Application Program For PCO5
Application Program For PCO5
Application Program For PCO5
Standard air-conditioning
units
Manual version: 1.0 - 14/09/97
Rif.: 36 EM
CONTENTS:
EPROM codes
Italian version: EPSTDICZUA
English version: EPSTDECZUA
French version: EPSTDFCZUA
German version: EPSTDDCZUA
2. INPUT/OUTPUT DESCRIPTION
The control card represents the heart of the system, as it contains the microprocessor that executes the control algorithm.
G 4
G0
J9 J8
1 J29 J28
B8
6
+24Vdc
B7
2 B6
AVSS
J15 J14 B5 5
3 B4
AVSS
VG0 B3
VG1 B2
Y1 AVSS
Y0 B1
ID11-220Vac IDCM2
ID11-24Vac ID10
ID11-Com ID9
ID8
ID12-Com ID7
ID12-24Vac ID6
ID12-220Vac
IDCM1
7
NO ID5
R11
R11 C ID4
NC ID3
ID2
NO ID1
R10 C R10
NC R1 C
NO R1
NO R9 R2
R9 C
C
NC NO R2
NO
R8 C R8 R3 C
R3
NO
NO
R7 C R7 R4 C
R4
NO
NO
R6 R6 R5 C
C
NO R5
NO
R13 R13 R12 C
C
NO R12
-List of components:
4. REGULATION STRATEGIES
The temperature control can be of the proportional or proportional + integral type; selection is possible in the M_MANUF_PARAM2 window, "Unit
configuration under manufacturers word branch.
The proportional control operates according to the difference between the temperature or humidity requested (SET POINT) and the value actually
being measured, consequently real;
The P+I regulation depends on the difference between the requested temperature and the temperature being measured and on the permanence
time (the integration constant is selectable at the M_MANUF_TIME2 window).
The humidity control is only proportional.
The PROPORTIONAL BAND defines the area of the temperature / humidity control. The control effect is proportional to the deviation from the set-point.
The DEAD ZONE defines an area near the set-point in which no device is energised.
PROPORTIONAL CONTROL
HEATING COOLING
DEAD ZONE
SET-POINT HALF OF TOTAL
SET BAND
HALF OF TOTAL
STEP CONCEPT
By step is meant an area of the proportional band which defines the values of switching on and off of a device (e.g. compressors; resistance;
humidifier; etc.)
MEANING OF STEP
the hysteresis is expressed as half the range between switching on (ON) and switching off (OFF).
Factory values:
- Compressor1set: 25% Compressor1 hysteresis: 25%
- Compressor2set: 75% Compressor1 hysteresis: 25%
If factory capacity-controlled compressors are utilised the steps of the compressors and its capacity controls coincide.
5.2. A TWO-COMPRESSOR UNIT WITH THE ENERGY SAVING OPTION
Factory values:
- Compressor1set: 49% Compressor1 hysteresis: 16%
- Compressor2set: 82% Compressor1hysteresis: 16%
If factory capacity-controlled compressors are utilised the steps of the compressors and its capacity controls coincide.
Factory values:
- Compressor set: 50% Compressor hysteresis: 50%
If factory capacity-controlled compressors are utilised the step of the compressor and its capacity control coincide.
Factory values:
- Compressor1 set: 66% Compressor1 hysteresis: 33%
If factory capacity-controlled compressors are utilised the step of the compressor and its capacity control coincide.
HOT WATER
RAMP
Factory values:
- Resistance1 set: 25% Resistance1 hysteresis: 25%
- Resistance2 set: 75% Resistance 2 hysteresis: 25%
5.6. SINGLE-RESISTANCE UNIT
Factory value:
- Resistance set: 50% Resistance hysteresis: 50%
6. DEVICE MANAGEMENT:
6.1. COMPRESSORS
Once started a compressor can not be stopped before 1 min. (factory-made) (MASK-SELECTABLE VALUE).
Once started a compressor can not be stopped before 6 min. (factory-made ) (MASK-SELECTABLE VALUE).
The possible starting of the second compressor can not take place within 3 min. from the starting of the first one (factory-made)
(MASK-SELECTABLE VALUE).
