Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Uputstvo EDS800 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 139

ISO9001:2008 Quality Management System Authentication

CE Authentication

EDS800 series
0.2-1.5KW
mini type
Ver. 2.2

Service manual

SHENZHEN ENCOM ELECTRIC TECHNOLOGIES CO., LTD


Foreword
Encom products are designed and produced under ISO9001:2000 quality
management system.
Thank you for purchasing EDS800 series mini universal inverter from
Shenzhen Encom Electric Technologies CO., LTD.
EDS800 series can fulfill all kinds of demand for general-purpose inverter
by advanced control manner which make high torque, high precision and
wide-range speed regulation drive be available. EDS800 is organic combine of
customers general need and industrial requirement to provide practical PID
adjuster, simple PLC, programmable input output terminal control, long-distance
synchronous control, impulse frequency provision and other special inverter
control with powerful function for customer and to provide highly-integrated
incorporative solution of high value for reducing system cost and improving
system reliability for device manufacturing and automatization engineering
customers.
EDS800s big torque low noise and low electromagnetic disturbance during
operation can fulfill customers environmental protection requirement by space
voltage vector PWM control technique and electromagnetic
compatibility unitary design.
Assembling wiring, parameter setting, troubleshooting and daily
maintenance notice are available in this manual. To make sure that you can
correctly assemble and operate EDS800 series inverters to exert their excellent
performance, please read this user manual detailedly before you assemble the
device and conserve the manual appropriately before the end-user get them.
Please contact our office or dealer in all places at any moment if you have
any doubts or special demands when using these inverters, and you can also
contact our after service center in our headquarters directly. We will serve you
with all our heart.
We reserve our right to notice you if we change contents of this manual.
Welcome to choose other inverters of our company:
EDS-V300 series sensorless current vector control inverter
EDS1000 series multi-function universal inverter
EDS2000 series high performance universal inverter
EDS2860 series special integrative inverter for injection
molding machine
EDS3000 series high performance closed loop vector control
inverter (in testing)
Contents
1 Safety information and use notice points 1
1.1 safety precautions 1
1.2 use range 2
1.3 use notice points 2
1.4 scrap notice points 4
2 Type and specification of the inverter 5
2.1 incoming inverter inspect 5
2.2 type explanation 5
2.3 nameplate explanation 5
2.4 series type explanation 6
2.5 appearance and parts name explanation 6
2.6 outer size and gross weight 6
2.7 outer size of keypad and its fixing box 7
2.8 product technic index and spec 7
3 Installation and wiring 10
3.1 installation ambient 10
3.1.1 demand for installation ambient 10
3.1.2 installation direction and space 10
3.2 parts disassembly and installation 10
3.2.1 key board disassembly and installation 10
3.2.2 plastic cover disassembly 11
3.3 wiring notice points 11
3.4 main loop terminal wiring 12
3.4.1 connection between inverter and fitting parts 12
3.4.2 main loop terminal wiring 13
3.5 basic running wiring diagram 14
3.6 control loop collocation and wiring 14
3.6.1 location&function of terminal and jump-wire 14
3.6.2 explanation for control panel terminal 16
3.6.3 analog input output terminal wiring 18
3.6.4 communication terminal wiring 19
3.7 installation guide for anti-jamming 20
3.7.1 restraining to noise disturbance 20
3.7.2 locale wiring and earthing 22
3.7.3 relation of long-distance wiring and current leak
and the countermeasure 23
3.7.4 installation demand for electromagnetic on-off
electronic device 23
4 Run and operation explanation for inverter 24
4.1 run of inverter 24
4.1.1 running order channels 24
4.1.2 frequency-provision channel 24
4.1.3 work state 24
4.1.4 run mode 25
4.2 operation and use of key board 26
4.2.1 keypad layout 26
4.2.2 keypad function description 26
4.2.3 LED and indicator light 27
4.2.4 key board display status 28
4.2.5 method for operating keypad 30
4.3 inverter electrification 33
4.3.1 check before electrification 33
4.3.2 first electrification 33

5 Function parameter schedule graph 35


5.1 symbol description 35
5.2 function parameter schedule graph 35

6 Detailed function description 51


6.1 basic run function parameter group: F0 51
6.2 start-up, stop, braking function parameter group:F1 56
6.3 auxiliary run function parameter group:F2 58
6.4 closed-loop run control parameter: F3 67
6.5 simple PLC run function parameter group:F4 74
6.6 terminal correlative function parameter group: F5 79
6.7 traverse special function parameter group:F6 91
6.8 frequency provision function parameter group: F7 92
6.9 motor and vector control function parameter group: F8 95
6.10 protection function parameter:F9 95
6.11 failure record function parameter: Fd 99
6.12 code and manufacturer function parameter: FF 99

7 Troubleshooting 101
7.1 failure and countermeasure 101
7.2 failure record lookup 104
7.3 failure reset 104
8 Maintenance 106
8.1 routine maintenance 106
8.2 inspection and replacement of damageable parts 107
8.3 repair guarantee 107
8.4 storage 108
9 Examples 109
9.1 common speed regulation running 109
9.2 terminal control running 110
9.3 multi-step speed control running 110
9.4 closed-loop control system 112
9.5 consecutive action running 113
10 Serial port 485 communication protocol 114
10.1 summarization 114
10.2 protocol content and description 114
Appendix 1 Modbus communication protocol 125
Appendix 2 Braking resistance 132
EDS800 series Service Manual

1 Safety information and use notice points


In order to ensure the safety of your personal and equipment, before using the
inverter, please read this chapter of contents conscientiously.
1.1 Safety precautions
There are three kinds of safe relevant warnings in this service manual, they
are as follows:
This symbol explains items that need to be paid attention to when being
! operated.

This symbol is briefed on some useful information.


note

This symbol briefs on: If does not operate on request, may cause death,
! severely injured or serious property loss.
.
(1) Forbid to connect U, V, W output end to AC power supply, otherwise cause the
complete damage of the inverter.
(2) Don't make P- and P + short-circuited, otherwise cause the inverter to be
damaged.
(3) The inverter is forbidden to install on the flammables, otherwise have danger of
fire.
(4) Don't install it in the environment with explosive gas, otherwise have danger of
causing explosion.
(5) After connecting main loop, should carry on insulating treatment to bare wiring
! end, otherwise have danger of getting an electric shock.
(6) If being connected to the power supply, don't operate the inverter with moist
hands, otherwise have danger of getting an electric shock.
(7) The ground terminal of the inverter must be grounded well.
(8) Inverter being connected to power supply, please don't open cover and carry on
wiring, can connect the wire or check only after closing power for 10 minutes.
(9) Only qualified personnel may carry on wiring and forbid leaving over any
conductive thing in machine, otherwise have danger of getting an electric shock
or causing damage of the inverter.
(10) Inverter stored for over 2 years, should be stepped up gradually with voltage
regulator first while having the electricity, otherwise have danger of getting
electric shock and explosion.

1
EDS800 series Service Manual

(1) It is prohibited that connect AC220V signal to control ends except TA, TB, TC,
otherwise have danger of damaging property.
(2) If the inverter is damaged or without all parts, please don't install and operate it,
! otherwise have danger of fire or cause personnel to be injured.
(3) When installing, should choose a place where can endure the inverter, otherwise
have danger of injuring personnel or damaging property while falling down.

1.2 Use range


(1) This inverter is only suitable for three phases AC asynchronous motor in general
industrial field.
(2) While applying inverter to such equipments that relate much to the life, great
property, safety devices etc., must handle cautiously, and consult with producer,
please.
(3) This inverter belongs to the control device of general industrial motor, if used in
dangerous equipment, must consider the security safeguard procedures when the
inverter breaks down.
1.3 Use notice points
(1) EDS800 series inverter is voltage-type inverter, so temperature, noise and
vibration slightly increasing compared to power source running when using,
belongs to normal phenomenon.
(2) If need to run for a long time with constant torque of low-speed, must select
motor of frequency conversion for use. Use general asynchronous AC motor
when running at a low speed, should control temperature of the motor or carry
on heat dissipation measure forcedly, so as not to burn the generator.
(3) Such mechanical device needing lubricating as the gearbox and gear wheel, etc.,
after running at a low speed for a long time, may be damaged as lubrication
result become poor, please take necessary measure in advance.
(4) When the motor running with frequency above specified, besides considering the
vibration, noise increase of the motor, must also confirm speed range of the
motor bearing and the mechanical device.
(5) For hoist and great inertia load, etc., the inverter would shut off frequently due to
over-current or over-voltage failure, in order to guarantee normal work, should
consider choosing proper brake package.
2
EDS800 series Service Manual

(6) Should switch on/off the inverter through terminal or other normal order
channels. It is prohibited that switch on/off the inverter frequently by using
strong electric switch such as magnetic control conductor, otherwise will cause
the equipment to be damaged.
(7) If need to install such switch as the magnetic control conductor, etc. between
inverter output and the motor, please guarantee the inverter is switched on/off
without output, otherwise may damage the inverter.
(8) The inverter may meet with mechanical resonance of the load within certain
range of frequency output, can set up jumping frequency to evade.
(9) Before using, should confirm the voltage of the power is within the working
voltage range allowed, otherwise should vary voltage or order special inverter.
(10) In the condition of altitude above 1000 meters, should use the inverter in lower
volume, reduce output current by 10% of specified current after each 1500
meters height increasing.
(11) Should make insulation check to the motor before using it for the first time or
after a long time placement. Please inspect with 500V voltage-type megohm
meter according to method shown as graph1-1 and insulation resistance should
not be smaller than 5 M, otherwise inverter may be damaged.
(12) To forbid assembling capacitor for improving power factor or lightningproof
voltage-sensible resistance etc., otherwise will cause malfunction trip of the
inverter or damage of the parts, shown as graph 1-2.
EDS800
After wiring, short-circuit U, V, W
U
to measure insulation resistance.
EDS800 V M
motor
U VW W

Grounding part
Megohm meter

Fig.1-1 motor insulation measure Fig.1-2 capacitor at output side forbidden

3
EDS800 series Service Manual

1.4 Scrap notice points


When disposing scrap inverter and its parts, please note:
(1) The unit: please discard as industrial useless.
(2) Electrolytic capacitor: when burning the inverter electrolytic capacitor in it
may explode.
(3) Plastic: when plastic, rubber parts etc. in the inverter are burning, they may
bring bad, poisonous gas, so please be ready to safeguards.

4
EDS800 series Service Manual

2 Type and specification of the inverter


2.1 Incoming inverter inspect
(1) Check if there is damage during transportation and inverter itself has damage or fall-off
parts.
(2) Check if parts presented in packing list are all ready.
(3) Please confirm rated data of the inverter is in line with your order requirement.
Our product is guaranteed by strict quality system during manufacturing,
packing, transportation etc., please contact our company or local agent rapidly if
some careless omission or mistake arise, well deal with it as soon as possible.
2.2 Type explanation
EDS800 4 T 0015 B
Inverter serial no code Fitting part

B built-in brake unit


Volt. grade code
built-in brake unit
220V 2 C
&brake resistance
380V 4
Motor power
Input volt. Code code
(KW)

Single phase S 0002 0.2


3 phase T 0004 0.4
0007 0.75
0015 1.5

Fig. 2-1 type description

If the inverter hasnt relevant content or can be defaulted, code after / will be ignored.
note

2.3 Nameplate explanation


Nameplate presented as figure 2-2 with type and rating data at the bottom of
inverter right side.

Series No.
Type
Rated input volt. and frequency
Output apparent power
Serial No.
Manufacturer

Fig.2-2 Nameplate
5
EDS800 series Service Manual

2.4 Series type explanation


Table 2-1 series type explanation
Inverter type Rated power Rated output Adapted motor
KVA currentA KW

EDS800-2S0002 0.6 1.6 0.2

EDS800-2S0004 1.1 3 0.4

EDS800-2S0007 1.8 4.7 0.75

EDS800-2S0015 2.8 7.5 1.5

EDS800-4T0007 1.5 2.3 0.75

EDS800-4T0015 2.4 3.7 1.5

2.5 Appearance and parts name explanation


LED
top cover analog potentiometer
keypad
terminal cover
take this part off to connect
brake resistance(options)

control cable inlet


vent power input and inverter output terminal

Fig. 2-3 Parts name sketch for EDS800


2.6 Outer size and gross weight

Fig.2-4 Outline Image


6
EDS800 series Service Manual

Table 2-2 EDS800-2S0002~EDS800-4T0015 mounting size


Fixing Gross
W H D D1 A B
Inverter type aperture weight
(mm) (mm) (mm) (mm) (mm) (mm)
(mm) (kg)
EDS800-2S0002 1
EDS800-2S0004 1
EDS800-2S0007 1.1
85 141.5 112.5 126 74 136 5
EDS800-2S0015 1.2
EDS800-4T0007 1.1
EDS800-4T0015 1.1
2.7 Outer size of keypad and its fixing box (unit: mm)

Fig.2-5 outer size of keypad and outline of its fixing box


2.8 Product technic index and spec.
item Item description
Rating volt.,frequency 3 phase 380V, 50Hz/60Hz; single phase 220V, 50Hz/60Hz
Input 3 phase voltage: 320V~460V;
Allowed work volt. range
single phase voltage: 200V~260V

Voltage 380V grade: 0~380V; 220V grade: 0~220V

Frequency 0Hz-400Hz
output

Over loading capacity 150% of rating current for1 minute200% of rating current for 0.5 second

Optimum space voltage vector SVPWM constant volt. Frequency ratio V/F
Control mode
performance

control
Control

Speed regulation range 1:100

Start-up torque 100% of rating torque at low frequency

7
EDS800 series Service Manual
Running speed stable state
0.5% of rating synchronous speed
precision

Digital setting: max. frequency0.01%; analog setting:


Frequency precision
max.frequency0.5%

Analog setting 0.1% of max. frequency-+96


Frequency
Digital setting 0.01Hz
resolution
Exterior pulse 0.5% of max. frequency
Torque boost Automatic torque boostmanual torque boost 0.1%~20.0%
Set rating frequency randomly at range of 5~400Hzcan choose constant
V/F curve (volt. frequency
torque, degressive torque 1, degressive torque 2, degressive torque 3 in total
characteristic) 4 kinds of curve
2 modes: straight line accelerating decelerating and S curve accelerating
Accelerating decelerating
decelerating; 7 kinds of accelerating decelerating time (unit
curve
minute/second can be optioned), max. time 6000 minutes.
Powerconsumption
exterior brake resistance
brake
brake
Optional start-up and stopaction frequency 0~15Hzaction volt. 0~15%
DC brake
action time 0~20.0 s
Jog frequency range: 0.50Hz~50.00Hz; jog accelerating decelerating time
Jog
0.1~60.0s can be set
Multisection speed running Realized by interior PLC or control terminal

Interior PID controller Be convenient to make closed-loop system


Automatic energy save Optimize V/F curve automatically based on the load to realize power save
running running
Automatic volt. regulation
Can keep constant output volt. When power source voltage varies.
(AVR)
Limit running current automatically to avoid frequent over-current which
Automatic current limiting
will cause trip
Running order specified
Key pad specified, control terminal specified, serial port specified
channel
Running function

Running frequency Digital provision, analog provision, impulse provision, serial port provision,
specified channel combined provisioncan be switched at any time by kinds of method

Impulse square wave signal output of 0~20KHzcan realize output of


pulse output channel
physical parameter such as setting frequency, output frequency etc.
1 channel of analog signal outputAO channel can be 4~20mA or 0~10V;
Analog output channel through it the inverter can realize output of physical parameter such as
setting frequency, output frequency etc.

Can display setting frequency, output frequency, output voltage, output


keypad

LED display
current etc. in total 14 kinds of parameter

Lock the button Lock all or part of the buttons(analog potentiometer cant be locked)

8
EDS800 series Service Manual

Over-current protection, over-voltage protection, lack-voltage


Protection function protection, over-heat protection, over-load protection, missing phase
protection (in option)etc.

brake subassembly, remote-control keypad, connecting cable for


Fitting parts
remote-control keypad etc.
indoornot bare to sunlightno dust, no corrosive gas, no flammable
Use ambient
gas, no oil fog, no vapor, no water drop or salt etc.
altitude Lower than 1000m
ambient

-10C~+40C(under ambient temperature 40C ~50C, please reduce the


Ambient temperature
volume or strengthen heat sink)

Ambient humidity Smaller than 95%RH, no condensation water

vibration Smaller than 5.9m/s(0.6g)

Storage temperature -40C~+70C

Defending grade IP20


Config-
uration
Cooling mode By fan with automatic temperature control

Mounting mode Wall hanging

To exert excellent performance of this inverter, please choose correct type and check
note relevant content according to this chapter before wiring for use.

Must choose correct type, otherwise may cause abnormal running of the motor or
! damage

9
EDS800 series Service Manual

3 Installation and wiring


3.1 Installation ambient
3.1.1 Demand for installation ambient
(1) Installed in drafty indoor placeambient temperature within -10C~40Cneed
external compulsory heat sink or reduce the volume if temperature exceeds40C.
(2) Avoid installing in place with direct sunlight, much dust, floating fibre and metal
powder.
(3) Forbid to install in place with corrosive, explosible gas.
(4) Humidity should be smaller than 95%RHwithout condensation water.
(5) Installed in place of plane fixing vibration smaller than 5.9m/s(0.6g).
(6) Keep away from electromagnetic disturbance source and other electronic
apparatus sensible to electromagnetic disturbance.
3.1.2 Installation direction and space
(1) Normally the inverter should be mounted vertically, horizontal mounting will
seriously affect heat dissipation and the inverter must be used in lower volume.
(2) Demand for minimum mounting space and distanceplease see Fig.3-1.
(3) When install multiple inverters up and down, must apply leading divider between
them, see fig. 3-2.
Fan
100 mm or more
exhaust
inverter

50mm 50mm
Leading
mm or more mm or more divider
inverter

100mm or more

Fig. 3-1 mounting space Fig. 3-2 mounting of multiple inverters


3.2 Parts disassembly and installation
3.2.1 Key board disassembly and installation
(1) disassembly
Let the forefinger press finger inlet on the keypaddepress fixing flexible plate on
the top lightly, draw it outward, then you can disassemble the keypad.
(2) assembly
10
EDS800 series Service Manual

First place the fixing hook at the bottom of keypad onto mounting claw on
keypad mounting hole, let forefinger press fixing flexible plate on top of keypad
and then push it inside, release it in proper location(after a crisp sound).
3.2.2 Plastic cover disassembly
Put the finger into handle hole on the bottom of cover, lift it, then you can
disassemble the cover.
3.3 wiring notice points
(1)Assure power cuf off completely for above 10 minutes before wiring, otherwise have danger of
getting electric shock.
(2)Forbid connecting power wire to output U, V, W of the inverter.
(3)There is current leakage in the inverter and leak current of middle/high power inverter is bigger than 5mA,
for safety reasoninverter and motor must be earthed safely, commonly use 3.5mm above copper wire as
ground wire and ground resistance smaller than 10.
(4)Before shipment compression resistance test of the inverter is passedso user should not conduct
! compression resistance test again.
(5)Should not assemble electromagnetic contactor and absorbing capacitance or other absorbing device,
see Fig.3-3.
(6)To be convenient to over current protect of input side and power off maintenance inverter should be
connected to power supply through relay.
(7)Connecting wire for relay input and output loop(X1~X8, OC1~OC4, FWD, REV), should use above
0.75mm glued wire or shielding wireone shielding layer end hung in the air, the other connected to
grounding end PE or E, connecting wire shorter than 20m.

(1)Before wiring, assure power supply is cut off completely for 10 minutes and all LED indicator ligh
extinguished.
(2)Before internal wiring, confirm that DC volt. Between main loop end P+ and P- fall down to below DC36V.
! (3)Wiring can only be done by professional person trained and qualified.
(4)Before electrification, check if voltage grade of the inverter is in line with that of power supply volt.,
otherwise will cause personnel injured and device damaged.

Inverter V M
W

Fig.3-3 banned magnetic control conductor and absorbing capacitance between


inverter and motor

11
EDS800 series Service Manual

3.4 Main loop terminal wiring

3 phase breaker EDS800


L1
U
Power
L2 V M
supply
W
L3
PE

Fig.3-4 main loop simple wiring


3.4.1 Connection between inverter and fitting parts
(1) Must assemble disjunction device such as isolation switch etc. between
powersource and the inverter to assure personal safety when repairing the inverter
and needing compulsory power off.
L1
(2) Power supply loop must have breaker or L2
L3
fuse with over current protection function to N
avoid malfunction expanding caused by failure
of after device. Isolation switch
(3) AC input reactor
Breaker or fuse
If high-order harmonics between inverter and
Power supply is biggish which cant fulfil
AC input reactor(in option)
system requirement, or need to improve input
side power factor, AC input reactor is needed.
Magnetic control conductor
(4) Magnetic control conductor only be applied
to power supply control and dont apply Input EMI filter(in option)
magnetic control conductor to controlling on/off
of the inverter.
L1 L2 L3
(5) Input side EMI filter
Can use EMI filter to inhibit high-frequency EDS800 Brake unit
conduction disturbance and emission PE U V W (in option)
Braking resistor
disturbance from inverter power supply wire.
(6) Output side EMI filter
Output EMI filter (in option)
Can use EMI filter to inhibit emission disturbance
noise and wire leakage current from output side. AC ouput reactor(in option)
(7) AC output reactor
Advise assembling AC outputreactor to avoid M
motor insulation damage, too large over current Fig.3-5 connection of inverter and fitting parts
and inverter frequent protection when connecting wire from inverter to motor
12
EDS800 series Service Manual

exceeds 50m.But voltage drop of AC output reactor must be considered. Improve


input output voltage of the inverter or let the motor in lower volume to avoid
burning off the motor.
(8) Complete ground wire
Inverter and motor must be earthed and grounding resistor smaller than
10.Grounding wire should be shorter enough and wire diameter be bigger
enough(not smaller than 3.5mm):
3.4.2 Main loop terminal wiring
For main loop input output terminal, see table 3-1.
Table 3-1 main loop input output terminal description
Adapted type Main loop terminal End name Function description
L1 Zero wire
EDS800-2S0002~ L2 live wire
EDS800-2S0015 E Grounding terminal
L1 L2 E U V W U,V,W 3 phase AC output end
L1,L2,L3 3 phase AC intput end
EDS800-4T0007
E Grounding terminal
EDS800-4T0015
L1 L2 L3 E U V W U,V,W 3 phase AC output end

13
EDS800 series Service Manual

3.5 Basic running wiring diagram


Braking unit (external,fitting part, interface at the
right side of inverter )

breaker P+ PB
L1 U
power L2 V M
L3 W
supply
Notice2 JP3 E
+10V H L
forward run/stop
FWD
reverse run/stop GND DC amperometer
REV EDS800
multi-function 1 4-20mA current signal
X1 AO
multi-function 2 or 0~10v voltage signal
X2 DO Cymometer
multi-function 3
X3 COM Output 12V impulse signal
multi-function 4
X4 OC open circuit collector output
multi-function 5 multi-function5 canbe
X5 used for high speed OCG Maximum 220VAC, 0.5A
Notice 1
pulse input
COM
speed command
+10V TA
0~10V
VCI TB Malfunction relay output
0~10V or 4~20mA
CCI TC
485A
GND Standard RS485
485B
communication port

Fig. 3-6 basic wiring diagram


Notice1:When FWD,RWV,X1X5 terminal imput signal need low level(or pup
joint with COM) is effective. Please put JP3 on L.
Notice2:When FWD,REV,X1X4 terminal imput signal need high level(or pup
joint with +10v) is effective. Please put JP3 on H.
3.6 Control loop collocation and wiring
3.6.1 Location&function of terminal and jump-wire:
For location of terminal and switch on the CPU board, please see Fig.3-7.
Function description of terminal provided for the user, please see Table 3-2
function and setup description of switch, please see Table 3-3terminal CN1 is for
manufacturers use. Should carry on terminal wiring correctly and set switch on the
CPU board before using the inverterto use at least No.24 conducting wire as
terminal connecting wire is recommended.

