Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Jumo Controleri

Download as pdf or txt
Download as pdf or txt
You are on page 1of 84

JUMO DICON 400/500

Universal Process Controller

Type 703575/2...

Type 703575/1...

Type 703570/0...

B 703570
Operating Manual

2013-10-01/00370043

Please read this operating manual before commissioning the instrument. Keep the manual in a
place which is accessible to all users at all times.
Your comments are appreciated and may help us in improving this manual.
All necessary settings are described in this operating manual. Manipulations not described in the
manual or expressly forbidden will jeopardize your warranty rights. Please contact the nearest subsidiary or the head office, should you encounter problems.

When accessing the inner parts of the unit and returning modules, assemblies or components,
please observe the regulations accordings to EN 61340-5-1 and EN 61340-5-2 Protection of
electrostatic sensitive devices. Only use ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD.
ESD=Electro Static Discharge

Contents
1

Introduction

1.1

Description .................................................................................................... 7

1.2

Block structure ............................................................................................. 7

1.3
1.3.1
1.3.2
1.3.3

Typographical conventions .........................................................................


Warning signs .................................................................................................
Note signs ......................................................................................................
Presentation ...................................................................................................

8
8
8
8

Identifying the instrument version

2.1

Type designation .......................................................................................... 9

2.2

Accessories ................................................................................................ 10

Installation

3.1

Location and climatic conditions .............................................................. 11

3.2
3.2.1
3.2.2
3.2.3

Dimensions .................................................................................................
Type 703570/0... ...........................................................................................
Type 703575/1... ..........................................................................................
Type 703575/2... ..........................................................................................

3.3

Edge-to-edge mounting ............................................................................ 13

3.4

Fitting in position ........................................................................................ 13

3.5

Cleaning the front panel ............................................................................ 13

3.6

Removing the controller chassis .............................................................. 14

Electrical connection

4.1

Installation notes ........................................................................................ 15

11
11
11
12
12

15

4.2 Connection diagrams ................................................................................. 16


4.2.1 Type 703570 ................................................................................................. 16
4.2.2 Type 703575 (portrait and landscape format) .............................................. 19
4.3

Isolation ....................................................................................................... 21

Contents
5

Operation

23

5.1

Displays and controls ................................................................................ 23

5.2

Operating modes and states ..................................................................... 24

5.3

Principle of operation ................................................................................ 25

5.4

Entering values and selecting settings .................................................... 26

5.5

Altering setpoints ....................................................................................... 27

5.6

Manual mode .............................................................................................. 28

5.7

Display switching ....................................................................................... 29

5.8

Operating level ........................................................................................... 30

Parameter level

31

Configuration level 1

33

7.1

Controller .................................................................................................... 35

7.2

Limit comparators ...................................................................................... 37

7.3

Inputs ........................................................................................................... 40

7.4

Outputs ........................................................................................................ 45

7.5

Ramp and profile program function ......................................................... 46

7.6

Maths and logic module ............................................................................ 48

7.7

Display ......................................................................................................... 53

7.8

Logic functions ........................................................................................... 56

7.9

Interface ...................................................................................................... 58

Optimisation

8.1

Self-optimisation ........................................................................................ 59

8.2

Checking the optimisation ........................................................................ 60

8.3

Fuzzy parameters ....................................................................................... 61

59

Contents
9

Retrofitting of cards

63

10

Interfaces

67

10.1 RS422/485 interface ................................................................................... 67


10.2 PROFIBUS-DP ............................................................................................ 68

11

Accessories

69

11.1 External relay module/logic module ER8/EL8 ......................................... 69


11.2 Setup program with commissioning software ........................................ 70

12

Appendix

71

12.1 Technical data ............................................................................................. 71


12.2 Alarm messages and display priorities in the normal display ............... 74
12.3 Character set for matrix display ............................................................... 77
12.4 Instrument features (configuration level 2) .............................................. 78
12.5 Notes for instruments with Germanischer Lloyd (GL) approval ............
12.5.1 Technical data .............................................................................................
12.5.2 Alarm messages .........................................................................................
12.5.3 Inhibits ........................................................................................................
12.5.4 Manual mode ..............................................................................................
12.5.5 Additional notes ..........................................................................................

79
79
79
79
79
79

13

81

Index

Contents

1 Introduction
1.1 Description
This series of universal, freely configurable process controllers is available in
the formats 96mm x 96mm and 96mm x 48mm (portrait and landscape).
The instruments feature two 4-digit 7-segment displays, five or eight LEDs for
indicating the switching status and operating modes, an 8-digit matrix display,
as well as six keys for operation and configuration.
The controller slots can be assigned flexibly by the user, according to the
block structure.
Additional functions include self-optimisation, parameter set switching, and up
to eight limit comparators.
Linearisations for conventional transducers are held in the memory; a customized linearisation table can be programmed.
The process controller can be adapted to a variety of tasks with the aid of a
maths module.
The instruments can be integrated into a data network via a serial interface, or
can be expanded through an external relay module.
A setup program is available for easy configuration from a PC.
The electrical connection is at the rear by screw terminals.

1.2 Block structure

Outputs:
- Relay
- Solid-state relay
- Logic output 5V
- Logic output 22V
- Analogue output
- Supply for
2-wire transmitter
Type 703570 only
Analogue inputs:
- Resistance thermometer
- Thermocouples
- Standard signals
- Potentiometer

1 Introduction
1.3 Typographical conventions
1.3.1 Warning signs

The signs for Danger and Warning are used


in this manual under the following conditions:

E
1.3.2 Note signs

Danger

This sign is used when there may be danger


to personnel if the instructions are disregarded or not followed accurately.

Warning

This sign is used when there may be damage


to equipment or data if the instructions are
disregarded or not followed accurately.

Warning

This sign is used when special care must be


taken when handling components that are
sensitive to electrostatic discharges.

Note

This symbol is used when your attention is


drawn to a specific remark.

Reference

This symbol refers to additional information in


other manuals, chapters or sections.

H Action

This sign refers to an action to be performed.


The individual steps are marked by this asterisk, e. g.
h Press I key

1.3.3 Presentation

E+I

Key combination The depiction of keys together with a plus


sign means that first the E key has to be
pressed and held down, and then a further
key is pressed.

CONFIG 1

Dot-matrix display Texts and messages are visualised on the


dot-matrix display.

2 Identifying the instrument version


2.1 Type designation
(1)
703570/ 0

(2)

(3)

(4)

(5)

(6)

(7)

0 0

0 0 0

Format 96mm x 96mm


703575/

Formats 48mm x 96mm and 96mm x 48mm

(1) Basic type extension


Format:
96mm x 96mm
48mm x 96mm portrait
96mm x 48mm landscape

(5) Interface
not assigned
RS422/485
PROFIBUS-DP
(no GL approval)

0
1
2

Version:
Standard with factory settings
Customized programming

(2) Analogue input


not assigned
Universal input

1
2
3
1 2 3 4
0 0 0 0

(all transducers except


voltage -10/2/0 10V)

1 1 1 1
2 2 2 2

voltage -10/2/0 10V


(3) Output
not assigned
Relay (changeover
contact)
Solid-state relay 230V 1A
Logic 0/5V
Logic 0/22V
Analogue output
Supply for 2-wire
transmitter
Two logic inputs

(6) Maths and logic module


not available
available

8
9

Language for instrument texts:


German
English
French

(7) Approvals
DIN EN 14597*
Germanischer Lloyd (GL)*
DIN EN 14597 and GL*
DIN EN 14597 and UL*
GL and UL*
DIN EN 14597, GL and UL*

Delivery package:

2
3
4
5

- seal

2
3
4
5

2
3
4
5

2
3
4
5

2
3
4
5

0 0
0 3

0
0
0
0
0
0

5
6
6
6
6
6

6
2
3
4
5
6

* only for Type 703570

1 2 3 4 5 6
0 0 0 0 0 0
1 1 1 1 1 1
2
3
4
5

0 0
5 4
6 4

- controller
- 2 fixing brackets

- Operating Manual B 703570

6 6 6 6 6 6
7 7 7 - - -

(4) Supply
110 240V AC +10/-15%
48 63Hz
20 30V DC/AC 48 63Hz

2 3
2 5

2 Identifying the instrument version


2.2 Accessories
External relay module ER8 (3A/230V)
Supply 110 240V AC
Part no. 00405292
(no GL approval)
External relay module ER8 (3A/230V)
Supply 20 53V DC/AC
Part no. 00405297
(no GL approval)
External logic module EL8 (0/12V)
Supply 110 240V AC
Part no. 00439131
(no GL approval)
External logic module EL8 (0/12V)
Supply 20 53V DC/AC
Part no. 00471459
(no GL approval)
PC interface for setup program
with USB/TTL converter, 2 adapters (socket, pins)
Part no. 00456352
Setup program including start-up software
for Windows NT4.0/2000/XP/Vista/7 (32/64 bit)
Part no. 00379085
Hardware requirements:
- 512 Mbyte RAM
- 50 Mbyte available on hard disk
- CD-ROM drive
- 1 free serial interface or USB interface

10

3 Installation
3.1 Location and climatic conditions
The instrument location must conform to the requirements specified under Technical Data. The ambient temperature at the location can be
between -5 and 55 C, at a relative humidity of not more than 95 %.

3.2 Dimensions
3.2.1 Type 703570/0...
Setup plug

panel cut-out to IEC 61554

11

3 Installation
3.2.2 Type 703575/1...

Setup plug
panel cut-out to
IEC 61554

3.2.3 Type 703575/2...


Setup
plug

panel cut-out to IEC 61554

12

3 Installation
3.3 Edge-to-edge mounting
Minimum spacing of the panel cut-outs
Type
horizontal
without setup plug:
703570/0...
11mm
703575/1... (portrait format)
11mm
703575/2... (landscape format)
30mm
with setup plug:
703570/0...
11mm
703575/1... (portrait format)
11mm
703575/2... (landscape format)
65mm

vertical
30mm
30mm
11mm
65mm
65mm
11mm

3.4 Fitting in position


h Fit the seal provided onto the
instrument housing.
h Insert the controller from the front
into the panel cutout.
h Insert the mounting brackets from
the rear of the panel into the guide
slots at the sides of the housing.
The flat sides of the brackets must
be against the housing.
h Place the brackets against the rear
of the panel and tighten them evenly
using a screwdriver.

