Gu3311 Operation Manual
Gu3311 Operation Manual
Gu3311 Operation Manual
Manual
GU3310 / GU3311
Genset Controller
HM1077ER1
Manual HM1077ER1 The Interpretation of the Symbol
WARNING:
A WARNING indicates a potentially hazardous situation which, if not
avoided, could result in death, serious personal injury or property damage.
CAUTION:
A CAUTION indicates a potentially hazardous situation which, if not avoided,
could result in damage to equipment or property.
NOTE:
A NOTE provides other helpful information that does not fall under the
warning or caution categories.
Harsen I
Manual HM1077ER1 The interpretation of the Symbol
WARNING:
Read this entire manual pertaining to the work to be performed before
installing, operating, or servicing this controller. Practice all plant and safety
instructions and precautions. Failure to follow instructions can cause
personal injury and/or property damage.
The engine or other type of prime mover should be equipped with an overs
peed shutdown device to protect against runaway or damage to the prime
mover with possible personal injury, loss of life, or property damage.
The over speed shutdown device must be totally independent of the prime
mover control system. An over temperature or low pressure shutdown device
may also be needed for safety, as appropriate.
CAUTION:
To prevent damage to a controller that uses an alternator or battery-charging
device, make sure the charging device is turned off before disconnecting the
battery from the system.
CAUTION:
Controllers contain static-sensitive parts. Observe the following precautions
to prevent damage to these parts:
Do not disassemble the rear of the controller and touch the components or
conductors on the printed circuit board.
CAUTION:
Controller has been set at Harsens standard before delivery. The setting
should be checked before starting the generator to confirm it meets the
actual application.
Harsen II
Manual HM1077ER1 History
History
Harsen III
Manual HM1077ER1 Contents
Contents
1. Description ........................................................................................................................................5
3. Panel Operation................................................................................................................................13
7. Parameter Settings...........................................................................................................................23
Harsen IV
Manual HM1077ER1 Description
1 Description
The GU3310 and GU3311 are a new generation on single generating set intelligent controller
which is new in shape and structure. It has improved the performance of the controller so that the new
product can meet the needs of the user and Generator assembly plants for the different types of
Automatic switch control generation and protection needed.
GU3310 is a Auto Start controller.
GU3311 is an Automatic Mains Failure Controller. When running in AUTO mode, it detects the
Mains. It starts the generator automatically on Mains voltage failure. The Gen is on load; when Mains
resumes to normal, it stops the generator after the delay, Mains is on load.
Characteristics:
l The voltage and current using true RMS measuring.
l Multi-Language menu.
l 128 x 64 graphic LCD.
l Unit maintenance time, presets and remind function.
l 3 Analogue inputs configurable with a variety of preset sensors and can also customize your
own sensor curves.
l 5 Configurable outputs.
l 3 Configurable inputs.
l Buttons on control panel are used for selecting control modes, starting and stopping the
operating procedure, displaying data and modifying the parameters. LED indicators are used
for indicating the operation mode of controller and the running status of Genset, and LCD
displays each measuring parameter and status.
l The controller can be connected to a PC and can read and set the running parameters of
controller.
l Optional Canbus, read and control the parameters for an ECU engine.
l All connections of the controller are by secure plug and socket, for ease and convenience to
connect, move, maintain and replace the device. When secured by the screw locks it prevents the
plugs from falling out by vibration etc.
This manual is only suitable for GU3310/GU3311, user must carefully read this manual first.
GU3310 controller
GU3311 controller
NOTE:
l Only GU3311 has port #5, #6, #7, #8.
3 phase 4 wire
3 phase 4 wire
3 phase 4 wire
3 phase 4 wire
3 Panel Operation
The operation panel consists of 3 sections: LCD display indicating measurement parameters, LED
indicator for common failure, and push buttons for Genset and selection of control modes.
LCD with 128*64 pixels can display multi-line data in the same time. LCD also has a backlight so
that the operator can clearly read information day or night. After pressing any button the backlight will
automatically turn off after a preset time.
The LCD display and its control push buttons provide a user friendly operational interface for the
operator to easily control the Genset, read information and parameter setting.
Scroll Button
Scroll menu for parameters display/ enter into or exit parameters setting by
pressing and holding this button for 2sec.
Operation Description
Press and hold the AUTO button, the LED above the button is
illuminated; the controller is running in AUTO mode.
Press and hold the MAN button, the LED above the button is
illuminated; the controller is running in MAN mode.
NOTE:
l Only 1 mode can be selected from above 2 modes.
l Controller keeps the states for the previous mode when changing the
operation mode, then implements the control procedure of the next mode
according to the present states.
NOTE:
l If a digital input has been set as "panel lock" and is activated, This will not
change the operation mode of the controller.
WARNING:
l When the Mains normal LED is illuminated it means that both voltage and
frequency of Mains are within the range of preset values; When the Mains
normal LED flashes means either voltage or frequency of the Mains are over
the range of preset values; If the Mains normal LED does not illuminate it
means that the Mains voltage is lower than 10% of the rated voltage.
l Do not assume the Mains is not available if Mains normal LED does not
illuminate, it may be still available but outside set parameters.
Mains Fail to load: If Mains close/open relay is closed the Mains fail to Load timer is activated
when it times out if the controller does not receive the Mains switch auxiliary contact feed back signal
then Mains fail to Load alarm is activated.
NOTE:
l The Above control procedure assumes that one of configurable inputs has
been configured as Mains Aux.Switch Closed and connects the ATS
switchs N.O. Aux. contact signal to this input.
l If you do not configure an input as Mains Aux.Switch Closed when the
MCB closed LED illuminates is only an indication that the circuit breaker
close/open relay should have been closed under this condition, the
alarm for Mains fail to load is inactive.
l If you do not configure a relay as Mains close/open, the controller without
power supply program, only has Mains parameter detection and display as
Mains status display and generator boot request condition.
The Start delay timer is activated, when it times out the preheat relay output is energised (if preheat
function selected), the timer starts. When it times out the fuel relay output is energised and operates the fuel
solenoid of the engine. After 300ms delay the start relay output is energized and the starter motor engages
and begins to crank the engine. When the engine speed reaches the crank disconnect speed the start relay
output is de-energised and the safety-on delay time starts. When the safety-on times out if the controller
detects that the parameters of the Genset such as voltage, frequency, oil pressure, coolant temperature are
normal and no other failure is detected this indicates the Genset has successfully started and running
normally. The LCD displays the Genset Measurement Parameters.
If you selected idle function, the idle relay will be closed at the same time as the crank relay is
closed, the idle timers will begin counting down after successful start up, when it times out, the idle
relay open, other procedure is the same as above.
NOTE:
l Controller will not detect under voltage, under frequency, under speed, and
charge failure during idle period.
l When no one input port as defined as remote start, the "remote start"
signal is not as boot judgment condition.
NOTE:
The start motor will power off while cranking if there are one of the following
conditions occur :
l The generator frequency reaches the preset value;
l The speed reaches crank cut off value;
l Generator Voltage reaches the crank cut off value (optional);
l Charger voltage reaches crank cut off value (optional);
l Oil pressure switch is opened and delay counter times up (optional);
l Cranking times up.
Controller can not implement crank procedure in one of following conditions:
l The generator frequency reaches the preset value;
l The speed reaches crank cut off value;
l Generator Voltage reaches the crank cut off value (optional);
l Oil pressure switch is opened or oil pressure is higher than crank cut off value (optional).
