Though the Document has been approved in CAT-I however, we are resubmitting it, as the
signals of Level Switch, Temp Element and Transmitter and Motorized valves have not
been included earlier.
Page 2 of 4
Project : (2x415MW) GAS POWER STATION, DADRI Purpose Category
Client : M/s. NTPC, DADRI I = Approved
Vendor : UNITECH MACHINES LIMITED I = For Information X II = Approved Subject to Comments
Package : REPLACEMENT OF PGB COOLERS BY PHE FOR NCPS-GAS A = For Approval III = Not Approved
UML Doc. No. : P317-I-409 IV = Approved For Information
Annunciatio
Signal Signal/
S. No. Tag No. Drive No. Location Description Scope of Signal Signal Source DI AI DO AO Remark
Form Contact Type
n IN OWS
43 PS-05 ACW Pump House Pressure Low at Common Suction Line of Cooling Water Pumps UML PS DI NO YES 1
Differential Pressure across Strainer-1 at suction of Cooling
44 DPS-01 - ACW Pump House UML DPS DI NO YES 1
Water Pumps High
Differential Pressure across Strainer-2 at suction of Cooling
45 DPS-02 - ACW Pump House UML DPS DI NO YES 1
Water Pumps High
46 PT-01 - ACW Pump House Pressure at discharge header of Cooling Water Pumps PT AI 4 to 20 mA YES 1
UML
47 PT-02 - ACW Pump House Pressure at discharge header of Cooling Water Pumps PT AI 4 to 20 mA YES 1
Temperature element with Transmitter mounted on cold DM
48 TT-01 - TT AI 4 to 20 mA YES 1
water outlet line of PHE-1.
Temperature element with Transmitter mounted on cold DM
49 TT-02 - UML TT AI 4 to 20 mA YES 1
DM Water Outlet Line water outlet line of PHE-2 .
near ACW Pump House Temperature element with Transmitter mounted on cold DM
50 TT-03 - TT AI 4 to 20 mA YES 1
water outlet line of PHE-3.
Temperature element with Transmitter mounted on cold DM
51 TT-04 - TT AI 4 to 20 mA YES 1
water outlet line of PHE-4.
Temperature element with Transmitter mounted on hot DM water
52 TT-05 - TT AI 4 to 20 mA YES 1
inlet line of PHE-1.
Temperature element with Transmitter mounted on hot DM water
53 TT-06 - UML TT AI 4 to 20 mA YES 1
DM Water Intlet Line inlet line of PHE-2 .
near ACW Pump House Temperature element with Transmitter mounted on hot DM water
54 TT-07 - TT AI 4 to 20 mA YES 1
inlet line of PHE-3.
Temperature element with Transmitter mounted on hot DM water
55 TT-08 - TT AI 4 to 20 mA YES 1
inlet line of PHE-4.
56 LT-01 Level Tranmsmitter mounted on Sump for Cooling Tower-1 * LT AI 4 to 20 mA YES 1 1
Near ACW Pump Temperature element withTranmsmitter mounted on Cooling
57 TT-09 Cooling Tower-1 UML TT Al 4 to 20 mA YES 1 1
House Tower-1 *
58 LS- 01 Level switch mounted on Sump for Cooling Tower-1 * 1
Page 3 of 4
Project : (2x415MW) GAS POWER STATION, DADRI Purpose Category
Client : M/s. NTPC, DADRI I = Approved
Vendor : UNITECH MACHINES LIMITED I = For Information X II = Approved Subject to Comments
Package : REPLACEMENT OF PGB COOLERS BY PHE FOR NCPS-GAS A = For Approval III = Not Approved
UML Doc. No. : P317-I-409 IV = Approved For Information
Annunciatio
Signal Signal/
S. No. Tag No. Drive No. Location Description Scope of Signal Signal Source DI AI DO AO Remark
Form Contact Type
n IN OWS
Common Discharge
65 PS-06 - Pressure at common discharge line of Cooling Towers High UML PS DI NO YES 1
Line of Cooling Towers
Total of A 39 16 16 6
B LT Switchgear Signals
3 I/CA-MCC Incomer-A ACW Pump House Incomer-A Breaker OFF status UML MCC DI NC 1
8 I/CB-MCC Incomer-B ACW Pump House Incomer-B Breaker OFF status UML MCC DI NC 1
13 B/C-MCC Buscoupler ACW Pump House BuscouplerBreaker OFF status UML MCC DI NC 1
Total of B 9 6
NOTE:
1.The I/O List of PLC System is Typical for both the modules of GT Cooling System.
2. Signals marked with "*" shall also be imterfaced with existing DDCMIS and necessary DOs / AOs for same have been considered.
MAIN SIGNALS(A+B) 48 16 22 6
SPARES(10% of DO/AI/AO/DI ) 5 2 3 1
TOTAL (MAIN SIGNALS + SPARES) 53 18 25 7
LEGENDS
PLC PLC PT Pressure Transmitter MOV Motorized Valve
MCC Motor Control Centre LT Level Transmitter
DPS Differential Pressure Switch TT Temp. Transmitter
LS Level Switch EPBS Emergensy Push Button Station
PS Pressure Switch