3.5 Cleaning the front panel


The front panel can be cleaned with the usual rinsing and cleaning agents. It
has limited resistance to organic solvents (e. g. methylated spirits, white spirit,
P1, xylol and similar.). Do not use high-pressure cleaning equipment.

13

3 Installation
3.6 Removing the controller chassis
The controller chassis can be removed from the housing for servicing.
h Press the knurled areas together at
top and bottom (left and right with
landscape format) on the front panel
and pull out the controller chassis.

14

When inserting the controller chassis, care must be taken that the lugs
(underneath the knurled areas) snap into position.

4 Electrical connection
4.1 Installation notes
The choice of cable, the installation and the electrical connection of the instrument must meet the requirements of VDE 0100 Regulations on the installation of power circuits with nominal voltages below 1000 V or the appropriate local regulations.
The electrical connection must only be carried out by qualified personnel.
The instrument shall be operated by mains protected with a branch circuitry
overcurrent protection device not more than 20 Amps.
For servicing/repairing a Disconnecting Device shall be provided to disconnect all conductors.
A current-limiting resistor interrupts the supply circuit in the event of a short
circuit. The load circuit has to be fused for the maximum relay current in
order to prevent welding of the output relay contacts in the event of a shortcircuit.
Electromagnetic compatibility conforms to the standards and regulations
specified under Technical data.
Input, output and supply lines should be routed separately, not parallel to
one another.
Arrange sensor and interface cables as twisted and screened cables. Do
not run them close to power cables or components. Earth the screen at one
end at the instrument, to the TE terminal.
Earth the instrument at terminal TE to the earth conductor. This line must
have at least the same cross-section as the supply lines. Earth lines should
be run in a star layout to a common earth point which is connected to the
earth conductor of the supply. Do not loop the earth connections, i. e. do
not run them from one instrument to another.
Do not connect additional loads to the supply terminals of the instrument.
The instrument is not suitable for installation in hazardous areas.
Apart from faulty installation, there is a possibility of interference or damage
to controlled processes due to incorrect settings on the controller (setpoint,
data of parameter and configuration levels, internal adjustments). Safety
devices independent of the controller, such as overpressure valves or temperature limiters/monitors, should always be provided and should be
capable of adjustment only by specialist personnel. Please refer to the appropriate safety regulations in this connection. Since adaptation (self-optimisation) cannot be expected to handle all possible control loops, there is
a
theoretical possibility of unstable parameter settings. The resulting process
value should therefore be monitored for its stability.
The maximum permitted voltage difference between the inputs of the controller and TE is 30 V AC or 50 V DC.

15

4 Electrical connection
4.2 Connection diagrams
4.2.1 Type 703570

V
H
H

1 2 3 4
BE1

7 8

BE2

The instrument version can be identified


by the type code.
PROFIBUS-DP:
v Interface Description B 703560.2.3

9 10 11

The electrical connection must only


be made by suitably qualified personnel.

Thermocouples

Resistance
thermometer
(3-wire)

Resistance
thermometer
(2-wire)
Voltage
0/210V

Current
0/420mA
+

Logic inputs 1+2

H
16

Analogue input 2

Potentiometer
A

Analogue input 1

v Section 9 Retrofitting of cards


Additional analogue input signals
Signal
Connection like
01V
010V
-1to +1V
010V
-10 to +10V
010V
0100mV
thermocouple
-100 to +100mV
thermocouple

When a thermocouple with internal temperature compensation is wired up to the analogue inputs 1, 3 or 4, Pt500, Pt1000 or KTY must not be connected to analogue input 2.

4 Electrical connection
Type 703570
PROFIBUS DP

Output 6
(Slot 6)

-20/0/420mA

-20/0/420mA

-10/0/210V

-10/0/210V

230V/1A

230V/1A

5V(22V)/30mA*

5V(22V)/30mA*

A GND

+5 V
20 mA B

Output 5
(Slot 5)

RS485/ER8
RxD/ RxD/
TxD TxD GND
(+) ()

Interface

RS422
RxD RxD TxD TxD GND
(+) () (+) ()

1 2 3 4 5

10 11 12
Thermocouples

Earth the screen for the


interface cable at one
end only to TE.

Resistance
thermometer
(2-wire)

230V/3A

1 2 3

6 7 8

* Supply for
2-wire transmitter (22V)
The output must be configured accordingly.

v Section 7.4 Outputs

Resistance
thermometer
(3-wire)

Resistance
thermometer
(2-wire)

Voltage
0/210V
+

Current
0/420mA

Current
0/420mA
+

Potentiometer

Potentiometer
E

Additional analogue input signals


Signal
Connection like
01V
010V
-1to +1V
010V
-10 to +10V
010V
0100mV
thermocouple
-100 to +100mV
thermocouple

Voltage
0/210V

v Section 9 Retrofitting of cards

10 11 12

Thermocouples

Resistance
thermometer
(3-wire)

230V/3A

Analogue input 4
(option)

Analogue input 3
(option)

Contact protection circuit (relays):


56/15nF between common-make/common-break

17

4 Electrical connection
Type 703570

Output 1
(Slot 1)
-20/0/420mA

i
-10/0/210V

u
230V/1A

5V(22V)/30mA** Supply for


2-wire transmitter (22V)
The output must be configured
accordingly
230V/3A
v Section 7.4 Outputs
+

1 2 3

L1 N

BE3

AC

TE

110240V

BE4
AC/DC

2030V
Contact protection circuit (relays):
56/15nF between common-make/common-break

18

Logic inputs 3+4


(Slot 1)

Mains supply

4 Electrical connection
4.2.2 Type 703575 (portrait and landscape format)

V
H

H
H

The electrical connection must only be


carried out by properly qualified personnel

The instrument version can be identified


by the type code.

Earth the screen for the


interface cable at one
end to TE.

PROFIBUS-DP:
v Interface Description B 703560.2.3

* Supply for 2-wire transmitter


The output must be configured accordingly.
v Section 7.4 Outputs

Contact protection circuit (relays):


56/15nF between common-make/common-break

19

4 Electrical connection
Type 703575

* Supply for
2-wire transmitter
The output must be configured accordingly.
v Section 7.4 Outputs
Contact protection circuit (relays):
56/15nF between common-make/common-break

1 2 3 4
BE1

7 8

9 10 11

BE2

Thermocouples

Resistance
thermometer
(3-wire)

Resistance
thermometer
(2-wire)
Voltage
0/2 10V

Current
0/4 20mA
+

Logic inputs 1+2

Analogue input 2

Potentiometer
A

Analogue input 1

v Section 9 Retrofitting of cards


Additional analogue input signals
Signal
Connection like
01V
010V
-1 to +1V
010V
-10 to +10V
010V
0100mV
thermocouple
-100 to +100mV
thermocouple

H
20

When a thermocouple with internal temperature compensation is wired up to analogue


input 1, a Pt500, Pt1000 or KTY must not be connected to analogue input 2.

4 Electrical connection
4.3 Isolation
For Type 703570 and Type 703575

(Type 703570 only)

(Type 703570 only)

21

4 Electrical connection

22

5 Operation
5.1 Displays and controls
(4)

(1)
(5)

(2)
(3)

(6)

(1) configurable
7-segment display (display 1)
4 digits, red
Type
Height
703570
13mm
703575
10mm
factory setting: process value
(2) configurable
7-segment display (display 2)
4 digits, green
Type
Height
703570
10mm
703575
7mm
factory setting: setpoint
(3) configurable dot-matrix display
(display 3)
8 digits, green
factory setting: output
(bar graph)

(4) Setup interface


Position depends on Style;
see dimensional drawings
v Section 3.2 Dimensions

(5) Status indication


6 (3) yellow LEDs for status indication
of the outputs1
2 green LEDs to display manual
mode and ramp/profile program
function

(6) Keys
see below

1. no display with analogue inputs

v Section 7.7 Display


Key designation

Keys from left to right:


PGM
for programming
Exit/Hand for programming and for manual mode1
Automatic to start programs
Increment to increase parameter values
Decrement to decrease parameter values
Enter
for programming and display switching

1. In the description below the key is shown according to its function ( X or M ).

23

5 Operation
5.2 Operating modes and states
Operating mode/
state

Display

Normal display

Notes
The displays present the values according to the
display configuration.
v Section 5.7 Display switching
factory setting:

- process value
- setpoint
- output (bar graph)

Ramp and
profile program
function

A ramp or a profile is run.


v Section 7.5 Ramp and profile program function

Manual mode

The output is modified by hand.


v Section 5.6 Manual mode

Self-optimisation

Self-optimisation is running.
v Section 8.1 Self-optimisation

Alarm messages
- LED is off;

24

- LED is on

v Section 12.2 Alarm messages and display priorities in the normal display

5 Operation
5.3 Principle of operation
Normal display

Initial status

Profile program
function

Eight segments of the program function are programmed here.


This level only appears when the profile program function has been activated.

Operating level

This level can be used to program setpoints and indicate process variables.

Parameter
level

The parameters at this level are used


to adapt the controller to the control
loop.

Configuration
level 1

This level serves to adapt the controller to the control task.

Configuration
level 2

The software version and the hardware


specifications of the controller are
indicated here.

Service

Only accessible to service personnel.

Time-out

If no key has been pressed during a


configurable period of time (factory
setting: 30sec), the controller automatically returns to normal display.

Code request

In order to access some levels, a code


has to be entered first. The codes can
be changed via the setup program.

Codes are entered digit by digit.

= factory setting

h Enter the digit with I and D


h Step on to the next digit with E

25

5 Operation
Levels and
menus

Each level is divided into menus, thus creating a tree structure which has a selection or a value input at the end of each branch.

