Vacuum Circuit-Breakers
Medium-Voltage
Equipment
Catalog HG 11.11
1999
3AH Vacuum
Circuit-Breakers 3AH Vacuum Circuit-Breakers
Description
1
R-HG11-059a eps
Siemens
8BJ50 medium-voltage
withdrawable switchgear
with 3AH vacuum circuit-breaker
on central truck
R-HG11-058 eps
Airport Munich
Medium-Voltage Equipment
Catalog HG 11.11 1999
Supersedes: Catalog HG 11.11 1997 Siemens AG 1999
3AH Vacuum Circuit-Breakers 3AH Vacuum
Circuit-Breakers
Description
Universal installation in all Synchronization tion Reclosing, for example, Making currents up to 10 kA
standard medium-voltage The closing times (for switching the following sequence: (peak value) are permissible;
equipment duties U and K) are so short O-t-CO-t'-CO-t'-CO-t'-CO higher values on request.
Suitable for use as 1-pole that, at the instant the contacts (t 0.3 s, t' 15 s).
or multi-pole medium- touch, the systems being paral- Switching of overhead lines
voltage circuit-breaker for leled are still sufficiently in Switching of transformers and cables
all switching duties in synchronism. Due to the special type of When unloaded overhead lines
indoor switchgear contact material used, the and cables are being discon-
For switching all resistive, Rapid load transfer chopping current of vacuum nected, the relatively low capa-
inductive and capacitive circuit-breakers is only 2 to 3 A, citive currents are interrupted
(Transfer of loads from one
currents which means that no danger- without restrike and, therefore,
source of supply to another
ous overvoltages arise when without overvoltage.
For switching generators without interruption of service)
Special
On req. On request On req. 7/2
* Please pay attention to the notes applications
Cases of application on page 1/2.
Siemens HG 11.11 19991/3
3AH Vacuum Circuit-Breakers 3AH Vacuum
Circuit-Breakers
Description
Technical specifications for details regarding service life, please refer to catalog sections 2 to 6
Operating times
Operating times Vacuum circuit- Vacuum circuit-breaker operating time
at rated voltage breaker equipment
3AH1 3AH2 3AH3 3AH4 3AH5 3AH3 83 3AH4 7
of secondary circuit
1) DC component 36% (higher values on request). 3) Shorter operating times on request. 5) With stored-energy mechanism.
2) 3150 A for rated voltage 17.5 kV. 4) Arcing time < 33 ms at rated frequency of 16 2/3 Hz.
HG11-2362a eps
3 000 zero, if the current falls below this
value. chamber
Description
R-HG11-060a eps
freely accessible, therefore en- 2 distance 160 mm
abling the insulating parts to be 3 31.5 kA / 1250 A
easily cleaned in the case 12
up to 17.5 kV
of difficult ambient conditions 4 13 25 kA / 1250 A
(fouling). 24 kV
5 25 kA / 1250 A
The pole assemblies are
1 mounted on the housing of the
operating mechanism by
means of post insulators.
6
7
14 36 kV
16 kA / 1250 A
The operating motion re-
8 sults from the operating
The vacuum interrupter (4) is 15 rod (16), lever (15) and
9
mounted rigidly to the upper opening and contact-
interrupter support (1). The 11 pressure spring (9) to the
HG11-2259a eps bracket (11) attached to
lower part of the interrupter is 16
3AH1 vacuum circuit-breaker Section the drive bolt (5).
inserted in the lower inter- 24 kV / 25 kA / 1250 A through the pole assembly;
rupter support (7). The struts mechanism version 1
(3 and 13) absorb the external
forces arising from switching
operations and contact pres- for 3AH1 and 3AH2
1
sure. up to 17.5 kV
R-HG11-061a eps
2 25 kA / 2000 A
3 versions of pole assemblies
31.5 kA / 1250 A
are available which differ in 3 12
function according to the 24 kV
method by which the operating 4 13 20 kA / 1250 A
25 kA / 1250 A
rods are attached to the
interrupters (see mechanism The operating motion re-
5 sults from the operating
versions shown opposite). 14
rod (16) and lever (15) to
the drive bolt (5).
Legend 6 The contact-pressure
11 Upper interrupter support 7 15 spring (10) acts on the
drive bolt (5) through the
12 Upper terminal 8 bracket (11) and lever (15).
13 Outer strut 10 16
14 Vacuum interrupter 11
HG11-2260b eps
15 Drive bolt of the 3AH2 vacuum circuit-breaker Section
vacuum interrupter 24 kV / 25 kA / 2500 A through the pole assembly;
mechanism version 2
16 Flexible connector
17 Lower interrupter support
for 3AH3 and 3AH4 1)
18 Lower terminal
1 up to 17.5 kV
19 Opening and 50 kA
contact-pressure spring 2
24 kV
40 kA
R-HG11-124 eps
10 Contact-pressure spring
36 kV
11 Bracket 31.5 kA
12
12 Upper post insulator The operating motion re-
13 Inner strut 3 sults from the operating
rod (16) and lever (15) to
14 Lower post insulator 4 the drive bolt (5).
15 Lever
16 Operating rod
14
5
6
7 15
8
1) 3AH4 7 traction circuit-breakers HG11-2261b eps 16
with 2 interrupter units per pole 3AH4 vacuum circuit-breaker Section
have a slightly different operating 24 kV / 40 kA / 2500 A through the pole assembly;
mechanism. (partitions not shown) mechanism version 3
Operating mechanisms
Control, display and operating elements (example)
The whole operating mechanism is con-
tained in a single housing, including the re- 1 6
leases, auxiliary switches, indicators and
actuating devices.
R-HG11-062a eps
1 Rating plate
Stored-energy operating mechanism 2 Hand crank coupling
The operating drive is usually a stored- 3 Closing spring charged
energy mechanism. The mechanism oper- 2 indicator
ates the pole assemblies through rods. The
closing spring can be charged either electri- 7 4 Operating cycle counter
cally or manually. It latches in when charg- 3
ing is complete. The closing spring acts as
the stored-energy mechanism.
To close the breaker, the closing spring can
4
5
8 5 CLOSED/OPEN
indicator
6 LV plug connector
1
be unlatched either mechanically by means
of the local CLOSE pushbutton or electri- 7 CLOSE pushbutton
cally by remote control. The closing spring 8 OPEN pushbutton
charges the contact-pressure/opening
springs as the breaker closes.
The now discharged closing spring will be 3AH1 vacuum circuit-breaker
charged again automatically by the mecha- 12 kV / 31.5 kA / 2000 A
Front side with control and display elements
nism motor if this exists.
The breaker is now capable of performing
the OPEN CLOSE OPEN switching se-
quence that is required for an unsuccessful
9 Motor and gearbox
R-HG11-063a eps
auto-reclosing operation.
