Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PIP ARC01015 Architectural and Building Utilities Design Criteria

Download as pdf or txt
Download as pdf or txt
You are on page 1of 39

COMPLETE REVISION

December 2014

Process Industry Practices


Architectural

PIP ARC01015
Architectural and Building Utilities Design Criteria
PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES

In an effort to minimize the cost of process industry facilities, this Practice has
been prepared from the technical requirements in the existing standards of major
industrial users, contractors, or standards organizations. By harmonizing these technical
requirements into a single set of Practices, administrative, application, and engineering
costs to both the purchaser and the manufacturer should be reduced. While this Practice
is expected to incorporate the majority of requirements of most users, individual
applications may involve requirements that will be appended to and take precedence over
this Practice. Determinations concerning fitness for purpose and particular matters or
application of the Practice to particular project or engineering situations should not be
made solely on information contained in these materials. The use of trade names from
time to time should not be viewed as an expression of preference but rather recognized
as normal usage in the trade. Other brands having the same specifications are equally
correct and may be substituted for those named. All Practices or guidelines are intended
to be consistent with applicable laws and regulations including OSHA requirements. To
the extent these Practices or guidelines should conflict with OSHA or other applicable
laws or regulations, such laws or regulations must be followed. Consult an appropriate
professional before applying or acting on any material contained in or suggested by the
Practice.

This Practice is subject to revision at any time.

Process Industry Practices (PIP), Construction Industry Institute, The University of


Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP Member
Companies and Subscribers may copy this Practice for their internal use. Changes or
modifications of any kind are not permitted within any PIP Practice without the express
written authorization of PIP. Authorized Users may attach addenda or overlays to clearly
indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users
may provide their clients, suppliers and contractors with copies of the Practice solely for
Authorized Users purposes. These purposes include but are not limited to the procurement
process (e.g., as attachments to requests for quotation/ purchase orders or requests for
proposals/contracts) and preparation and issue of design engineering deliverables for use
on a specific project by Authorized Users client. PIPs copyright notices must be clearly
indicated and unequivocally incorporated in documents where an Authorized User desires
to provide any third party with copies of the Practice.

PUBLISHING HISTORY
June 2002 Issued
February 2009 Complete Revision
December 2014 Complete Revision

Not printed with State funds


COMPLETE REVISION
December 2014

Process Industry Practices


Architectural

PIP ARC01015
Architectural and Building Utilities Design Criteria
Table of Contents
1. Introduction................................. 2 4.2 Products .............................................. 7
1.1 Purpose ............................................ 2 4.2.1 General ...................................... 7
1.2 Scope ............................................... 2 4.2.2 Concrete .................................... 7
4.2.3 Masonry ..................................... 7
2. References .................................. 2 4.2.4 Metals ........................................ 7
2.1 Process Industry Practices .............. 2 4.2.5 Woods ....................................... 7
2.2 Industry Codes and Standards ........ 2 4.2.6 Gypsum Board Assemblies ....... 7
2.3 Government Regulations ................. 5 4.2.7 Ceilings ...................................... 8
4.2.8 Flooring...................................... 8
3. Definitions ................................... 5 4.2.9 Thermal and Moisture
Protection .................................. 8
4. Requirements.............................. 6 4.2.10 Fire Resistance ........................ 9
4.1 Building Design ................................ 6 4.2.11 Doors and Windows ............... 10
4.1.1 General................................... 6 4.2.12 Specialties .............................. 10
4.1.2 Means of Egress .................... 6 4.2.13 Conveying Systems ............... 12
4.1.3 Foundation and Structure....... 6 4.3 Building Utilities ................................. 12
4.1.4 Materials and Methods of 4.3.1 Heating, Ventilation, and Air
Construction ........................... 6 Conditioning (HVAC) ............... 12
4.1.5 Pre-Engineered Metal 4.3.2 Electrical Work ........................ 26
Buildings ................................. 7 4.3.3 Communications ...................... 28
4.3.4 Fire Protection and Safety ....... 34
4.3.5 Plumbing.................................. 36

Process Industry Practices Page 1 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

1. Introduction
1.1 Purpose
This Practice provides the architect and the engineer with criteria for building design
and building utilities.
1.2 Scope
This Practice describes the minimum requirements for the design of buildings. This
Practice is intended to be used in conjunction with PIP ARC01016 - Building Data
Sheet, PIP CVC01017 - Plant Site Data Sheet, and PIP STC01015 - Structural
Design Criteria.
This Practice does not apply to open or partially enclosed industrial structures.

2. References
Applicable parts of the following Practices, industry codes and standards, and references shall
be considered an integral part of this Practice. The edition in effect on the date of contract
award shall be used, except as otherwise noted. Short titles are used herein where appropriate.

2.1 Process Industry Practices (PIP)


PIP ARC01016 - Building Data Sheet
PIP ARS08111 - Standard Steel Doors and Frames Supplier Specification
PIP ARS08390 - Blast Resistant Doors, Frames, and Related Hardware
Specification
PIP ARS08710 - Standard Steel Door Hardware Supplier Specification
PIP ARS13120 - Pre-Engineered Metal Buildings Specification
PIP CVC01017 - Plant Site Data Sheet
PIP STC01015 - Structural Design Criteria
PIP STC01018 - Blast Resistant Building Design Criteria
2.2 Industry Codes and Standards
Air Movement and Control Association (AMCA)
AMCA 511 - Certified Ratings Program Product Rating Manual for Air
Control Devices
Aluminum Association
Aluminum Design Manual
American Conference of Governmental Industrial Hygienists (ACGIH)
Industrial Ventilation: A Manual of Recommended Practice for Design
American Petroleum Institute (API)
API RP 540 - Electrical Installations in Petroleum Processing Plants

Process Industry Practices Page 2 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.


(ASHRAE)
ASHRAE Handbook - Fundamentals (I-P and SI Editions)
ASHRAE Handbook - HVAC Applications (I-P and SI Editions)
ASHRAE Handbook - Refrigeration (I-P and SI Editions)
ASHRAE 52.2 - Method of Testing General Ventilation Air-Cleaning Devices
for Removal Efficiency by Particle Size
ASHRAE 62.1 - Ventilation for Acceptable Indoor Air Quality
ASHRAE 110 - Method of Testing Performance of Laboratory Fume Hoods
ASHRAE 90551 - Fundamentals of HVAC Control Systems (I-P Edition)
ASHRAE 90552 - Fundamentals of HVAC Control Systems (SI Edition)
American Society of Mechanical Engineers (ASME)
ASME A17.1 - Safety Code for Elevators and Escalators
ASTM International (ASTM)
ASTM E84 - Standard Test Method for Surface Burning Characteristics of
Building Materials
ASTM E119 - Standard Test Methods for Fire Tests of Building Construction
and Materials
ASTM E1264 - Standard Classification for Acoustical Ceiling Products
ASTM F1066 - Standard Specification for Vinyl Composition Floor Tile
ASTM F1303 - Standard Specification for Sheet Vinyl Floor Covering with
Backing
ASTM F1344 - Standard Specification for Rubber Floor Tile
ASTM F1700 - Standard Specification for Solid Vinyl Floor Tile
ASTM F1860 - Standard Specification for Rubber Sheet Floor Covering with
Backing
ASTM F1861 - Standard Specification for Resilient Wall Base
ASTM F2195 - Standard Specification for Linoleum Floor Tile
Ceilings and Interior Systems Construction Association (CISCA)
Ceiling Systems Handbook
Recommended Test Procedures for Access Floors
Institute of Electrical and Electronic Engineers (IEEE)
IEEE 1100 - Recommended Practice for Powering and Grounding Electronic
Equipment
International Code Council (ICC)
International Building Code (IBC)
International Mechanical Code (IMC)
International Plumbing Code (IPC)

Process Industry Practices Page 3 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

International Society of Automation (ISA)


