Jumo Controleri
Jumo Controleri
Jumo Controleri
Type 703575/2...
Type 703575/1...
Type 703570/0...
B 703570
Operating Manual
2013-10-01/00370043
Please read this operating manual before commissioning the instrument. Keep the manual in a
place which is accessible to all users at all times.
Your comments are appreciated and may help us in improving this manual.
All necessary settings are described in this operating manual. Manipulations not described in the
manual or expressly forbidden will jeopardize your warranty rights. Please contact the nearest subsidiary or the head office, should you encounter problems.
When accessing the inner parts of the unit and returning modules, assemblies or components,
please observe the regulations accordings to EN 61340-5-1 and EN 61340-5-2 Protection of
electrostatic sensitive devices. Only use ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD.
ESD=Electro Static Discharge
Contents
1
Introduction
1.1
Description .................................................................................................... 7
1.2
1.3
1.3.1
1.3.2
1.3.3
8
8
8
8
2.1
2.2
Accessories ................................................................................................ 10
Installation
3.1
3.2
3.2.1
3.2.2
3.2.3
Dimensions .................................................................................................
Type 703570/0... ...........................................................................................
Type 703575/1... ..........................................................................................
Type 703575/2... ..........................................................................................
3.3
3.4
3.5
3.6
Electrical connection
4.1
11
11
11
12
12
15
Isolation ....................................................................................................... 21
Contents
5
Operation
23
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
Parameter level
31
Configuration level 1
33
7.1
Controller .................................................................................................... 35
7.2
7.3
Inputs ........................................................................................................... 40
7.4
Outputs ........................................................................................................ 45
7.5
7.6
7.7
Display ......................................................................................................... 53
7.8
7.9
Interface ...................................................................................................... 58
Optimisation
8.1
Self-optimisation ........................................................................................ 59
8.2
8.3
59
Contents
9
Retrofitting of cards
63
10
Interfaces
67
11
Accessories
69
12
Appendix
71
79
79
79
79
79
79
13
81
Index
Contents
1 Introduction
1.1 Description
This series of universal, freely configurable process controllers is available in
the formats 96mm x 96mm and 96mm x 48mm (portrait and landscape).
The instruments feature two 4-digit 7-segment displays, five or eight LEDs for
indicating the switching status and operating modes, an 8-digit matrix display,
as well as six keys for operation and configuration.
The controller slots can be assigned flexibly by the user, according to the
block structure.
Additional functions include self-optimisation, parameter set switching, and up
to eight limit comparators.
Linearisations for conventional transducers are held in the memory; a customized linearisation table can be programmed.
The process controller can be adapted to a variety of tasks with the aid of a
maths module.
The instruments can be integrated into a data network via a serial interface, or
can be expanded through an external relay module.
A setup program is available for easy configuration from a PC.
The electrical connection is at the rear by screw terminals.
Outputs:
- Relay
- Solid-state relay
- Logic output 5V
- Logic output 22V
- Analogue output
- Supply for
2-wire transmitter
Type 703570 only
Analogue inputs:
- Resistance thermometer
- Thermocouples
- Standard signals
- Potentiometer
1 Introduction
1.3 Typographical conventions
1.3.1 Warning signs
E
1.3.2 Note signs
Danger
Warning
Warning
Note
Reference
H Action
1.3.3 Presentation
E+I
CONFIG 1
(2)
(3)
(4)
(5)
(6)
(7)
0 0
0 0 0
(5) Interface
not assigned
RS422/485
PROFIBUS-DP
(no GL approval)
0
1
2
Version:
Standard with factory settings
Customized programming
1
2
3
1 2 3 4
0 0 0 0
1 1 1 1
2 2 2 2
8
9
(7) Approvals
DIN EN 14597*
Germanischer Lloyd (GL)*
DIN EN 14597 and GL*
DIN EN 14597 and UL*
GL and UL*
DIN EN 14597, GL and UL*
Delivery package:
2
3
4
5
- seal
2
3
4
5
2
3
4
5
2
3
4
5
2
3
4
5
0 0
0 3
0
0
0
0
0
0
5
6
6
6
6
6
6
2
3
4
5
6
1 2 3 4 5 6
0 0 0 0 0 0
1 1 1 1 1 1
2
3
4
5
0 0
5 4
6 4
- controller
- 2 fixing brackets
6 6 6 6 6 6
7 7 7 - - -
(4) Supply
110 240V AC +10/-15%
48 63Hz
20 30V DC/AC 48 63Hz
2 3
2 5
10
3 Installation
3.1 Location and climatic conditions
The instrument location must conform to the requirements specified under Technical Data. The ambient temperature at the location can be
between -5 and 55 C, at a relative humidity of not more than 95 %.
3.2 Dimensions
3.2.1 Type 703570/0...
Setup plug
11
3 Installation
3.2.2 Type 703575/1...
Setup plug
panel cut-out to
IEC 61554
12
3 Installation
3.3 Edge-to-edge mounting
Minimum spacing of the panel cut-outs
Type
horizontal
without setup plug:
703570/0...
11mm
703575/1... (portrait format)
11mm
703575/2... (landscape format)
30mm
with setup plug:
703570/0...
11mm
703575/1... (portrait format)
11mm
703575/2... (landscape format)
65mm
vertical
30mm
30mm
11mm
65mm
65mm
11mm
13
3 Installation
3.6 Removing the controller chassis
The controller chassis can be removed from the housing for servicing.
h Press the knurled areas together at
top and bottom (left and right with
landscape format) on the front panel
and pull out the controller chassis.
14
When inserting the controller chassis, care must be taken that the lugs
(underneath the knurled areas) snap into position.
4 Electrical connection
4.1 Installation notes
The choice of cable, the installation and the electrical connection of the instrument must meet the requirements of VDE 0100 Regulations on the installation of power circuits with nominal voltages below 1000 V or the appropriate local regulations.
The electrical connection must only be carried out by qualified personnel.
The instrument shall be operated by mains protected with a branch circuitry
overcurrent protection device not more than 20 Amps.
For servicing/repairing a Disconnecting Device shall be provided to disconnect all conductors.
A current-limiting resistor interrupts the supply circuit in the event of a short
circuit. The load circuit has to be fused for the maximum relay current in
order to prevent welding of the output relay contacts in the event of a shortcircuit.
Electromagnetic compatibility conforms to the standards and regulations
specified under Technical data.
Input, output and supply lines should be routed separately, not parallel to
one another.
