
and frequency conditions outside
the generators capabilities.
Figure 1.2-5 Part (B) shows the
recommended protection for multiple,
isolated, medium voltage, small
generators. Additional protection
may be desired and could include
generator differential, reverse power,
and loss of field protection. Differential
protection (Device 87) can be accomplished with either a self-balancing
set of CTs as in Figure 1.2-6 or with
a percentage differential scheme as
in Figure 1.2-7 on Page 1.2-6. The
percentage differential scheme
offers the advantage of reducing the
possibility for false tripping due to
CT saturation. The self-balancing
scheme offers the advantages of
increased sensitivity, needing three
current transformers in lieu of six,
and the elimination of current
transformer external wiring from
the generator location to the generator
switchgear location.
ANSI/IEEE
Std 242-1986
Generator Protection
ii
1
51
Alternate
Location
1
51V
32
40
1
2
3
51G
Gen
87
1
51
Preferred
Location
Gen
51G
(A)
(B)
6
7
8
9
50/5A
87-1
50/5A
87-2
50/5A
87-3
10
11
12
13
Gen
14
15
16
17
18
19
20
21
CA08104001E
1.2-6
April 2016
Sheet 01 028
i
ii
1
2
3
4
5
6
7
Grounding
Resistor
51G
87
01
PC
R1
R1
02
R2
Gen
OC
R2
03
87G
R3
R3
52
8
9
To Main Bus
10
11
OC = Operating coil
PC = Permissive coil
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.2-7
Sheet 01 029
i
3
81U/O
1
27/59
1
40
51V
3
ii
87B
1
32
46
1
87
87G
60
Voltage Regulator and
Metering Circuits
64
1
49
7
Gen
E
8
51G
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.2-8
April 2016
Sheet 01 030
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.2-9
Sheet 01 031
Motor loads:
200 hp motor. . . . . . . . . . . . .156 A
100 hp motor . . . . . . . . . . . . . .78 A
60 hp motor . . . . . . . . . . . . . . .48 A
Lighting load . . . . . . . . . . . . . . . .68 A
Miscellaneous loads . . . . . . . . . .95 A
Running amperes . . . . . . . . . . .445 A
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
15
13
14
Running kVA =
(445 A x 480 V x 1.732)/
1000 = 370 kVA
Starting kVA =
(516 A x 480 V x 1.732)/
1000 = 428 kVA
16
17
Solution
Generator must have a minimum
starting capability of 428 kVA and
minimum running capability of 370 kVA.
18
Figure 1.2-9. Typical Genset Installation
Note: Courtesy of Caterpillar, Inc.
CA08104001E
19
20
21
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-1
Sheet 01 033
Systems Analysis
A major consideration in the
design of a distribution system is to
ensure that it provides the required
quality of service to the various
loads. This includes serving each
load under normal conditions and,
under abnormal conditions, providing
the desired protection to service
and system apparatus so that
interruptions of service are minimized
consistent with good economic and
mechanical design.
Under normal conditions, the important technical factors include voltage
profile, losses, load flow, effects of
motor starting, service continuity and
reliability. The prime considerations
under faulted conditions are apparatus
protection, fault isolation and service
continuity. During the system preliminary planning stage, before selection
of the distribution apparatus, several
distribution systems should be analyzed and evaluated, including both economic and technical factors. During this
stage, if system size or complexity warrant, it may be appropriate to provide a
thorough review of each system under
both normal and abnormal conditions.
Harmonic analysis
Transient stability
Insulation coordination
Grounding study
Switching transient
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.3-2
April 2016
Sheet 01 034
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Short-Circuit Currents
General
The amount of current available in a
short-circuit fault is determined by the
capacity of the system voltage sources
and the impedances of the system,
including the fault. Voltage sources
include the power supply (utility or
on-site generation) plus all rotating
machines connected to the system at
the time of the fault. A fault may be
either an arcing or bolted fault. In an
arcing fault, part of the circuit voltage is
consumed across the fault and the total
fault current is somewhat smaller than
for a bolted fault, so the latter is the
worst condition, and therefore is the
value sought in the fault calculations.
Basically, the short-circuit current is
determined by applying Ohms Law
to an equivalent circuit consisting of
a constant voltage source and a timevarying impedance. A time-varying
impedance is used in order to account
for the changes in the effective voltages
of the rotating machines during the
fault. In an AC system, the resulting
short-circuit current starts out higher in
magnitude than the final steady-state
value and asymmetrical (due
to the DC offset) about the X-axis.
The current then decays toward a
lower symmetrical steady-state value.
The time-varying characteristic of the
impedance accounts for the symmetrical decay in current. The ratio of the
reactive and resistive components (X/R
ratio) accounts for the DC decay, see
Figure 1.3-1. The fault current consists
of an exponentially decreasing directcurrent component superimposed
upon a decaying alternating-current.
The rate of decay of both the DC and
AC components depends upon the
ratio of reactance to resistance (X/R)
of the circuit. The greater this ratio,
the longer the current remains higher
than the steady-state value that it
would eventually reach.
The total fault current is not symmetrical
with respect to the time-axis because
of the direct-current component, hence
it is called asymmetrical current. The
DC component depends on the point
on the voltage wave at which
the fault is initiated.
See Table 1.3-2 for multiplying factors
that relate the rms asymmetrical value
of total current to the rms symmetrical
value, and the peak asymmetrical
value of total current to the rms
symmetrical value.
2.0
Scale of Curent Values
1.5
1.0
0.5
1
0
0.5
1.0
1.5
2.0
CA08104001E
April 2016
1.3-3
Sheet 01 035
1.
Ip = I 2
Ip
----- = 2
I
t
-------------
1 + e X R
2. I rms asym = I 1 + 2e
1 + e X R =
2 260
--------------------------------120
--------------------------------XR
I rms asym
------------------------------ =
1 + 2e
ii
----------1 + e X R
1 + 2e
1
2
2
------------XR
2t
--------------XR
Peak mf = 2
Where:
-------
1 + e 15 =
4
2.5612
Ip = Peak current
rms mf = 1 + 2e
15
1.5217
e = 2.718
=2f
f = Frequency in Hz
t = Time in seconds
9
10
2.6
2.5
2.4
2.3
FA
C
1.7
11
12
13
14
1.6
LT
IP
LI
2.0
1.5
PE
AK
1.9
1.8
ON
OR
CT
FA
1.4
TI
ICA
1.7
1.3
L
TIP
UL
SM
1.6
1.2
RM
1.1
1.5
1.4
1.5
2.5
8 9 10
15
20
25
30
40
50
60 70 80 90 100
CA
TI
2.1
PEAK MULTIPLICATION FACTOR =
1.8
TO
R
2.2
RMS SYMMETRICAL
Based Upon:
2.7
RMS SYMMETRICAL
2.8
15
16
17
18
19
20
21
CA08104001E
1.3-4
April 2016
Sheet 01 036
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
208Y/120 V Systems
or
or
Calculation Methods
The following pages describe various
methods of calculating short-circuit
currents for both medium and low
voltage systems. A summary of
the types of methods and types of
calculations is as follows:
or
or
Medium voltage
switchgearexact
method . . . . . . . . . . . . . . Page 1.3-5
Medium voltage
switchgearquick
check table . . . . . . . . . . . Page 1.3-7
Medium voltage
switchgear
Example 1verify
ratings of breakers . . . . Page 1.3-8
Medium voltage
switchgear
Example 2verify
ratings of breakers
with rotating
loads . . . . . . . . . . . . . . . . Page 1.3-9
Medium voltage
switchgear Example 3
verify ratings of
breakers with
generators . . . . . . . . . . . Page 1.3-10
Medium voltage
fusesexact method . . Page 1.3-11
Power breakers
asymmetry
derating factors . . . . . . . Page 1.3-11
Molded-case
breakersasymmetry
derating factors . . . . . . . Page 1.3-12
Short-circuit
calculations
short cut method
for a system . . . . . . . . . . Page 1.3-13
Short-circuit
calculationsshort
cut method for
end of cable . . . . . . . . . . Page 1.3-15
Short-circuit
calculations
short cut method
for end of cable
chart method . . . . . . . . . Page 1.3-16
Short-circuit currents
chart of transformers
3003750 kVA. . . . . . . . . Page 1.5-9
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-5
Sheet 01 037
The purpose of the fault current calculations is to determine the fault current
at the location of a circuit breaker, fuse
or other fault interrupting device in
order to select a device adequate for the
calculated fault current or to check the
thermal and momentary ratings of noninterrupting devices. When the devices
to be used are ANSI-rated devices, the
fault current must be calculated and the
device selected as per ANSI standards.
ii
1
2
3
4
5
6
7
X
X
X
X
9 (714)
15 (1217)
80 (40120)
80 (40120)
20 (1332)
30 (1060)
0.75X
0.75X
16 (1650)
30 (1060)
1.5X
1.0X
20 (1335)
30 (1060)
1.5X
1.0X
17 (1525)
30 (1540)
3.0X
1.2X
17 (1525)
15 (240)
Neglect
Neglect
As specified
or calculated
15 (515)
As specified
or calculated
80 (40120)
OA to 10 MVA, 69 kV
8.0
8.0 to 10.5
Depends on
primary
windings BIL
rating
11
12
13
14
Transformers
OA to 10 MVA, above 69 kV
10
18 (724)
18 (724)
20 (730)
38 (3244)
15
16
Table 1.3-2. Typical System X/R Ratio Range (for Estimating Purposes)
17
Type of Circuit
X/R Range
Remote generation through other types of circuits such as transformers rated 10 MVA
or smaller for each three-phase bank, transmission lines, distribution feeders, etc.
15 or less
1540
3050
19
3050
20
Synchronous machines connected through transformers rated 100 MVA and larger
4060
40120
18
21
1.3-6
April 2016
Sheet 01 038
i
ii
1
2
3
4
5
6
7
8
9
10
130
130
130
120
120
120
110
110
19
20
21
80
80
40
3
TIME
PA
RT
ING
60
70
60
50
50
40
40
NT
AC
T
NT
AC
50
70
CO
60
Ratio X/R
T P
ART
ING
70
Ratio X/R
TIME
80
90
12
90
10
90
30
30
18
100
CO
17
Ratio X/R
14
16
100
100
13
15
110
12
11
5-CYCLE
BREAKER
30
5-CYCLE
BREAKER
20
20
20
10
10
10
1.0
1.1
1.2
1.3
1.4
5-CYCLE
BREAKER
1.0
1.1
1.2
1.3
1.4
April 2016
1.3-7
Sheet 01 039
Reclosing Duty
ANSI Standard C37.010 indicates the
reduction factors to use when circuit
breakers are used as reclosers. Eaton
VCP-W breakers are listed at 100%
rating factor for reclosing.
b.
V max
Operating Voltage
kV
Motor Load
2.4
100%
Altitude in
Feet (Meters)
Correction Factor
Current
Voltage
1.00
0.99
0.96
1.00
0.95
0.80
4.16
1.5
2
2.5
2.5
3
3
3.75
3.75
5
5
7.5
7.5
10 1
10
10
10
12 1
12
15
15
20
20 1
20
25
30
3
4
5
6
7
8
12
13.8
11
50 VCP-W 250
12 kA
50 VCP-W 250
36 kA
50 VCP-W 350
49 kA
50 VCP-W 250
10.1 kA
12
13
50 VCP-W 250
33.2 kA
14
50 VCP-W 350
46.9 kA
75 VCP-W 500
41.3 kA
50 1
1
10
6.6
0%
1
1.5
2
ii
15
150 VCP-W 750
35 kA
16
17
Transformer impedance 6.5% or more, all other transformer impedances are 5.5% or more.
18
19
20
21
CA08104001E
1.3-8
April 2016
Sheet 01 040
i
ii
1
2
E
I 3-Phase ----X
Given a circuit breaker interrupting and momentary rating in the table below,
verify the adequacy of the ratings for a system without motor loads, as shown.
Table 1.3-5. Short-Circuit Duty
Type
Breaker
V Max.
50VCPW250
4.76 kV
Max. KI
4.76
----------- (29) = 33.2 kA I1
4.16
LG symmetrical interrupting capability
29 kA
36 kA
36 kA
4
5
Check capabilities I1, I2 and I3 on the following utility system where there is no
motor contribution to short circuit.
7
8
2
2
2
2X
Z = X + R = R -------+ 1
2
R
375 MVA
Available
9
10
X = X
----- R = 15 (0.066) = .99%
R
11
13
1
1
------------------ 0.066%
15.03
266
----------------
13.8 kV
3750 kVA
12
----------------------2
X
-------- + 1
2
50VPC-W250
IB
I 3-Phase -----X
where X is per unit reactance
IB is base current
Note: Interrupting capabilities I1 and I2 at operating voltage must not exceed maximum
symmetrical interrupting capability Kl.
MVA
Base current I B = 3.75
= 0.52kA
3 4.16 kV
I1
0.52
I 3-Phase ----- ---------------------- 8.6 kA Sym.
0.0604
X
System X
9 (is less than 15)
R
would use 1.0 multiplying factor for
short-circuit duty, therefore, shortcircuit duty is 8.6 kA sym. for threephase fault I1 and momentary duty is
8.6 x 1.6 = 13.7 kA I3.
14
Answer
15
16
17
18
19
20
21
Z R
24.2 kW
R -------------------------------- 0.0065 pu or 0.65%
3750 kVA
2
(5.09) (0.65) =
25.91 0.42 =
25.48
X = 5.05%
X
13.8 kV System 0.99%
Transformer
5.05%
System Total 6.04%
or
0.0604 pu
R
X/R
0.066% 15
0.65%
8
0.716% 9
0.00716 pu
CA08104001E
April 2016
1.3-9
Sheet 01 041
7500 kVA
X/R
0.001
15
Transformer
0.0055
10
X = 15
R
21 kA Sym. Available
13.8 kV
13.8 kV System
Z = 5.53%
X = 5.5%
R = 0.55%
ii
X
= 10
R
6.9 kV
13.8 kV System
0.055
X
= 25
R
197A FL
X''d = 20%
X
= 35
R
173A FL
X''d = 25%
3000 hp
1.0 PF
Syn.
4
5
6
2500 hp
Ind.
7
Figure 1.3-7. Example 2One-Line Diagram
Source of
Short-Circuit Current
Interrupting
E/X Amperes
Momentary
E/X Amperes
X
R
X (1)
R (X)
1
R
I3 Source Transformer
0.628
0.070
= 8.971
0.628
= 8.971
0.070
11
11
0.070
= 157
0.628
= 0.656
(1.5) 0.638
0.628
= 0.984
0.638
25
25
0.638
= 39
0.628
= 0.461
(1.5) 0.908
0.628
= 0.691
0.908
35
35
0.908
= 39
I3F =
Type of Fault
Ratio
ThreePhase
LG
Three-Phase
and LG
Remote
X
System ----- = 0.062 (235) = 14.5 is a Multiplying Factor of 1.0 from Table 1.3-6
R
1.00
1.00
1.00
1.00
1.04
1.00
1.00
1.02
1.06
1.10
1.00
1.00
1.05
1.10
1.13
36
40
45
50
55
1.06
1.08
1.12
1.13
1.14
1.14
1.16
1.19
1.22
1.25
1.17
1.22
1.25
1.27
1.30
Breaker
Type
60
65
70
75
80
1.16
1.17
1.19
1.20
1.21
1.26
1.28
1.29
1.30
1.31
1.32
1.33
1.35
1.36
1.37
150VCP-W500
85
90
95
100
1.22
1.23
1.32
1.33
1.38
1.39
1.40
1.41
100
120
130
1.24
1.24
1.24
1.34
1.35
1.35
1.42
1.43
1.43
75VCP-W500
8.25 kV 33 kA
15 kV
18 kA
10
11
13
14
12
I B = 0.628 = 0.062
Total X = ------------------------10.1
I 3F
1
15 1
20
25
30
10.647
Total 1/R = 235
x 1.6
17.0 kA Momentary Duty
10.088
10.1 kA
or
Max. KI
41 kA
23 kA
Answer
Either breaker could be properly
applied, but price will make the type
150VCP-W500 the more economical
selection.
(33) = 39.5 kA
66 kA
15 (18) (39.1) = 23 kA
6.9
(But not to exceed KI)
37 kA
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 042
i
ii
Answer
Check breaker application or generator bus for the system of generators shown.
