Tech Catalog VSD ACS600 Manual EN - 600stdprg - FWmanual
Tech Catalog VSD ACS600 Manual EN - 600stdprg - FWmanual
Tech Catalog VSD ACS600 Manual EN - 600stdprg - FWmanual
Frequency Converters
for Speed and Torque Control of
2.2 to 3000 kW Squirrel Cage Motors
Technical Catalogue
ACS 600 SingleDrive
Frequency Converters
for Speed and Torque Control of
2.2 to 3000 kW Squirrel Cage Motors
Technical Catalogue
Chapter 1 Overview
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
ACS 600 SingleDrive in Brief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Suitable for Any Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
ACS 600 Drives for Specific Purposes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
ACS 600 MotionControl, ACP 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
ACS 600 CraneDrive, ACC 600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Product Type Designations Used in The Catalogue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
DC Magnetizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Automatic Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
DC Hold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Flux Braking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Flux Optimization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Acceleration and Deceleration Ramps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Critical Speeds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Constant Speeds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Speed Controller Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Accurate Speed Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Accurate Torque Control without Speed Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Scalar Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Actual Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Fault History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Programmable Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Programmable Analogue Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Input Signal Source Selections and Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Two Programmable Control Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Reference Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Programmable System Control Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Analogue Input Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Protection Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Programmable Fault Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Preprogrammed Protection Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
Main Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
No Fixed Switching Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
AC Choke . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
Wide Mains Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
Other Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Power Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Automatic Resets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
ACS 600 Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Parameter Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Built-in PID Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
Technical Data
ACS 600 SingleDrive ACS 600 SingleDrive is a new generation frequency converter that
in Brief achieves the ultimate in AC motor control performance. The first AC
drive to utilise Direct Torque Control (DTC), the ACS 600 accurately
controls the speed and torque of any standard squirrel cage motor.
Suitable for Any ACS 600 frequency converters meet the needs of any application -
Application from the simplest to the most critical and highly demanding.
Pumps - centrifugal, positive displacement, dosing
Fans - forced draught, induced draught, centrifugal, axial
Mixers
Conveyors, bottling lines, palletisers and other materials handling
applications
Lifts, elevators, cranes, hoists
Winders - films, paper, wire
Centrifuges
Extruders - melt pumps, pelletisers.
ACS 600 MotionControl, ACS 600 MotionControl provides state-of-the-art solution to a high-
ACP 600 precision control applications, i.e. positioning, synchronising, torque
control and speed control.
ACP 600 frequency converters belong to the ACS 600 product family.
The same advanced motor control and hardware solutions are used.
There are certain differences, however, due to a specific focus of
design:
special application program including Positioning, Synchronising,
Speed Control and Torque Control Application Macros
Advanced I/O Board with integrated incremental encoder interface
add-on board for an absolute encoder
Pulse Encoder Interface Module (NTACP-01) option
For more information, see the Technical Data appendix and ACS 600
Product Catalogue, code: 3BFE 64162021. The options are described
in Chapter 7 Optional Equipment.
ACS 600 CraneDrive, ACS 600 CraneDrive belongs to the ACS 600 product family. The same
ACC 600 advanced motor control and hardware solutions are used.
The ACS 600 CraneDrive is equipped with a special application
program that includes advanced functions for a standard crane system;
torque memory, power optimisation, limit switch supervision,
mechanical brake control, torque proving etc.
The special crane functions, together with the unique Direct Torque
Control (DTC) technology, used in all ACS 600 family members,
guarantee precise control in the most demanding crane applications.
For more information, see the Technical Data appendix and ACS 600
Product Catalogue, code: 3BFE 64162021. The options are described
in Chapter 7 Optional Equipment.
7KH&DWDORJXH
Direct Torque Control Direct Torque Control (DTC) is a unique motor control method for AC
Drives. The inverter switching directly controls the motor core
variables: the flux and the torque.
Mains
Rectifier
Speed controller
+ acceleration compensator Internal torque Torque Control Switch position
reference status signals commands
Torque DC bus
Torque reference
Torque comparator Optimum
controller
reference pulse
Flux selector
PID comparator
aInverter
Speed
reference Flux
Actual torque status ASIC
Flux Actual flux Switch
Flux reference positions
optimization controller
U Adaptive
ON/OFF f
motor model
U
Flux braking T
f
Internal flux
ON/OFF f reference
Actual speed
M
Motor currents DC bus voltage
3~
How Does DTC Differ In DTC, every switching is determined separately based on the values
from PWM Flux Vector of flux and torque, rather than switching in a predetermined pattern as
Drives? in conventional PWM flux vector drives.
Switching based on core motor variables Flux and Switching based on separate control of magnetising
Torque and torque producing components of current
Shaft speed and position typically not required Mechanical speed is essential. Requires shaft speed
and position (either measured or estimated)
Each inverter switching is determined separately Inverter switching based on average references to a
(every 25 m s). PWM modulator. This results in delays in response
and wasted switchings.
Torque Step Rise Time (open loop) is 1 to 5 ms. Torque Step Rise Time
Closed Loop 10 to 20 ms.
Sensorless 100 to 200 ms.
Scalar Control It is also possible to select scalar control as the motor control method.
There are some special cases when scalar control should be selected,
e.g. when running a multimotor application with variable motor
configuration.
For more information on scalar control, see Chapter 6 Standard
Features.
ACx 601 The ACx 601 hardware is arranged inside a wall-mountable metal
frame. The ACx 601 series comprises six different frames (R2 to R7).
The degree of protection of the frame housing is IP 22. IP 54 versions
are available as an option, except R7. R7 is available as IP 54 in the
ACx 607 series only.
The front section of the frame contains the electronics and the power
and control cable terminals. The rear section forms a cooling channel.
Two-section construction allows the unit to be installed protruding
through a wall, placing the rear section in a cooling air duct (frames
R2 to R6). In standard installations the converter is mounted directly
onto the wall. The upward cooling air flow is provided by a fan or fans in
the bottom part of the frame.
There is room for the Braking Chopper and for one Option Module in
frames R4 to R7. Frames R2 and R3 need to have these devices
installed outside the converter housing. For information on the optional
devices available, see Chapter 7 Optional Equipment.
For the degree of protection, materials etc. see the Technical Data
appendix.
ACS 600
ENTER
REM
Figure 3-1 The ACx 601. The dimensions and weights are shown in
Technical Data appendix.
ACx = ACS/ACC/ACP
Chapter 3 Hardware Description
ACx 604 / ACx 607 / The ACx 604 is a converter module which is installed into a cabinet and
ACS 617 / ACS 677 equipped with accessories by the user. The ACx 607 is housed inside a
Drives-MNS cabinet.
ACx 604 The ACx 604 hardware is arranged inside a metal frame. There are
three frame sizes: R7, R8 and R9. The ACx 604 frame is to be fitted in
a cabinet by the user. The degree of protection is IP 22 (ACx 604-0100-
3, -0120-3, -0120-5, -0140-5, -0100-6 and -0120-6) or IP 00 (ACx
604-0140-3 to -0320-3 and -0170-5 to -0400-5 and -0140-6 to -400-6).
The Control Panel mounting platform, the Control Panel and the other
optional devices are supplied separately. Most optional devices are to
be installed outside the unit. For more information on the Control Panel,
Control Panel Mounting Platform and the other optional add-on kits,
see Chapter 7 Optional Equipment.
$&[ $&6 The cabinet of ACx 607$&6 $&6 is equipped with a
$&6 hinged front door(s) that holds the mains switch, the Control Panel
mounting platform, and some optional devices. Cooling air intake and
exhaust vents are covered with grates to keep out unwanted objects.
As standard, the cabling is through the bottom of the unit. The mains
and motor cable can also be lead in through the roof of the cabinet.
See Chapter 7 Optional Equipment for more information.
There is room inside the cabinet to allow connections and optional
devices. The cabinet can be ordered as an extended version if more
space is required.
ACx 607 types up to -0610-3, -0760-5 and -0760-6 use the ACx 604
converter modules/frames.
ACS/ACC 607 types -0760-3, -0930-5, -0900-6 or above, and ACS/
ACC 617 and ACS/ACC 677 use the supply units and inverter
modules/frames of the ACS 600 MultiDrive.
For the degree of protection, materials etc. see the Technical Data
appendix.
ACx = ACS/ACC/ACP
Chapter 3 Hardware Description
ACS 600
V2
U2
W2
V2
UDC+
UDC-
W2
UDC+
UDC- PE
PE
Figure 3-2 The ACx 604 and the ACx 607 (up to -0610-3, -0760-5 and -0760-6). The dimensions and
weights are given in the Technical Data appendix.
ACx = ACS/ACC/ACP
Chapter 3 Hardware Description
(inverters, motor
connections)
Drive Unit
(input bridge)
Supply Unit
DC Choke
Incoming Unit
connections)
(mains
ACS 607-0930-3, -1120-3
ACS 607-1090-5, -1380-5
Control Unit
connections)
Auxiliary
(control
Figure 3-3 The ACS/ACC 607 (-0760-3, -0930-5, -0900-6 or above). The dimensions and weights are
given in the Technical Data appendix.
ACx = ACS/ACC/ACP
Chapter 4 User Interfaces
Overview The ACS 600 can be controlled from several control locations:
The detachable Control Panel which can be mounted on the
ACS 600 enclosure or a remote control desk.
External control devices that connect to the analogue and digital I/O
terminals or Standard Modbus Link (serial RS 485 connection) on
the Standard I/O Board, NIOC.
External control devices that connect to the ACS 600 option
modules (Analogue and Digital I/O Extension Modules and Fieldbus
Adapter Modules).
PC that connects via a PC adapter to the Application and Motor
Control Board, NAMC.
Control Panel The Control Panel is the user interface for monitoring, adjusting
parameters and controlling the ACS 600 operation.
Standard I/O See the Technical Data appendix, subsection Standard I/O.
Standard ModBus Link See the Technical Data appendix, subsection Standard I/O.
$&67HFKQLFDO&DWDORJXH 5-1
Chapter 5 Parameters and Application Macros
The parameters in the ACS 600 are organised into functional groups,
allowing the user to step through the groups, rather than having to step
through all the parameters one by one. This makes the right parameter
much easier and quicker to find.
I/O Settings in Macros Preprogrammed use of digital inputs (DI), relay outputs (RO), analogue
inputs (AI) and analogue outputs (AO) is shown below.
Factory Macro Input Signals Output Signals
DI1,2: Start, Stop, Direction AO1: Speed
AI1: Speed reference AO2: Current
DI5,6: Constant speed selection (3) RO1: Ready
DI4: Accel/Decel ramp selection (2) RO2: Running
RO3: Fault (-1)
5-2 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
This Chapter describes features of the ACS 600 equipped with the
Standard Application Program.
Overview Based on the Direct Torque Control motor control technology, the
ACS 600 offers highly advanced features as standard. As a default
setting the ACS 600 operates in DTC. There are some special cases
when scalar control should be selected, for example when running a
multimotor application with variable motor configuration.
The following features are available in DTC mode. The standard
features that are not available in the scalar control mode, and the
features that are only available in the scalar control mode, are listed in
section Scalar Control later in this chapter.
$&67HFKQLFDO&DWDORJXH 6-1
Chapter 6 Standard Features
Power Loss If the incoming supply voltage is cut off the ACS 600 will continue to
Ride-through operate by utilising the kinetic energy of the rotating motor. The
ACS 600 will be fully operational as long as the motor rotates and
generates energy to the ACS 600.
Umains
TM fout U DC
(Nm) (Hz) (V d.c.) UDC
160 80 520
120 60 390
fout
80 40 260
TM
40 20 130
t(s)
1.6 4.8 8 11.2 14.4
UDC = ACS 600 intermediate circuit voltage, fout = ACS 600 output frequency
TM = Motor torque
Figure 6-1 Loss of supply voltage at nominal load (fout = 40 Hz). The
intermediate circuit DC voltage drops to the minimum limit. The
controller keeps the voltage steady as long as the mains is switched off.
The ACS 600 runs the motor in generator mode. The motor speed falls
but the drive is fully operational as long as the motor has enough kinetic
energy.
Controlled Torque at The ACS 600 can control motor torque at zero speed without any pulse
Zero Speed encoder or tachogenerator feedback. E.g. a controlled change of
rotation direction can be performed. The feature is essential in several
applications including elevators and lifts. However, if long-term
operation at zero speed is required, a pulse encoder is used.
Automatic Start The Automatic Start feature of the ACS 600 outperforms the flying start
and ramp start features normally found in frequency converters.
6-2 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
Because ACS 600 can detect the state of the motor within a few
milliseconds, starting is immediate under all conditions. There is no
restart delay. The starting of turbining pumps or windmilling fans is
easy, for example.
0RWRU
DC Hold By activating the motor DC Hold 6SHHG
W
normal ACS 600 operation
resumes.
Flux Braking The ACS 600 can provide greater deceleration by raising the level of
magnetisation in the motor. By increasing the motor flux, the energy
generated by the motor during braking can be converted to motor
thermal energy. The feature is useful in motor power range below
15 kW.
0 RWRU 7%U
6SHHG 7 (%)
1
7 %U
%UDNLQJ7RUTXH
1R)OX[%UDNLQJ
7 1
1P
)OX[ %UDNLQJ
1R)OX[ %UDNLQJ
)OX[%UDNLQJ
WV I+]
+=+]
1
No Flux Braking
80
2
40 3
4
5
0 f (Hz)
5 10 20 30 40 50
The ACS 600 monitors the motor status continuously, also during Flux
Braking. Therefore, Flux Braking can be used both for stopping the
motor and for changing from one speed to another. The latter is not
possible with DC Injection Braking, which is offered in most frequency
converters. The other benefits of Flux Braking compared to DC
Injection Braking are:
The braking starts immediately after the Stop command is given.
In DC Injection Braking, there is typically a 500 ms delay after the
Stop command before braking can be started. The delay is essential
because DC Injection is possible only after the motor flux is
sufficiently reduced.
The cooling of the motor is more efficient.
The stator current of the motor increases during Flux Braking. With
DC Injection Braking the rotor current increases. The stator cools
much more efficiently than the rotor.
Flux Optimization Flux Optimization of the ACS 600 reduces the total energy
consumption and motor noise level when the drive operates below the
nominal load. The total efficiency (motor and the drive) can be
improved by 1 % to 10 %, depending on the load torque and speed.
Acceleration and ACS 600 provides two user-selectable acceleration and deceleration
Deceleration Ramps ramps. It is possible to adjust the acceleration/deceleration times
(0 to 1800 s) and the ramp shape. Switching between the two ramps
can be controlled via a digital input.
The available ramp shape alternatives are linear and S curve.
Linear: Suitable for drives requiring 0RWRU
VSHHG
Critical Speeds There is a Critical Speeds function available for applications where it is
necessary to avoid certain motor speeds or speed bands due to e.g.
mechanical resonance problems. The ACS 600 makes it possible to set
up 3 different speeds or speed bands which will be avoided during
operation.
6-4 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
deceleration ramp.
Constant Speeds In the ACS 600 it is possible to predefine 15 constant speeds. Constant
speeds are selected with digital inputs. Constant speed activation
overrides the external speed reference.
Speed Controller Tuning During the motor Identification (ID) Run the ACS 600 speed controller
is automatically tuned. However, it is possible to manually adjust the
controller gain, integration time and derivation time, or let the ACS 600
perform a separate speed controller Autotune Run. In Autotune Run,
the motor is driven through a series of movements and the speed
controller is tuned based on the load and inertia of the motor and the
machine.
n
nN %
A B C D
Accurate Speed Control The static speed control error is typically + 0.1% to + 0.5 % of motor
nominal speed, which satisfies most industrial applications. If even
more precise speed regulation is required, a pulse encoder can be
6-6 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
Table 6-2 Typical performance figures for torque control, when Direct
Torque Control is used.
Scalar Control With the ACS 600 it is possible to select Scalar Control as the motor
control method. In the Scalar Control Mode, the drive is controlled with
a frequency reference. The outstanding performance of the default
motor control method, Direct Torque Control, is not achieved in Scalar
Control.
It is recommended to activate the Scalar Control mode in certain
special applications:
In multimotor drives 1) if the load is not equally shared between the
motors, 2) if the motors are of different sizes, or 3) if the motors are
going to be changed after the motor identification.
If the nominal current of the motor is less than 1/6 of the nominal
output current of the ACS 600.
If the ACS 600 is used without a motor connected (for test purposes,
for example).
If the ACS 600 is used in a step-up transformer application.
(ACS 600 is running a medium voltage motor via a step-up
transformer.)
In the Scalar Control Mode, the following ACS 600 standard features
are not available: Motor ID Run, Automatic Start, Torque Control, DC
Magnetizing, Flux Braking, Flux Optimization, DC Hold, Underload
Function, Motor Phase Loss Function, Speed Limits, Torque Limits,
Speed Controller Tuning, Stall Function.
The following features are available only in Scalar Control: Limits for
Frequency (programmable), IR Compensation.
IR Compensation When IR Compensation is Motor
Voltage
activated, the ACS 600 gives an
extra voltage boost to the motor at IR Compensation
Diagnostics
Fault History The Fault History contains information on 64 most recent events (faults
or warnings) detected by the ACS 600 (16 remains in the memory over
a power switch off). The events are displayed in words along with the
total power-on time of the ACS 600.
Programmable The three programmable relay outputs can be used as potential free
Relay Outputs changeover contacts. With parameter setting it is possible to choose
which information to indicate with the RO: ready, running, fault,
warning, motor stall, motor temperature, ACS 600 temperature,
reversed selected, external control selected, preset speed limits (2
pcs), intermediate circuit voltage limits, preset motor current limit,
reference limits (2 pcs), loss of reference signal, ACS 600 started,
motor operating at reference speed, process PID controller actual
value limits (low, high) etc. It is also possible to control the relay outputs
through a communication (e.g. fieldbus adapter) module.
Programmable ACS 600 offers two programmable current outputs. Analogue output
Analogue Outputs signals can be inverted and filtered. The minimum level can be
adjusted to 0 mA or to 4 mA.
Depending on parameter selection, the analogue output signals can be
proportional to motor speed, process speed (scaled motor speed),
output frequency, output current, motor torque, motor power, DC bus
voltage, output voltage, application block output (the process PID
controller output), the active reference, or reference deviation
(difference between the reference and the actual value of the process
PID controller) etc.
Also, the output can be proportional to the process PID controller
actual value of the ACS 600. The process PID controller actual values
can be scaled, inverted and filtered.
It is also possible to control the analogue outputs through a
communication (e.g. fieldbus adapter) module.
6-8 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
Two Programmable The ACS 600 (with no optional devices) can receive Start/Stop/
Control Locations Direction commands and reference from the control panel, through
digital inputs and analogue inputs or through a serial RS 485 port
(Standard Modbus Link).
It is possible to predefine two separate External Control Locations
(EXT1 and EXT2) for both the Start/Stop/Direction commands and the
reference signal. The active External Control Location can be changed
with the control panel, through a digital input or through the Standard
Modbus Link.
The control panel always overrides the other control signal sources
when used in local mode.
Reference Signal The ACS 600 can accept a variety of speed references in addition to
Processing the conventional analogue input signal and control panel signals.
The ACS 600 reference can be given with two digital inputs: One
digital input increases the speed, the other decreases it.
ACS 600 accepts a joystick Speed
analogue speed reference. This
feature allows both the speed
and direction to be controlled 0
with a single analogue input.
The minimum signal is full speed Ref
reversed and the maximum 0 5 10 (VDC)
signal is full speed forward.
The ACS 600 can form a reference out of two analogue input signals
by using mathematical functions: Addition, Subtraction,
Multiplication, Minimum selection, and Maximum selection.
The ACS 600 can form a reference out of an analogue input signal
and a signal received through a serial communication interface by
using mathematical functions: Addition and Multiplication.
It is possible to scale the external reference so that the signal minimum
and maximum values correspond to a speed other than the minimum
and maximum speed limits.
Analogue Input The ACS 600 has three programmable analogue inputs: one voltage
Processing input and two current inputs. Each of these analogue inputs can be
processed by adjusting the signal min/max levels, the filtering time
constant, and the signal inversion selection.
Min/Max Setting The minimum setting of 0V/0mA, 2V/4mA or the input tuning can be
selected. The tuning allows the ACS 600 to read the value of the
applied minimum signal.
The maximum setting of 10V/20 mA or the input tuning can be
selected. The tuning allows the ACS 600 to read the value of the
applied maximum signal.
Readable range in tuning is 0 mA / 0 V to 20 mA / 10 V.
Filtering The analogue input signal filtering time constant is user-adjustable
from 0.01 to 10 s.
AI
(%) Unfiltered Signal
100
63
Filtered Signal
t
Filter time AI
Figure 6-3 Analogue input filtering time constant.