All stored-energy mechanisms perform the 10 Closing spring
switching duties of synchronizing and rapid
load transfer (U) as well as auto-reclosing (K). 11 Closing solenoid
9 13
Snap-action operating mechanism 12 Opening spring
10 (only on vacuum circuit-
On the snap-action operating mechanism, breakers of mechanism
closing inevitably follows charging of the versions 2 and 3, page 1/6)
closing spring.
11 13 Auxiliary switch S1
During closing operation, the opening and 14 available in a choice
contact-pressure springs are charged at the 12 of 3 versions:
same time, therefore a stored-energy 2 NO + 2 NC
mechanism is available for opening. 6 NO + 6 NC
12 NO + 12 NC
Opening can be initiated on all vacuum cir-
cuit-breakers by various releases or locally 14 1st shunt release
by the OPEN pushbutton. 3AH1 vacuum circuit-breaker
If there is a failure of power to the motor, 12 kV / 31.5 kA / 2000 A
Front side open with interior view of mechanism
the spring can always be recharged housing
manually.
Trip-free mechanism
The 3AH vacuum circuit-breakers are
equipped with a trip-free mechanism
according to IEC 60 056 and VDE 0670.
In the event of an opening command being
given after a closing operation has been
initiated, the moving contacts return to
the open position and remain there even
if the closing command is sustained.
This means that the contacts of vacuum
circuit-breakers are momentarily in the
closed position under these circumstan-
ces, which is permitted according to
IEC 60 056 and VDE 0670.
Abbreviations:
NO = normally-open
NC = normally-closed
Description
Motor short-circuit protection The scope of the 3AH vacuum Two different types of shunt
circuit-breaker secondary releases are available:
Rated voltage Operating Power con-- Smallest possible equipment depends on the par-
of operating voltage sumption of rated current of the The 1st shunt release
mechanism the motor m.c.b. with
ticular application and offers a 3AY15 10 is normally included
C-characteristic variety of possible variations in the basic equipment of the
max. min. which satisfy nearly every re- vacuum circuit-breaker (ex-
V V V W VA A quirement. In the following, all cept of 3AH5 vacuum circuit-
secondary modules are describ- breaker). With this design,
ed. The availability and com- the electric tripping pulse is
For 3AH1, 3AH2, 3AH5 vacuum circuit-breakers
bination possibilities are stated fed to the OPEN latching
DC 24 26 20 350 8 for the relevant breaker type mechanism by means of a di-
48 53 41 350 6 series (see catalog sections 2 rect-acting solenoid armature
60 66 51 350 4 to 6).
1 110
220
121
242
93
187
350
350
2
1.6 Releases
in order to open the circuit-
breaker.
The 3AX11 01 shunt release
AC 110 121 93 400 2 A release is a device which is fitted if more than one
230 244 187 400 1.6 transfers commands from an shunt release is required (2nd
external source, such as a con- or 3rd release). In the case of
For 3AH3, 3AH3 83, 3AH4, 3AH4 7 vacuum circuit-breakers trol room, to the latching me- the 3AH5 vacuum circuit-
chanism of the circuit-breaker breakers a maximum of 2
DC 24 26 20 500 16 so that it can be opened or shunt releases is possible.
48 53 41 500 8 closed. The various types of re-
60 66 51 500 6 leases available are described With this design, the electri-
110 121 93 500 3 in detail below. The VDE desig- cal opening command is
220 242 187 500 1.6 nations for the devices are also boosted by means of a sole-
AC 110 121 93 650 3 given (in brackets) when they noid armature unlatching a
230 244 187 650 1.6 differ from the terms used in stored-energy mechanism
this catalog. before being fed to the
OPEN latching mechanism
The releases are designed for in order to open the breaker.
Motors of operating short-time duty up to 1 minute. Shorter opening times are
mechanism In the case of 3AH1 to 3AH4 possible with this release
vacuum circuit-breakers they than with the 3AY15 10 type.
The motors operate in short- are reset internally and in the
time duty and therefore the case of 3AH5 vacuum circuit- Refer to the selection and
voltage and power consump- breakers the pulse time has to ordering data in catalog sec-
tion do not have to be in con- be limited externally. tions 2 to 6 for the relevant
formance with the data of the types of vacuum circuit-break-
rating plate. 3AY15 10 closing solenoid ers concerning the maximum
possible number of releases
Protection of the motors Available for DC or AC opera- that can be fitted.
tion.
See table above. The closing solenoid unlatches
The inrush current in the motor the charged closing spring of
can be neglected since it is of the vacuum circuit-breaker,
very brief duration. closing it by electrical means.
Shunt releases
Shunt releases are used for
automatic tripping of circuit-
breakers by suitable protective
relays and for deliberate trip-
ping by electrical means.
They are intended for connec-
tion to an external power sup-
ply (AC or DC) but, in special
cases, may also be connected
to a voltage transformer for
manual operation.
Secondary equipment
Description
Secondary equipment
Insulation Class C to
VDE 0110
Continuous current 10 A
1) Can be ordered from your
Siemens Partner or from Making current 50 A
Harting, Steckverbinder und Breaking capacity 2A
Systemtechnik GmbH & Co. KG at 220 V DC,
Postfach 2451 T = 20 ms
D-32381 Minden
Germany
Abbreviations: NO = normally-open
NC = normally-closed
1
1 NO+1 NC internally wired
and
Auxiliary switch -S1, 6 NO+6 NC , of which:
Description
Schematic diagrams for 3AH vacuum circuit-breakers (without 3AH5) Not binding examples only
Basic equipment
1 S10, Mechanical
S11 anti-pumping
S14, Electrical
-S7 -S6
Release OFF