5.4 Entering values and selecting settings


Value input

h Increase the parameter value with I


h Decrease the parameter value with D
The longer the key is pressed, the more quickly the value changes. Approx.
1sec after releasing the key, the entry is accepted automatically (display flashes briefly).
Parameters can be altered within their value range, or within the maximum
values that can be displayed (e. g. 2 decimal places: -99.99 to +99.99).

Shift decimal
point

h Increase the decimal places with


E+I
h Decrease the decimal places with
E + D (the last digit must be 0)

26

5 Operation
Code and
time input

Time inputs and codes are entered digit by digit.


h Increase or decrease the value (digit)
with I and D
h Confirm the entry and select the next
digit with E

Selection

h Step upwards in the selection list


with I
h Step downwards in the selection list
with D
The selection will be automatically
accepted after approx. 1sec.

5.5 Altering setpoints


The active setpoint (see setpoint switching) is altered in normal display.
h Alter the setpoint with
I and D
shift decimal point with
E + I and E + D
(The entry is documented in the
matrix display)

Setpoint
switching

Normal display (configurable!)

If setpoint switching is programmed, the active setpoint is altered in the normal display.

Setpoint inputs via the interface have priority.

27

5 Operation
Relevant
settings

Operating level r Setpoints


Configuration level 1 r Controller r Controller inputs
Configuration level 1 r Controller r Setpoint limits
Configuration level 1 r Logic functions

5.6 Manual mode


The control loop can be opened by changing over to manual mode, and the
output is then adjusted manually.
h Change to manual mode with M

Normal display (configurable!)

h Alter the controller output


with I and D
(The output is accepted automatically after approx. 2sec)
h Terminate manual mode with X
With modulating controllers, the I
and D keys are used to adjust the
clockwise/anticlockwise rotation of a
motorised actuator. The output is only
indicated with the stroke retransmission connected.

I - open actuator
D - close actuator

OUTPUT
I
D

100.

OPERATNG

The levels can also be accessed from the manual mode. The manual mode
can be inhibited.
v Section 7.1 Controller
Relevant
settings

Configuration level 1 r Controller r Controller inputs


Configuration level 1 r Controller r Manual output
Configuration level 1 r Controller r Manual mode
Configuration level 1 r Logic functions

28

5 Operation
5.7 Display switching
Two display configurations can be provided that determine the visualisation of
values and process variables on the 7-segment displays and the dot-matrix
display.
h Switch display over with E
or automatic changeover after an adjustable interval
Display switching can be deactivated.

Configuration 2

Configuration 1

Example

Relevant
settings

Display 1: process value

Display 2: setpoint
Display 3: output

Display 1: analogue input 3

Display 2: analogue input 4


Display 3: maths 1

Configuration level 1 r Display r Configuration 1+2


Configuration level 1 r Display r Automatic display switching

29

5 Operation
5.8 Operating level
General

Four setpoints can be indicated and altered at the operating level, in addition
different process variables can be displayed.

Access the level


by ...

h pressing P (2x P with activated program function) in normal display or


in manual mode
OPERATNG
Parameter

Value/selection

Setpoints
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4

SETPTS
W1
W2
W3
W4

0.
0.
0.
0.

Process variables
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Mathematics 1
Mathematics 2
Output

PROCESS
ANALOG 1
ANALOG 2
ANALOG 3
ANALOG 4
MATHS 1
MATHS 2
OUTPUT

0.
0.
0.
0.
0.
0.
0.

30

Description
Value input
within the defined setpoint limits

Value display

6 Parameter level
General

Two parameter sets can be stored.

Access the level


by ...

h pressing P twice (3x P with activated program function) in normal display or in manual mode.

Access code

The level is protected by a code.


factory-set code: 0001

Select
parameter set

h Select parameter set with P

PARAMETR PARASET1
Parameters

Display

Value range

Controller
structure

STR
STR

Meaning

XP1
XP2

0 9999 digit
0 9999 digit

0 digit
0 digit

Switching cyle
time

TV1
TV2
TN1
TN2
CY1
CY2

0 9999 sec
0 9999 sec
0 9999 sec
0 9999 sec
0 9999 sec
0 9999 sec

80 sec
80 sec
350 sec
350 sec
20 sec
20 sec

Structure 21 refers to the second output in


the case of a double-setpoint controller.
With modulating controllers, only PI and
PID are possible.
Size of the proportional band
At Xp1,2 =0 the controller structure is not
effective!(Limit comparator response)
With proportional controllers, Xp1,2 must
be >0
Influences the differential component of
the controller output signal

Proportional
band

Derivative time

Contact spacing

XSH

0 999 digit

0 digit

Switching
differential

XD1
XD2

0 999 digit
0 999 digit

1 digit
1 digit

Stroke time

TT

5 3000 sec

60 sec

Working point

Y0

-100 to +100% 0%

Reset time

1
2

factoryset
P, I, PD, PI, PID PID
P, I, PD, PI, PID PID

Influences the integral component of the


controller output signal
For a switching output, the cycle time
should be selected so that no impermissible fluctuations of the process value
are caused by the switched energy supply,
while, at the same time, not overloading
the switching devices.
Spacing between two control contacts for
double-setpoint controllers, modulating
controllers and proportional controllers
with integral actuator driver.
Differential of switching controllers
for Xp = 0.

Utilised stroke time of the control valve on


modulating controllers and proportional
controllers with integral actuator driver.
Output for P and PD controllers
(y = Y0 at x = w).

1. also Xp2, Tv2, Tn2; Cy2; Xd2

31

6 Parameter level
PARAMETR PARASET1
Output limiting
Minimum relay
ON time

Y1
Y2
TK1
TK2

0 100%
-100 to +100 %
0 60sec
0 60sec

100%
-100%
0sec
0sec

Maximum output limit


Minimum output limit
Limitation of the switching rate on
switching outputs

The display of the parameters on the unit depend on the controller


type that was selected.
v Section 7.1 Controller

Active
parameter set

32

When parameter set 2 is active, the


decimal point is lit up on the right of
display 2.

7 Configuration level 1
General

The following applies to the representation of parameters and functions on the


unit:
The parameter is not displayed when
- the instrument features do not permit the function assigned to the
parameter.
Example: Output 3 cannot be configured when output 3 is not available
to the instrument.
- the parameter is irrelevant for the function that was previously configured.
Example: Analogue input 1 is configured to Pt100, which means that
display start / end for standard signals will not be indicated.

Access the
level by ...

h pressing P 3 times (4x P with activated program function) in normal


display or in manual mode.

Access code

The level is protected by a code.


factory-set code: 0002

Overview
r Controller
v Page 35

r controller type
control direction
controller inputs

r process value

external setpoint
external setpoint
with correction
stroke retransmission
additive disturbance
multiplying disturbance

setpoint limits

r setpoint start
setpoint end

manual output
self-optimisation
output 1+ 2 for selfoptimisation
dead band
fuzzy control 1
fuzzy control 2
r Limit comparators
v Page 37

r limit comparator 18

r function
action
switching differential
limit value
function on over/
underrange
switch-on delay
pulse function
LK inputs

r limit comparator PV

limit comparator setpoint

= press E !

33

7 Configuration level 1
r Inputs
v Page 40

r analogue input 1 4

r transducer
linearisation
measurement correction
constant cold-junction
temperature
external cold-junction
temperature
display start
display end
range start
range end
filter time constant
customized recalibration

r start value
end value

supply frequency
unit
r Outputs
v Page 45

r output 1 6

r Ramp and
program function
v Page 46

r function
ramp slope
unit of slope

r Maths/logic
v Page 48

r mathematics 1+2

r function
output signal
zero point
end value
output signal on
under/overrange

r function
variable a
variable b
range start
range end
linearisation

logic 1+2
r Display
v Page 53

r configuration 1+2

r Logic function
v Page 56

r logic input 1 8
limit comparator 1 8
logic output 1+2

r Interface
v Page 58

r type of protocol
data format

time-out
automatic display
switching

34

r baud rate
parity
stop bit

instrument address
minimum response time

= press E !

r display 13

r display value

decimal point

7 Configuration level 1
7.1 Controller
The following are set here: controller type and input variables of the controller,
setpoint limits, conditions for manual mode, the presettings for self-optimisation and the fuzzy logic.

CONFIG
Controller type

Control direction

1 CONTRL.

Parameters

Value/selection Description

CTR.TYPE

1-SETPT
2-SETPT
MODULTNG
ACTUATNG

DIRECTN.

PROP.

single-setpoint controller
double-setpoint controller
modulating controller
proportional controller with integral
actuator driver
proportional controller

DIRECT
INVERSE

Direct
Inverse

inverse:
The controller output Y is > 0 when
the process value is smaller than the
setpoint (e. g. heating).
direct:
The controller output Y is > 0 when
the process value is larger than the
setpoint (e. g. cooling).
INPUTS?
Inputs of the
controller
PV
process value
EXTSET?
external setpoint
EXTCORR
external setpoint
with correction
Y RETRM
stroke
retransmission
ADD DIST
additive disturbance
MUL DIST
multiplying
disturbance

NO FUNCT
ANALOG 1
ANALOG 2
ANALOG 3
ANALOG 4
MATHS 1
MATHS 2

no function*
analogue input 1**
analogue input 2
analogue input 3
analogue input 4
Mathematics 1
Mathematics 2
Defines from which analogue inputs
or maths functions the controller
receives the signals. Stroke retransmission has to be configured in the
case of a proportional controller with
integral actuator driver!
External setpoint with correction:
External setpoint + setpoint 1 =
present setpoint
The external setpoint can be corrected upwards or downwards from
the keys (setpoint 1). The present
setpoint appears on the (LED) display.
* factory-set for all, except process
value
** factory-set for process value

Factory settings are shown bold.

35

7 Configuration level 1
CONFIG

1 CONTRL.

Parameters
Setpoint limits
setpoint start
setpoint end

WLIMITS
STARTVAL
END VAL

Value/selection Description
0.
400.

-19990 to +9999
-1999400 to +9999

A
MANUAL

101.

The setpoint limits are


ineffective with setpoint input
via the interface.
For external setpoint with
correction, the correction value
is limited.