Inversion With inversion activated, the minimum level of the analogue input signal
corresponds to the maximum reference and the maximum analogue
input signal corresponds to the minimum reference.
6-10 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
Protection Functions The ACS 600 offers several Programmable Fault Functions and other
non-user adjustable Preprogrammed Protection Functions.
3) Conditions 1 and 2 have been on longer than the period set by the
user (Stall Time Limit).
Underload Function Loss of motor load may indicate a process malfunction. ACS 600
provides an Underload Function to protect the machinery and process
in such a serious fault condition. The supervision limits: Underload
Curve and Underload Time can be chosen as well as the drive
operation in the underload condition (warning indication / fault
indication & stop the drive / no reaction).
6-12 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
Motor Phase The Phase Loss function monitors the status of the motor cable
Loss Function connection. The function is useful especially during the motor start: the
ACS 600 detects if any of the motor phases has not been connected
and refuses to start. The Phase Loss function also supervises the
motor connection status during normal operation.
The user can define the drive operation during motor phase loss. The
alternatives are either a fault indication and Stop, or no reaction.
Earth Fault Protection The Earth Fault protection detects earth faults in the motor, the motor
cable or the inverter.
In ACS 601, ACS 604, and the 6-pulse versions of ACS 607 up to
-0610-3, -0760-5 and -0760-6, the Earth Fault protection is based on
earth leakage current measurement with a summation current
transformer at the input of the converter. Depending on the users
selection, the Earth Fault function stops the drive and gives a fault
indication, or the drive continues operation, ignoring the detected earth
fault.
An earth fault in the mains does not activate the protection.
In earthed mains, the protection activates in 200 ms.
In floating mains, the mains capacitance should be 1 mF or more.
The capacitive currents due to screened copper motor cables up to
300 metres do not activate the protection.
In the12-pulse versions, i.e. ACS 627-0400-3 to -0610-3, -0490-5 to
-0760-5 and -0490-6 to -0760-5, the protection is based on the voltage
measurement of the supply neutral point. For more information on the
protection principle see Chapter 7 Optional Equipment.
For ACS 6x7-0760-3, -0930-5, -0900-6 or above the Earth Fault
protection is an optional feature. See Chapter 7 Optional Equipment.
Communication Fault The Communication Fault Function supervises the communication
Function between ACS 600 and an external control device (e.g. a fieldbus
adapter module).
The user can define the drive operation during communication loss,
and set the time delay for the function. The user can also define the
fault states for the ACS 600 relay or analogue outputs that are
YROWDJHLQWKHLQWHUPHGLDWHFLUFXLWFRUUHVSRQGLQJWRWKHPDLQVYROWDJH
WULSOHYHOLV9GFIRU9XQLWV9GFIRU9XQLWVDQG
9GFIRU9XQLWV
LQWHUPHGLDWHFLUFXLWFRUUHVSRQGLQJWRWKHPDLQVYROWDJHWULSOHYHOLV
ACS 600 ACS 600 supervises the inverter module temperature. If inverter
Temperature module temperature exceeds 115 C, a warning is given. Temperature
trip level is 125 C.
Short Circuit There are separate protection circuits for supervising the motor cable
and the inverter short circuits. If a short circuit occurs, the drive will not
start and a fault indication is given.
Input Phase Loss Input Phase Loss protection circuits supervise the mains cable
connection status by detecting intermediate circuit ripple. If a phase is
lost, the ripple increases. The drive is stopped and a fault indication is
given if ripple exceeds 13 %.
Note: The protection is designed by other means in the:
6- and 12-pulse versions of ACS 607-0400-3 to -0610-3, -0490-5 to
-0760-5, and -0490-6 to -0760-6
12-pulse versions of ACS 607-0760-3, -0930-5, -0900-6 or above.
Ambient Temperature The drive will not start if the ambient temperature is below -5 to
0 C or above 73 to 82 C (the exact limits vary within the given ranges
depending on ACS 600 type).
Overfrequency If the ACS 600 output frequency exceeds the preset level, the drive is
stopped and a fault indication is given. The preset level is 50 Hz over
the operating range absolute maximum speed limit (Direct Torque
Control mode active) or frequency limit (Scalar Control active). The
operating range limits are set by Parameters 20.1 and 20.2 (DTC mode
active) or 20.7 and 20.8 (Scalar control active).
Internal Fault on the I/O If the Application and Motor Control Board (NAMC) cannot
Control Board communicate with the I/O Control Board (NIOC) or the I/O extension
modules (Digital I/O Extension Modules or Analogue I/O Extension
6-14 $&67HFKQLFDO&DWDORJXH
Chapter 6 Standard Features
Module) connected to the I/O Extension Link, the drive is stopped and
a fault indication is given.
Internal Fault If the ACS 600 detects an internal fault the drive is stopped and a fault
indication is given.
User Macro The customer can create two own user macros and save them into the
permanent memory of the ACS 600. The macro can be loaded simply
by parameter selection. The User Macro protection function gives a
fault indication if an attempt is made to restore a nonexisting user
macro.
Main Circuit
No Fixed Switching ACS 600 has no fixed switching frequency. As a consequence, there is
Frequency no high-pitch audible whine that is found in motors driven by a PWM
technology frequency converter.
The average switching frequency is 2 or 3 kHz. The low average
switching frequency provides higher efficiency because of lower
switching losses.
AC Choke The AC choke is employed for harmonic current reduction, i.e. line
current waveform improvement purposes. This reduces filter capacitor
ripple current and extends capacitor life. The choke is placed on the AC
side of the rectifier bridge in order to protect the rectifier
semiconductors against power line transients. The choke also
attenuates frequency converter electromagnetic emissions.
In large units (ACS 607-0760-3, -0930-5, -0900-6 or above) there is a
DC choke. The choke is placed on the DC side of the input bridge.
Wide Mains One of the unique features of the ACS 600 is that it is capable of
Voltage Range utilizing a wide range of supply voltages.
The input voltage rating of the 500 V a.c. unit ranges from 380 V a.c to
500 V a.c. The 380 to 440 V a.c. mains voltage can be used with minor
adjustments. (In ACS 604 and ACS 607 types the voltage ratio of the
internal transformers should be adjusted.)
The reduced output capacity of the 500 V a.c unit with 380 to 460 V a.c.
mains connection should be taken into account.
Other Features
Limits The ACS 600 offers adjustable limits for speed, current (max.), torque
(max.) and DC voltage.
Power Limit The maximum allowed motor power is 1.5 Phd. If the limit is exceeded,
the motor torque is automatically restricted. The function protects the
input bridge of the ACS 600 against overload.
Automatic Resets The ACS 600 can automatically reset itself after Overcurrent,
Overvoltage, Undervoltage and AI<Min faults. The Automatic Resets
must be activated by the user.
Supervision Supervisions are a unique feature of the ACS 600 which allows the
drive to monitor certain user selectable variables. Each limit can be
defined as low or high.
The user may set two speed limits, one current limit, two torque limits,
two reference limits and two actual value limits. The indication of the
active limit will appear on the control panel display, and can also be
supervised through the relay outputs.
ACS 600 Information The ACS 600 software versions and test date can be displayed.
Parameter Lock The user can prevent unwanted parameter adjustment by activating the
Parameter Lock.
Built-in PID Controller There is a built-in process PID Controller in the ACS 600. The
controller can be used to control process variables such as pressure,
flow or fluid level.
Instead of applying a speed
reference to the ACS 600, a ACS 600
E NT E R
R EM
Level
feedback) is brought back to the Trans-
ducer
ACS 600 through one of the
analogue inputs. Actual Value
6-16 $&67HFKQLFDO&DWDORJXH
Chapter 7 Optional Equipment
Applicability Labels In this chapter, the following labels are used to indicate applicability:
ACS (ACS 600 with the Standard Application Program)
ACP (ACS 600 MotionControl)
ACC (ACS 600 CraneDrive)
ACx (any of the above).
The document Ordering Information (3AFY 58977985) specifies the
availability of options for each frequency converter type and size.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
I/O Options This section includes I/O extensions, pulse encoder interfaces, the
Panel Bus interface, fieldbus adapters and related options. All of the I/O
options can be ordered as separate add-on kits; most can also be
ordered as factory-installed (see text at each option).
Housing The I/O options listed in this section mainly use the IP20 plastic
housings illustrated below. (The housing type of each option is
indicated in the text at their individual descriptions.) The modules can
be mounted onto a standard EN 50022/DIN rail without tools.
10* 10*
All dimensions in millimetres
*Free space
for cooling
10* 10*
*Free space
for cooling
Module Placement ACx 601 frame R4 to R7 units can accommodate one module of
housing type 1 or 2, while frame R2 and R3 units (ACx 601-0005-3 to
-0016-3; ACx 601-0006-5 to -0020-5; ACx 601-0009-6 to -0020-6)
require external mounting. ACx 607 cabinets can accommodate six
modules as well as a power supply module.
Module Power Supply The ACx 600 Standard I/O Board (NIOC) provides a 24 V d.c., 250 mA
power supply. This is usually sufficient for at least one module.
Additional modules require an external 24 V d.c. power supply. A
suitable 3 A rail-mountable power supply (NPSM-02) is available.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Analogue I/O Extension The Analogue I/O Extension Module offers two current 0(4) to 20 mA
Module NAIO-03 or voltage 0(2) to 10 V inputs and two current 0(4) to 20 mA outputs.
(ACS) The Module is connected to a high speed (4 Mbit/s) fibre optic I/O link
on the ACS 600. The NAIO module provides:
bipolar inputs, unipolar outputs
better A/D and D/A decoding accuracy: 12-bit (unipolar) or 11-bit
(+ sign bit) (bipolar) signal resolution
distributed I/O connections through the module
galvanic isolation thanks to the fibre optic connection.
The standard application program supports one NAIO module. The
NAIO module inputs replace the standard analogue inputs AI2 and AI3;
the NAIO module outputs add to the standard analogue outputs.
Front view
Screw terminal block
for power supply connection
NAIO-03 SHF SHF SHF SHF AO2- AO2+ AO1- AO2+
X2
The module requires 24 V d.c. power (160 mA), which can be supplied
by the ACS 600 Standard I/O Board.
Digital I/O Extension The NDIO-02 Digital I/O Extension Module provides two digital inputs
Module NDIO-02 (24 to 250 V d.c. or 110 to 230 V a.c.) and two relay outputs
(ACS) (8 A/24 V d.c., 0.4 A/120 V d.c., 2000 VA/250 V a.c.). The inputs are
galvanically isolated from each other and from the power supply.
The NDIO module is connected to a high speed (4 Mbit/s) fibre optic
I/O link on the ACS 600. The Standard Application Program supports
maximum three NDIO modules. The inputs of the first NDIO module
replace standard digital inputs DI1 and DI2; the inputs of the second
NDIO replace DI3 and DI4; the inputs of the third NDIO replace DI5
and DI6.
The relay outputs of each NDIO module increase the total number of
the relay outputs available. The information which the module outputs
indicate is preprogrammed and not user-adjustable. The outputs of the
first NDIO module indicate the drive states READY and RUNNING. The
outputs of the second NDIO indicate the drive states FAULT and
WARNING. The outputs of the third NDIO indicate the drive states REF
2 SEL (Reference 2 selected) and AT SPEED (Actual value has
reached Reference value).
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Front view
Screw terminal block
for the relay output connection
NDIO-02 R2NO R2CM R2NC R1NO RICM R1NC
X2
The NDIO requires 24 V d.c. power (50 mA), which can be supplied by
the ACS 600 Standard I/O (NIOC) Board.
Pulse Encoder The NTAC-01 and NTAC-02 Pulse Encoder Interface Modules offer an
Interface Module interface for an incremental pulse encoder connection. By measuring
NTAC-01/02 the motor actual speed with a pulse encoder, speed control accuracy
(ACS/ACC) can be improved. See the speed control performance figures in
Chapter 6 Standard Features.
The NTAC-01 is compatible with Standard Application Program
versions 2.7 to 3.x, and the Crane Drive Application Program versions
up to 3.x. The NTAC-02 is compatible with the Standard and Crane
Application Programs, version 5.0 or later.
To achieve accurate speed control, special attention should be paid to
the pulse encoder resolution/signal accuracy. These are the
requirements for the encoder:
Supply voltage 12 V d.c. (15 V d.c. for NTAC-02) or 24 V d.c.
(supplied by the module)
Available signal channels: 1/A, 2/B, 0/Z/N; for differential connection
also 1/A, 2/B, 0/Z/N
90 (electrical) phase shift between channels 1 and 2
Minimum recommended output rate: 1024 pulses per revolution
Recommended output sinking/sourcing capability: 40 mA
Maximum signal frequency 100 kHz.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Front view
Screw terminal block
for the power supply/source
NTAC-01/02
+24V 0V 24 12 24/12 +V -V connections
X2
RXD
ENCODER
INTERFACE
RXD = Receiver
TXD = Transmitter
X1
A+ A- B+ B- Z+ Z- SH PE
170
Motor Speed
160 /rpm
Encoder Pulse Number: 1024 ppr 0 300 600 900 1200 1500 1800 2100 2400 2700 3000
Encoder Pulse Number: 2048 ppr 0 150 300 450 600 750 900 1050 1200 1350 1500
Encoder Pulse Number: 512 ppr 0 600 1200 1800 2400 3000 3600 4200 4800 5400 6000
Figure 7-1 The current consumption for four different encoder cable
lengths. The chart is based on a measurement with a 1024 ppr pulse
encoder with differential outputs coupled to a 1500 rpm motor shaft.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Double Pulse Encoder The NTACP-01 Double Pulse Encoder Interface Module (for the
Interface Module ACP 600) offers two incremental encoder inputs, one encoder output,
NTACP-01 four digital inputs and two digital outputs.
(ACP)
Either encoder input can be relayed to the encoder output, which can
then be used as a reference source for a follower drive, or as feedback
for a higher-level control system.
Typically, the first encoder input is used with a motor encoder, the
second with a master encoder for synchronisation.
The general encoder requirements are as follows:
Supply voltage 5 V d.c. (supply cable resistance compensation
available)
Available signal channels: 1/A, 2/B, 0/Z/N, 1/A, 2/B, 0/Z/N
90 (electrical) phase shift between channels 1 and 2
Maximum signal frequency 200 kHz.
Front view
Terminal block for the digital inputs/outputs
and power supply connections
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Bus Connection The NBCI-02 is used to connect a drive to a panel bus, which is
Interface Module controlled by a CDP 312 Control Panel or a Modbus controller (PLC or
NBCI-02 PC). PC connection usually requires an RS-232/485 converter,
available as NPCU-01.
The panel bus is a serial communication bus that uses the RS-485
physical interface. The panel bus employs the Modbus protocol at a
transfer rate of 9600 bit/s (max.). Through the use of the panel bus, it is
possible to
install the Control Panel (or a PC with an RS-232/485 converter) at
a distance of up to 1200 metres from the drive(s)
control, supervise and program any drive on the panel bus at a time
Note: This function is not supported by the ACC 600.
Front view
1%&,
%86&211(&7 ,21
,17 (5)$&(
1 2 3 4
Screw Terminal Blocks
for Bus and Power Supply
5 6 7 8
Connection
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
CDP CDP
24 V d.c. Supply
~ PC
The NBCI-02 requires 24 V d.c. power (20 mA). All modules on the
panel bus are powered by an external supply in order to retain galvanic
isolation between the panel bus and the drives.
RS-232 RS-485
PC CONNECTION UNIT
RS-485
NPCU-01
(COM) connector of
port of PC drive
Flat oval
telecomms cable
250 mm (max. 3 m)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Fieldbus Adapter There are several fieldbus adapter modules available for the ACx 600,
Modules Nxxx-0x including:
NAFA-01 Advant Fieldbus AF100 Adapter kit
NBAA-01 Building Automation Adapter Module
NCAN-02 CANopen Adapter Module
NCSA-01 CS 31 Adapter Module
NDNA-02 DeviceNet Adapter Module
NIBA-01 InterBus-S Adapter Module
NLON-01 LONWORKS Adapter Module
NMBA-01 Modbus Adapter Module
NMBP-01 Modbus Plus Adapter Module
NPBA-02 PROFIBUS Adapter Module.
The fieldbus cable connects to the terminal block(s) on the adapter
module. The adapter communicates with the ACx 600 via a fast
(4 Mbit/s) half duplex fibre optic link. The fieldbus adapter modules
require a 24 V d.c. power supply. See the entry for NPSM-02 below for
options.
The table below shows the housing type, weight and current
consumption of the fieldbus adapters.
Weight Current
Module Type Housing
[kg] (Gross) Consumption [mA]
Power Supply Module If the total current consumption of optional modules exceeds 250 mA
NPSM-02 (the maximum output of the ACx 600 Standard I/O Board), an external
24 V d.c. power supply is required. For that purpose, a DIN/EN rail-
mountable Power Supply Module (NPSM-02; 230 V a.c./+24 V d.c.,
3 A; degree of protection IP 20) is available.
The power supply can be ordered as an add-on kit. For ACx 607, the
power supply is automatically added if required by the total current
consumption of 24 V d.c. optional equipment.
The dimensions of the NPSM-02 are (H x W x D): 132 x 75 x 71 mm,
weight 0.6 kg.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
DDCS Communication The NDCO-xx DDCS Communication Options are add-on boards for
Options NDCO-01/02/03 the NAMC-11 Application and Motor Control Board. The NAMC-11 is
(ACS) used in ACS 600 frequency converters with the Standard Application
Program, manufactured after 5 October 1998.
The NDCO boards include the fibre optic connectors for DDCS
channels CH0, CH2 and CH3. (These channels are already present on
the NAMC-03 board, used on all ACS 600 units manufactured before
the above-mentioned date.)
The NAMC-11 requires the installation of the NDCO for use with
devices that connect to DDCS channels CH0, CH2 and CH3, e.g.
fieldbus adapters, NTAC-02 Pulse Encoder Interface Module and the
DriveWindow PC program.
The difference between NDCO-01, NDCO-02 and NDCO-03 is in the
optical components of the DDCS channels as indicated below.
NAMC-03
5 MBd 5 MBd 5 MBd 5 MBd
(ACS up to 4 Oct 1998/ACC/ACP)
NAMC-11
5 MBd
(ACS from 5 Oct 1998)
The optical components at each end of a fibre optic link must be of the
same type for the light intensity and receiver sensitivity levels to match.
10 MBd optical components enable the use of lower-attenuation
cables, and thus longer distances.
ACS 604 and ACS 607 frequency converters are always fitted with an
NDCO-03 at the factory. ACS 601 units ordered with a fieldbus adapter,
a pulse encoder interface module, or the Master/Follower Application
Macro are automatically fitted with an NDCO-03 board.
The NDCO kits are also available separately, including coated versions
designated NDCO-0xC.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Pump and Fan Control An ACS 600 equipped with the Pump and Fan Control (PFC)
(ACS) Application Macro can operate a pump/fan station with one to four
parallel pumps/fans. The principle is as follows:
Input Power The motor of pump no. 1 is connected to the ACS 600. The capacity
ACS 600
Process Act. Value
PI
~
~ of the pump is controlled by varying the motor speed.
Process Ref. Value
DI4 (Interlock 3) The motors of pumps nos. 2 and 3 are connected direct-on-line.
DI3 (Interlock 2)
DI2 (Interlock 1) ~ These pumps can be switched on and off by the ACS 600 whenever
RO3 RO2 RO1
Pump 1
necessary.
On/Off Pump 1
Regulated speed
M
The process reference and actual value are fed to the PI controller
3~
Pump 2
On/Off
~
included in the PFC macro. The PI controller adjusts the speed of
Pump 2
Constant speed
the first pump such that the process actual value follows the
Pump 3
M
3~ reference. When the speed exceeds the limit set by the user, the
On/Off
~ macro automatically starts the second pump. If even more capacity
Pump 3
+24 V d.c.
Constant speed
M
is required, the third pump is also started.
3~
Spinning Control The Spinning Control application program is designed for running
(ACS) spinning bobbins in ring frame textile machines. To achieve the best
possible form for the doff, the drive follows a pre-set spinning sequence
that can include 12 speed/time periods. These periods can also be
offset, facilitating change of material. Yarn breakage is prevented by
the wobbulation function, which adjusts the speed of the bobbin on the
grounds of the ring rail position and the doff build-up stage.
For further information, see the Spinning Control Application
Software brochure, code: 3BFE 64018965.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
The customer can tailor DriveSupport to meet the needs of his specific
process by adding his own graphics, user language, more detailed
instructions, spare part numbers and contact information.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Six-pulse Diode Supply A six-pulse diode supply is standard in ACx 600. The diode bridge
(ACx 60_) feeds power in one direction only. No regeneration is possible.