14
EDS800 series Service Manual

Fig. 3-7 switch on CPU board


Table 3-2 function description of terminal provided for user
symbol function Description
Malfunction relay signal Always-open connect pin of the relay closed when
CON2
output malfunction in inverter occurs
External terminal input Use this port when external terminal control inverter
CON3
output control running

Table 3-3 function description of switch provided for user


symbol function factory default
Analog AO output,010v exchange with 420mA
JP1 When be put on Vside,for 010v output;when be put 0~10V
onI,for 420mA output
Analog CCI input,010V exchange with 420mA.
JP2 When be put on Vside,for 010V input;when be put on 0~10V
Iside.for 420mA input.

Xi terminal iinput effective level exchange:when put


onHside,Xi input high level effective(the effective
JP3 Low level effective
voltage is 512V);When put on Lside. Xi input low
level effective(the effective voltage is 06V)

15
EDS800 series Service Manual

3.6.2 Explanation for control CPU board


(1) control loop terminal CON3 arranged as follows:
485A X1 X2 X3 X4 X5 COM FWD REV

485B +10V VCI CCI AO GND DO OC OCG


(2) CN2 terminal function description as Table 3-4.
Table 3-4 CPU board CN2 terminal function table
item symbol name Function description Spec.

Forward run Forward reverse run command, see Input impedance: R=2K
FWD
command

command F5.08 group double-wire and Max. input frequency: 200Hz


run

Reverse run three-wire control function


REV X5 can be pule input terminal
command description
Max. output Freq.: 50KHz
X1 Multi-function input 1 Input voltage range: 12~15V
Multi-function input termina

Used for multi-function input


X2 Multi-function input 2
terminal, for detailed see Chapter 6
X3 Multi-function input 3 Section 6.6 terminal function
parameter(F5 group)input end
X4 Multi-function input 4
function description.
X5 Multi-function input 5
Provide +10V power supply. Max. output current: 10mA
+10V +10V power supply
(negative pole: GND)
Common end+12V 12V grounds
COM power supply negative
pole
+10V power supply Reference ground of analog signal
GND
negative pole and +10V power supply
Input voltage range: 0~10V
voltage, current optioned by JP2 (input impedance: 70K)
Analog value input

Analog value input


CCI factory default is voltage. Input current range: 4~20mA
CCI
(reference ground: GND) (input impedance: 250)
Resolution: 1/1000
Input voltage range:
Analog value input
VCI Accept analog voltage input 0~10V (input impedance: 70K)
VCI
resolution: 1/1000

16
EDS800 series Service Manual
Provide analog voltage/current
Analog value output

outputcan express 6 kinds of


parameter see F5.17 parameter
Current output range: 4~20mA
AO Analog value output descriptionoutput voltage/current
voltage output range: 0~10V
optioned by JP1factory default
output voltage.
(reference ground: GND)
Used for multi-function switch Work voltage range:0~220V
output terminal, for detailed see Max. output current:500mA
Chapter 6 Section 6.6 terminal For use method please see
OC Relay output terminal
Multifunction output end

function parameter (F5 group) description of parameter F5.10


output end function description.
(common end: OCG)
Used for multi-function Output impulse voltage: 12V
impulse signal output Output frequency range:
terminal, for detailed see depending on parameter
H-speed impulse Chapter 6 Section 6.6 F5.24, max.20KHz
DO output terminal terminal function
parameter(F5 group) output
end function description. (common
end: COM)
(4) RS485 terminal function description as table 3-5

Table 3-5 CPU board RS485 terminal function table


item symbol name Function description spec
For standard 485
485A 485 485 difference signal positive end
communication interface
communication communication
please use twisted-pair or
485B interface 485 difference signal negative end
STP

(5) control terminal CON2arranged as follows:

TA TB TC
(6) CON2 terminal function description as Table 3-6.
Table 3-6 CPU board CON2 terminal function
Item symbol name Function description Spec
TB-TC: always-closed,
TA
Normal: TB-TC closed, TA-TC TA-TC: always-open contact
Relay Inverter
open capacity:
output TB malfunction
Malfunction: TB-TC open, AC250V/2A (COS=1)
terminal output relay
TA-TC closed AC250V/1A (COS=0.4)
TC
DC30V/1A

17
EDS800 series Service Manual
3.6.3 Analog input output terminal wiring
(1) VCI terminal accepts analog voltage signal inputwiring as follow:

+10V

0~+10V EDS800
+ VCI

GND
Shielded wire close end grounded PE

Fig.3-8 VCI terminal wiring diagram


(2) CCI terminal accepts analog signal input, input voltage(0~10V) or input
current(4~20mA)wiring mode as follows:

+10V
0~+10V EDS800
+ CCI
+
GND

Shielded wire close end grounded
PE

Fig.3-9 CCI terminal wiring diagram

(3) wiring of analog output terminals AO


Analog output terminals AO connected to analog meter and kinds of physical data
can be indicated, terminal wiring mode as Fig.3-10.

Analog meter
AO

EDS800

GND

Fig.3-10 analog output terminal wiring

(1) When inputing anglog signalcan connect filter capacitor or common module
inductance between VCI and GND or between CCI and GND .
note (2) Analog input, output signal is easy to be disturbedso must use shielded cable
when wiring and well grounded, wiring length should be as short as possible.

18
EDS800 series Service Manual

3.6.4 Communication terminal wiring


EDS800 inverter provides 485 serial communication interface for the user.
Following wiring methods make single-main single-sub control system or
single-main multi-sub control system possible. Using upper machine(PC or PLC
controller)software can realize real time supervision to inverter in the industrial
control system so that realize complicated run control such as long-distance control,
high automatization etc; you can also take one inverter as mainframe and the others
as submachine to form cascade or synchronous control network.
(1) When inverter 485 interface connected to other devices with 485 interface, you
can connect wire as below figure.
Device with
(485A) (485A) 485 interface
EDS800
(485B) (485B)
485
(E)PE

Fig.3-11 communication terminal wiring


(2) To connect remote control keypad, you can connect plug of remote control
keypad to RS485 directly. No need to set any parameterinverter local keypad and
remote control keypad can work at one time.
(3) Connection between inverter RS485 interface and upper machine(with RS232
interface): RS232/RS485 converter Shielded cable
terminal name signal Pin no.

power supply +5V PE shell

sending TXD RXD 2

receiving RXD TXD 3

grounding GND GND 5

DTR 4

DSR 6
terminal name name terminal
RI 9
Negative end B B Negative end
CD 1
Positive end A A Positive end
RTS 7

CTS 8

Fig. 3-12 RS485 communication wiring


(4)Multiple inverters can be connected together per RS485 and 31pcs inverter can be
connected together at most. Communication system is more prone to disturbance as
19
EDS800 series Service Manual

connected inverters increasing, following wiring is recommended:

EDS800 EDS800 EDS800


CPU board CPU board CPU board

Mainframe Submachine Submachine
485A 485B PE 485A 485B PE 485A 485B PE

Fig. 3-13 recommended wiring for multiple inverters communication (all inverters and
motors well earthed)
Normal communication still not available if using above wiring, can try to take
following measure:
1> Provide separate power supply for PLC (or upper machine) or isolate its power
supply.
2> Apply magnetic circle on the communication wire.
3> Reduce inverter carrier wave frequency properly.
(1) When form the network only by inverters, you must set local address parameter F2.15
of the mainframe EDS800 to 0.
note (2) For programming of RS485 interfaceplease refer to appendix communication
protocol.

3.7 Installation guide for anti-jamming


Main circuit of the inverter is composed of high-power semiconductor switch gear
so some electromagnetic noise will arise during workto reduce or stop disturbance
to environmentshow you assembling method of inverter disturbance suppressing
from many aspects such as disturbance suppressing, spot wiring, system grounding,
leak current, usage of power supply filter etc. in this section to be referred to during
spot assembling.
3.7.1 Restraining to noise disturbance
Disturbance brought by the working inverter may affect nearby electronic device
effect degree relates to surrounding electromagnetic environment of the inverter and
anti-disturbance capacity of this device.
(1) type of disturbance noise
According to work principle of the inverter, there are mainly 3 kinds of noise
disturbance source:
1> circuit conduction disturbance
2> space emission disturbance
20
EDS800 series Service Manual

3> electromagnetic induction disturbance


disturbance

conduction disturbance space emission disturbance electromagnetic induction disturbance

Input wire Inverter power Output wire


Leak current Power supply wire
induction parts induction induction
grounding loop high-order harmonic
disturbance current disturbance
Road Road Road
Road Road

Emission disturbance of Emission Emission disturbance


Inverter main loop switch disturbance from from power supply
And switching power motor wire U, V, W wire R, S, T

Road Road Road


Fig.3-14 type of noise disturbance
(2) noise spread road

TV


Power supply inverter
Wireless set meter

sensor
motor

Fig.3-15 noise disturbance spread road sketch


(3) basic countermeasure for suppressing disturbance
Table 3-7 disturbance suppressing countermeasure table
Noise
spread Countermeasure of weakening effect
road

21
EDS800 series Service Manual

When grounding wire of peripheral device and wiring of the inverter compose closed-loop, inverter
grounding wire leakage current would make the device do wrong action. Can reduce wrong action if
the device is not earthed here.
High-order harmonic from the inverter would make voltage and current transmit through power
supply wire when peripheral device and the inverter electrified by same power supply, would disturb
other devices in this same power supply systemcan take following suppressing measure: assemble
electromagnetic noise filter at inverter input endisolate other devices by isolation transformer;
connect power supply for peripheral device with remote power source; install ferrite filter magnetic
circle for L1, L2, L3 three-phase conducting wire of the inverter to suppress conduction of
high-frequency harmonic current.
Keep device and signal wire prone to disturbance from the inverter. Should use shielded signal
wire, shielding layer single end earthed and try best to keep away from the inverter and its input,
output wire. If signal wire must intersect strong power cable, must keep them in real intersection and
avoid parallel.
Install high-frequency noise filter(ferrite common module choke, folksay magnetic circle)
separately at input, output rootwhich can effectively suppress emission disturbance from dynamic
wire.
Should place motor cable shield of biggish thickness, for instance set it in tube with biggish
thickness (above 2mm) or bury it in cement slot. Dynamic wire set into metal tube and use shielding
wire to be grounded (use 4-core motor cable, one side is earthed through the inverter, the other side
connected to motor shell).
To prevent parallel or bundled power and weak conducting wireshould keep away from inverter
mounted device to the best and its wiring should keep away from power wire of the inverter such as

L1, L2, L3, U, V, W etc.. Should pay attention to relative mounting place between device with strong
electric field or strong magnetic field and the inverter, should keep distance and vertical intersection.
3.7.2 Local wiring and earthing
(1) Avoid parallel cable from inverter to motor (U, V, W terminal education wire) and power
supply wire (L1, L2, L3 terminal input wire). Should keep distance of 30cm above.
(2) Try your best to place motor table from U, V, W
terminals in metal tube or metal wiring slot. Power supply wire or
motor cable
(3) Should use shielded cable as common control
signal cableshielding layerclose-toinverter side Control signal cable
earthed after connected with PE terminal of inverter. Fig.3-16 system wiring demand
(4) Cable educed from inverter PE terminal must be connected directly to earth-plate
and cant be connected to ground through grounding wire of other devices.
(5) Powerful cable(L1, L2, L3, U, V, W)should not parallel control signal cable
closely, say nothing of being bundled together, must keep distance of 20~60cm

22
EDS800 series Service Manual

above (related to size of powerful current). Should cross each other vertically if
intersection, as Fig.3-16.
(6) Powerful grounding wire must be connected to earth separately from weak
grounding cable such as control signal and sensor cable etc.
(7) Forbid to connect other electricity consumption device to inverter power supply input end(L1,
L2, L3).
3.7.3 Relation of long-distance wiring and current leak and the countermeasure
High-order harmonic will form between-line leak current through distributing capacitor and
to-earth leak current when long-distance wiring between inverter and motor commence. Can
adopt following method to suppress:
(1) install ferrite magnetic circle or output reactor at inverter output side.
End voltage of the motor will be reduced markedly when installing reactor of 5% above rated voltage dropn
! and make long-distance wiring to U, V, W. Fully loaded motor have the danger of burning itselfshould
work in lower volume or step up its input output voltage.

(2) Reduce carrier wave frequency but motor noise would increase accordingly.
3.7.4 Installation demand for electromagnetic on-off electronic device
Relaymagnetic control conductor and electromagnetic iron and so on, these electromagnetic
on-off electronic device would bring lots of noise during work, so you should pay full attention to
when installing them beside the inverter or in the same control chamber with the inverter and
must install surge absorbing device as shown in Fig. 3-17.
diode

+
220VDC _
Voltage-sensible resistor

Inverter or

other electric
apparatus 220VAC

RC-filter


220VAC

Fig.3-17 installation demand for electromagnetic on-off device

23
EDS800 series Service Manual

4 Run and operation explanation for inverter


4.1 Run of inverter
4.1.1 Running order channels
There are 3 kinds of order channel for controlling run action of the inverter
such as run, stop, jog etc.:
0: keypad
Control by key RUN , STOP , REV JOG on keypad(factory default).
1: control terminal
Use control terminal FWD, REV, COM to make of double-line controlor use one
terminal of X1X5 and FWD or REV to make of three-line control.
2: serial port
Control run and stop of the inverter through upper machine or other device which
can communicate with the inverter.
Choose order channel by setting function code F0.02and also can choose by
multi-function input terminal(F5.00~F5.07 choose function 29, 30, 31).
Please make switching debugging in advance when switch the order channel to check if it
can fulfil system requirementotherwise have danger of damaging device and injuring
! personal.
4.1.2 Frequency-provision channel
Under EDS800 common run mode there are 9 kinds of provision channel:
0: keypad analog potentiometer provision
1: direct digital frequency provision
2: terminal UP/DOWN provision(store after power-off or stop)
3: serial port provision
4: analog value VCI provision
5: analog value CCI provision
6: reserved
7: terminal pulse(PULSE) provision
8: combination set;
9: terminal UP/DOWN provision(not store after power-off or stop)
4.1.3 Work state
Work state of EDS800 is classified as waiting state and running state:
waiting state: If there is no running command after the inverter electrified or
after stop command during running state, the inverter enters into waiting state.
running state: the inverter enters into running state after receiving run
command.
24
EDS800 series Service Manual

4.1.4 Run mode


EDS800 inverter have 6 kinds of run modefollowing is in turn according to
their priority: jog runclosed-loop runPLC runmultisection speed run
traverse runcommon run. Shown as Fig.4-1.
electrification

waiting
state

Y
Any jog command Jog run
high priority

N
N
Run command effective

Y
Y
Closed-loop effective

Y N closed-loop
N closed-loop invalidation
end closed run
Y
PLC effective

Y PLC N
N invalidation PLC run
end closed
Y multisection
multisection end effective? run

N
Y traverse
traverse run?
low priority run

N common
run
Fig.4-1 logic flow chart of EDS800 inverter run state

0: jog run
Upon receiving jog run command (for instance, press the REV JOG
key on keypad)
during waiting state, the inverter run at jog frequency (see function code F2.06~F2.08).
1: closed-loop run
The inverter will come into closed-loop run mode when closed loop run
control effective parameter is set(F3.00=1). Namely carry on PID adjustment to
specified value and feedback value(proportion integral differential calculation, see
F3 group function code) and PID adjustor output is inverter output frequency. Can
make closed-loop run mode ineffective and switch to lower level run mode by
multi-function terminal (function 20).
25
EDS800 series Service Manual

2: PLC run
The inverter will enter into PLC run mode and run according to run mode
preset(see F4 group function code description) through setting PLC function
effective parameter(F4.00 last bit0). Can make PLC run mode ineffective and
switch to lower level run mode by multi-function terminal (function 21).
3: multi-section speed run
By nonzero combination of multi-function terminal(1, 2, 3, 4 function)choose
multisection frequency 1~15(F2.30~F2.44) to run at multisection speed.
4: traverse run
The inverter will enter into traverse run mode when traverse function effective
parameterF6.00=1is set. Set relevant traverse run special parameter according to
textile traverse craft to realize traverse run.
5: common run
Common open loop run mode of general inverter.
In above 6 kinds of run mode except jog run the inverter can run according to
kinds of frequency setting method. InPID runPLC runmultisection
runcommon runmode the inverter can also carry on pendular frequency
adjustment.
4.2 Operation and use of key board
4.2.1 Keypad layout
Keypad is main unit for receiving command, displaying parameter. Outer
dimension of EN-KB6 is as Fig.4-2:
Failure alarm indicator light Forward run indicator light
Reverse run indicator light
Mode indicator light
Current unitA

Digital display (LED) Voltage unitV

Frequency unitHz
Stop, reset key

Run key Analog potentiometer

supervision key Function, data key

Rev/Jog key
Program, exit key

Data modification key


Fig.4-2 keypad layout sketch(EN-KB5)
4.2.2 Keypad function description
There are 8 key-presses and one adjusting button for analog potentiometer on
inverter Keypad and function definition of each key is as shown in table 4-1.
26
EDS800 series Service Manual

Table 4-1 keypad function table


key name Function description

ESC
MENU program/exit key Enter into or exit programming state

Can choose modification digit of set data under editor statecan switch
SHIFT shift/supervision key
display status supervision parameter under other state.
ENTER
DATA function/data key Enter into the next menu or data confirmation

REV Under keypad mode, to press this key can set reverse run or Jog run
JOG Rev/Jog key
according to the 2nd bit of parameter F0.03
RUN Run key Enter into reverse run under keypad mode

In common run status the inverter will be stopped according to set mode after
STOP pressing this key if run command channel is set as keypad stop effective mode.
RESET Stop/reset key
The inverter will be reset and resume normal stop status after pressing this key
when the inverter is in malfunction status.
Be used to set frequency; when F0.00=0 value set by analog
Analog potentiometer
potentiometer is frequency provision
To increase data or function code (to press it continuously can improve
Increasing button
increasing speed)
To decrease data or function code (to press it continuously can improve
Decreasing button
decreasing speed)
4.2.3 LED and indicator light
4 status indicator light: they are MODmode, ALMalarm, FWDforward
run, REVreverse runfrom left to right on the LED, their respective indicating
meaning is as shown in table 4-2.
Table 4-2 status indicator light description
item Function description

Digital display Display current run status parameter and set parameter

unit for relevant current digital displayed physical parameter(for current is


A,Hz,V
A, for voltage is Vfor frequency is Hz)
Display function

Status indicator light

This indicator light is lit in nonsupervision status and extinguished if no


MOD
key pressed for a minute, then come back to

ALM Alarm indicator light, indicate that the inverter is in over current or over voltage
suppressing status or failure alarm status

Forward run indicator lightindicate that the The inverter work in DC brake
FWD inverter output forward phase order and the status if FWD, REV indicator
light is lit at the same time
connected motor rotate in forward direction

27
EDS800 series Service Manual

reverse run indicator light, indicate that the


REV inverter output reversephase order and the
connected motor rotate in reverse direction
4.2.4 Key board display status
EDS800 keypad display status is classified as waiting status parameter display,
function code parameter editing status display, malfunction alarm status display, run status
parameter display in total 4 kinds of status. LED indicator light will all be lit after the
inverter electrified, and digital display LED will display character-EN- then enter into
set frequency display. As shown in Fig.4-3 a.
(1) waiting parameter display status
The inverter is in waiting status and waiting status supervision parameter is displayed
on keyboard, normally parameter F3.28 decide which status supervision parameter to be
displayed. As shown in Fig.4-3 bthe unit is indicated by rightward unit indicator light.
To press SHIFT keyit can display different waiting status supervision
parameter circularly(display 15 kinds of supervision parameter of C group
acquiescentlywhether the last 7 kinds of supervision parameter are displayed is
difined by function code F2.11F2.12, for detail please see C group status
supervision parameter in function parameter schedule graph of chapter 5).
(2) run parameter display status
The inverter enters into run status when receiving effective run command and
normally parameter F3.28 decide which status supervision parameter to be displayed on
the keypad. As shown in Fig.4-3 cunit is displayed by rightward unit indicator light.
To press SHIFT keycan display run status supervision parameter circularly
(defined by function code F2.11 and F2.12). During displaying, can press ENTER DATA to
switch to initial supervision parameter decided by F3.28, otherwise will display the
last displayed parameter all along.

28
EDS800 series Service Manual

electrification waiting status


Fig.a display-EN- run status, display
Fig.b display waiting Fig.c run status parameter
status parameter
Fig.4-3 inverter electrification, waiting, run status display
(3) Failure alarm display status
The inverter enters into failure alarm display status upon
detecting failure signal and display failure code sparklingly
over current in
(as shown in Fig.4-4);
accelerating
To press SHIFT key can look over relative parameter after
ESC
stopping runningCan press MENU key to enter into Fig.4-4 failure alarm
program status to see about Fd group parameter if want to search failure
information.
STOP
Can carry on failure restoration by RESET key, control terminal or
communication command on the keypad after troubleshooting. Keep displaying
failure code if failure exist continuously.
For some serious failuresuch as inverse module protectover current, over voltage
! etc., must not carry on failure reset forcibly to make the inverter run again without
failure elimination confirmed. Otherwise have danger of damaging the inverter

(4) function code editing status


Under waiting, run or failure alarm statuspress MENU ESC keycan enter into
editing status(If user password is setcan enter into editing status after inputting the
passwordsee also FF.00 description and Fig.4-10)and editing status is displayed
according to three classes menu modeas shown in Fig. 4-5. To press ENTER DATA key
can enter into one class by one class. Under function parameter display statusto
ENTER ESC
press DATA key to carry on parameter storage operationTo press MENU key
can only come back to upper class menu without stroring modified parameter.

29
EDS800 series Service Manual
first-class third-class
MENU ENTER Second-class ENTER menu
menu menu
electrification

Set frequency Frequency


run parameter Digital provision
Switch display setting mode

MENU/ESC
MENU MENU ENTER/DATA store para.
Waiting status parameter
Editing status
Display or run status
parameter display or
Fig.4-5
keypad display status switching
failure alarm display
(5) Special display function
You can change set frequency under supervision state directly when keypad
potentiometer is effective (F0.00=0) or keypad digital setting is effective (F0.00=1).
Here the inverter displays set frequency if its stop or displays output frequency if
its running. After set frequency stops changing for 1 second the inverter will go
back to normal display status.
4.2.5 Method for operating keypad
Can carry on various operation to the inverter through keypadfor example:
(1) status parameter display switching:
After pressing key SHIFT display C group status supervision parameter; after
displaying one supervision parameter code for 1 second, will display this parameter
value automatically.
LED displayed 1s 1s
content 50.00 C-01 para. value C-02 para. value
Key
operation Set frequency Output frequency Output current
order SHIFT SHIFT

1s 1s
para. value C-14 para. value C-03

Pulse input Output voltage


SHIFT SHIFT SHIFT

Fig. 4-6 waiting status parameter display operating example


Description:
1> All status parameters C-00C-14 can be displayed when the inverter leaves
factory. You can make a change by modifying function code F2.11, F2.12 if you
want to, for detail please refer to F2.11, F2.12function code description.
2> Can press ENTERDATA key to switch into constant supervision C-01 display status
directly when the user see about status supervision parameter.
30
EDS800 series Service Manual

(2) function code parameter setting


Take function code F2.06 modified from 5.00Hz to 6.00Hz as example. Boldface in
Fig.4-7 shows flickering digit.
LED
displayed 50.00 -F0- -F2- F2.00 F2.06
content
Key ESC ENTER ENTER
operation MENU Choose DATA Function
order Choose DATA
Enter into editing F2 group group confirmation function
status Display function Go into
Exit editing first-class menu code second-class menu code F2.06
status

ESC -F2- F2.07 06.00 05.00 05.00


MENU
ESC ENTER
MENU DATA SHIFT
Go back to Store modified Parameter Function code
Parameter
confirmation,
First-class value,back to modification, modification,
menu second-class menu 56 Choose Enter into
Display next parameter digit third-class
function code menu

Fig.4-7 example for parameter setting and modification


Description: under third-class menu, if the parameter has no blinking digitthis
function code cant be modifiedpossible reasons are as follows:
a. This function code shouldnt be modified, for example actual detected status
parameter, run record parameter etc.
b. This function code cant be modified under run status and can be changed after
stopping running
c. Parameter protected. All the function code cant be modified when function code
F2.13=1 or 2in order to avoid wrong operation. Need to set the function code F2.13
to 0 if you want to edit function code parameter.
(3) specified frequency adjustment for common run
Take example modifying specified frequency from 50.00Hz to 40.00Hz at
F0.00=0 during running for explanation.
LED displayed
content 50.00 49.99 45.00 40.00
Key
operation
order
Press Adjust Stop pressing after set
decreasing frequency value reached, go back
button for based on to normal display status
one time requirement after 1 second
Fig. 4-8 set frequency adjustment operation example
(4) jog run operation
For example, keypad as current run command channel, jog run frequency 5Hz,
waiting status.