CAUTION:
l If magnetic pickup is not used, since the engine cranking cut off signal is
sensed from the generator frequency. To avoid damage to the start motor
please make sure the output voltage is higher than the controller can
measure the voltage value while cranking.
Repeat Crank: During the crank period, if the engine does not fire the start relay output de-energises
and crank rest timer begins. Once crank rest timer times out the start relay energises once again and will
attempt to start engine again. The above procedure will be repeated until it was successful start up or
reaches the configured number of crank cycles.
If any shutdown alarm occurs during crank the controller will stop cranking immediately the genset only can
be restarted after clearing the failure.
Start Failure: The above procedure will be repeated until it reaches the configured number of
crank cycles. The crank relay output is then de-energised and locks out as Fail to Start. The failure
LED illuminates and the LCD displays Fail to Start.
CAUTION:
l If Fail to Start occurs the operator must check the whole Genset system to
find reason for failure, only after clearing the failure can STOP / RESET
button to reset fault lock out status, and restart the Genset.
NOTE:
l Effective remote no-load start input, or dispatch mode set to no-load,
generator only no-load operation
l The generator switching command is only achieved after the safety
inspection delay timer is over.
l If not a switch input port is defined as a Generator closed auxiliary contact,
then, the GEN. GCB led is illuminated only expresses the GCB relay
output of the controller ..
At the same time as the Mains close/open relay is energised the timer for cooling down delay is activated
when it times out the fuel relay de-energises, generator stops and recovers to its standby status.
After the Gen points brake and Mains power supply to normal, cooling time delay start the countdown, the
controller fuel relay action after timing end, disconnect instantly fuel solenoid valve, generator outage into standby mode.
Stop Failure: When cool down times out, if the controller detects that the voltage and frequency of
the generator or oil pressure are greater than the internally set values, the fail to stop delay timer begins.
When it times out the failure LED illuminates and the LCD displays Fail to stop.
NOTE:
l After stop failure, the controller will not energise the crank relay output if
the failure has not been removed and the controller reset.
4.4 The start and stop Sequence of engine with fuel solenoid is N. O. type (energise to stop):
There are two kind of fuel solenoids for an engine, one is N.C. type, the valve of this solenoid is
closed when the engine is in standby and it can be opened by switching on by power; another is N.O.
type, the valve of this solenoid is opened when engine is in standby and it can be closed by switching
on by power. All control sequence above are for N.C. type.
NOTE:
l Controller will not detect under voltage, under frequency, under speed, and
charge failure during idle period.
For preheat mode 1 to 3, please refer to the flow chart for start and stop for Preheat control levels.
For preheat mode 4 to 6, preheat function is active immediately when the controller is power up.
During crank attempt the preheat relay output will not energise in any of above modes.
CAUTION:
l We normally dont recommend using the second method to solve this
condition.
l Play attention on the installation of PB switch to avoid cranking when the genset is
running.
6 Alarm level
The controller configuration has different levels of alarm users can set according to the actual
application requirement. Different level configurations are shown in the table below
1 WarningThis warning does not interrupt equipment operation, does not send the public
alarm, LCD displays the warning content, Also this triggers a relay action so it can produce
a warning external to the unit itself, no other control behavior occurs.
Yes Yes No No
WarningThis warning does not interrupt equipment operation, public "warning" LED light
2 and audible buzzer sounds, LCD displays the warning content, Also this triggers a relay
action so it can produce a warning external to the unit itself no other control behavior
occurs.
Yes Yes Soft unloading No
3 WarningPublic "warning" LED light and buzzer sound, the controller performs uninstall
program and opens GCB, LCD displays warning content, Also this triggers a relay action
so it can produce a warning external to the unit itself, the generator does not stop.
4 Stop faultPublic "warning" LED light and buzzer Sound, the controller performs uninstall
program and opens GCB, the generator stops after cooling down, LCD displays fault
contents. Fault can be reset after the confirmation alarm.
5 Stop faultPublic "warning" LED light and buzzer Sound, immediately opens GCB, the
generator stops after cooling down, LCD display fault contents. Fault can be reset after
troubleshooting.
6 Stop faultPublic "warning" LED light and buzzer Sound, immediately opens GCB, the
generator instantly shutdown without cooldown, LCD display fault content. Fault can be
reset after the troubleshooting.
No No No No
0
Control: Only as a control condition, trigger relevant control command.
NOTE:
l Warning level alarm is a non-serious fault condition and does not
constitute a hazard to the Genset if only temporary but the operator must
pay attention to the condition and solve it immediately to ensure
continuous operation of the machinery. A warning does not lock the
system or stop it and will discharge automatically when the fault is cleared.
l With the Shutdown alarm the system will lock the fault must be cleared
and the rest button discharged before the Genset will restart
7 Parameters Setting
7.1 SYSTEM:
NO. Items Value Range Preset
1.0 Quit
1.1 Language
1.2 Password 0000 to 9999
1.3 Pressure unit 0Bar / 1 PSI 0
1.4 Temperature unit 0 / 1 0
1.5 Comm. address 1 to 247 1
1.6 Startup mode 0 manual / 1 automatic / 2 finally 0 0
1.7 CT ratio 5:5 to 6000:5 1000:5
1.8 PT ratio 1.0:1 to 10.0:1 1.0:1
1.9 Rated voltage 45 to 3000VAC 220V
1.10 Rated current 1 to 6000A 1000A
1.11 Voltage type 1 to 5 / Do not use 1
1.12 Display contrast 1 to 9% 5
1.13 Display brightness 1 to 9% 5
1.14 Saving brightness 0 to 9% 1
1.15 Auto scroll time 1 to 60S / Do not use Do not use
1.16 Starting alarm 0 no / 1 yes 0
1.17 CB close pulse 0 to 60 seconds /0 continuous 0
1.18 Reset to MAN 0 no / 1 yes 0
1.19 Default settings
Menu descriptions:
Language
l Used to select the Language which is displayed on the LCD.
Password
l There are 3 levels of password (CL0/CL1/CL2) for different users.
l CL0 for the operator, who can read parameters, start and stop controller. The default setting is no
password.
l CL1 for the technician, who have the authority of CL0 and can modify all parameters, the default setting
is 2213.
l CL2 for factory, who have the authority of CL1 and on-line update, the default setting as 3132.
l All passwords are automatically inactive 60 seconds after exiting menu.
Pressure unit
l Used to define oil pressure unit which is displayed on the LCD. 0 stand for Bar, 1 stand for PSI.
l Transfer formula: P[psi] =P[bar]*14.503.
Temperature unit
l Used to define temperature unit which is displayed on the LCD. 0 stand for , 1 stand for .
l Transfer formula: T[]=(T[]*1 .8)+32.
Comm. address
l Used to configure ID address for MODBUS
l Each controller on the same MODBUS has a unique communication address.
Startup mode
l Used to configure the begin control mode of controller when it is powered up.
l When parameter is configured as 0, the controller will be in Manual mode when it is powered up.
l When parameter is configured as 1, the controller will be in Automatic mode when it is powered up.
l When parameter is configured as 2, the controller will be in the mode which is the same as last
time when it is powered up.
CT ratio
l The current is derived from CT on generator or load. Secondary current on CT is fixed at 5A.
l Used to calculate for load: AKWKVARPF.
l Used for shutdown alarm: over/under current, etc.
PT ratio
l Definition Gen and Mains Voltage transformer turns ratio of the primary and secondary.
l used to Gen and Mains of Measurement computing: VHZKWKVARPF.
l Used to trigger for setting limits: high / low voltage, etc.
