Cooper Loadbreak Elbow 500287
Cooper Loadbreak Elbow 500287
Cooper Loadbreak Elbow 500287
Connectors
Electrical Apparatus
200 A 25 kV Class Loadbreak Elbow Connector with
Optional Integral Jacket Seal 500-28-7
general
The Cooper Power Systems Loadbreak
Elbow Connector is a fully-shielded
and insulated plug-in termination for
connecting underground cable to
transformers, switching cabinets and
junctions equipped with loadbreak
bushings. The elbow connector
and bushing insert comprise
the essential components of all
loadbreak connections. The Cooper
Elbow Connector is a fully rated
200 A switching device, designed
in accordance to IEEE Std 386™
standard - latest revision.
Cooper Loadbreak Elbows are molded
using high quality peroxide-cured
insulating and semi-conducting EPDM
rubber. Standard features include a
coppertop connector, tin-plated copper
loadbreak probe with an ablative
arc-follower tip and stainless steel
reinforced pulling-eye. An optional
capacitive test point, made of corrosion
resistant plastic, is available for use
with fault indicators (see Catalog
Section 320-40 and 320-42).
Cable ranges are designed to accept
a wide range of cable conductor and
insulation sizes with just three elbows
and accommodate cable manufactured
to either AEIC or ICEA standards.
The coppertop compression connector
is a standard item to transition from
the cable to the loadbreak probe. An
aluminum crimp barrel is inertia-welded
to a copper lug. The aluminum barrel
makes the connector easy to crimp
and the copper lug ensures a reliable,
tight, cool operating connection with
the loadbreak probe.
Optional Integral
Jacket Seal*
The optional integral jacket seal
provides a quick and easy means of
sealing the cable jacket to prevent
moisture ingress. Our jacket seal
is molded to the loadbreak elbow Figure 1 Figure 1A
eliminating the need for separate
cable sealing products. It’s
available with braided ground strap/
bleeder wire for terminating Tape
shielded cable. (See Figure 5.) Figure 1.
Loadbreak Elbow Connector with optional integral jacket seal and without test
point.
Figure 1A
*US Patent 7,661,979 Loadbreak Elbow without jacket seal and with test point.
INSULATION
semi-conductive insert High-quality peroxide-cured EPDM rubber formulated, mixed, and
High-quality peroxide-cured EPDM rubber milled in-house for consistent and reliable field performance.
creates a smooth surface around the “current semi-conductive shield
interchange” to evenly distribute electrical High-quality peroxide-cured EPDM rubber provides protective
stress within the insulation. deadfront shield that meets requirements of IEEE Std 592™
pulling eye standard.
Stainless steel reinforced
for positive shotgun stick
switching operations.
loadbreak probe
Tin-plated copper probe with arc-ablative
tip (arc follower) provides dependable
loadbreak switching characteristics.
Figure 2.
Elbow cutaway illustrates design features.
2
500-28-7
S Dim. 25 kV
S3 3.86”
(98.04 mm)
S4 S4 4.54”
(115.32 mm)
S3
S5 3.14”
S6 (79.76 mm)
S6 1.64”
(41.66 mm)
S5
Figure 3.
Elbow profile and stacking dimensions as referenced in IEEE Std 386™ standard.
— 40 kV
Minimum Corona Voltage Level
— 19 kV
Test Point Voltage Test
3
200 A 25 kV Class Loadbreak Elbow Connector with Optional Integral Jacket Seal
4
500-28-7
TABLE 4
Conductor Size and Type
Class B Stranded or
Compressed Compact or Solid Conductor
AWG mm2 AWG mm2 Code
No Connector 00
#6 16 #4 — 01
#4 — #3 25 02
#3 25 #2 35 03
#2 35 #1 — 04
#1 — 1/0 50 05
1/0 50 2/0 70 06
2/0 70 3/0 — 07
3/0 — 4/0 95 08
4/0 95 250 120 09
250* 120 300 — 10
*Compressed stranding only.
Note: Coppertop compression connector may be used on both aluminum and copper cable conductors.
5
200 A 25 kV Class Loadbreak Elbow Connector with Optional Integral Jacket Seal
TABLE 5 TABLE 6
Replacement 2.88” Long Coppertop Connectors Replacement Parts
Conductor Size Description Catalog
Number
Concentric or Compressed Compact or Solid
Catalog Loadbreak Probe Installation
AWG mm2 AWG mm2 Number Tool 2602733A01
#6 16 #4 — CC2C01T Loadbreak Probe Only 2637794B01
#4 — #3 25 CC2C02T Probe Kit (includes
#3 25 #2 35 CC2C03T Probe, Installation Tool, PK225
Silicone Lubricant,
#2 35 #1 — CC2C04T Installation Instruction Sheet)
#1 — 1/0 50 CC2C05T Silicone Grease
0.175 oz tube (5 grams) 2603393A03
1/0 50 2/0 70 CC2C06T 5.3 oz tube (150 grams) 2605670A02M
2/0 70 3/0 — CC2C07T Test Point Cap 2605725A54
3/0 — 4/0 95 CC2C08T Includes Ground Braid,
Constant Force Spring and
4/0 96 250 120 CC2C09T Mastic GRDBRAIDKIT
250* 120 300 — CC2C10T
* Compressed stranding only.
Note: Coppertop compression connector may be used on both aluminum and copper cable conductors.
accessories
Figure 5.
Braided ground strap kit.
6
500-28-7
7