In the two-compressor configuration the compressor ROTATION can be selected
RESISTANCE
In the 2-resistance configuration the following 2 functions are available:
STANDARD
during connection:
RESISTANCE1
RESISTANCE1 + RESISTANCE2
during disconnection:
RESISTANCE1 + RESISTANCE2
RESISTANCE1
BINARY
during insertion
RESISTANCE1
RESISTANCE2
RESISTANCE2 + RESISTANCE1
during connection
RESISTANCE2 + RESISTANCE1
RESISTANCE2
RESISTANCE1
- if in the M_MANUF_PARAM1window ("Compressors with valve in Energy Saving") you answer yes, then the compressor steps within the band
are delayed in reference to the cold-water ramp, but only when the necessary conditions for the energy saving operation occur. In the opposite
case, namely energy saving being enabled but in the absence of the functioning conditions, the compressors operate normally.
- if you answer no in this window, then the compressor steps are eliminated and only the ramp in action is maintained in the presence of the
conditions which require that energy saving be started. In the opposite case the compressors operate normally.
6.4. MANUAL CONTROL
This part of the program allows you to manually operate the units DEVICES, thus excluding the operation of the pCO control, but maintaining the
interlock with the protections in order to ensure the security and integrity of the components being utilised.
To enable manual functioning it is necessary to carry out the operations described in the paragraph dedicated to the pCO keypad.
The manual state of the machine is identified by the appearance of the message Manual procedure on the last line of the display.
- Dehumidification is enabled only if the ambient temperature falls within the alarm limits.
FOR VALUES EXCEEDING THIS TEMPERATURE RANGE DEHUMIDIFICATION IS INHIBITED (see graphs of the temperature control).
Humidification can be carried out through the ON/OFF control as for the dehumidification, described above (that is a humidification step is
selected in exactly the same way as for dehumidification) or with the integrated-humidifier control (selectable from M_MANUF_CONF4 mask,
under the Unit configuration branch, protected by manufacturers password).
HUMIDITY CONTROL
HUMIDIFICATION DEHUMIDIFICATION
SET BAND
HALF OF TOTAL
G
220 Vac 24Vac
G0
RS422
CONDUCTIVITY
B8
J1 +24
CURRENT
1 B7
B6
AVSS
J15 J14
B5
clock B4
AVSS
VG0 1 B8 G0 B7 G G0 O1 O2
J2 B3
VG1
B2 J6 J5 J4
J20
Y2
AVSS
Y1
1 B1
ID11R 1 IDCM2
LEVEL
ID10
ID11 ID9
J3
J21 ID8
ID12R
ID7
1 ID6
ID12
R11 IDCM1
NO11 1
ID5
C11
ID4
NC11
J4 ID3
R10 ID2
NO10
R1 1 ID1
C10 J22
NC10 C1
R9 R2
NO1
NO9 J5
J3 J2 J1
C9 C2
NC9 1 NO2
R8 R3 T1 T2 C1 C2 L1 L2
24 Vac NO8 1 C3
C8 NO3
R7 R4
POWER
NO7 C4
TAM
C7 NO4
DRAIN J24 J6
R6 R5
FILL
NO6 C5
C6 NO5
R13 R12
NO13 C12
C13 1 NO12
L1
C0 and C1 for E400TA three-phase cylinders with a nominal capacity from 8 to 13 Kg/h:
Nominal Capacity in Kg/h
8 Kg/h 13 Kg/h
C0 C1 C0 C1
208 95 250 103 250
220 84 250 93 250
230 78 250 85 250
240 72 250 79 250
380 34 250 37 250
400 32 250 34 250
415 30 250 32 250
440 28 250 30 250
480 26 250 27 250
575 21 250 22 250
C0 and C1 for I400TW three-phase cylinders with a nominal capacity from 23 to 42Kg/h
Nominal Capacity in Kg/h
23Kg/h 33Kg/h
C0 C1 C0 C1
208 57 500 59 500
220 52 500 53 500
230 48 500 49 500
240 44 500 46 500
380 20 500 22 500
400 18 500 20 500
415 17 500 19 500
440 16 500 17 500
480 14 500 16 500
575 11 500 13 500
Nominal Capacity
42Kg/h
C0 C1
380 23 150
400 21 150
415 20 150
440 19 150
480 18 150
575 15 150
ERP
100%
0%
SET-POINT
The preset capacity is the maximum required capacity and is a value that can change between the 30% of nominal C. and the 100% of nominal
C. According to the nominal capacity, the preset capacity and the ERP proportional humidity error, the following humidifier graph will be obtained :
A 100%P_NOM
ERP = propotional humidity error
relevant set and differential
B Steam production to de obtained :
A-100%Pn
C B-50%Pn
C-30%Pn
30%P_NOM
The humidifier has a minimum capacity equal to the 30% of the nominal C. when the ERP = 0 and increases proportionally to the increase of the
preset capacity when the ERP=100%
1 In case of current failure neither the control should operate, but if only a phase is absent you could measure no current whereas actually this is
above the security threshold
2 This to prevent the current, once the alarm has been reset and the power contactor reenergised, from raising quickly beyond the allowed limits.