Manual output

Manual mode

MAN.MODE

ENABLED
INHIBTD

enabled
inhibited

Self-optimisation

TUNE

ENABLED
INHIBTD

enabled
inhibited

Output 1 for
self-optimisation

TUNEOUT1

RELAY
Relay
solid-state relay and logic output
SSRELAY
ANOUTPUT analogue output

-100100
101 = last output
Defines the output after changing
over to manual mode.

type of controller output 1 on selfoptimisation


Output 2 for
self-optimisation

TUNEOUT2

RELAY
Relay
SSRELAY
solid-state relay and logic output
ANOUTPUT analogue output
type of controller output 2 on selfoptimisation

Dead band

DEADBAND

0.

0999digit
serves to minimise the output
movement within the dead band;
e. g. with noisy signals.

The deadband is only effective


with controller structures with Icomponent.
Fuzzy control 1

FC1

0.

0100
0 = fuzzy control off
Intensity of the fuzzy signal added to
the controller output to improve the
control quality.

Fuzzy control 2

FC2

30.

030100
Influences the controller parameters
during activated fuzzy module to
improve the control quality.

Factory settings are shown bold.

36

7 Configuration level 1
7.2 Limit comparators
Limit comparators (limit monitors, limit contacts) can be used to monitor an input variable (limit comparator process value) against a fixed limit value or another variable (limit comparator setpoint). When a limit is exceeded, a signal can
be output or an internal controller function initiated.

Limit
comparator
functions

Limit comparators can have different switching functions.


lk1
On

lk4
On

lk7
On

lk2

lk3

On

On

lk5

lk6

On

On

lk1 lk6:
Monitoring referred to the
limit comparator setpoint.
lk7/lk8:
Monitoring referred to a fixed
value AL

lk8
On

w= limit comparator setpoint, AL = limit,


x = limit comparator process value, XSd =differential

CONFIG
Parameters

1 LIMITC
Value/selection Description

Limit comparator 1 LIMITC1

...

Limit comparator 8 LIMITC8

Configuration of limit comparators


as in example limit comparator 1
below.

Factory settings are shown bold.

CONFIG
Function

1 LIMITC LIMITC1

Parameters

Value/selection Description

FUNCTION

NO FUNCT
LK1
...
LK8

no function
function lk1
...
function lk8

Factory settings are shown bold.

37

7 Configuration level 1
CONFIG

1 LIMITC LIMITC1

Parameters

Value/selection Description

Action

ACTION

ABSOLUTE absolute
RELATIVE relative

Switching
differential Xsd

DIFFERTL

1.

019999 digit

Limit value AL

LIMIT

0.

-19990 to +9999 digit

Function on
over/underrange

RANGEFCT

RELDE-EN relay de-energised


RELENERG relay energised

If a limit comparator is connected to an output, then the setting Output


signal on over/underrange of the output has priority.
v Section 7.4 Outputs

Switch-on delay

DELAY

0.

0 9999sec

Pulse function

PULSEFCT

0.

-10 to +9999s
The limit comparator is automatically reset after an adjustable
interval.
-1= The limit comparator has to be
reset with the E key or the
logic function (all displays off).

Limit comparator
inputs
limit comparator
process value
limit comparator
setpoint

INPUTS
PV
SET

LK
LK

ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT

analogue input 1*
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)**
ramp end value
control deviation
output
* factory-set for LK process value
** factory-set for LK setpoint

Factory settings are shown bold.

38

7 Configuration level 1
Absolute

At the time of the alteration, the limit comparator acts in accordance with its
function.

Relative

The limit comparator is in the OFF status.


An alteration of the limit or the (limit comparator) setpoint could cause the limit
comparator to switch ON. Such a reaction will be suppressed, and this condition maintained until the (limit comparator) process value has moved away
from the switch-on region (grey area).
Example:
Monitoring the (controller) process value x with function lk4
Setpoint alteration w1w2
a) Initial status

b) Status at the time of the alteration.


The limit comparator remains on OFF although the process value is within
the switch-on region.

c) Control stabilised
The limit comparator again operates according to its function.

This function also prevents a limit comparator from being triggered during the
start-up phase.

39

7 Configuration level 1
7.3 Inputs
The analogue inputs are configured here.

CONFIG

1 INPUTS

Parameters

Value/selection Description

Analogue input 1

ANALOG

...

...

Analogue input 4

ANALOG

Supply frequency

PWRFREQ

50
60

Unit

UNIT

DEGREE
DEGREE

Configuration of the analogue inputs


as in the example analogue input 1
below.

4
HZ
HZ

50Hz
60 Hz
C C
F F

Factory setting are shown bold.

CONFIG
Transducer

1 INPUTS ANALOG

Parameters

Value/selection Description

PROBE

NO FUNCT no function*
resistance thermometer**
RTD
TC INTRN thermocouple
(internal cold junction)
TC EXTRN thermocouple
(external cold junction)
TC CONST thermocouple
(constant cold junction)
RESTRANS potentiometer
0 - 20mA
0 - 1 V
0 -100mV
-1 - 1V
+/-100mV
4 - 20mA
0 - 10V
2 - 10V
+/-10V

020mA
01V
0100mV
-1to +1V
-100to +100mV
420mA
010V
210V
-10Vto +10V
* factory-set on analogue input 2, 3, 4
** factory-set on analogue input 1

The selection of the transducers depends on the hardware configuration


of the analogue inputs. -10/0/2 10V and -1 1V will only be indicated
with the appropriate hardware configuration.
v Section 9 Retrofitting of cards
Factory settings are shown bold.

40

7 Configuration level 1
CONFIG
Linearisation

1 INPUTS ANALOG

Parameters

Value/selection Description

LINTAB

LINEAR
PT100
PT1000
PT500
PT50
CU50
KTY
PTK9
NI100
TC TPE J
TC TPE E
TC TPE K
TC TPE N
TC TPE T
TC TPE B
TC TPE R
TC TPE S
TC TPE U
TC TPE L
CUST LIN
W5RE W26
W3RE W25
W3RE W26

linear
Pt 100
Pt 1000
Pt 500
Pt 50
Cu 50
KTY21-6 (1k at 25C)*
Pt K9
Ni 100
Fe-Con J
NiCr-Con E
NiCr-Ni K
NiCrSi-NiSi N
Cu-Con T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-Con U
Fe-Con L
customized linearisation
W5Re-W26Re
W3Re-W25Re
W3Re-W26Re
* for other types, see setup
program (extended configuration)
** for customized linearisation up to
20 interpolation points can be
realised (with setup program only).
x = physical measured value
y = displayed value

Measurement
correction

OFFSET

0.

-19990 to +9999 digit


Measurement correction can be
used to correct a measured value
by a certain amount upwards or
downwards.
Examples:
measured
value

offset

294.7
295.3

+0.3
- 0.3

displayed
value
295.0
295.0

The controller uses the


corrected value (= displayed
value) for its calculation.
This value does not correspond to the actually measured
value.
If incorrectly applied, this can
result in impermissible values
of the control variable.

Factory settings are shown bold.

41

7 Configuration level 1
CONFIG
Parameters
Constant
cold-junction
temperature for
thermocouples

CJTEMP

External
cold-junction
temperature for
thermocouples

EXTTEMP

1 INPUTS ANALOG

Value/selection Description
50.

050100 digit
Temperature of the cold-junction
thermostat

ANALOG
...
ANALOG

1 Analogue input 1
...
4 Analogue input 4
Measurement of the cold-junction
temperature with a temperature
probe.

Display start

DSPLSTRT

0.

Display end

DISPLEND

100.

-19990 to +9999 digit


-1999100to +9999 digit
On transducers with standard
signal and on potentiometers, a
displayed value is assigned to the
actual signal.
Example:
0 20mA  0 1500C.
The range of the physical signal can
be 20% wider or narrower without
signalling out-of-range.

Range start

RNGESTRT

-1999.

-1999 to +9999 digit

Range end

RANGEEND

9999.

-1999 to +9999 digit


When the measuring range is
restricted, the controller will switch
to the response defined for going
out-of-range at an earlier point.
Example:
Pt100 (range: -200 to +850C).
An alarm message is to be output
for temperatures outside the range
15 200C.
range start: 15
range end: 200

Filter time constant FILTER

0.6

00.6100 sec
To adjust the digital input filter
(0sec = filter off).
At a signal jump, 63% of the changes are registered after 2 x filter time
constant.
If the filter time constant is large:
- high damping of disturbance signals
- slow reaction of process value
indication to PV changes
- low limit-frequency
(2nd order low-pass filter)

Factory settings are shown bold.

42

7 Configuration level 1
CONFIG

1 INPUTS ANALOG

Parameters
Customized
recalibration
Start value
End value

Value/selection Description

RECAL
STARTVAL
ENDVALUE

0.
1.

-19990 to +9999 digit


-19991 to +9999 digit
(for explanation, see below)
factory-set access code: 0004
In contrast to all other settings,
input of the start and end values
is linked to the present
measured value at the corresponding measurement input.
These values cannot simply be
read in by another instrument.

Factory settings are shown bold.

Customized
recalibration

A signal is processed electronically (conversion, linearisation ) to produce a


measured value via the analogue inputs of the controller. This measured value
enters into the calculations of the controller and can be visualised on the displays (measured value = indicated value).
This fixed relationship can be modified if required, i. e. the position and the
slope of the measurement characteristic can be altered.

Procedure

Apply two measurement points ((1), (3)), one after another, to the controller;
they should be as far apart as possible.
At these measurement points, enter the required display value (start value, end
value) in the controller. A reference instrument is most convenient for determining the measured values M1 and M2.
Measurement conditions must remain stable during programming.

Programming

h Move to measurement point (1)


h Enter start value (2) 1
h Move to measurement point (3)

43

7 Configuration level 1
h Enter end value E (4) 1

If recalibration is carried out without reference instrument, the offset


must be taken into account when moving to measurement point (3).

To cancel recalibration, the start and end values have to be programmed to


the same value. This sets the start value to 0 and the end value to 1.
Any subsequent recalibration will otherwise be based on the corrected
characteristic.

