Relay Setting
Relay Setting
Relay Setting
Undervoltage Relay Setting (27) Trip when bus voltage (ph to ph) remain below for 70% nominal value
(ph to ph) remain below for 70% nominal value for 3.0 sec
LV Transformer Protection Setting:
Tag No.
Rating:
Voltage
% Impedance
CT Ratio
CT Ratio
Protection Relay
Model
Protection Function
Transformer FLA (Ip)
Transformer FLA (Is)
Through Fault Current (It)
Selected Setting:
Curve Selected
Selected Time Dial
Phase Inst. Setting
Curve Selected
Selected Setting:
Time Delay
Selected Setting
Curve Selected
Selected Time Dial
Phase Inst. Setting
Selected Setting:
Time Delay
80-TRN-0661, 80-TRN-0662
80-TRN-0663, 80-TRN-0664 & 80-TRN-0665
25 MVA
33/11.5kV
8.463
600/1(Primary Side)
2000/1 (Secondary Side)
Siemens Make
7SJ62
50, 50N, 51, 51G, 51N, 87T
437.4
1255
14831
1.2 x (Ip/Ict)
1.2 x (438/600)
0.88
IEC-Normal Inverse
0.4
1.5 x (It/Ict)
9.6906991789
Definte Time
13
0.01
Undervoltage Relay Setting (27) Trip when bus voltage (ph to ph) remain below for 70% nominal value
525.6
0.876
(ph to ph) remain below for 70% nominal value for 3.0 sec