ISA 71.04 - Environmental Conditions for Process Measurement and Control
Systems: Airborne Contaminants
National Fire Protection Association (NFPA)
NFPA 10 - Standard for Portable Fire Extinguishers
NFPA 13 - Standard for the Installation of Sprinkler Systems
NFPA 14 - Standard for the Installation of Standpipe and Hose Systems
NFPA 45 - Standard on Fire Protection for Laboratories Using Chemicals
NFPA 70 - National Electrical Code (NEC)
NFPA 72 - National Fire Alarm and Signaling Code
NFPA 75 - Standard for the Fire Protection of Information Technology
Equipment
NFPA 80 - Standard for Fire Doors and Other Opening Protectives
NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating
Systems
NFPA 91 - Standard for Exhaust Systems for Air Conveying, of Vapors, Gases,
Mists, and Noncombustible Particulate Solids
NFPA 101 - Life Safety Code
NFPA 232 - Standard for the Protection of Records
NFPA 252 - Standard Methods of Fire Tests of Door Assemblies
NFPA 496 - Standard for Purged and Pressurized Enclosures for Electrical
Equipment
NFPA 2001 - Standard on Clean Agent Fire Extinguishing Systems
National Roofing Contractors Association (NRCA)
The NRCA Roofing Manual: Steep-slope Roof Systems
The NRCA Roofing Manual: Metal Panel and SPF Roof Systems
The NRCA Roofing Manual: Membrane Roof Systems
The NRCA Roofing Manual: Architectural Metal Flashing, Condensation
Control and Reroofing
NRCA Vegetative Roof Systems Manual
Scientific Equipment and Furniture Association (SEFA)
SEFA Desk Reference Manual
Sheet Metal and Air Conditioning Contractors National Association (SMACNA)
SMACNA - Fire, Smoke and Radiation Damper Installation Guide for HVAC
Systems
SMACNA - HVAC Duct Construction Standards - Metal and Flexible
SMACNA - Architectural Sheet Metal Manual
Steel Deck Institute (SDI)
Design Manual for Composite Decks, Form Decks and Roof Decks-No. 31

Process Industry Practices Page 4 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

Telecommunication Industry Association (TIA)


TIA-568 - Commercial Building Telecommunications Cabling Standards
TIA-569 - Telecommunication Pathways and Spaces
TIA-570 - Residential Telecommunications Infrastructure Standard
TIA-606 - Administration Standard for Commercial Telecommunications
Infrastructure
TIA-607 - Generic Telecommunications Bonding and Grounding (Earthing)
for Customer Premises
Underwriters Laboratory (UL)
UL 10B - Standard for Safety - Fire Tests of Door Assemblies
UL 263 - Standard for Safety - Fire Tests of Building Construction and
Materials
UL 555 - Standard for Safety - Fire Dampers
UL 555C - Standard for Safety - Ceiling Dampers
UL 1863 - Standard for Safety - Communications-Circuit Accessories
UL 60950-1 - Standard for Safety - Information Technology Equipment -
Safety - Part 1: General Requirements
2.3 Government Regulations
U.S. Department of Labor (DOL) / Occupational Safety and Health
Administration (OSHA)
OSHA 29 CFR Part 1910 - Occupational Safety and Health Standards
U.S. Department of Justice (DOJ) / Americans with Disabilities Act (ADA)
2010 ADA Standards for Accessible Design
Guidance on the 2010 ADA Standards for Accessible Design
Federal Communications Commission (FCC)
Part 68 - Connection of Terminal Equipment to the Telephone Network, Code
of Federal Regulations, Title 47, Telecommunications

3. Definitions
contract documents: Any and all documents, including codes, studies, design drawings,
specifications, sketches, practices, and data sheets, that the purchaser or engineer of record
has transmitted or otherwise communicated, either by incorporation or reference, and made
part of the legal contract agreement or purchase order between the purchaser and the supplier.

owner: The party who has authority through ownership, lease, or other legal agreement over
the building or buildings covered by this document.

purchaser: The party who awards the contract to the supplier. The purchaser may be the
owner or the owners authorized agent.

supplier: The party responsible for providing the design of the building and associated
utilities.

Process Industry Practices Page 5 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4. Requirements
4.1 Building Design
4.1.1 General
4.1.1.1 In addition to local jurisdiction and government requirements, all
buildings shall be designed in accordance with IBC and OSHA 29
CFR Part 1910 unless otherwise specified in the purchasers
PIP ARC01016 Data Sheet or in the contract documents.
4.1.1.2 Buildings shall be designed in accordance with 2010 ADA Standards
for Accessible Design where required by law.
Comment: The supplier can refer to the Guidance on the 2010 ADA
Standards for Accessible Design for more information.
Comment: Buildings inside the fence may be exempted from
2010 ADA Standards for Accessible Design if the plant
safety requirements state that only able-bodied personnel
are allowed in the plant, with approval of the Authority
Having Jurisdiction (AHJ).
4.1.1.3 Buildings shall be designed using the information provided in
purchasers PIP CVC01017 Data Sheet.
4.1.1.4 Buildings shall be designed for all energy conservation codes
required by national, state, and local government regulations.
4.1.1.5 Buildings designated by the owner to be used as a temporary safe
haven and/or shelter in place shall meet all applicable requirements
of this Practice and any additional requirements of the owner
specified in the contract documents.
4.1.2 Means of Egress
4.1.2.1 Buildings shall be provided with means of egress in accordance with
the applicable building codes and 2010 ADA Standards for
Accessible Design if applicable based on use and occupancy.
4.1.2.2 Industrial occupancies shall be in accordance with the egress
requirements of IBC.
4.1.3 Foundation and Structure
4.1.3.1 The foundation and structure of a building shall also be designed in
accordance with PIP STC01015.
4.1.3.2 Buildings required to be blast resistant shall also be designed in
accordance with PIP STC01018.
4.1.4 Materials and Methods of Construction
4.1.4.1 Each building shall be designed with materials and methods of
construction appropriate for its occupancy.
4.1.4.2 The type of construction shall be in accordance with requirements of
governing building codes.

Process Industry Practices Page 6 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4.1.5 Pre-Engineered Metal Buildings


Pre-engineered metal buildings shall be in accordance with PIP ARS13120.
4.2 Products
4.2.1 General
Unless the contract documents or applicable governing jurisdictions specify
more stringent requirements, products for buildings shall be designed in
accordance with this Practice.
4.2.2 Concrete
Concrete design shall be in accordance with IBC and PIP STC01015.
4.2.3 Masonry
Masonry design shall be in accordance with IBC and PIP STC01015.
4.2.4 Metals
4.2.4.1 Steel design shall be in accordance with IBC and PIP STC01015.
4.2.4.2 Floor and roof decks shall be in accordance with SDI Design Manual
for Composite Decks, Form Decks and Roof Decks No. 31.
4.2.4.3 Aluminum design shall be in accordance with the Aluminum
Associations Aluminum Design Manual.
4.2.5 Woods
4.2.5.1 Wood design using allowable stress design shall be in accordance
with IBC.
4.2.5.2 Structural lumber shall be grade No. 2 or better.
4.2.5.3 Non-structural lumber shall be grade No. 3 or better.
4.2.6 Gypsum Board Assemblies
4.2.6.1 Interior walls shall be regular-type gypsum board on minimum
22-gage steel stud framing.
4.2.6.2 Type X gypsum board shall be used where fire-resistance-rated
assemblies are required.
4.2.6.3 Cement backing board shall be used where tile finish is scheduled.
4.2.6.4 Unless otherwise specified in the contract documents, core thickness
of all gypsum board shall be 5/8 (16 mm).
4.2.6.5 Gypsum board assemblies shall be taped, floated, and sanded.
4.2.6.6 For gypsum board assemblies with fire-resistance ratings, materials
and construction shall be provided that are identical to those tested in
assembly in accordance with ASTM E119 by an independent testing
and inspecting agency that is acceptable to authorities having
jurisdiction, such as UL 263.
4.2.6.7 Furr-outs shall be gypsum board on steel stud framing.

Process Industry Practices Page 7 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4.2.6.8 Unless otherwise specified in the contract documents, gypsum board


walls shall have a latex enamel painted finish.
4.2.7 Ceilings
4.2.7.1 Suspended acoustical ceiling installation shall be in accordance with
CISCAs Ceiling Systems Handbook.
4.2.7.2 Suspended ceiling acoustical panels shall be in accordance with the
following requirements:
a. ASTM E1264 classifications as designated by types, patterns,
acoustical ratings, and light reflectance.
b. If required for fire rated assemblies, panels shall be fire
resistance rated.
c. If specified in the contract documents, panels shall be moisture
resistant and/or scrubbable.
4.2.7.3 Metal suspension system for acoustical panel ceiling shall be
standard direct-hung metal suspension systems. Suspension system
shall be fire resistance rated if required for fire rated assemblies.
4.2.8 Flooring
4.2.8.1 Solid vinyl floor tile shall be in accordance with ASTM F1700.
4.2.8.2 Vinyl composition floor tile shall be in accordance with ASTM
F1066.
4.2.8.3 Rubber floor tile shall be in accordance with ASTM F1344.
4.2.8.4 Vinyl sheet floor covering shall be in accordance with ASTM F1303.
4.2.8.5 Rubber sheet floor covering shall be in accordance with ASTM
F1860.
4.2.8.6 Linoleum floor tile shall be in accordance with ASTM F2195.
4.2.8.7 Resilient wall base shall be rubber or vinyl as specified in the
contract documents and shall be in accordance with ASTM F1861.
4.2.8.8 Access floor systems shall be in accordance with Section 4.2.12.2 of
this Practice.
4.2.9 Thermal and Moisture Protection
4.2.9.1 Insulation
1. Insulation shall have a flame-spread rating of less than 25 and
shall not be exposed to potential fire areas.
2. Insulation shall be used for separation between roof decks and
the roofing membranes.
3. Insulation shall be provided in exterior walls and roofs, and in
walls separating conditioned/non-conditioned areas or zones of
differing temperature requirements.

