IS15301:2003
REAFFIRMED
IndianStandard
INSTALLATIONANDMAINTENANCEOFFIRE
FIGHTINGPUMPSCODEOFPRACTICE
ICS13.220.10
BIS2003
BUREAUOFINDIANSTANDARDS
MANAKBHAVAN,9BAHADURSHAHZAFARMARG
NEWDELHI110002
April2003
PriceGroup4
i FireFightingSectionalCommittee,CED22
FOREWORD
ThisIndianStandardwasadoptedbytheBureauofIndianStandards,afterthedraft
finalizedbytheFireFightingSectionalCommitteehadbeenapprovedbytheCivil
EngineeringDivisionCouncil.
Allbuildingsdependingupontheoccupancyuseandheightareprotectedbyfixed
firefightinginstallationsaspertheprovisionslaiddowninSP7(Part4).Thefixedfire
fightinginstallationsareprovidedinmultistoreyedbuildingofheight15metresorabove
andalsoothercategoriesofbuildingsoflesserheightbutwithspecialrisks/basement,etc.
Similarly,allfactories/manufacturingindustriesalsogoforinstallationoffixedfirefighting
systemforprotectionofthepropertyandlife.Thesystemmaybeintheformofwetriser,
externalhydrantorintheformofsprinkler/emulsifiers,etc,orallofthem.Themost
importantcomponentinsuchasystemisthefirepump.Acarefullychosenfirepumpof
appropriatecapacityandinstalledproperlywillformthebackboneofsuchsystem.Even
afterinstallation,itisabsolutelyessentialthatthefirepumpsareproperlymaintainedand
regularlytestedsothattheyareinserviceableconditionandcomeintooperationinstantly
atthetimeofexergencies.
Therequirementsinregardtotheinstallationandmaintenanceofinternalor
externalfirehydrantsarecoveredinseparateIndianStandards(seeIS3844andIS13039).
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 1/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
ThecompositionoftheCommitteeresponsibleforformulationofthisstandardis
giveninAnnexA.
Forthepurposeofdecidingwhetheraparticularrequirmentofthisstandardis
compliedwith,thefinalvalue,observedorcalculated,expressingtheresultofatestor
analysis,shallberoundedoffinaccordancewithIS2:1960Rulesforroundingoff
numericalvalues(revised).Thenumberofsignificantplacesretainedintheroundedoff
valueshouldbethesameasthatofthespecifiedvalueinthisstandard.
ii IndianStandard
INSTALLATIONANDMAINTENANCEOFFIRE
FIGHTINGPUMPSCODEOFPRACTICE
1SCOPE
Thisstandardlaysdowntherequirementsofinstallationandmaintenanceoffire
fightingpumps.
2REFERENCES
Thestandardslistedbelowcontainprovisionswhichthroughreferenceinthistext,
constituteprovisionsofthisstandard.Atthetimeofpublication,theeditionsindicated
werevalid.Allstandardsaresubjecttorevisionandpartiestoagreementsbasedonthis
standardareencouragedtoinvestigatethepossibilityofapplyingthemostrecenteditions
ofthestandardsindicatedbelow:
ISNo. Title
1710: Specificationforverticalturbinepumpsforclear,cold,freshwater(secondrevision)
1989
2974 Codeofpracticefordesignandconstructionofmachinefoundations:Part3
(Part3): Foundationsforrotarytypemachines(mediumandhighfrequency)(secondrevision)
1992
2974 Codeofpracticefordesignandconstructionofmachinefoundations:Part4
(Part4): Foundationsforrotarytypemachinesoflowfrequency(firstrevision)
1979
3844: Codeofpracticeforinstallationandmaintenanceofinternalfirehydrantsandhosereel
1984 onpremises
5120: Technicalrequirementsforrotodynamicspecialpurposepumps(firstrevision)
1977
6070: Codeofpracticeforselection,operationandmaintenanceoftrailerfirepumps,portable
1983 pumps,watertendersandmotorfireengines(firstrevision)
9137: Codeforacceptancetestforcentrifugal,mixedflowandaxialpumpsClassC
1978
13039: ExternalhydrantsystemsProvisionandmaintenanceCodeofpractice
1991
SP7(Part NationalbuildingcodeofIndia:Part4Fireprotection(firstrevision)
4):1983
3TERMINOLOGY
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 2/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
3TERMINOLOGY
Forthepurposeofthisstandard,thefollowingdefinitionsshallapply.
