Seismic IIT Arresters
Seismic IIT Arresters
Seismic IIT Arresters
Abstract - The performance of substation equipment during an performance features, performance objectives of substations
earthquake depends on their configuration, strength of structures are oriented toward protection of equipment rather
construction, ductility and dynamic properties. Substation than protection of structures. According to these objectives,
equipments are lightly damped structures having one or more the structures supporting equipment may be scarified to
natural modes within the frequency band of ground excitation.
prevent the equipment to be damaged, under seismic effects.
The satisfactory operation of substation during and after an
earthquake depends on the survival, without malfunction, of About the assessment of equipment seismic vulnerability,
many diverse type of equipment. Porcelain components are the injury studies and similar structures during past
identified as most vulnerable parts against earthquake vibrations earthquakes will always be checked, as a starting point
than any other components of the substation. Electrical perfectly reasonable and logical is desired. Equipment such as
equipment is mounted on support structure. Support structure current transformer, power transformer, and the circuit
and porcelain insulator amplify the ground acceleration at the breaker, is fixed components and critical component of every
base of porcelain components. Dynamic characteristics of single process. The failure rate of theses equipment have a
substation equipment are considered by carrying out finite direct connection with operating voltage, and Failure patterns
element analysis. In the present work, maximum response
each of them is nearly equal. The effect of the earthquake
spectral accelerations & displacements of supporting structures,
equipment and for both equipment placed on support structures occurred because of high vulnerability of substation
are evaluated with respect to the zone factors. Furthermore, equipment such as use of brittle materials in the core and
dynamic amplification factor (DAF) of substation support critical part of equipment (including ceramic materials)
structures and along with its electrical equipment are obtained inadequate lateral strength and stiffness. Low levels of
and effect of different parameters (e.g. support mass, height and equipment damping, interactions between adjacent equipment,
stiffness) are discussed along with the recommendations available interactions with the internal components of equipment,
in International standards. excessive equipment load, Inadequate and irregular
distribution of load on height, inappropriate installation and
Index terms - Circuit Breaker, Porcelain Components, Seismic
maintenance [1][2].
Qualification, Substation Equipment.
Experiences from past earthquake records showed that large
magnitude earthquakes could cause severe damage to
I. INTRODUCTION substations and result in major service disruption of a power
The electric power industry cascades at three levels, in the system. High-voltage substation components that have been
chain between power supply and power generation. designed without full consideration of the site seismicity
Considerable damage to the power systems is occurred due to and/or designed before the introduction of modern seismic
occurrence of even an elementary fault in substation design codes are the most vulnerable. The commonly observed
equipment may disrupt power supply. Besides collateral failure modes could be listed as failures in transformer oil
losses, direct losses could be humongous besides loss of leakage from bushings and Circuit breaker etc. Given diverse
precious human life. The experience of past earthquakes classes of assets exposed to seismic hazard, consistency in the
shows that damages of the Electrical network installation are process of risk assessment and management becomes a
very extensive in length and area but they are infrequent. challenging task. A key component of a substation is the
Power transmission and sub transmission substations must circuit breaker which is one of the single largest capital
considered as the most vulnerable and also the most risky investments (60% of the total investment). Hence, replacing a
nodes of power network experienced at the time of damaged circuit breaker with a new one or keeping a spare
earthquakes . The higher number of consumers of substation, circuit breaker in a substation is expensive.
higher the voltage of substation, then the higher the This research uses seismic vulnerability and risk in an
consequents and risk of malfunction of substation hence alternative way as the definition of the vulnerability follows
seismic vulnerability of equipment increases with substations the same logic as that of risk. Risk is related to future events
voltage due to the fact that higher voltage in substation leads (i.e., a seismic event) and their consequences (i.e., failure of
to higher isolation distances and then higher height of substation components), and vulnerability is related to the
substations equipment. Higher performances must be expected combination of consequences (i.e., failure of substation
from higher voltage substation structures. Unlikely to components) and associated uncertainty (i.e., uncertainty of
performance objectives of general structures that are the consequences). Risk assessments are crucial as they reduce
concentrated essentially on the structures and nonstructural the risks of unwanted events, which could be very costly both
International Engineering Research Journal Page No 459-466
physically and financially. It is essential for Governments and Fig.1 Seismic Qualification Process
decision makers to evaluate the seismic risk of substations. It Follow the right branch of the flow chart to find the first
directly contributes to the improvement of safety and security step in the process which is to select the seismic
in a power system against seismic hazard of varying qualification level of low, moderate or high. The 2007
magnitudes. version of the standard has qualification levels in Clause 8.
