PCC 1301 Service Manual
PCC 1301 Service Manual
PCC 1301 Service Manual
5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings
according to the size of each page you wishRedistribution
to print. or publication of this document
by any means, is strictly prohibited.
Service Manual
GenSet Model
GNAA, GNAB, GNAC
MS-4
iii Redistribution or publication of this document
by any means, is strictly prohibited.
ELECTRICAL SHOCK CAN CAUSE Used engine oils have been identified by some state
SEVERE PERSONAL INJURY OR DEATH or federal agencies as causing cancer or reproduc-
tive toxicity. When checking or changing engine oil,
take care not to ingest, breathe the fumes, or con-
Remove electric power before removing protective tact used oil.
shields or touching electrical equipment. Use rub-
ber insulative mats placed on dry wood platforms Keep multi-class ABC fire extinguishers handy.
over floors that are metal or concrete when around Class A fires involve ordinary combustible materials
electrical equipment. Do not wear damp clothing such as wood and cloth; Class B fires, combustible
(particularly wet shoes) or allow skin surface to be and flammable liquid fuels and gaseous fuels; Class
damp when handling electrical equipment. C fires, live electrical equipment. (ref. NFPA No. 10).
Make sure that rags are not left on or near the en-
Use extreme caution when working on electrical gine.
components. High voltages can cause injury or
death. DO NOT tamper with interlocks. Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating
Follow all applicable state and local electrical under the unit.
codes. Have all electrical installations performed by Remove all unnecessary grease and oil from the
a qualified licensed electrician. Tag and lock open unit. Accumulated grease and oil can cause over-
switches to avoid accidental closure. heating and engine damage which present a poten-
tial fire hazard.
DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. Keep the generator set and the surrounding area
Hazardous voltages can flow from the generator set clean and free from obstructions. Remove any de-
into the utility line. This creates a potential for elec- bris from the set and keep the floor clean and dry.
trocution or property damage. Connect only Do not work on this equipment when mentally or
through an approved isolation switch or an ap- physically fatigued, or after consuming any alcohol
proved paralleling device. or drug that makes the operation of equipment un-
safe.
GENERAL SAFETY PRECAUTIONS Substances in exhaust gases have been identified
by some state or federal agencies as causing can-
Coolants under pressure have a higher boiling point cer or reproductive toxicity. Take care not to breath
than water. DO NOT open a radiator or heat ex- or ingest or come into contact with exhaust gases.
changer pressure cap while the engine is running. Do not store any flammable liquids, such as fuel,
Allow the generator set to cool and bleed the system cleaners, oil, etc., near the generator set. A fire or
pressure first. explosion could result.
Benzene and lead, found in some gasoline, have Wear hearing protection when going near an oper-
been identified by some state and federal agencies ating generator set.
as causing cancer or reproductive toxicity. When To prevent serious burns, avoid contact with hot
checking, draining or adding gasoline, take care not metal parts such as radiator, turbo charger and ex-
to ingest, breathe the fumes, or contact gasoline. haust system.
1-1
Redistribution or publication of this document
by any means, is strictly prohibited.
SYSTEM OVERVIEW Jumper Leads.
The PCC is a microprocessor-based control for Tachometer or Frequency Meter.
Cummins Power Generation generator sets. All Wheatstone Bridge or Digital Ohmmeter.
generator set control functions are contained on Variac.
one circuit board (Base board). The Base board
Load Test Panel.
provides fuel control, main alternator voltage output
regulation and complete generator set control and Megger or Insulation Resistance Meter.
monitoring. InPower Service Tool (PC based genset ser-
The operating software provides control of the gen- vice tool).
erator set and its performance characteristics, and
HOW TO OBTAIN SERVICE
displays performance information on a digital dis-
play panel. It accepts menu-driven control and set- Always give the complete Model, Specification and
up input from the push button switches on the front Serial number of the generator set as shown on the
panel. nameplate when seeking additional service
information or replacement parts. The nameplate is
TEST EQUIPMENT located on the back of the control box.
To perform the test procedures in this manual, the WARNING Incorrect service or replacement of
following test equipment must be available parts can result in severe personal injury or
True RMS meter for accurate measurement of death, and/or equipment damage. Service per-
small AC and DC voltages. Fluke models 87 or sonnel must be trained and experienced to per-
8060A are good choices. form electrical and mechanical service. Read
Grounding wrist strap to prevent circuit board and follow Important Safety Instructions on
damage due to electrostatic discharge (ESD). pages iii and iv.
Battery Hydrometer.
1-2
Redistribution or publication of this document
by any means, is strictly prohibited.
2. Control Operation (Without Display)
GENERAL under load should be avoided to help prolong the
reliability of the generator set.
The following describes the function and operation
of the PowerCommand 1301 Control (without dis- The OFF mode is also used to acknowledge shut-
play). The switch/indicator and hour meter are lo- down messages after the fault has been corrected.
cated on the face of the control panel as illustrated Moving the switch to the OFF position clears the
in Figure 2-1. switch fault indication and resets the control.
REMOTE (Auto) Mode: The Remote (Auto) mode
CONTROL PANEL
is enabled by moving the control rocker switch to
Figure 2-1 shows the features of the front panel. It the bottom position. The Remote mode enables
includes onethree position rocker switch to oper- start/stop control of the genset from a remote loca-
ate the genset and a total hours genset meter. tion.
START Mode: The Start mode is enabled by mov-
Start/Off/Remote (Auto) Switch ing the control rocker switch to the top position.
This rocker switch is used to select the three operat- When moved to this position, the control will acti-
ing modes of the genset (Start/Off/Remote). This vate the starting system.
switch also contains a lamp which is used to indi- Switch Indicator
cate engine genset running and genset fault codes.
Used to indicate the following genset status:
OFF Mode: The OFF mode is enabled by moving
the control rocker switch to the middle position. The Genset running constant on
OFF mode will disable the control Auto or Manual Genset fault code flashing (refer to Section 5
modes. to interpret fault code indicator)
If moved to the OFF position during generator set Total Hours Meter
operation (manual or remote start), the engine will
immediately shut down. If possible, hot shutdown Displays the total hours of genset operation.
THREE POSITION
ROCKER SWITCH
HOUR
METER
J1-5
J2
J1
S1 SLEEP
MODE
SELECTION
SWITCH
OFF MODE
BUTTON
The function of the four selection buttons varies with When the symbol is displayed, the selec-
each menu. tion button is used to navigate to an editable
field within a menu.
