RB 2000 Act
RB 2000 Act
RB 2000 Act
RB 2000
< Balanced valve design eliminates Applications Description
inlet pressure effect The RB 2000 regulator is designed for use The RB 2000 regulator is a direct-acting,
< Rugged construction for durability in small commercial applications: gas supply spring -loaded regulator (lever type) with an
networks, small industries, heating plants integrated standard relief valve and an
< Rapid response to load changes
and for all types of installations where optional safety shut-off device.
< Integral shutoff valve accurate pressure control, easy adjustment The balanced compensation system ensures
< Internal relief and fast response times are required, such as constant outlet pressure when the upstream
burners, industrial ovens, boilers, etc pressure varies.
< Inlet strainer
It is also suitable for installation in cabinets, This eliminates changes to the orifice size
as a space saving regulator arising from different inlet pressure ranges.
The regulator is equipped with a built-in
filter (filtration grade 0.5 mm).
Technical features
Inlet pressure 0.35 6 bar (10 bar)
Outlet pressure 5 mbar 180 mbar (750 mbar)
Accuracy & lock-up pressure Up to AC5 / up to SG 10
Operating temperature -20C to +60C
Acceptable gases Natural gas, town gas, propane, butane, air, nitrogen or any non-corrosive gas
Installation Horizontal or vertical
Safety devices Standard relief valve
Optional built-in safety shut-off valve:
- over-pressure shut-off (OPSO)
- under-pressure shut-off (UPSO)
Options Internal or external control line
Monitor version
Connections
Sizes 1 x 1 by RB 201X/211X/221X/231X
1 x 11/2 by RB 261X
Type Gas female threaded according to ISO 228/1 or ISO 7/1
Materials
Body Spheroidal graphite iron SFP 500
Head Die cast aluminium
Internal parts Stainless steel and brass
Seals Nitrile rubber
R X X 4 7 X X DN X Variants
B Balanced - High accuracy version
E External impulse
I Internal impulse
0 Orifice ( 7 mm) External or internal impulse
1 Orifice ( 11 mm) External or internal impulse
2 Orifice ( 13 mm) External or internal impulse
3 Orifice ( 14 mm) External or internal impulse
6 Orifice ( 14 mm) Internal impulse only
0 Relief valve
1 Relief valve + Over-pressure shut-off valve
2 Relief valve + Over and low-pressure shut-off valve
M Monitor version - External impulse
TR Reduced head (see spring selection tables)
Example : RBE 2312/TR is a 2300 regulator with a balanced valve, an external impulse, a reduced head
RB 2011 and an OPSO / UPSO shut-off valve.
2
Flow capacity
The maximum flow capacities (St m3/h) The values given are those for
for different versions of the RB 2000 appropriately-sized pipe work. Velocity
regulator are shown in tables A, B, C, D, E restrictions may limit the flow rate values
(by relative gas density d=0.6, mentioned below.
temperature T=288K and absolute The flow capacity of the regulator without
pressure p=1.013 bar). a safety shut-off device is 5% higher.
3
RBE 2312 -1 x1 (with SSV) Table D
4
Outlet pressure range
Regulator
RB 201X / 211X / 221X / 231X / 261X Table F
Shut-off valve
Over-pressure shut-off springs (OPSO) Table G
Spring Characteristics Who (bar) Who (bar)
Code d De Lo It 2011-2611 2012-2612
mm mm mm ( 120) ( 120)
20563022 1.5 25 35 5.5 20 40 28 60
20563023 1.7 25 35 5.5 30 70 40 100
20563014 1.9 25 35 5.5 60 160 60 140
20563124 2.2 25 35 5.5 70 240 130 260
20563121 2.5 25 35 5.5 80 350 220 350
5
Dimensions (in mm)
180
132
42
Figure 2
Mod. 2010/2110/2210/2310/2610*
Weight 2 Kg
139
179
40
1/4 GAS
1 GAS
100
180
132
42
GA-0052.0-GB-02/03 - Copyright 2002, Actaris, All Rights Reserved. - Actaris reserves the right to change these specifications without prior notice.
Figure 3
Mod. 2011-2012/2111-2112/2311
2312/2611*-2612*
139
Weight 2.5 Kg
252
1/4 GAS
1 GAS
113