31
EDS800 series Service Manual

LED
displayed
content 50.00 0.01 5.00 0.01 50.00
waiting release
Key waiting keep
operation REV REV REV waiting
Display JOG JOG JOG Output frequency
order Display run Output
set output frequency Fall down to 0Hz
frequency frequency Increased by 5Hz Stop running

Fig.4-9 jog run operating example


(5) operation for entering to function code editing status after setting user
password
user passwordFF.00 is set to6886. Boldfaced digit in Fig.4-7 shows blinking
bit.
LED
displayed
content 50.00 0.0.0.0 0.0.0.6 0.0.0.6 6.0.0.6
Key ESC
operation MENU SHIFT
user password At first last move cursor Increase
order Nonediting effective, go into Digit flash, position to to6
status password increase to first digit
validation status 6

-F0- 6.8.8.6 6.8.0.6 6.8.0.6 6.0.0.6


ENTER
DATA SHIFT SHIFT
Increase Move to Move to
Press confirmation Increase
to8 Third digit Second
Key, pass validation, to8
digit
Go into editing status
Fig.4-10 inputting password to go into function code operation

(6) See about failure parameter under failure status


LED 1s 1s 1s
displayed Fd.06 50:00 Fd.07 45:00 Fd.08 5.5
content E001
Key Failure output freq.
Failure set freq. Failure current
operation
order SHIFT SHIFT SHIFT

1s 1s 1s
1500 Fd.14 1111 Fd.13 380 Fd.09
SHIFT

Failure run time Failure terminal status Failure output volt.


SHIFT SHIFT SHIFT
Fig.4-11 failure status searching operation example
Description:
1> If press SHIFT key under failure status the user can see about Fd group
function code parameter, search range Fd.06 Fd.14 LED first display
function code number when the user press SHIFT key and display parameter
digit of this function code after 1s.
32
EDS800 series Service Manual

2> When the user see about failure parametercan press ENTER DATA
key directly to
switch back to failure alarm display status (E0XX)
(7) keypad key-press locking operation
ESC
Under unlocked keypad situationpress MENU key for 5s to lock the keypad. For
detailed operation please refer to 2nd bit of F2.13 function code.
(8) keypad key-press unlocking operation
Under locked keypad situationpress MENU ESC key for 5s to unlock the keypad.
4.3 Inverter electrification
4.3.1 Check before electrification
Please carry on wiring based on operation requirement provided in inverter
wiring of this Service manual.
4.3.2 First electrification
Close input side AC power supply switch after correct wiring and power supply
confirmed, electrify the inverter and keypad LED display -EN -, contactor closed
normally, LED displayed set frequency shows that electrification is finished. First
electrification operation process is shown as Fig. 4-12.

33
EDS800 series Service Manual

start

wiring based on 3.5 section

N
wiring correct?
Y
N
input voltage correct?

electrify
Y
N
display-EN-
Y
hear N
contactor closedsound
Y
N
display set frequency
Y
failure
success

cut off
power

check
reason

Fig. 4-12 first electrification operation flow

34
EDS800 series Service Manual

5 Function parameter schedule graph


5.1 Symbol description
---- parameter cant be changed in process of running
---- parameter can be changed in process of running
* ---- read-only parameter, unmodifiable
5.2 Function parameter schedule graph
F0 basic run function parameter group
function Factory Modificat-
name Set range unit
code default ion
F0.00 Frequency input 0: keypad analog potentiometer setting 1 1
channel selection 1: keypad digital setting
2: terminal UP/DOWN adjust setting (stored after
power off)
3: serial port setting
4: VCI analog setting (VCI-GND)
5: CCI analog setting (CCI-GND)
6: reserved
7: terminal pulse (PULSE) setting
8: combination setting
9: terminal UP/DOWN adjust setting
(not stored after power off)
10:provision serial port (stored after power off)
11:terminal PWM pulse setting freq.
F0.01 Freq. digit setting Lower limit Freq.upper limit Freq. 0.01Hz 50.00Hz
F0.02 Run command 0: keypad run control 1 0
channel selection 1: terminal run command control
(keypad stop command ineffective)
2: terminal run command control
(keypad stop command effective)
3: serial port run command control
(keypad stop command ineffective)
4: serial port run command control
(keypad stop command effective)
F0.03 Run direction 1st bit: 0, forward run; 1, reverse run 1 00
setting 2nd bit: 0, reverse run allowed
1, reverse run banned
3rd bit: REV/JOG key selection
0: as reverse run key
1: as jog key
F0.04 Acce/Dece mode 0: linear accelerating decelerating mode 1 0
selection 1: S curve accelerating decelerating mode
F0.05 S curve start 10.050.0 Acce/Dece time
0.1() 20.0(%)
section time F0.05+F0.0690

35
EDS800 series Service Manual

F0.06 S curve risetime 10.070.0 Acce/Dece time


0.1() 60.0(%)
F0.05+F0.0690
F0.07 accelerating 0: second
decelerating time 1: minute 1 0
unit
F0.08 Acce time 1 0.16000.0 0.1 20.0
F0.09 Dece time 1 0.16000.0 0.1 20.0
F0.10 Upper limit freq. Lower limit freq.400.00Hz 0.01Hz 50.00Hz
F0.11 Lower limit freq. 0.00Upper limit freq. 0.01Hz 0.00Hz
F0.12 Lower limit freq. 0: run at lower limit freq.
1 0
run mode 1: stop running
F0.13 Torque boost 0: manual boost
1 0
mode 1: automatic boost
F0.14 Torque boost 0.020.0 0.1(%) 4.0(%)
F0.15 V/F curve setting 0: constant torque curve 1 0
1: degressive torque curve 1the 2.0nd power
2: degressive torque curve 2the 1.7th power
3: degressive torque curve 3the 1.2th power
F0.16 reserved

F1 start-up, stop, brake function parameter group


Function Factory Modificat-
name Set range unit
code default ion
F1.00 Start-up run mode 0: start at start-up freq. 1 0
1: first brake, then start at start-up freq.
2: reserved
F1.01 start-up freq. 0.010.00Hz 0.01Hz 0.00Hz
F1.02 start-up freq. duration 0.020.0S 0.1s 0.0s
F1.03 Zero freq. DC braking volt. 015 1 0
F1.04 Zero freq. DC braking time 0.020.0S 0.1s 0.0s
F1.05 Stop mode 0: Dec stop 1 0
1: free stop
2: DecDC brake stop
DC brake initiative freq. 0.015.00Hz
F1.06 0.01Hz 0.00Hz
when stop running
DC brake time when stop 0.020.0s
F1.07 0.1s 0.0s
running
DC brake voltage when stop 015
F1.08 1 0
running

F2 auxiliary run function parameter group


Function Factory modif-
name Set range unit
code default ication

36
EDS800 series Service Manual
Analog filter time 0.0030.00s
F2.00 0.01s 0.20s
constant
Forward reverse run 0.03600.0s
F2.01 0.1s 0.1s
dead-section time
F2.02 Automatic energy 0: no action
1 0
save run 1: action
F2.03 AVR function 0: no action 1 0
1: action all the time
2: no action only during Dec
Slip frequency 0150()0-no slip frequency
F2.04 1 0
compensation compensation
F2.05 Carrier wave 215.0K depend on
freq. 0.1K
machine type
Jog run frequency 0.1050.00Hz
F2.06 0.01Hz 5.00Hz
F2.07 Jog Acc time 0.160.0s 0.1s 20.0s
F2.08 Jog Dec time 0.160.0s 0.1s 20.0s
F2.09 Frequency input 0: VCICCI 1 0
channel combination 1: VCICCI
2: reserved
3: reserved
4: reserved
5: reserved
6: exterior pulse provisionCCI
7: exterior pulse provisionCCI
8: reserved
9: reserved
10: reserved
11: reserved
12: reserved
13: VCI, CCI any nonzero value effective,
VCI preferred
14: reserved
15: RS485+CCI
16: RS485-CCI
17: RS485+VCI
18: RS485-VCI
19: RS485+keypad potentiometer
20: RS485- keypad potentiometer
21: VCI+ keypad potentiometer
22: VCI- keypad potentiometer
23: CCI+ keypad potentiometer
24: CCI- keypad potentiometer
25: reserved
26: reserved
27: reserved
28: reserved
Principal subordinate 0500
Machine communication
F2.10 1(%) 100(%)
frequency provision
proportion

37
EDS800 series Service Manual

F2.11 LED display 0000-1111 1 1111


control 1 first bit: running time
0: not display
1: display
second bit: accumulative time
0: not display
1: display
third bit: input terminal status
0: not display
1: display
kilobit(fourth bit):
output terminal status
0: not display
1: display
F2.12 LED display 0000-1111 1 1111
control 2 first bit: analog input VCI
0: not display
1: display
second bit: reserved
third bit: analog input CCI
0: not display
1: display
kilobit(fourth bit): exterior pulse input
0: not display
1: display
F2.13 Parameter operation LED 1st bit: 1 000
control 0: all parameter allowed to be modified
1: except this parameterall other parameter
not allowed to be modified
2: except F0.01 and this parameterall other
parameter not allowed to be modified
LED 2nd bit:
0: no action
1: restore default value
2: clear history failure record
LED 3rd bit:
0: not locked
1: lock all buttons but not STOP key
2: lock all buttons but not ,
STOP key
3: lock all buttons but not RUN, STOP key
4: lock all buttons but not SHIFT, STOP key
F2.14 Communication LED first bit: baud rate selection 1 03
configuration 0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
LED second bit: data format
0: 181format, no checkout
1: 181 format, even checkout
2: 181 format, odd checkout
38
EDS800 series Service Manual

F2.15 Local address 0 127 127 is broadcast address. The


inverter only receive but not send when it is 1 1
set to be 127, 0 is address for main device.
F2.16 Communication overtime 0.01000.0s 0.1s 0.0s
F2.17 Local responsion delay 0200ms 1ms 5ms
F2.18 Acce time 2 0.16000.0 0.1 20.0
F2.19 Dece time 2 0.16000.0 0.1 20.0
F2.20 Acce time 3 0.16000.0 0.1 20.0
F2.21 Dece time 3 0.16000.0 0.1 20.0
F2.22 Acce time 4 0.16000.0 0.1 20.0
F2.23 Dece time 4 0.16000.0 0.1 20.0
F2.24 Acce time 5 0.16000.0 0.1 20.0
F2.25 Dece time 5 0.16000.0 0.1 20.0
F2.26 Acce time 6 0.16000.0 0.1 20.0
F2.27 Dece time 6 0.16000.0 0.1 20.0
F2.28 Acce time 7 0.16000.0 0.1 20.0
F2.29 Dece time 7 0.16000.0 0.1 20.0
F2.30 Multisection freq. 1 Lower limit freq.upper limit freq. 0.01Hz 5.00Hz
F2.31 Multisection freq. 2 Lower limit freq.upper limit freq. 0.01Hz 10.00Hz
F2.32 Multisection freq. 3 Lower limit freq.upper limit freq. 0.01Hz 20.00Hz
F2.33 Multisection freq. 4 Lower limit freq.upper limit freq. 0.01Hz 30.00Hz
F2.34 Multisection freq. 5 Lower limit freq.upper limit freq. 0.01Hz 40.00Hz
F2.35 Multisection freq. 6 Lower limit freq.upper limit freq. 0.01Hz 45.00Hz
F2.36 Multisection freq. 7 Lower limit freq.upper limit freq. 0.01Hz 50.00Hz
F2.37 Multisection freq. 8 Lower limit freq.upper limit freq. 0.01Hz 5.00Hz
F2.38 Multisection freq. 9 Lower limit freq.upper limit freq. 0.01Hz 10.00Hz
F2.39 Multisection freq. 10 Lower limit freq.upper limit freq. 0.01Hz 20.00Hz
F2.40 Multisection freq. 11 Lower limit freq.upper limit freq. 0.01Hz 30.00Hz
F2.41 Multisection freq. 12 Lower limit freq.upper limit freq. 0.01Hz 40.00Hz
F2.42 Multisection freq. 13 Lower limit freq.upper limit freq. 0.01Hz 45.00Hz
F2.43 Multisection freq. 14 Lower limit freq.upper limit freq. 0.01Hz 50.00Hz
F2.44 Multisection freq. 15 Lower limit freq.upper limit freq. 0.01Hz 50.00Hz
F2.45 Jumping freq. 1 0.00400.00Hz 0.01Hz 0.00Hz
F2.46 Jumping freq. 1 range 0.0030.00Hz 0.01Hz 0.00Hz
F2.47 Jumping freq. 2 0.00400.00Hz 0.01Hz 0.00Hz
F2.48 Jumping freq. 2 range 0.0030.00Hz 0.01Hz 0.00Hz
F2.49 Jumping freq. 3 0.00400.00Hz 0.01Hz 0.00Hz
F2.50 Jumping freq. 3 range 0.0030.00Hz 0.01Hz 0.00Hz
F2.51 Setting run time 065535 hours 1 0
F2.52 Accumulative run time 065535 hours 1 0 *

39
EDS800 series Service Manual

F2.53 RS485communication 0: a ASCII frame of 14 byte or 18 byte 1 0


frame format selection 1: a hex frame of 8 byte or 10 byte, original
response not changed
2: a hex frame of 8 byte or 10 byte, 12
command has no response
3: a hex frame of 8 byte or 10 byte, 14
command has no response
4: a hex frame of 8 byte or 10 byte, both 12
and 14 command have no response

F3 group closed-loop run function parameter group


Function Factory modif-
name Set range unit
code default ication
F3.00 Closed-loop run 0: closed-loop control ineffective 1 0
control selection 1: PID closed-loop control effective
2: reserved
F3.01 Provision channel 0: digital provision 1 1
selection 1: VCI analog 010V voltage provision
2: CCI analog provision
3: keypad potentiometer provision
F3.02 Feedback channel 0: VCI analog input voltage 010V 1 1
selection 1: CCI analog input
2: VCI+CCI
3: VCI-CCI
4: Min { VCI, CCI }
5: Max { VCI, CCI }
6: pulse feedback
Specified value digital
F3.03 0.0010.00V 0.01 0.00
setting
F3.04 Minimum specified value 0.0maximum specified value; percentage
0.1(%) 0.0(%)
relative to 10.00V
F3.05 feedback value
responding to
0.0100.0(%) 0.1(%) 0.0(%)
minimum specified
value
F3.06 maximum specified
Minimum specified value100.0 0.1(%) 100.0(%)
value
F3.07 feedback value
responding to
0.0100.0 0.1(%) 100.0(%)
maximum specified
value
F3.08 proportion gain Kp 0.0009.999 0.001 0.050
F3.09 Integral gain Ki 0.0009.999 0.001 0.050
F3.10 Differential gain Kd 0.0009.999 0.001 0.050
F3.11 Sampling cycle T 0.011.00s 0.01s 0.10s
F3.12 Deviation margin 0.020.0percentage relative to 10.00V 0.1(%) 2.0(%)
F3.13 Integral separation PID 0.1(%) 100.0(%)
0.0100.0%
adjusting threshold

40
EDS800 series Service Manual

F3.14 Closed-lop preset 0.01Hz 0.00Hz


0upper limit frequency
frequency
F3.15 Closed-loop preset 0.0-6000s 0.1s 0.0s
frequency holding
time
F3.16 Sleep frequency 0.01Hz 0.01Hz
0.00400.00Hz
threshold
F3.17 Revival frequency 0.01Hz 0.01Hz
0.00400.00Hz
threshold
F3.18 Sleep delay time 0.06000.0s 0.1 0.0
F3.19 Revival delay time 0.06000.0s 0.1 0.0
F3.20 Constant pressure 0: choose inverter OC1-OC4, one-drive-one 1 0
water supply mode water supply mode
selection 1: choose constant pressure water supply board ,
one-drive-one mode
2: choose constant pressure water supply board ,
one-drive-two mode
3: choose constant pressure water supply board ,
one-drive-three mode
F3.21 Long-distance pressure 0.001 1.000
0.0019.999Mpa
meter range
F3.22 Allowed offset for upper 0.1 0.0
limit frequency and
lower limit frequency 0.0100.0%
when add or reduce
pumps
F3.23 Pump switch judging 0.1 300.0
0.0999.9s
time
F3.24 Magnetic control 0.1 0.5
conductor switch delay 0.110.0s
time
F3.25 Automatic switch 1 0000
00009999minutes
intervel
F3.26 Water supply supervision 0: C-11, C-12 denote voltage value of VCI, CCI 1 0
parameter display 1: C-11, C-12 denote PID specified pressure and
feedback pressure
F3.27 Closed-loop adjusting 0: Forward function 0
characteristic 1: Reverse function

F3.28 LED initial 0: set frequency 1


supervision parameter 1: output frequency
selection 2: output current
3: output voltage
4: DC bus bar voltage
5: motor speed
6: heat sink temperature
7: run time
8: accumulative run time
9: input terminal status
10: output terminal status
11: analog input VCI/PID provision
12: analog input CCI/PID feedback
41
EDS800 series Service Manual
13: reserved
14: exterior pulse inputs
Zero freq. braking freq.
F3.29 0.00Hz-15.00Hz 0.01Hz 0.00Hz
at starting
F3.30 Failure relay TA, TB, TC 0: inverter runningRUN 15
function selection 1: frequency arriving signalFAR
2: frequency level detect signal (FDT1)
3: reserved
4: overload warning alarm signal (OL)
5: output frequency reach high limitFHL
6: output frequency reach low limitFLL
7: inverter under voltage blockage stop (LU)
8: external failure stop-runningEXT
9: inverter zero speed running
10: PLC running
11: simple PLC section running finished
12: PLC finish a cycle running
13: reserved
14: inverter ready to run (RDY)
15: inverter failure
16: traverse high and low limit restriction
17: interior counter reach final value
18: interior counter reach specified value
19: set run time arriving
20: interior timing arriving
21: reserved
22: reserved
23: reserved
24: reserved
F3.31 VCI analog input gain 0-800% 100

F4 simple PLC function parameter group


Function Factory modif-
name Set range unit
code default ication
F4.00 Simple PLC LED first bit: 1 000
running setting 0: no action
1: stop after single circulation
2: keep final value after single circulation
3: consecutive circulation
LED second bit:
0: start again from first section
1: continue to run at mid-section frequency
LED third bit: PLC run time unit
0: second
1: minute
F4.01 Section 1 setting 000621 1 000
LED first bit: frequency setting
0: multisection freq. i (i=1~7)
1: freq. determined by F0.00 function code
LED second bit: run direction selection
42
EDS800 series Service Manual
0: forward run
1: reverse run
2: determined by run command
LED third bit: Acc/Dec time selection
0: Acc/Dec time 1
1: Acc/Dec time 2
2: Acc/Dec time 3
3: Acc/Dec time 4
4: Acc/Dec time 5
5: Acc/Dec time 6
6: Acc/Dec time 7
F4.02 Section 1 run time 06000.0 0.1 10.0
F4.03 Section 2 setting 000621 1 000
F4.04 Section 2 run time 06000.0 0.1 10.0
F4.05 Section 3 setting 000621 1 000
F4.06 Section 3 run time 06000.0 0.1 10.0
F4.07 Section 4 setting 000621 1 000
F4.08 Section 4 run time 06000.0 0.1 10.0
F4.09 Section 5 setting 000621 1 000

F4.10 Section 5 run time 06000.0 0.1 10.0

F4.11 Section 6 setting 000621 1 000


F4.12 Section 6 run time 06000.0 0.1 10.0
F4.13 Section 7 setting 000621 1 000
F4.14 Section 7 run time 06000.0 0.1 10.0

F5 terminal correlative function parameter group


Function Factory modif-
name Set range unit
code default ication
F5.00 Input terminal X1 0: leave control terminal unused 1 0
function selection 1: multisection speed control terminal
2: multisection speed control terminal
3: multisection speed control terminal
4: multisection speed control terminal
5: external forward run jog control
6: external reverse run jog control
7: Acc/Dec time option terminal 1
8: Acc/Dec time option terminal 2
9: Acc/Dec time option terminal 3
10: external device failure input
11: external reset input
12: free stop input
13: external stop-running order
14: stop DC braking input command DB
15: inverter run banned
16: frequency increasing control (UP)
17: frequency degression control (DOWN)
43
EDS800 series Service Manual
18: Acc/Dec ban command
19: three-line run control
20: closed-loop ineffective
21: PLC ineffective
22: simple PLC pause control
23: PLC stop status reset
24: frequency provision channel option 1
25: frequency provision channel option 2
26: frequency provision channel option 3
27: frequency switched to CCI
28: command switched to terminal
29: run command channel option 1
30: run command channel option 2
31: run command channel option 3
32: traverse jump-in
33: external interruption input
34: interior counter reset end
35: interior counter triggering end
36: interior timer reset end
37: interior timer triggering end
38: pulse frequency input
(only effective for X5)
39: reserved
40: reserved
41: reserved
42: reserved
Input terminal X2 Same as above
F5.01
function selection
Input terminal X3 Same as above
F5.02
function selection
Input terminal X4 Same as above
F5.03
function selection
Input terminal X5 Same as above
F5.04
function selection
F5.05 reserved
F5.06 reserved
F5.07 reserved
F5.08 FWD/REV run mode 0: double-line control mode 1 1 0
selection 1: double-line control mode 2
2: three-line control mode 1
3: three-line control mode 2

F5.09 UP/DOWN velocity 0.0199.99Hz/s 0.01Hz/s 1.00Hz/s


F5.10 Open circuit collector 0: inverter runningRUN 1 0
output terminal OC 1: frequency arriving signalFAR
output setting 2: frequency level detect signal (FDT1)
3: reserved
4: overload warning alarm signal (OL)
5: output frequency reach high limitFHL
6: output frequency reach low limitFLL
7: inverter under voltage blockage stop (LU)

44
EDS800 series Service Manual
8: external failure stop-runninEXT
9: inverter zero rotate speed running
10: PLC running
11: simple PLC section running finished
12: PLC finish a cycle running
13: reserved
14: inverter ready to run (RDY)
15: inverter failure
16: traverse high and low limit restriction
17: interior counter reach final value
18: interior counter reach specified value
19: set run time arriving
20: interior timing arriving
21: reserved
22: reserved
23: reserved
24: reserved
F5.11 reserved
F5.12 reserved
F5.13 reserved
Frequency arriving 0.0050.00Hz 0.01Hz 5.00Hz
F5.14
(FAR) checkout scope
F5.15 FDT1 (frequency 0.00high limit frequency 0.01Hz 10.00Hz
level) electric level
F5.16 FDT1 lag 0.0050.00Hz 0.01Hz 1.00Hz
F5.17 Analog output (AO1) 0: output frequency(0high limit frequency) 1 0
selection 1: set frequency(0high limit frequency)
2: output current(02rated current)
3: output voltage(01.2load motor rated
voltage)
4: bus-bar voltage(0800V)
5: PID provision (0.00-10.00V)
6: PID feedback (0.00-10.00V)
7: reserved
8: reserved
9: reserved
F5.18 Analog output (AO) gain 0.002.00 0.01 1.00
F5.19 Analog output (AO) offset 0.0010.00V 0.01 0.00
F5.20 reserved