ACx 601, ACx 604, ACx 607 R8 to 2R9 ACx 607 R11i to 4R11i
Six-pulse Inverter
Six-pulse Inverter
diode-thyris-
diode bridge
tor bridge*
0DLQV M
3~
0DLQV M
3~
3 3
Twelve-pulse Diode The twelve-pulse diode supply is available for the cabinet assemblys in
Supply (ACx 627) range 400 to 3600 kVA (ACx 627 types). The option includes two six-
pulse rectifier bridges connected in parallel.
Total harmonics distortion can be remarkably reduced by using a
twelve-pulse rectifier, which eliminates the fifth and seventh harmonics.
Since a line filter cannot be used with a twelve-pulse rectifier (the
secondary side of the transformer is floating), it is recommended to
equip the supply transformer with a static screen to reduce conducted
emission. Other requirements for the transformer are:
Connection: Dyn 11 d0
Voltage difference between secondaries < 0.3%
Short circuit impedance of secondaries 5%
Short circuit impedance difference between secondaries < 3%
M
3 3 3~
0DLQV 3
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Regenerative IGBT A regenerative IGBT input bridge is available for the wall mounted
Supply (ACx 61_) ACS 600 types in range 25 to 70 kVA (ACx 611 types), and for the
cabinet assemblys in range 185 to 1380 kVA (ACx 617 types).
The IGBT bridge has the ability to regenerate back to the network, and
it provides considerable energy savings with applications requiring
excessive braking power.
Common DC bus
Idc
Supply network
AC choke
Iu
Uc
U0 U1 U2
u0
u1
t (ms)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
the sinusoidal waveform of the line current. The typical spectrum of the
line current and line-to-line voltage harmonics is quite wide, but there
are no high individual components. The Total Harmonic Distortion
(THD) in voltage depends highly on the Short Circuit Ratio in the Point
of Common Coupling (PCC).
Regenerative Thyristor A regenerative thyristor supply is available for the cabinet assemblys in
Supply (ACx 67_) range 185 to 3350 kVA (ACx 677 types). It consists of two six-pulse
thyristor bridges in antiparallel connection. Thyristor supply has the
ability to regenerate back to the network, and provides considerable
energy savings with applications requiring excessive braking power.
ACx 677
Six-pulse Inverter
thyristor
bridge
0DLQV M
3~
3
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Resistor Braking Effective motor braking and short deceleration times can be achieved
using resistor braking. In resistor braking, whenever the voltage in the
intermediate circuit of a frequency converter exceeds a certain limit, a
braking chopper connects the circuit to a braking resistor.
Braking Chopper The NBRA-6xx series includes braking choppers for all ACx 600 types.
NBRA-6xx Some of the choppers are to be mounted inside the converter unit;
others are to be mounted outside the converter unit. (See the footnote
at Table 7-1.)
The control board of the NBRA-6xx supervises the system status and
detects failures such as braking resistor and resistor cable short
circuits, chopper short circuit, chopper control card failure, and resistor
overtemperature (optional).
There is one digital input, one relay output, and two fibre optic
connectors on the chopper control board. The input can be connected
to a resistor-mounted temperature sensitive switch to protect the
resistor against overtemperature. The relay output indicates the faults
listed above. The fibre optic connectors can be used for synchronising
two or more choppers.
Braking Resistor The SACE/SAFUR braking resistors are separately available for all
SACE/SAFUR ACx 600 types. Resistors other than the standard resistors may be
used providing the specified resistance value is not decreased, and the
heat dissipation capacity of the resistor is sufficient for the drive
application. For resistor specifications, see Table 7-1.
Cables and Fuses Screened cable must be used. See the rating tables (Table 7-1 and
Table 7-2) for specifications for standard cables. Two-conductor cable
may also be used if available. The cable screen is essential for
minimising electromagnetic interference. The length of the cable
between the ACx 600 and the chopper must not exceed 5 metres; the
length of the cable between the chopper and resistor must not exceed
20 metres.
For ACx 601 units, no separate fuses in the braking circuit are required
if the following conditions are met:
the ACx 600 mains cable is protected with fuses
no mains cable/fuse overrating takes place
in the braking circuit the specified cable is used (Table 7-3)
For ACx 607 R8 to 2R9 and ACx 607 R11i to 4R11i, the cables in the
braking circuit must be protected with fuses. (Factory-installed
choppers are automatically equipped with fuses when necessary.)
Applicability The chopper(s) and resistor(s) suitable for each ACx 600 type, as well
as technical data for each configuration (maximum braking power,
fuses, cable cross-sections, etc.) are detailed in Tables 7-2 and 7-3.
Table 7-4 gives the dimensions and weights for each chopper and
resistor.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
PBRmax Maximum braking power of the ACx 600 equipped with the standard chopper and the standard resistor. The drive and
the chopper will withstand this braking power for one minute every ten minutes. Note: The braking energy transmitted
to the resistor during any period shorter than 400 seconds may not exceed ER.
R Resistance value for the listed resistor type. Note: This is also the minimum allowable resistance value for the braking
resistor.
ER Energy pulse that the resistor assembly will withstand (400 s duty cycle). This energy will heat the resistor element
from 40 C to the maximum allowable temperature.
PRcont Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER dissipates in 400 seconds.
A Conductor cross-sectional areas for the copper cable to be used for connecting the braking resistor and the chopper
(or the chopper and the ACx 600). The cable should have a concentric conductor (screen). The standard cables with
three-phase conductors and a concentric conductor are given. A two-conductor screened cable may also be used if
available.
* The SACE04RE44 resistor consists of two resistor elements connected in parallel. The resistance of one element is 88 ohm.
The SACE15RE13 resistor consists of four resistor elements connected in parallel. The resistance of one element is 52 ohm.
The SACE15RE22 resistor consists of four resistor elements connected in parallel. The resistance of one element is 88 ohm.
The SAFUR resistors consist of several resistor elements. The resistance of one element is 8 ohm.
The NBRA-653 and -663 are to be installed outside the converter module. Their degree of protection is IP54.
The NBRA-654, -655, -656, -657, -664, -666 and -667 are to be installed inside the converter module.
The NBRA-658, -659 and -669 are to be installed outside the converter module. Their degree of protection is IP00.
All braking resistors are to be installed outside the converter module.
The SACE braking resistors are built in an IP21 metal housing.
The SAFUR braking resistors are built in an IP00 metal frame.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Table 7-2 Braking circuit cable and fuse ratings for NBRA-658, NBRA-659 and NBRA-669.
(Note: All ratings are per one braking chopper.)
ACx 600
NBRA-6xx
Braking
Resistor(s)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
1)Ultrarapid Bussmann fuses (UN = 1250 V). Fuses with the same ratings from other manufacturers can also be used.
The type of the base for these fuses is 170H3005 (1400 V, 630 A, 110 mm).
2) In order for the installation to comply with the EMC Directive, unscreened single-core cable can only be used if routed inside a
cabinet that efficiently suppresses the radiated RFI emissions.
EMC Filters The EMC Filters option minimises the RFI emission of the ACx 600.
The option is available factory-installed as follows:
Internal RFI filter boards for ACx 601 R2 to R7
Line filter for ACx 607 R8 to 2R9, and ACx 607 frame R11i.
The option is not available for 690 V units or 12-pulse supplied units.
Also note that it is not allowed to use the EMC Filters option on an
unearthed (floating) mains supply network.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
du/dt Filters As with all frequency converters employing the most modern IGBT
inverter technology, the ACx 600 output comprises regardless of
output frequency pulses of approximately 1.35 times the mains
network voltage with a very short rise time. The voltage can be almost
double at the motor terminals, depending on motor cable properties.
du/dt filtering suppresses inverter output voltage spikes and rapid
voltage changes that stress motor insulation. Additionally, du/dt filtering
reduces capacitive leakage currents and high frequency emission of
the motor cable as well as high frequency losses and bearing currents
in the motor.
When to Use? The need of du/dt filtering depends on the motor insulation. (For
information on the construction of the motor insulation, consult its
manufacturer.) Failure of the motor to fulfil the following requirements
may shorten its life.
Nominal Mains
Motor Type Motor Insulation Requirement
Voltage (UN)
600 V < UN 690 V Reinforced insulation system in conjunction with du/dt filtering.
420 V < UN 500 V If the insulation system withstands LL = 1600 V and t = 0.2 ms, du/dt
filtering is not required.
With du/dt filtering, the insulation system must withstand LL = 1300 V.
Symbol Explanation
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
4
3.5
3 LL/ UN
2.5
Without du/dt filtering
du/dt / (kV/ms)
2
1.5
1
0.5
0
0 100 200 300 400 Cable length (m)
4
3.5
3
With du/dt filtering 2.5 LL/ UN
2
1.5
du/dt / (kV/ms)
1
0.5
0
0 100 200 300 400 Cable length (m)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Applicability Factory-installed du/dt Filters are available for ACx 607, ACx 617 and
ACx 677. They are installed inside the converter cubicle (no additional
cabinet is required).
The filters are separately available for all ACx 600 types. They need to
be mounted externally. Unprotected (IP00) filters must be encased.
Table 7-4 Applicability of du/dt Filters. The number indicates the
quantity of Filters required for the ACx 600 type. (Note that the kits
marked * include 3 filters.)
*NOCH0120-60
*NOCH0260-60
*NOCH0400-60
NOCH0016-60
NOCH0030-60
NOCH0070-60
NOCH0760-60
NOCH0016-62
NOCH0030-62
NOCH0070-62
NOCH0016-65
NOCH0030-65
NOCH0070-65
ACx 617/677 Types
Types
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
What to Consider The main items to consider when opting to use du/dt filtering are:
A slight decrease in motor pull-out torque caused by the voltage
drop over the du/dt filter(s)
Motor cable length restrictions
The length of the cable between ACx 600 and the filter(s) must not
exceed 3 metres
Cooling requirements when encasing filters.
More information is obtainable from separate publication du/dt Filters
Installation Guide (3AFY 58933368).
Dimensions and
Weights
Table 7-5 Dimensions and weights of the du/dt Filters.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Sine Filter / A sine filter is available as standard cabinet option for ACx 607-0210-6
Step-up Drive to 0760-6 and -0210-5 to -0760-5. For the other ACx 607 units,
ACx 617 and ACx 677, see section Special Cabinet Options. For the
ACx 601 units, commercial filters have been tested and approved by
ABB. For more information please consult your local ABB
representative.
The sine filter option includes:
Sine Filter
a filter connected at the ACx 607 output and installed inside an
additional cubicle
a modified drive software which is loaded at the factory to every
ACx 607 with a sine filter
The sine filter efficiently suppresses the high-frequency components of
the ACx 607 output; The voltage and current waveforms are
sinusoidal. The filter consists of single phase reactors and AC
capacitors.
When to Use? The sine filter makes it possible:
to control a medium voltage motor using ACx 607 (through an
additional step-up transformer)
to use ACx 607 with a motor which does not have an adequate
insulation level required with a frequency converter (i.e. a retrofit of
an old direct-on-line motor)
to use long motor cables (no voltage reflections)
Step-up Drive The Step-up drive consists of the components shown in the figure
below.
~
M
3~
~
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Factory-installed The standard cabinet options form pre-designed packages that are
Standard Cabinet easy to implement to the basic product. Only a little engineering work
Options at the factory is required: the part lists and the delivery drawings are
ready-made and easy to tailor for each delivery.
Cabling Direction As standard, all cables enter the cabinet from below. However, the
Options cabling direction options make it possible e.g. to lead the supply cables
into the cabinet from above.
Variant 1 For ACx 607 R7, R8 & R9, it is also possible to lead the supply cables
through the roof, or lead both the supply and motor cables through the
roof. The cabinet has two signal cable lead-throughs, one at the top,
one at the bottom.
Variant 2 For ACx 607 2R8, 2R9, the mains supply cables can alternatively be
led into the cabinet through the roof. The motor and signal cables are
led through the bottom.
Variant 3 For ACx 607 R11i to 4R11i, bottom or top entry can be selected for
the mains supply cables (or busbars). ACS 627 R11i and R12i (when
equipped with two B3 size rectifier modules) has two 600 mm
additional cubicles for the mains cable entries.
The following motor cabling options are available:
Motor cables exit the cabinet through the bottom of the inverter
cubicle(s). In case of multiple inverter units in parallel, motor
cables are run separately from each inverter unit to the motor.
The outputs of all inverter units are led to an additional common
motor terminal cubicle. Bottom or top motor cable exit can be
selected. (Note that the common motor terminal cubicle is
always required for top motor cable exit.) The widths of the
additional cubicles are:
For R11i: 400 mm
For R12i: 600 mm
For 2R11i: 600 mm
For 2R12i: 800 mm
For 4R11i: 800 mm
These converters are equipped with signal cable lead-throughs both at
the top and at the bottom.
Mains Supply ACx 607 converters are, as standard, equipped with power cable lead-
Conductor Types throughs. A busbar (bus duct) mains supply connection is available for
ACx 607 R11i to 4R11i, ACx 617 and ACx 677.
Earthing Switch The supply section of ACx 607 R11i to ACx 617 and ACx 677 (apart
from 12-pulse types ACx 627-0760-3, -0930-5, -1090-5, -0900-6 and -
1040-6) can be optionally equipped with an earthing switch. It is used
to earth the AC busbars for maintenance work on the system. The
earthing switch is mechanically or electrically interlocked with the main
switch.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Line Switching
Equipment, Emergency
Stop Functions
Variant 1 ACx 607 R7 to 2R9 are automatically equipped with a switch fuse. A
line contactor (two for 2R8 and 2R9) is optional. The line
contactor(s) option includes an emergency stop push-button and a
start/stop switch installed on the cabinet door. (External emergency
stop push-buttons can be wired to a terminal block inside the converter
cabinet.) Pressing the emergency stop push-button immediately opens
the line contactors and the motor coasts to stop. See Immediate
Removal of Power (IEC/EN60204-1 / Category 0) in subsection
Variant 2 below.
The Controlled Emergency Stop (IEC/EN60204-1 / Category 1) is a
special cabinet option for ACx 607 R7 to 2R9. See section Special
Cabinet Options.
Variant 2 ACx 607 R11i to 4R11i with supply unit type B3 (and type -0900-6)
are available equipped either with a manually-operated switch fuse or
with a switch fuse/contactor combination. Converters with supply unit
type B4 or B5 (excluding -0900-6) are available equipped either with a
manually-operated load switch/ disconnector or with an air circuit
breaker.
If a contactor or an air circuit breaker is ordered, an emergency stop
push-button and a start/stop switch are automatically included. One of
the following emergency stop modes can be selected:
Immediate Removal of Power (IEC/EN60204-1 / Category 0): the
Emergency Stop command blocks the inverter semiconductors and
opens the main contactor or air circuit breaker. The motor coasts to
stop.
Controlled Emergency Stop (IEC/EN60204-1 / Category 1): the
Emergency Stop command stops the drive according to a drive
parameter. After the drive is stopped, the main contactor or air
circuit breaker is opened. The effective use of the Controlled
Emergency Stop function requires a braking device (a chopper with
resistors or a regenerative input bridge).
Standards for the The Emergency Stop option is designed in accordance with the
Emergency Stop Option standards:
IEC/EN60204-1 :1997 Safety of machinery Electrical equipment
of machines Part 1: General requirements
EN418 :1992 Safety of machinery Emergency stop equipment,
functional aspects Principles for design
EN292 :1991 Safety of machinery. Basic concepts, general
principles for design. Part 2: Technical principles and specifications
EN954-1 :1996 Safety of machinery Safety-related parts of
control systems Part 1: General principles for design
prEN954-2 :1998
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Circuit Diagram 1 The figure below shows the Prevention of Unexpected Start-up circuit.
Circuit Diagram 2 The figure below shows the IGBT protection circuit.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
DC Busbar Material Aluminium DC busbars are standard for ACx 607 R11i to 4R11i,
ACx 617 and ACx 677. These converters are optionally available with
tin-plated copper DC busbars.
Thermistor (PTC) Relay The Thermistor Relay is available as an option for all ACx 607,
ACx 617 and ACx 677 units.
The option includes a PTC relay and an auxiliary relay wired to a
terminal block.
A thermistor relay is used for the overtemperature supervision of
motors equipped with the PTC thermistors. When the motor
temperature rises to the thermistor wake-up level, the thermistor
resistance increases sharply. The relay detects the change and
indicates motor overtemperature through its auxiliary contacts.
The figure below shows the factory wirings. The connections to be
done by the customer are drawn in dashed lines.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
User Wirings, Examples Example 1: Motor overtemperature causes main breaker trip. (See the
figures above/below.)
Connect motor PTC sensor(s) to the relay.
Connect the normally open contact 13-14 of relay K81 to the main
breaker control circuit.
Connect a reset switch to the relay, or short circuit the reset switch
terminals (= autoreset). Note: Autoreset is not allowed with the type
EEx e motor used in explosive gas atmosphere.
Example 2: Motor overtemperature causes ACS 600 fault trip. Panel
display shows a fault message. (See the figures above/below.)
Connect the motor PTC sensor(s) to the relay.
Connect the normally open contact 13-14 of relay K81 to a digital
input DI6.
Activate the ACS 600 external fault supervision, and set the digital
input DI6 to the fault signal interface.
Connect a reset switch to the relay, or short circuit the reset switch
terminals (= autoreset). Note: Autoreset is not allowed with the type
EEx e motor used in explosive gas atmosphere.
Motor Thermistor Example 1: Motor overtempera- Example 2: Motor overtemperature trips the drive
Connection ture trips the main breaker and generates a fault message on the panel display
13
K81 I/O Control Board NIOC
14
Digital inputs
DI6 Parameter settings (ACS 600
Standard Application Program):
- 30.04 MOTOR THERM PROT
~ 13 to FAULT (if a warning is pre-
K81 ferred instead of a fault trip: set
14 to WARNING).
t
M ~
+24 V - 30.05 MOT THERM P MODE
to THERMISTOR
t
~3
t M
~3
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Technical Data, The table below shows the technical data of the thermistor relay.
Thermistor Relay
Type ABB C506.02
Front view W: 22.5 Rated control voltage (Ui) 115 or 230 V a.c.
H: 104.2
D: 91.9 Rated frequency 50 Hz / 60 Hz
Dielectric test voltage 2.5 kV
Power consumption <2W
Conductor connection 2 (0.5 mm2 to 2.5 mm2)
PTC thermistor circuit
Total cold state resistance per sensor loop 1.5 kW
Triggering threshold 3.4 kW to 3.8 kW
READY LEDs Recovery threshold 1.5 kW to 1.65 kW
TRIPPED
Measuring circuit load 5 mW (at cold resistance 1.5 kW)
Thermistor circuit voltage 2 V (at cold resistance 1.5 kW)
2 2800 m
TEST Reset button
RESET Max conductor length between sensor and 2.5 mm2
relay 1.5 mm2 2 1500 m
0.5 mm2 2 500 m
Auxiliary contacts
Auxiliary contacts 1 normally open + 1 normally closed
Rated thermal current 5A
Rated operational current (AC-15) 3 A / 240 V
Mechanical endurance 20 million ops.
PDM-code: 00032021 - 24 Feb 2000
PTC Relay Operation The figure below shows the state of the PTC relay contacts and the
Diagram Tripped LED as a function of the temperature sensor resistance and
power supply status.
Power On
supply Off
3800 ohm
Sensor
resistance 1500 ohm
Reset
14 Closed 22 Open
Open Closed
13 21
Tripped On
LED Off
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Pt100 Motor Protection The Pt100 relay is available as an option for all ACx 607, ACx 617 and
ACx 677 units. The number of relays is selectable.
The option includes a Pt100 relays and an auxiliary relays wired to a
terminal block.
The Pt100 relay is used for the overtemperature supervision of motors
equipped with the Pt100 sensors. As the motor temperature rises the
sensor resistance increases linearly. At the adjustable wake-up level
the relay releases and indicates motor overtemperature through a
change-over contact.
The figure below shows the factory wirings of an assembly consisting
of five Pt100 and Pt100 relays: Three Pt100s measure the
temperature of motor windings, two Pt100s measure the temperature
of the bearings. The connections to be done by the customer are drawn
using dashed lines.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
User Wirings, Examples Example 1: Motor overtemperature causes main breaker trip
Connect the motor Pt100 sensors as shown in the figure above.
Connect the contact 13-14 of relay K81, and contact 13-14 of relay
K83 to the main breaker control circuit as shown in the figure below.
Example 2: Motor overtemperature causes ACS 600 fault trip. Panel
display shows a fault message.
Connect the motor Pt100 sensors as shown in the figure above.
Connect the contact 13-14 of relay K81, and contact 13-14 of relay
K83 to a digital input DI6 as shown in the figure below.
Activate the ACS 600 external fault supervision, and set the digital
input DI6 to the fault signal interface.
