Quemador Siemens Linco
Quemador Siemens Linco
Quemador Siemens Linco
ISO 9001
The LFL1... and this Data Sheet are intended for use by OEMs which integrate the
burner controls in their products.
Use
- Control and supervision of forced draft burners of expanding flame and interrupted
pilot construction
- For medium to high capacity
- For intermittent operation (at least one controlled shutdown every 24 hours)
- Universally applicable for multistage or modulating burners
- For use with dual-fuel burners
- For use with stationary air heaters
The difference between 01 series and 02 series is the duration of the safety time for the
pilot burner of burners equipped with pilot gas valves.
For burner controls for use with burners in continuous operation, refer to Data Sheet
7785 (LGK16...).
CC1N7451en
Siemens Building Technologies
11.06.2003 HVAC Products
Warning notes
Before performing any wiring changes in the connection area of the LFL1, com-
pletely isolate the unit from the mains supply (all-polar disconnection)
Ensure protection against electric shock hazard by providing adequate protection
for the burner controls connection terminals
Check to ensure that wiring is in an orderly state
Press the lockout reset button only manually (apply a force of no more than 10 N),
without using any tools or pointed objects
Do not press the lockout reset button on the unit or the remote lockout reset
button for more than 10 seconds since this damages the lockout relay in the
unit
Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage
In the case of flame supervision with UV detectors QRA..., it should be noted that
sources of radiation such as halogen lamps, welding equipment, special lamps, ig-
nition sparks, as well as X-rays and gamma radiation, can produce erroneous
flame signals
2/20
A z m a
t7 t16
t10
t11
P
t1
t3
t12
t3
TSA TSA
t4 1
t4
t9
t5 2
t5
B
AS C
D t6 t13
A
1 2 21 3 13 12 14 4 5 6 7 16 17 18 19 20 9 11 10 8 22 23 24
LR
+
d1 d2 QRA...
bv... W GP
SB 1
SA v a z m
R N N
M
3)
EK2 22 23 24
H TSA, t3, t4, nur bei:
BV1 BV2 BV3 LFL1.335,
M1 M2 Z LFL1.635 und
LK FE
S AL LP LFL1.638
L ZBV BV1 BV2
N
1 2 3 4 5 7451a02/0602 6 7
c Connect safety limit thermostat in the line (manual reset, e.g. SB)
d Remote reset
When remote reset button EK2 is connected to
- terminal 3, only remote reset is possible
- terminal 1, both remote emergency shutdown and remote reset are possible
e Required switching capacities
- of the switching devices connected between terminals 12 and 4 (refer to Technical data)
- of the switching devices connected between terminals 4 and 14 (refer to Technical data)
- depending on the loads applied to terminals 16...19 (refer to Technical data)
3/20
Installation notes
Commissioning notes
4/20
Type
LFL1.122 x --- x x x x
LFL1.133 x --- x x --- x
LFL1.322 x --- x x x x
LFL1.333 x --- x x x x
LFL1.335 x x x x x x
LFL1.622 x --- x x x x
LFL1.635 x --- x x x x
LFL1.638 x --- x --- x ---
Service notes
Disposal notes
The unit contains electrical and electronic components and may not be disposed of
together with household waste.
Local and currently valid legislation must be observed.
5/20
Plug-in base - Plug-in base and connectors of the LFL1... are designed such that only LFL1...
type burner controls can be plugged in
- With 24 connection terminals
- With auxiliary terminals 31 and 32
- With 3 earthing terminals, joining in a lug for earthing the burner
- With 3 neutral conductor terminals
prewired to terminal 2
- With 14 knockout holes for cable entry with cable entry glands
8 at the side
6 in the floor
- With 6 lateral threaded knockout holes for cable entry glands Pg11 or M16
Type summary
Switching times are given in seconds, in the burner startup sequence, valid for 50 Hz mains frequency. At 60 Hz, the switching
times are about 17 % shorter.