When the symbol is displayed, the When the + and symbols are displayed, the
selection button can be used to switch to selection buttons are used to increase or de-
Auto mode. crease a parameter or value shown on the
When the symbol is displayed, the selec- screen.
tion button can be used to switch to Manual When changing values, pressing the button be-
Run mode. low the + symbol increase the value and press-
When the up and down triangles ( and ) ing the button below the symbol decreases
are displayed, the selection buttons are used the value.
to navigate between a series of submenus. When SAVE is displayed, the selection but-
ton is used to save changes made in a sub-
NOTE: When any Operator menu (Figure 3-12
menu. If the Previous Menu button is
is displayed, a series of Service menus
pressed before pressing SAVE, the
can be viewed by simultaneously
changes are not saved.
pressing the and selection but-
tons for two seconds. Some menus include a list of numbered sub-
jects. These menus include numbers in pa-
NOTE: When a fault is displayed, it can be renthesis (for example, (1)) displayed above
cleared from the front panel by press- the selection buttons. The selection buttons
ing the or button. are then used to display submenus of the
subjects included in the list.
When a symbol is displayed, the selection
button can be used to abort the Auto or When a black box is displayed, the
Manual Run mode and return to the Operator selection button has no function.
Press the button to view the previous main Press the button to switch to the Off mode. The
menu. Off mode will disable the control Auto or Manual
modes.
NOTE: In the Screen Adjust menu, settings are not
If the button is pressed during generator set op-
saved when the button is pressed. eration (manual or remote start), the engine will im-
mediately shut down. If possible, hot shutdown un-
The button is also used to acknowledge warn- der load should be avoided to help prolong the reli-
ing and shutdown messages after the fault has ability of the generator set.
been corrected. Pressing this button clears the fault
from the front panel display and the previous menu The button is also used to acknowledge warn-
is redisplayed. ing and shutdown messages after the fault has
been corrected. Pressing this button clears the fault
NOTE: Pressing the or button also clears the from the front panel and resets the control.
fault from the front panel display. Not in Auto Indicator
This red lamp is lit when the control is not in the Auto
mode.
Shutdown Status Indicator
This red lamp is lit when the control detects a Shut-
down condition. The generator set cannot be
started when this lamp is on. After the condition is
corrected, the lamp can be reset by pressing the
(off) button.
Warning Indicator
OFF
This yellow lamp is lit whenever the control detects
BUTTON a warning condition. This lamp is automatically shut
off when the warning condition no longer exists.
Remote Start Indicator
This green lamp indicates the control is receiving a
remote run signal.
Auto Indicator
PREVIOUS MAIN
MENU BUTTON This green lamp indicates the control is in Auto
mode. Auto mode can be selected by pressing the
selection button from any of the Operator me-
nus (see Figure 3-12).
Manual Run Indicator
This green lamp indicates the control is in the Manu-
al Run mode. Manual Run mode can be selected by
FIGURE 3-3. PREVIOUS MAIN MENU AND OFF pressing the selection button from any of the Op-
BUTTONS erator menus (see Figure 3-12).
214
A SYMBOLIC
cleared from the control panel display by pressing WARNING
the , , or button. FAULT
EXAMPLE OF
A SYMBOLIC
SHUTDOWN 1
FAULT
AUTO MODE
SELECTED
Engine Status This menu displays genset power (in kVA), frequen-
cy, and engine speed (RPM). (In applications with-
Alternator Status out current transformers, the kVA is not shown.)
Line-to-Line Voltage Alternator Line-to-Line Voltage Menu
Line-to-Neutral Voltage
This menu displays L1-L2, L2-L3, and L3-L1 line-to-
Alternator Amperage line voltages for three phase applications only.
To navigate between the Operator menus, press Alternator Line-to-Neutral Voltage Menu
the buttons next to the and symbols in the
graphical display. This menu displays line-to-neutral voltages for L1,
L2, and L3 for three phase wye configurations only.
The Operator menus can be used to select Auto or (In delta configurations, this menu is not shown.)
Manual Run modes.
Alternator Single Phase Voltage Menu
Appendix A provides a block diagram that illustrates
This menu displays L1-N, L2-N, and L1-L2 voltages
the sequence of how the Operator Menus are dis-
played.
for single phase applications only.
Alternator Amperage Menu
Engine Status Menu
This menu displays L1, L2, and L3 amperage. (In
This menu displays the engine starting battery volt- applications without current transformers, this
age, engine coolant temperature, engine oil pres- menu is not shown.)
THREE PHASE
ONLY SINGLE
PHASE
ONLY
THREE PHASE
WYE ONLY
CURRENT
SENSE ONLY
THREE PHASE
ONLY SINGLE
PHASE
ONLY
THREE PHASE
WYE ONLY
CURRENT
SENSE ONLY
The first Service Menu can be viewed from any of Status Menu
the Operator menus by simultaneously pressing the
The Status menu is displayed when the (5) button is
and selection buttons for two seconds. The
pressed on the second Service Menu. The Status
first Service Menu provides access to the following
menu shows the following:
menus:
Voltage regulator (drive) level, in percentage
Setup Menus Used by Service personnel. of duty cycle
Adjusting the Setup menus is restricted by a
password and is described in Section 6. To Governor regulator (drive) level, in percent-
view the Setup menus only, press the VIEW age of duty cycle. This value is only dis-
button on the Setup password menu. played if the governor is enabled.
2ND 3RD
SERVICE SERVICE
MENU MENU
OR
Fault 2
Oldest Fault
(Maximum of 5)
BASE
BOARD
*CT2
FIGURE 4-2. BLOCK DIAGRAM
*CT3
4-2
SLEEP MODE
RS-485 SELECTION CUSTOMER
COMMUNICATIONS CONNECTIONS
S1
TB2 TB1
DS1 STATUS
INDICATOR
J11
J13
VOLTAGE/
FIELD
ENGINE
HARNESS
K8 K7 J12
FUEL STARTER
SHUTOFF RELAY CTS
RELAY
With Display: Press the button to switch to An example of a single digit fault code Two
the Off mode. blinks, followed by a two-second pause indicates a
fault code of 2.