3.1StaticWaterTank
Undergroundorsurfacewatertank,constructedtostorewaterforfirefighting
purpose.
3.2TerraceTank
Aconcrete/masonry/plastic/steeltankconstructedorerectedonterraceofbuilding
forfirefightingpurpose.
3.3PrimingTank
Asmalltankerectedinside/overthepumphouseandabovethefirefightingpumps
tokeepthepumpcasingandsuctionofthefirepumppermanentlyflooded.Thisisrequired
incaseofnegativesuction.
3.4FootValvecumStrainer
3.4.1
Avalvefixedinthesuctionstrainerofthefirepumpwhichopensonlyinwardsto
allowinflowofwaterintothepumpsuctionandfirepumpwhenthepumpisactuated
automatically/manually,ThisisrequiredincaseofNegativesuction.
3.4.2
Inapositive(flooded)suction,astrainerplacedinthesuctionlinebetweenthefire
tankandfirepumptoarrestanydirt/obstructionbeingfedintothepumpsuction.
3.5JockeyPump
Apumpofsmallcapacitywhichissettocomeintooperationautomaticallywith
dropinstaticpressureinthesystemandtoautomaticallystopwhenthepresetpressureis
reachedagain.
3.6TerracePump
Anelectricallydrivenpump,locatedontheterraceconnectedtoaterracetankwith
gatevalveonsuctionsideandtotheinternalhydrantsystemwithnonreturnvalveon
deliveryside.
3.7FirePump
Anelectric/dieselpumpinstalledatstaticwatertanktochargethewetriser
systems/sprinklersystem,etc.
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 3/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
1 3.8StandbyPump
Apumpofsamecapacityasfirepump,drivenbyadieselengineorconnectedtoany
otheralternatesourceofelectricsupply.
3.9PumpPanel
Panelcomprisingstarting,stoppingandindicatingdevicesoffirepumps.
3.10PressureSwitch
Aswitchconnectedondeliverylineoffirepump,orinthebodyofhydropneumatic
tankatpresetpressurelevelsodesignedtoautomaticallystartthefirepumporjockey
pump,asthecasemaybe,whenthepressureinthesystemfallsbelowthepresetlevel.
3.11CirculationReliefValve
Thecirculationreliefvalveputinbelowtheshutoffpressuretoprovidecirculation
andtherebyrelievetheextrapressureinthepump.
4FIREPUMPSANDPUMPHOUSE
4.1
Thepumphouseshouldbelocatedpreferablyoutsidethebuildingwithaminimum
clearanceof6mfromadjoiningbuildings.Thepumphouseshouldhaveadequatenatural
ventilationwithwindows,fittedwithexpandedmetalforprotection.Inordertofacilitate
properinstallationandmaintenanceoffirefightingpumps,thereshouldbeprovisionof
mildsteelgirderofappropriatexsectionatsuitableheightinpumphouseforfixingchain
pulleyblock.
4.2
Ifthepumphousehasadieselpump,theexhaustpipeofthedieselengineshouldbe
extendedtooutsidethepumphouseandexhaustdischargedatanappropriateheightinthe
openair.
4.3
Thefloorofthepumphouseshouldbeslopedtothefarthestendtodrainawayany
waterleakingfromglands,valves,etc.
4.4
Thepumphouseshouldhavenormallighting,andalsoemergencylightingfacility,
eitherfromasecondsourceorfromthegenerator.