1. If start value=0 or end value =1 is to be set, then the value must first be altered
using I or D to enable correction.

44

7 Configuration level 1
7.4 Outputs
The outputs are configured here.

CONFIG

1 OUTPUTS

Parameters

Value/selection Description

Output 1

OUTPUT1

...

...

Output 6

OUTPUT6

Configuration of the outputs as


shown in the example Output 1
below.

Factory settings are shown bold.

CONFIG
Function

1 OUTPUTS OUTPUT1

Parameters

Value/selection Description

FUNCTION

NO FUNCT
ANALOG1
...
ANALOG4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
W1
...
W4
CTRLOUT1
CTRLOUT2
VALUE XY
OUT LK1
...
OUT LK8
LOGIN B1
...
LOGIN B8
LOGIC 1
LOGIC 2
MAN.MODE
TRNSMITT

no function*
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint
ramp end value
control deviation
output
setpoint 1
...
setpoint 4
controller output 1**
controller output 2
address value
limit comparator output 1
...
limit comparator output 8
logic input 1
...
logic input 8
logic 1
logic 2
manual mode
supply for 2-wire transmitter
* factory-set on all outputs
except output 1
** factory-set on output 1

Output signal for


analogue output

SIGNAL

0 - 10 V
2 - 10 V
-10- 10V
0 - 20mV
4 - 20mA
-20-20mA

0 10V
2 10V
-10 to +10V
0 20mA
4 20mA
-20 to +20mA

Factory settings are shown bold.

45

7 Configuration level 1
CONFIG
Parameters

1 OUTPUTS OUTPUT1
Value/selection Description

Zero for
analogue signals

STARTVAL

0.

End value for


analogue signals

ENDVALUE

100.

-1999 0 to +9999 digit


-1999 100 to +9999 digit
A physical output signal is assigned
to the value range of an output
variable.
Example:
Setpoint 1 (value range:
150500C) is to be output via the
analogue output (020mA).
i.e.: 150 500C  0 20mA
zero: 150 / end value: 500

H Setting for controller outputs


for cooling.

For 2-setpoint controllers,


the following settings have
to be predefined:
zero: 0 / end value: -100

Output signal for


over/underrange

RANGEFCT

0.

0 101*
101 = last output signal
The output produces a defined
signal.

H If the output is a controller

output, the controller switches


over to manual mode and
produces an output of 0% or
the actuator is closed
(modulating controller).
vSection 7.1 Controller

* for switching outputs:


0 = off, 1 100 = on
Factory settings are shown bold.

7.5 Ramp and profile program function


The ramp or profile program function is activated here.

CONFIG

1 RAMP

Parameters

Value/selection Description

Function

FUNCTION

NO FUNCT no function
RAMP
ramp function
PROGRFCT profile program function

Ramp slope

SLOPE

Unit of slope

UNIT

0.

0999

DEGC/MIN degree Celsius/minute


DEGC/HR
degree Celsius/hour
DEGC/DAY degree Celsius/day
Factory setting are shown bold.

46

7 Configuration level 1
Ramp
function

A rising or a falling ramp function can be implemented. The ramp end-value is


determined by the setpoint input.

H
Profile program
function

The ramp function is interrupted on a probe break or for manual mode.


The outputs react as for over/underrange (configurable).

It is possible to produce a profile program with up to eight segments. When


this function is activated, an additional level (PROGRFCT) appears on the
screen at which the eight segment setpoints (W SEG01 W SEG08)
and the eight segment times (T SEG01 T SEG08) are
programmed.

The program starts at the process value or the program start (adjustable via
the setup program only!). When starting at the process value, the profile is
searched to find a setpoint that corresponds to the process value at the instant of the start. The program sequence starts at this point. If the process
value is outside the profile, a start is made at the first program segment. With
segments that are not required, the segment time must be 0.
Starting the
program

h Start and cancel program with A


or via the logic function

Holding the
program

h Hold and continue program with M


or via the logic function

47

7 Configuration level 1
7.6 Maths and logic module
This menu is shown only with enabled maths and logic module.

CONFIG
Parameters

1 MATHSLOG
Value/selection Description

Mathematics 1

MATHS

Mathematics 2

MATHS

Logic 1

LOGIC

NO FUNCT no function
FORMULA
logic formula (setup program)

Logic 2

LOGIC

NO FUNCT no function
FORMULA
logic formula (setup program)

Configuration of mathematics as
shown in example Maths 1 below.

Factory settings are shown bold.

CONFIG

1 MATHSLOG MATHS

Parameters

Value/selection Description

Function

FUNCTION

NO FUNCT
DIFFERNC
RATIO
HUMIDITY
FORMULA

no function
difference (a-b)
ratio (a/b)
humidity (a;b)
maths formula
(setup program)

Variable a

VAR

ANALOG1
...
ANALOG4
MATHS 1
MATHS 2

analogue input 1
...
analogue input 4
mathematics 1
mathematics 2

Variable b

VAR

ANALOG1
ANALOG2
ANALOG3
ANALOG4
MATHS 1
MATHS 2

analogue input 1
analogue input 2
analogue input 3
analogue input 4
mathematics 1
mathematics 2

Range start

RNGESTRT

-1999.

-1999 to +9999 digit

Range end

RANGEEND

9999.

-1999 to +9999 digit

Definition of a value range for the


result of a mathematical calculation.
If the value range is infringed (above
or below), an out-of range condition
is signalled.
Factory settings are shown bold.

48

7 Configuration level 1
CONFIG
Linearisation

1 MATHSLOG MATHS

Parameters

Value/selection Description

LINTAB

LINEAR
PT100
PT1000
PT500
PT50
CU50
KTY
PTK9
NI100
TC TPE J
TC TPE E
TC TPE K
TC TPE N
TC TPE T
TC TPE B
TC TPE R
TC TPE S
TC TPE U
TC TPE L
CUST LIN
W5RE W26
W3RE W25
W3RE W26

linear
Pt 100
Pt 1000
Pt 500
Pt 50
Cu 50
KTY21-6
Pt K9
Ni 100
Fe-Con J
NiCr-Con E
NiCr-Ni K
NiCrSi-NiSi N
Cu-Con T
Pt30Rh-Pt6Rh B
Pt13Rh-Pt R
Pt10Rh-Pt S
Cu-Con U
Fe-Con L
customized linearisation
W5Re-W26Re
W3Re-W25Re
W3Re-W26Re

Factory settings are shown bold.

Ratio control

The control is always based on variable a.


The maths module forms the ratio of the measurements a and b (a/b) and produces the setpoint for the controller. The ratio of the measured values a and b
can be called up and indicated via the Maths 1 or Maths 2 functions.
The required ratio a/b is programmed in the setpoint input as setpoint (ratio
setpoint).

Humidity
control

The humidity controller receives the process value from a psychrometric


humidity probe through the mathematical linkage of wet bulb and dry bulb
temperatures.
Variable a - dry bulb temperature
Variable b - wet bulb temperature

49

7 Configuration level 1
Formula input

- The formula character string consists of ASCII-characters and has a maximum length of 70 characters.
- The formula can only be entered in the setup program.
- The formulae can be entered freely according the the usual mathematical
rules.
- Spaces can be inserted in the formula character string without restriction.
No spaces are allowed within function designations, variable names and
constants.

Mathematical
formula

Mathematical signs and functions


Priority
high

Mathematical sign/function

Note

()

brackets

SQRT, MIN, MAX, LOG, LN, SIN, functions


COS, TAN, ABS, EXP, INT, FRC

low

**

exponent (xy)

+, -

sign

*, /

multiplication, division

+, -

addition, subtraction

Variables

50

Variable name

Note

E1

E4

analogue input 1

M1
M2

mathematics 1
mathematics 2

process value

WR

controller setpoint

WE

ramp end value

XW

control deviation

output

W1

W4

setpoint 1 (operating level)

setpoint 4 (operating level)

YH

output heating

YK

output cooling

ADRA

storage address (analogue)

TEMP

temperature at terminals

T0

sampling time

RXK1
RXK2

controller output 1
controller output 2

analogue input 4

7 Configuration level 1
Variable name

Note

ADRZ

storage address: time

ADRB

storage address (binary)

LK1

LK8

output limit comparator 1

output limit comparator 8

B1

B8

logic input 1

L1
L2

logic 1
logic 2

HAND

manual mode

logic input 8

Functions
Syntax

Function

SQRT(a)

square root of a
Examples: SQRT(E2)
SQRT(13.5+E3)

MIN (a1, a2 )

returns the smallest value of a series of arguments


Examples: MIN(3, 7) (returns the value 3)
MIN(E1, E2, E3, 0.1)

MAX (a1, a2 )

returns the largest value of a series of arguments


Examples: MAX(3, 7) (returns the value 7)
MAX(E1, E2, E3, 0.1)

LOG(a)

logarithm to base 10
Examples: LOG(1000) (returns the value 3)
LOG(E1/100)

LN(a)

logarithm to base e
Examples: LN(2.71828128) (returns the value 1)
LN(E1/100)

SIN(a)

sine of a
a in degrees (0 360C)
Examples: SIN(90) (returns the value 1)
SIN(E1*360/100)

COS(a)

cosine of a
a in degrees (0 360C)
Examples: COS(180) (returns the value -1)
COS (E1*360/100)

TAN(a)

tangent of a
a in degrees (0 360C)
Examples: TAN(45) (returns the value 1)
TAN(E1*45/100)

ABS(a)

absolute value of a
Examples: ABS(-12) (returns the value 12)
ABS(13.5+E3)

51

7 Configuration level 1

Logic formula

Syntax

Function

EXP(a)

exponential function ea
Examples: XP(1) (returns the value 2.718)
EXP(E1/100)

INT(a)

integer portion of a
Examples: INT(8.3) (returns the value 8)
INT(E1)

FRC(a)

decimal portion of a
Examples: FRC(8.3) (returns the value 0.3)
FRC(E1)

Logic operators
Priority
high

low

Operator

Note

()

brackets

NOT, !

negation

AND, &

AND linkage

XOR, ^

exclusive OR linkage

OR,

OR linkage

Variables
Variable names

Note

RXK1
RXK2

controller output 1
controller output 2

ADRB

storage address (binary)

Lk1

LK8

output limit comparator 1

output limit comparator 8

B1

B8

logic input 1

logic input 8

HAND

manual mode

Edge recognition

52

Edge

Note

variable is TRUE only with rising edge (e. g. /B1)

variable is TRUE only with falling edge (e. g. \B1)

7 Configuration level 1
Constants

Enabling maths
and logic
module

Constant name

Note

TRUE

logic 1

FALSE

logic 0

The maths and logic module can be enabled through a code via the setup program.
v Extras r Enabling extra Codes

7.7 Display
The two display configurations are set here, as well as the time-out during
configuration at the levels.

CONFIG
Parameters
Configuration 1

DSPCONF1

Configuration 2

DSPCONF2

Time-Out

TIMEOUT

Automatic
display switching

SCROLL

Language for
instrument texts

LANGUAGE

1 DISPLAY
Value/selection Description
Configuration of the displays as
shown in the example
Configuration 1 below.
30.

0309999sec
0 = time-out OFF
Interval after which an automatic
return to normal display occurs if no
key is pressed.

