3D Trasar Solid Cooling Water Analyzer Panel: Description
3D Trasar Solid Cooling Water Analyzer Panel: Description
3D Trasar Solid Cooling Water Analyzer Panel: Description
Specification SPEC-629
Description
The Nalco 3D TRASAR Solid Cooling Water Analyzer
Panel is the main component of the 3D TRASAR Solid
Cooling Water System.
Analyzes and controls feed of 3D TRASAR Solid
inhibitor product based on configured PPM
(part per million) set point
Analyzes and controls cooling water conductivity
based on configured set point
Analyzes and controls oxidizing biocide feed based
on configured ORP set point or timer
Controls feed of non-oxidizing biocide based on
configured timer
Controls and monitors the 3D TRASAR Solid
inhibitor dispenser
Logs and sends monitored and calculated data to
the Nalco server, website and the Nalco 360 remote
24/7 team of experts
Specification Details
Electrical power 85250 Vac, 50/60 Hz, Max.1560 VA (14.2 A @110 Vac, 6.8 A@230 Vac)
(Controller is supplied with a prewired power cord)
Analog inputs 8, non-isolated, 4...20mA or 010V. For voltage inputs, the input impedance is
240 for mA and 110K for V.
Digital inputs 16, contact or open collector NPN transistor/FET (5mA sink, 24Vdc, signal to ground):
8: e.g. flow switch, remote start/stop (interlock)
4: 0100 Hz, e.g. water meter pulse
4: 01000 Hz, e.g. flow meter
ORP Inputs 2, smart sensor, shield
Conductivity inputs 2, Each input can be temperature compensated (user selectable).
1: Inductive, toroidal, 2 coils, smart sensor, PT1000, range 5002,000,000 S/cm.
1: Contacting, smart sensor, range 05,000 S/cm.
Temperature inputs 6, non-isolated, 4-wire, 1000, platinum RTD (PT1000). Range: -18427C, 0800F.
Control relay outputs 8, SPDT (NO/NC), mechanical, max. 250Vac, max. 12A for all 8 relays combined.
Each relay fused at 4A, powered or contact operation.
Alarm relay outputs 2, SPDT (NO/NC), mechanical, max. 250 Vac, fused at 1.0 A. contact operation.
Analog outputs 8, non-isolated, self-powered, 4-20 mA. (<600 ). For PID control or monitoring of
measurements in DCS.
24Vdc power supply Regulated, max. 2.5A.
Enclosure NEMA 4, IP65, 449C, 40120F, Relative Humidity 0-95% non-condensing,
password protected.
Communications 3x Ethernet ports
1x USB for memory stick.
1x built-in wireless gateway, GSM/GPRS, CDMA, 3G, security via VPN firewall.
3D TRASAR Fluorometer
Multi-channel fluorescence and light monitor
Specification Details
TRASAR #2 and Tagged Range: 13 ppb15 ppm as TRASAR #2 or Tagged Polymer
Polymer measurements (e.g. 1.3 ppm1500 ppm inhibitor if Product Factor is 100)
Accuracy: +/- 5% of reading
Bio-reporter and Range: 030 0ppb
Bio-product measurements Accuracy: +/- 5% of reading
Turbidity measurement Range: Turbidity in Nalco turbidity units are consistent with Nephelometric
Turbidity Units up to 40 NTU; deviates from standard NTU above 40 NTU)
Accuracy: +/- 5% of reading
Cell fouling Range: 0100%
Accuracy: +/- 5% of reading
Calibration Single 2-point calibration for TRASAR, Tagged Polymer, Bio-reporter and
Bio-product
Sample temperature 460C @1.5 bar, 40140F @22 psi
Sample pressure 06.9 bar @35C, 0100 psi @95F
Power and communication Via 3D TRASAR controller (6V and Modbus)
Wetted materials PVC, Quartz, SS
ORP Probe
ORP: Oxidation Reduction Potential
(also known as redox potential)
Voltage measurement between a noble metal and a
reference electrode Indication of the free chlorine
concentration that is removed by dosing bi-sulfite.
Unit of measure: mV (millivolt)
Specification Details
Range pH: pH 014, ORP: 01000 mV
temperature: 0100C, 32212F
Calibration pH: 2-point with pH 7 and 10 or pH 4 and 7 + 1 point inline
ORP: 2-point with 200 mV and 600 mV + 1 point inline
Accuracy pH 0.05, ORP: +/-5% of reading
Sample Pressure 010.3 bar, 01500 psi @ temperature
Sample Temperature 5110C, 40230F @ pressure
Required conductivity 100-10,000 uS/cm
Wetted materials Body: PPS (Ryton), seal: FKM (Viton), sensor: glass
Max. cable length TBD
Conductivity Probe
Type: Inductive, toroidal
Smart sensor: automatic recognition of sensor type,
serial number, first calibration Coil 1 induces an
electrical current in the water. Coil 2 detects induced
current. The current is proportional to the conductivity
of the water. Unit of measure: S/cm (micro Siemens
per cm) contains an internal PT1000 temperature
sensor for temperature compensation.
Specification Details
Range 5002,000,000 S/cm, 0100C, 32212F
Calibration 2-point and 1-point calibration
Accuracy +/- 5% or reading
Sample Pressure Max. 6.9 bar @35C, 100 psi @95F
Sample Temperature 0100C, 32212F @ pressure
Wetted materials Body: PPO-PS blend (Noryl), seal: FKM (Viton synthetic rubber)
Max. cable length TBD
Flow Switch
Type: Reed contact switch
Magnetic float is pushed upwards by sample water flow.
Above a certain flow (fixed), the reed contact output
remains closed. Used for determining if sample water
is representative of system water.
Specification Details
Switching point 0.5 gpm, 113 L/h
Signal output Potential free contact
T-Strainer
Specification Details
Mesh size 20 (0.9 mm)
Pressure 010.3 bar @ 21C, 0150 psi @ 70F
06.9 bar @ 52C, 0100 psi @ 125F
Materials Top: PP, bowl: Nylon, Mesh: SS304
Mesh size 20 (0.9 mm)
To Order Support
Contact your local Nalco Sales Engineer. If you have any questions, please contact your Nalco
representative. In North America, you can contact
the Nalco Global Equipment Solutions Help Desk at
1-800-323-8483.
Plumbing
991-05053773.88 T-Strainer, PP,1, FPT,20 MESH, CLEAR
6000668 Flow Switch, PVC, 3/4, FPT
Material Description
3DT-CWSKIT1-88 3D TRASAR Solids Start Up & Calibration Kit (includes items below)
460-S0940.75 S0940-3D TRASAR
460-S0297.75 Soln 1 L 3000 Micromho Standard
460-S0298.75 Soln 1 L 600 Micromho Standard
460-S0800.75 Soln 1L 10% Sulfuric Acid
500-P2817.88 Tube Brush, Nylon, 5/16 x 2-1/2 x 16
500-P0116.88 Beaker Disp PLS 800 ML
500-P2147.88 Syringe, Plastic ,60 cc, Luer-Lok TIP
General Arrangement Drawing
3D TRASAR, Nalco 360, Ecolab, NALCO and the logos are Trademarks of Ecolab USA Inc.
All other trademarks are the property of their respective owners
2014 Ecolab USA Inc. All Rights Reserved 6-14