4.5
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 4/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
Ifthepumphouseislocatedinsidethebuilding,eitherongroundfloororinthe
basement,itshouldbeseparatedfromtherestportionwithawallhaving2hfirerating
andfirecheckdooratitsentrancehaving1hfirerating.Forpumphouseinbasement,
forcedmechanicalventilationshouldbeprovided.Pumphouseingroundfloorshouldbe
locatedonperipheryofbuildingwithaccessdirectlyfromoutside/openarea.Thepump
houselocatedinthebasementshouldalsohaveeasyaccessibilityfromoutsidepreferably
throughramp.
5ARRANGEMENTOFPUMPS
5.1
Thelayoutplansofpumpsinstalledandfirewaterlinesshouldbedisplayed.The
pumphouseshouldbeofadequatedimensiontohouseallthepumpswithsuction,delivery
pipes,fittingsandstartercontrolpanel,airvessel,etc,withadequatecirculationarea.
Adequateheadroomclearanceallaroundthepumpformaintenanceshallbemade
available.Aminimumclearanceof1matfrontandbackand0.75monsidesandbetween
pumpsshouldbeprovidedforallmajorpumpsexceeding22801/mincapacity.Forsmaller
pumps,includingjockeypumps,theclearancerequiredshouldbe0.75matfrontandback
and0.60matsidesandbetweenpumps.Theheadroomclearanceforallpumphouses
shouldbeminimum2.75m.
5.2
Thepumpcontrolpanelwhichshouldalsobehousedinthepumproombuteasily
accessible,shouldbeofadequatedimensiontoincorporatetripplepoolandneutral(TPN)
switchandhighrupturecapacity(HRC)switchbothofadequatecapacity,selectorswitch
ammeter,voltmeterandphaseindicatinglights,singlephasepreventer,startandstoppush
buttons,automanualswitch,auxiliarycontractorsforinterlocking/sequenceofoperations
andallnecessarygauges,fittingsrequiredtocompletethesystem(thebusbarshouldbeof
copperofappropriatethickness).Thepanelshouldbefloormountedwithpropergrouting
withthefloorandbecompartmentalized.Thegaugethicknessofpanelshouldbe1.8mm.
5.3
Wheredieselpumpisprovided,itshouldhaveaseparatepanel,alsolocatedinthe
samepumproomoradjoiningseparateroom.Thepanelshouldhaveitsseparatebattery,
withbatterychargingdevice,andautomanualchangeoverarrangement.Itshould
incorporateaninterlockingdevicewiththemainpumppanelsothatboththeelectric
pumpandthedieselpumpdonotoperatesimultaneously.Adequateprecautionshouldbe
takentoavoidspillageofdieseltoavoidanyfireexergency.
5.4
Airvesselofadequatecapacityshouldbeinstalledinthepumphouse,withpressure
switchesincorporatedonthedeliveryline.Thereshouldbetwopressureswitchesone
withupperandlowerlimitforjockeypumpandanotheronewithonlyforlowerpressure
limitforthemainpump.Stoppingofmainpumpsshouldbeonlybymanualpushbutton
whichshouldbeprominentlyindicatedonthepumppanel.
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 5/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
5.5
Similarlowerpressurelimitswitchshouldalsobeincorporatedinthedieselpumpto
makethestartautomaticallyatpresetdropinpressure.
6INSTALLATIONOFFIREPUMPS
6.1
Thecapacityofthefirepumpshouldbecarefullychosentomeetthemaximum
requirementfortherisk
2 tobeprotected.Thefirepumpshavebeendividedintothefollowingcapacities:
a.4501/min,
b.9001/min,
c.22801/min,
d.28501/min,and
e.45001/minandforspecialrisks67001/min.