12 14 22 24 32 34 42 44 52 54 62 64
HA
HG11-2393a eps
S15 local closing
S21, Position switches -Y1
S22 (switch off motor-operated me-
chanism after spring charging) -X0
S3 Position switch 5 NO + 5 NC contacts available to the
(opens when closing spring customer (see also page 1/11)
charged)
S41, Position switches
S42 (signal charging state) Additional equipment, motor-operated mechanism and auxiliary switch
S6 Breaker tripping signal
Motor-operated mechanism with electrical local closing
S7 Cut-out switch for breaker
tripping signal -X0
V1, Varistor modules* 14
V2 -S14 -S15 -Y9 -S14
X0 24-pole or 64-pole plug 13
11 -S3 22
connector, or 24-pole HE -S1
terminal strip 12
21
Y1 1st shunt release -S21 -S22 -S3 -S41 -S42 21 3
13
-K1
Y2 2nd shunt release *
22 14
Y2 Instantaneous release
-M1 M P -V1 u
31
(for 3AH4 7 traction circuit- -K1
breakers only) 4
-S7 -S6 32
Y4 Current transformer-operated Release OFF 14 -Y9 A1 -K1 A1
release HA -S15
HG11-2398 eps
(rated current of 0.5 A or 1 A) 13 A2 A2
HG11-2396a eps -Y1
Y6 Current transformer-operated
release -X0
(tripping pulse 0.1 Ws)
Electrical Closing and
Y7 Undervoltage release
local closing anti-pumping
Y9 Closing solenoid
* Option: Additional equipment, releases (for combination possibilities, refer to Secondary equipment, catalog sections 2 to 6)
Varistor circuitry
for 60 V DC (on request) Releases
43
-S1
33
-Y7 D1 44
-S1 U<
34 D2
HG11-2402a eps
HG11-2399a eps
HG11-2401a eps
21
23
-S21 22 22 -S1
11 -S3 22 -S7
22 24
-S1
-S10 12
21 21
21 1 3 21 1
13
A1 -K1
-M1 M * 22 14 14 *
-V1 u u -S6 -S41 13 -S42 21 -V2 u
-S11 22
D2
21 2 4 -K1
-Y9
31
32
A1 -K1 A1
13 14 22
-Y1 A1
2 1
22
HG11-2394a eps
-S22 21 A2 A2 A2
Auxiliary switch -S1 (12 NO + 12 NC), instead of the auxiliary switch with 6 NO + 6 NC
-X0 -X0
21
-S21 22
1
A1 11 13 21 23 31 33 41 43 51 53 61 63 71 73 81 83 91 93 101 103 111 113 121 123
* -S1
-M1 M -V1 u
D2 12 14 22 24 32 34 42 44 52 54 62 64 72 74 82 84 92 94 102 104 112 114 122 124
2
22
-S22
HG11-2397a eps
HG11-2395 eps
21
-X0 -X0
Motor-operated Contacts available to the customer: 11 NO + 11 NC
mechanism (see also page 1/11)
43 43
-S1 -S1 Wiring in the 33
-Y7 D1 44 -Y7 D1 44 vacuum cir-
U< U< -S1
cuit-breaker 34
D2 D2
for der-
itry n
a l circu f the u
c o
Typi ection ase
1 conn rele 1 -Y2 A1
age
-R1 volt -R1 -A1
2 2 A2
HG11-2403a eps
HG11-2404a eps
-X0 -X0
L- L- Wiring in the L
system
Description
Schematic diagrams for 3AH5 vacuum circuit-breakers Not binding examples only
Basic equipment
mechanism after spring -S7 -S6
charging) Release OFF 2 NO + 2 NC contacts
S3 Position switch HA available to the customer
(opens when closing spring
charged) HG11-2405a eps -Y1
S4 Position switch
(signal charging state)
S6 Breaker tripping signal
S7 Cut-out switch for breaker
tripping signal
X0 Lower plug part Additional equipment
Y1 1st shunt release
Y6 Low-energy current -X0 -X0 -X0 Auxiliary switch
transformer-operated release 6 NO + 6 NC or 12 NO + 12 NC
22 (instead of 2 NO + 2 NC in the
Y7 Undervoltage release 21 -S3 21
-S21 21
-S7 basic equipment).
Y9 Closing solenoid 13 21 Most of these contacts are avail-
22 -K1 able to the customer and on
22
22 14 request can in some cases be
A1 31 wired to a plug connector or ter-
-M1 M -K1 minal strip (see page 1/11).
-S6 13
D2 32
Wiring of the
22 -Y9 A1 -K1 A1 14 secondary equipment
-S22 The secondary equipment is
A2 A2
21 wired only in cases where the
HG11-2264a eps
HG11-2269a eps
HG11-2265b eps
1
-R1
HG11-2266a eps
HG11-2270a eps
HG11-2268a eps
HG11-2267a eps
Abbreviations:
NO = normally-open * Only when explicitly ordered:
NC = normally-closed For combination possibilities, refer to Secondary equipment in catalog section 4.
Standards
HG11-2271a eps
ANSI C37.013 Mechanical operation Highest value of
0.9 24-hour mean: +35 C
(only 3AH3 83 high-current Reliability
0.8 Lowest value: 5 C
Correction factor a
Insulating capacity
circuit-breakers up to 63 kA)
Temperature rise
Climatic withstand capability.
0.7
0.6
Relative humidity
(average values measured):
1
Extensive series of tests are 0.1
0
Over 24 hours: max. 95%
carried out for the type-tests 0 m 1000 2000 3000 4000 5000 Over 1 month: max. 90%
specified in the relevant stand-
ards in order to achieve Altitude above sea level
reliable results. Under these conditions, con-
densation may sometimes
If a customer wishes tests to The following expression thus arise.
be carried out by an independ- applies for the selection of the The ambient air is not heavily
ent organization, the testing fa- devices and equipment:
polluted with dust, smoke,
cilities of the following com- corrosive or flammable gases,
pany are also available: Rated lightning impulse vapours or salt.
withstand voltage to be selected 1)
PEHLA Required rated lightning impulse
Gesellschaft fr withstand voltage 1)
elektrische Hochleistungs-
1.1 a
prfungen
Theodor-Stern-Kai 1
D-60596 Frankfurt/Main If, however, the actual insulating
Germany capacity must be determined
at the installation site the
The tests encompass switch- withstand voltage the re-
ing capacity, current-carrying duction of the insulating capa-
capacity and, where applicable, city from that for an altitude of
insulating capacity. The fees 0 m (sea level) must be
for these tests are charged by calculated as follows:
PEHLA according to their
current price schedule. Withstand voltage 2) = rated light-
ning impulse withstand voltage 1)
of the selected device.
Definitions:
Rated lightning impulse with-
stand voltage or rated short-
time power frequency
voltage 1) = target value
according to VDE, IEC, etc.
referred to sea level.
Lightning impulse withstand
voltage or power frequency
withstand voltage 2)
= actual value
at the respective height.