Process Industry Practices Page 8 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4. Unless otherwise specified in the contract documents, R values


shall be in accordance with energy conservation codes required
by national, state, and local government regulations and the local
environmental conditions but shall not be less than R-11 for
walls and R-19 for roofs.
4.2.9.2 Roofing Systems
1. Roofing systems shall be designed in accordance with the
appropriate NRCA Roofing Manual(s). NRCA Roofing Manuals
are as follows.
a. The NRCA Roofing Manual: Steep-slope Roof Systems
b. The NRCA Roofing Manual: Metal Panel and SPF Roof
Systems
c. The NRCA Roofing Manual: Membrane Roof Systems
d. The NRCA Roofing Manual: Architectural Metal Flashing,
Condensation Control and Reroofing
e. NRCA Vegetative Roof Systems Manual
2. Low-slope roofs shall have a minimum slope of 1/4 inch per foot
(21 mm/m).
3. Overflow relief openings shall pass through the parapet where
applicable in accordance with SMACNA Architectural Sheet
Metal Manual.
4. The roof structure shall be designed for ponding up to the height
of the relief openings and with consideration to the deflected
shape under the full load.
5. If equipment or piping is placed on a building roof, appropriate
supports shall be provided in accordance with NRCA Roofing
Manuals to hold them above the roof and a suitable walking or
working surface shall be provided to prevent damage to the
roofing.
6. Exposed sides of working area and walkway within 6.0 ft
(1800 mm) of edge of roof shall be protected with standard
safety devices or railings.
7. Equipment shall be mounted a minimum of 8 inches (200 mm)
above the roofline to allow for efficient maintenance and repair
of the roofing material.
8. Equipment supports shall not be constructed of wood.
9. Roof flashing shall be in accordance with SMACNA
Architectural Sheet Metal Manual.
4.2.10 Fire Resistance
Buildings shall be designed for fire resistance in accordance with IBC.

Process Industry Practices Page 9 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4.2.11 Doors and Windows


4.2.11.1 Standard steel doors and frames shall be in accordance with PIP
ARS08111.
4.2.11.2 Door hardware shall be in accordance with PIP ARS08710.
4.2.11.3 Unless otherwise specified in the contract documents, overhead
2 2
coiling doors larger than 64 ft (6 m ) shall be motorized. The side
rails shall be made from structural steel. Rails made from cold-
rolled shapes are not acceptable.
4.2.11.4 Fire-rated doors shall be in accordance with NFPA 252, NFPA 80,
and UL 10B.
4.2.11.5 Blast-resistant doors shall be in accordance with PIP STC01018 and
PIP ARS08390, and shall be provided with automatic door closers.
4.2.11.6 Unless otherwise specified by the owner and permitted by
applicable fire safety and building codes, windows shall not be
permitted in buildings within 200 ft (60 m) of hazardous process
facilities.
4.2.12 Specialties
4.2.12.1 Exterior Louvers
1. Louvers shall be all-welded construction with drainable blades
to minimize water penetration while maintaining a high free
area.
2. Louvers shall be designed with a frame that includes a jamb
gutter, a recessed drip lip at the head, and an extended water
stop on the back of the sill and insect screens where required.
3. Louvers shall be in accordance with AMCA 511 and shall bear
the AMCA-certified rating seal for both air performance and
water penetration.
4.2.12.2 Access Floors
1. Panels and support systems shall be in accordance with CISCA-
Recommended Test Procedures for Access Floors.
2. Floor panels shall have a Class A flame-spread rating when
tested without floor covering in accordance with ASTM E84.
Floor panel covering shall be as specified on the purchasers
PIP ARC01016 Data Sheet.
3. Unless otherwise specified on the purchasers PIP ARC01016
Data Sheet, floor height shall be 24 inches (600 mm) above sub-
floor.
4. The supporting system shall be as follows:
a. A commercial heavy duty, bolted grid system
b. Free from vibration squeaks

Process Industry Practices Page 10 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

c. Designed to support the equipment that is to be located on


the access flooring system
d. Resistant to seismic loads in accordance with purchasers
PIP CVC01017 Data Sheet.
5. The floor system shall support the following minimum loads:
a. Static: 1000 lb (4.5 kN), concentrated
b. Dynamic:
(1) 1000 lb (4.5 kN) rolling load for 3-inches diameter by
1-13/16-inches wide (75-mm diameter by 46 mm) with
10 passes
(2) 500 lb (2.25 kN) for 6-inches diameter by 1-1/2-inches
wide (150-mm diameter by 38 mm) with 10,000 passes
c. Impact load: 250 lb (1.12 kN)
6. The entire flooring system shall be electrically grounded.
4.2.12.3 Toilet Compartments and Urinal Screens
1. Materials shall be commercial heavy duty, non-permeable,
corrosion and stain resistant.
2. Compartment doors shall be a minimum of 24 inches (600 mm)
wide, 36 inches (900 mm) on ADA accessible compartments
3. Each compartment shall be provided with a coat hook, toilet
tissue dispenser, sanitary napkin disposal (women only) and
door latch. Accessible stalls shall be provided with grab bars.
4. Screw and bolt heads shall match accessory finish and shall be
vandal-resistant.
4.2.12.4 Restrooms
1. Restrooms shall be provided with soap dispensers, paper towel
dispensers, waste receptacle, mirrors, and a shelf for personal
items.
2. Restrooms without toilet compartments shall be provided with
additional accessories as described in Section 4.2.12.3 of this
Practice for toilet compartments.
3. Materials shall be commercial, heavy duty, and corrosion
resistant.
4. Anchors shall be concealed and shall be made of nonferrous
metal or stainless steel.
4.2.12.5 Laboratory Casework
1. All casework, work-surfaces and service fixture construction
and performance characteristics shall be in accordance with
applicable parts of the SEFA Desk Reference Manual.

Process Industry Practices Page 11 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

2. Countertops shall be constructed to resist chemicals, moisture,


physical abuse, and acid splatters and shall be resistant to
damage from heavy instruments and abrasive cleaners.
3. Casework components shall withstand the following minimum
loads without damage to the components or to the casework
operation:
a. Base unit load capacity 500 plf (7.3 kN/m)
b. Suspended units 300 plf (4.4 kN/m)
c. Drawers in cabinets 150 lb (0.7 kN)
d. Utility tables (four-leg) 300 lb (1.4 kN)
e. Hanging wall cases 300 lb (1.4 kN)
f. Capacity for shelves of units 150 lb (0.7 kN)
4. Casework shall be of flush construction with the surface of
doors, and drawers and panel faces shall be flush with the
cabinet fronts, ends, and rails.
5. Base cabinets with double swinging doors shall provide full
access to the interior without center vertical post.
6. Drawers shall be rated for 150-lb (0.7-kN) load capacity at full
extension.
7. Drawers shall be sound-deadened, and all corners shall be fitted
smoothly.
4.2.12.6 Laboratory Fume Hoods
Fume hoods shall be in accordance with applicable parts of the
SEFA Desk Reference Manual and NFPA 45.
4.2.13 Conveying Systems
Elevators, escalators, and dumbwaiters shall be designed in accordance with
ASME A17.1.
4.3 Building Utilities
4.3.1 Heating, Ventilation, and Air Conditioning (HVAC)
4.3.1.1 Design Criteria
1. Climatic Conditions
a. Unless site specific design temperatures are specified on
purchasers PIP CVC01017 Data Sheet, climatic condition
values shall be in accordance with the ASHRAE Handbook -
Fundamentals.
b. For all HVAC systems, cooling load shall be calculated with
the summer design dry bulb (0.4%) and mean coincident wet
bulb temperatures, and the supply air requirements shall be
determined at these temperatures.
c. For HVAC systems that have more than 20% outside air
make-up, in addition to the cooling load calculations

Process Industry Practices Page 12 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

performed in accordance with Section 4.3.1.1.1.b of this


Practice, the cooling load shall also be calculated at the
design wet bulb (0.4%) and mean coincident dry bulb
temperature to determine which set of conditions results in
larger HVAC system capacity. The resultant larger HVAC
system capacity shall be used as the cooling capacity of the
refrigeration system. The airside capacity shall be as
determined from Section 4.3.1.1.1.b of this Practice.
d. For the selection of air-cooled packaged units, air-cooled
condensers, and air-cooled condensing units, the summer
design dry bulb (0.4%) temperature shall be used.
e. Heating load shall be calculated using the 99.6% heating dry
bulb temperature.
2. Indoor Design Conditions
a. Unless otherwise specified in the contract documents, the
minimum indoor conditions used for the design of HVAC
systems for various occupancies shall be in accordance with
Table 1 of this Practice.
b. Design conditions for other occupancies shall be based on
rooms listed in Table 1 of this Practice, having similar
functions.
c. HVAC systems shall be capable of maintaining dry bulb and
relative humidity within the performance range given in
Table 1 of this Practice and shall be designed based on
ASHRAE Handbook - Fundamentals, applicable health and
safety codes, and equipment manufacturers requirements.
d. Fresh air requirements for each space shall be based on
ASHRAE 62.1
4.3.1.2 Load Calculation
1. General Requirements
a. HVAC load calculations shall be in accordance with the
ASHRAE Handbook - Fundamentals methods and shall
include a minimum of 5% but not greater than 10% excess
capacity (sensible, latent, or heating) as safety factors.
b. Residential method, preferably total equivalent temperature
differential with time averaging (TETD/TA), shall be used
only for residential application.
c. Overall building cooling and heating loads shall be
calculated. Zoning, exposure, and building mass shall be
considered in heating and cooling calculations.
d. The air-conditioning system shall provide comfortable
conditions in all rooms throughout the operating period in
accordance with Table 1 of this Practice.