Example 1: Motor overtemperature trips the main Example 2: Motor overtemperature trips the drive and
breaker generates a fault message on the panel display
13
K83
14
I/O Control Board NIOC
13
K81 13
14 K83 Digital inputs
14
DI6 Parameter settings (ACS 600
13 Standard Application Program):
K81 - 30.04 MOTOR THERM PROT
14 to FAULT (if a warning is pre-
~ ferred instead of a fault trip:
set to WARNING).
+24 V - 30.05 MOT THERM P MODE
to THERMISTOR
~
M
~3
User Settings, Temperature range setting (Five DIP switches): The factory setting is
Pt100 Relay 50 to 150 C. However, it is a good practise to check the setting on
field. For the alternative settings, see the circuit diagram above.
Overtemperature wake-up level (adjusting knob): To be set on field.
x temperature range maximum C
100
x = percent value set with the knob
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Pt100 Relay Operation The figure below shows the state of the Pt100 relay as a function of the
Diagram supervised temperature and power supply status. The relay is set to
supervise overtemperature limit (DIP switch DI6 is off).
On
Power
supply Off
Wake-up
Motor level (C)
temp. Hysteresis
level (C)
Relay Hold
status Released
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Cubicle Heater The Cubicle Heater is available as an option for all ACx 607, ACx 617
and ACx 677 units. The heater prevents humidity condensation inside
the ACx 607 cabinet in a power-off state.
The Cubicle Heater option includes a heating element in each
converter cubicle (in 1000 and 1500 mm wide cubicle there are two).
The heater elements are to be supplied from an external 230 V a.c.
power supply by the user (50 W per element).
Variant 1 In units up to ACx 607 R7 to 2R9, the heating circuit must be
equipped with external disconnector and protection device(s) by the
user. Also the heater on/off control, if needed, should be arranged by
the user.
The figure below shows the equipment and wirings.
R1 R2
N
PDM-code: 00011581-C
Variant 2 In ACx 607 R11i to 4R11i, ACx 617 and ACx 677, the heating circuit is
equipped with a load switch and a protective circuit breaker. Heating is
switched off when the drive supply bridge is operating i.e. a relay output
on the I/O control board has energised relay K11.
The figure below shows the equipment and wirings.
Q41 RO3
K11
PDM-code: 00011580-C
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Starter for Auxiliary The Starter for Auxiliary Motor Fan option is available as an option for
Motor Fan all ACx 607, ACx 617 and ACx 677 units.
The option includes a motor protection switch and a contactor wired to
a terminal block. The starter supplies a fan of a separately ventilated
motor with a 3-phase supply voltage equal to the ACx 600 input
voltage. (1, 2 or 4 auxiliary motor fan starters can be selected for
ACx 607 R11i to 4R11i, ACx 617 and ACx 677)
Table 7-6 Available current ratings for the auxiliary motor fan starters.
1 to 1.6 A 1 to 1.6 A
1.6 to 2.5 A 1.6 to 2.5 A 1.6 to 2.5 A
2.5 to 4 A 2.5 to 4 A 2.5 to 4 A
4 to 6 A 4 to 6.3 A 4 to 6.3 A
6 to 10 A 6 to 10 A
9 to 14 A 9 to 14 A
13 to 18 A 13 to 18 A
18 to 25 A
25 to 40 A
(not for 690 V units)
40 to 50 A (not for 500 V and
690 V units)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Motor Heater Outputs The Motor Heater Outputs are available as a standard cabinet option
for ACx 607 R11i to 4R11i, ACx 617 and ACx 677. For the other units
see section Special Cabinet Options.
The heater prevents humidity condensation inside the motor enclosure
in the drive power-off state. When the main breaker of the drive is
closed, the heater is off.
The option includes:
Heater output terminals
Terminals for the external power supply (only if external power
supply is used)
A protective circuit breaker and an on/off contact wired between the
heater power supply and output terminals
Each heater output is rated to max. 230 V a.c., 4 A. The customer
specifies:
the number of heater outputs (two or four)
the heater power source: internal (from the ACx 607 auxiliary
voltage transformer), or external (a user-defined power supply)
The figure below shows the internal wiring of a configuration with two
heater outputs. The heater terminals are supplied internally from the
ACx 607 auxiliary transformer.
K11
x
F11 I>
y
x
K5
y
x x
K40
PE
PE
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Auxiliary Control As standard, all ACx 600 units are equipped with 230 V a.c. auxiliary
Voltage voltage components.
115 V a.c. auxiliary voltage circuitry and components are available as a
standard cabinet option for ACx 607 R11i to 4R11i, ACx 617 and
ACx 677. For the other units see section Special Cabinet Options.
Note: With combination 115 V a.c. / 50 Hz control voltage, the inverter
cooling fans need 230 V a.c. supply to meet the cooling requirements.
The extra arrangement is shown in the figure below.
380V
400V
415V
440V
460V
500V
Auxiliary voltage transformer
- 380 to 500 V / 50 Hz primary
- 115 V / 50 Hz secondary (auxiliary circuits)
- 230 V / 50 Hz secondary (inverter fans)
115 V auxiliary
circuits
NAMC/NIOC The NAMC and NIOC boards of the ACx 600 are, as standard,
Power Supply powered from the frequency converter intermediate DC link through a
Power Supply Board (NPOW). The NAMC and NIOC boards are live
when the DC link is live i.e. the main breaker is closed.
To keep the NAMC and NIOC live also when the main
contactor/breaker is open, the drive can be equipped with 230 V a.c. /
24 V d.c. power supply. See section Power Supply Module NPSM-02.
The NAMC/NIOC power supply is available as a standard cabinet
option for ACx 607 R11i to 4R11i, ACx 617 and ACx 677. For the
other units see section Special Cabinet Options.
Terminals for External The Terminals for External Control Voltage Supply (e.g. UPS) is
Control Voltage Supply available as an option for ACx 607 R11i to 4R11i, ACx 617 and
(e.g. UPS) ACx 677. For the other units see section Special Cabinet Options.
The external supply backs up the internal control voltage supply i.e. it
keeps the auxiliairy circuits live during a ACx 607 mains supply
interruption. The supply is to be selected and connected by the user.
Ratings:
230 or 115 V a.c. (according to the ACx 607 control voltage)
1000 VA
Option includes a disconnecting switch, connection terminals,
protective circuit breakers and ACx 607 internal wirings.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Additional I/O Terminal An additional terminal block X2 for the user digital and analogue I/O
Block X2 signal connections is included as default for ACx 607 R11i to 4R11i,
ACx 617 and ACx 677. X2 is available as an option for ACx 607 R7 to
2R9.
The terminal block X2 is installed beside the NIOC board on a easy-to-
access assembly plate. The X2 terminals are wired to the NIOC board
I/O terminals at the factory. See the figure below.
.
.
.
.
.
.
X2
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Terminals
NIOC
X27
X26
X25
X23
X22
X21
12
11
10
3
2
1
3
2
1
3
2
1
2
1
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
DGND
+24 V
VREF
RO33
RO32
RO31
RO23
RO22
RO21
RO13
RO12
RO11
AO2+
AO1+
+24V
+24V
AO2-
AO1-
GND
GND
AI3+
AI2+
AI1+
AI3-
AI2-
AI1-
DI6
DI5
DI4
DI3
DI2
DI1
X2:
terminals for the user I/O signal connections
conductors 0.5 to 2.5 mm 2 (# 20 to # 14 AWG)
X21, X22, X23, X25, X26, X27:
I/O terminals on the NIOC Board
conductors 0.5 to 1.5 mm 2 (# 20 to # 16 AWG)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Earth Fault Protection in The earth fault protection is a standard feature for ACx 607 R7 to 2R9.
IT Network (floating See Chapter 6 Standard Features.
mains supply)
The earth fault protection in IT network is available as an option for
ACx 607 R11i to 4R14i, ACx 617 and ACx 677. This section
describes the protection for these units.
The option includes an assembly of four resistors (SCAU-Z), a rectifier,
an overvoltage relay and an fault indication circuitry wired as shown
below.
Operation Three symmetrically connected resistors form an artificial neutral point
to the 3-phase system. A high resistance resistor is connected
between the artificial neutral point and the earth. The overvoltage relay
supervises the rectified voltage over the high resistance resistor. An
earth fault at the inverter output causes an asymmetry to the 3-phase
system and a voltage difference between the neutral point and the
earth. The overvoltage relay detects the voltage difference and wakes
up.
Stage Description
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Circuit Diagram 1 The figure below shows the Earth Fault Protection circuit.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Earth Fault Protection in The earth fault protection is a standard feature for ACx 607 R7 to 2R9.
an TN Network (earthed See Chapter 6 Standard Features.
mains supply)
The earth fault protection in TN network is available as an option for
ACx 607 R11i to 4R14i, ACx 617 and ACx 677. This section
describes the protection for these units.
The option includes a current transformer which is wired to an
analogue input which is either on a supply control board (diode supply
bridge) or an additional board (thyristor supply bridge). In addition the
earth fault supervision function in the rectifier control program is
activated.
Operation The earth fault protection in a TN network is based on a summation
current transformer, monitoring the sum of the three-phase supply
currents. Transformer output is monitored through an analogue input of
the rectifying bridge.
In normal operation conditions the current sum is approximately zero.
An earth fault leads to an imbalance in the 3-phase system and to a
current sum which is greater than zero. If the current induced to the
transformer secondary winding exceeds the limit set in the software,
the main contactor/breaker is tripped and a fault message is generated.
The transformer transformation ratio is fixed. The protection is tuned by
a rectifier control program parameter. The factory presetting (4 A) can
be retuned on field.
Circuit Diagram The figure below shows the wiring principle of the Earth Fault
Protection in an TN Network option based on the summation current
transformer.
~
L1
L2
L3
=
~
Digital output
I/O Terminals
Analogue input
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Cable Markings As standard the conductors and terminals in ACS 600 frequency
converters are marked in accordance with the Standard Class as
described below.
In the cabinet assemblys, the conductors outside the converter module
can also be equipped with additional markings. For information on the
optional marking types, contact a factory representative.
Standard Class In Standard Class, only input and output terminals, plug-in connectors,
PDM-code: 00012745.doc
fibre optic connectors and ribbon cables are marked. Conductor
bundles may have markings printed on the insulation. The table below
shows the marking principle.
X301
adhesive tape. Marking rings are not used on conductors that
cannot be detached from the connector otherwise than by a
special tool.
X301
A1/X4
A1/X4
Fibreoptics On fibreoptics, apparatus and terminal identifiers are marked
using marking rings or adhesive tape. A1 V1 6
Busbars and Main circuit terminals are marked either directly on the busbar
Cables or beside the connector, with the terminal or busbar identifier
printed on the insulating material. Earthing cables are marked
with yellow-and-green tape.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Cabinet Option Additional weight caused by some factory-installed cabinet options are
Weights given in the tables below.
Cabinet Weight/Width - - -
Extension 190 kg/m
1) ACx
607 units up to -0320-3, -0400-5, -0400-6 only.
2)
One power supply supplies one to six modules.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Special Cabinet The special cabinet options form no pre-designed packages as the
Options standard cabinet options i.e. they cannot be specified using the type
code key. Instead they require additional engineering work at the
factory: the part lists and the delivery drawings are done case by case
for each delivery. The actual connections and used components may
vary.
The special cabinet options are available only on request.
Note: It is also possible to have other special options than the ones
described in this document. Please consult a factory representative.
Controlled Emergency The Controlled Emergency Stop is available as a special cabinet option
Stop for ACx 607 R7 to 2R9.
The design is the same as for the ACx 617 and ACx 677. See section
Factory-installed Standard Cabinet Options.
Auxiliary Control 115 V a.c. auxiliary voltage circuitry and components are available as a
Voltage special cabinet option for ACx 607 R7 to 2R9.
Note: The converter module fans are always supplied from the
intermediate circuit DC link.
NAMC/NIOC The internal power supply is available as a special cabinet option for
Power Supply ACx 607 R7 to 2R9.
The design is the same as for the ACx 617 and ACx 677. See section
Factory-installed Standard Cabinet Options.
Sine Filter / Step-up The sine filter is available as a special cabinet option for ACx 607 R11i
Drive to 4R11i, ACx 617 and ACx 677.
The design is the same as described in section Sine Filter / Step-up
Drive.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Empty Cabinet Empty cabinet is available as special cabinet option for all ACx 607,
ACx 617 and ACx 677 units.
The cabinet is identical into which the ACx 607, ACx 617 and ACx 677
are assembled:
The same materials
The joints between the cover plates and the frame are sealed to fulfil
the Electromagnetic Compatibility requirements (European EMC
Directive).
The roof construction is the same including the air outlet (openings,
fabric filter, brass grid, and louvre).
The following needs to be specified using the document Empty
Cabinet Specification (EN code: 61411542) when ordering:
Loose cabinet or an additional empty cubicle attached to the drive
(left or right side).
Degree of protection: IP 21, IP 22, IP 42, IP 54 or IP54R
Door: With or without air inlet openings, with or without the panel
mounting platform
Blank (no holes) assembly plates inside the cabinet: None, one on
the back or one on the back and one on a side
Cable lead-through:
1. No cable lead-through needed.
2. Standard lead-through from above. See section Customer-
defined Cable Lead-through Plate.
3. Standard lead-through from below. See section Customer-
defined Cable Lead-through Plate.
4. Customer-defined lead-through (holes or without holes). See
section Customer-defined Cable Lead-through Plate.
Cabinet width: 400, 600, 700 or 800 mm
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Terminals for External The terminals for external control voltage supply (e.g. UPS) are
Control Voltage Supply available as a special cabinet option for ACx 607 R7 to 2R9.
(e.g. UPS)
The option includes connection terminals, protective circuit breakers
and ACx 607 internal wirings.
The external supply backs up the internal control voltage supply i.e. it
keeps the customer-selected auxiliary circuit live during an ACx 607
mains supply interruption. In the basic design the external supply
backs up the power supply of the optional modules: Digital I/O
extensions, analogue I/O extension, and/or fieldbus adapter. On
request other circuits can also be backed up.
The external power supply is to be selected and connected by the user.
Ratings:
230 or 115 V a.c. (according to the ACx 607 control voltage)
power depends on the power consumption of the circuits backed up
Note: No Uninterrupted Power Supply (UPS) is included: The user
selects and instals the UPS if a battery charged back up is needed.
However, it is possible to feed the user-defined UPS from the ACx 607
auxiliary voltage transformer.
Note: To keep the ACx 607 control live during a mains supply
interruption:
The control voltage supply is to be backed up.
The Application and Motor Control Board, NAMC, and Standard I/O
Control Board, NIOC, are to be fed through an optional 230 V a.c /
24 V d.c. power supply module. See subsection NAMC/NIOC Power
Supply.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Basic Wiring Diagram The figure below shows the internal wirings of the UPS connection.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Motor Heater Output The motor heater output is available as a special cabinet option for
ACx 607 R7 to 2R9.
The heater prevents humidity condensation inside the motor enclosure
in the drive power-off state. When the ACx 607 main breaker is closed,
the heater is off.
The option includes:
terminals for the motor heater (max. 230 V a.c., max. 4 A)
terminals for an external heater supply that needs to be connected
by the user: max. 230 V a.c., max. 4 A
a protective circuit breaker and an on/off contact wired between the
power supply and heater terminals
The figure below shows the ACx 607 internal wirings.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Cabinet Lighting The cabinet lighting is available as a special cabinet option for all
ACx 607, ACx 617 and ACx 677 units.
An example of the cabinet lighting is shown in the figure below.
F3.2 H1
T10 F5 S1
230 V (115 V)
50 Hz (60 Hz)
380 ... 690 V / 230 V 11 W
(115 V), 500 VA
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
6 Grommet Rubber
1)
Not in all units.
2)
Only with degree of protection IP 54.
The steel plates have a zinc surface treatment FE/Zn 8 c 2.
Top view
2
5
6
Top view
3 3 a)
4 4 a)
4
4 a)
4 b)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Ammeters One to three ammeters are available as a special cabinet option for all
ACx 607, ACx 617 and ACx 677 units.
The ammeters are installed on the front door. The equipment and
wiring of the current meters are shown in the figure below.
72 mm 5.5 mm
Meter type
EQ72-X
72 mm
Manufacturer
DEIF
63 mm More information
(inside cabinet) http:\\www.deif.com
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Voltmeter A voltmeter is available as a special cabinet option for all ACx 607,
ACx 617 and ACx 677 units.
The voltmeter and the phase selection switch are installed on the front
door. The equipment and wiring of the voltmeter option are shown in
the figure below.
Drive equipped with a fuse switch Drive equipped with an air circuit breaker
72 mm
63 mm
(inside cabinet)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Running Hour Counter A running hour counter is available as a special cabinet option for all
ACx 607, ACx 617 and ACx 677 units.
The counter is installed on the front door above the main disconnecting
switch. The counter runs when the drive is running (start signal and run
enable signals are on, no fault). The figure below shows the equipment
and the wiring.
Q1
48 mm
L1
L2 Meter type
HCQ48
L3 48 mm
0000000
, h
Manufacturer
DEIF
F2.2
5 mm More information
T1
http:\\www.deif.com
380 ... 690 V / 230 V
500 VA
F3
AI/O Galvanic Isolation The current analogue inputs and or outputs can be equipped with
galvanic isolators. The isolators are available as a special cabinet
option for all ACx 607, ACx 617 and ACx 677 units.
In the figure below a 0 to 20 mA reference signal is connected to
analogue input 2 via a galvanic isolator.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Analogue Output Signal Analogue output signal meters are available as special cabinet options
Meters for all ACx 607, ACx 617 and ACx 677 units.
The meter type is selected according to the value to be monitored.
Various scales/units are available. For example the following units can
be selected:
current
direct voltage
rotating speed
percentage
power
The meter is installed on the front door above the main disconnecting
switch. The drive actual value to be indicated through an analogue
output is selected with an application program parameter.
The figure below shows the wiring and the drive application program
parameter setting for an RPM-meter. Also the meter dimensions and
the very basic data is given below.
72 mm
63 mm
(inside cabinet)
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Key-operated Switch A key-operated switch is available as a special cabinet option for all
ACx 607, ACx 617 and ACx 677 units.
The switch is installed on the front door. The figure below shows an
example of the usage of the switch. The switch selects between two
control signal interfaces, i.e. the I/O signal terminals and the serial
communication link (fieldbus control). Accidental control interface
change is prevented by locking the switch.
Digital inputs
DI3
Parameter
setting: EXT1/EXT2 SELECT
+24 V
Push Buttons Push buttons are available as a special cabinet option for all ACx 607,
ACx 617 and ACx 677 units.
The push buttons are installed on the front door. The figure below
shows an example of the usage of the buttons.
Parameter settings
I/O Control Board NIOC (ACS 600 Standard Application Program):
DI2
+24 V
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Additional Relay(s) Additional relay(s) is available as a special cabinet option for all
ACx 607, ACx 617 and ACx 677 units.
The figure below shows an example of the usage of the additional
relay: A 230 V a.c. circuit is used as the source for the start and stop
commands. An additional relay is needed between the external 230 V
circuit and the ACx 607 digital input DI1 terminal (24 V d.c).
Parameter settings
I/O Control Board NIOC (ACS 600 Standard Application Program):
+24 V
Signal Lamp(s) Signal lamps are available as special cabinet options for all ACx 607,
ACx 617 and ACx 677 units.
The signal lamps are installed on the front door above the main
disconnecting switch. The figure below shows an example of the use of
signal lamps.
Relay outputs
RO1 H1
Parameter setting: READY H2
RO2 H3
Parameter setting: RUNNING
H4
RO3
Parameter setting: FAULT (-1)
0V
+24 V
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Other Options
Control Panel CDP 312 The detachable Control Panel is available as factory-installed and as
an add-on kit for ACx 601 and ACx 607. For ACx 604, the panel is
available as an add-on kit only. The dimensions of the CDP 312 are
(H x W x D): 170 x 80 x 21 mm, weight 0.2 kg.
Panel Link Cables The NPLC series consists of screened telecommunications cables with
NPLC-0xy crossover wiring (suffix C) or straight-through wiring (suffix S).
Length Example
Type Wiring
[m] Application
NPLC-00C 0.5
Crossover Control Panel
NPLC-02C 2
(1 to 6, 2 to 5, etc.) connection
NPLC-03C 3
NPLC-00S 0.5
Linking of NIOC
Straight-through
NPLC-01S 1 boards for common
(1 to 1, 2 to 2, etc.)
control
NPLC-02S 2
Control Panel Mounting The Panel Mounting Platform add-on kit NPMP-01 includes the Control
Platform Kit Panel Mounting Platform, a telephone connector, NDPI-02 Connection
NPMP-01/02/03 Board, and a 3-metre telephone cable. Gaskets are also included for
IP54 protection.
NPMP-02 contains the above parts and a CDP 311 Control Panel.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
NPMP-03 contains the above parts and a CDP 312 Control Panel.
