A048 AGF Manual
A048 AGF Manual
A048 AGF Manual
APPLICATIONS
Filtering surface water with high concentration of algae and other organic material.
Filtering well water to remove sand particles and undissolved iron.
SPECIFICATIONS
SPECIFICATIONS
Maximum Flow Rates: Good water quality - 25 GPM/sq. ft.
AGF HEADLOSS
Dirty water - 20 GPM/sq. ft. (for single filter in filtration cycle)
10
Minimum Operating Pressure for Filtration: 15 psi
PRESSURE PER SQUARE INCH
recommended.
MANIFOLD FILTRATION DIRTY WATER AVERAGE WATER CLEAN WATER WEIGHT MEDIA
FILTERS
SIZE AREA (ft2) 14-18 GPM/ft2 18-28 GPM/ft2 23-28 GPM/ft2 (FILTERS ONLY) REQUIRED
4 (TEE) T6" x 10" x 6" 50.0 700-900 900-1,150 1,150-1,400 1,060 LBS. 5,200 LBS.
5 (TEE) T6" x 10" x 6" 62.5 875-1,125 1,125-1,440 1,440-1,750 1,325 LBS. 6,500 LBS.
6 (TEE) T6" x 10" x 6" 75.0 1,050-1,350 1,350-1,725 1,725-2,100 1,590 LBS. 7,800 LBS.
DRAIN
G
OUTLET
OUTLET
MANIFOLD
E
L
H D
Outlet
Inlet
Backflush
BACKFLUSH MODE Port Backflush
During backflush, the inlet port closes and the backflush Valve
port opens. This reverses the flow of water in the filter. Clean
water from the other filters now flows into the filter from the
bottom, lifting the sand media and freeing the accumulated
debris. The debris will be flushed out the top of the filter
through the backflush valve into the backflush manifold.
Only one filter should backflush at a time. The backflush
flow depends on the pressure differential between the outlet
manifold and the backflush manifold.
From Outlet
Manifold
INSTALLATION
Bring the filter as close to the cement pad as possible. 17
Remove the plastic straps and the cover wrapping.
Set the 3 legs aside. Remove the styrofoam packaging and lay it next to FIGURE 1 - Height above ground level
the tank.
Lay the tank on its side on top of the packing material.
Insert the unattached legs as follows:
- Determine the correct filter height. Note: With the legs inserted as
provided, the outlet will be approximately 17 above ground level. If the
battery height needs to be lower, for example retrofitting to an existing
system, the legs may be cut to size. See Figure 1.
CAUTION: Once fully inserted, the legs cannot be removed. Carefully check
measurements before proceeding.
- Make all cuts as square as possible and verify that the three legs are
the same length after cutting.
- Insert the legs into the leg housing.
- Place a piece of wood over the leg base cap and strike the wood with
a hammer until the leg is fully seated in the housing. FIGURE 2 - Assembling the legs
See Figure 2.
When placing the filter upright, make sure that two legs are resting firmly
on the ground. Two people are recommended for this process.
Orient the AGF filter tanks on the foundation by facing tank access ports
in the same direction. See Figure 3.
Pump inlet should be 3 to 4 below the surface and a minimum of 2.5 off
the bottom to prevent intake of excess dirt when pumping from a ditch or
reservoir.
MANIFOLD ASSEMBLY
Align and attach the inlet manifold to the backflush valves with the grooved
victaulic couplings.
Align and attach the outlet manifold to the filter tank outlet with the grooved FIGURE 5 - Backflush valve installation
victaulic couplings.
Tighten only enough to hold the manifolds in place - do not overtighten.
Yellow
Master
Relay Valve
115 VAC 115 or 230 Solenoid on Tanks
M is master valve - used with Pressure Sustaining Normally Open OR
230 VAC
50/60 Hz
Transformer Solenoid Common
or Electric valves to control the downstream flow. See Figure 10. 12 VDC POWER WIRING
Terminals 1-8 for each solenoid are the hot lead. Do not use transformer and wire + 12 VDC to first two terminals. Do not use third terminal.