Each generator is 7.5 MVA, 4.16 kV 1040 A full load, IB = 1.04 kA
Sub transient reactance Xd = 11% or, X = 0.11 pu
Gen X
----- ratio is 30
R
1
1 1 1 3
1 1 1 3
1
and
RS R R R R
X X X X
XS
3
4
5
6
7
XXS
R
or XS X
Gen X
----- and R S ---- Therefore, System --------- -------- 30
R
R
3
3
RS
G1
G2
G3
Since generator neutral grounding reactors are used to limit the ILG to I3-phase or
below, we need only check the I3 short-circuit duty.
I B I B I B 31B 3(1.04)
IB Phase ----- + ------ + ------ + ------------ ----------------------- 28.4 kA Symmetrical E/X amperes
0.11
X X X X
4.16 kV
X
System ----- of 30 is a Multiplying Factor of 1.04 from Table 1.3-6.
R
Short-circuit duty is 28.4 (1.04) = 29.5 kA Symmetrical
8
9
V Max.
at V Max.
Max. KI
50VCP-W250
4.76 kV
29 kA
36 kA
4.76
(29) = 33.2 kA
4.16
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-11
Sheet 01 043
CA08104001E
ii
1
2
3
4
5
6
7
8
9
10
11
12
X/R
2 1 2.718
MF
2.29
13
14
15
2 X/R
1 2 2.718
MF
1.25
16
17
18
19
20
21
April 2016
Sheet 01 044
i
ii
1
2
3
4
5
6
7
8
R 2
1 + 2.718
MF ----------------------------------------------------X
1
R 1
1 + 2.718
X1 R1 = test X/R value
X2 R2 = X/R at point where breaker
is applied
11
12
13
Power Factor
Test Range
X/R Test
Range
0.450.50
0.250.030
0.150.20
1.981.73
3.873.18
6.64.9
X/R
Interrupting Rating
Molded Case or Insulated Case
9
10
m/ = 10 kA
>10 kA
m/ = 20 kA
L20 kA
Unfused
Fused
50
30
25
1.73
3.18
3.87
1.000
0.847
0.805
1.000
1.000
0.950
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
20
15
12
4.90
6.59
8.27
0.762
0.718
0.691
0.899
0.847
0.815
1.000
0.942
0.907
1.000
1.000
0.962
1.000
0.939
0.898
10
8.5
7
9.95
11.72
14.25
0.673
0.659
0.645
0.794
0.778
0.761
0.883
0.865
0.847
0.937
0.918
0.899
0.870
0.849
0.827
19.97
0.627
0.740
0.823
0.874
0.797
Note: These are derating factors applied to the breaker and are the inverse of MF.
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-13
Sheet 01 045
2.
kVA base 2
kVA base 1
kVA base 2
kVA base 1
(% impedance)
(10)
kVA base
6
7
8
9
(a) motor kVA 3 (kV) (I) where I = motor nameplate full-load amperes
10
11
Single-phase kVA
kV line-to-neutral
or
3 kV
12
pu Z
(c) rms Symmetrical current = ISC = (pu ISC) (IBase Amperes)
13
7.
8.
6.
kV 2
(b) if utility fault capacity given in rms symmetrical short circuit amperes
5.
100
(ohms impedance) (kVA base)
(b) % impedance = % Z =
10
kV 2
4.
1
2
1.
3.
ii
(e)
(g)
(kV) (1000)
= ----------------------------------3 (ohms Z)
14
15
16
17
18
9.
(a) synchronous motor5 times motor full load current (impedance 20%)
(b) induction motor4 times motor full-load current (impedance 25%)
See IEEE
Standard No. 141
(c) motor loads not individually identified, use contribution from group of motors as follows:
on 208Y/120 V systems2.0 times transformer full-load current
on 240-480-600 V three-phase, three-wire systems4.0 times transformer full-load current
on 480Y/277 V three-phase, four-wire systems
In commercial buildings, 2.0 times transformers full-load current (50% motor load)
In industrial plants, 4.0 times transformer full-load current (100% motor load)
CA08104001E
19
20
21
April 2016
Sheet 01 046
Example Number 1
How to Calculate Short-Circuit Currents at Ends of Conductors
ii
A. System Diagram
Utility Source
500 MVA
Major Contribution
Utility
2
Cables
Transformer
Switchboard Fault
1000 kV A
5.75%
480V
Cables
4
5
6
7
Fault
Cable
Switchboard Fault
100 ft (30m)
3350 kcmil Cable
in Steel Conduit
0.002 pu
1.00 pu
1.00 pu
1.00 pu
0.0575 pu
0.027 pu
Switchboard Fault
0.027 pu
0.027 pu
0.027 pu
Cable Fault
Cable Fault
Combining Series Impedances: ZTOTAL = Z1 + Z2 + ... +Zn
9
10
11
12
13
1 =
ZTOTAL
0.0595 pu
1 + 1 + ... 1
Z1
Z2
Zn
0.342 pu
E
0.027 pu
Equation
(See)
4(a)
3(a)
16
4(a) and
9(c)
17
3(a)
14
15
6(d)
19
20
21
0.0777 pu
0.027 pu
Calculation
Select 1000 kVA as most convenient base, since all data except utility source is on
secondary of 1000 kVA transformer.
18
6
0.0507 pu
pu
pu
%Z- = 5.75
= ------------------- = 0.0575 pu
100
100
base)
(0.00619)(1000)- = 0.027 pu
= (ohms)(kVA
-------------------------------------------------- = -----------------------------------------2
2
(kV) (1000)
(0.480) (1000)
6(d)
CA08104001E
April 2016
1.3-15
Sheet 01 047
Example Number 2
Z
{ RX == 0.1498
0.9887 Z
R
Z=
100 Ft. Two #2/0 Copper Conductors, Magnetic Conduit R = 0.0104 Ohms
X = 0.0051 Ohms
R=
75 kVA Single-Phase 480-120/240V; Z = 2.8%, R = 1.64%, X = 2.27%
6.6
X = 6.6 R
120V
F2
Half-winding of Transformer
1
2
6.6R + R = 43.56R + R =
X +R =
44.56R = 6.6753R
Z
6.6753
R = 0.1498Z
X = 6.6R
240V
F1
ii
X = 0.9887Z
% R by 1.5
{ Multiply
Multiply % X by 1.2 } Reference: IEEE Standard No. 141
Full-winding of Transformer
B. Impedance DiagramFault F1
RSyst = 0.00054
RSyst = 0.00356
RSyst = 0.00054
XSyst = 0.00356
RCond = 0.00677
RCond = 0.00332
RCond = 0.00677
XCond = 0.00332
RTfmr = 0.0164
RTfmr = 0.0227
RTfmr = 0.0246
XTfmr = 0.0272
RTotal = 0.02371
F1
RTotal = 0.02958
F1
C. Impedance DiagramFault F2
RTotal = 0.03191
F2
6
7
XTotal = 0.03408
F2
75
0.0018 pu
3 0.480 50,000
kVA Base
ZCond =
2
kV 1000
ohms
RSyst = 2 (0.1498 x Z)
= 0.00054 pu
XSyst = 2 (0.9887 x Z)
0.0104 75
RCond = 2
0.48 2 1000
0.0051 75
XCond = 2
0.48 2 1000
1.64
RTfmr =
100
= 0.00356 pu
XTfmr =
= 0.00677 pu
11
= 0.00332 pu
= 0.0164 pu
2.27
100
= 0.0277 pu
1.64
RTfmr = 1.5
100
XTfmr = 1.2
Impedance to Fault F1Full Winding
Impedance to Fault F2Half Winding
Short circuit current F1 = 75 (0.03791 x 0.240 kV) = 8,243 A Symmetrical
Short circuit current F2 = 75 (0.04669 x 0.120 kV) = 13,386 A Symmetrical
= 0.0272 pu
= 0.03791 pu
= 0.04669 pu
Z=
0.02371 + 0.02958
Z=
0.03191 + 0.03408
CA08104001E
15
16
13
14
2.27
100
Conductor ohms for 500 kcmil conductor from reference data in this section
in magnetic conduit is 0.00551 ohms
per 100 ft (30 m). For 100 ft (30 m) and
two conductors per phase we have:
12
= 0.0246 pu
10
17
18
30,000 A available
19
100 ft (30 m)
2500 kcmil per phase
20
If = 23,160 A
21
April 2016
Sheet 01 048
ii
1
2
3
4
5
6
Step Five
Enter the chart along the bottom horizontal scale with the
distance (in feet) from the transformer to the fault point.
Draw a vertical line up the chart to the point where it intersects the selected curve. Then draw a horizontal line to the
left from this point to the scale along the left side of the chart.
Motor Contribution
For system voltages of 120/208 V, it is reasonable to assume
that the connected load consists of 50% motor load, and that
the motors will contribute four times their full load current
into a fault. For system voltages of 240 and 480 V, it is reasonable to assume that the connected load consists of 100%
motor load, and that the motors will contribute four times
their full load current into a fault. These motor contributions
have been factored into each curve as if all motors were
connected to the transformer terminals.
Feeder Conductors
The conductor sizes most commonly used for feeders
from molded case circuit breakers are shown. For conductor
sizes not shown, the following table has been included for
conversion to equivalent arrangements. In some cases it
may be necessary to interpolate for unusual feeder ratings.
Table 1.3-10 is based on using copper conductor.
Table 1.3-10. Conductor Conversion (Based on Using Copper Conductor)
If Your Conductor is:
2500 kcmil
2500 kcmil
4750 kcmil
4750 kcmil
4750 kcmil
800 A busway
1000 A busway
1600 A busway
2500 kcmil
2500 kcmil
4750 kcmil
10
11
12
Step Six
The value obtained from the left-hand vertical scale is the fault
current (in thousands of amperes) available at the fault point.
For a more exact determination, see the formula method.
It should be noted that even the most exact methods for
calculating fault energy use some approximations and some
assumptions. Therefore, it is appropriate to select a method
which is sufficiently accurate for the purpose, but not more
burdensome than is justified. The charts that follow make
use of simplifications that are reasonable under most circumstances and will almost certainly yield answers that are
on the safe side. This may, in some cases, lead to application
of circuit breakers having interrupting ratings higher than
necessary, but should eliminate the possibility of applying
units which will not be safe for the possible fault duty.
14
15
17
18
19
20
21
F
12.5
10.0
1.
2.
3.
4.
System voltage
Transformer kVA rating (from transformer nameplate)
Transformer impedance (from transformer nameplate)
Primary source fault energy available in kVA
(from electric utility or distribution system engineers)
Step Three
Select the family of curves that is closest to the available
source kVA. The black line family of curves is for a source of
500,000 kVA. The lower value line (in red) family of curves is
for a source of 50,000 kVA. You may interpolate between
curves if necessary, but for values above 100,000 kVA it is
appropriate to use the 500,000 kVA curves.
Step Four
Select the specific curve for the conductor size being used. If
your conductor size is something other than the sizes shown
on the chart, refer to the conductor conversion Table 1.3-10.
UTILITY KVA
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
7.5
5.0
2.5
Step Two
16
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
UTILITY KV
Fault Current in Thousands of Amperes (Sym.)
13
15.0
30
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
25
20
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
B
F
15
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
CA08104001E
April 2016
1.3-17
Sheet 01 049
30
F
25
i
UTILITY KV
A
B
C
D
E
F
UTILITY KVA
Fault Current in Thousands of Amperes (Sym.)
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
INFINITE
500,000
250,0 0 0
150,0 0 0
10 0,0 0 0
50,000
20
15
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
120
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
100
80
60
40
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
ii
1
2
3
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
20
4
0
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
6
Fault Current in Thousands of Amperes (Sym.)
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
50
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
40
F
30
20
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
UTILITY KVA
UTILITY KVA
60
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
B
100
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
80
F
60
10
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
40
20
5000
120
11
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
12
13
60
B
50
UTILITY KVA
UTILITY KVA
Fault Current in Thousands of Amperes (Sym.)
14
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
40
30
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
20
10
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
12
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
10
B
15
16
F
8
18
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
17
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
19
5000
20
21
CA08104001E
April 2016
Sheet 01 050
1
2
3
UTILITY KVA
Fault Current in Thousands of Amperes (Sym.)
ii
UTILITY KVA
30
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
25
20
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
15
F
10
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
4
0
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
50
40
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
30
20
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
5000
60
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
9
10
11
12
13
30
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
25
20
UTILITY KVA
Fault Current in Thousands of Amperes (Sym.)
UTILITY KVA
Fault Current in Thousands of Amperes (Sym.)
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
B
F
15
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
60
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
50
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
40
F
30
20
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
15
16
17
18
14
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
30
B
25
UTILITY KVA
A INFINITE
B 500,000
C 250,000
D 150,000
E 100,000
F
50,000
20
15
4 750 kcmil
2 500 kcmil
250 kcmil
#1/0 AWG
#4 AWG
10
19
0
20
5
10
20
50
100
200
500 1000 2000
Distance in Feet from T ransformer to Breaker Location
5000
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-19
Sheet 01 051
500
3 R = 7300 W
3 0.480
%R = 0.0067 ohms
0.0067 500
%R = = 1.46%
2
10 0.48
%X =
Method 2:
Using same values above.
7300
= 1.46
10 500
2
i
ii
1
2
3
4
5
6
7
8
9
I R Losses
%R =
10 kVA
%X =
Method 2:
10
2
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 052
i
ii
1
2
3
4
5
6
7
8
9
10
Recommended Limits of
Voltage Variation
11
12
13
14
15
16
17
18
19
20
Motor Starting
Motor inrush on starting must be limited
to minimize voltage dips. Table 1.3-11
on the next page will help select the
proper type of motor starter for various
motors, and to select generators of
adequate size to limit voltage dip.
See Tab 29 for additional data on
reduced voltage motor starting.
Utility Systems
Where the power is supplied by a
utility network, the motor inrush can
be assumed to be small compared
to the system capacity, and voltage
at the source can be assumed to
be constant during motor starting.
Voltage dip resulting from motor
starting can be calculated on the basis
of the voltage drop in the conductors
between the power source and
the motor resulting from the inrush
current. Where the utility system is
limited, the utility will often specify the
maximum permissible inrush current
or the maximum hp motor they will
permit to be started across-the-line.
Transformer Considerations
If the power source is a transformer,
and the inrush kVA or current of the
motor being started is small compared
to the full-rated kVA or current of the
transformer, the transformer voltage
dip will be small and may be ignored.
As the motor inrush becomes a significant percentage of the transformer
full-load rating, an estimate of the
transformer voltage drop must be
added to the conductor voltage drop
to obtain the total voltage drop to the
motor. Accurate voltage drop calculation would be complex and depend
upon transformer and conductor
resistance, reactance and impedance,
as well as motor inrush current and
power factor. However, an approximation can be made on the basis of the
low power-factor motor inrush current
(3040%) and impedance of the
transformer.
For example, if a 480 V transformer
has an impedance of 5%, and the
motor inrush current is 25% of the
transformer full-load current (FLC),
then the worst case voltage drop will
be 0.25 x 5%, or 1.25%.
The allowable motor inrush current is
determined by the total permissible
voltage drop in transformer and
conductors.
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-21
Sheet 01 053
Starting Starting
How
Torque Current 2 Started
Starting
Starting Torque per Unit of
Current
Full Load Torque
% Full-Load 3 Motor Rpm
1750
1150 3
850
Full-Load Amperes
per kVA Generator
Capacity for Each
1% Voltage Drop
i
ii
Design A
Normal
Normal
Across-the-line
resistance
autotransformer
600700
480560
375450
1.5
0.96
0.96
1.35
0.87
0.87
1.25
0.80
0.80
0.0109.00936
0.0136.0117
0.0170.0146
Design B
Normal
Low
Across-the-line
resistance
autotransformer
500600
400480
320400
1.5
0.96
0.96
1.35
0.87
0.87
1.25
0.80
0.80
0.0131.0109
0.0164.01365
0.0205.0170
Design C
High
Low
Across-the-line
resistance
autotransformer
500600
400480
320400
0.2 to 2.5
1.28 to 1.6
1.28 to 1.6
0.0131.0109
0.0164.01365
0.0205.0170
Low
Secondary controller
100% current
for 100%
torque
0.0655
Across-the-line
Across-the-line
Autotransformer
300
450550
288350 4
0.0218
0.0145.0118
0.0228.0197
Wound Rotor
High
Consult NEMA MG-1 sections 1 and 12 for the exact definition of the design letter.
In each case, a solid-state reduced voltage starter can be adjusted and controlled to provide the required inrush current and torque characteristics.
Where accuracy is important, request the code letter of the the motor and starting and breakdown torques from the motor vendor.
Using 80% taps.
CA08104001E
Shortcut Method
Column 7 in Table 1.3-11 has been
worked out to simplify checking.