Rated voltage
l Used to define the rated voltage (phase to neutral) of Gen and Mains,
l Reference value for judging over/under voltage.
Rated current
l Used to define the rated current of Gen and Mains.
l Reference value for judging over current.
Voltage type
l There are 5 kinds of voltage type: Y 3P4W, 3P4W, 3P3W, 2P3W, 1P2W.
l 1 Y 3P4W (3 phases 4 wires):
l Relevant electrical parameter is invalid when the parameter is set to "do not use", controller does
not measure and display the parameters.
Display contrast
l Used to adjust the display contrast of the LCD.
Display brightness
l Used to adjust the backlight brightness with the operation panel and GEN operation of the LCD.
Saving brightness
l Used to adjust the backlight brightness when on standby state of the LCD.
l Start to scroll automatically 30 seconds after not pressing any button.
Starting alarm
l When parameter is configured as 0, the controller didn't make the noise alarm before the
generator start.
l When parameter is configured as 1, the controller star the generator will be made the noise alarm
when in startup time delay and the preheating.
CB close pulse
l When parameter is configured as continuous, the controller switching relay has been output,
unless the controller failure or points brake command.
l When parameter is configured as numerical, the relay closed output after the controller sending
the switching command. Timer timing, the closing relay off when the accumulated time reaching to
a set pulse time.
Reset to MAN
l When parameter is configured as 1, the controller happen stop fault, fault state lock. Press the
reset button when the fault eliminate, the controller will switch to MAN mode no matter in any
mode before.
l When parameter is configured as 0, the controller happen stop fault, fault state lock. Press the
reset button when the fault eliminate, the controller keeping to the original pattern.
CAUTION:
l When the Reset to MAN set to 0, press the reset button after automatic
mode, Generator may not have any warning start when the start conditions
meet.
Default settings
l All parameters are resumed to default setting.
7.2 GENERATOR:
NO. Items Value Range Preset
2.0 Quit
2.1 GEN V-monitor type 0 phase - phase /1 Phase - zero 1
2.2 GEN-V under 1
Function 0 no / 1 yes 1
Limit 20 to 200% 90%
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 2
2.3 GEN-V under 2
Function 0 no / 1 yes 0
Limit 20 to 200% 0%
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 5
2.4 GEN-V over 1
Function 0 no / 1 yes 0
Limit 20 to 200% 115%
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 2
2.5 GEN-V over 2
Function 0 no / 1 yes 0
Limit 20 to 200% 999%
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 5
2.6 GEN-Hz under 1
Function 0 no / 1 yes 1
Limit 10.0 to 100.0Hz 48.0Hz
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 2
2.7 GEN-Hz under 2
Function 0 no/1 yes 0
Limit 10.0 to 100.0Hz 0.0Hz
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 5
2.8 GEN-Hz over 1
Function 0 no/1 yes 1
Limit 10.0 to 100.0Hz 55.0Hz
Delay 0 to 999S 5S
Delay by 0 to 3 3
ALM. class 0 to 6 2
Menu descriptions:
GEN V-monitor type
l Used to choose the controller is phase - phase or phase - zero voltage as mains voltage monitoring object.
l Choose the controller is phase - phase or phase zero in different voltage input type, detection of
the different voltage, specific as follows table:
Parameters
Phase Phase Phase Zero
Voltage type
Y 3P4W VL1L2VL2L3VL3L1 VL1NVL2NVL3N
3P4W VL1L2VL2L3VL3L1 VL1NVL2NVL3N
3P3W VL1L2VL2L3VL3L1
2P3W VL1L2 VL1NVL2N
1P2W VL1N
GCB close
l Controller has to monitoring the Gen switch close, breakdown and control. E.g. to choose 1/2/3 alarm
level, when protection function activates, LCD displays !W:GEB close, to choose 4/5/6 alarm level,
when protection function activates, LCD displays !A:GEB close.
GCB open
l Controller has to monitoring the Gen switch open, breakdown and control. E.g. to choose 1/2/3 alarm
level, when protection function activates, LCD displays !W:GEB open, to choose 4/5/6 alarm level,
when protection function activates, LCD displays !A:GEB open.
NOTE:
If the GCB close and GCB open monitoring function effectively, must satisfy:
l One of the relay is defined as "Gen close/open".
l One of the switch input is defined as "Gen closed auxiliary contacts".
GEN. loading Hz
l Used to configure the frequency trigger value of the GCB close.
GEN. on delay
l Used to set from meet the loading condition to Gen automatic closed power supply delay time.
7.3 ENGINE:
NO. Items Value Range Preset
3.0 Quit
3.1 Engine type 1 diesel /2 ECU/3 gas 1
3.2 ECU type 1 to 20 1
3.3 Engine rated speed 99 to 9999RPM 1500
3.4 MPU input 0 no /1 yes 0
3.5 Fly wheel teeth 5 to 300 120
3.6 Set pickup now .
3.7 Pair of poles 1 to 8 2
3.8 Fuel mode 0 NC/1 NO 0
3.9 Start delay 0 to 999S 0S
3.10 Crank attempts 1 to 10 3
3.11 Critical C-attempt 1 to 20 time 6 time
3.12 Crank time 1 to 99S 8S
3.13 Crank time add 1 to 99S / Do not use Do not use
3.14 Crank reset time 1 to 300S 15S
3.15 Ignition speed 1 to 9999 RPM 200RPM
3.16 Ignition speed DLY 1 to 999S 5S
3.17 Gas valve on DLY 0 to 999S 5S
3.18 Crank cutout RPM 1 to 9999 RPM 300RPM
3.19 Crank cutout volt 1 to 100% / Do not use 85%
3.20 Crank cutout ALT-V 1.0 to 40.0 V / Do not use Do not use
3.21 Crank cutout Oil-P 0.1 to150.0Bar/PSI / Do not use 2.2
3.22 Crank cutout P-DLY 1 to 60S / Do not use Do not use
3.23 Idle time 1 to 9999S / Do not use Do not use
3.24 Pre-heat mode 1to 6 6
3.25 Pre-heat time 1 to 9999 / Do not use 3S
3.26 Safety-on delay 0 to 600S 10S
3.27 Cool down mode 0 At full speed /1 idle 1
3.28 Cool down time 0 to 9999S 300S
3.29 Stop time 0 to 60S 20S
3.30 EX. Crank permit 0 no/1 yes 0
3.31 Charge failure
92
Function 0 no/1 yes 1
Limit 0.0 to 40.0 8.0V
ALM. class 0 to 6 2
3.32 Pickup signal
100
Function 0 no/1 yes 1
Delay 0 to 999S 1S
Delay by 0 to 3 1
ALM. class 0 to 6 2
3.33 Overspeed level1
8.0V
Function 0 no/1 yes 1
Limit 1 to 19999RPM 1600RPM
Delay 0 to 999S 1S
Delay by 0 to 3 1
ALM. class 0 to 6 2
Menu descriptions:
Engine type
l Use in selection controller control object engine type.
l If the parameter is set to "1", is a traditional diesel engine. When the parameter is set to "2", is to
use the ECU of the engine. When the parameter is set to "3", is a traditional gas engine.
l When the control object is ECU engine, the controller will also activate "ECU warning", "ECU
failure", "ECU data fault."
l Diesel engine.
Start order:
Started delay began timing, when timing end, the preheating relay closed output as preset
Preheat function. Preheat time began timing, when timing end, fuel relay action and the engine fuel
electromagnetic valve open. After delaying 300Ms, crank delay closed output. Crank began, when
engine running speed reach the crank cutting speed, the crank stop and the engine run.