Mounting Platform
Dimensions (H x W x D):
320 x 193 x 47.5 mm
Protrusion: 22 mm
The NPMP-xx kits can be used with all ACx 600 types for installing the
Control Panel on a cabinet door or a remote control desk. The NDPI-02
Connection Board (supplied with the kit) is wired to the Standard I/O
Board (NIOC) of the ACx 600. (See also section Bus Connection
Interface Module NBCI-02 above.) The NDPI-02 has two LEDs which
indicate the status of the drive while the control panel is detached. The
green LED indicates that the ACx 600 is powered, the red LED
indicates that a fault is detected. The Control Panel is attached to the
Control Panel Mounting Platform on the cabinet door by pushing it into
the recess.
ACx = ACS/ACC/ACP
Chapter 7 Optional Equipment
Fibre Optic Cables The Fibre Optic Cables option includes two single-core plastic fibre
NLWC-xx optic cables with connectors at the ends. The option is available as an
add-on kit in five lengths:
2 metres (NLWC-02)
3 metres (NLWC-03)
5 metres (NLWC-05)
7 metres (NLWC-07)
10 metres (NLWC-10)
Fibre optic cables are needed e.g. when connecting an I/O Extension
or a fieldbus adapter module to the ACx 600. As standard, the module
package contains cable pairs of which the longest one is two metres. If
longer cables are required, a suitable type from the available NLWC-xx
Fibre Optic Cables options can be chosen.
Coated Circuit Boards The Coated Circuit Boards option can be ordered as factory-installed
for all ACx 600 types. (Coated boards are also available separately as
spare parts.) The following boards are coated when this option is
selected:
NAMC (Application and Motor Control Board)
NIOC (Standard I/O Control Board)
NINT (Main Circuit Interface Board)
NGDR (Gate Driver Board)
NDCO (DDCS Communication Option), if present
NBRC (Braking Chopper Control Board), if present.
The boards are varnished with a UL-approved acrylic coating for
protection against hazards like humidity, dust and dirt, and airborne
contaminants. Conformal coating remarkably increases the corrosion
resistance of the ACx 600.
To further improve the protection, it is recommended to combine the
Coated Circuit Boards option with IP54 protection of the ACx 600.
The allowable contamination levels for the boards are given in the
Technical Data appendix.
ACx = ACS/ACC/ACP
Chapter 8 Selecting the Motor and the ACS 600
Overview The excellent performance of the ACS 600 makes it suitable for most
applications.
To specify your ACS 600 drive, select the ACS 600 rating according to
the overload capacity required. Then choose a motor and a suitable
ACS 600 for your motor.
There is a DriveSize PC tool available for optimal motor and ACS 600
selection. See Chapter 7 Optional Equipment for more information.
T/TN Curve 4
2.0 Heavy-duty use 2 s every 15 s (at starting) for the 400 V and 500 V units.
For the 690 V units see Technical Data appendix
1.9
1.8
1.7 Curve 3
Normal use 2 s every 15 s (at starting)
1.6 Heavy-duty use 1 min every 10 min
1.5
1.4
1.3
Curve 2
1.2
Normal use 1 min every 10 min
1.1
1.0
0.9
0.8
0.7
0.6
Curve 1
0.5
Pump and Fan use, Normal use, Heavy-duty use
0.4
0.3
0.2
S QXPEHURISROHV
0.1
7 ORDGWRUTXH 0.0
0 10 20 30 40 50 60 70 80 90 100 f (Hz)
7 1 UDWHGPRWRUWRUTXH
p=2
Q VSHHG 0 600 1200 1800 2400 3000 3600 n (rpm)
I RXWSXWIUHTXHQF\RI
p=4
0 300 600 900 1200 1500 1800 2100 2400 n (rpm)
$&6 p=6
0 200 400 600 800 1000 1200 1400 1600 n (rpm)
p=8
0 150 300 450 600 750 900 1050 n (rpm)
$&67HFKQLFDO&DWDORJXH 8-1
Chapter 8 Selecting the Motor and the ACS 600
Note: If the ACS 600 is operated at high speeds (output frequency over
90 Hz), it should be observed that the motor maximum torque is not
exceeded.
At low frequencies, the reduction in the continuous load capacity is due
to the fact that the cooling capacity of a self-ventilated motor is
reduced. In the field weakening range (f > 50 Hz), the load capacity is
reduced because the output voltage of the ACS 600 cannot be
increased.
At frequencies above 37.5 Hz, the reduction in the 200 % peak
overload capacity (Figure 8-1, Curve 4) is due to the fact that the
internal power limit (1.5 Phd) restricts the allowed motor torque.
Selecting the There are three ratings for the ACS 600, the pump and fan use rating,
ACS 600 Rating the normal use rating and the heavy-duty use rating. Typically, the
ACS 600 rated for pump and fan use or for normal use is selected. The
pump and fan rating provides no overload capacity but the highest
possible continuous load capacity. It is suitable for the squared torque
applications (pump and fan drives). With the normal use rating
ACS 600 provides 110 % short term overload capacity and 150 % peak
overload capacity, which fulfils most requirements. If even higher
overload capacity is needed the ACS 600 rated for heavy-duty use is
selected.
Exception: If Scalar Control is used, the heavy-duty use rated ACS 600 must be
selected for constant torque applications, even if no high overload capacity is required.
Scalar Control must be used instead of Direct Torque Control in special applications,
such as variable configuration multimotor drives. For more information on Scalar
Control, see Chapter 2 Motor Control Methods and Chapter 6 Standard Features.
Motor Selection As a general rule, the motor rated speed should be selected so that the
motor continuous load capacity throughout the required speed range is
as high as possible.
Constant Torque
Required speed range is 500 to 1800 rpm
T/T N 1 = Motor rated speed is 1500 rpm
2 = Motor rated speed is 3000 rpm
1.5 3 = Motor rated speed is 1000 rpm
1.0
1
2
3
0.5
0.0 f (Hz)
0 10 20 30 40 50 60 70 80 90 100
8-2 $&67HFKQLFDO&DWDORJXH
Chapter 8 Selecting the Motor and the ACS 600
The rated motor power must be higher than the continuous power
required by the driven machine. In addition, the following factors must
be considered:
the continuous load capacity of the motor controlled by the
ACS 600,
the short-term overload capacity of the motor controlled by the
ACS 600,
the peak overload capacity of the motor controlled by the ACS 600.
The relation between the motor power and the torque is given by:
P = power (kW)
n = speed (rpm)
P = n T/9550 kW
T = torque (Nm)
p
ACS 600 Selection The ACS 600 is selected according to the rated motor power. It must be
then checked that the rated output current of the ACS 600 is higher
than, or equal to, the rated motor current.
In certain situations, it is possible to use an oversize motor. Please
consult an ABB representative for more information.
To Be Noted This chapter contains the general rating instructions for the motor and
the ACS 600. It is assumed that the motor overload capacities
correspond to the figures given for the ACS 600.
In applications requiring an exceptionally high short term overload
capacity, the simplification above may lead to selection of a motor with
higher rating to what is actually required. However, the ACS 600 is
correctly selected also in these cases. If in any doubt about the
preliminary motor selection, please refer to the actual overload
capacity figures given by the motor manufacturer.
In applications requiring high peak overload capacities (up to 200 %), it
should always be observed that the motor maximum torque is not
exceeded.
$&67HFKQLFDO&DWDORJXH 8-3
Chapter 8 Selecting the Motor and the ACS 600
Example 1.a The minimum and maximum speeds are 600 rpm and 1900 rpm. The
Constant Torque Drive continuous torque required on the motor shaft is constant at 20 Nm,
and the breakaway torque (during start for about one second) is
30 Nm. The supply voltage is 400 V.
Selecting the The ACS 600 is selected according to the normal use rating since the
ACS 600 Rating breakaway torque is not exceptionally high and no short term overload
capacity is required.
Motor Selection A four-pole motor is chosen. Its synchronous speed is 1500 rpm at
50 Hz.
The motor power rating is calculated:
The power corresponding to the continuous load torque (20 Nm) is
P = 1900 20/9550 = 4.0 kW.
The continuous load capacity of the motor controlled by ACS 600 is
89 % at 600 rpm and 80 % at 1900 rpm. See Figure 8-1, Curve 1.
The peak overload capacity of the motor controlled by ACS 600 is
150 %. See Figure 8-1, Curve 3.
No short term overload capacity is required.
The motor is rated according to the most critical point. The required
motor power is P = 1500 25/9550 = 3.9 kW. The next larger standard
motor from a motor catalogue is chosen. The rated power is 4 kW and
the rated current is 9 A.
ACS 600 Selection For the 4.0 kW motor, the ACS 601-0006-3 is selected. The rated
currents are checked. Since the rated motor current is lower than the
rated output current of the ACS 600, the selection is accepted.
8-4 $&67HFKQLFDO&DWDORJXH
Chapter 8 Selecting the Motor and the ACS 600
Example 1.b Constant The requirements are the same as in Example 1.a, except that a
Torque Drive High 70 Nm breakaway torque is required.
Breakaway Torque
Selecting the The ACS 600 is chosen according to the heavy-duty use rating since a
ACS 600 Rating breakaway torque higher than 150 % of continuous load torque is
required.
Motor Selection A four-pole motor is selected. Its synchronous speed is 1500 rpm
at 50 Hz.
The motor power rating is calculated:
The power corresponding to the continuous load torque of 20 Nm is
P = 1900 20/9550 = 4.0 kW.
The continuous load capacity of the motor controlled by ACS 600 is
89 % at 600 rpm and 80 % at 1900 rpm. See Figure 8-1, Curve 1.
The peak overload capacity of the motor controlled by ACS 600 is
200 %. See Figure 8-1, Curve 4.
No short term overload capacity is required.
The motor power is rated according to the most critical point. The
required motor power is P = 1500 35/9550 = 5.5 kW. A standard motor
is chosen from a motor catalogue. The rated power is 5.5 kW and the
rated current is 12 A.
ACS 600 Selection For the 5.5 kW motor, the ACS 601-0011-3 is selected. The rated
currents are checked. Since the rated motor current is lower than the
rated output current of the ACS 600, the selection is accepted.
$&67HFKQLFDO&DWDORJXH 8-5
Chapter 8 Selecting the Motor and the ACS 600
Example 2 Squared The power requirement of a centrifugal fan is 40 kW at 3000 rpm. The
Torque Drive maximum fan speed is 3600 rpm and the minimum speed is 1200 rpm.
The supply voltage is 400 V.
Selecting the The ACS 600 is selected according to the pump and fan use rating
ACS 600 Rating since no overload capacity is required.
Motor Selection A two-pole motor is chosen. Its synchronous speed is 3000 rpm
at 50 Hz.
Since the torque of a centrifugal fan increases according to the square
of the speed and the power according to the cube of the speed, the
required motor power is calculated only on the basis of the required
power at maximum speed.
P = (3600/3000)3 40 kW = 69.1 kW.
The continuous load capacity of the motor controlled by the ACS 600 is
83 % (Figure 8-1, Curve 1) at 3600 rpm. The required motor torque is T
= 9550 69.1/(3600 0.83) = 220.9 Nm and the required motor power is
P = 3000 220.9/9550 = 69.4 kW.
The next larger standard motor from a motor catalogue is selected. The
rated power is 75 kW and the rated current is 135 A.
ACS 600 Selection For the 75 kW motor, the ACS 601-0100-3 is selected. The rated
currents are checked. Since the rated motor current is lower than the
rated output current of the ACS 600, the selection is accepted.
8-6 $&67HFKQLFDO&DWDORJXH
Chapter 8 Selecting the Motor and the ACS 600
Example 3 Constant The drive is run at a constant 800 rpm speed. The load torque on the
Torque Drive High Short motor shaft varies in 10 minute cycles: the torque is 800 Nm for nine
Term Overload minutes and 1500 Nm for one minute. The starting torque is 1800 Nm
Required (needed for about one second). The supply voltage is 400 V.
Selecting the The ACS 600 is selected according to the heavy-duty use rating since
ACS 600 Rating short term overload capacity more than 110% of continuous load
torque is required.
Motor Selection An eight-pole motor is chosen. Its synchronous speed is 750 rpm
at 50 Hz.
The continuous power required by the driven machine is
P = 800 800/9550 = 67 kW.
The continuous load capacity of the motor controlled by the
ACS 600 is 94 % at 800 rpm. See Figure 8-1, Curve 1.
The peak overload capacity of the motor controlled by the ACS 600
is 200 % (during the start). See Figure 8-1, Curve 3.
The short term overload capacity of the ACS 600 is 140 % at 800
rpm during a one minute step. See Figure 8-1, Curve 3.
The motor is rated according to the most critical point. The required
motor power is P = 750 1071/9550 = 84.1 kW. The next larger
standard motor from a motor catalogue is chosen. The rated power is
90 kW and the rated current is 178 A.
ACS 600 Selection For the 90 kW motor, the ACS 607-0140-3 is selected. The rated
currents are checked. Since the rated motor current is lower than the
rated output current of the ACS 600, the selection is accepted.
$&67HFKQLFDO&DWDORJXH 8-7
Chapter 8 Selecting the Motor and the ACS 600
8-8 $&67HFKQLFDO&DWDORJXH
Chapter 9 Installation Guidelines
Input Fuses The fuses are needed for input bridge and mains cable short circuit
protection. The ACx 600 protects the installation against overload.
ACx 601 For frame sizes R5, R6 and R7, ultrarapid fuses must be used.
Ultrarapid fuses are recommended also for frame sizes R2, R3 and R4.
Fuses are to be installed outside the unit, one for each phase
conductor. The ultrarapid fuses protect the ACx 600 input bridge in
internal short circuits. When installed at the distribution board, they
also protect the mains cable against short-circuits.
$&[$&[ The ACx 607, ACx 617 and ACx 677 are equipped with internal
$&[ $&[ ultrarapid fuses that protect the input bridge against short-circuits. The
ACx 604 is not equipped with input fuses. When installing the ACx 604,
the supply must always be connected via ultrarapid fuses. When the
ultrarapid fuses are installed at the distribution board, they also protect
the mains cable against short-circuits.
Supply Disconnecting The ACx 601 and ACx 604 are not equipped with a disconnector or
Device main switch. According to European Standard EN 60204-1, Safety of
Machinery, a hand-operated supply disconnecting device shall be
installed in each power supply. The disconnecting device must be one
of the following types:
a switch-disconnector in accordance with EN 60947-3; utilization
category AC-23B or DC-23B;
a disconnector which has an auxiliary contact which in all cases
causes switching devices to break the load circuit before the
opening of the main contacts of the disconnector;
a circuit-breaker in accordance with EN 60947-2 suitable for
isolation in accordance with EN 60947-3.
The ACx 607, ACx 617 and ACx 677 can be equipped with a hand
operated main switch, which fulfils the above requirements for the
supply disconnecting device. The ACx 607 can also be equipped with
line contactor, start-stop switch and emergency stop switch.
ACx = ACS/ACP/ACC
Chapter 9 Installation Guidelines
ACx = ACS/ACP/ACC
ACS 600 Technical Data
Technical Data
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Mains Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Motor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Efficiency and Cooling Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Ambient Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Degree of Protection and Free Space. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
NIOC and NIOCP Board Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Encoder Signals at NIOCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
ACS 600 Control Connections on the NIOC Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
ACP 600 Control Connections on the NIOCP Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Application Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Application Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Macro/Language Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Applicable Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
CE Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
UL/CSA Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
C-tick Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Compliance with AS/NZS 2064 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Cable Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Markings in the Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Terminal Sizes and Tightening Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Cooling Air Flow Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensions and Weights (ACx 604/624) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensions and Weights (ACx 607/627) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Braking Chopper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Output Current Temperature Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Input Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Motor Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Efficiency and Cooling Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ambient Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
AC Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Branch Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Drive Section DC Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Braking Section DC Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Cable Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tightening Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Diode Supply Sections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Thyristor Supply Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
IGBT Supply Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Drive Sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
External Control Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
NIOC Board Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Drive Section Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cooling Air, Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Dynamic Braking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Application Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Applicable Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Materials (Cabinet & Busbars) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Transportation Lenghts and packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
CE Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CSA Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
C-tick Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Compliance with AS/NZS 2064 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Equipment Warranty and Liability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Limitation of Liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
iv ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and
ACx 607/627/677 R7 to 2R9
ACx = ACS/ACC/ACP 1
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
2 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
ACx = ACS/ACC/ACP 3
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Degree of Protection The cabinets, degrees of protection and free space requirements of
and Free Space ACx 600 types are given below.
ACx 600 Enclosure Degree of Space above Space below Space on Space in
Type Protection5) left/right front/back
mm in mm in mm in mm in
601 wall-mounted metal IP 22/IP 541) 300 12 300 12 50/50 2/2 20/0 0.8/0
frame
6042) frame R7 IP 22 300 12 300 12 50/50 2/2 20/0 0.8/0
3)
604 frames R8 and R9 IP 00 400 16 0 0 0/50 0/2 100/0 4/0
4)
607/627/ Drives-MNS cabinet IP 21 /22 200 8 0 0 0 0 200/0 8/0
677 IP 42/54
1) not for R7 frame size (ACx 601-0100-3, -0120-3, -0120-5, -0140-5, -0100-6, -0120-6), not for ACP 601 units
2)
ACx 604-0100-3, -0120-3, -0120-5, -0140-5, -0100-6, -0120-6
3) ACx 604-0140-3 to -0320-3 & -0170-5 to -0400-5, -0140-6 to -0400-6
4) not for frame sizes 2R8 and 2R9
5)
The degrees of protection is specified by listing the IEC standard IP (Ingress Protection) number. The first digit of the IP number specifies
the protection against solid objects and dirt. The second digit specifies the protection against liquids. IP 00 is an open chassis. NEMA 1
enclosures are comparable to approximately IP 20 to IP 33. NEMA 3R enclosures are comparable to IP 32. NEMA 12 and NEMA 13
enclosures are comparable to IP 54 to IP 65. NEMA 4 enclosures are comparable to IP 65 or IP 66.
4 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
NIOC and NIOCP Data of the external control connection boards of the ACS 600 product
Board Specifications family are given below.
ACx = ACS/ACC/ACP 5
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
DDCS Fibre Optic Protocol: DDCS (ABB Distributed Drives Communication System)
Link
Modbus RS 485
Communication
Transmission Rate: Max. 9600 bit/s
Link
Parity: Selectable
Connectors: Shielded modular
telecommunication socket
6 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Encoder Signals at The diagram below shows typical encoder output waveforms. The
NIOCP encoder output channel that leads when the motor is turning forward
should be connected to input A of the NIOCP board terminal X8, the
output channel that trails to input B of the NIOCP board terminal X8.
WY WY
D D D D
9
$
9
%
WG
9
=
D D D D WG WY WY
9
$
9
%
WG
9
=
WG
ACx = ACS/ACC/ACP 7
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
ACS 600 Control Below are the ACS 600 standard control connections on the NIOC
Connections on the board. For the control connections of ACC and ACP see the firmware
NIOC Board manuals.
NIOC Board
Programmable I/O
(A2)
Factory Settings
X22
1 DI1 Stop/Start
1) If Par. 10.3 is REQUEST. 2 DI2 Forward/Reverse 1)
3 DI3 Not used
2)
Operation: 0 = Open, 1 = Closed 4 DI4 ACCEL/DECEL 1/2
DI 5 DI 6 Output 5 DI5 Constant speed select 2)
0 0 Set speed through AI1 6 DI6 Constant speed select 2)
1 0 Constant Speed 1 7 +24V +24 V d.c. max. 100 mA
0 1 Constant Speed 2 8 +24V
1 1 Constant Speed 3 9 DGND Digital Ground
X23
Connector X28 for RS 485 connection*
1 +24 V Auxiliary voltage output, non-isolated,
1 TRANS 2 GND 24 V d.c. 250 mA
Standard Modbus Link
2 GND
X25
3 B-
4 A+
1 RO11 Relay output 1
2 RO12 Ready
5 GND
6 +24 V 3 RO13
X26
Connector X29 for RS 485 connection*
1 RO21
1 TRANS Relay output 2
Standard Modbus Link 2 RO22
2 FAULT Running
3 RO23
3 B-
X27
4 A+
5 GND 1 R031 Relay output 3
6 +24 V Fault 2 R032 Fault (-1)
3 R033
* Connector shield is connected via RC filter to frame.
8 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
ACP 600 Control External control connections of ACP 600 with NIOCP board (and
Connections on the Speed Control Application Macro) are shown below. External control
NIOCP Board connections are different with other application macros (see Firmware
Manual). ACP 600 can be equipped with the NIOCP or with the NIOC
board.
Terminal Block X7
1 RO1 NCC
2 RO1 CM 1 Relay Output, READY Signal
3 RO1 NOC
ACx = ACS/ACC/ACP 9
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Application Program Various application programs are available for the ACS 600 frequency
converters. Not all selections are available for all types. One application
program at a time can be loaded in the memory of the frequency
converter. See below for the application programs and the application
macros included in them.