2. Turn off or remove AC power from the battery
charger. An example of a two digit fault code first digit in
the code is flashed, followed by a half-second
3. Remove the negative () battery cable from the pause, and then the second digit is flashed, fol-
generator set starting battery. lowed by a two-second pause.
CURRENT
TRANSFORMERS
PANEL FUSES
F1, F3, F4
AC TERMINALS
TB1
BASE
BOARD
6. Engine misfires a. Air fuel ratio too lean. Adjust main fuel valve. Refer to Section 8.
b. Inspect spark plugs/gap.
c. Check spark plug wires.
d. Check ignition coil. See Ignition System, Section 8.
7. Excessive crank time (seven seconds or a. See step 8 in this table.
more) before starting b. Gas regulator may require adjustment. See Fuel System, Section
8.
8. Gaseous fuel delivery t o the set is inad- Check the gas supply pressure at the regulator input. Refer to Sec-
equate or fuel pressure is too high at tion 8.
light loads.
9. The engine is worn. Service the engine according to Section 8.
1 Indicates engine has overheated (coolant temperature has risen above the shut-
HIGH COOLANT TEMP down trip point).
Lamp: Shutdown Allow engine to cool down completely before proceeding with the following checks:
a. Check coolant level and replenish if low. Look for possible coolant leakage points
and repair if necessary.
b. Check for obstructions to cooling airflow and correct as necessary.
c. Check fan belt and repair or tighten if necessary.
d. Check blower fan and circulation pumps on remote radiator installations.
e. Reset control and restart after locating and correcting problem.
2 Indicates engine oil pressure has dropped below the shutdown trip point. Check oil
LOW OIL PRESSURE level. If oil level is low, replenish. Reset control and restart.
Lamp: Shutdown
12 Indicates that one or more of the phase voltages has exceeded 130% of nominal
HIGH AC VOLTAGE for 1.0 second, or has exceeded 110% of nominal for 10 seconds.
Lamp: Shutdown
13 Indicates that one or more of the phase voltages has dropped below 85% of nomi-
LOW AC VOLTAGE nal for 10 seconds.
Lamp: Shutdown
14 Indicates frequency is 10% above base frequency for 10 seconds.
OVER FREQUENCY
Lamp: Shutdown
15 Indicates that engine speed has dropped below 90% of nominal for 10 seconds.
UNDER FREQUENCY Check fuel supply pressure, intake air supply and load.
Lamp: Shutdown
27 Indicates a loss of all three voltage sense leads or failure in excitation circuit.
EXCITATION FAULT Check field wiring (X1 and X2) for shorts or opens. (Refer to Section 7.)
Lamp: Shutdown
31 Indicates engine has exceeded normal operating speed. The threshold is 1725
OVERSPEED RPM (50 Hz) or 2075 RPM (60 Hz).
Lamp: Shutdown Possible cause single step large block load removal. Reset control and restart.
38 Indicates that the Field AVR Duty Cycle has been at the maximum for at least 15
FIELD OVERLOAD seconds.
Lamp: Shutdown
45 Indicates that no magnetic pickup pulses are sensed for a Loss of Speed delay.
SPEED SIGNAL LOST
Lamp: Shutdown
46 Indicates that an individual phase of alternator output current has exceeded 150%
HIGH AC CURRENT of the rated output current continuously for more than 10 seconds.
Lamp: Shutdown Check load and load lead connections.
2. Move the rocker switch to the OFF position or press the OFF button.
204, 205 The nature of the fault is an optional customer selection. Example inputs: Low
CUSTOMER INPUT #1, #2 Coolant Level, Low Fuel Pressure, Ground Fault, etc.
Lamp: Warning Each of the fault functions can be programmed (using service tool), as follows:
Warning or Shutdown (Default: Warning) (See fault code 75/76 for Shutdown)
Change display name using up to 32 characters.
212 Indicates that the control has sensed that the engine coolant temperature sensor
COOL SENSOR OUT OF output is out of range (high or low). Check sender/connectors/wires.
RANGE
Lamp: Warning
213 Indicates battery voltage supply to the control is approaching a low level at which
LOW BATTERY unpredictable operation will occur.
Lamp: Warning a. Discharged or defective battery.
Check the battery charger fuse.
Recharge or replace the battery.
b. Poor battery cable connections. Clean the battery cable terminals and tighten all
connections.
c. Check battery wiring/calibration.
d. Check engine DC alternator. Replace engine DC alternator if normal battery
charging voltage is not obtained.
e. Check battery charge voltage float level if applicable (raise float level).
214 Indicates battery voltage supply to the control is approaching a high level at which
HIGH BATTERY damage to the control can occur. Check float level on battery charger if applicable
Lamp: Warning (lower float level). Check battery wiring/calibration.
215 Indicates engine oil pressure has dropped below the warning trip point. If genera-
PRE-LOW OIL PRESSURE tor is powering critical loads and cannot be shut down, wait until next shutdown
Lamp: Warning period and then follow code 2 procedure.
216 Indicates that one or more of the phase currents has exceeded 110% of nominal
HIGH AC CURRENT for 60 seconds.
Lamp: Warning Check load and load lead connections.
217 Indicates that the control has sensed that the engine oil pressure sensor output is
OIL PRESS SENSOR OUT out of range (high or low). Check sender/connectors/wires.
OF RANGE
Lamp: Warning
219 Indicates the battery charging alternator has not reached an acceptable voltage
CHARGER FAILURE range within the selected period (default = 120 seconds).
Lamp: Warning a. Fault threshold is not set correctly. Refer to Engine Protection Submenus in Sec-
tion 6.
b. Charging alternator is defective. Refer to engine service manual.
221 Indicates that during cranking, the battery voltage is at or below the weak battery
WEAK BATTERY warning trip point for a time greater than or equal to the weak battery set time. See
Lamp: Warning code 213 for corrective action.
222, 223, 224 The nature of the annunciator fault is an optional customer selection.
ANNUNCIATOR FAULT 1, 2,
3
Lamp: Warning
225 Indicates a mismatch in the configuration of one of the annunciator relay outputs.
ANNUNCIATOR OUTPUT
CONFIGURATION ERROR
Lamp: Warning
1ST
GENSET
SERVICE
MENU
2ND
GENSET
SERVICE
MENU
Volts AC: Displays the AC voltage (190, 200, Start: The genset start time delay can be ad-
208, 220, 230, 240, 380, 400, 416, 440, 460, justed from 0 to 300 seconds.
or 480 VAC).
