Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

A Booster

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

BOOSTER

PUMP
CONTROLLERS

BOOSTER PUMP CONTROLLERS


Booster pump controllers are installed to automatically SIMPLEX - DUPLEX - TRIPLEX
start and stop pump motor(s) on system demand in order
to maintain a constant pressure in a pressurized water
supply system. System demand can be detected by
pressure (standard) or current sensing (option).

The completely assembled and wired controllers are


factory tested before shipping. All components used in
Tornatech booster pump controllers are CSA listed and
UL approved.

Tornatech favors fuseless motor protection for easy field


maintenance.

STANDARD FEATURES included in SIMPLEX, DUPLEX


and TRIPLEX BOOSTER CONTROLLERS:
SIMPLEX

TRIPLEX
DUPLEX

STANDARD FEATURES

NEMA/CSA 1
enclosure ASA 61 grey 1 1 1

Main disconnect switch (HP rated)


c/w door interlocked handle 1 1 1

Thermomagnetic motor protector(s)


(Overload & Short circuit protection)* 1 2 3

Across-the-line contactor(s) (HP rated) 1 2 3

Control transformer 120V.


secondary c/w secondary fuse 1 1 1

''Power On'' white pilot light 1 1 1

''Run'' green pilot light(s) 1 2 3

''Low suction'' red pilot light Opt. 1 1

''Hand-Off-Auto'' selector switch(es) 1 2 3

Pressure switch(es) adjustable


for start-stop pump ** 1 1 2

Pressure switch adjustable for


low suction pressure shut-off ** Opt. 1 1

Run period adjustable timer(s) 1 1 2

Provision for aquastat/solenoid circuit 1 1 1

Automatic transfer to non-operating pump


in case of motor overload or short circuit N/A 1 1

* Replaced by single pole circuit breaker(s) and overload


relay(s) in single phase controllers.
** For clean water condition only.
BOOSTER
PUMP CONTROLLERS
BOOSTER PUMP CONTROLLERS SEQUENCE OF OPERATION:

SIMPLEX - DUPLEX - TRIPLEX SIMPLEX booster pump controller


Upon pressure drop as detected by discharge
OPTIONAL FEATURES AVAILABLE pressure switch, the pump starter is energized and
(Contact factory for details.): the pump starts
Upon re-establishment of system pressure, the run
Current sensing relays instead of pressure period timer is activated.
switch(es) Upon expiration of the run period timer delay, the
Various types of pressure switch(es) pump motor stops.
Time delays for various applications If during the run period timer the pressure drops,
Pilot lights and alarm contacts for different the timer is reset.
conditions such as overload, high pressure
Elapsed time meter(s)
Various types of enclosure: NEMA CSA 12, DUPLEX booster pump controller
NEMA CSA 4, Lead pump runs continuously.
Circuit breaker(s) instead of horsepower rated Upon pressure drop as detected by discharge
disconnect switch(es) pressure switch, the lag pump motor is energized
Ammeter(s) single phase or three phase and the lag pump starts.
Various manual alternations (duplex or triplex Upon re-establishment of system pressure, the run
controllers only) period timer starts counting.
Various automatic alternations (duplex or triplex
Upon expiration of the run period timer delay, the
controllers only)
No flow shut down (duplex or triplex controllers only) lag pump motor is de-energized and the lag pump
Low level shut down (duplex or triplex controllers stops.
only) If during the run period timer countdown the
High and low safety pressure shutdowns pressure drops, the timer is reset and the pump
keeps running until pressure is restored.
Start-up instructions:
TRIPLEX booster pump controller
Check name plate rating of booster pump controller and Lead pump runs continuously.
compare with incoming voltage and motor(s) rating(s). Upon pressure drop as detected by discharge
Adjust overload setting to full motor current rating. pressure switch, the first lag pump motor is
Check that motor protector push actuators are in start energized and the first lag pump starts.
position. If pressure cannot be re-established, the second
Check that water pressure switches are adjusted to lag pump motor is energized and the second lag
proper system pressure. Make sure water supply is pump starts.
available. Upon re-establishment of system pressure, the
Check that controller is properly connected to pump second run period timer starts counting.
motor(s). Upon expiration of the second run period timer
Turn Hand-Off-Auto selector switch(es) to Off position. delay, the lag pump motor is de-energized and the
Switch main disconnect switch to On position. second lag pump stops.
Turn Hand-Off-Auto selector switch(es) to Hand position. Upon re-establishment of system pressure, the
Pump motor(s) should start. Check motor rotation. first run period timer starts counting.
If all above checks out correctly, turn Hand-Off-Auto Upon expiration of the first run period timer delay,
selector switches to Auto position. the first lag pump motor is de-energized and the
first lag pump stops.
If during the run period timer countdown the
pressure drops, the timer is reset and the pump
keeps running until pressure is restored.
HOW TO ORDER: AB - V / C x HP / Ph / Hz
Ex.: DB3 - 480 / 2 x 7.5 / 3 / 60
A = SB simplex B = 1 single phase(120V) V = 120 C = 1 one pump HP = anything Ph = 1 single phase(120V) Hz = 50
DB duplex 2 single phase(240V) 208 2 two pumps between 2 single phase(240V) 60
TB triplex 3 three phase 240 3 three pumps .25 and 50 3 three phase
380
415
416
480
600

For dimensions or other voltages and HP, please contact factory.


Tornatech inc., 7075, Place Robert-Joncas, # 132, Montreal, Quebec, Canada H4M 2Z2
9BRO901.BOOSTER Rev.0
Tel.: 1 514 334 0523 1 800 363 8448 (Canada & U.S.A.) Fax: 1 514 334 5448 SUBJECT TO MODIFICATION WITHOUT NOTICE
E-mail: tornatech@tornatech.com www.tornatech.com All rights reserved. Printed in Canada

You might also like