Oftheabove,(a)and(b)arebasicallythepumpstobeinstalledontheterracetofeed
theDownComerSystem.Theotherpumpsaretobehousedinthepumphouse.Thepump
housemaybebelowthelevelofthewatertankorconstructedabovethewatertank
dependingupontheengineeringconveniences.Forfirefightingpurpose,apumphouse
havingthepumpsbelowthewatertankisalwaysdesirable,asthiseliminatesthenecessity
tohavenegativesuctionincorporatingprimingtank,footvalveandotherextravalves,etc.
AllpumpsarerequiredtobestartonAuto,whenthereisadropofpressureinthemains.
Thesearerequiredtobepresetonpredeterminedpressuresuitabletoparticularrisk.
6.2
Ifthepumpiselectricdriven,thecapacityofthepumpvisvisitsrevolutionsper
minutemustmatchwiththeelectricmotorbeingchosenforthesamejob.Electricmotors
requiredtofeedthepumpupto22801/minareusuallyrunningat2900rev/minandthe
pumpsrequiredtomatchthemotorsmustalsorunatthesamerevolutionsperminute.
ThesepumpsareknownasSingleStagePumpsandthesuctionisattheendofthepumpso
thatthesearecalledEndSuctionPumps.Smallcapacitypumps/jockeypumpsarealso
available/requiredtobeusedinmultistagedesign.Thespeedsofthesepumpsaresuitable
for2polemotoror4polemotor.
6.3
Thefirefightingpumpsarealmostinvariablycentrifugaltypeexceptinginsome
typicalcaseswhereverticalturbineorsubmersiblepumpsareinstalled.Afterthecapacityof
thepumpandmotorhasbeencarefullychosen,tomatcheachotherperfectly,installation
ofthepumpsinthepumphouseshouldbedonewithutmostcare.Ashasbeensaidabove,
thepumphouseshallhaveadequatespacestokeepenoughcirculationareawithinthe
pumphouseforthepumpoperatorintimesofemergencyormaintenance.Thepumpand
themotorsarealwayscasesconnectedtogetherbyconnectingcouplersandtheyare
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 6/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
mountedonacommonbaseplatewhichissuppliedbythepumpmanufacturersalongwith
thepump.Thebaseplateshallbeofsufficientlengthandwidthtohousethepumpandthe
motorcomfortably.
6.4
Inthefirststageoftheinstallation,pumpsaretobemountedonaconcrete
foundationhavingminimumgradeofreinforcedconcreteasM15.Thefoundationshallbe
ofadequatethicknessanddimensiondependinguponthetypeofthepumpwhichwillbe
installed.Thethicknessofthefoundationshallbe50mmminimumforsmallpumpsupto
9001/mincapacity,75mmforpumpsupto22801/mincapacityand100mmforbigger
pumpsupto45001/min.Forextraordinarybigpumps,thethicknessmaygoupto150
mm.Thesizeofthefoundationshallcoverthefulllengthandwidthofthepumpand
atleast150mmonthefrontandbackofthepumpand75mmonthesidesasclearance.
ThefoundationshallbedesignedasperIS2974(Part3)andIS2974(Part4).
6.5
Itisrecommendedtoprovideajockeypumptotakecareofsystemlosses.The
capacityofthejockeypumpshallneitherbelessthan3percent(withaminimumof180
1/min)normorethan10percentoftheinstalledpumpingcapacity.
6.6
Eachpumpshallbeprovidedwithapressuregaugeonthedeliverysidebetweenthe
pumpandthenonreturnvalveandamanufacturersplateindicatingthedeliveryhead,
capacityandthenumberofrevolutionsperminute.
6.7
Pumps(otherthanJockeypumps)shouldbeabletodevelopheadofgreaterthan65
percentofratedheadatcapacityof150percentofratedcapacity.Theratedheadfor
verticalturbinepumpswillberatedbowlhead.Theshutoffheadofpumps(otherthan
jockey)shouldnotexceed120percentofratedheadforhorizontalpumpsand140percent
ofratedbowlheadofverticalturbinepumps.