1) Rated
lightning impulse withstand voltage
Rated short-time
power frequency voltage
2) Lightning impulse withstand voltage
Power frequency withstand voltage
7.2 to 36 kV
2
R-HG11-065a eps
R-HG11-062a eps
R-HG11-064 eps
Vehicle production (photo Volkswagen Factory, Wolfsburg)
7.2 kV
3AH1 055-4
R-HG11-066a eps
Rated voltage 7.2 kV
31.5 kA / 2000 A Rated lightning impulse withstand voltage 60 kV
Rated short-time power frequency
withstand voltage 20 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
rm
iry fo
kA kA mm 800 A 1250 A 2000 A 2500 A 3150 A 4000 A Enqu e A / 2
ag
see p
Load char. No. 1 1
20 50 210 3AH1 053- 1 2
Electrical service life (load char. Nos. 1 to 8 ) Mechanical breaker service life 10,000 operating cycles
HG11-2235a eps
HG11-2236a eps
473
437
type 3AX11 03
587
HG11-2196e eps
2500/3150 A 565 mm
604 a On request:
More than 12 NO + 12 NC
Option: Gold-plated auxiliary
switch contacts
550
210 210 561 Terminal strip 24-pole or
plug connector
Electrical equipment
such as motor, release
64-pole or 24-pole wired to terminal strip or plug
105
50 kA / up to 3150 A connector
Weight approx. 180 kg Option: Gold-plated plug
connector contacts
211
668
494
Anti-pumping
HG11-2212a eps
610 571
Position switches (2 pieces)
for signalling
12 kV
3AH3 117-7
R-HG11-067a eps
Rated voltage 12 kV
50 kA / 3150 A Rated lightning impulse withstand voltage 75 kV
Rated short-time power frequency
withstand voltage 28 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
rm
iry fo
kA kA mm 800 A 1250 A 2000 A 2500 A 3150 A 4000 A Enqu e A / 2
ag
see p
Load char. No. 1 1
20 50 210 3AH1 113- 1 2
Electrical service life (load char. Nos. 1 to 8 ) Mechanical breaker service life 10,000 operating cycles
HG11-2235a eps
HG11-2236a eps
473
435
25 kA / up to 1250 A release 0.1 Ws, type 3AX11 04 system or with the protective
Weight approx. 75 kg relay made by SEG
Undervoltage release
2
190
HG11-2194c eps
473
437
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for customer
Auxiliary switch 12 NO + 12 NC* use
60
587
Anti-pumping
HG11-2196e eps
Dimension a in mm mechanical and electrical
1250/2000 A 550 mm
Breaker tripping signal
109
2500/3150 A 565 mm
604 a Operating cycle counter
Position switches (2 pieces)
for signalling
50 kA / up to 3150 A
Weight approx. 180 kg Varistor circuitry In the secondary circuit,
for 60 V DC
211
668
15 kV
R-HG11-074a eps
3AH1 166-6 Rated voltage 15 kV
40 kA / 2500 A Rated lightning impulse withstand voltage 95 kV
Rated short-time power frequency
withstand voltage 36 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
rm
iry fo
kA kA mm 800 A 1250 A 2000 A 2500 A 3150 A 4000 A Enqu e A / 2
ag
see p
Load char. No. 1 1
20 50 210 3AH1 163- 1 2
Electrical service life (load char. Nos. 1 to 8 ) Mechanical breaker service life 10,000 operating cycles
HG11-2235a eps
HG11-2236a eps
600
473
HG11-2215a eps
435
25 kA / up to 1250 A release 0.1 Ws, type 3AX11 04 system or with the protective
Weight approx. 75 kg relay made by SEG
Undervoltage release
190
2
HG11-2198d eps
473
type 3AX11 03
437
588
HG11-2200d eps
Weight
120 to 130 kg Anti-pumping
mechanical and electrical
Dimension a in mm
604 a 1250/2000 A 550 mm Operating cycle counter
2500/3150 A 565 mm Position switches (2 pieces)
for signalling
2nd release
Dimensions in mm
3rd release
192**
105*
To 3150A 4000 A
The 2nd and 3rd releases can be shunt releases, undervoltage
mm mm
releases or current transformer-operated releases as desired
776 d a 680 750 (0.5 A, 1 A or 0.1 Ws).
f b 668 733
e 1 piece per release. A maximum of 3 releases can be combined.
c 591
d 601
e 694
* Lowest breaker size up to 3150 A f 623 * Exchanged for the basic equipment (auxiliary switch 6 NO + 6 NC).
** Lowest breaker size for 4000 A g 697 Abbreviations: NO = normally-open, NC = normally-closed
17.5 kV
3AH3 228-7
R-HG11-057a eps
Rated voltage 17.5 kV
63 kA / 3150 A Rated lightning impulse withstand voltage 95 kV
(Partitions not Rated short-time power frequency
shown) withstand voltage 38 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
rm
iry fo
kA kA mm 800 A 1250 A 2000 A 2500 A 3150 A 4000 A Enqu e A / 2
ag
see p
Load char. No. 1 1
20 50 210 3AH1 213- 1 2
Electrical service life (load char. Nos. 1 to 7 ) Mechanical breaker service life 10,000 operating cycles
HG11-2238b eps
HG11-2378 eps
600
473
HG11-2215a eps
435
25 kA / up to 1250 A release 0.1 Ws, type 3AX11 04 system or with the protective
Weight approx. 75 kg relay made by SEG
Undervoltage release
190
2
HG11-2198d eps
473
type 3AX11 03
437
588
HG11-2200d eps
Weight
120 to 135 kg Anti-pumping
mechanical and electrical
Dimension a in mm
604 a
1250/2000 A 550 mm
Operating cycle counter
2nd release
Dimensions in mm
3rd release
192**
105*
To 3150A 4000 A
The 2nd and 3rd releases can be shunt releases, undervoltage
mm mm
releases or current transformer-operated releases as desired
776 d a 680 750 (0.5 A, 1 A or 0.1 Ws).
f b 668 733
e 1 piece per release. A maximum of 3 releases can be combined.
c 590
d 600
e 694
* Lowest breaker size up to 3150 A f 623 * Exchanged for the basic equipment (auxiliary switch 6 NO + 6 NC).
** Lowest breaker size for 4000 A g 697 Abbreviations: NO = normally-open, NC = normally-closed
24 kV
R-HG11-060a eps
3AH1 284-2 Rated voltage 24 kV
25 kA / 1250 A Rated lightning impulse withstand voltage 125 kV
Rated short-time power frequency
withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
rm
iry fo
kA kA mm 800 A 1250 A 1250 A 2000 A 2500 A Enqu e A / 2
ag
see p
Load char. No. 1 1
16 40 210 3AH1 252- 1 2
40 275 3AH1 262- 1 2
Electrical service life (load char. Nos. 1 to 6 ) Mechanical breaker service life 10,000 operating cycles
700
25 kA / up to 1250 A
HG11-2206c eps
Weight approx. 85 kg
1st shunt release Refer to table below for
102
2
190 120 kg to 130 kg
type 3AX11 03
437
Dimension a in mm
contacts available for customer
1250/2000 A 595 mm Auxiliary switch 12 NO + 12 NC* use
2500 A 610 mm On request:
188
More than 12 NO + 12 NC
604 a
Option: Gold-plated auxiliary
switch contacts
437
708 565
Weight
120 kg to 130 kg Position switches (2 pieces)
for signalling
210
778
2nd release
HG11-2218a eps
3rd release
The 2nd and 3rd releases can be shunt releases, undervoltage
releases or current transformer-operated releases as desired
194
36 kV
R-HG11-126 eps
3AH3 305-6 Rated voltage 36 kV*
31.5 kA / 2500 A Rated lightning impulse withstand voltage 170 kV**
(Partitions Rated short-time power frequency
not shown) withstand voltage 70 kV***
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 40.5 kV on request
** Up to 185 kV on request
*** Up to 85 kV on request
rm
iry fo
kA kA mm 1250 A 2000 A 2500 A Enqu e A / 2
ag
see p
Load char. No. 1 1
31.5 80 350 3AH3 305- 2 4 6
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 10,000 operating cycles
HG11-2255a eps
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
31.5 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
1000
solenoid
734
211
494
type 3AY15 10
HG11-2219a eps
Weight
approx. 175 kg type 3AX1101
A current transformer-operated
853 737 Current transformer-operated release for a tripping pulse of
release 0.5 A/1 A, type 3AX11 02 0.1 Ws is used in connection
Current transformer-operated with the 7SJ41 protective
release 0.1 Ws, type 3AX11 04 system or with the protective