The figures were obtained by using the
formula above and assuming
1 kVA generator capacity and 1%
voltage drop.
For more information, visit: www.eaton.com/consultants
Example:
Assuming a project having a
1000 kVA generator, where the
voltage variation must not exceed
10%. Can a 75 hp, 1750 rpm, 220 V,
three-phase, squirrel-cage motor be
started without objectionable lamp
flicker (or 10% voltage drop)?
From tables in the circuit protective
devices reference section, the full-load
amperes of this size and type of motor
is 158 A. To convert to same basis as
column 7, 158 A must be divided by
the generator capacity and % voltage
drop, or:
158
= 0.0158 A per kVA
1000 x 10 per 1% voltage drop
Checking against the table, 0.0158 falls
within the 0.01700.0146 range. This
indicates that a general-purpose motor
with autotransformer starting can
be used.
Note: Designers may obtain calculated
information from engine generator
manufacturers.
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
April 2016
Sheet 01 054
Approximate Method
ii
E VD = IR cos + IX sin
Exact Methods
2
3
Voltage drop
2
2 ZMVA R
E S = E R + --------------------------------- + 2ZMVA R cos R
2
ER
or
2
2
2 ZMVA R
- 2ZMVA S cos S
E R = E S + --------------------------------2
ES
where:
5
6
7
8
9
10
E VD = E R cos + I R + E R sin + IX E R
Voltage Drop
where:
ER
ES
= Receiving end PF
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.3-23
Sheet 01 055
Voltage Drop
Conductor
Size
No. 14 to No. 4
No. 2 to 3/0
4/0 to 500 kcmil
600 to 1000 kcmil
Percent Correction
Power Factors %
100
90
80
70
60
5.0
5.0
5.0
5.0
4.7
4.2
3.1
2.6
4.7
3.7
2.6
2.1
4.6
3.5
2.3
1.5
4.6
3.2
1.9
1.3
Calculations
To calculate voltage drop:
1. Multiply current in amperes by
the length of the circuit in feet to
get ampere-feet. Circuit length is
the distance from the point of
origin to the load end of the circuit.
2. Divide by 100.
3. Multiply by proper voltage drop
value in tables. Result is voltage
drop.
Example:
A 460 V, 100 hp motor, running at 80%
PF, draws 124 A full-load current. It is
fed by three 2/0 copper conductors in
steel conduit. The feeder length is
150 ft (46 m). What is the voltage drop
in the feeder? What is the percentage
voltage drop?
x 1.155
x 0.577
ii
3. Multiply by 100.
3
4
5
Example:
A three-phase, four-wire lighting
feeder on a 208 V circuit is 250 ft
(76.2 m) long. The load is 175 A at
90% PF. It is desired to use aluminum
conductors in aluminum conduit. What
size conductor is required to limit the
voltage drop to 2% phase-to-phase?
2
1. VD = 208 = 4.16 V
100
2.
4.16
= 0.0000951
175 250
3.
x 0.577
x 1.155
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 056
i
ii
Table 1.3-13. Voltage DropVolts per Ampere per 100 Feet (30 m); Three-Phase, Phase-to-Phase
Conductor Size
AWG
or kcmil
60
70
80
90
100
60
70
80
90
100
14
12
10
8
0.3390
0.2170
0.1390
0.0905
0.3910
0.2490
0.1590
0.1030
0.4430
0.2810
0.1790
0.1150
0.4940
0.3130
0.1980
0.1260
0.5410
0.3410
0.2150
0.1350
0.3370
0.2150
0.1370
0.0888
0.3900
0.2480
0.1580
0.1010
0.4410
0.2800
0.1780
0.1140
0.4930
0.3120
0.1970
0.1250
0.5410
0.3410
0.2150
0.1350
6
4
2
1
0.0595
0.0399
0.0275
0.0233
0.0670
0.0443
0.0300
0.0251
0.0742
0.0485
0.0323
0.0267
0.0809
0.0522
0.0342
0.0279
0.0850
0.0534
0.0336
0.0267
0.0579
0.0384
0.0260
0.0218
0.0656
0.0430
0.0287
0.0238
0.0730
0.0473
0.0312
0.0256
0.0800
0.0513
0.0333
0.0270
0.0849
0.0533
0.0335
0.0266
1/0
2/0
3/0
4/0
0.0198
0.0171
0.0148
0.0130
0.0211
0.0180
0.0154
0.0134
0.0222
0.0187
0.0158
0.0136
0.0229
0.0190
0.0158
0.0133
0.0213
0.0170
0.0136
0.0109
0.0183
0.0156
0.0134
0.0116
0.0198
0.0167
0.0141
0.0121
0.0211
0.0176
0.0147
0.0124
0.0220
0.0181
0.0149
0.0124
0.0211
0.0169
0.0134
0.0107
250
300
350
500
0.0122
0.0111
0.0104
0.0100
0.0124
0.0112
0.0104
0.0091
0.0124
0.0111
0.0102
0.0087
0.0120
0.0106
0.0096
0.0080
0.0094
0.0080
0.0069
0.0053
0.0107
0.0097
0.0090
0.0078
0.0111
0.0099
0.0091
0.0077
0.0112
0.0099
0.0091
0.0075
0.0110
0.0096
0.0087
0.0070
0.0091
0.0077
0.0066
0.0049
600
750
1000
0.0088
0.0084
0.0080
0.0086
0.0081
0.0077
0.0082
0.0077
0.0072
0.0074
0.0069
0.0063
0.0046
0.0040
0.0035
0.0074
0.0069
0.0064
0.0072
0.0067
0.0062
0.0070
0.0064
0.0058
0.0064
0.0058
0.0052
0.0042
0.0035
0.0029
12
10
8
0.3296
0.2133
0.1305
0.3811
0.2429
0.1552
0.4349
0.2741
0.1758
0.4848
0.3180
0.1951
0.5330
0.3363
0.2106
0.3312
0.2090
0.1286
0.3802
0.2410
0.1534
0.4328
0.2740
0.1745
0.4848
0.3052
0.1933
0.5331
0.3363
0.2115
6
4
2
1
0.0898
0.0595
0.0403
0.0332
0.1018
0.0660
0.0443
0.0357
0.1142
0.0747
0.0483
0.0396
0.1254
0.0809
0.0523
0.0423
0.1349
0.0862
0.0535
0.0428
0.0887
0.0583
0.0389
0.0318
0.1011
0.0654
0.0435
0.0349
0.1127
0.0719
0.0473
0.0391
0.1249
0.0800
0.0514
0.0411
0.1361
0.0849
0.0544
0.0428
1/0
2/0
3/0
4/0
0.0286
0.0234
0.0209
0.0172
0.0305
0.0246
0.0220
0.0174
0.0334
0.0275
0.0231
0.0179
0.0350
0.0284
0.0241
0.0177
0.0341
0.0274
0.0217
0.0170
0.0263
0.0227
0.0160
0.0152
0.0287
0.0244
0.0171
0.0159
0.0322
0.0264
0.0218
0.0171
0.0337
0.0274
0.0233
0.0179
0.0339
0.0273
0.0222
0.0172
11
250
300
350
500
0.0158
0.0137
0.0130
0.0112
0.0163
0.0139
0.0133
0.0111
0.0162
0.0143
0.0128
0.0114
0.0159
0.0144
0.0131
0.0099
0.0145
0.0122
0.0100
0.0076
0.0138
0.0126
0.0122
0.0093
0.0144
0.0128
0.0123
0.0094
0.0147
0.0133
0.0119
0.0094
0.0155
0.0132
0.0120
0.0091
0.0138
0.0125
0.0101
0.0072
12
600
750
1000
0.0101
0.0095
0.0085
0.0106
0.0094
0.0082
0.0097
0.0090
0.0078
0.0090
0.0084
0.0071
0.0063
0.0056
0.0043
0.0084
0.0081
0.0069
0.0085
0.0080
0.0068
0.0085
0.0078
0.0065
0.0081
0.0072
0.0058
0.0060
0.0051
0.0038
1
2
3
4
5
6
Copper Conductors
Aluminum Conductors
7
8
9
10
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-1
Sheet 01 057
Capacitors
Capacitor selection
Where to install capacitors in a plant
distribution system
Locating capacitors on reduced
voltage and multi-speed starters
Harmonic considerations
Eliminating harmonic problems
National Electrical Code
requirements
Medium Voltage
Capacitor Switching
Capacitance switching constitutes
severe operating duty for a circuit
breaker. At the time the breaker opens
at near current zero, the capacitor is
fully charged. After interruption, when
the alternating voltage on the source
side of the breaker reaches its opposite
maximum, the voltage that appears
across the contacts of the open breaker
is at least twice the normal peak lineto-neutral voltage of the circuit. If a
breakdown occurs across the open
contact, the arc is re-established. Due
to the circuit constants on the supply
side of the breaker, the voltage across
the open contact can reach three times
the normal line-to-neutral voltage.
After it is interrupted and with
subsequent alternation of the supply
side voltage, the voltage across the
open contact is even higher.
i
ii
1
Contactors:
Open type . . . . . . . . . . . . . . . . . . . 135%
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.4-2
April 2016
Sheet 01 058
Capacitors
i
ii
1
2
3
4
5
6
7
8
Definitions
9
10
11
12
Applied Voltage
Nameplate kvar ---------------------------------------------------------------------2
Nameplate Voltage
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-3
Sheet 01 059
1000
900
800
700
600
ii
1
2
3
4
5
6
4.16 kV
6000
7000
8000
9000
10,000
40 50 60
5000
30
4000
20
3000
6 7 8 9 10
2000
600
700
800
900
1000
500
400
300
.5 .6 .7 .8 .9 1
70
80
90
100
Overcurrent Protection
and Coordination
250 MVA
1000
900
800
700
600
500
500
400
400
300
300
200
200
CA08104001E
250A
1000
kVA
5.75%
50
40
ANSI Three-Phase
Thru Fault
Protection Curve
(More Than 10 in
Lifetime)
30
TIME IN SECONDS
20
4,160V
480/277V
100
90
80
70
60
30
1,600A
20
10
9
8
7
6
600A
M
20,000A
175A
A
B
1
.9
.8
.7
.6
1
.9
.8
.7
.6
100 hp
124A FLC
13
14
15
.5
.5
.4
.3
.4
.3
Ground
Fault Trip
.2
Transformer
Inrush
30
40 50 60
.02
Figure 1.4-1. Time-Current Characteristic Curves for Typical Power Distribution System
Protective Devices Coordination Analysis
For more information, visit: www.eaton.com/consultants
18
.03
19
.01
6000
7000
8000
9000
10,000
20
2000
6 7 8 9 10
600
700
800
900
1000
500
400
200
300
Max.
480V Fault
5000
.03
.04
4000
.04
.02
.05
Max. Three-Phase
4.16 kV Fault
.05
17
.1
.09
.08
.07
.06
3000
.1
.09
.08
.07
.06
.5 .6 .7 .8 .9 1
16
.2
.01
12
24,400A
10
11
50
40
19,600A
10
9
8
7
6
70
80
90
100
D
100
90
80
70
60
TIME IN SECONDS
20
21
1.4-4
April 2016
Sheet 01 060
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
4160
I 480V I 4160V
480
CA08104001E
April 2016
1.4-5
Sheet 01 061
i
ii
1
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.4-6
April 2016
Sheet 01 062
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-7
Sheet 01 063
Grounding
1. Equipment Grounding
Equipment grounding is essential
to safety of personnel. Its function is
to ensure that all exposed noncurrentcarrying metallic parts of all structures
and equipment in or near the electrical
distribution system are at the same
potential, and that this is the zero
reference potential of the earth.
Equipment grounding is required
by both the National Electrical Code
(Article 250) and the National Electrical
Safety Code regardless of how the
power system is grounded. Equipment
grounding also provides a return path
for ground fault currents, permitting
protective devices to operate. Accidental contact of an energized conductor of
the system with an improperly
grounded noncurrent-carry metallic
part of the system (such as a motor
frame or panelboard enclosure) would
raise the potential of the metal object
2. System Grounding
System grounding connects the
electrical supply, from the utility, from
transformer secondary windings, or
from a generator, to ground. A system
can be solidly grounded (no intentional
impedance to ground), impedance
grounded (through a resistance or
reactance), or ungrounded (with no
intentional connection to ground.
A
Ungrounded
B
Solidly Grounded
C
Reactance Grounded
D
Resistance Grounded
E
Resonant Grounded
(1) Apparatus
insulation
(2) Fault to
ground current
Fully insulated
Lowest
Partially graded
Partially graded
Partially graded
Usually low
Cannot satisfactorily be
reduced below one-half
or one-third of values for
solid grounding
Low
(4) Relaying
Difficult
Satisfactory
Satisfactory
Satisfactory
(5) Arcing
grounds
(6) Localizing
faults
Likely
Unlikely
Unlikely
Possible if reactance is
excessive
Effect of faults localized to
system or part of system
where they occur unless
reactance is quite high
Effect of faults
transmitted as excess
voltage on sound phases
to all parts of conductively
connected network
Unlikely unless
resistance is quite high
and insulation weak
Effect of faults
transmitted as excess
voltage on sound phases
to all parts of conductively
connected network
Seem to be more likely
but conclusive information
not available
(7) Double
faults
CA08104001E
Usually unimportant
Likely
Unlikely unless
reactance is quite high
and insulation weak
ii
1
2
3
4
5
6
7
8
9
10
11
12
Table 1.4-1. Features of Ungrounded and Grounded Systems (from ANSI C62.92)
(3) Stability
13
14
15
16
17
18
19
20
21
1.4-8
April 2016
Sheet 01 064
i
ii
A
Ungrounded
(8) Lightning
protection
C
Reactance Grounded
D
Resistance Grounded
E
Resonant Grounded
Ungrounded neutral
Highest efficiency and
service arresters must be lowest cost
applied at sacrifice in cost
and efficiency
Ungrounded neutral
service arresters must
be applied at sacrifice
in cost and efficiency
(9) Telephone
interference
(10) Radio
interference
(11) Line
availability
Cannot be interconnected
unless interconnected
system is resonant
grounded or isolating
transformers are used.
Requires coordination
between interconnected
systems in neutralizer
settings
1
2
3
4
5
6
7
B
Solidly Grounded
Will be greatest in
magnitude due to higher
fault currents but can
be quickly cleared
particularly with high
speed breakers
8
9
(13) Circuit
breakers
Interrupting capacity
determined by threephase conditions
Same interrupting
capacity as required for
three-phase short circuit
will practically always be
satisfactory
Interrupting capacity
determined by threephase fault conditions
Interrupting capacity
determined by threephase fault conditions
Interrupting capacity
determined by threephase fault conditions
(14) Operating
procedure
Simple
Simple
Simple
Intermediate
Intermediate
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
1.4-9
Sheet 01 065
Reactance Grounding
It is generally used in the grounding
of the neutrals of generators directly
connected to the distribution system
bus, in order to limit the line-to-ground
fault to somewhat less than the threephase fault at the generator terminals.
If the reactor is so sized, in all probability
the system will remain effectively
grounded.
Resistance Grounded
Medium voltage systems in general
should be low resistance grounded.
The ground fault is typically limited to
about 200400 A but less than 1000 A
(a cable shield consideration). With a
properly sized resistor and relaying
application, selective fault isolation
is feasible. The fault limit provided
has a bearing on whether residually
connected relays are used or ground
sensor current transformers are used
for ground fault relaying.
2
3
4
5
6
7
8
9
Ratios of Symmetrical
Component Parameters 1
Percent Fault
Current
X0/X1
R0/X1
R0/X0
0-3
0-1
0-1
0-0.1
>60
>95
2
<1.5
3-10
>10
0-1
<2
>25
<25
<2.3
2.73 8
0-10
>10
5
>100
2
(-1)
>2
<25
<1
<10
<1
<2.5
2.73
2.73
2.73
- to -40 6
-40 to 0
<8
>8
3 9
>3 79
Grounding Point
The most commonly used grounding
point is the neutral of the system or the
neutral point created by means of a
zigzag or a wye-broken delta grounding
transformer in a system that was operating as an ungrounded delta system.
In general, it is a good practice that all
source neutrals be grounded with the
same grounding impedance magnitude.
However, neutrals should not be tied
together to a single resistor. Where
one of the medium voltage sources is
the utility, their consent for impedance
grounding must be obtained.
The neutral impedance must have a
voltage rating at least equal to the rated
line-to-neutral voltage class of the system. It must have at least a 10-second
rating equal to the maximum future
line-to-ground fault current and a
continuous rating to accommodate the
triple harmonics that may be present.