Engine no ignition as turning time period, the crank stopped. Crank intermittent time to begin, try
to start the engine again after the end of time. Above the boot sequence repeated until the engine was
successfully ignited. When you start the crank reaches the preset number, the controller will stop start
control outputs and the LCD liquid crystal display "failed to start".
Stop order:
Cooling time began after GCB opening. When timing end, fuel relay action, the engine fuel
electromagnetic valve close and engine stop. After the end of the downtime in the engine timing, engine
fails to stop. LCD liquid crystal display, "stop failed".
l Gas engine:
Start order:
Started delay began timing, when timing end, crank relay action. Crank begin, both crank time
and ignition delay time are begin timing. Before the end of ignition delay time, engine speed reached
or higher than set of ignition speed, ignition relay electrical action. Ignition began, gas valve will open
after the end of gas valve open delay timing. When engine running speed reach the crank cutting
speed, the crank stop and the engine run.
After the end of ignition delay time, engine speed is not reached ignition speed, or after the end
of crank time, engine still not running ignition, the crank stopped. Crank intermittent time to begin, try
to start the engine again after the end of time. Above the boot sequence repeated until the engine was
successfully ignited. When you start the crank reaches the preset number, the controller will stop start
control outputs and the LCD liquid crystal display "failed to start".
Stop order:
Cooling time began after GCB opening. When timing end, gas valve closed and the engine
stopped. Ignition will stop after the engine failed to stop.
Engine fail to stop after the end of failed to stop delay. LCD liquid crystal display "stop failed".
NOTE:
l Normal shutdown procedures, to stop the ignition control output must be
after the engine shut down. Ignition output does not stop if engine fail to
stop after the end of failed to stop delay.
l Use the ECU engine, start and stop the processes controlled by the ECU, the controller can control
the power supply switch and on/off signal of ECU.
NOTE:
l If T4 is longer than T5, oil pressure protection is ignored during T5. If T4 is
shorter than T5, oil pressure protection becomes effective after T4.
MPU input
l Used to configure whether magnetic pick-up unit is used or not.
l When parameter is configured as 1, magnetic pick-up is used for the signal source of the engine
speed. When parameter configured as 0, the magnetic pick-up is not used, the engine speed is
calculated from the frequency of the generator.
l RPM = (Hz*60)/ Pair of Poles. For example: the frequency of generator is 50Hz, when Pair of Poles
configured as 2, RPM = (50*60)/2 = 1500 (RPM).
NOTE:
l This function is only used for the debug of the controller and genset.
Pair of Poles
l Used to configure the poles of excitation winding of the alternator.
l Use to calculate the engine speed with the frequency when without MPU input.
Fuel mode
l Used to configure the type of engine fuel valve (details refer to 4.6).
l N.C. type means the fuel valve is normally closed; N.O. type means the fuel valve is normally opened.
Start delay
l Used to configure the time delay from the meet open generator condition to carry out the engine
start program is energised.
l This time in the following condition start is active:
Remote open signal is active when in automatic operation mode.
l When the start delay timer is working, LCD display time course.
Crank attempts
l Used to configure how many times the controller repeat to crank the engine; this value is equal to
the maximum crank times.
Critical C-attempt
l The controller can be repeated start the engine when activate the emergency mode, the most
crank number is equal to the setting value.
Crank time
l Used to set the duration of the engine crank command.
l If this parameter is used on the diesel engine, it starts to time when crank command given
out, if used on the gas engine, it starts to time when gas valve open command given out.
CAUTION:
l The maximum crank time permit can not exceed the range of the
equipment safety.
Ignition speed
l Used to define the ignition command engine minimum speed.
l This parameter only on the gas engine is active.
Idle time
l The duration of engine idle running.
l Press the start button when the controller in the manual control mode, idle speed began to
computing time, press the start button when the controller in the automatic control mode, idle
speed began to computing time. When you choose the idle mode, the configurable relay defined as
idle output is energize, the relay recovers to open after the idle time has expired.
l When parameter is configured as not used, idle function is inactive.
Pre-heat mode
l Used to configure the mode of preheat.
l There are 6 pre-heat modes for selection, please read the description of preheat function as details.
Pre-heat time
l The preheat duration before engine crank, LCD display the time when it work.
l When parameter is configured as not used, pre-heat function is inactive.
Safety-on delay
l Used to configure the period from engine started successfully to Genset stable running.
l The protections of under speed, under voltage, under frequency, low oil pressure are disabled by
the controller during safety-on time delay.
CAUTION:
l As some of the protection are disabled during safety-on time delay, so the
safety-on delay should be set carefully and properly, this is very important,
or it may cause engine damage.
Stop time
l The maximum time permit for the engine stop.
l After the fuel relay output is de-energised (fuel relay output is energised for N.O. type fuel valve),
fail to stop delay timer begins, when it times out if controller detects generator voltage exceeds
crank disconnected voltage, or the speed exceeds crank disconnected speed, or oil pressure
exceeds crank disconnected oil pressure, then it means stop failure.
l If the fuel valve is N.O. type, the fuel relay output is de-energised after stop failure delay has expired.
Charge failure
l Controller through the "WL" port detect the auxiliary ac charging machine field contact voltage, in
order to judge whether the ac charger is working normal, when the test voltage is lower than set
limit, triggering charging failure protection function. E.g. to choose 1/2/3 alarm level, when
protection function sparks, LCD displays !W: Charge failure, to choose 4/5/6 alarm level, when
protection function sparks, LCD displays !A: Charge failure.
Pickup signal
l Controller can through the speed signal monitoring when using the pickup sensor, used to
determine whether there are speed sensor. When confirm the lost sensor signal, E.g. to choose
1/2/3 alarm level, when protection function sparks, LCD displays !W:Pickup signal, to choose
4/5/6 alarm level, when protection function sparks, LCD displays !A:Pickup signal.
If the overspeed more than the delay setting time, trigger alarm level defined action; If
Delay
the overspeed below this limit before the delay termination, delay time return to zero.
Start failure
l If the engine achieve to presetting start times still can't boot operation, instantly happen to start
failure command. E.g. to choose 1/2/3 alarm level, when protection function sparks, LCD displays
!W: Start failure, to choose 4/5/6 alarm level, when protection function sparks, LCD displays !A:
Start failure.
Stop failure
l When the controller perform to stop command, the fuel relay off output (normally open fuel, the
control relay closed output), the stop timer is activated, when it times out the controller detection to
the generator voltage is greater than the turning cutting voltage, or faster than turning cutting speed,
or oil pressure open, or oil pressure is greater than the turning cutting oil, then stop failure
happened. E.g. to choose 1/2 alarm level, when protection function sparks, LCD displays !W:Stop
failure, to choose 4/5/6 alarm level, when protection function sparks, LCD displays !A:Stop
failure.
Batt. overvolt
l Controller has a high limit protection of the battery voltage monitoring for warning, breakdown and
control. E.g. to choose 1/2/3 alarm level, when protection function sparks, LCD displays !W: Batt.
Overvolt, to choose 4/5/6 alarm level, when protection function sparks, LCD displays !A: Batt.
Overvolt.
Batt. undervolt
l Controller has a low limit protection of the battery voltage monitoring for warning, breakdown and
control. E.g. to choose 1/2/3 alarm level, when protection function sparks, LCD displays !W: Batt.
Undervolt, to choose 4/5/6 alarm level, when protection function sparks, LCD displays !A: Batt.
Undervolt.
