Type Type of Network 3P+N, 3P, 2P+N, 1P+N 3P+N
Type Type of Network 3P+N, 3P, 2P+N, 1P+N 3P+N
Type Type of Network 3P+N, 3P, 2P+N, 1P+N 3P+N
Unom Operating voltage in Volts 208, 220, 230, 240, 380, 400, 415, 440 415
Fnom Operating frequency in Hz 50, 60 50
(1) U<% Source 1, min voltage threshold in % As per the Unom voltage Dynamic
(2) U<% Source 2, min voltage threshold in % As per the Unom voltage Dynamic
(1) U>% Source 1, max voltage threshold in % As per the Unom voltage Dynamic
(2) U>% Source 2, max voltage threshold in % As per the Unom voltage Dynamic
(1) Hz<% Source 1, min frequency threshold in % From 0 to 10% if 50Hz, from 0 to 25% if 60Hz 5%
(2) Hz<% Source 2, min frequency threshold in % From 0 to 10% if 50Hz, from 0 to 25% if 60Hz 5%
(1) Hz>% Source 1, max frequency threshold in % From 0 to 30% if 50Hz, from 0 to 8% if 60Hz 5%
(2) Hz>% Source 2, max frequency threshold in% From 0 to 30% if 50Hz, from 0 to 8% if 60Hz 8%
ABC Phase sequence ABC, ACB, OFF (no check) ABC
(1) V/V Adjustment of voltage source 1 From 0 to 9999 1000
(2) V/V Adjustment of voltage source 2 From 0 to 9999 1000
Position Changeover switch position control YES, NO YES
Bklight Screen back-light control From 1 to 99, (1= black screen) 99
Contrast Screen contrast adjustment From 1 to 99, (1= max contrast) 10
Modbus Activation of the RS485 serial link YES, NO (no activation) NO
Prio EJP Management of EJP priority (see 7.9.1) YES, NO (no management) NO
(1) OK? Confirmation of return of voltage source 1 YES, NO (not confirmed) NO
NO % Confirmation of U and F thresholds OFF (no confirmation), ON OFF
Hist/U% U threshold hysteresis adjustment From 0 to 3% 2%
Hist/F% F threshold hysteresis adjustment From 0 to 2% 0%
(1)+/- Source 1 voltage gain adjustment From 0 to 999 100
No. Meaning Possible values By default
T00 Loss of voltage source 1 From 0 to 180 seconds 3 seconds
T01 Return of voltage source 1 From 0 to 999 seconds 5 seconds
T02 Min. voltage fault source 1 From 0 to 999 seconds 5 seconds
T03 Max. voltage fault source 1 From 0 to 999 seconds 5 seconds
T04 Min. voltage fault source 2 From 0 to 999 seconds 5 seconds
T05 Max. voltage fault source 2 From 0 to 999 seconds 5 seconds
T06 Min. frequency fault source 1 From 0 to 999 seconds 5 seconds
T07 Max. frequency fault source 1 From 0 to 999 seconds 5 seconds
T08 Min. frequency fault source 2 From 0 to 999 seconds 5 seconds
T09 Max. frequency fault source 2 From 0 to 999 seconds 5 seconds
T10 Source 1 control fault From 2 to 999 seconds 5 seconds
T11 Source 2 control fault From 2 to 999 seconds 5 seconds
T12 Switch of source From 0 to 999 seconds/10 10/10 seconds
T13 Stabilisation of voltage source 1 From 0 to 999 seconds/10 10/10 seconds
T14 Stabilisation of voltage source 2 From 0 to 999 seconds/10 30/10 seconds
T15 Establishment of voltage source 1 From 0 to 999 seconds/10 5/10 seconds
T16 Establishment of voltage source 2 From 0 to 999 seconds/10 5/10 seconds
T17 GS cooling source 1 From 0 to 999 seconds 60 seconds
T18 GS cooling source 2 From 0 to 999 seconds 60 seconds
T19 Test mode in progress From 0 to 999 seconds 600 seconds
T20 EJP notice (for France only) From 0 to 999 minutes 20 minutes
T21 EJP loss (For France only) From 0 to 999 seconds 600 seconds
T22 Power cut-off From 0 to 999 seconds 10 seconds
T23 Failure to start From 0 to 999 seconds 30 seconds
T24 Reserved for future development From 0 to 999 seconds 120 seconds
T25 Reserved for future development From 0 to 999 seconds 120 seconds
T26 Scrolling down of measurement screens From 1 to 10 seconds 5 seconds
T27 Reserved for future development From 0 to 999 seconds 3 seconds
T28 Critical min. voltage fault source 1 From 0 to 999 seconds 1 second
T29 Critical max. voltage fault source 1 From 0 to 999 seconds 1 second
T30 Critical min. voltage fault source 2 From 0 to 999 seconds 5 seconds
T31 Critical min. voltage fault source 2 From 0 to 999 seconds 5 seconds
T32 Critical min. frequency fault source 1 From 0 to 999 seconds 1 second
T33 Critical max. frequency fault source 1 From 0 to 999 seconds 1 second
T34 Critical min. frequency fault source 2 From 0 to 999 seconds 5 seconds
T35 Critical max. frequency fault source 2 From 0 to 999 seconds 5 seconds
T36 Final fault source 1 From 0 to 999 seconds/10 5/10 seconds
T37 Reserved for future development From 0 to 999 seconds 1 second
T38 Final fault source 2 From 0 to 999 seconds/10 5/10 seconds
T39 Reserved for future development From 0 to 999 seconds 1 second
T40 Production request From 0 to 999 seconds 10 seconds
T41 Switch in changeover switch power supply From 0 to 999 seconds 3 seconds
T42 Back-light activation From 0 to 999 seconds 15 seconds
T43 Reserved for future development From 0 to 999 seconds 5 seconds
T44 Reserved for future development From 0 to 999 seconds 5 seconds
T45 Reserved for future development From 0 to 999 seconds 3 seconds
T46 Reserved for future development From 0 to 999 seconds 3 seconds
T47 Reserved for future development From 0 to 999 seconds 3 seconds
T48 Reserved for future development From 0 to 999 seconds 3 seconds
T49 Reserved for future development From 0 to 999 seconds 3 seconds