You will likely already know which seismic qualification
II. BACKGROUND level applies to region. Generally, the high level is required
A. Seismic Qualification Process out west and the moderate level applies to active seismic
The IEEE 693 standard, Recommended Practice for zones in the eastern and central states.
Seismic Design of Substations, would be more descriptive as Move down to the next box to find the Annex for your
the Seismic Qualification of High Voltage Power specific equipment type. The qualifications procedure for
Equipment which is the primary content and purpose of the your equipment is given according to the voltage rating.
document. The document focuses on the high voltage power
equipment such as the breakers, transformers, disconnect B. Seismic Qualification Levels
switches, instrument transformers, reactors, circuit switchers Earthquakes events are generally defined by intensity and
and arresters. magnitude. Intensity, such as the Modified Mercalli scale is
The large high voltage equipment has been the most used to give a subjective description of the earthquakes
problematic in seismic events and is the most difficult to affect. The Magnitude scale gives a quantitative measure of
replace when damaged. The standard is not so much a guide seismic events based on the amplitude of motion recorded by a
on how to design the equipment to resist the earthquake but seismograph. For design and test purposes we need a more
instead defines the qualification process for seismic test or specific definition of the seismic event which can be related to
analysis to insure they survive a seismic event and maintain the dynamic acceleration that the ground applies to our
function. The standard depends more on shake table tests than equipment.
analysis to most reliably insure that a piece of equipment will The highest intensity and magnitude seismic events have
have acceptable seismic withstand capability [1]. peak ground accelerations over 0.5g and some may reach 1g.
The direct way to get started with applying IEEE 693 is to These accelerations can be applied horizontally as well as
go first to figure 1 in the standard, Using this vertically to the equipment and may cause even higher
recommended practice, for a flow chart or quick overview dynamic response accelerations in the equipment. The
of the document. problem arises because high voltage equipment may have
resonant or natural frequencies close to the frequency of the
seismic waves traveling through the ground during an
earthquake. Repeated cycles of the resonant frequency can
cause the equipment accelerations to build up to 2 or 3 g.
effectively this means that up to three times the weight maybe
applied horizontally to center of mass of the equipment or to
parts of the equipment. For tall, heavy high voltage
equipment, this may cause failure of the foundations,
supporting structures or high voltage insulators. A careful
study of stresses along the load path from the foundation to the
top of the equipment is needed to insure the equipment can
resist high seismic accelerations.
The most important tool that we have for seismic design and
qualification is the response spectrum. The response spectrum
is a graph of the response acceleration of single degree of
freedom oscillators, all with the same damping, to the same
ground acceleration. For the high seismic qualification level,
which has a peak input ground acceleration of 0.5g, the
required response spectrum (RRS) for is given in Fig 2 [3].
International Engineering Research Journal Page No 459-466
Model of equipment is designed in Unigraphics (NX-10) same boundary conditions to calculate natural frequency
based on all data which is required for FEM analysis. (resonance).
Functioning behavior of porcelain components used in circuit It is to be noted that sufficient modes should be included to
breaker with a supporting structure under damped condition ensure an adequate representation of the equipments
identified. Results will be obtained using finite element dynamic response. The acceptance criteria for establishing
analysis. Seismic qualification of the 33kV Circuit breaker by sufficiency in a particular direction should be that the
analysis will be carried out using Finite element analysis cumulative participating mass of the modes considered
software ANSYS 12.1. should be at least 90% of the sum of effective masses of all
modes (Ref: IEEE Std 693-2005). In this case, 10 modes
1) Structural modifications have been extracted in the frequency range of 0 Hz to 35 Hz.
The design of support structure is modified where The calculated mass participation in both horizontal
thickness and cross section of the main legs are changed directions (x&y) is nearly 95%.
from 65 x 65 x 6 to 75 x 75 x 8. In 3rd stage, the model is analyzed using response spectrum
The row of horizontal bracings is increased from 1 to 2. analysis where results from modal analysis have been used.
Additional support angles are added between the main legs The model is simulated under following inputs:
and the horizontal bracings. Constant damping ratio (Global damping) of 0.02 (2%) is
used for all modes.
The base excitations are given in the form of response
spectrum. RS accelerations are defined using required
response spectrum (RRS) for 2% damping and for zero
period acceleration (ZPA) value of 0.5g as per IEEE Std
693-2005. In this case, the available RRS of 0.25g is
extrapolated in order to get RRS at 0.5g. For each
horizontal direction, the RS acceleration is defined using
RRS with scale factor as 1.0 while for vertical direction,
the RS acceleration is defined using same RRS with scale
factor as 0.8.
For each component, a static force equals to the mass of the
component times the
percentage of mass missing
times the ZPA is applied.
The missing mass ZPA is
defined as 3 m/s2.
The total response in each
direction is determined by
applying the complete
quadratic combination
(CQC) technique to all
modal response
Fig.4Isomatric View of FEM Based GCB
components acting in that
The 'L' profile between the support structure and the direction.
housing is changed to 'C' profile keeping cross section and
thickness same. The support plate (gussets) inside this 3) Result and observations
profile are increased from 2 to 4. The additional 2 plates The maximum deformation
are placed such that the outer face of these plates align at top is reduced nearly by 40% due to modification in the
with the outer wall of the housing. The thickness is 12 mm support structure. This shows that this change is worked
which is same as the existing plates. positively.Due to reduction in the deformation the normal
The 2 angle ribs are added at both sides from inside of the stresses in the interrupter and in the support porcelains reduce
housing. They are aligned with the back face of the 'C' profile further which gives more safety margin.The stress levels on
and their thickness is kept as 6 mm. the support structure are significantly reduced and there are
hardly any locations where the stresses are beyond yield limit
2) Loading & boundary conditions of the material. The maximum equivalent stress is reduced
A static structural stress analysis is done in 1 st stage under from 730 MPa to 417 MPa.
the effect of standard earth gravity. In this case, base of the
support structure is fixed in all directions for translations and
rotations. The results of this analysis are linked to modal
analysis. Pre-stressed modal analysis is done in 2nd stage under
International Engineering Research Journal Page No 459-466
Fig.7 Housing
Considering all above results, it can be seen that there are
Fig.5 Support Structure
Similarly the stress concentration on top of the base frame no concerning or critical areas remain on the equipment. The
becomes less and also the magnitude of the maximum equipment and the support structure are looking completely
equivalent stress on the base frame came down nearly by safe under given seismic loading.
50%. There are very few stresses which are beyond yield
limit of the material. But considering their magnitude and the
area of concentration, they do not look concerning at all.The V. TYPE TESTING OF PRODUCT
major difference is seen on the support structure and at the Type testing is carried out in IIT Chennai for qualification
base of the housing which had shown high stress level of 0.5g. subjecting the specimen to a simulated seismic
excitation independently along the three orthogonal axis, of
magnitude 0.5g along two horizontal and one vertical
directions with a view to verify the mechanical capability of
the body frame, insulators etc. to withstand seismic forces.
The frequency range is frame 1.67-33.33 Hz (100-2000rpm)
in steps of 1.67 Hz (100 rpm) and at each frequency.
Excitation is maintained for 30 sec. strains are also to be
measured [4] [5].
A. Test setup
The specimen was mounted vertically on a rigid frame
made of steel channel fabrication and the entire frame with
the specimen was constrained to vibrate either in a vertical
plane or in a horizontal plane according to the requirements
by means of a reaction type of exciter. A double mass
unbalance exciter rigidly mounted on the framework
provided the excitation to the base of specimen. In the case of
vertical vibration, the frame was made to rest on elastic
supports namely helical springs while for the horizontal
vibration test the frame was made to rest on rollers instead.
Three acceleration pickups (seismic accelerometers) were
mounted in the direction of excitation, one at the base of the
support structure, one in middle (near the base of the
concentration areas.The overall stress levels are within yield insulator) and the other at the top of the specimen to sense
limit or are superficial and local. the corresponding acceleration levels (Fig. 8). This was done
for the longitudinal vibration mode and the transverse
Fig.6 Base Frame Profile
(bending) vibration modes of the specimen. Strain
The high stress concentration near base of the housing is measurements were carried out during horizontal modes of
also reduced and the stress results near connection between excitation by pasting strain gauges at the porcelain base.
the base profile and the housing are substantially improved.
This has mainly happened due to modification in the base
profile and the additional reinforcements provided at this
location. The stresses on the housing and on the profile are
within yield limit of the material.
International Engineering Research Journal Page No 459-466
B. Test Procedure
The frequency of vibration of the specimen was varied
from 1.67 to 33.33 Hz (100-2000 rpm) and the accelerometer
output was monitored and recorded for the three directions. A
block diagram (Fig.8) indicates schematically the
instrumentation setup. The excitation corresponding to 0.5g
pk for the horizontal direction as well as vertical direction
was maintained for 30 seconds after which the specimen was
checked for any visible damage. The curves of magnification
factor vs. frequency of excitation were plotted (Fig 9-11).
Base acceleration is plotted for all cases. Fig.11 Horizontal H2 Direction Response
REFERENCES
[1]IEEE Recommended Practices for Seismic Design of
Substations, IEEE Standard 693-2005.
[2]Hassani M., Safi M. and Hassani N., Evaluation of
Seismic Behavior of Circuit Breaker Based on Probabilistic
Approach, March 2014.
International Engineering Research Journal Page No 459-466