Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

7SR10

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Reyrolle

Protection
Devices

7SR10 Argus
Overcurrent and Earth Fault Relay

7SR10 Argus
Overcurrent and Earth Fault Relay
Supervision
74 T/CCS Trip and Close Circuit Supervision
Control
86 Lockout

CB Control
CB Trip/Close
Features
Cold Load Settings
Two Settings Groups
Password Protection 2 levels
User Programmable Logic
Self Monitoring
Circuit Breaker Trip and Maintenance Counter
Trip Timers

User Interface
20 Character x 4 Line Backlit LCD
Menu Navigation Keys
9 User Programmable Tri-colour LEDs
User Language Configuration

Description
The 7SR10 overcurrent and earth fault relay is developed by using
the latest generation of hardware technology and is available
in two variants depending on Binary IO configuration and data
communication facility. 7SR10 is a member of Siemens Reyrolle
protection devices Argus product family.
The 7SR10 overcurrent and earth fault relay is housed in a
4U high, size E4 non draw-out case and these relays provide
protection, monitoring, instrumentation, and metering with
integrated input and output logic, data logging and fault reports.
Communication access to the relay functionality is via a front USB
port for local PC connection or rear electrical RS485 (optional)
port for remote connection.

Function Overview
Protection
46BC
46 NPS
49
50
50N/G
51
51N/G
51c
50BF
81HLB2
50 SEF
51SEF
2

Broken Conductor, Load Unbalance


Negative Phase Sequence Overcurrent
Thermal Overload
Instantaneous Overcurrent Protection
Instantaneous Earth Fault
Time Delayed Overcurrent Protection
Time Delayed Derived/Measured Earth Fault Protection
Current Protection: Cold Load
Circuit Breaker Fail
Inrush Restraint
Instantaneous Sensitive Earth Fault
Time Delayed Sensitive Earth Fault Protection

Monitoring Functions
Primary/Secondary Current Phases and Earth
Positive Phase Sequence (PPS) Current
Negative Phase Sequence (NPS) Current
Zero Phase Sequence (ZPS) Current
Frequency
Binary Input/Output status
Trip circuit healthy/failure
Time and date
Starters
Fault records
Event records
Circuit breaker trip counters
I2t summation for contact wear

Hardware
4 CT
4 CT

3 Binary Inputs/3 Binary Outputs 10 LEDs


6 Binary Inputs/6 Binary Outputs 10 LEDs

Data Storage and Communication


Front USB port + Rear RS485 port (optional)
Protocols - IEC60870-5-103, DNP3.0 or Modbus RTU
Event Records - User Configurable
Fault Records
Waveform Records
Measurands
Commands
Time Synchronism
Viewing and Changing Settings

51c Cold Load Protection

Application
The 7SR10 overcurrent and earth fault relay is a numerical
overcurrent protection relay intended for use in the distribution and
industrial networks. It provides a highly comprehensive functional
software package with a range of integral application functions
aimed at reducing installation, wiring, and engineering time.
A wide range of measured values can be viewed on the front LCD
or remotely via the communication channel.
The integrated control feature allows the operation of a single
circuit breaker and monitoring its trip and closed circuits.

If a circuit breaker is closed onto a cold load, (i.e.) one that has
not been powered for a prolonged period, this can impose a
higher than normal load-current demand on the system which
could exceed normal settings. These conditions can exist for an
extended period and must not be interpreted as a fault. To allow
optimum setting levels to be applied for normal operation, the
cold load pickup feature will apply alternative current settings for
a limited period.
The feature resets when either the circuit breaker has been closed
for a settable period or if the current has reduced beneath a set
level for a user set period.
50/51 Phase Fault

7SR10 Functional Diagram

50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent


protection, each with independent settings for pickup current,
time-multiplier (51), and time-delays. User can select IEC
or ANSI time current characteristics. The IDMT stage has a
user programmable reset characteristic, either DTL or shaped
current ~ time reset characteristic to improve the grading with
electromechanical protection.
50G/51G/50N/51N/50SEF Earth Fault/Sensitive Earth Fault
Two earth fault measurement modes are available. One mode
directly measures the earth current from an independent CT or
the residual connection of the 3 line CTs.
This input can be ordered as earth fault or sensitive earth fault
(50G/51G/50SEF/51SEF)
The second mode derives the earth current internally from the
3 phase CT inputs to give earth fault (50N/51N).