Stop: The genset stop time delay can be ad-
Hertz: Displays the genset frequency (50 or
justed from 0 to 600 seconds.
60 Hz). The control selects limits, gains, and
frequency values based upon this selection.
Cycle Crank Menu
No. of Phases: Displays the number of
phases (1 or 3). The Cycle Crank menu allows for configuring the
Phase: Displays the phase type (Delta or generator for all starting modes (manual and re-
Wye). mote), as follows:
Genset Menu, Part 2 Crank: The cranking period can be set from 3
to 30 seconds. This time limit is used to de-
The second genset menu allows for enabling or dis- termine a Fail to Start status.
abling glow plugs and charging alternators.
Rest: The minimum amount of time between
Glow Plug: Allows control of Glow Plugs for crank attempts can be set from 0 to 60 sec-
a particular genset (Yes or No) onds.
Charging Alt. Enable:
Attempts: The maximum number of times the
A starter disconnect will occur whenever any starter can be engaged when attempting to
one of the following three possible signals start the engine with cycle cranking can be
reaches its disconnect setpoint. set from 1 to 7 attempts.
PART 2
A
CONTINUED ON
PAGE 6-9
BATTLE SHORT:
ACTIVE/INACTIVE IS ONLY
DISPLAYED IF THE SWITCH
INPUT IS SET TO
OPERATOR PANEL
YES NO
K
OR
G
C
GO TO AVR
SETUP MENUS
ON PAGE 6-13 IF AVR IS NOT
ENABLED
OR
YES NO IF AVR IS
ENABLED
OR
H
GO TO
E PAGE 6-13
CONTINUED
D ON PAGE 6-11
GO TO
GOVERNOR
SETUP MENUS
ON PAGE 6-15
RETURN TO
PAGE 6-9
G
Volts/Hz Rolloff Menu V/Hz Knee: The Knee Frequency can be ad-
justed from 0.0 to 10.0 Hertz in 0.1 Hz incre-
The Volts/Hz Rolloff function helps optimize the ments. When generator set speed decreases
gensets response to added load. If the engine by more than the value of the knee frequency,
speed drops below nominal frequency, the control the generator set voltage decreases by the
automatically drops the voltage until the engine %/Hz value.
speed starts to recover. V/Hz Rolloff: The Rolloff setting can be ad-
This menu allows for adjusting the knee frequency justed from 0.0 to 5.0 percent of rated volt-
and voltage setpoint slope parameters. The knee age, in 0.1% increments.
frequency is the value below nominal frequency at
which the rolloff function begins. For example, if the Regulator Gains Menu
knee frequency is set to 5 Hz on a 60 Hz genset, this The Regulator menu allows for setting proportional
function begins when the frequency drops below 55 Gain, Integral Gain, and Damping values.
Hz.
Slope refers to how fast the voltage is rolled off be- Gain: The proportional Gain (K1) multiplier
low the knee frequency. The voltage is rolled off the can be set from 5 to 1000%. This allows for a
slope percent setting for every 1 Hz below the knee. scale factor of 0.05 to 10.0.
For example, on a 60 Hz genset, if the slope is set to Int: The Integral Gain (K2) multiplier can be
5% and the knee frequency is set to 5 Hz, then if the set from 5 to 1000%.
frequency drops to 54 Hz, the voltage set point is re-
duced 5%. If the frequency drops to 53 Hz, the volt- D: The Damping adjustment can be set from
age set point is reduced 10%, etc. 95 to 105%.
RETURN TO
PAGE 6-9
RETURN TO
PAGE 6-11
The Meter Calib menu allows for adjusting the actu- Metering Current Adjust Menu
al output voltage of the genset. The percentage can
be set from 90 to 110%. The alternator voltage is The Metering Current Adjust menu allows for ad-
also shown on this menu. justing metered amps.
1. With the genset OFF, attach a calibrated am-
Freq. Adjust Menu meter to L1.
The Frequency Adjust menu allows for adjusting 2. Start the genset and allow it to reach normal
the genset frequency. The frequency can be adjust operating speed.
from 6.0 to +6.0 Hz. The actual frequency is also 3. Display the Metering Current Adjust menu.
shown on this menu. 4. Load the genset to maximum rated kVA at
rated voltage.
Metering Voltage Adjust Menu
5. Calibrate the reading for L1 current so that the
The Metering Voltage Adjust menu allows for ad- reading on the display agrees with calibrated
justing metered genset line voltage. ammeter.
1. With the genset OFF, attach a calibrated volt- 6. After adjusting, press the SAVE button to save
meter to the AC output from L1 to L2. (L1 to the setting.
Neutral for single phase alternators.)
7. Shut the generator set OFF.
2. Start the genset and allow it to reach normal
8. Repeat steps 1 through 7 for L2 and L3. (In step
operating speed.
1, attach meter to L2 to calibrate L2 current,
3. Display the Metering Voltage Adjust menu. and L3 to calibrate L3 current.)
The Annunciator submenus are available by press- The annunciator has three possible customer-de-
ing the (4) button on the second Genset Service fined fault conditions that can be shown on the PCC
menu (see Figure 6-3). 1301 display. The Annunciator Fault Text message
menus are used to enter an event type and descrip-
Seven annunciator submenus (see Figure 6-10) tion for those three customer-defined annunciator
can be used to define three Annunciator Fault Text faults.
messages and four Annunciator Output Maps. Type: Enter the event type (Warning, Shut-
down or Event.
Enter a brief description of the event (up to
32 characters).
CONTINUED ON
PAGE 6-23
SETUP
In the following menu entry descriptions, the default
PASSWORD
parameter/value is not shown because the default MENU
value is subject to change by model. Always create
and refer to the initial capture file for factory default
settings of system parameters/values.
To enter the Genset Setup password 1209: NOTE: If the button is pressed before
1. With the first character highlighted, press the pressing the SAVE button, the
button below to the + or symbols until the val- changes are not saved.
ue reads 1.
6. Press the button to return to the genset
2. Press the arrow selection button to move Setup Menus menu.
to the next numeric character.
3. Press the button below the + or symbols until 7. To return to the Service Menu from the genset
the value reads 2. Setup Menus menu, press the button.