Arrange sensor and interface cables as twisted and screened cables. Do
not run them close to power cables or components. Earth the screen at one
end at the instrument, to the TE terminal.
Earth the instrument at terminal TE to the earth conductor. This line must
have at least the same cross-section as the supply lines. Earth lines should
be run in a star layout to a common earth point which is connected to the
earth conductor of the supply. Do not loop the earth connections, i. e. do
not run them from one instrument to another.
Do not connect additional loads to the supply terminals of the instrument.
The instrument is not suitable for installation in hazardous areas.
Apart from faulty installation, there is a possibility of interference or damage
to controlled processes due to incorrect settings on the controller (setpoint,
data of parameter and configuration levels, internal adjustments). Safety
devices independent of the controller, such as overpressure valves or temperature limiters/monitors, should always be provided and should be
capable of adjustment only by specialist personnel. Please refer to the appropriate safety regulations in this connection. Since adaptation (self-optimisation) cannot be expected to handle all possible control loops, there is
a
theoretical possibility of unstable parameter settings. The resulting process
value should therefore be monitored for its stability.
The maximum permitted voltage difference between the inputs of the controller and TE is 30 V AC or 50 V DC.
15
4 Electrical connection
4.2 Connection diagrams
4.2.1 Type 703570
V
H
H
1 2 3 4
BE1
7 8
BE2
9 10 11
Thermocouples
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/210V
Current
0/420mA
+
H
16
Analogue input 2
Potentiometer
A
Analogue input 1
When a thermocouple with internal temperature compensation is wired up to the analogue inputs 1, 3 or 4, Pt500, Pt1000 or KTY must not be connected to analogue input 2.
4 Electrical connection
Type 703570
PROFIBUS DP
Output 6
(Slot 6)
-20/0/420mA
-20/0/420mA
-10/0/210V
-10/0/210V
230V/1A
230V/1A
5V(22V)/30mA*
5V(22V)/30mA*
A GND
+5 V
20 mA B
Output 5
(Slot 5)
RS485/ER8
RxD/ RxD/
TxD TxD GND
(+) ()
Interface
RS422
RxD RxD TxD TxD GND
(+) () (+) ()
1 2 3 4 5
10 11 12
Thermocouples
Resistance
thermometer
(2-wire)
230V/3A
1 2 3
6 7 8
* Supply for
2-wire transmitter (22V)
The output must be configured accordingly.
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/210V
+
Current
0/420mA
Current
0/420mA
+
Potentiometer
Potentiometer
E
Voltage
0/210V
10 11 12
Thermocouples
Resistance
thermometer
(3-wire)
230V/3A
Analogue input 4
(option)
Analogue input 3
(option)
17
4 Electrical connection
Type 703570
Output 1
(Slot 1)
-20/0/420mA
i
-10/0/210V
u
230V/1A
1 2 3
L1 N
BE3
AC
TE
110240V
BE4
AC/DC
2030V
Contact protection circuit (relays):
56/15nF between common-make/common-break
18
Mains supply
4 Electrical connection
4.2.2 Type 703575 (portrait and landscape format)
V
H
H
H
PROFIBUS-DP:
v Interface Description B 703560.2.3
19
4 Electrical connection
Type 703575
* Supply for
2-wire transmitter
The output must be configured accordingly.
v Section 7.4 Outputs
Contact protection circuit (relays):
56/15nF between common-make/common-break
1 2 3 4
BE1
7 8
9 10 11
BE2
Thermocouples
Resistance
thermometer
(3-wire)
Resistance
thermometer
(2-wire)
Voltage
0/2 10V
Current
0/4 20mA
+
Analogue input 2
Potentiometer
A
Analogue input 1
H
20
4 Electrical connection
4.3 Isolation
For Type 703570 and Type 703575
21
4 Electrical connection
22
5 Operation
5.1 Displays and controls
(4)
(1)
(5)
(2)
(3)
(6)
(1) configurable
7-segment display (display 1)
4 digits, red
Type
Height
703570
13mm
703575
10mm
factory setting: process value
(2) configurable
7-segment display (display 2)
4 digits, green
Type
Height
703570
10mm
703575
7mm
factory setting: setpoint
(3) configurable dot-matrix display
(display 3)
8 digits, green
factory setting: output
(bar graph)
(6) Keys
see below
23
5 Operation
5.2 Operating modes and states
Operating mode/
state
Display
Normal display
Notes
The displays present the values according to the
display configuration.
v Section 5.7 Display switching
factory setting:
- process value
- setpoint
- output (bar graph)
Ramp and
profile program
function
Manual mode
Self-optimisation
Self-optimisation is running.
v Section 8.1 Self-optimisation
Alarm messages
- LED is off;
24
- LED is on
v Section 12.2 Alarm messages and display priorities in the normal display
5 Operation
5.3 Principle of operation
Normal display
Initial status
Profile program
function
Operating level
This level can be used to program setpoints and indicate process variables.
Parameter
level
Configuration
level 1
Configuration
level 2
Service
Time-out
Code request
= factory setting
25
5 Operation
Levels and
menus
Each level is divided into menus, thus creating a tree structure which has a selection or a value input at the end of each branch.
Shift decimal
point
26
5 Operation
Code and
time input
Selection
Setpoint
switching
If setpoint switching is programmed, the active setpoint is altered in the normal display.
27
5 Operation
Relevant
settings
I - open actuator
D - close actuator
OUTPUT
I
D
100.
OPERATNG
The levels can also be accessed from the manual mode. The manual mode
can be inhibited.
v Section 7.1 Controller
Relevant
settings
28
5 Operation
5.7 Display switching
Two display configurations can be provided that determine the visualisation of
values and process variables on the 7-segment displays and the dot-matrix
display.
h Switch display over with E
or automatic changeover after an adjustable interval
Display switching can be deactivated.
Configuration 2
Configuration 1
Example
Relevant
settings
Display 2: setpoint
Display 3: output
29
5 Operation
5.8 Operating level
General
Four setpoints can be indicated and altered at the operating level, in addition
different process variables can be displayed.
Value/selection
Setpoints
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
SETPTS
W1
W2
W3
W4
0.
0.
0.
0.
Process variables
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Mathematics 1
Mathematics 2
Output
PROCESS
ANALOG 1
ANALOG 2
ANALOG 3
ANALOG 4
MATHS 1
MATHS 2
OUTPUT
0.
0.
0.
0.
0.
0.
0.