Maintenance
l Controller cumulative the generator running time, compares with the default parameters, provide a
protection unit maintenance time limit for warning, breakdown and control. E.g. to choose 1/2/3
alarm level, when protection function sparks, LCD displays Warning: Maintenance, to choose
4/5/6 alarm level, when protection function sparks, LCD displays Fault: Maintenance.
NOTE:
l When the engine shutdown, ECU closed, means the ECU has not
communication in normal situation, but will not trigger fault protection.
l Only the CAN controller has this protection function.
ECU Warning
l When the engine ECU happens to not stop fault, this is a warning level of fault, the engine
continues to run, engine manufacturer called "yellow light alarm". Controller can trigger an alarm
action when receives this signal. E.g. to choose 1/2/3 alarm level, when protection function sparks,
LCD displays Warning: ECU warning, to choose 4/5/6 alarm level, when protection function
sparks, LCD displays Fault: ECU warning.
NOTE:
l Engine continuous running when the ECU is warning level of fault. If the
controller used this signal to trigger 4/5/6 alarm level, the controller can
control the engine shut down.
l Only the CAN controller has this protection function.
ECU Shutdown
l When the engine ECU happens to stop fault, the engine shutdown, engine manufacturer called
"red light alarm". Controller can trigger an alarm action when receives this signal. E.g. to choose
1/2/3 alarm level, when protection function sparks, LCD displays Warning: ECU stop fault, to
choose 4/5/6 alarm level, when protection function sparks, LCD displays Fault: ECU stop fault.
Menu descriptions:
P-sensor type:
l Used to configure the type of LOP-sensor.
l Built-in LOP-sensors in controller, such as the following menu:
Code Type Note
0 Do not use
1 Low oil pressure switch 1 Closed (Low level) effective
2 Low oil pressure switch 2 Open (High level) effective
3 VDO 5 bar
4 VDO 10 bar
5 Datcon 7 bar
6 Murphy 7 bar
7 Pre-set 1
8 Pre-set 2
9 Pre-set 3
10 Pre-set 4
11 configurable 1
12 configurable 2
13 configurable 3
14
15
CAUTION:
l The LOP-sensor is used to measure the oil pressure, its accuracy is very
important to the protection of the Genset, so please match the right type of
the sensor or configure the right curve of the senor. Otherwise it may
cause engine damage.
VDO 10 bar
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0
R() 10 31 52 71 90 106 124 140 155 170 184
Datcon 7 bar:
P(Bar) 0.0 0.7 1.4 2.1 2.8 3.4 4.1 4.8 5.5 6.2 6.9
P(PSI) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0
R() 240 200 165 135 115 95 78 63 48 35 25
Murphy 7 bar:
P(Bar) 0.0 0.7 1.4 2.1 2.8 3.4 4.1 4.8 5.5 6.2 6.9
P(PSI) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0
R() 240 205 171 143 123 103 88 74 60 47 33
Pre-set 1
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0
R() 15 31 49 66 85 101 117 132 149 164 178
Pre-set 2
P(Bar) 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0
P(PSI) 0 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5 145.0
R() 30 41 65 88 110 115 145 150 172 185 190
Pre-set 3
P(Bar) 0 1.7 3.4 5.2 6.9 8.6 10.3
P(PSI) 0 25 50 75 100 125 150
R() 21 36 52 72 84 100 120
Pre-set 4
P(Bar) 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
P(PSI) 14.5 29.0 43.5 58.0 72.5 87.0 101.5 116.0 130.5
R() 195 155 127 107 88 72 61 54 48
NOTE:
l Configurable means user can input the data manually according to the
sensor curve. Configurable 1 only can be set through the software;
configurable 2 or 3 can be done through the push buttons on the front
panel or software.
l When configuring, please input the resistance- measured value from
small to big one by one.
T-sensor type:
l Used to configure the type of HET-sensor.
l Built-in Temp-sensors in the controller, such as the following menu:
Code Type Note
0 Do not use
1 High temperature switch 1 Closed (Low level) effective
2 High temperature switch 2 Open (High level) effective
3 VDO 120
4 VDO 150
5 Datcon
6 Murphy
7 Pt100
8 Pre-set 1
9 Pre-set 2
10 Pre-set 3
11 Pre-set 4
12 configurable 1
13 configurable 2
14 configurable 3
15
CAUTION:
l The Temp-sensor is used to measure the coolant temperature, its
accuracy is very important to the protection of the Genset, so please match
the right type of the sensor or configure the right curve of the senor.
Otherwise it may cause engine damage.
VDO 150
T() 50 60 70 80 90 100 110 120 130 140 150
T() 122 140 158 176 194 212 230 248 266 284 302
R() 322 221 155 112 93 62 47 37 29 23 19
Datcon
T() 40 50 60 70 80 90 100 110 120 130 140
T() 104 122 140 158 176 194 212 230 248 266 284
R() 900 600 400 278 200 141 104 74 50 27 4
Murphy
T() 40 50 60 70 80 90 100 110 120 130 140
T() 104 122 140 158 176 194 212 230 248 266 284
R() 1029 680 460 321 227 164 120 89 74 52 40
PT100
T() -100 -50 0 20 40 60 80 100 150 200 300
T() -148 -58 32 68 104 140 176 212 302 392 572
R() 60 81 100 108 116 123 131 139 157 176 212
Pre-set 1
T() 20 30 40 50 60 70 80 90 100 110 120
T() 68 86 104 122 140 158 176 194 212 230 248
R() 900 600 420 282 152 113 86 62 48 40 30
Pre-set 2
T() 30 50 60 70 80 90 100 110 120
T() 86 122 140 158 176 194 212 230 248
R() 980 400 265 180 125 90 65 50 38
Pre-set 3
T() 20 30 40 50 60 70 80 90 100 110 120
T() 68 86 104 122 140 158 176 194 212 230 248
R() 805 540 380 260 175 118 83 58 42 30 21
Pre-set 4
T() 28 35 40 50 60 70 80 90 95 98
T() 82 95 104 122 140 158 176 194 203 208
R() 579 404 342 250 179 136 103 77 67 63
NOTE:
l Configurable means user can input the data manually according to the
sensor curve. Configurable 1 only can be set through the software;
configurable 2 or 3 can be done through the push buttons on the front
panel or software.
l When configuring, please input the resistance-value from small to big
one by one.
Heater on level
l The parameters used to select preheating mode 5 defined as "preheating" relay work of low
temperature limit, and set "preheating control" relay work of low temperature limit.
l The temperature sensor type can not set to be "do not use" or "switch", otherwise the
parameters will not achieve.
Cooler on level
l The parameters used to define as "cooling" relay work of high temperature limit.
l The temperature sensor type can not set to be "do not use" or "switch", otherwise the
parameters will not achieve.
l When choosing temperature sensor, the controller built-in the following temperature sensor type for
user choice, please refer to the temperature sensor type list.
Fuel pump ON
l When the auxiliary sensor uses set to "1", this parameter is valid.
l This parameter is used to define "pump control" relay closed of the fuel level low limit
l Controller detects the engine day fuel tank through the fuel sensor, when the fuel is below the
setting value, "pump control" relay close.
l Controller detects the engine day fuel tank through the fuel sensor, when the fuel is higher than the
setting value, "pump control" relay close.
AUX1 low T level 1&2
l When the auxiliary sensor uses set to "2", this parameter is valid.
l Controller has two level low temperature limit value monitoring for warning, breakdown and control.