Imax
300%In
High current
250%In
200%In
170%In
130%In
Forced
drain
0 20 60 t
The forced drain lasts 5 seconds, and is not signalled. The high current alarm causes a 30-second water drainage and stops the humidifier.
Factory values being taken as machine parameters by the pCO if you answer yes to the first window of the Init. configuration in the
manufacturers menu:
9. ALARM MANAGEMENT
Every state of alarm is signalled:
- acoustically by the buzzer incorporated into the pCO relay card;
- visually by the LED lighting of the ALARM button
It is possible to recall a message relative to an alarm occurred by pressing the ALARM button. To rearm the alarms merely press the ALARM
button when an alarm window is displayed.
10.1. KEYPAD
The pCO is equipped with a 15-button keypad that along with the display represents the interface between the operator and the pCO system.
The keypad provides the operator with the following functions:
ON / OFF button Energises and deenergizes the unit. The unit has to be switched on by this button in order to carry out any
control, verification or operation. (See Regulation ON/OFF)
ALARM button The pressure of this button displays the first active alarm window and simultaneously it switches off the
buzzer. A second pressure of this button reactivates the alarm or the active alarm. The display of several
alarm masks can be obtained by pressing the UP / DOWN arrow buttons. If there are no active alarms in
storage, by pressing this button you go to the window NO ACTIVE ALARM.(See the regulation of the Alarms)
ENTER button In the value pre-setting masks, by pressing the button the first time, the cursor goes to the first parameter of
the window. When pressing again, the selected parameter is confirmed and the cursor moves to the following
parameter. Afterwards, from the last parameter you return to the position on the upper left (cursor in the
0.0 position of the display)
PROG button The password is requested. If properly introduced, you move to the M_PARAM_USER3 window
MENU+PROG buttons The buttons must be pressed and released simultaneously. The password is requested. If properly introduced,
you move to the M_MANUF_PASS window
10.2. LED
At the side of each button a green LED is found which lights up when the associated button is being pressed and indicates in which group of
masks the user is situated.
Three other LEDs are placed under the rubber buttons and indicate respectively:
1. ON / OFF button green LED
indicates that the instrument is ON and operating.
2. ALARM button red LED
indicates the presence of an alarm condition.
3. ENTER button yellow LED
Indicates that the instrument is properly supplied.
VERSION BUTTON
M_VERSION
MENU BUTTON
MAIN_MASK
Displays the current working modes
00:00 00/00/00 of temperature and humidity.
Room temp. 00.0 C
Room humid. 00.0%
WORK_MODE
Displays the current working
Working mode mode. The blackened box
means that the specific
Cooling Heating function at issue is now activated
Humid. Dehumid.
MAINTENANCE BUTTON
M_VIS_TIMER1
Shows the operating time of the equipments
Operating hours:
Main fan 000000
Compressor 1 000000
Compressor 2 000000
M_MAINT_PASS
Enter maintenance
password
0000
Right password!
