Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

RB 2000 Act

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Pressure Regulator

RB 2000
< Balanced valve design eliminates Applications Description
inlet pressure effect The RB 2000 regulator is designed for use The RB 2000 regulator is a direct-acting,
< Rugged construction for durability in small commercial applications: gas supply spring -loaded regulator (lever type) with an
networks, small industries, heating plants integrated standard relief valve and an
< Rapid response to load changes
and for all types of installations where optional safety shut-off device.
< Integral shutoff valve accurate pressure control, easy adjustment The balanced compensation system ensures
< Internal relief and fast response times are required, such as constant outlet pressure when the upstream
burners, industrial ovens, boilers, etc pressure varies.
< Inlet strainer
It is also suitable for installation in cabinets, This eliminates changes to the orifice size
as a space saving regulator arising from different inlet pressure ranges.
The regulator is equipped with a built-in
filter (filtration grade 0.5 mm).

Technical features
Inlet pressure 0.35 6 bar (10 bar)
Outlet pressure 5 mbar 180 mbar (750 mbar)
Accuracy & lock-up pressure Up to AC5 / up to SG 10
Operating temperature -20C to +60C
Acceptable gases Natural gas, town gas, propane, butane, air, nitrogen or any non-corrosive gas
Installation Horizontal or vertical
Safety devices Standard relief valve
Optional built-in safety shut-off valve:
- over-pressure shut-off (OPSO)
- under-pressure shut-off (UPSO)
Options Internal or external control line
Monitor version

Connections
Sizes 1 x 1 by RB 201X/211X/221X/231X
1 x 11/2 by RB 261X
Type Gas female threaded according to ISO 228/1 or ISO 7/1

Materials
Body Spheroidal graphite iron SFP 500
Head Die cast aluminium
Internal parts Stainless steel and brass
Seals Nitrile rubber

Pressure Regulator RB 2011 Diaphragm Rubberized fabric


Figure 1 - RBI 2612 Type
Operational Schematic

Type designation and options


To define the RB 2000 regulator you would like to order, please use the table below for
selecting the options and the relevant code.

R X X 4 7 X X DN X Variants
B Balanced - High accuracy version
E External impulse
I Internal impulse
0 Orifice ( 7 mm) External or internal impulse
1 Orifice ( 11 mm) External or internal impulse
2 Orifice ( 13 mm) External or internal impulse
3 Orifice ( 14 mm) External or internal impulse
6 Orifice ( 14 mm) Internal impulse only
0 Relief valve
1 Relief valve + Over-pressure shut-off valve
2 Relief valve + Over and low-pressure shut-off valve
M Monitor version - External impulse
TR Reduced head (see spring selection tables)

Example : RBE 2312/TR is a 2300 regulator with a balanced valve, an external impulse, a reduced head
RB 2011 and an OPSO / UPSO shut-off valve.

2
Flow capacity
The maximum flow capacities (St m3/h) The values given are those for
for different versions of the RB 2000 appropriately-sized pipe work. Velocity
regulator are shown in tables A, B, C, D, E restrictions may limit the flow rate values
(by relative gas density d=0.6, mentioned below.
temperature T=288K and absolute The flow capacity of the regulator without
pressure p=1.013 bar). a safety shut-off device is 5% higher.

RBE 2012 -1 x1 (with SSV) Table A

(St)m3/h Set point (mbar)


Inlet pressure (bar) 20 50 100 300 400
0.35 25 20 15
0.5 35 28 22 20
0.7 35 30 24 22 18
1 35 27 25 22 20
1.5 32 28 25 23 23
2 30 30 28 25 22
4 30 32 30 26 25
5 28 28 26 25 25
8 25 24 22 22 20
10 25 25 24 20 20

RBE 2112 -1 x1 (with SSV) Table B

(St)m3/h Set point (mbar)


Inlet pressure (bar) 20 50 100 300 400
0.35 30 25 20
0.5 40 30 25 22
0.7 40 32 30 26 22
1 45 60 68 55 45
1,5 45 56 65 65 41
2 40 36 32 28 27
4 38 35 32 30 27
5 35 38 35 32 30
8 35 36 36 34 34
10 35 37 35 33 33