30
Description
Value input
within the defined setpoint limits
Value display
6 Parameter level
General
h pressing P twice (3x P with activated program function) in normal display or in manual mode.
Access code
Select
parameter set
PARAMETR PARASET1
Parameters
Display
Value range
Controller
structure
STR
STR
Meaning
XP1
XP2
0 9999 digit
0 9999 digit
0 digit
0 digit
Switching cyle
time
TV1
TV2
TN1
TN2
CY1
CY2
0 9999 sec
0 9999 sec
0 9999 sec
0 9999 sec
0 9999 sec
0 9999 sec
80 sec
80 sec
350 sec
350 sec
20 sec
20 sec
Proportional
band
Derivative time
Contact spacing
XSH
0 999 digit
0 digit
Switching
differential
XD1
XD2
0 999 digit
0 999 digit
1 digit
1 digit
Stroke time
TT
5 3000 sec
60 sec
Working point
Y0
-100 to +100% 0%
Reset time
1
2
factoryset
P, I, PD, PI, PID PID
P, I, PD, PI, PID PID
31
6 Parameter level
PARAMETR PARASET1
Output limiting
Minimum relay
ON time
Y1
Y2
TK1
TK2
0 100%
-100 to +100 %
0 60sec
0 60sec
100%
-100%
0sec
0sec
Active
parameter set
32
7 Configuration level 1
General
Access the
level by ...
Access code
Overview
r Controller
v Page 35
r controller type
control direction
controller inputs
r process value
external setpoint
external setpoint
with correction
stroke retransmission
additive disturbance
multiplying disturbance
setpoint limits
r setpoint start
setpoint end
manual output
self-optimisation
output 1+ 2 for selfoptimisation
dead band
fuzzy control 1
fuzzy control 2
r Limit comparators
v Page 37
r limit comparator 18
r function
action
switching differential
limit value
function on over/
underrange
switch-on delay
pulse function
LK inputs
r limit comparator PV
= press E !
33
7 Configuration level 1
r Inputs
v Page 40
r analogue input 1 4
r transducer
linearisation
measurement correction
constant cold-junction
temperature
external cold-junction
temperature
display start
display end
range start
range end
filter time constant
customized recalibration
r start value
end value
supply frequency
unit
r Outputs
v Page 45
r output 1 6
r Ramp and
program function
v Page 46
r function
ramp slope
unit of slope
r Maths/logic
v Page 48
r mathematics 1+2
r function
output signal
zero point
end value
output signal on
under/overrange
r function
variable a
variable b
range start
range end
linearisation
logic 1+2
r Display
v Page 53
r configuration 1+2
r Logic function
v Page 56
r logic input 1 8
limit comparator 1 8
logic output 1+2
r Interface
v Page 58
r type of protocol
data format
time-out
automatic display
switching
34
r baud rate
parity
stop bit
instrument address
minimum response time
= press E !
r display 13
r display value
decimal point
7 Configuration level 1
7.1 Controller
The following are set here: controller type and input variables of the controller,
setpoint limits, conditions for manual mode, the presettings for self-optimisation and the fuzzy logic.
CONFIG
Controller type
Control direction
1 CONTRL.
Parameters
Value/selection Description
CTR.TYPE
1-SETPT
2-SETPT
MODULTNG
ACTUATNG
DIRECTN.
PROP.
single-setpoint controller
double-setpoint controller
modulating controller
proportional controller with integral
actuator driver
proportional controller
DIRECT
INVERSE
Direct
Inverse
inverse:
The controller output Y is > 0 when
the process value is smaller than the
setpoint (e. g. heating).
direct:
The controller output Y is > 0 when
the process value is larger than the
setpoint (e. g. cooling).
INPUTS?
Inputs of the
controller
PV
process value
EXTSET?
external setpoint
EXTCORR
external setpoint
with correction
Y RETRM
stroke
retransmission
ADD DIST
additive disturbance
MUL DIST
multiplying
disturbance
NO FUNCT
ANALOG 1
ANALOG 2
ANALOG 3
ANALOG 4
MATHS 1
MATHS 2
no function*
analogue input 1**
analogue input 2
analogue input 3
analogue input 4
Mathematics 1
Mathematics 2
Defines from which analogue inputs
or maths functions the controller
receives the signals. Stroke retransmission has to be configured in the
case of a proportional controller with
integral actuator driver!
External setpoint with correction:
External setpoint + setpoint 1 =
present setpoint
The external setpoint can be corrected upwards or downwards from
the keys (setpoint 1). The present
setpoint appears on the (LED) display.
* factory-set for all, except process
value
** factory-set for process value
35
7 Configuration level 1
CONFIG
1 CONTRL.
Parameters
Setpoint limits
setpoint start
setpoint end
WLIMITS
STARTVAL
END VAL
Value/selection Description
0.
400.
-19990 to +9999
-1999400 to +9999
A
MANUAL
101.
Manual output
Manual mode
MAN.MODE
ENABLED
INHIBTD
enabled
inhibited
Self-optimisation
TUNE
ENABLED
INHIBTD
enabled
inhibited
Output 1 for
self-optimisation
TUNEOUT1
RELAY
Relay
solid-state relay and logic output
SSRELAY
ANOUTPUT analogue output
-100100
101 = last output
Defines the output after changing
over to manual mode.
TUNEOUT2
RELAY
Relay
SSRELAY
solid-state relay and logic output
ANOUTPUT analogue output
type of controller output 2 on selfoptimisation
Dead band
DEADBAND
0.
0999digit
serves to minimise the output
movement within the dead band;
e. g. with noisy signals.
FC1
0.
0100
0 = fuzzy control off
Intensity of the fuzzy signal added to
the controller output to improve the
control quality.
Fuzzy control 2
FC2
30.
030100
Influences the controller parameters
during activated fuzzy module to
improve the control quality.
36
7 Configuration level 1
7.2 Limit comparators
Limit comparators (limit monitors, limit contacts) can be used to monitor an input variable (limit comparator process value) against a fixed limit value or another variable (limit comparator setpoint). When a limit is exceeded, a signal can
be output or an internal controller function initiated.
Limit
comparator
functions
lk4
On
lk7
On
lk2
lk3
On
On
lk5
lk6
On
On
lk1 lk6:
Monitoring referred to the
limit comparator setpoint.
lk7/lk8:
Monitoring referred to a fixed
value AL
lk8
On
CONFIG
Parameters
1 LIMITC
Value/selection Description
...