Process Industry Practices Page 13 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

e. Each zone, portion of a zone, and room with different load


profiles, orientations, or sensible loads shall be calculated.
f. A separate block load for each air-handling system shall also
be calculated.
2. Cooling Loads
a. Cooling load calculations shall consider all sensible and
latent heat sources.
b. Sensible cooling load shall be calculated for building
envelope, people, lights, equipment, interior non-conditioned
spaces, duct and plenum gains, and outside air that is
introduced into the system by air make-up or infiltration.
c. Latent cooling load shall be calculated for people, outside
air, and any process in which moisture is released to the air.
d. Outside air requirements shall be carefully evaluated for the
building pressurization in accordance with NFPA 496.
3. Heating Loads
a. Heat loads shall include heat losses from building envelope,
interior non-conditioned spaces (partitions, ceilings, floors),
duct and plenum losses, and outside air that is introduced
into the system by make-up air and infiltration.
b. Final discharge temperatures shall range between 85F
(30C) and 110F (43C).
4.3.1.3 System Considerations
1. Zoning
For buildings with separate interior and perimeter rooms, each
room or group of rooms (except for unoccupied spaces) having a
distinctive load profile shall have individual temperature control.
2. Air System Design
a. Air distribution systems shall be designed in accordance
with ASHRAE Handbook - Fundamentals, Duct Design
section.
b. If space conditions permit, supply air ductwork shall be
designed for a maximum pressure drop of 0.1 inch wg per
100 ft (0.82 Pa/m).
c. If space conditions permit, return, general exhaust, and
outside air duct shall be sized for a maximum pressure drop
of 0.08 inch wg per 100 feet (0.65 Pa/m).
d. Non-general exhaust duct sizing criteria shall be in
accordance with ACGIH - Industrial Ventilation: A Manual
of Recommended Practice for Design.

Process Industry Practices Page 14 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

e. All ductwork and fittings shall be fabricated in accordance


with the SMACNA - HVAC Duct Construction Standards
Metal and Flexible and in accordance with the static pressure
expected to be encountered in the system.
f. Flexible duct shall not be used for return or exhaust systems.
g. If flexible ducts are used in the supply air system, the ducts
shall not exceed 8.0 ft (2400 mm) in length.
h. Manufacturers standard diffusers, registers, and grilles shall
be used.
i. A volume damper shall be provided in each branch duct
serving a separate zone or room. Splitter dampers shall not
be used for duct branch take-offs.
j. Volume dampers shall be provided ahead of flexible duct
serving supply air grilles, registers, and diffusers.
k. Outside air intakes shall be designed and located to minimize
dust intrusion.
l. Outside air intakes shall not be less than 10 ft (3000 mm)
from an appliance vent outlet, a vent opening, or a plumbing
drainage system or discharge outlet of an exhaust fan unless
the outlet is 5 ft (1500 mm) above the outside air intake.
m. If practical, return air shall be drawn through a sealed ceiling
plenum.
n. If cable trays are located inside the ceiling plenum, a ducted
return air system rather than plenum-rated cables shall be
evaluated.
o. If building is pressurized in accordance with NFPA 496, the
air-conditioning equipment rooms shall not be used as return
air plenums.
p. Outside air intake ducts shall have combustible gas and
fire/smoke detectors to detect the presence of flammable
gas/vapors and/or smoke in buildings in NEC-classified
areas.
(1) If the detector detects greater than 10% of the lower
flammable limit, an alarm shall occur.
(2) If the detector detects greater than 25% of the lower
flammable limit, the air intake blowers shall shut down
and the outside air intake damper shall close
automatically.
(3) If the blowers shut down, dampers shall automatically
close.

Process Industry Practices Page 15 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

3. Control Systems
a. HVAC control systems shall be designed and installed using
commercially available equipment and techniques to control
temperature and, if required, humidity, pressure, and air
quality in accordance with ASHRAE 90551 or ASHRAE
90552 as applicable.
b. All thermostats shall be manually adjustable over the
operating range and have time/date setbacks or be tied to an
energy management system.
c. Fire dampers shall be installed in accordance with
NFPA 101.
d. Unless the building is always manned, HVAC units shall
automatically shut down in accordance with NFPA 90A and
NFPA 101 if fire alarm system is activated.
e. If the building is always manned (e.g., control building),
a manual shutdown switch shall be provided.
4. Piping and Coils
a. The location of air-conditioning equipment components shall
account for piping and equipment pressure drop, area
classification, and equipment clearance requirements.
b. Access space shall be provided for the removal of any coil or
other equipment component, in accordance with equipment
manufacturers recommendation.
c. Multiple compressor refrigerant piping shall be
interconnected in accordance with manufacturers
recommendations.
d. For any split condenser/compressor or
compressor/evaporator unit separated by more than 10 ft
(3000 mm), refrigerant lines shall be sized in accordance
with ASHRAE Handbook - Refrigeration, Refrigerant Line
Sizing section.
e. Coils may require corrosion protective coatings based on
local air quality conditions.
5. Humidity Control
a. If humidification is required, humidifiers shall be steam- or
ultrasonic-type humidifiers and have water blowdown
capability to minimize solids buildup.
b. A high-limit duct humidistat shall be used to limit moisture
carryover and condensation in the duct.
c. Normal humidity control shall be accomplished by a return
air or space humidistat.

Process Industry Practices Page 16 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

d. High humidity control shall be accomplished by use of the


cooling coil. The humidistat shall override the thermostat
and cooling with re-heating as required to maintain space
temperature.
6. Ventilation and Exhaust
a. All enclosed portions of buildings customarily used by
occupants shall be provided with fresh ventilation air.
b. The minimum amount of outside air shall either equal
10 percent of supply air in excess of all exhaust air or equal
the ventilation air requirements in accordance with ASHRAE
62.1, whichever is greater.
c. The toilet, locker, and shower rooms shall be provided with
a mechanically operated exhaust system capable of
providing as a minimum the ventilation requirements in
accordance with ASHRAE 62.1. The system shall exhaust
directly to the outside, and the point of discharge shall be at
least 5 ft (1500 mm) from any openable window or door and
3 ft (900 mm) above and 10 ft (3000 mm) away from any air
intake unless superceded by ASHRAE 62.1.
d. Occupied, non-air-conditioned enclosed spaces shall have
mechanically forced ventilation.
(1) The ventilation airflow rate shall be established to ensure
that space temperature does not exceed the ambient
outdoor temperature by more than 10F (5.5C).
(2) Outside air intakes shall be designed to minimize dust
intrusion.
e. Buildings or portions thereof where flammable or toxic
materials are used shall be designed for the required
ventilation rate in accordance with ACGIH - Industrial
Ventilation: A Manual of Recommended Practice for Design.
Exhaust ventilation shall be taken from a point at or near the
floor level for gases heavier than air and from near the
ceiling level for gases lighter than air.
f. Ventilation for special applications shall be in accordance
with ACGIH - Industrial Ventilation: A Manual of
Recommended Practice for Design.
g. Automotive-type garages, where vehicles operate under their
own power, shall either have a mechanical exhaust system or
have permanent openings to the outside in accordance with
IBC and ASHRAE 62.1.
7. Noise
HVAC-related background sound for an occupied room shall be
in accordance with the guideline criteria specified in ASHRAE
Handbook - HVAC Applications.