Application Macros The macros of the application programs are introduced below.
10 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
* This selection is for the North American market. The default parameter settings in the standard application macros
include minor changes to fulfil the local regulations, such as 3-wire start/stop.
ACx = ACS/ACC/ACP 11
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Protection Features Application program dependent features of the ACx 600 are listed
below. available as standard, optional. Not all selections are
available for all types. For more information refer to the appropriate
application program Firmware Manual.
Motion Control
Motion Control
MotionControl
Standard
PFC, M/F
Standard
PFC, M/F
Standard
PFC, M/F
Preprogrammed Programmable Programm.
System
System
System
Crane
Crane
Crane
Faults Fault Functions Supervision
Functions
12 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Applicable Standards The ACS 600 complies with the following standards:
EN 60204-1: 1992 + Corr. 1993 (IEC 204-1). Safety of machinery.
Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is
responsible for installing
- an emergency-stop device
- a supply disconnecting device (ACx 601 and ACx 604)
- the ACx 604 (IP 00) into a separate casing.
EN 60529: 1991 (IEC 529), IEC 664-1: 1992. Degrees of protection
provided by enclosures (IP code).
EN 61800-3 (1996): EMC product standard including specific test
methods.
AS/NZS 2064 (1997): Limits and methods of measurement of
electronic disturbance characteristics of industrial, scientific and
medical radiofrequency equipment. (ACS 600 complies with the
requirements given for class A equipment.) This standard is applied
in Australia and New Zealand.
Compliance with the EMC EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
Directive equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or system
within its locality.
The EMC Directive defines the requirements for immunity and emissions of electrical
equipment used in European Economic Area. The EMC product standard EN 61800-3
covers the requirements stated for frequency converters.
The ACx 601 and ACx 607/627/677 frequency converters comply with the EMC
Directive in industrial low-voltage network, public low-voltage network (restricted
distribution) and IT networks (unearthed mains) with the following provisions:
ACx = ACS/ACC/ACP 13
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Neighbouring network
Static screen
Point of measurement
Use of the ACx 601 or ACx 607/627/677 in Second Environment without EMC filtering
(EN 61800-3: second environment includes all establishments other than those directly
connected to a low-voltage power supply network which supplies buildings used for
domestic purposes.)
Table A-1 The EMC filtering of the ACx 601 or ACx 607/627 units is marked in the
type code as follows. * du/dt Filters + EMC Filters, ** du/dt Filters + No EMC Filters, ***
EMC Cabinet with EMC Filters.
Type Code
ACS 600 Type Character no. EMC Filter No EMC Filter
Selections Selections
ACS/ACC/ACP 601 ACxxxxxxxxxxxxxxxxxxxx 0 9
20
ACS/ACC/ACP 604 ACxxxxxxxxxxxxxxxxxxxx 0 9
20
ACS/ACC/ACP 607/627 ACxxxxxxxxxxxxxxxxxxxx 0, 3* 5**, 9
(up to -0610-3, -0760-5,
-0760-6)
20
ACS/ACC 607/627 (-0760-3, ACxxxxxxxxxxxxxxxxxxxxxxxxx... 1, 2*** 0,
-0930-5, -0900-6 or above)
26
ACS 600 MultiDrive ACA63xxxxxxxxxxxxx... 1, 2*** 0
Supply Section
16
Drive Section ACA610xxxxxxxxxxxx... 1 0
16
14 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Public Low-Voltage ACS/ACC 607/627 (-760-3, -0930-5, -0900-6 or above) nor ACx 677 types are not
Network designed for the public low-voltage nertworks.
Other ACx 601 or ACx 607/627 types:
1. The ACx 601 or ACx 607/627 is equipped with EMC filtering (refer to Table A-1).
2. The ACx 601 or ACx 607/627 is installed with motor and control cables as
specified in installation manual.
3. Maximum cable length is 100 metres.
Without considering the EMC requirements, do not use the ACx 601 or ACx 607/627
on a low voltage public network supplying domestic premises. This kind of use might
cause radio frequency interference.
Unearthed Mains 1. It is ensured that no excessive emission is propagated to neighbouring low-
(IT Network) voltage networks. In some cases, the natural suppression in transformers and
cables is sufficient. If in doubt, the supply transformer with static screening
between the primary and secondary windings can be used.
2. The ACx 601 or ACx 607/627/677 is installed with motor and control cables as
specified in installation manual.
Note: The ACx 601 or ACx 607/627 must not be equipped with EMC filtering (refer to
Table A-1) when installed to floating networks. The mains becomes connected to earth
potential through the EMC filter capacitors. In floating networks this may cause danger
or damage the unit.
Machinery Directive ACx 601 and ACx 604 and ACx 607/627/677 frequency converters comply with the
European Union Machinery Directive (89/392/EEC) requirements for an equipment
intended to be incorporated into machinery.
UL/CSA Markings The UL/CSA markings are required in North America. The UL/ULC/
CSA markings of the ACS 600 frequency converters are listed below
(x).
UL ACS 600 is suitable for use in a circuit capable of delivering not more than 65 kA rms
symmetrical amperes at 480 V maximum (500 V units), and at 600 V maximum (690 V
units).
ACS 600 provides overload protection in accordance with the National Electrical Code
(US). See ACS 600 Firmware Manual for setting. Default setting is off, must be
activated at start-up.
ACS 600 drives are to be used in a heated indoor controlled environment. See
subsection Ambient Conditions for specific limits.
ACS 600 brake chopper - ABB has brake chopper modules that, when applied with
appropriately sized braking resistors, will allow the drive to dissipate regenerative
ACx = ACS/ACC/ACP 15
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
C-tick Marking C-tick marking is required in Australia and New Zealand. A C-tick
mark is attached to ACx 601 and ACx 607 frequency converters to
verify that the unit follows the provisions of
Radiocommunications (Electromagnetic Compatibililty) Standard
1998
Radiocommunications (Compliance Labelling - Incidental
Emissions) Notice 1998
AS/NZS 2064: 1997. Limits and methods of measurement of
electronic disturbance characteristics of industrial, scientific and
medical (ISM) radiofrequency equipment.
Radiocommunication Regulations of New Zealand (1993).
Compliance with AS/ The above rules define the essential requirements for emissions of electrical
NZS 2064 equipment used in Australia and New Zealand. The standard AS/NZS 2064 (Limits and
methods of measurement of electronic disturbance characteristics of industrial,
scientific and medical radiofrequency equipment, 1997) covers the detailed
requirements for three-phase frequency converters.
The ACx 601 and ACx 607 frequency converters comply with AS/NZS 2064 for class A
equipment (suitable for use in all establishments other than domestic and those directly
connected to a low-voltage network which supplies buildings used for domestic
purposes). The compliance is valid with the following provisions:
1. The ACx 601 or ACx 607 is equipped with EMC filtering (refer to Table A-1).
2. The ACx 601 or ACx 607 is installed according to the instructions given in the
manual.
3. The motor and control cables are selected as specified in the manual.
4. Maximum cable length is 100 metres.
Note: The ACx 601 or ACx 607 must not be equipped with EMC filtering (refer to Table
A-1) when installed to IT networks. The mains becomes connected to earth potential
through the EMC filter capacitors. In IT networks this may cause danger or damage the
unit.
16 ACx = ACS/ACC/ACP
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
Materials The table below lists the enlosure and package materials.
Enclosure Package
hot-dip zink coated steel sheet 60 mm RAL 7035 Wood or plywood (seaworthy
ACx 604
Disposal ACx 601, ACx 604, and ACx 607/627/677 contain raw materials that
should be recycled, thus preserving energy and natural resources.
Package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or
burned under controlled circumstances, according to local regulations.
If recycling is not feasible, all parts excluding electrolytic capacitors can
be landfilled. The DC capacitors of the unit contain electrolyte which is
classified as hazardous waste. (Location of the electrolytic capacitors
is shown on a sticker in the back of the front cover, C11 to C13.) They
must be removed and handled according to local regulations.
For further information on environmental aspects, please contact your
local ABB distributor.
ACx = ACS/ACC/ACP 17
General Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9
18 ACx = ACS/ACC/ACP
ACx 601 Specific Technical Data
IEC Ratings The IEC ratings for ACS/ACC/ACP 601 with 50 Hz and 60 Hz supplies
are below. ACx = ACS/ACC/ACP. The 690 V series is not available for
ACP 600. Symbols are described below the table.
Normal Use Heavy-duty Use
Duty Cycle Duty Cycle Duty Cycle 1)
1/5 min 1/5 min 2/15 s
ACx 601 Frame
Type I2N I2Nmax SN PN PN I2hd I2hdmax I2hd I2hdmax Shd Phd Phd Type
4/5min 1/5min 4/5min 1/5min 13/15s 2/15s
[A] [A] [kVA] [kW] [HP] [A] [A] [A] [A] [kVA] [kW] [HP]
ACx = ACS/ACC/ACP 1
ACx 601 Specific Technical Data
Normal use (10 % overload capacity): Heavy-duty use (50 % or 100 % overload capacity):
I2N rated rms output current I2hd rated rms output current
I2Nmax rms overload current (allowed for one minute I2hdmax rms overload current (allowed for one minute
every 5 minutes): every 5 minutes or 2 seconds every 15
I2Nmax (1/5 min) = 1.1 I2N seconds). Maximum current depends on
parameter setting, refer to Firmware Manual.
I2Nmax (2/15 s) = 1.5 I2N (400 and 500 VAC I2hdmax (1/5 min) = 1.5 I2hd
units) I2hdmax (2/15 s) = 2.0 I2hd (400 and 500 VAC
units) or 1.5 I2hd (690 VAC units)
SN rated apparent output power Shd rated apparent output power
PN typical motor power. The power ratings in kW Phd typical motor power. The power ratings in kW
apply to most IEC 34 motors. The power apply to most IEC 34 motors. The power
ratings in HP apply to most four pole NEMA ratings in HP apply to most four pole NEMA
rated motors. rated motors.
2 ACx = ACS/ACC/ACP
ACx 601 Specific Technical Data
NEMA Ratings The NEMA ratings for ACS 601 with 60 Hz supply are below. Symbols
are described on previous page.
Normal Use Heavy-duty Use
Duty Cycle Duty Cycle Duty Cycle 1)
1/5 min 1/5 min 2/15 s
ACS 601 Frame
Type I2N I2Nmax PN I2hd I2hdmax I2hd I2hdmax Phd Type
4/5min 1/5min 4/5min 1/5min 13/15s 2/15s
[A] [A] [HP] [A] [A] [A] [A] [HP]
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS 601-0006-4 7.6 8.4 5 6.2 9.3 6.2 12.4 3 R2
ACS 601-0009-4 11 12 7.5 7.6 11 7.6 15.2 5
ACS 601-0011-4 15 17 10 11 17 11 22 7.5
ACS 601-0016-4 21 23 15 15 23 15 30 10 R3
ACS 601-0020-4 27 30 20 19 27 19 36 10
ACS 601-0025-4 34 37 25 24 36 24 48 15 R4
ACS 601-0030-4 41 45 30 31 47 31 62 20
ACS 601-0040-4 52 57 40 41 62 41 82 30 R5
ACS 601-0050-4 65 72 50 47 71 47 94 30
ACS 601-0060-4 77 85 60 58 87 58 116 40
ACS 601-0070-4 96 106 75 68 98 68 130 50 R6
ACS 601-0100-4 124 136 100 86 126 86 168 60
ACS 601-0120-4 156 172 125 113 168 113 224 75 R7
ACS 601-0140-4 180 198 150 141 203 141 270 100
Note: The US manufactured units are labelled to -4 types. The information in this manual concerning the corresponding -
5 type applies to them.
Output Current The output current is calculated by multiplying the current given in the
Temperature Derating rating table by the derating factor.
Temperature derating factor for degree of protection IP 21/22:
General rule: Above +40 C / +104 F (+35 C / +95 F for types
ACS 60x-0120-03 and ACS 60x-0140-5 with I2Nsq rating), the rated
output current is decreased 3.5 % for every additional 1 C / 1.8 F
(up to +50 C / +122 F).
Example 1. If the ambient temperature is 50 C / +122 F the
derating factor is
The output current is then 0.65 I2N , 0.65 I2hd or 0.65 I2Nsq.
Derating factor for ACx 601 with degree of protection IP 54:
From +25 C to +40 C, the output current is calculated using the
table below.
Above +40 C, the output current is decreased 3.5 % for every
additional 1 C (up to +50 C).
Example 1. If the ambient temperature is 38 C, the derating factor
for ACx 601-0006-3 is 95 % or 0.95 (Curve 2). The output current is
then 0.95 I2N.
ACx = ACS/ACC/ACP 3
ACx 601 Specific Technical Data
100 1
95 2
90
3
85 4
80 5
75
70
65
60
24 26 28 30 32 34 36 38 40
t ( C)
75 79 82 86 90 93 97 100 104
t ( F)
Curve 1
(100 % Curve 2 Curve 3 Curve 4 Curve 5
no derating)
ACx 601-0005-3 ACx 601-0006-3 ACx 601-0011-3 ACx 601-0009-3 ACx 601-0016-3
ACx 601-0006-5 ACx 601-0009-5 ACx 601-0020-3 ACx 601-0070-3 ACx 601-0020-5
ACx 601-0009-6 ACx 601-0016-6 ACx 601-0025-3 ACx 601-0011-5 ACx 601-0070-6
ACx 601-0025-5 ACx 601-0030-3 ACx 601-0100-5
ACx 601-0030-5 ACx 601-0040-3 ACx 601-0040-6
ACx 601-0040-5 ACx 601-0050-3 ACx 601-0050-6
ACx 601-0070-5 ACx 601-0060-3
ACx 601-0011-6 ACx 601-0016-5
ACx 601-0050-5
ACx 601-0060-5
ACx 601-0020-6
ACx 601-0025-6
ACx 601-0030-6
ACx 601-0060-6
4 ACx = ACS/ACC/ACP
ACx 601 Specific Technical Data
Fuses Recommended input fuse ratings of the ACx 601 are below.
2
A minimum rated current in amperes, A2s maximum I t value, V rated
voltage in volts.
Fuses
Type Type
DIN 43620 DIN 43653
ACx 601 Type A A2s V Manufacturer Size Size
ACx = ACS/ACC/ACP 5
ACx 601 Specific Technical Data
Cable Entries Mains and motor cable terminal sizes (per phase) and tightening
torques for the ACS/ACC/ACP 601 with cable diameters accepted by
the rubber glands are given below.
Cooling Air Flow Cooling air flow requirements are given below.
Requirements
6 ACx = ACS/ACC/ACP
ACx 601 Specific Technical Data
Cooling Air Duct Heat dissipations and cooling air flows of ACS/ACC/ACP 601 in a
cooling air duct installation are below.
Air flow out
Degree of Heat Dissipation Cooling Air Flow Out
Protection Heatsink Front Heatsink Front
IP 22 85 % 15 % 80 % 20 %
IP 54 90 % 10 % 100 % 0%
Air
in Max. 10 mm
Heatsink Front
Dimensions and Dimensions and weights of the wall-mounted ACS/ACC/ACP 601 units
Weights are given below.
L OC RES ET RE F
RE M
ACx = ACS/ACC/ACP 7
ACx 601 Specific Technical Data
Noise The noise values of the ACx 601 units are given in Table below.
8 ACx = ACS/ACC/ACP
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific
Technical Data
IEC Ratings The IEC ratings for ACx 604/624 and ACx 607/627 R7 to 2R9 with 50
Hz and 60 Hz supplies are below. ACx = ACS/ACC/ACP. See next page
for symbols.
ACx 6x4, ACx 6x7= The ratings are also valid for the corresponding 12 pulse units which have a doubled rectifying bridge
(type designations ACx 624 and ACx 627). The ACx 607/627 is housed in a cabinet. The ACx 604/627 is to be installed in
a cabinet by the user. The 690 V series and 2 x R8 and 2 x R9 frame sizes are not available for ACP 600.
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACx 604/607-0120-5 135 149 120 90 100 112 168 112 224 100 75 75 R7
ACx 604/607-0140-5 164 180 140 110 125 135 203 135 270 120 90 100
ACx 604/607-0170-5 200 220 170 132 150 164 246 164 328 140 110 125 R8
ACx 604/607-0210-5 240 264 210 160 200 200 300 200 400 170 132 150
ACx 604/607-0260-5 300 330 260 200 250 240 360 240 480 210 160 200
ACx 604/607-0320-5 365 402 320 250 300 300 450 300 600 260 200 250 R9
ACx 604/607-0400-5 460 506 400 315 350 365 548 365 730 320 250 300
ACx 6x4/6x7-0490-5 570 627 490 400 500 456 684 456 912 400 315 400 2xR8
ACx 6x4/6x7-0610-5 694 764 610 500 600 570 855 570 1140 490 400 500 2xR9
ACx 6x4/6x7-0760-5 874 961 760 630 700 694 1041 694 1388 610 500 600
ACx = ACS/ACC/ACP 1
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Pump and Fan The current ratings are the same regardless of the supply voltage
Use (Squared within one voltage range. The rated current of the ACx 60x must
Load) be higher than or equal to the rated motor current to achieve the
rated motor power given in the table.
ACS 604/607 I2Nsq PN Frame
Type Size Note 1: The maximum allowed motor shaft power is limited to 1.5
[A] [kW] Phd. If the limit are exceeded, the motor torque and the I2hdmax
2/15 s current is automatically restricted. The function protects the
Three-phase supply voltage 380 V, 400 V or input bridge of the ACS 600 against overload.
415 V
ACS 604/607-0100-3 178 90 R7 Note 2: The load capacity (current and power) decreases if the
ACS 604/607-0120-3 200 110 (100) installation site altitude exceeds 1000 metres, or if the ambient
ACS 604/607-0140-3 260 132 R8 temperature exceeds 40 C (or 35 C with ACx 60x-0120-03 and
ACS 604/607-0170-3 300 160 ACx 60x-0140-05 units in Pump and Fan Use). See Output
ACS 604/607-0210-3 375 200 Current Temperature Derating on page 3.
ACS 604/607-0260-3 480 250 R9
ACS 604/607-0320-3 510 315 (265)
ACS 6x4/6x7-0400-3 712 400 2xR8 Note 3: The Pump and Fan rating is not to be used with du/dt
ACS 6x4/6x7-0490-3 912 500 2xR9 filters. du/dt filters are usually needed at the output of 525 V to
ACS 6x4/6x7-0610-3 969 560 690 V units with random wound motors. No du/dt filters are usually
required with form wound motors.
Three-phase supply voltage 380 V, 400 V,
415 V, 440 V, 460 V, 480 V or 500 V
ACS 604/607-0120-5 164 110 R7 Notes concerning Pump and Fan Use only
ACS 604/607-0140-5 193 132
ACS 604/607-0170-5 240 160 R8 Pump and Fan rating is available for ACS 600 with Standard and
ACS 604/607-0210-5 285 200 Pump and Fan Control Application Programs.
ACS 604/607-0260-5 345 250
ACS 604/607-0320-5 460 315 R9 ( ) typically achieved motor power with I2Nsq
ACS 604/607-0400-5 490 400 (335)
ACS 6x4/6x7-0490-5 656 450 2xR8
ACS 6x4/6x7-0610-5 874 630 2xR9
ACS 60x4/6x7-0760-5 990 710
Normal use (10 % overload capacity): Heavy-duty use (50 % or 100 % overload capacity):
I2N rated rms output current I2hd rated rms output current
I2Nmax rms overload current (allowed for one minute I2hdmax rms overload current (allowed for one minute
every 5 minutes): every 5 minutes or 2 seconds every 15
I2Nmax (1/5 min) = 1.1 I2N seconds). Maximum current depends on
parameter setting, refer to Firmware Manual.
I2Nmax (2/15 s) = 1.5 I2N (400 and 500 VAC I2hdmax (1/5 min) = 1.5 I2hd
units) I2hdmax (2/15 s) = 2.0 I2hd (400 and 500 VAC
units) or 1.5 I2hd (690 VAC units)
SN rated apparent output power Shd rated apparent output power
PN typical motor power. The power ratings in kW Phd typical motor power. The power ratings in kW
apply to most IEC 34 motors. The power apply to most IEC 34 motors. The power
ratings in HP apply to most four pole NEMA ratings in HP apply to most four pole NEMA
rated motors. rated motors.
2 ACx = ACS/ACC/ACP
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
NEMA Ratings The NEMA ratings for ACS 604 and ACS 607 with 60 Hz supply are
below. Symbols are described on the previous page.