820 823
relay made by SEG
350 350 737 Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for customer
2
Auxiliary switch 12 NO + 12 NC*
105
use
On request:
More than 12 NO + 12 NC
791
1000
31.5 kA /
2500 A switch contacts
HG11-2220a eps
Weight connector
approx. 180 kg
853 737 Option: Gold-plated plug
connector contacts
Anti-pumping
mechanical and electrical
7.2 to 36 kV
R-HG11-127 eps
3
R-HG11-071b eps
R-HG11-070 eps
(partitions not shown)
7.2 kV
R-HG11-073a eps
3AH2 056-6 Rated voltage 7.2 kV
40 kA / 2500 A Rated lightning impulse withstand voltage 60 kV
Rated short-time power frequency
withstand voltage 20 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
2
6
2 2
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
30 000 30 000
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
85
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
31.5 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
1250 A, 2000 A,
2500 A Additional equipment
190 40 kA /
Electrical operating mechanism Can also be manually controlled
437
1250 A, 2000 A,
587
HG11-2227b eps
604 a
Dimension a in mm 1st shunt release
type 3AY15 10
Refer to table below for
release combinations
1250/2000 A 550 mm
2500/3150 A 565 mm 2nd shunt release Max. 3 releases can be combined
type 3AX1101
A current transformer-operated
Current transformer-operated release for a tripping pulse of
release 0.5 A /1 A, type 3AX11 02 0.1 Ws is used in connection
Current transformer-operated with the 7SJ41 protective
release 0.1 Ws, type 3AX11 04 system or with the protective
relay made by SEG
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for
Auxiliary switch 12 NO + 12 NC* customer use
On request:
More than 12 NO + 12 NC
12 kV
R-HG11-073a eps
3AH2 116-6 Rated voltage 12 kV
40 kA / 2500 A Rated lightning impulse withstand voltage 75 kV
Rated short-time power frequency
withstand voltage 28 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
2
6
2 2
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
30 000 30 000
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
85
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
31.5 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
1250 A, 2000 A,
2500 A Additional equipment
190 40 kA /
Electrical operating mechanism Can also be manually controlled
437
1250 A, 2000 A,
587
HG11-2227b eps
604 a
Dimension a in mm 1st shunt release
type 3AY15 10
Refer to table below for
release combinations
1250/2000 A 550 mm
2500/3150 A 565 mm 2nd shunt release Max. 3 releases can be combined
type 3AX1101
A current transformer-operated
Current transformer-operated release for a tripping pulse of
release 0.5 A /1 A, type 3AX11 02 0.1 Ws is used in connection
Current transformer-operated with the 7SJ41 protective
release 0.1 Ws, type 3AX11 04 system or with the protective
relay made by SEG
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for
Auxiliary switch 12 NO + 12 NC* customer use
On request:
More than 12 NO + 12 NC
15 kV
3AH2 166-6
R-HG11-074a eps
Rated voltage 15 kV
40 kA / 2500 A Rated lightning impulse withstand voltage 95 kV
Rated short-time power frequency
withstand voltage 36 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
2
6
2 2
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
30 000 30 000
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
85
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
31.5 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
1250 A, 2000 A,
2500 A Additional equipment
190 40 kA /
Electrical operating mechanism Can also be manually controlled
437
1250 A, 2000 A,
587
HG11-2228b eps
604 a
Dimension a in mm 1st shunt release
type 3AY15 10
Refer to table below for
release combinations
1250/2000 A 550 mm
2500/3150 A 565 mm 2nd shunt release Max. 3 releases can be combined
type 3AX1101
A current transformer-operated
Current transformer-operated release for a tripping pulse of
release 0.5 A/1 A, type 3AX1102 0.1 Ws is used in connection
Current transformer-operated with the 7SJ41 protective
release 0.1 Ws, type 3AX11 04 system or with the protective
relay made by SEG
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for
Auxiliary switch 12 NO + 12 NC* customer use
On request:
More than 12 NO + 12 NC
17.5 kV
R-HG11-074a eps
3AH2 215-6 Rated voltage 17.5 kV
31.5 kA / 2500 A Rated lightning impulse withstand voltage 95 kV
Rated short-time power frequency
withstand voltage 38 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
2
6
2
7
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
30 000 30 000
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
85
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
31.5 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
1250 A, 2000 A,
2500 A, 3150 A Additional equipment
190 40 kA /
Electrical operating mechanism Can also be manually controlled
437
1250 A, 2000 A,
587
HG11-2228b eps
604 a
Dimension a in mm 1st shunt release
type 3AY15 10
Refer to table below for
release combinations
1250/2000 A 550 mm
2500/3150 A 565 mm 2nd shunt release Max. 3 releases can be combined
type 3AX1101
A current transformer-operated
Current transformer-operated release for a tripping pulse of
release 0.5 A/1 A, type 3AX1102 0.1 Ws is used in connection
Current transformer-operated with the 7SJ41 protective
release 0.1 Ws, type 3AX11 04 system or with the protective
relay made by SEG
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for
Auxiliary switch 12 NO + 12 NC* customer use
On request:
More than 12 NO + 12 NC
24 kV
3AH4 266-6
R-HG11-124 eps
Rated voltage 24 kV
40 kA / 2500 A Rated lightning impulse withstand voltage 125 kV
(Partitions Rated short-time power frequency
not shown) withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
rm
iry fo
kA kA mm 1250 A 2000 A 2500 A Enqu e A / 2
ag
see p
Load char. No. 1 1 1
25 63 210 3AH2 254- 2 4 6
63 275 3AH2 264- 2 4 6
50 000 50 000
Permissible operating cycles
30 000 30 000
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
25 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value)
790
HG11-2229a eps
Closing solenoid
type 3AY15 10
Dimension a in mm
1st shunt release Refer to table below for
188
customer use
Dimension a in mm On request:
1250/2000 A 595 mm More than 12 NO + 12 NC
109
714 a
2500 A 610 mm
210
778
for signalling
HG11-2231a eps
Mechanical interlocking
704 645 Varistor circuitry In the secondary circuit,
for 60 V DC
Halogen-free and flame-
retardant wiring cables
Condensation protection For 230 V AC
Silver-plated or tinned External terminals and internal
primary current paths connections on both sides
Hand crank For manual charging of
the closing spring
Silicone-free design
36 kV
R-HG11-126 eps
3AH4 305-6 Rated voltage 36 kV
31.5 kA / 2500 A Rated lightning impulse withstand voltage 170 kV*
(Partitions Rated short-time power frequency
not shown) withstand voltage 70 kV**
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 185 kV on request
** Up to 85 kV on request
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 120,000 operating cycles
HG11-2248a eps
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
30 000 30 000
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
1 2
20 20
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
31.5 40
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