6.8
Eachfireservicepumpshallbeprovidedwithanindependentsuctionpipewithout
anysluiceorcutoffvalvestherein,unlessthepumpissituatedbelowthelevelofthewater
supplyinwhichcasesluiceorcutoffvalvesisessential.WheretheNetPositiveSuction
Head(NPSH)availableatsiteislessthan0.5minexcessoftheactualvaluerequiredat150
percentofthedutypointasperthemanufacturerscurvesorwherethewatersupplyhas
fibrousorequallyobjectionablematterinsuspensionormudand/orsandliabletocause
depositionintheinstallation,suctionpipe(s)shallbeinstalledinajackwell(suctiontank),
fedthroughapipe/pipesofappropriatediafromthemainwatersupply.Atthesupplyend
ofthemajortank,wherethemainsupplysourceisatadistanceexceeding20m,asluiceor
gatevalveshallbeprovided.Fromfirewaterstoragereservoirtwoseparateconnectionsare
takentosuctionheader(fromeachcompartmentoffirewaterstorage.)
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 7/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
6.9
Thediameterofthesuctionpipeshallbesuchthattherateofflowofwaterthrough
itdoesnotexceed1.5m/swhenthepumpisdeliveringatitsrateddischarge.If,however,
thepumpissituatedbelowthelevelofitswatersupply,thediameterofthesuction
pipe/headershallbebaseduponarateofflowof2m/s.
3
6.10
Whenthepumpisabovethelevelofitswatersupply,thereshallbeafootvalveanda
primingarrangement,thelatterconsistingofatank(havingacapacityatleastthreetimes
thatofthesuctionpipeincludingthepumpcasingfromthepumptothefootvalve),
connectedtothedeliverysideofthepumpbyametalpipehavingaminimuminternal
diameterof100mminthecaseofcentrifugalpumpswithastopvalveandanonreturn
valvethereinofthesamesize.Adependableindependentfillingarrangementandalevel
indicatorshallbeprovidedfortheprimingtank.Theprovisionofavacuumgaugeforthe
suctionpipeisrecommended.Wherecircumstancespermit,centrifugalpumpsshallbe
fixedpreferablybelowthelevelofthewatersupply.Ifthepumpisautomaticinaction,it
shallnecessarilybesofixed.
6.11
However,forlightandordinaryhazardoccupanciesiftheprimingarrangementsare
suchastoensurethatthesuctionpipeshallbeautomaticallymaintainedfullofwater
notwithstandingaseriousleakagetherefrom(thepumpbeingautomaticallybroughtinto
actiontoreplenishtheprimingtankshouldthelatterbedrawnuponatagreaterratethan
therateatwhichitisfedfromanyothersource),positivesuctionmaynotbeinsisted.In
suchcases,thecapacityoftheprimingtankneednotexceed4501andthediameterofthe
primingpipeneednotexceed50mm.Eachpumpshallbeprovidedwithanautomaticby
passconnectionandreliefvalvesetbelowtheshutoffpressure.Itshallprovidecirculation
ofsufficientwatertopreventthepumpfromoverheatingwhenoperatingwithclosed
deliveryandnodischarge.Thecirculationreliefvalveshoulddischargeapproximately35
percentofthepumprating.
TestLineEachpumpshallbeprovidedwithtestlineandshutoffvalvefor
individualtestingofpumpswithoutdischargingthesystem.
6.12
Pumpsshallnotbeinstalledintheopen.Thepumproomshallbesolocatedastobe
botheasilyaccessibleandwhereanyfallingmasonryandthelikefromotherbuildings
occasionedbyfireorothercause,cannotdamagethepumproom.Normally,pumprooms
shallbelocated6mawayfromallsurroundingbuildingsandoverheadstructures.Where
thisisnotfeasible,theymaybeattachedtoabuildingprovidedaperfectseperationwall
having4hfireratingisconstructedbetweenthepumproomandtheattachedbuilding,the
roofofthepumproomisofRCCconstructionatleast100mmthickandaccesstothe
pumproomisfromtheoutside.Thepumproomsshallnormallyhavebrick/concretewalls
andnoncombustibleroofwithadequatelighting,ventilationanddrainagearrangements.