Normal Use Heavy-duty Use
Duty Cycle Duty Cycle Duty Cycle 1)
1/5 min 1/5 min 2/15 s
ACS 604/607 Frame
Type I2N I2Nmax PN I2hd I2hdmax I2hd I2hdmax Phd Size
4/5min 1/5min 4/5min 1/5min 13/15s 2/15s
[A] [A] [HP] [A] [A] [A] [A] [HP]
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS 604/607-0120-4 156 172 125 113 168 113 224 75 R7
ACS 604/607-0140-4 180 198 150 141 203 141 270 100
ACS 604/607-0170-4 216 238 150 172 246 172 328 125 R8
ACS 604/607-0210-4 260 286 200 200 300 200 400 150
ACS 604/607-0260-4 316 348 250 240 360 240 480 200
ACS 604/607-0320-4 414 455 300/350 300 450 300 600 250 R9
ACS 604/607-0400-4 480 528 400 365 548 365 730 300
Note: The US manufactured units are labelled to -4 types. The information in this manual concerning the corresponding
-5 type applies to them.
Output Current The output current is calculated by multiplying the current given in the
Temperature Derating rating table by the derating factor.
General rule: Above +40 C / +104 F (+35 C / +95 F for types
ACS 60x-0120-03 and ACS 60x-0140-3 with I2Nsq rating), the rated
output current is decreased 1.5 % for every additional 1 C / 1.8 F
(up to +50 C / +122 F). This applies to I2N and I2Nsq (for I2hd no
derating is needed).
Example 1. If the ambient temperature is 50 C / +122 F the derating
factor is
ACx = ACS/ACC/ACP 3
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Fuses Input fuse ratings of the ACxP 607/627 and recommended input fuse
ratings of the ACx 604/624 are below. A minimum rated current in
amperes, A2s maximum I2t value, V rated voltage in volts. Only ultra
rapid fuses guarantee proper protection for the rectifier
semiconductors.
Fuses
Type Type
ACx 604/624
DIN 43620 DIN 43653
ACx 6207/627
A A2s V Manufacturer Size Size
Types
Note: Fuses from other manufacturers can be used if they meet the ratings given in the table. Only ultra rapid fuses guar-
antee proper protection for the rectifier semiconductors. The fuses recommended in the table are UL R/C (JFRHRZ)
fuses.
Example: For ACS 604-0260-3, the recommended fuses for the input bridge protection are 700 A ultrarapid fuses.
The values I2N, I2hd and I2Nsq for ACS 604-0260-3 are 395 A, 316 A and 480 A respectively. 1.1 395 A = 434.5 A and
1.5 316 A = 474 A and 1.0 480 A = 480 A. Normal fuses with nominal currents higher than 434.5 A, 474 A or 480 A can
be used to protect the input cable; thus, 450 A or 500 A fuses are selected depending on the use (normal, heavy-duty or
pump and fan, respectively).
4 ACx = ACS/ACC/ACP
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Cable Entries Input power and motor cable terminal wire size capabilities and
tightening torques for the ACx 604/624 and ACx 607/627 are in the
table below.
The capability is specified based on wire lug that the terminal accepts
(according to DIN 46234 for copper cables and DIN 46329 for
aluminium cables), cable cross section that will fit through the
European lead-through plate hole, and maximum electrically needed
European cable cross section. NEMA two hole lugs (1/2 inch in
diameter and 1.75 inches on center) can be used in frame sizes R8
and R9 and R7 output.
NEMA two hole lugs (1/2 inch in diameter and 1.75 inches on center)
can be used in frame sizes R8 and R9 and R7 output.
ACx = ACS/ACC/ACP 5
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Terminal Sizes and Input power and motor cable terminal wire size capabilities (per phase)
Tightening Torques and tightening torques for the ACx 604/624 and ACx 604/607 are
below. For terms used see above. T = Tightening torgue.
Earthing
Mains Terminals Motor Terminals Cabinet
Terminals
ACx 600 (Frame)
Type U1,V1,W1 T U2,V2,W2 T Earthing T
Cu Al Nm Cu Al PE
ACx 607/627
-0100-3/0120-5/0100-6 1x120 3) 1x120 3) 30 1x(12-120) 1x(12-120) 30 M12 30 MNS (R7)
3) 3)
-0120-3/0140-5/0120-6 1x185 1x185 22 1x(12-185) 1x(12-185) 30 M12 30
-0140-3/0170-5/0140-6 2x(12-185) 2x(12-185) 44 2x(12-185) 2x(12-185) 44 M12 30 MNS (R8)
6 ACx = ACS/ACC/ACP
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Cooling Air Flow Heat loss and cooling air flow requirements are given below.
Requirements
ACx 604/624 and ACx 607/627 Type Heat Loss / kW
0100-3 0100-6 1.9
0120-3 0120-5 0120-6 2.3
0140-3 0140-5 0140-6 2.8
0170-3 0170-5 0170-6 3.3
0210-3 0210-5 0210-6 4.0
0260-3 0260-5 0260-6 5.0
0320-3 0320-5 0320-6 6.3
-0400-3 0400-5 0400-6 7.9
-0490-3 -0490-5 -0490-6 10.0
-0610-3 7-0610-5 -0610-6 12.5
-0760-5 -0760-6 15.8
Dimensions and Dimensions and weights of the ACx 604/624s are given below.
Weights (ACx 604/624)
Height Width Depth Weight
ACS 604/624 Type
mm (in) mm (in) mm (in) kg (lbs)
0100-3 0120-5 0100-6 860 (33.86) 480 (18.89) 428 (16.85) 88 (194)
0120-3 0140-5 0120-6 860 (33.86) 480 (18.89) 428 (16.85) 88 (194)
0140-3 0170-5 0140-6/ 1250 (49.2) 462*/524 407 (16) 135 (297)
0170-6 (18.19/20.63)
0170-3 0210-5 0210-6 1250 (49.2) 462*/524 407 (16) 140 (308)
(18.19/20.63)
0210-3 0260-5 0260-6 1250 (49.2) 462*/524 407 (16) 140 (308)
(18.19/20.63)
0260-3 1600 (63) 462*/524 407 (16) 166 (365)
(18.19/20.63)
0320-3 1600 (63) 462*/524 407 (16) 166 (365)
(18.19/20.63)
0320-5 0320-6 1600 (63) 462*/524 407 (16) 171 (376)
(18.19/20.63)
0400-5 0400-6 1600 (63) 462*/524 407 (16) 171 (376)
(18.19/20.63)
0400-3 0490-5 0490-6 2 x Dimensions of ACx 604-0210-3
0490-3 0610-5 0610-6 2 x Dimensions of ACx 604-0260-3
0610-3 0760-5 0760-6 2 x Dimensions of ACx 604-0320-3
Width marked with * does not include motor cable terminals, PE terminal or DC bus
terminals.
ACx = ACS/ACC/ACP 7
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Dimensions and Dimensions and weights of the ACx 607/627s are given below.
Weights (ACx 607/627)
Height 1) Width Depth Weight 4)
ACx 607/627 Type
mm (in) mm (in) mm (in) kg (lbs)
0100-3 0120-5 0100-6 20781)/23162) 830 644 275/3005)
(81.8)/(91.2) (32.7) (25.35) (605)/(660)
0120-3 0140-5 0120-6 20781)/23162) 830 644 275/3005)
(81.8)/(91.2) (32.7) (25.35) (605)/(660)
0140-3 0170-5 0140-6/ 20781)/23162) 830/12303) 644 340/3905)
0170-6 (81.8)/(91.2) (32.7)/(48.4) (25.35) (748)/(858)
0170-3 0210-5 0210-6 20781)/23162) 830/12303) 644 345/3905)
(81.8)/(91.2) (32.7)/(48.4) (25.35) (749)/(858)
0210-3 0260-5 0260-6 20781)/23162) 830/12303) 644 345/3905)
(81.8)/(91.2) (32.7)/(48.4) (25.35) (749)/(858)
0260-3 20781)/23162) 830/12303) 644 370
(81.8)/(91.2) (32.7)/(48.4) (25.35) (814)
0320-3 20781)/23162) 830/12303) 644 370
(81.8)/(91.2) (32.7)/(48.4) (25.35) (814)
0320-5 0320-6 20781)/23162) 830/12303) 644 375/4355)
(81.8)/(91.2) (32.7)/(48.4) (25.35) (825)/(957)
0400-5 0400-6 20781)/23162) 830/12303) 644 375/4355)
(81.8)/(91.2) (32.7)/(48.4) (25.35) (825)/(957)
0400-3 0490-5 0490-6 20781)/22152) 21306) 644 710
(87.3)/(87.2) (83.9) (25.35) (1562)
0490-3 0610-5 0610-6 20781)/2215)2) 21306) 644 870
(87.3)/(87.2) (83.9) (25.35) (1914)
0610-3 0760-5 0760-6 20781)/22152) 21306) 644 870
(87.3)/(87.2) (83.9) (25.35) (1914)
1) 2)
Height of bottom entry/exit, degree of pro- Degree of protection IP 54
3)
tection IP 21 / IP 22 / IP 42. Heights EMC Line Filter version
include the lifting lugs. Hight of top entry/ 4)
Weight of the IP 21 / IP 22 / IP 42 version
exit is 2132 (83.9 in). 5)
Weight of the 690 V unit with du/dt filter
8 ACx = ACS/ACC/ACP
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
Braking Chopper The widths of ACx 607/627 units with braking choppers are below.
ACx
Width with Width with ACS 607 Width with Width with ACS 607 Width with Width with
607/627
Braking Braking Type Braking Braking Type Braking Braking
Type
Chopper Chopper and Chopper Chopper and Chopper Chopper and
Resistor(s) Resistor(s) Resistor(s)
0100-3 830 (32.7) 1230 (48.4) 0120-5 830 (32.7) 1230 (48.4) 0100-6 830 (32.7) 1230 (48.4)
0120-3 830 (32.7) 1230 (48.4) 0140-5 830 (32.7) 1230 (48.4) 0120-6 830 (32.7) 1230 (48.4)
0140-3 1230 (48.4) 1230 (48.4) 0170-5 1230 (48.4) 1230 (48.4) 0140-6 1230 (48.4) 1230 (48.4)
0170-3 1230 (48.4) 1530 (60.2) 0210-5 1230 (48.4) 1230 (48.4) 0170-6 1230 (48.4) 1230 (48.4)
0210-3 1230 (48.4) 1530 (60.2) 0260-5 1230 (48.4) 1530 (60.2) 0210-6 1230 (48.4) 1230 (48.4)
0260-3 1230 (48.4) 1530 (60.2) 0320-5 1230 (48.4) 1530 (60.2) 0260-6 1230 (48.4) 1530 (60.2)
0320-3 1230 (48.4) 1530 (60.2) 0400-5 1230 (48.4) 1530 (60.2) 0320-6 1230 (48.4) 1530 (60.2)
0400-3 2930 (115.4) 3530 (139) 0490-5 2930 (115.4) 3530 (139) 0400-6 1230 (48.4) 1530 (60.2)
0490-3 2930 (115.4) 3530 (139) 0610-5 2930 (115.4) 3530 (139) 0490-6 2930 (115.4) 3530 (139)
0610-3 2930 (115.4) 3530 (139) 0760-5 2930 (115.4) 3530 (139) 0610-6 2930 (115.4) 3530 (139)
0760-6 2930 (115.4) 3530 (139)
Noise The noise values of the ACx 604/624 and 607/627 units are given in
Table below.
ACx = ACS/ACC/ACP 9
ACx 604/624 and ACx 607/627 R7 to 2R9 Specific Technical Data
10 ACx = ACS/ACC/ACP
Technical Data ACS/ACC 607/627 R11i to 4R11i,
ACx 617 and ACx 677
ACx = ACS/ACC 1
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Frequency Drive Normal Use Duty Cycle 1/5min Duty Cycle 10/60s
Converter Frame I S P I I I I
2N N N 2hd 2hd 2hd 2hd
Type Size
4/5min 1/5min 50/60s 10/60s
[A] [kVA] [kW] [A] [A] [A] [A]
Supply voltage range 525, 550, 575, 600, 660 or 690 V
ACx 617/677-0205-6 R8i 176 205 160 132 198 127 254
ACx 617/677-0255-6 R8i 210 255 200 158 236 150 300
ACx 617/677-0315-6 R8i 264 315 250 198 297 179 358
ACx 617/677-0375-6 R9i 310 375 315 233 349 225 450
ACx 617/677-0485-6 R9i 410 485 400 308 461 265 530
ACx 617/677-0600-6 R10i 502 600 500 377 565 340 680
ACx 617/677-0750-6 R11i 630 750 630 473 709 428 856
ACx 607/617/627/677-0900-5 R11i 755 900 710 566 849 504 1008
ACx 607/617/627/677-1090/1095-5 R12i 874 1040/1045 800 656 983 641 1282
ACx 607/617/627/677-1380/1385-5 R12i 1156 1380/1385 1120 867 1301 755 1510
ACx 607/627/677-1710-6 2xR11i 1435 1710 1400 1076 1614 1007 2014
ACx 607/627/677-2120-6 2xR12i 1777 2120 1800 1333 1999 1283 2566
ACx 607/627/677-2540-6 2xR12i 2129 2540 2000 1597 2395 1511 3022
ACx 607/627/677-2800-6 4xR11i 2344 2800 2300 1758 2637 1710 3420
ACx 607/627/677-3350-6 4xR11i 2809 3350 2800 2107 3160 2014 4028
The current ratings are the same regardless of the supply voltage within one voltage range. The rated current of the
ACx 600 must be higher than or equal to the rated motor current to achieve the rated motor power given in the table.
Note 1: The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres, or if the
ambient temperature exceeds 40 C (units with degree of protection IP 21/22/42/54).
Note 2: Usually du/dt filters are needed at the output of 525 V to 690 V units with random wound motors. No du/dt filters
are usually required with form wound motors.
Note 3: For units with regenerative braking, the ratings are 90 percent of the values given in the table.
2 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Output Current The output current is calculated by multiplying the current given in the
Temperature Derating rating table by the derating factor.
Temperature derating factor for degree of protection IP 21/22/42/54:
General rule: Above +40 C, the rated output current is decreased
1.5 % for every additional 1 C (up to +50 C).
Example 1: If the ambient temperature is 50 C the derating factor is
100 % - 1.5 %C 10 C = 85 % or 0.85. The output current is then
0.85 I2N or I2hd.
Current (%)
100
-1.5 % per each + C
95
IP 21/22/42/54
90
85
IP 54R
80
36 40 44 48 52 T (C)
Derating Diagram: the effect of ambient temperature on the ACx 607, ACx 617 and
ACx 677 continuous load capacity.
ACx = ACS/ACC 3
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
4 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Ambient Conditions Environmental limits of the ACx 607, ACx 617 and ACx 677 frequency
converters are given below. The frequency converters are to be used in
a heated, indoor, controlled environment.
2)
See subsection Output Current Temperature Derating.
ACx = ACS/ACC 5
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Fuses Only ultra rapid fuses guarantee proper protection for the rectifier
semiconductors.
AC Fuses The a.c. fuses (Bussmann) used in the supply section of the ACx 607,
and ACx 677 are listed below. The a.c. fuses for the ACx 617 types are
given in the IGBT Supply Sections Users Manual. See the IGBT supply
types from the dimension table given in the subsection Cooling Air,
Dimensions.
6 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Branch Fuses The branch fuses (Bussmann) used in the supply section of the
ACx 607 and ACx 677 are listed below.
Drive Section DC Fuses The Bussmann fuses used in the inverters of the ACx 607, ACx 617
and ACx 677 are listed below. UN and IN are nominal voltage and
current of the fuse.
Braking Section DC The d.c. fuses (Bussmann) for the braking sections are listed below.
Fuses
ACx 607, ACx 617 or ACx 677 Dynamic Braking Section Fuse
Type UN (V) IN (A) Type Size
-0760-3...-2820-3 ACA 622-0320-3...-1920-3 10001250 630 170M 5146 2/110
-0930-5...-3450-5 ACA 622-0400-5...-2400-5 10001250 630 170M 5146 2/110
-0900-6...3350-6 ACA 622-0400-6...-2400-6 10001250 630 170M 5146 2/110
PDM code 00025310-A
ACx = ACS/ACC 7
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Cable Entries
Tightening Torque The tightening torques for screw connections, applicable to zinc and
chrome platings and screw strength class 8.8 are listed below.
Screw Torque (Nm) *
Soft aluminium Alloyed aluminium and copper
M5 3.5 3.5
M6 6 9
M8 17 20
M10 35 40
M12 55 70
M16 130 180
8x(13x18)
Number of connection
holes in terminal
Connection hole (or max. screw) diameter in mm
Note: Cable lugs can also be fastened using screws one size down from the hole
size. Example: A cable lug with a hole diameter of 12.5 mm can be fastened with
either a M12 or a M10 bolt.
8 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Diode Supply Sections The largest cable core and cable lug sizes accepted by the diode
supply sections are presented below.
Type Holes for cable No. of cable Bottom plate No. of cable Holes for bus
lugs per phase entries at bottom opening dimen- entries at top duct connection
(diameter 60 mm) sions (diameter 60 mm)
(mm)
UN = 400V (380V...415V)
ACx 627-0760- 4x14 2x6 502x280 (2 pcs) 2x6 -
ACx 607-0760- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-0930- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-0930- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1120- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-1120- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1140- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-1140- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-1770- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-1770- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2140- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-2140- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2340- 12x(13x18) 2x18 502x280 (2 pcs) 2x18 4x(13x24)
ACx 627-2820- 12x(13x18) 2x18 502x280 (2 pcs) 2x18 4x(13x24)
UN = 500V (380V...500V)
ACx 627-930-5 4x14 2x6 502x280 (2 pcs) 2x6 -
ACx 607-0930- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1090- 4x14 2x6 502x280 (2 pcs) 2x6 -
ACx 607-1090- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1380- 8x(13x18) 2x12 502x280 (2 pcs) 12 4x(13x24)
ACx 607-1380- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1760- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-1760- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2160- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-2160- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2620- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-2620- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2850- 12x(13x18) 2x18 502x280 (2 pcs) 2x18 4x(13x24)
ACx 627-3450- 12x(13x18) 2x18 502x280 (2 pcs) 2x18 4x(13x24)
UN = 690V (525V...690V)
ACx 627-0900- 4x14 2x6 502x280 (2 pcs) 2x6 -
ACx 607-0900- 4x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1040- 4x14 2x6 502x280 (2 pcs) 2x6 -
ACx 607-1040- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 607-1380- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-1380- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 627-1710- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-1710- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2120- 8x(13x18) 12 502x280 12 4x(13x24)
ACx 607-2120- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2540- 8x(13x18) 2x12 502x280 (2 pcs) 2x12 4x(13x24)
ACx 607-2540- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-2800- 12x(13x18) 2x18 502x280 (2 pcs) 2x18 4x(13x24)
ACx 607-2800- 12x(13x18) 18 502x280 18 4x(13x24)
ACx 627-3350- 12x(13x18) 2x18 502x280 (2 pcs) 2x18 4x(13x24)
ACx 607-3350- 12x(13x18) 18 502x280 18 4x(13x24)
ACx = ACS/ACC 9
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Thyristor Supply The largest cable core and cable lug sizes accepted by regenerative
Section thyristor supply sections are presented below.
Type Holes for cable Number of cable Bottom plate Number of cable Holes for bus
lugs per phase entries at bottom opening dimen- entries at top duct connection
(diameter 60 mm) sions (diameter 60 mm)
(mm)
UN = 400V (380V...415V)
ACx 677-0185-3 2x14 3 310x240 3 -
ACx 677-0225-3 4x14 6 502x280 6 -
ACx 677-0265-3
ACx 677-0335-3
ACx 677-0405-3
ACx 677-0500-3 4x(13x18) 12 502x280 12 4x(13x24)
ACx 677-0630-3
ACx 677-0760-3 8x(13x18) 12 502x280 12 4x(13x24)
ACx 677-0930-3
ACx 677-1120-3
ACx 677-1440-3 12x(13x18) 18 502x280 18 4x(13x24)
ACx 677-1770-3
ACx 677-2140-3 12x(13x18) 18 502x280 18 4x(13x24)
UN = 500V (380V...500V)
ACx 677-0215-5 2x14 3 310x240 3 -
ACx 677-0255-5
ACx 677-0325-5 4x14 6 502x280 6 -
ACx 677-0395-5
ACx 677-0495-5
ACx 677-0610-5 4x(13x18) 12 502x280 12 4x(13x24)
ACx 677-0770-5
ACx 677-0930-5 8x(13x18) 12 502x280 12 4x(13x24)
ACx 677-1040-5
ACx 677-1380-5
ACx 677-1760-5 12x(13x18) 18 502x280 18 4x(13x24)
ACx 677-2160-5
ACx 677-2620-5 12x(13x18) 18 502x280 18 4x(13x24)
UN = 690V (525V...690V)
ACx 677-0205-6 2x14 3 310x240 3 -
ACx 677-0255-6
ACx 677-0315-6 4x14 6 502x280 6 -
ACx 677-0375-6
ACx 677-0485-6
ACx 677-0600-6 4x(13x18) 12 502x280 12 4x(13x24)
ACx 677-0750-6
ACx 677-0900-6 4x(13x18) 12 502x280 12 4x(13x24)
ACx 677-1040-6 8x(13x18) 12 502x280 12 4x(13x24)
ACx 677-1380-6
ACx 677-1710-6 12x(13x18) 18 502x280 18 4x(13x24)
ACx 677-2120-6
ACx 677-2540-6
ACx 677-2800-6 12x(13x18) 18 502x280 18 4x(13x24)
ACx 677-3350-6
10 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
IGBT Supply Section The largest cable core and cable lug sizes accepted by IGBT thyristor
supply sections are given in the IGBT Supply Section Users Manual
(EN code: 64013700).