Phase A
Phase B
Phase C
Neutral
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Grounded Wye
Phase B
Phase C
Phase A
Neutral
17
18
Phase A
Phase B
Phase C
19
20
Corner-Grounded Delta
21
April 2016
Sheet 01 066
i
ii
1
2
3
4
Phase A
Phase B
Phase C
Ungrounded Delta
Phase A
Phase B
Phase C
Ungrounded Wye
5
6
7
Resistance-grounded systems
(Figure 1.4-4) are simplest with a
wye connection, grounding the neutral
point directly through the resistor.
Delta systems can be grounded by
means of a zig-zag or other grounding
transformer. Wye broken delta
transformer banks may also be used.
8
9
10
15
16
17
18
19
20
Phase A
12
14
Phase C
Resistance-Grounded Wye
11
13
Phase A
Phase B
N
R
Phase B
Phase C
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-11
Sheet 01 067
Main
Neutral
Service
Transformer
ii
GFR
Sensor
Typical
Feeder
Ground Bus
Main Bonding
Jumper
Grounding
Electrode
Conductor
Equipment
Grounding
Conductor
Typical
4W Load
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
April 2016
Sheet 01 068
ii
1
Zero
Sequence
Sensor
Alternate
Sensor
Location
Sensor
Polarity
Marks
Main
Residual
Sensors
Main
Neutral
Neutral
Typical
Feeder
5
Typical
4W Load
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Typical
4W Load
Power
Transformer
Neutral Sensor
Main Bkr. 52-1
Main
Bkr.
52-1
Neutral Sensor
Main Bkr. 52-2
Tie Bkr.
52-T
A, B, C
Neutral
Typical
4-Wire
Feeder
Neutral Sensor
Tie Bkr. 52-T
( )B5
( )B4
4-Wire
Load
B4
B5
Digitrip
Main
Bkr.
52-2
A, B, C
Neutral
M1N
M1G
Typical
Feeder
GFR
52-T
a
TN
GFR
TG
M2G
M2N
3352-T
B5
B4
Digitrip
Main Bkr.
52-1
B4
B5
Digitrip
Main Bkr.
52-T
( )B5
Typical
52-T 4-Wire
Feeder
a
B4
B5
Digitrip
Main Bkr.
52-2
( )B4
4-Wire
Load
B4
B5
Digitrip
CA08104001E
April 2016
1.4-13
Sheet 01 069
Power
Transformer
Power
Transformer
X
X
Neutral
Sensor Main
Breaker 52-2
Neutral
Sensor Main
Breaker 52-1
Main
Breaker
52-1
Typical
Four-Wire
Feeder
Trip Unit
Phase A,
Phase B,
Phase C
Neutral
Neutral Sensor X
Tie Breaker 52-T
X
X
52-1
a
52-T
a
Main
Breaker
52-2
52-2
a
Typical
Four-Wire
Feeder
Trip Unit
Main Breaker
52-1
X
X
Trip Unit
Trip Unit
Tie Breaker Main Breaker
52-T
52-2
Four-Wire Load
Four-Wire Load
Further Information
Phase A,
Phase B,
Phase C
Neutral
Tie Breaker
52-T
Trip Unit
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
April 2016
Sheet 01 070
i
ii
1
2
3
Grounding Electrodes
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Motors
Surge capacitors and, where appropriate, surge arresters should be applied
at the motor terminals.
Generators
Surge capacitors and station
class surge arresters at the machine
terminals.
Surge Protection
Eatons VacClad-W metal-clad switchgear is applied over a broad range of
circuits, and is one of the many types
of equipment in the total system. The
distribution system can be subject to
voltage transients caused by lighting
or switching surges.
Recognizing that distribution system
can be subject to voltage transients
caused by lighting or switching, the
industry has developed standards to
provide guidelines for surge protection
of electrical equipment. Those guidelines should be used in design and
protection of electrical distribution
systems independent of the circuit
breaker interrupting medium. The
industry standards are:
ANSI C62
Guides and Standards for Surge
Protection
IEEE 242Buff Book
IEEE Recommended Practice for
Protection and Coordination of
Industrial and Commercial Power
Systems
IEEE 141Red Book
Recommended Practice for
Electric Power Distribution for
Industrial Plants
IEEE C37.20.2
Standards for Metal-Clad Switchgear
Eatons medium voltage metal-clad
and metal-enclosed switchgear that
uses vacuum circuit breakers is applied
over a broad range of circuits. It is one
of the many types of equipment in the
total distribution system. Whenever a
switching device is opened or closed,
certain interactions of the power
system elements with the switching
device can cause high frequency voltage
transients in the system. Due to the
wide range of applications and variety
of ratings used for different elements
in the power systems, a given circuit
may or may not require surge protection. Therefore, Eaton does not include
surge protection as standard with its
metal-clad or metal-enclosed medium
voltage switchgear. The user exercises
the options as to the type and extent
of the surge protection necessary
depending on the individual circuit
characteristics and cost considerations.
The following are Eatons recommendations for surge protection of medium
voltage equipment. Please note these
recommendations are valid when
using Eatons vacuum breakers only.
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-15
Sheet 01 071
i
ii
1
2
3
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 072
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Surge Arresters
Surge Capacitors
ZORC
RC Snubber
A RC Snubber device consists of a
non-inductive resistor R sized to match
surge impedance of the load cables,
typically 20 to 30 ohms, and connected
in series with a Surge Capacitor C. The
Surge Capacitor is typically sized to be
0.15 to 0.25 microfarad. Under normal
operating conditions, impedance of
the capacitor is very high, effectively
isolating the resistor R from the
system at normal power frequencies,
and minimizing heat dissipation during
normal operation. Under high frequency
transient conditions, the capacitor
offers very low impedance, thus effectively inserting the resistor R in the
power system as cable terminating
resistor, thus minimizing reflection of
the steep wave-fronts of the voltage
transients and prevents voltage doubling of the traveling wave. The RC
Snubber provides protection against
high frequency transients by absorbing and damping and the transients.
Please note RC Snubber is most effective in mitigating fast-rising transient
voltages, and in attenuating reflections
and resonances before they have a
chance to build up, but does not limit
the peak magnitude of the transient.
Therefore, the RC Snubber alone may
not provide adequate protection. To
limit peak magnitude of the transient,
application of surge arrester should
also be considered.
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-17
Sheet 01 073
Further Information
i
ii
1
2
3
4
5
6
Low Resistance
Grounded System
High Resistance or
Solidly
Ungrounded System Grounded System
Nominal
Nominal
Arrester Ratings kV
Nominal
MCOV
Low Resistance
Grounded System
High Resistance or
Ungrounded System
Nominal
Nominal
Arrester Ratings kV
MCOV
MCOV
Nominal
MCOV
MCOV
MCOV
7
8
2.30
2.40
3.30
3
3
3
2.55
2.55
2.55
3
3
3
2.55
2.55
2.55
3
6
6
2.55
5.10
5.10
3
3
3
2.55
2.55
2.55
3
3
3
2.55
2.55
2.55
3
6
6
2.55
5.10
5.10
4.00
4.16
4.76
3
6
6
2.55
5.10
5.10
6
6
6
5.10
5.10
5.10
6
6
9
5.10
5.10
7.65
3
6
6
2.55
5.10
5.10
6
6
6
5.10
5.10
5.10
6
6
9
5.10
5.10
7.65
10
4.80
6.60
6.90
6
6
6
5.10
5.10
5.10
6
6
6
5.10
5.10
5.10
9
9
9
7.65
7.65
7.65
6
6
6
5.10
5.10
5.10
7.20
8.32
8.40
11.00
11.50
12.00
6
9
9
9
9
10
5.10
7.65
7.65
7.65
7.65
8.40
6
9
9
9
10
10
5.10
7.65
7.65
7.65
8.40
8.40
10
12
12
15
18
18
8.40
10.20
10.20
12.70
15.30
15.30
6
9
9
9
9
10
5.10
7.65
7.65
6
6
9
9
9
9
5.10
5.10
7.65
7.65
7.65
7.65
9
9
9
10
12
12
7.65
7.65
7.65
8.40
10.20
10.20
7.65
7.65
8.40
10
12
12
8.40
10.20
10.20
15
18
18
12.70
15.30
15.30
12.47
13.20
13.80
10
12
12
8.40
10.20
10.20
12
12
12
10.20
10.20
10.20
18
18
18
15.30
15.30
15.30
10
12
12
8.40
10.20
10.20
12
12
15
10.20
10.20
12.70
18
18
18
15.30
15.30
15.30
14.40
18.00
20.78
22.00
22.86
23.00
12
15
18
18
18
18
10.20
12.70
15.30
15.30
15.30
15.30
12
15
18
18
21
21
10.20
12.70
15.30
15.30
17.00
17.00
21
27
30
30
17.00
22.00
24.40
24.40
12
15
18
18
18
18
10.20
12.70
15.30
15.30
15.30
15.30
15
18
21
21
24
24
12.70
15.30
17.00
17.00
19.50
19.50
21
27
30
30
36
36
17.00
22.00
24.40
24.40
29.00
29.00
24.94
25.80
26.40
21
21
21
17.00
17.00
17.00
24
24
24
19.50
19.50
19.50
21
21
21
17.00
17.00
17.00
24
24
27
19.50
19.50
22.00
36
36
39
29.00
29.00
31.50
16
33.00
34.50
38.00
27
30
30
22.00
24.40
24.40
30
30
24.40
24.40
27
30
30
22.00
24.40
24.40
36
36
36
29.00
29.00
29.00
45
48
36.50
39.00
17
11
12
13
14
15
18
19
20
21
CA08104001E
April 2016
Sheet 01 074
Power Quality
ii
Introduction
2
3
4
5
6
7
8
9
10
11
12
15
16
13
14
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-19
Sheet 01 075
Power Quality
Methodology for Ensuring Effective
Power Quality to Electronic Loads
2. Surge Protection
1. Grounding
SPD
480V
Stage 1 Protection
(Service Entrance)
SPD
120/208V
Computer or
Sensitive
Loads
Stage 2 Protection
(Branch Location)
20,000V
PEAK VOLTAGE
CP
= SPD
Inputhigh energy
transient disturbance; IEEE Category
C3 Impulse 20,000V; 10,000A
Best achievable
performance with single SPD
at main panel (950V, at Stage 1)
800V
i
ii
1
3
4
6
7
8
10
11
12
13
14
15
400V
0
25 uS
50 uS
TIME (MICROSECONDS)
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 076
Power Quality
ii
1.
Identify Critical Loads
1
2.
Identify Non-Critical Loads
2
3
3.
Identify Noise and
Disturbance Generating Loads
4.
Review Internal Power Distribution Layout
5.
Identify Facility Exposure to
Expected Levels of Disturbance
8
Figure 1.4-13. System Approach for Installing SPDs
9
10
11
6.
Apply Mitigating Equipment to:
a) Service Entrance Main Panels
b) Key Sub-Panels
c) Critical Loads
d) Data and Communication Lines
12
208Y/120 Panelboard
(integrated versus side mounted SPD)
13
SPD Integrated
into Panelboards,
Switchboards, MCCs
Side-Mounted SPD
used for Retrofit
Applications
15
16
SPD
SPD
17
GRO UND
18
19
G RO UND
1000
14
800
600
400
Integrated SPD
(direct bus bar connection)
200
0
200
2.00
Surge
Event
0.00
2.00
4.00
6.00
8.00
10.00
Microseconds
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-21
Sheet 01 077
Power Quality
Reference Tab 34 for detailed
information on SPDs.
209V (23%)
673V (75%)
3 ft (914.4 mm)
Lead Length
Loose Wiring
Twisted Wires
14 AWG
10 AWG
4 AWG
1 ft (304.8 mm)
Lead Length,
Twisted Wires
3. Voltage Regulation
Voltage regulation (i.e., sags or overvoltage) disturbances are generally
site- or load-dependent. A variety of
mitigating solutions are available
depending upon the load sensitivity,
fault duration/magnitude and the
specific problems encountered. It is
recommended to install monitoring
equipment on the AC power lines to
assess the degree and frequency of
occurrences of voltage regulation
problems. The captured data will allow
for the proper solution selection.
4. Harmonics Distortion
Most facilities also have communication lines that are potential sources
for external surges. As identified by
the power quality pyramid, proper
grounding of communication lines is
essential for dependable operation.
NEC Article 800 states that all data,
power and cable lines be grounded
and bonded.
System impedance
Amount of distorted current
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
April 2016
Sheet 01 078
Power Quality
i
ii
1
2
Harmonic Issues
A Phase
4. Overloading of neutral.
5
6
5. Unacceptable neutral-to-ground
voltages.
120
Lagging
B Phase
8
120
Lagging
C Phase
9
10
Balance
Neutral
Current
11
12
60 Hz Fundamental
13
3rd Harmonic
A Phase
14
15
120
Lagging
B Phase
16
17
120
Lagging
C Phase
18
19
21
20
Neutral
Triplen
Current
Phase Triplen Harmonics
Added in the Neutral
April 2016
1.4-23
Sheet 01 079
Power Quality
Single-phase power supplies for
computer and fixture ballasts are
rich in third harmonics and their
odd multiples.
Even with the phase currents perfectly
balanced, the harmonic currents in
the neutral can total 173% of the
phase current. This has resulted in
overheated neutrals. The Information
Technology Industry Council (ITIC)
formerly known as CBEMA, recommends that neutrals in the supply to
electronic equipment be oversized
to at least 173% of the ampacity of
the phase conductors to prevent
problems. ITIC also recommends
derating transformers, loading them
to no more than 50% to 70% of their
nameplate kVA, based on a rule-ofthumb calculation, to compensate
for harmonic heating effects.
In spite of all the concerns they
cause, nonlinear loads will continue
to increase. Therefore, the design of
nonlinear loads and the systems that
supply them will have to be designed
so that their adverse effects are greatly
reduced. Table 1.4-4 shows the typical
harmonic orders from a variety of
harmonic generating sources.
Class
AN
DF
Special application 2
General system
Dedicated system
10
5
2
16,400
22,800
36,500
3%
5%
10%
Typical
Harmonics 1
Maximum
individual
harmonic
3.0%
6-pulse rectifier
12-pulse rectifier
18-pulse rectifier
Total
harmonic
distortion
5.0%
Switch-mode power
supply
Fluorescent lights
Arcing devices
Transformer energization
3, 5, 7, 9, 11, 13
3, 5, 7, 9, 11, 13
2, 3, 4, 5, 7
2, 3, 4
Source
<20 3
20<50
50<100
100<1000
>1000
3
Voltage
Range
1.5%
2.5%
1.0%
1.5%
Vh
Percentages are x 100 for each
V1
harmonic
and
h = hmax
Vthd =
1/2
<11
4.0
7.0
10.0
12.0
15.0
11 17
23
35 TDD
<h <h <h <h
<17 <23 <35
2.0
3.5
4.5
5.5
7.0
1.5
2.5
4.0
5.0
6.0
0.6
1.0
1.5
2.0
2.5
0.3
0.5
0.7
1.0
1.4
5.0
8.0
12.0
15.0
20.0
i
ii
1
2
3
4
5
6
Harmonic Solutions
In spite of all the concerns nonlinear
loads cause, these loads will continue
to increase. Therefore, the design
of nonlinear loads and the systems
that supply them will need design so
adverse harmonic effects are greatly
reduced. Table 1.4-8 and depicts many
harmonic solutions along with their
advantages and disadvantages.
Eatons Engineering Services &
Systems Group (EESS) can perform
harmonic studies and recommend
solutions for harmonic problems.
7
8
9
10
11
12
13
14
2
Vh
h=2
It is important for the system designer
to know the harmonic content of the
utilitys supply voltage because it will
affect the harmonic distortion of
the system.