Fig 1. Four Pole Overcurrrent Relay

Description of Functionality
46BC Phase Unbalance/Broken Conductor
Element has settings for pickup level and DTL delay. With the
circuit breaker closed, if the NPS: PPS current ratio is above setting
this could be due to a broken conductor.
46NPS Negative Phase Sequence Overcurrent
Each element has user settings for pickup level and IDMTL or DTL
delay, the element operates if NPS current exceeds setting and
delay. NPS current elements can be used to detect unbalances on
the system or remote earth faults when a delta-star transformer is
in circuit.

50 INST/DTL and 51 IDMTL/DTL elements provide overcurrent


protection, each with independent settings for pickup current,
time-multiplier (51) and time-delays. User can select IEC
or ANSI time current characteristics. The IDMT stage has a
user programmable reset characteristic either DTL or shaped
current ~ time reset characteristic to improve grading with
electromechanical protection.
50BF Circuit Breaker Fail
The circuit breaker fail function may be triggered from an internal
trip signal or from a binary input. Line currents and earth currents
are monitored following a trip signal and an output is issued if any
current is still detected above the setting after a specified time
interval. Alternatively, if the trip is from a mechanical protection
the circuit breaker position can be used to determine a failure.
A second time delay is available to enable another stage to be
utilized if required. An input is also available to bypass the time
delays when the circuit breaker is known to be faulty.

49 Thermal Overload
The thermal algorithm calculates the thermal states from the
measured currents and can be applied to lines, cables and
transformers. Alarm outputs are given for thermal overload and
thermal capacity.

Programmable Logic
The user can map binary inputs, protection elements, LEDs and
binary outputs together in a logical scheme.
Up to 4 logic equations can be defined using standard logic
functions e.g. Timers, AND/OR gates, Inverters and Counters to
provide the user required functionality.
Each logic equation output can be used for alarm & indication
and/or tripping.
Virtual Inputs/Outputs
There are 8 virtual inputs/outputs to provide internal logical states
to assist in the application of the functions. Each virtual I/O can be
assigned in the same way as a physical I/O.
Circuit Breaker Maintenance
Two circuit breaker operations counters are provided to assist with
maintenance scheduling. The maintenance counter records the
overall number of operations and the delta counter records the
number of operations since the last reset.

Fig 2. IEC Overcurrent Curves

An I2t summation counter provides a measure of the contact


wear indicating the total energy interrupted by the circuit breaker
contacts.
Each counter has a user set target operations count which, when
reached, can be mapped to raise alarms/binary outputs. A CB Trip
Time meter is also available, which measures the time between
the trip or open command being issued and the auxiliary contacts
changing state.
Control Mode
The relay has a control menu with access to commonly used
command operations. Access to the control commands is
restricted by a 4 character control function password. Each
command requires a select then execute operation, if the execute
operation is not performed within a time window the command
is aborted. The control mode supports the CB Operation control
function only.
CB Trip/Close
The circuit breaker (CB) control function is used to manually open
and close the CB when it is connected to the power system. Two
dedicated push buttons are provided on the HMI to execute the
CB manual close and open operations.

Fig 3. ANSI Overcurrent Curves

74T/CCS Trip and Close Circuit Supervision

Data Acquisition Via Communication Interface


Sequence of Event Records

The trip or close circuit(s) can be monitored via binary inputs. Trip
circuit failure raises an HMI alarm and output(s).

Up to 1000 events are stored and time tagged to 1 ms resolution.

81HBL2 Inrush Restraint

Fault Records

Where second harmonic current is detected (i.e. during


transformer energisation) user selectable elements can be
blocked and an alarm given.

The last 15 fault records are displayed on the relay fascia and are
also available through the communication interface with time and
date of trip, measured quantities, and type of fault.

Waveform Recorder
The waveform recorder stores analogue data for all poles and the
states of protection functions, binary inputs, LEDs, and binary
outputs with user settable pre and post trigger data. A record can
be triggered from protection function, binary input or via data
communications. 15 records of 1 second duration are stored.
Demand Metering
A rolling record of demand over the last 24 hour is stored. The
demand is averaged over a user selectable period of time. A
rolling record of such demand average is stored and provides the
demand history. A typical application is to record 15 min averages
for the last 7 days.