Process Industry Practices Page 17 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4.3.1.4 Special Applications


1. Chemical Laboratories
a. Design and operation of HVAC systems in chemical
laboratories shall be in accordance with the following codes
and standards:
(1) ASHRAE 62.1
(2) ASHRAE Handbook - HVAC Applications
(3) ACGIH - Industrial Ventilation: A Manual of
Recommended Practice for Design
(4) NFPA 45
(5) NFPA 90A
(6) NFPA 91
(7) ASHRAE 110
b. Air from laboratory work areas shall be continuously
discharged to the outdoors, and the area shall be maintained
at a negative pressure relative to the adjacent areas.
c. Air from laboratory work areas shall not be recirculated.
d. Ductwork, hoods, fans, drives, and other system components
shall be designed and selected in accordance with fire,
explosion, corrosion, and acid-resistant requirements.
e. Automatic fire dampers shall not be used in laboratory hood
exhaust systems.
f. Fire detection and alarm systems shall not be interlocked to
automatically shut down laboratory hood exhaust fans.
g. Fume hood exhaust shall be designed in accordance with the
IMC and ACGIH - Industrial Ventilation: A Manual of
Recommended Practice for Design.
h. Airflow indicators shall be installed on new laboratory hoods
or on existing laboratory hoods, if modified, in accordance
with NFPA 45.
2. Essential Operating Facilities
a. Essential operating facilities include rack rooms, computer
rooms, control rooms, communication equipment rooms, and
any other buildings housing electrical equipment and control
systems that are vital in the production, processing, and
transportation of the process. Office buildings, maintenance
facilities, dining halls, etc., are not typically essential
operating facilities.

Process Industry Practices Page 18 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

b. For pressurized buildings, the maximum amount of outside


air supplied to pressurize the building during normal
operation with all doors and windows closed shall be used in
HVAC load calculations.
c. 100% capacity of cooling and heating standby systems shall
be provided.
d. For buildings located in Class I, Division 2 electrical areas,
the HVAC system, alarms, and controls shall be designed to
prevent the entry of flammable vapors or gases in
accordance with NFPA 496, in the section titled Pressurized
Control Rooms.
e. Outside air for pressurization shall take into account all air
exhausted from the space, including all exhaust fans as if
operating on a continual basis, even if all exhaust fans do not
operate continuously.
f. HVAC equipment in hazardous areas shall be suitable for
operation in the area classification in which the equipment is
located.
g. Outside air for pressurization of buildings in classified areas
shall be taken from an unclassified area.
h. For pressurized buildings, the exterior envelope shall be
designed to be as air tight as practical. Air-locked vestibules
shall be provided at the building entrance doors.
i. A 100% standby fan shall be provided for buildings with
pressurization systems.
3. Battery Rooms
a. Battery rooms shall be ventilated to the outside of the
building at a minimum rate of one air change every 3 hours,
unless a higher exhaust airflow rate is required because of
the discharge of cooling air that cannot be recycled from the
room.
b. Air shall not be recycled from battery rooms.
c. For batteries located inside the electric/UPS rooms, if
analysis reveals that H2 evolution is less than 2% of the room
volume while charging, a once-through air system shall not
be required; however, a local exhaust system over the battery
area shall be provided.
d. The bottom of the supply air outlet into the battery room
shall not be higher than 6 inches (150 mm) above the floor.
e. The exhaust opening shall be in the ceiling or its upper edge
and shall be flush with the ceiling if the exhaust opening is
in a wall.

Process Industry Practices Page 19 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

f. Air inlets and outlets shall be located to provide effective


cross ventilation over the batteries.
g. Batteries with liquid medium shall be placed in an area with
full spill containment.
h. Battery supports/racks shall meet the seismic design
requirements of IBC.
4. Chemical Filtration
a. In all buildings containing electronic equipment, the
concentration of corrosive gases shall be limited to the G1
environmental classification level shown in Table 2 of this
Practice.
b. If it is confirmed that the concentration of corrosive gases in
the local plant environment exceeds the G1 classification
level, chemical filters shall be provided that limit to the G1
classification level the concentration of gases inside the
rooms containing the electronic equipment.
c. Unless otherwise specified in the purchasers PIP ARC01016
Data Sheet, activated charcoal shall be used.
5. Dust Filters
a. Dust filters shall be equipped with pre-filters and final
filters.
b. The pre-filters shall have a minimum of 25% efficiency, and
the final filters shall provide a minimum of 85% dust spot
efficiency, in accordance with ASHRAE 52.2.
c. The selected filters shall be easily available locally.
6. Insulation
a. All supply and return air ducts, located outdoors or exposed
to unconditioned air, shall be insulated.
b. Insulation shall not be required for return air ducts in a
ceiling space if both sides of the ceiling space are exposed to
conditioned air, and if the ceiling space is not used as a
return air plenum.
c. Supply air ducts in return air plenums shall be insulated.
d. Supply air ducts in conditioned space and return air ducts in
return air plenums shall be insulated.
e. Internal duct lining shall not be permitted except in the
following cases:
(1) For acoustically sensitive areas.
(2) For terminal boxes and air-handling units if protective
coating is required to prevent erosion.

Process Industry Practices Page 20 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

f. Refrigerant suction lines shall be insulated from the


evaporator to the compressor.
g. Condensate line shall be insulated from the unit to the drain
location.
7. Dampers
a. Each branch duct serving a separate zone or room shall have
a volume damper.
b. Branch duct dampers shall be sheet metal opposed blade
type, using pivot and rod, with locking quadrant damper.
c. Fire dampers shall bear the UL label.
d. Fire dampers shall be securely mounted in a rated fire
separation wall, ceiling, or floor, such that ducts can break
away without lessening fire separation rating.
e. Fire and smoke dampers shall be manufactured in
accordance with UL 555 or UL 555C and installed in
accordance with SMACNA - Fire, Smoke and Radiation
Damper Installation Guide for HVAC Systems.
f. For HVAC systems, inspection doors shall be provided to
allow access to all fire dampers.
g. Combination smoke/fire dampers shall be in accordance with
all requirements for smoke damper fire alarm closure and
fire damper latching.
4.3.1.5 Installation
1. All air handlers, refrigeration condenser units, pumps, and any
equipment mounted outside a building, shall be mounted on a
concrete housekeeping pad, at a minimum of 4 inches (100 mm)
above the floor or pavement or 6 inches (150 mm) above
surrounding unpaved areas.
2. Access doors shall be provided to every valve, damper, or
mechanical device that requires periodic inspection or
adjustment.
3. Access doors for fire dampers shall be positioned so that
dampers can be reset and fusible links can be replaced.
4. Unless otherwise specified by the equipment manufacturer,
a minimum 3-ft (900-mm) clearance shall be provided on each
side of equipment with removable panels or controls.
5. Adequate space shall be provided for coil removal.
6. All HVAC equipment shall be properly grounded in accordance
with NFPA 70 (NEC).

Process Industry Practices Page 21 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

Table 1 HVAC Room Descriptions and Design Criteria (See Note 1)


Thermostat-
Setting Temp. Pressure
(dB) % Relative Relative to Air
Room Name Room Functions Description F (C) Humidity Atmosphere Quality Remarks
Battery Rooms Contain battery systems. Not normally 77F (26C) N/A Negative As reqd These rooms are sometimes
occupied. summer pressure to the for gas classified for electrical
72F (22C) rest of the removal installations (i.e., Class I,
winter building Division 2).
Break Rooms Typically house a sink, microwave, or other 75F (24C) 50% 10% +0.05 ASHRAE
kitchen-type appliance. Typically have table(s) summer (12.5 Pa) 62.1
and chairs for people to sit and eat. Break 72F (22C)
rooms may or may not also have vending winter
machines. Occasionally occupied.
Change Rooms Areas for personnel to change clothes and may 75F (24C) 50% 10% Negative ASHRAE
include lockers and lavatories. They may be summer pressure to the 62.1
part of or adjacent to restrooms or shower 72F (22C) rest of the
rooms. Occasionally occupied. winter building
Coffee/Vending Contain vending machines and/or coffee 75F (24C) 50% 10% +0.05 ASHRAE
Rooms machines. May also have microwaves. These summer (12.5 Pa) 62.1
rooms are distinguished from break rooms in 72F (22C)
that they do not typically have tables, chairs, winter
or sinks. Not normally occupied.
Communications Contain communications equipment, cable 75F (24C) 50% 10% +0.10 N/A See Notes 3 and 4 for additional
Closets terminations, and associated cross-connect summer (25 Pa) requirements.
cable/wiring. Not normally occupied. 72F (22C)
winter
Communications Contain programming applications, electronic 75F (24C) 50% 10% +0.10 ISA See Note 4 for additional
Computer equipment such as servers, switches, hubs, summer (25 Pa) 71.04 requirements.
Rooms and routers. Occasionally occupied. 72F (22C)
winter
Communications Contain programming applications and 75F (24C) 50% 10% +0.10 ISA See Note 4 for additional
Equipment electronic equipment such as servers, switches, summer (25 Pa) 71.04 requirements.
Rooms hubs, and routers. Occasionally occupied. 72F (22C)
winter
Computer Mainly house computers and associated 75F (24C) 50% 10% +0.10 ISA See Note 3 for additional
Rooms equipment. May be considered either normally summer (25 Pa) 71.04 requirements.
or not normally occupied, depending on the 72F (22C)
project specific use. winter (Continued, next page)