0.

-1 09999sec
0 = automatic changeover OFF
-1 = changeover via keypad is not
possible
Interval between the changeover of
the two display configurations.

DEUTSCH
ENGLISH
FRANCAIS
ESPANOL

German
English
French
Spanish
This feature is available from instrument SW version 050.03.01.

Factory settings are shown bold.

53

7 Configuration level 1
Assignment
of the displays

Display 1
Display 2
Display 3

CONFIG

1 DISPLAY DSPCONF1

Parameters
Display 1
Display value

DISPLAY1
DISPLVAL

Decimal point

DECPOINT

Display 2
Display value

DISPLAY2
DISPLVAL

Decimal point

DECPOINT

Value/selection Description
NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL

no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value

XXXX.

XXXX.X.XXX

NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL

no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value

XXXX.

XXXX.X.XXX

Factory settings are shown bold.

54

7 Configuration level 1
CONFIG

1 DISPLAY DSPCONF1

Parameters
Display 3
Display value

DISPLAY3
DISPLVAL

Value/selection Description
NO FUNCT
ANALOG 1
...
ANALOG 4
MATHS 1
MATHS 2
PV
SETPOINT
RAMPENDV
CNTRLDEV
OUTPUT
VALDISPL
LIMITC
BARG Y
BARG XW
TXTDISPL

no function
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
process value
setpoint (present)
ramp end value
control deviation
output
display of a storage address value
limit comparators (switching states)
bar graph output
bar graph control deviation
text display
switching states of
limit comparators: 8 7 6 5 4 3 2 1
00000000
bar graph output:
1-setpoint ctrl.
0%
100%
and prop. ctrl.

2-setpoint ctrl. -100% 0% 100%

bar graph control deviation:


50C
0C 50C

Decimal point

DECPOINT

XXXX.

XXXX.X.XXX

Factory settings are shown bold.

Decimal point

If the value to be displayed can no longer be represented with the programmed decimal place, then the number of decimal places will be automatically reduced. If, subsequently, the measurement becomes smaller then
the number will be increased to the programmed decimal point value.

55

7 Configuration level 1
7.8 Logic functions
Functions are assigned here to the logic signals of the logic inputs, limit
comparators and the logic module.

CONFIG
Parameters
Logic input 1

LOGIN

...

...

Logic input 8

LOGIN

Limit comparator 1 OUT


...

Value/selection Description
B1
B8

LK1

...

Limit comparator 8 OUT

1 LOGICFCT

LK8

Logic 1

LOGIC

Logic 2

LOGIC

NO FUNCT
TUNESTRT
TUNESTOP
MAN.MODE
MANINHBT
RAMPSTOP
RAMP OFF
W SWITCH
X SWITCH
P SWITCH
KEYINHBT
LEVINHBT
TXTDISPL
DISPLOFF

no function
start self-optimisation
cancel self-optimisation
changeover to manual mode
manual mode inhibit
ramp stop/profile programm stop
ramp off/profile programm abort
setpoint switching
process value switching
parameter set switching
key inhibit
level inhibit
text display*
all displays off/acknowledgement of
limitcomparators
* A maximum of 10 texts are input
and assigned to the logic functions
in the setup program
The functions are active when the
contact is closed or the switching
status is ON.
All displays off:
- all displays are switched off
- limit comparators are acknowledged
Text display and all displays off:
response according to priority list

Switching
action

Factory settings are shown bold.

The logic functions are activated via the logic inputs (floating contacts (switches/relay contacts)), limit comparators or logic.

The functions are divided into two groups:

56

7 Configuration level 1
Edge-triggered
functions

The logic function reacts to switch-on edges.


The following functions are edge-triggered:
- start/stop self-optimisation
- acknowledge limit comparators

State-triggered
functions

The logic function reacts to ON or OFF switching states.

Combined
logic functions

A combination of two control variables


(logic inputs, limit comparators and logic) is used to implement the functions
setpoint/process value switching.

- all other functions

Any control variable can be selected.


The states Z1 Z2 are assigned to the
control variables in descending order
of the control variables (see list on the
right).

Example:
The process value is to be selected via
one logic input and the state of one limit
comparator.
This results in the following assignment:
Z1 - logic input 1
Z2 - limit comparator 1

Setpoint switching

Process value switching

Z2

Z1

setpoint 1/external setpoint/


program

configured controller process value

setpoint 2

analogue input 2

setpoint 3

analogue input 3

analogue input 4
1 = contact closed /ON

setpoint 4
0 = contact open /OFF

If switching between two setpoints or process values only is required, then only one logic function has to be configured.
If more than two logic functions are configured to setpoint switching (process value switching), then only the first two (see list
Control variable - State) are significant.

57

7 Configuration level 1
7.9 Interface
CONFIG

1 INTERFCE

Parameters

Value/selection Description

Protocol type

PROTOCOL

MODBUS
MODINT

MODbus/Jbus
MODbus int

Data format
Baud rate

DATAFMT
BAUDRATE

1200
2400
4800
9600
1920

1200 baud
2400 baud
4800 baud
9600 baud
19200 baud

Parity

PARITY

NONE
ODD
EVEN
ZERO

no parity
odd parity
even parity
zero parity

Stop bit

STOPBIT

1
2

1 stop bit
2 stop bits

Unit address

UNITADDR

0.

01 254

Minimum
response time

MIN

0.

0500msec

TIME

Minimum period of time that elapses


between the request of an instrument within a data network and
the response of the controller.
Factory settings are shown bold.

58

Interface description B 703570.2


Interface description B 703560.2.3

8 Optimisation
8.1 Self-optimisation
Procedure

Self-optimisation SO establishes the optimum controller parameters for PID or


PI controllers.
Depending on the controller type, the following controller parameters are
defined:
Reset time (Tn1, Tn2), derivative time (Tv1, Tv2), proportional band (Xp1, Xp2),
switching cycle time (Cy1, Cy2), filter time constant (dF)
The controller selects one of two procedures (a or b) in accordance with the
size of the control deviation.
b) SO at setpoint
a) SO in the start-up phase
Start of SO

Start of SO

Switching
line

The types of the controller outputs have to be defined for selfoptimisation.


v Section 7.1 Controller

Start of selfoptimisation

Self-optimisation is automatically terminated, or can be cancelled.

Starting self-optimisation is not


possible with active level inhibit.

59

8 Optimisation
8.2 Checking the optimisation
Start-up
procedure

The optimum adjustment of the controller to the process can be checked by


recording the start-up with the control loop closed. The diagrams below
indicate possible maladjustments and how these can be corrected.

Control
response

The control response of a third-order control loop of a PID controller is shown


as example. However, the procedure for adjusting the controller parameters
can also be applied to other control loops.

60

Xp too large

Tn, Tv too small

Xp too small

Tn, Tv too large

Cy too large

optimum
setting

8 Optimisation
8.3 Fuzzy parameters
In addition to the algorithms for the
various controller structures, the controller software also includes a fuzzy
module. This can be used to improve
both the control and the disturbance
response of controllers with I-action.
When the fuzzy module is activated,
the output y is made up of the controller output and the output signal of
the fuzzy module.

The parameter Fc1 affects the intensity of the fuzzy signal:


Fc1 = 0:
Fuzzy module not activated
0<Fc1 100: Fuzzy module activated
If the fuzzy module activated by Fc1 makes corrections to the output y,
the reset time Tn is influenced during correction.
The parameter Fc2 is used to adjust the degree of influence on the reset time
Tn.
Fc2 = 0:
no influence on Tn
0<Fc2 100: influence on Tn
When supplied, and also after self-optimisation, the fuzzy parameters are set
to Fc1 = 0 and Fc2 = 30.
The fuzzy module can be activated at any time by setting Fc1 > 0.
The setting Fc2 = 30 is suitable for many applications. The optimum setting
can be determined with the aid of the table below.

61

8 Optimisation
Action Reaction

Fc1

Fc1

Fc2

disturbance amplitude
reduced, stabilisation
time increased
disturbance amplitude
increased, stabilisation
time reduced
stabilisation time reduced

Fc2

stabilisation time
increased

If the fuzzy module is inactivated (Fc1=0), Fc2 is also ineffective


The action and sensitivity of the fuzzy parameters depend largely on
the process to be controlled.
The influence is greater in the case of proportional controllers than
with switching controllers.

62

9 Retrofitting of cards
The following steps are necessary for retrofitting cards:

Only qualified personnel are permitted to retrofit cards.

E rostatic charges during fitting and removal. Carry out the card change
The cards can be damaged by electrostatic discharge. Avoid electon a workbench which is earthed.

Identifying the
card

h Identify the card by the sales no. or part no. that is glued onto the
packaging.

The instrument is fitted from device software version 50.02.XX on with a


new type of analog input card. If analog input cards are retrofitted, it
must be noted that they cannot be operated together with the older type
of card (i.e. do not mix card types). Please note also that an update of
the setup program may be required in order to carry out the configuration through the setup program.
The Software-Version appears on the Display if the keys PGM +arrow
up are pressed.