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 080
Power Quality
i
ii
Solutions
Advantages
Disadvantages
Line reactors
Inexpensive
For 6-pulse standard drive/rectifier, can
1
2
DC choke
12-pulse convertor
Harmonic mitigating
transformers/phase shifting
6-pulse drives
Substantial (5080%) reduction in harmonics
on load balance
Must have even multiples of matched loads
Bus connectedaccommodates
Tuned filters
Broadband filters
18-pulse converter
load diversity
Provides PF correction
of 18-pulse
High cost
Computers/
switch-mode
power supplies
Active filters
High cost
High cost
May increase voltage distortion
Harmonic mitigating
transformers
10
11
12
above 100 hp
IEEE 519 compliant
7
8
Fluorescent
lighting
Oversized neutral/derated
transformer
K-rated transformer
Harmonic mitigating
transformers
13
K-rated transformer
Active filters
High cost
14
Welding/arcing
loads
harmonic correction
Reduces voltage flicker
15
Tuned filters
16
17
System
solutions
Tuned filters
Provides PF correction
Lower cost compared to other systems
Harmonic mitigating
transformers
No PF correction benefit
Active filters
Highest cost
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-25
Sheet 01 081
5. Uninterruptible Power
Systems (UPS)
The advent of solid-state semiconductors over 40 years ago, and their
subsequent evolution to transistors,
and the miniaturization of electronics
into microprocessor over 25 years ago,
has created numerous computation
machines that assist us in every
conceivable manner. These machines,
and their clever configurations,
whether they take the form of
computers, appliance controls, fax
machines, phone systems, computers
of all sizes, server systems and server
farms, emergency call centers, data
processing at banks, credit companies,
private company communication
networks, government institutions and
defense agencies, all rely on a narrow
range of nominal AC power in order
for these devices to work properly.
Indeed, many other types of equipment also require that the AC electrical
power source be at or close to nominal
voltage and frequency. Disturbances of
the power translate into failed
processes, lost data, decreased
efficiency and lost revenue.
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 082
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
High-Speed Rotary
Concept of Operation
Startup Mode
13
14
15
It = Ir + Ic + Ig
16
Input
Contactor
Id = Ih + Ix + Ir
Static Disconnect
Switch
Line Inductor
Output
Contactor
Source
Load
17
18
Flywheel Converter
Ix
Field Coil
Driver
dc
Ic
Filter Inductor
dc
ac
19
20
Utility Converter
Inverter
Fuse
Ig
ac
Output Transformer
Id = Output Current
Ih = Harmonic Current
Ix = Reactive Load Current
Ir = Real Load Current
Ih
Integrated Motor/Flywheel/
and Generator
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-27
Sheet 01 083
Immediately after the output is transferred from bypass to the power electronic module, the flywheel field is
excited, which also provides magnetic
lift to unload the flywheel bearings.
The flywheel inverter is turned on
and gradually increases frequency
at a constant rate to accelerate the
flywheel to approximately 60 rpm.
Once the flywheel reaches 60 rpm,
the flywheel inverter controls the
acceleration to keep currents below the
maximum charging and the maximum
input settings. Once the flywheel
reaches 4000 rpm, the UPS is fully
functional and capable of supporting
the load during a power quality event.
flywheel acceleration continues until
the Flywheel reaches full charge at
7700 rpm. The total time to complete
startup is less than 5 minutes.
Discharge Mode
The UPS senses the deviation of
the voltage or frequency beyond
programmed tolerances and quickly
disconnects the supply source by
turning off the static disconnect switch
and opening the input contactor. The
disconnect occurs in less than one-half
cycle. Then the utility converter starts
delivering power from the DC bus to
the load, and the flywheel converter
changes the firing point of its IGBTs
to deliver power to the DC bus. The
UPS maintains a clean output voltage
within 3% or nominal voltage to the
load when input power is lost.
Recharge Mode
When input power is restored to
acceptable limits, the UPS synchronizes
the output and input voltages, closes
the input contactor and turns on the
static disconnect switch. The utility
converter then transfers power from
the flywheel to the input source by
linearly increasing the real input
current. The transfer time is programmable from 1 to 15 seconds. As soon
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 084
ii
1
2
3
4
5
6
7
8
9
10
11
12
UPS Module
13
Bypass Static Switch
14
15
Source
Load
Normal Rectifier/Charger
Breaker
AC
Inverter
DC
DC
16
17
18
Output
Breaker
AC
Battery Breaker
Battery
Figure 1.4-19. Typical Static UPS, Double Conversion Type with Battery Backup
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-29
Sheet 01 085
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 086
UPS Module
ii
1
2
Load
Source
Normal
Breaker
3
4
Rectifier/
Charger
Inverter
AC
DC
DC
AC
Battery
Breaker
5
Battery
6
7
Output
Breaker
Figure 1.4-20. Typical Static UPS, Standby Type with Battery Backup
UPS Module
9
10
Load
Source
Inductor
11
Bidirectional
Inverter/Charger
12
DC
13
AC
14
15
16
Battery
Figure 1.4-21. Typical Static UPS, Line Interactive Type with Battery Backup
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.4-31
Sheet 01 087
Technical Factors
ii
1
2
3
4
5
6
Elevator
Panel
Typical
Practical Factors
Because most low voltage distribution
equipment available is rated for up to
600 V, and conductors are insulated for
600 V, the installation of 480 V systems
uses the same techniques and is
essentially no more difficult, costly, or
hazardous than for 208 V systems. The
major difference is that an arc of 120 V
to ground tends to be se lf-extinguishing, while an arc of 277 V to ground
tends to be self-sustaining and likely to
cause severe damage. For this reason,
the National Electrical Code requires
ground fault protection of equipment
on grounded wye services of more
than 150 V to ground, but not exceeding
600 V phase-to-phase (for practical
purpose, 480Y/277 V services), for any
service disconnecting means rated
1000 A or more. The National Electrical
Code permits voltage up to 300 V
to ground on circuits supplying
permanently installed electric discharge
lamp fixtures, provided the luminaires
do not have an integral manual switch
and are mounted at least 8 ft (2.4 m)
above the floor. This permits a threephase, four-wire, solidly grounded
480Y/277 V system to supply directly all
of the fluorescent and high-intensity
discharge (HID) lighting in a building at
277 V, as well as motors at 480 V.
Emergency
Lighting Panel
Typical
HVAC
Panel
(Typical Every
Third Floor)
HVAC
Feeder
Busway
Riser
11
Emergency
Lighting
Riser
Typical
Building and
Miscellaneous
Loads
10
Typical
480Y/277 V
208Y/120 V
Panel
Panel
Dry Type Transformer
480-208Y/120 V
(Typical Every Floor)
Elevator
Riser
Typical
12
13
Typical
14
Typical
Typical
Spare
1
15
Automatic
Transfer Switch
1 4000 A
Main CB
Gen. CB
CTs
PTs
Utility
Service
Utility
Metering
Emergency
or Standby
Generator
4000A at 480Y/277V
100,000A Available Fault Current
16
17
18
Figure 1.4-22. Typical Power Distribution and Riser Diagram for a Commercial Office Building
1
19
20
21
CA08104001E
April 2016
Sheet 01 088
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Economic Factors
Utilization equipment suitable for
principal loads in most buildings
is available for either 480 V or 208 V
systems. Three-phase motors and
their controls can be obtained for either
voltage, and for a given horsepower
are less costly at 480 V. Fluorescent and
HID lamps can be used with either 277 V
or 120 V ballasts. However, in almost all
cases, the installed equipment will have
a lower total cost at the higher voltage.
Energy Conservation
Because of the greatly increased cost
of electrical power, designers must
consider the efficiency of electrical
distribution systems, and design for
energy conservation. In the past,
especially in commercial buildings,
design was for lowest first cost,
because energy was inexpensive.
Today, even in the speculative office
building, operating costs are so high
that energy-conserving designs can
justify their higher initial cost with a
rapid payback and continuing savings.
Buildings that must meet LEED certifications may require energy-saving
designs. There are four major sources
of energy conservation in a commercial
buildingthe lighting system, the
motors and controls, the transformers
and the HVAC system.
The lighting system must take
advantage of the newest equipment
and techniques. New light sources,
familiar light sources with higher
efficiencies, solid-state ballasts with
dimming controls, use of daylight,
environmental design, efficient
luminaires, computerized or
programmed control, and the like,
are some of the methods that can
increase the efficiency of lighting
systems. They add up to providing
the necessary amount of light, with the
desired color rendition, from the most
efficient sources, where and when it is
needed, and not providing light where
or when it is not necessary. Using the
best of techniques, office spaces that
originally required as much as 3.5W
per square foot have been given
improved lighting, with less glare
and higher visual comfort, using as
little as 1.0 to 2.0W per square foot.
In an office building of 200,000 square
feet (60,960 m), this could mean a
saving of 400 kW, which, at $0.05 per
kWh, 250 days per year, 10 hours per
day, could save $50,000 per year in
energy costs. Obviously, efficient
lighting is a necessity.
150
115
360
420
490
480
620
610
885
805
1535 2450
1170 1950
80
500
TP-1 150 230
535
310
615
480
730
745
945 1410
1235 2280
No
25% 35% 50% 75% Full
Loss Load Load Load Load Load
CA08104001E
April 2016
1.4-33
Sheet 01 089
CA08104001E
Prime Power
DER can be used for generating prime
power or for cogeneration. Prime power
concerns a system that is electrically
separated from the electrical grid.
Prime power is generated at remote
sites where commercial electrical
power is not available.
Cogeneration
Cogeneration is another outgrowth of
the high cost of energy. Cogeneration
is the production of electric power concurrently with the production of steam,
hot water and similar energy uses. The
electric power can be the main product, and steam or hot water the
byproduct, as in most commercial
installations, or the steam or hot water
can be the most required product,
and electric power a byproduct, as
in many industrial installations. In
some industries, cogeneration has
been common practice for many
years, but until recently it has not
been economically feasible for most
commercial installations.
For more information, visit: www.eaton.com/consultants
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
April 2016
Sheet 01 090
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
1.4-35
Sheet 01 091
Emergency Power
Most areas have requirements
for emergency and standby power
systems. The National Electrical Code
does not specifically call for any
emergency or standby power, but
does have requirements for those
systems when they are legally
mandated and classed as emergency
(Article 700), legally required standby
(Article 701) by municipal, state,
federal or other codes, or by any
i
ii
1
2
3
4
5
6
7
8
9
Utility
Source
Typical Application: Three engine generator sets serve the load, plus one additional engine
generator set for redundancy to achieve N+1 level of performance. Open or Closed transition is available.
G1
G2
G3
G4
10
11
Paralleling Switchgear
with Distribution
Revenue
Metering
12
HMI
Touchscreen
52G1
52G2
52G3
52G4
Main
Service
D1
D2
D3
13
D4
14
15
16
To Normal
Distribution
Circuits
ATS1
To Emergency
Circuits
ATS2
EDP1
ATS3
EDP2
ATS4
EDP3
17
18
EDP4
19
Optional Remote PC
with Software
LP1
BP1
LP2
BP2
LP3
BP3
LP4
BP4
20
Figure 1.4-23. Typical Emergency Power System
21
CA08104001E
April 2016
Sheet 01 092
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Peak Shaving
Many installations now have
emergency or standby generators.
In the past, they were required for
hospitals and similar locations, but
not common in office buildings or
shopping centers. However, many
costly and unfortunate experiences
during utility blackouts in recent years
have led to the more frequent installation of engine generators in commercial and institutional systems for safety
and for supplying important loads.
Sound Levels
Sound Levels of Electrical Equipment
for Offices, Hospitals, Schools and
Similar Buildings
Insurance underwriters and building
owners desire and require that the
electrical apparatus be installed
for maximum safety and the least
interference with the normal use of
the property. Architects should take
particular care with the designs for
hospitals, schools and similar buildings to keep the sound perception of
such equipment as motors, blowers
and transformers to a minimum.
Even though transformers are
relatively quiet, resonant conditions
may exist near the equipment, which
will amplify their normal 120 Hz hum.
Therefore, it is important that consideration be given to the reduction of
amplitude and to the absorption of
energy at this frequency. This problem
begins in the designing stages of the
equipment and the building. There are
two points worthy of consideration: 1)
What sound levels are desired in the
normally occupied rooms of this building? 2) To effect this, what sound level
in the equipment room and what type
of associated acoustical treatment
will give the most economical
installation overall?
A relatively high sound level in the
equipment room does not indicate
an abnormal condition within the
apparatus. However, absorption may
be necessary if sound originating in
an unoccupied equipment room is
objectionable outside the room.
Furthermore, added absorption
material usually is desirable if
there is a build-up of sound
due to reflections.
CA08104001E
April 2016
1.4-37
Sheet 01 093
Area Consideration
In determining permissible sound levels within a building, it is necessary to
consider how the rooms are to be used
and what levels may be objectionable
to occupants of the building. The
ambient sound level values given in
Table 1.4-10 are representative average
values and may be used as a guide in
determining suitable building levels.
Decrease in sound level varies at an
approximate rate of 6 dB for each
doubling of the distance from the
source of sound to the listener. For
example, if the level 6 ft (1.8 m) from
a transformer is 50 dB, the level at a
distance of 12 ft (3.7 m) would be 44 dB
and at 24 ft (7.3 m) the level decreases
to 38 dB, etc. However, this rule applies
only to equipment in large areas
equivalent to an out-of-door installation,
with no nearby reflecting surfaces.
Table 1.4-10. Typical Sound Levels
Description
Average
Decibel
Level (dB)
2530
3035
3540
3540
3545
4045
Stores
Residence (radio, TV off)
and small offices
Medium office (3 to 10 desks)
4555
60
61
61
Large office
Average factory
Average street
64
70
80
53
58
Table 1.4-11. Maximum Average Sound Levels for Medium Voltage TransformersDecibels
kVA
Liquid-Filled Transformers
Dry-Type Transformers
Self-Cooled
Rating (OA)
Forced-Air
Cooled Rating (FA)
Self-Cooled
Rating (AA)
Forced-Air
Cooled Rating (FA)
300
500
750
55
56
57
67
58
60
64
67
67
67
1000
1500
2000
58
60
61
67
67
67
64
65
66
67
68
69
2500
3000
3750
62
63
64
67
67
67
68
68
70
71
71
73
5000
6000
7500
65
66
67
67
68
69
71
72
73
73
74
75
10,000
68
70
76
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-1
Sheet 01 095
Function
Definition
Typical
Uses
19
21
Distance relay
23
24
27
Undervoltage relay
33
34
Position switch
3
4
32
25
Annunciator relay
ii
1
30
7
8
9
10
11
12
13
14
15
37
38
40
Field relay
18
19
41
42
CA08104001E
16
17
20
21
1.5-2
April 2016
Sheet 01 096
Table 1.5-1. Selected IEEE Device Numbers for Switchgear Apparatus (Continued)
Device
Number
Function
Definition
Typical
Uses
43
44
46
Eaton FP-5000/FP-4000/EDR-5000/
EDR-4000 feeder protective relays and
MP-3000/MP-4000/EMR-3000 motor
protective relays.
47
Eaton FP-5000/FP-4000/EDR-5000/
EDR-4000 feeder protective relays
and MP-3000/MP-4000 motor
protective relays.
48
49
Eaton MP-3000/MP-4000/EMR-3000/
ETR-4000 motor protective relays.
50
Instantaneous overcurrent,
or rate-of-rise relay
51
52
AC circuit breaker
17
53
18
55
19
56
20
59
Overvoltage relay
ii
3
4
5
6
7
8
9
10
11
12
13
14
15
16
21
For more information, visit: www.eaton.com/consultants
Eaton FP-5000/FP-4000/EDR-5000
feeder protective relays and MP-4000
motor protective relay.
CA08104001E
April 2016
1.5-3
Sheet 01 097
Device
Number
Function
Definition
Typical
Uses
60
ii
62
63
Pressure switch
64
65
Governor
66
Eaton MP-3000/MP-4000/EMR-3000
motor protective relays.