E.g. to choose 1/2/3 alarm level, when protection function sparks, LCD displays !W:AUX1 low T
level1 or !W:AUX1 low T level2, to choose 4/5/6 alarm level, when protection function sparks,
LCD displays !A:AUX1 low T level1 or !A:AUX1 low T level2.
Heater 1 on level
l The parameters used to select preheating mode 6 defined as "preheating" relay work of low
temperature limit, and set "preheating 1 control" relay work of low temperature limit.
l The auxiliary sensor type can not set to be "do not use" or "switch", otherwise the
parameters will not achieve.
Cooler 1 on level
l The parameters used to define as "cooling 1" relay work of high temperature limit.
l The auxiliary sensor type can not set to be "do not use" or "switch", otherwise the
parameters will not achieve.
Menu descriptions:
D-Input * Config
l Used to define switch input function.
Define the role of the switch input, controller built-in functions for the user choice, such
Function
as the D-Input Config menu.
Select "0", switch input in closed (low level) effective
Logic
Select "1", switch input open effective.
If the switch quantity effective time more than the setting delay time value, trigger
Delay defined alarm level; If the switch quantitative change as invalid before the end of the
delay, delay time to zero.
Monitoring function active time range setting
Set it to be (0): work all the time
Starting point Set it to be (1): start with crank
Set it to be (2): start after the safety monitoring delay
Set it to be (3): start when running.
Used to define the trigger protection, the controller what the action happen. Detailed
ALM. class
refer to the alarm level configuration table.
Note:
l Only set to "1" in the function, which switch input function when the user
defined, time delay, the starting point and alarm level of the project such as
parameter setting is valid.
0 Not used
12 Spare
Choose this function of the switch input port connected to
13 Air-flap Closed install engine throttle auxiliary contact, through the switch
limit action to determine the working conditions of damper.
Choose this function of the switch input port connected to
install the engine preheater of the temperature switch,
14 Pre-heat temp. switch
Through the switch limit action to stop the preheating relay
output. Only used for preheating mode 4.
In the critical mode, all stop fault change to warning, the
15 Critical mode generator happens to stop fault, only alarm don't stop. LCD
screen display critical mode information.
Choose this function of the switch input signal effectively,
the controller alarm buzzer sound will stop, defined as
16 Alarm mute
"audible alarm" relay output shut down. This input signal is
the same of the controller panel "erase" button.
Choose this function of the switch input signal effectively,
17 Alarm reset
the controller remove stop fault locking.
Choose this function of the switch input signal effectively,
Generator starting and loading when the remote start signal
effectively and mains failure, Controller continue to control
Prohibit return generator operation and loading when the mains returned
18
to normal, Until the return signal to eliminate or stop fault
happens. LCD display limit return information. Only
GU3311 has this input.
19 Spare
Relay * Config
l Used to define relay output function.
Define relay output action, controller built-in functions for the user choice, such as the
Function
Relay Config menu.
Select "0", effective relay action
Logic
Select "1", effective relay not action.
0 Not used
Choose this function of the output relay is used to control the
1 Crank engine starting motor, when need the engine disk car action,
stop working when meet the crank cutting conditions.
Choose this function of the output relay is used to control the
2 Fuel diesel engine fuel electromagnet, if need to start the engine,
stop working when need to stop the engine.
Choose this function of the output relay is used to control
3 Gas valve gas engine fuel valve close/open, if need to start the engine,
stop working when need to stop the engine.
Choose this function of the output relay is used to gas
engine ignition system provides power supply or signal, it will
4 Ignition
be action when reach to ignition conditions, stop working
when the ignition delay time to stop.
Choose this function of the output relay, when there are one
5 Shutdown alarm or more stop failure action, stop working after the fault
eliminated and the fault reset.
Choose this function of the output relay, when there are one
6 Warning or more stop warming action, stop working after the fault
eliminated and the fault reset.
Choose this function of the output relay, the controller will be
7 Idle action when in idle speed calculation time, after the end of
the time to stop action.
Choose this function of the output relay action please refer to
8 Preheat output
the preheating function description.
9 Spare
10 Spare
Choose this function of the output relay, When the fuel level
below the pump open level low limit value, it will be action,
11 Fuel pump control
keep until to the fuel level arrive to pump stop level high limit
value, it will be stop action.
Choose this function of the output relay, when the generator
operation normal, engine speed, oil pressure and
12 Genset running
temperature arrive to normal parameters set limit range, it
will be action.
Choose this function of the output relay, the controller
13 Auto mode
running in the automatic operation mode action.
14 Spare
16 Spare
28 Charge failure After the charge failure, the output relay action.
It will be action when the engine fuel level is lower than low
39 Fuel low level1
fuel level 1 value and confirm delay.
It will be action when the engine fuel level is lower than low
40 Fuel low level2
fuel level 2 value and confirm delay.
It will be action when the generator voltage is lower than
41 Generator under volt level1
Gen low voltage level 1 value and confirm delay.
It will be action when the generator voltage is lower than
42 Generator under volt level2
Gen low voltage level 2 value and confirm delay.
It will be action when the generator voltage is higher than
43 Generator over volt level1
Gen high voltage level 1 value and confirm delay.
It will be action when the generator voltage is higher than
44 Generator over volt level2
Gen high voltage level 2 value and confirm delay.
It will be action when the generator frequency is lower than
45 Generator under HZ level1
Gen low frequency level 1 value and confirm delay.
It will be action when the generator frequency is lower than
46 Generator under HZ level2
Gen low frequency level 2 value and confirm delay.
It will be action when the generator frequency is higher than
47 Generator high HZ level1
Gen high frequency level 1 value and confirm delay.
It will be action when the generator frequency is higher than
48 Generator high HZ level2
Gen high frequency level 2 value and confirm delay.
It will be action when the generator current is higher than
49 Generator over current level1
Gen overcurrent level 1 value and confirm delay.
It will be action when the generator current is higher than
50 Generator over current level2
Gen overcurrent level 2 value and confirm delay.
51 Spare
52 Spare
56 Spare
57 Spare
58 Spare
59 Spare
60 Spare
67 Spare
Choose this function of the output relay, it will be action
when the engine cooling temperature below the low limit
68 Heater control preheating open level value, and keep until cooling
temperature higher than the high limit preheating stop level
value, it will stop to work.
Choose this function of the output relay, it will be action
when from auxiliary temperature sensor measurement
69 Heater2 control temperature below the low limit preheating 1 open level
value, and keep until the temperature higher than the high
limit preheating 1 stop level value, it will stop to work.
70 Spare
This output relay connected to the Gen load switch of GCB
71 GCB open shunt coil, when the controller command the Gen power cut
working, after the switch open will stop working.
This output relay connected to the mains load switch of MCB
72 MCB open shunt coil, when the controller command the mains power
cut working, after the switch open will stop working.
When the mains voltage is lower than set value trigger fault
73 Mains under volt alarm
movement.
When the mains voltage is lower than set value trigger fault
74 Mains over volt alarm
movement.
When the mains voltage is lower than set value trigger fault
75 Mains under HZ alarm
movement.
When the mains voltage is lower than set value trigger fault
76 Mains high HZ alarm
movement.
When the mains low frequency, high frequency, low voltage
77 Mains alarm and high voltage, any more than set limit trigger fault
movement.
78 Spare
Menu Descriptions:
PRES. Sensor 1
l Corresponds to the configurable 2 in the LOP-Sensor type.
PRES. Sensor 2
l Corresponds to the configurable 3 in the LOP-Sensor type.
TEMP. Sensor 1
l Corresponds to the configurable 2 in the HET-Sensor type.