1000
solenoid
734
211
494
type 3AY15 10
HG11-2232a eps
up to 2000 A
type 3AX1101
Weight A current transformer-operated
853 737 approx. 175 kg Current transformer-operated release for a tripping pulse of
release 0.5 A/1 A, type 3AX1102 0.1 Ws is used in connection
Current transformer-operated with the 7SJ41 protective
release 0.1 Ws, type 3AX11 04 system or with the protective
820 823 relay made by SEG
350 350 737 Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC Refer to page 1/11 concerning
contacts available for
Auxiliary switch 12 NO + 12 NC*
105
customer use
On request:
More than 12 NO + 12 NC
3
791
1000
switch contacts
31.5 kA /
HG11-2233a eps
2500 A connector
Weight Option: Gold-plated plug
853 737 approx. 180 kg connector contacts
Anti-pumping
mechanical and electrical
12 to 36 kV
R-HG11-076a eps
R-HG11-075a eps
Transformer station (Rheingau Elektrizittswerke GmbH)
Rated voltages 12 to 36 kV
Catalog section 4 Page
Maintenance-free up to 10,000 operating cycles
Rated data
Mechanical breaker service life 10,000 operating cycles
Selection and ordering data
Electrical and mechanical Rated short-circuit breaking currents up to 25 kA (r.m.s. value),
service life minimum 25 operating cycles
Dimensions and weights DC component 36%, higher values on request
Secondary equipment
User configurable secondary equipment
For rated voltages Optimum replacement for breakers of conventional design,
12 kV 4 / 44 / 3 e. g. low-oil breakers and dead-tank oil circuit-breakers
17.5 kV 4 / 44 / 5 Suitable for use in conjunction with, for example:
24 kV 4 / 64 / 7 Overhead lines and cables
36 kV 4 / 84 / 9 Transformers
Capacitors
Enquiry form A/3 Filter circuits
Motors
12 kV
3AH5 103-2 Rated voltage 12 kV
R-HG11-077a eps
20 kA / 1250 A Rated lightning impulse withstand voltage 75 kV
Rated short-time power frequency
withstand voltage 28 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
(in case of vacuum circuit-breakers for Isc = 20 kA and 25 kA)
4 20
40
50
210
160
3AH5 112-
1
2
3
2
50 210 3AH5 113- 1 2
Electrical service life (load char. Nos. 1 to 4 ) Mechanical breaker service life 10,000 operating cycles
HG11-2272 eps
HG11-2250a eps
cycles
Schaltspiele
435
35 kg to 45 kg
482 Additional equipment
44
435
Weight
40 kg to 45 kg 2nd shunt release Only a maximum of 2 releases
type 3AX1101 can be combined
44
16 kA / up to 1250 A Auxiliary switch 2 NO+2 NC, Free contacts available for customer use
Weight unwired Option: Auxiliary switch contacts
171
HG11-2223c eps
40 kg to 50 kg
435
482
unwired
210
592
505
210
491
491
Terminal strip 24-pole
Option: 12 NO + 12 NC available
only with 64-pole plug connector
Only in connection with auxiliary
4
or plug connector switches 6 NO+ 6 NC and 12 NO+12 NC
64-pole or 24-pole Option: Electrical equipment such
90
435
Weight
connector contacts
45 kg to 50 kg
Breaker tripping signal
44
6 Operating cycle
counter
8 combination possibilities of the releases
7 Closing solenoid
Basic equipment
8 Auxiliary switch Release Release combinations
14 1 2 3 4 5 6 7 8
8 9 PushbuttonCLOSED
1st shunt release type 3AY15 10
1 S1
10 PushbuttonOPEN
2nd shunt release type 3AX11 01
11 2nd release
Current trans- type 3AX11 02; 0.5 A or
2 9 12 1st release former-operated type 3AX11 02; 1 A or
10
S21
S22
S3
S4
7
* Exchanged for the basic equipment (auxiliary switch 2 NO + 2 NC).
Abbreviations: NO = normally-open, NC = normally-closed
Maximum equipment 13
17.5 kV
R-HG11-078a eps
3AH5 204-1 Rated voltage 17.5 kV
25 kA / 800 A Rated lightning impulse withstand voltage 95 kV
(Partitions Rated short-time power frequency
not shown) withstand voltage 38 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
Electrical service life (load char. No. 1 ) Mechanical breaker service life 10,000 operating cycles
50 000
Permissible operating cycles
20 000
10 000
5 000
2 000
1 000
500
200
100
50
25
20
1
10
0.5 1 2 5 10 20 kA 50
25
Breaking current (r.m.s. value)
Weight
40 kg to 45 kg
171 Basic equipment Remarks
630
HG11-2225c eps
435
482
S4
3 13 Mechanical
Condensation protection For 230 V AC
4 interlocking
11 or scanning Silver-plated or tinned primary External terminals and internal
5 current paths connections on both sides
99981 14 Low-voltage
6 12 plug connector Hand crank For manual charging of the closing spring
HG11-2253a eps
7 Silicone-free design
24 kV
R-HG11-083a eps
3AH5 252-1 Rated voltage 24 kV
16 kA / 800 A Rated lightning impulse withstand voltage 125 kV
(Partitions not Rated short-time power frequency
shown) withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Electrical service life (load char. No. 1 ) Mechanical breaker service life 10,000 operating cycles
50 000
Permissible operating cycles
20 000
10 000
5 000
2 000
1 000
500
200
100
50
25
20
1
10
0.5 1 2 5 10 20 kA 50
16
Breaking current (r.m.s. value)
Weight
55 kg to 70 kg Basic equipment Remarks
171
Additional equipment
767
435
HG11-2312c eps
Undervoltage release
type 3AX1103
Auxiliary switch 2 NO+2 NC, Free contacts available for customer use
unwired Option: Auxiliary switch contacts
708 567
30
1
8
Secondary equipment
View into the Terminal strip 24-pole
Option: 12 NO + 12 NC available
only with 64-pole plug connector
Only in connection with auxiliary
4
S1
mechanism housing or plug connector switches 6 NO+ 6 NC and 12 NO+12 NC
1 Gearbox 64-pole or 24-pole Option: Electrical equipment such
10 2 Position switch as motor, release wired to terminal
3 strip or plug connector
3 Closing spring
Option: Gold-plated plug
4 Motor connector contacts
12 5 Closing spring Breaker tripping signal
charged signal
HG11-2252 eps
S4
3 13 Mechanical
4 interlocking Hand crank For manual charging of the closing spring
11 or scanning
5 Silicone-free design
6
99981 14 Low-voltage
12 plug connector
HG11-2253a eps
36 kV
R-HG11-134 eps
3AH5 302-2 Rated voltage 36 kV
16 kA / 1250 A Rated lightning impulse withstand voltage 170 kV
(Partitions Rated short-time power frequency
not shown) withstand voltage 70 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Electrical service life (load char. No. 1 ) Mechanical breaker service life 10,000 operating cycles
50 000
Permissible operating cycles
20 000
10 000
5 000
2 000
1 000
500
200
100
50
25
20
1
10
0.5 1 2 5 10 20 kA 50
16
Breaking current (r.m.s. value)
973
645
171 Manual stored-energy mechanism
HG11-2258a eps
435
12
4 Motor
5 Closing spring
charged signal
Terminal strip 24-pole
Option: 12 NO + 12 NC available
only with 64-pole plug connector
Only in connection with auxiliary
4
or plug connector switches 6 NO+ 6 NC and 12 NO+12 NC
HG11-2252 eps
S4
17.5 kV
R-HG11-140 eps
R-HG11-143 eps
5
Xing Hydroelectric power plant, Brazil
17.5 kV
Rated
- voltage 17.5 kV
- lightning impulse withstand
R-HG11-139 eps
voltage 95 kV
- short-time power frequency
withstand voltage 38 kV*
- short-circuit duration 3 s
- short-circuit breaking current Isc and
- short-circuit making current Ima
see table
3AH3 838-7 * Up to 42 kV on request
63 kA / 8000 A
5
Possible
Electrical service life (load char. Nos. 1 to 3 ) Mechanical breaker service life 10,000 operating cycles
50 000
Permissible operating cycles
Zulssige Schaltspiele
20 000
10 000
5 000
HG11-2311a eps
2 000
1 000
500
High-current circuit-breaker, consisting of 3 individual
200
vacuum circuit-breakers with 3 poles per phase.