1ST
GENSET
SETUP
MENU
2ND
GENSET
SETUP
MENU
The Genset submenus are available by pressing The kVA Rating menu displays the kVA rating of
the (1) button on the first Genset Setup menu (see single-phase or three-phase, 50 or 60 hertz standby
Figure 6-12). genset systems. These value are used by the con-
trol to determine what is 100% load. The values
Appendix A provides a block diagram that illustrates must match the kVA rating of the genset application
the sequence of how the Genset Setup Submenus and cannot be more than 2000 kVA.
are displayed.
3Ph/50Hz: The three phase, 50 Hertz rating
Figure 6-13 (3 sheets) is a block representation of can be set from 0 to 2000 kVA.
the Genset Submenus.
3Ph/60Hz: The three phase, 60 Hertz rating
Genset Menu can be set from 0 to 2000 kVA.
1Ph/50Hz: The single phase, 50 Hertz rating
The Genset menu is used to set the CT Ratio, en- can be set from 0 to 2000 kVA.
able the Magnetic Pickup Unit (MPU), set the num-
ber of teeth pulses per revolution on the Flywheel, 1Ph/60Hz: The single phase, 60 Hertz rating
and set the Speed/Frequency Ratio. can be set from 0 to 2000 kVA.
CT Ratio: The CT Ratio value must be set to Prime kVA Rating Menu
match the CT Ratio of the current transform-
ers on the genset. The kVA Rating menu displays the kVA rating of
single-phase or three-phase, 50 or 60 hertz prime
MPU Enable: Displays whether or not the genset systems. These value are used by the con-
Magnetic Pickup Unit is installed (Yes or No). trol to determine what is 100% load. The values
must match the kVA rating of the genset application
Fly. Teeth: The total number of teeth pulses and cannot be more than 2000 kVA.
per revolution on the flywheel (used for elec-
tronic governed systems) can be set from 0 3Ph/50Hz: The three phase, 50 Hertz rating
to 256. can be set from 0 to 2000 kVA.
RPM/Hz Ratio: Allows for setting the Speed/ 3Ph/60Hz: The three phase, 60 Hertz rating
Frequency Ratio to 20, 30, or 60 RPM/Hz. can be set from 0 to 2000 kVA.
1Ph/50Hz: The single phase, 50 Hertz rating
Application Rating Select Menu can be set from 0 to 2000 kVA.
The genset application rating can be set to either 1Ph/60Hz: The single phase, 60 Hertz rating
Standby or Prime. can be set from 0 to 2000 kVA.
CONTINUED ON
PAGE 6-31
12V 24V
OR
D D
C
CONTINUED ON
PAGE 6-33
SWITCH SENDER
OR
CONTINUED ON
PAGE 6-41
CONTINUED ON
PAGE 6-43
The PCC Base board (Figure 6-17) provides con- Enter a brief description of the event (up to 32
nection points (TB1) for remote control and monitor characters).
options. The InPower service tool or access to the Genset
Service Menus is required to modify the customer
TB1 Customer Inputs fault inputs.
Available options will vary between PCC1301 control
models (PCC with or without display). TB1 Customer Outputs
Refer to Page 9-6 for typical connections to TB1. Available options will vary between PCC1300 control
Remote Start: When the control is in Auto/Remote models (PCC with or without display).
mode, grounding this input initiates the engine
cranking and start sequence. This circuit must be Refer to Page 9-6 for typical connections to TB1.
opened to permit resetting a shutdown condition
Customer Outputs 1 and 2: One set of normally
with the Reset input. (The remote stop is actually
open (NO) contacts, rated for 2 amps at 30 VDC for
the removal of the remote start signal to the control.)
each of the two output signals. The relays can be
Local/Remote Emergency Stop: Grounding this used to control small devices and indicator lamps.
input causes an immediate shutdown. Emergency
stop must be reset at the front panel. The nature of the customer output signal (contacts
closed) is an optional customer selection. Example
Customer Fault Inputs 1 and 2: Grounding any outputs: Genset running (event), common warning,
one of these inputs activates the corresponding common shutdown, etc. (Refer to Table 5-3 for the
warning or shutdown sequence. warning and shutdown code listing and page 5-3 for
the event code listing.)
External sensing equipment must be connected to
the designated digital input. Each relay can be independently programmed to
The nature of the fault is an optional customer energize by entering the a code number (0 through
selection. Example inputs: Low Coolant Level, Low 255, default = 0) for the desired event.
Fuel Pressure, Ground Fault, etc.
The InPower service tool or access to the Genset
Each of the two fault functions can be programmed Service Menus is required to modify the customer
as follows: outputs.
TB1
BASE BOARD
OIL SENDER
TEMPERATURE SENDER
ENGINE
FLYWHEEL
RING GEAR
Refer to the Reconnection Diagram to identify the B. Route the load lead (U, V or W) through the ap-
generator output leads/phase that must be routed propriate CT (refer to Reconnection Diagram).
through each CT, and also appropriate transformer C. The CTs have dual secondaries (3 pins). The
post selection for control sensing leads. The trans- CT secondary wire marked 1 is connected to
formers are labeled CT1, CT2 and CT3 on the re- pin 1 of the CT. CT secondary wire marked 2/3
connection wiring diagram. (The Reconnection Dia- is connected to pin 3 for low voltage gensets.
gram is located on the control box cover.) (Refer to Reconnection Diagram.)
ROTOR MAIN
SHAFT ROTOR
BEARING
O-RING EXCITER
ROTOR
END
BELL COOLING
BLADES
EXCITER THROUGH
STATOR STUD
+
F1
DIODE
12 VDC EXCITER DISCONNECT BASE
BATTERY BASE BOARD LEADS TO
STATOR BOARD EXCITER STATOR
F2
ONE OF SIX DIODE TERMINALS FOR CONNECTING THE POSITIVE (+) DIODE AS- NEGATIVE () DIODE AS-
EXCITER WINDING LEADS. TORQUE THE TERMINAL SEMBLYMOUNT ON SEMBLYMOUNT ON
NUTS TO 24 LB-IN (2.6 N-M) AND USE A FLAT WASHER TO LEFT-HAND SIDE WHEN RIGHT-HAND SIDE
PROTECT THE LEAD CONNECTOR ROTOR KEY IS UP WHEN ROTOR KEY IS UP
ONE OF TWO
MOUNTING
SCREWS FOR
EACH DIODE
ASSEMBLY
Connect either or both leads to the megger and con- Reconnect the rotor and surge suppressor leads
duct the test as instructed under Testing Winding In- and torque the terminals to 24 lb-in (2.7 N-m) when
sulation Resistance. reassembling.