Construction
The relay is housed in a non draw-out case 4U high size E4 case.
The rear connection comprises of user friendly pluggable type
terminals for wire connections for BI, BO, Communication, and
Power Supply.
The CT terminals are suitable for ring type lug connection to
provide a secure and reliable termination.

Real Time Clock


The time and date can be set and are maintained while the
relay is de-energised by a back up storage capacitor. The time
can be synchronized from a binary input pulse or the data
communication channel.
Language Editor
The Language editor software gives the user the ability to
customize the text displayed in the relays, Menu structure and
instrumentation views. The tool allows a language file to be
created and transferred to the relay also containing Western
European characters.
The data acquisition via communication interface can be done by
Reydisp Evolution.

Serial Communications
The relay offers a USB serial port as standard on the front of all
units. All of the relays functions can be set on a PC using Reydisp
Evolution via the USB port. The connection is made with a USB
cable and operates with a plug and play connection, so no presetting of the relay is required.
The front port can be switched off or set to use either the DNP3.0,
MODBUS-RTU, IEC60870-5-103 and ASCII protocols for testing
purposes.
A rear RS485 electrical connection is optionally available on the
relay for system interface connections. An internal terminating
resistor is provided, which can be connected into the circuit by
adding a wire loop between the relevant terminals.

Fig 4. Typical RS485 connection

The rear RS485 can be user selected to be OFF,


IEC60870-5-103, MODBUS RTU or DNP3.0 protocol.

Fig 5. 7SR10 Rear Terminal Diagram


5

User Interface

Technical Data
For full technical data, refer to the Technical Specification Section
of the User Manual.
Technical Data Overview

Fig 6. User Interface

The operator interface is designed to provide a user friendly


method of controlling, viewing menus, entering settings, and
retrieving data from the relay. Five buttons are provided for
navigation around the menu structure.

Product Family
(Auxiliary powered)

Non Directional, Overcurrent and Earth Fault


Protection Relay

Case and LEDs

Non Draw-out Polycarbonate case (E4 standard,


Non Draw-out design), 10 LEDs

Measuring Inputs
(Current)

1 A/5 A, 50/60 Hz

Auxiliary Voltage

60 - 240 V AC/DC
24 - 60 V DC

Communication

Default front communication port


Back port: RS485 (optional IEC 60870-5-103 or
Modbus RTU or DNP 3.0)

Protection Functions

50, 50G/N, 51, 51G/N, 50BF, 50SEF, 51SEF, 49,


46BC, 46NPS

Supervision and
control functions

74 T/CCS, 86, 81HBL2 (inrush restraint), 51c


(Cold load pickup)

Binary Input and


Binary Output

3 BI or 6 BI
3 BO or 6 BO, (2 changeover contact)
Threshold voltage
- 88 V AC/DC or 44 V AC/DC available with
60 V - 240 V AC/DC power supply version
- 19 V DC with 24 V - 60 V DC power supply version

Overvoltage

Category III

Pollution Degree

LCD
A 4 line by 20 character liquid crystal display with power save
operation indicates the relay identifier, settings, instrumentation,
fault data, and control commands. Up to 6 user programmable
general alarms can be configured to display your own indications
on the LCD.
LEDs
A green steadily illuminated LED indicates the Protection Healthy
condition. 9 users programmable LEDs are available eliminating
the need for expensive panel mounted pilot lights and associated
wiring. Each LED is tri- color (red, green, yellow) allowing for clear
indication of the associated functions state and has a label for
identification.
Relay Information
The device is identified by the rating label on the side cover of
the housing. The user can also give the device its own identity by
editing the Relay Identifier displayed on the LCD.