C 8 7 6 5 4 3 2 1 A M
12 VDC
From
Solar
+ Panel
Relay
Master
Valve
12 VDC Solenoid on Tanks
Battery
Loosen bolt (A). Pull hub assembly off. See Figure 11. FIGURE 10 - Backflush controller wiring
Remove (D) and push terminal (C) out with a screwdriver through
the access port.
A
Connect wires to 1 and 2 of the terminal block (C). For DCL B
solenoids, connect negative (black) to 1. If no conduit is used,
first put the wires through the 1/2 x 1/4 reducer. 2
C
BACKFLUSH OPERATION
BACKFLUSH PRINCIPLES Inlet
During backflush, once a preset pressure differential or preset time is reached, Backflush
Port Backflush
the backflush controller will activate one solenoid (valve and filter tank) at a time Valve
to perform a backflush operation. The inlet port closes and the backflush port
opens. This reverses the flow of water in the media filter; clean water from the
other filters now flows into the filter from the bottom and through every mushroom
with equal pressure, lifting the sand media and freeing the accumulated debris.
The debris will be flushed out the top of the filter through the backflush valve into
the backflush manifold to a suitable location. Only one filter should backflush at
a time. The water which is backflushing one filter will have passed through the
other filters and thus backflushing will be done with clean filtered water.
As debris builds up in the AGF filter, a pressure loss will develop across the filter.
From Outlet
The dirtier the filter becomes, the greater the pressure loss. When the pressure Manifold
loss reaches a critical limit, the filter is dirty and in need of a backflush. Backflush
controllers will sense the pressure loss through hydraulic connections and
command a backflush sequence to begin when necessary.
It is recommended to backflush every 2-4 hours regardless of pressure loss.
BACKFLUSH PRESSURE
Filters must have both adequate pressure and water velocity for proper backflush. It is recommended that AGF filters
have a minimum of 30 psi of pressure on the downstream side during backflush.
When the system consists of only two or three filters, the water pressure must be carefully considered. Backflushing
requires that all the water flows through one filter to backflush the other filter. This can change the pressure drop
through the one filter, resulting in inadequate pressure for the other filter - especially when using a pump with a steep
characteristic curve.
For low pressure or low flows, consult an Authorized Netafim Dealer for recommendations. Generally the addition of a
Pressure Sustaining Normally Open Valve downstream of the filter station will increase backflush efficiency.
SYSTEM MAINTENANCE
MONTHLY AND SEASONAL MAINTENANCE
Check the control filter every few weeks and clean the filter element.
Inject Chlorine upstream of the filters during and at the end of the season or as necessary to control algae and bacterial
growth.
At the beginning of the irrigation season, fill the filter with water and add Chlorine. Let stand for 30 minutes. Backflush
for 2 minutes and begin irrigation.
At the end of every irrigation season, add Chlorine to the water in the filter for 30 minutes and allow to set. Backflush for
at least 2 minutes. Drain all the water from the filter, leaving it dry and close the inlet and outlet valves.
The Chlorine injection rate in GPH is:
Strength (10% solution = 10 factor) x GPM x ppm Chlorine x 0.00006 = gallons of Chlorine per hour
Example: 10% solution x 40 GPM x 25 ppm Chlorine x 0.00006 = 0.6 GPH
Shock treatments may require 20 to 50 ppm.
Flush the entire system after the treatment as Chlorine is a dangerous chemical and all application regulations and
safety rules must be observed. Contact a qualified person for further assistance.
Recommended monthly - open upper cover and check sand level. Add media if required.
Check for external damage to the filter. Any damage to the protective coating of the filter must be repaired as soon as
possible.
At the end of the irrigation season, initiate a backflush cycle, at a minimum of 30 psi, to ensure a clean sand bed during
the off season.
NOTE: Use of gravel or any other material besides the recommended sand or silica media as indicated in the Adding
the Sand Media Chart on page 10, voids the warranty and can cause damage to the underdrain and tank
structure. Tanks must be filled with water prior to adding recommended media. Failure to do so could damage the
internal components and void the warranty.