TWO SETS OF LEADSFOR THE MAIN ROTOR AND FOR A SURGE SUPPRESSORPASS
THROUGH THE EXCITER ROTOR AND ARE CONNECTED TO THE F1+ AND F2 TERMINALS
ON THE ROTATING RECTIFIER ASSEMBLY. DISCONNECT THE LEADS FROM THE TERMINALS
WHEN TESTING THE MAIN ROTOR WINDINGS AND THE SURGE SUPPRESSOR.
REFERENCE
STACK
LENGTH
REFERENCE LENGTH
1. These are approximate reference dimensions for aiding generator identification. The corresponding rotor stack lengths are slightly greater than
the stator stack lengths.
2. Stator resistances are 5% of nominal at 77 F (25 C) and rotor resistance are 10%.
Never disconnect the battery cables while the 8. If it is necessary to remove the rotor, cinch a
generator set is cranking or running. hoisting strap around the middle of the main ro-
tor laminations and then remove the bolts se-
Always disconnect a battery charger from its curing the generator drive disc to the flywheel.
AC source before disconnecting the battery
cables. 9. Remove the two mounting screws if it is neces-
sary to remove the exciter stator from the gen-
Always disconnect the negative () cable first erator end bell.
and reconnect it last. (This prevents arcing if the
tool on the positive terminal touches grounded 10. Use a gear puller if it is necessary to remove
metal.) the rotor bearing.
A. The chamfered edge of the drive disc pe- 8. Wipe the bearing bore in the end bell lightly with
rimeter faces away from the rotor to make molybdenum disulfide grease and make sure
assembly to the flywheel easier. the rubber O-ring is in place.
B. The fan blade assembly goes on first. (It 9. Mount the end bell to the stator assembly, mak-
will be secured with the disc-to-flywheel ing sure the rotor bearing is fully seated in the
bolts.) bore and that the end bell part number is at the
top. Torque the nuts on the generator through-
C. The rounded edges of the washers are on studs to 28 lb-ft (38 N-m). Pull the field leads
the disc side. out the same opening as the main stator leads.
3. If the rotor was removed from the engine fly- 10. Secure the end bell cover plate and torque the
wheel, torque the eight drive disc-to-flywheel four screws to 8 lb-in (3.8 N-m).
bolts to 39 lb-ft (52 N-m) when remounting.
11. Reconnect or remount all the other compo-
4. If the flywheel housing was removed, torque nents that were disconnected or removed un-
the bolts to 60 lb-ft (81 N-m) when remounting. der Disassembly.
Contact an Onan/Cummins distributor for the spe- 5. Remove the radiator fan (turn the nut clock-
cial tools required for engine disassembly and reas- wise).
sembly.
6. Remove the fuel gas components.
The following procedures for disassembly and 7. Remove the ignition coils if necessary.
reassembly are meant more as checklists than as
sequences that must be rigidly followed. It is as- 8. Remove the inlet and exhaust manifolds.
sumed that the generator set housing and genera-
tor have already been removed and that the engine 9. Remove the cylinder head covers.
electrical harness and fuel supply have been dis-
connected and that coolant and oil have been 10. Remove the lifting eye(s).
drained.
11. Remove the valve rockers and push rods.
WARNING Hot coolant is under pressure and 12. Remove the coolant pump.
can cause severe burns. Always let the engine
cool down before removing the pressure/fill 13. Remove the cylinder head and gasket.
cap.
14. Lift out the push rod tubes, rubber seals and
WARNING Accidental starting can cause se- washers.
vere personal injury or death. To prevent acci-
dental starting, push the control panel switch to 15. Remove the oil filter.
OFF and disconnect the negative () battery
cable from the battery before working on the 16. Remove the dipstick and crankcase door.
generator set. 17. Remove the oil pressure relief valve and oil
strainer.
Arcing can ignite battery gases and cause se-
vere personal injury and can cause voltage 18. Remove the connecting rod caps.
spikes that can damage generator set control
circuits. To reduce arcing: 19. Carefully remove any carbon build-up from the
top of the cylinder bore.
Never disconnect the battery cables while the
generator set is cranking or running. 20. Turn the crankshaft until the piston is at TDC.
Always disconnect a battery charger from its 21. Lift out the piston and connecting rod.
AC source before disconnecting the battery
cables. 22. Remove the ignition pickup module bracket
(leave modules attached to bracket) and mag-
Always disconnect the negative () cable first netic rotor only if it is necessary to remove the
and reconnect it last. (This prevents arcing if the gear cover (Step 26).
tool on the positive terminal touches grounded
23. Remove the fan belt. To do so if the pickup
metal.)
module bracket is not being removed
(Step 22), remove only the long lower right
Disassembly
bracket bolt and spacer (Page 8-35).
1. Remove the radiator hoses. 24. Install the flywheel locking tool.
2. Remove the radiator. 25. Remove the crankshaft pulley (turn the bolt
clockwise).
3. Remove the starter motor.
26. Remove the gear cover (front end).
4. Loosen the alternator to free the fan belt from
the alternator and fan pulleys and remove the 27. Remove the two camshaft thrust plate screws.
30. Remove the crankshaft pinion. 10. Heat the crankshaft pinion and install it with its
key and with its timing marks outward.
31. Remove the flywheel.
11. Install the oil pump.
32. Remove the flywheel housing.
12. Install the camshaft, aligning the timing marks
and making sure the thrust plate is located cor-
33. Remove the main bearing housing (flywheel
rectly.
end).
13. Install the hydraulic valve tappets.
34. Use a manifold bolt to remove the center main
bearing locating dowel(s): 1 on 2-cylinder, 2 on 14. Install the gear cover (front end).
3-cylinder and 3 on 4-cylinder engines.
15. Install the flywheel locking tool.
35. Gently withdraw the crankshaft.
16. Install the crankshaft pulley (turn the bolt
36. Remove the front main bearing and camshaft counterclockwise).
bearing shells.