M_SEL_TIMER1
Pre-setting of the fan time operating time
Main fan hour meter established before the maintenance
Threshold: 000x1000
Req.reset: N 000000
M_SEL_TIMER2
As above
Compressor 1 hour
meter
Threshold:: 000x1000
Req.reset: N 000000
M_SEL_TIMER3
As above
Compressor 2 hour
meter
Threshold:: 000x1000
Req.reset: N 000000
M_CALIBRATION1
Probe calibration window no.1
Probe adjustment:
Room temp.: 0.0C
Supply air: 0.0C
Out water: 0.0C
M_CALIBRATION2
Probe calibration window no.2
Probe adjustment:
Inlet water: 0.0 C
Room humid.:0.0 %
M_MANUAL1
Manual activation of the devices
Manual procedure:
Main fan: N
Energy saving N
M_MANUAL2
As above
Manual procedure:
Dehumidifier N
Humidifier N
M_MANUAL3
As above
Manual procedure:
Open cool.fl.v. N
Close cool.fl.v. N
M_MANUAL4
As above
Manual procedure:
Unloader 1 N
Unloader 2 N
M_MANUAL5
As above
Manual procedure:
Open heat.fl.v. N
Close heat.fl.v. N
M _MANUAL6
As above
Manual procedure
Cool. valve N 00.0 V
Heat. valve N 00.0 V
M_DISABLE_HUMID
PRINTER BUTTON
M_PRINTER
Printer management
Cyclic print 000 h Time interval for the cyclic print
Immediate print of Activation /forcing of a print
unit report N
I/O BUTTON
M_SYNOPTIC1
Analog inputs Displays the state of the analog inputs and outputs
Room Temp. 00.0 C It is displayed with the I/O button
Supply air -00.0 C
Room humid. -00.0 %
M_SYNOPTIC2
As above
Analog Inputs
Inlet water -00.0 C
Outlet water-00.0 C
M_SYNOPTIC3
As above
Digital inputs
C=Close O=Open
01:CCCCC 06:CCCCC
11:CC
M_SYNOPTIC4
As above
Analog outputs
Cooling valve 00.0 V
Heating valve 00.0 V
M_SYNOPTIC5
As above
Digital outputs
C=Close O=Open
01:OOO 04:OOO
07:OOO 10:OO
M_SYNOPTIC6
As above
Humidifier
Main switch OFF
Fill valve OFF
Drain valve OFF
M_SYNOPTIC7
M_SYNOPTIC8
As above
Humidifier
Wat.level open
Conduct. 0000 uS/Cm
M_SYNOPTIC9
As above
Humidifier
Cyl. worn out N
Mode ---------
Status h. ---------
CLOCK BUTTON
M_REG_CLOCK
Regulation of the internal clock
Clock & date (it is necessary to mount the watch card)
Setting
Time 00:00
Date 00/00/00
M_CLOCK_PASS
M_DAILY_TEMP
Enabling of the automatic operation with
Daily time zone with change of the temperature set-point
automatic temper.
set-point variation
N
M_DAILY1_TEMP
Pre-setting of the time band no.1
Temperature The time band starting hour
Daily time zone 1 and the relevant temperature set-point
Start time 00:00 will be selected.
Set-point 00.0C The time band ending will be the
beginning of the following one.
M_DAILY2_TEMP
As above
Temperature
Daily time zone 2
Start time 00:00
Set-point 00.0C
M_DAILY3_TEMP
As above
Temperature
Daily time zone 3
Start time 00:00
Set-point 00.0C
M_DAILY4_TEMP
As above
Temperature
Daily time zone 4
Start time 00:00
Set-point 00.0 C
M_DAILY_HUMID
Enabling of the automatic operation with change of the
Daily time zone with humidity set-point
automatic humidity
set-point variation
N
M_DAILY_HUMID1
Time band no.1 pre-setting
Humidity The band hour-start and the relevant humidity
Daily time zone 1 set-point will be preset.
Start time 00:00 The end of the time band will be the start of the
Set-point 000.0 % following one.
M_DAILY_HUMID2
As above
Humidity
Daily time zone 2
Start time 00:00
Set-point 000.0 %
M_DAILY_HUMID3
As above
Humidity
Daily time zone 3
Start time 00:00
Set-point 000.0 %
M_DAILY_HUMID4
As above
Humidity
Humidity
Daily time zone 4
Start time 00:00
Set-point 000.0 %
SET BUTTON
M_CALC_SETP
Displays the values of the
Actual set-points active set-points.
Temperature 00.0 C (if the functions are active of time
Humidity 000.0 % and temperature compensation and
humidity or compensation)
M_SELECT_SETP
Change of the set-points.