69
72
73
Level switch
DC circuit breaker
Load-resistor contactor
3
4
5
6
7
8
67
71
9
10
11
12
13
14
15
16
74
Alarm relay
78
18
79
AC reclosing relay
19
17
20
21
CA08104001E
1.5-4
April 2016
Sheet 01 098
i
ii
Table 1.5-1. Selected IEEE Device Numbers for Switchgear Apparatus (Continued)
Device
Number
Function
Definition
Typical
Uses
81
Frequency relay
83
85
86
Locking-out relay
87
90
Regulating device
91
94
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-5
Sheet 01 099
Closing relay/contactor
CL
CS
Control switch
Main Device
Alarm/auxiliary power
AC
Alternating current
BP
Bypass
BT
Bus tie
Capacitor
DC
Direct current
Exciter
Lowering relay
Feeder/field
Opening relay/contactor
Generator/ground
OP
Motor/metering
MOC
PB
Push button
Synchronizing/secondary
Raising relay
Transformer
TOC
Truck-operated contacts
Auxiliary relay
Auxiliary relay
Auxiliary relay
Actuating Quantities
Automatic
BF
Breaker failure
Close
Decelerating/down
Emergency
Failure/forward
HS
High speed
Local/lower
Manual
Open
OFF
Off
ON
On
Raise/reclosing/remote/reverse
Test/trip
TDC
TDDO
10
11
Coil/condenser/capacitor
CC
TDO
HC
Holding coil
TDPU
Amperes/alternating
Operating motor
THD
Current
OC
Opening contactor
Frequency/fault
Solenoid
I0
SI
Seal-in
I-, I2
Target
I+, I1
TC
Trip coil
Power/pressure
PF
Power factor
Speed
Temperature
Voltage/volts/vacuum
VAR
Reactive power
VB
Vibration
Watts
ii
2
3
4
5
6
7
8
9
12
13
14
15
16
17
18
19
20
21
CA08104001E
1.5-6
April 2016
Sheet 01 100
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Professional Organizations
American National Standards Institute
(ANSI)
Headquarters:
1819 L Street, NW
6th Floor
Washington, DC 20036
202-293-8020
Operations:
25 West 43rd Street
4th Floor
New York, NY 10036
212-642-4900
www.nema.org
www.ansi.org
www.nfpa.org
Headquarters:
3 Park Avenue
17th Floor
New York, NY 10016-5997
212-419-7900
Operations:
445 Hoes Lane
Piscataway, NJ 08854-1331
732-981-0060
www.ieee.org
www.iaei.org
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-7
Sheet 01 101
Motor Protection
Consistent with the 2011 NEC
430.6(A)(1) circuit breaker, HMCP and
fuse rating selections are based on
full load currents for induction motors
running at speeds normal for belted
motors and motors with normal
torque characteristics using data taken
from NEC Table 430.250 (three-phase).
Actual motor nameplate ratings shall
be used for selecting motor running
overload protection. Motors built
special for low speeds, high torque
characteristics, special starting
conditions and applications will
require other considerations as
defined in the application section
of the NEC.
These additional considerations may
require the use of a higher rated HMCP,
or at least one with higher magnetic
pickup settings.
Circuit breaker, HMCP and fuse
ampere rating selections are in
line with maximum rules given in
NEC 430.52 and Table 430.250. Based
on known characteristics of Eaton type
breakers, specific units are recommended. The current ratings are no
more than the maximum limits set by
the NEC rules for motors with code
letters F to V or without code letters.
Motors with lower code letters will
require further considerations.
In general, these selections were
based on:
1. Ambientoutside enclosure not
more than 40 C (104 F).
2. Motor startinginfrequent
starting, stopping or reversing.
3. Motor accelerating time
10 seconds or less.
4. Locked rotormaximum 6 times
motor FLA.
Type HMCP motor circuit protector
may not set at more than 1300% of
the motor full-load current to comply
with NEC 430.52. (Except for NEMA
Design B energy high-efficiency
motors that can be set up to 1700%.)
Circuit breaker selections are based
on types with standard interrupting
ratings. Higher interrupting rating types
may be required to satisfy specific
system application requirements.
Table 1.5-2. Motor Circuit Protector (MCP), Circuit Breaker and Fusible Switch Selection Guide
Horsepower
Full Load
Amperes
(NEC) FLA
Recommended Eaton
Circuit
Breaker
Motor Circuit
Protector Type HMCP
Time Delay
Amperes
Amperes
Non-Time Delay
Adj. Range
i
ii
230 V, Three-Phase
1
1-1/2
2
3
3.6
5.2
6.8
9.6
10
10
15
20
15
20
25
30
15
15
15
20
7
15
15
30
2170
45150
45150
90300
5
7-1/2
10
15
15.2
22
28
42
30
40
50
80
50
70
90
150
30
50
60
90
30
50
50
70
90300
150500
150500
210700
20
25
30
40
54
68
80
104
100
125
150
200
175
225
250
350
100
125
150
150
100
150
150
150
3001000
4501500
4501500
7502500
50
60
75
100
130
154
192
248
250
300
350
450
400
500
600
800
200
225
300
400
150
250
400
400
7502500
12502500
20004000
20004000
125
150
200
312
360
480
600
700
1000
1000
1200
1600
500
600
700
600
600
600
18006000
18006000
18006000
1
2
3
4
5
6
7
460 V, Three-Phase
1
1-1/2
2
3
1.8
2.6
3.4
4.8
6
6
6
10
6
10
15
15
15
15
15
15
7
7
7
15
2170
2170
2170
45150
5
7-1/2
10
15
7.6
11
14
21
15
20
25
40
25
35
45
70
15
25
35
45
15
30
30
50
45150
90300
90300
150500
20
25
30
40
27
34
40
52
50
60
70
100
90
110
125
175
50
70
70
100
50
70
100
100
150500
210700
3001000
3001000
50
60
75
100
65
77
96
124
125
150
175
225
200
150
300
400
110
125
150
175
150
150
150
150
4501500
7502500
7502500
7502500
125
150
200
156
180
240
300
350
450
500
600
800
225
250
350
250
400
400
12502500
20004000
20004000
575 V, Three-Phase
8
9
10
11
12
13
1
1-1/2
2
3
1.4
2.1
2.7
3.9
3
6
6
10
6
10
10
15
15
15
15
15
3
7
7
7
930
2170
2170
2170
5
7-1/2
10
15
6.1
9
11
17
15
20
20
30
20
30
35
60
15
20
25
40
15
15
30
30
45150
45150
90300
90300
20
25
30
40
22
27
32
41
40
50
60
80
70
90
100
125
50
60
60
80
50
50
50
100
150500
150500
150500
3001000
50
60
75
100
52
62
77
99
100
110
150
175
175
200
250
300
100
125
150
175
100
150
150
150
3001000
7502500
7502500
7502500
18
125
150
200
125
144
192
225
300
350
400
450
600
200
225
300
250
250
400
12502500
12502500
20004000
19
14
15
16
17
20
21
CA08104001E
1.5-8
April 2016
Sheet 01 102
ii
THW
Time
Delay
Amperes
THWN
XHHN
Non-Time
Delay
Recommended Eaton:
Circuit
Breaker 2
Amperes
Motor Circuit
Protector
Amperes
Adjustable Range
115 V, Single-Phase
1
2
3
3/4
1
1-1/2
13.8
16
20
14
14
12
20
20
30
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
25
30
35
45
50
60
30
35
40
2
3
5
7-1/2
24
34
56
80
10
8
4
3
30
50
85
100
0.50 (12.7)
0.75 (19.1)
1.00 (25.4)
1.00 (25.4)
0.50 (12.7)
0.50 (12.7)
0.75 (19.1)
1.00 (25.4)
45
60
100
150
80
110
175
250
50
70
100
150
230 V, Single-Phase
3/4
1
1-1/2
6.9
8
10
14
14
14
20
20
20
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
15
15
20
25
25
30
15
20
25
2
3
5
7-1/2
12
17
28
40
14
12
10
8
20
30
50
50
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.75 (19.1)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
25
30
50
70
40
60
90
125
30
40
60
80
Two-pole device
not available
1
2
Two-pole device
not available
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-9
Sheet 01 103
240 V, Three-Phase
480 V, Three-Phase
600 V, Three-Phase
Transformer
Rating
ThreePhase
kVA and
Impedance
Percent
Maximum
ShortCircuit
kVA
Available
from
Primary
System
300
5%
50,000
100,000
150,000
834
834
834
14,900
15,700
16,000
1700
1700
1700
16,600
17,400
17,700
722
722
722
12,900
13,600
13,900
2900
2900
2900
15,800
16,500
16,800
361
361
361
6400
6800
6900
1400
1400
1400
7800
8200
8300
289
289
289
5200
5500
5600
1200
1200
1200
6400
6700
6800
250,000
500,000
Unlimited
834
834
834
16,300
16,500
16,700
1700
1700
1700
18,000
18,200
18,400
722
722
722
14,100
14,300
14,400
2900
2900
2900
17,000
17,200
17,300
361
361
361
7000
7100
7200
1400
1400
1400
8400
8500
8600
289
289
289
5600
5700
5800
1200
1200
1200
6800
6900
7000
1388
1388
1388
21,300
25,200
26,000
2800
2800
2800
25,900 1203
28,000 1203
28,800 1203
20,000
21,900
22,500
4800
4800
4800
24,800
26,700
27,300
601
601
601
10,000
10,900
11,300
2400
2400
2400
12,400
13,300
13,700
481
481
481
8000
8700
9000
1900
1900
1900
9900
10,600
10,900
1388
250,000
1388
500,000
Unlimited 1388
26,700
27,200
27,800
2800
2800
2800
29,500 1203
30,000 1203
30,600 1203
23,100
23,600
24,100
4800
4800
4800
27,900
28,400
28,900
601
601
601
11,600
11,800
12,000
2400
2400
2400
14,000
14,200
14,400
481
481
481
9300
9400
9600
1900
1900
1900
11,200
11,300
11,500
2080
2080
2080
28,700
32,000
33,300
4200
4200
4200
32,900 1804
36,200 1804
37,500 1804
24,900
27,800
28,900
7200
7200
7200
32,100
35,000
36,100
902
902
902
12,400
13,900
14,400
3600
3600
3600
16,000
17,500
18,000
722
722
722
10,000
11,100
11,600
2900
2900
2900
12,900
14,000
14,500
2080
250,000
2080
500,000
Unlimited 2080
34,400
35,200
36,200
4200
4200
4200
38,600 1804
39,400 1804
40,400 1804
29,800
30,600
31,400
7200
7200
7200
37,000
37,800
38,600
902
902
902
14,900
15,300
15,700
3600
3600
3600
18,500
18,900
19,300
722
722
722
11,900
12,200
12,600
2900
2900
2900
14,800
15,100
15,500
2776
2776
2776
35,900
41,200
43,300
5600
5600
5600
41,500 2406
46,800 2406
48,900 2406
31,000
35,600
37,500
9800
9800
9800
40,600 1203
45,200 1203
47,100 1203
15,500
17,800
18,700
4800
4800
4800
20,300
22,600
23,500
962
962
962
12,400
14,300
15,000
3900
3900
3900
16,300
18,200
18,900
2776
250,000
2776
500,000
Unlimited 2776
45,200
46,700
48,300
5600
5600
5600
50,800 2406
52,300 2406
53,900 2406
39,100
40,400
41,800
9800
9800
9800
48,700 1203
50,000 1203
51,400 1203
19,600
20,200
20,900
4800
4800
4800
24,400
25,000
25,700
962
962
962
15,600
16,200
16,700
3900
3900
3900
19,500
20,100
20,600
4164
4164
4164
47,600
57,500
61,800
8300
8300
8300
55,900 3609
65,800 3609
70,100 3609
41,200
49,800
53,500
14,400
14,400
14,400
55,600 1804
64,200 1804
57,900 1804
20,600
24,900
26,700
7200
7200
7200
27,800 1444
32,100 1444
33,900 1444
16,500
20,000
21,400
5800
5800
5800
22,300
25,800
27,200
4164
250,000
4164
500,000
Unlimited 4164
65,600
68,800
72,500
8300
8300
8300
73,900 3609
77,100 3609
80,800 3609
56,800
59,600
62,800
14,400
14,400
14,400
71,200 1804
74,000 1804
77,200 1804
28,400
29,800
31,400
7200
7200
7200
35,600 1444
37,000 1444
38,600 1444
22,700
23,900
25,100
5800
5800
5800
28,500
29,700
30,900
10
2406
2406
2406
24,700
31,000
34,000
9600
9600
9600
34,300 1924
40,600 1924
43,600 1924
19,700
24,800
27,200
7800
7800
7800
27,500
32,600
35,000
11
250,000
500,000
Unlimited
2406
2406
2406
36,700
39,100
41,800
9600
9600
9600
46,300 1924
48,700 1924
51,400 1924
29,400
31,300
33,500
7800
7800
7800
37,200
39,100
41,300
12
3008
3008
3008
28,000
36,500
40,500
12,000
12,000
12,000
40,000 2405
48,500 2405
52,500 2405
22,400
29,200
32,400
9600
9600
9600
32,000
38,800
42,000
250,000
500,000
Unlimited
3008
3008
3008
44,600
48,100
52,300
12,000
12,000
12,000
56,600 2405
60,100 2405
64,300 2405
35,600
38,500
41,800
9600
9600
9600
45,200
48,100
51,400
3609
3609
3609
30,700
41,200
46,600
14,000
14,000
14,000
44,700 2886
55,200 2886
60,600 2886
24,600
33,000
37,300
11,500
11,500
11,500
36,100
44,500
48,800
250,000
500,000
Unlimited
3609
3609
3609
51,900
56,800
62,800
14,000
14,000
14,000
65,900 2886
70,800 2886
76,800 2886
41,500
45,500
50,200
11,500
11,500
11,500
53,000
57,000
61,700
4511
4511
4511
34,000
47,500
54,700
18,000
18,000
18,000
52,000 3608
65,500 3608
72,700 3608
27,200
38,000
43,700
14,400
14,400
14,400
41,600
52,400
58,100
16
250,000
500,000
Unlimited
4511
4511
4511
62,200
69,400
78,500
18,000
18,000
18,000
80,200 3608
87,400 3608
96,500 3608
49,800
55,500
62,800
14,400
14,400
14,400
64,200
69,900
77,200
17
500
5%
750
5.75%
1000
5.75%
1500
5.75%
2000
5.75%
2500
5.75%
3000
5.75%
3750
5.75%
50,000
100,000
150,000
50,000
100,000
150,000
50,000
100,000
150,000
50,000
100,000
150,000
50,000
100,000
150,000
50,000
100,000
150,000
50,000
100,000
150,000
50,000
100,000
150,000
Rated
Load
Continuous
Current,
Amps
Short-Circuit Current
rms Symmetrical Amps
Trans50%
Comformer Motor bined
Alone 1 Load 2
Rated
Load
Continuous
Current,
Amps
Short-Circuit Current
rms Symmetrical Amps
Trans100%
Comformer Motor bined
Alone 1 Load 2
Rated
Load
Continuous
Current,
Amps
Short-Circuit Current
rms Symmetrical Amps
Trans100%
Comformer Motor bined
Alone 1 Load 2
Rated
Load
Continuous
Current,
Amps
Short-Circuit Current
rms Symmetrical Amps
Trans100%
Comformer Motor bined
Alone 1 Load 2
Short-circuit capacity values shown correspond to kVA and impedances shown in this table. For impedances other than these, short-circuit currents
are inversely proportional to impedance.
The motors short-circuit current contributions are computed on the basis of motor characteristics that will give four times normal current.