F5.21 reserved

F5.22 reserved

F5.23 DO terminal output Same as F5.17 1 0


function selection
F5.24 DO maximum pulse output 0.120.0(max. 20KHz)Max. DO port output 0.1KHz 10.0
frequency pulse frequency corresponds to Max. value
selected by F5.23
Set interior counting value 0--9999 1 0
F5.25
reaches provision
F5.26 Specified interior counting 0--9999 1 0

45
EDS800 series Service Manual
value reaches provision
F5.27 Interior timer setting 0.16000.0s 0.1 60.0

F6 traverse special function parameter group


Function Factory modif-
name Set range unit
code default ication
F6.00 Traverse function selection 0: traverse function not used 1 0
1: traverse function used
F6.01 traverse run mode LED first bit: jump-in mode 1 00
0: automatic jump-in mode
1: terminal manual jump-in mode
LED second bit:
0: changing traverse amplitude
1: fixed traverse amplitude
notice: traverse center frequency input
channel set by F0.00 function parameter
Traverse amplitude 0.050.0% 0.1(%) 0.0(%)
F6.02
threshold
Sudden jumping 0.050.0% 0.1(%) 0.0(%)
F6.03
frequency
F6.04 traverse cycle 0.1999.9s 0.1s 10.0s
F6.05 Triangle wave risetime traverse cycle
0.098% 0.1(%) 50.0(%)
F6.06 traverse preset frequency 0.00400.00Hz 0.01Hz 0.00Hz
F6.07 traverse preset frequency 0.06000s 0.1s 0.0s
latency time

F7frequency provision function parameter group


Function Factory modif-
name Set range unit
code default ication
F7.00 VCI min. provision 0.00F7.02 0.01V 0.00V
F7.01 VCI min. provision corresponding freq. 0.00high limit frequency 0.01Hz 0.00Hz
F7.02 VCI max. provision 0.0010.00V 0.01V 10.00V
F7.03 VCI max. provision corresponding freq. 0.00high limit frequency 0.01 Hz 50.00Hz
F7.04 CCI min. provision 0.00F7.06 0.01V 0.00V
F7.05 CCI min. provision corresponding freq. 0.00high limit frequency 0.01 Hz 0.00Hz
F7.06 CCI max. provision 0.0010.00V 0.01V 10.00V
F7.07 CCI max. provision corresponding freq. 0.00high limit frequency 0.01 Hz 50.00Hz
F7.08 Max. Input pulse width 0.1-999.9ms(whenF0.00=11) 0.1ms 100.0ms
F7.09 Min. provision pulse width 0.0-F7.11(Max.provision pulse) 0.1ms 0.0ms
(whenF0.00=11)
F7.10 min. provision corresponding freq. 0.00high limit frequency 0.01Hz 0.00Hz
F7.11 Max. provision pulse width F7.09(Min.provision 0.1ms 100.0ms

46
EDS800 series Service Manual

pulse)-F7.08(Max.input pulse)
F7.12 max. provision corresponding freq. 0.00- high limit frequency 0.01Hz 50.00Hz
F7.13 PULSE max. input pulse 0.120.0K 0.1K 10.0K
F7.14 PULSE min. provision 0.0F7.16(PULSE max. 0.1K 0.0K
provision)
F7.15 PULSE min. provision corresponding freq. 0.01 Hz 0.00 Hz
0.00high limit frequency

F7.16 PULSE max. provision F7.14 (PULSE min. provision) 0.1K 10.0K
F7.13 (max. input pulse)
F7.17 PULSE max. provision corresponding freq. 0.00high limit frequency 0.01 Hz 50.00Hz

F8motor and vector control parameter group


Function modif-
name Set range unit Factory default
code ication
F8.00 reserved
F8.01 Motor rated voltage 1480V 1V Depend on device type
F8.02 Motor rated current 0.1999.9A 0.1A Depend on device type
F8.03 Motor rated frequency 1.00400.00Hz 0.01Hz Depend on device type
F8.04 Motor rated speed 19999r/min 1r/min Depend on device type
F8.05 Motor pole 2-14 2 Depend on device type
F8.06 Motor rated power 0.1999.9KW 0.1 Depend on device type
F8.07 reserved
F8.08 reserved
F8.09 reserved
F8.10 reserved
F8.11 reserved
F8.12 reserved
F8.13 reserved
F8.14 reserved
F8.15 reserved
F8.16 Frequency display offset 0.00Hz-2.00Hz 0.01Hz 0.20Hz
F8.17 reserved

F9 protection correlative function parameter group


Function Factory modif-
name Set range unit
code default ication
F9.00 reserved
F9.00 Instantaneous power 0.010.0S 0.1S 0.0S
off restarting latency 0 indicates ineffective power off restarting
time Remark: no automatic reset function for
overload and overheating
47
EDS800 series Service Manual

F9.01 Failure self-renew 010 1 0


times 0 shows no automatic reset function
Remark: no automatic reset function for
overload and overheating
F9.02 Failure self-renew interval 0.520.0S 0.1S 5.0S
F9.03 Motor overload 0: no action 1 1
protection mode selection 1: inverter close off output
F9.04 Motor overload 20.0-120.0% 0.1(%) 100.0(%)
protection coefficient
Overload warning 20200% 1(%) 130(%)
F9.05 alarm checkout level
Overload warning 0.020.0s 0.1s 5.0s
F9.06
alarmDelay time
F9.07 Overvoltage stall selection 0: ban 1 1
1: allow
F9.08 Overvoltage stall point 120-150(%) 1(%) 140(%)
F9.09 Automatic current limit level 110200( %) 1(%) 150(%)
F9.10 Frequency declining rate 0.0099.99Hz/s 0.01Hz/s 10.00Hz/s
during current limiting
F9.11 Automatic current 0: constant speed ineffective 1 0
limiting action selection 1: constant speed effective
remark: Acc/Dec always effective

Fd failure record function parameter group


Function Factory modif-
name Set range unit
code default ication
Fd.00 Previous one time failure record Previous one time failure record 1 0 *
Fd.01 Previous two time failure record Previous two time failure record 1 0 *
Fd.02 Previous three time failure record Previous three time failure record 1 0 *
Fd.03 Previous four time failure record Previous four time failure record 1 0 *
Fd.04 Previous five time failure record Previous five time failure record 1 0 *
Fd.05 Previous six time failure record Previous six time failure record 1 0 *
Fd.06 Set freq. of previous failure Set freq. of previous failure 0.01Hz 0 *
Fd.07 output freq. of previous failure output freq. of previous failure 0.01Hz 0 *
Fd.08 output current of previous failure output current of previous failure 0.1A 0 *
Fd.09 output voltage of previous failure output voltage of previous failure 1V 0 *
Fd.10 DC bus-bar voltage of previous failure DC bus-bar voltage of previous 1V 0 *
failure
Fd.11 Load motor speed of previous failure Load motor speed of previous 1(r/m) 0 *
failure
Fd.12 Module temperature of previous failure Module temperature of previous 1 0 *
failure
Fd.13 Input terminal status of previous failure Input terminal status of previous 0 *
failure
Fd.14 Accumulative run time of previous failure Accumulative run time of previous 0 *
failure
48
EDS800 series Service Manual

FF password and manufacturer function parameter group


Function Factory modif-
name Set range unit
code default ication
FF.00 User password 00009999 1 0000
FF.01 Manufacturer password 00009999 1 0000
FF.02 Manufacturers special parameter
FF.0X

C supervision function parameter group


Function Factory modif-
name Set range unit
code default ication
C-00 Set frequency Current set frequency 0.01HZ
C-01 Output freq. Current output freq. 0.01HZ *
C-02 Output current Virtual value of current output current 0.1A *
C-03 Output voltage Virtual value of current output voltage 1V *
C-04 DC bus-bar voltage Current DC bus-bar voltage 1V *
C-05 Load motor speed Product of output frequency and load motor 1(r/m) *
speed emendation factor
C-06 Module temperature IGBT heat sink temperature 1 *
C-07 Run time Inverter electrification run time 1h *
C-08 accumulative run time Inverter accumulative run time 1h *
C-09 Input terminal status Switch value input terminal status *
C-10 output terminal status Switch value output terminal status *
C-11 Analog input VCI Analog input value of VCI V *
C-12 Analog input YCI Analog input value of YCI V *
C-13 reserved

C-14 Exterior pulse input Exterior pulse input 0.1KHz *

49
EDS800 series Service Manual

(1) input terminal status corresponding relation is as follows:

shows terminal input ineffective


shows terminal input effective
X1 terminal status REV input terminal
X2 terminal status FWD input terminal
X3 terminal status reserved
X4 terminal status X5 terminal status

(2) output terminal status corresponding relation is as follows:

shows that terminal has no output


OC1 output terminal reserved shows that terminal has output
reserved reserved

50
EDS800 series Service Manual

6 Detailed function description


Listed column content for parameter function code description in this chapter is
as follows:

code name Set range or description Factory default

6.1 Basic run function parameter group: F0


F0.00 Frequency input channel selection range0~11 1

0: keypad analog potentiometer. Set running frequency by keypad analog


potentiometer.
1: keypad frequency number setting. Initial set frequency value is F0.01can
change set frequency by changing F0.01 parameter through keypadand you can
also modify F0.01 by , key.
2: terminal UP/DOWN adjust set frequency(stored after power off or stop).
Initial set frequency value is the value stored during the last power off timeand you
can adjust set running frequency by terminal UP/DOWN.
3: serial port provision. Serial port frequency set initial value is F0.01change
set frequency by setting F0.01 through serial port.
4: VCI analog setting(VCIGND).Frequency setting determined by VCI
terminal analog voltageinput voltage range: DC0~10V.
5: CCI analog setting (CCIGND). Frequency setting determined by CCI
terminal analog voltage /currentinput range: DC0~10(CCI switch choose V side)
DC: 4~20mA (CCI switch choose A side).
6: reserved.
7: terminal pulse (PULSE) setting. Frequency set by terminal pulse( only
input through X5see F5.03, F5.04 definition)input pulse signal spec: voltage
range15~24Vfrequency ange 0~20.0KHz.
8: combination setting. See function parameter F2.09set frequency by each
channel combination setting.
9: terminal UP/DOWN adjust set frequency( not stored after power off or
stop)Initial set frequency value is F0.01and adjust set running frequency by
terminal UP/DOWN.
10:serial port specified(memory after electric off):when the inverter is

disconnected with electic,it will keep the currently running frequency,and next time
51
EDS800 series Service Manual

it will keep the former frequency running the electric on .

11: terminal PWM pulse set frequency.


Relation between frequency and input information is determined by function code
F7.00~F7.17 when frequency input channel is 4, 5, 6, 7please see Section 6.8.
note

F0.01 Freq. digital setting rangelow limit high limit 50.00Hz

F0.01 parameter is original set frequency of the inverter when frequency setting
channel is defined as number setting (F0.001, 3).
F0.02 Run command channel selection range04 0

0: keypad run frequency command channel. Start and stop the inverter
by RUN , STOP , REV key on the keypad.
JOG
1: terminal run command channel(keypad STOP command ineffective).
Start and stop the inverter by exterior control terminal FWD, REV, X1~X5 etc..
2: terminal run command channel(keypad STOP command effective). Start
and stop the inverter by exterior control terminal FWD, REV, X1~X5 etc..
3: serial port run command channel(keypad STOP command ineffective).
Start and stop the inverter by RS485 interface.
4: serial port run command channel(keypad STOP command effective).
Start and stop the inverter by RS485 interface.
The inverter can change run command channel by modifying F0.02 during waiting and
! runningplease confirm that modification is allowed during running on the spot.

F0.03 Run direction setting Range0, 1 100


This function is only effective for keypad and serial port run command channel
ineffective for terminal run command channel.
The 1st bit:
0: inverter forward run
1: inverter reverse run
The 2nd bit:
0: reverse run allowed
1: reverse run banned. The inverter will stop output when there is reverse run
command.
The 3rd bit: REV/JOG key selection
0: as REV key
1: as JOG key

52
EDS800 series Service Manual

If the 2nd bit is set to1this function is effective for keypad run command channel,
note terminal run command channel and serial port run command channel.

F0.04 Accelerating decelerating mode selection range0, 1 0


0: linear Acce/Dece mode. Output frequency increases or decreases according
to constant slope, just as shown in Fig.6-1.
1: S curve Acce/Dece mode. Output frequency increases or decreases
according to S curve, just as shown in Fig.6-2.
Freq.
Freq
50.00Hz 50.00Hz

time
time
t1 t2
Fig.6-1 linear Acce/Dece t1 t2
Fig.6-2 S curve Acce/Dece
range10.0()50.0() Acc/Dec
F0.05 S curve starting time 20.0(%)
timeF0.05F0.0690()
range10.0()80.0() Acc/Dec
F0.06 S curve rising time 60.0(%)
timeF0.05F0.0690()
F0.05, F0.06 is only effective when S curve Acc/Dec mode( F0.041)is
selected during Acc/Dec selection, and F0.05F0.0690%.
S curve starting time is shown as Fig. 6-2slope of output frequency variation
increases by degrees from 0.
S curve rising time is shown as Fig.6-2slope of output frequency variation is
constant.
S curve ending time is shown as Fig.6-2slope of output frequency variation steps
down to 0.
S curve Acc/Dec modesuitable for starting and stopping elevator, deferent belt, carrier transporter load etc..
note

F0.07 Acc/Dec time unit range0, 1 0


This function determines Acc/Dec time unit.
0: second
1: minute

53
EDS800 series Service Manual

(1) This function is effective for all Acc/Dec process except for jog run.
note (2) To choose second as time unit is recommended.

F0.08 Acc time 1 range0.16000.0 20.0


F0.09 Dec time 1 range0.16000.0 20.0
Accelerating time is defined as time for inverter accelerating from 0Hz to high
limit frequencysee t1 in Fig.6-3Dec time is defined as time for inverter
decelerating from high limit frequency to 0Hz, see t2 in Fig.6-3.

Output freq.

high limit frequency

time

t1 t2
Fig.6-3 Acc/Dec time definition

(1) In EDS800 series inverter 7 kinds of Acc/Dec time are defined in totalhere we
only define Acc/Dec time 1Acc/Dec time 2~7 are defined in F2.18~F2.29
please refer to Section 6.3.
note (2) Can choose time unit minute or second for Acc/Dec time 1~7 by F0.07, factory
default is second.

F0.10 high limit frequency rangelow limit400.00Hz 50.00Hz

F0.11 low limit frequency range0.00high limit 0.00Hz


Low limit freq. run range0:run at low limit freq. 1:stop
F0.12 0
mode running

The inverter will decrease output frequency gradually in set decelerating time
when actual set frequency is lower than low limit frequencyafter reaching low limit
frequencythe inverter will run at low limit frequency if F0.18 is set to 0The
inverter will reduce output frequency sequentially to zero frequency run if F0.12 is
set to 1.

F0.13 Torque boost mode range0manual 1automatic 0

0: manual boost. Torque boost voltage is determined completely by parameter


54
EDS800 series Service Manual

F0.14its characteristic is boost voltage fixedbut the motor is prone to magnetic


saturation when lightly loaded.
1: automatic torque boost. Torque boost voltage varies as stator current of the
motor changesbigger stator current corresponds to bigger boost voltage.
F0.14 inverter output current
Boost volt.= motor rated volt.2inverter rated current
100

F0.14 Torque boost Range0.020.0() 4.0()

To improve inverters low frequency torque characteristiccan carry on boost


compensation for output voltagedegressive torque curve and constant torque curve
torque boost are separately shown as Fig.6-4 (a), (b).
voltage voltage
motor rated volt. motor rated volt.

Volt. Volt.
Freq. Freq.
Boost Boost
rated freq. rated freq.
(a)degressive torque curve torque boost graph (b) constant torque curve torque boost graph

Fig.6-4 torque boost graph


(1) improper setting to this parameter can cause motor heating or over current
protection.
note (2) advise the user to adopt manual torque boost and to adjust V/F curve according
to motor parameter and usage occasion when driving synchronous motor.

F0.15 V/F curve setting range0~3 0


This function code defines EDS800 flexible V/F setting mode to satisfy
different load characteristic. Can choose 4 kinds of fixed curve according to
definition of F0.15.
If F0.15=0V/F curve bears constant torque characteristicas curve 0 in
Fig.6-5.
If F0.15=1V/F curve bears 2.0 order power degressive torque characteristic
as curve 3 in Fig.6-5.
If F0.15=2V/F curve bears 1.7 order power degressive torque characteristic
as curve 2 in Fig.6-5.
If F0.15=3V/F curve bears 1.2 order power degressive torque characteristic
as curve 1 in Fig.6-5.
55
EDS800 series Service Manual

The user can choose 1, 2, 3 V/F curve run mode according to load characteristic
to reach better energy save result while the inverter is driving degressive torque load
such as blower and water pump etc.

Output volt.

Rated volt.

0
1
2
3

Output freq.
0
rated freq.
Fig.6-5 V/F curve

F0.16 Reserved

6.2 Start-up, stop, braking function parameter group: F1


F1.00 Start-up run mode range0, 1, 2 0
0: start from starting frequency. The inverter start according to F1.01 starting
frequency and F1.02 starting frequency holding time.
1: first braking then starting. First brake according to DC braking voltage and
time (F1.03, F1.04)then start at starting frequency.
2: reserved.
(1) start-up mode 0: Advise the user to adopt start-up mode 0 in common application occasion and
when driving synchronous motor.
note (2) start-up mode 1: Be applicable to small inertia load with forward run or reverse run phenomena
when the moter doesnt drive any devicefor big inertia loadadvise not to adopt start-up mode 1.

F1.01 Starting frequency range0.010.00Hz 0.00 Hz

F1.02 Starting freq. holding time range0.020.0S 0.0S


Starting frequency means initial frequency at which the inverter start upas fs
shown in Fig.6-6Starting freq. holding time means consecutive run time during
which the inverter run at starting frequencyas t1 shown in Fig.6-6.

56
EDS800 series Service Manual

I
freq. Hz
fmax
IB

BR F
0
fs
starting
time F
freq.
starting 1/4 F1.04
t1 time running
F1.04

Fig.6-6 starting freq. and starting time Fig.6-7 Zero freq. DC braking Volt. And Time

Starting frequency is not limited by low limit frequency.


note

F1.03 Zero freq. DC braking volt. range015() 0()

F1.04 Zero freq. DC braking time range0.020.0S 0.0S

Zero Freq. DC braking is special function for FKM (Flat Knitting Machine).
Specific function is: the inverter enters into braking status automatically during
running when running frequency is lower than F3.29 (Zero Freq. Braking
frequency), and realizes continuance of current phase intelligently, fast and smooth
orientation for motors rotor. The inverter will stop braking automatically and
switch into running if specified frequency increased or reverse running instruction
provided in the braking, Curve figure as Fig6-7:
. IB is zero Freq. braking current, to set according to actual braking torque by
setting F1.03.
. BR is specified zero Freq. braking signal point, inverter enters into zero Freq.
braking status automatically after 1/4 F1.04.
. Fis any time in braking. When specified frequency increased or reverse
running instruction provided, the inverter will end zero Freq. braking and enter
into running status. But the inverter is still in running status and waits for
frequency raising instruction.
. After F1.04, the inverter stops output and the motor is in zero Freq. running
status if there is neither frequency raising instruction nor reverse instruction.

57
EDS800 series Service Manual

Output freq.

stop braking
initiative freq.

output volt.
(virtual
value)

DC braking value
stop braking time

run command

Fig.6-8 Dec stop+DC braking

F1.05 Stop mode Range0, 1, 2 0


0: Dec stop. The inverter reduces output frequency gradually according to set
Dec time upon receival of stop command and stops running after frequency is
reduced to 0.
1: free stop. The inverter stop outputting at once when receiving stop
command and the load stops freely according to mechanical inertia.
2: Dec plus DC braking stop. The inverter reduces output frequency gradually
according to set Dec time upon receival of stop command and start DC braking
when F1.06 stop braking initiative frequency is reached.

F1.06 Stop DC braking initiative frequency range0.015.00Hz 0.00Hz

F1.07 Stop DC braking time range0.020.0S 0.0S

F1.08 Stop DC braking voltage range015 0

F1.08 is percentage relative to inverter rated input voltage. Have no DC


braking process if stop braking time is 0.0sas shown in Fig.6-8.
6.3 Auxiliary run function parameter group: F2
F2.00 Analog filtering time constant Range0.0030.00S 0.20S

The time constant used when the inverter filter sampled value when frequency
is set by exterior analog channel. Can improve the situation by increasing this
filtering time constant if connecting wire is long or disturbance is serious which
cause unstable set frequency.
58
EDS800 series Service Manual
Analog filtering time constant must be bigger than F3.11(sampling cycle),
otherwise the system would run unsteadily.
F2.01 FWD REV run dead-section time range0.03600.0S 0.1S
During process of transiting from forward run to reverse run or from reverse run
to forward run, transition time during which the inverter wait at zero output
frequency, as t1 shown in Fig.6-9.
Output freq.

time

t1

Fig.6-9 FWD REV run dead-section time

F2.02 Automatic energy save run range0, 1 0


To reach better energy save result, the inverter would detect load current to get
the purpose of automatic energy save.
0: no action
1: action
Empty or lightly loaded motor can get the purpose of energy save by detecting
load current to adjust output voltage properly. Automatic energy save run is mainly
applied to occasion of stable load, speed.

This function commonly applied to load such as blower and water pump etc.
note

F2.03 AVR function range0, 1, 2 0


AVR namely automatic voltage adjusting function. Indicate that the inverter can
output constant voltage by AVR function when the inverter input voltage fluctuates.
0: no action
1: action all the time
2: no action only during Dec
1. when input voltage is higher than rated value, under normal situation should set F2.03=1. When F1.05=0
namely inverter in decelerating stopmotor Dec time is short and running current would be bigger. But the
motor decrease speed placidly with small run current and long Dec time if choose AVR action all the time.
note
2. should set F2.03=0, namely AVR function ineffective when the motor system oscillates which caused by
choosing AVR function.

59
EDS800 series Service Manual

F2.04 Slip freq. compensation range0150() 0


This function can adjust output frequency properly as the load varies to
compensate slip frequency of the asynchronous motor dynamically, so that control
motor speed in constant value. If act with automatic torque boost function, can get
better low speed moment characteristic. As shown in Fig.6-10.
100% Slip compensation
Output current

150%

100%
Before slip compensation After slip compensation
50%
Motor speed

Fig.6-10 slip freq. compensation graph

F2.05 Carrier freq. range215.0K Depend on device type


Carrier frequency mainly affects motor noise and heat consumption during
running. Relation between carrier frequency and motor noise, current leakage,
disturbance is as follows:
Carrier frequency increase()motor noise decrease()motor current leakage
increase()disturbance to environment increase()
Carrier frequency decrease ()motor noise increase ()motor current leakage
decrease ()disturbance to environment decrease ().
Should decrease carrier frequency properly to reduce heat consumption of the
inverter when ambient temperature is high and motor load is heavy. Relation of
EDS800 each type and carrier frequency is as shown in Table 6-1.
Table 6-1 relation table of device type and carrier frequency
carrier freq.
Max.carrier freq. (KHz) Min. carrier freq (KHz) factory default (KHz)
device type

0.2KW 15 2.0 2

0.4KW 15 2.0 2

0.75KW 14 2.0 2

1.5KW 13 2.0 2

60
EDS800 series Service Manual

(1) To get better control characteristicsuggest that the ratio of carrier frequency to inverter max. run
frequency be not smaller than 36.
note (2) Error exists in current displayed value when carrier frequency is small.

F2.06 Jog run frequency range0.1050.00Hz 5.00Hz

F2.07 Jog Acc time range0.160.0S 20.0S

F2.08 Jog Dec time range0.160.0S 20.0S

Jog frequency has the highest priority. Under any status, the inverter would
transit to run at jog frequency at once according to set jog accelerating,
decelerating time as long as jog command is inputted, as shown in Fig.6-11.
Jog accelerating time means time during which the inverter accelerate from 0Hz
to high limit frequencyJog Dec time means time during which the inverter
decelerate from high limit frequency to 0Hz.

Jog decelerating time


Jog
freq.
Jog accelerating Jog
time freq.