Cards

Code Sales No.

Card No.

Analogue input 3 and 4:


Universal input
up to software version 50.01.XX
from software version 50.02.XX on

1/2
1/2

70/00366099
70/00490339

358457
483509

1
2
3
4
5
6

70/00366100
70/00366101
70/00366102
70/00366103
70/00366104
70/00366105

358444
358452
358445
358447
358449
358447

70/00366106

358450

RS422/485 interface

54

70/00366107

358443

PROFIBUS-DP

64

70/00375280

368705

Outputs/logic inputs:
Relay (changeover contact)
Solid-state relay 230V 1A
Logic 0/5V
Logic 0/22V
Analogue output
Supply for
2-wire transmitter
Two logic inputs

63

9 Retrofitting of cards
Configuring
the analogue
input

The retrofitable analogue inputs 3 and 4 are supplied ex-factory as universal


input. They can be reconfigured as voltage input for certain measuring ranges
(-10/0/210V and -1V1V).
h Re-arrange push-on jumpers as in the diagram
Universal input
(remaining ranges)

Voltage -10/0/210V
-1 1V

The standard analogue inputs 1 and 2 are configured ex-factory as universal input or as voltage input for certain measuring ranges (see type
designation or order details). They can also be reconfigured:
Universal input
(remaining ranges)

Voltage -10/0/210V
-1 1V

1
1 = Analogue input 1
2 = Analogue input 2

64

9 Retrofitting of cards
Removing the
controller
chassis

h Pull off setup plug

Assigning the
slot

h Determine the corresponding slot for the card

h Press together the knurled areas on


the panel top and bottom (or left and
right with landscape format) and pull
out the controller chassis.

- Type 703570 only

65

9 Retrofitting of cards

Inserting the
card

h Pull off the guide plate (1)

Inserting the
controller
chassis

h Fit on the guide plate

66

h Insert the card into the guide until the projections on the card snap into
the notches provided (2).

h Push the controller chassis into the case until the lugs (underneath the
knurled area) snap into place.

10 Interfaces
10.1 RS422/485 interface
The controller can be integrated into a data network via the interface. The following applications can be implemented, for example:
- process visualisation
- system control
- generating a report
- configuration

The bus system is designed on the master-slave principle. A master computer


can address up to 31 controllers and instruments (slaves). The interface is a
serial interface to the RS422 and RS485 standards.
The following data protocols are possible:
- MODbus/Jbus protocol

Interface description B 703570.2

67

10 Interfaces
10.2 PROFIBUS-DP
Fieldbus

The controller can be incorporated into a fieldbus system according to the


PROFIBUS-DP standard, via the PROFIBUS-DP interface. This PROFIBUS
variant has been especially designed for the communication between automation systems and distributed peripheral devices at the fieldbus level, and is optimised for speed.

Data
transmission

Data transmission is performed serially, according to the RS485 standard.

GSD generator

With the aid of the project design tool included in the delivery (GSD generator;
GSD = Device Base Data), a standardised GSD file is created, which serves to
integrate the controller into the fieldbus system, through the selection of characteristic controller features.

68

Interface description B 703560.2.3

11 Accessories
11.1 External relay module/logic module ER8/EL8
By using the external relay module ER8 or logic module EL8, the controller can
be expanded by eight relay outputs (changeover contacts) or logic outputs (0/
12 V). Communication with the controller occurs via the RS422/485 interface.
All controller signals for switching outputs can be output by the module.
Configuration is only possible through the setup program.
v Section 7.4 Outputs

H
Connection

If the module ER8/EL8 is connected to the interface, no further


communication is possible via the interface.

The electrical connection is carried out like the connection to an RS485 interface (the figure below shows ER8; see also Operating Manual ER8/EL8,
B 703564).

PE L1 N

141

142

143

241

242

243

33411

33422

441

33433

442

443

(L+) (L-)

Power

K1

K2

K3

K4

K5

K6

K7

K8

Error

541

Configuring
the module

542

543

641

642

643

741

742

743

841

842

843

RxD RxD
TxD TxD GND
97 98 99

Type 703570: Terminal strip 2, terminal

3 4 5

Type 703575: Terminal strip 2, terminal

3 4 5

h Activate the relay module via the setup program


Edit r Settings only via setup r Expanded configuration
This activates the menu Edit r External relay module.
h Configure the module
The functions are related to the relay module, but they also apply to the
logic module (Off = 0 V; On = 12 V).

If the setup plug is connected to the controller, the module will not be
operated and the outputs are in idle position (logic outputs: 0 V).

69

11 Accessories
11.2 Setup program with commissioning software
Setup program

A setup program for Windows NT4.0/2000/XP/Vista/7 (32/64 bit) is available


for easy configuration of the controller.
Hardware requirements:
- 512 Mbyte RAM
- 50 Mbyte available on hard disk

- CD-ROM drive
- 1 free serial interface or USB interface

The program shows the current configuration as a list in the background. The
corresponding entry template is called up by double-clicking on the list, or via
the menus.

Some controller functions can only be configured via the setup program:
- Customized linearisation (input of a linearisation table)
- Display brightness of display 3
- Switch off code request (extended configuration)
- Configure relay module
- Alter passwords
Commissioning
software

The commissioning software is a part of the setup program and is available for
adapting the controller to the control loop, optimally and conveniently.
Different process variables (e.g. setpoint, process value, control deviation, signals from the controller outputs) can be displayed graphically. The controller
parameters can be altered and transferred to the controller via the setup/
RS422/485 interface.
Data recording is limited to 48 hours.

70

12 Appendix
12.1 Technical data
Thermocouple input
Range1

Designation
Fe-Con
Fe-Con
Cu-Con
Cu-Con
NiCr-Ni
NiCr-Con
NiCrSi-NiSi
Pt10Rh-Pt
Pt13Rh-Pt
Pt30Rh-Pt6Rh
W5Re-W26Re
W3Re-W25Re

L
J
U
T
K
E
N
S
R
B

-200 +900C
-200 +1200C
-200 +600C
-200 +400C
-200 +1372C
-200 +910C
-100 +1300C
-50 +1768 C
-50 +1768 C
0 1820 C
0 2320 C
0 2400 C

EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584

Cold junction

Meas. accuracy

Ambient
temperature error

0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%2
0.25%
0.25%

100 ppm per C


100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C

Pt100 internal, external or constant

1. The specifications refer to an ambient temperature of 20C.


2. within range 300 1820C

Resistance thermometer input


Designation

Type of connection

Range

Meas. accuracy

Ambient
temperature error

Pt100

EN 60751

2-wire/3-wire

-200 +850C

0.05%

50 ppm per C

Pt 50,500, 1000

EN 60751

2-wire/3-wire

-200 +850C

0.1%

50 ppm per C

2-wire/3-wire

-50 +200C

0.1%

50 ppm per C

2-wire/3-wire

-60 +250C

0.05%

50 ppm per C

-50 +150C

1.0%

50 ppm per C

Cu50
Ni100

DIN 43760

KTY21-6

2-wire

PtK9

2-wire

lithium-chloride sensor
max. 30 per conductor in 2-/3-wire circuit

Sensor lead resistance


Measuring current

250A

Lead compensation

not required for 3-wire circuit. For 2-wire circuit, lead compensation can be provided in the software
by process value correction.

Input for standard signals


Designation

Range

Voltage

0 10V,
-10 to +10V,
-1 to +1V,
0 1V,
0 100mV,
-100 to +100mV,

input resistance RE > 100k


input resistance RE > 100k
input resistance RE > 100k
input resistance RE > 100k
input resistance RE > 100k
input resistance
RE > 100k

4 20mA, voltage drop 1V


0 20mA, voltage drop 1V

Current

Meas. accuracy

Ambient
temperature error

0.05%
0.05%
0.05%
0.05%
0.05%
0.05%

100 ppm per C


100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C
100 ppm per C

0.1%
0.1%

100 ppm per C


100 ppm per C

min. 100 , max. 10k

Potentiometer

Measurement circuit monitoring1


Transducer

Over/underrange

Probe/lead short circuit

Probe/lead break

Thermocouple

Resistance thermometer

Voltage

2 10V
0 10V

Current

4 20mA
0 20mA

= recognised

-= not recognised

1. In the event of an error, the outputs move to defined states (configurable).

Standard version

71

12 Appendix
Outputs
Relay
contact rating
contact life
contact protection circuit
Logic
current limiting

changeover contact
3A at 250VAC resistive load
150 000 operations at rated load
56/15nF between common-make/common-break
0/5V
20mA

or

Solid-state relay
contact rating
protection circuit

0/22V
30mA

1A at 230V
Varistor

Voltage
output signals
load resistance

-10 to +10V / 0 10V / 2 10V


Rload 500 min.

Current
output signals
load resistance

-20 to +20mA / 0 20mA / 4 20mA


Rload 450 max.

Supply for 2-wire transmitter


voltage
current

22V
30mA

Controller
Controller type

Single-setpoint controller,
double-setpoint controller, modulating controller, proportional controller,
proportional controller with integral actuator driver

Controller structures

P/PD/PI/PID/I

A/D converter

resolution better than 15 bit

Sampling time

210msec

Electrical data
Supply (switched mode power supply)

110 240V +10/-15% AC 48 63Hz


20 30V DC/AC 48 63Hz

Test voltages (type test)

to EN 61010, Part 1
overvoltage category II, pollution degree 2

Power consumption

24VA max. for Type 703570


14VA max. for Type 703575

Data backup

EEPROM

Electrical connection

at the rear via screw terminals,


conductor cross-section up to 2.5mm2
and core-end sleeve (length: 10mm)

Electromagnetic compatibility
Interference emission
Immunity to interference

EN 61326-1
Class A - only for industrial use Industrial requirements

Safety standards

to EN 60730-1 for Type 703570


to EN 61010-1 for Type 703575

Housing
Housing type
Type
Bezel in mm
Depth behind panel in mm
Panel cut-out in mm

plastic housing for panel mounting (indoor use) acc. to IEC 61554
703575/1...