6.13
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 8/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
Thesubstation(s)and/orD.G.House(s)supplyingpowertothefirepump(s)shallbe
ofincombustibleconstructionandshallbelocatedatleast6mawayfromallsurrounding
buildings.Wherethisisnotfeasible,alldoorandwindowopeningsofthesurrounding
buildingswithin6mofthesubstation(s)and/orD.G.House(s)shallbeprotectedbysingle
fireproofdoorsand6mmthickwiredglassesinsteelframeworkrespectively.Likewise,
roofeaves,ifanyofthesurroundingbuildingsfallingwithin6mofthesubstation(s)
and/orD.G.House(s),shallbecutandwallraisedasaparapet.Theaboveprovisionsshall
alsoapplywhenthesubstation(s)andD.G.House(s)arewithin6mofeachother.
Wherethesubstation(s)andD.G.House(s)areattachedtobuildings,afourhour
ratedwallshallbeconstructedtosegregatethesubstation(s)andD.G.House(s).Thisshall
beofRCCconstructionatleast200mmthickorofmasonryconstructionatleast230mm
thick.
6.14
TransformercubiclesinsidethesubstationsshallbeseparatedfromH.T.andL.T.
cubiclesandfromeachotherbywallsofbrick/stone/concreteblocksor355mmthickness
orofRCCof200mmthicknesswithdooropenings,ifany,thereinbeingprotectedby
singlefireproofdoorshaving2hourfireresistance.Thesubstation(s)and/orD.G.
House(s)shallalsobeseperatedfromeachotherasabove.Transformersinstalledoutdoors,
whicharesupplyingpowertofirepump(s)shallalsobelocatedatleast6mawayfromall
surroundingbuildings[includingsubstation(s)and/orD.G.House(s)].Wherethisisnot
feasible,alldoorandwindowopeningsofthebuilding(s)[includingsubstation(s)and/or
D.G.House(s)within6mofthetransformers]shallbeprotectedbysinglefireproofdoors
and6mmthickwiredglassesinsteelframeworkrespectively.Likewise,roofeavesofthe
building(s)fallingwithin6mofthetransformersshallbecutandwallraisedasaparapet.
Blastwallsofbricks/stone/concreteblocksof355mmthicknessorofRCCof200mm
thicknessshallbeconstructedbetweentransformersandthesewallsshallbeextended
horizontally600mmbeyondtheextremitiesofthetransformersandvertically600mm
abovethehighestpointofthetransformers.
6.15
Theelectricsupplytothepumpset(s)shallbeentirelyindependentofallother
equipmentinthepremises,thatis,evenwhenthepowerthroughouttheentirepremisesis
switchedoff,thesupplyofthepumpshallcontinuetobeavailableuninterrupted.Thiscan
beachievedbytakingtheconnectionforthepump(s)fromtheincomingsideofthemain
L.T.Breaker.However,incaseswheretwoormoretransformersand/orsourcesofsupply
areconnectedtoacommonbusbarorwherethereisprovisionofa
4 buscouplerbetweenthebusbarsections,theconnectionmaybetakenthroughthe
busbars.
6.16FireExtinguisher
ThepumproomshouldbeprotectedbyappropriatetypeofextinguisherseitherC02
orDCP.Ifthepumpsareinbasement,itisdesirabletohavethepumpsprotectedby
automaticsprinklersystem.
7MAINTENANCE
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 9/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
7MAINTENANCE
7.1
Thefirepumpshallbemaintainedregularlyandproperly.Therefore,itisabsolutely
essentialthatsomeoneresponsiblepersonshouldbegiventhechargeofensuringthatthe
firepumpsareproperlymaintained.
7.2
Thefollowingmaintenancescheduleshallbemaintained.