Jog. Jog.
signal signal

Fig.6-11 jog run


(1) Keypad, control terminal and serial port can do jog control all.
note (2) The inverter will stop according to Dec stop mode after jog run command is withdrawn.

F2.09 Freq. input channel combination range028 0


0: VCICCI
1: VCICCI
2: reserved
3: reserved
4: reserved
5: reserved
6: external pulse provisionCCI
7: external pulse provisionCCI
8: reserved
9: reserved
61
EDS800 series Service Manual
10 : reserved
11 : reserved
12 : reserved
13 : VCI, CCI any nonzero value effective, VCI preferred
14 : reserved
15 : 485+CCI
16 : 485-CCI
17 : 485+VCI
18 : 485-VCI
19 : 485+ keypad analog potentiometer
20 : 485- keypad analog potentiometer
21 : VCI+ keypad analog potentiometer
22 : VCI- keypad analog potentiometer
23 : CCI+ keypad analog potentiometer
24 : CCI- keypad analog potentiometer
25 : reserved
26 : reserved
27 : reserved
28 : reserved

host inverter communication freq.


F2.10 range0500() 100()
provision proportion

Host&sub inverter communication freq. provision proportionthis parameter


need to be set in sub inverter but not need in host inverter.
F2.11 LED display control 1 range0000-1111 1111
F2.11 make use of 4 bits of the parameter to set if C-07C-10 is displayed in
parameter, thereinto 0 indicates not displayed, 1 indicates displayed. Set parameter of 4
bit is as following figure:

4th bit 3rd bit 2nd bit 1st bit

C-07: run time

C-08: accumulative run time

C-09: input end status

C-10: output end status

62
EDS800 series Service Manual

F2.12 LED display control 2 range0000-1111 1111

F2.12 make use of 4 bit of the parameter to set if C-11C-14 is displayed in


parameter, thereinto 0 indicates not displayed, 1 indicates displayed. Set parameter of 4
bit is as following figure:
4th bit 3rd bit 2nd bit 1st bit

C-11analog input VCI

C-12reserved

C-13analog input CCI

C-14outer pulse input

rangeLED 1st bit: 0~2


Parameter operation
F2.13 LED 2nd bit: 0~2 000
control
LED 3rd bit: 0~4

LED 1st bit


0: all parameter allowed to be modified
1: except this parameterall other parameter not allowed to be changed
2: except F0.01 and this parameterall other parameter not allowed to be
changed
LED 2nd bit
0: no action
1: renew factory default
2: clear history failure record
LED 3rd bit
0: Not locked
1: all the buttons locked except STOP key
2: all the buttons locked except , STOP key
3: all the buttons locked except RUN, STOP key
4: all the buttons locked except SHIFT, STOP key

63
EDS800 series Service Manual

(1)Factory default of this function parameter is 0i.e., all the function parameter can be
modified.After modifying the parameter, please first set this function code to 0 if you want to modify
function code setting.After modifying the parameter you can change this function code setting to
expected protection grade if parameter protection is needed.
note (2) After clearing memory information or renewing manufacturer parameter, the 1st bit of this
function code will resume 0 automatically.
(3) After the 3rd bit of F2.13 is setted, the keypad will be locked after you press ESC for 5
seconds, and then corresponding keys is locked. Please press ESC for 5 seconds again for
unlocking the keypad.

F2.14 communication deployment rangeLED 1st bit05 LED 2nd bit: 0, 1, 2 03

F2.14 make use of 1st bit, 2nd bit to set baud rate and data format of serial
communicationthereinto LED 1st bit represents communication baud rate, set
value as follows:
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
LED 2nd bit: represents data formatset value as follows:
0: 181 format, no checkout. Namely: 1 bit for starting, 8 bits for data, 1
bit for stop, no checkout.
1: 181 format, even checkout. Namely: 1 bit for starting, 8 bits for data, 1
bit for stop, even checkout.
2: 181 format, odd checkout. Namely: 1 bit for starting, 8 bits for data, 1
bit for stop, odd checkout.
F2.15 Local address range0127, 127 is broadcast address 1
This function code is used to identify address of this inverter during serial port
communication.127 is for main inverter during main and sub device communication
between inverters.
127 is broadcast addresscan only receive and execute broadcast command from upper
! machine but not respond to upper machine when 127 is set to broadcast address.

F2.16 Communication overtime checkout time range0.01000.0S 0.0S

When serial port communication fails and its continuous time exceed set value
of this function codethe inverter judge it as communication failure.
64
EDS800 series Service Manual

The inverter would not detect serial port communication signal, namely this
function ineffective when set value is 0.

F2.17 Local response delay time range0200ms 5ms

Local response delay time represents the time within which the inverter serial
port receive and execute command from upper device and then respond to upper
device, this function is just used for setting this delay time.

F2.18 Accelerating time 2 range0.16000.0 20.0

F2.19 Decelerating time 2 range0.16000.0 20.0

F2.20 Accelerating time 3 range0.16000.0 20.0

F2.21 Decelerating time 3 range0.16000.0 20.0

F2.22 Accelerating time 4 range0.16000.0 20.0

F2.23 Decelerating time 4 range0.16000.0 20.0

F2.24 Accelerating time 5 range0.16000.0 20.0

F2.25 Decelerating time 5 range0.16000.0 20.0

F2.26 Accelerating time 6 range0.16000.0 20.0

F2.27 Decelerating time 6 range0.16000.0 20.0

F2.28 Accelerating time 7 range0.16000.0 20.0

F2.29 Decelerating time 7 range0.16000.0 20.0

Can define 3 kinds of accelerating decelerating time and can choose


accelerating decelerating time 1 7 during inverter run process by different
combination of control terminalplease see definition for function of accelerating
decelerating time terminal in F5.00F5.07.

Accelerating decelerating time 1 is defined in F0.08 and F0.09.


note

65
EDS800 series Service Manual

F2.30 Multi-step freq. 1 rangelow limit high limit fre 5.00Hz

F2.31 Multi-step freq. 2 rangelow limit high limit 10.00Hz

F2.32 Multi-step freq. 3 rangelow limit high limit 20.00Hz

F2.33 Multi-step freq. 4 rangelow limit high limit 30.00Hz

F2.34 Multi-step freq. 5 rangelow limit high limit 40.00Hz

F2.35 Multi-step freq. 6 rangelow limit high limit 45.00Hz

F2.36 Multi-step freq. 7 rangelow limit high limit 50.00Hz

F2.37 Multi-step freq. 8 rangelow limit high limit 5.00Hz

F2.38 Multi-step freq. 9 rangelow limit high limit 10.00Hz

F2.39 Multi-step freq. 10 rangelow limit high limit 20.00Hz

F2.40 Multi-step freq. 11 rangelow limit high limit 30.00Hz

F2.41 Multi-step freq. 12 rangelow limit high limit 40.00Hz

F2.42 Multi-step freq. 13 rangelow limit high limit 45.00Hz

F2.43 Multi-step freq. 14 rangelow limit high limit 50.00Hz

F2.44 Multi-step freq. 15 rangelow limit high limit 50.00Hz

These set frequency will be used in multi-step speed run mode and simple PLC
run modeplease refer to multi-step speed run terminal function of F5.00F5.04
and F4 group simple PLC function.

F2.45 Jumping freq. 1 range0.00400.00Hz 0.00Hz

F2.46 Jumping freq. 1 range range0.0030.00Hz 0.00Hz

F2.47 Jumping freq. 2 range0.00400.00Hz 0.00Hz

F2.48 Jumping freq. 2 range range0.0030.00Hz 0.00Hz

F2.49 Jumping freq. 3 range0.00400.00Hz 0.00Hz

F2.50 Jumping freq. 3 range range0.0030.00Hz 0.00Hz

F2.45F2.50 function is set for keeping inverter output frequency away from
resonance frequency of mechanical load.
Inverter set frequency can jump around some frequency point according to mode
66
EDS800 series Service Manual

shown in Fig. 6-12, at most 3 jumping range can be defined.


Set freq. after adjusted

Jumping freq. 3 Jumping range 3

Jumping freq. 2 Jumping range 2

Jumping freq. 1 Jumping range 1

Set freq.

Fig.6-12 jumping frequency and range graph

F2.51 Set run time range065535h 0

F2.52 Run time accumulation range065535h 0

After run accumulative time reach set run time (F2.51)the inverter will output
indicator signalplease refer to F5.10 function introduction.
F2.52 denotes accumulative run time of the inverter from leaving factory to now.
F2.53 RS485/232 frame format selection range04 0
0: a frame of 14 bytes or 18 bytes ASCII
1: a frame of 8 bytes or 10 bytes hexprimary response not changed
2: a frame of 8 bytes or 10 bytes hex12 command has no response
3: a frame of 8 bytes or 10 bytes hex14 command has no response
4: a frame of 8 bytes or 10 bytes hexboth 12 and 14 command have no
response
6.4 Closed-loop run control parameter: F3
Analog feedback control system:
Input pressure specified value through VCI port, send 4~20mA feedback value
of pressure sensor to inverter CCI input portmake up of analog closed-loop control
system by built-in PID adjustoras shown in Fig.6-13.

67
EDS800 series Service Manual

QF send out
Power L1 EDS800 U

pressure sensor
L2 V M P
supply
L3 W
PE
FWD

COM 4~20mA
CCI

+10V GND
provision 1-3K VCI
GND

Fig.6-13 built-in PID analog feedback control system graph

Specified value can also be provided with option by F0.00 function code.
note

EDS800 built-in PID adjustor make up of control system and its work principle
chart is as follows: proportion
gain
+ (F3.08)
specified value e
Closed-loop error limit integral + closed-loop
specified value adjusting (F3.12)
_ gain output
(F3.06F3.06) +
(F3.09)
differenti-
differential
al gain
gain
(F3.10) closed-loop
feedback adjusting feedback
(F3.05F3.07) value

Fig.6-14 PID control principle diagram


In above Fig.6-14 ,definition of closed-loop specified value, feedback value,
error limit and proportion integral differential parameter is same as that of common
PID adjustor parameter, see respectively (F3.01~F3.12) definitionrelation of
specified value and expected feedback value is as shown in Fig.6-15. Thereinto
specified value take 10V as reference and feedback take 20mA as reference.
Specified value adjusting and feedback value adjusting in Fig.6-14 is for
confirming corresponding relation and unitive dimension between specified value
and feedback value.

68
EDS800 series Service Manual

Expected feedbck value

20mA

4mA specified value

0 10V
Fig.6-15 specified value and expected feedback value
When the system is determinedbasic steps for setting closed-loop parameter are as
follows:
(1) determine closed-loop provision and feedback channel(F3.01, F3.02)
(2) need to set relation between closed-loop provision and feedback for analog
closed-loop (F3.04~F3.07)
(3) set closed-loop presetting frequency function (F3.14, F3.15)
(4) set closed-loop proportion gain, integral gain, differential gain, sampling cycle,
error limit (F3.08~F3.12)

F3.00 Closed-loop run control selection range0, 1, 2 0

0: closed-loop run control ineffective


1: PID closed-loop run control effective
2: reserved
F3.01 provision channel selection range0~3 1
0: digital provision.
1: VCI analog 010V voltage provision
2: CCI analog provision. Can choose 0~10V voltage or 4~20mA current
provision
3: keypad analog potentiometer provision
F3.02 Feedback channel selection range0~6 1
0: VCI analog input voltage 010V
1: CCI analog input
2: VCI+CCI
3: VCI-CCI
4: Min { VCI, CCI }
69
EDS800 series Service Manual

5: Max { VCI, CCI }


When CCI analog input is selected to be current input, it will be converted to
voltage value in the inverter.
6: pulse feedback
F3.03 Specified value digital setting range0.0010.00V 0.00V
When F3.01=0, figure provision F3.03 will be as specified value of
closed-loop control system directly. Therefore when control closed-loop system
through keypad or serial port, can change system specified value by modifying
F3.03.

F3.04 min. specified value range: 0.0max. specified 0.0()

F3.05 corresponding feedback value


range0.0100.0(%) 0.0()
of min. specified value

F3.06 max. specified value rangemin. specified value -100.0() 100.0(%)

corresponding feedback value


F3.07 range0.0%100.0() 100.0(%)
of max. specified value

F3.04~F3.07 define relation curve of analog closed-loop provision and


expected feedback. Their set value is percentage of provision and feedback actual
value relative to reference (10V or 20mA).
corresponding
positive adjusting
feedback value of
feedback max. specified value
corresponding
feedback value of
min. specified value

negative adjusting corresponding min. provision max. provision


feedback value of
feedback max. specified value
corresponding
feedback value of
min. specified value
min. provision max. provision
Fig.6-16 provisionfeedback curve

F3.08 Proportion gain Kp range0.0009.999 0.050

F3.09 Integral gain Ki range0.0009.999 0.050

F3.10 Differential gain Kd range0.0009.999 0.000

F3.11 Sampling cycle T range0.011.00S 0.10S

70
EDS800 series Service Manual

The more big Kp proportion gain is, the more quick the response isbut overbig
is prone to bringing surge.
Only applying proportion gain Kp adjustment cant eliminate offset
completelycan apply integral gain Ki and differential gain to make up of PID
control in order to eliminate residual offset. The bigger Ki is, the more quickly the
system responds to changing offset, but overbig is prone to bringing surge.
Sampling cycle T is sampling cycle for feedback valueduring each sampling
cycle PID adjustor calculate for one timethe longer the sampling cycle is , the
slower the system responds.
F3.12 Offset limit range0.020.0() 2()
For Max. offset of closed-loop specified valueas shown in Fig.6-17PID
adjustor stops adjusting when feedback value is within this range. To utilize this
function reasonably redound to harmonizing the conflict between system output
precision and stabilization.
Feedback value
Specified offset Output Freq.
value limit
preset freq.

time

Output
Freq.
time

time
preset freq. holding time

Fig.6-17 offset limit Fig.6-18 closed-loop preset freq. run

F3.13 integral separation PID adjusting threshold range0.0100.0% 100.0%

PID integral separationintegral dont react when specified value and feedback
value are bigger than this limit, only when specified value and feedback value are
smaller than or equal to this limitintegral react. Can adjust system response speed
by adjusting this parameter.
F3.14 closed-loop preset frequency range0-high limit freq. 0.00Hz
F3.15 closed-loop preset frequencyholding time range0.0-6000S 0.0S

This function can make closed-loop adjusting enter into stable phase quickly.
After closed-loop run starts, the inverter first accelerates to preset frequency F3.14
in terms of accelerating time, and after running at this frequency for a period of time

71
EDS800 series Service Manual

F3.15, it runs according to closed-loop characteristic. As shown in Fig.6-18.

Set preset freq. and holding time to 0 if closed-loop preset freq. function is not needed.
note

F3.16 Revival frequency range0.00400.00Hz 0.00Hz

F3.17 Sleep frequency range0.00400.00Hz 0.00Hz


Revival frequency define frequency limit from sleep status to work status. If set
frequency is bigger than this limit and the situation sustains for a revival delay time,
the inverter will enter into work status from sleep status.
Sleep frequency define frequency limit from work status to sleep status. If set
frequency is smaller than this limit and the situation sustains for a sleep delay time,
the inverter will enter into sleep status from work status.
This function can realize sleep function and make energy save run possible,
avoid the inverter staring at threshold frequency frequently.
F3.18 Sleep delay time range0.06000.0S 0.0
This parameter is to set delay time when entering into sleep function. EDS800
will stop running if the output frequency is lower than sleep frequency and holding
time longer than this sleep delay time.

F3.19 Revival delay time range0.06000.0S 0.0

This parameter is to set delay time when entering into revival function.

F3.20 Constant pressure water supply mode selection range0~3 0

0: select inverter OC to act in one-drive-one water supply mode


1: select constant pressure water supply board to act in one-drive-one water
supply mode
2: select constant pressure water supply board to act in one-drive-two water
supply mode
3: select constant pressure water supply board to act in one-drive-three water
supply mode

F3.21 Long-distance manometer range range0.0019.999Mpa 1.000


To set 10V or 20mA by this parameter.

Allowed offset to high limit and lower


F3.22 range0.0100.0 0.0
limit Freq. when add or reduce pumps

By this parameter,we defines that the inverter begins to add or reduce pumps
72
EDS800 series Service Manual

when output frequency falls in offset range of high limit frequency or lower limit
frequency.The inverter begins to add or reduce pumps at high limit frequency or
lower limit frequency if this parameter is set to be 0.0.
F3.23 Pump switchover judging time range0.0999.9S 300.0
This parameter defines the judging time from output frequency up to high limit
to adding pump and the same from ouput frequency up to lower limit to reducing
pump.
Magnetic control conductor
F3.24 range0.110.0S 0.5
switchover delay time
This parameter defines the action delay time of magnetic control conductor
when its from power source to variable frequency or from variable frequency to
power source.
F3.25 Automatic switchover interval range00009999 minutes 0
This parameter defines automatic switchover interval, for more information
about automatic switchover please see parameter F3.30.
The inverter will close automatic switchover function if this parameter is set to
be 0000min.

! This time only includes EDS800 running time.

F3.26 Water supply supervision Para. display range0~1 0


0: C-11, C-12 display voltage value of VCI, CCI.
1: C-11, C-12 display PID specified pressure and feedback pressure.

F3.27 Closed-loop adjusting characteristic range0, 1 0

0: Forward function. motor speed increases as specified value increases.


1: Reverse function. motor speed decreases as specified value increases.
F3.28 LED initial supervision Para. selection range0~14 1
This parameter defines initial supervision parameter selection during running or
stop. For example F3.28=3, LED displays output voltage initially, please press
SHIFT key if you want to see about other supervision parameter.
0: set frequency:It displays set-frequency when standby and displays output
frequency when running.
1: output frequency:It displays output frequency while running and standby.
2: output current
73
EDS800 series Service Manual

3: output voltage
4: DC bus bar voltage
5: motor speed
6: heat sink temperature
7: run time
8: accumulative run time
9: input terminal status
10: output terminal status
11: analog input VCI/PID provision
12: analog input CCI/PID feedback
13: reserved
14: exterior pulse input

F3.29 Zero freq. braking freq. at starting Range:0.00-15.00Hz 0.00Hz

Same as detailed description for F1.03 and F1.04.

F3.30 Failure relay TATBTC function selection range0~24 15

Same as detailed description for F5.10.


F3.31 VCI analog input gain Range:0-800% 100
VCI analog input gain,figure as following:

f
Gain is 150%
50Hz Gain is 100%

Gain is 50%

VCI

VCI analog input gain

6.5 Simple PLC run function parameter group: F4


The user can set by himself the output frequency direction and running time
of the inverter during a running cycle by simple PLC function according to spot craft
demand, as shown in Fig.6-19.

74
EDS800 series Service Manual
f6
d7
f2 a6 f7
Simple PLC run
a2 f5
d3
f1 d7
a1 a5

a3
f3 d5
a4 f4
T1 T2 T3 T4 T5 T6 T7

500ms
PLC step finishing indication

PLC circle finishing indication


Fig.6-19 simple PLC run
EDS800 serial inverter simple PLC run function provide 7 kinds of multi-step
speed run modesee below an example of 7 step speed. In Fig.6-20a1~a5, d1~d5 is
accelerating or decelerating time of relative stepset by accelerating decelerating
time parameter F0.08, F0.09 and F2.18~F2.29 in total 7 kinds of parameterf1~f7,
T1~T7 indicating set frequency and run time set by function code F4.01~F4.14.
Simple PLC run a6 f6 d7
f2 f7
a2
f5
f1 d3 d7
a1 a5
a3 f3
d5
a4
f4
T1 T2 T3 T4 T5 T6 T7

RUN command
Fig.6-20 stop after PLC single circle
PLC step finishing and circle finishing indication can be realized by outputting
500mS pulse indicator signal through open circuit collector terminal OCdetailed
function defined by F5.10.
rangeLED 1st bit0~3
Simple PLC run
F4.00 LED 2nd bit0, 1 000
setting
LED 3rd bit0, 1

This function code make use of its 1st bit, 2nd bit, 3rd bit to set PLC run mode,
PLC rerun mode after interruption, set run time unit, detail as follows:
75
EDS800 series Service Manual

LED 1st:
0: no action. PLC run mode ineffective.
1: stop after single circle. As shown in Fig.6-20, the inverter stops automatically
after finishing a circle, can only start when another run command is available.
2: keep final value after single circle. As shown in Fig.6-21the inverter keep
running according to frequency, direction of final step after finishing a circlethe
inverter wont stop according to set decelerating time until the stop command is
available.
f2 a6 f6 d7 f7
a2 f5
f1 d3 a5 d7
a1
a3 f3
d5
a4
f4
T1 T2 T3 T4 T5 T6 T7

RUN command

STOP command

Fig.6-21 holding mode after PLC single circle


f6 f6

f2 f7 f2 f7
d1
f5 f5 f1
f1 f1
d1
d2
PLC run
f3
f3

f4 f4
T1 T2 T3 T4 T5 T6 T7 T1 T2 T3 T4 T5 T6 T7 T1
First circle Second circle

RUN command

STOP command

Fig.6-22 PLC consecutive circle mode


3: consecutive circle. As shown in Fig.6-22the inverter start next circle
automatically after finishing a circleuntil there is stop command.
LED 2nd bit:
76
EDS800 series Service Manual

0: start from first step. Stop during running caused by stop command, failure
or power offafter restarting the inverter will run from first step.
1: continue to run from step frequency of interruption moment. When stop
during running caused by stop command or failurethe inverter will record current
step used time automatically and enter into this step automatically after restarting
continue to run for residual time according to defined frequency of this step, as
shown in Fig.6-23. The inverter will rerun from first step after restarting if power
off. Interruption signal

output freq.Hz f1
a1 d2

f3
a3
f2
a2 Time t
Step 1 Step 2
Used time Step 2 residual time
a1step 1 accelerating time a2step 2 accelerating time
a3step 3 accelerating time d2step 2 decelerating time
f1step 1 frequency f2step 2 frequency
f3step 3 frequency
Fig.6-23 PLC starting mode 1
LED 3rd bit : PLC run time unit
0: second; 1: minute
This unit is only effective to PLC run step timefor accelerating decelerating
time of PLC run period, their unit selection is determined by F0.07.
(1) If run time of PLC segment is set to 0this segment is ineffective.
(2) can make PLC process a pause, ineffective, work etc. through terminal, for detail please refer
note to terminal correlative function parameter group F5.