CONFIG
Function
1 LIMITC LIMITC1
Parameters
Value/selection Description
FUNCTION
NO FUNCT
LK1
...
LK8
no function
function lk1
...
function lk8
37
7 Configuration level 1
CONFIG
1 LIMITC LIMITC1
Parameters
Value/selection Description
Action
ACTION
ABSOLUTE absolute
RELATIVE relative
Switching
differential Xsd
DIFFERTL
1.
019999 digit
Limit value AL
LIMIT
0.
Function on
over/underrange
RANGEFCT
Switch-on delay
DELAY
0.
0 9999sec
Pulse function
PULSEFCT
0.
-10 to +9999s
The limit comparator is automatically reset after an adjustable
interval.
-1= The limit comparator has to be
reset with the E key or the
logic function (all displays off).
Limit comparator
inputs
limit comparator
process value
limit comparator
setpoint
INPUTS
PV
SET
LK
LK
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
analogue input 1*
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)**
ramp end value
control deviation
output
* factory-set for LK process value
** factory-set for LK setpoint
38
7 Configuration level 1
Absolute
At the time of the alteration, the limit comparator acts in accordance with its
function.
Relative
c) Control stabilised
The limit comparator again operates according to its function.
This function also prevents a limit comparator from being triggered during the
start-up phase.
39
7 Configuration level 1
7.3 Inputs
The analogue inputs are configured here.
CONFIG
1 INPUTS
Parameters
Value/selection Description
Analogue input 1
ANALOG
...
...
Analogue input 4
ANALOG
Supply frequency
PWRFREQ
50
60
Unit
UNIT
DEGREE
DEGREE
4
HZ
HZ
50Hz
60 Hz
C C
F F
CONFIG
Transducer
1 INPUTS ANALOG
Parameters
Value/selection Description
PROBE
NO FUNCT no function*
resistance thermometer**
RTD
TC INTRN thermocouple
(internal cold junction)
TC EXTRN thermocouple
(external cold junction)
TC CONST thermocouple
(constant cold junction)
RESTRANS potentiometer
0 - 20mA
0 - 1 V
0 -100mV
-1 - 1V
+/-100mV
4 - 20mA
0 - 10V
2 - 10V
+/-10V
020mA
01V
0100mV
-1to +1V
-100to +100mV
420mA
010V
210V
-10Vto +10V
* factory-set on analogue input 2, 3, 4
** factory-set on analogue input 1
40
7 Configuration level 1
CONFIG
Linearisation
1 INPUTS ANALOG
Parameters
Value/selection Description
LINTAB
LINEAR
PT100
PT1000
PT500
PT50
CU50
KTY
PTK9
NI100
TC TPE J
TC TPE E
TC TPE K
TC TPE N
TC TPE T
TC TPE B
TC TPE R
TC TPE S
TC TPE U
TC TPE L
CUST LIN
W5RE W26
W3RE W25
W3RE W26
linear
Pt 100
Pt 1000
Pt 500
Pt 50
Cu 50
KTY21-6 (1k at 25C)*
Pt K9
Ni 100
Fe-Con J
NiCr-Con E
NiCr-Ni K
NiCrSi-NiSi N
Cu-Con T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-Con U
Fe-Con L
customized linearisation
W5Re-W26Re
W3Re-W25Re
W3Re-W26Re
* for other types, see setup
program (extended configuration)
** for customized linearisation up to
20 interpolation points can be
realised (with setup program only).
x = physical measured value
y = displayed value
Measurement
correction
OFFSET
0.
offset
294.7
295.3
+0.3
- 0.3
displayed
value
295.0
295.0
41
7 Configuration level 1
CONFIG
Parameters
Constant
cold-junction
temperature for
thermocouples
CJTEMP
External
cold-junction
temperature for
thermocouples
EXTTEMP
1 INPUTS ANALOG
Value/selection Description
50.
050100 digit
Temperature of the cold-junction
thermostat
ANALOG
...
ANALOG
1 Analogue input 1
...
4 Analogue input 4
Measurement of the cold-junction
temperature with a temperature
probe.
Display start
DSPLSTRT
0.
Display end
DISPLEND
100.
Range start
RNGESTRT
-1999.
Range end
RANGEEND
9999.
0.6
00.6100 sec
To adjust the digital input filter
(0sec = filter off).
At a signal jump, 63% of the changes are registered after 2 x filter time
constant.
If the filter time constant is large:
- high damping of disturbance signals
- slow reaction of process value
indication to PV changes
- low limit-frequency
(2nd order low-pass filter)
42
7 Configuration level 1
CONFIG
1 INPUTS ANALOG
Parameters
Customized
recalibration
Start value
End value
Value/selection Description
RECAL
STARTVAL
ENDVALUE
0.
1.
Customized
recalibration
Procedure
Apply two measurement points ((1), (3)), one after another, to the controller;
they should be as far apart as possible.
At these measurement points, enter the required display value (start value, end
value) in the controller. A reference instrument is most convenient for determining the measured values M1 and M2.
Measurement conditions must remain stable during programming.
Programming
43
7 Configuration level 1
h Enter end value E (4) 1
1. If start value=0 or end value =1 is to be set, then the value must first be altered
using I or D to enable correction.
44
7 Configuration level 1
7.4 Outputs
The outputs are configured here.
CONFIG
1 OUTPUTS
Parameters
Value/selection Description
Output 1
OUTPUT1
...
...
Output 6
OUTPUT6
CONFIG
Function
1 OUTPUTS OUTPUT1
Parameters
Value/selection Description
FUNCTION
NO FUNCT
ANALOG1
...
ANALOG4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
W1
...
W4
CTRLOUT1
CTRLOUT2
VALUE XY
OUT LK1
...
OUT LK8
LOGIN B1
...
LOGIN B8
LOGIC 1
LOGIC 2
MAN.MODE
TRNSMITT
no function*
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint
ramp end value
control deviation
output
setpoint 1
...
setpoint 4
controller output 1**
controller output 2
address value
limit comparator output 1
...
limit comparator output 8
logic input 1
...
logic input 8
logic 1
logic 2
manual mode
supply for 2-wire transmitter
* factory-set on all outputs
except output 1
** factory-set on output 1
SIGNAL
0 - 10 V
2 - 10 V
-10- 10V
0 - 20mV
4 - 20mA
-20-20mA
0 10V
2 10V
-10 to +10V
0 20mA
4 20mA
-20 to +20mA
45
7 Configuration level 1
CONFIG
Parameters
1 OUTPUTS OUTPUT1
Value/selection Description
Zero for
analogue signals
STARTVAL
0.