Mechanical Specifications
Design

Flush mounting, Non Draw-out Polycarbonate


moulded case

Enclosure

IP 54 (front panel)
IP 20 Protection for terminals (rear side)
Depth is 199 mm

Weight

1.6 kgs (appx)

Terminal Blocks
Current Inputs

12 position (Terminal X5), M4 Screw-type Barrier


Terminal block suitable for 2.5 mm2/ 4 mm2 cable

Auxiliary Supply

3 position (Terminal X3), M3 screw-type plug-in


terminals suitable for 2.5 mm2 cable

Rear Communication
Port

4 position (Terminal X2), M2 screw-type plug-in


terminals suitable for 1.5 mm2 cable

Front Communication
Port

USB, Type B

Binary Input

6 or 12 position (Terminal X1),


M3 screw-type plug-in terminals suitable for
2.5 mm2 cable

Binary Output

8 or 14 position (Terminal X4),


M3 screw-type plug-in terminals suitable for
2.5 mm2 cable

Binary Outputs

Inputs and Outputs


Current Inputs
Quantity

3 x Phase & 1 x Earth

Rated Current In

1 A/5 A

Measuring Range

80*In
8*In (SEF)

Instrumentation

1 % (typical)
( 0.1xIn to 3xIn)
> 3xIn to 80xIn ( 3%)

Frequency
Thermal Withstand:
Continuous
10 seconds
1 Second
Burden @ In

50 Hz (Range: 47 Hz to 52 Hz)
60 Hz (Range: 57 Hz to 62 Hz)
4 x In
30 In
100 A (1 A) 350 A (5 A)
0.3 VA per phase and earth for
both 1 A and 5 A

Auxiliary Supply
Rated Voltage

60 V - 240 V AC/DC
Tolerance - 20% to +10%

Allowable super imposed AC


component

15% of DC voltage

Typical Power consumption (DC)

<7 W

Typical Power consumption (AC)

<7 VA 0.5 PF

Max Interruption time


(Collapse to Zero)

100 ms (110 V DC)


1000 ms (230 V AC)

Number

3 or 6
(2 change over contacts)

Operating Voltage

Voltage Free

Operating Mode

User selectable - Self or Hand/


Electrical Reset or pulsed

Operating Time from energizing


Binary Input

<20 ms

Making Capacity:
Carry continuously
Make and carry
(L/R 40 ms and V 300 V)

5 A AC or DC
20 A AC or DC for 0.5 s
30 A AC or DC for 0.2 s

Breaking Capacity
( 5 A and 300 V):
AC Resistive
AC Inductive
DC Resistive
DC Inductive

1250 VA
250 VA at p.f. 0.4
75 W
30 W at L/R 40 ms
50 W at L/R 10 ms

Rear Communication Port


Quantity

1 No. (Optional)

Electrical Connection

RS485, 2 wire electrical

Protocol Support

MODBUS RTU,
IEC 60870-5-103,
DNP 3.0

Rate

Data Transfer rate:


2400 - 38400 bps

Front Communication Port

Auxiliary Supply
Rated Voltage

24 V - 60 V DC
Tolerance - 20% to +10%

Allowable super imposed AC


component

15% of DC voltage

Typical Power consumption (DC)

<7 W

Max Interruption time


(Collapse to Zero)

20 ms (24 V DC)

Quantity

1 No.

Electrical Connection

USB, Type B

Data Storage
Fault Record

15

Waveform Record

15 Rec x 1 Sec
7 Rec x 2 Sec
3 Rec x 5 Sec
1 Rec x 15 Sec
Pre trigger 1090%

Events

1000 events (1 ms Resolution)

Binary Inputs
Number
Operating Voltage

Maximum DC current for operation


60 V - 240 V AC/DC
24 V - 60 V DC

3 or 6
88 V
AC/DC *

Range 60 V - 240 V AC/DC

19 V DC

24 V - 60 V DC

44 V
AC/DC *

60 V - 240 V AC/DC

1.5 mA
3.0 mA

Pick Up Delay

User selectable 0 to 14,400,000 ms


(up to 4 hours)

Drop Off Delay

User selectable 0 to 14,400,000 ms


(up to 4 hours)

* Available in selected variants only.


For AC operation the BI pick-up delay should be set to 0 ms and the dropoff delay to 20 ms.
7

Mechanical Tests

Climatic Environmental Tests

Test

Standard

Temperature

Vibration

IEC 60255-21-1
Response and Endurance, Class I

IEC 60068-2-1/ IEC 60068-2-2

Shock and Bump

IEC 60255-21-2
Shock response and withstand Class I
Bump, Class I

Degree of Protection

-100C to + 600C

Storage Range

-250C to + 700C

IEC 60529
IP 54 front
IP 20 back

Humidity

Seismic

IEC 60255-21-3, Class I

IEC 60068-2-30/IEC 60068-2-78

Contact

IEC 60255-1 (Ref: Std IEC 61810-1)