6/20
Accessories
Plug-in bases
- With Pg11 threads for cable entry glands AGM410490550
- With M16 threads for cable entry glands AGM14.1
Technical data
General unit data Mains voltage AC 230 V 15 / +10 %
LFL1... AC 100 V 15 %...AC 110 V +10 %
Mains frequency 50...60 Hz 6 %
Unit fuse (built-in) T6,3H250V to DIN EN 60 127
Primary fuse (external) max. 10 A (slow)
Weight
- LFL1... approx. 1,000 g
- Plug-in base approx. 165 g
Flame detectors
- QRA... refer to Data Sheet 7712
- Ionization probe to be supplied by thirds
Power consumption approx. AC 3.5 VA
Mounting position optional
Degree of protection IP 40, with the exception of the connection
area
Perm. input current at terminal 1 max. 5 A continuously, peaks up to 20 A for
20 ms
Perm. load on control terminals 3, 6, 7, max. 4 A continuously, peaks up to 20 A for
9...11, 15...20 max. 20 ms, total max. 5 A
Required switching capacity of switching
devices 1 A, AC 250 V
- Between terminals 4 and 5 1 A, AC 250 V
- Between terminals 4 and 12 min. 1 A, AC 250 V
- Between terminals 4 and 14 depending on the load on terminals 16...19
7/20
) During the prepurge time with higher test voltage: Self-ignition and extraneous light test
) Multicore cable not permitted
+ 7451v02/0503
8/20
R LR R LR
t5
t11 t12 t5
100%
M M 100%
min.
LK 0... LK min.
BV2 0...
t11 t12
t13 RV
FS t13
7451a06/0600
FS
7451a07/0600
General The following features enable the LFL1... to offer a high level of additional safety:
- Detector and extraneous light test are resumed immediately on completion of the
afterburn time t13. Fuel valves that are not closed, or not fully closed, immedi-
ately initiate lockout on completion of the afterburn time t13. The test will only be
terminated when the prepurge time t1 of the next startup sequence has elapsed
- The proper functioning of the flame supervision circuit is automatically checked
during each startup phase of the burner
- During the postpurge time t6, the control contacts for the release of fuel are
checked to ensure they have not welded
- The built-in unit fuse protects the control contacts against overloads
9/20
Flame supervision - With the ionization probe, in networks with earthed or nonearthed neutral conduc-
tor. For this kind of supervision, the flame supervision circuit is designed such that
possible disturbances of the ionization current due to the ignition spark normally
have no impact on the establishment of the flame signal. A short-circuit between
ionization probe and burner ground cannot simulate a flame signal
- With UV detector QRA... (gas and oil burners)
- Simultaneous use of ionization probe and QRA... (e.g. with interrupted pilot burners
or gas-electrically ignited oil burners)
Preconditions - If, on startup, the required input signals are not present, the burner control inter-
for startup rupts the startup sequence at the points marked by symbols and initiates lockout
where required by safety regulations. The symbols used in this Data Sheet corre-
spond to those on the burner controls lockout indicator.
10/20
Shortly after the start of t1, the air pressure switch must change over from
terminal 13 to terminal 14.
Otherwise lockout
Start of air pressure check
At the same time, terminal 14 must be live since the ignition transformer will be
powered and the fuel released via this current path.