RBE 2212 -1 x1 (with SSV) Table C

(St)m3/h Set point (mbar)


Inlet pressure (bar) 20 50 100 300 400
0.35 35 30 28
0.5 45 35 32 30
0.7 55 42 38 35 32
1 60 48 48 46 45
1.5 60 52 50 48 45
2 58 58 55 52 50
4 60 60 58 55 55
5 65 64 64 62 60
8 65 65 63 62 60
10 65 64 62 62 60

3
RBE 2312 -1 x1 (with SSV) Table D

(St)m3/h Set point (mbar)


Inlet pressure (bar) 20 50 100 300 400
0.35 35 36 32
0.5 65 60 62 65
0.7 65 62 60 55 55
1 65 65 70 60 53
1.5 65 64 64 65 61
2 75 80 90 85 70
4 70 68 65 62 59
5 68 70 65 63 60
8 65 65 60 58 55
10 65 62 55 52 50

RBE 2612 -1 x11/2 (with SSV) Table E

(St)m3/h Set point (mbar)


Inlet pressure (bar) 20 50 100 300 400
0.35 38 35 30
0.5 65 60 55 52
0.7 70 68 65 62 60
1 110 110 117 95 87
1.5 110 105 105 115 110
2 105 104 130 120 110
4 80 80 78 80 75
5 75 80 78 75 75
8 72 70 65 60 58
10 70 65 62 60 55

4
Outlet pressure range
Regulator
RB 201X / 211X / 221X / 231X / 261X Table F

Spring Characteristics Wh (mbar)


Code d De Lo It 2000 2100-2200 2000/TR 2600/TR 2300 2600
mm mm mm ( 180) ( 180/TR) ( 180)
20564241 1.5 30 80 9.5 6 10
20564141 1.6 30 80 9.5 5 12 8 13
20564142 1.8 30 80 8.5 8 18 13 25
20564050 1.8 30 100 10 15 25 20 28
20564051 2 30 100 11.5 22 33 47 78 26 39
20564044 2.2 30 80 9 20 50 54 115 36 50
20564042 2.5 30 80 9 36 78 95 215 46 80
20564143 3 30 80 9 75 150 260 400 100 180
20564144 3.5 30 80 9 450 750
+ SMALL PAGE

Shut-off valve
Over-pressure shut-off springs (OPSO) Table G
Spring Characteristics Who (bar) Who (bar)
Code d De Lo It 2011-2611 2012-2612
mm mm mm ( 120) ( 120)
20563022 1.5 25 35 5.5 20 40 28 60
20563023 1.7 25 35 5.5 30 70 40 100
20563014 1.9 25 35 5.5 60 160 60 140
20563124 2.2 25 35 5.5 70 240 130 260
20563121 2.5 25 35 5.5 80 350 220 350

Under-pressure shut-off springs (UPSO) Table H


Spring Characteristics Whu (bar)
Code d De Lo It 2012 2612
mm mm mm ( 120)
20560522 0.7 10 20 7 4 14
20560511 0.8 10 20 7 10 25
20560515 0.8 10 30 10 20 35
20560518 0.9 10 30 10 32 45

5
Dimensions (in mm)

180
132
42

Figure 2
Mod. 2010/2110/2210/2310/2610*
Weight 2 Kg

139
179
40

1/4 GAS

1 GAS
100

180
132
42

GA-0052.0-GB-02/03 - Copyright 2002, Actaris, All Rights Reserved. - Actaris reserves the right to change these specifications without prior notice.
Figure 3
Mod. 2011-2012/2111-2112/2311
2312/2611*-2612*
139

Weight 2.5 Kg
252

1/4 GAS

1 GAS
113

* Except for 2600 series:


- body length 130 mm;
100 120 - outlet diameter 11/2.

Information to be specified when


ordering:
- Regulator type code
- Minimum and maximum inlet
pressures
- Outlet pressure range
- Outlet pressure setting
- Maximum flow rate
OPCO setting*
UPCO setting*
* (if requested)

Actaris Gaszhlerbau GmbH


Hardeckstrasse 2
D-76185 Karlsruhe - Germany tel + 49-721 5981 0
For more information, www.actaris.com fax + 49-721 5981 189