CB Acdb

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 2

Respon

sibilities
Legend
CSD

SITE TEST REPORT

Date :
Customer:
SEC-EOA

Contractors name:

SEC EOA Contract No. :

Name of substation:

Page 1 of 2

CIRCUIT BREAKER OF ACDB


Panel No:

Equip. No.:

Dwg. Ref.:

Record No.:

1. GENERAL DATA AND INFORMATION.


S.No:
Panel No:
Make
Type

Circuit Reference
Rated Voltage
Rated Current
Rated Frequency

2. MECHANICAL CHECKS AND VISUAL INSPECTION.


ITEM
1.
2.
3.
4.
5

DISCRIPTION
Inspect for any physical damage or defects.
Verify correct spring status indication (Spring charged/ spring discharged)
Check name plate information for correctness.
Check manual spring charge operation.
Check for correct breaker position indication (C.B open/ Closed)

DONE

REMARKS

3. ELECTRICAL TEST.
a. CONTACT RESISTANCE TEST.

MEASURED CONTECT RESISTANCE

INJECTED TEST CURRENT


C.B CLOSED POSITION

R-R

Y-Y

B-B

N-N

b. INSULATION RESISTANCE TESTS:


Applied Voltage ____5000_____ V DC
CB CONDITION

Time Duration _________ Minute

R- (Y+B+N+E)

Y- (R+B+N+E)

B- (R+Y+N+E)

N- (R+Y+B+E)

R-R

Y-Y

B-B

N-N

CLOSED
CB CONDITION
OPEND
TRIP TIMING TEST.
(i) LONG TIME PROTECTION.
DATE:
TESTING ENGINEER

CSD- Engineer

Signature: ________________

Signature: ________________

Name

Name

: ________________

: ________________

SITE TEST REPORT

Date :
Customer:
SEC-EOA

Contractors name:

SEC EOA Contract No. :

Name of substation:

Page 2 of 2

CIRCUIT BREAKER OF ACDB


Panel No:

Equip. No.:

LONG TIME

R
e
s
p

CURRENT (A) Ir

Dwg. Ref.:

SETTING TIME
(Sec)

INJECTED
CURRENT (A)

Record No.:
TRIP TIME (tr) Sec)
EXPECTED TIME
ACTUAL TIME
(Sec)
(Sec)

Longtime current (Ir) = Circuit breaker rating (In) X rating plug setting.
Time delay (s)

tr at 6 x Ir
tr at 1.5 x Ir

Accuracy = 0 to -20%
Accuracy = 0 to -30%

(ii) SHORT TIME PROTECTION.


SHORT TIME
CURRENT (A) Isd

SETTING TIME
(ms)

INJECTED
CURRENT (A)

TRIP TIME (tr) (ms)


EXPECTED TIME
ACTUAL TIME
(ms)
(ms)

Short time current (Isd) = Ir X rating plug setting

Time delay (s)

Accuracy

10

(iii) GROUND -FAULT PROTECTION.


GROUND TIME
SETTING CURRENT (A)

SETTING TIME
(ms)

INJECTED
CURRENT (A)

Ground-Fault current (Ig) = Circuit breaker rating (In) X rating plug setting.

TRIP TIME (tr) (ms)


EXPECTED
ACTUAL TIME
TIME (ms)
(ms)

Accuracy 10

1- TEST EQUIPMENT USED.

DATE:
TESTING ENGINEER

CSD- Engineer

Signature: ________________

Signature: ________________

Name

Name

: ________________

: ________________