Process Industry Practices Page 22 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

Table 1 HVAC Room Descriptions and Design Criteria (Continued)


Thermostat-
Setting Temp. Pressure
(dB) % Relative Relative to Air
Room Name Room Functions Description F (C) Humidity Atmosphere Quality Remarks
Conference Occasionally occupied. If occupied, these 75F (24C) 50% 10% +0.05 ASHRAE
Rooms or spaces may have a lower square foot per summer (12.5 Pa) 62.1
Auditorium person average than do normally occupied 72F (22C)
spaces. winter
Control Rooms Contain control consoles. Normally occupied. 75F (24C) 50% 10% +0.10 ISA
summer (25 Pa) 71.04
72F (22C)
winter
Copy/Fax Rooms Separate walled-in rooms for housing copy 75F (24C) 50% 10% +0.05 N/A
and/or fax machines. Not normally occupied. summer (12.5 Pa)
For HVAC design purposes, any normally 72F (22C)
occupied space listed as a copy/fax room winter
should be treated as an office space.
Electrical/ Specifically for housing electrical, telephone, 80F (26C) 50% 10% +0.05 N/A
Telephone/ or radio equipment. Distinguished from summer or as required by (12.5 Pa)
Radio Rooms mechanical room because they specifically 50F (10C) equipment
house electrical/telephone/radio equipment. winter manufacturer
Not normally occupied. or as required by
equipment
manufacturer
HVAC/ Contain HVAC equipment and/or other types of 80F (26C) N/A +0.05 N/A
Mechanical equipment such as pumps, water heaters, 50F (10C) (12.5 Pa)
Rooms electrical equipment, etc. Not normally
occupied.
I/O Rooms Contain I/O equipment. Not normally occupied. 75F (24C) 50% 10% +0.10 ISA
summer (25 Pa) 71.04
72F (22C)
winter
Janitors Room Contain service sinks and provide storage for 80F (26C) 50% 10% Negative N/A
various cleaning supplies. Not normally summer pressure to the
occupied. 50F (10C) rest of the
winter building
Libraries and Contain reference books, magazines, papers, 75F (24C) 50% 10% +0.05 ASHRAE
Reading Areas or other types of reading materials. They are summer (12.5 Pa) 62.1
distinguished from file/record storage because 72F (22C)
the reading materials are meant to be accessed winter
on a regular basis. Normally occupied. (Continued, next page)

Process Industry Practices Page 23 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

Table 1 HVAC Room Descriptions and Design Criteria (Continued)


Thermostat-
Setting Temp. Pressure
(dB) % Relative Relative to Air
Room Name Room Functions Description F (C) Humidity Atmosphere Quality Remarks
Lobbies and Typically open areas at the main entrance to a 75F (24C) 50% 10% +0.05 ASHRAE
Corridors building and may include waiting areas and summer (12.5 Pa) 62.1
receptionists desks. Corridors, also known as 72F (22C)
circulation, are hallways connecting various winter
rooms in a building. Corridors are considered
not normally occupied. Lobbies may be
considered either normally or not normally
occupied.
Offices Occupied by one or more persons and used for 75F (24C) 50% 10% +0.05 ASHRAE
office-type work. summer (12.5 Pa) 62.1
72F (22C)
winter
Record/File Storage areas for files and records. Not 75F (24C) 50% 10% +0.05 N/A
Rooms normally occupied. For HVAC design purposes, summer (12.5 Pa)
any normally occupied space listed as a 72F (22C)
record/file room should be treated as an office winter
space.
Reproduction Areas used for plotters, printers, copiers. 75F (24C) 50% 10% +0.05 ASHRAE
summer (12.5 Pa) 62.1
72F (22C)
winter
Restrooms Contain one or more of the following: 75F (24C) 50% 10% Negative ASHRAE
1. Water closet summer pressure to the 62.1
2. Urinal 72F (22C) rest of the
3. Lavatory winter building
4. Bidet
Considered occasionally occupied.
Shower Rooms Areas for showering or bathing. They may be 75F (24C) 50% 10% Negative ASHRAE
part of or adjacent to restrooms and/or change summer pressure to the 62.1
rooms. Considered occasionally occupied. 72F (22C) rest of the
winter building
Storage Rooms/ Areas for general storage that do not fall into 80F (26C) 50% 10% +0.05 N/A
Spaces the category of file/record rooms or any other summer (12.5 Pa)
specific type of storage area such as solvent or 50F (10C)
chemical storage. Not normally occupied. winter (Continued, next page)

Process Industry Practices Page 24 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

Table 1 HVAC Room Descriptions and Design Criteria (Continued)


Thermostat-
Setting Temp. Pressure
(dB) % Relative Relative to Air
Room Name Room Functions Description F (C) Humidity Atmosphere Quality Remarks
Switchgear Contain all switchgear and MCC equipment 77F (26C) 50% 10% +0.10 N/A
Rooms/MCC such as transformer, breakers, starters, and summer (25 Pa)
Rooms panel boards. Not normally occupied. 72F (22C)
winter
UPS Rooms Contain UPS equipment and/or battery charger. 77F (26C) 50% 10% +0.10 N/A
Not normally occupied. summer (25 Pa)
72F (22C)
winter
Training Rooms Areas for training classes and also may be used 75F (24C) 50% 10% +0.05 ASHRAE
as meeting rooms. They are distinguished from summer (12.5 Pa) 62.1
conference rooms in that these rooms are 72F (22C)
occupied on a regularly scheduled basis and winter
are considered normally occupied.
Waiting Rooms Separate walled-in rooms (as distinguished 75F (24C) 50% 10% +0.05 ASHRAE
from waiting areas in a lobby). Occasionally summer (12.5 Pa) 62.1
occupied. 72F (22C)
winter
Notes:
1. The following definitions apply:
a. Normally occupied - Any space or room in which a person or persons are assigned to be on a day-to-day basis
b. Not normally occupied - Any space or room in which a person or persons is not assigned on a day-to-day basis
c. Occasionally occupied - Any space or room in which a person or persons is not assigned on a day-to-day basis but at times may be fully occupied
2. The number values in this table shall be used unless otherwise specified by the purchaser.
3. Rooms contain non-active equipment; room temperature shall be maintained at 50F (10C) to 95F (35C), and humidity shall be below 85%.
4. TIA-569

Process Industry Practices Page 25 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

Table 2 ISA Classification


Gas Concentrations (Parts per Billion, by Volume)
H2S SO2 , SO3 Cl2 NOx HF NH3 O3
ISA Class G1 3 10 1 50 1 500 2
Note: ISA environmental classes, relative humidity 50%.

4.3.2 Electrical Work


4.3.2.1 General
1. Unless otherwise specified in the contract documents or by law,
all electrical work shall be in accordance with this Practice and
local, state, and national codes.
2. Electrical work shall be in accordance with NFPA 70 (NEC) and
energy conservation codes required by national, state, and local
government regulations.
3. Equipment, apparatus, or material required to be approved shall
be approved by a nationally recognized testing laboratory.
4. The electrical hazardous area classification for the buildings
shall be shown on the electrical area classification drawings.
4.3.2.2 Lighting
1. Unless otherwise specified in purchasers PIP ARC01016 Data
Sheet, building exterior electrical lighting and interior electrical
lighting shall be provided in accordance with local energy codes
2. Unless otherwise specified in the purchasers PIP ARC01016
Data Sheet, indoor lighting shall be fluorescent, light emitting
diode (LED), or high-intensity discharge (HID). Illumination
levels shall be in accordance with API RP 540.
3. For occupied buildings, interior lighting shall include egress
lighting and exit sign lighting with a secure power supply.
A secure power supply shall be a battery charger with a battery
or an uninterruptible power supply (UPS) sized for a minimum
of 90 minutes.
4. Unless otherwise specified in purchasers PIP ARC01016 Data
Sheet, lighting for each room shall be separately controlled by a
motion-sensor switch located on the wall near each door entering
the room or an energy management system.
4.3.2.3 Power
1. Unless otherwise specified in purchasers PIP ARC01016 Data
Sheet, power source for the building shall be a single 480-volt,
3-phase, 3-wire plus ground, 60-Hertz feeder brought to a point
to be designated by the owner. Unless otherwise specified by the
owner, this feeder shall not be a service.