On completion of the prepurge time, the burner control will drive the air damper
to the low-fire position via terminal 10, which is determined by the changeover
point of auxiliary switch m. During the positioning time, the sequence switch
stops again. A short time later, the motor of the sequence switch will be
switched to the control section of the burner control. This means that, from now
on, positioning signals delivered to terminal 8 have no impact on the burners
further startup sequence (and on subsequent burner operation):
t5 Interval
- On completion of t5, power is fed to terminal 20; at the same time, con-
trol outputs 9...11 and input 8 are galvanically separated from the units
control section
The LFL1... is now protected against return voltages from the power
control loop
- The startup sequence of the LFL1 ends with the release of LR at ter-
minal 20
- After a number of idle steps (steps with no change of the contact position),
the sequence switch switches itself off
11/20
t3 Preignition time
Release of fuel via terminal 18
t4 Interval ZBV-BV1
t4 Up to the release of the fuel valve at terminal 19 for the main burners start load
C Controlled shutdown
On controlled shutdown, the BV... will immediately be closed. At the same
time, the sequence switch starts and programs t6
t6 Postpurge time
- Fan M2 connected to terminal 7
- Shortly after the start of t6, power is fed to terminal 10
air damper will be driven to the MIN position
- Full closing of the air damper starts only shortly before t6 has elapsed
triggered by the control signal at terminal 11
- During the following burner off period, terminal 11 remains live
12/20
Times TSA, t3 and t4 only exist with burner controls of the 01 series.
13/20
The symbol above the indicators reading mark gives the type of fault:
No start One of the contacts is not closed (also refer to Preconditions for burner startup)
Extraneous light
Lockout during or after completion of the control sequence.
Examples:
Flames that have not extinguished
Leaking fuel valves
Defect in the flame supervision circuit
= Interruption of Terminal 8 has not received the OPEN signal from end switch a
startup sequence Terminals 6, 7 and 14 remain live until the fault has been corrected
P Lockout No indication of air pressure at the beginning of the air pressure check
Loss of air pressure after the air pressure check
> Interruption of Terminal 8 has not received the positioning signal from auxiliary switch m for the
startup sequence low-fire position
Terminals 6, 7 and 14 remain live until the fault has been corrected
2 Lockout No flame signal on completion of the second safety time (flame signal of main flame
with interrupted pilot burners)
If lockout occurs any other moment in time between start and preignition not indicated
by a symbol, the usual cause is a premature flame signal, that is, a faulty flame signal,
caused for instance by a self-igniting UV tube.
14/20
A z m a
t7 t16
t10
t11
P
t1
t3
t12
t3
TSA TSA
t4 1
t4
t9
t5 2
t5
B
AS C
D t6 t13
A
1 2 21 3 13 12 14 4 5 6 7 16 17 18 19 20 9 11 10 8 22 23 24
LR
+
d1 d2 QRA...
bv... W GP
SB 1
SA v a z m
R N N
M
3)
EK2 22 23 24
H TSA, t3, t4, nur bei:
BV1 BV2 BV3
LFL1.335,
M1 M2 Z LFL1.635 und
LK FE
S AL LP LFL1.638
L ZBV BV1 BV2
N
1 2 3 4 5 7451a02/0602 6 7
Connection diagram
L S
H
SB
1
AS FE
br1
a b 22 23 24
ar2
ar1 I a XV
a b b
4 12 6 7
QRA...
W +
d1 d2
GP LP
22 23 24
R M1 M2
N
5 13 14 V
fr3 fr2 FR
fr1
a b b a
XI XIII (1) (2)
b a a b XII NTC
XIV a b
AR IV
a b
VII
3) br2 a b
EK1 VI V III ar3
L1 II X VIII
E M a b a b M
BR b a a b a b SM
A
3 21 2 15 16 17 18 19 20 9 11 10 8
LR
1 SA v a z m
AL Z M LK
3) BV1
BV2 7451a12/1100
EK2 ZBV BV1
H
N BV2
Do not press the lockout reset button for more than 10 seconds!
For the connection of the safety shutoff valve, refer to the plant diagram provided by
the burner manufacturer.