ENDVALUE
100.
RANGEFCT
0.
0 101*
101 = last output signal
The output produces a defined
signal.
CONFIG
1 RAMP
Parameters
Value/selection Description
Function
FUNCTION
NO FUNCT no function
RAMP
ramp function
PROGRFCT profile program function
Ramp slope
SLOPE
Unit of slope
UNIT
0.
0999
46
7 Configuration level 1
Ramp
function
H
Profile program
function
The program starts at the process value or the program start (adjustable via
the setup program only!). When starting at the process value, the profile is
searched to find a setpoint that corresponds to the process value at the instant of the start. The program sequence starts at this point. If the process
value is outside the profile, a start is made at the first program segment. With
segments that are not required, the segment time must be 0.
Starting the
program
Holding the
program
47
7 Configuration level 1
7.6 Maths and logic module
This menu is shown only with enabled maths and logic module.
CONFIG
Parameters
1 MATHSLOG
Value/selection Description
Mathematics 1
MATHS
Mathematics 2
MATHS
Logic 1
LOGIC
NO FUNCT no function
FORMULA
logic formula (setup program)
Logic 2
LOGIC
NO FUNCT no function
FORMULA
logic formula (setup program)
Configuration of mathematics as
shown in example Maths 1 below.
CONFIG
1 MATHSLOG MATHS
Parameters
Value/selection Description
Function
FUNCTION
NO FUNCT
DIFFERNC
RATIO
HUMIDITY
FORMULA
no function
difference (a-b)
ratio (a/b)
humidity (a;b)
maths formula
(setup program)
Variable a
VAR
ANALOG1
...
ANALOG4
MATHS 1
MATHS 2
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
Variable b
VAR
ANALOG1
ANALOG2
ANALOG3
ANALOG4
MATHS 1
MATHS 2
analogue input 1
analogue input 2
analogue input 3
analogue input 4
mathematics 1
mathematics 2
Range start
RNGESTRT
-1999.
Range end
RANGEEND
9999.
48
7 Configuration level 1
CONFIG
Linearisation
1 MATHSLOG MATHS
Parameters
Value/selection Description
LINTAB
LINEAR
PT100
PT1000
PT500
PT50
CU50
KTY
PTK9
NI100
TC TPE J
TC TPE E
TC TPE K
TC TPE N
TC TPE T
TC TPE B
TC TPE R
TC TPE S
TC TPE U
TC TPE L
CUST LIN
W5RE W26
W3RE W25
W3RE W26
linear
Pt 100
Pt 1000
Pt 500
Pt 50
Cu 50
KTY21-6
Pt K9
Ni 100
Fe-Con J
NiCr-Con E
NiCr-Ni K
NiCrSi-NiSi N
Cu-Con T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-Con U
Fe-Con L
customized linearisation
W5Re-W26Re
W3Re-W25Re
W3Re-W26Re
Ratio control
Humidity
control
49
7 Configuration level 1
Formula input
- The formula character string consists of ASCII-characters and has a maximum length of 70 characters.
- The formula can only be entered in the setup program.
- The formulae can be entered freely according the the usual mathematical
rules.
- Spaces can be inserted in the formula character string without restriction.
No spaces are allowed within function designations, variable names and
constants.
Mathematical
formula
Mathematical sign/function
Note
()
brackets
low
**
exponent (xy)
+, -
sign
*, /
multiplication, division
+, -
addition, subtraction
Variables
50
Variable name
Note
E1
E4
analogue input 1
M1
M2
mathematics 1
mathematics 2
process value
WR
controller setpoint
WE
XW
control deviation
output
W1
W4
YH
output heating
YK
output cooling
ADRA
TEMP
temperature at terminals
T0
sampling time
RXK1
RXK2
controller output 1
controller output 2
analogue input 4
7 Configuration level 1
Variable name
Note
ADRZ
ADRB
LK1
LK8
B1
B8
logic input 1
L1
L2
logic 1
logic 2
HAND
manual mode
logic input 8
Functions
Syntax
Function
SQRT(a)
square root of a
Examples: SQRT(E2)
SQRT(13.5+E3)
MIN (a1, a2 )
MAX (a1, a2 )
LOG(a)
logarithm to base 10
Examples: LOG(1000) (returns the value 3)
LOG(E1/100)
LN(a)
logarithm to base e
Examples: LN(2.71828128) (returns the value 1)
LN(E1/100)
SIN(a)
sine of a
a in degrees (0 360C)
Examples: SIN(90) (returns the value 1)
SIN(E1*360/100)
COS(a)
cosine of a
a in degrees (0 360C)
Examples: COS(180) (returns the value -1)
COS (E1*360/100)
TAN(a)
tangent of a
a in degrees (0 360C)
Examples: TAN(45) (returns the value 1)
TAN(E1*45/100)
ABS(a)
absolute value of a
Examples: ABS(-12) (returns the value 12)
ABS(13.5+E3)
51
7 Configuration level 1
Logic formula
Syntax
Function
EXP(a)
exponential function ea
Examples: XP(1) (returns the value 2.718)
EXP(E1/100)
INT(a)
integer portion of a
Examples: INT(8.3) (returns the value 8)
INT(E1)
FRC(a)
decimal portion of a
Examples: FRC(8.3) (returns the value 0.3)
FRC(E1)
Logic operators
Priority
high
low
Operator
Note
()
brackets
NOT, !
negation
AND, &
AND linkage
XOR, ^
exclusive OR linkage
OR,
OR linkage
Variables
Variable names
Note
RXK1
RXK2
controller output 1
controller output 2
ADRB
Lk1
LK8
B1
B8
logic input 1
logic input 8
HAND
manual mode
Edge recognition
52
Edge
Note
7 Configuration level 1
Constants
Enabling maths
and logic
module
Constant name
Note
TRUE
logic 1
FALSE
logic 0
The maths and logic module can be enabled through a code via the setup program.
v Extras r Enabling extra Codes
7.7 Display
The two display configurations are set here, as well as the time-out during
configuration at the levels.
CONFIG
Parameters
Configuration 1
DSPCONF1
Configuration 2
DSPCONF2
Time-Out
TIMEOUT
Automatic
display switching
SCROLL
Language for
instrument texts
LANGUAGE
1 DISPLAY
Value/selection Description
Configuration of the displays as
shown in the example
Configuration 1 below.