Process Industry Practices Page 26 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

2. The building shall be provided with transformers, panelboards,


and other equipment as required to distribute power to all
building lighting, receptacles, HVAC equipment, and other
utility equipment.
3. All equipment shall be located indoors except for transformers
larger than 500 kVA.
4. All transformers inside buildings shall be dry type.
5. 120-volt, single phase duplex grounding receptacles supplied
from single phase 120-volt, 60-Hertz branch circuits shall be
provided in every room in accordance with NFPA 70 (NEC).
6. Additional receptacles shall be provided for any cord-and-plug-
connected building utility equipment.
7. All receptacles shall be grounding type.
8. Ground Fault Circuit Interrupters (GFCI) protected 120 volt
receptacles shall be supplied in accordance with NFPA 70
(NEC). Where supplied, the GFCI shall be of the self-testing
type.
9. If specified in purchasers PIP ARC01016 Data Sheet, Arc-Fault
Circuit Interrupters shall be supplied on 120 volt single phase
branch circuits in accordance with NFPA 70 (NEC).
4.3.2.4 Grounding
1. Grounding shall be in accordance with NFPA 70 (NEC)
requirements.
2. If specified in purchasers PIP ARC01016 Data Sheet, special
grounding shall be provided.
3. A grounding wire shall be provided with the building power
feeder, which shall be bonded to the building grounding system.
4. Proper grounding shall be the primary method of lightning
protection.
4.3.2.5 Wiring Methods
1. Unless otherwise specified in the contract documents, interior
wiring shall be in electrical metallic tubing (EMT) and flexible
metallic tubing.
2. Unless otherwise specified in the contract documents, exterior
wiring shall be in rigid galvanized steel conduit and liquid-tight
flexible metal conduit.
3. All conductors shall be copper.
4. Wiring in rooms with finished walls and ceilings shall not be
exposed.
5. In order to protect both personnel and equipment, buildings with
a high density of electronic equipment and/or high occupancy

Process Industry Practices Page 27 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

shall have cables and wiring specified as being low smoke zero
halogen (LSZH or LSOH or LS0H or LSFH or OHLS) wire and
cable to reduce the amount of toxic and corrosive gas emitted
during combustion.
4.3.2.6 Energy Management and Conservation
1. Electrical equipment, apparatus, and lighting shall be energy
efficient and shall be in accordance with energy conservation
codes required by national, state, and local government
regulations.
2. Unless otherwise specified, exterior lights shall be controlled by
photocells.
4.3.2.7 Rooms primarily intended for electrical power equipment shall have
locks on all doors.
4.3.2.8 Receptacle control switches and electrical equipment shall be readily
accessible to all potential occupants of the room in accordance with
2010 ADA Standards for Accessible Design if applicable.
4.3.3 Communications
4.3.3.1. General
1. This communications design criteria section shall be used in
conjunction with the following codes and standards:
a. IEEE 1100
b. FCC, Part 68
c. NFPA 70 (NEC)
d. NFPA 72
e. NFPA 75
f. NFPA 232
g. NFPA 2001
h. TIA-568
i. TIA-569
j. TIA-570
k. TIA-606
l. TIA-607
m. UL 1863
n. UL 60950-1
2. This section furnishes requirements for communications rooms
including the following:
a. Communications closet
b. Communications equipment room

Process Industry Practices Page 28 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

c. Communications computer room


d. Communication entrance facilities and entrance room
3. A communications room may contain the equipment used in
multiple communications systems (e.g., telephone, site access,
security, hotlines, closed circuit television, bar coding, weather
monitoring, etc.).
4. See Figure 1 of this Practice for typical communications room
arrangements.

Figure 1. Typical Communications Room Arrangements

4.3.3.2 Room Descriptions


1. Communications Closets
a. A communications closet shall contain communications
equipment, cable terminations, and associated cross-connect
cable/wiring.
b. A communications closet shall serve one floor area of one
building.
c. Communications closets for non-active equipment or active
equipment will be walk-in.

Process Industry Practices Page 29 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

2. Communications Equipment Rooms


a. Communications equipment rooms shall provide space and
maintain a suitable operating environment for large
communications or computer equipment.
b. Communications equipment rooms may serve a building or
multiple buildings.
c. A communications equipment room may also serve as a
communications closet.
3. Communications Computer Rooms
a. Communications computer rooms shall contain
programming applications and electronic equipment
(e.g., servers, switches, hubs, and routers) that directly effect
the business operations.
b. Communications computer rooms shall be provided with
environmental control and monitoring as required to protect
the communications equipment.
c. Rooms associated with the communications computer room
shall be adjacent to qualified personnel.
d. All buildings in a campus shall connect with the
communications computer room.
4. Communications Entrance Facilities
a. The communications entrance facility shall consist of the
communications service entrance to the building, including
the entrance through the building wall, and continuing to the
entrance room or space.
b. The communications entrance room may be the
communications closet, communications equipment room,
and in some cases the communications computer room.
c. 2-inch (50-mm) conduits shall be used with small diameter
0.5-inch (12-mm) cables (e.g., optical fiber and coaxial
cable).
d. 4-inch (100-mm) conduits shall be used with larger diameter
cables (e.g., multi-pair copper cables and innerduct).
e. As a minimum, either of the following shall be considered
for each entrance point:
(1) Two 4-inch (100-mm) conduits with as a minimum one
spare 4-inch (100-mm) conduit.
(2) Three 2-inch (50-mm) conduits.
f. A separate communications closet, or communications
equipment room, on the same floor as the entrance facility

Process Industry Practices Page 30 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

shall be provided for buildings with a communications


computer room.
g. Verify requirements for redundant entry/exits of
communication lines.
4.3.3.3 Building Facility
1. Buildings shall be served by at least one communications closet
or communications equipment room, with a minimum of one
communications closet per floor.
2. There is no maximum number of telecommunications closets
that may be provided within a building.
3. Communications rooms shall not be shared with other services
nor shall these rooms contain non-communications-related
equipment.
4. Piping, ductwork, pneumatic tubing, etc., other than for fire
surpression systems, shall not pass through communications
rooms.
5. All communications rooms shall be fitted with a locking
mechanism to prevent the entry of unauthorized personnel.
6. Communications closets and communications equipment rooms
shall be located as close as possible to the center of the floor
space being served, away from any threat of potential flooding.
7. Communications rooms shall not be below or adjacent to rooms
that store or require running water. Locations that are water
hazards (e.g., restrooms, break rooms (with sinks), and kitchens)
shall be avoided.
8. If a communications closet is at risk of water ingress, a floor
drain shall be provided.
9. For buildings that have a computer room, the communications
closet or communications equipment room shall be adjacent.
10. For qualifying the communications room location, the following
other key factors shall be considered:
a. Distances from required utilities
b. Expansion of communications systems
c. Building access for large equipment
d. Distance limitations of the cable being installed for service
11. Communications rooms shall not be located where subject to
vibration caused by equipment and other heavy machinery.
12. Sources of electromagnetic interference (EMI) shall be 10 ft
(3000 mm) away from the communications equipment room and
communications computer rooms. Examples of EMI sources

Process Industry Practices Page 31 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

include photocopying equipment, door openers, elevator


systems, factory equipment, etc.
4.3.3.4 Room Ancillaries
1. Floor materials for communications rooms shall have antistatic
properties. Carpet shall not be permitted.
2. Unless otherwise specified in purchasers PIP ARC01016 Data
Sheet, communications computer rooms shall have access floors.
3. Windows shall not be provided in communications rooms except
as required for cable entry.
4. Communications rooms shall not be shared with other services
nor shall these rooms accommodate pass-through of
non-communications-related services such as piping, ductwork,
pneumatic tubing, etc., except as required to service the room.
5. Lighting
a. Lighting shall be mounted at 8.5-ft (2600-mm) minimum
above finished floor.
b. Lighting shall not provide radio frequency interference (RFI)
that could interfere with the communications equipment.
c. Light fixture power shall not be from the same electrical
distribution panel as that of the communications equipment.
d. Communications computer areas shall be provided with
emergency lighting.
6. Communications closets with active equipment and
communications equipment rooms shall have a minimum of two
dedicated 120-volt receptacle circuits. For convenience, duplex
outlets shall be placed at 6-ft (1800-mm) intervals at a height of
6 inches (150 mm) above the floor and shall be identified and
marked.
7. A dedicated power panel, serving power to communications
equipment only, shall be installed within the room.
8. If the building has standby power, it shall be designed for the
communications equipment room requirements including
HVAC.
9. Distribution panels that serve lighting fixtures shall not serve
communications equipment.
10. Communications computer rooms shall have a guarded push
button at each door that initiates disconnection of power from
specified equipment. This equipment includes computer room
electronic equipment, servers, switches, hubs, etc. The operation
of the push button shall close the fire/smoke dampers on the
HVAC system.