For 208 V, 50% motor load is assumed while for other voltages 100% motor load is assumed. For other percentages, the motor short-circuit
current will be in direct proportion.
ii
1
2
3
4
5
6
13
14
15
18
19
20
21
CA08104001E
April 2016
Sheet 01 104
ii
30
45
75
208
240
480
83.3
125
208
72.2
108
180
312
416
625
271
361
541
135
180
271
36.1
54.1
90.2
600
28.9
43.3
72.2
2400
4160
7200
12,000
12,470
13,200
13,800
22,900
34,400
7.22
10.8
18.0
4.16
6.25
10.4
2.41
3.61
6.01
1.44
2.17
3.61
1.39
2.08
3.47
1.31
1.97
3.28
1.26
1.88
3.14
0.75
1.13
1.89
0.50
0.76
1.26
108
144
217
27.1
36.1
54.1
15.6
20.8
31.2
9.02
12.0
18.0
5.41
7.22
10.8
5.21
6.94
10.4
4.92
6.56
9.84
4.71
6.28
9.41
2.84
3.78
5.67
1.89
2.52
3.78
72.2
120
180
41.6
69.4
104
24.1
40.1
60.1
14.4
24.1
36.1
48.1
72.2
96.2
13.9
23.1
34.7
46.3
69.4
92.6
7.56
12.6
18.9
25.2
37.8
50.4
5.04
8.39
12.6
16.8
25.2
33.6
63.0
75.6
94.5
42.0
50.4
62.9
112-1/2
150
225
300
500
750
833
1388
2082
722
1203
1804
361
601
902
289
481
722
3
4
1000
1500
2000
2500
3000
3750
2776
4164
2406
3608
4811
1203
1804
2406
3007
3609
4511
962
1443
1925
2406
2887
3608
241
361
481
601
722
902
139
208
278
347
416
520
5000
7500
10,000
4811
1203
1804
2406
694
1041
1388
80.2
120
160
13.1
21.9
32.8
43.7
65.6
87.5
12.6
20.9
31.4
41.8
62.8
83.7
200
241
301
120
144
180
116
139
174
109
131
164
105
126
157
401
601
802
241
361
481
231
347
463
219
328
437
209
314
418
126
189
252
83.9
126
168
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-11
Sheet 01 105
Impedances Data
Network
Padmount
37.5
45
50
75
112.5
150
3.4
3.4
3.4
225
300
500
5.00
5.00
3.4
3.4
4.6
5.00
5.00
7.00
7.00
7.00
5.75
5.75
5.75
3750
5000
6.00
6.50
%Z
%R
%X
X/R
65 C Rise
112.5
150
225
5.00
5.00
5.00
1.71
1.88
1.84
4.70
4.63
4.65
2.75
2.47
2.52
300
500
750
5.00
5.00
5.75
1.35
1.50
1.41
4.81
4.77
5.57
3.57
3.18
3.96
1000
1500
2000
5.75
5.75
5.75
1.33
1.12
0.93
5.59
5.64
5.67
4.21
5.04
6.10
2500
5.75
0.86
5.69
6.61
%Z
%R
%X
X/R
300
500
750
4.50
5.75
5.75
2.87
2.66
2.47
3.47
5.10
5.19
1.21
1.92
2.11
1000
1500
2000
5.75
5.75
5.75
2.16
1.87
1.93
5.33
5.44
5.42
2.47
2.90
2.81
2500
5.75
1.74
5.48
3.15
300
500
750
4.50
5.75
5.75
1.93
1.44
1.28
4.06
5.57
5.61
2.10
3.87
4.38
1000
1500
2000
5.75
5.75
5.75
0.93
0.87
0.66
5.67
5.68
5.71
6.10
6.51
8.72
2500
5.75
0.56
5.72
10.22
% Efficiency
Liquid- Dry Transformers
Filled
Table 1.5-10. 600 V Primary Class ThreePhase DOE 2016 Energy-Efficient Dry-Type
Distribution Transformers, Aluminum Wound
kVA
80 C Rise
5.75
5.75
5.75
2000
2500
3000
kVA
150 C Rise
Liquid-Filled
750
1000
1500
%Z
%X
%R
X/R
4.04
2.52
3.75
2.08
1.13
2.64
3.46
2.25
2.67
0.60
0.50
0.99
75
112.5
150
4.05
4.66
3.48
3.34
4.22
3.09
2.29
1.99
1.61
1.46
2.12
1.92
225
300
4.20
4.46
3.96
4.26
1.39
1.32
2.85
3.23
3.77
2.34
4.26
2.08
1.37
3.44
3.14
1.90
2.52
0.66
0.72
1.37
75
112.5
150
4.45
5.17
3.89
3.90
4.81
3.59
2.14
1.89
1.49
1.83
2.54
2.41
225
300
4.90
4.80
4.73
4.65
1.28
1.21
3.69
3.85
80 C Rise Aluminum
15
30
45
4.19
2.50
2.43
2.94
1.76
2.01
2.98
1.78
1.37
0.99
0.99
1.46
75
112.5
150
225
3.11
2.61
2.80
3.35
2.81
2.31
2.64
3.20
1.32
1.21
0.93
0.99
2.12
1.92
2.85
3.23
%Z
%X
%R
X/R
i
ii
15
30
45
3.10
2.52
3.80
1.59
0.79
2.60
2.66
2.39
2.77
0.60
0.33
0.94
75
112.5
150
2.84
3.63
3.02
1.94
3.11
2.64
2.08
1.88
1.46
0.93
1.66
1.81
225
300
4.34
3.48
3.98
3.19
1.73
1.38
2.31
2.31
15
30
45
2.90
2.35
3.85
1.59
0.97
2.87
2.43
2.14
2.57
0.66
0.45
1.12
75
112.5
150
2.86
4.02
3.34
2.12
3.59
3.05
1.92
1.82
1.37
1.10
1.97
2.23
225
300
5.03
4.14
4.78
3.94
1.58
1.29
3.02
3.06
80 C Rise Copper
15
30
45
3.09
2.53
1.70
2.04
1.73
1.16
2.32
1.85
1.25
0.88
0.94
0.93
75
112.5
150
225
2.42
2.27
2.89
3.11
2.07
1.98
2.65
2.95
1.25
1.09
1.15
0.96
1.66
1.81
2.31
3.06
6
7
8
9
10
11
12
13
14
All
BILs
2545
kV BIL
4695
kV BIL
M96 kV
BIL
15
30
45
98.65
98.83
98.92
97.5
97.9
98.1
97.18
97.63
97.86
75
112.5
150
99.03
99.11
99.16
98.33
98.52
98.65
98.13
98.36
98.51
225
300
500
99.23
99.27
99.35
98.82
98.93
99.09
98.69
98.81
98.99
98.57
98.69
98.89
17
750
1000
1500
99.40
99.43
99.48
99.21
99.28
99.37
99.12
99.2
99.3
99.02
99.11
99.21
18
2000
2500
99.51
99.53
99.43
99.47
99.36
99.41
99.28
99.33
19
15
16
20
21
CA08104001E
April 2016
Sheet 01 106
Transformer Losses
i
ii
1
2
3
4
5
6
At 0% load:
1800 watts
At 50% load:
1800 watts + (13,300)(0.5)2 =
1800 watts + 3325 watts = 5125 watts
At 100% load:
1800 watts + 13,300 watts = 15,100 watts
At 110% load:
1800 watts + (13,300)(1.1)2 =
1800 watts + 16,093 watts = 17,893 watts
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-13
Sheet 01 107
Enclosures
Equipment
Watts
Loss
600
1400
2100
3700
500
750
840
600
1000
500
800
Table 1.5-13. Comparison of Specific Applications of Enclosures for Indoor Nonhazardous Locations
Provides a Degree of Protection Against the
Following Environmental Conditions
400
1000
1500
3200 A breaker
4000 A breaker
5000 A breaker
2400
3000
4700
Fuse limiters800 A CB
Fuse limiters1600 A CB
Fuse limiters2000 A CB
200
500
750
6P
12
12K 13
4
5
Table 1.5-14. Comparison of Specific Applications of Enclosures for Outdoor Nonhazardous Locations
Enclosure Type
3
1200
3S
3R 3
4000
5000
7000
4X
6P
11
Class
72 per foot
91 per foot
103 per foot
Acetylene
Hydrogen, manufactured gas
diethyl ether, ethylene, cyclopropane
I
I
I
I
II
II
II
III
MSHA
3200 A
4000 A
5000 A
39
56
92
124
244
200
Table 1.5-15. Comparison of Specific Applications of Enclosures for Indoor Hazardous Locations
Provides a Degree of Protection Against
Atmospheres Typically Containing
(For Complete Listing, See NFPA 497M)
1600 A
2000 A
2500 A
10
300
44 per foot
60 per foot
66 per foot
800 A
1200 A
1350 A
Structures3200 A
Structures4000 A
Structures5000 A
ii
Windblown dust
Hosedown
Corrosive agents
4X
3600
4500
225 A, 42 circuit
11 21 4
Fuse truck3200 A CB
Fuse truck4000 A CB
Enclosure Type
6
7
Enclosure Types
7 and 8, Class I Groups 6
Enclosure Type
9, Class II Groups 6
10
13
14
For Class III type ignitable fibers or combustible flyings, see the National Electrical Code, Article 500.
Due to the characteristics of the gas, vapor or dust, a product suitable for one class or group may
not be suitable for another class or group unless so marked on the product.
Note: If the installation is outdoors and/or additional protection is required by Tables 1.5-13 and
1.5-14, a combination-type enclosure is required.
> 96%
efficiency
12
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 108
Table 1.5-16. Conversion of NEMA Enclosure Type Ratings to IEC 60529 Enclosure Classification Designations (IP)
(Cannot be Used to Convert IEC Classification Designations to NEMA Type Ratings)
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-15
Sheet 01 109
Average Characteristics of
600 V Conductors
Ohms per 1000 ft (305 m)
The tables below are average characteristics based on data from IEEE
Standard 141-1993. Values from
different sources vary because of
operating temperatures, wire
stranding, insulation materials
and thicknesses, overall diameters,
random lay of multiple conductors
in conduit, conductor spacing, and
other divergences in materials, test
conditions and calculation methods.
These tables are for 600 V 5 kV and
15 kV conductors, at an average
temperature of 75 C. Other parameters are listed in the notes. For
medium voltage cables, differences
among manufacturers are considerably greater because of the wider variations in insulation materials and
thicknesses, shielding, jacketing, overall diameters, and the like. Therefore,
data for medium voltage cables should
be obtained from the manufacturer
of the cable to be used.
Z X R
For busway impedance data, see
Tab 21 of this catalog
For PF (power factor) values less
than 1.0, the effective impedance Ze
is calculated from
Z e R PF X sin (arc cos PF)
Application Notes
1
2
3
4
5
6
7
8
In Magnetic Duct
In Non-Magnetic Duct
5 kV Shielded and 15 kV
5 kV Shielded and 15 kV
8
8 (solid)
6
6 (solid)
0.811
0.786
0.510
0.496
0.0754
0.0754
0.0685
0.0685
0.814
0.790
0.515
0.501
0.811
0.786
0.510
0.496
0.0860
0.0860
0.0796
0.0796
0.816
0.791
0.516
0.502
0.811
0.786
0.510
0.496
0.0603
0.0603
0.0548
0.0548
0.813
0.788
0.513
0.499
0.811
0.786
0.510
0.496
0.0688
0.0688
0.0636
0.0636
4
4 (solid)
2
1
1/0
2/0
3/0
4/0
0.321
0.312
0.202
0.160
0.128
0.102
0.0805
0.0640
0.0632
0.0632
0.0585
0.0570
0.0540
0.0533
0.0519
0.0497
0.327
0.318
0.210
0.170
0.139
0.115
0.0958
0.0810
0.321
0.312
0.202
0.160
0.128
0.103
0.0814
0.0650
0.0742
0.0742
0.0685
0.0675
0.0635
0.0630
0.0605
0.0583
0.329
0.321
0.214
0.174
0.143
0.121
0.101
0.0929
0.321
0.312
0.202
0.160
0.127
0.101
0.0766
0.0633
0.0506
0.0506
0.0467
0.0456
0.0432
0.0426
0.0415
0.0398
0.325
0.316
0.207
0.166
0.134
0.110
0.0871
0.0748
0.321
0.312
0.202
0.160
0.128
0.102
0.0805
0.0640
0.0594
0.0594
0.0547
0.0540
0.814
0.789
0.514
0.500
0.326
0.318
0.209
0.169
0.0552
0.0464
0.0378
0.0356
0.0322
0.0294
0.0257
0.0216
0.0495
0.0493
0.0491
0.0490
0.0480
0.0466
0.0463
0.0495
0.0742
0.0677
0.0617
0.0606
0.0578
0.0551
0.0530
0.0495
0.0557
0.0473
0.0386
0.0362
0.0328
0.0300
0.0264
0.0223
0.0570
0.0564
0.0562
0.0548
0.0538
0.0526
0.0516
0.0497
0.0797
0.0736
0.0681
0.0657
0.0630
0.0505
0.0580
0.0545
0.0541
0.0451
0.0368
0.0342
0.0304
0.0276
0.0237
0.0194
0.0396
0.0394
0.0393
0.0392
0.0384
0.0373
0.0371
0.0356
0.0670
0.0599
0.0536
0.0520
0.0490
0.0464
0.0440
0.0405
0.0547
0.0460
0.0375
0.0348
0.0312
0.0284
0.0246
0.0203
0.0507
0.0504
0.0484
0.0466
0.0456
0.0451
0.0450
0.0438
0.138
0.114
0.0939
0.0792
0.0712
0.0644
0.0586
0.0559
0.0430
0.0421
0.0412
0.0396
0.0531
0.0508
0.0479
0.0445
250
300
350
400
450
500
600
750
ii
Table 1.5-17. 60 Hz Impedance Data for Three-Phase Copper Cable Circuits, in Approximate Ohms per 1000 ft (305 m) at 75 C (a) Three Single Conductors
Wire Size,
AWG or
kcmil
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 110
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Table 1.5-18. 60 Hz Impedance Data for Three-Phase Copper Cable Circuits, in Approximate Ohms per 1000 ft (305 m) at 75 C (b) Three Conductor Cable
Wire Size,
AWG or
kcmil
5 kV Shielded and 15 kV
5 kV Shielded and 15 kV
8
8 (solid)
6
6 (solid)
0.811
0.786
0.510
0.496
0.0577
0.0577
0.0525
0.0525
0.813
0.788
0.513
0.499
0.811
0.786
0.510
0.496
0.0658
0.0658
0.0610
0.0610
0.814
0.789
0.514
0.500
0.811
0.786
0.510
0.496
0.0503
0.0503
0.0457
0.0457
0.812
0.787
0.512
0.498
0.811
0.786
0.510
0.496
0.0574
0.0574
0.0531
0.0531
4
4 (solid)
2
1
1/0
2/0
3/0
4/0
0.321
0.312
0.202
0.160
0.128
0.102
0.0805
0.0640
0.0483
0.0483
0.0448
0.0436
0.0414
0.0407
0.0397
0.0381
0.325
0.316
0.207
0.166
0.135
0.110
0.0898
0.0745
0.321
0.312
0.202
0.160
0.128
0.103
0.0814
0.0650
0.0568
0.0508
0.0524
0.0516
0.0486
0.0482
0.0463
0.0446
0.326
0.317
0.209
0.168
0.137
0.114
0.0936
0.0788
0.321
0.312
0.202
0.160
0.127
0.101
0.0766
0.0633
0.0422
0.0422
0.0390
0.0380
0.0360
0.0355
0.0346
0.0332
0.324
0.315
0.206
0.164
0.132
0.107
0.0841
0.0715
0.321
0.312
0.202
0.160
0.128
0.102
0.0805
0.0640
0.0495
0.0495
0.0457
0.0450
0.813
0.788
0.513
0.499
0.325
0.316
0.207
0.166
0.0552
0.0464
0.0378
0.0356
0.0322
0.0294
0.0257
0.0216
0.0379
0.0377
0.0373
0.0371
0.0361
0.0349
0.0343
0.0326
0.0670
0.0598
0.0539
0.0514
0.0484
0.0456
0.0429
0.0391
0.0557
0.0473
0.0386
0.0362
0.0328
0.0300
0.0264
0.0223
0.0436
0.0431
0.0427
0.0415
0.0404
0.0394
0.0382
0.0364
0.0707
0.0640
0.0576
0.0551
0.0520
0.0495
0.0464
0.0427
0.0541
0.0451
0.0368
0.0342
0.0304
0.0276
0.0237
0.0197
0.0330
0.0329
0.0328
0.0327
0.0320
0.0311
0.0309
0.0297
0.0634
0.0559
0.0492
0.0475
0.0441
0.0416
0.0389
0.0355
0.0547
0.0460
0.0375
0.0348
0.0312
0.0284
0.0246
0.0203
0.0423
0.0420
0.0403
0.0389
0.0380
0.0376
0.0375
0.0366
0.135
0.110
0.090
0.0749
0.0666
0.0596
0.0530
0.0505
0.0359
0.0351
0.0344
0.0332
0.0476
0.0453
0.0422
0.0389
250
300
350
400
450
500
600
750
Table 1.5-19. 60 Hz Impedance Data for Three-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 Ft (305 m) at 90 C (a) Three Single Conductors
Wire Size,
AWG or
kcmil
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
1000
In Magnetic Duct
In Non-Magnetic Duct
5 kV Shielded and 15 kV
5 kV Shielded and 15 kV
0.847
0.532
0.335
0.265
0.210
0.167
0.133
0.106
0.053
0.050
0.046
0.048
0.043
0.041
0.040
0.039
0.849
0.534
0.338
0.269
0.214
0.172
0.139
0.113
0.532
0.335
0.265
0.210
0.167
0.132
0.105
0.068
0.063
0.059
0.056
0.055
0.053
0.051
0.536
0.341
0.271
0.217
0.176
0.142
0.117
0.847
0.532
0.335
0.265
0.210
0.167
0.133
0.105
0.042
0.040
0.037
0.035
0.034
0.033
0.037
0.031
0.848
0.534
0.337
0.267
0.532
0.335
0.265
0.054
0.050
0.047
0.535
0.339
0.269
0.0896
0.0750
0.0644
0.0568
0.0459
0.0388
0.0338
0.0318
0.0252
0.0384
0.0375
0.0369
0.0364
0.0355
0.0359
0.0350
0.0341
0.0341
0.0975
0.0839
0.0742
0.0675
0.0580
0.0529
0.0487
0.0466
0.0424
0.0892
0.0746
0.0640
0.0563
0.0453
0.0381
0.0332
0.0310
0.0243
0.0495
0.0479
0.0468
0.0459
0.0444
0.0431
0.0423
0.0419
0.0414
0.102
0.0887
0.0793
0.0726
0.0634
0.0575
0.0538
0.0521
0.0480
0.0894
0.0746
0.0640
0.0563
0.0453
0.0381
0.0330
0.0309
0.0239
0.0307
0.0300
0.0245
0.0291
0.213
0.170
0.137
0.109
0.0945
0.0804
0.0705
0.0634
0.210
0.167
0.132
0.105
0.0891
0.0744
0.0638
0.0560
0.045
0.044
0.042
0.041
0.0396
0.0383
0.0374
0.0367
0.215
0.173
0.139
0.113
0.0975
0.0837
0.0740
0.0700
0.0284
0.0287
0.0280
0.0273
0.0273
0.0535
0.0477
0.0433
0.0412
0.0363
0.0450
0.0377
0.0326
0.0304
0.0234
0.0355
0.0345
0.0338
0.0335
0.0331
0.0573
0.0511
0.0470
0.0452
0.0405
Table 1.5-20. 60 Hz Impedance Data for Three-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 ft (30 m) at 90 C (b) Three Conductor Cable
Wire Size,
AWG or
kcmil
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
1000
5 kV Shielded and 15 kV
5 kV Shielded and 15 kV
R
0.847
0.532
0.335
0.265
0.210
0.167
0.133
0.106
0.053
0.050
0.046
0.048
0.043
0.041
0.040
0.039
0.849
0.534
0.338
0.269
0.214
0.172
0.139
0.113
0.335
0.265
0.056
0.053
0.340
0.270
0.847
0.532
0.335
0.265
0.042
0.040
0.037
0.035
0.848
0.534
0.337
0.267
0.335
0.265
0.045
0.042
0.338
0.268
0.210
0.167
0.133
0.105
0.050
0.049
0.048
0.045
0.216
0.174
0.141
0.114
0.210
0.167
0.133
0.105
0.034
0.033
0.037
0.031
0.213
0.170
0.137
0.109
0.210
0.167
0.132
0.105
0.040
0.039
0.038
0.036
0.0896
0.0750
0.0644
0.0568
0.0459
0.0388
0.0338
0.0318
0.0252
0.0384
0.0375
0.0369
0.0364
0.0355
0.0359
0.0350
0.0341
0.0341
0.0975
0.0839
0.0742
0.0675
0.0580
0.0529
0.0487
0.0466
0.0424
0.0895
0.0748
0.0643
0.0564
0.0457
0.0386
0.0335
0.0315
0.0248
0.0436
0.0424
0.0418
0.0411
0.0399
0.0390
0.0381
0.0379
0.0368
0.100
0.0860
0.0767
0.0700
0.0607
0.0549
0.0507
0.0493
0.0444
0.0894
0.0746
0.0640
0.0563
0.0453
0.0381
0.0330
0.0309
0.0239
0.0307
0.0300
0.0245
0.0291
0.0284
0.0287
0.0280
0.0273
0.0273
0.0945
0.0804
0.0705
0.0634
0.0535
0.0477
0.0433
0.0412
0.0363
0.0893
0.0745
0.0640
0.0561
0.0452
0.0380
0.0328
0.0307
0.0237
0.0349
0.0340
0.0334
0.0329
0.0319
0.0312
0.0305
0.0303
0.0294
0.214
0.171
0.138
0.111
0.0959
0.0819
0.0722
0.0650
0.0553
0.0492
0.0448
0.0431
0.0378
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-17
Sheet 01 111
Conductor Ampacities
Current Carrying Capacities of Copper and Aluminum and Copper-Clad Aluminum Conductors
From National Electrical Code (NEC), 2011 Edition (NFPA 70-2011)
Table 1.5-21. Allowable Ampacities of Insulated Conductors Rated 02000 V, 60 to 90 C (140 to 194 F).