30.
0309999sec
0 = time-out OFF
Interval after which an automatic
return to normal display occurs if no
key is pressed.
0.
-1 09999sec
0 = automatic changeover OFF
-1 = changeover via keypad is not
possible
Interval between the changeover of
the two display configurations.
DEUTSCH
ENGLISH
FRANCAIS
ESPANOL
German
English
French
Spanish
This feature is available from instrument SW version 050.03.01.
53
7 Configuration level 1
Assignment
of the displays
Display 1
Display 2
Display 3
CONFIG
1 DISPLAY DSPCONF1
Parameters
Display 1
Display value
DISPLAY1
DISPLVAL
Decimal point
DECPOINT
Display 2
Display value
DISPLAY2
DISPLVAL
Decimal point
DECPOINT
Value/selection Description
NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL
no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value
XXXX.
XXXX.X.XXX
NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL
no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value
XXXX.
XXXX.X.XXX
54
7 Configuration level 1
CONFIG
1 DISPLAY DSPCONF1
Parameters
Display 3
Display value
DISPLAY3
DISPLVAL
Value/selection Description
NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL
LIMITC
BARG Y
BARG XW
TXTDISPL
no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value
limit comparators (switching states)
bar graph output
bar graph control deviation
text display
switching states of
limit comparators: 8 7 6 5 4 3 2 1
00000000
bar graph output:
1-setpoint ctrl.
0%
100%
and prop. ctrl.
Decimal point
DECPOINT
XXXX.
XXXX.X.XXX
Decimal point
If the value to be displayed can no longer be represented with the programmed decimal place, then the number of decimal places will be automatically reduced. If, subsequently, the measurement becomes smaller then
the number will be increased to the programmed decimal point value.
55
7 Configuration level 1
7.8 Logic functions
Functions are assigned here to the logic signals of the logic inputs, limit
comparators and the logic module.
CONFIG
Parameters
Logic input 1
LOGIN
...
...
Logic input 8
LOGIN
Value/selection Description
B1
B8
LK1
...
1 LOGICFCT
LK8
Logic 1
LOGIC
Logic 2
LOGIC
NO FUNCT
TUNESTRT
TUNESTOP
MAN.MODE
MANINHBT
RAMPSTOP
RAMP OFF
W SWITCH
X SWITCH
P SWITCH
KEYINHBT
LEVINHBT
TXTDISPL
DISPLOFF
no function
start self-optimisation
cancel self-optimisation
changeover to manual mode
manual mode inhibit
ramp stop/profile programm stop
ramp off/profile programm abort
setpoint switching
process value switching
parameter set switching
key inhibit
level inhibit
text display*
all displays off/acknowledgement of
limitcomparators
* A maximum of 10 texts are input
and assigned to the logic functions
in the setup program
The functions are active when the
contact is closed or the switching
status is ON.
All displays off:
- all displays are switched off
- limit comparators are acknowledged
Text display and all displays off:
response according to priority list
Switching
action
The logic functions are activated via the logic inputs (floating contacts (switches/relay contacts)), limit comparators or logic.
56
7 Configuration level 1
Edge-triggered
functions
State-triggered
functions
Combined
logic functions
Example:
The process value is to be selected via
one logic input and the state of one limit
comparator.
This results in the following assignment:
Z1 - logic input 1
Z2 - limit comparator 1
Setpoint switching
Z2
Z1
setpoint 2
analogue input 2
setpoint 3
analogue input 3
analogue input 4
1 = contact closed /ON
setpoint 4
0 = contact open /OFF
If switching between two setpoints or process values only is required, then only one logic function has to be configured.
If more than two logic functions are configured to setpoint switching (process value switching), then only the first two (see list
Control variable - State) are significant.
57
7 Configuration level 1
7.9 Interface
CONFIG
1 INTERFCE
Parameters
Value/selection Description
Protocol type
PROTOCOL
MODBUS
MODINT
MODbus/Jbus
MODbus int
Data format
Baud rate
DATAFMT
BAUDRATE
1200
2400
4800
9600
1920
1200 baud
2400 baud
4800 baud
9600 baud
19200 baud
Parity
PARITY
NONE
ODD
EVEN
ZERO
no parity
odd parity
even parity
zero parity
Stop bit
STOPBIT
1
2
1 stop bit
2 stop bits
Unit address
UNITADDR
0.
01 254
Minimum
response time
MIN
0.
0500msec
TIME
58
8 Optimisation
8.1 Self-optimisation
Procedure
Start of SO
Switching
line
Start of selfoptimisation
59
8 Optimisation
8.2 Checking the optimisation
Start-up
procedure
Control
response
60
Xp too large
Xp too small
Cy too large
optimum
setting
8 Optimisation
8.3 Fuzzy parameters
In addition to the algorithms for the
various controller structures, the controller software also includes a fuzzy
module. This can be used to improve
both the control and the disturbance
response of controllers with I-action.
When the fuzzy module is activated,
the output y is made up of the controller output and the output signal of
the fuzzy module.
61
8 Optimisation
Action Reaction
Fc1
Fc1
Fc2
disturbance amplitude
reduced, stabilisation
time increased
disturbance amplitude
increased, stabilisation
time reduced
stabilisation time reduced
Fc2
stabilisation time
increased
62
9 Retrofitting of cards
The following steps are necessary for retrofitting cards:
E rostatic charges during fitting and removal. Carry out the card change
The cards can be damaged by electrostatic discharge. Avoid electon a workbench which is earthed.
Identifying the
card
h Identify the card by the sales no. or part no. that is glued onto the
packaging.
Cards
Card No.
1/2
1/2
70/00366099
70/00490339
358457
483509
1
2
3
4
5
6
70/00366100
70/00366101
70/00366102
70/00366103
70/00366104
70/00366105
358444
358452
358445
358447
358449
358447
70/00366106
358450
RS422/485 interface
54
70/00366107
358443
PROFIBUS-DP
64
70/00375280
368705
Outputs/logic inputs:
Relay (changeover contact)
Solid-state relay 230V 1A
Logic 0/5V
Logic 0/22V
Analogue output
Supply for
2-wire transmitter
Two logic inputs
63
9 Retrofitting of cards
Configuring
the analogue
input
Voltage -10/0/210V
-1 1V
The standard analogue inputs 1 and 2 are configured ex-factory as universal input or as voltage input for certain measuring ranges (see type
designation or order details). They can also be reconfigured:
Universal input
(remaining ranges)
Voltage -10/0/210V
-1 1V
1
1 = Analogue input 1
2 = Analogue input 2
64
9 Retrofitting of cards
Removing the
controller
chassis
Assigning the
slot
65
9 Retrofitting of cards
Inserting the
card
Inserting the
controller
chassis
66
h Insert the card into the guide until the projections on the card snap into
the notches provided (2).
h Push the controller chassis into the case until the lugs (underneath the
knurled area) snap into place.