17. Remove the flywheel locking tool.
Reassembly 18. Install the ignition magnetic rotor.
See Table 8-2 for thread torques and Table 8-3 for 19. Secure the ignition pickup modules to their
recommended gasket and shim sealers and thread bracket if they have been removed.
sealing and lubricating compounds. Always use
new gaskets when reassembling an engine. 20. Place the belt over the crankshaft pulley and
install the ignition pickup module bracket. The
Use engine lubricating oil on all moving parts, espe- belt goes outside the left and upper bracket
cially on bearing surfaces, valve stems and push bolts but inside the lower right bolt
rod cups. The piston/connecting rod assembly (Page 8-35).
should be submerged in oil and then thoroughly
drained just before installing it in the cylinder. 21. Install the pistons and connecting rods.
1. Install the main (crankshaft) and camshaft 22. Install the oil pump relief valve and strainer.
bearing shells.
23. Install the crankcase door and dipstick.
2. Install the front (gear-end) crankshaft thrust 24. Install the oil filter.
bearings.
25. Install the push rod tube seals, washers and
3. Install the crankshaft making sure the center tubes.
bearing dowel hole(s) line up correctly: 1 on
2-cylinder, 2 on 3-cylinder and 3 on 4-cylinder 26. Install the cylinder head and gasket.
engines.
27. Install the push rods and the valve rockers.
4. Install the rear (flywheel-end) crankshaft thrust
bearings. 28. Install the cylinder head covers.
34. Adjust the fan belt. 37. Install the radiator hoses.
35. Install the starter motor. 38. Install the fuel system and governor.
1. Crankcase Doors2, 3
and 4 cylinder engines
2. Gear Cover
3. Main Bearing Housing
4. Cylinder Heads2, 3
and 4 cylinder engines
1. Replace the thrust washer if the thickness is less than 2.20 mm (0.0866 inch).
2. Replace the spring if the length is 42.5 mm (1.67 inch) or less.
1. Install the hydraulic valve tappets in the crank- A - Cylinder Head Seal
case if they have been removed (Page 8-13). B - Crankcase Seal
C - Crankcase Seal Washer
2. Lightly coat the bores of the new push rod tube
seals (Figure 8-3) with grease.
3. Fit the seals into the crankcase and cylinder FIGURE 8-3. PUSH ROD TUBE SEALS
head(s) making sure that the washers which
are fitted underneath the crankcase seals are
in position.
9. Install the valve push rods. FIGURE 8-4. CYLINDER HEAD BOLT LOCATIONS
Removing a Valve:
4. Secure the cylinder head on its side in a soft- FIGURE 8-9. VALVE GUIDE AND OIL SEAL
jawed vice.
4. Remove the crankcase door and gasket. A - 2-cylinderNos. 4 and 9 are studs
B - 3-cylinderNos. 8, 1 and 9 are studs
Installing the Crankcase Door: C - 4-cylinderNos. 13, 4, 3 and10 are studs
2. Install the crankcase door with a new, dry gas- FIGURE 8-12. CRANKCASE DOOR TIGHTENING
ket and torque the bolts to 11 N-m (8 lb-ft) in the SEQUENCES
sequence shown.
7. Replace the pulley and bolt. Turn the bolt 5. Gently ease the camshaft out of the crankcase,
counterclockwise to tighten it, and torque it keeping it perpendicular to the front face of the
to 300 N-m (221 lb-ft). crankcase.
Compression Ring (Middle): This ring has a FIGURE 8-16. PISTON RING AND GAP LOCATIONS
tapered face in contact with the piston barrel.
The side marked TOP must face up when
installed.
1. Lift the housing into position. 5. Remove the bearing housing. If the flywheel
housing has been removed, use the two re-
2. Thread the bolts in finger tight. cesses in the 3 Oclock and 9 Oclock positions
to lever off the housing. If the flywheel housing
3. Torque the retaining bolts to 81.0 N-m (60.0 lb-
is still in place, turn the crank until the rear bal-
ft).
ance lobe is in position to use as a fulcrum to
The Main Bearing Housing lever off the housing.
The main bearing housing is secured to the crank- 6. Clean all traces of the old shim and compound
case at the flywheel end. It has an oil drain which from the housing and crankcase.
must be located at the bottom of the housing when it
is installed. A single shim, installed between the 7. Remove the old oil seal taking care not to dam-
housing and the crankcase, determines crankshaft age the bearings if they are to be reused.
end play. Lubricating oil is supplied through a drilled
Installing the Crankshaft Oil Seal: The crankshaft
hole in the side of the bearing housing which lines
oil seal can be installed before or after the main
up with a similar hole in the crankcase.
bearing housing is installed.
The crankshaft oil seal in the main bearing housing
is of the lip-type, for which an installation tool is 1. Lightly grease the sealing lip of the new seal.
available. See THE LUBRICATING SYSTEM
2. Place the seal squarely on the housing. Do not
(Page 8-29) for further information on oil seals.
use any sealing compound.
Removing the Main Bearing Housing:
3. Hold the oil seal tool onto the outside face of the
1. Remove the flywheel (Page 8-22). seal and drive the seal into the bearing housing
until it is flush with the outside face of the hous-
2. Remove the crankcase door (Page 8-14). ing.
The Thermostat
3. Clean any debris and the old seal from the ther-
mostat housing.
The engine is equipped with an electronic ignition The spark plugs must be in good condition and have
system powered by the 12 volt battery. The ignition the proper gap. Always thread a spark plug in by
system consists of a magnetic rotor bolted to the hand to prevent cross threading.
pulley end of the crankshaft, one or more ignition
modules (Hall-effect devices), one or more ignition
coils and the spark plugs (Figure 8-33). If the engine misses or performance deteriorates,
remove and examine the spark plugs and look for
the following problems:
The ignition module makes and breaks the primary
circuit of the ignition coil as the north and south
poles of the magnetic rotor pass by one after the Light tan, gray or reddish deposits: Normal
other on each revolution. Breaking the primary coil
circuit (at the point of ignition timing) causes the One spark plug fouled: Broken spark plug
field to collapse, inducing 20,000 volts or more in cable or low cylinder compression
the secondary coil. The energy in the secondary coil
is discharged across the spark plug to ignite the fuel
in the cylinder. Oil fouled: Malfunctioning crankcase breath-
er, worn rings, worn valve guides or seals
Quick Ignition Test
Burned or overheated: Leaking intake man-
ifold gaskets, lean fuel mixture
If the engine misfires, test the ignition system as fol-
lows.