Process Industry Practices Page 32 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

11. Electrical power for the communications computer room shall be


supplied from a minimum of two dedicated power panels.
a. One panel shall be for receptacles.
b. The second panel shall be for the junction boxes in the
under-floor area. A minimum of four dedicated 120-volt
nominal, single-phase, non-switched, air-conditioning
duplex electrical outlet receptacles, each on a separate
20-amp-branch circuit, shall be provided.
12. The standby power for the buildings shall be designed to include
the communications computer room equipment and HVAC
systems.
4.3.3.5 Room Size
1. Additional communications closets shall be provided for the
following cases:
a. For each 10,000 ft2 (1000 m2) of building area
b. If a work area is more than 300 ft (90 m) from the closet
c. If the floor area served exceeds 10,000 ft2 (1000 m2)
2. Walk-in communications closets shall be a minimum of 4 ft,
6 inches deep by 4 ft, 6 inches wide (1350 mm by 1350 mm).
3. Communications closets layouts shall be in accordance with TIA-
569.
4. Communications equipment rooms shall be sized for the
equipment to be used, including working clearances and future
space if required.
5. Communications equipment room size shall be approximately
0.75 ft2 (0.07 m2) for each 100 ft2 (9 m2) of work area, with a
minimum size of 150 ft2 (14 m2).
6. Communications computer rooms shall be sized for the
equipment to be used. The design shall anticipate future needs
and technologies.
7. Adjacent to the communications computer room shall be the
support rooms (e.g., recorded media storage, UPS, I/O stations,
etc.). See NFPA 75, Appendix A, for a typical example.
4.3.3.6 Communications Closet HVAC
1. A communications closet shall maintain a temperature the same
as that of the adjacent office area.
2. Communications closets with active equipment shall maintain
continuous HVAC at all times.
3. If the building system cannot ensure the continuous HVAC
required, a stand-alone unit shall be provided.

Process Industry Practices Page 33 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4. The environmental equipment may be located inside the


communications closet.
5. Sensors and controls shall be placed 5 ft (1500 mm) above the
finished floor, located in the communications closet.
4.3.4 Fire Protection and Safety
4.3.4.1 General
1. Building fire protection systems shall be in accordance with
specified codes and/or standards and this document.
2. The design of the systems shall be in accordance with the
applicable NFPA standards and this Practice.
4.3.4.2 Standpipes
1. The design, placement, and installation of a standpipe system
shall be governed by NFPA 14. The type of standpipe system
required is based on building height, area per floor occupancy
classification, egress system design, required flow rate and
residual pressure, and the distance of the hose connection from
the source(s) of water supply.
2. The following describes the types of standpipes that shall be
provided and their intended use:
a. Class I: 2.5-inch (65-mm) hose connections to supply water
for use by fire departments and those trained in handling
heavy fire stream.
b. Class II: 1.5-inch (40-mm) hose stations to supply water for
use primarily by the building occupants or by the fire
department during initial response.
Comment: Class II is recommended for general
requirements.
c. Class III: 1.5-inch (40-mm) hose stations to supply water for
use by building occupants and 2.5-inch (65-mm) hose
connections to supply a large volume of water for use by fire
departments and those trained in handling heavy fire stream.
4.3.4.3 Automatic Fire Sprinkler Systems
1. Typically, the sprinkler systems shall be wet, dry, or pre-action
type, depending on the building contents or environmental
conditions.
2. Usually, wet pipe systems shall be used in all cases except as
specified in Section 4.3.4.3.3 of this Practice.
3. Typically, if inadvertent water leakage could damage high-value
or water sensitive contents, pre-action sprinkler systems shall be
used. A dry pipe system is typically used in areas where the
system can be exposed to freezing conditions (i.e., outdoors).

Process Industry Practices Page 34 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4. All sprinkler systems shall be designed and installed in


accordance with NFPA 13.
5. Sprinkler systems for laboratories shall have a design density in
accordance with NFPA 45.
4.3.4.4 Portable Fire Extinguishers
1. All fire extinguisher type, size, and placement shall be in
accordance with NFPA 10. Fire extinguisher type, size, and
placement are determined in NFPA 10 based on the type/size of
hazard.
2. If wheeled extinguishers are to be installed, consideration shall
be given to the mobility within the area in which they are to be
used. Doorways, aisles, and corridors shall be wide enough to
permit the ready passage of a wheeled fire extinguisher.
4.3.4.5 Clean Agent Fire Extinguishing Systems
1. Fixed fire suppression systems based on an environmentally
friendly agent shall be provided for the sub-floor spaces of
control rooms, auxiliary rooms, communications rooms, and
process control computer rooms.
2. Fixed fire suppression systems shall be designed and installed in
accordance with NFPA 2001.
3. Existing Halon 1301 systems may be retained in service until the
end of their expected working life.
4.3.4.6 Fire Alarm, Detection, and Control Systems
Building fire alarm detection and control systems shall be provided
in accordance with NFPA 72.
4.3.4.7 Gas Detection Systems
1. Building gas detectors shall be provided as required to maintain
a safe building environment.
2. The type of gas detector to be used depends on the possible
hazards and may include the following:
a. Combustible gas detectors
b. Toxic gas detectors
c. Oxygen analysis
3. If nitrogen is present and/or nitrogen back-up is provided in the
area, oxygen analysis shall be provided.
4. If combustible gas and toxic gas detectors are provided, they
shall be situated at the fresh air intake of the HVAC system.
The HVAC system shall be designed to interlock with these
gas-monitoring systems.

Process Industry Practices Page 35 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

4.3.5 Plumbing
4.3.5.1 General
1. The following systems, including associated piping, fittings,
valves, hangers and supports, fixtures, equipment, insulation, and
other trim, accessories, and related parts shall be in accordance
with this Practice:
a. Sanitary drainage, waste, and vent
b. Laboratory waste and vent
c. Distilled water, laboratory gas, air, vacuum, and steam
system
d. Potable hot and cold water
e. Safety showers and plumbing fixtures
f. HVAC condensate drainage
g. Roof drainage system
2. All plumbing design shall be in accordance with the local
plumbing code. In the absence of any locally adopted building
code, the building plumbing system shall be designed in
accordance with IPC and this Practice unless otherwise specified
on the purchasers PIP ARC01016 Data Sheet.
3. High-temperature equipment and piping, so located as to
endanger personnel or create a fire hazard, shall be properly
guarded or covered with insulation.
4.3.5.2 Plumbing System Layout and Design
1. The plumbing system shall be laid out by determining proper
elevations for all components of the system and using only the
minimum number of bends to produce a satisfactorily
functioning system.
2. Pipes shall be laid out to fall within partition, wall, or roof
cavities. Unless otherwise specified, furring shall not be
permitted.
3. Horizontal sanitary drainage piping 3 inches (75 mm) and larger
shall be run at a minimum uniform grade of 1/8 inch per ft
(3 mm per 300 mm) (i.e., 1% slope). Horizontal sanitary
drainage piping smaller than 3 inches (75 mm) shall be run at a
minimum uniform grade of inch per ft (6 mm per 300 mm)
(i.e., 2% slope).
4. Any portion of the drainage system installed underground or
below a basement or cellar shall not be less than 4 inches
(100 mm) in diameter.
5. New pipe shall match slope of existing pipe where new pipe ties
into existing pipe.

Process Industry Practices Page 36 of 37


PIP ARC01015 COMPLETE REVISION
Architectural and Building Utilities Design Criteria December 2014

6. Horizontal water piping shall be run with an adequate pitch in


direction of flow to permit complete drainage.
7. Sufficient swing joints, ball joints, expansion loops, and devices
shall be provided as necessary for a flexible piping system.
8. Piping shall be independently supported at pumps, coils, tanks,
and similar locations so that the equipment does not support the
weight of pipe.
9. The drains from drip pans, relief valves, air vents, and similar
locations shall be piped to spill over an open sight drain, floor
drain, or other acceptable discharge point, and terminated with a
plain end unthreaded pipe 6 inches (150 mm) above the drain.
10. Complete dielectric isolation shall be provided between ferrous
and nonferrous metals.
11. Plumbing pipes shall not be located inside rooms with major
electronic equipment.
4.3.5.3 Floor Drains
1. Floor drains shall be provided in toilet rooms, janitor closets,
lockers areas, shower stalls, eyewash/safety showers, equipment
rooms, and shop areas.
2. Except for shower stall floor drains which do not require trap
primer connections, all other floor drains shall be provided with
primer connections.
4.3.5.4 Cleanouts
1. Cleanouts shall be the same size as the pipes but not greater than
4 inches (100 mm).
2. Cleanouts shall be easily accessible.
4.3.5.5 Insulation and Pipe Coating
1. All indoor cold water lines shall be provided with anti-sweat
insulation.
2. Underground steel piping shall be coated and wrapped.
3. The following piping shall be insulated:
a. Domestic hot and cold water piping
b. Horizontal roof drains and overflow piping subject to
condensation
4.3.5.6 Grease and Oil Interceptors
1. Grease interceptors with automatic draw-off shall be provided
for drains in areas where food is prepared.
2. Oil interceptors shall be provided for drains in maintenance
shops or in similar rooms, near mechanical equipment if
potential exists for oil leakage or spillage.

Process Industry Practices Page 37 of 37

You might also like