ii
Not more than three current-carrying conductors in raceway, cable or earth (directly buried), based on ambient temperature of 30 C (86 F).
Size
AWG or
kcmil
Types
60 C (140 F)
TW, UF
75 C (167 F)
90 C (194 F)
60 C (140 F)
Size
75 C (167 F)
90 C (194 F)
RHW, THHW,
THW, THWN,
XHHW, USE
Types
RHW, THHW,
THW, THWN,
XHHW, USE, ZW
Copper
AWG or
kcmil
2
3
4
18
16
14 1
15
20
14
18
25
12 1
10 1
8
20
30
40
25
35
50
30
40
55
20
25
30
20
30
40
25
35
45
12 1
10 1
8
6
4
3
55
70
85
65
85
100
75
95
110
40
55
65
50
65
75
60
75
85
6
4
3
2
1
1/0
95
110
125
115
130
150
130
150
170
75
85
100
90
100
120
100
115
135
2
1
1/0
2/0
3/0
4/0
145
165
195
175
200
230
195
225
260
115
130
150
135
155
180
150
175
205
2/0
3/0
4/0
250
300
350
215
240
260
255
285
310
290
320
350
170
190
210
205
230
250
230
255
280
250
300
350
400
500
600
280
320
355
335
380
420
380
430
475
225
260
285
270
310
340
305
350
385
400
500
600
700
750
800
385
400
410
460
475
490
520
535
555
310
320
330
375
385
395
420
435
450
700
750
800
900
1000
1250
435
455
495
520
545
590
585
615
665
355
375
405
425
445
485
480
500
545
900
1000
1250
1500
1750
2000
520
545
560
625
650
665
705
735
750
435
455
470
520
545
560
585
615
630
1500
1750
2000
9
10
11
12
13
14
Note: For complete details of using Table 1.5-21, see NEC Article 310 in its entirety.
15
Table 1.5-22. Correction Factors From NFPA 70-2011 (See Table 310.15 [B][2][a])
Ambient
Temperature C
For ambient temperatures other than 30 C (86 F), multiply the allowable ampacities shown
above by the appropriate factor shown below.
Ambient
Temperature F
2125
2630
3135
1.08
1.00
0.91
1.05
1.00
0.94
1.04
1.00
0.96
1.08
1.00
0.91
1.05
1.00
0.94
1.04
1.00
0.96
07077
07886
08795
3640
4145
4650
0.82
0.71
0.58
0.88
0.82
0.75
0.91
0.87
0.82
0.82
0.71
0.58
0.88
0.82
0.75
0.91
0.87
0.82
096104
105113
114122
5155
5660
6170
0.41
0.67
0.58
0.33
0.76
0.71
0.58
0.41
0.67
0.58
0.33
0.76
0.71
0.58
123131
132140
141158
7180
0.41
0.41
159176
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 112
Conductor Ampacities
i
ii
1
2
3
4
5
6
7
(A) General.
(1) Tables or Engineering Supervision.
Ampacities for conductors shall
be permitted to be determined by
tables as provided in 310.15(B) or
under engineering supervision,
as provided in 310.15(C).
Note: Informational Note No. 1: Ampacities
provided by this section do not take voltage
drop into consideration. See 210.19(A),
Informational Note No. 4, for branch circuits
and 215.2(A), Informational No. 2, for feeders.
Note: Informational Note No. 2: For the
allowable ampacities of Type MTW wire,
see Table 13.5.1 in NFPA 79-2007, Electrical
Standard for Industrial Machinery.
11
12
8
9
10
13
14
15
16
17
18
19
20
21
Temperature
Adder F (C)
60 (33)
40 (22)
30 (17)
25 (14)
CA08104001E
April 2016
1.5-19
Sheet 01 113
Conductor Ampacities
(4) Bare or Covered Conductors.
Where bare or covered conductors
are installed with insulated
conductors, the temperature
rating of the bare or covered
conductor shall be equal to the
lowest temperature rating of the
insulated conductors for the
purpose of determining ampacity.
(5) Neutral Conductor.
(a) A neutral conductor that carries
only the unbalanced current from
other conductors of the same
circuit shall not be required to
be counted when applying the
provisions of 310.15(B)(3)(a).
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 114
i
ii
1
2
3
4
Direct
Current
hp 746
E % eff
kW 1000
Alternating Current
Two-PhaseFour-Wire 1
Three-Phase
kW 1000
E pf
hp 746
2 E % eff pf
kW 1000
2 E pf
kVA 1000
E
l E pf
1000
kVA 1000
2E
l E 2 pf
1000
Single-Phase
Kilowatts
IE
1000
kVA
IE
1000
IE2
1000
hp 746
3 E % eff pf
kW 1000
3 E % pf
kVA 1000
3E
l E 3 pf
1000
IE 3
1000
Horsepower (output)
I E % eff
746
I E % eff pf
746
I E 2 % eff pf
746
I E 3 % eff pf
746
hp 746
E % eff pf
Note: Units of measurement and definitions for E (volts), I (amperes), and other abbreviations are given below under Common Electrical Terms.
5
6
Volt (E)
Ohm (R)
= unit of resistance
7
8
Ampere (l)
E
Ohms law: I = (DC or 100% pf)
R
Megohm
= 1,000,000 ohms
10
Watt (W)
11
12
13
Kilowatt (kW)
= 1000 watts
VA
Watthour (Wh)
14
15
16
17
18
19
kW
---------kVA
Watts
Determining Watts pf = ---------------------------------------------Volts Amperes
Kilowatt-hour (kWh)
= 1000 watthours
Horsepower (hp)
Demand Factor
Diversity Factor
Load Factor
(F to C)
(C to F)
C = 5/9 (F32)
F = 9/5(C)+32
C 15
F
5
10
14
C 25
F 77
30
86
C 65
F 149
5
23
0
32
5
41
35 40 45
95 104 113
70 75
158 167
80 85
176 185
10
50
15
59
20
68
50
55
122 131
60
140
90
95
194 203
100
212
1 Inch
= 2.54 centimeters
1 Kilogram
= 2.20 lbs
1 Square Inch = 1,273,200 circular mills
1 Circular Mill = 0.785 square mil
1 Btu
= 778 ft lbs
= 252 calories
1 Year
= 8760 hours
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-21
Sheet 01 115
Seismic Requirements
Seismic Requirements
i
ii
1
General
In the 1980s, Eaton embarked on a
comprehensive program centered
around designing and building
electrical distribution and control
equipment capable of meeting and
exceeding the seismic load requirements of the Uniform Building Code
(UBC) and California Building Code
(CBC). These codes emphasize building design requirements. Electrical
equipment and distribution system
components are considered attachments to the building. The entire
program has been updated to show
compliance with the 2009 International
Building Code (IBC) and the 2010 CBC
seismic requirements. A cooperative
effort with the equipment user, the
building designer and the equipment
installer ensures that the equipment
is correctly anchored such that it can
withstand the effects of an earthquake.
Eatons electrical distribution and
control equipment has been tested
and seismically proven for requirements exceeding the IBC and CBC.
Over 100 different assemblies
representing essentially all product
lines have been successfully tested
and verified to seismic levels higher
than the maximum seismic requirements specified in the IBC and CBC.
The equipment maintained structural
integrity and demonstrated the ability
to function immediately after the
seismic tests. A technical paper,
Earthquake Requirements and Eaton
Distribution and Control Equipment
Seismic Capabilities (SA12501SE),
provides a detailed explanation
of the applicable seismic codes
and Eatons equipment qualification
program. The paper may be found
at www.eaton.com/seismic. Type
in SA12501SE in the document
search field.
2
3
4
5
6
Figure 1.5-1. Typical Earthquake Ground Motion Map for the United States
Process
According to Chapter 16 of the 2009
IBC, structure design, the seismic
requirements of electrical equipment
in buildings may be computed in two
steps. The first step is to determine
the maximum ground motion to be
considered at the site. The second step
is to evaluate the equipment mounting
and attachments inside the building
or structure. These are then evaluated
to determine appropriate seismic test
requirements. The ground motion,
seismic requirements of the equipment,
and the seismic response spectrum
requirements are discussed on
Page 1.5-23, see Figure 1.5-3.
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 116
Seismic Requirements
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Ground Motion
According to the code, the first and
most important step in the process
is to determine the maximum
considered earthquake spectral
response acceleration at short
periods of 0.2 seconds (SS) and at
a period of 1.0 second (S1). These
values are determined from a set
of 24 spectral acceleration maps
(Figure 1.5-1) and include numerous
contour lines indicating the severity
of the earthquake requirements at a
particular location in the country.
The spectral acceleration maps
indicate low to moderate seismic
requirements for the entire country,
with the exception of two particular
areas; the West Coast and the Midwest
(the New Madrid area). The seismic
requirements at the New Madrid area
are approximately 30% higher than the
maximum requirements of the West
Coast. The maps also suggest that the
high seismic requirements in both
regions, West Coast and Midwest,
quickly decrease as one moves away
from the fault area. Therefore, the high
requirements are only limited to a
relatively narrow strip along the fault
lines. Just a few miles away from this
strip, only a small percentage of the
maximum requirements are indicated.
Assuming the worse condition, which
is a site directly located near a fault,
the maximum considered earthquake
spectral response acceleration at short
periods of 0.2 seconds (SS) is equal to
285% gravity and at 1.0 second period
(S1) is 124% gravity. These numbers
are the maximum numbers for the
entire country except for the New
Madrid area. These particular sites are
on the border of California and Mexico
(S1) and in Northern California (SS).
To help understand the 2009 IBC (and
2010 CBC) seismic parameters for a
specific building location, the link to
the US Geological Society is extremely
helpful: http://earthquake.usgs.gov/
research/hazmaps/design/
Download the file Java Ground
Motion Parameter Calculatorand
save it to your hard drive, then run the
executable that was downloaded.
The program will allow one to enter
the latitude and longitude of a
location. (One must be connected
to the Internet to run this application,
even after downloading the program.)
The IBC (CBC) seismic parameters for
that location will then be displayed.
TS = SD1/SDS = 1.24/1.90 =
0.653 seconds (1.53 Hz)
According to the IBC and ASCE 7, the
spectral acceleration (Sa) at periods
less than 1.45 seconds may be computed by using the following formula:
Sa = SDS (0.6 T/T0 + 0.4)
Where T is the period where Sa is
being calculated:
Therefore, the acceleration at
0.0417 seconds (24 Hz), for example,
is equal to:
Sa = 1.90 (0.6 (0.0417/0.131) + 0.4) = 1.12 g
SDS
Sa =
SD1
T
SD1
Sa =
T0
TS
1.0
Period T (sec)
SD1 TL
T2
TL
CA08104001E
April 2016
1.5-23
Sheet 01 117
Seismic Requirements
Acceleration (g peak)
10
9
8
7
ii
1
2
3
Zero Period
Acceleration = Maximum
Table Test Motion
4
3
1.0
.9
.8
.7
.6
.5
Zero Period
Acceleration = Maximum
Floor Motion
.4
.3
.2
9
.1
1
4 5 6 78
9 10
20
30
40
60
80
100
Frequency Hz
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 118
Seismic Requirements
ii
2
3
4
5
6
7
8
9
10
11
12
13
14
10
Acceleration (g)
1
Eaton Seismic
0.1
1
10
100
Frequency (Hz)
Acceleration (g)
0.1
10
100
Frequency (Hz)
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
April 2016
1.5-25
Sheet 01 119
Seismic Requirements
ii
Eaton Equipment
Low voltage metal-enclosed switchgear
DS II
Magnum DS
High resistance ground
Panelboards
Pow-R-Line C 1a, 1a-LX, 2a, 2a-LX, 3a, 3E, 4,
5P, F-16 and Pow-R-Command
Switchboards
Instant
Pow-R-Line 5P
Integrated facilities
Pow-R-Line C
Multimeter
Pow-R-Line i
MCC
IT.
Advantage
Series 2100
FlashGard
Freedom 2100
Low voltage busway
Pow-R-Way and associated fittings
Pow-R-Way III and associated fittings
Dry type transformers
Mini powercenters
EP, EPT, DS-3, DT-3
Transfer switches
Automatic transfer switch equipment
Uninterruptible power supplies (UPS)
Battery modules
UPSs
Enclosed control safety switches
General-duty
Heavy-duty
Elevator control module
Medium voltage switchgear
Type VacClad-W
Type MMVS
MEF
Type MVS/MEB
MV bus
Metal-enclosed non-segregated phase bus
Network protectors
Type CM-22
Type CMD
Medium voltage control
AMPGARD
SC9000 drives
Substation transformers
Dry-type
Liquid type
Unitized dry-type power centers
1
2
3
4
5
6
7
8
9
10
11
12
13
Figure 1.5-6. Sample Seismic Certificate
14
15
16
17
18
19
20
21
CA08104001E
April 2016
Sheet 01 120
Seismic Requirements
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E