TEMP. Sensor 2
l Corresponds to the configurable 3 in the HET-Sensor type.
Note:
l Configurable sensor data means user can input the data manually
according to the sensor curve. When configuring, please input the
resistance- measured value from small to big one by one as following.
Fix Point 1 2 3 4 5 6 7 8 9 10
Resistance 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Measured Value 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
NOTE:
l Only GU3311 has above parameters.
Menu descriptions:
M V-monitor type:
l Used to choose the controller is phase - phase or phase - zero voltage as mains voltage monitoring object.
l Choose the controller is phase - phase or phase zero in different voltage input type, detection of the
different voltage, specific as follows table:
Parameters
Voltage type Phase Phase Phase Zero
M V low alarm:
l Used to configure low Mains voltage alarm value, the low Mains voltage alarm is inactive when
parameter configured as not used.
l Expressed by percentage, use Rated ph-voltage as factor.
l Controller will compare the "phase-zero" voltage or "phase-phase" voltage with the setting value,
when the measured voltage value is lower than the "rated voltage" * "Mains low fault voltage",
and not higher than the "rated voltage" * "Mains low voltage return value", the duration longer
than "Main fault confirming time", then it is low voltage alarm.
M V low Return:
l Used to configure low Mains voltage alarm value recovery value.
l Expressed by percentage, use Rated ph-voltage as factor.
l Controller will compare the "phase-zero" voltage or "phase-phase" voltage with the setting value,
when the measured voltage value is higher than the "rated voltage" * "Mains low voltage return
voltage", Mains low voltage fault reset confirm time, Mains returned to normal.
M V High alarm:
l Used to configure high Mains voltage alarm value, the high Mains voltage alarm is inactive when
parameter configured as not used.
l Expressed by percentage, use Rated ph-voltage as factor.
l Controller will compare the "phase-zero" voltage or "phase-phase" voltage with the setting value,
when the measured voltage value is higher than the "rated voltage" * "Mains high fault voltage",
and not lower than the "rated voltage" * "Mains high voltage return value", the duration longer
than "Main fault confirming time", then it is high voltage alarm.
M V High Return:
l Used to configure high Mains voltage alarm value recovery value.
l Expressed by percentage, use Rated ph-voltage as factor.
l Controller will compare the "phase-zero" voltage or "phase-phase" voltage with the setting value,
when the measured voltage value is lower than the "rated voltage" * "Mains high voltage return
voltage", Mains high voltage fault reset confirm time, Mains returned to normal.
M Hz low alarm:
l Used to configure low Mains frequency alarm value, the low Mains frequency alarm is inactive
when parameter configured as not used.
l Controller will compare the measurement frequency with the setting value, when the measure
voltage frequency value is lower than the setting value, and not higher than the "Mains low
frequency return value", the duration longer than "Main fault confirming time", then it is Mains
low frequency alarm.
M Hz low Return:
l Used to configure low Mains frequency alarm value recovery value.
l When the measure voltage frequency is higher than the "Mains low frequency return value",
Mains low frequency fault reset confirm time,
M Hz High ALM:
l Used to configure high Mains frequency alarm value, the high Mains frequency alarm is inactive
when parameter configured as not used.
l Controller will compare the measurement frequency with the setting value, when the measure
voltage frequency value is higher than the setting value, and not lower than the "Mains high
frequency return value", the duration longer than "Main fault confirming time", then it is Mains
high frequency alarm.
M Hz High Return:
l Used to configure high Mains frequency alarm value recovery value.
l When the measure voltage frequency is lower than the "Mains high frequency return value",
Mains high frequency alarm reset confirm time,
M alarm delay:
l Used to configure Mains alarm time is active.
NOTE:
l Confirm mains alarm when the mains voltage is lower than 10% of the
rated voltage.
M on delay:
l Used to configure from the mains voltage normal to the mains switch relay closed output delay.
MCB close
l Controller has to monitoring the Mains switch close, breakdown and control. E.g. to choose 1/2/3 alarm
level, when protection function sparks, LCD displays !W:MCB close, to choose 4/5/6 alarm level,
when protection function sparks, LCD displays !A:MCB close.
MCB open
l Controller has to monitoring the Mains switch open, breakdown and control. E.g. to choose 1/2/3
alarm level, when protection function sparks, LCD displays !W:MCB open, to choose 4/5/6 alarm
level, when protection function sparks, LCD displays !A:MCB open.
NOTE:
If the MCB close and MCB open monitoring function effectively, must satisfy:
l One of the relay is defined as "Mains close/open".
l One of the switch input is defined as " Mains closed auxiliary contacts".
Current type:
l Measure the current transformer can be installed in the Gen output end or the load switch end, this
menu for two kinds of type choices.
Prohibit return:
l Controller in automatic mode when configured to "0", the generator starting on load after the Mains
failure. Mains closed switch time to starts after the Mains returned to normal, when it times out,
Gen points brake, Mains switch loading, Generator stop after cooling, in standby state.
l Controller in automatic mode when configured to "1", the generator starting on load after the Mains
failure. The generator keep loading when the Mains returned to normal, LCD display: Prohibit
return. Until the following conditions:
"Automatic" change to "Manual" mode, through the manual closed command the Mains
loading, "Manual" change to "Automatic" mode again, can restore automatic mode of Mains
loading condition.
Happen to stop fault when the Gen loading, if the mains normal, the Gen points brake, Mains
closed loading.
7.8 MAINTENANCE
NO. Items Value Range Preset
8.1 DATE/TIME YY-MM-DD HH:MM:SS
8.2 Scheduler mode 0 without load/ 1 with load 0
8.3 Start time HH:MM
8.4 Run duration 1 to 1440 minutes 60 minutes
8.5 MON active 0 no/ 1 yes 0
8.6 TUE active 0 no/ 1 yes 0
8.7 WED active 0 no/ 1 yes 0
8.8 THU active 0 no/ 1 yes 0
8.9 FRI active 0 no/ 1 yes 0
8.10 SAT active 0 no/ 1 yes 0
8.11 SUN active 0 no/ 1 yes 0
Menu descriptions:
DATE/ TIME:
l Used to configure the date/ time: YY-MM-DD HH:MM:SS.
l The date displayed on LCD, the pre-alarm(warning) and alarm events with time stamp.
Scheduler mode:
l The function of the controller choice when the controller in the scheduling mode.
l Used to select with load or without load when controller is running in the exercise run schedule.
Start time
l Used to configure the start time when controller is active in exercise run scheduler.
Run duration
l Used to configure the duration when controller is active in exercise run schedule, the scheduler
mode will be reset after run duration has expired.
MON active
l The cycle of exercise run scheduler is 1 week. This menu is used to configure the exercise run
schedule on Monday active or not.
TUE active
l Used to configure the exercise run schedule on Tuesday active or not.
WED active
l Used to configure the exercise run schedule on Wednesday active or not.
THU active
l Used to configure the exercise run schedule on Thursday active or not.
FRI active
l Used to configure the exercise run schedule on Friday active or not.
SAT active
l Used to configure the exercise run schedule on Saturday active or not.
SUN active
l Used to configure the exercise run schedule on Sunday active or not.