Set-points The values must be included within the limits
Temperature 00.0 C being preset
Humidity 000.0 % in the M_PARAM_USERx masks
PROG BUTTON
M_SERV_PASS
M_PARAM_USER1
Presetting of the temperature set-point limits.
Temperature set-point
limits
Minimum 00.0C
Maximum 00.0 C
M_PARAM_USER2
Presetting of the humidity set-point limits
Humidity set-point
limits
Minimum 000.0 %
Maximum 000.0 %
M_PARAM_USER3
Presetting of the proportional band
Temperature and of the neutral zone for the temperature
Band 00.0C regulation.
Neutral zone 00.0C
M_PARAM_USER4
Humidity
Band 00.0 % Humidity proportional band
Production 00.0 kg/h Maximum preset production
M_PARAM_USER5
Automatic start enabling after voltage drop.
Automatic restart
after power fail. N
Remote on/off Enabling / disabling On/Off remote
enabled N (from digital input)
M_PARAM_USER6
Presetting of the offset parameter
Offset energy energy saving
saving 00.0 C
M_PARAM_USER7
Enabling of the temperature set-point compensation
Compensation
enabled N
M_PARAM_USER8
Parameters for the compensation
Compensation
Set-point 00.0C
Band 00.0 C
Offset 00.0 C
M_PARAM_USER9
Values that limit the temperature range
Room temperature
alarms Value to be subtracted from the temperature set-point
Offset low 00.0 C Value to be added to the temperature set-point
Offset high 00.0 C
M_PARAM_USER10
As above for the humidity
Room humidity
alarms
Offset low 000.0 %
Offset high 000.0 %
M_PARAM_USER11
Values within which the outlet water temperature has to
Outlet water temp. be maintained
thresholds alarms
Low 00.0 C
High 00.0 C
M_PARAM_USER12
Address for the serial connection
Identific. address to an external supervisory system
for supervisor
system network 000
M_PARAM_USER13
New user password presetting
Enter new service
password
0000
MENU+PROG BUTTON
M_MANUF_PASS
Enter manufacturer
password
0000
Right password
M_MANUF_MENU
Submenu of the manufacturer's branch.
Unit configuration To preset the item being requested
General parameters you move downwards with arrow and
Timing and presetting is made with ENTER
Unit initializat.
M_MANUF_CONF1
The devices present in the machine are enabled
Clock board N
Printer N
Supervisor board N
M_MANUF_CONF2
As above
Supply air temper.
probe enabled N
Outlet water temper.
probe enabled N
M_MANUF_CONF3
As above
External air temper.
probe enabled N
Inlet water temper.
probe enabled N
M_MANUF_CONF4
As above
Room humidity
probe enabled N
Integr. humidifier
enabled N
M_MANUF_CONF5
As above
Energy saving N
Heaters no. 0
Compressors no. 0
Unloader comp. N
M_MANUF_CONF6
As above
Cooling valve N
Heating valve N
Cooling fl.valve N
Heating fl.valve N
M_MANUF_PARAM1
M_MANUF_PARAM2
I two compressors are installed,
Temp.regulation P operation in rotation of the compressors;
Rotation comp. N no. of compressors for the dehumidification;
Comp.per dehumid. 0 capacity control logic: Normally Closed or
Logic unloader N.C. Normally Open. The regulation
proportional(P) or proportional +integral(P+I)
M_MANUF_PARAM3
Logic of the dehumidification relay
Logic
dehumidific. N.O.
M_MANUF_PARAM4
M_MANUF_PARAM5
As above
Step compressor 2
without energy sav.
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM6
As above
Step unloader 1
without energy sav.
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM7
As above
Step unloader 2
without energy sav.
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM8
Parameters relevant to the position of the compressors,
Step compressor 1 capacity controls with energy
with energy saving saving.