7.2.1
Afterthefirefightingpumphasbeencommissionedandthesystemhasbeentaken
overbytestingitaccordingtotheperformanceparameterslaiddownforthefirepump,
thisshouldberecordedinamaintenanceregister,tobekeptinthepumphouse.Theinitial
testshouldshowthefollowing:
a.Flowobtainedat7kgf/cm2,
b.Flowobtainedat4.5kgf/cm2(65percentof7kg),and
c.Pressuregaugerecordingat120percentof7kg.
7.3
Afterthisinitialtakeoverofthepump,thefollowingshallbetheroutine
maintenanceschedule.
7.3.1DailyCheck
a.TestingoftheJockeyPump
Testthejockeypumpdailybyopeningthedeliveryvalve/hosereelveryslightly
toallowthepressuretodropuptothepresetlevel.Notethetimingtakenbythe
jockeypumptorestorethepressureautomaticallybycutoffswitch.
b.MainPump
Themainpumpshallbetesteddailyatleastfor5min.Releasethesystem
pressurebyopeningthehydrantvalvepartially.Thejockeypumpwillcomein
operation.Openthevalvefullywhenfurtherdropinpressurewhichwillallowthe
mainpumptostartautomatically.Closethedeliveryoutletandallowthepumptorun
for5mineverymorning.
c.Checkthepumpglands,packings,etc,andreplacethedamagedglandforpacking
wheneverfounddamagedorwornout.
7.3.2WeeklyCheck
a.Checkbearingsgreasecutonceaweekandlubricateasneeded.
b.Cleaningofstartercontactseveryweek.
c.Checktheinsulationresistanceofpumpmotorcircuiteveryweek.
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 10/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
d.Checktheenginefueloiltankandensurethatthisisofappropriategradeand
quality.
e.Checkthequantityoffueloilinthetank.Thisshouldbesufficientfor4hrunning
withoutreplenishment.Checkthesludgeandsedimenttrapasprovidedinthe
auxiliaryequipmentlist.Checktheinspectionandcleaninghole,checkthe
battery/batteriesrequiredforstartingoftheengineandensurethatthesearein
satisfactorycondition.Alsocheckthebatterychargingarrangementbytrickier
charger.
Foreverycoldareas,spaceheatingisnecessarytokeeptheenginein
reasonablywarmconditionforimmediatestarting,Ifso,ensurethattheroom
heatingarrangementisworkingsatisfactory.
f.Startingdieselengineonceeveryweekandrunitfor10min.Thestartingshouldbe
testedbyswitchingoffthecurrentandallowingsystempressuretodropuptothe
presetlevelfordieselengine.Interlockarrangementwithpowersupplyshouldbe
restored.
g.Checkalignmentofpumpmotors,nuts,bolts,couplings,couplingguard,etc,once
everyweekafterthepumphasrunforcontinuous15min.
7.3.3
InspectionshallbecarriedoutaspertherequirementsgiveninIS1710,IS5120,IS
6070andIS9137.
7.4
Manufacturersshallprovidealistoffastmovingspares.