7.9 CALIBRATION
NO. Items Value Range Preset
9.1 GEN. V1 offset -9.9% to 9.9%
9.2 GEN. V2 offset -9.9% to 9.9%
9.3 GEN. V3 offset -9.9% to 9.9%
9.4 Current I1 offset -9.9% to 9.9%
9.5 Current I2 offset -9.9% to 9.9%
9.6 Current I3 offset -9.9% to 9.9%
9.7 MAINS V1 offset -9.9% to 9.9%
9.8 MAINS V2 offset -9.9% to 9.9%
9.9 MAINS V3 offset -9.9% to 9.9%
9.10 Pressure offset -9.9% to 9.9%
9.11 Temperature offset -9.9% to 9.9%
9.12 Batt. V offset -9.9% to 9.9%
9.13 AUX sensor offset -9.9% to 9.9%
Menu descriptions:
GEN. V1 offset:
l Used to modify the measured value display of GEN Phase 1 voltage.
l Reference to the rated voltage.
GEN. V2 offset:
l Used to modify the measured value display of GEN Phase 2 voltage.
l Reference to the rated voltage.
GEN. V3 offset:
l Used to modify the measured value display of GEN Phase 3 voltage.
l Reference to the rated voltage.
Current I1 offset:
l Used to modify the measured value display of Phase 1 current I1.
l Reference to the rated current.
Current I2 offset:
l Used to modify the measured value display of Phase 2 current I2.
l Reference to the rated current.
Current I3 offset:
l Used to modify the measured value display of Phase 3 current I3.
l Reference to the rated current.
Mains V1 offset:
l Used to modify the measured value display of Mains Phase 1 voltage.
l Reference to the rated voltage.
Mains V2 offset:
l Used to modify the measured value display of Mains Phase 2 voltage.
l Reference to the rated voltage.
Mains V3 offset:
l Used to modify the measured value display of Mains Phase 3 voltage.
l Reference to the rated voltage.
Pressure offset:
l Used to modify the measured value display of LOP-sensor.
Temperature offset:
l Used to modify the measured value display of HET-sensor.
Batt. V offset:
l Used to modify the measured value display of battery voltage.
8 Installation Guide
Cutout dimension: 109mm(W) x 91mm (H). Dashed box dimensions for the controller.
Note:
l The shock-proof equipment must be mounted if the enclosure is mounted
on Genset or other heavy vibrant device.
l In order to ensure the degrees of protection of the mounted controller meet
IP65, the cutout dimension on the panel must be correct.
8.2 Wiring
Please refer to the Typical Wiring Diagram for connection.
NOTE:
l A switch or fuse for overcurrent protection between power supply and controller
must be mounted, the recommended capacity is 1A.
l When powering, the controller will generate significant instantaneous peak
current, the maximum instantaneous peak current is relative to the power
impedance. You must consider the peak current when choosing a switch or
fuse for overcurrent protection.
WARNING:
l Make sure the connection between terminal negative of controller and
protective earth is good. A good ground is very important for operation of
the controller, otherwise it will impact the electrical measurement and even
damage the controller.
WARNING:
l For ensuring the accuracy of sensor please reduce the cable resistance
between controller and sensor as much as possible, the cable should not
be less than 2.5mm 2.
l When single pole sensor is used, the sensor shell and engine must be well
connected and do not use insulated material on sensor screw thread when
installing single pole sensor.
NOTE:
l The measuring accuracy of magnetic pick-up is related to fly wheel teeth:
Accuracy=120/ fly wheel teethRPM.
As the above formula, more fly wheel teeth leads to higher measuring
accuracy.
WARNING:
l Shield cable must be used for connection between controller and sensor,
and the shield should be earthed.
l Please play attention that the terminal #28 is connected to negative of the
power supply inside the controller.
8.2.4 Typical connection for voltage input and current that corresponding to difference
generator winding.
3P4W (3 phase 4 wire), CT measure at Gen side
Mains 3 phases VPh-N L1-N L2-N L3-N Mains 3 phases VPh-N L1-N L2-N L3-N
Mains 3 phases VPh-Ph L1-L2 L2-L3 L3-L1 Mains 3 phases VPh-Ph L1-L2 L2-L3 L3-L1
Mains frequency HzL1 Mains frequency HzL1
Gen 3 phases VPh-N L1-N L2-N L3-N Gen 3 phases VPh-N L1-N L2-N L3-N
Gen 3 phases VPh-Ph L1-L2 L2-L3 L3-L1 Gen 3 phases VPh-Ph L1-L2 L2-L3 L3-L1
Gen frequency HzL1 Gen frequency HzL1
Gen 3 phases current I1 I2 I3 Gen 3 phases current I1 I2 I3
Gen active power P Gen active power P
Gen reactive power Q Gen reactive power Q
Gen power factor PF Gen power factor PF
NOTE:
l Only GU3311 has port #5, #6, #7, #8 and M1.
l Only GU3311 has Mains measurement display data.
Mains 3 phases VPh-N L1-N L2-N L3-N Mains 3 phases VPh-N L1-N L2-N L3-N
Mains 3 phases VPh-Ph L1-L2 L2-L3 L3-L1 Mains 3 phases VPh-Ph L1-L2 L2-L3 L3-L1
Mains frequency HzL1 Mains frequency HzL1
Gen 3 phases VPh-N L1-N L2-N L3-N Gen 3 phases VPh-N L1-N L2-N L3-N
Gen 3 phases VPh-Ph L1-L2 L2-L3 L3-L1 Gen 3 phases VPh-Ph L1-L2 L2-L3 L3-L1
Gen frequency HzL1 Gen frequency HzL1
Mains/ Gen 3 phases current I1 I2 I3 Mains/ Gen 3 phases current I1 I2 I3
Mains/ Gen active power P Mains/ Gen active power P
Mains/ Gen reactive power Q Mains/ Gen reactive power Q
Mains/ Gen power factor PF Mains/ Gen power factor PF
NOTE:
l Only GU3311 has above connection mode.
NOTE:
l Only GU3311 has port #5, #6, #7, #8 and M1.
l Only GU3311 has Mains measurement display data.
NOTE:
l Only GU3311 has above connection mode.
NOTE:
l Only GU3311 has port #5, #6, #7, #8 and M1.
l Only GU3311 has Mains measurement display data.
NOTE:
l Only GU3311 has above connection mode.
NOTE:
l Only GU3311 has port #5, #6, #7, #8 and M1.
l Only GU3311 has Mains measurement display data.
NOTE:
l Only GU3311 has above connection mode.
Page 1 Description
Page 2 Description
Page 3 Description
Page 4 Description
Page 5 Description
Page 6 Description
Page 7 Description
Page 8 Description
Page 10 Description
Page 11 Description
Page 12 Description
Page 13 Description
[SETTING]
0QUIT
Press and hold 2sec, enter into parameters settings menu,
1. SYSTEM
then LCD displays:
2. GENERATOR
3. ENGINE
[ENGINE]
0QUIT
Press+ 2 times and then press , then LCD displays: 1. Engine type
2. ECU type
3. Engine rated speed
[Crank attempt]
Press+ 9 times and then press , then LCD displays: 3
[Crank attempt]
Press+ or - to change parameters, change at 2. 2
Press restore the default value, press and hold 2sec, [SYSTEM]
can quit parameter settings menu. DONE
Break off the power supply, then connect the computer with
communication cable, run the program software "ABLDs.exe",
open the serial interface and import upgrade program
as illustrated in figure, switch the power on then the controller
will keep to do program upgrade automatically.
If the operation failure, you can disconnect the power and try
again.
10 Technical Specification
10.1 AC voltage:
Measurement True RMS
Phase to Neutral 15 to 346VAC
Phase to Phase 25 to 600VAC
Max power wastage per line <0.1W
Accuracy 1%
Display 0 to 3000V