Honeywell V4043H Motorised Zone Valve
Honeywell V4043H Motorised Zone Valve
Honeywell V4043H Motorised Zone Valve
Application
The V4043H valve has been designed to control the flow of
water in iron and copper pipe systems. Although specifically
designed for small bore central heating systems, the valve
can be used in commercial and industrial applications.
Specifications
Voltage: 220-240V ~ 50Hz
Power consumption: 6W
Lead supplied: 1 metre, 5 core
Operating temperature range: +5 to +88°C
Maximum ambient temperature: +52°C
Pipe fitting sizes:
22mm & 28mm compression fitting, 3/4" & 1" BSP
Dimensions and KV values: See diagrams
Spares available
Powerhead Part No. 40003916-001
Motor Part No. 40002737-003
Ball & ‘O’ Ring Kit Part No. 272742A CARD
Installation
V4043H incorporates a
manual lever, the lever
should normally be in
‘AUTO’ position, but can be
moved to ‘MAN OPEN’ AUTO MAN
OPEN
Flow
position for system
draindown and filling Characteristics
purposes only.
Before fitting the valve, read
through the plumbing and
wiring instructions.
This product MUST be
installed by a competent person. The installation MUST
conform to I.E.E. Regulations and with The Electricity at
Work Regulations.
A Class ‘A’ switch (having contact separation of at least
3mm in all poles) must be incorporated in the fixed wiring
as a means of disconnecting the supply. The system must
be appropriately fused.
Plumbing
AUTO
OPEN
MAN
Wiring
The wiring diagram above shows relevant connections to a Honeywell junction box (Part No. 42002116-001).
Ensure that each numbered, lettered or coloured wire is connected to the correct terminal in the junction box.
Make sure all connections are good and all terminal screws are firmly tightened.
Notes:
a Wiring diagram shows connections to a programmer with separate control of heating and hot water.
b If single channel time clock is used, connect switched live from time clock to terminal 4 or 6 at junction box,
then link terminal 4 to terminal 6 with a link wire.
Whilst Honeywell takes all practicable steps to design and manufacture its products to comply with the requirements of the Health and Safety at Work Act 1974, all products
must be properly used and Purchasers are reminded that their obligations under the Act are to ensure that the installation and operation of such products at a place of work
should be safe and without risk to them.
Honeywell reserve the right at any time and without notice to change any product or information contained in this publication.
The wiring diagrams and installation instructions in this publication are provided for guidance purposes when installing recognised standard systems only. Any application of
this product not shown here, or any deviation from these instructions, is neither recommended nor advised. Any such application or deviation should be referred to
Honeywell for technical assistance.