15/20
Steuerausgang
A B C t6 D auf Klemme:
t11 t1 t12
a 12
I b t7 7
t3 t4
a 19
II b 16
a 10
III b 9
IV
a 9
V b 11
t16
VI 20
a
VII b 8
TSA t20
a 18
VIII b *t3 *t4 t9
a 17
X b *TSA t5
a
XI b
a
XII b t10 t13
a
XIII b
a
XIV b
a 12
XV b 7
t8
7451d01/0202
Positionen der Strungsanzeige
LFL P 1 2
16/20
a Changeover end switch for air dampers m Changeover auxiliary switch for the air
OPEN position dampers MIN position
AL Remote lockout warning device (alarm) M... Fan or burner motor
AR Load relay with contacts ar... NTC NTC resistor
AS Unit fuse QRA... UV detector
BR Lockout relay with contacts br... R Control thermostat or pressurestat
BV... Fuel valve RV Modulating fuel valve
bv... Control contact for the CLOSED position S Fuse
of gas valves SA Air damper actuator
d... Contactor or relay SB Safety limiter
EK... Lockout reset button SM Synchronous motor of sequence switch
FE Ionization probe v In the actuator: Changeover auxiliary switch
FR Flame relay with contacts fr.. For the position-dependent release of fuel
GP Gas pressure switch V Flame signal amplifier
H Main isolator W Limit thermostat or pressure switch
L1 Fault signal lamp z In the actuator: End switch for the air dampers
L3 Operational readiness indication CLOSED position
LK Air damper Z Ignition transformer
LP Air pressure switch ZBV Pilot gas valve
LR Load controller
17/20
Extension of the safety time is only permitted if in compliance with the rele-
vant national standards.
6 11 10 8
Burner without air damper If the case of burners with no air
damper (or with an air damper not
M controlled and monitored by the
N
7451a11/0396 burner control), terminals 8 and 6
must be linked, as otherwise the
burner control will not be able to start
the burner.
2-stage expanding flame burner Load control by a 2-position controller. The air damper is closed during
burner off periods.
16 17 18 19 9 20 11 10 8
LR L...
11 7 1 6 5 2 10 8 LR
SA
SA
IV I II III
M BV1/BV2
13 12 N 3 4 9
Z BV1 BV2 LK
N 7451a03/0396
A B C D
TP R
t7 t1 t6
M1
M
~ M2
t3
Z
TSA
BV1
t4
R LR
t5
100%
M
min.
LK 0...
BV2
t11 t12
t13
FS
7451a06/0600
Control of actuator SA according to the single-wire principle (actuator SA: E.g. SQN3... as per Data Sheet
7808). For other connections, refer to Connection diagrams.
18/20
16 17 18 19 20 9 11 10 8
L...
LR LR
N SA SA RV
a z m BV1
M
Z BV1 RV LK
N 7451a04/1295
A B C D
T R
P
t7 t1 t6
M1
M
~ M2
t3
Z
TSA
BV1
t4
R LR
t11 t12 t5
M 100%
LK min.
0...
RV
t13
FS
7451a07/0600
The air damper is kept closed during burner off periods. For other connections, refer to Connection diagrams.
2-stage interrupted pilot burner Controlled and supervised by a burner control of the 01 series.
(burner with pilot burner)
16 17 18 19 20 9 11 10 8
L...
LR
LR
ZBV SA SA
v a z m
M
BV1/BV2
ZBV
Z BV1 BV2 LK
N 7451a05/0496
A B C D
TP R
t7 t1 t6
M1
M
~ M2
t3
Z
TSA
ZBV
t4 t9
BV1
R LR
t5
100%
M
min.
LK
0...
BV2
t11 t12 t13
FS
7451a08/0202
The air damper is kept closed during burner off periods. For other connections, refer to Connection diagrams.
19/20
1,5
123
25 25
6
18,9
15,5
7,5
5
7
15 15 15
7451m02/0602
27,5 27,5
37
103
7,5
103
13 14 15 16 17 18 19 20 21 22 23 24
12
51,5
7,5 18,9
5,7
11
40
10
9
12,8
1
8
31
7
15
4,4
6
26,8
5
51,5
4
25
N
1,
3
5
32
2
1
5,2 5,2x6,7
7451m01/0602
5,7 12,8 40
51,5 51,5