10 Interfaces
10.1 RS422/485 interface
The controller can be integrated into a data network via the interface. The following applications can be implemented, for example:
- process visualisation
- system control
- generating a report
- configuration
67
10 Interfaces
10.2 PROFIBUS-DP
Fieldbus
Data
transmission
GSD generator
With the aid of the project design tool included in the delivery (GSD generator;
GSD = Device Base Data), a standardised GSD file is created, which serves to
integrate the controller into the fieldbus system, through the selection of characteristic controller features.
68
11 Accessories
11.1 External relay module/logic module ER8/EL8
By using the external relay module ER8 or logic module EL8, the controller can
be expanded by eight relay outputs (changeover contacts) or logic outputs (0/
12 V). Communication with the controller occurs via the RS422/485 interface.
All controller signals for switching outputs can be output by the module.
Configuration is only possible through the setup program.
v Section 7.4 Outputs
H
Connection
The electrical connection is carried out like the connection to an RS485 interface (the figure below shows ER8; see also Operating Manual ER8/EL8,
B 703564).
PE L1 N
141
142
143
241
242
243
33411
33422
441
33433
442
443
(L+) (L-)
Power
K1
K2
K3
K4
K5
K6
K7
K8
Error
541
Configuring
the module
542
543
641
642
643
741
742
743
841
842
843
RxD RxD
TxD TxD GND
97 98 99
3 4 5
3 4 5
If the setup plug is connected to the controller, the module will not be
operated and the outputs are in idle position (logic outputs: 0 V).
69
11 Accessories
11.2 Setup program with commissioning software
Setup program
- CD-ROM drive
- 1 free serial interface or USB interface
The program shows the current configuration as a list in the background. The
corresponding entry template is called up by double-clicking on the list, or via
the menus.
Some controller functions can only be configured via the setup program:
- Customized linearisation (input of a linearisation table)
- Display brightness of display 3
- Switch off code request (extended configuration)
- Configure relay module
- Alter passwords
Commissioning
software
The commissioning software is a part of the setup program and is available for
adapting the controller to the control loop, optimally and conveniently.
Different process variables (e.g. setpoint, process value, control deviation, signals from the controller outputs) can be displayed graphically. The controller
parameters can be altered and transferred to the controller via the setup/
RS422/485 interface.
Data recording is limited to 48 hours.
70
12 Appendix
12.1 Technical data
Thermocouple input
Range1
Designation
Fe-Con
Fe-Con
Cu-Con
Cu-Con
NiCr-Ni
NiCr-Con
NiCrSi-NiSi
Pt10Rh-Pt
Pt13Rh-Pt
Pt30Rh-Pt6Rh
W5Re-W26Re
W3Re-W25Re
L
J
U
T
K
E
N
S
R
B
-200 +900C
-200 +1200C
-200 +600C
-200 +400C
-200 +1372C
-200 +910C
-100 +1300C
-50 +1768 C
-50 +1768 C
0 1820 C
0 2320 C
0 2400 C
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
Cold junction
Meas. accuracy
Ambient
temperature error
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%2
0.25%
0.25%
Type of connection
Range
Meas. accuracy
Ambient
temperature error
Pt100
EN 60751
2-wire/3-wire
-200 +850C
0.05%
50 ppm per C
Pt 50,500, 1000
EN 60751
2-wire/3-wire
-200 +850C
0.1%
50 ppm per C
2-wire/3-wire
-50 +200C
0.1%
50 ppm per C
2-wire/3-wire
-60 +250C
0.05%
50 ppm per C
-50 +150C
1.0%
50 ppm per C
Cu50
Ni100
DIN 43760
KTY21-6
2-wire
PtK9
2-wire
lithium-chloride sensor
max. 30 per conductor in 2-/3-wire circuit
250A
Lead compensation
not required for 3-wire circuit. For 2-wire circuit, lead compensation can be provided in the software
by process value correction.
Range
Voltage
0 10V,
-10 to +10V,
-1 to +1V,
0 1V,
0 100mV,
-100 to +100mV,
Current
Meas. accuracy
Ambient
temperature error
0.05%
0.05%
0.05%
0.05%
0.05%
0.05%
0.1%
0.1%
Potentiometer
Over/underrange
Probe/lead break
Thermocouple
Resistance thermometer
Voltage
2 10V
0 10V
Current
4 20mA
0 20mA
= recognised
-= not recognised
Standard version
71
12 Appendix
Outputs
Relay
contact rating
contact life
contact protection circuit
Logic
current limiting
changeover contact
3A at 250VAC resistive load
150 000 operations at rated load
56/15nF between common-make/common-break
0/5V
20mA
or
Solid-state relay
contact rating
protection circuit
0/22V
30mA
1A at 230V
Varistor
Voltage
output signals
load resistance
Current
output signals
load resistance
22V
30mA
Controller
Controller type
Single-setpoint controller,
double-setpoint controller, modulating controller, proportional controller,
proportional controller with integral actuator driver
Controller structures
P/PD/PI/PID/I
A/D converter
Sampling time
210msec
Electrical data
Supply (switched mode power supply)
to EN 61010, Part 1
overvoltage category II, pollution degree 2
Power consumption
Data backup
EEPROM
Electrical connection
Electromagnetic compatibility
Interference emission
Immunity to interference
EN 61326-1
Class A - only for industrial use Industrial requirements
Safety standards
Housing
Housing type
Type
Bezel in mm
Depth behind panel in mm
Panel cut-out in mm
plastic housing for panel mounting (indoor use) acc. to IEC 61554
703575/1...
703575/2...
703570/0...