Position 000.0 % See "Unit with a compressor in energy saving"
Hysteresis 000.0 %
M_MANUF_PARAM9
As above
Step compressor 2
with energy saving
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM10
As above
Step unloader 1
with energy saving
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM11
As above
Step unloader 2
with energy saving
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM12
Presetting of of the step relevant to the resistance
Step heater 1 heating. See paragraph "Concept of step"
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM13
As above
Step heater 2
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM14
As above
Step heater binary
control
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM15
Parameters for the regulation
Cooling 0/10V valve of the 0/10V modulating cooling valve
type. The operating features
Begin 000.0 % are described in the paragraph "Temperature regulation
End 000.0 % graphs"
M_MANUF_PARAM16
As above
Heating 0/10V valve
Begin 000.0 %
End 000.0 %
M_MANUF_PARAM17
Parameters for the three-point modulating
Cooling 3p valve valve. See " Temperature regulation graphs"
Begin 000.0 %
End 000.0 %
M_MANUF_PARAM18
As above
Heating 3p valve
Begin 000.0 %
End 000.0 %
M_MANUF_PARAM19
Humidification step regulation.
Step humidification See "HUMIDITY CONTROL GRAPHS"
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM20
Humidification step regulation.
Step dehumidific. See "HUMIDITY CONTROL GRAPHS"
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM21
Dehumidification stop step.
Low temperature See "HUMIDITY CONTROL GRAPHS"
limit (stop dehum.)
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM22
Dehumidification stop step.
High temperature See "HUMIDITY CONTROL GRAPHS"
limit (stop dehum.)
Position 000.0 %
Hysteresis 000.0 %
M_MANUF_PARAM23
Parameters for the identification of
Nomin. prod. 00 kg/h humidifier type
Voltage 000 V
Phase number 1
TAM model 050
M_MANUF_PARAM24
Enabling of the drain without voltage
Enable drain without
voltage N
Parameter C0 0000 CAREL PARAMETER 0(see paragraph
M_MANUF_TIME1
Fan start time delay
Time delay switching
main fan on 000 sec Fan stop time delay
Time delay switching
main fan off 000 sec
M_MANUF_TIME2
M_MANUF_TIME3
Low pressure alarm Low pressure alarm delay. Starts when the
delay time 0000 sec compressor starts.
Temperature alarm high /low humidity alarm delay
delay time 0000 sec
M_MANUF_TIME4
Air flow controller acquisition delay
Air flow alarm delay
time 0000 sec
M_MANUF_TIME5
Compressor timing
Minimum compressor
off time 0000 sec
Minimum compressor
on time 0000 sec
M_MANUF_TIME6
As above
Delay between starts
same comp. 0000 sec
Delay between starts
diff. comp. 0000 sec
M_MANUF_TIME7
Resistance timing
Delay between starts
two unload. 0000 sec
Delay between starts
diff. heat. 0000 sec
M_DEFAULT
Storage loading of the factory values
Press key ENTER to See table "PROGRAMMABLE SETS"
insert manufacturer
parameters
WAIT PLEASE
M_PASS_MANUF
Enter new
manufacturer
password 0000
12. ALARMS:
AL_1
High pressure alarm or thermal
AL01 00:00 00/00/00 of the compressor number 1.
Compressor 1
General Alarm
AL_2
High pressure alarm or thermal
AL02 00:00 00/00/00 of the compressor number 2.
Compressor 2
General Alarm
AL_3
AL_4
AL_5
AL_6
AL_7
AL_8
AL_9
AL_10
AL_11
AL_12
AL_13
AL_14
AL_15
AL_16
AL_17
The operating threshold
AL17 00:00 00/00/00 preset in the mainutenance branch has been
Compressor 1 exceeded
Operation Hour
Alarm
AL_18
As above
AL18 00:00 00/00/00
Compressor 2
Operation Hours
Alarm
AL_19
As above
AL19 00:00 00/00/00
Main Fan
Operation Hours
Alarm
AL_20
AL_21
AL_22
AL_23
AL_24
AL_25
AL_26
AL_27
AL_28
AL_29
- user interface;
cod. PCOT000CB0 LCD "4X20"
- eprom;
cod. EPSTD*CZUA
English(E), Italian(I), French(F) and German(D) versions are available l
- pCO pCO relay card:
- extractable terminals cod. PCOB000A00 / PCOB000A21 / PCOB000B00 / PCOB0000B2
- probes:
of different type and code according to request.
Carel reserves the right to modify the features of its products without prior notice.
CAREL srl
Via dellIndustria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 Fax (+39) 049.9716600