5
ANNEXA
COMMITTEECOMPOSITION
(Foreword)
FireFightingSectionalCommittee,CED22
Organization Representative(s)
MinistryoilHomeAffairs,NewDelhi ShriOmPrakash(Chairman)
ShriD.K.Shami(Alternate)
AirportAuthorityofIndia,NewDelhi ShriL.C.Gupta
ShriH.S.Rawat(Alternate)
AndhraPradeshFireServices,Hyderabad ShriSwaranjitSen
BhabhaAtomicResearchCentre,Mumbai ChiefFireOfficer
BombayFireBrigade,Mumbai ChiefFireOfficer
ShriG.S.Sawant(Alternate)
CentralBuildingResearchInstitute,Roorkee DrT.P.Sharma
DrA.K.Gupta(Alternate)
CentralIndustrialSecurityForce,NewDelhi DeputyInspectorGeneral(Fire)
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 11/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
ShriS.L.Nagarkar(Alternate)
CentralPublicWorksDepartment,New ChiefEngineer(E)
Delhi
CentreforEnvironmentandExplosive ShriA.K.Kapoor
Safety,Delhi
ShriH.S.Kaparwan(Alternate)
ConcordAraiPvtLimited,Chennai ShriR.Ramakrishnan
ControllerateofQualityAssurance(Fire), ColG.P.Krishnamurthy
Pune
DefenceResearchandDevelopment Director(FireSafety)
Organization,Delhi
DeputyDirector(FireSafety)(Alternate)
DelhiFireService,NewDelhi ShriR.C.Sharma
ShriSurinderKumar(Alternate)
DirectorateGeneralofSuppliesand ShriM.Gangaraju
Disposals,Hyderabad
ShriV.K.Verma(Alternate)
EngineerinChiefsBranch,NewDelhi ShriR.A.Dubey
ShriAjayShankar(Alternate)
FireandSafetyAppliancesCompany, ShriS.N.Kundu
Kolkata
HomeDepartment(FireService),Chennai Director
DeputyDirector(Alternate)
InstitutionoffireEngineers(India),New President
Delhi
GeneralSecretary(Alternate)
KooverjiDevshi&Co(P)Limited,Mumbai ShriP.H.Sethna
ShriN.T.Panjwani(Alternate)
K.V.FireChemicals,NaviMumbai ShriH.M.Sabadra
LossPreventionAssociationofIndia, ManagingDirector
Mumbai
ShriD.K.Sarkar(Alternate)
MatherandPlatt(India)Limited,NewDelhi ShriDeepakAgarwal
MECONLimited,Ranchi ShriR.N.Chachra
ShriSunilDas(Alternate)
NewageIndustries,Mumbai ShriB.J.Shah
ShriA.M.Shah(Alternate)
NorthernRailway,NewDelhi ShriI.M.Mansoori
OilandNaturalGasCommission,Dehra ShriR.P.Saxena
Dun
ShriNeerajSharma(Alternate)
OilIndustrySafetyDirectorate,NewDelhi JointDirector(Process)
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 12/13
2017/1/26 IndianStandard:INSTALLATIONANDMAINTENANCEOFFIREFIGHTINGPUMPSCODEOFPRACTICE
RealValueAppliancesLimited,NewDelhi ShriAshutoshMangal
SafexFireServicesLimited,Mumbai ShriJitendraShah
ShriSandipShah(Alternate)
6 StateBankofIndia,Mumbai ShriJ.S.Gahlaut
StateFireTrainingCentre,Mumbai DrNavinchandraJain
SteelAuthorityofIndia,Rourkela ShriB.N.Das
ShriB.P.Das(Alternate)
SteelAuthorityofIndia,Bokaro ShriA.Rautela
ShriC.P.Singh(Alternate)
SteelageIndustriesLimited,NewDelhi ChiefExecutive
ShriV.Kamalanatha(Alternate)
SurexProductionandSales(P)Limited, ShriTaritSur
Kolkata
ShriD.Neogi(Alternate)
TariffAdvisoryCommittee,Mumbai ShriT.R.A.Krishnan
TariffAdvisoryCommittee,Chennai ShriA.Mukherjee
ShriH.C.MaheshKumar(Alternate)
VijayFireProtectionSystemsPvtLimited, ShriHarishSalot
Mumbai
WestBengalFireService,Kolkata ShriB.Pahak
Inpersonalcapacity(33/2965A,Vennala ShriG.B.Menon
HighSchool,Vennala,Cochin)
Inpersonalcapacity(29/25,Rajendra ShriS.K.Dheri
Nagar,NewDelhi)
BISDirectorateGeneral ShriS.K.Jain,Director&Head(CivEngg)
[RepresentingDirectorGeneral(ExOfficio)]
MemberSecretary
ShriS.Chaturvedi
JointDirector(CivEngg),BIS
8
7
https://law.resource.org/pub/in/bis/S03/is.15301.2003.html 13/13