Electrical Tests
Test

Standard

Insulation Resistance

IEC 60255-5, IEC 60255-27,


500 V DC, >100M Ohms

Impulse Voltage Withstand

IEC 60255-5, IEC 60255-27


5 kV, 5 +ve, -ve pulses

Hi Voltage (Dielectric) Voltage

IEC 60255-5, IEC 60255-27


2 kV@1 min

High Frequency Disturbance

IEC 60255-26

Electrostatic Discharge

IEC 60255-26

Electrical Fast Transient or Burst*

IEC 60255-26, Zone A

Surge Immunity *

IEC 60255-26, Zone A

Radiated Immunity

IEC 60255-26

Conducted Radio Frequency


Interference

IEC 60255-26

Power Frequency Magnetic Field

Damp heat test, Cyclic

6 days at 400C and 93% relative


humidity

Damp heat test, Steady State

4 days at 95% RH, +400C

Maximum Altitude of Operation

Upto 2000 m

Performance
46 Negative Phase Sequence Overcurrent
Number of Elements

DT & IT

DT Setting Range Is

0.05, 0.104.0 x In

DT Operate Level

100% Is, 5% or 1%xIn

DT Delay Setting td

0.00, 0.0120, 20.5100,


1011000, 101010000, 10100
14400 s

DT Basic Operate Time


0 to 2x Is
0 to 5x Is

40 ms 10 ms
30 ms 10 ms

DT Operate time following delay

Tbasic +td, 1% or 10 ms

IT Char Setting

IEC NI, VI, EI, LTI ANSI MI, VI, EI & DTL

IEC 60255-26

IT Setting Range

0.05..2.5

Conducted Emissions

IEC 60255-26

Tm Time Multiplier

0.025, 0.051.6, 1.7 5, 6 100

Radiated Emissions

IEC 60255-26

Char Operate Level

105% Is, 4% or 1%In

Thermal & Burden

IEC 60255-1 and IEC 60255-27

Overshoot Time

< 40 ms

Functional

IEC 60255-3

Inhibited by

Binary or Virtual Input

* Note: 45 ms DTL pick-up delay applied to binary inputs

Operating Temperature

49 Thermal Overload

50 BF Circuit Breaker Fail

Operate levels

Operate and Alarm

Setting Range Is

0.10, 0.113.0 x In

Operate Level

100% Is, 5% or 1%xIn

Time Constant Setting

1, 1.51000 min

Operate time
5% absolute or 100 ms where
Ip = prior current
Alarm Level

Disabled, 50, 51100%

Inhibited by

Binary or Virtual Input

50 Instantaneous & DTL OC&EF


Operation

Non directional

Elements

Phase, Derived Earth, Measured Earth

Setting Range Is (50SEF)

0.005.... 5 x In

Time Delay

0.0014400 s

Operate Level Iop

100% Is, 5% or 1%xIn

Reset level

95 % Iop

Operate Time:
50, 50G
50N

0 to 2x Is 35 ms, 10 ms,
0 to 5x Is 25 ms, 10 ms
0 to 2x Is 40 ms, 10 ms,
0 to 5x Is 30 ms, 10 ms

Operation

Current check - Phase and Measured


Earth with independent settings
Mechanical Trip
CB Faulty Monitor

Setting Range Is

0.05, 0.0552.0 x In

2 Stage Time Delays

Timer 1 2060000 ms
Timer 2 2060000 ms

Operate Level

100% Is, 5% or 1%x In

Disengaging time

< 20 ms

Operate time following delay

Tcbf 1% or 2 ms

Triggered by

Any function mapped as trip contact

Inhibited by

Binary/Virtual Input

Timer By pass

Yes, 50BF CB Faulty Input

74 T/CCS Trip/Close Circuit Supervision


Number of supervisable circuits

3 x Trip and 3 x Close

Number of BIs Required

1 or 2 per function

Note: Use the correct threshold voltages for BI when using TCS with 2 BI.