All the filters in Controller output Check that the controller is on and programmed correctly. Attempt to manually
station will not problem actuate the solenoid with the clock. The solenoids should emit a clicking noise
backflush when actuated.
Insufficient Use the manual knob on the base of the solenoid to backflush one tank. Note the
downstream pressure downstream pressure reading. If the pressure falls below 20 psi, it may be
for backflush necessary to throttle the field valves to build up sufficient backflush pressure.
Hydraulic command Check to be sure the isolation valve is in the on position. Remove one of the
system failure hydraulic tubes leading to the solenoids and verify that pressurized water is
available. Inspect the hydraulic command filter for contamination.
Filter station Gauge error Check gauge differential on manifolds against the differential gauge in the controller.
differential If there is a discrepancy, check readings with a new gauge.
remains high after
backflush Insufficient backflush Verify that the downstream pressure during backflush is at least 20 psi. If it is not, it
pressure may be necessary to throttle a valve downstream of the filter station to develop
sufficient backflush pressure.
Insufficient backflush Check the Backflush Restriction Valve setting. Adjust according to the procedures
flow outlined in the Backflush Restriction Valve Adjustments section.
Excessive Open the access cover and inspect the media bed after a backflush. Verify that the
contamination of media sand level is correct and that there is not an excessive amount of debris in the sand.
Verify that the backflush manifold line meets the size requirements outlined in the
Backflush Manifold Assembly section.
Leaking around Pinched gasket Remove couplings and inspect gasket. Apply gasket lube to prevent pinching.
grooved couplings
Torn or cracked gasket Remove torn gasket and replace.
Components out of Remove couplings and gaskets and inspect grooved fittings. Fittings should join
alignment squarely with no major gaps.
Leaking around Debris between gasket Remove gasket and inspect gasket and seat for any debris.
access ports or and seat
top access vent
Torn or cracked gasket Inspect gasket for cracking or other damage - replace if necessary.
Cracked access cover Inspect access cover for cracks or damage - replace if cracked or defective.
Torn or cracked O-ring Remove top access cover and inspect vent O-ring for damage - replace if
necessary.
One or several Controller output Check for correct controller output with multi-tester or switch solenoid wires with
filters will not problem another station to check for output signal.
backflush
Solenoid wiring is Use ohmmeter to verify that wiring is intact. Attempt to manually activate the
defective solenoid with the knob on the base.
On filters with manual Verify that selector valve knob is pointed towards the solenoid.
selector valve - valve
setting incorrect
Solenoids clogged or Open solenoids and inspect internal ports for evidence of clogging.
damaged Open carefully to avoid losing the internal spring-loaded plunger.
6 70620-009000 Pin
27AP28200028 1 16
7 70620-009400 Mushroom (55 per tank)
27AP28200030 2 15
8 70620-009270 Upper Diffuser Complex
27AP22480052 21 34
With mushrooms 35
3 20
9 70620-008850 27AP28200026 End Cup 22
10 70620-009260 27AP28200020 Drum 4
11 70620-009280 27AP22480054 Lower Diffuser Complex
with Mushrooms 19 5
12 70620-008500 27AP28200016 Outlet 7 6 27
13 70620-009500 27AP50050548 Cover Seal 8 11
10
14 70620-008780 27AP28200324 Lower Cover
15 70620-003975 25AP50032235 O-Ring 2-235 14 23
9
16 70620-008820 27AP28200340 Lower Plug 15 10 24
33
17 70620-008600 27AP28200036 Bridge
70620-008700 27AP28200038 Tightening Screw 16 25
18 27
13
19 70620-009100 27AP28200011 Lower Plug Assembly 12 26
20 70620-008800 27AP28200322 Upper Cover
32 3 28
21 70620-009590 27AP28200046 Vacuum Release 17
22 70620-007060 27AP50032310 O-Ring 2-310 1
30 18
23 - 27AP50403830 W 3/8 x 1 1/4 Screw 29
24 - 27AP50760248 Handle 31
42 43 44