F4.01 Step 1 setting range000621 000

F4.02 Step 1 runtime range06000.0 10.0

F4.03 Step 2 setting range000621 000

F4.04 Step 2 runtime range06000.0 10.0

F4.05 Step 3 setting range000621 000

F4.06 Step 3 runtime range06000.0 10.0

F4.07 Step 4 setting range000621 000

77
EDS800 series Service Manual

F4.08 Step 4 runtime range06000.0 10.0

F4.09 Step 5 setting range000621 000

F4.10 Step 5 runtime range06000.0 10.0

F4.11 Step 6 setting range000621 000

F4.12 Step 6 runtime range06000.0 10.0

F4.13 Step 7 setting range000621 000

F4.14 Step 7 runtime range06000.0 10.0

F4.01~F4.14 utilize LED 1st bit, 2nd bit, 3rd bit to separately define frequency
settingdirection and accelerating decelerating time of PLC Run, see following for
detail:
LED1st bit: frequency setting
0: multi-step frequency i i=1~7 is defined by F2.30~F2.44.
1: frequency is determined by function code F0.00
LED 2nd bit: run direction selection
0: forward run
1: reverse run
2: determined by run command (FWD,REV)
LED3rd bit: accelerating decelerating time selection
0: accelerating decelerating time 1
1: accelerating decelerating time 2
2: accelerating decelerating time 3
3: accelerating decelerating time 4
4: accelerating decelerating time 5
5: accelerating decelerating time 6
6: accelerating decelerating time 7

78
EDS800 series Service Manual

6.6 Terminal correlative function parameter group: F5


F5.00 Input terminal X1 function selection range0~42 0

F5.01 Input terminal X2 function selection range0~42 0

F5.02 Input terminal X3 function selection range0~42 0

F5.03 Input terminal X4 function selection range0~42 0

F5.04 Input terminal X5 function selection range0~42 0

F5.05 reserved

F5.06 reserved

F5.07 reserved

Multi-function input terminal X1~X5 provides 43 kinds of selection mode for


the usercan choose based on spot requirement. For parameter function table please
see Table 6-2.
Table 6-2 multifunction input function selection table
item corresponding function item corresponding function

0 Leave control terminal unused 1 Multi-step speed control terminal 1

2 Multi-step speed control terminal 2 3 Multi-step speed control terminal 3

4 Multi-step speed control terminal 4 5 External forward run jog control

6 External reverse run jog control 7 Accel/Decel time selecting terminal 1

8 Accel/Decel time selecting terminal 2 9 Accel/Decel time selecting terminal 3

10 External device failure input 11 External restoration input

12 Free stop input 13 External stop command

14 stop DC braking input command DB 15 Inverter run prohibition

16 Frequency increasing command( UP) 17 frequency descending command( DOWN)

18 Accel/Decel prohibited command 19 Three-wire run control

20 Closed-loop ineffective 21 PLC ineffective


PLC stop status restoration (reset variable of PLC
22 Simple PLC pause command 23
interruption moment, make it restart from first

24 Frequency provision channel selection 1 25 Frequency provision channel selection 2

26 Frequency provision channel selection 3 27 Frequency switched to CCI

28 Command switched to terminal 29 Run command channel selection 1

79
EDS800 series Service Manual

30 Run command channel selection 2 31 Run command channel selection 3

32 Traverse runin 33 External interruption input

34 interior counter clearing end 35 interior counter triggering end

36 Interior timer clearing end 37 interior timer triggering end

38 Pulse frequency input( only effective for X5) 39 Reserved

40 Reserved 41 Reserved

42 Reserved

Now explain listed function in Table 6-2 as follows:


1~4: Multi-step speed control terminal. Can set 15 step speed run frequency
by choosing ON/OFF combination of these function terminal.
Table 6-3 multi-step speed run selection table
K4 K3 K2 K1 Frequency setting
OFF OFF OFF OFF Common run frequency

OFF OFF OFF ON Multi-step frequency 1

OFF OFF ON OFF Multi-step frequency 2

OFF OFF ON ON Multi-step frequency 3

OFF ON OFF OFF Multi-step frequency 4

OFF ON OFF ON Multi-step frequency 5

OFF ON ON OFF Multi-step frequency 6

OFF ON ON ON Multi-step frequency 7

ON OFF OFF OFF Multi-step frequency 8

ON OFF OFF ON Multi-step frequency 9

ON OFF ON OFF Multi-step frequency 10

ON OFF ON ON Multi-step frequency 11

ON ON OFF OFF Multi-step frequency 12

ON ON OFF ON Multi-step frequency 13

ON ON ON OFF Multi-step frequency 14

ON ON ON ON Multi-step frequency 15

Above multi-step frequency can be used in multi-step speed run and simple
PLC run, please see below an example of multi-step speed run:
We now define control terminal X1, X2, X3, X4 separately as follows:
After set F5.00=1, F5.01=2, F5.02=3, F5.03=4, X1, X2, X3, X4 are used for
realizing multi-step runas shown in Fig.6-24.

80
EDS800 series Service Manual

Output frequency
speed 11
speed 2 speed 7
speed 6 speed 9
speed 1 speed 15
Common set freq. time

Run command K1
on K2
multisection speed control terminal 1
on K3
multisection speed control terminal 2
on K4
multisection speed control terminal 3
on K5
multisection speed control terminal 4

Fig.6-24 multi-step speed run

In fig.6-25 see an example of terminal run command channelcan make forward,


reverse run control by K5, K6. In Fig.6-24, by different logic combination of K1, K2,
K3, K4the inverter can run according to common set frequency or multi-step
frequency based on above table.

3 phase breaker EDS800


L1 U
power
L2 V M
supply KM
L3 W
PE
K1 EDS800
K2 X5

K3 K5
K4 FWD COM
K6
REV
COM
COM

Fig.6-25 multi-step speed run Fig.6-26 exterior device failure always-open input

5~6: external jog run control input JOGF/JOGR.When run command


channel is set to terminal run command channel F0.02=1JOGF is jog forward
runJOGR is jog reverse runjog operation frequency, jog accelerating decelerating
time is defined in F2.06~F2.08 (remark: jog run command channel is determined by
F0.02)
7~9: Accel&Decel time terminal selection

81
EDS800 series Service Manual

Table 6-4 Accel&Decel time terminal selection logic mode

Terminal 2 Terminal 2 Terminal 1 Accel/Decel time selection

OFF OFF OFF Accel time 1/ Decel time 1

OFF OFF ON Accel time 2/ Decel time 2

OFF ON OFF Accel time 3/ Decel time 3

OFF ON ON Accel time 4/ Decel time 4

ON OFF OFF Accel time 5/ Decel time 5

ON OFF ON Accel time 6/ Decel time 6

ON ON OFF Accel time 7/ Decel time 7

Can realize selection for Accel&Decel time1~7 by ON/OFF combination of


Accel&Decel time terminal.
10 : external equipment fault input. Can input fault signal of external
equipment by this terminal to be convenient for the inverter to monitor fault of
external equipment. The inverter displaysE0.14, namely external equipment fault
alarm after receiving the external equipment fault signal.
11 : exterior restoration input. After the fault alarm takes place in the
inverter, can restore the inverter through this terminal. Its function is same as
function of RESET key on the operation panel.
12 : free stop input. This function is same as free stop during running defined
in F1.05but its realized by control terminal to be convenient for long-distance
control.
13 : exterior stop command. This command is effective to all run command
channelwhen this function is effective the inverter stops running in mode set by
F1.05.
14 : DC injection braking input command DB during stop. Implement DC
injection braking to the motor during stop by control terminalin order to realize
urgent parking and accurate orientation of the motor. Braking initial frequency,
braking time are defined in F1.06, F1.07.
15 : inverter run forbiddance. The inverter during running stops freely
when this terminal is effective and forbidden to start in waiting status. Mainly
applied to occasion needing safe linkage.
16~17: frequency increasing command UP/descending command DOWN.
82
EDS800 series Service Manual

Realize frequency increasing or descending by control terminal, which substitute for


keypad to realize long-distance control. Effective during common run if
F0.00=2.Increasing descending speed is set by F5.09.
18 : Accel&Decel speed forbidden command. Let the motor not effected by
any foreign signal(except stop command)keep running at current frequency.
Ineffective during normal decelerating stop.
note

19 : three-wire run control. Please refer to function description of F5.08


run mode (three-wire run mode).
20 : closed-loop ineffective. Realize flexible switch to lower level run
mode under closed-loop run status.
(1) can switch between closed-loop and lower level run mode only during closed-loop run(F3.00=1).
(2) start stop control, direction and Accel&Decel time are subject to setting of corresponding run mode
note when its switched to lower level run mode.

21 : PLC ineffective. Realize flexible switch to lower level run mode under PLC
run status.
(1) can switch between PLC and lower level run mode only during PLC run(F4.000).
(2) start stop control, direction and Accel&Decel time are subject to setting of corresponding run mode
note when its switched to lower level run mode.

22 : simple PLC pause command. Implement pause control to PLC process


during runningrun at zero frequency when this terminal is effectivenot time for
PLC run .after ineffective implement automatic speed tracking start and continue
PLC run. For application method please refer to function description ofF4.00~F4.14.
23 : PLC stop status restoration. Under stop status of PLC run mode, will
clear PLC run step, runtime, run frequency etc. recorded when PLC run stops if this
terminal is effectiveplease see F4 group function description.
24~26 : terminal frequency provision channel selection. Through ON/OFF
combination of frequency provision channel selection terminal 24, 25, 26can
realize frequency provision channel switch shown in Table 6-5. For relation of
terminal switch and function code F0.00 setting, that is, latter effective.
Table 6-5 terminal frequency provision channel selection logic mode
frequency frequency frequency
frequency provision channel
provision channel provision channel provision channel
selection
selection end 3 selection end 2 selection end 1

OFF OFF OFF hold freq. setting

OFF OFF ON potentiometer provision

83
EDS800 series Service Manual

OFF ON OFF keypad number provision


terminal UP/DOWN adjusting
OFF ON ON
provision

ON OFF OFF serial port provision

ON OFF ON VCI

ON ON OFF CCI

ON ON ON end PULSE provision

27: switch frequency to CCI. Frequency provision channel is switched to CCI


provision compulsorily when this function terminal is effective, frequency provision
channel come back to previous status when this function terminal is ineffective.
28 : command switched to terminal. Run command channel is switched to
terminal run command channel compulsorily when this function terminal is
effective.
29~31: terminal select run command channel
Table 6-6 run command channel logic mode
Run command Run command Run command
channel selection channel selection channel selection Run command channel
terminal 3 terminal 2 terminal 1

OFF OFF OFF hold run command channel

OFF OFF ON keypad run command channel

end run command channel (keypad


OFF ON OFF
STOP command ineffective)
end run command channel (keypad
OFF ON ON
STOP command effective)
serial port run command channel
ON OFF OFF
(keypad STOP command ineffective)
serial port run command channel
ON OFF ON
(keypad STOP command effective)
Can realize control command selection shown in Table 6-6 by ON/OFF
combination of run command channel selection terminalFor relation of terminal
switch and function code F0.00 setting, that is, latter effective.
32 : traverse jump-in. When traverse start mode is manual jump-intraverse
function effective if this terminal effectivesee F6 function parameter description.
33 : exterior interruption input. The inverter close off output and run at zero
frequency during running upon receiving exterior interruption signal. The inverter
implement automatic speed tracking start-up to resume running once external
84
EDS800 series Service Manual

interruption signal is relieved.


34 : interior counter clearing end. To clear built-in counter in the inverter with
cooperation of counter triggering signal.
35 : interior counter triggering end. Counting pulse input port of built-in
counterpulse max. frequency: 200Hzsee function code F5.24, F5.25.
36 : interior timer clearing end. To clear built-in timer in the inverter with
cooperation of timer triggering signal.
37 : interior timer triggering end. Please see function description for parameter
F5.27.
38 : pulse frequency input( only effective to X5). Only effective for
multifunction input terminal X5, this function terminal receive pulse signal as
frequency provision, for relation between inputted signal pulse frequency and set
frequency in detail, please refer to F7 group parameter.
39 : reserved
40 : reserved
41 : reserved
42 : reserved
F5.08 FWD/REV run mode selection range03 0
This parameter defines 4 kinds of exterior terminal control mode for inverter
running.
0: 2-wire control mode 1
K2 K1 run EDS800
K1
0 0 stop FWD
K2
1 0 reverse run
REV
0 1 forward run
COM
1 1 stop

Fig.6-27 2-wire run mode 1


0: 2-wire control mode 2
K2 K1 run
EDS800
K1
0 0 stop
FWD
1 0 stop K2
REV
0 1 forward run
COM
1 1 reverse run

Fig.6-28 2-wire run mode

85
EDS800 series Service Manual

2: 3-wire control mode 1


thereinto:
EDS800
SB1: stop button SB2
FWD
SB1
SB2: forward run button Xi

SB3: reverse run button SB3


REV

COM

Fig.6-29 3-wire run mode 1


Xi is multifunction input terminal of X1~X5, here should define its corresponding
terminal function as No. 19 3-wire run control function.
3: 3-wire control mode 2
EDS800
SB1: stop button SB2
FWD run direction
SB2: run button K2
selection
SB1
Xi 0 Forward run
K2 1 Reverse run
REV

COM

Fig.6-30 3-wire run mode 2


Xi is multifunction input terminal X1~X5, here should define its corresponding
terminal function as No. 19 3-wire run control function.
The inverter restores after failure and start at once if run command channel
selecting terminal and terminal FWD/REV is effective during warning alarm stop.
F5.09 UP/DOWN speed range0.0199.99Hz/S 1.00Hz/S
This function code defines varying rate of the set frequency when its modified
by UP/DOWN terminal.

F5.10 Open collector output terminal OC output setting range0~24 0

F5.11 reserved

F5.12 reserved
F5.13 reserved
OC open collector output terminalTable 6-7 shows option of above 4 function
86
EDS800 series Service Manual

parameterchoosing same output terminal function repeatedly is allowed.


Table 6-7 output terminal function selection table
item corresponding function item corresponding function

0 Inverter running signal (RUN) 1 Frequency arriving signal (FAR)


2 Frequency level detectingsignal (FDT1) 3 reserved
4 Overload warning signal( OL) 5 Output Freq. reach high limit( FHL)
6 Output Freq. reach low limit( FLL) 7 Inverter stops for under voltage blockage (LU)
8 Stop for exterior failure( EXT) 9 Inverter zero speed running
10 In PLC run process 11 Simple PLC segment run finished
12 PLC finish one cycle run 13 reserved
14 Inverter is ready for run( RDY) 15 Inverter failure
16 traverse high&low limit restriction 17 Interior counter final value arrive
18 Interior counter specified value arrive 19 Set runtime arrive
20 Interior timer timing arrive 21 reserved
22 reserved 23 reserved
24 reserved

Now introduce function listed in Table 6-7 as follows:


0: inverter during running( RUN). The inverter is in run statusoutput
indicator signal.
1: frequency arriving signal( FAR). Refer to function description of F5.14.
2: Frequency level detecting signal( FDT1). Refer to function description of
F5.15~F5.16.
3: reserved
4: overload warning signal( OL). Inverter output current exceed F9.05
overload detect level and time exceed F9.06 overload detect timeoutput
indicator signal.
5: output frequency reach high limit( FHL). When set frequencyhigh limit
frequency and run frequency reach high limit frequencyoutput indicator signal.
6: output frequency reach low limit( FLL). When set frequencylow limit
frequency and run frequency reach low limit frequencyoutput indicator signal.
7: Inverter stops for under voltage blockage( LU). When the inverter is
running, LED displaysP.OFF and output indicator signal if DC bus-bar voltage is
lower than limitative level.
8: stop for exterior failure( EXT). When the inverter give the alarm (E014)
and stops for exterior failure, output indicator signal.
87
EDS800 series Service Manual

9 : inverter zero speed running. When the inverter output zero frequency
but
in run status, output indicator signal.
10 : In PLC run process
11: Simple PLC segment run finished. After simple PLC current segment run
is finishedoutput indicator signal(single pulse signalwidth 500ms).
12 : PLC finish one cycle run
13 : reserved
14 : Inverter is ready for run( RDY). If this signal is effective, shows that
bus-bar voltage is normal and run prohibition terminal is ineffective, the inverter can
receive start-up command.
15 : Inverter fault. If failure takes place when the inverter is running, the
inverter output indicator signal.
16 : Traverse high&low limit restriction. After choosing traverse
function, if frequency fluctuant range based on center frequency of traverse is above
high limit frequency F0.10 or under low limit frequency F0.11, the inverter will
output indicator signal, as shown in Fig. 6-31.
output
set
High limit freq. checkout range

Low limit time

Y
OC: traverse
fluctuation time

Fig.6-31 traverse range restriction Fig.6-32 freq. arriving signal output


17 : Interior counter final value arrive
18 : Interior counter specified value arrive
17~18 please refer to function description of F5.25~F5.26.
19 : Set runtime arrive. When accumulative runtime of the inverter (F2.52)
reach set runtime(F2.51)output indicator signal.
20 : Interior timer timing arrive. Refer to function description for F5.27.
21 : Reserved
22 : Reserved
23 : Reserved
24 : Reserved
88
EDS800 series Service Manual

F5.14 Freq. arriving(FAR)detect range range0.0050.00Hz 5.00Hz

This parameter is supplementary definition to No. 1 function in Table 6-7.As


shown in Fig.6-32when output frequency of the inverter is within high&low detect
range of set frequencyoutput pulse signal.
F5.15 FDT1freq. levelelectric level range0.00high limit frequency 10.00Hz

F5.16 FDT1 lag range0.0050.00Hz 1.00Hz


Output freq.
F5.15~F5.16 is supplementary
FDT1electric FDT1 lag
definition to No.2 function in level
Table 6-7, introduce as follows:When
time
output frequency exceed the set frequency
(FDT1 electric level)output indicator signal Y
till output frequency descend to be some
time
frequency(FDT1 electric level-FDT1 lag)
lower than FDT1 electric levelas shown in Fig.6-33. Fig.6-33 freq. level detecting

F5.17 Analog outputAOselection range09 0

0: output frequency( 0high limit frequency)


1: set frequency( 0high limit frequency)
2: output current( 02rated current)
3: output voltage( 01.2load motor rated voltage)
4: bus-bar voltage( 0800V)
5: PID provision (0.00-10.00V)
6: PID feedback (0.00-10.00V)
F5.18 Analog outputAOgain rang0.002.00 1.00

F5.19 Analog outputAOoffset rang0.0010.00V 0.00


For AO analog output, the user can modify display measuring range or emend
meter head error by adjusting output gain if necessary.

F5.20 reserved

F5.21 reserved

F5.22 reserved

89
EDS800 series Service Manual

F5.23 DO terminal output function selection range0~9 0


Same as F5.17 function parameter description.

F5.24 DO max. pulse output freq. range0.120.0max. 20KHz 10.0

DO port max. output pulse frequency corresponds to maximum value optioned


by F5.23for example 0: output frequencythen max. Output pulse frequency
corresponds to high limit frequency.
F5.25 Set interior count number arriving provision range09999 0

F5.26 Specified interior count number arriving provision range09999 0


F5.25, F5.26 is supplementary definition to No. 17, 18 function in Table 6-7.
Set count number provisionshows that when some number of pulse are
inputted to Xi(count triggering signal input function terminal), OC (open collector
Output terminal) output a indicator signal.
As shown in Fig.6-36OC output an indicator signal when the 8th pulse is
inputted to Xi. Here F5.25=8.
Specified count number provisionshows that when some number of pulse are
inputted to Xi, Yi output a indicator signaltill set count number is reached.
As shown in Fig.6-34TA, TB, TC start to output an indicator signal when the
5th pulse is inputted to Xi. Until set count number 8 is reached. Here F5.26=5.
Specified count number is ineffective when it is bigger than set count number.

1 2 3 4 5 6 7 8 9
Xi input

OC

TA, TB, TC

Fig.6-34 set count number and specified count number provision


F5.27 Interior timer timing setting range0.16000.0s 60.0

This parameter is used to set timing time of interior timer of the inverter.The
timer is activated by exterior triggering end(triggering end selected by F5.00~F5.07),
the timer begins timing upon receiving exterior triggering signal, after its up to
timing time one effective pulse signal of 0.5s will be outputted from relative OC end

90
EDS800 series Service Manual

6.7 traverse special function parameter group: F6


F6.00 traverse function selection range0, 1 0
0: traverse function ineffective
1: traverse function effective
rangeLED 1st bit: 0, 1
F6.01 traverse run mode 00
LED 2nd bit: 0, 1
0: automatic jump-in mode. After start-up run at traverse preset frequency for
a period of time, then enter into traverse operation automatically.
1: terminal manual run mode. When set the multifunction terminal Xi
( Xi=X1~X5)to function 32 and its effective, enter into traverse state; quit traverse
state if ineffective and run frequency is at traverse preset frequency.
LED 2nd bit:
0: changing amplitude. Amplitude AW varies with center frequency, for its
changing rate please see F6.02 definition.
1: fixed amplitude. Amplitude AW is determined by high limit frequency and
F6.02.

! Traverse center frequency input setting channel is set by F0.00 function.

F6.02 traverse amplitude range0.050.0() 0.0()

changing amplitude: AW=center frequencyF6.02


fixed amplitude: AW=high limit frequencyF6.02
Traverse run frequency is restricted by high limit, low limit frequencyif set improperly
note abnormal traverse operaion arise.

F6.03 Sudden jumping freq. range0.050.0% 0.0()

As shown in Fig.6-37.If this parameter is set to 0, no jumping frequency.

F6.04 traverse cycle range0.1999.9S 10.0S

Whole time for a cycle including traverse rising, descending process.


Triangle wave Range: 0.0-98.0()
F6.05 50.0(%)
rising time (traverse cycle)
Define runtime of traverse rising segment=F6.04F6.05 (s)runtime of
descending segment = F6.04(1-F6.05) (s). Please refer to description in Fig.6-35.
91
EDS800 series Service Manual

Traverse preset
F6.06 range0.00400.00Hz 0.00Hz
frequency
Traverse preset
F6.07 range0.06000S 0.0S
frequency latency time
F6.06 is used for defining inverter run frequency before entering into traverse
operation.
When automatic start-up mode is optionedF6.07 is used for setting holding
time running at traverse preset frequency before enter into traverse operationWhen
manual start-up mode is optionedF6.07 setting is ineffective. Please see description in
Fig.6-35.
traverse amplitude
Run freq. Hz
AW=Fset*F6.02
traverse high limit Fh
+AW
center freq.Fset
-AW
traverse low limit FL
traverse preset freq. Weaving sudden
jumping freq.
a1 =AW*F6.03

triangle wave rising time time t


weaving =F6.04*F6.05
Accel per start-up latency Decel per
traverse cycle
accel time time F6.07 Decel time
run command
stop command
Fig. 6-35 traverse

6.8 Frequency provision function parameter group: F7


F7.00 VCI minimum provision range0.00F7.02 0.0V
Corresponding freq. to VCI
F7.01 range0.00high limit frequency 0.00Hz
minimum provision
F7.02 VCI max. provision range0.0010.00V 10.0V
Corresponding freq. to VCI range0.00high limit
F7.03 50.00Hz
maximum provision frequency
F7.04 CCI minimum provision range0.00F7.06 0.00V
Corresponding freq. to CCI
F7.05 range0.00high limit frequency 0.00Hz
minimum provision
F7.06 CCI max. provision range0.0010.00V 10.00V

92
EDS800 series Service Manual

Corresponding freq. to CCI


F7.07 range0.00high limit frequency 50.00Hz
max. provision
F7.08 Max. Input pulse width 0.1-999.9ms(whenF0.00=11) 100.0ms
0.0-F7.11(Max.provision pulse)
F7.09 Min. Input pulse width 0.0ms
(whenF0.00=11)
min. provision
F7.10 0.00high limit frequency 0.00Hz
corresponding freq.
Rang:F7.09(Min.provision
Max. provision pulse
F7.11 pulse)-F7.08(Max.provision 100.0ms
width
pulse)
max. provision
F7.12 Range: 0.00high limit frequency 50.00Hz
corresponding freq.
F7.13 PULSE max. pulse input range0.120.0K 10.0K

PULSE minimum
F7.14 range0.0F7.16 0.0K
provision
Corresponding freq. to
F7.15 range0.00high limit frequency 0.00Hz
PULSE min. provision
rangeF7.14(PULSE min.
F7.16 PULSE max. provision provision)F7.13(max. 10.0K
input pulse)

Corresponding freq. to range0.00high limit


F7.17 50.00Hz
PULSE max. provision frequency

When choose F0.00=11(terminal pulse setting freq.).the function of above


parameter effective.
Pulse width in milliseconds ,the freq. of input pulse width can effect the precision
of output freq., to assure the precision of output freq.,customer advised use the freq.
of pulse width between 1Hz to 100Hz.
Please dont use these function for the application where there use close freq
control.
F2.00 sets the analog channel filtering time constantto filter input signalthe
more long filtering time is, the more great anti-jamming ability is, but response
speed descend; the more short filtering time is, the more fast the inverter respond,
but anti-jamming ability is weakened.