Control Functions
CB

Trip/Close

EF

IN/OUT

Operate time following delay

Tbasic +td, 1% or 10 ms

SEF

IN/OUT

Inhibited by

Binary or Virtual Input Inrush detector

Relay Mode

Local/Remote/Local or Remote

Reset

LEDs & O/Ps (Test/Reset key)

51 Time Delayed OC&EF


Operation

Non directional

Elements

Phase, Derived Earth, Measured Earth

Characteristic

IEC NI, VI, EI, LTI ANSI MI, VI, EI & DTL

Setting Range Is (51/51G)

0.05, 0.064 x In

Setting Range Is (51SEF)

0.005,...0.5 x In

Time Multiplier

0.01, 0.025, 1.6, 1.7 5, 6 100

Time Delay

0, 0.01 20 s

Operate Level

105% Is, 4% or 1%x In

CB Maintenance
Trip Counter

Total & Delta


010000

I2t Alarm

10100000

Minimum Operate Time


IEC

ANSI
5% absolute or 40ms
for TMS setting (0.01 to 0.24)
5% absolute or 30ms
for TMS setting (0.25 to 100)
Follower Delay

0 - 20 s

Reset

ANSI decaying, 0 60 s

Inhibited by

Binary or Virtual Input


Inrush detector
9

Case Dimensions

Fig 7. Front View

Fig 8. Rear View

Fig 9. Panel cut-out view

Fig 10. Side View

10

7SR10 Terminal/Wiring Diagram

Fig 11. Terminal/Wiring Diagram View (Extended Version)

Fig 12. Terminal/Wiring Diagram View (Basic Version)

Ordering Information
Use the following MLFB numbering series to order the 7SR10 overcurrent and earth fault relay.
7SR10 - Non Directional, E4 Non Draw-out, Polycarbonate moulded case, 4 CT, 10 LEDs, 1 A/5 A, 50 Hz/60 Hz
MLFB

Power Supply

Binary Input/
Binary Output

BI Operation

Binary Input

SEF

Communication Port

Breaker
Control
(Trip/Close)

7SR1002-1HA10-1CA0

60 V - 240 V AC/DC

3/3

DC only

88 V

USB (Front)

7SR1002-1GA10-1CA0

60 V - 240 V AC/DC

3/3

DC only

19 V

USB (Front)

7SR1003-1HA20-1CA0

60 V - 240 V AC/DC

6/6

DC only

88 V

USB (Front) + RS485 (Rear)

7SR1003-1GA20-1CA0

60 V - 240 V AC/DC

6/6

AC/DC BI

19 V

USB (Front) + RS485 (Rear)

7SR1002-1IA10-2CA0

60 V - 240 V AC/DC

3/3

AC/DC BI

44 V

USB (Front)

7SR1002-1KA10-2CA0

60 V - 240 V AC/DC

3/3

AC/DC BI

88 V

USB (Front)

7SR1002-1JA10-2CA0

24 V - 60 V DC

3/3

AC/DC BI

19 V

USB (Front)

7SR1003-1KA20-2CA0

60 V - 240 V AC/DC

6/6

AC/DC BI

88 V

USB (Front) + RS485 (Rear)

7SR1003-1IA20-2CA0

60 V - 240 V AC/DC

6/6

AC/DC BI

44 V

USB (Front) + RS485 (Rear)

7SR1003-1JA20-2CA0

24 V - 60 V DC

6/6

AC/DC BI

19 V

USB (Front) + RS485 (Rear)

7SR1003-2IA20-2CA0 *

60 V - 240 V AC/DC

6/6

AC/DC BI

44 V

USB (Front) + RS485 (Rear)

* Will be available for sales soon and currently not available.


11

Siemens Limited
Energy Managment
Energy Automation
Plot No. 6A, Sector 18
Maruti Industrial Area
Huda, Gurgaon 122015, India
Tel.: +91 124 3836000, 3837362
Fax: +91 124 3836261

Siemens Limited
Energy Managment
Energy Automation Works
Plot No. L-6, Verna Industrial Area
Panaji Margao Road
Verna 403722, Goa
Tel.: +91 832 3993000
Fax:+91 832 6723299

C53000-X7076-C002-4
EM-EA-7SR10-001

For any technical queries, please contact our customer support center
Siemens Limited
Energy Automation Works
Plot No. L-6, Verna Industrial Area
Panaji Margao Road
Verna 403722, Goa
India
Phone: +91 832 6723151

+91 832 6723165
Fax: +91 832 6723299
E-mail: EAsupport.in@siemens.com
Subject to change without notice, Printed in India.

You might also like