100
50
30 1
20
15 2 3
10
For dimensions for 1 phase, refer to page 5 / 3.
1 2 5 10 20 kA 50 100
63 80
Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
683
approx. 552 kg
494
solenoid
type 3AY15 10
1st
83
On request:
HG11-2380 eps
More than 12 NO + 12 NC
Option: Gold-plated auxiliary
149
switch contacts
63 kA / 8000 A
mechanical and electrical
80 kA / 8000 A
Weight of the Breaker tripping signal
211
3 vacuum Operating cycle counter
494
729
circuit-breakers
Position switches (2 pieces)
5
HG11-2381 eps
Silicone-free design
149
R-HG11-137 eps
R-HG11-138 eps
e. g. e. g.
1-pole traction circuit-breaker 1-pole traction circuit-breaker
27.5 kV, 50/60 Hz / 17.5 kV, 16 2/3 Hz /
25 kA / 2000 A 50 kA / 2500 A
R-HG11-044 eps
Krle substation, 110 / 15 kV, 16 2/3 Hz (traction power supply) with ICE power unit
R-HG11-136 eps
3AH4 757-6
50 kA / 2500 A Rated lightning impulse withstand voltage 125 kV
Rated short-time power frequency
withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Possible
Mechanical breaker service life Mechanical breaker service life Mechanical breaker service life
60,000 operating cycles 60,000 operating cycles 10,000 operating cycles
Load char. No. 1 Load char. No. 2 Load char. Nos. 3 4
HG11-2385b eps
Secondary
Dimensions and weights equipment
17.5 kV, 16 2/3 Hz
153 636
For a description of the secondary equipment,
refer to pages 1/ 8 to 1/ 13.
105
25 kA / 2000 A
31.5 kA / 2000 A Basic equipment Remarks
Additional equipment
Weight
approx. 90 kg
732
211
Electrical operating mechanism Can also be controlled manually
494
Closing solenoid
HG11-2389
type 3AY15 10
1st shunt release Refer to table below
68
211 On request:
More than 12 NO + 12 NC
Option: Gold-plated auxiliary
1276
switch contacts
plug connector
HG11-2390 eps
For 230 V AC
6
Silver-plated or tinned External terminals and internal
primary current paths connections on both sides
Hand crank For manual charging
of the closing spring
Silicone-free design
R-HG11-135 eps
3AH4 784-4 Rated voltage 27.5 kV, 50 / 60 Hz
25 kA / 2000 A Rated lightning impulse withstand voltage Up and
rated short-time power frequency
withstand voltage Ud
see table
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
6 Possible
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
50 000 50 000
Permissible operating cycles
Zulssige Schaltspiele
20 000 20 000
10 000 10 000
5 000 5 000
2 000 2 000
1 000 1 000
500 500
200 200
100 100
50 50
20 20
1 2
10 10
1 2 5 10 20 50 kA 100 1 2 5 10 20 50 kA 100
25 31.5
Breaking current (r.m.s. value) Breaking current (r.m.s. value) Ausschaltstrom (Effektivwert)
Secondary
Dimensions and weights equipment
27.5 kV, 50/60 Hz
153 721
For a description of the secondary equipment,
Up = 170 kV
refer to pages 1/ 8 to 1/ 13.
25 kA / up to 2000 A
90
732
HG11-2391 eps
1st
150
25 kA / up to 1250 A
Auxiliary switch 12 NO + 12 NC * contacts available
Weight approx. 135 kg
for customer use
On request:
More than 12 NO + 12 NC
211
494
plug connector
577
25 kA / up to 2000 A
Electrical local closing In place of mechanical
Weight approx. 135 kg local closing
Mechanical interlocking
211 Varistor circuitry In the secondary circuit,
494
for 60 V DC
Halogen-free and flame-
1238
7.2 to 36 kV
R-HG11-131 eps
R-HG11-130 eps
e. g. e. g.
special circuit-breaker, 2-pole explosion-protected circuit-breaker
24 kV / 25 kA / 800 A 12 kV / 23.6 kA / 630 A
R-HG11-129 eps
Mobile selective-cut road driving machine for underground mining type WAV 300 (photo Westfalia Lnen)
Special circuit-breakers
Catalog section 7 Page
Rated voltages 7.2 to 36 kV
Rated data
Maintenance-free up to 10,000 operating cycles
Service life
Secondary equipment
Ambient influences
Mechanical breaker service life 10,000 operating cycles
Rated short-circuit breaking currents up to 63 kA (r.m.s. value), min. 50 operating cycles
7
Standards
DC component 36 %, higher values on request
For
Special circuit-breakers 7 / 2 Explosion-protected circuit-breakers
1, 2 and 3-pole Rated voltages 7.2 and 12 kV
Explosion-protected 7/3 Maintenance-free up to 10,000 operating cycles
circuit-breakers
Mechanical breaker service life 10,000 operating cycles
Enquiry form A/5 Rated short-circuit breaking currents up to 23.6 kA (r.m.s. value)
o
ts int
q uiremen .
e
our r us a line
urn y p
We t . Just dro orm
in
reality uiry f
e ou r nq e A / 5
e
se ag
Also pendix, p
p
the A
7.2 to 36 kV
2-pole special
R-HG11-132 eps
1 and 2-pole special circuit-breakers
circuit-breaker can be derived from
24 kV / 3AH1 to 3AH4 3-pole vacuum
25 kA / 800 A circuit-breakers.