93
EDS800 series Service Manual

Set freq. Set freq.


fmax fmax

fmin fmin
A A

Amin Amax Amin Amax


(1) plus characteristic (2) minus characteristic
A:VCI provision
Amin:min. provision fmin:corresponding freq. of min. provision
Amax:max. provision fmax:corresponding freq. of max. provision

See below relation curve of CCI and set frequency:

Set freq. Set freq.


fmax fmax

fmin fmin
A A

Amin Amax Amin Amax


(1) plus characteristic (2) minus characteristic
A: CCI provision
Amin:min. provision fmin:corresponding freq. of min. provision
Amax:max. provision fmax:corresponding freq. of max. provision
See below relation curve of PULSE and set frequency:

Set freq. Set freq.


fmax fmax

fmin fmin
P P

Pmin Pmax Pmin Pmax


(1) plus characteristic (2) minus characteristic
P: PULSE provision
Pmin: min. provision fmin: corresponding freq. to min. provision
Pmax: max. provision fmax: corresponding freq. to max. provision

94
EDS800 series Service Manual

6.9 Motor and vector control function parameter group: F8


F8.00 reserved

F8.01 Motor rated voltage Range: 1480V Depend on device type

F8.02 Motor rated current Range: 0.1999.9A Depend on device type

F8.03 Motor rated frequency Range: 1.00400.00Hz Depend on device type

F8.04 Motor rated speed Range: 19999r/min Depend on device type

F8.05 Motor pole Range: 2-14 Depend on device type

F8.06 Motor rated power Range: 0.1999.9KW Depend on device type

F8.07 reserved

F8.08 reserved

F8.09 reserved

F8.10 reserved

F8.11 reserved

F8.12 reserved

F8.13 reserved

F8.14 reserved

F8.15 reserved

F8.16 Frequency display offset Range:0.00-2.00Hz 0.20Hz

F8.17 Reserved

Please set F8.01~F8.06 according to rated data of drived motor for safety.
6.10 Protection function parameter: F9

F9.00 reserved

F9.01 failure self-restoration times range010 0


F9.02 failure self-restoration interval range0.520.0S 5.0S
During run process, failure will take place accidently due to load fluctuation
and the inverter will cut off output, here failure self-restoration function can be

95
EDS800 series Service Manual

applied in order to let the device continue to run. During self-restoration, the inverter
will try to resume running in speed checking restart mode but stop outputting and
failure protected if the inverter cant resume running successfully within set times.
Self-restoration function will be shut down if failure self-restoration times is set to 0.
(1) To use failure self-restoration function must take device allowance and no essential
failure in the inverter as preconditions.
! (2) Self-restoration function is ineffective to failure protection caused by overload and
over heat.

F9.03 Motor overload protection mode selection range0, 1 1


This parameter defines protecting action mode when overload, overheat take
place in the inverter.
0: no action. No motor overload protection characteristic(apply with caution)
here the inverter have no overload protection for load motor
1: inverter cut off output at once. The inverter cut off output and motor stop
freely when overload, overheat take place.

F9.04 motor overload protection coefficient range20.0-120.0(%) 100.0(%)


This parameter sets sensibility of the inverter implementing thermal relay
protection to load motor, can implement correct heat protection to the motor by
setting this value when output current value of load motor dont match rated current
of the inverter, as shown in Fig.6-36.
Value of this parameter can be determined by following formula:
motor rated current
F9.04= 100
inverter rated output current
The inverter will lose thermal relay protection function when a piece of inverter drive multiple
motors in parallel. Please assemble heat protection relay at input side of each motor to protect
note them effectively.

time
Alarm level Output current
[F9.05]

[F9.04]=50% [F9.04]=100%
1 minute Yn

current
high high
55% 110% 150% (G)
time
105% 120% (P) [F9.06] [F9.06]
Fig.6-36 electronic thermal relay protection Fig.6-37 overload alarm
96
EDS800 series Service Manual

F9.05 overload alarm checkout level range20200() 130(%)

F9.06 overload alarm delay time range0.020.0S 5.0S


If output current exceeds electric level set by parameter F9.05 continuously
open collector outputs effective signal(refer to Fig.6-37 and interrelated description
of parameter F5.10 ) after delay time set by F9.06 passed.
F9.07 Overvoltage stall selection range0, 1 1

F9.08 Stall overvoltage point range120-150(%) 140(%)

0: banned
1: allowed
Actual descending rate of motor speed may be lower than that of output
frequency due to effect from load inertia when the inverter is in decelerating run
process, here the motor will feed electric energy back to inverter which will make
DC bus-bar voltage of the inverter increase, overvoltage protection will takes place
if not take steps. Overvoltage stall protection function, indicates that output
frequency of the inverter stops descending if bus-bar voltage detected during run
process exceed stall voltage point defined by F9.08 (relative to standard bus-bar
voltage) and the inverter continue to implement decelerating run when bus-bar
voltage detected again is lower than stall overvoltage point. As shown in Fig. 6-38.

stall
overvoltage
point

time

output frequency

time
Fig.6-38 overvoltage stall function

97
EDS800 series Service Manual

automatic current
F9.09 range110200() 150(%)
limiting level
frequency descending
F9.10 range0.0099.99HzS 10.00Hz/S
rate during current limiting
automatic current
F9.11 range0, 1 0
limiting action selection
By automatic current limiting function the inverter can limit load current not to
exceed automatic current limiting level set by F9.09 to avoid tripping out for failure
caused by rushing current. This function is especially suitable for some biggish
inertia or acutely changing load occasion.
Automatic current limiting (F9.09) defines current threshold value of automatic
current limiting action, its value is the percentage relative to inverter rated current.
Frequency descending rate during current limiting (F9.10) defines adjusting rate to
output frequency during automatic current limiting action.
If frequency descending rate during automatic current limiting F9.10 is too
smallinverter isnt easy to get rid of automatic current limiting state which may
cause overload failure finallyIf descending rate F9.10 is too big, the inverter may
be in generating state for long time which will cause overvoltage protection.
Automatic current limiting function is effective in accelerating decelerating state
and whether its effective in constant speed run state is determined by automatic
current limiting action selection (F9.11).
F9.11=0 indicates that automatic current limiting is ineffective during constant
speed running
F9.11=1 indicates that automatic current limiting is effective during constant
speed running
Output frequency may varies during automatic current limiting actionso
automatic current limiting function is not suitable for occasion demanding stable
output frequency during constant speed run.

98
EDS800 series Service Manual

6.11 Failure record function parameter: Fd


Fd.00 previous one failure record range 0~23 0

Fd.01 previous two failure record range 0~23 0

Fd.02 previous three failure record range 0~23 0

Fd.03 previous four failure record range 0~23 0

Fd.04 previous five failure record range 0~23 0

Fd.05 previous six failure record range 0~23 0


0: no failure
123: failure E0.01-E0.23please see chapter 7 for specified failure type.
Fd.06 Set freq. at previous failure range 0-high limit 0

Fd.07 Output freq. at previous failure range 0-high limit 0

Fd.08 output current at previous failure range 0-999.9A 0

Fd.09 output volt. at previous failure range0-999V 0

Fd.10 DC bus-bar vlot. at previous failure range0~800V 0

Fd.11 Load motor speed at previous failure range0~9999 0

Fd.12 Module temp. at previous failure range0~100 0

Fd.13 Input end state at previous failure 0

Fd.14 Accu. runtime at previous failure range0~65535h 0

6.12 Code and manufacturer function parameter: FF


FF.00 user password range 00009999 0000

User password setting function is used for prohibiting unauthorized personnel


from consulting and modifying function parameter.
Set this function code to 0000 when user password function isnt wanted.
ENTER
First input 4 bits number as user password and press DATA key to confirm, then
the password will come into effect at once.
Password modification:
ESC
Enter into password verification state by pressing MENU key, after inputting

99
EDS800 series Service Manual

primary 4 bits password parameter editing state is availablechoose FF.00(here


ENTER
FF.00=0000)input new password and press DATA key to confirmthen the
password come into effect at once.
Please keep the password you set without fail, in case the password is missing please
note consult the manufacturer.

FF.01 manufacturer password range 00009999 0000

Setting function for the manufacturer, user need not modify it.

100
EDS800 series Service Manual

7 Troubleshooting
7.1 Failure and countermeasure
Possible failure types in EDS800 are shown in Table 7-1 and failure code is
from E001 to E023. Some failure code is reserved for intelligent automatic diagnosis
function which will be executed continuously in future. When failure takes place in the
inverter, the user should check according to note of this table first and record failure
phenomena detailedly. Please contact our after-sale service and technical support
Department or agent in your local place when technical service is needed.
Table 7-1 failure type and the countermeasure
failure
failure type possible reason countermeasure
code
Accelerating time is too
Prolong accelerating time
short
Adjust V/F curve settingadjust
Improper V/F curve manual torque boost or change to
overcurrent automatic torque boost
during
E001 Set speed checking restart
accelerating Restart rotating motor
function
process
Low power source
Check input power supply
voltage
Too small power of the
Choose inverter with high-power
inverter
Decelerating time is too
Prolong decelerating time
short
overcurrent
Increase braking power of
during Have potential energy
E002 external energy consumption
decelerating load or big inertia load
braking subassembly
process
Power of inverter is a bit
Choose inverter with high-power
small
Load change suddenly or
Have unwonted Check or reduce break of the load
phenomena
overcurrent Accel/Decel time is set Prolong accelerating decelerating
E003 during constant to too short time properly
speed process low power source
Check input power supply
voltage
Power of inverter is a bit
Choose inverter with high-power
small
Unwonted input voltage Check input power supply
overvoltage
during Prolong accelerating time
E004 Accel time is set to too short
accelerating properly
process Set speed checking restart
Restart rotating motor
function

101
EDS800 series Service Manual
Decelerating time is too
overvoltage Prolong decelerating time
short
during
E005 Increase braking power of
decelerating Have potential energy
process external energy consumption
load or big inertia load
braking subassembly
Unwonted input voltage Check input power supply
Accel/Decel time is set Prolong accelerating decelerating
Overvoltage to too short time properly
E006 during constant
speed process Input voltage change Assemble reactor
abnormally
Use energy consumption
Load inertia is a bit big
subassembly
controlpower
Check input power supply or look for
E007 supply Unwonted input voltage
service
overvoltage
Accel time is set to too
Prolong accelerating time
short
DC injection braking is Reduce DC injection braking
too big currentprolong braking time
Adjust V/F curve and torque
improper V/F curve
Inverter boost
E008
overload Set speed checking restart
Restart rotating motor
function
power source voltage is
check power source voltage
too low
Load is too big Choose inverter with high-power
Adjust V/F curve and torque
improper V/F curve
boost
power source voltage is
check power source voltage
too low
Can choose frequency conversion
General motor run at low
motor for long time low speed
speed with big load
E009 Motor overload run
motor overload
to set motor overload protection
protection factor set
factor correctly
incorrectly
motor blocked up or load
change too suddenly and Check the load
quickly
To clear air-path or improve
Air-path blocked
ventilation condition
inverter over Ambient temperature is too Improve ventilation condition,
E010
heating high lower carrier frequency
Fan damaged Replace the fan
E011 reserved reserved reserved
E012 reserved reserved reserved

102
EDS800 series Service Manual
Transient overcurrent of the Refer to countermeasure for
inverter overcurrent
phase to phase short
circuit or earthing short wiring again
circuit of output 3 phase
Air-path blocked or fan To clear air-path or replace the
damaged fan
Ambient temperature is too
Lower ambient temperature
high
Inverting
Connecting wire or insert on
E013 module
protection control board Check and connect the wire again
loose
Unwonted current wave
caused by missing Check wiring
output phase etc.
Assistant power supply
Look for service from
damaged and drive
manufacturer or agent
voltage lacking
Unwonted control board Look for service from
manufacturer or agent
use sudden stop STOP
key in non-keypad run Look up operation mode
mode
external device Use sudden stop STOP
E014
failure key under condition of Set running parameter correctly
stall
Sudden stop terminal for Open external failure terminal after
external failure closed external failure is settled
Connecting wire or
insert on control board Check and connect the wire again
loose
current Assistant power supply Look for service from
E015 detecting circuit damaged manufacturer or agent
failure Hall component Look for service from
damaged manufacturer or agent
Unwonted amplifying Look for service from
circuit manufacturer or agent
Baud rate set improperly set Baud rate properly
Serial port STOP key to resetlook
press RESET
RS485 communication error
for service
E016 communication
failure Failure warning
Modify F2.16, F2.17
parameter set improperly
Upper device doesnt Check if upper device work and
work wiring is correct
E017 reserved reserved reserved
E018 reserved reserved reserved

103
EDS800 series Service Manual

E019 Under voltage Under voltage check spot input voltage


Reset by pressing RESETSTOP key

Serious disturbance or add mains filter at power


System
E020 supply input side
disturbance
Main control DSP read Reset by the key-press, look for
and write wrongly service
E021 reserved reserved reserved
E022 reserved reserved reserved
STOP
Reset by pressing RESET
E2PROM read Mistake take place when
E023 and read or write control Look for service from
write wrongly parameter manufacturer or agent
P.OFF Under voltage Under voltage check spot input voltage

7.2 Failure record lookup


This series inverter can record latest 6 failure code and inverter run parameter
of the last failure, to search these informations can redound to finding out reason of
the failure.
Failure information is all stored in Fd group parameterplease enter into Fd
group parameter to see about information by referring to keypad operation method.

code content code Content


Fd.00 previous one failure record Fd.08 output current at previous failure
Fd.01 previous two failure record Fd.09 output volt. at previous failure
Fd.02 previous three failure record Fd.10 DC bus-bar vlot. at previous failure
Fd.03 previous four failure record Fd.11 load motor speed at previous failure
Fd.04 previous five failure record Fd.12 module temp. at previous failure
Fd.05 previous six failure record Fd.13 input end state at previous failure
Fd.06 set freq. at previous failure Fd.14 Accu. runtime at previous failure
Fd.07 output freq. at previous failure

7.3 Failure reset


(1) Before reset you must find out reason of failure downright and eliminate it, otherwise
may cause permanent damage to the inverter.
! (2) If cant reset or failure takes place again after resetting, should look for reason and
continuous resetting will damage the inverter.
(3) Reset should take place 5 minutes after overload, overheat protection action.

104
EDS800 series Service Manual

To resume normal running when failure takes place in the inverter, you can
choose following any kind of operation:
Set any one terminal of X1~X5 to external RESET input (F5.00~F5.04=11),
open it after connected to COM.
STOP
When failure code is displayedpress RESET key after restoration is confirmed.
Cut off power supply.

105
EDS800 series Service Manual

8 Maintenance
8.1 Routine maintenance
When you use EDS800 series you must assemble and operate it according to
demand listed in thisservice manualstrictly. During run state, temperature,
humidity, vibration and aging parts may affect it. To avoid this, it is recommended to
perform routine inspections.
Table 8-1 Daily inspection items
period
Inspection
Inspection content Criterion
daily periodic item

(1)output current (1)within range of rated value


Run state
(2)output voltage (2)within range of rated value
parameter
(3)inside temp. (3)temp. increment < 35
(1)good ventilation, unblocked
(1)installing ambient
Cooling air-path

system (2)rotate normally without abnormal
(2)local fan
noise
(1)heating (1)no abnormality
Motor
(2)noise (2)even
(1)vibration balanced, proper wind
(1) vibration, heating
temp.
Inverter
(2)noise (2) without abnormal sound
(3)fixation of lead, terminal (3)fixed screw dont loose
(1)-10~+40
40~50used in lower volume
(1)temperature, humidity
or execute compulsory heat
Run
dissipating
ambient
(2)dust, water and leakage (2)no water leakage imprint, no dust
(3)gas (3)no peculiar smell
Recommend to inspect with following instrument:
Input voltage: electric voltmeteroutput voltage: rectifying voltmeterinput
output current: pincers ammeter.

106
EDS800 series Service Manual

8.2 Inspection and replacement of damageable parts


Some component parts in the inverter will be abraded or bear descending
performance for long-term usageto assure that the inverter can run stably and
reliably, it is recommended to perform defending maintenance and replace
corresponding parts if necessary.
(1) cooling fan
Abnormal noise, even oscillation may take place if the fan have wearing
bearing, aging blade, here replacement of the fan should be considered.
(2) filter electrolyte capacitance
When frequent-changing load causes increasing pulsant current and aging
electrolyte under high ambient temperature, the electrolyte capacitance may be
damaged and here should replace it.
8.3 Repair guarantee
(1) Within 18 months from purchasing date, if failure caused by inverter itself takes
place under normal conservation and usage, we will provide free repair service.
(2) We will take some upkeep if one of following situations takes place within
period of repair guarantee.
a. If did not use the inverter according toservice manualstrictly or did not use
it under ambient demanded inservice manual, which cause failure.
b. Failure caused by applying the inverter to non-normal function;
c. Failure caused by self-repair, refit which is not already allowed;
d. Damage caused by bad keeping, falling down from high place or other
extrinsic factor after purchasing the inverter;
e. Failure caused by natural disaster or its reason such as unwonted voltage,
thunderbolt, water fog, fire, salt corroding, gas corroding, earthquake and
storm etc.;
f. Make bold to tear up product logo (such as: nameplate etc.); Body serial
number dont accord with that in repair guarantee card.
(3) We calculate service fee based on actual cost, which is subject to contract if any.
(4) You can contact the agent and also our company directly if you have questions.
After repair guarantee period, we shall also provide lifetime charged repair
service for our products.

Our company will also provide lifetime repair service with fee for inverter which is not
note within period of repair guarantee.

107
EDS800 series Service Manual

8.4 Storage
The user must pay attention to following points for temporary storage and
long-term storage after purchasing the inverter:
(1) Avoid storing the inverter in high temperature, moist place and place of dust,
metal powder and assure good ventilation.
(2) Longtime storage will cause electrolyte capacitance of low quality, so must
assure that its electrified for one time within 2 years and electrification time is
not shorter than 5 hours and input voltage must be increased to rated value
gradually by voltage adjustor.

108
EDS800 series Service Manual

9 Examples
9.1 Common speed regulation running
9.1.1 Basic wiring diagram
3 phase breaker motor
L1 U
power supply L2 V M
EDS800 W
L3 E

TA failure waring light


L1
TB
ENTER
DATA
TC
L2

AO
cymometer
GND

Fig. 9-1
9.1.2 Set following basic parameter:
(1) set parameter F8.01-F8.06 according to rated value of the inverter.
(2) set F0.00 parameter to 0choose keypad analog potentiometer to set frequency.
(3) set F0.02 parameter to 0choose keypad to control start-up, stop.
(4) use F0.03 parameter to set run direction.

(1) Press key to set frequency.


STOP
(2) To press RESET keythe inverter will stop.
ENTER
note (3) To press DATA keyinverter enter into next menu or confirm data.
(4) Press key to increase or decrease the data.

9.1.3 Realized function


(1) realize stepless speed regulation to the motor, use keypad to control start/stop and keypad
analog potentiometer to adjust frequency.
(2) bear failure warning function.
(3) connect with cymometerwhich indicates output frequency of the inverter.
9.1.4 Application field
Used for common speed regulation fieldsuch as: transportation machine, china
machine, baccy machine, metallurgy machine etc.
109
EDS800 series Service Manual

9.2 Terminal control running


9.2.1 Basic wiring diagram
3 phase breaker
L1 U motor
V M
power supply L2 EDS800
W
L3 E

TA failure waring light


forward run FWD L1
reverse run TB
REV
TC L2
COM

+10V
specified signal 10K AO
VCI ammeter
GND GND

Fig. 9-2
9.2.2 Parameter setting
(1) set parameter F8.01-F8.06 according to rated value of the inverter.
(2) set F0.00 parameter to 4, 5 to choose VCI, CCIaccordingly, can accept frequency
set signal within 0~10V.
(3) set F0.02 parameter to 1to choose terminal run command channel.
(1) if F5.08=0,namely 2 wire control mode 1FWD and COM are closedmoter is in
forward runREV and COM are closedmotor is in reverse run FWD, REV and
note
COM are closed or opened togetherthe inverter stop.
(2) set frequency is specified through VCI analog channel.

9.2.3 Realized function


(1) control forward run/reverse run of the motor by external on-off quantum.
(2) control speed of the motor by 0~10V signal.
(3) bear failure warning and output current indication function.
9.2.4 Application field
Used in field where need long-distance control to start/stop of the motor such
as blower, food, chemical machine, packing machine, transportation machine etc.
9.3 Multi-step speed control running
9.3.1 Parameter setting
(1) set parameter F8.01-F8.06 according to rated value of the inverter. set F0.02

110
EDS800 series Service Manual

parameter to 1to choose terminal run command channel.


(2) F2.30-F2.44: multi-step speed frequency setting.
(3) F5.00-F5.04 set multi-step speed terminal control function.
(1) If F5.08=0,namely 2 wire control mode 1FWD and COM are closedmoter is
in forward runREV and COM are closedmotor is in reverse runFWD, REV and
COM are closed or opened togetherthe inverter stop.
(2)If any one or more terminal of X1, X2, X3 and COM are closed together, the
! inverter will run according to multi-step speed frequency determined by X1, X2,
X3 (multi-step speed frequency set value are determined by F2.30-F2.44).Can
realize manual control and automatic control for multiple frequency, and also
control for forward run, reverse run, free stop, reset, warning protection.

9.3.2 Basic wiring diagram



L1 U
EDS800 V
power supply L2 M
W
L3
E
forward run FWD
TA failure waring light
reverse run REV L1
TB
COM
multi-step speed control 1 X1 TC
L2
multi-step speed control 2 X2 PLC run indicator light
multi-step speed control 3 X3 OC
free stop X4 24V/220VAC
OCG
reset X5

Fig.9-3
9.3.3 Realized function
(1) make use of external on-off quantum signal to control start/stop of the motor.
(2) make use of external on-off quantum signal to make the motor run at set
frequency.
(3) bear free stop and reset function by utilizing external on-off quantum
signal.
(4) bear warning alarm and PLC run indication function.
9.3.4 Application field:
Applied in field where need frequent multi-speed adjustment to motor speed
such as toughened glass, weaving, paper making, chemical etc..

111
EDS800 series Service Manual

9.4 Closed-loop control system


9.4.1 Parameter setting
(1) set parameter F8.01F8.06 according to rated value of the inverter.
(2) F3.00=1: setting channel selectionhere PID closed loop run control is
effective.
(3) F3.01=1: setting channel selectionhere choose VCI as provision channel of
PID adjustor.
(4) F3.02=1: feedback channel selectionhere choose CCI as feedback channel,
4-20mA/0-10V feedback signal.
(5) F3.08-F3.10, set according to spot requirement.
9.4.2 Basic wiring diagram

3 phase breaker motor


L1 U
power supply EDS800 V M
L2
W
L3 E

forward run FWD TA failure waring light


L1
reverse run REV TB
COM TC
L2
+10V
AO
provision signal 10K VCI
ammeter
GND GND
0-10V feedback signal CCI

Fig.9-4
9.4.3 Realized function
(1) The inverter can adjust output automatically according to feedback signal to
make constant voltage, constant temperature, constant current etc. available.
(2) can control start/stop of the motor from long distance.
(3) bear failure alarm and current indicator function.
9.4.4 Application field
Applied in field where need stable system, pressure, flux such as blower
pump, constant pressure water supply, air compressor, air conditioner, freezer
cooling tower, music fountain, heat supply etc..