48 x 96 (portrait)
96 x 48 (landscape)
96 x 96
130
130
130
45+0.6 x 92+0.8
92+0.8 x 45+0.6
92+0.8 x 92+0.8
Site altitude
Operating position
unrestricted
Protection
Weight (fully fitted)
Standard version
72
approx. 420g
approx. 730g
12 Appendix
Approvals/marks of conformity
Mark of
conformity
Testing laboratory
Certificates/certification
numbers
Test basis
valid for
DIN
Registernummer TR1117
DIN EN 14 597
DICON 500
GL - Hardware
GL - Software
Germanischer Lloyd
Certificate
No. 15 694-00 HH
GL-Baumusterprfung
Kategorie C, EMC1
DICON 500
c UL us
Underwriters Laboratories
E 201387
UL 61010-1
DICON 400/500
CAN/CSA-C22.2 No. 61010-1
73
12 Appendix
12.2 Alarm messages and display priorities in the normal display
Priority
Display
Matrix
high
7-segment
Possible error /
notes
Assignment
Error handling
check/repair/replacement
controller
+LEDs
8888.
8888. (blinks)
(no display)
(no display)
- supply faulty
BREAK
BREAK
E1
E4
external
signal
generator
- probe/lead short-circuit at
standard-signal input
- overrange at standard-signal
input
- underrange at standard-signal
input
ORANGE
ORANGE
URANGE
URANGE
-1999.
(blinks)
or ( )*
external
signal
generator
- underrange of resistance
thermometer and thermocouple
input
- probe/lead short-circuit of
resistance thermometer
- probe/lead break of resistance
thermometer 1.10, 1.7, 2.11,
3.11
ORANGEM1
( )*
( )*
MATH1
ERR ( )*
ERR
mathematical error
(violation of mathematical rules;
impermissible values)
controller
MATH2
( )*
logic error
(violation of mathematical rules)
controller
( )*
BUSERROR
( )*
no communication
periphery
check periphery
(Text)
(Text)
( )*
(Text)
(Text)
( )*
(Text)
( )*
( )*
ORANGEM2
URANGEM1
URANGEM2
LOG1
ERR
LOG2
ERR
ER8
(Text)
ERR
74
12 Appendix
Priority
Display
Matrix
high
7-segment
Assignment
Error handling
check/repair/replacement
SOACTIVE
( )*
----
----
controller
or ( )*
low
Possible error /
notes
- retrofit card
-
75
76
Pt100
Example:
No. Transducer
20500C
Measuring
range
Machinery room
boiler
temperature 1
Measurement
site
Measurement input
Output
100%
Output 1
Output 2
Output 3
Output 4
Output 5
12 Appendix
12 Appendix
12.3 Character set for matrix display
The special characters for text entries in the setup program are shown below.
They are entered from the keys using the key combination Alt + XXX
77
12 Appendix
12.4 Instrument features (configuration level 2)
The software version and the hardware features of the process controller are
shown here
CONF
Parameters
Value/selection
Description
Version
VERSION
50.0X.0X
version number
VDN number
VDN
STANDARD
XXX.XXXX
standard version
VDN number
NO.
IN3
IN4
IN1
IN2
IN3
IN4
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
10V
10V
10V
10V
NO
YES
not available
available
universal input
NO
YES
not available
available
voltage input
-10/0/2 10V
NO
RELAY
SSRELAY
ANOUTPUT
LOGIC 5V
OUTP 22V
LOGIN
not available
relay
solid-state relay
analogue output
logic output 5V
logic output 22V or
voltage output for
2-wire transmitter
two logic inputs
Setup interface
SETUP
NO
YES
not connected
connected
Interface
INTERFCE
NO
RS422/485
PROFIBUS
not available
RS 422/485
PROFIBUS-DP
Mathematics
MATHLOG
NO
YES
not available
available
78
12 Appendix
12.5 Notes for instruments with Germanischer Lloyd (GL) approval
The information below is intended to supplement or replace the details that
have already been given.
-5 to 55C
100% r. h.
0.7g
Relative humidity
Vibration
Electromagnetic compatibility
The electromagnetic compatibility corresponds to the GL guidelines for type
examinations (10.97).
12.5.3 Inhibits
All levels are inhibited by codes. Alterations, whether accidental or deliberate,
cannot be made easily. The operating level is not inhibited by a code. In this
case, it is possible to lock the entire keypad via a logic contact (e.g. keyswitch).
v Section 5.3
79
12 Appendix
H
H
80
13 Index
A
Accessories 10
Action 38
Alarm messages 74
Analogue input 9, 40
configuring 64
Approvals 9
B
Basic type extension 9
C
Card
identifying 63
retrofitting 63
Code request 25
Cold-junction temperature
constant 42
external 42
Configuration level 1 25
Configuration level 2 25
Connection diagrams 1620
Control direction 35
Controller 35
Controller chassis, removal of 14
Controller type 35
H
Humidity control 49
I
Inputs 40
of controller 35
Installation notes 15
Instrument name 55
Interface 9
Isolation 21
K
Key designation 23
L
Language for instrument texts 53
Levels and menus 26
Limit comparator 37
absolute 39
relative 39
Limit comparator functions 37
Limit value 38
Linearisation 41, 49
Logic formula 52
Logic functions 56
combined 57
Logic input 56
Data format 58
Deadband 36
Decimal point
shift 26
Dimensions 1112
Display 53
Display end 42
Display start 42
Display switching 29
automatic 53
Displays and controls 23
Normal display 25
F
Filter time constant 42
Fitting in position 13
Formula input 50
O
Operating level 25, 30
Operating modes 24
Optimisation 60
Output 9, 45
self-optimisation 36
81
13 Index
P
Parameter level 25, 31
Parameter set
active 32
Profile program
holding 47
starting 47
Profile program function 25, 4647
Protocol type 58
Pulse function 38
R
Ramp function 4647
Ramp slope 46
Range end 42, 48
Range start 42, 48
Ratio control 49
Recalibration
customized 43
Response time
minimum 58
S
Selection 27
Self-optimisation 59
Setpoint
altering 27
Setpoint limits 36
Setpoint switching 27
82
Supply frequency 40
Switching action 56
Switching differential 38
Switch-on delay 38
T
Technical data 71
Time 48
Time input 27
Time-out 25, 53
Transducer 40
Type designation 9
U
Unit 40
of slope 46
Unit address 58
V
Value input 26
Variable a 48
Variable b 48
Z
Zero
for analogue signals 46
Street address:
Moritz-Juchheim-Strae 1
36039 Fulda, Germany
Delivery address:
Mackenrodtstrae 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax:
+49 661 6003-607
E-mail: mail@jumo.net
Internet: www.jumo.net
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:
+44 1279 635262
E-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk