Reclosers: Form 6 Microprocessor-Based Recloser Control Programming Guide
Reclosers: Form 6 Microprocessor-Based Recloser Control Programming Guide
Figure 1.
Form 6 recloser control.
Table of Contents
Section 1: Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
What's In This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Upgrading Form 6 Control Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Upgrading from ProView4.0.1, 4.0, or 3.2.2 Software Version to ProView5.0 Software Version. . . . . . . . . . . . . 1-9
Password Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
ProView Registration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Three Levels of Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Front Panel Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Connecting ProView to the Control Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Front Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
Status Indication and Control Programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
LCD Menu Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14
Recloser Operation and Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
Section 2: Front Panel Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Settings Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Modify Protection Profile Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Curve Selection for TCC1 and TCC2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Operation Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Reclose Intervals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Reset Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Cold Load Pickup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Loadshed Restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Sensitive Earth Fault (SEF). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-32
Ungrounded Sensitive Earth Fault (SEF). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-35
Metering Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-39
Instantaneous Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-39
Demand Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-40
Power Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-43
!
SAFETY
!
SAFETY
FOR LIFE
SAFETY FOR LIFE FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively pro-
mote safe practices in the use and maintenance of our products through our service literature, instructional training programs,
and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and
service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around
high voltage lines and equipment and support our Safety For Life mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a Safety Instructions
substitute for proper training or adequate experience in
the safe operation of the equipment described. Only com- Following are general caution and warning statements that
petent technicians who are familiar with this equipment apply to this equipment. Additional statements, related to
should install, operate, and service it. specific tasks and procedures, are located throughout the
manual.
A competent technician has these qualifications:
Is thoroughly familiar with these instructions.
Is trained in industry-accepted high- and low-voltage
DANGER:
Hazardous voltage. Contact with hazardous voltage will
safe operating practices and procedures. cause death or severe personal injury. Follow all locally
Is trained and authorized to energize, de-energize, approved safety procedures when working around high-
clear, and ground power distribution equipment. and low-voltage lines and equipment. G103.3
1-2
!
S280-70-21
SAFETY
FOR LIFE
1-3
Form 6 Microprocessor-Based Recloser Control Programming Guide
1-4
!
S280-70-21
SAFETY
FOR LIFE
1-5
Form 6 Microprocessor-Based Recloser Control Programming Guide
1-6
!
S280-70-21
SAFETY
FOR LIFE
Section 1: Introduction
Thank you for purchasing the Form 6 Microprocessor-based
IMPORTANT: Do not open a ProView 4.0 or Recloser Control. Offered in a rack mount, yard mount, and
ProView 4.0.1 Form 6 control scheme with pole mount design, the Form 6 Recloser Control provides a
ProView 5.0 software. ProView 5.0 software will universal platform that can be programmed for many protec-
only operate correctly with ProView5.0 schemes. tive applications. The Form 6 control supports customization
If it is desired to use a ProView 4.0 or 4.0.1 of features to permit design and manufacture of customer-
scheme with ProView 5.0 software, convert the specific configuration and operating logic.
scheme with the ProView 5.0 F6-F6TS Upgrade The Form 6 recloser control provides phase and ground cur-
Wizard included on your ProView5.0 software CD.
rent sensing and three-phase voltage sensing. The Form 6
control can compute power, energy, power factor, and power
flow direction from the current and voltage sensing.
The Form 6 control can be programmed and interrogated
from the front panel. The front panel also displays metering
and alarm information.
In addition to front panel programming, control param-
eters can be programmed via personal computer using the
ProView interface software. Temporary connection to the
control is made through the operator front panel RS-232 port.
The back panel RS-232, as well as the optional fiber-optic,
ethernet, and RS-485 ports are available for SCADA or inter-
connections to other devices. The interface program includes
functions used to create, modify, and graphically display
time-current curves (TCCs) and provide diagnostic informa-
tion. The Form 6 control analysis tools include fault locating,
event recording, data profiler, recloser replay, application
one-line diagram, and oscillography functions. Customization
tools include TCC Editor II, a time-current curve modification
program, and the Idea Workbench, a complete software cus-
tomization program that enables you to design your distribu-
tion system to your specific application. Verification of settings
and customized logic are easily obtained with the Virtual Test
Set feature.
1-7
Form 6 Microprocessor-Based Recloser Control Programming Guide
1-8
!
S280-70-21
SAFETY
FOR LIFE
1-9
Form 6 Microprocessor-Based Recloser Control Programming Guide
12. Locate the DLL folder from within the folder list and open
it. The firmware file version appropriate for the control you
are connected to will appear.
13. Click on the firmware file that appears to select it. Click
the Open button.
14. Read the Caution statement. Click OK only if you have
read and understand the Caution statement.
15. After completing the ProView5.0 firmware download,
all of the Form6 control front panel LEDs will illuminate
and the firmware version will be displayed on the LCD.
Disconnect Form6 dataport-to-laptop communications.
16. Close the version of ProView software that was used to
perform the Firmware Upgrade.
17. Launch ProView5.0 application software.
18. Select File>Open Scheme from File... from the main
menu.
19. When the Open dialog appears, double-click on the
Form 6 folder.
C:\Program Files\Cooper\ProView50\Form6
20. Select the appropriate default Form 6 recloser control
scheme file from within the Form 6 folder:
F6-5.0 default (read only).f6s
F6TS-5.0 default (read only).f6s (for triple-single
controls)
21. Click the button.
22. Select the communication port used for serial communi-
cations on your PC. Click OK.
23. When the Enter password dialog is displayed, type
Modify (case-sensitive) and click OK.
24. After the ProView software compares the scheme on the
PC to the scheme in the connected Form 6 control, the
Connect using Com ? dialog will be displayed. Click the
Done button.
Note: Firmware and software versions must match.
25. Select Manage>Device>Download structure and settings
from the main menu.
26. After successfully completing the scheme download, you
will have a fully functional ProView5.0 Form6 control.
At this point, you can modify the settings or download a
custom scheme.
1-10
!
S280-70-21
SAFETY
FOR LIFE
Password Access
A password is required to access the appropriate user level
necessary to initiate any scheme setting and structure modi-
fications to the Form 6 recloser control. A password is also
required to connect to the Form 6 recloser control.
ProView Registration
ProView 4.0 (or greater) does not require a software authori-
zation key, but registration is still recommended.
Register online at www.cooperpowercentral.com/software/
proview/
1-11
Form 6 Microprocessor-Based Recloser Control Programming Guide
Front Panel
The Form 6 recloser control front panel offers extensive oper-
ation capabilities:
View instantaneous and demand metering quantities
CONTROL OK A PHASE FAULT ALARM A PHASE VOLTAGE INDICATOR 4
View and reset targets
CONTROL POWER
MENU
LAMP TEST CHANGE Note: The default settings are programmed to turn off the front
panel after ten minutes of inactivity. Except, if Hot Line Tag is
EXPANDED
MEMORY
ENTER ON, the Hot Line Tag LEDs will remain illuminated.
RS-232 DATA PORT
Note: Pressing the ENTER button while in any menu with a setting
KYLE F6 Recloser Control ON
GND TRIP NON SUPERVISORY
change option (even if a setting change had not actually been
TRIP CLOSE CLOSE
BLOCKED RECLOSING OFF
made) will disable the MMI Menu resetting functionality until a
settings change is confirmed via the front panel by selecting
CIRCUIT ALTERNATE ALTERNATE ALTERNATE
HOT LINE TAG PROFILE#1 PROFILE#2 PROFILE#3
DISABLE
OPTION#1 OPTION#2 OPTION#3 USE (F1), a setting change or scheme is downloaded from
(LOCKOUT) the PC to the control, or the Protection Profile is changed.
Selecting REVERT (F2) does not re-enable the MMIMenu
resetting functionality.
This section of the manual is designed to familiarize you with
the structure and operation of the front panel of the Form 6
control.
LAMP TEST
MENU
CHANGE
position.
Note: There are several conditions that will cause the alternate
ENTER blinking of the CONTROL LOCKOUT, RECLOSER OPEN, and
CONTROL OK
CONTROL POWER
A PHASE FAULT
B PHASE FAULT
ALARM
ABOVE MIN TRIP
A PHASE VOLTAGE
B PHASE VOLTAGE
RS-232 DATA PORT
X PHASE VOLTAGE
Y PHASE VOLTAGE
RECLOSER CLOSED LEDs: Failure to Trip, Failure to Close,
CONTROL LOCKOUT
RECLOSER OPEN KYLE
C PHASE FAULT
F6GROUND
Recloser
FAULT Control
TIE
ON
SECTIONALIZER
C PHASE VOLTAGE
FREQUENCY TRIP
Z PHASE VOLTAGE
INDICATOR 7
Interrupter Malfunction, and 52a/b Disagreement.
GND TRIP NON SUPERVISORY
RECLOSER CLOSED SENSITIVE GND LS DISABLED VOLTAGE TRIP INDICATOR 8
BLOCKED RECLOSING OFF
TRIP CLOSE CLOSE
ALTERNATE ALTERNATE ALTERNATE
The LED blinking pattern for these conditions is the
CIRCUIT
METERING
DISABLE
HOT LINE TAG PROFILE#1 PROFILE#2 PROFILE#3
SETTINGS
CONTROL LOCKOUT green LED and RECLOSER CLOSED
RESET
OPTION#1 OPTION#2 OPTION#3
OPER
red LED alternating with the RECLOSER OPEN green LED.
In addition to the above LED blinking pattern, the red ALARM
TARGETS COUNTER
(LOCKOUT)
F1 F2 F3 F4
LED will also be illuminated for these alarms: Failure to Trip,
+
EVENTS ALARMS
MENU
CHANGE
Failure to Close, and Interrupter Malfunction.
LAMP TEST
ENTER
RS-232 DATA PORT
1-13
Form 6 Microprocessor-Based Recloser Control Programming Guide
+
EVENTS ALARMS
MENU
>SETTINGS
METERING
SEQUENCE OF EVENTS
ALARM LOG & STATUS
COUNTERS
BATTERY
DNP PROTOCOL
WORKBENCH
CLOCK
FAULT LOCATOR
DIAGNOSTICS
I/O CONTROL
I/O STATUS
SELF-CLEAR FAULT: N
TEST MODES
NAMEPLATE DATA
ENTER
1-14
!
S280-70-21
SAFETY
FOR LIFE
MENU
LAMP TEST CHANGE
EVENTS: Displays the last 25 SOEevents.
EXPANDED
MEMORY
ENTER LAMP TEST: Illuminates all operator panel LEDs for
verification of proper operation. Enables the text mes-
sage display feature.
SETTINGS: Modify or View settings on the LCD display.
OPER COUNTER: Displays the total number of trip
operations, target operations, and resets all counters.
ALARMS: Provides status for all recloser alarms.
CHANGE: Must be pressed to enable the nine function
keys (OPTION pushbuttons).
Note: The CHANGE mode is a 10 second period in which one
function setting can be changed. If no change is made in
that time, the control front panel returns to the root menu.
ON
CLOSE Pushbutton: Returns the control to the initial or
KYLE F6 Recloser Control
home sequence position and closes the recloser. The
TRIP CLOSE CLOSE
control is ready for a new trip/reclose sequence.
CIRCUIT
DISABLE HOT LINE TAG Note: Pressing the CLOSE pushbutton from the Lockout
position initiates Cold Load Pickup (CLPU) protection,
if the feature is enabled.
(LOCKOUT) The user does have the ability to block COLD LOAD
PICKUP through the LCD menu or by configuring one
of the Option one-touch function keys via the Idea
Workbench feature in ProView.
If the recloser is closed, pushing and holding the
CLOSE pushbutton does not activate the Cold Load
Pickup feature.
CLOSE CIRCUIT DISABLE: Provides a visible discon-
nect in the closed circuit. Removing the 15 Amp fuse
disables all electrical closing of the recloser. Refer to
the appropriate Form 6 control installation manual for
additional information on Close Circuit Disable.
1-15
Form 6 Microprocessor-Based Recloser Control Programming Guide
HOT LINE TAG: Hot Line Tag is provided for live-line work
! WARNING: Hazardous voltage. Do not use Hot
Line Tag as a substitute for a visible disconnect.
applications. All closing operations are disabled when the
Hot Line Tag feature is activated.
Always establish a visible disconnect prior to performing
any work requiring a de-energized line. Failure to comply Hot Line Tag prevents all closing attempts and shifts pro-
may cause death, severe personal injury, or equipment tection to one trip-to-lockout on the composite curve of
damage. T276.0
the Hot Line Tag definite time and the TCC1 curve (which
ever is faster). Hot Line Tag takes precedence over Cold
IMPORTANT: Hot Line Tag activation does not cause the Load Pickup and Fast Trips Disabled.
recloser to trip open. It only prevents the recloser from Hot Line Tag can be enabled from multiple sources (front
closing. panel switch, SCADA, or Hardware Workbench); all must
be in a de-asserted (OFF) state to de-activate Hot Line
IMPORTANT: Hot Line Tag is intended solely for live-
Tag.
line work applications, such as maintenance, repairs or
improvements to the distribution system, that occur while Refer to the appropriate Form 6 control installation manual
the line remains energized. for additional information on Hot Line Tag.
ALTERNATE
NON-RECLOSING: Disables any automatic reclosing
ALTERNATE ALTERNATE
PROFILE#1 PROFILE#2 PROFILE#3 operations. Non-reclosing does not alter the active time-
current curve (TCC).
OPTION#1 OPTION#2 OPTION#3 SUPERVISORY OFF: Blocks the ability of the recloser to
respond to supervisory commands sent by serial com-
Form 6 Control Option pushbuttons munication ports or hardwired inputs. In the default Form
6 control scheme, when SUPERVISORY OFF is active,
Hot Line Tag can be remotely set; however, it cannot
The CHANGE button must be pressed prior to be remotely reset.
activating or de-activating these functions. OPTION 1 through OPTION 3: These option pushbut-
tons are customizable through the Idea Workbench. Refer
to the appropriate Form 6 control installation manual for
instructions on labeling customized options.
These option pushbuttons are only available on the stan-
Form 6-LS Control Option pushbuttons dard Form 6 Control:
ALTERNATE PROFILES 1, 2, 3: The Form 6 control has a
GND TRIP NON SUPERVISORY "Normal" profile and three Alternate profiles that change
BLOCKED RECLOSING OFF all protection parameters for the control. If Alternate profile
1, 2, or 3 is active, the corresponding option pushbutton
SOURCE I SOURCE II
LS RESET
ENABLED ENABLED LED illuminates. Normal profile is active, when all of the
Alternate profile option pushbutton LEDs are not illumi-
OPTION#1 OPTION#2 OPTION#3
nated. Only one profile is active at any time.
These option pushbuttons are only available on the Form
6-LS Control:
Note: Refer to Form 6 Loop Scheme Control in Section 5 for addi-
tional information.
IMPORTANT: The control includes a Power Save
LS RESET: Resets the LS function, so the control is ready
feature that will turn off the LEDs and backlit LCD
display after 10 minutes of inactivity at the front to respond to the next loss of voltage occurrence.
panel (no buttons pressed). The CONTROLOK and SOURCE I ENABLED: The control is in LS mode and
HOTLINETAG LEDs are not affected by the power responding to voltage conditions on Source I (Source side
save mode. Pressing any key on the front panel will - Phases A, B, and C).
turn the LCD backlight on and restore all LEDs to their SOURCE II ENABLED: The control is in LS mode and
current on/off states.
responding to voltage conditions on Source II
(Load side - Phases X, Y, and Z).
1-16
!
SAFETY
S280-70-21
FOR LIFE
E N T E R P A S S W ORD
Press the + or keys To access the SETTINGS Menu in VIEW ONLY mode:
to select the password
VALUE: 0
(if changed from the
default password 0).
1. Move the cursor (>) to SETTINGS or press the
VIEW ONLY CANCEL
SETTINGS shortcut key.
F1
(or Press F1
ENTER F4
(or Press F4
+ 2. Press ENTER.
to VIEW ONLY) to CANCEL)
3. The >MOD/VIEW SETTINGS screen appears. Press
>Actv Profi Norm
ENTER.
Edit Profi Norm
O v e r c u r r e n t Setting
O p e r S e q u e nce 4. The ENTERPASSWORD screen appears. Press F1 to
Reclose Intervals enter VIEW ONLYmode.
ResetTime 30.00
Cold Load Pickup
Freqency
5. Choose the applicable setting to View.
Voltage
Loadshed Restore 6. Press ENTER.
Sensitive Earth Flt
Ungrounded SEF
To access the SETTINGS Menu in MODIFY mode:
ENTER
1. Move the cursor (>) to SETTINGS or press the
SETTINGS shortcut key.
METERING
2. Press ENTER.
SETTINGS
RESET
TARGETS
OPER
COUNTER
3. The >MOD/VIEW SETTINGS screen appears. Press
F1 F2 F3 F4
ENTER.
SETTINGS Shortcut
+
EVENTS ALARMS
MENU
CHANGE
Key 4. Press ENTER.
LAMP TEST
2-1
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
(or Press F4 to CANCEL)
F4
The EDIT PROFI line item now displays the new profile group
>Actv Profi Norm
to be modified.
Edit Profi Alt1
Overcurrent Setting
Oper Sequence New profile group
to be modified.
Alternate Profiles
Normal profile is active, when none of the Alternate Profile
ALTERNATE ALTERNATE ALTERNATE
option pushbutton LEDs are illuminated.
To activate an Alternate Overcurrent Protection profile:
PROFILE #1 PROFILE #2 PROFILE #3
2-2
!
SAFETY
S280-70-21
FOR LIFE
ENTER
Each Minimum Trip LCD screen will show:
TCCPMinTrip see help the unit of measurement in primary Amperes
MIN: 5.00 MAX: 3200
VALUE: 100.000 Before changing the minimum to maximum input value range
CANCEL ^
minimum trip values,
Press < or > to move the selection
cursor to the position underneath refer to Changing the Minimum Trip setting value (can be changed from
the digit you want to change. Overcurrent Protection the front panel)
Press + or - to increase or decrease
the number above the selection cursor. Parameters in the Form Note: Phase, Ground, and Negative Sequence Tripping can be inde-
6 Control Schemes pendently disabled with the ProView interface software.
TCCPMinTrip see help
MIN: 5.00 MAX: 3200
Settings Operations
VALUE: 110.000 Parameters section of Caution: Equipment damage. Verify the maximum
CANCEL ^
this manual for setting
ENTER short time recloser limit for the recloser type prior to
F1 range information.
changing minimum trip values. Refer to Reference Data
(or Press F1 to CANCEL)
R280-91-34. Failure to do so can cause damage to the
>TCCPMinTrip 110.0 recloser under load conditions. T310.0
TCC1
TCC2
F1 F2 F4
IMPORTANT: Always verify the minimum trip values are
appropriate for the programmed CTRatio.
Note: The screen setup is the same for Phase, Ground, and
Negative Sequence.
2-3
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER PASSWORD Screens TCC1 and TCC2 (Phase, Ground, and Negative
VALUE: 0
Sequence) settings define the characteristics of the following
VIEW ONLY CANCEL time-current curves: Kyle TCCs 101 through 202, along with
F1 ENTER F4 a Constant (1 second definite time) TCC; ANSI Moderately
Inverse, Very Inverse, Extremely Inverse; IEC Inverse, Very
Actv Profi
Edit Profi
Norm
Norm Inverse, Extremely Inverse; and 5 custom curves identified as
>Overcurrent Setting
Oper Sequence USER1 through USER5.
ENTER Note: The user curves are definable using the TCC Editor II through
the interface software.
>Phase
Ground
Negative Sequence
Note: "P" applies to Phase, "G" applies to Ground, and "Q" applies
to Negative Sequence.
ENTER The diagram at the left shows the screen process of selecting
TCCPMinTrip 100.0 TCCPMinTrip 100.0 a phase curve for use as TCC1 or TCC2. This process is the
>TCC1 TCC1
TCC2 >TCC2 same for selecting ground and negative sequence curves for
TCC1 and TCC2.
ENTER ENTER
Inverse Time Characteristics
>TCC1PCurve 104 >TCC2PCurve 117
TCC1PMultE
TCC1PMult
Disable
1.000
TCC2PMultE
TCC2PMult
Disable
1.000
The ANSI and IEC Form 6 control curves are derived based
TCC1PAddEn Disable TCC2PAddEn Disable on the following equations:
ENTER ENTER
Trip Time:
( )
TCC1PCurve TCC2PCurve
PRESS [+] or [-] KEY PRESS [+] or [-] KEY A
117
CANCEL
101
CANCEL
Tt=TM x P
+B
M -1
ENTER F4 ENTER F4
(or Press F4 to CANCEL) (or Press F4 to CANCEL)
>TCC1PCurve 117 >TCC2PCurve 101 When Disk-like reset is selected for the ANSI curve shapes,
TCC1PMultE Disable TCC2PMultE Disable
TCC1PMult 1.000 TCC2PMult 1.000 the reset time is determined by the following formula:
TCC1PAddEn Disable TCC2PAddEn Disable
SELECT AN OPTION
FOR THE ALTERED
MENU
Tr=TM x ( )
RCC
2
M -1
SETTINGS:
USE REVERT BACK Where:
F1 F2 F4 M = Multiples of pickup
TM = Time multiplier setting
IMPORTANT: Pressing the ENTER button while
in any menu with a setting change option (even if
a setting change had not actually been made) will Curve Type A B P RCC
disable the MMI Menu resetting functionality until a ANSI MI 0.0515 0.114 0.02 4.85
settings change is confirmed via the front panel by
selecting USE (F1), a setting change or scheme is ANSI VI 19.61 0.491 2.0 21.6
downloaded from the PC to the Form 6 control, or ANSI EI 28.2 0.1217 2.0 29.1
the Protection Profile is changed. IEC INV 0.14 0 0.02 N/A
Selecting REVERT (F2) does not re-enable the IEC VI 13.5 0 1.0 N/A
MMIMenu resetting functionality.
IEC EI 80.0 0 2.0 N/A
2-4
!
SAFETY
S280-70-21
FOR LIFE
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
To Set Multiplier:
ENTER ENTER
TCC1PMult TCC2PMult
MIN: 0.10 MAX: 25.0 MIN: 0.10 MAX: 25.0
VALUE: 1.000 VALUE: 1.000
CANCEL ^ CANCEL ^
Press < or > to move the selection cursor to the position underneath
the digit you want to change.
TCC1PMult TCC2PMult
MIN: 0.10 MAX: 25.0 MIN: 0.10 MAX: 25.0
VALUE: 1.030 VALUE: 1.030
CANCEL ^ CANCEL ^
F1 ENTER F1 ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-5
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER ENTER
Similarly, if the same curve has a multiplier of 2 producing an
operate time of 5 seconds, the one second time adder pro-
TCC1PMultE
TCC1PMult
Disable
1.000
TCC2PMultE
TCC2PMult
Disable
1.000 duces a modified time of 6 seconds.
>TCC1PAddEn Disable >TCC2PAddEn Disable
TCC1PAdd 0.000 TCC2PAdd 0.000 5 seconds (2.5 seconds x 2) + 1 second = 6 seconds
ENTER ENTER Note: The Time Multiplier takes precedence over the Time Adder.
TCC1PAddEnable
PRESS [+] or [-] KEY
TCC2PAddEnable
PRESS [+] or [-] KEY
Note: These curve modifications can be predefined and viewed in
Enable Enable TCC Editor II and imported using the ProView Interface soft-
CANCEL CANCEL
ware included with the Form 6 control.
ENTER F4 ENTER F4
(or Press F4 to CANCEL) (or Press F4 to CANCEL) The diagram at the left shows the screen process of select-
TCC1PMultE Disable TCC2PMultE Disable ing an Adder for the phase curves selected as TCC1 and
TCC1PMult
>TCC1PAddEn
1.000
Enable
TCC2PMult
>TCC2PAddEn
1.000
Enable TCC2. This process is the same for selecting an Adder for the
TCC1PAdd 0.000 TCC2PAdd 0.000
ground and negative sequence curves selected as TCC1 and
MENU TCC2.
SELECT AN OPTION When you select the Adder parameter, the minimum and
FOR THE ALTERED
SETTINGS: maximum selection limits of the setting are displayed.
USE REVERT BACK
F1 F2 F4
To Set Adder:
ENTER ENTER
TCC1PAdd TCC2PAdd
MIN: 0.00 MAX: 30.0 MIN: 0.00 MAX: 30.0
VALUE: 0.000 VALUE: 0.000
CANCEL ^ CANCEL ^
Press < or > to move the selection cursor to the position underneath
the digit you want to change.
Press + or - to increase or decrease the number above the selection cursor.
TCC1PAdd TCC2PAdd
MIN: 0.00 MAX: 30.0 MIN: 0.00 MAX: 30.0
VALUE: 2.000 VALUE: 2.000
CANCEL ^ CANCEL ^
F1 ENTER F1 ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-6
!
SAFETY
S280-70-21
FOR LIFE
6 360
MENU 5 300
4 240
SELECT AN OPTION 3 180
FOR THE ALTERED
SETTINGS: 120
F1 F2 F4 1 60
TIME (sec)
.8 48
.6 36
To Set MRTA: .5 30
.4 24
20000
30000
40000
1000
2000
3000
4000
5000
6000
8000
100
200
300
400
500
600
800
50
60
80
TCC1PMRTA TCC2PMRTA
MIN: 0.01 MAX: 1.00 MIN: 0.01 MAX: 1.00 CURRENT (percent of minimum trip)
VALUE: 0.015 VALUE: 0.015
CANCEL ^ CANCEL ^
F1 ENTER F1 ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-7
Form 6 Microprocessor-Based Recloser Control Programming Guide
TCCPMinTrip 100.0 TCCPMinTrip 100.0 The diagrams on this page show the screen process of
>TCC1
TCC2
TCC1
>TCC2
selecting a HCT for the phase curves selected as TCC1 and
TCC2. This process is the same for selecting a HCT for the
ENTER ENTER ground and negative sequence curves selected as TCC1 and
TCC1PMRTA 0.013 TCC2PMRTA 0.013
TCC2.
>TCC1PHCTEn Disable >TCC2PHCTEn Disable
TCC1PHCT Mul 32.00 TCC2PHCT Mul 32.00 When you select the HCT parameters, the minimum and
TCC1PHCTDly 0.016 TCC2PHCTDly 0.016
maximum selection limits of the settings are displayed.
ENTER ENTER
Note: The High Current Trip (HCT) time delay takes precedence
TCC1PHCTEnable
PRESS [+] or [-] KEY
TCC2PHCTEnable
PRESS [+] or [-] KEY
over the Time Multiplier, Time Adder, and Minimum Response
Enable Enable Time Adder (MRTA).
CANCEL CANCEL
ENTER F4 ENTER F4
(or Press F4 to CANCEL) (or Press F4 to CANCEL)
F1 ENTER F1 ENTER
TCC1PHCT Mul TCC2PHCT Mul
MIN: 1.00 MAX: 32.0 MIN: 1.00 MAX: 32.0
VALUE: 32.000 VALUE: 32.000 (or Press F1 to CANCEL) (or Press F1 to CANCEL)
CANCEL ^ CANCEL ^
TCC1PMRTA 0.013 TCC2PMRTA 0.013
Press < or > to move the selection cursor to the position underneath
TCC1PHCTEn Disable TCC2PHCTEn Disable
the digit you want to change. TCC1PHCT Mul 32.00 TCC2PHCT Mul 32.00
Press + or - to increase or decrease the number above the selection cursor. >TCC1PHCTDly 0.019 >TCC2PHCTDly 0.019
F1 F2 F4
(or Press F1 to CANCEL) (or Press F1 to CANCEL)
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-8
!
SAFETY
S280-70-21
FOR LIFE
Operation Sequence
The Operation Sequence submenu lets you program:
the operations-to-lockout
the sequence of overcurrent trip operations for phase/
negative sequence, and ground
Operations-to-Lockout
Operations-to-Lockout defines the maximum number of trip
operations in a sequence before the recloser opens and the
>SETTINGS control locks out. The count includes phase, ground, and
METERING
SEQUENCE OF EVENTS negative sequence trips as well as sequence coordination
ALARM LOG & STATUS
operations.
ENTER
>Mod/View Settings
The diagram at the left shows the screen process of setting
the total number of operations-to-lockout.
ENTER
Note: Pressing (+) increases the number of operations; pressing ()
decreases the number.
ENTER PASSWORD
VALUE: 0
VIEW ONLY CANCEL
F1 ENTER F4
ENTER
Operations to LO
PRESS [+] or [-] KEY
3
CANCEL
ENTER F4
(or Press F4 to CANCEL)
>Operations 3
Phase/Neg Seq
Ground
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-9
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
Operations 4
>Phase/Neg Seq
Ground
ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-10
!
SAFETY
S280-70-21
FOR LIFE
ENTER
Operations 4
Phase/Neg Seq
>Ground
ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-11
Form 6 Microprocessor-Based Recloser Control Programming Guide
Reclose Intervals
Reclose interval settings define the time the recloser is open
following a trip operation, prior to reclosing.
The diagram shows the screen process of setting the Reclose
Intervals for Phase/Negative Sequence.
When you select the Phase/Negative Sequence Reclose
Interval parameter, the minimum and maximum selection lim-
its of the setting are displayed.
Phase/Negative Sequence
>SETTINGS
METERING
SEQUENCE OF EVENTS
ALARM LOG & STATUS
ENTER
>Mod/View Settings
ENTER
ENTER PASSWORD
VALUE: 0
VIEW ONLY CANCEL
F1 ENTER F4
ENTER
>Phase/Neg Seq
Ground
ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-12
!
SAFETY
S280-70-21
FOR LIFE
Ground
The Reclose Intervals for Ground operation are programmed
independent of the Phase/Negative Sequence Reclose
Settings.
The diagram shows the screen process of setting the Reclose
Intervals for Ground.
When you select the Ground Reclose Interval parameter, the
minimum and maximum selection limits of the setting are dis-
played.
>SETTINGS
METERING
SEQUENCE OF EVENTS
ALARM LOG & STATUS
ENTER
>Mod/View Settings
ENTER
ENTER PASSWORD
VALUE: 0
VIEW ONLY CANCEL
F1 ENTER F4
ENTER
Phase/Neg Seq
>Ground
ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-13
Form 6 Microprocessor-Based Recloser Control Programming Guide
Reset Time
Reset Time is the user-settable time delay that is used by
the Form 6 control after a successful reclose to reset the
> S E T T I NGS
M E T E R ING sequence position to zero (Home position). Reset after suc-
S E Q U E NCE OF EVENTS
A L A R M LOG & STATUS
cessful reclose occurs when the recloser is closed and no
ENTER
current above an overcurrent minimum trip setting is detect-
ed.
> M o d / V iew Settings
The diagram at the left shows the screen process of setting
the Reset Time.
ENTER
When you select the Reset Time parameter, the minimum and
E N T E R PASSWORD
maximum selection limits of the setting are displayed.
VALUE: 0
V I E W O NLY CANCEL
F1 ENTER F4
O v e r c urrent Setting
O p e r Sequence
R e c l o se Intervals
> R e s e t Time 30.00
ENTER
R e s e t T ime (sec)
M I N : 3 .00 MAX: 1800
VALUE: 30.000
CANCEL ^
Press < or > to move the selection
cursor to the position underneath
the digit you want to change.
Press + or - to increase or decrease
the number above the selection cursor.
R e s e t T ime (sec)
M I N : 3 .00 MAX: 1800
VALUE: 32.000
CANCEL ^
F1 ENTER
O v e r c urrent Setting
O p e r Sequence
R e c l o se Intervals
> R e s e t Time 32.00
MENU
S E L E C T AN OPTION
F O R T H E ALTERED
S E T T I N GS:
USE REVERT BACK
F1 F2 F4
2-14
!
SAFETY
S280-70-21
FOR LIFE
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
CLPUActivation Time
The above left diagram shows the screen process of setting
the CLPU Activation Time.
When you select the CLPU Activation Time parameter, the
minimum and maximum selection limits of the setting are dis-
played.
2-15
Form 6 Microprocessor-Based Recloser Control Programming Guide
>CLPUPMinTrip 201.0
CLPUPCurve 117
CLPUPMultE Disable
CLPUPMult 1.000
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-16
!
SAFETY
S280-70-21
FOR LIFE
CLPUBlock Yes
Note: "P" applies to Phase, "G" applies to Ground, and "Q" applies
>Phase to Negative Sequence.
Ground
Negative Sequence
The diagram at the left shows the screen process of selecting
ENTER a phase CLPU TCC. This process is the same for selecting
CLPUPMinTrip 200.0 ground and negative sequence curves for CLPU TCCs.
>CLPUPCurve 117
CLPUPMultE
CLPUPMult
Disable
1.000 Time-current curves selected for TCC1 and TCC2 can also
ENTER
be used as Cold Load Pickup curves.
CLPUPCurve
PRESS [+] or [-] KEY
118
CANCEL
ENTER F4
(or Press F4 to CANCEL)
CLPUPMinTrip 200.0
>CLPUPCurve 118
CLPUPMultE Disable
CLPUPMult 1.000
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-17
Form 6 Microprocessor-Based Recloser Control Programming Guide
CLPU Multiplier
The CLPU Multiplier settings define a Time Multiplier to
>SETTINGS
modify the position of the original TCC in time-current space
METERING and the ability to enable the multiplier. With the CLPU Time
SEQUENCE OF EVENTS
ALARM LOG & STATUS Multiplier enabled, the trip time of a given TCC at the mea-
ENTER sured current is shifted in time by the specific multiplier.
>Mod/View Settings For example, if a curve has an operation time of 40 millisec-
onds, and a multiplier of 2, the modified operation time
would be 80 milliseconds.
ENTER
ENTER PASSWORD 40 ms x 2 = 80 ms
VALUE: 0 Similarly, if the same curve has an operation time of 5 sec-
VIEW ONLY CANCEL
onds, the multiplier produces a modified time of 10 seconds.
F1 ENTER F4
5 seconds x 2 = 10 seconds
Oper Sequence
Reclose Intervals Note: These curve modifications can be predefined and viewed in
ResetTime 30.00
>Cold Load Pickup
TCC Editor II and imported using the ProView Interface soft-
ware included with the Form 6 control.
ENTER
The diagram at the left shows the screen process of select-
CLPUBlock Yes ing a Multiplier for the phase CLPU TCC. This process is the
>Phase
Ground same for selecting a Multiplier for the ground and negative
Negative Sequence
sequence CLPU TCC.
ENTER
To Enable Multiplier: To Set Multiplier: When you select the CLPU Multiplier parameter, the minimum
CLPUPMinTrip
CLPUPCurve
200.0
117
CLPUPMinTrip
CLPUPCurve
200.0
117
and maximum selection limits of the setting are displayed.
>CLPUPMultE Disable CLPUPMultE Disable
CLPUPMult 1.000 >CLPUPMult 1.000
ENTER ENTER
CLPUPMultEnable CLPUPMult
PRESS [+] or [-] KEY MIN: 0.10 MAX: 25.0
Enable VALUE: 1.000
CANCEL CANCEL ^
Press < or > to move the selection
ENTER F4 cursor to the position underneath
(or Press F4 to CANCEL) the digit you want to change.
Press + or - to increase or decrease
CLPUPMinTrip 200.0 the number above the selection cursor.
CLPUPCurve 117
>CLPUPMultE Enable
CLPUPMult 1.000 CLPUPMult
MIN: 0.10 MAX: 25.0
MENU VALUE: 2.000
CANCEL ^
SELECT AN OPTION F1 ENTER
FOR THE ALTERED
SETTINGS:
(or Press F1 to CANCEL)
USE REVERT BACK
CLPUPMinTrip 200.0
F1 F2 F4
CLPUPCurve 117
CLPUPMultE Disable
>CLPUPMult 2.000
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-18
!
SAFETY
S280-70-21
FOR LIFE
CLPU Adder
The CLPU Adder settings define a Time Adder to modify the
>SETTINGS position of the original TCC in time-current space and the
METERING
SEQUENCE OF EVENTS ability to enable the Adder. With the CLPU Adder enabled,
ALARM LOG & STATUS
the trip time of a given TCC at a measured current is shifted
ENTER in time by the specified additional time. In contrast to the
>Mod/View Settings CLPU Time Multiplier, the CLPU Adder adds a constant time
to the curve, regardless of the unmodified curve operating
time.
ENTER
ENTER PASSWORD
For example, if a curve has an operate time of 40 ms. and a
VALUE: 0
1 second time adder, the modified operate time is 1.040 sec-
VIEW ONLY CANCEL onds.
ENTER
F1 F4
0.040 seconds + 1 second = 1.040 seconds
Oper Sequence Similarly, if the same curve has a multiplier of 2 producing
Reclose Intervals
ResetTime 30.00 an operate time of 5 seconds, the one second time adder
>Cold Load Pickup
would produce a modified time of 6 seconds.
ENTER
5 seconds (2.5 seconds x 2) + 1 second = 6 seconds
CLPUBlock Yes Note: The CLPUTime Multiplier takes precedence over the CLPU
>Phase
Ground Time Adder.
Negative Sequence
Note: These curve modifications can be predefined and viewed in
ENTER
To Enable Adder: To Set Adder: TCC Editor II and imported using the ProView Interface soft-
CLPUPMultE Disable CLPUPMultE Disable ware included with the Form 6 control.
CLPUPMult 1.000 CLPUPMult 1.000
>CLPUPAddEn
CLPUPAdd
Disable
0.000
CLPUPAddEn
>CLPUPAdd
Disable
0.000
The diagram at the left shows the screen process of selecting
an Adder for the phase CLPU TCC. This process is the same
ENTER ENTER
for selecting an Adder for the ground and negative sequence
CLPUPAddEnable CLPUPAdd CLPU TCC.
PRESS [+] or [-] KEY MIN: 0.00 MAX: 30.0
Enable
CANCEL
VALUE:
CANCEL
0.000
^ When you select the CLPU Adder parameter, the minimum
Press < or > to move the selection and maximum selection limits of the setting are displayed.
ENTER F4 cursor to the position underneath
(or Press F4 to CANCEL) the digit you want to change.
Press + or - to increase or decrease
CLPUPMultE Disable the number above the selection cursor.
CLPUPMult 1.000
>CLPUPAddEn Enable
CLPUPAdd 0.000 CLPUPAdd
MIN: 0.00 MAX: 30.0
MENU VALUE: 1.000
CANCEL ^
SELECT AN OPTION F1 ENTER
FOR THE ALTERED
SETTINGS:
(or Press F1 to CANCEL)
USE REVERT BACK
CLPUPMultE Disable
F1 F2 F4
CLPUPMult 1.000
CLPUPAddEn Disable
>CLPUPAdd 1.000
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-19
Form 6 Microprocessor-Based Recloser Control Programming Guide
>Mod/View Settings
When enabled, the CLPU minimum response time of a given
TCC can be no less that the value of the CLPU MRTA.
Note: These curve modifications can be predefined and viewed in
ENTER TCC Editor II and imported using the ProView interface soft-
ENTER PASSWORD ware included with the Form 6 control.
VALUE:
VIEW ONLY
0
CANCEL
The diagram at the left shows the screen process of selecting
ENTER
a CLPU MRTA for the phase CLPU TCC. This process is the
F1 F4
same for selecting a CLPU MRTA for the ground and negative
Oper Sequence sequence CLPU TCC.
Reclose Intervals
ResetTime 30.00
>Cold Load Pickup
When you select the CLPU MTRA parameter, the minimum
and maximum selection limits of the setting are displayed.
ENTER
Note: The CLPU Minimum Response Time Adder (MRTA) takes
CLPUBlock Yes
>Phase precedence over both the CLPU Time Multiplier and CLPU
Ground
Negative Sequence
Time Adder.
ENTER
To Enable MRTA: To Set MRTA:
CLPUPAddEn Disable CLPUPAddEn Disable
CLPUPAdd 0.000 CLPUPAdd 0.000
>CLPUPMRTAE Disable CLPUPMRTAE Disable
CLPUPMRTA 0.013 >CLPUPMRTA 0.013
ENTER ENTER
CLPUPMRTAEnable CLPUPMRTA
PRESS [+] or [-] KEY MIN: 0.01 MAX: 1.00
Enable VALUE: 0.013
CANCEL CANCEL ^
Press < or > to move the selection
ENTER F4 cursor to the position underneath
(or Press F4 to CANCEL) the digit you want to change.
Press + or - to increase or decrease
CLPUPAddEn Disable the number above the selection cursor.
CLPUPAdd 0.000
>CLPUPMRTAE Enable
CLPUPMRTA 0.013 CLPUPMRTA
MIN: 0.01 MAX: 1.00
MENU VALUE: 0.015
CANCEL ^
SELECT AN OPTION F1 ENTER
FOR THE ALTERED
SETTINGS:
(or Press F1 to CANCEL)
USE REVERT BACK
CLPUPAddEn Disable
F1 F2 F4
CLPUPAdd 0.000
CLPUPMRTAE Disable
>CLPUPMRTA 0.015
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-20
!
SAFETY
S280-70-21
FOR LIFE
ENTER
Note: These curve modifications can be predefined and viewed in
TCC Editor II and imported using the ProView Interface soft-
>Mod/View Settings
ware included with the Form 6 control.
The diagram at the left shows the screen process of selecting
ENTER a CLPU HCT for the phase CLPU TCC. This process is the
ENTER PASSWORD same for selecting a CLPU HCT for the ground and negative
VALUE: 0 sequence CLPU TCC.
VIEW ONLY CANCEL
ENTER
When you select the CLPU HCT parameters, the minimum
F1 F4
and maximum selection limits of the settings are displayed.
Oper Sequence
Reclose Intervals
Note: The CLPU High Current Trip (HCT) time delay takes prece-
ResetTime 30.00 dence over the CLPU Time Multiplier, CLPU Time Adder, and
>Cold Load Pickup
CLPU Minimum Response Time Adder (MTRA).
ENTER
CLPUBlock Yes
>Phase
Ground
Negative Sequence
ENTER
To Enable To Set To Set
HCT: HCT Multiplier: HCT Time Delay:
CLPUPMRTA 0.013 CLPUPMRTA 0.013 CLPUPMRTA 0.013
>CLPUPHCTEn Disable CLPUPHCTEn Disable CLPUPHCTEn Disable
CLPUPHCT Mul 32.00 >CLPUPHCT Mul 32.00 CLPUPHCT Mul 32.00
CLPUPHCTDly 0.016 CLPUPHCTDly 0.016 >CLPUPHCTDly 0.016
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-21
Form 6 Microprocessor-Based Recloser Control Programming Guide
Frequency
The Frequency Protection feature provides both under and
>SETTINGS
METERING
overfrequency protection. Frequency protection includes two
SEQUENCE OF EVENTS stages to prioritize loadshedding feeders.
ALARM LOG & STATUS
ENTER
>Mod/View Settings
ENTER
ENTER PASSWORD
VALUE: 0
VIEW ONLY CANCEL
F1 ENTER F4
Reclose Intervals
ResetTime 30.00
Cold Load Pickup
>Frequency
ENTER
ENTER
>Underfrequency
Overfrequency
Freq:MinVolt 3.600
ENTER
>UFreqEnabl Off
UFreq1PU see 56.00
UFreq1Time 100.00
UFreq2PU see 56.00
ENTER
UFreqEnable
PRESS [+] or [-] KEY
On
CANCEL
ENTER F4
(or Press F4 to CANCEL)
>UFreqEnabl On
UFreq1PU see 56.00
UFreq1Time 100.00
UFreq2PU see 56.00
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-22
!
SAFETY
S280-70-21
FOR LIFE
Frequency Pickup
The Frequency Pickup settings define the frequency at which
Reclose Intervals
ResetTime 30.00 the frequency elements begin to operate.
Cold Load Pickup
>Frequency For Underfrequency, the function operates if the measured
ENTER frequency is less than the pickup frequency.
For Overfrequency, the function operates if the measured fre-
>Underfrequency
Overfrequency quency is greater than the pickup setting.
Freq:MinVolt 3.600
Note: The front panel (as well as the ProView Interface software)
ENTER allows you to program two under and two overfrequency pro-
tection elements. Additionally, the interface software allows
UFreqEnabl Off programming of a single underfrequency and a single overfre-
>UFreq1PU see 56.00
UFreq1Time 100.00 quency alarm.
UFreq2PU see 56.00
The diagram at the left shows the screen process to set the
ENTER
Frequency Pickup settings for Underfrequency Protection.
UFreq1PU seeHelp for The same process is followed for Overfrequency Protection.
MIN: 46.0 MAX: 64.0
VALUE:
CANCEL
56.000
^
When you select the Frequency Pickup parameter, the mini-
Press < or > to move the selection mum and maximum selection limits of the setting are dis-
cursor to the position underneath
the digit you want to change.
played.
Press + or - to increase or decrease
the number above the selection cursor.
IMPORTANT: Always verify the pickup values are appropri-
UFreq1PU seeHelp for ate for the system frequency.
MIN: 46.0 MAX: 64.0
VALUE: 57.000
CANCEL ^
F1 ENTER
UFreqEnabl Off
>UFreq1PU see 57.00
UFreq1Time 100.00
UFreq2PU see 56.00
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-23
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
UFreq1Time (sec)
MIN: 0.00 MAX: 100.
VALUE: 100.000
CANCEL ^
Press < or > to move the selection
cursor to the position underneath
the digit you want to change.
Press + or - to increase or decrease
the number above the selection cursor.
UFreq1Time (sec)
MIN: 0.00 MAX: 100.
VALUE: 99.000
CANCEL ^
F1 ENTER
UFreqEnabl Off
UFreq1PU see 56.00
>UFreq1Time 99.00
UFreq2PU see 56.00
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-24
!
SAFETY
S280-70-21
FOR LIFE
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-25
Form 6 Microprocessor-Based Recloser Control Programming Guide
Voltage
The Under and Overvoltage settings are used for loss of volt-
> S E T T INGS
M E T E RING
age detection and/or overvoltage protection applications.
S E Q U ENCE OF EVENTS
A L A R M LOG & STATUS Undervoltage protection includes both single-phase or three-
ENTER phase loss of sensing and single-phase trip with three-phase
> M o d / View Settings inhibit.
Single-phase undervoltage sensing responds when
one or more phases is below the pickup setting. The
ENTER
UVolt1PEnable setting must be ON to enable this fea-
E N T E R PASSWORD
ture.
VALUE: 0
V I E W ONLY CANCEL Three-phase sensing will only respond when all
F1 ENTER F4 three phases are below the pickup setting. The
UVolt3PEnable setting must be ON to enable this fea-
R e s e tTime 30.00
C o l d Load Pickup ture.
F r e q uency
> V o l t age
Single-phase sensing with three-phase inhibit will
ENTER
respond like single-phase sensing, except it will
>Undervoltage
Overvoltage
Undervoltage
>Overvoltage
not react to a three-phase condition. Both the
UVolt1PEnable and UVolt1P/3Pinhibit settings must be
ENTER ENTER
ON to enable this feature.
>U V o l t 1 P E n a O ff >OVoltEnabl Off Overvoltage sensing includes both single-phase and three-
UVolt1P/3P
UVolt3PEna
O ff
O ff
OVolt1PPU
OVolt1PTime
16.20
100.0 phase sensing.
UVolt1PPU 1 1 . 52 OVolt3PPU 16.20
UV o l t 1 P T i m e 1 0 0 .0 OVolt3PTime 100.0
UVolt3PPU 1 1 . 52
UVolt3PTime 1 0 0 .0
ENTER
>UVolt1PEna Off
UVolt1P/3P Off
UVolt3PEna Off
UVolt1PPU 11.52
ENTER
UVolt1PEnable
PRESS [+] or [-] KEY
On
CANCEL
ENTER F4
(or Press F4 to CANCEL)
>UVolt1PEna On
UVolt1P/3P Off
UVolt3PEna Off
UVolt1PPU 11.52
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-26
!
SAFETY
S280-70-21
FOR LIFE
Voltage Pickup
The Voltage Pickup settings define the primary voltage (kV) at
R e setTime 30.00 which the voltage elements begin to operate.
C o ld Load Pickup
F r equency
> V o ltage
For Undervoltage, the function operates if the measured pri-
mary voltage (kV) is less than the pickup voltage.
ENTER
For Overvoltage, the function operates if the measured pri-
> U n dervoltage
O v ervoltage
mary voltage (kV) is more than the pickup voltage.
Note: The front panel (as well as the software) allows you to pro-
gram single-phase and three-phase under and overvoltage
ENTER
pickup settings. Additionally, the interface software allows
U V olt1PEna Off
programming of a single undervoltage and overvoltage alarm.
U V olt1P/3P Off
U V olt3PEna Off The diagram at the left shows the screen process to set the
> U V olt1PPU 11.52
Pickup settings for the Undervoltage Protection. The same
ENTER
process is followed for the Overvoltage Protection.
U V o l t1PPU (kVpri)
M I N : 0.00 MAX: 200. When you select the Voltage Pickup parameter, the minimum
V A L U E:
C A N C EL
11.520
^ and maximum selection limits of the setting are displayed.
Press < or > to move the selection
cursor to the position underneath
the digit you want to change.
Press + or - to increase or decrease
the number above the selection cursor.
U V o l t1PPU (kVpri)
M I N : 0.00 MAX: 200.
V A L U E: 11.530
C A N C EL ^
F1 ENTER
U V o lt1PEna Off
U V o lt1P/3P Off
U V o lt3PEna Off
> U V o lt1PPU 11.53
MENU
S E L E CT AN OPTION
F O R THE ALTERED
S E T T INGS:
USE REVERT BACK
F1 F2 F4
2-27
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
U V o l t 1PTime (sec)
M I N : 0.00 MAX: 100.
VALUE: 100.000
CANCEL ^
Press < or > to move the selection
cursor to the position underneath
the digit you want to change.
Press + or - to increase or decrease
the number above the selection cursor.
U V o l t 1PTime (sec)
M I N : 0.00 MAX: 100.
VALUE: 90.000
CANCEL ^
F1 ENTER
U V o l t1PPU 11.52
> U V o l t1PTime 90.00
U V o l t3PPU 11.52
U V o l t3PTime 100.0
MENU
S E L E C T AN OPTION
F O R T HE ALTERED
S E T T I NGS:
USE REVERT BACK
F1 F2 F4
2-28
!
SAFETY
S280-70-21
FOR LIFE
Loadshed Restore
Cold Load Pickup
The Form 6 control provides an Undervoltage, Overvoltage,
Frequency
Voltage
and Underfrequency loadshed restoration feature to allow the
>Loadshed Restore recloser to automatically close when voltage and/or frequency
ENTER
returns to within configured settings.
Loadshed Restore allows for restoration after an undervolt-
>VoltRestor Off
VoltRestor Any Sing age, overvoltage, or underfrequency trip condition. The res-
VoltRestHiL
VoltRestLoL
15.12
13.68 toration function can be enabled and restoration parameters
VoltFreqRe Off can be adjusted and set.
FreqRestor Off
Freq:81OR:PU 60.04
Freq:62Sched 300.0
Freq:62Trans 0.300
Freq:62Abort 600.0
>VoltRestor Off
VoltRestor Any Sing
VoltRestHiL 15.12
VoltRestLoL 13.68
VoltFreqRe Off
FreqRestor Off
Freq:81OR:PU 60.04
Freq:62Sched 300.0
Freq:62Trans 0.300
Freq:62Abort 600.0
To Enable Loadshed Restoration
To Enable Under/Overvoltage Using Both Voltage and To Enable Underfrequency
Loadshed Restoration: Frequency Restoration Limits: Loadshed Restoration:
>VoltRestor Off VoltRestor Any Sing VoltRestHiL 15.12
VoltRestor Any Sing VoltRestHiL 15.12 VoltRestLoL 13.68
VoltRestHiL 15.12 VoltRestLoL 13.68 VoltFreqRe Off
VoltRestLoL 13.68 >VoltFreqRe Off >FreqRestor Off
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-29
Form 6 Microprocessor-Based Recloser Control Programming Guide
>VoltRestor Off
VoltRestor Any Sing
VoltRestHiL 15.12
VoltRestLoL 13.68
VoltFreqRe Off
FreqRestor Off
Freq:81OR:PU 60.04
Freq:62Sched 300.0
Freq:62Trans 0.300
Freq:62Abort 600.0
To Set Under/Overvoltage
Loadshed Restoration Mode: To Set High Voltage Limit: To Set Low Voltage Limit: To Set Frequency Limit:
>VoltRestor Any Sing VoltRestor Any Sing VoltRestor Any Sing >Freq:81OR:PU 60.04
VoltRestHiL 15.12 >VoltRestHiL 15.12 VoltRestHiL 15.12 Freq:62Sched 300.0
VoltRestLoL 13.68 VoltRestLoL 13.68 >VoltRestLoL 13.68 Freq:62Trans 0.300
VoltFreqRe Off VoltFreqRe Off VoltFreqRe Off Freq:62Abort 600.0
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-30
!
SAFETY
S280-70-21
FOR LIFE
>VoltRestor Off
VoltRestor Any Sing
VoltRestHiL 15.12
VoltRestLoL 13.68
Even though the setting names
VoltFreqRe Off
Freq:62Sched, Freq:62Trans, and FreqRestor Off
Freq:62Abort imply Frequency Restoration Freq:81OR:PU
Freq:62Sched
60.04
300.0
only, they also apply to Voltage Restoration. Freq:62Trans 0.300
Freq:62Abort 600.0
Press < or > to move the selection cursor to the position underneath the digit you want to change.
Press + or - to increase or decrease the number above the selection cursor.
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-31
Form 6 Microprocessor-Based Recloser Control Programming Guide
Frequency
Voltage
Loadshed Restore
>Sensitive Earth Flt
ENTER
>SEFBlock Enable
SEFMinTrip 40.00
SEFTime 120.0
SEFReclInt 2.000
ENTER
SEFBlock
PRESS [+] or [-] KEY
Disable
CANCEL
ENTER F4
(or Press F4 to CANCEL)
>SEFBlock Disable
SEFMinTrip 40.00
SEFTime 120.0
SEFReclInt 2.000
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-32
!
SAFETY
S280-70-21
FOR LIFE
SEFMinTrip (A pri)
MIN: 0.50 M A X: 100.
VALUE: 40.000
CANCEL ^
Press < or > to move the selection cursor to the
position underneath the digit you want to change.
Press + or - to increase or decrease the number above the selection cursor.
SEFMinTrip (A pri)
MIN: 0.50 M AX: 100.
VALUE: 41.000
CANCEL ^
F1 ENTER
SEFBlock Enable
>SEFMinTrip 41.00
SEFTime 120.0
SEFReclInt 2.000
MENU
S E L E C T A N O P TION
F O R T H E A L T E RED
SETTINGS:
USE REVERT BACK
F1 F2 F4
ENTER
SEFTime (sec)
MIN: 0.10 MAX: 3 0 0 .
VALUE: 12 0 . 0 0 0
CANCEL ^
Press < or > to move the selection cursor to the
position underneath the digit you want to change.
Press + or - to increase or decrease the number above the selection cursor.
SEFTime (sec)
MIN: 0.10 MAX: 3 0 0 .
VALUE: 12 1 . 0 0 0
CANCEL ^
F1 ENTER
SEFBlock Enable
SEFMinTrip 40.00
>SEFTime 121.0
SEFReclInt 2.000
MENU
SELECT AN OPTI O N
FOR THE ALTERE D
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-33
Form 6 Microprocessor-Based Recloser Control Programming Guide
S E F R e c l I nt (sec)
M I N : 1 . 0 0 MAX: 100.
VALUE: 3.000
CANCEL ^
F1 ENTER
SEFBlock Enable
S E F M i n T rip 40.00
SEFTime 120.0
> S E F R e c l Int 3.000
MENU
S E L E C T A N OPTION
F O R T H E ALTERED
SETTINGS:
USE R E VERT BACK
F1 F2 F4
ENTER
S E F M inTrip 40.00
S E F T ime 120.0
S E F R eclInt 2.000
> S E F N umOps 4
ENTER
S E F N u m Ops
P R E S S [+] or [-] KEY
3
CANCEL
ENTER F4
(or Press F4 to CANCEL)
S E F M i nTrip 40.00
S E F T i me 120.0
S E F R e clInt 2.000
> S E F N u mOps 3
MENU
S E L E C T AN OPTION
F O R T H E ALTERED
S E T T I N GS:
USE REVERT BACK
F1 F2 F4
2-34
!
SAFETY
S280-70-21
FOR LIFE
Activating Sensitive
Voltage
Earth Fault
Loadshed Restore
Sensitive Earth Flt
The diagram at the left shows the screen process to activate
>Ungrounded SEF the Ungrounded Sensitive Earth Fault feature.
ENTER
>USEFBlock Enable
USEFMinTrip 40.0
USEFTime 10.0
USEFRecloseInter.
ENTER
USEFBlock
PRESS [+] or [-] KEY
Enable
CANCEL
+ or -
USEFBlock
PRESS [+] or [-] KEY
Disable
CANCEL
ENTER F4
(or Press F4 to CANCEL)
>USEFBlock Disable
USEFMinTrip 40.0
USEFTime 10.0
USEFRecloseInter.
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-35
Form 6 Microprocessor-Based Recloser Control Programming Guide
USEFMinTrip ( A pri)
MIN: 0.50 M A X : 100.
VALUE: 5 0 .00
CANCEL ^
F1 ENTER
USEFBlock E n able
>U S E F M i n T r i p 5 0.00
USEFTime 1 0.0
USEFRecloseInter.
MENU
SE L E C T A N O P T I O N
FO R T H E A L T E R E D
SE T T I N G S :
USE REVERT B ACK
F1 F2 F4
USEFBlock E nable When you select the USEF Trip Time parameter, the minimum
USEFMinTrip 40.00
>USEFTime 10.0
and maximum selection limits of the setting are displayed.
U S E F R e c l o s e I n t e r.
ENTER
US E F T i m e ( sec)
MI N : 0 . 1 0 M A X : 3 00.
VA L U E : 1 2 0 . 000
CA N C E L ^
Press < or > to move the selection cursor to the
position underneath the digit you want to change.
Press + or - to increase or decrease the number above the selection cursor.
US E F T i m e ( sec)
MI N : 0 . 1 0 M A X : 3 00.
VA L U E : 1 3 0 . 000
CA N C E L ^
F1 ENTER
USEFBlock E n able
USEFMinTrip 4 0.00
USEFTime 1 30.0
>USEFRecloseIntern
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT B ACK
F1 F2 F4
2-36
!
SAFETY
S280-70-21
FOR LIFE
Voltage
Loadshed Restore
Sensitive Earth Flt
>Ungrounded SEF
ENTER
USEFBlock Enable
USEFMinTrip 40.00
USEFTime 10.0
>USEFRecloseInter.
ENTER
MENU
SELECT AN OPTION
FOR THE ALTERED
SETTINGS:
USE REVERT BACK
F1 F2 F4
2-37
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
U S E F MinTrip 40.00
U S E F Time 10.0
U S E F RecloseInter.
> U S E F NumOps 1
ENTER
U S E F N u mOps
P R E S S [+] or [-] KEY
1
CANCEL
+ or -
U S E F N u mOps
P R E S S [+] or [-] KEY
4
CANCEL
ENTER F4
(or Press F4 to CANCEL)
U S E F MinTrip 40.00
U S E F Time 120.0
U S E F ReclInt 2.000
> U S E F NumOps 4
MENU
S E L E C T AN OPTION
F O R T HE ALTERED
S E T T I NGS:
USE REVERT BACK
F1 F2 F4
ENTER
USEFTime 10.0
U S E F R e c l o s e I n t er.
USEFNumOps 1
>U S E F V O 0.480
ENTER
USEFVO ( kVpri)
MIN: 0.48 M A X : 14.4
VALUE: 0.480
CANCEL ^
Press < or > to move the selection cursor to the
position underneath the digit you want to change.
Press + or - to increase or decrease the number above the selection cursor.
US E F V O ( kVpri)
MI N : 0 . 4 8 M A X : 14.4
VA L U E : 0.480
CA N C E L ^
F1 ENTER
USEFTime 10.00
U S E F R e c l o s e I n t er.
USEFNumOps 1
>USEFVO 0.490
MENU
SE L E C T A N O P T I O N
FO R T H E A L T E R E D
SE T T I N G S :
USE REVERT BACK
F1 F2 F4
2-38
!
SAFETY
S280-70-21
FOR LIFE
Metering Menu
The Form 6 control displays metering data on the front panel
SETTINGS
LCD as well as through the ProView interface software.
>METERING
SEQUENCE OF E V E N T S Note: The Metering menu LCD displays Metering Data only. All
ALARM LOG & S T A T U S
metering programming is done via the ProView interface soft-
ENTER ware included with the Form 6 recloser control.
>Inst. Meter i n g
Demand Mete r i n g The Metering menu shows:
Power Meter i n g
Energy Mete r i n g
Instantaneous Phase and Ground Currents and
Vsec. Metering
Isec. Metering Source-Side Primary Voltages
Power Factor
freq = 60.000 Hz
Instantaneous Secondary Phase and Ground Currents
ENTER and Source-Side and Load-Side Voltages
Primary Demand and Peak Phase and Ground
Currents
Primary Demand and Peak Power Values (kW and kvar)
METERING Shortcut Key Instantaneous Power Values (kW and kvar)
Energy Values (kWH and kvarH)
Instantaneous Power Factor Values
METERING SETTINGS
RESET OPER
Frequency
TARGETS COUNTER
The Metering module calculates and maintains the power-
related parameters for the forward (out) and reverse (in)
F1 F2 F3 F4
+
EVENTS ALARMS
LAMP TEST
MENU
CHANGE
metering directions.
Detailed information on programming Metering data via
EXPANDED
MEMORY
ENTER the interface software is available in the Form 6 Control
Schemes section of this manual.
Note: As a shortcut, the Instantaneous Metering display can be
accessed from the front panel METERING shortcut key.
Instantaneous Metering
The front panel LCD display for instantaneous metering
shows the Primary Current values for A, B, C phase and
Ground.
The Instantaneous Voltage for each source-side phase is dis-
played as Primary voltages.
Vsec. Metering will show instantaneous secondary values for
SETTINGS load- and source-side voltages.
>METERING
S E Q U E N C E OF EVENTS Isec. Metering will show instantaneous values for secondary
A L A R M L O G _ STATUS
current values for A, B, and C phase and Ground.
ENTER
The primary voltage values displayed in the Instantaneous
> I n s t . M e tering
D e m a n d M etering Metering menu are determined by the PT connection setting.
P o w e r M e tering
E n e r g y M etering
With a Wye conection setting, line-to-neutral values will be
shown. With a Delta connection setting, line-to-line values
ENTER
will be shown. Regardless of the number of connected PTs,
IA: 0 .VA: 0. as defined in the System Configuration setting dialog box, all
IB: 0 .VB: 13816.
IC: 0 .VC: 0. three primary voltage values will be displayed if the Phantom
IG: 0.0
Phase functionality is enabled.
MENU
2-39
Form 6 Microprocessor-Based Recloser Control Programming Guide
Demand Metering
The Demand Metering display shows the calculated:
Inst. Me tering
>Demand M etering Primary Demand and Peak Currents (A, B, C Phase
Power Me tering
Energy M etering and Ground)
ENTER Total Demand and Peak real and reactive power values
>Reset De mand Peaks
Demand P hase Amps
Per phase Demand and Peak real and reactive power
Demand T ot kW, kvar values
Demand k W-out
Demand kW-in All demand-metered power values include measurements in
Demand kvar-out
Demand kvar-in the forward (out) or reverse (in) direction. As an example,
ENTER
Demand kW-out displays demand kilowatts in the forward
direction for loads with no co-generation, while forward kW-in
displays demand kilowatts in the reverse direction when sup-
plied from the co-generator.
Note: Demand Metering values are automatically reset when a pro-
tection profile is changed, a new setting is downloaded from
the PC, or when a scheme is downloaded from the PC.
Detailed Demand Metering programming information is found
in the Form 6 Control Schemes section of this manual.
ENTER
ENTER
F4 MENU (abort)
Press F4 and hold.
MENU
2-40
!
SAFETY
S280-70-21
FOR LIFE
MENU
ENTER
ENTER
>2005-08-16 10:18:59
kW
Demand Tot kW, kvar
Time of Peak
MENU
ENTER
ENTER
>2005-08-16 07:27:36
A->
Demand kW-out
Time of Peak
MENU
2-41
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
>2005-08-16 07:27:36
A->
Demand kW-in
Time of Peak
MENU
ENTER
>2005-08-16 07:27:36
A->
Demand kvar-out
Time of Peak
MENU
ENTER
>2005-08-16 07:27:36
A->
Demand kvar-in
Time of Peak
MENU
2-42
!
SAFETY
S280-70-21
FOR LIFE
Power Metering
SETTINGS The Power Metering LCD screen shows the calculated instan-
>METERING
SEQUENCE OF EVENTS
taneous Real Power (kW) and Reactive Power (kvar) values
ALARM LOG & STATUS
for each phase and the Total Instantaneous Real and Reactive
ENTER
power value of all three phases.
Inst. Metering
Demand Metering
>Power Metering
Energy Metering
Vsec. Metering
Isec. Metering
Power Factor
freq = 60.000 Hz
ENTER
>k W A = 0.0
kWB = 0.0
kWC = 0.0
kWT = 0.
kvarA = 0.0
kvarB = 0.0
kvarC = 0.0
kvarT = 0.0
Energy Metering
SETTINGS The Energy Metering LCD screen shows the calculated Real
>METERING
SEQUENCE OF EVENTS Energy (kWH) and Reactive Energy (kvarH) values for each
ALARM LOG & STATUS
phase and the Total Real and Reactive Energy valueof all
ENTER
three phases.
Inst. Metering
Demand Metering
Power Metering
>Energy Metering
Vsec. Metering
Isec. Metering
Power Factor
freq = 60.000 Hz
ENTER
>R e s e t E n e r g y M e t e r s
Energy Meters (Out)
Energy Meters (In)
ENTER
F4 MENU (abort)
Press F4 and hold.
MENU
2-43
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER ENTER
Vsec Metering
S E T T I NGS Vsec Metering will show instantaneous secondary values for
> M E T E R ING
S E Q U E NCE OF EVENTS load and source side.
A L A R M LOG & STATUS
ENTER
I n s t . Metering
D e m a n d Metering
P o w e r Metering
E n e r g y Metering
>Vsec. Metering
Isec. Metering
Power Factor
freq = 60.000 Hz
ENTER
Va: 0.Vx: 0.
Vb: 0.Vy: 0.
Vc: 0.Vz: 0.
MENU
Isec Metering
Isec Metering will show instantaneous values for secondary
S E T T I N GS
> M E T E R I NG
current values for A, B, C phase and ground.
S E Q U E N CE OF EVENTS
A L A R M LOG & STATUS
ENTER
I n s t . Metering
D e m a n d Metering
P o w e r Metering
E n e r g y Metering
Vsec. Metering
>Isec. Metering
Power Factor
freq = 60.000 Hz
ENTER
Ia: 0.0000000
Ib: 0.0000000
Ic: 0.0000000
Ig: 0.0000000
MENU
2-44
!
SAFETY
S280-70-21
FOR LIFE
Power Factor
The front panel read-only Power Factor screen shows the
SETTINGS Instantaneous power factor (pf) of each individual phase and
> METERING
SEQUENCE OF EVENTS the Total power factor (pfT) of all three phases.
ALARM LOG & STATUS
ENTER
Demand Metering
Power Metering
Energy Metering
Vsec. Metering
Isec. Metering
>Power Factor
ENTER
Frequency
Frequency, a read-only display, is automatically updated
SETTINGS and displayed in the METERING menu. The phase or phas-
> METERING
SEQUENCE OF EVENTS es are selected via the ProView interface software in the
ALARM LOG & STATUS Configure>System Configuration dialog box.
ENTER
When freq = (n/a) Hz is displayed, no voltage is present on
Power Metering
Energy Metering the selected phase or phases.
Vsec. Metering
Isec. Metering
Power Factor
>freq = 60.000 Hz
2-45
Form 6 Microprocessor-Based Recloser Control Programming Guide
> E N T E R t o v i ew SOE
The Sequence of Events menu shows:
Event Definition
Date of Event Year/Month/Day
ENTER Event
1 N O R M A L P R OFILE Example Time of Event
0 5 / 0 8 / 1 5 1 0 : 26:59.9
A 0B 0C 0 A, B, and C Phase Current
G 0 A 0 B 116C 0
Press the downward cursor movement
Ground Current
arrow to scroll to the next event.
A, B, and C Phase Secondary Voltage
EVENTS Shortcut Key The secondary voltage values displayed in the
Sequence of Events menu will either be line-to-neutral
METERING SETTINGS values if the PTs are connected in a Wye configuration
RESET
TARGETS
OPER
COUNTER or simulated, equivalent, line-to-neutral values if the PTs
F1 F2 F3 F4 are connected in a Delta configuration. Only the sec-
+ ondary voltage values of the connected PTs, as defined
EVENTS ALARMS
MENU
in the System Configuration setting dialog box, will be
LAMP TEST CHANGE
2-46
!
SAFETY
S280-70-21
FOR LIFE
IMPORTANT: There are several alarms No AC Present (Only available for Form 6 pole mount
that will cause the alternate blinking of the controls. The Pole Mounted Control box in the
CONTROL LOCKOUT, RECLOSER OPEN, and ProView System Configuration screen must be select-
RECLOSER CLOSED LEDs: Failure to Trip, ed. Refer to Configure - System Configuration sec-
Failure to Close, Interrupter Malfunction, and tion for additional information.)
52a/b Disagreement. Hot Line Tag Close Attempt
The LED blinking pattern for these conditions Self-Clear Fault
is the CONTROL LOCKOUT green LED and
Load Side PT Error
RECLOSER CLOSED red LED alternating with
the RECLOSER OPEN green LED. CT Ratio Error This alarm will assert if the current
sensing hardware option in your Form 6 control does
In addition to the above LED blinking pattern,
not match the CT Type setting in the ProView applica-
the red ALARM LED will also be blinking for
these alarms: Failure to Trip, Failure to Close, tion software. For instance, your Form 6 control has a
and Interrupter Malfunction. current sensing option intended for a 1 Amp CT and
you downloaded settings that are only compatible with
a 5 Amp CT type by selecting X:5 CT in the System
Configuration dialog box.
RIFComm Failure
There are two types of Status Alarms:
ALARMS Shortcut Key
Control Alarm Signified by the continuous illumination
METERING
of the Alarm LED. These are Control Alarms:
SETTINGS
Power Supply Malfunction
RESET OPER
TARGETS COUNTER RAM Failure
F1 F2 F3 F4 ROM Failure
+
EVENTS ALARMS
Battery Alarm
MENU
LAMP TEST CHANGE Load side PT Error
CT Ratio Error
ENTER No AC Present (pole mount only)
RIFComm Failure
System Alarm Signified by the flashing Alarm LED.
These are System Alarms:
Trip Malfunction (Failure to Trip)
Close Malfunction (Failure to Close) (Refer to
Resetting Alarms.)
Interrupter Malfunction
Loss of Sensing
Sync Close Alarm
Hot Line Tag Close Attempt
Self-Clear Fault
Note: As a shortcut, the ALARM menu can be accessed from the
ALARMS shortcut key on the front panel.
2-47
Form 6 Microprocessor-Based Recloser Control Programming Guide
Resetting Alarms
The Alarm settings listed in the LCD display can be reset
S E T TINGS from the front panel. The diagram shows the screen process
M E T ERING
S E Q UENCE OF EVENTS to reset control parameter alarms.
> A L A RM LOG & STATUS
Note: After F4 (RESET) is pressed, the phrase --ALARMS ARE
ENTER
RESET-- appears in the LCD display for approximately 2
> R e set Alarms
T r ip Malfunction.. 0
seconds.
C l ose Malfunction. 0
I n terrupter Malf.. 0 The alarm will only reset if the condition that triggered the
ENTER alarm is no longer present.
> P u s h RESET to reset >Push RESET to reset Note: The Close Malfunction alarm must be reset before Closing
a l l alarms. all alarms.
P u s h MENU to abort.
OR
Push MENU to abort. will be allowed.
. . . . ..........RESET ..............RESET
F4 MENU (abort)
Press F4 and hold.
> P u s h RESET to rese t >Reset Alarms
a l l alarms. Trip Malfunction..0
P u s h MENU to abort . Close Malfunction.0
- - A L ARMS ARE RESET- - Interrupter Malf..0
2-48
!
SAFETY
S280-70-21
FOR LIFE
Counters Menu
ME TERING
Counters are part of the historical data record within the Form
SE QUENCE OF EVENTS 6 Recloser control. The Form 6 control contains counter data
AL ARM LOG & STATUS
>CO UNTERS saved in non-volatile memory, and is resettable from the front
ENTER panel. Counters display the cumulative number of operations
>Res et Target Cntrs for specific functions.
Tri p Counter 0
A P h Targ Cntr 0 The counters increment each time an operation takes place,
B P h Targ Cntr 0
C P h Targ Cntr 0 independent of any time interval. Counters can be reset
Gnd Targ Cntr 0
SEF Targ Cntr 0 locally from the front panel or through the Form 6 ProView
USE F Targ Cntr 0
Res et Trip Counter
Interface software.
The counters are:
Trip Operations Counter
METERING SETTINGS
A-Phase, B-Phase, C-Phase, Ground, and Sensitive
RESET
TARGETS
OPER
COUNTER
Earth Fault Target Counters
F1 F2 F3 F4 Note: As a shortcut, the COUNTERS menu can be accessed from
+
EVENTS ALARMS the OPER COUNTER shortcut key on the front panel.
MENU
LAMP TEST CHANGE
ENTER
Resetting Counters
If the Form 6 recloser control is replacing another Cooper
METERING Power Systems control, the counters can be set to match the
S E Q U E N C E O F E VENTS
A L A R M L O G & S TATUS
counter of the current control.
>COUNTERS
Target and Operations (Trip) Counters program-
ENTER
ming information is found in the Form 6 Control
> R e s e t T a r g e t Cntrs
Trip Counter 0
Schemes>Settings>Presets section of this manual.
A Ph Targ Cntr 0
B Ph Targ Cntr 1 The diagram at the left shows the screen process for reset-
ENTER
ting Target Counters. The same process is followed for the
Trip Counter, which is the last sub-menu item.
> P u s h R E S E T t o reset >Push RESET to reset
T a r g e t c o u n t e r s. OR Target counters.
P u s h M E N U t o a bort. Push MENU to abort.
. . . . . . . . . . . . . . RESET ..............RESET
F4 MENU (abort)
Press F4 and hold.
> P u s h R E S E T t o reset
T a r g e t c o u n t e r s.
P u s h M E N U t o a bort.
. . . . . . . . . . . . . . RESET
MENU
> R e s e t T a r g e t Cntrs
Trip Counter 0
A Ph Targ Cntr 0
B Ph Targ Cntr 0
1 T. Takagi, Y. Yamakoshi, J. Baba, K. Uemura, T. Sakaguchi, "A New Algorithm of an Accurate Fault Location for EHV/UHV Transmission Lines: Part I
- Fourier Transformation Method", IEEE Trans. on PAS, Vol. PAS-100, No. 3, March 1981, pp 1316-1323.
2-49
Form 6 Microprocessor-Based Recloser Control Programming Guide
2-50
!
SAFETY
S280-70-21
FOR LIFE
2-51
Form 6 Microprocessor-Based Recloser Control Programming Guide
Workbench Menu
The Workbench screen provides access to custom user mes-
sages, custom analog data, status data, virtual switches, and
Workbench name information that is configured as part of the
Idea Workbench.
Workbench Messages: Displays user-configured mes-
sages. Refer to Workbench Message Outputs to MMI
in the Idea Workbench section of this manual for mes-
sage customization information.
Workbench Analogs: Displays Workbench configured
analog measurements. Refer to Workbench Analog
Outputs to MMI in the Idea Workbench section of this
manual for description customization information.
Workbench Status: Displays Workbench configured sta-
tus points for user-defined Sequence of Events. Refer to
the Workbench Status Outputs to MMI and SOE and
Workbench Outputs Toolbox sections of this manual
for additional information.
Workbench Switches: Accesses Workbench configured
virtual switches. Refer to Workbench MMI Softkey
Switches in the Idea Workbench section of this manu-
al for description customization information.
Workbench Name: Displays the user-defined Workbench
C O U N T ERS Description. Refer to Workbench Description in the
B A T T E RY
D N P P ROTOCOL Idea Workbench section of this manual for description
> W O R K B ENCH
customization information.
ENTER
ENTER
> W O R K B ENCH MESSAGES WORKBENCH MESSAGES WORKBENCH MESSAGES WORKBENCH MESSAGES WORKBENCH ANALO GS
W O R K B ENCH ANALOGS > WORKBENCH ANALOGS WORKBENCH ANALOGS WORKBENCH ANALOGS WORKBENCH STATU S
W O R K B ENCH STATUS WORKBENCH STATUS >WORKBENCH STATUS WORKBENCH STATUS WORKBENCH SWITC HES
W O R K B ENCH SWITCHES WORKBENCH SWITCHES WORKBENCH SWITCHES >WORKBENCH SWITCHES >WORKBENCH NAME
T h e r e Are No > Analog #01= 0.000 >0=MMI(#01) status >Momentary Switch #1 WORKBENCH NAME.. .
Active Analog #02= 0.000 0=MMI(#02) status Momentary Switch #2 Form6
User Analog #03= 0.000 0=MMI(#03) status Momentary Switch #3
M e s s a g es Analog #04= 0.000 0=MMI(#04) status Momentary Switch #4
MENU Analog #05= 0.000 0=MMI(#05) status
Analog #06= 0.000 0=MMI(#06) status MENU
Analog #07= 0.000 0=MMI(#07) status >Push YES to operate
Analog #08= 0.000 0=MMI(#08) status Push MENU to abort.
0=MMI(#09) status Momentary Switch #1
0=MMI(#10) status ................YES
MENU
0=MMI(#11) status
0=MMI(#12) status F4
0=MMI(#13) status Press F4 and hold.
0=MMI(#14) status
0=MMI(#15) status >Push YES to operate
0=MMI(#16) status Push MENU to abort.
0=MMI(#17) status Momentary Switch #1
0=MMI(#18) status ----(OPERATING!)----
0=MMI(#19) status
0=MMI(#20) status >Push YES to operate
0=MMI(#21) status Push MENU to abort.
0=MMI(#22) status Momentary Switch #1
0=MMI(#23) status ................YES
0=MMI(#24) status
MENU
MENU
>Momentary Switch #1
Momentary Switch #2
Momentary Switch #3
Momentary Switch #4
2-52
!
SAFETY
S280-70-21
FOR LIFE
Clock Menu
The LCD display shows the year, month, date, hour, minutes,
and seconds.
BATTERY
D N P P R OTOCOL
W O R K B E NCH The diagram at left shows the screen process for setting/
>CLOCK
changing the clock.
ENTER
Note: The time/date clock will continue to operate for approximately 30
> 2 0 1 2 - 0 8-16 14:19:36 days after loss of control power.
ENTER
2 0 1 2 - 0 8-16 14:19:36
^
CANCEL
Press < or > to move the selection cursor to the
position underneath the digit you want to change.
Press + or - to increase or decrease
the number above the selection cursor.
2 0 1 2 - 0 8-16 15:19:36
^
CANCEL
ENTER F4
(or Press F4 to CANCEL)
MENU
2-53
Form 6 Microprocessor-Based Recloser Control Programming Guide
2-54
!
SAFETY
S280-70-21
FOR LIFE
Diagnostics Menu
The Diagnostics screen displays the current status of the
recloser connected to the Form 6 recloser control.
W O R K BENCH These are specific signals displayed to the user in real time.
CLOCK
F A U L T LOCATOR
> D I A G NOSTICS Trip Signal
ENTER 0 = Recloser is not in the process of issuing a trip sig-
> T r i p Signal.......0 nal.
C l o s e Signal......0
R e c l ose Interval..0
S e q u ence Position.0
1 = Recloser is in the process of issuing a trip signal.
A c t Recl Int 2.0s
Close Signal
S R M Counter.......0
R e s e t SRM Counter
0 = Recloser is not in the process of issuing a close
signal.
1 = Recloser is in the process of issuing a close sig-
nal.
Reclose Interval (time between fault interruptions)
0 = Control is not in the reclosing interval.
1 = Control is in the reclosing interval.
Sequence Position
0 = Recloser is at the HOME position.
1 = Recloser tripped once in the sequence.
2 = Recloser tripped twice in the sequence.
3 = Recloser tripped three times in the sequence.
4 = Recloser tripped four times in the sequence.
Actual Reclose Interval
#s = Next reclose interval as configured by the user.
SRM Counter (Self Recovery Mechanism)
A log of unintentional expiration of the hardware
watchdog.
Reset SRM Counter
Press ENTER and then RESET to reset the SRM
counter to 0.
2-55
Form 6 Microprocessor-Based Recloser Control Programming Guide
CLOCK
FAULT LOCATOR
DIAGNOSTICS
>I/O CONTROL
ENTER
>Activate Out 1 -4 Activate Out 1-4 Activate Out 1-4 Activate Out 1-4
Activate Out S S1 >Activate Out SS1 Activate Out SS1 Activate Out SS1
Activate Out 5 -8 Activate Out 5-8 >Activate Out 5-8 Activate Out 5-8
Activate Out 9 -12 Activate Out 9-12 Activate Out 9-12 >Activate Out 9-12
F1 F2 F3 F4 F1 F1 F2 F3 F4 F1 F2 F3 F4
Push F1, F2, F3, or F4 and hold. Push F1 and hold. Push F1, F2, F3, or F4 and hold. Push F1, F2, F3, or F4 and hold.
2 4 6 8 10 12 14 16 18
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11 CO12
1 3 5 7 9 11 13 15 17 19 21 1 3 5 7 9 11 13
TB3 TB4
2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11 CO12
2-56
!
SAFETY
S280-70-21
FOR LIFE
C 11 C S 111
I 123 4 5 6 78901 0 1234S 56789012
MENU MENU
2 4 6 8 10 12 14 16 18
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11 CO12
1 3 5 7 9 11 13 15 17 19 21 1 3 5 7 9 11 13
TB3 TB4
2 4 6 8 10 12 14 16 18 20 2 4 6 8 10 12
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6 CO7 CO8 CO9 CO10 CO11CO12
2-57
Form 6 Microprocessor-Based Recloser Control Programming Guide
2-58
!
SAFETY
S280-70-21
FOR LIFE
ENTER ENTER
ENTER
(or Press F4 to CANCEL)
>Test Mode On
Targ Cntr Off
MENU
2-59
Form 6 Microprocessor-Based Recloser Control Programming Guide
2-60
!
SAFETY
S280-70-21
FOR LIFE
3-1
Form 6 Microprocessor-Based Recloser Control Programming Guide
3-2
!
SAFETY
S280-70-21
FOR LIFE
3-3
Form 6 Microprocessor-Based Recloser Control Programming Guide
3-4
!
SAFETY
S280-70-21
FOR LIFE
Login / Logout
When the Login/Logout screen appears:
1. Click on the arrow next to the NAME box.
2. Select the name of the appropriate access level.
MODIFY: User has all the capabilities of the
OPERATE level, plus the ability to make
scheme setting and structure modifica-
tions.
OPERATE: User has all the capabilities of the
VIEW level, plus the ability to download
schemes, settings, and firmware; delete
events, and complete other scheme-
dependent operations. No scheme set-
ting or structure modifications are allowed
at the OPERATE level.
VIEW: User can view metering and event data,
check settings, print and print preview,
and other read-only operations. No
changes are allowed at the VIEWlevel.
Shortcut: Type the first letter of the access level you
wish to enter; the name will appear in the box
(i.e. V for View).
3. Select the PASSWORD box.
4. Type in the password. The default password is the
same as what you selected in the NAME box.
Note: Passwords are case-sensitive. Therefore, type the
name in the PASSWORD box exactly the way it
appears. Capitalize the first letter of the word. The
password is disguised with asterisks (*).
5. Select LOGIN.
Note: If you choose not to login, select EXIT to exit ProView.
You are now ready to load a scheme.
Note: If you double-clicked on the Form 6 recloser control scheme
icon located on your desktop, the scheme will automatically
open.
Refer to the Loading Schemes section of this manual for
additional information.
3-5
Form 6 Microprocessor-Based Recloser Control Programming Guide
3-6
!
SAFETY
S280-70-21
FOR LIFE
File Menu
Use the Main FILE drop down menu to OPEN a Form 6
scheme in a new window. You can open multiple schemes at
one time.
The FILE menu is where you EXIT the ProView session.
3-7
Form 6 Microprocessor-Based Recloser Control Programming Guide
Manage Menu
When a scheme is not open, the ProView MANAGE drop-
down menu only lets you open the MANAGE CONNECTIONS
dialog box, which is used for editing the characteristics of the
PC communication connections.
Manage Menu options when
a scheme is not open.
User Menu
The ProView USER drop-down menu lets you login and log
out of the ProView session.
Open a scheme from the PC hard drive.
This menu also accesses the User Editor dialog box that is
used to add/remove users and change passwords. Refer to
Adding / Deleting Users and Changing Passwords in the
Login / Logout section of this manual for additional informa-
tion.
View Menu
The ProView VIEW drop-down menu lets you display the
Toolbar, the Status bar, and the Connection Status.
The Toolbar consists of the icons below the main ProView
menu.
The Status Bar displays information at the bottom of the
ProView window when you highlight menu items with the cur-
sor.
The Connection Status (displayed next to the Toolbar) shows
View Menu options when the connection status between ProView and the Form 6
a scheme is not open. recloser control.
3-8
!
SAFETY
S280-70-21
FOR LIFE
Help Menu
The HELP drop-down menu accesses ProView Online Help
and Scheme Help. Scheme Help is only available when a
scheme is open.
3-9
Form 6 Microprocessor-Based Recloser Control Programming Guide
3-10
!
SAFETY
S280-70-21
FOR LIFE
Loading Schemes
The FILE menu dropdown lists the Form 6 control schemes
at the bottom. Schemes can be opened by selecting one
from the list or by using the OPEN command at the top of the
FILE menu.
4-1
Form 6 Microprocessor-Based Recloser Control Programming Guide
T216.2
Communications Information
The Select Connection dialog box will appear.
4. Select the appropriate connection and click OK.
Note: Verify that no additional software (i.e. hand-held PDA
devices) requires the same serial communication port
(COM port) as the designated ProView software.
Note: Additional connections can be added to this list. Refer
to Adding ProView Connection Profiles section
in this manual for additional information.
5. You will be prompted to enter the control password.
There are two control password levels:
The first level is the Upload Level, which only allows
you to upload items from the control (i.e., SOE,
Oscillographic Events, Settings).
The default password for the Upload Level is View.
The second level is the Download Level, which
allows you to upload items from the control (i.e.,
SOE, Oscillographic Events, Settings) and down-
load items to the control (i.e. Scheme, Settings,
Operate via Application Diagram, Firmware).
The default password for the Download Level is
Modify.
Note: If you typically login to ProView using the View access
level, you should connect to the control using the
Upload Level password.
If you typically login to ProView using the Modify or
Operate access level, you should connect to the con-
trol using the Download Level password.
Note: If you forget the control password, contact the Switchgear
Support Group at 1-800-497-5953.
4-2
!
SAFETY
S280-70-21
FOR LIFE
Note: If you attempt to connect via the wrong port, you can abort
the connection attempt by clicking on CONNECT anytime it
appears with the yellow question mark (?) symbol. Clicking
on CONNECT after communication has been established will
disconnect the PC from the control.
The yellow question mark (?) symbol can occur for the
following reasons: incompatible version of ProView,
incorrect communication port, or no cable connected.
4-3
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-4
!
SAFETY
S280-70-21
FOR LIFE
4-5
Form 6 Microprocessor-Based Recloser Control Programming Guide
Ethernet Configuration
Device settings can only be changed once a connection is
made to the Form 6 control via the RS-232 port. Connect to
the front panel for initial network setup.
Complete the fields in the Device Settings dialog box:
Modem initialization string If the control is being connected
through a modem and it is necessary to setup the modem
upon power up, this field allows you to setup the modem
upon power up.
TCP/IP Configuration
Network name: This setting is user-defined.
Domain name: This setting is user-defined.
IP Address: A static IP address must be allocated to function.
This address is provided by the user IT Department.
Subnet Mask: A static subnet mask must be allocated to
function. This address is provided by the user IT Department.
SDU (Session Data Unit) size: This value must remain set to
8192.
Buffer segment size: This value must remain set at 1050.
Note: The above two variables might change in the future as UCA
develops.
ProView port: This value can be any valid IP port setting, but
must match ProView and the Form 6 control. 1024 is the
default setting and can be changed as necessary to match
individual network settings. Contact your IT department for
further consultation.
Default gateway: If the device you are connecting to is on a
different network segment (defined by the subnet mask) a
default gateway must be entered in this field.
Primary Ethernet interface: This specifies which of the two
ports on the Ethernet card is the primary communications
port. Value 1 denotes the port nearest to the edge of the
control and 2 denotes the port closest to the RS-232 port.
Note: The Ethernet Interface will not automatically change between
primary and secondary ports in the event of network failure.
Physical Address Configuration
Factory address: This is the MAC (media access control-
ler) address or physical address of the card. This address is
unique to this piece of hardware and cannot be changed by
the user.
Alternate address: This field must be empty for normal
operation. When retrofitting new equipment into an existing
network, entering the old factory MAC address in this field is
required for the network to function properly.
Note: All settings in this dialog box are maintained within the Form
6 control when downloading firmware or scheme files. This
allows for Ethernet-based connections to be preserved when
downloading files from remote locations.
4-6
!
SAFETY
S280-70-21
FOR LIFE
4-7
Form 6 Microprocessor-Based Recloser Control Programming Guide
This dialog box only shows the values of the settings that are
different between the control and the PC. The comma-delim-
ited values represent the setting for each setting group.
4-8
!
SAFETY
S280-70-21
FOR LIFE
! WARNING: Equipment misoperation. Use of Caution: System misoperation. The process of down-
an incompatible or inappropriate file in a con- loading a new scheme or settings will cause this device
trol, relay, recloser, or switch can result in equipment to stop functioning as a protective device for a period of
misoperation leading to equipment damage, severe approximately 8 seconds. Safe operating practices must
personal injury, or death. G140.2 be observed while downloading scheme files or settings.
Failure to comply can result in system misoperation.
!
T299.1
WARNING: Equipment misoperation. Use of
the ProView operating system may result in
the creation of many combinations of settings and
scheme files. Many of these combinations can be
downloaded into any device using the ProView
operating system. Before downloading settings and
scheme files to the equipment, verify they are test-
ed and correct for the location and application.
Downloading settings or scheme files designed for
a different location or application can result in death,
severe personal injury, and equipment damage. G169.0
4-9
Form 6 Microprocessor-Based Recloser Control Programming Guide
Settings
Just as in Form 6 Recloser Control front panel programming,
the SETTINGS menu allows viewing and modification of func-
tion settings. There are additional functions in ProView that
are not available in the LCD displays from the front panel. The
illustration at the left shows the functions available in ProView.
Each function of the SETTINGS menu and detailed instruction
on accessibility and programming are described in this section.
4-10
!
SAFETY
S280-70-21
FOR LIFE
Simplified Setup
The Simplified Setup dialog box provides one summarized
screen to view and modify commonly used settings for the
current protection profile.
Changes made to this screen will also be reflected in the
appropriate drop-down menu for the same setting.
4-11
Form 6 Microprocessor-Based Recloser Control Programming Guide
Operations Parameters
4-12
!
SAFETY
S280-70-21
FOR LIFE
4-13
Form 6 Microprocessor-Based Recloser Control Programming Guide
Minimum Trip
Minimum Trip is the threshold setting for overcurrent protec-
tion. Once the threshold is exceeded, the control begins tim-
ing on the programmable time-current curve.
4-14
!
SAFETY
S280-70-21
FOR LIFE
Ground
Units: Amps
Range: 10 to 1600 A (2000:1 CTRatio)
5 to 800 A (1000:1 CTRatio)
2 to 400 A (500:1 CTRatio)
Accuracy: 5% and 1mA secondary for settings greater than
10mA secondary
Front Panel LCD display designation: TCCGMinTrip
Block <Element> Trip
Block Trip disables the Phase, Ground, or Negative Sequence
tripping functions.
Note: Ground tripping can be blocked from the front operator panel
function key GND TRIP BLOCKED. When the Ground Trip
Blocked feature is enabled, the Sensitive Earth Fault feature is
disabled.
Note: Block settings can also be programmed through the Idea
Workbench.
Overcurrent Alarm and Alarm Time Delay
Overcurrent alarms are active when the user-programmed
alarm threshold and time delay settings have been reached.
Overcurrent alarms automatically reset (without any intentional
time delay) when the condition is below the setting point.
If the user wants an Overcurrent Alarm to be recorded in
the Event Recorder or perform any additional functions, the
alarm must be configured via the Hardware Workbench or the
Communications Workbench.
The alarm will only be recorded as an event-type if the user
configures it as a user-defined SOE event.
Note: Refer to Workbench Outputs Toolbox in the Idea
Workbench section and Sequence of Events in the
Display section of this manual for additional event
recorder information.
The values and ranges of Overcurrent Alarm and Alarm Time
Delay are:
Overcurrent Alarm for Phase and Negative Sequence (3I2)
Units: Amps
Range: 5 to 3200 A
Accuracy: 5% and 1mA secondary for settings greater than
10mA secondary
Overcurrent Alarm for Ground
Units: Amps
Range: 2 to 1600 A
Accuracy: 5% and 1mA secondary for settings greater than
10mA secondary
Alarm Time Delay
Units: seconds
Range: 0 to 3600 seconds
Accuracy: 1% and 10 ms
4-15
Form 6 Microprocessor-Based Recloser Control Programming Guide
IMPORTANT: Verify where you are saving the curve. The curve
must be saved to the same folder the scheme file (.f6s) resides in.
4-16
!
SAFETY
S280-70-21
FOR LIFE
Curve Type
The Curve Type defines the shape of the TCC. There are fifty
unique curves available in the Form 6 recloser control. The
available curve types are:
Kyle Curves 101 through 202.
Constant (1 second definite time) Curves
ANSI Moderately Inverse, Very Inverse, Extremely
Inverse; IEC Inverse, Very Inverse, Extremely Inverse;
and five custom curves (User 1 through 5).
Note: All curves, including User curves, can be viewed and modi-
fied using the TCC Editor II.
Below are the available curve types and their associated
index identification within the recloser scheme settings file.
F6 Curve* F3 Cross F6 Curve* Name F3 Cross Refer to Section 2:Front
Name Reference Index Reference Index Panel Operation,
Kyle 101 A 0 Kyle 151 18 31 Overcurrent Protection
Kyle 102 1 1 Kyle 152 7 32 Settings - Curve
Selection for TCC1 and
Kyle 103 17 2 Kyle 161 T 33
TCC2 section for Inverse
Kyle 104 N 3 Kyle 162 K-Phase 34 Time Characteristics.
Kyle 105 R 4 Kyle 163 F 35
Kyle 106 4 5 Kyle 164 J 36
Kyle 107 L 6 Kyle 165 K-Ground 37
Kyle 111 8*, 8+ 7 IEC Inv (200) n/a 38
Kyle 112 15 8 IEC VI (201) n/a 39
Kyle 113 8 9 IEC EI (202) n/a 40
Kyle 114 5 10 Constant n/a 41
Kyle 115 P 11 ANSI MI n/a 42
Kyle 116 D 12 ANSI VI n/a 43
Kyle 117 B 13 ANSI EI n/a 44
* These curve names
Kyle 118 M 14 USER1 n/a 45 also apply to the fol-
Kyle 119 14 15 USER2 n/a 46 lowing Cooper Power
Kyle 120 Y 16 USER3 n/a 47 Systems recloser con-
Kyle 121 G 17 USER4 n/a 48 trols: Form 4A, Form
4C, and Form 5.
Kyle 122 H 18 USER5 n/a 49
Kyle 131 9 19
Time Multiplier
Kyle 132 E 20
This setting defines the Time Multiplier and the TCC Multiplier
Kyle 133 C 21
Enable to modify the position of the original TCC in time-cur-
Kyle 134 Z 22 rent space. If the TCC Multiplier is Enabled, the trip time of
Kyle 135 2 23 a given TCC at a measured current is shifted in time by the
Kyle 136 6 24 specified multiple.
Kyle 137 V 25 For example, if a curve has an operate time of 40 ms and a
Kyle 138 W 26 multiplier of 2, the "modified" operate time would be 80 ms.
Kyle 139 16 27 40 ms x 2 = 80 ms
Kyle 140 3 28 Similarly, if the same curve has an operate time of 5 seconds,
Kyle 141 11 29 the "modified" operate time would be 10 seconds.
Kyle 142 13 30 5 seconds x 2 = 10 seconds
4-17
Form 6 Microprocessor-Based Recloser Control Programming Guide
Time Adder
The adder settings define a Time Adder and a TCC Add
Enable to modify the position of the original TCC in time-cur-
rent space. If the Time Adder is enabled, the trip time of a
given TCC at a measured current is shifted in time by the
These diagrams show specified additional time. In contrast to the time multiplier, the
modified TCCs with Time Adder adds a constant time to the curve, regardless of
and without the effects of the unmodified curve.
high current trip. For example, if a curve has an operate time of 40 ms and a
1 second time adder, the modified operate time is 1.040 sec-
They also show the onds.
precedence when more Minimum Response Time
than one modifier is used. The Minimum Response Time (MRT) settings define a
Minimum Response Time and a TCCMRTA Enable to modify
the shape of the original TCC in time-current space. If the
TCC Modifiers without High Current Trip
1) Basic TCC
MRT is Enabled, the minimum trip time of a given TCC is
2) Minimum Response Time (10 cycles) defined to be no less than the value of MRT.
3) 2x Multiplier
4) 0.08 sec. Time Adder (10 cycles)
High Current Trip
High Current Trip (HCT) settings define a HCT Minimum Trip
Multiplier, a HCT Time Delay, and a HCT Enable to modify
the shape of the original TCC in time-current space. If HCT is
Enabled, the shape of the TCC at currents beyond the HCT
Minimum Trip Multiplier setting will be definite time, as defined
1
by the HCT Time Delay.
4
2 Reset Coefficient
3
The Reset Coefficient settings define the rate at which the
control resets the TCC if a non-instantaneous reset is speci-
fied. The reset coefficient is the equivalent of the mechanical
reset of induction disk controls. The TCC reset time is deter-
mined by the following equation:
2
TCC Modifiers With High Current Trip TCC Reset Time = (TM*RCC)/(M -1) where TM equals
1) Basic TCC
2) Minimum Response Time (10 cycles) the TCC Time Multiplier setting from the TCC Modifiers,
3) High Current Trip Time Delay
Response Time (4 Cycles)
RCC is the reset coefficient setting, and M is the ratio
4) Min Trip Mult 10 of the applied current to the minimum trip setting of the
5) 2x Multiplier
6) 0.08 Second Time Adder TCC type.
(4.8 cycles) Does not add to High Current
Time Delay Note: When Disk Reset is used, the reclose interval must be long
enough to allow the disk to fully reset to avoid faster than
expected tripping times encountered on successive shots.
5
Fast Trip Block
Fast Trip Block appears only in the TCC1 operation parame-
ters dialog box. The function of Fast Trip Block is to eliminate
6
1 the fast TCC1 tripping curve.
4 TCC Editor
TCC Editor is activated from the TCC1 and TCC2 dialog
2
boxes, enabling you to read or write to the TCC Editor linked
3
to the associated curve shape modifier. See Using TCC
Editor II section of this chapter.
Note: Modifications to the operation parameters can be pre-defined
in and viewed by the TCC Editor and imported using the con-
trols in the TCC1 and TCC2 dialog boxes.
4-18
!
SAFETY
S280-70-21
FOR LIFE
4-19
Form 6 Microprocessor-Based Recloser Control Programming Guide
Copying Profiles
Entire profiles can be copied from one to another:
1. Click on the profile you want to copy.
2. Select COPY from the EDIT drop-down menu.
3. Click on the profile you want to copy to.
4. Select PASTE from the EDIT drop down menu.
Tree Icons
These icons define TCC status:
white icon
yellow icon
green icon
yellow icon
blue icon
red icon
4-20
!
SAFETY
S280-70-21
FOR LIFE
The Insert TCC dialog box appears from the EDIT menu of
the Form 6 tree.
Note: If you have selected a TCC node that does not have a TCC
assigned to it, the Name box in the Library Source section
will show three question marks (???) when the Insert TCC
dialog box appears.
4. Click CHANGE to access the applicable Time-Current
Curve library.
The program allows you to select TCCs from the Kyle library
of curves or the ANSI and IEC standard curves.
5. Select the desired curve.
6. Click OK.
The Insert TCC dialog box appears with the name of the
TCC in the Library Source section of the box.
At this point, you can elect to modify or use the selected TCC
with its current parameters.
4-21
Form 6 Microprocessor-Based Recloser Control Programming Guide
TCC Selection
There are two ways to select an individual Form 6 control
TCC.
One way is to expand the tree nodes and click on a TCC icon
as shown at the left.
Phase 1 represents TCC1 for Phase (fast curve).
Phase 2 represents TCC2 for Phase (slow curve).
Ground 1 represents TCC1 for Ground.
Ground 2 represents TCC2 for Ground.
4-22
!
SAFETY
S280-70-21
FOR LIFE
Modifying Curves
Once a TCC is assigned to a protection profile element
(Phase, Ground, Negative Sequence, Cold Load Pickup), you
will be able to modify that TCC.
To select a TCC for modification proceed as follows:
1. Left-click on the applicable TCC node.
2. Right-click on the node.
3. Select and left-click on MODIFY.
Note: The selected curve turns red on the graph.
Shortcut: You can modify a selected curve from the TCC Editor
EDIT menu.
4-23
Form 6 Microprocessor-Based Recloser Control Programming Guide
The General curve properties page of the dialog box has the
following information:
Displays Frequency Class of the curve
Displays if the curve is a Maximum Response Time
curve
Indicates if the curve is from the Kyle Library of curves
Indicates if the curve has been modified
4-24
!
SAFETY
S280-70-21
FOR LIFE
TCC Report
The TCC Report displays all the modifications made to the
TCCs in each protection profile group. The report provides
the following information:
The exact location of the root curve grouping (i.e.,
Curve1)
The date the report was generated
How the report was generated
4-25
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-26
!
SAFETY
S280-70-21
FOR LIFE
4-27
Form 6 Microprocessor-Based Recloser Control Programming Guide
Reclose
When SEQUENCE COORDINATION is enabled, the Form 6 recloser control sequences for a
fault up to the maximum operations programmed on sequence coordination.
4-28
!
SAFETY
S280-70-21
FOR LIFE
Open Intervals
Reclose (Open) interval settings define the time the recloser
is open following a trip operation, prior to issuing a reclose
command to the recloser.
Open Interval settings and allowable setting limits are listed
below.
Phase/Negative Sequence Reclose (Open) Interval Time
Units: Seconds
Range: 1st Open Interval 0.3 to 1000
2nd Open Interval 1.8 to 1000
3rd Open Interval 1.8 to 1000
Accuracy: 1% and 30 ms
Front Panel LCD display designation:
PQOpenInt#1, PQOpenInt#2, PQOpenInt#3
Ground Reclose (Open) Interval Time
Units: Seconds
Range: 1st Open Interval 0.3 to 1000
2nd Open Interval 1.8 to 1000
3rd Open Interval 1.8 to 1000
Accuracy: 1% and 30 ms
Front Panel LCD display designation:
GndOpenInt#1, GndOpenInt#2, GndOpenInt#3
Reset Time
Reset Time is the intentional time delay introduced by the
control after a successful reclose, before the control resets
the sequence position counter to zero. Reset after successful
reclose occurs when the recloser is closed and no overcur-
rent is detected.
Reset Time
Units: Seconds
Range: 3 to 1800
Accuracy: 1% and 10 ms
Front Panel LCD display designation: ResetTime
Reset Targets
If RESET TARGETS box is checked, the front panel LED tar-
gets reset automatically after expiration of Reset Targets Time
Delay.
Reset Targets Time
Units: Seconds
Range: 2 to 3600
Accuracy: 1% and 10 ms
Sequence Coordination
If ALLOW SEQUENCE COORDINATION BOX is checked, the
Form 6 recloser control sequences for a fault up to the maxi-
mum operations programmed on sequence coordination.
Sequence Coordination Operations
Note: For an operating sequence of 2 fast and
Units: none
2 delayed operations, the Sequence
Range: 1 to 3
Coordination Operations should be set to 2.
No LCD display designation
4-29
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-30
!
SAFETY
S280-70-21
FOR LIFE
Operations Sequence
The Operation Sequence lets you program these settings:
Number of Trip Operations-to-Lockout
Sequence of Overcurrent Trip Operations for Phase/
Negative Sequence, and Ground
Operations-to-Lockout
Operations-to-Lockout defines the maximum number of trip
operations in a sequence before the control opens and locks
out. The count includes phase, ground, and negative trips as
well as sequence coordination operations.
Operation Sequence
(Phase/Negative Sequence and Ground)
Operations Sequence settings for Phase/Negative Sequence
define the order in which phase and negative sequence
curves designated as TCC1 and TCC2 will trip.
Operations Sequence settings for Ground define the order in
which Ground curves designated as TCC1 and TCC2 will trip.
4-31
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-32
!
SAFETY
S280-70-21
FOR LIFE
4-33
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-34
!
SAFETY
S280-70-21
FOR LIFE
Select CHANGE SETTING GROUP to activate the SETTING GROUP SELECTION box.
After making changes, always click OK before clicking CHANGE SETTING GROUP. Otherwise,
the change will not be registered.
4-35
Form 6 Microprocessor-Based Recloser Control Programming Guide
30 1800
20 1200
133
10 600
8 480
6 360
5 300
4 240
3 180
2 120
.8 48
.6 36
.5 30
.4 24
.3 18
High-Current
.2 Lockout Level 12
0.1 6.0
.08 4.8
.06 3.6
.05 3.0
.04 2.4
.03 1.8
.02 1.2
Nor mal Sequence Modified Sequence
To Lockout To Lockout
.01 0.6
50000
10000
30000
40000
20000
1000
2000
3000
5000
6000
8000
4000
500
600
100
200
300
400
800
50
80
60
4-36
!
SAFETY
S280-70-21
FOR LIFE
Using the High Current Trip and High Current Lockout Features
In certain situations the high current trip and high current
lockout features can be used to reduce transformer through-
faults. These features can also be utilized together to provide
overall feeder coordination tailored to provide overcurrent
protection characteristics suited for individual sections of a
feeder.
The Example Feeder shown below can explain the benefits
of using the high current trip and high current lockout fea-
tures.
7000
4500 3800
RE1 RE2
7000
4500 3800
RE1 RE2
4-37
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-38
!
SAFETY
S280-70-21
FOR LIFE
7000
4500 3800
RE1 RE2
The actual settings for the high current trip and high current
lockout will be dependent on the maximum available fault cur-
rent at various locations along the feeder.
High Current Trip
The downline fuse (the fuse just upline of recloser RE2) is at
a location where the available fault current is 3800 amps,
the high current trip on the RE1 recloser control must be set
higher than this level. 4.75 (3800 A 800 A) is the minimum
setting for the high current trip, 5.0 is selected. For fault cur-
rents above 4000 amps (5.0 x 800 A) recloser RE1 will oper-
ate instantaneously with four operations to lockout. The fuse
should operate properly since it is outside the high current trip
zone.
High Current Lockout
The downline sectionalizer (S1) is at a location where the
available fault current is 4500 amps, the high current lockout
on the RE1 recloser control must be set higher than this level.
4800 amps is selected to allow a margin and keep faults of
4500 amps or lower from activating the high current lockout.
For fault currents above 4800 amps, recloser RE1 will oper-
ate instantaneously and lockout immediately after one or two
operations. The sectionalizer should operate properly since it
is outside the high current lockout zone.
4-39
Form 6 Microprocessor-Based Recloser Control Programming Guide
Select CHANGE
SETTING GROUP to
activate the SETTING
GROUP SELECTION
box.
Note: An error
message
appears if the
setting entered
is outside the
value limits of
the setting.
There must be a TCC loaded (in each profile) in the parameter you want to import prior
to Importing Curve Parameters from TCCEditor.
For instance, if you want to import a Phase Operation Number 1 custom user curve,
a Phase 1 curve must be loaded in Normal, Alternate 1, Alternate 2, and Alternate 3
profiles.
4-40
!
SAFETY
S280-70-21
FOR LIFE
Curve Type
Highlight current setting and type in new setting. The CLPU curve defines the shape of the TCC. There are fifty
unique curves available in the Form 6 recloser control. The
available curve types are:
Kyle Curves 101 through 202
Constant (1 second definite time) Curves
ANSI Moderately Inverse, Very Inverse, Extremely
Inverse; IEC Inverse, Very Inverse, Extremely Inverse;
and five custom curves (User 1 through 5)
Note: All curves, including User curves, can be viewed and modi-
fied using TCC Editor II.
Note: The Form 6 recloser control is a three-phase device; all three
phases trip on the settings programmed.
Front Panel LCD display designation:
CLPUPCurve, CLPUQCurve, CLPUGCurve
4-41
Form 6 Microprocessor-Based Recloser Control Programming Guide
Note: When Hot Line Tag and CLPU are both active the Form 6
control reverts back to the original minimum pick-up values
(i.e. disables CLPU settings).
CLPU Phase/Negative Sequence
Units: Amps
Range: 20 to 3200 (2000:1 CTRatio)
10 to 1600 (1000:1 CTRatio)
5 to 800 (500:1 CTRatio)
Accuracy: 5% and 1 mA secondary for settings greater
than 10mA secondary
Front Panel LCD display designation: CLPUPMinTrip,
CLPUQMinTrip
CLPU Ground
Units: Amps
Range: 10 to 1600 (2000:1 CTRatio)
5 to 800 (1000:1 CTRatio)
2 to 400 (500:1 CTRatio)
Accuracy: 5% and 1 mA secondary for settings greater
than 10mA secondary
Front Panel LCD display designation: CLPUGMinTrip
4-42
!
SAFETY
S280-70-21
FOR LIFE
CLPU Multiplier
4-43
Form 6 Microprocessor-Based Recloser Control Programming Guide
CLPU Adder
Highlight current
setting and type in Check boxes to activate
applicable setting. applicable setting.
4-44
!
SAFETY
S280-70-21
FOR LIFE
The CLPU High Current Trip (HCT) settings define a cold load
pickup high current trip setting, a time delay, and an enable
setting to modify the shape of the selected CLPU TCC in
time-current space. If Cold Load Pickup HCT is enabled,
the shape of the TCC at currents beyond the HCT setting is
definite time as defined by the CLPU HCT time delay.
CLPU HCT (Phase, Neg. Sequence, and Ground)
Units: Multiples of Minimum Trip
Range: 1 to 32
Accuracy: 5% and 1mA secondary for settings greater
than 10mA secondary
Front Panel LCD display designation: CLPUPHCT
CLPUQHCT
CLPUGHCT
CLPU HCT Time Delay (Phase, Neg. Sequence, and Ground)
Units: seconds
Range: 0.01 to 0.15
Accuracy: 1% and 10 ms
Front Panel LCD display designation: CLPUPHCTDly
CLPUQHCTDly
CLPUGHCTDly
4-45
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-46
!
SAFETY
S280-70-21
FOR LIFE
User Curves
User Curves are user-defined, custom curves created in TCC
Editor II for the Form 6 recloser control. The User Curves dia-
log box enables user curve data to be read from the respec-
tive setting files (User1 settings.txt through User5 settings.txt).
These files can be viewed with any text editor. Setting files are
located: Program Files/Cooper/ProviewXX/Form6.
There must be a TCC loaded (in each profile) in the parameter you want to import
prior to Importing Curve Parameters from TCCEditor.
For instance, if you want to import a Phase Operation Number 1 custom user
curve, a Phase 1 curve must be loaded in Normal, Alternate 1, Alternate 2, and
Alternate 3 profiles.
4-47
Form 6 Microprocessor-Based Recloser Control Programming Guide
Select the number of trip operations (1, 2, 3, or 4). Time Length of Reclose Interval
CLPU Control
Check box to de-activate Cold Load Pickup. Set Cold Load Pickup Activation time.
Set the Cold Load Pickup activation time or the CLPU Block
feature.
CLPU Activation Time
Units: Seconds
Range: 0 to 3600
Accuracy: 1% and 10 ms
Front Panel LCD display designation: CLPUActTime
CLPU Block
Front Panel LCD display designation: CLPUBlock
Range: Yes or No
Note: When Hot Line Tag and CLPU are both active the Form 6
control reverts back to the original minimum pick-up values
(i.e. disables CLPU settings).
4-48
!
SAFETY
S280-70-21
FOR LIFE
Sensitive Earth
The Sensitive Earth Fault (SEF) feature is used on 3-wire sys-
tems that require lower, independent minimum trip values
than normal ground sensing.
Sensitive Earth Fault (SEF) allows the Form 6 recloser control
to detect and authorize the recloser to trip after a selectable,
definite time for ground currents above SEF minimum trip
levels. Sensitive Earth Fault has programmable lockout set-
tings and reclose intervals. Like all the features in the Settings
menu, Sensitive Earth Fault is independently selectable for
each protection profile.
Note: When the Ground Trip Blocked feature is Enabled, the
Sensitive Earth Fault feature is Disabled.
Sensitive Earth Fault feature requires four settings once it is
enabled:
SEF Minimum Trip
SEF Time Delay
SEF Reclose Interval
SEF Operations-to-Lockout
4-49
Form 6 Microprocessor-Based Recloser Control Programming Guide
SEF Operations-to-Lockout
Operations-to-Lockout defines the maximum number of trip
operations in a sequence before the control opens and locks
out. The count includes phase, ground, and negative trip
operations.
SEF Operations to Lockout
Range: 1 to 4
Front Panel LCD display designation: SEFNumOps
4-50
!
SAFETY
S280-70-21
FOR LIFE
4-51
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-52
!
SAFETY
S280-70-21
FOR LIFE
USEF Operations-to-Lockout
Operations-to-Lockout defines the maximum number of trip
operations in a sequence before the control opens and locks
out.
USEF Operations to Lockout
Range: 1 to 4
Front Panel LCD display designation: USEFNumOps
USEF Supervision
The USEF directional torque feature provides accurate direc-
tional supervision for faults..
Note: Current measuring functions are only supervised when
DIRECTION FORWARD or DIRECTION REVERSE are
enabled.
4-53
Form 6 Microprocessor-Based Recloser Control Programming Guide
Low Set
Low Set Overcurrent Protection is for programming and
enabling settings associated with the low-set definite-time
overcurrent. A separate pickup and time delay threshold is
provided for phase, negative sequence, and ground.
Pickup
Pickup defines the setting at which the definite time activates.
IMPORTANT: Always verify the pickup values
Phase and Negative Sequence Pickup
are appropriate for the CTRatio.
Units: Amps
Range: 20 to 3200 (2000:1 CTRatio)
10 to 1600 (1000:1 CTRatio)
5 to 800 (500:1 CTRatio)
Accuracy: 5% and 1mA secondary for settings greater
than 10mA secondary
Ground Pickup
Units: Amps
Range: 10 to 1600 (2000:1 CTRatio)
5 to 800 (1000:1 CTRatio)
2 to 400 (500:1 CTRatio)
Accuracy: 5% and 1mA secondary for settings greater
than 10mA secondary
Time Delay
Phase, Negative Sequence, and Ground Time Delay
Units: seconds
Range: 0 to 100
Accuracy: 1% and 10 ms
4-54
!
SAFETY
S280-70-21
FOR LIFE
Voltage
The Voltage dialog box enables you to program the Form 6
recloser control under and overvoltage protection settings for
alarm and trip on system excursions from nominal.
Under and overvoltage settings are used for loss of voltage
detection and/or overvoltage applications.
Undervoltage can be enabled for single-phase, three-
phase, or single-phase with three-phase inhibit mode.
Overvoltage, when enabled, will automatically assert for
both single-phase and three-phase detection.
The overvoltage and undervoltage alarms must be configured
through the Workbench Inputs Alarms toolbox.
Note: Non-latched system alarms will not illuminate the Alarm LED
on the front panel. Non-latched system alarms must be
programmed via the Idea Workbench to associate with a
front panel Indicator LED.
Select CHANGE SETTING GROUP to activate the SETTING GROUP SELECTION box.
After making changes, always click OK before clicking CHANGE SETTING GROUP
Otherwise, the change will not be registered.
4-55
Form 6 Microprocessor-Based Recloser Control Programming Guide
Undervoltage Settings
The Undervoltage settings define the single and three-phase
tripping thresholds and delay times, as well as the alarm
pickup and time delay.
Checkboxes are provided to allow the user to enable single-
and three-phase undervoltage tripping. When single-phase
UV tripping is enabled the user can select 3-Phase Inhibit.
Checking "Enable 1P UV Trips" will allow tripping based on
the phase settings. Tripping will occur regardless if any one
phase, any combination of two phases, or all three phases
are involved.
Checking both "Enable 1P UV Trips" and "with 3P Inhibit" or
checking only "with 3P Inhibit" and properly utilizing the "1P
UV Trips Enable" Workbench output will allow tripping based
on the phase settings. Tripping will occur regardless if any
one phase or any combination of two phases are involved.
Tripping will not occur if all three phases are involved.
Note: Checking only "with 3P Inhibit" will have no effect on tripping
unless single-phase undervoltage trips is enabled.
Checking "Enable 3P UV Trips" will allow tripping based on
the three-phase settings. Tripping will only occur if all three
phases are involved.
Checking both "Enable 1P UV Trips" (with or without checking
"with 3P Inhibit") and "Enable 3P UV Trips" will allow tripping
based on both the phase and three-phase settings.
Single-Phase Undervoltage Pickup
Note: The Single-Phase Undervoltage Pickup set-
ting controls the voltage indication for the Units: kV (Primary)
front panel voltage present target LEDs. Range: 0 to 200
For a Form 6-LS control, the front panel Accuracy: 1% and 1 V secondary
voltage present LEDs are controlled by Front Panel LCD display designation: UVolt1PPU
the Voltage Controls settings in the Loop
Scheme Settings dialog box. A, B, and C Single-Phase Undervoltage Time Delay
phase is Source I for the Form 6-LS control. Units: Seconds
Refer to Form 6 Loop Scheme Control in Range: 0 to 100
Section 5 for additional information.
Accuracy: 1% and 10 ms
Front Panel LCD display designation: UVolt1PTime
Three-Phase Undervoltage Pickup
Units: kV (Primary)
Range: 0 to 200
Accuracy: 1% and 1 V secondary
Front Panel LCD display designation: UVolt3PPU
Three-Phase Undervoltage Time Delay
Units: Seconds
Range: 0 to 100
Accuracy: 1% and 10 ms
Front Panel LCD display designation: UVolt3PTime
4-56
!
SAFETY
S280-70-21
FOR LIFE
Overvoltage Settings
The Overvoltage settings define the single and three-phase
tripping thresholds and delay times, as well as the alarm
pickup and time delay.
Single-Phase Overvoltage Pickup
Units: kV (Primary)
Range: 0 to 200
Accuracy: 1% and 1 V secondary
Front Panel LCD display designation: OVolt1PPU
Single-Phase Overvoltage Time Delay
Units: Seconds
Range: 0 to 100
Accuracy: 1% and 10 ms
Front Panel LCD display designation: OVolt1PTime
Three-Phase Overvoltage Pickup
Units: kV (Primary)
Range: 0 to 200
Accuracy: 1% and 1 V secondary
Front Panel LCD display designation: OVolt3PPU
Three-Phase Overvoltage Time Delay
Units: Seconds
Range: 0 to 100
Accuracy: 1% and 10 ms
Front Panel LCD display designation: OVolt3PTime
Overvoltage Alarm Pickup
Units: kV (Primary)
Range: 0 to 200
Accuracy: 1% and 1 V secondary
Overvoltage Alarm Time Delay
Units: Seconds
Range: 0 to 3600
Accuracy: 1% and 10 ms
4-57
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-58
!
SAFETY
S280-70-21
FOR LIFE
Frequency
Frequency provides over and underfrequency protection as
well as a frequency restoration feature to allow the recloser to
automatically close when frequency returns within configured
settings for a user-settable time.
Any phase can be used for Frequency measurement and
protection as long as that phase is enabled in the Configure:
System Configuration dialog box.
4-59
Form 6 Microprocessor-Based Recloser Control Programming Guide
Under/Overfrequency Pickup
The Stage 1 and Stage 2 underfrequency and overfrequency
IMPORTANT: Always verify the pickup and alarm pickup settings define the frequency level at which the pro-
values are appropriate for the system frequency. tection becomes active. For underfrequency protection to
become active, the frequency level must be less than the
pickup setting. For overfrequency protection to become
active, the frequency level must be greater than the pickup
setting.
The Frequency dialog box enables you to set two overfre-
quency and two underfrequency pickup settings (Stage 1 and
Stage 2). You can also set a single overfrequency alarm and a
single underfrequency alarm.
Stage 1 and 2 Alarm and Over/Underfrequency
Units: Hertz (Hz)
Range: 46 to 54 (50 Hz)
56 to 64 (60 Hz)
Accuracy: 0.005 Hz
Front Panel LCD display designation: UFreq1PU,
UFreq2PU,
OFreq1PU
OFreq2PU
Time Delays
Each under and overfrequency setting has a settable time
delay to coordinate system frequency functionality.
Stage 1 and 2 Time Delays
Units: seconds
Range: 0 to 100
Accuracy: 1% and 10 ms
Front Panel LCD Display Designation: UFreq1Time
UFreq2Time
OFreq1Time
OFreq2Time
Under and Overfrequency Time Delay Alarm
Units: seconds
Range: 0 to 3600
Accuracy: 1% and 10 ms
Note: The over and underfrequency alarms have a factory-defined
50 ms delay programmed into the feature to minimize nui-
sance alarming.
Underfrequency Restoration
Underfrequency Restoration settings allow the user to specify
if and when the feeder will automatically restore following an
underfrequency trip event. As long as the frequency remains
above the restoration frequency setting, the restoration logic
runs the Schedule Timer. The Schedule Timer is an accumu-
lated timer to provide coordination with multiple devices. This
timer dictates the restoration schedule for the feeder in rela-
tion to other feeders on the system.
4-60
!
SAFETY
S280-70-21
FOR LIFE
4-61
Form 6 Microprocessor-Based Recloser Control Programming Guide
Restoration Frequency
Units: Hertz (Hz)
Range: 46 to 54 (50 Hz)
56 to 64 (60 Hz)
Accuracy: 0.005 Hz
Front Panel LCD display designation: Freq:810R:PU
Restoration Abort Time
Units: seconds
Range: 0.1 to 3600
Accuracy: 1% and 10 ms
Front Panel LCD display designation: Freq:62Abort
Schedule Time
Units: seconds
Range: 1.0 to 3600
Accuracy: 1% and 10 ms
Front Panel LCD display designation: Freq:62Sched
Transient Time
Units: seconds
Transient Timer = .3 Seconds Schedule Timer = 15 Seconds Abort Timer = 30 Seconds
Range: 0.1 to 3600
30 30
5
Transient Timer = .3 Seconds Schedule Timer = 15 Seconds Abort Timer = 30 Seconds Accuracy: 1%5and 10 ms
30
25 30 25
.3 25
5
25
5
Front Panel LCD display designation: Freq:62Trans
.3 20 20
20 20
15 10
15 15 10 10 15 10
59.3
TIME
52A: 1
1
0 0
Stage 1 Pickup = 59.6
Stage 1Time Delay = 5 seconds
This is only an example of the Underfrequency Restoration Scheduling functionality. Actual
Stage 2 Pickup = 59.3
pick-up and time values will vary based on system requirements.
Stage 2 Time Delay = 0.5 seconds
Restoration Frequency = 59.9
4-62
!
SAFETY
S280-70-21
FOR LIFE
Directional
The Directional Supervision feature maintains system coordi-
nation from either direction (forward or reverse), as well as cir-
cuit reconfiguration for each protection profile. The Directional
feature applies to phase, ground, and negative sequence pro-
tection.
The Form 6 recloser control contains two directional func-
tions: a positive sequence function to provide directional
measurement for balanced three-phase faults, and a negative
sequence function to provide directional measurement for all
unbalanced faults (phase-phase, phase-phase-ground, and
ground).
4-63
Form 6 Microprocessor-Based Recloser Control Programming Guide
Directional Supervision
Note: Current measuring functions for Phase, Ground, and Negative
Sequence are only supervised when Direction Forward
or Direction Reverse is enabled.
Ground/Sensitive Earth
Directional Supervision
Ground/Sensitive Earth directional torque feature pro-
vides accurate directional supervision for unbalanced (zero
sequence) faults.
Negative Sequence
Directional Supervision
Negative Sequence directional torque feature provides
accurate directional supervision for unbalanced (negative
sequence) faults.
4-64
!
SAFETY
S280-70-21
FOR LIFE
Sync Check
The Form 6 recloser control contains capabilities to sync
check based on source and line-side PTs. The PTs are
assumed to be accurate and phase and magnitude supply
the control with a true sinusoidal signal. Sync Check is a fre-
quency measuring anticipatory close feature, with accommo-
dation for static angles.
Review sync check parameters for the application.
The sync check system is a permissive system used to
qualify any close signal to the mechanism, when the system
is enabled via the sync check settings. The sync check has
the ability to close for any combination of dead/live bus/line
condition and to perform anticipatory closing for a live bus/
live line condition by calculating the slip and leading the close
based on the mechanism closing delay.
The system slip is measured by comparing the sync PT (Vs)
(line) to the selected phase of the three phase BUS PTs. The
slip is then converted to an angular velocity, measured in
degrees/second. The mechanism operating delay setting is
utilized to calculate the lead angle or the angle prior to top
dead center (TDC) at which the close will be permitted.
Select CHANGE SETTING GROUP to activate the SETTING GROUP SELECTION box.
After making changes, always click OK before clicking CHANGE SETTING GROUP. Otherwise, the change will not be registered.
4-65
Form 6 Microprocessor-Based Recloser Control Programming Guide
Close Conditions
Close Conditions settings define the voltage conditions allow-
able on the source (bus) and load (line) side of the recloser for
a close to occur.
For example, by enabling DEAD LINE/HOT BUS CLOSING,
the recloser allows a close when the source side of the
mechanism is live and the load side is dead. If HOT LINE/
HOT BUS is enabled (and Sync Check) is enabled, the pro-
grammed synchronizing parameters are activated.
4-66
!
SAFETY
S280-70-21
FOR LIFE
Dead Threshold
Dead Threshold is the voltage used to compare to the line
and bus voltages to determine if the voltage should be con-
sidered dead. If the measured voltage is less than the Dead
Threshold, the line/bus is dead.
Units: Volts
Range: 0 to 200000
Accuracy: 1% and 1 V secondary
Live Threshold
Live Threshold is the voltage used to compare to the line and
bus voltages to determine if the voltage should be considered
live. If the measured v oltage is greater than the live thresh-
old, the line/bus is live.
Units: Volts
Range: 0 to 200000
Accuracy: 1% and 1 V secondary
Upper Voltage Limit
Upper Voltage Limit defines the upper voltage closing limit.
Units: Volts
Range: 0 to 200000
Accuracy: 1% and 1 V secondary
Lower Voltage Limit
Lower Voltage Limit defines the lower voltage closing limit.
Units: Volts
Range: 0 to 200000
Accuracy: 1% and 1 V secondary
Upper Frequency Limit
IMPORTANT: Always verify the frequency closing limit Upper Frequency defines the upper frequency closing limit.
values are appropriate for the system frequency.
Units: Hertz
Range: 56 to 64 (60 Hz)
46 to 54 (50 Hz)
Accuracy: 0.005 Hz
Lower Frequency Limit
Lower Frequency defines the lower frequency closing limit
Units: Hertz
Range: 56 to 64 (60 Hz)
46 to 54 (50 Hz)
Accuracy: 0.005 Hz
Fail to Close Timer
The Fail to Close Timer defines the length of time a sync close is
maintained. After the expiration of the Fail to Close Timer, the close
deactivates, and an alarm is activated.
Units: Seconds
Range: 0 to 3600
Accuracy: 1% and 10 ms
4-67
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-68
!
SAFETY
S280-70-21
FOR LIFE
These green 0 alarm status indicators will Go Online to view SCF counters, rates, and alarms.
display as a red 1 if an SCF alarm is present.
4-69
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-70
!
SAFETY
S280-70-21
FOR LIFE
Metering
The Metering Settings dialog box enables the user to pro-
gram Demand Metering, Alarm Data, and Power Factor
Setup.
The metering module of the control calculates and maintains
the power-related settings for the demand integration, alarm
thresholds, and power factor alarms. All metering informa-
tion is programmed from the ProView interface software.
Information is viewed from the Form 6 recloser control front
panel LCD display.
Set the time interval over which the peak demand current is calculated.
4-71
Form 6 Microprocessor-Based Recloser Control Programming Guide
Demand Metering
Demand-metered values are programmed for a specific for-
ward or reverse metering direction.
The Demand Interval setting defines the time interval over
which the demand value is calculated.
Demand Interval
Units: Minutes
Range: 1 to 60
Accuracy: 1% and 10 ms
The Demand Alarm Threshold settings define the measured
demand values. If any value limit is exceeded, the respective
demand alarm activates.
Phase Current Threshold
Units: Primary Amps
Range: 10 to 2000
Accuracy: 1%
Single-Phase Real Power (kW-1P) Threshold
Units: kW
Range: 10 to 15000
Accuracy: 1%
Single-Phase Reactive Power (kVAr - 1P) Threshold
Units: kVAr
Range: 10 to 15000
Accuracy: 1%
Three-Phase Real Power (kW - 3P) Threshold
Units: kW
Range: 10 to 15000
Accuracy: 1%
Three-Phase Reactive Power (kVAr - 3P) Threshold
Units: kVAr
Range: 10 to 15000
Accuracy: 1%
Power Factor Alarm Threshold
Units: per unit
Range: 0 to 1
Accuracy: 1%
Power Factor Alarm Time Delay
Units: seconds
Range: 0 to 3600
Accuracy: 1% and 10 ms
4-72
!
SAFETY
S280-70-21
FOR LIFE
Presets
Counter Presets are the operation counter and trip counter
settings preset on a per-phase basis. Counters include:
Ground and A, B, C Phase Targets
Sensitive Earth Fault (SEF) Target
Recloser Interrupting % Duty Cycle Used
Upon setting the counters or duty cycle information, clicking
on the Preset button will immediately download the values to
the control (provided the PC is connected to the control).
These items are not part of the setting file and are not updat-
ed when a setting file is sent to the control from the PC. This
allows the user to make setting changes independent of the
counters.
4-73
Form 6 Microprocessor-Based Recloser Control Programming Guide
MMIReset Menu
This menu lets the user choose what screen the Form 6 con-
trol front panel will revert to after a defined period of inactivity.
These choices are the same as some of the front panel short-
cut keys.
METERING SETTINGS
RESET OPER
TARGETS COUNTER
F1 F2 F3 F4
+
EVENTS ALARMS
MENU
LAMP TEST CHANGE
ENTER
4-74
!
SAFETY
S280-70-21
FOR LIFE
4-75
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-76
!
SAFETY
S280-70-21
FOR LIFE
Settings File
The Settings File Read/Write dialog box allows the user to
read from a setting file or write the current user settings from
the control into a file.
All user settings can be read from and written to the software
files. The scheme stores these User Settings files with the
name Control_Settings_*.txt. Replace the * with a unique
name for the setting file.
4-77
Form 6 Microprocessor-Based Recloser Control Programming Guide
Settings List
The Settings List screen enables the user to view and print
the Key Settings List for the Form 6 control. This list shows
the following settings for each profile:
Overcurrent Settings
Phase
Ground
Negative Sequence
User Curve
Operations Sequence
Phase/Neg Sequence
Ground
Reclose Intervals
Phase/Neg Sequence
Ground
Cold Load Pickup
Phase
Ground
Negative Sequence
Frequency
Underfrequency
Overfrequency
UF Loadshed Restore
ReclsTime and Control
Reclose Retry
Voltage
Undervoltage
Overvoltage
Sensitive Earth Fault
Ungrounded Sensitive Earth Fault
Directional Control
Low Set
Phase
Ground
Negative Sequence
Sync Check
4-78
!
SAFETY
S280-70-21
FOR LIFE
4-79
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-80
!
SAFETY
S280-70-21
FOR LIFE
4-81
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-82
!
SAFETY
S280-70-21
FOR LIFE
System Setup
This section of the Model Fault
Setup box contains all of the set-
tings necessary to define the sys-
tem impedance characteristics.
Note: All impedances are per unit.
The actual base unit is not
required, just that all quantities
are on the same base.
4-83
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-84
!
SAFETY
S280-70-21
FOR LIFE
Maximum Fault Duration (TD) Maximum fault duration in seconds. This timer starts when the fault initiates. No limit
After it expires, the VTS jumps to the post-fault phasors. This timer resets with
each reclose event.
Fault Clearing Time (TC) Maximum clearing time. Similar to Maximum Fault Duration, except this timer No limit
starts running at the beginning of the entire simulation and continues running
through all reclose events.
Simulation Halt Time (TE) This defines the maximum amount of time the simulation will free-run before No limit
automatically stopping. Counting starts at the beginning of the whole simulation.
Recloser Mechanism The time delay that occurs before the virtual recloser in the VTS trips 0 3600 0 3600 seconds
Trip Delay seconds Trip Delay after the scheme initiates a TRIP command. This time delay
appears in the time it takes for the current to stop flowing and for the simulated
52a contact to change status.
Slip from T1 to TC Change in system frequency that occurs at time T1 (fault). Frequency restores to Delta Hz
original frequency at time TC.
Slip from T1 to TC Rate of change of the system frequency that occurs at time T1. Hz/second
Slip from T1 to TC Rate of acceleration of the rate of change of the system frequency that occurs Hz/sec2
at time T1.
4-85
Form 6 Microprocessor-Based Recloser Control Programming Guide
Simulation Settings
The user can save and/or restore all of the simulation settings
and create a whole library of standard simulations to load and
run as needed.
To save, view or load simulator settings, go to any of the four
options available in the Virtual Test Setup dropdown menu.
4-86
!
SAFETY
S280-70-21
FOR LIFE
4-87
Form 6 Microprocessor-Based Recloser Control Programming Guide
Running a Simulation
After setting up the simulation parameters, select Simulation
from the Manage menu. The Simulation Control Panel toolbar
will appear.
To prepare the PC for the simulation, click INIT to begin initial-
ization. If the scheme is not ready, a progress bar will appear
with the preparation status. When ready, the Simulation
Control Panel toolbar will reappear.
A simulation can now be run.
Note: It is recommended to run the simulation while viewing a
screen displaying oscillography, the Application Diagram, or
the Idea Workbench. Refer to the Display or Application
Diagram sections in this manual for viewing information.
The entire system becomes "live" during event playback just
as if the PC were connected to the Form 6 control in View
Online mode.
Click on STEP. Each click will play into the system one data
point for each voltage and current. The data points represent
simulated output from the controls analog input channels.
Click on FREE-RUN to continuously generate signals until
a PC event record is generated. A PC event can be saved
to disk and reloaded at any time. Once the VTS has been
started and initialized, clicking TRIGGER EVENT will cause a
200-sample event record to be recorded as a PC Event in the
Oscillographic Event Manager.
Note: PC Events triggered by the Virtual Test Set do not trigger an
event within the Form 6 control; however, they can be saved
and recalled as any other event.
4-88
!
SAFETY
S280-70-21
FOR LIFE
Configure
The Configuration Menu allows access to the following
System and Load-side PT Configuration functions.
System Configuration
System Configuration allows the user to program the control
with the settings associated with the general system arrange-
ment and configuration. This dialog box lets you program the
following:
System Configuration (includes Type and Primary
Rating for CT and PT)
System Zero-Sequence Source Impedance
Fault Locator (only available when three voltages
are supplied and all three Connected PT boxes are
checked)
Manual Close Time Delay
Duty Cycle Factor
PT Connection (for BUS or Source-Side-PTs)
Bushing Configuration (for both Source and Load-Side
PTs)
System Rotation
Connected PTs (on Bus or Source-Side)
The PT connection should be consistent with the Load-side
PT connection.
4-89
Form 6 Microprocessor-Based Recloser Control Programming Guide
The Pole
Mounted
Control The System Rotation section
checkbox* allows the user to specify the
must be system rotation
selected for (ABC - phase rotation) or
all Form 6 (ACB - phase rotation).
Pole Mount This data is used when
Recloser calculating the proper inputs
Controls. to the sequence filters, and
This includes affect the negative sequence
both directional and overcurrent
pole and elements.
substation
applications.
4-90
!
SAFETY
S280-70-21
FOR LIFE
Load-side PT Configuration
The Load-side PT Configuration dialog box enables the user
to select the Connected PTs, set the PT Ratio and PT con-
nection (Wye or Delta), and enable or disable phantom phase.
The Load-side PT connection should be consistent with the
Source-side PT connection in the System Configuration dia-
log.
Note: (This note only applies to Form 6 Pole Mount controls under
Serial Number 10,000 and all Form 6 Rack and Yard Mount
controls): Do not select more than one Load-side input.
Doing so will result in a Load-Side PT Error alarm.
4-91
Form 6 Microprocessor-Based Recloser Control Programming Guide
Display
The Display Menu allows access to the following features:
Sequence of Events
Application Diagram
Oscillography
Data Profiler
Factory Nameplate
Sequence of Events
The Form 6 recloser control contains capabilities to perform
Sequence of Events time-stamping for up to 32 event types.
This event recorder includes the date and time of the event
and metering analogs for each event type. Sixteen additional
event types are user-defined through the Idea Workbench.
The Sequence of Events Recorder maintains a minimum of
90 events.
The Sequence of Events screen provides date and time
stamped event data along with the instantaneous voltage
(secondary volts) and current magnitudes for each phase at
the time of the event.
Green signal indicates Note: The displayed A, B, and C phase secondary voltage values
Red signal indicates signal
event is de-asserted are normalized by dividing the corresponding primary voltage
is asserted
(i.e. gnd trip blk off). value by the A:AB PTratio shown on the Configure>System
(i.e. gnd trip blk on).
Configuration screen.
4-92
!
SAFETY
S280-70-21
FOR LIFE
4-93
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-94
!
SAFETY
S280-70-21
FOR LIFE
4-95
Form 6 Microprocessor-Based Recloser Control Programming Guide
Application Diagram
The Application Diagram provides a display of all logic ele-
ments, voltages, currents, watts, and vars of the Form 6
recloser control. This live display of the connected recloser
provides a quick summary of the distribution system and the
active control functions. The application program is also ideal
for testing or for providing a quick system overview via
modem connection.
Confirm Before
Operate Screens
4-96
!
SAFETY
S280-70-21
FOR LIFE
Oscillography
The Display Oscillography feature enables oscillography
events to be played back through the control scheme, even
with altered settings. This feature allows the user to determine
how the Form 6 recloser control would have behaved for the
same fault under different settings.
Save future fault incidences with past fault performance
analysis.
View accurate graphical events to compare actual con-
trol performance against expected results.
Users can view event records using pre-defined oscillographic
views or those from the Sequence of Events recorder. Both
actual event records and those created with the Virtual Test
Set (VTS) can be downloaded and viewed.
Note: A maximum of twelve 8-cycle events can be captured.
4-97
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-98
!
SAFETY
S280-70-21
FOR LIFE
The event will be open and the Cursor Control Panel will
appear.
Digital traces
4-99
Form 6 Microprocessor-Based Recloser Control Programming Guide
Oscillography Replay
Oscillography Replay enables the user to see how the Form 6
recloser control would behave for a open event record if the
settings were different. Use this feature as follows:
4-100
!
SAFETY
S280-70-21
FOR LIFE
Data Profiler
The Data Profiler is used for acquiring metering data for a
specific period of time. The Data Profiler is not automatic; it
must be manually configured. The Data Profiler is capable of
retaining metering data for each phase. The number of data
samples that can be retained is dependent upon the number
of metering forms used and the sample rate interval.
By selecting the fewest and most appropriate metering forms
at a high sample rate, a large amount of metering data can
be acquired to determine the cause of many line and power
quality issues.
1. Select Data Profiler dialog box from the Display menu.
4-101
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-102
!
SAFETY
S280-70-21
FOR LIFE
Name Description
Demand(IA:pri) Demand Current Phase A
Demand(IB:pri) Demand Current Phase B
Demand(IC:pri) Demand Current Phase C
Demand(Ig:pri) Demand Current Ground
Inst. VA (Ph-N:pri) Instantaneous Voltage Phase A to Neutral
Inst. VB (Ph-N:pri) Instantaneous Voltage Phase B to Neutral
Inst. VC (Ph-N:pri) Instantaneous Voltage Phase C to Neutral
PhA-PhB Volts Instantaneous A Phase to B Phase Voltage
PhB-PhC Volts Instantaneous B Phase to C Phase Voltage
PhC-PhA Volts Instantaneous C Phase to A Phase Voltage
IA:THD Metering Current THD Phase A
IB:THD Metering Current THD Phase B
IC:THD Metering Current THD Phase C
IG:THD Metering Current THD Ground
IA:2nd Harm Metering Current 2nd Harmonic Phase A
IA:3rd Harm Metering Current 3rd Harmonic Phase A
IA:4th Harm Metering Current 4th Harmonic Phase A
IA:5th Harm Metering Current 5th Harmonic Phase A
IA:6th Harm Metering Current 6th Harmonic Phase A
IA:7th Harm Metering Current 7th Harmonic Phase A
IA:8th Harm Metering Current 8th Harmonic Phase A
IA:9th Harm Metering Current 9th Harmonic Phase A
IA:10th Harm Metering Current 10th Harmonic Phase A
IA:11th Harm Metering Current 11th Harmonic Phase A
IA:12th Harm Metering Current 12th Harmonic Phase A
IA:13th Harm Metering Current 13th Harmonic Phase A
IA:14th Harm Metering Current 14th Harmonic Phase A
IA:15th Harm Metering Current 15th Harmonic Phase A
IB:2nd Harm Metering Current 2nd Harmonic Phase B
IB:3rd Harm Metering Current 3rd Harmonic Phase B
IB:4th Harm Metering Current 4th Harmonic Phase B
IB:5th Harm Metering Current 5th Harmonic Phase B
IB:6th Harm Metering Current 6th Harmonic Phase B
IB:7th Harm Metering Current 7th Harmonic Phase B
IB:8th Harm Metering Current 8th Harmonic Phase B
IB:9th Harm Metering Current 9th Harmonic Phase B
IB:10th Harm Metering Current 10th Harmonic Phase B
IB:11th Harm Metering Current 11th Harmonic Phase B
IB:12th Harm Metering Current 12th Harmonic Phase B
IB:13th Harm Metering Current 13th Harmonic Phase B
IB:14th Harm Metering Current 14th Harmonic Phase B
IB:15th Harm Metering Current 15th Harmonic Phase B
IC:2nd Harm Metering Current 2nd Harmonic Phase C
IC:3rd Harm Metering Current 3rd Harmonic Phase C
4-103
Form 6 Microprocessor-Based Recloser Control Programming Guide
Name Description
IC:4th Harm Metering Current 4th Harmonic Phase C
IC:5th Harm Metering Current 5th Harmonic Phase C
IC:6th Harm Metering Current 6th Harmonic Phase C
IC:7th Harm Metering Current 7th Harmonic Phase C
IC:8th Harm Metering Current 8th Harmonic Phase C
IC:9th Harm Metering Current 9th Harmonic Phase C
IC:10th Harm Metering Current 10th Harmonic Phase C
IC:11th Harm Metering Current 11th Harmonic Phase C
IC:12th Harm Metering Current 12th Harmonic Phase C
IC:13th Harm Metering Current 13th Harmonic Phase C
IC:14th Harm Metering Current 14th Harmonic Phase C
IC:15th Harm Metering Current 15th Harmonic Phase C
IG:2nd Harm Metering Current 2nd Harmonic Phase G
IG:3rd Harm Metering Current 3rd Harmonic Phase G
IG:4th Harm Metering Current 4th Harmonic Phase G
IG:5th Harm Metering Current 5th Harmonic Phase G
IG:6th Harm Metering Current 6th Harmonic Phase G
IG:7th Harm Metering Current 7th Harmonic Phase G
IG:8th Harm Metering Current 8th Harmonic Phase G
IG:9th Harm Metering Current 9th Harmonic Phase G
IG:10th Harm Metering Current 10th Harmonic Phase G
IG:11th Harm Metering Current 11th Harmonic Phase G
IG:12th Harm Metering Current 12th Harmonic Phase G
IG:13th Harm Metering Current 13th Harmonic Phase G
IG:14th Harm Metering Current 14th Harmonic Phase G
IG:15th Harm Metering Current 15th Harmonic Phase G
VA:THD Metering Voltage THD Phase A
VB:THD Metering Voltage THD Phase B
VC:THD Metering Voltage THD Phase C
VS:THD Metering Voltage THD Synch voltage
VA:2nd Harm Metering Voltage 2nd Harmonic Phase A
VA:3rd Harm Metering Voltage 3rd Harmonic Phase A
VA:4th Harm Metering Voltage 4th Harmonic Phase A
VA:5th Harm Metering Voltage 5th Harmonic Phase A
VA:6th Harm Metering Voltage 6th Harmonic Phase A
VA:7th Harm Metering Voltage 7th Harmonic Phase A
VA:8th Harm Metering Voltage 8th Harmonic Phase A
VA:9th Harm Metering Voltage 9th Harmonic Phase A
VA:10th Harm Metering Voltage 10th Harmonic Phase A
VA:11th Harm Metering Voltage 11th Harmonic Phase A
VA:12th Harm Metering Voltage 12th Harmonic Phase A
VA:13th Harm Metering Voltage 13th Harmonic Phase A
VA:14th Harm Metering Voltage 14th Harmonic Phase A
VA:15th Harm Metering Voltage 15th Harmonic Phase A
VB:2nd Harm Metering Voltage 2nd Harmonic Phase B
VB:3rd Harm Metering Voltage 3rd Harmonic Phase B
4-104
!
SAFETY
S280-70-21
FOR LIFE
Name Description
VB:4th Harm Metering Voltage 4th Harmonic Phase B
VB:5th Harm Metering Voltage 5th Harmonic Phase B
VB:6th Harm Metering Voltage 6th Harmonic Phase B
VB:7th Harm Metering Voltage 7th Harmonic Phase B
VB:8th Harm Metering Voltage 8th Harmonic Phase B
VB:9th Harm Metering Voltage 9th Harmonic Phase B
VB:10th Harm Metering Voltage 10th Harmonic Phase B
VB:11th Harm Metering Voltage 11th Harmonic Phase B
VB:12th Harm Metering Voltage 12th Harmonic Phase B
VB:13th Harm Metering Voltage 13th Harmonic Phase B
VB:14th Harm Metering Voltage 14th Harmonic Phase B
VB:15th Harm Metering Voltage 15th Harmonic Phase B
VC:2nd Harm Metering Voltage 2nd Harmonic Phase C
VC:3rd Harm Metering Voltage 3rd Harmonic Phase C
VC:4th Harm Metering Voltage 4th Harmonic Phase C
VC:5th Harm Metering Voltage 5th Harmonic Phase C
VC:6th Harm Metering Voltage 6th Harmonic Phase C
VC:7th Harm Metering Voltage 7th Harmonic Phase C
VC:8th Harm Metering Voltage 8th Harmonic Phase C
VC:9th Harm Metering Voltage 9th Harmonic Phase C
VC:10th Harm Metering Voltage 10th Harmonic Phase C
VC:11th Harm Metering Voltage 11th Harmonic Phase C
VC:12th Harm Metering Voltage 12th Harmonic Phase C
VC:13th Harm Metering Voltage 13th Harmonic Phase C
VC:14th Harm Metering Voltage 14th Harmonic Phase C
VC:15th Harm Metering Voltage 15th Harmonic Phase C
VS:2nd Harm Metering Voltage 2nd Harmonic Phase S
VS:3rd Harm Metering Voltage 3rd Harmonic Phase S
VS:4th Harm Metering Voltage 4th Harmonic Phase S
VS:5th Harm Metering Voltage 5th Harmonic Phase S
VS:6th Harm Metering Voltage 6th Harmonic Phase S
VS:7th Harm Metering Voltage 7th Harmonic Phase S
VS:8th Harm Metering Voltage 8th Harmonic Phase S
VS:9th Harm Metering Voltage 9th Harmonic Phase S
VS:10th Harm Metering Voltage 10th Harmonic Phase S
VS:11th Harm Metering Voltage 11th Harmonic Phase S
VS:12th Harm Metering Voltage 12th Harmonic Phase S
VS:13th Harm Metering Voltage 13th Harmonic Phase S
VS:14th Harm Metering Voltage 14th Harmonic Phase S
VS:15th Harm Metering Voltage 15th Harmonic Phase S
pfA Power Factor Phase A
pfB Power Factor Phase B
pfC Power Factor Phase C
S:Phase A (kVA pri) Filtered KVA Phase A
S:Phase B (kVA pri) Filtered KVA Phase B
S:Phase C (kVA pri) Filtered KVA Phase C
4-105
Form 6 Microprocessor-Based Recloser Control Programming Guide
Name Description
S:3phase (kVA pri) Filtered KVA Total
Demand(P:Phase A (kW pri)) Demand KW Phase A Out
Demand(P:Phase B (kW pri)) Demand KW Phase B Out
Demand(P:Phase C (kW pri)) Demand KW Phase C Out
Demand(P:3phase (kW pri)) Demand KW Total Out
Demand(Q:Phase A (kvar pri)) Demand KVAR Phase A Out
Demand(Q:Phase B (kvar pri)) Demand KVAR Phase B Out
Demand(Q:Phase C (kvar pri)) Demand KVAR Phase C Out
Demand(Q:3phase (kvar pri)) Demand KVAR Total Out
Demand(-P:Phase A (kW pri)) Demand KW Phase A In
Demand(-P:Phase B (kW pri)) Demand KW Phase B In
Demand(-P:Phase C (kW pri)) Demand KW Phase C In
Demand(-P:3phase (kW pri)) Demand KW Total In
Demand(-Q:Phase A (kvar pri)) Demand KVAR Phase A In
Demand(-Q:Phase B (kvar pri)) Demand KVAR Phase B In
Demand(-Q:Phase C (kvar pri)) Demand KVAR Phase C In
Demand(-Q:3phase (kvar pri)) Demand KVAR Total In
KWH-A-Out (pri) Metering kWhr Phase A Out
KWH-B-Out (pri) Metering kWhr Phase B Out
KWH-C-Out (pri) Metering kWhr Phase C Out
KWH-3P-Out (pri) Metering kWhr Total Out
KWH-A-In (pri) Metering kWhr Phase A In
KWH-B-In (pri) Metering kWhr Phase B In
KWH-C-In (pri) Metering kWhr Phase C In
KWH-3P-In (pri) Metering kWhr Total In
4-106
!
SAFETY
S280-70-21
FOR LIFE
Factory Nameplate
The Factory Nameplate dialog box displays the following
information:
Scheme Number
Custom Engineered Scheme Number
Date Code
ProView Version
4-107
Form 6 Microprocessor-Based Recloser Control Programming Guide
Metering
Demand
4-108
!
SAFETY
S280-70-21
FOR LIFE
Measured Demand
The Measured Demand dialog box allows the user to view the
current and power (real and reactive) demands, based on the
Demand Interval Time setting in the Metering Settings dialog
box. Refer to Metering in the Settings section of this manual
for Demand Interval Time setting information.
The user must be online to view the demands in the control.
The values displayed are the current period demand read-
ings.
Click the Go Online button. The current period demand read-
ings are displayed.
4-109
Form 6 Microprocessor-Based Recloser Control Programming Guide
Peak Demand
The Peak Demand dialog box allows the user to view the cur-
rent and power (real and reactive) peak demands and times,
based on the Demand Interval Time setting in the Metering
Settings dialog box, as measured since the last reset. Refer to
Metering in the Settings section of this manual for Demand
Interval Time setting information.
The user must be online to view the peak demands in the
control. The values displayed are the current peak demand
readings.
Click the Go Online button. The current peak demand read-
ings and times are displayed.
4-110
!
SAFETY
S280-70-21
FOR LIFE
Instantaneous
4-111
Form 6 Microprocessor-Based Recloser Control Programming Guide
Symmetrical
4-112
!
SAFETY
S280-70-21
FOR LIFE
Counters
The Counters dialog box allows the user to view the counters
retained by the Form 6 control.
The user must be online to view the counters in the control.
Click the Go Online button. The counter values maintained by
the control are displayed.
Trip and Target Counters are preset to zero for a new
recloser.
If retrofitting an existing recloser, preset the control
counters to match the recloser counters. If a Form
6 control is attached to a mechanism that has a
known operating history, the trip and target counters
and duty cycle information can be pre-programmed
into the control via the Presets dialog box. Refer to
Settings - Presets in the ProView Form 6 Control
Schemes section in this manual for additional infor-
mation.
4-113
Form 6 Microprocessor-Based Recloser Control Programming Guide
Energy
The Energy dialog box allows the user to view the current
and power (real and reactive) energy values measured by the
Form 6 recloser control.
Click the Reset Energy button to reset the The user must be online to view the energy values in the control.
accumulated energy from ProView.
Click the Go Online button. The energy values are displayed.
This can also be accomplished via the Form
6 control front panel MMI. Refer to Metering
Menu in the Front Panel Operation section
of this manual.
4-114
!
SAFETY
S280-70-21
FOR LIFE
Lower Harmonics
4-115
Form 6 Microprocessor-Based Recloser Control Programming Guide
Higher Harmonics
4-116
!
SAFETY
S280-70-21
FOR LIFE
4-117
Form 6 Microprocessor-Based Recloser Control Programming Guide
4-118
!
SAFETY
S280-70-21
FOR LIFE
5-1
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-2
!
SAFETY
S280-70-21
FOR LIFE
Click here
to access Click on any
the User terminal block to
Workbench open up a view of Click here to open the
blocks. that terminal block. Color Key screen.
5-3
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-4
!
SAFETY
S280-70-21
FOR LIFE
5-5
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-6
!
SAFETY
S280-70-21
FOR LIFE
An example of
Idea Workbench
white space.
5-7
Form 6 Microprocessor-Based Recloser Control Programming Guide
EXCLUSIVE OR Gate
Two Input NOR Gate
Dropout Timer
Reset Priority Latch
5-8
!
SAFETY
S280-70-21
FOR LIFE
An example of
Idea Workbench
white space.
5-9
Form 6 Microprocessor-Based Recloser Control Programming Guide
Minimum Operator
Delay One Iteration
Maximum Operator
Array Lookup Operator
Negation Operator
Absolute Value Operator
Addition Operator
Subtraction Operator
Real-Part Operator
Multiplication Operator
Numeric Probe
(shows numeric value)
Imaginary-Part Operator
Breaker Simulator
(not for use with the
Non-Volatile Sr Latch Form 6 control)
5-10
!
SAFETY
S280-70-21
FOR LIFE
5-11
Form 6 Microprocessor-Based Recloser Control Programming Guide
Name: Two Input Multiplexor (This function cant be used to drive timer durations.)
Function: Passes one of two inputs to its output depending upon the state of the third input.
Input terminal 0 (upper): First input signal.
Input terminal 1 (middle): Second input signal.
Input terminal 2 (lower): Selector input. If a Logical 0, the first input is passed to the output.
If a Logical 1, the second input is passed to the output.
Name: Equality Operator
Function: Determines if the two inputs are equal. Both inputs must be of the same data
type (integer to integer, float to float, etc). Otherwise, it will cause an error message when
ProView prepares to download the logic to the control.
Input terminal 0 (upper): Value of first input quantity.
Input terminal 1 (lower): Value of second input quantity.
Output terminal 0: Goes to a Logical 1 when the values of the two inputs are equal.
Otherwise, a Logical 0 is output.
Name: Global Input
Function: To input the value of a global system variable to the Idea Workbench. This is for
the advanced user who is developing specific schemes that require low-level operating signals.
Usage:
1. To use the Global input, first drag one into the scheme.
2. Use the mouse to point to the Global input block and right-click.
3. Select Block Configuration from the resulting pop-up menu.
The Block Configuration dialog box will appear. The text "Global Input" will be in the Name field.
4. Replace this text with information as directed from the factory. As an example:
"ExecSetup1": This is a binary output that changes to a Logical "1" at the exact
moment the control boot-up procedure has ended and the algorithms start running.
This signal indicates that the control has started functioning as a control following
start-up or a setting group change. An exclamation point in the value means that the
signal is not configured correctly. The output is case sensitive.
Function: All of these blocks provide the ability to introduce settings into the User
Workbenches. The name of each block describes the data type created for that setting.
Output (0): The value of the setting.
This produces a binary setting that can be set to a 0 or 1 only. This is used to drive logic
gates, etc.
This is a floating point setting. This is used to drive inputs such as timers, comparators, etc.
This is a complex, floating point setting. This is typically used to provide settings that are
involved in phasor math operations.
This is a 16-bit integer setting. The range goes from -32,768 to +32,768.
This is a 32-bit integer setting. It is used when an integer setting is required where the setting
range goes beyond +32,768.
5-12
!
SAFETY
S280-70-21
FOR LIFE
5-13
Form 6 Microprocessor-Based Recloser Control Programming Guide
fb
LOGIC
5-14
!
SAFETY
S280-70-21
FOR LIFE
5-15
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-16
!
SAFETY
S280-70-21
FOR LIFE
5-17
Form 6 Microprocessor-Based Recloser Control Programming Guide
Threshold Settings
WB threshold settings 14 allow the user to create thresholds
whose values will be used in mathematical functions within
the workbench. Once the function is created, the threshold
value can be changed within the Workbench User Settings
dialog. Separate settings can be entered for each of the four
profiles (Normal, Alternate 1, Alternate 2, Alternate 3). A WB
Threshold is a floating point setting identical in function to the
"Advanced Tools" "Float Setting", although the WB threshold
value can be modified from outside of the Workbench envi-
ronment.
Protection Settings
Protection Settings menu elements annunciate the active
profile, provide minimum trip settings for all four profiles, and
provide active minimum trip settings.
5-18
!
SAFETY
S280-70-21
FOR LIFE
5-19
Form 6 Microprocessor-Based Recloser Control Programming Guide
Demand Currents
The Demand Currents menu provides four elements to
annunciate demand current peak values for A, B, and C
Phase and Ground.
5-20
!
SAFETY
S280-70-21
FOR LIFE
Communications
The Communications menu is divided into two categories:
The DNP Communications menu provides two ele-
ments, one for Pulsed Binary Outputs and one for
Latched Binary Outputs. These outputs can be used
multiple times.
Note: DNP elements are only active and for use when DNP
is installed on the Workbench.
5-21
Form 6 Microprocessor-Based Recloser Control Programming Guide
Recloser Status
The Recloser Status menu provides 14 elements to annunci-
ate recloser status, an additional 2 elements to annunciate
Reclose Retry Active and Reclose Retry Lockout, and one
Battery Test Active element.
Voltage Status
The Voltage Status menu contains three elements to annunci-
ate the presence of Bus Voltage for A, B, and C phases and
one logic element to annunciate the Sensing Voltage Alarm
Status.
Sync-Check
The Sync-Check menu provides four elements to annunciate
sync-check statuses and six elements to annunciate enabled
and measured sync-check Close conditions.
5-22
!
SAFETY
S280-70-21
FOR LIFE
Blocking Status
The Blocking Status menu provides elements to annunciate
the blocking status of Phase Overcurrent, Negative Sequence
Overcurrent, Battery Test, Oscillography, Lock Status for
Target Counters, and Lock Status for All Accumulators
(excluding Targets).
Targets
The Targets menu provides elements that annunciate the sta-
tus of various protective functions.
5-23
Form 6 Microprocessor-Based Recloser Control Programming Guide
Frequency Detection
The Frequency Detection menu provides 10 elements to indi-
cate Frequency related quantities and status.
Four elements annunciate the status of under and overfre-
quency loadshed, one provides Frequency Restoration status,
three provide Frequency Measurement analogs, and two vali-
date Frequency Measurement.
Current Detection
The Current Detection menu provides a total of six elements,
two of the elements annunciate detection of any single or
three phase current. The remaining four elements annunciate
Fault Detection results.
5-24
!
SAFETY
S280-70-21
FOR LIFE
Alarms
The Alarms menu provides a total of 27 elements to annunci-
ate Control, System, and Collected alarms.
Non-Latched Demand Alarms
The Non-Latched Demand Alarms menu provides a total of
17 elements to annunciate Demand alarms.
5-25
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-26
!
SAFETY
S280-70-21
FOR LIFE
Data Profiler
The Data Profiler menu provides one element to annunciate
the Data Profiler status.
5-27
Form 6 Microprocessor-Based Recloser Control Programming Guide
Auxiliary Targets
A Phase Fault Trip
A target indicating that the A-phase current was either the
maximum phase current or within 80% of the maximum when
a trip signal was issued.
1 = An A-phase trip occurred.
B Phase Fault Trip
A target indicating that the B-phase current was either the
maximum phase current or within 80% of the maximum when
a trip signal was issued.
1 = A B-phase trip occurred.
C Phase Fault Trip
A target indicating that the C-phase current was either the
maximum phase current or within 80% of the maximum when
a trip signal was issued.
1 = A C-phase trip occurred.
Ground Fault Trip
A target indicating that a Ground tripping function was assert-
ed at the time the trip signal was asserted.
1 = A ground involved trip occurred.
SEF Trip
A target indicating that the sensitive Earth fault tripping func-
tion was asserted at the time the trip signal was asserted.
1 = An SEF trip occurred.
Voltage Trip
A target indicating that an overvoltage or undervoltage trip-
ping function was asserted at the time the trip signal was
asserted.
1 = A voltage involved trip occurred.
Frequency Trip
A target indicating that an overfrequency or underfrequency
tripping function was asserted at the time the trip signal was
asserted.
1 = A frequency involved trip occurred.
CLPU P/Q Trip
A target indicating that Cold Load Pickup Phase or Negative
Sequence function was asserted at the time the trip signal
was asserted.
1 = A Cold Load Pickup phase or negative sequence trip
occurred.
CLPU Gnd Trip
A target indicating that a Cold Load Pickup Ground trip-
ping function was asserted at the time the trip signal was
asserted.
1 = A Cold Load Pickup ground involved trip occurred.
5-28
!
SAFETY
S280-70-21
FOR LIFE
P/Q Trip
A target indicating that Phase or Negative Sequence function
was asserted at the time the trip signal was asserted.
1 = A phase or negative sequence trip occurred.
BFI-LBB: Trip
A Breaker Failed/Initiate Local Breaker Backup condition
was detected because the local mechanism did not trip in
the desired time after issuing a trip signal to the mechanism.
Breaker fail action should be initiated.
1 = A breaker fail condition exists, and a trip and lockout
signal has been sent to the connected mechanism.
Note: This is not a maintained signal and is only active while the
condition exists.
Interrupter Malfunction: Trip
An Interrupter malfunction has been detected in the connect-
ed mechanism. Current did not extinguish within five seconds
of the trip signal being issued. Breaker fail action should be
initiated.
1 = An Interrupter malfunction condition exists, and a trip
and lockout signal has been sent to the connected
mechanism.
Note: This is not a maintained signal and is only active while the
condition exists.
Above Minimum Trip
A target indicating one of the currents through the recloser are
above one of the Minimum Trip (phase, ground, or negative
sequence, or CLPU thresholds, if CLPU is active) settings.
1 = The measured current is above one of the minimum trip
thresholds.
Note: This is not a maintained signal and is only active while the
condition exists.
TCC1Ground Above Min. Trip
A target indicating the calculated residual current through the
recloser is above the TCCG Minimum Trip setting and that
TCC1 is the active TCC.
1 = The calculated residual current is above the TCCG
threshold and TCC1 is timing.
Note: This is not a maintained signal and is only active while the
condition exists.
TCC2Ground Above Min. Trip
A target indicating the calculated residual current through the
recloser is above the TCCG Minimum Trip setting and that
TCC2 is the active TCC.
1 = The calculated residual current is above the TCCG
threshold and TCC2 is timing.
Note: This is not a maintained signal and is only active while the
condition exists.
5-29
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-30
!
SAFETY
S280-70-21
FOR LIFE
5-31
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-32
!
SAFETY
S280-70-21
FOR LIFE
5-33
Form 6 Microprocessor-Based Recloser Control Programming Guide
Digital traces
5-34
!
SAFETY
S280-70-21
FOR LIFE
5-35
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-36
!
SAFETY
S280-70-21
FOR LIFE
Torque Control
The operation of these output signals is intended to be
analogous to the like-named input contacts on electrome-
chanical relays. When the torque control signal is asserted,
operating torque is then passed to the rotating "disk" (TCC
timing begins). But when the signal is unasserted, the disk is
allowed to rotate back to its initial position, acting only under
the force of the spring (TCC reset occurs).
These signals act differently than simple supervision of the
trip output. In the typical application, this output signal could
be driven by directional elements. The TCC timing is not even
allowed to start unless the measured fault direction is correct.
Since directional determination can be subject to transient
effects, placing such a restriction on TCC timing increases
tripping security, helping to avoid misoperation until the direc-
tional measurement is no longer subject to transient error.
Normal
Control Ground TCC Torque
Control Neg Seq TCC Torque
Control Phase TCC Torque
When CLPU is Active
Control CLPU Ground TCC Torque
Control CLPU Neg Seq TCC Torque
Control CLPU Phase TCC Torque
Blocking
These outputs block Phase Trips, Negative Sequence Trips,
Oscillography, and Battery Testing. Blocking persists only
while associated output is asserted (set to a Logical 1).
5-37
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-38
!
SAFETY
S280-70-21
FOR LIFE
Special
Hot Line Tag
HLT On Setting this output to a logical 1 turns on the
Hot Line Tag function.
HLT Off Setting this output to a logical 1 turns off the
Hot Line Tag function.
Supervisory
Supervisory Off Setting this output to a logical 1 turns
on the Supervisory Off function.
@Alternative Control Outputs Accomplishes the same
as above.
Reset Functions
Reset Targets Setting this output to a logical 1 resets
all targets.
Reset Alarms Setting this output to a logical 1 resets
all alarms.
Reset Recloser Setting this output to a logical 1 gives
the user the ability to immediately reset the sequence
position back to zero.
Note: The default logic will prevent a reset if there is fault
current present.
Note: The front panel LCD Diagnostics menu screen displays
the sequence position of the recloser connected to the
Form 6 control.
Note: This output provides the same type of function as
Reset Time through the ProView Settings menu. Refer
to the Reclose in the Settings section in this manual
for additional information.
Reset SCFCounters Setting this output to a logical
1 gives the user the ability to immediately reset the
SCFCounters back to zero.
Note: The front panel LCD Self-Clear Fault menu screen also
allows the user to Reset Fault Data.
Note: This output provides the same type of function as
Clear SCFcounters through the ProView Settings
menu. Refer to the Incipient Cable Splice Fault in
the Settings section in this manual for additional infor-
mation.
Control Recloser
Trip and Lockout Setting this output to a logical 1 will
initiate a Trip and Lockout signal.
Trip with Reclose Setting this output to a logical 1 will
initiate a Trip signal (Control may issue a reclose signal
dependent on sequence position and control OCP pro-
gramming).
Close Setting this output to a logical 1 will initiate a
Close signal.
Block of Close Setting this output to a logical 1 will
initiate a Block of Close signal.
5-39
Form 6 Microprocessor-Based Recloser Control Programming Guide
Oscillography Controls
Trigger Oscillography Setting this output to a logical 1
will initiate an Oscillographic event.
Battery Operations
Test Battery Setting this output to a logical 1 will initi-
ate a Battery Test.
Lock Accumulators...(...lock all except Target Counters)
Activate Test Mode Setting this output to a logical 1
will initiate Test Mode.
Note: The front panel Test Modes menu screen also allows
the user to activate Test Mode (except for Targets).
(...lock Target Counters)
Lock Target Counters Setting this output to a logical
1 will lock the target counters.
Note: The front panel Test Modes menu screen also allows
the user to lock the target counters.
Front Panel
Wake Up Front Panel Setting this output to a logical
1 will illuminate active Front Panel LEDs and turn on the
LCD Display Backlight.
Data Profiler
Configure up to ten metering options not already available
with the Data Profiler. Drive the signals from the Workbench,
use Analogs only:
WB Data Profiler (#01) through (#10)
Refer to Data Profiler in the Display section of this manual
for additional information regarding available metering options.
Drive the following signals from the Workbench, Logic only:
WB Trigger Data Profiler
WB Enable Data Profiler
5-40
!
SAFETY
S280-70-21
FOR LIFE
5-41
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-42
!
SAFETY
S280-70-21
FOR LIFE
This will create a new block that contains the logic enclosed
in the original box.
3. Right-click on the block (in either its open or closed
condition) and select Block>Configuration from the
pop-up menu.
5-43
Form 6 Microprocessor-Based Recloser Control Programming Guide
Workbench Files
At the upper-left corner of the Idea Workbench is a button
labeled Workbench Files. Click on this button to display the
menu options.
5-44
!
SAFETY
S280-70-21
FOR LIFE
5-45
Form 6 Microprocessor-Based Recloser Control Programming Guide
Communications Workbench
Configuring Protocol Communications
The Form 6 recloser control has user-selectable implemen-
tation of ProView-based DNP3, Modbus, IEC870-5-101,
IEC870-5-104, 2179, and DNP TCP/IP communications.
Communication protocols are configured via a
Communications Workbench. General use of the
Communications Workbench follows the concept of the Idea
Workbench. Refer to the Hardware Idea Workbench section
of this manual for additional menu and screen information.
5-46
!
SAFETY
S280-70-21
FOR LIFE
Workbench Files
At the upper-left corner of the Communications Workbench is
a button labeled Workbench Files. Click on this button to dis-
play the menu options.
5-47
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-48
!
SAFETY
S280-70-21
FOR LIFE
5-49
Form 6 Microprocessor-Based Recloser Control Programming Guide
DNP Workbench
All Communications changes must take place in the appropri-
ate Workbench. The Form 6 control allows users to custom
configure DNP3 points and settings.
Access the DNP Workbench as follows:
1. Click on the DNP Workbench graphic.
The DNP Workbench blocks will appear.
2. Click on the applicable block.
Note: The DNP default point database is in the Cooper/ProView50/
Form6 folder. The document title is dnpf6dat.xls.
5-50
!
SAFETY
S280-70-21
FOR LIFE
5-51
Form 6 Microprocessor-Based Recloser Control Programming Guide
DNPUnsolicited Settings
5-52
!
SAFETY
S280-70-21
FOR LIFE
Optional LSOutputs
Optional Loop Scheme outputs are available for Form 6
controls equipped with the LS option. The LS scheme and
Workbenches must be loaded.
Setting these outputs to a logical 1 will activate these loop
scheme-specific communication functions:
Comm LSDisable
Comm SI Disable
Comm SII Disable
Reset LS
Optional LSInputs
Seventeen intermediate variables are provided to allow signals
to be sent between Workbench blocks.
The Voltage Level Indicators menu provides three intermedi-
ate variables for Source I and Source II.
Once defined, the intermediate variables can be used by
dragging them out of the Optional LSInputs menu.
5-53
Form 6 Microprocessor-Based Recloser Control Programming Guide
Modbus Workbench
All Communications changes must take place in the appropri-
ate Workbench. The Form 6 control allows users to custom
configure Modbus points and settings.
The user should be familiar with SCADA control and have a
basic understanding of Modbus.
The default Workbench structures provides the user access
to analog and control parameters within the scheme. The
flexibility of the Modbus system allows the user to modify the
structure via the Communications Workbench.
Access the Modbus Workbench as follows:
1. Click on the Modbus Workbench graphic.
The Modbus Workbench blocks will appear.
2. Click on the applicable block.
Note: The Modbus default point database is in the Cooper/
ProView50/Form6 folder. The document title is modbusf6dat.
xls.
5-54
!
SAFETY
S280-70-21
FOR LIFE
2179 Workbench
All Communications changes must take place in the appropriate
Workbench. The Form 6 control allows users to custom config-
ure 2179 protocol points and settings.
Access the 2179 Workbench as follows:
1. Click on the 2179 Workbench graphic.
The 2179 Workbench blocks will appear.
2. Click on the applicable block.
Note: The 2179 default point database is in the Cooper/ProView50/
Form6 folder. The document title is 2179F6dat.xls.
Click here
to open
the input
toolboxes. Click here to access factory-
assigned and user analog, binary,
and counter inputs mapping.
5-55
Form 6 Microprocessor-Based Recloser Control Programming Guide
Communication Settings
5-56
!
SAFETY
S280-70-21
FOR LIFE
Optional LSOutputs
Optional Loop Scheme outputs are available for Form 6
controls equipped with the LS option. The LS scheme and
Workbenches must be loaded.
Setting these outputs to a logical 1 will activate these loop
scheme-specific communication functions:
Comm LSDisable
Comm SI Disable
Comm SII Disable
Reset LS
Optional LSInputs
Seventeen intermediate variables are provided to allow signals
to be sent between Workbench blocks.
The Voltage Level Indicators menu provides three intermediate
variables for Source I and Source II.
Once defined, the intermediate variables can be used by drag-
ging them out of the Optional LSInputs menu.
5-57
Form 6 Microprocessor-Based Recloser Control Programming Guide
IEC870-5-101 Workbench
All Communications changes must take place in the appropri
ate Workbench. The Form 6 control allows users to custom
configure IEC870-5-101 protocol points and settings.
Access the IEC870-5-101 Workbench as follows:
1. Click on the IEC870-5-101 Workbench graphic.
The IEC870-5-101 Workbench blocks will appear.
2. Click on the applicable block.
Note: The IEC60870-5-101 default point database is in the Cooper/
ProView50/Form6 folder. The document title is iec608705f6dat.
xls.
Click here
to open
the input
toolboxes.
5-58
!
SAFETY
S280-70-21
FOR LIFE
5-59
Form 6 Microprocessor-Based Recloser Control Programming Guide
Optional LSInputs
Seventeen intermediate variables are provided to allow signals
to be sent between Workbench blocks.
The Voltage Level Indicators menu provides three intermedi-
ate variables for Source I and Source II.
Once defined, the intermediate variables can be used by
dragging them out of the Optional LSInputs menu.
Optional LSOutputs
Optional Loop Scheme outputs are available for Form 6
controls equipped with the LS option. The LS scheme and
Workbenches must be loaded.
Setting these outputs to a logical 1 will activate these loop
scheme-specific communication functions:
Comm LSDisable
Comm SI Disable
Comm SII Disable
Reset LS
5-60
!
SAFETY
S280-70-21
FOR LIFE
IEC870-5-104 Workbench
All Communications changes must take place in the appropri
ate Workbench. The Form 6 control allows users to custom
configure IEC870-5-104 protocol points and settings.
Access the IEC870-5-104 Workbench as follows:
1. Click on the IEC870-5-104 Workbench graphic.
The IEC870-5-104 Workbench blocks will appear.
2. Click on the applicable block.
Note: The IEC60870-5-104 default point database is in the Cooper/
ProView50/Form6 folder. The document title is iec608705f-
6dat.xls.
Click here
to open
the input
toolboxes.
5-61
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-62
!
SAFETY
S280-70-21
FOR LIFE
Optional LSInputs
Seventeen intermediate variables are provided to allow signals
to be sent between Workbench blocks.
The Voltage Level Indicators menu provides three intermedi-
ate variables for Source I and Source II.
Once defined, the intermediate variables can be used by
dragging them out of the Optional LSInputs menu.
Optional LSOutputs
Optional Loop Scheme outputs are available for Form 6
controls equipped with the LS option. The LS scheme and
Workbenches must be loaded.
Setting these outputs to a logical 1 will activate these loop
scheme-specific communication functions:
Comm LSDisable
Comm SI Disable
Comm SII Disable
Reset LS
5-63
Form 6 Microprocessor-Based Recloser Control Programming Guide
Refer to DNP Basic and Advanced Click here to access the HTML
Settings sections for screen information. screen that displays the DNP Tables.
5-64
!
SAFETY
S280-70-21
FOR LIFE
5-65
Form 6 Microprocessor-Based Recloser Control Programming Guide
Optional LSOutputs
Optional Loop Scheme outputs are available for Form 6
controls equipped with the LS option. The LS scheme and
Workbenches must be loaded.
Setting these outputs to a logical 1 will activate these loop
scheme-specific communication functions:
Comm LSDisable
Comm SI Disable
Comm SII Disable
Reset LS
Optional LSInputs
Seventeen intermediate variables are provided to allow signals
to be sent between Workbench blocks.
The Voltage Level Indicators menu provides three intermediate
variables for Source I and Source II.
Once defined, the intermediate variables can be used by
dragging them out of the Optional LSInputs menu.
5-66
!
SAFETY
S280-70-21
FOR LIFE
Examples of configured Group Dependent User Settings added to the Idea Workbench.
5-67
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-68
!
SAFETY
S280-70-21
FOR LIFE
5-69
Form 6 Microprocessor-Based Recloser Control Programming Guide
ENTER
>W O R K B E N C H MESSAGES
WORKBENCH ANALOGS
WORKBENCH STATUS
WORKBENCH SWITCHES
WORKBENCH NAME
ENTER
>WORKBENCH MESSAGES
WORKBENCH ANALOGS
WORKBENCH STATUS
WORKBENCH SWITCHES
ENTER
Fa i l u r e t o T r i p
MENU
5-70
!
SAFETY
S280-70-21
FOR LIFE
MENU
5-71
Form 6 Microprocessor-Based Recloser Control Programming Guide
TER ENTER
Example
ENTER
of custom analog ENTER ENTER
No
value routed to the Form 6
>Ana l o g #01= 0.000 >0=MMI(#01) status >Momentary Switch #1 WORKBENCH NAME...
Ana l o g #02= 0.000 control front
0=MMI(#02) panel MMI.Momentary Switch
status #2 Form6
Ana l o g #03= 0.000 0=MMI(#03) status Momentary Switch #3
Ana l o g #04= 0.000 0=MMI(#04) status Momentary Switch #4
ENU Ana l o g #05= 0.000 0=MMI(#05) status
Ana l o g #06= 0.000 0=MMI(#06) status MENU
Ana l o g #07= 0.000 0=MMI(#07) status >Push YES to operate
Ana l o g #08= 0.000 0=MMI(#08) status Push MENU to abort.
0=MMI(#09) status Mom entary Switch #1
................YES
MENU 0=MMI(#10) status
0=MMI(#11) status
0=MMI(#12) status F4
0=MMI(#13) status Press F4 and hold.
0=MMI(#14) status
0=MMI(#15) status >Push YES to operate
0=MMI(#16) status Push MENU to abort.
Momentary Switch #1
Name of Workbench Outputs Listing
MENU Result of Driving the Block Input
----(OPERATING!)----
WB(Analog#04) 4th Workbench Analog signal on the Form 6 Recloser Control MMI.
WB(Analog#05) 5th Workbench Analog signal on the Form 6 Recloser Control MMI.
WB(Analog#06) 6th Workbench Analog signal on the Form 6 Recloser Control MMI.
WB(Analog#07) 7th Workbench Analog signal on the Form 6 Recloser Control MMI.
WB(Analog#08) 8th Workbench Analog signal on the Form 6 Recloser Control MMI.
5-72
!
SAFETY
S280-70-21
FOR LIFE
MENU
>Momentary Switc h #1
Momentary Switc h #2
Momentary Switc h #3 Name of Workbench Inputs Listing Result of Driving the Blocks Output
Momentary Switc h #4
Softkey Pushbuttons from MMI Output is logical 1 if the:
Momentary Switch #1=0 Momentary Switch #1 on the front panel MMI is pressed.
Momentary Switch #2=0 Momentary Switch #2 on the front panel MMI is pressed.
Momentary Switch #3=0 Momentary Switch #3 on the front panel MMI is pressed.
Momentary Switch #4=0 Momentary Switch #4 on the front panel MMI is pressed.
5-73
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-74
!
SAFETY
S280-70-21
FOR LIFE
5-75
Form 6 Microprocessor-Based Recloser Control Programming Guide
Workbench Description
The Workbench Description dialog box enables the user to
change a Workbench name.
Note: This feature is also available via the Workbench Files menu or
the Settings>Simplified Setup screen.
1. Open the Workbench Description dialog box.
The Description text will be highlighted.
2. Type in the new Description text.
3. Click on OK.
5-76
!
SAFETY
S280-70-21
FOR LIFE
R1
Source 1 Sectionalizing
Recloser
Fault 1
Load
Normally closed
Fault 2
R2
Source 2 Tie Recloser
Normally open
Fault 1 Fault 2
R1
Source 1 Sectionalizing
S1 Feeder Recloser
Normally
closed
R3
TIE Recloser
Normally
open
R2
Source 2 Sectionalizing
S2 Feeder Recloser
Normally
closed
5-78
!
SAFETY
S280-70-21
FOR LIFE
R1 R3
Source 1 Feeder Midpoint
Sectionalizing Sectionalizing
S1 Recloser Recloser
Fault 1 Fault 2
800 amps
R5
Tie
Recloser
400 amps
R2 R4
Source 2 Feeder Midpoint
S2 Sectionalizing Sectionalizing
Recloser Recloser
800 amps
280 amps
560 amps
Loop Sectionalizing with Five Reclosers
5-79
Form 6 Microprocessor-Based Recloser Control Programming Guide
Next, Tie Recloser R5 times out, closes in the fault, and R3 will
lock out. The fault is isolated between R1 and R3. Service is
maintained to the remaining major portion of the loop. If a perma-
nent fault occurs at Fault 2, R3 operates to lockout normally, R5
senses the loss of voltage after its programmed time delay, R5
closes into the fault and operates to lockout. The fault is isolated
between R3 and R5. Service is maintained to the remaining major
portion of the loop.
5-80
!
SAFETY
S280-70-21
FOR LIFE
5-81
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-82
!
SAFETY
S280-70-21
FOR LIFE
Tie Options
These options are only available when LS is configured in tie
mode from drop down dialog.
1. LS Reset on Manual Trip to Lockout allows auto-
matic LS reset when LS is tripped locally via front
panel. This eliminates an extra step of resetting
after manual trip.
5-83
Form 6 Microprocessor-Based Recloser Control Programming Guide
Sectionalizing Options
These options are only available when LS is configured in
sectionalizing mode from drop down dialog.
1. LS Auto Reset applies to feeder and midpoint only
with TD3 timer. An LS sectionalizer control may be
in the closed position and trip and lock out on loss
of voltage for Source 1. With LS Auto Reset on TD3
Timeout selected, the LS will reset after the Source 1
voltage returns and the programmed TD3 time has
expired.
2. TD3 is the Auto Reset Time Delay interval during
which restoration of voltage must be continuously
detected before an automatic LS reset will occur.
3. Auto Close on LS Auto Reset will allow feeder
reclosers to automatically close back in upon LS
Auto Reset.
4. Auto Return to Normal, LS Reset will automatically
return the midpoint or feeder to normal profile when
forward power flow direction occurs.
5. Permit Manual Close while LS Not Reset allows front
panel close operation if loop scheme is not reset.
6. LS Reset on Manual Close allows automatic LS
reset when LS is closed locally via front panel. This
eliminates an extra step of resetting after manual
close.
Note: The LS Auto Reset will not reset and close if the loss of volt-
age was preceded by fault current.
Source Options
Sectionalizing applications will use one source for voltage
sensing and tie applications may use one or two sources.
1. Source II is always disabled when LS type is set
to Sectionalizing. LS Enable SI and LS Enable SII
Source Load checkboxes enable use of voltage restoration mode
and after LS Actions for respective source input.
User Option Buttons #5 & #6 are programmed to
Recloser enable Source 1 and 2 respectively via front panel.
2. Define load and source side voltage inputs from
drop down menu.
3. Voltage Response Mode define whether voltage
source is three- or single-phase sensing.
ABC XYZ
SI SII 4. Voltage Transfer TD1 Delay is loss of voltage timer
to initiate loop scheme.
5. LS Action define what action the loop scheme
takes after satisfying TD1 timer supervision: No
One-Line Diagram for Sectionalizing or Tie Action, Trip to Lock Out, or Close.
Applications
5-84
!
SAFETY
S280-70-21
FOR LIFE
After LS Action
The Form 6-LS control can change profiles when an LS
action occurs.
1. Select whether Ground Trip Blocked mode will
make No Change, Latch On until LS Reset or
Toggle On for given momentary function delay TD2.
2. Select whether Non-Reclosing mode will make No
Change, Latch On until LS Reset or Toggle On for
given momentary function delay TD2.
3. Select the protective profile control should activate
after LS action: Normal Profile, Alternate Profile 1,
Alternate Profile 2, or Alternate Profile 3.
4. Alternate Profile/Switch Mode allows user to select
whether control makes No Change, latches onto
alternate profile or momentarily switches to the
alternate profile setting for duration of momentary
function delay TD2.
5-85
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-86
!
SAFETY
S280-70-21
FOR LIFE
Switch/Sectionalizer Mode
General Overview
With introduction of ProView 5.0, the Form 6 is capable of
being operated in switch mode, or sectionalizer mode. These
modes can be applied for both Form 6 and Form 6 Triple
Single. The definition of both modes is defined below:
Switch Mode
All overcurrent protection is disabled in the control, and the
recloser will behave as a switch only. When the Switch Mode
Workbench Structure is loaded into the scheme, Alternate
Profile #2 enables Switch Mode. The remaining profiles avail-
able for use are Normal, Alternate Profile #1, and Alternate
Profile #3 only.
Sectionalizer Mode
All overcurrent protection is disabled in the control, and
the recloser will behave as a sectionalizer only. When the
Sectionalizer Workbench Structure is loaded into the scheme,
Alternate Profile #3 enables Sectionalizer Mode. The remain-
ing profiles available for use are Normal, Alternate Profile #1,
and Alternate Profile #2 only.
Note: There is an existing Switch/Sectionalizer Mode Workbench
Structure available which allows the Form 6 to have the
Switch Mode and Sectionalizer Mode loaded onto the con-
trol. Alternate Profile #2 is for Switch Mode, and Alternate
Profile #3 is for Sectionalizer Mode only. The remaining pro-
files available for use are Normal, and Alternate Profile #1
only.
5-87
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-88
!
SAFETY
S280-70-21
FOR LIFE
Switch Mode
For Non-Triple Single, select and open: WBI-Form6-
Switch.sch
5-89
Form 6 Microprocessor-Based Recloser Control Programming Guide
Sectionalizer
For non-Triple Single, select and open: WBI-Form6-
Sectionalizer.sch
5-90
!
SAFETY
S280-70-21
FOR LIFE
5-91
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-92
!
SAFETY
S280-70-21
FOR LIFE
5-93
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-94
!
SAFETY
S280-70-21
FOR LIFE
5-95
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-96
!
SAFETY
S280-70-21
FOR LIFE
5-97
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-98
!
SAFETY
S280-70-21
FOR LIFE
5-99
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-100
!
SAFETY
S280-70-21
FOR LIFE
5-101
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-102
!
SAFETY
S280-70-21
FOR LIFE
5-103
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-104
!
SAFETY
S280-70-21
FOR LIFE
5-105
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-106
!
SAFETY
S280-70-21
FOR LIFE
5-107
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-108
!
SAFETY
S280-70-21
FOR LIFE
5-109
Form 6 Microprocessor-Based Recloser Control Programming Guide
5-110
!
SAFETY
S280-70-21
FOR LIFE
5-111
Form 6 Microprocessor-Based Recloser Control Programming Guide
!
All Cooper logos, Cooper Power Systems, Kyle, Communications
Workbench, Idea Workbench, ProView, TCC Editor, Virtual
Test Set, and PeerComm are valuable trademarks of Cooper
Industries in the U.S. and other countries. You are not permitted
to use Cooper trademarks without the prior written consent of
Cooper Industries. SAFETY
Microsoft Windows, Windows NT, and Windows Vista FOR LIFE
are either registered trademarks or trademarks of Microsoft
Corporation in the United States and/or other countries.
Intel and Pentium are registered trademarks of Intel
Corporation in the U.S. and other countries.
Acrobat and Reader are either registered trademarks or trade-
marks of Adobe Systems Incorporated in the United States and/
or other countries.
IEEE Std C37.111-1999 standard is a trademark of the
Institute of Electrical and Electronics Engineers, Inc. (IEEE). This
product is not endorsed or approved by the IEEE.
IEEE is a registered trademark of the Institute of Electrical
and Electronics Engineers, Inc. (IEEE). This publication is not
endorsed or approved by the IEEE. 2300 Badger Drive
One Cooper | www.cooperpower.com | Online Waukesha, WI 53188