Pole-centre distance
550 mm
7 Current transformer-operated release, type 3AX11 04, for tripping pulse 0.1 Ws
Undervoltage release, type 3AX11 03
Instantaneous release, type 3AX60 1.
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC 1)
7.2 and 12 kV
Explosion-
R-HG11-133 eps
protected
circuit-breaker
12 kV /
23.6 kA / 630 A
R-HG11-142 eps
R-HG11-141 eps
3AH vacuum circuit-breaker
assembly line
Berlin switchgear factory of Siemens AG
Motor-operated mechanism DC V AC V, Hz
Company
Closing solenoid DC V AC V, Hz
Department
1st shunt release DC V AC V, Hz
Undervoltage release DC V AC V, Hz
Postcode/town
Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC
Tel.
Low-voltage connection Plug connector or Terminal strip, 24-pole
64-pole
FAX
24-pole
Varistor circuitry at 60 V DC
Department
Language of operating German English French Spanish
instructions
Name
Field of application and other requirements
A Street
Postcode/town
FAX
,
form
copy this it to your
e
Pleas and send
in r.
fill it ns partne
ie m e
S
Postcode/town
Field of application and other requirements A
FAX
,
form
copy this it to your
e
Pleas and send
in r.
fill it ns partne
ie m e
S
Rated short-circuit
25 kA 31.5 kA 40 kA 50 kA kA
breaking current
requesting Rated normal current 1250 A 2000 A 2500 A A
Offer
Phone call
Secondary equipment
Visit Refer to pages 6 / 3 and 6 / 5 for combination possibilities
Closing solenoid DC V AC V, Hz
Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC
Street
Varistor circuitry at 60 V DC
Department
Field of application and other requirements
Name
A Street
Postcode/town
FAX
,
form
copy this it to your
e
Pleas and send
in r.
fill it ns partne
e
Siem
Closing solenoid DC V AC V, Hz
Department
1st shunt release DC V AC V, Hz
Name
2nd shunt release DC V AC V, Hz
Street Current transf.- operated 0.5 A 1A Tripping pulse min. 0.1 Ws
release
Undervoltage release DC V AC V, Hz
Tel.
Auxiliary switch 6 NO + 6 NC 12 NO + 12 NC
FAX
Low-voltage connection Plug connector or Terminal strip, 24-pole
64-pole
24-pole
Siemens AG
Electrical local closing
Mechanical interlocking
Department
Varistor circuitry at 60 V DC
Name
Language of operating German English French Spanish
instructions
Street
Postcode/town
Field of applications and other requirements A
FAX
,
form
copy this it to your
e
Pleas and send
in r.
fill it ns partne
ie m e
S
HG 21.4 Surge Counting Devices for Surge Arresters E50001- K1521-A401- A1-7600
A
Protection and Power Quality
Substation
Control Systems SR 10.1.1 Fault and Digital Recorder SIMEAS R E50001-K4011-A101-A1-7600
SR 10.1.2 Central Fault Data Unit DAKON see Intranet
SR 10.1.3 OSCOP P The Program for Power Quality Recorders E50001-K4013-A101-A1-7600
SR 10.2 Power System Quality Analysis OSCILLOSTORE E50001-K4020-A101-A1-7600
SR 10.2.5 SIMEAS Q Quality Recorder E50001-K4025-A101-A1-7600
SR 10.2.6 SIMEAS P Power Meter E50001-K4026-A101-A1-7600
SR 10.4 SIMEAS T Transducers for Power Variables E50001-K4040-A101-A1-7600
SR 10.5 Active Filter and Power Conditioner for Distribution Networks SIPCON P/S E50001-K4050-A201-A1-7600
SR 10.6 Low Voltage Capacitors and Power Factor Correction Units SIPCON T E50001-K4060-A101-A1-7600
Energy Automation
Distribution Transformers
Transformers
GEAFOL Buchholz Relays to DIN 42 566 with Change-over Contacts A19100-T5101-A9A-7600
TV 1 Cast-Resin Transformers 100 to 2500 kVA E50001-K7101-A101-A2-7600
TV 2 TUMETIC and TUNORMA Oil-Immersed Distribution Transformers 50 to 2500 kVA E50001-K7102-A101-A1-7600
Energy Meters
Energy Meters
Z 9.1.1 7EC48 Solid-State 3-Phase Meter with Drum-Type Registers E50001-K8991-A101-A1-7600
Z 9.1.2 7E.62/63 Static Multifunction Meters E50001-K8991-A111-A3-7600
Z 9.1.3 7EC49 Electronic 3-Phase Meter with Drum-Type Registers E50001-K8991-A121-A1-7600
Z 9.1.4 7EC60/61 Multi-Tariff Maximum Demand Meter E50001-K8991-A131-A1-7600
Z 9.1.5 7E.64/65 Electronic Precision Meters E50001-K8991-A141-A1-7600
Z 9.2.2 DATAREG 48 Data Recording and Transmission Unit E50001-K8992-A111-A1-7600
Z 9.2.3 7FM803/804 Universal Tariff Unit E50001-K8992-A121-A1-7600
A Power Cables
Power Cables
SK 1.12 Power Cables Flexible Electric Cables for Cranes
and Material Handling Equipment E50001-K8112-A101-A1-7600
SK 3.30 SIENOPYR Power Cables E50001-K8133-A101-A1-7600
SK 3.40 Installation Cables, Power Cables E50001-K8134-A101-A2-7600
SK 4.20 Special-Purpose Cables for Industrial Applications E50001-K8142-A101-A1-7600
Subject to the
General Conditions of Supply The technical data, dimensions We reserve the right to adjust the
and Delivery and weights are subject to prices and shall charge the prices
for Products and Services change unless otherwise stated applying on the date of delivery.
of the Electrical and Electronic on the individual pages of this
Industry and to any other catalog.
conditions agreed upon with
the recipients of catalogs. The illustrations are
for reference only. A En 1.91a
In accordance with the present An export licence may however All product designations used are
provisions of the German Export be required due to country- trademarks or product names of
List and the US Commercial specific application and final Siemens AG or of other suppliers.
Control List, export licences are destination of the products.
Dimensions
not required for the products
Relevant are the export criteria
listed in this catalog.
stated in the delivery note and
the invoice regarding a possible All dimensions in this catalog are
export and reexport licence. given in mm.
Subject to change without notice.
Responsible for:
Technical contents: General editing:
Hermann Bierfelder, Gabriele Pollok,
Siemens AG, Dept. EV MNK V, Siemens AG, Dept. EV BK T,
Erlangen Erlangen
Printed in Germany
A/10Siemens HG 11.11 1999
KGK 08.99 12.0 80 101200 6101/ U886
Bereich
Energiebertragung und -verteilung
Geschftsgebiet Mittelspannung
Postfach 32 20
D-91050 Erlangen
http: // www.ev.siemens.de
Power
to the
Siemens Aktiengesellschaft Order No.: E50001-K1511-A111-A4-7600