703575/2...

703570/0...

48 x 96 (portrait)

96 x 48 (landscape)

96 x 96

130

130

130

45+0.6 x 92+0.8

92+0.8 x 45+0.6

92+0.8 x 92+0.8

Ambient/storage temperature range


Climatic conditions

-5 to 55C / -40 to +70C


rel. humidity not exceeding 95% annual mean, no condensation

Site altitude

up tp 2000 m above sea level

Operating position

unrestricted

Protection
Weight (fully fitted)

Standard version

72

acc. to EN 60529, front IP65, rear IP20


approx. 420g

approx. 420g

approx. 730g

12 Appendix
Approvals/marks of conformity
Mark of
conformity

Testing laboratory

Certificates/certification
numbers

Test basis

valid for

DIN

Deutsche Industrie Norm

Registernummer TR1117

DIN EN 14 597

DICON 500

GL - Hardware
GL - Software

Germanischer Lloyd

Certificate
No. 15 694-00 HH

GL-Baumusterprfung
Kategorie C, EMC1

DICON 500

c UL us

Underwriters Laboratories

E 201387

UL 61010-1
DICON 400/500
CAN/CSA-C22.2 No. 61010-1

73

12 Appendix
12.2 Alarm messages and display priorities in the normal display
Priority

Display
Matrix

high

7-segment

Possible error /
notes

Assignment

Error handling
check/repair/replacement

controller

replace controller when


initialisation is longer than 5sec

+LEDs

8888.
8888. (blinks)

watchdog or power-on will trigger


initialisation (reset)

(no display)

(no display)

- logic function All displays off is - no error


configured and active
- controller
- controller faulty
- supply

- open logic input


- replace controller
- check supply

- supply faulty

BREAK

BREAK

E1

9999. (blinks) - probe/lead break of resistance


or ( )*

E4

thermometer (connection 1.9,


1.11, 1.4, 1.8, 2.10, 2.12, 3.20,
3.12) or standard-signal input

external
signal
generator

- probe/lead short-circuit at
standard-signal input

- check probe for break or shortcircuit


- check probe connection and
terminals
- check lead

- overrange at standard-signal
input
- underrange at standard-signal
input

ORANGE

ORANGE

9999. (blinks) - overrange of resistance


or ( )*

URANGE

URANGE

-1999.
(blinks)

or ( )*

thermometer and thermocouple


input

external
signal
generator

- is the medium to be measured


within the measuring range (too
hot - too cold?)

- probe/lead break of thermocouple input

- check probe for break and shortcircuit

- underrange of resistance
thermometer and thermocouple
input

- check probe connection and terminals


- check lead

- probe/lead short-circuit of
resistance thermometer
- probe/lead break of resistance
thermometer 1.10, 1.7, 2.11,
3.11

ORANGEM1

( )*

overrange (maths module)


(calculation result > range end)

( )*

underrange (maths module)


(calculation result < range start)

MATH1

ERR ( )*

check maths formulae

ERR

mathematical error
(violation of mathematical rules;
impermissible values)

controller

MATH2

( )*

logic error
(violation of mathematical rules)

controller

check logic formulae

( )*

error on relay module


(not applicable with GL approval)

BUSERROR

( )*

no communication

periphery

check periphery

(Text)

(Text)

( )*

text display (logic input 1)

text display (logic input 8)

(Text)

(Text)

( )*

text display (limit comparator 1)

text display (limit comparator 8)

(Text)

( )*

text display (logic 1)

( )*

text display (logic 2)

ORANGEM2
URANGEM1
URANGEM2

LOG1

ERR

LOG2

ERR

ER8

(Text)

ERR

* display according to configuration


1. can be acknowledged
(continued on next page)
low

74

12 Appendix
Priority

Display
Matrix

high

7-segment

Assignment

Error handling
check/repair/replacement

SOACTIVE

( )*

self-optimisation has been


activated

----

----

measurement input not available


or not configured

controller

- configure measurement input

or ( )*
low

Possible error /
notes

(display according to configuration)

- retrofit card
-

* display according to configuration

Acknowledging alarm messages


On pressing the E key, the message disappears.

75

76

Pt100

Example:

No. Transducer

20500C

Measuring
range

Machinery room
boiler
temperature 1

Measurement
site

Measurement input

Output
100%

Output 1

Output 2

Limit comparator off

Output 3

Output 4

Output 5

Response of the outputs in the event of error


Output 6

12 Appendix

Table: Assignment of the measurement inputs/response of the outputs in the event


of an error (to be filled in by the user)

12 Appendix
12.3 Character set for matrix display
The special characters for text entries in the setup program are shown below.
They are entered from the keys using the key combination Alt + XXX

200 210 reserved for bar graph display

77

12 Appendix
12.4 Instrument features (configuration level 2)
The software version and the hardware features of the process controller are
shown here
CONF

Parameters

Value/selection

Description

Version

VERSION

50.0X.0X

version number

VDN number

VDN

STANDARD
XXX.XXXX

standard version
VDN number

NO.

(alteration to the standard


version)
Analogue input 3
Analogue input 4

IN3
IN4

Analogue inp. 1 10V


Analogue inp. 2 10V
Analogue inp. 3 10V
Analogue inp. 4 10V

IN1
IN2
IN3
IN4

Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6

OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6

10V
10V
10V
10V

NO
YES

not available
available
universal input

NO
YES

not available
available
voltage input
-10/0/2 10V

NO
RELAY
SSRELAY
ANOUTPUT
LOGIC 5V
OUTP 22V
LOGIN

not available
relay
solid-state relay
analogue output
logic output 5V
logic output 22V or
voltage output for
2-wire transmitter
two logic inputs

Setup interface

SETUP

NO
YES

not connected
connected

Interface

INTERFCE

NO
RS422/485
PROFIBUS

not available
RS 422/485
PROFIBUS-DP

Mathematics

MATHLOG

NO
YES

not available
available

78

12 Appendix
12.5 Notes for instruments with Germanischer Lloyd (GL) approval
The information below is intended to supplement or replace the details that
have already been given.

12.5.1 Technical data


Ambient conditions according to application category C for enclosed areas
Temperature

-5 to 55C

100% r. h.
0.7g

Relative humidity
Vibration

Electromagnetic compatibility
The electromagnetic compatibility corresponds to the GL guidelines for type
examinations (10.97).

12.5.2 Alarm messages


vSection 12.2

12.5.3 Inhibits
All levels are inhibited by codes. Alterations, whether accidental or deliberate,
cannot be made easily. The operating level is not inhibited by a code. In this
case, it is possible to lock the entire keypad via a logic contact (e.g. keyswitch).
v Section 5.3

12.5.4 Manual mode


vSection 5.6

Manual mode is only possible with a fully operational instrument!

12.5.5 Additional notes

If servicing is required, the instrument has to be sent back to the


main factory.
In accordance with the regulations of the Germanischer Lloyd, certain applications require the availability of a reserve instrument.

79

12 Appendix

H
H

80

The instrument can only be used with restrictions on the bridge,


since a continuous dimming of the display brightness is not possible!

it is recommended that a print-out of the setup program be kept on


site, together with the technical documentation for the controller
(can be requested, if necessary).

13 Index
A
Accessories 10
Action 38
Alarm messages 74
Analogue input 9, 40
configuring 64
Approvals 9

B
Basic type extension 9

C
Card
identifying 63
retrofitting 63
Code request 25
Cold-junction temperature
constant 42
external 42
Configuration level 1 25
Configuration level 2 25
Connection diagrams 1620
Control direction 35
Controller 35
Controller chassis, removal of 14
Controller type 35

Front panel, cleaning of 13


Fuzzy control 36

H
Humidity control 49

I
Inputs 40
of controller 35
Installation notes 15
Instrument name 55
Interface 9
Isolation 21

K
Key designation 23

L
Language for instrument texts 53
Levels and menus 26
Limit comparator 37
absolute 39
relative 39
Limit comparator functions 37
Limit value 38
Linearisation 41, 49
Logic formula 52
Logic functions 56
combined 57
Logic input 56

Data format 58
Deadband 36
Decimal point
shift 26
Dimensions 1112
Display 53
Display end 42
Display start 42
Display switching 29
automatic 53
Displays and controls 23

Manual mode 28, 36


Manual output 36
Mathematical formula 50
Maths and logic module 9, 48
Measurement circuit monitoring 71
Measurement correction 41

Edge-to edge mounting 13


End value
for analogue signals 46
External relay module 69

Normal display 25

F
Filter time constant 42
Fitting in position 13
Formula input 50

O
Operating level 25, 30
Operating modes 24
Optimisation 60
Output 9, 45
self-optimisation 36

81

13 Index
P
Parameter level 25, 31
Parameter set
active 32
Profile program
holding 47
starting 47
Profile program function 25, 4647
Protocol type 58
Pulse function 38

R
Ramp function 4647
Ramp slope 46
Range end 42, 48
Range start 42, 48
Ratio control 49
Recalibration
customized 43
Response time
minimum 58

S
Selection 27
Self-optimisation 59
Setpoint
altering 27
Setpoint limits 36
Setpoint switching 27

82

Supply frequency 40
Switching action 56
Switching differential 38
Switch-on delay 38

T
Technical data 71
Time 48
Time input 27
Time-out 25, 53
Transducer 40
Type designation 9

U
Unit 40
of slope 46
Unit address 58

V
Value input 26
Variable a 48
Variable b 48

Z
Zero
for analogue signals 46

JUMO GmbH & Co. KG

JUMO Instrument Co. Ltd.

JUMO Process Control, Inc.

Street address:
Moritz-Juchheim-Strae 1
36039 Fulda, Germany
Delivery address:
Mackenrodtstrae 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax:
+49 661 6003-607
E-mail: mail@jumo.net
Internet: www.jumo.net

JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax:
+44 1279 635262
E-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk

6733 Myers Road


East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax:
315-437-5860
E-mail: info.us@jumo.net
Internet: www.jumousa.com

You might also like