Worn: Service life up.
WARNING Gaseous fuels are flammable and
explosive and can cause severe personal injury Ignition Coil
or death. Ventilate the area thoroughly before
conducting this test and make sure the manual
Inspect the high tension terminals for corrosion,
fuel shutoff valve is close. Keep a type ABC fire
looseness, cracks or other damage. Look for car-
extinguisher handy.
bon runners and other signs of electrical leakage.
Replace a damaged or leaking coil.
1. Close the manual fuel shutoff valve to prevent
gas from escaping during this test.
Double-Terminal Coils Replace a double-termi-
nal type of coil (2- and 4-cylinder engines) if primary
WARNING HIGH VOLTAGE: To avoid elec- resistance is not 3 to 5 ohms and secondary resist-
tric shock do not touch the spark plug ance 10,000 to 14,000 ohms.
cables during this test.
2. Disconnect each spark plug cable, in turn, from Single-Terminal Coils Replace a single-terminal
its spark plug and hold the end of the cable near type of coil (3-cylinder engines) if primary resist-
the end of the spark plug terminal with an insu- ance is not 2.8 to 4.4 ohms and secondary resist-
lated spark plug cable holder. Crank the engine ance 3600 to 5400 ohms.
and observe the spark. Service the ignition sys-
tem if the spark is weak, inconsistent or miss- Rotor-To-Pickup Air Gap
ing. If the spark is strong and consistent, the
problem is elsewhere.
If either the magnetic rotor or the pickup modules or
bracket have been loosened or removed, check the
Spark Plug Cables air gap between the rotor and modules while turning
the engine through one complete revolution. Loos-
Replace a spark plug cable if resistance across the en and resecure the bracket if the gap is less than
cable is not 3,000 to 15,000 ohms or if it appears 0.030 inch (0.76 mm) or more than 0.120 inch
damaged in any way. (2.29 mm) between the rotor and any module.
MAGNETIC ROTOR
FLYWHEEL SIDE OUT
IGNITION
MODULE SECONDARY SIDE (HIGH TENSION)
SPARK
PLUG
SCHEMATICPRIMARY SIDE
Red
DOUBLE-TERMINAL
IGNITION TYPE OF IGNITION COIL
Red + Black MODULE
B+
SINGLE-TERMINAL
TYPE OF IGNITION COIL
IGNITION COIL
TEST
LIGHT
Firing Order for 4Cylinder Engines: The firing Bright light (B+) at the negative () terminal of
order is 1342. The engine has two double-termi- the coil indicates that the circuit to ground
through the ignition module is open; dim light
nal ignition coils and two ignition modules, located (1 volt or less) that the circuit to ground is
180 apart. The ignition modules cause the two sets closed (schematic, Figure 8-33). The light will
of spark plugs, via the coils, to fire once every revo- stay on for somewhat less than half a revolution.
lution,* 180 apart. Therefore the front coil (closer to
the radiator) should be connected to spark plugs 1 4. Continue rotating the engine clockwise, but
and 4 and the rear coil to spark plugs 2 and 3. now very slowly. Stop when the light just be-
comes bright (meter jumps to 12 volts) and
Firing Order for 3Cylinder Engines: The firing check the timing mark on the flywheel.
order is 123. The engine has three single-termi-
5. If the timing is off:
nal ignition coils and three ignition modules located
120 apart. The ignition modules cause the spark A. Remove the fan/belt guard.
plugs, via the coils, to fire once every revolution.*
The ignition modules should be positioned 132 in B. Loosen the center bolt of the magnetic ro-
a clockwise direction on the mounting plate. tor.
Dynamic Timing Check: A dynamic check of tim- C. Rotate the engine so that the pointer in the
ing should indicate 10 BTDC for LPG and window in the housing points to 11 BTDC
20 BTDC for natural gas. or 21 BTDC on the flywheel, as appropri-
ate for the fuel being used.
Static Timing: Set timing by the following static
D. Rotate the rotor clockwise through at least
method to 11 BTDC for LPG and 21 BTDC for nat-
one rotation to catch the location where
ural gas. (The static timing settings are necessary
the light just becomes bright (meter jumps
to obtain the true [dynamic] timings of the specifica-
to 12 volts). Tighten the center bolt at that
tion.)
point.
WARNING Accidental starting can cause se- E. Recheck timing by repeating Steps 3
vere personal injury or death. Prevent starting and 4 and repeat Substeps C and D if the
by disconnecting the fuel shutoff solenoid. timing is still off.
* Though power strokes occur only once every other revolution, the spark plugs fire once every revolution because the magnetic rotor rotates at
the same speed as the crankshaft. The extra spark has no function.
3. Gently push the throttle lever counterclockwise 6. Reconnect the link to the throttle lever. Make
as far as it will go (closed throttle). If the throttle sure the linkage does not bind.
ACTUATOR
CLEVIS
LINK
THROTTLE
LEVER
THROTTLE
STOP SCREW
No. 630-2796 sh 1 of 1
Rev. C
Modified 12-04
No. 630-2936 sh 1 of 3
Rev. C
Modified 01-05
WIRING DIAGRAM
No. 01840207
Rev. F
Modified 05-05
No. 01840207
Rev. F
Modified 05-05
No. 620-0277 sh 1 of 1
Rev. B
Modified 01-05
CUSTOMER CONNECTIONS
THREE
PHASE
ONLY
SINGLE
PHASE
ONLY
THREE
PHASE
WYE ONLY
CURRENT
SENSE
AMPERAGE
MANUAL
RUN MODE
SELECTED
AUTO MODE
SELECTED
VIEWING AND
VIEWING ONLY ADJUSTING
GO TO GENSET
OR
SETUP AND
SERVICE MENUS
ON PAGE A-4
YES NO
OR
IF AVR IS
NOT
ENABLED
OR
IF AVR IS
YES NO ENABLED
OR
OR
GO TO GENSET
SERVICE MENUS
ON PAGE A-3
VIEWING AND
VIEWING ONLY ADJUSTING
OR
FIGURE A-3. GENSET SETUP AND SERVICE MENUS
12V 24V
OR
OR
A-4
SWITCH SENDER
OR