112
EDS800 series Service Manual

9.5 Consecutive action running


9.5.1 Basic wiring diagram

power QF QF
L1 1# U L1 U
supply M
L2 W
V L2 2# V M
L3 EDS800 E L3 EDS800 W
E
FWD run TA failure waring light failure waring light
FWD L1 TA
TB L1
command COM TC TB
L2 TC
10V L2
10K VCI 485+ 485+
GND
485- 485-

Fig.9-5
9.5.2 Parameter setting
set 1# inverter as follows:
(1) F0.02=1: terminal run command control.
(2) F5.23=0: DO terminal output pulse signal for 1# inverter output frequency.
(3) F5.10=0: 1# inverter running signal is outputted by digital output terminal OC.
set 2# inverter as follows:
(5) F0.00=7: terminal pulse setting is frequency provision for 2# inverter.
(6) F0.02=1: terminal run command control.
(7) F5.04=38X5 is for pulse frequency input.
After above setting, can use digital/pulse output quantum of 1# inverter to realize consecutive
action of 2# inverter.
9.5.3 Operation description
After receive forward run command from external switch(closed) and
frequency specified value( 0~10V)from analog input terminal VCI, 1# inverter run
at this frequency value. At the same time, already running state of 1# invertermake
2# inverter get forward run command through open circuit collector output end OC
hererun frequency value from high-speed pulse output terminal of 1# inverter is
passed to 2# inverter through X5 terminal.
9.5.4 Application field
Applied in field such as conveyer belt, coiler, factory production line, food
chemistry, piece drawer etc.
113
EDS800 series Service Manual

10 Serial port 485 communication protocol


10.1 Summarization
We provide general RS485/RS232 communication interface in our
inverters(such as EDS2000 seriesEDS2800 seriesEDS1000 series etc.) for the user.
Through this communication interface upper device (such as PC, PLC controller etc.)
can perform centralized monitor to the inverter (such as to set inverter parameter,
control run of inverter, read work state of the inverter) and also long-distance control
keypad can be connected to realize various usage requirement of the user.
This communication protocol is interface criterion file designed for realizing
above-mentioned function, please read it earnestly and program according to it so
that realize long-distance and network control to the inverter.
10.2 Protocol content and description
10.2.1 Communication net buildup mode
mainframe is PC or mainframe is PLC or EDS800 mainframe

RS232

232-485
conversion module

RS485

EDS800 EDS800 EDS1000 EDS1000

Fig.10-1 net buildup graph

10.2.2 Communication mode


At present, EDS800 inverter can be used only as auxiliary device in 485
net. Can realize communication between inverters through PC or PLC if its
needed. Specific communication mode is as mentioned below:
(1) PC or PLC as mainframeinverter as auxiliary devicepoint-to-point
communication between mainframe and auxiliary device.
(2) Auxiliary device dont response when mainframe send out command by
broadcast address.
114
EDS800 series Service Manual

(3) User can set local address, baud rate and data format of the inverter through
auxiliary device keypad or serial communication mode.
(4) Auxiliary device report current failure information to mainframe in the last
response frame.
(5) EDS800 provides 485 interface.
10.2.3 Transport mode
Asynchronous serialsemiduplex transport mode. Default format and
transport rate: 8-N-19600bps.For specific parameter setting please see
description for F2.14~F2.17 group function code.
10.2.4 Data command frame format
main device command frame format
sending
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
order
frame head

auxiliary device address


main device command

main device command


assistant index
assistant index
command index
command index
set data
set data
set data
set data
checkout sum
checkout sum
checkout sum
checkout sum

frame end
auxiliary device address

Defi-
command setting data
head

nition address Index area checkout area end


area area

sending
1 2 2 4 4 4 1
byte

115
EDS800 series Service Manual

auxiliary device response frame format


sending
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
order
frame head

auxiliary device address

failure index
failure index
command index
command index
run data
run data
run data
run data
checkout sum
checkout sum
checkout sum
checkout sum
frame end
auxiliary device address

auxiliary device reponse


auxiliary device reponse

Definiti- reponse
head

on address area Index area Run data area Checkout area end

sending
1 2 2 4 4 4 1
byte
Fig.10-2 command/response frame format
Remark:
(1) Setting data area and run data area may not be existent in some
command/data frame format, so in protocol command list its marked with
nothing.
(2) In protocol effective character set is: ~, 1, 2, 3, 4, 5, 6, 7, 8, 9, A, B, C, D, E, F
and hex data 0DHASCII lowercase a, b, c, d, e, f are invalid.
(3) Effective command frame length is 14 or 18 byte.
10.2.5 Explanation and description for format
(1) frame head
Its character~( namely hex 7E),single byte.
(2) auxiliary device address
Data meanings: local address of auxiliary device, double byte. ASCII format.
Inverter factory default is 01.
(3) mainframe command/auxiliary device respond
Data meanings: mainframe send out command and auxiliary device respond
to the command. Double byte, ASCII format.
Response code function classification:
Species 1>: command code=10 mainframe ask auxiliary device to report
current preparation state and control situation.

116
EDS800 series Service Manual

Table 10-1 response code meanings for command code 10


meanings
response
code Control from
preparation state of
ASCII mainframe is To set frequency is allowed
auxiliary device
allowed
10 Dont get ready no meaning
11 get ready allow allow
12 get ready allow allow
13 get ready dont allow dont allow
14 get ready dont allow dont allow
20 frame error
Species 2>: command code=11~15 , 5 kinds of function command
which mainframe send to auxiliary device, for detail please see protocol command
list.
Table 10-2 response code meanings for command code 11~15
response
code Meanings of response code description
ASCII
Auxiliary device communication and
control is normal function code
00
modification is effective
password is correct.
(1) frame checkout error When this response code is reported,
(2)command areadata data of command area, index area
overrun and running data area are not
20 (3)index areadata overrun reported.
(4) frame length error/non
ASCII byte exist in area except
frame head, frame end.
(1) control to auxiliary device is Whether report this response code
ineffective relate to current set state of auxiliary
(2)ineffective function code device. When report data of area,
30 parameter modification index area and
(3)setting/running dataarea run data areaare reported
data overrun. according to protocol
(4) password error. requirement.
(4) auxiliary index/command index/failure index
Data meanings: include auxiliary index byte and command index byte.

117
EDS800 series Service Manual

For mainframe, auxiliary index, command index are used for cooperating
mainframe command in realizing specific function.
For auxiliary device, auxiliary index, command index are used for reporting
failure state code, command index are reported without modification.
Data type: hex4 byte, ASCII format.
Command index occupy 2 low byte, data range: 00~FF.
Auxiliary index occupy 2 high byte, data range: 00~FF.
Auxiliary device failure state occupyauxiliary indexbytesee Appendix
table 10-3.
Table 10-3 failure type description
failure failure
description description
code code
Converting module
1 Accelerating run over current 13
protection
2 decelerating run over current 14 External device failure
constant speed run over current detecting circuit
3 15
current failure
RS485 communication
4 accelerating run over voltage 16
failure
5 decelerating run over voltage 17 reserved
constant speed run over
6 18 reserved
voltage
controller power supply over
7 19 Under voltage
voltage
8 Inverter overload 20 System disturbance

9 Motor overload 21 Reserved

10 Inverter over heat 22 Reserved


E2PROM read and write
11 reserved 23
error
12 reserved

(5) checkout sum


Data meanings: frame checkout4 byte, ASCII.
Calculation method: accumulative sum of ASCII code value of all byte fromauxiliary
device addresstorun data.
118
EDS800 series Service Manual

(6) frame end


Hex 0Dsingle byte.
10.2.7 Protocol command list
Frame 7E and frame end 0D, address, checkout sumASCII character format are
omitted in following description.
Table 10-4 protocol command table
mainframe sending
examplesuch as PC
main- auxi- run data control operation of
order run data Descripti-
Name frame liary setting inverter(C language
index precision on
order index range cluster format
auxiliary deviceaddress
is set to 01)
look up auxiliary
10 00 00 no ~010A00000192\r 1
motor state
current set no
11 00 00 ~010B00000193\r 0.01Hz
freq.
current run no
11 00 01 ~010B00010194\r 0.01Hz
freq.
Output voltage 11 00 02 no ~010B00020195\r 1V
Output current 11 00 03 no ~010B00030196\r 0.1A
Bus-bar voltage 11 00 04 no ~010B00040197\r 1V
Read parameter of auxiliary motor

Load motor no
11 00 05 ~010B00050198\r 1rpm
speed
Module temp. 11 00 06 no ~010B00060199\r 10C
Runtime 11 00 07 no ~010B0007019A\r 1h
accumulative no
11 00 08 ~010B0008019B\r 1h
time
Input terminal 11 00 09 no ~010B0009019C\r no
output terminal 11 00 0A no ~010B000A01A4\r no
analog input
11 00 0B no ~010B000B01A5\r 0.01V
VCI
analog input
11 00 0C no ~010B000C01A6\r 0.01V
CCI
reserved 11 00 0D no ~010B000D01A7\r 0.01V
exterior pulse
11 00 0E no ~010B000E01A8\r 0.01Hz
input
read inverter
11 00 0F no ~010B000F01A9\r no
state

119
EDS800 series Service Manual
auxiliary device
12 00 00 no ~010C00000194\r no
run command
set current 0Hz~ Set freq.
run frequency high =40.00Hz
12 00 01 ~010C00010FA0027C\r 0.01Hz
provision of limit
auxiliary device freq.
auxiliary device 0Hz~ auxiliary
run with run high device run
12 00 02 ~010C00020FA0027D\r 0.01Hz
freq. provision limit set freq.
freq. =40.00Hz
auxiliary device
forward run 12 00 03 no ~010C00030197\r no

auxiliary device
reverse run 12 00 04 no ~010C00040198\r no

auxiliary device forward


0Hz~
forward run run
high
with 12 00 05 ~010C00050FA00280\r 0.01Hz boot-strap
Run control and adjusting function

limit
run freq. set freq.
freq.
provision =40.00Hz
reverse
auxiliary device 0Hz~
run
reverse run with high
12 00 06 ~010C00060FA00281\r 0.01Hz boot-strap
run freq. limit
set freq.
provision freq.
=40.00Hz
auxiliary device
stop 12 00 07 no ~010C0007019B\r no

auxiliary device
jog run 12 00 08 no ~010C0008019C\r no

auxiliary device
forward jog run 12 00 09 no ~010C0009019D\r no

auxiliary device
reverse jog run 12 0A no ~010C000A01A5\r no

auxiliary device
stop jog run 12 00 0B no ~010C000B01A6\r no

auxiliary device
failure
12 00 0C no ~010C000C01A7\r no
restoration

auxiliary device
urgent stop 12 00 0D no ~010C000E01A8\r no

120
EDS800 series Service Manual

Run freq. digital


13 00 01 no ~010D00010196\r 0.01Hz
setting F0.01
Read function code

Run direction
13 00 03 no ~010D00030198\r 1
parameter

setting F0.03
accelerating
time1 13 00 0A no ~010D000E01AA\r 0.1S
F0.08
decelerating
time1 13 00 0B no ~010D000F01AB\r 0.1S
F0.09
Set
Set function code parameter

0Hz~
function
Run freq. digital high
14 00 01 ~010E00011388026B\r 0.01Hz code
setting F0.01 limit
F0.01=
freq.
50.00Hz
Set
function
Run direction
code
setting 14 00 03 0, 1 ~010E00030001025A\r 1
F0.03 to
F0.03
reverse
run
Set
function
accelerating
14 00 09 0~8CA0 ~010E000E03E8028B\r 0.1S code
time1 F0.08
F0.08 to
10.0s
Set
function
decelerating
14 00 0A 0~8CA0 ~010E000F03E8028C\r 0.1S code
time1 F0.09
F0.09 to
10.0s
query order
Software version

Query auxiliary
device software 15 00 00 no ~010F00000197\r 1
version

121
EDS800 series Service Manual

Table 10-5 response state word meanings of reading inverter state command

signification
bit
description 0 1
Bit0 Stop/run state stop run
Bit1 Logo for under voltage normal Under voltage
Bit2 FWD/REV run logo Forward run Reverse run
Bit3 traverse run mode logo ineffective effective
Bit4 Common run mode logo ineffective effective
Bit5 jog run mode logo no Jog
Bit6 PLC run mode logo no Yes
Bit7 multi-step freq. run mode logo no Yes
Bit8 PI closed loop run mode logo no Yes
Bit9 Set counting value arriving logo no Yes
Bit10 specified counting value arriving logo no Yes
Bit11~15 reserved

Table 10-6 read auxiliary device function code parameter

function Read auxiliary device function code parameter: all function code
definition parameter except user password and manufacturer password

frame order checkout


meanings address order run data frame end
head index sum

mainframe
7EH ADDR 13 see remark none BCC 0DH
order

byte quantity 1 2 2 4 0 4 1

auxiliary
Function
device 7EH ADDR 06 see remark BCC 0DH
code para.
respond

byte quantity 1 2 2 4 4 4 1

122
EDS800 series Service Manual
Command index=combinated by function code group number and hex
code of function code number. For instance:
If want to read parameter of F0.05 function code, order index=000B
If want to read parameter of F2.11 function code, order index =020B
If want to read parameter of F2.15 function code, order index =0212
If want to read parameter of F2.13 function code, order index =0210
Corresponding relation between decimal and hex value of function code group No.

function function
decimal hex decimal hex
remark group group

F0 0 00H F6 6 06H
F1 1 01H F7 7 07H
F2 2 02H F8 8 08H
F3 3 03H F9 9 09H
F4 4 04H FD 13 0DH
F5 5 05H FF 15 0FH
virtual data 0~FFFF (namely 0~65535)
Please input correct user password before you set user function code parameter.

Table 10-7 set auxiliary device function code parameter

function Set auxiliary device function code parameter: all function code parameter except
definition user password and manufacturer password
frame order checkout
meanings address order run data frame end
head index sum

mainframe see
7EH ADDR 14 No BCC 0DH
order remark

byte
1 2 2 4 0 4 1
quantity
auxiliary
see Function
device 7EH ADDR 06 BCC 0DH
remark code para.
respond
byte
1 2 2 4 4 4 1
quantity

123
EDS800 series Service Manual
Command index=combinated by function code group number and hex
code of function code number. For instance:
If want to set parameter of F0.05 function code, order index=000B
If want to set parameter of F2.11 function code, order index =020B
If want to set parameter of F2.15 function code, order index =0212
If want to set parameter of F2.13 function code, order index =0210
Corresponding relation between decimal and hex value of function
Code group No.

remark function function


decimal hex decimal hex
group group
F0 0 00H F6 6 06H
F1 1 01H F7 7 07H
F2 2 02H F8 8 08H
F3 3 03H F9 9 09H
F4 4 04H FD 13 0DH
F5 5 05H FF 15 0FH

Virtual data 0~FFFF (namely 0~65535)

124
EDS800 series Service Manual

Appendix 1 Modbus communication protocol


1.1 Summarization
We provide general RS485 communication interface in our inverters (such as
EDS800 series, EDS1000 series and etc.) for the user. Through this communication
interface upper device (such as HMI, PC, PLC controller and etc.) can perform
centralized monitor to the inverter (such as to set inverter parameter, control run of
inverter, read work state of the inverter).
This communication protocol is interface criterion file designed for realizing
above-mentioned function, please read it earnestly and program according to it so
that realize long-distance and network control to the inverter.
1.2 Communication net buildup mode
mainframe is PC or mainframe is PLC

RS232

232-485 conversion
module

RS485

EDS800 EDS800 EDS1000 EDS1000

Fig.1 net buildup graph


1.3 Communication mode
At present, EDS800 inverter can be used only as auxiliary device in RS485 net.
Can realize communication between inverters through PC, PLC or HMI if its
needed. Specific communication mode is as mentioned below:
(1) PC or PLC as mainframe inverter as auxiliary device, point-to-point
communication between mainframe and auxiliary device.
(2) Auxiliary device dont response when mainframe send out command by
broadcast address.
(3) User can set local address, baud rate and data format of the inverter through
auxiliary device keypad or serial communication mode.
(4) EDS800 provides optional RS485 interface.
(5) Default mode: Asynchronous serialsemiduplex transport mode. RTU mode.
Default format and transport rate: 8-N-1, 9600bps.
125
EDS800 series Service Manual

For specific parameter setting please see description for function code
F2.14~F2.17 as follows:
(remarkBelow definition for F2.14~F2.17 is only effective under Modbus
communication mode, and definition for other parameters are the same as
original)
F2.14 Communication LED first bitbaud rate selection 1 003
configuration 01200BPS
12400BPS
24800BPS
39600BPS
419200BPS
538400BPS
LED second bitdata format
01-8-1 formatno checkout
11-8-1 formateven checkout
21-8-1 formatodd checkout
LED third bitresponse selection
0 Respond to host command and
reply to data packet
1Respond to host command, but not
reply
F2.15 Local address 01270 is broadcast address 1 1
Communication 0.01000.0s,
F2.16 timeout 0 means communication timeout 0.1s 0.0s
detection time detection invalid
F2.17 Local response delay 0200ms 1ms 5ms

1.4 RTU Communication Mode


1.4.1 Data frame format
Using RTU mode, messages are sent at least 3.5 character time interval pause. The
first transmitted field is device address, the character you can transfer is hexadecimal
0x00 ~ 0xFF. Network equipment Continuously monitor the bus, including pauses.
When the address field is received, all equipment determine whether it is sent to
their own. when the last character of the packet transfer is complete, at least a 3.5
character times pause mean the end of the message. A new message can begin after
this pause.
The entire message frame must be transmitted as a continuous flow. If a new
message start transmitting in less than 3.5 character times after a message and then
receiving device will consider it a continuation of the previous message. This will
cause an error, because in the final CRC field value can not be right.
RTU frame format as the talbe below
Frame Header 3.5 characters time pause
Slave address Slave value1~127
03Hread slave parameter
Communication command code
06Hwrite slave parameter
Data content DATA The contents of packet:
Data content DATA Parameter address16bit;

126
EDS800 series Service Manual

Number of parameter or bytes of parameter


value;
Parameter value16bit
CRC check value low byte 16bit Unsigned check value
CRC check value high byte
Closing Flag 3.5 characters time pause
Regarding generation method of CRC check value, please refer to this Appendix
check way paragraph.
1.4.2 Host read slave parameter
Command code 03H. Host can read or one or more parameter( up to ten) by
initiating a communication transaction .
E.g., read 2 contiguous inverter parameter values from the address 0000H of
inverter whoes address is 01, the contents of host command
ADR 01H
CMD 03H
Parameters initial address high byte 00H
Parameters initial address low byte 00H
Number of parameter high byte 00H
Number of parameter low byte 02H
CRC check value low byte Be calculated
CRC check value high byte Be calculated
The contents of slave reply
ADR 01H
CMD 03H
Parameter value bytes 04H
Address 0000H content high byte 00H
Address 0000H content low byte 01H
Address 0001H content high byte 13H
Address 0001H content low byte 88H
CRC check value low byte Be calculated
CRC check value high byte Be calculated

1.4.3 Host write slave parameter


Command code 06H. Host can write an parameter by initiating a communication
transaction .
E.g.,The decimal system 5000 (1388H) written to the inverter 0001H address
whose slave address is 02host command including
ADR 02H
CMD 06H
Parameter address high byte 00H
Parameter address low byte 01H
Parameter value high byte 13H
Parameter value low byte 88H
CRC check value low byte Be calculated
127
EDS800 series Service Manual

CRC check value high byte Be calculated

The contents of slave reply


ADR 02H
CMD 06H
Parameter address high byte 00H
Parameter address low byte 01H
Address 0903H content high byte 13H
Address 0903H content low byte 88H
CRC check value low byte Be calculated
CRC check value high byte Be calculated

1.5 Data communication address allocation


1.5.1 Function code Fd-F0 group communication address
Inverter function parameters MODBUS communication address addressing
process follows PPnn way: PP means high byte of the address, corresponding to
function parameters group number; nn means low byte of the address,
corresponding to function code parameters group internal code. For example: F3.21
function codes communication address is 0315H, 03H is the hex form of group
number 3, 15H is the hex form of grop internal code 21.
F0.00~F9.11 communication address is 0000H~090BH, Fd group fault record
parameter start address is 0D00H.
1.5.2 control command and status word communication address
Variable Name Communication Reading-writing Command data or response value
address attribute meaning
run command 2000H 1: inching run
word 2: inching stop
3: forward inching run
4: reversal inching run
5: run
Writing only
6: stop
7: forward run
8: reversal run
9: fault reset
10: emergency stop
Serial port 2001H Reading and
Lower frequency ~ upper frequency
frequency provision writing
Inverter status 2100H 1: forwarder running
2: reversal running
Reading only
3: stop
4: alarm status
Alarm code 2180H 0: without alarm
Reading only
1~23:mean E001~E023 alarm

128
EDS800 series Service Manual

1.5.3 Monitor parameter communication address


Monitor
Name Communication address (Reading only)
parameter
C-00 Set frequency 1000H
C-01 Output frequency 1001H
C-02 Output current 1002H
C-03 Output voltage 1003H
C-04 DC bus-bar vlotage 1004H
C-05 Load motor speed 1005H
C-06 module temperature. 1006H
C-07 Power on running time 1007H
C-08 Accumulative running time 1008H
C-09 Input terminal status 1009H
C-10 Output terminal status 100AH
C-11 Analog input VCI value 100BH
C-12 Analog input CCI value 100CH
C-13 reserved
C-14 External impulse frequency 100EH

1.6 Communication error processing


Inverter receiving data packet detection error, it finds reading&writing parameter
address or parameter value invalid, so reply to the host with communication error
response packet. Communication error response packet (host command code +80H)
as command code, with 1 byte error code.
Format for communication error response packet as follows:
ADR 01H
CMD 83H/86H
communication error code 01H~06H (for details, please check below table)
Low byte of CRC checksum Obtain by calculating
High byte of CRC checksum Obtain by calculating

Meaning for each communication error code value as follows:


Communication error code value Type of communication error

0x01 CRC checksum error


0x02 Command code illegal
0x03 Register address visited illegal
0x04 Value to register illegal
0x05 Not allow to modify parameters
0x06 Register number read illegal

129
CRC CRC CRC CRC

9C

9C

36

44
08

08
09

09

Low bit Low bit Low bit Low bit


CRC CRC CRC CRC

DE

DE
42

42

B8
8E
02

02

high bit high bit high bit high bit


Low Low Low Low
05

05

06

06

88

88

01

00
High byte High byte High byte High byte
EDS800 series Service Manual

Data Data Data Data


00

00

00

00

13

13

00

00
High byte High byte High byte High byte
Register Register Register Register

1.7.3 Set 1# inverter given value to 50Hz


00

00

bytecount ) 20
address

(Respond value
00

00

01

01

00
address address address

130
Low byte

1.7.4 Read 1# inverter running state


Low byte Low byte Low byte
Register Register Register Register
20

20
address

20

20

20

20

21
1.7.1 start 1# inverter running

address address

1.7.2 Stop 1# inverter running


address
High byte
High byte High byte High byte
1.7 Data frames examples

Order 06

06
Order Order

06

06

06

06

03

03
code Order code
code code
Auxiliary Auxiliary Auxiliary Auxiliary

01

01
Inverter

01

01

01

01

01

01
Inverter Inverter Inverter
Address Address Address Address

command

Auxiliary

command

command
Auxiliary

Auxiliary

command

Auxiliary
respond

respond

respond

respond
frames

frames

frames

frames

frames

frames

frames

frames
Data

host

host

host

host
Data Field Data Field Data Field
Field
EDS800 series Service Manual

1.8 CRC checksum mode


CRC checksum value calculating function written by C language is as follows:
unsigned int cal_crc_value (unsigned char *pval, unsigned char len)
{
unsigned int crc_value=0xFFFF;
unsigned int i;

while(len--)
{
crc_value ^= *pval++;
for(i=0; i<8; i++)
{
if(crc_value & 0x0001)
{
crc_value >>= 1;
crc_value ^= 0xA001;
}
else
{
crc_value >>= 1;
}
}
}
return(crc_value);
}

131
EDS800 series Service Manual

Appendix 2 Braking resistance


1.1 Braking resistance
The motors electric potential energy will charge inverters capacitance up
reversely if speed of the motor decends too quickly or load of the motor wobbles too
quickly while the inverter is running, which will increase the voltage upon power
modules suddenly and is easy to make the inverter damaged. The inverter will
control it according to load size and performance. You have to connect external
resistance to realize timely energy discharge when the braking is not enough. To
connect external resistance is a kind of energy consumption braking mode, as all the
energy is consumed by the braking resistance.
EDS800-2S0002~EDS800-2S0015 have built-in braking unit,you can add
external braking resistance ,but the external resistance need booking.
External braking resistance configuration table
Power of braking
Type Braking resistance Qty. Remark
resistance
External braking
EDS800-2S0002 500 1 60W
resistance

External braking
EDS800-2S0007 500 1 60W
resistance

External braking
EDS800-2S0015 500 1 60W
resistance

External braking
EDS800-4T0007 500 1 60W
resistance

External braking
EDS800-4T0015 500 1 60W
resistance

132
Shenzhen Encom Electric Technologies CO., LTD.
Address: Floor5-6, building4, Pingshan Minqi Science Park,
Taoyuan Str., Nanshan Area, Shenzhen, China 518055
Web: www.enc.net.cn/en
E-mail: encvfd@enc.net.cn
encvfd@encvfd.com
Tel : 86-755-26984485
Fax: 86-755-26985120

You might also like