Drive Sections The largest cable core and cable lug sizes accepted by drive sections
are presented below.
ACx 607, Holes for cable lugs No. of cable entries at Bottom plate opening No. of cable entries at
ACx 617 or per phase bottom (diameter dimensions top (diameter 60 mm)
ACx 677 60 mm) (mm)
999
ACx = ACS/ACC 11
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
External Control For the external control connections see the subsection ACS 600
Connection Diagrams Control Connections on the NIOC Board in General Technical Data
ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9.
External control wiring is connected to terminals on the NIOC board
through a terminal block X2 (IEC standard designation) or an optional
terminal block 2TB (ANSI standard designation, for US manufactured
units only). For the terminal markings see the Hardware Manual (EN
code: 61329005)
NIOC Board For the specification of the Standard I/O Control Board, NIOC, see
Specifications subsection NIOC and NIOCP Board Specifications in General
Technical Data ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9.
Cabinet Below are the cabinets, degrees of protection and free space
requirements of ACx 607, ACx 617 and ACx 677 types.
Cabinet Degree of Space Space Space on Space in
Protection above below left/right front/back
mm mm mm mm
Drives-MNS cabinet / IP 21, IP 22, 500 0 0 200/1002)
Common cabinet IP 42, IP 54,
IP 54 R 1)
1)
IP 21 = standard, R = air outlet duct
2)
200 between cabinets when installed back to back
Note: The additional space requirement for the door opening is 800 mm
Drive Section The frequency converter types contain inverters given below.
Hardware Frequency Converter Type Inverter Drive Frame Size
Supply voltage 380, 400 or 415V
ACx 617/677-0185-3 ACN 634-0185-3 R8i
ACx 617/677-0225-3 ACN 634-0225-3 R8i
ACx 617/677-0265-3 ACN 634-0265-3 R8i
ACx 617/677-0335-3 ACN 634-0335-3 R9i
ACx 617/677-0405-3 ACN 634-0405-3 R9i
ACx 617/677-0500-3 ACN 634-0500-3 R10i
ACx 617/677-0630-3 ACN 634-0630-3 R11i
ACx 607/617/627/677-0760/0765-3 ACN 634-0755-3 R11i
ACx 607/617/627/677-0930/0935-3 ACN 634-0935-3 R12i
ACx 607/617/627/677-1120/1125-3 ACN 634-1125-3 R12i
ACx 607/627/677-1440-3 ACN 634-1445-3 2xR11i
ACx 607/627/677-1770-3 ACN 634-1775-3 2xR12i
ACx 607/627/677-2140-3 ACN 634-2145-3 2xR12i
ACx 627-2340-3 ACN 634-2345-3 4xR11i
ACx 627-2820-3 ACN 634-2825-3 4xR11i
Supply voltage 380, 400, 415, 440, 460, 480 or 500V
ACx 617/677-0215-5 ACN 634-0215-5 R8i
ACx 617/677-0255-5 ACN 634-0255-5 R8i
ACx 617/677-0325-5 ACN 634-0325-5 R8i
ACx 617/677-0395-5 ACN 634-0395-5 R9i
12 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Cooling Air, Below are the heights and depths of ACx 607, ACx 617, ACx 627 and
Dimensions ACx 677.
ACx = ACS/ACC 13
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
14 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Frequency IGBT Supply Section Drive Air Flow Heat Width Weight
Converter Frame Type Frame [m3/h] Loss [mm] [kg]
Type Size Type [kW]
Supply voltage 400V IGBT Supply
ACx 617-0185-3 R8i ACA 635-0265-3 R8i 3850 7.7 2600 900
ACx 617-0225-3 R8i ACA 635-0265-3 R8i 3850 9.6 2600 900
ACx 617-0265-3 R8i ACA 635-0265-3 R8i 3850 11.7 2600 900
ACx 617-0335-3 R9i ACA 635-0405-3 R9i 3850 14.5 2800 970
ACx 617-0405-3 R9i ACA 635-0405-3 R9i 3850 18 2800 970
ACx 617-0500-3 R10i ACA 635-0500-3 R10i 7750 12.5 3800 1550
ACx 617-0630-3 R11i ACA 635-0765-3 R11i 7750 26 4200 1730
ACx 617-0765-3 R11i ACA 635-0765-3 R11i 7750 32 4200 1730
ACx 617-0935-3 R12i ACA 635-1125-3 R12i 10850 39 5200 2800
ACx 617-1125-3 R12i ACA 635-1125-3 R12i 10850 48 5200 2800
Supply voltage 500V IGBT Supply
ACx 617-0215-5 R8i ACA 635-0325-5 R8i 3850 9.0 2600 900
ACx 617-0255-5 R8i ACA 635-0325-5 R8i 3850 10.9 2600 900
ACx 617-0325-5 R8i ACA 635-0325-5 R8i 3850 14.4 2600 900
ACx 617-0395-5 R9i ACA 635-0495-5 R9i 3850 17 2800 970
ACx 617-0495-5 R9i ACA 635-0495-5 R9i 3850 22 2800 970
ACx 617-0610-5 R10i ACA 635-1610-5 R10i 7750 28 3800 1550
ACx 617-0770-5 R11i ACA 635-0935-5 R11i 7750 32 4200 1730
ACx 617-0935-5 R11i ACA 635-0935-5 R11i 7750 40 4200 1730
ACx 617-1090-5 R12i ACA 635-1385-5 R12i 10850 43 5200 2800
ACx 617-1385-5 R12i ACA 635-1385-5 R12i 10850 59 5200 2800
Supply voltage 690V IGBT Supply
ACx 617-0205-6 R8i ACA 635-0315-6 R8i 3850 8.7 2600 900
ACx 617-0255-6 R8i ACA 635-0315-6 R8i 3850 10.9 2600 900
ACx 617-0315-6 R8i ACA 635-0315-6 R8i 3850 14.0 2600 900
ACx 617-0375-6 R9i ACA 635-0485-6 R9i 3850 16 2800 970
ACx 617-0485-6 R9i ACA 635-0485-6 R9i 3850 22.1 2800 970
ACx 617-0600-6 R10i ACA 635-0600-6 R10i 7750 27.0 3800 1550
ACx 617-0750-6 R11i ACA 635-0900-6 R11i 7750 31.0 4200 1730
ACx 617-0900-6 R11i ACA 635-0900-6 R11i 7750 38.0 4200 1730
ACx 617-1045-6 R12i ACA 635-1385-6 R12i 10850 42.0 5200 2800
ACx 617-1385-6 R12i ACA 635-1385-6 R12i 10850 59.0 5200 2800
ACx = ACS/ACC 15
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
16 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
ACx = ACS/ACC 17
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Noise The noise values of the ACx 607, ACx 617, ACx 627 and ACx 677 units
are given below.
Type Noise Type Noise Type Noise
(dB) (dB) (dB)
ACx 617-0185-3 65 ACx 617-0215-5 65 ACx 617-0205-6 65
ACx 617-0225-3 65 ACx 617-0255-5 65 ACx 617-0255-6 65
ACx 617-0265-3 65 ACx 617-0325-5 65 ACx 617-0315-6 65
ACx 617-0335-3 65 ACx 617-0395-5 65 ACx 617-0375-6 65
ACx 617-0405-3 65 ACx 617-0495-5 65 ACx 617-0485-6 65
ACx 617-0500-3 70 ACx 617-0610-5 70 ACx 617-0600-6 70
ACx 617-0630-3 70 ACx 617-0770-5 70 ACx 617-0750-6 70
ACx 617-0765-3 70 ACx 617-0935-5 70 ACx 617-0900-6 70
ACx 617-0935-3 73 ACx 617-1090-5 73 ACx 617-1045-6 73
ACx 617-1125-3 73 ACx 617-1385-5 73 ACx 617-1385-6 73
18 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Dynamic Braking Below are Dynamic Braking Sections for the ACx 607, ACx 627,
ACx 617, ACx 627 and ACx 677.
ACx 607, ACx 617 Dynamic Section Chopper Resistor
ACx 627 or Braking Width (mm) Type
ACx 677
Type Rmin Er Pbr,max
Section Type (ohm) (kJ) (kW)
Supply voltage 400V
-0760-3 ACA 622-0960-3 3x(400+800) 3xNBRA-659 3x(2xSAFUR180F460) 3x(1.20) 36000 1060
-0930-3 ACA 622-0960-3 3x(400+800) 3xNBRA-659 3x(2xSAFUR180F460) 3x(1.20) 36000 1060
-1120-3 ACA 622-1280-3 4x(400+800) 4xNBRA-659 4x(2xSAFUR180F460) 4x(1.20) 48000 1411
-1440-3 ACA 622-1600-3 5x(400+800) 5xNBRA-659 5x(2xSAFUR180F460) 5x(1.20) 60000 1764
-1770-3 ACA 622-1600-3 5x(400+800) 5xNBRA-659 5x(2xSAFUR180F460) 5x(1.20) 60000 1764
-2140-3 ACA 622-1920-3 6x(400+800) 6xNBRA-659 6x(2xSAFUR180F460) 6x(1.20) 72000 2117
-2340-3 ACA 622-1920-3 6x(400+800) 6xNBRA-659 6x(2xSAFUR180F460) 6x(1.20) 72000 2117
-2820-3 ACA 622-1920-3 6x(400+800) 6xNBRA659 6x(2xSAFUR180F460) 6x(1.20) 72000 2117
Supply voltage 500V
-0930-5 ACA 622-1200-5 3x(400+800) 3xNBRA-659 3x(2xSAFUR200F500) 3x(1.35) 32400 1208
-1090-5 ACA 622-1200-5 3x(400+800) 3xNBRA-659 3x(2xSAFUR200F500) 3x(1.35) 32400 1208
-1380-5 ACA 622-1200-5 3x(400+800) 3xNBRA-659 3x(2xSAFUR200F500) 3x(1.35) 32400 1208
-1760-5 ACA 622-1600-5 4x(400+800) 4xNBRA-659 4x(2xSAFUR200F500) 4x(1.35) 43200 1611
-2160-5 ACA 622-2000-5 5x(400+800) 5xNBRA-659 5x(2xSAFUR200F500) 5x(1.35) 54000 2014
-2620-5 ACA 622-2400-5 6x(400+800) 6xNBRA-659 6x(2xSAFUR200F500) 6x(1.35) 64800 2417
-2850-5 ACA 622-2400-5 6x(400+800) 6xNBRA-659 6x(2xSAFUR200F500) 6x(1.35) 64800 2417
-3450-5 ACA 622-2400-5 6x(400+800) 6xNBRA-659 6x(2xSAFUR200F500) 6x(1.35) 64800 2417
Supply voltage 690V
-0900-6 ACA 622-1200-6 3x(400+800) 3xNBRA-669 3x(2xSAFUR200F500) 3x(1.35) 32400 1211
-1040-6 ACA 622-1200-6 3x(400+800) 3xNBRA-669 3x(2xSAFUR200F500) 3x(1.35) 32400 1211
-1380-6 ACA 622-1200-6 3x(400+800) 3xNBRA-669 3x(2xSAFUR200F500) 3x(1.35) 32400 1211
-1710-6 ACA 622-1600-6 4x(400+800) 4xNBRA-669 4x(2xSAFUR200F500) 4x(1.35) 43200 1615
-2120-6 ACA 622-2000-6 5x(400+800) 5xNBRA-669 5x(2xSAFUR200F500) 5x(1.35) 54000 2019
-2540-6 ACA 622-2400-6 6x(400+800) 6xNBRA-669 6x(2xSAFUR200F500) 6x(1.35) 64800 2422
-2800-6 ACA 622-2400-6 6x(400+800) 6xNBRA-669 6x(2xSAFUR200F500) 6x(1.35) 64800 2422
-3350-6 ACA 622-2400-6 6x(400+800) 6xNBRA-669 6x(2xSAFUR200F500) 6x(1.35) 64800 2422
ACx = ACS/ACC 19
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Application Programs See the subsection Application Program in General Technical Data
ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9.
Applicable Standards See the subsection Applicable Standards in General Technical Data
ACx 601, ACx 604 and ACx 607/627/677 R7 to 2R9.
Materials (Cabinet & Table below shows the cabinet and busbar materials.
Busbars)
Enclosure Coating Color
Thickness
hot-dip zinc coated steel sheet 1.0 to 2.5 mm with 60 mm RAL 7035 light
polyester thermosetting powder coating in visible beige semigloss
surfaces
Flat Busbars: aluminium (standard), copper (optional), tin plated copper (optional)
Package: wood or plywood (seaworthy package). Plastic covering of the package:
PE-LD, bands PP or steel.
Transportation Length: max. 4 metres, weight max. 2400 kg, Position: upright
Lenghts and Max. crate dimensions:
packages
length shipping length + 100 mm
depth shipping split depth + 150 mm
height height + 80 mm
Max. seaworthy dimensions:
length shipping length + 200 mm
depth shipping split depth + 185 mm
height 2200 mm
Disposal See subsection Disposal in General Technical Data ACx 601, ACx
604 and ACx 607/627/677 R7 to 2R9.
20 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Compliance with the EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
EMC Directive equipment to operate without problems within an electromagnetic environment.
Likewise, the equipment must not disturb or interfere with any other product or system
within its locality.
The EMC Directive defines the requirements for immunity and emissions of electrical
equipment used in the European Economic Area. The EMC product standard EN
61800-3 covers the requirements stated for frequency converters.
The ACx 607/627/677 frequency converters (630 kW to 3000 kW) comply with the
EMC Directive in industrial low-voltage network, and IT networks (unearthed mains)
with the following provisions:
Type Code
ACS 600 Type Character no. EMC Filter No EMC Filter
Selections Selections
ACS/ACC 607, ACxxxxxxxxxxxxxxxxxxxxxxxxx... 1, 2*** 0,
ACx 627 or
ACx 677
26
ACS 600 1, 2*** 0
MultiDrive ACA63xxxxxxxxxxxxx...
Supply Section
16
16
ACx = ACS/ACC 21
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Neighbouring network
Static screen
Point of measurement
Equipment Equipment
Use of ACx 600 in Second Environment without EMC filtering (EN 61800-3: second
environment includes all establishments other than those directly connected to a low-
voltage power supply network which supplies buildings used for domestic purposes.)
Machinery Directive ACx 607/617/627/677 frequency converters comply with the European
Union Machinery Directive (89/392/EEC) requirements for an
equipment intended to be incorporated into machinery.
CSA Marking The CSA marking is often required in North America. CSA marked
ACx 607, ACx 617 and ACx 677 frequency converters (630 kW to 3000
kW) are available on request.
22 ACx = ACS/ACC
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
Compliance with AS/ The above rules define the essential requirements for emissions of electrical
NZS 2064 equipment used in Australia and New Zealand. The standard AS/NZS 2064 (Limits and
methods of measurement of electronic disturbance characteristics of industrial,
scientific and medical radiofrequency equipment, 1997) covers the detailed
requirements for three-phase frequency converters.
The ACx 607 frequency converters (630 kW to 3000 kW) comply with AS/NZS 2064 for
class A equipment (suitable for use in all establishments other than domestic and those
directly connected to a low-voltage network which supplies buildings used for domestic
purposes). The compliance is valid with the following provisions:
1. The ACx 607 is equipped with EMC filtering (refer to Table A-1).
2. The ACx 607 is installed according to the instructions given in this manual.
3. The motor and control cables are selected as specified in this manual.
4. Maximum cable length is 100 metres.
Note: The ACx 607 must not be equipped with EMC filtering (refer to Table A-1) when
installed to IT networks. The mains becomes connected to earth potential through the
EMC filter capacitors. In IT networks this may cause danger or damage the unit.
Equipment Warranty General: ABB warrants the Equipment supplied by ABB against defects in material and
workmanship for a period of twelve (12) months after installation or twenty four (24)
and Liability months from date of shipment from factory, whichever first occurs.
Should any failure to conform with the applicable warranties appear during the
specified periods under normal and proper use and provided the Equipment has been
properly stored, installed, operated and maintained, and if given prompt notice by
Purchaser, ABB shall correct such nonconformity, at its option; by (1) repair or
replacement of the nonconforming equipment or parts thereof. Repairs or
replacements pursuant to warranty shall not renew or extend the applicable original
equipment warranty period, provided however, that any such repairs or replacement of
equipment or parts thereof shall be warranted for the time remaining of the original
warranty period or 30 days, whichever is longer.
ABB shall not be responsible for providing working access to the defect, including
disassembly and reassembly of equipment or for providing transportation to and from
repair or factory facility, all of which shall be at Purchasers risk and expense.
These warranties shall not apply to any Equipment or parts thereof which (1) have
been improperly repaired or altered; (2) have been subjected to misuse, negligence or
accident; (3) have been used in a manner contrary to ABBs instructions; (4) are
comprised of materials provided or designed stipulated by Purchaser; or (5) are used
equipment.
The foregoing warranties are exclusive and in lieu of all other warranties of quality and
performance, written, oral or implied, and all other warranties including any implied
warranties of merchantability or fitness for a particular purpose are hereby disclaimed
by ABB and all equipment manufacturers.
Correction of nonconformities in the manner and for the period of time provided above
shall be the Purchasers exclusive remedy and shall constitute fulfilment of all liabilities
of ABB and any Equipment manufacturer (including any liability for direct, indirect,
special, incidental or consequential damages) whether in warranty, contract,
negligence, tort, strict liability, or otherwise with respect to any nonconformance of or
defect or deficiency in the equipment supplied or services furnished hereunder.
ACx = ACS/ACC 23
Technical Data ACS/ACC 607/627 R11i to 4R11i, ACx 617 and ACx 677
OR OTHERWISE, including, but not limited to loss of profits or revenue, loss of use of
the Equipment or any associated equipment, cost of capital, cost of substitute
equipment, facilities or services, downtime costs, delays, or claims of customers of the
Purchaser or other third parties for such or other damages. ABBs liability on any claim
whether in contract, warranty, negligence, tort, strict liability, or otherwise for any loss or
damage arising out of, connected with, or resulting from the contract or the
performance or breach thereof, or from the design, manufacture, sale, delivery, resale,
repair, replacement, installation, technical direction of installation, inspection, operation
or use of any equipment covered by or in connection therewith, shall in no case exceed
the purchase price of the Equipment or part thereof or services which give rise to the
Claim.
All clauses of action against ABB arising out of or relating to the contract or the
performance or breach hereof shall expire unless brought within one year of the time of
accrual thereof.
In no event, regardless of cause, shall ABB assume responsibility for or be liable for
penalties or penalty clauses of any description or for indemnification of customer or
others for costs, damages, or expenses each arising out of or related to the goods or
services of the order.
Your local distributor or ABB office may hold different guarantee details, which are
specified in the sales terms, conditions, or guarantee terms. These terms are available
on request.
If you have any questions concerning your ABB frequency converter, please contact
the local distributor or ABB office. The technical data, information and specifications
are valid at the time of printing. The manufacturer reserves the right to modifications
without prior notice.
24 ACx = ACS/ACC
Product Type Designations Used in The Catalogue
The figure below describes the product type designations used in this
catalogue. The complete 22 to 39 digit type code key for the ACS 600
SingleDrive is given in the Ordering Information document (EN code
58977985).
A C S 6 0 7 R7 to 2R9
Drive type (1
S Standard drive
C Crane drive
P Position drive
Input bridge
0 Six-pulse diode bridge
1 IGBT diode bridge
2 Twelve-pulse diode bridge
7 Thyristor bridge
Construction
1 Wall-mounted drive
4 Converter module to be installed into
cabinet by user
7 Drive assembled inside a cabinet
.
.
.
EFFECTIVE: 2000-06-09 / EN
3AFY 58059412 R0525
ABB Industry Oy
Drives
P.O. Box 184
FIN-00381 HELSINKI
FINLAND
Telephone +358 10 22 2000
Telefax +358 10 22 22681
Internet http://www.abb.com/automation